Manual Current Protection Relay RevB
Manual Current Protection Relay RevB
I1 I3 < (20% of In
> 20% of In
Overcurrent
Hysteresis -Hysteresis)
OC
In
I2
UC Undercurrent
Hysteresis
Time (sec)
Td Td Td 5sec
Pd Rd Rd Rd
Relay 1
&
Relay 2 Over Current Under Current UnBalance
Figure : Tripping functionality for 3 Phase System with default Energised Relay
(b) Second Setting (Not applicable for 1P System) : Enable Unbalance / Disable Unbalance
Step 1: Release the PRG / RST button after long press (for > 1sec) until all LEDs glow. The P-ON LED blinks twice per second indicating the
Second Setting.
Step 2: The LEDs - UC and OC indicate options : Enable UB and Disable UB, respectively.
Use the PRG / RST button to toggle between the two options.
Step 3: Only Long press (until all LEDs glow) of PRG / RST button confirms the selected option.
If PRG / RST button is not long pressed, then the new setting (Enable/Disable Unbalance) will not get stored.
The meter automatically comes out of setting if RST / PRG button is not pressed for 1 minute, hence not storing the changes.
1 5 UB
I/p-A PRG/RST
2. To Reset Relay Manually in NORMAL condition if Manual Reset Mode setting is done and fault is recovered.
Automatic / Manual reset :
1. Automatic fault reset - In this mode for undercurrent, over current, unbalance fault (If unbalance enabled) the relay resets automatically
to Normal (No fault) condition and manual intervention is not required.
2. Manual fault reset - In this mode, after the fault recovers, the relay does not reset to Normal but remains in Trip condition unless the
PRG/RST switch is not pressed.
Pressing of switch is memorized in this mode. For example if fault is present and switch is pressed then Key function is memorized and
relay resets to Normal condition once the fault is recovered.
Test Certificate:
Model : Current Protection Relay Relay Test : Pass
Accuracy Test : Pass Adjustment Test : Pass
Tripping Test : Pass