Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

PCD2.F2xxx Serial Interface Modules: Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

Manual

PCD2.F2xxx
serial interface modules

Document 27-649 │ Version ENG02 │ 2018-08-15


Saia-Burgess Controls AG Contents
Inhalt

0 Contents
0 Contents
0
0.1 Document versions ............................................................................................ 0-2
0.2 Brand names and trademarks  ........................................................................... 0-2

1 PCD2.F2xxx serial interface modules


1.1 I/O-Slot Modules overview ................................................................................. 1-1
1.1.1 Serial interface modules PCD7.F1xxS ............................................................ 1-1
1.1.2 Block diagram .................................................................................................. 1-2
1.2 General info on the PCD2.F2xxx ....................................................................... 1-3
1.3 Module description ............................................................................................. 1-4
1.3.1 Connection terminals ....................................................................................... 1-5
1.3.2 LEDs  ................................................................................................................ 1-5
1.3.3 Technical data ................................................................................................. 1-6
1.3.4 Restrictions  ...................................................................................................... 1-7
1.4 Module variants .................................................................................................. 1-8
1.4.1 RS-422/485 on module - PCD2.F2100 port x.0 .............................................. 1-8
1.4.2 RS-232 on module - PCD2.F2210 Port x.0 (for modem) ................................ 1-10
1.4.3 Belimo MP-Bus on module - PCD2.F2810 port x.0 ......................................... 1-11
1.5 PCD7.F1xxS serial interface modules for port x.1 ............................................. 1-12
1.5.1 PCD7.F1xxS modules overview ...................................................................... 1-12
1.5.2 RS-485/RS-422 - PCD7.F110S serial interface module .................................. 1-13
1.5.3 RS-232 up to 115 kbit/s, suitable for modem connection
PCD7.F121S serial interface module .............................................................. 1-14
1.5.4 RS-485 galv. isolation - PCD7.F150S serial interface module ........................ 1-15
1.5.5 Belimo MP-Bus PCD7.F180S - serial interface module .................................. 1-16
1.5.6 PCD7.Fxxx - Overview of older interface modules
(no longer available) ........................................................................................ 1-17

2 PCD2 slots are available on...


2.1 PCD1.M22xx-C15 
.............................................................................................. 2-1
2.2 PCD1.M21xx 
...................................................................................................... 2-2
2.3 PCD2.M4xxx 
...................................................................................................... 2-3
2.4 PCD2.M5xxx 
...................................................................................................... 2-4

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 0-1


Saia-Burgess Controls AG Contents
Dokumenthistorie

0.1 Document versions


0
Version Date Updated Comments
ENG01 2018-02-08 2018-02-08 Translated from the german version
ENG02 2018-08-15 - Revised, overview improved, Chapter 2

0.2 Brand names and trademarks


Saia PCD® and Saia PG5®
are registered trademarks of Saia-Burgess Controls AG.

Technical changes based on the current technical state of the art

Saia-Burgess Controls AG, 2017. ® All rights reserved.

Published in Switzerland

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 0-2


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Modules overview

1 PCD2.F2xxx serial interface modules

1.1 I/O-Slot Modules overview


1
Serial communications modules with two serial interface ports
PCD2.F2100
Port x.0: RS-422 / RS-485
Port x.1: slot for PCD7.F1xxS module

PCD2.F2210
Port x.0: RS-232
Port x.1: slot for PCD7.F1xxS module

PCD2.F2810
Port x.0: Belimo MP-Bus
Port x.1: slot for PCD7.F1xxS module

1.1.1 Serial interface modules PCD7.F1xxS

Serial interface modules PCD7.F1xxS to port x.1 insertion of PCD2.F2xxx modules

PCD7.F110S RS-422 / RS-485 with connectable terminating


resistors

PCD7.F121S RS-232

PCD7.F150S RS-485 galv. isolation and with connectable termi-


nating resistors

PCD7.F180S Belimo MP-Bus

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-1


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
General info on the PCD2.F2xxx

1.1.2 Block diagram

1
PCD
PCD2.F2xxx
I/O Bus
CPU Power supply
Interface
I/O Bus 3.3 V Port x.0
(CPLD)

Clamp connector
serial line
driver/receiver

Port x.0
RS-232 or
I/O Port RS-422/485
equipped
Microcontroller
ARM7
UART 1
SPI SPI (Slave) Port x.1

Clamp connector
Bus Interface serial line
interface

Port x.1
Interrupt Interrupt Slot for one
Input Output module
UART 2
PCD7.F1xxS

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-2


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
PCD2 slots are available on...

