RCMS460-490 D00067 M Xxen
RCMS460-490 D00067 M Xxen
RCMS460-490 D00067 M Xxen
RCMS460-490_D00067_03_M_XXEN/12.2017
Bender GmbH & Co. KG
Londorfer Str. 65 • 35305 Gruenberg • Germany
P. O. Box 1161 • 35301 Gruenberg • Germany
Tel.: +49 6401 807-0
Fax: +49 6401 807-259
Email: info@bender.de
www.bender.de
RCMS460-490_D00067_03_M_XXEN/12.2017 3
Table of Contents
4 RCMS460-490_D00067_03_M_XXEN/12.2017
Table of Contents
RCMS460-490_D00067_03_M_XXEN/12.2017 5
Table of Contents
RCMS460-490_D00067_03_M_XXEN/12.2017 6
1. Important information
Always keep this manual within easy reach for future reference.
To make it easier for you to understand and revisit certain sections in this man-
ual, we have used symbols to identify important instructions and information.
The meaning of these symbols is explained below:
This signal word indicates a low level risk that can result in
minor or moderate injury or damage to property if not
avoided.
CAUTION
This manual has been compiled with great care. It might nevertheless contain
errors and mistakes. Bender cannot accept any liability for injury to persons or
damage to property resulting from errors or mistakes in this manual.
RCMS460-490_D00067_03_M_XXEN/12.2017 7
Important information
Commissioning
Troubleshooting
8 RCMS460-490_D00067_03_M_XXEN/12.2017
Important information
products
Analysis of the electrical installation in the building (power quality test,
*Available from 7.00 a.m. to 8.00 p.m. 365 days a year (CET/UTC+1)
**Mo-Thu 7.00 a.m. - 8.00 p.m., Fr 7.00 a.m. - 13.00 p.m
RCMS460-490_D00067_03_M_XXEN/12.2017 9
Important information
10 RCMS460-490_D00067_03_M_XXEN/12.2017
Important information
device.
Failure to observe the instructions in this operating manual regarding
manufacturer.
Non-observance of technical data.
RCMS460-490_D00067_03_M_XXEN/12.2017 11
Important information
1.7 Disposal
Abide by the national regulations and laws governing the disposal of this de-
vice. Ask your supplier if you are not sure how to dispose of the old equip-
ment.
The directive on waste electrical and electronic equipment (WEEE directive)
and the directive on the restriction of certain hazardous substances in electri-
cal and electronic equipment (RoHS directive) apply in the European Commu-
nity. In Germany, these policies are implemented through the "Electrical and
Electronic Equipment Act" (ElektroG). According to this, the following applies:
Electrical and electronic equipment are not part of household waste.
Batteries and accumulators are not part of household waste and must
be disposed of in accordance with the regulations.
Old electrical and electronic equipment from users other than private
households which was introduced to the market after 13 August 2005
must be taken back by the manufacturer and disposed of properly.
12 RCMS460-490_D00067_03_M_XXEN/12.2017
2. Safety instructions
If the device is used outside the Federal Republic of Germany, the applicable
local standards and regulations must be complied with. The European stand-
ard EN 50110 can be used as a guide.
RCMS460-490_D00067_03_M_XXEN/12.2017 13
Safety instructions
14 RCMS460-490_D00067_03_M_XXEN/12.2017
Safety instructions
Any use other than that described in this manual is regarded as improper.
RCMS460-490_D00067_03_M_XXEN/12.2017 15
Safety instructions
16 RCMS460-490_D00067_03_M_XXEN/12.2017
3. System description
In buildings and industrial installations, a fault or failure of the power supply
involves high costs. In installations which require a high fault tolerance and
good safety, an RCMS system should constantly monitor the TN-S system for
insulation deterioration to ensure that the system is "clean" and electromag-
netically compatible.
RCMS460-490_D00067_03_M_XXEN/12.2017 17
System description
Digital input
Each individual channel can be used for one of the following monitoring func-
tions:
– As digital input using a potential-free contact 1/0
– Or for current or residual current monitoring in combination with
measuring current transformers.
18 RCMS460-490_D00067_03_M_XXEN/12.2017
System description
Analysis of harmonics
The analysis of the harmonics of the measured currents can be selected via a
menu item in RCMS460-D, RCMS490-D. There, the DC component, the THF
and the current value of the harmonics (1…40 at 50/60 Hz, 1…5 at 400 Hz) is
displayed numerically and graphically.
