Mge Comet
Mge Comet
Mge Comet
c o m
Setup
Load
Alarms
Battery
Inputs
Main
Load Protected
0%
% KVA
Load
KA2
UPS
Input
load
KA1
K3N
QF1
EMERGENCY
POWER OFF
fault
CO M E T
MG E
UPS SYSTEMS
Comet 40-150kVA
Uninterruptible Power Supply
Comet
40 - 150kVA
Installation and User Manual
Revision History
Comet 40-150kVA UPS Installation and User Manual 86-160310-00
Revision:
A00
B00
C00
D00
E00
Initial Release
ECN#: 289-91
ECN#: 290-30
ECN#: 002456
ECN#: 004466
03/1997
01/1998
07/1998
02/2002
08/2005
86-160310-00 E00
Comet 40-150kVA
WARNING
ATTENTION
L'ouverture des cabinets expose des tensions dangereuses. Assurez-vous toujours que le
service ne soit fait que par des personnes qualifiees.
WARNUNG!
WARNING
As standards, specifications, and designs are subject to change, please ask for confirmation of the information given in this publication.
ATTENTION
WARNUNG!
Normen, Spezifizierungen und Plne unterliegen Anderungen. Bitte verlangen Sie eine
Besttigung ber alle Informationen, die in dieser Ausgabe gemacht wurden.
NOTE
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to
cause harmful interference in which case the user will be required to correct the
interference at user's own expense.
WARNING
To reduce the risk of fire or electric shock, install in a controlled indoor environment free of
conductive contaminants.
This equipment is intended only for installations in a RESTRICTED ACCESS LOCATION.
ATTENTION
Pour rduire le riske d'inccendie ou d'lectrocution, installer dans une enciente intrieure
contrle en temprature et humidit et sans contaminants conducteurs.
Ce matriel est destin seulement pour des installations dans un EMPLACEMENT
RESTREINT D'ACCES.
WARNUNG!
Um die Gefahr von Feuer und elektrischem Schock zu reduzieren, muss das Gert in
einem temperatur - und feuchtigkeitskontrollierten Raum, frei von leitungsfhigen
Verunreinigungen, installiert werden. Dieses Gert ist nur fr die Installation an einem
Ort mit qeingeschrnkter Zugangserlaubnis vorgesehen.
Diese Ausrstung ist nur fr Anlagen in einem EINGESCHRNKTEN ZUGRIFF STANDORT
bestimmti.
ii
86-160310-00 E00
WARNING
ATTENTION
WARNUNG!
Safety of Persons
The UPS has its own internal power source (the battery). Consequently, the power outlets may be
energized even if the UPS is disconnected from the AC power source.
The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the
directives listed below must be observed:
- Never burn the battery (risk of explosion).
- Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
- Comply with all applicable regulations for the disposal of the battery.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
Precautions must be taken for all handling: remove watches, rings, bracelets and any other metal
objects, use tools with insulated handles.
- Do not lay tools or metal parts on top of batteries.
Product Safety
The UPS can be disconnected from the AC power source by opening the input circuit breaker.
Special Precautions
The UPS connection instructions and operation described in the manual must be followed in the indicated
order.
Check that the indications on the rating plate correspond to your AC powered system and to the actual
electrical consumption of all the equipment to be connected to the UPS.
Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be
energized for a period of 24 hours, at least once every 3 months (for a normal storage temperature less
than 25C). This charges the battery, thus avoiding possible irreversible damage.
86-160310-00 E00
iii
Comet 40-150kVA
iv
86-160310-00 E00
Contents
section
description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . .ii
Certification Standards - Three Phase UPS . . . . . . . . . . . . . . . . . . . .iii
Safety of Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Product Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
Special Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
CAUTION: Record All Serial Numbers! . . . . . . . . . . . . . . . . . . . . . .c iv
Symbol Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .c vi
Section Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .c vi
Section 1
Section 2
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1
Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 3
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 8
AC Input Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 9
AC Output Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 9
DC Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 9
Mechanical Specifications (UPS Cabinet Only) . . . . . . . . . . . . .1 10
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .1 10
DB15 Connector Pinouts and Designations . . . . . . . . . . . . . . . .1 10
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 11
UPS Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 11
Software and Communication Package . . . . . . . . . . . . . . . . . . .1 11
Installation
2.0
2.1
2.2
2.3
2.4
2.4.1
2.4.2
2.4.3
2.5
2.5.1
86-160310-00 E00
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 1
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 1
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 1
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 2
Prerequisite to Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 2
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 2
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 3
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 3
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 4
Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 4
Contents
ci
Comet 40-150kVA
Section 2
section
description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
Installation
(continued)
2.6
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 4
Main AC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 4
Bypass AC Input (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 4
Remote Emergency Power Off (REPO) . . . . . . . . . . . . . . . . . . .2 4
AC Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 5
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 5
2.6.1
2.6.2
2.6.3
2.6.4
2.6.5
Section 3
Operation
3.0
3.1
3.1.1
3.1.2
3.1.3
3.2
3.3
3.3.1
3.3.2
3.4
3.5
3.5.1
3.5.2
3.5.3
3.5.4
3.6
3.7
3.8
3.8.1
3.8.2
3.9
3.9.1
3.9.2
3.10
Section 4
Maintenance
4.0
4.1
4.2
4.3
c ii
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1
Power Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1
Power Flow, For Normal Operation . . . . . . . . . . . . . . . . . . . . . . .3 1
Power Flow, For On Battery Operation . . . . . . . . . . . . . . . . . . . .3 1
Power Flow, For Bypass Operation . . . . . . . . . . . . . . . . . . . . . . .3 2
Graphical User Interface, Controls and Indicators . . . . . . . . . . . .3 2
Startup Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 5
Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 5
Powering Up the Comet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 5
Inverter Manual Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 5
Operating Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 6
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 6
Operation on Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 6
Battery Duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 6
3.5.3.1 Return to AC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 6
Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 7
Emergency Shutdown Using EPO/REPO . . . . . . . . . . . . . . . . . .3 8
Forced Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 8
Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 8
From Normal Maintenance Bypass Mode . . . . . . . . . . . . . . . . . .3 8
From Maintenance Bypass to Normal Mode . . . . . . . . . . . . . . . .3 9
Shutdown Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 10
Inverter Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 10
Powering Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 10
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 10
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1
Battery Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 2
Contents
86-160310-00 E00
Figures
figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
1-1:
1-2:
1-3:
1-4:
1-5:
1-6:
1-7:
1-8:
1-9:
Comet 40-80kVA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 1
Single Line Diagram for the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . .1 2
Single Line Diagram for the Comet 100-150kVA . . . . . . . . . . . . . . . . . . .1 2
Front View of the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 4
Rear View of the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 5
Front View of the Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . .1 6
Front View of Communications Components for
the Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 7
Pinouts on the DB15 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 10
2-1:
3-1:
3-2:
3-3:
3-4:
3-5:
3-6:
1
1
2
3
7
7
Tables
table description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
1-1:
1-2:
2-1:
Glossary
Reorder Form
86-160310-00 E00
Contents
c iii
Comet 40-150kVA
______________________________
____________________________
______________________________
____________________________
______________________________
____________________________
______________________________
____________________________
______________________________
____________________________
______________________________
NOTES:
c iv
86-160310-00 E00
86-160310-00 E00
cv
Comet 40-150kVA
Symbol Usage
This manual uses five icon symbols with text to convey important information and tips.
WARNING
Information provided to protect the user and service personnel against safety
hazards and/or possible equipment damage.
CAUTION
Information provided to protect the user and service personnel against possible
equipment damage.
ELECTRICAL
Information provided to protect the user and service personnel against possible
electrical hazard and equipment damage.
IMPORTANT
NOTE
Section Descriptions
1
Provides a general description of the Comet 40-150kVA Uninterruptible Power Systems major components,
available options, and system specifications.
2
Installation
Installation of the Comet 40-150kVA UPS, which include receiving, handling, and storage procedures;
prerequisites to installation; installation procedures; and startup procedures.
3
Operation
Important information on the Comet 40-150kVA systems operation procedure sequences; for normal, on
battery, and bypass operation, with descriptions of the control and display indicators.
NOTE
For details on the Graphical User Interface (GUI) display, please refer to
manual 86-160316-00.
Maintenance
Preventive maintenance and battery safety instructions for Comet 40-150kVA UPS, and information about
replacement parts, and customer service.
A Glossary provides definitions of abbreviations and terms used in this manual.
NOTE
c vi
86-160310-00 E00
1.0
Scope
Provides a general description of the Comet 40-150kVA Uninterruptible Power Systems major components,
available options, and system specifications.
1.1
General Description
The Comet family consists of compact, high-efficiency Uninterruptible Power Systems which are available in power
ratings from 40-150kVA, and are optimized for compatibility with nonlinear computer-type loads. Computer-aided
UPS diagnostics and modular construction assure that any required service can be identified and completed rapidly.
Remote system monitoring, remote annunciation of UPS performance signals and communication capabilities allow
total control of the UPS by its user. See Figures 1-1 and 1-2.
The Comet UPS and its auxiliary equipment are designed for installation in a room where humidity and temperature
can be controlled. The recommended and maximum environmental parameters are listed in the Specifications
section of this document.
Figure 1-1: Comet 40-80kVA.
Setup
Load
Alarms
Battery
Inputs
Main
Load Protected
0%
% KVA
Load
KA2
UPS
Input
Setup
Load
Alarms
Battery
Inputs
Main
load
KA1
Load Protected
0%
% KVA
Load
KA2
K3N
UPS
Input
QF1
load
KA1
K3N
QF1
EMERGENCY
POWER OFF
EMERGENCY
POWER OFF
fault
fault
CO M E T
CO M E T
MG E
UPS SYSTEMS
MG E
UPS SYSTEMS
86-160310-00 E00
11
Comet 40-150kVA
Figure 1-3, and 1-4 show single-line diagrams of a typical UPS system installation. During normal operation,
utility power (Main Input) is supplied to the UPS Rectifier where it is converted to DC voltage. The Inverter
converts the DC voltage from the Rectifier to three-phase regulated AC voltage, which supplies the critical load.
During power failure conditions, the Inverter is supplied by the stored energy in the batteries, and the load is
powered continuously with no disruption.
Figure 1-3: Single Line Diagram for the Comet 40-80kVA.
UPS CABINET
STATIC SWITCH
KA2
BYPASS
AC INPUT
(OPTIONAL)
SR1
KA1
MAIN
AC INPUT
K3N
INPUT
FUSES
RECTIFIER
BATTERY
CABINET
INVERTER
TO
CRITICAL
LOAD
OUTPUT
FUSES
QF1
BATTERY
UPS CABINET
BYPASS
AC INPUT
STATIC SWITCH
KA2
SR1
KA1
MAIN
AC INPUT
K3N
INPUT
FUSES
RECTIFIER
BATTERY
CABINET
INVERTER
OUTPUT
FUSES
TO
CRITICAL
LOAD
QF1
BATTERY
12
86-160310-00 E00
1.2
Major Components
The following is a description of the cabinets and major components. Refer to Figures 1-5 to 1-8.
UPS Cabinet
Converts the input AC power to direct current and charges the battery. DC power
is converted back to clean AC power by the inverter for the critical load. Section
3 describes the operation in detail.
Auxiliary Cabinet
Performs the voltage conversion for the input AC and/or bypass AC using stepup and/or step-down transformers.
Battery Cabinet
The battery cabinet stores energy for use by the Inverter. The stored energy is
utilized in the event that the AC input power from the utility source fails, or falls
outside of acceptable tolerances. The internal Battery Charger maintains the
charge of the battery system. The DC output voltage of the charger is temperature regulated to ensure an optimal charge voltage. If a customer supplied battery
system is to be used, an external battery charger may be necessary.
The standard battery system is housed in a separate enclosure. For systems where
additional back-up time is required, up to two (2) additional battery cabinets are
available.
A standard battery cabinet is available in an adjacent configuration or a standalone configuration. Adjacent battery cabinets are attached to the right side of the
UPS using c-brackets provided with the cabinet. Stand-alone battery cabinets
are remote from the UPS. Refer to the battery cabinet installation drawing for
more details. An external battery system can also be supplied by the customer.
Rectifier
Converts the AC input voltage from the utility source into a DC voltage, supplying
the Inverter.
Inverter
Converts the DC voltage supplied from either the Rectifier or the battery system into
a three-phase AC voltage. An AC output filter is used to achieve a computer-grade
sinewave output voltage waveform, with a total harmonic distortion of less than 2%
under linear-load conditions.
Static Switch
Transfers the load between the Inverter output and the bypass AC source without
interrupting the supply of power to the load, allowing the load to continue
operation in the event of a UPS fault. The Static Switch circuit assures that
voltage from the UPS output cannot be fed back to the utility input lines.
Battery System
Stores energy for use by the Inverter. The stored energy is utilized in the event
that the AC input power from the utility source fails, or falls outside of acceptable
tolerances. The internal Battery Charger maintains the charge of the battery
system. The DC output voltage of the charger is temperature regulated to ensure
an optimal charge voltage. If a customer supplied battery system is to be used,
an external battery charger may be necessary.
86-160310-00 E00
13
Comet 40-150kVA
Inverter Assembly
Feedback PCA
10
11
Interconnect PCA
12
13
14
15
16
17
Battery Connections
18
19
20
21
22
Ground Busbar
23
Neutral Busbar
24
25
Battery Charger
01
04
05
02
14
86-160310-00 E00
TOP ENTRY
CONDUIT LANDING
TOP ENTRY
CHANNEL
T1 INPUT
TRANSFORMER
(OPTIONAL)
T2 OUTPUT
TRANSFORMER
(OPTIONAL)
86-160310-00 E00
15
Comet 40-150kVA
Rectifier
Static Switch
Inverter Assembly
10
Chopper Assembly
11
Interconnect PCA
12
Ground Busbar
13
14
Charger PCA
15
16
DC Cap Modules
16
18
19
86-160310-00 E00
Figure 1-8: Front View of Communications Components for the Comet 100-150kVA.
