Multilin M60
Comprehensive Protection for Medium Protection and Control
to Large Motors • Enhanced thermal model with RTD and
current unbalance compensation
The MultilinTM M60 motor protection system offers comprehensive protection and control solutions for
• Stator Differential, Mechanical Jam/Stall, Short
medium to large-sized three-phase motors. The M60 includes advanced automation and communication circuit tripping, under-Current & -Power and
capabilities, extensive I/O options, and powerful fault recording features that can simplify postmortem Phase reversal
fault analysis and help minimize motor downtime.
• Two-speed motor protection and reduced
The M60 provides superior protection, control, and diagnostics that includes a proven thermal model voltage starting
with RTD and current unbalance biasing, stator differential, reverse and low forward power, external • Optional internal RTDs & external RTD module
RRTD module, two-speed motors, reduced voltage starting, and broken rotor bar detection.
• Protection and control functionality in one box,
reducing the number of devices
Key Benefits • High density inputs/outputs to support the
• Extended motor life with advanced protection and control elements including a flexible and powerful control of many switchyard assets – all from
thermal model and standard, custom, and voltage dependent overload curves one powerful device
• Integrated automation and process control functions eliminating the need for additional discrete • Integrated large, full color display, for real-time
devices visualization and control of the protected bay
• Simplified setup and configuration with EnerVista M60 Motor Settings auto-configurator
• Enhanced motor-learned data provides critical information for preventative maintenance Advanced Communications
• An integrated large, full color display, provides real-time visualization and control of the protected bay, • Support industry standard protocols with 3
via a bay mimic as well as annunciator functionality and graphical visualization of phasors independent Ethernet ports for simultaneous &
• Advanced IEC 61850 Ed. 1 and Ed. 2 certified implementation, complete settings via SCL files and dedicated connection with IEEE 1588 support
comprehensive process bus support (IEC 61850-9-2LE or IEC 61869 or IEC 61850-9-2 Hardfiber) ensures • DeviceNet and Profibus protocol support using
interoperability, device managing optimization and reduced cost of ownership D485 and P485 protocol converters
• Routable GOOSE (R-GOOSE) enables customer to send GOOSE messages beyond the substation, • IEC 61850-9-2LE/IEC 61869 networked or
which enables WAPC and more cost effective communication architectures for wide area applications IEC61850-9-2 Hardfiber process bus support
• Increased network availability via failover time reduced to zero through IEC® 62439-3 “PRP” support
• Supports IEEE C37.111-1999/2013, IEC 60255-24 Ed 2.0 COMTRADE standard Cyber Security
• CyberSentry™ provides high-end cyber security
Applications aligned to industry standards and services
• Protection & control of most popular construction type medium to large three-phase induction motors (NERC® CIP, AAA, Radius, RBAC, Syslog)
• Protection of medium to large synchronous motors when paired with the SPM Synchronous Motor
Protection System Monitoring & Metering
• Automation or process control functionality • Advanced recording capabilities with high-
• Stand-alone protection or component in automated substation control system capacity event recorder, configurable and
extended waveform capture and data logger
• Metering: current, voltage, power, energy,
frequency, and harmonics
M60 Motor Protection System
2 GEGridSolutions.com
M60 Motor Protection System
1000
2
TIME TO TRIP IN SECONDS
100
3
10
4
5 The M60 percent differential element has enhanced saturation detection algorithms to provide
1.0
additional security against AC and DC saturation that can occur during faults near the motor.
GEGridSolutions.com 3
M60 Motor Protection System
4 GEGridSolutions.com
M60 Motor Protection System
For each motor start, the M60 will provide a oscillation and bearing wear, can be avoided. With 7628, IEC 62351 and IEC 62443 cyber security
record that contains the fol lowing information: the advanced broken rotor bar detection system, requirements and standards. Additionally secure
advanced warning of impending problems FW upgrade is granted through UR Setup’s digital
• Date of each motor start
reduces catastrophic failures, maximizing motor signature validation capabilities.
• Motor acceleration time life and system uptime.
