Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
0% found this document useful (0 votes)
26 views34 pages

108 User

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 34

DKG-108 User Manual V-2.0 (12.07.

2016)

DKG-108 POWER
FACTOR CONTROLLER
8 BANKS, HARMONIC
DISTORTION DISPLAY

FEATURES DESCRIPTION
Small size DFC-0108 is a high technology controller
Cost effective and high performance allowing the power factor of the installation to
True RMS AC measurements, high accuracy be stabilized to the requested value by
4096 samples/sec measurement rate switching capacitor banks through
Easy commissioningthrough automatic setup contactors. The unit allows also the
visualization of various AC parameters like a
Automatic CT reverse polarity correction
network analyzer.
Automatic detection of faulty banks
Electronic/mechanical power counter selection The unit makes harmonic analysis up to the
Per-phase regulation capability 31th component. The THD values of all
voltages and currents are available.
Supports both single-phase and tri-phase banks
Connection/disconnection of all banks at once Stepping algorithms are selectable between
Adjustable delay timers various types. Thanks to the automatic setup
Dynamic update of capacitor ratings function, the commissioning and
programming are made easy.
Equal aging of contactors
Per phase and total V-A-kW-kVAr-cos display The unit fits into a standard 96x96mm panel
THD display of all V-I parameters (31 harmonic) opening.
fVT ratio for MV applications
kW and kVAr tick output possibility
Front panel programmable
Low panel depth, easy installation
Wide temperature range
Sealed front panel (IP54)
Plug-in connection system for easy replacement

-1-
DKG-108 User Manual V-2.0 (12.07.2016)

SAFETY NOTICE
Failure to follow below instructions will result in
death or serious injury

 Electrical equipment should be installed only by qualified


specialist. No responsibility is assured by the
manufacturer or any of its subsidiaries for any
consequences resulting from the non-compliance to
these instructions.
 Check the unit for cracks and damages due to
transportation. Do not install damaged equipment.

 Do not open the unit. There is no serviceable parts inside.


 Fuses must be connected to the phase voltage inputs, in
close proximity of the unit.
 Fuses must be of fast type (FF) with a maximum rating of
6A.
 Disconnect all power before working on equipment.
 When the unit is connected to the network do not touch
terminals.
 Short circuit terminals of unused current transformers.
 Any electrical parameter applied to the device must be in
the range specified in the user manual.
 Do not try to clean the device with solvent or the like.
Only clean with a dump cloth.
 Verify correct terminal connections before applying
power.
 Only for front panel mounting.

Current Transformers must be used for current


measurement.
No direct connection allowed.

-2-
DKG-108 User Manual V-2.0 (12.07.2016)

TABLE OF CONTENTS

Section
1. INSTALLATION
1.1. FRONT / REAR PANELS
1.2. MECHANICAL INSTALLATION
1.3. ELECTRICAL INSTALLATION
1.4. CONNECTION DIAGRAM
2. AUTOMATIC SETUP
3. PUSHBUTTON FUNCTIONS
4. DISPLAYS
4.1. DISPLAYS IN AUTO AND MANUAL MODES
4.2. TEST MODE, MANUAL STEP CONTROL
5. STEPPING PROGRAMS
5.1. COMPARAISON OF LEGACY AND OPTIMAL PROGRAMS
6. ALARMS
7. PROGRAMMING
7.1. ENTERING EXITING PROGRAMMING
7.2. LAMP TEST
7.3. MODIFYING PROGRAM PARAMETERS
7.4. PROGRAM PARAMETER LIST
8. TECHNICAL SPECIFICATIONS

-3-
DKG-108 User Manual V-2.0 (12.07.2016)

1. INSTALLATION

Before installation:
 Read the user manual carefully, determine the correct connection diagram.
 Remove all connectors and mounting brackets from the unit, then pass the unit through
the mounting opening.
 Put mounting brackets and tighten. Do not tighten too much, this can brake the
enclosure.Self mating brackets do not require tightening.
 Make electrical connections with plugs removed from sockets, then place plugs to their
sockets.
 Make sure that relay outputs are not overloaded. If necessary use extra contactors.

Below conditions may damage the device:


 Incorrect connections.
 Incorrect power supply voltage.
 Voltage at measuring terminals beyond specified range.
 Current at measuring terminals beyond specified range.
 Overload or short circuit at relay outputs

Current Transformers must be used for current


measurement.
No direct connection allowed.

