Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Alarm Valve: Model-H (Ductile Iron)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

ALARM VALVE

MODEL-H (DUCTILE IRON) HD FIRE PROTECT


PVT. LTD.

TECHNICAL DATA
MODEL H
END CONNECTION Flange X Flange
Flange X Groove
Groove X Groove
NOMINAL SIZE 200, 150, 100 & 80 NB
MAXIMUM SERVICE 17.6 kg/sq.cm (250 psi)*
PRESSURE
THREADED OPENING BSPT
MOUNTING Vertical
FLANGE ANSI B16.42 #150 (Flange
CONNECTION drilling matching to ANSI B
16.5#150) Standard Supply.
TRIM Galvanized fittings with
Brass Valves
FACTORY 35 bar (500 psi)
HYDROSTATIC TEST DESCRIPTION
PRESSURE
Alarm Valve is a double seated clapper check valve
FRICTIONAL LOSS 200 NB - 7.5 Mtrs. with grooved seat design, which ensures positive
IN TERMS OF 150 NB - 7.0 Mtrs. water flow for alarm operation and is designed for
EQUIVALENT LENGTH 100 NB - 6.1 Mtrs. installation in wet pipe sprinkler system. External
OF PIPE ( C-120 ) 80 NB - 4.7 Mtrs. bypass prevents false alarm under all supply pressure
FINISH Red RAL 3001 condition. In the event of variable pressure condition,
false alarm is prevented with the provision of retard
APPROVAL UL Listed & FM Approved chamber, thus the design allows for installation under
ORDERING Specify size of valve, trim both variable and constant supply pressure condition.
INFORMATION details, grooved valve pipe Operation of one or more automatic fire sprinklers
outside diameter. causes the water to flow into the sprinkler system
REFERENCE NFPA 13 and NFPA 25 causing the alarm valve to open, allowing continuous
flow of water into the system and transmittal of
* For 200 NB, FM approval is rated upto 200 psi (14 kg/sq.cm) alarms, both electrical and mechanical.

WEIGHT IN KG
OPERATION
Valve Size Flange X Flange Flange X Groove Groove X Groove
The fire protection system initially when being
3” (80 NB) 18 15.0 12.10
pressurized, will allow water to flow into the system
27 22.1 17.30
until water supply and system pressure is equalized
4” (100 NB
and the clapper closes the waterway. Once the
6” (150 NB) 42 35.8 28.0
pressure is stabilized, the fire protection system
8” (200 NB) 65 54.0 44.0 is ready to be placed in service and then the alarm
control valve must be opened. Under normal condition,
GROOVE PIPE SIZE the water pressure gauge connected to the system
side of the alarm valve would show a higher or equal
NORMAL SIZE Pipe OD in mm
pressure reading than the water pressure gauge
3” (80 NB) 89 connected to the supply side of the valve. This occurs
4” (100 NB) 114.3 because of the bypass line connecting downstream
6” (150 NB) 165.1 and upstream side of the alarm valve, which allows
water pressure surge to pass without lifting the valve
6” (150 NB) 168.3
clapper off its seat, thereby causing excessive high
8” (200 NB) 219.1 pressure surge entrapped in the system side due to
NOTE: FOR 6” (150 NB) STANDARD SUPPLY IS 168.3 mm OD PIPE presence of a check valve, which generally prevents
GROOVE. FOR 165.1mm REQUIREMENT, SPECIFY IN ORDER false alarm.

