V-2158-0201-A-8002 - 3 - 0020 VFD ACS1000i
V-2158-0201-A-8002 - 3 - 0020 VFD ACS1000i
V-2158-0201-A-8002 - 3 - 0020 VFD ACS1000i
原図 3N4-S4293202 2
ABB
原図 3N4-S4293202 3
ABB
Table of contents
List of figures
List of tables
Copyright notice 1
Document identification 1
Contact information 1
Equipment covered by the manual 1
Structure of the user documentation 2
Target groups and required qualifications 2
Relevant chapters of the manual 3
User’s responsibilities 4
Intended equipment use 4
Quality certificates and applicable standards 4
Writing conventions 5
Meaning of icons 5
Text conventions 5
Related documentation 6
Items covered by delivery 6
Identifying the delivery 7
原図 3N4-S4293202 4
Table of contents ABB
Chapter 2 - Power electronics and cabinet features 2-1
原図 3N4-S4293202 5
ABB Table of contents
原図 3N4-S4293202 6
Table of contents ABB
6.5 Feeder and motor cables 6-5
6.5.1 Further information 6-5
6.5.2 Cable entry 6-5
6.5.3 Additional cabinet compartments 6-8
6.5.4 Final checks 6-8
6.6 Auxiliary power, control and serial communication cables 6-8
6.6.1 Further information 6-8
6.6.2 Cable preparation 6-8
6.6.3 Connecting auxiliary power cables 6-9
6.6.4 Connecting control cables 6-10
Mechanical installation 1
Electrical installation 1
Main circuit breaker (MCB) 2
Motor 2
Insulation tests 2
Power supply 3
Miscellaneous 3
原図 3N4-S4293202 7
ABB Table of contents
原図 3N4-S4293202 8
Table of contents ABB
10.2.3 Understanding wiring diagrams 10-2
10.3 Troubleshooting 10-3
10.3.1 Alarm and fault indications 10-3
10.3.2 Error message levels 10-3
10.3.3 Troubleshooting procedure 10-5
10.4 Malfunctioning grounding switch 10-6
10.5 Panel removal 10-6
10.6 LEDs and switches on PCBs and I/O devices 10-7
10.6.1 AMC circuit board 10-8
10.6.2 IOEC I/O modules 10-9
10.6.3 Serial communication interfaces 10-10
10.7 Maintenance 10-10
10.7.1 Overview on maintenance and service tasks 10-10
10.7.2 Safety 10-11
10.7.3 De-energizing the drive 10-12
10.7.4 Visual checks on the drive 10-13
10.7.5 Cleaning 10-14
10.7.6 Checking wire and cable connections 10-14
10.7.7 Checking and replacing the filter mats 10-15
10.7.8 Inspecting and replacing the battery 10-17
10.7.9 Replacing a fan unit 10-19
Maintenance schedule
原図 3N4-S4293202 9
ABB
List of figures
Figure 1 ACS 1000i delivered items 6
Figure 2 Location of rating label and CD-ROM 7
Figure 1-1 Safety labels 1-4
Figure 1-2 Drive system overview 1-5
Figure 1-3 MCB opening timing diagram 1-6
Figure 2-1 ACS 1000i with optional redundant fans 2-1
Figure 2-2 Elementary diagram 2-2
Figure 2-3 Drive overview with power supplies 2-3
Figure 2-4 Three-level voltage source inverter principle 2-5
Figure 2-5 Voltage and current waveforms at the drive output 2-6
Figure 2-6 The ACS 1000i (24-pulse, typical layout) 2-7
Figure 2-7 Terminal compartment 2-8
Figure 2-8 Input disconnector and grounding switch operation 2-9
Figure 2-9 Control compartment with open front door (typical layout) 2-10
Figure 2-10 Rectifier, filter and optional input contactor 2-11
Figure 2-11 Inverter compartment 2-12
Figure 2-12 Air flow through the drive 2-13
Figure 2-13 Air flow through the drive with redundant fan units 2-14
Figure 2-14 Operating principle with redundant fans 2-15
Figure 2-15 Door locks 2-17
Figure 3-1 Control compartment with open front door (typical layout) 3-1
Figure 3-2 Local operator panel (standard version) 3-2
Figure 3-3 Simplified illustration of control system 3-4
Figure 3-4 AMC mounted on INT circuit board (typical view) 3-5
Figure 3-5 DTC principle 3-6
Figure 4-1 Lifting the ACS 1000i 4-3
Figure 4-2 Moving the ACS 1000i sideways 4-3
Figure 4-3 Moving the ACS 1000i backwards or forwards 4-4
Figure 5-1 Typical anchor bolt 5-3
Figure 5-2 Position of mounting holes 5-3
Figure 5-3 Levelling the drive 5-4
Figure 5-4 Fan units 5-5
Figure 5-5 Positioning a fan unit 5-5
Figure 5-6 Mounting a fan unit 5-6
Figure 6-1 Grounding the drive equipment (recommended scheme) 6-4
Figure 6-2 Terminal compartment 6-5
Figure 6-3 Connection with spring and flat washers 6-7
Figure 6-4 Control cable entry 6-8
Figure 6-5 Fastening rail and terminals 6-9
Figure 6-6 Cable entry from top (A) and from bottom (B) 6-9
Figure 6-7 Shield grounding clamp 6-10
Figure 8-1 Local operator panel 8-2
Figure 9-1 CDP control panel 9-1
Figure 10-1 Example for device identification 10-2
原図 3N4-S4293202 10
List of figures ABB
Figure 10-2 AMC circuit board 10-8
Figure 10-3 IOEC circuit board 10-9
Figure 10-4 Location of filter mat 10-15
Figure 10-5 Removing the grille of the inverter compartment 10-17
Figure 10-6 Grille of inverter compartment removed. 10-17
Figure 10-7 Hole grate behind filter mat (seen from rear side) 10-17
Figure 10-8 Battery (A) and UPS (B) 10-18
Figure 10-9 Fan unit 10-19
Figure 10-10 Fan insert with fixing screws 10-20
原図 3N4-S4293202 11
ABB
List of tables
Table 3-1 I/O module configuration with number and type of I/O 3-9
Table 3-2 Fieldbus adapters 3-12
Table 6-1 Control cable requirements 6-4
Table 6-2 Creepage distance 6-6
Table 9-1 Actual signal parameter groups 9-4
Table 9-2 Commonly used parameter groups 9-11
Table 10-1 Filter material specification with type code 10-16
原図 3N4-S4293202 12
List of tables ABB
原図 3N4-S4293202 13
ABB
Cluster A cluster is a synonym for a group of hardware modules of the drive control system.
Drive system The drive system includes all equipment used to convert electrical into mechanical
power to give motion to the machine.
DriveDebug DriveDebug is part of ABB’s DriveWare® software tools for drives using the DDCS
communications protocol. DriveDebug runs on computers with Windows® operating
systems. DriveDebug is a specialist’s tool used to diagnose, tune and troubleshoot ABB
drives.
DriveMonitorTM DriveMonitor is a monitoring and diagnostics system that allows secure access to the
drive via the internet from a remote location. DriveMonitor provides long-term monitoring
functions that allow to infer equipment status and improve equipment performance.
Ground Earth
To ground The conducting path (e.g. conductor) between the electric equipment (e.g. frequency
converter) and the earth. The electric equipment is connected to the earth, e.g. by a
grounding set or a grounding switch.
INU Inverter unit of the drive. The INU converts the DC voltage to the required AC motor
voltage and frequency.
IOEC module The IOEC module is an active input and output device for digital and analog signals.
Line voltage RMS voltage of the main power supply of the drive
原図 3N4-S4293202 14
Terms, abbreviations, trademarks ABB
PCC Point of common coupling. The PCC is the point in the electrical power supply system
where the responsibility of the utility changes to the industrial customer. The utility is
responsible to provide clean voltage and current with respect to harmonic distortion up to
the PCC. The industrial customer is responsible not to distort voltage and current by its
electrical systems.
PE Protective earth
Zero speed threshold Used in the manual to indicate that the drive has reached the value “zero speed” that is
set in a parameter. The value can be set in the range of 0 and maximum speed (the unit
for the speed is rpm).
原図 3N4-S4293202 15
ABB Terms, abbreviations, trademarks
Trademarks
Names that are believed to be trademarks of other companies and organizations are designated as
such. The absence or presence of such a designation should however not be regarded as an offence
of the legal status of any trademark. The following registrations and trademarks are used in this
manual:
Trademarks Meaning
原図 3N4-S4293202 16
Terms, abbreviations, trademarks ABB
原図 3N4-S4293202 17
ABB
General information on manual and equipment
Copyright notice
The information in this manual is subject to change without notice.
This manual and parts thereof must not be reproduced or copied, or
disclosed to third parties, nor used for any unauthorized purpose without
written permission from ABB Switzerland Ltd, Medium Voltage Drives.
The hardware and software described in this manual is provided under a
license and may be used, copied, or disclosed only in accordance with the
terms of such license.
Document identification
Ownership ABB Switzerland Ltd
Medium Voltage Drives
Revision index A
Contact information
Address ABB Switzerland Ltd
Medium Voltage Drives
CH-5300 Turgi, Switzerland
E-mail mvdrives@ch.abb.com
原図 3N4-S4293202 18
General information on manual and equipment ABB
If information is required beyond the instructions in this manual refer the
matter to ABB.
原図 3N4-S4293202 19
ABB General information on manual and equipment
Mechanical installation The personnel must be qualified to prepare the installation site according
to the site and equipment requirements and to perform the installation
accordingly.
Electrical installation The personnel must have a sound knowledge of the relevant electrical
codes and specifications covering low and medium voltage equipment,
be experienced with electrical wiring principles, and know the electrical
symbols typically used in wiring diagrams.
Operation The personnel include all persons who operate the equipment from the
local operating panel of the drive. The personnel must know the functions
of the operating panel, be adequately trained for the equipment, and know
the driven process. Special knowledge of frequency converter technology
is not required.