Below conditions may cause abnormal operation:


 Power supply voltage below minimum acceptable level.
 Power supply frequency out of specified limits
 Current transformers not matching related phases.
 Current transformer polarity incorrect. (if automatic correction is not applied).
 Inadequate on-delay setting
 Inadequate off-delay setting.

-4-
DKG-108 User Manual V-2.0 (12.07.2016)

1.1 FRONT / REAR PANELS

1.2 MECHANICAL INSTALLATION

Panel Cutout Required Panel Depth

-5-
DKG-108 User Manual V-2.0 (12.07.2016)

1.3 ELECTRICAL INSTALLATION

Do not install the unit close to high electromagnetic


noise emitting devices like contactors, high current
busbars, switchmode power supplies and the like.

Although the unit is protected against electromagnetic disturbance, excessive disturbance


can affect the operation, measurement precision and data communication quality.

 ALWAYS remove plug connectors when inserting wires with a screwdriver.

 Fuses must be connected to phase voltage inputs, in close proximity of the unit.

 Fuses must be of fast type (FF) with a maximum rating of 6A.

 Use cables of appropriate temperature range.

 Use adequate cable section, at least 0.75mm2 (AWG18).

 For current transformer inputs, use at least 1.5mm2 section (AWG15) cable.

 The current transformer cable length should not exceed 1.5 meters. If longer
cable is used, increase the cable section proportionally.

 Follow national rules for electrical installation.

 Current transformers must have 5A output.

Current Transformers must be used for current


measurement.
No direct connection allowed.

Make sure that relay outputs are not overloaded.


If necessary use extra contactors.

-6-
DKG-108 User Manual V-2.0 (12.07.2016)

1.4 CONNECTION DIAGRAM

-7-
DKG-108 User Manual V-2.0 (12.07.2016)

2. AUTOMATIC SETUP

In automatic setup mode, the unit :


-automatically detects and corrects reverse connected current transformers.
-automatically measures and memorizes capacitor bank ratings.

For a successful auto setup, voltage connections


must be 3 phased.
Otherwise the unit will give ALARM_01 and will not
perform automatic setup.

For a successful auto setup, STEP_1 capacitors must


be 3 phased.
Otherwise the unit cannot detect connection errors,
gives ALARM_02 and will not perform automatic
setup.

For a successful auto setup, current transformers


must be connected to correct CT inputs.
The connection polarity is not important.
Otherwise the unit will give ALARM_03 and will not
perform automatic setup.

It is preferable that there should be no other load on


the capacitor panel. However with constant or slow
changing loads the unit is able to perform auto setup.
If there are fast changing loads, the unit may be
unable to correct CT polarity errors or may read
incorrect bank capacitor ratings. In such cases, auto
setup should be repeated and capacitor ratings
should be checked/corrected through
PROGRAMMING menu.

-8-
DKG-108 User Manual V-2.0 (12.07.2016)

STEP BY STEP AUTO SETUP


PUSHBUTTON OPERATION DISPLAY
In order to enter the auto setup mode, power-
up the unit with MENU button pressed and
hold the button pressed for 10 seconds. The
display will show ctrFand the unit will ask the
current transformer primary rating.
Press again the MENU button. The display will
show the CT primary rating.

Adjust required CT primary rating with arrow


buttons.
For fast increase/decrease please hold the
button pressed.
Press again the MENU button. The display will
show MtErand the unit will ask the power
meter type.
Press again the MENU button. The display will
show the power meter type.

Adjust required power meter type with arrow


buttons.
0  analog power meter
1  digital power meter
Press again the MENU button. The display will
show LErnand the unit will ask to enter the
quick commissioning mode.
Press again the MENU button. The display will
show 0.

Set the parameter to 1 with arrow buttons.

Press again the MENU button. The display will


show the total kVArvalue.
The unit will check CT connections, correct if
necessary, then activate all banks (one by one)
in order to determine capacitor ratings.
When auto setup is finished successfully the
unit will revert to normal operation.

-9-
DKG-108 User Manual V-2.0 (12.07.2016)

3. PUSHBUTTON FUNCTIONS

Access to programming and measurement displays is achieved through 3 pushbuttons on


the front panel.

PUSHBUTTON FUNCTION

In AUTO mode, acknowledges the displayed alarm.


If the same alarm occurs again, it will not appear on the display.

HELD PRESSED DURING 5 SEC:


Resets all alarms and the alarm led.
Any new coming alarm will appear on the display.

HELD PRESSED DURING 10 SEC AT POWER-ON:


The unit enters automatic setup mode.

