Man 1112 Sigma XT Manual 26
Man 1112 Sigma XT Manual 26
Man 1112 Sigma XT Manual 26
1. Introduction ......................................................................................................... 5
2. Safety and mounting ............................................................................................ 6
2.1 Safety ................................................................................................................. 6
2.2 Mounting ............................................................................................................. 7
3. Technical specification ......................................................................................... 8
4. Control panel fascia’s ......................................................................................... 12
4.1 Removing the fire detection equipment chassis ...................................................... 13
5. Connecting to the circuit boards ......................................................................... 14
6. Detection zone wiring ......................................................................................... 17
7. Sounder circuit wiring (alarm devices as required by EN12094-1) ..................... 17
8. Using intrinsically safe barriers .......................................................................... 18
9. Connection to monitored inputs ......................................................................... 19
10. Connection to extinguishant output.................................................................. 19
10.1 Solenoid wiring ................................................................................................. 19
10.2 Igniting actuator wiring ..................................................................................... 20
10.3 Setting up extinguishant monitoring circuit .......................................................... 20
11. Connection to remote control terminals ........................................................... 21
12. Aux 24V DC supply outputs (extinguishant modules only) ............................... 21
13. Connection to relay contacts ............................................................................ 22
13.1 Common Fault relay (on detection part of control panel) ........................................ 22
13.2 Fault relay (on extinguishing part of control panel) ............................................... 22
13.2 Local fire relay (on detection part of control panel) ............................................... 22
13.3 Fire relay (on detection part of control panel) ....................................................... 22
13.4 1st stage alarm relay (on extinguishing modules) .................................................. 22
13.5 2nd stage alarm relay (on extinguishing modules) ................................................ 22
13.6 Released relay (on extinguishing modules) .......................................................... 22
13.7 Aborted relay (on extinguishing modules) ............................................................ 22
13.8 Extract relay (on extinguishing modules) ............................................................. 22
14. Connection and configuration of status units and ancillary boards ................... 23
14.1 Adding new status units/ancillary boards ............................................................. 24
14.2 Removing status units or ancillary boards ............................................................ 24
15. Configuring the panel ....................................................................................... 27
15.1 Detection part .................................................................................................. 27
15.2 Extinguishing modules ....................................................................................... 29
15.2.1 Language selection .....................................................................................................29
15.2.2 Extinguishant output mode..........................................................................................29
15.2.3 Configuring the activation mode...................................................................................30
15.2.4 Configuring Stage 1 /Hold Output ................................................................................30
15.2.5 Configuring the activation zones ..................................................................................30
15.2.6 Reset inhibit time .......................................................................................................31
15.2.7 Pre-release delay time ................................................................................................31
15.2.8 Output 2 delay...........................................................................................................31
15.2.9 Extinguishant release time ..........................................................................................31
15.2.10 Second stage alarm pulsing/continuous (alarm devices as required by EN12094-1) ..........32
15.2.11 Released indication ...................................................................................................32
15.2.12 Delay on manual release ...........................................................................................32
15.2.13 Release timer (infinite extinguishant duration) .............................................................32
15.2.14 R0V not removed on reset .........................................................................................33
15.2.15 Disable earth fault monitoring ....................................................................................33
15.2.16 Disable fault output ..................................................................................................33
15.2.17 Invert low pressure switch input.................................................................................34
15.2.18 Invert Released Pressure switch input .........................................................................34
Man-1112 Sigma XT+_26 Page 2 of 52
15.2.19Extinguishant output monitoring levels.........................................................................34
16. Panel operation – Access levels 1 and 2 ........................................................... 35
16.1 Normal condition .............................................................................................. 35
16.2 Detection section – Access level 2. ...................................................................... 35
16.2.1 Test mode .................................................................................................................35
16.2.2 Disable zones ............................................................................................................35
16.2.3 Disable sounder outputs..............................................................................................35
16.2.4 Activate delays ..........................................................................................................36
16.3 Extinguishant modules – Access level 2 ...........................................................................36
16.3.1 Disable extinguishant release outputs. ..........................................................................36
16.3.2 Disable Manual release ...............................................................................................36
16.3.3 Disable Stage 1 output ...............................................................................................36
16.3.4 Disable Stage 2 output ...............................................................................................37
16.3.5 Disable Released output ..............................................................................................37
16.3.6 Disable Extract output ................................................................................................37
16.3.7 Turn on Extract output................................................................................................37
16.3.8 Select Reserve Solenoid Output (Configuration Option) ...................................................37
16.4 Single zone Fire condition ................................................................................. 38
16.5 Double zone Fire condition ................................................................................. 38
16.6 Silence/sound alarms ........................................................................................ 38
16.7 Reset .............................................................................................................. 38
16.8 Detection Zone fault.......................................................................................... 38
16.9 Sounder fault ................................................................................................... 38
16.10 Power fault ..................................................................................................... 38
16.11 System fault – Detection section ....................................................................... 38
16.12 System fault – Extinguishant modules ............................................................... 39
16.13 General fault – Detection section ...................................................................... 39
16.14 Lamp test ...................................................................................................... 39
16.15 Hold condition ................................................................................................ 39
16.16 Released condition .......................................................................................... 39
16.17 Low pressure switch ........................................................................................ 39
16.18 Manual only mode ........................................................................................... 39
16.19 Manual Release............................................................................................... 39
16.19 Abort input ..................................................................................................... 39
17. Internal Controls .............................................................................................. 40
17.1 Detection part .................................................................................................. 40
17.1.1 Watchdog reset..........................................................................................................40
17.1.2 Processor reset ..........................................................................................................40
17.1.3 Write enable switch ....................................................................................................40
17.2 Extinguishant modules ...................................................................................... 40
17.2.1 Watchdog reset..........................................................................................................40
17.2.2 Processor reset ..........................................................................................................40
17.2.3 Terminate extinguishant .............................................................................................40
17.2.4 Write enable switch ....................................................................................................40
17.2.5 Address switch...........................................................................................................41
18. Internal indications .......................................................................................... 41
18.1 Detection part .................................................................................................. 41
18.1.1 Mains fail ..................................................................................................................41
18.1.2 Batt fail.....................................................................................................................41
18.1.3 CPU fault...................................................................................................................41
18.1.4 Aux 24V fault ............................................................................................................41
18.1.5 Batt low ....................................................................................................................41
18.1.6 Comms fault ..............................................................................................................42
18.1.7 Earth fault .................................................................................................................42
18.1.8 Sys fuse fault ............................................................................................................42
18.1.9 S1 fault.....................................................................................................................42
18.1.10 S2 fault ...................................................................................................................42
18.2 Extinguishant modules ...................................................................................... 42
18.2.1 Watchdog..................................................................................................................42
18.2.2 System fuse ..............................................................................................................42
The SIGMA XT+ range of control panels are designed in accordance with European standards EN54-2 and EN54-4 Fire
Detection and Fire Alarm systems - Control and Indicating Equipment and EN12094-1 Fixed firefighting systems -
Components for gas extinguishing systems - Part 1: Requirements and test methods for electrical automatic control
and delay devices.
The control equipment is a combined fire alarm control panel and extinguishing system with up to eight detection
zones, and up to four extinguishant flooding areas.
Control panels have an integral, mains powered battery charger and power supply designed in accordance with the
requirements of EN54-4.
In addition to the requirements of EN54-2 the control panel has the following facilities:
Test condition to allow the automatic resetting of zones in alarm for testing purposes. EN54-2 Section 10: option with
requirements.
Delay of the actioning of fire alarm devices (sounders) so that an alarm may be verified before a premises is evacuated.
EN54-2 Section 7.11: (option with requirements).
Fire alarm devices to enable an audible warning to be sounded throughout premises upon the detection of a fire
condition or the operation of a manual call point. EN54-2 Section 7.8: (option with requirements).
In addition to the requirements of EN54-2, all control panels have voltage free relay contacts for fire and local fire
which operate upon a fire condition. These are to be used for local control and signalling.
The following compulsory functions required by EN12094-1 are included:
4.3.2a Reception and processing of at least one input triggering signal from an f.d.a.s and an input triggering signal
from manual triggering device(s) connected directly to the e.c.d.
4.3.2b Transmission of the extinguishing signal upon receipt of input triggering signal(s).
4.3.2c Activation of alarm devices upon receipt of input triggering signal(s).
4.2.2d Unambiguous indication of each condition.
4.2.3e Transmission of the information of the incorrect ststus of components and of the fault warning condition.
4.3.2f Transmission of the information of the released condition.
In addition to the compulsory requirements of EN12094-1 the control panel has the following facilities:
Delay of extinguishing signal of up to 60 seconds. EN12094-1 Section 4.17: (option with requirements).
Signal representing the flow of extinguishing agent to indicate the released condition. EN12094-1 Section 4.18: (option
with requirements).
Monitoring of the status of components by way of a low pressure switch input. EN12094-1 Section 4.19 : (option with
requirements).
Emergency hold device to enable the extinguishant delay time to be extended. EN12094-1 Section 4.20: (option with
requirements).
Control of flooding time to deactivate the releasing output after a set period of time. EN12094-1 Section 4.21: option
with requirements.
Manual only mode to disable the release of extinguishant via automatic detection devices. EN12094-1 Section 4.23:
(option with requirements).
Triggering of equipment outside the system by way of first and second stage contacts, extract fan output etc. EN12094-
1 Section 4.26: (option with requirements).
Activation of alarm devices with different signals to indicate pre- discharge and released warnings using different
sounds. EN12094-1 Section 4.30: (option with requirements).
Emergency Abort device to inhibit the extinguishing signal until the emergency abort device has been de-activated and
the panel has been reset. EN12094-1 Section 4.27: (option with requirements).
Extinguishing signals to spare cylinders. EN12094-1 section 4.25 (option with requirements)
According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that
you make any appropriate information about this product available to anyone concerned with its use.
This equipment is designed to operate from 230V 50Hz mains supplies and is of class 1 construction. As such it must
be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double
pole disconnect device meeting the requirements of EN60950/IEC950 which disconnects live and neutral simultaneously
shall be incorporated in the fixed wiring.
Switch disconnect devices such as MK Sentry 63A or similar are suitable for this.
Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the
protective earth will render the equipment unsafe.
This control panel is environmental class A and is designed for indoor use only at temperatures between -50C (+/- 3)
and +400C (+/- 2) and with a maximum relative humidity of 95%.
The IP rating for the enclosure is IP30.
Operation outside of these limits may render the equipment unsafe.
5mm DIAMETER
SCREWS
Note: LCMU (Line Continuity Monitoring Device) part number K14060 allows call points mounted down line of
detectors that have been removed from diode bases to continue to operate.
This drawing shows the fascia’s of the models available in the Sigma XT+ range.
K21082M3
K21083M4 K21084M4
The fascia’s are divided into sections for the detection panel and extinguishant modules. A standard EN54-2 control
and indicating equipment section with up to eight zones is located in the top aperture of the panel fascia and
EN12094-1 extinguishant modules are fitted in the lower apertures.
All connections for field wiring are to rows of terminals along the top and bottom of the
circuit boards.
Shielded fire alarm cable such as FP200 and metal cable glands must be used for all connections to the panel.
The shield of the cable must be bonded securely to the enclosure earth via a metal cable gland.
The resistance of any core of any cable must not exceed 25 ohms. The shield of the cable must be bonded
securely to the enclosure via the metal gland.
Wiring should enter the enclosure at the top or back of the panel using the knockouts provided and be formed tidily
to the appropriate terminals ensuring that no cables are run close (minimum 50mm) to the surface of any of the
circuit boards.
Route mains cables away from all other cables and segregate by 50mm.
Terminals are capable of accepting wires of up to 2.5mm2.
Wiring must not go across the front of the circuit boards. If cable entries need to be in positions other than at the
knockouts provided, wiring must be fed behind and well away from the surface of the circuit board.
The space at the bottom of the enclosure is largely occupied by the standby batteries so this must be borne in mind
when considering cable entries.
The detection zones provide a nominal 20V DC to power conventional detectors and call points as listed in the
compatibility tables 2 and 3.
The wiring is monitored for open and short circuit fault conditions by removing the 6K8 0.5W end of line monitoring
resistors that are supplied fitted to the control panels’ terminals and placing them across the last device that is wired
to the zone circuit.
Detection zone circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring
circuit to work correctly.
For systems that are required to comply with BS5839 Part1:2002 detector removal requirements, either detector
bases fitted with a Schottky diode should be used and the end of line resistor replaced with an LCMU active end of
line monitoring device or zener clamping bases such as Hochiki PA6 or Apollo Savwire used.
CALL
DETECTOR
POINT
-
ZONE
TERMINALS line resistor
- IN - OUT
Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring circuit
to work correctly.
