Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Multilin M60 Brochure EN 12756L LTR 202303

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

Grid Solutions

Multilin M60
Comprehensive Protection for Medium Protection and Control
to Large Motors • Enhanced thermal model with RTD and
current unbalance compensation
The MultilinTM M60 motor protection system offers comprehensive protection and control solutions for
• Stator Differential, Mechanical Jam/Stall, Short
medium to large-sized three-phase motors. The M60 includes advanced automation and communication circuit tripping, under-Current & -Power and
capabilities, extensive I/O options, and powerful fault recording features that can simplify postmortem Phase reversal
fault analysis and help minimize motor downtime.
• Two-speed motor protection and reduced
The M60 provides superior protection, control, and diagnostics that includes a proven thermal model voltage starting
with RTD and current unbalance biasing, stator differential, reverse and low forward power, external • Optional internal RTDs & external RTD module
RRTD module, two-speed motors, reduced voltage starting, and broken rotor bar detection.
• Protection and control functionality in one box,
reducing the number of devices
Key Benefits • High density inputs/outputs to support the
• Extended motor life with advanced protection and control elements including a flexible and powerful control of many switchyard assets – all from
thermal model and standard, custom, and voltage dependent overload curves one powerful device
• Integrated automation and process control functions eliminating the need for additional discrete • Integrated large, full color display, for real-time
devices visualization and control of the protected bay
• Simplified setup and configuration with EnerVista M60 Motor Settings auto-configurator
• Enhanced motor-learned data provides critical information for preventative maintenance Advanced Communications
• An integrated large, full color display, provides real-time visualization and control of the protected bay, • Support industry standard protocols with 3
via a bay mimic as well as annunciator functionality and graphical visualization of phasors independent Ethernet ports for simultaneous &
• Advanced IEC 61850 Ed. 1 and Ed. 2 certified implementation, complete settings via SCL files and dedicated connection with IEEE 1588 support
comprehensive process bus support (IEC 61850-9-2LE or IEC 61869 or IEC 61850-9-2 Hardfiber) ensures • DeviceNet and Profibus protocol support using
interoperability, device managing optimization and reduced cost of ownership D485 and P485 protocol converters
• Routable GOOSE (R-GOOSE) enables customer to send GOOSE messages beyond the substation, • IEC 61850-9-2LE/IEC 61869 networked or
which enables WAPC and more cost effective communication architectures for wide area applications IEC61850-9-2 Hardfiber process bus support
• Increased network availability via failover time reduced to zero through IEC® 62439-3 “PRP” support
• Supports IEEE C37.111-1999/2013, IEC 60255-24 Ed 2.0 COMTRADE standard Cyber Security
• CyberSentry™ provides high-end cyber security
Applications aligned to industry standards and services
• Protection & control of most popular construction type medium to large three-phase induction motors (NERC® CIP, AAA, Radius, RBAC, Syslog)

• Protection of medium to large synchronous motors when paired with the SPM Synchronous Motor
Protection System Monitoring & Metering
• Automation or process control functionality • Advanced recording capabilities with high-
• Stand-alone protection or component in automated substation control system capacity event recorder, configurable and
extended waveform capture and data logger
• Metering: current, voltage, power, energy,
frequency, and harmonics
M60 Motor Protection System

Protection and Control M60 - Protection, Metering, Monitoring and Control


Designed as an asset management device,
the M60 utilizes a proven thermal model that
mimics the design characteristics of each
motor it protects. As part of the Universal Relay
(UR) family, the M60 provides the modularity,
flexibility, and reliability required to deliver
superior protection and control capabilities,
including:

Motor Thermal Model


The M60 features an enhanced motor
thermal model consisting of the following
elements:

• Thermal limit curves - NEMA standard,


voltage dependent and customized The M60 provides protection, control, metering, and monitoring in a single device, easily integrated into
• IEC 60255-8 thermal overload curves existing HMI or SCADA monitoring and control systems.