COMMUNICATION
PCAs
86-160310-00 E00
17
Comet 40-150kVA
1.3
Specifications
The Comet 40-150kVA UPS systems are rated for various input and output voltages (see Table 1-1). When
different input and/or output voltages are specified, optional transformers provide step up/down functions as
required.
Table 1-1: Comet 40-150kVA Specifications.
INPUT
VOLTAGE
(VAC)
OUTPUT OUTPUT
VOLTAGE CURRENT
(VAC)
(Amperes)
INPUT
CURRENT
(on UPS/
on bypass)
TOTAL
WIDTH
(in/mm)
NET
WEIGHT
(lb/kg)
HEAT
LOSS
(Btu/hr)
(Amperes)
40kVA/32 kW
50kVA/40 kW
65kVA/52 kW
80kVA/64 kW
100kVA/80 kW
125kVA/100 kW
150kVA/120 kW
208
208
111
102/111
32.75/832
1760/800
13500
220
220
105
96/105
32.75/832
1760/800
13500
480
208
111
43/111
32.75/832
1360/617
12135
480
480
48
43/48
32.75/832
880/400
8220
600
208
111
35/111
60.00/1524
2820/1279
13500
208
208
139
127/139
32.75/832
1760/800
16873
220
220
131
120/131
32.75/832
1760/800
16873
480
208
139
54/139
32.75/832
1360/617
15169
480
480
60
54/60
32.75/832
880/400
10276
600
208
139
44/139
60.00/1524
2820/1279
16873
208
208
180
162/180
32.75/832
2115/960
17552
220
220
170
153/170
32.75/832
2115/960
17552
480
208
180
70/180
32.75/832
1590/721
15433
480
480
78
70/78
32.75/832
970/440
11328
600
208
180
57/180
60.00/1524
2910/1320
17552
208
208
222
200/222
32.75/832
2115/960
21603
220
220
210
190/210
32.75/832
2115/960
21603
480
208
222
86/222
32.75/832
1590/721
21603
480
480
96
86/96
32.75/832
970/440
13992
600
208
222
70/222
60.00/1524
2910/1320
21603
208
208
278
256/278
69.50/1765
3400/1543
28300
220
220
263
242/263
69.50/1765
3400/1543
28300
480
208
278
109/278
42.75/1086
2450/1112
22278
480
480
120
109/120
42.75/1086
1460/662
15420
600
600
96
89/96
96.00/2438
3700/1678
28300
600
208
278
91/278
69.50/1765
3400/1543
28300
208
208
347
316/347
69.50/1765
3400/1543
38247
220
220
328
298/328
69.50/1765
3400/1543
38247
480
208
347
134/347
42.75/1086
2450/1112
30662
480
480
150
134/150
42.75/1086
1460/662
20804
600
600
120
109/120
96.00/2438
3700/1678
38247
600
208
347
109/347
69.50/1765
3400/1543
38247
208
208
417
378/417
69.50/1765
3400/1543
50759
220
220
394
375/394
69.50/1765
3400/1543
50759
480
208
417
160/417
42.75/1086
2450/1112
41560
480
480
180
160/180
42.75/1086
1460/662
26351
600
600
145
131/145
69.50/1765
3700/1678
50759
600
208
417
131/417
96.00/2438
3400/1543
50759
86-160310-00 E00
NOTES:
1. Total width, weight, and heat loss are for system line-up excluding battery cabinets.
2. Data does not include battery data; refer to the installation drawings supplied with your equipment.
Consult the installation drawings provided with your equipment.
1.3.1
AC Input Ratings
Voltage
480 VAC, + 12%, -15%
Frequency
60 Hz 4%
Phases
3 (phase sequence must be A, B, C, clockwise)
Wires
3 wires plus ground (480-480 VAC only)
Power factor
Approximately 0.98 at full load
Current (on UPS/ on BYPASS) @ 480 VAC
1.3.2
40kVA
50kVA
65kVA
80kVA
100kVA
125kVA
150kVA
43A/48A
54A/60A
70A/78A
86A/96A
109A/120A
134A/150A
160A/180A
AC Output Ratings
Voltage (inverter only)
Frequency
60 Hz 0.1% (free-running)
Phases
Wires
Power factor
0.8
65kVA
80kVA
100kVA
125kVA
150kVA
48A
78A
96A
120A
150A
180A
60A
Total harmonic
distortion (THD)
Dynamic regulation
Dynamic response
Overload
1.3.3
DC Ratings
Battery voltage (25 C)
float:
nominal:
minimum:
490 Vdc
432 Vdc
360 Vdc
50kVA
65kVA
80kVA
100kVA
125kVA
150kVA
96 ADC
120 ADC
154 ADC
189 ADC
235 ADC
294 ADC
353 ADC
86-160310-00 E00
19
Comet 40-150kVA
1.3.4
66.70 in/1694 mm
Width
32.75 in/832 mm
Depth
33.42 in/823 mm
1.3.5
40/50kVA
65/80kVA
100-150kVA
880 lbs/400 kg
970 lbs/440 kg
1460 lbs/662 kg
Environmental Specifications
Temperature
Operating:
1.3.6
0 C to 30 C (32 F to 86 F) continuous
15C(60F) to <25 C (<77 F) recommended
40 C (104 F) up to 8 hrs at 75% load
Non-operating
and storage:
Humidity
0 to 95% non-condensing
Altitude
The UPS Manager connector enables communication with the most common computer systems (AS/400,
NOVELL, etc.), or with the optional "UPS Manager UM1" software.
Table 1-2: UPS Manager Dry Contact Interface.
UPS Manager Dry Contact Interface (DB15)
Softunor (DB9)
Operation on Inverter
Operation on Bypass
Operation on Battery
Low Battery Shutdown Warning
UPS Remote Inverter Shutdown
PIJO PC board
NO
NC
Breaking
capacity of
contacts is:
P = 3va
V = 30VDC max.
I = 100mA max.
NO
NC
Operation on Inverter
Operation on
Bypass
10
NO
NC
8 7 6 5 4 3 2 1
Operation on Battery
11
15 14 13 12 11 10 9
13
NO
NC
12
14
GROUND
Please note that once the UPS remote inverter shutdown signal is applied, the Inverter stops and the
load transfers to bypass after a predetermined time (typically 2 minutes).
1 10
86-160310-00 E00
1.4
The auxiliary cabinet may provide one or both of the following options: an input
bypass step up/down transformer, and an output distribution panel. An output
distribution panel provides connection points for distribution of AC power to
computers and other equipment. Also available are external maintenance bypass
cabinets.
Extended Battery Cabinets Up to two Extended Battery Cabinets are available to provide extra back-up time
during power outage.
1.4.1
UPS Options
Communication Options
Monitor Plus
Mini terminal for control and display of system parameters. This option can be installed locally or remotely.