POLARISED POLARISED
SOUNDER SOUNDER
-
OUTPUT
TERMINALS line resistor
- IN - OUT - IN - OUT
Connection of the I.S. barrier changes the characteristics of the detection circuit so zones that have I.S. barriers
connected must be adjusted to work with them.
Programmable options C61 to C68 on the detection section allow each zone to operate with I.S. barriers.
The amount of detectors and call points that can be connected to a zone is limited by the I.S. approval system
diagram which should be supplied by the detector manufacturer. The power rating of the end of line resistor will be
dependent upon the Zone classification rating (Gas class) this will be specified on the system diagram.
- IN - OUT
-
ZONE
TERMINALS MTL5061 GALVANIC I.S. I.S. CALL
ISOLATOR DETECTOR POINT
DETECTION + 6 7
+ IN + OUT 6K8 end of
-
ZONE 5 8
TERMINALS line resistor
4 9
3 10
2 11 - IN - OUT
POLARISED POLARISED
SOUNDER SOUNDER
+
MTL7778ac
SOUNDER
+ IN + OUT + IN + OUT 10 K end of
-
OUTPUT
TERMINALS line resistor
- IN - OUT - IN - OUT
+ PRESSURE
SWITCH
-
6K8 END
OF LINE
REISTOR
470
OHMS
The extinguishant output is capable of supplying up to 1 Amp for the maximum duration to a solenoid or 3 Amps for
20 milliseconds to an igniting actuator or Metron.
The wiring for solenoids and igniting actuators is different as shown below. Igniting actuators of different types or
from different manufacturers should not be mixed on the same circuit.
+ +
EXTING
-
DIODE 1N 4004
BAND END TO +
3 OR 4 ACTUATORS
WIRED IN SERIES
(MAXIMUM OF 4)
M M M M
+
EXTING
1 OR 2 ACTUATORS
WIRED IN SERIES
M M
+ FIT 2R2 2.5W RESISTOR
EXTING
IN SERIES WITH
ACTUATORS IF ONLY 1 OR
- 2 ACTUATORS ARE USED
To guarantee firing under all conditions, the total resistance of actuators, monitoring resistor and cable should not
exceed 7 ohms.
Ac c e s s l e v e l 2 ►
E NT E R f o r Me n u
Operate the WRITE ENABLE switch by gently sliding it to the left. The LCD will show:
A L 3 Up d a t e s = x x
E NT E R f o r Me n u
Press the ENTER button and then the UP button repeatedly until the LCD displays:
E x t i n g . O/ P 1
L e v e l = XX X
The XXX displayed here is the previous (factory) level to which the monitoring level had been set.
E x t i n g . O/ P 1
L e v e l = XX X ?
The XXX shown here is the current monitoring level detected on the extinguishing output. Press the ENTER button
to learn the new monitoring level.
Press the UP button to set the monitoring level for output 2 in the same way if it is being used, otherwise switch the
write enable slide switch to the right (off) position and check that an open or short circuit fault on the extinguishing
output(s) is detected and shown on the control panel.
To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open switch
or contact and via a resistance of no greater than 100 ohms.
All of the remote control inputs are non-latching.
R0V SIL AL FLT RST
FAULT INPUT
RESET INPUT
A L 3 Up d a t e s = x x
E NT E R f o r Me n u
Press the ENTER button and then the UP button repeatedly until the LCD displays:
R0 V No t Re mo v e d
On S y s t e m Re s e t
R0 V No t Re mo v e d
On S y s t e m Re s e t ?
R0 V Re mo v e d
On S y s t e m Re s e t
The Aux 24V supply outputs are fitted with an electronic, self resetting fuse rated at 0.5 Amps to protect the control
panel’s 24V supply in the event of a wiring fault. The Aux 24V outputs should not be loaded with any more than
100milliamps per module.
Any standing load on the Aux 24V supply outputs must be taken into account when calculating battery standby times
as standby time will be significantly affected by even modest standing loads on these outputs. It is recommended
that the Aux24V outputs are not used to power standing loads.
Where the Aux 24V supply outputs are used to power electromechanical devices such as relays or door retainers it
is imperative that a suppression diode is fitted across the coil of the device to prevent the generation of high voltage
transients back to the control panel power supply.
To switch on the extract relay, operate the enable keyswitch and then press ENTER on the module on which the
required Extract relay is fitted.
The LCD will show:
DI S A B L E
E X T I NG REL E A S E ? Press the down button until the display shows:
T URN ON
E X T RA CT OUT P UT ? Press ENTER to turn on the Extract output.
T URN Of f
E X T RA CT OUT P UT ?
TP34
C12
R12
D2
R87 R90
+
Q17
OPT1
C31 C7 R110
R55
TP28
R22
R59
R24
C81
W3 C16 D1 Q16
U14 TP36 R11 R161
C82 L34 R168
TP3 D12 R74 R160 R91
R169
R171
R88 R165 R173
U8
LED10
LED12
U1 R170 R65
U5
R159 k R172k R92
C80 C83 D11 D10 LED8
U13 R164 k R167 R68 R70 C70
k C2
+
TP23
C77
+
R28
R166
D29 C19 C21
R29
LK4
C18
C20
R7 R6
LK2 U12 D17 D16 D15 D43 D14 D13 D9 D4 TP26
C25
C78 C27
R182 C26
C79 F3 U3
C71 C72
U4 R54 R51 R50 R48 R47 R42 R176 R175 R41 R40 R35 R34 R33 R32 R31 R30
+
R181
R180
R179
+
C6
L32
C75
L8 L7 L6 L5 L4 L3 L2
R8
C5
R89 R86
C76 C74 C50 C49 C47 C46 C43 C42 C111C110 C41 C40 C39 C38 C37 C36 C35 C34
U11
Each status unit and ancillary board has a 3-bit DIL switch and must be allocated a unique address between 1 and
7. A maximum of 3 status units or Ancillary boards can be powered from the extinguishing module 24V output.
More units should use external 24V power supply.
The system is able to distinguish between status units and ancillary boards so it is possible to have a status unit set
to address 1 and an ancillary board set to address 1 if desired.
The address switch is located on the bottom left hand corner of the status unit or ancillary board PCB. Note: The
address is only read when the boards are first powered or if the processor reset switch on the ancillary board or
status unit is pressed, so address switches should not be altered on a system that has power applied.
It is important that each individual status unit and ancillary board is allocated a unique address in the range 1 to 7.
Units of the same type with the same address will cause intermittent faults to be displayed.
