Modbus Register Mapping

Control

AUX101/102
DEIF AGC-5
DMC 1000/DMC 1500
ECO Tier4
MCM 3320
PC500/PC550
PC40
PC80
PCC 1301
PowerCommand 1.x/2.x/3.x
PS0500/PS060X
PowerBloc™

English
Original Instructions 8-2023 A029X159 (Issue 31)
Table of Contents
1. IMPORTANT SAFETY INSTRUCTIONS ....................................................................................... 1
1.1 Warning, Caution, and Note Styles Used in This Manual ..................................................... 1
1.2 Fuel and Fumes Are Flammable ............................................................................................ 1
1.2.1 Gaseous Fuels ............................................................................................................. 2
1.2.2 Exhaust Gases Are Deadly.......................................................................................... 2
1.3 Moving Parts Can Cause Severe Personal Injury or Death ................................................... 2
1.4 Do Not Operate in Flammable and Explosive Environments ................................................. 2
1.5 Electrical Shock Can Cause Severe Personal Injury Or Death.............................................. 2
1.5.1 Medium Voltage Equipment (601 V to 15 kV - U.S. and Canada) .............................. 3
1.6 General Safety Precautions.................................................................................................... 3
1.7 Decommissioning and Disassembly ....................................................................................... 6

2. INTRODUCTION............................................................................................................................ 7
2.1 Controllers............................................................................................................................... 7
2.2 Bitmapping .............................................................................................................................. 8
2.2.1 32-Bit Float Representation ......................................................................................... 8

3. NFPA 110 BITMAP ...................................................................................................................... 11


3.1 NFPA 110 and Extended Annunciation Bitmap.................................................................... 11
3.2 NFPA 110 Bitmap (PS060X) ................................................................................................ 13
3.3 NFPA 110 Bitmap (PC80)..................................................................................................... 15
3.4 NFPA 110 Bitmap (PC40)..................................................................................................... 16

4. AUX101/102 MODBUS REGISTER MAP.................................................................................... 19

5. DEIF AGC-5 ................................................................................................................................. 23


5.1 DEIF AGC-5 Modbus Register Map ..................................................................................... 23
5.1.1 Function Code 2 (02h): Read Discrete Input ............................................................. 24
5.1.2 Function Code 3 (03h): Read Holding Registers ....................................................... 35
5.1.3 Function Code 4 (04h): Read Input Registers (Address, Bit: 500-593) ..................... 41
5.1.4 Function Code 4 (04h): Read Input Registers (Address, Bit: 642-799) ..................... 62
5.1.5 Function Code 4 (04h): Read Input Registers (Address, Bit: 800-900) ..................... 71
5.1.6 Function Code 4 (04h): Read Input Registers (Address, Bit: 1000-1003) ................. 88
5.1.7 Function Code 4 (04h): Read Input Registers (Address, Bit: 1004-1010) ................. 95
5.1.8 Function Code 4 (04h): Read Input Registers (Address, Bit: 1011-1017) ............... 102
5.1.9 Function Code 4 (04h): Read Input Registers (Address, Bit: 1018-1040) ............... 109
5.1.10 Function Code 4 (04h): Read Input Registers (Address, Bit: 1041-1054) ............. 119
5.1.11 Function Code 4 (04h): Read Input Registers (Address, Bit: 1055-1650) ............. 129
5.1.12 Function Code 4 (04h): Read Input Registers (Address, Bit: 1651-1714) ............. 140
5.1.13 Function Code 4 (04h): Read Input Registers (Address, Bit: 1715-1728) ............. 151
5.1.14 Function Code 4 (04h): Read Input Registers (Address, Bit: 1732-1750) ............. 161
5.1.15 Function Code 4 (04h): Read Input Registers (Address, Bit: 1751-1762) ............. 172
5.1.16 Function Code 4 (04h): Read Input Registers (Address, Bit: 1763-1773) ............. 183

A029X159 (Issue 31) i Copyright © 2023 Cummins Inc.


Table of Contents 8-2023

5.1.17 Function Code 4 (04h): Read Input Registers (EIC) (Address, Bit: 593-1370) ..... 192
5.1.18 Function Code 4 (04h): Read Input Registers (EIC) (Address, Bit: 1371-
1994).......................................................................................................................... 199

6. DMC 1000 .................................................................................................................................. 209


6.1 DMC 1000 Modbus Register Map ...................................................................................... 209
6.1.1 DMC 1000 Modbus Parametric Data ....................................................................... 209
6.1.2 DMC 1000 Modbus Enumerated Data..................................................................... 241
6.1.3 DMC 1000 Modbus Bitmap Data ............................................................................. 264

7. DMC 1500 .................................................................................................................................. 267


7.1 DMC 1500 Communication Server 1 .................................................................................. 267
7.1.1 Modbus Address: 2 (Slave)...................................................................................... 267
7.1.2 Generator Set Bus Data........................................................................................... 270
7.1.3 Utility Bus Data ........................................................................................................ 272
7.1.4 ATS 1-5 DATA ......................................................................................................... 273
7.1.5 Word Data ................................................................................................................ 275
7.1.6 ATS 6-10 DATA ....................................................................................................... 276
7.2 DMC 1500 Communication Server 2 .................................................................................. 278
7.2.1 Modbus Address: 1 (Slave)...................................................................................... 278
7.2.2 Generator Raw Data Gen 1-5.................................................................................. 282
7.2.3 Word Data ................................................................................................................ 284
7.2.4 Generator Raw Data Gen 6-8.................................................................................. 286

8. ECO TIER4 MODBUS TCP REGISTER MAP........................................................................... 289

9. MCM3320................................................................................................................................... 295
9.1 MCM3320 Modbus Register Map ....................................................................................... 295
9.1.1 Modbus Communications......................................................................................... 295
9.1.2 Reference Documents ............................................................................................. 295
9.1.3 Serial Port Configuration.......................................................................................... 295
9.1.4 Device Addresses .................................................................................................... 295
9.1.5 Power-Up Time ........................................................................................................ 295
9.1.6 Response Time ........................................................................................................ 295
9.1.7 Data Formatting ....................................................................................................... 295
9.1.8 Modbus Activity LED................................................................................................ 296
9.1.9 Supported Functions ................................................................................................ 296
9.1.10 Holding Register Function...................................................................................... 296
9.1.11 Preset Single/Preset Multiple Registers Function.................................................. 296
9.1.12 Diagnostic Counters............................................................................................... 296
9.1.13 Register Maps ........................................................................................................ 297
9.1.14 Application Layer.................................................................................................... 297
9.1.15 Read Hold Registers.............................................................................................. 297
9.1.16 Set Single Register ................................................................................................ 297
9.1.17 Modbus Loopback.................................................................................................. 297
9.1.18 Set Multiple Registers ............................................................................................ 298
9.1.19 Modbus Register Table.......................................................................................... 298

Copyright © 2023 Cummins Inc. ii A029X159 (Issue 31)


8-2023 Table of Contents

9.2 MCM3320 Modbus Fault Status Bitmaps ........................................................................... 395


9.3 MCM3320 Modbus Address 42506, 42507 ........................................................................ 397

10. PC500/550 MODBUS TCP REGISTER MAP .......................................................................... 399

11. PC40......................................................................................................................................... 409


11.1 PC40 Modbus Register Map............................................................................................. 409
11.1.1 PC40 Modbus Parametric Data ............................................................................. 409
11.1.2 Alarm Condition Codes .......................................................................................... 422
11.1.3 Modbus Alarms ...................................................................................................... 423

12. PC80......................................................................................................................................... 425


12.1 General Instructions.......................................................................................................... 425
12.1.1 Modbus Protocol Application Guide Notes ............................................................ 425
12.2 PC80 Modbus Register Map............................................................................................. 438
12.2.1 PC80 Modbus Parametric Data ............................................................................. 438
12.2.2 PC80 Modbus Enumerated Data ........................................................................... 465

13. PCC 1301/POWERCOMMAND 1.X/PS0500 MODBUS REGISTER MAP .............................. 467

14. POWERCOMMAND 2.X/3.X MODBUS REGISTER MAP ....................................................... 513


14.1 Modbus Communications ................................................................................................. 513
14.2 Parametrics (Analog Values) ............................................................................................ 513

15. POWERCOMMAND 2.X/3.X/PS0500 MODBUS FAULT STATUS BITMAPS ......................... 831

16. PS060X MODBUS REGISTER MAP ....................................................................................... 933


16.1 General Instructions.......................................................................................................... 933
16.1.1 Modbus RTU Supported Functions........................................................................ 933
16.1.2 Modbus RTU Serial Port Configuration Options .................................................... 934
16.2 PS060X Modbus Register Map ........................................................................................ 938

17. POWERBLOC .......................................................................................................................... 973


17.1 PLC Modbus Register Bitmap .......................................................................................... 973
17.2 NFPA 110 Bitmaps ........................................................................................................... 997
17.2.1 NFPA 110(1) Bitmap.............................................................................................. 997
17.2.2 NFPA 110(2) Bitmap.............................................................................................. 998
17.3 StatusWord Bitmaps ......................................................................................................... 999
17.3.1 StatusWord 1 Bitmap ............................................................................................. 999
17.3.2 StatusWord 2 Bitmap ............................................................................................. 999
17.3.3 StatusWord 3 Bitmap ........................................................................................... 1000
17.4 AlarmWord Bitmaps ........................................................................................................ 1001
17.4.1 AlarmWord 1 Bitmap............................................................................................ 1001
17.4.2 AlarmWord 2 Bitmap............................................................................................ 1001
17.4.3 AlarmWord 3 Bitmap............................................................................................ 1002
17.4.4 AlarmWord 4 Bitmap............................................................................................ 1002

A029X159 (Issue 31) iii Copyright © 2023 Cummins Inc.


Table of Contents 8-2023

This page is intentionally blank.

Copyright © 2023 Cummins Inc. iv A029X159 (Issue 31)


1 Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed
during installation and maintenance of the generator set and batteries.
Before operating the generator set, read the Operator's Manual and become familiar with it and the
equipment. Safe and efficient operation can be achieved only if the equipment is properly operated
and maintained. Many accidents are caused by failure to follow fundamental rules and precautions.

1.1 Warning, Caution, and Note Styles Used in This


Manual
The following safety styles and symbols found throughout this manual indicate potentially hazardous
conditions to the operator, service personnel, or equipment.

DANGER
Indicates a hazardous situation that, if not avoided, will result in death or serious injury.

WARNING
Indicates a hazardous situation that, if not avoided, could result in death or serious injury.

CAUTION
Indicates a hazardous situation that, if not avoided, could result in minor or moderate injury.

NOTICE
Indicates information considered important, but not hazard-related (e.g., messages relating to
property damage).

1.2 Fuel and Fumes Are Flammable


Fire, explosion, and personal injury or death can result from improper practices.
• DO NOT fill fuel tanks while the engine is running unless the tanks are outside the engine
compartment. Fuel contact with hot engine or exhaust is a potential fire hazard.
• DO NOT permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition source
near the generator set or fuel tank.
• Fuel lines must be adequately secured and free of leaks. Fuel connection at the engine should be
made with an approved flexible line. Do not use copper piping on flexible lines as copper will
become brittle if continuously vibrated or repeatedly bent. Do not use zinc coated fuel lines with
diesel fuel.
• Make sure all fuel supplies have a positive shutoff valve.
• Make sure the battery area has been well-ventilated prior to servicing near it. Lead-acid batteries
emit a highly explosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc.

A029X159 (Issue 31) 1 Copyright © 2023 Cummins Inc.


1. Important Safety Instructions 8-2023

1.2.1 Gaseous Fuels


Natural gas is lighter than air, and will tend to gather under covered areas.

1.2.2 Exhaust Gases Are Deadly


• Provide an adequate exhaust system to properly expel discharged gases away from enclosed or
sheltered areas, and areas where individuals are likely to congregate. Visually and audibly inspect
the exhaust system daily for leaks per the maintenance schedule. Make sure that exhaust manifolds
are secured and not warped. Do not use exhaust gases to heat a compartment.
• The exhaust vent should be high enough to help clear gases, avoid accumulation of snow, and in
accordance with all local mechanical codes.
• Make sure the unit is well ventilated.
• Engine exhaust and some of its constituents are known to the state of California to cause cancer,
birth defects, and other reproductive harm.

1.3 Moving Parts Can Cause Severe Personal Injury or


Death
• Keep hands, clothing, and jewelry away from moving parts.
• Before starting work on the generator set, disconnect the battery charger from its AC source, then
disconnect the starting batteries using an insulated wrench, negative (–) cable first. In lean-burn
natural gas (LBNG) generator sets, also make sure the starter's air supply line is disconnected or
completely vented until the generator set is ready to start. This will prevent accidental starting.
• Make sure that fasteners on the generator set are secure. Tighten supports and clamps; keep
guards in position over fans, drive belts, etc.
• Do not wear loose clothing or jewelry in the vicinity of moving parts or while working on electrical
equipment. Loose clothing and jewelry can become caught in moving parts.
• If any adjustments must be made while the unit is running, use extreme caution around hot
manifolds, moving parts, etc.

1.4 Do Not Operate in Flammable and Explosive


Environments
Flammable vapor can cause an engine to overspeed and become difficult to stop, resulting in possible fire,
explosion, severe personal injury, and death. Do not operate a generator set where a flammable vapor
environment can be created, unless the generator set is equipped with an automatic safety device to block
the air intake and stop the engine. The owners and operators of the generator set are solely responsible
for operating the generator set safely. Contact your authorized Cummins distributor for more information.

1.5 Electrical Shock Can Cause Severe Personal Injury


Or Death
• Remove electric power before removing protective shields or touching electrical equipment. Use
rubber insulated mats placed on dry wood platforms over floors that are metal or concrete when
around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin
surface to be damp when handling electrical equipment. Do not wear jewelry. Jewelry can short out
electrical contacts and cause shock or burning.

Copyright © 2023 Cummins Inc. 2 A029X159 (Issue 31)


8-2023 1. Important Safety Instructions

• Use extreme caution when working on electrical components. High voltages can cause injury or
death. DO NOT tamper with interlocks.
• Follow all applicable state and local electrical codes. Have all electrical installations performed by a
qualified licensed electrician. Tag and lock open switches to avoid accidental closure.
• DO NOT CONNECT GENERATOR SET DIRECTLY TO ANY BUILDING ELECTRICAL SYSTEM.
Hazardous voltages can flow from the generator set into the utility line. This creates a potential for
electrocution or property damage. Connect only through an approved isolation switch or an
approved paralleling device.

1.5.1 Medium Voltage Equipment (601 V to 15 kV - U.S. and


Canada)
• Medium voltage acts differently than low voltage. Special equipment and training is required to work
on or around medium voltage equipment. Operation and maintenance must be done only by persons
trained and experienced to work on such devices. Improper use or procedures will result in severe
personal injury or death.
• Do not work on energized equipment. Unauthorized personnel must not be permitted near energized
equipment. Due to the nature of medium voltage electrical equipment, induced voltage remains even
after the equipment is disconnected from the power source. Plan the time for maintenance with
authorized personnel so that the equipment can be de-energized and safely grounded.

1.6 General Safety Precautions


WARNING
Hot Pressurized Liquid
Contact with hot liquid can cause severe burns.
Do not open the pressure cap while the engine is running. Let the engine cool down before
removing the cap. Turn the cap slowly and do not open it fully until the pressure has been
relieved.

WARNING
Moving Parts
Moving parts can cause severe personal injury.
Use extreme caution around moving parts. All guards must be properly fastened to prevent
unintended contact.

WARNING
Toxic Hazard
Used engine oils have been identified by some state and federal agencies to cause cancer or
reproductive toxicity.
Do not ingest, breathe the fumes, or contact used oil when checking or changing engine oil.
Wear protective gloves and face guard.

WARNING
Electrical Generating Equipment
Incorrect operation can cause severe personal injury or death.
Do not operate equipment when fatigued, or after consuming any alcohol or drug.

A029X159 (Issue 31) 3 Copyright © 2023 Cummins Inc.


1. Important Safety Instructions 8-2023

WARNING
Toxic Gases
Substances in exhaust gases have been identified by some state and federal agencies to cause
cancer or reproductive toxicity.
Do not breathe in or come into contact with exhaust gases.

WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause severe burns or
death.
Do not store fuel, cleaners, oil, etc., near the generator set.

WARNING
High Noise Level
Generator sets in operation emit noise, which can cause hearing damage.
Wear appropriate ear protection at all times.

WARNING
Hot Surfaces
Contact with hot surfaces can cause severe burns.
The unit is to be installed so that the risk of hot surface contact by people is minimized. Wear
appropriate PPE when working on hot equipment and avoid contact with hot surfaces.

WARNING
Electrical Generating Equipment
Incorrect operation and maintenance can result in severe personal injury or death.
Make sure that only suitably trained and experienced service personnel perform electrical and/or
mechanical service.

WARNING
Toxic Hazard
Ethylene glycol, used as an engine coolant, is toxic to humans and animals.
Wear appropriate PPE. Clean up coolant spills and dispose of used coolant in accordance with
local environmental regulations.

WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause severe burns or
death.
Do not use combustible liquids like ether.

Copyright © 2023 Cummins Inc. 4 A029X159 (Issue 31)


8-2023 1. Important Safety Instructions

WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the starting battery
cables (negative [–] first).

WARNING
Fire Hazard
Materials drawn into the generator set are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from obstructions.

WARNING
Fire Hazard
Materials drawn into the generator set are a fire hazard. Fire can cause severe burns or death.
Make sure the generator set is mounted in a manner to prevent combustible materials from
accumulating under the unit.

WARNING
Fire Hazard
Accumulated grease and oil are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from obstructions. Repair oil
leaks promptly.

NOTICE
Keep multi-type ABC fire extinguishers close by. Class A fires involve ordinary combustible
materials such as wood and cloth. Class B fires involve combustible and flammable liquid fuels
and gaseous fuels. Class C fires involve live electrical equipment. (Refer to NFPA No. 10 in the
applicable region.)

NOTICE
Before performing maintenance and service procedures on enclosed generator sets, make sure
the service access doors are secured open.

NOTICE
Stepping on the generator set can cause parts to bend or break, leading to electrical shorts, or to
fuel leaks, coolant leaks, or exhaust leaks. Do not step on the generator set when entering or
leaving the generator set room.

A029X159 (Issue 31) 5 Copyright © 2023 Cummins Inc.


1. Important Safety Instructions 8-2023

1.7 Decommissioning and Disassembly


NOTICE
Decommissioning and disassembly of the generator set at the end of its working life must
comply with local guidelines and legislation for disposal/recycling of components and
contaminated fluids. This procedure must only be carried out by suitably trained and
experienced service personnel. For more information contact your authorized distributor.

Copyright © 2023 Cummins Inc. 6 A029X159 (Issue 31)


2 Introduction
2.1 Controllers
NOTICE
• Cummins controllers that have Modbus RS485 Communication built-in have a dedicated
Modbus holding register for "Save Trims". The number of write cycles on any flash memory
device are finite.
• Only save trims once all configuration changes are complete; saving them on a schedule
can reduce the lifetime of the physical control. Do not save trims unless a change has
occurred.

NOTICE
There is a fixed number of write cycles available in the life of the control. Once these are used
up, the control must be replaced.

NOTICE
Throughout this document, if a parameter is marked for PCC3300 and PCC3300V2, then it is
applicable to both. If it is marked for PCC3300V2, then it is applicable to PCC3300V2 only.

This note is targeted to, but not limited to, the following Modbus registers per Cummins device. If the
device is not listed in the table, please reference the dedicated Modbus register for "Save Trims".

Device Holding Register Access Specifications Description


Address
PC 1.x 40004 Read and Write 0: No action Save configuration
PS0500 1: Save unconditional parameters or
PCC 1301 adjustments to non-
volatile memory.
PCC 1302
Perform Save Trims
PS060X 408039 Read and Write 0: IsFalse after all configurations
1: IsTrue have been updated.
Do not save trims
PC 2.x 43910 Read and Write 0: Do nothing unless a change has
PC 3.x 1: Save Trims occurred.
PCC 2300
PCC 3300
DMC 1000/DMC 42004 Read and Write 0: Do nothing
1: Save Trims
Default: Do Nothing
AUX 101 43052 Read and Write 0: Do Nothing
1: Save Trims
PC80 410570 Operator (Read and 0: Do Nothing
Write) 1: Save Trims

A029X159 (Issue 31) 7 Copyright © 2023 Cummins Inc.


2. Introduction 8-2023

2.2 Bitmapping
Bitmapped registers are based in a 0-bit system. For a 16-bit register, 0 is the low-order bit and 15 is the
high-order bit.

2.2.1 32-Bit Float Representation


For devices that support floating point natively, most parameters that hold values are floating point type.
Use the method below calculate the value of single precision 32-bit float parameters. The architecture of
number formatting used is IEEE 754 (see Figure 1).
• Sign bit (S): 1 bit
• Exponent (E): 8 bits
• Fraction (F): 23 bits

FIGURE 1. BIT FORMAT FOR IEEE 754


The calculation would be = (-1)^S * 2^(E [dec format]-127) * (1.F)[Base 10]
• A = high register value
• B = low register value
For example, consider how to read the value of Load L1 RMS Current, a 32-bit parameter in registers
410587 and 410588, as shown below:
• 410587 (High register value): 0100 0001 0100 1100
• 410588 (Low register value): 1010 0011 1110 1110

Combine the two registers in binary format to become: 0100 0001 0100 1100 1010 0011 1110 1110
This combined value can be put in the below IEEE 754 format.

TABLE 1. IEEE 754 FORMAT

S Exponent Fraction
0 1 0 0 0 0 0 1 0 1 0 0 1 1 0 0 1 0 1 0 0 0 1 1 1 1 1 0 1 1 1 0

The value in Exponent is 10000010, which is 130 in decimal. The remaining portion is placed in Fraction,
which is 0.0100 1100 1010 0011 1110 1110 (base 2).
In base 2 (binary), 1.F is 1.0100 1100 1010 0011 1110 1110, which equals 1.29937636852264404296875
in base 1.0
Placing this in the formula results in the following:
(-1)^(0) * 2^(130-127)*(1.29937636852264404296875) = 10.395

Copyright © 2023 Cummins Inc. 8 A029X159 (Issue 31)


8-2023 2. Introduction

Using this method, here is an example on how to write a value of 12.65 amps to Load L1 RMS Current.
• 12.65 can be represented in binary as follows:
◦ 12 = 1100
◦ 0.65 = 0.1010 0110 0110 0110 0110 0110 0110 0110011001100110011001100110011001...
• Combining the two values = 1100. 1010 0110 0110 0110 0110 0110
◦ Total of 23 Fraction points can be included in the format of Figure 1
◦ The above number can be represented in the following binary scientific notation: 1.100 1010
0110 0110 0110 0110 0110 * 2exp3
▪ S = 0 ( since value is positive number)
▪ E = 127 + 3 = 130 (1000 0010) (IEE 754 bias for exponent is 127 for 32 bits)
▪ F = 0.100 1010 0110 0110 0110 0110 0110...
▫ This number can be represented in the below IEEE 754 format.

TABLE 2. IEEE 754 FORMAT FOR LOAD L1 RMS CURRENT

S Exponent Fraction
0 1 0 0 0 0 0 1 0 1 0 0 1 0 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0

▫ 410587 (high register value) - 0 1000 010 1001 010 (16716)


▫ 410588 (low register value) - 0110 0110 0110 0110 (41966)
To write 32-bit values to 2 Modbus addresses, always write the high register value followed by the low
register value.

A029X159 (Issue 31) 9 Copyright © 2023 Cummins Inc.


2. Introduction 8-2023

This page is intentionally blank.

Copyright © 2023 Cummins Inc. 10 A029X159 (Issue 31)


3 NFPA 110 Bitmap
3.1 NFPA 110 and Extended Annunciation Bitmap
TABLE 3. NFPA110 BITMAP

Bit Description
15 Common Alarm
14 Genset Supplying Load
13 Genset Running
12 Not in Auto
11 High Battery Voltage
10 Low Battery Voltage
9 Charger AC Failure
8 Fail to Start
7 Low Coolant Temperature
6 Pre–high Engine Temperature
5 High Engine Temperature
4 Pre–low Oil Pressure
3 Low Oil Pressure
2 Overspeed
1 Low Coolant Level
0 Low Fuel Level

See Chapter 13 Reg. 40016, Section 14.2 Reg. 40716, 40717, and Section 6.1.1

TABLE 4. EXTENDED ANNUNCIATION BITMAP

Bit Description
15 Check Genset
14 Ground Fault
13 High AC Voltage
12 Low AC Voltage
11 Under Frequency
10 Overload
9 Overcurrent
8 Short Circuit

A029X159 (Issue 31) 11 Copyright © 2023 Cummins Inc.


3. NFPA 110 Bitmap 8-2023

Bit Description
7 Reverse KW
6 Reverse kVAR
5 Fail to Sync
4 Fail to Close
3 Load Demand
2 Genset Circuit Breaker Tripped
1 Utility Circuit Breaker Tripped
0 Emergency Stop

SeeChapter 13 Reg. 40017 and Section 6.1.1

TABLE 5. NFPA110 BITMAP

Bit Description
15 Source 1 Connected
14 Source 2 Connected
13 NA
12 Not in Auto
11 NA
10 NA
9 Charger AC Failure
8 NA
7 NA
6 NA
5 NA
4 NA
3 NA
2 NA
1 NA
0 NA

See Section 6.1.2

TABLE 6. EXTENDED ANNUNCIATION BITMAP

Bit Description
15 Source 1 Available
14 Source 2 Available

Copyright © 2023 Cummins Inc. 12 A029X159 (Issue 31)


8-2023 3. NFPA 110 Bitmap

Bit Description
13 Source 1 Connected
12 Source 2 Connected
11 ATS Common Alarm
10 Not In Auto
9 Test / Exercise In Progress
8 Low Battery Voltage
7 Load Shed
6 Transfer Inhibit
5 Retransfer Inhibit
4 Fail To Close
3 Fail To Disconnect
2 Fail To Synchronize
1 Bypass to Source 1
0 Bypass to Source 2

See Section 6.1.2

3.2 NFPA 110 Bitmap (PS060X)


TABLE 7. NFPA110 BITMAP FOR PS060X

Bit Description
31 Check Genset
30 Ground Fault
29 High AC Voltage
28 Low AC Voltage
27 Under Frequency
26 Overload Warning OR Overload Shutdown
25 Overcurrent
24 Short Circuit
23 Reverse KW
22 Reverse KVAR
21 Fail to Sync
20 Fail to Close
19 Load Demand
18 Genset Circuit Breaker Tripped

A029X159 (Issue 31) 13 Copyright © 2023 Cummins Inc.


3. NFPA 110 Bitmap 8-2023

17 Utility Circuit Breaker Tripped


16 Emergency Stop
15 Common Alarm
14 Genset Supplying Load
13 Genset Running
12 Not in Auto
11 High Battery Voltage
10 Low Battery Voltage OR Weak Battery
9 Charger AC Failure
8 Fail to Start
7 Low Coolant Temperature
6 Pre–High Engine Temperature
5 High Engine Temperature
4 Pre–Low Oil Pressure
3 Low Oil Pressure
2 Overspeed
1 Low Coolant Level
0 Low Fuel Level

See Section 16.2.

NOTICE
To view 32-bit data of NFPA110 register in Modbus tool, length shall be provided as 2 for 400016
address for read/write values.

TABLE 8. NFPA110 EXTENDED ANNUNCIATION BITMAP FOR PS060X

Bit Description
15 Source 1 Available
14 Source 2 Available
13 Source 1 Connected
12 Source 2 Connected
11 ATS Common Alarm
10 Not in Auto
9 Test/Excercise in Progress
8 Low Battery Voltage
7 Load Shed

Copyright © 2023 Cummins Inc. 14 A029X159 (Issue 31)


8-2023 3. NFPA 110 Bitmap

6 Transfer Inhibit
5 Retransfer Inhibit
4 Fail to close
3 Fail to disconnect
2 Fail to Synchronize
1 Bypass To Source 1
0 Bypass To Source 2

3.3 NFPA 110 Bitmap (PC80)


TABLE 9. NFPA110 STATUS (ADDRESS: 410571) BIT REPRESENTATION

Bit Description
15 (LSB) NA
14 NA
13 NA
12 NA
11 NA
10 NA
9 NA
8 NA
7 NA
6 Charger AC Failure
5 NA
4 NA
3 Not in Auto
2 NA
1 Source 2 Connected
0 (MSB) ATS Common Alarm

TABLE 10. NFPA110 EXTENDED STATUS (ADDRESS: 410572) BIT REPRESENTATION

Bit Description
15 (LSB) NA
14 NA
13 Fail to Synchronize
12 Fail to Disconnect

A029X159 (Issue 31) 15 Copyright © 2023 Cummins Inc.


3. NFPA 110 Bitmap 8-2023

Bit Description
11 Fail to close
10 Retransfer Inhibit
9 Transfer Inhibit
8 Load Shed
7 NA
6 Test / Exercise in Progress
5 Not in Auto
4 ATS Common Alarm
3 Source 2 Connected
2 Source 1 Connected
1 Source 2 Available
0 (MSB) Source 1 Available

3.4 NFPA 110 Bitmap (PC40)


TABLE 11. NFPA110 STATUS (ADDRESS: 41649) BIT REPRESENTATION

Bit Description
15 (LSB) NA
14 NA
13 NA
12 NA
11 NA
10 NA
9 NA
8 NA
7 NA
6 Charger AC Failure
5 NA
4 NA
3 Not in Auto
2 NA
1 Source 2 Connected
0 (MSB) ATS Common Alarm

Copyright © 2023 Cummins Inc. 16 A029X159 (Issue 31)


8-2023 3. NFPA 110 Bitmap

TABLE 12. NFPA110 EXTENDED STATUS (ADDRESS: 41650) BIT REPRESENTATION

Bit Description
15 (LSB) NA
14 NA
13 Fail to Synchronize
12 Fail to Disconnect
11 Fail to Close
10 Retransfer Inhibit
9 Transfer Inhibit
8 Load Shed
7 NA
6 Test / Exercise in Progress
5 Not in Auto
4 ATS Common Alarm
3 Source 2 Connected
2 Source 1 Connected
1 Source 2 Available
0 (MSB) Source 1 Available

A029X159 (Issue 31) 17 Copyright © 2023 Cummins Inc.


3. NFPA 110 Bitmap 8-2023

This page is intentionally blank.

Copyright © 2023 Cummins Inc. 18 A029X159 (Issue 31)


4 AUX101/102 Modbus Register Map
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

System
Addr. Access Specifications Comments
Name

Default: Modbus Changing the address causes no


Modbus Read As supported by Address 13 communication with the annunciator
43044
Device ID Only Modbus protocol until the Modbus Master also
Type: Trim changes its sending address.
0: 2400 Baud
1: 4800 Baud
Changing the baud rate causes no
Modbus Read 2: 9600 Baud Default: 3 communication with the annunciator
43045
Baud Rate Only 3: 19200 Baud Type: Trim until the Modbus Master also
changes its baud rate.
4: 38400 Baud
5: 57600 Baud
0: Even Changing the parity causes no
Modbus Read Default: 2 communication with the annunciator
43046 1: Odd
Parity Only Type: Trim until the Modbus Master also
2: None changes its parity.

1 Changing the stop bits causes no


Modbus Read Default: 1 communication with the annunciator
43047
Stop Bits Only 2 Type: Trim until the Modbus Master also
changes its stop bits.
Changes the communication
Read 0: RS485 Default: 0 protocol between RS485 and
43048 Protocol Modbus.
Only Type: Trim
1: Modbus

Software Read Default: NA Sends AUX101 current firmware


43049
Version Only Type: Trim version.

Device Read Default: 59


43050 AUX101 Device Type
Type Only Type: Trim

AUX 102 Read 0: Not Available Default: 0 Indicates if AUX102 expansion


43051
Available Only 1: Available Type: Trim board is available.

A029X159 (Issue 31) 19 Copyright © 2023 Cummins Inc.


4. AUX101/102 Modbus Register Map 8-2023

System
Addr. Access Specifications Comments
Name
0: Do Nothing Save configuration parameters or
adjustments to non-volatile
Read/ Do Nothing memory. Perform Save Trims after
43052 Save Trims
Write 1: Save Trims Type: Trim all configurations have been
updated. Do not save trims unless
a change has occurred.
Relay 1
Parameters to allow the Relay to be
Relay 2
turned on/off. The lower 8 bits are
Relay 3 used to store out relay values.
Relay 1 is stored in bit 0 and Relay
Relay 4 Read/ 0: Inactive 8 is stored in bit 7. The upper 8 bits
42001 Default: 0
Relay 5 Write 1: Active are 0. In the event of a power cycle
or reboot, all the output values are
Relay 6 reset to 0. This register is used as
heartbit for AUX101 and indicates a
Relay 7
secure communication.
Relay 8
Relay 9
Relay 10
Relay 11
Relay 12 Read/ 0: Inactive Parameters to allow the Relay to be
42009 Default: 0
Relay 13 Write 1: Active turned on/off.

Relay 14
Relay 15
Relay 16
Read Register that contains the value of
42017 Input 1 Default: NA
Only Input 1.
Read Register that contains the value of
42018 Input 2 Default: NA
Only Input 2.
Read Register that contains the value of
42019 Input 3 Default: NA
Only Input 3.
Read Register that contains the value of
42020 Input 4 Default: NA
Only Input 4.
Read Register that contains the value of
42021 Input 5 Default: NA
Only Input 5.
Read Register that contains the value of
42022 Input 6 Default: NA
Only Input 6.
Read Register that contains the value of
42023 Input 7 Default: NA
Only Input 7.
Read Register that contains the value of
42024 Input 8 Default: NA
Only Input 8.

Copyright © 2023 Cummins Inc. 20 A029X159 (Issue 31)


8-2023 4. AUX101/102 Modbus Register Map

System
Addr. Access Specifications Comments
Name
Bit 0 of this register is used for
Input 9
Input 9 when AUX102 is available.
Bit 1 of this register is used for
Input 10
Read Input 10 when AUX102 is available.
42025 Default: NA
Only Bit 2 of this register is used for
Input 11
Input 11 when AUX102 is available.
Bit 3 of this register is used for
Input 12
Input 12 when AUX102 is available.
Current Default: NA
Read/
42029 Source 1 mA = CS/10 Set for Analog Input 3.
Write Type: Trim
Settings
Current Default: NA
Read/
42030 Source 2 mA = CS/10 Set for Analog Input 4.
Write Type: Trim
Settings
Current Default: NA
Read/
42031 Source 3 mA = CS/10 Set for Analog Input 5.
Write Type: Trim
Settings
Current Default: NA
Read/
42032 Source 4 mA = CS/10 Set for Analog Input 6.
Write Type: Trim
Settings
0: Sender
Input 1 Read/ Default: NA
42033 1: Switch - Active Low Register to configure Input 1.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 2 Read/ Default: NA
42034 1: Switch - Active Low Register to configure Input 2.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 3 Read/ Default: NA
42035 1: Switch - Active Low Register to configure Input 3.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 4 Read/ Default: NA
42036 1: Switch - Active Low Register to configure Input 4.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 5 Read/ Default: NA
42037 1: Switch - Active Low Register to configure Input 5.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 6 Read/ Default: NA
42038 1: Switch - Active Low Register to configure Input 6.
Settings Write Type: Trim
2: Switch - Active High

A029X159 (Issue 31) 21 Copyright © 2023 Cummins Inc.


4. AUX101/102 Modbus Register Map 8-2023

System
Addr. Access Specifications Comments
Name
0: Sender
Input 7 Read/ Default: NA
42039 1: Switch - Active Low Register to configure Input 7.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 8 Read/ Default: NA
42040 1: Switch - Active Low Register to configure Input 8.
Settings Write Type: Trim
2: Switch - Active High

Copyright © 2023 Cummins Inc. 22 A029X159 (Issue 31)


5 DEIF AGC-5
5.1 DEIF AGC-5 Modbus Register Map
The controller contains data that can be read by a device communicating via Modbus PCB or via TCP/IP
port, as shown in the figure below.

FIGURE 2. DEIF AGC-5 MODBUS REGISTER MAP DIAGRAM

A029X159 (Issue 31) 23 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

FIGURE 3. CONVERSION TABLE FROM FUNCTION CODE TO PLC ADDRESSES

5.1.1 Function Code 2 (02h): Read Discrete Input

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
0 GB position X
ON
0 TB position ON X X
1 MB position X X
ON
1 MB Position X
ON(stand-
alone)
2 Not used
3 Running X
4 Generator X
voltage/frequen
cy OK
5 Mains failure X X
5 Mains failure X
(stand-alone)
6 Block mode X
7 Manual mode X

Copyright © 2023 Cummins Inc. 24 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
8 Semi-auto X X X X
mode
9 Auto mode X X X X
10 Test mode X X X X
11 Not used: 11-
12
13 Island X X X X
14 Automatic X X X X
mains failure
(AMF)
15 Peak shaving X X X X
16 Fixed power X X X X
17 Mains power X X X X
export (MPE)
18 Load takeover X X X X
(LTO)
19 Power X X
management
20 Any alarm DG1 X X X
21 Any alarm DG2 X X X
22 Any alarm DG3 X X X
23 Any alarm DG4 X X X
24 Any alarm DG5 X X X
25 Any alarm DG6 X X X
26 Any alarm DG7 X X X
27 Any alarm DG8 X X X
28 Any alarm X X X
mains (Mains
Command
Unit)
29 Not used: 29-
30
31 Ready auto- X X X
start DG1
32 Ready auto- X X X
start DG2
33 Ready auto- X X X
start DG3

A029X159 (Issue 31) 25 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
34 Ready auto- X X X
start DG4
35 Ready auto- X X X
start DG5
36 Ready auto- X X X
start DG6
37 Ready auto- X X X
start DG7
38 Ready auto- X X X
start DG8
39 Not used: 39-
54
55 Any G7 mains X X
sync. inhibit
56 Not used: 56-
22499
22500 Digital input 97 X X X X
22501 Digital input 96 X X X X
22502 Digital input 95 X X X X
22503 Digital input 94 X X X X
22504 Digital input 93 X X X X
22505 Digital input 92 X X X X
22506 Digital input 91 X X X X
22507 Digital input X X X X
133
22508 Digital input X X X X
132
22509 Digital input X X X X
131
22510 Digital input X X X X
130
22511 Digital input X X X X
129
22512 Digital input X X X X
128
22513 Digital input X X X X
127
22514 Digital input 29 X X X X
22515 Digital input 30 X X X X

Copyright © 2023 Cummins Inc. 26 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
22516 Digital input 31 X X X X
22517 Digital input 32 X X X X
22518 Digital input 33 X X X X
22519 Digital input 34 X X X X
22520 Digital input 35 X X X X
22521 Digital input 65 X X X X
22522 Digital input 66 X X X X
22523 Digital input 67 X X X X
22524 Digital input 68 X X X X
22525 Digital input 69 X X X X
22526 Digital input 70 X X X X
22527 Digital input 71 X X X X
22528 Digital input 43 CH3130 Oil X X X X
Slow Flow
Meter Fault
22529 Digital input 44 CH3140 Fault X X X X
Reset
22530 Digital input 45 CH3150 X X X X
Customer
Configurable
Input 1 Fault -
Warning
22531 Digital input 46 CH3160 X X X X
Customer
Configurable
Input 2 Fault -
Shutdown
22532 Digital input 47 CH3170 X X X X
Customer
Configurable
Input 3 Fault -
Controlled
Shutdown
22533 Digital input 48 CH3180 X X X X
Customer
Configurable
Input 4 Fault -
Earth Fault

A029X159 (Issue 31) 27 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
22534 Digital input 49 CH3190 X X X X
Customer
Configurable
Input 5 Fault -
Differential
Fault
22535 Digital input 50 CH3200 X X X X
Customer
Configurable
Input 6 Fault
22536 Digital input 51 CH3210 X X X X
Customer
Configurable
Input 7 Fault
22537 Digital input 52 CH3220 X X X X
Customer
Configurable
Input 8 Fault
22538 Digital input 53 CH3230 Start X X X X
Inhibit No 1
22539 Digital input 54 CH3240 Start X X X X
Inhibit No 2
22540 Digital input 55 CH3250 Fire X X X X
Protection Trip
Shutdown
22541 Digital input 23 CH3000 Local X X X X
Emergency
Stop
22542 Not used:
22542-22582
22583 Digital input Remote X X X X
118 Emergency
Stop
22584 Digital input CH3480 X X X X
117 Alternator
Voltage
Sensing
22585 Digital input CH3470 Start X X X X
116 System Trip
22586 Digital input CH3460 X X X X
115 Remote Start
22587 Digital input CH3450 X X X X
114 Derate
Authorization

Copyright © 2023 Cummins Inc. 28 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
22588 Digital input CH3440 X X X X
113 Generator
Breaker Inhibit
22589 Digital input CH3430 Utility X X X X
112 Breaker Inhibit
22590 Not used
22591 Digital input X X X X
108 Not Used
22592 Digital input Alternator X X X X
105 Bearing NDE
R1 (RD)
22593 Digital input Alternator X X X X
102 Bearing DE R1
(RD)
22594 CIO 116 #1 Coolant Heater X X X X
Input 10 Element Trip
22595 CIO 116 #1 Coolant Heater X X X X
Input 11 Element On
22596 CIO 116 #1 Gearbox Oil X X X X
Input 12 Heater
Element Trip
22597 CIO 116 #1 Gearbox Oil X X X X
Input 13 Heater
Element On
22598 CIO 116 #1 Oil Heater X X X X
Input 14 Pump Trip
22599 CIO 116 #1 Oil Heater X X X X
Input 15 Pump On
22600 CIO 116 #1 Oil Heater X X X X
Input 16 Element Trip
22601 CIO 116 #1 Oil Heater X X X X
Input 17 Element On
22602 CIO 116 #1 AC ISO Switch X X X X
Input 19 Status
22603 CIO 116 #1 Coolant Heater X X X X
Input 20 Pump Trip
22604 CIO 116 #1 Coolant Heater X X X X
Input 21 Pump On
22605 CIO 116 #1 Alternator X X X X
Input 22 Heater Trip
22606 CIO 116 #1 Alternator X X X X
Input 23 Heater On

A029X159 (Issue 31) 29 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
22607 CIO 116 #1 HT Valve X X X X
Input 24 Motor Trip
22608 CIO 116 #1 LT Valve Motor X X X X
Input 25 Trip
22609 CIO 116 #1 AC GFI Outlet X X X X
Input 26
22610 CIO 116 #2 Alternator X X X X
Input 10 Auto-Lube
22611 CIO 116 #2 Alternator X X X X
Input 11 Bearing
Vibration
Warning
22612 CIO 116 #2 UPS Control X X X X
Input 12 Battery Charge
Low
22613 CIO 116 #2 Replace UPS X X X X
Input 13 Control Battery
22614 CIO 116 #2 Customer X X X X
Input 14 Convenience
DC Power
Fault
22615 CIO 116 #2 ISB Converter X X X X
Input 15 Over
Temperature
Warning
22616 CIO 116 #2 ISB Converter X X X X
Input 16 Over
Temperature
Shutdown
22617 CIO 116 #2 Spare X X X X
Input 17
22618 CIO 116 #2 HT ACW Stop X X X X
Input 19 Indication
22619 CIO 116 #2 HT CW Stop X X X X
Input 20 Indication
22620 CIO 116 #2 LT ACW Stop X X X X
Input 21 Indication
22621 CIO 116 #2 LT CW Stop X X X X
Input 22 Indication
22622 CIO 116 #2 HT AC Pump X X X X
Input 23 State
22623 CIO 116 #2 HT AC Pump X X X X
Input 24 Trip

Copyright © 2023 Cummins Inc. 30 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
22624 CIO 116 #2 LT AC Pump X X X X
Input 25 State
22625 CIO 116 #2 LT AC Pump X X X X
Input 26 Trip
22626 CIO 116 #3 HT Tank Low X X X X
Input 10 Level
22627 CIO 116 #3 HT Tank Very X X X X
Input 11 Low Level
22628 CIO 116 #3 LT Tank Low X X X X
Input 12 Level
22629 CIO 116 #3 LT Tank Very X X X X
Input 13 Low Level
22630 CIO 116 #3 Radiator Fan X X X X
Input 14 Trip
22631 CIO 116 #3 Louver Closed X X X X
Input 15
22632 CIO 116 #3 Louver Trip X X X X
Input 16
22633 CIO 116 #3 Vent Fan Trip X X X X
Input 17
22634 CIO 116 #3 Spare X X X X
Input 19
22635 CIO 116 #3 Spare X X X X
Input 20
22636 CIO 116 #3 Gearbox Oil X X X X
Input 21 Tank Heater
Fault
22637 CIO 116 #3 Engine Oil Pan X X X X
Input 22 Heater Fault
22638 CIO 116 #3 VPS2 Fault X X X X
Input 23
22639 CIO 116 #3 VPS2 X X X X
Input 24 Operation
22640 CIO 116 #3 FSOV2 V1CPI X X X X
Input 25 Upstream
Signal
22641 CIO 116 #3 FSOV2 V2CPI X X X X
Input 26 Downstream
Signal
22642 Not used:
22642-22700
23000 Relay 65 X X X X

A029X159 (Issue 31) 31 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
23001 Relay 67 X X X X
23002 Relay 69 X X X X
23003 Relay 71 X X X X
23004 Relay 132 Load Dump X X X X
(NO)
23005 Relay 130 Genset Ready X X X X
To Load (NO)
23006 Relay 128 Engine X X X X
Idle/Rated
Speed (NO)
23007 Relay 126 Genset X X X X
Running Above
600 RPM (NO)
23008 Relay 96 X X X X
23009 Relay 94 X X X X
23010 Relay 92 X X X X
23011 Relay 90 X X X X
23012 Relay 29 X X X X
23013 Relay 31 X X X X
23014 Relay 33 X X X X
23015 Relay 35 X X X X
23016 Relay 57 ESTOP Reset X X X X
Latch NO
23017 Relay 59 Spare Relay X X X X
59
23018 Relay 61 Spare Relay X X X X
61
23019 Relay 63 Gearbox X X X X
Heater MCB
Coil NO
23020 Not used
23021 Not used
23022 Not used
23023 Not used
23024 Not used
23025 Relay 5 KeySwitch X
Command
23026 Not used

Copyright © 2023 Cummins Inc. 32 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
23027 Not used
23028 Not used
23029 Not used
23030 Relay 20 LVRT event X X X X
transistor
output
23031 Relay 21 Spare X X X X
transistor
output
23032 Not used:
23032-23046
23047 Relay 69 X X X X
23048 Relay 71 X X X X
23049 Run coil X
23050 Start prepare X
23051 Start X
relay(crank)
23052 Stop coil X
23053 LED CAN B X X X X
23054 LED CAN A X X X X
23055 LED USB X X X X
23056 CIO 208 #1 Oil Heater X X X X
Output 9 COM
23057 CIO 208 #1 Coolant X X X X
Output 11 Heater COM
23058 CIO 208 #1 Coolant X X X X
Output 13 Heater & Oil
Heater Pumps
COM
23059 CIO 208 #1 HT Coolant X X X X
Output 15 Circuit
Colder/Open
COM
23060 CIO 208 #1 HT Coolant X X X X
Output 18 Circuit
Warmer/Close
COM
23061 CIO 208 #1 Alternator X X X X
Output 21 Heater COM

A029X159 (Issue 31) 33 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
23062 CIO 208 #1 LT Coolant X X X X
Output 24 Circuit
Colder/Open
COM
23063 CIO 208 #1 LT Coolant X X X X
Output 27 Circuit
Warmer/Close
COM
23064 CIO 208 #2 Common X X X X
Output 9 Fault Event
COM
23065 CIO 208 #2 Start Inhibit X X X X
Output 11 Event COM
23066 CIO 208 #2 Louvre X X X X
Output 13 Control COM
23067 CIO 208 #2 Vent Fan X X X X
Output 15 Control COM
23068 CIO 208 #2 Coolant Rad X X X X
Output 18 Control Fan
COM
23069 CIO 208 #2 Common X X X X
Output 21 Control
Shutdown
COM
23070 CIO 208 #2 Common X X X X
Output 24 Shutdown
COM
23071 CIO 208 #2 Common X X X X
Output 27 Warning COM
23072 CIO 208 #3 X X X X
Output 9
23073 CIO 208 #3 X X X X
Output 11
23074 CIO 208 #3 X X X X
Output 13
23075 CIO 208 #3 X X X X
Output 15
23076 CIO 208 #3 X X X X
Output 18
23077 CIO 208 #3 X X X X
Output 21
23078 CIO 208 #3 X X X X
Output 24

Copyright © 2023 Cummins Inc. 34 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content/Positi Description AGC-5C AGC-5C AGC-5C AGC-5C


on DG Group Plant Mains
23079 CIO 208 #3 X X X X
Output 27
23080 CIO 116 #1 X X X X
conf. status out
23081 CIO 116 #2 X X X X
conf. status out
23082 CIO 116 #3 X X X X
conf. status out
23083 CIO 208 #1 X X X X
conf. status out
23084 CIO 208 #2 X X X X
conf. status out
23085 CIO 208 #3 X X X X
conf. status out
23086 CIO 308 #1 X X X X
conf. status out
23087 CIO 308 #2 X X X X
conf. status out
23088 CIO 308 #3 X X X X
conf. status out
23089 Not used:
23089-23100

5.1.2 Function Code 3 (03h): Read Holding Registers

Address, Bit Content AGC-5C AGC-5C AGC-5C AGC-5C


DG Group Plant Mains
0 Power regulator X
setpoint -
0...100% of
nominal power.
Activated in menu
7501
1 cosPhi regulator X
setpoint - 60...100
stated as cosPhi
value/100. The
value 100 means
cosPhi = 1.
Activated in menu
7504

A029X159 (Issue 31) 35 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Content AGC-5C AGC-5C AGC-5C AGC-5C


DG Group Plant Mains
2 Reactive power X
regulator setpoint
- +/-100% of
nominal power. A
negative value
means capacitive
reactive power
and a positive
value means
inductive reactive
power.Activated in
menu 7505
3 Frequency X
regulator setpoint
- +/-100%
corresponding to
+/10.0%of
nominal
frequency.
Activated in menu
7502
4 Voltage regulator X
setpoint - +/-100%
corresponding to
+/10.0%of
nominal voltage.
Activated in menu
7503
5.00 Not used
5.01 Remote start X
5.02 Remote GB ON X
5.02 Remote TB ON X X
5.03 Remote GB OFF X
5.03 Remote TB OFF X X
5.04 Remote stop X
5.05 Reset GOV/AVR X
regulation output
to offset
5.06 Start+sync. (semi) X
5.07 Alarm inhibit 1 X X X X
5.08 Alarm inhibit 2 X X X X
5.09 Alarm inhibit 3 X X X X
5.10 Alarm ack. X X X X

Copyright © 2023 Cummins Inc. 36 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Content AGC-5C AGC-5C AGC-5C AGC-5C


DG Group Plant Mains
5.11 Nominal setting 1 X X X X
5.12 Nominal setting 2 X X X X
5.13 Nominal setting 3 X X X X
5.14 Nominal setting 4 X X X X
5.15 Deload/stop X
(semi)
6.00 This bit must be 1 X X X X
when writing the
command word. If
the bit is 0, the
control command
is ignored.
6.01 Island X X X X
6.02 Automatic mains X X X X
failure (AMF)
6.03 Peak shaving X X X X
6.04 Fixed power X X X X
6.05 Mains power X X X X
export (MPE)
6.06 Load takeover X X X X
(LTO)
6.07 Not used
6.08 Not used
6.09 MB ON (Stand- X
alone)
6.09 MB ON X X
6.10 MB OFF (Stand- X
alone)
6.10 MB OFF X X
6.11 Auto start/stop X X X X
6.12 Manual mode X
6.13 Auto mode X X X X
6.14 Semi-Auto mode X X X X
6.15 Test mode X X X X

A029X159 (Issue 31) 37 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Content AGC-5C AGC-5C AGC-5C AGC-5C


DG Group Plant Mains
7.00 This bit must be 1 X X X X
when writing the
command word. If
the bit is 0, the
control command
is ignored.
7.01 External X
frequency control
7.02 External voltage X
control
7.03 External power X X X X
control
7.04 External reactive X
power control
7.05 External power X
factor control
7.06 Capacitive PF X X X X
7.07 Not used
7.08 1. priority X X
7.09 Application 1 X X X X
7.10 Application 2 X X X X
7.11 Application 3 X X X X
7.12 Application 4 X X X X
7.13 Not used
7.14 Not used
7.15 Synchronize clock X X X X
to 4:00 a.m.
8.00 This bit must be 1 X X X X
when writing the
command word. If
the bit is 0, the
control command
is ignored.
8.01 Virtual event 1 X X X X
8.02 Virtual event 2 X X X X
8.03 Virtual event 3 X X X X
8.04 Virtual event 4 X X X X
8.05 Virtual event 5 X X X X
8.06 Virtual event 6 X X X X

Copyright © 2023 Cummins Inc. 38 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Content AGC-5C AGC-5C AGC-5C AGC-5C


DG Group Plant Mains
8.07 Virtual event 7 X X X X
8.08 Virtual event 8 X X X X
8.09 Virtual event 9 X X X X
8.10 Virtual event 10 X X X X
8.11 Virtual event 11 X X X X
8.12 Virtual event 12 X X X X
8.13 Virtual event 13 X X X X
8.14 Virtual event 14 X X X X
8.15 Virtual event 15 X X X X
9.00 This bit must be 1 X X X X
when writing the
command word. If
the bit is 0, the
control command
is ignored.
9.01 Virtual event 16 X X X X
9.02 Virtual event 17 X X X X
9.03 Virtual event 18 X X X X
9.04 Virtual event 19 X X X X
9.05 Virtual event 20 X X X X
9.06 Virtual event 21 X X X X
9.07 Virtual event 22 X X X X
9.08 Virtual event 23 X X X X
9.09 Virtual event 24 X X X X
9.10 Virtual event 25 X X X X
9.11 Virtual event 26 X X X X
9.12 Virtual event 27 X X X X
9.13 Virtual event 28 X X X X
9.14 Virtual event 29 X X X X
9.15 Virtual event 30 X X X X
10.00 This bit must be 1 X X X X
when writing the
command word. If
the bit is 0, the
control command
is ignored.
10.01 Virtual event 31 X X X X

A029X159 (Issue 31) 39 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Content AGC-5C AGC-5C AGC-5C AGC-5C


DG Group Plant Mains
10.02 Virtual event 32 X X X X
10.03 Reserved X X X X
10.04 Clear log X X X X
10.05 Clear Parameter X X X X
edits
10.06 Not used
10.07 Not used
10.08 Not used
10.09 Not used
10.10 Not used
10.11 Not used
10.12 Not used
10.13 Not used
10.14 Not used
10.15 Not used
11 Not used: 11-12
13.00 This bit must be 1 X X X X
when writing the
command word. If
the bit is 0, the
control command
is ignored.
13.01 Enable external X
frequency control
13.02 Disable external X
frequency control
13.03 Enable external X
voltage control
13.04 Disable external X
voltage control
13.05 Enable external X X X X
power control
13.06 Disable external X X X X
power control
13.07 Enable external X
VAr control
13.08 Disable external X
VAr control

Copyright © 2023 Cummins Inc. 40 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Content AGC-5C AGC-5C AGC-5C AGC-5C


DG Group Plant Mains
13.09 External power X
factor control
13.09 Enable external X
CosPhi control
13.10 External power X
factor control
13.10 Disable external X
CosPhi control
13.11 Not used
13.12 Not used
13.13 Reset horn X X X X
13.14 Not used
13.15 Not used
14 Not used: 14-200
58000 Year (2003-2099) X X X X
58001 Month (1-12) X X X X
58002 Date (1-31) X X X X
58003 Day (1-7, Monday X X X X
- Sunday)
58004 Hour (0-23) X X X X
58005 Min (0-59) X X X X
58006 Sec (0-59) X X X X

5.1.3 Function Code 4 (04h): Read Input Registers (Address, Bit:


500-593)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
500 Application X X X X
version
U
501 L1-L2 Generator X
voltage L1-
L2 [V]
U
501 L1-L2 Group X
voltage L1-
L2 [V]

A029X159 (Issue 31) 41 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
U
501 L1-L2 Mains X X
voltage L1-
L2 [V]
U
502 L2-L3 Generator X
voltage L2-
L3 [V]
U
502 L2-L3 Group X
voltage L2-
L3 [V]
U
502 L2-L3 Mains X X
voltage L2-
L3 [V]
U
503 L3-L1 Generator X
voltage L3-
L1 [V]
U
503 L3-L1 Group X
voltage L3-
L1 [V]
U
503 L3-L1 Mains X X
voltage L3-
L1 [V]
U
504 L1-N Generator X
voltage L1-N
[V]
U
504 L1-N Group X
voltage L1-N
[V]
U
504 L1-N Mains X X
voltage L1-N
[V]
U
505 L2-N Generator X
voltage L2-N
[V]
U
505 L2-N Group X
voltage L2-N
[V]
U
505 L2-N Mains X X
voltage L2-N
[V]
U
506 L3-N Generator X
voltage L3-N
[V]
U
506 L3-N Group X
voltage L3-N
[V]

Copyright © 2023 Cummins Inc. 42 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
U
506 L3-N Mains X X
voltage L3-N
[V]
f
507 L1 Generator f 1/100 X
L1 [Hz/100]
f
507 L1 Group f L1 1/100 X
[Hz/100]
f
507 L1 Mains f L1 1/100 X X
[Hz/100]
f
508 L2 Generator f 1/100 X
L2 [Hz/100]
f
508 L2 Group f L2 1/100 X
[Hz/100]
f
508 L2 Mains f L2 1/100 X X
[Hz/100]
f
509 L3 Generator f 1/100 X
L3 [Hz/100]
f
509 L3 Group f L3 1/100 X
[Hz/100]
f
509 L3 Mains f L3 1/100 X X
[Hz/100]
510 Phi Generator 10-Jan X
voltage
phase angle
L1-L2
[Deg/10]
510 Phi Group X
voltage
phase angle
L1- L2
[Deg/10]
510 Phi Mains X X
voltage
phase angle
L1- L2
[Deg/10]
511 Phi Generator X
voltage
phase angle
L2-L3
[Deg/10]

A029X159 (Issue 31) 43 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
511 Phi Group X
voltage
phase angle
L2- L3
[Deg/10]
511 Phi Mains X X
voltage
phase angle
L2- L3
[Deg/10]
512 Phi Generator X
voltage
phase angle
L3-L1
[Deg/10]
512 Phi Group X
voltage
phase angle
L3- L1
[Deg/10]
512 Phi Mains X X
voltage
phase angle
L3- L1
[Deg/10]
I
513 L1 Generator X
current L1
[A]
I
513 L1 Group X
current L1
[A]
I
513 L1 Mains X
current L1
[A]
I
513 L1 Plant current X
L1 [A]
I
514 L2 Generator X
current L2
[A]
I
514 L2 Group X
current L2
[A]
I
514 L2 Mains X
current L2
[A]

Copyright © 2023 Cummins Inc. 44 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
I
514 L2 Plant current X
L2 [A]
I
515 L3 Generator X
current L3
[A]
I
515 L3 Group X
current L3
[A]
I
515 L3 Mains X
current L3
[A]
I
515 L3 Plant current X
L3 [A]
P
516 L1 Generator X
power L1
[kW]
P
516 L1 Group power X
L1 [kW]
P
516 L1 Mains power X
L1 [kW]
P
516 L1 Plant power X
L1 [kW]
P
517 L2 Generator X
power L2
[kW]
P
517 L2 Group power X
L2 [kW]
P
517 L2 Mains power X
L2 [kW]
P
517 L2 Plant power X
L2 [kW]
P
518 L3 Generator X
power L3
[kW]
P
518 L3 Group power X
L3 [kW]
P
518 L3 Mains power X
L3 [kW]
P
518 L3 Plant power X
L3 [kW]
519 P Generator X
power [kW]

A029X159 (Issue 31) 45 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
519 P Group power X
[kW]
519 P Mains power X
[kW]
519 P Plant power X
[kW]
Q
520 L1 Generator X
reactive
power L1
[kVAr]
Q
520 L1 Group X
reactive
power L1
[kVAr]
Q
520 L1 Mains X
reactive
power L1
[kVAr]
Q
520 L1 Plant X
reactive
power L1
[kVAr]
Q
521 L2 Generator X
reactive
power L2
[kVAr]
Q
521 L2 Group X
reactive
power L2
[kVAr]
Q
521 L2 Mains X
reactive
power L2
[kVAr]
Q
521 L2 Plant X
reactive
power L2
[kVAr]
Q
522 L3 Generator X
reactive
power L3
[kVAr]
Q
522 L3 Group X
reactive
power L3
[kVAr]

Copyright © 2023 Cummins Inc. 46 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
Q
522 L3 Mains X
reactive
power L3
[kVAr]
Q
522 L3 Plant X
reactive
power L3
[kVAr]
523 Q Generator X
reactive
power [kVAr]
523 Q Group X
reactive
power [kVAr]
523 Q Mains X
reactive
power [kVAr]
523 Q Plant X
reactive
power [kVAr]
S
524 L1 Generator X
apparent
power L1
[kVA]
S
524 L1 Group X
apparent
power L1
[kVA]
S
524 L1 Mains X
apparent
power L1
[kVA]
S
524 L1 Plant X
apparent
power L1
[kVA]
S
525 L2 Generator X
apparent
power L2
[kVA]
S
525 L2 Group X
apparent
power L2
[kVA]

A029X159 (Issue 31) 47 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
S
525 L2 Mains X
apparent
power L2
[kVA]
S
525 L2 Plant X
apparent
power L2
[kVA]
S
526 L3 Generator X
apparent
power L3
[kVA]
S
526 L3 Group X
apparent
power L3
[kVA]
S
526 L3 Mains X
apparent
power L3
[kVA]
S
526 L3 Plant X
apparent
power L3
[kVA]
527 S Generator X
apparent
power [kVA]
527 S Group X
apparent
power [kVA]
527 S Mains X
apparent
power [kVA]
527 S Plant X
apparent
power [kVA]
R
528 EXP Generator X
Export,
reactive
energy
counter
[kVArh] [Hi]

Copyright © 2023 Cummins Inc. 48 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
R
528 EXP Group X
Export,
reactive
energy
counter
[kVArh] [Hi]
R
528 EXP Mains X
Export,
reactive
energy
counter
[kVArh] [Hi]
R
528 EXP Plant Export, X
reactive
energy
counter
[kVArh] [Hi]
R
529 EXP Generator X
Export,
reactive
energy
counter
[kVArh] [Lo]
R
529 EXP Group X
Export,
reactive
energy
counter
[kVArh] [Lo]
R
529 EXP Mains X
Export,
reactive
energy
counter
[kVArh] [Lo]
R
529 EXP Plant Export, X
reactive
energy
counter
[kVArh] [Lo]
E
530 EXP Generator X
Export,
active energy
counter, day
[kWh] [Hi]

A029X159 (Issue 31) 49 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
E
530 EXP Group X
Export,
active energy
counter, day
[kWh] [Hi]
E
530 EXP Mains X
Export,
active energy
counter, day
[kWh] [Hi]
E
530 EXP Plant Export, X
active energy
counter, day
[kWh] [Hi]
E
531 EXP Generator X
Export,
active energy
counter, day
[kWh] [Lo]
E
531 EXP Group X
Export,
active energy
counter, day
[kWh] [Lo]
E
531 EXP Mains X
Export,
active energy
counter, day
[kWh] [Lo]
E
531 EXP Plant Export, X
active energy
counter, day
[kWh] [Lo]
E
532 EXP Generator X
Export,
active energy
counter,
week [kWh]
[Hi]
E
532 EXP Group X
Export,
active energy
counter,
week [kWh]
[Hi]

Copyright © 2023 Cummins Inc. 50 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
E
532 EXP Mains X
Export,
active energy
counter,
week [kWh]
[Hi]
E
532 EXP Plant Export, X
active energy
counter,
week [kWh]
[Hi]
E
533 EXP Generator X
Export,
active energy
counter,
week [kWh]
[Lo]
E
533 EXP Group X
Export,
active energy
counter,
week [kWh]
[Lo]
E
533 EXP Mains X
Export,
active energy
counter,
week [kWh]
[Lo]
E
533 EXP Plant Export, X
active energy
counter,
week [kWh]
[Lo]
E
534 EXP Generator X
Export,
active energy
counter,
month [kWh]
[Hi]
E
534 EXP Group X
Export,
active energy
counter,
month [kWh]
[Hi]

A029X159 (Issue 31) 51 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
E
534 EXP Mains X
Export,
active energy
counter,
month [kWh]
[Hi]
E
534 EXP Plant Export, X
active energy
counter,
month [kWh]
[Hi]
E
535 EXP Generator X
Export,
active energy
counter,
month [kWh]
[Lo]
E
535 EXP Group X
Export,
active energy
counter,
month [kWh]
[Lo]
E
535 EXP Mains X
Export,
active energy
counter,
month [kWh]
[Lo]
E
535 EXP Plant Export, X
active energy
counter,
month [kWh]
[Lo]
E
536 EXP Generator X
Export,
active energy
counter, total
[kWh] [Hi]
E
536 EXP Group X
Export,
active energy
counter, total
[kWh] [Hi]
E
536 EXP Mains X
Export,
active energy
counter, total
[kWh] [Hi]

Copyright © 2023 Cummins Inc. 52 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
E
536 EXP Plant Export, X
active energy
counter, total
[kWh] [Hi]
E
537 EXP Generator X
Export,
active energy
counter, total
[kWh] [Lo]
E
537 EXP Group X
Export,
active energy
counter, total
[kWh] [Lo]
E
537 EXP Mains X
Export,
active energy
counter, total
[kWh] [Lo]
E
537 EXP Plant Export, X
active energy
counter, total
[kWh] [Lo]
538 PF Generator X
PF [PF/100]
538 PF Group PF X
[PF/100]
538 PF Mains PF X X
[PF/100]
U
539 L1-L2 Busbar / X
Generator
busbar volt-
age L1-L2
[V]
U
539 L1-L2 Busbar X
voltage L1-
L2 [V]
U
539 L1-L2 Generator X
busbar
voltage L1-
L2 [V]
U
539 L1-L2 Group X
busbar
voltage L1-
L2 [V]

A029X159 (Issue 31) 53 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
U
540 L2-L3 Busbar / X
Generator
busbar volt-
age L2-L3
[V]
U
540 L2-L3 Busbar X
voltage L2-
L3 [V]
U
540 L2-L3 Generator X
busbar
voltage L2-
L3 [V]
U
540 L2-L3 Group X
busbar
voltage L2-
L3 [V]
U
541 L3-L1 Busbar / X
Generator
busbar volt-
age L3-L1
[V]
U
541 L3-L1 Busbar X
voltage L3-
L1 [V]
U
541 L3-L1 Generator X
busbar
voltage L3-
L1 [V]
U
541 L3-L1 Group X
busbar
voltage L3-
L1 [V]
U
542 L1-N Busbar / X
Generator
busbar volt-
age L1-N [V]
U
542 L1-N Busbar X
voltage L1-N
[V]
U
542 L1-N Generator X
busbar
voltage L1-N
[V]
U
542 L1-N Group X
busbar
voltage L1-N
[V]

Copyright © 2023 Cummins Inc. 54 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
U
543 L2-N Busbar / X
Generator
busbar volt-
age L2-N [V]
U
543 L2-N Busbar X
voltage L2-N
[V]
U
543 L2-N Generator X
busbar
voltage L2-N
[V]
U
543 L2-N Group X
busbar
voltage L2-N
[V]
U
544 L3-N Busbar / X
Generator
busbar volt-
age L3-N [V]
U
544 L3-N Busbar X
voltage L3-N
[V]
U
544 L3-N Generator X
busbar
voltage L3-N
[V]
U
544 L3-N Group X
busbar
voltage L3-N
[V]
f
545 L1 Busbar / X
Generator
busbar f L1
[Hz/100]
f
545 L1 Busbar f L1 X
[Hz/100]
f
545 L1 Generator X
busbar f L1
[Hz/100]
f
545 L1 Group X
busbar f L1
[Hz/100]
f
546 L2 Busbar / X
Generator
busbar f L2
[Hz/100]

A029X159 (Issue 31) 55 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
f
546 L2 Busbar f L2 X
[Hz/100]
f
546 L2 Generator X
busbar f L1
[Hz/100]
f
546 L2 Group X
busbar f L1
[Hz/100]
f
547 L3 Busbar / X
Generator
busbar f L3
[Hz/100]
f
547 L3 Busbar f L3 X
[Hz/100]
f
547 L3 Generator X
busbar f L1
[Hz/100]
f
547 L3 Group X
busbar f L1
[Hz/100]
Phi
548 L1-L2 Busbar / X
Generator
busbar volt-
age phase
angle L1-L2
[Deg/10]
Phi
548 L1-L2 Busbar X
voltage
phase angle
L1- L2
[Deg/10]
Phi
548 L1-L2 Generator X
busbar
voltage
phase angle
L1-L2
[Deg/10]
Phi
548 L1-L2 Group X
busbar
voltage
phase angle
L1-L2
[Deg/10]

Copyright © 2023 Cummins Inc. 56 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
Phi
549 L2-L3 Busbar / X
Generator
busbar volt-
age phase
angle L2-L3
[Deg/10]
Phi
549 L2-L3 Busbar X
voltage
phase angle
L2- L3
[Deg/10]
Phi
549 L2-L3 Generator X
busbar
voltage
phase angle
L2-L3
[Deg/10]
Phi
549 L2-L3 Group X
busbar
voltage
phase angle
L2-L3
[Deg/10]
Phi
550 L3-L1 Busbar / X
Generator
busbar volt-
age phase
angle L3-L1
[Deg/10]
Phi
550 L3-L1 Busbar X
voltage
phase angle
L3- L1
[Deg/10]
Phi
550 L3-L1 Generator X
busbar
voltage
phase angle
L3-L1
[Deg/10]
Phi
550 L3-L1 Group X
busbar
voltage
phase angle
L3-L1
[Deg/10]

A029X159 (Issue 31) 57 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
Phi
551 L1-L1 U BB L1 - U X
Gen. L1
phase an-
gle [Deg/10]
Phi
551 L1-L1 U BB L1 - U X
Mains L1
phase angle
[Deg/10]
Phi
551 L1-L1 U Gen. BB X
L1 - U Group
BB L1 phase
angle
[Deg/10]
Phi
551 L1-L1 U Group BB X
L1 - U Mains
L1 phase
angle
[Deg/10]
Phi
552 L2-L2 U BB L2 - U X
Gen. L2
phase an-
gle [Deg/10]
Phi
552 L2-L2 U BB L2 - U X
Mains L2
phase angle
[Deg/10]
Phi
552 L2-L2 U Gen. BB X
L2 - U Group
BB L2 phase
angle
[Deg/10]
Phi
552 L2-L2 U Group BB X
L2 - U Mains
L2 phase
angle
[Deg/10]
Phi
553 L3-L3 U BB L3 - U X
Gen. L3
phase an-
gle [Deg/10]
Phi
553 L3-L3 U BB L3 - U X
Mains L3
phase angle
[Deg/10]

Copyright © 2023 Cummins Inc. 58 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
Phi
553 L3-L3 U Gen. BB X
L3 - U Group
BB L3 phase
angle
[Deg/10]
Phi
553 L3-L3 U Group BB X
L3 - U Mains
L3 phase
angle
[Deg/10]
554 Abs. run. Absolute X
hours running
hours [Hi]
555 Abs. run. Absolute X
hours running
hours [Lo]
556 Rel. run. Relative X
hours running
hours [Hi]
557 Rel. run. Relative X
hours running
hours [Lo]
558 Alarms No. of alarms X X X X
559 Alarms No. of X X X X
unacknowled
ged alarms
560 Alarms No. of active X X X X
acknowledge
d alarms
561 Not used:
561, 562
GB
563 oper No. of GB X
operations
TB
563 oper No. of TB X X X
operations
MB
564 oper No. of MB X X X
operations
565 Not used
566 Start Start X
attempts attempts
U
567 SUPPLY DC supply X X X X
term. 1-2
[V/10]

A029X159 (Issue 31) 59 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
U
568 SUPPLY DC supply X X X X
M4 term. 98-99
[V/10]
569 Service Service timer X
1 running
hours
570 Service Service timer X
1 running
days
571 Service Service timer X
2 running
hours
572 Service Service timer X
2 running
days
573 Cos-phi Cos-phi X X X X
[cosPhi/100]
574 Cos-phi Cos-phi X X X X
Inductive/Ca
pacitive
0=Inductive,
1=Capacitive
575 Not used
576 RPM RPM X
577 Running Running X
hours load hours load
profile profile [Hi]
578 Running Running X
hours load hours load
profile profile [Lo]
579 Not used
580 Reserved: X X X X
580-582
583 Multi-input X X X X
102-
Alternator
Bearing DE
R1 (RD)
584 Multi-input X X X X
105-
Alternator
Bearing NDE
R1 (RD)

Copyright © 2023 Cummins Inc. 60 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
585 Multi-input X X X X
108-
Not Used
586 Ain Analogue X X X X
input 91-
Configurable
Analog
Output No 2
Return
587 Ain Analogue X X X X
input 93- Not
Used
588 Ain Analogue X X X X
input 95-
Configurable
Analog
Output No 3
Return
589 Ain Analogue X X X X
input 97- Not
Used
590 Internal X X X X
Temperature
[Deg C /10]
591 P TB power, X
Multi-input
105
(Transducer)
592 P Group X
power, Multi-
input 102
(Transducer)
592 P Mains power, X
Multi-input
102
(Transducer)
592 P Mains power, X
Multi-input
102
(Transducer)
592 P Plant power, X
Multi-input
102
(Transducer)

A029X159 (Issue 31) 61 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
593 Engine X
J1939 data,
593-641, see
Function
code 4 (EIC)

5.1.4 Function Code 4 (04h): Read Input Registers (Address, Bit:


642-799)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
642 RegAddr. Control X X X X
register
address 0
643 RegAddr. Control X X X X
register
address 1
644 RegAddr. Control X X X X
register
address 2
645 RegAddr. Control X X X X
register
address 3
646 RegAddr. Control X X X X
register
address 4
647 RegAddr. Control X X X X
register
address 5
648 RegAddr. Control X X X X
register
address 6
649 RegAddr. Control X X X X
register
address 7
650 RegAddr. Control X X X X
register
address 8
651 RegAddr. Control X X X X
register
address 9
652 RegAddr. Control X X X X
register
address 10

Copyright © 2023 Cummins Inc. 62 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
653 RegAddr. Control X X X X
register
address 11
654 RegAddr. Control X X X X
register
address 12
655 Ain Control X X X X
register
address 13
656 Ain Analogue X X X X
input 127
657 Ain Analogue X X X X
input 129
658 Ain Analogue X X X X
input 131
659 Ext Ain Analogue X X X X
input 133
660 Ext Ain External Ain X X X X
1/CIO 308
no. 1.
Input 8
[Config]
661 Ext Ain External Ain X X X X
2/CIO 308
no. 1.
Input 11
[Config]
662 Ext Ain External Ain X X X X
3/CIO 308
no. 1.
Input 14
[Config]
663 Ext Ain External Ain X X X X
4/CIO 308
no. 1.
Input 17
[Config]
664 Ext Ain External Ain X X X X
5/CIO 308
no. 1.
Input 20
[Config]

A029X159 (Issue 31) 63 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
665 Ext Ain External Ain X X X X
6/CIO 308
no. 1.
Input 23
[Config]
666 Ext Ain External Ain X X X X
7/CIO 308
no. 1.
Input 26
[Config]
667 Ext Ain External Ain X X X X
8/CIO 308
no. 1.
Input 29
[Config]
668 Ext Ain CIO 308 no. X X X X
2. Input 8
[Config]
669 Ext Ain CIO 308 no. X X X X
2. Input 11
[Config]
670 Ext Ain CIO 308 no. X X X X
2. Input 14
[Config]
671 Ext Ain CIO 308 no. X X X X
2. Input 17
[Config]
672 Ext Ain CIO 308 no. X X X X
2. Input 20
[Config]
673 Ext Ain CIO 308 no. X X X X
2. Input 23
[Config]
674 Ext Ain CIO 308 no. X X X X
2. Input 26
[Config]
675 Ext Ain CIO 308 no. X X X X
2. Input 29
[Config]
676 Ext Ain CIO 308 no. X X X X
3. Input 8
[Config]

Copyright © 2023 Cummins Inc. 64 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
677 Ext Ain CIO 308 no. X X X X
3. Input 11
[Config]
678 Ext Ain CIO 308 no. X X X X
3. Input 14
[Config]
679 Ext Ain CIO 308 no. X X X X
3. Input 17
[Config]
680 Ext Ain CIO 308 no. X X X X
3. Input 20
[Config]
681 Ext Ain CIO 308 no. X X X X
3. Input 23
[Config]
682 Ext Ain CIO 308 no. X X X X
3. Input 26
[Config]
683 CIO 308 no. X X X X
3. Input 29
[Config]
684 Not used:
684-689
690 RegAddr. Control X X X X
register
address 14
691 RegAddr. Control X X X X
register
address 15
692 Not used:
692-695
696 Engine X
J1939 data,
696-699, see
Function
code 4 (EIC)
700 Actual X X X X
nominal
power
(Includes
derate etc.)
701 Group power X
transducer
used

A029X159 (Issue 31) 65 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
701 Mains power X
transducer
used
701 Mains power X X
transducer
used
702 Fan A X
running
hours [Hi]
703 Fan A X
running
hours [Lo]
704 Fan B X
running
hours [Hi]
705 Fan B X
running
hours [Lo]
706 Fan C X
running
hours [Hi]
707 Fan C X
running
hours [Lo]
708 Fan D X
running
hours [Hi]
709 Fan D X
running
hours [Lo]
710 Reserved: X X X X
710 to 736
737 Not used: X X X X
737 to 779
780 LVRT X
activated 1
781 LVRT tripped X
1
782 LVRT X
activated 2
783 LVRT tripped X
2
784 Not used:
784-789

Copyright © 2023 Cummins Inc. 66 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
R
790 EXP Generator X
Export
reactive
energy
counter,
month
[kvarh] [Hi]
R
790 EXP Group export X
reactive
energy
counter,
month
[kvarh] [Hi]
R
790 EXP Mains export X
reactive
energy
counter,
month
[kvarh] [Hi]
R
790 EXP Plant export X
reactive
energy
counter,
month
[kvarh] [Hi]
R
791 EXP Generator X
Export
reactive
energy
counter,
month
[kvarh] [Lo]
R
791 EXP Group export X
reactive
energy
counter,
month
[kvarh] [Lo]
R
791 EXP Mains export X
reactive
energy
counter,
month
[kvarh] [Lo]

A029X159 (Issue 31) 67 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
R
791 EXP Plant export X
reactive
energy
counter,
month
[kvarh] [Lo]
R
792 EXP Generator X
Export
reactive
energy
counter,
week [kvarh]
[Hi]
R
792 EXP Group export X
reactive
energy
counter,
week [kvarh]
[Hi]
R
792 EXP Mains export X
reactive
energy
counter,
week [kvarh]
[Hi]
R
792 EXP Plant export X
reactive
energy
counter,
week [kvarh]
[Hi]
R
793 EXP Generator X
Export
reactive
energy
counter,
week [kvarh]
[Lo]
R
793 EXP Group export X
reactive
energy
counter,
week [kvarh]
[Lo]

Copyright © 2023 Cummins Inc. 68 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
R
793 EXP Mains export X
reactive
energy
counter,
week [kvarh]
[Lo]
R
793 EXP Plant export X
reactive
energy
counter,
week [kvarh]
[Lo]
R
794 EXP Generator X
Export
reactive
energy
counter, total
[kvarh] [Hi]
R
794 EXP Group export X
reactive
energy
counter, total
[kvarh] [Hi]
R
794 EXP Mains export X
reactive
energy
counter, total
[kvarh] [Hi]
R
794 EXP Plant export X
reactive
energy
counter, total
[kvarh] [Hi]
R
795 EXP Generator X
Export
reactive
energy
counter, total
[kvarh] [Lo]
R
795 EXP Group export X
reactive
energy
counter, total
[kvarh] [Lo]
R
795 EXP Mains export X
reactive
energy
counter, total
[kvarh] [Lo]

A029X159 (Issue 31) 69 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
R
795 EXP Plant export X
reactive
energy
counter, total
[kvarh] [Lo]
E
796 IMP Generator X
Import active
energy
counter, total
[kWh] [Hi]
E
796 IMP Group import X
active energy
counter, total
[kWh] [Hi]
E
796 IMP Mains import X
active energy
counter, total
[kWh] [Hi]
E
796 IMP Plant import X
active energy
counter, total
[kWh] [Hi]
E
797 IMP Generator X
Import active
energy
counter, total
[kWh] [Lo]
E
797 IMP Group import X
active energy
counter, total
[kWh] [Lo]
E
797 IMP Mains import X
active energy
counter, total
[kWh] [Lo]
E
797 IMP Plant import X
active energy
counter, total
[kWh] [Lo]
E
798 IMP Generator X
Import active
energy
counter,
month [kWh]
[Hi]

Copyright © 2023 Cummins Inc. 70 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
E
798 IMP Group import X
active energy
counter,
month [kWh]
[Hi]
E
798 IMP Mains import X
active energy
counter,
month [kWh]
[Hi]
E
798 IMP Plant import X
active energy
counter,
month [kWh]
[Hi]
E
799 IMP Generator X
Import active
energy
counter,
month [kWh]
[Lo]
E
799 IMP Group import X
active energy
counter,
month [kWh]
[Lo]
E
799 IMP Mains import X
active energy
counter,
month [kWh]
[Lo]
E
799 IMP Plant import X
active energy
counter,
month [kWh]
[Lo]

5.1.5 Function Code 4 (04h): Read Input Registers (Address, Bit:


800-900)

A029X159 (Issue 31) 71 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
E
800 IMP Generator X
Import active
energy
counter,
week [kWh]
[Hi]
E
800 IMP Group import X
active energy
counter,
week [kWh]
[Hi]
E
800 IMP Mains import X
active energy
counter,
week [kWh]
[Hi]
E
800 IMP Plant import X
active energy
counter,
week [kWh]
[Hi]
E
801 IMP Generator X
Import active
energy
counter,
week [kWh]
[Lo]
E
801 IMP Group import X
active energy
counter,
week [kWh]
[Lo]
E
801 IMP Mains import X
active energy
counter,
week [kWh]
[Lo]
E
801 IMP Plant import X
active energy
counter,
week [kWh]
[Lo]
E
802 IMP Generator X
Import active
energy
counter, day
[kWh] [Hi]

Copyright © 2023 Cummins Inc. 72 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
E
802 IMP Group import X
active energy
counter, day
[kWh] [Hi]
E
802 IMP Mains import X
active energy
counter, day
[kWh] [Hi]
E
802 IMP Plant import X
active energy
counter, day
[kWh] [Hi]
E
803 IMP Generator X
Import active
energy
counter, day
[kWh] [Lo]
E
803 IMP Group import X
active energy
counter, day
[kWh] [Lo]
E
803 IMP Mains import X
active energy
counter, day
[kWh] [Lo]
E
803 IMP Plant import X
active energy
counter, day
[kWh] [Lo]
R
804 IMP Generator X
Import
reactive
energy
counter, total
[kvarh] [Hi]
R
804 IMP Group import X
reactive
energy
counter, total
[kvarh] [Hi]
R
804 IMP Mains import X
reactive
energy
counter, total
[kvarh] [Hi]

A029X159 (Issue 31) 73 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
R
804 IMP Plant import X
reactive
energy
counter, total
[kvarh] [Hi]
R
805 IMP Generator X
Import
reactive
energy
counter, total
[kvarh] [Lo]
R
805 IMP Group import X
reactive
energy
counter, total
[kvarh] [Lo]
R
805 IMP Mains import X
reactive
energy
counter, total
[kvarh] [Lo]
R
805 IMP Plant import X
reactive
energy
counter, total
[kvarh] [Lo]
R
806 IMP Generator X
Import
reactive
energy
counter,
month
[kvarh] [Hi]
R
806 IMP Generator X
Import
reactive
energy
counter,
month
[kvarh] [Lo]
R
806 IMP Group import X
reactive
energy
counter,
month
[kvarh] [Hi]

Copyright © 2023 Cummins Inc. 74 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
R
806 IMP Mains import X
reactive
energy
counter,
month
[kvarh] [Hi]
R
807 IMP Generator X
Import
reactive
energy
counter,
week [kvarh]
[Hi]
R
807 IMP Group import X
reactive
energy
counter,
month
[kvarh] [Lo]
R
807 IMP Mains import X
reactive
energy
counter,
month
[kvarh] [Lo]
R
807 IMP Plant import X
reactive
energy
counter,
month
[kvarh] [Lo]
R
808 IMP Generator X
Import
reactive
energy
counter,
week [kvarh]
[Lo]
R
808 IMP Group import X
reactive
energy
counter,
week [kvarh]
[Hi]

A029X159 (Issue 31) 75 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
R
808 IMP Mains import X
reactive
energy
counter,
week [kvarh]
[Hi]
R
808 IMP Plant import X
reactive
energy
counter,
week [kvarh]
[Hi]
R
809 IMP Generator X
Import
reactive
energy
counter, day
[kvarh] [Hi]
R
809 IMP Group import X
reactive
energy
counter,
week [kvarh]
[Lo]
R
809 IMP Mains import X
reactive
energy
counter,
week [kvarh]
[Lo]
R
809 IMP Plant import X
reactive
energy
counter,
week [kvarh]
[Lo]
R
810 IMP Generator X
Import
reactive
energy
counter, day
[kvarh] [Lo]
R
810 IMP Group import X
reactive
energy
counter, day
[kvarh] [Hi]

Copyright © 2023 Cummins Inc. 76 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
R
810 IMP Mains import X
reactive
energy
counter, day
[kvarh] [Hi]
R
810 IMP Plant import X
reactive
energy
counter, day
[kvarh] [Hi]
R
811 IMP Generator X
import
reactive
energy
counter, day
[kvarh] [Lo]
R
811 IMP Group import X
reactive
energy
counter, day
[kvarh] [Lo]
R
811 IMP Mains import X
reactive
energy
counter, day
[kvarh] [Lo]
R
811 IMP Plant import X
reactive
energy
counter, day
[kvarh] [Lo]
812 Counter Pulse X X X X
counter 01
[Hi]
813 Counter Pulse X X X X
counter 01
[Lo]
814 Counter Pulse X X X X
counter 02
[Hi]
815 Counter Pulse X X X X
counter 02
[Lo]
I
816 peak Demand of X X X X
peak current
1

A029X159 (Issue 31) 77 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
I
817 peak Demand of X X X X
peak current
2
I
818 peak Demand of X X X X
peak current
3
I
819 peak, AVG Demand of X X X X
avg. peak
current 1
I
820 peak, AVG Demand of X X X X
avg. peak
current 2
I
821 peak, AVG Demand of X X X X
avg. peak
current 3
822 Digital input X X X X
23- Local
Emergency
Stop (NO)
822.01 Digital input X X X X
24-
Utility Circuit
Breaker
Tripped (NO)
(OPEN)
822.02 Digital input X X X X
25- Utility
Circuit
Breaker
Position (A)
(NO)
(CLOSED)
822.03 Digital input X X X X
26- Genset
Circuit
Breaker
Tripped (NO)
(OPEN)
822.04 Digital input X X X X
27- Genset
Circuit
Breaker
Position (A)
(NO)
(CLOSED)

Copyright © 2023 Cummins Inc. 78 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
822.05 Digital input X X X X
43- Oil Slow
Flow Meter
822.06 Digital input X X X X
44- Fault
Reset (NO)
822.07 Digital input X X X X
45-
Customer
Input/Fault
No 1
Warning
(NO)
822.08 Digital input X X X X
46-
Customer
Input/Fault
No 2
Shutdown
(NO)
822.09 Digital input X X X X
47-
Customer
Input/Fault
No 3
Controlled
Shutdown
(NO)
822.1 Digital input X X X X
48-
Customer
Input/Fault
No 4 Earth
Fault (NO)
822.11 Digital input X X X X
49-
Customer
Input/Fault
No 5
Differential
Fault (NC)
822.12 Digital input X X X X
50-
Customer
Input/Fault
No 6
(Configurabl
e) (NO)

A029X159 (Issue 31) 79 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
822.13 Digital input X X X X
51-
Customer
Input/Fault
No 7
(Configurabl
e) (NO)
822.14 Digital input X X X X
52
822.15 Digital input X X X X
53
823 Digital input X X X X
54
823.01 Digital input X X X X
55- Fire
Protection
Trip
Shutdown
(Open to
Trip) (NC)
823.02 Digital input X X X X
112- Utility
Circuit
Breaker
Close (To)
Inhibit (NO)
823.03 Digital input X X X X
113- Genset
Circuit
Breaker
Close (To)
Inhibit (NO)
823.04 Digital input X X X X
114- Derate
Authorization
(NO)
823.05 Digital input X X X X
115- Remote
Start (NO)
823.06 Digital input X X X X
116- Alt
voltage
sensing OK
(NC)

Copyright © 2023 Cummins Inc. 80 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
823.07 Digital input X X X X
117- Start
system trip
warning (NC)
823.08 Emergency X X X X
STOP
823.09 Not used
823.1 Not used
823.11 Not used
823.12 Not used
823.13 Not used
823.14 Not used
823.15 Not used
824 Regulator X
output, GOV
[%/10]
825 Regulator X
output, AVR
[%/10]
826 Regulator X
output, PID1
[%/10]
827 Regulator X
output, PID2
[%/10]
828 Regulator X
output, PID3
[%/10]
829 Regulator X
output, PID4
[%/10]
830 Mlogic Timer X X X X
1 Remaining
831 Mlogic Timer X X X X
2 Remaining
832 Mlogic Timer X X X X
3 Remaining
833 Mlogic Timer X X X X
4 Remaining

A029X159 (Issue 31) 81 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
834 Fan X
analogue
transducer
out- put [/10]
835 External X X X X
digital
input/CIO
116 no. 1.
Input 10-
Coolant
Heater
Element Trip
835.01 External X X X X
digital
input/CIO
116 no. 1.
Input 11-
Coolant
Heater
Element CB
Feedback
835.02 External X X X X
digital
input/CIO
116 no. 1.
Input 12- Oil
Heater
Element
Gearbox Trip
835.03 External X X X X
digital
input/CIO
116 no. 1.
Input 13-
835.04 External X X X X
digital
input/CIO
116 no. 1.
Input 14- Oil
Heater
Element
(Immersion)
CB
Feedback

Copyright © 2023 Cummins Inc. 82 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
835.05 External X X X X
digital
input/CIO
116 no. 1.
Input 15- Oil
Heater Pump
CB
Feedback
835.06 External X X X X
digital
input/CIO
116 no. 1.
Input 16- Oil
Heater
Element Trip
835.07 External X X X X
digital
input/CIO
116 no. 1.
Input 17- Oil
Heater
Element
Feedback
835.08 External X X X X
digital
input/CIO
116 no. 1.
Input 19- AC
ISO Switch
Status
835.09 External X X X X
digital
input/CIO
116 no. 1.
Input 20-
Coolant
Heater Pump
Trip
835.1 External X X X X
digital
input/CIO
116 no. 1.
Input 21-
Coolant
Heater Pump
CB
Feedback

A029X159 (Issue 31) 83 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
835.11 External X X X X
digital
input/CIO
116 no. 1.
Input 22-
Alternator
Heater Trip
835.12 External X X X X
digital
input/CIO
116 no. 1.
Input 23-
Alternator
Heater CB
Feedback
835.13 External X X X X
digital
input/CIO
116 no. 1.
Input 24- HT
Valve Motor
Trip
835.14 External X X X X
digital
input/CIO
116 no. 1.
Input 25- LT
Valve Motor
Trip
835.15 External X X X X
digital
input/CIO
116 no. 1.
Input 26- AC
GFI Outlet
836 CIO 116 no. X X X X
2. Input 10-
Alternator
Auto-Lube
Alarm
836.01 CIO 116 no. X X X X
2. Input 11-
Bearing
Vibration
Warning

Copyright © 2023 Cummins Inc. 84 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
836.02 CIO 116 no. X X X X
2. Input 12-
UPS Control
Battery Low
Signal
836.03 CIO 116 no. X X X X
2. Input 13-
UPS
Replace
Control
Battery
Signal
836.04 CIO 116 no. X X X X
2. Input 14-
Customer
Convenience
DC Power is
Applied
836.05 CIO 116 no. X X X X
2. Input 15-
Spare
836.06 CIO 116 no. X X X X
2. Input 16-
ISB Power is
Applied
836.07 CIO 116 no. X X X X
2. Input 17-
Spare
836.08 CIO 116 no. X X X X
2. Input 19-
HT ACW
Stop
Indication
836.09 CIO 116 no. X X X X
2. Input 20-
HT CW Stop
Indication
836.1 CIO 116 no. X X X X
2. Input 21-
LT ACW
Stop
Indication
836.11 CIO 116 no. X X X X
2. Input 22-
LT CW Stop
Indication

A029X159 (Issue 31) 85 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
836.12 CIO 116 no. X X X X
2. Input 23-
HT AC Pump
State
836.13 CIO 116 no. X X X X
2. Input 24-
HT AC Pump
Trip
836.14 CIO 116 no. X X X X
2. Input 25-
LT AC Pump
State
836.15 CIO 116 no. X X X X
2. Input 26-
LT AC Pump
Trip
837 CIO 116 no. X X X X
3. Input 10-
HT Tank Low
Level
837.01 CIO 116 no. X X X X
3. Input 11-
HT Tank
Very Low
Level
837.02 CIO 116 no. X X X X
3. Input 12-
LT Tank Low
Level
837.03 CIO 116 no. X X X X
3. Input 13-
LT Tank
Very Low
Level
837.04 CIO 116 no. X X X X
3. Input 14-
Radiator Fan
Common
Trip Warning
837.05 CIO 116 no. X X X X
3. Input 15-
Louver
closed
warning
837.06 CIO 116 no. X X X X
3. Input 16-
Louver Trip

Copyright © 2023 Cummins Inc. 86 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
837.07 CIO 116 no. X X X X
3. Input 17-
Vent Fan
Trip Warning
837.08 CIO 116 no. X X X X
3. Input 19-
Spare
837.09 CIO 116 no. X X X X
3. Input 20-
Gearbox Oil
Tank Level
Low
837.1 CIO 116 no. X X X X
3. Input 21-
Gearbox Oil
Tank Heater
Fault
837.11 CIO 116 no. X X X X
3. Input 22-
Engine Oil
Pan Heater
Fault
837.12 CIO 116 no. X X X X
3. Input 23-
VPS2 Fault
837.13 CIO 116 no. X X X X
3. Input 24-
VPS2
Operation
837.14 CIO 116 no. X X X X
3. Input 25-
V2CPI US
Signal
837.15 CIO 116 no. X X X X
3. Input 26-
V2CPI DS
Signal
838 Not
used:838-
839
840 PID 1 X
reference
841 PID 1 actual X
842 PID 1 output X
843 PID 1 P X

A029X159 (Issue 31) 87 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
844 PID 1 I X
845 PID 1 D X
846 PID 2 X
reference
847 PID 2 actual X
848 PID 2 output X
849 PID 2 P X
850 PID 2 I X
851 PID 2 D X
852 PID 3 X
reference
853 PID 3 actual X
854 PID 3 output X
855 PID 3 P X
856 PID 3 I X
857 PID 3 D X
858 PID 4 X
reference
859 PID 4 actual X
860 PID 4 output X
862 PID 4 I X
863 PID 4 D X
864 Not used:
864-867
900 Engine
J1939 data,
900-988, see
Function
code 4 (EIC)

5.1.6 Function Code 4 (04h): Read Input Registers (Address, Bit:


1000-1003)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1000 1000 Gen. -P> 1 X
1000 1000 Group -P> 1 X

Copyright © 2023 Cummins Inc. 88 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1000 1000 Mains -P> 1 X
1000 1000 Plant -P> 1 X
1000.01 1010 Gen. -P> 2 X
1000.01 1010 Group -P> 2 X
1000.01 1010 Mains -P> 2 X
1000.01 1010 Plant -P> 2 X
1000.02 Not used
1000.03 1030 Gen. I> 1 X
1000.03 1030 Group I> 1 X
1000.03 1030 Mains I> 1 X
1000.03 1030 Plant I> 1 X
1000.04 1040 Gen. I> 2 X
1000.04 1040 Group I> 2 X
1000.04 1040 Mains I> 2 X
1000.04 1040 Plant I> 2 X
1000.05 1050 Gen. I> 3 X
1000.05 1050 Group I> 3 X
1000.05 1050 Mains I> 3 X
1000.05 1050 Plant I> 3 X
1000.06 1060 Gen. I> 4 X
1000.06 1060 Group I> 4 X
1000.06 1060 Mains I> 4 X
1000.06 1060 Plant I> 4 X
1000.07 1090 Gen. I> inv. X
1000.07 1090 Group I> inv. X
1000.07 1090 Mains I> inv. X
1000.07 1090 Plant I> inv. X
1000.08 1110 Gen. Iv> X
1000.08 1110 Group X
busbar Iv>
1000.08 1110 Mains Iv> X X
1000.09 1130 Gen. I>> 1 X
1000.09 1130 Group I>> 1 X
1000.09 1130 Mains I>> 1 X

A029X159 (Issue 31) 89 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1000.09 1130 Plant I>> 1 X
1000.1 1140 Gen I>> 2 X
1000.1 1140 Group I>> 2 X
1000.1 1140 Mains I>> 2 X
1000.1 1140 Plant I>> 2 X
1000.11 1150 Gen. U> 1 X
1000.11 1150 Group BB X
U> 1
1000.11 1150 Mains U> 1 X X
1000.12 1160 Gen. U> 2 X
1000.12 1160 Group BB X
U> 2
1000.12 1160 Mains U> 2 X X
1000.13 1170 Gen. U< 1 X
1000.13 1170 Group BB X
U< 1
1000.13 1170 Mains U< 1 X X
1000.14 1180 Gen. U< 2 X
1000.14 1180 Group BB X
U< 2
1000.14 1180 Mains U< 2 X X
1000.15 1190 Gen. U< 3 X
1000.15 1190 Group BB X
U< 3
1001 1210 Gen. f> 1 X
1001 1210 Group BB f> X
1
1001 1210 Mains f> 1 X X
1001.01 1220 Gen. f> 2 X
1001.01 1220 Group BB f> X
2
1001.01 1220 Mains f> 2 X X
1001.02 1230 Gen. f> 3 X
1001.02 1230 Group BB f> X
3
1001.02 1230 Mains f> 3 X X

Copyright © 2023 Cummins Inc. 90 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1001.03 1240 Gen. f< 1 X
1001.03 1240 Group BB f< X
1
1001.03 1240 Mains f< 1 X X
1001.04 1250 Gen. f< 2 X
1001.04 1250 Group BB f< X
2
1001.04 1250 Mains f< 2 X X
1001.05 1260 Gen. f< 3 X
1001.05 1260 Group BB f< X
3
1001.05 1260 Mains f< 3 X X
1001.06 1270 BB U> 1 X
1001.06 1270 Gen. BB U> X X
1
1001.06 1270 Group BB X
U> 1
1001.07 1280 BB U> 2 X
1001.07 1280 Gen. BB U> X X
2
1001.07 1280 Group BB X
U> 2
1001.08 1290 BB U> 3 X
1001.08 1290 Gen. BB U> X X
3
1001.08 1290 Group BB X
U> 3
1001.09 1300 BB U< 1 X
1001.09 1300 Gen. BB U< X X
1
1001.09 1300 Group BB X
U< 1
1001.1 1310 BB U< 2 X
1001.1 1310 Gen. BB U< X X
2
1001.1 1310 Group BB X
U< 2
1001.11 1320 BB U< 3 X

A029X159 (Issue 31) 91 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1001.11 1320 Gen. BB U< X X
3
1001.11 1320 Group BB X
U< 3
1001.12 1330 BB U< 4 X
1001.12 1330 Gen. BB U< X X
4
1001.12 1330 Group BB X
U< 4
1001.13 1350 BB f> 1 X
1001.13 1350 Gen. BB f> 1 X X
1001.13 1350 Group BB f> X
1
1001.14 1360 BB f> 2 X
1001.14 1360 Gen. BB f> 2 X X
1001.14 1360 Group BB f> X
2
1001.15 1370 BB f> 3 X
1001.15 1370 Gen. BB f> 3 X X
1001.15 1370 Group BB f> X
3
1002 1380 BB f< 1 X
1002 1380 Gen. BB f< 1 X X
1002 1380 Group BB f< X
1
1002.01 1390 BB f< 2 X
1002.01 1390 Gen. BB f< 2 X X
1002.01 1390 Group BB f< X
2
1002.02 1400 BB f< 3 X
1002.02 1400 Gen. BB f< 3 X X
1002.02 1400 Group BB f< X
3
1002.03 1410 BB f< 4 X
1002.03 1410 Gen. BB f< 4 X X
1002.03 1410 Group BB f< X
4

Copyright © 2023 Cummins Inc. 92 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1002.04 1420 df/dt X X X X
(ROCOF)
1002.05 1430 Vector jump X X X X
1002.06 1440 BB pos. seq. X X X X
volt. low
1002.07 1450 Gen. P> 1 X
1002.07 1450 M P> 1 X X
1002.07 1450 Mains P> 1 X
1002.08 1460 Gen. P> 2 X
1002.08 1460 M P> 2 X X
1002.08 1460 Mains P> 2 X
1002.09 1470 Gen. P> 3 X
1002.09 1470 M P> 3 X X
1002.09 1470 Mains P> 3 X
1002.1 1480 Gen. P> 4 X
1002.1 1480 M P> 4 X X
1002.1 1480 Mains P> 4 X
1002.11 1490 Gen. P> 5 X
1002.11 1490 M P> 5 X X
1002.11 1490 Mains P> 5 X
1002.12 1500 Unbalance X X X X
curr. 1
1002.13 1510 Unbalance X X X X
volt.
1002.14 1520 Gen. -Q> X
1002.14 1520 M -Q> X X
1002.14 1520 Mains -Q> X
1002.15 1530 Gen. Q> X
1002.15 1530 M Q> X X
1002.15 1530 Mains Q> X
1003 1540 Gen. neg. X
seq. I
1003 1540 Group BB X
neg. seq. I
1003 1540 Mains neg. X X
seq. I

A029X159 (Issue 31) 93 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1003.01 1550 Generator X
neg. seq. U
1003.01 1550 Group BB X
neg. seq. U
1003.01 1550 Mains neg. X X
seq. U
1003.02 1570 Gen. zero X
seq. I
1003.02 1570 Group BB X
zero seq. I
1003.02 1570 Mains zero X X
seq. I
1003.03 1580 Group BB X
zero seq. U
1003.03 1580 Mains zero X X
seq. U
1003.03 1580 Zero seq. U X
1003.04 1600 Directional X X X X
overcurrent 1
1003.05 1610 Directional X X X X
overcurrent 2
1003.06 1620 BB X
unbalance U
1003.06 1620 Gen. BB X
unbalance U
1003.06 1620 Group BB X X
unbalance U
1003.07 Not used
1003.08 Not used
1003.09 Not used
1003.1 Not used
1003.11 Not used
1003.12 Not used
1003.13 Not used
1003.14 Not used
1003.15 Not used

Copyright © 2023 Cummins Inc. 94 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

5.1.7 Function Code 4 (04h): Read Input Registers (Address, Bit:


1004-1010)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1004 Not used
1004.01 Not used
1004.02 Not used
1004.03 Not used
1004.04 Not used
1004.05 Not used
1004.06 1960 U and Q< 1 X X X X
1004.07 1970 U and Q< 2 X X X X
1004.08 1981 GB ext. trip X
1004.08 1981 TB ext. Trip X X
1004.09 1983 MB ext. trip X
1004.09 1983 MB ext. Trip X
1004.09 1983 MB ext. trip X
1004.1 1650 Ut< 1 X X X X
monitoring
active
1004.11 1660 Ut< 1 X X X X
1004.12 1690 Ut< 2 X X X X
monitoring
active
1004.13 1700 Ut< 2 X X X X
1004.14 1760 Gen. P dep. X
Q<
1004.14 1760 Group BB P X
dep. Q<
1004.14 1760 Mains P dep. X X
Q<
1004.15 1790 Gen. P dep. X
Q>
1004.15 1790 Group BB P X
dep. Q>
1004.15 1790 Mains P dep. X X
Q>

A029X159 (Issue 31) 95 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1005 2120 Synchronizin X X X X
g window
1005.01 2130 Synchronizin X
g failure GB
1005.01 2130 Synchronizin X X
g failure TB
1005.02 2140 Synchronizin X X X
g failure MB
1005.03 2150 Phase seq. X X X X
failure A
1005.04 2160 GB open X
failure
1005.04 2160 TB open X X
failure
1005.05 2170 GB close X
failure
1005.05 2170 TB close X X
failure
1005.06 2180 GB pos. X
failure
1005.06 Not used
1005.06 2180 TB pos. X X
failure
1005.07 2200 MB open X X X
failure
1005.07 Not used
1005.08 2210 MB close X X X
failure
1005.08 Not used
1005.09 2220 MB pos. X X X
failure
1005.09 Not used
1005.1 2270 Close before X
excitation
failure
1005.1 Not used
1005.11 Not used
1005.11 2155 Phase seq. X X X X
failure B
1005.12 Not used

Copyright © 2023 Cummins Inc. 96 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1005.12 Not used
1005.13 Not used
1005.13 Not used
1005.14 Not used
1005.14 Not used
1005.15 Not used
1005.15 Not used
1006 2560 GOVERNOR X
regulation
fail.
1006.01 2630 Deload error X
1006.02 2680 AVR X
regulation
fail.
1006.03 Not used
1006.04 Not used
1006.05 Not used
1007 3000 Digital alarm X X X X
input 23-
Local
Emergency
Stop (NO)
1007.01 3010 Digital alarm X X X X
input 24-
Utility Circuit
Breaker
Tripped (NO)
(OPEN)
1007.02 3020 Digital alarm X X X X
input 25-
Utility Circuit
Breaker
Position (A)
(NO)
(CLOSED)
1007.03 3030 Digital alarm X X X X
input 26-
Genset
Circuit
Breaker
Tripped (NO)
(OPEN)

A029X159 (Issue 31) 97 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1007.04 3040 Digital alarm X X X X
input 27-
Genset
Circuit
Breaker
Position (A)
(NO)
(CLOSED)
1007.05 Not used
1007.06 3060 Digital alarm X X X X
input 29
1007.07 3070 Digital alarm X X X X
input 30
1007.08 3080 Digital alarm X X X X
input 31
1007.09 3090 Digital alarm X X X X
input 32
1007.1 3100 Digital alarm X X X X
input 33
1007.11 3110 Digital alarm X X X X
input 34
1007.12 3120 Digital alarm X X X X
input 35
1007.13 Not used
1007.14 Not used
1007.15 Not used
1008 3130 Digital alarm X X X X
input 43- Oil
Slow Flow
Meter
1008.01 3140 Digital alarm X X X X
input 44-
Fault Reset
(NO)
1008.02 3150 Digital alarm X X X X
input 45-
Customer
Input/Fault
No 1
Warning
(NO)

Copyright © 2023 Cummins Inc. 98 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1008.03 3160 Digital alarm X X X X
input 46-
Customer
Input/Fault
No 2
Shutdown
(NO)
1008.05 3180 Digital alarm X X X X
input 48-
Customer
Input/Fault
No 4 Earth
Fault (NO)
1008.06 3190 Digital alarm X X X X
input 49-
Customer
Input/Fault
No 5
Differential
Fault (NC)
1008.07 3200 Digital alarm X X X X
input 50-
Customer
Input/Fault
No 6
(Configurabl
e) (NO)
1008.08 3210 Digital alarm X X X X
input 51-
Customer
Input/Fault
No 7
(Configurabl
e) (NO)
1008.09 3220 Digital alarm X X X X
input 52
1008.1 3230 Digital alarm X X X X
input 53
1008.11 3240 Digital alarm X X X X
input 54
1008.12 3250 Digital alarm X X X X
input 55- Fire
Protection
Trip
Shutdown
(Open to
Trip) (NC)
1008.13 Not used

A029X159 (Issue 31) 99 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1008.14 3170 Digital alarm X X X X
input 47-
Customer
Input/Fault
No 3
Controlled
Shutdown
(NO)
1008.14 Not used
1008.15 Not used
1009 3260 Digital alarm X X X X
input 65
1009.01 3270 Digital alarm X X X X
input 66
1009.02 3280 Digital alarm X X X X
input 67
1009.03 3290 Digital alarm X X X X
input 68
1009.04 3300 Digital alarm X X X X
input 69
1009.05 3310 Digital alarm X X X X
input 70
1009.06 3320 Digital alarm X X X X
input 71
1009.07 3330 Digital alarm X X X X
input 91
1009.08 3340 Digital alarm X X X X
input 92
1009.09 3350 Digital alarm X X X X
input 93
1009.1 3360 Digital alarm X X X X
input 94
1009.11 3370 Digital alarm X X X X
input 95
1009.12 3380 Digital alarm X X X X
input 96
1009.13 3390 Digital alarm X X X X
input 97
1009.14 Not used
1009.15 Not used

Copyright © 2023 Cummins Inc. 100 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1010 3400 Multi-in. X X
Alarm 102-
Alternator
Bearing DE
1010 3400 Multi-in. X
Alarm 102-
Alternator
Bearing DE
1010 3400 Wire fail. X
102-
Alternator
Bearing DE
1010.01 3410 Multi-in. X X
Alarm 105-
Alternator
Bearing NDE
1010.01 3410 Multi-in. X
Alarm 105-
Alternator
Bearing NDE
1010.01 3410 Wire fail. X
105-
Alternator
Bearing NDE
1010.02 3420 Multi-in. X X
Alarm 108
1010.02 3420 Multi-in. X
Alarm 108
1010.02 3420 Wire fail. 108 X
1010.03 3401 Wire fail. X X X X
102-
Alternator
Bearing DE
1010.04 3411 Wire fail. X X X X
105-
Alternator
Bearing NDE
1010.05 3421 Wire fail. 108 X X X X
1010.06 3430 Digital alarm X X X X
input 112-
Utility Circuit
Breaker
Close (To)
Inhibit (NO)

A029X159 (Issue 31) 101 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1010.07 3440 Digital alarm X X X X
input 113-
Genset
Circuit
Breaker
Close (To)
Inhibit (NO)
1010.08 3450 Digital alarm X X X X
input 114-
Derate
Authorization
(NO)
1010.09 3460 Digital alarm X X X X
input 115-
Remote Start
(NO)
1010.1 3470 Digital alarm X X X X
input 116- Alt
voltage
sensing OK
(NC)
1010.11 3480 Digital alarm X X X X
input 117-
Start system
trip warning
(NC)
1010.12 3490 Digital alarm X X X X
input 118-
Emergency
stop
1010.13 Not used
1010.14 Not used
1010.15 Not used
1010.15 Stop coil X
relay

5.1.8 Function Code 4 (04h): Read Input Registers (Address, Bit:


1011-1017)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1011 3500 Digital alarm X X X X
input 127

Copyright © 2023 Cummins Inc. 102 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1011.01 3510 Digital alarm X X X X
input 128
1011.02 3520 Digital alarm X X X X
input 129
1011.03 3530 Digital alarm X X X X
input 130
1011.04 3540 Digital alarm X X X X
input 131
1011.05 3550 Digital alarm X X X X
input 132
1011.06 3560 Digital alarm X X X X
input 133
1011.07 3570 M-Logic X X X X
alarm 1
1011.08 3580 M-Logic X X X X
alarm 2
1011.09 3590 M-Logic X X X X
alarm 3
1011.1 3600 M-Logic X X X X
alarm 4
1011.11 3610 M-Logic X X X X
alarm 5
1011.12 Not used
1011.13 Not used
1011.14 Not used
1011.15 Not used
1012 4000 Analogue X X X X
input 91.1
1012.01 4010 Analogue X X X X
input 91.2
1012.02 4020 Wire failure X X X X
analogue 91
1012.03 4030 Analogue X X X X
input 93.1
1012.04 4040 Analogue X X X X
input 93.2
1012.05 4050 Wire failure X X X X
analogue 93
1012.06 4060 Analogue X X X X
input 95.1

A029X159 (Issue 31) 103 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1012.07 4070 Analogue X X X X
input 95.2
1012.08 4080 Wire failure X X X X
analogue 95
1012.09 4090 Analogue X X X X
input 97.1
1012.1 4100 Analogue X X X X
input 97.2
1012.11 4110 Wire failure X X X X
analogue 97
1012.12 Not used
1012.13 Not used
1012.14 Not used
1012.15 Not used
1013 4120 Multi input X X X X
terminal
102.1
1013 4160 Multi input X X X X
terminal
102.1
1013 4180 Multi input X X X X
terminal
102.1
1013 4200 Multi input X X X X
terminal
102.1
1013 4220 Multi input X X X X
terminal
102.1
1013.01 4130 Multi input X X X X
terminal
102.2
1013.01 4170 Multi input X X X X
terminal
102.2
1013.01 4190 Multi input X X X X
terminal
102.2
1013.01 4210 Multi input X X X X
terminal
102.2

Copyright © 2023 Cummins Inc. 104 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1013.01 4230 Multi input X X X X
terminal
102.2
1013.02 4240 W. fail. 102 X X X X
1013.03 4250 Multi input X X X X
terminal
105.1
1013.03 4290 Multi input X X X X
terminal
105.1
1013.03 4310 Multi input X X X X
terminal
105.1
1013.03 4330 Multi input X X X X
terminal
105.1
1013.03 4350 Multi input X X X X
terminal
105.1
1013.04 4260 Multi input X X X X
terminal
105.2
1013.04 4300 Multi input X X X X
terminal
105.2
1013.04 4320 Multi input X X X X
terminal
105.2
1013.04 4340 Multi input X X X X
terminal
105.2
1013.04 4360 Multi input X X X X
terminal
105.2
1013.05 4370 W. fail. 105 X X X X
1013.06 4380 Multi input X X X X
terminal
108.1
1013.06 4420 Multi input
terminal
108.1
1013.06 4440 Multi input
terminal
108.1

A029X159 (Issue 31) 105 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1013.06 4460 Multi input
terminal
108.1
1013.06 4480 Multi input
terminal
108.1
1013.07 4390 Multi input X X X X
terminal
108.2
1013.07 4430 Multi input
terminal
108.2
1013.07 4450 Multi input
terminal
108.2
1013.07 4470 Multi input
terminal
108.2
1013.07 4490 Multi input
terminal
108.2
1013.08 4500 W. fail. 108 X X X X
1013.09 4510 Overspeed 1 X
1013.1 4520 Overspeed 2 X
1013.11 4530 Crank failure X
1013.12 4540 Running X
feedback
failure
1013.13 4550 MPU wire X
failure
1013.14 4560 Hz/V failure X
1013.15 4570 Start failure X
1014 4580 Stop failure X
1014.01 4960 U< aux. X
term. 1
1014.02 4970 U> aux. X
term. 1
1014.03 4980 U< aux. X
term. 98
1014.04 4990 U> aux. X
term. 98

Copyright © 2023 Cummins Inc. 106 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1014.05 4590 Underspeed X
1
1014.06 Not used
1014.07 Not used
1014.08 Not used
1014.09 Not used
1014.1 Not used
1014.11 Not used
1014.12 Not used
1014.13 Not used
1014.14 Not used
1014.15 Not used
1015 6110 Service timer X
1
1015.01 6120 Service timer X
2
1015.02 6270 Stop coil wire X
break
1015.03 6280 Internal X X X X
communicati
on failure
1015.04 6270 Standby heat X
1 alarm
1015.05 Not used
1015.07 Not used
1015.08 Not used
1015.09 Not used
1015.1 Not used
1015.11 Not used
1015.12 6540 Unit not in X X X X
auto
1015.13 6940 Fuel pump X X X X
logic
1015.14 6290 Standby heat X
2 alarm
1015.15 Not used
1015.16 Not used

A029X159 (Issue 31) 107 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1016 5000 Relay 5 X X X X
1016.01 5010 Relay 8 X X X X
1016.02 5020 Relay 11 X X X X
1016.03 5030 Relay 14 X X X X
1016.04 5040 Relay 17 X X X X
1016.05 5050 Relay T20 X X X X
1016.06 5060 Relay T21 X X X X
1016.07 5070 Relay 29 X X X X
1016.08 5080 Relay 31 X X X X
1016.09 5090 Relay 33 X X X X
1016.1 5100 Relay 35 X X X X
1016.11 5110 Relay 57 X X X X
1016.12 5120 Relay 59 X X X X
1016.13 5130 Relay 61 X X X X
1016.14 5140 Relay 63 X X X X
1016.15 Not used
1017 5150 Relay 65 X X X X
1017.01 5160 Relay 67 X X X X
1017.02 5170 Relay 69 X X X X
1017.03 5180 Relay 71 X X X X
1017.04 5190 Relay 90 X X X X
1017.05 5200 Relay 92 X X X X
1017.06 5210 Relay 94 X X X X
1017.07 5220 Relay 96 X X X X
1017.08 5230 Relay 126 X X X X
1017.09 5240 Relay 128 X X X X
1017.1 5250 Relay 130 X X X X
1017.11 5260 Relay 132 X X X X
1017.12 Run. coil X
relay
1017.13 Start prepare X
1017.14 Start relay X

Copyright © 2023 Cummins Inc. 108 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

5.1.9 Function Code 4 (04h): Read Input Registers (Address, Bit:


1018-1040)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1018 Mains failure X X
1018 Mains failure X
(stand-
alone)
1018.01 MB position X X
ON
1018.01 MB position X
ON (stand-
alone)
1018.02 DG ramp X
down
1018.03 Start X
GOV/AVR
reg- ulation
1018.04 GB position X
ON
1018.04 TB position X X
ON
1018.05 GB X
synchronizin
g
1018.05 TB X X
synchronizin
g
1018.06 Engine X
running
1018.07 6173 Running X
detected,
timer expired
1018.08 6220 DG Hz/V OK, X
timer expired
1018.09 Not used
1018.1 Not used
1018.11 GB position X
OFF
1018.11 TB position X X
OFF

A029X159 (Issue 31) 109 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1018.12 MB position X X
OFF
1018.12 MB position X
OFF (stand-
alone)
1018.13 BB Hz/V OK X
1018.13 BB Hz/V OK X X
1018.13 Generator X
BB Hz/V OK
1018.14 MB X
synchronizin
g (stand-
alone)
1018.14 Single DG, X X
MB syn-
chronising
1018.15 Dry mode X
1019 Block mode X
1019.01 Manual X
mode
1019.02 Semi auto X X X X
mode
1019.03 Auto mode X X X X
1019.04 Test X X X X
1019.05 Island X X X X
1019.06 AMF X X X X
1019.07 Peak X X X X
shaving
1019.08 Fixed power X X X X
1019.09 Mains power X X X X
export
1019.1 Load X X X X
takeover
1019.11 Genset X
Group
1019.11 Power X
management
1019.12 Not used
1019.13 Not used

Copyright © 2023 Cummins Inc. 110 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1019.15 AMF active X X
1019.15 AMF active X
(stand-
alone)
1019.4 Not used
1020 Engine X
J1939 data,
1020-1029,
see Function
code 4 (EIC)
1030 CIO 208 no. X X X X
3. Out-
put 9
1030.01 CIO 208 no. X X X X
3. Out-
put 11
1030.02 CIO 208 no. X X X X
3. Out-
put 13
1030.03 CIO 208 no. X X X X
3. Out-
put 15
1030.04 CIO 208 no. X X X X
3. Out-
put 18
1030.05 CIO 208 no. X X X X
3. Out-
put 21
1030.06 CIO 208 no. X X X X
3. Out-
put 24
1030.07 CIO 208 no. X X X X
3. Out-
put 27
1030.08 Not used
1030.09 Not used
1030.1 Not used
1030.11 Not used
1030.12 Not used

A029X159 (Issue 31) 111 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1030.13 Not used
1030.14 Not used
1030.15 Not used
1031 Not used:
1031-1032
1033 Reserved X X X X
1033.01 Reserved X X X X
1033.02 7520 Ext . X X X X
communicati
on error
1033.03 Not used
1033.04 Not used
1033.05 Not used
1033.06 Not used
1033.07 Not used
1033.08 Not used
1033.09 Not used
1033.1 Not used
1033.11 Not used
1033.12 Not used
1033.13 Not used
1033.14 Not used
1033.15 Not used
1034 Reserved X X X X
1034.01 Ext. Modbus X X X X
comm. error
on CAN ID 1
1034.02 Ext. Modbus X X X X
comm. error
on CAN ID 2
1034.03 Ext. Modbus X X X X
comm. error
on CAN ID 3
1034.04 Ext. Modbus X X X X
comm. error
on CAN ID 4

Copyright © 2023 Cummins Inc. 112 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1034.05 Ext. Modbus X X X X
comm. error
on CAN ID 5
1034.06 Ext. Modbus X X X X
comm. error
on CAN ID 6
1034.07 Ext. Modbus X X X X
comm. error
on CAN ID 7
1034.08 Ext. Modbus X X X X
comm. error
on CAN ID 8
1034.09 Ext. Modbus X X X X
comm. error
on CAN ID 9
1034.1 Ext. Modbus X X X X
comm. error
on CAN ID
10
1034.11 Ext. Modbus X X X X
comm. error
on CAN ID
11
1034.12 Ext. Modbus X X X X
comm. error
on CAN ID
12
1034.13 Ext. Modbus X X X X
comm. error
on CAN ID
13
1034.14 Ext. Modbus X X X X
comm. error
on CAN ID
14
1034.15 Ext. Modbus X X X X
comm. error
on CAN ID
15
1035 Ext. Modbus X X X X
comm. error
on CAN ID
16
1035.01 Not used
1035.02 Not used

A029X159 (Issue 31) 113 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1035.03 Not used
1035.04 Not used
1035.06 Not used
1035.07 Not used
1035.08 Not used
1035.09 Not used
1035.1 Not used
1035.11 Not used
1035.12 Not used
1035.13 Not used
1035.14 Not used
1035.15 Not used
1036 12000 Ext. X X X X
Analogue in.
1.1
1036.01 12010 Ext. X X X X
Analogue in.
1.2
1036.02 Not used
1036.04 12040 Ext. X X X X
Analogue in.
2.2
1036.05 Not used
1036.06 12060 Ext. X X X X
Analogue in.
3.1
1036.07 12070 Ext. X X X X
Analogue in.
3.2
1036.08 Not used
1036.09 12090 Ext. X X X X
Analogue in.
4.1
1036.1 12100 Ext. X X X X
Analogue in.
4.2
1036.11 Not used

Copyright © 2023 Cummins Inc. 114 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1036.12 12120 Ext. X X X X
Analogue in.
5.1
1036.13 12030 Ext. X X X X
Analogue in.
2.1
1036.13 12130 Ext. X X X X
Analogue in.
5.2
1036.14 Not used
1036.15 12150 Ext. X X X X
Analogue in.
6.1
1037 12160 Ext. X X X X
Analogue in.
6.2
1037.01 Not used
1037.02 12180 Ext. X X X X
Analogue in.
7.1
1037.03 12190 Ext. X X X X
Analogue in.
7.2
1037.04 Not used
1037.05 12210 Ext. X X X X
Analogue in.
8.1
1037.06 12220 Ext. X X X X
Analogue in.
8.2
1037.07 Not used
1037.08 Not used
1037.09 Not used
1037.1 Not used
1037.11 Not used
1037.12 Not used
1037.13 Not used
1037.14 Not used
1037.15 Not used
1038 12540 External X X X X
digital input 1

A029X159 (Issue 31) 115 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1038.01 12550 External X X X X
digital input 2
1038.02 12560 External X X X X
digital input 3
1038.03 12570 External X X X X
digital input 4
1038.04 12580 External X X X X
digital input 5
1038.05 12590 External X X X X
digital input 6
1038.06 12600 External X X X X
digital input 7
1038.07 12610 External X X X X
digital input 8
1038.08 12620 External X X X X
digital input 9
1038.09 12630 External X X X X
digital input
10
1038.1 12640 External X X X X
digital input
11
1038.11 12650 External X X X X
digital input
12
1038.12 12660 External X X X X
digital input
13
1038.13 12670 External X X X X
digital input
14
1038.14 12680 External X X X X
digital input
15
1038.15 12690 External X X X X
digital input
16
1039 12790 External X X X X
digital output
1
1039.01 12800 External X X X X
digital output
2

Copyright © 2023 Cummins Inc. 116 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1039.02 12810 External X X X X
digital output
3
1039.03 12820 External X X X X
digital output
4
1039.04 12830 External X X X X
digital output
5
1039.05 12840 External X X X X
digital output
6
1039.06 12850 External X X X X
digital output
7
1039.07 12860 External X X X X
digital output
8
1039.08 12870 External X X X X
digital output
9
1039.09 12880 External X X X X
digital output
10
1039.1 12890 External X X X X
digital output
11
1039.11 12900 External X X X X
digital output
12
1039.12 12910 External X X X X
digital output
13
1039.13 12920 External X X X X
digital output
14
1039.14 12930 External X X X X
digital output
15
1039.15 12940 External X X X X
digital output
16
1040 CAN Pri. X X X X
missing ID 1

A029X159 (Issue 31) 117 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1040.01 CAN Pri. X X X X
missing ID 2
1040.02 CAN Pri. X X X X
missing ID 3
1040.03 CAN Pri. X X X X
missing ID 4
1040.04 CAN Pri. X X X X
missing ID 5
1040.05 CAN Pri. X X X X
missing ID 6
1040.06 CAN Pri. X X X X
missing ID 7
1040.07 CAN Pri. X X X X
missing ID 8
1040.08 CAN Pri. X X X X
missing ID 9
1040.09 CAN Pri. X X X X
missing ID
10
1040.1 CAN Pri. X X X X
missing ID
11
1040.11 CAN Pri. X X X X
missing ID
12
1040.12 CAN Pri. X X X X
missing ID
13
1040.13 CAN Pri. X X X X
missing ID
14
1040.14 CAN Pri. X X X X
missing ID
15
1040.15 CAN Pri. X X X X
missing ID
16

Copyright © 2023 Cummins Inc. 118 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

5.1.10 Function Code 4 (04h): Read Input Registers (Address, Bit:


1041-1054)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1041 CAN Pri. X X X X
missing ID
17
1041.01 CAN Pri. X X X X
missing ID
18
1041.02 CAN Pri. X X X X
missing ID
19
1041.03 CAN Pri. X X X X
missing ID
20
1041.04 CAN Pri. X X X X
missing ID
21
1041.05 CAN Pri. X X X X
missing ID
22
1041.06 CAN Pri. X X X X
missing ID
23
1041.07 CAN Pri. X X X X
missing ID
24
1041.08 CAN Pri. X X X X
missing ID
25
1041.09 CAN Pri. X X X X
missing ID
26
1041.1 CAN Pri. X X X X
missing ID
27
1041.11 CAN Pri. X X X X
missing ID
28
1041.12 CAN Pri. X X X X
missing ID
29

A029X159 (Issue 31) 119 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1041.13 CAN Pri. X X X X
missing ID
30
1041.14 CAN Pri. X X X X
missing ID
31
1041.15 CAN Pri. X X X X
missing ID
32
1042 CAN Pri. X X
missing ID
33
1042.01 CAN Pri. X X
missing ID
34
1042.02 CAN Pri. X X
missing ID
35
1042.03 CAN Pri. X X
missing ID
36
1042.04 CAN Pri. X X
missing ID
37
1042.05 CAN Pri. X X
missing ID
38
1042.06 CAN Pri. X X
missing ID
39
1042.07 CAN Pri. X X
missing ID
40
1042.08 Not used
1042.09 Not used
1042.1 Not used
1042.11 Not used
1042.12 Not used
1042.13 Not used
1042.14 Not used
1042.15 Not used

Copyright © 2023 Cummins Inc. 120 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1043 CAN Sec. X X X X
missing ID 1
1043.01 CAN Sec. X X X X
missing ID 2
1043.02 CAN Sec. X X X X
missing ID 3
1043.03 CAN Sec. X X X X
missing ID 4
1043.04 CAN Sec. X X X X
missing ID 5
1043.05 CAN Sec. X X X X
missing ID 6
1043.06 CAN Sec. X X X X
missing ID 7
1043.07 CAN Sec. X X X X
missing ID 8
1043.08 CAN Sec. X X X X
missing ID 9
1043.09 CAN Sec. X X X X
missing ID
10
1043.1 CAN Sec. X X X X
missing ID
11
1043.11 CAN Sec. X X X X
missing ID
12
1043.12 CAN Sec. X X X X
missing ID
13
1043.13 CAN Sec. X X X X
missing ID
14
1043.14 CAN Sec. X X X X
missing ID
15
1043.15 CAN Sec. X X X X
missing ID
16
1044 CAN Sec. X X X X
missing ID
17

A029X159 (Issue 31) 121 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1044.01 CAN Sec. X X X X
missing ID
18
1044.02 CAN Sec. X X X X
missing ID
19
1044.03 CAN Sec. X X X X
missing ID
20
1044.04 CAN Sec. X X X X
missing ID
21
1044.05 CAN Sec. X X X X
missing ID
22
1044.06 CAN Sec. X X X X
missing ID
23
1044.07 CAN Sec. X X X X
missing ID
24
1044.08 CAN Sec. X X X X
missing ID
25
1044.09 CAN Sec. X X X X
missing ID
26
1044.1 CAN Sec. X X X X
missing ID
27
1044.11 CAN Sec. X X X X
missing ID
28
1044.12 CAN Sec. X X X X
missing ID
29
1044.13 CAN Sec. X X X X
missing ID
30
1044.14 CAN Sec. X X X X
missing ID
31
1044.15 CAN Sec. X X X X
missing ID
32

Copyright © 2023 Cummins Inc. 122 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1045 CAN Sec. X X
missing ID
33
1045.01 CAN Sec. X X
missing ID
34
1045.02 CAN Sec. X X
missing ID
35
1045.03 CAN Sec. X X
missing ID
36
1045.04 CAN Sec. X X
missing ID
37
1045.05 CAN Sec. X X
missing ID
38
1045.06 CAN Sec. X X
missing ID
39
1045.07 CAN Sec. X X
missing ID
40
1045.08 Not used
1045.09 Not used
1045.1 Not used
1045.11 Not used
1045.12 Not used
1045.13 Not used
1045.14 Not used
1045.15 Not used
1046 4800 Analogue X X X X
input 127.1
1046.01 4810 Analogue X X X X
input 127.2
1046.02 4820 Wire fail X X X X
analogue
input 127
1046.03 4830 Analogue X X X X
input 129.1

A029X159 (Issue 31) 123 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1046.04 4840 Analogue X X X X
input 129.2
1046.05 4850 Wire fail X X X X
analogue
input 129
1046.06 4860 Analogue X X X X
input 131.1
1046.07 4870 Analogue X X X X
input 131.2
1046.08 4880 Wire fail X X X X
analogue
input 131
1046.09 4890 Analogue X X X X
input 133.1
1046.1 4900 Analogue X X X X
input 133.2
1046.11 4910 Wire fail X X X X
analogue
input 133
1046.12 Not used
1046.13 Not used
1046.14 Not used
1046.15 Not used
1047 Top level X X
CAN miss-
ing ID 1
1047.01 Top level X X
CAN miss-
ing ID 2
1047.02 Top level X X
CAN miss-
ing ID 3
1047.03 Top level X X
CAN miss-
ing ID 4
1047.04 Top level X X
CAN miss-
ing ID 5
1047.05 Top level X X
CAN miss-
ing ID 6

Copyright © 2023 Cummins Inc. 124 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1047.06 Top level X X
CAN miss-
ing ID 7
1047.07 Top level X X
CAN miss-
ing ID 8
1047.08 Top level X X
CAN miss-
ing ID 9
1047.09 Top level X X
CAN miss-
ing ID 10
1047.1 Top level X X
CAN miss-
ing ID 11
1047.11 Top level X X
CAN miss-
ing ID 12
1047.12 Top level X X
CAN miss-
ing ID 13
1047.13 Top level X X
CAN miss-
ing ID 14
1047.14 Top level X X
CAN miss-
ing ID 15
1047.15 Top level X X
CAN miss-
ing ID 16
1048 Top level X X
CAN miss-
ing ID 17
1048.01 Top level X X
CAN miss-
ing ID 18
1048.02 Top level X X
CAN miss-
ing ID 19
1048.03 Top level X X
CAN miss-
ing ID 20
1048.04 Top level X X
CAN miss-
ing ID 21

A029X159 (Issue 31) 125 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1048.05 Top level X X
CAN miss-
ing ID 22
1048.06 Top level X X
CAN miss-
ing ID 23
1048.07 Top level X X
CAN miss-
ing ID 24
1048.08 Top level X X
CAN miss-
ing ID 25
1048.09 Top level X X
CAN miss-
ing ID 26
1048.1 Top level X X
CAN miss-
ing ID 27
1048.11 Top level X X
CAN miss-
ing ID 28
1048.12 Top level X X
CAN miss-
ing ID 29
1048.13 Top level X X
CAN miss-
ing ID 30
1048.14 Top level X X
CAN miss-
ing ID 31
1048.15 Top level X X
CAN miss-
ing ID 32
1049 Not used
1050 Ready to X
autostart
1050.01 DG X
U>30%*U
nomi- nal
1050.01 Group BB X
U>30%*U
nominal

Copyright © 2023 Cummins Inc. 126 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1050.01 Mains X X
U>30%*U
nominal
1050.02 BB X
U>30%*U
nomi- nal
1050.02 BB X
U>30%*U
nomi- nal
1050.02 Generator X
BB
U>30%*U
nominal
1050.02 Group BB X
U>30%*U
nominal
1050.03 Not used
1050.04 Not used
1050.05 Not used
1050.06 Not used
1050.07 Not used
1050.08 Not used
1050.09 Not used
1050.1 Not used
1050.11 Not used
1050.12 Not used
1050.13 Not used
1050.14 Not used
1050.15 Not used
1051 Virtual X X X X
events 1-16
1052 Virtual X X X X
events 17-32
1053 6590 Fan A X
Failure
1053.01 6600 Fan B X
Failure
1053.02 6610 Fan C X
Failure

A029X159 (Issue 31) 127 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1053.03 6620 Fan D X
Failure
1053.04 4610 Delta X X X X
analogue 1 -
fail 1
1053.05 4620 Delta X X X X
analogue 1 -
fail 2
1053.06 4630 Delta X X X X
analogue 2 -
fail 1
1053.07 4640 Delta X X X X
analogue 2 -
fail 2
1053.08 4650 Delta X X X X
analogue 3 -
fail 1
1053.09 4660 Delta X X X X
analogue 3 -
fail 2
1053.1 4680 Delta X X X X
analogue 4 -
fail 1
1053.11 4690 Delta X X X X
analogue 4 -
fail 2
1053.12 4700 Delta X X X X
analogue 5 -
fail 1
1053.13 4710 Delta X X X X
analogue 5 -
fail 2
1053.14 4720 Delta X X X X
analogue 6 -
fail 1
1053.15 4730 Delta X X X X
analogue 6 -
fail 2
1054 Not used
1054.01 Not used
1054.02 Not used
1054.03 6202 External X
Engine Stop

Copyright © 2023 Cummins Inc. 128 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1054.04 1710 Unbalance X X X X
curr. 2
1054.05 7480 Avg U BB > X X X X
1
1054.06 7490 Avg U BB > X X X X
2
1054.07 Not used
1054.08 Not used
1054.09 Not used
1054.1 Not used
1054.11 Not used
1054.12 Not used
1054.13 Not used
1054.14 Not used
1054.15 Not used

5.1.11 Function Code 4 (04h): Read Input Registers (Address, Bit:


1055-1650)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1055 Not used
1055.01 Not used
1055.02 Not used
1055.03 Not used
1055.04 4750 Delta X X X X
analogue 7 -
fail 1
1055.05 4760 Delta X X X X
analogue 7 -
fail 2
1055.06 4770 Delta X X X X
analogue 8 -
fail 1
1055.07 4780 Delta X X X X
analogue 8 -
fail 2

A029X159 (Issue 31) 129 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1055.08 4790 Delta X X X X
analogue 9 -
fail 1
1055.09 4800 Delta X X X X
analogue 9 -
fail 2
1055.1 Reserved X X X X
1055.11 Reserved X X X X
1055.12 Reserved X X X X
1055.13 Reserved X X X X
1055.14 Reserved X X X X
1055.15 Reserved X X X X
1056 7830 Digital AVR X
Communicati
on Error
1056.01 7761 Digital AVR X
Warning
1056.02 7763 Digital AVR X
Trip
1056.03 Not used
1056.04 Not used
1056.05 Not used
1056.06 Not used
1056.07 Not used
1056.08 Not used
1056.09 Not used
1056.1 Not used
1056.11 Not used
1056.12 Not used
1056.13 Not used
1056.14 Not used
1056.15 Not used
1057 Alarm active: X X X X
Block
1057.01 Alarm active: X X X X
Warn- ing
1057.02 Alarm active: X
Trip GB

Copyright © 2023 Cummins Inc. 130 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1057.02 Alarm active: X X X
Trip TB
1057.03 Alarm active: X
Trip GB +
stop
1057.04 Alarm active: X
Shut- down
1057.05 Alarm active: X X X
Trip MB
1057.05 Alarm active: X
Trip MB
(stand-alone)
1057.06 Alarm active: X
Safety stop
1057.07 Alarm active: X
Trip MB/GB
1057.07 Alarm active: X X X
Trip MB/TB
1057.08 Alarm active: X
Controlled
stop (deload
+ cooldown)
1057.09 Not used
1057.1 Not used
1057.11 Not used
1057.12 Not used
1057.13 Not used
1057.14 Not used
1057.15 Not used
1058 Engine
J1939 data,
1058-1075,
see Function
code 4 (EIC)
1076 Average X X X X
Voltage
PhPh
1077 Average X X X X
Voltage PhN
1078 Average X X X X
Frequency

A029X159 (Issue 31) 131 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1079 Average X X X X
Current
1080 Engine X
J1939 data,
1080-1106,
see Function
code 4 (EIC)
1500 Total active X X X X
power in
present
section
1501 Total X X X X
available
power in
present sec-
tion
1502 Total X X X X
nominal
power in
present sec-
tion
1503 Total active X X X
DG power in
present
section
1504 Total X X X X
reactive
power in
present sec-
tion
1505 Number of X X X
gensets in
application
1506 Plant type X X X X
1507 Load- X X
dependent
stop, active
setpoint
1508 Load- X X
dependent
start, active
setpoint
1509 Not used
1510 Nominal X X X X
power ID 1

Copyright © 2023 Cummins Inc. 132 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1511 Nominal X X X X
power ID 2
1512 Nominal X X X X
power ID 3
1513 Nominal X X X X
power ID 4
1514 Nominal X X X X
power ID 5
1515 Nominal X X X X
power ID 6
1516 Nominal X X X X
power ID 7
1517 Nominal X X X X
power ID 8
1518 Nominal X X X X
power ID 9
1519 Nominal X X X X
power ID 10
1520 Nominal X X X X
power ID 11
1521 Nominal X X X X
power ID 12
1522 Nominal X X X X
power ID 13
1523 Nominal X X X X
power ID 14
1524 Nominal X X X X
power ID 15
1525 Nominal X X X X
power ID 16
1526 Active Power X X X X
ID 1
1527 Active Power X X X X
ID 2
1528 Active Power X X X X
ID 3
1529 Active Power X X X X
ID 4
1530 Active Power X X X X
ID 5

A029X159 (Issue 31) 133 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1531 Active Power X X X X
ID 6
1532 Active Power X X X X
ID 7
1533 Active Power X X X X
ID 8
1534 Active Power X X X X
ID 9
1535 Active Power X X X X
ID 10
1536 Active Power X X X X
ID 11
1537 Active Power X X X X
ID 12
1538 Active Power X X X X
ID 13
1539 Active Power X X X X
ID 14
1540 Active Power X X X X
ID 15
1541 Active Power X X X X
ID 16
1542 Reactive X X X X
Power ID 1
1543 Reactive X X X X
Power ID 2
1544 Reactive X X X X
Power ID 3
1545 Reactive X X X X
Power ID 4
1546 Reactive X X X X
Power ID 5
1547 Reactive X X X X
Power ID 6
1548 Reactive X X X X
Power ID 7
1549 Reactive X X X X
Power ID 8
1550 Reactive X X X X
Power ID 9

Copyright © 2023 Cummins Inc. 134 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1551 Reactive X X X X
Power ID 10
1552 Reactive X X X X
Power ID 11
1553 Reactive X X X X
Power ID 12
1554 Reactive X X X X
Power ID 13
1555 Reactive X X X X
Power ID 14
1556 Reactive X X X X
Power ID 15
1557 Reactive X X X X
Power ID 16
1558 Not used:
1558-1568
1569 Active Power X X X X
ID 17
1570 Active Power X X X X
ID 18
1571 Active Power X X X X
ID 19
1572 Active Power X X X X
ID 20
1573 Active Power X X X X
ID 21
1574 Active Power X X X X
ID 22
1575 Active Power X X X X
ID 23
1576 Active Power X X X X
ID 24
1577 Active Power X X X X
ID 25
1578 Active Power X X X X
ID 26
1579 Active Power X X X X
ID 27
1580 Active Power X X X X
ID 28

A029X159 (Issue 31) 135 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1581 Active Power X X X X
ID 29
1582 Active Power X X X X
ID 30
1583 Active Power X X X X
ID 31
1584 Active Power X X X X
ID 32
1585 Reactive X X X X
Power ID 17
1586 Reactive X X X X
Power ID 18
1587 Reactive X X X X
Power ID 19
1588 Reactive X X X X
Power ID 20
1589 Reactive X X X X
Power ID 21
1590 Reactive X X X X
Power ID 22
1591 Reactive X X X X
Power ID 23
1592 Reactive X X X X
Power ID 24
1593 Reactive X X X X
Power ID 25
1594 Reactive X X X X
Power ID 26
1595 Reactive X X X X
Power ID 27
1596 Reactive X X X X
Power ID 28
1597 Reactive X X X X
Power ID 29
1598 Reactive X X X X
Power ID 30
1599 Reactive X X X X
Power ID 31
1600 Reactive X X X X
Power ID 32

Copyright © 2023 Cummins Inc. 136 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1601 Active Power X X
ID 33
1602 Active Power X X
ID 34
1603 Active Power X X
ID 35
1604 Active Power X X
ID 36
1605 Active Power X X
ID 37
1606 Active Power X X
ID 38
1607 Active Power X X
ID 39
1608 Active Power X X
ID 40
1609 Reactive X X
Power ID 33
1610 Reactive X X
Power ID 34
1611 Reactive X X
Power ID 35
1612 Reactive X X
Power ID 36
1613 Reactive X X
Power ID 37
1614 Reactive X X
Power ID 38
1615 Reactive X X
Power ID 39
1616 Reactive X X
Power ID 40
1617 Not used:
1617-1648
1649 Mains X X X X
transducer-
configured,
ID 17
1649.01 Mains X X X X
transducer-
configured,
ID 18

A029X159 (Issue 31) 137 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1649.02 Mains X X X X
transducer-
configured,
ID 19
1649.03 Mains X X X X
transducer-
configured,
ID 20
1649.04 Mains X X X X
transducer-
configured,
ID 21
1649.05 Mains X X X X
transducer-
configured,
ID 22
1649.06 Mains X X X X
transducer-
configured,
ID 23
1649.07 Mains X X X X
transducer-
configured,
ID 24
1649.08 Mains X X X X
transducer-
configured,
ID 25
1649.09 Mains X X X X
transducer-
configured,
ID 26
1649.1 Mains X X X X
transducer-
configured,
ID 27
1649.11 Mains X X X X
transducer-
configured,
ID 28
1649.12 Mains X X X X
transducer-
configured,
ID 29

Copyright © 2023 Cummins Inc. 138 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1649.13 Mains X X X X
transducer-
configured,
ID 30
1649.14 Mains X X X X
transducer-
configured,
ID 31
1649.15 Mains X X X X
transducer-
configured,
ID 32
1650 TB X X X X
transducer-
configured,
ID 17
1650.01 TB X X X X
transducer-
configured,
ID 18
1650.02 TB X X X X
transducer-
configured,
ID 19
1650.03 TB X X X X
transducer-
configured,
ID 20
1650.04 TB X X X X
transducer-
configured,
ID 21
1650.05 TB X X X X
transducer-
configured,
ID 22
1650.06 TB X X X X
transducer-
configured,
ID 23
1650.07 TB X X X X
transducer-
configured,
ID 24

A029X159 (Issue 31) 139 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1650.08 TB X X X X
transducer-
configured,
ID 25
1650.09 TB X X X X
transducer-
configured,
ID 26
1650.1 TB X X X X
transducer-
configured,
ID 27
1650.11 TB X X X X
transducer-
configured,
ID 28
1650.12 TB X X X X
transducer-
configured,
ID 29
1650.13 TB X X X X
transducer-
configured,
ID 30
1650.14 TB X X X X
transducer-
configured,
ID 31
1650.15 TB X X X X
transducer-
configured,
ID 32

5.1.12 Function Code 4 (04h): Read Input Registers (Address, Bit:


1651-1714)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1651 Not used:
1651-1652
1653 Nominal X X X X
power ID 17
1654 Nominal X X X X
power ID 18

Copyright © 2023 Cummins Inc. 140 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1655 Nominal X X X X
power ID 19
1656 Nominal X X X X
power ID 20
1657 Nominal X X X X
power ID 21
1658 Nominal X X X X
power ID 22
1659 Nominal X X X X
power ID 23
1660 Nominal X X X X
power ID 24
1661 Nominal X X X X
power ID 25
1662 Nominal X X X X
power ID 26
1663 Nominal X X X X
power ID 27
1664 Nominal X X X X
power ID 28
1665 Nominal X X X X
power ID 29
1666 Nominal X X X X
power ID 30
1667 Nominal X X X X
power ID 31
1668 Nominal X X X X
power ID 32
1669 Not used
1700 TB available X X
1700.01 Mains unit X
available
1700.02 Any MB pos. X X X X
ON
1700.03 All MB pos. X X X X
OFF
1700.04 TB pos. ON X X X X
(Mains
Command
Unit)

A029X159 (Issue 31) 141 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1700.05 TB pos. OFF X X X X
(Mains
Command
Unit)
1700.06 Any GB pos. X X X
ON
1700.07 All GB pos. X X X
OFF
1700.08 Any TB pos. X X X X
ON
1700.09 All TB pos. X X X X
OFF
1700.1 Any BTB X X X X
pos. ON
1700.11 Any BTB X X X X
pos. OFF
1700.12 Not used
1700.13 Not used
1700.14 Not used
1700.15 Not used
1701 GB pos. ON X X X
ID 1
1701.01 GB pos. ON X X X
ID 2
1701.02 GB pos. ON X X X
ID 3
1701.03 GB pos. ON X X X
ID 4
1701.04 GB pos. ON X X X
ID 5
1701.05 GB pos. ON X X X
ID 6
1701.06 GB pos. ON X X X
ID 7
1701.07 GB pos. ON X X X
ID 8
1701.08 GB pos. ON X X X
ID 9
1701.09 GB pos. ON X X X
ID 10

Copyright © 2023 Cummins Inc. 142 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1701.1 GB pos. ON X X X
ID 11
1701.11 GB pos. ON X X X
ID 12
1701.12 GB pos. ON X X X
ID 13
1701.13 GB pos. ON X X X
ID 14
1701.14 GB pos. ON X X X
ID 15
1701.15 GB pos. ON X X X
ID 16
1702 GB pos. OFF X X X
ID 1
1702.01 GB pos. OFF X X X
ID 2
1702.02 GB pos. OFF X X X
ID 3
1702.03 GB pos. OFF X X X
ID 4
1702.04 GB pos. OFF X X X
ID 5
1702.05 GB pos. OFF X X X
ID 6
1702.06 GB pos. OFF X X X
ID 7
1702.07 GB pos. OFF X X X
ID 8
1702.08 GB pos. OFF X X X
ID 9
1702.09 GB pos. OFF X X X
ID 10
1702.1 GB pos. OFF X X X
ID 11
1702.11 GB pos. OFF X X X
ID 12
1702.12 GB pos. OFF X X X
ID 13
1702.13 GB pos. OFF X X X
ID 14

A029X159 (Issue 31) 143 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1702.14 GB pos. OFF X X X
ID 15
1702.15 GB pos. OFF X X X
ID 16
1703 DG Hz/V OK, X X X
ID 1
1703.01 DG Hz/V OK, X X X
ID 2
1703.02 DG Hz/V OK, X X X
ID 3
1703.03 DG Hz/V OK, X X X
ID 4
1703.04 DG Hz/V OK, X X X
ID 5
1703.05 DG Hz/V OK, X X X
ID 6
1703.06 DG Hz/V OK, X X X
ID 7
1703.07 DG Hz/V OK, X X X
ID 8
1703.08 DG Hz/V OK, X X X
ID 9
1703.09 DG Hz/V OK, X X X
ID 10
1703.1 DG Hz/V OK, X X X
ID 11
1703.11 DG Hz/V OK, X X X
ID 12
1703.12 DG Hz/V OK, X X X
ID 13
1703.13 DG Hz/V OK, X X X
ID 14
1703.14 DG Hz/V OK, X X X
ID 15
1703.15 DG Hz/V OK, X X X
ID 16
1704 Not used
1705 Ready for X X X
auto start, ID
1

Copyright © 2023 Cummins Inc. 144 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1705.01 Ready for X X X
auto start, ID
2
1705.02 Ready for X X X
auto start, ID
3
1705.03 Ready for X X X
auto start, ID
4
1705.04 Ready for X X X
auto start, ID
5
1705.05 Ready for X X X
auto start, ID
6
1705.06 Ready for X X X
auto start, ID
7
1705.07 Ready for X X X
auto start, ID
8
1705.08 Ready for X X X
auto start, ID
9
1705.09 Ready for X X X
auto start, ID
10
1705.1 Ready for X X X
auto start, ID
11
1705.11 Ready for X X X
auto start, ID
12
1705.12 Ready for X X X
auto start, ID
13
1705.13 Ready for X X X
auto start, ID
14
1705.14 Ready for X X X
auto start, ID
15
1705.15 Ready for X X X
auto start, ID
16

A029X159 (Issue 31) 145 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1706 Not used
1707 Any alarms, X X X X
ID 1
1707.01 Any alarms, X X X X
ID 2
1707.02 Any alarms, X X X X
ID 3
1707.03 Any alarms, X X X X
ID 4
1707.04 Any alarms, X X X X
ID 5
1707.05 Any alarms, X X X X
ID 6
1707.06 Any alarms, X X X X
ID 7
1707.07 Any alarms, X X X X
ID 8
1707.08 Any alarms, X X X X
ID 9
1707.09 Any alarms, X X X X
ID 10
1707.1 Any alarms, X X X X
ID 11
1707.11 Any alarms, X X X X
ID 12
1707.12 Any alarms, X X X X
ID 13
1707.13 Any alarms, X X X X
ID 14
1707.14 Any alarms, X X X X
ID 15
1707.15 Any alarms, X X X X
ID 16
1708 Not used
1709 Engine X X X
running, ID 1
1709.01 Engine X X X
running, ID 2
1709.02 Engine X X X
running, ID 3

Copyright © 2023 Cummins Inc. 146 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1709.03 Engine X X X
running, ID 4
1709.04 Engine X X X
running, ID 5
1709.05 Engine X X X
running, ID 6
1709.06 Engine X X X
running, ID 7
1709.07 Engine X X X
running, ID 8
1709.08 Engine X X X
running, ID 9
1709.09 Engine X X X
running, ID
10
1709.1 Engine X X X
running, ID
11
1709.11 Engine X X X
running, ID
12
1709.12 Engine X X X
running, ID
13
1709.13 Engine X X X
running, ID
14
1709.14 Engine X X X
running, ID
15
1709.15 Engine X X X
running, ID
16
1710 Not used
1711 GB X X X
synchronizin
g, ID 1
1711.01 GB X X X
synchronizin
g, ID 2
1711.02 GB X X X
synchronizin
g, ID 3

A029X159 (Issue 31) 147 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1711.03 GB X X X
synchronizin
g, ID 4
1711.04 GB X X X
synchronizin
g, ID 5
1711.05 GB X X X
synchronizin
g, ID 6
1711.06 GB X X X
synchronizin
g, ID 7
1711.07 GB X X X
synchronizin
g, ID 8
1711.08 GB X X X
synchronizin
g, ID 9
1711.09 GB X X X
synchronizin
g, ID 10
1711.1 GB X X X
synchronizin
g, ID 11
1711.11 GB X X X
synchronizin
g, ID 12
1711.12 GB X X X
synchronizin
g, ID 13
1711.13 GB X X X
synchronizin
g, ID 14
1711.14 GB X X X
synchronizin
g, ID 15
1711.15 GB X X X
synchronizin
g, ID 16
1712 Mains OK, ID X X X X
17
1712.01 Mains OK, ID X X X X
18

Copyright © 2023 Cummins Inc. 148 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1712.02 Mains OK, ID X X X X
19
1712.03 Mains OK, ID X X X X
20
1712.04 Mains OK, ID X X X X
21
1712.05 Mains OK, ID X X X X
22
1712.06 Mains OK, ID X X X X
23
1712.07 Mains OK, ID X X X X
24
1712.08 Mains OK, ID X X X X
25
1712.09 Mains OK, ID X X X X
26
1712.1 Mains OK, ID X X X X
27
1712.11 Mains OK, ID X X X X
28
1712.12 Mains OK, ID X X X X
29
1712.13 Mains OK, ID X X X X
30
1712.14 Mains OK, ID X X X X
31
1712.15 Mains OK, ID X X X X
32
1713 Mains not in X X X X
semi 17
1713.01 Mains not in X X X X
semi 18
1713.02 Mains not in X X X X
semi 19
1713.03 Mains not in X X X X
semi 20
1713.04 Mains not in X X X X
semi 21
1713.05 Mains not in X X X X
semi 22

A029X159 (Issue 31) 149 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1713.06 Mains not in X X X X
semi 23
1713.07 Mains not in X X X X
semi 24
1713.08 Mains not in X X X X
semi 25
1713.09 Mains not in X X X X
semi 26
1713.1 Mains not in X X X X
semi 27
1713.11 Mains not in X X X X
semi 28
1713.12 Mains not in X X X X
semi 29
1713.13 Mains not in X X X X
semi 30
1713.14 Mains not in X X X X
semi 31
1713.15 Mains not in X X X X
semi 32
1714 Any alarms, X X X X
ID 17
1714.01 Any alarms, X X X X
ID 18
1714.02 Any alarms, X X X X
ID 19
1714.03 Any alarms, X X X X
ID 20
1714.04 Any alarms, X X X X
ID 21
1714.05 Any alarms, X X X X
ID 22
1714.06 Any alarms, X X X X
ID 23
1714.07 Any alarms, X X X X
ID 24
1714.08 Any alarms, X X X X
ID 25
1714.09 Any alarms, X X X X
ID 26

Copyright © 2023 Cummins Inc. 150 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1714.1 Any alarms, X X X X
ID 27
1714.11 Any alarms, X X X X
ID 28
1714.12 Any alarms, X X X X
ID 29
1714.13 Any alarms, X X X X
ID 30
1714.14 Any alarms, X X X X
ID 31
1714.15 Any alarms, X X X X
ID 32

5.1.13 Function Code 4 (04h): Read Input Registers (Address, Bit:


1715-1728)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1715 MB pos. ON, X X X X
ID 17
1715.01 MB pos. ON, X X X X
ID 18
1715.02 MB pos. ON, X X X X
ID 19
1715.03 MB pos. ON, X X X X
ID 20
1715.04 MB pos. ON, X X X X
ID 21
1715.05 MB pos. ON, X X X X
ID 22
1715.06 MB pos. ON, X X X X
ID 23
1715.07 MB pos. ON, X X X X
ID 24
1715.08 MB pos. ON, X X X X
ID 25
1715.09 MB pos. ON, X X X X
ID 26
1715.1 MB pos. ON, X X X X
ID 27

A029X159 (Issue 31) 151 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1715.11 MB pos. ON, X X X X
ID 28
1715.12 MB pos. ON, X X X X
ID 29
1715.13 MB pos. ON, X X X X
ID 30
1715.14 MB pos. ON, X X X X
ID 31
1715.15 MB pos. ON, X X X X
ID 32
1716 MB pos. X X X X
OFF, ID 17
1716.01 MB pos. X X X X
OFF, ID 18
1716.02 MB pos. X X X X
OFF, ID 19
1716.03 MB pos. X X X X
OFF, ID 20
1716.04 MB pos. X X X X
OFF, ID 21
1716.05 MB pos. X X X X
OFF, ID 22
1716.06 MB pos. X X X X
OFF, ID 23
1716.07 MB pos. X X X X
OFF, ID 24
1716.08 MB pos. X X X X
OFF, ID 25
1716.09 MB pos. X X X X
OFF, ID 26
1716.1 MB pos. X X X X
OFF, ID 27
1716.11 MB pos. X X X X
OFF, ID 28
1716.12 MB pos. X X X X
OFF, ID 29
1716.13 MB pos. X X X X
OFF, ID 30
1716.14 MB pos. X X X X
OFF, ID 31

Copyright © 2023 Cummins Inc. 152 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1716.15 MB pos. X X X X
OFF, ID 32
1717 Mains failure, X X X X
ID 17
1717.01 Mains failure, X X X X
ID 18
1717.02 Mains failure, X X X X
ID 19
1717.03 Mains failure, X X X X
ID 20
1717.04 Mains failure, X X X X
ID 21
1717.05 Mains failure, X X X X
ID 22
1717.06 Mains failure, X X X X
ID 23
1717.07 Mains failure, X X X X
ID 24
1717.08 Mains failure, X X X X
ID 25
1717.09 Mains failure, X X X X
ID 26
1717.1 Mains failure, X X X X
ID 27
1717.11 Mains failure, X X X X
ID 28
1717.12 Mains failure, X X X X
ID 29
1717.13 Mains failure, X X X X
ID 30
1717.14 Mains failure, X X X X
ID 31
1717.15 Mains failure, X X X X
ID 32
1718 MB X X X X
synchronizin
g, ID 17
1718.01 MB X X X X
synchronizin
g, ID 18

A029X159 (Issue 31) 153 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1718.02 MB X X X X
synchronizin
g, ID 19
1718.03 MB X X X X
synchronizin
g, ID 20
1718.04 MB X X X X
synchronizin
g, ID 21
1718.05 MB X X X X
synchronizin
g, ID 22
1718.06 MB X X X X
synchronizin
g, ID 23
1718.07 MB X X X X
synchronizin
g, ID 24
1718.08 MB X X X X
synchronizin
g, ID 25
1718.09 MB X X X X
synchronizin
g, ID 26
1718.1 MB X X X X
synchronizin
g, ID 27
1718.11 MB X X X X
synchronizin
g, ID 28
1718.12 MB X X X X
synchronizin
g, ID 29
1718.13 MB X X X X
synchronizin
g, ID 30
1718.14 MB X X X X
synchronizin
g, ID 31
1718.15 MB X X X X
synchronizin
g, ID 32
1719 TB pos. ON, X X X X
ID 17

Copyright © 2023 Cummins Inc. 154 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1719.01 TB pos. ON, X X X X
ID 18
1719.02 TB pos. ON, X X X X
ID 19
1719.03 TB pos. ON, X X X X
ID 20
1719.04 TB pos. ON, X X X X
ID 21
1719.05 TB pos. ON, X X X X
ID 22
1719.06 TB pos. ON, X X X X
ID 23
1719.07 TB pos. ON, X X X X
ID 24
1719.08 TB pos. ON, X X X X
ID 25
1719.09 TB pos. ON, X X X X
ID 26
1719.1 TB pos. ON, X X X X
ID 27
1719.11 TB pos. ON, X X X X
ID 28
1719.12 TB pos. ON, X X X X
ID 29
1719.13 TB pos. ON, X X X X
ID 30
1719.14 TB pos. ON, X X X X
ID 31
1719.15 TB pos. ON, X X X X
ID 32
1720 TB pos. X X X X
OFF, ID 17
1720.01 TB pos. X X X X
OFF, ID 18
1720.02 TB pos. X X X X
OFF, ID 19
1720.03 TB pos. X X X X
OFF, ID 20
1720.04 TB pos. X X X X
OFF, ID 21

A029X159 (Issue 31) 155 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1720.05 TB pos. X X X X
OFF, ID 22
1720.06 TB pos. X X X X
OFF, ID 23
1720.07 TB pos. X X X X
OFF, ID 24
1720.08 TB pos. X X X X
OFF, ID 25
1720.09 TB pos. X X X X
OFF, ID 26
1720.1 TB pos. X X X X
OFF, ID 27
1720.11 TB pos. X X X X
OFF, ID 28
1720.12 TB pos. X X X X
OFF, ID 29
1720.13 TB pos. X X X X
OFF, ID 30
1720.14 TB pos. X X X X
OFF, ID 31
1720.15 TB pos. X X X X
OFF, ID 32
1721 TB X X X X
synchronizin
g, ID 17
1721.01 TB X X X X
synchronizin
g, ID 18
1721.02 TB X X X X
synchronizin
g, ID 19
1721.03 TB X X X X
synchronizin
g, ID 20
1721.04 TB X X X X
synchronizin
g, ID 21
1721.05 TB X X X X
synchronizin
g, ID 22
1721.06 TB X X X X
synchronizin
g, ID 23

Copyright © 2023 Cummins Inc. 156 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1721.07 TB X X X X
synchronizin
g, ID 24
1721.08 TB X X X X
synchronizin
g, ID 25
1721.09 TB X X X X
synchronizin
g, ID 26
1721.1 TB X X X X
synchronizin
g, ID 27
1721.11 TB X X X X
synchronizin
g, ID 28
1721.12 TB X X X X
synchronizin
g, ID 29
1721.13 TB X X X X
synchronizin
g, ID 30
1721.14 TB X X X X
synchronizin
g, ID 31
1721.15 TB X X X X
synchronizin
g, ID 32
1722 Any alarms, X X
PV ID 33
1722.01 Any alarms, X X
PV ID 34
1722.02 Any alarms, X X
PV ID 35
1722.03 Any alarms, X X
PV ID 36
1722.04 Any alarms, X X
PV ID 37
1722.05 Any alarms, X X
PV ID 38
1722.06 Any alarms, X X
PV ID 39
1722.07 Any alarms, X X
PV ID 40

A029X159 (Issue 31) 157 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1722.08 Not used
1722.09 Not used
1722.1 Not used
1722.11 Not used
1722.12 Not used
1722.13 Not used
1722.14 Not used
1722.15 Not used
1723 BTB pos. X X X X
ON, ID 33
1723.01 BTB pos. X X X X
ON, ID 34
1723.02 BTB pos. X X X X
ON, ID 35
1723.03 BTB pos. X X X X
ON, ID 36
1723.04 BTB pos. X X X X
ON, ID 37
1723.05 BTB pos. X X X X
ON, ID 38
1723.06 BTB pos. X X X X
ON, ID 39
1723.07 BTB pos. X X X X
ON, ID 40
1723.08 Not used
1723.09 Not used
1723.1 Not used
1723.11 Not used
1723.12 Not used
1723.13 Not used
1723.14 Not used
1723.15 Not used
1724 BTB pos. X X X X
OFF, ID 33
1724.01 BTB pos. X X X X
OFF, ID 34
1724.02 BTB pos. X X X X
OFF, ID 35

Copyright © 2023 Cummins Inc. 158 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1724.03 BTB pos. X X X X
OFF, ID 36
1724.04 BTB pos. X X X X
OFF, ID 37
1724.05 BTB pos. X X X X
OFF, ID 38
1724.06 BTB pos. X X X X
OFF, ID 39
1724.07 BTB pos. X X X X
OFF, ID 40
1724.08 Not used
1724.09 Not used
1724.1 Not used
1724.11 Not used
1724.12 Not used
1724.13 Not used
1724.14 Not used
1724.15 Not used
1725 Not used
1726 Ext. Modbus X X X X
comm. error,
CAN ID 1
1726.01 Ext. Modbus X X X X
comm. error,
CAN ID 2
1726.02 Ext. Modbus X X X X
comm. error,
CAN ID 3
1726.03 Ext. Modbus X X X X
comm. error,
CAN ID 4
1726.04 Ext. Modbus X X X X
comm. error,
CAN ID 5
1726.05 Ext. Modbus X X X X
comm. error,
CAN ID 6
1726.06 Ext. Modbus X X X X
comm. error,
CAN ID 7

A029X159 (Issue 31) 159 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1726.07 Ext. Modbus X X X X
comm. error,
CAN ID 8
1726.08 Ext. Modbus X X X X
comm. error,
CAN ID 9
1726.09 Ext. Modbus X X X X
comm. error,
CAN ID 10
1726.1 Ext. Modbus X X X X
comm. error,
CAN ID 11
1726.11 Ext. Modbus X X X X
comm. error,
CAN ID 12
1726.12 Ext. Modbus X X X X
comm. error,
CAN ID 13
1726.13 Ext. Modbus X X X X
comm. error,
CAN ID 14
1726.14 Ext. Modbus X X X X
comm. error,
CAN ID 15
1726.15 Ext. Modbus X X X X
comm. error,
CAN ID 16
1727 Ext. Modbus X X X X
comm. error,
CAN ID 17
1727.01 Ext. Modbus X X X X
comm. error,
CAN ID 18
1727.02 Ext. Modbus X X X X
comm. error,
CAN ID 19
1727.03 Ext. Modbus X X X X
comm. error,
CAN ID 20
1727.04 Ext. Modbus X X X X
comm. error,
CAN ID 21
1727.05 Ext. Modbus X X X X
comm. error,
CAN ID 22

Copyright © 2023 Cummins Inc. 160 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1727.06 Ext. Modbus X X X X
comm. error,
CAN ID 23
1727.07 Ext. Modbus X X X X
comm. error,
CAN ID 24
1727.08 Ext. Modbus X X X X
comm. error,
CAN ID 25
1727.09 Ext. Modbus X X X X
comm. error,
CAN ID 26
1727.1 Ext. Modbus X X X X
comm. error,
CAN ID 27
1727.11 Ext. Modbus X X X X
comm. error,
CAN ID 28
1727.12 Ext. Modbus X X X X
comm. error,
CAN ID 29
1727.13 Ext. Modbus X X X X
comm. error,
CAN ID 30
1727.14 Ext. Modbus X X X X
comm. error,
CAN ID 31
1727.15 Ext. Modbus X X X X
comm. error,
CAN ID 32
1728 Not used:
1728-1731

5.1.14 Function Code 4 (04h): Read Input Registers (Address, Bit:


1732-1750)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1732 BB Hz/V OK, X X X X
ID 1
1732.01 BB Hz/V OK, X X X X
ID 2

A029X159 (Issue 31) 161 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1732.02 BB Hz/V OK, X X X X
ID 3
1732.03 BB Hz/V OK, X X X X
ID 4
1732.04 BB Hz/V OK, X X X X
ID 5
1732.05 BB Hz/V OK, X X X X
ID 6
1732.06 BB Hz/V OK, X X X X
ID 7
1732.07 BB Hz/V OK, X X X X
ID 8
1732.08 BB Hz/V OK, X X X X
ID 9
1732.09 BB Hz/V OK, X X X X
ID 10
1732.1 BB Hz/V OK, X X X X
ID 11
1732.11 BB Hz/V OK, X X X X
ID 12
1732.12 BB Hz/V OK, X X X X
ID 13
1732.13 BB Hz/V OK, X X X X
ID 14
1732.14 BB Hz/V OK, X X X X
ID 15
1732.15 BB Hz/V OK, X X X X
ID 16
1733 BB Hz/V OK, X X X X
ID 17
1733.01 BB Hz/V OK, X X X X
ID 18
1733.02 BB Hz/V OK, X X X X
ID 19
1733.03 BB Hz/V OK, X X X X
ID 20
1733.04 BB Hz/V OK, X X X X
ID 21
1733.05 BB Hz/V OK, X X X X
ID 22

Copyright © 2023 Cummins Inc. 162 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1733.06 BB Hz/V OK, X X X X
ID 23
1733.07 BB Hz/V OK, X X X X
ID 24
1733.08 BB Hz/V OK, X X X X
ID 25
1733.09 BB Hz/V OK, X X X X
ID 26
1733.1 BB Hz/V OK, X X X X
ID 27
1733.11 BB Hz/V OK, X X X X
ID 28
1733.12 BB Hz/V OK, X X X X
ID 29
1733.13 BB Hz/V OK, X X X X
ID 30
1733.14 BB Hz/V OK, X X X X
ID 31
1733.15 BB Hz/V OK, X X X X
ID 32
1734 BB Hz/V OK, X X
PV ID 33
1734.01 BB Hz/V OK, X X
PV ID 34
1734.02 BB Hz/V OK, X X
PV ID 35
1734.03 BB Hz/V OK, X X
PV ID 36
1734.04 BB Hz/V OK, X X
PV ID 37
1734.05 BB Hz/V OK, X X
PV ID 38
1734.06 BB Hz/V OK, X X
PV ID 39
1734.07 BB Hz/V OK, X X
PV ID 40
1734.08 Not used
1734.09 Not used
1734.1 Not used
1734.11 Not used

A029X159 (Issue 31) 163 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1734.12 Not used
1734.13 Not used
1734.14 Not used
1734.15 Not used
1735 BB Hz/V X X X X
present, ID 1
1735.01 BB Hz/V X X X X
present, ID 2
1735.02 BB Hz/V X X X X
present, ID 3
1735.03 BB Hz/V X X X X
present, ID 4
1735.04 BB Hz/V X X X X
present, ID 5
1735.05 BB Hz/V X X X X
present, ID 6
1735.06 BB Hz/V X X X X
present, ID 7
1735.07 BB Hz/V X X X X
present, ID 8
1735.08 BB Hz/V X X X X
present, ID 9
1735.09 BB Hz/V X X X X
present, ID
10
1735.1 BB Hz/V X X X X
present, ID
11
1735.11 BB Hz/V X X X X
present, ID
12
1735.12 BB Hz/V X X X X
present, ID
13
1735.13 BB Hz/V X X X X
present, ID
14
1735.14 BB Hz/V X X X X
present, ID
15

Copyright © 2023 Cummins Inc. 164 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1735.15 BB Hz/V X X X X
present, ID
16
1736 BB Hz/V X X X X
present, ID
17
1736.01 BB Hz/V X X X X
present, ID
18
1736.02 BB Hz/V X X X X
present, ID
19
1736.03 BB Hz/V X X X X
present, ID
20
1736.04 BB Hz/V X X X X
present, ID
21
1736.05 BB Hz/V X X X X
present, ID
22
1736.06 BB Hz/V X X X X
present, ID
23
1736.07 BB Hz/V X X X X
present, ID
24
1736.08 BB Hz/V X X X X
present, ID
25
1736.09 BB Hz/V X X X X
present, ID
26
1736.1 BB Hz/V X X X X
present, ID
27
1736.11 BB Hz/V X X X X
present, ID
28
1736.12 BB Hz/V X X X X
present, ID
29
1736.13 BB Hz/V X X X X
present, ID
30

A029X159 (Issue 31) 165 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1736.14 BB Hz/V X X X X
present, ID
31
1736.15 BB Hz/V X X X X
present, ID
32
1737 BB Hz/V X X X X
present, PV
ID 33
1737.01 BB Hz/V X X X X
present, PV
ID 34
1737.02 BB Hz/V X X X X
present, PV
ID 35
1737.03 BB Hz/V X X X X
present, PV
ID 36
1737.04 BB Hz/V X X X X
present, PV
ID 37
1737.05 BB Hz/V X X X X
present, PV
ID 38
1737.06 BB Hz/V X X X X
present, PV
ID 39
1737.07 BB Hz/V X X X X
present, PV
ID 40
1737.08 Not used
1737.09 Not used
1737.1 Not used
1737.11 Not used
1737.12 Not used
1737.13 Not used
1737.14 Not used
1737.15 Not used
1738 BA Hz/V OK, X X X X
PV ID 33
1738.01 BA Hz/V OK, X X X X
PV ID 34

Copyright © 2023 Cummins Inc. 166 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1738.02 BA Hz/V OK, X X X X
PV ID 35
1738.03 BA Hz/V OK, X X X X
PV ID 36
1738.04 BA Hz/V OK, X X X X
PV ID 37
1738.05 BA Hz/V OK, X X X X
PV ID 38
1738.06 BA Hz/V OK, X X X X
PV ID 39
1738.07 BA Hz/V OK, X X X X
PV ID 40
1738.08 Not used
1738.09 Not used
1738.1 Not used
1738.11 Not used
1738.12 Not used
1738.13 Not used
1738.14 Not used
1738.15 Not used
1739 DG Hz/V X X X
present, ID 1
1739.01 DG Hz/V X X X
present, ID 2
1739.02 DG Hz/V X X X
present, ID 3
1739.03 DG Hz/V X X X
present, ID 4
1739.04 DG Hz/V X X X
present, ID 5
1739.05 DG Hz/V X X X
present, ID 6
1739.06 DG Hz/V X X X
present, ID 7
1739.07 DG Hz/V X X X
present, ID 8
1739.08 DG Hz/V X X X
present, ID 9

A029X159 (Issue 31) 167 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1739.09 DG Hz/V X X X
present, ID
10
1739.1 DG Hz/V X X X
present, ID
11
1739.11 DG Hz/V X X X
present, ID
12
1739.12 DG Hz/V X X X
present, ID
13
1739.13 DG Hz/V X X X
present, ID
14
1739.14 DG Hz/V X X X
present, ID
15
1739.15 DG Hz/V X X X
present, ID
16
1740 Mains Hz/V X X X X
present, ID
17
1740.01 Mains Hz/V X X X X
present, ID
18
1740.02 Mains Hz/V X X X X
present, ID
19
1740.03 Mains Hz/V X X X X
present, ID
20
1740.04 Mains Hz/V X X X X
present, ID
21
1740.05 Mains Hz/V X X X X
present, ID
22
1740.06 Mains Hz/V X X X X
present, ID
23
1740.07 Mains Hz/V X X X X
present, ID
24

Copyright © 2023 Cummins Inc. 168 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1740.08 Mains Hz/V X X X X
present, ID
25
1740.09 Mains Hz/V X X X X
present, ID
26
1740.1 Mains Hz/V X X X X
present, ID
27
1740.11 Mains Hz/V X X X X
present, ID
28
1740.12 Mains Hz/V X X X X
present, ID
29
1740.13 Mains Hz/V X X X X
present, ID
30
1740.14 Mains Hz/V X X X X
present, ID
31
1740.15 Mains Hz/V X X X X
present, ID
32
1741 BA Hz/V X X
present, PV
ID 33
1741.01 BA Hz/V X X
present, PV
ID 34
1741.02 BA Hz/V X X
present, PV
ID 35
1741.03 BA Hz/V X X
present, PV
ID 36
1741.04 BA Hz/V X X
present, PV
ID 37
1741.05 BA Hz/V X X
present, PV
ID 38
1741.06 BA Hz/V X X
present, PV
ID 39

A029X159 (Issue 31) 169 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1741.07 BA Hz/V X X
present, PV
ID 40
1741.08 Not used
1741.09 Not used
1741.1 Not used
1741.11 Not used
1741.12 Not used
1741.13 Not used
1741.14 Not used
1741.15 Not used
1742 Not used:
1742-1748
1749 Dry Mode X X X
active on ID1
1749.01 Dry Mode X X X
active on ID2
1749.02 Dry Mode X X X
active on ID3
1749.03 Dry Mode X X X
active on ID4
1749.04 Dry Mode X X X
active on ID5
1749.05 Dry Mode X X X
active on ID6
1749.06 Dry Mode X X X
active on ID7
1749.07 Dry Mode X X X
active on ID8
1749.08 Dry Mode X X X
active on ID9
1749.09 Dry Mode X X X
active on
ID10
1749.1 Dry Mode X X X
active on
ID11
1749.11 Dry Mode X X X
active on
ID12

Copyright © 2023 Cummins Inc. 170 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1749.12 Dry Mode X X X
active on
ID13
1749.13 Dry Mode X X X
active on
ID14
1749.14 Dry Mode X X X
active on
ID15
1749.15 Dry Mode X X X
active on
ID16
1750 GB pos. ON X X X
ID 17
1750.01 GB pos. ON X X X
ID 18
1750.02 GB pos. ON X X X
ID 19
1750.03 GB pos. ON X X X
ID 20
1750.04 GB pos. ON X X X
ID 21
1750.05 GB pos. ON X X X
ID 22
1750.06 GB pos. ON X X X
ID 23
1750.07 GB pos. ON X X X
ID 24
1750.08 GB pos. ON X X X
ID 25
1750.09 GB pos. ON X X X
ID 26
1750.1 GB pos. ON X X X
ID 27
1750.11 GB pos. ON X X X
ID 28
1750.12 GB pos. ON X X X
ID 29
1750.13 GB pos. ON X X X
ID 30
1750.14 GB pos. ON X X X
ID 31

A029X159 (Issue 31) 171 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1750.15 GB pos. ON X X X
ID 32

5.1.15 Function Code 4 (04h): Read Input Registers (Address, Bit:


1751-1762)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1751 GB pos. OFF X X X
ID 17
1751.01 GB pos. OFF X X X
ID 18
1751.02 GB pos. OFF X X X
ID 19
1751.03 GB pos. OFF X X X
ID 20
1751.04 GB pos. OFF X X X
ID 21
1751.05 GB pos. OFF X X X
ID 22
1751.06 GB pos. OFF X X X
ID 23
1751.07 GB pos. OFF X X X
ID 24
1751.08 GB pos. OFF X X X
ID 25
1751.09 GB pos. OFF X X X
ID 26
1751.1 GB pos. OFF X X X
ID 27
1751.11 GB pos. OFF X X X
ID 28
1751.12 GB pos. OFF X X X
ID 29
1751.13 GB pos. OFF X X X
ID 30
1751.14 GB pos. OFF X X X
ID 31
1751.15 GB pos. OFF X X X
ID 32

Copyright © 2023 Cummins Inc. 172 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1752 GB X X X
synchronizin
g, ID 17
1752.01 GB X X X
synchronizin
g, ID 18
1752.02 GB X X X
synchronizin
g, ID 19
1752.03 GB X X X
synchronizin
g, ID 20
1752.04 GB X X X
synchronizin
g, ID 21
1752.05 GB X X X
synchronizin
g, ID 22
1752.06 GB X X X
synchronizin
g, ID 23
1752.07 GB X X X
synchronizin
g, ID 24
1752.08 GB X X X
synchronizin
g, ID 25
1752.09 GB X X X
synchronizin
g, ID 26
1752.1 GB X X X
synchronizin
g, ID 27
1752.11 GB X X X
synchronizin
g, ID 28
1752.12 GB X X X
synchronizin
g, ID 29
1752.13 GB X X X
synchronizin
g, ID 30
1752.14 GB X X X
synchronizin
g, ID 31

A029X159 (Issue 31) 173 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1752.15 GB X X X
synchronizin
g, ID 32
1753 DG Hz/V OK, X X X
ID 17
1753.01 DG Hz/V OK, X X X
ID 18
1753.02 DG Hz/V OK, X X X
ID 19
1753.03 DG Hz/V OK, X X X
ID 20
1753.04 DG Hz/V OK, X X X
ID 21
1753.05 DG Hz/V OK, X X X
ID 22
1753.06 DG Hz/V OK, X X X
ID 23
1753.07 DG Hz/V OK, X X X
ID 24
1753.08 DG Hz/V OK, X X X
ID 25
1753.09 DG Hz/V OK, X X X
ID 26
1753.1 DG Hz/V OK, X X X
ID 27
1753.11 DG Hz/V OK, X X X
ID 28
1753.12 DG Hz/V OK, X X X
ID 29
1753.13 DG Hz/V OK, X X X
ID 30
1753.14 DG Hz/V OK, X X X
ID 31
1753.15 DG Hz/V OK, X X X
ID 32
1754 Ready for X X X
auto start, ID
17
1754.01 Ready for X X X
auto start, ID
18

Copyright © 2023 Cummins Inc. 174 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1754.02 Ready for X X X
auto start, ID
19
1754.03 Ready for X X X
auto start, ID
20
1754.04 Ready for X X X
auto start, ID
21
1754.05 Ready for X X X
auto start, ID
22
1754.06 Ready for X X X
auto start, ID
23
1754.07 Ready for X X X
auto start, ID
24
1754.08 Ready for X X X
auto start, ID
25
1754.09 Ready for X X X
auto start, ID
26
1754.1 Ready for X X X
auto start, ID
27
1754.11 Ready for X X X
auto start, ID
28
1754.12 Ready for X X X
auto start, ID
29
1754.13 Ready for X X X
auto start, ID
30
1754.14 Ready for X X X
auto start, ID
31
1754.15 Ready for X X X
auto start, ID
32
1755 Engine X X X
running, ID
17

A029X159 (Issue 31) 175 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1755.01 Engine X X X
running, ID
18
1755.02 Engine X X X
running, ID
19
1755.03 Engine X X X
running, ID
20
1755.04 Engine X X X
running, ID
21
1755.05 Engine X X X
running, ID
22
1755.06 Engine X X X
running, ID
23
1755.07 Engine X X X
running, ID
24
1755.08 Engine X X X
running, ID
25
1755.09 Engine X X X
running, ID
26
1755.1 Engine X X X
running, ID
27
1755.11 Engine X X X
running, ID
28
1755.12 Engine X X X
running, ID
29
1755.13 Engine X X X
running, ID
30
1755.14 Engine X X X
running, ID
31
1755.15 Engine X X X
running, ID
32

Copyright © 2023 Cummins Inc. 176 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1756 Dry Mode X X X
active on
ID17
1756.01 Dry Mode X X X
active on
ID18
1756.02 Dry Mode X X X
active on
ID19
1756.03 Dry Mode X X X
active on
ID20
1756.04 Dry Mode X X X
active on
ID21
1756.05 Dry Mode X X X
active on
ID22
1756.06 Dry Mode X X X
active on
ID23
1756.07 Dry Mode X X X
active on
ID24
1756.08 Dry Mode X X X
active on
ID25
1756.09 Dry Mode X X X
active on
ID26
1756.1 Dry Mode X X X
active on
ID27
1756.11 Dry Mode X X X
active on
ID28
1756.12 Dry Mode X X X
active on
ID29
1756.13 Dry Mode X X X
active on
ID30
1756.14 Dry Mode X X X
active on
ID31

A029X159 (Issue 31) 177 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1756.15 Dry Mode X X X
active on
ID32
1757 MB pos. ON, X X X X
ID 1
1757.01 MB pos. ON, X X X X
ID 2
1757.02 MB pos. ON, X X X X
ID 3
1757.03 MB pos. ON, X X X X
ID 4
1757.04 MB pos. ON, X X X X
ID 5
1757.05 MB pos. ON, X X X X
ID 6
1757.06 MB pos. ON, X X X X
ID 7
1757.07 MB pos. ON, X X X X
ID 8
1757.08 MB pos. ON, X X X X
ID 9
1757.09 MB pos. ON, X X X X
ID 10
1757.1 MB pos. ON, X X X X
ID 11
1757.11 MB pos. ON, X X X X
ID 12
1757.12 MB pos. ON, X X X X
ID 13
1757.13 MB pos. ON, X X X X
ID 14
1757.14 MB pos. ON, X X X X
ID 15
1757.15 MB pos. ON, X X X X
ID 16
1758 MB pos. X X X X
OFF, ID 1
1758.01 MB pos. X X X X
OFF, ID 2
1758.02 MB pos. X X X X
OFF, ID 3

Copyright © 2023 Cummins Inc. 178 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1758.03 MB pos. X X X X
OFF, ID 4
1758.04 MB pos. X X X X
OFF, ID 5
1758.05 MB pos. X X X X
OFF, ID 6
1758.06 MB pos. X X X X
OFF, ID 7
1758.07 MB pos. X X X X
OFF, ID 8
1758.08 MB pos. X X X X
OFF, ID 9
1758.09 MB pos. X X X X
OFF, ID 10
1758.1 MB pos. X X X X
OFF, ID 11
1758.11 MB pos. X X X X
OFF, ID 12
1758.12 MB pos. X X X X
OFF, ID 13
1758.13 MB pos. X X X X
OFF, ID 14
1758.14 MB pos. X X X X
OFF, ID 15
1758.15 MB pos. X X X X
OFF, ID 16
1759 MB X X X X
synchronizin
g, ID 1
1759.01 MB X X X X
synchronizin
g, ID 2
1759.02 MB X X X X
synchronizin
g, ID 3
1759.03 MB X X X X
synchronizin
g, ID 4
1759.04 MB X X X X
synchronizin
g, ID 5

A029X159 (Issue 31) 179 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1759.05 MB X X X X
synchronizin
g, ID 6
1759.06 MB X X X X
synchronizin
g, ID 7
1759.07 MB X X X X
synchronizin
g, ID 8
1759.08 MB X X X X
synchronizin
g, ID 9
1759.09 MB X X X X
synchronizin
g, ID 10
1759.1 MB X X X X
synchronizin
g, ID 11
1759.11 MB X X X X
synchronizin
g, ID 12
1759.12 MB X X X X
synchronizin
g, ID 13
1759.13 MB X X X X
synchronizin
g, ID 14
1759.14 MB X X X X
synchronizin
g, ID 15
1759.15 MB X X X X
synchronizin
g, ID 16
1760 TB pos. ON, X X X X
ID 1
1760.01 TB pos. ON, X X X X
ID 2
1760.02 TB pos. ON, X X X X
ID 3
1760.03 TB pos. ON, X X X X
ID 4
1760.04 TB pos. ON, X X X X
ID 5

Copyright © 2023 Cummins Inc. 180 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1760.05 TB pos. ON, X X X X
ID 6
1760.06 TB pos. ON, X X X X
ID 7
1760.07 TB pos. ON, X X X X
ID 8
1760.08 TB pos. ON, X X X X
ID 9
1760.09 TB pos. ON, X X X X
ID 10
1760.1 TB pos. ON, X X X X
ID 11
1760.11 TB pos. ON, X X X X
ID 12
1760.12 TB pos. ON, X X X X
ID 13
1760.13 TB pos. ON, X X X X
ID 14
1760.14 TB pos. ON, X X X X
ID 15
1760.15 TB pos. ON, X X X X
ID 16
1761 TB pos. X X X X
OFF, ID 1
1761.01 TB pos. X X X X
OFF, ID 2
1761.02 TB pos. X X X X
OFF, ID 3
1761.03 TB pos. X X X X
OFF, ID 4
1761.04 TB pos. X X X X
OFF, ID 5
1761.05 TB pos. X X X X
OFF, ID 6
1761.06 TB pos. X X X X
OFF, ID 7
1761.07 TB pos. X X X X
OFF, ID 8
1761.08 TB pos. X X X X
OFF, ID 9

A029X159 (Issue 31) 181 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1761.09 TB pos. X X X X
OFF, ID 10
1761.1 TB pos. X X X X
OFF, ID 11
1761.11 TB pos. X X X X
OFF, ID 12
1761.12 TB pos. X X X X
OFF, ID 13
1761.13 TB pos. X X X X
OFF, ID 14
1761.14 TB pos. X X X X
OFF, ID 15
1761.15 TB pos. X X X X
OFF, ID 16
1762 TB X X X X
synchronizin
g, ID 1
1762.01 TB X X X X
synchronizin
g, ID 2
1762.02 TB X X X X
synchronizin
g, ID 3
1762.03 TB X X X X
synchronizin
g, ID 4
1762.04 TB X X X X
synchronizin
g, ID 5
1762.05 TB X X X X
synchronizin
g, ID 6
1762.06 TB X X X X
synchronizin
g, ID 7
1762.07 TB X X X X
synchronizin
g, ID 8
1762.08 TB X X X X
synchronizin
g, ID 9
1762.09 TB X X X X
synchronizin
g, ID 10

Copyright © 2023 Cummins Inc. 182 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1762.1 TB X X X X
synchronizin
g, ID 11
1762.11 TB X X X X
synchronizin
g, ID 12
1762.12 TB X X X X
synchronizin
g, ID 13
1762.13 TB X X X X
synchronizin
g, ID 14
1762.14 TB X X X X
synchronizin
g, ID 15
1762.15 TB X X X X
synchronizin
g, ID 16

5.1.16 Function Code 4 (04h): Read Input Registers (Address, Bit:


1763-1773)

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1763 Mains X X X X
transducer-
configured,
ID 1
1763.01 Mains X X X X
transducer-
configured,
ID 2
1763.02 Mains X X X X
transducer-
configured,
ID 3
1763.03 Mains X X X X
transducer-
configured,
ID 4
1763.04 Mains X X X X
transducer-
configured,
ID 5

A029X159 (Issue 31) 183 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1763.05 Mains X X X X
transducer-
configured,
ID 6
1763.06 Mains X X X X
transducer-
configured,
ID 7
1763.07 Mains X X X X
transducer-
configured,
ID 8
1763.08 Mains X X X X
transducer-
configured,
ID 9
1763.09 Mains X X X X
transducer-
configured,
ID 10
1763.1 Mains X X X X
transducer-
configured,
ID 11
1763.11 Mains X X X X
transducer-
configured,
ID 12
1763.12 Mains X X X X
transducer-
configured,
ID 13
1763.13 Mains X X X X
transducer-
configured,
ID 14
1763.14 Mains X X X X
transducer-
configured,
ID 15
1763.15 Mains X X X X
transducer-
configured,
ID 16

Copyright © 2023 Cummins Inc. 184 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1764 TB X X X X
transducer-
configured,
ID 1
1764.01 TB X X X X
transducer-
configured,
ID 2
1764.02 TB X X X X
transducer-
configured,
ID 3
1764.03 TB X X X X
transducer-
configured,
ID 4
1764.04 TB X X X X
transducer-
configured,
ID 5
1764.05 TB X X X X
transducer-
configured,
ID 6
1764.06 TB X X X X
transducer-
configured,
ID 7
1764.07 TB X X X X
transducer-
configured,
ID 8
1764.08 TB X X X X
transducer-
configured,
ID 9
1764.09 TB X X X X
transducer-
configured,
ID 10
1764.1 TB X X X X
transducer-
configured,
ID 11

A029X159 (Issue 31) 185 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1764.11 TB X X X X
transducer-
configured,
ID 12
1764.12 TB X X X X
transducer-
configured,
ID 13
1764.13 TB X X X X
transducer-
configured,
ID 14
1764.14 TB X X X X
transducer-
configured,
ID 15
1764.15 TB X X X X
transducer-
configured,
ID 16
1765 Mains OK, ID X X X X
1
1765.01 Mains OK, ID X X X X
2
1765.02 Mains OK, ID X X X X
3
1765.03 Mains OK, ID X X X X
4
1765.04 Mains OK, ID X X X X
5
1765.05 Mains OK, ID X X X X
6
1765.06 Mains OK, ID X X X X
7
1765.07 Mains OK, ID X X X X
8
1765.08 Mains OK, ID X X X X
9
1765.09 Mains OK, ID X X X X
10
1765.1 Mains OK, ID X X X X
11
1765.11 Mains OK, ID X X X X
12

Copyright © 2023 Cummins Inc. 186 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1765.12 Mains OK, ID X X X X
13
1765.13 Mains OK, ID X X X X
14
1765.14 Mains OK, ID X X X X
15
1765.15 Mains OK, ID X X X X
16
1766 Mains not in X X X X
semi 1
1766.01 Mains not in X X X X
semi 2
1766.02 Mains not in X X X X
semi 3
1766.03 Mains not in X X X X
semi 4
1766.04 Mains not in X X X X
semi 5
1766.05 Mains not in X X X X
semi 6
1766.06 Mains not in X X X X
semi 7
1766.07 Mains not in X X X X
semi 8
1766.08 Mains not in X X X X
semi 9
1766.09 Mains not in X X X X
semi 10
1766.1 Mains not in X X X X
semi 11
1766.11 Mains not in X X X X
semi 12
1766.12 Mains not in X X X X
semi 13
1766.13 Mains not in X X X X
semi 14
1766.14 Mains not in X X X X
semi 15
1766.15 Mains not in X X X X
semi 16

A029X159 (Issue 31) 187 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1767 Mains failure, X X X X
ID 1
1767.01 Mains failure, X X X X
ID 2
1767.02 Mains failure, X X X X
ID 3
1767.03 Mains failure, X X X X
ID 4
1767.04 Mains failure, X X X X
ID 5
1767.05 Mains failure, X X X X
ID 6
1767.06 Mains failure, X X X X
ID 7
1767.07 Mains failure, X X X X
ID 8
1767.08 Mains failure, X X X X
ID 9
1767.09 Mains failure, X X X X
ID 10
1767.1 Mains failure, X X X X
ID 11
1767.11 Mains failure, X X X X
ID 12
1767.12 Mains failure, X X X X
ID 13
1767.13 Mains failure, X X X X
ID 14
1767.14 Mains failure, X X X X
ID 15
1767.15 Mains failure, X X X X
ID 16
1768 Breaker ON, X X
PV ID 33
1768.01 Breaker ON, X X
PV ID 34
1768.02 Breaker ON, X X
PV ID 35
1768.03 Breaker ON, X X
PV ID 36

Copyright © 2023 Cummins Inc. 188 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1768.04 Breaker ON, X X
PV ID 37
1768.05 Breaker ON, X X
PV ID 38
1768.06 Breaker ON, X X
PV ID 39
1768.07 Breaker ON, X X
PV ID 40
1768.08 Not used
1768.09 Not used
1768.1 Not used
1768.11 Not used
1768.12 Not used
1768.13 Not used
1768.14 Not used
1768.15 Not used
1769 Breaker X X
OFF, PV ID
33
1769 Breaker X X
synchronizin
g, PV ID 33
1769.01 Breaker X X
OFF, PV ID
34
1769.01 Breaker X X
synchronizin
g, PV ID 34
1769.02 Breaker X X
OFF, PV ID
35
1769.02 Breaker X X
synchronizin
g, PV ID 35
1769.03 Breaker X X
OFF, PV ID
36
1769.03 Breaker X X
synchronizin
g, PV ID 36

A029X159 (Issue 31) 189 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1769.04 Breaker X X
OFF, PV ID
37
1769.04 Breaker X X
synchronizin
g, PV ID 37
1769.05 Breaker X X
OFF, PV ID
38
1769.05 Breaker X X
synchronizin
g, PV ID 38
1769.06 Breaker X X
OFF, PV ID
39
1769.06 Breaker X X
synchronizin
g, PV ID 39
1769.07 Breaker X X
OFF, PV ID
40
1769.07 Breaker X X
synchronizin
g, PV ID 40
1769.08 Not used
1769.09 Not used
1769.1 Not used
1769.11 Not used
1769.12 Not used
1769.13 Not used
1769.14 Not used
1769.15 Not used
1770 Not used
1771 Running, PV X X
ID 33
1771.01 Running, PV X X
ID 34
1771.02 Running, PV X X
ID 35
1771.03 Running, PV X X
ID 36