DECEMBER, 2021 PAGE 1 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

Sudden high pressure surge, as might be encountered from functioning properly as well as void listing,
by start-up of a large fire pump may lead the valve approval and the manufacturer’s warranty.
clapper to lift momentarily, allowing water to flow
5. Care must be exercised while installing the
through grooves in the valve seat to the retard
check valve in the trim to ascertain that they are
chamber. The water in the alarm line is automatically
located with the arrow mark on the check valve
drained out, which helps to prevent false alarm due
body and pointed in proper direction.
to successive transient surge in supply pressure.
The restriction assembly located beneath the retard 6. The contraction and expansion associated with an
chamber consists of inlet and drain restriction excessive volume of trapped air could cause the
orifices, which are established by considering the waterway clapper to periodically open and shut.
volume of the retard chamber to meet the listing This may result in false alarm or intermittent
and approval requirements about time-to-alarm alarm. To avoid these, it is recommended to have
factor. These requirements represent a balancing of breather valve in the system piping network & a
the need to reduce the possible false alarm due to vent valve at the extreme end of the system to
a transient surge in supply pressure and to achieve bleed-off the air.
desired minimum time- to- alarm following a sprinkler
7. The ball valve provided on the alarm line must
operation.
be kept open and strapped in set position.
In constant pressure installation, the retard chamber
8. Pipe connecting the retard chamber and sprinkler
is not required and the water passing through the
alarm bell must be supported properly to avoid
groove in the alarm valve seat flows directly through
loading on the retard chamber.
restriction nozzle assembly to activate the mechanical
and electrical alarm. 9. All the newly installed system pipes must be flushed
properly before alarm valve is put into service.
ACCESSORIES

Retard Chamber:
INSPECTION AND MAINTENANCE
HD retard chamber model RC9 is required when A qualified and trained person must commission
the Alarm Valve is installed on systems with a the system. After few initial successful tests an
variable pressure water supply to curtail unwant- authorised person must be trained to perform
ed and false alarms. inspection and testing of the system.
• Water Motor Sprinkler Alarm: It is recommended to carry out physical inspection
Alarm Valve model H is designed to operate a of the system at least twice a week. The inspection
mechanical alarm gong during a sustained flow of should verify that all control valves are in proper
water (such as the flow required by an open sprin- position as per the requirement of the system and
kler). Refer to the water motor sprinkler alarm no damage has taken place to any component. It is
catalogue HD 107 for further details. recommended that the alarm valve and its accessories
should be examined and performed for following at
• Pressure Switch (Optional):
least quarterly or as demanded by local authorities to
Alarm Valve trim allows connection of pressure
ensure reliable and trouble free operation and service.
switch to activate local electric alarms or remote
electric alarms during a constant flow of water 1. Inspection and testing is to be carried out only by
(such as the flow required by open sprinklers). an authorized person. DO NOT TURN OFF the
water supply valve to undertake repair work or to
INSTALLATION test the valve, without placing a roving fire patrol
in the area covered by the system. The patrol
1. HD sprinkler alarm valve, Model-H must be
should continue until the system is back into
installed vertically only.
service. Also do inform the local security personnel
2. The alarm valve must be installed in a readily visible and alarm control station, so that a false alarm
and accessible location and provision to be made is not signaled.
in such a way that alarm line drain is visible and
2. Open the alarm test valve. Verify that the sprinkler
accessible.
alarm bell and/or the pressure alarm switch/
3. Where water pressure fluctuates, the variable electric alarm properly actuates. Close the alarm
pressure trim with retard chamber must be used. test valve and verify that water has ceased
Under non-fluctuating water pressure condition, to flow from the alarm line drain.
the constant pressure trim, which does not 3. Clean the 20 NB (3/4”) strainer provided on the
include retard chamber, may be used. sprinkler alarm bell line.
4. The valve must be installed with trim in accordance 4. Clean the strainer of restriction assembly.
with the trim data. Failure to follow the appropiate
trim connection guidelines may prevent the device 5. Inspect the check valve clapper located on
the bypass line.

DECEMBER, 2021 PAGE 2 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

FALSE ALARM
1. Inspect the valve rubber clapper face. If worn
or damaged, replace it. Be certain that dirt, stone
or any other foreign object have not accumulated
under the clapper face and lodged in the groove
or holes. Clean the clapper face thoroughly. If the
seat ring surface is nicked or scoured, it might be
possible to repair the same using lapping
compound. If not, replace the complete valve or
return it to the manufacturer’s works for repair.
2. If sprinkler alarm bell is not functioning or the
impeller is jammed, please follow the maintenance
guidelines provided in the catalogue for sprinkler
alarm bell.
3. If pressure alarm switch gives a steady signal, but
sprinkler alarm generates an intermittent alarm,
check sprinkler alarm bell shaft. If both the
sprinkler alarm bell and pressure alarm switch are
generating intermittent alarm then check for the
possible air which is trapped within the sprinkler
system. Trapped air is to be bled off. Also intermittent
alarm may occur due to sudden pressure drop or
increase in the system pressure. These problems
can be corrected by maintaining a steady supply.

