PLC Connection Guide

Siemens S7-1200 (Symbolic Addressing)


(Ethernet)
Supported Series: Siemens S7-1200 series Ethernet.
Website: http://www.siemens.com/entry/cc/en/

HMI Setting:
Parameters Recommended Options Notes
PLC type Siemens S7-1200 (Symbolic Addressing) (Ethernet)
PLC I/F Ethernet
Port no. 102
Rack 0
CPU slot 1

On-line simulator Yes Multi-HMI connect TIA Settings *Note

*Note:
According to Connection resource / HMI Communication settings
PLC Connection Guide

PLC Setting:
1. In S7-1200 program software create PLC program and tag and then download to
PLC.
2. Select Go offline, EasyBuilder will connect to PLC and get tag data. In PLC type
select “SIEMENS S7-1200 (Ethernet)”.

3. Click “Settings…”, input PLC IP address.


PLC Connection Guide
4. Check the PLC that is not connected to any PC. Click “Get tag info…”.
5. Supported by firmware V3.X and previous versions. For V4.0 or later, please see How
to Connect With S7-1200 Firmware V4.0)
PLC Connection Guide
6. If the software used is a version later than TIA Portal V11,SP2, a dialog of
FunctionBlock directory will be shown, users have to define the mapping from FB to
DB in this directory then click “Check OK”. The tag information will be gained and
a successful message is shown.
PLC Connection Guide
7. When opening an existing project and get the tag information again, if the PLC
software used is TIA Portal V12 and later versions, the DB name must be entered
again in order to compile the project.

8. Added Tag Manager that allows selecting the Siemens S7-1200 PLC tags to be
imported.
PLC Connection Guide
9. Create an object and click read address “Setting…”

10. In PLC name select S7-1200 then click Tag.

11. Select PLC tag.


PLC Connection Guide

How to Connect With S7-1200 Firmware V4.0


There are certain restrictions in S7-1200 firmware V4.0, therefore, to avoid communication
errors, please follow the steps to set up.( EasyBuilder8000 does not support Siemens
S7-1200 firmware V4.0 and later versions).

Right click on the PLC program, and then click [Properties].

Select [Protection], and then select [Permit access with PUT/GET communication
from remote partner (PLC,HMI,OPC,…].

The following part introduces how to export S7-1200 PLC Tags and Program Blocks.
PLC Connection Guide
Exporting PLC Tags (I,Q,M tags)
1. Under [PLC tags] select [Show all tags].

2. Click [Export] to export the tags.

3. Browse for the directory to save the exported file and then click [OK].
PLC Connection Guide
Exporting Program Blocks(DB)
1. When the database contains Struct data type, please note the following restrictions.
Please at least add one data member that doesn’t belong to Struct data type into DB,
otherwise, the data cannot be imported to EasyBuilder.
Multidimensional Arrays and Multilayer Structs are not supported.
After building DB, please do the following actions for Struct address:
(1) Copy the complete Struct data.
(2) Delete data.
(3) Add a new row.
(4) Paste data.

2. Right click on DB, click [Generate source from blocks], and then enter the file name
to save.
PLC Connection Guide
After building and importing PLC Tags and Program Blocks, click [Download to device].

Importing PLC Tags and Program Blocks(DB)


1. Launch EasyBuilder and set the IP address.

2. Click [Import Tag…].


PLC Connection Guide
3. Select the PLC Tags and Program Blocks to be imported. Please remember to change
DB number, and select [Use S7-1200 firmware version 4.0 or later versions]. Click
[Import] to import the files. The I, Q, and M addresses will be checked, if an error
occurs, the communication will fail. If this happens, please check your communication
environment, and try to import again.
* At least one db file must be imported. If only plc tags cannot be imported
successfully.

4. The “Import status” field will display the result, click [OK].
PLC Connection Guide
5. Select the tags to be imported and then click [OK].

6. The following message is displayed when the import has succeed.


PLC Connection Guide

Support Device Type:


S7-1200 data type EasyBuilder data format Memo
Bool bit
Byte 16-bit BCD, Hex, Binary, Unsigned 8-bit
SInt 16-bit BCD, Hex, Binary, Signed 8-bit
USInt 16-bit BCD, Hex, Binary, Unsigned 8-bit
Word 16-bit BCD, Hex, Binary, Unsigned 16-bit
Int 16-bit BCD, Hex, Binary, Signed 16-bit
UInt 16-bit BCD, Hex, Binary, Unsigned 16-bit
DWord 32-bit BCD, Hex, Binary, Unsigned 32-bit
DInt 32-bit BCD, Hex, Binary, Signed 32-bit
Real 32-bit Float 32-bit
UDInt 32-bit BCD, Hex, Binary, Unsigned 32-bit
LInt 64-bit Signed 64-bit

ULInt 64-bit Unsigned 64-bit

LWord 64-bit Unsigned 64-bit

Double 64-bit Float 64-bit

Char 16-bit BCD, Hex, Binary, Unsigned USInt


CREF Struct
Date 16-bit BCD, Hex, Binary, Unsigned UInt
DTL Read only
ErrorStruct
IEC_COUNTER
IEC_DCOUNTER
IEC_SCOUNTER
IEC_TIMER
IEC_UCOUNTER
IEC_UDCOUNTER
IEC_USCOUNTER
NREF
PLC Connection Guide
S7-1200 data type EasyBuilder data format Memo
Time 32-bit BCD, Hex, Binary, Unsigned DWord
Time_Of_Day 32-bit BCD, Hex, Binary, Unsigned DWord
Bool, Byte, SINT,
USInt, Word, Int,
Array UInt, DWord, Dint,
Real, UDInt
Bool, Byte, SINT,
USInt, Word, Int,
Struct UInt, DWord, Dint,
Real, UDInt
Note: EBPro V6.03.02 or later supports 64 bits data type (cMT Series only), but please
note that the address limit range is 48 bits in maximum.

Wiring Diagram:
Ethernet cable: