Standard PCCP Control System For QSM11 Series With CM570 Module
Standard PCCP Control System For QSM11 Series With CM570 Module
Standard PCCP Control System For QSM11 Series With CM570 Module
FOREWORD
The purpose of this manual is to provide the users with sound, general information. It is for
guidance and assistance with recommendations for correct and safe procedures. Cummins Power
Generation Limited cannot accept any liability whatsoever for problems arising as a result of
following recommendations in this manual.
The information contained within the manual is based on information available at the time of going
to print. In line with the Cummins Power Generation Limited policy of continual development and
improvement, information may change at any time without notice. The users should therefore
ensure that before commencing any work, they have the latest information available.
Users are respectfully advised that it is their responsibility to employ competent persons to carry
out any installation work in the interests of good practice and safety. It is essential that the utmost
care is taken with the application, installation and operation of any diesel engine due to their
potentially dangerous nature. Careful reference should also be made to other Cummins Power
Generation Limited literature, in particular the engine Operation and Maintenance Manual.
CONTENTS
Section Title Page
2 Introduction.......................................................................................................... 2-1
2.1 General.......................................................................................................................2-1
2.2 Generating Set Identification .......................................................................................2-1
2.3 After Sales Services....................................................................................................2-2
2.3.1 Maintenance .........................................................................................................2-2
2.3.2 Warranty ...............................................................................................................2-2
2.3.3 Spares ..................................................................................................................2-2
2.3.4 Overseas...............................................................................................................2-2
Contents Page i
Publication 3544(GB) Standard PCCP Control Systems
for QSM11 Series with CM570 Module
CONTENTS (continued)
Section Title Page
4 Operation ..............................................................................................................4-1
4.1 Safety ........................................................................................................................ 4-1
4.2 Introduction................................................................................................................. 4-1
4.3 Maintenance............................................................................................................... 4-1
4.3.1 Control Mode Definitions....................................................................................... 4-2
4.4 Functional Description ................................................................................................ 4-3
4.4.1 Sequence of Operation ......................................................................................... 4-3
4.4.2 Control Panel ........................................................................................................ 4-4
4.4.3 Emergency Stop Controls ................................................................................... 4-20
4.5 Start / Run Procedures ............................................................................................. 4-21
4.5.1 Operating Options............................................................................................... 4-21
4.5.2 Lockout ............................................................................................................... 4-22
4.5.3 Manual Start Procedure ...................................................................................... 4-23
4.6 Paralleling................................................................................................................. 4-24
4.6.1 Speed and Voltage Matching .............................................................................. 4-24
4.6.2 Operation When in Parallel ................................................................................. 4-24
4.7 Shutdown Procedures .............................................................................................. 4-25
4.7.1 Normal Stop........................................................................................................ 4-25
4.7.2 Emergency Stop ................................................................................................. 4-25
4.7.3 Emergency Stop Reset ....................................................................................... 4-26
4.8 Locking the Genset Out of Service ........................................................................... 4-27
4.8.1 Introduction......................................................................................................... 4-27
4.8.2 Immobilising the Plant for Safe Working.............................................................. 4-27
Page ii Contents
Standard PCCP Control Systems Publication 3544(GB)
for QSM11 Series with CM570 Module
CONTENTS (continued)
Section Title Page
5 Maintenance......................................................................................................... 5-1
CONTENTS (continued)
Illustrations
Figure Title Page
Tables
Figure Title Page
Supplementary Publications
The Supplementary Publications appropriate to your system will also be supplied with the system.
Where appropriate the corresponding Instruction Manual(s) will also be supplied with any
accessory that you order.
Page iv Contents
Standard PCCP Control Systems Publication 3544(GB)
for QSM11 Series with CM570 Module
Schedule of Abbreviations
AC Alternating Current MCB Miniature Circuit Breaker
ACB Air Circuit Breaker MCCB Moulded Case Circuit Breaker
ACH Anti-Condensation Heaters MF Mains Failed
ATS Automatic Transfer Switch MFSS Master First Start Sensor
AVR Automatic Voltage Regulator MR Mains Returned
MST Mains Sensing Transformer
BHP Brake Horsepower MSU Mains Sensing Unit
BMS Building Management System MV Medium Voltage
BST Busbar Sensing Transformer
NEC Neutral Earthing Contact
CB Circuit Breaker
TM
CCA Cold Cranking Amps PCCP PowerCommand Control Paralleling
CHP Combined Heat and Power PCL A low cost control system
COP Continuous Power Rating PF Power Factor
CT Current Transformer PFC Power Factor Controller
PLC Programmable Logic Controller
dB(A) Unit of noise level PMG Permanent Magnet Generator
DC Direct Current PRP Prime Power Rating
DIP Dual In-line Package PSU Power Supply Unit
DMC Digital Master Controlä PT/CT Potential Transformer / Current Transformer
DMSU Demand Load Standby Unit
QCC Quadrature Current Control
EMCU Engine Monitoring and Control Unit
EMF Electromotive Force RFI Radio Frequency Interference
EPU Engine Protection Unit RMS Root Mean Square
RPM Revolutions Per Minute
FSS First Start Sensor RTD Resistive Temperature Detector
Note: A short piece of text giving information that augments the current text.
1.2 Warnings
1.2.1 Electricity
1.2.3 Maintenance
Caution: If the engine has been running recently, explosive gases (given off
during battery charging) may be present in the vicinity of the batteries.
Ensure the area is well ventilated before disconnecting batteries.
1. Turn the Mode switch (S12) on the PCCP front panel to OFF.
OFF
RUN AUTO
2. Isolate and lock off the supply to the battery charger, where fitted.
3. Disconnect the starting batteries and control system batteries, (if separate).
4. Isolate and lock off the heater control box, where fitted.
5. Isolate the fuel supply to the engine.
6. Fit Warning notices at each of the above points to indicate Maintenance in Progress
– Plant Immobilised for Safe Working.
The procedure for reinstatement is the reverse of the procedure for isolation.
Before operating the genset, read this manual and become familiar with the equipment
and its operation (including all controls, manually operated valves and shutdown devices).
Correct operation and maintenance is essential for safe and efficient operation of this
unit.
Read and become familiar with the Safety Precautions listed in this section. Many
accidents result from a failure to observe fundamental safety rules and precautions.
There are many potential hazards that can occur during the operation of a genset, which
cannot always be anticipated. Therefore a warning cannot be included in the manual for
every possible circumstance that might involve a potential hazard.
Should a procedure be used that has not been specifically recommended, then the
personnel involved must be satisfied that it is safe and will not damage the genset.
NO RADIO FREQUENCY
COMMUNICATIONS EQUIPMENT
MAY BE OPERATED IN THE
VICINITY OF THIS APPARATUS
1.6 Standards
The genset and its control system has been designed, constructed and tested generally
in accordance with the following Standards where applicable:
KEY:
1. A related, but not equivalent, standard: A BSI publication, the content of which to any extent
at all, short of complete identity or technical equivalence, covers subject matters similar to
that covered by a corresponding international standard.
2. An identical standard: A BSI publication identical in every detail with a corresponding
international standard.
Exhaust fumes are toxic and all necessary measures must be taken to ensure
that they do not escape into, or re-circulate within, the plant room or associated
buildings.
Visually and audibly inspect the exhaust system as detailed in the Maintenance
Schedule. Ensure that all exhaust components are secured and true (not
warped).
Ensure that the genset is kept well ventilated. Thoroughly ventilate the genset
plant room to remove all fumes and explosive vapours before disconnecting or
connecting battery cables thus reducing the possibility of accidental sparks
causing an explosion.
Should repeated attempts to start the engine fail, unburnt fuel gas may build up
in the exhaust system creating a potentially dangerous situation. Allow these
gases to disperse before carrying out further attempts to start.
Benzene and lead, found in some diesel oils, have been identified as causing
cancer or reproductive toxicity. When checking, draining or adding diesel, take
care not to ingest, breathe the fumes, or contact diesel.
Used engine oils have been identified as causing cancer or reproductive toxicity.
When checking or changing engine oil, take care not to ingest, breathe the
fumes, or contact used oil.
With the use of fuel, lubricating oils and batteries, there is a fire hazard. Naked
flames or sparks should not be allowed near the genset, fuel tank and battery.
Explosive fuel and oil vapours are always present in the vicinity of a genset,
while a battery on charge can produce inflammable hydrogen gas.
Ensure that adequate ventilation is maintained within the plant room at all times.
Thoroughly ventilate the genset plant room to remove all fumes and explosive
vapours before disconnecting or connecting battery cables thus reducing the
possibility of accidental sparks causing an explosion.
In the event of a fuel or oil leak, the spillage should be absorbed using a
proprietary material (e.g. Fuller’s Earth granules, or similar). Sawdust should not
be used, as this will create a fire hazard. Appropriate fire fighting equipment
should be readily available - (CO2 or BCF type fire extinguishers are
recommended).