Switch to upper display or previous parameter


or increase related value (programming mode)

Switch to lower display or next parameter


or decrease related value (programming mode)

HELD PRESSED DURING 5 SEC:


Switches between AUTO and MANUAL modes.In MANUAL mode
the stepping is disabled. From the MANUAL mode TEST mode
can be selected in order to test each step manually.
HELD PRESSED DURING 5 SEC IN MANUAL MODE:
Switches between MANUAL and TEST modes. In TEST mode, all
steps may be turned on and off manually. For more detailed
information please check chapter 4.2.

HELD PRESSED TOGETHER DURING 5 SEC:


Enters or exits programming mode.

NO PUSHBUTTON PRESSED DURING 15 MINUTES:


Returns to the programmed main display screen.

-10-
DKG-108 User Manual V-2.0 (12.07.2016)

4. DISPLAYS

Display parameter leds at right describe C+ led shown excessive regulation.


the measurement on the display. OK led indicates a balanced system.

Phase indicator leds at left describe the Current display: If the current
phase related to the display: transformer (CT) ratio is lower than
 2 phase leds are on for Ph-Ph values. 200/5A, currents are displayed with 0.1A
 All 3 leds are on for totalcosø, kW, precision. Otherwise they are displayed
with 1A precision.
kVAr.
 All leds are off for frequency. Voltage display:If the voltage
 For THD values, THD led,V or A led transformer (VT) ratio is lower than
and related phase ledsare on 50.0/1, voltages are displayed in volts.
together. Otherwise they are displayed with in kV
with 0.01kV precision.
Alarm led turns on if any fault condition
occurs. If the alarm list is displayed, this kW, kVA, kVArdisplay: If the
led flashes. VTxCTproduct is lower than 1000, then
values are shown with 0.1k precision.
Step leds turn on if the related capacitor Otherwise they are shown with 1k
bank is activated. If the capacitor bank is precision.
faulty, the led flashes once every 5
seconds. When the step is about to Capacitor bank rating display: The
become active or inactive the led flashes display shows alternatively CAPxand the
differently. rating in kVAr. If the capacitor is single
phase, the related phase led turns on.
C- led shows insufficient regulation. Otherwise all phase leds are on.
-11-
DKG-108 User Manual V-2.0 (12.07.2016)

4.1 DISPLAYS IN AUTO AND MANUAL MODES

Holding the pushbutton pressed for 5 seconds


switches betweenAUTO and MANUAL modes.

If AUTO mode is selected with a step output activated


in MANUAL mode, then the AUTO position starts
with this step activated. The step then may be
deactivated following automatic stepping program.

In AUTOmode, the AUTO ledis on. If the generator input is active or if there is any alarm
preventing automatic operation, then the AUTO led is flashing. In MANUAL mode, the
AUTO led is off.

As default the unit displays the total cosø.

With pushbuttons various measured values are scrolled.

If no button is pressed during 15 minutes, the display reverts back to total cosø display

4.2 TEST MODE, MANUAL STEP CONTROL

Holding the pushbutton pressed for 5 seconds


switches betweenTEST and MANUAL modes.

In TEST mode, if no button is pressed during 1


minute the unit will automatically return back to
MANUAL mode.

InTESTmode only the total kVAr value is displayed.

WhenTEST mode is selected then the step-1 indicator led will flash. Pressing the

pushbutton will activate this step.Pressing the pushbutton will deactivate this step.

Pressing the MENUpushbutton will select the next step and the related step led will

flash.Using pushbuttons the step may be activated or deactivated. Using the


-12-
DKG-108 User Manual V-2.0 (12.07.2016)
MENUpushbutton all steps may be scrolled manually.

5. STEPPING PROGRAMS

The unit is able to apply various stepping programs.

The stepping program is selected through “ProG” parameter.

It is advised to use the OPTIMAL program (10).


Fastest and the most precise regulation is achieved
with this program.

ProG BANK CONFIGURATION and STEPPING


1 1.1.1.1.1.1.1.1: standardconfiguration, legacy program (a single step is
activated or deactivated at each period).
2 1.2.4.4.4.4.4.4 : standard configuration, legacy program (a single step is
activated or deactivated at each period).
3 1.2.3.3.3.3.3.3 : standard configuration, legacy program (a single step is
activated or deactivated at each period).
4 1.1.2.3.3.3.3.3 : standard configuration, legacy program (a single step is
activated or deactivated at each period).
5 1.1.2.4.4.4.4.4 : standard configuration, legacy program (a single step is
activated or deactivated at each period).
6 1.2.2.4.4.4.4.4 : standard configuration, legacy program (a single step is
activated or deactivated at each period).
7 1.2.3.4.4.4.4.4 : standard configuration, legacy program (a single step is
activated or deactivated at each period).

