ABB - Cause & Effect Diagram

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

29.06.

2021
RED FIRE ALARM SUBSTATION NAME: 132KV SUBSTATION UMM AL QUWAIN
DOC. NO. 12118.20/ABB/UAQ/M05/40428
AMBER SUPERVISORY & FAULT CONTRACT NO: 12118.2

GREEN DELUGE / SPRINKLER MAIN CONTRACTOR: ABB Industries (L.L.C) DUBAI BY APP BY SHEET

BLUE GAS RELEASED SUB CONTRACTOR: CORODEX AGENCIES CO. L.L.C U.N MR 1 OF 2

FACP PANEL FECP PANEL


SCADA SIGNALS SHUTDOWN RELAYS NOTIFICATION ANNUNCIATION
INDICATION INDICATION
INPUT DEIVICE ADDRESS
SERIAL NUMBER

Solenoid Release Respective Hazard


PANEL NO.

132KV BASEMENT VENTILATION


SPRIKLER SYSTEM OPERATED

Battery Room Exhause FAN ON


DELUGE SYSTEM OPERATED
DEVICE

FM-200 GAS / CLEAN AGENT


FIRE PROTECTION SYSTEM
ZONE

STATUS / INPUT

BASEMENT VENTILATION
BASEMENT LHD SYSTEM

HVAC SYSTEM-1 (132KV


LOCATION AND TYPE OF DEVICE

LV & CONTROL CABLE


FIRE ALARM COMMON

SOUNDER CIRCUIT # 1

SOUNDER CIRCUIT # 2
ACTION

FAULT / CPU FAULT

SOUNDER CIRCUIT

SOUNDER CIRCUIT

REPEATER PANEL
GAS DISCHARGE

HVAC SYSTEM-2
SUPERVISORY

SUPERVISORY

MIMIC PANEL
Second Stage

MAIN FACP
OPERATED

GIS ROOM)

First Stage
FAULT

FAULT
FIRE

FIRE
1 02 01 001 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E13 FIRE a a a a a a a a a a
2 02 01 002 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E12 FIRE a a a a a a a a a a
3 02 01 003 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E11 FIRE a a a a a a a a a a
4 02 01 004 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E10 FIRE a a a a a a a a a a
5 02 01 005 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E09 FIRE a a a a a a a a a a
6 02 01 006 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E08 FIRE a a a a a a a a a a
7 02 01 007 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E07 FIRE a a a a a a a a a a
8 02 01 008 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E06 FIRE a a a a a a a a a a
9 02 01 009 2 SMOKE DETECTOR 132KV GIS ROOM GROUP-1 LCC-E05 FIRE a a a a a a a a a a
10 02 01 010 2 SMOKE DETECTOR 132KV GIS ROOM GROUP-1 LCC-E04 FIRE a a a a a a a a a a
11 02 01 011 2 SMOKE DETECTOR 132KV GIS ROOM GROUP-1 LCC-E03 FIRE a a a a a a a a a a
12 02 01 012 2 SMOKE DETECTOR 132KV GIS ROOM GROUP-1 LCC-E02 FIRE a a a a a a a a a a
13 02 01 013 2 SMOKE DETECTOR 132KV GIS ROOM GROUP-1 LCC-E01 FIRE a a a a a a a a a a
14 02 01 014 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
15 02 01 015 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
16 02 01 016 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
17 02 01 017 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
18 02 01 018 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
19 02 01 019 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
20 02 01 020 4 SMOKE DETECTOR SCADA/TELECOM ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
21 02 01 021 4 SMOKE DETECTOR SCADA/TELECOM ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
22 02 01 022 4 SMOKE DETECTOR SCADA/TELECOM ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
23 02 01 023 4 SMOKE DETECTOR SCADA/TELECOM ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
24 02 01 024 5 SMOKE DETECTOR LVAC & DC ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
25 02 01 025 5 SMOKE DETECTOR LVAC & DC ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a