General information x x x x
Safety x x x x
Power electronics and x x
cabinet features
原図 3N4-S4293202 20
General information on manual and equipment ABB
Control system x x
Transportation, x
storage and disposal
Mechanical installation x x
Electrical installation x
Operation x x
CDP control panel x x
Troubleshooting and x
maintenance
User’s responsibilities
It is the responsibility of those in charge of the equipment to ensure that
each person involved in the installation, operation or maintenance of the
equipment has received the appropriate training and has thoroughly read
and clearly understood the instructions in this manual and the relevant
safety instructions.
原図 3N4-S4293202 21
ABB General information on manual and equipment
Writing conventions
The following icons and text conventions are used in the manual.
Meaning of icons
Text conventions
• Bulleted list
Used to list items or steps in a procedure, where the sequence does
not matter.
• Bulleted list of a subsection following a main paragraph
Used to list items or for procedures, where the sequence does
not matter.
1 Steps of a procedure, to be followed in the specified order (e.g. 1, 2,
3 etc.)
1 Figure legend, numbers identify the items referred to in the illustration
above (e.g. 1, 2, 3 etc.)
Arial Bold is used to highlight switches to be operated, status messages
shown in a display and special terms.
UPPERCASE letters refer to a parameter.
Italic is used for references to illustrations, chapters and supplementary
documentation.
原図 3N4-S4293202 22
General information on manual and equipment ABB
Related documentation
The following documents are available for supplementary information:
1
2
原図 3N4-S4293202 23
ABB General information on manual and equipment
• Lever for input disconnector and grounding switch inside the control
compartment (4)
• Additional components depending on options
Legend
1 Rating label
2 CD-ROM with user’s manual
原図 3N4-S4293202 24
General information on manual and equipment ABB
原図 3N4-S4293202 25
ABB
Chapter 1 - Safety
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could
result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to personal injury.
The safety instructions are derived from the following standards:
• ISO 3864-2:2004 (E)
Graphical symbols – Safety colors and safety signs – Part 2: Design
principles for product safety labels
• ANSI Z535.6
American National Standard for Product Safety Information in
Product Manuals, Instructions, and Other Collateral Materials
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 1-1 (8)
原図 3N4-S4293202 26
Chapter 1 - Safety ABB
• Before starting to work on the drive, make sure that:
• the main and auxiliary power supply to the drive is switched off,
locked out, and tagged out,
• the drive is dead,
• safety ground connections are in place,
• appropriate personal protective equipment is provided and used
when required,
• everyone involved is informed.
• When working near the running drive protective earmuffs should be
worn.
• Before work is carried out simultaneously on the drive and on other
drive system equipment, make sure that:
• the relevant safety codes and standards are observed,
• all energy sources of the equipment are turned off,
• lockout and tagout devices are in place,
• barriers and appropriate covers are used on equipment which is
still live,
• everyone involved is informed.
• In case of fire in the drive room:
• Observe the established rules and regulations for fire protection.
• Only firemen with appropriate protective equipment are allowed
to enter the drive room.
1-2 (8) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 27
ABB Chapter 1 - Safety
• Software errors
• Faulty hardware
• Hazardous touch voltages can be present on drive system
components caused by, for example:
• Operation of the equipment outside the scope of the specifica-
tions
• External influence on, or damage of the equipment
• Induced voltages by external equipment
• Condensation on equipment components, or pollution
• Faulty hardware
• High temperatures, noise, particles, or gases can be emitted from
drive system components caused by, for example:
• Operation of the equipment outside the scope of the specifica-
tions
• External influence on, or damage of the equipment
• Wrong parameter settings
• Software errors
• Faulty hardware
• Hazardous substances can be emitted from drive system
components due to, for example:
• Incorrect disposal of components
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 1-3 (8)
原図 3N4-S4293202 28
Chapter 1 - Safety ABB
1-4 (8) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 29
ABB Chapter 1 - Safety
MCB
Protection
relay CT
Converter
transformer
Higher-level
Drive control system
Local MCB control
Motor M
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 1-5 (8)
原図 3N4-S4293202 30
Chapter 1 - Safety ABB
1.5.1 Safety and protection requirements
For safety and protection reasons, the MCB must meet the stipulated
minimum requirements of the specifications of ABB MV Drives. It is the
system integrator's responsibility to ensure that the minimum require-
ments are met. The minimum requirements for the MCB are stated in this
note and in the respective MCB specifications, which are available for
each medium voltage drive from ABB.
The safety requirements for the drive are based on the following
standards:
• ISO 13849-1 Safety of machinery - Safety-related parts of control
systems - Part 1: General principles for design, section 6.2.6
Category 3
• IEC 60204-1 Safety of machinery - Electrical equipment of machines
- Part 1: General requirements
Short-circuit occurs
1-6 (8) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 31
ABB Chapter 1 - Safety
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 1-7 (8)
原図 3N4-S4293202 32
Chapter 1 - Safety ABB
1-8 (8) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 33
ABB
2.1 Overview
The air-cooled ACS 1000i is a general purpose frequency converter with
integrated converter transformer for the control of standard induction
motors.
See the technical specifications and/or the rating plate of your drive for
information on the power and voltage range of your drive.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 2-1 (18)
原図 3N4-S4293202 34
Chapter 2 - Power electronics and cabinet features ABB
2.1.1 Drive topology
Figure 2-2 shows the elementary circuit diagram of the ACS 1000i.
3
NP M
1 2 3 4 5 6 7 8 9
Legend
2-2 (18) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 35
ABB Chapter 2 - Power electronics and cabinet features
ACS 1000
Control and cooling equipment
Cooling equipment
Auxiliary
power
Auxiliary distribution
power supply Control system
Converter
Main transformer M
power supply
MCB
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 2-3 (18)
原図 3N4-S4293202 36
Chapter 2 - Power electronics and cabinet features ABB
2.2.2 Auxiliary power supply
The total auxiliary power demand of the drive includes:
• Auxiliary power for the cooling system and a short-time power
demand for the charging unit of the drive,
• Auxiliary power for the control hardware and the gate units which are
used to trigger the power semiconductors.
The total auxiliary power can be fed to the drive in the following two ways:
• Through a common power supply
The total auxiliary power is supplied to the drive by a three-phase AC
power supply.
If the power supply is interrupted, drive internal batteries provide a
backup for the control system, thus enabling the drive to ride-through
and/or to perform a controlled shutdown.
• Through separate power supplies
The auxiliary power is supplied to the drive by a three-phase AC
power supply and by a UPS to a separate single-phase AC or DC
input.
Feeding the control power separately by a UPS has the advantage
that the main control hardware will remain energized, the full ride-
through capabilities of the drive can be used, and the communication
to a higher-level control system will not be lost in the event of an auxil-
iary power outage.
Note: If the auxiliary voltage of the three-phase AC power supply is
applied the fuses on the customer side must be rated for the
corresponding inrush currents (see rating label for current rating).
2.3 Technology
2-4 (18) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 37
ABB Chapter 2 - Power electronics and cabinet features
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 2-5 (18)
原図 3N4-S4293202 38
Chapter 2 - Power electronics and cabinet features ABB
2.4.1 Overview
The drive is equipped with an input transformer and a forced air cooling
system (see 2.4.7 Air cooling system).
2-6 (18) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 39
ABB Chapter 2 - Power electronics and cabinet features
1 2 3 4 3 5 6
Legend
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 2-7 (18)
原図 3N4-S4293202 40
Chapter 2 - Power electronics and cabinet features ABB
2.4.2 Power terminal compartment
The left most compartment of the drive contains the power terminals
(Figure 2-7). The power terminals are located behind a bolted cover plate.
1
Legend
1 Terminal compartment
2 Feeder terminals and input isolator
3 Feeder terminals (detail)
4 Ground bus and terminal
5 Motor terminals (detail)
The terminal compartment provides the terminals for the feeder and motor
cables, the input isolator and the ground bus for the termination of the
ground cable and the cable screens.
The cables are either entered through the roof or through the floor of the
cabinet. The terminal compartment is prepared in the factory for top cable
2-8 (18) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 41
ABB Chapter 2 - Power electronics and cabinet features
entry and can be changed to bottom entry during installation. See Chapter
6 - Electrical installation for further details on cable entry and connection.
A B
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 2-9 (18)
原図 3N4-S4293202 42
Chapter 2 - Power electronics and cabinet features ABB
Figure 2-9 Control compartment with open front door (typical layout)
Legend
2-10 (18) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 43
ABB Chapter 2 - Power electronics and cabinet features
Legend
1 Surge arrestors
2 Grounding switch
3 24-pulse rectifier bridge
4 24-pulse input transformer
5 Optional input contactor
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 2-11 (18)
原図 3N4-S4293202 44
Chapter 2 - Power electronics and cabinet features ABB
2.4.6 Inverter compartment
The inverter compartment contains the inverter stacks, the sine filter and
DC link capacitors.
2-12 (18) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 45
ABB Chapter 2 - Power electronics and cabinet features
Air intakes
The air intakes are provided with air filters to prevent dust and particles
from entering into the drive. The air filters can be replaced from outside
while the drive is in operation.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 2-13 (18)
原図 3N4-S4293202 46
Chapter 2 - Power electronics and cabinet features ABB
Air intakes
Figure 2-13 Air flow through the drive with redundant fan units
Normal operation Under normal conditions, i. e. with both fans operable, the main cooling
fan (fan one) is switched on as soon as the main circuit breaker (MCB) is
closed (see Figure 2-14).
When opening the MCB, the cooling circuit will be switched off after some
delay. This delay corresponds to the discharging time of the drive which
can be up to 5 minutes.
The redundant fans are operated alternatively with different running
periods. The total cycle time is 10 hours by default and a fan switch-over
takes place twice within 10 hours.
