405_USER
405_USER
405_USER
DKM-405 NETWORK
ANALYSER
WITH TOTAL HARMONIC
DISTORTION DISPLAY
INTRODUCTION FEATURES
The DKM-405 is a low cost precision True RMS measurements
instrument designed to display various AC Total harmonic distortion display
parameters in a 3-phase distribution panel.
Max demand display
The standard unit is designed for 230/400V
Configurable relay output
network. A different version is available for
120/208V systems. Energy pulse output capability
The harmonic analysis is available for up to Optically isolated, configurable digital input
31 harmonics. THD values of both voltage Active-reactive power counters
and current inputs are available. Hour counter
The optional digital input accepts both AC Voltage transformer ratio for MV applications
and DC signals and has programmable Front panel programming
functions.
Reduced panel depth
The optional relay output is programmable.
Relay function is selected through a list. Wide operating temperature range
Sealed front panel (IP54)
The unit fits into a standard 92x92mm panel
opening. Plug-in connection system
-1-
DKM-405 User Manual V-1.5
SAFETY NOTICE
Failure to follow below instructions will
result in death or serious injury
-2-
DKM-405 User Manual V-1.5
TABLE OF CONTENTS
Section
1. INSTALLATION
1.1. FRONT / REAR PANELS
1.2. MECHANICAL INSTALLATION
1.3. ELECTRICAL INSTALLATION
1.4. CONNECTION DIAGRAM
2. PUSHBUTTON FUNCTIONS
3. DISPLAY NAVIGATION
4. DEVICE CONFIGURATION
4.1. INTRODUCTION
4.2. RESETTING DEMAND VALUES
4.3. RESETTING ENERGY COUNTERS
4.4. RESETTING THE HOUR COUNTER
4.5. RESETTING ALARMS
4.6. SETTING THE DEFAULT SCREEN
4.7. SETTING THE CURRENT TRANSFORMER RATIO
4.8. SETTING THE VOLTAGE TRANSFORMER RATIO
4.9. SETTING HIGH AND LOW VOLTAGE LIMITS
4.10. SETTING HIGH AND LOW FREQUENCY LIMITS
4.11. SETTING THE OVERCURRENT LIMIT
4.12. SETTING HIGH AND LOW ACTIVE POWER LIMITS
4.13. SETTING HIGH AND LOW REACTIVE POWER LIMITS
4.14. SETTING HIGH AND LOW POWER FACTOR LIMITS
4.15. CONFIGURING THE DIGITAL INPUT
4.16. CONFIGURING THE RELAY OUTPUT
4.17. DISPLAYING THE FIRMWARE VERSION
4.18. CALIBRATION
4.19. LAMP TEST
5. TECHNICAL SPECIFICATIONS
-3-
DKM-405 User Manual V-1.5
1. INSTALLATION
Before installation:
• Read the user manual carefully, determine the correct connection diagram.
• Remove all connectors and mounting brackets from the unit, then pass the unit through
the mounting opening.
• Put mounting brackets and tighten. Do not tighten too much, this can brake the
enclosure.
• Make electrical connections with plugs removed from sockets, then place plugs to their
sockets.
• Note that the power supply terminal is separated from measurement terminals.
-4-
DKM-405 User Manual V-1.5
-5-
DKM-405 User Manual V-1.5
• Fuses must be connected to the power supply and phase voltage inputs, in close
proximity of the unit.
• For current transformer inputs, use at least 1.5mm2 section (AWG15) cable.
• The current transformer cable length should not exceed 1.5 meters. If longer
cable is used, increase the cable section proportionally.
-6-
DKM-405 User Manual V-1.5
-7-
DKM-405 User Manual V-1.5
2. PUSHBUTTON FUNCTIONS
Three buttons on the front panel provide access to configuration and measurement
screens.
BUTTON FUNCTION
Selects display context
• THD display
• Minimum values display
• Maximum values display
• Demand display
• If all leds are off then actual measurements
display.
Upper screen
or
Increase related value (configuration mode)
Lower screen
or
Decrease related value (configuration mode)
-8-
DKM-405 User Manual V-1.5
3. DISPLAY NAVIGATION
The button will select the display context and buttons will navigate between
possible values of this context.
Phase indication leds will reflect the phase displayed on the screen.
Phase status leds will turn-on if the related phase voltage is above 70 volts.
Relay led will turn-on when the relay output is active.
Kilo leds will turn on if the displayed value is in kA/kV/kW/kVA/kVAr.
Sigma led will turn on when displaying total values.
V / Hz leds will turn-on when the displayed value is in volts or hertz.
Display of currents: If the CT ratio is below 200/5 then currents will be displayed with
0.1A precision. If the CT ratio is between 200/5 and 2000/5 then currents are displayed
with 1A precision. If the CT ratio is above 2000/5 then currents are displayed with 0.01 kA
precision and the “k” led will turn on.
Display of voltages: If the VT ratio is above 100.0/1 then voltages will be displayed with
0.1kV precision. If the VT ratio is between 100.0/1 and 20.0/1 then voltages will be
displayed with 0.01kV precision. In both cases the “k” led will turn on. If the VT ratio is
below 20.0/1 then voltages are directly displayed with 1V precision.
Display of kW, kVA, kVAr: If the product CTxVT is below 1000 then the values will be
displayed with 0.1k precision. Otherwise they will be displayed with 1k precision.
Display of kWh, kVArh, Hours: Values are displayed with a precision of 0.1 k (or hour).
