PCD2.F2xxx Serial Interface Modules: Manual
PCD2.F2xxx Serial Interface Modules: Manual
PCD2.F2xxx Serial Interface Modules: Manual
PCD2.F2xxx
serial interface modules
0 Contents
0 Contents
0
0.1 Document versions ............................................................................................ 0-2
0.2 Brand names and trademarks ........................................................................... 0-2
Published in Switzerland
PCD2.F2210
Port x.0: RS-232
Port x.1: slot for PCD7.F1xxS module
PCD2.F2810
Port x.0: Belimo MP-Bus
Port x.1: slot for PCD7.F1xxS module
PCD7.F121S RS-232
1
PCD
PCD2.F2xxx
I/O Bus
CPU Power supply
Interface
I/O Bus 3.3 V Port x.0
(CPLD)
Clamp connector
serial line
driver/receiver
Port x.0
RS-232 or
I/O Port RS-422/485
equipped
Microcontroller
ARM7
UART 1
SPI SPI (Slave) Port x.1
Clamp connector
Bus Interface serial line
interface
Port x.1
Interrupt Interrupt Slot for one
Input Output module
UART 2
PCD7.F1xxS
The second interface with the designation Port # 1 allows free loading with a
PCD7.F1xxS module of your choice or as a reserve for later assembly.
The following points must be noted when using the PCD2.F2xxx interface
modules:
●● Each Saia PCD® system has a limitation on the maximum number of PCD2.
F2xxx modules. For an overview, see chapter 2 in this manual.
PCD2.F2100
Port x.0: RS-422 / RS-485 (equipped)
Port x.1: slot for PCD7.F1xxS module
PCD2.F2210
Port x.0: RS-232 (equipped)
Port x.1: slot for PCD7.F1xxS module
PCD2.F2810
Port x.0: Belimo MP-Bus (equipped)
Port x.1: slot for PCD7.F1xxS module
1.3.2 LEDs
Current consumption
+5 V-Bus V+
Basis module Port x.1 config. [I in mA] [I in mA]
none 110 0
PCD7.F110S 150 0
PCD7.F121S 125 0
PCD2.F2100
PCD7.F130 190 22
PCD7.F150S 240 0
PCD7.F180S 125 15
none 90 0
PCD7.F110S 130 0
PCD7.F121S 105 0
PCD2.F2210
PCD7.F130 120 22
PCD7.F150S 225 0
PCD7.F180S 105 15
none 90 15
PCD7.F110S 130 15
PCD7.F121S 105 15
PCD2.F2810
PCD7.F130 115 37
PCD7.F150S 225 15
PCD7.F180S 105 30
1.3.4 Restrictions
The PCD2.F2xxx modules for the PCD2 systems enable users to create up to 8
additional serial interfaces. Note: every additional interface uses CPU capacity. 1
The use of these 8 ports depends on the type of communication, the baud rate
required and the volume of the data transfer.
Switch for
network terminator
port x.0 (RS-485)
RS-422 connection
Port x.0
RS-422
0 PGND Tx 1
2 /Tx Rx 3
10 pin spring-loaded terminal block
4 /Rx PGND 5
6 RTS /RTS 7
8 CTS /CTS 9
The line terminator in RS-422 mode occurs at 150 Ω in all cases on the
PCD2.F2100 module.
Terminal Peripherie-
RS-422 device
Pin
PGND 10 PGND
TX 11 TX
/TX 12 /TX
RX 13 RX
/RX 14 /RX
PGND 15 SGND
RTS 16 RTS
/RTS 17 /RTS
CTS 18 CTS
/CTS 19 /CTS
RS 485 connection
Port x.0
RS-485 1
0 PGND Rx-Tx 1
2 /Rx-/Tx 3
4 PGND 5
10 pin spring-loaded terminal block
6 7
8 (SGD) 9
Peripherie-
Terminal RS-485 device
GND
x0 PGND PGND
RS-485
x1 RX - TX RX - TX
RS-485
x2 /RX - /TX /RX - /TX
Line terminator:
+5 V +5 V
n /n n /n
Pull up
330 Ohm
/RX - /TX
28 /n
Termination
Resistor Bus RS-485
150 Ohm RX - TX
29 n
Pull down
330 Ohm Segment length max. 1200 m
max. 32 stations
The line terminator for port x.0 is integrated into the module and can be activated
using a switch on the module. In addition to the switch, the following indications
appear on the LP: ‘O’ for OPEN and ‘C’ for CLOSED.
The PCD2.F2210 module has a full RS-232 interface on port x.0 an. This port is
designed in particular for all modem connections, including the RTS/CTS, DTR/ 1
DSR and DCD.
RS-232 connection
Port x.0
RS-232
0 PGND TxD 1
2 RxD RTS 3 10 pin spring-loaded terminal
4 CTS PGND 5 block
6 DTR DSR 7
8 COM DCD 9
The PCD2.F2810 module has a full Belimo MP-Bus interface on port x.0 an. An
MP-Bus with up to 8 drives and sensors can therefore be connected to port x.0. 1
Belimo connection
Port x.0
Belimo MP-Bus
0 PGND Acom 1
2 MST IN 3 10 pin
4 PGND 5 spring-loaded terminal block
6 7
8 9
MP-Bus cabling
PCD7.F121S RS-232
Port x.1
0 1
2 3 10 pin
4 5 spring-loaded terminal block
6 7
8 9
O
C
1 2
RS-422 connection
Port x.1
RS-422
0 PGND Tx 1
2 /Tx Rx 3
4 /Rx PGND 5
10 pin spring-loaded terminal block
6 RTS /RTS 7
8 CTS /CTS 9
The line terminator in RS-422 mode occurs at 150 Ω in all cases on the PCD2.
