Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

Sigma-XT

Conventional
Fire Panel
Extinguishant Control
Operation and
Maintenance Manual

Australia Version 2.51 – Oct 2023


Contents
1. Introduction............................................................................................................................................ 4
2. Mounting ................................................................................................................................................ 4
3. Access Levels .......................................................................................................................................... 5
3.1. Access Levels 1 and 2 ............................................................................................................. 5
3.2. Access Level 3 – Slide Switches ............................................................................................... 5
4. Technical specification ............................................................................................................................. 6
5. FDCIE - Control Panel .............................................................................................................................. 8
6. Connecting to the circuit board ................................................................................................................ 9
7. SIGMA-CP............................................................................................................................................. 10
7.1. Detection zone wiring ........................................................................................................... 10
7.2. Sounder circuit wiring ........................................................................................................... 11
7.3. Connection to remote control terminals (not normally used).................................................... 11
7.4. Aux 24V DC supply ............................................................................................................... 12
7.5. Connection to relay contacts ................................................................................................. 12
7.5.1. Local fire relay ....................................................................................................... 12
7.5.2. Fire relay ............................................................................................................... 12
7.5.3. Fault relay (Alarm Module) ...................................................................................... 12
8. Extinguishant Release Module ................................................................................................................ 13
8.1. Warning Sign and Status Unit Connection .............................................................................. 14
8.1.1. Adding or Removing Status units ............................................................................. 15
8.2. Alternative Configuration of RS485 Circuit. ............................................................................. 15
8.3. Thermal Fuse / Pressure Switch Connection ........................................................................... 16
8.4. Fault relay (Extinguishant Module) ......................................................................................... 16
8.5. First stage alarm relay (Extinguishant Module) ....................................................................... 16
8.6. Second stage alarm relay (Extinguishant Module) ................................................................... 16
8.7. Released relay (Extinguishant Module) ................................................................................... 16
8.8. Aborted relay (Extinguishant Module) .................................................................................... 17
8.9. Extract relay (Extinguishant Module) ...................................................................................... 17
9. Aerosol Releasing Controller .................................................................................................................. 17
9.1. Overview ............................................................................................................................. 17
9.2. Actuator connections ............................................................................................................ 18
9.3. Input connections ................................................................................................................. 18
9.4. Indications ........................................................................................................................... 19
9.5. End of line monitoring: ......................................................................................................... 19
9.6. Fault monitoring links: .......................................................................................................... 19
9.7. Isolate slide switch ............................................................................................................... 20
10. Configuring the panel .................................................................................................................. 21
10.1. Alarm Module ....................................................................................................................... 21
10.2. Alarm Module Codes ............................................................................................................. 21
10.3. Extinguishant Module ............................................................................................................ 23
10.3.1. General Settings ..................................................................................................... 23
10.3.2. Extinguishant Output mode ..................................................................................... 23
10.3.3. Configuring the Activation Mode .............................................................................. 23
10.3.4. User Output Mode .................................................................................................. 23
10.3.5. Configuring the Activation Zones ............................................................................. 24
10.3.6. Reset Inhibit Time .................................................................................................. 24
10.3.7. Pre-Release Delay Time .......................................................................................... 24
10.3.8. Extinguishant Release Time .................................................................................... 25
10.3.9. Second stage alarm - Pulsing/Continuous................................................................. 25
10.3.10. Released Indication ................................................................................................ 25
10.3.11. Delay on manual release ......................................................................................... 25
10.3.12. Pre-Release Delay – Reset/Disable .......................................................................... 26
10.3.13. Release timer (infinite extinguishant duration) ......................................................... 26
10.3.14. R0V Removed on System Reset ............................................................................... 26
10.3.15. Earth Fault Monitoring – Enable/Disable................................................................... 26
10.3.16. Fault Output – Enable/Disable ................................................................................. 26
10.3.17. Low Pressure Switch – Normal/Invert ...................................................................... 27
10.3.18. Release Pressure Switch – Normal/Invert ................................................................. 27
10.3.19. Extinguishant output monitoring levels .................................................................... 28
11. Panel operation – Access levels 1 and 2 ........................................................................................ 28
11.1. Normal condition .................................................................................................................. 28
11.2. Alarm Module – Access level 2............................................................................................... 29
11.2.1. Test mode ............................................................................................................. 29
11.2.2. Disable zones ......................................................................................................... 29
11.2.3. Disable sounder outputs ......................................................................................... 29
11.2.4. Activate delays ....................................................................................................... 30
11.3. Extinguishant modules .......................................................................................................... 30
11.3.1. Extinguishant System Service Isolate ....................................................................... 30
11.3.2. Extinguishant modules – Menu Access ..................................................................... 30
11.3.3. Extinguishant release outputs. ................................................................................ 30
11.3.4. Manual release ....................................................................................................... 30
11.3.5. Disable Stage 1 output ........................................................................................... 31
11.3.6. Disable Stage 2 output ........................................................................................... 31
11.3.7. Disable Released output ......................................................................................... 31
11.3.8. Extract output ........................................................................................................ 31
11.3.9. Select Reserve Solenoid Output (Configuration Option) ............................................. 31
11.4. Single zone Fire condition ..................................................................................................... 32
11.5. Double zone Fire condition .................................................................................................... 32
11.6. Silence/sound alarms ............................................................................................................ 32
11.7. Reset ................................................................................................................................... 33
11.8. Detection Zone fault ............................................................................................................. 33
11.9. Sounder fault ....................................................................................................................... 33
11.10. Other Faults ......................................................................................................................... 33
11.11. Lamp test ............................................................................................................................ 33
11.12. Lock Off condition ................................................................................................................ 34
11.13. Released condition ............................................................................................................... 34
11.14. Low pressure switch ............................................................................................................. 34
11.15. Manual only mode ................................................................................................................ 34
11.16. Manual Release .................................................................................................................... 34
11.17. Abort input........................................................................................................................... 34
12. Internal Controls ......................................................................................................................... 35
12.1. Fire Alarm Module ................................................................................................................ 35
12.1.1. Watchdog reset ...................................................................................................... 35
12.1.2. Processor reset ...................................................................................................... 35
12.1.3. Write enable switch ................................................................................................ 35
12.2. Extinguishant Module ............................................................................................................ 35
12.2.1. Watchdog reset ...................................................................................................... 35
12.2.2. Processor reset ...................................................................................................... 35
12.2.3. Terminate extinguishant ......................................................................................... 35
12.2.4. Address switch ....................................................................................................... 36
13. Watchdog reset switch ................................................................................................................. 36
14. Processor reset switch ................................................................................................................. 36
15. Internal indications – troubleshooting ........................................................................................... 36
15.1. Indicators – Detection and Alarm Panel ................................................................................. 36
15.2. Indicators - Extinguishant modules ........................................................................................ 37
16. Power supply............................................................................................................................... 37
17. Maintenance ................................................................................................................................ 39
18. Zone designation label ................................................................................................................. 39
19. Commissioning instructions and Record of Configuration ................................................................ 39

Sigma_XT_v2.51.docx Page 3 of 44
1. Introduction
The SIGMA XT, and SIGMA XT-A, conventional fire alarm control panel with Extinguishant Control Unit and Aerosol
Agent Controller, is designed to comply with AS7240-2, AS7240-4 Fire Detection and Fire Alarm Systems - Control
and Indicating Equipment, and AS ISO 14520.1 2009 Gaseous Fire Extinguishant Systems.

The control equipment is a combined fire alarm control panel and extinguishant system with up to eight detection
zones, and up to two extinguishant flooding areas. It has an integral, mains powered battery charger and power
supply designed in accordance with the requirements of AS7240-4.

In addition to the requirements of AS7240-2 the control panel has the following facilities:
• Test condition to allow the automatic resetting of zones in alarm for testing purposes. AS7240-2 Section 11
option with requirements.
• Delay of the actioning of fire alarm devices (sounders) so that an alarm may be verified before a premises
is evacuated. AS7240-2 Section 7.11 option with requirements.
• Fire alarm devices to enable an audible warning to be sounded throughout a premises upon the detection of
a fire condition or the operation of a manual call point. AS7240-2 Section 7.8 option with requirements.
• Voltage free relay contacts for fire and local fire which operate upon fire condition. These are to be used for
local control and signalling.

2. Mounting
This product should be installed, commissioned and maintained in accordance with the following:
(i) Local regulations for electrical equipment in buildings
(ii) Codes of practice
(iii) Statutory requirements
(iv) Any instructions specifically advised by the manufacturer

This equipment is designed to be operated from 230V 50Hz mains supplies and is of class 1 construction. As such
it must be connected to earth conductor in the fixed wiring of the installation and a readily accessible double pole
disconnect device which disconnects live and neutral simultaneously shall be incorporated in the fixed wiring.
Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to earth will render
the equipment unsafe.
This control panel is designed for indoor use only and at temperatures between -50C (+/- 3) and +400C (+/-2) and
with a maximum relative humidity of 95%. Standard
panels are rated to IP30 and suitable for mounting
indoors. IP65 is available if required. A rack mount
version is available on special order.
Operation outside of these limits may render the
equipment unsafe.

MOUNTING - The control panel should be mounted on


a dry, flat surface, at eye height to the display and in a
level position such that the enclosure is not distorted.
Suitable fixings of a minimum of 5mm diameter are to be
used at all fixing points such that the control panel is
securely mounted.
It should be positioned in an accessible position as agreed
with the end user. The panel should not be mounted in
another enclosure or near sources of excessive heat.
Cables should be connected using cable glands fitted to
the knockouts. If additional entry points are required, all
swarf and debris caused by drilling of additional cable
entries must be cleared before power is applied to the panel.

DIMENSIONS - H x W x D mm
M3 Cabinet : 520 x 385 x 110 Warning Sign : 195 x 300 x 50 LCS : 135 x 186 x 50
Sigma_XT_v2.51.docx Page 4 of 44
3. Access Levels
For more information on Access Levels, please see Section 11 - Panel operation – Access levels 1 and 2.

3.1. Access Levels 1 and 2


Optional cabinet door has 3 locks:

The centre lock opens the display window,


allowing for operation of the controls.

The display window contains a door


switch. Operation of this door switch
places the panel in Access Level 2.

Door Switch in Access Level 1 Door Switch in Access Level 2


The top and bottom locks will open the complete cabinet front allowing for full access to the panel wiring and
workings. Opening this door only WILL NOT OPERATE THE DOOR SWITCH and will not allow operation of
the controls

3.2. Access Level 3 – Slide Switches


Access Level 3 – Configuration is achieved on each section using “Write Enable” slide switches.

Normal – The Slide To Access Level 3 – move the Slide Access Level 3 – The Slide Switch
Switch is to the Left Switch to the Right is to the Right
CP Control Panel – Zone Detection Portion. Note: A General Fault will occur if the Slide Switch is in the Access
Level 3 position, and the Door Switch is returned to Access Level 1.

XT - Extinguishant Control

Normal – The Slide To Access Level 3 – move the Access Level 3 – The Slide
Switch is to the Right Slide Switch to the Left Switch is to the Left

A “CONFIG WP” Fault will occur if the Slide Switch is in the Access
Level 3 position, and the Door Switch is returned to Access Level 1.