1 of 5
RED FIRE ALARM SUBSTATION NAME: 132KV SUBSTATION UMM AL QUWAIN
DOC. NO. 12118.20/ABB/UAQ/M05/40428
AMBER SUPERVISORY & FAULT CONTRACT NO: 12118.2

GREEN DELUGE / SPRINKLER MAIN CONTRACTOR: ABB Industries (L.L.C) DUBAI BY APP BY SHEET

BLUE GAS RELEASED SUB CONTRACTOR: CORODEX AGENCIES CO. L.L.C U.N MR 1 OF 2

FACP PANEL FECP PANEL


SCADA SIGNALS SHUTDOWN RELAYS NOTIFICATION ANNUNCIATION
INDICATION INDICATION
INPUT DEIVICE ADDRESS
SERIAL NUMBER

Solenoid Release Respective Hazard


PANEL NO.

132KV BASEMENT VENTILATION


SPRIKLER SYSTEM OPERATED

Battery Room Exhause FAN ON


DELUGE SYSTEM OPERATED
DEVICE

FM-200 GAS / CLEAN AGENT


FIRE PROTECTION SYSTEM
ZONE

STATUS / INPUT

BASEMENT VENTILATION
BASEMENT LHD SYSTEM

HVAC SYSTEM-1 (132KV


LOCATION AND TYPE OF DEVICE

LV & CONTROL CABLE


FIRE ALARM COMMON

SOUNDER CIRCUIT # 1

SOUNDER CIRCUIT # 2
ACTION

FAULT / CPU FAULT

SOUNDER CIRCUIT

SOUNDER CIRCUIT

REPEATER PANEL
GAS DISCHARGE

HVAC SYSTEM-2
SUPERVISORY

SUPERVISORY

MIMIC PANEL
Second Stage

MAIN FACP
OPERATED

GIS ROOM)

First Stage
FAULT

FAULT
FIRE

FIRE
26 02 01 026 5 SMOKE DETECTOR LVAC & DC ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
27 02 01 027 5 SMOKE DETECTOR LVAC & DC ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
28 02 01 028 5 SMOKE DETECTOR LVAC & DC ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
29 02 01 029 6 HEAT DETECTOR BATTERY ROOM - HEAT DETECTOR FIRE a a a a a a a a a a
30 02 01 030 6 HEAT DETECTOR BATTERY ROOM - HEAT DETECTOR FIRE a a a a a a a a a a
31 02 01 031 6 HEAT DETECTOR BATTERY ROOM - HEAT DETECTOR FIRE a a a a a a a a a a
32 02 01 032 6 HEAT DETECTOR BATTERY ROOM - HEAT DETECTOR FIRE a a a a a a a a a a
<<END OF LOOP 1 >>

1 02 03 001 1 SMOKE DETECTOR 132kV GIS Room Group 2 LCC-E013 FIRE a a a a a a a a a a


2 02 03 002 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E12 FIRE a a a a a a a a a a
3 02 03 003 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E11 FIRE a a a a a a a a a a
4 02 03 004 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E10 FIRE a a a a a a a a a a
5 02 03 005 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E09 FIRE a a a a a a a a a a
6 02 03 006 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E08 FIRE a a a a a a a a a a
7 02 03 007 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E07 FIRE a a a a a a a a a a
8 02 03 008 1 SMOKE DETECTOR 132KV GIS ROOM GROUP-2 LCC-E06 FIRE a a a a a a a a a a
9 02 03 009 2 SMOKE DETECTOR 132KV GIS ROOM GROUP-1 LCC-E05 FIRE a a a a a a a a a a
10 02 03 010 2 SMOKE DETECTOR 132KV GIS ROOM GROUP-1 LCC-E04 FIRE a a a a a a a a a a
11 02 03 011 2 SMOKE DETECTOR 132KV GIS ROOM GROUP-1 LCC-E03 FIRE a a a a a a a a a a
12 02 03 012 2 SMOKE DETECTOR 132KV GIS ROOM GROUP-1 LCC-E02 FIRE a a a a a a a a a a
13 02 03 013 2 SMOKE DETECTOR 132KV GIS ROOM GROUP-1 LCC-E01 FIRE a a a a a a a a a a
14 02 03 014 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
15 02 03 015 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
16 02 03 016 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
17 02 03 017 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a