RCMS460-D
Device version RCMS460-D utilises a backlit graphical display. This version is
used for local display of detailed information about all devices connected to the
bus in the control cabinet. This device can be used to parameterise all RCMS de-
vices connected to the BMS bus and to display all measurement details. Several
RCMS-D devices can be used within one system.
RCMS460-L
Device version RCMS460-L utilises a two-digit 7-segment display where the
address of this device is displayed within the BMS bus. The alarm LEDs indicate
in which measuring channel the response value has been exceeded. Parameters
can be set via an RCMS…D, an Ethernet gateway (z. B. COM460IP) or a Condi-
tion Monitor (z. B. COMTRAXX CP700).
RCMS490-D/RCMS490-L
The function of the device versions RCMS490-D/RCMS490-L corresponds to
the function described above. In addition, a galvanically isolated alarm con-
tact (N/O contact) is available, e.g. for triggering a circuit breaker in this sub-
circuit when a response value is exceeded.
RCMS460-490_D00067_03_M_XXEN/12.2017 19
System description
RCMS…-D4/RCMS…-L4
The function of device version RCMS…-D4/RCMS…-L4 corresponds to the
function described before. The functions of measuring channels k9 … k12
vary from those described before. They are exclusively designed for current
measurements with type A measuring current transformers (measuring ran-
ge 100 mA … 125 A). For that reason, the measuring channels k9…k12 cannot
be used in combination with W…AB series measuring current transformers or
as digital inputs.
20 RCMS460-490_D00067_03_M_XXEN/12.2017
4. Installation and connection
4.1 Unpacking
Unpack all the parts supplied with the system. Avoid sharp-edged tools
that may damage the content of the packaging.
Compare your order with our delivery note to check that you have
received all products in full. The article numbers and type designation
printed on the nameplates provides an easy means of uniquely identifying
each device.
Check all parts supplied for any evidence of damage in transit. Equip-
ment damaged in transit must not be used. If a device has sustained
damage, please contact Bender. Details of who to contact are indicated
on the delivery documents.
When storing the devices in a cold environment as it is in winter, note
the following: Leave the devices to stand for 3 to 4 hours at room tem-
perature before connecting the power supply. When the devices are
moved from a cold to a warm environment, condensation will be evi-
dent on all parts. Putting damp devices into operation can result in
damage to electrical components and electric shock in case of contact.
RCMS460-490_D00067_03_M_XXEN/12.2017 21
Installation and connection
Mount the measuring current transformers in accordance with the notes in the
"Transformer installation“ technical information. When connecting the measu-
ring current transformers, it is essential that you observe the maximum cable
lengths, the conductor cross section and that you use shielded cables.
22 RCMS460-490_D00067_03_M_XXEN/12.2017
Installation and connection
Dimensions in mm
RCMS460-490_D00067_03_M_XXEN/12.2017 23
Installation and connection
4.4 Connection
24 RCMS460-490_D00067_03_M_XXEN/12.2017
Installation and connection
R, T/R External reset button (N/O contact). The external reset but-
tons of several devices must not be connected to one ano-
ther.
T, T/R External test button (N/O contact). The external test buttons
of several devices must not be connected to one another.
C11, C12, Common alarm relay K1: Alarm 1, common message for
C14 alarm, prewarning, device error.
C21, C22, Common alarm relay K2: ALARM 2, common message for
C24 alarm, prewarning, device error.
RCMS460-490_D00067_03_M_XXEN/12.2017 25
Installation and connection
26 RCMS460-490_D00067_03_M_XXEN/12.2017
Installation and connection
R, T/R External reset button (N/O contact). The external reset but-
tons of several devices must not be connected to one ano-
ther.
T, T/R External test button (N/O contact). The external test buttons
of several devices must not be connected to one another.
C11, C12, Common alarm relay K1: Alarm 1, common message for
C14 alarm, prewarning, device error.
C21, C22, Common alarm relay K2: Alarm 2, common message for
C24 alarm, prewarning, device error.
11, 14 … Alarm relay per channel: One N/O contact per measuring
121, 124 channel (e.g. N/O contacts 11,14 for channel 1).