If the drive is running continuously, fan one (main fan) will be running by
default up to a total of six hours (which is 60% of 10 hours). Consequently,
fan two (redundant fan) will be running the remaining 40% (4 hours).
Switching over between running and stand-by status will take place
automatically.
If the drive is running intermittently, the same fan will be selected
repeatedly until its duty cycle has elapsed.
If one fan is not available, the remaining unit will operate on a 100% cycle.
2-14 (18) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 47
ABB Chapter 2 - Power electronics and cabinet features
With the 60-to-40% default ratio, the resulting long-time operating times of
the two fans are not equal and the risk of a simultaneous failure of both
fans is minimized.
The total cycle time and the running times of the fans are adjusted by
setting the corresponding parameter during commissioning.
1
ACS 1000 MCB
0
10 h 10 h
Cycle time
Fan 1 1
0
60% 60%
1
Fan 2
0
40%
Non scheduled switch- A non scheduled switch-over to the stand-by unit occurs in the following
over situations:
• If the running fan has tripped (indicated with alarm Fan Grp 1 or
Fan Grp 2)
• If alarm FanDiffPress (differential pressure supervision across
inverter) is activated.
• Upon an alarm reset following one of the above mentioned situations.
By resetting the alarm, the fan which initially caused the alarm will be
taken back to operation.
For alarm definition see Chapter 10 - Troubleshooting and maintenance,
10.3.2 Error message levels.
A failure of one fan is indicated with an alarm. In opposition to all other
drive alarms, the above mentioned alarms are not reset automatically after
the disturbance has disappeared. They must be reset manually by setting
parameter 41.04 FAN ALARM RESET to RESET.
A drive shutdown will be initiated if the stand-by unit has already tripped
when a non-scheduled switch-over is requested, i. e. both fans are not
available (indicated with fault Fan Grp 1 or Fan Grp 2 or fault
FanDiffPress).
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 2-15 (18)
原図 3N4-S4293202 48
Chapter 2 - Power electronics and cabinet features ABB
EMC has been achieved by applying a cabinet design consisting of folded,
galvanized sheet metal plates (thickness of approximately 2 mm) and
minimizing the space between the rivets. The inside walls of the cabinet
are not painted, because paint tends to reduce the effectiveness of
metallic bonding which is paramount to successful EMC.
Accordingly, only the front of the drive is painted while all other walls are
galvanized. However, the cabinet can be ordered optionally with the whole
of the outside painted. EMC performance is further enhanced by the use
of metal cable ducts.
Doors of power The doors of the power compartments of the drive are mechanically
compartments interlocked with the safety grounding switch and with the main circuit
breaker upstream of the drive transformer.
• The interlocking system ensures that the main power cannot be
connected to the drive unless the doors are securely closed and the
grounding switch is in position I (not grounded).
• The interlocking system also ensures that the doors cannot be
opened until the main power is disconnected, the DC link capacitors
are discharged and the grounding switch is in position 0 (grounded).
The door locks of the power compartments use triangular keys (Figure 2-
15).
Door of control The door of the control compartment is not linked to the interlocking
compartment system and can be opened at any time. The high voltage busbar
compartment is located behind the control swing frame and separated
from the control compartment by a bolted protective shield.
Additionally, the doors of the medium voltage compartments have locks
with different inserts than the control compartment door. The different lock
inserts ensure that these doors can only be opened by personnel
authorized to do so.
The door lock of the control compartment uses double-bit keys (Figure 2-
15).
Doors of additional The power compartment doors of all additional cabinets (e.g. braking
cabinets chopper cabinet) are electromechanically interlocked by separate door
switches since they are not included in the mechanical interlock system.
These door monitoring switches are wired to the safety grounding switch.
The doors can only be opened if the grounding switch unlocked lamp is
on. If any of the doors are opened during operation, the MCB will be
tripped immediately.
2-16 (18) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 49
ABB Chapter 2 - Power electronics and cabinet features
1 2 3 4
8 mm
Legend
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 2-17 (18)
原図 3N4-S4293202 50
Chapter 2 - Power electronics and cabinet features ABB
2-18 (18) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 51
ABB
1 IOEC4 module
(optional)
2 IOEC3 module 1
(optional)
3 IOEC2 module
2
4 IOEC1 module
5 Delta p-transmitter
6 Control power supply
7 Delta p-transmitter
3
8 Fused terminal block for
internal aux. power
9 Motor starters and 4
circuit breakers
5
10 Option: batteries
11 Terminal blocks 6
(internal, cooling, fans,
external) 7
12 AC aux. supply 8
13 AMC and interface
board 9
14 Control panel
15 Control pushbuttons
and indication lights
16 Emergency-off
pushbutton 10
17 Transformer protection 11
12
13 14 15 16 17
Figure 3-1 Control compartment with open front door (typical layout)
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 3-1 (14)
原図 3N4-S4293202 52
Chapter 3 - Control system ABB
3.1.2 Terminal and control compartment
The control hardware (processor and communication circuit board) is
mounted on the swing frame. Details can be seen in Figure 3-1. The
customer I/Os for customer control and protection signals as well as I/Os
for auxiliary power supply are also located on the swing frame.
Legend
3-2 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 53
ABB Chapter 3 - Control system
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 3-3 (14)
原図 3N4-S4293202 54
Chapter 3 - Control system ABB
Fieldbus
Control compartment
PC tools
DDCS
RS485
DDCS
AMC controller
DDCS
IOEC1
Fiber optic
IOEC2
IOEC3*
INT circuit board
IOEC4**
Fiber optic
Converter compartment
* and ** Additional option for air-cooled ACS 1000
** Additional option for water-cooled ACS 1000
3-4 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 55
ABB Chapter 3 - Control system
Control tasks General control, protection and monitoring tasks regarding the whole
drive as well as all rectifier and line related functions of the drive are
implemented in the AMC controller.
All relevant drive variables (e.g. speed, torque, current, voltage) are
continuously monitored by the control system. Pre-programmed
protection functions ensure that these variables remain within certain
limits in order to maintain safe operation of the drive. These internal
functions are not programmable by the user.
Other general control, protection and monitoring tasks regarding the
whole drive include control and monitoring of:
• Main circuit breaker (MCB)
• Grounding switch
• Door interlocking
• Cooling system
Optionally, the drive offers monitoring of signals from external
equipment.These can be activated and adjusted by parameter settings.
Main circuit breaker The MCB is an important switching and protection device of the drive
control system. Therefore it must only be controlled and monitored by the drive.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 3-5 (14)
原図 3N4-S4293202 56
Chapter 3 - Control system ABB
The feedback signals from the MCB upon a close or an open command
from the drive are monitored. These signals must have the correct status
and must arrive within a preset time at the drive:
• If the drive applies a close command and the expected feedback
signal does not arrive after a preset time, the close command is reset
and the MCB is tripped.
• If the open command from the drive to the MCB is a maintained
signal, it is reset after receiving the open feedback signal from the
switchgear. If the feedback signal does not arrive after a preset time,
a trip command to the MCB is issued.
Speed and torque The speed and torque of the motor is controlled by DTC (Direct Torque
control Control). The DTC motor control platform is unique to ABB and has been
proven in all variable speed drives of the ACS product range. DTC
provides accurate speed and torque control, and high dynamic speed
response. DTC is implemented in the AMC controller.
3-6 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 57
ABB Chapter 3 - Control system
Peripheral I/O devices The peripheral input and output devices connected to the AMC controller
include:
• Drive control interfaces
• IOEC modules for parallel signal transfer to external devices
• Optional advant or fieldbus adapters for serial data transfer to a
higher-level control system
• Local CDP control panel
• PC-based service tools comprising:
• DriveWare® software tools
DriveWare® includes software tools such as the commissioning
and maintenance tools DriveWindow and DriveDebug, and
DriveOPC for data transfer between ABB drives and Windows®-
based applications.
• DriveMonitorTM (Option)
DriveMonitorTM is a monitoring and diagnostics tool that allows
access to the drive from any location in the world via a secure in-
ternet connection.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 3-7 (14)
原図 3N4-S4293202 58
Chapter 3 - Control system ABB
• Booster pumps of district heating systems
• Speed control of different types of material handling systems
where the material flow has to be regulated.
The PID control mode controls the process variable by adjusting the
speed of the motor accordingly.
Legend
1
1 Reference value
2 Level transducer 2
3 Actual value
4 Pump
See Appendix G - Signal and parameter table, Group 99, Start-up data for
an overview of control mode settings.
3-8 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 59
ABB Chapter 3 - Control system
4 Analog (AI) 0 to 20 mA or 4 to 20 mA or 0 to 10 V or 2 to 10 V
inputs scalable by parameter setting
2 Analog (AO) 0 to 20 mA or 4 to 20 mA
outputs scalable by parameter setting
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 3-9 (14)
原図 3N4-S4293202 60
Chapter 3 - Control system ABB
3.5.1 Programmable digital and analog outputs
Programmable digital Four digital outputs on the IOEC2 module can be programmed
outputs individually. Each output has floating change-over contacts and can be
allocated to an internal binary control or status signal via parameter
setting.
Examples are:
• ready, running, fault, warning, motor stall, motor temperature alarm or
trip, ACS 1000 temperature alarm or trip, reverse rotation selected,
external control selected, preset speed limits, DC voltage limits,
preset motor current limit, reference limits, loss of reference signal,
motor operating at reference speed, process PID controller actual
value limits (low, high) etc.
If optional modules IOEC3 and/or IOEC4 are installed, a maximum of
12 additional digital outputs (6 on each module) are available.
Programmable analog Two programmable analog outputs on each IOEC module are at the user’s
outputs disposal.
Depending on the setting of the corresponding parameters, the analog
output signals can represent for example:
• motor speed, process speed (scaled motor speed), output frequency,
output current, motor torque, motor power, DC link voltage, output
voltage, application block output (process PID controller output),
active reference, reference deviation (difference between the
reference and the actual value of the process PID controller).