1.2 General info on the PCD2.F2xxx


System properties of the PCD2.F2xxx modules
1
One plug-in socket (orange) for each interface. The first port named Port # 0 is
factory-fitted with a fixed serial port depending on your choice.

The second interface with the designation Port # 1 allows free loading with a
PCD7.F1xxS module of your choice or as a reserve for later assembly.

The following points must be noted when using the PCD2.F2xxx interface
modules:

●● Each Saia PCD® system has a limitation on the maximum number of PCD2.
F2xxx modules. For an overview, see chapter 2 in this manual.

●● The PCD systems have a high-performance processor that processes the


application and the serial interfaces. The appropriate CPU capacity is required
to process the interface modules. Please note the following when defining the
maximum communication capacity per PCD2 system:

●● The communication volume is determined by the peripheral devices connect-


ed. This may be the case if, for example, a PCD2 is used as an S-Bus slave
station. If a PCD2 control unit is bombarded with a heavy telegram transfer
at high baud rates, there will be little CPU capacity remaining to process the
actual application. The following rules apply here: the use of 8 interfaces with
9.6 kbps requires approx. 50% of the CPU capacity. Two 57.6 kbps interfac-
es require approx. 50% of the CPU capacity. Two 115 kbps interfaces require
approx. 60% of the CPU capacity.

●● If the PCD is the initiator of the communication, the communication volume


and therefore the communication capacity is defined by the user program
in the PCD (the PCD is used as the master station). Theoretically, all inter-
faces can be operated with a maximum baud rate of 115 kbps. The effective
data throughput will however depend on the user program and the number
of interfaces and can be correspondingly low. The essential factor is that the
connected peripheral devices can work with the selected configuration and
communication capacity.

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-3


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
PCD2 slots are available on...

1.3 Module description


The PCD2.F2xxx communications modules are designed for the PCD2.Mxxxx sys-
tems. Each module has two serial ports, a fixed interface and a second which can 1
be equipped with one of the PCD7.F1xxS modules if required.

Serial communications modules with two serial


interface ports:

PCD2.F2100
Port x.0: RS-422 / RS-485 (equipped)
Port x.1: slot for PCD7.F1xxS module

PCD2.F2210
Port x.0: RS-232 (equipped)
Port x.1: slot for PCD7.F1xxS module

PCD2.F2810
Port x.0: Belimo MP-Bus (equipped)
Port x.1: slot for PCD7.F1xxS module

Port x.1 still Port x.0 fix,


without PCD7. depending on the
F1xxS module PCD2.F2xxx Example of one of the PCD7.F1xxS modules
module selected

Examples with attached PCD2.F_ module on Portx.1:


with serie PCD2.FxxS with old serie PCD2.FxxS

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-4


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
PCD2 slots are available on...

1.3.1 Connection terminals


RS-232 RS-422 RS-485
0 PGND TxD 1 0 PGND Tx 1 0 PGND Rx-Tx 1 1
2 RxD RTS 3 2 /Tx Rx 3 2 /Rx-/Tx 3
4 CTS PGND 5 4 /Rx PGND 5 4 PGND 5
6 DTR DSR 7 6 RTS /RTS 7 6 7
8 COM DCD 9 8 CTS /CTS 9 8 (SGD) 9
Terminal to port Terminal to port
x.1 x.0
10 pin (2x5) 10 pin (2x5) TTY (CL) Belimo MP-Bus
0 PGND TS 1 0 PGND Acom 1
2 RS TA 3 2 MST IN 3
4 RA PGND 5 4 PGND 5
6 TC RC 7 6 7
8 TG RG 9 8 9

Type K terminal block


(2x item no. 4 405 5048 0 are also supplied)
Each serial port has its own individual 10 pin spring-loaded terminal block.
Two type K spring-loaded terminal blocks are fitted on the PCD2.F2xxx module,
the right for port x.0 and the left for port x.1.

Maximum wire gauge: 1.0 mm2 AWG 18

1.3.2 LEDs

LED TxD Transmission data detection


LED RxD Data reception detection
LED status The LED status indicates the status of
< LED Status x.1

< LED Status x.0

the serial ports.


