Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Instruments Catalogue

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

INSTRUMENTS CATALOGUE

153
150
Beck.
The adjustable
differential pressure switches.

154
151
Differential pressure switch
930.8x Climair®
with adjustable switching pressure

Applications Pressure connections


Adjustable differential pressure switch for monitoring 2 plastic pipe connection pieces (P1 and P2), external
overpressure, vacuum and differential pressure of air or other diameter 6.0 mm:
non-combustible, non-aggressive gases. Possible fields of P1 for connection to higher pressure (marked +)
application include: P2 for connection to lower pressure (marked –)
● Monitoring air filters and ventilators
Housing materials
● Monitoring industrial cooling-air circuits
● Overheating protection for fan heaters Switch body made of PA 6.6.
● Monitoring flows in ventilation ducts
Cover made of PS.
● Controlling air and fire-protection flaps
Weight
● Frost protection for heat exchangers
With cover 150 g
Without cover 110 g
Versions Mechanical working life
With this pressure switch the switching pressure can be
Over 106 switching operations.
adjusted without a pressure gauge using a scaled adjustment
knob. The switching differential can also be adjusted with a
Electrical rating
screwdriver.
Standard version max. 1.0 A (0.4 A) / 250 VAC
Type Adjustment range for Switching Tolerance for Low-voltage version max. 0.1 A / 24 VDC
upper switching differential upper and lower
pressure set to switching pressure Electrical connections
from to
AMP flat plug 6.3 mm x 0.8 mm in accordance with DIN
930.80 20 200 Pa 10 Pa ± 15% 46244 or push-on screw terminals.
930.81 40 100 Pa 20 Pa ± 15% Cable conduit PG-11 or M20x1.5 with cable strain relief.
930.82 40 200 Pa 20 Pa ± 15%
Arrangement of contacts
930.83 50 500 Pa 20 Pa ± 15%
930.85 200 1000 Pa 100 Pa ± 15% 2 NO 1 Break contact
930.86 500 2500 Pa 150 Pa ± 15% 3 COM 2 Operating contact
930.87 1000 4000 Pa 250 Pa ± 15% 1 NC 3 Power supply line
P
Switching pressure specifications apply to vertical installation
which is also the recommended position with pressure-pipe
connections pointing downwards. If the switches are installed Protection category
horizontally with AMP connection terminals uppermost, the
IP 54 with cover
switching values are approx. 20 Pa higher.
IP 00 without cover

Maximum operating pressure Approvals


CE marking according to EC Low Voltage Directive
10 kPa for all pressure ranges.
73/23/EEC.
Medium
Accessories
Air, non-combustible and non-aggressive gases.
See order matrix.
Temperature range
Medium and ambient temperature from –20°C to +85°C.
Storage temperature from –40°C to +85°C.

Diaphragm material
Silicone, tempered at 200°C, free of gas emissions.
Other materials available on request.

rh range -0 to +95%.

155
152
Differential pressure switches
930.8x Climair®
with adjustable switching pressure

930.8x Climair® Mounting bracket 6481

7
ø5
65 05

40
50

60 2

ø6

71
46
57 5

75
18

19
22

Mounting bracket 6482 2


59
ø4 5
5
8

90 5
65 5
19 5
10

40 ø5 10
60

Climaset® Climaset® Mounting bracket 6401 Mounting bracket 6402


6550/6556 6555/6557
ø6 ø4
40
18 5

ø5 0
0 ø5
ø4
ø6

55
50

70 5
65 5
60
100

21 5
10

60
ø 16
ø5

40 10
ø6 5 ø10
ø4 5 60
77
ø3 4

11
18

40

ø 16
ø 25

Beck GmbH
Druckkontrolltechnik
DB 930 ENG 10/02

P.O. Box 11 31
D-71140 Steinenbronn
Telephone +49 (71 57) 52 87-0
Telefax +49 (71 57) 52 87-83
e-mail sales@beck-sensors.com
http://www.beck-sensors.com