Yl620-A - Setup

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Program Line 50Hz Line 50Hz 110V 60Hz 110V 60Hz

Function Setup Range Notes


Code Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz
P00.00 Line input Frequency 0-120HZ(400HZ) 50.0HZ 50.0HZ 60Hz 60 60Hz line input
P00.01 Start / stop command source 0: Operator VFD Front panel button 0 0 0 0 Use VFD front
1: From external input (X1-X6); (VFD Stop panel for now
Button enabled)
2: From external input (X1-X6); (VFD Stop
Button disabled)
3:From Serial (Modbus Rs485)
4:By user application program control
Electric machinery
P00.02 Reserved 0 NA
P00.03 Stopping Mode 0: Decelerate to stop 0 0 0 0 Decelerate
1: Coast to Stop to Stop
2: Use DC brake resistor to stop
P00.04 VF:Highest output frequency 1.0-120.0HZ(400HZ) 50 400 60 400 Max motor speed
VF:Maximum Voltage Output
P00.05 5.0-120.0HZ(400HZ) 50 400 60 400 Max motor speed
Frequency
P00.06 VF:Highest output Voltage 10.0%-150.0% 100% 100% 100% 100 default
P00.07 VF:Middle Frequency 1.0-120.0HZ(400HZ) 3.0Hz 3.5Hz 3.0Hz 3.5 default
P00.08 VF:Middle Voltage 10.0%-100.0% 10% 20% 10% 10 default
P00.09 VF:Min Frequency 0-120.0HZ(400HZ) 0.2HZ 0.2Hz 0.2Hz 0.2 default
P00.10 VF:Min Voltage 0%-100.0% 5% 10.00% 5.00% 5 default
Analog Input 1 Regulation
P00.11 0%-100% 100 100 100 100 default
Multistage velocity
P00.12 VF :Curve Setting 0-4 0 0 0 0 default
P00.13 Parameter change Lock 0: Unlocked 0
1: Locked
10: Restore To Factory Defaults
P00.14 Reserved NA default
0:Power on time,enable External end
Power on Time prohibit
P00.15 input effective level,start-up Electric 1 1 1 1 default
External end son Start-up
machinery
1:Power on time, disable External end
input effective level,start-up Electric
machinery
P00.16 External input terminal Options 0 default
Note: all external digital inputs are LOW TRUE = ON (pull input to ground XGND) for enable. Select 0 through 8 see booklet
0: A) FWD (X5) ON=Run FWD; B) X4 ON = Run REV; C) X4 & X5 OFF = STOP
1: A) X4 sets direction, B) ON= REV; C) X5=Run/Stop (ON/OFF);
2: X3, REV (X4), & FWD (X5) = Three wire motor control
3: FWD(X5) = RUN/(Fast STOP); REV(X4) = Shut Down/Fast STOP
4: FWD (X5) turn off Instantaneous
5: FWD (X5) turn off Instantaneous
6: Stop FWD(X5) turn off Instantaneous
7: A) X4 OFF & X5 ON= Start Run FWD; B) If X4 ON = inhibit Start; C)If Running, X4 ON = STOP
8: Wire cutting Left & Right limit control (more)
P00.17 External input X1 mode See Table XVI 1 default
P00.18 External input X2 mode See Table XVI 1 default
P00.19 External input X3 mode See Table XVI 0 default
P00.20 External input X4 mode See Table XVI 0 default

Raise/Lower speed frequency- 20 20


P00.21 0.0-600Hz (delta frequecy) 1 1 default
step change (1000RPM) (1200RPM)
Raise/Lower speed time-to-
P00.22 0-65535.5 seconds 2 1 1 default
make-change
Physics amount display
P00.23 Proportion Constant (display 0-999.9% 100 100 100 100 default
value change)
P00.24 Power-ON default display mode 0: Display current target frequency 0 0 0 0 default
1:Display motor run frequency.
2:Display motor run current.
3:Display input AC voltage
4:Display Main Line voltage
5:Display output voltage
6:Display speed paragraph Number SP x
7:Display inverter temperature t deg C
8:Display input signal X1-X3/output signal
9:Display user variable
10:Dislay y user Count value
11:Dislay y temporary debugging variable
12:Display automatic multi segment run step and time
Automatic Return to default
P00.25 0:delay=OFF ;1-6: delay=10-60Sec 1 1 1 1 10 sec delay
display delay-timer (10/S)

