ANALYSIS RESULTS
• Note: A value of 0 in the results column indicates that the particular gas is below detection limits.
Fault Analysis as per IEEE C57.104-2019 / IEC 60599:2015 (Duval Trianale method)
Fault Code: PD
Corona partial discharges. Possible causes: Discharges in gas-filled cavities resulting from
Diagnosis: incomplete impregnation, highhumidity in paper, oil super saturation or cavitation, and
leading to X-wax formation
CO2/CO ratio Not applicable since one or both of these gases is in normal range.
Disclaimer: The above mentioned remarks and interpretations are computer generated and suggestive in nature. Please correlate with other factors
before making a decision.