This software option delivers the following core
• Motor starting current
features:
• Motor thermal capacity used during starts
Fault and Disturbance Recording
• Average motor load The advanced disturbance and event recording AAA Server Support (Radius/LDAP)
features within the M60 can significantly reduce
• Running time after a start Enables integration with centrally managed
the time needed for postmortem analysis
authentication and accounting of all user
Advanced Motor Diagnostics of power system events and the creation of
activities and uses modern industry best
regulatory reports. Recording functions include:
The Multilin M60 provides advanced motor practices and standards that meet and exceed
diagnostics including a broken rotor bar • Sequence of Event (SOE) NERC CIP requirements for authentication and
detection function. The broken rotor bar - 1024 time stamped events password management.
detection is a condition maintenance function • Oscillography
that continuously monitors the motor’s health - Supports IEEE C37.111-1999/2013, Role Based Access Control (RBAC)
while in operation. The advanced Motor Current IEC 60255-24 Ed 2.0 COMTRADE standard Efficiently administrate users and roles within
Signature Analysis (MCSA) continuously - 128 digital & up to 56 analog channels UR devices. The new and advanced access
analyzes the motor current signature and based - Events up to 45s in length functions allow users to configure up to five
on preset algorithms, will determine when a • Data Logger and Disturbance Recording roles for up to eight configurable users with
broken rotor bar is present in the motor. With - 16 channels up to 1 sample/cycle/channel independent passwords. The standard “Remote
fully programmable alarms, the broken rotor bar Authentication Dial In User Service” (Radius) is
The very high sampling rates and the large amount
function will provide early detection of any rotor used for authentication.
of storage space available for data recording in the
problems and advise maintenance personnel
M60 can eliminate the need for installing costly
of the impending issue, allowing for predictive Event Recorder (Syslog for SEM)
stand-alone recording equipment.
maintenance of the motor and prevention of Capture all cyber security related events within
catastrophic motor failures. Cyber Security – CyberSentry UR a SOE element (login, logout, invalid password
By providing early indication of potential rotor attempts, remote/local access, user in session,
CyberSentryTM is a software option that delivers
problems, serious system issues, such as reduced settings change, FW update, etc), and then
wide range of cyber security features that help
starting torque, overloads, torque and speed serve and classify data by security level using
customers to comply with NERC CIP, NIST® IR
standard Syslog data format. This will enable
integration with established SEM (Security Event
Management) systems.
Power System Troubleshooting
The M60 contains many tools and reports that simplify and reduce the amount of time required for
troubleshooting power system events.
Communications
The M60 provides advanced commun-ications
technologies for remote data and engineering
access, making it the easiest and most flexible
motor protection relay to use and integrate into
new and existing infrastructures. Direct support
for fiber optic Ethernet provides high-bandwidth
communications allowing for low-latency
controls and high-speed file transfers of relay
fault and event record information. The available
three independent Ethernet ports, redundant
Ethernet option and the embedded managed
Ethernet switch provide the means of creating
fault tolerant communication architectures in an
easy, cost-effective manner without the need for
intermediary communication hardware.
Analyze motor operating characteristics by recording analog waveforms during system voltage recovery.
GEGridSolutions.com 5
M60 Motor Protection System
The M60 supports the most popular industry • Communication with up to 16 UR relays setup software, and in the product manuals.
standard protocols enabling easy, direct in single or redundant rings rather than Easily switch between English and an additional
integration into DCS and SCADA systems. simplistic point-to-point configurations language on the local displays without uploading
• Connect to standard DS0 channel banks new firmware.
• IEC 61850 Ed. 1 and Ed. 2 Station Bus, IEC
61850-2-2LE / IEC 61869 networked or IEC through standard RS422, G.703 or IEEE
C37.94 interfaces or via direct fiber optic
61850-9-2 HardFiber Process Bus EnerVista Software
connections
• DNP 3.0 (serial & TCP/IP) The EnerVista suite is an industry-leading set of
• Built-in continuous loop and channel
• Ethernet Global Data (EGD) software programs that simplifies every aspect
monitoring provides real-time diagnostics
• IEC 60870-5-103 and IEC 60870-5-104 of using the M60 relay. The EnerVista suite
of your communication channels with no
provides all the tools to monitor the status of
• Modbus RTU, Modbus TCP/IP external or handheld tester required
your motor, maintain your relay, and integrate
• HTTP, TFTP, SFTP and MMS file transfer LAN Redundancy information measured by the M60 into DCS
• IEEE 1588 and redundant SNTP for time or SCADA monitoring systems. Convenient
Substation LAN redundancy has been
synchronization COMTRADE and SOE viewers are an integral part
traditionally accomplished by reconfiguring
of the UR setup software included with every UR
• PRP as per IEC 62439-3 the active network topology in case of failure.