2 of 5
RED FIRE ALARM SUBSTATION NAME: 132KV SUBSTATION UMM AL QUWAIN
DOC. NO. 12118.20/ABB/UAQ/M05/40428
AMBER SUPERVISORY & FAULT CONTRACT NO: 12118.2

GREEN DELUGE / SPRINKLER MAIN CONTRACTOR: ABB Industries (L.L.C) DUBAI BY APP BY SHEET

BLUE GAS RELEASED SUB CONTRACTOR: CORODEX AGENCIES CO. L.L.C U.N MR 1 OF 2

FACP PANEL FECP PANEL


SCADA SIGNALS SHUTDOWN RELAYS NOTIFICATION ANNUNCIATION
INDICATION INDICATION
INPUT DEIVICE ADDRESS
SERIAL NUMBER

Solenoid Release Respective Hazard


PANEL NO.

132KV BASEMENT VENTILATION


SPRIKLER SYSTEM OPERATED

Battery Room Exhause FAN ON


DELUGE SYSTEM OPERATED
DEVICE

FM-200 GAS / CLEAN AGENT


FIRE PROTECTION SYSTEM
ZONE

STATUS / INPUT

BASEMENT VENTILATION
BASEMENT LHD SYSTEM

HVAC SYSTEM-1 (132KV


LOCATION AND TYPE OF DEVICE

LV & CONTROL CABLE


FIRE ALARM COMMON

SOUNDER CIRCUIT # 1

SOUNDER CIRCUIT # 2
ACTION

FAULT / CPU FAULT

SOUNDER CIRCUIT

SOUNDER CIRCUIT

REPEATER PANEL
GAS DISCHARGE

HVAC SYSTEM-2
SUPERVISORY

SUPERVISORY

MIMIC PANEL
Second Stage

MAIN FACP
OPERATED

GIS ROOM)

First Stage
FAULT

FAULT
FIRE

FIRE
18 02 03 018 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
19 02 03 019 3 SMOKE DETECTOR CONTROL & RELAY ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
20 02 03 020 4 SMOKE DETECTOR SCADA/TELECOM ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
21 02 03 021 4 SMOKE DETECTOR SCADA/TELECOM ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
22 02 03 022 4 SMOKE DETECTOR SCADA/TELECOM ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
23 02 03 023 4 SMOKE DETECTOR SCADA/TELECOM ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
24 02 03 024 5 SMOKE DETECTOR LVAC & DC ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
25 02 03 025 5 SMOKE DETECTOR LVAC & DC ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
26 02 03 026 5 SMOKE DETECTOR LVAC & DC ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
27 02 03 027 5 SMOKE DETECTOR LVAC & DC ROOM - SMOKE DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
28 02 03 028 5 SMOKE DETECTOR LVAC & DC ROOM - SMOKE DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
29 02 03 029 6 HEAT DETECTOR BATTERY ROOM - HEAT DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
30 02 03 030 6 HEAT DETECTOR BATTERY ROOM - HEAT DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
31 02 03 031 6 HEAT DETECTOR BATTERY ROOM - HEAT DETECTOR (ROOM VOID) FIRE a a a a a a a a a a
32 02 03 032 6 HEAT DETECTOR BATTERY ROOM - HEAT DETECTOR (CEILING VOID) FIRE a a a a a a a a a a
<<END OF LOOP 3 >>