Inspect the fuel system before each operation and periodically while running.
Keep a fire extinguisher available in or near the plant room and in other areas
throughout the site. Use the correct extinguisher for the area.
Safety guards and covers must be securely fitted and all cubicle doors, cover-
plates, etc, should be firmly in place while the genset is in operation.
Keep hands and loose clothing away from moving parts. Do not wear jewellery
while servicing any part of the genset.
Never step on the genset. It can stress and break unit components, possibly
resulting in dangerous operating conditions – from leaking fuel, leaking exhaust
fumes, etc.
While the genset is running, and for a period following shutdown, avoid contact
with exhaust, radiator and other components that are likely to become hot. At all
times, avoid contact with hot oil, hot coolant and hot exhaust gases.
DO NOT drain coolant or lubricating oil until the genset has cooled completely.
The genset should be connected only to loads compatible with its electrical
characteristics and rated output.
Only suitably trained and qualified engineers, who are authorised to do so,
should connect the genset load. Connection must also be in compliance with
relevant codes and standards.
The metalwork of the generating plant, bed frame and other exposed parts must
be bonded to an effective earth point.
Do not touch any electrically energised parts of the genset or cables / conductors
with any part of the body or with any non electrically insulated object.
Do not operate the genset with any terminal box cover open.
Ensure that all electrical equipment and connections are kept clean and dry.
Replace any defective terminal covers and wiring immediately and ensure that
all terminations are secure.
Before carrying out any maintenance, isolate all supplies to the genset and any
control panels. Render the genset inoperative by disconnecting the plant battery
- see also Section 4.8 Locking the Genset Out of Service.
1.8.7 Noise
1.8.8 General
Information on first aid procedures and facilities should be displayed near the
plant.
The area around the genset should be clear of obstructions and dangerous
objects. In addition, the floor should be kept clean, dry and clear of oil deposits.
Never lift the genset using the engine or alternator lifting lugs. Refer to the lifting
recommendation drawings “Lifting Ilus” series.
1.8.9 Fluids
There is a health risk associated with exposure to fuel, lubricating oils, coolant
additives and battery electrolyte. Avoid contact with these fluids and always wear
the appropriate personal protective equipment. Reference should be made to the
(Control of Substances Hazardous to Health) COSHH Publication No. 3334,
supplied with this manual.
Avoid fluid spillage and discard clothing contaminated by fuel oil, coolant,
lubricants or battery electrolyte.
Ensure that remote fuel storage systems are installed in compliance with
relevant codes, standards and local requirements.
The user should also contact their supplier of fluids used in the genset for
Manufacturers’ recommendation on Health & Safety.
SECTION 2 - INTRODUCTION
2 Introduction
2.1 General
Before any attempt is made to operate the generator, the user should take time to read
this manual and to familiarise him or herself with the Warnings and Operating
Procedures.
2.3.1 Maintenance
For customers who wish to have their gensets expertly serviced at regular intervals the
Customer Service Department offers a complete maintenance contract package. This
covers all items subject to routine maintenance and includes a detailed report on the
condition of the set. In addition, this can be linked to a 24-hour call-out arrangement,
providing assistance 365 days a year if necessary. Specialist engineers are available to
maintain optimum performance levels from customer’s gensets, and it is recommended
that maintenance tasks are only undertaken by trained and experienced engineers
provided by the Customer Service Department.
2.3.2 Warranty
All gensets have a twelve months warranty from the commissioning date as standard.
Extended warranty coverage is also available. In the event of a breakdown prompt
assistance can normally be given by factory trained service engineers with facilities to
undertake all minor and many major repairs to equipment on site.
2.3.3 Spares
An extensive Spare Parts Department is available for any emergency breakdown and for
the engineer who carries out his own routine maintenance.
Please quote Plant Nos., Serial Nos., and Part Nos. when ordering spares.
2.3.4 Overseas
Agents and representatives in almost 100 countries throughout the world offer installation
and after sales service for the equipment provided. We can provide the name and
address of the agent for your specific location.
3 System Description
3.1 Generator Components
The main components of the Generator System are shown below. Refer to the Engine
and Alternator Manuals for location of other components, e.g. oil filler, dipstick, etc.
Various options are available although they may not be available for all models.
Note that the Load Terminal Box, item 9, is mounted optionally on the left or right side
and includes the load connection gland plate (with optional entry point location).
KEY:
3.1.1 Engine
All generators employ a 4-stroke, water-cooled engine and incorporate a governor control
and full engine protection system. Refer to the Generating Set Rating Plate for engine
type and rating details.
For further information refer to the Engine manufacturer’s Operation and Maintenance
Manual supplied with this manual.
3.1.2 Alternator
All generator types use AC alternators of a brushless, rotating field design, which
eliminates the maintenance associated with slip rings and brushes. Refer to the
Generating Set Rating Plate for alternator type and rating details.
For further information refer to the Alternator manufacturer’s Installation, Service and
Maintenance Manual supplied with this manual.
Free standing main tanks with stands providing 450, 900 and 1350 litre capacity are
available as options.
Free standing fuel tanks can be filled manually using an optional hand fuel transfer pump.
Alternatively, fuel tanks (base tank or free standing) can be filled automatically using an
electrical fuel transfer pump. This pump, which is supplied complete with starter, operates
under the control of Low and High Fuel Level switches fitted to the tank.
On automatically filled systems, the base tank filler cap is replaced with an overflow /
breather connection to allow piping to a safe area or return to a bulk tank.
Optional Set-mounted fuel / water separators are available to provide protection for the
engine fuel injection system where water-free fuel supplies cannot be guaranteed.
Battery type, size and voltage are selected to suit the generator capacity and application
on ordering and include lead acid and NiCad types. (All types are options).
Lead acid batteries are Set-mounted. NiCad batteries are free standing.
Optional single phase, mains powered battery chargers, which can be panel or wall
mounted, are available to maintain the battery in a charged condition when the generator
is not running.
All customer control connections, and the external modules which act as interface
modules between the PCCP and the genset are inside the Accessory Box which is
mounted on the front face of the control housing. Situated in the Accessory Box are the
four modules required for the operation of the PCCP. These modules are:
Various genset parameters are measured by sensors, senders, RTDs etc and the
resulting signals are applied to the PCCP.
1. Fuel Ramping - Upon receiving the Start signal, the digital control system energises
the engine fuel system only enough to allow the engine to start. When the control
system senses that the engine has reached start disconnect speed, it gradually
increases fuel flow to ramp up engine speed, for controlled acceleration up to rated
operating conditions. This minimises black smoke emission and frequency overshoot,
as well as improving cold starting capability.
2. Fail to Crank - As the Start signal is initiated, the control system checks the speed
monitoring pick-up to check that the engine is rotating. If the engine is not rotating,
the control system switches off the starter and then makes two further attempts. If the
final attempt fails, a Shutdown message is signalled on the alphanumeric display and
the genset cannot be started until the fault is cleared. This process helps prevent
starter or ring gear damage.
3. Temperature Dynamic Governing - A temperature dynamic adjustment capability
enhances cold starting ability, and improves stability when the engine is cold starting,
by automatically adjusting governing characteristics based on engine temperature. It
also helps limit black smoke emission on cold starting.
4. Digital Excitation Control - The genset voltage regulation system is 3-phase
sensing and includes torque matching to provide enhanced load pick-up capability.
During starting, the control system ramps output voltage to rated value to minimise
voltage overshoot.
5. Cycle Cranking - The PCCP system includes a standard cycle cranking system,
which allows the operator to select continuous or cycle cranking mode. The operator
can select between three and six cranking cycles, and adjust the crank / rest times
between seven and twenty seconds. The standard setting is three cranking cycles,
with five seconds crank duration followed by ten seconds rest.
6. Battery Monitoring System - The PCCP system continuously monitors the battery
charging system for low and high DC voltage. Functions and messages include:
• Low DC voltage - battery voltage less than 24VDC (12VDC for 12V battery)
• High DC voltage - battery voltage greater than 32VDC (16VDC for 12V battery)
• Weak battery - main battery droop is monitored at start-up and, if the voltage
drops below 60% of nominal for more than two seconds, the indication will be
given
• First Start Sensor - provides a positive interlock to prevent multiple gensets from
simultaneously closing to a dead system bus. A back-up system is provided to
allow normal system operation in the event that the Primary First Start Sensor fails
• Common Warning alarm relay - Operates on all Warning conditions. Rated at 2A,
30VDC
• Common Shutdown alarm relay - Operates on all Shutdown conditions. Rated at
2A, 30VDC
• Ready to load relay - Operates when the genset reaches 90% of rated voltage and
frequency. Rated at 2A, 30VDC
• Auxiliary Run relays (up to 3 optional) - Each relay is rated at 2A, 30VDC
• Breaker operation contacts - Provide breaker open and breaker close signals for a
paralleling circuit. Rated at 5A, 30VDC
• Load shed relay - Operates for a specified period of time when an Overload warning
occurs. Rated at 6A, 30VDC
3.2.6 DC Power
The PCCP system is powered by the genset’s battery system. The control system will
function over a voltage range between 8 and 34VDC.