relay, to carry out postmortem event analysis
• IEC61850 GOOSE, Routable GOOSE and Regardless of the type of LAN architecture (tree,
and ensure proper protection system operation.
legacy UCA fixed GOOSE mesh, etc), reconfiguring the active LAN requires
UR Setup also provides an export/import setting
time to switchover, during which the LAN is
Interoperability with Embedded file tool which allows customer to transfer
unavailable. UR devices deliver redundancy as
IEC 61850 Ed. 1 and Ed. 2 specific settings from one file to another. This
specified by PRP-IEC 62439-3, which eliminates
tool also provides comprehensive setting file
The new IEC 61850 implementation in the UR the dependency on LAN reconfiguration and the
comparison. These features, together with UR
Family positions GE as an industry leader in this associated switchover time. The UR becomes a
single setting file, help users to simplify their
standard. dual attached node that transmits data packets
setting file management experience.
over both main and redundant networks
• Implements, user selectable, Ed. 1 and Ed. 2 of
simultaneously, so in case of failure, one of the EnerVista Launchpad
the standard across the entire UR Family
data packets will reach the receiving device with
• Provides full relay setting management via EnerVista Launchpad is a powerful software
no time delay.
standard SCL files (ICD, CID and IID) package that provides users with all of the
Multi-Language setup and support tools needed for configuring
• Enables automated relay setting
and maintaining Multilin products. The setup
management using 3rd party tools through UR devices support multiple languages: English,
software within Launchpad allows for the
standard file transfer services (MMS and French, Russian, Chinese, Turkish, German,
configuration of devices in real-time by
SFTP) Polish and Japanese. These language options
communicating using serial, Ethernet, or modem
• Increases the number of Logical Devices and are available on the front panel, in the EnerVista
data mapped to them, GOOSE messages
from up to 64 remote devices, and reports
to support different organizational needs Simplifying Commissioning and Testing
for data transfer and reduce dependency on
generic logical nodes
• Configures GE Systems based on IEC 61850
using universal 3rd party tools
• R-GOOSE enable customer to send GOOSE
messages beyond the substation, which
enables WAPC and more cost effective
communication architectures for wide area
applications
6 GEGridSolutions.com
M60 Motor Protection System
Viewpoint Monitoring
Viewpoint Monitoring is a simple-to-use and
full-featured monitoring and data recording
software package for small systems. Viewpoint
Monitoring provides a complete HMI package
with the following functionality:
GEGridSolutions.com 7
M60 Motor Protection System
Typical Wiring
TYPICAL CONFIGURATION
THE AC SIGNAL PATH IS CONFIGURABLE
POSITIVE WATTS
CIRCUIT BREAKER
A
B 52
M1a
M2a
M3a
M4a
M1b
M2b
M3b
M4b
M1c
M2c
M3c
M4c
F5a
F6a
F7a
F1a
F2a
F3a
F4a
F1b
F2b
F3b
F4b
F5c
F6c
F7c
F1c
F2c
F3c
F4c
VB
VC
VA
IG5
IG1
VB
VC
IG
IG5
IG1
VA
IG
IA5
IA1
IB
IC
IA
IC5
IC1
IB5
IB1
IA5
IA1
IB
IC
IA
IC5
IC1
IB5
IB1
CURRENT SUPERVISION
VOLTAGE AND
VOLTAGE INPUTS CURRENT INPUTS CURRENT INPUTS
8F / 8G 8F / 8G
P5a CONTACT INPUT P5a DIGITAL INPUTS/OUTPUTS 6G I P1a TC 1
P5c CONTACT INPUT P5c P1 P1b
V
P6a CONTACT INPUT P6a P1c