Sigma_XT_v2.51.docx Page 5 of 44
4. Technical specification
Table 1 – Electrical Specifications
Mains supply 230V AC +10% - 15% (100 Watts maximum)
Mains supply fuse 1.6Amp (F1.6A L250V) Replace only with similar type
Power supply rating 3 Amps total including battery charge 28V +/ 2V
Maximum ripple current 1.5 Volts
Output voltage 18.5 to 29V DC +/- 2%
Imax a 400 milliamps
Imax b 2.3 Amps
Imin 0.065A
Battery type (Yuasa NP) Two 12 Volt sealed lead acid (7Ah maximum) See Table 2 for capacities
Battery charge voltage 27.6VDC nominal (temperature compensated) See Table 3
Battery charge current 0.7A maximum
Battery lead fuse 20mm, 3.15A glass Replace only with the same type
Battery high impedance warning (Rimax) 1.35 ohms max
Low battery voltage indication 21V +/- 2%
Low battery shut off voltage 18.5V +/- 2%
Max current draw from batteries 3 Amps With main power disconnected
R0V output Fused with electronic fuse
Dedicated sounder outputs
24V Fused at 500mA with electronic fuse 1.6 Amp total load over all circuits
Zonal sounder outputs
Aux 24V output (detection module) 200 mA max continuous load
Fused at 500mA with electronic fuse
Aux 24V output (Extinguishant module) 18.5 to 30V DC
1.0 Amp total load over all circuits
First and Second stage Sounder output 18 to 30V DC Fused at 1A with electronic fuse
Voltage reversing DC
Fault relay contact rating
Fire relay contact rating 30VDC 1A Amp maximum for each Max ratings not to be exceeded
Local fire relay contact rating
First stage contact rating
5 to 30VDC 1A Amp maximum for each
Second stage contact rating Max ratings not to be exceeded
Volt free changeover contact
Extract contact rating
Zone quiescent current 1.6mA maximum See Table 4 for detector types
Terminal capacity 0.5mm2 to 2.5mm2 solid or stranded wire
Number of detectors per zone > 20 Dependent on type
Number of sounders per circuit Dependent on type and current consumption See Table 6 for sounder types
Detection circuit end of line 6K8 5% ½ Watt resistor
Monitored input end of line 6K8 +/- 5% ½ Watt resistor
Supplied in terminals
Sounder circuit end of line 10K 5% ¼ Watt resistor
Extinguishant output end of line 1N4004 Diode
No. of detection circuits See Table 2 for each model Dependent on model
No. of sounder outputs 2 (plus one per zone on T models)
1 A maximum load –for 5 minutes
Extinguishant release output 18 to 30V DC. Fused at 1 Amp
3 A for 20 milliseconds
Extinguishant release delay Adjustable 0 to 60 seconds (+/- 10%) 5 second steps
Extinguishant release duration Adjustable 60 to 300 seconds 5 second steps
SIL, AL, FLT, RST inputs Switched -ve, max resistance 100 Ohms
Zone normal threshold 8K ohm TO 1K ohm
Detector alarm threshold 999 ohms to 400 ohms
Call point alarm threshold 399 ohms to 100 ohms
Short circuit threshold 99 ohms to 0 ohms
Zener clamp detector base to be
Head removal condition 15.5 to 17.5 volts
used
FP200 or equivalent (maximum capacitance 1uF
Cabling Metal cable glands must be used
maximum inductance 1 millihenry)
Monitored inputs normal threshold
10K ohm to 2K ohm
(Allowable EOL)
Monitored inputs alarm threshold 2K ohms to 150 ohms +/- 5%
Monitored inputs Short circuit threshold 140 ohms to 0 ohms +/- 5%
Status unit/Ancillary board connection Two wire RS485 (EIA-485 specification) Max 7 units per area- RS485 cable.
Status unit power output 18 - 30V DC, Fused 500mA with electronic fuse 250 mA max load. Max 3 modules

Sigma_XT_v2.51.docx Page 6 of 44
Table 2 - Standby battery capacity required for fully loaded system

Panel model 24 hrs standby 48 hrs standby 72 hrs standby Standby current Max panel alarm current
8 Zones 3.75Ah 5.95Ah 8.2Ah 0.093A 0.63A
Table 3 - Battery charge voltage versus temperature
Temp 0C Battery charge voltage
0 29.2
10 28.56
20 27.99
30 27.55
40 27.13
Table 4 – Compatible Detectors

Model Type Manufacturer Maximum Number per zone


SLV-AS OPTICAL HOCHIKI 40
DCD-A HEAT HOCHIKI 40
DCD-C HEAT HOCHIKI 35
DFJ-60B HEAT HOCHIKI 40
DFJ-90D HEAT HOCHIKI 35
DFG-60BLKJ HEAT HOCHIKI 40
DRD-AS FLAME HOCHIKI 25
SPC-AS BEAM HOCHIKI 6
Table 5 – Compatible detector bases and call points

Model Type Manufacturer Comments


YBN-R/4C PLAIN BASE HOCHIKI
YBO-R/4A LED BASE HOCHIKI
YBO-R/6PA LED BASE HOCHIKI

MCP1A-R470SG-P039-01 CALL POINT KAC


MCP1A-R470SF-01 CALL POINT KAC
MCP1B-R470FF-K013-01 CALL POINT KAC SAV-WIRE
STIRPRF01 CALL POINT STI
Table 6 – compatible sounders

Model Type Manufacturer Comments


ROSHNI FULLEON
SQUASHNI FULLEON
SQUASHNI MICRO FULLEON

Sigma_XT_v2.51.docx Page 7 of 44
5. FDCIE - Control Panel

The displays are divided into sections for the Alarm Module and Extinguishant Modules. A standard AS7240-
2 control and indicating equipment section with up to eight zones is located in the top aperture of the panel
and an AS4214 extinguishant module is fitted in the lower aperture.
In addition to the mandatory controls and indications required by the AS7240-2 standard, two seven- segment
LED displays and Mode, Select and Enter buttons are provided to allow easy entry and storage of codes to
configure the control panel to suit the requirements of the installation.

Opening the fascia The fascia of the control panel


is held in place by a screw on the right hand side.
Opening the fascia allows more room when mounting
the cabinet and fitting cables.

AS7240
ALARM Module

AS ISO 14520.1 2009


EXTINGUISHANT Module

Aerosol Releasing
Controller
Mounted in rear of cabinet

Software revision number

Sigma_XT_v2.51.docx Page 8 of 44
C 7 C6
X1
C5 C4 C3 C2 C 1 C 23 C 22 C 21 C 20 C127 C128 C 35 C 36 C 33 C 34 C 60 C 61
X2
C 106 C 107
New features may be added to Sigma CP fire control
panels from time to time and when this is done the

FB7

VDR2
FB21 FB20

FB10
FB8

FB1
FB6

FB5

FB4

FB2
VDR4

FB3

FB9
VDR3 VDR1

C102

C100

C108

C109
C101

C99
C98
F2 C 97 C 93 F 10

operating software of the unit is updated.

C92
F1

F9
R8

R99
C 51

R51
R14 R18
TR 23 TR 19

R12
F4

F3

R60

F12
RL 3 RL 2 RL 1 R2 RL 10 RL 9 Z 11

LED10

LED16

R117

R168
C94
R98
R6
The software revision can be located on the main
D4 F 11
+
C76
R19

R166 R167
TR3

TR1
TR2

LED34
LED12
C 75 C 74 C 73 TR47
D 12

R103
D3 D2 D1 TR9 D 11
R 13 R7 R1

TR26
processor by removing the plate holding the PCB from the

C105

R158

R53 R69
C30

R54 R58 C19


D 35 D 34 D 33 D 32
+ + + + IC 2
R22A R21

R10D R11
R16C R17
R16B R15

R57
R4D R3
R10C R9

R4E R5

LED9
LED11 LED15
C104
R157
R80 R156
R81 C103
C31 R155
C 68 C 67 C 66 C 65 REG1
R16E

enclosure and turning it over.


R16F

R10E

R10B
R10A
R16D

R10F
R16A

R4C
R4B
R4A

R56

R52
R55
R4F
C 24

D20
LED13
D 30
+

R116 C39 C38 C37 C40 C96


R89

J1 R 129 TR 24
D9 IC 4
C45 C44

R 87 D 16 IC 1
XTL1

D 10

LED14
R61
R64

R65
LED8

R63
The software version will have a number such as
R 104

R118
D 15
TR 28 R 126

R128

R102
R137
R 85

C95
TR 25

C55
R112 R67
C83 C81
R113 R62

R109 R66
Sig27. hex D 14
+

R107
REG3
R 86 D 41
IC 6

R110
Jason C 25

“216.hex” and it is this number which will determine


IC 10 R 130 D 13
R 131
+

R88 R111 R114


D 23 VR 1
R 132 Z 14

C43
C 27 L1
R 133 D 22 IC 5
C42 R90

C 82
R 78

which features the panel has installed and its

R74
R73
R71
R72
C 41 R 135
R 134

compatibility with Sigma CP ancillary board, sounders


C 56
T3 SW2 SW1
SW4
SERIAL NUMBER TH 1
+

LED 17 LED 35 LED5


D 1008 ISSUE06
LED4 LED3 LED6 LED7
R 75

R 76 boards, repeaters etc.


R 70

SOFTWARE VERSION LABEL

6. Connecting to the circuit board

Cabling must comply with the Australian Standards. The resistance of any cable must not exceed 25 ohms.
Terminals are capable of accepting wires of up to 2.5mm 2.

Wiring must not go across the front of the circuit board plate or between the plate and the circuit board.

If cable entries need to be in positions other than at the knockouts provided, wiring must be fed behind and well
away from the surface of the circuit board.

The space at the bottom of the enclosure is largely occupied by the batteries so this must be kept in mind when
considering cable entries.

Sigma_XT_v2.51.docx Page 9 of 44
7. SIGMA-CP

7.1. Detection zone wiring


The detection zones provide a nominal 24V DC to power compatible conventional detectors and call points.
The wiring is monitored for open and short circuit fault conditions. The 6K8 end of line monitoring resistors that
are factory fitted to the control panel’s terminals must be removed and placed across the last device that is wired
to the zone circuit.

Wiring can be conventional using standard detector bases (K series), or by the use of special detector bases it is
possible to wire the system such that detection devices and sounders are fitted to the same pair of wires. (T series)

Detection zone circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring
circuit to work correctly.

Polarised sounders may also be wired across the detection zone but in reverse polarity to that shown by the zone
terminals (see figure 5 below). Each zone can be configured individually as a 2-wire type zone or a non 2-wire
type zone using configuration options C1 to C8.

Sigma_XT_v2.51.docx Page 10 of 44
7.2. Sounder circuit wiring
All sounders must be of the polarised type. If non-polarised sounders are used the control panel will permanently
show a fault condition.

Sounder circuits are monitored for open and short circuit faults by placing a 10K end of line monitoring resistor
across the last device on the circuit.

Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring
circuit to work correctly. A maximum of 1.6 Amps is available for powering sounders with a maximum load of 0.41
Amps on any one circuit.

7.3. Connection to remote control terminals (not normally used)


Some functions of the control panel can be controlled externally from the panel if required. Operation of these
inputs must be restricted by an access level 2 control as defined in AS7240-2. These are abbreviated at the
terminals block as follows:
a) Remote 0V supply – R0V
b) Silence Alarm – SIL
c) Sound Alarm – AL
d) Fault – FLT
e) Reset – RST

To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open switch
or contact and via a resistance of no greater than 100 ohms. All of the remote control inputs are non-latching.

Sigma_XT_v2.51.docx Page 11 of 44
7.4. Aux 24V DC supply
An auxiliary 24V DC supply is provided to enable local signalling or control of ancillary systems such as door release
controllers. The terminals for the Aux 24V supply are labelled Aux 24V and ROV. The ROV terminal is the negative
terminal and is the same terminal that should be used to switch the remote control terminals.

It is possible to make the ROV terminal pulsing so that by connecting it to the AL terminal via a remote volt-free
contact, it can be used to pulse the dedicated sounder circuits in response to a signal from another system for
example to give an alert. See programming code 24.