< LED RxD x.1

< LED RxD x.0


< LED TxD x.1

< LED TxD x.0

‘green’ means that the port is working


properly
green red Status of the serial port
- 100% F2xxx not operating
25% 75% F2xxx start procedure
F2xxx operating, but
50% 50% no communication with
CPU
F2xxx operating,
75% 25%
channel closed
F2xxx operating,
90% 10%
channel open with error
F2xxx operating,
100% -
channel open OK

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-5


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
PCD2 slots are available on...

1.3.3 Technical data

Communication modes supported:


1
MC0 character mode without automatic handshaking
MC1 character mode with RTS/CTS handshaking
MC2 character mode with Xon/Xoff protocol
MC4 character mode for RS-485 interface
MC5 similar to MC4 with rapid switching between sending and receiving

SM1 S-Bus master, parity mode


SM2 S-Bus master, data mode

SS1 S-Bus slave, parity mode


SS2 S-Bus slave, data mode

GS1 S-Bus gateway slave, parity mode


GS2 S-Bus gateway slave, data mode

GM S-Bus gateway master

→ Gateway always via the PCD2.

Baud rates supported (bit/s):

1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200

Current consumption
+5 V-Bus V+
Basis module Port x.1 config. [I in mA] [I in mA]
none 110 0
PCD7.F110S 150 0
PCD7.F121S 125 0
PCD2.F2100
PCD7.F130 190 22
PCD7.F150S 240 0
PCD7.F180S 125 15
none 90 0
PCD7.F110S 130 0
PCD7.F121S 105 0
PCD2.F2210
PCD7.F130 120 22
PCD7.F150S 225 0
PCD7.F180S 105 15
none 90 15
PCD7.F110S 130 15
PCD7.F121S 105 15
PCD2.F2810
PCD7.F130 115 37
PCD7.F150S 225 15
PCD7.F180S 105 30

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-6


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Module description

1.3.4 Restrictions

The PCD2.F2xxx modules for the PCD2 systems enable users to create up to 8
additional serial interfaces. Note: every additional interface uses CPU capacity. 1
The use of these 8 ports depends on the type of communication, the baud rate
required and the volume of the data transfer.

Additional important factors are:

●● Communication on the PCD, i.e. Profi-S-Net, Ether-S-Net, USB


●● Use of the web server
●● Data transfer from the CPU to the memory
●● User program in the PCD

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-7


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Module description

1.4 Module variants


1.4.1 RS-422/485 on module - PCD2.F2100 port x.0
1
The PCD2.F2100 module contains two different interface types on port x.0, RS-
422 with RTS/CTS and RS-485 (electrically connected). The line terminator is
integrated into the module and can be connected to the module via a switch.

Switch for
network terminator
port x.0 (RS-485)

RS-422 connection

Port x.0
RS-422
0 PGND Tx 1
2 /Tx Rx 3
10 pin spring-loaded terminal block
4 /Rx PGND 5
6 RTS /RTS 7
8 CTS /CTS 9

The line terminator in RS-422 mode occurs at 150 Ω in all cases on the
PCD2.F2100 module.

Terminal Peripherie-
RS-422 device
Pin
PGND 10 PGND
TX 11 TX
/TX 12 /TX
RX 13 RX
/RX 14 /RX
PGND 15 SGND
RTS 16 RTS
/RTS 17 /RTS
CTS 18 CTS
/CTS 19 /CTS

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-8


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Module description

RS 485 connection

Port x.0
RS-485 1
0 PGND Rx-Tx 1
2 /Rx-/Tx 3
4 PGND 5
10 pin spring-loaded terminal block
6 7
8 (SGD) 9

(Electrically connected RS-485 interface)

Peripherie-
Terminal RS-485 device
GND
x0 PGND PGND
RS-485
x1 RX - TX RX - TX
RS-485
x2 /RX - /TX /RX - /TX

Line terminator:

First station Middle stations End station

+5 V +5 V
n /n n /n
Pull up
330 Ohm
/RX - /TX
28 /n
Termination
Resistor Bus RS-485
150 Ohm RX - TX
29 n
Pull down
330 Ohm Segment length max. 1200 m
max. 32 stations

The line terminator for port x.0 is integrated into the module and can be activated
using a switch on the module. In addition to the switch, the following indications
appear on the LP: ‘O’ for OPEN and ‘C’ for CLOSED.

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-9


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Module description

1.4.2 RS-232 on module - PCD2.F2210 Port x.0 (for modem)

The PCD2.F2210 module has a full RS-232 interface on port x.0 an. This port is
designed in particular for all modem connections, including the RTS/CTS, DTR/ 1
DSR and DCD.

