Instruction Manual: Operates With ISO9001 Certified Quality System
Instruction Manual: Operates With ISO9001 Certified Quality System
Instruction Manual: Operates With ISO9001 Certified Quality System
INSTRUCTION MANUAL
VRT200
1MN0046 REV. 0
TECSYSTEM S.r.l.
20094 Corsico (MI)
Tel.: +39-024581861
Fax: +39-0248600783
R. 1.4 07/11/16
ENGLISH
“Translations of the original instructions”
First of all we wish to thank you for choosing to use a TECSYSTEM product and recommend you read this instruction
manual carefully: You will understand the use of the equipment and therefore be able to take advantage of all its
functions.
ATTENTION! THIS MANUAL IS VALID AND COMPLETE FOR THE UNIT VRT200
CONTENTS
PAGE
1) SAFETY REQUIREMENTS ………………………………….. 3
2) ACCESSORIES ………………………………….. 4
5) INSTALLATION ………………………………….. 8
• OPERATION ………………………………….. —
7) PROGRAMMING ………………………………….. 11
9) TROUBLESHOOTING ………………………………….. —
2 VRT200
SAFETY REQUIREMENTS
ATTENTION:
Read the manual carefully before starting to use the control unit. Keep the instructions for future reference.
Do not open the device, touching any internal components can cause electric shock. Contact with 230 Volts
AC can be fatal. To reduce the risk of electric shock, do not dismantle the back of the device for any reason. Moreover
its opening would void the warranty.
Before connecting the device to the power supply, make sure that all the connections are correct. Always
disconnect the unit from the supply before any cabling modification.
Failure to comply with these instructions can cause damages, fires or electric shock, and possible serious injuries!
POWER SUPPLY
CLEANING
Disconnect the power cable before cleaning the control unit, use a dry cloth to dust it, without any solvent or detergents, and
compressed air.
OBJECTS
Never insert any objects into the cracks of the control unit. If this happens, disconnect the control unit and
contact an engineer.
ACCESSORIES
The use of non-original accessories or spare parts might damage the unit and endanger users' safety. In the event of faults,
contact technical service.
LOCATION
Install the control unit indoors, in a place protected from water splashes and sun rays. Do not place near heat sources
exceeding the parameters stated in this manual. Position on a stable surface, far from any possible vibrations. Position the
unit as far as possible from any intense magnetic fields.
REPAIRS
Do not open the control unit. For any fault, always use qualified personnel. The opening of the control unit and/or the removal
of the series identifying label entails the automatic forfeiture of the warranty. The Warranty seal is applied to all devices, any
attempt to open the unit would break the seal and cause the consequent automatic forfeiture of the warranty.
TECHNICAL INFORMATION
3 VRT200
Control unit
1MN0030 REV. 2
ATTENTION: always install the device using the terminals included in the pack. The use of terminals other
than those included with the control unit might cause malfunctions.
4 VRT200
POWER SUPPLY
INPUTS
OUTPUTS
DIMENSIONS
5 VRT200
Dielectric strength 1500 Vac for 1 minute: supply - relay fault, supply - remote. ●
6 VRT200
FRONT PANEL
8) Fans' control mode REM/LOC button 18) Programming selection LED (yellow)
(REMOTE or LOCAL) (% In, d.start, d.trip)
9) ENT/RESET button: alarm reset and 19) Monitoring delay LED (yellow) at start up
programming data selection d.start
10) Motors' auto-tuning phase LED (yellow) 20) Trip delay LED (yellow) d.trip
7 VRT200
1
1
1MN0063 REV. 0
3) Identification label
1 2 3 4
1MN0008 REV. 0
8 VRT200
ELECTRICAL CONNECTIONS
VRT200
5 3
1MN0046 REV. 0
1) AUX 1 - AUX 2 (COM) inputs fan 4) Control unit and fan line supply 230V±10%
temperature control PTC sensor connection 50-60 Hz 10 Amp.max
2) Remote enabling contact ENABLE 5) FAULT relay (fault signal)
3) M1-M2 motor line connection (5A max)
Note: with the power to the unit ON, the FAULT relay switches, contacts 8-9 open (NO) and 7-9 closed (NC).
7 8 9 7 8 9
FAULT 8-9 NC: ALARM FAULT OR POWER OFF FAULT 7-9: NC POWER ON
9 VRT200
The VRT200 control unit must be supplied with 230Vac ±10% 50/60Hz, check the connection diagrams on pages 9
and 10.
A variation in the network voltage of over 10% might cause alarms because of the current variation in the load.
