Technical Information
Levelflex FMP50
Guided wave radar
Application
• Rod or rope probe
• Process connection: 3/4" thread or adapter flange
• Process temperature: –20 to +80 °C (–4 to +176 °F)
• Process pressure: –1 to +6 bar (–14.5 to +87 psi)
• Maximum measuring range: Rod 4 m (13 ft); rope 12 m (39 ft)
• Accuracy: ±2 mm (±0.08 in)
• International explosion protection certificates; WHG; EN10204-3.1
• Linearity protocol (3-point, 5-point)
Your benefits
• Reliable measurement even for changing product and process conditions
• HistoROM data management for easy commissioning, maintenance and
diagnostics
• Highest reliability due to Multi-Echo Tracking
• Hardware and software developed according to IEC 61508 (up to SIL3)
• Seamless integration into control or asset management systems
• Intuitive user interface in national languages
• Bluetooth® wireless technology for commissioning, operation and maintenance via
free iOS / Android app SmartBlue
• Easy proof test for SIL and WHG
• Heartbeat Technology™
Levelflex FMP50
Table of contents
Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Process temperature range . . . . . . . . . . . . . . . . . . . . . . 53 Device-specific accessories . . . . . . . . . . . . . . . . . . . . . . 87
2 Endress+Hauser
Levelflex FMP50
Communication-specific accessories . . . . . . . . . . . . . . . . 94
Service-specific accessories . . . . . . . . . . . . . . . . . . . . . . 95
System components . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Supplementary documentation . . . . . . . . . . . . . . . 95
Brief Operating Instructions (KA) . . . . . . . . . . . . . . . . . . 95
Operating Instructions (BA) . . . . . . . . . . . . . . . . . . . . . 95
Safety Instructions (XA) . . . . . . . . . . . . . . . . . . . . . . . . 95
Endress+Hauser 3
Levelflex FMP50
Electrical symbols
Direct current
Alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
Reference to documentation
Reference to graphic
Result of a step
1, 2, 3, ...
Item numbers
A, B, C, ...
Views
Temperature resistance of the connection cables
Specifies the minimum value of the temperature resistance of the connection cables
4 Endress+Hauser
Levelflex FMP50
20 mA
100%
D
E
LN F
4 mA
0%
A0011360
If the εr value is less than 7 in the case of rope probes, measurement is not possible in the area
of the tensioning weight (0 to 250 mm (0 to 9.84 in) from the probe end), (lower blocking
distance).
The reference point R of the measurement is located at the process connection.
Endress+Hauser 5
Levelflex FMP50
Dielectric constant
The dielectric constant (DC) of the medium directly affects the degree of reflection of the high-
frequency pulses. In the case of large DC values, such as with water or ammonia, there is strong
pulse reflection while, in the case of low DC values, such as with hydrocarbons, pulse reflection is
weak.
Input
The reflected pulses are transmitted from the probe to the electronics. Here, a microprocessor
evaluates the signals and identifies the level echo which was caused by the reflection of the high-
frequency pulses at the product surface. This clear signal detection system benefits from over 30
years of experience with pulse time-of-flight procedures that have gone into the development of the
PulseMaster® software.
The distance D to the product surface is proportional to the time of flight t of the impulse:
D = c · t/2,
with c being the speed of light.
Based on the known empty distance E, the level L is calculated:
L=E–D
The Levelflex has functions for interference echo suppression that can be activated by the user. They
guarantee that interference echoes from internal fixtures and struts, for example, are not interpreted
as level echoes.
Output
The Levelflex is preadjusted at the factory to the probe length ordered so that in most cases only the
application parameters that automatically adapt the device to the measuring conditions need to be
entered. For models with a current output, the factory adjustment for zero point E and span F is 4
mA and 20 mA, for digital outputs and the display module 0 % and 100 %. A linearization function
with max. 32 points, based on a table entered either manually or semi-automatically, can be
activated locally or remotely. This function allows the level to be converted into units of volume or
mass, for example.
6 Endress+Hauser
Levelflex FMP50
Probe selection
FMP50
For level measurement in liquids
A0011387
2 Rod probe
Endress+Hauser 7
Levelflex FMP50
Rod probe
• Maximum probe length
4 m (13 ft)
• Material:
316L
A0011388
Rope probe
• Maximum probe length
12 m (40 ft)
• Material:
316L
8 Endress+Hauser
Levelflex FMP50
Input
Measured variable The measured variable is the distance between the reference point and the product surface.
The level is calculated based on "E", the empty distance entered.
Optionally, the level can be converted to other variables (volume, mass) by linearization (32 points).
Measuring range The following table describes the media groups and the possible measuring range as a function of
the media group.
Levelflex FMP50
Measuring range
Typical
Media group εr Bare metallic Bare metallic
liquids
rod probes rope probes
The formation of buildup, particularly of moist products, can reduce the maximum possible
measuring range.
Endress+Hauser 9
Levelflex FMP50
Blocking distance The upper blocking distance (= UB) is the minimum distance from the reference point of the
measurement (mounting flange) to the maximum level.
R
SD UB
100%
E
F
LN
0%
A0011279
10 Endress+Hauser
Levelflex FMP50
Output
Output signal HART
• Signal coding:
FSK ±0.5 mA over current signal
• Data transmission rate:
1 200 Bit/s
• Galvanic isolation:
Yes
Bluetooth® wireless technology
• Device version:
Order code 610 "Accessory mounted", option NF "Bluetooth"
• Operation / configuration:
Via the SmartBlue app
• Range under reference conditions:
> 10 m (33 ft)
• Encryption:
Encrypted communication and password encryption prevent incorrect operation by unauthorized
persons
PROFIBUS PA
• Signal coding:
Manchester Bus Powered (MBP)
• Data transmission rate:
31.25 kBit/s, Voltage mode
• Galvanic isolation:
Yes
FOUNDATION Fieldbus
• Signal coding:
Manchester Bus Powered (MBP)
• Data transmission rate:
31.25 kBit/s, Voltage mode
• Galvanic isolation:
Yes
Switch output
For HART devices, the switch output is available as an option.
• Function:
Open collector switch output
• Switching behavior:
Binary (conductive or non-conductive), switches when the programmable switch-on point/switch-
off point is reached
• Failure mode:
Non-conductive
• Electrical connection data:
U = 16 to 35 VDC, I = 0 to 40 mA
• Internal resistor:
RI < 880 Ω
The voltage drop at this internal resistor must be taken into account when planning the
configuration. For example, the resulting voltage at a connected relay must be sufficient to switch
the relay.