RCMS460-490_D00067_03_M_XXEN/12.2017 27
Installation and connection
28 RCMS460-490_D00067_03_M_XXEN/12.2017
Installation and connection
Coding
RCMS460-490_D00067_03_M_XXEN/12.2017 29
Installation and connection
30 RCMS460-490_D00067_03_M_XXEN/12.2017
Installation and connection
RCMS460-490_D00067_03_M_XXEN/12.2017 31
Installation and connection
distribution
series board
W...AB
series
W..., WR...,
WS..., WF... series
W..., WR..., series
WS..., W..., WR...,
series WS..., WF...
W...AB series
W...AB
series
W...AB
32 RCMS460-490_D00067_03_M_XXEN/12.2017
Installation and connection
COM465IP
COMTRAXX®
ON
ETHERNET/IP
MODBUS/RTU
BMS
N L
DI-1DL
B/N A/P B/N A/P
RCMS460-490_D00067_03_M_XXEN/12.2017 33
Installation and connection
DI-1DL The DI-1DL repeater only is required when the length of the
cable exceeds 1200 m or when more than 32 devices are
connected to the bus.
CT W…, WR…, WS…, WF…, W…AB series measuring current
transformers.
a b
a Potential-free contact
Status Resistance between k and l
0: > 250 Ω
1: < 100 Ω
b Measuring current transformer
34 RCMS460-490_D00067_03_M_XXEN/12.2017
5. Commissioning
5.1 Before switching on
Note on opening the transparent front panel cover:
Take hold of the cover at the bottom edge and swivel it
upwards. The cover can also be removed completely. Once
the adjustments have been completed, the front panel cover
must be refitted.
RCMS460-490_D00067_03_M_XXEN/12.2017 35
Commissioning
5.2 Switching on
1. Connect the supply voltage of all devices connected to the BMS bus.
Initially, the "ON" LED flashes on the RCMS… and the RCMS460…-D
graphic display shows the (Bender) welcome screen. The "ON" LED
then lights up permanently.
2. Set the BMS bus addresses. Never assign one address twice. Check, if
address 001 and thus the master function has been assigned.
3. Select the language (see page 71).
4. Set the CT type for each channel (page 66).
5. Start the preset function (see page 56).
6. Switch off unassigned measuring channels to avoid device errors (see
page 63).
7. Fault messages may be caused by measuring current transformers not
being connected. Check the measuring current transformer connec-
tions. Switch off the CT monitoring of the measuring channels not cur-
rently used (see page 67).
8. Eliminate insulation faults and the associated fault messages. If a res-
ponse value is exceeded or device error messages occur, this is indica-
ted on the RCMS… by means of the alarm LEDs lighting up and an
associated message appearing on the graphic display (RCMS…-D
only).
– You can find information about the alarms on the RCMS460…-D in
the "Alarm/Meas. values" menu. Information on the RCMS…-L can
be displayed via the BMS master.
– Eliminate the insulation faults detected by the RCMS. Check whe-
ther the set response values are correct and practical for this sys-
tem. If you want to readjust all response values, use the preset
function of the device.
– The RCMS…-D displays any device errors that have occurred. The
RCMS…-L… displays an error code. If a device error continues to
exist after a reset has been carried out, the RCMS… has to be
replaced.
36 RCMS460-490_D00067_03_M_XXEN/12.2017
6. Operation
6.1 Operating and display elements RCMS460…-D
RCMS460-D RCMS490-D
1 LINETRAXX®
4
5
2 6
8 7
3
RCMS460-490_D00067_03_M_XXEN/12.2017 37
Operation
RCMS460-L RCMS490-L
1 LINETRAXX®
4
5
2 6
7
3
8 9
38 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
Channel disabled
100% (height = 1 graduation m
50% Channel enabled
Channel enabled,
0% current is flowing
k 1 2 3 4 5 6 7 8 9 10 11 12
(height ≥ 2 graduation m
The RCMS…-L shows its BMS bus address (e.g. 02). Only the green "Power ON"
LED is lit.
RCMS460-490_D00067_03_M_XXEN/12.2017 39
Operation
ALARM 1/1
Residual current
130 mA
Addr.: 2 Chan.: 12
Line 1: ALARM, PREWARNING or FAULT
Alarm 1 of 1 pending alarms
Line 2: Alarm status and alarm text: (e.g. residual current, digital in-
put, no Master, CT connection).