Line 50Hz Line 50Hz Line 60Hz Line 60Hz


Code Function Setup Range Notes
Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz
P01.00 REVerse RUN enable 0: Reverse Run Enabled 0 0 0 0
1: Reverse Run Disabled
Delay before reversing motor
P01.01 Seconds (uses braking mode) 3
(sec)
Deceleration Prevention
P01.02 Percent % 140 140 140 140
overvoltage setting(%)
Accelerated Prevention
P01.03 Percent % 140 140 140 140
overcurrent setting(%)
P01.04 Overcurrent Set up (%) Percent % 120 120 120 120
P01.05 Overload protection Set up (%) Percent % 130 130 130 130
Overload protection time Set
P01.06 Seconds 120 120 120 120
up (s)
Under voltage protection Set up
P01.07 Percent % 80 80 80 80
(%)
Overvoltage protection Set up
P01.08 Percent % 150 150 150 150
(%)
After shutdown, start DC Brake
P01.09 Percent % 15 15 15 15
voltage Setup (%)
After shutdown, End DC Brake
P01.10 Percent % 0 0 0 0
voltage Setup (%)
After shutdown, DC Braking
P01.11 Seconds 2 2 2 2
Time Set up
After shutdown, DC Braking
P01.12 Hz 0.6 0.6 0.6 0.6
Initial Frequency Set up
Before start , input DC brake
P01.13 Percent % 20 20 20 20
voltage set up (%)
Before start , End DC Brake
P01.14 Percent % 15 15 15 15
voltage Set up (%)
Before start , DC Braking Time
P01.15 Seconds 3 3 3 3
Set up
Direct start Initial frequency
P01.16 Percent % 100 100 100 100
(Improve starting torque )
3 Direct start Initial frequency
P01.17 Seconds 0 0 0 0
Hold time
P01.18 power failure frequency decline 80 80 80 80
The power down frequency
P01.19 Seconds 5 5 5 5
decline rate
P01.20 Restart No load time Seconds 10 10 10 10
P01.21 Restart voltage rise time Seconds 200 200 200 200

Line 50Hz Line 50Hz Line 60Hz Line 60Hz


Code Function Setup Range Notes
Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz
When speed up torque will
P02.00 100 100 100 100 default
increased
Deceleration time - Torque
P02.01 100 100 100 100 default
Boost
P02.02 Accelerate curve Choice 0 0 0 0 default
P02.03 Deceleration curve Choice 0 0 0 0 default
P02.04 Avoid the f requency 1 #1 resonance center frequency Hz 0 0 0 0 default
P02.05 Avoid the f requency 2 #2 resonance center frequency Hz 0 0 0 0 default
P02.06 Avoid the f requency 3 #3 resonance center frequency Hz 0 0 0 0 default
P02.07 Avoid the frequency Width #1 Band width of resonance Hz 0 0 0 0 default
P02.08 Window frequency 1 0 0 0 0 default
P02.09 Window frequency 2 0 0 0 0 default

Line 50Hz Line 50Hz Line 60Hz Line 60Hz


Code Function Setup Range Notes
Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz
P02.10 Arbitrary Frequency Setpoint 0-400Hz default

P03.00 RS485 Communication 0: 1200Bps 4 4 4 4 Select for


Baud Rate 1: 2400Bps Best
2: 4800Bps Conection
3: 9600Bps
4: 19200Bps
5: 38400Bps
6: Contact Manufacturer
P03.01 RS485 Communication Address 1-254 default 10 10 10 10 10 Device # Ten
P03.02 Data transfer Mode 0: 8 bit data, 1 stop bits, odd parity 2 8N1
(Databits, Stop Bits, Parity) 1:8 bit data, 1 stop bits, parity check
2: 8 bit data, 1 stop bit, no parity
3: 8 bit data, 2 stop bits, odd parity
4: 8 bit data, 2 stop bits, parity check
5: 8 bit data, 2 stop bit, no parity
P03.03 Communication error handling 0: Decelerate to Stop 0 0
1: Coast to stop
2: DC Brake to Stop
3: No Down Time (Continue to Run)
Communication error tolerance
P03.04 msec 500 500 500 500
time
P03.05 4-20mA Break detection time msec 500 500 500 500
Line 50Hz Line 50Hz Line 60Hz Line 60Hz
Code Function Setup Range Notes
Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz
Panel potentiometer,Lower
P03.06 0-1023 (0-5Volts) 3 3
limit of AD norm
Panel potentiometer,Upper
P03.07 0-1023 (0-5Volts) 1020 1015 1020 1020
limit of AD specification
Panel potentiometer, frequency
P03.08 0.0-600Hz 0 0 0 0
at lower limit.
Panel potentiometer, frequency
P03.09 0-120HZ(400HZ) 60.0HZ 50 400 60 400
at Upper limit
P03.10 Analog lnput 1 A/D lower limit 0-1023 (A/D count = 0-10Volts input) 3 60 3 60