The selected analog output signals can be inverted and filtered. The
minimum signal level can be set to 0 mA, 4 mA or 10 mA.
3-10 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 61
ABB Chapter 3 - Control system
See the ACS 1000 Terminal lists for the complete list of standard and
optional customer control signals.
Overview The NTAC interface is part of the control system of the drive if pulse
encoder feedback is used to control the motor.
Terminals X1 Terminals X2
1 A+ Channel A 1 -V 0V
2 A- 2 -V 24 V
3 B+ Channel B 3 +V
4 B- 4 24 and 25
5 Z+ Channel Z 5 15
6 Z- 6 24
7 SH Shield 7 0V
8 SH 8 +24 V
Communication with The NTAC module communicates with the AMC controller via a fast optical
AMC controller link using the standard DDCS protocol. The optical fibers are connected
to channel 1 of the AMC controller.
AMC controller
DDCS
NTAC
Location The NTAC interface is mounted to the left of the IOEC1 module (see
Figure 3-1).
The indicated mounting position may vary depending on the number of
optional devices present in the control compartment.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 3-11 (14)
原図 3N4-S4293202 62
Chapter 3 - Control system ABB
commands, status messages of the drive, speed or torque reference
values, and actual values are transmitted.
Communication with the AMC controller is done with data sets, each
containing 3 x 16 bit integers. Each data set contains a standardized set
of process data. The content of the data sets is programmed accordingly
in the remote control system.
Available fieldbuses The drive can be equipped with one of the following fieldbus adapters.
Table 3-2 Fieldbus adapters
DeviceNet NDNA-02
Ethernet NETA-01
Modbus NMBA-01
Profibus DP NPBA-12
Communication with The optional fieldbus adapter is connected to channel 0 of the AMC
AMC controller controller via optical fibers.
3-12 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 63
ABB Chapter 3 - Control system
Fieldbus
adapter
DDCS
AMC controller
Location The fieldbus adapter is mounted to the left of the IOEC1 module (see
Figure 3-1).
The indicated mounting position may vary depending on the number of
optional devices present in the control compartment.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 3-13 (14)
原図 3N4-S4293202 64
Chapter 3 - Control system ABB
3-14 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 65
ABB
4.1 Safety
The drive must only be handled by personnel who are skilled and
experienced in unpacking and transporting heavy equipment.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 4-1 (6)
原図 3N4-S4293202 66
Chapter 4 - Transportation, storage and disposal ABB
NOTICE
Do not lift and move the drive or a transport unit using a forklift. The frame
of the cabinets could be damaged. If a crane is not available, contact ABB
for instructions on other means of transport.
NOTICE
When working on the drive, ensure that foreign matter cannot enter the
cabinet. Close the doors and cover openings completely when work is
discontinued.
Any foreign matter which accidentally dropped into the cabinet must be
retrieved. Metallic dust in particular could cause malfunction and damage
when the drive is energized.
• If the drive is delivered in several transport units, the drive must not
be lifted and moved by crane after the transport units have been
joined. Appropriate transport means such as heavy load hydraulic
rollers or air cushions must be used instead. If in doubt, contact ABB
for instructions.
• Drive components can be damaged during transportation. Therefore,
the cabinet must be transported in upright position.
4-2 (6) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 67
ABB Chapter 4 - Transportation, storage and disposal
β
Protect
β
edges!
Note: The lugs can be removed after the cabinet has been installed
at its final location.
• Observe the center of gravity.
• Lift the cabinet slowly and steadily to the required clearance height
maintaining the cabinet in upright position.
• Check the horizontal position of the cabinet. Reposition the slings if
necessary.
To move the drive backwards or forwards (see Figure 4-3) rollers with a
length of 1m should be used, with at least 4 pieces each placed in the
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 4-3 (6)
原図 3N4-S4293202 68
Chapter 4 - Transportation, storage and disposal ABB
areas directly beneath the control cubicle and between the left side and
the left lifting ring.
NOTICE
The rollers must be able to take the full weight of the drive cubicle.
Take appropriate measures when moving the drive cubicle with the rollers.
4.5 Storage
The drive can be stored for up to one year in the original packaging as long
as it is not damaged or opened. For information on longer storage periods
contact the ABB service organization.
4.5.2 Storage
If the drive is taken out of service for a longer time proceed as follows:
1 Remove the batteries (if applicable).
2 Cover all cable inlets and ventilation slots with an impermeable plastic
or aluminum foil and a wooden panel.
3 Add a desiccant of the appropriate quality:
• 1 unit desiccant (30 g) absorbs 6 g water vapor.
4-4 (6) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 69
ABB Chapter 4 - Transportation, storage and disposal
NOTICE
Static electricity can damage printed circuit boards.
Apply static-sensitive precautions when handling these components.
Check the spare parts immediately after receipt for damages. Report any
damage to the shipping company and the ABB service organization.
Observe the following to maintain spare parts in good condition and to
keep the warranty valid during the warranty period:
• Keep spare parts in their original packaging.
• Store printed circuit boards in antistatic bags or boxes.
• Storage temperature range: -5 °C to + 55 °C (23 °F to 131 °F)
• Storage place requirements:
• Free of vibration and shock.
• Protected against dust, sand, vermin and insects.
• Free of corrosive gases, salt or other impurities that could
damage electronic equipment.
• Dry; no condensation
Relative air humidity: 5 to 85%
If in doubt whether the maximum allowed humidity is exceeded,
protect the spare parts by an external heater.
• Do not touch a component without wearing a wrist grounding
strap.
• Put the component on a grounded working surface protected
against electrostatic discharges.
• Hold the component only at the edge.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 4-5 (6)
原図 3N4-S4293202 70
Chapter 4 - Transportation, storage and disposal ABB
4.7 Disposal of packaging materials and components
Dispose of the packaging materials and the components at the end of the
life time of the drive according to local regulations.
4-6 (6) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 71
ABB
5.1 Safety
All installation work must be carried out by qualified personnel according
to the site and equipment requirements and in compliance with local
regulations.
NOTICE
When working on the drive, ensure that foreign matter cannot enter the
cabinet. Close the doors and cover openings completely when work is
discontinued.
Any foreign matter which accidentally dropped into the cabinet must be
retrieved. Metallic dust in particular could cause malfunction and damage
when the drive is energized.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 5-1 (6)
原図 3N4-S4293202 72
Chapter 5 - Mechanical installation ABB
Contact the ABB service organization if the condition of the installation site
is not within the specifications or if the transportation or the installation
require special measures.
See
• Rating plate of the drive for the maximum ambient temperature
• Appendix B - Technical data for information on the climatic and
environmental conditions based on IEC 60721-3
Classification: 3K3 / 3B1 / 3C2 / 3S2 / 3M3
5-2 (6) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 73
ABB Chapter 5 - Mechanical installation
x x ACS 1000i
x x
If the doors do not open and close properly place levelling plates under the
base (see 5.4.2 Installation procedure).
NOTICE
When working on the drive, ensure that foreign matter cannot enter the
cabinet. Close the doors and cover openings completely when work is
discontinued.
Any foreign matter which accidentally dropped into the cabinet must be
retrieved. Metallic dust in particular could cause malfunction and damage
when the drive is energized.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 5-3 (6)
原図 3N4-S4293202 74
Chapter 5 - Mechanical installation ABB
Proceed as follows:
1 Drill the floor fixing holes before moving the drive to the final location.
2 Be careful when moving the drive.
See Chapter 4 - Transportation, storage and disposal, 4.2 Transport
conditions for information to be observed.
3 Check if the doors are misaligned.
If the doors do not open and close properly place levelling plates
(80 x 300 x 0.5 mm) under the base:
1 Lift the drive by crane at the corresponding side (see Figure 5-3).
2 Place the required number of plates under the base.
For the position of the levelling plates see the arrows in
Figure 5-3.
5-4 (6) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 75
ABB Chapter 5 - Mechanical installation
Mounting the cable The cable duct must be mounted if the power cables are entered through
duct the roof of the cabinet.
The cable duct is fastened to the cabinet roof using the supplied screws.
Mounting the fan units Standard drives have two fan units. Redundant versions have four fan
units.
The fan units have different sizes. The mounting position can be identified
by the cutout in the drive roof. The mounting surface of a fan unit
corresponds to the cutout in the drive roof.
Proceed as follows:
1 Remove the transportation covers on top of the cabinet.
2 Carefully lift the fan unit onto of the cabinet using the supplied lifting
eyes.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 5-5 (6)
原図 3N4-S4293202 76
Chapter 5 - Mechanical installation ABB
3 Align the four screw holes on the underside of the fan unit with the
screw holes on the cabinet roof and carefully lower the fan unit to the
roof.
4 Enter the supply cable of the fan motor through the cable entry.
Cable entry
Rear
5 Fix the fan unit to the roof, using the supplied bolts.
6 Mount the fan cover.
7 Plug the supply cable into its counterpart inside of the drive.
5-6 (6) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 77
ABB
6.1 Safety
WARNING
Hazardous voltage!
Improper work could lead to life-threatening injury or death.
The electrical installation must be carried out by qualified personnel
according to the site and equipment requirements, and the relevant
electrical codes.
When the electrical installation is completed, the main and auxiliary power
supply to the drive must not be switched on without the consent of the ABB
commissioning personnel.
Take appropriate measures to prevent main and auxiliary power supply
being switched on during installation.
6.3.1 General
The connection from the mains supply to the drive and from the drive to
the motor comprises the following power cables:
• Feeder cables (transformer primary cables)
• Motor cables
Recommendations for the installation of these components are given
below. All applicable manufacturer's instructions and local regulations
must be followed when installing this equipment.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 6-1 (10)
原図 3N4-S4293202 78
Chapter 6 - Electrical installation ABB
6.3.2 Power cable dimensions
In order to determine the exact dimensions for a specific project, the actual
situation (method of installation, voltage drop due to cable length etc.) and
local regulations must be considered. Refer also to the specifications
supplied by the power cable manufacturer.