• Overcurrent
• Short circuit
• Over / under voltage
• Over / under frequency
• Overload
• Reverse power
• Loss of excitation
• Alternator phase rotation
• Paralleling circuit breaker failure to close
Current flow is regulated to 300% for both single phase and 3-phase faults when a short
circuit condition is sensed.
If the genset is operating for an extended period at a potentially damaging current flow
level, an Overcurrent alarm will sound to warn the operator of an impending problem
before it causes a system failure. If an Overcurrent condition persists for the time pre-
programmed in the time current characteristic for the alternator, the permanent magnet
generator (PMG) excitation system is de-energised, avoiding alternator damage. The
Overcurrent protection is time delayed in accordance with the alternator thermal capacity.
This allows current to flow until secondary fuses or circuit breakers operate, isolating the
fault and thus achieving selective co-ordination (discrimination).
After the fault is cleared, AmpSentryTM Protection softly loads the genset by controlled
ramping of output voltage to rated level, allowing the genset to resume normal operation
without a potentially damaging voltage overshoot.
Fixed over / under voltage and under frequency time delayed set points also provide a
degree of protection for load equipment. Over / under voltage conditions trigger a
Shutdown message on the alphanumeric display; and under frequency conditions prompt
both a Warning and Shutdown message, depending on the length of time and magnitude
of variance under rated frequency.
AmpSentryTM Protection includes an overload signal that can be used in conjunction with
transfer switches or Master Controls to automatically shed load, preventing a potential
genset Shutdown. The overload signal is programmable for operation at a specific kW
level, on the basis of an under frequency condition.
AmpSentryTM Protection for paralleling also includes protection for genset reverse power,
loss of excitation, alternator phase rotation and circuit breaker failure to close. It includes
permissive (synchronising check) functions for automatic and manual breaker closure
operations.
1. Does the generator FL current monitored change within PCCP for voltage
settings?
Yes! The control system uses the genset kW rating and voltage to calculate rated
current and reset the position of the protection curve within the control system. The
control system will use the highest current found on any phase as a basis for the over
current actions taken by the control.
2. When the set is selected and entered into PCCP along with the voltage, how is
the trip curve changed to accommodate the current which is derived from the
kVA and voltage?
The actual algorithms and operating system that we use to get to the trip
performance shown on R1053 are proprietary. However, you can think of the
protection as operating in a similar fashion to that shown on the protection curve.
Protection on various units within an alternator family is performed as a function of
multiples of the steady state current rating. So, as the current rating changes, the
curve automatically shifts to compensate for it.
3. For a given over load current would you expect the alarm position to be given
on the R1053 curve or in some place to the left of the curve?
The over current pre-alarm point is fixed at 110% and 60 seconds. The Shutdown
point is defined by the curve shown on R1053. The genset will Shutdown at the
point shown on the curve, with the only deviations to this due to the calibration
and/or accuracy of the CTs driving the system. Note that the CTs are selected to
allow them to not saturate at five times rated current, so that they can provide
accurate readings when the system is running in an over current condition. Note also
that the algorithms in the control have integrating functions which result in the control
reducing the time to trip if you have consecutive faults applied to the system. To
completely reset the control you would need to wait for at least six minutes before
another fault or test was commenced in order to get an accurate reading of trip time
on a specific event.
4. For a 175% and above current would you expect to see the trip point on the
curve or to the left of the curve? I assume these levels are closer to the curve.
Again, I would expect the unit to trip at the point shown on the curve, not to the right
or left of it.
5. Why is the horizontal trip area starting at 4 x FLI when the genset only
manages 3 X FLI as a maintained current?
The protection curve was drawn based on the thermal capabilities of the alternator,
not the ability of the alternator to produce current. We purposely drew the protection
curve as close to the damage curve as practical, to minimise the possibility of
nuisance tripping, and facilitate discrimination with downstream devices. The curve
goes horizontal at the point shown because it is the point of maximum output current
for the alternator, and to continue dropping the curve would have no meaning or
purpose.
It is worth noting that another significant difference between PCCP and other control
systems is that PCCP measures and regulates fault current. In other systems, the
voltage regulator will switch to full field operation on a fault, and the magnitude of
fault current that you actually get is determined by the physical capabilities of the
machine. Consequently, in non-PCCP machines it is not uncommon for the value of
fault current provided to be somewhat more or less than the 300% level which is
commonly specified. With PCCP, you will get 300%, because the output of the
system is regulated to that level, in a very similar fashion to the way that voltage is
regulated on normal operation conditions.
7. For single phase faults, does the time get multiplied up for the extra heating
effect such a fault has on the alternator?
No! Prototype testing that we did on the system, which included applying bolted
faults to machines and measuring temperature rise in the alternators, did not indicate
a need to modify the over current algorithms for single phase operation.
8. What happens when the set is de-rated and the output drops? I assume here
that protection carries on for the 40°C rated product ratings.
When you go to de-rate the genset for altitude or temperature, we don't move the
protection curve, so the situation is similar to that noted in question number seven
above--the protection gets more conservative. However, if you actually plot the
differences on the curve, you will see that there is not a very significant impact in the
location of the damage curve and the protection provided by the control.
Note that most of the problems of discrimination revolve around interference in the
instantaneous region of the breaker curves. Since the AmpSentryTM curve goes
horizontal at 0.6 seconds, and most breakers have instantaneous set at around 0.05
seconds max, there is a lot of room for discrimination that you can't get in any other
way. Even if the downstream breakers have long time ratings as long as 30 cycles,
PCCP will allow discrimination between PCCP and the first downstream device(s).
10. We do not show or display anywhere what our settings are. They are not
visible on the genset control.
We do provide R1053 to describe the performance of the over current protection
system, and allow customers and designers to verify system co-ordination. Unlike
circuit breaker applications where a single protective device may be applied to many
different situations, we have the luxury of only having to protect our machines, so
there is no real need for adjustment in the over current protection and a single
protective function curve can always be used to describe performance. We have
tested the control system with actual short circuits of varying magnitude on real
gensets, and also with current injection tests witnessed by third party authorities and
proved that the control system functions as shown on our documentation. Since we
are talking about processor-based control here, it's practically impossible that the
control would fail to function properly, unless the inputs to the control are not
performing properly. (In other words, the CTs are not properly calibrated, or are not
working right due to improper sizing, etc.) Also, there are some cumulative functions
in the control that result in faster tripping under conditions where repeated faults hit
the control.
11. Does every customer test the current trips and plot his curve to know where he
is?
No! The customer is best served by using our curves.
12. Are you saying the curve is reliable and he does not need to test? If you are,
then supportive data is needed for each control to present to the customer
showing the performance against the output conditions.
Yes, the curve is a reliable depiction of actual unit operation. We are proceeding with
third party certification of the performance of the control system as part of our effort
to get UL2200 listing of the product. At that point testing at your site to verify
This is one function that is easy to test in the control, because by simply reversing
the CT wiring you can make the control think that positive power output is reverse
power. So, in the future, when you test for reverse power, I'd suggest that you use
that means rather than a current injection test.
A remote access, single-site version of PCCP is provided for each site. Alternatively, one
remote access, multi-site version of PCCP can be provided for a host monitoring
computer.
A separate Earth Fault Reset button is provided on the control housing to allow resetting
of an earth fault alarm. The resulting Shutdown indication on the control unit must be
reset, using the Reset membrane switch on the front panel - see Section 4 - Operation.
Up to 1250A generator rating circuit breakers are installed in a Set-mounted load box
which is close coupled to the alternator output terminal box. Customer cables are fed to
the circuit breaker via a bottom or side exit gland plate.
Above 1250A generator rating circuit breakers are installed in a free-standing enclosure.
With this arrangement the control panel remains Set-mounted using resilient mountings to
reduce vibration.
3.4 Heaters
Caution: Heater(s) must not be energised if the coolant system has been
drained.
Caution: The engine heater is in no way intended to protect the engine and
cooling system from freezing in sub zero conditions. If there is any
danger from freezing, then a suitable antifreeze agent must be added to
the cooling system.
The alternator heater is supplied with power via the Engine Heater Isolator switch, which
should normally be left in the On position as heater operation is controlled automatically
by a relay and thermostat. The relay is controlled by the PCCP.
If the charger is fitted with a Boost Charge switch, the Boost position should be selected
at intervals detailed by the battery manufacturer (normally around every six months).
Caution: Batteries should not be left on Boost Charge for extended periods as
this will result in excessive water consumption, gassing and may impair
battery performance.
4 Operation
4.1 Safety
Only suitably qualified and experienced personnel should carry out genset operations.
Before operating the system, the operator should become familiar with Section 1 of this
manual – Preliminary and Safety instructions. Observe the following WARNINGS and
CAUTIONS at all times.
Caution: Only technically qualified personnel should open the PCCP front panel.
Lower level voltages (18VAC to 24VAC) are present in the PCCP which
can cause electrical shock, resulting in personnel injury.
Even with power removed, improper handling of components can cause
electrostatic discharge and damage circuit board components.
4.2 Introduction
This section describes the control settings required for operation of the genset, and the
sequences that occur during generator Start-up and Running. Normal and Emergency
Stop procedures are described, together with Alarm and Shutdown procedures, and
controls. The text should be read in conjunction with the System Description, and the
Engine and Alternator Operating Manuals.
4.3 Maintenance
To secure maximum performance and reliability from your genset it is essential that
certain components are inspected periodically and, where necessary, maintenance
procedures carried out as detailed in Section 5 - Maintenance.
Initiating Condition /
Control Mode Definition Generator Load
Reset
Normal Stop A stop initiated Stop with PCCP Auto ramping down of
manually during STOP switch. load before stopping.
normal genset Manually reset any
running. alarm at PCCP
before restart.
Alarm Alarm condition Non critical alarm Loading maintained.
with alarm condition. Alarm reset
indication / horn / at PCCP.
beacon.
Controlled Alarm condition Alarm requiring Auto ramping down of
Shutdown with alarm controlled engine load.
indication / horn / stop. Switch off &
beacon. manually reset at
PCCP before restart.
Immediate Critical alarm Critical alarm All of load dumped with
Shutdown condition with condition. Switch off immediate engine
immediate engine & manually reset at shutdown
stop alarm PCCP before restart.
indication / horn /
beacon.
Lockout Engine inhibited Start inhibit due to Load previously
from starting with critical fault condition. removed. Engine
alarm indication / Reset at PCCP when stopped
horn / beacon. alarm condition is
clear.
Table 4-1 Control Mode Definitions
When the PCCP is put in the Run mode, the genset performs an automatically
sequenced manual start. When the PCCP is put in the Auto mode, the genset performs
an automatically sequenced start when initiated by a start signal from a remote device.
First, the PCCP initiates a starter cranking signal and verifies that the engine is rotating.
Then it provides sufficient fuel to the engine to accelerate to start-disconnect speed.
After the initial start procedure, the control system ramps the genset to rated speed and
voltage. On reaching rated speed and voltage, the PCCP checks the system bus voltage.
If the genset is working in a multiple (paralleling) genset installation and no bus voltage is
present, it waits for a pulse from a remote Master First Start Sensor (MFSS). On receiving
that pulse, the control will signal the paralleling breaker to close.
If bus voltage is present, the PCCP checks for proper phase rotation, adjusts the genset
to the bus voltage and frequency level, and then synchronises the genset to the system
bus automatically. When a synchronised condition is achieved, PCCP will send a signal
to close the paralleling breaker and the genset will assume its proportional share of the
total load on the system bus.
1 2 3 4
5
16
6
15
14
7
13
12 11 10 9
The illustration shows the PCCP’s alphanumeric display and the menu selection
membrane switches. Refer to section 4.4.2.1 Front Panel, which describes the display
and all the switches.
ENGINE GEN
ADJUST >>
RESET MENU
In the Standby (sleep) Mode, to activate and view the menu displays without starting the
genset, press and release the Self-Test membrane switch (see Front Panel illustration).
This will initialise the PCCP operating software and permit operation of the menu display
panel. If no menu selections are made, a software timer will shutdown the display after 30
seconds.
In the Power On (awake) Mode, power is continuously supplied to the control panel and
the alphanumeric display will remain on.
Note: In the alphanumeric display, the >> symbol indicates that selecting the adjacent
membrane switch causes the operating program to branch to the next menu
display as shown in the menu diagrams.
Note: The << symbol indicates that selecting the adjacent membrane switch causes
the operating program to return to the previous menu displayed.
The facing page shows the Main Menu and a block representation of the menu tree,
including all available sub-menus. Initially the alphanumeric display shows the titles in the
central block (i.e. Engine, Gen, Adjust, >>). Pressing a membrane switch next to a title
displays the next indication in the tree.
As shown in the diagram, the Main Menu can branch into one of four directions:
1. Engine: To display engine parameters, such as oil pressure and temperature, water
temperature, engine speed (RPM), and exhaust temperature, press the membrane
switch next to the word Engine in the display. Refer to Engine menu.
2. Gen: To display generator parameters, such as volts, amps, power (kW), and
frequency, press the membrane switch next to the word Gen in the display. Bus
voltage, frequency and a digital synchroscope can also be viewed from this menu
branch. Refer to Gen menu.
3. Adjust: To adjust output voltage and frequency, or start and stop delays, press the
membrane switch next to the word Adjust in the display. Refer to Adjust menu.
4. >> (version): To display the selected genset model and the resident version
software, press the membrane switch next to the >> in the display. From this
selection, you can also review a History file that can record and save up to twenty
error messages. Refer to Version menu.
The facing page shows a block representation of the Engine menu tree, including all
available sub-menus. Pressing the membrane switch next to the word Engine in the
display introduces the first Engine sub-menu.
1. Oil / Coolant sub-menu: This is the first sub-menu. Select Oil for a display of oil
pressure and oil temperature. Select Coolant for a display of coolant temperature.
When oil or coolant parameters are displayed, pressing the membrane switch next to
the << will return the display (Back) to the Oil Coolant sub-menu.
2. Battery / Hours sub-menu: From the Oil Coolant sub-menu, press the membrane
switch next to the >> in the display to move to the Battery / Hours sub-menu. Select
Battery for a display of battery voltage. Select Hours for a display of the number of
starts and the running hours. When battery or hours parameters are displayed,
pressing the membrane switch next to the << will return the display (Back) to the
Battery / Hours sub-menu.
3. RPM / Exhaust sub-menu: From the Battery / Hours sub-menu, press the
membrane switch next to the >> in the display to move to the RPM / Exhaust sub-
menu. Select RPM for a display of engine RPM. Select Exhaust for a display of the
(optional) exhaust temperature. When RPM or exhaust parameters are displayed,
pressing the membrane switch next to the << will return the display (Back) to the
RPM / Exhaust sub-menu.
The facing page shows a block representation of the Gen (generator) menu tree,
including all available sub-menus. Pressing the membrane switch next to the word Gen in
the display introduces the first Gen sub-menu.
1. Volts / Amps sub-menu: This is the first sub-menu. Select Volts for a display of a
line-to-line or line-to-neutral selection, or for viewing of the system bus line-to-line
voltage. Select line-line or line-neutral for the desired voltage display. Select Amps
for a display of Ll, L2, and L3 current in amps. When voltage or current parameters
are displayed, pressing the membrane switch next to the << will return the display
(Back) to the L-L / L-N sub-menu.
Note: If Delta is selected in the Initial Start Set-up sub-menu when selecting Volts, the
line-line or line-neutral sub-menus will not be displayed. Only the Ll2, L23, L31
sub-menu will be displayed.
2. Power / kW Hours sub-menu: From the Volts / Amps sub-menu, press the
membrane switch next to the >> in the display to move to the Power / kW Hours sub-
menu. Select Power for a display of power output in kilowatts and a power factor
value. Select kW Hours for a display of kilowatt-hours. When Power or kW Hours
parameters are displayed, pressing the membrane switch next to the << will return
the display (Back) to the Power / kW Hours sub-menu.
Note: The PF reading will contain an asterisk if the power factor is leading (for
example, *.3PF).
Note: Beginning at PCC Version 1.06, N/A is displayed in the PF field when the genset
is not running.
3. % Gov / Reg / Frequency sub-menu: From the Power/ kW Hours sub-menu, press
the membrane switch next to the >> in the display to move to the % Gov / Reg /
Frequency sub-menu. Select % Gov / Reg for a display of voltage regulator and
governor duty cycle (drive) levels in percentage of maximum. Select Frequency for a
display of the generator output frequency, the bus frequency, or the digital
synchroscope. When voltage regulator and governor or frequency parameters are
displayed, pressing the membrane switch next to the << will return the display (Back)
to the % Gov / Reg / Frequency sub-menu.
Bus Frequency (Digital Synchroscope) sub-menu: When the bus frequency
(digital synchroscope) information is displayed, the operator can observe the genset
synchronising with the system bus. The display indicates bus frequency and number
of degrees from synchronous condition (+ indicates faster, - indicates slower). When
the genset is operating within the sync-check window, an asterisk will indicate that
the paralleling breaker can be closed.
When –– –– –– is displayed, the synchroniser is not active.
As shown in the diagram, the Adjust menu has six sub-menus, including a save / exit
procedure.
Voltage and frequency can be adjusted only when the genset is running under normal
operating parameters (not in idle mode). For example, if voltage adjustment is selected
when the set is in Idle mode or not running, the alphanumeric display will be:
Ý VOLTAGE
ß N/A >>
1. Voltage sub-menu: This is the first sub-menu. Use the buttons next to the Ý and
ß symbols to adjust output voltage ± 5%.