The supply is fitted with an electronic self-resetting fuse to protect the control panel’s 24V supply.

Any standing load on the Aux 24V supply must be taken into account when calculating battery standby times as
standby time will be significantly affected by even modest standing loads. It is recommended that the Aux24V
output is not used to power standing loads and not used to supply loads of greater than 500 milliamps.
Where the Aux 24V supply is used to power electromechanical devices such as relays or door retainers it is
imperative that a suppression diode is fitted across the coil of the electromechanical device to prevent the
generation of high voltage transients back to the control panels power supply.

The Aux 24V DC Supply is not suitable for powering Sigma CP sounder boards or status units.

7.5. Connection to relay contacts


Volt free changeover relay contacts are provided for local control and signalling if required. These contacts are
rated for switching signalling circuits only and the maximum ratings listed in Table 1 MUST not be exceeded.

7.5.1. Local fire relay


The Local Fire Relay will energise upon activation of a fire condition on any of the zones or pressing of the Sound
Alarm Button on the front panel. The relay will remain activated until the alarm is silenced or the panel is reset.
This relay will not operate upon activation of the remote AL input or when a fire condition is triggered on a zone
that is in test mode.

7.5.2. Fire relay


The Fire Relay will energise upon activation of a fire condition on any of the zones. The relay will remain activated
until the control panel is reset. This relay will NOT operate upon activation of the remote AL input. Individual
zones can be configured not to operate the Fire relay by setting configuration options E1 to E8.

7.5.3. Fault relay (Alarm Module)


The Fault Relay is normally energised and will de-energise upon any fault condition on the detection part or the
extinguishant part of the control panel including total loss of power.

Sigma_XT_v2.51.docx Page 12 of 44
8. Extinguishant Release Module

1 24vDC Input from PSU 12 ** Releasing Solenoid 1N4004 Diode

2 PF Input from PSU 13 ** Releasing Solenoid 1N4004 Diode

3 Aux 24vDC Output 14 Remote Manual Release Switch EOL 6K8

4 Fault relay Contact 15 Remote Hold Switch EOL 6K8

5 Stop Air Conditioning 16 Remote Abort Switch EOL 6K8

6 Shutdown Power 17 Remote Auto/Manual Select Switch EOL 6K8

7 Released Relay Contact 18 Exting Release Pressure Switch EOL 6K8

8 Aborted Relay Contact 19 Exting Low Pressure Switch EOL 6K8

9 Extract Fan Power 20 Internal Connection from Panel

10 Ist Stage Sounders EOL 10K 21 Serial data to Status Units

11 2nd Stage Sounders EOL 10K 22 Power to Status Units

** Note output 12 & 13 are unavailable when an Aerosol Releasing Controller is fitted.

Sigma_XT_v2.51.docx Page 13 of 44
8.1. Warning Sign and Status Unit Connection

Each Sign requires BOTH 24v POWER and RS485 connections as shown. MAXIMUM devices 7.

Individual addresses required for each Sign. The address switch is located on the bottom left hand corner of the
status unit. The address is only read when the boards are first powered, so address switches should not be altered
on a system that has power applied, as changes will not be recognised.

ADDRESS 1 2 3 4 5 6 7

VERTICAL SWITCH POSITIONS

Horizontal Switch Positions

Units of the with the same address will cause intermittent faults to be displayed.

Sigma_XT_v2.51.docx Page 14 of 44
8.1.1. Adding or Removing Status units
PANEL SHOULD BE POWERED DOWN before any changes are made to status units. When the system is first
powered on, it will search for connected status units connected to
extinguishant module. If status units are connected correctly and X FAULTS
Enter TO VIEW
detected by the control panel, the LCD will display:

Open the Display Window and Press Enter on the module to which the
status units are connected. Use the “+” button on the module to view STATUS UNIT X
the faults. If status units are detected the LCD will display, X = the FAULT
address of the status unit found.

To accept the status units found, slide the WRITE ENABLE switch,
on the module to which the status units or ancillary boards are STATUS UNIT X
connected to write mode. The LCD will then display, X= the address of Enter TO ACCEPT
the status unit found.

Then press the Enter button, the selected status unit or ancillary board will be added to the system and the next
unit to be added will be displayed. Press the Enter button on the extinguishant module until all of the units have
been accepted then slide the Write Enable switch to enable mode.

All of the status units found module have now been added and disconnection of any of them will be displayed as a
fault on the module and on the detection part of the system. If any
status units are disconnected, a Lock Off activated indication will also REMOTE BUS
be displayed at the extinguishant module and all ancillary boards or FAULT
status units that remain connected. With the Display Window Closed,
the LCD will display:

The Status units which are disconnected will have all their indicators flashing. When additional status units are
added, these will be shown on the LCD when the system is powered up.

8.2. Alternative Configuration of RS485 Circuit.


The Panel is normally configured for one RS485 cable from the panel. It is possible to have 2 separate cables for
the RS485 circuit with the panel effectively in the middle of the circuit rather than at one end.

Where this configuration is required the link LK2 must be removed or positioned over 1 pin only.

PANEL MUST BE POWERED DOWN BEFORE ANY CHANGES TO SIGNS. If process is done with power connected
the is a possibility that a short could occur and damage the panel.

Sigma_XT_v2.51.docx Page 15 of 44
8.3. Thermal Fuse / Pressure Switch Connection
Monitored inputs (Mode select, manual release,
Lock Off, Abort, Released pressure switch and Low
pressure switch) have the same characteristics as
detection zone inputs and require a 6K8 0.5W end
of line monitoring resistor and a nominal, 470 ohm
1 W trigger resistor.

Example of wiring to a monitored input

Connection to Thermal Fuse


The Thermal Fuse allows notification to a
control panel that an Aerosol unit has
activated. It should be installed in
accordance with the instructions included in
the relevant Thermal Fuse document.
Menu setting in the XT card allows for a
normally closed (inverted) input to
be used (10.3.16).

Connect Thermal Fuse to


Rel.P Switch

8.4. Fault relay (Extinguishant Module)


These fault relays are normally energised and will de-energise upon any fault condition on the extinguishant module
or total loss of power. These relays provide individual fault outputs.

8.5. First stage alarm relay (Extinguishant Module)


The First Stage Alarm Relay will operate upon activation of a zone that has been configured to contribute to the
extinguishant release and will de-activate only when the panel has been reset.
This relay will also operate upon activation of the panel mounted or a remote manual release switch. The stage 1
relay output can be disabled at access level 2 via the menus on the Sigma XT module.

8.6. Second stage alarm relay (Extinguishant Module)


The Second Stage Alarm Relay will operate when the panel is in the activated condition (i.e. the release countdown
timer has started) and will de-activate only when the panel has been reset from the released condition.
The stage 2 relay output can be disabled at access level 2 via the menus on the Sigma XT module.

8.7. Released relay (Extinguishant Module)


The Released Relay on the extinguishant module will operate when the module is in the released condition.
The Released output can be disabled at access level 2 via the menus on the Sigma XT module.

Sigma_XT_v2.51.docx Page 16 of 44
8.8. Aborted relay (Extinguishant Module)
The Aborted Relay will operate when the panel is in the aborted condition via an abort switch input.

8.9. Extract relay (Extinguishant Module)


This provides a means to vent a room of extinguishant gases but prevents the gases from being vented during a
discharge. To switch on Extract Relay, pen the display window press Enter .
The LCD will show:
TURN ON
Press “-” until the LCD shows: EXTRACT OUTPUT
Press Enter to turn ON the Extract output and the LCD will show:
TURN OFF
EXTRACT OUTPUT

9. Aerosol Releasing Controller


9.1. Overview

Aerosol Releasing Controller enables connection of actuator devices. Multiple boards can be connected together to
provide control and supervision of up to 40 igniting actuator devices from a single extinguishing control panel
circuit.

Where multiple boards are connected, the system comprises one Master board connected to up to 4 Slave boards.
Releasing Controller provide “Activated” and “Fault” indications. A master “Isolate” control with indication of the
isolated status is also available Master display boards.

All outputs can be isolated such that the system can be tested by observing the “Activated” and “Fault” indications
with no danger of operating the igniting actuators. Isolation can be performed via the slide switch mounted on the
Master Aerosol Releasing Controller board, or a keyswitch mounted to the panel. On activation from the control
panel, the outputs on each controller operate sequentially such that only one pair of actuator outputs are operated
at a time in sequence.

Sigma_XT_v2.51.docx Page 17 of 44
Quick disconnect terminals are provided in 4 groups of 6 for the connection of actuator devices. To connect the
wiring push on the white button on top of the terminal block and insert wire into the aperture making sure that
the wire is pushed to the full depth of the aperture. A firm tug on the wire will confirm that it is seated correctly.

9.2. Actuator connections

Actuator connections Quick disconnect terminals are provided in 4 groups of 6 for the connection of igniting
actuator devices as follows:

A+ = ACUATOR 1+ A+ = ACTUATOR 2+
A- = ACTUATOR 1- A- = ACTUATOR 2-
S = ACTUATOR 1 screen S = ACTUATOR 2 screen

To connect the wiring push on the white button on top of the terminal block and insert wire into the aperture
making sure that the wire is pushed to the full depth of the aperture. A firm tug on the wire will confirm that it is
seated correctly

9.3. Input connections


Standard screw terminal connections are provided for connection of the input cables from an extinguishing
control panel. These are duplicated to allow the extinguishing circuit to be continued on to other devices if
required. A fault will be indicated at the extinguishing control panel if either the trigger input wiring or the 24V
power wiring is disconnected from the board.

Standard screw terminals are provided for the connection of a remote Isolate switch and indicator. Closing a volt
free contact across the ISOL I/P terminals will isolate all outputs.

The Isolated condition can be indicated at a remote location via the ISOL O/P volt free terminals.

Sigma_XT_v2.51.docx Page 18 of 44
To Panel Key switch and indicator

9.4. Indications
Actuator outputs are supervised for circuit faults and a yellow Fault indicator is provided for each of the 4 dual
actuator outputs. This indication is extended to the optional display board.

Activation of each of the 4 dual actuator outputs is indicated by a red Activated indicator which will illuminate as
soon as the output operates and remain illuminated until the triggering extinguishing signal is removed.

The yellow Fault indicator will illuminate along with the red Activated indicator. This indication is extended to the
optional display board. Upon initial power up and after activation Fault LEDs may be illumined for a few seconds
while the system stabilises.

A yellow Isolated indicator is provided which will illuminate upon operation of the onboard Isolate slide switch or
the front panel mounted Isolate keyswitch or the ISOL input at the terminal block on the Master MSA

9.5. End of line monitoring:

All boards are supplied with jumper links fitted at position LK1 in the bottom right hand corner of the PCB. This
jumper should be removed and placed on one pin of the 2 pin header only on all boards except the last one fitted
to the line. If only one board is fitted the jumper can remain in place. This ensures that the ribbon cable
connecting multiple boards is supervised for disconnection and a fault is announced at the extinguishing control
panel.

9.6. Fault monitoring links:

All boards are supplied with LK2 to LK5 fitted. These links must be fitted to allow the actuator outputs to be
supervised. If any of the actuator outputs are not being used the link associated with that actuator output can be
removed and placed on one pin of the 2 pin header only

Sigma_XT_v2.51.docx Page 19 of 44
9.7. Isolate slide switch

As well as the front panel keyswitch connected to the screw terminals, The Master board has a slide switch which
can be used to isolate all outputs.

Operation of the Isolate switch is accompanied by a yellow LED and allows testing to be performed by activating
the control panels releasing output and observing the indicators on the MSA boards illuminating in sequence.