NOTE: 10 lamp status units (models K911113M8, K911113F8 and W911113W8) are not compatible with Sigma XT+
extinguishant modules.
Press ENTER on the module to which the status units or ancillary boards are connected with the ENABLE control
switch keyswitch off and use the UP button on the module to view the faults. If status units and/or ancillary boards
are detected the LCD will display:
out put uni t X X = the address of the ancillary board unit found
E NT E R T O A CCE PT
When the ENTER button is pressed on the module to which the status units or ancillary boards are connected, the
selected status unit or ancillary board will be added to the system and the next unit to be added will be displayed.
Press the ENTER button on the extinguishing module until all of the units have been accepted then gently slide the
WRITE ENABLE switch on the module to the right.
All of the status units and ancillary boards found by the extinguishant module have now been added and
disconnection of any of them will be displayed as a fault on the module and on the detection part of the system. If
any status units are disconnected, a HOLD activated indication will also be displayed at the extinguishing module
and all ancillary boards or status units that remain connected. With the ENABLE controls keyswitch off, the LCD will
display:
RE MOT E B US
F A UL T
When additional status units or ancillary boards are added to the system, these will be shown on the LCD of the
extinguishing module when the system is powered up or the processor reset switch is pressed on the module to
which the status unit or ancillary board is connected and can be added to the system by following the procedure
above.
RE MOT E B US
F A UL T
Press the processor reset button on the extinguishant module to which the status unit or ancillary board is connected.
When the extinguishant module has re-started, it will display:
Turn the ENABLE controls keyswitch on and gently slide the write enable switch on the extinguishant module to
which the status units or ancillary boards are connected, to the left.
The LCD will then display:
out put uni t X X = the address of the remaining ancillary boards unit found
E NT E R T O A CCE PT
When the ENTER button is pressed on the module to which the status units or ancillary boards are connected, the
selected status unit or ancillary board will be added to the system and the next unit to be added will be displayed.
Press the ENTER button on the extinguishing module until all of the units have been accepted then gently slide the
WRITE ENABLE on the extinguishing module switch to the right.
Full details of status units and ancillary boards can be found in documents MAN-1089 (Sigma XT Status unit operation
an maintenance manual) and MAN-1095 (Ancillary board operation and maintenance manual).
D1036S ISSUE 04
S/NO.
X1
IC7
+ - + -
R22 R25
R30C R28
+24V- +24V-
W6 LED1
PF Z1 Z2 Z3 MAN DISAB REL ACT HOLD EXTR MAN
R13
C14
F IR E F IR E F IR E MODE REL RS485 RS485
R30A
R30D
R23 R26
R30B
C20
C19
R21
R24
DC DC IN OU T W5 IC4
D3
IC6 LED2
R1
R29
R29B
R29A
MODE HOLD
R27
R17 D7 T R6 D10 T R5 Z1 LED3
J2
C17 +
R29C
R29D
R20
D8 D9 Z2
R18
IC2 T R2 BZ1 LED5
-
OUT
LED6
T R4
+
OR STATUS UNIT
RS485
R7 C11
D1
C3
R9
R6
Z10 X1
LED7
-
IC3 D5
R10
IC1
IN
+
X4
C4
D4
D6 T R1 LED8
C1
R2
R3
R4
C2
-
R19
C18
R5
C6
+
24V DC
C12
C13
XTAL1
+ LED9
C21
IC5
C9
-
+
R15
C8
REG1 + LED10
R16
R32
C7
C10 F1
R8 C5 D2 LED4
T R3 R12
HOL LED14
COM LED12
MOD LED13
CPU LED11
FUSE LED15
W4 W3 SW5
R11
SW2 SW1
PROC WDOG
ADDR RESET RESET
PROC ESSOR
MAN F USE RESET
Z1 Z2 Z3 MAN DISAB REL ACT REL EXTR HOLD OK FAIL
SW2
SW1
ADDR ESS
Access level 3 (Write enable) enable switch location – slide gently to the right to enable
Configuration options are simple to enter using the codes the table below. When the control panel is at access level
3, the sub-text of the Mode and Select buttons is used to enter a number using tens (+10) and units (+1).
When the required code number is displayed, pressing the enter button will cause the dot on the units seven segment
display to flash. This indicates that a configuration option has been set.
To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1 to A8,
C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set.
21* DISABLE FIRE BUZZER Buzzer will not operate on fire condition
22* DISABLE FAULT OUTPUT Fault relay will not operate except upon total power
failure
23 DISABLE EARTH FAULT MONITORING Connection of fire alarm wiring will not announce a fault
24 PULSED REMOTE CONTROL OUTPUT Aux 24V supply pulses 1 sec on/1 sec off
25 ENABLE SOUNDERS ON DETECTION Not used
CIRCUITS
26 DISABLE FIRE OUTPUT Fire relay will not operate upon any alarm
27 DO NOT CHANGE DO NOT CHANGE
31 ZONE 1 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options
32 ZONE 2 ALARM FROM DETECTOR DELAYED 0-9 when selected zone(s) triggered by detector only.
33 ZONE 3 ALARM FROM DETECTOR DELAYED Note access level 2 function Ad must be set for this to
34 ZONE 4 ALARM FROM DETECTOR DELAYED take effect.
35 ZONE 5 ALARM FROM DETECTOR DELAYED
36 ZONE 6 ALARM FROM DETECTOR DELAYED
37 ZONE 7 ALARM FROM DETECTOR DELAYED
38 ZONE 8 ALARM FROM DETECTOR DELAYED
41 ZONE 1 ALARM FROM CALL POINT DELAYED Sounder outputs will be delayed by time set at options
42 ZONE 2 ALARM FROM CALL POINT DELAYED 0-9 when selected zone(s) triggered by call point only.
43 ZONE 3 ALARM FROM CALL POINT DELAYED Note access level 2 function Ad must be set for this to
44 ZONE 4 ALARM FROM CALL POINT DELAYED take effect.
45 ZONE 5 ALARM FROM CALL POINT DELAYED
46 ZONE 6 ALARM FROM CALL POINT DELAYED
47 ZONE 7 ALARM FROM CALL POINT DELAYED
48 ZONE 8 ALARM FROM CALL POINT DELAYED
61 CONFIGURE Z1 FOR I.S BARRIER Detection threshold changed for use with IS barrier
62 CONFIGURE Z2 FOR I.S BARRIER
63 CONFIGURE Z3 FOR I.S BARRIER
64 CONFIGURE Z4 FOR I.S BARRIER
65 CONFIGURE Z5 FOR I.S BARRIER
66 CONFIGURE Z6 FOR I.S BARRIER
67 CONFIGURE Z7 FOR I.S BARRIER
68 CONFIGURE Z8 FOR I.S BARRIER
71* ZONE 1 SHORT CIRCUIT INDICATES ALARM Changes the trigger threshold of the
72* ZONE 2 SHORT CIRCUIT INDICATES ALARM zone so that the control panel can be
73* ZONE 3 SHORT CIRCUIT INDICATES ALARM used on older systems that had no short
74* ZONE 4 SHORT CIRCUIT INDICATES ALARM circuit monitoring.