Installation The installation must be in compliance with standard industry practice for
medium voltage equipment.
Installation The installation must be in compliance with standard industry practice for
medium voltage equipment.
6-2 (10) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 79
ABB Chapter 6 - Electrical installation
Requirements It is important that the drive is properly grounded to maintain safety and to
ensure smooth functioning of the equipment.
The equipotential bonding conductor must be securely tied to the ground
system of the installation site and to the ground bus closest to the cable
entry of the drive. See 6.4 Recommended grounding scheme for further
information.
Cross-section The cross-section of the equipotential bonding conductor and the ground
connection must be in compliance with national and local electrical codes.
Recommended minimum cross-section of equipotential bonding
conductor: 50 mm2.
Power cables Routing of mains and motor cables must be carried out in compliance with
the local regulations and according to the specifications and
recommendations of the cable manufacturer.
• For best EMC performance, screened three phase cables are
recommended.
• If single phase cables are used, the cables with the three different
phases must be grouped close together to ensure best EMC
performance.
• Phase interchange must be accomplished according to local
regulations.
If the cross-section of the cable screening is less than 50% of the cross-
section of one phase, an additional grounding wire should be laid along
the power cables to avoid excessive heat losses in the cable screenings.
See the local regulations for further details.
Cable termination Cables must be terminated with connectors according to the cable
manufacturer's requirements.
Grounding wire Routing of the grounding connection must comply with local regulations.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 6-3 (10)
原図 3N4-S4293202 80
Chapter 6 - Electrical installation ABB
Control cables should not be laid in parallel to the power cables. If this
cannot be avoided, a minimum distance of 30 cm must be maintained
between control and power cables. Control and power cables should be
crossed at an angle of 90°.
Table 6-1 Control cable requirements
1 Integrated input
transformer 1
2 Drive
3 Motor
4 Earth electrode ACS 1000i
5 Ground cable
2 4
6 Cable screen (optional)
7 Cable shield (optional)
8 Equipotential bonding
conductor (optional) U2 V2 W2 PE
5
1 2 3
6
7 Optional
8
1 2 3
U V W PE
5
3 M
4
Figure 6-1 Grounding the drive equipment (recommended scheme)
6-4 (10) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 81
ABB Chapter 6 - Electrical installation
Cable entry and termi- Cable entry into the power terminal compartment is through the top or the
nation bottom of the cabinet. The power terminal compartment is located behind
the bolted cover on the left side of the drive. It is accessible after the cover
and the acrylic pane behind it have been removed. The terminal bars can
be identified by their phase designations.
Legend 1
1 Terminal compartment
2 Feeder terminals and
input isolator
3 Feeder terminals 2
(detail)
4 Ground bus and
terminal
5 Motor terminals (detail)
3
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 6-5 (10)
原図 3N4-S4293202 82
Chapter 6 - Electrical installation ABB
See Appendix C - Mechanical drawings for details on entry plates
(dimensions) and on busbars (dimensions, layout).
Minimum creepage When using spacers for cable connection to a busbar, the minimum
distance required creepage distance must be observed. Depending on the
Comparative Tracking Index (CTI) of the insulation material of the cable
the following Minimum Creepage Distances (MCD) apply:
Table 6-2 Creepage distance
MCD in mm CTI
63 600
71 400 to 600
80 175 to 400
If the CTI value of the insulation material is unknown, the values in row
three of the table apply.
Equipotential bonding The terminal compartment is equipped with a ground bus (marked PE,
conductor and cable Protective Earth). The ground bus (see Figure 6-2) is provided to ground
screen connections the armor and screens of the cables and to connect the equipotential
bonding conductor.
NOTICE
If possible, do not cut cables inside the terminal compartment. Make sure
that waste from cable cutting and stripping cannot enter the cabinet. Any
waste which accidentally dropped into the cabinet must be retrieved. The
waste could cause damage or malfunction.
Determining the cable Determine the required length of a cable between the point of entry and
length the connection point inside the cabinet. Cut the cable to the required
length before connection to avoid excess cable to be stored in the cable
ducts.
6-6 (10) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 83
ABB Chapter 6 - Electrical installation
If two conductors are used per phase, mount the second conductor
on the rear side of the busbar.
WARNING
High voltages will be present in the terminal compartment. High voltages
can cause flashover between the potential of a phase conductor and
ground.
The required minimum creepage and sparking distances as stated earlier
in this compartment must be observed.
Material requirements Use stainless steel bolts and nuts with the appropriate steel grade and
for bolted connections property class for the connection (recommended: A2-70 [designation
according to ISO 3506]). Nuts with bonded coating can be used as an
alternative to uncoated stainless steel nuts.
Connection type The following connection type is recommended when connecting a cable
lug (3) to a busbar:
Spring washer (1) and flat washer (2) on each side of the busbar (4).
1 2 4 3 2 1
Other washers may be used, provided they can maintain the required
contact pressure.
Lubrication If stainless steel bolts and nuts are used, lubricate the thread and head
contact surface of the bolt using recommended pasts, e.g. Molykote D
paste.
Note: If a coated nut (e.g. with bonded molybdenum-disulfide [MoS2]
coating) is used, the connection does not have to be lubricated.
Tightening torque Tighten bolted connections with the nominal torque recommended by the
cable manufacturer (typical value for M12: 40 Nm)
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 6-7 (10)
原図 3N4-S4293202 84
Chapter 6 - Electrical installation ABB
6.5.3 Additional cabinet compartments
If optional additional cabinet compartments are delivered as separate
units, they must be connected to the drive on site according to the supplied
specific mounting instructions.
Determining the cable Determine the required length of a cable between the point of entry and
length the connection point inside the cabinet. Cut the cable to the required
length before connection to avoid excess cable to be stored in the cable
ducts.
Cable entry and cable 1 Remove the cover of the cable entry. The cover can be used as an
connection entry plate.
Figure 6-4 illustrates the top cable entry (1) for control and auxiliary
power cables.
6-8 (10) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 85
ABB Chapter 6 - Electrical installation
2 Drill holes adequate for the diameter of the cables and cable glands.
3 Enter the cables through the roof or the bottom.
4 Connect the cables and fasten them to the fastening rail as shown in
Figure 6-5.
4
3
Figure 6-5 Fastening rail and terminals
Figure 6-6 Cable entry from top (A) and from bottom (B)
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 6-9 (10)
原図 3N4-S4293202 86
Chapter 6 - Electrical installation ABB
With bottom cable entry the cable is routed as shown in B in Figure 6-6
and connected to the terminals shown in Figure 6-5.
It is recommended to seal the bottom cable entry with polyurethan foam.
Terminal sizes The size of the terminals is suitable for wires with a maximum cross-
section of 0.2 to 2.5 mm2.
Terminal sizes The size of the terminals is suitable for wires with a maximum cross-
section of 0.2 to 2.5 mm2.
Shielded cables If shielded cables are used, connect the cable shield to PE using shield
grounding clamps (e.g. Phoenix) as shown in Figure 6-7. The shield
grounding clamps are fastened to the fastening rail inside the control
compartment as illustrated in 4 in Figure 6-5.
6-10 (10) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 87
ABB
Chapter 7 - Commissioning
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 7-1 (2)
原図 3N4-S4293202 88
Chapter 7 - Commissioning ABB
7-2 (2) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 89
ABB
Mechanical installation
4 Visual inspection:
- no badly affixed or damaged components
- no foreign objects inside cabinet
- no dirt, dust and humidity inside cabinet
Electrical installation
1 Types and cross-sections of control cables suitable for the signal type and signal level
2 Types and cross-sections of power cables selected according to the “ABB power cable
specification”
3 Pulse encoder connected according to the relevant manual (only applicable for drives
with pulse encoder interface)
5 All control cable screens and conductors are connected according to the instructions of
the User’s manual, appropriately labelled, and the customer-side connections are
completed
6 Equipotential bonding conductor of drive securely connected at both ends
7 Supply and motor cables not connected at both ends (cables and drive must be
meggered before connection)
原図 3N4-S4293202 90
Commissioning check list ABB
Main circuit breaker (MCB)
Motor
Insulation tests
1 All power cables to converter transformer, between converter transformer and drive,
and from drive to motor are meggered, and measured values are within the required
limits.
2 Test report of the megger test available
Note: If the test is carried out by the commissioning engineer of the drive, an additional
day per drive motor combination needs to be reserved. After the test, the feeder cables
can be connected, except at the drive end. The test must comply with the specification.
原図 3N4-S4293202 91
ABB Commissioning check list
Power supply
Miscellaneous
原図 3N4-S4293202 92
Commissioning check list ABB
原図 3N4-S4293202 93
ABB
Chapter 8 - Operation
8.1 Overview
The chapter outlines the local operation using the CDP control panel and
the control switches on the control compartment door of the drive as
illustrated in 8.3.1 Overview of local operator panel.
Control of the drive via a PLC or higher-level control systems is not
described in this chapter. If the drive is controlled from remote, see the
appropriate manuals for information.
Note: The panel messages and parameter settings used in this chapter
are typical examples to illustrate the related instructions and display
functions and may therefore differ from the actual messages and
parameter settings in your drive.
8.2 Safety
The drive system must only be operated by qualified and authorized
personnel, i.e. personnel who are familiar with the operation of the drive
system and the hazards involved.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 8-1 (14)
原図 3N4-S4293202 94
Chapter 8 - Operation ABB
Legend
See Chapter 9 - CDP control panel for further information on the CDP
control panel.
8-2 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 95
ABB Chapter 8 - Operation
See the status words in the Appendix G - Signal and parameter table of
the drive for information on other status messages, such as fault status
messages in particular.
The status message signals that the drive is healthy and ready for the ON
RdyForMCBOn command. The ON command initiates charging of the DC link capacitors
and closing of the main circuit breaker of the drive. Depending on the
control place, the command can either be sent from the higher-level
control system to the drive or be initiated by pressing the Main circuit
online pushbutton on the control compartment door.
