Sigma XT+

Extinguishant Control Panel

Operation and Maintenance Manual


Man-1112 Issue 26 Oct 2019
Index

1. Introduction ......................................................................................................... 5
2. Safety and mounting ............................................................................................ 6
2.1 Safety ................................................................................................................. 6
2.2 Mounting ............................................................................................................. 7
3. Technical specification ......................................................................................... 8
4. Control panel fascia’s ......................................................................................... 12
4.1 Removing the fire detection equipment chassis ...................................................... 13
5. Connecting to the circuit boards ......................................................................... 14
6. Detection zone wiring ......................................................................................... 17
7. Sounder circuit wiring (alarm devices as required by EN12094-1) ..................... 17
8. Using intrinsically safe barriers .......................................................................... 18
9. Connection to monitored inputs ......................................................................... 19
10. Connection to extinguishant output.................................................................. 19
10.1 Solenoid wiring ................................................................................................. 19
10.2 Igniting actuator wiring ..................................................................................... 20
10.3 Setting up extinguishant monitoring circuit .......................................................... 20
11. Connection to remote control terminals ........................................................... 21
12. Aux 24V DC supply outputs (extinguishant modules only) ............................... 21
13. Connection to relay contacts ............................................................................ 22
13.1 Common Fault relay (on detection part of control panel) ........................................ 22
13.2 Fault relay (on extinguishing part of control panel) ............................................... 22
13.2 Local fire relay (on detection part of control panel) ............................................... 22
13.3 Fire relay (on detection part of control panel) ....................................................... 22
13.4 1st stage alarm relay (on extinguishing modules) .................................................. 22
13.5 2nd stage alarm relay (on extinguishing modules) ................................................ 22
13.6 Released relay (on extinguishing modules) .......................................................... 22
13.7 Aborted relay (on extinguishing modules) ............................................................ 22
13.8 Extract relay (on extinguishing modules) ............................................................. 22
14. Connection and configuration of status units and ancillary boards ................... 23
14.1 Adding new status units/ancillary boards ............................................................. 24
14.2 Removing status units or ancillary boards ............................................................ 24
15. Configuring the panel ....................................................................................... 27
15.1 Detection part .................................................................................................. 27
15.2 Extinguishing modules ....................................................................................... 29
15.2.1 Language selection .....................................................................................................29
15.2.2 Extinguishant output mode..........................................................................................29
15.2.3 Configuring the activation mode...................................................................................30
15.2.4 Configuring Stage 1 /Hold Output ................................................................................30
15.2.5 Configuring the activation zones ..................................................................................30
15.2.6 Reset inhibit time .......................................................................................................31
15.2.7 Pre-release delay time ................................................................................................31
15.2.8 Output 2 delay...........................................................................................................31
15.2.9 Extinguishant release time ..........................................................................................31
15.2.10 Second stage alarm pulsing/continuous (alarm devices as required by EN12094-1) ..........32
15.2.11 Released indication ...................................................................................................32
15.2.12 Delay on manual release ...........................................................................................32
15.2.13 Release timer (infinite extinguishant duration) .............................................................32
15.2.14 R0V not removed on reset .........................................................................................33
15.2.15 Disable earth fault monitoring ....................................................................................33
15.2.16 Disable fault output ..................................................................................................33
15.2.17 Invert low pressure switch input.................................................................................34
15.2.18 Invert Released Pressure switch input .........................................................................34
Man-1112 Sigma XT+_26 Page 2 of 52
15.2.19Extinguishant output monitoring levels.........................................................................34
16. Panel operation – Access levels 1 and 2 ........................................................... 35
16.1 Normal condition .............................................................................................. 35
16.2 Detection section – Access level 2. ...................................................................... 35
16.2.1 Test mode .................................................................................................................35
16.2.2 Disable zones ............................................................................................................35
16.2.3 Disable sounder outputs..............................................................................................35
16.2.4 Activate delays ..........................................................................................................36
16.3 Extinguishant modules – Access level 2 ...........................................................................36
16.3.1 Disable extinguishant release outputs. ..........................................................................36
16.3.2 Disable Manual release ...............................................................................................36
16.3.3 Disable Stage 1 output ...............................................................................................36
16.3.4 Disable Stage 2 output ...............................................................................................37
16.3.5 Disable Released output ..............................................................................................37
16.3.6 Disable Extract output ................................................................................................37
16.3.7 Turn on Extract output................................................................................................37
16.3.8 Select Reserve Solenoid Output (Configuration Option) ...................................................37
16.4 Single zone Fire condition ................................................................................. 38
16.5 Double zone Fire condition ................................................................................. 38
16.6 Silence/sound alarms ........................................................................................ 38
16.7 Reset .............................................................................................................. 38
16.8 Detection Zone fault.......................................................................................... 38
16.9 Sounder fault ................................................................................................... 38
16.10 Power fault ..................................................................................................... 38
16.11 System fault – Detection section ....................................................................... 38
16.12 System fault – Extinguishant modules ............................................................... 39
16.13 General fault – Detection section ...................................................................... 39
16.14 Lamp test ...................................................................................................... 39
16.15 Hold condition ................................................................................................ 39
16.16 Released condition .......................................................................................... 39
16.17 Low pressure switch ........................................................................................ 39
16.18 Manual only mode ........................................................................................... 39
16.19 Manual Release............................................................................................... 39
16.19 Abort input ..................................................................................................... 39
17. Internal Controls .............................................................................................. 40
17.1 Detection part .................................................................................................. 40
17.1.1 Watchdog reset..........................................................................................................40
17.1.2 Processor reset ..........................................................................................................40
17.1.3 Write enable switch ....................................................................................................40
17.2 Extinguishant modules ...................................................................................... 40
17.2.1 Watchdog reset..........................................................................................................40
17.2.2 Processor reset ..........................................................................................................40
17.2.3 Terminate extinguishant .............................................................................................40
17.2.4 Write enable switch ....................................................................................................40
17.2.5 Address switch...........................................................................................................41
18. Internal indications .......................................................................................... 41
18.1 Detection part .................................................................................................. 41
18.1.1 Mains fail ..................................................................................................................41
18.1.2 Batt fail.....................................................................................................................41
18.1.3 CPU fault...................................................................................................................41
18.1.4 Aux 24V fault ............................................................................................................41
18.1.5 Batt low ....................................................................................................................41
18.1.6 Comms fault ..............................................................................................................42
18.1.7 Earth fault .................................................................................................................42
18.1.8 Sys fuse fault ............................................................................................................42
18.1.9 S1 fault.....................................................................................................................42
18.1.10 S2 fault ...................................................................................................................42
18.2 Extinguishant modules ...................................................................................... 42
18.2.1 Watchdog..................................................................................................................42
18.2.2 System fuse ..............................................................................................................42

Man-1112 Sigma XT+_26 Page 3 of 52


18.2.3 Man. Release .............................................................................................................42
19. Power supply .................................................................................................... 43
21. Maintenance ..................................................................................................... 45
23. CE Mark ............................................................................................................ 46
24. Commissioning instructions.............................................................................. 47

Man-1112 Sigma XT+_26 Page 4 of 52


1. Introduction

The SIGMA XT+ range of control panels are designed in accordance with European standards EN54-2 and EN54-4 Fire
Detection and Fire Alarm systems - Control and Indicating Equipment and EN12094-1 Fixed firefighting systems -
Components for gas extinguishing systems - Part 1: Requirements and test methods for electrical automatic control
and delay devices.
The control equipment is a combined fire alarm control panel and extinguishing system with up to eight detection
zones, and up to four extinguishant flooding areas.
Control panels have an integral, mains powered battery charger and power supply designed in accordance with the
requirements of EN54-4.
In addition to the requirements of EN54-2 the control panel has the following facilities:

Test condition to allow the automatic resetting of zones in alarm for testing purposes. EN54-2 Section 10: option with
requirements.
Delay of the actioning of fire alarm devices (sounders) so that an alarm may be verified before a premises is evacuated.
EN54-2 Section 7.11: (option with requirements).
Fire alarm devices to enable an audible warning to be sounded throughout premises upon the detection of a fire
condition or the operation of a manual call point. EN54-2 Section 7.8: (option with requirements).

In addition to the requirements of EN54-2, all control panels have voltage free relay contacts for fire and local fire
which operate upon a fire condition. These are to be used for local control and signalling.
The following compulsory functions required by EN12094-1 are included:
4.3.2a Reception and processing of at least one input triggering signal from an f.d.a.s and an input triggering signal
from manual triggering device(s) connected directly to the e.c.d.
4.3.2b Transmission of the extinguishing signal upon receipt of input triggering signal(s).
4.3.2c Activation of alarm devices upon receipt of input triggering signal(s).
4.2.2d Unambiguous indication of each condition.
4.2.3e Transmission of the information of the incorrect ststus of components and of the fault warning condition.
4.3.2f Transmission of the information of the released condition.

In addition to the compulsory requirements of EN12094-1 the control panel has the following facilities:
Delay of extinguishing signal of up to 60 seconds. EN12094-1 Section 4.17: (option with requirements).
Signal representing the flow of extinguishing agent to indicate the released condition. EN12094-1 Section 4.18: (option
with requirements).
Monitoring of the status of components by way of a low pressure switch input. EN12094-1 Section 4.19 : (option with
requirements).
Emergency hold device to enable the extinguishant delay time to be extended. EN12094-1 Section 4.20: (option with
requirements).
Control of flooding time to deactivate the releasing output after a set period of time. EN12094-1 Section 4.21: option
with requirements.
Manual only mode to disable the release of extinguishant via automatic detection devices. EN12094-1 Section 4.23:
(option with requirements).
Triggering of equipment outside the system by way of first and second stage contacts, extract fan output etc. EN12094-
1 Section 4.26: (option with requirements).
Activation of alarm devices with different signals to indicate pre- discharge and released warnings using different
sounds. EN12094-1 Section 4.30: (option with requirements).
Emergency Abort device to inhibit the extinguishing signal until the emergency abort device has been de-activated and
the panel has been reset. EN12094-1 Section 4.27: (option with requirements).
Extinguishing signals to spare cylinders. EN12094-1 section 4.25 (option with requirements)

Man-1112 Sigma XT+_26 Page 5 of 52


2. Safety and mounting
2.1 Safety
Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work act 1974 to ensure
as reasonably as is practical that the article will be safe and without risk to health when properly used.
An article is not regarded as properly used if it is used ‘without regard to any relevant information or advice’ relating
to its use made available by the supplier.
This product should be installed, commissioned and maintained by trained service personnel in accordance with the
following:

(i) IEE regulations for electrical equipment in buildings


(ii) Codes of practice
(iii) Statutory requirements
(iv) Any instructions specifically advised by the manufacturer

According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that
you make any appropriate information about this product available to anyone concerned with its use.
This equipment is designed to operate from 230V 50Hz mains supplies and is of class 1 construction. As such it must
be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double
pole disconnect device meeting the requirements of EN60950/IEC950 which disconnects live and neutral simultaneously
shall be incorporated in the fixed wiring.
Switch disconnect devices such as MK Sentry 63A or similar are suitable for this.
Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the
protective earth will render the equipment unsafe.
This control panel is environmental class A and is designed for indoor use only at temperatures between -50C (+/- 3)
and +400C (+/- 2) and with a maximum relative humidity of 95%.
The IP rating for the enclosure is IP30.
Operation outside of these limits may render the equipment unsafe.

Man-1112 Sigma XT+_26 Page 6 of 52


2.2 Mounting
The control panel should be mounted on a dry, flat surface, at eye height to the displays and in a level position such
that the enclosure is not distorted.
Screws or bolts of a minimum of 5mm diameter must be used to mount the enclosure in all four mounting positions.
It should be positioned in an accessible place as agreed with the end user.
Suitable fixings should be used at all fixing points such that the control panel is securely mounted and is not liable to
move once fixed.
The control panel should not be mounted in another enclosure or near sources of excessive heat.
Cables should be connected using suitable cable glands fitted to the knockouts provided. If additional cable entry points
are required, all swarf and debris caused by drilling of additional cable entries must be cleared before power is applied
to the panel.
Cables should not be installed in the bottom of the enclosure. This space must be kept free for batteries.

SIDE VIEW FRONT VIEW

5mm DIAMETER
SCREWS

FIX TO FLAT SURFACE USING


SUITABLE WALL PLUGS

Man-1112 Sigma XT+_26 Page 7 of 52


3. Technical specification
Table 1 - Electrical specifications
ITEM ELECTRICAL RATING COMMENT COMMUNICATION
PARAMETERS
Mains supply 230V AC, 50Hz +10% - 15% (100 Watts maximum) Standard European mains
connection
Mains supply fuse (K21021, 1.6 Amp ( F1.6A L250V) Replace only with similar type
K21041, K21042, K21081,
K21082)
Mains supply fuse (K21083, F3A 250V TD 20mm Replace only with similar type
K21084)
Power supply rating (K21021, 3 Amps when battery charging is not required See section 19 for maximum loading for
K21041, K21042, K21081, each model
K21082)
Power supply rating (K21083, 5.25 Amps when battery charging is not required See section 19 for maximum loading for
K21084) each model
Maximum ripple voltage 1 Volt
Power supply output voltage 19 to 30V DC
Battery type (Yuasa NP) 2 x 12 Volt sealed lead acid in series
Battery charge voltage 27.6VDC nominal (temperature compensated) See chart below Modulated DC
Battery charge current 0.7A maximum - (K21021, K21041, K21042, K21081, K21082) Modulated DC
1,25A maximum - (K21083, K21084)
Low Battery Voltage 21V
Imax a 0.85A - K21021, K21041, K21042, K21081, K21082
4A - K21083, K21084
Imax b 3A - K21021, K21041, K21042, K21081, K21082
5A - K21083, K21084
Ri max 1.35R - K21021, K21041, K21042, K21081, K21082
1R - K21083, K21084
Battery fuse 20mm, 3.15A glass (K21021, K21041, K21042, K21081, Replace only with the same type
K21082) models only.
Current draw in mains fail K21021- 119 milliamps quiescent – 207 milliamps full alarm Full alarm current consumption figure is
condition K21041 – 130 milliamps quiescent – 317 milliamps full alarm with all zones in alarm and all modules
K21042 – 185 milliamps quiescent – 424 milliamps full alarm activated.
K21081 – 150 milliamps quiescent – 657 milliamps full alarm
K21082 – 200 milliamps quiescent – 764 milliamps full alarm
K21083 – 255 milliamps quiescent – 871 milliamps full alarm
K21084 – 300 milliamps quiescent – 978 milliamps full alarm
Maximum current draw from 3 Amps (K21021, K21041, K21042, K21081, K21082) With main power source disconnected
batteries 7 Amps (K21083, K21084)
Aux 24V output (Exting modules) Fused at 500mA with electronic fuse – 1 per extinguishant area 200 milliamp maximum continuous load 16 to 30 V DC
(Min 16V @ Final Voltage)
Aux 24V output (detection Fused at 500mA with electronic fuse 200 milliamp maximum continuous load 16 to 30V DC
module) (Min 16V @ Final Voltage)
Final Voltage (Cut off Voltage) 19V ±1V
1st and 2nd stage Sounder outputs 18 to 30V DC Fused at 1A with electronic fuse 1.0 Amp total load over all circuits Voltage reversing DC
Fault relay contact rating 5 to 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Volt free changeover contact
Fire relay contact rating 5 to 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Volt free changeover contact

