Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Troubleshooting - EMV PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

Energy Guide

© Rolls-Royce Power Engineering plc (2012)


The information in this document is the property of Rolls-Royce Power Engineering plc. The information EG 038
may not be copied, or communicated to a third party, or used for any purpose other than that for which it is
supplied, without the prior written consent of Rolls-Royce Power Engineering plc.

 
Title:‐ 

Meggitt EMV with Moog DS2000XP controller 
Troubleshooting Guide 
Purpose:‐ 

The purpose of EG038 is to provide troubleshooting assistance to customers and field service who are faced 
with rectifying in‐service faults in Electric Metering Valve (EMV) systems which were previously fault‐free and 
operating normally. 
This guide can also be used as a source of reference information for new or upgraded installations. 

Applicable to:‐ 

EG038 is applicable to all Gas, Liquid and Hot Air EMVs which use the Moog DS2000XP motor controller. 
 

Rev.  Date  Author


Initial  31.July.2012  R.Gibbins
A     
B   
C   
D   
E   
F   
G   

Whilst this information is given in good faith, based on the latest information available
to Rolls-Royce Power Engineering plc, no warranty or representation is given
concerning such information, which must not be taken as establishing any contractual
or other commitment binding upon Rolls-Royce Power Engineering plc or any of its
subsidiary or associated companies.

Rolls-Royce Power Engineering plc, Registered office: Moor Lane, Derby DE24 8BJ
Company number: 1305027, Registered in England Produced in Great Britain
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 2 of 48

Contents 
1.  GENERAL .............................................................................................................................................. 3 
1.1  INTRODUCTION ........................................................................................................................................... 3 
1.2  APPLICABILITY ............................................................................................................................................. 3 
1.3  EMV EQUIPMENT SUPPLIERS ......................................................................................................................... 3 
1.4  GLOSSARY .................................................................................................................................................. 4 
2.  EMV DESCRIPTIONS .............................................................................................................................. 5 
2.1  GAS EMV (1.5 INCH AND 2.0 INCH VARIANTS) ................................................................................................. 5 
2.2  LIQUID EMV (1.5 INCH VARIANT) ................................................................................................................... 7 
2.3  HOT AIR EMV (4.0 INCH) ............................................................................................................................. 9 
2.4  MOOG DS2000XP MOTOR CONTROLLER ....................................................................................................... 10 
3.  EMV OPERATION & CONTROL ............................................................................................................. 11 
3.1  THE GENERAL OPERATION OF AN EMV ........................................................................................................... 11 
3.2  EMV ACTUATION ...................................................................................................................................... 11 
3.3  EMV INSTRUMENTATION ............................................................................................................................ 12 
3.4  EMV CABLING .......................................................................................................................................... 12 
3.5  EMV POWER ............................................................................................................................................ 13 
3.6  EMV MOTOR CONTROLLER OPERATION .......................................................................................................... 13 
3.7  EMV SYSTEM FAULT DIAGNOSTICS ................................................................................................................ 15 
4.  EMV SYSTEM FAULT‐FINDING ............................................................................................................. 16 
4.1  BASIC SYMPTOMS OF AN EMV PROBLEM ........................................................................................................ 16 
4.2  EMV FAULT‐FINDING TABLE ....................................................................................................................... 17 
4.3  ACTIONS & CHECKS.................................................................................................................................... 21 
5.  APPENDIX – DIAGNOSTIC INFORMATION AVAILABLE FROM THE DS2000XP MOTOR CONTROLLER ...... 25 
5.1  MOTOR CONTROLLER FAULT STATUS REPORTED TO THE UNIT HMI ...................................................................... 25 
5.2  FRONT PANEL LED STATUS INFORMATION ...................................................................................................... 28 
5.3  FRONT PANEL HMI DISPLAY INFORMATION ..................................................................................................... 29 
5.4  MOTOR CONTROLLER, GUI INFORMATION ...................................................................................................... 34 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 3 of 48

1. General 

1.1 Introduction 
The  gas  and  liquid  fuel  metering  versions  of  the  Electric  Metering  Valve  (EMV)  were  first  introduced  into 
service  on  Rolls‐Royce  GT  applications  in  2000  and  have  since  become  the  standard  offerings  for  the 
Rolls‐Royce industrial fleet of Avon, RB211 and Trent applications. A further version of the EMV is also used as 
the Hot Air Valve (HAV) that bleeds HP6 compressor delivery air on RB211‐DLE applications.  The EMVs are 
driven by motor controllers fitted inside motor boxes that act as electrical interfaces and which also provide 
enclosure protection for the motor controllers.  There are two distinct variants of motor box: the standard box 
designed for mounting in a safe zone and the flameproof box designed for a hazardous zone. 
The original EMVs contained electric actuators from Kollmorgen/Parker and used motor controllers from the 
same supplier source to drive the EMVs.  The original electric actuators have now been superseded by Moog 
electric actuators for current production EMVs.  Likewise the original motor controllers have been replaced by 
the Moog DS2000XP series motor controller which is used in the current production motor boxes used on new 
Rolls‐Royce GT applications.   
The guide begins by providing some background information on the EMV valves and the controller and how 
the system works.  Section 4 then provides a matrix of the possible causes of EMV system shutdowns and the 
suggested actions to test for particular faults that could cause such shutdowns. 
Section  5  is  an  appendix  detailing  what  status  or  fault  information  can  be  read  directly  from  the  DS2000XP 
controller together with suggested actions against faults identified by the controller itself. 

1.2 Applicability 
This guide is applicable to all gas, liquid or hot air EMVs using the Moog DS2000XP controller.  This covers the 
new  production  EMVs  using  Moog  actuators  and  driven  by  Moog  motor  controllers  but  it  also  covers  those 
in‐service  combinations  of  original  EMVs  running  with  the  current Moog  motor  controllers  that  exist  due  to 
control system retrofits.   

1.3 EMV equipment suppliers 
Whittaker Controls Inc. was the original manufacturer of the EMVs introduced in the early 2000’s onto RB211 
and  Trent  GT  packages.    The  early  Whittaker  EMVs  used  actuators  and  motor  controllers  supplied  by 
Kollmorgen/Parker  but  later  Whittaker  EMVs  used  actuators  and  motor  controllers  supplied  by  Moog.  
Whittaker  Controls  were  bought  by  the  Meggitt  group  in  the  late  2000’s  and  the  company  is  now  called 
Meggitt  Control  Systems  (MCS).    In‐service  EMVs  will  therefore  be  labelled  as  either  Whittaker  or  Meggitt 
valves depending on when they were delivered to site. 
The  original  EMV  systems  used  Rolls‐Royce  motor  boxes  but  later  GT  applications  have  used  motor  boxes 
supplied by Meggitt which contain one or more Moog motor controllers to suit the GT application. 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 4 of 48

1.4 Glossary 
The following abbreviations, terms, definitions, etc. are used within this guide:‐ 
BITE ................................... Built‐In Test Equipment 
ECS .................................... Engine Control System 
EMI ................................... Electro‐Magnetic Interference 
EMV .................................. Electric Motorised Valve 
DeviceNET ........................ A type of communications link for connecting multiple devices in a network 
DS2000XP ......................... The series of Moog high‐performance servo motor drive that is used as the motor 
controller  for  Whittaker  EMVs.    Rolls‐Royce  use  the  ‘power  generation’  variant  of 
the DS2000XP.  
FMV .................................. Fuel Metering Valve 
HAV ................................... Hot Air Valve 
Meggitt ............................. Meggitt  Control  Systems  (MCS)  is  the  current  name  for  the  EMV  manufacturer 
following the purchase of Whittaker by the Meggitt group. 
Moog ................................ Moog  Inc.  –  Industrial  Controls  Group.    Moog  are  the  current  manufacturer  of 
(a) the electric actuator forming a part of each EMV and (b) the  motor controller 
used to position the EMV. 
Motor Controller .............. The motor controller is the electric servo motor drive that controls the EMV.  The 
motor controller receives position demand instructions from the ECS and converts 
them into electrical drive signals to the servo motor windings in the EMV. 
Motor Box ........................ The motor box is an assembly comprising some form of enclosure plus one or more 
EMV  motor  controllers.    A  ‘standard’  motor  box  is  designed  for  operation  in 
non‐hazardous environments such as a control room whereas a ‘flameproof’ motor 
box is designed for operation within the GT package or other site locations where 
there are potentially explosive atmospheres. 
PCS .................................... Plant/Package Control System 
PSU ................................... Power Supply Unit 
Servo Motor ..................... The EMV uses a brushless DC servo motor as the actuation for the valve  
UCP ................................... Unit Control Panel 
Whittaker ......................... Whittaker Controls Inc. was the original name for the EMV manufacturer. 
 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 5 of 48

2. EMV descriptions 
Section 2 provides general descriptions of each of the main types of EMV used by Rolls‐Royce  

2.1 Gas EMV (1.5 inch and 2.0 inch variants) 
The major components of the gas EMV are:‐ 
1)  an electric actuator 
2)  a gas flow metering valve 
3)  an intermediate yoke assembly 
The  gas  EMV  electric  actuator  incorporates  an  electric  servo  motor  which  is  driven  by  a  dedicated  motor 
controller.  The motor used is a 3‐phase, brushless DC type with three stator windings that are excited in order 
(i.e. U‐V‐W) by the motor controller to rotate the motor output shaft in one direction.  Changing the order of 
excitation (i.e. U‐W‐V) therefore rotates the shaft in the other direction.  The operation of the servo motor is 
done  by  the  motor  controller  which  controls  the  timing  and  order  of  motor  stator  winding  excitation  as 
required to control both the speed of the output shaft and its direction of rotation.  An integral resolver fitted 
to the motor shaft provides the motor controller with an accurate reading of the motor shaft angle relative to 
the stator windings.  This is necessary to allow the windings to be excited at the right time. 
The gas EMV uses a linear motion, pressure‐balanced poppet valve to meter gas flow.  The pressure balance is 
provided  by  a  piston  on  the  top  of  the  valve  stem  that  is  subject  to  the  same  gas  pressure  as  that  on  the 
bottom of the poppet valve.  A pair of seals around the valve stem prevent any gas leakage from the valve into 
the intermediate yoke assembly.  A connection in the assembly housing vents the space  between the valve 
stem seals allowing any gas leakage past the 1st seal to be piped away to a safe area.   
The linear motion of the gas valve means that the intermediate yoke assembly of the gas EMV has to convert 
the multiple rotations of the servo motor output shaft to a limited linear movement.  This is done by having a 
ball‐screw  mechanism  on  the  motor  output  shaft  that  is  attached  to  a  coupling  connected  to  the  gas  valve 
stem.  This ball‐screw coupling converts the rotary motion of the servo motor into a linear movement of the 
gas valve poppet and thus sets the flow area of the gas valve.  For a particular gas at a constant temperature 
the metered gas flow is proportional to the effective area of the poppet valve and the pressure ratio across it. 
There are no minimum and maximum valve travel stops as such but the valve seat effectively determines the 
minimum  position  of the EMV  whilst  the  maximum  travel  is  limited  by  the  distance  between  the  top  of  the 
valve stem coupling and the motor casing. 
The yoke assembly takes advantage of the linear movement of the ball‐screw coupling in two ways.  A pointer 
arm fitted to the ball‐screw coupling provides a physical indication of linear valve travel with the end of the 
pointer  viewable  through  a  window.    The  position  scale  is  calibrated  in  tenths  of  an  inch  NOT  %.    The  full 
stroke (100%) of the 1.5” Gas Valve is 1” whereas the full stroke length of the 2” valve is 1.2”. A separate lever 
assembly fitted to the ball‐screw coupling is used to actuate the closed position switch. 
The gas EMV is required to provide failsafe action to close the gas EMV in the event of a loss of motor control.  
This is done by means of a return spring connected between the EMV body and the ball‐screw coupling which 
acts to close the gas valve.  As soon as the servo motor stops providing a counterbalancing torque then the 
EMV return spring forces the gas valve closed and so the gas EMV can also be considered to act as a gas Shut 
Off Valve (SOV) in the package gas fuel system.  The poppet valve has a hard seat which provides a metal‐to‐
metal gas seal when the valve is closed by the motor controller or the return spring, and so a degree of leakage 
through a closed gas EMV in accordance with ANSI Class IV is to be expected.  
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 6 of 48

