Design of Tension Members
Design of Tension Members
Design of Tension Members
Introduction
Members that carry pure tension, generally referred to as ties, are relatively simple to
design. In reality, the tension forces are frequently accompanied by moments and the
member must be designed for the combined effects.
Figure 3.6 illustrates various examples of structures with some members that are commonly
assumed to be loaded only in tension. Figure 3.7 shows typical cross sections of tension
members. Simple or built-up rolled sections are commonly used in trusses, lattice girders and
as bracing members. Cables, flats or bars are used in bracing systems.
Typically, the governing design situation for members subject to tension corresponds to the
location of the joints. In these cross sections, either because of bolting, the net area of the
cross section must be taken into account.
p is the spacing of the centers of the same two holes measured perpendicular to the
member axis.
The summation in expression above represents the number of segments between staggered
holes.
In the case of angles, or other member with holes in more than one plane, the spacing p should
be measured along the mid-plane of the legs, as illustrated in Figure 3.2.
For sections with holes the design tension resistance Nt,Rd should be taken as the smallest of:
where A is the gross cross section area, fy is the yield strength of steel and γM0 is the
partial safety factor.
2- Design ultimate resistance of the net cross section at holes for fasteners,
where Anet is the net cross section area, fu is the ultimate strength of steel and γM2 is
the partial safety factor.
When the member is under cyclic loading, the design plastic resistance Npl,Rd
should be less than the design ultimate resistance of the net section at fasteners
holes Nu,Rd.
For angles connected by one leg and other unsymmetrically connected members
in tension (such as T sections or channel sections), the eccentricity in joints and
the effects of the spacing and edge distances of the bolts should be taken into
account in determining the design resistance (clause 3.10.3(1) of EC3-1-8).
Members that comprise angles connected by welding only in one leg can be treated
as being concentrically loaded. Resistance is determined using equation (3.6), but
based on an effective cross section area. The area of the effective cross section,
according to clause 4.13 of EC3-1-8, must be evaluated as follows:
1. for angles of equal legs or unequal legs that are connected by the larger leg,
the area of the effective section may be considered as equal to the gross area;
2. for angles of unequal legs, connected by the smaller leg, the area of the
effective section should be taken as equal to the gross area of an equivalent
angle, with legs that are equal to the smaller of the legs.
3. A common detail is an angle connected by one leg using one or more rows
of bolts as shown below:
where γM0 =1.0, f y = 235 MPa and A is the gross area of the section. Considering the
design axial force, NEd = 220 kN, then:
From a table of commercial profiles, a solution with two angles 50x50x5mm, with a total
area of 2×4.8 = 9.6cm2, satisfies the above safety requirement.
where, γM0 = 1.0, γM2 = 1.25, fy = 235 MPa, fu = 360 MPa, A is the gross area of the cross
section, Anet is the net area of the bolted section, and is a factor obtained from Table 3.1
(or Table 3.8 of EC3-1-8). A first check based on the plastic design of the gross cross
section leads to:
Hence, the section obtained in the previous design, two angles 50x50x5 mm (A = 9.6
cm2), also satisfies this safety requirement.
The second condition (equation (3.11), reproduced above) requires the evaluation of the
net area Anet, (illustrated in Figure 3.14) and the factor 2, both evaluated according to
clause 3.10.3 of EC3-1-8.
For do 18 mm , 2.5do 45 mm and 5do 90 mm .
The net area of the bolted section made up of two angles is given by:
However, NEd 220kN Nu,Rd 157.2 kN ; therefore, the chosen cross section is not
appropriate. By adopting a cross section with enhanced resistance, for example, two
angles 60x60x6 mm (A = 13.82 cm2 and Anet =11.66 cm2), then:
As pl,Rd 324.8 kN Nu,Rd 235.1 kN , failure is non-ductile; however, since this is not
a design condition, the section defined by two angles 60x60x6 mm can be accepted.