The message Rdy to Strt tells the operator that the drive is energized and
Rdy to Strt ready for operation. As soon as the start command is initiated, the motor
is magnetized and the drive starts to modulate.
The status message Rdy to Strt changes to Magnetizing when the firing
Magnetizing pulses of the inverter are released.
Stopping indicates that the drive has received a stop command and that
Stopping a ramp or coast stop has been initiated. The stopping mode depends on
the parameter setting. The status indication changes to Rdy to Strt when
the zero speed threshold is reached.
When a start command is given while the drive is stopping, the drive
resumes operation and the status indication changes to Running again.
The status message Rdy to Strt changes to Discharging when the MCB
Discharging has opened and the DC link capacitors are discharging.
The status message indicates that a fault condition has occurred that
Tripped requires a shutdown of the drive. The status message always alternates
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 8-3 (14)
原図 3N4-S4293202 96
Chapter 8 - Operation ABB
with the specific fault message. The type of shutdown depends on the fault
class the fault condition is assigned to in the drive software.
8-4 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 97
ABB Chapter 8 - Operation
Not ready on
Ready on conditions:
Auxiliary supply on
Doors closed and locked
Drive not grounded
No emergency off
No fault
RdyForMCBOn
On command
Charging
DC link charges
Fan switches on
MCB closes
Rdy to Strt
Start command
Magnetizing
Running
Operation
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 8-5 (14)
原図 3N4-S4293202 98
Chapter 8 - Operation ABB
8.4.3 Stop sequence
Operation
Running
Stop command
Stopping
Rdy to Strt
Off command
Discharging
MCB opens
DC link discharges
Fan switches off
after a delay
RdyForMCBOn Actions:
Drive is grounded
Doors are released for opening
Auxiliary supply is switched off
Not ready on
8-6 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 99
ABB Chapter 8 - Operation
Operation
Running
Emergency-off command
MCB opens
Inverter stops to modulate
Speed coasts down
Not ready on
8.5.1 Prerequisites
The drive has been properly installed and commissioned.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 8-7 (14)
原図 3N4-S4293202 100
Chapter 8 - Operation ABB
8.5.2 Checks before starting the drive system
DANGER
Hazardous voltages!
All doors must be closed and all covers must be screwed in place to
prevent unintentional contact with energized components.
When the drive system is put into service after it has been commissioned,
or after it has been taken out of service for a longer period, check the drive
according to the following list:
• Check that no tools and foreign objects are left inside the cabinet.
• Check that all auxiliary power supplies from external sources are
switched on.
• Check that all internal circuit breakers of the drive are closed.
• Check that all covers are mounted and the doors are closed, locked
or bolted.
• Check that the input disconnector and grounding switch lever is in
position I (not grounded.)
• If applicable: check that input and output isolators are closed.
• Check that the MCB is in operating position.
• Check that there is no run interlock active.
The drive is now ready to be started.
8-8 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 101
ABB Chapter 8 - Operation
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 8-9 (14)
原図 3N4-S4293202 102
Chapter 8 - Operation ABB
See also Flow diagram in 8.4.2 Start sequence of the drive.
After the motor has been magnetized, the motor speed ramps up to
the setpoint.
While the motor is accelerating, the run status indication on the
display blinks. When the motor speed has reached the setpoint, the
run status indication lights up permanently.
8-10 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 103
ABB Chapter 8 - Operation
The display shows Running to indicate that the drive system is oper-
ating:
8.6 Stopping
Press the stop key on the CDP control panel.
The motor stops according to the preset stop function and the drive stops
modulating. While the motor stops, the status line of the display shows
Stopping. The run status indication blinks during the stop sequence.
When the drive has stopped modulating, the CDP control panel displays
Rdy to Strt:
As long as the MCB has not been opened, the motor can be started again.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 8-11 (14)
原図 3N4-S4293202 104
Chapter 8 - Operation ABB
8.7 Emergency-off
8.7.1 Function
The drive is equipped with a hard-wired emergency-off circuit. When an
emergency situation occurs during operation, this safety feature ensures
that the drive system can be disconnected without delay from the main
power supply. If the emergency-off pushbutton has been pressed while the
drive is at standstill, the main power supply cannot be connected to the
drive, hence the drive cannot be started up.
The emergency-off pushbutton of the drive is part of the operator control
panel (see Figure 8-1) and features a latching switch action.
Note: Pressing the emergency-off pushbutton does not disconnect the
auxiliary power supply from the drive.
8-12 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 105
ABB Chapter 8 - Operation
Now, the main power supply can be connected to the drive again and the
drive system can be started up.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 8-13 (14)
原図 3N4-S4293202 106
Chapter 8 - Operation ABB
8-14 (14) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 107
ABB
9.1 Overview
Note: The panel messages and parameter settings used in this chapter
are typical examples to illustrate the related instructions and display
functions and may therefore differ from the actual messages and
parameter settings in your drive.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 9-1 (22)
原図 3N4-S4293202 108
Chapter 9 - CDP control panel ABB
The CDP control panel can be attached to or detached from the drive
without having to switch off the auxiliary power supply first.
Using the CDP control panel it is possible to
• enter start-up data,
• control the drive with a reference value and start, stop and direction
commands,
• display actual values (three values can be read simultaneously),
• display and adjust parameters,
• display information on the most recent forty fault events,
• upload and download complete parameter sets from one drive to
another.
........
9-2 (22) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 109
ABB Chapter 9 - CDP control panel
After 2-3 seconds, information on the drive (1, 2) and the drive
identification (3) is displayed.
ID-NUMBER 1 3
After another few seconds, the display changes to the actual signal
display mode.
9.5.1 Overview
Two kinds of displays can be selected in the actual signal display mode:
• Actual signal display
• Fault history display
The actual signal display appears first when the actual signal display
mode has been selected. However, when the drive is in a fault condition,
the fault display will be shown instead.
The actual signal display is used to monitor the drive without interfering
its operation. Three selectable actual values are shown continuously on
the display.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 9-3 (22)
原図 3N4-S4293202 110
Chapter 9 - CDP control panel ABB
The CDP control panel will automatically return to the actual signal
display mode from other modes within one minute when no keys are
pressed (exceptions: status display and common reference display
when in drive selection and fault display mode).
See Appendix G - Signal and parameter table for the complete list of
selectable actual signals.
1 Status line
2 Actual signal names and
values
3 Selects the function
mode 1 L -> 600.0 rpm 1
Status RdyForMCBOn
4 Selects actual signals
and faults
MotorSpeed 0.00 rpm 2
Power 0.0 %
5 Scrolls through signal
and fault messages
6 Enters the selection 3
mode
Acknowledges the 4
selection 5
6
9-4 (22) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 111
ABB Chapter 9 - CDP control panel
Fault memory The fault memory includes information on the 64 most recent fault events
that occurred in the drive. The name of the fault and the actual time are
displayed. The procedure for selecting and clearing the fault history is
described in 9.5.5 Displaying and resetting an active fault.
When a fault or warning is generated in the drive, the message will be
displayed immediately, except when in drive selection mode.
Changing from the fault display mode to other display modes is possible
without resetting the fault first. When no keys are pressed, the fault or
warning text is displayed as long as the fault is pending.
Selecting the actual The actual signal display mode is selected by pressing the ACT key.
signal display
Toggle between actual When in actual signal display mode, the fast up or down keys allow to
signal display and fault toggle between actual signal display and fault history display.
history
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 9-5 (22)
原図 3N4-S4293202 112
Chapter 9 - CDP control panel ABB
9.5.2 Displaying three actual signals
1 To display the full name of three actual signals, press and hold the
ACT key:
9-6 (22) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 113
ABB Chapter 9 - CDP control panel
3 To enter the actual signal selection function, press the ENTER key:
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 9-7 (22)
原図 3N4-S4293202 114
Chapter 9 - CDP control panel ABB
7 To cancel the selection and keep the original selection, press any of
the mode keys:
9-8 (22) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 115
ABB Chapter 9 - CDP control panel
2 To enter the fault history display, press any of the fast navigation
keys:
H MIN S
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 9-9 (22)
原図 3N4-S4293202 116
Chapter 9 - CDP control panel ABB
5 To return to the actual signal display mode, press any of the fast
navigation keys:
9-10 (22) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 117
ABB Chapter 9 - CDP control panel
NOTICE
Running the drive system with incorrect data can result in improper oper-
ation, reduction of control accuracy and damage of equipment. Do not
change any parameter, if the meaning of the parameter and the effects of
the change are not fully understood.
9.6.1 Overview
Parameters allow the drive to be configured and set-up specifically for an
application. Parameters are organized in functional groups. All control
functions are represented by a parameter group and can be activated and
set-up individually by the parameter mode.
Table 9-2 Commonly used parameter groups
Group 17 Utilities
Group 20 Limits
See Appendix G - Signal and parameter table for further information on the
parameters, their settings and functions.
When the parameter mode is entered for the first time after the auxiliary
voltage of the drive has been switched on, the display will show the first
parameter of parameter group 99 (Language: ENGLISH). The next time
the parameter mode is entered, the previously selected parameter is
shown.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 9-11 (22)
原図 3N4-S4293202 118
Chapter 9 - CDP control panel ABB
Some parameter values cannot be changed while the drive is running. If
tried, the following warning will be displayed:
** Warning **
Write Access Denied
Parameter Setting
Not Possible
Legend
1 Status line
2 Group number and name
3 Parameter number and
name 1 L -> 600.0 rpm 0 1
4 Parameter value 75 OPTION MODULES 2
5 Selects the parameter 01 IOEC3 OptionBoard 3
mode YES 4
6 Selects the parameter
number and name
5
7 Selects the parameter
value
8 Enters change mode 6
7
Acknowledges the
selection 8
9-12 (22) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 119
ABB Chapter 9 - CDP control panel
9.6.2 Procedure
1 To enter the parameter mode, press the PAR key:
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 9-13 (22)
原図 3N4-S4293202 120
Chapter 9 - CDP control panel ABB
4 To enter the parameter setting function, press the ENTER key:
7 To cancel the setting and keep the original selection, press any of the
mode keys.