Man-1112 Sigma XT+_26 Page 8 of 52


Local fire relay contact rating 5 to 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Volt free changeover contact
First stage contact rating 5 to 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Volt free changeover contact
Second stage contact rating 5 to 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Volt free changeover contact
Extract contact rating 5 to 30VDC 1A Amp maximum for each Maximum ratings not to be exceeded Volt free changeover contact
Zone quiescent current 0mA minimum, 2mA maximum See tables 2 and 3 for detector types
Terminal capacity 0.5mm2 to 2.5mm2 solid or stranded wire
Number of detectors per zone Dependent on type See table 2
Number of sounders per circuit Dependent on type and current consumption See table 4 for sounder types
Detection circuit end of line 6K8 +/- 5% ½ Watt resistor Supplied in terminals
Monitored input end of line 6K8 +/- 5% ½ Watt resistor Supplied in terminals
Sounder circuit end of line 10K +/- 5% ¼ Watt resistor Supplied in terminals
Extinguishant output end of line 1N4004 Diode Supplied in terminals
No. of detection circuits Two to eight. 21 VDC Dependent on model
No. of sounder circuits Dependent on model 18 to 30V DC 2 x on detection section –1st stage and 2nd stage sounders are outputs
1 x 2nd stage per exting area. to alarm devices as required by
EN12094-1
Extinguishant release output 18 to 30V DC. Fused at 1 Amp 1 Amp maximum load –for 5 minutes Voltage reversing DC with
3 Amps for 20 milliseconds calibration facility
Extinguishant release delay Adjustable 0 to 60 seconds (+/- 10%) 5 second steps
Extinguishant release duration Adjustable 60 to 300 seconds 5 second steps
SIL, AL, FLT, RST inputs Switched -ve, min resistance 0 ohms, max resistance 100 Only to be used with Aux ROV terminal Switched DC
Ohms
Zone normal threshold (Allowable 8K ohm to 1K ohm Use 6K8 end of line resistor
EOL)
Detector alarm threshold 999 ohms to 400 ohms Nominal trigger resistance 470 ohms
Call point alarm threshold 399 ohms to 100 ohms Nominal trigger resistance 270 ohms
Short circuit threshold 99 ohms to 0 ohms
Head removal condition 15.5 to 17.5 volts 2-wire detector base or schottky diode
base
Cabling FP200 or equivalent (maximum capacitance 1uF max Metal cable glands must be used
inductance 1 mH
Monitored inputs normal threshold 10K ohm to 2K ohm
(Allowable EOL)
Monitored inputs alarm threshold 2K ohms to 150 ohms +/- 5%
Monitored inputs Short circuit 140 ohms to 0 ohms +/- 5%
threshold
Status unit/Ancillary board Two wire RS485 connection (EIA-485 specification) Maximum of 7 units per area- RS485 (EIA-485 specification)
connection data cable.
Compatible status units - K911000M8,
K911000F8, K911100M8, K911100F8,
K911110M8, K911110F8, W911000W8,
W911100W8, W911110W8
Status unit power output 18 to 30V DC, Fused at 500mA with electronic fuse 250 milliamp maximum load Max 3 per module – More status
units must be supplied with
external power supply

Man-1112 Sigma XT+_26 Page 9 of 52


Table 2 - Compatible detectors
Model Type Manufacturer Maximum Number per zone
SLR-E/SLR-E3 OPTICAL Hochiki 32
SIJ-E/ IONISATION Hochiki 32
DCD-1E/DCD-AE3 HEAT Hochiki 32
DCD-2E HEAT Hochiki 32
DCD-1RE/DCD-CE3 HEAT Hochiki 32
DFG-60E HEAT Hochiki 32
DFJ-60E/DFJAE3 HEAT Hochiki 32
DFJ90-E/DFJCE3 HEAT Hochiki 32
SPB-ET BEAM Hochiki 8
SRA-ET BEAM Hochiki 5

55000-200/210 - SERIES 60 IONISATION Apollo 32


55000-300 - SERIES 60 OPTICAL Apollo 32
55000-100 - SERIES 60 HEAT Apollo 32
55000-101 - SERIES 60 HEAT Apollo 32
55000-102 - SERIES 60 HEAT Apollo 32
55000-103 - SERIES 60 HEAT Apollo 32
55000-104 - SERIES 60 HEAT Apollo 32

55000-215 -SERIES 65 IONISATION Apollo 32


55000-216 - SERIES 65 IONISATION Apollo 32
55000-217 - SERIES 65 IONISATION Apollo 32
55000-218 - SERIES 65 IONISATION Apollo 32
55000-219 - SERIES 65 IONISATION Apollo 32
55000-220 - SERIES 65 IONISATION Apollo 32
55000-315 - SERIES 65 OPTICAL Apollo 32
55000-316 - SERIES 65 OPTICAL Apollo 32
55000-317 - SERIES 65 OPTICAL Apollo 32
55000-120 - SERIES 65 HEAT Apollo 32
55000-121 - SERIES 65 HEAT Apollo 32
55000-122 - SERIES 65 HEAT Apollo 32

53541-151 - SERIES 30 IONISATION Apollo 32


53541-152 - SERIES 30 IONISATION Apollo 32
53551-101 - SERIES 30 OPTICAL Apollo 32
53531-221 - SERIES 30 HEAT Apollo 28
53531-211 - SERIES 30 HEAT Apollo 28
53531-212 - SERIES 30 HEAT Apollo 28
53531-213 - SERIES 30 HEAT Apollo 28
53531-214 - SERIES 30 HEAT Apollo 28

ORB-OP-12001-APO Optical Apollo 15


ORB-OH-13001-APO Multisensor Apollo 15
ORB-HT-11001-APO A1R Heat Apollo 15
ORB-HT-11002-APO A2S Heat Apollo 15
ORB-HT-11003-APO BR Heat Apollo 15
ORB-HT-11004-APO BS Heat Apollo 15
ORB-HT-11005-APO CR Heat Apollo 15
ORB-HT-11006-APO CS Heat Apollo 15

NID-58 IONISATION Nittan 32


2KC/2KD OPTICAL Nittan 32
2SA-LS/2SA-70T-LS HEAT Nittan 32
TCA-70-LS HEAT Nittan 32
NFD-18-2/NFD-18-5 FLAME Nittan 3
NID-48F IONISATION Nittan 32
NS-12-7 HEAT Nittan 32
NC-9C-70T HEAT Nittan 32

ECO1002 HEAT/PHOTO System Sensor 21


ECO1003 PHOTO System Sensor 26
ECO1005 HEAT System Sensor 22
ECO1005T HEAT System Sensor 22
Although the current consumption of many detection devices would allow more than 32 to be connected to a zone,
this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the
indication of a fire alarm from more than 32 fire detectors and/or call points as required by European standard
EN54-2. If an active end of line LCMU (K14060) is used fit a maximum of 20 detectors per zone.

Man-1112 Sigma XT+_26 Page 10 of 52


Table 3 - Compatible detector bases and call points
Model Type Manufacturer Comments
YBN-R/6 STANDARD WITH REMOTE LED Hochiki
YBO-R/4(IS) STANDARD WITH REMOTE LED (I.S.) Hochiki
YBN-R/6SK DIODE BASE Hochiki Must be used with
LCMU
YBO-R/6R STANDARD LATCHING RELAY Hochiki
YBO-R/6RN STANDARD NON-LATCHING RELAY Hochiki
YBO-R/6RS DIODE BASE WITH LATCHING RELAY Hochiki Must be used with
LCMU

ECO1000R STANDARD System Sensor


ECO1000BRSD DIODE BASE System Sensor Must be used with
LCMU

456821-200 STANDARD BASE Apollo


456821-201 DIODE BASE Apollo Must be used with
LCMU
ORB-MB-00001-APO Timesaver Base Apollo
ORB-DB-00003-APO Timesaver Diode Base Apollo
ORB-RB-10004-APO Timesaver Relay Base Apollo

MCP1 470 OHM CALL POINT KAC


CX 470 OHM CALL POINT Fulleon

NCP-T CALL POINT Nittan

ELECTRONICS FREE BASES ALL

Note: LCMU (Line Continuity Monitoring Device) part number K14060 allows call points mounted down line of
detectors that have been removed from diode bases to continue to operate.

Table 4 - Compatible sounders


Model Type Manufacturer Comments
BANSHEE ELECTRONIC VIMPEX
WAFER ELECTRONIC VIMPEX
FIRECRYER RANGE ELECTRONIC VOICE VIMPEX
KOBELL MOTORISED VIMPEX

ASKARI ELECTRONIC FULLEON


ROSHNI ELECTRONIC FULLEON
SQUASHNI ELECTRONIC FULLEON
SYMPHONI ELECTRONIC FULLEON
ELECTRONIC BELL ELECTRONIC FULLEON
CFB BELLS MOTORISED FULLEON
B6 AND B8 BELLS SOLENOID FULLEON

Table 5 - Compatible I.S. barriers


Model Type Manufacturer
MTL5061 DETECTION ZONE GALVANIC ISOLATOR MTL
MTL7778ac ALL SOUNDER CIRCUITS MTL

Note: Use galvanic isolator with Hochiki or Apollo detectors only

Man-1112 Sigma XT+_26 Page 11 of 52


4. Control panel fascia’s

This drawing shows the fascia’s of the models available in the Sigma XT+ range.

K21021M3 K21041M3 K21042M3 K21081M3

K21082M3

K21083M4 K21084M4

The fascia’s are divided into sections for the detection panel and extinguishant modules. A standard EN54-2 control
and indicating equipment section with up to eight zones is located in the top aperture of the panel fascia and
EN12094-1 extinguishant modules are fitted in the lower apertures.

Man-1112 Sigma XT+_26 Page 12 of 52


4.1 Removing the fire detection equipment chassis
Open the control panel lid using the two 801 lock keys.
Before the chassis can be removed it will be necessary to disconnect the power connector terminal block on the left
hand side of the PCB. This is fitted on pins and can be pulled towards you to remove it. Do not remove the wires
from the terminals.
The chassis is held in place by two screws. Undo the two screws and lift the chassis gently away from the box
towards you.
With the chassis removed, there is much more room inside the panel for making off and dressing cables.
When cabling work is complete, the chassis can be re-fitted with the two screws and the terminal block plugged
back onto the pins on the board.
The extinguishant module chassis should not be removed.

Man-1112 Sigma XT+_26 Page 13 of 52


5. Connecting to the circuit boards

All connections for field wiring are to rows of terminals along the top and bottom of the
circuit boards.
Shielded fire alarm cable such as FP200 and metal cable glands must be used for all connections to the panel.
The shield of the cable must be bonded securely to the enclosure earth via a metal cable gland.
The resistance of any core of any cable must not exceed 25 ohms. The shield of the cable must be bonded
securely to the enclosure via the metal gland.

Wiring should enter the enclosure at the top or back of the panel using the knockouts provided and be formed tidily
to the appropriate terminals ensuring that no cables are run close (minimum 50mm) to the surface of any of the
circuit boards.

Route mains cables away from all other cables and segregate by 50mm.
Terminals are capable of accepting wires of up to 2.5mm2.

Wiring must not go across the front of the circuit boards. If cable entries need to be in positions other than at the
knockouts provided, wiring must be fed behind and well away from the surface of the circuit board.
The space at the bottom of the enclosure is largely occupied by the standby batteries so this must be borne in mind
when considering cable entries.

Man-1112 Sigma XT+_26 Page 14 of 52


Detection panel terminals

Man-1112 Sigma XT+_26 Page 15 of 52


Extinguishant panel terminals

Man-1112 Sigma XT+_26 Page 16 of 52


6. Detection zone wiring

The detection zones provide a nominal 20V DC to power conventional detectors and call points as listed in the
compatibility tables 2 and 3.
The wiring is monitored for open and short circuit fault conditions by removing the 6K8 0.5W end of line monitoring
resistors that are supplied fitted to the control panels’ terminals and placing them across the last device that is wired
to the zone circuit.

Detection zone circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring
circuit to work correctly.

For systems that are required to comply with BS5839 Part1:2002 detector removal requirements, either detector
bases fitted with a Schottky diode should be used and the end of line resistor replaced with an LCMU active end of
line monitoring device or zener clamping bases such as Hochiki PA6 or Apollo Savwire used.

CALL
DETECTOR
POINT

DETECTION + + IN + OUT 6K8 end of

-
ZONE
TERMINALS line resistor

- IN - OUT

See manufacturers See manufacturers


details for detailed details for detailed
connection information connection information

7. Sounder circuit wiring (alarm devices as required by EN12094-1)


All sounders must be of the polarised type. If non-polarised sounders are used the control panel will permanently
show a fault condition. See table 4 for a list of compatible sounder types.
Sounder circuits are monitored for open and short circuit faults by placing a 10K 0.25W end of line monitoring
resistor across the last device on the circuit.

Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring circuit
to work correctly.

POLARISED POLARISED
SOUNDER SOUNDER

SOUNDER + + IN + OUT + IN + OUT 10K end of

-
OUTPUT
TERMINALS line resistor

- IN - OUT - IN - OUT

See manufacturers See manufacturers


details for detailed details for detailed
connection information connection information

Man-1112 Sigma XT+_26 Page 17 of 52


8. Using intrinsically safe barriers
SIGMA XT+ control panels support the use of I.S. barriers for connecting to equipment in hazardous areas.
Only certified detectors, call points and sounders may be used in hazardous areas and these must be
connected to the control panel via a compatible I.S. barrier as listed in table 5.