• Insulation voltages:
Floating, insulation voltage 1 350 VDC in relation to power supply and 500 VAC ground
• Switch point:
User-programmable, separate for switch-on point and switch-off point
• Switching delay:
User-programmable in the 0 to 100 s range, separate for switch-on point and switch-off point
Endress+Hauser 11
Levelflex FMP50
• Scan rate:
Corresponds to the measuring cycle
• Signal source / device variables:
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude
• Diagnostic values, advanced diagnostic blocks
• Only for active interface measurement
• Number of switch cycles:
Unlimited
Linearization The device's linearization function allows the user to convert the measured value to any length or
volume units. Linearization tables for calculating the volume in cylindrical vessels are
preprogrammed into the device. Other tables of up to 32 value pairs can be entered manually or
semi-automatically.
Galvanic isolation All circuits for the outputs are galvanically isolated from each other.
12 Endress+Hauser
Levelflex FMP50
Manufacturer ID 17 (0x11)
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
• Level linearized
• Distance
• Electronic temperature
• Relative echo amplitude
Measured values for SV, TV, QV (second, third and fourth variable)
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Calculated εr value
Start-up current 4 mA
Starting time 80 s
Endress+Hauser 13
Levelflex FMP50
PROFIBUS PA
Manufacturer ID 17 (0x11)
FOUNDATION Fieldbus
Manufacturer ID 0x452B48
Choice of "Link Master" and "Basic Device" Yes; Factory setting: Basic Device
14 Endress+Hauser
Levelflex FMP50
Number of VCRs 44
Permanent entries 1
Client VCRs 0
Server VCRs 10
Source VCRs 43
Sink VCRs 0
Subscriber VCRs 43
Publisher VCRs 43
Slot time 4
Transducer Blocks
Block Contents Output values
Setup Transducer Block Contains all the parameters for standard • Level or volume (channel
commissioning 1)
(depending on the block
configuration)
• Distance (channel 2)
Advanced Setup Contains all the parameters for more accurate No output values
Transducer Block measurement configuration
Display Transducer Block Contains parameters to configure the onsite display No output values
Expert Configuration Contains parameters that require the user to have No output values
Transducer Block in-depth knowledge of the operation of the device in
order to configure the parameters appropriately
Expert Information Contains parameters that provide information about No output values
Transducer Block the state of the device
Service Sensor Contains parameters that can only be accessed by No output values
Transducer Block Endress+Hauser Service
Data Transfer Contains parameters for backing up the device No output values
Transducer Block configuration in the display module and for writing
the saved configuration to the device. Access to
these parameters is reserved for Endress+Hauser
Service.
Endress+Hauser 15
Levelflex FMP50
Function blocks
Block Contents Number of Number of Execution Functionality
permanent instantiatable time
blocks blocks
16 Endress+Hauser
Levelflex FMP50
Up to 20 blocks can be instantiated in the device altogether, including the blocks already
instantiated.
Endress+Hauser 17
Levelflex FMP50
Power supply
Terminal assignment
Terminal assignment 2-wire: 4-20 mA HART
A B
+
1 1 -
2 2
+
-
1 3
A0036498
3 4
2 5
1 6
+ + 1
I
- - 2
A0036499
18 Endress+Hauser
Levelflex FMP50
3
4
A B
+
3 3 -
4 4
+ +
- 1 -
2 1
+ 2
-
2
1 5
A0036500
3 4
2 5
1 6
+ + 1
I
- - 2
+ 3 Y
- 4
7
A0036501
Endress+Hauser 19
Levelflex FMP50
3
4
A B
+
3 3 -
4 4
+ +
- 1 -
2 1
+ 2
-
2
1 5
A0036500
3 4
2 5
1 6
+ + 1
I
- - 2
+ + 3 Y
- - 4
7
8
A0036502
20 Endress+Hauser
Levelflex FMP50
1
2
L+
L- 3
4
+
-
2 3
1
A0036516
3 4
2 5
1 6
+ 3
I
- 4
L+ 1
L- Y
2
7
A0036526
Endress+Hauser 21
Levelflex FMP50
1
2
L
N 3
4
+
-
2 3
1
A0036519
LCAUTION
To ensure electrical safety:
‣ Do not disconnect the protective connection.
‣ Disconnect the supply voltage before disconnecting the protective earth.
Connect protective earth to the internal ground terminal (3) before connecting the supply
voltage. If necessary, connect the potential matching line to the external ground terminal.
In order to ensure electromagnetic compatibility (EMC): Do not only ground the device via the
protective earth conductor of the supply cable. Instead, the functional grounding must also be
connected to the process connection (flange or threaded connection) or to the external ground
terminal.
An easily accessible power switch must be installed in the proximity of the device. The power
switch must be marked as a disconnector for the device (IEC/EN61010).
22 Endress+Hauser
Levelflex FMP50
3 4
2 5
1 6
+ 3
I
- 4
L 1
N Y
2
7
A0036527
3
4
A B
+
3 3 -
4 4
+ +
- 1 -
2 1
+ 2
-
2
1 5
A0036500
Endress+Hauser 23
Levelflex FMP50
2 3
+ 1
I
- 2
1 + 3 Y
- 4
4
A0036530
24 Endress+Hauser
Levelflex FMP50
3+
Ri +
-
4-
A0015909
17 Connection of a relay
+
1
2
3+
Ri
4-
A0015910
Endress+Hauser 25
Levelflex FMP50
Device plugs In device versions with a device plug (M12 or 7/8"), it is not necessary to open the housing in
order to connect the signal cable.
4 3
1 2
A0011175
1 3
2 4
A0011176
26 Endress+Hauser
Levelflex FMP50
• Non-Ex 11.5 to 35 V 3) 4)
R [!]
• Ex nA
• Ex ic 500
• CSA GP
Ex ia / IS 11.5 to 30 V 4)
0
10 20 30 35 U0 [V]
11.5 22.5
A0035511
4) 5)
• Ex d / XP 13.5 to 30 V R [Ω]
• Ex ic[ia]
• Ex tD / DIP
500
0
U0 [V]
10 20 30
13.5 24.5
A0034969
Endress+Hauser 27
Levelflex FMP50
• Ex ia / IS 13.5 to 30 V 3) 4)
• Ex ia + Ex d[ia] / IS + XP 0
10 20 30 U0 [V]
13.5 24.5 35
A0034971
any Channel 1:
13.5 to 30 V 3) 4) 5) R [Ω]
500
0
U0 [V]
10 20 30
13.5 24.5
A0034969
Channel 2:
12 to 30 V R [!]
