Professional Documents
Culture Documents
Specification-Cable Tray
Specification-Cable Tray
SECTION 26 05 36
TABLE OF CONTENTS
Volume 2 Part C
Section 26 05 36 Cable Trays for Electrical Systems Page 1 of 6
PGC-190003-C-P1
PART 1 - GENERAL
1.01 SCOPE
A. Metallic cable trays including ventilated (perforated) bottom and ladder.
1.05 WARRANTY
A. The Contractor shall warrant that all materials and equipment are suitable for
continuous use and operation in the climatic conditions encountered on site.
B. Written warranty shall be provided, signed by manufacturer and installer agreeing to
replace devices and equipment that fail in materials or workmanship within warranty
period.
Volume 2 Part C
Section 26 05 36 Cable Trays for Electrical Systems Page 2 of 6
PGC-190003-C-P1
1.06 SUBMITTAL
A.
remedies, limitations, and exclusions.
B. Manufacturer
C. Product certificates: Signed by manufacturers of components certifying that products
furnished comply with requirements.
D.
to demonstrate their capabilities and experience. Include lists of completed projects
with project names and addresses, names and addresses of architects/engineers and
owners, and other information specified or required by Engineer.
E. Tests and Certificates: Submit complete certi
Article.
F.
specification section. Indicate and interpret test results for compliance with system
description and performance requirements.
G. Warranties: Warranties specified in this Section.
H. Certificate of Origin.
PART 2 - PRODUCT
2.01 CABLE TRAYS
A. Cable tray systems shall be of indicated types, sizes, and standard classes and shall be
complete with manufacturer's recommended covers, barrier strips, dropouts, fittings,
conduit adaptors, hold-down devices, grommets, and blind ends as required and
indicated.
B. Cable tray products shall have rounded edges (Return Flange type) and smooth
surfaces.
Volume 2 Part C
Section 26 05 36 Cable Trays for Electrical Systems Page 3 of 6
PGC-190003-C-P1
C. Perforated type trays shall be heavy duty, heavy gauge perforated sheet steel, hot-dip
galvanized after manufacture, minimum 1.5 mm thick, with sides not less than 45 mm
deep, and as shown on Drawings. Fittings shall be same as that of the material used for
tray. Covers, where shown on Drawings, shall be minimum 1.0 mm thick galvanized
sheet steel, Snap-On type or forming a rigid assembly with tray.
D. Ladder type trays shall be heavy duty, hot dip galvanized after manufacture, fabricated
from 2 mm mild carbon steel. Ladder side channels shall be minimum 127 x 23 mm,
strengthened by reinforcing inserts for torsional rigidity. Rungs shall be slotted to take
cable cleats or ties and conduit clamps. Rungs shall be minimum 50 x 25 mm channels,
spaced at 300 mm centers.
E. Except as otherwise indicated, provide metal cable trays, with splice plates, bolts, nuts
and washers for connecting units; capable of supporting concentrated loads of 90kg at
any point, over and above full cable load.
F. Provide cable tray supports and connectors, including bonding jumpers, as indicated
and as recommended by cable tray manufacturer.
G. Steel Galvanizing: shall be in accordance with EN ISO 1461 applied after fabrication,
wit
H. Tray or ladder is to have strength and rigidity to provide support for cables contained
within. Deflection between supports is not to exceed 1/350 under full loading capacity.
I. Earthing Connector: for trays or ladders, provide earthing connector on each coupling
between adjacent sections.
2.03 ACCESSORIES
A. Covers: ventilated-hat type, of same materials and finishes as cable trays.
Volume 2 Part C
Section 26 05 36 Cable Trays for Electrical Systems Page 4 of 6
PGC-190003-C-P1
3. Powder-Driven Threaded Studs: heat-treated steel, designed specifically for
intended service.
PART 3 - EXECUTION
3.01 INSTALLATION
A. Install cable trays in accordance with equipment manufacturer's written instructions.
B. Remove burrs and sharp edges of cable trays.
C. Conform to manufacturer's recommendations for selection and installation of supports.
D. Strength of each support including fastenings to structure shall be adequate to carry
present and future load multiplied by a safety factor of at least four or calculated load
plus 90 kg, whichever is greater. Spacing of supports is not to exceed 1.5 m.
E. Installation of supports shall be in accordance with cable tray manufacturer's written
instructions and recommendations.
F. Fastening Supports: unless otherwise indicated, fasten cable tray supports securely to
building structure as specified in Section 26 05 29.
G. Support at Connections to Equipment: where cable trays are connected to equipment,
provide flanged fittings fastened to tray and to equipment. Support tray separately. Do
not carry weight of tray on equipment enclosure.
H. Thermal Contraction and Expansion: install expansion connectors in cable tray runs that
exceed following length:
1. Steel Tray: 52.5 m.
2. Spacings and gap settings for expansion connectors shall not exceed
recommendations of approved applicable standards.
I. Direction Changes: make changes in direction of cable tray with standard cable tray
fittings.
J. Locate cable tray above piping except as required for tray accessibility and as otherwise
indicated.
K. Fire-stopping: where cable trays penetrate fire and smoke barriers including walls,
partitions, floors, and ceilings, install fire-stopping at penetrations after cables are
installed.
L. Sleeves for Future Cables: install capped sleeves for future cables through fire-stopped
cable tray penetrations of fire/smoke barriers.
M. Working Space: install cable trays with sufficient space to permit access for installing
cables.
Volume 2 Part C
Section 26 05 36 Cable Trays for Electrical Systems Page 5 of 6
PGC-190003-C-P1
N. Barriers: where cable trays carry conductors of different systems such as power,
communication and data, or different insulation voltage levels, separate cable trays shall
different systems or voltages on same cable tray, use proper insulating barriers to
g to
requirements of codes and recommendations of manufacturers.
3.02 GROUNDING
A. Electrically earth cable trays and ensure continuous electrical conductivity of cable tray
system. Use tray as an equipment earthing conductor for itself only, not for connected
equipment.
END OF SECTION
Volume 2 Part C
Section 26 05 36 Cable Trays for Electrical Systems Page 6 of 6