Self-Operated Pressure Regulators ANSI Version: T 2521 EN Type 2405 Pressure Reducing Valve
Self-Operated Pressure Regulators ANSI Version: T 2521 EN Type 2405 Pressure Reducing Valve
Self-Operated Pressure Regulators ANSI Version: T 2521 EN Type 2405 Pressure Reducing Valve
Application
Pressure reducing valve for set points from 0.075 to 150 psi (5 mbar to 10 bar) · Valve size NPS ½ to 2 1) (DN 15 to 50)
Pressure rating Class 125 to 300 (PN 16 to 40) · Suitable for gases at temperatures from –5 to +140 °F/32 to 300 °F 2) (–20 to
+60 °C/0 to +150 °C) 2)
Special features
• Low-maintenance proportional regulators
• Compact regulator design providing excellent control
accuracy
• Internal set point springs with set point adjustment using a
nut on the actuator
• Spring-loaded, single-seated valve balanced by a balanc-
ing diaphragm
• External connection of a control line
• Meets strict emission requirements Fig. 1: Type 2405 Pressure Reducing Valve
• Minimum leakage class IV
• Suitable for use as a vacuum breaker Special versions
• Version with FDA-compliant materials for the food and
Version pharmaceutical industries
Valves in NPS ½ to 2 (DN 15 to 50) · Flanged connections • NACE version for sour gas applications
Soft-seated plug · Body made of cast iron, cast steel or cast • Version with force limiter (for higher pressures across the
stainless steel operating diaphragm)
• Actuator with seal and leakage line connection (also as
vacuum breaker)
• Version with connected control line. Pressure
1) NPS ½ and ¾ not in Class 125 tapped directly at the valve body
2) For unbalanced versions with FKM diaphragm and FKM soft seal
SAMSON AKTIENGESELLSCHAFT · Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany Edition June 2022
Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 · samson@samsongroup.com · www.samsongroup.com
Principle of operation
The medium flows through the valve in the direction indicated move the valve plug according to the force of the set point
by the arrow. The position of the plug determines the flow rate spring (7).
across the area released between plug (3) and seat (2). The spring force is adjustable at the set point nut (8). When
In the pressureless state (control line not connected and no the force resulting from the downstream pressure p2 rises
pressure applied) the valve is opened by the force of the set above the adjusted pressure set point, the valve closes propor-
point spring (7). tionally to the change in pressure.
The downstream pressure p2 to be controlled is tapped down- In the version with pressure balancing, the forces produced by
stream of the valve and transmitted over the control line to the the upstream and downstream pressures acting on the plug
control line connection (9) on the actuator housing (6) where it are eliminated by the balancing diaphragm (10). The plug is
is converted into a positioning force. This force is used to fully balanced.
12
7
6
11
4
9
p2
2
p1
3
10
p2
p1 p2
p1
2 T 2521 EN
Table 1: Technical data
NPS ½ NPS ¾ NPS 1 NPS 1½ NPS 2
Valve size
(DN 15) (DN 20) (DN 25) (DN 40) (DN 50)
Pressure rating (valve) Class 125, Class 150, Class 300 · PN 16, PN 25, PN 40
Standard 5 7.5 9.4 23 37
T 2521 EN 3
Table 2: Materials · Material numbers according to ASTM and DIN EN
Valve body A126B, A216 WCC A351 CF8M
Seat 316L 316L
Plug 316L 316L
Plug spring 1.4310 1)
Plug stem 316L
Seal EPDM · FKM · NBR
Balancing diaphragm EPDM · FKM · NBR
Actuator housing 1.0332 1.4301
Operating diaphragm EPDM · FKM · NBR
1) Optional 316L (1.4404)
1 2
– Actuator housing on top, actuator
facing upwards Inert gas for blanketing
– The direction of flow must match the
direction indicated by the arrow on
the body. In
Out
– In applications in which the blanketing gas can liquefy,
condensate may form in the control line, causing damage
to the regulator. To allow condensate to run back into the
If the pressure p of the inert gas in the tank falls below the set point
tank, install the control line with an approximate 10 %
p2 adjusted at the Type 2405 Pressure Reducing Valve (1), it opens
slope to the pressure tapping point at the tank. to allow more gas to enter the tank. The valve (1) closes again
– Distance between the pressure tapping point and regulator when the pressure p of the blanketing gas rises to the adjusted set
point p2.
min. 6 x NPS (6 x DN).
If the pressure is too high, the inert gas is vented off over the
In exceptional cases, the regulator can also be installed in Type 2406 Excess Pressure Valve (2).
vertical pipelines with the direction of flow from the top (see
Fig. 3: Sample application, Type 2405 used for tank blanketing
u EB 2520 for more details).