CAUTION
1. The UL Listing, FM Approval and manufacturer’s
warranty are valid only when the alarm valve
is installed with HD trim set and installed as per
installation guidelines.
2. Pressure relief valve is required with wet pipe sys-
tem when a rise in ambient temperature can
cause system pressure to exceed beyond 17.5 kg/
sq.cm (250 psi). In that case, suitable pressure
relief valve setting should be used.
3. For proper operation of the wet system and to
minimize unwanted false alarm, it is important to
remove trapped air from the system. Air trapped
in the system may also cause intermittent
operation of the Water Motor Alarm during
sustained flow of water.

DECEMBER, 2021 PAGE 3 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

ALARM VALVE, MODEL – H SIZE 200 / 150 / 100 / 80 NB

FLANGE X GROOVE 2

1
1
7

11 3

GROOVE X GROOVE 6
9
5
9 12
4
8 FLANGE X FLANGE
13
11
10

PART LIST
PART NO. QTY.
MATERIAL
ITEM 200 150 100 80 DESCRIPTION 200 150 100 80 SPECIFICATION
NB NB NB NB NB NB NB NB
1 NA NA NA NA HOUSING (FLANGE X FLANGE) 1 1 1 1 DUCTILE IRON
1 NA NA NA NA HOUSING (FLANGE X GROOVE) 1 1 1 1 DUCTILE IRON
1 NA NA NA NA HOUSING (GROOVE X GROOVE) 1 1 1 1 DUCTILE IRON
2 NA NA NA NA SEAT 1 1 1 1 STAINLESS STEEL*
3 2600 2600 2600 2600 CLAPPER BUSH 2 2 2 2 BRASS
4 9102 9101 9101 9101 HEX. HEAD BOLT 4 1 1 1 STAINLESS STEEL
5 2636 2628 2619 2656 RUBBER CLAMP 1 1 1 1 STAINLESS STEEL
6 117769 117765 117761 117757 RUBBER SEAT 1 1 1 1 EPDM **
7 2634 2603 2617 2654 CLAPPER 1 1 1 1 DUCTILE IRON
8 2638 2608 2258 2658 HINGE PIN 1 1 1 1 STAINLESS STEEL
9 2599 2599 2599 2599 BODY BUSH 2 2 2 2 BRASS
10 9004 9004 9004 8373 HEX. HEAD BOLT 6 6 4 4 STEEL
11 9430 9430 9430 9430 SQ. HEAD PLUG 2 2 2 2 DUCTILE IRON
12 117767 117763 117759 117752 COVER GASKET 1 1 1 1 EPDM **
13 2631 2604 2615 2651 COVER 1 1 1 1 DUCTILE IRON

* Stainless Steel is a standard supply, Bronze is an optional supply


** EPDM is a standard supply, Neoprene is an optional supply
NA : Not Applicable as these parts cannot be replaced

DECEMBER, 2021 PAGE 4 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

Nominal Pressure Loss vs Flow - Alarm Valve (Model H)

Flow Rate - Gallons Per Minute (gpm)


70 100 200 300 500 700 1000 2000 3000 5000
3 0.2

Nominal Pressure Loss in bar


Nominal Pressure Loss in psi

0.1

1 0.07

8”)
0.7 0.05
4”)

6”)
3”)

B(
0.04
B(

B(
(

0N
NB

0.5
0N

0N

0.03

20
80

0.4
10

15

0.3 0.02

0.2

0.01

0.1
200 300 500 700 1000 2000 3000 5000 7000 10000 20000

Flow Rate - Litres Per Minute (lpm)

DECEMBER, 2021 PAGE 5 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

CONSTANT PRESSURE TRIM FOR ALARM VALVE MODEL - H


200 / 150 / 100 / 80 NB

GROOVE X GROOVE FLANGE X GROOVE

17 17

NO 25
16
14 15 NO
14 24
15 18 D
16
13
FLANGE X FLANGE

29
2

P1
28
#
1
# 12
@ NC 2,29
22 10 2
1
11 9
19
28 8 4
28 NO 5 7
1 ,2 3
2 8 1,28
10 6
21 26 19
30 3
1 29
23 27
26

20

D
NOTES:-
D
# - PRESSURE SWITCH (OPTIONAL)
@ - NOT SUPPLIED WHEN PRESSURE SWITCH IS ORDERED
D - TO OPEN DRAIN
- STANDARD LENGTH SUPPLY OR USER TO SPECIFY (TO SUIT AT SITE) FOR ANY ALTERATIONS .
NO - NORMALLY OPEN
NC - NORMALLY CLOSED