8 1.2.4.8.8.8.8.8 : standard configuration, legacy program (a single step is


activated or deactivated at each period).
9 Free configuration(programmed or auto-configured),legacy program (a single
step is activated or deactivated at each period).
10 Free configuration (programmed or auto-configured), optimal program (all
necessary steps are activated/deactivated at once).

-13-
DKG-108 User Manual V-2.0 (12.07.2016)

5.1 COMPARAISON OF LEGACY AND OPTIMAL PROGRAMS


Step configuration: 1.2.3.4.4.4.4.4
Step type: 3 Phase
Basic step rating: 1kVAr
Target CosØ= 1.000
Inductive reactive load: 20kVar

LEGACY PROGRAM
The unit has reached the target cosø in
STEPS
10 periods, by operating 1 step at each
Request 1 2 3 4 5 6 7 8 kVAr period.
During this time the cosøhad been
1 ↑ 1 1 different from the target and the
2 ↑ 1 2 3 reactive power counter has recorded
reactive power.
3 ↑ 1 2 3 6 The unit has made 10
contactoroperations.
4 ↑ 1 2 3 4 10
The unit has reached the target cosø
5 ↑ 1 2 3 4 4 14 with 6 banks in service.
6 ↑ 1 2 3 4 4 4 18
7 ↑ 1 2 3 4 4 4 4 22
8 ↓ 2 3 4 4 4 4 21
9 ↓ 3 4 4 4 4 19
10 ↑ 1 3 4 4 4 4 20

OPTIMAL PROGRAM
The unit has reached the target cosø in
STEPS
1 period. As the target cosøis reached
Request 1 2 3 4 5 6 7 8 kVAR faster, the reactive power counter has
recorded less power.
1 ↑ 4 4 4 4 4 20 The unit has made 5
contactoroperations. Thus longer
contactor life is achieved.
The unit has reached the target cosø
with 5 banks in service. Thus capacitor
aging is kept at minimum.

-14-
DKG-108 User Manual V-2.0 (12.07.2016)

6. ALARMS

The unit constantly monitors abnormal situations occurring in the system.


Every monitored parameter has programmable alarm limits and delay timer. Alarms may be
of latching or unlatching types. The automatic operation may be programmed to be aborted
or continued. For more details please consider the PROGRAMMING section of this
manual.
When any alarm occurs the ALARM led turns on and the alarm code appears on the
display. Following programming, the auxiliary relay output may be activated. The automatic
operation may be aborted or continued, based on programming.

AL-01: NETWORK NOT 3 PHASED AL-11: EXCESS CAPACITIVE kVAr


Occurs if automatic setup is attempted Occurs if the total reactive power is
with non 3 phased network. capacitive and above rCAP limit during r-
AL-02:FIRST BANK NOT 3 PHASED dU period. (Welded contactors)
Occurs if automatic setup is attempted AL-12:INDUCTIVE CosØ
with non 3 phased capacitors at the fist Occurs if the total cosø is inductive and
bank. below cInd limit during C-dU period.
AL-03:FAULTY CT ORDER AL-13:CAPACITIVE CosØ
Occurs if automatic setup is attempted Occurs if the total cosø is capacitive and
with CTs not connected to related phases. below cCAP limit during C-dU period.
AL-04:HIGH VOLTAGE (Welded contactors)
Occurs if at least 1 phase voltage is AL-14: EXCESS CURRENT
above u-Hi limit during u-dUperiod. Occurs if at least 1 phase current is above
AL-05: LOW VOLTAGE CrHi limit during CrdU period.
Occurs if at least 1 phase voltage is below AL-15:EXCESS THD(V)
u-Lo limit during u-dU period. Occurs if at least 1 phase voltage THD is
AL-06: HIGH FREQUENCY above thdu limit during uhdU period.
Occurs if the frequency is above F-Hi limit AL-16:EXCESS THD(I)
during F-dU period. Occurs if at least 1 phase current THD is
AL-07: LOW FREQUENCY above thdi limit during chdU period.
Occurs if the frequency is belowF-Lo limit rAt1...rAt8 CAPACITORVALUE LOSS
during F-dU period. Occurs when the measured step rating is
AL-08:EXCESS kW below rtio % compared to its nominal
Occurs if the total active power is above value. In order to enable this alarm dYnC
A-Hi limit during A-dU period. parameter must be 1.
AL-09: LOW kW AL-18:PHASE ORDER FAULT
Occurs if the total active power is below Occurs if the voltage phase order is faulty.
A-Lo limit during A-dU period. Err1...Err8: CAPACITOR DEFECTIVE
AL-10:EXCESS INDUCTIVE kVAr Occurs when the measured capacitor
Occurs if the total reactive power is rating is below 20% of its nominal value.
inductive and above rInd limit during r-dU
period.