No alarm
Prewarning
Alarm, fault
Line 3: r.m.s. value
Line 4: BMS bus address of the RCMS and measuring channel on
which the alarm has occurred.
40 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
page 68).
An alarm message is sent on the BMS bus.
Auto test
The RCMS460…-D then displays the set response value for the highest
functioning measuring channel.
Press the "" button several times to display the correct functioning of
the other measuring channels.
TEST 12/12
Residual current
100 mA
Addr.: 2 Chan.: 12
RCMS460-490_D00067_03_M_XXEN/12.2017 41
Operation
After successful testing, all LEDs must go out again, with the exception of the
LED "ON" and the alarm relays must return to their initial position.
RCMS…-D… only: First press the "ESC" button to exit the display of the cur-
rent alarm message. The "RESET" button cannot be pressed before the stan-
dard display appears (bar chart).
Saved alarm messages that are no longer pending are deleted. The alarm relay
drops out, the alarm LEDs go out and there are no longer any alarm messages
on the BMS bus.
42 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
RESET
RCMS460-D
10.03.16 12:59
Address :2
Software: D233V2.50
RCMS460-490_D00067_03_M_XXEN/12.2017 43
Operation
– Language – Time/date
44 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
Exit
1.Alarm/meas.values
2.% Bar graph
3.History
In the main menu, use the following buttons:
ESC Exit this function without storing or go up one menu level.
, Select menu items
↵ Confirm selected menu item (Enter).
Enter
password:
0 0 0
RCMS460-490_D00067_03_M_XXEN/12.2017 45
Operation
1.Alarm/meas.values Exit
2.% Bar graph 1.General
2.PRESET
3.History
3.Channel
4.Harmonics
4.Relay
5.Data logger 5.History
6.Data logger
6.Settings 7.Language
8.Interface
9.Alarm addresses
10.Clock
11.Password
12.Factory setting
13.Service
Exit
Exit
1.TEST
7.Control
2.RESET
8.External devices 3.Test communication
9.Info
Exit
46 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
RCMS460-490_D00067_03_M_XXEN/12.2017 47
Operation
48 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
RCMS460-490_D00067_03_M_XXEN/12.2017 49
Operation
1. If you are searching for an event that occurred at a specific time, use
the arrow buttons to navigate to the required entry.
2. Press the "↵" button to call up details about the current entry in the his-
tory memory.
50 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
Channel:1 121mA
THF 3%
DC 3mA
1. 85mA
THF: The total harmonic factor (THF) specifies the ratio of the har-
monics r.m.s value of an alternating quantity to the funda-
mental r.m.s. value. The smaller the THF, the more sinusoidal
the current signal.
RCMS460-490_D00067_03_M_XXEN/12.2017 51
Operation
Exit
1.Data logger
2.Data logger
3.Data logger
52 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
RCMS460-490_D00067_03_M_XXEN/12.2017 53
Operation
54 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
1. Fault memory
Faults that only occur temporarily can be saved.
on After eliminating the cause of fault all alarm messages remain
stored until a reset is carried out.
off RCMS… exits the alarm mode as soon as the cause of fault is
eliminated.
2. Prewarning
Setting as a percentage of the response value. Setting range: 10…100 %,
resolution of setting 1%.
3. Hysteresis
If the measured value were to oscillate around the response value, the
RCMS… would constantly change from alarm to normal status and back
again. If a hysteresis of 20 % is set, the alarm status is not exited until the mea-
sured value is 20 % below resp. above the response value.
Setting range: 2…40 %, resolution of setting 1%.
4. Frequency
Select the rated frequency of the monitored current. Only if the setting is cor-
rect, can the RCMS… determine the harmonics currents properly.
Setting options: DC, 50 Hz, 60 Hz, 400 Hz.
RCMS460-490_D00067_03_M_XXEN/12.2017 55
Operation
5. Start-up delay t
Time delay after the RCMS… is switched on.
No alarm messages are generated during this period. This time delay is requi-
red if the RCMS…-D and the monitored system are switched on simultaneous-
ly. Currents caused by switching actions are ignored.