500
0
10 20 30 U0 [V]
12 23
A0022583
28 Endress+Hauser
Levelflex FMP50
Endress+Hauser 29
Levelflex FMP50
K: 4-wire 90-253VAC; 4-20mA HART 90 to 253 VAC (50 to 60 Hz), overvoltage 500 Ω
category II
Polarity sensitive No
Nominal current 3.6 to 22 mA, the start-up current for multidrop mode can be parametrized (is
set to 3.6 mA on delivery)
PROFIBUS PA
Nominal current 14 mA
30 Endress+Hauser
Levelflex FMP50
FOUNDATION Fieldbus
FISCO
Ui 17.5 V
Ii 550 mA
Pi 5.5 W
Ci 5 nF
Li 10 μH
M: "Prepared for display FHX50 + M16 cable gland, custom connection" M12 cable gland
N: "Prepared for display FHX50 + NPT1/2 thread, custom connection" Thread NPT1/2
Endress+Hauser 31
Levelflex FMP50
HART
• A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended if using the HART protocol. Observe grounding concept of the
plant.
• For 4-wire devices: Standard device cable is sufficient for the power line.
PROFIBUS
Use a twisted, screened two-wire cable, preferably cable type A.
For further information on the cable specifications, see Operating Instructions BA00034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning", PNO Guideline 2.092
"PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
FOUNDATION Fieldbus
Endress+Hauser recommends using twisted, shielded two-wire cables.
For further information on the cable specifications, see Operating Instructions BA00013S
"FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).
Overvoltage protection If the measuring device is used for level measurement in flammable liquids which requires the use of
overvoltage protection according to DIN EN 60079-14, standard for
test procedures 60060-1 (10 kA, pulse 8/20 μs), an overvoltage protection module has to be
installed.
Technical data
32 Endress+Hauser
Levelflex FMP50
Performance characteristics
Reference operating • Temperature = +24 °C (+75 °F) ±5 °C (±9 °F)
conditions • Pressure = 960 mbar abs. (14 psia) ±100 mbar (±1.45 psi)
• Humidity = 60 % ±15 %
• Reflection factor ≥ 0.8 (metal plate for rod and rope probe with min. 1 m (40 in) diameter)
• Flange for rod or rope probe ≥ 300 mm (12 in) diameter
• Distance to obstacles ≥ 1 m (40 in)
Reference accuracy Typical data under reference operating conditions: DIN EN IEC 61298-2 / DIN EN IEC 60770-1;
percentage values in relation to the span.
Differing from this, the following measured error applies in the area of the lower probe end:
D
80 (3.15)
60 (2.36) DC = 2
40 (1.57)
DC = 80
20 (0.79)
0
-20 (-0.79)
-40 (-1.57)
-60 (-2.36)
-80 (-3.15)
0
50 (1.97)
100 (3.94)
150 (5.91)
250 (9.84)
300 (11.8)
A
20 (0.79)
200 (7.87)
40 (1.57)
80 (3.15)
A0021480
21 Measured error at the probe end for rod and coax probes
A Distance from the probe end [mm(in)]
D Measured error: Sum of non-linearity, non-repeatability and hysteresis
Endress+Hauser 33
Levelflex FMP50
D
80 (3.15)
60 (2.36) DC = 80
40 (1.57)
20 (0.79)
0
-20 (-0.79)
-40 (-1.57)
-60 (-2.36)
-80 (-3.15)
50 (1.97)
100 (3.94)
150 (5.91)
200 (7.87)
300 (11.8)
A
0
20 (0.79)
250 (9.84)
A0021482
If the DC value is less than 7 in the case of rope probes, measurement is not possible in the area
of the tensioning weight (0 to 250 mm from the probe end), (lower blocking distance).
The following measured error applies in the area of the upper probe end:
R
D
40 (1.57)
30 (1.18) DC = 2
DC = 80
10 (0.39)
2 (0.08)
0 (0)
- 2 (- 0.08)
- 10 (-0.39)
- 30 (- 1.18)
- 40 (- 1.57)
Resolution • Digital: 1 mm
• Analog: 1 μA
34 Endress+Hauser
Levelflex FMP50
Response time The response time can be configured. The following step response times (in accordance with DIN EN
IEC 61298-2 / DIN EN IEC 60770-1) 1) are when damping is switched off:
Level measurement
Influence of ambient The measurements are performed according to DIN EN IEC 61298-3 / DIN EN IEC 60770-1
temperature • Digital (HART, PROFIBUS PA, FOUNDATION Fieldbus): average TK = 0.6 mm/10 K
For devices with a remote sensor, 2) there is an additional offset error of
±0.3 mm/10K (±0.01 in/10K) per 1 m (3.3 ft) of the remote cable.
• Analog (current output):
• Zero point (4 mA): average TK = 0.02 %/10 K
• Span (20 mA): average TK = 0.05 %/10 K
1) According to DIN EN IEC 61298-2 / DIN EN IEC 60770-1, the step response time is the time that elapses after an abrupt change in the input
signal until the change in the output signal has adopted 90% of the steady-state value for the first time.
2) Product structure: feature 600, version MB, MC or MD)
Endress+Hauser 35
Levelflex FMP50
Installation
Installation conditions Suitable mounting position
1 2 3
A 4
A0012606
36 Endress+Hauser
Levelflex FMP50
Additional conditions
• When mounting outdoors, a weather protection cover (1) can be used to protect the device against
extreme weather conditions.
• In metallic vessels, preferably do not mount the probe in the center of the vessel (2), as this would
lead to increased interference echoes.
If a central mounting position cannot be avoided, it is essential to perform interference echo
suppression (mapping) after commissioning the device.
• Do not mount the probe in the filling curtain (3).
• Avoid buckling the rope probe during installation or operation (e.g. as a result of product
movement against silo wall) by selecting a suitable mounting location.
In the case of freely suspended rope probes (probe end not fixed at the bottom), the distance
between the probe rope and internal fittings, which can change due to the movement of the
product, must never be less than 300 mm (12 in). Occasional contact between the probe end
weight and the cone of the vessel, however, does not influence the measurement provided that
the dielectric constant is at least DC = 1.8.
When the housing is mounted in a recess (e.g. in a concrete ceiling), observe a minimum
distance of 100 mm (4 in) between the cover of the connection compartment/electronics
compartment and the wall. Otherwise the connection compartment/electronics compartment
will not be accessible after installation.