RS-232 connection

Port x.0
RS-232
0 PGND TxD 1
2 RxD RTS 3 10 pin spring-loaded terminal
4 CTS PGND 5 block
6 DTR DSR 7
8 COM DCD 9

RS-232 connection to DTE RS-232 connection to DCE


Peripherie External modem
cable cable
device (DTE) (ETCD) DCE
0 PGND PGND 0 PGND PGND
1 TXD TX 1 TXD TX
2 RXD RX 2 RXD RX
3 RTS RTS 3 RTS RTS
4 CTS CTS 4 CTS CTS
5 PGND SGND 5 PGND SGND
6 DTR DTR 6 DTR DTR
7 DSR DSR 7 DSR DSR
8 Reserve 8 Reserve
9 DCD DCD 9 DCD DCD

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-10


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Module variants

1.4.3 Belimo MP-Bus on module - PCD2.F2810 port x.0

The PCD2.F2810 module has a full Belimo MP-Bus interface on port x.0 an. An
MP-Bus with up to 8 drives and sensors can therefore be connected to port x.0. 1

Belimo connection

Port x.0
Belimo MP-Bus
0 PGND Acom 1
2 MST IN 3 10 pin
4 PGND 5 spring-loaded terminal block
6 7
8 9

MP-Bus cabling

0 PGND Earth connection, MP line


1 MP Multi-point
The MP-Bus is the Belimo master slave bus. Up to 8
slaves can be connected to a master device.
These are:
-- MFT(2) flap drives
-- MFT(2) valve drives
-- MFT fire damper drives
-- VAV NMV-D2M compact controller
2 ‘MFT’ MFT programming unit (internal MP-Bus)
3 ‘IN’ detection of MFT programming unit
(input 10 kΩ, Z5V1)
5 PGND Earth connection, MFT programming unit

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-11


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Module variants

1.5 PCD7.F1xxS serial interface modules for port x.1


1.5.1 PCD7.F1xxS modules overview
1
PCD7.F1xxS serial interface modules will be used, among others, for the insertion
of port x.1 of the PCD2.F2xxx modules. A second interface can be mounted on
each CD2.F2xxx module depending on the purpose of the application.

PCD7.F110S RS-422 / RS-485 with connectable terminating


resistors

PCD7.F121S RS-232

PCD7.F150S RS-485 galv. isolation and with connectable


terminating resistors

PCD7.F180S Belimo MP-Bus

PCD7.F1xxS modules for port x.1

Port x.1

0 1
2 3 10 pin
4 5 spring-loaded terminal block
6 7
8 9

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-12


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Module variants

1.5.2 RS-485/RS-422 - PCD7.F110S serial interface module

The terminating connectors can be linked using slide switches (CLOSED) or


isolated (OPEN). 1
PCD7.F110S RS-485 terminator
Slider Open not terminated
(factory setting)
O
C
1 2

Slider Closed terminated

O
C
1 2

RS-422 connection

Port x.1
RS-422
0 PGND Tx 1
2 /Tx Rx 3
4 /Rx PGND 5
10 pin spring-loaded terminal block
6 RTS /RTS 7
8 CTS /CTS 9

The line terminator in RS-422 mode occurs at 150 Ω in all cases on the PCD2.
F2100 module.

Terminal Peripherie-
RS-422 device
Pin
PGND 10 PGND
TX 11 TX
/TX 12 /TX
RX 13 RX
/RX 14 /RX
PGND 15 SGND
RTS 16 RTS
/RTS 17 /RTS
CTS 18 CTS
/CTS 19 /CTS

RS 485 connection
Port x.1
RS-485
0 PGND Rx-Tx 1
2 /Rx-/Tx 3
4 PGND 5
10 pin spring-loaded terminal block
6 7
8 (SGD) 9

(Electrically connected RS-485 interface)

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-13


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Module variants

Peripherie-
Terminal RS-485 device
GND
x0 PGND PGND
x1 RX - TX
RS-485
RS-485
RX - TX 1
x2 /RX - /TX /RX - /TX

More details are available in the manual 26-740 “Installation components for RS-
485 networks”.