P03.11 Analog lnput 1 A/D Upper limit 0-1023 (A/D count = 0-10Volts input) 1020 1015 1020 1020
Analog lnput 1 frequency at
P03.12 0-600Hz 0 60 0 60 3600 RPM
lower limit
Analog lnput 1 frequency at
P03.13 0-600Hz 50 400 60 400 24000 RPM
Upper limit
P03.14 Analog lnput 2 A/D lower limit 0-1023 (A/D count = 0-10Volts input) 3 60 60

P03.15 Analog lnput 2 A/D Upper limit 0-1023 (A/D count = 0-10Volts input) 1020 1015 1020 1020
Analog lnput 2 frequency at
P03.16 0-600Hz 3 60 60
lower limit
Analog lnput 2 frequency at
P03.17 0-600Hz 50 400 60 400
Upper limit
P03.18 Analog output correlation See JP1 jumper config table 0 0
P03.19 Analog output gain setting 0-200% 100 100 100 100

Line 50Hz Line 50Hz Line 60Hz Line 60Hz


Code Function Setup Range Notes
Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz
Mo analog multiplier output
P04.00 Output pin Mo 10 10 10 10
frequency multiplier
P04.01 Mo1 Function Option Output (Option) 0 0 0
P04.02 Mo2 Function Option Output (Option) 1 1 1
P04.03 Multi-function Relay 1 0:Fault status; Fault=ON; 2
Function select 0-25 No-Fault=OFF
P04.04 Multi-function Relay 2 Function 1:Fault status; Fault=OFF; 3
select 0-25 No-Fault=ON
2: Resserved
3:Motor is at setpoint, Relay=ON; See
P02-10 setting
4:Warning: Power Down, Relay=ON
5:Warning: Low Voltage, Relay=ON
6: Warning: Over Voltage, Relay=ON
7: Warning: Over current, Relay=ON
8:Non zero velocity, Relay=ON
9:DC Bake active, Relay= ON
10:Warning: Over torque, Relay=ON
11:External interrupt faulted, Relay=ON
12:Forward Mode,Relay=ON
13:Reversal Mode, Relay ON
14:Move Time, Relay=ON
15:Accererating, Relay=ON
16:Decelrating, Relay=ON
17:At constant speed, Relay=ON
18:X1 active, Relay=ON
19:X2 active, Relay=ON
20:X3 active, Relay=ON
21:X4 active Relay=ON
22:X5 active, Relay=ON
23:X6 active, Relay=ON
24: Forward and bus voltage greater than
400V Time, Relay=ON
25: Reverse and bus voltage greater than
400V Time, Relay=ON
Multi-function Relay 1, Activate
P04.05 0-65.5 Sec 0 0 0
Delay Time
Multi-function Relay 1; Release
P04.06 0-65.5 Sec 0 0 0
delay time
Multi-function Relay 2, Activate
P04.07 0-65.5 Sec 0 0 0
Delay Time
Multi-function Relay 2; release
P04.08 0-65.5 Sec 0 0 0
delay time
P04.09 Stalled rotor detection time 0-65.5 sec 1 1 1
Switch amount (Di) sampling
P04.10 0-1000msec 8 24 8 24
time (Debounce?)
P04.11 Stopping Mode 0:Decelerate to stop; (See P06.xx) 0 0 0 0 Controlled stop
1: Coast to stop