1 02 05 01,02 2 MONITOR MODULE 132KV GIS ROOM - MANUAL RELEASE - (GROUP-2) FIRE a a a a a a a a a a a a
2 02 05 003 2 MONITOR MODULE 132KV GIS ROOM - LOCK OFF SWITCH (GROUP-2) SUPERVISORY a a a a a a
3 02 05 007 2 MONITOR MODULE 132KV GIS ROOM - LOW PRESSURE SWITCH (MAIN) (GROUP-2) SUPERVISORY a a a a a a
4 02 05 008 2 MONITOR MODULE 132KV GIS ROOM - LOW PRESSURE SWITCH (RESERVE) (GROUP-2) SUPERVISORY a a a a a a
5 02 05 009 2 MONITOR MODULE 132KV GIS ROOM - SOLENOID CUTTER SUPERVISORY (MAIN) (GROUP-2) SUPERVISORY a a a a a a
6 02 05 010 2 MONITOR MODULE 132KV GIS ROOM - SOLENOID CUTTER SUPERVISORY (RESERVE) (GROUP-2) SUPERVISORY a a a a a a
7 02 05 011 2 MONITOR MODULE 132KV GIS ROOM - PRESSURE OPERATED SWITCH (GROUP-2) GAS DISCHARGE a a a a a a a a a a a
8 2 5 12,13 1 MONITOR MODULE 132KV GIS ROOM - MANUAL RELEASE (GROUP-1) FIRE a a a a a a a a a a a a
9 02 05 014 1 MONITOR MODULE 132KV GIS ROOM - LOCK OFF SWITCH (GROUP-1) SUPERVISORY a a a a a a

3 of 5
RED FIRE ALARM SUBSTATION NAME: 132KV SUBSTATION UMM AL QUWAIN
DOC. NO. 12118.20/ABB/UAQ/M05/40428
AMBER SUPERVISORY & FAULT CONTRACT NO: 12118.2

GREEN DELUGE / SPRINKLER MAIN CONTRACTOR: ABB Industries (L.L.C) DUBAI BY APP BY SHEET

BLUE GAS RELEASED SUB CONTRACTOR: CORODEX AGENCIES CO. L.L.C U.N MR 1 OF 2

FACP PANEL FECP PANEL


SCADA SIGNALS SHUTDOWN RELAYS NOTIFICATION ANNUNCIATION
INDICATION INDICATION
INPUT DEIVICE ADDRESS
SERIAL NUMBER

Solenoid Release Respective Hazard


PANEL NO.

132KV BASEMENT VENTILATION


SPRIKLER SYSTEM OPERATED

Battery Room Exhause FAN ON


DELUGE SYSTEM OPERATED
DEVICE

FM-200 GAS / CLEAN AGENT


FIRE PROTECTION SYSTEM
ZONE

STATUS / INPUT

BASEMENT VENTILATION
BASEMENT LHD SYSTEM

HVAC SYSTEM-1 (132KV


LOCATION AND TYPE OF DEVICE

LV & CONTROL CABLE


FIRE ALARM COMMON

SOUNDER CIRCUIT # 1

SOUNDER CIRCUIT # 2
ACTION

FAULT / CPU FAULT

SOUNDER CIRCUIT

SOUNDER CIRCUIT

REPEATER PANEL
GAS DISCHARGE

HVAC SYSTEM-2
SUPERVISORY

SUPERVISORY

MIMIC PANEL
Second Stage

MAIN FACP
OPERATED

GIS ROOM)