 
 
Figure 1 – Typical gas EMV (2 inch valve shown) 
 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 7 of 48

2.2 Liquid EMV (1.5 inch variant) 
The major components of the liquid EMV are:‐ 
1)  an electric actuator 
2)  a liquid flow metering valve with constant ΔP pressure regulator 
3)  an intermediate assembly 
The liquid EMV electric actuator incorporates a similar electric servo motor to that of the gas EMV and which is 
controlled in a similar way by a dedicated motor controller. 
The Whittaker liquid EMV uses a rotary sleeve valve to meter liquid flow.  For a particular liquid the metered 
liquid  flow  is  proportional  to  the  effective  area  of  the  sleeve  valve  and  the  pressure  difference  across  it.  
Pressure compensation to make the liquid EMV delivery independent of the delivery pressure is achieved by 
means  of  a  separate  pressure  regulator.    This  spills  excess  inlet  flow  back  to  the  LP  side  of  the  liquid  fuel 
system  to  maintain  a  constant  pressure  difference  across  the  sleeve  valve.    With  a  constant  pressure 
difference  across  the  valve  (designed  to  be  between  110‐120psid),  metered  liquid  flow  is  proportional  to 
sleeve valve area alone. 
The  rotary  sleeve  valve  requires  less  than  90°  of  rotation  between  the  closed  and  maximum  flow  area 
positions  and  so  the  multiple  rotations  of  the  servo  motor  shaft  have  to  be  converted  to  a  limited  rotary 
motion of about a quarter turn.  This is done by a step‐down gearbox in the electric actuator assembly that 
effectively converts the servo motor into a limited rotation actuator. 
Like  the  yoke  assembly  of  the  gas  EMV,  the  intermediate  assembly  on  the  liquid  EMV  provides  a  physical 
indication of liquid valve rotation and actuation of the closed position switch.  In this case the pointer arm is 
connected to the coupling linking the actuator output shaft to the sleeve valve input shaft and so provides an 
indication  of  valve  rotation.    Likewise  the  closed  position  switch  is  actuated  by  rotary  movement  of  a  lever 
connected to the same shaft coupling. 
Unlike the gas EMV, the sleeve valve doesn’t have a valve seat or other features to limit rotation and so the 
intermediate  assembly  includes  both  a  minimum  position stop  and  a  maximum  position  stop  in  the  form  of 
adjustable bolts that use a cam feature on the shaft coupling to limit the rotation of the sleeve valve. 
 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 8 of 48

 
Figure 2 – Typical liquid EMV (1.5 inch valve shown) 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 9 of 48

2.3 Hot Air EMV (4.0 inch) 
The major components of the Hot Air EMV are:‐ 
1)  an electric actuator 
2)  a Hot Air Valve (HAV) 
3)  an intermediate yoke assembly 
The hot air EMV electric actuator incorporates a similar electric servo motor to that of the gas EMV and which 
is controlled in a similar way by a dedicated motor controller. 
The  linear  motion  of  the  valve  means  that the  intermediate  yoke assembly  of  the  hot  air  bleed EMV  has  to 
convert the multiple rotations of the servo motor output shaft to a limited linear movement.  This is done by 
having a ball‐screw mechanism on the motor output shaft that is attached to a coupling connected to the valve 
stem.  This ball‐screw coupling converts the rotary motion of the servo motor into a linear movement of the 
valve and thus sets the flow area of the valve.   

 
Figure 3 – Hot Air Bleed Valve 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 10 of 48

2.4 Moog DS2000XP motor controller 
The  photograph  below  shows  the  cold‐plate  version  of  the  Moog  motor  controller.    This  uses  the  large 
mounting plate as a heat sink that transfers the heat generated by the drive out through the enclosure wall of 
the EMV motor box.  This arrangement allows cold‐plate Moog controllers to be mounted in the flameproof 
variant of the motor box which are sealed and unventilated with no internal air cooling.  Standard variants of 
the  EMV  motor  box  are  located  in  safe  areas  and  so  they  may  include  cooling  fans  to  circulate  cooling  air 
within the motor box and around the motor controller(s). 
 

 
Figure 4 – DS2000XP motor controller 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 11 of 48

3. EMV operation & control 
Section 3 covers the basic control configuration of an EMV and how it is typically operated. 

3.1 The general operation of an EMV 
Each EMV is a flow metering assembly comprising a Fuel Metering Valve (FMV) or Hot Air Valve (HAV) with an 
electrically actuated servo motor that provides the necessary linear or rotary actuation to the valve via some 
form  of  gearing.    Each EMV  position  demand  signal  comes  from  the  Engine  Control System  (ECS)  controller 
which changes the position demand to control (a) an engine fuel flow or (b) a compressor bleed airflow. 
The EMV is driven by its own high power motor controller (i.e. the Moog DS2000XP) that controls the rotation 
of the electrical servo motor.  The motor controller includes a closed loop position controller that compares 
the calculated position of the metering valve against its demanded position and then drives the electrical servo 
motor in the direction that minimises the position error.   

 
Figure 5 – EMV control loop 

3.2 EMV actuation 
The  servo  motor  used  is  a  3‐phase,  brushless  DC  type  with  three  stator  windings  that  are  excited  in  order 
(i.e. UVW) by the motor controller to rotate the motor output shaft in one direction.  Changing the order 
of excitation (i.e. UWV) therefore rotates the shaft in the opposite direction.  The servo motor is driven by 
the  motor  controller  which  controls  the  timing,  order  and  duration  of  motor  stator  winding  excitation  as 
required to control both the speed of the output shaft and its direction of rotation.  The resolver fitted to the 
servo motor shaft provides the motor controller with an accurate reading of the motor shaft angle relative to 
the stator windings.  This reading is necessary to allow the windings to be excited at the right time. 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 12 of 48

3.3 EMV instrumentation 
Rather than measure EMV valve position directly with a limited rotation sensor, instead the rotational position 
of the servo motor is measured by a resolver than provides an accurate measurement of the servo motor shaft 
angle.  The percentage travel of the EMV valve is then calculated within the motor controller by counting the 
number  of  revolutions  of  the  servo  motor  from  its  ‘home’  position  where  ‘home’ corresponds  to the  EMV’s 
minimum  or  closed  position.    It  is  the  calculated  EMV  valve  travel  that  is  used  in  the  closed  loop  position 
controller to drive the electrical servo motor towards the EMV demanded position.   
A  ‘closed’  position  switch  fitted  to  the  EMV  valve/actuator  linkage  mechanism  provides  an  independent 
indication that a valve is closed.  The switch is actuated when the valve reaches the (almost) closed position.   
The  EMV  servo  motor  of  the  valve  incorporates  a  thermistor,  which can  be used  by  the  motor  controller  to 
monitor motor temperature and thus provide motor over‐temperature protection as part of its BITE.  

3.4 EMV cabling 
3.4.1 DeviceNet control configuration 
Most  installations  of  the  Moog  actuated  EMV  with  DSP2000XP  controller  incorporate  a  DeviceNet  network 
communications  link  to  the  ECS.  The  purpose  of  this  network  link  is  to  pass  the  valve  position  demand  and 
position  feedback  values  between  the  ECS  and  the  motor  controller  as  well  as  passing  a  series  of  motor 
controller fault status bits to the ECS for fault annunication indication.  If the unit uses a number of EMVs for 
engine control (e.g. dual fuel or DLE applications) then only a single DeviceNet link is needed to chain all the 
EMV motor controllers together and connect them to the single ECS DeviceNet interface. 
The main cables between the ECS, motor controller and EMV are designated as follows in this guide:‐ 
  Cable D carries the network communications between the ECS and the EMV(s) 
  Cable E carries the discrete ‘enable’ signal to the motor controller that allows closed loop position control 
  Cable F returns the discrete ‘controller fault’ condition from the motor controller to the ECS 
  Cable P provides the controller with its power supply 
  Cable M provides the power drives to the 3 servo motor windings 
  Cable R carries the resolver excitation signal and the separate resolver SIN and COS return signals that are 
used to calculate servo motor angular position 
  Cable T carries a servo motor temperature signal to the controller 
  Cable S returns the discrete ‘valve closed’ condition to the ECS 

 
Figure 6 – EMV cabling with DeviceNet control 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 13 of 48

3.4.2 Analogue control configuration 
Some installations (e.g. the FT55 Trent control systems) do not utilise a network communications link between 
the ECS and the controller but use analogue signals for position control.  Instead of sending number values, the 
valve  position  demand  from  the  ECS  is  sent  as  a  4‐20mA  signal  to  the  controller  (cable  A1)  and  the  valve 
position feedback is returned to the ECS as a 4‐20mA signal (cable A2).  With no communications link then no 
detailed fault status information from the controller can be reported to the ECS other than the common fault 
status indicated by  the controller’s hardwired fault contact (cable F).  
With  the  exception  of the  analogue  position  demand  and  feedback  signals  carried by  cables A1  and  A2,  the 
cabling for all other EMV system functions is the same as that described previously in section 3.4.1. 