75* ZONE 5 SHORT CIRCUIT INDICATES ALARM
76* ZONE 6 SHORT CIRCUIT INDICATES ALARM
91 ZONE 1 DOES NOT SOUND ALARMS Prevents the zone from operating the two common
92 ZONE 2 DOES NOT SOUND ALARMS sounder outputs.
93 ZONE 3 DOES NOT SOUND ALARMS
94 ZONE 4 DOES NOT SOUND ALARMS
95 ZONE 5 DOES NOT SOUND ALARMS
96 ZONE 6 DOES NOT SOUND ALARMS
97 ZONE 7 DOES NOT SOUND ALARMS
98 ZONE 8 DOES NOT SOUND ALARMS
99
A1* ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously
A2* ZONE 2 ANY ALARM DELAYED before an alarm is generated.
A3* ZONE 3 ANY ALARM DELAYED
A4* ZONE 4 ANY ALARM DELAYED
A5* ZONE 5 ANY ALARM DELAYED
A6* ZONE 6 ANY ALARM DELAYED
A7* ZONE 7 ANY ALARM DELAYED
A8* ZONE 8 ANY ALARM DELAYED
E1* ZONE 1 WILL NOT OPERTATE FIRE RELAY Enables individual zones to be selected to not operate the
E2* ZONE 2 WILL NOT OPERTATE FIRE RELAY fire relay. This is sometimes combined with the non-
E3* ZONE 3 WILL NOT OPERTATE FIRE RELAY latching function to prevent ring around on
E4* ZONE 4 WILL NOT OPERTATE FIRE RELAY interconnected panels
E5* ZONE 5 WILL NOT OPERTATE FIRE RELAY
E6* ZONE 6 WILL NOT OPERTATE FIRE RELAY
E7* ZONE 7 WILL NOT OPERTATE FIRE RELAY
E8* ZONE 8 WILL NOT OPERTATE FIRE RELAY
NOTE: Setting the options marked with asterisks does not comply with EN54-2
E X T I NG O/ P MODE.
= COMMON Press the ENTER button and the display will show:
E X T I NG O/ P MODE.
= MA I N/ RES E RV E ? Press the ENTER button to select main/reserve.
To save the settings, slide the write enable switch gently to the right.
When the extinguishing module is activated, only extinguishant output 1 will switch on.
There will also be an additional menu item at access level 2 to allow the reserve extinguishant output to be
selected.
Man-1112 Sigma XT+_26 Page 29 of 52
15.2.3 Configuring the activation mode
It is possible to configure the extinguishing modules to be activated by coincidence (any 2 zones in a range of
zones) or a single zone in a range of zones. The activation mode is factory set to coincidence.
To change this, switch on the enable controls keyswitch and slide the write enable switch on the module to be
configured gently to the left. Press the ENTER button on the extinguishing module then press the UP button. The
display will show:
A CT I V A T I ON MODE.
= COI NCI DE NCE Press the ENTER button and the display will show:
A CT I V A T I ON MODE.
= si ngl e ? Press the ENTER button to select single zone activation mode.
To save the settings, slide the write enable switch gently to the right.
Operation of any of the zones in the range of zones selected to trigger the module (see below) will now put the
module into the activated condition. Coincidence mode must not be set if single activation is required.
The ‘1st Stage’ relay output is factory set to activate when as a stage 1 alarm contact, it can be re-configured to
activate when the ‘Hold’ input is activated.
To change this, switch on the enable controls keyswitch and slide the write enable switch on the module to be
configured gently to the left. Press the ENTER button on the extinguishing module then press the UP button. The
display will show:
Us e r O/ p Mo d e
= St a g e 1 Press the ENTER button and the display will show:
Us e r O/ p Mo d e
= Ho l d ? Press the ENTER button to change mode.
To save the settings, slide the write enable switch gently to the right.
To do this, switch on the enable controls keyswitch and slide the write enable switch on the module to be
configured gently to the left. Press the ENTER button on the extinguishing module and then the up button until the
display will shows:
F I RS T A CT I V .
Z ONE = X X will be the number of the zone currently selected to be the first activation zone.
This can be changed if required by using the UP and DOWN buttons to select the require zone number. When the
required zone number is displayed, pres the ENTER button. The display will show:
F I RS T A CT I V .
Z ONE = X ? X will be the number of the zone selected to be the first activation zone.
Press the ENTER button and then the UP button. The display will then show:
L A S T A CT I V .
Z ONE = X X will be the number of the zone currently selected to be the last activation zone.
This can be changed if required by using the UP and DOWN buttons to select the require zone number. When the
required zone number is displayed, pres the ENTER button. The display will show:
l a s t A CT I V .
Z ONE = X ? X will be the number of the zone selected to be the last activation zone.
Activation of any of the zones in the range selected will now contribute to activation of this module.
RE S E T I NHI B I T
T I ME = 0 Press the ENTER button and the display will show:
RE S E T I NHI B I T
T I ME = 0 ? To change the reset inhibit time, press the UP or DOWN buttons until the time
required is displayed and then press ENTER.
To save the settings, slide the write enable switch gently to the right.
Resetting of the extinguishing module after it has been activated will now be prohibited until the set reset inhibit
time.
pr e- r el del ay
T I ME = 3 0 s e c . Press the ENTER button and the display will show:
pr e- r el del ay
T I ME = 3 0 s e c . ? To change the time, press the UP or DOWN buttons until the required time is
displayed.
To save the settings, slide the write enable switch gently to the right.
The pre=release delay time will now be set to the chosen value.
This could be used to provide an additional discharge of extinguishing agent to maintain concentration for a longer
period of time.