Copyright © 2023 Cummins Inc. 190 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1771.04 Running, PV X X
ID 37
1771.05 Running, PV X X
ID 38
1771.06 Running, PV X X
ID 39
1771.07 Running, PV X X
ID 40
1771.08 Not used
1771.09 Not used
1771.1 Not used
1771.11 Not used
1771.12 Not used
1771.13 Not used
1771.14 Not used
1771.15 Not used
1772 Not used
1772 Ready to X X
autostart, PV
ID 33
1772.01 Ready to X X
autostart, PV
ID 34
1772.02 Ready to X X
autostart, PV
ID 35
1772.03 Ready to X X
autostart, PV
ID 36
1772.04 Ready to X X
autostart, PV
ID 37
1772.05 Ready to X X
autostart, PV
ID 38
1772.06 Ready to X X
autostart, PV
ID 39
1772.07 Ready to X X
autostart, PV
ID 40

A029X159 (Issue 31) 191 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address, Bit Value/Para Content Scaling AGC-5CDG AGC- AGC- AGC-


meter 5CGroup 5CPlant 5CMains
1772.08 Not used
1772.09 Not used
1772.11 Not used
1772.12 Not used
1772.13 Not used
1772.14 Not used
1772.15 Not used
1773 Engine X
J1939 data,
1773-1999,
see Function
code 4 (EIC)

5.1.17 Function Code 4 (04h): Read Input Registers (EIC)


(Address, Bit: 593-1370)

Address Content SPN Scaling AGC-5C Note


593 Engine speed 190 1/1 X
594 Engine Coolant 110 1/10 X
Temperature
595 Engine Oil 100 1/100 X
Pressure
596 Number of Actual DM1 X
Faults
597 Engine Oil 175 1/10 X
Temperature
598 Fuel Temperature 174 1/10 X
599 Boost Pressure 102 1/100 X
600 Air Inlet 172 1/1 X
Temperature
601 Coolant Level 111 1/10 X
602 Fuel Rate 182 1/10 X
604 Charge Air 105 1/10 X
Temperature
605 Drivers demand 512 1/1 X
percent torque
606 Actual engine - 513 1/1 X
percent torque

Copyright © 2023 Cummins Inc. 192 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content SPN Scaling AGC-5C Note


609 Air Inlet Pressure 106 1/100 X
610 Exhaust gas 173 1/10 X
temperature
611 Engine Hours 247 1/1 X
612 Oil Filter 99 1/100 X
Differential
Pressure
613 Battery potential 158 1/10 X
(voltage),
switched
614 Fuel delivery 94 1/100 X
pressure
615 Engine oil level 98 1/10 X
616 Crankcase 101 1/100 X
pressure
617 Coolant pressure 109 1/100 X
623 Turbo Oil 176 1/10 X
Temperature
624 Particulate Trap 81 1/100 X
Inlet Pressure
625 Air Filter 1 107 1/1000 X
Differential
pressure
626 Coolant filter 112 1/100 X
Differential
pressure
627 Atmospheric 108 1/100 X
Pressure
628 Ambient air 171 1/1 X
temperature.
629 Exhaust 2434 1/10 X
Temperature
Right
630 Exhaust 2435 1/10 X
Temperature Left
637 Engine Intercooler 52 1/10 X
Temperature
684 Alternator 4078 1/100 X
efficiency
687 Supply gas 5867 1/100 X
methane
percentage

A029X159 (Issue 31) 193 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content SPN Scaling AGC-5C Note


901 Nominal power 166 1/1 X
911 Intake Manifold 1 3563 1/100 X
Absolute Pressure
913 Fuel supply pump 1381 1/100 X
inlet pres.
914 Fuel Filter 1382 1/100 X
Differential
Pressure
916 DAVR generator 1/1 X
voltage
917 DAVR generator 1/10 X
frequency
918 DAVR generator 1/1 X
current
919 DAVR Excitation 3381 1/10 X
Field Current
921 DAVR generator 1/1 X
reactive power
922 DAVR generator 1/100 X
power factor
923 DAVR generator X 0 = Lagging
power factor
lagging 1 = Leading

925 DAVR generator 1/1 X


power
927 DAVR generator 1/1 X
apparent power
928 DAVR PT100 1 1/1 X
929 DAVR PT100 2 1/1 X
930 DAVR PT100 3 1/1 X
939 Engine ECU 1136 1/10 X
temperature
947 Exh.P T01 1137 1/10 X
948 Exh.P T02 1138 1/10 X
949 Exh.P T03 1139 1/10 X
950 Exh.P T04 1140 1/10 X
951 Exh.P T05 1141 1/10 X
952 Exh.P T06 1142 1/10 X
953 Exh.P T07 1143 1/10 X
954 Exh.P T08 1144 1/10 X

Copyright © 2023 Cummins Inc. 194 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content SPN Scaling AGC-5C Note


955 Exh.P T09 1145 1/10 X
956 Exh.P T10 1146 1/10 X
957 Exh.P T11 1147 1/10 X
958 Exh.P T12 1148 1/10 X
959 Exh.P T13 1149 1/10 X
960 Exh.P T14 1150 1/10 X
961 Exh.P T15 1151 1/10 X
962 Exh.P T16 1152 1/10 X
963 Exh.P T17 1153 1/10 X
964 Exh.P T18 1154 1/10 X
965 Exh.P T19 1155 1/10 X
966 Exh.P T20 1156 1/10 X
971 Aux Coolant temp 1212 1/1 X
974 Turbo inlet 1172 1/1 X
temperature
975 HT Coolant Outlet 1637 1/10 X
Temp. high
resolution
976 Turbocharger 103 X Multiply by 4 for
Speed 1 actual RPM
Unscaled
977 Turbocharger Oil 1665 X 0=Off
Level Switch
1=On
978 LT Coolant Outlet 1203 1/100 X
Pressure
981 HT Coolant Inlet 8487 1/10 X
Temperature High
Resolution
982 LT Coolant Inlet 8488 1/10 X
Temperature High
Resolution
983 LT Coolant Outlet 8489 1/10 X
Temperature High
Resolution
984 HT Coolant Outlet 5708 1/100 X
Pressure 2
987 Throttle Valve 1 5631 1/100 X
Differential
Pressure

A029X159 (Issue 31) 195 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content SPN Scaling AGC-5C Note


988 Turbocharger 1169 X Multiply by 4 for
Speed 2 actual RPM
Unscaled
1021.13 Malfunction 1213 X
indicator lamp
1021.14 Amber warning 624 X
lamp
1021.15 Red stop lamp 623 X
1060 Turbocharger 1188 1/1 X
Wastegate
Actuator 1
Position
1072 Engine Mixer 1 8477 1/100 X
Intake Pressure
1073 Engine Mixer 2 8607 1/100 X
Intake Pressure
1074 Turbocharger 1 1184 1/10 X
Turbine Outlet
Temperature
1075 Turbocharger 1 2629 1/10 X
Compressor
Outlet
Temperature
1080 LT Coolant Inlet 1/100 X
Pressure
1081 Knock Level cyl 1 1352 1/1 X
Child
1082 Knock Level cyl 2 1353 1/1 X
Child
1083 Knock Level cyl 3 1354 1/1 X
Child
1084 Knock Level cyl 4 1355 1/1 X
Child
1085 Knock Level cyl 5 1356 1/1 X
Child
1086 Knock Level cyl 6 1357 1/1 X
Child
1087 Spark Voltage 1294 1/100 X
Cylinder 1 Child
1088 Spark Voltage 1295 1/100 X
Cylinder 2 Child
1089 Spark Voltage 1296 1/100 X
Cylinder 3 Child

Copyright © 2023 Cummins Inc. 196 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content SPN Scaling AGC-5C Note


1090 Spark Voltage 1297 1/100 X
Cylinder 4 Child
1091 Spark Voltage 1298 1/100 X
Cylinder 5 Child
1092 Spark Voltage 1299 1/100 X
Cylinder 6 Child
1093 Ignition Timing 1413 1/10 X
Cylinder 1 Child
1094 Ignition Timing 1414 1/10 X
Cylinder 2 Child
1095 Ignition Timing 1415 1/10 X
Cylinder 3 Child
1096 Ignition Timing 1416 1/10 X
Cylinder 4 Child
1097 Ignition Timing 1417 1/10 X
Cylinder 5 Child
1098 Ignition Timing 1418 1/10 X
Cylinder 6 Child
1099 Knock Counter 1/1 X
Cylinder 1 Child
1100 Knock Counter 1/1 X
Cylinder 2 Child
1101 Knock Counter 1/1 X
Cylinder 3 Child
1102 Knock Counter 1/1 X
Cylinder 4 Child
1103 Knock Counter 1/1 X
Cylinder 5 Child
1104 Knock Counter 1/1 X
Cylinder 6 Child
1105 Engine throttle 3464 1/100 X
actuator 1 control
command
1106 Engine fuel 633 1/100 X
actuator 1 control
command
1365 DAVR LED state X
U=U
1365.1 DAVR LED state X
PF/KVAR
1365.2 DAVR LED state X
Manuel

A029X159 (Issue 31) 197 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content SPN Scaling AGC-5C Note


1365.3 DAVR LED state X
Fault
1365.4 DAVR LED state X
Iexc
1365.5 DAVR LED state X
volt
1365.6 DAVR LED state X
Hz
1365.7 DAVR LED state X
Power ON
1365.8 DAVR LED state X
Blink Iexc
1366 DAVR alarm X
General trip
1366.1 DAVR alarm X
Short circuit
1366.1 DAVR alarm over X
temperature
PT100 3
1366.11 DAVR alarm over X
stator current
1366.12 DAVR alarm X
current U
1366.13 DAVR alarm X
current V
1366.14 DAVR alarm X
current W
1366.15 DAVR alarm X
imbalance stator
current
1366.2 DAVR alarm loss X
of voltage sensing
1366.3 DAVR alarm X
under excitation
1366.4 DAVR alarm over X
excitation on level
1366.5 DAVR alarm over X
excitation on
curve
1366.6 DAVR alarm over X
voltage alarm

Copyright © 2023 Cummins Inc. 198 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content SPN Scaling AGC-5C Note


1366.7 DAVR alarm over X
temperature
PT100 1
1366.8 DAVR alarm over X
temperature PTC
1366.9 DAVR alarm over X
temperature
PT100 2
1367 DAVR alarm open X
diode
1367.1 DAVR alarm short X
circuit diode
1370 SPN1 HI-Word DM1

5.1.18 Function Code 4 (04h): Read Input Registers (EIC)


(Address, Bit: 1371-1994)

Address Content SPN Scaling AGC-5C Note


1371 SPN1 LO-Word DM1
1372 SPN2 HI-Word DM1
1373 SPN2 LO-Word DM1
1374 SPN3 HI-Word DM1
1375 SPN3 LO-Word DM1
1376 SPN4 HI-Word DM1
1377 SPN4 LO-Word DM1
1378 SPN5 HI-Word DM1
1379 SPN5 LO-Word DM1
1380 SPN6 HI-Word DM1
1381 SPN6 LO-Word DM1
1382 SPN7 HI-Word DM1
1383 SPN7 LO-Word DM1
1384 SPN8 HI-Word DM1
1385 SPN8 LO-Word DM1
1386 SPN9 HI-Word DM1
1387 SPN9 LO-Word DM1
1388 SPN10 HI-Word DM1
1389 SPN10 LO-Word DM1

A029X159 (Issue 31) 199 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content SPN Scaling AGC-5C Note


1402 FMI1 DM1
1403 FMI2 DM1
1404 FMI3 DM1
1405 FMI4 DM1
1406 FMI5 DM1
1407 FMI6 DM1
1408 FMI7 DM1
1409 FMI8 DM1
1410 FMI9 DM1
1411 FMI10 DM1
1418 Occurrence DM1
counter 1
1419 Occurrence DM1
counter 2
1420 Occurrence DM1
counter 3
1421 Occurrence DM1
counter 4
1422 Occurrence DM1
counter 5
1423 Occurrence DM1
counter 6
1424 Occurrence DM1
counter 7
1425 Occurrence DM1
counter 8
1426 Occurrence DM1
counter 9
1427 Occurrence DM1
counter 10
1434 SPN1 HI-Word DM2
1435 SPN1 LO-Word DM2
1436 SPN2 HI-Word DM2
1437 SPN2 LO-Word DM2
1438 SPN3 HI-Word DM2
1439 SPN3 LO-Word DM2
1440 SPN4 HI-Word DM2
1441 SPN4 LO-Word DM2

Copyright © 2023 Cummins Inc. 200 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content SPN Scaling AGC-5C Note


1442 SPN5 HI-Word DM2
1443 SPN5 LO-Word DM2
1444 SPN6 HI-Word DM2
1445 SPN6 LO-Word DM2
1446 SPN7 HI-Word DM2
1447 SPN7 LO-Word DM2
1448 SPN8 HI-Word DM2
1449 SPN8 LO-Word DM2
1450 SPN9 HI-Word DM2
1451 SPN9 LO-Word DM2
1452 SPN10 HI-Word DM2
1453 SPN10 LO-Word DM2
1466 FMI1 DM2
1467 FMI2 DM2
1468 FMI3 DM2
1469 FMI4 DM2
1470 FMI5 DM2
1471 FMI6 DM2
1472 FMI7 DM2
1473 FMI8 DM2
1474 FMI9 DM2
1475 FMI10 DM2
1482 Occurrence DM2
counter 1
1483 Occurrence DM2
counter 2
1484 Occurrence DM2
counter 3
1485 Occurrence DM2
counter 4
1486 Occurrence DM2
counter 5
1487 Occurrence DM2
counter 6
1488 Occurrence DM2
counter 7

A029X159 (Issue 31) 201 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content SPN Scaling AGC-5C Note


1489 Occurrence DM2
counter 8
1490 Occurrence DM2
counter 9
1491 Occurrence DM2
counter 10
1777 Turbocharger 5370 1/1 X
Wastegate
Actuator 1
Desired Position
1792 Maximum Crank 3670 1/1 X
Attempts per Start
Attempt
1793 Turbocharger 1 5541 1/100 X
Turbine Outlet
Pressure
1794 Turbocharger 2 5544 1/100 X
Turbine Outlet
Pressure
1795 Engine Fuel 6393 1/100 X
System 1 Total
Intake Mass Air
Flow Rate
1796 Engine Fuel 8310 1/100 X
System 2 Total
Intake Mass Air
Flow Rate
1797 Engine Exhaust 5749 1/100 X
Pressure 2
1798 Crank Attempt 3671 1/1 X
Count on Present
Start Attempt
1799 Lube Oil Pressure 8622 1/100 X
Threshold
1800 Knock Level cyl 1 1352 1/1 X
1801 Knock Level cyl 2 1353 1/1 X
1802 Knock Level cyl 3 1354 1/1 X
1803 Knock Level cyl 4 1355 1/1 X
1804 Knock Level cyl 5 1356 1/1 X
1805 Knock Level cyl 6 1357 1/1 X
1806 Knock Level cyl 7 1358 1/1 X
1807 Knock Level cyl 8 1359 1/1 X

Copyright © 2023 Cummins Inc. 202 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content SPN Scaling AGC-5C Note


1808 Knock Level cyl 9 1360 1/1 X
1809 Knock Level cyl 1361 1/1 X
10
1810 Knock Level cyl 1362 1/1 X
11
1811 Knock Level cyl 1363 1/1 X
12
1824 Exhaust Port 1137 1/10 X
Temp cyl 1
1825 Exhaust Port 1138 1/10 X
Temp cyl 2
1826 Exhaust Port 1139 1/10 X
Temp cyl 3
1827 Exhaust Port 1140 1/10 X
Temp cyl 4
1828 Exhaust Port 1141 1/10 X
Temp cyl 5
1829 Exhaust Port 1142 1/10 X
Temp cyl 6
1830 Exhaust Port 1143 1/10 X
Temp cyl 7
1831 Exhaust Port 1144 1/10 X
Temp cyl 8
1832 Exhaust Port 1145 1/10 X
Temp cyl 9
1833 Exhaust Port 1146 1/10 X
Temp cyl 10
1834 Exhaust Port 1147 1/10 X
Temp cyl 11
1835 Exhaust Port 1148 1/10 X
Temp cyl 12
1844 Ignition Timing 1413 1/10 X
Cylinder 1
1845 Ignition Timing 1414 1/10 X
Cylinder 2
1846 Ignition Timing 1415 1/10 X
Cylinder 3
1847 Ignition Timing 1416 1/10 X
Cylinder 4
1848 Ignition Timing 1417 1/10 X
Cylinder 5

A029X159 (Issue 31) 203 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content SPN Scaling AGC-5C Note


1849 Ignition Timing 1418 1/10 X
Cylinder 6
1850 Ignition Timing 1419 1/10 X
Cylinder 7
1851 Ignition Timing 1420 1/10 X
Cylinder 8
1852 Ignition Timing 1421 1/10 X
Cylinder 9
1853 Ignition Timing 1422 1/10 X
Cylinder 10
1854 Ignition Timing 1423 1/10 X
Cylinder 11
1855 Ignition Timing 1424 1/10 X
Cylinder 12
1864 Spark Voltage 1294 1/100 X
Cylinder 1
1865 Spark Voltage 1295 1/100 X
Cylinder 2
1866 Spark Voltage 1296 1/100 X
Cylinder 3
1867 Spark Voltage 1297 1/100 X
Cylinder 4
1868 Spark Voltage 1298 1/100 X
Cylinder 5
1869 Spark Voltage 1299 1/100 X
Cylinder 6
1870 Spark Voltage 1300 1/100 X
Cylinder 7
1871 Spark Voltage 1301 1/100 X
Cylinder 8
1872 Spark Voltage 1302 1/100 X
Cylinder 9
1873 Spark Voltage 1303 1/100 X
Cylinder 10
1874 Spark Voltage 1304 1/100 X
Cylinder 11
1875 Spark Voltage 1305 1/100 X
Cylinder 12
1887 Battery Potential / 168 1/10 X
P1
1897 Knock Counter 1/1 X
Cylinder 1

Copyright © 2023 Cummins Inc. 204 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content SPN Scaling AGC-5C Note


1898 Knock Counter 1/1 X
Cylinder 2
1899 Knock Counter 1/1 X
Cylinder 3
1900 Knock Counter 1/1 X
Cylinder 4
1901 Knock Counter 1/1 X
Cylinder 5
1902 Knock Counter 1/1 X
Cylinder 6
1903 Knock Counter 1/1 X
Cylinder 7
1904 Knock Counter 1/1 X
Cylinder 8
1905 Knock Counter 1/1 X
Cylinder 9
1906 Knock Counter 1/1 X
Cylinder 10
1907 Knock Counter 1/1 X
Cylinder 11
1908 Knock Counter 1/1 X
Cylinder 12

A029X159 (Issue 31) 205 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content SPN Scaling AGC-5C Note


1920 Operating State 3543 X Bit state 0000b =
Engine Stopped
Bit state 0001b =
Pre-Start
Bit state 0010b =
Starting
Bit state 0011b =
Warm-Up
Bit state 0100b =
Running
Bit state 0101b =
Cool-down
Bit state 0110b =
Engine Stopping
Bit state 0111b =
Post-Run
Bit states 1000-
1101b = available
for SAE
assignment
Bit state 1110b =
reserved
Bit state 1111b =
not available
1924 Fuel Shutoff 1 632 X 0 = Open (fuel
control supplied to
engine)
1 = Closed (no
fuel supplied to
engine)
2 = Reserved
3 = Don't care /
take no action
1925 Fuel Shutoff 2 2807 X 0 = Open (fuel
control supplied to
engine)
1 = Closed (no
fuel supplied to
engine)
2 = Reserved
3 = Don't care /
take no action

Copyright © 2023 Cummins Inc. 206 A029X159 (Issue 31)


8-2023 5. DEIF AGC-5

Address Content SPN Scaling AGC-5C Note


1927 Oil Pressure 3589 X 0=Off
Priming Pump
Control 1=On

1932 Controlled 3606 X 0=Off


Shutdown
Request 1=On
2=Reserved
3=No action
1933 Emergency 3607 X 0=Off
Shutdown
Indication 1=On
2=Reserved
3=No action
1934 Derate Request 3644 1/1 X
1936 Fuel Valve Diff 1391 1/100 X
Pressure
1951 Pre Filter Oil 1208 1/10 X
Pressure
1952 Exhaust Gas 1209 1/100 X
Pressure
1954 Gas Mass Flow 1241 1/10 X
Rate 1
1959 Throttle Valve 1 51 1/1 X
Position
1960 Throttle Valve 2 3673 1/1 X
Position
1962 ECU Temperature 1136 1/10 X
1976 Turbo Compr. 3470 1/100 X
Bypass Actuator 1
Command
1978 Turbo Compr. 3675 1/1 X
Bypass Actuator 1
Position
1988 Oil Priming Pump 3550 X 0 = OFF
Switch
1 = ON
2 = Error

A029X159 (Issue 31) 207 Copyright © 2023 Cummins Inc.


5. DEIF AGC-5 8-2023

Address Content SPN Scaling AGC-5C Note


1989 Oil Priming State 3551 X 0 = Not
sufficiently
lubricated
1 = Sufficiently
lubricated
2 = Unable to
determine if
sufficiently
lubricated
3 = not installed /
not available
1994 Engine Torque 899 X 15 states
Mode

Copyright © 2023 Cummins Inc. 208 A029X159 (Issue 31)


6 DMC 1000
6.1 DMC 1000 Modbus Register Map
6.1.1 DMC 1000 Modbus Parametric Data
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Addr System Name Access Specifications Description Function

Multiplier: Unit:
1.000000000000 Lower Limit: .000 Logical address
MB Logical Read/ Offset: 0
42001 Upper Limit: to be read via Communications
Read Address Write
Size (bits): 16 65535.000 Modbus
Sign: U Default: 0
Multiplier:
Unit:
1.000000000000 Logical data to
MB Logical Read Lower Limit:
42002 Offset: 0 be read via Communications
Read Data Only Upper Limit:
Size (bits): 32 Modbus
Default:
Sign: U
Multiplier:
Unit:
1.000000000000 Hard coded
Read Lower Limit:
42009 Device Type Offset: 0 device type id = Communications
Only Upper Limit:
Size (bits): 16 52 (0x0034)
Default:
Sign: U
Multiplier:
Unit:
0.000100000000
Software Read Lower Limit: Software version Controller
42010 Offset: 0
Version Only Upper Limit: number Information
Size (bits): 16
Default:
Sign: U
Multiplier: The most
Unit:
1.000000000000 recently
Current Fault Read Lower Limit: Fault and Event
42012 Offset: 0 occurring fault
Status Only Upper Limit: Info
Size (bits): 16 which is still
Default: active
Sign: U

A029X159 (Issue 31) 209 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Multiplier:
Unit: Volts
1.000000000000
Genset L1N Read Lower Limit: Generator set
42018 Offset: 0 Voltage
Voltage Only Upper Limit: L1N voltage
Size (bits): 16
Default
Sign: U
Multiplier:
1.000000000000 Unit: Volts
Genset L2N Read Offset: 0 Lower Limit: Generator set
42019 Voltage
Voltage Only Size (bits): 16 Upper Limit: L2N voltage
Sign: U Default

Multiplier:
Unit: Volts
1.000000000000
Genset L3N Read Lower Limit: Generator set
42020 Offset: 0 Voltage
Voltage Only Upper Limit: L3N voltage
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Volts
Genset LN 1.000000000000 Generator set
Read Lower Limit:
42021 Average Offset: 0 LN average Voltage
Only Upper Limit:
Voltage Size (bits): 16 voltage
Default
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L1L2 Read Lower Limit: Generator set
42022 Offset: 0 Voltage
Voltage Only Upper Limit: L1L2 voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L2L3 Read Lower Limit: Generator set
42023 Offset: 0 Voltage
Voltage Only Upper Limit: L2L3 voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L3L1 Read Lower Limit: Generator set
42024 Offset: 0 Voltage
Voltage Only Upper Limit: L3L1 voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
Genset LL 1.000000000000 Generator set
Read Lower Limit:
42025 Average Offset: 0 LL average Voltage
Only Upper Limit:
Voltage Size (bits): 16 voltage
Default:
Sign: U

Copyright © 2023 Cummins Inc. 210 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Multiplier:
Unit: Amps
1.000000000000
Genset L1 Read Lower Limit: Generator set
42026 Offset: 0 Current
Current Only Upper Limit: L1 current
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Genset L2 Read Lower Limit: Generator set
42027 Offset: 0 Current
Current Only Upper Limit: L2 current
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Genset L3 Read Lower Limit: Generator set
42028 Offset: 0 Current
Current Only Upper Limit: L3 current
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Amps
Genset 1.000000000000
Read Lower Limit: Generator set
42029 Average Offset: 0 Current
Only Upper Limit: average current
Current Size (bits): 16
Default
Sign: U
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: Generator set
42030 Genset L1 kW Offset: 0 Current
Only Upper Limit: L1 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: Generator set
42031 Genset L2 kW Offset: 0 Current
Only Upper Limit: L2 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: Generator set
42032 Genset L3 kW Offset: 0 Power
Only Upper Limit: L3 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Genset Total Read Lower Limit: Generator set
42033 Offset: 0 Power
kW Only Upper Limit: total kW
Size (bits): 16
Default:
Sign: S

A029X159 (Issue 31) 211 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Multiplier:
Unit: kVAR
1.000000000000
Genset L1 Read Lower Limit: Generator set
42034 Offset: 0 Power
kVAR Only Upper Limit: L1 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset L2 Read Lower Limit: Generator set
42035 Offset: 0 Power
kVAR Only Upper Limit: L2 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset L3 Read Lower Limit: Generator set
42036 Offset: 0 Power
kVAR Only Upper Limit: L3 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset Total Read Lower Limit: Generator set
42037 Offset: 0 Power
kVAR Only Upper Limit: total kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit:
0.010000000000 Generator set
Genset Total Read Lower Limit:
42038 Offset: 0 total power Power
Power Factor Only Upper Limit:
Size (bits): 8 factor
Default:
Sign: S
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: Generator set
42039 Genset L1 kVA Offset: 0 Power
Only Upper Limit: L1 kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: Generator Set
42040 Genset L2 kVA Offset: 0 Power
Only Upper Limit: L2 kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: Generator set
42041 Genset L3 kVA Offset: 0 Power
Only Upper Limit: L3 kVA
Size (bits): 16
Default:
Sign: U

Copyright © 2023 Cummins Inc. 212 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Multiplier:
Unit: kVA
1.000000000000
Genset Total Read Lower Limit: kVA Generator set
42042 Offset: 0 Power
kVA Only Upper Limit: kVA total kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Hz Generator set
0.100000000000
MB Genset Read Lower Limit: Hz line frequency
42043 Offset: 0 Communications
Frequency Only Upper Limit: Hz scaled by 10 =
Size (bits): 16 1Hz for Modbus
Default:
Sign: U
Multiplier:
Unit: kWh Generator set
1.000000000000
Genset Total Read Lower Limit: kWh total negative
42044 Offset: 0 Energy
Negative kWh Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh Generator set
.100000000000
Genset Total Read Lower Limit: kWh total positive
42046 Offset: 0 Energy
Positive kWh Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Generator set
Genset Total Read Lower Limit: kWh
42048 Offset: 0 total net kWh Energy
Net kWh Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVARh Generator set
Genset Total 1.000000000000
Read Lower Limit: kVARh total negative
42050 Negative Offset: 0 Energy
Only Upper Limit: kVARh kVARh
kVARh Size (bits): 32
Default: accumulation
Sign: U
Multiplier:
Unit: kVARh Generator set
1.000000000000
Genset Total Read Lower Limit: kVARh total positive
42052 Offset: 0 Energy
Positive kVARh Only Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kVARh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVARh
42054 Offset: 0 total net kVARh Energy
Net kVARh Only Upper Limit: kVARh
Size (bits): 32 accumulation
Default:
Sign: S

A029X159 (Issue 31) 213 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Multiplier:
Unit: kVAh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVAh
40056 Offset: 0 total kVAh Energy
kVAh Only Upper Limit: kVAh
Size (bits): 32 accumulation
Default:
Sign: U
Calculated
Multiplier: Amps which
Unit: Amps
Genset 1.000000000000 represent 100%
Read Lower Limit:
42058 Available Offset: 0 generator set Current
Only Upper Limit:
Current Size (bits): 16 bus current --
Default: used by
Sign: U
barograph
Generator set
Multiplier: L1 current as
Unit: %
Genset L1 0.100000000000 percent of
Read Lower Limit:
42059 Current Offset: 0 generator set Current
Only Upper Limit:
Percent Size (bits): 16 total current
Default: capacity--used
Sign: U
by barograph
Generator set
Multiplier: L2 current as
Unit: %
Genset L2 0.100000000000 percent of
Read Lower Limit:
42060 Current Offset: 0 generator set Current
Only Upper Limit:
Percent Size (bits): 16 total current
Default: capacity--used
Sign: U
by barograph
Generator set
Multiplier: L3 current as
Unit: %
Genset L3 0.100000000000 percent of
Read Lower Limit:
42061 Current Offset: 0 generator set Current
Only Upper Limit:
Percent Size (bits): 16 total current
Default: capacity--used
Sign: U
by barograph

Multiplier: Generator set


Unit: % total kW as
0.100000000000
Genset Total Read Lower Limit: percent of total
42062 Offset: 0 Power
kW Percent Only Upper Limit: generator set
Size (bits): 16 capacity -- used
Default:
Sign: S by barograph
Generator set
Multiplier: frequency as
Unit: %
Genset 0.100000000000 percent of
Read Lower Limit:
42063 Frequency Offset: 0 system Frequency
Only Upper Limit:
Percent Size (bits): 16 frequency --
Default: used by
Sign: U
barograph

Copyright © 2023 Cummins Inc. 214 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Multiplier:
Unit: %
0.100000000000
Genset L1L2 Read Lower Limit: Generator set
42064 Offset: 0 Voltage
Voltage% Only Upper Limit: L1L2 voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
0.100000000000
Genset L2L3 Read Lower Limit: Generator set
42065 Offset: 0 Voltage
Voltage% Only Upper Limit: L2L3 voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
0.100000000000
Genset L3L1 Read Lower Limit: Generator set
42066 Offset: 0 Voltage
Voltage% Only Upper Limit: L3L1 voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L1N Read Lower Limit: Utility L1N
42118 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L2N Read Lower Limit: Utility L2N
42119 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L3N Read Lower Limit: Utility L3N
42120 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
Utility LN 1.000000000000
Read Lower Limit: Utility LN
42121 Average Offset: 0 Voltage
Only Upper Limit: average voltage
Voltage Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L1L2 Read Lower Limit: Utility L1L2
42122 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U

A029X159 (Issue 31) 215 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Multiplier:
Unit: Volts
1.000000000000
Utility L2L3 Read Lower Limit: Utility L2L3
42123 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L3L1 Read Lower Limit: Utility L3L1
42124 Offset: 0 Voltage
Voltage Only Upper Limit: voltage
Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Volts
Utility LL 1.000000000000
Read Lower Limit: Utility LL
42125 Average Offset: 0 Voltage
Only Upper Limit: average voltage
Voltage Size (bits): 16
Default: 0
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility L1 Read Lower Limit:
42126 Offset: 0 Utility L1 current Current
Current Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility L2 Read Lower Limit:
42127 Offset: 0 Utility L2 current Current
Current Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility L3 Read Lower Limit:
42128 Offset: 0 Utility L3 current Current
Current Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility Average Read Lower Limit: Utility average
42129 Offset: 0 Current
Current Only Upper Limit: current
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit:
42130 Utility L1 kW Offset: 0 Utility L1 kW Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: S

Copyright © 2023 Cummins Inc. 216 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Multiplier:
Unit: kW
1.000000000000
Read Lower Limit:
42131 Utility L2 kW Offset: 0 Utility L2 kW Power
Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit:
42132 Utility L3 kW Offset: 0 Utility L3 kW Power
Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit:
42133 Utility Total kW Offset: 0 Utility total kW Power
Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Utility L1 Read Lower Limit:
42134 Offset: 0 Utility L1 kVAR Power
kVARt Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Read Lower Limit:
42135 Utility L2 kVAR Offset: 0 Utility L2 kVAR Power
Only Upper Limit:
Size (bits): 16
Default
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Read Lower Limit:
42136 Utility L3 kVAR Offset: 0 Utility L3 kVAR Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Utility Total Read Lower Limit:
42137 Offset: 0 Utility total kVAR Power
kVAR Only Upper Limit:
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit:
.010000000000
Utility Total Read Lower Limit: Utility total
42138 Offset: 0 Power
Power Factor Only Upper Limit: power factor
Size (bits): 8
Default:
Sign: S

A029X159 (Issue 31) 217 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit:
42139 Utility L1 kVA Offset: 0 Utility L1 kVA Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit:
42140 Utility L2 kVA Offset: 0 Utility L2 kVA Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit:
42141 Utility L3 kVA Offset: 0 Utility L3 kVA Power
Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Utility Total Read Lower Limit:
42142 Offset: 0 Utility total kVA Power
kVA Only Upper Limit:
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Hz Utility line
.100000000000
MB Utility Read Lower Limit: frequency
42143 Offset: 0 Communications
Frequency Only Upper Limit: scaled by 10 =
Size (bits): 16 1Hz for Modbus
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit:
42144 Offset: 0 negative kWh Energy
Negative kWh Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit:
42146 Offset: 0 positive kWh Energy
Positive kWh Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit:
42148 Offset: 0 kWh Energy
kWh Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: S

Copyright © 2023 Cummins Inc. 218 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Multiplier:
Unit: kVARh
Utility Total 1.000000000000 Utility total
Read Lower Limit:
42150 Negative Offset: 0 negative kVARh Energy
Only Upper Limit:
kVARh Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kVARh
1.000000000000 Utility total
Utility Total Read Lower Limit:
42152 Offset: 0 positive kVARh Energy
Positive kVARh Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kVARh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit:
42154 Offset: 0 kVARh Energy
kVARh Only Upper Limit:
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVARh
1.000000000000
Utility Total Read Lower Limit: Utility total kVAh
42156 Offset: 0 Energy
kVAh Only Upper Limit: accumulation
Size (bits): 32
Default:
Sign: U
Multiplier:
Unit: kW Sum of
1.000000000000
System Total Read Lower Limit: generator set
42158 Offset: 0 Power
kW Only Upper Limit: bus and utility
Size (bits): 16 bus kW
Default:
Sign: S
Multiplier:
Unit: kVAR Sum of
1.000000000000
System Total Read Lower Limit: generator set
42159 Offset: 0 Power
kVAR Only Upper Limit: bus and utility
Size (bits): 16 bus kVAR
Default:
Sign: S

Multiplier: System total


Unit: power factor
0.010000000000
System Total Read Lower Limit: (totalized value
42160 Offset: 0 Power
Power Factor Only Upper Limit: of utility bus plus
Size (bits): 8 generator set
Default:
Sign: S bus)
Multiplier:
Unit: kVA Sum of
1.000000000000
System Total Read Lower Limit: generator set
42161 Offset: 0 Power
kVA Only Upper Limit: bus and utility
Size (bits): 16 bus kVA
Default:
Sign: U

A029X159 (Issue 31) 219 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Multiplier:
Unit: %
Utility L1 .100000000000
Read Lower Limit:
42162 Current Offset: 0 barograph Current
Only Upper Limit:
Percent Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
Utility L2 .100000000000
Read Lower Limit:
42163 Current Offset: 0 barograph Current
Only Upper Limit:
Percent Size (bits): 16
Default:
Sign: U
Multiplier:
.100000000000 Unit: %
Utility L3 Offset: 0 Lower Limit:
Read
42164 Current barograph Current
Only Size (bits): 16 Upper Limit:
Percent
Sign: U Default:

Multiplier:
.100000000000 Unit: % Utility total kW
Offset: 0 Lower Limit: as percent of
Utility Total kW Read
42165 total utility Power
Percent Only Size (bits): 16 Upper Limit: capacity -- used
Sign: S Default: by barograph

Multiplier: Unit: % Utility frequency


.100000000000 Lower Limit: as percent of
Utility
Read Offset: 0 System
42166 Frequency Upper Limit: Frequency
Only Frequency --
Percent Size (bits): 16 Default: used by
Sign: U barograph
Multiplier:
Unit: %
.100000000000
Utility L1L2 Read Lower Limit: Utility L1L2
42167 Offset: 0 Voltage
Voltage% Only Upper Limit: voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
.100000000000
Utility L2L3 Read Lower Limit: Utility L2L3
42168 Offset: 0 Voltage
Voltage% Only Upper Limit: voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
.100000000000
Utility L3L1 Read Lower Limit: Utility L3L1
42169 Offset: 0 Voltage
Voltage% Only Upper Limit: voltage%
Size (bits): 16
Default:
Sign: U

Copyright © 2023 Cummins Inc. 220 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Multiplier:
Unit: NA Number of
1.000000000000
Total Number Read Lower Limit: generator sets System
42200 Offset: 0
of Gensets Only Upper Limit: with non-zero Information
Size (bits): 16 ratings entered
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000 Sum of the
Total System Read Lower Limit: System
42201 Offset: 0 generator set
Capacity Only Upper Limit: Information
Size (bits): 16 kW ratings
Default:
Sign: S
Multiplier: Sum of the
Unit: kW
1.000000000000 generator set
Total Online Read Lower Limit: System
42202 Offset: 0 kW ratings for
Capacity Only Upper Limit: Information
Size (bits): 16 generator sets
Default: which are online
Sign: S
Multiplier:
Unit: seconds Countdown
Programmed .100000000000
Read Lower Limit: value of the
42203 Transition Offset: 0 PTC Timers
Only Upper Limit: programmed
Timer Size (bits): 16
Default: transition timer
Sign: U
Multiplier:
Unit: seconds
.100000000000 Countdown
Read Lower Limit:
42204 Transfer Timer Offset: 0 value of the PTC Timers
Only Upper Limit:
Size (bits): 16 transfer timer
Default: 0
Sign: U
Multiplier:
Unit: seconds
.100000000000 Countdown
Retransfer Read Lower Limit:
42205 Offset: 0 value of the PTC Timers
Timer Only Upper Limit:
Size (bits): 16 retransfer timer
Default:
Sign: U
Multiplier:
Unit: seconds Countdown
.100000000000
Maximum Read Lower Limit: value of the
42206 Offset: 0 PTC Timers
Parallel Timer Only Upper Limit: maximum
Size (bits): 16 parallel timer
Default:
Sign: U
Multiplier:
Unit: kW kW control
1.000000000000
kW Load Read Lower Limit: reference value Master Load
42207 Offset: 0
Reference Only Upper Limit: for utility Control
Size (bits): 16 paralleling
Default:
Sign: S

A029X159 (Issue 31) 221 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Multiplier:
Unit: seconds
Active .010000000000 Countdown
Read Lower Limit:
42212 Transition Offset: 0 timer value of PTC Timers
Only Upper Limit:
Timer Size (bits): 16 active timer
Default:
Sign: U
Multiplier:
Unit: Indicates the
1.000000000000
Hardware Read Lower Limit: hardware
42213 Offset: 0 Discrete Inputs
Version Only Upper Limit: version of the
Size (bits): 8 board
Default:
Sign: U

Multiplier: Unit: seconds


1.000000000000 Lower Limit: 0.000 Amount of time
Controller On Read Offset: 0 in seconds Controller
42214 Upper Limit:
Time Only controller has Information
Size (bits): 32 4294967295.000 been powered
Sign: U Default: 0.000
Multiplier:
Unit: kVAR kVAR control
1.000000000000
kVAR Load Read Lower Limit: reference value Master Load
42220 Offset: 0
Reference Only Upper Limit: for extended Control
Size (bits): 16 paralleling
Default:
Sign: S
Multiplier: Engineering
kVAR Load Unit: %
.010000000000 units value for
Setpoint Engr Read Lower Limit:
42221 Offset: 0 the kVAR load Analog Inputs
Units Display Only Upper Limit:
Size (bits): 16 setpoint analog
Value Default
Sign: S input

Multiplier: Engineering
kW Load Unit: %
.010000000000 units value for
Setpoint Engr Read Lower Limit:
42222 Offset: 0 the kW load Analog Inputs
Units Display Only Upper Limit:
Size (bits): 16 setpoint analog
Value Default:
Sign: S input

Multiplier: Power factor


Unit: setpoint analog
.010000000000
Power Factor Read Lower Limit: input value
42223 Offset: 0 Analog Inputs
Setpoint Only Upper Limit: (uses kVAR load
Size (bits): 8 setpoint analog
Default:
Sign: S input)
Multiplier:
Unit: degrees Utility to
.010000000000
Sync Phase Read Lower Limit: generator set L1
42226 Offset: 0 Phase
Difference Only Upper Limit: voltage phase
Size (bits): 16 angle
Default:
Sign: S

Copyright © 2023 Cummins Inc. 222 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Multiplier:
Unit:
1.000000000000
Current Add Read Lower Limit: Indicates the Load Add Shed
42250 Offset: 0
Level Only Upper Limit: next level to add Control
Size (bits): 8
Default:
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates the
Current Shed Read Lower Limit: Load Add Shed
42251 Offset: 0 next level to
Level Only Upper Limit: Control
Size (bits): 8 shed
Default
Sign: U
Multiplier: Engineering
Unit: VDC
Battery Voltage .010000000000 units value for
Read Lower Limit:
42291 Engr Units Offset: 0 the battery Analog Inputs
Only Upper Limit:
Display Value Size (bits): 16 voltage analog
Default input
Sign: U
Multiplier: Voltage level
kVAR Master Unit: VDC
.010000000000 commanded to
Load Control Read Lower Limit:
42292 Offset: 0 kVAR Master Analog Outputs
Output Only Upper Limit:
Size (bits): 16 load control
Predictor Value Default
Sign: S analog output

Multiplier: Voltage level


kW Master Unit: VDC
.010000000000 commanded to
Load Control Read Lower Limit:
42293 Offset: 0 kW Master load Analog Outputs
Output Only Upper Limit:
Size (bits): 16 control analog
Predictor Value Default
Sign: S output

Multiplier: Voltage level


Master Unit: VDC
.010000000000 commanded to
Frequency Read Lower Limit:
42294 Offset: 0 Master Analog Outputs
Bias Output Only Upper Limit:
Size (bits): 16 frequency bias
Predictor Value Default
Sign: S analog output

Multiplier: Voltage level


Unit: VDC
Master Voltage .010000000000 commanded to
Read Lower Limit:
42295 Bias Output Offset: 0 Master voltage Analog Outputs
Only Upper Limit:
Predictor Value Size (bits): 16 bias analog
Default: output
Sign: S
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 01 kW Read/ Offset: 0 Sets gen1 kW System
42305 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 1000.000

A029X159 (Issue 31) 223 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 02 kW Read/ Offset: 0 Sets gen2 kW System
42306 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 03 kW Read/ Offset: 0 Sets gen3 kW System
42307 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 04 kW Read/ Offset: 0 Sets gen4 kW System
42308 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 05 kW Read/ Offset: 0 Sets gen5 kW System
42309 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 06 kW Read/ Offset: 0 Sets gen6 kW System
42310 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 07 kW Read/ Offset: 0 Sets gen7 kW System
42311 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 08 kW Read/ Offset: 0 Sets gen8 kW System
42312 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 09 kW Read/ Offset: 0 Sets gen9 kW System
42313 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000

Copyright © 2023 Cummins Inc. 224 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 10 kW Read/ Offset: 0 Sets gen10 kW System
42314 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 11 kW Read/ Offset: 0 Sets gen11 kW System
42315 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Multiplier: Unit: kW
1.000000000000 Lower Limit: 0.000 kW
Genset 12 kW Read/ Offset: 0 Sets gen12 kW System
42316 Upper Limit: 32000.00
Rating Write rating Information
Size (bits): 16 kW
Sign: S Default: 0.000
Unit: seconds
Multiplier:
0.100000000000 Lower Limit: 0.000 Sets the
Programmed seconds
Read/ Offset: 0 programmed
42317 Transition PTC Timers
Write Upper Limit: 60 transition time
Delay (TDPT) Size (bits): 16
seconds delay
Sign: U
Default: 3.000
Unit: seconds
Multiplier:
0.100000000000 Lower Limit: 0.000
Transfer Delay Read/ seconds Sets the transfer
42318 Offset: 0 PTC Timers
(TDNE) Write Upper Limit: 120 time delay
Size (bits): 16
seconds
Sign: U
Default: 10.000
Unit: seconds
Multiplier:
0.100000000000 Lower Limit: 0.000
seconds Sets the
Retransfer Read/ Offset: 0
42319 retransfer time PTC Timers
Delay (TDEN) Write Upper Limit: 1800
Size (bits): 16 delay
seconds
Sign: U
Default: 600.000
Unit seconds
Multiplier: Sets the
0.000000000000 Lower Limit: 0.000
Maximum seconds maximum
Read/ Offset: 0
42320 Parallel Time parallel time for PTC Timers
Write Upper Limit: 1800
(TDMP) Size (bits): 16 soft load
seconds transfers
Sign: U
Default: 20.000

Multiplier: Unit: % Sets %kW


.010000000000 Lower Limit: –5.000 % generator set
Genset Bus Read/ Offset: 0 output level for Master Load
42321 Upper Limit: 105.000
%kW Setpoint Write open loop base Control
Size (bits): 16 % load extended
Sign: S Default: 80.000 paralleling

A029X159 (Issue 31) 225 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 110.000
Genset Volts
Read/ Offset: 0 Generator set
42322 Nominal AC Setup
Write Upper Limit: nominal voltage
Voltage Size (bits): 16
45000.000 Volts
Sign: U
Default: 480.000
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 110.000
Utility Nominal Read/ Volts Utility nominal
42323 Offset: 0 AC Setup
Voltage Write Upper Limit: voltage
Size (bits): 16
45000.000 Volts
Sign: U
Default: 480.000
Sets the center
Multiplier: frequency for
Unit: Hz
0.100000000000 the generator
Genset Center Read/ Lower Limit: 45.000 Hz
42324 Offset: 0 set frequency PTC Sensors
Frequency Write Upper Limit: 65.000
Size (bits): 16 sensor
Default: 60.000 bandwidth
Sign: U
settings
Sets the center
Multiplier: frequency for
Unit: Hz
0.100000000000
Utility Center Read/ Lower Limit: 45.000 Hz the utility
42325 Offset: 0 frequency PTC Sensors
Frequency Write Upper Limit: 65.000 Hz sensor
Size (bits): 16
Default: 60.000 bandwidth
Sign: U
settings
Multiplier:
Unit: Hz Use to define
0.100000000000
System Read/ Lower Limit: 45.000 Hz the system System
42327 Offset: 0
Frequency Write Upper Limit: 65.000 Hz nominal Information
Size (bits): 16 frequency
Default: 60.000
Sign: U
Multiplier: Unit: kW Sets the base
1.000000000000 Lower Limit: 0.000 kW load kW setpoint
Genset Bus Read/ Offset: 0 Master Load
42330 Upper Limit: in closed loop
kW Setpoint Write Control
Size (bits): 16 32767.000 kW extended
Sign: S Default: 0.000 paralleling

Unit: kVAR Sets the base


Multiplier:
1.000000000000 Lower Limit: 0.000 load kVAR
Genset Bus Read/ kVAR setpoint in Master Load
42331 Offset: 0
kVAR Setpoint Write Upper Limit: 32767 closed loop Control
Size (bits): 16 extended
kVAR
Sign: S paralleling
Default: 0.000

Copyright © 2023 Cummins Inc. 226 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function

Multiplier: Unit: % Sets %kVAR


.010000000000 Lower Limit: –5.000 % generator set
Genset Bus
Read/ Offset: 0 output level for Master Load
42332 %kVAR Upper Limit: 105.000
Write open loop base Control
Setpoint Size (bits): 16 % load extended
Sign: S Default: 0.000 paralleling

Multiplier: Sets the desired


Unit: generator set
Genset Bus .010000000000
Read/ Lower Limit: 0.700 bus power factor Master Load
42333 Power Factor Offset: 0
Write Upper Limit: 1.000 in closed loop Control
Setpoint Size (bits): 8
Default: 1.000 extended
Sign: S paralleling

Multiplier: Unit: kW
Genset 1.000000000000 Lower Limit: Setpoint for
Read/ Offset: 0 Master Load
42334 Unloaded -32768.000 kW generator set
Write Control
Level Size (bits): 16 Upper Limit: 32767 kW unloaded level
Sign: S Default: 50.000

Multiplier: Unit: kW Sets the peak


1.000000000000 Lower Limit: shave kW
Utility Bus kW Read/ Offset: 0 -32768.000 kW setpoint in Master Load
42337
Setpoint Write closed loop Control
Size (bits): 16 Upper Limit: 32767 kW extended
Sign: S Default: 100.000 paralleling
Unit: kW
Multiplier: Sets the utility
1.000000000000 Lower Limit:
Utility Bus kW kW constraint
Read/ Offset: 0 –32768.000 kW Master Load
42338 Constraint level for base
Write Upper Limit: Control
Level Size (bits): 16 load extended
32767.000 kW paralleling
Sign: S
Default: 100.000
Unit: kVAR Sets the peak
Multiplier:
1.000000000000 Lower Limit: shave kVAR
Utility Bus Read/ 32768.000 kVAR setpoint in Master Load
42339 Offset: 0
kVAR Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kVAR
Sign: S paralleling
Default: 100.000
Multiplier: Sets the desired
Unit:
Utility Bus .010000000000 utility bus power
Read/ Lower Limit: 0.700 Master Load
42340 Power Factor Offset: 0 factor in closed
Write Upper Limit: 1.000 Control
Setpoint Size (bits): 8 loop extended
Default: 1.000 paralleling
Sign: S
Unit: kW
Multiplier:
1.000000000000 Lower Limit:
Utility –32768.000 kW Setpoint for
Read/ Offset: 0 Master Load
42341 Unloaded utility unloaded
Write Upper Limit: Control
Level Size (bits): 16 level
32767.000 kVAR
Sign: S
Default: 50.000

A029X159 (Issue 31) 227 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Unit: seconds
Multiplier:
.100000000000 Lower Limit: 10.000 Sets ramp load
Extended seconds
Read/ Offset: 0 time for Master Load
42348 Parallel Ramp
Write Upper Limit: 900.000 extended Control
Load Time Size (bits): 16
seconds paralleling
Sign: U
Default: 60.000
Unit: seconds
Multiplier:
.200000000000 Lower Limit: 10.000 Sets the fail to
Fail To seconds
Read/ Offset: 0 synchronize Master Sync
42351 Synchronize
Write Upper Limit: 900.000 diagnostic time Control
Time Size (bits):16
seconds delay
Sign: U
Default: 120.000
Multiplier: Sets the
Unit: Hz
.00100000000 synchronizer slip
Read/ Lower Limit: –3.000 Hz Master Sync
42354 Slip Frequency Offset: 0 frequency (used
Write Upper Limit: 3.000 Hz Control
Size (bits):16 when sync
Default: 0.100 method is slip)
Sign: S
Unit: seconds
Multiplier:
.10000000000 Lower Limit: 0.000
seconds Sets the
Start Time Read/ Offset: 0 PTC Operating
42355 generator sets
Delay (TDES) Write Upper Limit: 3600.000 Mode
Size (bits):16 start time delay
seconds
Sign: U
Default: 0.000
Unit: seconds
Multiplier:
.100000000000 Lower Limit: 0.000
seconds Sets the
Stop Time Read/ Offset: 0 PTC Operating
42356 generator sets
Delay (TDEC) Write Upper Limit: 3600.000 Mode
Size (bits):16 stop time delay
seconds
Sign: U
Default: 0.000
Unit: seconds Indicates delay
Multiplier:
1.000000000000 Lower Limit: 0.000 between add
Genset Bus seconds
Read/ Offset: 0 levels when all Load Add Shed
42364 Load Add
Write Upper Limit: 60.000 generator sets Control
Delay Size (bits): 16
seconds are online and
Sign: U no utility
Default: 1.000
Unit: seconds
Multiplier:
1.000000000000 Lower Limit: 0.000 Indicates delay
Utility Bus seconds
Read/ Offset: 0 between add Load Add Shed
42365 Load Add
Write Upper Limit: 60.000 levels when on Control
Delay Size (bits): 16
seconds utility
Sign: U
Default: 1.000

Copyright © 2023 Cummins Inc. 228 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Unit: seconds
Multiplier: Lower Limit: 1.000
.100000000000 seconds Indicates delay
Load Shed Read/ Offset: 0 between shed Load Add Shed
42366 Upper Limit: 10.000
Delay Write levels when on Control
Size (bits): 8 seconds
generator sets
Sign: U Default: 1.000

Multiplier:
Unit:
1.000000000000 Indicates which
Load 1 Add Read/ Lower Limit: 1.000 Load Add Shed
42373 Offset: 0 add level load 1
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 1.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 2 Add Read/ Lower Limit: 1.000 Load Add Shed
42374 Offset: 0 add level load 2
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 2.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 3 Add Read/ Lower Limit: 1.000 Load Add Shed
42375 Offset: 0 add level load 3
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 3.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 4 Add Read/ Lower Limit: 1.000 Load Add Shed
42376 Offset: 0 add level load 4
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 4.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 5 Add Read/ Lower Limit: 1.000 Load Add Shed
42377 Offset: 0 add level load 5
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 5.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 6 Add Read/ Lower Limit: 1.000 Load Add Shed
42378 Offset: 0 add level load 6
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 6.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 1 Shed Read/ Lower Limit: 0.000 Load Add Shed
42379 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 1 is assigned to
Default: 0.000
Sign: U

A029X159 (Issue 31) 229 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Multiplier:
Unit:
1.000000000000 Indicates which
Load 2 Shed Read/ Lower Limit: 0.000 Load Add Shed
42380 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 2 is assigned to
Default: 5.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 3 Shed Read/ Lower Limit: 0.000 Load Add Shed
42381 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 3 is assigned to
Default: 4.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 4 Shed Read/ Lower Limit: 0.000 Load Add Shed
42382 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 4 is assigned to
Default: 3.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 5 Shed Read/ Lower Limit: 0.000 Load Add Shed
42383 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 5 is assigned to
Default: 2.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 6 Shed Read/ Lower Limit: 0.000 Load Add Shed
42384 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 6 is assigned to
Default: 1.000
Sign: U
Multiplier: Unit: % Use to set the
Genset Bus 1.000000000000 Lower Limit: 80.000 % %kW threshold
Read/ Offset: 0 System
42386 %kW Overload Upper Limit: 140.000 for gen bus
Write Information
Threshold Size (bits): 8 % overload
Sign: U Default: 105.000 condition

Unit: second
Multiplier:
1.000000000000 Lower Limit: 0.000
Genset Bus second Sets the delay
Read/ Offset: 0 System
42387 kW Overload time for overload
Write Upper Limit: 120.000 Information
Delay Size (bits): 8 based on kW
second
Sign: U
Default: 60.000

Multiplier: Use to set the


Genset Bus Unit: Hz underfrequency
.100000000000
Underfrequenc Read/ Lower Limit: 0.100 Hz offset threshold System
42388 Offset: 0
y Overload Write Upper Limit: 10.000 Hz for gen bus Information
Threshold Size (bits): 16 overload
Default: 3.000
Sign: U condition

Copyright © 2023 Cummins Inc. 230 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Multiplier:
Genset Bus Unit: second Sets the delay
1.000000000000
Underfrequenc Read/ Lower Limit: 0.000 Hz time for overload System
42389 Offset: 0
y Overload Write Upper Limit: 20.000 Hz based on Information
Delay Size (bits): 8 frequency
Default: 3.000
Sign: U
Unit: minute
Multiplier: Sets the initial
1.000000000000 Lower Limit: 1.000
minute delay time
Load Demand Read/ Offset: 0 Load Demand
42395 before load
Initial Delay Write Upper Limit: 60.000 Control
Size (bits): 8 demand will
minute operate
Sign: U
Default: 5.000

Multiplier: Sets the load


Unit: % demand restart
Load Demand 1.000000000000
Read/ Lower Limit: 20 % threshold (make Load Demand
42396 Restart Offset: 0
Write Upper Limit: 100 % larger than Control
Percent Size (bits): 8
Default: 80.000 shutdown
Sign: U percent)

Multiplier: Unit: Hours Sets run hours


1.000000000000 Lower Limit: 1.000 differential for
Load Demand
Read/ Offset: 0 Hours restarting a Load Demand
42397 Run Hours
Write generator set Control
Differential Size (bits): 16 Upper Limit: 500 Hours stopped due to
Sign: S Default: 50.000 load demand
Unit: minute Sets the delay
Multiplier:
1.000000000000 Lower Limit: 1.000 time between
Load Demand minute
Read/ Offset: 0 stopping Load Demand
42398 Shutdown
Write Upper Limit: 60.000 generator sets Control
Delay Size (bits): 8
minute due to load
Sign: U demand
Default: 5.000

Multiplier: Sets the load


Unit: % demand
Load Demand 1.000000000000
Read/ Lower Limit: 20 % shutdown Load Demand
42399 Shutdown Offset: 0
Write Upper Limit: 100 % threshold (make Control
Percent Size (bits): 8
Default: 60.000 smaller than
Sign: U restart percent)
Unit: seconds Sets how long to
Multiplier:
1.000000000000 Lower Limit: 10.000 wait for a
Genset Fail Read/ seconds generator set to Load Demand
42400 Offset: 0
Time Delay Write Upper Limit: 900.000 come online Control
Size (bits): 16 before declaring
seconds
Sign: U it failed
Default: 60.000
Unit: seconds
Multiplier:
.020000000000 Lower Limit: 0.100
seconds Sets the utility
Util CB Fail to Read/ Offset: 0
42401 breaker fail to Breaker Control
Close Delay Write Upper Limit: 1.000
Size (bits): 16 close time delay
seconds
Sign: U
Default: 0.26

A029X159 (Issue 31) 231 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Unit: seconds
Multiplier:
.200000000000 Lower Limit: 0.200
seconds Sets the utility
Util CB Fail to Read/ Offset: 0
42402 breaker fail to Breaker Control
Open Delay Write Upper Limit: 5.000
Size (bits): 8 open time delay
seconds
Sign: U
Default: 1
Unit: seconds
Multiplier:
.020000000000 Lower Limit: 0.000 Sets the time to
Util CB seconds
Read/ Offset: 0 allow for utility
42403 Recharge Breaker Control
Write Upper Limit: 60 breaker
Delay Size (bits): 16
seconds recharge
Sign: U
Default: 10.000
Unit: seconds
Multiplier:
.020000000000 Lower Limit: 0.100 Sets the
Gen CB Fail to Read/ seconds generator set
42404 Offset: 0 Breaker Control
Close Delay Write Upper Limit: 1.000 breaker fail to
Size (bits): 16 close time delay
seconds
Sign: U
Default: 0.260
Unit: seconds
Multiplier:
0.200000000000 Lower Limit: 0.200 Sets the
Gen CB Fail to Read/ seconds generator set
42405 Offset: 0 Breaker Control
Open Delay Write Upper Limit: 5.000 breaker fail to
Size (bits): 8 open time delay
seconds
Sign: U
Default: 1.000
Unit: seconds
Multiplier: Sets the time to
.020000000000 Lower Limit: 0.000
Gen CB seconds allow for
Read/ Offset: 0
42406 Recharge generator set Breaker Control
Write Upper Limit: 60.000
Delay Size (bits): 16 breaker
seconds recharge
Sign: U
Default: 10.000
Unit: degrees Sets the
Multiplier:
0.01000000000 Lower Limit: 0.100 permissive +/-
Permissive Read/ degrees phase angle Master Sync
42407 0Offset: 0
Phase Window Write Upper Limit: 20.000 window for the Control
Size (bits): 16 sync check
degrees
Sign: S function
Default: 10.000
Sets the
Multiplier: permissive +/-
Unit: %
Permissive .100000000000 voltage
Read/ Lower Limit: 0.5000 % Master Sync
42408 Voltage Offset: 0 acceptance
Write Upper Limit: 10.000 % Control
Window Size (bits): 16 window for the
Default: 5.000 sync check
Sign: U
function

Copyright © 2023 Cummins Inc. 232 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Unit: seconds Sets the
Multiplier:
.020000000000 Lower Limit: 0.500 permissive
Permissive Read/ seconds acceptance Master Sync
42409 Offset: 0
Window Time Write Upper Limit: 5.000 window dwell Control
Size (bits): 16 time for the sync
seconds
Sign: U check function
Default: 0.500

Multiplier: Sets the


Unit: Hz maximum
Permissive .001000000000
Read/ Lower Limit: 0.001 Hz frequency Master Sync
42410 Frequency Offset: 0
Write Upper Limit: 1.000 Hz difference Control
Window Size (bits): 32
Default: 1.000 allowed for
Sign: U permissive close
Unit: degrees Sets a sync
Multiplier:
0.010000000000 Lower Limit: –50.000 phase offset to
Sync Phase Read/ degrees accommodate Master Sync
42412 Offset: 0
Offset Write Upper Limit: 50.000 sync across Control
Size (bits): 16 transformer with
degrees
Sign: S phase shift
Default: 0.000

Multiplier: Proportional
Unit: gain for kW
1.000000000000
Read/ Lower Limit: 0.000 closed loop Master Load
42414 kW Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 60.000
Sign: U paralleling
Multiplier: Integral gain for
Unit:
1.000000000000 kW closed loop
Read/ Lower Limit: 0.000 Master Load
42415 kW KI Offset: 0 control in
Write Upper Limit: 255.000 Control
Size (bits): 8 extended
Default: 60.000 paralleling
Sign: U

Multiplier: Proportional
Unit: gain for kVAR
1.000000000000
Read/ Lower Limit: 0.000 closed loop Master Load
42416 kVAR Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 120.000
Sign: U paralleling
Multiplier: Integral gain for
Unit:
1.000000000000 kVAR closed
Read/ Lower Limit: 0.000 Master Load
42417 kVAR KI Offset: 0 loop control in
Write Upper Limit: 255.000 Control
Size (bits): 8 extended
Default: 50.000 paralleling
Sign: U
Multiplier:
Unit: Selects which
1.000000000000
Scheduler Read/ Lower Limit: 1.000 scheduler System
42418 Offset: 0
Program Select Write Upper Limit: 12.000 program to view Scheduler
Size (bits): 8 or edit
Default: 1.000
Sign: U

A029X159 (Issue 31) 233 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Unit: hour
Multiplier:
1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler hour
Read/ Offset: 0 start hour for the System
42423 Program x
Write Upper Limit: 23.000 selected Scheduler
Start Hour Size (bits): 8
hour program
Sign: U
Default: 0.000
Unit: minute
Multiplier:
1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler minute
Read/ Offset: 0 start minute for System
42424 Program x
Write Upper Limit: 59.000 the selected Scheduler
Start Minute Size (bits): 8
minute program
Sign: U
Default: 0.000
Unit: hour
Multiplier:
1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler hour
Read/ Offset: 0 duration hours System
42425 Program x
Write Upper Limit: 23.000 for the selected Scheduler
Duration Hours Size (bits): 8
hour program
Sign: U
Default: 0.000
Unit: minute
Multiplier:
Scheduler 1.000000000000 Lower Limit: 0.000 Use to adjust
Program x Read / minute duration minutes System
42426 Offset: 0
Duration Write Upper Limit: 59.000 for the selected Scheduler
Minutes Size (bits): 8 program
minute
Sign: U
Default: 0.000
Multiplier:
Unit: Selects which
Scheduler 1.000000000000
Read/ Lower Limit: 1.000 scheduler System
42427 Exception Offset: 0
Write Upper Limit: 6.000 exception to Scheduler
Select Size (bits): 8
Default: 1.000 view or edit
Sign: U
Unit: month
Multiplier:
1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler month
Read/ Offset: 0 the month of the System
42430 Exception x
Write Upper Limit: 12.000 selected Scheduler
Month Size (bits): 8
month exception
Sign: U
Default: 1.000
Unit: date
Multiplier:
1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler date
Read/ Offset: 0 the date of the System
42431 Exception x
Write Upper Limit: 31.000 selected Scheduler
Date Size (bits): 8
date exception
Sign: U
Default: 1.000

Copyright © 2023 Cummins Inc. 234 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Unit: hour
Multiplier:
1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler hour
Read/ Offset: 0 the start hour of System
42432 Exception x
Write Upper Limit: 23.000 the selected Scheduler
Hour Size (bits):8
hour exception
Sign: U
Default: 0.000
Unit: minute
Multiplier:
1.000000000000 Lower Limit: 0.000 Use to adjust
Scheduler minute
Read/ Offset: 0 the start minute System
42433 Exception x
Write Upper Limit: 59.000 of the selected Scheduler
Minute Size (bits): 8
minute exception
Sign: U
Default: 0.000
Unit: days
Multiplier: Use to adjust
1.000000000000 Lower Limit: 0.000
Scheduler days the duration
Read/ Offset: 0 System
42434 Exception x days of the
Write Upper Limit: 44.000 Scheduler
Duration Days Size (bits): 8 selected
days exception
Sign: U
Default: 0.000
Multiplier: Unit: hour Use to adjust
Scheduler 1.000000000000 Lower Limit: 0.000 the duration
Read/ Offset: 0 hour System
42435 Exception x hours of the
Write Scheduler
Duration Hours Size (bits): 8 Upper Limit: 23 hour selected
Sign: U Default: 0.000 exception

Unit: minute
Multiplier: Use to adjust
Scheduler 1.000000000000 Lower Limit: 0.000
minute the duration
Exception x Read/ Offset: 0 System
42436 minutes of the
Duration Write Upper Limit: 59.000 Scheduler
Size (bits): 8 selected
Minutes minute
Sign: U exception
Default: 0.000
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 110.000
Genset PT Volts Generator Set
Read/ Offset: 0
42440 Primary PT primary AC Setup
Write Upper Limit:
Voltage Size (bits): 16 voltage
45000.000 Volts
Sign: U
Default: 480
Multiplier: Unit: Volts
Genset PT 1.000000000000 Lower Limit: 110.000 Generator set
Read/ Offset: 0
42441 Secondary Volts Upper Limit: 500 PT secondary AC Setup
Write
Voltage Size (bits): 16 Volts voltage
Sign: U Default: 120

Unit: Amp
Multiplier:
1.000000000000 Lower Limit: 5.000
Genset CT Amp Generator set
Read/ Offset: 0
42442 Primary CT primary AC Setup
Write Upper Limit:
Current Size (bits): 16 current
10000.000 Amp
Sign: U
Default: 100

A029X159 (Issue 31) 235 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 110.000
Utility PT Volts
Read/ Offset: 0 Utility PT
42445 Primary AC Setup
Write Upper Limit: primary voltage
Voltage Size (bits): 16
45000.000 Volts
Sign: U
Default: 480
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 110.000
Utility PT Volts Utility PT
Read/ Offset: 0
42446 Secondary secondary AC Setup
Write Upper Limit: 500.000
Voltage Size (bits): 16 voltage
Volts
Sign: U
Default: 120
Unit: Amps
Multiplier:
1.000000000000 Lower Limit: 5.000
Utility CT Amps
Read/ Offset: 0 Utility primary
42447 Primary AC Setup
Write Upper Limit: 10000.00 current
Current Size (bits): 16
Amps
Sign: U
Default: 100

Multiplier: Unit: kW Generator set


Load Add Shed 1.000000000000 Lower Limit: 0.000 kW kW capacity that
Required Read/ Offset: 0 must be online Load Add Shed
42449 Upper Limit:
Online Write to start timed Control
Capacity Size (bits): 16 32000.000 kW load add; 0
Sign: S Default: 0 disables this
Multiplier: Unit: kW Sets how much
Load Demand 1.000000000000 Lower Limit: 0.000 kW capacity must
Minimum Read/ Offset: 0 Load Demand
42450 Upper Limit: always be online
Online Write Control
Size (bits): 16 32767.000 kW regardless of
Capacity
Sign: S Default: 0 what the load is

Unit: seconds Sets generator


Multiplier:
0.100000000000 Lower Limit: 0.000 restart delay
Load Demand Read/ seconds time to avoid Load Demand
42451 Offset: 0
Restart Delay Write Upper Limit: 25.000 nuisance Control
Size (bits): 8 restarts due to
seconds
Sign: U load transients
Default: 1
Unit: Amps
Multiplier:
1.000000000000 Lower Limit: 1.000
Utility Available Read/ Amps
42452 Offset: 0 barograph AC Setup
Current Write Upper Limit:
Size (bits): 16
32000.000 Amps
Sign: U
Default: 1000
Multiplier: Unit: kW Use to set how
1.000000000000 Lower Limit: 1.000 kW kW = 100%
Total Utility Read/ Offset: 0
42453 Upper Limit: 32000.00 utility kW -- AC Setup
Capacity Write
Size (bits): 16 kW Used by
Sign: S Default: 1000 barograph

Copyright © 2023 Cummins Inc. 236 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Unit: VDC
Multiplier:
0.010000000000 Lower Limit: 28.000
24 V High VDC Sets 24V high
Read/ Offset: 0 Battery Voltage
42455 Battery Voltage battery voltage
Write Upper Limit: 34.000 Protection
Threshold Size (bits): 16 fault threshold
VDC
Sign: U
Default: 32
Unit: VDC
Multiplier:
0.010000000000 Lower Limit: 22.000
24 V Low VDC Sets 24V low
Read/ Offset: 0 Battery Voltage
42456 Battery Voltage battery voltage
Write Upper Limit: 26.000 Protection
Threshold Size (bits): 16 fault threshold
VDC
Sign: U
Default: 24
Unit: VDC
Multiplier:
0.010000000000 Lower Limit: 14.000
12 V High VDC Sets 12V high
Read/ Offset: 0 Battery Voltage
42457 Battery Voltage battery voltage
Write Upper Limit: 17.000 Protection
Threshold Size (bits): 16 fault threshold
VDC
Sign: U
Default: 16
Unit: VDC
Multiplier: Lower Limit: 11.000
12 V Low 0.010000000000 VDC Sets 12V low
Read/ Offset: 0 Battery Voltage
42458 Battery Voltage Upper Limit: 13.000 battery voltage
Write Protection
Threshold Size (bits): 16 VDC fault threshold
Sign: U Default: 12

Multiplier:
Unit: second
High Battery 1.000000000000
Read/ Lower Limit: 2 second Sets high Battery Voltage
42459 Voltage Set Offset: 0 battery voltage
Write Upper Limit: 60 second set time Protection
time Size (bits): 8
Default: 60
Sign: U
Multiplier:
Unit: second
Low Battery 1.000000000000
Read/ Lower Limit: 2 second Sets low battery Battery Voltage
42460 Voltage Set Offset: 0
Write Upper Limit: 60 second voltage set time Protection
Time Size (bits): 8
Default: 60
Sign: U

Multiplier: Unit: kW Sets the online


Genset Online 1.000000000000 Lower Limit: 0.000 kW kW threshold at
Capacity Read/ Offset: 0 which generator
42462 Upper Limit: PTC Sensors
Sensor Write set bus is
Threshold Size (bits): 16 32000.000 kW available for
Sign: S Default: 0 loading
Multiplier:
Unit: Bitmapped state
1.000000000000
Fault Status Read Lower Limit: of utility and Fault and Event
42500 Offset: 0
BitMap 1 Only Upper Limit: other faults - 32 Info
Size (bits): 32 bits
Default:
Sign: U

A029X159 (Issue 31) 237 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Multiplier:
Unit: Bitmapped state
1.000000000000
Fault Status Read Lower Limit: of generator set Fault and Event
42502 Offset: 0
BitMap 2 Only Upper Limit: and other faults Info
Size (bits): 32 - 32 bits
Default:
Sign: U
Multiplier:
Unit:
1.000000000000 Bitmapped state
Event Status Read Lower Limit: Fault and Event
42505 Offset: 0 of events - 32
BitMap 1 Only Upper Limit: Info
Size (bits): 32 bits
Default:
Sign: U

Multiplier: Bitmapped word


Unit: with status of
Genset 1.000000000000
Read Lower Limit: generator set AC Interrupt
42506 Metering Fault Offset: 0
Only Upper Limit: AC metering out Service
Status Size (bits): 16
Default: of range
Sign: U conditions
Multiplier: Bitmapped word
Unit:
1.000000000000 with status of
Utility Metering Read Lower Limit: AC Interrupt
42507 Offset: 0 utility AC
Fault Status Only Upper Limit: Service
Size (bits): 16 metering out of
Default: range conditions
Sign: U
Unit: Hours
Multiplier:
0.000277778 Lower Limit: 0.000
Gen1 Online Read Hours Total online time System
42704 Offset: 0
Time Only Upper Limit: for Gen1 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
0.000277778 Lower Limit: 0.000
Gen2 Online Read Hours Total online time System
42706 Offset: 0
Time Only Upper Limit: for Gen2 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
0.000277778 Lower Limit: 0.000
Gen3 Online Read Hours Total online time System
42708 Offset: 0
Time Only Upper Limit: for Gen3 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
0.000277778 Lower Limit: 0.000
Gen4 Online Read Hours Total online time System
42710 Offset: 0
Time Only Upper Limit: for Gen4 Information
Size (bits): 32
1193046.000 Hours
Sign: U
Default: 0

Copyright © 2023 Cummins Inc. 238 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function

Multiplier: Indicates how


Unit: many of the
Total Number 1.000000000000
Read Lower Limit: defined Gen1 System
42717 of Gensets Offset: 0
Only Upper Limit: thru Gen4 Information
Online Size (bits): 8
Default: generator sets
Sign: U are online

Multiplier: Difference
Unit: kW between online
Total Spare 1.000000000000
Read Lower Limit: capacity (4 System
42718 Online Offset: 0
Only Upper Limit: generator sets) Information
Capacity Size (bits): 16
Default: and Genset Bus
Sign: S Total kW

Multiplier: Indicates kW
Unit: kW threshold for
Next Gen 1.000000000000
Read Lower Limit: gen bus at Load Demand
42719 Restart Offset: 0
Only Upper Limit: which the next Control
Threshold Size (bits): 16
Default: generator set
Sign: S will restart
Indicates kW
Multiplier: threshold for
Unit: kW
Next Gen 1.000000000000 gen bus at
Read Lower Limit: Load Demand
42720 Shutdown Offset: 0 which the next
Only Upper Limit: Control
Threshold Size (bits): 16 generator set
Default: will load demand
Sign: S
stop

Multiplier: Calculated kW
Unit: kW overload
Genset Bus 1.000000000000
Read Lower Limit: threshold based System
42727 kW Overload Offset: 0
Only Upper Limit: on online Information
Threshold Size (bits): 16
Default: capacity and %
Sign: S setting
Multiplier:
Unit:
Modbus Bus 1.000000000000
Read Lower Limit: Modbus bus
42732 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
Multiplier:
Unit:
1.000000000000
Modbus CRC Read Lower Limit: Modbus CRC
42733 Offset: 0 Communications
Error Count Only Upper Limit: error count
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit:
Modbus 1.000000000000
Read Lower Limit: Modbus
42734 Exception Offset: 0 Communications
Only Upper Limit: exception count
Count Size (bits): 16
Default:
Sign: U

A029X159 (Issue 31) 239 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr System Name Access Specifications Description Function


Multiplier:
Unit:
Modbus No 1.000000000000
Read Lower Limit: Modbus no
42735 Response Offset: 0 Communications
Only Upper Limit: response count
Count Size (bits): 16
Default:
Sign: U
Multiplier:
Unit:
Modbus Slave 1.000000000000
Read Lower Limit: Modbus slave
42736 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
Multiplier: Unit: year
1.000000000000 Lower Limit: .000 year Use to set or
Read/ Offset: 0
42739 Clock Year Upper Limit: 99.000 read current Real Time Clock
Write
Size (bits): 8 year year
Sign: U Default:
Unit: month
Multiplier:
1.000000000000 Lower Limit: 1.000
month Use to set or
Read/ Offset: 0
42740 Clock Month read current Real Time Clock
Write Upper Limit: 12.000
Size (bits): 8 month
month
Sign: U
Default:
Unit: date
Multiplier:
1.000000000000 Lower Limit: 1.000
date Use to set or
Read/ Offset: 0
42741 Clock Date read current Real Time Clock
Write Upper Limit: 31.000
Size (bits): 8 date
date
Sign: U
Default:
Multiplier: Unit: hour
1.000000000000 Lower Limit: .000 hour Use to set or
Read/ Offset: 0
42742 Clock Hour Upper Limit: 23.000 read current Real Time Clock
Write
Size (bits): 8 hour hour
Sign: U Default:
Unit: minute
Multiplier:
1.000000000000 Lower Limit: .000
minute Use to set or
Read/ Offset: 0
42743 Clock Minute read current Real Time Clock
Write Upper Limit: 59.000
Size (bits): 8 minute
minute
Sign: U
Default:
Unit: seconds
Multiplier:
1.000000000000 Lower Limit: .000
seconds Use to set or
Read/ Offset: 0
42744 Clock Second read current Real Time Clock
Write Upper Limit: 59.000
Size (bits): 8 seconds
seconds
Sign: U
Default:

Copyright © 2023 Cummins Inc. 240 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr System Name Access Specifications Description Function


Multiplier:
Unit: seconds Countdown
0.100000000000
Read Lower Limit: timer value for PTC Operating
42746 Start Timer Offset: 0
Only Upper Limit: generator set Mode
Size (bits): 16 start timer
Default:
Sign: U
Multiplier:
Unit: seconds Countdown
.100000000000
Read Lower Limit: timer value for PTC Operating
42747 Stop Timer Offset: 0
Only Upper Limit: generator set Mode
Size (bits): 16 stop timer
Default:
Sign: U
Multiplier:
Unit: VDC Battery voltage
Low Battery 0.010000000000
Read Lower Limit: with respect to Battery Voltage
42748 Voltage Offset: 0
Only Upper Limit: the set low Protection
Threshold Size (bits): 16
Default: battery threshold
Sign: U
Multiplier:
Unit: VDC Battery voltage
High Battery 0.010000000000
Read Lower Limit: with respect to Battery Voltage
42749 Voltage Offset: 0
Only Upper Limit: set high battery Protection
Threshold Size (bits): 16
Default: threshold
Sign: U

6.1.2 DMC 1000 Modbus Enumerated Data


NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

A029X159 (Issue 31) 241 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. System Name Access Specifications Description Function


Save
configuration
parameters or
adjustments to
non-volatile
memory.
0: Do Nothing Perform Save
Save Read / Size (bits): 8 Controller
42004 1: Save Trims Trims after all
Adjustments Write Number of Fields: 2 Information
Default: Do Nothing configurations
have been
updated. Do
not save trims
unless a
change has
occurred.
0: Time Delay Start
1: Time Delay Stop Indicates state
Genset Run Size (bits): 8
Read of the PTC Operating
42011 Sequence 2: Stop
Only Number of Fields: 4 generator set Mode
State 3: Run run sequence
Default:
0: Unavailable Energization
Genset Bus Read Size (bits): 8 1: Dead status of the
42017 PTC Sensors
Status Only Number of Fields: 3 2: Live generator set
Default: bus

0: Unavailable
Size (bits): 8 1: Dead Energization
Utility Bus Read
42117 status of the PTC Sensors
Status Only Number of Fields: 3 2: Live utility bus
Default:
0: Not Available
Size (bits): 8 1: Not Unloaded Indicates utility
Utility Unload Read Master Load
42208 unloaded
Status Only Number of Fields: 3 2: Unloaded Control
status
Default:
0: Not Available Indicates
Genset Unload Read Size (bits): 8 1: Not Unloaded generator set Master Load
42209
Status Only Number of Fields: 3 2: Unloaded unloaded Control
Default: status

Copyright © 2023 Cummins Inc. 242 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. System Name Access Specifications Description Function


0: Not Available
1: TD Start
2: TD Stop
3: TD Programmed
Transition
4: TD Transfer
5: TD Retransfer
6: Synchronizing
7: Sync Check OK Indicates what
Size (bits): 8 8: Inhibit
Read / state the System
42210 System State Number of Fields:
Write 9: Unassigned control is Information
18 currently in
10: Ramp Unload
11: Ramp Load
12: Manual
13: Utility Failure
14: Test
15: Standby
16: Factory Test
17: Extended Parallel
Default: Not Available
0: Manual
Size (bits): 8 1: Normal Indicates the
Number of Fields: 6 2: Normal Override current PTC
PTC Operating Read operating PTC Operating
42211 3: Test
Mode Only mode. Mode
4: Utility Fail Read/Write in
5: Extended Parallel Comp mode
Default:
Indicates
0: Not Available availability of
Genset Size (bits): 8 1: Available generator set
Read
42216 Availability for loading as Availability
Only Number of Fields: 3 2: Unknown
Status determined by
Default: generator set
sensors
Indicates
0: Not Available availability of
Utility Size (bits): 8 1: Available
Read utility for
42217 Availability Availability
Only Number of Fields: 3 2: Unknown loading as
Status
Default: determined by
utility sensors
Size (bits): 8
0: Open
Number of Fields: 3 Generator set
Gen CB Read 1: Closed
42218 breaker Breaker Control
Position Status Only 2: Not Available position
Default:

A029X159 (Issue 31) 243 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. System Name Access Specifications Description Function


Size (bits): 8
Number of Fields: 3 0: Open
Util CB Read 1: Closed Utility breaker
42219 Breaker Control
Position Status Only 2: Not Available position
Default:

0: Not Enabled
Indicates the
1: No Source connected
Connected state of the
Read Size (bits): 8 PTC State
42224 PTC State 2: Utility Connected power transfer
Only Number of Fields: 5 Machine
3: Genset Connected control
4: Paralleled Read/Write in
Comp.
Default:
Size (bits):8 Indicates
Number of Fields: 2 0: Not Allowed whether any
Sync Check Read Master Sync
42225 1: Allowed sync check
Close Allowed Only Control
Default: conditions for
have been met

Size (bits): 8
0: Synchronizer Off Indicates state
Synchronizer Read Number of Fields: 2 Master Sync
42227 1: Synchronizer On of the
Status Only Control
Default: synchronizer

Size (bits): 8 Faults have


Number of Fields: 2 0: Inactive occurred which
System Read prevent normal System
42228 1: Active
Lockout Status Only system Information
Default: operation;
reset faults
Size (bits): 8
0: Open
Number of Fields: 3 Indicates
Breaker 1 Read 1: Closed Load Add Shed
42229 position status
Position Only 2: Not Available Control
of breaker 1
Default: Not Available

0: Open
Size (bits): 8 Indicates
Breaker 2 Read 1: Closed Load Add Shed
42230 Number of Fields: 3 position status
Position Only 2: Not Available Control
of breaker 2
Default: Not Available
0: Open
Size (bits): 8 1: Closed Indicates
Breaker 3 Read Load Add Shed
42231 position status
Position Only Number of Fields: 3 2: Not Available Control
of breaker 3
Default: Not Available

Copyright © 2023 Cummins Inc. 244 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. System Name Access Specifications Description Function


Size (bits): 8 0: Open
Number of Fields: 3 1: Closed Indicates
Breaker 4 Read Load Add Shed
42232 2: Not Available position status
Position Only Control
Default: Not Available of breaker 4

0: Open
Size (bits): 8 1: Closed Indicates
Breaker 5 Read Load Add Shed
42233 position status
Position Only Number of Fields: 3 2: Not Available Control
of breaker 5
Default: Not Available
0: Open
Size (bits): 8 1: Closed Indicates
Breaker 6 Read Load Add Shed
42234 position status
Position Only Number of Fields: 3 2: Not Available Control
of breaker 6
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 1 Trip Read Load Add Shed
42235 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 1
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 2 Trip Read Load Add Shed
42236 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 2
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 3 Trip Read Load Add Shed
42237 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 3
Default: Not Available
Size (bits): 8
0: Not Available
Number of Fields: 3 Indicates trip
Breaker 4 Trip Read 1: Normal Load Add Shed
42238 status of
Status Only 2: Tripped Control
breaker 4
Default: Not Available

0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 5 Trip Read Load Add Shed
42239 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 5
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 6 Trip Read Load Add Shed
42240 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 6
Default: Not Available

A029X159 (Issue 31) 245 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. System Name Access Specifications Description Function


0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42241 ATS 1 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 1
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42242 ATS 2 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 3
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42243 ATS 3 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 3
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits):8 Load Add Shed
42244 ATS 4 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 4
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42245 ATS 5 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 5
4: Paralleled
Default: Not Available
0: Not Available
1: No Source
Connected Indicates
Read Size (bits): 8 Load Add Shed
42246 ATS 6 Position 2: Source 1 Connected position status
Only Number of Fields: 5 Control
3: Source 2 Connected of ATS 6
4: Paralleled
Default: Not Available

Copyright © 2023 Cummins Inc. 246 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. System Name Access Specifications Description Function


0: Failed
PCCNet Size (bits): 8 1: Good Indicates
Read
42248 Communication status of Communications
Only Number of Fields: 3 2: Wait
s Status PCCNet
Default: Wait
Indicates the
Expansion 0: Disabled status of the
Board Read Size (bits): 8 SID to
42249 1: Enabled Communications
Communication Only Number of Fields: 2 expansion
s Default: Disabled board
connection
0: Do Nothing Indicates
Add Level 1 Read Size (bits): 8 Load Add Shed
42252 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 1

0: Do Nothing Indicates
Add Level 2 Read Size (bits):8 Load Add Shed
42253 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 2

0: Do Nothing Indicates
Add Level 3 Read Size (bits): 8 Load Add Shed
42254 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 3

0: Do Nothing Indicates
Add Level 4 Read Size (bits): 8 Load Add Shed
42255 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 4

0: Do Nothing Indicates
Add Level 5 Read Size (bits): 8 Load Add Shed
42256 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 5

0: Do Nothing Indicates
Add Level 6 Read Size (bits): 8 Load Add Shed
42257 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 6

0: Do Nothing Indicates
Shed Level 1 Read / Size (bits): 8 Load Add Shed
42258 1: Shed Level status of shed
Command Write Number of Fields: 2 Control
Default: Do Nothing level 1

0: Do Nothing Indicates
Shed Level 2 Read Size (bits): 8 Load Add Shed
42259 1: Shed Level status of shed
Command Only Number of Fields: 2 Control
Default: Do Nothing level 2

0: Do Nothing Indicates
Shed Level 3 Read / Size (bits): 8 Load Add Shed
42260 1: Shed Level status of shed
Command Write Number of Fields: 2 Control
Default: Do Nothing level 3

0: Do Nothing Indicates
Shed Level 4 Read Size (bits): 8 Load Add Shed
42261 1: Shed Level status of shed
Command Only Number of Fields: 2 Control
Default: Do Nothing level 4

A029X159 (Issue 31) 247 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Shed Level 5 Read Size (bits): 8 Load Add Shed
42262 1: Shed Level status of shed
Command Only Number of Fields: 2 Control
Default: Do Nothing level 5

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42263 Level 1 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 1

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42264 Level 2 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 2

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42265 Level 3 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 3

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42266 Level 4 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 4

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42267 Level 5 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 5

0: Do Nothing Operator input


Manual add Size (bits): 8
Read / to add loads Load Add Shed
42268 Level 6 1: Add Level
Write Number of Fields: 2 assigned to Control
Command Default: Do Nothing level 6

0: Do Nothing Operator input


Manual Shed Read / Size (bits): 8 to shed loads Load Add Shed
42269 1: Shed Level
Level 1 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 1

0: Do Nothing Operator input


Manual Shed Read / Size (bits): 8 to shed loads Load Add Shed
42270 1: Shed Level
Level 2 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 2

0: Do Nothing Operator input


Manual Shed Read / Size (bits): 8 to shed loads Load Add Shed
42271 1: Shed Level
Level 3 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 3

0: Do Nothing Operator input


Manual Shed Read / Size (bits): 8 to shed loads Load Add Shed
42272 1: Shed Level
Level 4 Write Number of Fields:2 assigned to Control
Default: Do Nothing level 4

0: Do Nothing Operator input


Manual Shed Read / Size (bits): 8 to shed loads Load Add Shed
42273 1: Shed Level
Level 5 Write Number of Fields: 2 assigned to Control
Default: Do Nothing level 5

Copyright © 2023 Cummins Inc. 248 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. System Name Access Specifications Description Function

0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 1 Load Add Shed
42274 Level 1 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 2 Load Add Shed
42275 Level 2 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 3 Load Add Shed
42276 Level 3 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 4 Load Add Shed
42277 Level 4 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 5 Load Add Shed
42278 Level 5 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates add
Add Load 1 Read Size (bits): 8 Load Add Shed
42279 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 1

0: Do Nothing Indicates add


Add Load 2 Read Size (bits): 8 Load Add Shed
42280 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 2

0: Do Nothing Indicates add


Add Load 3 Read Size (bits): 8 Load Add Shed
42281 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 3

0: Do Nothing Indicates add


Add Load 4 Read Size (bits): 8 Load Add Shed
42282 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 4

0: Do Nothing Indicates add


Add Load 5 Read Size (bits): 8 Load Add Shed
42283 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 5

0: Do Nothing Indicates add


Add Load 6 Read Size (bits): 8 Load Add Shed
42284 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 6

0: Do Nothing Indicates shed


Shed Load 1 Read Size (bits): 8 Load Add Shed
42285 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 1

0: Do Nothing Indicates shed


Shed Load 2 Read Size (bits): 8 Load Add Shed
42286 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 2

A029X159 (Issue 31) 249 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates shed
Shed Load 3 Read Size (bits): 8 Load Add Shed
42287 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 3

0: Do Nothing Indicates shed


Shed Load 4 Read Size (bits): 8 Load Add Shed
42288 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 4

0: Do Nothing Indicates shed


Shed Load 5 Read Size (bits): 8 Load Add Shed
42289 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 5

0: Do Nothing Indicates shed


Shed Load 6 Read Size (bits): 8 Load Add Shed
42290 1: Shed Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 6

0: Manual
1: Normal Indicates the
PTC Genset 2: Normal Override current
Read Size (bits):8 PTC Operating
42296 Operating 3: Test operating
Only Number of Fields: 6 Mode
Mode 4: Utility Fail mode of the
5: Extended Parallel generator sets
Default:
0: Manual
1: Normal Indicates the
PTC Transfer 2: Normal Override current
Read Size (bits):8 PTC Operating
42297 Pair Operating 3: Test operating
Only Number of Fields: 6 Mode
Mode 4: Utility Fail mode of the
5: Extended Parallel transfer pair
Default:

0: Open Transition Indicates the


1: Hard Closed transition type
Size (bits): 8 Transition currently
PTC Operating Read PTC Operating
42298 applicable to
Transition Type Only Number of Fields: 3 2: Soft Closed Mode
the PTC
Transition function
Default: operation
0: Master Synchronize
Only
1: Isolated Bus w/out Main setting:
GM Sets system
System Read / Size (bits): 8 2: Isolated Bus w/GM topology; Application
42300
Topology Write Number of Fields: 6 3: Common Bus control must be Configuration
4: Transfer Pair in manual to
5: Component Mode set
Default: Master
Synchronize Only

Copyright © 2023 Cummins Inc. 250 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. System Name Access Specifications Description Function


0: Open Transition
1: Hard Closed
Transition Sets the type
Read / Size (bits):8 of transition Application
42301 Transition Type 2: Soft Closed
Write Number of Fields: 3 that will be Configuration
Transition used
Default: Open
Transition

0: Disabled Use to enable


Extended Read / Size (bits): 8 extended Application
42302 1: Enabled
Parallel Enable Write Number of Fields: 2 paralleling Configuration
Default: Disabled operation
Size (bits): 8
0: None
Number of Fields: 3
Load Demand Read / 1: Fixed Sequence Sets load Load Demand
42303
Type Write 2: Run Hours demand type Control
Default: None

0: Manual
Priority Control Read / Size (bits): 8 Sets priority
42304 1: Automatic Priority Control
Method Write Number of Fields: 2 control method
Default: Manual

0: Disabled Use to enable


Test With Load Read / Size (bits): 8 or disable load Application
42326 1: Enabled
Enable Write Number of Fields: 2 transfer during Configuration
Default: Disabled a test
selects where
0: Internal the generator
Genset Bus Size (bits):8
Read / set kW setpoint Master Load
42328 kW Setpoint 1: Analog Input
Write Number of Fields: 2 will come from Control
Source Default: Internal for extended
paralleling
Selects where
the generator
Genset Bus 0: Internal set kVAR
Read / Size (bits):8 Master Load
42329 kVAR Setpoint 1: Analog Input setpoint will
Write Number of Fields: 2 Control
Source Default: Internal come from
extended
paralleling
Selects where
0: Internal the utility kW
Utility Bus kW Size (bits):8
Read / setpoint will Master Load
42335 Setpoint 1: Analog Input
Write Number of Fields: 2 come from for Control
Source Default: Internal extended
paralleling
Selects where
0: Internal the utility kVAR
Utility Bus Size (bits):8
Read / setpoint will Master Load
42336 kVAR Setpoint 1: Analog Input
Write Number of Fields: 2 come from Control
Source Default: Internal extended
paralleling

A029X159 (Issue 31) 251 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. System Name Access Specifications Description Function

0: Inactive Use to
Clear Fault Read / Size (bits):8 completely Fault and Event
42342 1: Active
History Table Write Number of Fields: 2 clear the fault Info
Default: Inactive history table
Use to
completely
Clear Size (bits):8 0: Inactive clear the
Read / Fault and Event
42343 Occurrence Number of Fields: 2 1: Active counts in faults
Write Info
Table Default: Inactive and events
occurrence
tables
Use to
0: Do Nothing permanently
Genset Reset Size (bits):8
Read / clear all
42344 All Energy 1: Clear Counters Energy
Write Number of Fields: 2 generator set
Meters Default: Do Nothing energy meter
values

Size (bits):8 Use to


0: Do Nothing permanently
Utility Reset All Read / Number of Fields: 2
42345 1: Clear Counters clear all utility Energy
Energy Meters Write
Default: Do Nothing energy meter
values
0: Genset % Level
(Open Loop)
1: Genset Bus kW Sets how and
(Closed Loop) where the kW
Extended
Size (bits):8 will be
Paralleling kW Read / 2: Genset Bus kW Master Load
42346 controlled for
Load Control Write Number of Fields: 4 w/Utility (open Loop) Control
extended
Type 3: Utility Bus kW parallel
(Closed Loop) operation
Default: Genset Bus %
Level (Open Loop)
0: Genset Controllers
1: Genset Bus % Level
(Open Loop)
2: Genset Bus Power
Factor Sets how and
3: Genset Bus kVAR where the
Extended (Closed Loop)
Size (bits):8 kVAR will be
Paralleling Read / Master Load
42347 4: Genset Bus Power controlled for
kVAR Load Write Number of Fields: 7 Control
Factor (Closed Loop) extended
Control Type
5: Utility Bus kVAR parallel
(Closed Loop) operation
6:Utility Bus Power
Factor(Closed Loop)
Default: Genset
Controllers

Copyright © 2023 Cummins Inc. 252 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. System Name Access Specifications Description Function

0: Disabled Enable if want


Fail To Sync Read / Size (bits):8 synchronizing Master Sync
42349 1: Enabled
Lockout Enable Write Number of Fields: 2 to stop if fail to Control
Default: Disabled sync occurs
Fail to Sync Use to enable
Open 0: Disabled or disable an
Read / Size (bits):16 PTC State
42350 Transition 1: Enabled open transition
Write Number of Fields: 2 Machine
Retransfer Default: Disabled retransfer upon
Enable a fail to sync
In manual
Size (bits):8 mode, can be
0: Closed Requested
Number of Fields: 3 used to
Gen CB Read / 1: No Command
42352 semi–manually Breaker Control
Manual Control Write 2: Open Command control the
Default: No Command generator set
breaker
In manual
0: Closed Requested mode, can be
Util CB Manual Read / Size (bits):8 1: No Command used to
42353 Breaker Control
Control Write Number of Fields: 3 2: Open Command semi–manually
Default: No Command control the
utility breaker
0: Normal Use to invert
Synchronizer Read / Size (bits):8 Master Sync
42357 1: Invert synchronizer
Polarity Write Number of Fields: 2 Control
Default: Normal polarity

0: Phase Match Sets the


Synchronize Read / Size (bits):8 Master Sync
42358 1: Slip Frequency synchronizing
Method Write Number of Fields: 2 Control
Default: Phase Match method

Allows protocol
0: PCCNet CT the
Port Protocol Read / Size (bits): 8 PCCNet port to
42359 1: MON Communications
Selection Write Number of Fields: 2 be changed to
Default: PCCNet MON for
troubleshooting

0: Disabled Use to enable


System Size (bits): 8
Read / or disable the System
42360 Scheduler 1: Enabled
Write Number of Fields: 2 system Scheduler
Enable Default: Disabled scheduler

0: Disabled Use to enable


Load Add Shed Read / Size (bits): 8 or disable the Load Add Shed
42361 1: Enabled
Enable Write Number of Fields: 2 load add shed Control
Default: Disabled feature
Use to enable
Open
0: Disabled or disable the
Transition Size (bits): 8
Read / shedding of Load Add Shed
42362 Retransfer 1: Enabled
Write Number of Fields: 2 loads during Control
Load Shed Default: Disabled open transition
Enable
retransfer

A029X159 (Issue 31) 253 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. System Name Access Specifications Description Function


Indicates
Auto/Manual Size (bits): 8 0: Auto automatic or
Read / Load Add Shed
42363 Load Add Number of Fields: 2 1: Manual manual load
Write Control
Restore Mode Default: Auto add restore
operation
Indicates type
0: None of load
Load 1 Device
Read / Size (bits): 8 1: Breaker connection to Load Add Shed
42367 Type
Write Number of Fields: 3 2: ATS load 1 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 2 Device Read / Size (bits): 8 1: Breaker connection to Load Add Shed
42368
Type Write Number of Fields: 3 2: ATS load 2 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 3 Device Read / Size (bits): 8 1: Breaker connection to Load Add Shed
42369
Type Write Number of Fields: 3 2: ATS load 3 add Control
Default: None shed control
and status I/O

