30gx082 Carrier
30gx082 Carrier
30gx082 Carrier
50 Hz
N GLOBAL CHILLER
IO
S
ER
V
RY
A
IN
IM
EL
PR
The cover photograph is for illustrative purposes only and is not part of any offer for sale or contract.
3
I - INTRODUCTION
The purpose of this catalogue id to describe a set of air-cooled 30GX 182, 267 and 358 will not be proposed in heat recov-
liquid chillers, with simultaneous heating without the intention ery. These units are economized and less tolerant for opera-
to obtain a complete balance between heating and cooling tions without refrigerant liquid seal leaving AC condenser.
capacities.
The heat recovery system as described in the following pages 1.3 - Limits
is simple, easy to install and to use. It presents an economical
· Limits are dictated by system operating pressures (oil
solution compared to separate heating and cooling systems.
pressure) and especially on these flooded units, by the
This advanced product catalogue is to be used as a supple- requirement of a saturated cooler temperature above
ment to the respective 30GX catalogues (for selection and freezing. Cooler refrigerant level must always be good
installation). enough to allow a saturated suction above freeze tripping
point. This implies air cooled condenser capacity (this
refrigerant velocity) must be kept sufficient to properly
II - OPERATIONS subcool the refrigerant flow rate to allow the expansion
device to properly feed the cooler.
1.1 - General
A heat recovery system may not be confounded with a heat Control will vary condensing temperature setpoint Vs unit
pump system : capacity or will actuate condenser the 3 way water valve when
low return water temperatures to insure proper unit operations
· Heat recovery does not reverse the refrigeration cycle. It
(note that for all heat recovery units, cold water start up is out
needs permanent operation of refrigeration.
of the range for the application and usually would implies the
· Heat pump, the refrigeration cycle is reversed (usually a 4
use of such device ). For 30 GX, control have the capability to
way valve is used).
control a 0-10V actuated 3 way valve and this valve is deliv-
ered with the chiller to be connected (hydraulically & electri-
In heat recovery systems, refrigeration is the primary use and cally) as well as insulated. Its best location is near the recovery
chiller control is based on chilled water loop. Condenser heat condenser (short water loop).
can be rejected or recovered.
(It cannot be connected from factory as outside of chiller
Typical heat recovery units will have a water cooled condenser envelope).
(used to recover heat from the system) and an air cooled
condenser.
· Heat recovery capacity limits: Max cap recovered 50% of
available heat rejection when unit full load down to 20% at
1.2 - Principle of operation 30GX 082 to 328 units
unit minimum load for OAT above 15°C.
Heat recovery on 30GX is done by mean of a heat recovery · Cooler loop limits: same as standard units (brine application
condenser (two refrigerant circuits, one water circuit similar not considered).
design as flooded coolers) in serie with air cooled condensers.
(See circuit schematic for one circuit). · Heat recovery condenser loop design limits: High 55°C
leaving (but this will usually penalize unit COP compared to
The heat recovery condenser is sized to allow 50% heat
non heat recovery operation). Low 40°C entering.
recovery at full load at Eurovent condition (12/7°C & 35°C).
Temperature delta of 3 to 10 °C will be considered (2 pass
Leaving condenser water temperature is obtained by varying condensers, Higher rise may be out of minimum water
air cooled condenser capacity (fan stages & variable speed fan velocity limit).
stage) to maintain the proper saturated condensing temperature
for heat recovery. (Design value will have to be entered via Pro 1.3.1 - Outside air temperature limits:
dialogue interface). · High ambient: Max oat is reduced by 3 °C compared to std
unit (see diagram range of operation std units ) in air cooled
In addition, unit control will also manage:
mode.
· Condenser pump: it will be turned on when unit is switched · Low outside ambient option & cooler heater need to be
to recovery mode. ordered separately if needed. For low outside temperature
· A factory supplied field installed 3 way valve: (controlled by and low unit load, heat recovery capacity will be the balance
unit) bypassing the recovery condenser it will allow to run between Air cooled condensers natural convection and heat
the unit in proper range of operating conditions when low recovery condensers. This can provide low to no recovery.
condenser return water. For condenser loop freeze protection, field installed Heat
Physically heat recovery condenser will be installed: recovery condenser pipe heaters will have to cover also
· On an added chassis on one side of 30GX 080 to 162 entering water box (if no glycol used or condenser drained),
increasing unit length of 350 mm. condenser shell and opposite water box will be protected by
· In the central section of 30GX 207 to 328 (no changes in unit heaters.
overall dimensions).