Connection of the I.S. barrier changes the characteristics of the detection circuit so zones that have I.S. barriers
connected must be adjusted to work with them.
Programmable options C61 to C68 on the detection section allow each zone to operate with I.S. barriers.

The amount of detectors and call points that can be connected to a zone is limited by the I.S. approval system
diagram which should be supplied by the detector manufacturer. The power rating of the end of line resistor will be
dependent upon the Zone classification rating (Gas class) this will be specified on the system diagram.

SAFE AREA HAZARDOUS AREA


I.S. I.S. CALL
DETECTOR POINT

+ IN + OUT 6K8 end of


line resistor

- IN - OUT

DETECTION + See manufacturers


details for detailed
connection information
See manufacturers
details for detailed
connection information

-
ZONE
TERMINALS MTL5061 GALVANIC I.S. I.S. CALL
ISOLATOR DETECTOR POINT

DETECTION + 6 7
+ IN + OUT 6K8 end of

-
ZONE 5 8
TERMINALS line resistor
4 9

3 10

2 11 - IN - OUT

1 12 See manufacturers See manufacturers


details for detailed details for detailed
connection information connection information

Detection zone wiring through an MTL5061 galvanic isolator

SAFE AREA HAZARDOUS AREA

POLARISED POLARISED
SOUNDER SOUNDER

+
MTL7778ac

SOUNDER
+ IN + OUT + IN + OUT 10 K end of

-
OUTPUT
TERMINALS line resistor

- IN - OUT - IN - OUT

I.S. See manufacturers See manufacturers


EARTH
details for detailed details for detailed
connection information connection information

Sounder circuit wiring through an MTL7778ac I.S. barrier

Man-1112 Sigma XT+_26 Page 18 of 52


9. Connection to monitored inputs
Monitored inputs (Mode select, manual release, Hold, Abort, Released pressure switch and Low pressure switch)
have the same characteristics as detection zone inputs and require a 6K8 0.5W end of line monitoring resistor and
a nominal, 470 ohm 1 W trigger resistor.

+ PRESSURE
SWITCH

-
6K8 END
OF LINE
REISTOR
470
OHMS

Example of wiring to a monitored input

10. Connection to extinguishant output

The extinguishant output is capable of supplying up to 1 Amp for the maximum duration to a solenoid or 3 Amps for
20 milliseconds to an igniting actuator or Metron.

The wiring for solenoids and igniting actuators is different as shown below. Igniting actuators of different types or
from different manufacturers should not be mixed on the same circuit.

10.1 Solenoid wiring


Solenoids must have a resistance of greater than 28 ohms to ensure that the maximum current rating of the
extinguishant output is not exceeded.
Solenoids should be fitted with a suppression diode to prevent EMF generated by the solenoid when it de-energises
from upsetting the operation of the control panel.
Only polarised solenoids (i.e. solenoids fitted with an internal polarising diode) should be used.

+ +
EXTING

-
DIODE 1N 4004
BAND END TO +

Example of wiring a solenoid

Man-1112 Sigma XT+_26 Page 19 of 52


10.2 Igniting actuator wiring
A maximum of four igniting actuators can be wired in series. If only one or two actuators are fitted, a 2R2, 2.5 Watt
resistor must be wired in series with them to provide the correct monitoring resistance. The end of line diode can
be discarded when igniting actuators are used.

3 OR 4 ACTUATORS
WIRED IN SERIES
(MAXIMUM OF 4)

M M M M
+
EXTING

1 OR 2 ACTUATORS
WIRED IN SERIES

M M
+ FIT 2R2 2.5W RESISTOR
EXTING

IN SERIES WITH
ACTUATORS IF ONLY 1 OR
- 2 ACTUATORS ARE USED

To guarantee firing under all conditions, the total resistance of actuators, monitoring resistor and cable should not
exceed 7 ohms.

10.3 Setting up extinguishant monitoring circuit


The extinguishing output circuit is factory set to monitor the end of line diode that is fitted to the terminals and will
normally show a value of around 270.
If the parameters of the extinguishant output change e.g. by connecting a solenoid in parallel with the monitoring
diode or removing the diode and fitting igniting actuators, then the extinguishing output monitoring level will need
to be “learnt”. See section 15.2 for details. To do this, operate the enable controls keyswitch to put the system into
access level 2.

The LCD will show:

Ac c e s s l e v e l 2 ►
E NT E R f o r Me n u
Operate the WRITE ENABLE switch by gently sliding it to the left. The LCD will show:

A L 3 Up d a t e s = x x
E NT E R f o r Me n u

Press the ENTER button and then the UP button repeatedly until the LCD displays:

E x t i n g . O/ P 1
L e v e l = XX X

The XXX displayed here is the previous (factory) level to which the monitoring level had been set.

Press the ENTER button. The LCD will now show:

E x t i n g . O/ P 1
L e v e l = XX X ?

The XXX shown here is the current monitoring level detected on the extinguishing output. Press the ENTER button
to learn the new monitoring level.
Press the UP button to set the monitoring level for output 2 in the same way if it is being used, otherwise switch the
write enable slide switch to the right (off) position and check that an open or short circuit fault on the extinguishing
output(s) is detected and shown on the control panel.

Man-1112 Sigma XT+_26 Page 20 of 52


11. Connection to remote control terminals
Some functions of the control panel can be controlled externally from the panel if required. The external equipment
operating inputs must be restricted by an access level 2 control as defined in EN54-2 The functions are
abbreviated at the terminals block on the detection zone PCB in the top part of the control panel as follows:

a) Remote 0 V supply – ROV


b) Silence Alarm – SIL (Silences sounder outputs S1 &S2)
c) Sound Alarm – AL (Operates sounder outputs S1 & S2)
d) Fault – FLT (Generates a general fault and operates the fault relay)
e) Reset – RST (Resets the system back to normal condition)

To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open switch
or contact and via a resistance of no greater than 100 ohms.
All of the remote control inputs are non-latching.
R0V SIL AL FLT RST

SILENCE ALARM INPUT

SOUND ALARM INPUT

FAULT INPUT

RESET INPUT

12. Aux 24V DC supply outputs (extinguishant modules only)


The terminals for the Aux 24V supply are labelled Aux 24V + and ROV. The ROV terminal is the negative terminal.
It is possible to have the Aux24V supply outputs removed for a few seconds when the panel is reset.
Aux 24V not removed upon reset is set as default on the extinguishing modules. To change this, switch the system
to access level 2 by operating the enable control keyswitch and then operate the extinguishing module WRITE
ENABLE switch by gently sliding it to the left.
The LCD will show:

A L 3 Up d a t e s = x x
E NT E R f o r Me n u
Press the ENTER button and then the UP button repeatedly until the LCD displays:

R0 V No t Re mo v e d
On S y s t e m Re s e t

Press the ENTER button. The LCD will now show:

R0 V No t Re mo v e d
On S y s t e m Re s e t ?

Press the ENTER button. The LCD will now show:

R0 V Re mo v e d
On S y s t e m Re s e t

Press the exit button.

The Aux 24V supply outputs are fitted with an electronic, self resetting fuse rated at 0.5 Amps to protect the control
panel’s 24V supply in the event of a wiring fault. The Aux 24V outputs should not be loaded with any more than
100milliamps per module.
Any standing load on the Aux 24V supply outputs must be taken into account when calculating battery standby times
as standby time will be significantly affected by even modest standing loads on these outputs. It is recommended
that the Aux24V outputs are not used to power standing loads.
Where the Aux 24V supply outputs are used to power electromechanical devices such as relays or door retainers it
is imperative that a suppression diode is fitted across the coil of the device to prevent the generation of high voltage
transients back to the control panel power supply.

Man-1112 Sigma XT+_26 Page 21 of 52


13. Connection to relay contacts
Volt free changeover relay contacts are provided for local control and signalling if required. These contacts are rated
for switching signalling circuits only and the maximum ratings listed in table 1 should not be exceeded under any
circumstances.
Typically, the Aux 24V outputs of the control panel are switched through these relays and used to control other
systems.

13.1 Common Fault relay (on detection part of control panel)


The common fault relay is normally energised and will de-energise upon any fault condition on the detection part or
the extinguishing part of the control panel including total loss of power.
The fault relay can be disabled by setting configuration option 22 at access level 3 as shown in the Fire Detection
configuration options table.

13.2 Fault relay (on extinguishing part of control panel)


These fault relays are normally energised and will de-energise upon any fault condition on the extinguishing module
or total loss of power. These relays provide individual “flooding zone fault” outputs

13.2 Local fire relay (on detection part of control panel)


The local fire relay will energise upon activation of a fire condition on any of the zones or pressing of the sound
alarm button on the front panel. The relay will remain activated until the alarm is silenced or the panel is reset. This
relay will not operate upon activation of the remote AL input or when a fire condition is triggered on a zone that is
in test mode. This makes the Local fire relay suitable for inter panel signalling without the panels latching each
other.

13.3 Fire relay (on detection part of control panel)


The fire relay will energise upon activation of a fire condition on any of the zones or pressing of the sound alarm
button on the front panel. The relay will remain activated until the alarm is silenced or the panel is reset. This relay
will not operate upon activation of the remote AL input and the Silenced/ Sound Alarm button. The fire relay can be
disabled by setting configuration option 26 at access level 3 as shown in the Fire Detection configuration options
table.

13.4 1st stage alarm relay (on extinguishing modules)


First stage alarm relays will operate upon activation of a zone that has been configured to contribute to the
extinguishant release and will de-activate only when the panel has been reset.
This relay will also operate upon activation of the panel mounted or a remote manual release switch. The stage 1
relay output can be disabled at access level 2 via the menus on the Sigma XT+ module.

13.5 2nd stage alarm relay (on extinguishing modules)


Second stage alarm relays will operate when the panel enters the activated condition (i.e. the release countdown
timer has started) and will de-activate only when the panel has been reset from the released condition.
The stage 2 relay output can be disabled at access level 2 via the menus on the Sigma XT+ module.

13.6 Released relay (on extinguishing modules)


The released relay on the extinguishing module will operate when the module enters the released condition either
by being activated automatically via detection zones or by being activated by a manual release input. The released
relay will also operate if the panel enters the released condition via the released pressure switch input.
The Released output can be disabled at access level 2 via the menus on the Sigma XT+ module.

13.7 Aborted relay (on extinguishing modules)


Aborted relays will operate when the panel is in the aborted condition via an abort switch input.

13.8 Extract relay (on extinguishing modules)


The extract relay will operate when selected at access level 2. This provides a means to vent a room of extinguishant
gases but prevents the gases from being vented during a discharge.

To switch on the extract relay, operate the enable keyswitch and then press ENTER on the module on which the
required Extract relay is fitted.
The LCD will show:

DI S A B L E
E X T I NG REL E A S E ? Press the down button until the display shows:

T URN ON
E X T RA CT OUT P UT ? Press ENTER to turn on the Extract output.

The display will show:

T URN Of f
E X T RA CT OUT P UT ?

Pressing ENTER again with turn the extract output off.

Man-1112 Sigma XT+_26 Page 22 of 52


14. Connection and configuration of status units and ancillary boards
The control panel should not be powered during the connection of status units or ancillary boards.
Status units and ancillary boards require a four-wire connection from the associated extinguishing module, which
drops into each unit and connects to the corresponding data and power, in and out terminals. Two of the cables
carry power to the units (24V) and the other two carry data. A four core cable suitable for carrying RS485 data
should be used. If this is a twisted pair cable then one twisted pair should be used for the data connections and the
second pair used for the power connections.
When fitting status or ancillary boards, link LK2 must be removed from the rear of the extinguishant module. The
last status unit connected to the serial bus will have a terminating link fitted as described in manuals MAN-1089 and
MAN-1095.

REMOVE LK2 WHEN FITTING STATUS UNITS OR ANCILLARY BOARDS

TP34

C12
R12

D2

R87 R90
+

Q17
OPT1
C31 C7 R110

R55
TP28

R22
R59
R24
C81

W3 C16 D1 Q16
U14 TP36 R11 R161
C82 L34 R168
TP3 D12 R74 R160 R91
R169
R171
R88 R165 R173

U8

LED10
LED12
U1 R170 R65

U5
R159 k R172k R92
C80 C83 D11 D10 LED8
U13 R164 k R167 R68 R70 C70
k C2
+
TP23
C77

+
R28

R162 R177 R133 R163 C69


TP21 TP24
+

R166
D29 C19 C21
R29

LK4
C18
C20
R7 R6
LK2 U12 D17 D16 D15 D43 D14 D13 D9 D4 TP26
C25

C78 C27
R182 C26

C79 F3 U3
C71 C72
U4 R54 R51 R50 R48 R47 R42 R176 R175 R41 R40 R35 R34 R33 R32 R31 R30
+
R181

R180
R179

+
C6

L32
C75

L8 L7 L6 L5 L4 L3 L2
R8

C5

C73 L16 L15 L14 L13 L11 L10 L44 L43 L9


R1
L33

R89 R86
C76 C74 C50 C49 C47 C46 C43 C42 C111C110 C41 C40 C39 C38 C37 C36 C35 C34
U11

REAR VIEW OF EXTINGUISHING MODULE

Each status unit and ancillary board has a 3-bit DIL switch and must be allocated a unique address between 1 and
7. A maximum of 3 status units or Ancillary boards can be powered from the extinguishing module 24V output.
More units should use external 24V power supply.
The system is able to distinguish between status units and ancillary boards so it is possible to have a status unit set
to address 1 and an ancillary board set to address 1 if desired.

ADDRESS SWITCH POSITIONS


1
2
3
4
5
6
7

The address switch is located on the bottom left hand corner of the status unit or ancillary board PCB. Note: The
address is only read when the boards are first powered or if the processor reset switch on the ancillary board or
status unit is pressed, so address switches should not be altered on a system that has power applied.

It is important that each individual status unit and ancillary board is allocated a unique address in the range 1 to 7.
Units of the same type with the same address will cause intermittent faults to be displayed.
NOTE: 10 lamp status units (models K911113M8, K911113F8 and W911113W8) are not compatible with Sigma XT+
extinguishant modules.