1.5.3 RS-232 up to 115 kbit/s, suitable for modem connection


PCD7.F121S serial interface module

PCD7.F121S

RS-232 connection

Port x.1
RS-485
0 PGND TxD 1
2 RxD RTS 3
4 CTS PGND 5
10 pin spring-loaded terminal block
6 DTR DSR 7
8 COM DCD 9

RS-232 connection to DTE RS-232 connection to DCE


Peripherie External modem
cable cable
device (DTE) (ETCD) DCE

0 PGND PGND 0 PGND PGND


1 TXD TX 1 TXD TX
2 RXD RX
2 RXD RX
3 RTS RTS
3 RTS RTS
4 CTS CTS
4 CTS CTS 5 PGND SGND
5 PGND SGND 6 DTR DTR
6 DTR DTR 7 DSR DSR
7 DSR DSR 8 Reserve
8 Reserve 9 DCD DCD
9 DCD DCD

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-14


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Module variants

1.5.4 RS-485 galv. isolation - PCD7.F150S serial interface module

Electrical isolation is achieved using three optical couplers and a DC/DC converter.
The data signals are protected against excess voltages by a suppressor diode 1
(10 V). The terminating connectors can be linked using slide switches (CLOSED)
or isolated (OPEN).

PCD7.F150S RS-485 terminator


Closed terminated

ON
1
2
Slider

Open not terminated


(factory setting)

ON
1
2

Slider

RS 485 connection
Port x.1
RS-485
0 PGND Rx-Tx 1
2 /Rx-/Tx 3
4 PGND 5
10 pin spring-loaded terminal block
6 7
8 (SGD) 9

Peripherie-
Terminal RS-485 device
GND
x0 PGND PGND
RS-485
x1 RX - TX RX - TX
RS-485
x2 /RX - /TX /RX - /TX

Line terminator:

First station Middle stations End station

+5 V +5 V
n /n n /n
Pull up
330 Ohm
/RX - /TX
28 /n
Termination
Resistor Bus RS-485
150 Ohm RX - TX
29 n
Pull down
330 Ohm Segment length max. 1200 m
max. 32 stations

The line terminator for port x.1 is integrated into the module and can be activated
using a switch on the module. In addition to the switch, the following indications
appear on the LP: ‘O’ for OPEN and ‘C’ for CLOSED.

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-15


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Module variants

When using this module, the permitted ambient temperature for the control unit is
reduced by 5°C.
1
More details are available in the manual 26-740 “Installation components
for RS-485 networks”.

1.5.5 Belimo MP-Bus PCD7.F180S - serial interface module

Up to a maximum of 8 actuating drives and sensors can be connected.

PCD7.F180S

Belimo connection

Port x.1
Belimo MP-Bus
0 PGND MP 1
2 ‘MFT’ ‘IN’ 3
4 PGND 5
10 pin spring-loaded terminal block
6 7
8 (SGD) 9

MP-Bus cabling

0 PGND Earth connection, MP line


1 MP Multi-point
The MP-Bus is the Belimo master slave
bus. Up to 8 slaves can be connected to
a master device.
These are:
-- MFT(2) flap drives
-- MFT(2) valve drives
-- MFT fire damper drives
-- VAV NMV-D2M compact controller
2 ‘MFT’ MFT programming unit (internal MP-Bus)
3 ‘IN’ detection of MFT programming unit
(input 10 kΩ, Z5V1)
5 PGND Earth connection, MFT programming unit

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-16


Saia-Burgess Controls AG PCD2.F2xxx serial interface modules
Module variants

1.5.6 PCD7.Fxxx - Overview of older interface modules


(no longer available)

The older serial interface modules PCD7.F1xx (without «S» at the end) are no 1
longer available.
Except PCD7.F130 current loop 20 mA

For completeness they are still listed here.

Their functions are the same as with the newer models with the “S” in the article
number at the end.

PCD7.F110 Serial interface module RS-422 / RS-485


PCD7.F121 Serial interface module RS-232, for modem connection
PCD7.F130 Serial interface module, current loop 20 mA
PCD7.F150 Serial interface module, RS-485, electrically isolated
PCD7.F180 Serial interface module for Belimo MP bus, for max. 8 actuators
and sensors

An equipped PCD2.F2xxx looks like this:

Example of an older module

0 1
2 3
4 5
6 7
8 9

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 1-17


Saia-Burgess Controls AG PCD2 slots are available on...
PCD1.M22xx-C15

2 PCD2 slots are available on...


This chapter indicates which PCD controllers can be used with which PCD2.F2xxx
modules.