Endress+Hauser 37
Levelflex FMP50
A B
6 Nm 6 Nm
(4.42 lbf ft) (4.42 lbf ft)
6 Nm 6 Nm
(4.42 lbf ft) (4.42 lbf ft)
A0014794
38 Endress+Hauser
Levelflex FMP50
FMP50
Rope 4mm (1/6") 316
2 kN
FMP50
Rod 8mm (1/3") 316L
10 Nm
With:
cw: coefficient of friction
ρ [kg/m3]: density of the medium
v [m/s]: flow velocity of the medium, perpendicular to the probe rod
d [m]: diameter of the probe rod
L [m]: level
LN [m]: probe length
Sample calculation
Coefficient of friction cw 0.9 (assuming turbulent flow - high Reynolds number)
d
A0014175
14.0
12.0
10.0
8.0
6.0
4.0
2.0
0.0 v=0.5m/s
0.4 0.8 1.2 1.6 2 2.4 2.8 3.2 3.6 4 v=0.7m/s
Probe length [LN] in meters v=1.0m/s
A0014182-EN
Endress+Hauser 39
Levelflex FMP50
Threaded connection
A0015121
Seal
The thread and the type of seal comply with DIN 3852 Part 1, screwed plug, form A.
The following types of sealing ring can be used:
For thread G3/4": According to DIN 7603 with dimensions 27 mm × 32 mm
Use a sealing ring according to this standard in form A, C or D and of a material that offers
appropriate resistance for the application.
Refer to the dimensional drawing for the length of the screwed plug:
Nozzle mounting
!150 (6)
H
ø !150 (6)
A0015122
H Length of the centering rod or the rigid part of the rope probe
40 Endress+Hauser
Levelflex FMP50
1
3
2
A0014199
Endress+Hauser 41
Levelflex FMP50
B
2
A
A0012609
• The end of the rope probe must be secured (fixed down) under the following conditions:
If the probe would otherwise temporarily come into contact with the vessel wall, the cone, internal
fittings/beams or another part of the installation
• A female thread is provided in the probe weight to secure the end of the probe:
Rope 4 mm (1/6"), 316: M 14
• When fixed down, the end of the probe must be either reliably grounded or reliably insulated. Use
an insulated fastening kit if it is not otherwise possible to secure the probe with a reliably
insulated connection.
42 Endress+Hauser
Levelflex FMP50
øa
øb
!50 (1.97)
3
mm (in)
A0014127
1 Probe rod
2 Sleeve with narrow bore to ensure electrical contact between the sleeve and the rod.
3 Short metal pipe, e.g. welded in place
NOTICE
Poor grounding of the probe end may cause incorrect measurements.
‣ Use a sleeve with a narrow bore to ensure good electrical contact between the sleeve and the
probe rod.
NOTICE
Welding can damage the main electronics module.
‣ Before welding: Ground the probe rod and remove the electronics.
Endress+Hauser 43
Levelflex FMP50
A B
1 2
(3.94)
!100
3
A0014129
44 Endress+Hauser
Levelflex FMP50
Underground tanks
A0014142
In the case of nozzles with large diameters, use FMP51 with a coax probe to avoid reflections at the
nozzle wall.
Endress+Hauser 45
Levelflex FMP50
Mounting at an angle
LN
!
A0014145
46 Endress+Hauser
Levelflex FMP50
Non-metal vessels
A0012527
1 Non-metal vessel
2 Metal sheet or metal flange
To ensure good measurement results when mounting on non-metal vessels, at the process
connection mount a metal sheet with a diameter of at least 200 mm (8 in) at a right angle to the
probe.
Endress+Hauser 47
Levelflex FMP50
Plastic and glass vessels: Mounting the probe on the outside wall
In the case of plastic and glass vessels, the probe can also be mounted on the outside wall under
certain conditions.
1
3
A0014150
Requirements
• Dielectric constant of the medium: εr > 7.
• Non-conductive vessel wall.
• Maximum wall thickness (a):
• Plastic: < 15 mm (0.6 in)
• Glass: < 10 mm (0.4 in)
• No metal reinforcements on the vessel.
Note the following when mounting the device:
• Mount the probe directly on the vessel wall without any space between the wall and probe.
• To prevent any influence on the measurement, fit a plastic half pipe with a diameter of at least
200 mm (8 in), or a similar protective unit, on the probe.
• For vessel diameters less than 300 mm (12 in):
On the opposite side of the vessel, fit a grounding plate that is conductively connected to the
process connection and covers around half of the vessel's circumference.
• For vessel diameters of 300 mm (12 in) and higher:
At the process connection, fit a metal plate with a diameter of at least 200 mm (8 in) at a right
angle to the probe (see above).
48 Endress+Hauser
Levelflex FMP50
2 3
1
MAX MAX
A0014653
Endress+Hauser 49
Levelflex FMP50
Local display –20 to +70 °C (–4 to +158 °F), the readability of the display may be impaired at
temperatures outside the temperature range.
1) This range applies if the option JN "Transmitter ambient temperature –50 °C (–58 °F)" has been selected in
order code 580 "Test, certificate". If the temperature is permanently below –40 °C (–40 °F), the chance of
failure increases.
Ambient temperature limits The following diagrams only consider functional aspects. Additional restrictions may apply for
certified device versions. See the separate Safety Instructions for more information.
50 Endress+Hauser
Levelflex FMP50
In the event of temperature (Tp) at the process connection, the permitted ambient temperature (Ta)
is reduced as indicated in the following diagram (temperature derating):
[°C] ([°F])Ta
Ta
+80(+176)
Tp
A: 4...20 mA HART
-20(-4) Tp
-20 +80 [°C]
(-4) (+176) ([°F])
[°C] ([°F])Ta
GT20: +79 (+174) GT20
GT19: +74 (+165)
4...20 mA HART GT19: +73(+163)
C:
4...20 mA
K: 90...253 VAC
L: 10.4...48 VDC
-20(-4) Tp
-20 +74 +80 [°C]
(-4) (+165) (+176) ([°F])
[°C] ([°F])Ta
+76 (+169)
GT20: +76(+168)
G 1: PROFIBUS PA
FOUNDATION Fieldbus
-20(-4) Tp
-20 +76 +80 [°C]
(-4) (+169) (+176) ([°F])
[°C] ([°F])Ta
+74 (+164)
GT20: +73(+163)
2
G : PROFIBUS PA
FOUNDATION Fieldbus
Switch output
-20(-4) Tp
-20 +74 +80 [°C]
(-4) (+164) (+176) ([°F])
A0013944
1) In the case of PROFIBUS PA and FOUNDATION Fieldbus, the temperature derating depends on whether
the switch output (terminals 3 and 4) is used (G2) or not (G1).
Endress+Hauser 51
Levelflex FMP50
Storage temperature • Permitted storage temperature: –40 to +80 °C (–40 to +176 °F)
• Use original packaging.
Cleaning the probe Dirt or buildup may form on the probe depending on the application. A thin, even layer has little
impact on the measurement. Thick layers can dampen the signal and then reduce the measuring
range. Very uneven deposit formation, e.g. caking due to crystallization, can result in incorrect
measurements. In such cases, we recommend the use of a non-contact measuring principle, or a
regular inspection of the probe for contamination.