Man-1112 Sigma XT+_26 Page 23 of 52


14.1 Adding new status units/ancillary boards
When the system is powered up, it will search for connected status units and/or ancillary boards connected to
extinguishant modules.
If status units or ancillary boards are fitted and detected by the control panel, the LCD will display:

X F A UL T S ► X = the number of faults


E NT E R T O V I E W

Press ENTER on the module to which the status units or ancillary boards are connected with the ENABLE control
switch keyswitch off and use the UP button on the module to view the faults. If status units and/or ancillary boards
are detected the LCD will display:

S T A T US UNI T X X = the address of the status unit found


F A UL T
Or

out put uni t x X = the address of the ancillary board found


f aul t
To accept the status units and/or ancillary boards found, turn the ENABLE controls keyswitch on and slide the WRITE
ENABLE switch on the module to which the status units or ancillary boards are connected gently to the left.

The LCD will then display:

S T A T US UNI T X X = the address of the status unit found


E NT E R T O A CCE PT
Or

out put uni t X X = the address of the ancillary board unit found
E NT E R T O A CCE PT
When the ENTER button is pressed on the module to which the status units or ancillary boards are connected, the
selected status unit or ancillary board will be added to the system and the next unit to be added will be displayed.
Press the ENTER button on the extinguishing module until all of the units have been accepted then gently slide the
WRITE ENABLE switch on the module to the right.

All of the status units and ancillary boards found by the extinguishant module have now been added and
disconnection of any of them will be displayed as a fault on the module and on the detection part of the system. If
any status units are disconnected, a HOLD activated indication will also be displayed at the extinguishing module
and all ancillary boards or status units that remain connected. With the ENABLE controls keyswitch off, the LCD will
display:

RE MOT E B US
F A UL T
When additional status units or ancillary boards are added to the system, these will be shown on the LCD of the
extinguishing module when the system is powered up or the processor reset switch is pressed on the module to
which the status unit or ancillary board is connected and can be added to the system by following the procedure
above.

14.2 Removing status units or ancillary boards


If a status units or ancillary board needs to be removed from the system, disconnect the status unit or ancillary
board taking care not to short power supply or data cables. The extinguishing module will display:

RE MOT E B US
F A UL T
Press the processor reset button on the extinguishant module to which the status unit or ancillary board is connected.
When the extinguishant module has re-started, it will display:

S T A T US UNI T X X = the address of the disconnected status unit


F A UL T
Or

out put uni t x X = the address of the disconnected ancillary board


f aul t

Turn the ENABLE controls keyswitch on and gently slide the write enable switch on the extinguishant module to
which the status units or ancillary boards are connected, to the left.
The LCD will then display:

Man-1112 Sigma XT+_26 Page 24 of 52


S T A T US UNI T X X = the address of the remaining status units found
E NT E R T O A CCE PT
Or

out put uni t X X = the address of the remaining ancillary boards unit found
E NT E R T O A CCE PT

When the ENTER button is pressed on the module to which the status units or ancillary boards are connected, the
selected status unit or ancillary board will be added to the system and the next unit to be added will be displayed.
Press the ENTER button on the extinguishing module until all of the units have been accepted then gently slide the
WRITE ENABLE on the extinguishing module switch to the right.

Full details of status units and ancillary boards can be found in documents MAN-1089 (Sigma XT Status unit operation
an maintenance manual) and MAN-1095 (Ancillary board operation and maintenance manual).

Man-1112 Sigma XT+_26 Page 25 of 52


SIGMA XT+ EXTINGUISHANT MODULE

CIE Status Status


serial serial power
+ - + - + - + - + -

D1036S ISSUE 04
S/NO.
X1
IC7
+ - + -

R22 R25

R30C R28
+24V- +24V-
W6 LED1
PF Z1 Z2 Z3 MAN DISAB REL ACT HOLD EXTR MAN

R13
C14
F IR E F IR E F IR E MODE REL RS485 RS485

R30A
R30D
R23 R26

R30B
C20

C19

R21
R24
DC DC IN OU T W5 IC4
D3
IC6 LED2
R1

R29

R29B
R29A

MODE HOLD
R27
R17 D7 T R6 D10 T R5 Z1 LED3

J2
C17 +

R29C
R29D
R20
D8 D9 Z2

R18
IC2 T R2 BZ1 LED5

TO NEXT ANCILLARY BOARD


R31
C16
C15
R33
T R7 R14

-
OUT
LED6
T R4
+

OR STATUS UNIT
RS485
R7 C11

D1
C3

R9
R6
Z10 X1
LED7

-
IC3 D5

R10
IC1

IN
+

X4

C4
D4
D6 T R1 LED8

C1
R2

R3
R4
C2

-
R19
C18
R5
C6
+

24V DC
C12

C13
XTAL1
+ LED9

C21
IC5
C9

-
+

R15

C8
REG1 + LED10

R16
R32

C7
C10 F1
R8 C5 D2 LED4
T R3 R12

HOL LED14
COM LED12

MOD LED13
CPU LED11
FUSE LED15
W4 W3 SW5

R11
SW2 SW1
PROC WDOG
ADDR RESET RESET

PROC ESSOR
MAN F USE RESET
Z1 Z2 Z3 MAN DISAB REL ACT REL EXTR HOLD OK FAIL
SW2

SW1
ADDR ESS

Wiring to status units and ancillary boards

Man-1112 Sigma XT+_26 Page 26 of 52


15. Configuring the panel

15.1 Detection part


Sigma XT+ control panels consist of 2 parts. The detection part has 2, 4 or 8 detection zones and has a number of
configuration options which can be set at the time of commissioning to suit the requirements of the installation.
These options are normally set once and will rarely need to change. The configuration options are only available at
access level 3 which is accessed by operating the Write enable switch to the left as shown below. When the panel is
at access level 3, the buzzer will “pip” three times every few seconds as an indication that it is at this access level.

WRITE ENABLE SWITCH

Access level 3 (Write enable) enable switch location – slide gently to the right to enable

Configuration options are simple to enter using the codes the table below. When the control panel is at access level
3, the sub-text of the Mode and Select buttons is used to enter a number using tens (+10) and units (+1).
When the required code number is displayed, pressing the enter button will cause the dot on the units seven segment
display to flash. This indicates that a configuration option has been set.
To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1 to A8,
C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set.

ZONE 1 I.S. BARRIER ZONE 1 I.S. BARRIER


OPTION SET OPTION NOT SET
DOT
NO DOT
FLASHING

Example display showing option set and not set.

Man-1112 Sigma XT+_26 Page 27 of 52


CODE FUNCTION COMMENTS
00 SOUNDER DELAY TIME = 30 SECONDS Sets the time delay before sounders operate in
01 SOUNDER DELAY TIME = 1 MINUTE combination with configuration codes 31 to 48 and access
02 SOUNDER DELAY TIME = 2 MINUTES level 2 function AD.
03 SOUNDER DELAY TIME = 3 MINUTES
04 SOUNDER DELAY TIME = 4 MINUTES
05 SOUNDER DELAY TIME = 5 MINUTES
06 SOUNDER DELAY TIME = 6 MINUTES
07 SOUNDER DELAY TIME = 7 MINUTES
08 SOUNDER DELAY TIME = 8 MINUTES
09 SOUNDER DELAY TIME = 9 MINUTES
10 COMMON ALARM MODE (default) All sounders operate upon any fire condition
11 TWO-STAGE ALARM MODE Continuous sounders in activated zone, pulsing elsewhere
12 ZONED ALARM MODE Only sounders connected to zone in alarm operate

21* DISABLE FIRE BUZZER Buzzer will not operate on fire condition
22* DISABLE FAULT OUTPUT Fault relay will not operate except upon total power
failure
23 DISABLE EARTH FAULT MONITORING Connection of fire alarm wiring will not announce a fault
24 PULSED REMOTE CONTROL OUTPUT Aux 24V supply pulses 1 sec on/1 sec off
25 ENABLE SOUNDERS ON DETECTION Not used
CIRCUITS
26 DISABLE FIRE OUTPUT Fire relay will not operate upon any alarm
27 DO NOT CHANGE DO NOT CHANGE

31 ZONE 1 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options
32 ZONE 2 ALARM FROM DETECTOR DELAYED 0-9 when selected zone(s) triggered by detector only.
33 ZONE 3 ALARM FROM DETECTOR DELAYED Note access level 2 function Ad must be set for this to
34 ZONE 4 ALARM FROM DETECTOR DELAYED take effect.
35 ZONE 5 ALARM FROM DETECTOR DELAYED
36 ZONE 6 ALARM FROM DETECTOR DELAYED
37 ZONE 7 ALARM FROM DETECTOR DELAYED
38 ZONE 8 ALARM FROM DETECTOR DELAYED

41 ZONE 1 ALARM FROM CALL POINT DELAYED Sounder outputs will be delayed by time set at options
42 ZONE 2 ALARM FROM CALL POINT DELAYED 0-9 when selected zone(s) triggered by call point only.
43 ZONE 3 ALARM FROM CALL POINT DELAYED Note access level 2 function Ad must be set for this to
44 ZONE 4 ALARM FROM CALL POINT DELAYED take effect.
45 ZONE 5 ALARM FROM CALL POINT DELAYED
46 ZONE 6 ALARM FROM CALL POINT DELAYED
47 ZONE 7 ALARM FROM CALL POINT DELAYED
48 ZONE 8 ALARM FROM CALL POINT DELAYED

51 COINCIDENCE ZONE 1 Zone contributes to ancillary board coincidence O/P. Any


52 COINCIDENCE ZONE 2 number of zones can be selected to contribute.
53 COINCIDENCE ZONE 3
54 COINCIDENCE ZONE 4
55 COINCIDENCE ZONE 5
56 COINCIDENCE ZONE 6
57 COINCIDENCE ZONE 7
58 COINCIDENCE ZONE 8

61 CONFIGURE Z1 FOR I.S BARRIER Detection threshold changed for use with IS barrier
62 CONFIGURE Z2 FOR I.S BARRIER
63 CONFIGURE Z3 FOR I.S BARRIER
64 CONFIGURE Z4 FOR I.S BARRIER
65 CONFIGURE Z5 FOR I.S BARRIER
66 CONFIGURE Z6 FOR I.S BARRIER
67 CONFIGURE Z7 FOR I.S BARRIER
68 CONFIGURE Z8 FOR I.S BARRIER

71* ZONE 1 SHORT CIRCUIT INDICATES ALARM Changes the trigger threshold of the
72* ZONE 2 SHORT CIRCUIT INDICATES ALARM zone so that the control panel can be
73* ZONE 3 SHORT CIRCUIT INDICATES ALARM used on older systems that had no short
74* ZONE 4 SHORT CIRCUIT INDICATES ALARM circuit monitoring.
75* ZONE 5 SHORT CIRCUIT INDICATES ALARM
76* ZONE 6 SHORT CIRCUIT INDICATES ALARM

Man-1112 Sigma XT+_26 Page 28 of 52


77* ZONE 7 SHORT CIRCUIT INDICATES ALARM
78* ZONE 8 SHORT CIRCUIT INDICATES ALARM

CODE FUNCTION COMMENTS


81* ZONE 1 NON-LATCHING Renders the zone self-resetting so that
82* ZONE 2 NON-LATCHING it can be used to receive signals from
83* ZONE 3 NON-LATCHING other systems and will reset when the
84* ZONE 4 NON-LATCHING input is removed.
85* ZONE 5 NON-LATCHING Note: It can take up to 20 seconds for zone to reset itself
86* ZONE 6 NON-LATCHING when sounders are operating
87* ZONE 7 NON-LATCHING
88* ZONE 8 NON-LATCHING

91 ZONE 1 DOES NOT SOUND ALARMS Prevents the zone from operating the two common
92 ZONE 2 DOES NOT SOUND ALARMS sounder outputs.
93 ZONE 3 DOES NOT SOUND ALARMS
94 ZONE 4 DOES NOT SOUND ALARMS
95 ZONE 5 DOES NOT SOUND ALARMS
96 ZONE 6 DOES NOT SOUND ALARMS
97 ZONE 7 DOES NOT SOUND ALARMS
98 ZONE 8 DOES NOT SOUND ALARMS
99
A1* ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously
A2* ZONE 2 ANY ALARM DELAYED before an alarm is generated.
A3* ZONE 3 ANY ALARM DELAYED
A4* ZONE 4 ANY ALARM DELAYED
A5* ZONE 5 ANY ALARM DELAYED
A6* ZONE 6 ANY ALARM DELAYED
A7* ZONE 7 ANY ALARM DELAYED
A8* ZONE 8 ANY ALARM DELAYED

C1 ZONE 1 SOUNDERS INHIBITED Not used


C2 ZONE 2 SOUNDERS INHIBITED
C3 ZONE 3 SOUNDERS INHIBITED
C4 ZONE 4 SOUNDERS INHIBITED
C5 ZONE 5 SOUNDERS INHIBITED
C6 ZONE 6 SOUNDERS INHIBITED
C7 ZONE 7 SOUNDERS INHIBITED
C8 ZONE 8 SOUNDERS INHIBITED

E1* ZONE 1 WILL NOT OPERTATE FIRE RELAY Enables individual zones to be selected to not operate the
E2* ZONE 2 WILL NOT OPERTATE FIRE RELAY fire relay. This is sometimes combined with the non-
E3* ZONE 3 WILL NOT OPERTATE FIRE RELAY latching function to prevent ring around on
E4* ZONE 4 WILL NOT OPERTATE FIRE RELAY interconnected panels
E5* ZONE 5 WILL NOT OPERTATE FIRE RELAY
E6* ZONE 6 WILL NOT OPERTATE FIRE RELAY
E7* ZONE 7 WILL NOT OPERTATE FIRE RELAY
E8* ZONE 8 WILL NOT OPERTATE FIRE RELAY

NOTE: Setting the options marked with asterisks does not comply with EN54-2

15.2 Extinguishing modules

15.2.1 Language selection


The module is capable of displaying two languages if factory programmed to do so. The first access level 3 option
is to select the local language or the default language (English)

15.2.2 Extinguishant output mode


The Sigma XT+ module has two extinguishing outputs. These can be configured to operate together at the same
time (common) or be configured as main and reserve outputs.
The factory default setting for the extinguishing outputs is common.
To change this, switch on the enable controls keyswitch and slide the write enable switch on the module to be
configured gently to the left. Press the ENTER button on the extinguishing module. The display will show:

E X T I NG O/ P MODE.
= COMMON Press the ENTER button and the display will show:

E X T I NG O/ P MODE.
= MA I N/ RES E RV E ? Press the ENTER button to select main/reserve.

