Generator Automatic Voltage Regulator Operation Manual: Kutai Electronics Industry Co., LTD
Generator Automatic Voltage Regulator Operation Manual: Kutai Electronics Industry Co., LTD
Generator Automatic Voltage Regulator Operation Manual: Kutai Electronics Industry Co., LTD
2. WIRING (Refer to Figure 3) If the exciter field voltage exceeds 100 ± 5 VDC, the
regulator automatically removes the field current
● Power input 3, 4. after a time delay. The time delay is inversely
● Sensing input 4, P. proportional to the magnitude of the detected over
voltage condition up to the 135 VDC point. Beyond
● F+, F– : Exciter.
140 VDC, the field voltage is removed within 0.2
● EXT. VAR : External Voltage Adjustment. seconds.
4. OVEREXCITATION SHUTDOWN
______________________________________________________________________________________
2 EA04C
3. Ensure proper fuse is installed. 7. FIELD FLASHING
4. Turn voltage and stability potentiometer full
When the regulator is operated with the generator
anticlockwise (lowest voltage level).
for the first time, the polarity residual magnetism
5. If used, turn external voltage potentiometer to the may not correct or the magnitude not enough. If the
middle position. generator does not build-up after startup, shut down
the prime mover and proceed with the following
6. Use 600 VAC Voltage meter connect to AC
steps :
output terminal and measure the output voltage.
5.2 Startup Procedure 1. With the prime mover at rest, apply a dc source
(not grounded) of not more than 12V, to
1. To start and run the generator at no load and terminals F+ (positive) and F– (negative) in
rated speed. The generator output voltage series with a limiting resistor of 3 ~ 5 ohms.
should build up to a minimum level if the voltage
2. Allow approximately 3 seconds before removing
does not build up, It may cause by low residual
the dc source.
voltage of generator. Refer to field flashing
section in generator manual. 3. Start prime mover and measure voltage at
regulator leads 3 and 4. If voltage is greater then
2. Slowly adjust voltage potentiometer until the
5 volts, voltage build-up should be successful.
generator voltage reach the proper value.
Repeat field flashing procedure if less than 6V
residual is measured.
6. STABILITY ADJUSTMENTS
4. If repeating steps 1 and 2 does not result in
1. Slowly rotate the STAB control in the clockwise generator voltage build-up, replace the voltage
(CW) direction will change the AVR and regulator.
generator’s response time, if over adjusted the
voltage will become unstable, if under, the WARNING
instant heavy load voltage will change Please make sure you have read and
significantly. understand the contents of the instruction
2. It is advised to use a voltmeter DCV to adjust the manual prior to installation. Incorrect wiring
STAB control F+, F– until the oscillate becomes connection may result in irreversible damage
minor. By doing so helps to improve and reduce to the product and other equipments.
the voltage change under heavy load.
120
GENERATOR OUTPUT VOLTAGE
100
80
(% OF NOMINAL)
SW Volt Stab
50HZ
Stab 60HZ
Volt 60
SW
40
EXT
VR
EXT
VR
FUSE
FUSE
5A
20
UNIT : mm 0 10 20 30 40 50 60
F- F+ 3 4 P
FREQUENCY (HZ)
Outline dimension Frequency compensation curves
Figure 1 Figure 2
______________________________________________________________________________________
EA04C 3
R R
S G S G
T
~ ~
T
N
Field Field
1K OHM
1K OHM
P 4 3 F+ F- VAR VAR P 4 3 F+ F- VAR VAR
1 2 3 1 2 3
SW EA04C SW EA04C
8. SW DESCRIPTION
(1) SW-1 Sensing voltage selector
AC Power Input :
ON for 220V OFF for 380 / 480V.
3, 4 90 ~ 240VAC 50/60Hz
(2) SW-2 Frequency selector Sensing Input :
ON for 50Hz OFF for 60Hz. P, 4 160 ~ 265VAC 50/60Hz
300 ~ 550VAC 50/60Hz
(3) SW-3 Response
DC Output Power :
ON for fast OFF for slow. F+, F– Max 63VDC 4A
EXT. VAR (1 K)
ON
SW CAUTION
Meggers and high potential test equipment
1 2 3 must not be used. Incorrect use of such
equipment could damage the semiconductors
contained in the regulator.
※ Use only original supplied spare protection fuse for fuse replacement.
※ Please accept our sincere apology if any modification in performance, specification or appearance is
made without prior notice.
______________________________________________________________________________________
4 EA04C