Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Installation and Commisioning of Eagle Controller

Download as pdf or txt
Download as pdf or txt
You are on page 1of 42

Installation &

Commissioning
EAGLE Controller Instructions

TABLE OF CONTENTS

Safety Information ................................................................ 2  LonWorks Communications ............................................. 27 


General Safety Information ............................................... 2  General Information ....................................................... 27 
Information as per EN 60730 ............................................ 2  Connecting to the LONWORKS Network ........................... 27 
WEEE Directive ................................................................ 2 
Standards, Approvals, etc. ................................................ 2  BACnet MS/TP Bus Connection ....................................... 28 
BACnet MS/TP Bus Considerations ............................... 28 
3rd-Party Software Licenses ............................................... 2  Connecting RS485-1 to BACnet MS/TP Buses .............. 28 
Connecting RS485-2 to BACnet MS/TP Buses .............. 30 
Specifications of Controller................................................. 3 
Modbus Connection .......................................................... 31 
System Overview .................................................................. 4  Modbus Considerations.................................................. 31 
Overview of Models .......................................................... 4  Connecting RS485-1 to the Modbus .............................. 31 
System Architecture .......................................................... 5  Connecting RS485-2 to the Modbus .............................. 32 
Bus and Port Connections ................................................ 6 
M-Bus Connection ............................................................. 33 
Mounting/Dismounting ...................................................... 12  M-Bus Considerations .................................................... 33 
Before Installation ........................................................... 12  M-Bus Connection Procedure ........................................ 34 
Dimensions ..................................................................... 12 
Troubleshooting ................................................................ 35 
Wiring and Set-Up .............................................................. 14  EAGLE Controller Troubleshooting ................................ 35 
General Safety Considerations ....................................... 14  Panel Bus I/O Module Troubleshooting .......................... 35 
Wiring Terminals ............................................................. 14 
Power Supply .................................................................. 14  Appendix 1: Earth Grounding ........................................... 36 
Terminal Assignment ...................................................... 15  EAGLE Systems and SELV ........................................... 36 
RIN-APU24 ..................................................................... 16  EAGLE Systems and Standard EN60204-1 ................... 36 
Lightning Protection ........................................................ 16  Earth Grounding of EN60204-1 Applicable Systems ...... 37 
CLEA2026Bxx Connection Examples ............................. 17 
Internal I/Os of the EAGLE ............................................. 19  Appendix 2 ......................................................................... 39 
Sensor Input Accuracy ................................................... 39 
Engineering, Commissioning ............................................ 21  Recognition of Sensor Failure of Sensor Inputs ............. 39 
Required Preparations .................................................... 21  Sensor Characteristics ................................................... 39 
Behavior of Outputs during Download ............................ 21 
Index ................................................................................... 42 
Extra Parts .......................................................................... 22 

Panel Bus Connection ....................................................... 23 


Overview of Panel Bus I/O Modules ............................... 23  Trademark Information
Panel Bus Considerations ............................................... 23  LON, LONWORKS, and Neuron are trademarks of Echelon
Connecting RS485-1 to Panel Buses.............................. 24  Corporation registered in the United States and other
Connecting RS485-2 to Panel Buses.............................. 25  countries.
Cable Specifications ....................................................... 26 

® U.S. Registered Trademark


Copyright © 2016 Honeywell Inc. • All Rights Reserved EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

SAFETY INFORMATION Table 1. Information as per EN 60730


Shock protection Class II
General Safety Information Pollution degree 2
► When performing any work, all instructions given by the
manufacturer and in particular the safety instructions Installation Class 3
provided in these Installation and Commissioning Rated impulse voltage 330 V for SELV, 2500 V for relay
Instructions are to be observed. Make sure that the local outputs
standards and regulations are observed at all times.
Automatic action Type 1.C (micro-interruption for
► The EAGLE System (including the EAGLE Controller, the relay outputs)
Panel Bus I/O modules, manual disconnect modules, and
Software class Class A
auxiliary terminal packages) may be installed and mounted
only by authorized and trained personnel. Ball-pressure test housing parts >75 °C
► If the controller housing is damaged or missing, temperature terminals >125 °C
immediately disconnect it from any power.
► If the device is broken or defective, do not attempt to repair WEEE Directive
it yourself; rather, return it to the manufacturer.
WEEE: Waste Electrical and Electronic
► Always check these Installation Instructions in order to Equipment Directive
determine which relay terminals are suitable for 230 V.  At the end of the product life, dispose
Connect only suitable relay terminals to 230 V. of the packaging and product in an
► It is recommended that devices be kept at room tem- appropriate recycling center.
perature for at least 24 hours before applying power. This  Do not dispose of the device with the
is to allow any condensation resulting from low shipping / usual domestic refuse.
storage temperatures to evaporate.  Do not burn the device.
► The EAGLE System must be installed in such a manner
(e.g., in a lockable cabinet) as to ensure that uncertified
persons have no access to the terminals. Standards, Approvals, etc.
► In the case of vertical mounting on DIN rails, the EAGLE Degree of Protection: IP20 (mounted on walls, with two
controller should be secured in place using a accessory MVC-80-AC1 covers)
commercially-available stopper. IP30 (mounted in cabinet doors, with
► If the EAGLE System is modified in any way, except by the
accessory MVC-80-AC2)
manufacturer, all warranties concerning operation and Device meets BTL, AMEV AS-A, EN 60730-1, EN 60730-2-
safety are invalidated. 9, UL60730, and UL916.
► Rules regarding electrostatic discharge should be followed. Refer to Code of Practice standards IEC 61000-5-1 and -2
► Use only accessory equipment which comes from or has for guidance.
been approved by Honeywell. The device complies with Ethernet Protocol versions IEEEC
802.3.
Information as per EN 60730 The device supports BACnet IP and BACnet MS/TP
Purpose communications as per ANSI / ASHRAE 135-2010.
The purpose of the device is: OPERATING CONTROL. The
EAGLE Controller is a multifunctional non-safety control
device intended for HVAC in home (residential, commercial, 3RD-PARTY SOFTWARE LICENSES
and light-industrial) environments. This product contains software provided by third parties. See
also EAGLE Controller – Third-Party Software Licenses
(Product Literature No.: EN2Z-0991GE51).
Construction
The EAGLE Controller is an independently mounted
electronic control unit with fixed wiring.

Mounting Method
The EAGLE Controller is suitable for mounting as follows:
► in cabinets;
► in fuse boxes conforming with standard DIN43880, and
having a slot height of max. 45 mm;
► in cabinet front doors (using accessory MVC-80-AC2);
► on walls (using accessory MVC-80-AC1).

EN1Z-0970GE51 R0216 2
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

SPECIFICATIONS OF CONTROLLER
Table 2. EAGLE specifications
19 … 29 VAC, 50/60 Hz or
Power supply
20 … 30 VDC
typically dc: 5 W; max. 6 W
Power consumption
typically ac: 9 VA; max. 11 VA
typically dc: 210 mA; max. 240 mA
Current consumption
typically ac: 370 mA; max. 410 mA
0 … 40 °C (wall-mounting)
Ambient temperature
0 … 50 °C (cabinet/door mounting)
Storage temperature -20 … +70 °C
Humidity 5 … 95% r.h. non-condensing
Dimensions See Fig. 18 and Fig. 20.
IP20 (mounted on walls, with two accessory MVC-80-AC1 covers)
Degree of protection
IP30 (mounted in cabinet doors, with accessory MVC-80-AC2)
Fire class V0
Weight 0.6 kg (excl. packaging)

3 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

SYSTEM OVERVIEW
Overview of Models
Table 3. Overview of models
order no.

CLEA2014B21

CLEA2014B31

CLEA2014B22

CLEA2014B32

CLEA2026B21

CLEA2026B31

CLEA2000B21

CLEA2000B31
max. cable
feature description
length

NTC10kΩ / NTC20kΩ / 0…10V / slow BI 400 m 4 4 4 4 8 8 - -


UI
NTC10kΩ / NTC20kΩ / 0…10V fix pull-up / slow BI 400 m - - - - 2 2 - -
BI open = 24 V / closed 2.0 mA / totalizer 15 Hz 400 m 4 4 4 4 4 4 - -
AO 0..11 V (max. 1 mA) 400 m 2 2 2 2 4 4 - -
Relay N.O. contact 400 m 3 3 3 3 4 4 - -
BO Relay N.O. contact (high in-rush) 400 m 1 1 1 1 1 1 - -
Relay N.O. contact with one common 400 m - - - - 3 3 - -
(1)
RS485-1, isolated, BACnet MS/TP, Panel Bus , or Modbus RTU (2)
1200 m 1 1 1 1 1 1 1 1
Master communication
(1)
RS485-2, non-isolated, BACnet MS/TP, Panel Bus , or Modbus (2)
1200 m 1 1 1 1 1 1 1 1
RTU Master communication
Ethernet / RJ45 e-mail communication, browser access 100 m - - 1 1 1 1 1 1
bus
interfaces socket BACnet IP communication 100 m - - 1 1 1 1 1 1
USB 2.0 Device Interface (as Network Interface) 3m 1 1 1 1 1 1 1 1
USB 2.0 Host Interface (max. 500 mA) 3m 1 1 1 1 1 1 1 1
(3)
RS232 M-Bus communication via PW3 / PW20 / PW60 converters 1000 m 1 1 1 1 1 1 1 1
HMI with graphic LCD -- X - X - X - X -
user
Fast Access buttons -- 6 - 6 - 6 - 6 -
interface
push and turn button -- 1 - 1 - 1 - 1 -
power LED (green) -- 1 1 1 1 1 1 1 1
status LED (red, controllable by firmware) -- 1 1 1 1 1 1 1 1
LEDs applications-specific LED L1 (yellow) -- 1 1 1 1 1 1 1 1
USB LED L2 (yellow) -- 1 1 1 1 1 1 1 1
bus status LEDs (for isolated RS485-1 interface) -- 2 2 2 2 2 2 2 2
Socket for
RJ45 socket for connection of CLEAHMI21 External HMI 5m -- X -- X -- X -- X
CLEAHMI21
(1)
See also section "Restriction Applying to CLEA2014B21 and CLEA2014B31" on pg. 8.
(2)
Depending upon baud rate. For max. cable lengths, see section "RS485 Standard" on pg. 9. In the case of the Panel Bus, see also section
"Panel Bus Considerations" on pg. 23. In the case of the BACnet MS/TP Bus, see also section "BACnet MS/TP Bus Considerations" on pg. 28.
In the case of the Modbus, see also section "Modbus Considerations" on pg. 31.
(3)
Depending upon baud rate. See also section "M-Bus Considerations" on pg. 33.

EN1Z-0970GE51 R0216 4
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

System Architecture
An EAGLE System consists of the EAGLE Controller and various Panel Bus I/O modules. The EAGLE Controller provides
interface connections, which allow connection to external systems (e.g., BACnet controllers). Via the IF-LON External Interface,
the EAGLE can also communicate with LONWORKS systems, including CentraLine LONWORKS I/O Modules.
Auxiliary parts (see section “Extra Parts” on page 22) enable special features.

ENERGY
MOBILE
MANAGEMENT ARENA
AX
DEVICES
ESSENTIALS
BACnet IP

BTL

BTL

FALCON EAGLE HAWK


EXTERNAL HMI

LONWORKS BACnet MS/TP BTL


BACnet MS/TP BTL

CLIOL8... HON Inverter LYNX BACnet LYNX BACnet

LONWORKS PANEL BUS LONWORKS

XL 10/12 local CLIOP8... remote CLIOP8... CLIOL8... XL 10/12 LYNX LonWorks

LONWORKS LONWORKS

SERVAL IF-LON SERVAL CLIOL8... XL 10/12

M-BUS

Modbus M-BUS

Modbus

Fire, Security,
CCTV

Room Control
(HON wireless)

evohome

Fig. 1. CentraLine BACnet System architecture

5 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Bus and Port Connections 1 8

Overview

MID
BIAS
END
WARNING J1 J8

Risk of electric shock or equipment damage!


2 3
► Do not touch any live parts in the cabinet!
Fig. 4. All models (side view)
► Disconnect the power supply before making connections
to or removing connections from terminals of the EAGLE
Controller or Panel Bus I/O modules. Legend
1 RS232 / RJ45 socket (for M-Bus connection and
► Do not reconnect the power supply until you have
factory debugging)
completed installation.
2 USB 2.0 Host Interface (for connection to IF-LON)
► It is prohibited to power the EAGLE Controller with the
same transformer used to power other controllers or 3 Ethernet / RJ45 socket (for BACnet IP communication)
devices (e.g., the PW M-Bus Adapter). – all models except CLEA2014B21 and CLEA2014B31
► Observe the rules regarding electrostatic discharge. 4 RS485-1* (isolated; for BACnet MS/TP, Panel Bus, or
Modbus RTU Master communication)
5 RS485-2* (non-isolated; for BACnet MS/TP, Panel
8 Bus, or Modbus RTU Master communication)
1 2 3 4 5 6 7 6 LEDs
7 USB 2.0 Device Interface (for connection to CARE /
XW-Online and web browsers, CL-Touch, or other 3rd-
24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 party touch panels)
BIAS
END
RS232

MID

GND1

GND2
485-1+

485-2+
485-1-

485-2-

GND

UI10
BI1

UI1
BI2
BI3

UI9

UI2
UI3

UI6
UI7
UI8
BI4

UI4
UI5

RS485-1
8 Three-position slide switch (for setting bias and ter-
mination resistance of RS485-1)
9 RJ45 socket for connection of CLEAHMI21 External
HMI – CLEA2000B31, CLEA2014B31, CLEA2014B32,
CLEA2026B31, only
GND
DO1

AO1
24V-0

DO2
DO3

DO7

DO8

AO2
AO3
DO4

DO5

DO6

AO4
24V~

IN4

IN5
IN6

IN7
IN8
IN

1 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
* Modbus RTU Master communication is possible on either
one of the two RS485 interfaces, but not on both of them
concurrently.
NOTE: In the case of the CLEA2014B21 and
Fig. 2. Models with built-in HMI (top view) CLEA2014B31, at least one of the two RS485
interfaces must be assigned to BACnet MS/TP. The
other RS485 interface can then be assigned to either
8 Panel Bus, Modbus, or BACnet MS/TP.
1 2 3 4 5 6 7

WARNING
24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
BIAS
END
RS232

MID

GND1

GND2
485-1+

485-2+
485-1-

485-2-

GND

UI10
BI1

UI1
BI2
BI3

UI9

UI2
UI3

UI5
UI6
UI7
UI8
BI4

UI4

RS485-1
Risk of electric shock or equipment damage!
► It is prohibited to connect any of the RJ45 sockets of the
J1 J8
EAGLE Controller to a so-called PoE-enabled device
("Power over Ethernet").
GND
DO1

AO1
24V-0

DO2
DO3

DO5

DO6
DO7

DO8

AO2
AO3
DO4

AO4
24V~

IN7
IN8
IN4

IN5
IN6
IN

1 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

9
Fig. 3. Models without built-in HMI (top view)

EN1Z-0970GE51 R0216 6
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

RS232 / RJ45 Socket


Via its RS232 / RJ45 socket, the EAGLE Controller can be
connected (using an XW586 cable) to a PW M-Bus Adapter
and thus to M-Bus networks. See also section "M-Bus
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
Connection" on pg. 33.