To save the settings, slide the write enable switch gently to the right.
When the extinguishing module is activated, only extinguishant output 1 will switch on.
There will also be an additional menu item at access level 2 to allow the reserve extinguishant output to be
selected.
Man-1112 Sigma XT+_26 Page 29 of 52
15.2.3 Configuring the activation mode
It is possible to configure the extinguishing modules to be activated by coincidence (any 2 zones in a range of
zones) or a single zone in a range of zones. The activation mode is factory set to coincidence.
To change this, switch on the enable controls keyswitch and slide the write enable switch on the module to be
configured gently to the left. Press the ENTER button on the extinguishing module then press the UP button. The
display will show:

A CT I V A T I ON MODE.
= COI NCI DE NCE Press the ENTER button and the display will show:

A CT I V A T I ON MODE.
= si ngl e ? Press the ENTER button to select single zone activation mode.

To save the settings, slide the write enable switch gently to the right.
Operation of any of the zones in the range of zones selected to trigger the module (see below) will now put the
module into the activated condition. Coincidence mode must not be set if single activation is required.

15.2.4 Configuring Stage 1 /Hold Output

The ‘1st Stage’ relay output is factory set to activate when as a stage 1 alarm contact, it can be re-configured to
activate when the ‘Hold’ input is activated.

To change this, switch on the enable controls keyswitch and slide the write enable switch on the module to be
configured gently to the left. Press the ENTER button on the extinguishing module then press the UP button. The
display will show:

Us e r O/ p Mo d e
= St a g e 1 Press the ENTER button and the display will show:

Us e r O/ p Mo d e
= Ho l d ? Press the ENTER button to change mode.

To save the settings, slide the write enable switch gently to the right.

15.2.5 Configuring the activation zones


The extinguishing modules are factory set to be activated by coincidence activation of the logical zones in the
detection part of the panel and are addressed logically from 1 to 4.
This means that on an 8 zone, 4 extinguishing area panel for instance, zones 1 and 2 will be set to activate the
extinguishing module at address 1, zones 3 and 4 will be set to activate the extinguishing module at address 2 and
so on.
This can be changed if required so that any zones can activate the extinguishing module.
Note: The number of the first activation zone must be lower than the last activation zone.

To do this, switch on the enable controls keyswitch and slide the write enable switch on the module to be
configured gently to the left. Press the ENTER button on the extinguishing module and then the up button until the
display will shows:

F I RS T A CT I V .
Z ONE = X X will be the number of the zone currently selected to be the first activation zone.

This can be changed if required by using the UP and DOWN buttons to select the require zone number. When the
required zone number is displayed, pres the ENTER button. The display will show:

F I RS T A CT I V .
Z ONE = X ? X will be the number of the zone selected to be the first activation zone.

Press the ENTER button and then the UP button. The display will then show:

L A S T A CT I V .
Z ONE = X X will be the number of the zone currently selected to be the last activation zone.

This can be changed if required by using the UP and DOWN buttons to select the require zone number. When the
required zone number is displayed, pres the ENTER button. The display will show:

l a s t A CT I V .
Z ONE = X ? X will be the number of the zone selected to be the last activation zone.

Activation of any of the zones in the range selected will now contribute to activation of this module.

Man-1112 Sigma XT+_26 Page 30 of 52


15.2.6 Reset inhibit time
It is a requirement of the extinguishing control panel standard EN12094-1 to inhibit reset of the system after it
has been activated until there is a signal representing the end of the discharge (a released input) or for an
adjustable time period of up to 30 minutes. The factory default for the reset inhibit time is 0.
To change the reset inhibit time, switch on the enable controls keyswitch and slide the write enable switch on the
module to be configured gently to the left. Press the ENTER button on the extinguishing module then press the UP
button until the display shows:

RE S E T I NHI B I T
T I ME = 0 Press the ENTER button and the display will show:

RE S E T I NHI B I T
T I ME = 0 ? To change the reset inhibit time, press the UP or DOWN buttons until the time
required is displayed and then press ENTER.

To save the settings, slide the write enable switch gently to the right.
Resetting of the extinguishing module after it has been activated will now be prohibited until the set reset inhibit
time.

15.2.7 Pre-release delay time


The extinguishing control panel standard EN12094-1 allows for a time delay to be set from activation of the
extinguishing module to operation of the extinguishing release output. This time may be between 0 and 60
seconds with a maximum of 5 second steps.
The factory default time delay on the Sigma XT+ extinguishing modules is 30 seconds.
To change the pre release delay time, switch on the enable controls keyswitch and slide the write enable switch on
the module to be configured gently to the left. Press the ENTER button on the extinguishing module then press the
UP button until the display shows:

pr e- r el del ay
T I ME = 3 0 s e c . Press the ENTER button and the display will show:

pr e- r el del ay
T I ME = 3 0 s e c . ? To change the time, press the UP or DOWN buttons until the required time is
displayed.

To save the settings, slide the write enable switch gently to the right.
The pre=release delay time will now be set to the chosen value.

15.2.8 Output 2 delay


If the configured extinguishing output mode is Common (rather than MAIN/RESERVE), it is possible to set
extinguishing output 2 to have a further delay of up to 10 minutes in steps of 1 minute.
Extinguishing output 2 delay timer will be started when extinguishing output 1 is asserted.

This could be used to provide an additional discharge of extinguishing agent to maintain concentration for a longer
period of time.

Ou t p u t 2 De l a y
T I ME = 0 0 mi n . Press the ENTER button and the display will show:

Ou t p u t 2 De l a y
T I ME = 0 0 mi n . ? To change the time, press the UP or DOWN buttons until the required time is
displayed

To save the settings, slide the write enable switch gently to the right.
The extinguishing release time will now be set to the chosen value.

Note: This option is available only on modules fitted with firmware version 1.59 or higher.

15.2.9 Extinguishant release time


The time that the extinguishant output is active for can be set between 60 and 300 seconds. The factory default
time for this is 60 seconds. It is also possible to disable this timer such that the extinguishant outputs remain
active until the module is reset. See Release timer menu option section 15.2.12.

To change the extinguishant release time, switch on the enable controls keyswitch and slide the write enable
switch on the module to be configured gently to the left. Press the ENTER button on the extinguishing module then
press the UP button until the display shows:

E X T I NG. RE L E A S E
T I ME = 6 0 s e c . Press the ENTER button and the display will show:

Man-1112 Sigma XT+_26 Page 31 of 52


E X T I NG. RE L E A S E
T I ME = 6 0 s e c . ? To change the time, press the UP or DOWN buttons until the required time is
displayed

To save the settings, slide the write enable switch gently to the right.
The extinguishing release time will now be set to the chosen value.

15.2.10 Second stage alarm pulsing/continuous (alarm devices as required by EN12094-1)


The second stage alarm output can be configured to be steady or pulsing at about 1 second on, 1 second off to
suit the desired application.
The factory default for the second stage alarm is pulsing.

To change the operation of the second stage sounders, switch on the enable controls keyswitch and slide the write
enable switch on the module to be configured gently to the left. Press the ENTER button on the extinguishing
module then press the UP button until the display shows:

P UL S E D
A CT I V . A L A RMS Press the ENTER button and the display will show:

S T E A DY
A CT I V . A L A RMS ? To change to steady second stage alarms, press the ENTER button.

To save the settings, slide the write enable switch gently to the right.
The second stage alarm output will now be steady when the module is activated.

Note: Setting the option for ST EADY ACT I V. AL ARMS is not compliant with EN12094-1

15.2.11 Released indication


It is possible to select whether the released indication on a module is operated at the same time as the
extinguishant release outputs operate or by operation of a pressure switch connected to the released, pressure
switch input.
The factory default setting is for the released indication to be operated by operation of a pressure switch
connected to the released, pressure switch input.

To change the operation of the released indication, switch on the enable controls keyswitch and slide the write
enable switch on the module to be configured gently to the right. Press the ENTER button on the extinguishing
module then press the UP button until the display shows:

RE L E A S E D I ND ON
RE L E A S E D I NP UT Press the ENTER button and the display will show:

RE L E A S E D I ND ON To change to this, press the ENTER button.


E X T I NG. RE L ?
To save the settings, slide the write enable switch gently to the right.
The released indication will now be lit when the extinguishant outputs operate.

15.2.12 Delay on manual release


The manual release function (panel mounted and remote) can be configured to have a pre-release time delay (as
per the set pre-release time) or to have no pre-release delay allowing immediate operation of the extinguishant
outputs when a manual release is operated.
The factory default setting for this is for the manual release to have a delay time the same as the pre-release delay.

To configure the module to have no delay when a manual release is operated, switch on the enable controls
keyswitch and slide the write enable switch on the module to be configured gently to the left. Press the ENTER
button on the extinguishing module then press the UP button until the display shows:

DE L A Y ON
MA NUA L REL E A S E Press the ENTER button and the display will show:

NO DE L A Y ON
MA NUA L REL E A S E ? To change to this, press the ENTER button.

To save the settings, slide the write enable switch gently to the right.
Operation of a manual release will now operate the extinguishant outputs immediately with no delay.

15.2.13 Release timer (infinite extinguishant duration)


The release timer can be disabled such that once the extinguishant outputs have operated; they remain operated
until the system is reset.

To disable the release timer, switch on the enable controls keyswitch and slide the write enable switch on the
module to be configured gently to the left. Press the ENTER button on the extinguishing module then press the
DOWN button until the display shows:
Man-1112 Sigma XT+_26 Page 32 of 52
RE L E A S E T I ME R
E NA B L E D Press the ENTER button and the display will show:

RE L E A S E T I ME R To disable the release timer, press the ENTER button.


DI S A B L E D ?
To save the settings, slide the write enable switch gently to the right.
With the release timer disabled, the extinguishant outputs will remain operated until the system is reset.

15.2.14 R0V not removed on reset


It is possible to configure the AUX24V output on the Sigma XT+ module to be removed for a few seconds when
the system is reset.
The factory default setting is for the Aux24V output not to be removed when the system is reset.

To configure the module such that Aux24V output is removed for a few seconds when the system is reset, switch
on the enable controls keyswitch and slide the write enable switch on the module to be configured gently to the
left. Press the ENTER button on the extinguishing module then press the DOWN button until the display shows:

R0 V NOT RE MOV E D
ON S Y S T E M RE S E T Press the ENTER button and the display will show:

R0 V RE MOVE D
ON S Y S T E M RE S E T ? To select this option, press the enter button.

To save the settings, slide the write enable switch gently to the right.
With the release module configured to remove the R0V output on system reset, the Aux 24V output will be removed
for a few seconds when the reset button is pressed.

15.2.15 Disable earth fault monitoring


The earth fault monitoring facility can be disabled on each module individually.
The factory default setting is for the earth fault monitoring facility to be enabled.

To disable the earth fault monitoring, switch on the enable controls keyswitch and slide the write enable switch on
the module to be configured gently to the left. Press the ENTER button on the extinguishing module then press the
DOWN button until the display shows:

E A RT H F A UL T
E NA B L E D Press the ENTER button and the display will show:

E A RT H F A UL T
DI S A B L E D ? To select this option, press the enter button.

To save the settings, slide the write enable switch gently to the right.
The earth fault monitoring facility on the module will now be disabled, the Aux 24V output will be removed for a few
seconds when the reset button is pressed.

15.2.16 Disable fault output


The fault output relay can be disabled on each module individually.
The factory default setting is for the fault output relay to be enabled.

To disable the fault output relay, switch on the enable controls keyswitch and slide the write enable switch on the
module to be configured gently to the left. Press the ENTER button on the extinguishing module then press the
DOWN button until the display shows:

F A UL T o u t p u t
E NA B L E D Press the ENTER button and the display will show:

F A UL T o u t p u t
d i s ABL ED ? To select this option, press the enter button.

To save the settings, slide the write enable switch gently to the right.
The fault output relay on the module will now be disabled.
Note: Disabling the fault output does not comply with the requirements of EN54-2.

Man-1112 Sigma XT+_26 Page 33 of 52


15.2.17 Invert low pressure switch input
To enable low pressure switches to be used which have normally closed rather than normally open contacts, it is
possible to invert the low pressure switch input.
The factory default setting is for the low pressure switch input to use a normally open contact.

To invert the low pressure switch input, switch on the enable controls keyswitch and slide the write enable switch
on the module to be configured gently to the left. Press the ENTER button on the extinguishing module then press
the DOWN button until the display shows:

L OW P RE S S. I / P
MODE = NORMA L Press the ENTER button and the display will show:

L OW P RE S S. I / P
MODE = I NV E RT E D ? To select this option, press the enter button.

To save the settings, slide the write enable switch gently to the right.
The low pressure switch input will now require a normally closed contact via a 470R trigger resistor and 6K8 end of
line resistor for correct supervision.

Note: If the Low pressure input is configured as INVERTED in the menu option, an error will display
EXTING.PRESS.FAULT if the switch is not configured correctly.
The INVERTED input is looking for the 470 ohm trigger resistor to be removed on activation.

15.2.18 Invert Released Pressure switch input


To enable Released pressure switches to be used which have normally closed rather than normally open contacts, it
is possible to invert the Released pressure switch input.
The factory default setting is for the Released pressure switch input to use a normally open contact.

To invert the Released pressure switch input, switch on the enable controls keyswitch and slide the write enable
switch on the module to be configured gently to the left. Press the ENTER button on the extinguishing module then
press the DOWN button until the display shows:

Re l e a s e d I n p u t
MODE = NORMA L Press the ENTER button and the display will show:

Re l e a s e d I NP UT
MODE = I NV E RT E D ? To select this option, press the enter button.

To save the settings, slide the write enable switch gently to the right.
The Released pressure switch input will now require a normally closed contact via a 470R trigger resistor and 6K8
end of line resistor for correct supervision.

Note: When Released pressure input is configured as INVERTED in the menu option, the released condition will be
established and indicated.
The INVERTED input is looking for the 470 ohm trigger resistor to be removed on activation.