Size (bits): 8 Indicates type


0: None of load
Number of Fields: 3
Load 4 Device Read / 1: Breaker connection to Load Add Shed
42370
Type Write 2: ATS load 4 add Control
Default: None shed control
and status I/O
Indicates type
Size (bits): 8 0: None of load
Load 5 Device Read / Number of Fields: 3 1: Breaker connection to Load Add Shed
42371
Type Write 2: ATS load 5 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 6 Device Read / Size (bits):8 1: Breaker connected to Load Add Shed
42372
Type Write Number of Fields: 3 2: ATS load 6 add Control
Default: None shed control
and status I/O
0: Both kW and Use to choose
Frequency method for
Genset Bus Size (bits):8 1: kW Only
Read / determining System
42385 Overload
Write Number of Fields: 3 2: Frequency Only generator bus Information
Method
Default: Both kW and overload
Frequency condition

Copyright © 2023 Cummins Inc. 254 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. System Name Access Specifications Description Function

0: Disabled Use to enable


Load Demand Read / Size (bits):8 or disable the Load Demand
42390 1: Enabled
Enable Write Number of Fields: 2 load demand Control
Default: Disabled feature
0: Gen1
1: Gen2 Sets GenA for
Load Demand Read / Size (bits): 8 Load Demand
42391 2: Gen3 fixed sequence
GenA Write Number of Fields: 4 Control
3: Gen4 load demand
Default: Gen1
0: Gen1
1: Gen2 Sets GenB for
Load Demand Read / Size (bits):8 Load Demand
42392 2: Gen3 fixed sequence
GenB Write Number of Fields: 4 Control
3: Gen4 load demand
Default: Gen2
0: Gen1
1: Gen2 Sets GenC for
Load Demand Read / Size (bits):8 Load Demand
42393 2: Gen3 fixed sequence
GenC Write Number of Fields: 4 Control
3: Gen4 load demand
Default: Gen3
0: Gen1 Sets GenD
1: Gen2 (first to stop)
Load Demand Read / Size (bits):8 Load Demand
42394 2: Gen3 for fixed
GenD Write Number of Fields: 4 Control
3: Gen4 sequence load
Default: Gen4 demand

0: L1–L2–L3 Defines what


System Phase Read / Size (bits):8 the system System
42413 1:L1–L3–L2
Rotation Write Number of Fields: 2 phase rotation Information
Default: L1–L2–L3 sequence is

0: Disable Use to enable


Scheduler Size (bits):8
Read / or disable the System
42419 Program x 1: Enable
Write Number of Fields: 2 selected Scheduler
Enable Default: Disable program

A029X159 (Issue 31) 255 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. System Name Access Specifications Description Function


0: Once
1: Every Week
2: Every 2 Weeks
3: Every 3 Weeks
4: Every 4 Weeks
5: Every 5 Weeks
Size (bits):8 6: First Week of Month Use to adjust
Scheduler
Read / 7: Second Week of repeat interval System
42420 Program x Number of Fields:
Write Month for the selected Scheduler
Repeat Interval 11 program
8: Third Week of
month
9: Forth Week of the
Month
10: Last Week of the
Month
Default: Once
0: No Load Use to adjust
Scheduler Size (bits): 8 1: With Load
Read / run mode for System
42421 Program x Run
Write Number of Fields: 3 2: Extended Parallel the selected Scheduler
Mode
Default: No Load program

0: Sunday
1: Monday
2: Tuesday Use to adjust
Scheduler Size (bits): 8 3: Wednesday start day of
Read / System
42422 Program x week for the
Write Number of Fields: 7 4: Thursday Scheduler
Start Day selected
5: Friday program
6: Saturday
Default: Sunday

0: Disable Use to enable


Scheduler Size (bits): 8
Read / or disable the System
42428 Exception x 1: Enable
Write Number of Fields: 2 selected Scheduler
Enable Default: Disable exception
Use to adjust
Scheduler 0: Once Only the repeat
Read / Size (bits): 8 System
42429 Exception x 1: Every Year setting of the
Write Number of Fields: 2 Scheduler
Repeat Default: Once Only selected
exception

0: Disabled Enables the


Daylight Size (bits): 8
Read / daylight
42437 Saving Time 1: Enabled Real Time Clock
Write Number of Fields: 2 savings time
Enable Default: Disabled feature
Use to force a
Load Demand 0: Do Nothing
Size (bits): 8 refresh of the
Refresh Read / Load Demand
42438 1: Refresh Sequence active load
Sequence Write Number of Fields: 2 Control
Default: Do Nothing demand
Command
sequence

Copyright © 2023 Cummins Inc. 256 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. System Name Access Specifications Description Function

Genset 0: Wye Delta or Wye


Read / Size (bits):8
42439 Connection 1: Delta for generator AC Setup
Write Number of Fields: 2
Type Default: Wye set connection

Genset CT 0: 1 Amp Generator set


Read / Size (bits): 8
42443 Secondary 1: 5 Amp CT secondary AC Setup
Write Number of Fields: 2
Current Default: 5 Amp current

Utility 0: Wye Delta or Wye


Read / Size (bits): 8
42444 Connection 1: Delta for utility AC Setup
Write Number of Fields: 2
Type Default: Wye connection

Utility CT 0: 1 Amp Utility CT


Read / Size (bits): 8
42448 Secondary 1: 5 Amp secondary AC Setup
Write Number of Fields: 2
Current Default: 5 Amp current

0: 12V DC voltage
Nominal Read / Size (bits): 8 Battery Voltage
42454 1: 24V provided to the
Battery Voltage Write Number of Fields: 2 Protection
Default: 24V control

Use to enable
Genset Online 0: Disable or disable the
Read / Size (bits): 8
42461 Capacity 1: Enable generator set PTC Sensors
Write Number of Fields: 2
Sensor Enable Default: Disable online capacity
sensor
Indicates that
0: Inactive the generator
Gen Bus Base Read Size (bits):8 System
42472 1: Active bus is on base
Load Status Only Number of Fields: 2 Information
Default: load extended
paralleling
Indicates that
0: Inactive the utility bus is
Util Bus Peak Read Size (bits): 8 System
42473 1: Active on peak shave
Shave Status Only Number of Fields: 2 Information
Default: extended
paralleling

0: Stop State of
Extended Size (bits): 8
Read / extended
42600 Parallel Start 1: Start Discrete Inputs
Write Number of Fields: 2 parallel start
Vol Default: Stop volatile input

0: inactive State of
Synchronizer Read / Size (bits): 8 synchronizer
42601 1: Active Discrete Inputs
Enable Vol Write Number of Fields: 2 enable volatile
Default: inactive input
0: inactive State of utility
Utility Source Read / Size (bits): 8
42602 1: Active source failure Discrete Inputs
Failure Vol Write Number of Fields: 2
Default: inactive volatile input

0: No Inhibit State of
Transfer Inhibit Read / Size (bits):16
42603 1: Inhibit transfer inhibit Discrete Inputs
Vol Write Number of Fields: 2
Default: No Inhibit volatile input

A029X159 (Issue 31) 257 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. System Name Access Specifications Description Function

0: No Inhibit State of
Retransfer Read / Size (bits):8 retransfer
42604 1: Inhibit Discrete Inputs
Inhibit Vol Write Number of Fields: 2 inhibit volatile
Default: No Inhibit input

0: No Inhibit State of
Gen CB Inhibit Read / Size (bits): 8 generator CB
42605 1: Inhibit Discrete Inputs
Vol Write Number of Fields: 2 inhibit volatile
Default: No Inhibit input
0: No Inhibit State of utility
Util CB Inhibit Read / Size (bits): 8
42606 1: Inhibit CB inhibit Discrete Inputs
Vol Write Number of Fields: 2
Default: No Inhibit volatile input

0: Auto State of
Auto/Manual Read / Size (bits): 8
42607 1: Manual auto/manual Discrete Inputs
Vol Write Number of Fields: 2
Default: Auto volatile input

Size (bits): 8 0: Stop State of test


Read /
42608 Test Start Vol Number of Fields: 2 1: Start start volatile Discrete Inputs
Write
Default: Stop input

0: Not Reset State of fault


Read / Size (bits): 8
42609 Fault Reset Vol 1: Reset reset volatile Discrete Inputs
Write Number of Fields: 2
Default: Not Reset input

0: No Override State of
Read / Size (bits): 8
42610 Override Vol 1: Override override Discrete Inputs
Write Number of Fields: 2
Default: No Override volatile input

0: Start State of
Extended Size (bits): 8
Read extended
42611 Parallel Start 1: Stop Discrete Inputs
Only Number of Fields: 2 parallel start
Sw Default: input
0: Inactive State of
Synchronizer Read Size (bits): 8
42612 1: Active synchronizer Discrete Inputs
Enable Sw Only Number of Fields: 2
Default: enable input

0: Inactive State of utility


Utility Source Read Size (bits): 8
42613 1: Active source failure Discrete Inputs
Failure Sw Only Number of Fields: 2
Default: input

0: No Inhibit State of
Transfer Inhibit Read Size (bits): 8
42614 1: Inhibit transfer inhibit Discrete Inputs
Sw Only Number of Fields: 2
Default: input

0: No Inhibit State of
Retransfer Read Size (bits): 8
42615 1: Inhibit retransfer Discrete Inputs
Inhibit Sw Only Number of Fields: 2
Default: inhibit input

0: No Inhibit Sate of
Gen CB Inhibit Read Size (bits): 8
42616 1: Inhibit generator CB Discrete Inputs
Sw Only Number of Fields: 2
Default: inhibit input

Copyright © 2023 Cummins Inc. 258 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. System Name Access Specifications Description Function


0: No Inhibit
Util CB Inhibit Read Size (bits): 8 State of utility
42617 1: Inhibit Discrete Inputs
Sw Only Number of Fields: 2 CB inhibit input
Default:
0: Auto State of
Auto/Manual Read Size (bits): 8
42618 1: Manual auto/manual Discrete Inputs
Sw Only Number of Fields: 2
Default: input

0: Stop
Read Size (bits): 8 State of test
42619 Test Start Sw 1: Start Discrete Inputs
Only Number of Fields: 2 start input
Default:
0: No Reset
Read Size (bits): 8 State of fault
42620 Fault Reset Sw 1: Reset Discrete Inputs
Only Number of Fields: 2 reset input
Default:
0: No Override
Read Size (bits): 8 State of
42621 Override Sw 1: Override Discrete Inputs
Only Number of Fields: 2 override input
Default:
0: No Inhibit Indicates state
Read Size (bits): 8
42622 Master Inhibit 1: Inhibit of Master Priority Control
Only Number of Fields: 2
Default: priority inhibit

0: Inactive State of
Gen CB Read Size (bits): 8
42623 1: Active generator CB Discrete Inputs
Tripped Sw Only Number of Fields: 2
Default: tripped input

0: Inactive State of
Gen CB Read / Size (bits): 8 generator CB
42624 1: Active Discrete Inputs
Tripped Vol Write Number of Fields: 2 tripped volatile
Default: Inactive input
0: Inactive State of utility
Util CB Tripped Read Size (bits): 8
42625 1: Active CB tripped Discrete Inputs
Sw Only Number of Fields: 2
Default: input

Size (bits): 8 0: Inactive State of utility


Util Cb Tripped Read /
42626 Number of Fields: 4 1: Active CB tripped Discrete Inputs
Vol Write
Default: Inactive volatile input

0: L1–L2–L3
Genset Phase Read Size (bits): 8 Generator set
42627 1: L1–L3–L2 Phase
Rotation Only Number of Fields: 2 phase rotation
Default:
Size (bits): 8 0: L1–L2–L3
Utility Phase Read Utility phase
42628 Number of Fields: 2 1: L1–L3–L2 Phase
Rotation Only rotation
Default:
Size (bits): 8 0: Breaker Open State of Gen1
Gen1 CB Read
42629 Number of Fields: 2 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

A029X159 (Issue 31) 259 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. System Name Access Specifications Description Function


0: Breaker Open State of Gen1
Gen1 CB Read / Size (bits): 8
42630 1: Breaker Closed CB position Discrete Inputs
Position Vol Write Number of Fields: 2
Default: Open volatile input

0: Breaker Open State of Gen2


Gen2 CB Read Size (bits): 8
42631 1: Breaker Closed CB position Discrete Inputs
Position Sw Only Number of Fields: 2
Default: input

0: Breaker Open State of Gen2


Gen2 CB Read / Size (bits): 8
42632 1: Breaker Closed CB position Discrete Inputs
Position Vol Write Number of Fields: 2
Default: Open volatile input

0: Breaker Open State of Gen3


Gen3 CB Read Size (bits):16
42633 1: Breaker Closed CB position Discrete Inputs
Position Sw Only Number of Fields: 2
Default: input

0: Breaker Open State of Gen3


Gen3 CB Read / Size (bits): 8
42634 1: Breaker Closed CB position Discrete Inputs
Position Vol Write Number of Fields: 2
Default: Open volatile input

0: Breaker Open State of Gen4


Gen4 CB Read Size (bits): 8
42635 1: Breaker Closed CB position Discrete Inputs
Position Sw Only Number of Fields: 2
Default: input

0: Breaker Open State of Gen4


Gen4 CB Read / Size (bits): 8
42636 1: Breaker Closed CB position Discrete Inputs
Position Vol Write Number of Fields: 2
Default: Open volatile input

0: No Inhibit Use to
Network Read / Size (bits): 8
42637 1: Inhibit manually inhibit Priority Control
Master Inhibit Write Number of Fields: 2
Default: No Inhibit the module

0: Gen Does Not Exist


1: Offline For load
Gen1 Size (bits): 8 2: Waiting for Gen
Read demand use - Load Demand
42700 Availability
Only Number of Fields: 5 3: Online Indicates Control
State
4: Failed status of Gen1
Default:
0: Gen Does Not Exist
1: Offline For load
Gen2 Size (bits): 8 2: Waiting for Gen
Read demand use - Load Demand
42701 Availability
Only Number of Fields: 5 3: Online Indicates Control
State
4: Failed status of Gen2
Default:
0:Gen Does Not Exist
1: Offline For load
Gen3 Size (bits): 8 2: Waiting for Gen
Read demand use - Load Demand
42702 Availability
Only Number of Fields: 5 3: Online Indicates Control
State
4: Failed status of Gen3
Default:

Copyright © 2023 Cummins Inc. 260 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. System Name Access Specifications Description Function


0:Gen Does Not Exist
1: Offline For load
Gen4 Size (bits): 8
Read 2: Waiting for Gen demand use - Load Demand
42703 Availability Number of Fields: 5
Only 3: Online Indicates Control
State
4: Failed status of Gen4
Default:
Size (bits): 8 0: Gen1 Indicates which
Number of Fields: 4 1: Gen2 generator set is
Read Load Demand
42712 GenA 2: Gen3 currently GenA
Only Control
3: Gen4 for load
Default: demand

Size (bits): 8 0: Gen1 Indicates which


Number of Fields: 4 1: Gen2 generator set is
Read Load Demand
42713 GenB 1: Gen3 currently GenB
Only Control
1: Gen4 for load
Default: demand

0: Gen1 Indicates which


1: Gen2 generator set is
Read Size (bits): 8 Load Demand
42714 GenC 1: Gen3 currently GenC
Only Number of Fields: 4 Control
1: Gen4 for load
Default: demand

0: Gen1 Indicates which


1: Gen2 generator set is
Read Size (bits): 8 currently GenD Load Demand
42715 GenD 1: Gen3
Only Number of Fields: 4 (first to stop) Control
1: Gen4 for load
Default: demand
Size (bits): 8
0: Off Indicates
Number of Fields: 3
Load Demand Read 1: Initial Delay Timing operating state Load Demand
42716
State Only 2: Load Monitor of the load Control
Default: demand control

0: Gen1
Indicates which
Size (bits): 8 1: Gen2 generator set is
Next Gen To Read Number of Fields: 5 2: Gen3 next to be Load Demand
42721
Restart Only 3: Gen4 restarted if load Control
4: None conditions are
met
Default:
0: Gen1
Size (bits): 8 Indicates which
1: Gen2 generator set is
Number of Fields: 5
Next Gen To Read 2: Gen3 next to be Load Demand
42722
Shutdown Only 3: Gen4 stopped if load Control
4: None conditions are
met
Default:

A029X159 (Issue 31) 261 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. System Name Access Specifications Description Function


Size (bits): 8
Number of Fields: 2 0: Run Status of the
Load Demand
Read load demand
42723 Gen1 Driver 1: Load Demand Stop Discrete Outputs
Only Gen1 driver
Status Default: output

0: Run Status of the


Load Demand Size (bits): 8
Read load demand
42724 Gen2 Driver 1: Load Demand Stop Discrete Outputs
Only Number of Fields: 2 Gen2 driver
Status Default: output

0: Run Status of the


Load Demand Size (bits): 8
Read load demand
42725 Gen3 Driver 1: Load Demand Stop Discrete Outputs
Only Number of Fields: 2 Gen3 driver
Status Default: output
Size (bits): 8
Number of Fields: 2 0: Run Status of the
Load Demand
Read load demand
42726 Gen4 Driver 1: Load Demand Stop Discrete Outputs
Only Gen4 driver
Status Default: output

Size (bits): 8 Indicates


Genset Bus 0: No Overload whether
Read Number of Fields: 2 System
42728 kW Overload 1: Overload generator bus
Only Information
Status Default: is overloaded
based on kW

Size (bits): 8 Indicates


Genset Bus Number of Fields: 2 0: No Overload whether
Underfrequenc Read generator bus System
42729 1: Overload
y Overload Only is overloaded Information
Status Default: based on
frequency

Copyright © 2023 Cummins Inc. 262 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. System Name Access Specifications Description Function


0: None
1: Program 1
2: Program 2
3: Program 3
4: Program 4
5: Program 5
6: Program 6
Size (bits): 8 7: Program 7
Number of Fields: 8: Program 8 Indicates the
19 9: Program 9 currently active
Active Read System
42730 scheduler
Schedule Only 10: Program 10 Scheduler
program or
11: Program 11 exception
12: Program 12
13: Exception 1
14: Exception 2
15: Exception 3
16: Exception 4
17: Exception 5
18: Exception 6
Default:

0: Off Indicates
1: No Load current run
Scheduler Run Read Size (bits): 8 command System
42731 2: With Load
Command Only Number of Fields: 4 coming from Scheduler
3: Extended Parallel the scheduler
Default: function
0: Do Nothing Clears all the
Modbus Clear Read / Size (bits): 8
42737 1: Clear Counters Modbus Communications
Counters Write Number of Fields: 2
Default: Do Nothing counters

Size (bits): 8
0: Normal
Number of Fields: 3 Use to set
Read / 1: Set Clock
42738 Clock Mode clock and save Real Time Clock
Write 2: Save Clock setting
Default: Normal

0: Sunday
1: Monday
2: Tuesday
Size (bits): 8 3: Wednesday Indicates day
Read
42745 Clock Day of week for Real Time Clock
Only Number of Fields: 7 4: Thursday current date
5: Friday
6: Saturday
Default:

A029X159 (Issue 31) 263 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

6.1.3 DMC 1000 Modbus Bitmap Data


NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table, it is not implemented.

Addr. Bit# System Name Fault Code Event Name Response


42500 0 Fault Status 1455 Utility Main Warning
Bitmap 1 Breaker Position
Contact Warning
42500 1 Fault Status 2396 Utility Main Warning
Bitmap 1 Breaker Fail To
Close Warning
42500 2 Fault Status 2397 Utility Main Warning
Bitmap 1 Breaker Fail To
Open Warning
42500 3 Fault Status 1219 Utility Main Warning
Bitmap 1 Breaker Tripped
Warning
42500 4 Fault Status 1914 Utility Bus Phase Warning
Bitmap 1 Rotation Warning
42500 5 Fault Status 1912 Utility Bus Loss Warning
Bitmap 1 Of Phase
Warning
42500 6 Fault Status 2331 Utility Bus Warning
Bitmap 1 Undervoltage
Warning
42500 7 Fault Status 2358 Utility Bus Warning
Bitmap 1 Overvoltage
Warning
42500 8 Fault Status 1223 Utility Bus Warning
Bitmap 1 Frequency
Warning
42500 24 Fault Status 2648 Remote I/O Warning
Bitmap 1 Communication
Failure Warning
42500 25 Fault Status 1689 Real Time Clock Warning
Bitmap 1 Power Interrupt
Warning

Copyright © 2023 Cummins Inc. 264 A029X159 (Issue 31)


8-2023 6. DMC 1000

Addr. Bit# System Name Fault Code Event Name Response


42500 26 Fault Status 1335 AC Metering Out Warning
Bitmap 1 Of Range
Warning
42500 27 Fault Status 1999 Maximum Parallel Warning
Bitmap 1 Time Warning
42500 28 Fault Status 343 Hardware Failure Warning
Bitmap 1 Warning
42500 29 Fault Status 1456 Synchronizer Warning
Bitmap 1 Output Limit
Warning
42500 30 Fault Status 2416 Calibration Warning
Bitmap 1 Checksum
Warning
42500 31 Fault Status 353 EEPROM Write Warning
Bitmap 1 Error Warning
42502 0 Fault Status 1454 Genset Main Warning
Bitmap 2 Breaker Position
Contact Warning
42502 1 Fault Status 1452 Genset Main Warning
Bitmap 2 Breaker Fail To
Close Warning
42502 2 Fault Status 1453 Genset Main Warning
Bitmap 2 Breaker Tripped
Warning
42502 3 Fault Status 1328 Genset Bus Warning
Bitmap 2 Phase Rotation
Warning
42502 4 Fault Status 1915 Genset Bus Warning
Bitmap 2 Phase Rotation
Warning
42502 5 Fault Status 1913 Genset Bus Loss Warning
Bitmap 2 Of Phase
Warning
42502 6 Fault Status 1225 Genset Bus Warning
Bitmap 2 Undervoltage
Warning
42502 7 Fault Status 1224 Genset Bus Warning
Bitmap 2 Overvoltage
Warning
42502 8 Fault Status 1226 Genset Bus Warning
Bitmap 2 Frequency
Warning
42502 24 Fault Status 1541 Genset Failed To Warning
Bitmap 2 Come Online
Warning

A029X159 (Issue 31) 265 Copyright © 2023 Cummins Inc.


6. DMC 1000 8-2023

Addr. Bit# System Name Fault Code Event Name Response


42502 25 Fault Status 2647 Load Demand Warning
Bitmap 2 Setup Warning
42502 26 Fault Status 1444 Genset Bus Warning
Bitmap 2 Overload Warning
42502 27 Fault Status 1989 kW Load Control Warning
Bitmap 2 Output Limit
Warning
42502 28 Fault Status 1991 kVAR Load Warning
Bitmap 2 Control Output
Limit Warning
42502 29 Fault Status 1121 Fail To Warning
Bitmap 2 Disconnect
Warning
42502 30 Fault Status 1458 Synchronizer Warning
Bitmap 2 Phase Rotation
Mismatch
Warning
42502 31 Fault Status 1457 Fail To Warning
Bitmap 2 Synchronizer
Warning
42505 0 Event Status 1222 Not in Automatic Event
Bitmap 1 Event
42505 1 Event Status 1483 Common Warning Event
Bitmap 1 Event
42505 2 Event Status 2965 Genset Bus Event
Bitmap 1 Available Event
42505 3 Event Status 2328 Utility Bus Event
Bitmap 1 Available Event
42505 4 Event Status 2333 Genset Bus Event
Bitmap 1 Connected Event
42505 5 Event Status 2332 Utility Bus Event
Bitmap 1 Connected Event
42505 6 Event Status 2971 Test / Extended Event
Bitmap 1 Parallel Event
42505 7 Event Status 1916 Synchronized Event
Bitmap 1 Event
42505 8 Event Status 1534 Load Control Event
Bitmap 1 Output Event

Copyright © 2023 Cummins Inc. 266 A029X159 (Issue 31)


7 DMC 1500
7.1 DMC 1500 Communication Server 1
7.1.1 Modbus Address: 2 (Slave)
NOTICE
If an address or bit is not listed in this table, it is not implemented.

NOTICE
The external device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.

Modbus Address Bit # Alarm Event


40001 0 (LSB) Utility Main Breaker Position Contact Warning
40001 1 Utility Main Breaker Fail To Close Warning
40001 2 Utility Main Breaker Fail To Open Warning
40001 3 Utility Main Breaker Tripped Warning
40001 4 Utility Bus Phase Rotation Warning
40001 5 Utility Bus Loss of Phase Warning
40001 6 Utility Bus Undervoltage Warning
40001 7 Utility Bus Overvoltage Warning
40001 8 Utility Bus Frequency Warning
40001 9 Remote IO Comm Failure Warning
40001 10 Real Time Clock Power Interrupt Warning
40001 11 AC Metering Out Of Range Warning
40001 12 Maximum Parallel Time Warning
40001 13 Not Implemented
40001 14 Synchronizer Output Limit Warning
40001 15 (MSB) Calibration Checksum Warning MCM 3320

Modbus Address Bit # Alarm Event


40002 0 (LSB) EEPROM Write Error Warning MCM 3320
40002 1 Genset Main Breaker Position Contact Warning

A029X159 (Issue 31) 267 Copyright © 2023 Cummins Inc.


7. DMC 1500 8-2023

Modbus Address Bit # Alarm Event


40002 2 Genset Main Breaker Fail to Close Warning
40002 3 Genset Main Breaker Fail to Open Warning
40002 4 Genset Main Breaker Tripped Warning
40002 5 Genset Bus Phase Rotation Warning
40002 6 Genset Bus Loss of Phase Warning
40002 7 Genset Bus Undervoltage Warning
40002 8 Genset Bus Overvoltage Warning
40002 9 Genset Bus Frequency Warning
40002 10 Low Battery Voltage Warning MCM 3320
40002 11 High Battery Voltage Warning MCM 3320
40002 12 Genset Failed to Come Online Warning
40002 13 Load Demand Setup Warning
40002 14 Genset Bus Over Load Limit Warning
40002 15 (MSB) kW Load Control Output Limit Warning

Modbus Address Bit # Alarm Event


40003 0 (LSB) kVAR Load Control Output Limit Warning
40003 1 Fail to Disconnect Warning
40003 2 Synchronizer Phase Rotation Mismatch Warning
40003 3 Fail to Synchronize Warning
40003 4 Normal Operation Lockout
40003 5 Common Warning MCM 3320
40003 6 Common Server 1 to Network ATS Comm Failure
40003 7 Common Server 1 to MCM3320 Comm Failure
40003 8 Common Server 1 Battery Warning
40003 9 Common Server 1 Comm Server 2 Comm Failure
40003 10 Not Implemented
40003 11 Not Implemented
40003 12 Not Implemented
40003 13 Not Implemented
40003 14 Not Implemented
40003 15 (MSB) Not Implemented

Copyright © 2023 Cummins Inc. 268 A029X159 (Issue 31)


8-2023 7. DMC 1500

Modbus Address Bit # Alarm Event


40004 0 (LSB) Feeder Breaker 1 Trip
40004 1 Feeder Breaker 2 Trip
40004 2 Feeder Breaker 3 Trip
40004 3 Feeder Breaker 4 Trip
40004 4 Feeder Breaker 5 Trip
40004 5 Feeder Breaker 6 Trip
40004 6 Feeder Breaker 7 Trip
40004 7 Feeder Breaker 8 Trip
40004 8 Feeder Breaker 9 Trip
40004 9 Feeder Breaker 10 Trip
40004 10 Not Implemented
40004 11 Not Implemented
40004 12 Not Implemented
40004 13 Not Implemented
40004 14 Not Implemented
40004 15 (MSB) Not Implemented

NOTICE
40005 is not implemented.

Modbus Address Bit # Alarm Event


40006 0 (LSB) System in Auto-Opened Transition
40006 1 System in Auto-Hard Closed Transition
40006 2 System in Auto-Soft Closed Transition
40006 3 System Manual Mode Active
40006 4 System Automatic Mode Active
40006 5 Common Warning Event
40006 6 Genset Bus Available Event
40006 7 Utility Bus Available Event
40006 8 Genset Bus Connected Event
40006 9 Utility Bus Connected Event
40006 10 Synchronized Event
40006 11 Load Control Output Event

A029X159 (Issue 31) 269 Copyright © 2023 Cummins Inc.


7. DMC 1500 8-2023

Modbus Address Bit # Alarm Event


40006 12 Genset Source Unloaded Event
40006 13 Utility Source Unloaded Event
40006 14 Genset Bus Load Event
40006 15 (MSB) Utility Bus Peak Shave Event

Modbus Address Bit # Alarm Event


40007 0 (LSB) Extended Paralleling Enable
40007 1 Extended Paralleling Disable
40007 2 System in Extended Parallel
40007 3 System in Test with Load
40007 4 System in Test without Load
40007 5 System Test Off
40007 6 Load Demand Enable
40007 7 Load Demand Disable
40007 8 Extended Parallel Off
40007 9 Not Implemented
40007 10 Not Implemented
40007 11 Not Implemented
40007 12 Not Implemented
40007 13 Not Implemented
40007 14 Not Implemented
40007 15 (MSB) Not Implemented

7.1.2 Generator Set Bus Data


Generator Bus Data MB Address Data Type Multiplier Units
Generator Set L1N Volts 40009 16U 1 Volts
Generator Set L2N Volts 40010 16U 1 Volts
Generator Set L3N Volts 40011 16U 1 Volts
Generator Set LN Average Volt 40012 16U 1 Volts
Generator set L1L2 Volts 40013 16U 1 Volts
Generator Set L2L3 Volts 40014 16U 1 Volts
Generator Set L3L1 Volts 40015 16U 1 Volts
Generator Set LL Average Volts 40016 16U 1 Volts

Copyright © 2023 Cummins Inc. 270 A029X159 (Issue 31)


8-2023 7. DMC 1500

Generator Bus Data MB Address Data Type Multiplier Units


Generator Set L1 Current 40017 16U 1 Amps
Generator Set L2 Current 40018 16U 1 Amps
Generator Set L3 Current 40019 16U 1 Amps
Generator Set Average Current 40020 16U 1 Amps
Generator Set L1 kW 40021 16S 1 kW
Generator Set L2 kW 40022 16S 1 kW
Generator Set L3 kW 40023 6S 1 kW
Generator Set Total kW 40024 16S 1 kW
Generator Set L1 kVAR 40025 16S 1 kVAR
Generator Set L2 kVAR 40026 16S 1 kVAR
Generator Set L3 kVAR 40027 16S 1 kVAR
Generator Set Total kVAR 40028 16S 1 kVAR
Generator Set Total Power Factor 40029 16S 0.01
Generator Set L1 kVA 40030 16U 1 kVA
Generator Set L2 kVA 40031 16U 1 kVA
Generator Set L3 kVA 40032 16U 1 kVA
Generator Set Total kVA 40033 16U 1 kVA
MB Generator Set Frequency 40034 16U 0.1 Hz
Generator Set Total Negative kWh 40035 32U 1 kWh
40036
Generator Set Total Positive kWh 40037 32U 1 kWh
40038
Generator Set Total Net kWh 40039 32S 1 kWh
40040
Generator Set Total Negative kVARh 40041 32U 1 kVARh
40042
Generator Set Total Positive kVARh 40043 32U 1 kVARh
40044
Generator Set Total Net kVARh 40045 32S 1 kVARh
40046
Generator Set Total kVAh 40047 32U 1 kVAh
40048
Generator Set Available Current 40049 16U 1 Amps
Generator Set L1 Current Percent 40050 16U 0.1 %

A029X159 (Issue 31) 271 Copyright © 2023 Cummins Inc.


7. DMC 1500 8-2023

Generator Bus Data MB Address Data Type Multiplier Units


Generator Set L2 Current Percent 40051 16U 0.1 %
Generator Set L3 Current Percent 40052 16U 0.1 %
Generator Set Total kW Percent 40053 16U 0.1 %
Generator Set Frequency Percent 40054 16S 0.1 %
Generator Set L1L2 Voltage Percent 40055 16U 0.1 %
Generator Set L2L3 Voltage Percent 40056 16U 0.1 %
Generator Set L3L1 Voltage Percent 40057 16U 0.1 %

7.1.3 Utility Bus Data


Utility Bus Data MB Address Data Type Multiplier Units
Utility L1N Voltage 40059 16U 1 Volts
Utility L2N Voltage 40060 16U 1 Volts
Utility L3N Voltage 40061 16U 1 Volts
Utility LN Average Voltage 40062 16U 1 Volts
Utility L1L2 Voltage 40063 16U 1 Volts
Utility L2L3 Voltage 40064 16U 1 Volts
Utility L3L1 Voltage 40065 16U 1 Volts
Utility LL Average Voltage 40066 16U 1 Volts
Utility L1 Current 40067 16U 1 Amps
Utility L2 Current 40068 16U 1 Amps
Utility L3 Current 40069 16U 1 Amps
Utility Average Current 40070 16U 1 Amps
Utility L1 kW 40071 16S 1 kW
Utility L2 kW 40072 16S 1 kW
Utility L3 kW 40073 16S 1 kW
Utility Total kW 40074 16S 1 kW
Utility L1 kVAR 40075 16S 1 kVAR
Utility L2 kVAR 40076 16S 1 kVAR
Utility L3 kVAR 40077 16S 1 kVAR
Utility Total kVAR 40078 16S 1 kVAR
Utility Total Power Factor 40079 16S 0.01
Utility L1 kVA 40080 16U 1 kVA
Utility L2 kVA 40081 16U 1 kVA
Utility L3 kVA 40082 16U 1 kVA

Copyright © 2023 Cummins Inc. 272 A029X159 (Issue 31)


8-2023 7. DMC 1500

Utility Bus Data MB Address Data Type Multiplier Units


Utility Total kVA 40083 16U 1 kVA
MB Utility Frequency 40084 16U 0.1 Hz
Utility Total Negative kWh 40085 32U 1 kWh
40086
Utility Total Positive kWh 40087 32U 1 kWh
40088
Utility Total Net kWh 40089 32S 1 kWh
40090
Utility Total Negative kVARh 40091 32U 1 kVARh
40092
Utility Total Positive kVARh 40093 32U 1 kVARh
40094
Utility Total Net kVARh 40095 32S 1 kVARh
40096
Utility Total kVAh 40097 32U 1 kVAh
40098
System Total kW 40099 16S 1 kW
System Total kVAR 40100 16S 0.01 kVAR
System Total Power Factor 40101 16S 1
System Total kVA 40102 16U 1 KVA

7.1.4 ATS 1-5 DATA


ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
Device Type 40257 40317 40377 40437 40497
Mode (See Table 14 on page 275) 40258 40318 40378 40438 40498
State (See Table 13 on page 275) 40259 40319 40379 40439 40499
Fault Code 40260 40320 40380 40440 40500
Fault Type (See Table 15 on page
40261 40321 40381 40441 40501
276)
Percent Amps 40262 40322 40382 40442 40502 0.5 %
Total kW 40263 40323 40383 40443 40503
NFPA 110 (See Table 5 on page
40264 40324 40384 40444 40504
12)
NFPA Extended(See Table 6 on
40265 40325 40385 40445 40505
page 12)

A029X159 (Issue 31) 273 Copyright © 2023 Cummins Inc.


7. DMC 1500 8-2023

ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
Frequency Load 40266 40326 40386 40446 40506 0.1 Hz
Total pf Load 40267 40327 40387 40447 40507 0.00005 pf
Total kVA Load 40268 40328 40388 40448 40508 kVA
Total kW Load 40269 40329 40389 40449 40509 kW
Total kVAR Load 40270 40330 40390 40450 40510 kVAR
Volts ab Load 40271 40331 40391 40451 40511 Volts
Volts bc Load 40272 40332 40392 40452 40512 Volts
Volts ca Load 40273 40333 40393 40453 40513 Volts
Volts a Load 40274 40334 40394 40454 40514 Volts
Volts b Load 40275 40335 40395 40455 40515 Volt
Volts c Load 40276 40336 40396 40456 40516 Volts
Amps a Load 40277 40337 40397 40457 40517 Amps
Amps b Load 40278 40338 40398 40458 40518 Amps
Amps c Load 40279 40339 40399 40459 40519 Amps
Percent Amps a Load 40280 40340 40400 40460 40520 0.5 %
Percent Amps b Load 40281 40341 40401 40461 40521 0.5 %
Percent Amps c Load 40282 40342 40402 40462 40522 0.5 %
Frequency SRC1 40283 40343 40403 40463 40523 0.1 Hz
Total pf SRC1 40284 40344 40404 40464 40524 0.00005 PF
Total kVA SRC1 40285 40345 40405 40465 40525
Total kW SRC1 40286 40346 40406 40466 40526
Total kVAR SRC1 40287 40347 40407 40467 40527
Volts ab SRC1 40288 40348 40408 40468 40528
Volts bc SRC1 40289 40349 40409 40469 40529
Volts ca SRC1 40290 40350 40410 40470 40530
Volts a SRC1 40291 40351 40411 40471 40531
Volts b SRC1 40292 40352 40412 40472 40532 Volts
Volts c SRC1 40293 40353 40413 40473 40533
Amps a SCR1 40294 40354 40414 40474 40534 Amps
Amps b SCR1 40295 40355 40415 40475 40535
Amps c SRC1 40296 40356 40416 40476 40536
Percent Amps a SCR1 40297 40357 40417 40477 40537 0.5 %
Percent Amps b SCR1 40298 40358 40418 40478 40538 0.5 %
Percent Amps c SCR1 40299 40359 40419 40479 40539 0.5 %

Copyright © 2023 Cummins Inc. 274 A029X159 (Issue 31)


8-2023 7. DMC 1500

ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
Frequency SRC2 40300 40360 40420 40480 40540 0.1 Hz
Total pf SRC2 40301 40361 40421 40481 40541 0.00005 pf
Total kVA SRC2 40302 40362 40422 40482 40542 kVA
Total kW SRC2 40303 40363 40423 40483 40543 kW
Total kVAR SRC2 40304 40364 40424 40484 40544 kVAR
Volts ab SRC2 40305 40365 40425 40485 40545 Volts
Volts bc SRC2 40306 40366 40426 40486 40546 Volts
Volts ca SRC2 40307 40367 40427 40487 40547 Volts
Volts a SRC2 40308 40368 40428 40488 40548 Volts
Volts b SRC2 40309 40369 40429 40489 40549 Volts
Volts c SRC2 40310 40370 40430 40490 40550 Volts
Amps a SRC2 40311 40371 40431 40491 40551 Amps
Amps b SRC2 40312 40372 40432 40492 40552 Amps
Amps c SRC2 40313 40373 40433 40493 40553 Amps
Percent Amps a SRC2 40314 40374 40434 40494 40554 0.5 %
Percent Amps b SRC2 40315 40375 40435 40495 40555 0.5 %
Percent Amps c SRC2 40316 40376 40436 40496 40556 0.5 %

7.1.5 Word Data


Reference Tables ATS 1-5 and 6-10.

TABLE 13.

Digital State
0 Neutral
1 Source 1 Connected
2 Source 2 Connected
3 Source 1 and 2 Connected

TABLE 14.

Digital Mode
0 Test
1 Utility / Genset
2 Utility / Utility
3 Genset / Genset

A029X159 (Issue 31) 275 Copyright © 2023 Cummins Inc.


7. DMC 1500 8-2023

TABLE 15.

Digital Fault Type


0 No Faults
1 Warning

7.1.6 ATS 6-10 DATA


ATS Raw Data ATS 6 ATS 7 ATS 8 ATS 9 ATS 10 Multiplier Units
Device Type 40557 40617 40677 40737 40797
Mode (See Table 14 on page 275) 40558 40618 40678 40738 40798
State (See Table 13 on page 275) 40559 40619 40679 40739 40799
Fault Code 40560 40620 40680 40740 40800
Fault Type (See Table 15 on page
40561 40621 40681 40741 40801
276)
Percent Amps 40562 40622 40682 40742 40802 0.5 %
Total kW 40563 40623 40683 40743 40803
NFPA 110 (See Table 3 on page
40564 40624 40684 40744 40804
11)
NFPA Extended (See Table 4 on
40565 40625 40685 40745 40805
page 11)
Frequency Load 40566 40626 40686 40746 40806 0.1 Hz
Total pf Load 40567 40627 40687 40747 40807 0.00005 PF
Total kVA Load 40568 40628 40688 40748 40808 kVA
Total kW Load 40569 40629 40689 40749 40809 kW
Total kVAR Load 40570 40630 40690 40750 40810 kVAR
Volts ab Load 40571 40631 40691 40751 40811 Volts
Volts bc Load 40572 40632 40692 40752 40812 Volts
Volts ca Load 40573 40633 40693 40753 40813 Volts
Volts a Load 40574 40634 40694 40754 40814 Volts
Volts b Load 40575 40635 40695 40755 40815 Volts
Volts c Load 40576 40636 40696 40756 40816 Volts
Amps a Load 40577 40637 40697 40757 40817 Amps
Amps b Load 40578 40638 40698 40758 40818 Amps
Amps c Load 40579 40639 40699 40759 40819 Amps
Percent Amps a Load 40580 40640 40700 40760 40820 0.5 %
Percent Amps b Load 40581 40641 40701 40761 40821 0.5 %
Percent Amps c Load 40582 40642 40702 40762 40822 0.5 %

Copyright © 2023 Cummins Inc. 276 A029X159 (Issue 31)


8-2023 7. DMC 1500

ATS Raw Data ATS 6 ATS 7 ATS 8 ATS 9 ATS 10 Multiplier Units
Frequency SRC1 40583 40643 40703 40763 40823 0.1 Hz
Total pf SRC1 40584 40644 40704 40764 40824 0.00005 PF
Total kVA SRC1 40585 40645 40705 40765 40825 kVA
Total kW SRC1 40586 40646 40706 40766 40826 kW
Total kVAR SRC1 40587 40647 40707 40767 40827 kVAR
Volts bc SRC1 40588 40648 40708 40868 40828 Volts
Volts bc SRC1 40589 40649 40709 40869 40829 Volts
Volts ca SRC1 40590 40650 40710 40870 40830 Volts
Volts a SRC1 40591 40651 40711 40871 40831 Volts
Volts b SRC1 40592 40652 40712 40872 40832 Volts
Volts c SRC1 40593 40653 40713 40873 40833 Volts
Amps a SCR1 40594 40654 40714 40874 40834 Amps
Amps b SCR1 40595 40655 40715 40875 40835 Amps
Amps c SRC1 40596 40656 40716 40876 40836 Amps
Percent Amps a SCR1 40597 40657 40717 40777 40837 0.5 %
Percent Amps b SCR1 40598 40658 40718 40778 40838 0.5 %
Percent Amps c SCR1 40599 40659 40719 40779 40839 0.5 %
Frequency SRC2 40600 40660 40720 40780 40840 0.1 Hz
Total pf SRC2 40601 40661 40721 40781 40841 0.00005 pf
Total KVA SRC2 40602 40662 40722 40782 40842 kVA
Total kW SRC2 40603 40663 40723 40783 40843 kW
Total KVAR SRC2 40604 40664 40724 40784 40844 kVAR
Volts ab SRC2 40605 40665 40725 40785 40845 Volts
Volts bc SRC2 40606 40666 40726 40786 40846 Volts
Volts ca SRC2 40607 40667 40727 40787 40847 Volts
Volts a SRC2 40608 40668 40728 40788 40848 Volts
Volts b SRC2 40609 40669 40729 40789 40849 Volts
Volts c SRC2 40610 40670 40730 40790 40850 Volts
Amps a SRC2 40611 40671 40731 40791 40851 Amps
Amps b SRC2 40612 40672 40732 40792 40852 Amps
Amps c SRC2 40613 40673 40733 40793 40853 Amps
Percent Amps a SRC2 40614 40674 40734 40794 40854 0.5 %
Percent Amps b SRC2 40615 40675 40735 40795 40855 0.5 %
Percent Amps c SRC2 40616 40676 40736 40796 40856 0.5 %

A029X159 (Issue 31) 277 Copyright © 2023 Cummins Inc.


7. DMC 1500 8-2023

7.2 DMC 1500 Communication Server 2


7.2.1 Modbus Address: 1 (Slave)
NOTICE
If an address or bit is not listed in this table, it is not implemented.

NOTICE
The external device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.

Modbus Address Bit # Alarm Event


40001 0 (LSB) Neutral Earthing 1 Fail to Open Warning
40001 1 Neutral Earthing 2 Fail to Open Warning
40001 2 Neutral Earthing 3 Fail to Open Warning
40001 3 Neutral Earthing 4 Fail to Open Warning
40001 4 Neutral Earthing 5 Fail to Open Warning
40001 5 Neutral Earthing 6 Fail to Open Warning
40001 6 Neutral Earthing 7 Fail to Open Warning
40001 7 Neutral Earthing 8 Fail to Open Warning
40001 8 Neutral Earthing 1 Fail to Closed Warning
40001 9 Neutral Earthing 2 Fail to Closed Warning
40001 10 Neutral Earthing 3 Fail to Closed Warning
40001 11 Neutral Earthing 4 Fail to Closed Warning
40001 12 Neutral Earthing 5 Fail to Closed Warning
40001 13 Neutral Earthing 6 Fail to Closed Warning
40001 14 Neutral Earthing 7 Fail to Closed Warning
40001 15 (MSB) Neutral Earthing 8 Fail to Closed Warning

Modbus Address Bit # Alarm Event


40002 0 (LSB) Neutral Earthing 1 Tripped Warning
40002 1 Neutral Earthing 2 Tripped Warning
40002 2 Neutral Earthing 3 Tripped Warning
40002 3 Neutral Earthing 4 Tripped Warning
40002 4 Neutral Earthing 5 Tripped Warning

Copyright © 2023 Cummins Inc. 278 A029X159 (Issue 31)


8-2023 7. DMC 1500

Modbus Address Bit # Alarm Event


40002 5 Neutral Earthing 6 Tripped Warning
40002 6 Neutral Earthing 7 Tripped Warning
40002 7 Neutral Earthing 8 Tripped Warning
40002 8 Undergrounded Bus Warning
40002 9 Undergrounded Bus Failure - System Shutdown
40002 10 Multiple NECs Connected
40002 11 Multiple System Grounds Connected
40002 12 Not Implemented
40002 13 Not Implemented
40002 14 Not Implemented
40002 15 (MSB) Not Implemented

Modbus Address Bit # Alarm Event


40003 0 (LSB) Station Battery Power Supply Fault
40003 1 UPS Fault
40003 2 On Station Battery Warning
40003 3 System Manual Mode Active
40003 4 Utility Failure
40003 5 Utility Out of Limits for Extended Parallel
40003 6 Common Server 2 Battery Warning
40003 7 System Emergency Stop
40003 8 Hardware Failure Warning MCM 3320
40003 9 Not Implemented
40003 10 Not Implemented
40003 11 Not Implemented
40003 12 Not Implemented
40003 13 Not Implemented
40003 14 Not Implemented
40003 15 (MSB) Not Implemented

Modbus Address Bit # Alarm Event


40004 0 (LSB) Illegal Genset Node Address Assignment
40004 1 Not Implemented

A029X159 (Issue 31) 279 Copyright © 2023 Cummins Inc.


7. DMC 1500 8-2023

Modbus Address Bit # Alarm Event


40004 2 Not Implemented
40004 3 Comm Server 2 to Comm Server 1 Comm Failure
40004 4 Manufacturing Test Mode Active
40004 5 Not Implemented
40004 6 Not Implemented
40004 7 Not Implemented
40004 8 Comm Server 2 to Genset 1 Comm Failure
40004 9 Comm Server 2 to Genset 2 Comm Failure
40004 10 Comm Server 2 to Genset 3 Comm Failure
40004 11 Comm Server 2 to Genset 4 Comm Failure
40004 12 Comm Server 2 to Genset 5 Comm Failure
40004 13 Comm Server 2 to Genset 6 Comm Failure
40004 14 Comm Server 2 to Genset 7 Comm Failure
40004 15 (MSB) Comm Server 2 to Genset 8 Comm Failure

NOTICE
40005 is unused.

Modbus Address Bit # Alarm Event


40006 0 (LSB) Gen 1 Breaker Closed
40006 1 Gen 2 Breaker Closed
40006 2 Gen 3 Breaker Closed
40006 3 Gen 4 Breaker Closed
40006 4 Gen 5 Breaker Closed
40006 5 Gen 6 Breaker Closed
40006 6 Gen 7 Breaker Closed
40006 7 Gen 8 Breaker Closed
40006 8 Gen 1 Breaker Open
40006 9 Gen 2 Breaker Open
40006 10 Gen 3 Breaker Open
40006 11 Gen 4 Breaker Open
40006 12 Gen 5 Breaker Open
40006 13 Gen 6 Breaker Open

Copyright © 2023 Cummins Inc. 280 A029X159 (Issue 31)


8-2023 7. DMC 1500

Modbus Address Bit # Alarm Event


40006 14 Gen 7 Breaker Open
40006 15 (MSB) Gen 8 Breaker Open

Modbus Address Bit # Alarm Event


40007 0 (LSB) Gen 1 Running
40007 1 Gen 2 Running
40007 2 Gen 3 Running
40007 3 Gen 4 Running
40007 4 Gen 5 Running
40007 5 Gen 6 Running
40007 6 Gen 7 Running
40007 7 Gen 8 Running
40007 8 Gen 1 Fault
40007 9 Gen 2 Fault
40007 10 Gen 3 Fault
40007 11 Gen 4 Fault
40007 12 Gen 5 Fault
40007 13 Gen 6 Fault
40007 14 Gen 7 Fault
40007 15 (MSB) Gen 8 Fault

Modbus Address Bit # Alarm Event


40008 0 (LSB) Gen 1 Shut Down in Load Demand
40008 1 Gen 2 Shut Down in Load Demand
40008 2 Gen 3 Shut Down in Load Demand
40008 3 Gen 4 Shut Down in Load Demand
40008 4 Gen 5 Shut Down in Load Demand
40008 5 Gen 6 Shut Down in Load Demand
40008 6 Gen 7 Shut Down in Load Demand
40008 7 Gen 8 Shut Down in Load Demand
40008 8 Gen Start Signal On MCM 3320
40008 9 Gen Start Signal Off MCM 3320
40008 10 Gen Main Breaker Closed

A029X159 (Issue 31) 281 Copyright © 2023 Cummins Inc.


7. DMC 1500 8-2023

Modbus Address Bit # Alarm Event


40008 11 Gen Main Breaker Opened
40008 12 Utility Main Breaker Closed
40008 13 Utility Main Breaker Opened
40008 14 Utility Failure
40008 15 (MSB) Return to Utility

Modbus Address Bit # Alarm Event


40009 0 (LSB) Remote Commands Enable
40009 1 Remote Commands Disable
40009 2 Remote Test On
40009 3 Remote Test Off
40009 4 Remote Extended Parallel On
40009 5 Remote Extended Parallel Off
40009 6 Remote Transfer Inhibit On
40009 7 Remote Transfer Inhibit Off
40009 8 Remote Retransfer Inhibit On
40009 9 Remote Retransfer Inhibit Off
40009 10 Auto Genset Start Inhibit in Manual Mode Enable
40009 11 Auto Genset Start Inhibit in Manual Mode Disable
40009 12 Not Implemented
40009 13 Not Implemented
40009 14 Not Implemented
40009 15 (MSB) Not Implemented

7.2.2 Generator Raw Data Gen 1-5


Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Device Type 40011 40066 40121 40176 40231
Control Switch (See Table 22 on
40012 40067 40122 40177 40232
page 286)
State (See Table 16 on page 284) 40013 40068 40123 40178 40233
Fault Code 40014 40069 40124 40179 40234
Fault Type (SeeTable 21 on page
40015 40070 40125 40180 40235
285)
Percent kW Standby 40016 40071 40126 40181 40236 0.5 %

Copyright © 2023 Cummins Inc. 282 A029X159 (Issue 31)


8-2023 7. DMC 1500

Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Total kW 40017 40072 40127 40182 40237
NFPA 110 (See Table 3 on page
40018 40073 40128 40183 40238
11)
NFPA Extended (See Table 4 on
40019 40074 40129 40184 40239
page 11)
Frequency 40020 40075 40130 40185 40240 0.1 Hz
Total pf 40021 40076 40131 40186 40241 0.00005 pf
Total kVA 40022 40077 40132 40187 40242 kVA
Total kW 40023 40078 40133 40188 40243 kW
Total kVAR 40024 40079 40134 40189 40244 kVAR
Volts ab 40025 40080 40135 40190 40245 Volts
Volts bc 40026 40081 40136 40191 40246 Volts
Volts ca 40027 40082 40137 40192 40247 Volts
Volts a 40028 40083 40138 40193 40248 Volts
Volts b 40029 40084 40139 40194 40249 Volt
Volts c 40030 40085 40140 40195 40250 Volts
Amps a 40031 40086 40141 40196 40251 Amps
Amps b 40032 40087 40142 40197 40252 Amps
Amps c 40033 40088 40143 40198 40253 Amps
Percent Amps a 40034 40089 40144 40199 40254 0.5 %
Percent Amps b 40035 40090 40145 40200 40255 0.5 %
Percent Amps c 40036 40091 40146 40201 40256 0.5 %
Battery Voltage 40037 40092 40147 40202 40257 0.1 Volts
Oil Pressure 40038 40093 40148 40203 40258 0.1 kPa
Oil Temp 40039 40094 40149 40204 40259 0.1 Deg K
Coolant Temp 40040 40095 40150 40205 40260 0.1 Deg K
Fuel Rate 40041 40096 40151 40206 40261 0.001 GPH
Engine RPM 40042 40097 40152 40207 40262 RPM
Engine Starts 40043 40098 40153 40208 40263 Starts
Engine Runtime High 40044 40099 40154 40209 40264
Engine Runtime Low 40045 40100 40155 40210 40265 0.1 Sec
Total kWH High 40046 40101 40156 40211 40266
Total kWH Low 40047 40102 40157 40212 40267 KWH
Total Fuel High 40048 40103 40158 40213 40268
Total Fuel Low 40049 40104 40159 40214 40269 0.01 GAL

A029X159 (Issue 31) 283 Copyright © 2023 Cummins Inc.


7. DMC 1500 8-2023

Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Bus Frequency 40050 40105 40160 40215 40270 0.1 Hz
Bus Volts ab 40051 40106 40161 40216 40271 Volts
Bus Volts bc 40052 40107 40162 40217 40272 Volts
Bus Volts ca 40053 40108 40163 40218 40273 Volts
Bus Volts a 40054 40109 40164 40219 40274 Volts
Bus Volts b 40055 40110 40165 40220 40275 Volts
Bus Volts c 40056 40111 40166 40221 40276 Volts
Customer Faults 40057 40112 40167 40222 40277
Network Faults 40058 40113 40168 40223 40278
Customer Faults 40059 40114 40169 40224 40279
ES State (See Table 17 on page
40060 40115 40170 40225 40280
284)
Load Share State (See Table 18 on
40061 40116 40171 40226 40281
page 285)
Load Govern State kW (See Table
40062 40117 40172 40227 40282
22 on page 286)
Load Govern State kVAR (SeeTable
40063 40118 40173 40228 40283
20 on page 285)

7.2.3 Word Data


Reference the ATS 6-1 and 6-10 tables in Section 8.

TABLE 16.

Digital State
0 Stopped
1 Start Pending
2 Warm-up at Idle
3 Running
4 Cooldown at Rated
5 Cooldown at idle

TABLE 17.

Digital ES State
0 Standby
1 Dead Bus Close
2 Synchronizing

Copyright © 2023 Cummins Inc. 284 A029X159 (Issue 31)


8-2023 7. DMC 1500

Digital ES State
3 Load Share
4 Load Govern

TABLE 18.

Digital Load Share State


0 Not in Load Share
1 Track Load
2 Ramp Load
3 Ramp Unload
4 Load Demand Shutdown

TABLE 19.

Digital Load Govern State kW


0 NA
1 Ramp Load
2 Track Target Load
3 Ramp Unload
4 Ramp Unload Done

TABLE 20.

Digital Load Govern State kVAR


0 NA
1 Ramp Load
2 Track Target Load
3 Ramp Unload
4 Ramp Unload Done

TABLE 21.

Digital Fault Type


0 Normal
1 Warning
2 Derate
3 Shutdown with Cooldown

A029X159 (Issue 31) 285 Copyright © 2023 Cummins Inc.


7. DMC 1500 8-2023

Digital Fault Type


4 Shutdown

TABLE 22.

Digital Control Switch


0 Off
1 Manual
2 Automatic

7.2.4 Generator Raw Data Gen 6-8


Generator Raw Data Gen 6 Gen 7 Gen 8 Multiplier Units
Device Type 40286 40341 40396
Control Switch (See Table 22 on page 286) 40287 40342 40397
State (See Table 16 on page 284) 40288 40343 40398
Fault Code 40289 40344 40399
Fault Type (See Table 21 on page 285) 40290 40345 40400
Percent kW Standby 40291 40346 40401 0.5 %
Total kW 40292 40347 40402
NFPA 110 (See Table 5 on page 12) 40293 40348 40403
NFPA Extended (See Table 6 on page 12) 40294 40349 40404
Frequency 40295 40350 40405 0.1 Hz
Total pf 40296 40351 40406 0.00005 PF
Total kVA 40297 40352 40407 kVA
Total kW 40298 40353 40408 kW
Total kVAR 40299 40354 40409 kVAR
Volts ab 40300 40355 40410 Volts
Volts bc 40301 40356 40411 Volts
Volts ca 40302 40357 40412 Volts
Volts a 40303 40358 40413 Volts
Volts b 40304 40359 40414 Volts
Volts c 40305 40360 40415 Volts
Amps a 40306 40361 40416 Amps
Amps b 40307 40362 40417 Amps
Amps c 40308 40363 40418 Amps
Percent Amps a 40309 40364 40419 0.5 %

Copyright © 2023 Cummins Inc. 286 A029X159 (Issue 31)


8-2023 7. DMC 1500

Generator Raw Data Gen 6 Gen 7 Gen 8 Multiplier Units


Percent Amps b 40310 40365 40420 0.5 %
Percent Amps c 40311 40366 40421 0.5 %
Battery Voltage 40312 40367 40422 0.1 Volts
Oil Pressure 40313 40368 40423 0.1 kPa
Oil Temp 40314 40369 40424 0.1 Deg K
Coolant Temp 40315 40370 40425 0.1 Deg K
Fuel Rate 40316 40371 40426 0.001 GPH
Engine RPM 40317 40372 40427 RPM
Engine Starts 40318 40373 40428 Starts
Engine Runtime High 40319 40374 40429
Engine Runtime Low 40320 40375 40430 0.1 Sec
Total kWH High 40321 40376 40431
Total kWH Low 40322 40377 40432 KWH
Total Fuel High 40323 40378 40433
Total Fuel Low 40324 40379 40434 0.01 GAL
Bus Frequency 40325 40380 40435 0.1 Hz
Bus Volts ab 40326 40381 40436 Volts
Bus Volts bc 40327 40382 40437 Volts
Bus Volts ca 40328 40383 40438 Volts
Bus Volts a 40329 40384 40439 Volts
Bus Volts b 40330 40385 40440 Volts
Bus Volts c 40331 40386 40441 Volts
Customer Faults 40332 40387 40442
Network Faults 40333 40388 40443
Customer Faults 40334 40389 40444
ES State (See Table 17 on page 284) 40335 40390 40445
Load Share State (See Table 18 on page
40336 40391 40446
285)
Load Govern State kW (See Table 19 on
40337 40392 40447
page 285)
Load Govern State kVAR (See Table 20 on
40338 40393 40448
page 285)

A029X159 (Issue 31) 287 Copyright © 2023 Cummins Inc.


7. DMC 1500 8-2023

This page is intentionally blank.

Copyright © 2023 Cummins Inc. 288 A029X159 (Issue 31)


8 ECO Tier4 Modbus TCP Register Map
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

FAULT CODE 3697 - Engine Control Module Calibration Memory - Bad Intelligent Device or
Component

Associated Procedures
Procedure Title Procedure Number Service Model Name Bulletin Number
Engine Control Module Refer to Procedure 019-031 ISF2.8 CM2220 EC2CF 4310641
Engine Control Module Refer to Procedure 019-031 ISF2.8 CM2220 E ISF2.8 4022178
CM2220 AN
ISF2.8 CM2220 IAN
Engine Control Module Refer to Procedure 019-031 ISF3.8 CM2220 ISF3.8 4021704
CM2220 AN
ISF3.8 CM2220 IAN
Engine Control Module Refer to Procedure 019-031 ISF2.8 CM2220 F122 5467376
Engine Control Module Refer to Procedure 019-031 ISF3.8 CM2220 F103 4310839
Engine Control Module Refer to Procedure 019-031 ISB4.5, ISB6.7, ISD4.5, and 4022188
ISD6.7 CM2150 SN
Engine Control Module Refer to Procedure 019-031 ISV5.0 CM3230 V104 4367291
Engine Control Module Refer to Procedure 019-031 ISL8.9 CM2150 SN 4022190
Engine Control Module Refer to Procedure 019-031 ISM11 CM876 SN 4022196
Engine Control Module Refer to Procedure 019-031 ISZ13 CM2150 4022133
Engine Control Module Refer to Procedure 019-031 ISX15 CM2250 4022250
GX CM2250
Engine Control Module Refer to Procedure 019-031 ISX12/ISX11.9 CM2250 2883445
Engine Control Module Refer to Procedure 019-031 QSL9 CM2250 4022256
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2250 4022255
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2250 EC 2883621
Engine Control Module Refer to Procedure 019-031 QSB3.3 CM2250 EC 2883647
Engine Control Module Refer to Procedure 019-031 QSX15 CM2250 ECF 2883557

A029X159 (Issue 31) 289 Copyright © 2023 Cummins Inc.


8. ECO Tier4 Modbus TCP Register Map 8-2023

Engine Control Module Refer to Procedure 019-031 PowerGen QSX15 CM2250 4310661
ECF
Engine Control Module Refer to Procedure 019-031 PowerGen QSX15 CM2250 4310664
Engine Control Module Refer to Procedure 019-031 QSX11.9 CM2250 ECF 2883561
Engine Control Module Refer to Procedure 019-031 ISB6.7 CM2350 B101 2883567
Engine Control Module Refer to Procedure 019-031 ISL9 CM2350 L101 4310787
Engine Control Module Refer to Procedure 019-031 ISX12 CM2350 X102 4310646
Engine Control Module Refer to Procedure 019-031 ISX15 CM2350 X101 4310641
Engine Control Module Refer to Procedure 019-031 ISX15 CM2250 SN 4310736
Engine Control Module Refer to Procedure 019-031 ISB4.5 CM2350 B104 4332646
Engine Control Module. Refer to Procedure 019-031 ISB6.7 CM2350 B103 4332641
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2350 B105 4332778
Engine Control Module Refer to Procedure 019-031 QSL9 CM2350 L102 4332796
Engine Control Module Refer to Procedure 019-031 ISB/ISD4.5 CM2150 B119 4358465
Engine Control Module Refer to Procedure 019-031 ISB/ISD6.7 CM2150 B120 4358470
Engine Control Module Refer to Procedure 019-031 ISL8.9 CM2350 L110 4358475
Engine Control Module Refer to Procedure 019-031 ISF3.8 CM2220 F110 4358480
Engine Control Module Refer to Procedure 019-031 QSL9 M CM2250 L106 4358343
Engine Control Module Refer to Procedure 019-031 QSZ13 CM2150 Z101 4358364
Engine Control Module Refer to Procedure 019-031 QSZ13 CM2150 Z102 4358369
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2350 B112 4358498

Associated Procedures
Procedure Title Procedure Number Service Model Name Bulletin Number
Engine Control Module Refer to Procedure 019-031 QSF2.8 CM2880 F105 4358561
Engine Control Module Refer to Procedure 019-031 ISL9 CM2350 L111 4367223
Engine Control Module Refer to Procedure 019-031 QSB4.5 CM2350 B106 4367376
Engine Control Module Refer to Procedure 019-031 QSF3.8 CM2350 F107 4367316
Engine Control Module Refer to Procedure 019-031 QSG12 CM2350 G110 4367323
Engine Control Module Refer to Procedure 019-031 QSF2.8 CM2880 F114 4383734
Engine Control Module Refer to Procedure 019-031 ISF2.8 CM2220 F117 4388578
Engine Control Module Refer to Procedure 019-031 QSL9 CM2350 L107 4367386
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2250 B128 4388601
Engine Control Module Refer to Procedure 019-031 QSL9 CM2250 L115 4388626
Engine Control Module Refer to Procedure 019-031 QSF3.8 CM2350 F118 4388708

Copyright © 2023 Cummins Inc. 290 A029X159 (Issue 31)


8-2023 8. ECO Tier4 Modbus TCP Register Map

Engine Control Module Refer to Procedure 019-031 QSF3.8 CM2350 F119 4388703
Engine Control Module Refer to Procedure 019-031 ISF3.8 CM2220 F116 4383664
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2350 B130 4388668
Engine Control Module Refer to Procedure 019-031 QSL9 CM2350 L118 4388673
Engine Control Module Refer to Procedure 019-031 QSB4.5 CM2350 B122 4388767
Engine Control Module Refer to Procedure 019-031 ISF2.8 CM2220 F126 5411159
Engine Control Module Refer to Procedure 019-031 X15 CM2350 X114B 5411181
Engine Control Module Refer to Procedure 019-031 X15 CM2350 X116B 5411186
Engine Control Module Refer to Procedure 019-031 B6.7 CM2350 B121B 5411223
Engine Control Module Refer to Procedure 019-031 ISB6.7 CM2350 B142 5411131
Engine Control Module Refer to Procedure 019-031 QSX15 CM2250 X115 4388739
Engine Control Module Refer to Procedure 019-031 QSB4.5 CM2250 B131 4388774
Engine Control Module Refer to Procedure 019-031 QSB3.3 CM2250 B137 5411058
Engine Control Module Refer to Procedure 019-031 L9 CM2350 L116B 5411330
Engine Control Module Refer to Procedure 019-031 F3.8 CM350 F120B 5411237
Engine Control Module Refer to Procedure 019-031 B4.5 CM2350 B129B 5411247
Engine Control Module Refer to Procedure 019-031 B6.7 CM2350 B135B 5411257
Engine Control Module Refer to Procedure 019-031 B4.5 CM2350 B147B 5411252
Engine Control Module Refer to Procedure 019-031 B6.7 CM2350 B148B 5411262
Engine Control Module Refer to Procedure 019-031 L9 CM2350 L119B 5411267
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2350 B145 5411273
Engine Control Module Refer to Procedure 019-031 QSL9 CM2350 L122 5411278
Engine Control Module Refer to Procedure 019-031 QSB4.5 CM2350 B144 5411382
Engine Control Module Refer to Procedure 019-031 L9 CM2350 L123B 5411465
Engine Control Module Refer to Procedure 019-031 QSF2.8 CM2880 F124 5411484
Engine Control Module Refer to Procedure 019-031 QSF2.8 CM2880 F131 5411489
Engine Control Module Refer to Procedure 019-031 ISF4.5 CM2220 F123 5411320
Engine Control Module Refer to Procedure 019-031 QSF3.8 CM2350 F125 5411494
Engine Control Module Refer to Procedure 019-031 QSX15 CM2350 X118 5467247
Engine Control Module Refer to Procedure 019-031 QSG12 CM2350 G113 5467252
Engine Control Module Refer to Procedure 019-031 R2.8 CM2220 R101B 5467556
Engine Control Module Refer to Procedure 019-031 F3.8 CM2350 F132B 5467327
Engine Control Module Refer to Procedure 019-031 ISB5.9 CM2880 B110 4332883
Engine Control Module Refer to Procedure 019-031 B6.7 CM2350 B136C 5504194
Engine Control Module Refer to Procedure 019-031 L9 CM2350 L120C 5504199

A029X159 (Issue 31) 291 Copyright © 2023 Cummins Inc.


8. ECO Tier4 Modbus TCP Register Map 8-2023

Engine Control Module Refer to Procedure 019-031 ISF3.8 CM2220 F134B 5504165

Associated Procedures
Procedure Title Procedure Number Service Model Name Bulletin Number
Engine Control Module Refer to Procedure 019-031 F3.8 CM2350 F133C 5504278
Engine Control Module Refer to Procedure 019-031 F3.8 CM2350 F128C 5504273
Engine Control Module Refer to Procedure 019-031 B4.5 CM2350 B145C 5504283
Engine Control Module Refer to Procedure 019-031 F2.8 CM2620 F135B 5504616
Engine Control Module Refer to Procedure 019-031 F2.8 CM2620 F136B 5504621
Engine Control Module Refer to Procedure 019-031 F3.8 CM2620 F137B 5579617
Engine Control Module Refer to Procedure 019-031 F4.5 CM2620 F139B 5579622

TROUBLESHOOTING STEPS
STEP 1: Check the fault codes.
STEP 1A: Check for active fault codes.

Condition:
• Turn keyswitch ON.
• Connect INSITE™ electronic servicetool.
Action Specification/Repair Next Step
Check the fault codes. Fault Code 111 active? Fault Code 111
• Use INSITE™ electronic service YES troubleshooti ng tree.
tool to read the fault codes. Fault Code 111 active? 2A
NO

STEP2: Calibrate the ECM.


STEP 2A: Calibrate the ECM.

Condition:
• Connect all components.
• Turn keyswitch ON.
• Connect INSITE™ electronic service tool.
Action Specification/Repair Next Step

Copyright © 2023 Cummins Inc. 292 A029X159 (Issue 31)


8-2023 8. ECO Tier4 Modbus TCP Register Map

Use INSITE™ electronic service tool Fault Code 3697 active after 2B
to calibrate the ECM with the latest calibrating the ECM?
engine calibration. Refer to the YES
calibration revisions listed in the ECM Repair:
Calibration Revision History to find
Replace the ECM. Refer to Procedure
the latest calibration available for the
engine being serviced. 019-031 in the Associated Procedures
Table.
• Use INSITE™ electronic service
tool to find the present ECM Fault Code 3697 active after 2B
code and revision number in the calibrating the ECM?
ECM. The ECM code and NO
revision number are found in the
Calibration Information section
of System ID and Dataplate in
Features and Parameters.

A029X159 (Issue 31) 293 Copyright © 2023 Cummins Inc.


8. ECO Tier4 Modbus TCP Register Map 8-2023

This page is intentionally blank.

Copyright © 2023 Cummins Inc. 294 A029X159 (Issue 31)


9 MCM3320
9.1 MCM3320 Modbus Register Map
9.1.1 Modbus Communications
This section defines the Modbus communications interface. Serial communications use an RTU (Remote
Terminal Unit) two-wire RS485 multi-drop network configuration described in the Modbus Protocol
Reference Guide. The Cummins control is a Slave unit.

9.1.2 Reference Documents


1. “Modbus Over Serial Line Specification and Implementation Guide V1.02" describes the lower levels
of Modbus protocol.
2. “Modbus Application Protocol Specification V1.1b3" describes the application layer of the Modbus
protocol.

9.1.3 Serial Port Configuration


The port communications occur, by default, at a baud rate of 19200 using eight data bits, one stop-bit with
even parity, and are configurable via MON and PCCNet logically.

9.1.4 Device Addresses


The PLC is the Master device in the Modbus network. The Modbus node address is configurable and is
set to node 1 by default.

9.1.5 Power-Up Time


The MCM3320 is capable of supporting communication transactions within 10 seconds following initial
power-up.

9.1.6 Response Time


The controller responds within 100 ms of a request for information from the Master.

9.1.7 Data Formatting


The format for each register is defined in the Modbus register table.
All data parameters are transmitted as registers. All registers are two 8 bit bytes in length (16 bits per
register). If a register requires more than 16 bits, then, the subsequent registers are also used. Therefore,
with a 32 bit register X and X+1, the X register contains the upper 16 bits of data and the X+1 register
contains the lower 16 bits. A register with 1 bit of data uses the least significant bit of a 16 bit register.
For all discrete data referenced a by bit number, the least significant bit for the register is numbered as 0
inch and the most significant bit as 15 inch. For all fault statuses and event statuses, a 1 inch indicates the
fault or event is active and a 0 inch indicates inactive.

A029X159 (Issue 31) 295 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

9.1.8 Modbus Activity LED


The Modbus activity LED is on when either the control is receiving a Modbus packet or sending a Modbus
packet. It is also on when a protocol timer is in timer mode. This precedes a protocol switch on the SCI1
port. Otherwise, the LED is off.

9.1.9 Supported Functions


The controller is only capable of processing the following Modbus data and control function queries from
the Master:
• Read holding registers (Function Code 03)
• Preset single register (Function Code 06)
• Diagnostics (Function Code 08)
• Preset multiple registers (Function Code 16)
The control responds to any query containing a function code, other than codes 03, 06, 08 and 16, by
sending an exception response with the exception code set to 01 (Illegal Function).
The control responds to any read of a single address that is not defined in this specification by sending an
exception response with the exception code set to 02 (Illegal Address).
The control responds to any read of a block of 2 or more addresses containing an address that is not
defined in this specification by returning data of 0xFFFF for that address.
The control responds to Preset Single Register and Preset Multiple Register functions when the data is
out of bounds by sending an exception response with the exception code set to 03 (Illegal Data Value).

9.1.10 Holding Register Function


The control provides the ability to read all read only and read/write registers in the Modbus Registers
Table via the Holding Register function. From 1 to 40 contiguous registers can be read at a time. If an
attempt is made to read a register that's not available, then an error is returned and none of the data will
be returned.

9.1.11 Preset Single/Preset Multiple Registers Function


The control provides the ability to write to (preset) Read/Write registers in the Modbus registers table via
both the preset single register (Function Code 06) and the preset multiple registers (Function Code 16). A
write to a single register can be performed by the Master using the Modbus data and control function
query preset single register (Function Code 06). For writes requiring writes to 1 to 40 contiguous registers,
the Master uses the Modbus data and control function query called preset multiple registers (Function
Code 16). If a write attempt is made and any of the data is invalid or if an attempt is made to write to a
register that's not available, then an error is returned and none of the data will be written.

9.1.12 Diagnostic Counters


The following diagnostic counters is also available via the Modbus diagnostic function (Function Code 08).
The following parameters are updated and available via MON and Modbus logical access. A single logical
is also available to clear all counters.
• Bus Message Count - Total Modbus packets on bus
• CRC Errors Count - Total Modbus packets received with a bad CRC
• Exception Count - Total Modbus packets received where an exception was sent back
• No Response Count - Total Modbus packets received where no response sent back
• Slave Message Count - Total Modbus packets on bus addressed to this node

Copyright © 2023 Cummins Inc. 296 A029X159 (Issue 31)


8-2023 9. MCM3320

9.1.13 Register Maps


Addresses were assigned to maintain compatibility with the existing Modlon gateway where applicable.
The following conventions are followed:
• 40xxx - Genset control registers
• 41xxx - Transfer switch control register
• 42xxx - Master control registers (MCM3320)
• 4x0xx - General data registers (volts, current, etc.) primarily for genset bus
• 4x1xx - General data registers (volts, current, etc.) primarily for utility bus
• 4x2xx - Configuration and status registers - Block 1
• 4x3xx - Settings - Block 1
• 4x4xx - Settings - Block 2
• 4x5xx - Bitmap
• 4x6xx - Switch I/O
• 4x7xx - Configuration and status registers - Block 2

9.1.14 Application Layer


The application layer processes the packet. Four functions are supported: Read Hold Registers, Set
Single Register, Modbus Loopback, and Set Multiple Registers. If the request packet specifies an
unsupported function, then an illegal function response is returned. See the "Modbus Application Protocol
Specification" to see how the request and response packets are formatted and how each function
processes the data.

9.1.15 Read Hold Registers


Given a starting address and the quantity of registers desired, this function gets the data, formats it if
required, and writes it to the TX buffer. If any register in the range is not supported, then an error is
returned.

9.1.16 Set Single Register


Given a register address and data, this function verifies that the data is within range; then if OK, writes the
data.

9.1.17 Modbus Loopback


This function performs Modbus diagnostic functionality. Some of the functionality defined here is also
available via MON and PCCNet logicals. See the "Diagnostic Counters" section of this document for
details. The Loopback function supports:
• 0x00 Return Query Data
• 0x01 Restart
• 0x04 Force Listen Only Mode
• 0x0A Clear Counter
• 0x0B Return Bus Message Count
• 0x0C Return Bus Communication Error Count (bad CRC)
• 0x0D Return Bus Exception Error Count

A029X159 (Issue 31) 297 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

• 0x0E Return Slave Message Count


• 0x0F Return Slave No Response Count

9.1.18 Set Multiple Registers


Given a starting address, the quantity of registers, and two bytes of data for each register, this function
verifies that all the data is within range; then if OK, writes all data. If any register in the range is not
supported or any of the data is out of range then an error is returned and no data is written. A 32-bit
parameter is written using "Write Multiple Register" (Command Code 16) only. Using "Write Single
Register" (Command Code 06) returns an exception code 2 - Illegal Address. If both registers are not in
the same block, the control sends an exception code 2-Illegal Address.

9.1.19 Modbus Register Table


NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

Addr. System Name Access Specifications Description Function

Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Logical
MB logical Read / Offset: 0 address to be
42001 Upper Limit: Communications
Read Address Write read via
Size (bits):16 65535.000 Modbus
Sign: U Default: 0
Multiplier:
Unit: NA
1.000000000000 Logical data to
MB Logical Read Lower Limit:
42002 Offset: 0 be read via Communications
Read Data Only Upper Limit:
Size (bits): 32 Modbus
Default:
Sign: U
Save
configuration
parameters or
adjustments to
non-volatile
memory.
0: Do Nothing Perform Save
Save Read / Controller
42004 1: Save Trims Trims after all
Adjustments Write Information
Default: Do Nothing configurations
have been
updated. Do
not save trims
unless a
change has
occurred.

Copyright © 2023 Cummins Inc. 298 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA
1.000000000000 Hard coded
Read Lower Limit:
42009 Device Type Offset: 0 device type id= Communications
Only Upper Limit:
Size (bits):16 52 (0x0034)
Default:
Sign: U
Multiplier:
Unit: NA
.000100000000
Software Read Lower Limit: Software Controller
42010 Offset: 0
Version Only Upper Limit: version number Information
Size (bits):16
Default:
Sign: U
0: Time Delay Start
1: Time Delay Stop Indicates state
Genset Run
Read of the PTC Operating
42011 Sequence 2: Stop
Only generator set Mode
State 3: Run run sequence
Default:
Multiplier: The most
Unit: NA
1.000000000000 recently
Current Fault Read Lower Limit: Fault and Event
42012 Offset: 0 occurring fault
Status Only Upper Limit: Information
Size (bits):16 which is still
Default: active
Sign: U
0: Unavailable Energization
Genset Bus Read 1: Dead status of
42017 PTC Sensors
Status Only 2: Live generator Set
Default: bus

Multiplier:
Unit: Volts
1.000000000000
Genset L1N Read Lower Limit: Volts Generator set
42018 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L1N voltage
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L2N Read Lower Limit: Volts Generator set
42019 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L2N voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L3N Read Lower Limit: Volts Generator set
42020 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L3N voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
Genset LN 1.000000000000 Generator set
Read Lower Limit: Volts
42021 Average Offset: 0 LN average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default:
Sign: U

A029X159 (Issue 31) 299 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Multiplier:
1.000000000000 Unit: Volts
Genset L1L2 Read Offset: 0 Lower Limit: Volts Generator set
42022 Voltage
Voltage Only Upper Limit: Volts L1L2 voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L2L3 Read Lower Limit: Volts Generator set
42023 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L2L3 voltage
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L3L1 Read Lower Limit: Volts Generator set
42024 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L3L1 voltage.
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Volts
Genset LL 1.000000000000 Generator set
Read Lower Limit: Volts
42025 Average Offset: 0 LL Average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Genset L1 Read Lower Limit: Amps Generator set
42026 Offset: 0 Current
Current Only Upper Limit: Amps L1 current
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Genset L2 Read Lower Limit: Amps Generator set
42027 Offset: 0 Current
Current Only Upper Limit: Amps L2 current
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Genset L3 Read Lower Limit: Amps Generator set
42028 Offset: 0 Current
Current Only Upper Limit: Amps L3 current
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
Genset 1.000000000000 Generator set
Read Lower Limit: Amps
42029 Average Offset: 0 average Current
Only Upper Limit: Amps
Current Size (bits): 16 current
Default:
Sign: U

Copyright © 2023 Cummins Inc. 300 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW Generator set
42030 Genset L1 kW Offset: 0 Power
Only Upper Limit: kW L1 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW Generator set
42031 Genset L2 kW Offset: 0 Power
Only Upper Limit: kW L2 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW Generator set
42032 Genset L3 kW Offset: 0 Power
Only Upper Limit: kW L3 kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Genset Total Read Lower Limit: kW Generator set
42033 Offset: 0 Power
kW Only Upper Limit: kW total kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset L1 Read Lower Limit: kVAR Generator set
42034 Offset: 0 Power
kVAR Only Upper Limit: kVAR L1 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset L2 Read Lower Limit: kVAR Generator set
42035 Offset: 0 Power
kVAR Only Upper Limit: kVAR L2 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset L3 Read Lower Limit: kVAR Generator set
42036 Offset: 0 Power
kVAR Only Upper Limit: kVAR L3 kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Genset Total Read Lower Limit: kVAR Generator set
42037 Offset: 0 Power
kVAR Only Upper Limit: kVAR total kVAR
Size (bits): 16
Default:
Sign: S

A029X159 (Issue 31) 301 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA
1.000000000000
Genset Total Read Lower Limit: Generator set
42038 Offset: 0 Power
Power Factor Only Upper Limit: L1 power factor
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA Generator set
42039 Genset L1 kVA Offset: 0 Power
Only Upper Limit: kVA L1 kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA Generator set
42040 Genset L2 kVA Offset: 0 Power
Only Upper Limit: kVA L2 kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA Generator set
42041 Genset L3 kVA Offset: 0 Power
Only Upper Limit: kVA L3 kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Genset Total Read Lower Limit: kVA Generator set
42042 Offset: 0 Power
kVA Only Upper Limit: kVA total kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Generator set
Unit: Hz
.100000000000 line frequency
MB Genset Read Lower Limit: Hz
42043 Offset: 0 scaled by 10 = Communications
Frequency Only Upper Limit: Hz
Size (bits): 16 1Hz for
Default: Modbus
Sign: U
Multiplier:
Unit: kWh Generator set
1.000000000000
Genset Total Read Lower Limit: kWh total negative
42044 Offset: 0 Energy
Negative kWh Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh Generator set
1.000000000000
Genset Total Read Lower Limit: kWh total positive
42046 Offset: 0 Energy
Positive kWh Only Upper Limit: kWh kWh
Size (bits): 32 accumulation
Default:
Sign: U

Copyright © 2023 Cummins Inc. 302 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kWh
1.000000000000 Generator set
Genset Total Read Lower Limit: kWh
42048 Offset: 0 total net kWh Energy
Net kWh Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVARh Generator set
Genset Total 1.000000000000
Read Lower Limit: kVARh total negative
42050 Negative Offset: 0 Energy
Only Upper Limit: kVARh kVARh
kVARh Size (bits): 32
Default: accumulation
Sign: U
Multiplier:
Unit: kVARh Generator set
1.00000000000
Genset Total Read Lower Limit: kVARh total positive
40052 0Offset: 0 Energy
Positive kVARh Only Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kVARh Generator set
1.000000000000
Genset Total Read Lower Limit: kVARh total net
42054 Offset: 0 Energy
Net kVARh Only Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVARh
1.000000000000 Generator set
Genset Total Read Lower Limit: kVARh
42056 Offset: 0 total kVAh Energy
kVAh Only Upper Limit: kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Calculated
Multiplier: amps which
Unit: Amps
Genset 1.000000000000 represent 100-
Read Lower Limit: Amps
42058 Available Offset: 0 % generator Current
Only Upper Limit: Amps
Current Size (bits): 16 set bus current
Default: - used by
Sign: U
bargraph
Generator set
Multiplier: L1 current as
Unit: %
Genset L1 .100000000000 percent of
Read Lower Limit: %
42059 Current Offset: 0 generator Set Current
Only Upper Limit: %
Percent Size (bits): 16 total current
Default: capacity - used
Sign: S
by bargraph
Generator set
Multiplier: L2 current as
Unit: %
Genset L2 .100000000000 percent of
Read Lower Limit: %
42060 Current Offset: 0 generator Set Current
Only Upper Limit: %
Percent Size (bits): 16 total current
Default: capacity - used
Sign: U
by bargraph

A029X159 (Issue 31) 303 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Generator set
Multiplier: L3 current as
Unit: %
Genset L3 .100000000000 percent of
Read Lower Limit: %
42061 Current Offset: 0 generator Set Current
Only Upper Limit: %
Percent Size (bits): 16 total current
Default: capacity - used
Sign: U
by bargraph

Multiplier: Generator set


Unit: % kW as percent
.100000000000
Genset Total Read Lower Limit: % of total
42062 Offset: 0 Power
kW Percent Only Upper Limit: % generator set
Size (bits): 16 capacity - used
Default:
Sign: S by bargraph
Generator set
Multiplier: frequency as
Unit: %
Genset .100000000000 percent of
Read Lower Limit: %
42063 Frequency Offset: 0 system Frequency
Only Upper Limit: %
Percent Size (bits): 16 frequency -
Default: used by
Sign: U
bargraph
Multiplier:
Unit: %
.100000000000
Genset L1L2 Read Lower Limit: % Generator set
42064 Offset: 0 Voltage
Voltage% Only Upper Limit: % L1L2 voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
.100000000000
Genset L2L3 Read Lower Limit: % Generator set
42065 Offset: 0 Voltage
Voltage% Only Upper Limit: % L2L3 voltage %
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
.100000000000
Genset L3L1 Read Lower Limit: % Generator set
42066 Offset: 0 Voltage
Voltage% Only Upper Limit: % L3L1 voltage%
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000 Generator set
Genset Total Read Lower Limit: kW
42070 Offset: 0 total kW in 32 Power
kW_32bit Only Upper Limit: kW
Size (bits): 32 bit
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000 Generator set
Genset Total Read Lower Limit: kVAR
42072 Offset: 0 total kVAR in Power
kVAR_32bit Only Upper Limit: kVAR
Size (bits): 32 32 bit
Default:
Sign: S

Copyright © 2023 Cummins Inc. 304 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kVA
1.000000000000 Generator set
Genset Total Read Lower Limit: kVA
42074 Offset: 0 total kVA in 32 Power
kVA_32bit Only Upper Limit: kVA
Size (bits): 32 bit
Default:
Sign: U
0: Unavailable
1: Dead Energization
Utility Bus Read
42117 status of the PTC Sensors
Status Only 2: Live utility bus
Default:
Multiplier:
Unit: Volts
1.000000000000
Utility L1N Read Lower Limit: Volts Utility L1N
42118 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L2N Read Lower Limit: Volts Utility L2N
42119 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L3N Read Lower Limit: Volts Utility L3N
42120 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
Utility LN 1.000000000000 Utility LN
Read Lower Limit: Volts
42121 Average Offset: 0 average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L1L2 Read Lower Limit: Volts Utility L1L2
42122 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L2L3 Read Lower Limit: Volts Utility L2L3
42123 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Utility L3L1 Read Lower Limit: Volts Utility L3L1
42124 Offset: 0 Voltage
Voltage Only Upper Limit: Volts voltage
Size (bits): 16
Default:
Sign: U

A029X159 (Issue 31) 305 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: Volts
Utility LL 1.000000000000 Utility LL
Read Lower Limit: Volts
42125 Average Offset: 0 average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility L1 Read Lower Limit: Amps Utility L1
42126 Offset: 0 Current
Current Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility L2 Read Lower Limit: Amps Utility L2
42127 Offset: 0 Current
Current Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility L3 Read Lower Limit: Amps Utility L3
42128 Offset: 0 Current
Current Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Amps
1.000000000000
Utility Average Read Lower Limit: Amps Utility average
42129 Offset: 0 Current
Current Only Upper Limit: Amps current
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW
42130 Utility L1 kW Offset: 0 Utility L1 kW Power
Only Upper Limit: kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW
42131 Utility L2 kW Offset: 0 Utility L2 kW Power
Only Upper Limit: kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW
42132 Utility L3 kW Offset: 0 Utility L3 kW Power
Only Upper Limit: kW
Size (bits): 16
Default:
Sign: S

Copyright © 2023 Cummins Inc. 306 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kW
1.000000000000
Read Lower Limit: kW
42133 Utility Total kW Offset: 0 Utility total kW Power
Only Upper Limit: kW
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Read Lower Limit: kVAR
42134 Utility L1 kVAR Offset: 0 Utility L1 kVAR Power
Only Upper Limit: kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Read Lower Limit: kVAR
42135 Utility L2 kVAR Offset: 0 Utility L2 kVAR Power
Only Upper Limit: kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Read Lower Limit: kVAR
42136 Utility L3 kVAR Offset: 0 Utility L3 kVAR Power
Only Upper Limit: kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Utility Total Read Lower Limit: kVAR Utility total
42137 Offset: 0 Power
kVAR Only Upper Limit: kVAR kVAR
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: NA
1.000000000000
Utility Total Read Lower Limit: Utility L1 power
42138 Offset: 0 Power
Power Factor Only Upper Limit: factor
Size (bits): 16
Default:
Sign: S
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA
42139 Utility L1 kVA Offset: 0 Utility L1 kVA Power
Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA
42140 Utility L2 kVA Offset: 0 Utility L2 kVA Power
Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U

A029X159 (Issue 31) 307 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kVA
1.000000000000
Read Lower Limit: kVA
42141 Utility L3 kVA Offset: 0 Utility L3 kVA Power
Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kVA
1.000000000000
Utility Total Read Lower Limit: kVA
42142 Offset: 0 Utility total kVA Power
kVA Only Upper Limit: kVA
Size (bits): 16
Default:
Sign: U
Multiplier: Utility line
Unit: Hz
1.000000000000 frequency
MB Utility Read Lower Limit: Hz
42143 Offset: 0 scaled by 10 = Communications
Frequency Only Upper Limit: Hz
Size (bits): 16 1Hz for
Default: Modbus
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit: kWh
42144 Offset: 0 negative kWh Energy
Negative kWh Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Utility total
Utility Total Read Lower Limit: kWh
42146 Offset: 0 positive kWh Energy
Positive kWh Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kWh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit: kWh
42148 Offset: 0 kWh Energy
kWh Only Upper Limit: kWh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVARh Utility total
1.000000000000
Utility Total Read Lower Limit: kVARh negative
42150 Offset: 0 Energy
Negative Only Upper Limit: kVARh kVARh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kVARh
1.000000000000 Utility total
Utility Total Read Lower Limit: kVARh
42152 Offset: 0 positive kVARh Energy
Positive kVARh Only Upper Limit: kVARh
Size (bits): 32 accumulation
Default:
Sign: U

Copyright © 2023 Cummins Inc. 308 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kVARh
1.000000000000 Utility total net
Utility Total Net Read Lower Limit: kVARh
42154 Offset: 0 kVARh Energy
kVARh Only Upper Limit: kVARh
Size (bits): 32 accumulation
Default:
Sign: S
Multiplier:
Unit: kVAh
1.000000000000 Utility total
Utility Total Read Lower Limit: kVAh
42156 Offset: 0 kVARh Energy
kVAh Only Upper Limit: kVAh
Size (bits): 32 accumulation
Default:
Sign: U
Multiplier:
Unit: kW Sum of
1.000000000000
System Total Read Lower Limit: kW generator set
42158 Offset: 0 Power
kW Only Upper Limit: kW bus and utility
Size (bits): 16 bus kW
Default:
Sign: S
Multiplier:
Unit: kVAR Sum of
1.000000000000
System Total Read Lower Limit: kVAR generator set
42159 Offset: 0 Power
kVAR Only Upper Limit: kVAR bus and utility
Size (bits): 16 bus kVAR
Default:
Sign: S

Multiplier: System total


Unit: NA power factor
.010000000000
System Total Read Lower Limit: (totalized value
42160 Offset: 0 Power
Power Factor Only Upper Limit: of utility bus
Size (bits): 16 plus generator
Default:
Sign: S set bus)
Multiplier:
Unit: kVA Sum of
1.000000000000
System Total Read Lower Limit: kVA generator set
42161 Offset: 0 Power
kVA Only Upper Limit: kVA bus and utility
Size (bits): 16 bus kVA
Default:
Sign: U

Multiplier: Utility L1
Unit: % current as % of
Utility L1 .100000000000
Read Lower Limit: % utility total
42162 Current Offset: 0 Current
Only Upper Limit: % current
Percent Size (bits): 16
Default: capacity - used
Sign: U by bargraph

Multiplier: Utility L2
Unit: % current as % of
Utility L2 .100000000000
Read Lower Limit: % utility total
42163 Current Offset: 0 Current
Only Upper Limit: % current
Percent Size (bits): 16
Default: capacity - used
Sign: U by bargraph

A029X159 (Issue 31) 309 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function

Multiplier: Utility L3
Unit: % current as
Utility L3 .100000000000
Read Lower Limit: % as % of utility
42164 Current Offset: 0 Current
Only Upper Limit: % total current
Percent Size (bits): 16
Default: capacity - used
Sign: U by bargraph
Multiplier: Utility total kW
Unit: %
.100000000000 as percent of
Utility Total kW Read Lower Limit %
42165 Offset: 0 total utility Power
Percent Only Upper Limit: %
Size (bits): 16 capacity - used
Default: by bargraph
Sign: S
Utility
Multiplier: frequency as
Unit: %
Utility .100000000000 percent of
Read Lower Limit: %
42166 Frequency Offset: 0 system Frequency
Only Upper Limit: %
Percent Size (bits): 16 frequency -
Default: used by
Sign: U
bargraph
Multiplier:
Unit: %
.100000000000
Utility L1L2 Read Lower Limit: % Utility L1L2
42167 Offset: 0 Voltage
Voltage % Only Upper Limit: % voltage %
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
.100000000000
Utility L2L3 Read Lower Limit: % Utility L2L3
42168 Offset: 0 Voltage
Voltage % Only Upper Limit: % voltage %
Size (bits): 16
Default:
Sign: U

Addr. System Name Access Specifications Description Function


Multiplier:
Unit:%
.100000000000
Utility L3L1 Read Lower Limit: % Utility L3L1
42169 Offset: 0 Voltage
Voltage % Only Upper Limit: % voltage %
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000
Utility Total kW Read Lower Limit: kW
42170 Offset: 0 Utility total kW Power
_32 bit Only Upper Limit: kW
Size (bits): 32
Default:
Sign: S
Multiplier:
Unit: kVAR
1.000000000000
Utility total Read Lower Limit: kVAR Utility total
42172 Offset: 0 Power
kVAR_32 bit Only Upper Limit: kVAR kVAR in 32 bit
Size (bits): 32
Default:
Sign: S

Copyright © 2023 Cummins Inc. 310 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: kVA
1.000000000000
Utility total Read Lower Limit: kVA Utility total kVA
42174 Offset: 0 Power
kVA_32 bit Only Upper Limit: kVA in 32 bit
Size (bits): 32
Default:
Sign: U
Multiplier:
Unit: kW Sum of
1.000000000000
System Total Read Lower Limit: kW generator bus
42176 Offset: 0 Power
kW_32 bit Only Upper Limit: kW and utility bus
Size (bits): 32 kW in 32 bit
Default:
Sign: S
Multiplier:
Unit: kVAR Sum of
1.000000000000
System Total Read Lower Limit: kVAR generator bus
42178 Offset: 0 Power
kVAR_32 bit Only Upper Limit: kVAR and utility bus
Size (bits): 32 kVAR in 32 bit
Default:
Sign: S
Multiplier:
Unit: kVA Sum of
1.000000000000
System Total Read Lower Limit: kVA generator set
42180 Offset: 0 Power
kVA_32 bit Only Upper Limit: kVA and utility bus
Size (bits): 32 kVA in 32 bit
Default:
Sign: U
Multiplier:
Unit: NA Number of
1.000000000000
Total Number Read Lower Limit: generator sets System
42200 Offset: 0
of Gensets Only Upper Limit: with non–zero Information
Size (bits): 16 rating entered
Default:
Sign: U
Multiplier:
Unit: kW
1.000000000000 Sum of the
Total System Read Lower Limit: kW System
42201 Offset: 0 generator set
Capacity Only Upper Limit: kW Information
Size (bits): 16 kW ratings
Default:
Sign: U

Multiplier: Sum of the


Unit: kW generator set
1.000000000000
Total Online Read Lower Limit: kW kW ratings for System
42202 Offset: 0
Capacity Only Upper Limit: kW generator sets Information
Size (bits): 16 which are
Default:
Sign: S Online
Multiplier:
Unit: seconds Countdown
Programmed .100000000000
Read Lower Limit: seconds value of the
42203 Transition Offset: 0 PTC Timers
Only Upper Limit: seconds programmed
Timer Size (bits): 16
Default: transition timer
Sign: U

A029X159 (Issue 31) 311 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: seconds
.100000000000 Countdown
Read Lower Limit: seconds
42204 Transfer Timer Offset: 0 value of the PTC Timers
Only Upper Limit: seconds
Size (bits): 16 transfer timer
Default:
Sign: U
Multiplier:
Unit: seconds
.100000000000 Countdown
Retransfer Read Lower Limit: seconds
42205 Offset: 0 value of the PTC Timers
Timer Only Upper Limit: seconds
Size (bits): 16 retransfer timer
Default:
Sign: U
Multiplier:
Unit: seconds Countdown
.100000000000
Maximum Read Lower Limit: seconds value of the
42206 Offset: 0 PTC Timers
Parallel Timer Only Upper Limit: seconds maximum
Size (bits): 16 parallel timer
Default:
Sign: U
Multiplier:
Unit: kW kW Control
1.000000000000
Read Lower Limit: kW reference value Master Load
42207 kW Reference Offset: 0
Only Upper Limit: kW for utility Control
Size (bits): 16 paralleling
Default:
Sign: S
0: Not Available
Utility 1: Not Unloaded Indicates utility
Read Master Load
42208 Unloaded unloaded
Only 2: Unloaded Control
Status status
Default:
0: Not Available Indicates
Genset 1: Not Unloaded
Read generator set Master Load
42209 Unloaded
Only 2: Unloaded unloaded Control
Status
Default: status

Copyright © 2023 Cummins Inc. 312 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Not Available
1: TD Start
2: TD Stop
3: TD Programmed Transition
4: TD Transfer
5: TD Retransfer
6: Synchronizing
7: Sync Check OK
8: Inhibit Indicates what
Read state the System
42210 System State 9: Unassigned
Only control is Information
10: Ramp Upload currently IN
11. Ramp Load
12: Manual
13: Utility Failure
14: Test
15: Standby
16: Factory Test
17: Extended Parallel
Default: Not Available
0: Manual
1: Normal Indicates the
2: Normal Override Current PTC
PTC Operating Read Operating PTC Operating
42211 3: Test
Mode Only mode. Read/ Mode
4: Utility Fail Write on comp
5: Extended Parallel mode.
Default:
Multiplier:
Unit: seconds
Active .100000000000 Countdown
Read Lower Limit: seconds
42212 Transition Offset: 0 timer value of PTC Timers
Only Upper Limit: seconds
Timer Size (bits): 16 active timer
Default:
Sign: U
Multiplier:
Unit: NA Indicates the
1.000000000000
Hardware Read Lower Limit: hardware
42213 Offset: 0 Discrete Inputs
Version Only Upper Limit: version of the
Size (bits): 16 board
Default:
Sign: U
Multiplier: Unit: seconds
1.000000000000 Lower Limit: .000 sec. Amount of time
Controller On Read Offset: 0 in seconds the Controller
42214 Upper Limit:
Time Only controller has Information
Size (bits): 32 4294967295.000 sec been powered
Sign: U Default: 0

A029X159 (Issue 31) 313 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Indicates
0: Not Available availability of
Genset 1: Available generator set
Read
42216 Availability for Loading, as PTC Availability
Only 2: Unknown
Status determined by
Default: the generator
set sensors
Indicates
0: Not Available availability of
Utility 1: Available utility for
Read
42217 Availability loading as PTC Availability
Only 2: Unknown
Status determined by
Default: the utility
sensors
0: Open
1: Closed Generator set
Gen CB Read
42218 breaker Breaker Control
Position Status Only 2: Not Available position
Default:
0: Open
Util CB Read 1: Closed Utility breaker
42219 Breaker Control
Position Status Only 2: Not Available position
Default:
Multiplier:
Unit: kVAR kVAR control
1.000000000000
kVAR Load Read Lower Limit: kVAR reference value Master Load
42220 Offset: 0
Reference Only Upper Limit: kVAR for extended Control
Size (bits): 16 paralleling
Default:
Sign: S
Multiplier: Engineering
kVAR Load Unit: %
.010000000000 units value for
Setpoint Engr Read Lower Limit: %
42221 Offset: 0 the kVAR load Analog Inputs
Units Display Only Upper Limit: %
Size (bits): 16 setpoint analog
Value Default:
Sign: U Input

Multiplier: Engineering
kW Load Unit: %
.010000000000 units value for
Setpoint Engr Read Lower Limit: %
42222 Offset: 0 the kW load Analog Inputs
Units Display Only Upper Limit: %
Size (bits): 16 setpoint analog
Value Default:
Sign: S input

Multiplier: Power factor


Unit: NA setpoint analog
.010000000000
Power Factor Read Lower Limit: input value
42223 Offset: 0 Analog Inputs
Setpoint Only Upper Limit: (uses kVAR
Size (bits): 16 load setpoint
Default:
Sign: S analog input)

Copyright © 2023 Cummins Inc. 314 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Not Enabled
Indicates the
1: No Source Connected connected
Read 2: Utility Connected state of power PTC State
42224 PTC State
Only 3: Genset Connected transfer Machine
4: Paralleled control. read /
write in comp.
Default:
Indicates
0: Not Allowed whether any
Sync Check Read Master Sync
42225 1: Allowed sync check
Close Allowed Only Control
Default: conditions
have been met
Multiplier:
Unit: degrees Utility to
.010000000000
Sync Phase Read Lower Limit: degrees generator set
42226 Offset: 0 Phase
Difference Only Upper Limit: degrees L1 voltage
Size (bits): 16 phase angle
Default:
Sign: S
0: Synchronizer Off Indicates state
Synchronizer Read Master Sync
42227 1: Synchronizer On of the
Status Only Control
Default: synchronizer

Faults have
0: Inactive occurred which
System Read prevent normal System
42228 1: Active
Lockout Status Only system Information
Default: operation;
reset faults
0: Open
1: Closed Indicates the
Breaker 1 Read Load Add Shed
42229 position status
Position Only 2: Not Available Control
of breaker 1
Default: Not Available
0: Open
1: Closed Indicates the
Breaker 2 Read Load Add Shed
42230 position status
Position Only 2: Not Available Control
of breaker 2
Default: Not Available
0: Open
1: Closed Indicates the
Breaker 3 Read Load Add Shed
42231 position status
Position Only 2: Not Available Control
of breaker 3
Default: Not Available
0: Open
1: Closed Indicates the
Breaker 4 Read Load Add Shed
42232 position status
Position Only 2: Not Available Control
of breaker 4
Default: Not Available

A029X159 (Issue 31) 315 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Open
1: Closed Indicates the
Breaker 5 Read Load Add Shed
42233 position status
Position Only 2: Not Available Control
of breaker 5
Default: Not Available
0: Open
1: Closed Indicates the
Breaker 6 Read Load Add Shed
42234 position status
Position Only 2: Not Available Control
of breaker 6
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 1 Trip Read Load Add Shed
42235 status of
Status Only 2: Tripped Control
breaker 1
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 2 Trip Read Load Add Shed
42236 status of
Status Only 2: Tripped Control
breaker 2
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 3 Trip Read Load Add Shed
42237 status of
Status Only 2: Tripped Control
breaker 3
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 4 Trip Read Load Add Shed
42238 status of
Status Only 2: Tripped Control
breaker 4
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 5 Trip Read Load Add Shed
42239 status of
Status Only 2: Tripped Control
breaker 5
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 6 Trip Read Load Add Shed
42240 status of
Status Only 2: Tripped Control
breaker 6
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42241 ATS 1 Position position status
Only 3: Source 2 Connected Control
of ATS 1
4: Paralleled
Default: Not Available

Copyright © 2023 Cummins Inc. 316 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42242 ATS 2 Position position status
Only 3: Source 2 Connected Control
of ATS 2
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42243 ATS 3 Position position status
Only 3: Source 2 Connected Control
of ATS 3
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42244 ATS 4 Position position status
Only 3: Source 2 Connected Control
of ATS 4
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42245 ATS 5 Position position status
Only 3: Source 2 Connected Control
of ATS 5
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42246 Position position status
Only 3: Source 2 Connected Control
of ATS 6
4: Paralleled
Default: Not Available
0: Missing
1: Good Indicates
Read 2: Connecting status of SID1
42247 SID1 Status Communications
Only 3: No EXP Board (AUX 101 / 102
4: Not Applicable module 1)
Default:
0: Missing
1: Good Indicates
Read 2: Connecting status of SID0
42248 SID0 Status Communications
Only 3: No EXP Board (AUX 101 / 102
4: Not Applicable module 0)
Default:

A029X159 (Issue 31) 317 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Indicates the
Expansion 0: Disable status of SIDO
Board Read
42249 1: Enable to expansion Communications
Communication Only
Default: Disable board
s
connection
Multiplier:
Unit: NA
1.000000000000 Indicates the
Current Add Read Lower Limit: Load Add Shed
42250 Offset: 0 next level to
Level Only Upper Limit: Control
Size (bits): 16 add
Default:
Sign: U
Multiplier:
Unit: NA
1.000000000000 Indicates the
Current Shed Read Lower Limit: Load Add Shed
42251 Offset: 0 next level to
Level Only Upper Limit: Control
Size (bits): 16 shed
Default:
Sign: U
0: Do Nothing Indicates
Add Level 1 Read Load Add Shed
42252 1: Add Level status of add
Command Only Control
Default: Do Nothing level 1

0: Do Nothing Indicates
Add Level 2 Read Load Add Shed
42253 1: Add Level status of add
Command Only Control
Default: Do Nothing level 2

0: Do Nothing Indicates
Add Level 3 Read Load Add Shed
42254 1: Add Level status of add
Command Only Control
Default: Do Nothing level 3

0: Do Nothing Indicates
Add Level 4 Read Load Add Shed
42255 1: Add Level status of add
Command Only Control
Default: Do Nothing level 4

0: Do Nothing Indicates
Add Level 5 Read Load Add Shed
42256 1: Add Level status of add
Command Only Control
Default: Do Nothing level 5

0: Do Nothing Indicates
Add Level 6 Read Load Add Shed
42257 1: Add Level status of add
Command Only Control
Default: Do Nothing level 6

0: Do Nothing Indicates
Shed Level 1 Read Load Add Shed
42258 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 1

0: Do Nothing Indicates
Shed Level 2 Read Load Add Shed
42259 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 2

0: Do Nothing Indicates
Shed Level 3 Read Load Add Shed
42260 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 3

Copyright © 2023 Cummins Inc. 318 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Shed Level 4 Read Load Add Shed
42261 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 4

0: Do Nothing Indicates
Shed Level 5 Read Load Add Shed
42262 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 5

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42263 Level 1 1: Add Level
Only to add level 1 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42264 Level 2 1: Add Level
Only to add level 2 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42265 Level 3 1: Add Level
Only to add level 3 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42266 Level 4 1: Add Level
Only to add level 4 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42267 Level 5 1: Add Level
Only to add level 5 Control
Command Default: Do Nothing

Manual Add 0: Do Nothing


Read Operator input Load Add Shed
42268 Level 6 1: Add Level
Only to add level 6 Control
Command Default: Do Nothing

0: Do Nothing Operator input


Manual Shed
Read to shed loads Load Add Shed
42269 Level 1 1: Add Level
Only assigned to Control
Command Default: Do Nothing level 1

0: Do Nothing Operator input


Manual Shed
Read to shed loads Load Add Shed
42270 Level 2 1: Add Level
Only assigned to Control
Command Default: Do Nothing level 2

0: Do Nothing Operator input


Manual Shed
Read to shed loads Load Add Shed
42271 Level 3 1: Add Level
Only assigned to Control
Command Default: Do Nothing level 3

0: Do Nothing Operator input


Manual Shed
Read to shed loads Load Add Shed
42272 Level 4 1: Add Level
Only assigned to Control
Command Default: Do Nothing level 4

0: Do Nothing Operator Input


Manual Shed
Read to Shed Loads Load Add Shed
42273 Level 5 1: Add Level
Only Assigned to Control
Command Default: Do Nothing Level 5

A029X159 (Issue 31) 319 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function

0: Do Nothing Indicates if
Restored Shed
Read shed level 1 Load Add Shed
42274 Level 1 1: Add Level
Only has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restored Shed
Read shed level 2 Load Add Shed
42275 Level 2 1: Add Level
Only has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restored Shed
Read shed level 3 Load Add Shed
42276 Level 3 1: Add Level
Only has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restored Shed
Read shed level 4 Load Add Shed
42277 Level 4 1: Add Level
Only has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restored Shed
Read shed level 5 Load Add Shed
42278 Level 5 1: Add Level
Only has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates add
Add Load 1 Read Load Add Shed
42279 1: Add Level command for
Command Only Control
Default: Do Nothing load 1

0: Do Nothing Indicates add


Add Load 2 Read Load Add Shed
42280 1: Add Level command for
Command Only Control
Default: Do Nothing load 2

0: Do Nothing Indicates add


Add Load 3 Read Load Add Shed
42281 1: Add Level command for
Command Only Control
Default: Do Nothing load 3

0: Do Nothing Indicates add


Add Load 4 Read Load Add Shed
42282 1: Add Level command for
Command Only Control
Default: Do Nothing load 4.