Sigma_XT_v2.51.docx Page 20 of 44
10. Configuring the panel
10.1. Alarm Module
The Alarm Module has 2 or 8 detection zones and has a number of configuration options which can be set at the
time of commissioning to suit the requirements of the installation.

The configuration options are only available at access level 3 which is accessed by operating the Write Enable
switch to the left as shown below. When the panel is at access level 3, the buzzer will “pip” three times every few
seconds as an indication that it is at this access level.

Configuration options are simple to Enter using the codes the table
below. When the control panel is at access level 3, the sub-text of
the Mode and Select buttons is used to Enter a number using tens
(+10) and units (+1).

When the required code number is displayed, pressing the Enter


button will cause the dot on the units seven segment display to
flash. This indicates that a configuration option has been set.

To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1 to A8,
C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set.

10.2. Alarm Module Codes


CODE FUNCTION COMMENTS
00 SOUNDER DELAY TIME = 30 SECONDS
01 SOUNDER DELAY TIME = 1 MINUTE
02 SOUNDER DELAY TIME = 2 MINUTES
03 SOUNDER DELAY TIME = 3 MINUTES Sets the time delay before sounders operate in
04 SOUNDER DELAY TIME = 4 MINUTES combination with configuration codes 31 to 48 and access
05 SOUNDER DELAY TIME = 5 MINUTES level 2 function AD.
06 SOUNDER DELAY TIME = 6 MINUTES
07 SOUNDER DELAY TIME = 7 MINUTES
08 SOUNDER DELAY TIME = 8 MINUTES
09 SOUNDER DELAY TIME = 9 MINUTES
10 COMMON ALARM MODE (default) All sounders operate upon any fire condition
11 TWO-STAGE ALARM MODE Continuous sounders in activated zone, pulsing elsewhere
12 ZONED ALARM MODE Only sounders connected to zone in alarm operate
21* DISABLE FIRE BUZZER Buzzer will not operate on fire condition
22* DISABLE FAULT OUTPUT Fault relay will not operate except upon total power failure
23 DISABLE EARTH FAULT MONITORING Connection of fire alarm wiring will not announce a fault
24 PULSED REMOTE CONTROL OUTPUT Aux 24V supply pulses 1 sec on/1 sec off
25 ENABLE SOUNDERS ON DETECTION CIRCUITS Not used
26 DISABLE FIRE OUTPUT Fire relay will not operate upon any alarm
27 DO NOT CHANGE DO NOT CHANGE
31 ZONE 1 ALARM FROM DETECTOR DELAYED
32 ZONE 2 ALARM FROM DETECTOR DELAYED
33 ZONE 3 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set at options 0-9
34 ZONE 4 ALARM FROM DETECTOR DELAYED when selected zone(s) triggered by detector only.
35 ZONE 5 ALARM FROM DETECTOR DELAYED Note access level 2 function Ad must be set for this to take
36 ZONE 6 ALARM FROM DETECTOR DELAYED effect.
37 ZONE 7 ALARM FROM DETECTOR DELAYED
38 ZONE 8 ALARM FROM DETECTOR DELAYED
41 ZONE 1 ALARM FROM CALL POINT DELAYED

Sigma_XT_v2.51.docx Page 21 of 44
42 ZONE 2 ALARM FROM CALL POINT DELAYED
43 ZONE 3 ALARM FROM CALL POINT DELAYED
Sounder outputs will be delayed by time set at options 0-9
44 ZONE 4 ALARM FROM CALL POINT DELAYED
when selected zone(s) triggered by call point only.
45 ZONE 5 ALARM FROM CALL POINT DELAYED
Note access level 2 function Ad must be set for this to take
46 ZONE 6 ALARM FROM CALL POINT DELAYED
47 ZONE 7 ALARM FROM CALL POINT DELAYED effect.
48 ZONE 8 ALARM FROM CALL POINT DELAYED
51 COINCIDENCE ZONE 1
52 COINCIDENCE ZONE 2
53 COINCIDENCE ZONE 3
54 COINCIDENCE ZONE 4 Zone contributes to ancillary board coincidence O/P. Any
55 COINCIDENCE ZONE 5 number of zones can be selected to contribute.
56 COINCIDENCE ZONE 6
57 COINCIDENCE ZONE 7
58 COINCIDENCE ZONE 8
61 CONFIGURE Z1 FOR I.S BARRIER
62 CONFIGURE Z2 FOR I.S BARRIER
63 CONFIGURE Z3 FOR I.S BARRIER
64 CONFIGURE Z4 FOR I.S BARRIER
Detection threshold changed for use with IS barrier
65 CONFIGURE Z5 FOR I.S BARRIER
66 CONFIGURE Z6 FOR I.S BARRIER
67 CONFIGURE Z7 FOR I.S BARRIER
68 CONFIGURE Z8 FOR I.S BARRIER
71* ZONE 1 SHORT CIRCUIT INDICATES ALARM
72* ZONE 2 SHORT CIRCUIT INDICATES ALARM Changes the trigger threshold of the zone so that the
73* ZONE 3 SHORT CIRCUIT INDICATES ALARM control panel can be used on older systems that had no
74* ZONE 4 SHORT CIRCUIT INDICATES ALARM short circuit monitoring.
75* ZONE 5 SHORT CIRCUIT INDICATES ALARM
76* ZONE 6 SHORT CIRCUIT INDICATES ALARM DOES NOT COMPLY WITH AS7240.2
77* ZONE 7 SHORT CIRCUIT INDICATES ALARM
78* ZONE 8 SHORT CIRCUIT INDICATES ALARM
81* ZONE 1 NON-LATCHING
82* ZONE 2 NON-LATCHING
Sets the zone to self-resetting so can be used to receive
83* ZONE 3 NON-LATCHING
signals from other systems and will reset when input is
84* ZONE 4 NON-LATCHING
removed. Note: Can take up to 20 secs for zone to reset lf
85* ZONE 5 NON-LATCHING
86* ZONE 6 NON-LATCHING
when sounders are operating.
87* ZONE 7 NON-LATCHING DOES NOT COMPLY WITH AS7240.2
88* ZONE 8 NON-LATCHING
91 ZONE 1 DOES NOT SOUND ALARMS
92 ZONE 2 DOES NOT SOUND ALARMS
93 ZONE 3 DOES NOT SOUND ALARMS
94 ZONE 4 DOES NOT SOUND ALARMS Prevents the zone from operating the two common
95 ZONE 5 DOES NOT SOUND ALARMS sounder outputs.
96 ZONE 6 DOES NOT SOUND ALARMS
97 ZONE 7 DOES NOT SOUND ALARMS
98 ZONE 8 DOES NOT SOUND ALARMS
A1* ZONE 1 ANY ALARM DELAYED
A2* ZONE 2 ANY ALARM DELAYED
A3* ZONE 3 ANY ALARM DELAYED Zone needs to be triggered for 30 secs continuously before
A4* ZONE 4 ANY ALARM DELAYED an alarm is generated.
A5* ZONE 5 ANY ALARM DELAYED
A6* ZONE 6 ANY ALARM DELAYED DOES NOT COMPLY WITH AS7240.2
A7* ZONE 7 ANY ALARM DELAYED
A8* ZONE 8 ANY ALARM DELAYED
C1 ZONE 1 SOUNDERS INHIBITED
C2 ZONE 2 SOUNDERS INHIBITED
C3 ZONE 3 SOUNDERS INHIBITED
C4 ZONE 4 SOUNDERS INHIBITED
C5 ZONE 5 SOUNDERS INHIBITED
Not used
C6 ZONE 6 SOUNDERS INHIBITED
C7 ZONE 7 SOUNDERS INHIBITED
C8 ZONE 8 SOUNDERS INHIBITED
E1* ZONE 1 WILL NOT OPERATE FIRE RELAY Enables individual zones to be selected to not operate the
E2* ZONE 2 WILL NOT OPERATE FIRE RELAY fire relay. This is sometimes combined with the non-
E3* ZONE 3 WILL NOT OPERATE FIRE RELAY
E4* ZONE 4 WILL NOT OPERATE FIRE RELAY

Sigma_XT_v2.51.docx Page 22 of 44
E5* ZONE 5 WILL NOT OPERATE FIRE RELAY latching function to prevent ring around on interconnected
E6* ZONE 6 WILL NOT OPERATE FIRE RELAY panels
E7* ZONE 7 WILL NOT OPERATE FIRE RELAY
E8* ZONE 8 WILL NOT OPERATE FIRE RELAY DOES NOT COMPLY WITH AS7240.2

10.3. Extinguishant Module


10.3.1. General Settings
LINKS - The Sigma XT module contains 3 Links.
LK1 CIE Serial Terminator – This terminates the RS485 comms from the control section
LK2 Status Serial Terminator – This terminates the RS485 comms to the Status units and Warning Signs
LK3 PF Input Inversion – Removing this jumper inverts the PF input so that it must be normally
connected to 0V for no fault to be present.

PF INPUT - is used to signal a power failure to the XT Module and id active (power fail mode) when connected to
0V. The function of this input can be inverted by the removal of LK3 on the rear of the board.

LANGUAGE SELECTION - The module is capable of displaying two languages if factory programmed to do so.
The first access level 3 option is to select the local language or the default language (English)
10.3.2. Extinguishant Output mode
The Sigma XT module has two extinguishant outputs. These can be configured to operate together at the same
time (common) or be configured as main and reserve outputs. The factory default setting is common.

To change, open the Display Window and slide the Write Enable switch
EXTING. O/P MODE
the left. Press the Enter button. The LCD will show:
= COMMON

Press the Enter button the LCD will show:


Press the Enter button to select main/reserve.
EXTING O/P MODE
MAIN / RESERVE ?
To save, slide the Write Enable switch to the right. When the
extinguishant module is activated, only extinguishant output 1 will switch on. There will also be an additional menu
item at access level 2 to allow the reserve extinguishant output to be selected.
10.3.3. Configuring the Activation Mode
It is possible to configure the extinguishant modules to be activated by coincidence (any 2 zones in a range of
zones) or a single zone in a range of zones. The activation mode is
factory set to coincidence. ACTIVATION MODE
= COINCIDENCE
To change, open the Display Window and slide the Write Enable switch
to the left. Press the Enter button on the extinguishant module then
press the “+” button. The LCD will show:
ACTIVATION MODE
Press the Enter button The LCD will show: = SINGLE

To save, slide the Write Enable switch to the right.


10.3.4. User Output Mode
The clean contact User output can be programmed to be activated
USER OUTPUT.
either when a First Stage Alarm occurs, or the Hold Input is activated.
= STAGE 1
It is usual for this relay to be used as a First Stage Alarm.

To change this, open the Display Window and slide the Write Enable
switch to the left. Press the Enter button then press the “+” button. USER OUTPUT.
= HOLD
Press the Enter button The LCD will show:

Sigma_XT_v2.51.docx Page 23 of 44
The OUTPUT is now set to HOLD. If the Enter button is pressed again
The LCD will show: USER OUTPUT.
STAGE 1 ?

Press the Enter button and the LCD will show. The output is now set to
Stage 1
USER OUTPUT.
STAGE 1
To save the settings, slide the Write Enable switch gently to the right.
Operation of either a STAGE 1 alarm or the HOLD input, as set above,
will result in the activation of the User Output relay.
10.3.5. Configuring the Activation Zones
The extinguishant modules are factory set to be activated by coincidence activation.

This means that on an 8 zone, 4 extinguishant area panel for instance, zones 1 and 2 will be set to activate the
extinguishant module at address 1, zones 3 and 4 will be set to activate the extinguishant module at address 2 and
so on. This can be changed if required so that any zones can activate the extinguishant module.