Ou t p u t 2 De l a y
T I ME = 0 0 mi n . Press the ENTER button and the display will show:
Ou t p u t 2 De l a y
T I ME = 0 0 mi n . ? To change the time, press the UP or DOWN buttons until the required time is
displayed
To save the settings, slide the write enable switch gently to the right.
The extinguishing release time will now be set to the chosen value.
Note: This option is available only on modules fitted with firmware version 1.59 or higher.
To change the extinguishant release time, switch on the enable controls keyswitch and slide the write enable
switch on the module to be configured gently to the left. Press the ENTER button on the extinguishing module then
press the UP button until the display shows:
E X T I NG. RE L E A S E
T I ME = 6 0 s e c . Press the ENTER button and the display will show:
To save the settings, slide the write enable switch gently to the right.
The extinguishing release time will now be set to the chosen value.
To change the operation of the second stage sounders, switch on the enable controls keyswitch and slide the write
enable switch on the module to be configured gently to the left. Press the ENTER button on the extinguishing
module then press the UP button until the display shows:
P UL S E D
A CT I V . A L A RMS Press the ENTER button and the display will show:
S T E A DY
A CT I V . A L A RMS ? To change to steady second stage alarms, press the ENTER button.
To save the settings, slide the write enable switch gently to the right.
The second stage alarm output will now be steady when the module is activated.
Note: Setting the option for ST EADY ACT I V. AL ARMS is not compliant with EN12094-1
To change the operation of the released indication, switch on the enable controls keyswitch and slide the write
enable switch on the module to be configured gently to the right. Press the ENTER button on the extinguishing
module then press the UP button until the display shows:
RE L E A S E D I ND ON
RE L E A S E D I NP UT Press the ENTER button and the display will show:
To configure the module to have no delay when a manual release is operated, switch on the enable controls
keyswitch and slide the write enable switch on the module to be configured gently to the left. Press the ENTER
button on the extinguishing module then press the UP button until the display shows:
DE L A Y ON
MA NUA L REL E A S E Press the ENTER button and the display will show:
NO DE L A Y ON
MA NUA L REL E A S E ? To change to this, press the ENTER button.
To save the settings, slide the write enable switch gently to the right.
Operation of a manual release will now operate the extinguishant outputs immediately with no delay.
To disable the release timer, switch on the enable controls keyswitch and slide the write enable switch on the
module to be configured gently to the left. Press the ENTER button on the extinguishing module then press the
DOWN button until the display shows:
Man-1112 Sigma XT+_26 Page 32 of 52
RE L E A S E T I ME R
E NA B L E D Press the ENTER button and the display will show:
To configure the module such that Aux24V output is removed for a few seconds when the system is reset, switch
on the enable controls keyswitch and slide the write enable switch on the module to be configured gently to the
left. Press the ENTER button on the extinguishing module then press the DOWN button until the display shows:
R0 V NOT RE MOV E D
ON S Y S T E M RE S E T Press the ENTER button and the display will show:
R0 V RE MOVE D
ON S Y S T E M RE S E T ? To select this option, press the enter button.
To save the settings, slide the write enable switch gently to the right.
With the release module configured to remove the R0V output on system reset, the Aux 24V output will be removed
for a few seconds when the reset button is pressed.
To disable the earth fault monitoring, switch on the enable controls keyswitch and slide the write enable switch on
the module to be configured gently to the left. Press the ENTER button on the extinguishing module then press the
DOWN button until the display shows:
E A RT H F A UL T
E NA B L E D Press the ENTER button and the display will show:
E A RT H F A UL T
DI S A B L E D ? To select this option, press the enter button.
To save the settings, slide the write enable switch gently to the right.
The earth fault monitoring facility on the module will now be disabled, the Aux 24V output will be removed for a few
seconds when the reset button is pressed.
To disable the fault output relay, switch on the enable controls keyswitch and slide the write enable switch on the
module to be configured gently to the left. Press the ENTER button on the extinguishing module then press the
DOWN button until the display shows:
F A UL T o u t p u t
E NA B L E D Press the ENTER button and the display will show:
F A UL T o u t p u t
d i s ABL ED ? To select this option, press the enter button.
To save the settings, slide the write enable switch gently to the right.
The fault output relay on the module will now be disabled.
Note: Disabling the fault output does not comply with the requirements of EN54-2.
To invert the low pressure switch input, switch on the enable controls keyswitch and slide the write enable switch
on the module to be configured gently to the left. Press the ENTER button on the extinguishing module then press
the DOWN button until the display shows:
L OW P RE S S. I / P
MODE = NORMA L Press the ENTER button and the display will show:
L OW P RE S S. I / P
MODE = I NV E RT E D ? To select this option, press the enter button.
To save the settings, slide the write enable switch gently to the right.
The low pressure switch input will now require a normally closed contact via a 470R trigger resistor and 6K8 end of
line resistor for correct supervision.
Note: If the Low pressure input is configured as INVERTED in the menu option, an error will display
EXTING.PRESS.FAULT if the switch is not configured correctly.
The INVERTED input is looking for the 470 ohm trigger resistor to be removed on activation.
To invert the Released pressure switch input, switch on the enable controls keyswitch and slide the write enable
switch on the module to be configured gently to the left. Press the ENTER button on the extinguishing module then
press the DOWN button until the display shows:
Re l e a s e d I n p u t
MODE = NORMA L Press the ENTER button and the display will show:
Re l e a s e d I NP UT
MODE = I NV E RT E D ? To select this option, press the enter button.
To save the settings, slide the write enable switch gently to the right.
The Released pressure switch input will now require a normally closed contact via a 470R trigger resistor and 6K8
end of line resistor for correct supervision.
Note: When Released pressure input is configured as INVERTED in the menu option, the released condition will be
established and indicated.
The INVERTED input is looking for the 470 ohm trigger resistor to be removed on activation.
ex t i ng. o/ p 2
l ev el = 206 Press the ENTER button and the display will show:
ex t i ng. o/ p 2 The XXX here will be the actual monitoring level read by the module.
l evel = xxx ? To save this setting press the ENTER button.
To set the monitoring level for extinguishant output 1, press the DOWN button. The display will show:
ext i ng. o/ p 1
Man-1112 Sigma XT+_26 Page 34 of 52
l evel = 206 Press the ENTER button and the display will show:
ex t i ng. o/ p 1 The XXX here will be the actual monitoring level read by the module.
l evel = xxx ? To save this setting press the ENTER button.
To save the settings, slide the write enable switch gently to the right.
The extinguishing output levels will now be set and any significant variation detected in the monitoring levels will be
announced as and EXTING. O/P fault.