If the electrical system is affected by harmonic frequencies, alarm warnings might be triggered because of the
consequent variation in the current absorbed by the motors.
It is good practice to make sure that the level of system harmonics is not such as to cause malfunction or damages to
all the connected electrical and electronic instruments, in compliance with the regulations in force for the type of
system.
OPERATION
When switched on, the device carries out a LAMP TEST and is set either in REMOTE or LOCAL mode, according to
how it was set before being switched off.
In REMOTE mode the fans are activated when contact 52-53 closes, which must be connected to the FAN contact of
the temperature control unit.
In LOCAL mode the fans are activated by pressing the <START-STOP> button. The status of operation is stored in
N.B.: A motor in a state of alarm or the interruption of supply to the device make contacts 8-9 of the FAULT relay close.
To reset an alarm due to under-current, over-current, overtemp-aux, press the RESET button after carrying out the
necessary checks and any repairs might be required.
The 400 and 600 bars are fitted with low current variation motors in case of a motor block. To optimise the operation
of the VRT200 control unit with these bars, we recommend the alarm threshold is programmed at 5%.
The proper functioning of the VRT unit is guaranteed only for: fans with current absorption between 250mA
(IN MAX 20%) or 300mA (IN MAX 30%) and 5A , single phase, single speed and power variation is not
greater than ± 10%.
IMPORTANT NOTE: if an existing control unit must be replaced with a new one, to guarantee
its correct and safe operation, all the connecting terminals must be replaced with the new terminals supplied,
on condition the brand of the new terminals is different from the one of the previously installed ones.
10 VRT200
Programming start Keep pressing for 5 seconds until the ON PRG
1
LED switches ON.
VRT200 By enabling this function it is possible to connect
a PTC (or series of PTCs) to control the motor
7 Going to the “OVERTEMP-AUX temperature. AUX1 for the M1 line
STOP” programming step and AUX2 for the M2 line
LEDS ▲ ON: PTCs enabled
VRT200 LEDs ▼ ON: PTC disabled
N.B.: if the PTC sensors are not
8
Enabling or disabling PTC inputs. connected, the function must be disabled.
Default disabled
ATTENTION:
We recommend you check the control unit before starting the device.
The default parameters set by TECSYSTEM might not suit your requirements.
Programming the device is the end user’s responsibility: the set alarm thresholds and the enabled
functions described in this manual must be checked (by a specialized technician) referring them to the
application and system characteristics on which the control unit is installed.
11 VRT200
WARRANTY CONDITIONS
The Product purchased is covered by the manufacturer's or seller's warranty at the terms and conditions set forth in
the "Tecsystem s.r.l's General Conditions of Sale", available at www.tecsystem.it and / or in the purchase agreement.
The warranty is considered valid only when the product is damaged by causes attributable to TECSYSTEM
srl, such as manufacturing or components defects.
The warranty is invalid if the Product proves to have been tampered with / modified, incorrectly connected,
because of voltages outside the limits, non-compliance with the assembly and use technical data, as described in
this instruction manual.
The warranty is always ex Corsico as stated in the "General Conditions of Sale".
Check that: the connector is correctly inserted into its housing, the
The control unit does not switch on and the wires are tightened, there is no evidence of burning on the
supply to terminals 40-42 is correct. connectors. Disconnect the power supply, carry out the above and
reconnect.
Check the condition of the fans and replace any faulty ones. Re-
M1 or M2 over-current red LED ON
program the device.
Check the condition of the fans, the cables and the supply. Re-
M1 or M2 under-current yellow LED ON
program the device.
Memory error, press RESET and repeat the programming
All the LEDs are flashing
procedure.
Likely microcontroller fault, return the device to Tecsystem for repair.
All the LEDs are ON
Contact TECSYSTEM Technical Department if the problem persists.
EQUIPMENT DISPOSAL
European directives 2012/19/EC (WEEE) and 2011/65/EC (RoHS) have been approved to reduce electrical and
electronic waste and promote the recycling and reuse of the materials and components of this equipment, cutting down
on the disposal of the residues and harmful components of electrical and electronic materials.
All the electrical and electronic equipment supplied after 13 August 2005 is marked with this symbol, pursuant
to the European directive 2002/96/EEC on electrical and electronic waste (WEEE). Any electrical or electronic
equipment marked with this symbol must be disposed of separately from normal domestic waste.
Returning used electrical devices: contact TECSYSTEM or the TECSYSTEM agent for information on the correct
disposal of the devices.
TECSYSTEM is aware of the impact its products have on the environment and asks its customers active support in the
correct and environmentally-friendly disposal of its devices.