To change, open the Display Window and slide the Write Enable switch to the left. Press the Enter button on the
extinguishant module and then the “+” button until the display shows, X will
be the number of the zone selected to be the first activation zone. FIRST ACTIV.
To change use the “+” and “-” buttons to ZONE = X
FIRST ACTIV. select the required zone number. When
ZONE = X ? the required zone is displayed, press the Enter button. The display will show
the first activation zone.
Press the Enter button and then the “+” button. The display will then show,
X will be the last activation zone. LAST ACTIV.
ZONE = X
LAST ACTIV. To change use the “+” and “-” buttons
ZONE = X ? to select the require zone number.
When the required zone is displayed, press the Enter button.

10.3.6. Reset Inhibit Time


This setting can be used to inhibit the reset of the system after it has been
activated until there is a signal representing the end of the discharge (a RESET INHIBIT
released input) or for an adjustable time period of up to 30 minutes. The TIME = 0 ?
factory default for the reset inhibit time is 0.
RESET INHIBIT
To change, open the Display Window and slide the Write Enable switch to TIME = 0
the left. Press the Enter button on the extinguishant module then press the
“+” button until the display shows:

Press the Enter button and the display shows. To change, press the “+” or “-” buttons until the time required is
displayed and then press Enter. To save, slide the Write Enable switch to the right.
10.3.7. Pre-Release Delay Time
This setting allows for a time delay to be set from activation of the extinguishant module to operation of the
extinguishant release output. This time may be between 0 and 30 seconds with a maximum of 5 second steps.
The factory default time delay on the Sigma XT extinguishant modules is 30
seconds. PRE-REL DELAY
TIME = 30 SEC
To change, open the Display window and slide the Write Enable switch to the
left. Press the Enter button on the extinguishant module then press the “+” button until the display shows:
Press the Enter button and the display will show. To change, press the “+”
or “-” buttons until the time required is displayed and then press Enter. PRE-REL DELAY
TIME = 30 ?
To save, slide the Write Enable switch to the right.

Sigma_XT_v2.51.docx Page 24 of 44
10.3.8. Extinguishant Release Time
The time that the extinguishant output is active for can be set between 60 and 300 seconds. The factory default
time for this is 60 seconds. It is also possible to disable this timer such that the extinguishant outputs remain
active until the module is reset. See Release timer menu option section 10.3.13.

To change the Extinguishant Release Time, open the Display Window and
EXTING. RELEASE
slide the Write Enable switch to the left. Press the Enter button then press TIME = 60 SEC
the “+” button until the display shows:

Press the Enter button and the display will show. To change, press the “+”
EXTING. RELEASE
or “-” buttons until the time required is shown then press Enter. TIME = 60 ?

To save, slide the Write Enable switch to the right.


10.3.9. Second stage alarm - Pulsing/Continuous
The Second Stage Alarm Output can be configured to be steady or pulsing at about 1 second on, 1 second off to
suit the desired application. The factory default for the second stage alarm is pulsing.

To change, open the Display Window and slide the Write Enable switch to the
left. Press the Enter button on the extinguishant module then press the “+” PULSED
ACTIV. ALARMS
button until the display shows:

To change to steady second stage alarms, press Enter . To save, slide the
Write Enable switch to the right. STEADY
ACTIV. ALARMS ?

The Second Stage Alarm Output will now be steady when the module is
activated. This MUST be set to STEADY when using output for a system Shutdown
10.3.10. Released Indication
It is possible to select whether the released indication on a module is operated at the same time as the extinguishant
release outputs operate or by operation of a pressure switch connected to the released, pressure switch input.

The factory default setting is for the released indication to be operated by


RELEASE IND ON
operation of a pressure switch connected to the pressure switch input. RELEASED INPUT

To change, open the Display Window and slide the Write Enable switch on the
module to be configured gently to the right. Press the Enter button on the
RELEASED IND ON
extinguishant module then press the “+” button until the display shows: EXTING. REL ?

To change press Enter . To save, slide the Write Enable switch to the right.
10.3.11. Delay on manual release
The factory default setting for this is for the manual release to have a delay
DELAY ON
time the same as the pre-release delay.
MANUAL RELEASE

To change to have no delay when a manual release is operated, open the Display Window and slide the Write
Enable switch to the left. Press the Enter button on the extinguishant module
then press the “+” button until the display shows: NO DELAY ON
MANUAL RELEASE ?

Press the Enter button and the display will show. To change press Enter.

To save, slide the Write Enable switch to the right. Operation of a manual release will now operate the extinguishant
outputs immediately with no delay.

Sigma_XT_v2.51.docx Page 25 of 44
10.3.12. Pre-Release Delay – Reset/Disable
Once activated, an extinguishant module cannot be reset until after the reset inhibit time has expired and the
extinguishant release timer has expired. It is possible to configure the module such that it can be reset during the
pre-release delay.

Open the Display Window and slide the Write Enable switch, on the module to be configured, gently to the left.
Press the Enter button on the extinguishant module then press the “+”
button until the display shows: PRE-RELEASE DELAY
RESET DISABLED

Press the Enter button to change press Enter.


To save, slide the Write Enable switch to the right. It will now be possible
to reset the module during the pre-release delay but not while the PRE-RELEASE DELAY
extinguishant outputs have operated until after the expiry on the reset RESET ENABLED
inhibit time.

Note: Disabling the Pre-release delay reset may not comply with the requirements of Australian Standards.
10.3.13. Release timer (infinite extinguishant duration)
The release timer can be disabled such that once the extinguishant outputs have operated; they remain operated
until the system is reset.
To disable, open the Display Window and slide the Write Enable switch RELEASE TIMER
on the module to be configured gently to the left. Press the Enter button ENABLED
then press the “-” button until the display shows:
RELEASE TIMER
Press the Enter button to change to this. To save, slide the Write Enable DISABLED ?
switch to the right. With the release timer disabled, the extinguishant
outputs will remain operated until the system is reset.
10.3.14. R0V Removed on System Reset
This setting should not be changed, and should never be set.
10.3.15. Earth Fault Monitoring – Enable/Disable
The factory default setting is for the earth fault monitoring facility to be enabled.

To disable the earth fault monitoring, open the Display Window and slide
the Write Enable switch to the left. Press the Enter button on the EARTH FAULT
extinguishant module then press the “-” button until the display shows: ENABLED

Press the Enter button to change to this. To save the settings, slide the
Write Enable switch to the right. EARTH FAULT
DISABLED ?
Once disabled, the Aux 24V output will be removed for a few seconds
when the reset button is pressed.
10.3.16. Fault Output – Enable/Disable
The factory default setting is for the fault output relay to be enabled.
FAULT OUTPUT
ENABLED
Open the Display Window and slide the Write Enable switch to the left.
Press the Enter button then press the “-” button until the display shows:

Press the Enter button to change. To save, slide the Write Enable switch.
The fault output relay on the module will now be disabled. FAULT OUTPUT
DISABLED ?

Note: Disabling the fault output does not comply with the requirements
of AS7240-2.

Sigma_XT_v2.51.docx Page 26 of 44
10.3.17. Low Pressure Switch – Normal/Invert
To enable low pressure switches to be used which have normally closed rather than normally open contacts, it is
possible to invert the input. The default setting is for the low pressure switch input to use a normally open contact.

To invert the low pressure switch input, open the Display Window and
slide the Write Enable switch to the left. Press the Enter button on the LOW PRESS I/P
extinguishant module then press the “-” button until the display shows: MODE = NORMAL

Press the Enter button to change to this.


LOW PRESS. I/P
MODE = INVERTED ?
To save, slide the Write Enable switch to the right. The low pressure
switch input will now require a normally closed contact via a 470R
trigger resistor and 6K8 end of line resistor for correct supervision.
10.3.18. Release Pressure Switch – Normal/Invert
To enable released pressure switches to be used which have normally closed rather than normally open contacts,
it is possible to invert the released pressure switch input. The factory default setting is for the pressure switch
input to use a normally open contact.
RELEASED INPUT
To invert, open the Display Window and slide the Write Enable switch to MODE = NORMAL
the left. Press the Enter button on the extinguishant module then press
the “-” button until the display shows:
Press the Enter button to change to this.
RELEASED INPUT
The released pressure switch input needs to be disconnected to bring it MODE – INVERTED ?
into fault before changing from Normal to Inverted or back in order to
prevent the input from activating.

To save, slide the Write Enable switch to the right. The released pressure switch input will now require a normally
closed contact via a 470R trigger resistor and 6K8 end of line resistor for correct supervision.

Sigma_XT_v2.51.docx Page 27 of 44
10.3.19. Extinguishant output monitoring levels
The extinguishant outputs are able to monitor both solenoid and igniting actuator releasing devices. This requires
that the outputs be calibrated with the releasing device and the cable to it, fitted as it will be in the working system.

The extinguishant outputs are normally fitted with a 1N4004 diode at the factory and the default monitoring level
will be set at approximately 206 but may be between 204 and 208.

If the parameters of the extinguishant change e.g. by replacing an actuator, then the extinguishant output
monitoring level will need to be “learned”.

Before calibrating the extinguishant outputs ensure that the releasing device are fitted

To calibrating, enable access level 2 and slide the Write Enable switch to ACCESS LEVEL 2
the left. Enter for MENU

Press the Enter button on the extinguishant module then press the “+” button until the display shows:

EXTING. O/P 1
The XXX here will be the actual monitoring level read by the module. To LEVEL = XXX ?
save this setting press the Enter button.

To set the monitoring level for extinguishant output 1, Press Enter button accept the monitoring level.

Press the Enter button and the display will show:


EXTING. O/P 2
LEVEL = XXX ?
The XXX here will be the actual monitoring level read by the module. To
save this setting press the Enter button.

To save, slide the Write Enable switch to the right.

NOTE: Value of 255 means that the output is OPEN CIRCUIT. This must be corrected and the circuit re-calibrated.

11. Panel operation – Access levels 1 and 2


11.1. Normal condition
Under normal conditions and with all modules in Manual & Auto mode, control panels will have only the green,
Power On LED lit on the Sigma XT detection part and on each of the
extinguishing modules. AUTO & MANUAL

With the display window closed, the display on the detection part of the
panel will be blank and, the LCDs on the extinguishing modules will show:

Any modules that are in Manual Only mode with have an additional,
Manual Only yellow LED lit and their display will show: MANUAL MODE

The Manual Only LED on the module or ECU/LCS which placed the system in manual mode will be flashing.

The control panel has 3 access levels.


• Access level 1 is available at all times and allows operation of the Alarm/Fault Warning Silence and Lamp
Test buttons on the detection part of the panel only.
• Access level 2 is enabled after opening the display window.

Sigma_XT_v2.51.docx Page 28 of 44
• Access level 3 allows configuration options to be set on both the detection part of the panel and the
extinguishant modules following operation of their respective Write Enable switches at access level 2 (the
display window is open).

When the display window is open (Access level 2) the display on the ACCESS LEVEL 2
MANUAL MODE
detection part of the control panel will show and the LCDs on the
extinguishing modules will show:

11.2. Alarm Module – Access level 2.


11.2.1. Test mode
It is possible to put one or more zones into Test mode. When a zone is in test mode it will self-reset after a few
seconds. This enables the system to be tested without having to return to the control panel to reset between each
device activation on the zone that is being tested.
To put a zone into test mode, open the Display Window.

The 7 segment display will show


(test zone 1). To put zone 1 into test mode, press the Enter button on the Sigma XT detection part.

The display will now show a flashing dot next to the and the yellow Test LED will be lit.

To select further zones to put into test mode, press the Select button and then the Enter button so that the flashing
dot appears next to the selected display e.g.