0: Do Nothing Indicates add


Add Load 5 Read Load Add Shed
42283 1: Add Level command for
Command Only Control
Default: Do Nothing load 5

0: Do Nothing Indicates add


Add Load 6 Read Load Add Shed
42284 1: Add Level command for
Command Only Control
Default: Do Nothing load 6

0: Do Nothing Indicates shed


Shed Load 1 Read Load Add Shed
42285 1: Add Level command for
Command Only Control
Default: Do Nothing load 1

0: Do Nothing Indicates shed


Shed Load 2 Read Load Add Shed
42286 1: Add Level command for
Command Only Control
Default: Do Nothing load 2

Copyright © 2023 Cummins Inc. 320 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates shed
Shed Load 3 Read Load Add Shed
42287 1: Add Level command for
Command Only Control
Default: Do Nothing load 3

0: Do Nothing Indicates Shed


Shed Load 4 Read Load Add Shed
42288 1: Add Level Command for
Command Only Control
Default: Do Nothing Load 4

0: Do Nothing Indicates shed


Shed Load 5 Read Load Add Shed
42289 1: Add Level command for
Command Only Control
Default: Do Nothing load 5

0: Do Nothing Indicates shed


Shed Load 6 Read Load Add Shed
42290 1: Add Level command for
Command Only Control
Default: Do Nothing load 6

Multiplier: Engineering
Unit: VDC
Battery Voltage .010000000000 units value for
Read Lower Limit: VDC
42291 Engr Units Offset: 0 the battery Analog Inputs
Only Upper Limit: VDC
Display Value Size (bits): 16 voltage analog
Default Input
Sign: U
Multiplier: Voltage level
kVAR Master Unit: VDC
.010000000000 commanded to
Load Control Read Lower Limit: VDC
42292 Offset: 0 kVAR Master Analog Inputs
Output Only Upper Limit: VDC
Size (bits): 16 load control
Predictor Value Default
Sign: S analog output

Multiplier: Voltage level


kW Master Unit: VDC
.010000000000 commanded to
Load Control Read Lower Limit: VDC
42293 Offset: 0 kW Master Analog Inputs
Output Only Upper Limit: VDC
Size (bits): 16 load control
Predictor Value Default
Sign: S analog output

Multiplier: Voltage level


Master Unit: VDC
.010000000000 commanded to
Frequency Read Lower Limit: VDC
42294 Offset: 0 Master Analog Inputs
Bias Output Only Upper Limit: VDC
Size (bits): 16 frequency bias
Predictor Value Default
Sign: S analog output

Multiplier: Voltage level


Unit: VDC
Master Voltage .010000000000 commanded to
Read Lower Limit: VDC
42295 Bias Output Offset: 0 Master voltage Analog Inputs
Only Upper Limit: VDC
Predictor Value Size (bits): 16 bias analog
Default output
Sign: S

A029X159 (Issue 31) 321 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Manual
1: Normal Indicates the
PTC Genset 2: Normal Override current
Read PTC Genset
42296 Operating 3: Test operating
Only Operating Mode
Mode 4: Utility Fail mode of the
5: Extended Parallel generator set
Default
0: Manual
1: Normal Indicates the
PTC Transfer 2: Normal Override current
Read PTC Genset
42297 Pair Operating 3: Test operating
Only Operating Mode
Mode 4: Utility Fail mode of the
5: Extended Parallel transfer pair
Default:
Indicates the
0: Open Transition transition type
1: Hard Closed Transition currently
PTC Operating Read PTC Genset
42298 applicable to
Transition Type Only 2: Soft Closed Transition Operating Mode
the PTC
Default: function
operation

Addr. System Name Access Specifications Description Function


Indicates the
Expansion 0: Disabled status of the
Board Read SID1 to
42299 1: Enabled Communications
Communication Only expansion
s1 Default: Disabled board
connection
0: Master Synchronize Only
1: Isolated Bus w/ out GM Main setting:
2: Isolated Bus w/GM sets system
System Read/ topology; Application
42300 3: Common Bus
Topology Write control must be Configuration
4: Transfer Pair in manual to
5: Component Mode set
Default: Master Synchronize Only
0: Open Transition Sets the type
Read/ 1: Hard Closed Transition of transition Application
42301 Transition Type
Write 2: Soft Closed Transition that will be Configuration
Default: Open Transition used

0: Disabled Use to enable


Extended Read/ extended Application
42302 1: Enabled
Parallel Enable Write paralleling Configuration
Default: Disabled operation

Copyright © 2023 Cummins Inc. 322 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: None
Load Demand Read/ 1: Fixed Sequence Sets the load Load Demand
42303
Type Write 2: Run Hours demand type Control
Default: None
0: Manual
Priority Control Read/ Set the priority
42304 1: Automatic Priority Control
Method Write control method
Default: Manual
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 01 kW Read/ Offset: 0 Sets generator System
42305 Upper Limit:
Rating Write 1 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 1000
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 02 kW Read/ Offset: 0 Sets generator System
42306 Upper Limit:
Rating Write 2 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 03 kW Read/ Offset: 0 Sets generator System
42307 Upper Limit:
Rating Write 3 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 04 kW Read/ Offset: 0 Sets generator
42308 Upper Limit: PC 3.x
Rating Write 4 kW rating
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 05 kW Read/ Offset: 0 Sets generator System
42309 Upper Limit:
Rating Write 5 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 06 kW Read/ Offset: 0 Sets generator System
42310 Upper Limit:
Rating Write 6 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 07 kW Read/ Offset: 0 Sets generator System
42311 Upper Limit:
Rating Write 7 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0

A029X159 (Issue 31) 323 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 08 kW Read/ Offset: 0 Sets generator System
42312 Upper Limit:
Rating Write 8 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 09 kW Read/ Sets generator System
42313 Offset: 0 Upper Limit:
Rating Write 9 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0

Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 10 kW Read/ Offset: 0 Sets generator System
42314 Upper Limit:
Rating Write 10 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 11 kW Read/ Sets generator System
42315 Offset: 0 Upper Limit:
Rating Write 11 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0

Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 12 kW Read/ Offset: 0 Sets generator System
42316 Upper Limit:
Rating Write 12 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Unit: Seconds
Multiplier:
.100000000000 Lower Limit: .000 Set the
Programmed Seconds
Read/ Offset: 0 programmed
42317 Transition PTC Timers
Write Upper Limit: 60.000 transition time
Delay (TDPT) Size (bits): 16
Seconds delay
Sign: U
Default: 3
Unit: Seconds
Multiplier:
.100000000000 Lower Limit: .000
Seconds Sets the
Transfer Delay Read/ Offset: 0
42318 transfer time PTC Timers
(TDNE) Write Upper Limit: 120.000
Size (bits): 16 delay
Seconds
Sign: U
Default: 10
Unit: Seconds
Multiplier:
.100000000000 Lower Limit: .000
Seconds Sets the
Retransfer Read/ Offset: 0
42319 transfer time PTC Timers
Delay (TDEN) Write Upper Limit: 1800.000
Size (bits): 16 delay
Seconds
Sign: U
Default: 600

Copyright © 2023 Cummins Inc. 324 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Unit: Seconds
Multiplier: Sets the
.100000000000 Lower Limit: .000
Maximum Seconds maximum
Read/ Offset: 0
42320 Parallel Time parallel time for PTC Timers
Write Upper Limit: 1800.000
(TDMP) Size (bits): 16 soft load
Seconds transfers
Sign: U
Default: 20
Multiplier:
Unit: %
.010000000000 Generator set
Genset Bus Read/ Lower Limit: -5.000% Master Load
42321 Offset: 0 nominal
%kW Setpoint Write Upper Limit: 105.000% voltage Control
Size (bits): 16
Default: 80
Sign: S
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Genset Volts Generator set
Read/ Offset: 0
42322 Nominal nominal AC Setup
Write Upper Limit:
Voltage Size (bits): 16 voltage
45000.000 Volts
Sign: U
Default: 480
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Utility Nominal Read/ Volts Utility nominal
42323 Offset: 0 AC Setup
Voltage Write Upper Limit: voltage
Size (bits): 16
45000.000 Volts
Sign: U
Default: 480
Multiplier: Sets the center
Unit: Hz
.100000000000
Genset Center Read/ Lower Limit: 45.000 Hz frequency
42324 Offset: 0 sensor PTC Sensors
Frequency Write Upper Limit: 65.000 Hz bandwidth
Size (bits): 16
Default: 60 settings
Sign: U
Multiplier: Sets the center
Unit: Hz
.100000000000
Utility Center Read/ Lower Limit: 45.000 Hz frequency
42325 Offset: 0 sensor PTC Sensors
Frequency Write Upper Limit: 65.000 Hz bandwidth
Size (bits): 16
Default: 60 settings
Sign: U

0: Disable Use to enable


test With Load Read/ or disable load Application
42326 1: Enable
Enable Write transfer during Configuration
Default: Disable a Test
Multiplier:
Unit: Hz Use to define
.100000000000
System Read/ Lower Limit: 45.000 Hz the system System
42327 Offset: 0
Frequency Write Upper Limit: 65.000 Hz nominal Information
Size (bits): 16 frequency
Default: 60
Sign: U

A029X159 (Issue 31) 325 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Selects where
0: Internal the generator
Genset Bus
Read/ set kW setpoint Master Load
42328 kW Setpoint 1: Analog Input
Write will come from Control
Source Default Internal for extended
paralleling
Selects where
the generator
Genset Bus 0: Internal set kVAR
Read/ Master Load
42329 kVAR Setpoint 1: Analog Input setpoint will
Write Control
Source Default Internal come from for
extended
paralleling

Multiplier: Unit: kW Set the base


1.000000000000 Lower Limit: .000 kW load kW
Genset Bus Read/ Offset: 0 setpoint in Master Load
42330 Upper Limit:
kW Setpoint Write closed loop Control
Size (bits): 16 32767.000 kW extended
Sign: S Default: 0 paralleling
Unit: kVAR Sets the base
Multiplier:
1.000000000000 Lower Limit: .000 load kVAR
Genset Bus Read/ kVAR setpoint in Master Load
42331 Offset: 0
kVAR Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kVAR
Sign: S paralleling
Default: 0

Multiplier: Sets % kVAR


Unit: % generator
.010000000000
Genset Bus % Read/ Lower Limit: -5.000% output level for Master Load
42332 Offset: 0
kVAR Setpoint Write Upper Limit: 105.000% open loop base Control
Size (bits): 16 load extended
Default: 0
Sign: S paralleling
Sets the
Multiplier: desired
Unit: NA
Genset Bus .010000000000 generator set
Read/ Lower Limit: .700 Master Load
42333 Power Factor Offset: 0 bus power
Write Upper Limit: 1.000 Control
Setpoint Size (bits): 16 factor in closed
Default: 1.00 loop extended
Sign: S
paralleling
Unit: kW
Multiplier:
1.000000000000 Lower Limit:
Genset -32768.000kW Setpoint for
Read/ Offset: 0 Master Load
42334 Unloaded generator set
Write Upper Limit: Control
Level Size (bits): 16 unloaded level
32767.000 kW
Sign: S
Default: 50

Copyright © 2023 Cummins Inc. 326 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Selects where
0: Internal the utility kW
Utility Bus kW
Read/ setpoint will Master Load
42335 Setpoint 1: Analog Input
Write come from for Control
Source Default: Internal extended
paralleling
Selects where
0: Internal the utility kVAR
Utility Bus
Read/ setpoint will Master Load
42336 kVAR Setpoint 1: Analog Input
Write come from for Control
Source Default: Internal extended
paralleling
Unit: kW Sets the peak
Multiplier:
1.000000000000 Lower Limit: Shave kW
Utility Bus kW Read/ -32768.000kW setpoint in Master Load
42337 Offset: 0
Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kW
Sign: S paralleling
Default: 100
Unit: kW
Multiplier: Sets the utility
1.000000000000 Lower Limit:
Utility Bus kW -32768.000kW kW constraint
Read/ Offset: 0 Master Load
42338 Constraint level for base
Write Upper Limit: Control
Level Size (bits): 16 load extended
32767.000 kW paralleling
Sign: S
Default: 100
Unit: kW Sets the peak
Multiplier:
1.000000000000 Lower Limit: shave kVAR
Utility Bus Read/ -32768.000 kVAR setpoint in Master Load
42339 Offset: 0
kVAR Setpoint Write Upper Limit: closed loop Control
Size (bits): 16 extended
32767.000 kVAR
Sign: S paralleling
Default: 100

Multiplier: Sets the


Unit: NA desired utility
Utility Bus .010000000000
Read/ Lower Limit: .700 bus power Master Load
42340 Power Factor Offset: 0
Write Upper Limit: 1.000 factor in loop Control
Setpoint Size (bits): 16
Default: 1.00 extended
Sign: S paralleling
Unit: kW
Multiplier:
1.000000000000 Lower Limit:
Utility -32768.000kW Setpoint for
Read/ Offset: 0 Master Load
42341 Unloaded utility unloaded
Write Upper Limit: Control
Level Size (bits): 16 level
32767.000 kW
Sign: S
Default: 50

0: Inactive Use to
Clear Fault Read/ completely Fault and Event
42342 1: Active
History Table Write clear the fault Info
Default: Inactive history table

A029X159 (Issue 31) 327 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Use to
completely
0: Inactive clear the
Clear
Read/ counters in Fault and Event
42343 Occurrence 1: Active
Write faults and Info
Tables Default: Inactive events
occurrence
tables
Use to
0: Do Nothing permanently
Genset Reset
Read/ clear all
42344 All Energy 1: Clear Counters Energy
Write generator set
Meters Default: Do Nothing energy meter
values
Use to
0: Do Nothing permanently
Utility Reset All Read/
42345 1: Clear Counters clear all utility Energy
Energy Meters Write
Default: Do Nothing energy meter
values

0: Genset Bus % Level (Open Loop) Sets how and


1: Genset Bus kW (Closed Loop) where the kW
Extended
will be
Paralleling kW Read/ 2: Genset Bus kW w/ Utility Constraint Master Load
42346 controlled for
Load Control Write (Closed Loop) Control
extended
Type 3: Utility Bus kW (Closed Loop) parallel
Default: Genset Bus % Level (Open Loop) operation
0: Genset Controllers
1: Genset Bus % Level (Open Loop) Sets how and
2: Genset Bus Power Factor (Open Loop) where the
Extended
3: Genset Bus kVAR (Closed Loop) kVAR will be
Paralleling Read/ Master Load
42347 controlled for
kVAR Load Write 4: Genset Bus Power Factor (Closed Loop) Control
extended
Control Type 5: Utility Bus kVAR (Closed Loop) parallel
6: Utility Bus Power Factor (Closed Loop) operation
Default: Genset Controllers
Unit: seconds
Multiplier:
.10000000000 Lower Limit: 10.000 Set ramp load
Extended seconds
Read/ Offset: 0 time for Master Load
42348 Parallel Ramp
Write Upper Limit: 900.000 extended Control
Load Time Size (bits): 16
seconds paralleling
Sign: U
Default:60

0:Disabled Enable if want


Fail To Sync Read/ synchronizing Master Sync
42349 1:Enabled
Lockout Enable Write to stop if fail to Control
Default: Disable sync occurs

Copyright © 2023 Cummins Inc. 328 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Fail To Sync Use to enable
Open 0:Disabled or disable an
Read/ PTC State
42350 Transition 1:Enabled open transition
Write Machine
Retransfer Default: Disable retransfer upon
Enable fail to sync
Unit: seconds
Multiplier:
.200000000000 Lower Limit: 10.000 Set the fill to
Fail To seconds
Read/ Offset: 0 synchronize Master Sync
42351 Synchronize
Write Upper Limit: 900.000 diagnostic time Control
Time Size (bits): 16
seconds delay
Sign: U
Default:120
In manual
0: Closed Requested mode can be
1: No Command used to semi-
Gen CB Read/
42352 manually Breaker Control
Manual Control Write 2: Open Commanded control the
Default: No Command generator set
breaker
In Manual
0: Closed Requested Mode can be
Util CB Manual Read/ 1: No Command used to Semi-
42353 Breaker Control
Control Write 2: Open Commanded Manually
Default: No Command Control the
Utility Breaker

Multiplier: Sets the


Unit: seconds Synchronizer
.001000000000
Read/ Lower Limit: -3.000 Hz Slip Frequency Master Sync
42354 Slip Frequency Offset: 0
Write Upper Limit: 3.000 Hz (used when Control
Size (bits): 16 Sync Method is
Default:0.1
Sign: S Slip)
Unit: seconds
Multiplier:
.100000000000 Lower Limit: .000 Sets the
Start Time Read/ seconds generator set PTC Operating
42355 Offset: 0
Delay (TDES) Write Upper Limit: 3600.000 Start Time Mode
Size (bits): 16 Delay
seconds
Sign: U
Default: 0
Unit: seconds
Multiplier:
.100000000000 Lower Limit: .000 Sets the
Stop Time Read/ seconds generator set PTC Operating
42356 Offset: 0
Delay (TDEC) Write Upper Limit: 3600.000 Stop Time Mode
Size (bits): 16 Delay
seconds
Sign: U
Default: 0
0: Normal Use to Invert
Synchronizer Read/ Master Sync
42357 1: Invert Synchronizer
Polarity Write Control
Default: Normal Polarity

A029X159 (Issue 31) 329 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Phase Match Sets the
Synchronize Read/ Master Sync
42358 1: Slip Frequency synchronizing
Method Write Control
Default: Phase Match method

Allows protocol
0: PCCNet of the PCCNet
Port Protocol Read/ port to be
42359 1: MON Communications
Selection Write changed to
Default: PCCNet MON for
troubleshooting

0: Disabled Use to enable


System
Read/ or disable the System
42360 Scheduler 1: Enabled
Write system Scheduler
Enable Default: Disabled scheduler

0: Disabled Use the enable


Load Add Shed Read/ or disable the Load Add Shed
42361 1: Enabled
Enable Write load add shed Control
Default: Disabled feature
Use to enable
Open
0: Disabled or disable the
Transition
Read/ shedding of Load Add Shed
42362 Retransfer 1: Enabled
Write loads during Control
Load Shed Default: Disabled open transition
Enable
retransfer
Indicates
Auto/Manual 0: Auto automatic or
Read/ Load Add Shed
42363 Load Add 1: Manual manual load
Write Control
Restore Mode Default: Auto add restore
operation
Unit: second Indicates delay
Multiplier:
1.000000000000 Lower Limit: .000 between add
Genset Bus second
Read/ Offset: 0 levels when all Load Add Shed
42364 Load Add
Write Upper Limit: 60.000 generator sets Control
Delay Size (bits): 16
second are online and
Sign: U no utility
Default: 1
Unit: second
Multiplier:
1.000000000000 Lower Limit: .000 Indicates delay
Utility Bus second
Read/ Offset: 0 between add Load Add Shed
42365 Load Add
Write Upper Limit: 60.000 levels when on Control
Delay Size (bits): 16
second utility
Sign: U
Default: 1
Unit: seconds
Multiplier:
1.000000000000 Lower Limit: 1.000 Indicates delay
Load Shed Read/ seconds between shed Load Add Shed
42366 Offset: 0
Delay Write Upper Limit: 10.000 levels when on Control
Size (bits): 16 generator sets
seconds
Sign: U
Default: 1

Copyright © 2023 Cummins Inc. 330 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Indicates type
0: None of load
Load 1 Device Read/ 1: Breaker connected to Load Add Shed
42367
Type Write 2: ATS load 1 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 2 Device Read/ 1: Breaker connected to Load Add Shed
42368
Type Write 2: ATS load 2 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 3 Device Read/ 1: Breaker connected to Load Add Shed
42369
Type Write 2: ATS load 3 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 4 Device Read/ 1: Breaker connected to Load Add Shed
42370
Type Write 2: ATS load 4 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 5 Device Read/ 1: Breaker connected to Load Add Shed
42371
Type Write 2: ATS load 5 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 6 Device Read/ 1: Breaker connected to Load Add Shed
42372
Type Write 2: ATS load 6 add Control
Default: None shed control
and status I/O
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 1 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42373 Offset: 0
Level Write Upper Limit: 18.000 1 is assigned Control
Size (bits): 16 to
Default: 1
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 2 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42374 Offset: 0
Level Write Upper Limit: 18.000 2 is assigned Control
Size (bits): 16 to
Default: 2
Sign: U

A029X159 (Issue 31) 331 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 3 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42375 Offset: 0
Level Write Upper Limit: 18.000 3 is assigned Control
Size (bits): 16 to
Default: 3
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 4 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42376 Offset: 0
Level Write Upper Limit: 18.000 4 is assigned Control
Size (bits): 16 to
Default: 4
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 5 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42377 Offset: 0
Level Write Upper Limit: 18.000 5 is assigned Control
Size (bits): 16 to
Default: 5
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 6 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42378 Offset: 0
Level Write Upper Limit: 18.000 6 is assigned Control
Size (bits): 16 to
Default: 6
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 1 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42379 Offset: 0
Level Write Upper Limit: 17.000 1 is assigned Control
Size (bits): 16 to
Default: 1
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 2 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42380 Offset: 0
Level Write Upper Limit: 17.000 2 is assigned Control
Size (bits): 16 to
Default: 2
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 3 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42381 Offset: 0
Level Write Upper Limit: 17.000 3 is assigned Control
Size (bits): 16 to
Default: 3
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 4 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42382 Offset: 0
Level Write Upper Limit: 17.000 4 is assigned Control
Size (bits): 16 to
Default: 4
Sign: U

Copyright © 2023 Cummins Inc. 332 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 5 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42383 Offset: 0
Level Write Upper Limit: 17.000 5 is assigned Control
Size (bits): 16 to
Default: 5
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 6 Shed Read/ Lower Limit: 1.000 shed level load Load Add Shed
42384 Offset: 0
Level Write Upper Limit: 17.000 6 is assigned Control
Size (bits): 16 to
Default: 6
Sign: U
Use to choose
0: Both kW and Frequency method for
Genset Bus 1: kW Only
Read/ determining System
42385 Overload
Write 2: Frequency Only generator bus Information
Method
Default: Both kW and Frequency overload
condition

Multiplier: Use to set


Unit: % the % kW
Genset Bus 1.000000000000
Read/ Lower Limit: 80.000% threshold for System
42386 kW Overload Offset: 0
Write Upper Limit: 140.000% generator bus Information
Delay Size (bits): 16
Default: 105 overload
Sign: U condition
Unit: second
Multiplier:
1.000000000000 Lower Limit: .000 Sets the delay
Genset Bus second
Read/ Offset: 0 time for System
42387 kW Overload
Write Upper Limit: 120.000 overload based Information
Delay Size (bits): 16
second on kW
Sign: U
Default: 60

Multiplier: Use to set the


Genset Bus Unit: Hz underfrequency
1.000000000000
Underfrequenc Read/ Lower Limit: .1000 Hz offset threshold System
42388 Offset: 0
y Overload Write Upper Limit: 10.000 Hz for generator Information
Threshold Size (bits): 16 bus overload
Default: 3
Sign: U condition
Unit: second
Multiplier:
Genset Bus 1.000000000000 Lower Limit:.000 Sets the delay
Underfrequenc Read/ second time for System
42389 Offset: 0
y Overload Write Upper Limit: 20.000 overload based Information
Delay Size (bits): 16 on frequency
second
Sign: U
Default: 3

0: Disable Use enable or


Load Demand Read/ disable the Load Demand
42390 1: Enable
Enable Write load demand Control
Default: Disable feature

A029X159 (Issue 31) 333 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenA
Load Demand Read/ (never stop) for Load Demand
42391 8: Gen9
GenA Write fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen1
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenB
Load Demand Read/ (never stop) for Load Demand
42392 8: Gen9
GenB Write fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen2

Copyright © 2023 Cummins Inc. 334 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenC
Load Demand Read/ (never stop) for Load Demand
42393 8: Gen9
GenC Write fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen3
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenD
Load Demand Read/ (never stop) for Load Demand
42394 8: Gen9
GenD Write fixed sequence Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen4
Unit: minute
Multiplier: Sets the Initial
1.000000000000 Lower Limit: 1.000
minute delay time
Load Demand Read/ Offset: 0 Load Demand
42395 before load
Initial Delay Write Upper Limit: 60.000 Control
Size (bits): 16 demand will
minute operate
Sign: U
Default: 5
Multiplier: Sets load
Unit: %
Load Demand 1.000000000000 demand restart
Read/ Lower Limit: 20.000% Load Demand
42396 Restart Offset: 0 threshold when
Write Upper Limit: 100.000% Control
Percent Size (bits): 16 method is
Default: 80 %kW
Sign: U

A029X159 (Issue 31) 335 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Unit: Hours Sets run hours
Multiplier:
1.000000000000 Lower Limit: 1.000 differential for
Load Demand Hours
Read/ Offset: 0 restart a Load Demand
42397 Run Hours
Write Upper Limit: 500.000 generator set Control
Differential Size (bits): 16
Hours stopped due to
Sign: U load demand
Default: 50
Unit: minute Sets the delay
Multiplier:
1.000000000000 Lower Limit: 1.000 time between
Load Demand minute
Read/ Offset: 0 stopping Load Demand
42398 Shutdown
Write Upper Limit: 60.000 generator sets Control
Delay Size (bits): 16
minute due to load
Sign: U demand
Default: 5

Multiplier: Unit: % Sets load


1.000000000000 Lower Limit: 20.000 % demand
Load Demand
Read/ Offset: 0 shutdown Load Demand
42399 Shutdown Upper Limit: 100.000
Write threshold when Control
Percent Size (bits): 16 % method is
Sign: U Default: 60 %kW

Unit: seconds Sets how long


Multiplier: to wait for a
1.000000000000 Lower Limit: 10.000
seconds generator set
General Fail Read/ Offset: 0 Load Demand
42400 to come online
Time Delay Write Upper Limit: 900.000 Control
Size (bits): 16 before
second declaring it
Sign: U
Default: 59 failed
Unit: seconds
Multiplier:
.020000000000 Lower Limit: .100 Sets the utility
Util CB Fail to Read/ seconds breaker fail to
42401 Offset: 0 Breaker Control
Close Delay Write Upper Limit: 1.000 close time
Size (bits): 16 delay
seconds
Sign: U
Default: 0.26
Unit: seconds
Multiplier:
.200000000000 Lower Limit: .200 Sets the utility
Util CB Fail to Read/ seconds breaker fail to
42402 Offset: 0 Breaker Control
Open Delay Write Upper Limit: 5.000 open time
Size (bits): 16 delay
seconds
Sign: U
Default: 1
Unit: seconds
Multiplier:
.020000000000 Lower Limit: .000 Sets time to
Util CB seconds
Read/ Offset: 0 allow for utility
42403 Recharge Breaker Control
Write Upper Limit: 60.000 breaker
Delay Size (bits): 16
seconds recharge
Sign: U
Default: 10

Copyright © 2023 Cummins Inc. 336 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Unit: seconds
Multiplier: Sets the
.020000000000 Lower Limit: .100
seconds generator Set
Gen CB Fail to Read/ Offset: 0
42404 breaker fail to Breaker Control
Close Delay Write Upper Limit: 1.000
Size (bits): 16 close time
seconds delay
Sign: S
Default: 0.26
Unit: seconds
Multiplier:
.200000000000 Lower Limit: .200 Sets generator
Gen CB Fail to Read/ seconds set breaker fail
42405 Offset: 0 Breaker Control
Open Delay Write Upper Limit: 5.000 to open time
Size (bits): 16 delay
seconds
Sign: U
Default: 1
Unit: seconds
Multiplier: Sets the time
.020000000000 Lower Limit: .000
Gen CB seconds to allow for
Read/ Offset: 0
42406 Recharge generator set Breaker Control
Write Upper Limit: 60.000
Delay Size (bits): 16 breaker
second recharge
Sign: U
Default: 10
Unit: degrees Sets the
Multiplier:
.010000000000 Lower Limit: .100 permissive +/-
Permissive Read/ degrees phase angle Master Sync
42407 Offset: 0
Phase Window Write Upper Limit: 20.000 window for Control
Size (bits): 16 sync check
degrees
Sign: S function
Default: 10
Sets the
Multiplier: permissive +/-
Unit: %
Permissive .100000000000 voltage
Read/ Lower Limit: .500 % Master Sync
42408 Voltage Offset: 0 acceptance
Write Upper Limit: 10.000 % Control
Window Size (bits): 16 window for
Default: 5 sync check
Sign: U
function
Unit: seconds Sets the
Multiplier:
.020000000000 Lower Limit: .500 permissive
Permissive Read/ seconds acceptance Master Sync
42409 Offset: 0
Window Time Write Upper Limit: 5.000 window dwell Control
Size (bits): 16 time for sync
seconds
Sign: U check function
Default: 0.5

Multiplier: Sets maximum


Unit: Hz frequency
Permissive .001000000000
Read/ Lower Limit: .001 Hz difference Master Sync
42410 Frequency Offset: 0
Write Upper Limit: 1.000 Hz allowed for Control
Window Size (bits): 32
Default: 1 permissive
Sign: U close

A029X159 (Issue 31) 337 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Unit: degrees Sets a sync
Multiplier:
.010000000000 Lower Limit: -50.000 phase offset to
Sync Phase Read/ degrees accommodate Master Sync
42412 Offset: 0
Offset Write Upper Limit: 50.000 sync across Control
Size (bits): 16 transformer
degrees
Sign: S with phase shift
Default: 0

0: L1-L2-L3 Defines what


System Phase Read/ the system System
42413 1: L1-L3-L2
Rotation Write phase rotation Information
Default: L1-L2-L3 sequence is

Multiplier: Proportional
Unit: NA gain for kW
1.00000000000
Read/ Lower Limit: .000 closed loop Master Load
42414 kW Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 60
Sign: U paralleling
Multiplier: Integral gain
Unit: NA
1.00000000000 for kW closed
Read/ Lower Limit: .000 Master Load
42415 kW KI Offset: 0 loop control in
Write Upper Limit: 255.000 Control
Size (bits): 16 extended
Default: 60 paralleling
Sign: U

Multiplier: Proportional
Unit: NA gain for kVAR
.100000000000
Read/ Lower Limit: .000 closed loop Master Load
42416 kVAR Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 120
Sign: U paralleling

Multiplier: Integral gain


Unit: NA for kVAR
1.00000000000
Read/ Lower Limit: .000 closed loop Master Load
42417 kVAR K1 Offset: 0
Write Upper Limit: 255.000 control in Control
Size (bits): 16 extended
Default: 50
Sign: U paralleling
Multiplier:
Unit: NA Selects which
1.00000000000
Scheduler Read/ Lower Limit: 1.000 scheduler System
42418 Offset: 0
Program Select Write Upper Limit: 12.000 program to Scheduler
Size (bits): 16 view or edit
Default: 1
Sign: U

0: Disable Use to enable


Scheduler
Read/ or disable the System
42419 Program 1: Enable
Write selected Scheduler
Enable Default: Disable program

Copyright © 2023 Cummins Inc. 338 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Once
1: Every Week
2: Every 2 Weeks
3: Every 3 Weeks
Scheduler 4: Every 4 Weeks use to adjust
Program x Read/ 5: Every 5 Weeks repeat interval System
42420
Repeats Write 6: First Week of the Month for the selected Scheduler
Interval 7: Second Week of the Month program
8: Third Week of the Month
9: Forth Week of the Month
10: Last Week of the Month
Default: Once
0: No Load Use to adjust
Scheduler 1: With Load
Read/ run mode for System
42421 Program x Run
Write 2: Extended Parallel the selected Scheduler
Mode
Default: No Load program

0: Sunday
1: Monday
2: Tuesday Use to adjust
Scheduler 3: Wednesday start day of
Read/ System
42422 Program x week for the
Write 4: Thursday Scheduler
Start Day selected
5: Friday program
6: Saturday
Default: Sunday
Multiplier: Unit: hour
1.00000000000 Lower Limit: .000 hour Use to adjust
Scheduler
Read/ Offset: 0 start hour for System
42423 Program x Upper Limit: 23.000
Write the selected Scheduler
Start Hour Size (bits): 16 hour program
Sign: U Default: 0
Unit: minute
Multiplier:
1.00000000000 Lower Limit: .000 Use to adjust
Scheduler minute
Read/ Offset: 0 start minute for System
42424 Program x
Write Upper Limit: 59.000 the selected Scheduler
Start Minute Size (bits): 16
minute program
Sign: U
Default: 0
Multiplier: Unit: hour
1.00000000000 Lower Limit: .000 hour Use to adjust
Scheduler
Read/ Offset: 0 duration hours System
42425 Program x Upper Limit: 23.000
Write for the selected Scheduler
Duration Hours Size (bits): 16 hour program
Sign: U Default: 0

A029X159 (Issue 31) 339 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Unit: minute
Multiplier:
Scheduler 1.000000000000 Lower Limit: .000 Use to adjust
Program x Read/ minute duration minute System
42426 Offset: 0
Duration Write Upper Limit: 59.000 for the selected Scheduler
Minutes Size (bits): 16 program
minute
Sign: U
Default: 0
Multiplier:
Unit: NA Selects which
Scheduler 1.000000000000
Read/ Lower Limit: 1.000 scheduler System
42427 Exception Offset: 0
Write Upper Limit: 6.000 exception to Scheduler
Select Size (bits): 16
Default: 1 view or edit
Sign: U

0: Disable Use to enable


Scheduler
Read/ or disable the System
42428 Exception x 1: Enable
Write selected Scheduler
Enable Default: Disable exception
Use to adjust
Scheduler 0: Once Only the repeat
Read/ System
42429 Exception x 1: Every Year setting of the
Write Scheduler
Repeat Default: Only Once selected
exception
Unit: month
Multiplier:
1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler month
Read/ Offset: 0 the month of System
42430 Exception x
Write Upper Limit: 12.000 the selected Scheduler
Month Size (bits): 16
month exception
Sign: U
Default: 1
Unit: date
Multiplier:
1.000000000000 Lower Limit: 1.000 Use to adjust
Scheduler date
Read/ Offset: 0 the start date System
42431 Exception x
Write Upper Limit: 31.000 of the selected Scheduler
Date Size (bits): 16
date exception
Sign: U
Default: 1
Multiplier: Unit: hour
1.000000000000 Lower Limit: .000 hour Use to adjust
Scheduler
Read/ Offset: 0 the start hour System
42432 Exception x Upper Limit: 23.000
Write of the selected Scheduler
Hour Size (bits): 16 hour exception
Sign: U Default: 0
Unit: minute
Multiplier:
Scheduler 1.000000000000 Lower Limit: .000 Use to adjust
Exception x Read/ minute the start minute System
42433 Offset: 0
Duration Write Upper Limit: 59.000 of the selected Scheduler
Minute Size (bits): 16 exception
minute
Sign: U
Default: 0

Copyright © 2023 Cummins Inc. 340 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier: Unit: days Use to adjust
Scheduler 1.000000000000 Lower Limit: .000 days the duration
Read/ Offset: 0 System
42434 Exception x Upper Limit: 44.000 days of the
Write Scheduler
Duration Days Size (bits): 16 days selected
Sign: U Default: 0 exception

Multiplier: Unit: hour Use to adjust


Scheduler 1.000000000000 Lower Limit: .000 hour the duration
Read/ Offset: 0 System
42435 Exception x Upper Limit: 23.000 hours of the
Write Scheduler
Duration Hours Size (bits): 16 hour selected
Sign: U Default: 0 exception

Unit: minute
Multiplier: Use to adjust
Scheduler 1.000000000000 Lower Limit: .000:
minute the duration
Exception x Read/ Offset: 0 System
42436 minutes of the
Duration Write Upper Limit: 59.000: Scheduler
Size (bits): 16 selected
Minutes minute
Sign: U exception
Default: 0

0: Disable Enables the


Daylight
Read/ daylight
42437 Saving Time 1: Enable Real Time Clock
Write savings time
Enable Default: Disable feature
Use to force a
Load Demand 0: Do Nothing refresh of the
Refresh Read/ Load Demand
42438 1: Refresh Sequence active load
Sequence Write Control
Default: Do Nothing demand
Command
sequence

Genset 0: Wye Delta or wye


Read/
42439 Connection 1: Delta for generator AC Setup
Write
Type Default: Wye set connection

Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Genset PT Volts Generator set
Read/ Offset: 0
42440 Primary PT primary AC Setup
Write Upper Limit:
Voltage Size(bits): 16 voltage
45000.000 Volts
Sign: U
Default: 480
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Genset PT Volts Generator set
Read/ Offset: 0
42441 Secondary PT secondary AC Setup
Write Upper Limit: 500.000
Voltage Size(bits): 16 voltage
Volts
Sign: U
Default: 120
Unit: Amps
Multiplier:
1.000000000000 Lower Limit: 5.000
Genset CT Amps Generator set
Read/ Offset: 0
42442 Primary CT primary AC Setup
Write Upper Limit:
Current Size(bits): 16 current
25000.000 Volts
Sign: U
Default: 100

A029X159 (Issue 31) 341 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function

Genset CT 0: 1 Amp Generator set


Read/
42443 Secondary 1: 5 Amp CT secondary AC Setup
Write
Current Default: 5 Amp current

Utility 0: Wye Delta or wye


Read/
42444 Connection 1: Delta for utility AC Setup
Write
Type Default: Wye connection

Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Utility PT Volts
Read/ Offset: 0 Utility PT
42445 Primary AC Setup
Write Upper Limit: primary voltage
Voltage Size(bits): 16
45000.000 Volts
Sign: U
Default: 480
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Utility PT Volts Utility PT
Read/ Offset: 0
42446 Secondary secondary AC Setup
Write Upper Limit: 500.000
Voltage Size(bits): 16 voltage
Volts
Sign: U
Default: 120
Unit: Amps
Multiplier:
1.000000000000 Lower Limit: 5.000
Utility CT Amps
Read/ Offset: 0 Utility CT
42447 Primary AC Setup
Write Upper Limit: primary current
Current Size(bits): 16
25000.000 Amps
Sign: U
Default: 100

Utility CT 0: 1 Amp Utility CT


Read/
42448 Secondary 1: 5 Amp secondary AC Setup
Write
Current Default: 5 Amp current

Generator set
Multiplier: Unit: kW kW capacity
Load Add Shed 1.000000000000 Lower Limit: .000 kW that must be
Required Read/ Offset: 0 Load Add Shed
42449 Upper Limit: online to start
Online Write Control
Size(bits): 16 32767.000 kW timed load
Capacity
Sign: S Default: 0 add : 0
disables this
Sets how much
Multiplier: Unit: kW capacity must
Load Demand 1.000000000000 Lower Limit: .000 kW always be
Minimum Read/ Offset: 0 Load Demand
42450 Upper Limit: online
Online Write Control
Size(bits): 16 32767.000 kW regardless of
Capacity
Sign: S Default: 0 what the load
is

Copyright © 2023 Cummins Inc. 342 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Unit: second Sets generator
Multiplier:
.100000000000 Lower Limit: .000 restart delay
Load Demand Read/ second time to avoid Load Demand
42451 Offset: 0
Restart Delay Write Upper Limit: 25.000 nuisance Control
Size(bits): 16 restarts due to
second
Sign: U load transients
Default: 1
Unit: Amps
Multiplier: Use to set how
1.000000000000 Lower Limit: 1.000
Amps many amps =
Utility Available Read/ Offset: 0
42452 100% utility kW AC Setup
Current Write Upper Limit:
Size(bits): 16 - used by
32000.000 Amps bargraph
Sign: U
Default: 1000
Multiplier: Unit: kW Use to set hoe
1.000000000000 Lower Limit: 1.000 kW many kW =
Total Utility Read/ Offset: 0
42453 Upper Limit: 100% utility kW AC Setup
Capacity Write
Size(bits): 16 32000.000 kW - used by
Sign: S Default: 1000 bargraph

0: 12V DC voltage
Nominal Read/ Battery Voltage
42454 1: 24V provided to the
Battery Voltage Write Protection
Default: 24V control

Unit: VDC
Multiplier:
.0100000000000 Lower Limit: 28.000
24V High VDC Sets 24V high
Read/ Offset: 0 Battery Voltage
42455 Battery Voltage battery voltage
Write Upper Limit: 34.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 32
Unit: VDC
Multiplier:
.0100000000000 Lower Limit: 22.000
24V Low VDC Sets 24V low
Read/ Offset: 0 Battery Voltage
42456 Battery Voltage battery voltage
Write Upper Limit: 26.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 24
Unit: VDC
Multiplier:
.0100000000 Lower Limit: 14.000
12V High VDC Sets 12V high
Read/ Offset: 0 Battery Voltage
42457 Battery Voltage battery voltage
Write Upper Limit: 17.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 16
Unit: VDC
Multiplier:
.010000000000 Lower Limit: 11.000
12 V Low VDC Sets 12V low
Read/ Offset: 0 Battery Voltage
42458 Battery Voltage battery voltage
Write Upper Limit: 13.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 12

A029X159 (Issue 31) 343 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Unit: second
Multiplier:
1.000000000000 Lower Limit: 2.000
High Battery second Sets high
Read/ Offset: 0 Battery Voltage
42459 Voltage Set battery voltage
Write Upper Limit: 60.000 Protection
Time Size(bits): 16 set time
second
Sign: U
Default: 60
Unit: second
Multiplier:
1.000000000000 Lower Limit: 2.000
Low Battery second Sets low
Read/ Offset: 0 Battery Voltage
42460 Voltage Set battery voltage
Write Upper Limit: 60.000 Protection
Time Size(bits): 16 set time
second
Sign: U
Default: 60
Used to enable
Genset Online 0: Disable or disable the
Read/
42461 Capacity 1: Enable generator set PTC Sensors
Write
Sensor Enable Default: Disable online capacity
sensor

Multiplier: Unit: kW Sets the online


Genset Online 1.000000000000 Lower Limit: .000 kW kW threshold
Capacity Read/ Offset: 0 at which
42462 Upper Limit: PTC Sensors
Sensor Write generator set
Threshold Size(bits): 16 32000.000 kW bus is available
Sign: S Default: 0 for loading
Use to enable
Nominal 0: Disable or disable the
Read/ Battery Voltage
42463 Battery Voltage 1: Enable nominal battery
Write Protection
Check Enable Default: Disable voltage
monitoring
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42464 Upper Limit: Discrete Outputs
Output1 Code Write configurable
Size(bits): 16 65535.000 output 1
Sign: U Default: 1483
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42465 Upper Limit: Discrete Outputs
Output2 Code Write configurable
Size(bits): 16 65535.000 output 2
Sign: U Default: 1457
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42466 Upper Limit: Discrete Outputs
Output3 Code Write configurable
Size(bits): 16 65535.000 output 3
Sign: U Default: 2965

Copyright © 2023 Cummins Inc. 344 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42467 Upper Limit: Discrete Outputs
Output4 Code Write configurable
Size(bits): 16 65535.000 output 4
Sign: U Default: 2328
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42468 Upper Limit: Discrete Outputs
Output5 Code Write configurable
Size(bits): 16 65535.000 output 5
Sign: U Default: 1121
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ code tied to
42469 Offset: 0 Upper Limit: Discrete Outputs
Output6 Code Write configurable
Size(bits): 16 65535.000 output 6
Sign: U Default: 1916

Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42470 Upper Limit: Discrete Outputs
Output7 Code Write configurable
Size(bits): 16 65535.000 output 7
Sign: U Default: 0
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42471 Upper Limit: Discrete Outputs
Output8 Code Write configurable
Size(bits): 16 65535.000 output 8
Sign: U Default: 343

0: None Indicates that


1: Breaker the generator
Gen Bus Base Read/ System
42472 bus is on base
Load Status Write 2: ATS Information
load extended
Default: None paralleling

0: None Indicates that


1: Breaker the utility bus is
Util Bus Peak Read/ System
42473 on peak shave
Shave Status Write 2: ATS Information
extended
Default: None paralleling
Indicates type
0: None of load
Load 7 Device Read/ 1: Breaker connected to Load Add Shed
42474
Type Write 2: ATS load 7 add Control
Default: None shed control
and status I/O

A029X159 (Issue 31) 345 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Indicates type
0: None of load
Load 8 Device Read/ 1: Breaker connected to Load Add Shed
42475
Type Write 2: ATS load 8 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 9 Device Read/ 1: Breaker connected to Load Add Shed
42476
Type Write 2: ATS load 9 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 10 Read/ 1: Breaker connected to Load Add Shed
42477
Device Type Write 2: ATS load 10 add Control
Default: None shed control
and status I/O
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 7 Add Read/ Lower Limit: .000 add level load Load Add Shed
42478 Offset: 0
Level Write Upper Limit: 17.000 7 is assigned Control
Size (bits): 16 to
Default: 7
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 8 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42479 Offset: 0
Level Write Upper Limit: 18.000 8 is assigned control
Size (bits): 16 to
Default: 8
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 9 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42480 Offset: 0
Level Write Upper Limit: 18.000 9 is assigned control
Size (bits): 16 to
Default: 9
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 10 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42481 Offset: 0
Level Write Upper Limit: 18.000 10 is assigned control
Size (bits): 16 to
Default: 10
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 7 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42482 Offset: 0
Level Write Upper Limit: 17.000 7 is assigned control
Size (bits): 16 to
Default: 6
Sign: U

Copyright © 2023 Cummins Inc. 346 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 8 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42483 Offset: 0
Level Write Upper Limit: 17.000 8 is assigned control
Size (bits): 16 to
Default: 7
Sign: U

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 9 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42484 Offset: 0
Level Write Upper Limit: 17.000 9 is assigned control
Size (bits): 16 to
Default: 8
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 10 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42485 Offset: 0
Level Write Upper Limit: 17.000 10 is assigned control
Size (bits): 16 to
Default: 9
Sign: U
Selects
whether to
Load Demand 0: %kW shutdown /
Read/ Load Add Shed
42486 Threshold 1: kW restart
Write control
Method Default: %kW generator sets
based on %kW
or absolute kW

Multiplier: Unit: kW Sets minimum


1.000000000000 Lower Limit: .000 kW kW reserve
Load Demand
Read/ Offset: 0 capacity when Load Add Shed
42487 Restart kW Upper Limit:
Write threshold control
Threshold Size (bits): 16 32000.000 kW method is
Sign: S Default: 500 absolute kW

Multiplier: Unit: kW Sets maximum


1.000000000000 Lower Limit: .000 kW kW reserve
Load Demand
Read/ Offset: 0 capacity when Load Add Shed
42488 Shutdown kW Upper Limit:
Write threshold control
Threshold Size (bits): 16 32000.000 kW method is
Sign: S Default: 1000 absolute kW

A029X159 (Issue 31) 347 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenE for
Load Demand Read/ Load Demand
42489 8: Gen9 fixed sequence
GenE Write Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen5
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenF for
Load Demand Read/ Load Demand
42490 8: Gen9 fixed sequence
GenF Write Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen6

Copyright © 2023 Cummins Inc. 348 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenG for
Load Demand Read/ Load Demand
42491 8: Gen9 fixed sequence
GenG Write Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen7
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8 Sets GenH for
Load Demand Read/ Load Demand
42492 8: Gen9 fixed sequence
GenH Write Control
9: Gen10 load demand
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default: Gen8
Sets how long
Unit: second to wait for
Multiplier:
.200000000000 Lower Limit: 2.000 generator set
Virtual Gen second
Read/ Offset: 0 paralleling
42494 Main Fail to Breaker Control
Write Upper Limit: 30.000 circuit breakers
Open Delay Size (bits): 16
second to open when
Sign: U no generator
Default: 5
main

A029X159 (Issue 31) 349 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 13 kW Read/ Offset: 0 Sets generator System
42495 Upper Limit:
Rating Write 13 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 14kW Read/ Offset: 0 Sets generator System
42496 Upper Limit:
Rating Write 14 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 15kW Read/ Offset: 0 Sets generator System
42497 Upper Limit:
Rating Write 15 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 16kW Read/ Offset: 0 Sets generator System
42498 Upper Limit:
Rating Write 16 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier:
Unit: NA Bitmapped
1.000000000000
Fault Status Read Lower Limit: state of utility Fault and Event
42500 Offset: 0
BitMap 1 Only Upper Limit: and other faults Info
Size (bits): 32 - 32 bits
Default: 0
Sign: U
Multiplier: Bitmapped
Unit: NA
1.000000000000 state of
Fault Status Read Lower Limit: Fault and Event
42502 Offset: 0 generator set
BitMap 2 Only Upper Limit: Info
Size (bits): 32 and other faults
Default: 0 - 32 bits
Sign: U
Multiplier:
Unit: NA
1.000000000000 Bitmapped
Event Status Read Lower Limit: Fault and Event
42505 Offset: 0 state of events
BitMap 1 Only Upper Limit: Info
Size (bits): 32 - 32 bits
Default: 0
Sign: U
Bit mapped
Multiplier: word with
Unit: NA
Genset 1.000000000000 status of
Read Lower Limit: AC Interrupt
42506 Metering Fault Offset: 0 generator set
Only Upper Limit: Service
Status Size (bits): 16 AC metering
Default: 0 out of range
Sign: U
conditions

Copyright © 2023 Cummins Inc. 350 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function

Multiplier: Bit mapped


Unit: NA word with
1.000000000000
Utility Metering Read Lower Limit: status of utility AC Interrupt
42507 Offset: 0
Fault Status Only Upper Limit: AC metering Service
Size (bits): 16 out of range
Default: 0
Sign: U conditions

0: Stop State of
Extended
Read / extended
42600 Parallel Start 1: Start Discrete Inputs
Write parallel start
Vol Default: Stop volatile input

0: Inactive State of
Synchronizer Read / synchronizer
42601 1: Active Discrete Inputs
Enable Vol Write enable volatile
Default: Inactive input
0: Inactive State of utility
Utility Source Read /
42602 1: Active source failure Discrete Inputs
Fail Vol Write
Default: Inactive volatile input

0: No Inhibit State of
Transfer Inhibit Read /
42603 1: Inhibit transfer inhibit Discrete Inputs
Vol Write
Default: No Inhibit volatile input

0: No Inhibit State of
Retransfer Read / retransfer
42604 1: Inhibit Discrete Inputs
Inhibit Vol Write inhibit volatile
Default: No Inhibit input

0: No Inhibit State of
Gen CB Inhibit Read / generator CB
42605 1: Inhibit Discrete Inputs
Vol Write inhibit volatile
Default: No Inhibit input
0: No Inhibit State of utility
Utility CB Read /
42606 1: Inhibit CB inhibit Discrete Inputs
Inhibit Vol Write
Default: No Inhibit volatile input

0: Auto State of
Auto/Manual Read/
42607 1: Manual auto/manual Discrete Inputs
Vol Write
Default: Auto volatile input

0: Stop state of test


Read/
42608 Test Start Vol 1: Start start volatile Discrete Inputs
Write
Default: Stop input

0: No Reset state of fault


Read/
42609 Fault Reset Vol 1: Reset reset volatile Discrete Inputs
Write
Default: No Reset input

0: No Override State of
Read/
42610 Override Vol 1: Override override Discrete Inputs
Write
Default: No Override volatile input

A029X159 (Issue 31) 351 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function

0: Stop State of
Extended
Read extended
42611 Parallel Start 1: Start Discrete Inputs
Only parallel start
Sw Default: input
0: Inactive State of
Synchronizer Read
42612 1: Active synchronizer Discrete Inputs
Enable Sw Only
Default: enable input

0: Inactive State of utility


Utility Source Read
42613 1: Active source failure Discrete Inputs
Failure Sw Only
Default: input

0: No Inhibit Status of
Transfer Inhibit Read
42614 1: Inhibit transfer inhibit Discrete Inputs
Sw Only
Default: input

0: No Inhibit Status of
Retransfer Read
42615 1: Inhibit retransfer Discrete Inputs
Inhibit Sw Only
Default: inhibit input

0: No Inhibit State of
Gen CB Inhibit Read
42616 1: Inhibit generator CB Discrete Inputs
Sw Only
Default: inhibit input

0: No Inhibit
Utility CB Read State of utility
42617 1: Inhibit Discrete Inputs
Inhibit Sw Only CB inhibit input
Default:
0: Auto
Auto/Manual Read State of auto /
42618 1: Manual Discrete Inputs
Sw Only manual input
Default:
0: Stop
Read State of test
42619 Test Start Sw 1: Start Discrete Inputs
Only start input
Default:
0: No Reset
Read State of fault
42620 Fault Reset Sw 1: Reset Discrete Inputs
Only reset input
Default:
0: No Override
Read State of
42621 Override Sw 1: Override Discrete Inputs
Only override input
Default:
0: No Inhibit Indicates state
Read
42622 Master Inhibit 1: Inhibit of Master Priority Control
Only
Default: priority inhibit

0: Inactive State of
Genset CB Read
42623 1: Active generator CB Discrete Inputs
Tripped Sw Only
Default: tripped input

Copyright © 2023 Cummins Inc. 352 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function

0: Inactive State of
Genset CB Read/ generator CB
42624 1: Active Discrete Inputs
Tripped Vol Write tripped volatile
Default: Inactive input
0: Inactive State of Utility
Utility CB Read
42625 1: Active CB tripped Discrete Inputs
Tripped Sw Only
Default: input

0: Inactive State of Utility


Util CB Tripped Read/
42626 1: Active CB tripped Discrete Inputs
Vol Write
Default: Inactive volatile input

0: L1-L2-L3
Genset Phase Read Generator set
42627 1: L1-L3-L2 Phase
Rotation Only phase rotation
Default:
0: L1-L2-L3
Utility Phase Read Utility phase
42628 1: L1-L3-L2 Phase
Rotation Only rotation
Default:
0: Breaker Open State of Gen1
Gen1 CB Read
42929 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: Open input

0: Breaker Open State of Gen1


Gen1 CB Read/
42630 1: Breaker Closed CB volatile Discrete Inputs
Position Vol Write
Default: Open input

0: Breaker Open State of Gen2


Gen2 CB Read
42631 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen2


Gen2 CB Read/
42632 1: Breaker Closed CB volatile Discrete Inputs
Position Vol Write
Default: Open input

0: Breaker Open State of Gen3


Gen3 CB Read
42633 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen3


Gen3 CB Read/
42634 1: Breaker Closed CB volatile Discrete Inputs
Position Vol Write
Default: Open input

0: Breaker Open State of Gen4


Gen4 CB Read
42635 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen4


Gen4 CB Read/
42636 1: Breaker Closed CB volatile Discrete Inputs
Position Vol Write
Default: Open input

A029X159 (Issue 31) 353 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: No Inhibit Use to
Network Read/
42637 1: Inhibit manually inhibit Priority Control
Master Inhibit Write
Default: No Inhibit the module

0: Breaker Open State of Gen5


Gen5 CB Read
42638 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen5


Gen5 CB Read/
42639 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen6


Gen6 CB Read
42640 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen6


Gen6 CB Read/
42641 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen7


Gen7 CB Read
42642 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen7


Gen7 CB Read/
42643 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen8


Gen8 CB Read
42644 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen8


Gen8 CB Read/
42645 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42646 ATS 7 Position position status
Only 3: Source 2 Connected Control
of ATS 7
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42647 ATS 8 Position position status
Only 3: Source 2 Connected Control
of ATS 8
4: Paralleled
Default: Not Available

Copyright © 2023 Cummins Inc. 354 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42648 ATS 9 Position position status
Only 3: Source 2 Connected Control
of ATS 9
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 10 Read Load Add Shed
42649 position status
Position Only 3: Source 2 Connected Control
of ATS 10
4: Paralleled
Default: Not Available
0: Open
1: Closed Indicates
Breaker 7 Read Load Add Shed
42650 position status
Position Only 2: Not Available Control
of breaker 7
Default: Not Available
0: Open
1: Closed Indicates
Breaker 8 Read Load Add Shed
42651 position status
Position Only 2: Not Available Control
of breaker 8
Default: Not Available
0: Open
1: Closed Indicates
Breaker 9 Read Load Add Shed
42652 position status
Position Only 2: Not Available Control
of breaker 9
Default: Not Available
0: Open
1: Closed Indicates
Breaker 10 Read Load Add Shed
42653 position status
Position Only 2: Not Available Control
of breaker 10
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 7 Trip Read Load Add Shed
42654 status of
Status Only 2: Tripped Control
breaker 7
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 8 Trip Read Load Add Shed
42655 status of
Status Only 2: Tripped Control
breaker 8
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 9 Trip Read Load Add Shed
42656 status of
Status Only 2: Tripped Control
breaker 9
Default: Not Available

A029X159 (Issue 31) 355 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Not Available
1: Normal Indicates trip
Breaker 10 trip Read Load Add Shed
42657 status of
Status Only 2: Tripped Control
breaker 10
Default: Not Available
0: Breaker Open State of Gen9
Gen9 CB Read
42658 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen9


Gen9 CB Read/
42659 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen10


Gen10 CB Read
42660 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen10


Gen10 CB Read/
42661 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen11


Gen11 CB Read
42662 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen11


Gen11 CB Read/
42663 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen12


Gen12 CB Read
42664 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen12


Gen12 CB Read/
42665 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen13


Gen13 CB Read
42666 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen13


Gen13 CB Read/
42667 1: Breaker Closed CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen


Gen14 CB Read
42668 1: Breaker Closed 14 CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen


Gen14 CB Read/
42669 1: Breaker Closed 14 CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

Copyright © 2023 Cummins Inc. 356 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Breaker Open State of Gen
Gen15 CB Read
42670 1: Breaker Closed 15 CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen


Gen15 CB Read/
42671 1: Breaker Closed 15 CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Breaker Open State of Gen


Gen16 CB Read
42672 1: Breaker Closed 16 CB position Discrete Inputs
Position Sw Only
Default: input

0: Breaker Open State of Gen


Gen16 CB Read/
42673 1: Breaker Closed 16 CB position Discrete Inputs
Position Vol Write
Default: Open volatile input

0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 11 Read Load Add Shed
42674 position status
Position Only 3: Source 2 Connected Control
of ATS 11
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 12 Read Load Add Shed
42675 position status
Position Only 3: Source 2 Connected Control
of ATS 12
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 13 Read Load Add Shed
42676 position status
Position Only 3: Source 2 Connected Control
of ATS 13
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 14 Read Load Add Shed
42677 position status
Position Only 3: Source 2 Connected Control
of ATS 14
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 15 Read Load Add Shed
42678 position status
Position Only 3: Source 2 Connected Control
of ATS 15
4: Paralleled
Default: Not Available

A029X159 (Issue 31) 357 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 16 Read Load Add Shed
42679 position status
Position Only 3: Source 2 Connected Control
of ATS 16
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 17 Read Load Add Shed
42680 position status
Position Only 3: Source 2 Connected Control
of ATS 17
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 18 Read Load Add Shed
42681 position status
Position Only 3: Source 2 Connected Control
of ATS 18
4: Paralleled
Default: Not Available
0: Open
1: Closed Indicates
Breaker 11 Read Load Add Shed
42682 position status
Position Only 2: Not Available Control
of breaker 11
Default: Not Available
0: Open
1: Closed Indicates
Breaker 12 Read Load Add Shed
42683 position status
Position Only 2: Not Available Control
of breaker 12
Default: Not Available
0: Open
1: Closed Indicates
Breaker 13 Read Load Add Shed
42684 position status
Position Only 2: Not Available Control
of breaker 13
Default: Not Available
0: Open
1: Closed Indicates
Breaker 14 Read Load Add Shed
42685 position status
Position Only 2: Not Available Control
of breaker 14
Default: Not Available
0: Open
1: Closed Indicates
Breaker 15 Read Load Add Shed
42686 position status
Position Only 2: Not Available Control
of breaker 15
Default: Not Available
0: Open
1: Closed Indicates
Breaker 16 Read Load Add Shed
42687 position status
Position Only 2: Not Available Control
of breaker 16
Default: Not Available

Copyright © 2023 Cummins Inc. 358 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Open
1: Closed Indicates
Breaker 17 Read Load Add Shed
42688 position status
Position Only 2: Not Available Control
of breaker 17
Default: Not Available
0: Open
1: Closed Indicates
Breaker 18 Read Load Add Shed
42689 position status
Position Only 2: Not Available Control
of breaker 18
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 11 Trip Read Load Add Shed
42690 status of
Status Only 2: Tripped Control
breaker 11
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 12 Trip Read Load Add Shed
42691 status of
Status Only 2: Tripped Control
breaker 12
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 13 Trip Read Load Add Shed
42692 status of
Status Only 2: Tripped Control
breaker 13
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 14 Trip Read Load Add Shed
42693 status of
Status Only 2: Tripped Control
breaker 14
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 15 Trip Read Load Add Shed
42694 status of
Status Only 2: Tripped Control
breaker 15
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 16 Trip Read Load Add Shed
42695 status of
Status Only 2: Tripped Control
breaker 16
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 17 Trip Read Load Add Shed
42696 status of
Status Only 2: Tripped Control
breaker 17
Default: Not Available
0: Not Available
1: Normal Indicates trip
Breaker 18 Trip Read Load Add Shed
42697 status of
Status Only 2: Tripped Control
breaker 18
Default: Not Available

A029X159 (Issue 31) 359 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Disabled Indicates the
Load Add Shed Read 1: Enabled overall state of Load Add Shed
42698
Enable Status Only 2: Paused the load add Control
Default: shed function

0: No Connection Indicates
1: Connected overall state of
Read
42699 PCCNet Status the PCCNet Communications
Only 2: Connecting communication
Default: s bus
0: Gen Does Not Exist
1: Offline For load
Gen1 2: Waiting For Gen
Read demand use - Load Demand
42700 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen1
Default:
0: Gen Does Not Exist 1: Offline
2: Waiting For Gen For load
Gen2
Read demand use - Load Demand
42701 Availability 3: Online
Only indicates status Control
State 4: Failed of Gen2
Default:
0: Gen Does Not Exist 1: Offline For load
Gen3 2: Waiting For Gen
Read demand use - Load Demand
42702 Availability
Only 3: Online 4: Failed indicates status Control
State
Default: of Gen3

0: Gen Does Not Exist 1: Offline


2: Waiting For Gen For load
Gen4
Read demand use - Load Demand
42703 Availability 3: Online
Only indicates status Control
State 4: Failed of Gen4
Default:

Multiplier: Unit: Hours


.000277777780 Lower Limit:.000 Hours
Gen1 Online Read Offset: 0 Total online System
42704 Upper Limit:
Time Only time for Gen1 Information
Size (bits): 32 1193046.000 Hours
Sign: U Default: 0
Unit: Hours Lower
Multiplier: Limit: .000 Hours
Gen2 Online Read .000277777780 Total online System
42706 Upper Limit:
Time Only Offset: 0 time for Gen2 Information
1193046.000 Hours
Size (bits): 32
Default: 0
Unit: Hours Lower
Multiplier:
Limit: .000 Hours
Gen3 Online Read .000277777780 Total online System
42708 Upper Limit:
Time Only Offset: 0 time for Gen3 Information
1193046.000 Hours
Size (bits): 32
Default: 0

Copyright © 2023 Cummins Inc. 360 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Unit: Hours Lower
Multiplier:
Limit: .000 Hours
Gen4 Online Read .000277777780 Total online System
42710 Upper Limit:
Time Only Offset: 0 time for Gen4 Information
1193046.000 Hours
Size (bits): 32
Default: 0
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read currently GenA Load Demand
42712 GenA 8: Gen9
Only (never stops) Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42713 GenB 8: Gen9 currently GenB
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

A029X159 (Issue 31) 361 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42714 GenC 8: Gen9 currently GenC
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator sets
Read Load Demand
42715 GenD 8: Gen9 is currently
Only Control
9: Gen10 GenD for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Off Indicates
Load Demand Read 1: Initial Delay Timing operating state Load Demand
42716
State Only 2: Load Monitor of the load Control
Default demand control

Indicates how
Multiplier: many of the
Unit: NA
Total Number 1.000000000000 generator sets
Read Lower Limit: System
42717 of Gensets Offset: 0 are online
Only Upper Limit: Information
Online Size (bits): 16 which are
Default: sensed by CB
Sign: U
position

Copyright © 2023 Cummins Inc. 362 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function

Multiplier: Difference
Unit: kW between
Total Spare 1.000000000000
Read Lower Limit: kW sensed online System
42718 Online Offset: 0
Only Upper Limit: kW capacity and Information
Capacity Size (bits): 16
Default: generator set
Sign: S bus total kW

Multiplier: Indicates kW
Unit: kW threshold for
Next Gen 1.000000000000
Read Lower Limit: kW generator bus Load Demand
42719 Shutdown Offset: 0
Only Upper Limit: kW at which next Control
Threshold Size (bits): 16
Default: generator set
Sign: S will restart
Indicates kW
Multiplier: threshold for
Unit: kW
Next Gen 1.000000000000 generator bus
Read Lower Limit: kW Load Demand
42720 Shutdown Offset: 0 at which the
Only Upper Limit: kW Control
Threshold Size (bits): 16 next generator
Default: set will load
Sign: S
demand stop
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Next Gen Read next to be Load Demand
42721 8: Gen9
Restart Only restarted if load Control
9: Gen10 conditions are
10: Gen11 met
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

A029X159 (Issue 31) 363 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Next Gen Read next to be Load Demand
42722 8: Gen9
Shutdown Only stopped if load Control
9: Gen10 conditions are
10: Gen11 met
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

0: Run Status of the


Load Demand
Read load demand
42723 Gen1 Driver 1: Load Demand Stop Discrete Outputs
Only Gen1 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42724 Gen2 Driver 1: Load Demand Stop Discrete Outputs
Only Gen2 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42725 Gen3 Driver 1: Load Demand Stop Discrete Outputs
Only Gen3 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42726 Gen4 Driver 1: Load Demand Stop Discrete Outputs
Only Gen4 driver
Status Default: output

Multiplier: Calculated kW
Unit: kW overload
Genset Bus 1.000000000000
Read Lower Limit: kW threshold System
42727 kW Overload Offset: 0
Only Upper Limit: kW based on Information
Status Size (bits): 16
Default: online capacity
Sign: S and % setting
Indicates
Genset Bus 0: No Overload whether
Read System
42728 kW Overload 1: Overload generator bus
Only Information
Status Default: is overloaded
based on kW

Copyright © 2023 Cummins Inc. 364 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Indicates
Genset Bus 0: No Overload whether
Underfrequenc Read generator bus System
42729 1: Overload
y Overload Only is overloaded Information
Status Default: based on
frequency
0: None
1: Program 1
2: Program 2
3: Program 3
4: Program 4
5: Program 5
6: Program 6
7: Program 7
8: Program 8 Indicates the
9: Program 9 currently active
Active Read System
42730 scheduler
Schedule Only 10: Program 10 Scheduler
program or
11: Program 11 exception
12: Program 12
13: Exception 1
14: Exception 2
15: Exception 3
16: Exception 4
17: Exception 5
18: Exception 6
Default:

0: Off Indicates
1: No Load current run
Scheduler Run Read command System
42731 2: With Load
Command Only coming from Scheduler
3: Extended Parallel scheduler
Default: function
Multiplier:
Unit: NA
Modbus Bus 1.000000000000
Read Lower Limit: Modbus
42732 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: NA
1.000000000000
Modbus CRC Read Lower Limit: Modbus CRC
42733 Offset: 0 Communications
Error Count Only Upper Limit: error count
Size (bits): 16
Default:
Sign: U

A029X159 (Issue 31) 365 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA
Modbus 1.000000000000 Modbus
Read Lower Limit:
42734 Exception Offset: 0 exception Communications
Only Upper Limit:
Count Size (bits): 16 count
Default:
Sign: U
Multiplier:
Unit: NA
Modbus No 1.000000000000
Read Lower Limit: Modbus no
42735 Response Offset: 0 Communications
Only Upper Limit: response count
Count Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: NA
Modbus Slave 1.000000000000
Read Lower Limit: Modbus slave
42736 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
0: Do Nothing Clears all
Modbus Clear Read/
42737 1: Clear Counters Modbus Communications
Counters Write
Default: Do Nothing counters

0: Normal
1: Set Clock Use to set
Read/
42738 Clock Mode clock and save Real Time Clock
Write 2: Save Clock setting
Default: Normal
Unit: year
Multiplier:
1.000000000000 Lower Limit: .000 year
Use to set or
Read/ Offset: 0 Upper Limit: 99.000
42739 Clock Year read current Real Time Clock
Write year
Size (bits): 16 year
Default: Read from
Sign: U
RTC chip
Unit: month
Multiplier: Lower Limit: 1.000
1.000000000000 month Use to set or
Read/ Offset: 0
42740 Clock Month Upper Limit: 12.000 read current Real Time Clock
Write
Size (bits): 16 month month
Sign: U Default: Read from
RTC chip
Unit: date
Multiplier: Lower Limit: 1.000
1.000000000000 date Use to set or
Read/ Offset: 0
42741 Clock Date Upper Limit: 31.000 read current Real Time Clock
Write
Size (bits): 16 date date
Sign: U Default: Read from
RTC chip

Copyright © 2023 Cummins Inc. 366 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Unit: hour
Multiplier: Lower Limit: 1.000
1.000000000000 hour Use to set or
Read/ Offset: 0
42742 Clock Hour Upper Limit: 23.000 read current Real Time Clock
Write
Size (bits): 16 hour hour
Sign: U Default: Read from
RTC chip
Unit: minute
Multiplier: Lower Limit: 1.000
1.000000000000 minute Use to set or
Read/ Offset: 0
42743 Clock Minute Upper Limit: 59.000 read current Real Time Clock
Write
Size (bits): 16 minute minute
Sign: U Default: Read from
RTC chip
Unit: second
Multiplier: Lower Limit: .000
1.000000000000 second Use to set or
Read/ Offset: 0
42744 Clock Second Upper Limit: 59.000 read current Real Time Clock
Write
Size (bits): 16 second second
Sign: U Default: Read from
RTC chip
0: Sunday
1: Monday
2: Tuesday
3: Wednesday Indicates day
Read
42745 Clock Day of the week for Real Time Clock
Only 4: Thursday current date
5: Friday
6: Saturday
Default:
Multiplier:
Unit: seconds Countdown
.100000000000
Read Lower Limit: seconds timer value for PTC Operating
42746 Start Timer Offset: 0
Only Upper Limit: seconds generator set Mode
Size (bits): 16 start timer
Default:
Sign: U
Multiplier:
Unit: seconds Countdown
.100000000000
Read Lower Limit: seconds timer value for PTC Operating
42747 Stop Timer Offset: 0
Only Upper Limit: seconds generator set Mode
Size (bits): 16 stop timer
Default:
Sign: U
Multiplier:
Unit: VDC Battery voltage
Low Battery .010000000000
Read Lower Limit: VDC with respect to Battery Voltage
42748 Voltage Offset: 0
Only Upper Limit: VDC set low battery Protection
Threshold Size (bits): 16
Default: threshold
Sign: U

A029X159 (Issue 31) 367 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: VDC Battery voltage
High Battery .010000000000
Read Lower Limit: VDC with respect to Battery Voltage
42749 Voltage Offset: 0
Only Upper Limit: VDC set high battery Protection
Threshold Size (bits): 16
Default: threshold
Sign: U
0: Gen Does Not Exist
1: Offline For load
Gen5 2: Waiting for Gen
Read demand use - Load Demand
42750 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen5
Default:
0: Gen Does Not Exist
1: Offline For load
Gen6 2: Waiting for Gen
Read demand use - Load Demand
42751 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen6
Default:
0: Gen Does Not Exist
1: Offline For load
Gen7 2: Waiting for Gen
Read demand use - Load Demand
42752 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen7
Default:
0: Gen Does Not Exist
1: Offline For load
Gen8 2: Waiting for Gen
Read demand use - Load Demand
42753 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen8
Default:

0: Run Status of the


Load Demand
Read load demand
42754 Gen5 Driver 1: Load Demand Stop Discrete Outputs
Only Gen5 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42755 Gen6 Driver 1: Load Demand Stop Discrete Outputs
Only Gen6 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42756 Gen7 Driver 1: Load Demand Stop Discrete Outputs
Only Gen7 driver
Status Default: output

0: Run Status of the


Load Demand
Read load demand
42757 Gen8 Driver 1: Load Demand Stop Discrete Outputs
Only Gen8 driver
Status Default: output

Copyright © 2023 Cummins Inc. 368 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7 Indicates which
7: Gen 8 generator set is
Read Load Demand
42758 GenE 8: Gen 9 currently GenE
Only Control
9: Gen 10 for load
10: Gen 11 demand
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7 Indicates which
7: Gen 8 generator set is
Read Load Demand
42759 GenF 8: Gen 9 currently GenF
Only Control
9: Gen 10 for load
10: Gen 11 demand
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:

A029X159 (Issue 31) 369 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7 Indicates which
7: Gen 8 generator set is
Read Load Demand
42760 GenG 8: Gen 9 currently GenG
Only Control
9: Gen 10 for load
10: Gen 11 demand
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7 Indicates which
7: Gen 8 generator set is
Read Load Demand
42761 GenH 8: Gen 9 currently GenH
Only Control
9: Gen 10 for load
10: Gen 11 demand
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default:
0: Do Nothing Indicates
Add Level 7 Read Load Add Shed
42762 1: Add Level status of add
Command Only Control
Default: Do Nothing level 7

0: Do Nothing Indicates
Add Level 8 Read Load Add Shed
42763 1: Add Level status of add
Command Only Control
Default: Do Nothing level 8

0: Do Nothing Indicates
Add Level 9 Read Load Add Shed
42764 1: Add Level status of add
Command Only Control
Default: Do Nothing level 9

Copyright © 2023 Cummins Inc. 370 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Add Level 10 Read Load Add Shed
42765 1: Add Level status of add
Command Only Control
Default: Do Nothing level 10

0: Do Nothing Indicates add


Add Load 7 Read Load Add Shed
42766 1: Add Level command for
Command Only Control
Default: Do Nothing load 7

0: Do Nothing Indicates add


Add Load 8 Read Load Add Shed
42767 1: Add Level command for
Command Only Control
Default: Do Nothing load 8

0: Do Nothing Indicates add


Add Load 9 Read Load Add Shed
42768 1: Add Level command for
Command Only Control
Default: Do Nothing load 9

0: Do Nothing Indicates add


Add Load 10 Read Load Add Shed
42769 1: Add Level command for
Command Only Control
Default: Do Nothing load 10

0: Do Nothing Indicates
Shed Level 6 Read Load Add Shed
42770 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 6

0: Do Nothing Indicates
Shed Level 7 Read Load Add Shed
42771 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 7

0: Do Nothing Indicates
Shed Level 8 Read Load Add Shed
42772 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 8

0: Do Nothing Indicates
Shed Level 9 Read Load Add Shed
42773 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 9

0: Do Nothing Indicates shed


Shed Load 7 Read Load Add Shed
42774 1: Shed Load command for
Command Only Control
Default: Do Nothing load 7

0: Do Nothing Indicates shed


Shed Load 8 Read Load Add Shed
42775 1: Shed Load command for
Command Only Control
Default: Do Nothing load 8

0: Do Nothing Indicates shed


Shed Load 9 Read Load Add Shed
42776 1: Shed Load command for
Command Only Control
Default: Do Nothing load 9

0: Do Nothing Indicates shed


Shed Load 10 Read Load Add Shed
42777 1: Shed Load command for
Command Only Control
Default: Do Nothing load 10

A029X159 (Issue 31) 371 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function

0: Do Nothing Indicates if
Restore Shed
Read shed level 6 Load Add Shed
42778 Level 6 1: Restore Level
Only has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 7 Load Add Shed
42779 Level 7 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 8 Load Add Shed
42780 Level 8 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 9 Load Add Shed
42781 Level 9 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen5 Online Read hours Total online System
42782 Offset: 0
Time Only Upper Limit: time for Gen5 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0
Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen6 Online Read hours Total online System
42784 Offset: 0
Time Only Upper Limit: time for Gen6 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0
Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen7 Online Read hours Total online System
42786 Offset: 0
Time Only Upper Limit: time for Gen7 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0
Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen8 Online Read hours Total online System
42788 Offset: 0
Time Only Upper Limit: time for Gen8 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42790 Level 7 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 7

Copyright © 2023 Cummins Inc. 372 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42791 Level 8 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 8

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42792 Level 9 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 9

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42793 Level 10 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 10

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42794 Level 6 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 6

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42795 Level 7 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 7

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42796 Level 8 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 8

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42797 Level 9 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 9
0: Gen Does Not Exist
1: Offline For load
Gen9 2: Waiting For Gen
Read demand use - Load Demand
42798 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen9
Default:
0: Gen Does Not Exist
1: Offline For load
Gen10 2: Waiting For Gen
Read demand use - Load Demand
42799 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen10
Default:
0: Gen Does Not Exist
1: Offline For load
Gen11 2: Waiting For Gen
Read demand use - Load Demand
42800 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen11
Default:

A029X159 (Issue 31) 373 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Gen Does Not Exist
1: Offline For load
Gen12 2: Waiting For Gen
Read demand use - Load Demand
42801 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen12
Default:
0: Gen Does Not Exist
1: Offline For load
Gen13 2: Waiting For Gen
Read demand use - Load Demand
42802 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen13
Default:
0: Gen Does Not Exist
1: Offline For load
Gen14 2: Waiting for Gen
Read demand use - Load Demand
42803 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen14
Default:
0: Gen Does Not Exist
1: Offline For load
Gen15 2: Waiting for Gen
Read demand use - Load Demand
42804 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen15
Default:
0: Gen Does Not Exist
1: Offline For load
Gen16 2: Waiting for Gen
Read demand use - Load Demand
42805 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen16
Default:

Load Demand 0: Run Status of load


Read
42806 Gen9 Driver 1: Load Demand Stop demand Gen9 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42807 Gen10 Driver 1: Load Demand Stop demand Gen10 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42808 Gen11 Driver 1: Load Demand Stop demand Gen11 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42809 Gen12 Driver 1: Load Demand Stop demand Gen12 Discrete Outputs
Only
Status Default: driver output

Copyright © 2023 Cummins Inc. 374 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function

Load Demand 0: Run Status of load


Read
42810 Gen13 Driver 1: Load Demand Stop demand Gen13 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42811 Gen14 Driver 1: Load Demand Stop demand Gen14 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42812 Gen15 Driver 1: Load Demand Stop demand Gen15 Discrete Outputs
Only
Status Default: driver output

Load Demand 0: Run Status of load


Read
42813 Gen16 Driver 1: Load Demand Stop demand Gen16 Discrete Outputs
Only
Status Default: driver output

0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42814 GenI 8: Gen9 currently GenI
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

A029X159 (Issue 31) 375 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42815 GenJ 8: Gen9 currently GenJ
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42816 GenK 8: Gen9 currently GenK
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

Copyright © 2023 Cummins Inc. 376 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42817 GenL 8: Gen9 currently GenL
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42818 GenM 8: Gen9 currently GenM
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

A029X159 (Issue 31) 377 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42819 GenN 8: Gen9 currently GenN
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42820 GenO 8: Gen9 currently GenO
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:

Copyright © 2023 Cummins Inc. 378 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42821 GenP 8: Gen9 currently GenP
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Do Nothing Indicates
Add Level 11 Read Load Add Shed
42822 1: Add Level status of add
Command Only Control
Default: Do Nothing level 11

0: Do Nothing Indicates
Add Level 12 Read Load Add Shed
42823 1: Add Level status of add
Command Only Control
Default: Do Nothing level 12

0: Do Nothing Indicates
Add Level 13 Read Load Add Shed
42824 1: Add Level status of add
Command Only Control
Default: Do Nothing level 13

0: Do Nothing Indicates
Add Level 14 Read Load Add Shed
42825 1: Add Level status of add
Command Only Control
Default: Do Nothing level 14

0: Do Nothing Indicates
Add Level 15 Read Load Add Shed
42826 1: Add Level status of add
Command Only Control
Default: Do Nothing level 15

0: Do Nothing Indicates
Add Level 16 Read Load Add Shed
42827 1: Add Level status of add
Command Only Control
Default: Do Nothing level 16

0: Do Nothing Indicates
Add Level 17 Read Load Add Shed
42828 1: Add Level status of add
Command Only Control
Default: Do Nothing level 17

0: Do Nothing Indicates
Add Level 18 Read Load Add Shed
42829 1: Add Level status of add
Command Only Control
Default: Do Nothing level 18

A029X159 (Issue 31) 379 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates add
Add Load 11 Read Load Add Shed
42830 1: Add Load command for
Command Only Control
Default: Do Nothing load 11

0: Do Nothing Indicates add


Add Load 12 Read Load Add Shed
42831 1: Add Load command for
Command Only Control
Default: Do Nothing load 12

0: Do Nothing Indicates add


Add Load 13 Read Load Add Shed
42832 1: Add Load command for
Command Only Control
Default: Do Nothing load 13

0: Do Nothing Indicates add


Add Load 14 Read Load Add Shed
42833 1: Add Load command for
Command Only Control
Default: Do Nothing load 14

0: Do Nothing Indicates add


Add Load 15 Read Load Add Shed
42834 1: Add Load command for
Command Only Control
Default: Do Nothing load 15

0: Do Nothing Indicates add


Add Load 16 Read Load Add Shed
42835 1: Add Load command for
Command Only Control
Default: Do Nothing load 16

0: Do Nothing Indicates add


Add Load 17 Read Load Add Shed
42836 1: Add Load command for
Command Only Control
Default: Do Nothing load 17

0: Do Nothing Indicates add


Add Load 18 Read Load Add Shed
42837 1: Add Load command for
Command Only Control
Default: Do Nothing load 18

0: Do Nothing Indicates
Shed Level 10 Read Load Add Shed
42838 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 10

0: Do Nothing Indicates
Shed Level 11 Read Load Add Shed
42839 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 11

0: Do Nothing Indicates
Shed Level 12 Read Load Add Shed
42840 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 12

0: Do Nothing Indicates
Shed Level 13 Read Load Add Shed
42841 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 13

0: Do Nothing Indicates
Shed Level 14 Read Load Add Shed
42842 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 14

Copyright © 2023 Cummins Inc. 380 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Do Nothing Indicates
Shed Level 15 Read Load Add Shed
42843 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 15

0: Do Nothing Indicates
Shed Level 16 Read Load Add Shed
42844 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 16

0: Do Nothing Indicates
Shed Level 17 Read Load Add Shed
42845 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 17

0: Do Nothing Indicates shed


Shed Load 11 Read Load Add Shed
42846 1: Shed Load command for
Command Only Control
Default: Do Nothing load 11

0: Do Nothing Indicates shed


Shed Load 12 Read Load Add Shed
42847 1: Shed Load command for
Command Only Control
Default: Do Nothing load 12

0: Do Nothing Indicates shed


Shed Load 13 Read Load Add Shed
42848 1: Shed Load command for
Command Only Control
Default: Do Nothing load 13

0: Do Nothing Indicates shed


Shed Load 14 Read Load Add Shed
42849 1: Shed Load command for
Command Only Control
Default: Do Nothing load 14

0: Do Nothing Indicates shed


Shed Load 15 Read Load Add Shed
42850 1: Shed Load command for
Command Only Control
Default: Do Nothing load 15

0: Do Nothing Indicates shed


Shed Load 16 Read Load Add Shed
42851 1: Shed Load command for
Command Only Control
Default: Do Nothing load 16

0: Do Nothing Indicates shed


Shed Load 17 Read/ Load Add Shed
42852 1: Shed Load command for
Command Write Control
Default: Do Nothing load 17

0: Do Nothing Indicates shed


Shed Load 18 Read/ Load Add Shed
42853 1: Shed Load command for
Command Write Control
Default: Do Nothing load 18

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 10 Load Add Shed
42854 Level 10 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 11 Load Add Shed
42855 Level 11 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

A029X159 (Issue 31) 381 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 12 Load Add Shed
42856 Level 12 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 13 Load Add Shed
42857 Level 13 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 14 Load Add Shed
42858 Level 14 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 15 Load Add Shed
42859 Level 15 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 16 Load Add Shed
42860 Level 16 1: Restore Level
Write has been Control
Command Default: Do Nothing restored

0: Do Nothing Indicates if
Restore Shed
Read/ shed level 17 Load Add Shed
42861 Level 17 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen9 Online Read Hours Total online System
42862 Offset: 0
Time Only Upper Limit: time for Gen9 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen10 Online Read Hours Total online System
42864 Offset: 0
Time Only Upper Limit: time for Gen10 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen11 Online Read Hours Total online System
42866 Offset: 0
Time Only Upper Limit: time for Gen11 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

Copyright © 2023 Cummins Inc. 382 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen12 Online Read Hours Total online System
42868 Offset: 0
Time Only Upper Limit: time for Gen12 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen13 Online Read Hours Total online System
42870 Offset: 0
Time Only Upper Limit: time for Gen13 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen14 Online Read Hours Total online System
42872 Offset: 0
Time Only Upper Limit: time for Gen14 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen15 Online Read Hours Total online System
42874 Offset: 0
Time Only Upper Limit: time for Gen15 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen16 Online Read Hours Total online System
42876 Offset: 0
Time Only Upper Limit: time for Gen16 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42878 Level 11 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 11

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42879 Level 12 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 12

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42880 Level 13 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 13

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42881 Level 14 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 14

A029X159 (Issue 31) 383 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42882 Level 15 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 15

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42883 Level 16 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 16

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42884 Level 17 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 17

0: Do Nothing Operator input


Manual Add
Read/ to add loads Load Add Shed
42885 Level 18 1: Add Level
Write assigned to Control
Command Default: Do Nothing level 18

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42886 Level 10 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 10

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42887 Level 11 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 11

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42888 Level 12 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 12

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42889 Level 13 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 13

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42890 Level 14 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 14

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42891 Level 15 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 15

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42892 Level 16 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 16

0: Do Nothing Operator input


Manual Shed
Read/ to shed loads Load Add Shed
42893 Level 17 1: Shed Level
Write assigned to Control
Command Default: Do Nothing level 17

Copyright © 2023 Cummins Inc. 384 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Indicates type
0: None of load
Load 11 Read/ 1: Breaker connected to Load Add Shed
42894
Device Type Write 2: ATS load 11 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 12 Read/ 1: Breaker connected to Load Add Shed
42895
Device Type Write 2: ATS load 12 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 13 Read/ 1: Breaker connected to Load Add Shed
42896
Device Type Write 2: ATS load 13 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 14 Read/ 1: Breaker connected to Load Add Shed
42897
Device Type Write 2: ATS load 14 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 15 Read/ 1: Breaker connected to Load Add Shed
42898
Device Type Write 2: ATS load 15 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 16 Read/ 1: Breaker connected to Load Add Shed
42899
Device Type Write 2: ATS load 16 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 17 Read/ 1: Breaker connected to Load Add Shed
42900
Device Type Write 2: ATS load 17 add Control
Default: None shed control
and status I/O
Indicates type
0: None of load
Load 18 Read/ 1: Breaker connected to Load Add Shed
42901
Device Type Write 2: ATS load 18 add Control
Default: None shed control
and status I/O