First Stage
FAULT

FAULT
FIRE

FIRE
10 2 5 15 1 MONITOR MODULE 132KV GIS ROOM - LOW PRESSURE SWITCH (MAIN) (GROUP-1) SUPERVISORY a a a a a a
11 02 05 016 1 MONITOR MODULE 132KV GIS ROOM - LOW PRESSURE SWITCH (RESERVE) (GROUP-1) SUPERVISORY a a a a a a
12 02 05 017 1 MONITOR MODULE 132KV GIS ROOM - SOLENOID CUTTER SUPERVISORY (MAIN) (GROUP-1) SUPERVISORY a a a a a a
13 02 05 018 1 MONITOR MODULE 132KV GIS ROOM - SOLENOID CUTTER SUPERVISORY (GROUP-1) SUPERVISORY a a a a a a
14 02 05 021 1 MONITOR MODULE 132KV GIS ROOM - MRTS RESERVE MODE INDICATION SUPERVISORY a a a a a a
15 02 05 022 1 MONITOR MODULE 132KV GIS ROOM - OFF INDICATION TO FECP TO LCC CUBICAL (01 TO 05) (GROUP-1) SUPERVISORY a a a a a a
16 02 05 023 2 MONITOR MODULE 132KV GIS ROOM - OFF INDICATION TO FECP TO LCC CUBICAL (6 TO 13) (GROUP-2) SUPERVISORY a a a a a a
17 02 05 024 1 MONITOR MODULE 132KV GIS ROOM - PRESSURE OPERATED SWITCH (GROUP-1) GAS DISCHARGE a a a a a a a a a a a
18 02 05 27,28 3 MONITOR MODULE CONTROL & RELAY ROOM - ABORT STATION SUPERVISORY a a a a a a
19 02 05 29,30 3 MONITOR MODULE CONTROL & RELAY ROOM - MANUAL RELEASE FIRE a a a a a a a a a a a a
20 02 05 031 3 MONITOR MODULE CONTROL & RELAY ROOM - LOCK OFF SWITCH SUPERVISORY a a a a a a
21 02 05 033 3 MONITOR MODULE CONTROL & RELAY ROOM - LOW PRESSURE SWITCH SUPERVISORY a a a a a a
22 02 05 035 3 MONITOR MODULE CONTROL & RELAY ROOM - SOLENOID CUTTER SUPERVISORY SUPERVISORY a a a a a a
23 02 05 036 3 MONITOR MODULE CONTROL & RELAY ROOM - PRESSURE OPERATED SWITCH GAS DISCHARGE a a a a a a a a a a a
24 02 05 39,40 3 MONITOR MODULE CONTROL & RELAY ROOM - ABORT STATION SUPERVISORY a a a a a a
26 02 05 41,42 3 MONITOR MODULE CONTROL & RELAY ROOM - MANUAL RELEASE FIRE a a a a a a a a a a a a
27 02 05 043 3 MONITOR MODULE CONTROL & RELAY ROOM - LOCK OFF SWITCH SUPERVISORY a a a a a a
28 02 05 46,47 4 MONITOR MODULE SCADA/TELECOM ROOM - ABORT STATION SUPERVISORY a a a a a a
29 02 05 48,49 4 MONITOR MODULE SCADA/TELECOM ROOM - MANUAL RELEASE FIRE a a a a a a a a a a a a
30 02 05 050 4 MONITOR MODULE SCADA/TELECOM ROOM - LOCK OFF SWITCH SUPERVISORY a a a a a a
31 02 05 052 4 MONITOR MODULE SCADA/TELECOM ROOM - LOW PRESSURE SWITCH SUPERVISORY a a a a a a
32 02 05 054 4 MONITOR MODULE SCADA/TELECOM ROOM - SOLENOID CUTTER SUPERVISORY SUPERVISORY a a a a a a
33 02 05 055 4 MONITOR MODULE SCADA/TELECOM ROOM - PRESSURE OPERATED SWITCH GAS DISCHARGE a a a a a a a a a a a
34 02 05 58,59 5 MONITOR MODULE LVAC & DC ROOM - ABORT STATION SUPERVISORY a a a a a a
35 02 05 60,61 5 MONITOR MODULE LVAC & DC ROOM - MANUAL RELEASE FIRE a a a a a a a a a a a a

4 of 5
RED FIRE ALARM SUBSTATION NAME: 132KV SUBSTATION UMM AL QUWAIN
DOC. NO. 12118.20/ABB/UAQ/M05/40428
AMBER SUPERVISORY & FAULT CONTRACT NO: 12118.2

GREEN DELUGE / SPRINKLER MAIN CONTRACTOR: ABB Industries (L.L.C) DUBAI BY APP BY SHEET

BLUE GAS RELEASED SUB CONTRACTOR: CORODEX AGENCIES CO. L.L.C U.N MR 1 OF 2

FACP PANEL FECP PANEL


SCADA SIGNALS SHUTDOWN RELAYS NOTIFICATION ANNUNCIATION
INDICATION INDICATION
INPUT DEIVICE ADDRESS
SERIAL NUMBER

Solenoid Release Respective Hazard


PANEL NO.