-9-
DKM-405 User Manual V-1.5
4. DEVICE CONFIGURATION
4.1 INTRODUCTION
In order to offer the maximum flexibility to the user, the unit has several configurable
parameters.
- 10 -
DKM-405 User Manual V-1.5
Parameter value:
0: No action
1: Reset Demand values
SET
values.
The parameter value is not stored into
memory and reads always 0.
MENU
PGM
MENU
Parameter value:
0: No action
1: Reset kWh and kVArh counters
SET
PGM
MENU
- 11 -
DKM-405 User Manual V-1.5
Parameter value:
0: No action
1: Reset hour counter
SET
PGM
MENU
Parameter value:
0: No action
1: Reset alarms
SET
PGM
MENU
- 12 -
DKM-405 User Manual V-1.5
is pressed.
SET
Setting this parameter to 0 will cancel the
default screen.
Param. Upper Lower display
value displays
0 no change no change
MENU
1 Voltages L-N Frequency
PGM
2 Voltages L-L Frequency
MENU
3 Voltages L-L Voltage L1-N
4 Currents Total current
5 Currents Frequency
6 Currents Voltage L1-N
7 Phase kW Total kW
8 Phase kW Frequency
9 Phase kW Voltage L1-N
10 Phase kVAr Total kVAr
11 Phase kVAr Frequency
12 Phase kVAr Voltage L1-N
13 Phase kVA Total kVA
14 Phase kVA Frequency
15 Phase kVA Voltage L1-N
16 Phase cosø Average cosø
17 Phase cosø Frequency
18 Phase cosø Voltage L1-N
19 - kWh counter
20 - kVArh counter
21 - hour counter
- 13 -
DKM-405 User Manual V-1.5
SET
Current transformer secondary rating
should be 1 Amps.
MENU
PGM
MENU
SET
All voltage and power measurements will
be displayed after multiplication with this
parameter.
The factory set default value is 1.0
Acceptable values are 0.1 to 200.0
MENU
PGM
MENU
- 14 -
DKM-405 User Manual V-1.5
SET
Only phase to neutral voltages are
monitored and generate alarms.
MENU
SET
Only phase to neutral voltages are
monitored and generate alarms.
MENU
- 15 -
DKM-405 User Manual V-1.5
SET
If the parameter is set to 0 then no high
frequency alarm will occur.
MENU
PGM
MENU
SET
If the parameter is set to 0 then no low
frequency alarm will occur.
MENU
PGM
MENU
- 16 -
DKM-405 User Manual V-1.5
SET
If the parameter is set to 0 then no
overcurrent alarm will occur.
MENU
PGM
MENU
- 17 -
DKM-405 User Manual V-1.5
SET
If the parameter is set to 0 then no excess
active power alarm will occur.
MENU
PGM
MENU
SET
If the parameter is set to 0 then no low
active power alarm will occur.
MENU
PGM
MENU
- 18 -
DKM-405 User Manual V-1.5
SET
If the parameter is set to 0 then no excess
reactive power alarm will occur.
MENU
PGM
MENU
SET
If the parameter is set to 0 then no low
reactive power alarm will occur.
MENU
PGM
MENU
- 19 -
DKM-405 User Manual V-1.5
SET
If the parameter is set to 0.000 then no high
cosø alarm will occur.
MENU
PGM
MENU
SET
If the parameter is set to 0.000 then no low
cosø alarm will occur.
MENU
PGM
MENU
- 20 -
DKM-405 User Manual V-1.5
SET
0: input active when signal applied
1: input active when signal removed
MENU
SET
This delay is necessary to prevent spurious
signal detection due to electrical noise.
MENU
PGM
MENU
- 21 -
DKM-405 User Manual V-1.5
SET
The factory set default value is 0.
MENU
PGM
MENU
- 22 -
DKM-405 User Manual V-1.5
logic is explained in the next picture.
SET
Each of 4 available functions is selected
from the below list. Unused functions
should be left as 0.
Value Relay Function
0 -
MENU
1 Follows the digital input
PGM
2 kWh tick
MENU
3 kVArh tick
4 High voltage alarm
5 Low voltage alarm
6 High frequency alarm
7 Low frequency alarm
8 Overcurrent alarm
9 Excess active power alarm
10 Low active power alarm
11 Excess reactive power alarm
12 Low reactive power alarm
13 High cosø alarm
14 Low cosø alarm
15 Phase sequence alarm
16 Relay active if any alarm exists
combined functions may be attributed to
SET the relay output.
This parameter defines how functions are
combined in order to generate the relay
output.
0: Functions logically OR’ed. The relay
MENU
output is active if any of the 4 functions is
PGM
active.
MENU
1: Functions loagically AND’ed. The relay
output is active if all 4 functions are active.
- 23 -
DKM-405 User Manual V-1.5
SET
The firmware version may be required by
the manufacturer together with any
customer application.
MENU
PGM
MENU
- 24 -
DKM-405 User Manual V-1.5
4.18 CALIBRATION
SET
If recalibration is required, Please enter
“3282” at the bottom display then press
button.
MENU
PGM
MENU
MENU
- 25 -
DKM-405 User Manual V-1.5
MENU
PGM
on.
Press any button to exit LAMP TEST and
return to normal operating mode.
MENU
- 26 -
DKM-405 User Manual V-1.5
5. TECHNICAL SPECIFICATIONS
- 27 -