DECEMBER, 2021 PAGE 6 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

CONSTANT PRESSURE TRIM FOR ALARM VALVE MODEL - H


200 / 150 / 100 / 80 NB

QUANTITY
ITEM CODE
DESCRIPTION SIZE PER ALARM VALVE SIZE
NO. NO.
200NB 150NB 100NB 80NB
1 8625 HEX NIPPLE 3/4” 4 4 5 2
2 8620 TEE 3/4” 3 3 3 2
3 8617 ELBOW 3/4” 2 2 2 -
3 8616 ELBOW 1/2” - - - 2
4 8951 PIPE NIPPLE 3/4” X 150 MM LONG 1 - - -
4 9407 PIPE NIPPLE 3/4” X 130 MM LONG - 1 - -
4 9406 PIPE NIPPLE 3/4” X 100 MM LONG - - 1 -
4 9397 PIPE NIPPLE 1/2” X 100 MM LONG - - - 1
5 9406 PIPE NIPPLE 3/4” X 100 MM LONG 1 - - -
5 9441 PIPE NIPPLE 3/4” X 80 MM LONG - 1 - -
6 9397 PIPE NIPPLE 1/2” X 100 MM LONG 1 1 - 1
6 9480 PIPE NIPPLE 1/2” X 80 MM LONG - - 1 -
7 8628 UNION 3/4” 1 1 1 -
7 8627 UNION 1/2” - - - 1
8 9421 SWING CHECK VALVE 3/4” 1 1 1
8 9455 SWING CHECK VALVE 1/2” - - - 1
9 8663 PIPE NIPPLE 3/4” X 70MM LONG 1 1 - -
9 9426 PIPE NIPPLE 3/4” X 60MM LONG - - 1 -
9 9498 PIPE NIPPLE 1/2” X 75MM LONG - - - 1
10 9423 BALL VALVE 1/2” 2 2 2 2
11 8633 REDUCING HEX NIPPLE 3/4” X 1/2” - - - 1
12 8632 REDUCING HEX NIPPLE 3/4” X 1/4” 1 1 1 1
13 8631 REDUCING HEX NIPPLE 1/2” X 1/4” 1 1 1 1
14 9477 BALL VALVE 1/4” 2 2 2 2
15 8698 HEX NIPPLE 1/4” 2 2 2 2
16 8357 ELBOW 1/4” 2 2 2 2
17 114071 PRESSURE GUAGE 0-300 PSI, ‘UL’ LISTED 2 2 2 2
18 2301 ALARM TEST LINE ASSEMBLY 1/2” - - - 1
18 2302 ALARM TEST LINE ASSEMBLY 1/2” - - 1 -
18 2303 ALARM TEST LINE ASSEMBLY 1/2” - 1 - -
18 2304 ALARM TEST LINE ASSEMBLY 1/2” 1 - - -
19 8355 REDUCING BUSH 3/4” X 1/2” 2 2 2 1
20 1027 RESTRICTION NOZZLE ASSEMBLY - 1 1 1 1
21 117441 ‘Y‘ TYPE STRAINER 3/4” 1 1 1 1
22 8629 PLUG 1/2” 1 1 1 1
23 1416 SPRINKLER ALARM - 1 1 1 1
24 8359 HEX NIPPLE 2” 1 1 1 -
24 8360 HEX NIPPLE 1-1/4” - - - 1
25 9394 ANGLE VALVE 2” 1 1 1 -
25 9392 ANGLE VALVE 1-1/4” - - - 1
26 9561 PIPE NIPPLE 1/2” X 60MM LONG 2 2 2 2
27 9441 PIPE NIPPLE 3/4” X 80MM LONG 1 1 1 1
28 8624 HEX NIPPLE 1/2” 3 3 3 5
29 8619 TEE 1/2” 2 2 2 3
30 9406 PIPE NIPPLE 3/4” X 100MM LONG 1 1 1 1
OPTIONAL
P1 - PRESSURE SWITCH - 1 1 1 1