132KV BASEMENT VENTILATION


SPRIKLER SYSTEM OPERATED

Battery Room Exhause FAN ON


DELUGE SYSTEM OPERATED
DEVICE

FM-200 GAS / CLEAN AGENT


FIRE PROTECTION SYSTEM
ZONE

STATUS / INPUT

BASEMENT VENTILATION
BASEMENT LHD SYSTEM

HVAC SYSTEM-1 (132KV


LOCATION AND TYPE OF DEVICE

LV & CONTROL CABLE


FIRE ALARM COMMON

SOUNDER CIRCUIT # 1

SOUNDER CIRCUIT # 2
ACTION

FAULT / CPU FAULT

SOUNDER CIRCUIT

SOUNDER CIRCUIT

REPEATER PANEL
GAS DISCHARGE

HVAC SYSTEM-2
SUPERVISORY

SUPERVISORY

MIMIC PANEL
Second Stage

MAIN FACP
OPERATED

GIS ROOM)

First Stage
FAULT

FAULT
FIRE

FIRE
36 02 05 062 5 MONITOR MODULE LVAC & DC ROOM - LOCK OFF SWITCH SUPERVISORY a a a a a a
37 02 05 064 5 MONITOR MODULE LVAC & DC ROOM - LOW PRESSURE SWITCH SUPERVISORY a a a a a a
38 02 05 066 5 MONITOR MODULE LVAC & DC ROOM - SOLENOID CUTTER SUPERVISORY SUPERVISORY a a a a a a
39 02 05 067 5 MONITOR MODULE LVAC & DC ROOM - PRESSURE OPERATED SWITCH GAS DISCHARGE a a a a a a a a a a a
40 02 05 70,71 6 MONITOR MODULE BATTERY ROOM - ABORT STATION SUPERVISORY a a a a a a
41 02 05 72,73 6 MONITOR MODULE BATTERY ROOM - MANUAL RELEASE FIRE a a a a a a a a a a a a
42 02 05 074 6 MONITOR MODULE BATTERY ROOM - LOCK OFF SWITCH SUPERVISORY a a a a a a
43 02 05 076 6 MONITOR MODULE BATTERY ROOM - LOW PRESSURE SWITCH SUPERVISORY a a a a a a
45 02 05 078 6 MONITOR MODULE BATTERY ROOM - SOLENOID CUTTER SUPERVISORY SUPERVISORY a a a a a a
46 02 05 079 6 MONITOR MODULE BATTERY ROOM - PRESSURE OPERATED SWITCH GAS DISCHARGE a a a a a a a a a a a
<<END OF LOOP 5 >>

5 of 5
RED RED FIRE ALARM SUBSTATION NAME: 132KV SUBSTATION UMM AL QUWAIN
DOC. NO. 12118.20/ABB/UAQ/M05/40428
AMBER AMBER SUPERVISORY & FAULT CONTRACT NO: 12118.2
GREEN GREEN DELUGE / SPRINKLER MAIN CONTRACTOR: ABB Industries (L.L.C) DUBAI BY APP BY SHEET

BLUE BLUE GAS RELEASED SUB CONTRACTOR: CORODEX AGENCIES CO. L.L.C U.N MR 1 OF 2
FACP PANEL FECP PANEL
SCADA SIGNALS SHUTDOWN RELAYS NOTIFICATION ANNUNCIATION
INDICATION INDICATION