• Current unbalance biasing


• Independent running and stopped Overtemperature Protection Acceleration Time
exponential cooling curves
The M60 supports up to 16 programmable The M60 protects the motor from overheating
• Optional RTD biasing of the thermal RTD inputs that allow for the configuration of in cases of abnormal loading during motor
model to adapt to real-time temperature the alarm and trip temperature of each RTD, starts. The motor can be tripped if the motor
measurements detecting RTD shorting conditions, and selecting does not reach a running condition within the
• Compensation for hot/cold motor conditions RTD voting that requires more than one RTD to programmable motor acceleration time.
detect an over-temperature condition before it
The M60 thermal model integrates both stator
will issue a trip command. Stator Differential
and rotor heating and cooling into a single model.
The M60 provides stator differential protection
Mechanical Jam for fast clearing of stator phase faults. Advanced
FlexCurves™
The mechanical jam element senses increased CT saturation detection algorithms and dual-
For applications that require greater flexibility,
loading associated with process or load related slope characteristics are incorporated for
FlexCurves can be used to define custom curve
faults such as an overloaded conveyor. A increased security during heavy faults.
shapes. These curves can be used to protect
programmable delay setting can be used to
motors with different rotor and stator damage
allow the process to attempt to clear itself
curves, allowing complete protection over the
before issuing a trip.
total motor capacity.

Functional Block Diagram ANSI® Device Numbers & Functions


DEVICE
FUNCTION
NUMBER
27P Phase Undervoltage
27X Auxiliary Undervoltage
32 Sensitive Directional Power
52
Trip Close 59N 59P 27P 59_2 47 81O 81U 37 Undercurrent
37P Underpower
46 Current Unbalance
50G 51G
47 Phase Sequence Voltage
49 Thermal Model
50BF Breaker Failure
50G Ground Instantaneous Overcurrent
37P 67P 32 50BF 50P 51P 46 37 49 67N 51N 50N 50NBF
50N Neutral Instantaneous Overcurrent
50P Phase Instantaneous Overcurrent
51G Ground Time Overcurrent
51N Neutral Time Overcurrent
M 51P Phase Time Overcurrent
RTD 59N Neutral Overvoltage
Metering
59P Phase Overvoltage
87S
59X Auxiliary Overvoltage
59_2 Negative Sequence Overvoltage
66 Starts Per Hour, Time Between Starts
M60 Motor Protection System 67N Neutral Directional Overcurrent
833730A1.CDR
67P Phase Directional Overcurrent
81O Overfrequency
81U Underfrequency
87S Stator Differential
--- Mechanical Jam

2 GEGridSolutions.com
M60 Motor Protection System

TYPICAL CUSTOM CURVE - 6500 HP, 13800 VOLT


INDUCED DRAFT FAN MOTOR
10000

1000

2
TIME TO TRIP IN SECONDS

100

3
10

4
5 The M60 percent differential element has enhanced saturation detection algorithms to provide
1.0
additional security against AC and DC saturation that can occur during faults near the motor.

Start Inhibit temperatures. Each RTD input has 2 operational


levels: alarm and trip. The M60 supports RTD trip
The start inhibit function prevents the starting
0.1 voting and provides open RTD failure alarming.
0.5 1.0 10 100 of a motor when the motor is too hot and does
MULTIPLE OF PER UNIT CURRENT Alternatively, a remote RTD module “RRTD”,
not have a sufficient amount of thermal capacity
which supports 12 RTD inputs, can also be used
1 PROGRAMMED FLEXCURVE
available to allow a start without being tripped
2 RUNNING SAFETIME (STATOR LIMIT) with the M60 for temperature monitoring. The
offline.
3 ACCELERATION SAFETIME (ROTOR LIMIT)
RRTD provides cost savings compared with
4 MOTOR CURRENT @ 100% VOLTAGE

Breaker Failure Protection standard RTD wiring.