2. Frequency sub-menu: From the Voltage sub-menu, press the button next to the >>
in the display to move to the Frequency sub-menu. Use the buttons next to the Ý and
ß symbols to adjust output frequency ± 5%.
3. Start Delay sub-menu: This delay applies only to remote starting in the Auto mode.
From the Frequency sub-menu, press the button next to the >> in the display to
move to the Start Delay sub-menu. Use the buttons next to the Ý and ß symbols to
set the start delay. The start delay adjustment range is 0 to 300 seconds.
4. Stop Delay sub-menu: This delay applies only to remote stopping in the Auto mode.
From the Start Delay sub-menu, press the button next to the >> in the display to
move to the Stop Delay sub-menu. Use the buttons next to the Ý and ß symbols to
set the stop delay. The stop delay adjustment range is 0 to 600 seconds
5. Idle Speed sub-menu: From the Stop Delay sub-menu, press the button next to the
>> in the display to move to the Idle Speed sub-menu. Use the buttons next to the Ý
and ß symbols to set the idle speed. The idle speed adjustment range is 800 RPM
±100 RPM (Default value is 800 RPM). The idle speed can be adjusted only when
the genset is running in the Idle mode. When not in Idle mode, N/A is displayed in the
RPM field.
Note: The Idle Speed sub-menu will not be used for gensets that do not require their
speed to be reduced to idle before shutting down. Under this circumstance only
the Stop Delay sub menu is used to initiate a cooling run before shutting down
the genset.
6. Save/Exit sub-menu: From the Stop Delay sub-menu, press the button next to the
>> in the display to move to the Save/Exit sub-menu. Select Save to save your
changes. At the Changes Saved sub-menu, select Exit to return to the main menu.
If you select Save, the adjustments will be retained after shutdown, and will be
in effect when the set is restarted. If you select Exit without saving first, the
adjustments will remain in effect until the genset is shut down, but will be reset
(and will not be in effect) when the set is restarted.
The facing page shows a block representation of the Version sub-menus. If you press the
button next to the >> in the Main menu display, the Version/Set-Up/Cal menu will appear.
Version sub-menu: If you select Version, the display will show the genset model
number, frequency and kW rating, and the date and version of the operating software.
To display the genset configuration options, press the button next to the >> in the sub-
menu that displays the model number, frequency, etc. This menu provides the following
information:
• Genset voltage
• Wye (i.e., Star) or Delta and Full or Standard
• Standby or Prime
• 1 or 3-phase
To modify any of these entries, you must return to the Initial Start Set-up sub-menus
described in the Service manual.
History: From the Version menu, press the button next to the >> in the display to move to
the History sub-menu. Press the button next to History to display the last (latest) recorded
error message.
The software will record (i.e. save) up to twenty error messages. The last error detected
will always be displayed first. As each new error is detected, the oldest error recorded
after twenty will be deleted.
To view the genset runtime at which the error occurred and to scroll through the
remaining recorded errors, press the button next to the >> in the error message menu to
display the Runtime, Newer/Older menu.
The buttons next to Newer and Older are used to scroll up and down through the error
messages. For example, pressing Older will display the next oldest recorded error
message. When pressing Newer the last (newest) error message will be displayed, the
display will return to the History menu.
Caution: The Emergency Stop push-switch must not be used for a normal shut-
down, as this will prevent a cooling down run in which the lubricating oil
and engine coolant carry heat away from the engine combustion
chamber and bearings in a safe manner.
• PCCP Switch
The Emergency Stop push-switch, located in the lower right hand corner of the
PCCP front panel, is a mechanically latched switch that will unconditionally stop the
engine when pressed. When the switch is pressed the PCCP panel will display the
Shutdown condition by illuminating the red Shutdown status LED and displaying the
following message on the alphanumeric display:
EMERGENCY STOP
102 - SHUTDOWN
The Emergency Stop push-switch must not be used for a normal shutdown, as this
will prevent a cooling run in which the lubricating oil and engine coolant carry heat
away from the engine combustion chamber and bearings in a safe manner.
EMERGENCY STOP
102 - SHUTDOWN
A remote Emergency Stop push-switch must not be used for a normal Shutdown, as
this will prevent a cooling run in which the lubricating oil and engine coolant carry
heat away from the engine combustion chamber and bearings in a safe manner.
Caution: Avoid off-load running for other than short periods. A minimum loading
of 30% is recommended. This loading will help to prevent the build up of
carbon deposits in the injectors, due to unburnt fuel, and reduce the risk
of fuel dilution of the engine lubricating oil. The engine must be
shutdown as soon as possible after the appropriate functions have been
checked.
An additional option in the control system is that the PCCP can be set to run with its
indicators blanked, to save battery power, or with the indicators showing all the time if the
optional battery charger is used. Either way, the PCCP is still functioning in the
background.
In the Standby (sleep) Mode, selector switch S5, located on a printed circuit board inside
the PCC, is set to the right. If no menu selections are made, the power to the control
panel will shut down after 30 seconds. The PCCP’s operating software is inactive and the
LEDs and displays on the front panel are all de-activated. The panel appears to be dead.
In the Power On (awake) Mode, selector switch S5 is set to the left. The PCCP initialises
the operating software and activates the menu display panel continuously. It is
recommended that switch S5 be left in the Power On Mode, unless battery charging is not
available.
If the PCCP is set to Standby Mode, the operating software is initialised and the front
panel automatically reactivated in response to a run signal or any one of eight wake up
signals from remote sensing switches. The wake up signals are:
• Emergency Stop
• Low Coolant Level
• Low Coolant Temperature
• Low Fuel
• Customer Fault Inputs 2 and 3
Automatic control of the genset is provided by positioning the three position Mode switch
to the Auto position.
Note: A red Non-automatic Status Indicator lamp on the PCCP will flash continuously if
the Mode switch is not in the Auto position.
Manual control of the genset is provided by positioning the three position Mode switch to
the Run position.
Note: The red Non-automatic Status indicator lamp on the PCC will flash continuously
if the Mode switch is not in the Auto position.
4.5.2 Lockout
The engine will be inhibited from starting if a critical fault condition exists when an attempt
is made to start the genset. An indication is initiated and a horn and beacon are activated.
Additionally, a number of non-critical circumstances arise where starting is prevented
such as:
The installed generators start independently of each other, controlled by their respective
PCCPs. During starting, automatic checks are carried out for the integrity of various
protection systems, such as the speed probe and the critical temperature sensors. The
PCCP will not allow the genset to continue the starting sequence if the integrity of a
sensor is considered to be in doubt by the PCCP checking system.
The starting sequence consists of three cranking intervals of approximately five seconds,
each followed by a rest period of fifteen seconds. If, at any time during the sequence, the
engine is sensed to have achieved firing speed (a speed calculated to be beyond the
starter motor capability), the remainder of the sequence is aborted. If, at the end of the
third crank period, firing speed has not been detected, the PCCP ends the start sequence
and a fail to start situation is indicated as an Overcrank.
When the engine is called to start, and firing speed is attained, the starter motor function
ceases and is then locked out. The run-up sequence is closely controlled by the PCCP
software to reduce smoke emission.
Upon attaining correct speed (frequency), and correct output voltage, the generator is
deemed to be running by the PCCP. During running, all systems associated with the
engine and its auxiliary systems will be monitored by the PCCP to control the generator
and to detect any abnormal conditions.
If in Auto mode, the genset will continue to run off-load until signalled by the PCCP to
close the genset breaker. In Manual (Run) mode, it will continue to run off-load, if the
circuit breaker is open, until the Mode switch is changed to Off (which will initiate the stop
sequence), or Auto (which will initiate a load transfer, if required).
Caution: The engine should not be allowed to run off-load for extended periods,
except as absolutely necessary during maintenance or cooling cycles.
4.6 Paralleling
4.6.1 Speed and Voltage Matching
Once the generator has achieved nominal voltage and frequency, the genset is ready to
be paralleled with the busbar supply. Each genset is paralleled completely independently
of the others.
The PCCP monitors both the incoming supply and the busbar voltage and frequency and
adjusts the incoming supply to match the busbar supply over a wide span of busbar
parameters. Synchronisation is achieved under full control, and at the correct phase
coincidence.
In Automatic mode, the PCCP receives a breaker close signal when synchronisation has
been achieved and signals the main breaker to close. In Run mode, the main breaker is
closed to connect the genset to the busbars, by using the breaker Open / Close push-
buttons.
Apart from the protection systems, there is no common coupling between gensets. This
allows for any genset, or its relevant controls, to be under maintenance without affecting
the others.
When the control system detects that the generator is up to speed and voltage, the load
is then ramped from the mains to the generator, the engine governor control system
keeping the electrical output within the correct parameters.