2
2.1 PCD1.M22xx-C15
A maximum of two PCD2.F2xxx modules can be used on the two slots. The slots
can be accessed with the following port addresses via communication FBoxes:

Slot 0 with the PCD2.F2xxx


module
-- Port 100 for the 0.0 port
-- Port 101 for the 0.1 port
(with PCD7.F1xxx)

Slot 1 with the PCD2.F2xxx


module
-- Port 110 for the 1.0 port
-- Port 111 for the 1.1 port
(with PCD7.F1xxx)

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 2-1


Saia-Burgess Controls AG PCD2 slots are available on...
PCD1.M21xx

2.2 PCD1.M21xx
Slots IO0 and IO1 on the PCD1.M2_ can also be equipped with the PCD2.F2xxx
interface modules. The slots can be accessed with the following port addresses
via communication FBoxes (or AWL commands):
2

PCD1.M2120 /PCD1.M2160 PCD1.M2110-Room


Module Module port Module Module Module port Module
slot address terminal block slot address terminal block
100 Port x.0 100 Port x.0
0 0
101 Port x.1 101 Port x.1
110 Port x.0
1
111 Port x.1

PCD7.F1xxS PCD7.F1xxS PCD7.F1xxS

PCD2.F2100 PCD2.F2100 PCD2.F2100

0 1 0 W-
Modul

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 2-2


Saia-Burgess Controls AG PCD2 slots are available on...
PCD2.M4xxx

2.3 PCD2.M4xxx
Die PCD2.M4xxx kann die Module PCD2.F2xxx in den E/A-Slots 0…3 bzw. 0 … 1
aufnehmen. Wie in der folgenden Abbildung gezeigt, sind die E/A-Slots folgender-
massen bezeichnet:
2
PCD2.M4560 PCD4.M4160
Module Module port Module Module Module port Module
slot address terminal block slot address terminal block
100 Port x.0 100 Port x.0
0 101 Port x.1 0 101 Port x.1
110 Port x.0 110 Port x.0
1 111 Port x.1 1 111 Port x.1
120 Port x.0
2 121 Port x.1
130 Port x.0
3 131 Port x.1

PCD7.F1xxS PCD7.F1xxS PCD7.F1xxS PCD7.F1xxS

PCD2.F2100 PCD2.F2100 PCD2.F2100 PCD2.F2100

0 1 0 1

3 2 3 2

PCD2.F2100 PCD2.F2100

PCD7.F1xxS PCD7.F1xxS

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 2-3


Saia-Burgess Controls AG PCD2 slots are available on...
PCD2.M5xxx

2.4 PCD2.M5xxx
The PCD2.F2xxx modules are intended for inclusion in the I/O slot 0...3 on a
PCD2.Mxxxx. As shown in the diagram, the I/O slots are labelled as follows:

Module slot
Module port Module terminal 2
address block
100 Port x.0
0
101 Port x.1
110 Port x.0
1
111 Port x.1
120 Port x.0
2
121 Port x.1
130 Port x.0
3
131 Port x.1

PCD7.F1xxS PCD7.F1xxS PCD7.F1xxS PCD7.F1xxS

PCD2.F2100 PCD2.F2100 PCD2.F2100 PCD2.F2100

0 1 2 3

7 6 5 4

If a PCD2.F2xxx module is connected to I/O slot 0, port 1 cannot be used. Instead,


the PCD2.F2xxx module is connected to the two ports 100 and 101.

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 2-4


Saia-Burgess Controls AG Appendix
Icons

A Appendix

A.1 Icons

This symbol indicates that additional information on this topic exists in this manual,
a different manual or technical documentation. There are no direct links to these A
documents.

This symbol indicates instructions that require strict compliance.

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 A-1


Saia-Burgess Controls AG Appendix
Contact details

A.2 Contact details


Saia-Burgess Controls AG
Bahnhofstrasse 18
3280 Murten, Switzerland
A
Head office telephone ............. +41 26 580 30 00
SBC Support telephone ........... +41 26 580 31 00
Fax........................................... +41 26 580 34 99

Email support: ......................... support@saia-pcd.com


Support website: ..................... www.sbc-support.com
SBC website: .......................... www.saia-pcd.com

International agencies and SBC subsidiaries: www.saia-pcd.com/contact

Postal address for customers to return products in Switzerland:

Saia-Burgess Controls AG
After sales service
Bahnhofstrasse 18
3280 Murten, Switzerland

Manual PCD2.F2xxx serial interface modules │ Document 27-649 ENG02 │ 2018-08-15 A-2

You might also like