Solenoid Release Respective Hazard


132KV BASEMENT VENTILATION
SPRIKLER SYSTEM OPERATED

Battery Room Exhause FAN ON


DELUGE SYSTEM OPERATED
INPUT DEIVICE ADDRESS

FM-200 GAS / CLEAN AGENT


FIRE PROTECTION SYSTEM

BASEMENT VENTILATION
BASEMENT LHD SYSTEM

HVAC SYSTEM-1 (132KV

LV & CONTROL CABLE


FIRE ALARM COMMON

SOUNDER CIRCUIT # 1

SOUNDER CIRCUIT # 2
FAULT / CPU FAULT
SERIAL NUMBER

SOUNDER CIRCUIT

SOUNDER CIRCUIT

REPEATER PANEL
GAS DISCHARGE

HVAC SYSTEM-2
SUPERVISORY

SUPERVISORY

Second Stage

MIMIC PANEL
PANEL NO.

OPERATED

MAIN FACP
GIS ROOM)

First Stage
DEVICE

LOCATION AND TYPE OF DEVICE Status/Output Action

FAULT

FAULT
ZONE

FIRE

FIRE
Status/Input Action

1 02 01 1 TO 8 SMOKE DETECTOR
132KV GIS ROOM (LCC CUBICAL INSIDE) -GROUP-2 SYSTEM
1 CROSS ZONE DETECTOR ACTIVATE
E6 - E13
FIRE a a a a a a a a a a a a
2 02 03 1 TO 8 SMOKE DETECTOR

1 02 01 9 TO 13 SMOKE DETECTOR
132KV GIS ROOM (LCC CUBICAL INSIDE) -GROUP-1 SYSTEM
2 CROSS ZONE DETECTOR ACTIVATE
E1 - E5
FIRE a a a a a a a a a a a a
2 02 03 9 TO 13 SMOKE DETECTOR

1 02 01 14 TO 19 SMOKE DETECTOR
3 CROSS ZONE DETECTOR ACTIVATE CONTROL & RELAY ROOM FIRE a a a a a a a a a a a a
2 02 03 14 TO 19 SMOKE DETECTOR

1 02 01 20 TO 23 SMOKE DETECTOR
4 CROSS ZONE DETECTOR ACTIVATE SCADA/TELECOM ROOM FIRE a a a a a a a a a a a a
2 02 03 20 TO 23 SMOKE DETECTOR

1 02 01 24 TO 28 SMOKE DETECTOR
5 CROSS ZONE DETECTOR ACTIVATE LVAC & DC ROOM FIRE a a a a a a a a a a a a
2 02 03 24 TO 28 SMOKE DETECTOR

1 02 01 29 TO 32 HEAT DETECTOR
6 CROSS ZONE DETECTOR ACTIVATE BATTERY ROOM FIRE a a a a a a a a a a a a
2 02 03 29 TO 32 HEAT DETECTOR

DISCHARGE PRESSURE SWITCH 132KV GIS ROOM (LCC CUBICAL INSIDE) -GROUP-2 SYSTEM
1 02 05 011 MONITOR MODULE 2
ACTIVATE E6 - E13
GAS DISCHARGE a a a a a a a a a a a
DISCHARGE PRESSURE SWITCH 132KV GIS ROOM (LCC CUBICAL INSIDE) -GROUP-1 SYSTEM
2 02 05 024 MONITOR MODULE 1
ACTIVATE E1 - E5
GAS DISCHARGE a a a a a a a a a a a
DISCHARGE PRESSURE SWITCH
3 02 05 036 MONITOR MODULE 3
ACTIVATE
CONTROL & RELAY ROOM GAS DISCHARGE a a a a a a a a a a a
DISCHARGE PRESSURE SWITCH
4 02 05 055 MONITOR MODULE 4
ACTIVATE
SCADA/TELECOM ROOM GAS DISCHARGE a a a a a a a a a a a
DISCHARGE PRESSURE SWITCH
5 02 05 067 MONITOR MODULE 5
ACTIVATE
LVAC & DC ROOM GAS DISCHARGE a a a a a a a a a a a
DISCHARGE PRESSURE SWITCH
6 02 05 079 MONITOR MODULE 6
ACTIVATE
BATTERY ROOM GAS DISCHARGE a a a a a a a a a a a