In the event of a Normal Stop, load will be ramped down before the generator circuit
breaker is opened, and the engine enters a cooling run under the control of the PCCP
before stopping. The cooling run allows for the safe dissipation of excess engine heat,
before the engine stops and the cooling system is de-energised.
OR
Press one of the Remote Emergency Stop push switches located in the Plant Room (if
separate switches are provided).
Note: When an emergency stop is initiated all generator load is dumped immediately
and the engine is stopped without a cooling run.
Caution: If the engine has been running recently, explosive gases (given off
during battery charging) may be present in the vicinity of the batteries.
Ensure the area is well ventilated before disconnecting batteries.
1. Turn the Mode switch on the PCCP panel to the Off position.
2. Isolate and lock off the supply to the battery charger, where fitted.
3. As an additional precaution, disconnect the starting batteries and control system
batteries, (if separate).
4. Isolate and lock off the heater control box, where fitted.
5. Isolate the fuel supply to the engine.
6. As an additional precaution, disconnect the starter / control system batteries
7. Fit warning notices at each of the above points to indicate Maintenance in Progress -
Plant Immobilised for Safe Working.
4.9.1 Alarm
In the event of the PCCP detecting a non-critical condition, an alarm indication will be
initiated and a beacon will be activated. If the genset is loaded, that loading will be
maintained and the generator will continue to run at regulated speed.
Additional indications can be shown on the alphanumeric display. The indications are
genset output voltage (3-phase, line-to-line or line-to-neutral) and parallel bus voltage (3-
phase, line-to-line).
The generator output voltage is given on the Generator Set Rating Plate
Additional indications of genset output current can be accessed by selecting the Gen
menu on the alphanumeric display.
The generator output current is given on the Generator Set Rating Plate.
Additional indications are provided on the alphanumeric display. The indications are
genset output frequency and parallel bus frequency.
Frequency is directly related to engine speed and, for a nominal engine speed of 1500
RPM (or 1800 RPM), the relationship between engine speed and frequency is given by
the following formula:
The generator output frequency is given on the Plant Rating Plate on the generator.
Caution: Under no circumstances must the Set be operated outside the rated
frequency range stamped on the Generator Set Rating Plate. Serious
damage or injury may result if this condition is allowed to occur.
Note: The PCCP inhibits closure of the paralleling breaker outside the sync-check
window. Therefore the breaker close control can be operated even before
synchronisation, although the breaker will not close until a signal is sent from the
PCCP to allow it.
• Oil temperature
• Coolant temperature
• Exhaust gas temperature.(option)
• Oil pressure
• Engine speed
• Battery voltage
• Engine operating hours
• Number of starts
4.12 Heaters
Caution: Heater(s) must not be energised if coolant system has been drained.
Caution: The coolant heater is in no way intended to protect the engine and
cooling system from freezing in sub zero conditions. If there is any
danger of freezing then a suitable antifreeze agent must be added to
the cooling system.
• Lubrication - Check the engine lubricating oil level and ensure that the level is always
maintained as detailed in the engine Operation and Maintenance manual
• Coolant - Check the engine coolant level and ensure that the level is always
maintained at the coolant expansion tank. Fill the cooling system to the bottom of the
fill neck in the radiator fill or expansion tank. Do not check while the engine is hot
Note: Some radiators have two fill necks, both of which must be filled when the
cooling system has been drained.
Caution: Do not attempt to remove a radiator pressure cap while the generator is
running, or is stationary but hot. Always allow it to cool before removing
the cap.
• Cooling Air Inlet / Outlets - Ensure that the cooling air inlets / outlets are unobstructed
• Exhaust Outlet - Ensure that exhaust components are secured and not warped, and
that the exhaust outlet is unobstructed; that no combustible materials are near the
system, and gases are discharged away from building openings. Ensure that there
are no leaks and that all fittings are tight
• Fuel Supply - Ensure that the fuel tank is filled to the normal level and that the fuel
system is primed and all the valves required for operation are open. Ensure that
there are no leaks and that all fittings are tight
• Batteries – Ensure that the batteries are charged, that the electrolyte is at the correct
level and that all connections are correct
• Auxiliary AC Supplies - Ensure that all auxiliary equipment is receiving power from
the Load Terminal Box
• Emergency Stop / Fire Detection Equipment - Ensure that all related equipment is
fully operational
Caution: Do not use an Emergency Stop switch to shut down an engine unless a
serious fault develops. The Emergency Stop push-switch must not be
used for a normal shut-down, as this will prevent a cooling down run in
which the lubricating oil and engine coolant carry heat away from the
engine combustion chamber and bearings in a safe manner.
Caution: Avoid off-load running for other than short periods. A minimum loading
of 30% is recommended. This loading will help to prevent the build up of
carbon deposits in the injectors, due to unburnt fuel, and reduce the risk
of fuel dilution of the engine lubricating oil. The engine must be
shutdown as soon as possible after the appropriate functions have been
checked.
The PCCP will automatically make up to three start attempts, and lock the engine out of
service if the third attempt fails. If the PCCP senses an operating fault, either a Warning
will be indicated on the PCCP or the engine will be shut down automatically. Automatic
shutdowns require no operator action other than to observe the detail.
Note: The Non-Automatic LED on the PCCP will be illuminated whenever the Mode
switch is not set to Auto. Also, if the PCCP is set to operate with the Standby
(Sleep) Mode active, the PCCP indications may de-activate and need to be
reactivated (press the Self-Test membrane switch to reactivate).
1. As a precautionary measure, for the initial runs only, place suitable fire extinguishers
at strategic locations around the genset. Also ensure that all test personnel are fully
aware of the positions of all emergency shutdown switches and fire break glass units
(if fitted).
2. If the ambient temperature is low, it is preferable to have had the engine / alternator /
panel heaters on for some time beforehand to improve starting and to eliminate any
condensation.
3. On the PCCP, set the Mode switch to Run and check that the engine starts and runs
automatically. The PCCP may make up to three start attempts before it terminates
the automatic start-up function. If all three start attempts fail, the fault must be
investigated before the system is reset and another start-up is initiated.
4. During start-up and the initial run, observe the PCCP and check for unusual
indications that may highlight a problem; observe the associated power systems for
signs of flashovers, burning, etc. Should any items require urgent attention, shut
down the genset immediately and rectify the fault, using skilled assistance if required.
5. Activate the PCCP’s Engine menu and check the engine lubrication oil pressure
(consult the engine Operation and Maintenance Manual for correct value). Check the
engine speed and ensure that the engine is running near to nominal speed. The
speed governing should be stable with no tendency to hunt. Make careful
observations of any sign of a malfunction of the engine, alternator and auxiliary
systems.
Engine operating speed is adjusted at the factory to 1500 RPM at full load (50 Hz
Sets) and 1800 RPM at full load (60 Hz Sets).
The no-load operating speed is within 2 to 2.5 Hz higher than the full load operating
speed.
6. Activate the PCCP’s GEN menu and check the alternator output voltage and
frequency. Refer to the alternator Installation, Service and Maintenance Manual.
7. Check the engine / associated pipe-work, including the exhaust system, for leaks. In
the event of a fuel or exhaust leak, shut down the genset immediately.
Caution: Take extreme care when working on a hot exhaust system. In case of a
fuel or lubricating oil leak, the spilled fluid should be absorbed using a
proprietary material (Fullers Earth granules or similar).
Sawdust should not be used, as this will create a fire hazard.
8. After a short period of running off-load (between five and fifteen minutes), shut down
the Genset by the Mode switch to Off. A controlled shutdown is effected by the
PCCP, and this may include a short cooling down run.
If the genset is in order on the off-load initial run, arrange for an on-load (mains failure)
test run. This should be performed during a non-critical period, as it may be necessary to
stop the genset during the test.
4. Allow the genset to run for fifteen minutes on-load to check initial readings and
functions of the engine. Engine parameters can be checked on the PCCP’s Engine
menu and power parameters on the analogue meters and the Gen menu.
5. Oil pressure should be maintained after an initial drop and should stabilise as the
engine temperature stabilises. The pressure should always be within the
manufacturer's specification.
6. Engine temperature should rise rapidly and then stabilise after a few minutes. The
normal running temperature should be within the range 176°F to 203°F (80OC to
95OC).
7. Voltage should be maintained within ± 2% for stable load conditions.
8. Frequency should be maintained within 2 Hz for all stable loads between zero and
full-load.
9. Check all engine systems for leaks. If any leaks are detected, the genset should be
shut down by setting Mode switch to Off, and the leaks rectified. If the leak is serious
or may cause immediate danger, use an Emergency Stop switch to shut down the
engine.
10. On satisfactory completion of the test the generator can be signalled to stop (set the
Mode switch to Off) and the mains supply can be returned. The genset will open the
circuit breaker and automatically be put into a cooling run off-load before performing
a controlled shutdown.