-15-
DKG-108 User Manual V-2.0 (12.07.2016)

7. PROGRAMMING

7.1 ENTERING AND EXITING PROGRAMMING


In order to provide the maximum flexibility to the user, the unit features many
programmable parameters.
The parameters are recorded in a non-volatile memory and are not affected by power
supply failures.
The entry to the programming menu is password protected. The factory set password
value is “1” and can be modified with the program parameter “PASS”.
Additionally the password “3282” is always valid and cannot be modified.

PUSHBUTTON OPERATION DISPLAY


In order to enter PROGRAM mode please
hold pressed arrow buttons for 5 seconds.
The display will showUser.

When USEr appears please press MENU


pushbutton. The password entry display will
come.

Use the arrow buttons to enter the password.


The factory set password value is “1”
In order to fast increase/decrease please
hold arrow pushbuttons pressed.
Press MENU pushbutton. The first parameter
name(LErn) will come to display.

PUSHBUTTON OPERATION DISPLAY


In order to leave the program mode please
hold pressed both arrow buttons during 5
seconds.

If no pushbutton is pressed during 3 minutes, the unit


will automatically terminate the PROGRAM mode.

-16-
DKG-108 User Manual V-2.0 (12.07.2016)

7.2 LAMP TEST

The unit makes a LAMP TEST when exiting the


PROGRAM mode. During lamp test all lights turn on.
By pressing the MENU pushbutton, normal
operation is resumed.

If no pushbutton is pressed for 3 minutes the unit will


automatically terminate the PROGRAM mode
without lamp test.

7.3 MODIFYING PROGRAM PARAMETERS

PUSHBUTTON OPERATION DISPLAY


When parameter names are displayed, select
required parameter with arrow buttons.

When the required parameter is found press


MENU pushbutton. The parameter value will
be displayed.

Adjust required value with arrow buttons.


In order to fast increase/decrease please
hold arrow pushbuttons pressed.
Press MENU pushbutton. The parameter
value will be recorded and the parameter
name will be displayed again.

-17-
DKG-108 User Manual V-2.0 (12.07.2016)

7.4 PROGRAM PARAMETER LIST

DISPLAY DESCRIPTION MIN STD MAX


PASSWORD ENTRY 0 1 9999
The user password is required. The
password is determined by the program
parameter “PASS”. The factory set value
is “1”.
The password “3282” is always valid.
AUTOMATIC SETUP 0 0 1
When this parameter is set to 1, and if
the unit is in MANUAL mode, steps are
activated consecutively and bank ratings
are measured.
RESETTING DYNAMIC STEP VALUES 0 0 1
AND FAULT COUNTERS
When this parameter is set to 1, fault
counters and dynamic bank values are
reset.
RESETTING STEP COUNTERS 0 0 1
When this parameter is set to 1, step
activation and operation counters are
reset.
RETURN TO FACTORY SETTINGS 0 0 1
When this parameter is set to 1, all
program parameters return back to
factory set values.
TARGETcosø 0.800 0.999 0.800
This is the target cosøvalue that the unit cap. ind. ind.
is trying to reach in AUTO mode. The
value can be adjusted between 0.800
capacitive and 0.800 inductive.
Capacitive values are shown in c.999
format. Inductive values are shown in
0.999 format.
ADJUSTING THE NUMBER OF STEPS 1 8 8
The number of used steps can be
adjusted between 1 and 8. Unused steps
are not taken into account in the
stepping program.

-18-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


STEPPING PROGRAM SELECTION 1 10 10

This parameter selects


betweenLEGACY and OPTIMAL
stepping programs.
The unit is advised to be operated under
OPTIMAL program.
Program details are emphasized in
chapter 5.

STEP TURN-ON DELAY 1 sec 20 sec 2000


sec
When a new capacitor combination is
required, the unit continues
measurements during this timer and the
new combination found at the end of this
timer is directed to step outputs.
STEP TURN-OFF DELAY 1 sec 30 sec 2000
sec
When a new capacitor combination is
set to step outputs, stepping is disabled
during this period.
DISCHARGE TIMER 3 sec 60 sec 2000
Common discharge timer for all steps. A sec
deactivated bank cannot be reactivated
before this timer has expired.
CAPACITOR TYPE (CON1...CON8) 0 0 3

Selects capacitor connection type.