Setting range: 0…99 s. Resolution of settings as follows:
Displayed by a formula:
Response value = (currently measured value x factor) + Offset
Exit
1.Factor: *3
2.Offset: 30 mA
3.PRESET
56 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
3. PRESET
RCMS460-490_D00067_03_M_XXEN/12.2017 57
Operation
58 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
Factory setting:
Factor: *1, CT monitoring: on
RCMS460-490_D00067_03_M_XXEN/12.2017 59
Operation
Bender-Messstromwandler
Bender-
Messstromwandler
Settings:
Factor = (X / N)
= 100/1
= *100
Measuring current transformer monitoring: On
60 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
Example 3:
The wire to be monitored is "wound" several times through the
Bender current transformer in order to amplify the signal
Setting:
Factor: /3
Measuring current transformer monitoring: On
2. Response value
The response value is the value at which an alarm is output. In case of digital
inputs, set the status (0 or 1) at which an alarm is to be signalled.
RCMS460-490_D00067_03_M_XXEN/12.2017 61
Operation
Depending on the settings in the "Channel -> Mode" menu and "Channel ->
CT" menu the following response values can be selected:
62 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
3. Function
Monitoring the measuring channel for overcurrent or undercurrent. Use of the
measuring channel as digital input. Unused measuring channels have to be
disabled.
> Alarm when the response value is exceeded.
< Alarm when the value falls below the set response value.
0/1 Use of the measuring channel as digital input.
off Measuring channel disabled.
RCMS460-490_D00067_03_M_XXEN/12.2017 63
Operation
RCMS…- RCMS…-
RCMS…-D/-L
Measuring function D4/-L4, D4/-L4,
Channel
(selectable) Channel Channel
1…12
1…8 9…12
64 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
6. Cutoff frequency
Set the characteristics for the frequency response of residual current measu-
rement IΔn and current measurement I.
Param. Objective
The frequency response of the equipment can be set for a linear frequency re-
sponse (up to the maximum frequency of 2000 Hz) if used for fire protection
or for a frequency response in accordance with IEC 60990 for personnel pro-
tection. For plant protection, the residual current is measured up to the rated
system frequency. The figure below shows the corresponding frequency res-
ponse.
RCMS460-490_D00067_03_M_XXEN/12.2017 65
Operation
Frequency response
50 Hz 60 Hz
Response factor
IEC
none
(cut-off frequency)
I(d)
Response factor =
I(dn)
I(d) Residual current IΔ: r.m.s. value currently measured
I(dn) Rated residual operating current IΔn: Set response value
7. CT
Set the type of measuring current transformer.
Type A Pulsating current sensitive W…, WR…, WS…
series measuring current transformers
Flex. Flexible WF… series measuring current trans-
formers
Type AB AC/DC sensitive W…AB series measuring cur-
rent transformers
66 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
8. CT monitor.
Enable or disable the measuring current transformer connection monitoring.
on Measuring current transformer connection is monitored.
Connection interruption, short-circuit or failure of the power supply
unit generate an alarm message after 20 seconds at the latest (W…AB
series) (Fault: CT connection). The "ALARM 1" LED lights up.
off Measuring current transformer connection is not monitored.
* This function can also be activated via the BMS bus. By sending the command
"off" or "on" via the BMS bus, the switching of the relay can be activated. This
relay does not respond to alarms. It only serves as a signal converter (BMS-bus
signals/relay contact signals.
RCMS460-490_D00067_03_M_XXEN/12.2017 67
Operation
Set a Relay: 1
single relay:
Exit
1.Mode of opera-
tion:N/O
Set both Relay: 1..2
relays:
Exit
1.Op.mode
2.Alarm: --
68 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
1. Relay mode
Set the relay mode of operation:
2. Alarm
on Relay switches in the event of an alarm.
off Relay does not switch in the event of an alarm.
3. Prewarning
on Relay switches in the event of a prewarning.
off Relay does not switch in the event of a prewarning.
4. Device error
on Relay switches in the event of a device error.
off Relay does not switch in the event of a device error.
5. Ext. Alarm
on Relay switches in the event of an external alarm*.
off Relay does not switch in the event of an external alarm*.
* Alarm on an external device the address of which has been set to "on" in the
"Alarm addresses" menu. (see “Settings menu 9: Alarm addresses” on page 71).