Dimensions
H2
H2
L
ØD L
ØD
NPS ½ to 1 (DN 15 to 25) NPS 1½ and 2 (DN 40 and 50)
The control line connection is turned by 90° in the drawing. The connection is normally located opposite the side with the arrow indicating
the direction of flow.
An adapter G ¼ to ¼-18 NPT (order no. 0230-3417) must be ordered separately.
4 T 2521 EN
Table 3: Dimensions in inch/mm · Weights in lb/kg
Valve size NPS ½ NPS ¾ NPS 1 NPS 1½ NPS 2
(DN 15) (DN 20) (DN 25) (DN 40) (DN 50)
inch – – 7.3 8.8 10
Class 125
mm – – 184 222 254
inch 7.3 7.3 7.3 8.8 10
Length L Class 150
mm 184 184 184 222 254
inch 7.5 7.6 7.8 9.3 10.5
Class 300
mm 191 194 197 235 267
inch 1.8 2.8
Cast steel
mm 44 72
Height H2
inch 2.1 – 2.8 3.7 3.9
Forged steel
mm 53 – 70 92 98
Set point range Valve with actuator · Dimensions and weights
Without balancing 12.8” (325 mm) 14.6” (370 mm)
0.075 to 0.25 psi Height H
With balancing 13.9” (352 mm) –
5 to 15 mbar
Actuator ØD = 19.1” · 485 mm, A = 186 in² · 1200 cm²
Without balancing 12.6” (318 mm) 14.4” (366 mm)
Height H
0.15 to 0.42 psi With balancing 13.8” (345 mm) –
10 to 30 mbar
ØD = 19.1” · 485 mm,
Actuator ØD = 15” · 380 mm, A = 100 in² · 640 cm²
A = 186 in² · 1200 cm²
Without balancing 12.6” (318 mm) 14.4” (366 mm)
Height H
0.35 to 0.87 psi With balancing 13.8” (345 mm) –
25 to 60 mbar
ØD = 15” · 380 mm,
Actuator ØD = 11.2” · 285 mm, A = 50 in² · 320 cm²
A = 100 in² · 640 cm²
Without balancing 12.6” (318 mm) 14.4” (366 mm)
0.75 to 3 psi Height H
With balancing 13.8” (345 mm) 14.6” (370 mm)
50 to 200 mbar
Actuator ØD = 11.2” · 285 mm, A = 50 in² · 320 cm²
Without balancing 12.6” (318 mm) 14.4” (366 mm)
1.5 to 8 psi Height H
With balancing 13.8” (345 mm) 14.6” (370 mm)
0.1 to 0.6 bar
Actuator ØD = 11.2” · 285 mm, A = 50 in² · 320 cm²
Without balancing 12.6” (318 mm) 14.4” (366 mm)
3 to 15 psi Height H
With balancing 13.8” (345 mm) 14.6” (370 mm)
0.2 to 1 bar
Actuator ØD = 8.9” · 225 mm, A = 25 in² · 160 cm²
Without balancing 13” (330 mm) 14.4” (365 mm)
10 to 35 psi Height H
With balancing 14” (356 mm) 14.6” (369 mm)
0.8 to 2.5 bar
Actuator ØD = 6.7” · 170 mm, A = 12 in² · 80 cm²
Without balancing 13.2” (333 mm) 14.5” (368 mm)
30 to 75 psi Height H
With balancing 14.2” (359 mm) 14.7” (373 mm)
2 to 5 bar
Actuator ØD = 6.7” · 170 mm, A = 6 in² · 40 cm²
Without balancing 17.2” (437 mm) 19.1” (485 mm)
65 to 150 psi Height H
With balancing 18.3” (463 mm) 19.3” (489 mm)
4.5 to 10 bar
Actuator ØD = 6.7” · 170 mm, A = 6 in² · 40 cm²
T 2521 EN 5
Valve size NPS ½ NPS ¾ NPS 1 NPS 1½ NPS 2
(DN 15) (DN 20) (DN 25) (DN 40) (DN 50)
0.075 to 0.25 psi
61.7 lb · 28 kg
5 to 15 mbar
88.2 lb · 40 kg
0.15 to 0.42 psi
39.7 lb · 18 kg
10 to 30 mbar
0.35 to 0.87 psi
66.1 lb · 30 kg
25 to 60 mbar
0.75 to 3 psi
30.9 lb · 14 kg
50 to 200 mbar
57.3 lb · 26 kg
1.5 to 8 psi Weight in lb and kg
1)
Ordering text
Type 2405 Pressure Reducing Valve
Valve size NPS (DN) ..., set point range … psi (mbar/bar), CV (KVS) coefficient …,
Body material …, optionally, special version ...
Materials: plug seal ..., balancing diaphragm ..., operating diaphragm ...
Optionally, special version
2022-06-23 · English