Line 50Hz Line 50Hz Line 60Hz Line 60Hz


Code Function Setup Range Notes
Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz
PID Output Upper limit
P05.00 Hz 50 400 60 400 default
frequency
PID Output lower limit
P05.01 Hz 25 200 30 200 default
frequency
P05.02 PID Given Source 0 0 default
P05.03 PID Values Given 0.2 0.2 default
PID Output characteristic (FOR
P05.04 0 0 default
/REV)
PID Output characteristic
P05.05 0 0 default
(FOR/REV)
P05.06 PID Proportional Gain 0-100.0 50 50 default
P05.07 PID Integration Time Ti 0-100.0 50 50 default
P05.08 PID Derivative Time Td 0-100.0 50 50 default
P05.09 PID Deviation Limit 0-50.0 5 5 default
P05.10 PID Integral upper limit 50 50 default
P05.11 PID Given Change Time 0-600.0 1 1 default
P05.12 PID Feedback Filter Time 0 0 default

Line 50Hz Line 50Hz Line 60Hz Line 60Hz


Code Function Setup Range Notes
Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz
P06.00 Acceleration Time 0 0 0 0
P06.01 Accel.Time 1 0.1-6553.5 Seconds 5 9 5 3
P06.02 Decel. Time 1 0.1-6553.5 Seconds 5 8.6 5.05 3
P06.03 Accel.Time 2 0.1-6553.5 Seconds 2 2 2 3
P06.04 Decel. Time 2 0.1-6553.5 Seconds 2 2 2 3
P06.05 Accel.Time 3 0.1-6553.5 Seconds 2 2 2 3
P06.06 Decel. Time 3 0.1-6553.5 Seconds 2 2 2 3
P06.07 Accel.Time 4 0.1-6553.5 Seconds 2 2 2 3
P06.08 Decel. Time 4 0.1-6553.5 Seconds 2 2 2 3
P06.09 Accel.Time 5 0.1-6553.5 Seconds 2 2 2 3
P06.10 Decel. Time 5 0.1-6553.5 Seconds 2 2 2 3
P06.11 Accel.Time 6 0.1-6553.5 Seconds 2 2 2 3
P06.12 Decel. Time 6 0.1-6553.5 Seconds 2 2 2 3
P06.13 Accel.Time 7 0.1-6553.5 Seconds 2 2 2 3
P06.14 Decel. Time 7 0.1-6553.5 Seconds 2 2 2 3
P06.15 Accel.Time 8 0.1-6553.5 Seconds 2 2 2 3
P06.16 Decel. Time 8 0.1-6553.5 Seconds 2 2 2 3
P06.17 Jog Acceleration Time 0.1-6553.5 Seconds 2 2 2 3
P06.18 Jog Deceleration Time 0.1-6553.5 Seconds 2 2 2 3

Line 50Hz Line 50Hz Line 60Hz Line 60Hz


Code Function Setup Range Notes
Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz
P07.00 Frequency 1 (Preset speeds) 0-120HZ(400HZ) 50 (2.5Krpm) 400 60 3600rpm 400 24000 RPM
P07.01 Frequency 2 (Inputs X1-X3) 0-120HZ(400HZ) 45 350 55 350 21000 RPM
P07.02 Frequency 3 (See Table XII) 0-120HZ(400HZ) 40 300 50 300 18000 RPM
P07.03 Frequency 4 (See P00.17-19) 0-120HZ(400HZ) 35 250 45 250 15000 RPM
P07.04 Frequency 5 0-120HZ(400HZ) 30 200 40 200 12000 RPM
P07.05 Frequency 6 0-120HZ(400HZ) 25 150 35 150 9000 RPM
P07.06 Frequency 7 0-120HZ(400HZ) 20 100 30 100 6000 RPM
P07.07 Frequency 8 0-120HZ(400HZ) 15 50 25 50 3000 RPM
0: Operator VFD Front Panel (parameter:
P07.08 Frequency 1 select method 0 0 0
P03.06)
1: Pre-set Freq, P00.01 Set frequency
P07.09 Frequency 2 select method value ,Operation panel keyboard,Can be 0 0
set directly
P07.10 Frequency 3 select method 2:No. X paragraph frequency
P07.11 Frequency 4 select method 3: Analog Input. :(P03.10-P03.13) 2 2
P07.12 Frequency 5 select method 4: external simulation amount 2 (VI2)
P07.13 Frequency 6 select method 5: (Modbus Rs485) Given frequency 2 2 2
6: User application program, given
P07.14 Frequency 7 select method 2 2 2
frequency
P07.15 Frequency 8 select method 7:( Pid)Output frequency 2 2 2
Other Reserved
Note Three control methods 1.The motor speed is controlled by the operating panel
2.Motor speed control by external terminals (Potentiometer 10K). P00.01 set to 1, P07.08 set to 3
3.Motor speed control by external terminals. P00.01 set to 1, P07.08 set to 1.
P07.16 Jogging Frequency FORWARD 0-120HZ(400HZ) 15.0HZ 15.0Hz 60 18
P07.17 Jogging Frequency REV 0-120HZ(400HZ) 15.0Hz 60 18