GND

UI10
n.a.

BI1

UI1
BI2

UI2
BI3

UI9

UI3

UI5
UI6
UI7
UI8
BI4

UI4
J8 J1

USB 2.0 Device Interface


Fig. 7. USB 2.0 Device Interface
MID
BIAS
END

A standard USB type-B connector can be inserted into this


USB 2.0 Device Interface. This USB 2.0 Device Interface is
the recommended interface for connection to CARE.
RS232-RJ45 SOCKET
Fig. 5. RS232 / RJ45 socket Ethernet / RJ45 Socket
All models of the EAGLE Controller (except CLEA2014B21
USB 2.0 Host Interface and CLEA2014B31) are equipped with an Ethernet / RJ45
Via its USB 2.0 Host interface, the EAGLE Controller can be socket featuring one LED.
connected to, e.g., the IF-LON External Interface Adapter and
thus to LONWORKS networks. Max. 500 mA, high speed. See
also section "LonWorks Communications" on pg. 27.

J8 J1

J8 J1

MID
BIAS
END
MID
BIAS
END

Ethernet / RJ45 socket


Fig. 8. Ethernet / RJ45 socket (CLEA2000Bxx,
CLEA2014Bx2, and CLEA2026Bxx, only)
USB 2.0 Host Interface
Fig. 6. USB 2.0 Host interface This Ethernet / RJ45 socket is a 10/100-Mbaud Ethernet
interface permitting communication (as per IEEEC 802.3) on
BACnet IP networks.
USB 2.0 Device Interface
All models of the EAGLE Controller are equipped with a USB
2.0 Device Interface at the front. This interface is for LINK/ACT.
connection to CARE / XW-Online and web browsers, CL-
rd
Touch, or other 3 -party touch panels.

Fig. 9. Ethernet / RJ45 socket

NOTE: The Ethernet / RJ45 socket is usually earth-


grounded. For additional information on earth
grounding, see also “Appendix 1: Earth Grounding”
on pg. 36.

7 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

RS485-1 Bias and Termination Resistors


LEDs RS485-1 is equipped with a three-position slide switch which
The EAGLE Controller features the following LEDs: can be used to switch its bias resistors OFF (position “MID” –
this is the default), ON (position “BIAS”), and ON with an
additional 150Ω termination resistor (position “END”).

J8 J1

Fig. 10. EAGLE Controller LEDs

MID
BIAS
END
Table 4. EAGLE Controller LEDs
symbol color function, description
application-specific LED indicating status

MID
BIAS
END
L1 yellow information (“Cooling Mode”, “Heating
Mode” “Service Interval” etc.)
Indicates connection of operationally ready
L2 yellow
device to USB 2.0 Host Interface.
RS485-1 status LED indicating trans- RS485-1
Tx yellow
mission of communication signals. 3-POSITION SLIDE SWITCH
RS485-1 status LED indicating reception Fig. 11. RS485-1 three-position slide switch
Rx yellow
of communication signals.
status LED indicating hardware problems, The recommended slide switch setting depends upon the
! red lack of application, sensor failure, or Panel location and usage of the given EAGLE – see Fig. 12 and
Bus failure Table 5; it also depends upon the selected communication
green power LED protocol (BACnet MS/TP, Panel Bus, or Modbus RTU Master
communication, respectively).
See also section “EAGLE Controller Troubleshooting” on
page 35 for a detailed description of the behaviors of the Tx Table 5. Recommended slide switch settings
and Rx LEDs, the status LED, and the power LED and their setting remarks
meanings. Controllers located on either end of bus should have
END
this setting.
RS485 Interfaces BIAS
In small bus networks, a min. of one and a max. of
General two controllers should have this setting.
The EAGLE Controller features two RS485 interfaces: All other controllers (not set to “END” or “BIAS”) on
MID
 RS485-1 (consisting of push-in terminals 24 [GND-1], 25, bus should have this setting (which is the default).
and 26) is isolated and can be used for BACnet MS/TP
bus, Panel Bus, or Modbus RTU Master communication.
+5VISO
 RS485-2 (consisting of push-in terminals 29, 30, and 31
[GND-2]) is non-isolated (i.e. GND-2 is internally con- 47 kOHM
nected with terminal 1 [24V~0] and terminals 19+37 MID (DEFAULT)
[system ground]) and can be used for BACnet MS/TP bus,
Panel Bus, or Modbus RTU Master communication.
RS485-1 (+) 25
Restriction Applying to CLEA2014B21 and CLEA2014B31
MID
BIAS
END

In the case of the CLEA2014B21 and CLEA2014B31, CARE


RS485-1 (-) 26
automatically assigns a minimum of one of the two RS485
interfaces to BACnet MS/TP. Although the user has the
47 kOHM
option of shifting this assignment from the automatically
assigned RS485 interface to the other, the user cannot alter
GND-1
the fact that a minimum of one of the two RS485 interfaces Fig. 12. RS485-1 three-position slide switch setting MID
will be assigned to BACnet MS/TP. Thus, in the case of the
CLEA2014B21 and CLEA2014B31, the total max. no. of
Panel Bus I/O modules is reduced from 128 to only 64.

EN1Z-0970GE51 R0216 8
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

+5VISO +5V
550 OHM 550 OHM
BIAS
RS485-1 (+) 25 RS485-2 (+) 30
130 OHM
MID
BIAS
END

RS485-1 (-) 26 RS485-2 (-) 31


550 OHM 550 OHM
GND-1 GND-2
Fig. 13. RS485-1 three-position slide switch setting BIAS Fig. 15. RS485-2 bias and termination resistors

NOTE: GND-2 is internally connected with 24V-0


+5VISO (terminal 1) and system GND (terminals 19+37)
550 OHM
END RS485 Standard
RS485-1 (+) 25 According to the RS485 standard (TIA/EIA-485: “Electrical
Characteristics of Generators and Receivers for Use in
150 OHM Balanced Digital Multipoint Systems”), only one driver com-
municating via an RS485 interface may transmit data at a
MID
BIAS
END

RS485-1 (-) 26 time. Further, according to U.L. requirements, each RS485


interface may be loaded with a max. of 32 unit loads. E.g.,
550 OHM CentraLine devices have as little as ¼ unit load each, so that
up to 128 devices can be connected.
GND-1 BACnet MS/TP connections to the RS485 interfaces must
Fig. 14. RS485-1 three-position slide switch setting END comply with the aforementioned RS485 standard. Thus, it is
recommended that each end of every connection be equipped
with one termination resistor having a resistance equal to the
NOTE: All terminals are protected (up to 24 Vac) against
cable impedance (120 Ω / 0.25 – 0.5 W).
short-circuiting and incorrect wiring – except when
the 3-position slide switch is set to “END,” in which RS485 systems frequently lack a separate signal ground wire.
case the terminals of the RS485-1 bus (24, 25, and However, the laws of physics still require that a solid ground
26) have no such protection. Higher voltages may connection be provided for in order to ensure error-free
damage the device. communication between drivers and receivers – unless all of
the devices are electrically isolated and no earth grounding
exists.
NOTE: According to BACnet standards, a minimum of one
and a maximum of two BACnet devices must have
its/their bias resistors switched ON. In the case of IMPORTANT
the RS485-1 interface of the EAGLE, setting its slide In the case of new EAGLE controller installations, we
switch to either "BIAS" or "END" fulfills this require- strongly recommend using a separate signal ground
ment. wire. Doing otherwise may possibly lead to
unpredictable behavior if other electrically non-isolated
devices are connected and the potential difference is
RS485-2 Bias and Termination Resistors too high.
The RS485-2 interface is not affected by the aforementioned In the case of the installation of EAGLE controllers in
three-position slide switch. The 550Ω bias resistors and 130Ω already-existent RS485 two-wire systems (e.g., when
termination resistor of the RS485-2 are thus always ON. replacing PANTHER or LION controllers with EAGLE
controllers), not using a separate signal ground wire
will probably have no undesirable effects.

The cable length affects the baud rate. The following table
provides a few examples.

9 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Table 6. Baud rate vs. max. cable length for RS485 For connection details, see section "Modbus Connection" on
Baud rate Max. cable length (L) pg. 31.
9.6 - 76.8 kbps 1200 m
Shielding
*115.2 kbps 800 m
Shielding is especially recommended when the Modbus cable
** In the case of configuration of RS485-2 for Panel Bus, the is installed in areas with expected or actual electromagnetic
communication rate is set to 115.2 kbps. noise. Avoiding such areas is to be preferred.
Use shielded twisted pair cable shielded twisted pair cable J-
For information on wire gauge, max. permissible cable length, Y-(St)-Y 2 x 2 x 0,8 and connect the Modbus to a noise-free
possible shielding and grounding requirements, and the max. earth ground – only once per Modbus connection.
number of devices which can be connected to a bus, refer to
standard EIA-485. RS485 Repeaters
RS485 repeaters are possible, but have not been tested by
Modbus Connection Honeywell. Hence it is within responsibility of the
The EAGLE controller can function as a Modbus Master. installing/commissioning person to ensure proper function.
In general, the RS485 wiring rules must be followed. NOTE: Each Modbus segment will require its own line
polarization and line termination.
Wiring Topology
Only daisy-chain wiring topology is allowed. Modbus Master Specifications
Modbus Compliance
As per the Modbus standard, the EAGLE controller is a con-
MODBUS MODBUS MODBUS ditionally compliant "regular" Modbus device.
MASTER SLAVE SLAVE
The EAGLE controller differs from an unconditionally com-
pliant "regular" Modbus device in that it does not support
communication rates of 1.2, 2.4, and 4.8 kBaud (because
these communication rates are not market-relevant).
MODBUS MODBUS
SLAVE SLAVE
Physical Layer
Fig. 16. Allowed Modbus wiring topology 2-wire serial line RS485 (EIA-485) (with additional common)
Communication rates: 9.6, 19.2, 38.4, 57.6, 76.8, and
Other wiring topologies (e.g., star wiring, or mixed star wiring 115.2 kBaud supported.
and daisy chain wiring) are prohibited; this is to avoid com- Max. number of devices: 32
munication problems of the physical layer. Cable and wiring specifications: See section "Wiring and Set-
Up" on pg. 14.
MODBUS MODBUS MODBUS
MASTER SLAVE SLAVE Communication Mode
Modbus Master.

Transmission Mode
RTU (Remote Terminal Unit)

Address Range
MODBUS MODBUS MODBUS
SLAVE SLAVE SLAVE Modbus slaves can have an address between 1 and 247.
Discrete Inputs, Coils, Input Registers and Holding Registers
can have an address between 1 and 65534.
MODBUS
SLAVE
Function Codes
Fig. 17. Prohibited Modbus wiring topology (example) The following function codes are supported:
Table 7. Supported function codes
Cables function code (hex) function
See also section "EIA 485 Cable Specifications" on pg. 26. 02 Read Discrete Inputs
Use shielded twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8. 01 Read Coils
05 Write Single Coil
You must use three wires:
04 Read Input Register
 One wire for D1 = Modbus + 03 Read Holding Register
 One wire for D0 = Modbus – 06 Write Single Register
10 Write Multiple Registers
 One wire for the signal common
When using one pair for D1 and D0 and one wire of another Exception Codes
pair for the signal common, CAT5 cable may also be used. Upon reception of any of the following exception codes,
datapoints of the EAGLE application will show "no response."