To remove test mode from a zone, press the Select button to reveal any zones that have a flashing dot and then
press the Enter button to take that zone out of test mode. Once all zones have been taken out of test mode, the
yellow, Test LED will go off.
11.2.2. Disable zones
It is possible to disable one or more zones. When a zone is disabled it will not report fire or fault conditions. This
enables the system to be worked on without false fire or fault conditions being announced.

To disable one or more zones, open the Display Window. The 7-segment display will show (test zone 1)

Press the Mode button and the display will show . To disable zone 1 press the Enter button. The display will
show and the yellow Disablement LED will be lit.

To select further zones to disable, press the Select button and then the Enter button so that the flashing dot
appears next to the selected display e.g.

To remove disablements, press the Select button to reveal any zones that have a flashing dot next to the displayed
zone number and then press the Enter button. Once all zones have been enabled, the yellow, Disabled LED will
go off.
11.2.3. Disable sounder outputs
The sounder outputs on the detection part of the panel can be disabled if required.
To disable the panel sounder outputs, open the Display Window.

The 7 segment display will show (test zone 1). Press the Mode button until the display shows

Press the Enter button. The display will now show the yellow Disablement and Sounder Fault LEDs will be lit.
To enable the sounder outputs, press the Mode button while at Access level 2 and scroll with the mode button until
is displayed. Press the Enter button. The display will change to and the Sounder Fault and Disablement
LEDs will go OFF if there are no other disablements active on the panel.

Sigma_XT_v2.51.docx Page 29 of 44
11.2.4. Activate delays
It is possible to set delays before sounder outputs will operate (see section 10.1). Before these time delays become
effective it is necessary to turn on the Activate Delays function.

To do this, open the Display Window. The 7 segment display will show (test zone 1)
Press the Mode button until the display shows . Press the Enter button, the display will now show and the
yellow Alarm Delay and Disablement LEDs will be lit.

To switch off the delay, press the Mode button while at Access level 2 (Display Window open) and scroll with the
Mode button until is displayed. Press the Enter button. The display will change to and the Alarm Delay
and Disablement LEDs will go off if there are no other disablements active on the panel.

11.3. Extinguishant modules


11.3.1. Extinguishant System Service Isolate
An Extinguishant System Service Isolate keyswitch is provided on each risk and prevents of firing line to the
extinguishant solenoid or detonator.

This minimises the chance of an accidental release of the extinguishant during testing or maintenance, thus allowing
the system to be fully functionally tested.

Turning the Extinguishant System Service Isolate keyswitch clockwise will isolate the extinguishant circuit, and a
fault is generated and the Service Isolated LED is lit.
11.3.2. Extinguishant modules – Menu Access
With the Display Window open, all extinguishant modules will display:
ACCESS LEVEL 2
ENTER FOR MENU

11.3.3. Extinguishant release outputs.


Extinguishant release outputs, press the “+” button on the module
while at access level 2. The display will show: DISABLE
EXTING. RELEASE ?

Press the Enter button to select this function. The display will show
Disabled and the Disabled LED will be lit.

ENABLE
Close the Display Window to leave the disablement active. EXTING. RELEASE ?

11.3.4. Manual release


Manual release inputs (front panel mounted and remotely connected),
press the “+” button on the module while at access level 2 until the DISABLE
MANUAL RELEASE ?
module displays:

Press the Enter button to select this function. The LCD shows Disabled
and the Disabled LED will be lit. ENABLE
MANUAL RELEASE ?

Close the Display Window to leave the disablement active.

Sigma_XT_v2.51.docx Page 30 of 44
11.3.5. Disable Stage 1 output
To disable the First Stage relay output, press the “+” button on the
module while at access level 2 until the display shows: DISABLE
STAGE 1 OUTPUT ?

Press the Enter button to select this function. The display will show and
the yellow Disabled LED will be lit.
ENABLE
Close the Display Window to leave the disablement active. STAGE 1 OUTPUT ?

11.3.6. Disable Stage 2 output


To disable the Second Stage relay output, press the “+” button on the DISABLE
module while at access level 2 until the display shows: STAGE 2 OUTPUT ?

Press the Enter button to select this function. The LCD will show and
the yellow Disabled LED will be lit. ENABLE
STAGE 2 OUTPUT ?
Close the Display Window to leave the disablement active.

11.3.7. Disable Released output


To disable the Released relay output, press the “+” button on the
module while at access level 2 until the display shows: DISABLE1
RELEASED OUTPUT ?

Press the Enter button to select this function. The LCD will show and
the yellow Disabled LED will be lit.
ENABLE
RELEASED OUTPUT ?
Close the Display Window to leave the disablement active

11.3.8. Extract output


To disable Extract relay output, press the “+” button on the module while at
DISABLE
access level 2 until the display shows: EXTRACT OUTPUT ?

Press the Enter button to select this function. The LCD will show and the yellow
Disabled LED will be lit. ENABLE
EXTRACT OUTPUT ?
Close the Display Window to leave the disablement active.

To turn on the extract relay output, press the “-” button on the module while TURN ON
at access level 2 until the display shows: EXTRACT OUTPUT ?

Press Enter to turn ON the Extract output. The display will show. Pressing
Enter again will turn OFF the Extract output TURN OFF
EXTRACT OUTPUT ?
Close the Display Window to leave the Extract output active Note: the extract
output does not turn off when the module is reset.
11.3.9. Select Reserve Solenoid Output (Configuration Option)
If the extinguishing module is configured for Main/Reserve solenoid operation (See section 15.2.1) then an
additional menu option is given to select which output is used.
SELECT RESERVE
EXTING. OUTPUT

Sigma_XT_v2.51.docx Page 31 of 44
To turn on the Reserve Solenoid output, press the “+” button on the module
while at access level 2 until the display shows:
SELECT MAIN
EXTING. OUTPUT ?
Press the Enter button to select this function. The display will show:
The yellow Reserve Cylinders LED indicator on the module will be lit.

Note: This menu option is not shown if the panel is configured to Common Solenoid mode.

11.4. Single zone Fire condition


Upon receipt of a fire condition by activation of a detector or call point, the Common Fire indicator on the detection
section will light, the fire buzzer will sound and the zonal Fire indicator(s) will flash at around 2Hz.

The fire and local fire relays will also operate and signal any systems to which they are connected.
Any sounders connected to the sounder circuits S1 & S2 on the detection section will operate. These sounders
may be silenced by operation of the silence alarm button with the enable keyswitch operated such that the panel
is at access level 2.

If the zone that has activated is contributing to the extinguishant release sequence on an extinguishant module
and the module is configured for coincidence activation, the Activated LED on
the module will flash, the First Stage relay contact will operate, the First Stage
PREACTIVATED
sounder output will operate and the display will show:

Pressing the Silence Alarm button on the detection section will turn off the sounder outputs on the detection section
and the First Stage Alarm outputs on the extinguishant module.

11.5. Double zone Fire condition


Upon receipt of a second fire condition that contributes to extinguishant release on modules that are switched to
Automatic and Manual mode with their Lock Off inputs not active and the Disable Extinguishant function has not
been invoked, the detection section will respond as above and extinguishant modules will respond as listed below:

a) The second stage alarm output will operate. (Sounder circuit S3)
b) The Second stage contact will operate.
c) The Activated indicator will operate
d) The display will indicate ACTIVATED and show the time remaining until release in seconds.
e) The extinguishant output will operate after the configured delay time and for the configured duration.
f) The display will show ACTIVATED DISCHARGING for the duration of the release time.

When detection zones have activated and the activated condition is reached (i.e. the Activated indicator is lit) it
shall not be possible to reset the extinguishant section of the panel until the Reset Inhibit timer has elapsed.

11.6. Silence/sound alarms


The Silence/Sound alarm button can only be operated at access level 2. (Enable Control keyswitch operated).

To silence the sounders, insert the Enable Control key, turn to the right and press the Silence/Sound alarm button.
When the sounders have been silenced, the Zone Fire LEDs will change from flashing to a steady state.

Pressing the Silence/Sound alarm button whilst the control panel is in this silenced condition will cause the sounders
to operate again.

The sounders can be toggled on and off with the Silence/Sound alarm button as required.

Sigma_XT_v2.51.docx Page 32 of 44
11.7. Reset
To reset the panel, operate the Enable Control keyswitch, then press the Reset button.

The extinguishant section will reset only after the Reset Inhibit timer has expired once the activated condition has
been established.

11.8. Detection Zone fault


Removal of a detector from its base or a fault on any of the zone wiring will cause the Fault LED and Zone Fault
LEDs to flash, indicating the zone in which the fault has occurred.

11.9. Sounder fault


A fault on the wiring to the detection section sounder circuits will cause the Fault LED to light and the Sounder
Fault LED to flash.
A fault on the sounder circuits of extinguishant modules (alarm devices as required by AS7240-1) will light the Fault
LED on the detection section and on the extinguishant module.

The extinguishant module will display:


STAGE 2 ALARMS
STAGE 1 ALARMS
or FAULT
FAULT

11.10. Other Faults


POWER - Failure of the mains power or disconnection of the standby battery will cause the Fault and Power Fault
LEDs to light on the detection section indicating an abnormality in the power supply to the
control panel. There will be no indication of this condition on the extinguishant modules.
Power fault is non-latching and will automatically reset once the fault has been rectified.

SYSTEM FAULT – DETECTION MODULE - The System Fault and general fault LEDs will light if the configuration
memory has not been set or has become corrupted. System fault is non-latching and will
automatically reset once the configuration has been rectified.

SYSTEM FAULT – EXTINGUISING MODULE - The System Fault and general fault LEDs will light if the
configuration memory has not been set or has become corrupted. System fault is non-latching
and will automatically reset once the configuration has been rectified.

GENERAL FAULT - The General fault LED will be illuminate under any fault condition. This LED will also light if
the Write Enable switch has been left on and the system is in Access Level 1.

CONFIG WP FAULT – EXTINGUISHING MODULE - The Write Enable switch on the Extinguishant Module has
been left in the access level 3 position and the system is in Access Level 1.

11.11. Lamp test


All LED indicators on the panel can be tested at any time by pressing the Lamp Test button on the Detection part.
Indicators on individual extinguishant modules can be lamp tested by holding down the Exit button for more than
2 seconds.

Sigma_XT_v2.51.docx Page 33 of 44
11.12. Lock Off condition
Activation of the Lock Off input or a fault on the monitored wiring of the Lock Off circuit on a module or at a
remotely mounted status unit will cause the Lock Off Activated indicator to light on the module and on any status
units or ancillary boards connected to it.

If the extinguishant module is in the Activated condition and the pre-release timer is running then the extinguishant
release sequence will be halted and the pulsing, Second stage sounders shall change to 1 second on, 2 seconds
off.
Release of the Lock Off input will re-start the pre-release timer from maximum.

11.13. Released condition


The released pressure switch input will be connected to a pressure switch mounted on the extinguishant cylinder
which operates when the extinguishant has been released. This will activate the released indicator on the control
panel.

If the extinguishant has been released by mechanical means i.e. the control panel is not in the activated condition,
operation of the released pressure switch input will establish the Released condition. (See also 15.2.8)

11.14. Low pressure switch


The low pressure switch input will be connected to a pressure switch on the extinguishant cylinder which will
operate if the pressure in the cylinder falls below a set point.

This will happen after the extinguishant has been released but may happen before release through a leak. The
fault LED on the module and on the detection part will light and the buzzer will sound when this input is operated.

11.15. Manual only mode


The mode of the system can be toggled between Manual Only and Automatic & Manual by operating the Mode
Select pushbutton on the modules.
The safety cap must be lifted upwards before the pushbutton can be operated.