Line 50Hz Line 50Hz Line 60Hz Line 60Hz


Code Function Setup Range Notes
Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz

Binary data format to set the direction of


Automatic many paragraph operation, see (the automatic multi
P08.00 0 0 0 0 default
Running: Running direction segment operation, the operation of the
direction set table)
P08.01 Automatic many paragraph 0:Automatic sequencer is disabled; 0 0 0 0 default
Running: mode Choice 1:After last sequence complete, Stop
2: After last sequence complete,
Continue running in last state;
3:After sequence complete, Repeat
sequence from begining.
Automatic many paragraph
P08.02 0:Seconds; 1:Minutes 0 0 0 0 default
Running time Units:S/M
NOTE: Automaticmulti-section run time, Set up Section speed run time Time units are determined by P08.02. If P08.01 = 0, then this section is not executed.
Automatic sequence: No.1
P08.03 10 (Seconds or Minutes P08.02) 1 1 No need
Running time
Automatic sequence: No.2
P08.04 10 (Seconds or Minutes P08.02) 1.5 1.5
Running time
Automatic sequence: No.3
P08.05 10 (Seconds or Minutes P08.02) 1 1
Running time
Automatic sequence: No.4
P08.06 10 (Seconds or Minutes P08.02) 1.5 1.5
Running time
Automatic sequence: No.5
P08.07 10 (Seconds or Minutes P08.02) 1 1
Running time
Automatic sequence: No.6
P08.08 10 (Seconds or Minutes P08.02) 1.5 1.5
Running time
Automatic sequence: No.7
P08.09 10 (Seconds or Minutes P08.02) 1 1
Running time
Automatic sequence: No.8
P08.10 10 (Seconds or Minutes P08.02) 1.5 1.5
Running time

P09.00 frequency Range(%) 0-200% 0 0


P09.01 frequency wave Range(%) 0-400% 200 30 30
P09.02 frequency Rise time(S) 0.1-999.9 Sec 6 6 6 3
P09.03 frequency decline time(S) 0.1-999.9 Sec 5 5 5 3

P10.00 Counter reload,value counts 1000 1000 1000 no need


P10.01 Counter current value counts 0 0 0
P10.02 Timer reload,value counts 1000 1000 1000
P10.03 Timer current value counts 0 0 0

Line 50Hz Line 50Hz Line 60Hz Line 60Hz


Code Function Setup Range Notes
Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz
P11.00 Output Status 1 1 1 NA read only
P11.01 Output Voltage (V) 0 0 NA read only
P11.02 Output Current (A) 5 5 NA read only
P11.03 Output Frequency (Hz) 50 400 60 NA read only
P11.04 Current Heatsink Temp Temperature Deg C 25 25 25 NA read only