15.2.19Extinguishant output monitoring levels


The extinguishant outputs are able to monitor both solenoid and igniting actuator releasing devices. This requires
that the outputs be calibrated with the releasing device and the cable to it, fitted as it will be in the working system.
The extinguishant outputs are fitted with a 1N4004 diode at the factory and the default monitoring level will be set
at approximately 206 but may be between 204 and 208.
Before calibrating the extinguishant outputs ensure that the releasing device is fitted to the cable as shown in section
10.
To change the monitoring level for extinguishing output 2, switch on the enable controls keyswitch and slide the
write enable switch on the module to be configured gently to the left. Press the ENTER button on the extinguishing
module then press the DOWN button until the display shows:

ex t i ng. o/ p 2
l ev el = 206 Press the ENTER button and the display will show:

ex t i ng. o/ p 2 The XXX here will be the actual monitoring level read by the module.
l evel = xxx ? To save this setting press the ENTER button.

To set the monitoring level for extinguishant output 1, press the DOWN button. The display will show:

ext i ng. o/ p 1
Man-1112 Sigma XT+_26 Page 34 of 52
l evel = 206 Press the ENTER button and the display will show:

ex t i ng. o/ p 1 The XXX here will be the actual monitoring level read by the module.
l evel = xxx ? To save this setting press the ENTER button.

To save the settings, slide the write enable switch gently to the right.
The extinguishing output levels will now be set and any significant variation detected in the monitoring levels will be
announced as and EXTING. O/P fault.

16. Panel operation – Access levels 1 and 2


16.1 Normal condition
Under normal conditions and with all modules in Manual & Auto mode, control panels will have only the green, Power
On LED lit on the Fire detection part and on each of the extinguishing modules. With the ENABLE controls keyswitch
off, the display on the detection part of the panel will be blank and, the LCDs on the extinguishing modules will
show:

Ma n u a l & Au t o
Any modules that are in Manual Only mode with have an additional, Manual only yellow LED lit and their display will
show:

MA NUA L MODE
The control panel has 3 access levels. Access level 1 is available at all times and allows operation the Alarm/Fault
warning buzzer silence and Lamp test buttons on the detection part of the panel only. Access level 2 is enabled after
operation of the front panel mounted Enable Controls keyswitch and Access level 3 allows configuration options to
be set on both the detection part of the panel and the extinguishing modules following operation of their respective
Write Enable switches at access level 2 (Enable Controls keyswitch operated).

When the ENABLE controls keyswitch is operated (Access level 2) the display on the detection part of the control
panel will show and the LCDs on the extinguishing modules will show:

Ac c e s s l e v e l 2 ►
E NT E R f o r Me n u

16.2 Detection section – Access level 2.


16.2.1 Test mode
It is possible to put one or more zones into Test mode. When a zone is in test mode it will self reset after a few
seconds. This enables the system to be tested without having to return to the control panel to reset between each
device activation on the zone that is being tested.
To put a zone into test mode, switch the Enable Controls keyswitch on.

The 7 segment display will show (test zone 1)


To put zone 1 into test mode, press the ENTER button on the Sigma CP detection part.
The display will now show a flashing dot next to the and the yellow Test LED will be lit.
To select further zones to put into test mode, press the Select button and then the Enter button so that the flashing
dot appears next to the selected display e.g.

To remove test mode from a zone, press the Select button to reveal any zones that have a flashing dot and then
press the Enter button to take that zone out of test mode. Once all zones have been taken out of test mode, the
yellow, Test LED will go off.

16.2.2 Disable zones


It is possible to disable one or more zones. When a zone is disabled it will not report fire or fault conditions. This
enables the system to be worked on without false fire or fault conditions being announced.
To disable one or more zones, switch the Enable Controls keyswitch on.

The 7 segment display will show (test zone 1)


Press the Mode button and the display will show
To disable zone 1 press the Enter button. The display will show and the yellow Disablement LED will be lit.

To select further zones to disable, press the Select button and then the Enter button so that the flashing dot appears
next to the selected display e.g.

To remove disablements, press the Select button to reveal any zones that have a flashing dot next to the displayed
zone number and then press the Enter button. Once all zones have been enabled, the yellow, Disabled LED will go
off.

16.2.3 Disable sounder outputs


The sounder outputs on the detection part of the panel can be disabled if required.
Man-1112 Sigma XT+_26 Page 35 of 52
To disable the panel sounder outputs, switch the Enable Controls keyswitch on.

The 7 segment display will show (test zone 1)


Press the Mode button until the display shows
Press the Enter button. The display will now show the yellow disablement and sounder fault LEDs will be lit.

To enable the sounder outputs, press the Mode button while at Access level 2 (Enable keyswitch operated) and scroll
with the mode button until is displayed. Press the Enter button. The display will change to and the Sounder
fault and Disablement LEDs will go off if there are no other disablements active on the panel.

16.2.4 Activate delays


It is possible to set delays before sounder outputs will operate (see section 15.1). Before these time delays become
effective it is necessary to turn on the Activate delays function.
To do this, switch the Enable Controls keyswitch on.

The 7 segment display will show (test zone 1)


Press the Mode button until the display shows
Press the Enter button, the display will now show and the yellow Delay On and Disablement LEDs will be lit.

To switch off the delay, press the Mode button while at Access level 2 (Enable keyswitch operated) and scroll with
the mode button until is displayed. Press the Enter button. The display will change to and the Alarm
delay and Disablement LEDs will go off if there are no other disablements active on the panel.

16.3 Extinguishant modules – Access level 2


With the Enable Control keyswitch operated, all extinguishant modules will display:

Ac c e s s l e v e l 2 ►
E NT E R f o r Me n u

16.3.1 Disable extinguishant release outputs.


To disable both of the extinguishant release outputs, press the UP button on the module while at access level 2.
The display will show:

DI S A B L E
E X T I NG. RE L E A S E ? Press the Enter button to select this function. The display will show:

E NA B L E
E X T I NG. RE L E A S E ? The yellow disabled LED on the module that has been disabled
will be lit.

Turn the Enable keyswitch off to leave the disablement active. To re-enable the extinguishant outputs repeat the
procedure above.

16.3.2 Disable Manual release


To disable all Manual release inputs (front panel mounted and remotely connected), press the UP button on the
module while at access level 2 until the module displays:

DI S A B L E
ma n u a l REL E A S E ? Press the Enter button to select this function. The display will show:

enabl e
ma n u a l REL E A S E ? The yellow disabled LED on the module that has been disabled
will be lit.

Turn the Enable keyswitch off to leave the disablement active. To re-enable the manual release facility repeat the
procedure above.

16.3.3 Disable Stage 1 output


To disable the 1st Stage relay output, press the UP button on the module while at access level 2 until the display
shows:

DI S A B L E
s t age 1 out put ? Press the Enter button to select this function. The display will show:

E NA B L E
S T A GE 1 OUT P UT ? The yellow disabled LED on the module that has been disabled
will be lit.

Man-1112 Sigma XT+_26 Page 36 of 52


Turn the Enable keyswitch off to leave the disablement active. To re-enable the Stage 1 relay output repeat the
procedure above.

16.3.4 Disable Stage 2 output


To disable the 2nd Stage relay output, press the UP button on the module while at access level 2 until the display
shows:

DI S A B L E
s t age 2 out put ? Press the Enter button to select this function. The display will show:

E NA B L E
S T A GE 2 OUT P UT ? The yellow disabled LED on the module that has been disabled
will be lit.

Turn the Enable keyswitch off to leave the disablement active. To re-enable the Stage 2 relay output repeat the
procedure above.

16.3.5 Disable Released output


To disable the Released relay output, press the UP button on the module while at access level 2 until the display
shows:

DI S A B L E
r el eased out put ? Press the Enter button to select this function. The display will show:

E NA B L E
r e l e a s e d OUT P UT ? The yellow disabled LED on the module that has been disabled
will be lit.

Turn the Enable keyswitch off to leave the disablement active. To re-enable the Released relay output repeat the
procedure above.

16.3.6 Disable Extract output


To disable Extract relay output, press the UP button on the module while at access level 2 until the display shows:

DI S A B L E
ex t r ac t out put ? Press the Enter button to select this function. The display will show:

E NA B L E
ext r act OUT P UT ? The yellow disabled LED on the module that has been disabled
will be lit.

Turn the Enable keyswitch off to leave the disablement active. To re-enable the Extract relay output repeat the
procedure above.

16.3.7 Turn on Extract output


To turn on the extract relay output, press the DOWN button on the module while at access level 2 until the display
shows:

T URN ON
E X T RA CT OUT P UT Press the Enter button to select this function. The display will show:

T URN OF F
E X T r a CT OUT P UT ? The yellow disabled LED on the module that has been disabled
will be lit.

Turn the Enable keyswitch off to leave the Extract output active. To turn off the Extract output, repeat the procedure
above. Note: the extract output does not turn off when the module is reset.

16.3.8 Select Reserve Solenoid Output (Configuration Option)


If the extinguishing module is configured for Main/Reserve solenoid operation (See section 15.2.1) then an
additional menu option is given to select which output is used.

To turn on the Reserve Solenoid output, press the UP button on the module while at access level 2 until the
display shows:

S E L E CT RES E RV E
E X T I NG. OUT P UT Press the Enter button to select this function. The display will
show:

S E L E CT MAI N
E X T I NG. OUT P UT ? The yellow Reserve Cylinders LED indicator on the module
will be lit.

Turn the Enable keyswitch off to leave the Reserve solenoid output active. To revert to the Main solenoid output,
repeat the procedure above.

Man-1112 Sigma XT+_26 Page 37 of 52


Note: This menu option is not shown if the panel is configured to Common Solenoid mode.

16.4 Single zone Fire condition


Upon receipt of a fire condition by activation of a detector or call point, the Common Fire indicator on the detection
section will light, the fire buzzer will sound and the zonal Fire indicator(s) will flash at around 2Hz.
The fire and local fire relays will also operate and signal any systems to which they are connected.
Any sounders connected to the sounder circuits S1 & S2 on the detection section will operate. These sounders may
be silenced by operation of the silence alarm button with the enable keyswitch operated such that the panel is at
access level 2.
If the zone that has activated is contributing to the extinguishant release sequence on an extinguishant module and
the module is configured for coincidence activation, the Release Imminent LED on the module will flash, the first
stage relay contact will operate, the first stage sounder output will operate and the display will show:

pr eac t i v at ed ►

Pressing the Silence alarm button on the detection section will turn off the sounder outputs on the detection section
and the first stage alarm outputs on the extinguishant module.

16.5 Double zone Fire condition


Upon receipt of a second fire condition that contributes to extinguishant release on modules that are switched to
Automatic and Manual mode with their Hold inputs not active and the Disable Extinguishant function has not been
invoked, the detection section will respond as above and extinguishant modules will respond as listed below:

a) The second stage alarm output will operate. (Sounder circuit S3)
b) The 2nd stage contact will operate.
c) The Activated indicator will operate
d) The display will indicate A c t i v a t e d and show the time remaining until release in seconds.
e) The extinguishant output will operate after the configured delay time and for the configured duration.
f) The display will show A c t i v a t e d Di s c h a r g i n g for the duration of the release time.

When detection zones have activated and the activated condition is reached (i.e. the Activated indicator is lit) it shall
not be possible to reset the extinguishant section of the panel until the Reset Inhibit timer has elapsed.

16.6 Silence/sound alarms


The Silence/Sound alarm button can only be operated at access level 2. (Enable Control keyswitch operated).
To silence the sounders, insert the Enable Control key, turn to the right and press the Silence/Sound alarm button.
When the sounders have been silenced, the Zone Fire LEDs will change from flashing to a steady state.
Pressing the Silence/Sound alarm whilst the control panel is in this silenced condition will cause the sounders to
operate again.
The sounders can be toggled on and off with the Silence/Sound alarm button as required.

16.7 Reset
To reset the panel, insert the Enable key, turn to the right then press the Reset button.
The extinguishant section will reset only after the Reset Inhibit timer has expired once the activated condition has
been established.

16.8 Detection Zone fault


Removal of a detector from its base or a fault on any of the zone wiring will cause the Fault LED and Zone Fault
LEDs to flash, indicating the zone in which the fault has occurred.

16.9 Sounder fault


A fault on the wiring to the detection section sounder circuits will cause the Fault LED to light and the Sounder Fault
LED to flash. A fault on the sounder circuits of extinguishant modules (alarm devices as required by EN12094-1) will
light the Fault LED on the detection section and on the extinguishant module. The extinguishant module will display:

s t a g e 1 a l a r ms
f aul t
or

s t a g e 2 a l a r ms
f aul t

16.10 Power fault


Failure of the mains power or disconnection of the standby battery will cause the Fault and Power Fault LEDs to light
on the detection section indicating an abnormality in the power supply to the control panel. There will be no indication
of this condition on the extinguishant modules.

16.11 System fault – Detection section


The System Fault and general fault LEDs will light if the configuration memory has not been set or has become
corrupted.

Man-1112 Sigma XT+_26 Page 38 of 52


16.12 System fault – Extinguishant modules
The System Fault and general fault LEDs will light if the configuration memory has not been set or has become
corrupted.

16.13 General fault – Detection section


The General fault LED will be illuminate under any fault condition.
This LED will also light if the write enable switch has been left in the access level 3 position and the Enable Controls
keyswitch is turned off.

16.14 Lamp test


All LED indicators on the panel can be tested at any time by pressing the Lamp Test button on the Detection part.
The Enable Control keyswitch does not need to be operated test the indicators.
Indicators on individual extinguishant modules cam be lamp tested by holding down the EXIT button for more than
2 seconds.

16.15 Hold condition


Activation of the Hold input or a fault on the monitored wiring of the Hold circuit on a module or at a remotely
mounted status unit will cause the Hold Activated indicator to light on the module and on any status units or ancillary
boards connected to it.

If the extinguishant module is in the Activated condition and the pre-release timer is running then the extinguishant
release sequence will be halted and the pulsing, 2nd stage sounders shall change to 1 second on, 2 seconds off.
Release of the Hold input will re-start the pre-release timer from maximum.