5 MOTOR CURRENT @ 80% VOLTAGE

The breaker failure protection element monitors Two-Speed Motor Protection


Typical FlexCurve overload curve.
for timely operation of the connected breaker.
The two-speed motor protection feature allows
If a trip command is not successful in operating
RTD Bias Maximum for the protection of motors that can operate
100 the breaker and clearing the fault, the breaker
at two different speeds and have different full
90 failure element can be used to send trip signals
RTD Thermal Capacity Used (%)

load capacity levels at each speed. This feature


80 to upstream breakers to clear the fault.
70
can be used on motors that have two sets of
60 Undercurrent Protection windings on each stator, where each set is used
50 to operate the motor at a different speed.
The undercurrent protection element provides
40
the ability to trip the motor due to external Underpower Protection
30
conditions that can cause the load being pulled
20 The underpower protection feature provides for
RTD RTD by the motor to drop below a preset level. This
10 Bias Minimum Bias Center Point sensitive detection of a loss of load condition.
0 element is useful when the loss of the load
The underpower protection element can be more
-50 0 50 100 150 200 250 results in a loss of cooling which will cause the
Maximum Stator RTD Temperature ( C) sensitive for detecting loss of load conditions
asset to overheat.
caused by process-related problems than is
RTD bias curve. Under/Over Frequency Protection possible using a standard undercurrent element.

The under/over frequency protection element Reduced Voltage Starting


Short Circuit Protection detects when the motor is operating at off-
The reduced voltage starting feature provides
nominal frequencies (which can damage the
Short circuit overcurrent protection protects the controls for signaling the motor to switch
process) or signals to upstream protection or
damage to the motor during a locked rotor over from a reduced voltage (that is used during
control to implement load-shedding actions.
condition. The M60 comes with up to 8 startup) to the full voltage for motor running
instantaneous overcurrent elements that can be operation. This feature can issue the command to
RTD Protection (Module Option 5C)
configured for protection, alarming, and control switch to full operating voltage, by detecting: a) if
during locked rotor conditions. The M60 RTD option provides 8 programmable the motor load has reached a preset current level,
RTD inputs per module that are used for or b) if a time delay has elapsed (after starting), or
monitoring the stator, bearing and ambient c) both of these conditions combined.

GEGridSolutions.com 3
M60 Motor Protection System

IEC 61869 and 61850-9-2LE Topologies:


Station Bus
Process Bus PRP Start
Hot-Stanby
Three UR process bus modules enable
communicating to Merging Units “MU” that
comply to either IEC 61869 standard or
IEC 61850-9-2LE technical report. MUs connect Integrated Station and
to the primary asset and translate analog signals Process bus (available)
and digital status/commands to standard sample
values “SV” data and GOOSE messages.
Topologies: Process Bus:
Flexibility for connecting to different network
HSR ring IEC 61850-9-2LE or 61869* SV
size and topology is granted through 100Mbps
and/or 1Gbps Ethernet port support, plus IEC PRP start IEEE 1588 Grand Master or
P-2-P Process Bus slave 61850-9-1 GOOSE
62439 PRP or HSR standard redundancy, plus
Star, Ring and Point-to-point network support.