RCMS460-490_D00067_03_M_XXEN/12.2017 69
Operation
Chan.: 1
Exit
1.Modific.: 10%
2.Overwrite:yes
1. Modific.
A new measured value will be saved if it differs from the previous measured
value by the percentage value defined here.
Setting range: 0…100 %, resolution of setting 1 %.
70 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
2. Overwrite
Yes If the memory (300 measuring values) for this measuring
channel is full, the oldest measured value is deleted to create
space for the new measured value entry.
No Data logger records 300 measured values then stops.
3. Delete
The recorded measured values of this measuring channel are deleted. To pre-
vent unwanted execution of this function, the entry must be confirmed once
more.
RCMS460-490_D00067_03_M_XXEN/12.2017 71
Operation
Exit
1.Address: on
2.Address: off
3.Address: off
on Messages of this device will be displayed.
off Messages of this device will not be displayed.
Set the time and date at the BMS bus master (addr. 1). All
slaves adopt this setting. The setting is synchronised every
hour.
The "Clock" menu setting remains stored for approx. 2 h after
power supply failure.
1. Format
Select the German or American format.
d.m.y German format (day.month.year)
m-d-y American format (month-day-year)
2. Date
Set the date (e.g. 20.08.2014).
3. Time
Set the time (e.g. 16:44).
4. Summer time
Setting for automatic switchover to Central European Summer Time.
CEST Automatic switchover
Off No switchover (winter time is retained)
72 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
1. Password
Change password. Factory setting: 000
2. Status
Activate or deactivate password protection.
Enter
password:
0 0 0
RCMS460-490_D00067_03_M_XXEN/12.2017 73
Operation
Channel disabled
Exit
1.Chan.: --
74 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
1. Use the button to go to the measuring channel setting. Press the "↵"
button.
2. Use the Up/Down buttons to select a measuring channel. Press "↵" to
confirm your selection.
An alarm message is sent to the BMS bus. This is indicated by the alarm
display . Depending on the function set for the measuring channel,
an alarm (residual current, overcurrent, undercurrent) is output or a
digital input is indicated.
Residual current
Exit
1.Chan.: 1
RCMS460-490_D00067_03_M_XXEN/12.2017 75
Operation
Exit
1.RCMS460-D
2.RCMS460-L
3. --
Use the Up/Down buttons to select the address of the external device and
confirm with the "↵" button.
3: --
If "no access to the menu" appears, press the "ESC“ button to exit the display.
Possible causes are:
76 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
The "External devices" menu is not suitable for programming this RCMS… If
you otherwise try to program it, the error message "Own address" will appear.
Press the "ESC" button to exit this menu.
When the device has been recognised, the RCMS…-D reads the current set-
tings of the connected device. The address and the device type will be dis-
played in the first line.
2:RCMS460-L
Exit
1.Alarm/meas.values
2.% Bar graph
RCMS460-490_D00067_03_M_XXEN/12.2017 77
Operation
Use the Up/Down buttons to select the appropriate function or device setting
and confirm with the "↵" button.
78 RCMS460-490_D00067_03_M_XXEN/12.2017
Operation
RCMS460-490_D00067_03_M_XXEN/12.2017 79
Operation
80 RCMS460-490_D00067_03_M_XXEN/12.2017
7. Tests, service, troubleshooting
Observe the applicable national and international standards which require re-
gular testing of electrical equipment.
Please contact our Service Department for more information. You will find the
address on page 9 of this manual.
RCMS460-490_D00067_03_M_XXEN/12.2017 81
Tests, service, troubleshooting
7.3 Troubleshooting
Error
Description
code
RCMS…-D… RCMS…-L…
Device error: xx Er
xx (alternately displayed)
xx = Error code
82 RCMS460-490_D00067_03_M_XXEN/12.2017
Tests, service, troubleshooting
Fault 1/1
Device error
11
Addr.: 2 Chan.: 4
Line 1: Fault,
Alarm 1 of 1 pending alarm.
Line 2: Alarm status and alarm text.
No alarm
Prewarning
Alarm, fault
Line 3: Error code (refer to „Display device error“ on page 82).
Line 4: BMS bus address of the RCMS and measuring channel on
which the alarm has occurred.