 
Figure 7 – EMV cabling with analogue control 

3.5 EMV power 
There are several configurations with regards to the design of the power supply to the EMV controller(s). The 
project specific schematics should always be used as the reference for troubleshooting. 
Typically,  the  EMV  controllers  are  powered  from,  two  off  144VDC  power  supply  units  (PSU)  connected  in 
Parallel via a Diode pack. Each PSU is a dual 72VDC power supply feed from either a 24Vdc or 240VAC supply. 
The two 72VDC outputs of a single PSU are connected in series to provide the 144VDC output to the Diode 
pack.  Typically  each  PSU  has  its  own  fuse,  normally  a  10A  fuse  would  be  used  for  units  which  are  24VDC 
powered. 
Although  one  PSU  may  be  able  to  provide  adequate  power  for  two  controllers  under  normal  steady  state 
conditions, the two PSU’s are not intended to offer system redundancy. Both PSU’s must be in operation for 
the system to work reliably. 
When checking the output of the each PSU, the other PSU should be powered down to ensure that the checks 
conducted on the PSU under test are not influenced by the other PSU.  
 

3.6 EMV motor controller operation 
3.6.1 Enabling the motor controller 
The Moog DS2000XP motor controller has an ENABLE input which must be energised with a 24VDC signal for 
the controller to be able to carry out closed loop position control of the EMV.  If the ENABLE signal is lost or 
removed for any reason then the motor drive signals are switched off and the EMV is forced to its minimum 
valve position by the action of its failsafe return spring. 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 14 of 48

The  ENABLE  input  to  the  controller  will  typically  be  sent  via  the  hardwired  contacts  of  one  of  a  number  of 
shutdown  relays  that  are  controlled  by  the  trip  string  of  the  unit  control  system.    A  broken  trip  string  will 
disable the EMV by opening the contacts on the EMV shutdown relay and removing the ENABLE.  Any standing 
unit  shutdown  that  has  broken  the  trip  string  will  mean  that  the  ENABLE  signal  cannot  be  received  by  the 
controller.   This means that an EMV cannot be stroked for test purposes with a standing shutdown.   
All  unit  shutdowns  should  normally  be  cleared  first  before  stroking  an  EMV  for  test  purposes  but  if  it  is 
absolutely necessary to stroke the EMV while the unit remains in a tripped state then jumper around the EMV 
shutdown contact so that the controller can be enabled for stroking.  Any such jumper MUST be removed prior 
to any start or crank of the unit.  (It is NOT recommended that a slave 24Vdc supply be used.)   

 
Figure 8 – A typical EMV enable/fault configuration 
 
3.6.2 Reset of the motor controller 
The Moog motor controller has no separate RESET input. Instead, the energising of the ENABLE input acts as 
the reset command.  If the controller is already powered up and enabled then a reset command requires that 
the ENABLE input signal be removed and then reapplied because it is the transition of the ENABLE input from 
OFF  to  ON  that  resets  the  controller.    Typically  the  UCP  will  provide  a  RESET  relay  in  parallel  with  the  EMV 
shutdown contact to allow any motor controller faults to be reset and cleared which would otherwise keep the 
motor controller disabled and locked out. 
3.6.3 Motor controller power‐up 
Upon completion of the initial power up sequence, the motor controller will be in a fault condition with the  
panel  LED  #1  (RED)  lit  and  the  fault  o/p  to  the  ECS  signalling  an  ‘EMV  controller  fault’  condition.    Assuming 
there are no EMV faults, the controller requires a reset command to clear the fault condition.  If the controller 
has been reset and is running OK then no panel LED’s should be lit.  Once the controller becomes activated 
with the application of the ENABLE signal and is running fault‐free then panel LED #4 (GREEN) will be lit. 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 15 of 48

3.7 EMV system fault diagnostics 
3.7.1 Controller fault relay 
The  motor  controller  contains  Built‐In  Test  Equipment  (BITE)  which  carry  out  self‐diagnostics  as  well  as 
monitoring the EMV system for particular fault conditions.  If BITE detects any motor controller or EMV system 
fault then it puts the controller’s ‘EMV controller fault’ relay into the fault condition.  The ECS monitors the 
status of the EMV controller fault’ relay and if the N/O contacts are open (closed contacts indicate a healthy 
controller)  then  the  ECS  assumes  there  is  an  EMV  system  fault.    The  ECS  is  programmed  to  trigger  a  unit 
shutdown  in  the  event  of  an  EMV  system  fault  and  so  the  hardwired  controller  fault  contact  is  the  primary 
trigger of a unit shutdown if there is an EMV system fault.  The presence of a standing EMV system fault will 
also prevent a unit start. 
3.7.2 Status flags sent via DeviceNet link 
Where  the  ECS  is  linked  to  the  EMV  via  a  DeviceNet  communications  link  then  additional  fault  information 
from the motor controller can be supplied to the ECS as individual fault flags.  These flags can be sent to the 
HMI for local display or interrogated within the ECS itself.  Where a DeviceNet link is not used for command 
communications (e.g. the FT55 Trent control systems) then this additional fault information can’t be passed to 
the  ECS  or  the  HMI.    For  such  motor  controllers  using  analogue  position  demand  &  feedback  links  then 
additional fault information can only be accessed directly from the motor controller itself. 
3.7.3 Controller panel HMI 
The motor controller fascia panel has a number of LEDs which can provide basic controller status information 
but the LEDs are quite limited in what they can tell you.  More usefully, the motor controller also has a local 
HMI  panel  with  an  LCD  display  and  some  pushbuttons  allowing  navigation  by  menu.    This  local  HMI  can  be 
used to display the detected controller faults from a defined list of fault conditions.  (The same HMI can be 
used  to  display  other  menus  that  allow  the  motor  controller  configuration  parameters  to  be  checked  or 
adjusted.) 
3.7.4 Controller GUI1 
If necessary the motor controller can also be connected directly to a PC via a communications link to a comms 
port on the motor controller.  If the PC has the appropriate Graphical User Interface (GUI) software to match 
the Moog DS200XP controller then the status of the motor controller can be interrogated from the PC.  The 
GUI provides access to similar lists of configuration parameters and fault status flags as the controller’s front 
panel display but it provides more comprehensive coverage.  (See Table 5 and Table 6 for fault listings).  The 
GUI will also allow data‐logging of control parameters directly from the motor controller to the PC.  These logs 
can be inspected later for fault diagnosis. 
3.7.5 ECS position error check 
All necessary self‐diagnostics and condition monitoring for an EMV can be done by the motor controller BITE 
alone.  However, as an independent check of EMV function, the ECS does monitor EMV position error based on 
the difference between the ECS position demand & feedback values.  If EMV position error measured by the 
ECS goes outside of the specified limits then the ECS will trigger a unit shutdown, even if the motor controller 
fault relay still indicates a healthy condition.  
3.7.6 EMV position switch 
The ‘valve closed’ position switch contacts on the EMV are monitored by the Plant Control System (PCS).  The 
switch  provides  independent  confirmation  that  the  EMV  valve  is  closed  when  expected  rather  than  relying 
entirely  on  the  valve  position  calculated  by  the  motor  controller.    This  position  switch  is  therefore  typically 
used within the PCS start sequence logic as a start permissive, i.e. the start sequence is aborted if the switch 
indicates the EMV is not closed when it ought to be during the start. 

                                                                 
1
 Refer to document LSF 0577 “DS2000XP Graphical User Interface Manual” (Moog Industrial Controls Division) for information on 
installing & using the Moog motor controller GUI. 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 16 of 48

4. EMV system fault­finding 
This  guide  is  intended  for  troubleshooting  problems  with  an  EMV  that  has  been  successfully  installed  & 
commissioned  but which is now causing unit shutdowns or preventing unit starts. 

4.1 Basic symptoms of an EMV problem 
There  are  three  basic  fault  conditions  in  an  installation  that  will  cause  a  previously  healthy  EMV  to  stop 
working and either trip the unit or else prevent unit starts:‐ 
1.  If the “EMV controller fault” relay operated by the motor controller signals a fault condition then 
the ECS is programmed to shutdown the unit. 
The hardwired fault contact of a motor controller provides a robust method of providing indication to 
the ECS and operator that controller has detected a fault.  Although the alarm is issued by the motor 
controller,  the  fault  may  not  be  related  to  the  controller  itself  and  may  instead  indicate  a  valve  or 
wiring problem. 
On  initial  power‐up  of  a  controller,  the  hardwired  fault  contact  will  be  in  an  unhealthy  state  until 
communications  have been established  and  the  controller  has  been  reset  i.e.  when  LED1  no  longer 
displays  red.    The  controller  does  not  have  an  independent  reset  coil,  a  reset  of  the  controller  is 
achieved by toggling the ENABLE input. A fault on the enable circuit to the controller may mean that 
the controllers don’t reset after power‐up. 
The  hardware  contact  provides  indication  of  a  common  fault  detected  by  the  controller  and  will 
normally be accompanied by any of the controller status bits sent via DeviceNet (where applicable) 
are unhealthy, but is not limited only to these status bits. 
2. If the EMV motor controller uses a DeviceNet communications link and this communications link is 
lost then the ECS is programmed to shutdown the unit. 
The ECS monitors a watchdog status bit sent over the DeviceNet link.  If the watchdog check fails then 
command and control of EMV is assumed lost and the ECS must shutdown the unit. 
3. If the ECS detects that the error between the position demand and actual position values within the 
ECS is out‐of‐limits then the ECS is programmed to shutdown the unit. 
The ECS continuously performs a position error check by comparing the valve actual position against 
the setpoint.  An error of more than X% for Y seconds will generate this shutdown2. 
A  position  error  shutdown  occurring  while  the  unit  is  running  may  suggest  that  either  drive  to  the 
valve  has  stopped  or  the  valve  has  stuck  in  position.  The  HMI  Historical  Trend  or  data  logs  can  be 
checked  to  determine  if  the  valve  maintained  position  or  dropped  suddenly.    If  the  valve  held 
position, valve stiction is likely and a stroke test of the valve should be conducted. If the valve appears 
to have closed rapidly before the setpoint, drive to the valve may have failed.  
 
For fault cases 1, 2 and 3 above, the ECS shuts down the unit by de‐energising and/or breaking the continuity 
of  the  hardwired  trip  string  in  the  Unit  Control  Panel  (UCP)  thus  removing  the  ENABLE  signal  to  the  motor 
controller.    (Other  dedicated  unit  trips  can  break  the  trip  string  which  has  the  same  effect  in  removing  the 
ENABLE  signal  but  these  are  not  flagged  up  as  EMV  shutdowns).    Without  the  ENABLE  signal  present,  a 
disabled motor controller switches off the drives to the EMV motor, allowing the failsafe action of the EMV 
return springs to close the valves. 
There are numerous faults that can cause one of the three fault conditions listed above to occur.  The tables 
included  in  the  rest  of  section  4  can  be  used  to  trace  the  fault  and  suggest  remedial  action  to  restore  the 
system  where  applicable.    In  some  cases  the  only  action  possible  will  be  the  replacement  of  the  EMV  or  its 
motor controller. 
 

                                                                 
2
 The typical test criteria for an EMV position error shutdown are a >5% error persisting for >5 seconds.  However, the particular position 
error test values in an ECS can differ between engines and applications so service personnel should always confirm what the correct test 
settings should be for position error detection. 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 17 of 48

4.2 EMV Fault‐Finding Table 
The following table provides a list of symptoms due to particular EMV system faults which may be encountered in‐service.   
Against each possible EMV fault the table lists the suggested service action to check if that particular fault is the cause of the EMV system problem.  More detail on particular service 
actions can be found in section 4.3. Although descriptions may vary slightly from installation to installation, the possible cause and suggested actions will be similar.   Any EMV related 
fault which has been identified by the control system or controller should result in one of the shutdowns tabled below. Where a unit has tripped either during normal operation or 
while on standby, the chart below should be used in the first instance for identifying the possible cause and suggested action. 
 
Table 1 – EMV system fault‐finding 
  Symptom  Possible Fault / Explanation    Suggested Action 
S1  Gas EMV reported as inoperative  A1  Check whether the gas EMV can be stroked normally or not. 
Gas EMV position switch fault If the gas EMV can be stroked normally, check the wiring & 
A2  function of the position switch 
Gas EMV valve fault If the gas EMV can be stroked normally, check if the EMV 
A3  flows any gas when stroked fully open.  If the actuator valve 
can be driven open but no gas flows there is a valve fault. 
Gas EMV actuator wiring fault If the gas EMV can’t be stroked, check the wiring to the EMV 
A4  actuator. 
S2  Liquid EMV reported as inoperative  Check whether the liquid EMV can be stroked normally or 
A5  not. 
Liquid EMV position switch fault If the liquid EMV can be stroked normally, check the wiring & 
A6  function of the position switch 
Liquid EMV valve fault If the liquid EMV can be stroked normally, check if the EMV 
flows any liquid when stroked fully open.  If the actuator 
A7  valve can be driven open but no liquid flows there is a valve 
fault. 
Liquid EMV actuator wiring fault If the liquid EMV can’t be stroked, check the wiring to the  
A8  EMV actuator. 
S3  Drift in the Liquid EMV flow calibration  Liquid valve DP pressure regulator fault  A9  If the LFMV can’t maintain a constant DP then the regulator 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 18 of 48

  Symptom  Possible Fault / Explanation    Suggested Action 


Fouling of the DP regulator is faulty or fouled.  Replace the regulator
S4  HAV reported as inoperative  A10  Check whether the HAV can be stroked normally or not. 
HAV control circuit fault If the HAV can be stroked normally but is not fully closed 
A11  when de‐energised, check the HAV control function.  Also 
check if the HAV thermostat has cut in. 
HAV valve fault If the HAV can be stroked normally, check if the HAV flows 
A12  any air when stroked fully open.  If the actuator can be driven 
open but no air flows there is a valve fault. 
HAV actuator wiring fault If the HAV can’t be stroked, check the wiring to the HAV 
A13  actuator. 
S5  ECS SHUTDOWN EMV controller is in fault A14  Check for faults on the unit HMI or the controller. 
(LSS65UC044, LSS65UC045, LSS65UC046) 
Wiring fault with motor controller fault  Check if other related EMV related faults are present.  If this 
Metering Valve Failure 
contact    is the case the fault is most likely genuine and not wiring 
Central / Primary / Secondary EMV 
fault with the controller fault contact.   
If the “fault” circuit isn’t OK then it can send a 
This ECS shutdown indicates a common fault has 
false signal of a controller fault to the ECS  Verify the wiring between the ECS Digital Input (DI) card and 
been signalled by one of the DS2000XP motor    the controller. 
controllers.  The shutdown is determined from 
an unhealthy condition of the hardwired fault  Jumper the fault contact terminals at the controller and 
contact of the motor controller in fault.    verify that the shutdown clears.  
ECS Digital Input (DI) card fault Check if other related EMV related faults are present. If this 
  is the case the fault is most likely genuine and not wiring 
fault with the digital input card.   
Jumper the fault contact terminals at the controller and 
  verify that the shutdown clears.  
DeviceNet communications fault Check for DeviceNet Communications SD.  The metering 
  valve fault will always come up when there is a standing  
DeviceNet communications fault. 

EMV Motor Drive Wiring fault   Inspect the motor drive wiring between controller and EMV. 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 19 of 48

  Symptom  Possible Fault / Explanation    Suggested Action 


EMV Resolver Wiring fault Inspect the motor resolver wiring between the controller and 
  the EMV. 

  Verify resolver resistors are fitted.
S6  ECS SHUTDOWN Power‐up sequence error Disconnect the DeviceNet cable at the ECS DeviceNet card, 
(LSS65UC001, LSS65UC002, LSS65UC003)  wait 60 seconds and reconnect.  Allow 60 seconds for 
Where the DS2000XP and / or ECS Rack has 
Device Net Communications Failure  communications to re‐establish. 
been powered off and back on, the power‐up 
Central / Primary / Secondary EMV   
sequence can result in lost communications. 
Applicable to FT125 applications only. 
This ECS shutdown means that the DeviceNet 
communications between the ECS and the 
DeviceNet wiring fault For new installations, verify correct DeviceNet wiring 
Moog DS2000XP controller(s) have stopped.  
  between the ECS rack and DS2000XP. Including cable 
The shutdown is determined from a status bit    
specification. 
received by the ECS over DeviceNet from the 
  
DS2000XP.  Inspect for loose connections and trapped insulation, 
  damaged cable insulation.  
Verify that a 120 Ohm termination resistor is fitted at each 
  end of the DeviceNet trunk line. 
Controller power failure Verify 144V DC power at controller(s). Confirm each PSU is 
providing 144V DC output. 
This shutdown will occur if power to the   
DS2000XP is lost. 
DeviceNet Bus voltage fault Verify 24V DC on the Pos (Red) and Neg (Black) of the 
  DeviceNet network. 
Motor controller fault   Review Controller faults on DS2000XP LCD and Moog GUI.  
ECS Rack DeviceNet card or configuration  Verify that the DeviceNet configuration is correct and if 
fault    necessary replace the card.  
S7  ECS SHUTDOWN Valve sticking Check HMI Historical Trend or data logs where available for 
(LSS65UC115, LSS65UC116, LSS65UC117)    signs of the valve actual position holding position and failing 
Valve Position Error Failure   to track the setpoint.  

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 20 of 48

  Symptom  Possible Fault / Explanation    Suggested Action 


Central / Primary / Secondary EMV  Stroke check the EMV, ensuring that the feedback tracks the 
  setpoint.  Verify that the position indicator on the valve also 
The ECS continuously performs a position error 
track the demand signal.  
check by comparing the valve actual position 
against the setpoint.  An error of more than 5%  Listen for an audible knock or chattering of the EMV while 
for 5 seconds will generate this shutdown    stoking it.  

  If the EMV has elapsed 50K hours, replace the valve.  
Controller ENABLE lost   Check the controller ENABLE signal wiring
Set the valve stroke enable in the ECS software and check for 
  24V DC and the enable contact of the controller. 
Controller power interruption   Check the 144VDC power supplies.
Controller fault   Check for other Controller related faults.
     
 
 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 21 of 48

A3 Gas EMV Visual Position Indicator Moves Normally – No Significant Gas Flow 
4.3 Actions & Checks  When Open 
(a)  With  the  actuator  energized,  the  position  indicator  shows  the  valve  is  in  the 
Gas EMV valve checks  fully open position, but there is no measurable gas flow. 
A1 Gas EMV Reported Inoperative  (b)  At several open positions, if there is no measurable fuel flow greater than the 
permitted  leakage  flow  (0.10  pound  or  45g  per  minute),  return  the  valve  to 
(a)  Visually  check  for  valve  operation  by  observing  for  movement  of  the  visual  Meggitt for repair. 
position indicator when the valve is cycled (energized and de‐energized). 
(b)  If visual position indicator moves normally, proceed to actions A2 and A3. If the  A4 Gas EMV Visual Position Indicator Will Not Move – Possible Actuator Fault 
visual position indicator does not move normally, proceed to action A4.   (a)  Remove  the  screws  securing  the  actuator  motor  terminal  block  junction  box 
cover. Check/verify that all wiring connections are correct and that the terminal 
A2 Gas EMV Visual Position Indicator Moves Normally – Possible Position  screws are tight. Check for continuity between the junction box terminals and 
Indicating Switch Fault  the motor amplifier connector. Locate and correct any external circuit faults. 
(a)  With the actuator de‐energized, visually verify that position indicator shows the 
valve  is  in  the  fully  closed  position.  If  the  visual  position  indicator  shows  the  Important! Be sure that power is off prior to opening the EMV’s junction
box or touching the electrical wires.
valve partially open and there is excessive leakage flow (more than 0.10 pound 
[45 g] per minute), return the valve to Meggitt for repair.   (b)  Remove  power  and  disconnect  the  electrical  power  input  lead  wires  from 
(b)  Remove the screws securing the closed position indicating switch junction box  terminals 1, 2 and 3 of the terminal block. If the actuator is hot, allow sufficient 
cover.   time for the windings to cool to room temperature (60 to 80°F [16 to 26°C]). 

(c)  With  the  actuator  de‐energized  and  the  visual  position  indicator  showing  the  (c)  Measure  the  resistance  between  terminals  1  and  2  (Brown‐Red),  terminals  1 
valve in the fully closed position, verify that continuity exists between the C and  and 3 (Brown‐White), and terminals 2 and 3 (Red‐White) of the terminal block. 
NC  switch  terminals.  If  an  open  circuit  exists,  manually  actuate  the  closed  With the motor windings at room temperature, each resistance value must be 
position  indicating  switch  while  monitoring  for  continuity  between  the  C  and  0.288  ohms  (±10%).  If  the  resistance  value  is  satisfactory,  reconnect  the 
NC switch terminals.  electrical power input lead wires to terminals 1, 2 and 3 (tighten the terminal 
screws to within 3.5 to 5.3 inch‐pounds [0.4 to 0.6 Nm] torque) and proceed to 
(d)  If  the  closed  position  indicating  switch  functions  normally  (opens  and  closes),  step  D  below.  If  the  resistance  value  is  not  within  the  specified  limits,  return 
adjust the switch to close when the valve is within 0.020 inch (0.51 mm) from  the valve to Meggitt for repair. 
the fully closed position. If the switch will not function or cannot be adjusted, 
replace the switch.  (d)  Measure the resistance of the resolver coils. The resistance values must be as 
follows:‐ 
(e)  Energize  the  actuator  and  verify  that  the  closed  position  indicating  switch 
operates correctly.    Red/White to Yellow/White (E to F) ................................. 24.3 ‐ 34.1 ohms 
  Red to Black (A to B) ............................................................ 57.6 ‐ 99 ohms 
  Yellow to Blue (C to D) ......................................................... 57.6 ‐ 99 ohms 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 22 of 48