Refer to dimensional drawings for more details.
4
1.3.2 - Compromise for design operating conditions
Heat recovery operation should not affect significantly unit
COP compared to regular air cooled chiller, i.e. if design is
30°C ambient, saturated condensing will be approx. 50°C, if an
heat recovery of 52°C leaving heat recovery condenser is
required, saturated condensing temperature will have to be
controlled at 57°C contributing to cooling capacity losses and
increased unit kW input. This should always be part of return
cost calculation of the installation.
HR_EWT/
1
HR_LWT 2 3 4
Condensor A
5
17
6
16 15
Condensor A
7
14
A2 A1
10
13 12
11
9
EXV 8
Legend
5
III - CHARACTERISTICS
30GX 082 092 102 112 122 132 152 162 207 227 247 298 328
Min flow open loop (1) l/s 4.0 4.0 4.0 4.9 4.9 4.9 6.4 6.4 11.0 11.0 11.0 12.2 13.4
Max operating pressure water side (2)
kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Legend
(1) Based on 0.3 m/s water velocity for closed loop & 0.9 m/s for open loop.
(2) When condenser water side in a system where by accident water can reach 100°C, a pressure safety valve must be filed installed on the circuit.
Max operating pressure refrigerant side France Germany Italy Sweden** Finland** Austria**
6
IV - DIMENSIONAL DRAWINGS
Note: Refer to the certified dimensional drawings supplied with the unit, when designing an installation.
T˚C
F
2287
30GX-082 C
30GX-092
30GX-102 30GX-152
30GX-112 30GX-162 A mm B mm C mm D mm Kg Opt 50A Opt 50B
30GX-122
30GX-132 30GX-082 3516 DN50 DN65
30GX-092 3320 2215 1745 108 3557 DN50 DN65
30GX-102 3572 DN50 DN65
80
1
2
RECOMMANDED EXTRA SPACE FOR COOLER
TUBE REMOVAL.(CAN BE LEFT OR RIGHT.)
1 1
2256
POWER SUPPLY
2 2
7
2- 30GX 207 - 247
E mm F mm Kg
PROTECTION
DN50 230 145 26
E DN65 290 180 47
DN80 310 200 57
DN100 350 225 75
DN125 400 255 101
172
water drain
T˚C
F
1774
DN
30GX-207
30GX-227
30GX-247 Opt 50A Opt 50B
A mm B mm Kg DN DN
1
1 OPERATION AND SERVICE CLEARANCES.
POWER SUPPLY
8
3- 30GX 298 - 328
PROTECTION E mm F mm Kg
T˚C
F
DN
1854
30GX-298
Opt 50A Opt 50B
30GX-328
A mm B mm Kg DN DN
1
1 OPERATION AND SERVICE CLEARANCES.
POWER SUPPLY
V - UNIT PERFORMANCES
9
Performances tables
Legend
CAP Gross cooling capacities
kW Unit kW input
HR CAP Heat recovery capacities
P Drop Condenser pressure drop
VP Drop 3 way valve pressure drop
Note
(1) Only half of fan input power is accounted, for higher outside air temperature, the second half of fan power is to be taken into account with 2.75 Kw a fan.
10
VI - START UP AND OPERATIONS VII - OPERATION PRECAUTIONS
2
ckt B ckt A
Legend
1 3 way valve
2 To supply
3 From supply
4 Recommanded pressure balance valve option 50B
11
Order No: 13006-76, 1999 07 30 preliminary version from 14th oct. 1998 bulletin- Supersedes No: NEW Manufacturer: Carrier S.A., Montluel, France.
Manufacturer reserves the right to change any product specifications without notice. Printed in the Netherlands on chlorine-free paper.