When a module is in Manual Only mode, the extinguishant cannot be released by the operation of automatic
detectors.

The mode can also be changed to manual by the external mode select input or a Mode Select pushbutton on a
status unit. Any mode select input that is switched to Manual only mode will override any modules switched to
Automatic and Manual mode. All inputs must be switched to Manual and Automatic mode for a module to be in
Automatic and Manual mode.

11.16. Manual Release


Extinguishant modules may be activated by Manual release inputs via the manual release control on the front of
each module, a remotely mounted Manual release control connected the monitored manual release inputs or by a
manual release control mounted on a status unit.

Activation of any of these Manual release controls will immediately activate the extinguishant module and begin
the pre-release timer if the module is configured to have a time delay for Manual release inputs.

11.17. Abort input


Each module has the facility for connection of an Abort control. Operation of the Abort input or a fault on the
monitored wiring of the Abort circuit during the pre-release delay time or before activation will light the Abort
indicator on the module and the extinguishant release timer will be cancelled i.e. the extinguishant will not be
released. The module can be immediately reset from this condition.

Sigma_XT_v2.51.docx Page 34 of 44
12. Internal Controls
12.1. Fire Alarm Module
12.1.1. Watchdog reset
If for any reason the microprocessor in the Fire Alarm Module of the control panel fails to carry out its operation
correctly it will attempt to restart. This process is called a “watchdog” and the control panel must record and
indicate these events.

If a watchdog event occurs, the fire alarm module will show the Fault and System Fault LEDs on the front panel,
the CPU fault LED inside the panel will light and the buzzer will sound. This fault can only be cleared by pressing
the Watchdog Reset button on the PCB inside the control panel. The control panel buzzer will continue to sound
until the watchdog activation is reset.
12.1.2. Processor reset
Once started, the microprocessor controlling the fire alarm module of the panel should continue to run continuously
without interruption. If the microprocessor fails to run correctly it can be reset by pressing the Processor Reset
button on the PCB inside the control panel.

This should not normally be necessary but should be done as a matter of course if the system is behaving
abnormally. The system should resume normal operation within a couple of seconds of pressing the processor
reset button. It will be necessary to press the Watchdog Reset button a few seconds after pressing the Processor
Reset button to clear the Watchdog indication and buzzer.
12.1.3. Write enable switch
To protect the configuration memory of the panel while it is running normally the Write
Enable switch is provided.

The memory Write Enable switch must be switched on before any changes can be made
to the configuration. The Write Enable switch is quite fragile and should be operated
with care.

12.2. Extinguishant Module


12.2.1. Watchdog reset
If the microprocessor on an extinguishant module fails to carry out its operation correctly it will attempt to restart.

If a watchdog event occurs, the Extinguishant module will show Fault and System Fault LEDs on the front panel,
the detection part of the panel will show a fault and the buzzer will sound and the display on the Extinguishant
module will show CPU fault.

This fault can only be cleared by pressing the Watchdog Reset button on the Extinguishant module. The control
panel buzzer will continue to sound until the watchdog activation is reset.
12.2.2. Processor reset
If the microprocessor on an Extinguishant module fails to run correctly it can be reset by pressing the Processor
Reset button on the PCB inside the control panel.

This should not normally be necessary but should be done as a matter of course if the system is behaving
abnormally. The system should resume normal operation within a couple of seconds of pressing the processor
reset button.
12.2.3. Terminate extinguishant
Once the extinguishant outputs have been operated they cannot be switched off until after the reset inhibit timer
has elapsed. For test purposes a terminate extinguishant button is provided which will terminate operation of the
extinguishant outputs and allow the system to be reset.

Sigma_XT_v2.51.docx Page 35 of 44
12.2.4. Address switch
Extinguishant modules are connected to the serial bus of the Sigma XT detection part of the control panel
and each module must be allocated an address between 1 and 7 using the binary coded DIP
switch.
Term. Exting. Proc. Reset W/dog Reset Address Write Enable

13. Watchdog reset switch


If for any reason the microprocessor in the control panel fails to carry out its operation correctly it will attempt to
restart itself. This process is called a “watchdog” and the control panel must record and indicate these events.

If a watchdog event occurs, the control panel will show the Fault and System Fault LEDs on the front panel, the
CPU Fault LED inside the panel.

This fault can only be cleared by pressing the Watchdog Reset button on the PCB inside the control panel. The
control panel buzzer cannot be silenced and will continue to sound until the watchdog activation is reset.

14. Processor reset switch


Once started, the microprocessor controlling the panel should continue to run continuously without interruption. If
the microprocessor fails to run correctly it can be reset by pressing the Processor Reset button on the PCB inside
the control panel.

This should not normally be necessary but should be done as a matter of course if the system is behaving
abnormally. The system should resume normal operation within a couple of seconds of pressing the Processor
Reset button. Note: A Watchdog Reset should always be performed following a Processor Reset.

15. Internal indications – troubleshooting


15.1. Indicators – Detection and Alarm Panel
MAINS FAIL - Indicates that the 230V AC supply is not present and the system is running on standby batteries.
If there is not a power cut, check the panels mains fuse.

BATT FAIL - Indicates that the standby battery has become disconnected or that the charging circuit of the control
panel has a high resistance or has failed. Check that both batteries are connected and linked together. Test the
battery. Disconnect the battery and ensure that 28 Volts can be measured on battery charger leads.

CPU FAULT - Indicates that the central processor unit has failed to correctly execute code and has been re-started
by the system watchdog. The Watchdog Reset switch must be pressed to clear the CPU Fault condition. If system
does not return to normal after the Watchdog Reset switch is pressed then the panel is probably damaged and the
circuit board needs replacing.

AUX 24V FAULT - The Aux 24V and R0V terminals provide a 500 milliamp, 24V DC power supply for power fire
alarm ancillary equipment. This LED indicates that fuse protecting the R0V output has operated and the rating of
this output has been exceeded. The fuse is a self-resetting type and the supply will resume when the fault condition
is removed.

BATT LOW - Illuminates when the system is running on batteries and the battery voltage is lower than 21V +/-
2% (the minimum battery voltage).

COMMS FAULT - Indicates that communication has been lost with an extinguishant module, repeater panel or
ancillary board. Check for comms fault at all extinguishant modules, repeaters and ancillary boards to identify the
source of the problem.

Sigma_XT_v2.51.docx Page 36 of 44
EARTH FAULT - Indicates that part of the system wiring is connected to earth. Remove all system wiring and re-
connect cables one at a time until the earth fault returns. This will indicate which cable the earth fault is present
on.

SYS FUSE FAULT - Indicates that the total power rating of the power supply has been exceeded and that the
system fuse has come into operation. Remove and review all loads and re-connect one at a time until over rated
circuit trips fuse to identify troublesome circuit.

S1 FAULT and S2 FAULT - Indicates a short or open circuit on sounder outputs. Remove wiring and refit end of
line resistors. Check sounder circuit wiring.

15.2. Indicators - Extinguishant modules


WATCHDOG - Indicates that the processor has failed to correctly execute code and has been re-started by the
watchdog circuit. The watchdog reset switch must be pressed to clear the Watchdog fault condition.
Press the Watchdog reset button. If system does not return to normal, then the module is probably damaged and
needs the circuit board replacing.

SYSTEM FUSE - Indicates that the modules main fuse has been overloaded and the module is shut down. Remove
and review all loads then re-connect one at a time.

MAN. RELEASE - Indicates that either the front panel mounted or a remotely connected Manual release control
has been operated. This indication can only be cleared by power cycling the module or pressing the processor
reset switch.

REMOTE BUS FAULT (on display) - Indicates that one or more devices on the remote serial bus is not responding
either through a disconnection or failure. Any disconnected status unit will have all indicators and LED displays
flashing 88. Any disconnected ancillary board will have its COMMS LED illuminated.
First place to check are the warning signs and LCS modules. Make sure that addresses are different, and that
status cabling is correct.

OUTPUT UNIT FAULT (on display) - On panel initialisation after power up or a processor reset indicates that a
warning sign or ancillary board has been added or removed from the communications bus. During normal operation
indicates that a warning sign or ancillary board has had a processor failure.

STATUS UNIT FAULT (on display) - On panel initialisation after power up or a processor reset indicates that a
status unit has been added or removed from the communications bus. During normal operation indicates that a
status unit has had a processor failure.

16. Power supply


The control panel requires a 230V (+10%/-15%), 50/60Hz, AC mains power supply which connects to the fused
terminal block labelled “230V”.

Panels with a 3A power supply have a 20mm, F1.6A L250V mains fuse.
Panels with a 5A power supply have a 20mm T2A L250V mains fuse.

These fuses should only be replaced with fuses of the same or similar types.
This table shows the power supply rating and recommended battery capacity for each model in the Sigma XT range.

Model Description Power supply rating Batteries for 24 hr standby


(Including Battery Charge) (Max battery size)
SIGMA-x-M3-ECU Single Extinguishing area
3A (0.8A) 7Ah (9.2 Ah)
in a M3 enclosure
SIGMA-x-D3-ECU Single Extinguishing area
5.25A (1.25A) 9 Ah (24 Ah*)
in a D3 enclosure
SIGMA-x-D4-ECU Single Extinguishing area
5.25A (1.25A) 9 Ah (24 Ah*)
in a D4 enclosure
where x = number of conventional zones
Sigma_XT_v2.51.docx Page 37 of 44
* indicates supplier dependent sizing

The maximum loading on the power supply must be carefully considered when connecting externally powered
equipment such as sounders and solenoids.

Exceeding the maximum power supply rating may cause a fuse or other protective device to operate and render
the equipment inoperative until the fuse is replaced or protective devices are reset.
The table below can be used to calculate the loading for all models by adding the loads in the second column.

Current in milliamps Quiescent Current Alarm Current


Detection section max alarm load 100 mA 550 mA
Extinguishing module max alarm load 105 mA 105 mA
Detection section total sounder load (S1&S2)
Detection section Aux 24V supply
Extinguishant module total sounder load
Extinguishant module extinguishant output load
Extinguishant module Aux 24V supply
Warning signs @ 130mA (without buzzer)
Warning signs @ 145mA (with buzzer)
Status indicators @ 33mA
TOTAL LOAD
(must be less than 2.2A or 4A depending on the PSU)

The output voltage of the power supply is between 18 and 30V depending on mains and battery condition and the
total current rating is either 3A or 4A depending on the model (see tables above).

The incoming mains cable should be routed away from other lower
voltage wiring by a distance of at least 50mm.

Mains wiring MUST include an earth conductor, which is securely


bonded to the building earth and should enter the enclosure as close
as possible to the mains terminal block. Mains wires should be kept
very short inside the enclosure and secured together close to the mains
terminal block with a cable tie.

Maximum capacity batteries are 9Ah for Sigma–X-M3 models and 24Ah
for Sigma-X-D3 or Sigma-X-D4 models.

Maximum current drawn from the batteries when the main power
source is disconnected is 3 Amps.

When the batteries are discharged to a level at which a low battery indication is given, the Batt Fail indicator will
also be lit.

WRONGLY CONNECTED BATTERIES COULD CAUSE DAMAGE TO THE CONTROL PANEL.

Battery leads are supplied wired to the power supply along with a link to connect the two batteries together.
It is most important that the polarity of the batteries is carefully observed when
connecting.
TEMPERATURE
SENSOR WIRE

The panels have a temperature compensation sensor held in place on the


power supply chassis with adhesive tape. The tip of the sensor must be fitted to TEMPERATURE

one of the batteries with the tape supplied for correct temperature compensation.
SENSOR

TAPE

BATTERY

Sigma_XT_v2.51.docx Page 38 of 44
17. Maintenance
Sigma XT control panels do not require any specific maintenance but should the control panel become dirty it can
be wiped over with a damp cloth and should then be dried with a dry, lint free cloth. Detergents or solvents should
not be used to clean the panel and care must be taken that water does not Enter the enclosure.