Electromagnetic Electromagnetic compatibility in accordance with all of the relevant requirements outlined in the EN
compatibility (EMC) 61326 series and NAMUR Recommendation EMC (NE 21). For details, refer to the Declaration of
Conformity.
Download at www.endress.com.
52 Endress+Hauser
Levelflex FMP50
Process
Process temperature range The maximum temperature permitted at the process connection is determined by the O-ring version
ordered:
FMP50 FKM (Viton GLT) –20 to +80 °C (–4 to 176 °F) FDA
Extension of the rope probes Elongation from temperature increase from 30 °C (86 °F) to 80 °C (176 °F): 1 mm / m rope length
due to temperature
Endress+Hauser 53
Levelflex FMP50
Mechanical construction
Dimensions Dimensions of the electronics housing
R110
99 (3.9)*
78 (3.07) 90 (3.54)
)
.17
6 (4
144 (5.67)
ø106 (4.17)
ø10
113.5 (4.47)
A0011346
R110 98 (3.86)*
78 (3.07) 90 (3.54)
07)
(4.
ø112 (4.41)
145.5 (5.73)
3.5
141.5 (5.57)
ø108.5 (4.27)
ø10
61 (2.4)
A0020751
54 Endress+Hauser
Levelflex FMP50
A B
ø42...60
(1.65...2.36)
52 (2)
122 (4.8) 127...140
161 (6.34) (5...5.51)
162...175
(6.38...6.89)
(3.4)
(2.8)
86
70
A0014793
With "remote sensor" device versions (see feature 060 in the product structure), the mounting
bracket is included in the scope of delivery. However, it can also be ordered separately as an
accessory (order number: 71102216).
122(4.8)
(2.05)
52
15 (0.6)
ø10
(0. .2
4)
(2.4)
61
43 (1.7)
ø82.5
(3.25)
A0023856
30 Connection piece for remote probe; length of connecting cable: as per order. Unit of measurement mm (in)
Endress+Hauser 55
Levelflex FMP50
(0.98)
69 (2.72)
25
36 mm
R
G¾
NPT¾
B C
7 mm 7 mm
ø4 (0.16)
LN
150 (5.91)
29.5 (1.16)
ø8 (0.31)
M14
ø22 (0.87)
A0012644
56 Endress+Hauser
Levelflex FMP50
Shortening probes If necessary, probes can be shortened by observing the following instructions:
Endress+Hauser 57
Levelflex FMP50
Weight Housing
Part Weight
FMP50
Part Weight Part Weight
Sensor Approx. 0.25 kg Rope probe 4 mm Approx. 0.1 kg/m probe length
58 Endress+Hauser
Levelflex FMP50
2.2
5.2
6
5.1
7
4 9 8
A0013788
1 Housing PBT
5.1 Dummy plug, coupling, adapter or connector • Dummy plug, depending on device version:
(depending on device version) • PE
• PBT-GF
• Coupling, depending on device version:
• Brass (CuZn), nickel-plated
• PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
• Connector M12: brass, nickel-plated 1)
• Connector 7/8": 316 (1.4401) 2)
5.2 Dummy plug, coupling or adapter (depending on • Dummy plug, depending on device version:
device version) • PE
• PBT-GF
• Steel, galvanized
• Coupling, depending on device version:
• Brass (CuZn), nickel-plated
• PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
6 Dummy plug or M12 socket (depending on device • Dummy plug: brass (CuZn), nickel-plated
version) • M12 socket: GD-Zn, nickel-plated
Endress+Hauser 59
Levelflex FMP50
2.2
5.2
6
5.1
7
4 3 9 8
A0036037
2.1 Electronics compartment cover, RAL 7035 (gray) • Cover: AlSi10Mg(<0.1% Cu)
• Window: glass
• Cover seal: NBR
• Window seal: NBR
• Thread coating: graphite-based lubricant varnish
2.2 Connection compartment cover, RAL 7035 (gray) • Cover: AlSi10Mg(<0.1% Cu)
• Cover seal: NBR
• Thread coating: graphite-based lubricant varnish
5.1 Dummy plug, coupling, adapter or connector • Dummy plug, depending on device version:
(depending on device version) • PE
• PBT-GF
• Coupling, depending on device version:
• Brass (CuZn), nickel-plated
• PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
• M12 plug: brass, nickel-plated 1)
• 7/8" plug: 316 (1.4401) 2)
5.2 Dummy plug, coupling or adapter (depending on • Dummy plug, depending on device version:
device version) • PE
• PBT-GF
• Steel, galvanized
• Coupling, depending on device version:
• Brass (CuZn), nickel-plated
• PA
• Adapter: 316L (1.4404/1.4435)
• Seal: EPDM
6 Dummy plug or M12 socket (depending on device • Dummy plug: brass (CuZn), nickel-plated
version) • M12 socket: GD-Zn, nickel-plated
60 Endress+Hauser
Levelflex FMP50
1) In the version with the M12 plug, the seal material is Viton (different from standard).
2) In the version with the 7/8" plug, the seal material is NBR (different from standard).
Endress+Hauser 61
Levelflex FMP50
1 1 PPS-GF40
2 316L (1.4404)
2 3 PPS-GF40
3
A0013834
62 Endress+Hauser
Levelflex FMP50
1 316L (1.4404)
2 316 (1.4401)
3 Setscrew: A4-70
1
1 4 Bracing screw: A2-70
2
4
A0036583 A0036584
Endress+Hauser 63
Levelflex FMP50
12
12
11
10
A0015143
Screws/nuts A4-70
64 Endress+Hauser
Levelflex FMP50
4 3
A0021722
1 Cable FRNC
Screw A4-70
Endress+Hauser 65
Levelflex FMP50
Materials: Weather
protection cover 1
6
4
5
A0015473
5 Ground terminal
• Screw: A4
• Spring washer: A4
• Clamp: 316L (1.4404)
• Bracket: 316L (1.4404)
6 • Washer: A4
• Cylinder screw: A4-70
66 Endress+Hauser
Levelflex FMP50
Operability
Operating concept Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Operating languages
• English
• Deutsch
• Français
• Español
• Italiano
• Nederlands
• Portuguesa
• Polski
• русский язык (Russian)
• Svenska
• Türkçe
• 中文 (Chinese)
• 日本語 (Japanese)
• 한국어 (Korean)
• Bahasa Indonesia
• tiếng Việt (Vietnamese)
• čeština (Czech)
Feature 500 of the product structure determines which of these languages is preset on delivery.