Ma n u a l & Au t o
Any modules that are in Manual Only mode with have an additional, Manual only yellow LED lit and their display will
show:
MA NUA L MODE
The control panel has 3 access levels. Access level 1 is available at all times and allows operation the Alarm/Fault
warning buzzer silence and Lamp test buttons on the detection part of the panel only. Access level 2 is enabled after
operation of the front panel mounted Enable Controls keyswitch and Access level 3 allows configuration options to
be set on both the detection part of the panel and the extinguishing modules following operation of their respective
Write Enable switches at access level 2 (Enable Controls keyswitch operated).
When the ENABLE controls keyswitch is operated (Access level 2) the display on the detection part of the control
panel will show and the LCDs on the extinguishing modules will show:
Ac c e s s l e v e l 2 ►
E NT E R f o r Me n u
To remove test mode from a zone, press the Select button to reveal any zones that have a flashing dot and then
press the Enter button to take that zone out of test mode. Once all zones have been taken out of test mode, the
yellow, Test LED will go off.
To select further zones to disable, press the Select button and then the Enter button so that the flashing dot appears
next to the selected display e.g.
To remove disablements, press the Select button to reveal any zones that have a flashing dot next to the displayed
zone number and then press the Enter button. Once all zones have been enabled, the yellow, Disabled LED will go
off.
To enable the sounder outputs, press the Mode button while at Access level 2 (Enable keyswitch operated) and scroll
with the mode button until is displayed. Press the Enter button. The display will change to and the Sounder
fault and Disablement LEDs will go off if there are no other disablements active on the panel.
To switch off the delay, press the Mode button while at Access level 2 (Enable keyswitch operated) and scroll with
the mode button until is displayed. Press the Enter button. The display will change to and the Alarm
delay and Disablement LEDs will go off if there are no other disablements active on the panel.
Ac c e s s l e v e l 2 ►
E NT E R f o r Me n u
DI S A B L E
E X T I NG. RE L E A S E ? Press the Enter button to select this function. The display will show:
E NA B L E
E X T I NG. RE L E A S E ? The yellow disabled LED on the module that has been disabled
will be lit.
Turn the Enable keyswitch off to leave the disablement active. To re-enable the extinguishant outputs repeat the
procedure above.
DI S A B L E
ma n u a l REL E A S E ? Press the Enter button to select this function. The display will show:
enabl e
ma n u a l REL E A S E ? The yellow disabled LED on the module that has been disabled
will be lit.
Turn the Enable keyswitch off to leave the disablement active. To re-enable the manual release facility repeat the
procedure above.
DI S A B L E
s t age 1 out put ? Press the Enter button to select this function. The display will show:
E NA B L E
S T A GE 1 OUT P UT ? The yellow disabled LED on the module that has been disabled
will be lit.
DI S A B L E
s t age 2 out put ? Press the Enter button to select this function. The display will show:
E NA B L E
S T A GE 2 OUT P UT ? The yellow disabled LED on the module that has been disabled
will be lit.
Turn the Enable keyswitch off to leave the disablement active. To re-enable the Stage 2 relay output repeat the
procedure above.
DI S A B L E
r el eased out put ? Press the Enter button to select this function. The display will show:
E NA B L E
r e l e a s e d OUT P UT ? The yellow disabled LED on the module that has been disabled
will be lit.
Turn the Enable keyswitch off to leave the disablement active. To re-enable the Released relay output repeat the
procedure above.
DI S A B L E
ex t r ac t out put ? Press the Enter button to select this function. The display will show:
E NA B L E
ext r act OUT P UT ? The yellow disabled LED on the module that has been disabled
will be lit.
Turn the Enable keyswitch off to leave the disablement active. To re-enable the Extract relay output repeat the
procedure above.
T URN ON
E X T RA CT OUT P UT Press the Enter button to select this function. The display will show:
T URN OF F
E X T r a CT OUT P UT ? The yellow disabled LED on the module that has been disabled
will be lit.
Turn the Enable keyswitch off to leave the Extract output active. To turn off the Extract output, repeat the procedure
above. Note: the extract output does not turn off when the module is reset.
To turn on the Reserve Solenoid output, press the UP button on the module while at access level 2 until the
display shows:
S E L E CT RES E RV E
E X T I NG. OUT P UT Press the Enter button to select this function. The display will
show:
S E L E CT MAI N
E X T I NG. OUT P UT ? The yellow Reserve Cylinders LED indicator on the module
will be lit.
Turn the Enable keyswitch off to leave the Reserve solenoid output active. To revert to the Main solenoid output,
repeat the procedure above.
pr eac t i v at ed ►
Pressing the Silence alarm button on the detection section will turn off the sounder outputs on the detection section
and the first stage alarm outputs on the extinguishant module.
a) The second stage alarm output will operate. (Sounder circuit S3)
b) The 2nd stage contact will operate.
c) The Activated indicator will operate
d) The display will indicate A c t i v a t e d and show the time remaining until release in seconds.
e) The extinguishant output will operate after the configured delay time and for the configured duration.
f) The display will show A c t i v a t e d Di s c h a r g i n g for the duration of the release time.
When detection zones have activated and the activated condition is reached (i.e. the Activated indicator is lit) it shall
not be possible to reset the extinguishant section of the panel until the Reset Inhibit timer has elapsed.
16.7 Reset
To reset the panel, insert the Enable key, turn to the right then press the Reset button.
The extinguishant section will reset only after the Reset Inhibit timer has expired once the activated condition has
been established.
s t a g e 1 a l a r ms
f aul t
or
s t a g e 2 a l a r ms
f aul t
If the extinguishant module is in the Activated condition and the pre-release timer is running then the extinguishant
release sequence will be halted and the pulsing, 2nd stage sounders shall change to 1 second on, 2 seconds off.
Release of the Hold input will re-start the pre-release timer from maximum.
18.1.9 S1 fault
Indicates a short or open circuit on sounder outputs. Remove wiring and refit end of line resistors. Check sounder
circuit wiring.
18.1.10 S2 fault
Indicates a short or open circuit on sounder outputs. Remove wiring and refit end of line resistors. Check sounder
circuit wiring.
The table below shows the power supply rating and recommended battery capacity for each model in the Sigma XT+
range.