If “Prog” parameter is selected between
1 and 8, these parameters have no
effect and all banks are supposed to be
3 phased.
0  3 phase capacitor
1  single phase capacitor at phase L1
2 single phase capacitor at phase L2
3 single phase capacitor at phase L3

-19-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


CAPACITOR RATING (CAP1...CAP8) 0.0 1.0 999.9
kVAr kVAR kVAr
This is thecapacitor bank rating,
adjusted between 0.1 and 999.9 kVAr.
If the parameter“Prog” is set to a value
between 1 and 8, then only CAP1
parameter is used. Other CAPx
parameters are don’t care.

CURRENT TRANSFORMER RATIO 5 Amp 500 5000


The CT ratio is the primary rating of both Amp Amp
phase CTs, adjusted in 5A steps.
The CT secondary rating must be 5A.
VOLTAGE TRANSFORMER RATIO 0.1 1.0 200.0
The voltage transformer ratio is adjusted
between 0.1 and 200.0 in 0.1 steps.

SELECTION OF POWER METER TYPE 0 1 1

For the correct operation of the


controller, this parameter must be set
properly.
0  analog power meter (the sum of all
phases are regulated)
1  digital power meter (each phase is
individually regulated)
DYNAMIC MEASUREMENT OF 0 0 1
CAPACITOR kVArRATINGS
When this parameter is set to 1,
capacitor kVAr ratings are continuously
measured and modified in small
amounts.
DEFAULT DISPLAY SCREEN 0 14 32

If no pushbutton is pressed during 15


minutes, the display switches
automatically to this selection. The
factory set value is the total cosø
display.
0 L1 voltage
1 L2 voltage
2 L3 voltage
3  Frequency display
The order is the same as the
measurements display.

-20-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


REGULATION LIMIT FOR C-/C+ LEDS 1% 5% 20 %

This is the difference from the target


cosø for C-,OK,C+ leds to turn on.

NOMINAL VOLTAGE 70 V 220V 9999 V

This is the phase-to-neutral voltage for


which bank ratings are defined.

NOMINAL FREQUENCY 30 Hz 50 Hz 400 Hz

This is the network frequency for which


bank ratings are valid.

NUMBER OF FIXED STEPS 0 0 4

This number of steps, starting from the


step-1 will be always active.

TURN_ON ALERT TIMER 0 sec 3 sec 2000


After a new step combination has been sec
determined, the leds of steps to be
modified start to flash and only after
expiration of this timeout the steps are
activated.
During this timer no new step
combination is calculated.
TURN_OFF ALERT TIMER 0 sec 1 sec 2000
After a new step combination has been sec
determined, the leds of steps to be
modified start to flash and only after
expiration of this timeout the steps are
deactivated.
During this timer no new step
combination is calculated.

-21-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


AUTOMATIC TESTING OF 3 hour 10 200
DEFECTIVE BANKS hour hour
A defective bank is not used in
regulation. But if the value of this timer is
not zero, then defective banks are
activated regularly with this period and
tested again.
If the bank is no more defective then the
alarm will disappear and the bank will be
used in regulation. A bank value below
20% of its nominal value is considered
as defective. A bank value above 80% of
its nominal value is considered as
operational.
In order to determine the capacitor’s
defective/healthy condition, this test is
applied 3 times. If the same result is
obtained at each test then the new
capacitor condition is accepted.

PHASE ORDER CHECK 0 0 1

0 Phase order is not monitored


1 Phase order is monitored

SINGLE PHASE OPERATION 0 0 1

0 3 phased connection
1 Single phase connection

-22-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


HIGH VOLTAGE ALARM LIMIT 0V 0V 9999 V
Any phase voltage above this limit will
generate a high voltage alarm.
If this limit is set to zero then the alarm is
not monitored.
LOW VOLTAGE ALARM LIMIT 0V 0V 9999 V
Any phase voltage below this limit will
generate a low voltage alarm.
If this limit is set to zero then low voltage
alarm is not monitored.
VOLTAGE ALARM DELAY 0 sec 30 sec 200
For any voltage alarm, the limit must be sec
overridden during this period.

VOLTAGE ALARM FUNCTION 0 0 3


0 In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
1 In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
2 In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3 In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.