EN1Z-0970GE51 R0216 10
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Table 8. Supported exception codes Bit Unpack


exception code (hex) function The EAGLE allows direct reading of single bits of an Input
01 illegal function Register or of a Holding Register into a data-point.
02 illegal data address In typical situations in which several different status bits of a
03 illegal data value Modbus slave’s Register need to be read and linked into the
04 slave device failure EAGLE application, this allows for very efficient application
05 acknowledge engineering.
06 slave device busy
Number of Stop Bits
Register Sizes One and two stop bits are supported.
The following Register sizes are supported:
 16-bit Registers for Discrete inputs, Coils, Input Registers, Error Checking Mode
and Holding Registers
Parity checking: No parity, even parity, odd parity.
 32-bit Registers for Input Registers and Holding Registers.
Frame checking: Cyclical redundancy checking (CRC).
Data Types
The following data types are supported: Life Check of Modbus Slaves
 Discrete Inputs: The EAGLE checks the Modbus every 15 seconds for lost
- BOOL Modbus slave devices.
 Coils:
- BOOL Message Response Timeout
 Input Registers: 20 msec ... 5000 msec.
- BOOL
- INT16, UINT16 Modbus Slaves Scan Cycle
- INT32, UINT32 The measurement cycle of all addressable Modbus slaves
- FLOAT depends upon the number of connected Modbus slaves and
 Holding Registers: the total number of mapped datapoints. The minimum
- BOOL measurement cycle is 500 msec. This cycle time is based
- INT16, UINT16 upon the read cycle of the datapoint manager in the firmware.
- INT32, UINT32
- FLOAT Modbus Communication Failure Indication
- 32-bit floating points can be transmitted as two As soon as the EAGLE runs an application which includes
consecutive 16-bit registers. Modbus points, it will try to communicate with the Modbus
devices based on the Modbus to datapoint mapping of the
Byte and Word Order Transmission application.
 Most Significant Byte First (default) If a Modbus slave does not respond to a message from the
 Lower Significant Byte First EAGLE controller, the message will be repeated two times. If
the Modbus slave does not respond to the two message
 Most Significant Word first (default) repeats either, the EAGLE will stall the messaging to this
 Lower Significant Word first Modbus slave for 15 seconds. After these 15 seconds, the
Modbus slave will be again addressed with the same two
repeats, if necessary. This cycle will be repeated endlessly.
If the EAGLE does not receive any response for a duration of
six (6) seconds, the System Alarm "MODB COMM ERROR"
will be issued.

11 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

MOUNTING/DISMOUNTING
Before Installation
IMPORTANT
To allow the evaporation of any condensation resulting from low shipping / storage temperatures, keep the controller at
room temperature for at least 24 h before applying power.
US requirement, only: This device must be installed in a UL-listed enclosure offering adequate space to maintain the
segregation of line voltage field wiring and Class 2 field wiring.
In the case of vertical mounting on DIN rails, the EAGLE controller should be secured in place using a commercially-available
stopper.
See also the EAGLE Mounting Instructions (MU1Z-0970GE51).

Dimensions
215.5 57.5
49.5

24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
BIAS
RS232

END

MID

GND1

GND2
485-1+

485-2+
485-1-

485-2-

GND

UI10
BI1

UI1
BI2

UI2
BI3
BI4

UI9

UI3
UI4
UI5
UI6
UI7
UI8
RS485-1

55.5

110
GND
45 52
BO1

AO1
24V-0

BO2
BO3

BO4

BO5

BO6
BO7

BO8

AO2
AO3
AO4
24V~

IN8
IN4

IN5
IN6

IN7
IN

1 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

Fig. 18. EAGLE Controller with built-in HMI, dimensions (in mm)

215.5 57.5
49.5

24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
BIAS
RS232

END

MID

GND1

GND2
485-1+

485-2+
485-1-

485-2-

GND

UI10
BI1

UI1
BI2
BI3

UI9

UI2
UI3

UI6
UI7
UI8
BI4

UI4
UI5

RS485-1 110

J1 J8

45 52
GND
BO1

AO1
24V-0

BO2
BO3

BO6
BO7

BO8

AO2
AO3
BO4

BO5

AO4
24V~

IN5
IN6

IN7
IN8
IN4
IN

1 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

Fig. 19. EAGLE Controller with RJ45 socket for connection of CLEAHMI21 External HMI, dimensions (in mm)

EN1Z-0970GE51 R0216 12
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

215.5 57.5

55.5

147
52

Fig. 20. EAGLE Controller with built-in HMI (with MVC-80-AC1), dimensions (in mm)
215.5 57.5

147
J1 J8

52

Fig. 21. EAGLE Controller with RJ45 socket for CLEAHMI21 External HMI (with MVC-80-AC1), dimensions (in mm)
NOTE: Use of the covers (MVC-80-AC1) obstructs access to the Ethernet and USB 2.0 Host Interfaces and RS232 socket.

13 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

WIRING AND SET-UP


General Safety Considerations
 All wiring must comply with applicable electrical codes and
ordinances, including VDE, National Electric Code (NEC)
or equivalent, and any local regulations must be observed.
Refer to job or manufacturer’s drawings for details. Local
wiring guidelines (e.g., IEC 364-6-61 or VDE 0100) may
take precedence over recommendations provided here. Fig. 22. Inserting/removing wires from push-in terminals
 Electrical work should be carried out by a qualified
electrician. NOTE: With solid conductors, ferrules are prohibited.
 Electrical connections must be made at terminal blocks. NOTE: Use only one conductor per push-in terminal.
 For Europe only: To comply with CE requirements, devices NOTE: If, nevertheless, two stranded wires are to be
with a voltage in the range of 50 ... 1000 VAC or 75 ... connected to a single push-in terminal, twin wire end
1500 VDC which are not provided with a supply cord and ferrules must be used.
plug or with other means for disconnection from the supply
having a contact separation of at least 3 mm in all poles
must have the means for disconnection incorporated in the Table 9. EAGLE push-in terminal wiring specifications
2
fixed wiring. plug gauge 0.2 … 1.50 mm
2
solid conductor H05(07) V-K 0.2 … 1.50 mm
2
stranded conductor H05(07) V-K 0.2 … 1.50 mm
WARNING stranded conductor with wire end 2
0.2 … 1.50 mm
ferrules (w/o plastic collar)
Risk of electric shock or equipment damage! stripping length 10.0 +1.0 mm
► Observe precautions for handling electrostatic sensitive
devices.
► Do not touch any live parts in the cabinet. Power Supply
► Do not open the controller housing.
► Disconnect the power supply before making connections to
Powering EAGLE
or removing connections from terminals of the EAGLE Power is supplied via a removable terminal plug (attached to
Controller and devices wired to it. terminals 1 and 2). See also Fig. 25.
► Do not use spare terminals as wiring support points. The power supply of the EAGLE Controller must conform to
► Mixing of different voltages (e.g., 24 V and 230 V) within Safety Class II. To reduce overall current consumption, the
individual relay blocks of the EAGLE is not allowed EAGLE can be powered by a switch power supply (rather
► To prevent risk of injury due to electrical shock and/or than by a transformer). See also Table 2 on pg. 3.
damage to the device due to short-circuiting, low-voltage NOTE: Danger of short-circuiting when another controller
and high-voltage lines must be kept separate from one besides the EAGLE Controller is supplied by the
another. same transformer if proper polarity is not ensured.
► All terminals are protected (up to 24 Vac) against short- See Fig. 23.
circuiting and incorrect wiring (unless the 3-position slide
switch is set to “END,” in which case the terminals of the N, L
RS485-1 bus [24, 25, and 26] have no such protection). EARTH GROUND
SHORT-CIRCUITING!
Higher voltages may damage the device.
► Do not reconnect the power supply until you have PC 1 PC 2

completed the installation.


CPU 1 CPU 2
USB 2.0

Fusing Specifications Device Interface

24V~0 24V~ 24V~0 24V~


System Fusing
We recommend that the user equip the system with an 1 2 1 2

external fuse. REVERSED


! POLARITY!
24 V~
L
Fusing of Active Field Devices LINE
N
F2 (depends upon loads in use). 24 V~0 NOISE-FREE EARTH GROUND
(ONLY ONE PER SYSTEM)

Fig. 23. Incorrect polarity → SHORT-CIRCUITING!


Wiring Terminals
The EAGLE is equipped with push-in terminal plugs.

EN1Z-0970GE51 R0216 14
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Terminal Assignment
Table 10. Terminal assignment

CLEA2014Bxx

CLEA2026Bxx

CLEA2000Bxx
terminal no.

signal Description

1 24V-0 supply voltage (GND), internally connected with term. 31 and system GND (term. 19+37) X X X
2 24V~ supply voltage (24V) X X X
3,4 - not used - - -
5 BO1 Binary output 1. N.O. relay contact switching input power connected to terminal 8 - X -
6 BO2 Binary output 2. N.O. relay contact switching input power connected to terminal 8 - X -
7 BO3 Binary output 3. N.O. relay contact switching input power connected to terminal 8 - X -
8 IN1,2,3 Common relay contact for BO1, BO2, and BO3 - X -
9 IN4 Relay contact for BO4 X X -
10 BO4 Binary output 4. N.O. relay contact switching input power connected to terminal 9 X X -
11 BO5 Binary output 5. N.O. relay contact switching input power connected to terminal 12 X X -
12 IN5 Relay contact for BO5 X X -
13 IN6 Relay contact for BO6 X X -
14 BO6 Binary output 6. N.O. relay contact switching input power connected to terminal 13 X X -
15 BO7 Binary output 7. N.O. relay contact switching input power connected to terminal 16 X X -
16 IN7 Relay contact for BO7 X X -
17 IN8 Relay contact for BO8 - X -
18 BO8 Binary output 8. N.O. relay contact switching input power connected to terminal 17 - X -
19 GND Ground terminal (see NOTE below) X X -
20 AO1 Analog output 1 X X -
21 AO2 Analog output 2 X X -
22 AO3 Analog output 3 - X -
23 AO4 Analog output 4 - X -
24 GND-1 ref. GND of RS485-1 (isolated) X X X
25 485-1+ “+” signal for RS485-1 (isolated) X X X
26 485-1- “-” signal for RS485-1 (isolated) X X X
27,28 not used - - -
29 485-2+ “+” signal for RS485-2 (non-isolated) X X X
30 485-2- “-” signal for RS485-2 (non-isolated) X X X
31 GND-2 ref. GND of RS485-2, int. connected with 24V-0 (term. 1) and system GND (term. 19+37) X X X
32 - not used - - -
33 BI1 Binary input 1 (static dry contact) / pulse counter (fast totalizer) X X -
34 BI2 Binary input 2 (static dry contact) / pulse counter (fast totalizer) X X -
35 BI3 Binary input 3 (static dry contact) / pulse counter (fast totalizer) X X -
36 BI4 Binary input 4 (static dry contact) / pulse counter (fast totalizer) X X -
37 GND Ground terminal (see NOTE below) X X -
38 UI9 Universal input 9 (for NTC10kΩ / NTC20kΩ / 0..10V / slow BI) - X -
39 UI10 Universal input 10 (for NTC10kΩ / NTC20kΩ / 0..10V / slow BI) - X -
40 UI1 Universal input 1 (for NTC10kΩ / NTC20kΩ / 0..10V / slow BI) X X -
41 UI2 Universal input 2 (for NTC10kΩ / NTC20kΩ / 0..10V / slow BI) X X -
42 UI3 Universal input 3 (for NTC10kΩ / NTC20kΩ / 0..10V / slow BI) X X -
43 UI4 Universal input 4 (for NTC10kΩ / NTC20kΩ / 0..10V / slow BI) X X -
44 UI5 Universal input 5 (for NTC10kΩ / NTC20kΩ / 0..10V / slow BI) - X -
45 UI6 Universal input 6 (for NTC10kΩ / NTC20kΩ / 0..10V / slow BI) - X -
46 UI7 Universal input 7 (for NTC10kΩ / NTC20kΩ / 0..10V / slow BI) - X -
47 UI8 Universal input 8 (for NTC10kΩ / NTC20kΩ / 0..10V / slow BI) - X -

NOTE: All AOs, UIs, and BIs share the same ground potential. It is thus possible to connect just one combined GND signal for
all AOs, UIs, and BIs. Auxiliary terminals may be used if needed.

15 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Transformer Data signal disturbances on the 0…10 V / sensor cables.


In Europe, if the EAGLE is powered by transformers, then See also section “Cable Specifications” on page 26.
such transformers must be safety isolating transformers
conforming to IEC61558-2-6. Powering Field Devices and EAGLE via Separate Transformers
In the U.S. and Canada, if the EAGLE is powered by trans-  24 V actuator connected to separate transformer
formers, then such transformers must be NEC Class-2
 Field device located max. 400 m from EAGLE
transformers.

Table 11. 1450 series transformers data 24 V0 230 V~


24 V~
part #
primary side secondary side F2
1450 7287 EAGLE

-001 120 Vac 24 Vac, 50 VA 230 V~ 24 V~ 2


Y (0...10 Vdc)
24V~
24 V0 1 20...23 Y
2 x 24 Vac, 40 VA, and 100 VA
-002 120 Vac 19 GND
from separate transformer
24 Vac, 100 VA, and 24 Vdc, 600 max. 400 m
-003 120 Vac
mA Fig. 25. Power supply of EAGLE and field devices by
-004 240/220 Vac 24 Vac, 50 VA separate transformer
2 x 24 Vac, 40 VA, and 100 VA
-005 240/220 Vac
from separate transformer Powering Field Devices and Panel Bus I/O Module via Separate
24 Vac, 100 VA, and 24 Vdc, Transformers
-006 240/220 Vac
600 mA  24 V actuator connected to, e.g., an analog output module
 Field device located 100 … 400 m from the Panel Bus I/O
Table 12. Overview of CRT Series AC/DC current module
primary max. AC max. DC
transformer
side current current 24 V0
230 V~
CRT 2 230 Vac 2A 500 mA 24 V~
F1 CLIOP822A F2
CRT 6 230 Vac 6A 1300 mA
24 V~ 73 24V~
230 V~ Y (0...10 Vdc)
CRT 12 230 Vac 12 A 2500 mA 24 V0 74 1...8 Y
11...18 GND

PRIMARY
SIDE EAGLE
max. 400 m
Fig. 26. Power supply via a separate transformer

230 Vac 24 V~ 2
Powering Field Devices via Panel Bus I/O Module
120 Vac 24 V0 1  24 V actuator connected to, e.g., an analog output module
 Field device located max. 100 m from the Panel Bus I/O
module
NOT
RECOMMENDED
F2
Fig. 24. Connection of EAGLE Controller
F1 CLIOP822A

RIN-APU24 230 V~
24 V~ 73
74 1...8
Y (0...10 Vdc)
24V~
Y
24 V0
The RIN-APU24 Uninterruptable Power Supply can be 11...18 GND
directly wired to an EAGLE Controller.
See RIN-APU24 Uninterruptable Power Supply – Mounting max. 100 m
Instructions (EN0B-0382GE51) for a detailed wiring diagram.
Fig. 27. Power supply via Panel Bus I/O Module

Powering Panel Bus I/O Modules and Field Devices


The EAGLE, Panel Bus I/O modules, and field devices can be
Lightning Protection
powered by either separate transformers (see Fig. 25, Fig. 26, Please contact your local Honeywell representative for
and Fig. 27) or by the same transformer (see Fig. 28 on pg. information on lightning protection.
17).
NOTE: Use a min. distance of 10 cm between power cables
and 0…10 V / sensor cables in order to prevent

EN1Z-0970GE51 R0216 16
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

CLEA2026Bxx Connection Examples


DRY NTC20kOHM NTC20kOHM ACTIVE SENSOR
TOTALIZER
CONTACT SENSOR SENSOR 1: GND (24V~0)
1: GND
1: GND 1: GND 1: GND 2: 24V~ POWER
2: SIGNAL
2: SIGNAL 2: SIGNAL 2: SIGNAL 3: 0...10 VDC
1 2 1 2 1 2 1 2 1 2 3

37/GND

37/GND

37/GND

37/GND
1 2

24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
GND1

GND2
485-1+

485-2+
485-1-

485-2-

GND

UI10
n.a.
n.a.

n.a.