Model Description Power supply rating Batteries recommended
for 24 hour standby
K21021M3 Two zone single area 3A 7Ah
K21041M3 Four zone single area 3A 7Ah
K21042M3 Four zone two area 3A 7Ah
K21081M3 Eight zone single area 3A 7Ah
K21082M3 Eight zone two area 3A 7Ah
K21083M3 Eight zone three area 5.25A 12Ah
K21084M3 Eight zone four area 5.25A 12Ah
The maximum loading on the power supply must be carefully considered when connecting externally powered
equipment such as sounders and solenoids.
Exceeding the maximum power supply rating may cause a fuse or other protective device to operate and
render the equipment inoperative until the fuse is replaced or protective devices are reset.
The tables below can be used to calculate the loading for all models by adding the loads in the second column.
K21021M3 2 zone single area Current in milliamps
Detection section max alarm load 100
Extinguishing module max alarm load 105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module total sounder load
Extinguishant module extinguishant output load
Extinguishant module Aux 24V supply
The output voltage of the power supply is between 18 and 30V depending on mains and battery condition and the
total current rating is either 3A or 5.25A depending on the model (see tables above).
The incoming mains cable should be routed well away from other lower voltage wiring by a distance of at least
50mm.
Mains wiring should include an earth conductor, which is securely bonded to the building earth and should enter the
enclosure as close as possible to the mains terminal block. Mains wires should be kept very short inside the enclosure
and secured together close to the mains terminal block with a cable tie.
The maximum capacity batteries that should be fitted are 7Ah for KXXXXM3 models and 17Ah for KXXXXM4 models.
The maximum current drawn from the batteries when the main power source is disconnected is 3 Amps for KXXXXM3
models and 5.25 Amps for KXXXXM4 models.
TAPE
BATTERY
Battery leads are supplied wired to the power supply along with a link to connect the two batteries together.
It is most important that the polarity of the batteries is carefully observed when connecting. Wrongly
connected batteries could cause damage to the control panel.
21. Maintenance
SIGMA XT+ control panels do not require any specific maintenance but should the control panel become dirty it can
be wiped over with a barely damp cloth. Detergents or solvents should not be used to clean the panel and care must
be taken that water does not enter the enclosure.
The control panel contains sealed lead acid batteries to provide standby power in the event of mains failure.
These batteries have a life expectancy of around 4 years. It is recommended that these batteries be tested in
accordance with the battery manufacturer’s recommendations annually to determine their suitability for continued
standby applications.
Testing of the extinguishant system should only be carried out by trained personnel and must be done with
appropriate isolation measures in place to ensure that accidental discharge of the extinguishant agent is avoided.
Should the control panel become faulty the complete electronic assemblies and front plates can be replaced.
To do this, any configured options should be noted then both mains and battery power should be removed before
the work is started.
The field wiring should be carefully labelled and removed from the terminals. The power terminal block can be
unplugged from the PCB by pulling it towards you.
The faulty PCB plate assembly can now be taken out of the panel by removing the 2 screws.
Fitting the new PCB is the reverse of the procedure for removing the board.
24.2 When power is applied, if all connections are correct, only the green Power On indicators should be lit.
If any fault indicators are lit the wiring to the appropriate input or output should be checked an all faults
cleared before proceeding.
24.3 Once the panel is fault free, it can be configured with the desired options as
described in section 15 .
24.4 Once the panel has been configured the system should be thoroughly tested to ensure that the control panels
responds as expected and required.
24.5 After satisfactory testing, any final connections should be made (such as to the
extinguishant release actuator).
24.6 A record of the configuration options that have been set should be recorded in the tables below and this
manual provided as part of the documentation recommended by BS5839:Part 1:2002 section 40.2 b).
Detection section
CODE FUNCTION TICK IF SET
00 SOUNDER DELAY TIME = 30 SECONDS
01 SOUNDER DELAY TIME = 1 MINUTE
02 SOUNDER DELAY TIME = 2 MINUTES
03 SOUNDER DELAY TIME = 3 MINUTES
04 SOUNDER DELAY TIME = 4 MINUTES
05 SOUNDER DELAY TIME = 5 MINUTES
06 SOUNDER DELAY TIME = 6 MINUTES
07 SOUNDER DELAY TIME = 7 MINUTES
08 SOUNDER DELAY TIME = 8 MINUTES
09 SOUNDER DELAY TIME = 9 MINUTES
10 COMMON ALARM MODE (default)
11 TWO-STAGE ALARM MODE
12 ZONED ALARM MODE
51 COINCIDENCE ZONE 1
Man-1112 Sigma XT+_26 Page 47 of 52
52 COINCIDENCE ZONE 2
53 COINCIDENCE ZONE 3
54 COINCIDENCE ZONE 4
55 COINCIDENCE ZONE 5
56 COINCIDENCE ZONE 6
57 COINCIDENCE ZONE 7
58 COINCIDENCE ZONE 8
Extinguishant module 2
Extinguishant module 3
Man-1112 Sigma XT+_26 Page 49 of 52
CONFIGURATION OPTION WRITE SETTING
E x t i n g u i s h a n t o u t p u t mo d e =
A CT I V A T I ON MODE =
Us e r O/ p Mo d e =
F I RS T A CT I V . Z ONE =
L A S T A CT V. Z ONE =
RE S E T I NHI B I T T I ME =
P RE - RE L . DE L A Y T I ME =
E X T I NG. RE L E A S E T I ME =
P UL S E D A CT I V . AL A RMS ?
S T E A DY A CT I V . AL A RMS ?
RE L E A S E D I ND. ON RE L E A S E D I NP UT ?
RE L E A S E D I ND. ON E X T I NG RE L E A S E ?
DE L A Y ON MA NUA L RE L E A S E ?
NO DE L A Y ON MA NUA L RE L E A SE ?
P RE - RE L DE L A Y RES E T E NA B L E D ?
P RE - RE L DE L A Y RES E T DI S A BL E D ?
RE L E A S E T I ME R ENA B L E D ?
RE L E A S E T I ME R DI S A B L E D ?
R0 V NOT RE MOV E D ON S Y S T E M RE S E T ?
R0 V RE MOVE D ON SY S T E M RE SE T ?
E A RT H F A UL T E NABL E D ?
E A RHT F A UL T DI ASL A B L E D ?
F A UL T OUT P UT E NAB L E D ?
F A UL T OUT P UT DI SA B L E D ?
L OW P RE S S. I / P NORMA L ?
L OW P RE S S. I / P I NV E RT E D ?
E X T I NG. O/ P 1 L EV E L =
E X T I NG O/ P 2 L EVE L =
Extinguishant module 4