Endress+Hauser 67
Levelflex FMP50
A0036312 A0036313
Format for displaying measured variables and status variables can be individually configured
Permitted ambient temperature for the display: –20 to +70 °C (–4 to +158 °F)
The readability of the display may be impaired at temperatures outside the temperature
range.
Operating local operation with 3 push buttons (, , ) external operation via touch control; 3
elements optical keys: , ,
A0036314
68 Endress+Hauser
Levelflex FMP50
2
A0036790
This operation option is only available for devices with Bluetooth module. There are the following
options:
• The device has been ordered with a Bluetooth module:
Feature 610 "Accessory Mounted", option NF "Bluetooth"
• The Bluetooth module has been ordered as an accessory (ordering number: 71377355) and has
been mounted. See Special Documentation SD02252F.
1 2 3
A0034939
Endress+Hauser 69
Levelflex FMP50
2 3 6 8
1 4 5 7
A0036169
2
3
1
PROFIBUS DP
PROFIBUS PA
T
4 4 4
A0036301
70 Endress+Hauser
Levelflex FMP50
IN
. -
FF-HSE BT
1
FF-H1 SB 2
PS BT
LD 4
3
BT
PS
FF-H1
BT
1
2
A0017188
IN Industrial network
SB Safety Barrier
BT Bus Terminator
Endress+Hauser 71
Levelflex FMP50
1
A0032466
72 Endress+Hauser
Levelflex FMP50
Integration in tank gauging The Endress+Hauser Tank Side Monitor NRF81 provides integrated communications for sites with
system multiple tanks, each with one or more sensors on the tank, such as radar, spot or average
temperature, capacitive probe for water detection and/or pressure sensors. Multiple protocols out of
the Tank Side Monitor guarantee connectivity to nearly any of the existing industry standard tank
gauging protocols. Optional connectivity of analog 4...20 mA sensors, digital I/O and analog output
simplify full tank sensor integration. Use of the proven concept of the intrinsically safe HART bus for
all on-tank sensors yields extremely low wiring costs, while at the same time providing maximum
safety, reliability and data availability.
1 2 3
4 5
8 6
7
A0016590
Endress+Hauser 73
Levelflex FMP50
SupplyCare inventory SupplyCare is a web-based operating program for coordinating the flow of material and information
management software along the supply chain. SupplyCare provides a comprehensive overview of the levels of
geographically distributed tanks and silos, for instance, providing complete transparency over the
current inventory situation, regardless of time and location.
Based on the measuring and transmission technology installed onsite, the current inventory data are
collected and sent to SupplyCare. Critical levels are clearly indicated and calculated forecasts provide
additional security for material requirements planning.
The main functions of SupplyCare:
Inventory visualization
SupplyCare determines the inventory levels in tanks and silos at regular intervals. It displays current
and historical inventory data and calculated forecasts of future demand. The overview page can be
configured to suit the user's preferences.
Master data management
With SupplyCare you can create and manage the master data for locations, companies, tanks,
products and users, as well as user authorization.
Report Configurator
The Report Configurator can be used to create personalized reports quickly and easily. The reports
can be saved in a variety of formats, such as Excel, PDF, CSV and XML. The reports can be
transmitted in many ways, such as by http, ftp or e-mail.
Event management
Events, such as when levels drop below the safety stock level or plan points, are indicated by the
software. In addition, SupplyCare can also notify pre-defined users by e-mail.
Alarms
If technical problems occur, e.g. connection issues, alarms are triggered and alarm e-mails are sent to
the System Administrator and the Local System Administrator.
Delivery planning
The integrated delivery planning function automatically generates an order proposal if a pre-set
minimum inventory level is undershot. Scheduled deliveries and disposals are monitored
continuously by SupplyCare. SupplyCare notifies the user if scheduled deliveries and disposals are not
going to be met as planned.
Analysis
In the Analysis module, the most important indicators for the inflow and outflow of the individual
tanks are calculated and displayed as data and charts. Key indicators of material management are
automatically calculated and form the basis for optimizing the delivery and storage process.
Geographical visualization
All the tanks and the tank inventories are represented graphically on a map (based on Google Maps).
The tanks and inventory situations can be filtered by tank group, product, supplier or location.
Multi-language support
The multi-language user interface supports 9 languages, thereby enabling global collaboration on a
single platform. The language and settings are recognized automatically using the browser settings.
SupplyCare Enterprise
SupplyCare Enterprise runs by default as a service under Microsoft Windows on an application server
in an Apache Tomcat environment. The operators and administrators operate the application via a
Web browser from their workstations.
74 Endress+Hauser
Levelflex FMP50
2
3
10
5 7 8
9
.
A0034288
Endress+Hauser 75
Levelflex FMP50
1
3
WWW
4
10
5 7 8
9
.
A0034289
With SupplyCare Hosting, users do not need to make the initial software purchase or install and run
the IT infrastructure needed. Endress+Hauser constantly update SupplyCare Hosting and enhance
the capability of the software in conjunction with the customer. The hosted version of SupplyCare is
thus always up-to-date and can be customized to meet different customer requirements. Other
services are also offered in addition to the IT infrastructure and the software that is installed in a
secure, redundant Endress+Hauser data center. These services include defined availability of the
global Endress+Hauser Service and Support Organization and defined response times in a service
event.
76 Endress+Hauser
Levelflex FMP50
CE mark The measuring system meets the legal requirements of the applicable EU Directives. These are listed
in the corresponding EU Declaration of Conformity along with the standards applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
RoHS The measuring system complies with the substance restrictions of the Restriction on Hazardous
Substances Directive 2011/65/EU (RoHS 2).
RCM-Tick marking The supplied product or measuring system meets the ACMA (Australian Communications and Media
Authority) requirements for network integrity, interoperability, performance characteristics as well
as health and safety regulations. Here, especially the regulatory arrangements for electromagnetic
compatibility are met. The products are labelled with the RCM- Tick marking on the name plate.
A0029561
Ex approval The devices are certified for use in hazardous areas and the relevant safety instructions are provided
in the separate "Safety Instructions" (XA, ZD) document. Reference is made to this document on the
nameplate.
The separate "Safety Instructions" documentation (XA) containing all the relevant explosion
protection data is available from your Endress+Hauser sales organization.
Dual seal according to The devices have been designed according to ANSI/ISA 12.27.01 as dual seal devices, allowing the
ANSI/ISA 12.27.01 user to waive the use and save the cost of installing external secondary process seals in the conduit
as required by the process sealing sections of ANSI/NFPA 70 (NEC) and CSA 22.1 (CEC) These
instruments comply with the North-American installation practice and provide a very safe and cost-
saving installation for pressurized applications with hazardous fluids.
Further information can be found in the Safety Instructions (XA) of the relevant devices.