Possible causes:
W…AB series measuring current transformers are not calibrated.
The device errors remain saved until the "RESET“ button is pressed. An entry is
stored in the history memory with the suffix "Device error".
If a device error continues to exist after a reset has been carried out, the
RCMS… has to be replaced.
RCMS460-490_D00067_03_M_XXEN/12.2017 83
Tests, service, troubleshooting
Fault 1/1
CT connection
Addr.: 2 Chan.: 4
The "CT fault" is displayed in the same way as „Device error display (channel-
related)“ on page 83.
Possible causes:
Measuring current transformer defective.
Failure of the power supply unit AN420 or AN110 when W…AB series
Possible causes:
Alarm message from an external device.
Device failure
84 RCMS460-490_D00067_03_M_XXEN/12.2017
8. Data
8.1 Standards
Observe the applicable national and international standards. The RCMS… se-
ries corresponds to the following device standards:
DIN EN 62020 (VDE 0663):2005-11
The operating manuals for the individual system components provide you
with information about the standards that apply to that particular device.
The specified standards take into account the edition valid until 11.2017 un-
less otherwise indicated.
RCMS460-490_D00067_03_M_XXEN/12.2017 85
Data
86 RCMS460-490_D00067_03_M_XXEN/12.2017
Data
b) RCMS4x0-D2
Supply voltage US ............................................................................................. AC/DC 100…240 V (-20…+15 %)
Supply voltage frequency........................................................................................................................... DC, 50/60 Hz
RCMS460-490_D00067_03_M_XXEN/12.2017 87
Data
88 RCMS460-490_D00067_03_M_XXEN/12.2017
Data
RCMS460-490_D00067_03_M_XXEN/12.2017 89
Data
Switching elements
Number ................................................................................................................2 x 1 changeover contact (RCMS460)
.............................................................................................2 x 1 changeover contact, 12 x 1 N/O contact (RCMS490)
Operating principle ............................................................................................NC or N/O operation (N/O operation)*
Electrical endurance under rated operating conditions, number of cycles......................................................... 10.000
Contact data acc. to IEC 60947-5-1
Utilisation category....................................................................................... AC-13 AC-14 DC-12 DC-12 DC-12
Rated operational voltage.............................................................................230 V 230 V 24 V 110 V 220 V
Rated operational current (common alarm relay)............................................5 A 3 A 1 A 0.2 A 0.1 A
Rated operational current (alarm relay)............................................................ 2 A 0.5 A 5 A 0.2 A 0.1 A
Minimum contact rating.............................................................................................................1 mA at AC/DC ≥ 10 V
Environment/EMC
EMC................................................................................................................................................................. IEC 62020
Operating temperature......................................................................................................................... –25…+ 55 °C
Climatic class acc. to IEC 60721
Stationary use (IEC 60721-3-3)........................................................ 3K5 (except condensation and formation of ice)
Transport (IEC 60721-3-2) ................................................................ 2K3 (except condensation and formation of ice)
Long-term storage (IEC 60721-3-1)................................................. 1K4 (except condensation and formation of ice)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ...............................................................................................................................3M4
Transport (IEC 60721-3-2) ....................................................................................................................................... 2M2
Long-term storage (IEC 60721-3-1)........................................................................................................................ 1M3
Connection screw terminals
Connection properties:
Rigid/flexible/conductor sizes....................................................................... 0.2…4/0.2…2.5 mm2/AWG 24…12
Multi-conductor connection (2 conductors with the same cross section):
Rigid/flexible........................................................................................................................ 0.2…1.5/0.2…1.5 mm2
Stripping length ............................................................................................................................................. 8…9 mm
Tightening torque ..................................................................................................................................... 0.5…0.6 Nm
Other
Operating mode ............................................................................................................................continuous operation
Mounting............................................................................................................................................... display-oriented
Degree of protection, internal components (IEC 60529) ....................................................................................... IP30