DECEMBER, 2021 PAGE 7 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

VARIABLE PRESSURE TRIM FOR ALARM VALVE MODEL - H


200 / 150 / 100 / 80 NB

GROOVE X GROOVE FLANGE X GROOVE

17 17

NO 25
16
P1 14 15 NO
# 14 24
15 18 D
# 16
13
@ FLANGE X FLANGE
22
19 29
2

2 28

21 1 1
31
27 12
23 NC 2,29
10 2
1
11 9
28 8 4
30 28 NO 5 7
1 ,2 3
8 1,28
10 6
D 26 19
3
1 29
26

20

NOTES: - D

# - PRESSURE SWITCH (OPTIONAL)


@ - NOT SUPPLIED WHEN PRESSURE SWITCH IS ORDERED
D - TO OPEN DRAIN
- STANDARD LENGTH SUPPLY OR USER TO SPECIFY (TO SUIT AT SITE) FOR ANY ALTERATIONS .
NO - NORMALLY OPEN
NC - NORMALLY CLOSED

DECEMBER, 2021 PAGE 8 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

VARIABLE PRESSURE TRIM FOR ALARM VALVE MODEL - H


200 / 150 / 100 / 80 NB

QUANTITY
ITEM CODE
DESCRIPTION SIZE PER ALARM VALVE SIZE
NO. NO.
200NB 150NB 100NB 80NB
1 8625 HEX NIPPLE 3/4” 5 5 6 3
2 8620 TEE 3/4” 3 3 3 2
3 8617 ELBOW 3/4” 2 2 2 -
3 8616 ELBOW 1/2” - - - 2
4 8951 PIPE NIPPLE 3/4” X 150 MM LONG 1 - - -
4 9407 PIPE NIPPLE 3/4” X 130 MM LONG - 1 - -
4 9406 PIPE NIPPLE 3/4” X 100 MM LONG - - 1 -
4 9397 PIPE NIPPLE 1/2” X 100 MM LONG - - - 1
5 9406 PIPE NIPPLE 3/4” X 100 MM LONG 1 - - -
5 9441 PIPE NIPPLE 3/4” X 80 MM LONG - 1 - -
6 9397 PIPE NIPPLE 1/2” X 100 MM LONG 1 1 - 1
6 9480 PIPE NIPPLE 1/2” X 80 MM LONG - - 1 -
7 8628 UNION 3/4” 1 1 1 -
7 8627 UNION 1/2” - - - 1
8 9421 SWING CHECK VALVE 3/4” 1 1 1
8 9455 SWING CHECK VALVE 1/2” - - - 1
9 8663 PIPE NIPPLE 3/4” X 70MM LONG 1 1 - -
9 9426 PIPE NIPPLE 3/4” X 60MM LONG - - 1 -
9 9498 PIPE NIPPLE 1/2” X 75MM LONG - - - 1
10 9423 BALL VALVE 1/2” 2 2 2 2
11 8633 REDUCING HEX NIPPLE 3/4” X 1/2” - - - 1
12 8632 REDUCING HEX NIPPLE 3/4” X 1/4” 1 1 1 1
13 8631 REDUCING HEX NIPPLE 1/2” X 1/4” 1 1 1 1
14 9477 BALL VALVE 1/4” 2 2 2 2
15 8698 HEX NIPPLE 1/4” 2 2 2 2
16 8357 ELBOW 1/4” 2 2 2 2
17 114071 PRESSURE GUAGE 0-300 PSI, ‘UL’ LISTED 2 2 2 2
18 2301 ALARM TEST LINE ASSEMBLY 1/2” - - - 1
18 2302 ALARM TEST LINE ASSEMBLY 1/2” - - 1 -
18 2303 ALARM TEST LINE ASSEMBLY 1/2” - 1 - -
18 2304 ALARM TEST LINE ASSEMBLY 1/2” 1 - - -
19 8355 REDUCING BUSH 3/4” X 1/2” 2 2 2 1
20 1027 RESTRICTION NOZZLE ASSEMBLY - 1 1 1 1
21 117441 ‘Y‘ TYPE STRAINER 3/4” 1 1 1 1
22 8629 PLUG 1/2” 1 1 1 1
23 1416 SPRINKLER ALARM - 1 1 1 1
24 8359 HEX NIPPLE 2” 1 1 1 -
24 8360 HEX NIPPLE 1-1/4” - - - 1
25 9394 ANGLE VALVE 2” 1 1 1 -
25 9392 ANGLE VALVE 1-1/4” - - - 1
26 9561 PIPE NIPPLE 1/2” X 60MM LONG 2 2 2 2
27 9441 PIPE NIPPLE 3/4” X 80MM LONG 1 1 1 1
28 8624 HEX NIPPLE 1/2” 3 3 3 5
29 8619 TEE 1/2” 2 2 2 3
30 2300 RETARD CHAMBER - 1 1 1 1
31 9406 PIPE NIPPLE 3/4” X 100MM LONG 1 1 1 1
OPTIONAL
P1 - PRESSURE SWITCH - 1 1 1 1

