Ins CH 3-2
Ins CH 3-2
Ins CH 3-2
ECEg4241
Lecture 3 part 2
Department of Electrical & Computer
Engineering
Debre Berhan University
By Degarege.A
1
Wire and cable size selection for known constant loads
The size should neither be so small so as to have a large internal voltage drop and large heat nor
be too large so as to cost too much.
Voltage drop: caused by the resistance of the cable of the required length must not exceed a
limit given as a standard.
The maximum current: liable to flow in the circuit without undue heating.
Grouping, their spacing distance, underground or in open air as well as insulation factors
Con…..
Individual conductor wires and each conductor of a cable are manufactured in the
following international standard sizes in which the wires are circular and may be solid or
stranded.
Standard
nominal
cross
section 0.5 0.75 1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630
of bare
wire
(mm2)
Purpose Data Electric power cables
3
cable etc
Cable size selection accounting voltage drop calculation
Cable/conductor size selection for dc and single phase wires (Using pure analytical
method (without table reference)
Let consider the two wire circuit (single phase). The voltage drop on the pair of cable is
V V1 – V2 2IR
where R = L/σA ; R in Ω, L in meters, A in mm2 and σ in m/Ω-mm2
For copper σ = 57 m/Ω-mm2 (i.e in unit of meter per ohm mm2 ) and for aluminum σ =
33 m/Ω-mm2
Cont.d
Thus cross sectional area of the wire can be related to the loading must satisfy
A mm 200 xI [ A]xL[m] / CV
2
In lighting designs voltage drop of up to 5% of rated value are allowed [EEPCO regulation 2.5%
max].
Example 1
A 1 kW electric appliance is to be supplied from a 220V from a single phase
source 200m away. Assuming an allowed 2.5% voltage drop, what cross
sectional area of copper wire must be used?
Solution:
Since 2 x 5.8mm2 cable is not available in the standard, the next higher size,
i.e. 2 x 6 mm2 cable will be used.
Example 2
Each conductor of a copper cable of length 200m has a cross sectional area of 10mm2. The cable supplies power to a 220V
single phase motor of 5 kW rating that works on full load at cos ϕ = 0.87 and efficiency of 87%. Determine; the sending side
voltage required, the power loss in the cable, the inductance voltage drop at 50Hz
Solution: Resistance of the conductor of the cable pair, R = L/σA, Rph = 200/ (57 x 10) = 0.35 Ω
The current in each conductor, I = P/ (ɳVLcos ϕL) = 5000/ (0.87 x 220 x 0.87) = 30 A
Vs = Vr + ∆VR = where ∆VR = 2IR cos ϕL = 2 x30 x 0.35 x 0.87 = 18.27 V and Vs = 220 + 18.27 = 238.27 V
Inductance: X = 0.4 Ω/km for overhead lines and X = 0.1 Ω/km for cables
Thus using the above approximate value ; ∆Vx = 2 I X sin ϕL = 2 x 30 x (0.1Ω/km x 0.2 km) x 0.493 = 0.59 V
We see ∆Vx << ∆VR ; Reactive power in the cable would be Q = 2I2X = 2 x 302 x 0.1 H/km x 0.2km = 36 var
Con…
∆V = 2RI cos ϕ, Since, R = L/σA, ∆V = 2 I L cos ϕ/(σA ),
Lost power in %, PL%= (Pl /P) x 100 = [2RI2/ (V I cos ϕ)] x 100 =200 RI/ (V cos ϕ)
efficiency = 0.82 is connected. Voltage drop is 6.6V. Determine the cable size and percentage of lost
power in the cable.
Solution
A(mm2) = 2LP/( ɳσV∆V) = 2 x 50 x 5000/(0.82 x 56 x 220 x 6.6) = 7.4875 mm2,
choose 10 mm2
Or C = (6.6/220) x 100 = 3 %
A (mm2) = 200 LP/ (ɳσ C V2) = 200 x 50 x 5000/ (0.82x56x3x2202) = 7.4875mm2
PL%= 200 LP/( ɳ2σ A V2 cos2 ϕ) = 200 x 50 x 5000/(0.822 x 56 x 6 x 2202 x 0.82) =7.125 %
Or PL%= 200 L I/ (ɳσAVcos ϕ) where I = P/ (ɳVcos ϕ) = 5000/(0.82 x 220 x 0.8) = 34.65A
PL%= 200 x 50 x 34.65/ (0.82 x 56 x 6 x 220 x 0.8) = 7.125%
Cable size calculation with voltage drop in unbranched three phase wires
General ac load (reactive + resistive)
The triple wire power cable of length L is assumed to have only resistance R in each line but negligible
inductance.
Lost power on cable ∆P = PS - Pr
∆P = 1.73 I x Vs cos ϕs - 1.73 I x Vr cos ϕ
∆P = 1.73 I (Vs cos ϕs - Vr cos ϕ) = 3 I2R
∆V = 1.73 I R cos ϕ and with R = L/σA, ∆V = 1.73I L cos ϕ/(σA)
A(mm2) = 1.73 L I cos ϕ/(σ ∆V)
Since I (A) = P/( ɳ1.73 Vcos ϕ)
A (mm2) = 1.73 L [P/( 1.73 Vcos ϕ) ] cos ϕ/(σ ∆V)
A (mm2) = L P /( ɳ σ ∆V V)
L = 50m, ∆V = 5V
14
Maximum continuous loading of insulated conductors and coordination of
protective devices (Copper conductors at 25 Deg Celsius ambient temperature)
15
Example 6
A tannery requires three raw waste transfer pumps of rating 10 HP
where supply to the motors is 380V line. For each motor cos ϕ is
Type of cable selected = 4 core PVC sheathed and the allowable voltage drop = (2.5/100) x 380 = 9.5V
From the above table we calculate for 1mm2: max. continuous current rating 16A; ∆V/A/m = 36 mV
for 4 mm2: rating 35A; ∆V/A/m = 9 mV: ∆V = 14.64 x 50 x 9 x 10-3 = 6.6 V < 9.5V
Solution
According to EEPCOs regulation, for an enclosed cable, ∆V/A/m = 5V/50m/40A = 2.85 mV/A/m
The more cables there are in the group the dissipation properties of the cable are reduced.