11. Complete a Commissioning Form, if required.
6. If the genset fails to start, as detailed above, reset the control system as follows:
a) Return the Mode switch to the Off position
b) Identify and clear the fault before any further start attempts are made.
c) Press the Reset button.
d) Select Run or Auto, as required, and repeat the above starting procedure
7. With the genset running, activate the Engine menu on the PCCP and check the
following engine parameters:
a) Oil pressure should be maintained after an initial drop. The pressure should
always be within the manufacturer's specification
b) Engine temperature should rise rapidly and then stabilise after a few minutes.
The normal running temperature should be within the range 176°F to 203°F
(800C to 950C)
8. Load the genset to at least 30% rated kilowatt output and observe the
performance closely. Avoid off-load running for extended periods.
9. Check the engine and associated pipework, including the exhaust system, for leaks.
In the event of an exhaust leak, the genset should be shut down immediately and
measures taken to ensure personal safety. Observe the ‘Exhaust Gas Hazards’
safety requirements listed in Section 1.
Caution: Take extreme care when working on a hot exhaust system. In case of a
fuel or lubricating oil leak, the spilled fluid should be absorbed using a
proprietary material (Fullers Earth granules or similar). Sawdust should
not be used, as this will create a fire hazard
10. Activate the Gen menu on the PCCP and check the generator output by observing
the analogue meters and the more detailed information on the digital display:
a) Voltage should be maintained within ± 2% for stable load conditions
b) Frequency should be maintained within 2 Hz for all stable loads between zero
and full-load
Note: If required, the Phase Select switch can be used to select alternative phase data
on the analogue voltmeter and ammeter.
11. On satisfactory completion of the test, open the genset circuit breaker to return the
load to the mains supply.
12. This operation applies to the initial start-up only. Confirm correct operation of the
Emergency Stop facility as follows:
a) Press the Emergency Stop push-button on the PCCP and ensure that the engine
shuts down immediately, without a cooling down run
b) When the engine has stopped rotating, pull the Emergency Stop push switch to
unlatch the switch
c) Return the Mode switch to Off
d) Press the Reset membrane switch
13. As soon as possible after the Emergency Stop, set the Mode switch on the PCCP to
Run or Auto as required for a restart. Ensure that the genset starts and runs and that
the engine temperature stabilises. Avoid off-load running for extended periods.
14. If plant room Emergency Stop push switches are provided, repeat the above two
paragraphs for each of the push buttons provided, always allowing time for the
engine temperature to stabilise. Bear in mind that shutting the engine down without a
cooling down run can cause overheating, so space the checks accordingly.
Note: The requirement for further checks on the Emergency Shutdown system will
depend on generator usage. Contact an authorised Service Department for a
site-specific recommendation.
15. Perform the following procedure to shut down the genset, and ensure that the engine
completes a short cooling run before shutting down:
a) On Manual Start Gensets, turn the Mode switch to the Off position
b) On Automatic/Remote Start Gensets remove the Remote Start signal
16. Return the genset to its normal operating mode as required.
17. Keep a record of all maintenance work carried out.
SECTION 5 – MAINTENANCE
5 Maintenance
Maintenance work, particularly in confined areas, should be carried out by two engineers
working together.
Ensure that adequate lighting and staging (where required) are installed.
Caution: Only authorised and qualified maintenance engineers who are familiar
with the equipment and its operation should carry out maintenance.
Caution: Before carrying out any maintenance work, become familiar with the
Generator Plant Safety Code given in Section 1 of this manual.
SECTION 6 – TROUBLESHOOTING
6 Troubleshooting
6.1 Introduction
Fault diagnosis charts are provided in this section to assist in locating and identifying the
possible causes of faults in the genset system.
The PCCP displays faults and warnings by illuminating its lamps, and also displays
numbered fault messages on its digital display. These are detailed in the PCCP Fault
Finding Charts. If an operating fault occurs, first check the PCCP indications against
these charts. If the problem cannot be resolved, continue with the General Fault Finding
Charts that contain basic troubleshooting procedures.
The engine Operation and Maintenance Manual contains its own fault finding charts and
covers many possible engine faults. Similarly, the alternator Installation, Service and
Maintenance Manual contains its own fault finding details.
High voltages are present within the genset output box when the generator is running.
The installation of a genset can be designed for remote starting. When troubleshooting a
genset that is shutdown ensure that the set cannot be accidentally re-started. To prevent
accidental starting always remove the negative (-) battery lead from the set starting
battery.
Before starting any fault finding, ensure that the following basic checks are carried out:
Control does not power-up when There is no DC power to the a) Check the battery electrolyte level
the Mode switch is set to Run or control and specific gravity
the Self-test switch is pressed b) Check terminals are clean and tight
c) Check Fuse 1 on the engine interface
board
d) Contact an Authorised Service Centre
Warning, Shutdown, and Non- None a) Indicates all engine systems are
Automatic lamps are not lit. Digital normal
display shows main menu or b) No corrective action required
selected menu
Non-Automatic lamp flashes Mode switch is not in the Auto a) Move the Mode switch to the Auto
position. This will prevent position for automatic operation
automatic starting b) None Automatic lamp stops flashing
MESSAGE: PCCP idles the engine at start up if Indicates that the engine is operating in
IDLE MODE jacket temperature is below 140°F Idle mode.
o
101 — INDICATION ONLY (40 C), and continues to do so until a) When the genset is operating in the
this temperature is reached. Run mode, grounding the engine idle
Engine continues to operate at
PCCP idles the engine during input causes generator build-up to be
reduced RPM
cooling run before shutting down. inhibited and the engine to be
The above conditions only apply to governed at idling speed
engines requiring these b) When ground is removed from this
procedures to be set up input, the genset returns to normal
speed and voltage
c) When the engine idle function is
enabled, the control automatically
sets lower oil pressure warning and
shutdown trip points to reflect the
lower operating speed
d) When the engine idle function is
removed and the genset reverts to
normal operating speed, the control
automatically resets the oil pressure
warning and shutdown trip points to
the normal settings
Shutdown lamp lights Local or remote Emergency Stop To Reset:
MESSAGE: Operated a) Pull the switch and allow it to un-latch
EMERGENCY STOP b) Turn the Mode switch to Off
c) Press the Reset switch
102 — SHUTDOWN
d) Select Run or Auto as required
Engine shuts down and will not
crank
Warning lamp lights Indicates that the engine oil a) The engine must be stopped as
MESSAGE: pressure has dropped to an soon as possible to prevent
unacceptable level. Possibly due serious damage. If the engine can
LOW OIL PRESSURE
to high oil temperature, low oil be stopped, do so
200 — WARNING level, dirty filters, dirty cooler, relief b) If the generator is powering critical
Engine continues to operate valve failure, potential oil pump loads and cannot be shut down, wait
failure, excessively worn engine until the next shutdown period then
bearings — eventual bearing follow the next procedure, - Low Oil
failure Pressure. Shutdown
Shutdown lamp lights Indicates that the engine oil a) Check all possible causes as in 200
MESSAGE: pressure has dropped below the —warning
shutdown trip point. The reason for b) Rectify the problem
LOW OIL PRESSURE
this shutdown must be determined c) Reset the control system and re-start
201 — SHUTDOWN d) Check engine running conditions
before restarting the engine.
Engine shuts down Check possible causes as in 200 under no load
— warning e) Contact an Authorised Service Centre
if the problem persists
Warning lamp lights Indicates that the engine oil a) Check that the engine oil pressure
MESSAGE: pressure sender is not functioning sender is properly connected
correctly b) Contact an Authorised Service Centre
OIL PRES SENDER
if problem persists
204 — WARNING
Warning lamp lights Indicates that the engine coolant Check for the following conditions:
MESSAGE: heater is not operating or is not a) Coolant heater not connected to the
LOW COOLANT TEMP circulating coolant power supply
b) Check for blown fuse or disconnected
210 — WARNING
heater cord and correct as required
The genset is in standby mode but c) Check for low coolant level and
is not operating. Warning occurs replenish if required
when the engine coolant d) Look for possible coolant leakage
temperature is 21°C (70°F) or points and repair as required
lower. e) Contact an Authorised Service Centre
Note: In applications where the if none of above
ambient temperature falls below Note: This signal wakes-up the PCCP
4°C (40°F), Low Engine Temp may from the Standby condition
be indicated even though the
coolant heaters are operating
Warning lamp lights Indicates that the engine has If the engine can be stopped.