Contact 5
This option offers communication of five different signals via dry relay contacts:
Load on UPS
Load on Bypass
Operation on Battery
U-Talk
JBUS/RS485
1.4.2
Solution-Pac
86-160310-00 E00
Automatic file shutdown during power outage or severe brownout for standalone systems.
Automatic file shutdown for network servers plus additional monitoring and
network communication functions.
1 11
COMET 40-150kVA
1 12
Chaptername
86-160310-00 E00
Comet 40-150kVA
1 13
86-160310-00 E00
Installation
2.0
Scope
Installation of the Comet 40-150kVA UPS, which include receiving, handling, and storage procedures; prerequisites
to installation; installation procedures; and startup procedures.
CAUTION
2.1
Receiving
Before accepting the shipment from the freight carrier, inspect the exterior surfaces of shipping container(s),
packaging, and equipment for damage that may have occurred during transit. If the shipping containers or
equipment show evidence of damage, note the damage on the receiving document (bill of lading) prior to
signing for receipt of equipment. Verify that the equipment nameplate corresponds with the equipment ordered.
Damage claims should be filed directly with the carrier. Replacements for damaged components can be ordered
by calling 1-800-438-7373.
2.2
Handling
Any equipment shipped on a shipping pallet is intended for handling by a pallet jack or a fork lift truck. Move
the equipment to its intended location while still mounted on its pallet, and remove the equipment from the pallet
when it is near its final location. See Figure 2-1.
The Comet UPS and optional auxiliary cabinets have heavy-duty casters to allow the equipment to be moved
into position easily once they have been unloaded from the shipping truck. Once the UPS is in its final position,
the leveling jacks on all four-bottom corners should be lowered to secure the cabinet in place. Refer to the
installation drawings that were shipped with the cabinets.
Battery cabinet weighing less than 3000 lbs. are equipped with casters for ease of handling on site. For
shipment, these cabinets are mounted on pallets to prevent movement on ramps and other inclined surfaces.
A forklift (4000 lbs capacity or greater) is required to remove the battery cabinet from its pallet. The 42" battery
cabinets should be lifted from the side only. For battery cabinets weighing more than 3000 lbs., no casters are
provided, and therefore must be moved by forklift only.
86-160310-00 E00
Installation
21
Comet 40-150kVA
If the equipment is to be stored for more than three months before installation, it should be unpacked and
connected to an AC input source to allow the batteries to be recharged. Refer to the installation instructions that
follow, and the installation drawings.
Figure 2-1: The Comet 100-150kVA on Pallet.
2.3
Storage
If the equipment is to be stored prior to installation, it should be stored in a cool, dry, well-ventilated location
that is protected against rain, splashing water, chemical agents, etc. The equipment should be covered with a
tarpaulin or plastic wrapper to protect it against dust, dirt, paint, or other foreign materials.
IMPORTANT
2.4
Batteries should be stored no longer than three (3) months at approximately 25C
(77 F) prior to recharging. Too high or too low a temperature will damage batteries.
Exceeding the recommended ambient storage temperature will reduce back-up time
and may adversely affect life.
Prerequisite to Installation
This section provides more information for a successful and efficient installation of the Comet 40-150kVA.
Installation of equipment must be handled by skilled technicians and electrician's familiar with the requirements
of high energy electrical equipment. The installation must comply with the requirements of the National
Electrical Code (NEC, ANSI/NFPA 70, latest issue) and with local codes and requirements as applicable. We
strongly recommend contracting MGE Customer Support Services for startup. Do not allow unqualified
personnel to handle or operate the equipment.
2.4.1
Environmental
The Comet 40-150kVA UPS is intended for use in an environment where control of temperature and humidity is
provided. The maximum operating and recommended environmental parameters are provided in the Specifications
section of this document.
The Comet UPS generates heat and exhausts air through the top portion of its enclosure. Heat loss data is
provided in Table 1-1.
Consult the installation drawings provided with your equipment.
22
Installation
86-160310-00 E00
2.4.2
Mechanical
The Comet UPS can be mounted on a raised computer room floor, or flush-mounted on a concrete floor. All
floors must be level. On a raised floor, conduits can be run below the floor, with cut-outs made in the floor tiles
as shown on the installation drawings.
Allow at least three feet of clearance in front of the UPS for normal operation (access to the UPS controls). The
Comet requires at least 36 inches top clearance for ventilation.
2.4.3
Electrical
Electrical service for the Comet UPS should be supplied on its own dedicated branch circuit. Main input cables and
upstream protective devices must be provided and sized per the National Electrical Code (NEC, ANSI/NFPA 70,
latest issue), and as appropriate for your load and distribution requirements. Cable sizing data is provided on the
installation drawings supplied with the equipment. The Comet 480/480V UPS is not a separately-derived source.
The Comet 208/208V UPS is a separately derived source. The neutral must be grounded on a separately derived
source (like the Comet 208/208V UPS).
CAUTION
The customer supplied upstream protective device shall open in one cycle
when 10 times the output rated current is applied or in the event of an output
short circuit when the unit is working on Static Switch.
Refer to the upstream circuit breaker manufacturers characteristic curves for
proper trip settings.
40kVA
50kVA
65kVA
80kVA
100kVA
125kVA
150kVA
208
150A
175A
225A
300A
350A
450A
500A
220
150A
175A
225A
300A
350A
450A
500A
480
70A
80A
100A
125A
150A
200A
225A
600
60A
70A
80A
100A
125A
150A
200A
86-160310-00 E00
Installation
23
Comet 40-150kVA
2.5
Installation Procedures
The steps to be followed are:
Installation of UPS equipment must be handled by skilled technicians and electrician's familiar with the special
requirements of high-energy electrical equipment. We strongly recommend contracting MGE Customer Support
Services for start-up of the installed Comet UPS system. Do not allow unqualified personnel to handle or
operate the Comet UPS.
Refer to the installation drawings for proper placement and connections of auxiliary cabinets.
2.5.1
Placement
Move the Comet UPS, battery cabinets (if any), and auxiliary cabinets (if any), to their final location (see Figure
2-2). For cabinets installed adjacent to each other, alignment is critical to properly install the mechanical and
cable interconnections. Allow at least 36 inches clearance above all cabinets for maintenance and cooling.
Figure 2-2: Placement of UPS and other Cabinets.
AUX
CAB
UPS
BATTERY
CABINET(s)
36" recommended
2.6
Connections
Electrical connections and cabinet interconnection will vary depending upon the configuration of your Comet
UPS system. Refer to Figures 2-3 & 2-4 and to the installation drawings supplied with your equipment.
CAUTION
2.6.1
Before making any electrical connections, verify that all battery disconnect
circuit breaker (QF1) are in the off position. Customer-supplied upstream
protective devices and distribution circuits should be OFF.
Main AC Input
The connections to be made are the three phases, and ground cables from the utility AC power source to the
UPS. The main AC input cables are terminated at the "Main Input" Terminal Block (TB1) for 40-80kVA and the
input busbars for 100-150kVA. Complete wiring instructions for your installation are provided on the installation
drawings supplied with the equipment.
2.6.2
The connections to be made are the three phases, and ground cables from the bypass AC input power source
to the UPS. The bypass AC input cables are terminated at the "Bypass Input" Terminal Block (TB3) for 40-80kVA
and the bypass busbars for 100-150kVA. This option provides a separate AC input source for bypass operation.
2.6.3
The control connections are available for "Remote Emergency Power Off" (REPO) through a customer-supplied
normally closed pushbutton. With REPO connected, the jumper on the "REPO" terminal blocks must be removed.
24
Installation
86-160310-00 E00
2.6.4
AC Output
The connections to be made are the three phases, and ground cables from the load source to the UPS. The
output cables are terminated at the Output Terminal Block (TB2) for 40-80kVA, and the output busbars for 100150kVA.
Load cables must be run separately from all other cables (power supply or computer-system interconnection
cables). They should not pass near interference-emitting equipment or sensitive loads.
2.6.5
Battery
The connections to be made are the positive, negative, and ground cables from the battery cabinet to the UPS.
These are terminated at the appropriate connections in the UPS cabinet (see Figures 2-3 and 2-4). Additionally,
control wires and temperature sensors in the battery cabinet must be terminated. Refer to the battery cabinet
installation drawings for more details.
Figure 2-3: Connections for Comet 40-80kVA UPS.
Separate Bypass
Input Terminal
Battery
Block TB3
Connections
(Optional)
Main Input
Terminal Block
TB1
Ground Busbar
Output
Fan Control
Terminal Block
Switch
TB2
SR2
Fan and
Teleservice Fuses
FU7-FU12
Neutral Busbar
OUTPUT
OPT
B4
A4
A5
BYPASS
A3
INPUT
86-160310-00 E00
C4
B5
C3
B3
C5
BATT.
Installation
25
COMET 40-150kVA
26
Chaptername
86-160310-00 E00
Comet 40-150kVA
27
86-160310-00 E00
Operation
3.0
Scope
Important information on the Comet 40-150kVA systems operation procedure sequences; for normal, on battery,
and bypass operation, with descriptions of the control and display indicators.
3.1
Power Flow
3.1.1
During normal operation the AC input source supplies the Rectifier, which converts the incoming AC power to
DC. The rectifier in turn supplies the Inverter, which converts DC power to AC to supply the attached load (see
Figure 3-1).
Figure 3-1: Power Flow, For Normal Operation.
STATIC SWITCH
BYPASS
INPUT
(OPTIONAL)
RECTIFIER
INVERTER
MAIN
INPUT
TO LOAD
BATTERY
3.1.2
When AC input power fails, the UPS goes to on-battery operation. DC power is supplied from the UPS battery
system to the inverter, which converts battery power (DC) to AC power to supply the attached load (see Figure
3-2).
Figure 3-2: Power Flow, For On Battery Operation.
STATIC SWITCH
BYPASS
INPUT
(OPTIONAL)
RECTIFIER
INVERTER
MAIN
INPUT
TO LOAD
BATTERY
86-160310-00 E00
Operation
3 1
Comet 40-150kVA
3.1.3
Should there be an internal fault in the UPS, the load will automatically be transferred to the "Static Switch".
(If bypass AC input is within tolerance). The load is supplied without interruption while the UPS is bypassed (see
Figure 3-3).
Figure 3-3: Power Flow, For Bypass Operation.
STATIC SWITCH
BYPASS
INPUT
(OPTIONAL)
RECTIFIER
INVERTER
MAIN
INPUT
TO LOAD
BATTERY
3.2
An alert buzzer.
Four (4) LED's which indicate the overall operating status of the UPS.
Danger of a break in the supply of power to the load (load not protected)
When the buzzer is activated it will provide an audible warning to the operator by sounding a pulsed beep
when any of the following conditions occur:
The load is supplied directly by AC input power via the "Static Switch".
It beeps softly and slowly for minor faults and during Inverter operation on battery power. When the low battery
shutdown warning level has been reached, the sound volume and the frequency of the beeps increase.
In the event of an Inverter shutdown, a continuous alarm is emitted. A buzzer reset key is provided on the front
panel. Detection of a new fault will reactivate the buzzer.
3 2
Operation
86-160310-00 E00
1
Setup
Load
Alarms
Battery
Inputs
Load Protected
0%
Main
% KVA
Load
KA2
UPS
Input
load
KA1
K3N
QF1
3
2
EMERGENCY
POWER OFF
11
9
fault
10
1
10
Security Key
11
NOTE
86-160310-00 E00
For details on the Graphical User Interface (GUI) display, please refer to
manual 86-160316-00.
Operation
3 3
Comet 40-150kVA
3 4
Graphical User
Interface Display
This red Emergency Power Off (EPO) pushbutton is used to stop the unit during
an emergency situation only. All power is removed from the load.
Direct supply of power to the load by AC input power via the "Static Switch"
because of Inverter shutdown (voluntary or following an overload or an
internal fault).
Battery power is not available. Battery circuit breaker is in the "OFF" position
or battery not connected.
Fault LED
It flashes to indicate that the low battery shutdown warning level has been
reached.
If the LED flashes when the system is not on battery power, battery
conditions should be checked.
This green LED indicates that the Comet is operating normally. The load is
protected and supplied via the Inverter output. Bypass Switch SR1 must be in the
"NORMAL" position.
Inverter on
Inverter off
Fault Reset
This key clears the faults stored in memory. Clearing of alarms in memory is
accepted only after the alarm conditions themselves have been corrected.
Security Key
This key enables forced operation. The security key must be held down while the
desired function is executed. Refer to the Forced Transfer section.
Buzzer Reset
This key allows the user to silence the buzzer after a particular alarm. However,
the buzzer will sound if another alarm occurs.
Operation
86-160310-00 E00
3.3
Startup Procedures
3.3.1
Preliminary Checks
Verify that the battery circuit breaker(s) are in the "OFF" position.
Verify that the Manual Bypass Switch SR1 is set to the NORMAL position.
Check that the ventilation system is not blocked (air entry through the bottom front and exhaust through the top).
Check that there is a minimum of 36 inches clearance at the front and top for ventilation.
Check that the Comet no longer rests on its 4 wheels (lifting levelers in place).
Check that the load-circuit breaker(s) (where applicable) are in the "OFF" position.
3.3.2
3.4
As soon as AC input power is supplied to the Comet (customer supplied upstream circuit breaker is in the ON position), the load is initially supplied
via the Static Switch. The Graphical User Interface (GUI) display will begin
to startup.
Apply AC input power to the unit by closing the upstream circuit breaker.
The inverter automatically starts up, except if the system is in manual startup mode (optional).
If the transfer conditions (AC input power within tolerances) are correct, the Inverter comes on line and supplies
the load. The green "Load Protected" LED goes on.
The Inverter starts and if the transfer conditions are correct, the load is transferred to the Inverter.