A029X159 (Issue 31) 385 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 11 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42902 Offset: 0
Level Write Upper Limit: 18.000 11 is assigned Control
Size (bits): 0 to
Default: 11
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 12 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42903 Offset: 0
Level Write Upper Limit: 18.000 12 is assigned Control
Size (bits): 0 to
Default: 12
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 13 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42904 Offset: 0
Level Write Upper Limit: 18.000 13 is assigned Control
Size (bits): 0 to
Default: 13
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 14 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42905 Offset: 0
Level Write Upper Limit: 18.000 14 is assigned Control
Size (bits): 0 to
Default: 14
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 15 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42906 Offset: 0
Level Write Upper Limit: 18.000 15 is assigned Control
Size (bits): 0 to
Default: 15
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 16 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42907 Offset: 0
Level Write Upper Limit: 18.000 16 is assigned Control
Size (bits): 0 to
Default: 16
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 17 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42908 Offset: 0
Level Write Upper Limit: 18.000 17 is assigned Control
Size (bits): 0 to
Default: 17
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 18 Add Read/ Lower Limit: 1.000 add level load Load Add Shed
42909 Offset: 0
Level Write Upper Limit: 18.000 18 is assigned Control
Size (bits): 0 to
Default: 18
Sign: U

Copyright © 2023 Cummins Inc. 386 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier:
Unit: NA Indicates which
1.000000000000
Load 11 Shed Read/ Lower Limit: .000 shed level load Load Add Shed
42910 Offset: 0
Level Write Upper Limit: 17.000 11 is assigned Control
Size (bits): 0 to
Default: 10
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 12 Shed Read Lower Limit: .000 shed level load Load Add Shed
42911 Offset: 0
Level /Write Upper Limit: 17.000 12 is assigned Control
Size (bits): 0 to
Default: 11
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 13 Shed Read Lower Limit: .000 shed level load Load Add Shed
42912 Offset: 0
Level /Write Upper Limit: 17.000 13 is assigned Control
Size (bits): 16 to
Default: 12
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 14 Shed Read Lower Limit: .000 shed level load Load Add Shed
42913 Offset: 0
Level /Write Upper Limit: 17.000 14 is assigned Control
Size (bits): 16 to
Default: 13
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 15 Shed Read Lower Limit: .000 shed level load Load Add Shed
42914 Offset: 0
Level /Write Upper Limit: 17.000 15 is assigned Control
Size (bits): 16 to
Default: 14
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 16 Shed Read Lower Limit: .000 shed level load Load Add Shed
42915 Offset: 0
Level /Write Upper Limit: 17.000 16 is assigned Control
Size (bits): 16 to
Default: 15
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 17 Shed Read Lower Limit: .000 shed level load Load Add Shed
42916 Offset: 0
Level /Write Upper Limit: 17.000 17 is assigned Control
Size (bits): 16 to
Default: 16
Sign: U
Multiplier:
Unit: NA Indicates which
1.000000000000
Load 18 Shed Read Lower Limit: .000 shed level load Load Add Shed
42917 Offset: 0
Level /Write Upper Limit: 17.000 18 is assigned Control
Size (bits): 16 to
Default: 17
Sign: U

A029X159 (Issue 31) 387 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenI for
Load Demand Read Load Demand
42918 8: Gen 9 fixed sequence
GenI /Write Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen9
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenJ for
Load Demand Read Load Demand
42919 8: Gen 9 fixed sequence
GenJ /Write Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen10

Copyright © 2023 Cummins Inc. 388 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenK for
Load Demand Read Load Demand
42920 8: Gen 9 fixed sequence
GenK /Write Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen11
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenL for
Load Demand Read Load Demand
42921 8: Gen 9 fixed sequence
GenL /Write Shed Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen12

A029X159 (Issue 31) 389 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenM for
Load Demand Read Load Demand
42922 8: Gen 9 fixed sequence
GenM /Write Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen13
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenN for
Load Demand Read Load Demand
42923 8: Gen 9 fixed sequence
GenN /Write Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen14

Copyright © 2023 Cummins Inc. 390 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenO for
Load Demand Read Load Demand
42924 8: Gen 9 fixed sequence
GenO /Write Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen15
0: Gen 1
1: Gen 2
2: Gen 3
3: Gen 4
4: Gen 5
5: Gen 6
6: Gen 7
7: Gen 8 Sets GenP for
Load Demand Read Load Demand
42925 8: Gen 9 fixed sequence
GenP /Write Control
9: Gen 10 load demand
10: Gen 11
11: Gen 12
12: Gen 13
13: Gen 14
14: Gen 15
15: Gen 16
Default: Gen16
0: Missing
1: Good Indicates
Read 2: Connecting status of SID2
42926 SID2 Status Communications
Only 3: No Exp Board (aux101/102
4: Not Applicable module 2)
Default:

A029X159 (Issue 31) 391 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


0: Missing
1: Good Indicates
Read 2: Connecting status of SID3
42927 SID3 Status Communications
Only 3: No Exp Board (aux101/102
4: Not Applicable module 3)
Default:
Indicates the
Expansion 0: Disabled status of the
Board Read 1: Enabled SID2 to
42928 Communications
Communication Only 2: Connecting expansion
s2 Default: Disabled board
connection
Indicates the
Expansion 0: Disabled status of the
Board Read 1: Enabled SID3 to
42929 Communications
Communication Only 2: Connecting expansion
s3 Default: Disabled board
connection

0: After Transfer Delay PTC - point in


Utility Breaker Read time at which
42930 1: Upon Utility Failure PTC Connected
Opening Point /Write system opens
Default: After Transfer Delay utility breaker
PTC - sets
0: Utility Disconnect point at which
Commit To 1: Genset Start
Read system PTC Operating
42931 Transfer
/Write 2: No Commit commits to Mode
Method
Default: Utility Disconnect transfer to
generator set
PTC - indicates
0: Not Committed if system is
Commit To Read PTC Operating
42932 1: Committed committed to
Transfer State Only Mode
Default: transferring to
generator set
Multiplier:
Unit: kW Sum of the
1.000000000000
Total System Read Lower Limit: kW generator set System
42933 Offset: 0
Capacity 32bit Only Upper Limit: kW kW ratings in Information
Size (bits): 32 32bit
Default:
Sign: S
Sum of the
Multiplier: generator set
Unit: kW
1.000000000000 kW ratings in
Total Online Read Lower Limit: kW System
42935 Offset: 0 32bit for
Capacity 32bit Only Upper Limit: kW Information
Size (bits): 32 generator sets
Default: which are
Sign: S
online

Copyright © 2023 Cummins Inc. 392 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Multiplier: kW control
Unit: kW
kW Load 1.000000000000 reference value
Read Lower Limit: kW Master Load
42937 Reference Offset: 0 in 32bit for
Only Upper Limit: kW Control
32bit Size (bits): 3 extended
Default: paralleling
2Sign: S
Multiplier: kVAR control
Unit: kVAR
kVAR Load 1.000000000000 reference value
Read Lower Limit: kVAR Master Load
42939 Reference Offset: 0 in 32bit for
Only Upper Limit: kVAR Control
32bit Size (bits): 32 extended
Default: paralleling
Sign: S
Unit: kW Sets the base
Multiplier: Lower Limit: .000 kW load kW
Genset Bus
Read 1.000000000000Off Upper Limit: setpoint in Master Load
42943 kW Setpoint
/Write set: 0Size (bits): 2147483647.000 32bit in closed Control
32bit
32Sign: S kW loop extended
Default: 0 paralleling

Unit: kVAR
Multiplier: Lower Limit: .000 Sets the base
1.000000000000 kVAR load kVAR
Genset Bus
Read Offset: 0 setpoint in Master Load
42945 kVAR Setpoint Upper Limit:
/Write 32bit in closed Control
32bit Size (bits): 32 2147483647.000 loop extended
Sign: S kVAR paralleling
Default: 0
Unit: kW
Multiplier:
1.000000000000 Lower Limit: Setpoint for
Genset -2147483648.000 kW
Read Offset: 0 generator set Master Load
42947 Unloaded
/Write Upper Limit: unloaded level Control
Level 32bit Size (bits): 32
2147483647.000 kW in 32bit
Sign: S
Default:50
Unit: kW Sets the peak
Multiplier:
1.000000000000 Lower Limit: shave kW
Utility Bus kW Read -2147483648.000 kW setpoint in Master Load
42949 Offset: 0
Setpoint 32bit /Write Upper Limit: 32bit in closed Control
Size (bits): 32 loop extended
2147483647.000 kW
Sign: S paralleling
Default: 100
Unit: kW sets the utility
Multiplier:
1.000000000000 Lower Limit: kW constraint
Utility Bus kW -2147483648.000 kW
Read / Offset: 0 level in 32bit Master Load
42951 Constraint
write Upper Limit: for base load Control
Level 32bit Size (bits): 32
2147483647.000 kW extended
Sign: S paralleling
Default: 100

A029X159 (Issue 31) 393 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Addr. System Name Access Specifications Description Function


Unit: kVAR
Multiplier: Lower Limit: Sets the peak
1.000000000000 -2147483648.000 shave kVAR
Utility Bus kVAR
Read / Offset: 0 setpoint in Master Load
42953 kVAR Setpoint
write Upper Limit: 32bit in closed Control
32bit Size (bits): 32
2147483647.000 loop extended
Sign: S kVAR paralleling
Default: 100
Unit: kW
Multiplier:
1.000000000000 Lower Limit:
Utility -2147483648.000 kW Setpoint for
Read / Offset: 0 Master Load
42955 Unloaded utility unload
write Upper Limit: Control
Level 32bit Size (bits): 32 level in 32bit
2147483647.000 kW
Sign: S
Default: 50

Multiplier: Unit: kW generator set


Load Add Shed 1.000000000000 Lower Limit: .000 kW kW capacity
Required Read / Offset: 0 that must be Load Demand
42957 Upper Limit:
Online write online to start Control
Capacity 32bit Size (bits): 32 2147483647.000 kW timed load add;
Sign: S Default: 0 0 disables this
Sets how much
Multiplier: Unit: kW capacity must
Load Demand 1.000000000000 Lower Limit: .000 kW always be
Minimum Read / Offset: 0 Load Demand
42959 Upper Limit: online
Online write Control
Size (bits): 32 2147483647.000 kW regardless of
Capacity 32bit
Sign: S Default: 0 what the load
is

Multiplier: Unit: kW Use to set how


1.000000000000 Lower Limit: 1.000 kW many kW
Total Utility Read / Offset: 0 (32bit) =100%
42961 Upper Limit: AC Setup
Capacity 32bit write utility kW --
Size (bits): 32 2147483647.000 kW used by
Sign: S Default: 1000 bargraph

Multiplier: Unit: kW Set the online


Genset Online 1.000000000000 Lower Limit: .000 kW kW threshold
Capacity Read / 32bit at which
42963 Offset: 0 Upper Limit: PTC Sensors
Sensor write generator set
Threshold 32bit Size (bits): 32 2147483647.000 kW but is available
Sign: S Default: 0 for loading
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW Set minimum
Load Demand
Read Offset: 0 kW reserve Load Demand
42965 Restart kW Upper Limit:
/Write capacity when Control
Threshold 32bit Size (bits): 32 2147483647.000 kW kW in 32bit
Sign: S Default: 500

Copyright © 2023 Cummins Inc. 394 A029X159 (Issue 31)


8-2023 9. MCM3320

Addr. System Name Access Specifications Description Function


Sets maximum
Multiplier: Unit: kW kW reserve
Load Demand 1.000000000000 Lower Limit: .000 kW capacity when
Read / Offset: 0 Load Demand
42967 Shutdown kW Upper Limit: threshold
write Control
Threshold 32bit Size (bits): 32 2147483647.000 kw method is
Sign: S Default: 1000 absolute kW in
32bit
Difference
Multiplier: between
Unit: kW
Total Spare 1.000000000000 sensed online
Read Lower Limit: kW System
42971 Online Offset: 0 capacity and
Only Upper Limit: kW Information
Capacity 32bit Size (bits): 32 generator Set
Default: bus total kW in
Sign: S
32bit

Multiplier: Shows 32 bit


Unit: kW kW threshold
Next Gen 1.000000000000
Read Lower Limit: kW for generator Load Demand
42973 Restart Offset: 0
Only Upper Limit: kW bus at which Control
Threshold 32bit Size (bits): 32
Default: next generator
Sign: S set will restart
Shows 32 bit
Multiplier: kW threshold
Unit: kW for generator
Next Gen 1.000000000000
Read Lower Limit: kW bus at which Load Demand
42975 Shutdown Offset: 0
Only Upper Limit: kW next generator Control
Threshold 32bit Size (bits): 32
Default: set load
Sign: S demand stops
in

Multiplier: Calculated kW
Unit: kW overload
Genset Bus 1.000000000000
Read Lower Limit: kW threshold in System
42977 kW Overload Offset: 0
Only Upper Limit: kW 32bit based on Information
Threshold 32bit Size(bits): 32
Default: online capacity
Sign: S and % setting

9.2 MCM3320 Modbus Fault Status Bitmaps


NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

A029X159 (Issue 31) 395 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Fault
Addr. Bit# System Name Event Name Response
Code
Utility Main Breaker Position Contact
42500 0 Fault Status Bitmap 1 1455 Warning
Warning
42500 1 Fault Status Bitmap 1 2396 Utility Main Breaker Fail To Close Warning Warning
42500 2 Fault Status Bitmap 1 2397 Utility Main Breaker Fail To Open Warning Warning
42500 3 Fault Status Bitmap 1 1219 Utility Main Breaker Tripped Warning Warning
42500 4 Fault Status Bitmap 1 1914 Utility Bus Phase Rotation Warning Warning
42500 5 Fault Status Bitmap 1 1912 Utility Bus Loss Of Phase Warning Warning
42500 6 Fault Status Bitmap 1 2331 Utility Bus Undervoltage Warning Warning
42500 7 Fault Status Bitmap 1 2358 Utility Bus Overvoltage Warning Warning
42500 8 Fault Status Bitmap 1 1223 Utility Bus Frequency Warning Warning
42500 21 Fault Status Bitmap 1 4137 Advanced Grid Protection Warning Warning
42500 22 Fault Status Bitmap 1 3924 Utility Reverse kW Warning Warning
42500 23 Fault Status Bitmap 1 2939 Modbus Communication Failure Warning Warning
42500 24 Fault Status Bitmap 1 2648 Remote IO Communication Failure Warning Warning
42500 25 Fault Status Bitmap 1 1689 Real Time Clock Power Interrupt Warning Warning
42500 26 Fault Status Bitmap 1 1335 AC Metering Out Of Range Warning Warning
42500 27 Fault Status Bitmap 1 1999 Maximum Parallel Time Warning Warning
42500 28 Fault Status Bitmap 1 343 Hardware Failure Warning Warning
42500 29 Fault Status Bitmap 1 1456 Synchronizer Output Limit Warning Warning
42500 30 Fault Status Bitmap 1 2416 Calibration Checksum Warning Warning
42500 31 Fault Status Bitmap 1 353 EEPROM Write Error Warning Warning
Genset Main Breaker Position Contact
42502 0 Fault Status Bitmap 2 1454 Warning
Warning
42502 1 Fault Status Bitmap 2 1452 Genset Main Breaker Fail To Close Warning Warning
42502 2 Fault Status Bitmap 2 1453 Genset Main Breaker Fail To Open Warning
42502 3 Fault Status Bitmap 2 1328 Genset Main Breaker Tripped Warning Warning
42502 4 Fault Status Bitmap 2 1915 Genset Bus Phase Rotation Warning Warning
42502 5 Fault Status Bitmap 2 1913 Genset Bus Loss Of Phase Warning Warning
42502 6 Fault Status Bitmap 2 1225 Genset Bus Undervoltage Warning Warning
42502 7 Fault Status Bitmap 2 1224 Genset Bus Overvoltage Warning Warning
42502 8 Fault Status Bitmap 2 1226 Genset Bus Frequency Warning Warning
42502 22 Fault Status Bitmap 2 441 Low Battery Voltage Warning Warning
42502 23 Fault Status Bitmap 2 442 High Battery Voltage Warning Warning
42502 24 Fault Status Bitmap 2 1541 Genset Failed To Come Online Warning Warning

Copyright © 2023 Cummins Inc. 396 A029X159 (Issue 31)


8-2023 9. MCM3320

Fault
Addr. Bit# System Name Event Name Response
Code
42502 25 Fault Status Bitmap 2 2647 Load Demand Setup Warning Warning
42502 26 Fault Status Bitmap 2 1444 Genset Bus Overload Warning Warning
42502 27 Fault Status Bitmap 2 1989 kW Load Control Output Limit Warning Warning
42502 28 Fault Status Bitmap 2 1991 kVAR Load Control Output Limit Warning Warning
42502 29 Fault Status Bitmap 2 1121 Failure To Disconnect Warning Warning
Synchronizer Phase Rotation Mismatch
42502 30 Fault Status Bitmap 2 1458 Warning
Warning
42502 31 Fault Status Bitmap 2 1457 Fail To Synchronize Warning Warning
42505 0 Fault Status Bitmap 1 1222 Not In Automatic Event Event
42505 1 Fault Status Bitmap 1 1483 Common Warning Event Event
42505 2 Fault Status Bitmap 1 2965 Genset Bus Available Event Event
42505 3 Fault Status Bitmap 1 2328 Utility Bus Available Event Event
42505 4 Fault Status Bitmap 1 2333 Genset Bus Connected Event Event
42505 5 Fault Status Bitmap 1 2332 Utility Bus Connected Event Event
42505 6 Fault Status Bitmap 1 2971 Test / Extended Parallel Event Event
42505 7 Fault Status Bitmap 1 1916 Synchronized Event Event
42505 8 Fault Status Bitmap 1 1534 Load Control Output Event Event
42505 9 Fault Status Bitmap 1 2781 Genset Source Unloaded Event Event
42505 10 Event Status Bitmap 1 2779 Utility Source Unloaded Event Event
42505 11 Event Status Bitmap 1 3226 Genset Bus Base Load Event Event
42505 12 Event Status Bitmap 1 3227 Utility Bus Peak Shave Event Event

9.3 MCM3320 Modbus Address 42506, 42507


NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

A029X159 (Issue 31) 397 Copyright © 2023 Cummins Inc.


9. MCM3320 8-2023

Metering Fault Status Bitmaps


Bit (LSB = 0) Parameter Metering Fault Status Bitmaps
0 ZXA Timeout Zero Crossing cannot be detected on L1 voltage signal
1 ZXB Timeout Zero Crossing cannot be detected on L2 voltage signal
2 ZXC Timeout Zero Crossing cannot be detected on L3 voltage signal
Voltage scaling error due to incompatible combination of
3 (See Note 1) Voltage Out of Range settings for Nominal Voltage, PT Primary Voltage, and PT
Secondary Voltage
Current Input is saturated; actual current cannot be
4 (See Note 1) Current Out of Range
determined
Frequency Out of
5 Frequency input is out of range; valid range 24-80 Hz
Range
Loss Phase Out of One or more zero crossings of voltage cannot be
6
Range detected; loss phase cannot be determined
Synchronizer phase difference cannot be measured due
to any of the following: genset frequency out of range,
Sync Phase Out of
7 utility frequency out of range, genset L1 voltage zero
Range
crossing not detected, or utility L1 voltage zero crossing
not detected
kW is out of range; valid range is - 2147483648 to
8 (See Note 1) kW Out of Range
+2147483647 kW
kVAR is out of range; valid range is - 2147483648 to
9 (See Note 1) kVAR Out of Range
+2147483647 kVAR
10 (See Note 1) kVA Out of Range kVA is out of range; valid range is 0 to 4294867295 kVA
Power Factor Out of Power factor is out of range due to either kW > kVA or
11 (See Note 1)
Range kVA = 0; should not normally occur
Main processor is unable to communicate with metering
12 AC Metering Failure
processor
13 Not Implemented
14 Not Implemented
15 Not Implemented
NOTE:
1. If any of bits are active (1), the "AC Metering Out of Range Warning" fault
will be active.
2. If Bit 12 is active (1), the "Hardware Failure Warning" fault will be active.
3. Some bits do not generate warning faults because they are a normal occurrence (e.g. if a source is dead).

Copyright © 2023 Cummins Inc. 398 A029X159 (Issue 31)


10 PC500/550 Modbus TCP Register Map
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

PC500/550 (PC5xx)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40001 U ENUM 64= PC500/PC550
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40002 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40003 U Configurable from User Interface
Sensor assigned to Analog Input on No scaling is required. The scaled
40004 S NA
PC5xx value is displayed.
Sensor assigned to Discrete Input 1 on
40005 U NA
PC5xx
Sensor assigned to Discrete Input 2 on
40006 U NA
PC5xx
Sensor assigned to Discrete Output 1
40007 U NA
status on PC5xx
Sensor assigned to Discrete Output 2
40008 U NA
status on PC5xx
PC500/550 (Device 1)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40011 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40012 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40013 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40014 U ENUM
2=Not Communicating
Communications Error Counter 40015 U

A029X159 (Issue 31) 399 Copyright © 2023 Cummins Inc.


10. PC500/550 Modbus TCP Register Map 8-2023

Last Successful Communication


40016 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40017 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40018 U Bitfield See Note 5
(Seconds, Milliseconds)
PC500/550 (Device 2)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40021 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40022 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40023 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40024 U ENUM
2=Not Communicating
Communications Error Counter 40025 U
Last Successful Communication
40026 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40027 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40028 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 3)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40031 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40032 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40033 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40034 U ENUM
2=Not Communicating
Communications Error Counter 40035 U
Last Successful Communication
40036 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40037 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40038 U Bitfield See Note 5
(Seconds, Milliseconds)

Copyright © 2023 Cummins Inc. 400 A029X159 (Issue 31)


8-2023 10. PC500/550 Modbus TCP Register Map

PC500/550 (Device 4)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40041 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40042 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40043 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40044 U ENUM
2=Not Communicating
Communications Error Counter 40045 U
Last Successful Communication
40046 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40047 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40048 U Bitfield See Note 5
(Seconds, Milliseconds)
PC500/550 (Device 5)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40051 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40052 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40053 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40054 U ENUM
2=Not Communicating
Communications Error Counter 40055 U
Last Successful Communication See Note 5
40056 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40057 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40058 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 6)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40061 U ENUM 1=Genset, 2=ATS, 4=AUX101/102

A029X159 (Issue 31) 401 Copyright © 2023 Cummins Inc.


10. PC500/550 Modbus TCP Register Map 8-2023

0=N/A, 1=3300, 2=2300, 4=1301,


Device Model 40062 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40063 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40064 U ENUM
2=Not Communicating
Communications Error Counter 40065 U
Last Successful Communication See Note 5
40066 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40067 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40068 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 7)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40071 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40072 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40073 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40074 U ENUM
2=Not Communicating
Communications Error Counter 40075 U
Last Successful Communication See Note 5
40076 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40077 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40078 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 8)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40081 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40082 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40083 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40084 U ENUM
2=Not Communicating

Copyright © 2023 Cummins Inc. 402 A029X159 (Issue 31)


8-2023 10. PC500/550 Modbus TCP Register Map

Communications Error Counter 40085 U


Last Successful Communication See Note 5
40086 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40087 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40088 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 9)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40091 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40092 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40093 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40094 U ENUM
2=Not Communicating
Communications Error Counter 40095 U
Last Successful Communication See Note 5
40096 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40097 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40098 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 10)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40101 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40102 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40103 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40104 U ENUM
2=Not Communicating
Communications Error Counter 40105 U
Last Successful Communication See Note 5
40106 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40107 U Bitfield
(Day, Hour, Minutes)

A029X159 (Issue 31) 403 Copyright © 2023 Cummins Inc.


10. PC500/550 Modbus TCP Register Map 8-2023

Last Successful Communication See Note 5


40108 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 11)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40111 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40112 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40113 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40114 U ENUM
2=Not Communicating
Communications Error Counter 40115 U
Last Successful Communication See Note 5
40116 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40117 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40118 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 12)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40121 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40122 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40123 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40124 U ENUM
2=Not Communicating
Communications Error Counter 40125 U
Last Successful Communication See Note 5
40126 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40127 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40128 U Bitfield
(Seconds, Milliseconds)

Copyright © 2023 Cummins Inc. 404 A029X159 (Issue 31)


8-2023 10. PC500/550 Modbus TCP Register Map

NOTES:
1. Modbus TCP can be enabled/disabled in the PC500/550 User Interface (Setup > Modbus Settings).
2. Default Modbus TCP port is 502 and is configurable in the PC500/550 User Interface (Setup > Modbus Settings).
No more than 2 Modbus TCP sessions can be established at a time.
3. PC5xx provides READ ONLY access over Modbus TCP.
4. PC500/550 registers return details about all configured devices in PC5xx (Generator Set, ATS, AUX101/102) and
can be accessed using Modbus TCP Unit ID 255 (default for PC500/550).
5. In PC500/550 registers, Devices 1 through 12 are numbered in the same order as they are arranged in the
Interface Device Configuration grid. To access details of these devices over Modbus TCP, the user must use the
Modbus TCP Unit ID (returned by register 4xxx3) in the query.
6. Bitmap registers indicating Last Successful Communication (4xxx6, 4xxx7, 4xxx8) are formatted as below:

7. Site IOs (sensors) and AUX101/102 data cannot be accessed over Modbus TCP.

Generator Set
Modbus
Scale Sign Units Description Comments
Register
40001 1 U ENUM Switch Position 0=Off, 1=AUTO, 2=Manual
0=Stopped, 1=Pending, 2=Warm
Up, 3=Running, 4=Cool Down
40002 1 U ENUM Control State (rated),
5=Cool Down (idle)
40003 1 U Fault Code
0=Normal, 1=Warning,
2=Derate,
40004 1 U ENUM Fault Type
3=Shutdown w/Cooldown,
4=Shutdown
40005 1 U Bitfield NFPA110 See Table 3 on page 11
40006 1 U Bitfield NFPA Extended See Table 4 on page 11
40007 1 U Volts L1N Voltage
40008 1 U Volts L2N Voltage
40009 1 U Volts L3N Voltage
40010 1 U Volts L1L2 Voltage
40011 1 U Volts L2L3 Voltage
40012 1 U Volts L3L1 Voltage
40013 1 U Amps L1 Current

A029X159 (Issue 31) 405 Copyright © 2023 Cummins Inc.


10. PC500/550 Modbus TCP Register Map 8-2023

Generator Set
Modbus
Scale Sign Units Description Comments
Register
40014 1 U Amps L2 Current
40015 1 U Amps L3 Current
40016 1 S kVA Total kVA
40017 0.01 U Hz Frequency
40018 0.1 U % PercentAmps APhase
40019 0.1 U % PercentAmps BPhase
40020 0.1 U % PercentAmps CPhase
40021 1 S kW Total kW
40022 0.01 S Total Power Factor
40023 0.01 S Volts Battery Voltage
40024 0.1 S psi Oil Pressure
40025 0.1 S _F Oil Temperature
40026 0.1 S _F Coolant Temperature
40027 1 U GPH Fuel Rate
40028 0.1 U Gallons Fuel Level
40029 1 U RPM Average Engine Speed
40030 1 U Engine Starts
40031 0.1 U Hours Engine Runtime

ATS
Modbus
Scale Sign Units Description Comments
Register
0=Test 1=Utility/Genset,
40001 1 U ENUM Mode 2=Utility/Utility,
3=Genset/Genset
0=None,
1=EngineStartASource2,
2=EngineStartBSource1,
3=NormaltoEmergency (TDNE),
4=EmergencytoNormal (TDEN),
40002 1 U ENUM Active Transfer Timer 5=EngineCooldownA (TDECa),
6=EngineCooldownB (TDECb),
7=ProgramTransition (TDPT),
8=Transfer Pend./Elevator
(TDEL),
255=Unknown

Copyright © 2023 Cummins Inc. 406 A029X159 (Issue 31)


8-2023 10. PC500/550 Modbus TCP Register Map

ATS
Modbus
Scale Sign Units Description Comments
Register
40003 1 U Fault Code
40004 1 U ENUM Fault Type 0=No Faults, 1=Warning
40005 1 U Bitfield NFPA110 See Table 5 on page 12
40006 1 U Bitfield NFPA Extended See Table 6 on page 12
40007 1 U Volts L1N Voltage (Load)
40008 1 U Volts L2N Voltage (Load)
40009 1 U Volts L3N Voltage (Load)
40010 1 U Volts L1L2 Voltage (Load)
40011 1 U Volts L2L3 Voltage (Load)
40012 1 U Volts L3L1 Voltage (Load)
40013 1 U Amps L1 Current (Load)
40014 1 U Amps L2 Current (Load)
40015 1 U Amps L3 Current (Load)
40016 1 S kW Total kW (Load)
40017 0.01 S Total Power Factor (Load)
40018 1 S kVAR Total kVAR (Load)
40019 1 S kVA Total kVA (Load)
40020 0.01 U Hz Frequency (Load)
40021 0.1 U % PercentAmps APhase (Load)
40022 0.1 U % PercentAmps BPhase (Load)
40023 0.1 U % PercentAmps CPhase (Load)
40024 1 U Volts L1N Voltage Source1
40025 1 U Volts L2N Voltage Source1
40026 1 U Volts L3N Voltage Source1
40027 1 U Volts L1L2 Voltage Source1
40028 1 U Volts L2L3 Voltage Source1
40029 1 U Volts L3L1 Voltage Source1
40037 0.01 U Hz Frequency Source1
40041 1 U Volts L1N Voltage Source2
40042 1 U Volts L2N Voltage Source2
40043 1 U Volts L3N Voltage Source2
40044 1 U Volts L1L2 Voltage Source2

A029X159 (Issue 31) 407 Copyright © 2023 Cummins Inc.


10. PC500/550 Modbus TCP Register Map 8-2023

ATS
Modbus
Scale Sign Units Description Comments
Register
40045 1 U Volts L2L3 Voltage Source2
40046 1 U Volts L3L1 Voltage Source2
40054 0.01 U Hz Frequency Source2

Copyright © 2023 Cummins Inc. 408 A029X159 (Issue 31)


11 PC40
11.1 PC40 Modbus Register Map
11.1.1 PC40 Modbus Parametric Data

TABLE 23. PC40 MODBUS PARAMETRIC DATA

Address System Name Access Specifications System Description


401149 S1 Frequency Read Only Multiplier: 0.1 Measured Frequency
Size (Bits): 16
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 70
Default:
401150-51 S1 L1-N RMS Voltage Read Only Multiplier: 0.1 RMS Voltage
Size (Bits): 32 between Line 1 and
Sign: U Neutral
Unit: V
Lower Limit: 0
Upper Limit: 18,000
Default:
401154-53 S1 L2-N RMS Voltage Read Only Multiplier: 0.1 RMS Voltage
Size (Bits): 32 between Line 2 and
Sign: U Neutral
Unit: V
Lower Limit: 0
Upper Limit: 18,000
Default:
401154-55 S1 L3-N RMS Voltage Read Only Multiplier: 0.1 RMS Voltage
Size (Bits): 32 between Line 3 and
Sign: U Neutral
Unit: V
Lower Limit: 0
Upper Limit: 18,000
Default:

A029X159 (Issue 31) 409 Copyright © 2023 Cummins Inc.


11. PC40 8-2023

Address System Name Access Specifications System Description


401156-57 S1 L1-L2 RMS Read Only Multiplier: 0.1 RMS Voltage
Voltage Size (Bits): 32 between Line 1 and
Sign: U Line 2
Unit: V
Lower Limit: 0
Upper Limit: 30,000
Default:
401158-59 S1 L2-L3 RMS Read Only Multiplier: 0.1 RMS Voltage
Voltage Size (Bits): 32 between Line 2 and
Sign: U Line 3
Unit: V
Lower Limit: 0
Upper Limit: 30,000
Default:
401160-61 S1 L3-L1 RMS Read Only Multiplier: 0.1 RMS Voltage
Voltage Size (Bits): 32 between Line 3 and
Sign: U Line 1
Unit: V
Lower Limit: 0
Upper Limit: 30,000
Default:
401162-63 S1 L1 RMS Current Read Only Multiplier: 0.1 RMS Current through
Size (Bits): 32 Line 1
Sign: U
Unit: A
Lower Limit: 0
Upper Limit: 99,999.9
Default:
401164-65 S1 L2 RMS Current Read Only Multiplier: 0.1 RMS Current through
Size (Bits): 32 Line 2
Sign: U
Unit: A
Lower Limit: 0
Upper Limit: 99,999.9
Default:
401166-67 S1 L3 RMS Current Read Only Multiplier: 0.1 RMS Current through
Size (Bits): 32 Line 3
Sign: U
Unit: A
Lower Limit: 0
Upper Limit: 99,999.9
Default:

Copyright © 2023 Cummins Inc. 410 A029X159 (Issue 31)


8-2023 11. PC40

Address System Name Access Specifications System Description


401170-71 S1 L1 kW Read Only Multiplier: 1 kW value at Line 1
Size (Bits): 32
Sign: S
Units: W
Lower Limit:
-99,999,999
Upper Limit:
99,999,999
Default:
401172-73 S1 L2 kW Read Only Multiplier: 1 kW value at Line 2
Size (Bits): 32
Sign: S
Units: W
Lower Limit:
-99,999,999
Upper Limit:
99,999,999
Default:
401174-75 S1 L3 kW Read Only Multiplier: 1 kW value at Line 3
Size (Bits): 32
Sign: S
Units: W
Lower Limit:
-99,999,999
Upper Limit:
99,999,999
Default:
401177 S2 Frequency Read Only Multiplier: 0.1 Measured Frequency
Size (Bits): 16
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 70
Default:
401178-79 S2 L1-N RMS Voltage Read Only Multiplier: 0.1 RMS Voltage
Size (Bits): 32 between Line 1 and
Sign: U Neutral
Unit: V
Lower Limit: 0
Upper Limit: 18,000
Default:

A029X159 (Issue 31) 411 Copyright © 2023 Cummins Inc.


11. PC40 8-2023

Address System Name Access Specifications System Description


401180-81 S2 L2-N RMS Voltage Read Only Multiplier: 0.1 RMS Voltage
Size (Bits): 32 between Line 2 and
Sign: U Neutral
Unit: V
Lower Limit: 0
Upper Limit: 18,000
Default:
401182-83 S2 L3-N RMS Voltage Read Only Multiplier: 0.1 RMS Voltage
Size (Bits): 32 between Line 3 and
Sign: U Neutral
Unit: V
Lower Limit: 0
Upper Limit: 18,000
Default:
401184-85 S2 L1-L2 RMS Read Only Multiplier: 0.1 RMS Voltage
Voltage Size (Bits): 32 between Line 1 and
Sign: U Line 2
Unit: V
Lower Limit: 0
Upper Limit: 30,000
Default:
401186-87 S2 L2-L3 RMS Read Only Multiplier: 0.1 RMS Voltage
Voltage Size (Bits): 32 between Line 2 and
Sign: U Line 3
Unit: V
Lower Limit: 0
Upper Limit: 30,000
Default:
401188-89 S2 L3-L1 RMS Read Only Multiplier: 0.1 RMS Voltage
Voltage Size (Bits): 32 between Line 3 and
Sign: U Line 1
Unit: V
Lower Limit: 0
Upper Limit: 30,000
Default:
401190-91 S2 L1 RMS Current Read Only Multiplier: 0.1 RMS Current through
Size (Bits): 32 Line 1
Sign: U
Unit: A
Lower Limit: 0
Upper Limit: 99,999.9
Default:

Copyright © 2023 Cummins Inc. 412 A029X159 (Issue 31)


8-2023 11. PC40

Address System Name Access Specifications System Description


401192-93 S2 L2 RMS Current Read Only Multiplier: 0.1 RMS Current through
Size (Bits): 32 Line 2
Sign: U
Unit: A
Lower Limit: 0
Upper Limit: 99,999.9
Default:
401194-95 S2 L3 RMS Current Read Only Multiplier: 0.1 RMS Current through
Size (Bits): 32 Line 3
Sign: U
Unit: A
Lower Limit: 0
Upper Limit: 99,999.9
Default:
401198-99 S2 L1 kW Read Only Multiplier: 1 kW value at Line 1
Size (Bits): 32
Sign: S
Units: W
Lower Limit:
-99,999,999
Upper Limit:
99,999,999
Default:
401200-01 S2 L2 kW Read Only Multiplier: 1 kW value at Line 2
Size (Bits): 32
Sign: S
Units: W
Lower Limit:
-99,999,999
Upper Limit:
99,999,999
Default:
401202-03 S2 L3 kW Read Only Multiplier: 1 kW value at Line 3
Size (Bits): 32
Sign: S
Units: W
Lower Limit:
-99,999,999
Upper Limit:
99,999,999
Default:

A029X159 (Issue 31) 413 Copyright © 2023 Cummins Inc.


11. PC40 8-2023

Address System Name Access Specifications System Description


401205-06 Load L1 Current Read Only Multiplier: NA RMS Current present
Size (Bits): 16 through Line 1 on the
Sign: U load side
Unit: A
Lower Limit: 0
Upper Limit: 99,999.9
Default:
401207-08 Load L2 Current Read Only Multiplier: NA RMS Current present
Size (Bits): 16 through Line 2 on the
Sign: U load side
Unit: A
Lower Limit: 0
Upper Limit: 99,999.9
Default:
401209-10 Load L3 Current Read Only Multiplier: NA RMS Current present
Size (Bits): 16 through Line 3 on the
Sign: U load side
Unit: A
Lower Limit: 0
Upper Limit: 99,999.9
Default:
401218 S1 Phase Rotation Read Only Multiplier: NA Phase rotation of the
Size (Bits): 16 source in terms of L1-
Sign: U L2-L3 or L1-L3-L2
Unit: NA
Lower Limit: 0
Upper Limit: 3
Default:
401219 S2 Phase Rotation Read Only Multiplier: NA Phase rotation of the
Size (Bits): 16 source in terms of L1-
Sign: U L2-L3 or L1-L3-L2
Unit: NA
Lower Limit: 0
Upper Limit: 3
Default:
401263-64 Load L1-N Voltage Read Only Multiplier: NA RMS Voltage
Size (Bits): 16 between Line 1 and
Sign: U Neutral
Unit: V
Lower Limit: 0
Upper Limit: 18,000
Default:

Copyright © 2023 Cummins Inc. 414 A029X159 (Issue 31)


8-2023 11. PC40

Address System Name Access Specifications System Description


401265-66 Load L2-N RMS Read Only Multiplier: NA RMS Voltage
Voltage Size (Bits): 16 between Line 2 and
Sign: U Neutral
Unit: V
Lower Limit: 0
Upper Limit: 18,000
Default:
401267-68 Load L3-N RMS Read Only Multiplier: NA RMS Voltage
Voltage Size (Bits): 16 between Line 3 and
Sign: U Neutral
Unit: V
Lower Limit: 0
Upper Limit: 18,000
Default:
401269-70 Load L1-L2 Voltage Read Only Multiplier: NA RMS Voltage
Size (Bits): 16 between Line 1 and
Sign: U Line 2
Unit: V
Lower Limit: 0
Upper Limit: 30,000
Default:
401271-72 Load L2-L3 Voltage Read Only Multiplier: NA RMS Voltage
Size (Bits): 16 between Line 2 and
Sign: U Line 3
Unit: V
Lower Limit: 0
Upper Limit: 30,000
Default:
401273-74 Load L3-L1 Voltage Read Only Multiplier: NA RMS Voltage
Size (Bits): 16 between Line 3 and
Sign: U Line 1
Unit: V
Lower Limit: 0
Upper Limit: 30,000
Default:
401275-76 Load Frequency Read Only Multiplier: NA Measured Frequency
Size (Bits): 16
Sign: U
Unit: Hz
Lower Limit: 0
Upper Limit: 70
Default:

A029X159 (Issue 31) 415 Copyright © 2023 Cummins Inc.


11. PC40 8-2023

Address System Name Access Specifications System Description


401537-38 S2 Total Watts Read Only Multiplier: 1 Sum of kW values of
Size (Bits): 32 all phases
Sign: S
Unit: W
Lower Limit:
-99,999,999
Upper Limit:
99,999,999
Default:
401539-40 S2 L1 kVA Read Only Multiplier: 1 kVA value at line 1
Size (Bits): 32
Sign: U
Unit: VA
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401541-42 S2 L2 kVA Read Only Multiplier: 1 kVA value at line 2
Size (Bits): 32
Sign: U
Unit: VA
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401543-44 S2 L3 kVA Read Only Multiplier: 1 kVA value at line 3
Size (Bits): 32
Sign: U
Unit: VA
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401545-46 S2 Total VA Read Only Multiplier: 1 Sum of kVA values of
Size (Bits): 32 all phases
Sign: U
Unit: VA
Lower Limit: 0
Upper Limit:
99,999,999
Default:

Copyright © 2023 Cummins Inc. 416 A029X159 (Issue 31)


8-2023 11. PC40

Address System Name Access Specifications System Description


401547-48 S2 L1 kVAR Read Only Multiplier: 1 kVAR value at line 1
Size (Bits): 32
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401549-50 S2 L2 kVAR Read Only Multiplier: 1 kVAR value at line 2
Size (Bits): 32
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401551-52 S2 L3 kVAR Read Only Multiplier: 1 kVAR value at line 3
Size (Bits): 32
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401553-54 S2 Total VAR Read Only Multiplier: 1 Sum of kVAR values
Size (Bits): 32 of all phases
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401555 S2 L1 Power Factor Read Only Multiplier: 0.01 Power factor at line 1
Size (Bits): 16
Sign: S
Unit: NA
Lower Limit: –1
Upper Limit: 1
Default:

A029X159 (Issue 31) 417 Copyright © 2023 Cummins Inc.


11. PC40 8-2023

Address System Name Access Specifications System Description


401556 S2 L2 Power Factor Read Only Multiplier: 0.01 Power factor at line 2
Size (Bits): 16
Sign: S
Unit: NA
Lower Limit: –1
Upper Limit: 1
Default:
401557 S2 L3 Power Factor Read Only Multiplier: 0.01 Power factor at line 3
Size (Bits): 16
Sign: S
Unit: NA
Lower Limit: –1
Upper Limit: 1
Default:
401558 S2 Average Power Read Only Multiplier: 0.01 Average power factor
Factor Size (Bits): 16 of all the line power
Sign: S factors
Unit: NA
Lower Limit: –1
Upper Limit: 1
Default:
401561-562 S1 Total Watts Read Only Multiplier: 1 Sum of kW values of
Size (Bits): 32 all phases
Sign: U
Unit: VAR
Lower Limit:
-99,999,999
Upper Limit:
99,999,999
Default:
401563-64 S1 L1 kVA Read Only Multiplier: 1 kVA value at line 1
Size (Bits): 32
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:

Copyright © 2023 Cummins Inc. 418 A029X159 (Issue 31)


8-2023 11. PC40

Address System Name Access Specifications System Description


401565-66 S1 L2 kVA Read Only Multiplier: 1 kVA value at line 2
Size (Bits): 32
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401567-68 S1 L3 kVA Read Only Multiplier: 1 kVA value at line 3
Size (Bits): 32
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401569-70 S1 Total VA Read Only Multiplier: 1 Sum of kVA values of
Size (Bits): 32 all phases
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401571-72 S1 L1 kVAR Read Only Multiplier: 1 kVAR value at line 1
Size (Bits): 32
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401573-74 S1 L2 kVAR Read Only Multiplier: 1 kVAR value at line 2
Size (Bits): 32
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:

A029X159 (Issue 31) 419 Copyright © 2023 Cummins Inc.


11. PC40 8-2023

Address System Name Access Specifications System Description


401575-76 S1 L3 kVAR Read Only Multiplier: 1 kVAR value at line 3
Size (Bits): 32
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401577-78 S1 Total VAR Read Only Multiplier: 1 Sum of kVAR values
Size (Bits): 32 of all phases
Sign: U
Unit: VAR
Lower Limit: 0
Upper Limit:
99,999,999
Default:
401579 S1 L1 Power Factor Read Only Multiplier: 0.01 Power factor at line 1
Size (Bits): 16
Sign: S
Unit: NA
Lower Limit: –1
Upper Limit: 1
Default:
401580 S1 L2 Power Factor Read Only Multiplier: 0.01 Power factor at line 2
Size (Bits): 16
Sign: S
Unit: NA
Lower Limit: –1
Upper Limit: 1
Default:
401581 S1 L3 Power Factor Read Only Multiplier: 0.01 Power factor at line 3
Size (Bits): 16
Sign: S
Unit: NA
Lower Limit: –1
Upper Limit: 1
Default:
401582 S1 Average Power Read Only Multiplier: 0.01 Average power factor
Factor Size (Bits): 16 of all the line power
Sign: S factors
Unit: NA
Lower Limit: –1
Upper Limit: 1
Default:

Copyright © 2023 Cummins Inc. 420 A029X159 (Issue 31)


8-2023 11. PC40

Address System Name Access Specifications System Description


401801-02 S2 Total Exported Read Only Multiplier: 0.1 Total exported kWh
kWh Size (Bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4.29 x
10^9
Default:
401805-06 S2 Total kVAh Read Only Multiplier: 0.1 Total kVAh
Size (Bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4.29 x
10^9
Default:
401807-08 S2 Total Exported Read Only Multiplier: 0.1 Total exported kVArh
kVArh Size (Bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4.29 x
10^9
Default:
401811-12 S1 Total Exported Read Only Multiplier: 0.1 Total exported kWh
kWh Size (Bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4.29 x
10^9
Default:
401815-16 S1 Total kVAh Read Only Multiplier: 0.1 Total kVAh
Size (Bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4.29 x
10^9
Default:

A029X159 (Issue 31) 421 Copyright © 2023 Cummins Inc.


11. PC40 8-2023

Address System Name Access Specifications System Description


401817-18 S1 Total Exported Read Only Multiplier: 0.1 Total exported kVArh
kVArh Size (Bits): 32
Sign: U
Unit: kWh
Lower Limit: 0
Upper Limit: 4.29 x
10^9
Default:

11.1.2 Alarm Condition Codes


TABLE 24. ALARM CONDITION CODES

Condition Description
0 Disabled Digital Input
1 Not Active Alarm
2 Warning Alarm
3 Shutdown Alarm
4 Electrical Trip Alarm
5–7 Reserved
8 Inactive Indication (No String)
9 Inactive Indication (Displayed String)
10 Active Indication
11–14 Reserved
15 Unimplemented Alarm

Copyright © 2023 Cummins Inc. 422 A029X159 (Issue 31)


8-2023 11. PC40

11.1.3 Modbus Alarms


TABLE 25. MODBUS ALARMS

Address Bits System Name Access Specifications System


Description
439426 1/16 - S2 Failure Unlatched Read Size (Bits): 16 See Alarm Source 2 failure
4/16 Only Sign: U Condition unlatched alarm
Codes
439426 5/16 - S2 Failure Latched Read Size (Bits): 16 Source 2 failure
8/16 Only Sign: U latched alarm

439426 9/16 - Battery Low Voltage Read Size (Bits): 16 Battery low
12/16 Only Sign: U voltage alarm

439426 13/16 - Battery High Voltage Read Size (Bits): 16 Battery high
16/16 Only Sign: U voltage alarm

439427 1/16 - Fail to Stop Read Size (Bits): 16 Genset failed to


4/16 Only Sign: U stop alarm

439427 5/16 - Fail to Start Read Size (Bits): 16 Genset failed to


8/16 Only Sign: U start alarm

439427 9/16 - S1 Failure Unlatched Read Size (Bits): 16 Source 1 failure


12/16 Only Sign: U unlatched alarm

439427 13/16 - S1 Failure Latched Read Size (Bits): 16 Source 1 failure


16/16 Only Sign: U latched alarm

439428 9/16 - Failed to Reach Read Size (Bits): 16 Genset failed to


12/16 Loading Frequency Only Sign: U reach loading
frequency
439428 13/16 - Failed to Reach Read Size (Bits): 16 Genset failed to
16/16 Loading Voltage Only Sign: U reach loading
voltage

A029X159 (Issue 31) 423 Copyright © 2023 Cummins Inc.


11. PC40 8-2023

This page is intentionally blank.

Copyright © 2023 Cummins Inc. 424 A029X159 (Issue 31)


12 PC80
12.1 General Instructions
12.1.1 Modbus Protocol Application Guide Notes
1) Modbus Supported Functions
The control supports the following Modbus function codes:
• Read Holding Registers (Function Code 03)
• Read Input Registers (Function Code 04)
• Write Single Holding Register (Function Code 06)
• Write Multiple Holding Registers (Function Code 16)

The control shall respond to any function code other than those listed above by sending an exception
response of Illegal Function (01).

A. Read Holding Registers


The control provides the ability to read 1 to 125 consecutive holding registers.
The control shall respond to any read request to address not defined in the control by returning 0xFFFF
data for that address.

The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the holding register read request is not defined on the control.
• The first register in the holding register read request does not allow for the full representation of a
numeric value. This would occur if the first register in the read request is not mapped to the most
significant 2 bytes of a binary value parameter.
• The last register in the holding register read request does not allow for the full representation of a
numeric value. This would occur if the last register in the read request is not mapped to the least
significant 2 bytes of a binary value parameter.

Read requests for string type parameters where not every register associated with the string is in the
request shall return only the requested portion of the string.

B. Read Input Registers


The control provides the ability to read 1 to 125 consecutive input registers.

The control shall respond to any read request to address not defined in the control by returning 0xFFFF
data for that address.

A029X159 (Issue 31) 425 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the input register read request is not defined on the control.
• The first register in the input register read request does not allow for the full representation of a
numeric value. This would occur if the first register in the read request is not mapped to the most
significant 2 bytes of a parameter.
• The last register in the input register read request does not allow for the full representation of a
numeric value. This would occur if the last register in the read request is not mapped to the least
significant 2 bytes of a parameter.

The Input Registers support by each port on the control are listed in the Read Input Registers Table
below.

C. Write Single Holding Register

The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The register in the holding register write request is not defined on the control.
• The register in the holding register write request does not allow for the full writing of a numeric value.
This would occur if the register is part of a numeric parameter that requires more than one address
to represent.
• If writing to a string values, the register in the holding register write request is not the first register of
that string.

Write requests for string type parameters where not every register associated with the string is in the
request shall write only the requested portion of the string.

Write requests to this control may return an Illegal Data Value exception code 03. This means that the
requested write failed to occur.

D. Write Multiple Holding Registers


The control provides the ability to write to 1 to 123 consecutive holding registers.
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the holding register write request is not defined on the control.
• The first register in the holding register write request does not allow for the full writing of a numeric
value. This would occur if the first register in the write request is not mapped to the most significant
2 bytes of a parameter.
• The last register in the holding register write request does not allow for the full writing of a numeric
value. This would occur if the last register in the write request is not mapped to the least significant 2
bytes of a parameter.
• If string values are in the write request, the first register for any string is not within the requested
register range.

Write requests for string type parameters where not every register associated with the string is in the
request shall write only the requested portion of the string.

Copyright © 2023 Cummins Inc. 426 A029X159 (Issue 31)


8-2023 12. PC80

Write requests to this control may return an Illegal Data Value exception code 03. This means that some
or all of the requested writes failed to occur. It is the responsibility of the requestor to read the data again
to determine which parameters were not written to their requested new values and to respond as
necessary.

For any of these function codes, if there is an internal problem within the control software that prevents the
control from completing the requested action, the control will return a Server Device Failure exception
code of 04.

For any of these function codes while using Modbus TCP only, if data requests come from the Client and
fill up internal Modbus TCP Server message queue's faster than the protocol can process these data
requests, the control will return a Slave Device Busy exception code of 06.

2) Modbus RTU Serial Port Configuration Options

The following configuration options shall be available for each port the control that supports the Modbus
RTU protocol. See the controller Modbus register map for individual register assignments for these
parameters on any given port.

TABLE 26. MODBUS RTU SERIAL PORT CONFIGURATION OPTIONS

Parameter Name Description Specification


Modbus Node Address Sets this ports node address. Multiplier: 1
Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 247
Modbus Baud Rate Sets this ports baud rate. 0: 2400
1: 4800
2: 9600
3: 19200
4: 28800
5: 38400
6: 57600
7: 115200
Modbus Parity and Stop Bit Selection Sets this ports parity and stop bit 0: Even Parity (1 Stop)
communications settings. 1: Odd Parity (1 Stop)
2: No Parity (2 Stop)
3: No Parity (1 Stop)

A029X159 (Issue 31) 427 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Parameter Name Description Specification


Modbus Failure Time Delay Sets the time delay for the detection Multiplier: 1
of the lack of Modbus packets on the Offset: 0
communications bus. Size (bits): 8
Sign: U
Unit: seconds
Lower Limit: 1
Upper Limit: 60

NOTICE
Changes to the Modbus Baud Rate and the Modbus Parity and Stop Bit Selection parameters will
immediately be reflected on the serial port being configured. Any Modbus commands in progress
on that port in the old communications settings will fail until the Modbus master also updates its
communications settings to match those of the slave.

3) Modbus TCP Port Configuration Options


The following configuration options shall be available for the Modbus TCP port. See the controller Modbus
register map for individual register assignments for these parameters.

TABLE 27. MODBUS TCP PORT CONFIGURATION OPTIONS

Parameter Name Description Specification


Modbus TCP Unit Identifier Sets the Unit Identifier (UID) (i.e. the Multiplier: 1
Server Device Address) for Modbus Offset: 0
TCP Server. Size (bits): 8
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 255
Modbus TCP Port1 Number Sets the number for Port1 of Modbus Multiplier: 1
TCP Server. User can Set this Offset: 0
number as per requirement - default Size (bits): 16
is 502. Can be set to any value >1024
Sign: U
up to 65535. The number should be
unique between Modbus TCP Port1 Unit:
and Port2. One of the Modbus TCP Lower Limit: 0
ports must be set to default value Upper Limit: 65535
502. Default: 502

Copyright © 2023 Cummins Inc. 428 A029X159 (Issue 31)


8-2023 12. PC80

Parameter Name Description Specification


Modbus TCP Port2 Number Sets the number for Port2 of Modbus Multiplier: 1
TCP Server. User can Set this Offset: 0
number as per requirement - default Size (bits): 16
is 502. Can be set to any value >1024
Sign: U
up to 65535. The number should be
unique between Modbus TCP Port1 Unit:
and Port2. One of the Modbus TCP Lower Limit: 0
ports must be set to default value Upper Limit: 65535
502. Default: 1025
Modbus TCP Session Inactivity Sets the Modbus TCP Session Multiplier: 1
Timeout Inactivity/Timeout. The Offset: 0
interval/timeout is for detection of the Size (bits): 8
lack of Modbus TCP packets in a
Sign: U
session (on the socket). Common
timeout period for every session. If Unit: seconds
the inactivity timer for a session Lower Limit: 1
expires, the Modbus TCP Server will Upper Limit: 60
disconnect from the socket Default: 10
maintaining that session.

4) Modbus Extended Status Information

The control represents abnormal states in the data by using the five most positive values of the data to
convey that these abnormal states exist. The states will only be applicable to numeric parameters with the
following data types:
• UINT8, INT8, UINT16, INT16, UINT32, INT32, UINT64, INT64, FLOAT32 (signed and unsigned 8 bit
thru 64-bit parameters and 32-bit floating-point parameters)

Note that enumerated parameters and parameters with a floating-point data type will not follow this
abnormal state representation methods.

The following abnormal states are supported:


• Unsupported (Not Available) Data: “Not Available” data shall be represented as the highest
positive value for that parameter. For example, for a two-byte unsigned integer the value would be
65535. For a signed two-byte integer the value would be 32767. For a 32-bit floating-point value this
would be 3.4028234663852886 x 10^38.
◦ Parameters which are not available due to the sensor not being installed or not enabled in the
controller’s configuration will be classified as this.
• Network Failed Data: “Network Failure” data shall be represented as three · less than the highest
positive value for that parameter. For example, for a two-byte unsigned integer the value would be
65532. For a signed two-byte integer the value would be 32764. For a 32-bit floating-point value this
would be 3.4028228579130005 x 10^38.
◦ Data that comes from a network that has failed such as sensor data coming from I/O modules
on a PCCnet or CAN network will be classified as this.

A029X159 (Issue 31) 429 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

• Hardware/Component Failure: “Hardware/Component Failure” data shall be represented as four


less than the highest positive value for that parameter. For example, for a two-byte unsigned integer,
the value would be 65531. For a signed two-byte integer the value would be 32763. For a 32-bit
floating-point value this would be 3.4028226550889045 x 10^38
◦ An on-controller hardware/component failure that provides data like voltage, current and power
for example will be classified as this.
• Out of Range High/Out of Range: “Out of Range High/Out of Range” data shall be represented as
one less than the highest positive value for that parameter. For example, for a two-byte unsigned
integer the value would be 65534. For a signed two-byte integer the value would be 32766. For a
32-bit floating-point value this would be 3.4028232635611926 x 10^38
◦ Data that has been determined to be out of range high or out of range (when there is no
distinction between out of range high and out of range low) due to an open sensor for
example, will be classified as this.
• Out of Range Low: “Out of Range Low” data shall be represented as two less than the highest
positive value for that parameter. For example, for a two-byte unsigned integer the value would be
65533. For a signed two-byte integer the value would be 32765. For a 32-bit floating-point value this
would be 3.4028230607370965 x 10^38
◦ Data that has been determined to be out of range high or out of range (when there is no
distinction between out of range high and out of range low) due to an open sensor, for
example, will be classified as this.

Note that this leaves the usable data range for extended data types to the following:
• For unsigned integer datatypes: 0 to (2^size - 6)
• For signed datatypes: -2^(size/2) to (2^(size/2) - 6)
• For float32: -3.4028234663852886 x 10+38 to +3.4028224522648084 x 10+38

5) Working with 8-Bit Data Types

When reading a register that contains information in an 8-bit data type, the data will be put the least
significant byte of the register. If the data type is unsigned, the upper byte will be populated with zero's. If
the data type is signed, the upper byte will be sign extended with the sign bit value of the data byte.

When writing a register that contains information that is expected to be in an 8-bit data type, the control
will expect the data to be in the least significant byte of the register and ignore the upper byte.

6) Representation of Multi-Register Parameters

For numeric parameters requiring more than one Register to represent the data, the Register Address
listed in the Controller’s Modbus Register Map represents the most significant 2 bytes of the data. The
additional bytes of the data will always be provided in Register Address + 1, Register Address + 2, and
Register Address +3 as appropriate.

Copyright © 2023 Cummins Inc. 430 A029X159 (Issue 31)


8-2023 12. PC80

For string parameters, the first two characters in the string will be mapped to the Register Address listed in
the Controllers Modbus Register Map. Additional characters will be provided in the following registers. For
example, for the string "String1" at address 40031, the characters will be mapped the following registers:
40031: "St" 40032: "ri" 40033: "ng" 40034: "1_"

7) Modbus RTU Slave Protocol Support for Read Input Registers

Each port instance of Modbus RTU Slave Protocol shall support interface to the following read input
registers through function code 04. These are the only input registers supported by this control.

The following table applies for each instance of the Modbus RTU protocol on any control and will return
the data from the port being read only.

TABLE 28. READ INPUT REGISTERS TABLE

Register Name Description Data Type Size Scaling Factor


Address
30001 Bus Message This parameter uint32 2 registers 1
Count contains the
quantity of
messages that
this port has
detected on the
communications
system since its
last restart, clear
counters
operation, or
power–up.
30003 Bus CRC Error This parameter uint32 2 registers 1
Count stores quantity of
CRC errors
encountered by
this port since its
last restart, clear
counters
operation, or
power–up.
30005 Bus Exception This parameter uint32 2 registers 1
Error Count contains the
quantity of
exception
responses
returned by this
port since its last
restart, clear
counters
operation, or
power–up.

A029X159 (Issue 31) 431 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Register Name Description Data Type Size Scaling Factor


Address
30007 Server No This parameter uint32 2 registers 1
Response Count contains the
quantity of
messages
addressed to this
port for which it
has returned no
response since its
last restart, clear
counters
operation, or
power–up.
30009 Server Message The parameter uint32 2 registers 1
Count contains the
quantity of
messages
addressed to this
port that it has
processed since
its last restart,
clear counters
operation, or
power–up.
30011 Modbus Time This parameter uint8 1 register 1
Stamp at Counter holds the year of
Reset - Year the time stamp
record when
counters were
cleared last time.
30012 Modbus Time This parameter uint8 1 register 1
Stamp at Counter holds the month
Reset - Month of the time stamp
record when
counters were
cleared last time.
30013 Modbus Time This parameter uint8 1 register 1
Stamp at Counter holds the day of
Reset - Date the month of the
time stamp record
when counters
were cleared last
time.
30014 Modbus Time This parameter uint8 1 register 1
Stamp at Counter holds the hour of
Reset – Hour the time stamp
record when
counters were
cleared last time.

Copyright © 2023 Cummins Inc. 432 A029X159 (Issue 31)


8-2023 12. PC80

Register Name Description Data Type Size Scaling Factor


Address
30015 Modbus Time This parameter uint8 1 register 1
Stamp at Counter holds the minute
Reset - Minute of the time stamp
record when
counters were
cleared last time.
30016 Modbus Time This parameter uint8 1 register 1
Stamp at Counter holds the seconds
Reset - Seconds of the time stamp
record when
counters were
cleared last time.
30017 Modbus Time This parameter uint32 2 registers 1
Since Last maintains the time
Counter Reset in seconds since
the last reset of
Modbus
diagnostic
counters.

8) Modbus TCP Protocol (Server) Support for Read Input Registers

Modbus TCP Protocol (server) implementation shall support interface to the following read input registers
through function code 04. These are the only input registers supported by this control.

The following table applies for the only instance of the Modbus TCP protocol on any control and will return
the data from the port being read only.

TABLE 29. READ INPUT REGISTERS TABLE

Register Name Description Data Type Size Scaling Factor


Address
30019 Modbus TCP This parameter uint32 2 registers 1
Port1 Message contains the
Count quantity of
messages that
this port has
detected on the
communications
system since its
last restart, clear
counters
operation, or
power-up.

A029X159 (Issue 31) 433 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Register Name Description Data Type Size Scaling Factor


Address
30021 Port1 This parameter uint32 2 registers 1
Communication stores quantity of
Error count errors
encountered at
port 1 of Modbus
TCP since its last
restart, clear
counters
operation, or
power–up.
30023 Modbus TCP This parameter uint32 2 registers 1
Port1 Exception contains the
Count quantity of
exception
responses
returned by this
port since its last
restart, clear
counters
operation, or
power–up.
30025 Modbus TCP This parameter uint32 2 registers 1
Port1 No contains the
Response Count quantity of
messages
addressed to this
port for which it
has returned no
response since its
last restart, clear
counters
operation, or
power–up.
30027 ModbusTCPPort1 This parameter uint8 1 register 1
Time Stamp At holds the year of
Counter Reset- the time stamp
Year record when
counters were
cleared last time.
30028 ModbusTCPPort1 This parameter uint8 1 register 1
Time Stamp At holds the month
Counter Reset- of the time stamp
Month record when
counters were
cleared last time.

Copyright © 2023 Cummins Inc. 434 A029X159 (Issue 31)


8-2023 12. PC80

Register Name Description Data Type Size Scaling Factor


Address
30029 ModbusTCPPort1 This parameter uint8 1 register 1
Time Stamp At holds the day of
Counter Reset- the month of the
Date time stamp record
when counters
were cleared last
time.
30030 ModbusTCPPort1 This parameter uint8 1 register 1
Time Stamp At holds the hour of
Counter Reset- the time stamp
Hour record when
counters were
cleared last time.
30031 ModbusTCPPort1 This parameter uint8 1 register 1
Time Stamp At holds the minute
Counter Reset- of the time stamp
Min record when
counters were
cleared last time.
30032 ModbusTCPPort1 This parameter uint8 1 register 1
Time Stamp At holds the seconds
Counter Reset- of the time stamp
Sec record when
counters were
cleared last time.
30033 Modbus TCP This parameter uint8 1 register 1
Port1 Time Since maintains the time
Last Counter in seconds since
Reset the last reset of
Modbus
diagnostic
counters.
30035 Modbus TCP This parameter uint8 1 register 1
Port2 Message contains the
Count quantity of
messages that
this port has
detected on the
communications
system since its
last restart, clear
counters
operation, or
power–up.

A029X159 (Issue 31) 435 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Register Name Description Data Type Size Scaling Factor


Address
30037 Port2 This parameter uint32 2 registers 1
Communication contains the
Error count quantity of errors
encountered at
port 2 of modbus
TCP since its last
restart, clear
counters
operation, or
power–up.
30039 Modbus TCP This parameter uint32 2 registers 1
Port2 Exception stores quantity of
Count errors
encountered at
port 2 of Modbus
TCP since its last
restart, clear
counters
operation, or
power–up.
30041 Modbus TCP This parameter uint32 2 registers 1
Port2 No contains the
Response Count quantity of
messages
addressed to this
port for which it
has returned no
response since its
last restart, clear
counters
operation, or
power–up.
30043 ModbusTCPPort2 This parameter uint8 1 register 1
Time Stamp At holds the year of
Counter Reset- the time stamp
Year record when
counters were
cleared last time.
30044 ModbusTCPPort2 This parameter uint8 1 register 1
Time Stamp At holds the month
Counter Reset- of the time stamp
Month record when
counters were
cleared last time.

Copyright © 2023 Cummins Inc. 436 A029X159 (Issue 31)


8-2023 12. PC80

Register Name Description Data Type Size Scaling Factor


Address
30045 ModbusTCPPort2 This parameter uint8 1 register 1
Time Stamp At holds the day of
Counter Reset- the month of the
Date time stamp record
when counters
were cleared last
time.
30046 ModbusTCPPort2 This parameter uint8 1 register 1
Time Stamp At holds the hour of
Counter Reset- the time stamp
Hour record when
counters were
cleared last time.
30047 ModbusTCPPort2 This parameter uint8 1 register 1
Time Stamp At holds the minute
Counter Reset- of the time stamp
Min record when
counters were
cleared last time.
30048 ModbusTCPPort2 This parameter uint8 1 register 1
Time Stamp At holds the seconds
Counter Reset- of the time stamp
Sec record when
counters were
cleared last time.
30049 Modbus TCP This parameter uint8 1 register 1
Port2 Time Since maintains the time
Last Counter in seconds since
Reset the last reset of
Modbus
diagnostic
counters.

9) Other MODBUS TCP Client Considerations

The Modbus TCP server can only handle 1 Modbus transaction at a time per Client/Server connection. If
the Modbus TCP server does not respond to a request in a timely manner (i.e. a Client side transaction
timeout occurs), it is recommended that the Client disconnect from the Server and then reconnect before
attempting another Modbus transaction.

A029X159 (Issue 31) 437 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

12.2 PC80 Modbus Register Map


12.2.1 PC80 Modbus Parametric Data
NOTICE
Daily Peak Power Timestamp (Address 410507) will be displayed in format DDMMYY.
For example:
If Parameter reading shows 81118 this will mean November 8 2018.
If parameter reading shows 10120 this will mean January 01, 2020.

TABLE 30. PC80 MODBUS PARAMETRIC DATA

Addr. System Name Access Specifications System Description


410001 S1 Average Power Read Only Multiplier: 1 This is the average
Factor Offset: 0 power factor of all the
Size (Bits): 32 line power factors
Sign: S
Units:
Lower Limit: -1
Upper Limit: 1
Default/Initial: 0
410003 S1 Frequency Read Only Multiplier: 1 Measured Frequency
Offset: 0
Size (Bits): 32
Sign: S
Units: Hz
Lower Limit: 0
Upper Limit: 100
Default/Initial: 0
410013 S1 L1 kVA Read Only Multiplier: 1 kVA value at Line 1
Offset: 0
Size (Bits): 32
Sign: S
Units: kVA
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0

Copyright © 2023 Cummins Inc. 438 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410017 S1 L1 kVAR Read Only Multiplier: 1 kVAR value at Line 1
Offset: 0
Size (Bits): 32
Sign: S
Units: kVAR
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410019 S1 L1 kW Read Only Multiplier: 1 kW value at Line 1
Offset: 0
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410021 S1 L1 Power Factor Read Only Multiplier: 1 Power factor for Line
Offset: 0 1
Size (Bits): 32
Sign: S
Units:
Lower Limit: -1
Upper Limit: 1
Default/Initial: 0
410023 S1 L1 RMS Current Read Only Multiplier: 1 RMS Current through
Offset: 0 Line 1
Size (Bits): 32
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0
410025 S1 L1-L2 RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 1 and
Size (Bits): 32 Line 2
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0

A029X159 (Issue 31) 439 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410027 S1 L1-N RMS Voltage Read Only Multiplier: 1 RMS Voltage
Offset: 0 between Line 1 and
Size (Bits): 32 Neutral
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410037 S1 L2 kVA Read Only Multiplier: 1 kVA value at Line 2
Offset: 0
Size (Bits): 32
Sign: S
Units: kVA
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410041 S1 L2 kVAR Read Only Multiplier: 1 kVAR value at Line 2
Offset: 0
Size (Bits): 32
Sign: S
Units: kVAR
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410043 S1 L2 kW Read Only Multiplier: 1 kW value at Line 2
Offset: 0
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410045 S1 L2 Power Factor Read Only Multiplier: 1 Power factor for Line
Offset: 0 2
Size (Bits): 32
Sign: S
Units:
Lower Limit: -1
Upper Limit: 1
Default/Initial: 0

Copyright © 2023 Cummins Inc. 440 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410047 S1 L2 RMS Current Read Only Multiplier: 1 RMS Current through
Offset: 0 Line 2
Size (Bits): 32
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0
410049 S1 L2-L3 RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 2 and
Size (Bits): 32 Line 3
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410051 S1 L2-N RMS Voltage Read Only Multiplier: 1 RMS Voltage
Offset: 0 between Line 2 and
Size (Bits): 32 Neutral
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410061 S1 L3 kVA Read Only Multiplier: 1 kVA value at Line 3
Offset: 0
Size (Bits): 32
Sign: S
Units: kVA
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410065 S1 L3 kVAR Read Only Multiplier: 1 kVar value at Line 3
Offset: 0
Size (Bits): 32
Sign: S
Units: kVAR
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0

A029X159 (Issue 31) 441 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410067 S1 L3 kW Read Only Multiplier: 1 kW value at Line 3
Offset: 0
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410069 S1 L3 Power Factor Read Only Multiplier: 1 Power factor for Line
Offset: 0 3
Size (Bits): 32
Sign: S
Units:
Lower Limit: -1
Upper Limit: 1
Default/Initial: 0
410071 S1 L3 RMS Current Read Only Multiplier: 1 RMS Current through
Offset: 0 Line 3
Size (Bits): 32
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0
410073 S1 L3-L1 RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 3 and
Size (Bits): 32 Line 1
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410075 S1 L3-N RMS Voltage Read Only Multiplier: 1 RMS Voltage
Offset: 0 between Line 3 and
Size (Bits): 32 Neutral
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0

Copyright © 2023 Cummins Inc. 442 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410077 S1 LN RMS Current Read Only Multiplier: 1 Neutral RMS current
Offset: 0
Size (Bits): 32
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0
410079 S1 Phase Rotation Read Only Multiplier: 1 Phase rotation of the
Offset: 0 source in terms of L1-
Size (Bits): 8 L2-L3 or L1-L3-L2
Sign: U
Units:
Lower Limit: 0
Upper Limit: 1
Default/Initial: 0
410080 S1 Total Exported Read Only Multiplier: 1 Accumulated total
kVArh Offset: 0 kVArh exported by
Size (Bits): 32 source on all lines
Sign: S
Units: kVArh
Lower Limit: -3.4E+38
Upper Limit: 3.4E+38
Default/Initial: 0
410082 S1 Total Exported Read Only Multiplier: 1 Accumulated total
kWh Offset: 0 kWh exported by the
Size (Bits): 32 source on all lines
Sign: S
Units: kWh
Lower Limit: -3.4E+38
Upper Limit: 3.4E+38
Default/Initial: 0
410088 S1 Total kVA Read Only Multiplier: 1 Sum of kVA values of
Offset: 0 all phases
Size (Bits): 32
Sign: S
Units: kVA
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0

A029X159 (Issue 31) 443 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410090 S1 Total kVAh Read Only Multiplier: 1 Sum of kVAh values
Offset: 0 of all phases
Size (Bits): 32
Sign: S
Units: kVAh
Lower Limit: -3.4E+38
Upper Limit: 3.4E+38
Default/Initial: 0
410092 S1 Total kVar Read Only Multiplier: 1 Sum of kVar values of
Offset: 0 all phases
Size (Bits): 32
Sign: S
Units: kVAR
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410094 S1 Total kW Read Only Multiplier: 1 Sum of kW values of
Offset: 0 all phases
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410096 S1 L1 Voltage THD % Read Only Multiplier: 1 Total Harmonic
Offset: 0 Distortion present in
Size (Bits): 32 the Line 1 to neutral
voltage.
Sign: S
Units: %
Lower Limit: 0
Upper Limit: 100
Default/Initial: 0
410098 S1 L2 Voltage THD % Read Only Multiplier: 1 Total Harmonic
Offset: 0 Distortion present in
Size (Bits): 32 the Line 2 to neutral
voltage.
Sign: S
Units: %
Lower Limit: 0
Upper Limit: 100
Default/Initial: 0

Copyright © 2023 Cummins Inc. 444 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410100 S1 L3 Voltage THD % Read Only Multiplier: 1 Total Harmonic
Offset: 0 Distortion present in
Size (Bits): 32 the Line 3 to neutral
voltage.
Sign: S
Units: %
Lower Limit: 0
Upper Limit: 100
Default/Initial: 0
410102 S1 Average Voltage Read Only Multiplier: 1 Averaged Total
THD % Offset: 0 Harmonic Distortion
Size (Bits): 32 present in the line to
neutral voltages
Sign: S
feeding the load.
Units: %
Lower Limit: 0
Upper Limit: 100
Default/Initial: 0
410104 S1 L1 Phase Angle Read Only Multiplier: 1 Angle by which the
Offset: 0 voltage lags the
Size (Bits): 32 current on Line 1
Sign: S
Units: deg
Lower Limit: -360
Upper Limit: 360
Default/Initial: 0
410106 S1 L2 Phase Angle Read Only Multiplier: 1 Angle by which the
Offset: 0 voltage lags the
Size (Bits): 32 current on Line 2
Sign: S
Units: deg
Lower Limit: -360
Upper Limit: 360
Default/Initial: 0
410108 S1 L3 Phase Angle Read Only Multiplier: 1 Angle by which the
Offset: 0 voltage lags the
Size (Bits): 32 current on Line 3
Sign: S
Units: deg
Lower Limit: -360
Upper Limit: 360
Default/Initial: 0

A029X159 (Issue 31) 445 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410251 S2 Average Power Read Only Multiplier: 1 This is the average
Factor Offset: 0 power factor of all the
Size (Bits): 32 line power factors
Sign: S
Units:
Lower Limit: -1
Upper Limit: 1
Default/Initial: 0
410253 S2 Frequency Read Only Multiplier: 1 Measured Frequency
Offset: 0
Size (Bits): 32
Sign: S
Units: Hz
Lower Limit: 0
Upper Limit: 100
Default/Initial: 0
410263 S2 L1 kVA Read Only Multiplier: 1 kVA value at Line 1
Offset: 0
Size (Bits): 32
Sign: S
Units: kVA
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410267 S2 L1 kVar Read Only Multiplier: 1 kVar value at Line 1
Offset: 0
Size (Bits): 32
Sign: S
Units: kVAR
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410269 S2 L1 kW Read Only Multiplier: 1 kW value at Line 1
Offset: 0
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0

Copyright © 2023 Cummins Inc. 446 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410271 S2 L1 Power Factor Read Only Multiplier: 1 Power factor of Line 1
Offset: 0
Size (Bits): 32
Sign: S
Units:
Lower Limit: -1
Upper Limit: 1
Default/Initial: 0
410273 S2 L1 RMS Current Read Only Multiplier: 1 RMS Current through
Offset: 0 Line 1
Size (Bits): 32
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0
410275 S2 L1-L2 RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 1 and
Size (Bits): 32 Line 2
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410277 S2 L1-N RMS Voltage Read Only Multiplier: 1 RMS Voltage
Offset: 0 between Line 1 and
Size (Bits): 32 Neutral
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410287 S2 L2 kVA Read Only Multiplier: 1 kVA value at Line 2
Offset: 0
Size (Bits): 32
Sign: S
Units: kVA
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0

A029X159 (Issue 31) 447 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410291 S2 L2 kVar Read Only Multiplier: 1 kVar value at Line 2
Offset: 0
Size (Bits): 32
Sign: S
Units: kVAR
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410293 S2 L2 kW Read Only Multiplier: 1 kW value at Line 2
Offset: 0
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410295 S2 L2 Power Factor Read Only Multiplier: 1 Power factor of Line 2
Offset: 0
Size (Bits): 32
Sign: S
Units:
Lower Limit: -1
Upper Limit: 1
Default/Initial: 0
410297 S2 L2 RMS Current Read Only Multiplier: 1 RMS Current through
Offset: 0 Line 2
Size (Bits): 32
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0
410299 S2 L2-L3 RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 2 and
Size (Bits): 32 Line 3
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0

Copyright © 2023 Cummins Inc. 448 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410301 S2 L2-N RMS Voltage Read Only Multiplier: 1 RMS Voltage
Offset: 0 between Line 2 and
Size (Bits): 32 Neutral
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410311 S2 L3 kVA Read Only Multiplier: 1 kVA value at Line 3
Offset: 0
Size (Bits): 32
Sign: S
Units: kVA
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410315 S2 L3 kVar Read Only Multiplier: 1 kVar value at Line 3
Offset: 0
Size (Bits): 32
Sign: S
Units: kVAR
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410317 S2 L3 kW Read Only Multiplier: 1 kW value at Line 3
Offset: 0
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410319 S2 L3 Power Factor Read Only Multiplier: 1 Power factor of Line 3
Offset: 0
Size (Bits): 32
Sign: S
Units:
Lower Limit: -1
Upper Limit: 1
Default/Initial: 0

A029X159 (Issue 31) 449 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410321 S2 L3 RMS Current Read Only Multiplier: 1 RMS Current through
Offset: 0 Line 3
Size (Bits): 32
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0
410323 S2 L3-L1 RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 3 and
Size (Bits): 32 Line 1
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410325 S2 L3-N RMS Voltage Read Only Multiplier: 1 RMS Voltage
Offset: 0 between Line 3 and
Size (Bits): 32 Neutral
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410327 S2 LN RMS Current Read Only Multiplier: 1 Neutral RMS current
Offset: 0
Size (Bits): 32
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0
410329 S2 Phase Rotation Read Only Multiplier: 1 Phase rotation of the
Offset: 0 source in terms of L1-
Size (Bits): 8 L2-L3 or L1-L3-L2
Sign: U
Units:
Lower Limit: 0
Upper Limit: 1
Default/Initial: 0

Copyright © 2023 Cummins Inc. 450 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410330 S2 Total Exported Read Only Multiplier: 1 Accumulated total
kVARh Offset: 0 kVARh exported by
Size (Bits): 32 source on all lines
Sign: S
Units: kVARh
Lower Limit: -3.4E+38
Upper Limit: 3.4E+38
Default/Initial: 0
410332 S2 Total Exported Read Only Multiplier: 1 Accumulated total
kWh Offset: 0 kWh exported by the
Size (Bits): 32 source on all lines
Sign: S
Units: kWh
Lower Limit: -3.4E+38
Upper Limit: 3.4E+38
Default/Initial: 0
410338 S2 Total kVA Read Only Multiplier: 1 Sum of kVA values of
Offset: 0 all phases
Size (Bits): 32
Sign: S
Units: kVA
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410340 S2 Total kVAh Read Only Multiplier: 1 Sum of kVAh values
Offset: 0 of all phases
Size (Bits): 32
Sign: S
Units: kVAh
Lower Limit: -3.4E+38
Upper Limit: 3.4E+38
Default/Initial: 0
410342 S2 Total kVar Read Only Multiplier: 1 Sum of kVAR values
Offset: 0 of all phases
Size (Bits): 32
Sign: S
Units: kVAR
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0

A029X159 (Issue 31) 451 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410344 S2 Total kW Read Only Multiplier: 1 Sum of kW values of
Offset: 0 all phases
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410346 Sync Phase Read Only Multiplier: 1 Phase difference
Difference Offset: 0 between the two
Size (Bits): 32 sources
Sign: S
Units: deg
Lower Limit: -360
Upper Limit: 360
Default/Initial: 0
410348 Frequency Difference Read Only Multiplier: 1 Measured Frequency
Offset: 0 difference between
Size (Bits): 32 the two sources.
Sign: S
Units: Hz
Lower Limit: -100
Upper Limit: 100
Default/Initial: 0
410350 S2 L1 Voltage THD % Read Only Multiplier: 1 Total Harmonic
Offset: 0 Distortion present in
Size (Bits): 32 the Line 1 to neutral
voltage.
Sign: S
Units: %
Lower Limit: 0
Upper Limit: 100
Default/Initial: 0
410352 S2 L2 Voltage THD % Read Only Multiplier: 1 Total Harmonic
Offset: 0 Distortion present in
Size (Bits): 32 the Line 2 to neutral
voltage.
Sign: S
Units: %
Lower Limit: 0
Upper Limit: 100
Default/Initial: 0

Copyright © 2023 Cummins Inc. 452 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410354 S2 L3 Voltage THD % Read Only Multiplier: 1 Total Harmonic
Offset: 0 Distortion present in
Size (Bits): 32 the Line 3 to neutral
voltage.
Sign: S
Units: %
Lower Limit: 0
Upper Limit: 100
Default/Initial: 0
410356 S2 Average Voltage Read Only Multiplier: 1 Averaged Total
THD % Offset: 0 Harmonic Distortion
Size (Bits): 32 present in the line to
neutral voltages
Sign: S
feeding the load.
Units: %
Lower Limit: 0
Upper Limit: 100
Default/Initial: 0
410358 S2 L1 Phase Angle Read Only Multiplier: 1 Angle by which the
Offset: 0 voltage lags the
Size (Bits): 32 current on Line 1
Sign: S
Units: deg
Lower Limit: -360
Upper Limit: 360
Default/Initial: 0
410360 S2 L2 Phase Angle Read Only Multiplier: 1 Angle by which the
Offset: 0 voltage lags the
Size (Bits): 32 current on Line 2
Sign: S
Units: deg
Lower Limit: -360
Upper Limit: 360
Default/Initial: 0
410362 S2 L3 Phase Angle Read Only Multiplier: 1 Angle by which the
Offset: 0 voltage lags the
Size (Bits): 32 current on Line 3
Sign: S
Units: deg
Lower Limit: -360
Upper Limit: 360
Default/Initial: 0

A029X159 (Issue 31) 453 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410501 Daily Peak Power Read Only Multiplier: 1 Daily Peak Power in
Offset: 0 kW
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410503 Previous Daily Peak Read Only Multiplier: 1 Previous Daily Peak
Power Offset: 0 Power in kW
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410505 Total Time Load Read Only Multiplier: 1 Total number of hours
Energized Offset: 0 for which normal and
Size (Bits): 32 emergency sources
have been connected
Sign: U
and available
Units: sec
Lower Limit: 0
Upper Limit:
4.29E+09
Default/Initial: 0
410507 Daily Peak Power Read Only Multiplier: 1 Timestamp for Daily
Timestamp Offset: 0 Peak Power
Size (Bits): 32
Sign: U
Units:
Lower Limit: 0
Upper Limit:
4.29E+09
Default/Initial: 0
410509 Weekly Peak Power Read Only Multiplier: 1 Weekly Peak Power
Offset: 0 in kW
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0

Copyright © 2023 Cummins Inc. 454 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410511 Previous Weekly Read Only Multiplier: 1 Previous Weekly
Peak Power Offset: 0 Peak Power in kW
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410513 Previous Monthly Read Only Multiplier: 1 Previous Monthly
Peak Power Offset: 0 Peak Power in kW
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410515 Total S2 Failures Read Only Multiplier: 1 Total number of
Offset: 0 source 2 failures
Size (Bits): 32 detected by the
controller
Sign: U
Units:
Lower Limit: 0
Upper Limit:
4.29E+09
Default/Initial: 0
410517 Total S1 Failures Read Only Multiplier: 1 Total number of
Offset: 0 source 1 failures
Size (Bits): 32 detected by the
controller
Sign: U
Units:
Lower Limit: 0
Upper Limit:
4.29E+09
Default/Initial: 0
410519 Monthly Peak Power Read Only Multiplier: 1 Monthly Peak Power
Offset: 0 in kW
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0

A029X159 (Issue 31) 455 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410521 Application Device Read Only Multiplier: 1 Unique identifier for
Type Offset: 0 this device.
Size (Bits): 16
Sign: U
Units:
Lower Limit: 0
Upper Limit: 65535
Default/Initial: 0
410522 Application Software Read Only Multiplier: 0.001 The version of the
Version Offset: 0 software running in
Size (Bits): 32 the device.
Sign: U
Units:
Lower Limit: 0
Upper Limit: 4294967
Default/Initial: 0
410524 Reset Event All Operator Multiplier: 1 When this parameter
Categories Offset: 0 is set to True Event
Size (Bits): 8 Handler shall reset
events of all
Sign: U
categories.
Units:
Lower Limit: 0
Upper Limit: 1
Default/Initial: 0
410525 Common Alarm Read Only Multiplier: 1 Indicates status of the
Status Offset: 0 Common Alarm
Size (Bits): 8 variable
Sign: U
Units:
Lower Limit: 0
Upper Limit: 1
Default/Initial: 0
410526 Load add shed Read Only Multiplier: 1 Load1 Add/Shed
contact 1 connected Offset: 0 command status:
Size (Bits): 8 0=shed, 1=add.
Sign: U
Units:
Lower Limit: 0
Upper Limit: 1
Default/Initial: 0

Copyright © 2023 Cummins Inc. 456 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410527 Load add shed Read Only Multiplier: 1 Load3 Add/Shed
contact 3 connected Offset: 0 command status:
Size (Bits): 8 0=shed, 1=add.
Sign: U
Units:
Lower Limit: 0
Upper Limit: 1
Default/Initial: 0
410528 Load add shed Read Only Multiplier: 1 Load2 Add/Shed
contact 2 connected Offset: 0 command status:
Size (Bits): 8 0=shed, 1=add.
Sign: U
Units:
Lower Limit: 0
Upper Limit: 1
Default/Initial: 0
410529 Load add shed Read Only Multiplier: 1 Load4 Add/Shed
contact 4 connected Offset: 0 command status:
Size (Bits): 8 0=shed, 1=add.
Sign: U
Units:
Lower Limit: 0
Upper Limit: 1
Default/Initial: 0
410530 Retransfer Count Factory Multiplier: 1 Number of times the
Offset: 0 system has re-
Size (Bits): 16 transferred from
standby to preferred
Sign: U
source.
Units:
Lower Limit: 0
Upper Limit: 65535
Default/Initial: 0
410531 Transfer Count Factory Multiplier: 1 Number of times the
Offset: 0 system has
Size (Bits): 16 transferred from
preferred to standby
Sign: U
source.
Units:
Lower Limit: 0
Upper Limit: 65535
Default/Initial: 0

A029X159 (Issue 31) 457 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410532 S1 Type Operator Multiplier: 1 Configuration
Offset: 0 indicating the type of
Size (Bits): 8 source 1 is an utility
or a generator set. In
Sign: U
case this source
Units: location is upstream
Lower Limit: 0 select the source type
Upper Limit: 1 to match the sources
Default/Initial: 0 connected to the
upstream ATS.
Assuming both
upstream sources are
of the same type.
410533 S2 Type Operator Multiplier: 1 Configuration
Offset: 0 indicating the type of
Size (Bits): 8 source 2 is an utility
or a generator set. In
Sign: U
case this source
Units: location is upstream
Lower Limit: 0 select the source type
Upper Limit: 1 to match the sources
Default/Initial: 1 connected to the
upstream ATS.
Assuming both
upstream sources are
of the same type.
410534 S1 Preferred Standby Read Only Multiplier: 1 Current effective
State Offset: 0 priority state of source
Size (Bits): 8 1.
Sign: U
Units:
Lower Limit: 0
Upper Limit: 2
Default/Initial: 0
410535 Time Until Automatic Read Only Multiplier: 1 Time remaining until
Source Priority Offset: 0 automatic source
Changeover Size (Bits): 32 priority changeover
takes effect.
Sign: U
Units: sec
Lower Limit: 0
Upper Limit:
4.29E+09
Default/Initial: 0

Copyright © 2023 Cummins Inc. 458 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410537 S2 Preferred Standby Read Only Multiplier: 1 Current effective
State Offset: 0 priority state of source
Size (Bits): 8 2.
Sign: U
Units:
Lower Limit: 0
Upper Limit: 2
Default/Initial: 0
410538 ATS Serial Number Technician Multiplier: 1 Serial Number for the
Offset: 0 ATS
Size (Bits): 168
Sign: NA
Units:
Lower Limit: 1E+10
Upper Limit:
123456789
Default/Initial: 0
410548 ATS Model Number Technician Multiplier: 1 Contains the model
Offset: 0 number of the ATS
Size (Bits): 168
Sign: NA
Units:
Lower Limit: 0
Upper Limit: 1E+10
Default/Initial:
CTPC80
410558 ATS Name Tag Technician Multiplier: 1 Installation specific
Offset: 0 name
Size (Bits): 168
Sign: NA
Units:
Lower Limit: 0
Upper Limit: 1E+10
Default/Initial: ATS
Name
410568 Network Test Request Operator Multiplier: 1 A network test
Boolean Offset: 0 request with ON/OFF
Size (Bits): 8 options
Sign: U
Units:
Lower Limit: 0
Upper Limit: 1
Default/Initial: 1

A029X159 (Issue 31) 459 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410569 Network Test Request Operator Multiplier: 1 Test request from
Offset: 0 network source.
Size (Bits): 8
Sign: U
Units:
Lower Limit: 0
Upper Limit: 5
Default/Initial: 4
410570 Save Trims Operator Multiplier: 1 Setting this parameter
Offset: 0 to True will trigger a
Size (Bits): 8 save of all non-volatile
trims on the entire
Sign: U
device.
Units:
Lower Limit: 0
Upper Limit: 1
Default/Initial: 0
410571 NFPA110 Status Read Only Multiplier: 1 Use to broadcast
Offset: 0 NFPA110 status on
Size (Bits): 16 Modbus
Sign: U
Units:
Lower Limit: 0
Upper Limit: 65535
Default/Initial: 0
410572 NFPA110 Extended Read Only Multiplier: 1 Use to broadcast
Status Offset: 0 NFPA110 extended
Size (Bits): 16 status on Modbus
Sign: U
Units:
Lower Limit: 0
Upper Limit: 65535
Default/Initial: 0
410573 Broadcast Fault Code Read Only Multiplier: 1 Use to broadcast the
Offset: 0 event code over
Size (Bits): 16 Modbus
Sign: U
Units:
Lower Limit: 0
Upper Limit: 65535
Default/Initial: 0

Copyright © 2023 Cummins Inc. 460 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410574 Broadcast FC Level Read Only Multiplier: 1 Used to broadcast FC
Offset: 0 level over Modbus
Size (Bits): 8
Sign: U
Units:
Lower Limit: 0
Upper Limit: 255
Default/Initial: 0
410575 Load L1-N RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 1 and
Size (Bits): 32 the Neutral on the
Load side
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410577 Load L2-N RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 2 and
Size (Bits): 32 the Neutral on the
Load side.
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410579 Load L3-N RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 3 and
Size (Bits): 32 the Neutral on the
Load side
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410581 Load L1-L2 RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 1 and
Size (Bits): 32 Line 2 on the Load
side
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0

A029X159 (Issue 31) 461 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410583 Load L2-L3 RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 2 and
Size (Bits): 32 Line 3 on the Load
side
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410585 Load L3-L1 RMS Read Only Multiplier: 1 RMS Voltage
Voltage Offset: 0 between Line 3 and
Size (Bits): 32 Line 1 on the Load
side
Sign: S
Units: V
Lower Limit: 0
Upper Limit: 45000
Default/Initial: 0
410587 Load L1 RMS Current Read Only Multiplier: 1 RMS current present
Offset: 0 in line 1 on the load
Size (Bits): 32 side
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0
410589 Load L2 RMS Current Read Only Multiplier: 1 RMS current present
Offset: 0 in line 2 on the load
Size (Bits): 32 side
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0
410591 Load L3 RMS Current Read Only Multiplier: 1 RMS Current present
Offset: 0 in Line 3 on the load
Size (Bits): 32 side.
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0

Copyright © 2023 Cummins Inc. 462 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410593 Load Average Power Read Only Multiplier: 1 3 phase averaged
Factor Offset: 0 ratio of Watts to Volt-
Size (Bits): 32 Amperes on the load
side
Sign: S
Units:
Lower Limit: -1
Upper Limit: 1
Default/Initial: 0
410595 Load LN RMS Current Read Only Multiplier: 1 RMS Current present
Offset: 0 in the neutral on the
Size (Bits): 32 load side.
Sign: S
Units: A
Lower Limit: 0
Upper Limit: 10000
Default/Initial: 0
410597 ATS HMI Banner 1 Read Only Multiplier: 1 0
Text Offset: 0
Size (Bits): 8
Sign: U
Units:
Lower Limit: 0
Upper Limit: 38
Default/Initial: 0
410598 ATS HMI Banner 2 Read Only Multiplier: 1 0
Text Offset: 0
Size (Bits): 8
Sign: U
Units:
Lower Limit: 0
Upper Limit: 38
Default/Initial: 0
410599 ATS HMI Banner 1 Read Only Multiplier: 1 0
Time Offset: 0
Size (Bits): 32
Sign: S
Units: sec
Lower Limit: 0
Upper Limit: 3.4E+38
Default/Initial: 0

A029X159 (Issue 31) 463 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Addr. System Name Access Specifications System Description


410601 ATS HMI Banner 2 Read Only Multiplier: 1 0
Time Offset: 0
Size (Bits): 32
Sign: S
Units: sec
Lower Limit: 0
Upper Limit: 3.4E+38
Default/Initial: 0
410605 Load Total kW Read Only Multiplier: 1 Total kW provided to
Offset: 0 load.
Size (Bits): 32
Sign: S
Units: kW
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410609 Load Total kVAR Read Only Multiplier: 1 Total kVAR provided
Offset: 0 to load
Size (Bits): 32
Sign: S
Units: kVAR
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410613 Load Total kVA Read Only Multiplier: 1 Total kVAR provided
Offset: 0 to Load.
Size (Bits): 32
Sign: S
Units: kVA
Lower Limit: -100000
Upper Limit: 100000
Default/Initial: 0
410615 Load Frequency Read Only Multiplier: 1 Load Frequency
Offset: 0
Size (Bits): 32
Sign: S
Units: Hz
Lower Limit: 0
Upper Limit: 100
Default/Initial: 0

Copyright © 2023 Cummins Inc. 464 A029X159 (Issue 31)


8-2023 12. PC80

Addr. System Name Access Specifications System Description


410617 Local Override Read Only Multiplier: 1 Setting this parameter
Request Access Offset: 0 to True/On (1)
Size (Bits): 8 requests to override
timers and inhibits
Sign: U
same as if initiated
Units: from HMI front panel
Lower Limit: 0 Override button. This
Upper Limit: 1 value will self clear
Default/Initial: 0 back to False/Off (0).
Note: Uses the Off On
Enumeration Type.
Register is used for
PC80 V1.013 only.

12.2.2 PC80 Modbus Enumerated Data

Enumeration Type Field


System_Phase_Rotation 0: L1 L2 L3
1: L1 L3 L2
BooleanEnum 0: IsFalse
1: IsTrue
Off On 0: Off
1: On
Source Type 0: Utility
1: Genset
Source Priority State 0: UNDETERMINED
1: PREFERRED
2: STANDBY
Test Request Full 0: Test Without Load
1: Test With Load
2: Transfer to Standby
3: Extended Parallel
4: Not in Test
5: Test Button

A029X159 (Issue 31) 465 Copyright © 2023 Cummins Inc.


12. PC80 8-2023

Enumeration Type Field


Banner Text 0: Banner Inactive
1: Transfer Timer
2: Retransfer Timer
3: Programmed Transition
4: S2 Engine Start
5: S2 Engine Cooldown
6: S1 Engine Start
7: S1 Engine Cooldown
8: Elevator Pre
9: Elevator Post
10: Automatic Changeover
11: Dual Standby Start Inhibit Active
12: Transfer Inhibit Active
13: Retransfer Inhibit Active
14: Local Test Without Load Active
15: Local Test With Load Active
16: Local Transfer to Standby Active
17: Local Extended Parallel Active
18: Remote Test Without Load Active
19: Remote Test With Load Active
20: Remote Transfer to Standby Active
21: Remote Extended Parallel Active
22: Network Test Without Load Active
23: Network Test With Load Active
24: Network Transfer to Standby Active
25: Network Extended Parallel Active
26: Exercise Without Load Active
27: Exercise With Load Active
28: Exercise Transfer to Standby Active
29: Exercise Extended Parallel Active
30: Exercise Exception Active
31: Local Bypass Test Active
32: Remote Bypass Test Active
33: Network Bypass Test Active
34: Bypass Test Step Timer
35: ATS in Connected Position
36: ATS in Test Position
37: ATS in Isolated Position
38: Load Shed Request Active

Copyright © 2023 Cummins Inc. 466 A029X159 (Issue 31)


13 PCC 1301/PowerCommand 1.x/PS0500
Modbus Register Map
The controller contains data that can be read by a master device communicating via Modbus RTU
protocol on a two-wire RS485 multi-drop bus. The Cummins control is a slave unit.
For more information about the Modbus protocol, refer to Modbus Application Protocol V1.1b3 and
Modbus Serial Line Implementation Guide V1.02, which are both available at www.modbus.org.