For time synchronization purposes, this Process


bus module can become an IEEE 1588 slave
Merging units
clock (61850-9-3 profile) or a 1588 Grand Master
clock which removes the need of external time
sources connected to the process bus network.
Conventional or
Customers who may not be using GE MU Optical CT/VTs
devices, could use MU from other vendors.
Interoperability with MU from other vendors is
expected when they comply to the mentioned
SCADA capabilities that far surpass what is • RTD inputs allow biasing of the motor thermal
standards. model, as well as overtemperature protection
found in the average motor protection relay. The
M60 integrates seamlessly with other UR relays of the stator, bearings, and other heat-
IEC 61850-9-2 HardFiber for complete system protection, including the sensitive components of the motor
adjacent motors, feeders and other balance of
Process Bus • Types of digital outputs include trip-
plant protection. rated Form-A and Solid State Relay (SSR)
The IEC 61850 Process Bus module is designed mechanically latching, and
to interface with the Multilin HardFiber System, FlexLogic Form-C outputs
allowing bi-directional IEC 61850 fiber optic
FlexLogic is the powerful UR-platform • DCmA inputs are available to monitor
communications. The HardFiber System is
programming logic engine that provides the equipment and process parameters
designed to integrate seamlessly with existing
ability to create customized protection and
UR applications, including protection functions,
control schemes, minimizing the need and
FlexLogic™, metering and communications. Monitoring and Metering
associated costs of auxiliary components and
The Multilin HardFiber System offers the The M60 includes high accuracy metering and
wiring. With 1024 lines of FlexLogic, the M60
following benefits: recording for all AC signals. Voltage, current,
can be programmed to provide the required
• Communicates using open standard tripping logic along with custom scheme logic and power metering are built into the relay
IEC 61850 messaging for motor breaker control (including interlocking as a standard feature. Current and voltage
with internal motor start supervision and parameters are available as total RMS
• Drastically reduces P&C design, installation
synchrocheck), interlocking schemes with magnitude, and as fundamental frequency
and testing labor by eliminating individual
adjacent protections (for example, preventing magnitude and angle.
copper terminations
sympathetic tripping of healthy feeders), and
• Integrates with existing M60’s by replacing Advanced Device Health Diagnostics
traditional CT/VT inputs with the IEC 61850 dynamic setting group changes.
The M60 performs advanced motor health
Process Bus module
Scalable Hardware diagnostics and records this information
• Does not introduce new cyber security
The M60 is available with a multitude of I/O for each of the last 250 consecutive motor
concerns
configurations to suit the most demanding starts. Analyzing this diagnostic information
Visit the HardFiber System product page on the application needs. The expandable modular for operating parameters that have changed
GE Grid Solutions web site for more details. design allows for easy configuration and future over these successive starts can indicate
upgrades. maintenance requirements before damage
occurs and costly repairs are required
Advanced Automation • Multiple CT/VT configurations allow for the
The M60 incorporates advanced automation implementation of many protection schemes,
features including powerful FlexLogic including applications with high-impedance
programmable logic, communication, and machine grounding

4 GEGridSolutions.com
M60 Motor Protection System

For each motor start, the M60 will provide a oscillation and bearing wear, can be avoided. With 7628, IEC 62351 and IEC 62443 cyber security
record that contains the fol lowing information: the advanced broken rotor bar detection system, requirements and standards. Additionally secure
advanced warning of impending problems FW upgrade is granted through UR Setup’s digital
• Date of each motor start
reduces catastrophic failures, maximizing motor signature validation capabilities.
• Motor acceleration time life and system uptime.
This software option delivers the following core
• Motor starting current
features:
• Motor thermal capacity used during starts
Fault and Disturbance Recording