P6c CONTACT INPUT P6c I P2a
P5b COMMON P5b P2 P2b
VOLTAGE SUPERVISION
V
P2c
P7a CONTACT INPUT P7a
I P3a
P7c CONTACT INPUT P7c
P3 P3b TC 2
P8a CONTACT INPUT P8a V
P3c
P8c CONTACT INPUT P8c
I P4a
P7b COMMON P7b
P4 P4b
V
P8b SURGE P4c
H1a Hot
RTD H1
5C
H1c Comp
DB-9
H1b Return for RTDs H1 and H2
RS-232
H2a Hot (front)
( DC ONLY )
RTD H2
H2c Comp
8 8 5
H6a Hot
RTD H6 9 9 22
H6c Comp
CRITICAL
B1a FAILURE 9
B2b D CPU
B3a 48 V DC
DC OUTPUT
B3b
F
POWER SUPPLY
B5b HI 8
CONTROL CT/VT
AC or DC B6b LO G
POWER
B6a
B8a SURGE H 5
B8b FILTER RTD
J
* Optic
Fibre Tx1 100BaseFX
PORT 1
K
T
Rx1
L
Tx2 100BaseFX CONTACTS SHOWN
PORT 2
Rx2 WITH NO M 8
Shielded Tx3 100BaseFX CONTROL POWER CT/VT
Ground at Rx3
PORT 3 N
twisted pairs
UR
D1a P 6
Device
RS485 Inputs/
D2a COM 2 R outputs
D3a com
D4b S
D4a IRIG-B
(Rear view)
Input
BNC VERTICAL
CPU
Co-axial
MODULE ARRANGEMENT
833728A3.CDR
HORIZONTAL MODULE ARRANGEMENT
X W V U T S R P N M L K J H G F D B
6 8 5 8 9 1 This diagram is based on the following order code:
No. 10AWG M60-T00-HCH-F8F-H5C-M8F-P6G-UXX-WXX
minimum Input/ VT/CT RTD VT/CT CPU Power This diagram provides an example of how the device
MODULES MUST BE * * output Supply
GROUNDED IF is wired, not specifically how to wire the device. Please
GROUND
BUS
TERMINAL IS (Rear View) refer to the Instruction Manual for additional details on
PROVIDED * Optional wiring based on various configurations.
8 GEGridSolutions.com
Ordering
M60 - * 00 - H * * - F ** - H ** - M ** - P ** - U ** - W/X ** For full sized horizontal mount
Base Unit M60 Base Unit
CPU T RS485 + three multimode SFP LC 100BaseFX
U RS485 + two multimode SFP LC 100BaseFX + one SFP RJ45 100BaseT
V RS485 + three SFP RJ45 100BaseT
W RS485 + two 100BaseFx Eth, Multimode ST + one 10/100BaseT Eth, RJ-453
Software Options1 00 No Software Options
03 IEC 61850
A0 CyberSentry UR Lvl 1
B0 IEEE 1588
C0 PRP
D0 IEEE 1588 + CyberSentry UR
Mount / Coating H Horizontal (19” rack) - Standard
A Horizontal (19” rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface E 7” Graphical display, USB front port & programmable pushbuttons - Multi-Language (FW 7.6x or higher)
F Vertical Front Panel with English Display
I Enhanced German Front Panel
J Enhanced German Front Panel with User-Programmable Pushbuttons
K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
W Enhanced Turkish Front Panel
Y Enhanced Turkish Front Panel with User-Programmable Pushbuttons
H Enhanced Polish Front Panel3
O Enhanced Polish Front Panel with User-Programmable Pushbuttons3
Z Enhanced Japanese Front Panel3
X Enhanced Japanese Front Panel with User-Programmable Pushbuttons3
Power Supply H 125 / 250 V AC/DC
2
Ordering Notes:
. To view all available model order codes, options for M60 or to order the UR Classic Front Panel, please
1
visit GE’s On-Line Store at http://store.gedigitalenergy.com/viewprod.asp?model=M60
2. Redundant power supply only available in horizontal unit. If redundant is chosen, must be same type.
Maximum 2 per chassis
3. Option available soon
4. Process bus module requires empty slots next to it.
5. Conventional DSP and Process Bus modules cannot run simultaneously
GEGridSolutions.com
IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General
Electric Company.
GE reserves the right to make changes to specifications of products described at any time without
notice and without obligation to notify any person of such changes.