16.16 Released condition


The released pressure switch input will be connected to a pressure switch mounted on the extinguishant cylinder
which operates when the extinguishant has been released. This will activate the released indicator on the control
panel. If the extinguishant has been released by mechanical means i.e. the control panel is not in the activated
condition, operation of the released pressure switch input will establish the Released condition. (See also 15.2.8)

16.17 Low pressure switch


The low pressure switch input will be connected to a pressure switch on the extinguishant cylinder which will operate
if the pressure in the cylinder falls below a set point. This will happen after the extinguishant has been released but
may happen before release through a leak. The fault LED on the module and on the detection part will light and the
buzzer will sound when this input is operated.

16.18 Manual only mode


The mode of the system can be toggled between Manual Only and Automatic & Manual by operating the Mode select
keyswitches on the modules.
When a module is in Manual Only mode, the extinguishant cannot be released by the operation of automatic
detectors.
The mode can also be changed to manual by the external mode select input or a keyswitch on a status unit. Any
mode select input that is switched to Manual only mode will override any keyswitches switched to Automatic and
Manual mode. All inputs must be switched to Manual and Automatic mode for a module to be in Automatic and
Manual mode.

16.19 Manual Release


Extinguishant modules may be activated by Manual release inputs via the manual release control on the front of
each module, a remotely mounted Manual release control connected the monitored manual release inputs or by a
manual release control mounted on a status unit.
Activation of any of these Manual release controls will immediately activate the extinguishant module and begin the
pre-release timer if the module is configured to have a time delay for Manual release inputs.

16.19 Abort input


Each module has the facility for connection of an Abort control. Operation of the Abort input or a fault on the
monitored wiring of the Abort circuit during the pre-release delay time or before activation will light the Abort
indicator on the module and the extinguishant release timer will be canceled i.e. the extinguishant will not be
released. The module can be immediately reset from this condition.

Man-1112 Sigma XT+_26 Page 39 of 52


17. Internal Controls
17.1 Detection part

17.1.1 Watchdog reset


If for any reason the microprocessor in the detection part of the control panel fails to carry out its operation correctly
it will attempt to restart. This process is called a “watchdog” and the control panel must record and indicate these
events.
If a watchdog event occurs, the detection part panel will show the Fault and System Fault LEDs on the front panel,
the CPU fault LED inside the panel will light and the buzzer will sound. This fault can only be cleared by pressing the
Watchdog Reset button on the PCB inside the control panel. The control panel buzzer will continue to sound until
the watchdog activation is reset.

17.1.2 Processor reset


Once started, the microprocessor controlling the detection part of the panel should continue to run continuously
without interruption. If the microprocessor fails to run correctly it can be reset by pressing the Processor Reset
button on the PCB inside the control panel.
This should not normally be necessary but should be done as a matter of course if the system is behaving abnormally.
The system should resume normal operation within a couple of seconds of pressing the processor reset button. It
will be necessary to pres the Watchdog Reset button a few seconds after pressing the Processor Reset button to
clear the Watchdog indication and buzzer.

17.1.3 Write enable switch


It is necessary to protect the configuration memory of the panel while it is running normally. To do this a memory
Write Enable switch is provided. The memory Write Enable switch must be switched on before any changes can be
made to the configuration. The Write Enable switch is quite fragile and should be operated with care.

Internal controls on detection part of


control panel

W/ DOG PROC WRITE


RESET .
RESET ENABLE

17.2 Extinguishant modules

17.2.1 Watchdog reset


If the microprocessor on an extinguishant module fails to carry out its operation correctly it will attempt to restart.
If a watchdog event occurs, the Extinguishant module will show Fault and System Fault LEDs on the front panel, the
detection part of the panel will show a fault and the buzzer will sound and the display on the Extinguishant module
will show CPU fault
This fault can only be cleared by pressing the Watchdog Reset button on the Extinguishant module. The control
panel buzzer will continue to sound until the watchdog activation is reset.

17.2.2 Processor reset


If the microprocessor on an Extinguishant module fails to run correctly it can be reset by pressing the Processor
Reset button on the PCB inside the control panel.
This should not normally be necessary but should be done as a matter of course if the system is behaving abnormally.
The system should resume normal operation within a couple of seconds of pressing the processor reset button.

17.2.3 Terminate extinguishant


Once the extinguishant outputs have been operated they can not be switched off until after the reset inhibit timer
has elapsed. For test purposes a terminate extinguishant button is provided which will terminate operation of the
extinguishant outputs and allow the system to be reset.

17.2.4 Write enable switch


It is necessary to protect the configuration memory of extinguishant modules while the system is running
normally. To do this a memory Write Enable switch is provided on each module. The memory Write Enable switch
must be switched on before any changes can be made to the configuration. The Write Enable switch is quite fragile
and should be operated with care.

Man-1112 Sigma XT+_26 Page 40 of 52


17.2.5 Address switch
Extinguishant modules are connected to the serial bus of the Sigma CP detection part of the control panel and each
module must be allocated an address between 1 and 7 using the binary coded DIP switch.

The switch setting are shown in this table

ADDRESS SWITCH POSITIONS


1
2
3
4
5
6
7

Internal controls on extinguishant modules

Term. Exting. Proc. Reset W/dog Reset Address Write Enable

18. Internal indications


18.1 Detection part
To assist in identifying fault conditions which are not detailed on the front of the control panel, a number of internal
indicators are visible with the control panel door open as follows:

18.1.1 Mains fail


Indicates that the 230V AC supply is not present and the system is running on standby batteries.
If there is not a power cut, check the panels mains fuse.

18.1.2 Batt fail


Indicates that the standby battery has become disconnected or that the charging circuit of the control panel has
failed. Check that both batteries are connected and linked together. Test battery. Disconnect battery and ensure
that 28 Volts can be measured on battery charger leads.

18.1.3 CPU fault


Indicates that the processor has failed to correctly execute code and has been re-started by the system watchdog.
The watchdog reset switch must be pressed to clear the CPU fault condition.
Press watchdog reset. If system does not return to normal then the panel is probably damaged and needs the circuit
board replacing.

18.1.4 Aux 24V fault


The Aux 24V and R0V terminals provide a 100 milliamp, 24V DC power supply for power fire alarm ancillary
equipment. This LED indicates that fuse protecting the R0V output has operated and the rating of this output has
been exceeded. The fuse is a self resetting type and the supply will resume when the fault condition is removed.

18.1.5 Batt low


Illuminates when the system is running on batteries and the battery voltage is between 21.5 V and 20.5 V (the
minimum battery voltage).
Man-1112 Sigma XT+_26 Page 41 of 52
18.1.6 Comms fault
Indicates that communication has been lost with an Extinguishant module, Repeater panel or Ancillary board. Check
for comms fault at all Extinguishant modules, Repeaters and Ancillary boards to identify the source of the problem.

18.1.7 Earth fault


Indicates that part of the system wiring is connected to earth. Remove all system wiring and re-connect cables one
at a time until the earth fault returns. This will indicate which cable the earth fault is present on.

18.1.8 Sys fuse fault


Indicates that the total power rating of the power supply has been exceeded and that the system fuse has come
into operation. Remove and review all loads then re-connect one at a time.

18.1.9 S1 fault
Indicates a short or open circuit on sounder outputs. Remove wiring and refit end of line resistors. Check sounder
circuit wiring.

18.1.10 S2 fault
Indicates a short or open circuit on sounder outputs. Remove wiring and refit end of line resistors. Check sounder
circuit wiring.

18.2 Extinguishant modules


18.2.1 Watchdog
Indicates that the processor has failed to correctly execute code and has been re-started by the watchdog circuit.
The watchdog reset switch must be pressed to clear the Watchdog fault condition.
Press the Watchdog reset button. If system does not return to normal then the module is probably damaged and
needs the circuit board replacing.

18.2.2 System fuse


Indicates that the modules main fuse has been overloaded and the module is shut down. Remove and review all
loads then re-connect one at a time.

18.2.3 Man. Release


Indicates that either the front panel mounted or a remotely connected Manual release control has been operated.
This indication can only be cleared by power cycling the module or pressing the processor reset switch.

Man-1112 Sigma XT+_26 Page 42 of 52


19. Power supply
The control panel requires a 230V (+10%/-15%), 50/60Hz, AC mains power supply which connects to the fused
terminal block labelled “230V”.
Panels with a 3A power supply have a 20mm, F1.6A L250V mains fuse.
Panels with a 5.25A power supply have a 20mm T3A L250V mains fuse.
These fuses should only be replaced with fuses of the same or similar types.

The table below shows the power supply rating and recommended battery capacity for each model in the Sigma XT+
range.
Model Description Power supply rating Batteries recommended
for 24 hour standby
K21021M3 Two zone single area 3A 7Ah
K21041M3 Four zone single area 3A 7Ah
K21042M3 Four zone two area 3A 7Ah
K21081M3 Eight zone single area 3A 7Ah
K21082M3 Eight zone two area 3A 7Ah
K21083M3 Eight zone three area 5.25A 12Ah
K21084M3 Eight zone four area 5.25A 12Ah

The maximum loading on the power supply must be carefully considered when connecting externally powered
equipment such as sounders and solenoids.

Exceeding the maximum power supply rating may cause a fuse or other protective device to operate and
render the equipment inoperative until the fuse is replaced or protective devices are reset.

The tables below can be used to calculate the loading for all models by adding the loads in the second column.
K21021M3 2 zone single area Current in milliamps
Detection section max alarm load 100
Extinguishing module max alarm load 105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module total sounder load
Extinguishant module extinguishant output load
Extinguishant module Aux 24V supply

TOTAL LOAD (must be less than 3A)

K21041M3 4 zone single area Current in milliamps


Detection section max alarm load 210
Extinguishing module max alarm load 105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module total sounder load
Extinguishant module extinguishant output load
Extinguishant module Aux 24V supply

TOTAL LOAD (must be less than 3A)

K21042M3 4 zone two area Current in milliamps


Detection section max alarm load 210
Extinguishing module 1 max alarm load 105
Extinguishing module 2 max alarm load 105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module 1 total sounder load
Extinguishant module 2 total sounder load
Extinguishant module 1 extinguishant output load
Extinguishant module 2 extinguishant output load
Extinguishant module 1 Aux 24V supply
Extinguishant module 2 Aux 24V supply

TOTAL LOAD (must be less than 3A)

K21081M3 8 zone single area Current in milliamps


Detection section max alarm load 550
Extinguishing module max alarm load 105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module total sounder load
Extinguishant module extinguishant output load
Extinguishant module Aux 24V supply

TOTAL LOAD (must be less than 3A)

Man-1112 Sigma XT+_26 Page 43 of 52


K21082M3 8 zone two area Current in milliamps
Detection section max alarm load 550
Extinguishing module 1 max alarm load 105
Extinguishing module 2 max alarm load 105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module 1 total sounder load
Extinguishant module 2 total sounder load
Extinguishant module 1 extinguishant output load
Extinguishant module 2 extinguishant output load
Extinguishant module 1 Aux 24V supply
Extinguishant module 2 Aux 24V supply

TOTAL LOAD (must be less than 3A)

K21083M4 8 zone three area Current in milliamps


Detection section max alarm load 550
Extinguishing module 1 max alarm load 105
Extinguishing module 2 max alarm load 105
Extinguishing module 3 max alarm load 105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module 1 total sounder load
Extinguishant module 2 total sounder load
Extinguishant module 3 total sounder load
Extinguishant module 1 extinguishant output load
Extinguishant module 2 extinguishant output load
Extinguishant module 3 extinguishant output load
Extinguishant module 1 Aux 24V supply
Extinguishant module 2 Aux 24V supply
Extinguishant module 3 Aux 24V supply

TOTAL LOAD (must be less than 5.25A)

K21084M4 8 zone four area Current in milliamps


Detection section max alarm load 550
Extinguishing module 1 max alarm load 105
Extinguishing module 2 max alarm load 105
Extinguishing module 3 max alarm load 105
Extinguishing module 4 max alarm load 105
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module 1 total sounder load
Extinguishant module 2 total sounder load
Extinguishant module 3 total sounder load
Extinguishant module 4 total sounder load
Extinguishant module 1 extinguishant output load
Extinguishant module 2 extinguishant output load
Extinguishant module 3 extinguishant output load
Extinguishant module 4 extinguishant output load
Extinguishant module 1 Aux 24V supply
Extinguishant module 2 Aux 24V supply
Extinguishant module 3 Aux 24V supply
Extinguishant module 4 Aux 24V supply

TOTAL LOAD (must be less than 5.25A)

The output voltage of the power supply is between 18 and 30V depending on mains and battery condition and the
total current rating is either 3A or 5.25A depending on the model (see tables above).
The incoming mains cable should be routed well away from other lower voltage wiring by a distance of at least
50mm.
Mains wiring should include an earth conductor, which is securely bonded to the building earth and should enter the
enclosure as close as possible to the mains terminal block. Mains wires should be kept very short inside the enclosure
and secured together close to the mains terminal block with a cable tie.
The maximum capacity batteries that should be fitted are 7Ah for KXXXXM3 models and 17Ah for KXXXXM4 models.
The maximum current drawn from the batteries when the main power source is disconnected is 3 Amps for KXXXXM3
models and 5.25 Amps for KXXXXM4 models.

Man-1112 Sigma XT+_26 Page 44 of 52


TEMPERATURE
SENSOR WIRE

K21083M4 and K21084M4 models have a temperature compensation


sensor held in place on the power supply chassis with adhesive tape. The
tip of the sensor must be fitted to one of the batteries with the tape supplied
TEMPERATURE
for correct temperature compensation.
SENSOR

TAPE

BATTERY

Battery leads are supplied wired to the power supply along with a link to connect the two batteries together.
It is most important that the polarity of the batteries is carefully observed when connecting. Wrongly
connected batteries could cause damage to the control panel.

21. Maintenance
SIGMA XT+ control panels do not require any specific maintenance but should the control panel become dirty it can
be wiped over with a barely damp cloth. Detergents or solvents should not be used to clean the panel and care must
be taken that water does not enter the enclosure.

The control panel contains sealed lead acid batteries to provide standby power in the event of mains failure.
These batteries have a life expectancy of around 4 years. It is recommended that these batteries be tested in
accordance with the battery manufacturer’s recommendations annually to determine their suitability for continued
standby applications.

Testing of the extinguishant system should only be carried out by trained personnel and must be done with
appropriate isolation measures in place to ensure that accidental discharge of the extinguishant agent is avoided.

Should the control panel become faulty the complete electronic assemblies and front plates can be replaced.

To do this, any configured options should be noted then both mains and battery power should be removed before
the work is started.