• Average motor load The advanced disturbance and event recording AAA Server Support (Radius/LDAP)
features within the M60 can significantly reduce
• Running time after a start Enables integration with centrally managed
the time needed for postmortem analysis
authentication and accounting of all user
Advanced Motor Diagnostics of power system events and the creation of
activities and uses modern industry best
regulatory reports. Recording functions include:
The Multilin M60 provides advanced motor practices and standards that meet and exceed
diagnostics including a broken rotor bar • Sequence of Event (SOE) NERC CIP requirements for authentication and
detection function. The broken rotor bar - 1024 time stamped events password management.
detection is a condition maintenance function • Oscillography
that continuously monitors the motor’s health - Supports IEEE C37.111-1999/2013, Role Based Access Control (RBAC)
while in operation. The advanced Motor Current IEC 60255-24 Ed 2.0 COMTRADE standard Efficiently administrate users and roles within
Signature Analysis (MCSA) continuously - 128 digital & up to 56 analog channels UR devices. The new and advanced access
analyzes the motor current signature and based - Events up to 45s in length functions allow users to configure up to five
on preset algorithms, will determine when a • Data Logger and Disturbance Recording roles for up to eight configurable users with
broken rotor bar is present in the motor. With - 16 channels up to 1 sample/cycle/channel independent passwords. The standard “Remote
fully programmable alarms, the broken rotor bar Authentication Dial In User Service” (Radius) is
The very high sampling rates and the large amount
function will provide early detection of any rotor used for authentication.
of storage space available for data recording in the
problems and advise maintenance personnel
M60 can eliminate the need for installing costly
of the impending issue, allowing for predictive Event Recorder (Syslog for SEM)
stand-alone recording equipment.
maintenance of the motor and prevention of Capture all cyber security related events within
catastrophic motor failures. Cyber Security – CyberSentry UR a SOE element (login, logout, invalid password
By providing early indication of potential rotor attempts, remote/local access, user in session,
CyberSentryTM is a software option that delivers
problems, serious system issues, such as reduced settings change, FW update, etc), and then
wide range of cyber security features that help
starting torque, overloads, torque and speed serve and classify data by security level using
customers to comply with NERC CIP, NIST® IR
standard Syslog data format. This will enable
integration with established SEM (Security Event
Management) systems.
Power System Troubleshooting
The M60 contains many tools and reports that simplify and reduce the amount of time required for
troubleshooting power system events.
Communications
The M60 provides advanced commun-ications
technologies for remote data and engineering
access, making it the easiest and most flexible
motor protection relay to use and integrate into
new and existing infrastructures. Direct support
for fiber optic Ethernet provides high-bandwidth
communications allowing for low-latency
controls and high-speed file transfers of relay
fault and event record information. The available
three independent Ethernet ports, redundant
Ethernet option and the embedded managed
Ethernet switch provide the means of creating
fault tolerant communication architectures in an
easy, cost-effective manner without the need for
intermediary communication hardware.

Analyze motor operating characteristics by recording analog waveforms during system voltage recovery.

GEGridSolutions.com 5
M60 Motor Protection System

The M60 supports the most popular industry • Communication with up to 16 UR relays setup software, and in the product manuals.
standard protocols enabling easy, direct in single or redundant rings rather than Easily switch between English and an additional
integration into DCS and SCADA systems. simplistic point-to-point configurations language on the local displays without uploading
• Connect to standard DS0 channel banks new firmware.
• IEC 61850 Ed. 1 and Ed. 2 Station Bus, IEC
61850-2-2LE / IEC 61869 networked or IEC through standard RS422, G.703 or IEEE
C37.94 interfaces or via direct fiber optic
61850-9-2 HardFiber Process Bus EnerVista Software
connections
• DNP 3.0 (serial & TCP/IP) The EnerVista suite is an industry-leading set of
• Built-in continuous loop and channel
• Ethernet Global Data (EGD) software programs that simplifies every aspect
monitoring provides real-time diagnostics
• IEC 60870-5-103 and IEC 60870-5-104 of using the M60 relay. The EnerVista suite
of your communication channels with no
provides all the tools to monitor the status of
• Modbus RTU, Modbus TCP/IP external or handheld tester required
your motor, maintain your relay, and integrate
• HTTP, TFTP, SFTP and MMS file transfer LAN Redundancy information measured by the M60 into DCS
• IEEE 1588 and redundant SNTP for time or SCADA monitoring systems. Convenient
Substation LAN redundancy has been
synchronization COMTRADE and SOE viewers are an integral part
traditionally accomplished by reconfiguring
of the UR setup software included with every UR
• PRP as per IEC 62439-3 the active network topology in case of failure.
relay, to carry out postmortem event analysis
• IEC61850 GOOSE, Routable GOOSE and Regardless of the type of LAN architecture (tree,
and ensure proper protection system operation.
legacy UCA fixed GOOSE mesh, etc), reconfiguring the active LAN requires
UR Setup also provides an export/import setting
time to switchover, during which the LAN is
Interoperability with Embedded file tool which allows customer to transfer
unavailable. UR devices deliver redundancy as
IEC 61850 Ed. 1 and Ed. 2 specific settings from one file to another. This
specified by PRP-IEC 62439-3, which eliminates
tool also provides comprehensive setting file
The new IEC 61850 implementation in the UR the dependency on LAN reconfiguration and the
comparison. These features, together with UR
Family positions GE as an industry leader in this associated switchover time. The UR becomes a
single setting file, help users to simplify their
standard. dual attached node that transmits data packets
setting file management experience.
over both main and redundant networks
• Implements, user selectable, Ed. 1 and Ed. 2 of
simultaneously, so in case of failure, one of the EnerVista Launchpad
the standard across the entire UR Family
data packets will reach the receiving device with
• Provides full relay setting management via EnerVista Launchpad is a powerful software
no time delay.
standard SCL files (ICD, CID and IID) package that provides users with all of the
Multi-Language setup and support tools needed for configuring
• Enables automated relay setting
and maintaining Multilin products. The setup
management using 3rd party tools through UR devices support multiple languages: English,
software within Launchpad allows for the
standard file transfer services (MMS and French, Russian, Chinese, Turkish, German,
configuration of devices in real-time by
SFTP) Polish and Japanese. These language options
communicating using serial, Ethernet, or modem
• Increases the number of Logical Devices and are available on the front panel, in the EnerVista
data mapped to them, GOOSE messages
from up to 64 remote devices, and reports
to support different organizational needs Simplifying Commissioning and Testing
for data transfer and reduce dependency on
generic logical nodes
• Configures GE Systems based on IEC 61850
using universal 3rd party tools
• R-GOOSE enable customer to send GOOSE
messages beyond the substation, which
enables WAPC and more cost effective
communication architectures for wide area
applications