86-160310-00 E00
Operation
3 5
Comet 40-150kVA
3.5
Operating Procedures
3.5.1
Normal Operation
The green "Load Protected" LED is on. The GUI display indicates the operating status of the UPS.
The power drawn by the load is supplied by AC input power via the Rectifier and Inverter modules. The Battery
Charger float charges or recharges the battery.
3.5.2
When AC input power fails or is out of tolerance, the Rectifier shuts down and the battery supplies the power
required by the Inverter to supply the load. The battery discharges.
The green "Load Protected" LED is on. The GUI display indicates the operating status of the UPS.
The user is warned of operation on battery power by the buzzer and by the yellow "Battery Status" LED. This
information is also available via the standard UPS MANAGER DB15 connector.
3.5.3
Battery Duration
During an AC input power failure, the duration of Inverter operation on battery power depends on:
The real backup time, which depends on the actual load, may be greater if the Inverter operates at less than
full rated load. It is possible, during operation on battery power, to increase the battery backup time by reducing
the power drawn by the load (shedding of non-priority load).
A low battery shutdown warning signal is available via the standard UPS MANAGER DB15 connector for remote
indications. It warns the user of upcoming battery shutdown at a user-determined level of remaining power.
On the UPS itself, the buzzer beeps louder and more rapidly, and the yellow "Battery Status" LED flashes
rapidly.
The end of battery power occurs when the battery reaches shutdown level. At this point, the Inverter shuts down
and the UPS goes into "Stand-By" mode. Load is no longer supported. If the input AC power does not return to
within tolerance within approximately 2 hours, the unit will shutdown.
Once input AC power returns, the batteries begin their charging cycle. It takes approximately 10 hours of online
operation to restore 10 minutes of backup time.
3.5.3.1 Return to AC Power
When the AC input power failure ends or power returns to within tolerances:
3 6
If the end of battery backup power was not reached, the Comet returns to normal operating mode.
If the end of battery backup power was reached and unit is in "Standby" mode, the Rectifier and the Inverter
automatically start up (the inverter must be manually started if the system is in manual startup mode).
If the end of "Stand-By" mode was reached, follow the Startup procedure.
Operation
86-160310-00 E00
3.5.4
Overload
When an Inverter temporary overload occurs, the load is transferred to the "Static Switch". Return to normal
mode of operation is automatic, following elimination of the overload.
The Inverter can handle a continuous overload for a given duration depending on the size of the output current
overload (see Figure 3-5) or the output power overload (see Figure 3-6).
When an overload occurs:
The Inverter shuts down at the end of its corresponding overload time.
The operating status of the UPS is provided by the GUI display. If the overload continues during operation via
the "Static Switch", the supply of power to the load is interrupted after a specified time.
When the Comet shuts down because of a continuous overload, the "Fault Reset" key must be pressed prior to
return to normal operation and after elimination of the overload.
Figure 3-5: Output Current Overload Curve.
time
10 mn
1 mn
10 s
1s
rated load
current
0.15 s
1.05 1.1
1.3
1.5
1.7
1.9
I (A)
1 mn
10 s
1s
rated load
power
0.3 s
1.1
86-160310-00 E00
1.3
1.5
1.7
Operation
1.9
P (kw)
3 7
Comet 40-150kVA
3.6
Pressing the Emergency Power Off (EPO) or Remote Emergency Power Off
(REPO) pushbutton disconnects the attached load. The EPO is to be used during
emergency situations only, where a hazard to personnel or equipment exists, such
as during a fire. DO NOT USE THE EPO TO TURN THE UPS ON OR OFF.
Follow the procedures listed in this section for turning the Inverter on and off.
During an emergency situation, such as a fire in the computer or electrical room, the UPS and all downstream
devices can be instantly shut down by pressing the EPO pushbutton on the front panel of the UPS cabinet, or
by pressing the "Remote Emergency Power Off" (REPO) optional pushbutton.
The EPO or REPO pushbuttons should not be used for normal shutdown of the equipment.
If the EPO pushbutton has been pressed, it must be reset by pressing it again and by pressing the "Fault Reset"
key on the front panel to allow the UPS to restart.
3.7
Forced Transfer
CAUTION
Using the forced transfer functions will cause the load to experience a power
interruption for a minimum of 500 milliseconds. Be certain that the load can
tolerate this interruption.
Forced transfer is required if bypass input is out of tolerance. The load can be transferred from the Inverter
output to the bypass input source, or back, with a power interruption of 500 milliseconds.
Transferring the Load to Bypass Input From Inverter
On the front panel, press the "Security" key and hold it while pressing the gray "Inverter OFF" pushbutton for 3
seconds.
Transferring the Load to Inverter From Bypass Input
On the front panel, press the "Security" key and hold it while pressing the green "Inverter ON" pushbutton for 3
seconds.
3.8
Maintenance Bypass
This procedure assumes that the UPS is operating normally, with the attached load supplied via the Inverter.
3.8.1
1.
Stop the Inverter by pressing the gray "Inverter OFF" pushbutton on the UPS front panel for approximately three
(3) seconds. The audible alarm will sound; silence the alarm by pressing the "Buzzer Reset" pushbutton. If the
transfer conditions are not satisfied (bypass out of tolerance or other reason), a forced transfer will be required.
Refer to the "Forced Transfers" section for more information.
2.
NOTE
3 8
The battery circuit breaker QF1 will automatically trip open if left in the ON
position when the UPS is placed in the Maintenance Bypass mode.
3.
Turn the manual bypass switch to the "TRANSFER" position, then to the "BYPASS" position.
4.
Operation
86-160310-00 E00
NOTE
The cooling fans will remain operational when the UPS is placed on
Maintenance Bypass mode to prevent the optional input/output transformers
inside the UPS from overheating. If it is necessary to de-energize the fans,
move the fan control switch (SR2) to the OFF position.
CAUTION
In this mode of operation, the UPS is ready for maintenance, but voltage is
still present on terminal blocks and various internal components.
WARNING
Failure to follow the proper Startup sequence will result in load loss. After
SR1 is set to TRANSFER, it takes the UPS five (5) to six (6) \seconds to test
the input power before turning on the Static Switch. During this time, the
load is still supplied by the Maintenance Bypass line, and moving SR1 to
NORMAL will result in interruption of power to the load.
1.
Move the fan control switch (SR2) to the ON position if the cooling fans were de-energized during
maintenance.
2.
3.
4.
Turn the Inverter off by pressing the gray "Inverter OFF" pushbutton on the front panel for approximately
3 seconds if your Comet has been programmed to automatically restart.
CAUTION
ALWAYS turn the Inverter off before rotating the Manual Bypass Switch (SR1).
5.
6.
7.
Turn the Inverter on by pressing the green Inverter ON" pushbutton on the front panel. If the transfer
conditions are not satisfied (bypass out of tolerance or other reason), a forced transfer will be required.
Refer to the "Forced Transfers" section for more information.