BI1

UI1
BI2

UI9

UI2

UI7
UI8
BI3

UI3

UI5
UI6
BI4

UI4
CLEA2026Bxx
~
BLOCK 1 BLOCK 2

GND
BO1

AO1
24V-0

BO2
BO3

BO7

BO8

AO2
AO3
BO5

BO6
BO4

AO4
24V~

IN6

IN7
IN8
IN4

IN5
IN

1 2 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

L 1 2
N
FAN FAN
1 2 1 2
1: GND FAN 1: 230V N FAN
2: 24V~ 1: 24V~0 2: 230V~ 1: 24V~0
24Vac M
2: 24V~
M
2: 24V~

! WARNING 24V~ DRIVE with


0...10V SIGNAL 1 2 3
Risk of electric shock or equipment damage! 1: GND (24V~0)
Low voltage and line voltage must not be wired 2: 24V~ POWER
within the same block. 3: 0...10 VDC M 0...10 VDC

Fig. 28. CLEA2026Bxx connection example


For fusing specifications see section "Fusing Specifications" on page 14.
NOTE: Use a min. distance of 10 cm between power cables and 0…10 V / sensor cables in order to prevent signal
disturbances on the 0…10 V / sensor cables.

17 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

ACTIVE SENSOR DRY


1: GND (24V~0) CONTACT
2: 24V~ POWER 1: GND
3: 0...10 VDC 2: SIGNAL
1 2 3 1 2

40

A1 A2 A3 A4 A5 A6 A7 B1 B2 B3 B4 B5 B6 B7
XS830 33
1 2 3 4 5 6 7 1 2 3 4 5 6 7

2
1

24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
GND1

GND2
485-1+

485-2+
485-1-

485-2-

GND

UI10
n.a.
n.a.

n.a.

BI1

UI1
BI2

UI2
BI3

UI9

UI3

UI6
UI7
UI8
BI4

UI4
UI5
CLEA2026Bxx
~
BLOCK 1 BLOCK 2

GND
BO1

AO1
24V-0

BO2
BO3

BO7

BO8

AO2
AO3
BO5

BO6
BO4

AO4
24V~

n.a.
n.a.

IN7
IN8
IN5
IN6
IN4
IN

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

A1 A2 A3 A4 A5 A6 A7 B1 B2 B3 B4 B5 B6 B7
XS830
1 2 3 4 5 6 7 1 2 3 4 5 6 7

24Vac
14 15
L N
! WARNING FAN
1 2
FAN
1 2
FAN
1 2
Risk of electric shock or equipment damage! 1: 230V N 1: 230V N 1: 230V N
Low voltage and line voltage must not be wired 2: 230V~ 2: 230V~ 2: 230V~
within the same block. M M M

Fig. 29. CLEA2026Bxx connection example (with two XS830 Auxiliary Terminal Packages)
The XS830 and XS831 Auxiliary Terminal Packages are optional accessories which can be mounted onto the top and/or bottom
of the EAGLE Controller in order to equip them with additional terminals for the connection of, e.g., shields, sensors, GND, N,
230 V, or 24 V (but not earth!).
NOTE: Use a min. distance of 10 cm between power cables and 0…10 V / sensor cables in order to prevent signal
disturbances on the 0…10 V / sensor cables.

EN1Z-0970GE51 R0216 18
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Internal I/Os of the EAGLE


10 VDC
The CLEA2000Bxx is not equipped with inputs or outputs.
The following sub-sections thus apply only to the 25 k
CLEA2026Bxx and CLEA2014Bxx.

Universal Inputs Vi 200 k


The CLEA2026Bxx is equipped with ten (CLEA2014Bxx: four)
universal inputs (UIs) configurable (in CARE).
For information on the accuracy of the sensor inputs, their
GND
differential measurement error, the characteristics (i.e., re-
sistances and resultant voltages in dependence upon tem-
perature) of the various different sensor types which can be Fig. 31. Internal wiring of UI1-UI10 configured for input
connected to them, and on the thresholds at which sensor from NTC10kΩ / NTC20kΩ / voltage input (with pull-up
failures are recognized, see section “Appendix 2” on page 39. resistor)
Table 13. Specifications of UIs
Slow Binary Input Specifications
criteria value
When configured as slow binary inputs, the universal inputs of
voltage input  UI1-UI10: 0 … 10 VDC with pull-up resistor the EAGLE have the following specifications:
(default)
 UI1-UI8: 0…10 VDC w/o pull-up resistor open contact ≥ 100 kΩ
 UI1-UI8: 2…10 VDC w/o pull-up resistor closed contact ≤ 100 Ω
current input  UI1-UI10: 0 … 10 VDC w/o pull-up resistor,
external 499Ω resistor required to measure The polarity (normal = N.O. contact or reverse = N.C. contact)
0…20 mA configuration defines if a logical 1 or a logical 0 is detected for
a closed contact. This is done by selecting (in CARE) one of
 UI1-UI8: 2…10 VDC w/o pull-up resistor, the following options:
external 499Ω resistor required to measure
4…20 mA
closed external contact → state=1
supported  NTC10kΩ (-30…+100 °C) normal (default)
sensor types open external contact → state=0
 NTC20kΩ (-50…+150 °C) closed external contact → state=0
reverse
 Slow binary input (static, dry-contact) open external contact → state=1
resolution 12-bit resolution
accuracy ±75 mV (0 ... 10 V) Pulse Counter Specifications
Using CARE, the universal inputs of the EAGLE can be con-
protection against short-circuiting, 24 VAC
figured as pulse counters (totalizers).
If the duty cycle is 50% / 50%, the pulse counter supports up
to 0.4 Hz. Counting is done on the rising edge.
Table 14. UIs of EAGLE configured as slow BIs
frequency max. 0.4 Hz
pulse ON min. 1.25 s
pulse OFF min. 1.25 s
Vi 200 k
bounce max. 50 ms

GND Analog Outputs


The CLEA2026Bxx is equipped with four (CLEA2014Bxx: two)
Fig. 30 Internal wiring of UI1-UI8 configured for voltage analog outputs (AOs).
input (without pull-up resistor) In the event of an application stop (e.g., during application
download), the analog outputs assume the safety positions
configured in CARE.
The analog outputs can be configured in CARE as binary
outputs (with an output of 0 V or 10 V, as the case may be).

19 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Table 15. Specifications of AOs Table 17. BIs of EAGLE configured as fast totalizers
criteria value frequency max. 15 Hz
 0…10 V (default) pulse ON min. 25 ms
output type
 2…10 V
pulse OFF min. 25 ms
max. output range 0 … 11 VDC (1 mA)
min. resolution 8 bit bounce max. 5 ms
min. accuracy ± 150 mV
max. wire length 400 m
24V
wire cross section See Table 9 on pg. 14.
protection against short-circuiting, 24 VAC

Binary Inputs / Pulse Counters BI

Both the CLEA2026Bxx and the CLEA2014Bxx are equipped DRY CONTACT
24 VDC = open
with four binary inputs (static dry-contact inputs) / pulse 0 V = closed

counters (fast totalizers).


COM
Table 16. Specifications of BIs FAST
TOTALIZER GND
criteria value
 binary input (static dry-contact) Fig. 32. Internal wiring of BI
input type
 pulse counter (fast totalizer)
current rating
2 mA
Binary Outputs
(closed input) The EAGLE features eight (CLEA2026Bxx) or four
open contact (CLEA2014Bxx) binary outputs arranged in two blocks
24 VDC (BO1…4 and BO5..8, respectively).
voltage
protection against short-circuiting, 24 VAC

Binary Input Specifications WARNING


The binary inputs of the EAGLE are static dry-contact inputs.
This reduces the wiring effort, as it is then not necessary to Risk of electric shock or equipment damage!
distribute an auxiliary voltage signal. Low voltage and line voltage must not be wired within
the same block.
open contact ≥ 3000 Ω (24 VDC on BI terminal)
closed contact ≤ 500 Ω (short-circuit current: 2.0 mA)
In the event of an application stop (e.g., during application
download), the binary outputs assume the safety positions
The polarity (normal = N.O. contact or reverse = N.C. contact) configured in CARE.
configuration defines if a logical 1 or a logical 0 is detected for
The polarity (normal = N.O. contact or reverse = N.C. contact)
a closed contact. This is done by selecting (in CARE) one of
configuration defines if a relay is open or closed, depending
the following options:
upon whether there is a logical 1 or a logical 0. This is done
by selecting (in CARE) one of the following options:
closed external contact → state=1
normal (default)
open external contact → state=0 state=1 → relay contact is closed
closed external contact → state=0 normal (default)
reverse state=0 → relay contact is opened
open external contact → state=1 state=0 → relay contact is closed
reverse
state=1 → relay contact is opened
Pulse Counter Specifications
Using CARE, the binary inputs of the EAGLE can be con-
figured as pulse counters (fast totalizers) for operation in
conjunction with devices equipped with an open collector
output.
If the duty cycle is 50% / 50%, the pulse counter supports up
to 15 Hz. Counting is done on the rising edge.

EN1Z-0970GE51 R0216 20
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Table 18. Relay specifications of the EAGLE For access via USB, the EAGLE Controller has a permanent
block 1 block 2 default IP address 192.168.255.241. Your PC's IP address
must match the EAGLE Controller's default IP address sub-
BO1…3 BO4 BO5…8
net: We recommend using DHCP or “Obtain an automatic IP
contact volt. AC 5…253 V 5…253 V 5…253 V address”.
contact volt. DC 5…30 V 20…30 V 5…30 V
max. contact cur-
3A 10 A 3A Option 2: Standard Ethernet Interface
rent AC (resistive) The standard IP address can be set in CARE. For this
max. contact cur- purpose, connect first with the USB interface. In any case,
0.3 A* 10 A 0.3 A*
rent AC (induct.) your PC's IP address must match the EAGLE Controller's
max. contact cur- default IP address subnet. We recommend using DHCP or
2 A** 10 A 2 A** “Obtain an automatic IP address”.
rent AC (induct.)
max. contact cur-
3A 7A 3A
rent DC Behavior of Outputs during Download
100 mA / 40 mA / 100 mA / Table 19. Behavior of outputs during firmware download /
min. load
5 Vdc 24 Vdc 5 Vdc application download
* typically 250,000 cycles; ** typically 50,000 cycles output behavior during output behavior
analog, binary, and
firmware / Linux during application
floating outputs
download download
NOTE: The total max. sum load for all binary outputs
(BO1…8) equals 14 A. Outputs remain in
onboard outputs
Outputs go to 0 / OFF. the previous
NOTE: Binary output 4 supports the switching of high in- of EAGLE, itself
position / state
rush currents (e.g., motors, incandescent lights,
etc.). The max. allowed switch current is 80 A for a As soon as "receive
duration of max. 20 ms. heartbeat" (the value
outputs of Panel Outputs remain in
of which CANNOT be
I/O modules the previous
altered using CARE)
(CLIOP82x) position / state
ENGINEERING, COMMISSIONING expires, outputs go to
safety position.
Please refer also to CARE User Guide (Product Literature
No.: EN2B-0182GE51) for detailed information. As soon as "receive
outputs of heartbeat" (the value
Outputs remain in
LONWORKS I/O of which can be
the previous
Required Preparations modules altered using CARE)
position / state.
In order to access (with a laptop or PC) the EAGLE Controller (CLIOL82x) expires, outputs go to
via Ethernet/IP for the first time, you may employ any one of safety position.
the following two options:
NOTE: These behaviors were determined using a test
Option 1: USB 2.0 Device (recommended) application with a cycle time of 10 seconds. A value
update was triggered every 10 seconds.
This USB 2.0 Device interface is the recommended interface
for downloading applications and firmware via CARE. An “A-
Male to B-Male” USB cable is required.

Fig. 33. A-male to B-male USB cable

21 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

EXTRA PARTS
Table 20. Extra parts
order number description
Removable terminal plugs, push-in type; complete set of 9 plugs (for
TPU-45-01
terminals 1 - 47); for the CLEA2014Bxx and CLEA2026Bxx.

Removable terminal plugs, push-in type; complete set of 3 plugs (for


TPU-11-01
terminals 1 - 47); for the CLEA2000Bxx.

Terminal cover (color: RAL9011); package of 10; for EAGLE


MVC-80-AC1
Controllers.

Front door mounting accessory (color: RAL9011); package of 10; for


MVC-80-AC2
EAGLE Controllers.