MESSAGE: begun to overheat and the coolant a) Allow the engine to cool before
HIGH COOLANT TEMP temperature has risen to an checking the coolant level and
unacceptable level: replenish if required
211 — WARNING
101°C (215°F) – Standby / 97°C b) Determine reason for coolant loss
Engine continues to operate (207°F) – Primary. and rectify
c) Check coolant pump & pump drive
d) Check radiator matrix for air-born
If the generator is powering non-
debris and clean if required or if heat
critical and critical loads and
exchanger is employed check raw
cannot be shutdown — reduce the
water pump and raw water supply
load if possible by turning off non-
e) Check fan belt and / or fan motor
critical loads.
circuitry
Check air inlets and outlets and f) Access the Coolant Temp menu prior
remove any obstructions to airflow to clearing the fault
g) Run engine on no load test after
rectifying the fault
Shutdown lamp lights Indicates that the engine has Allow the engine to cool down completely
MESSAGE: overheated (coolant temperature before proceeding with the following
HIGH COOLANT TEMP has risen above the shutdown trip checks:
point: a) Check the coolant level and replenish
212 — SHUTDOWN
101°C (215°F) – Standby / 97°C if low
Engine shuts down (207°F) – Primary b) Look for coolant leakage and repair if
necessary
c) Check for obstructions to cooling
airflow and correct as necessary
d) Carry out all checks as in 211 —
warning
e) Run engine on no load test after
rectifying the fault
Warning lamp lights Indicates that the resistance of the a) Check the sender. Resistance should
MESSAGE: coolant temperature sender is out be 500 to 2k ohm
of range b) If faulty — fit new sender
ENG COOLANT SENDER
213 — WARNING
Shutdown lamp lights Indicates that the engine coolant a) Check the coolant level and replenish
MESSAGE: level has fallen below the trip point. if low
Allow the engine to cool down b) Look for possible coolant leakage
LOW COOLANT LVL
completely before proceeding. points and repair if necessary
214 — WARNING c) Reset the control system and restart
Note: This signal wakes up the
Engine shuts down PCCP. after locating and correcting the
OR problem
(Low Coolant Warning only)
LOW COOLANT LVL d) Contact Authorised Service Centre if
215 — SHUTDOWN problem persists
e) LOW COOLANT LVL Shutdown will
not occur if genset is in Idle mode
Shutdown lamp lights Indicates that the magnetic pick-up a) Check that the pickup sensing head
MESSAGE: speed indication is not being is clean
sensed or does not match the b) Check cable for continuity and good
MAG PICKUP
genset output frequency screening
220 — SHUTDOWN c) Restart and check RPM on the digital
Engine shuts down display
d) Contact an Authorised Service Centre
if the problem persists
Engine will not crank Indicates a possible fault with the Check for the following conditions:
Shutdown lamp lights control or starting system. a) Check fuse F3 on the Engine
MESSAGE: Discharged or defective battery. Interface Board
FAIL TO CRANK Poor battery cable connections. b) Recharge or replace the battery
221 — SHUTDOWN Locked starter motor or damaged c) Clean the battery cable terminals and
flywheel starter ring tighten all connections including
starter motor
d) Contact an Authorised Service Centre
for service of starter and starting
system
Shutdown lamp lights Indicates a possible fuel problem a) Replenish fuel supply tank
Engine Stops Cranking or air induction problem: b) Renew fuel filters
MESSAGE: Fuel supply tank low level or c) Ensure engine heaters are operating
OVERCRANK contaminated fuel. d) Clean/renew induction filters
222 — SHUTDOWN Fuel filters choked. e) Reset air shut-off valves
Waxed fuel. f) Reset the control system and restart
Air induction filters choked. after correcting the problem
Air shut-off valves operated g) Contact an Authorised Service Centre
if none of the above
Engine runs and then shuts down Indicates that the engine has a) Contact an Authorised Service Centre
Shutdown lamp lights exceeded its normal operating
MESSAGE: speed trip point.
OVERSPEED
223 — SHUTDOWN
Warning lamp lights Indicates that the battery voltage is a) Check the battery electrolyte level
MESSAGE: below 24V DC. (12V DC for 12V and specific gravity
LOW DC VOLTAGE battery) b) Repair battery charger
230 — WARNING Discharged or defective battery. c) Recharge or replace the battery
Battery charger fault/fuse d) Poor battery cable connections
e) Clean the battery cable terminals and
tighten all connections
f) Contact an Authorised Service Centre
if none of the above
Warning lamp lights. Indicates that the battery voltage a) Contact an Authorised Service Centre
MESSAGE: exceeds 32V DC (16V DC for 12V
HIGH DC VOLTAGE battery)
231 — WARNING
Warning lamp lights Indicates the battery voltage a) See Warning Message 230 LOW DC
MESSAGE: dropping below 60% of nominal for VOLTAGE
WEAK BATTERY two seconds, during starting.
232 — WARNING Discharged or defective battery
Engine continues to run
Warning lamp lights Indicates that the day tank fuel a) Check the fuel supply and replenish
MESSAGE: supply is running low as required
LOW FUEL DAY Note: This signal wakes up the PCCP
240 — WARNING
Warning lamp lights. Indicates that the fuel supply is a) Check the fuel supply and replenish
MESSAGE: running low as required
LOW FUEL
241 — WARNING
Shutdown lamp lights. Indicates PCCP memory error. a) Contact an Authorised Service Centre
MESSAGE: Data corruption of critical operating
EEPROM ERROR parameters
250 — SHUTDOWN
Warning lamp lights. Indicates PCCP memory error. a) Contact an Authorised Service Centre
MESSAGE: Data corruption of non-critical
EEPROM ERROR operating parameters
251 — WARNING
or
252 — WARNING
Engine continues to run
Shutdown lamp lights. When any one of these customer a) Contact an Authorised Service Centre
MESSAGE: defined inputs is closed to ground,
CUSTOMER FAULT 1 the corresponding fault message is
displayed. The nature of the fault is
260 — SHUTDOWN
an optional customer selection.
or These fault functions can be
GROUND FAULT programmed to initiate a Shutdown
261 — SHUTDOWN or a Warning. Customer fault 261
or or 262 input can wake-up the
control if it is not operating.
RUPTURE BASIN
As indicated by the Shutdown
262 — SHUTDOWN
lamp, a shutdown response has
or been pre-selected
HIGH GEN TEMP Note: Customer fault messages
263 — SHUTDOWN are editable. The message
Engine shuts down displayed for the code shown (260
to 263) may have been edited and
will not appear as shown in this
table
Warning lamp lights. When any one of these customer a) Contact an Authorised Service Centre
MESSAGE: defined inputs is closed to ground,
CUSTOMER FAULT 1 the corresponding fault message is
displayed. The nature of the fault is
260 — WARNING
an optional customer selection.
or These fault functions can be
GROUND FAULT programmed to initiate a Shutdown
261 — WARNING or a Warning. Customer fault 261
or or 262 input can wake-up the
control if it is not operating.
RUPTURE BASIN
As indicated by the Warning lamp,
262 — WARNING
a shutdown response has been
or pre-selected
HIGH GEN TEMP Note: Customer fault messages
263 — WARNING are editable. The message
displayed for the code shown (260
to 263) may have been edited and
will not appear as shown in this
table
Shutdown lamp lights. Indicates that one of the phase a) Contact an Authorised Service Centre
MESSAGE: voltages has exceeded 130% of
HIGH AC VOLTAGE nominal, or has exceeded 110% of
nominal for 10 seconds
301 — SHUTDOWN
Engine shuts down
Shutdown lamp lights. Indicates that one of the phase a) Contact an Authorised Service Centre
MESSAGE: voltages has dropped below 85%
LOW AC VOLTAGE of nominal for 10 seconds
303 — SHUTDOWN
Engine shuts down
Shutdown lamp lights. Indicates that engine speed has a) Contact an Authorised Service Centre
MESSAGE: dropped below 90% of nominal for
UNDER FREQUENCY 10 seconds
313 — SHUTDOWN Note: Five seconds before
Shutdown, a Load Dump signal is
Engine shuts down initiated
Warning lamp lights. Indicates that the generator output a) Contact an Authorised Service Centre
MESSAGE: current has exceeded 110% of
OVERCURRENT rated value for 60 seconds
320 — WARNING
Engine continues to run
Shutdown lamp lights. Indicates that the generator output a) Contact an Authorised Service Centre
MESSAGE: current has exceeded 110% of
OVERCURRENT rated value and that a PCCP
time/current calculation has
321 — SHUTDOWN
initiated an overcurrent Shutdown
Engine shuts down
Shutdown lamp lights. Indicates that the generator output a) Contact an Authorised Service Centre
MESSAGE: current has exceeded 175% of
SHORT CIRCUIT rated value
322 — SHUTDOWN
Engine shuts down
Warning lamp lights. Indicates that the 3-phase power a) Contact an Authorised Service Centre
MESSAGE: exceeds 105% of Standby (or
OVERLOAD 115% of Prime) rating.
After 5 seconds the Load Dump
320 — WARNING
output is activated.
Engine continues to run After 60 seconds the Overload
warning is activated
Shutdown lamp lights. Indicates improper CT or PT a) Contact an Authorised Service Centre
MESSAGE: phasing (Non-paralleling units
REVERSE POWER only)
335 — SHUTDOWN
Engine starts from the generator Check the control wiring between a) Contact an Authorised Service Centre
control panel but will not start the remote switch and the PCCP
automatically or from a remote
panel.
Note: The Mode switch must be in
the Auto position for automatic or
remote starting