Now the UPS is in normal operating mode. The green "Load Protected" LED is illuminated on the front panel,
and the operating status of the UPS is provided by the GUI display.
86-160310-00 E00
Operation
3 9
Comet 40-150kVA
3.9
Shutdown Procedures
3.9.1
Inverter Shutdown
Press and hold the gray "Inverter OFF" pushbutton for 3 seconds.
3.9.2
Powering Down
It is recommended not to power down the Comet for long periods because the battery should remained charged.
However, to carry out a power down, proceed as follows:
3.10
Alarms
Any state other than normal operation (green Load Protected LED on) is considered a fault by the diagnostics
system.
Before undertaking any servicing or other action, note the status of the different LED's and the GUI messages
displayed on the panel.
If an alarm is present and the load still functions, it is supplied via the "Static Switch", i.e. it is not protected.
Table 3-1: Alarm Indications.
status or action producing the indication
inverter start-up phase prior to load
transfer. The "inverter on" button has
been pressed.
normal operation;
load supplied by Comet UPS
(SR1 in normal position)
inverter shutdown following pressing of the
"inverter off" button or a major fault;
load supplied via the "static switch"
beep
beep
beep
beep
beep
beep
beep
beep
minor fault;
(load continues to be supplied via inverter)
UPS shutdown;
load supplied via maintenance bypass
buzzer on,
light on,
light flashing
3 10
Operation
86-160310-00 E00
Maintenance
4.0
Scope
Preventive maintenance and battery safety instructions for Comet 40-150kVA UPS, and information about
replacement parts, and customer service.
4.1
Battery Safety
IMPORTANT SAFETY INSTRUCTIONS FOR SERVICING BATTERIES
A. Servicing of batteries should be performed or supervised by personnel knowledgeable with batteries and
the required precautions. Keep unauthorized personnel away from batteries.
B. When replacing batteries, use the same model and manufacturer of batteries.
C. CAUTION Do not dispose of battery or batteries in a fire. The battery may explode.
D. CAUTION Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
and eyes. It may be toxic.
E. CAUTION A battery can present a risk of electrical shock and high short-circuit current. The following
precautions should be observed when working with batteries:
4.2
1.
2.
3.
4.
5.
6.
Determine if ground faults exists. If so, remove the source of ground. Contact with any part of a grounded
battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are
removed during installation and maintenance.
Preventive Maintenance
The following preventive maintenance routines should be considered the minimum requirements; your
installation and site may require additional preventive maintenance to assure optimal performance from your
installed Comet UPS and associated equipment. These routines should be performed twice a year (more often
if required). We strongly recommend contracting MGE Customer Support Services for preventive and remedial
maintenance at 1-800-438-7373.
The technician or electrician performing preventive maintenance on the UPS must be familiar with the
indicators, controls, and operation of the UPS.
a.
Isolate and de-energize all Comet UPS equipment for all maintenance operations. Lock and tag all upstream
circuit breaker(s) during maintenance.
b.
Ensure that all equipment is clean and free of dust, dirt, and debris. The exterior of the UPS enclosure may
be cleaned with a mild solution of soap and water, lightly applied with a lint-free cloth.
c.
Clean/replace the air intake filters, exhaust plates, and the enclosure interior with a vacuum cleaner.
d.
e.
Test the main operating sequences as applicable to your installation (see Section 3).
86-160310-00 E00
Maintenance
4 1
Comet 40-150kVA
4.3
Replacement Parts
There are no user serviceable parts inside the Comet UPS.
Three levels of replacement parts are available for the Comet. The three levels are designated A, B, and C. The
level that you should keep on hand for your installation will vary depending on the type of maintenance planned
on site, and the configuration of your UPS system.
Having the replacement parts on hand will prevent any unacceptable delays (because of time involved obtaining
spares) during critical periods, such as system startup. Any items used during start-up will be replaced by MGE
at no charge. Contact MGE Customer Care Center at 1-800-438-7373 for specific recommendations.
A description of each level is provided below:
Level
4 2
Description
This level of replacement parts consists of consumable items, specifically power and control fuses.
It is recommended to have these items on hand during installation of the UPS systems, including initial startup.
This level of replacement parts is recommended when the user can tolerate short-duration UPS down-time
to obtain replacement parts in the event of a major UPS failure. This level of replacement parts consists of
consumable items, specifically power and control fuses, fans, and the most critical circuit board assemblies.
This level of replacement parts is recommended when the user can tolerate only a minimum of down-time in
the event of a major UPS failure. This level of replacement parts consists of consumable items, specifically
power and control fuses, fans, and a significant set of circuit board assemblies.
Maintenance
86-160310-00 E00
MGE Warranty & Proprietary Rights Statement for Three Phase Products
(Applicable within the United States, Canada and Mexico)
MGE Standard Three Phase Warranty
MGE UPS SYSTEMS, INC. (MGE) warrants three phase products it manufactures to be free from defects in
materials and workmanship for a period of three hundred sixty five (365) days counting from the date of purchase by
or for the first end user (Purchaser), or, if applicable, the date of MGEs completion of initial startup of the subject
product, provided however said warranty shall not exceed eighteen (18) months from the date of delivery of the
subject product to Purchaser (the Warranty Period). MGEs liability hereunder is limited to replacing or repairing at
MGEs factory or on the job site, at MGEs option, any part or parts that are defective and reported to MGE during
the Warranty Period. MGE shall have the sole right to determine if the parts are to be repaired at the job site or
whether they are to be returned to the factory for repair or replacement. All items returned to MGE for repair or
replacement must be sent freight prepaid to its factory. Purchaser must obtain MGEs Return Goods Authorization
(RGA) prior to returning items. The conditions stated herein must be met for MGEs warranty to be valid. MGE will
not be liable for any damage done by unauthorized repair work, unauthorized replacement parts, from any misapplication of the subject product, for damage due to accident, abuse, or act of God (such as earthquake, flood, inclement
weather, rain or fire), or relating to Purchasers failure to follow proper environmental conditions for the product.
In no event shall MGE be liable for loss, damage, or expense directly or indirectly arising from the use of or any
defects in the subject product, or from any other cause, except as expressly stated in this warranty. EXCEPT AS
EXPRESSLY STATED IN THIS WARRANTY, MGE UPS SYSTEMS, INC. MAKES NO WARRANTIES, EXPRESS OR
IMPLIED, INCLUDING ANY WARRANTY AS TO MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE OR USE OR NON-INFRINGEMENT. MGE is not liable for and Purchaser waives any right of action it
has or may have against MGE for any consequential or special damages arising out of any breach of warranty, and
for any damages Purchaser may claim for damage to any property or injury or death to any person arising out of its
purchase or the use, operation or maintenance of the subject product. The warranty stated herein includes parts and
labor; however, MGE will not be liable for any labor subcontracted or performed by Purchaser for preparation of the
warranted item for return to MGEs factory or for preparation work for field repair or replacement, and MGE will not
be responsible to pay any invoice therefore.