DECEMBER, 2021 PAGE 9 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

CONSTANT PRESSURE TRIM - SCHEMATIC


ALARM VALVE MODEL - H FLANGE X FLANGE 200/150/100/80 NB
DOWNSTREAM SYSTEM SUPPLY
(TO SYSTEM)
PRESSURE PRESSURE
PG PG

PS *
*G

AT
(NC)
AV ~
TO DRAIN
AC

~ (NO)
OD

TO DRAIN

UPSTREAM
(FROM SUPPLY)

VARIABLE PRESSURE TRIM - SCHEMATIC


ALARM VALVE MODEL - H FLANGE X FLANGE 200 / 150 / 100 / 80 NB
DOWNSTREAM
(TO SYSTEM)
SYSTEM SUPPLY
PRESSURE PRESSURE
PG PG

PS *
*G

AT RC
(NC)
AV ~
TO DRAIN
AC

~ (NO)
OD

TO DRAIN

UPSTREAM
(FROM SUPPLY)

ABBREVIATION & SYMBOLS


NON RETURN VALVE NO - NORMALLY OPEN PG - PRESSURE GUAGE
VALVE NC - NORMALLY CLOSE PS - PRESSURE SWITCH
ANGLE VALVE OD - OPEN DRAIN AC - SPRINKLER ALARM CONTROL VALVE

STRAINER AV - ALARM VALVE AT - SPRINKLER ALARM TEST VALVE

RESTRICTION NOZZLE ASSEMBLY G - SPRINKLER ALARM ---- - BY USER (NOT IN ‘HD’ SCOPE OF SUPPLY)

 OPTIONAL RC - RETARD CHAMBER

NOTE :-

1) SPRINKLER ALARM CONTROL VALVE MUST BE KEPT NORMALLY OPEN.


IF THIS VALVE IS KEPT CLOSED, THE SPRINKLER ALARM BELL/ ELECTRIC ALARM WILL NOT SIGNAL.

2) SPRINKLER ALARM TEST VALVE MUST BE KEPT NORMALLY CLOSED.


VALVE IS OPENED TO TEST THE SPRINKLER ALARM BELL /ELECTRIC ALARM.

DECEMBER, 2021 PAGE 10 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

CONSTANT PRESSURE TRIM - SCHEMATIC


ALARM VALVE MODEL - H FLANGE X GROOVE 200 / 150 / 100 / 80 NB
DOWNSTREAM
(TO SYSTEM) SYSTEM SUPPLY
PRESSURE PRESSURE
PG PG

PS *
*G

AT
AV (NC) ~
TO DRAIN
AC
~ (NO)
OD

TO DRAIN

UPSTREAM
(FROM SUPPLY)

VARIABLE PRESSURE TRIM - SCHEMATIC


ALARM VALVE MODEL - H FLANGE X GROOVE 200 / 150 / 100 / 80 NB
DOWNSTREAM
(TO SYSTEM)
SYSTEM SUPPLY
PRESSURE PRESSURE
PG PG

PS *
*G

AT RC
AV (NC) ~
TO DRAIN
AC
~ (NO)
OD

TO DRAIN

UPSTREAM
(FROM SUPPLY)

ABBREVIATION & SYMBOLS


NON RETURN VALVE NO - NORMALLY OPEN PG - PRESSURE GUAGE
VALVE NC - NORMALLY CLOSE PS - PRESSURE SWITCH
ANGLE VALVE OD - OPEN DRAIN AC - SPRINKLER ALARM CONTROL VALVE

STRAINER AV - ALARM VALVE AT - SPRINKLER ALARM TEST VALVE

RESTRICTION NOZZLE ASSEMBLY G - SPRINKLER ALARM ---- - BY USER (NOT IN ‘HD’ SCOPE OF SUPPLY)

 OPTIONAL RC - RETARD CHAMBER

NOTE :-

1) SPRINKLER ALARM CONTROL VALVE MUST BE KEPT NORMALLY OPEN.