  If any of the resistance values is not within the specified limits, return the valve  (d)  If  the  closed  position  indicating  switch  functions  normally  (opens  and  closes), 
to Meggitt for repair.  adjust the switch to close when the valve is within 4 to 6 degrees from the fully 
closed  position.  If  the  switch  will  not  function  or  cannot  be  adjusted,  replace 
(e)  Measure  the  resistance  of  the  motor  coils.  With  the  motor  windings  at  room 
the switch. 
temperature, the resistance must be as follows: 
(e)  Energize  the  actuator  and  verify  that  the  closed  position  indicating  switch 
  Brown wire to Red wire ................................................... 0.288±10% ohms 
operates correctly. 
  Red wire to White wire .................................................... 0.288±10% ohms 
  White wire to Brown wire ................................................ 0.288±10% ohms 
A7 Liquid EMV Visual Position Indicator Moves Normally – No Significant Fuel 
(f)  If  the  wiring  connections  and  the  resistance  values  are  verified  to  be  correct,  Flow When Open 
and the valve still will not operate, return the valve to Meggitt for repair. 
(a)  With  the  actuator  energized,  the  position  indicator  shows  the  valve  is  in  the 
fully open position, but there is no measurable fuel flow. 
Liquid EMV valve checks 
(b)  At several open positions, if there is no measurable fuel flow greater than the 
A5 Liquid EMV Reported Inoperative  permitted leakage flow (0.6 gpm or 2.27 l/min), return the valve to Meggitt for 
repair. 
(a)  Visually  check  for  valve  operation  by  observing  for  movement  of  the  visual 
position indicator when the valve is cycled (energized and de‐energized). 
A8 Liquid EMV Visual Position Indicator Will Not Move – Possible Actuator Fault 
(b)  If visual position indicator moves normally, proceed to actions A6 and A7. If the 
 (a)  Remove  the  lock  screws  securing  the  actuator  motor  terminal  block  junction 
visual position indicator does not move normally, proceed to action A8. 
box  cover,  unscrew  the  cover.  Check/verify  that  all  wiring  connections  are 
correct  and  that  the  terminal  screws  are  tight.  Check  for  continuity  between 
A6 Liquid EMV Visual Position Indicator Moves Normally – Possible Position 
the  junction  box  terminals  and  the  motor  amplifier  connector.  Locate  and 
Indicating Switch Fault 
correct any external circuit faults. 
(a)  With the actuator de‐energized, visually verify that position indicator shows the 
valve  is  in  the  fully  closed  position.  If  the  visual  position  indicator  shows  the  Important! Be sure that power is off prior to opening the EMV’s junction
valve partially open and there is excessive leakage flow (more than 0.6 gpm or  box or touching the electrical wires.
2.27 l/min), return the valve to Meggitt for repair. 
 (b)  Remove  power  and  disconnect  the  electrical  power  input  lead  wires  from 
(b)  Remove the screws securing the closed position indicating switch junction box  terminals  U,  V  and  W  of  the  terminal  block.  If  the  actuator  is  hot,  allow 
cover.  sufficient time for the windings to cool to room temperature (60 to 80°F) (15 to 
27°C). 
(c)  With  the  actuator  de‐energized  and  the  visual  position  indicator  showing  the 
valve in the fully closed position, verify that continuity exists between the C and 
NC  switch  terminals.  If  an  open  circuit  exists,  manually  actuate  the  closed 
position  indicating  switch  while  monitoring  for  continuity  between  the  C  and 
NC switch terminals. 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 23 of 48

(c)  Measure the resistance between terminals U and W (Black), terminals U and V  (b)  If visual position indicator moves normally, proceed to actions A11 and A12. If 


(Black‐White), and terminals V and W (Red‐White) of the terminal block. With  the visual position indicator does not move normally, proceed to action A13.  
the  motor  windings  at  room  temperature,  each  resistance  value  must  be  4.9 
ohms  (±10%).  If  the  resistance  value  is  satisfactory,  reconnect  the  electrical  A11 HAV Visual Position Indicator Moves Normally ‐ Possible Control Circuit Fault  
power input lead wires to terminals U, V and W (tighten the terminal screws to 
(a)  With the actuator de‐energized, visually verify that position indicator shows the 
within  3.5  to  5.3  inch‐pounds  [0,4  to  0,6  Nm]  torque)  and  proceed  to  step  D 
valve  is  in  the  fully  closed  position.  If  the  visual  position  indicator  shows  the 
below.  If the resistance value is not within the specified limits, return the valve 
valve partially open and there is excessive leakage flow.  
to Meggitt for repair. 
(b)  From  the  controller,  check  all  of  the  fault  indicators  for  normal  indications. 
(d)  Measure the resistance of the resolver coils. The resistance values must be as 
Make  sure  that  the  valve  is  correctly  commanded  and  that  there  is  not  a 
follows:‐ 
feedback or communication problem.  
  Red/White to Yellow/White  .......................................... 24.3 to 34.1 ohms 
(c)  Check  the  valve  thermostat  circuit  for  continuity.  If  the  thermostat  is  open, 
  Red to Black ....................................................................... 57.6 to 99 ohms 
allow  sufficient  cooling  time  for  it  to  reset.  If  the  thermostat  will  not  reset. 
  Yellow to Blue .................................................................... 57.6 to 99 ohms 
return the valve to Meggitt for repair.  
  If any of the resistance values is not within the specified limits, return the valve 
to Meggitt for repair.  A12 HAV Visual Position Indicator Moves Normally ‐ No Significant Gas Flow When 
Open  
(e)  If  the  wiring  connections  and  the  resistance  values  are  verified  to  be  correct, 
and the valve still will not operate, return the valve to Meggitt for repair.  (a)  With  the  actuator  energized,  the  position  indicator  shows  the  valve  is  in  the 
fully open position, but there is no measurable gas flow.  
A9 Liquid EMV fails to maintain 90‐120 psid between Pin and Pout, and the flow 
(b)  At several open positions, if there is no measurable gas flow greater than the 
characteristic drifts from standard. 
permitted leakage flow, return the valve to Meggitt for repair. 
(a)  Where the fuel particulate contamination is known to be an issue, the pressure 
regulator can become clogged, seize and cease to function.  A13 HAV Visual Position Indicator Will Not Move – Possible Actuator Fault  
(b)  The preferred course of action is to return the valve to Meggitt for overhaul.  (a)  Access  the  electrical  connections  at  the  external  terminal  block.  Check/verify 
that all wiring connections are correct and that the terminal screws are tight. 
(c)  The  alternative  action  to  (b)  is  to  purchase  a  replacement  regulator 
Check for continuity between the terminals and the motor amplifier connector. 
(C236825‐1)  and  replace  per  part  3  of  the  REPAIR  section  in  the  C236765 
Locate and correct any external circuit faults.  
manual. 
Important! Be sure that power is off prior to opening the EMV’s junction
Hot Air Valve (HAV) checks  box or touching the electrical wires.

A10 HAV Reported Inoperative    (b)  Remove  power  and  disconnect  the  electrical  power  input  lead  wires  from 
terminals. If the actuator is hot, allow sufficient time for the windings to cool to 
(a)  Visually  check  for  valve  operation  by  observing  for  movement  of  the  visual 
room temperature (60 to 80°F [16 to 26°C).  
position indicator when the valve is cycled (energized and de‐energized).  

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 24 of 48

(c)  Measure  the  resistance  of  the  motor  coils.  With  the  motor  windings  at  room  controller.  The removed controller will need to be returned to the supplier for repair.  
temperature, the resistance must be as follows:‐  If the BITE identifies an external fault as the cause of the problem then, depending on 
what  the  fault  is,  it  should  be  possible  to  restore  the  system  to  health  by  fixing  the 
  Brown wire to Red wire .......................................................... 0.4 Ω (±10%)  
external fault. 
  Red wire to White wire  .......................................................... 0.4 Ω (±10%)  
  White wire to Brown wire ....................................................... 0.4 Ω (±10%)    
  If the resistance value is satisfactory, reconnect the electrical power input lead 
wires  to  their  assigned  (tighten  the  terminal  screws  to  within  3.5  to 5.3  inch‐
pounds  torque)  and  proceed  to  step  D  below.  If  the  resistance  value  is 
significantly  outside  of  the  specified  limits,  return  the  valve  to  Meggitt  for 
repair.  
(d)  Disconnect  and  measure  the  resistance  of  the  resolver  coils.  The  resistance 
values must be as follows:‐ 
  Red/White wire to Yellow/White wire ................................ 24.3 Ω ‐ 34.1 Ω  
  Red wire to Black wire ............................................................ 57.6 Ω ‐ 99 Ω  
  Yellow wire to Blue wire ......................................................... 57.6 Ω ‐ 99 Ω  
  If  any  of  the  resistance  values  is  significantly  outside  of  the  specified  limits, 
return the valve to Meggitt for repair. 

EMV motor controller checks 

A14 Interrogate motor controller diagnostics  
Upon  any  indication  that  a  motor  controller  is  in  a  genuine  fault  condition,  all  the 
following  motor  controller  diagnostics  (where  available)  should  be  inspected  to  find 
out  if  the  motor  controller  BITE  has  identified  the  particular  fault  condition  that  has 
put the controller into fault:‐ 
(a)  Unit HMI status    (refer to section 5.1 for details) 
(b)  Front Panel LEDs    (refer to section 5.2 for details) 
(c)  Front Panel HMI Display  (refer to section 5.3 for details) 
(d)  Motor controller GUI   (refer to section 5.4 for details) 
If the motor controller BITE detects an internal controller fault as the cause of an EMV 
shutdown then the only way to restore the EMV system is to fit a replacement motor 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 25 of 48

5. Appendix – Diagnostic information available from the DS2000XP Motor Controller  

5.1 Motor controller fault status reported to the unit HMI  
The  following table  lists  the EMV  controller  faults  which are  reported  on  the  FT210  HMI.    These  HMI  flags  are  based  on  the  controller  fault status  information  supplied over  the 
DeviceNet network to the ECS.  This EMV fault information is only available on the HMI if the EMV is connected with a DeviceNet communications link. 
Table 2 only lists the most commonly detected faults within the controller.  The motor controller can detect a number of other faults which are not reported to the HMI but which 
trigger a shutdown via the hardwired “EMV fault” relay contact on the controller. 
 