MVC-40-AC3 Strain relief; package of ten; for EAGLE Controllers.

Set of ten packages. Each Auxiliary Terminal Package consists of two


groups of nine internally connected push-in terminals, for distributing
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9 XS830 signals / power. For the Mixed Panel Bus I/O Module and the EAGLE
Controller, only. Please refer to CentraLine I/O Modules - Installation &
Commissioning Instructions (EN1Z-0973GE51) for more information.
Set of ten packages. Each Auxiliary Terminal Package consists of two
groups of four pairs of push-in terminals (each with a 499 Ω resistor),
for converting 0…20 mA signals into 0…10 VDC signals, and one
A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 B7 A8 B8 G2 XS831 push-in ground terminal per group. For the Mixed Panel Bus I/O
Module and the EAGLE Controller, only. Please refer to CentraLine I/O
Modules - Installation & Commissioning Instructions (EN1Z-0973GE51)
for more information.

External HMI with LCD display which derives needed electrical energy
from the EAGLE controller. Suitable for connection to the RJ45 socket
CLEAHMI21
on the front of the CLEA2000B31, CLEA2014B31, CLEA2014B32, and
CLEA2026B31.

EN1Z-0970GE51 R0216 22
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

PANEL BUS CONNECTION


The EAGLE Controller features two RS485 interfaces to which Panel Bus modules can be connected: RS485-1 (consisting of
push-in terminals 24 [GND-1], 25, and 26) and/or RS485-2 (consisting of push-in terminals 29, 30, and 31 [GND-2]).
NOTE: GND-2 is internally connected with 24V-0 (terminal 1) and system GND (terminals 19+37)

Overview of Panel Bus I/O Modules


pluggable
pluggable pluggable pluggable pluggable
FLOATING
MIXED I/Os
ANALOG INPUT ANALOG OUTPUT BINARY INPUT RELAY OUTPUT (with integrated electronic module)
OUTPUT

PANEL BUS I/O CLIOPR822A CLIOPR824A CLIOPR825A CLIOP830A


ELECTRONIC
MODULES Honeywell
B7
7
Binary Inputs
B8
8
B9
9
B10 B11 B12
10 11 12
Analog Inputs
AI5
17
AI6
18
AI7
19
AI8
20
GND Analog Outputs
AO5 AO6 AO7 AO8
25 26 27 28 35
24V Relays
CO1 CO2 CO3 CO4 CO5 CO6
36 37 38 39 40
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 G1 G2 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
!
Install. Instr. 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
MU1B-0473GE51 DI DO

CLIOP821A CLIOP822A CLIOP823A CLIOP824A CLIOP831A

Honeywell Binary Inputs Analog Inputs GND Analog Outputs 24V Relays

PANEL BUS PANEL BUS PANEL BUS PANEL BUS


B7 B8 B9 B10 B11 B12 AI5 AI6 AI7 AI8 AO5 AO6 AO7 AO8 CO1 CO2 CO3 CO4 CO5 CO6
7 8 9 10 11 12 17 18 19 20 25 26 27 28 35 36 37 38 39 40
1 2 3 4 5 6 13 14 15 16 41 42 21 22 23 24 29 30 31 32 33 34
B1 B2 B3 B4 B5 B6 AI1 AI2 AI3 AI4 G1 G2 AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
!
Install. Instr. 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6
MU1B-0473GE51 DI DO

XS821-22 XS823 XS824-25


XSU821-22 XSU823 XSU824-25 CLIOP830A
EAGLE CLIOP831A
Fig. 34. Overview of Panel Bus I/O Modules

Panel Bus Considerations


 RS485-1 (isolated)
- Max. Panel Bus length:
o 40 meters. Any type of cabling and topology (including star and loop topology) possible. No additional end
termination permitted.
o 800 meters. Mandatory twisted-pair or telephone cable and daisy chain topology. The EAGLE must be positioned
at one end of the Panel Bus, and an end termination (120 Ω) at the other end. Further, the three-position slide
switch (see Fig. 11 on pg. 8) must be set to "END."
 RS485-2 (non-isolated)
- Max. Panel Bus length:
o 40 meters. Any type of cabling and topology (including star and loop topology) possible. No additional end
termination permitted.
o 800 meters. Mandatory twisted-pair or telephone cable and daisy chain topology. The EAGLE Controller must be
positioned at one end of the Panel Bus, and an end termination (120 Ω) at the other end.
- Must not extend beyond a single building or building floor
 Max. no. of Panel Bus I/O modules per RS485 interface
- Max. no. of Panel Bus I/O modules of a given model: 16
- Total max. no. of Panel Bus I/O modules: 64
 Max. no. of Panel Bus I/O modules per EAGLE
- Max. no. of Panel Bus I/O modules of a given model: 32
- Total max. no. of Panel Bus I/O modules: 128 (see NOTE below)
 Max. no. of hardware I/O points + NVs per EAGLE: 600
- Max. no. of mapped NVs allowed per EAGLE is thus 600 minus the no. of hardware I/O points.
NOTE: In the case of the CLEA2014B21 and CLEA2014B31, the total max. no. of Panel Bus I/O modules is reduced from
128 to only 64. See also section "Restriction Applying to CLEA2014B21 and CLEA2014B31" on pg. 8.
Refer to CentraLine I/O Modules - Installation & Commissioning Instructions (EN1Z-0973GE51) for more information about
connection, current requirements, power supply, overvoltage protection, cable specifications, fusing, effects of manual overrides,
etc. of Panel Bus I/O modules and field devices connected to them.

23 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Connecting RS485-1 to Panel Buses


NOTE: When connecting RS485-1 of the EAGLE with Panel Bus I/O modules, it is recommended that the slide switch be set
to “END.”
CentraLine I/O Module CentraLine I/O Module CentraLine I/O Module
71 Com a 75 71 Com a 75 71 Com a 75
RS485-1 72 Com b 76 72 Com b 76 72 Com b 76
73 24V~ 77 73 24V~ 77 73 24V~ 77
EAGLE 74 24~0 78 74 24~0 78 74 24~0 78
242526
GND-1

+5VISO GND-1
550 OHM 150 OHM 550 OHM

RS485-1 (+) RS485-1 (-) CentraLine I/O Module CentraLine I/O Module
71 Com a 75 71 Com a 75
24V~
24~0

RT 72 Com b 76 72 Com b 76
END 120 Ohm
1 2 73 24V~ 77 73 24V~ 77
74 24~0 78 74 24~0 78
MID
BIAS
END

F1

24 V

230 V

Fig. 35. Connecting RS485-1 of the EAGLE with Panel Bus I/O Modules (single transformer)

CentraLine I/O Module CentraLine I/O Module CentraLine I/O Module


71 Com a 75 71 Com a 75 71 Com a 75
RS485-1 72 Com b 76 72 Com b 76 72 Com b 76
73 24V~ 77 73 24V~ 77 73 24V~ 77
EAGLE 74 24~0 78 74 24~0 78 74 24~0 78
242526
GND-1

+5VISO GND-1
550 OHM 150 OHM 550 OHM

RS485-1 (+) RS485-1 (-) CentraLine I/O Module CentraLine I/O Module
71 Com a 75 71 Com a 75
24V~
24~0

RT 72 Com b 76 72 Com b 76
END 120 Ohm
1 2 73 24V~ 77 73 24V~ 77
74 24~0 78 74 24~0 78
MID
BIAS
END

F1 F1

24 V 24 V

230 V 230 V

Fig. 36. Connecting RS485-1 of the EAGLE with Panel Bus I/O Modules (two transformers)

EN1Z-0970GE51 R0216 24
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Connecting RS485-2 to Panel Buses


CentraLine I/O Module CentraLine I/O Module CentraLine I/O Module
71 Com a 75 71 Com a 75 71 Com a 75
RS485-2 72 Com b 76 72 Com b 76 72 Com b 76
73 24V~ 77 73 24V~ 77 73 24V~ 77
EAGLE 74 24~0 78 74 24~0 78 74 24~0 78
2930 31
GND-2

+5VISO GND-2
550 OHM 130 OHM 550 OHM

RS485-2 (+) RS485-2 (-) CentraLine I/O Module CentraLine I/O Module
NO EFFECT ON RS485-2 71 Com a 75 71 Com a 75
24V~
24~0

RT 72 Com b 76 72 Com b 76
120 Ohm
1 2 73 24V~ 77 73 24V~ 77
74 24~0 78 74 24~0 78
MID
BIAS
END

F1

24 V

230 V

Fig. 37. Connecting RS485-2 of the EAGLE with Panel Bus I/O Modules (single transformer)

CentraLine I/O Module CentraLine I/O Module CentraLine I/O Module


71 Com a 75 71 Com a 75 71 Com a 75
RS485-2 72 Com b 76 72 Com b 76 72 Com b 76
73 24V~ 77 73 24V~ 77 73 24V~ 77
EAGLE 74 24~0 78 74 24~0 78 74 24~0 78
2930 31
GND-2

+5VISO GND-2
550 OHM 130 OHM 550 OHM

RS485-2 (+) RS485-2 (-) CentraLine I/O Module CentraLine I/O Module
NO EFFECT ON RS485-2 71 Com a 75 71 Com a 75
24V~
24~0

RT 72 Com b 76 72 Com b 76
120 Ohm
1 2 73 24V~ 77 73 24V~ 77
74 24~0 78 74 24~0 78
MID
BIAS
END

F1 F1

24 V 24 V

230 V 230 V

Fig. 38. Connecting RS485-2 of the EAGLE with Panel Bus I/O Modules (two transformers)

25 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Cable Specifications Field Devices


Panel Bus I/O Modules Depending on the distance from the controller, field devices
can be supplied with power by the same transformer used for
When checking the length of the power supply cable, the
the Panel Bus I/O Modules, or by a separate transformer,
connection cables to all Panel Bus I/O Modules must be
using cables as specified in Table 23.
taken into account.
Table 23. Power / communication cable specifications
Table 21. Power supply cable specifications
cross-sectional area
max. length 3 m (from transformer to final module)
2
type of signal  100 m (Fig. 27)  400 m (Fig. 26)
cross section min. 0.75 mm (AWG 18)
single transformer sep. transformers
2 not allowed for
EIA 485 Cable Specifications 24 VAC power 1.5 mm (16 AWG)
> 100 m (300 ft)
The following cable specification is valid for all EIA 485 buses 2
(e.g., Panel Bus and BACnet MS/TP). 0…10 V signals 0.081 – 2.08 mm (28 – 14 AWG)
Table 22. EIA 485 cable specifications
max. length 1000 m For wiring field devices, see section “Powering Panel Bus I/O
Modules and Field Devices” on page 16.
twisted pair, shielded (foil or braided
cable type
shields are acceptable)
Routing Cables to Field Devices
characteristic Route low-voltage signal and output cables to field devices
100…130 Ω
impedance separately from mains cables.
distributed Table 24. Minimum distances to power mains cables
capacitance Less than 100 pF per meter (30 pF per cable min. distance
between foot)
shielded 10 mm (0.4 in.)
conductors
unshielded 100 mm (4 in.)
distributed
capacitance
Less than 200 pF per meter (60 pF per All low-voltage signal and output cables should be regarded
between
foot) as communication circuits in accordance with VDE 0100 and
conductors and
VDE 0800 (or NEC or other equivalent).
shield
 If the general guidelines for cable routing are observed, it
is not necessary to shield field device signal and power
The following cables fulfill this requirement: supply cables.
 AWG 18;  If, for whatever reason, the routing guidelines cannot be
 shielded, twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8; observed, the field device signal and power supply cables
 CAT 5,6,7 cable (use only one single pair for one bus); must be shielded.
 Belden 9842 or 9842NH. – Shielding of cables leading to field devices must be
grounded only at one end.
– Do not connect the shield to the EAGLE Controller.

EN1Z-0970GE51 R0216 26
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

LONWORKS COMMUNICATIONS
General Information IF-LON
The EAGLE can be connected to LONWORKS networks. This
requires the use of an IF-LON (see section "IF-LON" below),
which is then plugged into to the EAGLE's USB 2.0 Host
Interface (see also section "USB 2.0 Host Interface" on pg. 7). Fig. 39. IF-LON
This permits individual EAGLE controllers to be connected / See also IF-LON – Mounting Instructions (MU1B-0545GE51).
disconnected from the LONWORKS network without disturbing Depending upon the chosen network configuration, one or two
the operation of other devices. terminations may be required.
The LONWORKS network is insensitive to polarity, eliminating The following LONWORKS termination module is available:
the possibility of installation errors due to miswiring.  LONWORKS connection / termination module
Different network configurations (daisy-chain, loop, and star (mountable on DIN rails and in fuse boxes),
configurations, or any combination thereof) are possible (see order no.: XAL-Term2
also Excel 50/500 LONWORKS Mechanisms Interface
Description, EN0B-0270GE51). LONWORKS TERMINATION
PLUG-IN JUMPER

Connecting to the LONWORKS Network 1


5
IMPORTANT 2 6
Do not bundle wires carrying field device signals or
LONWORKS communications together with high-voltage
power supply or relay cables. Specifically, maintain a
min. separation of 3 inches (76 mm) between such PARK POSITION
cables. Local wiring codes may take precedence over (NO TERMINATION)

this recommendation.
IMPORTANT
Try to avoid installing in areas of high electromagnetic FTT/LPT BUS FTT/LPT FREE
noise (EMI). 3 4
FTT/LPT FTT/LPT
1 BUS TOPOLOGY: FREE TOPOLOGY:
2 5 105 OHM 52.3 OHM
6

Cable Types 1 1
100 μ 100 μ
The unit must be wired to the LONWORKS network using either
34 105 Ohm 52.3 Ohm
 level IV 22 AWG (Belden part number 9D220150)
100 μ 2 100 μ 2
or REMOVABLE SCREW-TYPE
2-POLE TERMINAL BLOCK
 plenum-rated level IV 22 AWG (Belden part number
9H2201504) non-shielded, twisted-pair, solid-conductor
Fig. 40. LONWORKS connection and termination module
wire.
When possible, use Honeywell AK3781, AK3782, AK3791, or
AK3792 cable (US part numbers). See Excel 50/5000
LONWORKS Mechanisms, EN0B-0270GE51, for details,
including maximum lengths.
Use wire with a minimum size of 20 AWG (0.5 mm2) and a
maximum size of 14 AWG (2.5 mm2).