IF THIS VALVE IS KEPT CLOSED, THE SPRINKLER ALARM BELL/ ELECTRIC ALARM WILL NOT SIGNAL.

2) SPRINKLER ALARM TEST VALVE MUST BE KEPT NORMALLY CLOSED.


VALVE IS OPENED TO TEST THE SPRINKLER ALARM BELL /ELECTRIC ALARM.

DECEMBER, 2021 PAGE 11 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

CONSTANT PRESSURE TRIM - SCHEMATIC


ALARM VALVE MODEL - H GROOVE X GROOVE 200 / 150 / 100 / 80 NB
DOWNSTREAM
(TO SYSTEM) SYSTEM SUPPLY
PRESSURE PRESSURE
PG PG

PS *
*G

AT
AV (NC)
~
TO DRAIN
AC
~
OD (NO)

TO DRAIN

UPSTREAM
(FROM SUPPLY)

VARIABLE PRESSURE TRIM - SCHEMATIC


ALARM VALVE MODEL - H GROOVE X GROOVE 200 / 150 / 100 / 80 NB
DOWNSTREAM
(TO SYSTEM) SYSTEM SUPPLY
PRESSURE PRESSURE
PG PG

PS *
*G

AT RC
AV (NC)
~
TO DRAIN
AC
~ (NO)
OD

TO DRAIN

UPSTREAM
(FROM SUPPLY)

ABBREVIATION & SYMBOLS


NON RETURN VALVE NO - NORMALLY OPEN PG - PRESSURE GUAGE
VALVE NC - NORMALLY CLOSE PS - PRESSURE SWITCH
ANGLE VALVE OD - OPEN DRAIN AC - SPRINKLER ALARM CONTROL VALVE

STRAINER AV - ALARM VALVE AT - SPRINKLER ALARM TEST VALVE

RESTRICTION NOZZLE ASSEMBLY G - SPRINKLER ALARM ---- - BY USER (NOT IN ‘HD’ SCOPE OF SUPPLY)

 OPTIONAL RC - RETARD CHAMBER

NOTE :-

1) SPRINKLER ALARM CONTROL VALVE MUST BE KEPT NORMALLY OPEN.


IF THIS VALVE IS KEPT CLOSED, THE SPRINKLER ALARM BELL/ ELECTRIC ALARM WILL NOT SIGNAL.

2) SPRINKLER ALARM TEST VALVE MUST BE KEPT NORMALLY CLOSED.


VALVE IS OPENED TO TEST THE SPRINKLER ALARM BELL /ELECTRIC ALARM.