Line 50Hz Line 50Hz Line 60Hz Line 60Hz


Code Function Setup Range Notes
Motor 50Hz Motor 400Hz Motor 60Hz Motor 400Hz
P12.00 Rated Motor Current Amps 5 5 5 8 See Motor
P12.01 Rated Motor Voltage Volts 220 220 110 110 Nameplate
P12.02 Motor Pole number 2-100 2 2 2 2 typical
P12.03 Motor no-load current % percent 5 measured
Motor no-load current
P12.04 Seconds 10 10 10 default
detection time(S)
P12.05 Converter rated current(A) Amps 5 5 15 see VFD
P12.06 Converter rated Voltage(V) Volts 220 220 110 110 nameplate
P12.07 DC bus output voltage% % percent 140 130 140 140 default
Heat sink over temperature
P12.08 Deg C 75 75 75 75 default
protection point
Radiating fin temperature
P12.09 Mode # 1 1 1 1 default
sensor configuration
Abnormal reset auto restart
P12.10 Seconds 120 120 120 120 default
delay time
P12.11 Fan Function Modes 0: Fan runs when motor runs; 1 1 1 1 default
1: If above setpoint (P12.12) Fan=ON; If
Temperature Controlled below setpoint, Fan one minute delay to
OFF.
2: Fan always ON;
3: Fan always OFF;
P12.12 Fan ON/OFF Temperature Fan Temperature setpoint in Deg C 45 45 45 45 default
P12.13 Fan Testing 0 0 0 0 default
P12.14 Bypass relay closed detection 0 0 0 0 default
P12.15 Bypass Relay delay time sec 1.5 1 1.5 1 default
Power on delay timer initial
P12.16 Seconds 50 50 50 50 default
value(S)
Electric current sensor To
P12.17 Sensor # 1 1 1 1 default
configure
Automatic stable pressure
P12.18 ?? 1 1 1 1 default
function Choice
2.0-15.0KHZ (110V=13.0KHZ
P12.19 PWM Frequency 8.0KHZ 8.0KHz 13 KHz 13 KHz 110V
220V=11.0KHZ 380V=6.0KHZ)
P12.20 SVPWM Pattern 0: Three phase induction motor 0 0 0 0 3 phase
Select: 3 phase or 2 phase
1: Two Phase asynchronous motor (Single-
motor type
phase motor, 90 degree phase
difference,No Starting capacitor)
Product Information All fields are read only
P13.00 Softwarer Version # read only
P13.01 Hardware Version # read only
P13.02 Producer read only
P13.03 Mfg year & date YY:WK read only
P13.04 Product ID # read only
P13.05 Cumulative Opeating Time Hours read only

P14.00
P14.01
P14.02
P14.03
P14.04
P14.05
P14.06
P14.07
P14.08
P14.09
P14.10
P14.11
P14.12
P14.13
P14.14

Table XII Correspondence between Multi-Segment Speed Instruction and Frequency Segment and parameter line
Inputs P00.17 through P00.19 control manual fixed speeds from table P07.00 through P07.07
X1-X3 Inputs are LOW TRUE = ON Multi stage external input ==> X3 X2 X1 Use Speed Binary X3X2X1
X1-X3 pulled to XGND = ON Select frequency P07.00 OFF OFF OFF 0 000
Select frequency P07.01 OFF OFF ON 1 001
Select frequency P07.02 OFF ON OFF 2 010
Select frequency P07.03 OFF ON ON 3 011
Select frequency P07.04 ON OFF OFF 4 100
Select frequency P07.05 ON OFF ON 5 101
Select frequency P07.06 ON ON OFF 6 110
Select frequency P07.07 ON ON ON 7 111
Table XIII JP2 & JP3 (Three pin Headers) ANALOG Input Voltage / Mode selection
Analog Volts input VI1 Volts input VI2
JP2 pins 1-2 JP2 Pins 2-3 JP3 pins 1-2 JP3 pins 2-3
0-5V OFF OFF OFF OFF
0-10V OFF ON OFF ON Default
0-20mA ON OFF OFF OFF
Note: It is possible that JP1 and JP3 are the same jumper. See picture

TABLE XVI For P00.17 through P00.20


0 Retain: Input Not used
1 Multi-segment Speed Instruction; Select Speeds 0 through 7, using X1 through X3
5 ON = Run Forward; OFF = Do not run Forward , OFF = STOP if running
6 ON = Run Reverse; OFF = Do not run Reverse; OFF = STOP if running
7 OFF = Stop; ON = Run; Note REV (X4) = Direction select:
8 ON = Instant STOP (Normally Open E-STOP)
9 OFF = Instant STOP fast (Normally Closed E-STOP)
10 OFF = Instant STOP with BRAKE (Ignores PV StopMode setting)
11 Momentary ON = Increase Motor Speed; valid for main freq P00.00 only; Step freq up specified by P00.21)
12 Momentary ON = Decrease Motor Speed; valid for main freq P00.00 only; Step freq down specified by P00.21)
13 External fault input; Transition to ON = generate delayed "external fault" (external fault often opens)
14 External fault input; Transition to ON = generate instant "external fault"
15 External Fault: Transition to ON = generate "external fault"
16 External Fault; Transition to OFF = generate "external failure" (disconnect generated fault)
17 Used as external Fault reset; Momentary ON = Reset/Clear fault
Note: ON = activated (input pulled to XGND) Off = no input = not pulled to XGND ;