Table 2 – EMV fault status information reported to the unit HMI via DeviceNet  
Unit HMI Controller Fault  Description    Action 
Flags that  the DeviceNet communications between the ECS 
EMV DeviceNet Communications  and the Moog DS2000XP controller(s) have stopped.  The 
 
Failure  shutdown is determined from a status bit received by the ECS   
over DeviceNet from the DS2000XP. 
Detects the BUS overvoltage condition;
the drive cuts off the current. This can be due to a recovery 
EMV Bus Overvoltage Fault  resistance interruption or the resistance value is too high for  a.  Check 144VDC bus supply voltage meets the specification. 
the application and it cannot dissipate the energy recovered  b.  Verify the drive configuration parameters “motor bus voltage 
by the motor and the drive.    (drv.mtrbus)” = 110.  
Detects the BUS undervoltage condition; c.  Verify there is no Connection to Recovery Resistor on the Drive. 
the drive cuts off the current. This can be  d.  Check for faulty 24V‐>144VDC supply. 
EMV Bus Undervoltage Fault  e.  Check for an Actuator drawing too much current. 
due to a power line interruption or to an excessive current 
absorption by the drive with respect to the resistance  f.  Possible Faulty Drive; Replace the Drive. 
Detects the lack of DC BUS or a value lower than 80 V 
EMV No Bus Voltage Fault   
(minimum default factory set value). 
EMV Bus Voltage Rate of Change   
EMV Bus Reading Fault   
a. Verify the drive fan is working if the drive fan exists.   
Indicates the drive heat‐sink over‐temperature. This can be 
caused by the drive operating with current higher than the  b.  Check current draw of actuator for abnormally high current 
EMV Drive Overtemperature Fault  drive can supply.  This may also be an indication of improper    levels.  If levels are high replace the actuator.   
drive cooling.  c.  Turn off drive and let cool, If fault appears after cooling replace 
the drive. 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 26 of 48

Unit HMI Controller Fault  Description    Action 


a. Reload parameter set
Indicates a control cards exchange between two different size  b.  Verify the correct drive model number is used 
EMV Drive Size Fault  drives.    
c.  If still exists download parameters, and perform a “Save 
Parameters” from the “Utility Menu” 
a. Power cycle the Drive
b.  If still exists download parameters, and perform a “Save 
EMV EEPROM Checksum Fault  Indicates an internal memory error.    Parameters” from the “Utility Menu” 
c.  Attempt another full Power Cycle 
d.  Possible Faulty Drive; Replace the Drive 
Indicates an error in the internal Try to switch the drive off and cut off the line. In case the FAULT 
EMV Flash EEPROM Read Fault  reading of the parameters memorized inside the drive; it is    persists, try to re‐set parameters and save all data again; if the error 
possible a reading error in the internal memory.  persists the section is damaged 
EMV Home LS Fault   
EMV Home Time Fault   
Indicates that the +15 V internal power value is out of  a. Check 144VDC bus supply voltage meets the specification. 
EMV +15 volt Fault    b.  Verify the J2B pin 1 on the control head has no connection and is 
tolerance 
not under load 
c.  If intermittent Monitor drive load under normal operation and 
Indicates that the ‐15 V internal power value is out of  check for abnormally high loads.  If spikes occur in parallel with 
EMV ‐15 Volt Fault    15 volt supply fault check actuator condition 
tolerance 
d.  Check for excessive ambient heat 
e.  Possible Faulty Drive; Replace the Drive 
Indicates that the max speed set inside the drive has been  This fault is disabled in the DSP
EMV Motor Overspeed Fault   
exceeded more than 12%.    
This fault is disabled in the DSP
EMV Motor Temperature Fault  Indicates the motor over‐temperature.      Check the application size, during the cycle an effective current higher 
than the one the motor can manage is absorbed. 
EMV Position Error Fault   
EMV Position Home Fault   
EMV Pre Home Fault   

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 27 of 48

Unit HMI Controller Fault  Description    Action 


a. Check Resolver Wiring 
b.  Verify Drive Parameters drv.respoles, tstif.respoles 
Indicates the presence of errors on the connection signals  c.  Check Resolver Supply Voltage 20VPP @ 10KHZ with no load.  If 
EMV Resolver Fault  inside the resolver section.   
incorrect voltage replace drive.  
d.  If Connections, parameters, and drive supply are correct replace 
actuator. 
a. Remove high power and allow drive voltage to dissipate.  
Measure voltage at the drive input for safe working voltages 
before proceeding  
Detects the excess current or short circuit condition of the  b.  Verify system is shielded and grounded properly 
output IGBT three‐phase bridge or the recovery circuit IGBT.   c.  Check drive outputs(U2, V2, W2) with and ohmmeter for short 
EMV UVW Phase IGBT Fault  This can be generated by noise from an improperly shielded   
system or a shorted IGBT on the drive power stage.    circuit from each output phase to all other output phases 
d.  Check drive outputs for phase to chassis ground short circuits. 
e.  If fault is permanent and the shorts are measured replace the 
drive.   
 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 28 of 48

5.2 Front panel LED status information 
There are four LED’s on the front of the DS200XP controller which can be used to provide some basic controller diagnostic information. 
 
Table 3 – Controller panel LED status information 
1  2  3  4  Controller LED status  Description    Action 
Controller HEALTHY but NOT ENABLED N/A – NO FAULT
        All LEDs OFF 
Controller POWERED DOWN N/A – NO FAULT
This will occur at power‐up. Toggle the ENABLE input to 
 
CONTROLLER FAULT  reset the controller. 
        LED #1 (RED) ON 
Any fault detected by controller BITE will light LED #2  Verify that the ENABLE is toggling 24V on a UCP reset. 
Check Controller Diagnostics for further information 
        LED #2 (YELLOW) ON  CURRENT FOLDBACK FAULT (warning or error) Check Controller Diagnostics for further information 
APPLICATION CODE NOT RECOGNISED 
    Perform a configuration download (refer to GUI Manual) 
Model is not running, the controller may have detected a 
      LED #2 (YELLOW) FLASHING 
mismatch in the database on power up and then reverted 
    Check Controller Diagnostics for further information 
back to factory defaults. 
        LED #3 (YELLOW) ON  POSITION FOLLOWING ERROR Check Controller Diagnostics for further information 
Check Valve controller wiring.
        LED #2 & #3 (YELLOW) ON  HOMING FAULT 
Check Controller Diagnostics for further information 
        LED #4 (GREEN) ON  DRIVE ENABLED N/A ‐ NO FAULT
 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 29 of 48

5.3  Front panel HMI display information 
The Moog controller has a built in panel LCD display which may be used to provide some basic diagnostic information. This can 
be particularly useful where there is no fault information available on the control system HMI but the controller has tripped on 
EMV Controller Fault. 
The six keys on the DS2000XP front panel allow the visualization of the whole menu as well as the relevant drive configuration. 
A further key allows the display contrast adjustment. 
The keys can be divided according to their function: 
ENTER     This key allows to enter a menu and browse it. The variables scanning inside a menu is recursive. In some cases, this 
key activates a routine function (i.e. inside the ?Utility? menu). 
< and >    These keys allow the menu horizontal scrolling from right to left and vice versa. 
+  and ‐    These keys allow to increase and decrease a variable. Holding the key down approx. 5 s the fast forward starts. 
ESC  This  key allows to go back inside the menu or terminate a function. 
  Holding down the yellow key, it is possible to adjust the display contrast by means of the + / ‐ keys. In order to keep 
the setting, it is necessary to save the parameters before switching off the drive. 
Notes 
1.  First screen at drive start‐up show you the DS2000XP size. The DRIVE ENABLE and REFERENCE ENABLE signals are shown in the start‐up screen on the display by two stylised 
letters: D? and ?R? respectively. 
2.  The first menu level can be accessed pressing ENTER. The first level is characterized by the two < and > arrows which indicate the possibility of scrolling the menu from right to 
left.  Once in the first menu level, to access the Fault Detection menu, press the > key until “Fault Detection” is displayed and press ENTER.  The controller will auto scroll to the 
first active fault.  
3.  To exit the menu, press ESC.  Keep on pressing if the displayed parameter is not the first item of the menu. 
4.  The main menu is not circular; when the bottom is reached, press ESC or < to go back.  The ENTER button can be used to go forward through the menu. 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 30 of 48

The following table lists the EMV controller faults which may be reported on the DS2000XP panel display. 
Table 4 – Controller LCD “fault detection” menu display  
LCD “Fault Detection” item Description    Action
IGBT FAULT U PHASE/HS 
a.  Remove high power and allow drive voltage to dissipate.  
IGBT FAULT V PHASE/HS  Measure voltage at the drive input for safe working voltages 
before proceeding  
IGBT FAULT W PHASE/HS  Detects the excess current or short circuit condition of the output  b.  Verify system is shielded and grounded properly 
IGBT three‐phase bridge or the recovery circuit IGBT.  This can be 
generated by noise from an improperly shielded system or a    c.  Check drive outputs(U2, V2, W2) with and ohmmeter for short 
IGBT FAULT U PHASE/LS  circuit from each output phase to all other output phases 
shorted IGBT on the drive power stage.   
d.  Check drive outputs for phase to chassis ground short circuits. 
IGBT FAULT V PHASE/LS  e.  If fault is permanent and the shorts are measured replace the 
drive.   
IGBT FAULT W PHASE/LS 
It detects the excess current or short circuit condition of the 
IGBT FAULT RECOVERY  recovery circuit IGBT.     
Detects the BUS overvoltage condition; the drive cuts off the 
current. This can be due to a recovery resistance interruption or 
BUS OVERVOLTAGE  the resistance value is too high for the application and it cannot 
dissipate the energy recovered by the motor and the drive.  a.  Check 144VDC bus supply voltage meets the specification. 
Detects the BUS under‐voltage condition; the drive cuts off the  b.  Verify the drive configuration parameters “motor bus voltage 
current. This can be due to a power line interruption or to an  (drv.mtrbus)” = 110.  
BUS UNDERVOLTAGE  excessive current absorption by the drive with respect to the    c.  Verify there is no Connection to Recovery Resistor on the Drive. 
resistance.  d.  Check for faulty 24V‐>144VDC supply. 
Detects the DC BUS variation at DRIVE ON when the supplied  e.  Check for an Actuator drawing too much current. 
UNSTABLE BUS AT DRIVE ON  power is low (reduced or null speed). This could be due to a fuse  f.  Possible Faulty Drive; Replace the Drive. 
interruption on the three‐phase line. 
Detects the lack of DC BUS or a value lower than 80 V (minimum 
NO BUS  default factory set value). 
a. Check 144VDC bus supply voltage meets the specifications.   
b.  Verify the drive configuration parameters “motor bus voltage 
BUS/MOT.VOLTAGE  Detects the wrong setting of motor voltage rating with respect to  (drv.mtrbus)” = 110 
UNCOMPATIBLE  the voltage detected on DCBUS.   
c.  Check drive bus reading “dsp measured bus voltage (dpr.vbus)” 
d.  Possible Faulty Drive; Replace the Drive 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 31 of 48

LCD “Fault Detection” item Description    Action


Indicates the wrong value used for the recovery resistor in 
connection to the line voltage. A wrong Ohm‐value (lower than the  a.  Verify parameters rgn_g_powext=250, rgn_g.resext = 33.   
RES.REC./MAIN  recommended one) causes a recovery IGBT damage due to over‐
UNCOMPATIBLE    b.  Verify there is no connection at terminal RR.   
current. Attention: A value higher than the recommended one can  c.  Possible Faulty Drive; Replace the Drive 
prevent braking in max supplied current condition at max speed. 
SYSTEM ERROR ON VBUS  It indicates an anomaly inside the voltage reading system on DC  a. Try to switch the drive off and cut off the line.
DETECT  BUS   
b.  In case the FAULT persists the drive is broken. 
a. Power cycle the Drive
b.  If still exists download parameters, and perform a “Save 
FLASH‐ERROR DEFAULT  Indicates an error in the internal reading of the parameters in the  Parameters” from the “Utility Menu” and reload configuration.   
 