DECEMBER, 2021 PAGE 12 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

INSTALLATION DIMENSION WITH TRIM


ALARM VALVE MODEL - H FLANGE X FLANGE 200 / 150 / 100 / 80 NB

A) CONSTANT PRESSURE TRIM WITH CONSTANT PRESSURE TRIM


SIZE 80NB 100NB 150NB 200NB
A 279 312 331 350
B 457 464 486 527
E

C 434 434 434 443


D 127 140 173 192
E 201 219 234 269
F 262 274 315 378
D

DIMENSIONS are approx. and in millimeters


C
F

A B

B) VARIABLE PRESSURE TRIM WITH VARIABLE PRESSURE TRIM


SIZE 80NB 100NB 150NB 200NB
A 279 312 331 350
B 482 488 510 551
E

C 588 588 588 597


D 127 140 173 192
E 201 219 234 269
F 262 274 315 378
D

DIMENSIONS are approx. and in millimeters


C
F

A B

DECEMBER, 2021 PAGE 13 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

INSTALLATION DIMENSION WITH TRIM


ALARM VALVE MODEL - H FLANGE X GROOVE 200 / 150 / 100 / 80 NB

A) CONSTANT PRESSURE TRIM WITH CONSTANT PRESSURE TRIM


SIZE 80NB 100NB 150NB 200NB
A 279 312 331 350
E

B 457 464 486 527


C 434 434 434 443
D 127 140 173 204
E 201 219 234 269
D

F 275 291.3 316.8 395.2

DIMENSIONS are approx. and in millimeters


C
F

A B

B) VARIABLE PRESSURE TRIM WITH VARIABLE PRESSURE TRIM


SIZE 80NB 100NB 150NB 200NB
A 279 312 331 350
B 482 488 510 551
E

C 588 588 588 597


D 127 140 173 204
E 201 219 234 269
D

F 275 291.3 316.8 395.2

DIMENSIONS are approx. and in millimeters


C
F

A B

DECEMBER, 2021 PAGE 14 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

INSTALLATION DIMENSION WITH TRIM


ALARM VALVE MODEL - H GROOVE X GROOVE 200 / 150 / 100 / 80 NB

A) CONSTANT PRESSURE TRIM WITH CONSTANT PRESSURE TRIM


SIZE 80NB 100NB 150NB 200NB
A 279 312 331 350
B 457 464 486 527
E

C 439 443 442 443


D 127 140 173 204
E 201 219 234 269
D

F 280 300 324 405

DIMENSIONS are approx. and in millimeters


C
F

A B

B) VARIABLE PRESSURE TRIM WITH VARIABLE PRESSURE TRIM


SIZE 80NB 100NB 150NB 200NB
A 279 312 331 350
B 482 488 510 551
E

C 593 596 596 607


D 127 140 173 204
E 201 219 234 269
D

F 280 300 324 405

DIMENSIONS are approx. and in millimeters


C
F

A B

DECEMBER, 2021 PAGE 15 OF 16 HD 247


HD FIRE PROTECT
PVT. LTD.

LIMITED WARRANTY
HD FIRE PROTECT PVT. LTD. hereby referred to as HD FIRE warrants to the original purchaser of the fire protection products manufactured by HD FIRE and to any other person
to whom such equipment is transferred, that such products will be free from defect in material and workmanship under normal use and care, for two (2) years from the date of
shipment by HD FIRE. Products or Components supplied or used by HD FIRE, but manufactured by others, are warranted only to the extent of the manufacturer’s warranty.
No warranty is given for product or components which have been subject to misuse, improper installation, corrosion, unauthorized repair, alteration or un-maintained.
HD FIRE shall not be responsible for system design errors or improper installation or inaccurate or incomplete information supplied by buyer or buyer’s representatives.
HD FIRE will repair or replace defective material free of charge, which is returned to our factory, transportation charge prepaid, provided after our inspection the material is
found to have been defective at the time of initial shipment from our works. HD FIRE shall not be liable for any incidental or consequential loss, damage or expense arising directly
or indirectly from the use of the product including damages for injury to person, damages to property and penalties resulting from any products and components manufactured
by HD FIRE. HD FIRE shall not be liable for any damages or labour charges or expense in making repair or adjustment to the product. HD FIRE shall not be liable for any
damages or charges sustained in the adaptation or use of its engineering data & services. In no event shall HD Fire’s product liability exceed an amount equal to the sale price.
The foregoing warranty is exclusive and in lieu of all other warranties and representation whether expressed, implied, oral or written, including but not limited
to, any implied warranties or merchantability or fitness for a particular purpose. All such other warranties and representations are hereby cancelled.

NOTICE :
The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the
provision of government codes or ordinances wherever applicable.
The information provided by us is to the best of our knowledge and belief, and consist of general guidelines only. Site handling and installation control is not in our scope.
Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or
damages due to our product.
Product development is a continuous programme of HD FIRE PROTECT PVT. LTD. and hence the right to modify any specification without prior notice is reserved with
the company.

D-6/2, ROAD NO. 34, WAGLE INDUSTRIAL ESTATE, THANE 400 604, INDIA.
HD FIRE PROTECT PVT. LTD. • TEL: + (91) 22 2158 2600 • FAX: +(91) 22 2158 2602
Protecting What Matters Most to You • EMAIL: info@hdfire.com • WEB: www.hdfire.com

DECEMBER, 2021 PAGE 16 OF 16 HD 247

You might also like