Functional safety Use for level monitoring (MIN, MAX, range) up to SIL 3 (homogeneous redundancy), independently
evaluated by TÜV Rheinland in accordance with IEC 61508, refer to the "Functional Safety Manual"
SD00326F for more information.
Pressure equipment with Pressure instruments with a flange and threaded boss that do not have a pressurized housing do not
allowable pressure fall within the scope of the Pressure Equipment Directive, irrespective of the maximum allowable
≤ 200 bar (2 900 psi) pressure.
Reasons:
According to Article 2, point 5 of EU Directive 2014/68/EU, pressure accessories are defined as
"devices with an operational function and having pressure-bearing housings".
If a pressure instrument does not have a pressure-bearing housing (no identifiable pressure chamber
of its own), there is no pressure accessory present within the meaning of the Directive.
Radio approval Satisfies "Part 15" of the FCC rules for an unintentional radiator. All probes meet the requirements
for a Class A digital device.
In addition, coax probes and all probes in metal vessels meet the requirements for a Class B digital
device.
Endress+Hauser 77
Levelflex FMP50
Test reports, declarations and inspection certificates are available in electronic format in the
W@M Device Viewer:
Enter the serial number that appears on the device (www.endress.com/deviceviewer)
This concerns the options for the following order codes:
• 550 "Calibration"
• 580 "Test, certificate"
Hard-copy product Hard-copy versions of the test reports, declarations and inspection certificates can also be order via
documentation order code 570 "Service", option I7 "Hard-copy product documentation". The documents are then
supplied with the product.
78 Endress+Hauser
Levelflex FMP50
Endress+Hauser 79
Levelflex FMP50
Ordering information
Ordering information Detailed ordering information is available for your nearest sales organization
www.addresses.endress.com or in the Product Configurator under www.endress.com :
1. Click Corporate
2. Select the country
3. Click Products
4. Select the product using the filters and search field
5. Open the product page
The Configuration button to the right of the product image opens the Product Configurator.
80 Endress+Hauser
Levelflex FMP50
3-point linearity protocol The following points must be considered if option F3 (3-point linearity protocol) was selected in
feature 550 ("Calibration").
The 3 points of the linearity protocol are defined as follows, depending on the selected probe:
A
1 1
2 2
LN
B
3 3
C
A0021843
Position of 1st measuring A =350 mm (13.8 in) A =350 mm (13.8 in) A =350 mm (13.8 in)
point
Position of 2nd measuring In the middle between the 1st and In the middle between the 1st and 3rd In the middle between the 1st and 3rd
point 3rd measuring point measuring point measuring point
Position of 3rd measuring C = 250 mm (9.84 in) C = 500 mm (19.7 in) A+B = 5 500 mm (217 in)
point
Minimum measuring range B ≥ 400 mm (15.7 in) B ≥ 400 mm (15.7 in) B ≥ 400 mm (15.7 in)
Minimum probe length LN ≥ 1 000 mm (39.4 in) LN ≥ 1 250 mm (49.2 in) LN ≥ 1 250 mm (49.2 in)
• In the case of rod and rope probes, the linearity check is performed with the entire device.
• The linearity check is performed under reference operating conditions.
Endress+Hauser 81
Levelflex FMP50
5-point linearity protocol The following points must be considered if option F4 (5-point linearity protocol) was selected in
feature 550 ("Calibration").
The 5 points of the linearity protocol are evenly distributed over the measuring range (0% - 100%).
Empty calibration (E) and Full calibration (F) must be specified in order to define the measuring
range 3).
The following restrictions must be considered when selecting E and F:
A
E
B
F
C
A0014673
• In the case of rod and rope probes, the linearity check is performed with the entire device.
• The linearity check is performed under reference operating conditions.
The selected values for Empty calibration and Full calibration are only used to create the
linearity protocol. Afterwards, the values are reset to the default values specific for the probe. If
values other than the default values are required, they must be ordered as a customized
parameterization → 83.
3) If (E) and (F) are not specified, probe-dependent default values will be used instead.
82 Endress+Hauser
Levelflex FMP50
Customer-specific If the option IJ: "Customized parameterization HART", IK "Customized parameterization PA" or IL
configuration "Customized parameterization FF" has been selected in feature 570 "Service", presettings that differ
from the default settings can be selected for the following parameters:
Designation in the Electronic The first 32 characters of the measuring point designation
Name Plate (ENP)
Designation on the display The first 12 characters of the measuring point designation
module
Endress+Hauser 83
Levelflex FMP50
Application packages
Heartbeat Diagnostics Availability
Available in all device versions.
Function
• Continuous self-monitoring of the device.
• Diagnostic messages output to
• the local display.
• an asset management system (e.g. FieldCare/DeviceCare).
• an automation system (e.g. PLC).
Advantages
• Device condition information is available immediately and processed in time.
• The status signals are classified in accordance with VDI/VDE 2650 and NAMUR recommendation
NE 107 and contain information about the cause of the error and remedial action.
Detailed description
See the "Diagnostics and troubleshooting" section of the Operating Instructions for the device.
84 Endress+Hauser
Levelflex FMP50
Advantages
• No onsite presence is required to use the function.
• The DTM 4) triggers verification in the device and interprets the results. No specific knowledge is
required on the part of the user.
• The verification report can be used to prove quality measures to a third party.
• Heartbeat Verification can replace other maintenance tasks (e.g. periodic check) or extend the
test intervals.
SIL/WHG-locked devices 5)
• The Heartbeat Verification module contains a wizard for the proof test which must be performed
at appropriate intervals for the following applications:
• SIL (IEC61508/IEC61511)
• WHG (German Water Resources Act)
• To perform a proof test, the device must be locked (SIL/WHG locking).
• The wizard can be used via FieldCare, DeviceCare or a DTM-based process control system.
In the case of SIL-locked and WHG-locked devices, it is not possible to perform verification
without taking additional measures (e.g. bridging the output current) because the output
current must be simulated (Increased safety mode) or the level must be approached manually
(Expert mode) during subsequent re-locking (SIL/WHG locking).
Detailed description
SD01872F
4) DTM: Device Type Manager; controls device operation via DeviceCare, FieldCare or a DTM-based process control system.
5) Only relevant for devices with SIL or WHG approval: order code 590 ("Additional approval"), option LA ("SIL") or LC ("WHG").
Endress+Hauser 85
Levelflex FMP50
Function
• In addition to the verification parameters, the corresponding parameter values are also logged.
• Existing measured variables, such as the echo amplitude, are used in the Foam detection and
Build-up detection wizards.
In the Levelflex FMP5x, the Foam detection and Build-up detection wizards cannot be used
together.
Advantages
• Early detection of changes (trends) to ensure plant availability and product quality.