The selected CDP control panel mode is entered.
9-14 (22) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 121
ABB Chapter 9 - CDP control panel
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 9-15 (22)
原図 3N4-S4293202 122
Chapter 9 - CDP control panel ABB
9.7 Function mode
9.7.1 Overview
The function mode is used to set the display contrast.
Legend
1 Status line
2 Selectable functions
3 Selects the function
mode
1 L -> 0.0 rpm 0 1
4 Selects the line UPLOAD <= <=
5 Acknowledges the DOWNLOAD => => 2
selection CONTRAST 4
4
5
9.7.2 Procedure
1 To enter the function mode, press the FUNC key:
9-16 (22) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 123
ABB Chapter 9 - CDP control panel
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 9-17 (22)
原図 3N4-S4293202 124
Chapter 9 - CDP control panel ABB
5 To accept the selection and to return to the actual signal display
mode, press the ENTER key:
6 To cancel the setting and keep the original selection, press any of the
mode keys.
The selected CDP control panel mode is entered:
Local control When the CDP control panel is switched to local, operation via the
pushbuttons on the control compartment door and the CDP control panel
is possible. Control commands from remote have no effect.
9-18 (22) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 125
ABB Chapter 9 - CDP control panel
Remote control When the CDP control panel is switched to remote, the pushbuttons on
the control compartment door and the operational keys of the CDP control
panel are disabled. Operational commands and reference value from a
remote control station are transmitted via fieldbus or remote I/O to the
drive. Switching from remote to local while the drive is running is not
possible.
Selecting local To select local control, press the LOC- REM key. The local control location
is indicated by the letter L.
1 L 600.0 rpm 0
Status Ready to Strt
MotorSpeed 0.00 rpm
Power 0.0 %
Selecting remote To select remote control, press the LOC - REM key. The remote control
location is normally indicated by a blank (see arrow).
1 600.0 rpm 0
Status Ready to Strt
MotorSpeed 0.00 rpm
Power 0.0 %
If desired, the START or STOP command can then be given and the
reference value can be set from the CDP control panel (for example
START or STOP from remote while the reference value is set from the
CDP control panel). To achieve this, the relevant parameters 11.01, 11.02,
12.03 or 12.06 must be set to KEYPAD.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 9-19 (22)
原図 3N4-S4293202 126
Chapter 9 - CDP control panel ABB
If any of these parameters is set to KEYPAD and remote control is
selected, this is indicated by the letter R (see arrow).
1 R 600.0 rpm 0
Status Ready to Strt
MotorSpeed 0.00 rpm
Power 0.0 %
9-20 (22) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 127
ABB Chapter 9 - CDP control panel
When the direction of rotation is changed while the motor is running, the
speed will automatically ramp to zero and the motor will accelerate in
opposite direction to the preset speed. The direction of the arrow on the
display changes to the new direction when the motor has reached zero
speed.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 9-21 (22)
原図 3N4-S4293202 128
Chapter 9 - CDP control panel ABB
4 To exit the setpoint setting mode, press any of the mode keys:
9-22 (22) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 129
ABB
10.1.5 Logbook
It is recommended to record all troubleshooting and maintenance work in
a logbook including:
• Date and time
• Detailed description
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 10-1 (20)
原図 3N4-S4293202 130
Chapter 10 - Troubleshooting and maintenance ABB
10.2 Identifying electrical equipment
10-2 (20) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 131
ABB Chapter 10 - Troubleshooting and maintenance
10.3 Troubleshooting
The display message can be saved and viewed in the fault logger of the
drive when a PC with the DriveWindow, DriveDebug or DriveMonitorTM
tool is connected to the drive. The fault logger can also be called up on the
CDP control panel.
Alarm or warning An alarm does not shut down the drive. However, a persisting alarm
condition can often lead to a fault if the condition causing the alarm is not
corrected. An alarm cannot be reset manually (Exception: Pump alarm, if
Parameter 41.1 is set). The alarm message will be deleted from the
display as soon as the alarm condition has been corrected.
Fault A fault always shuts down the drive. The type of shutdown depends on the
origin of the fault.
Depending on the type of fault, the MCB is opened by the drive or stays
closed.
In general, a fault condition must be corrected and the fault be manually
reset before the drive can be started again.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 10-3 (20)
原図 3N4-S4293202 132
Chapter 10 - Troubleshooting and maintenance ABB
• Then the zero voltage vector will be switched to short circuit the
machine. After a programmable period (5 times the rotor time
constant, at least 1second) the inverter will be switched off.
• Trip 1 (with de-magnetization)
Trip 1 will be used for slower protective actions and includes the
following actions:
• The flux will be reduced with a ramp in order to avoid overcur-
rents.
• Then the zero voltage vector will be switched to short-circuit the
machine. After a programmable period (5 times rotor time
constant, at least 1second) the inverter will be switched off.
• Depending on the failure, the MCB will stay closed (trip 1a) or be
opened (trip 1b).
• Trip 2 (without de-magnetization)
Trip 2 will be used for fast protective actions and includes the
following actions:
• All inverter IGCTs will be switched off immediately.
• In case of a GUSP failure the protection IGCTs will be opened
immediately. In case of another fault the protection IGCTs will
stay closed until the DC link voltage reaches the undervoltage
alarm level.
• Depending on the failure, the MCB will stay closed (trip 2a) or be
opened (trip 2b).
• Trip 3 (with zero vector)
Trip 3 is an enhanced version of trip 2 and normally only is initiated if
a serious damage to the inverter has occurred:
• The zero voltage vector will be switched immediately to short
circuit the machine.
• In case of short circuit faults the protection IGCTs will be opened
immediately. In case of another fault the protection IGCTs will
stay closed until the DC link voltage reaches the undervoltage
alarm level.
• the MCB will be opened.
Alarm and fault In the event of an alarm or a fault, a specific message is saved in the fault
handling logger of the drive. Information on the 64 most recent fault and alarm
events are saved.
The faults are entered into the fault buffer as they occur and are
numbered; the last fault entered always has number 1 assigned to it and
the first fault always has the highest number in the fault buffer.
Date and time stamps facilitate fault tracing, especially when a fault leads
to several subsequent faults.
10-4 (20) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 133
ABB Chapter 10 - Troubleshooting and maintenance
Example:
1. -Fault RESET FAULT 2011-04-26 14:57:56.5370
2. +Fault Undervoltage 2011-04-26 14:47:41.1110
3. +Warn Undervoltage 2011-04-26 14:47:41.1000
4. +Fault MCB Disturb 2011-04-26 14:47:38.0230
In the above example:
• 4. +Fault MCB Disturb is the reason for the failure of the drive, as it
occurred first.
• The message 3. +Warn Undervoltage occurred approx. 3 sec after
the first fault.
• The message 2. +Fault Undervoltage immediately followed the
warning.
• The message 1. -Fault RESET FAULT informs that the fault has been
reset.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 10-5 (20)
原図 3N4-S4293202 134
Chapter 10 - Troubleshooting and maintenance ABB
After the fault has been rectified, start the drive as described in Chapter 8
- Operation.
CAUTION
If the control circuit of the grounding switch malfunctions, it is possible that
the grounding switch can be closed while the DC link is still charged.
As a consequence, the DC capacitors are short-circuited and the short-
circuit will cause a loud bang.
To avoid a temporary minor hearing impairment, follow the instructions
below.
After the DC link of the drive has been de-energized, the lamp
GROUNDING SWITCH UNLOCKED lights up to indicate that the
grounding switch is released and can be turned to the grounded position.
If for some reason the lamp does not light up or if a malfunctioning of the
grounding circuit is presumed, proceed as follows:
1 Do not try with force to turn the grounding switch in any direction.
The handle or the switch could be damaged if tried.
2 Verify that the DC link has been discharged.
The discharging level can be viewed in parameter 2.01 DC
VOLTAGE. The value should be below 50 V.
3 Verify that the MCB is in the open position and racked out.
4 Check if there are any alarm and fault messages on the display.
5 Try to rectify the reason for the alarms and faults, and then press the
reset key on the CDP control panel.
6 Call ABB service if the cause for the malfunctioning grounding switch
cannot be rectified.
See General information on manual and equipment for address.
10-6 (20) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 135
ABB Chapter 10 - Troubleshooting and maintenance
1 2 3
Meaning of the LEDs The green LED (see arrow in 3) is illuminated when the control voltage has
been switched on.
The red LED is not used.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 10-7 (20)
原図 3N4-S4293202 136
Chapter 10 - Troubleshooting and maintenance ABB
10.6.1 AMC circuit board
F R
M P
T1 T2
S3 S1
S4 S0
P green Supply OK
10-8 (20) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 137
ABB Chapter 10 - Troubleshooting and maintenance
LEDs
1 2 3 4 5
LED Meaning
Cluster address Each IOEC module has a unique cluster address that identifies the module
in the software and links it to a parameter.
The address is set with the rotary switch on the module (see 3 in Figure
10-3). The factory set value must not be changed.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 10-9 (20)
原図 3N4-S4293202 138
Chapter 10 - Troubleshooting and maintenance ABB
10.6.3 Serial communication interfaces
See Appendix D - Wiring diagrams or the Parts list to identify the serial
communication interface in your drive and select the appropriate manual
from the list below for further information:
• AF 100 fieldbus - NAFA-01 installation and start-up guide
• DeviceNet - NDNA-02 installation and start-up guide
• Ethernet - user’s manual ethernet adapter module NETA-01
• Modbus - NMBA-01 installation and start-up guide
• Profibus - NPBA-12 installation and start-up guide
• CI858 DriveBus - user’s manual
10.7 Maintenance
10-10 (20) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 139
ABB Chapter 10 - Troubleshooting and maintenance
10.7.2 Safety
DANGER
Hazardous voltages!