IF-LON
The IF-LON is equipped with a free-topology transceiver
(FTT10A) for communication (at a data transmission rate of
78 Kbaud) on LONWORKS® networks (using the LonTalk
protocol).
The LONWORKS network is insensitive to polarity, eliminating
the possibility of installation errors due to miswiring. Different
network configurations (daisy-chain, loop, and star con-
figurations, or any combination thereof) are possible. See
Excel 50/5000 LONWORKS Mechanisms (EN0B-0270GE51)
for details.

27 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

BACNET MS/TP BUS CONNECTION


The EAGLE Controller features two RS485 interfaces to which BACnet MS/TP devices can be connected: RS485-1 (consisting
of push-in terminals 24 [GND-1], 25, and 26) and/or RS485-2 (consisting of push-in terminals 29, 30, and 31 [GND-2]).
NOTE: GND-2 is internally connected with 24V-0 (terminal 1) and system GND (terminals 19+37)

BACnet MS/TP Bus Considerations


 RS485-1 (isolated)
˗ Max. BACnet MS/TP bus length: 800-1200 meters, depending on baud rate (see section “RS485 Standard” on pg. 9)
˗ Use only shielded, twisted-pair cable and daisy-chain topology
˗ Must conform to EIA-RS485 cabling guidelines
 RS485-2 (non-isolated)
˗ Max. BACnet MS/TP bus length: 800-1200 meters, depending on baud rate (see section "RS485 Standard" on pg. 9)
˗ Use only shielded, twisted-pair cable and daisy-chain topology
˗ Ground noise should not exceed the EIA-485 common mode voltage limit
˗ Must conform to EIA-RS485 cabling guidelines
˗ Should not extend beyond a single building
 Max. no. of BACnet MS/TP devices
˗ The max. number of BACnet MS/TP devices per RS485 interface depends on the given traffic. The current limit is 200
messages per minute. The max. number of room controllers is 20, assuming a typical traffic of 10 messages per minute.
In the case of non-room applications, the max. number of MS/TP devices can be up to 32 (including the EAGLE, itself) –
provided the traffic does not exceed 200 messages per minute. Following the same logic, the max. number of BACnet
MS/TP devices per EAGLE is 40 room controllers or 62 non-room MS/TP devices – provided the traffic does not exceed
200 messages per minute per RS485 interface.

Connecting RS485-1 to BACnet MS/TP Buses


With regards to Fig. 41 through Fig. 43, please note the following:
NOTE: Always power each EAGLE and the connected BACnet MS/TP modules via separate transformers.
NOTE: For “L,” see section “RS485 Standard” on pg. 9.
NOTE: If any devices are not electrically isolated, signal ground connection is recommended. See section “RS485 Standard”
on pg. 9).

Example 1: Single EAGLE Controller and Connected BACnet Modules (with inserted termination resistor)
L

RT
120 Ohm

RS485-1

EAGLE
GND

GND

GND

GND

GND
RS485 +

RS485 +

RS485 +

RS485 +

RS485 +
RS485 -

RS485 -

RS485 -

RS485 -

RS485 -

242526
GND-1

+5VISO GND-1
BACnet BACnet BACnet BACnet BACnet
550 kOHM 150 kOHM 550 kOHM Module #2 Module #3 Module #4 Module #N-1 Module #N
RS485-1 (+) RS485-1 (-)
24V~
24~0

END
1 2
BACnet
MID
BIAS
END

Module #1

F1
24 V
*CONNECT GND, IF AVAILABLE.
230 V

Fig. 41. Connection of RS485-1 to a BACnet MS/TP Bus

The termination resistor must be inserted directly into the terminals of the last BACnet MS/TP module.

EN1Z-0970GE51 R0216 28
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Example 2: Multiple EAGLE Controllers and Connected BACnet Modules


L

RS485-1 RS485-1 RS485-1 RS485-1

EAGLE EAGLE EAGLE EAGLE

GND

GND
RS485 +

RS485 +
RS485 -

RS485 -
24 25 26 24 25 26 24 25 26 24 25 26
GND-1 GND-1 GND-1 GND-1

+5VISO GND-1
BACnet +5VISO GND-1
BACnet +5VISO GND-1 +5VISO GND-1
550 OHM 150 OHM 550 OHM Module #2 47 kOHM 47 kOHM Module #4 47 kOHM 47 kOHM 550 OHM 150 OHM 550 OHM

RS485-1 (+) RS485-1 (-) RS485-1 (+) RS485-1 (-) RS485-1 (+) RS485-1 (-) RS485-1 (+) RS485-1 (-)
24V~

24V~

24V~

24V~
24~0

24~0

24~0

24~0
END MID MID END
1 2 1 2 1 2 1 2
BACnet BACnet BACnet BACnet
MID
BIAS
END

MID
BIAS
END
MID
BIAS
END

MID
BIAS
END
Module #1 Module #3 Module #N-1 Module #N

F1 F1 F1 F1
24 V 24 V
*CONNECT GND, IF AVAILABLE. 24 V 24 V

230 V 230 V 230 V 230 V

Fig. 42. Connection of RS485-1 to a BACnet MS/TP Bus

Example 3: Multiple EAGLE Controllers and Connected BACnet Modules (with inserted termination resistor)
L

RT
120 Ohm

RS485-1 RS485-1 RS485-1 RS485-1

EAGLE EAGLE EAGLE EAGLE


GND

GND
RS485 +

RS485 +
RS485 -

24 25 26 24 25 26
RS485 - 24 25 26 24 25 26
GND-1 GND-1 GND-1 GND-1

+5VISO GND-1
BACnet +5VISO GND-1
BACnet +5VISO GND-1 +5VISO GND-1
550 OHM 150 OHM 550 OHM Module #2 47 kOHM 47 kOHM Module 47 kOHM 47 kOHM 550 OHM 550 OHM

RS485-1 (+) RS485-1 (-) RS485-1 (+) RS485-1 (-) RS485-1 (+) RS485-1 (-) RS485-1 (+) RS485-1 (-)
24V~

24V~

24V~

24V~
24~0

24~0

24~0

24~0
END MID MID BIAS
1 2 1 2 1 2 1 2
BACnet BACnet BACnet BACnet
MID
BIAS
END

MID
BIAS
END

MID
BIAS
END

MID
BIAS
END
Module #1 Module #3 Module #N-1 Module #N

F1 F1 F1 F1
24 V 24 V
*CONNECT GND, IF AVAILABLE. 24 V 24 V

230 V 230 V 230 V 230 V

Fig. 43. Connection of RS485-1 to a BACnet MS/TP Bus

The termination resistor must be inserted directly into the terminals of the last BACnet MS/TP module (in this example, that is
the rightmost EAGLE, the 3-position slide switch of which has been set to "BIAS.")

29 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Connecting RS485-2 to BACnet MS/TP Buses


With regards to Fig. 44 and Fig. 45, please note the following:
NOTE: Always power each EAGLE and the connected BACnet MS/TP modules via separate transformers.
NOTE: For “L,” see section “RS485 Standard” on pg. 9.
NOTE: If any devices are not electrically isolated, signal ground connection is recommended. See section “RS485 Standard”
on pg. 9).
NOTE: Between devices equipped with non-isolated RS485 bus interfaces, potential differences of max. ±7 V are allowed.
Further, this bus should not extend beyond a single building.

Example 1: Single EAGLE Controller and Connected BACnet Modules (with inserted termination resistor)
L

RT
120 Ohm

RS485-2

EAGLE
GND

GND

GND

GND

GND
RS485 +

RS485 +

RS485 +

RS485 +

RS485 +
RS485 -

RS485 -

RS485 -

RS485 -

RS485 -
2930 31
GND-2

+5V GND-2
BACnet BACnet BACnet BACnet BACnet
550 OHM 130 OHM 550 OHM Module #2 Module #3 Module #4 Module #N-1 Module #N
RS485-2 (+) RS485-2 (-)

NO EFFECT ON RS485-2
24V~
24~0

1 2
BACnet
MID
BIAS
END

Module #1

F1
24 V
*CONNECT GND, IF AVAILABLE.
230 V

Fig. 44. Connection of RS485-2 to a BACnet MS/TP Bus

The termination resistor must be inserted directly into the terminals of the last BACnet MS/TP module.

Example 2: Multiple EAGLE Controllers and Connected BACnet Modules


L

RS485-2 RS485-1 RS485-1 RS485-2

EAGLE EAGLE EAGLE EAGLE


GND

GND
RS485 +

RS485 +
RS485 -

RS485 -

29 30 31 24 25 26 24 25 26 29 30 31
GND-2 GND-1 GND-1 GND-2

+5V GND-2
BACnet +5VISO GND-1
BACnet +5VISO GND-1 +5V GND-2
550 OHM 130 OHM 550 OHM Module #2 47 kOHM 47 kOHM Module 47 kOHM 47 kOHM 550 OHM 130 OHM 550 OHM

RS485-2 (+) RS485-2 (-) RS485-1 (+) RS485-1 (-) RS485-1 (+) RS485-1 (-) RS485-2 (+) RS485-2 (-)

NO EFFECT ON RS485-2 NO EFFECT ON RS485-2


24V~

24V~

24V~

24V~
24~0

24~0

24~0

24~0

MID MID
1 2 1 2 1 2 1 2
BACnet BACnet BACnet BACnet
MID
BIAS
END

MID
BIAS
END
MID
BIAS
END

MID
BIAS
END

Module #1 Module #3 Module #N-1 Module #N

F1 F1 F1 F1
24 V 24 V
*CONNECT GND, IF AVAILABLE. 24 V 24 V

230 V 230 V 230 V 230 V

Fig. 45. Connection of RS485-2 to a BACnet MS/TP Bus

EN1Z-0970GE51 R0216 30
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

MODBUS CONNECTION
The EAGLE controller supports Modbus RTU Master functionality.
Modbus slaves can be connected to either of the two onboard RS485 interfaces (but not to both simultaneously): RS485-1
(consisting of push-in terminals 24 [GND-1], 25, and 26) or RS485-2 (consisting of push-in terminals 29, 30, 31 [GND-2]).
NOTE: GND-2 is internally connected with 24V-0 (terminal 1) and system GND (terminals 19+37)

Modbus Considerations
RS485-1 (isolated)

˗ Max. Modbus length: 800-1200 meters, depending on baud rate (see section “RS485 Standard” on pg. 9)
˗ Use only shielded, twisted-pair cable and daisy-chain topology
˗ Must conform to EIA-RS485 cabling guidelines
RS485-2 (non-isolated)

˗ Max. Modbus length: 800-1200 meters, depending on baud rate (see section "RS485 Standard" on pg. 9)
˗ Use only shielded, twisted-pair cable and daisy-chain topology
˗ Ground noise should not exceed the EIA-485 common mode voltage limit
˗ Must conform to EIA-RS485 cabling guidelines
˗ Should not extend beyond a single building
 Max. no of Modbus devices per EAGLE: 32 (including the EAGLE, itself, which is counted twice)

Connecting RS485-1 to the Modbus


With regards to Fig. 46, please note the following:
NOTE: Always power each EAGLE and the connected Modbus slaves via separate transformers.
NOTE: For “L,” see section “RS485 Standard” on pg. 9.
NOTE: If any devices are not electrically isolated, signal ground connection is recommended. See section “RS485 Standard”
on pg. 9).

Example: EAGLE Modbus Master Controller and Connected Modbus RTU Slaves (with inserted termination
resistor)
L

RT
120 Ohm

RS485-1

EAGLE
GND

GND

GND

GND

GND
RS485 +

RS485 +

RS485 +

RS485 +

RS485 +
RS485 -

RS485 -

RS485 -

RS485 -

RS485 -
242526
GND-1

+5VISO GND-1
Modbus Modbus Modbus Modbus Modbus
550 OHM 150 OHM 550 OHM Slave #1 Slave #2 Slave #3 Slave #N-1 Slave #N
RS485-1 (+) RS485-1 (-)
24V~
24~0

END
1 2
Modbus
MID
BIAS
END

Module

F1
24 V
*CONNECT GND, IF AVAILABLE.
230 V

Fig. 46. Connection of EAGLE Modbus Master Controller to Modbus RTU slaves via RS485-1

The termination resistor must be inserted directly into the terminals of the last Modbus RTU slave.

31 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Connecting RS485-2 to the Modbus


With regards to Fig. 47, please note the following:
NOTE: Always power each EAGLE and the connected Modbus slaves via separate transformers.
NOTE: For “L,” see section “RS485 Standard” on pg. 9.
NOTE: If any devices are not electrically isolated, signal ground connection is recommended. See section “RS485 Standard”
on pg. 9).
NOTE: Between devices equipped with non-isolated RS485 bus interfaces, potential differences of max. ±7 V are allowed.
Further, this bus should not extend beyond a single building.

