Controlling Harmonics While Improving Power Factor
Controlling Harmonics While Improving Power Factor
Controlling Harmonics While Improving Power Factor
While Improving
Power Factor
Interactions between electrical systems, power factor capacitors, and non-linear convertors are examined.
By using traps, power factor can be improved, while problems with harmonic distortion are avoided.
By Michael Z. Lowenstein, Manager, Research & Development, Jim Holley, National Sales Manager
and Myron Zucker, P.E., Chairman of the Board, Myron Zucker, Inc.
Dirty Power
Waveform distortion, often referred to as
The use of capacitors to improve power Capacitors at the load, by providing “dirty power”, becomes serious when the
factor in electrical systems is well known. reactive power where it is needed, power deviates significantly from a pure
A number of different strategies have been reduce the current which must be carried sine wave. Such distortion can take many
well tested in the field. If, for instance, a out by wires all the way back to the forms. High voltage spikes, high frequency
plant load is reasonably constant, power substation. Because I2R losses are ringing, voltage “sag”, and, as in the case of
factor correction capacitors can be reduced, smaller wires can be used, and the wire drawing plant mentioned above,
connected to medium voltage feeders. If a circuit capacity formerly used to system harmonic resonance, can all be found
switched to follow the load. Alternatively, provide reactive power is released for a in situation where dirty power is a problem.
correction can be carried out using low- more beneficial use. Unfortunately, The problem, readily visible on an
voltage capacitor banks installed at the what has historically been a simple oscilloscope as shown in Fig. 1, manifest
main switching centers. Automatic solution to low power factor has been itself within the plant in a number of ways.
controllers can switch capacitance on and made more complicated by the increase
off line to compensate for the varying of in-plant harmonic distortion. The
loads. Investigations have shown that a symptoms have been visible for a
favorable location for power factor number of years.
capacitors is as close to the load as
possible.
Premature motor or capacitor failures have been
traceable to dirty power. Motor symptoms
include overheating, arcing of starting contacts,
and in some cases bearing failure brought about
by rapid pulsing of the rotor. Capacitors have
been observed to overheat, leak, and even burst.
Overheating is also the prime symptom of
conductors and transformers subjected to
harmonic distortion. In the modern computer-
controlled plant effect of dirty controls can
include out-of-sequence operation, faculty of
lost data, can complete failure with destruction
of circuit boards.
The problem of capacitor interaction with SCR drives has been a seri-
ous one. Manufacturers of variable speed drives have traditionally re-
commended against locating power factor correction capacitors in close
electrical proximity to the drives.
While such filters work quite well for individual pieces of electronic equipment, they are not cost effective for filtering of an entire
distribution line carrying hundreds of amperes, since the entire current of the line must be carried by the filter. For industrial power
distribution systems almost all harmonic removal is carried out using tuned shunt filters.
A shunt filter is designed to have a low impedance at high frequencies and to short circuit or "trap" frequencies above those of interest,
thus keeping them from circulating throughout the system. "High pass" filters, are installed as shown in Fig.11. Shunt filters need carry
only a fraction of the current that a series filter would carry and are thus suitable for use in high current systems. The simplest filter is
single tuned and consists of an inductor (or coil) in series with a capacitor. The filter has a low impedance at the frequency to which it is
tuned and the impedance rises slowly at higher frequencies.
In practice filters are designed with fairly broad tuning so that they provide effective removal of several frequencies. For example, a
filter, or "trap," tuned to remove the fifth harmonic (300 Hz) will have some effect in removing the seventh harmonic (420 Hz) as well.
The harmonic current requirements of the SCR drive are not reduced when a trap is installed. The trap, in the same manner that a power
factor capacitor provides reactive power, provides both reactive power and the required harmonic power. The harmonic currents now
circulate between the trap and the load, reducing harmonics in the system. Maximum benefit of a trap will be obtained when it is located
as close to the harmonic source as possible.
An example of the application of a fifth harmonic trap to the line supplying a typical SCR convertor is shown in Fig.12.
Typical ringing in an electrical system containing an SCR convertor and a capacitor is shown in Fig.9. Note the ringing current decays are
retriggered six times per cycle, corresponding to commutation notches of the six-pulse convertor. The ringing frequency in this case is about
2000 Hz. Ringing current adds to the rms current through the capacitor and can contribute to capacitor fuse blowing. In addition to the
ringing phenomenon, the commutation notches can result in excessive currents through the SC. At the moment when the SCR appears as a
short circuit between two phases, a nearby fully charged capacitor can discharge through the SCR. The resulting current peaks rapidly
(large di/dt) and tic instantaneous currents can reach several thousand amperes. Cases have been reported where a large current d spike
has destroyed an SCR before a fuse protecting it could blow.
The problems posed by interactions between SCRs and capacitors so far discussed are not going to go away, in fact they will increase
as more and more SCR power convertors are brought into use. Nor will the need for correcting low power factor disappear. More and
more utilities are recognizing their need to charge for poor power factor, while the increased use of convertors is resulting in overall
lowered power factors and higher customer charges. Since the problem cannot be ignored, what can be done?
Harmonics
A tried and true way to reduce harmonic distortion in a power distribution system is through the use of tuned filters. In many
low-power installations or in specific sensitive systems such as computers, series filters are used. Passing only frequencies below their
tuning point, these are known as "low pass" filters. Such a filter, installed as shown in Fig. 10., can, because of its high impedance at
frequencies above a certain point, effectively block the entrance of such frequencies into a load. The desired 60 Hz fundamental is
passed through the filter with little attenuation.
Note the reduction of harmonic distortion in the line as evidenced by the improved wave shape. Harmonic currents required by the
drive are now being provided locally by the trap. Figure 13 shows the current waveform to an induction motor with power factor
correction, following installation of an SCR convertor on the same line. When the power capacitor was replaced with a 5th harmonic
trap, the harmonic distortion in the line was dramatically reduced, while power factor correction was maintained.
Conclusion
It is clear that traps can dramatically reduce the harmonic currents circulating in a power distribution system by providing these
currents locally. At the same time the capacitors in the filter provide power factor improvement. The engineer who wishes to improve
power factor at the load, but who has been kept from doing so because of SCR convertors in the plant, now has a solution to his
problem. The inductors in a trap limit instantaneous current through any nearby SCR during commutation, and block the square-wave
pulses that trigger ringing.
Traps can be installed anywhere in the electrical system with no danger of damage to SCR convertors. Harmonic traps can be sized
to almost any system and they will allow use of both the output control capabilities of SCR convertors and the advantages of power
factor improvement provided by capacitors at the load.
The Authors
Michael Z. Lowenstein is manager of research and development and marketing director for Myron Zucker, Inc. He received an AB
degree from Oberlin College and MS and PhD degrees in physical chemistry, physics, and instrumentation from Arizona State
University.
Jim Holley is national sales manager for the same firm. He received a BSME degree from Massachusetts Institute of Technology.
Myron Zucker is founder and Chairman of the Board of Myron Zucker, Inc. He obtained a BSEE degree from Cornell University and
a MSEE degree from Union College. |