Direct I/O Messaging


Direct I/O allows for the sharing of high-speed
digital information between multiple UR
relays via direct back-to-back connections or
multiplexed through a standard DS0 multiplexer
channel bank. Regardless of the connection
method, direct I/O provides continuous real-time
channel monitoring that supplies diagnostics
information on channel health.

Direct I/O provides superior relay-to-relay


communications that can be used in advanced The internal operation of the M60 elements, logic, and outputs can be monitored in real-time to simplify
interlocking and blocking schemes. commissioning and troubleshooting procedures.

6 GEGridSolutions.com
M60 Motor Protection System

connections, or offline by creating setting files to User Interface


be sent to devices at a later time.
The M60 front panel provides extensive local HMI capabilities. The local display is used for monitoring,
Included in Launchpad is a document archiving status messaging, fault diagnosis, and device configuration. User-configurable messages that combine text
and management system that ensures critical with live data can be displayed when user-defined conditions are met.
documentation is up-to-date and available when
A 7” color, graphic HMI is optionally available that allows users to have customizable bay diagrams with
needed. Documents made available include:
local monitoring of status, values and control functionality. The alarm annunciator panel provides the
• Manuals configuration of up to 96 signals (alarms and status) with full text description.
• Application Notes
• Guideform Specifications
• Brochures LED indicators 7” large color graphic HMI
• Wiring Diagrams
• FAQs 8 user
programmable
• Service Bulletins pushbuttons
The UR setup software now contains an M60
Motor Setting Auto-Configurator that configures
all of the settings required to protect and control
a motor in six simple steps. Simply entering
the motor nameplate data, the CT and VT
parameters, motor starting data, and application
Up to 40 side-screen
information, will allow the UR setup software to
pushbuttons
generate a complete setting file customized for
protecting and controlling the motor.

Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-use and
full-featured monitoring and data recording
software package for small systems. Viewpoint
Monitoring provides a complete HMI package
with the following functionality:

• Plug & Play Device Monitoring


• System Single-Line Monitoring & Control
• Annunciator Alarm Screens
• Trending Reports
• Automatic Event Retrieval
• Automatic Waveform Retrieval

GEGridSolutions.com 7
M60 Motor Protection System

Typical Wiring
TYPICAL CONFIGURATION
THE AC SIGNAL PATH IS CONFIGURABLE
POSITIVE WATTS
CIRCUIT BREAKER
A

B 52

M1a

M2a

M3a

M4a
M1b

M2b

M3b

M4b
M1c

M2c

M3c

M4c
F5a

F6a

F7a

F1a

F2a

F3a

F4a
F1b

F2b

F3b

F4b
F5c

F6c

F7c

F1c

F2c

F3c

F4c
VB

VC
VA

IG5

IG1
VB

VC

IG

IG5

IG1
VA

IG
IA5

IA1

IB

IC
IA

IC5

IC1
IB5

IB1

IA5

IA1

IB

IC
IA

IC5

IC1
IB5

IB1

CURRENT SUPERVISION
VOLTAGE AND
VOLTAGE INPUTS CURRENT INPUTS CURRENT INPUTS
8F / 8G 8F / 8G
P5a CONTACT INPUT P5a DIGITAL INPUTS/OUTPUTS 6G I P1a TC 1
P5c CONTACT INPUT P5c P1 P1b
V
P6a CONTACT INPUT P6a P1c
P6c CONTACT INPUT P6c I P2a
P5b COMMON P5b P2 P2b

VOLTAGE SUPERVISION
V
P2c
P7a CONTACT INPUT P7a
I P3a
P7c CONTACT INPUT P7c
P3 P3b TC 2
P8a CONTACT INPUT P8a V
P3c
P8c CONTACT INPUT P8c
I P4a
P7b COMMON P7b
P4 P4b
V
P8b SURGE P4c

H1a Hot
RTD H1
5C

H1c Comp
DB-9
H1b Return for RTDs H1 and H2
RS-232
H2a Hot (front)
( DC ONLY )

RTD H2
H2c Comp

H3a Hot M60 COMPUTER


RTD H3
H3c Comp 1 1 8
H3b Return for RTDs H3 and H4 TXD 2 2 3 RXD
H4a Hot RXD 3 3 2 TXD
RTD H4
H4c Comp 4 4 20
SGND 5 5 7 SGND
H5a Hot
RTD H5 6 6 6
H5c Comp
7 7 4
H5b Return for RTDs H5 and H6
TRANSDUCER INPUTS/OUTPUTS

8 8 5
H6a Hot
RTD H6 9 9 22
H6c Comp

H7a Hot 9 PIN 25 PIN

M60 MOTOR PROTECTION SYSTEM


RTD H7
H7c Comp CONNECTOR CONNECTOR
H7b Return for RTDs H7 and H8
H8a Hot
RTD H8
H8c Comp 1
Power
H8b SURGE supply
B
B1b
1

CRITICAL
B1a FAILURE 9
B2b D CPU
B3a 48 V DC
DC OUTPUT
B3b
F
POWER SUPPLY

B5b HI 8
CONTROL CT/VT
AC or DC B6b LO G
POWER
B6a
B8a SURGE H 5
B8b FILTER RTD
J
* Optic
Fibre Tx1 100BaseFX
PORT 1
K
T

Rx1
L
Tx2 100BaseFX CONTACTS SHOWN
PORT 2
Rx2 WITH NO M 8
Shielded Tx3 100BaseFX CONTROL POWER CT/VT
Ground at Rx3
PORT 3 N
twisted pairs
UR
D1a P 6
Device
RS485 Inputs/
D2a COM 2 R outputs
D3a com
D4b S
D4a IRIG-B
(Rear view)
Input
BNC VERTICAL
CPU

Co-axial
MODULE ARRANGEMENT

833728A3.CDR
HORIZONTAL MODULE ARRANGEMENT
X W V U T S R P N M L K J H G F D B
6 8 5 8 9 1 This diagram is based on the following order code:
No. 10AWG M60-T00-HCH-F8F-H5C-M8F-P6G-UXX-WXX
minimum Input/ VT/CT RTD VT/CT CPU Power This diagram provides an example of how the device
MODULES MUST BE * * output Supply
GROUNDED IF is wired, not specifically how to wire the device. Please
GROUND
BUS
TERMINAL IS (Rear View) refer to the Instruction Manual for additional details on
PROVIDED * Optional wiring based on various configurations.