This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a
writing signed by an authorized officer of MGE UPS SYSTEMS, INC. This warranty shall extend to the Purchaser
but to no one else. Accessories supplied by MGE, but manufactured by others, carry any warranty the manufacturers have made to MGE, and which can be passed on to Purchaser.
MGE UPS SYSTEMS, INC. makes no warranty with respect to whether the products sold hereunder infringe any
patent, U.S. or foreign, and Purchaser represents that any specially ordered products do not infringe any patent.
Purchaser agrees to indemnify and hold MGE UPS SYSTEMS, INC. harmless from any liability by virtue of any
patent claims where Purchaser has ordered a product conforming to Purchasers specifications, or conforming to
Purchasers specific design.
Purchaser has not relied and shall not rely on any oral representation regarding any products sold hereunder and
any oral representation shall not bind MGE UPS SYSTEMS, INC. and shall not be part of any warranty.
There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS
SYSTEMS, INC. be responsible for consequential damages or for any other damages except as expressly stated
herein.
Proprietary Rights Statement
The information in this manual is the property of MGE UPS SYSTEMS, INC., and represents a proprietary article in
which MGE UPS SYSTEMS, INC. retains any and all intellectual property rights, including exclusive rights of use
and/or manufacture and/or sale. Possession of this information does not convey any permission to reproduce,
print, manufacture or have made the article or articles shown herein. Such permission may be granted only by
specific written authorization signed by an authorized officer of MGE UPS SYSTEMS, INC.
IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and
MGE UPS SYSTEMS are trademarks of MGE UPS SYSTEMS, INC. Other trademarks that may be used herein
are owned by their respective companies and are referred to in an editorial fashion only.
For Three Phase Warranty outside of the United States, Canada and Mexico, refer to Three Phase International
Warranty.
January 2005 Rev C00
________________________________________
First name
________________________________________
Company name
________________________________________
Address
________________________________________
Zip code
________________________________________
City
________________________________________
State/Province
________________________________________
Country
________________________________________
Tel
________________________________________
Fax
________________________________________
________________________________________
Product Information
Model
________________________________________
Serial Number
________________________________________
Date of purchase
________________________________________
MGE UPS SYSTEMS, INC., 1660 Scenic Avenue, Costa Mesa, CA 92626, USA
Tel: 714-557-1636
Fax: 714-557-9788
41-000154-53 Rev B02 8/2005
Technical questions? If you encounter a problem while following the instructions in this manual, or have
questions about the operation, repair, or servicing of your equipment, please direct calls to MGE UPS SYSTEMS,
INC. Customer Care Center or visit our web site www.mgeups.com for complete service information.
To insure that your questions are correctly answered, please obtain the serial number of the unit and include
them in any discussions or correspondence.
Serial number:
_____________________________________________________________________
Who To Contact
Customer FAQ
or International calls:
1-714-557-1636
Commitment: MGE UPS SYSTEMS, INC. is committed to providing easy to access factory trained experts that
will provide responses to any questions that you might have.
Should you require factory service for your equipment, contact MGE Customer Care Center and obtain a Return
Goods Authorization (RGA) prior to shipping your unit. Never ship equipment to MGE without first obtaining an RGA
number.
Date:
______________________________________________________
RGA Number:
______________________________________________________
Comet 40-150kVA
W4
86-160310-00 E00
Glossary
Term used
Definition / Meaning
At.
And/or.
+/-
Plus or Minus.
Number.
Degree Celsius.
Degree Fahrenheit.
Phase angle.
Trade Mark.
2nd
Second.
AC or ac
Ambient Temp.
Ambient noise
ANSI
AWG
Breaker
BTU or Btu
British thermal unit. Defined as the amount of heat required to raise the temperature of one pound of water by 1F.
BYPASS
BYPASS mode
Carrier
The company or individual responsible for delivering goods from one location to another.
Common.
CB
Circuit breaker.
cm
Centimeter.
CSA
dB
Decibels.
DC
Direct current.
Conduit
86-160310-00 E00
Glossary
G1
Comet 40-150kVA
G2
C.S.S.
Current rating
The maximum current that a conductor or equipment can carry reliably without damage.
dBA
Decibel Adjusted.
dBrnC
DC or dc
Digital Meter
Earth ground
ECO Mode
Operating mode by which the load is supplied directly by the AC source if it is within the
tolerances defined by the user. This mode reduces the consumption of electrical power.
Electrician
FCC
FET
Freq.
Frequency.
The change in frequency per unit of time. Given in term of Hz per second (Hz/sec.).
GND
Ground (safety).
Hz
Inverter mode
Current.
IEC
IEEE
The input circuit from the building power panel to the equipment.
Inverter
IGBT
I/O
Input/Output.
I/T or IT
Information Technology.
kVA
Line.
LCD
LED
Mains or Mains 1
Mains 2
mA
Milliampere.
MAX.
Maximum.
MCM
Thousand circular mil; standard wire sizes for multiple stranded conductors over 4/0 AWG in
diameter. M is from Roman numerical system indicating 1000.
Glossary
86-160310-00 E00
Neutral.
NC
Normally closed.
NO
Normally open.
NEC
NEMA
NFPA
PF
Power factor.
PN
Part number.
On-line mode
Off-line mode
Inverter output is off, and the load connected at the inverter output receives power
from utility line via a static transfer switch or maintenance bypass relay.
OSHA
PCA
PCB
PWM
SCR
Shipping damage
SPDT
Static Transfer
Technician
Test connector
DB-9 type connector on the LCD panel allowing MGE UPS SYSTEMS Customer
Support Service technician to access programmable and diagnostic features of the
system.
UL
UPS
Volts
VA
Volt amperes
VA
VAC or Vac
Voltage of AC type.
VDC or Vdc
Voltage of DC type.
ve
Battery voltage.
Via
By way of.
86-160310-00 E00
Glossary
G3
Comet 40-150kVA
G4
86-160310-00 E00
Reorder Form
NAME
____________________________________________________________________________________
COMPANY _________________________________________________________________________________
STREET ADDRESS ___________________________________________________________________________
CITY ________________________________________ STATE __________________ ZIP __________________
I would like to order______ (quantity @ $75.00 each) additional copies of the:
Comet 40-150kVA
Installation and User Manual
86-160310-00 E00
w w w. m g e u p s . c o m
Contact MGE
United States
MGE UPS SYSTEMS
1660 Scenic Ave.
Costa Mesa, CA 92626
Tel: (714) 557-1636
CCC: (800) 438-7373
Fax: (714) 557-9788
email: info@mgeups.com
www: mgeups.com
Canada
MGE UPS SYSTEMS
#9, 2789 Thamesgate Drive
Mississauga, ON L4T 4E8
Tel: (905) 672-0990
(877) 672-0990
Fax: (905) 672-7667
email: info@mgeups.com
www: mgeups.com
Latin America and
Other International
MGE UPS SYSTEMS
1660 Scenic Ave.
Costa Mesa, CA 92626
Tel: (714) 513-7831
Fax: (714) 434-0199
email: info@mgeups.com
www: mgeups.com