SETTING  drive.  
c.  Attempt another full Power Cycle 
d.  Possible Faulty Drive; Replace the Drive 
a. Verify the drive fan is working if the drive fan exists.   
Indicates the drive heat‐sink over‐temperature. This can be caused  b.  Check current draw of actuator for abnormally high current 
HEATSINK FAULT  by the drive operating with current higher than the drive can    levels.  If levels are high replace the actuator.   
supply.  This may also be an indication of improper drive cooling.  c.  Turn off drive and let cool, If fault appears after cooling replace 
the drive. 
This fault is disabled in the DSP
MOTOR FAULT 
OVERTEMPERATURE  Indicates the motor over‐temperature.      Check the application size, during the cycle an effective current higher 
than the one the motor can manage is absorbed. 
Indicates that the max speed set inside the drive has been  This fault is disabled in the DSP
OVERCOME MAX. SPEED  exceeded more than 12%.    
 

An ENCODER is not used in this application.  All the R‐R EMVs use a 
RESOLVER. 
UVW ENCODER DETECTION  Indicates the presence of errors on the connection signals inside  .  Verify on the GUI Drive Configuration Screen that the 
 
ERROR  the encoder section.  Position/Speed Fdbck Source is Resolver 
b.  Verify parameter “drv.posfbsrc = 2” 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 32 of 48

LCD “Fault Detection” item Description    Action

ENCODER PULSES DETECTION 
ERROR 

 
a. Check Resolver Wiring 
b.  Verify Drive Parameters drv.respoles, tstif.respoles 
Indicates the presence of errors on the connection signals inside  c.  Check Resolver Supply Voltage 20VPP @ 10KHZ with no load.  If 
FAULT RESOLVER  the resolver section.   
incorrect voltage replace drive.  
d.  If Connections, parameters, and drive supply are correct replace 
actuator. 
a.  Check 144VDC bus supply voltage meets the specification. 
+15 SUPPLY FAULT  Indicates that the +15 V internal power value is out of tolerance.  b.  Verify the J2B pin 1 on the control head has no connection and is 
not under load 
c.  If intermittent Monitor drive load under normal operation and 
  check for abnormally high loads.  If spikes occur in parallel with 
15 volt supply fault check actuator condition 
‐15 SUPPLY FAULT  Indicates that the ‐15 V internal power value is out of tolerance.  d.  Check for excessive ambient heat 
e.  Possible Faulty Drive; Replace the Drive 
a. Reload parameter set
Indicates a control cards exchange between two different size  b.  Verify the correct drive model number is used 
FAULT SIZE  drives.    
c.  If still exists download parameters, and perform a “Save 
Parameters” from the “Utility Menu” 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 33 of 48

LCD “Fault Detection” item Description    Action


a. Power cycle the Drive
b.  If still exists download parameters, and perform a “Save 
FLASH ERROR CHECKSUM  Indicates an internal memory error.    Parameters” from the “Utility Menu” 
c.  Attempt another full Power Cycle 
d.  Possible Faulty Drive; Replace the Drive 
Indicates that the IGBT protection begin active for excessive phase  This fault should be disabled in the Drive.
IGBT FAULT I2T PROTECTION  current at locked rotor or very low speed condition.   
a.  Verify parameters:‐  igbt.fltena =0, igbt.run = 0.  
a. Verify parameters:‐
Indicates an excessive estimated temperature of the recovery      rgn_g_powext=250, rgn_g.resext = 33.  
FAULT RR PROTECTION   
resistor.  b.  Verify there is no connection at terminal RR.   
c.  Possible Faulty Drive; Replace the Drive 
END OF SCANNING Press ENTER for exit  
 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 34 of 48

5.4 Motor controller, GUI information 
If a PC is available that has had the Moog controller GUI application software loaded then it can be connected to the RS232 port on the controller (using a suitable communications 
cable).  With the GUI available, the controller configuration and fault status can be interrogated directly from the controller.  The GUI provides access to similar lists of controller 
parameters and fault conditions as the controller’s fascia panel LCD display but provides more comprehensive coverage.  For this reason the same faults appear in both Table 4 and 
Table 5 and the recommended service action will be similar. 
The GUI should only be used if other fault‐diagnostics are unable to trace a problem with the motor controller. 
Table 5 – Controller GUI display: MCC faults 
GUI – “MCC Fault” item Description    Action
a. Verify on the Drive Configuration Screen that the model is 
DYNAMIC POS. FOLLOWING  Indicates while the actuator is in motion it has exceeded the  enabled 
ERROR  dynamic position error limit.  This limit is settable via the Combined    b.  Verify parameter Set (mdlrun = 1, drv.dynposwin = N/A) 
Tuning screen parameter set. 
c.  This fault is not used while the model is running 
a. Verify on the Drive Configuration Screen that the model is 
STATIC POS FOLLOWING  Indicates while the actuator is stationary it has exceeded the static  enabled 
ERROR  position error limit.  This limit is settable via the Combined Tuning    b.  Verify parameter Set (mdlrun = 1, drv.staposwin = N/A) 
screen parameter set. 
c.  This fault is not used while the model is running 

     

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 35 of 48

GUI – “MCC Fault” item Description    Action


a. Verify the CAN cable connection
b.  Power cycle the drive and the Host connection 
c.  Verify parameters model execution rate(mdlrte) = 2 if using 
FIELDBUS COMMS ERROR  Indicates the Fieldbus(Can bus) is not responding    device net, or model execution rate(mdlrte) = 1 if using analog 
d.  Verify “Controller Sample Period” = 0.00025 for an analog system, 
and Controller Sample Period = 0.0005 for a device net system. 
e.  Replace Drive 
a. Verify the host command algorithm.
b.  Verify parameters model execution rate(mdlrte) = 2 if using 
device net, or model execution rate(mdlrte) = 1 if using analog 
COMMAND BUFFER FULL  Drive is receiving more commands on the Fieldbus than can be   
processed causing Buffer overrun   c.  Verify “Controller Sample Period” = 0.00025 for an analog system, 
and Controller Sample Period= 0.0005 for a device net system. 
d.  Verify on the Combined Tuning screen that 
Reference Source = Bus. 
a. Verify the CAN cable
b.  Verify the host command algorithm. 
c.  Verify parameters model execution rate(mdlrte) = 2 if using 
device net, or model execution rate(mdlrte) = 1 if using analog 
d.  Verify “Controller Sample Period” = 0.00025 for an analog system, 
Occurs when the Reference source has no command.  If the  and Controller Sample Period= 0.0005 for a device net system. 
COMMAND BUFFER EMPTY  Reference Source is configured for BUS but no command is received    e.  Verify on the Combined Tuning screen that 
over the Fieldbus this fault will occur.    Reference Source = Bus. 

 
INTERPOLATION FAULT     This fault is not used

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 36 of 48

GUI – “MCC Fault” item Description    Action


a. Check Parameters on Combined Tuning, Drive Configuration 
screens and verify the Controller Parameter Database. 

PARAMETERS INVALID  Certain Configuration Parameters are out of range.      Lower limit

upper limit

Actual setting

 
PLL TIMEOUT  Phase Lock Loop cannot lock into fieldbus time synchronization.    Only used in Serco Fieldbus communications.
a. Cycle drive power
MODEL ERROR  Drive Model code is corrupt    b.  Perform a File‐>EEPROM save‐>Model Save and click Write 
Parameters and cycle power. 
c.  Replace drive 

The EMVs use a RESOLVER not an ENCODER 
UNKNOWN ENCODER  The encoder connected to the DS2000XP was not recognised as a   
supported type  a.  Verify on the GUI Drive Configuration Screen that Position/Speed 
Fdbck Source is set to Resolver 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 37 of 48

GUI – “MCC Fault” item Description    Action

ENCODER CHECKSUM ERROR  The EEPROM onboard the encoder has an invalid checksum  

ENCODER SERIAL TIMEOUT  An error was detected on the Sin/cosine line of the encoder 

ENCODER CALIBRATION  The position calibration of the encoder failed 
FAULT 

 
b.  An encoder is not used in this application Verify parameter 
“drv.posfbsrc = 2” 
a. Check Resolver Wiring 
b.  Verify Drive Parameters drv.respoles, tstif.respoles 
FAULT RESOLVER  Indicates the presence of errors on the connection signals inside the    c.  Check Resolver Supply Voltage 20VPP @ 10KHZ with no load.  If 
resolver section  incorrect voltage replace drive.  
d.  If Connections, parameters, and drive supply are correct replace 
actuator.   
a.  Check 144VDC bus supply voltage meets the specification. 
+15 SUPPLY FAULT  Indicates that the +15 V internal power value is out of tolerance.  b.  Verify the J2B pin 1 on the control head has no connection and is 
not under load 
c.  If intermittent Monitor drive load under normal operation and 
  check for abnormally high loads.  If spikes occur in parallel with 
15 volt supply fault check actuator condition 
‐15 SUPPLY FAULT  Indicates that the ‐15 V internal power value is out of tolerance.  d.  Check for excessive ambient heat 
e.  Possible Faulty Drive; Replace the Drive 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 38 of 48

GUI – “MCC Fault” item Description    Action


a. Reload parameter set
FAULT SIZE  Indicates a control cards exchange between two different size    b.  Verify the correct drive model number is used 
drives.   c.  If still exists download parameters, and perform a “Save 
Parameters” from the “Utility Menu” 
a. Power cycle the Drive
Indicates an internal memory error.  b.  If still exists download parameters, and perform a “Save 
FLASH ERROR CHECKSUM    Parameters” from the “Utility Menu” 
  c.  Attempt another full Power Cycle 
d.  Possible Faulty Drive; Replace the Drive 
a. Verify parameters rgn_g_powext=250, rgn_g.resext = 33.  
Indicates an excessive estimated temperature of the recovery 
FAULT RR PROTECTION  resistor.    b.  Verify there is no connection at terminal RR.   
c.  Possible Faulty Drive; Replace the Drive 
a. Measure the DC Supply and look for variations in the 144VDC 
SYSTEM ERROR ON VBUS  supply voltage.   
Indicates an anomaly inside the voltage reading system on DC BUS.    
DETECT  b.  Switch the drive off and cut off the line. If the FAULT persists, the 
drive is broken. 
a. Reload parameter set
INVALID DRIVE SIZE  The stored value of the Drive Size and the actual Size of the Power    b.  Verify the correct drive model number is used 
Stage are different.    c.  If still exists download parameters, and perform a “Save 
Parameters” from the “Utility Menu” 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 39 of 48

GUI – “MCC Fault” item Description    Action


Perform a File‐>EEPROM save‐>Factory Save and click Write 
Parameters. 