Copyright GE Multilin Inc. All rights reserved.

8 GEGridSolutions.com
Ordering
M60 - * 00 - H * * - F ** - H ** - M ** - P ** - U ** - W/X ** For full sized horizontal mount
Base Unit M60 Base Unit
CPU T RS485 + three multimode SFP LC 100BaseFX
U RS485 + two multimode SFP LC 100BaseFX + one SFP RJ45 100BaseT
V RS485 + three SFP RJ45 100BaseT
W RS485 + two 100BaseFx Eth, Multimode ST + one 10/100BaseT Eth, RJ-453
Software Options1 00 No Software Options
03 IEC 61850
A0 CyberSentry UR Lvl 1
B0 IEEE 1588
C0 PRP
D0 IEEE 1588 + CyberSentry UR
Mount / Coating H Horizontal (19” rack) - Standard
A Horizontal (19” rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface E 7” Graphical display, USB front port & programmable pushbuttons - Multi-Language (FW 7.6x or higher)
F Vertical Front Panel with English Display
I Enhanced German Front Panel
J Enhanced German Front Panel with User-Programmable Pushbuttons
K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
W Enhanced Turkish Front Panel
Y Enhanced Turkish Front Panel with User-Programmable Pushbuttons
H Enhanced Polish Front Panel3
O Enhanced Polish Front Panel with User-Programmable Pushbuttons3
Z Enhanced Japanese Front Panel3
X Enhanced Japanese Front Panel with User-Programmable Pushbuttons3
Power Supply H 125 / 250 V AC/DC
2

H RH 125/250 V AC/DC with redundant 125/250 V AC/DC


L 24 - 48 V (DC only)
L RL 24 - 48 V (DC only) with redundant 24 - 48 V (DC only)
CT/VT DSP 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8M 8M Sensitive Ground 4CT/4VT w/ enhanced diagnostics
8N 8N Standard 8CT w/ enhanced diagnostics
8R 8R Sensitive Ground 8CT w/ enhanced diagnostics
IEC 61850 Process Bus4, 5 81 8 Port IEC 61850 Process Bus Module
85 -9-2LE & 61869 Process Bus, 2 x 1000BaseF
86 -9-2LE & 61869 Process Bus, 4 x 1000BaseF + 4 x 100BaseFx
87 -9-2LE & 61869 Process Bus, 4 x 100BaseFx
Digital I/O XX XX XX XX XX No module
4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4D 4D 4D 4D 4D 16 Digital Inputs with Auto-Burnish
4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
6W 6W 6W 6W 6W 30 Contact Inputs - Pin Terminals3
6X 6X 6X 6X 6X 18 Form-A (No Monitoring) Outputs - Pin Terminals3
Transducer I/O 5C 5C 5C 5C 5C 8 RTD Inputs
5E 5E 5E 5E 5E 4 dcmA Inputs, 4 RTD Inputs
5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 7B 1300 nm, multimode, LED, 1 Channel
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels

Ordering Notes:
 . To view all available model order codes, options for M60 or to order the UR Classic Front Panel, please
1
visit GE’s On-Line Store at http://store.gedigitalenergy.com/viewprod.asp?model=M60
2. Redundant power supply only available in horizontal unit. If redundant is chosen, must be same type.
Maximum 2 per chassis
3. Option available soon
4. Process bus module requires empty slots next to it.
5. Conventional DSP and Process Bus modules cannot run simultaneously

GEGridSolutions.com
IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General
Electric Company.

GE reserves the right to make changes to specifications of products described at any time without
notice and without obligation to notify any person of such changes.

Copyright 2023, General Electric Company. All Rights Reserved. GEA-12756L(EN)


English
230413

You might also like