• Use of information for the proactive planning of measures (e.g. cleaning/maintenance).
• Identification of undesirable process conditions as the basis to optimizing the facility and the
processes.
• Automated control of measures to remove foam or buildup.
Detailed description
SD01872F
86 Endress+Hauser
Levelflex FMP50
Accessories
Device-specific accessories Weather protection cover
Accessory Description
222 (8.74)
A0015466
4)
38
35°
65°
(6.1
15 6
A0015472
Enclosed",
The weather protection cover can be ordered together with the device (product structure, feature 620 "Accessory
option PB "Weather Protection Cover").
Alternatively, it can be separately ordered as an accessory; order code 71162242.
Endress+Hauser 87
Levelflex FMP50
Accessories Description
ø42...60
(1.65...2.36)
52 (2)
122 (4.8) 127...140
161 (6.34) (5...5.51)
162...175
(6.38...6.89)
(3.4)
(2.8)
86
70
A0014793
With "remote sensor" device versions (see feature 060 in the product structure), the mounting bracket is included in
the scope of delivery. However, it can also be ordered separately as an accessory (order number: 71102216).
88 Endress+Hauser
Levelflex FMP50
Accessories Description
D
A0013586
The mounting kit can also be ordered directly with the device (Levelflex
product structure, feature 620 "Accessory enclosed", version PG "mounting kit,
insulated, rope").
Endress+Hauser 89
Levelflex FMP50
Centering star
Accessories Description
10 (0.39)
• 16.4 mm (0.65 in)
• 37 mm (1.46 in)
suitable for
FMP50
A: ø16.4 (0.65)
B: ø37 (1.46)
A0014577
The centering star is suitable for probes with a rod diameter of 8 mm (0.3 in),
12 mm (0.47 in) and 16 mm (0.63 in) (including coated rod probes) and can be
used in pipes from DN40 to DN50. See also Operating Instructions
BA00378F/00/A2.
• Material: PFA
• Permitted process temperature range: –200 to +250 °C (–328 to +482 °F)
• Order number
• Probe 8 mm (0.3 in) : 71162453
• Probe 12 mm (0.47 in): 71157270
• Probe 16 mm (0.63 in): 71069065
90 Endress+Hauser
Levelflex FMP50
Accessories Description
2.
1.
4.
3.
A0019128
• Material:
• Plastic PBT
• 316L/1.4404
• Aluminum
• Degree of protection: IP68 / NEMA 6P and IP66 / NEMA 4x
• Suitable for display modules:
• SD02 (push buttons)
• SD03 (touch control)
• Connecting cable:
• Cable supplied with device up to 30 m (98 ft)
• Standard cable supplied by customer up to 60 m (196 ft)
• Ambient temperature range: –40 to 80 °C (–40 to 176 °F)
• Ambient temperature range (option): –50 to 80 °C (–58 to 176 °F) 1)
• IfL, the remote display should be used, order the device version "Prepared for display FHX50" (feature 030, version
M or N). For the FHX50, you must select option A: "Prepared for display FHX50" under feature 050 "Measuring
device version".
• If the device version "Prepared for display FHX50" was not originally ordered and a FHX50 display is to be
retrofitted, you must select version B "Not prepared for display FHX50" under feature 050: "Measuring device
version" when ordering the FHX50. In this case, a retrofit kit for the device is supplied with the FHX50. The kit
can be used to prepare the device so that the FHX50 can be used.
FHX50
Use of the FHX50 may be restricted for transmitters with an approval. A device can only be retrofitted with the
if the option L, M or N ("Prepared for FHX50") is listed under Basic specifications, item 4 "Display, operation"
in the Safety Instructions (XA) for the device.
Also pay attention to the Safety Instructions (XA) of the FHX50.
Endress+Hauser 91
Levelflex FMP50
Overvoltage protection
Accessories Description
A0021734
Technical data
• Resistance per channel: 2 × 0.5 Ωmax
• Threshold DC voltage: 400 to 700 V
• Threshold surge voltage: < 800 V
• Capacitance at 1 MHz: < 1.5 pF
• Nominal leakage current (8/20 μs): 10 kA
• Suitable for conductor cross-sections: 0.2 to 2.5 mm2 (24 to 14 AWG)
92 Endress+Hauser
Levelflex FMP50
Accessory Description
Bluetooth module
A0036493
When using the Bluetooth module the minimum supply voltage increases by up to 3 V.
Ordering with device
The Bluetooth module is preferably ordered with the device. See product structure, feature 610 "Accessory
Mounted", option NF "Bluetooth". A separate order is only necessary in case of retrofitting.
Endress+Hauser 93
Levelflex FMP50
Commubox FXA291
Connects Endress+Hauser field devices with a CDI interface (= Endress+Hauser Common Data
Interface) and the USB port of a computer or laptop
Order number: 51516983
For details, see "Technical Information" TI00405C
Fieldgate FXA42
Fieldgates enable communication between connected 4 to 20 mA, Modbus RS485 and Modbus TCP
devices and SupplyCare Hosting or SupplyCare Enterprise. The signals are transmitted either via
Ethernet TCP/IP, WLAN or mobile communications (UMTS). Advanced automation capabilities are
available, such as an integrated Web-PLC, OpenVPN and other functions.
For details, see "Technical Information" TI01297S and Operating Instructions BA01778S.
94 Endress+Hauser
Levelflex FMP50
FieldCare SFE500
FDT-based plant asset management tool
It can configure all smart field units in your system and helps you manage them. By using the status
information, it is also a simple but effective way of checking their status and condition.
Technical Information TI00028S
RN221N
Active barrier with power supply for safe separation of 4 to 20 mA standard signal circuits. Offers
bidirectional HART transmission.
Technical Information TI00073R and Operating Instructions BA00202R
RN221
Supply unit for powering two 2-wire measuring devices solely in the non-Ex area. Bidirectional
communication is possible via the HART communication jacks.
Technical Information TI00081R and Brief Operating Instructions KA00110R
Supplementary documentation
The following documentation types are available in the Downloads section of the Endress+Hauser
website (www.endress.com/downloads):
For an overview of the scope of the associated Technical Documentation, refer to the following:
• W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from
nameplate
• Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the
2D matrix code (QR code) on the nameplate
Brief Operating Instructions Guide that takes you quickly to the 1st measured value
(KA) The Brief Operating Instructions contain all the essential information from incoming acceptance to
initial commissioning.
Safety Instructions (XA) Depending on the approval, the following Safety Instructions (XA) are supplied with the device. They
are an integral part of the Operating Instructions.
The nameplate indicates the Safety Instructions (XA) that are relevant to the device.
Endress+Hauser 95
*71488020*