FACTORY CONFIG INVALID  Factory Parameters are not configured properly.     

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 40 of 48

GUI – “MCC Fault” item Description    Action


a. Verify parameters model execution rate(mdlrte) = 2 if using 
device net, or model execution rate(mdlrte) = 1 if using analog 
b.  Verify “Controller Sample Period” = 0.00025 for an analog system, 
and Controller Sample Period= 0.0005 for a device net system. 

The model could not execute in the allotted time.  The drive 
MODEL OVERRUN ERROR  parameter set must be set so the model has sufficient time to   
execute it’s commands. 

 
a. Verify Overcurrent timeout on the Drive Configuration Screen is 
properly set for the application: “I2T time”= 0.5. 
I2T FAULT  The I2T(current limiting) time has expired.   
b.  Verify Parameter igbt.fltena = 0 
c.  Verify the motor/actuator is not jammed. 
a. Verify parameters rgn_g_powext=250, rgn_g.resext = 33. 
REGEN EXCEED FAULT  Continuous regen power has been exceeded.      b.  Verify there is no connection at terminal RR. 
c.  Possible Faulty Drive; Replace the Drive 
a. Verify parameters rgn_g_powext=250, rgn_g.resext = 33. 
REGEN CONFIGUATION FAULT  The selected Regen resisitor is wrong for the drive size and supply    b.  Verify there is no connection at terminal RR. 
voltage.   
c.  Possible Faulty Drive; Replace the Drive 
INCOMP BOARD FIRMWARE  Hardware control card version (Can bus/Firewire/Sercos) does not    Replace drive 
match the firmware.   

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 41 of 48

GUI – “MCC Fault” item Description    Action


The EMVs use a RESOLVER not an ENCODER
a.  Verify on the GUI Drive Configuration Screen that Position/Speed 
Fdbck Source is set to RESOLVER 

Hyperface Encoder position has been modified. Auto Phasing 
ENCODER POSITION CHANGED  should be repeated.    

 
b.  An encoder is not used: Verify parameter “drv.posfbsrc = 2” 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 42 of 48

GUI – “MCC Fault” item Description    Action


a. Verify parameter Set (mdlrun = 1, drv.velwin = N/A)
b.  This fault is not used while the model is running 

VELOCITY ERROR FAULT  Velocity error has exceeded the programmed window and time. See   
settings on the Combined Tuning Screen.     

 
a. Check for sticking actuator
PHASE U OVERCURRENT  Overcurrent detect on Phase U   
b.  Faulty drive 
a. Check for sticking actuator
PHASE V OVERCURRENT  Overcurrent detect on phase V.    
b.  Faulty drive 
a. Cycle power
SOFTWARE ERROR  Internal Software Error has occurred.      b.  Reload configuration & power cycle 
c.  Replace drive 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 43 of 48

GUI – “MCC Fault” item Description    Action


a. Perform a File‐>EEPROM save‐>Model Save and click “Write 
Parameters” and cycle power. 
b.  If the problem persists the EEPROM might be damaged so replace 
the drive. 

MODEL PARAMETERS INVALID  Occur Model parameters are invalid or corrupted.   

 
SOFTWARE WATCHDOG  The internal software watchdog expired.    Verify the sample period on the Drive Configuration Screen 
TIMEOUT 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 44 of 48

 
Table 6 – Controller GUI Display, DSP Faults 
GUI – “DSP Fault” item Description    Action
a. Check 144VDC bus supply voltage meets the specification. 
b.  Verify the drive configuration parameters “motor bus voltage 
Detects the BUS overvoltage condition; the drive cuts off the  (drv.mtrbus)” = 110.  
BUS OVERVOLTAGE  current. This can be due to a recovery resistance interruption or the    c.  Verify there is no Connection to Recovery Resistor on the Drive 
resistance value is too high for the application and it cannot 
dissipate the energy recovered by the motor and the drive.  d.  Check for faulty 24V‐>144VDC supply    
e.  Check for an actuator drawing too much current 
f.  Possible Faulty Drive; Replace the Drive 
Detects the BUS under‐voltage condition; the drive cuts off the 
BUS UNDERVOLTAGE  current. This can be due to a power line interruption or to an     
excessive current absorption by the drive with respect to the 
resistance. 
The detected voltage on the DC bus fluctuates too much.
RATE OF CHAN. BUS VOLTAGE  Detects the DC BUS variation at DRIVE ON when the supplied power    Verify fuses on the three phase input line. 
is low (reduced or null speed). This could be due to a fuse 
interruption on the three‐phase line. 
The Motor Voltage parameter (rated bus voltage of the motor) 
value and the power stage max bus voltage are incompatible. 
INCOMPATIBLE BUS & MOTOR     
Detects the wrong setting of motor voltage rating with respect to 
the voltage detected on DCBUS. 
The detected DC Bus is below 70 Volt.
NO BUS  Detects the lack of DC BUS or a value lower than 80 V (minimum     
default factory set value). 
BUS READ  The drive cannot read the DC bus properly.    Cycle power.  If the fault persists the drive is damaged.
The internal temperature in the drive is too high.  If the drive is  a. Verify that cooling fans are operating properly if the drive fans 
improperly sized for the application the drive must absorb too  exists.   
much current during the cycle.   b.  Check current draw of actuator for abnormally high current 
HEATSINK TEMPERATURE   
Indicates the drive heat‐sink over‐temperature. This can be caused  levels.  If levels are high replace the actuator.   
by the drive operating with current higher than the drive can  c.  Turn off drive and let cool, If fault appears after cooling replace 
supply.  This may also be an indication of improper drive cooling.  the drive. 
U PHASE HIGH SIDE IGBT  Excess current or a short circuit condition detected on the high side  a.  Remove high power and allow drive voltage to dissipate.  
or low side leg of an IGBT output stage or the recovery circuit IGBT.   Measure voltage at the drive input for safe working voltages 
V PHASE HIGH SIDE IGBT  This can be generated by noise from an improperly shielded system    before proceeding  
W PHASE HIGH SIDE IGBT   or a shorted IGBT on the drive power stage.    b.  Verify system is shielded and grounded properly 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 45 of 48

GUI – “DSP Fault” item Description    Action


U PHASE LOW SIDE IGBT   c. Check drive outputs(U2, V2, W2) with an ohmmeter for short 
circuit from each output phase to all other output phases 
V PHASE LOW SIDE IGBT   d.  Check drive outputs for phase to chassis ground short circuits.   
W PHASE LOW SIDE IGBT   e.  If fault is permanent and the shorts are measured replace the 
drive.   
a. Cycle Power.
FLASH READ  The EEPROM cannot be read during power up.     b.  If problem persists, do a Save Parameters on the front panel of 
the DS2000XP.   
c.  If problem persist the EEPROM is damaged. 
FEEDBACK RESOLUTION  The configured Feedback Resolution is invalid.     Check Hiperface Parameters screen and verify Encoder Feedback 
Resolution value. 
+15V RAIL ERROR  The internal +15Vdc is out of tolerance.  
+15V RAIL ERROR  The internal ‐15Vdc is out of tolerance.  
POWER SIZE MISMATCH  The stored value of the Drive Size and the actual size of the Power    Perform a Save Parameters on the front panel of the DS2000XP. 
Stage are different.  
This fault is disabled in DSP
MOTOR TEMPERATURE FAULT  The Motor NTC/PTC over temperature threshold was exceeded.    Check the application size, during the cycle an effective current higher 
than the one the motor can manage is absorbed. 
This fault is disabled in DSP
MOTOR OVERSPEED  The Max. Motor Speed value was exceeded by more than 10   
percent.   Check that the speed loop is properly calibrated and that the motor 
braking torque is sufficient with respect to the connected load. 
a. Cycle power. 
FLASH CHECKSUM ERROR  The EEPROM of the DSP card has a checksum error.     b.  If problem persists perform a Save Parameters from the front 
panel of the DS2000XP. 
c.  If problem still persists the EEPROM is damaged. 
RESOLVER FAULT  An error was detected on the resolver.    Check signal wires for proper connections.
DS2000XP CARD FAULT  This fault is set when any DSP or MCC fault is active.  It will     
automatically clear when no errors are present. 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 46 of 48

 
 
 

 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 47 of 48

 
 
© Rolls-Royce Power Engineering plc (2012)
The information in this document is the property of Rolls-Royce Power Engineering plc. The information may not be
EG 038
copied, or communicated to a third party, or used for any purpose other than that for which it is supplied, without the
prior written consent of Rolls-Royce Power Engineering plc. Page 48 of 48

 
Engineering for Services (E4S) for the Rolls‐Royce Energy Business can be contacted at the following address:‐ 
 
 
 
Engineering for Services (E4S) 
Rolls‐Royce Power Engineering plc 
Iceni Centre, Warwick Technology Park 
Gallows Hill 
WARWICK CV34 6DA 
  Tel:  +44 (0)1926 3 07700 
  Fax:  +44 (0)1926 3 07987 
 

 
 
 
 
 
 
 

Regional technical support for the Rolls‐Royce Energy Business can be contacted at the following addresses:‐ 
 
Europe, Russia & Africa  Asia Pacific
   
Engineering for Services (E4S)  Customer Business 
Rolls‐Royce Power Engineering plc  Rolls‐Royce Pte Limited 
Iceni Centre, Warwick Technology Park  16, International Business Park 
Gallows Hill  Unit 03‐09 
WARWICK CV34 6DA  Singapore 609929 
  Tel:  +44 (0)1926 3 07700    Tel:   +65   6899 0092 
  Fax:  +44 (0)1926 3 07987    Fax:   +65   6862 4495 

North & Central America  Middle East & Central Asia
   
Customer Business  Customer Business 
Rolls‐Royce Energy  Rolls‐Royce Energy 
8303 McHard Road  Fotouh Al Khair Centre 
Houston  Tower 3, Floor 0 
TX 77053  PO Box 44183 
USA  Abu Dhabi 
  Tel:   +1   281 436 6700  UAE 
  Fax:   +1   281 436 6777    Tel:   +971   2 6311959 
  Fax:   +971   2 6351242 

South America 
 
Customer Business 
Rolls‐Royce Energy 
Av. Prefeito Aristeu Ferreira da Silva, 1900 
27.930‐070 ‐ Novo Cavaleiros ‐ Macaé 
Rio de Janeiro 
Brazil 
  Tel:   +55   22 2796 7400 

 
 

Whilst this information is given in good faith, based on the latest information available to Rolls-Royce Power
Engineering plc, no warranty or representation is given concerning such information, which must not be taken as
establishing any contractual or other commitment binding upon Rolls-Royce Power Engineering plc or any of its
subsidiary or associated companies.

Rolls-Royce Power Engineering plc, Registered office: Moor Lane, Derby DE24 8BJ
Company number: 1305027, Registered in England Produced in Great Britain

You might also like