The control panel contains sealed lead acid batteries to provide standby power in the event of a mains failure.
These batteries have a life expectancy of around 2 years. It is recommended that these batteries be tested in
accordance with the battery manufacturer’s recommendations annually to determine their suitability for continued
standby applications.

Testing of the extinguishant system should only be carried out by trained personnel and must be done with
appropriate isolation measures in place to ensure that accidental discharge of the extinguishant agent is avoided
and any malfunction should be reported to the fire alarm maintenance company immediately.
Should the control panel become faulty the complete electronic assembly can be replaced.

To do this, any configured options should be noted then both mains and battery power should be removed before
the work is started.

The field wiring should be carefully labelled and removed from the terminals.
The faulty PCB can now be taken out of the panel by removing the screw and hinge pins holding the plate in
position.

Fitting the new PCB is the reverse of the procedure for removing the board.

18. Zone designation label


All Sigma XT control panels are supplied with a zone designation label onto which zone designations
can be written.

This enables each zone to be given a text description allowing easier identification of any zones showing an
abnormal condition. The placement of this label is at the user’s discretion.

19. Commissioning instructions and Record of Configuration


Before applying power to the panel, any solenoids or igniting actuators must be physically isolated from the system
by disconnecting both wires to it. This will prevent any accidental release of extinguishant.

When power is applied, if all connections are correct, only the green Power On and either the Automatic and Manual
or Manual Only indicators should be lit. If any fault indicators are lit the wiring to the appropriate input or output
should be checked and all faults have been cleared before proceeding.

Once the panel is fault free, it can be configured with the desired options as described in section 15.
Once the panel has been configured the system should be thoroughly tested to ensure that the control panel
responds as expected and required.

After satisfactory testing, any final connections should be made (such as to the extinguishant release actuator).
Use the Table below to record the configuration codes that have been set on the control panel for future reference.
Place a tick in the “SET” column for any configuration options that are set. It is recommended that a copy of this
Table is left with the control panel under the supervision of the person responsible for the fire detection system.

Sigma_XT_v2.51.docx Page 39 of 44
CODE FUNCTION COMMENTS SET
00 SOUNDER DELAY TIME = 30 SECONDS
01 SOUNDER DELAY TIME = 1 MINUTE
02 SOUNDER DELAY TIME = 2 MINUTES
03 SOUNDER DELAY TIME = 3 MINUTES
Sets the time delay before sounders operate
04 SOUNDER DELAY TIME = 4 MINUTES in combination with configuration codes 31
to 48 and access level 2 function AD.
05 SOUNDER DELAY TIME = 5 MINUTES
06 SOUNDER DELAY TIME = 6 MINUTES
07 SOUNDER DELAY TIME = 7 MINUTES
08 SOUNDER DELAY TIME = 8 MINUTES
09 SOUNDER DELAY TIME = 9 MINUTES
10 COMMON ALARM MODE All sounders operate upon any fire condition
11 TWO-STAGE ALARM MODE Continuous sounders in activated zone,
pulsing elsewhere
12 ZONED ALARM MODE Only sounders connected to zone in alarm
operate
21* DISABLE FIRE BUZZER Buzzer will not operate on fire condition
22* DISABLE FAULT OUTPUT Fault relay will not operate except upon total
power failure
23 DISABLE EARTH FAULT MONITORING
24 PULSED REMOTE CONTROL OUTPUT Aux 24V supply pulses 1 sec on/1 sec off
25 ENABLE SOUNDERS ON DETECTION CIRCUITS Set as default if panel is two wire “T” series
(detectors and call points on same cables)
26 DISABLE FIRE OUTPUT Fire relay will not operate upon any alarm
27 DO NOT CHANGE
28 INDICATE CALL POINT ACTIVATION Activation of a call point with a 270R
resistance fitted is indicated by a flashing
zone indicator and “Pu” on the 7 segment
display. Activation of a detector will be
indicated by a steady zone indicator and
nothing on the 7 segment display
29 DO NOT RE-SOUND ALARMS FROM ANOTHER Silenced sounders will not re-sound upon
ZONE further zone activations
31 ZONE 1 ALARM FROM DETECTOR DELAYED
32 ZONE 2 ALARM FROM DETECTOR DELAYED
33 ZONE 3 ALARM FROM DETECTOR DELAYED Sounder outputs will be delayed by time set
at options
34 ZONE 4 ALARM FROM DETECTOR DELAYED 0-9 when selected zone(s) triggered by
35 ZONE 5 ALARM FROM DETECTOR DELAYED detector only.
Note access level 2 function Ad must be set
36 ZONE 6 ALARM FROM DETECTOR DELAYED for this to take effect.
37 ZONE 7 ALARM FROM DETECTOR DELAYED
38 ZONE 8 ALARM FROM DETECTOR DELAYED
41 ZONE 1 ALARM FROM CALL POINT DELAYED
42 ZONE 2 ALARM FROM CALL POINT DELAYED
43 ZONE 3 ALARM FROM CALL POINT DELAYED Sounder outputs will be delayed by time set
at options
44 ZONE 4 ALARM FROM CALL POINT DELAYED 0-9 when selected zone(s) triggered by call
45 ZONE 5 ALARM FROM CALL POINT DELAYED point only.
Note access level 2 function Ad must be set
46 ZONE 6 ALARM FROM CALL POINT DELAYED for this to take effect.
47 ZONE 7 ALARM FROM CALL POINT DELAYED
48 ZONE 8 ALARM FROM CALL POINT DELAYED
51 COINCIDENCE ZONE 1
52 COINCIDENCE ZONE 2

Sigma_XT_v2.51.docx Page 40 of 44
53 COINCIDENCE ZONE 3
Zone contributes to ancillary board
54 COINCIDENCE ZONE 4 coincidence O/P. Any number of zones can
55 COINCIDENCE ZONE 5 be selected to contribute.

56 COINCIDENCE ZONE 6
57 COINCIDENCE ZONE 7
58 COINCIDENCE ZONE 8
61 CONFIGURE Z1 FOR I.S BARRIER
62 CONFIGURE Z2 FOR I.S BARRIER
63 CONFIGURE Z3 FOR I.S BARRIER
64 CONFIGURE Z4 FOR I.S BARRIER Detection threshold changed for use with IS
barrier
65 CONFIGURE Z5 FOR I.S BARRIER
66 CONFIGURE Z6 FOR I.S BARRIER
67 CONFIGURE Z7 FOR I.S BARRIER
68 CONFIGURE Z8 FOR I.S BARRIER
71* ZONE 1 SHORT CIRCUIT INDICATES ALARM
72* ZONE 2 SHORT CIRCUIT INDICATES ALARM
73* ZONE 3 SHORT CIRCUIT INDICATES ALARM
74* ZONE 4 SHORT CIRCUIT INDICATES ALARM Changes the trigger threshold of the zone so that
the control panel can be used on older systems
75* ZONE 5 SHORT CIRCUIT INDICATES ALARM that had no short circuit monitoring.

76* ZONE 6 SHORT CIRCUIT INDICATES ALARM


77* ZONE 7 SHORT CIRCUIT INDICATES ALARM
78* ZONE 8 SHORT CIRCUIT INDICATES ALARM
81* ZONE 1 NON-LATCHING
82* ZONE 2 NON-LATCHING
83* ZONE 3 NON-LATCHING
Renders the zone self-resetting so that it can be
84* ZONE 4 NON-LATCHING used to receive signals from other systems and will
reset when the input is removed.
85* ZONE 5 NON-LATCHING Note: It can take up to 20 seconds for zone to
reset itself when sounders are operating
86* ZONE 6 NON-LATCHING
87* ZONE 7 NON-LATCHING
88* ZONE 8 NON-LATCHING
91 ZONE 1 DOES NOT SOUND ALARMS
92 ZONE 2 DOES NOT SOUND ALARMS
93 ZONE 3 DOES NOT SOUND ALARMS
94 ZONE 4 DOES NOT SOUND ALARMS Prevents the zone from operating the two
common sounder outputs
95 ZONE 5 DOES NOT SOUND ALARMS
96 ZONE 6 DOES NOT SOUND ALARMS
97 ZONE 7 DOES NOT SOUND ALARMS
98 ZONE 8 DOES NOT SOUND ALARMS
A1* ZONE 1 ANY ALARM DELAYED
A2* ZONE 2 ANY ALARM DELAYED
A3* ZONE 3 ANY ALARM DELAYED
A4* ZONE 4 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds
continuously before an alarm is generated.
A5* ZONE 5 ANY ALARM DELAYED
A6* ZONE 6 ANY ALARM DELAYED
A7* ZONE 7 ANY ALARM DELAYED
A8* ZONE 8 ANY ALARM DELAYED

Sigma_XT_v2.51.docx Page 41 of 44
C1 ZONE 1 SOUNDERS INHIBITED
C2 ZONE 2 SOUNDERS INHIBITED
C3 ZONE 3 SOUNDERS INHIBITED
Enables individual zones to be configured not to
C4 ZONE 4 SOUNDERS INHIBITED operate zonal sounders.
On 2 wire “T” series panels this enables individual
C5 ZONE 5 SOUNDERS INHIBITED zones to be configured for use with conventional
(non-savwire) detector bases.
C6 ZONE 6 SOUNDERS INHIBITED
C7 ZONE 7 SOUNDERS INHIBITED
C8 ZONE 8 SOUNDERS INHIBITED
E1* ZONE 1 WILL NOT OPERATE FIRE RELAY
E2* ZONE 2 WILL NOT OPERATE FIRE RELAY
E3* ZONE 3 WILL NOT OPERATE FIRE RELAY
Enables individual zones to be selected to not
E4* ZONE 4 WILL NOT OPERATE FIRE RELAY operate the fire relay. This is sometimes combined
with the non-latching function to prevent ring
E5* ZONE 5 WILL NOT OPERATE FIRE RELAY
around on interconnected panels.
E6* ZONE 6 WILL NOT OPERATE FIRE RELAY
E7* ZONE 7 WILL NOT OPERATE FIRE RELAY
E8* ZONE 8 WILL NOT OPERATE FIRE RELAY

NOTE: Setting the options marked with asterisks does not comply with AS7240-2

Extinguishant Module
CONFIGURATION OPTION Exting. Module 1 Exting. Module 2
EXTINGUISHANT OUTPUT MODE =
ACTIVTION MODE =
FIRST ACTIV. ZONE =
LAST ACTIV. ZONE =
RESET INHIBIT TIME =
PRE-REL.DELAY TIME =
EXTING. RELEASE TIME =
PULSED ACTIV. ALARMS ?
STEADY ACTIV. ALARMS ?
RELEASED IND. ON RELEASED INPUT ?
RELEASED IND. ON EXTING RELEASE ?
DELAY ON MANUAL RELEASE ?
PRE-REL DELAY RESET Enabled / Disabled
RELEASE TIMER Enabled / Disabled
EARTH FAULT ENABLED ?
EARTH FAULT DISABLED ?
FAULT OUTPUT ENABLED ?
FAULT OUTPUT DISABLED ?
LOW PRESS. I/P Normal / Inverted
EXTING. O/P 1 LEVEL =
EXTING. O/P 2 LEVEL =

Sigma_XT_v2.51.docx Page 42 of 44
Notes:

Sigma_XT_v2.51.docx Page 43 of 44

You might also like