TABLE 31. RS485 PINS

PCC 1301 PS0500/PowerCommand 1.x


A (+) TB2-3 TB15-3
B (-) TB2-4 TB15-4
Common TB2-1 TB15-1

NOTICE
Earlier versions of this software may not support all of the Modbus registers in the table below. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
For the PS0500 control, Modbus functionality is ONLY available from software version 6.02 and
later.

NOTICE
If an address or bit is not listed in the table below, it has not been implemented.

NOTICE
The master device can read 1-16 contiguous registers, write 1-16 contiguous registers, or read
diagnostic counters.

TABLE 32. PCC 1301/POWERCOMMAND 1.X/PS0500 MODBUS REGISTER MAP

Addr. Parameter Access Specifications Description Control


40004 Save Trims Read and 0: No action Save configuration PC1.x,
Write 1: Save Unconditional parameters or adjustments to PS0500,
non-volatile memory; perform PCC1301
Save Trims after all
configurations have been
updated; do not save trims
unless a change has
occurred

A029X159 (Issue 31) 467 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


40009 Controller Read Only Multiplier: 1 Device type of controller PC1.x,
Type Size(Bits): 8 PS0500,
Sign: U PCC1301
Lower Limit: 0
Upper Limit: 255
40010 Operation Read Only 0: Off Current position of the PC1.x,
Mode Switch 1: Auto generator set switch panel PS0500,
Position 2: Manual Off-Run-Auto switch as seen PCC1301
by the generator set control
40011 Genset State Read Only 0: Ready This parameter reflects the PC1.x,
1: Precrank current state of the generator PS0500,
2: Ramp set. PCC1301
3: Running
40012 Active Fault Read Only Multiplier: 1 This register contains the PC1.x,
Offset: 0 fault code number of the PS0500,
Size(Bits) 16 currently active fault. See the PCC1301
service manual for a list of
Sign: U
supported fault codes.
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
40013 Active Fault Read Only 0: Normal This register contains the PC1.x,
Type 1: Warning fault type of the currently PS0500,
4: Shutdown active fault. PCC1301
40016 NFPA 110 Read Only Multiplier: 1 16 bit number to represent PC1.x,
fault register Offset: 0 the status of the NFPA110 PS0500,
Size(Bits): 16 logical; see Table 3 on page PCC1301
11
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40017 Extended Read Only Multiplier: 1 16 bit number to represent PC1.x,
Annunciation Offset: 0 the status of the NFPA110 PS0500,
fault register Size(Bits): 16 logical; see Table 3 on page PCC1301
11
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA

Copyright © 2023 Cummins Inc. 468 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40018 Alternator L1- Read Only Multiplier: 1 Generator set L1-N voltage PC1.x,
N Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40019 Alternator L2- Read Only Multiplier: 1 Generator set L2-N voltage PC1.x,
N Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40020 Alternator L3- Read Only Multiplier: 1 Generator set L3-N voltage PC1.x,
N Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40022 Alternator L1- Read Only Multiplier: 1 Generator set L1-L2 voltage PC1.x,
L2 Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40023 Alternator L2- Read Only Multiplier: 1 Generator set L2-L2 voltage PC1.x,
L3 Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 31) 469 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


40024 Alternator L3- Read Only Multiplier: 1 Generator set L3-L1 voltage PC1.x,
L1 Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40025 Alt Voltage Read Only Multiplier: 1 Generator set line to line PC1.x,
Offset: 0 average voltage PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 0
Upper Limit: 65535
Default: NA
40026 Alternator L1 Read Only Multiplier: 0.1 Monitors the generator set L1 PC1.x,
Current Offset: 0 current value PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA
40027 Alternator L2 Read Only Multiplier: 0.1 Monitors the generator set L2 PC1.x,
Current Offset: 0 current value PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA
40028 Alternator L3 Read Only Multiplier: 0.1 Monitors the generator set L3 PC1.x,
Current Offset: 0 current value PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2023 Cummins Inc. 470 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40029 Genset Read Only Multiplier: 0.1 Generator set average PC1.x,
Average Offset: 0 current PS0500,
Current Size(Bits): 16 PCC1301
Sign: U
Units: amps
Lower Limit: 0
Upper Limit: 65535
Default: NA
40040 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
Output Volt- Offset: 0 amperes (Phase A) PS0500,
Amperes Size(Bits): 16 PCC1301
(Phase A)
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40041 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
Output Volt- Offset: 0 amperes (Phase B) PS0500,
Amperes Size(Bits): 16 PCC1301
(Phase B)
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40042 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
Output Volt- Offset: 0 amperes (Phase C) PS0500,
Amperes Size(Bits): 16 PCC1301
(Phase C)
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40043 Alternator Read Only Multiplier: 1 Alternator output volt- PC1.x,
Output Volt- Offset: 0 amperes (total) PS0500,
Amperes Size(Bits): 16 PCC1301
(Total)
Sign: U
Units: kVa
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 31) 471 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


40044 Average Alt Read Only Multiplier: 0.1 Average alternator line PC1.x,
Line Offset: 0 frequency PS0500,
Frequency Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA
40058 Rated Read Only Multiplier: 0.1 Monitors the generator set PC1.x,
Alternator L1 Offset: 0 standby L1 current PS0500,
Current (%) Size(Bits): 16 percentage output PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA
40059 Rated Read Only Multiplier: 0.1 Monitors the generator set PC1.x,
Alternator L2 Offset: 0 standby L2 current PS0500,
Current (%) Size(Bits): 16 percentage output PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA
40060 Rated Read Only Multiplier: 0.1 Monitors the generator set PC1.x,
Alternator L3 Offset: 0 standby L3 current PS0500,
Current (%) Size(Bits): 16 percentage output PCC1301
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 65535
Default: NA
40061 Battery Read Only Multiplier: 0.1 Value of battery voltage PC1.x,
Voltage Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Vdc
Lower Limit: 0
Upper Limit: 65535
Default: NA

Copyright © 2023 Cummins Inc. 472 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40062 Oil Pressure Read Only Multiplier: 1 Monitor point for oil pressure PC1.x,
Offset: 0 PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: kPa
Lower Limit: 0
Upper Limit: 65535
Default: NA
40064 Coolant Read Only Multiplier: 0.1 Monitor point for coolant PC1.x,
Temperature Offset: 0 temperature PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: degc
Lower Limit: 0
Upper Limit: 65535
Default: NA
40068 Engine Read Only Multiplier: 1 Monitor point for average PC1.x,
Speed Offset: 0 engine speed PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Rpm
Lower Limit: 0
Upper Limit: 65535
Default: NA
40069 Total Runs Read Only Multiplier: 1 Parameter reflects total PC1.x,
Offset: 0 number of starts PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
40070 Engine Run Read Only Multiplier: 1 Total engine run time PC1.x,
Time (High Offset: 0 PS0500,
Byte) Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 65535
Default: NA

A029X159 (Issue 31) 473 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


40071 Engine Run Read Only Multiplier: 1 Total engine run time PC1.x,
Time (Low Offset: 0 PS0500,
Byte) Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 65535
Default: NA
40210 AUX101 Read Only Multiplier: 0.01 AUX101 speed bias PCC1301
Speed Bias Offset: 0
Size(Bits): 16
Sign: S
Units: RPM
Lower Limit: -100
Upper Limit: 100
Default: NA
40211 AUX101 Read Only Multiplier: 0.01 AUX101 Voltage bias PCC1301
Voltage Bias Offset: 0
Size(Bits): 16
Sign: S
Units: Volt
Lower Limit: -100
Upper Limit: 100
Default: NA
40229 Barometric Read Only Multiplier : 0.1 Monitor point for the PC 1.x
Absolute Offset: 0 barometric absolute pressure
Pressure Size (Bits) : 16
Sign: U
Units: PSI
Lower Limit: 0
Upper Limit: 19
Default: NA
40242 LTA Read Only Multiplier : 1 The processed value of the PC 1.x
Temperature Offset: 0 LTA temperature sensor for
Size (Bits) : 16 the system IO module
Sign: S
Units: degF
Lower Limit: NA
Upper Limit: NA
Default: NA
40254 Fuel Pressure Read Only 0. Invalid Indicates if the fuel pressure PC 1.x
Valid 1. Valid is valid/invalid from the
AUX101 or ECM datalink

Copyright © 2023 Cummins Inc. 474 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40278 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #4 1. Active input
Status
40300 Genset start Read and 0: Stop Remote start via Modbus PC1.x,
stop control Write 1: Start PS0500,
via Modbus PCC1301
40301 Fault reset Read and 0: Inactive Fault reset PC1.x,
via Modbus Write 1: Active PCC1301,
(No logical) PS0500
40302 Genset E- Read and 0: E-stop Inactive Status of E-stop switch PC1.x,
stop switch Write 1: E-stop Active PCC1301,
via Modbus PS0500
(no logical)
40400 Fault status Read Only Multiplier: 1 16bit diesel Fault Bitmap for PS0500
Bitmap 1 Offset: 0 modbus interface- Shutdown
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40401 Fault status Read Only Multiplier: 1 16bit diesel Fault Bitmap for PS0500
Bitmap 2 Offset: 0 modbus interface- Shutdown
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40402 Fault status Read Only Multiplier: 1 16bit diesel Fault Bitmap for PS0500
Bitmap 3 Offset: 0 modbus interface- Shutdown
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40403 Fault status Read Only Multiplier: 1 16bit diesel Fault Bitmap for PS0500
Bitmap 4 Offset: 0 modbus interface- Shutdown
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535

A029X159 (Issue 31) 475 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


40404 Fault status Read Only Multiplier: 1 16bit diesel Fault Bitmap for PS0500
Bitmap 5 Offset: 0 modbus interface- Shutdown
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40405 Fault status Read Only Multiplier: 1 16bit diesel Fault Bitmap for PS0500
Bitmap 6 Offset: 0 modbus interface- Shutdown
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40406 Fault status Read Only Multiplier: 1 16bit diesel Fault Bitmap for PS0500
Bitmap 7 Offset: 0 modbus interface- Shutdown
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40407 Fault status Read Only Multiplier: 1 16bit diesel Fault Bitmap for PS0500
Bitmap 8 Offset: 0 modbus interface- Shutdown
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40408 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 9 Offset: 0 modbus interface- Shutdown
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40409 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 10 Offset: 0 modbus interface- Shutdown
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535

Copyright © 2023 Cummins Inc. 476 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40410 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 11 Offset: 0 modbus interface- Warning
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40411 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 12 Offset: 0 modbus interface- Warning
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40412 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 13 Offset: 0 modbus interface- Warning
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40413 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 14 Offset: 0 modbus interface- Warning
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40414 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 15 Offset: 0 modbus interface- Warning
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40415 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 16 Offset: 0 modbus interface- Warning
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535

A029X159 (Issue 31) 477 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


40416 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 17 Offset: 0 modbus interface- Warning
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40417 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 18 Offset: 0 modbus interface- Warning
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40418 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 19 Offset: 0 modbus interface- Warning
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40419 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 20 Offset: 0 modbus interface- Warning
Size (Bits): 16 Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40420 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 21 Offset: 0 modbus interface-
Size (Bits): 16 Configurable Input Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40421 Fault status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 22 Offset: 0 modbus interface-
Size (Bits): 16 Configurable Input Faults
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535

Copyright © 2023 Cummins Inc. 478 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


40425 Event status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 2 Offset: 0 modbus interface- Events
Size (Bits): 16
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40426 Event status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 3 Offset: 0 modbus interface- Events
Size (Bits): 16
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40430 Event status Read Only Multiplier: 1 16bits diesel Fault Bitmap for PS0500
Bitmap 1 Offset: 0 modbus interface- Events
Size (Bits): 16
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 65535
40535 Customer Read Only 0. Inactive Output of Customer Output 1 PC 1.x
Output 1 1. Active Event command
Event
40536 Customer Read Only 0. Inactive Output of Customer Output 2 PC 1.x
Output 2 1. Active Event command
Event
40583 Dead Battery Read Only Multiplier : 1 Tracks the number of crank PC 1.x
Prevention Offset: 0 attempts in order to limit the
Counter Size (Bits) : 8 attempts when the battery is
so low that the control resets
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
40587 Exercise Read Only 0. Inactive Displays the status of the PC 1.x
Scheduler 1. Active Exercise Scheduler
Status

A029X159 (Issue 31) 479 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43000 Alternator Read and Multiplier: 1 This register represents PC1.x,
Nominal Write Offset: 0 alternator nominal voltage. PS0500,
Voltage Size(Bits): 16 PCC1301
Sign: U
Units: Vac
Lower Limit: 190
Upper Limit: 600
Default: 208
43001 Alternator Read and 0: 60 Hz Set to 50 Hz or 60 Hz PC1.x,
Frequency Write 1: 50 Hz PS0500,
Switch PCC1301
43002 Single/3 Read and 0: Single Phase Generator output connection PC1.x
Phase Write 1: Three Phase type
Connection
43003 Connection Read and 0: Delta Alternator connection type PC1.x,
Type Write 1: Wye PS0500,
PCC1301
43004 Glow Plug Read and 0: Disable Glow plug driver feature PC1.x,
Enable Write 1: Enable enable PS0500,
PCC1301
43005 Charging Read and 0: Disable Used to disable the controller PC1.x,
Alternator Write 1: Enable related charging alt functions PS0500,
Functions PCC1301
Disable
43006 Start Time Read and Multiplier: 1 Remote start time delay PC1.x,
Delay Write Offset: 0 setting PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 300
Default: 0
43007 Stop Time Read and Multiplier: 1 Remote stop time delay PC1.x,
Delay Write Offset: 0 setting PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: Sec
Lower Limit: 0
Upper Limit: 600
Default: 0

Copyright © 2023 Cummins Inc. 480 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43008 Cycle Crank Read and Multiplier: 1 Maximum number of start PC1.x,
Attempts Write Offset: 0 attempts for cycle crank PS0500,
Size(Bits): 16 mode PCC1301
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 7
Default: 3
43009 Cycle Crank Read and Multiplier: 1 Maximum starter engage time PC1.x,
Engage Time Write Offset: 0 for cycle crank mode PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: sec
Lower Limit: 3
Upper Limit: 30
Default: 15
43010 Cycle Crank Read and Multiplier: 1 Engine starting cycle crank PC1.x,
Reset Time Write Offset: 0 attempts setting PS0500,
Size(Bits): 16 PCC1301
Sign: U
Units: sec
Lower Limit: 0
Upper Limit: 60
Default: 30
43011 Fault bypass Read and 0: Disable Operator panel enable for PC1.x,
(battle short) Write 1: Enable Battle Short PCC1301
feature
enable

A029X159 (Issue 31) 481 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43012 Battle Short Read and 0: None, Switch Input for Battle Short PC1.x
Switch Input Write 1: Configurable Input #1, 0= None
2: Configurable Input #2, 1=Customer Input 1
3: Configurable Input #3, 2=Customer Input 2
4: Configurable Input #4, 3 =Customer Input 3
5: Operator Panel 4 =Customer Input 4
5=Operator Panel
PCC1301 Modbus mapping
for parameters having
different limits as compared
to PC1.x and PS0500; see
Table 33 on page 504

Note: For PC1.x SW versions


less than 2.73, the "Battle
Short Switch Input" range is 0
to 3. For PC1.x SW versions
2.73 and greater, the "Battle
Short Switch Input" range is 0
to 5.
43013 AVR Enable Read and 0: Disable Automatic voltage regulation PC1.x,
Write 1: Enable enable PCC1301
43014 V/Hz Knee Read and Multiplier: 0.1 Automatic voltage regulator PC1.x,
Frequency Write Offset: 0 volts per hertz roll off knee PCC1301
Size(Bits): 16 setting
Sign: S
Units: Hz
Lower Limit: 0
Upper Limit: 1000
Default: 500
43015 V/Hz Rolloff Read and Multiplier: 0.1 Automatic voltage regulator PC1.x,
Slope Write Offset: 0 volts per hertz roll off slope PCC1301
Size(Bits): 16 setting
Sign: U
Units: %v/Hz
Lower Limit: 0
Upper Limit: 50
Default: 22
43016 AVR Gain Read and Multiplier: 1 Automatic voltage regulator PC1.x,
Adjust Write Offset: 0 gain setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100

Copyright © 2023 Cummins Inc. 482 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43017 AVR K2 Gain Read and Multiplier: 1 Automatic voltage regulator PC1.x,
Adjust Write Offset: 0 K2 gain setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100
43018 AVR D Gain Read and Multiplier: 1 Automatic voltage regulator PC1.x,
Adjust Write Offset: 0 K2 gain setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 95
Upper Limit: 105
Default: 100
43019 Electronic Read and 0: Disable Electronic governor enable PC1.x,
Governor Write 1: Enable feature PCC1301
Enable
43020 Initial Crank Read and Multiplier: 0.1 Electronic governing initial PC1.x,
Fueling Write Offset: 0 duty cycle setting PCC1301
Command Size(Bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 999
Default: 250
43021 Initial Crank Read and Multiplier: 0.1 Time spent at Initial Crank PC1.x,
Fueling Write Offset: 0 Fueling command PCC1301
Period Size(Bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 20
43022 Crank Fueling Read and Multiplier: 0.1 Electronic governing start PC1.x,
Ramp Rate Write Offset: 0 ramp duty cycle setting PCC1301
Size(Bits): 16
Sign: U
Units: %/sec
Lower Limit: 50
Upper Limit: 1000
Default: 250

A029X159 (Issue 31) 483 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43023 Maximum Read and Multiplier: 0.1 Electronic governing PC1.x,
Crank Fueling Write Offset: 0 maximum duty cycle setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 500
Upper Limit: 1000
Default: 1000
43024 Governor Read and Multiplier: 1 Electronic governing gain PC1.x,
Gain Adjust Write Offset: 0 setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100
43025 Gov K2 Gain Read and Multiplier: 1 Electronic governor K2 gain PC1.x,
Adjust Write Offset: 0 setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 5
Upper Limit: 1000
Default: 100
43026 Gov D Gain Read and Multiplier: 1 Electronic governor damping PC1.x,
Adjust Write Offset: 0 adjustment PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 95
Upper Limit: 105
Default: 100
43027 Crank Exit Read and Multiplier: 0.1 Electronic governing crank PC1.x,
Fueling Write Offset: 0 exit fuel duty cycle setting PCC1301
Command Size(Bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 1000
Default: 250

Copyright © 2023 Cummins Inc. 484 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43028 Dither Factor Read and Multiplier: 1 Electronic governing dither PC1.x,
Write Offset: 0 factor setting PCC1301
Size(Bits): 16
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 30
Default: 25
43029 Governor Read and Multiplier: 1 Electronic governing start PC1.x,
Ramp Time Write Offset: 0 ramp time setting PCC1301
Size(Bits): 16
Sign: U
Units: sec
Lower Limit: 0
Upper Limit: 15000
Default: 25
43030 Governor Read and Multiplier: 1 Engine speed at which PC1.x,
Enable Write Offset: 0 governor is enabled PS0500,
Speed Size(Bits): 16 PCC1301
Sign: U
Units: RPM
Lower Limit: 0
Upper Limit: 1400
Default: 1100
43031 Minimum Read and Multiplier: 1 Setting for electronic PC1.x,
Governor Write Offset: 0 governor minimum duty cycle PCC1301
Duty Cycle Size(Bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 20
43032 Maximum Read and Multiplier: 1 Setting for electronic PC1.x,
Governor Write Offset: 0 governor maximum duty cycle PCC1301
Duty Cycle Size(Bits): 8
Sign: U
Units: %
Lower Limit: 0
Upper Limit: 100
Default: 95

A029X159 (Issue 31) 485 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43033 Model Read and Multiplier: 1 Byte 1 for model number PC1.x,
number Write Offset: 0 PS0500,
character #1 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43034 Model Read and Multiplier: 1 Byte 2 for model number PC1.x,
number Write Offset: 0 PS0500,
character #2 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43035 Model Read and Multiplier: 1 Byte 3 for model number PC1.x,
number Write Offset: 0 PS0500,
character #3 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43036 Model Read and Multiplier: 1 Byte 4 for model number PC1.x,
number Write Offset: 0 PS0500,
character #4 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43037 Model Read and Multiplier: 1 Byte 5 for model number PC1.x,
number Write Offset: 0 PS0500,
character #5 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

Copyright © 2023 Cummins Inc. 486 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43038 Model Read and Multiplier: 1 Byte 6 for model number PC1.x,
number Write Offset: 0 PS0500,
character #6 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43039 Model Read and Multiplier: 1 Byte 7 for model number PC1.x,
number Write Offset: 0 PS0500,
character #7 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43040 Model Read and Multiplier: 1 Byte 8 for model number PC1.x,
number Write Offset: 0 PS0500,
character #8 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43041 Model Read and Multiplier: 1 Byte 9 for model number PC1.x,
number Write Offset: 0 PS0500,
character #9 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43042 Model Read and Multiplier: 1 Byte 10 for model number PC1.x,
number Write Offset: 0 PS0500,
character #10 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

A029X159 (Issue 31) 487 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43043 Model Read and Multiplier: 1 Byte 11 for model number PC1.x,
number Write Offset: 0 PS0500,
character #11 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43044 Model Read and Multiplier: 1 Byte 12 for model number PC1.x,
number Write Offset: 0 PS0500,
character #12 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43045 Model Read and Multiplier: 1 Byte 13 for model number PC1.x,
number Write Offset: 0 PS0500,
character #13 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43046 Model Read and Multiplier: 1 Byte 14 for model number PC1.x,
number Write Offset: 0 PS0500,
character #14 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43047 Model Read and Multiplier: 1 Byte 15 for model number PC1.x,
number Write Offset: 0 PS0500,
character #15 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

Copyright © 2023 Cummins Inc. 488 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43048 Model Read and Multiplier: 1 Byte 16 for model number PC1.x,
number Write Offset: 0 PS0500,
character #16 Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43049 Serial number Read and Multiplier: 1 Byte 1 for serial number PC1.x,
character #1 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43050 Serial number Read and Multiplier: 1 Byte 2 for serial number PC1.x,
character #2 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43051 Serial number Read and Multiplier: 1 Byte 3 for serial number PC1.x,
character #3 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43052 Serial number Read and Multiplier: 1 Byte 4 for serial number PC1.x,
character #4 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

A029X159 (Issue 31) 489 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43053 Serial number Read and Multiplier: 1 Byte 5 for serial number PC1.x,
character #5 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43054 Serial number Read and Multiplier: 1 Byte 6 for serial number PC1.x,
character #6 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43055 Serial number Read and Multiplier: 1 Byte 7 for serial number PC1.x,
character #7 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43056 Serial number Read and Multiplier: 1 Byte 8 for serial number PC1.x,
character #8 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43057 Serial number Read and Multiplier: 1 Byte 9 for serial number PC1.x,
character #9 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

Copyright © 2023 Cummins Inc. 490 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43058 Serial number Read and Multiplier: 1 Byte 10 for serial number PC1.x,
character #10 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43059 Serial number Read and Multiplier: 1 Byte 11 for serial number PC1.x,
character #11 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43060 Serial number Read and Multiplier: 1 Byte 12 for serial number PC1.x,
character #12 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43061 Serial number Read and Multiplier: 1 Byte 13 for serial number PC1.x,
character #13 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43062 Serial number Read and Multiplier: 1 Byte 14 for serial number PC1.x,
character #14 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA

A029X159 (Issue 31) 491 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43063 Serial number Read and Multiplier: 1 Byte 15 for serial number PC1.x,
character #15 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43064 Serial number Read and Multiplier: 1 Byte 16 for serial number PC1.x,
character #16 Write Offset: 0 PS0500,
Size(Bits): 8 PCC1301
Sign: Char
Units: NA
Lower Limit: 0
Upper Limit: 255
Default: NA
43065 Configurable Read and 0: None Configurable Input #1 Fault PC1.x,
Input #1 Fault Write 1: Warning Level Response PS0500,
Level 2: Shutdown PCC1301
Response
43066 Configurable Read and 0: None Configurable Input #2 Fault PC1.x,
Input #2 Fault Write 1: Warning Level Response PS0500,
Level 2: Shutdown PCC1301
Response
43067 Configurable Read and Multiplier: 1 Configurable Customer PC1.x,
Customer Write Offset: 0 Output 1; the default setting PS0500,
Output 1 Size(Bits): 16 for FC 1540 which is a PCC1301
COMMON WARNING fault
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 1540
43068 Configurable Read and Multiplier: 1 Configurable Customer PC1.x,
Customer Write Offset: 0 Output 2; the default setting PS0500,
Output 2 Size(Bits): 16 for FC 1541 which is a PCC1301
COMMON SHUTDOWN fault
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 1541

Copyright © 2023 Cummins Inc. 492 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43069 Voltage Read and Multiplier: 0.0001 Make actual voltage match PC1.x
Regulator Write Offset: 0 nominals 60 Hz when the set
Calibration Size(Bits): 16 point = 100%
60Hz PCC1301 Modbus mapping
Sign: U
for parameters have different
Units: %
limits as compared to PC1.x;
Lower Limit: 9000 see Table 33 on page 504.
Upper Limit: 11000
Default: 10000
43070 Voltage Read and Multiplier: 0.0001 Make actual voltage match PC1.x
Regulator Write Offset: 0 nominals 50 Hz when the set
Calibration Size(Bits): 16 point = 100%
50Hz PCC1301 Modbus mapping
Sign: U
for parameters have different
Units: %
limits as compared to PC1.x;
Lower Limit: 9000 see Table 33 on page 504.
Upper Limit: 11000
Default: 10000
43071 Frequency Read and Multiplier: 0.1 PC1.x,
Adjust Trim Write Offset: 0 PCC1301
Size(Bits): 16
Sign: S
Units: Hz
Lower Limit: -600
Upper Limit: 600
Default: 0
43072 Alternator L1- Read and Multiplier: 0.0001 60 Hz line 1 to neutral PC1.x,
N 60Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 PCC1301 Modbus mapping
Display for parameters have different
Sign: U
Adjust limits as compared to PC1.x
Units: %
and PS0500; see Table 33
Lower Limit: 9000* on page 504.
Upper Limit: 11000*
Default: 10000 *Note: For the PS0500
control, SW versions lower
than 6.03, the range is 6000
to 14000. For the PS0500
control, SW versions higher
than 6.03, the range is 9000
to 11000.

A029X159 (Issue 31) 493 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43073 Alternator L2- Read and Multiplier: 0.0001 60 Hz line 2 to neutral PC1.x,
N 60Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.

43074 Alternator L3- Read and Multiplier: 0.0001 60 Hz line 3 to neutral PC1.x,
N 60Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.

43075 Alternator L1- Read and Multiplier: 0.0001 50 Hz line 1 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.

43076 Alternator L2- Read and Multiplier: 0.0001 50 Hz line 2 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.

43077 Alternator L3- Read and Multiplier: 0.0001 50 Hz line 3 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.

Copyright © 2023 Cummins Inc. 494 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43078 Alternator L1 Read and Multiplier: 0.001 60 Hz line 1 metering current PC1.x,
60Hz Current Write Offset: 0 calibration PS0500,
Adjust Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43079 Alternator L2 Read and Multiplier: 0.001 60 Hz line 2 metering current PC1.x,
60Hz Current Write Offset: 0 calibration PS0500,
Adjust Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43080 Alternator L3 Read and Multiplier: 0.0001 Adjust to make the displayed PC1.x
60Hz Current Write Offset: 0 current match actual values in
Adjust Size(Bits): 16 50 Hz applications
Sign: U
Units: NA
Lower Limit: .8
Upper Limit: 1.2
Default: 1
43081 Alternator L1 Read and Multiplier: 0.001 50 Hz line 1 metering current PC1.x,
50Hz Current Write Offset: 0 calibration PS0500,
Adjust Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43082 Alternator L2 Read and Multiplier: 0.001 50 Hz line 2 metering current PC1.x,
50Hz Current Write Offset: 0 calibration PS0500,
Adjust Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000

A029X159 (Issue 31) 495 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43083 Alternator L3 Read and Multiplier: 0.001 50 Hz line 3 metering current PC1.x,
50Hz Current Write Offset: 0 calibration PS0500,
Adjust Size(Bits): 16 PCC1301
Sign: U
Units: %
Lower Limit: 8000
Upper Limit: 12000*
Default: 1000
43084 Annunciator Read and 0: None Sets the generator set PC1.x,
#1 Switch Write 1: Warning response to an active PCC1301
Fault 2: Shutdown Annunciator #1 switch input
Response
43085 Annunciator Read and 0: None Sets the generator set PC1.x,
#2 Switch Write 1: Warning response to an active PCC1301
Fault 2: Shutdown Annunciator #2 switch input
Response
43086 Annunciator Read and 0: None Sets the generator set PC1.x,
#3 Switch Write 1: Warning response to an active PCC1301
Fault 2: Shutdown Annunciator #3 switch input
Response
43087 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,
Output 1 Write Offset: 0 output #1 event code number PCC1301
Event Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43088 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,
Output 2 Write Offset: 0 output #2 event code number PCC1301
Event Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43089 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,
Output 3 Write Offset: 0 output #3 event code number PCC1301
Event Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

Copyright © 2023 Cummins Inc. 496 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43090 Annunciator Read and Multiplier: 1 Annunciator configurable PC1.x,
Output 4 Write Offset: 0 output #4 event code number PCC1301
Event Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43344 Clock Date Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 date
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 31
Default: NA
43345 Clock Hours Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 hour
Size (Bits) : 8
Sign: U
Units: hours
Lower Limit: 1
Upper Limit: 12
Default: 0
43346 Clock Read Write Multiplier : 1 Use to set or read the current PC 1.x
Minutes Offset: 0 minute
Size (Bits) : 8
Sign: U
Units: minutes
Lower Limit: 0
Upper Limit: 59
Default: 0
43347 Clock Mode Read Write 0. NORMAL_MODE Allows the user to go into Set PC 1.x
1. SET_MODE Mode for Clock setup and in
2. SAVE_CLOCK_MODE Clock Save Mode

43348 Clock Month Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 month
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: NA

A029X159 (Issue 31) 497 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43349 Clock Read Only Multiplier : 1 Use to set or read the current PC 1.x
Seconds Offset: 0 second
Size (Bits) : 8
Sign: U
Units: seconds
Lower Limit: NA
Upper Limit: NA
Default: 0
43350 Clock Year Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 year
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 99
Default: NA
43351 Daylight Read Write Multiplier : 1 Use to set the hour of the day PC 1.x
Savings End Offset: 0 when Daylight Savings Time
Hour Size (Bits) : 8 ends
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 2
43352 Daylight Read Write Multiplier : 1 Use to set the month when PC 1.x
Savings End Offset: 0 Daylight Savings Time ends
Month Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 10
43353 Daylight Read Write 0. Default Use to set the end week PC 1.x
Savings End 1.FIRST_OCCURRENCE occurrence in a Daylight
Week Occ 2. SECOND_OCCURRENCE Savings Time end month
Month
3. THIRD_OCCURRENCE
4. FOURTH_OCCURRENCE
5. FIFTH_OCCURRENCE

Copyright © 2023 Cummins Inc. 498 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43354 Daylight Read Write 0. Sunday Use to set the day of the PC 1.x
Savings Start 1. Monday week when Daylight Savings
Day 2. Tuesday Time starts
3. Wednesday
4. Thursday
5. Friday
6. Saturday
43355 Daylight Read Write Multiplier : 1 Use to set the hour of the day PC 1.x
Savings Start Offset: 0 when Daylight Savings Time
Hour Size (Bits) : 8 starts
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 23
Default: 2
43356 Daylight Read Write Multiplier : 1 Use to set the month when PC 1.x
Savings Start Offset: 0 Daylight Savings Time starts
Month Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 4
43357 Daylight Read Write 0. Default Use to set the week PC 1.x
Savings Start 1.FIRST_OCCURRENCE occurrence in a Daylight
Week Occ 2. SECOND_OCCURRENCE Savings Time start month
Month
3. THIRD_OCCURRENCE
4. FOURTH_OCCURRENCE
5. FIFTH_OCCURRENCE
43358 Daylight Read Write Multiplier : 1 Use to set the amount of PC 1.x
Savings Time Offset: 0 Daylight Savings Time
Adjustment Size (Bits) : 8 adjustment applied
Sign: U
Units: minutes
Lower Limit: 0
Upper Limit: 120
Default: 60
43359 Daylight Read Write 0. Disabled Use to enable the Daylight PC 1.x
Savings Time 1. Enabled Savings Time feature
Enable
43376 Scheduler Read Write 0. PCCNet Devices User to set Duration in PC 1.x
Prog Duration 1. Group for PCCNet device Minutes for Exercise
(Mins) interface parameters Scheduler

A029X159 (Issue 31) 499 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43377 Scheduler Read Write 0. Disabled Trim - user to edit for running PC 1.x
Prog x 1. Enabled the Scheduler Exercise
Enable Program
43378 Scheduler Read Write 0. Weekly User to select the Exercise PC 1.x
Prog Repeat 1. Bi-Monthly Scheduler Interval
Interval 2. Monthly
3. Quarterly
4. Semi-Annual
43380 Scheduler Read Write 0. Sunday User can set the Start Day of PC 1.x
Prog Start 1. Monday the week, month for Exercise
Day 2. Tuesday Scheduler
3. Wednesday
4. Thursday
5. Friday
6. Saturday
43381 Scheduler Read Write Multiplier : 1 User to set Start Hour for PC 1.x
Prog Start Offset: 0 Exercise Scheduler
Hour Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: 2
43382 Scheduler Read Write Multiplier : 1 User to set Start Minute for PC 1.x
Prog Start Offset: 0 Exercise Scheduler
Minute Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 1
43383 Daylight Read Write 0. Sunday Use to set the day of the PC 1.x
Savings End 1. Monday week when Daylight Savings
Day 2. Tuesday Time ends
3. Wednesday
4. Thursday
5. Friday
6. Saturday

Copyright © 2023 Cummins Inc. 500 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43719 AUX101 Read Only Multiplier: 1 AUX101 input as Alternator PCC1301
Alternator Offset: 0 Temp
Temp Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43722 AUX101 Read Only Multiplier: 1 AUX101 input as Ambient PCC1301
Ambient Offset: 0 Temp
Temp Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43723 AUX101 input Read Only Multiplier: 1 AUX101 input 1 voltage PCC1301
1 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43724 AUX101 input Read Only Multiplier: 1 AUX101 input 2 voltage PCC1301
2 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43725 AUX101 input Read Only Multiplier: 1 AUX101 input 3 voltage PCC1301
3 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

A029X159 (Issue 31) 501 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43726 AUX101 input Read Only Multiplier: 1 AUX101 input 4 voltage PCC1301
4 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43727 AUX101 input Read Only Multiplier: 1 AUX101 input 5 voltage PCC1301
5 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43728 AUX101 input Read Only Multiplier: 1 AUX101 input 6 voltage PCC1301
6 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43729 AUX101 input Read Only Multiplier: 1 AUX101 input 67voltage PCC1301
67 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43730 AUX101 input Read Only Multiplier: 1 AUX101 input 8 voltage PCC1301
8 Voltage Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0

Copyright © 2023 Cummins Inc. 502 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43741 AUX101 Read Only Multiplier: 1 AUX101 input as Exhaust PCC1301
Exhaust Offset: 0 Temp
Temp Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43745 AUX101 Fuel Read Only Multiplier: 1 AUX101 input as Fuel Level PCC1301
Level Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43750 AUX101 Read Only Multiplier: 1 AUX101 input as Intake PCC1301
Intake Offset: 0 Manifold Temp
Manifold Size(Bits): 16
Temp
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43757 AUX101 Oil Read Only Multiplier: 1 AUX101 input as Oil Temp PCC1301
Temp Offset: 0
Size(Bits): 16
Sign: U
Units: NA
Lower Limit: 0
Upper Limit: 65535
Default: 0
43793 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #1 1. Active input
Status
43794 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #2 1. Active input
Status
43795 Configurable Read Only 0. Inactive Measured state of hardware PC 1.x
Input #3 1. Active input
Status

A029X159 (Issue 31) 503 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43822 Re-Transfer Read Write Multiplier : 1 This is the delay after the PC 1.x
Delay Offset: 0 utility has returned and before
Size (Bits) : 8 the transfer switch is moved
back to the utility side
Sign: U
position.
Units: NA
Lower Limit: 0
Upper Limit: 59
Default: 1
43825 Transfer Read Write Multiplier : 1 This is the delay after the PC 1.x
Delay Offset: 0 generator set is started
Size (Bits) : 16 before the transfer switch is
moved to the generator set
Sign: U
side position.
Units: seconds
Lower Limit: 60
Upper Limit: 600
Default: 300
43905 Network Read and 0: Normal Used to command a fixed 0.5 PC1.x
Speed Adjust Write 1: Active Hz increase in the speed
Command setpoint.

TABLE 33. PCC1301 MODBUS MAPPING FOR PARAMETERS HAVING DIFFERENT LIMITS AS COMPARED
TO PC1.X AND PS05000

Addr. Parameter Access Specifications Description Control


43012 Battle Short Read and 0: None, Switch input for Battle Short PCC1301
Switch Input Write 1: Configurable Input #1, ONLY
2: Configurable Input #2,
3: Configurable Input #3
43069 Voltage Read and Multiplier: 0.0001 Make actual voltage match PCC1301
Regulator Write Offset: 0 nominals 60 Hz when the set ONLY
Calibration Size(Bits): 16 point = 100%
60Hz
Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43070 Voltage Read and Multiplier: 0.0001 Make actual voltage match PCC1301
Regulator Write Offset: 0 nominals 50 Hz when the set ONLY
Calibration Size(Bits): 16 point = 100%
50Hz
Sign: U
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000

Copyright © 2023 Cummins Inc. 504 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


43072 Alternator L1- Read and Multiplier: 0.0001 60 Hz line 1 to neutral PCC1301
N 60Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43073 Alternator L2- Read and Multiplier: 0.0001 60 Hz line 2 to neutral PCC1301
N 60Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43074 Alternator L3- Read and Multiplier: 0.0001 60 Hz line 3 to neutral PCC1301
N 60Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43075 Alternator L1- Read and Multiplier: 0.0001 50 Hz line 1 to neutral PCC1301
N 50Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
43076 Alternator L2- Read and Multiplier: 0.0001 50 Hz line 2 to neutral PCC1301
N 50Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000

A029X159 (Issue 31) 505 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


43077 Alternator L3- Read and Multiplier: 0.0001 50 Hz line 3 to neutral PCC1301
N 50Hz Write Offset: 0 metering voltage calibration ONLY
Voltage Size(Bits): 16
Display
Sign: U
Adjust
Units: %
Lower Limit: 6000
Upper Limit: 14000
Default: 10000
46364 Modbus Read Only Multiplier: 0 Modbus register RO Enable PC 1.x
Register RO Offset: 0
Enable Size (Bits): 8
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 1
47031 Auto Mains Read Only Multiplier: 0 Auto Mains Failure Enable PC 1.x
Failure Offset: 0 Disable 0
Enable Size (Bits): 8 Enable 1
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 1
47032 Transition to Read Write Multiplier : 0 Transition to genset delay PC 1.x
Genset Delay Offset: 0
Size (Bits) : 8
Sign: U
Units: seconds
Lower Limit: 1
Upper Limit: 10
47033 Re-Transition Read Write Multiplier : 0 Re-Transition to Utility Delay PC 1.x
to Utility Offset: 0
Delay Size (Bits) : 8
Sign: U
Units: seconds
Lower Limit: 1
Upper Limit: 10
47034 Utility Fail To Read Write Multiplier : 0 Utility Fail To Close Delay PC 1.x
Close Delay Offset: 0
Size (Bits) : 8
Sign: U
Units: seconds
Lower Limit: 1
Upper Limit: 10

Copyright © 2023 Cummins Inc. 506 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


47035 Genset Fail Read Write Multiplier : 0 Genset Fail To Close Delay PC 1.x
To Close Offset: 0
Delay Size (Bits) : 8
Sign: U
Units: seconds
Lower Limit: 1
Upper Limit: 10
47036 Transfer Read Write Multiplier : 1 This is the delay after the PC 1.x
Switch Signal Offset: 0 transfer switch is moved to any
Unknown Size (Bits) : 8 of the sides, awaiting for the
Warning fault to become active or
Sign: U
Delay inactive.
Units: seconds
Lower Limit: 5
Upper Limit: 10
Default: 5
47037 Transfer Read Only 0. At Utility This is the status of the PC 1.x
Switch 1. At Genset transfer switch depending upon
Feedback 2. Unknown Position the feedback received.
Status
3. Not Available
47038 Transfer Read Only 0. Not Available This is the status of the PC 1.x
Retransfer 1. OFF transfer and retransfer
Status 2. Transfer Start process.
3. Retransfer Start
4. Transfer Progress
5. Retransfer Progress
6. Transfer Complete
7. Retransfer Complete
8. Transfer Failed
9. Retransfer Failed
47039 Transfer Read Only 0. At Utility This is the status of the PC 1.x
Switch 1. At Genset transfer switch depending upon
2. Unknown Position the fault.
3. Not Available
47040 Clock Cycle Read Write 0. AM Used to set AM_PM Cycle or PC 1.x
1. PM read the same

47041 Scheduler Read Write 0. AM User can set the AM/PM period PC 1.x
Prog Start 1. PM for the Scheduler
Period
47042 Transfer Read Write 0. Disable Trim to enable transfer switch PC 1.x
Switch 1. Enable feedback logic
Feedback
Enable

A029X159 (Issue 31) 507 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


47043 Fuel System Read Write 0. Diesel Type of fuel and ignition PC 1.x
1. Gas system used by the generator
set
47044 Gas Fuel Read Write 0. Natural Gas Trim to set the type of gaseous PC 1.x
Type 1. Propane fuel
2. Dual
47045 Low Fuel Read Only 0.Inactive Displays inactive/active status PC 1.x
Pressure 1.Active of the switch
Switch
47046 Low Fuel Read Write 0. Active Closed State selection of the low fuel PC 1.x
Pressure 1. Active Open pressure switch
Switch Active
State
Selection
47047 LTA Read Only Multiplier : 1 The processed value of the PC 1.x
Temperature Offset: 0 LTA Temperature sensor for
Size (Bits) : 16 the System IO Module
Sign: S
Units: DegF
Lower Limit: NA
Upper Limit: NA
Default: NA
47048 Intake Read Write 0. Disabled Trim to enable the detection of PC 1.x
Manifold Over 1. Enabled Intake Manifold Backfire
Pressure condition
(IMOP)
Enable
47049 Intake Read Write 0. SPN 105 Source for Intake Manifold PC 1.x
Manifold 1. SPN 52 Temperature; SPN 105 Default
Temperature Source and SPN 52 when the
Source IMOP is enabled
47050 Intake Read Write Multiplier : 0.1 Threshold to decide the Intake PC 1.x
Manifold Offset: 0 Manifold Backfire condition; the
Temp Rate of Size (Bits) : 8 value entered is for degF/secs;
Change degF/2secs is obtained by a
Sign: U
Threshold scalar of 2 in the PCC software
Units: DegF/sec
Lower Limit: 2
Upper Limit: 10
Default: 5
47051 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 1 1.Driver On Annunciator
Status
47052 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 1 1.Driver On Annunciator
Status

Copyright © 2023 Cummins Inc. 508 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


47053 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 3 1.Driver On Annunciator
Status
47054 Annunciator Read Only 0. Driver Off State of output as seen by the PC 1.x
Output 4 1.Driver On Annunciator
Status
47055 KTA Fuel Read Only Multiplier : 0.1 The D.F.P for the KTA engine's PC 1.x
Differential Offset: 0 high side sensor
Pressure Size (Bits) : 16
High Side
Sign: S
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA
47056 KTA Fuel Read Only Multiplier : 0.1 The D.F.P for the KTA engine's PC 1.x
Differential Offset: 0 low side sensor
Pressure Low Size (Bits) : 16
Side
Sign: S
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA
47057 Air Shutoff Read Only Multiplier : 0.01 The Air Shutoff Valve Voltage PC 1.x
Valve Offset: 0 configured for SID sender input
Voltage Size (Bits) : 16 7 or 8 (enabled only for oil and
gas features)
Sign: S
Units: Vdc
Lower Limit: NA
Upper Limit: NA
Default: NA
47058 Percent Dirty Read Only Multiplier : 0.1 The calculated level at which PC 1.x
Fuel Filter Offset: 0 the fuel filter is clogged
Size (Bits) : 16
Sign: U
Units: %
Lower Limit: NA
Upper Limit: NA
Default: NA

A029X159 (Issue 31) 509 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

Addr. Parameter Access Specifications Description Control


47059 QSK Read Only Multiplier : 0.1 The fuel pressure measure on PC 1.x
Differential Offset: 0 the QSK engine's low side of
Pressure Low Size (Bits) : 16 the fuel filter
Side
Sign: S
Units: PSI
Lower Limit: NA
Upper Limit: NA
Default: NA
47060 Main Relay Read Only Multiplier : 1 System IO Main Relay Status PC 1.x
Status Offset: 0
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
47061 Expansion Read Only Multiplier : 1 System IO Expansion Relay PC 1.x
Relay Status Offset: 0 Status
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: NA
Upper Limit: NA
Default: NA
47062 Switched B+ Read Only Multiplier: 0 Switched B+ plus Run Time PC 1.x
Run Time Offset: 0 Higher 2 bytes. Scaling should
Size (Bits): 16 be same as that of Engine
running Time.
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 1
47063 Switched B+ Read Only Multiplier: 0 Switched B+ plus Run Time PC 1.x
Run Time Offset: 0 Lower 2 bytes
Size (Bits): 16
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 1

Copyright © 2023 Cummins Inc. 510 A029X159 (Issue 31)


8-2023 13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map

Addr. Parameter Access Specifications Description Control


47066 Switched B Read/write Multiplier: 1 Switched B+ plus Enable PC 1.x
Plus Run Offset: 0
Time Enable Size (Bits): 8
Sign: U
Unit: NA
Lower Limit: 0
Upper Limit: 1

A029X159 (Issue 31) 511 Copyright © 2023 Cummins Inc.


13. PCC 1301/PowerCommand 1.x/PS0500 Modbus Register Map 8-2023

This page is intentionally blank.

Copyright © 2023 Cummins Inc. 512 A029X159 (Issue 31)


14 PowerCommand 2.x/3.x Modbus
Register Map
14.1 Modbus Communications
Use the following equation to calculate the value of 32-bit parameters.
• A = high register value
• B = low register value
parameter = (A * 65536 * multiplier) + (B * multiplier)
alternate formula: parameter = ((A*65536)+B)* multiplier
For example: Engine Running Time is a 32-bit parameter in registers 40070 and 40071.
• Register 40070 has 322 (high register value = A).
• Register 40071 has 15637 (low register value = B).
Engine Running Time = (322 * 65536 * 0.1) + (15637 * 0.1)
The engine run-time is 2111823 seconds, or 586.6 hours.
To write a 32-bit value to 2 Modbus registers, calculate the value for each register as follows:
• A (High register value) = INT ((Parameter / Multiplier) / 65536))
• B (Low register value) = INT ((Parameter / Multiplier) % (65536))
• % = Modulus (the remainder of integer division)
For example: To write Load Demand Genset Run Hours = 80000.5
• Register 40769 (high register value A) should be written to INT ((80000.5/0.1)/65536) = 12
• Register 40770 (low register value B) should be written to INT ((80000.5/.01)%65536) = 13573
To write 32-bit values to 2 modbus addresses always write the high register value followed by the low
register value. Both registers must be written to change the 32-bit value in the control.

14.2 Parametrics (Analog Values)


Unsupported (Not Available) Data=> "Not Available" data shall be represented as highest positive value
for that parameter. For example for a two byte, unsigned integer that would be 65535. For a signed
integer that would be 32767.
• Parameters which are not available due to the sensor not being installed, or not enabled in the
controllers configuration will classified like this.
Network Failed Data=> "Network Failure" data shall be represented as three less than the highest
positive value for that parameter. For example for a two byte, unsigned integer that would be 65532. For a
signed integer that would be 32764.
• Data that comes from a network that has failed, such as sensors on the PCCnet I/O Module or
sensor data coming in via the CAN datalink will be classified like this.

A029X159 (Issue 31) 513 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Hardware/Component Failure=> "Hardware/Component Failure" data shall be represented as four less


than the highest positive value for that parameter. For example for a two byte, unsigned integer that would
be 65531. For a signed integer that would be 32763.
• A hardware/component failure that provides the data, such as the voltage, current and power data
that comes from an external metering chip will be classified like this.
Out of Range High/Out of Range=> "Out of Range High/Out of Range" data shall be represented as one
less than the highest positive value for that parameter. For example for a two byte, unsigned integer that
would be 65534. For a signed integer that would be 32766.
• Data that has been determined to be out of range high or out of range (when there is no distinction
between out of range high and out of range low) due to an open sensor for example, will be
classified like this.
Out of Range Low=> "Out of Range Low" data shall be represented as two less than the highest positive
value for that parameter. For example for a two byte, unsigned integer that would be 65533. For a signed
integer that would be 32765.
• Data that has been determined to be out of range low due to a shorted sensor for example, will be
classified like this.
Data within Normal Operating Range (Valid)=> Anything other than above.

NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

NOTICE
The Master device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.

NOTICE
The lowest Modbus register value is considered as the High Register Value and the highest
Modbus register value is considered as the Low Register Value.

NOTICE
Throughout this document, if a parameter is marked for PCC3300 and PCC3300V2, then it is
applicable to both. If it is marked for PCC3300V2, then it is applicable to PCC3300V2 only.

Copyright © 2023 Cummins Inc. 514 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

TABLE 34.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40010 Control Read Only 0: Off Current position of the PCC3300,
Switch generator set switch PCC2300,
Position 1: Manual panel Off-Run-Auto PCC3300V2
2: Auto switch as seen by the
generator set control.
Modbus mapping shall
be in both addresses
40580 and 40010. For
40010 Modbus Only:
0: Off 1: Auto 2:
Manual
40012 Most Recent Read Only Multiplier: 1 Unit: Fault Code This Modbus Register PCC3300,
Fault or displays most recent PCC2300,
Warning Offset: 0 Lower Limit: Fault or Warning. It is PCC3300V2
Size (bits): 16 Upper Limit: not mapped with any
logical.
Sign: U
40013 Modbus Read Only 0: None This register returns PCC3300,
register the Fault Type of the PCC2300,
40013 1: Warning Fault Code. This is not PCC3300V2
2: Shutdown associated with any
logical.
40014 Genset % Read Only Multiplier: 0.01 Unit: % Monitors the total PCC3300,
Standby generator set standby PCC2300,
Total kW Offset: 0 Lower Limit: KW percentage PCC3300V2
Size (bits): 16 Upper Limit: output.

Sign: S
40018 Genset L1N Read Only Multiplier: 1 Unit: Vac Generator set L1N PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40019 Genset L2N Read Only Multiplier: 1 Unit: Vac Generator set L2N PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40020 Genset L3N Read Only Multiplier: 1 Unit: Vac Generator set L3N PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U

A029X159 (Issue 31) 515 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40022 Genset L1L2 Read Only Multiplier: 1 Unit: Vac Generator set L1L2 PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40023 Genset L2L3 Read Only Multiplier: 1 Unit: Vac Generator set L2L3 PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40024 Genset L3L1 Read Only Multiplier: 1 Unit: Vac Generator set L3L1 PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40025 Genset LL Read Only Multiplier: 1 Unit: Vac Generator set Line to PCC3300,
Average Line average voltage PCC2300,
Voltage Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40026 Genset L1 Read Only Multiplier: 1 Unit: Amps Monitors the generator PCC3300,
Current set L1 current value. PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40027 Genset L2 Read Only Multiplier: 1 Unit: Amps Generator set L2 PCC3300,
Current current PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40028 Genset L3 Read Only Multiplier: 1 Unit: Amps Generator set L3 PCC3300,
Current current PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40029 Genset Read Only Multiplier: 1 Unit: Amps Generator set average PCC3300,
Average current PCC2300,
Current Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 516 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40030 Genset Read Only Multiplier: 1 Unit: Amps Generator set neutral PCC3300,
Neutral current PCC3300V2
Current Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40031 Genset L1 Read Only Multiplier: 1 Unit: kW Generator set L1 kW PCC3300,
kW PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40032 Genset L2 Read Only Multiplier: 1 Unit: kW Generator set L2 kW PCC3300,
kW PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40033 Genset L3 Read Only Multiplier: 1 Unit: kW Generator set L3 kW PCC3300,
kW PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40034 Genset Total Read Only Multiplier: 1 Unit: kW Generator set total kW PCC3300,
kW PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40035 Genset L1 Read Only Multiplier: 1 Unit: kVAR Generator set L1 PCC3300,
kVAR KVAR PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40036 Genset L2 Read Only Multiplier: 1 Unit: kVAR Generator set L2 Kvar PCC3300,
kVAR PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-32768
Size (bits): 16 Upper Limit:
32762
Sign: S
40037 Genset L3 Read Only Multiplier: 1 Unit: kVAR Generator set L3 Kvar PCC3300,
kVAR PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S

A029X159 (Issue 31) 517 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40038 Genset Total Read Only Multiplier: 1 Unit: kVAR Generator set total PCC3300,
kVAR kVAR PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40039 Genset Total Read Only Multiplier: 0.01 Unit: PF Generator set total PCC3300,
Power Factor power factor PCC2300,
Offset: 0 Lower Limit: (L1+L2+L3) PCC3300V2
Size (bits): 8 Upper Limit:
Sign: S
40040 Genset L1 Read Only Multiplier: 1 Unit: kVA Generator set L1 kVA PCC3300,
kVA PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40041 Genset L2 Read Only Multiplier: 1 Unit: kVA Generator set L2 kVA PCC3300,
kVA PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40042 Genset L3 Read Only Multiplier: 1 Unit: kVA Generator set L3 kVA PCC3300,
kVA PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40043 Genset Total Read Only Multiplier: 1 Unit: kVA Generator set total PCC3300,
kVA kVA PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40046 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total PCC3300,
Negative negative kWh PCC2300,
kWh Offset: 0 Lower Limit: accumulation PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40047 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total PCC3300,
Negative negative kWh PCC2300,
kWh Offset: 0 Lower Limit: accumulation PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 518 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40048 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total PCC3300,
Positive kWh positive kWh PCC2300,
Offset: 0 Lower Limit: 0 accumulation PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
40049 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total PCC3300,
Positive kWh positive kWh PCC2300,
Offset: 0 Lower Limit: 0 accumulation PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
40050 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total net PCC3300,
Net kWh kWh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-2147483648
Size (bits): 32 Upper Limit:
2147483643
Sign: S
40051 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total net PCC3300,
Net kWh kWh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-2147483648
Size (bits): 32 Upper Limit:
2147483643
Sign: S
40052 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total PCC3300,
Negative negative kVARh PCC2300,
kVARh Offset: 0 Lower Limit: accumulation PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40053 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total PCC3300,
Negative negative kVARh PCC2300,
kVARh Offset: 0 Lower Limit: accumulation PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40054 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total PCC3300,
Positive positive kVARh PCC2300,
kVARh Offset: 0 Lower Limit: 0 accumulation PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U

A029X159 (Issue 31) 519 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40055 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total PCC3300,
Positive positive kVARh PCC2300,
kVARh Offset: 0 Lower Limit: 0 accumulation PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
40056 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total net PCC3300,
Net kVARh kVARh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-2147483648
Size (bits): 32 Upper Limit:
2147483643
Sign: S
40057 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total net PCC3300,
Net kVARh kVARh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-2147483648
Size (bits): 32 Upper Limit:
2147483643
Sign: S
40058 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Standby L1 set standby L1 current PCC2300,
Current Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40059 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Standby L2 set standby L2 current PCC2300,
Current Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40060 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Standby L3 set standby L3 current PCC2300,
Current Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40061 Battery Read Only Multiplier: 0.001 Unit: Vdc "Battery voltage value. PCC3300,
Voltage Modbus and PCCnet PCC2300,
Offset: 0 Lower Limit: has different multiplier PCC3300V2
Size (bits): 16 Upper Limit: value. For Modbus
use only,
Sign: U multiplier/units = 0.1
Volts"

Copyright © 2023 Cummins Inc. 520 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40062 Oil Pressure Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Oil Pressure. Modbus PCC2300,
Offset: 0 Lower Limit: and PCCnet have PCC3300V2
Size (bits): 16 Upper Limit: different multiplier
value. For modbus
Sign: U use only,
Multiplier/Units = 1kPa
40063 Oil Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Temperature Oil Temperature PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40064 Coolant Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Temperature Coolant Temperature. PCC2300,
Offset: 0 Lower Limit: Modbus mapping shall PCC3300V2
Size (bits): 16 Upper Limit: be to both 46126 and
40064 addresses. For
Sign: S Modbus use only,
Multiplier/Units = 0.1C
40065 Intake Read Only Multiplier: 0.1 Unit: degF To monitor Intake PCC3300,
Manifold Manifold Temperature. PCC2300,
Temperature Offset: 0 Lower Limit: -40 This parameter PCC3300V2
Size (bits): 16 Upper Limit: 410 represents "Intake
Manifold Temperature
Sign: S 1".
40066 Fuel Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Temperature Fuel Temperature PCC2300,
Offset: 0 Lower Limit: -40 PCC3300V2
Size (bits): 16 Upper Limit: 410
Sign: S
40067 Fuel Rate Read Only Multiplier: 0.05 Unit: gal/hr Monitor point for the PCC3300,
Fuel Rate PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40068 Average Read Only Multiplier: 0.125 Unit: rpm Monitor point for the PCC3300,
Engine Average Engine PCC2300,
Speed Offset: 0 Lower Limit: Speed. Modbus and PCC3300V2
Size (bits): 16 Upper Limit: PCCnet have different
multiplier value. For
Sign: U modbus use only,
Multiplier/Units = 1
RPM

A029X159 (Issue 31) 521 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40070 Engine Read Only Multiplier: 0.05 Unit: hours Amount of time that PCC3300,
Running the engine has been PCC2300,
Time Offset: 0 Lower Limit: running. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40071 Engine Read Only Multiplier: 0.05 Unit: hours Amount of time that PCC3300,
Running the engine has been PCC2300,
Time Offset: 0 Lower Limit: running. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40072 Total Fuel Read Only Multiplier: 0.1 Unit: gallons Total fuel consumption PCC3300,
Consumption since start of engine. PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40073 Total Fuel Read Only Multiplier: 0.1 Unit: gallons Total fuel consumption PCC3300,
Consumption since start of engine. PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40074 Total Read/Write Multiplier: 1 Unit: Total number of PCC3300,
Number of generator set runs. PCC2300,
Runs Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U
40075 Total Read/Write Multiplier: 1 Unit: Total number of PCC3300,
Number of generator set runs. PCC2300,
Runs Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U

Copyright © 2023 Cummins Inc. 522 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40076 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40077 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40078 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.

A029X159 (Issue 31) 523 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40079 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40080 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40081 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.

Copyright © 2023 Cummins Inc. 524 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40082 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40083 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40084 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.

A029X159 (Issue 31) 525 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40085 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40086 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40087 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.

Copyright © 2023 Cummins Inc. 526 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40088 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40089 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40090 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.

A029X159 (Issue 31) 527 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40091 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40092 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40096 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.

Copyright © 2023 Cummins Inc. 528 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40097 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40098 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40099 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.

A029X159 (Issue 31) 529 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40100 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40101 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40102 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.

Copyright © 2023 Cummins Inc. 530 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40103 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40104 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40105 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.

A029X159 (Issue 31) 531 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40106 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40107 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40108 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.

Copyright © 2023 Cummins Inc. 532 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40109 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40110 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40111 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.

A029X159 (Issue 31) 533 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40112 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40118 Utility L1N Read Only Multiplier: 1 Unit: Vac Utility L1N voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40119 Utility L2N Read Only Multiplier: 1 Unit: Vac Utility L2N voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40120 Utility L3N Read Only Multiplier: 1 Unit: Vac Utility L3N voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40122 Utility L1L2 Read Only Multiplier: 1 Unit: Vac Utility L1L2 voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40123 Utility L2L3 Read Only Multiplier: 1 Unit: Vac Utility L2L3 voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40124 Utility L3L1 Read Only Multiplier: 1 Unit: Vac Utility L3L1 voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 534 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40125 Utility LL Read Only Multiplier: 1 Unit: Vac Utility Line to Line PCC3300,
Average average voltage PCC3300V2
Voltage Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40126 Utility L1 Read Only Multiplier: 1 Unit: Amps Utility L1 current PCC3300,
Current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40127 Utility L2 Read Only Multiplier: 1 Unit: Amps Utility L2 current PCC3300,
Current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40128 Utility L3 Read Only Multiplier: 1 Unit: Amps Utility L3 current PCC3300,
Current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40131 Utility L1 kW Read Only Multiplier: 1 Unit: kW Utility L1 kW PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40132 Utility L2 kW Read Only Multiplier: 1 Unit: kW Utility L2 kW PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40133 Utility L3 kW Read Only Multiplier: 1 Unit: kW Utility L3 kW PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40134 Utility Total Read Only Multiplier: 1 Unit: kW Utility total kW PCC3300,
kW PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S

A029X159 (Issue 31) 535 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40135 Utility L1 Read Only Multiplier: 1 Unit: kVAR Utility L1 Kvar PCC3300,
kVAR PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40136 Utility L2 Read Only Multiplier: 1 Unit: kVAR Utility L2 Kvar PCC3300,
kVAR PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40137 Utility L3 Read Only Multiplier: 1 Unit: kVAR Utility L3 Kvar PCC3300,
kVAR PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40138 Utility Total Read Only Multiplier: 1 Unit: kVAR Utility total kVAR PCC3300,
kVAR PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40139 Utility Total Read Only Multiplier: 0.01 Unit: PF Utility total power PCC3300,
Power Factor factor PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
40140 Utility L1 kVA Read Only Multiplier: 1 Unit: kVA Utility L1 kVA PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40141 Utility L2 kVA Read Only Multiplier: 1 Unit: kVA Utility L2 kVA PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40142 Utility L3 kVA Read Only Multiplier: 1 Unit: kVA Utility L3 kVA PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 536 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40143 Utility Total Read Only Multiplier: 1 Unit: kVA Utility total kVA PCC3300,
kVA PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40144 Utility Read Only Multiplier: 0.001 Unit: Hz Utility line frequency PCC3300,
Frequency PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40145 Utility Read Only Multiplier: 0.001 Unit: Hz Utility line frequency PCC3300,
Frequency PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40146 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total negative PCC3300,
Negative kWh accumulation PCC3300V2
kWh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40147 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total negative PCC3300,
Negative kWh accumulation PCC3300V2
kWh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40148 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total positive PCC3300,
Positive kWh kWh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40149 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total positive PCC3300,
Positive kWh kWh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40150 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total net kWh PCC3300,
Net kWh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: S

A029X159 (Issue 31) 537 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40151 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total net kWh PCC3300,
Net kWh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: S
40152 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total negative PCC3300,
Negative kVARh accumulation PCC3300V2
kVARh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40153 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total negative PCC3300,
Negative kVARh accumulation PCC3300V2
kVARh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40154 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total positive PCC3300,
Positive kVARh accumulation PCC3300V2
kVARh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40155 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total positive PCC3300,
Positive kVARh accumulation PCC3300V2
kVARh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40156 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total net kVARh PCC3300,
Net kVARh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: S
40157 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total net kVARh PCC3300,
Net kVARh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: S
40158 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L1N Voltage L1N voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 538 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40159 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L2N Voltage L2N voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40160 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L3N Voltage L3N voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40162 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L1L2 Voltage L1L2 voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40163 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L2L3 Voltage L2L3 voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40164 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L3L1 Voltage L3L1 voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40165 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
LL Average Line to Line average PCC3300V2
Voltage Offset: 0 Lower Limit: voltage
Size (bits): 16 Upper Limit:
Sign: U
40166 Genset Bus Read Only Multiplier: 1 Unit: Amps Generator set Bus L1 PCC3300,
L1 Current current PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
40167 Genset Bus Read Only Multiplier: 1 Unit: Amps Generator set Bus L2 PCC3300,
L2 Current current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U

A029X159 (Issue 31) 539 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40168 Genset Bus Read Only Multiplier: 1 Unit: Amps Generator set Bus L3 PCC3300,
L3 Current current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40171 Genset Bus Read Only Multiplier: 1 Unit: kW Generator set Bus L1 PCC3300,
L1 kW kW PCC3300V2
Offset: 0 Lower Limit:
-32768
Size (bits): 16 Upper Limit:
32762
Sign: S
40172 Genset Bus Read Only Multiplier: 1 Unit: kW Generator set Bus L2 PCC3300,
L2 kW kW PCC3300V2
Offset: 0 Lower Limit:
-32768
Size (bits): 16 Upper Limit:
32762
Sign: S
40173 Genset Bus Read Only Multiplier: 1 Unit: kW Generator set Bus L3 PCC3300,
L3 kW kW PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40174 Genset Bus Read Only Multiplier: 1 Unit: kW Generator set Bus PCC3300,
Total kW total kW PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40175 Genset Bus Read Only Multiplier: 1 Unit: kVAR Generator set bus L1 PCC3300,
L1 kVAR Kvar PCC3300V2
Offset: 0 Lower Limit:
-32678
Size (bits): 16 Upper Limit:
32672
Sign: S
40176 Genset Bus Read Only Multiplier: 1 Unit: kVAR Generator set bus L2 PCC3300,
L2 kVAR Kvar PCC3300V2
Offset: 0 Lower Limit:
-32768
Size (bits): 16 Upper Limit:
32762
Sign: S

Copyright © 2023 Cummins Inc. 540 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40177 Genset Bus Read Only Multiplier: 1 Unit: kVAR Generator set bus L3 PCC3300,
L3 kVAR Kvar PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40178 Genset Bus Read Only Multiplier: 1 Unit: kVAR Generator set bus PCC3300,
Total kVAR total kVAR PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40179 Genset Bus Read Only Multiplier: 0.01 Unit: PF Generator set Bus PCC3300,
Total Power Total power factor PCC3300V2
Factor Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
40180 Genset Bus Read Only Multiplier: 1 Unit: kVA Generator set Bus L1 PCC3300,
L1 kVA kVA PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40181 Genset Bus Read Only Multiplier: 1 Unit: kVA Generator set Bus L2 PCC3300,
L2 kVA kVA PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40182 Genset Bus Read Only Multiplier: 1 Unit: kVA Generator set Bus L3 PCC3300,
L3 kVA kVA PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40183 Genset Bus Read Only Multiplier: 1 Unit: kVA Generator set bus PCC3300,
Total kVA total kVA PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U

A029X159 (Issue 31) 541 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

TABLE 35.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40184 Genset Bus Read Only Multiplier: 0.001 Unit: Hz Generator set bus line PCC3300,
Frequency frequency PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40185 Genset Bus Read Only Multiplier: 0.001 Unit: Hz Generator set bus line PCC3300,
Frequency frequency PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40186 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total total negative kWh PCC3300V2
Negative Offset: 0 Lower Limit: accumulation
kWh Size (bits): 32 Upper Limit:
Sign: U
40187 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total total negative kWh PCC3300V2
Negative Offset: 0 Lower Limit: accumulation
kWh Size (bits): 32 Upper Limit:
Sign: U
40188 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total Positive total positive kWh PCC3300V2
kWh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
40189 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total Positive total positive kWh PCC3300V2
kWh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
40190 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total Net total net kWh PCC3300V2
kWh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: S
40191 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total Net total net kWh PCC3300V2
kWh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: S

Copyright © 2023 Cummins Inc. 542 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40192 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set bus PCC3300,
Total total negative kVARh PCC3300V2
Negative Offset: 0 Lower Limit: accumulation
kVARh Size (bits): 32 Upper Limit:
Sign: U
40193 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set bus PCC3300,
Total total negative kVARh PCC3300V2
Negative Offset: 0 Lower Limit: accumulation
kVARh Size (bits): 32 Upper Limit:
Sign: U
40194 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set bus PCC3300,
Total Positive total positive kVARh PCC3300V2
kVARh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
40195 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set bus PCC3300,
Total Positive total positive kVARh PCC3300V2
kVARh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
40196 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set Bus PCC3300,
Total Net total net kVARh PCC3300V2
kVARh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: S
40197 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set Bus PCC3300,
Total Net total net kVARh PCC3300V2
kVARh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: S
40198 Ground Read Only Multiplier: 0.1 Unit: amps Ground current PCC3300,
Current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40199 Genset Read Only Multiplier: 0.01 Unit: % Genset Negative PCC3300,
Negative Sequence Current as PCC2300,
Sequence Offset: 0 Lower Limit: Percent of Standby PCC3300V2
Current % Size (bits): 16 Upper Limit: Current Rating

Sign: U

A029X159 (Issue 31) 543 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40200 LVRT Read Only Multiplier: 1 Unit: Counter to keep track PCC3300,
Counter of number of LVRT PCC3300V2
Offset: 0 Lower Limit: 0 Events
Size (bits): 16 Upper Limit:
65535
Sign: U
40201 Coolant Read Only 0: PGBU Either PGBU(Onan) or PCC3300,
Temperature EBU(Cummins) PCC3300V2
Sensor Type 1: EBU sensor. MODBUS
Access: Read Only
40202 LVRT Enable Read Only 0: Disabled Displays whether the PCC3300,
Status LVRT Functionality PCC3300V2
1: Enabled has been enabled to
detect LVRT Events.
40207 Battery Read Only Multiplier: 0.001 Unit: Vdc The Battery Charger PCC3300,
Charger Alternator Flash PCC2300,
Alternator Offset: 0 Lower Limit: 0 Voltage after all PCC3300V2
Flash Size (bits): 16 Upper Limit: 35 scaling and validity
Voltage checks.
Sign: U
40208 Battery 1 Read Only Multiplier: 0.01 Unit: Vdc Battery 1 Voltage PCC3300,
Voltage measured through PCC3300V2
(Aux101) Offset: 0 Lower Limit: 0 AUX101. Applicable
Size (bits): 16 Upper Limit: when multiple
3850 batteries are used.

Sign: U
40209 Battery 2 Read Only Multiplier: 0.01 Unit: Vdc Battery 2 Voltage PCC3300,
Voltage measured through PCC3300V2
(Aux101) Offset: 0 Lower Limit: 0 AUX101. Applicable
Size (bits): 16 Upper Limit: when multiple
3850 batteries are used.

Sign: U
40210 External Read Only Multiplier: 0.01 Unit: % Monitor point for the PCC3300,
Speed Bias external speed bias PCC2300,
Input Offset: 0 Lower Limit: -100 input. PCC3300V2
Size (bits): 16 Upper Limit: 100
Sign: S
40211 External Read Only Multiplier: 0.01 Unit: % Monitor point for the PCC3300,
Voltage Bias external voltage bias PCC2300,
Input Offset: 0 Lower Limit: -100 input. PCC3300V2
Size (bits): 16 Upper Limit: 100
Sign: S

Copyright © 2023 Cummins Inc. 544 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40212 Battery 3 Read Only Multiplier: 0.01 Unit: Vdc Battery 3 Voltage PCC3300,
Voltage measured through PCC3300V2
(Aux101) Offset: 0 Lower Limit: 0 AUX101. Applicable
Size (bits): 16 Upper Limit: when multiple
3850 batteries are used.

Sign: U
40213 Battery 4 Read Only Multiplier: 0.01 Unit: Vdc Battery 4 Voltage PCC3300,
Voltage measured through PCC3300V2
(Aux101) Offset: 0 Lower Limit: 0 AUX101. Applicable
Size (bits): 16 Upper Limit: when multiple
3850 batteries are used.

Sign: U
40226 Speed Bias Read Only Multiplier: 0.01 Unit: Vdc Configurable analog PCC3300,
Output / output voltage output PCC3300V2
Configurable Offset: 0 Lower Limit: value (predicted)
Analog Size (bits): 16 Upper Limit:
output #1
Output Sign: S
Predictor
40227 Voltage Bias Read Only Multiplier: 0.01 Unit: Vdc Configurable analog PCC3300,
Output / output voltage output PCC3300V2
Configurable Offset: 0 Lower Limit: value (predicted)
Analog Size (bits): 16 Upper Limit:
output #2
Output Sign: S
Predictor
40228 Amber Read Only 0: Inactive Engine Control PCC3300,
Warning System indicates a PCC2300,
Lamp Status 1: Active warning condition. PCC3300V2
40229 Barometric Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Absolute Barometric Absolute PCC2300,
Pressure Offset: 0 Lower Limit: Pressure. Displayed PCC3300V2
Size (bits): 16 Upper Limit: as "Ambient Pressure"
in the HMI.
Sign: U
40230 Boost Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Pressure Boost Absolute PCC2300,
Offset: 0 Lower Limit: Pressure PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40231 CAN Datalink Read Only 0: Inactive Indicates the status of PCC3300,
Status the CAN datalink PCC2300,
1: Active PCC3300V2
2: Failed

A029X159 (Issue 31) 545 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40232 Crankcase Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Pressure Crankcase Pressure. PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-35.67
Size (bits): 16 Upper Limit: 38
Sign: S
40235 ECM Derate Read Only 0: No Derate Request made by the PCC3300,
Request Request ECS for a reduction in PCC2300,
load PCC3300V2
1: Derate
Request
2: Error
3: Don't Care
40236 Engine Read Only 0: ECM Monitor point for the PCC3300,
Application output of the Engine PCC2300,
Type 1: Hydro- application type. Either PCC3300V2
Mechanical ECM (CAN) or Hydro-
Mechanical.
40238 PGI Major Read Only Multiplier: 1 Unit: "Displays Power PCC3300,
Version Generation Interface PCC2300,
Offset: 0 Lower Limit: 0 Major Version to which PCC3300V2
Size (bits): 8 Upper Limit: 255 Engine Software is
complying"
Sign: U
40239 PGI Minor Read Only Multiplier: 1 Unit: "Displays Power PCC3300,
Version Generation Interface PCC2300,
Offset: 0 Lower Limit: 0 Minor Version to which PCC3300V2
Size (bits): 8 Upper Limit: 255 Engine Software is
complying"
Sign: U
40240 PGI Read Only Multiplier: 1 Unit: "Displays Power PCC3300,
Informational Generation Interface PCC2300,
Version Offset: 0 Lower Limit: 0 Informational Version PCC3300V2
Size (bits): 8 Upper Limit: 255 to which Engine
Software is complying"
Sign: U
40242 Aftercooler Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Temperature Aftercooler PCC2300,
Offset: 0 Lower Limit: -40 Temperature. PCC3300V2
Size (bits): 16 Upper Limit: 410
Sign: S

Copyright © 2023 Cummins Inc. 546 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40243 Internal ECM Read Only Multiplier: 0.1 Unit: degF "Internal temperature PCC3300,
Module 1 of the engine PCC3300V2
Temperature Offset: 0 Lower Limit: electronic control
Size (bits): 16 Upper Limit: module 1"

Sign: S
40244 Internal ECM Read Only Multiplier: 0.1 Unit: degF "Internal temperature PCC3300,
Module 2 of the engine PCC3300V2
Temperature Offset: 0 Lower Limit: electronic control
Size (bits): 16 Upper Limit: module 2"

Sign: S
40245 Internal ECM Read Only Multiplier: 0.1 Unit: degF "Internal temperature PCC3300,
Module 3 of the engine PCC3300V2
Temperature Offset: 0 Lower Limit: electronic control
Size (bits): 16 Upper Limit: module 3"

Sign: S
40246 Internal ECM Read Only Multiplier: 0.1 Unit: degF "Internal temperature PCC3300,
Module 4 of the engine PCC3300V2
Temperature Offset: 0 Lower Limit: electronic control
Size (bits): 16 Upper Limit: module 4"

Sign: S
40247 ECM Module Read Only Multiplier: 0.1 Unit: Vdc "Engine Control PCC3300,
1 Battery Module 1 Battery PCC3300V2
Voltage Offset: 0 Lower Limit: 0 Voltage."
Size (bits): 16 Upper Limit:
65535
Sign: U
40248 ECM Module Read Only Multiplier: 0.1 Unit: Vdc "Engine Control PCC3300,
2 Battery Module 2 Battery PCC3300V2
Voltage Offset: 0 Lower Limit: 0 Voltage."
Size (bits): 16 Upper Limit:
65535
Sign: U
40249 ECM Module Read Only Multiplier: 0.1 Unit: Vdc "Engine Control PCC3300,
3 Battery Module 3 Battery PCC3300V2
Voltage Offset: 0 Lower Limit: 0 Voltage."
Size (bits): 16 Upper Limit:
65535
Sign: U

A029X159 (Issue 31) 547 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40250 ECM Module Read Only Multiplier: 0.1 Unit: Vdc "Engine Control PCC3300,
4 Battery Module 4 Battery PCC3300V2
Voltage Offset: 0 Lower Limit: 0 Voltage."
Size (bits): 16 Upper Limit:
65535
Sign: U
40254 Fuel Supply Read Only Multiplier: 0.1 Unit: psi "Monitor point for the PCC3300,
Pressure Fuel Supply Pressure. PCC2300,
Offset: 0 Lower Limit: 0 Displayed as Fuel PCC3300V2
Size (bits): 16 Upper Limit: 145 Supply Pressure in the
HMI."
Sign: U
40257 Intake Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Manifold 4 Intake Manifold 4 PCC2300,
Temperature Offset: 0 Lower Limit: -40 Temperature PCC3300V2
Size (bits): 16 Upper Limit: 410
Sign: S
40258 Fuel Outlet Read Only Multiplier: 0.1 Unit: psi "Monitor point for the PCC3300,
Pressure Fuel Outlet Pressure PCC2300,
Offset: 0 Lower Limit: Pressure. Displayed PCC3300V2
Size (bits): 32 Upper Limit: as Fuel Rail Pressure
in the HMI."
Sign: U
40259 Fuel Outlet Read Only Multiplier: 0.1 Unit: psi "Monitor point for the PCC3300,
Pressure Fuel Outlet Pressure PCC2300,
Offset: 0 Lower Limit: Pressure. Displayed PCC3300V2
Size (bits): 32 Upper Limit: as Fuel Rail Pressure
in the HMI."
Sign: U
40260 Intake Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Manifold 2 Intake Manifold 2 PCC2300,
Temperature Offset: 0 Lower Limit: -40 Temperature PCC3300V2
Size (bits): 16 Upper Limit: 410
Sign: S
40261 Intake Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Manifold 3 Intake Manifold 3 PCC2300,
Temperature Offset: 0 Lower Limit: -40 Temperature PCC3300V2
Size (bits): 16 Upper Limit: 410
Sign: S

Copyright © 2023 Cummins Inc. 548 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40264 Percent Read Only Multiplier: 1 Unit: % Monitor point for the PCC3300,
Engine percent engine torque PCC2300,
Torque/Duty Offset: 0 Lower Limit: output and the PCC3300V2
Cycle Size (bits): 16 Upper Limit: governor percent duty
cycle output when
Sign: S used with the HM
ECM
40276 Post-Filter Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Oil Pressure Post-Filter Oil PCC2300,
Offset: 0 Lower Limit: 0 Pressure PCC3300V2
Size (bits): 16 Upper Limit: 145
Sign: U
40277 Pre-Filter Oil Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Pressure Pre-Filter Oil Pressure PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit: 145
Sign: U
40278 Configurable Read Only 0: Inactive Configurable Input #14 PCC3300,
Input #14 input software state PCC2300,
Switch 1: Active status. Gives software PCC3300V2
Inactive/Active state
40279 Turbocharger Read Only Multiplier: 1 Unit: rpm Monitor point for the PCC3300,
1 Speed Turbocharger 1 Speed PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40280 Turbocharger Read Only Multiplier: 1 Unit: rpm Monitor point for the PCC3300,
1 Speed Turbocharger 1 Speed PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40281 Turbocharger Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
2 Boost Turbocharger 2 Boost PCC2300,
Pressure Offset: 0 Lower Limit: Pressure PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40282 Water in Fuel Read Only 0: No Water in Fuel PCC3300,
Indicator Indication PCC2300,
1: Yes PCC3300V2

A029X159 (Issue 31) 549 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40283 Controller Read Only 0: Off The controller mode PCC3300,
Mode PCC2300,
1: Ready PCC3300V2
2: Setup
3: Starting
4: Idle
5: Rated
6: Stop Normal
7: Stop
Emergency
8: Factory Test
9: Wait to Power
Down
10: Regeneration
40285 Power Down Read Only Multiplier: 1 Unit: seconds Timer to count down PCC3300,
Mode Timer the time before the PCC2300,
Offset: 0 Lower Limit: 0 control goes to sleep PCC3300V2
Size (bits): 16 Upper Limit: 600
Sign: U
40290 Controller On Read/Write Multiplier: 1 Unit: Seconds Controller ON time in PCC3300,
Time seconds. Upper limit is PCC2300,
Offset: 0 Lower Limit: 0 136 years. PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U
40291 Controller On Read/Write Multiplier: 1 Unit: Seconds Controller ON time in PCC3300,
Time seconds. Upper limit is PCC2300,
Offset: 0 Lower Limit: 0 136 years. PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U
40298 Runs Since Read/Write Multiplier: 1 Unit: Number of runs since PCC3300,
Reset the last reset. Upper PCC2300,
Offset: 0 Lower Limit: 0 limit is 2^32 - 1. PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U

Copyright © 2023 Cummins Inc. 550 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40299 Runs Since Read/Write Multiplier: 1 Unit: Number of runs since PCC3300,
Reset the last reset. Upper PCC2300,
Offset: 0 Lower Limit: 0 limit is 2^32 - 1. PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
40300 Remote Start Read/Write 0: Inactive Modbus Remote Start PCC3300,
Switch(Modb PCC2300,
us) 1: Active PCC3300V2
40301 Fault Reset Read/Write 0: Inactive Modbus fault reset. PCC3300,
(Modbus) PCC2300,
1: Active PCC3300V2
40320 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40321 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40322 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40323 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40324 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40325 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C

A029X159 (Issue 31) 551 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40326 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40327 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40328 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40329 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40330 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40331 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40332 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40333 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C

Copyright © 2023 Cummins Inc. 552 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40334 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40335 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40336 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40337 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40338 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40339 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40340 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40341 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C

A029X159 (Issue 31) 553 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40342 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40343 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40344 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40345 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40346 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40347 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40348 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40349 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C

Copyright © 2023 Cummins Inc. 554 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40350 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40351 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40352 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40353 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40354 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40355 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40356 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40357 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C

A029X159 (Issue 31) 555 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40358 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40359 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40360 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40361 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40362 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40363 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40364 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40365 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C

Copyright © 2023 Cummins Inc. 556 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40366 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40367 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40368 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40369 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40370 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40371 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40372 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40373 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C

A029X159 (Issue 31) 557 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40374 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40375 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40376 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40377 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40378 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40379 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40380 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40381 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C

Copyright © 2023 Cummins Inc. 558 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40382 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40383 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40384 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40385 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40386 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40387 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40388 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40389 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C

A029X159 (Issue 31) 559 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40390 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40391 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40392 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40393 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40394 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40395 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40396 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40397 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C

Copyright © 2023 Cummins Inc. 560 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40398 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40399 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C

TABLE 36.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40500 Low Fuel Read Only 0: Inactive Low Fuel input PCC3300,
Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
40501 Low Read Only 0: Inactive This is the status of PCC3300,
Fuel/Configur the Configurable Input PCC2300,
able Input #6 1: Active #6. PCC3300V2
Switch
40503 Differential Read Only 0: Inactive Differential fault trip PCC3300,
Fault Trip monitor point. PCC3300V2
1: Active
2: Reserved
3: Not Available
40509 PTC Mode Read Only 0: Inactive PTC Mode Switch PCC3300,
Switch function output status. PCC3300V2
1: Active Gives software
Inactive/Active state
40510 Extended Read Only 0: Inactive This is the status of PCC3300,
Parallel/Confi the Configurable Input PCC3300V2
gurable Input 1: Active #32.
#32 Switch
40512 Remote E- Read Only 0: Inactive Remote E-stop input PCC3300,
stop Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state

A029X159 (Issue 31) 561 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40513 Remote Start Read Only 0: Inactive Remote Start input PCC3300,
Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
40515 Retransfer Read Only 0: Inactive This is the status of PCC3300,
Inhibit/Config the Configurable Input PCC3300V2
urable Input 1: Active #21.
#21 Switch
40516 Rupture Read Only 0: Inactive Rupture Basin input PCC3300,
Basin Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
40517 Rupture Read Only 0: Inactive This is the status of PCC3300,
Basin/Config the Configurable Input PCC2300,
urable Input 1: Active #12. PCC3300V2
#12 Switch
40519 Start Type Read Only 0: Inactive Start Type input PCC3300,
Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
40521 Sync Read Only 0: Inactive This is the status of PCC3300,
Enable/Confi the Configurable Input PCC3300V2
gurable Input 1: Active #30.
#30 Switch
40524 Transfer Read Only 0: Inactive This is the status of PCC3300,
Inhibit/Config the Configurable Input PCC3300V2
urable Input 1: Active #20.
#20 Switch
40525 Utility CB Read Only 0: Inactive This is the status of PCC3300,
Inhibit/Config the Configurable Input PCC3300V2
urable Input 1: Active #25.
#25 Switch
40526 Utility CB Read Only 0: Inactive This is the status of PCC3300,
Pos the Configurable Input PCC3300V2
B/Configurab 1: Active #23.
le Input #23
Switch
40527 Utility CB Read Only 0: Inactive This is the status of PCC3300,
Tripped/Confi the Configurable Input PCC3300V2
gurable Input 1: Active #24.
#24 Switch
40528 Utility Single Read Only 0: Inactive This is the status of PCC3300,
Mode the Configurable Input PCC3300V2
Verify/Config 1: Active #29.
urable Input
#29 Switch

Copyright © 2023 Cummins Inc. 562 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40530 Utility CB Read Only 0: Inactive Utility CB Pos A input PCC3300,
Pos A Switch software state status. PCC3300V2
1: Active Gives software
Inactive/Active state
40531 Utility CB Read Only 0: Inactive Utility CB Pos B input PCC3300,
Pos B Switch software state status. PCC3300V2
1: Active Gives software
Inactive/Active state
40535 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #1 output’s status is PCC2300,
Status 1: Active Inactive or Active PCC3300V2
40536 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #2 output’s status is PCC2300,
Status 1: Active Inactive or Active PCC3300V2
40537 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #20 output’s status is PCC3300V2
Status 1: Active Inactive or Active
40538 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #21 output’s status is PCC3300V2
Status 1: Active Inactive or Active
40539 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #22 output’s status is PCC3300V2
Status 1: Active Inactive or Active
40540 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #3 output’s status is PCC2300,
Status 1: Active Inactive or Active PCC3300V2
40541 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #4 output’s status is PCC2300,
Status 1: Active Inactive or Active PCC3300V2
40542 Delayed Off / Read Only 0: Inactive Indicates if the PCC3300,
Configurable output’s status is PCC2300,
Output #10 1: Active Inactive or Active PCC3300V2
Status
40543 Fuel Shutoff Read/Write 0: Inactive Indicates if the PCC3300,
Status output’s status is PCC2300,
1: Active Inactive or Active PCC3300V2
40547 Keyswitch Read Only 0: Inactive Indicates if the PCC3300,
Status output’s status is PCC2300,
1: Active Inactive or Active PCC3300V2
40549 Load Dump / Read Only 0: Inactive Indicates if the PCC3300,
Configurable output’s status is PCC2300,
Output #11 1: Active Inactive or Active PCC3300V2
Status

A029X159 (Issue 31) 563 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40550 Local Status Read Only 0: Inactive Indicates if the PCC3300,
/ output’s status is PCC2300,
Configurable 1: Active Inactive or Active PCC3300V2
Output #7
Status
40552 Oil Priming Read Only 0: Inactive Indicates if the PCC3300,
Pump / output’s status is PCC2300,
Configurable 1: Active Inactive or Active PCC3300V2
Output #6
Status
40553 Ready To Read Only 0: Inactive Indicates if the PCC3300,
Load output’s status is PCC2300,
/Configurable 1: Active Inactive or Active PCC3300V2
Output #5
Status
40554 Run Relay Read Only 0: Inactive Indicates if the PCC3300,
#1 Status output’s status is PCC2300,
1: Active Inactive or Active PCC3300V2
40555 Run Relay Read Only 0: Inactive Indicates if the PCC3300,
#2 Status output’s status is PCC2300,
1: Active Inactive or Active PCC3300V2
40556 Speed/Voltag Read Only 0: Inactive Indicates if the PCC3300,
e Bias Relay output’s status is PCC3300V2
Status 1: Active Inactive or Active
40561 Common Read Only 0: Inactive The status of the PCC3300,
Alarm Fault Common Alarm Fault PCC2300,
Status 1: Active PCC3300V2
40562 Common Read Only 0: Inactive The status of the PCC3300,
Shutdown common shutdown PCC2300,
Command 1: Active command PCC3300V2
40563 Common Read Only 0: Inactive The status of the PCC3300,
Shutdown Common Shutdown PCC2300,
Event Status 1: Active Event PCC3300V2
40565 Common Read Only 0: Inactive The status of the PCC3300,
Warning Common Warning PCC2300,
Event Status 1: Active Event PCC3300V2
40570 Fault Reset Read Only 0: Inactive One shot due to fault PCC3300,
Command reset switch being PCC2300,
1: Active active. PCC3300V2
40577 Base Read Only Multiplier: 0.001 Unit: Hz Provides a point to PCC3300,
Frequency monitor the base PCC2300,
Offset: 0 Lower Limit: frequency PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 564 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40578 Base Read Only Multiplier: 0.001 Unit: Hz Provides a point to PCC3300,
Frequency monitor the base PCC2300,
Offset: 0 Lower Limit: frequency PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40586 Excitation Read Only 0: Disabled Shows the enable PCC3300,
State status of the excitation PCC2300,
1: Enabled enabled = regulator PCC3300V2
on.
40587 Exercise Read Only 0: Inactive The output of the PCC3300,
Command Exercise Command PCC2300,
1: Active OR logic PCC3300V2
2: Reserved
3: Not Available
40589 Exercise Read Only Multiplier: 0.1 Unit: hours Time remaining until PCC3300,
Time exercise stop PCC2300,
Remaining Offset: 0 Lower Limit: 0 sequence begins PCC3300V2
Size (bits): 16 Upper Limit: 25
Sign: U
40592 Battle Short Read Only 0: Inactive Indicates status of PCC3300,
Command battle short inputs PCC2300,
1: Active PCC3300V2
40595 Final Read Only Multiplier: 0.001 Unit: Hz The frequency scaled PCC3300,
Frequency version of the final PCC2300,
Reference Offset: 0 Lower Limit: 0 speed reference PCC3300V2
Size (bits): 32 Upper Limit: 100
Sign: U
40596 Final Read Only Multiplier: 0.001 Unit: Hz The frequency scaled PCC3300,
Frequency version of the final PCC2300,
Reference Offset: 0 Lower Limit: 0 speed reference PCC3300V2
Size (bits): 32 Upper Limit: 100
Sign: U
40600 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40601 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C

A029X159 (Issue 31) 565 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40602 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40603 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40604 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40605 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40606 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40607 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40608 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40609 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C

Copyright © 2023 Cummins Inc. 566 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40610 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40611 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40612 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40613 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40614 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40615 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40620 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40621 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C

A029X159 (Issue 31) 567 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40622 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40623 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40624 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40625 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40626 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40627 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40628 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40629 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C

Copyright © 2023 Cummins Inc. 568 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40630 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40631 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40632 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40633 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40634 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40635 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40640 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40641 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C

A029X159 (Issue 31) 569 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40642 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40643 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40644 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40645 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40646 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40647 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40648 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40649 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C

Copyright © 2023 Cummins Inc. 570 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40650 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40651 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40652 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40653 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40654 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40655 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40660 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40661 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C

A029X159 (Issue 31) 571 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40662 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40663 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40664 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40665 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40666 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40667 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40668 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40669 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C

Copyright © 2023 Cummins Inc. 572 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40670 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40671 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40672 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40673 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40674 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40675 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40709 Device Type Read Only Multiplier: 1 Unit: This modbus register PCC3300,
(Modlon) is created for Modlon PCC3300V2
Offset: 0 Lower Limit: register mapping. This
Size (bits): 8 Upper Limit: parameter is not
associated with any
Sign: U logical.
40710 Control Read Only 0: Off This modbus register PCC3300,
Switch is created for Modlon PCC3300V2
Position 1: Manual register mapping.
(Modlon) 2: Auto

A029X159 (Issue 31) 573 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40711 Genset Run Read Only 0: Stop This modbus register PCC3300,
Sequence is created for Modlon PCC3300V2
State 1: Time Delay to register mapping.
(Modlon) Start
2: Warmup at
Idle
3: Rated Freq
and Voltage
4: Cooldown /
Stop Delay
5: Cooldown at
Idle
6: Rated to Idle
Trasition Delay
40712 Most Recent Read Only Multiplier: 1 Unit: Fault Code This modbus register PCC3300,
Fault or is created for Modlon PCC3300V2
Warning Offset: 0 Lower Limit: register mapping. This
(Modlon) Size (bits): 16 Upper Limit: modbus register is not
associated with any
Sign: U logical Address
40713 Fault Type Read Only 0: None This modbus register PCC3300,
(Modlon) is created for modlon PCC3300V2
1: Warning register mapping. This
2: Derate modbus register is not
associated with any
3: Shutdown with logical address.
Cooldown
4: Shutdown
40714 Genset % Read Only Multiplier: 0.5 Unit: % This modbus register PCC3300,
Standby is created for modlon PCC3300V2
Total kW Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Monitors the total
generator set standby
Sign: U KW percentage
output. Modbus has
different multiplier than
PCCnet. For Modlon
use only, use
multiplier 0.5 %
40715 Genset Total Read Only Multiplier: 1 Unit: kW This modbus register PCC3300,
kW (Modlon is created for modlon PCC3300V2
GenStatus) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set total
kW.
Sign: S

Copyright © 2023 Cummins Inc. 574 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

TABLE 37.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40716 NFPA 110 Read Only Multiplier: 1 Unit: This modbus register PCC3300,
Logical is created for modlon PCC3300V2
Status Offset: 0 Lower Limit: register mapping. 32-
(Modlon) Size (bits): 32 Upper Limit: bit number to
represent the status of
Sign: U the NFPA 110 logical.
See NFPA110 bitmap.
40717 NFPA 110 Read Only Multiplier: 1 Unit: This modbus register PCC3300,
Logical is created for modlon PCC3300V2
Status Offset: 0 Lower Limit: register mapping. 32-
(Modlon) Size (bits): 32 Upper Limit: bit number to
represent the status of
Sign: U the NFPA 110 logical.
See NFPA110 bitmap.
40718 Genset Read Only Multiplier: 0.1 Unit: Hz This modbus register PCC3300,
Frequency is created for modlon PCC3300V2
OP (Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set
Frequency OP.
Sign: U Modbus has different
multiplier than
PCCnet. For Modlon
use only,
Multiplier/Units = 0.1
Hz
40719 Genset Total Read Only Multiplier: Unit: PF This modbus register PCC3300,
Power Factor 0.00005 is created for modlon PCC3300V2
(Modlon) register mapping.
Offset: 0 Lower Limit: Generator set total
Size (bits): 16 Upper Limit: power factor
(L1+L2+L3). Modbus
Sign: S and PCCnet has
different multiplier
value. For Modlon,
use 0.00005 PF.
40720 Genset Total Read Only Multiplier: 1 Unit: kVA This modbus register PCC3300,
kVA is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set total
kVA
Sign: U
40721 Genset Total Read Only Multiplier: 1 Unit: kW This modbus register PCC3300,
kW (Modlon is created for modlon PCC3300V2
GenACData) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set total kW
in Gen AC Data.
Sign: S

A029X159 (Issue 31) 575 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40722 Genset Total Read Only Multiplier: 1 Unit: kVAR This modbus register PCC3300,
kVAR is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set total
kVAR
Sign: S
40723 Genset L1L2 Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L1L2
voltage
Sign: U
40724 Genset L2L3 Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L2L3
voltage
Sign: U
40725 Genset L3L1 Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L3L1
voltage
Sign: U
40726 Genset L1N Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L1N
voltage
Sign: U
40727 Genset L2N Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L2N
voltage
Sign: U
40728 Genset L3N Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L3N
voltage
Sign: U
40729 Genset L1 Read Only Multiplier: 1 Unit: Amps This modbus register PCC3300,
Current is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Monitors the generator
set L1 current value.
Sign: U

Copyright © 2023 Cummins Inc. 576 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40730 Genset L2 Read Only Multiplier: 1 Unit: Amps This modbus register PCC3300,
Current is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L2
current
Sign: U
40731 Genset L3 Read Only Multiplier: 1 Unit: Amps This modbus register PCC3300,
Current is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L3
current
Sign: U
40732 Genset % Read Only Multiplier: 0.5 Unit: % This modbus register PCC3300,
Standby L1 is created for modlon PCC3300V2
Current Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Monitors the generator
set standby L1 current
Sign: U percentage output.
Modbus and PCCnet
have different
multiplier value. For
modlon use 0.5 %
40733 Genset % Read Only Multiplier: 0.5 Unit: % This modbus register PCC3300,
Standby L2 is created for modlon PCC3300V2
Current Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Monitors the generator
set standby L2 current
Sign: U percentage output.
Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.5 %
40734 Genset % Read Only Multiplier: 0.5 Unit: % This modbus register PCC3300,
Standby L3 is created for modlon PCC3300V2
Current Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Monitors the generator
set standby L3 current
Sign: U percentage output.
Modbus and PCCnet
has different multiplier
value. For Modlon use
0.5 %
40735 Battery Read Only Multiplier: 0.1 Unit: Vdc This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Battery voltage value.
Modbus and PCCnet
Sign: U has different multiplier
value. For Modlon use
0.1Volts

A029X159 (Issue 31) 577 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40736 Oil Pressure Read Only Multiplier: 0.1 Unit: kPa This modbus register PCC3300,
(Modlon) is created for modlon PCC3300V2
Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Monitor point for the
Oil Pressure. Modbus
Sign: U and PCCnet have
different multiplier
value. For modlon,
use 0.1 KPA
40737 Oil Read Only Multiplier: 0.1 Unit: degK This modbus register PCC3300,
Temperature is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Monitor point for the
Oil Temperature.
Sign: S Modbus and PCCnet
has different multiplier
value. For Modlon use
0.1 deg Kelvin
40738 Coolant Read Only Multiplier: 0.1 Unit: degK This modbus register PCC3300,
Temperature is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Monitor point for the
Coolant Temperature.
Sign: S Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.1deg Kelvin.
40739 Intake Read Only Multiplier: 0.1 Unit: degK This modbus register PCC3300,
Manifold is created for modlon PCC3300V2
Temperature Offset: 0 Lower Limit: -40 register mapping. To
(Modlon) Size (bits): 16 Upper Limit: 410 monitor Intake
Manifold Temperature.
Sign: S Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.1 deg Kelvin
40740 Fuel Read Only Multiplier: 0.1 Unit: degK This modbus register PCC3300,
Temperature is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: -40 register mapping.
Size (bits): 16 Upper Limit: 410 Monitor point for the
Fuel Temperature.
Sign: S Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.1 deg Kelvin.