Example: EAGLE Modbus Master Controller and Connected Modbus RTU Slaves (with inserted termination
resistor)
L

RT
120 Ohm

RS485-2

EAGLE
GND

GND

GND

GND

GND
RS485 +

RS485 +

RS485 +

RS485 +

RS485 +
RS485 -

RS485 -

RS485 -

RS485 -

RS485 -
2930 31
GND-2

+5V GND-2
Modbus Modbus Modbus Modbus Modbus
550 OHM 130 OHM 550 OHM Slave #1 Slave #2 Slave #3 Slave #N-1 Slave #N
RS485-2 (+) RS485-2 (-)

NO EFFECT ON RS485-2
24V~
24~0

1 2
Modbus
MID
BIAS
END

Module

F1
24 V
*CONNECT GND, IF AVAILABLE.
230 V

Fig. 47. Connection of EAGLE Modbus Master Controller to Modbus RTU slaves via RS485-2

The termination resistor must be inserted directly into the terminals of the last Modbus RTU slave.

EN1Z-0970GE51 R0216 32
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

M-BUS CONNECTION
The EAGLE controller supports M-Bus Master functionality 87654321
via its onboard RS232 / RJ45 socket.
It uses standard PW3/PW20/PW60 converters to connect to
the M-Bus devices.

Fig. 49. EAGLE RS232 / RJ45 socket


M-Bus Considerations
Max. no. of M-Bus devices per EAGLE: 60. Table 26. RS232-to-PW cable specifications
RJ45 plug, 9-Pin sub-D
Bus Length RS232 function
pin no. connector pin no.
 Max. M-Bus length: 350 meters from PW3 / PW20 / 1 DCD 1
PW60, at baud rates of 9.6 kbaud or slower with shielded,
2 RxD 2
twisted pair cable: J-Y-(St)-Y 2 x 2 x 0,8.
3 TxD 3
 The M-Bus can be extended to 1,000 meters, depending
upon the baud rate, and provided that the following 4 DTR 4
electrical limitations are observed: 5 GND 5
˗ Bus voltage must at no point fall below 12 VDC 6 DSR 6
˗ Maximum cable capacitance of 180 nF 7 RTS 7
For bus length extension, M-Bus repeaters can be used, but 8 CTS 8
have not been tested by Honeywell. Hence, it is the
-- Not used 9
responsibility of the installing / commissioning personnel to
ensure proper functioning.
RJ45 plug with clip at front RS232 plug
Wiring Topology SHIELD sub-D male

8 7 6 5 4 3 2 1
M-Bus meters are connected to the bus cable in parallel. DCD
DSR

5 4 3 2 1
RxD

9 8 7 6
RTS
TxD
SLAVE 1 SLAVE 2 SLAVE 3 CTS
DTR
+5V GND
PW
EAGLE CONVERTER

XW586
Fig. 48. Allowed M-Bus wiring topology
Fig. 50. XW586 power / communication cable details

Cabling EAGLE to PW3/PW20/PW60


 Use the XW586 cable between the RS232 / RJ45 socket Cabling PW3/PW20/PW60 to M-Bus
of the EAGLE and the PW adapters.  Use shielded, twisted pair cable J-Y-(St)-Y 2 x 2 x 0,8.
 The XW586 cable has a length of 1.8 m, and the pin-out  Shielding is especially recommended when the M-Bus
listed in Table 26. cable is installed in areas with expected or actual electro-
magnetic noise. Avoiding such areas is to be preferred.
 In case a third-party cable is used instead of the XW586
cable, the third-party cable must have a max. length of  Connect the shield to a noise-free earth ground – only
15 meters and a max. cable capacitance of 2,500 pF. once per M-Bus connection.
 Power the EAGLE controller and the PW M-Bus Adapter
Table 25. EAGLE RS232 / RJ45 socket specifications with separate transformers – see WARNING below.
RJ45 plug, NOTE: If, alternatively, only a single transformer is avail-
RS232 function able, when connecting a laptop, PC, web browser,
pin no. rd
CL-Touch, or 3 -party touch panel to the USB 2.0
1 Device Interface on the front of the EAGLE con-
2 RxD troller, use an optical isolator for the USB con-
3 TxD nection or substitute an M-Bus Mikro-Master USB
(Relay GmbH, D-33106 Paderborn) for the PW M-
4
Bus Adapter.
5 GND
6
7
8

33 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

M-Bus Connection Procedure EAGLE


1. Install the PW M-Bus Adapter on DIN rail. Insert a
screwdriver into the slot in the DIN rail clamp on the J8 J1

underside of the PW and pry downward to loosen clamp


until the unit snaps onto the rail.
RS232 / RJ45

MID
BIAS
END
SOCKET

XW586
M-BUS
DIN RAIL
DEVICE

Fig. 53. Connecting the EAGLE to the PW M-Bus adapter


3
4. Connect 24 V power to the M-Bus Adapter.

2
WARNING

Risk of electric shock or equipment damage!


Fig. 51. Mounting of PW (PW3 shown here) ► It is prohibited to power the EAGLE Controller with the
same transformer used to power other controllers or
2. Connect the M-Bus devices to the PW M-Bus Adapter. devices (e.g., the PW M-Bus Adapter).
All M+ and M- terminals are connected in parallel in the
PW M-Bus Adapter.
CLEAxxxxxx
INSERT
METER-BUS
WIRES CLEAxxxxxx

! PANTHER,
TIGER, LION,
etc.

PW3, PW20,
PW60, etc.

230 VAC 24 VAC


120 VAC 0V CLEAxxxxxx

230 VAC 24 VAC


120 VAC 0V CLEAxxxxxx
XW586

INSERT POWER 230 VAC 24 VAC


PANTHER,
SUPPLY WIRES 120 VAC 0V TIGER, LION,
etc.

Fig. 52. PW M-Bus adapter connections PW3, PW20,


230 VAC 24 VAC
120 VAC 0V PW60, etc.

3. Connect the PW M-Bus Adapter to the RS232 / RJ45


Fig. 54. Connecting power to the PW M-Bus adapter
socket of the EAGLE using the XW586 cable.

EN1Z-0970GE51 R0216 34
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

TROUBLESHOOTING
EAGLE Controller Troubleshooting
The following LEDs of the EAGLE Controller can be used for troubleshooting purposes:
 Power LED (green)
 Status LED (red)
 Tx (sending data on RS485-1) and Rx (receiving data on RS485-1) LEDs

Power LED (green) of EAGLE


Table 27. EAGLE Controller power LED
case power LED meaning remedy
1 ON Normal operation No action necessary.
2 OFF Power supply not OK. ► Check power supply voltage.
► Check wiring.
► If problem persists, replace hardware.

Status LED (red) of EAGLE


Table 28. EAGLE Controller status LED
case status LED meaning remedy
1 LED remains Normal operation. No action necessary.
OFF after
power-up
2 LED remains – No or invalid firmware, or ► Try powering down and then powering up the
ON – No or corrupt application, or EAGLE Controller.
continuously ► If problem persists, check and – if necessary –
after power-up – License invalid or feature missing, or
reload the application.
– I/O module not found or configuration
mismatch, or ► If problem still persists, replace hardware.

– Communication error, or
– Sensor failure on internal inputs, or
– Hardware error detected, or
– USB memory stick error.

Tx and Rx LEDs
Table 29. EAGLE Controller bus LEDs Tx and Rx
case bus LEDs meaning remedy
1 Both Tx and Rx Normal operation; RS485-1 is functioning No action necessary
are flashing properly.
2 Both Tx and Rx No communication on RS485-1. ► Switch ON communication on RS485-1. L1 should
are OFF then flash. Further handling like case 4 (below).
3 Rx is flashing Communication on RS485-1 has been ► Switch ON communication on RS485-1. If this
and Tx is OFF switched OFF, but the EAGLE is receiving proves unsuccessful, the hardware may be
data from other controllers. defective.
4 Tx is flashing The EAGLE Controller is attempting to ► The communication rate (Kbaud) on RS485-1 has
and Rx is OFF establish communication on RS485-1, but not been correctly set; other controllers on the bus
there is no answer. may have been incorrectly assigned the same
device number; wiring problem or hardware defect.

Panel Bus I/O Module Troubleshooting


Please refer to CentraLine I/O Modules - Installation & Commissioning Instructions (EN1Z-0973GE51) for more information
about Panel Bus I/O module troubleshooting.

35 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

APPENDIX 1: EARTH GROUNDING


EAGLE Systems and SELV When is EN60204-1 Applicable to EAGLE Systems?
In order to avoid distribution of noise or earth ground  Safety against electrical impact
potential differences over networks or other connections, the – EN60204-1 is not mandatory; this is because electrical
EAGLE Controller is designed to be in compliance with safety is provided by the use of SELV and
SELV (Safety Extra-Low Voltage). transformers according to standard EN60742.
Furthermore, SELV offers the greatest possible safety
 Safety against unexpected start-up of
against electrical impact.
rotating/moving machines
To support SELV, all Honeywell external (CRT series) or
internal transformers comply with standard EN60742. – If the application/plant does not contain machines that
Earth grounding is therefore not recommended. can be harmful to the operator due to an unexpected
start-up, the standard EN60204-1 is not applicable.
If such machines are encountered, then EN60204-1 must be
EAGLE Systems and Standard EN60204-1 followed. Grounding is required.
However, if compliance with EN60204-1 is required, note the
following:

General Information about EN60204-1


EN60204-1 defines electrical safety for a complete
application/machine including controllers, sensors, actuators
and any connected/controlled electrical device.
EN60204-1 requires controllers to be powered by PELV
(Protective Extra-Low Voltage) and earth grounding of the
secondary side of the used transformers or earth grounding
of the system ground.
Earth grounding is prescribed to prevent unexpected start-
up of connected rotating/moving machines due to an
insulation fault and double earth grounding somewhere in
the plant.
In order to fulfill PELV (if earth grounding is prohibited), the
use of an earth leakage monitor is also possible.

EN1Z-0970GE51 R0216 36
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Earth Grounding of EN60204-1 Applicable ► If system protective earth grounding is planned, use a
cable as short as possible for grounding:
Systems min. 1.5 mm² (16 AWG).
NOTE: Our recommendation is that each CPU be ► For connection details, refer to the following examples.
supplied with electricity from its own dedicated
transformer.

Example 1
The following explains how to connect and earth multiple
CPUs (e.g., multiple EAGLEs, PANTHERs, TIGERs, LIONs,
etc. or any combination thereof) earth-grounded as per
EN60204-1.
NOTE: Use a noise-free earth ground inside the cabinet.
NOTE: If a field device that prohibits earth grounding is
connected to the system ground, an isolation
monitoring device must be used instead of earth
grounding.
► Connect earth ground to the respective terminal of the
CPU, see Fig. 56.

CPU 1 I/O MODULE I/O MODULE

24V~0 24V~ RS485-2 + RS485-2 -


COM COM 24V~ 24V~0 COM COM 24V~ 24V~0
A B A B

1 2 29 30 71 72 73 74 71 72 73 74
FIELD DEVICE

24 V~
L 24 V~

LINE Y

N 24 V~0
GND

NOISE-FREE EARTH GROUND


(ONLY ONE PER SYSTEM)

CPU 2

24V~0 24V~ RS485-2 + RS485-2 -


RECOMMENDED
1 2 29 30

24 V~
L
LINE
N 24 V~0

NOISE-FREE EARTH GROUND


(ONLY ONE PER SYSTEM)

Fig. 55. Connecting and earthing multiple CPUs


(RECOMMENDED USE OF SEPARATE
TRANSFORMERS)

37 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

Example 2
When connecting multiple CPUs to a single transformer, it is
imperative that the polarity of the power supply terminals of
the CPUs and the polarity of the transformer always cor-
respond (namely: 24V-0 of the transformer must always be
connected to 24V-0 of the CPU, and 24V~ of the trans-
former must always be connected with 24V~ of the CPU).
Depending upon the individual CPU, the numbering of the
corresponding two terminals may possibly deviate from the
norm (which is usually "terminal 1 = 24V-0" and "terminal 2 =
24V~"). In the following example, CPU 3 has a deviating
numbering and must be connected accordingly.
NOTE: When using a single transformer for several
CPUs, each CPU ground must wired separately
to the star-point.
NOTE: If the field device transformer is physically far
away from the CPUs, earth grounding must still
be performed for the controller.
NOTE: Use one star-point to split power for multiple
CPUs and field devices.

► Connect earth ground to the proper terminal of the CPU.

DEVIATING
NUMBERING!

CPU 1 CPU 2 CPU 3 CPU N

24V~0 24V~ 24V~0 24V~ 24V~ 24V~0 24V~0 24V~

1 2 1 2 2 1 1 2
FIELD DEVICE

24 V~
L 24 V~

LINE Y

N 24 V~0
GND

NOISE-FREE EARTH GROUND


(ONLY ONE PER SYSTEM)

Fig. 56. Connecting and earthing multiple CPUs

EN1Z-0970GE51 R0216 38
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

APPENDIX 2
Sensor Input Accuracy
The internal sensor inputs of the EAGLE Controller support both NTC10kΩ and NTC20kΩ sensors (see also section “Universal
Inputs” on page 19). The following table lists the typical minimum accuracies of the hardware and software for temperature
sensors.
Table 30. Accuracies of internal NTC20kΩ sensor inputs of the EAGLE
range measurement error (excl. sensor characteristics)
(1
NTC10kΩ sensors NTC20kΩ sensors
-50 … -20 °C (-58 … -4 °F) ≤ 5.0 K ≤ 5.0 K
-20 … 0 °C (-4 … +32 °F) ≤ 1.0 K ≤ 1.0 K
0 … 30 °C (32 … 86 °F) ≤ 0.5 K ≤ 0.3 K
30 … 70 °C (86 … 158 °F) ≤ 0.5 K ≤ 0.5 K
70 … 100 °C (158 … 212 °F) ≤ 1.0 K ≤ 1.0 K
100 … 130 °C (212 … 266 °F) -- ≤ 3.0 K
130 … 150 °C (266 … 302 °F) -- ≤ 5.5 K
150 … 400 °C (302 … 752 °F) -- --
(1
NTC10kΩ specified for -30 … +100 °C, only.