If cables were loaded to their ungrouped level, when they are grouped they would overheat.
For instance, for two enclosed multicore cables bunched and clipped direct to a non-metallic surface, Cg =
0.80. This means that for two circuits, only 80 percent of the single circuit current is allowed.
Con…
Table for correction factors Cg to account for grouping
No. of multicore groups, or multiple circuit 1 2 3 4
group
Grouping correction factor, Cg 1 0.8 0.7 0.65
then the new current capacity when grouped with other cables will reduce
to I/z = Cg x Iz
Con…..
If, ambient temperature change is encountered for the bunched cables, the combined
correction factor of grouping and temperature will be C = Cg x Ca.
This means that the current capacities of each of the cables is reduced by a factor of C,
i.e. I/z = C x Iz.
If the cable is run in heat-insulating material, its ability to dissipate heat will be impaired.
A heat insulation correction factor Ci is applied to the length of the cable Combined
effects will result a combined correction factor C = Cg x Ca x Ci and I/z = C x Iz.
Cable size selection accounting protective device & correction factors
The protective device current rating In should be greater than the design
current Ib of the circuit or appliance. That is, In ≥ Ib and its value is
selected from standard tables.
For the protective device to protect the cable against overload, the
minimum cable rating, Iz=In or Iz ≥In.
If any of the factors are not applicable, ignore them or replace with equal to 1
26
Example 9
Single-phase 240V, 36A loads are to be supplied by means of 70°C
thermoplastic PVC twin and earth cables having copper conductors, 25m
in length, in an area having an ambient temperature of 35°C (Ca= 0.94).
The cables are touching and single-layer clipped to a non-metallic surface
(for 3 circuits Cg=0.79). The overcurrent device at the origin of the
installation is a type-B MCB to BS EN 60898. Calculate the minimum
permissible cable size.
Solution
Design current Ib =36A. Nominal rating of the device (from table)
=53.86A
is 10mm2.
Con…..
A(sq.mm) Multicore cable, Max. Permissible
Continuous loading (A)
1 16
1.5 20
2.5 27
4.0 36
6.0 47
10 65
16.0 85
29
Con…
If the volt drop does not exceed 4% of the nominal voltage of the mains
We now need to check that the voltage drop in the 10mm2 cable is within these limits.
Table for the cable gives voltage drop in millivolts per ampere per meter of 4.2.
Design current Ib=36A. Nominal rating of the device In=40A (a rewireable fuse to BS
3036); Cg=0.79, Ca=0.97.
Socket outlets
Up to 8 sockets outlets can be fed by a feeder of cable size not less than 2.5mm2
protected by fuse of 15A, if the socket outlets are to serve less than 30m2 area, but not
kitchen.
If the area is above 30 m2 and cable is 2.5mm2, the number of socket outlets connected
to a feeder has to be 4 or less with 15A protection fuse.
But, if the cable size is increased to 4 mm2 with a protection fuse of 25A, the number
of socket outlets can be up to 8 for area more than 30m2.
Con….
Maximum number of socket outlets on one feeder when the
load is not known exactly is limited to 12.
If the power of lighting point is not known exactly, a 100W can be
assumed per lamp holder for the feeder total current calculation.
Any appliance with power rating of more than 1500W has to be fed by a
dedicated cable with its own control and protection
Electric Motor Installation
Electric motors can be of continuous duty, intermittent duty or short time duty.
Six steps can be used for the installation of electrical motors
Determining the motor full load current.
Determine the fuse size (dual element) to be used as motor branch-circuit short circuit and
ground fault protection.
Determine the requirement for the motor control circuit over current protection
Example 11
It is desired to design and installs a squirrel cage induction electric motor fed from a
380V bus-bar. The electric motor nameplate values are Pn= 2.2 kW, nn=2850 rpm,
Vn=380V, pf=0.8, ɳ=0.8. The motor is for continuous duty operation.
Solution:
Step 1: The full load current of the motor can be obtained from the following equation. If
the efficiency is to be considered the motor current would be slightly higher.
Pn 2200
Ib 5.22 A
3VL * * pf 1.73*380*0.8*0.8
Step 2: Assuming no correction factors for ambient and group, etc. the minimum ampacity of
conductor to be used according to standards is 125% of the motor full load.
The corresponding size for particular cable to be used checked from table.
Table I: Single core PVC insulated copper conductor with sheath, current carrying capacity
and voltage drop.
41
Solution
Circuit Power without DF Power with DF
Lighting 4 x 220 x 10 = 8800W 0.7 x 8800 = 6160W
Socket outlet 3 x 220 x 16 = 10560W 0.2 x 10560 = 2112W
Water heater 220 x 16 = 3520W 0.2 x 3520 = 704W
Space heater 220 x 25 = 5500W 0.2 x 5500 = 1100W
28380 Pmax 10076W
43
Assignment
44
Thank you