90 RCMS460-490_D00067_03_M_XXEN/12.2017
Data
( )* factory setting
** In the frequency range of < 15 Hz, the relative uncertainty is between –35…+100 %.
RCMS460-490_D00067_03_M_XXEN/12.2017 91
Data
Accessories
92 RCMS460-490_D00067_03_M_XXEN/12.2017
Data
RCMS460-490_D00067_03_M_XXEN/12.2017 93
Data
94 RCMS460-490_D00067_03_M_XXEN/12.2017
Data
RCMS460-490_D00067_03_M_XXEN/12.2017 95
Data
* Absolute values
96 RCMS460-490_D00067_03_M_XXEN/12.2017
Data
RCMS460-490_D00067_03_M_XXEN/12.2017 97
Data
AC 16…72 V, 42…460 Hz
WF170-1 170 B78080201
DC 9,6…94 V
AC 70…300 V, 42…460 Hz
WF170-2 170 B78080202
DC 70…300 V
AC 16…72 V, 42…460 Hz
WF250-1 250 B78080203
DC 9,6…94 V
AC 70…300 V, 42…460 Hz
WF250-2 250 B78080204
DC 70…300 V
AC 16…72 V, 42…460 Hz
WF500-1 500 B78080205
DC 9,6…94 V
98 RCMS460-490_D00067_03_M_XXEN/12.2017
Data
AC 70…300 V, 42…460 Hz
WF500-2 500 B78080206
DC 70…300 V
AC 16…72 V, 42…460 Hz
WF800-1 800 B78080207
DC 9,6…94 V
AC 70…300 V, 42…460 Hz
WF800-2 800 B78080208
DC 70…300 V
AC 16…72 V, 42…460 Hz
WF1200-1 1200 B78080209
DC 9,6…94 V
AC 70…300 V, 42…460 Hz
WF1200-2 1200 B78080210
DC 70…300 V
AC 16…72 V, 42…460 Hz
WF1800-1 1800 B78080221
DC 9,6…94 V
AC 70…300 V, 42…460 Hz
WF1800-2 1800 B78080222
DC 70…300 V
RCMS460-490_D00067_03_M_XXEN/12.2017 99
Data
WXS-100 1 B98080506
WXS-250 2.5 B98080507
WXS-500 5 B98080508
WXS-1000 10 B98080509
100 RCMS460-490_D00067_03_M_XXEN/12.2017
INDEX
A Environment
AC/DC sensitive measured value acquisition - cold 21
14 Error code 82
Alarm 39, 49 External measuring current transformer 60
Alarm status 40, 49, 83
alternating currents 14 F
Approvals and certifications 85 Factor 59
- Determination 59
B Factory settings 73
Back-up fuses 22 Fault memory 55
Bar graph 39, 49 Frequency response 14, 65
Bender-Service 73
Bus address 71 H
Harmonics 14, 51
C High fault tolerance 17
Checking the device function. 41 History memory 50
Commissioning 35, 81 How to use this manual 7
Control 74 Hysteresis 55
Cutoff frequency 65
I
D Intended use 14, 15
Damage in transit 21
Data logger 70 L
Date 72 Language 71
DC component 52
Delay on release 65 M
Main menus 44, 45
E Maintenance 81
EMC 17 Menu mode 44
RCMS460-490_D00067_03_M_XXEN/12.2017 101
N Summer time 72
Nominal insulation voltage 22 Support 8
Switching actions 56
O Switching on 35, 36
Offset 56, 57
Operating mode 39 T
Ordering information 91 Test communication 74
Overcurrent 63 Test function 81
Overview diagram 46 THD 47, 51
Time 72
P Tolerances 61
Password 73 Training courses 10
Personnel protection 65 Transformation ratio 59
Presetting 56 Transformer monitoring 67
Prewarning 39, 55
Property protection 65 U
Protection against fire 65 Undercurrent 63
Pulsating currents 14 Unpacking 21
R W
r.m.s. value 49 Wiring diagram 25, 27
r.m.s. value of the measured residual cur- Work activities on electrical installations 13
rent 40 Workshops 10
Rated frequency 51, 55
Relay mode of operation 69
RESET 42
Response delay 64
S
Service 8
Shielded conductors 30
Standard information 43, 79
Standards 81
102 RCMS460-490_D00067_03_M_XXEN/12.2017
Bender GmbH & Co. KG
Londorfer Str. 65 • 35305 Gruenberg • Germany
P. O. Box 1161 • 35301 Gruenberg • Germany
Tel.: +49 6401 807-0
Fax: +49 6401 807-259
Email: info@bender.de
www.bender.de