F2100 module.
Terminal Peripherie-
RS-422 device
Pin
PGND 10 PGND
TX 11 TX
/TX 12 /TX
RX 13 RX
/RX 14 /RX
PGND 15 SGND
RTS 16 RTS
/RTS 17 /RTS
CTS 18 CTS
/CTS 19 /CTS
RS 485 connection
Port x.1
RS-485
0 PGND Rx-Tx 1
2 /Rx-/Tx 3
4 PGND 5
10 pin spring-loaded terminal block
6 7
8 (SGD) 9
Peripherie-
Terminal RS-485 device
GND
x0 PGND PGND
x1 RX - TX
RS-485
RS-485
RX - TX 1
x2 /RX - /TX /RX - /TX
More details are available in the manual 26-740 “Installation components for RS-
485 networks”.
PCD7.F121S
RS-232 connection
Port x.1
RS-485
0 PGND TxD 1
2 RxD RTS 3
4 CTS PGND 5
10 pin spring-loaded terminal block
6 DTR DSR 7
8 COM DCD 9
Electrical isolation is achieved using three optical couplers and a DC/DC converter.
The data signals are protected against excess voltages by a suppressor diode 1
(10 V). The terminating connectors can be linked using slide switches (CLOSED)
or isolated (OPEN).
ON
1
2
Slider
ON
1
2
Slider
RS 485 connection
Port x.1
RS-485
0 PGND Rx-Tx 1
2 /Rx-/Tx 3
4 PGND 5
10 pin spring-loaded terminal block
6 7
8 (SGD) 9
Peripherie-
Terminal RS-485 device
GND
x0 PGND PGND
RS-485
x1 RX - TX RX - TX
RS-485
x2 /RX - /TX /RX - /TX
Line terminator:
+5 V +5 V
n /n n /n
Pull up
330 Ohm
/RX - /TX
28 /n
Termination
Resistor Bus RS-485
150 Ohm RX - TX
29 n
Pull down
330 Ohm Segment length max. 1200 m
max. 32 stations
The line terminator for port x.1 is integrated into the module and can be activated
using a switch on the module. In addition to the switch, the following indications
appear on the LP: ‘O’ for OPEN and ‘C’ for CLOSED.
When using this module, the permitted ambient temperature for the control unit is
reduced by 5°C.
1
More details are available in the manual 26-740 “Installation components
for RS-485 networks”.
PCD7.F180S
Belimo connection
Port x.1
Belimo MP-Bus
0 PGND MP 1
2 ‘MFT’ ‘IN’ 3
4 PGND 5
10 pin spring-loaded terminal block
6 7
8 (SGD) 9
MP-Bus cabling
The older serial interface modules PCD7.F1xx (without «S» at the end) are no 1
longer available.
Except PCD7.F130 current loop 20 mA
Their functions are the same as with the newer models with the “S” in the article
number at the end.
0 1
2 3
4 5
6 7
8 9
2
2.1 PCD1.M22xx-C15
A maximum of two PCD2.F2xxx modules can be used on the two slots. The slots
can be accessed with the following port addresses via communication FBoxes:
2.2 PCD1.M21xx
Slots IO0 and IO1 on the PCD1.M2_ can also be equipped with the PCD2.F2xxx
interface modules. The slots can be accessed with the following port addresses
via communication FBoxes (or AWL commands):
2
0 1 0 W-
Modul
2.3 PCD2.M4xxx
Die PCD2.M4xxx kann die Module PCD2.F2xxx in den E/A-Slots 0…3 bzw. 0 … 1
aufnehmen. Wie in der folgenden Abbildung gezeigt, sind die E/A-Slots folgender-
massen bezeichnet:
2
PCD2.M4560 PCD4.M4160
Module Module port Module Module Module port Module
slot address terminal block slot address terminal block
100 Port x.0 100 Port x.0
0 101 Port x.1 0 101 Port x.1
110 Port x.0 110 Port x.0
1 111 Port x.1 1 111 Port x.1
120 Port x.0
2 121 Port x.1
130 Port x.0
3 131 Port x.1
0 1 0 1
3 2 3 2
PCD2.F2100 PCD2.F2100
PCD7.F1xxS PCD7.F1xxS
2.4 PCD2.M5xxx
The PCD2.F2xxx modules are intended for inclusion in the I/O slot 0...3 on a
PCD2.Mxxxx. As shown in the diagram, the I/O slots are labelled as follows:
Module slot
Module port Module terminal 2
address block
100 Port x.0
0
101 Port x.1
110 Port x.0
1
111 Port x.1
120 Port x.0
2
121 Port x.1
130 Port x.0
3
131 Port x.1
0 1 2 3
7 6 5 4
A Appendix
A.1 Icons
This symbol indicates that additional information on this topic exists in this manual,
a different manual or technical documentation. There are no direct links to these A
documents.
Saia-Burgess Controls AG
After sales service
Bahnhofstrasse 18
3280 Murten, Switzerland