Before starting to work on the drive, make sure that:
• the main and auxiliary power supply to the drive is switched off,
locked out, and tagged out,
• the drive is dead,
• safety ground connections are in place,
• personal protective equipment is provided and used when required,
• everyone involved is informed.
Before energizing the drive again, make sure that:
• all foreign objects are removed from the drive,
• all internal and external covers are securely fastened and all doors
are closed, locked and/or bolted.
DANGER
Hazardous voltages!
If a phase module has to be removed from the drive, the connection of
grounding equipment at the appropriate locations is a must. The
grounding equipment ensures that hazardous voltages cannot be fed into
the drive neither from the main power supply nor the motor.
NOTICE
When working on the drive, ensure that foreign matter cannot enter the
cabinet. Close the doors and cover openings completely when work is
discontinued.
Any foreign matter which accidentally dropped into the cabinet must be
retrieved. Metallic dust in particular could cause malfunction and damage
when the drive is energized.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 10-11 (20)
原図 3N4-S4293202 140
Chapter 10 - Troubleshooting and maintenance ABB
10.7.3 De-energizing the drive
The following section describes how to de-energize the drive using the
local operator panel of the drive. If the drive is controlled from remote,
follow the established shutdown procedures.
10-12 (20) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 141
ABB Chapter 10 - Troubleshooting and maintenance
See Rating label of the drive for information on the permitted air
temperature range.
• Dust built-up inside the drive room and inside the drive
• Signs for overheated components, wires, cables or busbars
• Corrosion on circuit boards, connectors or busbars
• Appropriate fastening of cables and wires and connections of cable
screens
See Chapter 6 - Electrical installation if further information is required.
• Integrity of cable insulation
The outer cable sheath must not be damaged.
• Correct type of signal and power cables
See applicable cable specifications for reference.
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 10-13 (20)
原図 3N4-S4293202 142
Chapter 10 - Troubleshooting and maintenance ABB
10.7.5 Cleaning
Dust on electrical components and wiring can cause malfunction and
damage the components. Dust and moisture can build up in loose
connections and cause loss of low-level signals.
For these reasons, the cabinet should be checked regularly and cleaned
if necessary.
When cleaning the drive cabinet, mind the following:
• Cover equipment or assemblies to prevent dirt falling into them.
• The drive contains components which are sensitive to electrostatic
discharge. Therefore, take electrostatic-sensitive precautions and
use suitable tools when cleaning circuit boards and assemblies that
are sensitive to electrostatic discharge.
Circuit boards should be cleaned with special care using antistatic
brushes and a vacuum cleaner with a soft nozzle to prevent compo-
nent damage.
• Dust inside the cabinet (assemblies, busbars etc.) can be removed
with a vacuum cleaner and lint-free cleaning cloths.
• Water, oily or greasy deposits on assemblies, components, busbars
etc. should be removed with water- and oil-absorbing microfibers
such as "3M Scotch Brite".
• Use a nylon brush or a vacuum cleaner to remove dust or deposits
from holes.
• The outside of the drive enclosure can be cleaned using a vacuum
cleaner and cleaning cloths.
Do not use alcohol or solvents.
10-14 (20) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 143
ABB Chapter 10 - Troubleshooting and maintenance
Location The drive is equipped with an open air cooling. The filter mats are located
behind the air intake grilles of the inverter compartment door (1 in Figure
10-4) and in the lower area of the rectifier and filter compartment (2 in
Figure 10-4).
Note: Filter mats can be checked, cleaned and replace while the drive is
in operation.
DANGER
High voltage can cause injury or death.
When removing the filter mats of the air intakes, especially while the drive
is in operation, be careful that no items (such as wires, screw drivers etc.)
can enter the hole grate by accident (see Figure 10-7).
These items can cause short circuits which can result in injury, death and
severe damage of the drive.
Checking Check the filter mats regularly. The intervals at which the mats are
checked depend on the cleanliness of the cooling air.
Cleaning The filter mats can be cleaned using compressed air or a vacuum cleaner.
Cleaning should always be carried out away from the drive so that dust
cannot enter the cabinet.
Replacement When removing a filter mat, proceed as quickly as possible and do not
discontinue work for a longer period to prevent foreign matter entering the
drive.
If the filter mats are replaced, filter material for the minimum particle size
as specified in the type code of the drive must be used. Position 29 of the
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 10-15 (20)
原図 3N4-S4293202 144
Chapter 10 - Troubleshooting and maintenance ABB
type code (see highlighted positions in Table 10-1) specifies the required
minimum particle size the mat must be able to filter.
Table 10-1 Filter material specification with type code
ACS1x4x-Ax-xx-xx-xxxx-xxxx-xxxx-xxxC-xxxxx-xx ≥ 18 μm
ACS1x4x-Ax-xx-xx-xxxx-xxxx-xxxx-xxxD-xxxxx-xx or ≥ 12 μm
ACS1x4x-Ax-xx-xx-xxxx-xxxx-xxxx-xxxE-xxxxx-xx or
ACS1x4x-Ax-xx-xx-xxxx-xxxx-xxxx-xxxF-xxxxx-xx or
ACS1x4x-Ax-xx-xx-xxxx-xxxx-xxxx-xxxG-xxxxx-xx
ACS1x4x-Ax-xx-xx-xxxx-xxxx-xxxx-xxxH-xxxxx-xx or ≥ 10 μm
ACS1x4x-Ax-xx-xx-xxxx-xxxx-xxxx-xxxJ-xxxxx-xx or
ACS1x4x-Ax-xx-xx-xxxx-xxxx-xxxx-xxxK-xxxxx-xx or
ACS1x4x-Ax-xx-xx-xxxx-xxxx-xxxx-xxxL-xxxxx-xx
10-16 (20) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 145
ABB Chapter 10 - Troubleshooting and maintenance
Figure 10-7 Hole grate behind filter mat (seen from rear side)
Checking the battery The end of the battery life is indicated in two ways:
• The CDP control panel displays an alarm message.
• The alarm LED on the power supply unit for the battery lights up (see
B in Figure 10-8).
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 10-17 (20)
原図 3N4-S4293202 146
Chapter 10 - Troubleshooting and maintenance ABB
Replacement proce- Note: Batteries can be changed while the drive is in operation.
dure
WARNING
Hazardous voltage.
When the drive is in operation, voltages are present in the control
compartment.
Do not touch any live circuitry!
10-18 (20) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 147
ABB Chapter 10 - Troubleshooting and maintenance
Replacement proce- 1 Disconnect all power supplies to the drive and ground the drive.
dure
See 10.7.3 De-energizing the drive if further information is required.
Switch off the motor starter of the fan unit to isolate the fan unit from
the auxiliary power supply.
2 Unplug the supply cable of the fan inside of the drive.
3 Remove the fan cover by loosening and removing the 12 bolts (Figure
10-9).
4 Loosen and remove the five screws located to the left and right side
of the fan insert (1 in Figure 10-10).
ACS 1000i User’s manual 3BHS206977 ZAB E01 Rev. A 10-19 (20)
原図 3N4-S4293202 148
Chapter 10 - Troubleshooting and maintenance ABB
1 1
1
2
1 1
WARNING
The total weight of the fan is approximately 50 kg. It could fall down.
Take appropriate measures when transporting the fan.
10-20 (20) 3BHS206977 ZAB E01 Rev. A ACS 1000i User’s manual
原図 3N4-S4293202 149
ABB
Maintenance schedule
The maintenance schedule applies to all air-cooled and water-cooled medium voltage drives. Note
the maintenance items in the schedule which only apply to particular drives.
The recommended intervals for maintenance and component replacement are based on the normal
operational conditions of the drive. The drive should be checked at least every two years by qualified
personnel whose recommendations should be followed. Depending on the actual condition of the
drive, the maintenance work can be carried out before or after the recommended interval.
A Applies to ACS 1000i, ACS 1000A, ACS 1000W, ACS 2000, ACS 5000A, ACS 5000W, ACS 6000, MEGADRIVE-LCI
B Applies to ACS 1000i, ACS 1000A, ACS 1000W, ACS 2000, ACS 5000A, ACS 5000W
C Applies to all water-cooled drives
D Applies only to ACS 1000i, ACS 1000A, ACS 1000W
1 Air filters can be replaced or cleaned. The decision to replace or clean a filter depends on the condition of the filter.
原図 3N4-S4293202 150
Maintenance schedule ABB
2 The device can be serviced or be replaced by authorized service personnel. It is recommended to replace the device
after four years of operation.
3 The average lifetime of the deionizer is 2-4 years, depending mainly on the water quality. At the same time the
deionizer is changed, the micro filter should also be replaced and the strainer should be cleaned.
4 The expected lifetime of the capacitors depends mainly on the ambient conditions. The recommended intervals are
based on operation with rated current and maximum permitted temperature. A capacitor should be replaced when
regularly taken measurements show significant deviation from the rated capacitance.
5 The expected lifetime of the optical fibers depends mainly on the ambient conditions. The recommended intervals are
based on operation with rated current and maximum permitted temperature. An optical fiber should be replaced when
regularly taken measurements show significant deterioration of the fiber.
6 Improvements based on further development, software modifications, etc. When printed circuit boards must be
replaced, an upgrade of the control system should be considered as well.
原図 3N4-S4293202 151
原図 3N4-S4293202 152
Contact us
Last page
© Copyright 2009 ABB. All rights reserved. Specifications subject to change without notice. 3BHS206977 ZAB E01 Rev. A.
ABB Switzerland Ltd
Medium Voltage Drives
CH-5300 Turgi
Phone: +41 58 589 27 95
Fax: +41 58 589 29 84
E-Mail: mvdrives@ch.abb.com
www.abb.com/drives
原図 3N4-S4293202 153