The field wiring should be carefully labelled and removed from the terminals. The power terminal block can be
unplugged from the PCB by pulling it towards you.

The faulty PCB plate assembly can now be taken out of the panel by removing the 2 screws.
Fitting the new PCB is the reverse of the procedure for removing the board.

Man-1112 Sigma XT+_26 Page 45 of 52


23. CE Mark
All control panels have a label affixed to the inside of the lid as shown below.
This label should not be removed under any circumstances.

Man-1112 Sigma XT+_26 Page 46 of 52


24. Commissioning instructions
24.1 Before applying power to the panel, any solenoids or igniting actuators must be physically isolated from the
system by disconnecting both wires to it. This will prevent any accidental release of extinguishant.

24.2 When power is applied, if all connections are correct, only the green Power On indicators should be lit.
If any fault indicators are lit the wiring to the appropriate input or output should be checked an all faults
cleared before proceeding.

24.3 Once the panel is fault free, it can be configured with the desired options as
described in section 15 .

24.4 Once the panel has been configured the system should be thoroughly tested to ensure that the control panels
responds as expected and required.

24.5 After satisfactory testing, any final connections should be made (such as to the
extinguishant release actuator).

24.6 A record of the configuration options that have been set should be recorded in the tables below and this
manual provided as part of the documentation recommended by BS5839:Part 1:2002 section 40.2 b).

Detection section
CODE FUNCTION TICK IF SET
00 SOUNDER DELAY TIME = 30 SECONDS
01 SOUNDER DELAY TIME = 1 MINUTE
02 SOUNDER DELAY TIME = 2 MINUTES
03 SOUNDER DELAY TIME = 3 MINUTES
04 SOUNDER DELAY TIME = 4 MINUTES
05 SOUNDER DELAY TIME = 5 MINUTES
06 SOUNDER DELAY TIME = 6 MINUTES
07 SOUNDER DELAY TIME = 7 MINUTES
08 SOUNDER DELAY TIME = 8 MINUTES
09 SOUNDER DELAY TIME = 9 MINUTES
10 COMMON ALARM MODE (default)
11 TWO-STAGE ALARM MODE
12 ZONED ALARM MODE

21* DISABLE FIRE BUZZER


22* DISABLE FAULT OUTPUT
23 DISABLE EARTH FAULT MONITORING
24 PULSED REMOTE CONTROL OUTPUT
25 ENABLE SOUNDERS ON DETECTION CIRCUITS
26 DISABLE FIRE OUTPUT
27 DO NOT CHANGE
28 INDICATE CALL POINT ACTIVATION Activation of a call point with a 270R
resistance fitted is indicated by a
flashing zone indicator and “Pu” on
the 7 segment display. Activation of
a detector will be indicated by a
steady zone indicator and nothing
on the 7 segment display.
29 DO NOT RE-SOUND ALARMS FROM Silenced sounders will not re-sound
ANOTHER ZONE upon further zone activations.

31 ZONE 1 ALARM FROM DETECTOR DELAYED


32 ZONE 2 ALARM FROM DETECTOR DELAYED
33 ZONE 3 ALARM FROM DETECTOR DELAYED
34 ZONE 4 ALARM FROM DETECTOR DELAYED
35 ZONE 5 ALARM FROM DETECTOR DELAYED
36 ZONE 6 ALARM FROM DETECTOR DELAYED
37 ZONE 7 ALARM FROM DETECTOR DELAYED
38 ZONE 8 ALARM FROM DETECTOR DELAYED

41 ZONE 1 ALARM FROM CALL POINT DELAYED


42 ZONE 2 ALARM FROM CALL POINT DELAYED
43 ZONE 3 ALARM FROM CALL POINT DELAYED
44 ZONE 4 ALARM FROM CALL POINT DELAYED
45 ZONE 5 ALARM FROM CALL POINT DELAYED
46 ZONE 6 ALARM FROM CALL POINT DELAYED
47 ZONE 7 ALARM FROM CALL POINT DELAYED
48 ZONE 8 ALARM FROM CALL POINT DELAYED

51 COINCIDENCE ZONE 1
Man-1112 Sigma XT+_26 Page 47 of 52
52 COINCIDENCE ZONE 2
53 COINCIDENCE ZONE 3
54 COINCIDENCE ZONE 4
55 COINCIDENCE ZONE 5
56 COINCIDENCE ZONE 6
57 COINCIDENCE ZONE 7
58 COINCIDENCE ZONE 8

61 CONFIGURE Z1 FOR I.S BARRIER


62 CONFIGURE Z2 FOR I.S BARRIER
63 CONFIGURE Z3 FOR I.S BARRIER
64 CONFIGURE Z4 FOR I.S BARRIER
65 CONFIGURE Z5 FOR I.S BARRIER
nt 66 CONFIGURE Z6 FOR I.S BARRIER
67 CONFIGURE Z7 FOR I.S BARRIER
68 CONFIGURE Z8 FOR I.S BARRIER

71* ZONE 1 SHORT CIRCUIT INDICATES ALARM


72* ZONE 2 SHORT CIRCUIT INDICATES ALARM
73* ZONE 3 SHORT CIRCUIT INDICATES ALARM
74* ZONE 4 SHORT CIRCUIT INDICATES ALARM
75* ZONE 5 SHORT CIRCUIT INDICATES ALARM
76* ZONE 6 SHORT CIRCUIT INDICATES ALARM
77* ZONE 7 SHORT CIRCUIT INDICATES ALARM
78* ZONE 8 SHORT CIRCUIT INDICATES ALARM

81* ZONE 1 NON-LATCHING


82* ZONE 2 NON-LATCHING
83* ZONE 3 NON-LATCHING
84* ZONE 4 NON-LATCHING
85* ZONE 5 NON-LATCHING
86* ZONE 6 NON-LATCHING
87* ZONE 7 NON-LATCHING
88* ZONE 8 NON-LATCHING

91 ZONE 1 DOES NOT SOUND ALARMS


92 ZONE 2 DOES NOT SOUND ALARMS
93 ZONE 3 DOES NOT SOUND ALARMS
94 ZONE 4 DOES NOT SOUND ALARMS
95 ZONE 5 DOES NOT SOUND ALARMS
96 ZONE 6 DOES NOT SOUND ALARMS
97 ZONE 7 DOES NOT SOUND ALARMS
98 ZONE 8 DOES NOT SOUND ALARMS
99
A1* ZONE 1 ANY ALARM DELAYED
A2* ZONE 2 ANY ALARM DELAYED
A3* ZONE 3 ANY ALARM DELAYED
A4* ZONE 4 ANY ALARM DELAYED
A5* ZONE 5 ANY ALARM DELAYED
A6* ZONE 6 ANY ALARM DELAYED
A7* ZONE 7 ANY ALARM DELAYED
A8* ZONE 8 ANY ALARM DELAYED

C1 ZONE 1 SOUNDERS INHIBITED


C2 ZONE 2 SOUNDERS INHIBITED
C3 ZONE 3 SOUNDERS INHIBITED
C4 ZONE 4 SOUNDERS INHIBITED
C5 ZONE 5 SOUNDERS INHIBITED
C6 ZONE 6 SOUNDERS INHIBITED
C7 ZONE 7 SOUNDERS INHIBITED
C8 ZONE 8 SOUNDERS INHIBITED

E1* ZONE 1 WILL NOT OPERTATE FIRE RELAY


E2* ZONE 2 WILL NOT OPERTATE FIRE RELAY
E3* ZONE 3 WILL NOT OPERTATE FIRE RELAY
E4* ZONE 4 WILL NOT OPERTATE FIRE RELAY
E5* ZONE 5 WILL NOT OPERTATE FIRE RELAY
E6* ZONE 6 WILL NOT OPERTATE FIRE RELAY
E7* ZONE 7 WILL NOT OPERTATE FIRE RELAY
Extinguishant module 1

Man-1112 Sigma XT+_26 Page 48 of 52


Extinguishant module 1

CONFIGURATION OPTION WRITE SETTING


E x t i n g u i s h a n t o u t p u t mo d e =
A CT I V A T I ON MODE =
Us e r O/ p Mo d e =
F I RS T A CT I V . Z ONE =
L A S T A CT V. Z ONE =
RE S E T I NHI B I T T I ME =
P RE - RE L . DE L A Y T I ME =
E X T I NG. RE L E A S E T I ME =
P UL S E D A CT I V . AL A RMS ?
S T E A DY A CT I V . AL A RMS ?
RE L E A S E D I ND. ON RE L E A S E D I NP UT ?
RE L E A S E D I ND. ON E X T I NG RE L E A S E ?
DE L A Y ON MA NUA L RE L E A S E ?
NO DE L A Y ON MA NUA L RE L E A SE ?
RE L E A S E T I ME R ENA B L E D ?
RE L E A S E T I ME R DI S A B L E D ?
R0 V NOT RE MOV E D ON S Y S T E M RE S E T ?
R0 V RE MOVE D ON SY S T E M RE SE T ?
E A RT H F A UL T E NABL E D ?
E A RHT F A UL T DI ASL A B L E D ?
F A UL T OUT P UT E NAB L E D ?
F A UL T OUT P UT DI SA B L E D ?
L OW P RE S S. I / P NORMA L ?
L OW P RE S S. I / P I NV E RT E D ?
E X T I NG. O/ P 1 L EV E L =
E X T I NG O/ P 2 L EVE L =

Extinguishant module 2

CONFIGURATION OPTION WRITE SETTING


E x t i n g u i s h a n t o u t p u t mo d e =
A CT I V A T I ON MODE =
Us e r O/ p Mo d e =
F I RS T A CT I V . Z ONE =
L A S T A CT V. Z ONE =
RE S E T I NHI B I T T I ME =
P RE - RE L . DE L A Y T I ME =
E X T I NG. RE L E A S E T I ME =
P UL S E D A CT I V . AL A RMS ?
S T E A DY A CT I V . AL A RMS ?
RE L E A S E D I ND. ON RE L E A S E D I NP UT ?
RE L E A S E D I ND. ON E X T I NG RE L E A S E ?
DE L A Y ON MA NUA L RE L E A S E ?
NO DE L A Y ON MA NUA L RE L E A SE ?
P RE - RE L DE L A Y RES E T E NA B L E D ?
P RE - RE L DE L A Y RES E T DI S A BL E D ?
RE L E A S E T I ME R ENA B L E D ?
RE L E A S E T I ME R DI S A B L E D ?
R0 V NOT RE MOV E D ON S Y S T E M RE S E T ?
R0 V RE MOVE D ON SY S T E M RE SE T ?
E A RT H F A UL T E NABL E D ?
E A RHT F A UL T DI ASL A B L E D ?
F A UL T OUT P UT E NAB L E D ?
F A UL T OUT P UT DI SA B L E D ?
L OW P RE S S. I / P NORMA L ?
L OW P RE S S. I / P I NV E RT E D ?
E X T I NG. O/ P 1 L EV E L =
E X T I NG O/ P 2 L EVE L =

Extinguishant module 3
Man-1112 Sigma XT+_26 Page 49 of 52
CONFIGURATION OPTION WRITE SETTING
E x t i n g u i s h a n t o u t p u t mo d e =
A CT I V A T I ON MODE =
Us e r O/ p Mo d e =
F I RS T A CT I V . Z ONE =
L A S T A CT V. Z ONE =
RE S E T I NHI B I T T I ME =
P RE - RE L . DE L A Y T I ME =
E X T I NG. RE L E A S E T I ME =
P UL S E D A CT I V . AL A RMS ?
S T E A DY A CT I V . AL A RMS ?
RE L E A S E D I ND. ON RE L E A S E D I NP UT ?
RE L E A S E D I ND. ON E X T I NG RE L E A S E ?
DE L A Y ON MA NUA L RE L E A S E ?
NO DE L A Y ON MA NUA L RE L E A SE ?
P RE - RE L DE L A Y RES E T E NA B L E D ?
P RE - RE L DE L A Y RES E T DI S A BL E D ?
RE L E A S E T I ME R ENA B L E D ?
RE L E A S E T I ME R DI S A B L E D ?
R0 V NOT RE MOV E D ON S Y S T E M RE S E T ?
R0 V RE MOVE D ON SY S T E M RE SE T ?
E A RT H F A UL T E NABL E D ?
E A RHT F A UL T DI ASL A B L E D ?
F A UL T OUT P UT E NAB L E D ?
F A UL T OUT P UT DI SA B L E D ?
L OW P RE S S. I / P NORMA L ?
L OW P RE S S. I / P I NV E RT E D ?
E X T I NG. O/ P 1 L EV E L =
E X T I NG O/ P 2 L EVE L =

Extinguishant module 4

CONFIGURATION OPTION WRITE SETTING


E x t i n g u i s h a n t o u t p u t mo d e =
A CT I V A T I ON MODE =
Us e r O/ p Mo d e =
F I RS T A CT I V . Z ONE =
L A S T A CT V. Z ONE =
RE S E T I NHI B I T T I ME =
P RE - RE L . DE L A Y T I ME =
E X T I NG. RE L E A S E T I ME =
P UL S E D A CT I V . AL A RMS ?
S T E A DY A CT I V . AL A RMS ?
RE L E A S E D I ND. ON RE L E A S E D I NP UT ?
RE L E A S E D I ND. ON E X T I NG RE L E A S E ?
DE L A Y ON MA NUA L RE L E A S E ?
NO DE L A Y ON MA NUA L RE L E A SE ?
P RE - RE L DE L A Y RES E T E NA B L E D ?
P RE - RE L DE L A Y RES E T DI S A BL E D ?
RE L E A S E T I ME R ENA B L E D ?
RE L E A S E T I ME R DI S A B L E D ?
R0 V NOT RE MOV E D ON S Y S T E M RE S E T ?
R0 V RE MOVE D ON SY S T E M RE SE T ?
E A RT H F A UL T E NABL E D ?
E A RHT F A UL T DI ASL A B L E D ?
F A UL T OUT P UT E NAB L E D ?
F A UL T OUT P UT DI SA B L E D ?
L OW P RE S S. I / P NORMA L ?
L OW P RE S S. I / P I NV E RT E D ?
E X T I NG. O/ P 1 L EV E L =
E X T I NG O/ P 2 L EVE L =

Man-1112 Sigma XT+_26 Page 50 of 52


Man-1112 Sigma XT+_26 Page 51 of 52