-23-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


HIGH FREQUENCY ALARM LIMIT 0 Hz 0 Hz 400 Hz
If the frequency is above this limit, it will
generate a high frequency alarm.
If this limit is set to zero then the alarm is
not monitored.
LOW FREQUENCY ALARM LIMIT 0 Hz 0 Hz 400 Hz

If the frequency is below this limit, it will


generate a low frequency alarm.
If this limit is set to zero then the alarm is
not monitored.
FREQUENCY ALARM DELAY 0 sec 30 sec 200
sec
For any frequency alarm, the limit must
be overridden during this period.

FREQUENCY ALARM FUNCTION 0 0 3

0  In the occurrence of alarm, stepping


continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
1  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
2  In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.

-24-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


ACTIVE POWER HIGH LIMIT 0 kW 0kW 6500
If the active power is above this limit, it kW
will generate an excess kW alarm.
If this limit is set to zero then the alarm is
not monitored.
ACTIVE POWER LOW LIMIT 0 kW 0 kW 6500
If the active power is below this limit, it kW
will generate a low kW alarm.
If this limit is set to zero then the alarm is
not monitored.
ACTIVE POWER ALARM DELAY 0 sec 30 sec 200
For any kW alarm, the limit must be sec
overridden during this period.

ACTIVE POWER ALARM FUNCTION 0 0 3

0  In the occurrence of alarm, stepping


continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
1  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
2  In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3 In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.

-25-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


CAPACITIVE REACTIVE POWER 0 0 6500
HIGH LIMIT kVAR kVAR kVAR
If the reactive power is capacitive and
above this limit, it will generate an
excess kVAr capacitive alarm.
If this limit is set to zero then the alarm is
not monitored.

INDUCTIVE REACTIVE POWER HIGH 0 0 6500


LIMIT kVAR kVAR kVAR
If the reactive power is inductive and
above this limit, it will generate an
excess kVAr inductive alarm.
If this limit is set to zero then the alarm is
not monitored.
REACTIVE POWER ALARM DELAY 0 sec 30 sec 200
For any kVAr alarm, the limit must be sec
overridden during this period.

REACTIVE POWER ALARM 0 0 3


FUNCTION
0  In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
1  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
2  In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3 In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.

-26-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


CAPACITIVE POWER FACTOR 0.000 0.000 0.999
(CosØ) LOW LIMIT
If the power factor is capacitive and
below this limit, it will generate a low
power factor capacitive alarm.
If this limit is set to 0.000 then the alarm
is not monitored.

INDUCTIVE POWER FACTOR (CosØ) 0.000 0.000 0.999


LOW LIMIT
If the power factor is inductive and below
this limit, it will generate a low power
factor inductive alarm.
If this limit is set to 0.000 then the alarm
is not monitored.
LOW POWER FACTOR ALARM 0 sec 30 sec 200
DELAY sec
For any low power factor alarm, the limit
must be overridden during this period.
LOW POWER FACTOR ALARM 0 0 3
FUNCTION
0  In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
1  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
2  In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.

-27-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


OVERCURRENT ALARM LIMIT 0A 0A 5000 A

Any phase current above this limit will


generate an overcurrent alarm.
If this limit is set to zero then the alarm is
not monitored.
OVERCURRENT ALARM DELAY 0 sec 30 sec 200
sec
For an overcurrent alarm, the limit must
be overridden during this period.

OVERCURRENT ALARM FUNCTION 0 0 3

0  In the occurrence of alarm, stepping


continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
1  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
2  In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.

-28-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


THD(V) HIGH ALARM LIMIT 0% 0% 99%

Any phase voltage THD above this limit


will generate a high THD(V) alarm.
If this limit is set to zero then the alarm is
not monitored.
THD(V) ALARM DELAY 0 sec 30 sec 200
sec
For a high THD(V) alarm, the limit must
be overridden during this period.

THD(V) ALARM FUNCTION 0 0 3

0  In the occurrence of alarm, stepping


continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
1  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
2  In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.

-29-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


THD(I) HIGH ALARM LIMIT 0% 0% 99 %

Any phase current THD above this limit


will generate a high THD(I) alarm.
If this limit is set to zero then the alarm is
not monitored.
THD(I) ALARM DELAY 0 sec 30 sec 200
sec
For a high THD(I) alarm, the limit must
be overridden during this period.

THD(I) ALARM FUNCTION 0 0 3

0  In the occurrence of alarm, stepping


continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
1  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
2  In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.