NOTE: This is the accuracy of the internal sensor input (hardware + software [linearization]), only. This table does not include
the characteristics of the sensors, themselves (see section “Sensor Characteristics” below). If a different sensor or
sensor accuracy is required, one may instead use the inputs of, e.g., a connected Panel I/O module.

Recognition of Sensor Failure of Sensor Inputs


The thresholds at which sensor failures – i.e., sensor breaks (SB) and short-circuits (SC) – are recognized depends upon the
given sensor type. In the event of a recognized sensor failure, the sensor inputs assume the safety values configured in CARE.
Table 31 lists the measurement ranges and the corresponding thresholds for the recognition of sensor failure for the various
different sensor types:
Table 31. Thresholds for short-circuit (SC) and sensor-break (SB) recognition
I/O configuration measurement range recognition thresholds
2…10 V 2…10 V / 4…20 mA (without pull-up) SC: < 1.5 V / 3 mA; SB: no recognition
NTC10kΩ -30 … +100 °C SC: < 20 Ω; SB: < -70 °C
NTC20kΩ -50 … +150 °C SC: < 20 Ω; SB: < -70 °C

NOTE: In the case of temperatures lying outside the aforementioned ranges, the lowest/highest value within the range, instead,
will be communicated. Thus a temperature of -51 °C will be communicated as “-50 °C.”

Sensor Characteristics
The characteristics (resistance in relation to temperature) of the sensors and the resultant voltage are listed on the following
pages. The stated values do not include failures due to: sensor failures; wiring resistance or wiring failures; misreadings due to a
meter connected to measure resistance or voltage at the input.

39 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

NTC 20 k (same voltages for inputs of Panel Bus I/O Modules and onboard inputs of EAGLE)
Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal
[°C] [k voltage [V] [°C] [k voltage [V] [°C] [k voltage [V] [°C] [k voltage [V]
-50.0 1659 8.78 6.0 51.1 6.20 62.0 4.18 1.41 118.0 0.64 0.252
-49.0 1541 8.77 7.0 48.5 6.10 63.0 4.03 1.37 119.0 0.63 0.245
-48.0 1432 8.76 8.0 46.0 6.00 64.0 3.88 1.32 120.0 0.61 0.238
-47.0 1331 8.75 9.0 43.7 5.90 65.0 3.73 1.28 121.0 0.59 0.231
-46.0 1239 8.74 10.0 41.6 5.80 66.0 3.59 1.24 122.0 0.57 0.225
-45.0 1153 8.72 11.0 39.5 5.70 67.0 3.46 1.20 123.0 0.56 0.219
-44.0 1073 8.71 12.0 37.6 5.59 68.0 3.34 1.16 124.0 0.54 0.213
-43.0 1000 8.70 13.0 35.7 5.49 69.0 3.21 1.13 125.0 0.53 0.207
-42.0 932 8.69 14.0 34.0 5.38 70.0 3.10 1.09 126.0 0.51 0.201
-41.0 869 8.67 15.0 32.3 5.28 71.0 2.99 1.06 127.0 0.50 0.196
-40.0 811 8.66 16.0 30.8 5.17 72.0 2.88 1.02 128.0 0.49 0.191
-39.0 757 8.64 17.0 29.3 5.07 73.0 2.78 0.991 129.0 0.47 0.186
-38.0 706 8.62 18.0 27.9 4.96 74.0 2.68 0.960 130.0 0.46 0.181
-37.0 660 8.60 19.0 26.6 4.85 75.0 2.58 0.929 131.0 0.45 0.176
-36.0 617 8.58 20.0 25.3 4.75 76.0 2.49 0.900 132.0 0.43 0.171
-35.0 577 8.56 21.0 24.2 4.64 77.0 2.41 0.872 133.0 0.42 0.167
-34.0 539 8.54 22.0 23.0 4.53 78.0 2.32 0.844 134.0 0.41 0.162
-33.0 505 8.52 23.0 22.0 4.43 79.0 2.24 0.818 135.0 0.40 0.158
-32.0 473 8.49 24.0 21.0 4.32 80.0 2.17 0.792 136.0 0.39 0.154
-31.0 443 8.47 25.0 20.0 4.22 81.0 2.09 0.767 137.0 0.38 0.150
-30.0 415 8.44 26.0 19.1 4.12 82.0 2.02 0.744 138.0 0.37 0.146
-29.0 389 8.41 27.0 18.2 4.01 83.0 1.95 0.720 139.0 0.36 0.142
-28.0 364 8.38 28.0 17.4 3.91 84.0 1.89 0.698 140.0 0.35 0.139
-27.0 342 8.35 29.0 16.6 3.81 85.0 1.82 0.676 141.0 0.34 0.135
-26.0 321 8.32 30.0 15.9 3.71 86.0 1.76 0.655 142.0 0.33 0.132
-25.0 301 8.28 31.0 15.2 3.62 87.0 1.70 0.635 143.0 0.32 0.128
-24.0 283 8.25 32.0 14.5 3.52 88.0 1.65 0.616 144.0 0.32 0.125
-23.0 266 8.21 33.0 13.9 3.43 89.0 1.59 0.597 145.0 0.31 0.122
-22.0 250 8.17 34.0 13.3 3.33 90.0 1.54 0.578 146.0 0.30 0.119
-21.0 235 8.13 35.0 12.7 3.24 91.0 1.49 0.561 147.0 0.29 0.116
-20.0 221 8.08 36.0 12.1 3.15 92.0 1.44 0.544 148.0 0.29 0.113
-19.0 208 8.04 37.0 11.6 3.06 93.0 1.40 0.527 149.0 0.28 0.110
-18.0 196 7.99 38.0 11.1 2.97 94.0 1.35 0.511 150.0 0.27 0.107
-17.0 184 7.94 39.0 10.7 2.89 95.0 1.31 0.496
-16.0 174 7.89 40.0 10.2 2.81 96.0 1.27 0.481
-15.0 164 7.83 41.0 9.78 2.72 97.0 1.23 0.466
-14.0 154 7.78 42.0 9.37 2.64 98.0 1.19 0.452
-13.0 146 7.72 43.0 8.98 2.57 99.0 1.15 0.439
-12.0 137 7.66 44.0 8.61 2.49 100.0 1.11 0.425
-11.0 130 7.60 45.0 8.26 2.42 101.0 1.08 0.413
-10.0 122 7.53 46.0 7.92 2.34 102.0 1.05 0.401
-9.0 116 7.46 47.0 7.60 2.27 103.0 1.01 0.389
-8.0 109 7.39 48.0 7.29 2.20 104.0 0.98 0.378
-7.0 103 7.32 49.0 7.00 2.14 105.0 0.95 0.367
-6.0 97.6 7.25 50.0 6.72 2.07 106.0 0.92 0.356
-5.0 92.3 7.17 51.0 6.45 2.01 107.0 0.90 0.346
-4.0 87.3 7.09 52.0 6.19 1.94 108.0 0.87 0.336
-3.0 82.6 7.01 53.0 5.95 1.88 109.0 0.84 0.326
-2.0 78.2 6.93 54.0 5.72 1.82 110.0 0.82 0.317
-1.0 74.1 6.85 55.0 5.49 1.77 111.0 0.79 0.308
0.0 70.2 6.76 56.0 5.28 1.71 112.0 0.77 0.299
1.0 66.5 6.67 57.0 5.08 1.66 113.0 0.75 0.290
2.0 63.0 6.58 58.0 4.88 1.61 114.0 0.73 0.282
3.0 59.8 6.49 59.0 4.69 1.56 115.0 0.70 0.274
4.0 56.7 6.40 60.0 4.52 1.51 116.0 0.68 0.266
5.0 53.8 6.30 61.0 4.35 1.46 117.0 0.66 0.259

EN1Z-0970GE51 R0216 40
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

NTC10kΩ (same voltages for inputs of Panel Bus I/O Modules and onboard inputs of EAGLE)
Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal Temp. Resistance Terminal
[°C] [k voltage [V] [°C] [k voltage [V] [°C] [k voltage [V] [°C] [k voltage [V]

-30 177 7.904 4 26.68 4.859 38 5.775 1.840 72 1.637 0.612

-29 166.35 7.848 5 25.388 4.750 39 5.546 1.781 73 1.583 0.593

-28 156.413 7.790 6 24.166 4.641 40 5.327 1.724 74 1.531 0.575

-27 147.136 7.730 7 23.01 4.532 41 5.117 1.669 75 1.481 0.557

-26 138.47 7.666 8 21.916 4.423 42 4.917 1.616 76 1.433 0.541

-25 130.372 7.601 9 20.88 4.316 43 4.726 1.564 77 1.387 0.524

-24 122.8 7.534 10 19.898 4.209 44 4.543 1.514 78 1.342 0.508

-23 115.718 7.464 11 18.968 4.103 45 4.369 1.465 79 1.299 0.493

-22 109.089 7.392 12 18.087 3.998 46 4.202 1.418 80 1.258 0.478

-21 102.883 7.318 13 17.252 3.894 47 4.042 1.373 81 1.218 0.464

-20 97.073 7.241 14 16.46 3.792 48 3.889 1.329 82 1.179 0.450

-19 91.597 7.161 15 15.708 3.690 49 3.743 1.286 83 1.142 0.436

-18 86.471 7.080 16 14.995 3.591 50 3.603 1.244 84 1.107 0.423

-17 81.667 6.996 17 14.319 3.492 51 3.469 1.204 85 1.072 0.411

-16 77.161 6.910 18 13.678 3.396 52 3.34 1.166 86 1.039 0.399

-15 72.932 6.821 19 13.068 3.300 53 3.217 1.128 87 1.007 0.387

-14 68.962 6.731 20 12.49 3.207 54 3.099 1.092 88 0.976 0.375

-13 65.231 6.639 21 11.94 3.115 55 2.986 1.057 89 0.947 0.365

-12 61.723 6.545 22 11.418 3.025 56 2.878 1.023 90 0.918 0.354

-11 58.424 6.448 23 10.921 2.937 57 2.774 0.990 91 0.89 0.344

-10 55.321 6.351 24 10.449 2.850 58 2.675 0.959 92 0.863 0.334

-9 52.399 6.251 25 10 2.767 59 2.579 0.928 93 0.838 0.324

-8 49.648 6.150 26 9.572 2.684 60 2.488 0.898 94 0.813 0.315

-7 47.058 6.047 27 9.165 2.603 61 2.4 0.870 95 0.789 0.306

-6 44.617 5.943 28 8.777 2.524 62 2.316 0.842 96 0.765 0.297

-5 42.317 5.838 29 8.408 2.447 63 2.235 0.815 97 0.743 0.289

-4 40.15 5.732 30 8.057 2.372 64 2.158 0.790 98 0.721 0.280

-3 38.106 5.624 31 7.722 2.299 65 2.083 0.765 99 0.7 0.276

-2 36.18 5.516 32 7.402 2.228 66 2.011 0.740 100 0.68 0.265

-1 34.363 5.408 33 7.098 2.159 67 1.943 0.718

0 32.65 5.299 34 6.808 2.091 68 1.877 0.695

1 31.027 5.189 35 6.531 2.025 69 1.813 0.673

2 29.494 5.079 36 6.267 1.962 70 1.752 0.652

3 28.047 4.969 37 6.015 1.900 71 1.694 0.632

41 EN1Z-0970GE51 R0216
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS

INDEX
accuracies see sensor input accuracies via RS485-1 4, 6, 8, 31
BACnet architecture 5 via RS485-2 4, 6, 8, 32
Panel Bus
BACnet IP 2
connection 23
LED 7
multiple rails, single transformer 24, 25
via Ethernet / RJ45 socket 4
via RS485-1 4, 8
BACnet MS/TP 2 via RS485-2 4, 8
BACnet MS/TP via RS485-1 4, 6, 8, 28, 29, 30, 32 power supply
LEDs 4, 8, 35 failure indication 35
troubleshooting 35
power supply (field devices)
BACnet MS/TP via RS485-2 4, 6, 8 cable specifications 26
disposal via EAGLE 16
WEEE Directive 2002/96/EC 2 via I/O module 16
Ethernet / RJ45 socket 6 via I/O module via EAGLE 16
details 7 power supply (Panel Bus I/Os)
protocol version 2 cable specifications 26
External HMI RS232 / RJ45 socket 6, 7
details 22 safety
power consumption 3 electrical safety as per EN60204-1 36
RJ45 socket 4, 6, 12, 13 general safety information 2, 14
extra parts PELV 36
External HMI 22 SELV 36
MVC-80-AC1 terminal cover 22 safety values/positions
MVC-80-AC2 front door mounting accessory 22 safety positions of AOs 19
MVC-80-AC3 strain relief 22 safety positions of relays 20
TPU-11-01 removable push-in terminal plugs 14, 22 safety values of sensor inputs 39
TPU-45-01 removable push-in terminal plugs 14, 22
sensor characteristics
XS830 Auxiliary Terminal Package 18, 22
NTC 20 kOhm 40
XS831 Auxiliary Terminal Package 18, 22
sensor input accuracies 19, 39
fusing 14
AOs 20
LEDs 6 UIs 19
BACnet MS/TP LED
USB
troubleshooting 8, 35
USB 2.0 Device Interface 4, 6
L1 4, 8
details 7
L2 4, 8
initially accessing EAGLE via Ethernet/IP 21
power LED 4, 8
USB 2.0 Host Interface 4, 6
troubleshooting 35
details 7
status LED 4, 8
LED 8
troubleshooting 35
XS830 Auxiliary Terminal Package
M-Bus
connection example 18
connection 33
XW-Online 6, 7
Modbus
connection 10, 31

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:

CentraLine
Honeywell GmbH
Böblinger Strasse 17
71101 Schönaich, Germany
Phone +49 (0) 7031 637 845
Fax +49 (0) 7031 637 740
info@centraline.com Subject to change without notice
www.centraline.com EN1Z-0970GE51 R0216

You might also like