-30-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


CAPACITOR VALUE LOSS ALARM 0% 0% 80 %
LIMIT
If the measured capacitor bank rating is
less than the percent defined by this
parameter, compared to its nominal
value, then a capacitor value loss alarm
is given.
The low capacitor value must be
measured at least 3 times below the
limit.
If this limit is set to zero then the alarm is
not monitored.

CAPACITOR VALUE LOSS ALARM 0 sec 30 sec 200


DELAY sec

For a value loss alarm, the limit must be


overridden during this period.
CAPACITOR VALUE LOSS ALARM 0 0 3
FUNCTION
0  In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
1  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will disappear after
the delay defined by the parameter
“MutE”.
2  In the occurrence of alarm, stepping
continues. When the alarm source is
removed, the alarm will persist and can
be only reset manually.
3  In the occurrence of alarm, stepping
stops. When the alarm source is
removed, the alarm will persist and can
be only reset manually.

-31-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


RELAY OUTPUT FUNCTION 0 21 21

0: Regulation OK
1: Regulation not OK
2: Regulation failure
3: kWh tick
4: kVArh tick
5: High voltage alarm
6: Low voltage alarm
7: High frequency alarm
8: Low frequency alarm
9:Excess kW alarm
10: Low kW alarm
11: kVAr overregulation (capacitive load)
12: kVArunder regulation(inductive load)
13: cos overregulation (capacitive load)
14: cos under regulation(inductive load)
15: Overcurrent alarm
16: High THD-V alarm
17: High THD-I alarm
18: Capacitor value loss alarm
19: Phase order alarm
20: Defective capacitor alarm
21: Any alarm

-32-
DKG-108 User Manual V-2.0 (12.07.2016)

DISPLAY DESCRIPTION MIN STD MAX


PROGRAMMING PASSWORD 1 1 9999

The program mode entry password may


be selected between 1 and 9999.

kW-kVArPULSEFUNCTION 0 0 2

The unit is able to give a 100ms pulse


for each kWh or kVArh. This parameter
selects the condition for this pulse.
0 Pulse is always given
1  Pulse is given when the generator is
off
2 Pulse is given when the generator is
on.
ALARM RESET DELAY 0 sec 30 sec 200
sec
When the alarm source is removed, any
non-latching alarm will disappear after
the delay defined by this parameter.
FIRMWARE VERSION / MANUAL 0 0 9999
CALIBRATION
Displays the unit’s firmware version.
If this parameter value is set to 3282,
then the unit enters manual calibration
mode where all voltage and current
inputs can be manually calibrated.

-33-
DKG-108 User Manual V-2.0 (12.07.2016)

8. TECHNICAL SPECIFICATIONS

Power Supply Input: 170 - 275VAC, 50 - 60Hz nominal (± 10%) between L1-N
Measurement Input Range:
Voltage inputs: 10 - 300 V AC (L-N)
20 - 520 V AC (L-L)
Current inputs: 0.2 – 5.5 A AC
Frequency: 30 - 100 Hz
Accuracy:
Voltage: 0.5%+1digit
Current: 0.5%+1 digit
Frequency: 0.5%+1 digit
Power(kW,kVAr): 1.0%+2digit
Power factor: 0.5%+1 digit
Measurement Range:
CT range: 5/5A to 5000/5A
VT range: 0.1/1 to 200.0/1
kW range: 0.1 kW to 6.5 MW
Power Consumption: < 4 VA
Voltage burden: < 0.1VA per phase
Current burden: < 1VA per phase
Relay Outputs: 5A @ 250VAC
Operating Temperature: -20°C to +70°C (-4 to +158F).
Maximum humidity: 95% non-condensing.
Degree of Protection: IP 54 (Front Panel), IP 30 (Back panel)
Enclosure: Non-flammable, ROHS compliant, ABS/PC (UL94-V0)
Installation: Flush mounting with rear retaining brackets
Dimensions: 102x102x53mm (WxHxD)
Panel Cutout: 92x92mm
Weight: 370 gr

EU Directives Conformity: Norms of reference:


2006/95/EC (low voltage) EN 61010 (safety requirements)
2004/108/EC (EMC) EN 61326 (EMC requirements)

PACKAGING INFORMATION
Pieces per Package: 12 pieces
Package Size: 280 x 170 x 215mm (LxWxH)
Package Weight: 4.6 kg

DATAKOM Electronics Ltd.


Tel: +90-216-466 84 60 Fax: +90-216-364 65 65 e-mail: datakom@datakom.com.tr http: www.datakom.com.tr

-34-

You might also like