Copyright © 2023 Cummins Inc. 578 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40741 Fuel Rate Read Only Multiplier: 0.01 Unit: gal/hr This modbus register PCC3300,
(Modlon) is created for modlon PCC3300V2
Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Monitor point for the
Fuel Rate. Modbus
Sign: U and PCCnet has
different multiplier
value. For Modlon,
use 0.01 gph
40742 Average Read Only Multiplier: 1 Unit: rpm This modbus register PCC3300,
Engine is created for modlon PCC3300V2
Speed Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Monitor point for the
Average Engine
Sign: U Speed. Modbus and
PCCnet have different
multiplier value. For
Modlon, use 1 rpm.
40743 Total Read Only Multiplier: 1 Unit: This modbus register PCC3300,
Number of is created for modlon PCC3300V2
Runs Offset: 0 Lower Limit: 0 register mapping.
(Modlon) Size (bits): 32 Upper Limit: Total number of
4294967295 generator set runs.

Sign: U
40744 Engine Read Only Multiplier: 0.1 Unit: seconds This modbus register PCC3300,
Running is created for modlon PCC3300V2
Time Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Total engine run time.
Modbus has different
Sign: U multiplier than
PCCnet. For Modbus,
use 0.1 sec
40745 Engine Read Only Multiplier: 0.1 Unit: seconds This modbus register PCC3300,
Running is created for modlon PCC3300V2
Time Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Total engine run time.
Modbus has different
Sign: U multiplier than
PCCnet. For Modbus,
use 0.1 sec
40746 Genset Total Read Only Multiplier: 1 Unit: kWh This modbus register PCC3300,
Net kWh is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
-2147483648 Generator set total net
Size (bits): 32 Upper Limit: kWh accumulation
2147483643
Sign: S

A029X159 (Issue 31) 579 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40747 Genset Total Read Only Multiplier: 1 Unit: kWh This modbus register PCC3300,
Net kWh is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
-2147483648 Generator set total net
Size (bits): 32 Upper Limit: kWh accumulation
2147483643
Sign: S
40748 Total Fuel Read Only Multiplier: 0.01 Unit: gallons This modbus register PCC3300,
Consumption is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 32 Upper Limit: Total fuel consumption
since start of engine.
Sign: U Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.01 Gallons
40749 Total Fuel Read Only Multiplier: 0.01 Unit: gallons This modbus register PCC3300,
Consumption is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 32 Upper Limit: Total fuel consumption
since start of engine.
Sign: U Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.01 Gallons
40750 Utility/Genset Read Only Multiplier: 0.1 Unit: Hz This modbus register PCC3300,
Bus is created for modlon PCC3300V2
Frequency Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility line frequency or
Generator set Bus
Sign: U Frequency depending
on Paralleling
Application. Modbus
and PCCnet has
different multiplier
value. For Modlon,
use 0.1 Hz.
40751 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L1L2 is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L1L2 Voltage or
Generator set Bus
Sign: U L1L2 voltage
depending on
paralleling application.

Copyright © 2023 Cummins Inc. 580 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40752 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L2L3 is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L2L3 voltage

Sign: U
40753 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L3L1 is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L3L1 voltage or
Generator set Bus
Sign: U L3L1 voltage
depending on
paralleling application.
40754 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L1N is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L1N voltage or
Generator set Bus
Sign: U L1N voltage
depending on
paralleling application.
40755 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L2N is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L2N voltage or
Generator set Bus
Sign: U L2N voltage
depending on
paralleling application.
40756 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L3N is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L3N voltage or
Generator set Bus
Sign: U L3N voltage
depending on
paralleling application.
40757 Customer Read Only Multiplier: 1 Unit: This modbus register PCC3300,
Faults is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: 0 register mapping. 16
Size (bits): 16 Upper Limit: bit fault bitmap for
65530 modbus interface.

Sign: S

A029X159 (Issue 31) 581 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40760 ES State Read Only 0: Standby This modbus register PCC3300,
(Modlon) is created for modlon PCC3300V2
1: Dead Bus register mapping.
2: Synchronize Internal paralleling
status variable
3: Load Share
4: Load Govern
40761 Load Read Only 0: Inactive This modbus register PCC3300,
Demand is created for modlon PCC3300V2
Stop 1: Active register mapping.
Command Modbus input for load
(Modlon) demand stop
command.
40764 Genset CB Read Only 0: Open This modbus register PCC3300,
Position is created for modlon PCC3300V2
Status 1: Closed register mapping.
(Modlon) 2: Not Available indicates generator set
breaker position
40765 Utility CB Read Only 0: Open This modbus register PCC3300,
Position is created for modlon PCC3300V2
Status 1: Closed register mapping.
(Modlon) 2: Not Available indicates utility breaker
position
40766 Remote Start Read/Write 0: Inactive This modbus register PCC3300,
Switch(Modlo is created for modlon PCC3300V2
n) 1: Active register mapping.
Modbus Remote Start
40767 Fault Reset Read/Write 0: Inactive This modbus register PCC3300,
(Modlon) is created for modlon PCC3300V2
1: Active register mapping.
Modbus fault reset.
40768 System Read Only 0: Inactive Indicates PCC3300,
Network communication status PCC3300V2
Datalink 1: Active of the local generator
Status 2: Failed set on System
Network (used for load
demand).
40769 Load Read/Write Multiplier: 0.1 Unit: hours Run hour accumulator PCC3300,
Demand used for load demand PCC3300V2
Genset Run Offset: 0 Lower Limit: 0 run hour equalization.
Hours Size (bits): 32 Upper Limit: This is writable.
999999.9
Sign: U

Copyright © 2023 Cummins Inc. 582 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40770 Load Read/Write Multiplier: 0.1 Unit: hours Run hour accumulator PCC3300,
Demand used for load demand PCC3300V2
Genset Run Offset: 0 Lower Limit: 0 run hour equalization.
Hours Size (bits): 32 Upper Limit: This is writable.
999999.9
Sign: U
40771 Load Read Only 0: Inactive Indicates the status of PCC3300,
Demand the spare capacity PCC3300V2
Spare 1: Active request input. When
Capacity ACTIVE additional
Request spare capacity (set by
Status Load Demand Spare
Capacity Request
Value) is requested.
40772 System Read Only 0: OFF Indicates the status of PCC3300,
Network the on-board CAN PCC3300V2
Termination 1: ON termination resistor
Resistor 2: Reserved switch (S1).
Switch
Status 3: N/A
4: Network
Failure
40773 Genset ID Read/Write 0: Gen1 Generator set PCC3300,
identifier. All load PCC3300V2
1: Gen2 demand generator
2: Gen3 sets must have a
unique Generator set
3: Gen4 ID.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 31) 583 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40774 Load Read/Write Multiplier: 1 Unit: kW Sets the kW value of PCC3300,
Demand additional capacity to PCC3300V2
Spare Offset: 0 Lower Limit: 0 be requested from the
Capacity Size (bits): 32 Upper Limit: system when the Load
Request 80000 Demand Spare
Value Capacity Request
Sign: U Status is YES.
40775 Load Read/Write Multiplier: 1 Unit: kW Sets the kW value of PCC3300,
Demand additional capacity to PCC3300V2
Spare Offset: 0 Lower Limit: 0 be requested from the
Capacity Size (bits): 32 Upper Limit: system when the Load
Request 80000 Demand Spare
Value Capacity Request
Sign: U Status is YES.
40776 Load Read/Write 0: Disable Disables or Enables PCC3300,
Demand load demand on this PCC3300V2
Genset 1: Enable genset only. When set
Enable to disable the genset
is not included in the
load demand system
and can be removed
without triggering a
com error.
40777 System Read Only 0: Out of Sync Indicates whether the PCC3300,
Settings system settings on the PCC3300V2
Status 1: In Sync local genset are in
2: Standalone sync with ones from
other genset in the
network.
40778 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40779 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40780 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C

Copyright © 2023 Cummins Inc. 584 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40781 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40782 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40783 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40784 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40785 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40786 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40787 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40788 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C

A029X159 (Issue 31) 585 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40789 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40790 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40791 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40792 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40793 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40794 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40795 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40796 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C

Copyright © 2023 Cummins Inc. 586 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40797 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40800 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40801 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40802 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40803 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40804 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40805 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40806 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 587 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40807 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40808 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40809 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40810 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40811 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40812 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40813 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40814 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 588 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40815 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40816 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40817 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40818 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40819 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40820 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40821 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40822 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 589 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40823 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40824 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40825 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40826 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40827 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40828 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40829 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40830 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 590 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40831 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40832 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40833 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40834 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40835 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40836 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40837 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40838 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 591 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40839 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40840 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40841 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40842 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40843 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40844 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40845 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40846 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 592 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40847 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40848 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40849 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40850 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40851 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40852 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40853 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40854 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 593 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40855 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40856 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40857 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40858 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40859 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40860 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40861 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40862 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 594 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40863 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40864 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40865 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40866 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40867 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40868 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40869 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40870 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 595 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40871 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40872 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40873 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40874 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40875 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40876 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40877 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40878 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 596 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40879 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40880 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40881 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40882 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40883 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40884 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40885 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40886 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 597 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40887 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40888 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40889 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40890 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40891 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40892 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40893 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40894 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 598 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40895 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40896 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40897 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40898 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40899 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40900 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40901 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40902 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 599 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40903 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40904 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40905 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40906 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40907 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40908 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40909 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40910 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 600 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40911 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40912 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40913 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40914 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

TABLE 38.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40915 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40916 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40917 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 601 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40918 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40919 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40920 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40921 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40922 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40923 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40924 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40925 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 602 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40926 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40927 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40928 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40929 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40930 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40931 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40932 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40933 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 603 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40934 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40935 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40936 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40937 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40938 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40939 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40940 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40941 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 604 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40942 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40943 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40944 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40945 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40946 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40947 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40948 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40949 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 605 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40950 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40951 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40952 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40953 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40954 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40955 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40956 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40957 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 606 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40958 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40959 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40960 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40961 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40962 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40963 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40964 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40965 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 607 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40966 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40967 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40968 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40969 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40970 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40971 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40972 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40973 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 608 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40974 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40975 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40976 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40977 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40978 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40979 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40980 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40981 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 609 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40982 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40983 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40984 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40985 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40986 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40987 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40988 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40989 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 610 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40990 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40991 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40992 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40993 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40994 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40995 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40996 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40997 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 611 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40998 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
40999 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
41000 Load Read/Write 0: Disable Disables or Enables PCC3300,
Demand load demand PCC3300V2
System 1: Enable operation of all
Enable connected gensets.
41001 Load Read/Write 0: Run Hours Sets the sequencing PCC3300,
Demand Equalization priority for load PCC3300V2
Type demand.
1: Fixed
Sequence
41002 Load Read/Write 0: kW Sets whether the load PCC3300,
Demand demand start/stop PCC3300V2
Threshold 1: %kW control is based on a
Method relative (%) or
absolute (kW)
threshold.
41003 Load Read/Write Multiplier: 1 Unit: % When the ratio of load PCC3300,
Demand to capacity is greater PCC3300V2
Start Offset: 0 Lower Limit: 25 than this value the
Threshold Size (bits): 8 Upper Limit: 100 next genset will start.
(%kW) Must be greater than
Sign: U Load Demand Stop
Threshold by at least
5%.
41004 Load Read/Write Multiplier: 1 Unit: kW When surplus capacity PCC3300,
Demand is less than this value PCC3300V2
Start Offset: 0 Lower Limit: 5 the next genset will
Threshold Size (bits): 16 Upper Limit: start. Must be less
(kW) 5000 than Load Demand
Stop Threshold (kW).
Sign: U

Copyright © 2023 Cummins Inc. 612 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41005 Load Read/Write Multiplier: 1 Unit: % When the ratio of load PCC3300,
Demand to capacity is less than PCC3300V2
Stop Offset: 0 Lower Limit: 20 this value the next
Threshold Size (bits): 8 Upper Limit: 95 genset will stop. Must
(%kW) be less than Load
Sign: U Demand Start
Threshold by at least
5%.
41006 Load Read/Write Multiplier: 1 Unit: kW When surplus capacity PCC3300,
Demand is greater than this PCC3300V2
Stop Offset: 0 Lower Limit: 5 value the next genset
Threshold Size (bits): 16 Upper Limit: will stop. Must be
(kW) 5000 greater than Load
Demand Start
Sign: U Threshold (kW).
41007 Load Read/Write Multiplier: 1 Unit: hours When the difference PCC3300,
Demand Run between Load PCC3300V2
Hours Offset: 0 Lower Limit: 1 Demand Genset Run
Differential Size (bits): 16 Upper Limit: 250 Hours between any
running genset and
Sign: U any stopped genset
reaches this value the
stopped genset will be
started.
41008 Load Read/Write Multiplier: 1 Unit: seconds Sets the time delay PCC3300,
Demand that the system waits PCC3300V2
Genset Fail Offset: 0 Lower Limit: 10 for a genset to come
Delay Size (bits): 16 Upper Limit: 900 online before declaring
it as failed.
Sign: U
41009 Load Read/Write Multiplier: 1 Unit: seconds Sets the time delay PCC3300,
Demand before gensets are PCC3300V2
Initial Delay Offset: 0 Lower Limit: 60 allowed to stop after
Size (bits): 16 Upper Limit: initial start or after
1500 resuming halted load
demand.
Sign: U
41010 Load Read/Write Multiplier: 1 Unit: seconds Sets the time delay PCC3300,
Demand before next genset is PCC3300V2
Start Delay Offset: 0 Lower Limit: 0 allowed to start.
Size (bits): 16 Upper Limit:
1500
Sign: U

A029X159 (Issue 31) 613 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41011 Load Read/Write Multiplier: 1 Unit: seconds Sets the time delay PCC3300,
Demand before next genset is PCC3300V2
Stop Delay Offset: 0 Lower Limit: 60 allowed to stop.
Size (bits): 16 Upper Limit:
1500
Sign: U
41012 Clear Lost Read/Write 0: No When set to YES all PCC3300,
Gensets gensets in state "Lost" PCC3300V2
Local 1: Yes will change to state
"Gen Does Not Exist"
in order to clear Lost
Genset Warning.
41013 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 1. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
1 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

Copyright © 2023 Cummins Inc. 614 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41014 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 2. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
2 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41015 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 3. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
3 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 31) 615 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41016 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 4. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
4 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41017 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 5. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
5 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

Copyright © 2023 Cummins Inc. 616 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41018 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 6. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
6 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41019 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 7. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
7 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 31) 617 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41020 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 8. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
8 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41021 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 9. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
9 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

Copyright © 2023 Cummins Inc. 618 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41022 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 10. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
10 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41023 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 11. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
11 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 31) 619 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41024 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 12. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
12 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41025 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 13. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
13 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

Copyright © 2023 Cummins Inc. 620 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41026 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 14. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
14 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41027 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 15. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
15 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 31) 621 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41028 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 16. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
16 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41030 Synchronize Read/Write 0: No When set to YES PCC3300,
System system settings from PCC3300V2
Settings 1: Yes the genset will be
broadcasted and
synchronized to all
other gensets in the
network.
41031 Battery Read Only 0: Inactive Battery Charger 2 PCC3300,
Charger 2 Failed Switch function PCC3300V2
Failed Switch 1: Active output status; gives
software
Inactive/Active state
41032 Battery Read Only 0: Inactive Battery Charger 3 PCC3300,
Charger 3 Failed Switch function PCC3300V2
Failed Switch 1: Active output status; gives
software
Inactive/Active state
41033 Battery Read Only 0: Inactive Battery Charger 4 PCC3300,
Charger 4 Failed Switch function PCC3300V2
Failed Switch 1: Active output status; gives
software
Inactive/Active state

Copyright © 2023 Cummins Inc. 622 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41034 Intake Air Read Only 0: Inactive Intake Air Restriction PCC3300,
Restriction Indicator 1 fault switch PCC3300V2
Indicator 1 1: Active function output status;
fault switch gives software
Inactive/Active state
41035 Intake Air Read Only 0: Inactive Intake Air Restriction PCC3300,
Restriction Indicator 2 fault switch PCC3300V2
Indicator 2 1: Active function output status;
fault switch gives software
Inactive/Active state
41036 Intake Air Read Only 0: Inactive Intake Air Restriction PCC3300,
Restriction Indicator 3 fault switch PCC3300V2
Indicator 3 1: Active function output status;
fault switch gives software
Inactive/Active state
41037 Intake Air Read Only 0: Inactive Intake Air Restriction PCC3300,
Restriction Indicator 4 fault switch PCC3300V2
Indicator 4 1: Active function output status;
fault switch gives software
Inactive/Active state
41038 Starter Air Read Only 0: Inactive "Starter Air Supply PCC3300,
Supply Pressure Low Fault PCC3300V2
Pressure 1: Active Switch function output
Low Fault status; gives software
Switch Inactive/Active"
41039 Starter Air Read Only 0: Inactive "Starter Air Tank PCC3300,
Tank Volume Volume Low Fault PCC3300V2
Low Fault 1: Active Switch function output
Switch status; gives software
Inactive/Active state"
41040 Instantaneou Read Only Multiplier: Unit: kg/hr Instantaneous PCC3300,
s HC 0.0078125 Emissions Parameter PCC3300V2
received via PGN
Offset: 0 Lower Limit: 130900 from ECM.
Size (bits): 16 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41041 Instantaneou Read Only Multiplier: Unit: kg/hr Instantaneous PCC3300,
s NOx 0.0078125 Emissions Parameter PCC3300V2
received via PGN
Offset: 0 Lower Limit: 130900 from ECM.
Size (bits): 16 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.

A029X159 (Issue 31) 623 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41042 Instantaneou Read Only Multiplier: Unit: kg/hr Instantaneous PCC3300V2
s CO 0.0078125 Emissions Parameter PCC3300,
received via PGN
Offset: 0 Lower Limit: 130900 from ECM.
Size (bits): 16 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41043 Instantaneou Read Only Multiplier: Unit: kg/hr Instantaneous PCC3300,
s PM 0.0078125 Emissions Parameter PCC3300V2
received via PGN
Offset: 0 Lower Limit: 130900 from ECM.
Size (bits): 16 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41044 Instantaneou Read Only Multiplier: Unit: kg/hr Instantaneous PCC3300,
s SO2 0.0078125 Emissions Parameter PCC3300V2
received via PGN
Offset: 0 Lower Limit: 130900 from ECM.
Size (bits): 16 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41045 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of HC received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41046 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of HC received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41047 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of NOx received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.

Copyright © 2023 Cummins Inc. 624 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41048 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of NOx received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41049 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of CO received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41050 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of CO received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41051 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of PM received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41052 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of PM received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41053 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of SO2 received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.

A029X159 (Issue 31) 625 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41054 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of SO2 received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41055 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of HC received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41056 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of HC received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41057 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of NOx received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41058 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of NOx received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41059 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of CO received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.

Copyright © 2023 Cummins Inc. 626 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41060 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of CO received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41061 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of PM received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41062 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of PM received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41063 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of SO2 received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41064 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of SO2 received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41065 Reverse Read Only Multiplier: 0.01 Unit: % Sets the Reverse PCC3300V2
kVAR kVAR fault trip
Threshold Offset: 0 Lower Limit: 15 threshold as
Size (bits): 16 Upper Limit: 50 percentage of Standby
kVA rating.
Sign: U

A029X159 (Issue 31) 627 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41066 Reverse Read Only Multiplier: 0.1 Unit: seconds Sets the Reverse PCC3300V2
kVAR Time kVAR fault trip time
Delay Offset: 0 Lower Limit: 1 delay.
Size (bits): 16 Upper Limit: 60
Sign: U
41067 High AC Read Only Multiplier: 0.01 Unit: % Percent of desired PCC3300V2
Voltage voltage at which High
Threshold Offset: 0 Lower Limit: 105 AC Voltage fault
Size (bits): 16 Upper Limit: 125 becomes active.
Sign: U
41068 High AC Read Only 0: Inverse Time “Fixed Time” setup PCC3300V2
Voltage Trip allows a greater time
Characteristi 1: Fixed Time delay until shutdown
c when voltage
overshoots (good for
starting motors). When
the control is set up to
operate as “Inverse
Time”, the fault will be
more sensitive to
voltage spikes and will
trip more rapidly.
41069 High AC Read Only Multiplier: 0.1 Unit: seconds Time delay before PCC3300V2
Voltage High AC Voltage fault
Delay Offset: 0 Lower Limit: 0.1 becomes active.
Size (bits): 8 Upper Limit: 10
Sign: U
41070 Low AC Read Only Multiplier: 0.01 Unit: % Percent of desired PCC3300V2
Voltage voltage at which Low
Threshold Offset: 0 Lower Limit: 50 AC Voltage fault
Size (bits): 16 Upper Limit: 95 becomes active.

Sign: U
41071 Low AC Read Only Multiplier: 0.1 Unit: seconds Time delay before Low PCC3300V2
Voltage AC Voltage fault
Delay Offset: 0 Lower Limit: 2 becomes active
Size (bits): 8 Upper Limit: 20
Sign: U
41072 Reverse kW Read Only Multiplier: 0.01 Unit: % Sets the Reverse kW PCC3300V2
Threshold fault trip threshold as
Offset: 0 Lower Limit: 5 percentage of Standby
Size (bits): 16 Upper Limit: 30 kW rating.

Sign: U

Copyright © 2023 Cummins Inc. 628 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41073 Reverse kW Read Only Multiplier: 0.1 Unit: seconds Sets the Reverse kW PCC3300V2
Time Delay fault trip time delay
Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 15
Sign: U
41074 Overfrequen Read Only Multiplier: 0.1 Unit: Hz Number of Hertz PCC3300V2
cy Threshold Alternator Line
Offset: 0 Lower Limit: 2 Frequency may be
Size (bits): 8 Upper Limit: 10 over nominal
frequency before
Sign: U Overfrequency fault
becomes active.
41075 Overfrequen Read Only Multiplier: 0.1 Unit: seconds Time delay before PCC3300V2
cy Delay Overfrequency fault
Offset: 0 Lower Limit: 1 becomes active.
Size (bits): 8 Upper Limit: 20
Sign: U
41076 Underfreque Read Only Multiplier: 0.1 Unit: Hz Number of Hertz PCC3300V2
ncy Alternator Line
Threshold Offset: 0 Lower Limit: 0.1 Frequency may be
Size (bits): 16 Upper Limit: 10 under nominal
frequency before
Sign: U Underfrequency fault
becomes active.
41077 Underfreque Read Only Multiplier: 0.1 Unit: seconds Time delay before the PCC3300V2
ncy Delay Underfrequency fault
Offset: 0 Lower Limit: 1 becomes active.
Size (bits): 8 Upper Limit: 20
Sign: U
41078 Custom Read Only 0: Disabled use to enable custom PCC3300V2
Overcurrent time overcurrent
Protection 1: Enabled protection
Enable
41079 Custom Read Only Multiplier: 0.1 Unit: % % standby current PCC3300V2
Overcurrent above which custom
Threshold Offset: 0 Lower Limit: 50 overcurrent feature
Size (bits): 16 Upper Limit: 150 starts timing
Sign: U
41080 Custom Read Only Multiplier: 0.001 Unit: seconds sets the timing PCC3300V2
Overcurrent characteristic of
Time Offset: 0 Lower Limit: 0.1 custom overcurrent
Characteristi Size (bits): 16 Upper Limit: 65
c
Sign: U

A029X159 (Issue 31) 629 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41081 Aux101 Read Only Multiplier: 1 Unit: degF Low limit for the LBNG PCC3300V2
LBNG Aux 101 I/O Module
Alternator Offset: 0 Lower Limit: 0 Alternator Temp Out
Temp OOR Size (bits): 16 Upper Limit: 509 of Range faults.
High Limit
Sign: U
41082 Aux101 Read Only Multiplier: 1 Unit: degF Low limit for the LBNG PCC3300V2
LBNG Aux 101 I/O Module
Alternator Offset: 0 Lower Limit: 0 Alternator Temp Out
Temp OOR Size (bits): 16 Upper Limit: 509 of Range faults.
Low Limit
Sign: U
41083 Aux101 Read Only Multiplier: 1 Unit: degF High limit for the PCC3300V2
LBNG LBNG Aux 101 I/O
Drive/Non- Offset: 0 Lower Limit: 0 Module Drive/Non-
Drive End Size (bits): 16 Upper Limit: 509 Drive End Bearing
Bearing Temp Out of Range
Temp OOR Sign: U faults.
High Limit
41084 Aux101 Read Only Multiplier: 1 Unit: degF Low limit for the LBNG PCC3300V2
LBNG Aux 101 I/O Module
Drive/Non- Offset: 0 Lower Limit: 0 Drive/Non-Drive End
Drive End Size (bits): 16 Upper Limit: 509 Bearing Temp Out of
Bearing Range faults.
Temp OOR Sign: U
Low Limit
41085 Application Read Only 0: Standby Selects genset's PCC3300V2
Rating Select standby/prime/base
1: Prime application rating.
2: Base
41086 AVR Read Only Multiplier: 0.01 Unit: Increases or PCC3300V2
Damping decreases the output
Effect (50 Offset: 0 Lower Limit: 0 response of the AVR.
Hz) Size (bits): 16 Upper Limit: A lower input value will
99.99 increase the transient
response. A higher
Sign: U value will decrease the
transient response.
41087 AVR Read Only Multiplier: 0.01 Unit: Increases or PCC3300V2
Damping decreases the output
Effect (60 Offset: 0 Lower Limit: 0 response of the AVR.
Hz) Size (bits): 16 Upper Limit: A lower input value will
99.99 increase the transient
response. A higher
Sign: U value will decrease the
transient response.

Copyright © 2023 Cummins Inc. 630 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41088 V/Hz Method Read Only 0: Fixed Knee Sets the knee PCC3300V2
Frequency frequency logic
characteristic of the
1: Relative Knee V/Hz curve either fixed
Frequency knee or relative (to
Target Speed) knee
frequency.
41089 AmpSentry Read Only 0: Disable "Disable Override PCC3300V2
Maintenance function for AmpSentry
Mode 1: Enable Maintenance Mode.
Disable Used for engineering
Override purposes and heavy
motors starting that
may look like a short
circuit"
41090 High Read Only Multiplier: 1 Unit: degF High Alternator PCC3300V2
Alternator Temperature 1
Temperature Offset: 0 Lower Limit: 100 Shutdown Threshold
1 Shutdown Size (bits): 16 Upper Limit: for the I/O Module
Threshold 1000 Fault (AUX 101)

Sign: S
41091 High Read Only Multiplier: 0.1 Unit: seconds High Alternator PCC3300V2
Alternator Temperature 1
Temperature Offset: 0 Lower Limit: 1 Shutdown Time for the
1 Shutdown Size (bits): 16 Upper Limit: 30 I/O Module Fault (AUX
Time 101)
Sign: U
41092 High Read Only Multiplier: 1 Unit: degF High Alternator Temp PCC3300V2
Alternator 1 Threshold for the I/O
Temperature Offset: 0 Lower Limit: 100 Module fault. Warning
1 Threshold Size (bits): 16 Upper Limit: Threshold
(Aux101) 1000
Sign: S
41093 High Read Only Multiplier: 0.1 Unit: seconds High Alternator Temp PCC3300V2
Alternator 1 fault time for the I/O
Temperature Offset: 0 Lower Limit: 0.1 Module fault. Warning
1 Time Size (bits): 16 Upper Limit: 30 Time
(Aux101)
Sign: U
41094 High Read Only Multiplier: 1 Unit: degF High Alternator PCC3300V2
Alternator Temperature 2
Temperature Offset: 0 Lower Limit: 100 Shutdown Threshold
2 Shutdown Size (bits): 16 Upper Limit: for the I/O Module
Threshold 1000 Fault

Sign: S

A029X159 (Issue 31) 631 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41095 High Read Only Multiplier: 0.1 Unit: seconds High Alternator PCC3300V2
Alternator Temperature 2
Temperature Offset: 0 Lower Limit: 1 Shutdown Time for the
2 Shutdown Size (bits): 16 Upper Limit: 30 I/O Module Fault
Time
Sign: U
41096 High Read Only Multiplier: 1 Unit: degF High Alternator Temp PCC3300V2
Alternator 2 Threshold for the I/O
Temperature Offset: 0 Lower Limit: 100 Module fault. Warning
2 Threshold Size (bits): 16 Upper Limit: Threshold
(Aux101) 1000
Sign: S
41097 High Read Only Multiplier: 0.1 Unit: seconds High Alternator Temp PCC3300V2
Alternator 2 fault time for the I/O
Temperature Offset: 0 Lower Limit: 0.1 Module fault. Warning
2 Time Size (bits): 16 Upper Limit: 30 Time.
(Aux101)
Sign: U
41098 High Read Only Multiplier: 1 Unit: degF High Alternator PCC3300V2
Alternator Temperature 3
Temperature Offset: 0 Lower Limit: 100 Shutdown Threshold
3 Shutdown Size (bits): 16 Upper Limit: for the I/O Module
Threshold 1000 Fault

Sign: S
41099 High Read Only Multiplier: 0.1 Unit: seconds High Alternator PCC3300V2
Alternator Temperature 3
Temperature Offset: 0 Lower Limit: 1 Shutdown Time for the
3 Shutdown Size (bits): 16 Upper Limit: 30 I/O Module Fault
Time
Sign: U
41100 High Read Only Multiplier: 1 Unit: degF High Alternator Temp PCC3300V2
Alternator 3 Threshold for the I/O
Temperature Offset: 0 Lower Limit: 100 Module fault. Warning
3 Threshold Size (bits): 16 Upper Limit: Threshold
(Aux101) 1000
Sign: S
41101 High Read Only Multiplier: 0.1 Unit: seconds High Alternator Temp PCC3300V2
Alternator 3 fault time for the I/O
Temperature Offset: 0 Lower Limit: 1 Module fault. Warning
3 Time Size (bits): 16 Upper Limit: 30 Time.
(Aux101)
Sign: U

Copyright © 2023 Cummins Inc. 632 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41102 AUX101 DE Read Only 0: Disable Enables the Drive End PCC3300V2
Temp Bearing Temperature
Shutdown 1: Enable shutdown Fault for
Fault Enable Non LBNG
applications.
41103 High Drive Read Only Multiplier: 1 Unit: degF High Drive End PCC3300V2
End Bearing Bearing Temperature
Temperature Offset: 0 Lower Limit: 100 Shutdown Threshold
Shutdown Size (bits): 16 Upper Limit: for the I/O Module
Threshold 1000 Fault

Sign: S
41104 High Drive Read Only Multiplier: 0.1 Unit: seconds High Drive End PCC3300V2
End Bearing Bearing Temperature
Temperature Offset: 0 Lower Limit: 1 Shutdown Time for the
Shutdown Size (bits): 16 Upper Limit: 30 I/O Module Fault
Time
Sign: U
41105 High Drive Read Only Multiplier: 1 Unit: degF High Drive End PCC3300V2
End Bearing Bearing Temp
Temperature Offset: 0 Lower Limit: 100 Threshold for the I/O
Threshold Size (bits): 16 Upper Limit: Module fault.
(Aux101) 1000
Sign: S
41106 High Drive Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
End Bearing the High Drive End
Temperature Offset: 0 Lower Limit: 0.1 Bearing Temp fault
Time Size (bits): 16 Upper Limit: 30 becomes active, from
(Aux101) the I/O Module.
Sign: U
41107 High Exhaust Read Only Multiplier: 1 Unit: degF High Exhaust Stack PCC3300V2
Stack Temp 1 Threshold for
Temperature Offset: 0 Lower Limit: 200 the I/O Module fault.
1 Threshold Size (bits): 16 Upper Limit:
(Aux101) 1600
Sign: S
41108 High Exhaust Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Stack the High Exhaust
Temperature Offset: 0 Lower Limit: 0.1 Stack Temp 1 fault
1 Time Size (bits): 16 Upper Limit: 30 becomes active, from
(Aux101) the I/O Module.
Sign: U

A029X159 (Issue 31) 633 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41109 High Exhaust Read Only Multiplier: 1 Unit: degF High Exhaust Stack PCC3300V2
Stack Temp 2 Threshold for
Temperature Offset: 0 Lower Limit: 200 the I/O Module fault.
2 Threshold Size (bits): 16 Upper Limit:
(Aux101) 1600
Sign: S
41110 High Exhaust Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Stack the High Exhaust
Temperature Offset: 0 Lower Limit: 0.1 Stack Temp 2 fault
2 Time Size (bits): 16 Upper Limit: 30 becomes active, from
(Aux101) the I/O Module.
Sign: U
41111 High Oil Read Only Multiplier: 1 Unit: degF High Oil Temp PCC3300V2
Temperature Threshold for the I/O
Threshold Offset: 0 Lower Limit: 100 Module HOT fault.
(Aux101) Size (bits): 16 Upper Limit: 300
Sign: S
41112 High Oil Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Temperature the High Oil Temp
Time Offset: 0 Lower Limit: 0.1 fault becomes active,
(Aux101) Size (bits): 16 Upper Limit: 30 from the I/O Module.

Sign: U
41113 High Intake Read Only Multiplier: 1 Unit: degF High Intake Manifold PCC3300V2
Manifold Temp 1 Threshold for
Temperature Offset: 0 Lower Limit: 100 the I/O Module fault.
1 Threshold Size (bits): 16 Upper Limit: 270
(Aux101)
Sign: S
41114 High Intake Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Temperature the High Intake
1 Time Offset: 0 Lower Limit: 0.1 Manifold Temp 1 fault
(Aux101) Size (bits): 16 Upper Limit: 30 becomes active, from
the I/O Module.
Sign: U
41115 AUX101 Read Only 0: Disable Enables the Non Drive PCC3300V2
NDE Temp End Bearing
Shutdown 1: Enable Temperature
Fault Enable shutdown Fault for
Non LBNG
applications.

Copyright © 2023 Cummins Inc. 634 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41116 High Non- Read Only Multiplier: 1 Unit: degF High Non-Drive End PCC3300V2
Drive End Bearing Temperature
Bearing Offset: 0 Lower Limit: 100 Shutdown Threshold
Temperature Size (bits): 16 Upper Limit: for the I/O Module
Shutdown 1000 Fault
Threshold
Sign: S
41117 High Non- Read Only Multiplier: 0.1 Unit: seconds High Non-Drive End PCC3300V2
Drive End Bearing Temperature
Bearing Offset: 0 Lower Limit: 1 Shutdown Time for the
Temperature Size (bits): 16 Upper Limit: 30 I/O Module Fault
Shutdown
Time Sign: U

41118 High Non- Read Only Multiplier: 1 Unit: degF High Non-Drive End PCC3300V2
Drive End Bearing Temp
Bearing Offset: 0 Lower Limit: 100 Threshold for the I/O
Temperature Size (bits): 16 Upper Limit: Module fault.
Threshold 1000
(Aux101)
Sign: S
41119 High Non- Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Drive End the High Non-Drive
Bearing Offset: 0 Lower Limit: 0.1 End Bearing Temp
Temperature Size (bits): 16 Upper Limit: 30 fault becomes active,
Time from the I/O Module.
(Aux101) Sign: U

41120 High Fuel Read Only Multiplier: 0.1 Unit: % High Fuel Level PCC3300V2
Level Threshold for the I/O
Threshold Offset: 0 Lower Limit: 50 Module fault.
(Aux101) Size (bits): 16 Upper Limit: 100
Sign: U
41121 High Fuel Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Level Time the High Fuel Level
(Aux101) Offset: 0 Lower Limit: 0.1 fault becomes active,
Size (bits): 16 Upper Limit: 30 from the I/O Module.

Sign: U
41122 Low Fuel Read Only Multiplier: 0.1 Unit: % Low Fuel Level PCC3300V2
Level Threshold for the I/O
Threshold Offset: 0 Lower Limit: 10 Module fault.
(Aux101) Size (bits): 16 Upper Limit: 70
Sign: U

A029X159 (Issue 31) 635 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41123 Low Fuel Read Only Multiplier: 0.1 Unit: seconds Low Fuel Level fault PCC3300V2
Level Time time for the I/O
(Aux101) Offset: 0 Lower Limit: 0.1 Module fault.
Size (bits): 16 Upper Limit: 30
Sign: U
41124 Very Low Read Only Multiplier: 0.1 Unit: % Very Low Fuel Level PCC3300V2
Fuel Level Threshold for the AUX
Threshold Offset: 0 Lower Limit: 0 101 I/O Module fault.
(Aux101) Size (bits): 16 Upper Limit: 50
Sign: U
41125 Very Low Read Only Multiplier: 0.1 Unit: seconds Very Low Fuel Level PCC3300V2
Fuel Level fault time for the AUX
Time Offset: 0 Lower Limit: 0.1 101 I/O Module fault.
(Aux101) Size (bits): 16 Upper Limit: 30
Sign: U
41126 Fuel Level Read Only Multiplier: 1 Unit: Ohm During setup this trim PCC3300V2
100 Percent is set the 100%
Resistance Offset: 0 Lower Limit: 30 resistance, when the
(Aux101) Size (bits): 16 Upper Limit: fuel tank is full.
2500
Sign: U
41127 Fuel Level Read Only Multiplier: 1 Unit: Ohm Trim to set the 0% (or PCC3300V2
Zero Percent empty) resistance
Resistance Offset: 0 Lower Limit: 0 level on the sensor for
(Aux101) Size (bits): 16 Upper Limit: the tank to be
2500 measured.

Sign: U
41128 Fuel Tank Read Only Multiplier: 1 Unit: gallons Trim to set the fuel PCC3300V2
Capacity tank capacity.
(Aux101) Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
15000
Sign: U
41129 Aux101 Read Only 0: Disable Enables the Aux 101 PCC3300V2
Alternator I/O Module Alternator
Temperature 1: Enable Temp Out of Range
OOR Check faults. For use with
Enable either LBNG or non-
LBNG gensets.

Copyright © 2023 Cummins Inc. 636 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41130 Aux101 Read Only Multiplier: 0.1 Unit: seconds Time limit for the Aux PCC3300V2
Alternator 101 I/O Module
Temperature Offset: 0 Lower Limit: 0 Alternator Temp Out
OOR Time Size (bits): 16 Upper Limit: 10 of Range faults. For
use with either LBNG
Sign: U or non-LBNG gensets.
41131 Aux101 Read Only 0: Disable Enable the Aux 101 PCC3300V2
Ambient I/O Module Ambient
Temp OOR 1: Enable Temp Out of Range
Check faults
Enable
41132 Aux101 Drive Read Only 0: Disable Enable the Aux 101 PCC3300V2
End Bearing I/O Module Drive End
Temperature 1: Enable Bearing Temp Out of
OOR Check Range faults. For use
Enable with either LBNG or
non-LBNG gensets.
41133 Aux101 Read Only Multiplier: 0.01 Unit: Vdc High limit for the Aux PCC3300V2
Drive/Non- 101 I/O Module
Drive End Offset: 0 Lower Limit: 0 Drive/Non-Drive End
Bearing Size (bits): 16 Upper Limit: 5 Bearing Temp Out of
Temp OOR Range faults.
High Limit Sign: S

41134 Aux101 Read Only Multiplier: 0.01 Unit: Vdc Low limit for the Aux PCC3300V2
Drive/Non- 101 I/O Module
Drive End Offset: 0 Lower Limit: 0 Drive/Non-Drive End
Bearing Size (bits): 16 Upper Limit: 5 Bearing Temp Out of
Temp OOR Range faults.
Low Limit Sign: S

41135 Aux101 Read Only Multiplier: 0.1 Unit: seconds Time limit for the Aux PCC3300V2
Drive/Non- 101 I/O Module
Drive End Offset: 0 Lower Limit: 0 Bearing Temp Out of
Bearing Size (bits): 16 Upper Limit: 10 Range faults. For use
Temperature with either LBNG or
OOR Time Sign: U non-LBNG gensets.
41136 Aux101 Read Only 0: Disable Enables the Aux 101 PCC3300V2
Exhaust I/O Module Exhaust
Stack Temp 1: Enable Stack Temp 1 Out of
1 OOR Range fault.
Check
Enable
41137 Aux101 Read Only 0: Disable Enables the Aux 101 PCC3300V2
Exhaust I/O Module Exhaust
Stack Temp 1: Enable Stack Temp 2 Out of
2 OOR Range fault.
Check
Enable

A029X159 (Issue 31) 637 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41138 Aux101 Read Only Multiplier: 0.01 Unit: Vdc High limit for the Aux PCC3300V2
Exhaust 101 I/O Module
Stack Temp Offset: 0 Lower Limit: 0 Exhaust Stack Temp
OOR High Size (bits): 16 Upper Limit: 5 Out of Range faults.
Limit
Sign: S
41139 Aux101 Read Only Multiplier: 0.01 Unit: Vdc Low limit for the Aux PCC3300V2
Exhaust 101 I/O Module
Stack Temp Offset: 0 Lower Limit: 0 Exhaust Stack Temp
OOR Low Size (bits): 16 Upper Limit: 5 Out of Range faults.
Limit
Sign: S
41140 Aux101 Read Only Multiplier: 0.1 Unit: seconds Time limit for the Aux PCC3300V2
Exhaust 101 I/O Module
Stack Temp Offset: 0 Lower Limit: 0 Exhaust Stack Temp
OOR Time Size (bits): 16 Upper Limit: 10 Out of Range faults.

Sign: U
41141 Aux101 Fuel Read Only 0: Disable Enables the Aux 101 PCC3300V2
Level OOR I/O Module Fuel Level
Check 1: Enable Out of Range fault.
Enable
41142 Aux101 Fuel Read Only Multiplier: 0.01 Unit: Vdc High limit for the Aux PCC3300V2
Level OOR 101 I/O Module Fuel
High Limit Offset: 0 Lower Limit: 0 Level Out of Range
Size (bits): 16 Upper Limit: 5 fault.

Sign: S
41143 Aux101 Fuel Read Only Multiplier: 0.01 Unit: Vdc Low limit for the Aux PCC3300V2
Level OOR 101 I/O Module Fuel
Low Limit Offset: 0 Lower Limit: 0 Level Out of Range
Size (bits): 16 Upper Limit: 5 fault.

Sign: S
41144 Aux101 Fuel Read Only Multiplier: 0.1 Unit: seconds Time limit for the Aux PCC3300V2
Level OOR 101 I/O Module Fuel
Time Offset: 0 Lower Limit: 0 Level Out of Range
Size (bits): 16 Upper Limit: 10 fault.

Sign: U
41145 Aux101 Read Only 0: Disable Enables the Aux 101 PCC3300V2
Intake I/O Module Intake
Manifold 1: Enable Manifold Temp Out of
Temp OOR Range faults.
Check
Enable

Copyright © 2023 Cummins Inc. 638 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41146 Aux101 Non- Read Only 0: Disable Enables the Aux 101 PCC3300V2
Drive End I/O Module Non-Drive
Bearing 1: Enable End Bearing Temp
Temperature Out of Range faults.
OOR Check For use with either
Enable LBNG or non-LBNG
gensets.
41147 Aux101 Oil Read Only 0: Disable Enables the Aux 101 PCC3300V2
Temp OOR I/O Module Oil Temp
Check 1: Enable Out of Range faults.
Enable
41148 Aux101 Read Only Multiplier: 0.01 Unit: Vdc High limit for the Aux PCC3300V2
Oil/Ambient/I 101 I/O Module Oil
ntake Offset: 0 Lower Limit: 0 Temp Ambient Temp
Manifold Size (bits): 16 Upper Limit: 5 and Intake Manifold
Temp OOR Temp Out of Range
High Limit Sign: S faults
41149 Aux101 Read Only Multiplier: 0.01 Unit: Vdc Low limit for the Aux PCC3300V2
Oil/Ambient/I 101 I/O Module Oil
ntake Offset: 0 Lower Limit: 0 Temp Ambient Temp
Manifold Size (bits): 16 Upper Limit: 5 and Intake Manifold
Temp OOR Temp Out of Range
Low Limit Sign: S faults
41150 Aux101 Read Only Multiplier: 0.1 Unit: seconds Time limit for the Aux PCC3300V2
Oil/Ambient/I 101 I/O Module Oil
ntake Offset: 0 Lower Limit: 0 Temp Ambient Temp
Manifold Size (bits): 16 Upper Limit: 10 and Intake Manifold
Temp OOR Temp Out of Range
Time Sign: U faults
41151 Excitation Read Only 0: Shunt The type of excitation PCC3300V2
Source power source PMG or
1: PMG Shunt
2: Auxiliary
Winding
41152 High LTA Read Only Multiplier: 1 Unit: degF "High LTA PCC3300V2
Temperature Temperature
Threshold Offset: 0 Lower Limit: -40 Threshold for the I/O
(Aux101) Size (bits): 16 Upper Limit: 300 Module fault"
Sign: S
41153 High LTA Read Only Multiplier: 0.1 Unit: seconds "Time limit for the Aux PCC3300V2
Temperature 101 I/O Module High
Time Offset: 0 Lower Limit: 0 LTA Temperature
(Aux101) Size (bits): 16 Upper Limit: 30 faults"

Sign: U

A029X159 (Issue 31) 639 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41154 Aux101 LTA Read Only Multiplier: 0.01 Unit: Vdc "High limit for the Aux PCC3300V2
Temperature 101 I/O Module LTA
OOR High Offset: 0 Lower Limit: 0 Temperature Out of
Limit Size (bits): 16 Upper Limit: 5 Range faults."

Sign: U
41155 Aux101 LTA Read Only Multiplier: 0.01 Unit: Vdc "Low limit for the Aux PCC3300V2
Temperature 101 I/O Module LTA
OOR Low Offset: 0 Lower Limit: 0 Temperature Out of
Limit Size (bits): 16 Upper Limit: 5 Range faults."

Sign: U
41156 Aux101 LTA Read Only Multiplier: 0.1 Unit: seconds "Time limit for the Aux PCC3300V2
Temperature 101 I/O Module LTA
OOR Time Offset: 0 Lower Limit: 0 Temperature Out of
Size (bits): 16 Upper Limit: 10 Range faults"

Sign: U
41157 Aux101 LTA Read Only 0: Disabled "Enables the AUX101 PCC3300V2
Temperature I/O Module LTA
OOR Check 1: Enabled Temperature Out Of
Enable Range Faults."
41158 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 1 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch

Copyright © 2023 Cummins Inc. 640 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
41158 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 1 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 641 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41159 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 2 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 642 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41159 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 2 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 643 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41160 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 3 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 644 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41160 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 3 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 645 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41161 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 4 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 646 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41161 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 4 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 647 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41162 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 5 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 648 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41162 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 5 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 649 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41163 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 6 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 650 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41163 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 6 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 651 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41164 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 7 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 652 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41164 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 7 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 653 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41165 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 8 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 654 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41165 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 8 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 655 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41166 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 1 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 656 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41166 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 1 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 657 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41167 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 2 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 658 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41167 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 2 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 659 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41168 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 3 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 660 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41168 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 3 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 661 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41169 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 4 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 662 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41169 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 4 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

A029X159 (Issue 31) 663 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41170 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 5 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

Copyright © 2023 Cummins Inc. 664 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41170 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 5 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
41171 Aux101 1 Read Only 0: Analog Input Selects whether the PCC3300V2
Analog Input input will be active
6 Sensor 1: Switch Input - open, active closed, or
Type Active Closed an analog input.
2: Switch Input -
Active Open

A029X159 (Issue 31) 665 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41172 Aux101 1 Read Only 0: Do Nothing Selects the type of PCC3300V2
Analog Input analog input sensor.
6 Function 1: Oil
Pointer Temperature
2: Exhaust Stack
Temperature 1
3: Exhaust Stack
Temperature 2
4: Ambient
Temperature
5: Fuel Level
6: Alternator
Temperature 1
7: Alternator
Temperature 2
8: Alternator
Temperature 3
9: Intake
Manifold
Temperature 1
10: Drive End
Bearing
Temperature
11: Non-Drive
End Bearing
Temperature
12: LTA
Temperature
13: Bank A
Pressure Sensor
14: Bank B
Pressure Sensor

Copyright © 2023 Cummins Inc. 666 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41173 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 7 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

A029X159 (Issue 31) 667 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41173 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 7 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch

Copyright © 2023 Cummins Inc. 668 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41174 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 8 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch

A029X159 (Issue 31) 669 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41174 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 8 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
41175 Configurable Read Only 0: None If the configurable PCC3300V2
Input #1 input #1 is configured
Fault 1: Warning as a fault input, this
Response 2: Shutdown sets the fault level

3: Shutdown
w/Cooldown
4: Derate

Copyright © 2023 Cummins Inc. 670 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41176 Configurable Read Only 0: None If the configurable PCC3300V2
Input #2 input #2 is configured
Fault 1: Warning as a fault input, this
Response 2: Shutdown sets the fault level

3: Shutdown
w/Cooldown
4: Derate
41177 Start Read Only 0: Active Closed Start Type input PCC3300V2
Type/Configu software logic state
rable Input 1: Active Open inversion bypass
#11 Active control
State
Selection
41178 Speed Bias Read Only Multiplier: 0.01 Unit: Vdc The analog value that PCC3300V2
Output / corresponds to the
Configurable Offset: 0 Lower Limit: -10 high engineering value
Analog Size (bits): 16 Upper Limit: 10 (scaling unit) and
output #1 upper clamp
Analog Out Sign: S
High
Function
Setpoint
41179 Speed Bias Read Only Multiplier: 0.01 Unit: Vdc The analog value that PCC3300V2
Output / corresponds to the
Configurable Offset: 0 Lower Limit: -10 high engineering value
Analog Size (bits): 16 Upper Limit: 10 (scaling unit) and
output #1 upper clamp
Analog Out Sign: S
High Setpoint
41180 Speed Bias Read Only Multiplier: 0.01 Unit: Vdc The analog value that PCC3300V2
Output / corresponds to the
Configurable Offset: 0 Lower Limit: -10 Low engineering value
Analog Size (bits): 16 Upper Limit: 10 (scaling unit) and
output #1 lower clamp
Analog Out Sign: S
Low Function
Setpoint
41181 Speed Bias Read Only Multiplier: 0.01 Unit: Vdc The analog value that PCC3300V2
Output / corresponds to the
Configurable Offset: 0 Lower Limit: -10 Low engineering value
Analog Size (bits): 16 Upper Limit: 10 (scaling unit) and
output #1 lower clamp
Analog Out Sign: S
Low Setpoint

A029X159 (Issue 31) 671 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41182 Speed Bias Read Only 0: Default Pointes to the fucntion PCC3300V2
Output / that controls the
Configurable 1: Do Nothing analog output
Analog 2: Genset
Output #1 Average Voltage
Analog
Output 3: Genset
Function Average Current
Pointer
4: Genset Total
Power Factor
5: Genset
Frequency
6: Genset Total
kW
7: Genset Total
kVAR
8: Engine Speed
9: Coolant
Temperature
10: Oil Pressure
11: Oil
Temperature
12: Intake
Manifold
Temperature
13: Genset %
Application Total
kW
41183 Speed Bias Read Only Multiplier: 1 Unit: The engingeering PCC3300V2
Output / value that corresponds
Configurable Offset: 0 Lower Limit: to the High Analog
Analog -32768 output value (scaling
output #1 Size (bits): 16 Upper Limit: unit)
Engineering 32762
In High
Function Sign: S
Setpoint
41184 Speed Bias Read Only Multiplier: 1 Unit: The engingeering PCC3300V2
Output / value that corresponds
Configurable Offset: 0 Lower Limit: to the High Analog
Analog -32768 output value (scaling
output #1 Size (bits): 16 Upper Limit: unit)
Engineering 32762
In High
Setpoint Sign: S

Copyright © 2023 Cummins Inc. 672 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41185 Speed Bias Read Only Multiplier: 1 Unit: The engineering value PCC3300V2
Output / that corresponds to
Configurable Offset: 0 Lower Limit: the Low Analog output
Analog -32768 value (scaling unit)
output #1 Size (bits): 16 Upper Limit:
Engineering 32762
In Low
Function Sign: S
Setpoint
41186 Speed Bias Read Only Multiplier: 1 Unit: The engineering value PCC3300V2
Output / that corresponds to
Configurable Offset: 0 Lower Limit: the Low Analog output
Analog -32768 value (scaling unit)
output #1 Size (bits): 16 Upper Limit:
Engineering 32762
In Low
Setpoint Sign: S

41187 Maintenance Read Only Multiplier: 0.01 Unit: hours Displays Maintenance PCC3300V2
Due wrt ERT required with respect
Offset: 0 Lower Limit: 0 to Engine Running
Size (bits): 32 Upper Limit: Hours
4294967295
Sign: U
41188 Maintenance Read Only Multiplier: 0.01 Unit: hours Displays Maintenance PCC3300V2
Due wrt ERT required with respect
Offset: 0 Lower Limit: 0 to Engine Running
Size (bits): 32 Upper Limit: Hours
4294967295
Sign: U
41189 ECM HOT Read Only Multiplier: 0.1 Unit: degF "Displays High Engine PCC3300V2
Warning Oil Temperature
Threshold Offset: 0 Lower Limit: Warning Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: S CAN(OTIS)"
41190 ECM HOT Read Only Multiplier: 0.1 Unit: degF "Displays High Engine PCC3300V2
Shutdown Oil Temperature
Threshold Offset: 0 Lower Limit: Shutdown Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: S CAN(OTIS)"
41191 ECM HCP Read Only Multiplier: 0.1 Unit: psi "Displays High PCC3300V2
Warning Crankcase Pressure
Threshold Offset: 0 Lower Limit: Warning Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: S CAN(OTIS)"

A029X159 (Issue 31) 673 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41192 ECM HCP Read Only Multiplier: 0.1 Unit: psi "Displays High PCC3300V2
Shutdown Crankcase Pressure
Threshold Offset: 0 Lower Limit: Shutdown Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: U CAN(OTIS)"
41193 ECM Read Only Multiplier: 1 Unit: rpm "Displays Engine PCC3300V2
Overspeed Overspeed Shutdown
Shutdown Offset: 0 Lower Limit: Threshold received via
Threshold Size (bits): 16 Upper Limit: ECM over
CAN(OTIS)"
Sign: U
41194 ECM LOP Read Only Multiplier: 0.01 Unit: psi "Displays Low Engine PCC3300V2
Warning Oil Pressure Warning
Threshold Offset: 0 Lower Limit: Threshold value for
(1500 rpm) Size (bits): 16 Upper Limit: 1500 rpm received via
ECM over
Sign: S CAN(OTIS)"
41195 ECM LOP Read Only Multiplier: 0.01 Unit: psi "Displays Low Engine PCC3300V2
Warning Oil Pressure Warning
Threshold Offset: 0 Lower Limit: Threshold value for
(1800 rpm) Size (bits): 16 Upper Limit: 1800 rpm received via
ECM over
Sign: S CAN(OTIS)"
41196 ECM LOP Read Only Multiplier: 0.01 Unit: psi "Displays Low Engine PCC3300V2
Shutdown Oil Pressure
Threshold Offset: 0 Lower Limit: Shutdown Threshold
(1500 rpm) Size (bits): 16 Upper Limit: value for 1500 rpm
received via ECM over
Sign: S CAN(OTIS)"
41197 ECM LOP Read Only Multiplier: 0.01 Unit: psi "Displays Low Engine PCC3300V2
Shutdown Oil Pressure
Threshold Offset: 0 Lower Limit: Shutdown Threshold
(1800 rpm) Size (bits): 16 Upper Limit: value for 1800 rpm
received via ECM over
Sign: S CAN(OTIS)"
41198 ECM HCT Read Only Multiplier: 0.1 Unit: degF "Displays High PCC3300V2
Warning Coolant Temperature
Threshold Offset: 0 Lower Limit: Warning Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: S CAN(OTIS)"

Copyright © 2023 Cummins Inc. 674 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41199 ECM HCT Read Only Multiplier: 0.1 Unit: degF "Displays High PCC3300V2
Shutdown/w Coolant Temperature
Cooldown Offset: 0 Lower Limit: Shutdown with
Threshold Size (bits): 16 Upper Limit: Cooldown Threshold
value received via
Sign: S ECM over
CAN(OTIS)"
41200 ECM HCT Read Only Multiplier: 0.1 Unit: degF "Displays High PCC3300V2
Shutdown Coolant Temperature
Threshold Offset: 0 Lower Limit: Shutdown Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: S CAN(OTIS)"
41300 AmpSentry Read Only 0: Inactive "A protection mode PCC3300,
Maintenance that causes the PCC2300,
Mode Status 1: Active alternator to shutdown PCC3300V2
instantly when a short
circuit is detected.
Used to limit arc flash
energy with personnel
working around set."
41303 Fuel System Read/Write 0: Diesel Type of fuel and PCC3300,
ignition system used PCC2300,
1: Gas by genset. PCC3300V2
41304 Gas Fuel Read/Write 0: Natural Gas "Trim to set the type of PCC2300,
Type gaseous fuel." PCC3300,
1: Propane PCC3300V2
2: Dual
41305 Low Fuel Read Only 0: Inactive "Displays PCC2300,
Pressure Inactive/Active status PCC3300,
Switch 1: Active of Switch. Activates if PCC3300V2
Status Low Fuel Pressure
switch remains active
for Fuel Pressure
Fault delay."
41306 Maintenance Read/Write Multiplier: 1 Unit: hours Sets Hours for PCC3300V2
ERT Interval Maintenance
Offset: 0 Lower Limit: 250 Diagnostic
Size (bits): 16 Upper Limit:
5000
Sign: U
41307 Maintenance Read/Write Multiplier: 1 Unit: Sets Real Time Clock PCC3300V2
RTC Date Date for Maintenance
Interval Offset: 0 Lower Limit: 1 Diagnostic
Size (bits): 8 Upper Limit: 31
Sign: U

A029X159 (Issue 31) 675 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41308 Maintenance Read/Write Multiplier: 1 Unit: Sets Real Time Clock PCC3300V2
RTC Month Month for
Interval Offset: 0 Lower Limit: 1 Maintenance
Size (bits): 8 Upper Limit: 12 Diagnostic

Sign: U
41309 Maintenance Read/Write Multiplier: 1 Unit: Sets Real Time Clock PCC3300V2
RTC Year Year for Maintenance
Interval Offset: 0 Lower Limit: 0 Diagnostic
Size (bits): 8 Upper Limit: 99
Sign: U
42000 Load Read Only 0: Off Indicates the status of PCC3300,
Demand Load Demand PCC3300V2
State 1: Halted operation.
2: Initial Delay
3: Load Monitor
42001 Load Read Only Multiplier: 1 Unit: kW Indicates the total load PCC3300,
Demand of System Network PCC3300V2
Genset Bus Offset: 0 Lower Limit: 0 connected gensets
Total kW Size (bits): 32 Upper Limit:
80000
Sign: U
42002 Load Read Only Multiplier: 1 Unit: kW Indicates the total load PCC3300,
Demand of System Network PCC3300V2
Genset Bus Offset: 0 Lower Limit: 0 connected gensets
Total kW Size (bits): 32 Upper Limit:
80000
Sign: U
42003 Load Read Only Multiplier: 1 Unit: kW Indicates the amount PCC3300,
Demand of unused online kW PCC3300V2
Surplus Offset: 0 Lower Limit: 0 bus capacity (spinning
Capacity Size (bits): 32 Upper Limit: reserve).
80000
Sign: U
42004 Load Read Only Multiplier: 1 Unit: kW Indicates the amount PCC3300,
Demand of unused online kW PCC3300V2
Surplus Offset: 0 Lower Limit: 0 bus capacity (spinning
Capacity Size (bits): 32 Upper Limit: reserve).
80000
Sign: U

Copyright © 2023 Cummins Inc. 676 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42005 Load Read Only Multiplier: 1 Unit: kW Indicates the total PCC3300,
Demand amount of online kW PCC3300V2
Online Offset: 0 Lower Limit: 0 bus capacity for load
Capacity Size (bits): 32 Upper Limit: demand. Only gensets
80000 which are eligible for
load demand count.
Sign: U
42006 Load Read Only Multiplier: 1 Unit: kW Indicates the total PCC3300,
Demand amount of online kW PCC3300V2
Online Offset: 0 Lower Limit: 0 bus capacity for load
Capacity Size (bits): 32 Upper Limit: demand. Only gensets
80000 which are eligible for
load demand count.
Sign: U

TABLE 39.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42007 Load Read Only Multiplier: 1 Unit: seconds Indicates the time PCC3300,
Demand remaining before PCC3300V2
Initial Delay Offset: 0 Lower Limit: 0 generator sets are
Timer Size (bits): 16 Upper Limit: allowed to stop after
1500 initial start or after
resuming halted load
Sign: U demand. This timer is
set by Load Demand
Initial Delay.
42008 Load Read Only Multiplier: 1 Unit: seconds Indicates the time PCC3300,
Demand remaining before next PCC3300V2
Start Delay Offset: 0 Lower Limit: 0 generator set is
Timer Size (bits): 16 Upper Limit: allowed to start. This
1500 timer is set by Load
Demand Start Delay.
Sign: U
42009 Load Read Only Multiplier: 1 Unit: seconds Indicates the time PCC3300,
Demand remaining before next PCC3300V2
Stop Delay Offset: 0 Lower Limit: 0 generator set is
Timer Size (bits): 16 Upper Limit: allowed to stop. This
1500 timer is set by Load
Demand Stop Delay.
Sign: U
42010 Load Read Only 0: No Indicates when the PCC3300,
Demand current load and spare PCC3300V2
Spare 1: Yes capacity requirements
Capacity are satisfied.
Available

A029X159 (Issue 31) 677 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42011 Load Read Only Multiplier: 1 Unit: kW Indicates the total kW PCC3300,
Demand value of all currently PCC3300V2
Total Spare Offset: 0 Lower Limit: 0 active spare capacity
Capacity Size (bits): 32 Upper Limit: requests in the
Requested 80000 system.

Sign: U
42012 Load Read Only Multiplier: 1 Unit: kW Indicates the total kW PCC3300,
Demand value of all currently PCC3300V2
Total Spare Offset: 0 Lower Limit: 0 active spare capacity
Capacity Size (bits): 32 Upper Limit: requests in the
Requested 80000 system.

Sign: U
42013 Load Read Only Multiplier: 1 Unit: kW The kW load at which PCC3300,
Demand the next generator set PCC3300V2
Next Start Offset: 0 Lower Limit: 0 will be started.
Threshold Size (bits): 32 Upper Limit:
(kW) 80000
Sign: U
42014 Load Read Only Multiplier: 1 Unit: kW The kW load at which PCC3300,
Demand the next generator set PCC3300V2
Next Start Offset: 0 Lower Limit: 0 will be started.
Threshold Size (bits): 32 Upper Limit:
(kW) 80000
Sign: U
42015 Load Read Only Multiplier: 1 Unit: kW The kW load at which PCC3300,
Demand the next generator set PCC3300V2
Next Stop Offset: 0 Lower Limit: 0 will be stopped.
Threshold Size (bits): 32 Upper Limit:
(kW) 80000
Sign: U
42016 Load Read Only Multiplier: 1 Unit: kW The kW load at which PCC3300,
Demand the next generator set PCC3300V2
Next Stop Offset: 0 Lower Limit: 0 will be stopped.
Threshold Size (bits): 32 Upper Limit:
(kW) 80000
Sign: U

Copyright © 2023 Cummins Inc. 678 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42017 Load Read Only 0: Gen1 Indicates the next PCC3300,
Demand generator set to start PCC3300V2
Next Gen to 1: Gen2 by ID.
Start 2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
42018 Load Read Only 0: Gen1 Indicates the next PCC3300,
Demand generator set to stop PCC3300V2
Next Gen to 1: Gen2 by ID.
Stop 2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16

A029X159 (Issue 31) 679 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42019 Load Read Only 0: Inactive Indicates the status of PCC3300,
Demand the Load Demand PCC3300V2
Inhibit Local 1: Active Inhibit input. When
ACTIVE all the
generator sets will
start.
42020 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42021 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42022 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42023 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42024 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42025 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42026 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C

Copyright © 2023 Cummins Inc. 680 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42027 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42028 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42029 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
43000 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L1 PCC2300,
L1 Current Offset: 0 Lower Limit: current percentage PCC3300V2
Size (bits): 16 Upper Limit: output.

Sign: U
43001 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L2 PCC2300,
L2 Current Offset: 0 Lower Limit: current percentage PCC3300V2
Size (bits): 16 Upper Limit: output.

Sign: U
43002 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L1 KVA PCC2300,
L1 kVA Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43003 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L3 PCC2300,
L3 Current Offset: 0 Lower Limit: current percentage PCC3300V2
Size (bits): 16 Upper Limit: output.

Sign: U
43004 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L2 KVA PCC2300,
L2 kVA Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U

A029X159 (Issue 31) 681 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43005 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L3 KVA PCC2300,
L3 kVA Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43006 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L1 KW PCC2300,
L1 kW Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
43007 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L2 KW PCC2300,
L2 kW Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
43008 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L3 KW PCC2300,
L3 kW Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
43009 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the total PCC3300,
Application generator set PCC2300,
Total kVA Offset: 0 Lower Limit: application KVA PCC3300V2
Size (bits): 16 Upper Limit: percentage output.

Sign: U
43010 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the total PCC3300,
Application generator set PCC2300,
Total kW Offset: 0 Lower Limit: application KW PCC3300V2
Size (bits): 16 Upper Limit: percentage output.

Sign: S
43017 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the total PCC3300,
Standby generator set standby PCC2300,
Total kVA Offset: 0 Lower Limit: KVA percentage PCC3300V2
Size (bits): 16 Upper Limit: output.

Sign: U
43018 Genset Read Only Multiplier: 0.1 Unit: kVA The generator set PCC3300,
Application KVA rating. PCC2300,
kVA rating Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 682 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43019 Genset Read Only Multiplier: 0.1 Unit: kW The generator set KW PCC3300,
Application rating. PCC2300,
kW rating Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43020 Genset Read Only Multiplier: 1 Unit: Amps The value of the PCC3300,
Application generator set PCC2300,
Nominal Offset: 0 Lower Limit: application nominal PCC3300V2
Current Size (bits): 16 Upper Limit: current. Displayed as
"Genset Application
Sign: U Rated Current" in HMI
43021 Genset Read Only Multiplier: 0.01 Unit: % Generator set average PCC3300,
Average voltage percentage. PCC2300,
Voltage% Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43030 Genset L1 Read Only Multiplier: 0.01 Unit: PF Generator set L1 PCC3300,
Power Factor power factor PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 8 Upper Limit:
Sign: S
43031 Genset L1L2 Read Only Multiplier: 0.01 Unit: Degrees Generator set L1L2 PCC3300,
Phase voltage phase angle PCC2300,
Difference Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43032 Genset L1L2 Read Only Multiplier: 0.01 Unit: % Generator set L1L2 PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43033 Genset L1N Read Only Multiplier: 0.01 Unit: % Generator set L1N PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43044 Genset L2 Read Only Multiplier: 0.01 Unit: PF Generator set L2 PCC3300,
Power Factor power factor PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-1.28
Size (bits): 8 Upper Limit: 1.27
Sign: S

A029X159 (Issue 31) 683 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43045 Genset L2L3 Read Only Multiplier: 0.01 Unit: Degrees Generator set L2L3 PCC3300,
Phase voltage phase angle PCC2300,
Difference Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
655.3
Sign: U
43046 Genset L2L3 Read Only Multiplier: 0.01 Unit: % Generator set L2L3 PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43047 Genset L2N Read Only Multiplier: 0.01 Unit: % Generator set L2N PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
655.3
Sign: U
43058 Genset L3 Read Only Multiplier: 0.01 Unit: PF Generator set L3 PCC3300,
Power Factor power factor PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-1.28
Size (bits): 8 Upper Limit: 1.22
Sign: S
43059 Genset L3L1 Read Only Multiplier: 0.01 Unit: Degrees Generator set L3L1 PCC3300,
Phase voltage phase angle PCC2300,
Difference Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
655.3
Sign: U
43060 Genset L3L1 Read Only Multiplier: 0.01 Unit: % Generator set L3L1 PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
655.3
Sign: U
43061 Genset L3N Read Only Multiplier: 0.01 Unit: % Generator set L3N PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 684 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43062 Genset Read Only Multiplier: 0.1 Unit: kVA KVA rating for the PCC3300,
Standby kVA generator set in PCC2300,
rating Offset: 0 Lower Limit: Standby configuration. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43063 Genset Read Only Multiplier: 0.1 Unit: kW KW rating for the PCC3300,
Standby kW generator set in PCC2300,
rating Offset: 0 Lower Limit: Standby configuration. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43064 Genset Read Only Multiplier: 1 Unit: Amps The value of the PCC3300,
Standby generator set standby PCC2300,
Nominal Offset: 0 Lower Limit: nominal current. PCC3300V2
Current Size (bits): 16 Upper Limit: Displayed as "Genset
Standby Rated
Sign: U Current" in HMI
43065 Genset Total Read Only Multiplier: 1 Unit: kVAh Generator set total PCC3300,
kVAh kVAh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
43066 Genset Total Read Only Multiplier: 1 Unit: kVAh Generator set total PCC3300,
kVAh kVAh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
43067 Genset Total Read Only Multiplier: 0.01 Unit: % Total KVAR's per PCC3300,
kVARs per Standby KVA. PCC2300,
Standby kVA Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
43111 Genset Bus Read Only Multiplier: 0.01 Unit: PF Generator set Bus L1 PCC3300,
L1 Power power factor PCC3300V2
Factor Offset: 0 Lower Limit:
-1.28
Size (bits): 8 Upper Limit: 1.22
Sign: S
43112 Genset Bus Read Only Multiplier: 0.01 Unit: Degrees Generator set bus PCC3300,
L1L2 Phase L1L2 voltage phase PCC3300V2
Difference Offset: 0 Lower Limit: angle
Size (bits): 16 Upper Limit:
Sign: U

A029X159 (Issue 31) 685 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43125 Genset Bus Read Only Multiplier: 0.01 Unit: PF Generator set Bus L2 PCC3300,
L2 Power power factor PCC3300V2
Factor Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
43126 Genset Bus Read Only Multiplier: 0.01 Unit: Degrees Generator set bus PCC3300,
L2L3 Phase L2L3 voltage phase PCC3300V2
Difference Offset: 0 Lower Limit: angle
Size (bits): 16 Upper Limit:
Sign: U
43139 Genset Bus Read Only Multiplier: 0.01 Unit: PF Generator set Bus L3 PCC3300,
L3 Power power factor PCC3300V2
Factor Offset: 0 Lower Limit:
-1.28
Size (bits): 8 Upper Limit: 1.22
Sign: S
43140 Genset Bus Read Only Multiplier: 0.01 Unit: Degrees Generator set bus PCC3300,
L3L1 Phase L3L1 voltage phase PCC3300V2
Difference Offset: 0 Lower Limit: angle
Size (bits): 16 Upper Limit:
Sign: U
43143 Genset Bus Read Only Multiplier: 1 Unit: kVAh Generator set bus PCC3300,
Total kVAh total kVAh PCC3300V2
Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
43144 Genset Bus Read Only Multiplier: 1 Unit: kVAh Generator set bus PCC3300,
Total kVAh total kVAh PCC3300V2
Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
43146 Paralleling Read/Write 0: None Determines what the PCC3300,
Application function of the Other PCC3300V2
1: Utility Meter is.
2: Genset Bus
43162 Utility L1 Read Only Multiplier: 0.01 Unit: PF Utility L1 power factor PCC3300,
Power Factor PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S

Copyright © 2023 Cummins Inc. 686 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43163 Utility L1L2 Read Only Multiplier: 0.01 Unit: Degrees Utility L1L2 voltage PCC3300,
Phase phase angle PCC3300V2
Difference Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
43176 Utility L2 Read Only Multiplier: 0.01 Unit: PF Utility L2 power factor PCC3300,
Power Factor PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
43177 Utility L2L3 Read Only Multiplier: 0.01 Unit: Degrees Utility L2L3 voltage PCC3300,
Phase phase angle PCC3300V2
Difference Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
43190 Utility L3 Read Only Multiplier: 0.01 Unit: PF Utility L3 power factor PCC3300,
Power Factor PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
43191 Utility L3L1 Read Only Multiplier: 0.01 Unit: Degrees Utility L3L1 voltage PCC3300,
Phase phase angle PCC3300V2
Difference Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
43194 Utility Total Read Only Multiplier: 1 Unit: kVAh Utility total kVAh PCC3300,
kVAh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
43195 Utility Total Read Only Multiplier: 1 Unit: kVAh Utility total kVAh PCC3300,
kVAh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
43196 Exhaust Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Stack Exhaust Stack PCC3300V2
Temperature Offset: 0 Lower Limit: -459 Temperature Right
Right Bank Size (bits): 16 Upper Limit: Bank received from
3155 ECM

Sign: S

A029X159 (Issue 31) 687 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43197 Exhaust Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Stack Exhaust Stack PCC3300V2
Temperature Offset: 0 Lower Limit: -459 Temperature Left
Left Bank Size (bits): 16 Upper Limit: Bank received from
3155 ECM

Sign: S
43200 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43201 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43202 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43203 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.

Copyright © 2023 Cummins Inc. 688 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43204 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43205 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43206 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43207 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43208 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.

A029X159 (Issue 31) 689 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43209 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43210 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43211 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43212 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43213 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.

Copyright © 2023 Cummins Inc. 690 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43214 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43215 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43216 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43217 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43218 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.

A029X159 (Issue 31) 691 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43219 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43220 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43221 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43222 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.

Copyright © 2023 Cummins Inc. 692 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43223 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43224 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43225 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43226 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.

A029X159 (Issue 31) 693 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43227 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43228 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43229 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43230 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.

Copyright © 2023 Cummins Inc. 694 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43231 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43232 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43233 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43234 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.

A029X159 (Issue 31) 695 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43235 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43236 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43237 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43238 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.

Copyright © 2023 Cummins Inc. 696 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43239 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43240 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43241 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43242 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43243 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43244 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.

A029X159 (Issue 31) 697 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43245 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43246 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43247 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43248 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43249 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43250 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43251 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.

Copyright © 2023 Cummins Inc. 698 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43252 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43253 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43254 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43255 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43256 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43257 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43258 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.

A029X159 (Issue 31) 699 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43259 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set' s PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43260 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43261 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43262 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43263 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43264 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.

Copyright © 2023 Cummins Inc. 700 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43265 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43266 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43267 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43268 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.

TABLE 40.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43269 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.

A029X159 (Issue 31) 701 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43270 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43271 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43272 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43273 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43274 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43275 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.

Copyright © 2023 Cummins Inc. 702 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43276 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43277 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43278 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43279 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43280 Coolant Read Only 0: Inactive Coolant Level input PCC3300,
Level Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
43281 Coolant Read Only 0: Inactive This is the status of PCC3300,
Level/Config the Configurable Input PCC2300,
urable Input 1: Active #5. PCC3300V2
#5 Switch
43283 Fault Reset Read Only 0: Inactive Fault Reset input PCC3300,
Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
43284 Fault Read Only 0: Inactive This is the status of PCC3300,
Reset/Config the Configurable Input PCC2300,
urable Input 1: Active #10. PCC3300V2
#10 Switch

A029X159 (Issue 31) 703 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43285 Genset CB Read Only 0: Inactive This is the status of PCC3300,
Inhibit/Config the Configurable Input PCC3300V2
urable Input 1: Active #28.
#28 Switch
43286 Genset CB Read Only 0: Inactive This is the status of PCC3300,
Pos the Configurable Input PCC3300V2
B/Configurab 1: Active #26.
le Input #26
Switch
43287 Genset CB Read Only 0: Inactive This is the status of PCC3300,
Tripped/Confi the Configurable Input PCC3300V2
gurable Input 1: Active #27.
#27 Switch
43289 Genset CB Read Only 0: Inactive Generator set CB Pos PCC3300,
Pos A Switch A input software state PCC3300V2
1: Active status. Gives software
Inactive/Active state
43290 Genset CB Read Only 0: Inactive Generator set CB Pos PCC3300,
Pos B Switch B input software state PCC3300V2
1: Active status. Gives software
Inactive/Active state
43292 Ground Fault Read Only 0: Inactive Ground Fault Switch PCC3300,
Switch function output status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
43293 High Alt Read Only 0: Inactive High Alt Temp Switch PCC3300,
Temp Switch function output status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
43295 Load Read Only 0: Inactive This is the status of PCC3300,
Demand the Configurable Input PCC3300V2
Stop/Configu 1: Active #31.
rable Input
#31 Switch
43296 Local E-stop Read Only 0: Inactive Monitors the E-Stop PCC3300,
Switch switch. PCC2300,
1: Active PCC3300V2
43297 Low Coolant Read Only 0: Inactive Low Coolant #2 PCC3300,
#2 Switch Switch function output PCC2300,
1: Active status. Gives software PCC3300V2
Inactive/Active state
43298 Low Engine Read Only 0: Inactive Low Engine PCC3300,
Temperature Temperarure Switch PCC2300,
Switch 1: Active function output status. PCC3300V2
Gives software
Inactive/Active state

Copyright © 2023 Cummins Inc. 704 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43299 Low Fuel In Read Only 0: Inactive Low Fuel In Day Tank PCC3300,
Day Tank Switch function output PCC2300,
Switch 1: Active status. Gives software PCC3300V2
Inactive/Active state
43300 Genset Bus Read/Write 0: Delta Delta or Wye for Utility PCC3300,
Delta/Wye connection PCC3300V2
Connection 1: Wye

43301 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
Nominal nominal voltage PCC3300V2
Voltage Offset: 0 Lower Limit: 110
Size (bits): 16 Upper Limit:
45000
Sign: U
43302 Genset Read Only 0: Delta Delta or Wye for PCC3300,
Delta/Wye Generator set PCC2300,
Connection 1: Wye connection PCC3300V2
43303 Genset Read Only Multiplier: 1 Unit: Vac Generator set nominal PCC3300,
Nominal line-line voltage PCC2300,
Voltage Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 16 Upper Limit:
45000
Sign: U
43304 Single/3 Read Only 0: Single Phase Setup mode PCC3300,
Phase interlocked. Generator PCC2300,
Connection 1: Three Phase set's single phase/3 PCC3300V2
phase metering setup
configuration.
43306 Utility Read/Write 0: Delta Delta or Wye for Utility PCC3300,
Delta/Wye connection PCC3300V2
Connection 1: Wye

43307 Utility Read Only Multiplier: 1 Unit: Vac Utility nominal voltage PCC3300,
Nominal PCC3300V2
Voltage Offset: 0 Lower Limit: 110
Size (bits): 16 Upper Limit:
45000
Sign: U
43309 Overfrequen Read/Write 0: Disabled Enables PCC3300,
cy Enable overfrequency PCC2300,
1: Enabled diagnostic witness PCC3300V2
test.

A029X159 (Issue 31) 705 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43310 Overload Read/Write Multiplier: 1 Unit: seconds The time delay until an PCC3300,
Warning Set overload condition is PCC2300,
Time Offset: 0 Lower Limit: 1 reported as a fault PCC3300V2
Size (bits): 8 Upper Limit: 120
Sign: U
43311 Overload Read/Write Multiplier: 0.01 Unit: % Sets the Overload PCC3300,
Warning Warning fault trip PCC2300,
Threshold Offset: 0 Lower Limit: 70 threshold as PCC3300V2
Size (bits): 16 Upper Limit: 140 percentage of
generator set
Sign: U application kW rating.
43312 Overload Read/Write Multiplier: 1 Unit: seconds The time delay until an PCC3300,
Shutdown overload condition is PCC2300,
Set Time Offset: 0 Lower Limit: 1 reported as Shutdown PCC3300V2
Size (bits): 8 Upper Limit: 120 fault
Sign: U
43313 Overload Read/Write Multiplier: 0.01 Unit: % "Sets the Overload PCC3300,
Shutdown Shutdown fault trip PCC2300,
threshold Offset: 0 Lower Limit: 70 threshold as PCC3300V2
Size (bits): 16 Upper Limit: percentage of
655.35 generator set
application kW rating
Sign: U in the range of 70 to
140%. To disable the
Overload shutdown
fault set the value to
655.35 or Not
Available."
43314 Prelube Read/Write 0: GCS Selects whether PCC3300,
Function prelube function is PCC3300V2
Owner 1: ECS being controlled by
GCS or ECS
43338 CAN Failure Read/Write Multiplier: 1 Unit: Sets the maximum PCC3300,
Retries number of CAN PCC2300,
Offset: 0 Lower Limit: 0 communication retries PCC3300V2
Size (bits): 8 Upper Limit: 10
Sign: U
43339 Auto Sleep Read/Write 0: Awake in Auto Trim that determines if PCC3300,
Enable the control will Stay PCC2300,
1: Sleep in Auto Awake in Auto mode PCC3300V2
or Fall asleep in Auto
mode.

Copyright © 2023 Cummins Inc. 706 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43340 Max Setup Read/Write Multiplier: 1 Unit: Seconds Max time allowed in PCC3300,
Mode Time Setup Mode. PCC2300,
Offset: 0 Lower Limit: 30 PCC3300V2
Size (bits): 16 Upper Limit:
3600
Sign: U
43341 Power Down Read/Write 0: Disable Trim to enable sleep PCC3300,
Mode Enable mode PCC2300,
1: Enable PCC3300V2
43342 Power Down Read/Write Multiplier: 1 Unit: seconds Timer setting for the PCC3300,
Mode Time Power Down delay PCC2300,
Delay Offset: 0 Lower Limit: 0 feature PCC3300V2
Size (bits): 16 Upper Limit: 600
Sign: U
43343 Setup Mode Read/Write 0: Disable Voltatile to allow entry PCC3300,
Enable into Setup Mode PCC2300,
1: Enable PCC3300V2
43344 Clock Date Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
current date. PCC2300,
Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 8 Upper Limit: 31
Sign: U
43345 Clock Hour Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
current hour. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 23
Sign: U
43346 Clock Minute Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
current minute. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 59
Sign: U
43347 Clock Mode Read/Write 0: Normal Use to set the real PCC3300,
time clock and save PCC2300,
1: Set Clock settings. PCC3300V2
2: Save Clock
43348 Clock Month Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
current month. PCC2300,
Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 8 Upper Limit: 12
Sign: U

A029X159 (Issue 31) 707 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43349 Clock Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
Second current second. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 59
Sign: U
43350 Clock Year Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
current year. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 99
Sign: U
43351 Daylight Read/Write Multiplier: 1 Unit: Use to set the hour of PCC3300,
Savings End the day when daylight PCC2300,
Hour Offset: 0 Lower Limit: 2 savings time ends. PCC3300V2
Size (bits): 8 Upper Limit: 19
Sign: U
43352 Daylight Read/Write Multiplier: 1 Unit: Use to set the month PCC3300,
Savings End when daylight savings PCC2300,
Month Offset: 0 Lower Limit: 1 time ends. PCC3300V2
Size (bits): 8 Upper Limit: 12
Sign: U
43353 Daylight Read/Write 0: First Use to set the week of PCC3300,
Savings End Occurrence the month when PCC2300,
Week daylight savings time PCC3300V2
Occurrence 1: Second ends.
in Month Occurrence
2: Third
Occurrence
3: Fourth
Occurrence
4: Last
Occurrence
43354 Daylight Read/Write 0: Sunday Use to set the day of PCC3300,
Savings Start the week when PCC2300,
Day 1: Monday daylight savings time PCC3300V2
2: Tuesday starts.

3: Wednesday
4: Thursday
5: Friday
6: Saturday

Copyright © 2023 Cummins Inc. 708 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43355 Daylight Read/Write Multiplier: 1 Unit: Use to set the hour of PCC3300,
Savings Start the day when daylight PCC2300,
Hour Offset: 0 Lower Limit: 2 savings time starts. PCC3300V2
Size (bits): 8 Upper Limit: 19
Sign: U
43356 Daylight Read/Write Multiplier: 1 Unit: Use to set the month PCC3300,
Savings Start when daylight savings PCC2300,
Month Offset: 0 Lower Limit: 1 time starts. PCC3300V2
Size (bits): 8 Upper Limit: 12
Sign: U
43357 Daylight Read/Write 0: First Use to set the week of PCC3300,
Savings Start Occurrence the month when PCC2300,
Week daylight savings time PCC3300V2
Occurrence 1: Second starts.
in Month Occurrence
2: Third
Occurrence
3: Fourth
Occurrence
4: Last
Occurrence
43358 Daylight Read/Write Multiplier: 1 Unit: Minutes Use to set the amount PCC3300,
Savings of daylight savings PCC2300,
Time Offset: 0 Lower Limit: 0 time adjustment PCC3300V2
Adjustment Size (bits): 8 Upper Limit: 120 applied.
Sign: U
43359 Daylight Read/Write 0: Disabled Use to enable the PCC3300,
Savings daylight savings time PCC2300,
Time Enable 1: Enabled feature. PCC3300V2
43360 Exercise Read/Write 0: Disabled Enables the exercise PCC3300,
Scheduler scheduler. PCC2300,
Enable 1: Enabled PCC3300V2
43361 Reset Fuel Read/Write 0: Inactive The reset trip fuel PCC3300,
Consumption consumption PCC2300,
1: Active command. PCC3300V2
43362 Reset Runs Read/Write 0: Inactive The reset runs PCC3300,
command. PCC2300,
1: Active PCC3300V2
43363 Reset Start Read/Write 0: Inactive The reset start PCC3300,
Attempts attempts command. PCC2300,
1: Active PCC3300V2

A029X159 (Issue 31) 709 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43364 Scheduler Read/Write Multiplier: 1 Unit: Used to select an PCC3300,
Exception exception to adjust. PCC2300,
Select Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 8 Upper Limit: 6
Sign: U
43369 Scheduler Read/Write 0: Disable Used to enable or PCC3300,
Exception x disable the selected PCC2300,
Enable 1: Enable exception. PCC3300V2
43374 Scheduler Read/Write Multiplier: 1 Unit: Used to select a PCC3300,
Program program to adjust. PCC2300,
Select Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 8 Upper Limit: 12
Sign: U
43377 Scheduler Read/Write 0: Disable Used to enable or PCC3300,
Program x disable the selected PCC2300,
Enable 1: Enable program. PCC3300V2
43379 Scheduler Read/Write 0: No Load Used to adjust the run PCC3300,
Program x mode for the selected PCC3300V2
Run Mode 1: With Load program.
2: Extended
Parallel
43383 Daylight Read/Write 0: Sunday Use to set the day of PCC3300,
Savings End the week when PCC2300,
Day 1: Monday daylight savings time PCC3300V2
2: Tuesday ends.

3: Wednesday
4: Thursday
5: Friday
6: Saturday
43502 Idle Rated Read Only 0: Idle The output command PCC3300,
Command of the Idle/Rated Logic PCC2300,
1: Rated PCC3300V2
43507 Load Dump Read Only 0: Inactive Monitors the state of PCC3300,
Overload the load dump PCC2300,
Condition 1: Active overload detection PCC3300V2
2: Reserved algorithm

3: Not Available

Copyright © 2023 Cummins Inc. 710 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43508 Load Dump Read Only 0: Inactive The state of the load PCC3300,
Underfreque dump underfrequency PCC2300,
ncy 1: Active detection algorithm PCC3300V2
Condition 2: Reserved
3: Not Available
43509 Low Battery Read Only Multiplier: 0.1 Unit: Vdc The low battery PCC3300,
Voltage voltage threshold PCC2300,
Running Offset: 0 Lower Limit: when the generator PCC3300V2
Threshold Size (bits): 16 Upper Limit: set is in rated mode

Sign: U
43510 Low Battery Read Only Multiplier: 0.1 Unit: Vdc The low battery PCC3300,
Voltage voltage threshold PCC2300,
Stopped Offset: 0 Lower Limit: when the generator PCC3300V2
Threshold Size (bits): 16 Upper Limit: set is not in rated
mode
Sign: U
43511 Low Battery Read Only Multiplier: 0.1 Unit: Vdc The selection of the PCC3300,
Voltage running or stopped PCC2300,
Threshold Offset: 0 Lower Limit: threshold PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43516 Prelube Read Only 0: Crank After Set to a required PCC3300,
Mode Prelube mode based on the PCC2300,
type of starting PCC3300V2
1: Crank With requirement
Prelube
2: Prelube Only
43517 Prelube Read Only 0: Complete The monitor point for PCC3300,
State the prelube state. PCC2300,
1: Armed PCC3300V2
2: Prelube
Output ON
3: Prelube
Output OFF
4: Enable Crank
43524 Remote Start Read Only 0: Stop The output of the PCC3300,
Command Remote Start PCC2300,
1: Start Command OR logic PCC3300V2
43530 Speed and Read Only 0: Inactive Monitor point for the PCC3300,
Voltage Bias command which PCC3300V2
Relay 1: Active closes the on-board
Command relay enabling the
voltage and speed
bias outputs.

A029X159 (Issue 31) 711 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43533 Start Read Only Multiplier: 1 Unit: seconds Time remaining until PCC3300,
Countdown start is initiated PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit: 300
Sign: U
43538 Starter Read Only 0: Inactive State of hardware PCC3300,
Command output. PCC2300,
1: Active PCC3300V2
2: Reserved
3: Not Available
43539 Stop Read Only Multiplier: 1 Unit: seconds Time remaining until PCC3300,
Countdown generator set stops PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
5000
Sign: U
43543 Time At No Read Only Multiplier: 1 Unit: seconds Amount of time the PCC3300,
Load generator set has run PCC2300,
Offset: 0 Lower Limit: 0 at no load PCC3300V2
Size (bits): 16 Upper Limit: 600
Sign: U
43544 Time at Read Only Multiplier: 1 Unit: seconds Amount of time spend PCC3300,
Rated in Rated Cooldown PCC2300,
Cooldown Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
5000
Sign: U
43547 Voltage Read Only Multiplier: 0.01 Unit: % The voltage setpoint PCC3300,
Setpoint command PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit: 150
Sign: U
43550 Weak Battery Read Only Multiplier: 0.1 Unit: Vdc Monitor point for the PCC3300,
Threshold weak battery voltage PCC2300,
Offset: 0 Lower Limit: 6 threshold PCC3300V2
Size (bits): 16 Upper Limit: 16
Sign: U
43551 Weak Battery Read/Write Multiplier: 1 Unit: seconds The time delay until a PCC3300,
Voltage Set weak battery condition PCC2300,
Time Offset: 0 Lower Limit: 1 is reported as a fault PCC3300V2
Size (bits): 16 Upper Limit: 5
Sign: U

Copyright © 2023 Cummins Inc. 712 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43553 Synchronizer Read Only 0: Synchronizer Indicates whether PCC3300,
Status Off synchronizer is on or PCC3300V2
off
1: Synchronizer
On
43554 Active Read Only Multiplier: 0.1 Unit: seconds Countdown value of PCC3300,
Transition the active transition PCC3300V2
Timer Offset: 0 Lower Limit: timer
Size (bits): 16 Upper Limit:
Sign: U
43555 Active Read Only 0: None Indicates the active PCC3300,
Transition transition type for PTC PCC3300V2
Type 1: Programmed
Transition
2: Transfer
3: Retransfer
4: Max Parallel
43558 ES State Read Only 0: Standby Internal paralleling PCC3300,
status variable PCC3300V2
1: Dead Bus
2: Synchronize
3: Load Share
4: Load Govern
43560 Genset CB Read Only 0: Inactive Generator set cb close PCC3300,
Close command status PCC3300V2
Command 1: Active

43562 Genset CB Read Only 0: Open Indicates generator set PCC3300,


Position breaker position PCC3300V2
Status 1: Closed
2: Not Available
43563 Genset Read Only 0: Not Available Indicates status of the PCC3300,
Availability generator set source PCC3300V2
Status 1: Available
2: Unknown
43564 Bus Status Read Only 0: Unavailable Indicates status of the PCC3300,
bus PCC3300V2
1: Dead
2: Live
43565 Genset CB Read Only 0: Inactive Generator set cb PCC3300,
Inhibit inhibit command PCC3300V2
Command 1: Active

A029X159 (Issue 31) 713 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43566 Genset CB Read Only 0: Inactive Generator set cb PCC3300,
Tripped tripped command PCC3300V2
Command 1: Active

43568 Genset Read Only Multiplier: 0.1 Unit: Hz Indicates the lower PCC3300,
Frequency drop-out threshold in PCC3300V2
Lower Drop- Offset: 0 Lower Limit: Hz for generator set
Out Size (bits): 16 Upper Limit: frequency sensor
Threshold
Sign: U
43569 Genset Read Only Multiplier: 0.1 Unit: Hz Indicates the lower PCC3300,
Frequency pick-up threshold in PCC3300V2
Lower Pick- Offset: 0 Lower Limit: Hz for generator set
Up Threshold Size (bits): 16 Upper Limit: frequency sensor

Sign: U
43570 Genset Read Only 0: Unknown Indicates generator set PCC3300,
Frequency frequency sensor PCC3300V2
Sensor 1: Picked Up status
Status 2: Dropped Out
43571 Genset Read Only Multiplier: 0.1 Unit: Hz Indicates the upper PCC3300,
Frequency drop-out threshold in PCC3300V2
Upper Drop- Offset: 0 Lower Limit: Hz for generator set
Out Size (bits): 16 Upper Limit: frequency sensor
Threshold
Sign: U
43572 Genset Read Only Multiplier: 0.1 Unit: Hz Indicates the upper PCC3300,
Frequency pick-up threshold in PCC3300V2
Upper Pick- Offset: 0 Lower Limit: Hz for generator set
Up Threshold Size (bits): 16 Upper Limit: frequency sensor

Sign: U
43573 Genset Loss Read Only 0: Unknown Indicates generator set PCC3300,
of Phase loss of phase sensor PCC3300V2
Sensor 1: Picked Up status
Status 2: Dropped Out
43574 Genset Read Only Multiplier: 1 Unit: Vac Indicates the drop-out PCC3300,
Overvoltage threshold in volts for PCC3300V2
Drop-Out Offset: 0 Lower Limit: generator set
Threshold Size (bits): 16 Upper Limit: overvoltage sensor

Sign: U
43575 Genset Read Only Multiplier: 1 Unit: Vac Indicates the pick-up PCC3300,
Overvoltage threshold in volts for PCC3300V2
Pick-Up Offset: 0 Lower Limit: generator set
Threshold Size (bits): 16 Upper Limit: overvoltage sensor

Sign: U

Copyright © 2023 Cummins Inc. 714 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43576 Genset Read Only 0: Unknown Indicates generator set PCC3300,
Overvoltage overvoltage sensor PCC3300V2
Sensor 1: Picked Up status
Status 2: Dropped Out
43577 Genset Read Only 0: Unknown Indicates generator set PCC3300,
Phase phase rotation sensor PCC3300V2
Rotation 1: Picked Up status
Sensor 2: Dropped Out
Status
43578 Genset Read Only Multiplier: 1 Unit: Vac Indicates the drop-out PCC3300,
Undervoltage threshold in volts for PCC3300V2
Drop-Out Offset: 0 Lower Limit: generator set
Threshold Size (bits): 16 Upper Limit: undervoltage sensor

Sign: U
43579 Genset Read Only Multiplier: 1 Unit: Vac Indicates the pick-up PCC3300,
Undervoltage threshold in volts for PCC3300V2
Pick-Up Offset: 0 Lower Limit: generator set
Threshold Size (bits): 16 Upper Limit: undervoltage sensor

Sign: U
43580 Genset Read Only 0: Unknown Indicates generator set PCC3300,
Undervoltage undervoltage sensor PCC3300V2
Sensor 1: Picked Up status
Status 2: Dropped Out
43584 Paralleling Read Only 0: Isochronous Indicates which speed PCC3300,
Speed control algorithm is in PCC2300,
Control Mode 1: Droop effect PCC3300V2
2: Synchronize
3: Load Share
4: Load Govern
43585 Paralleling Read Only 0: Isochronous Indicates which PCC3300,
Voltage voltage control PCC2300,
Control Mode 1: Droop algorithm is in effect PCC3300V2
2: Synchronize
3: Load Share
4: Load Govern
43589 PTC Read Only 0: Open Indicates the transition PCC3300,
Operating Transition type currently in effect PCC3300V2
Transition
Type 1: Hard Closed
Transition
2: Soft Closed
Transition

A029X159 (Issue 31) 715 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43590 PTC State Read Only 0: PTC Not Indicates the PCC3300,
Enabled connected state of the PCC3300V2
Power Transfer
1: No Source Control
Connected
2: Utility
Connected
3: Genset
Connected
4: Paralleled
43597 Utility CB Read Only 0: Inactive Utility cb close PCC3300,
Close command status PCC3300V2
Command 1: Active

43598 Utility CB Read Only 0: Inactive Utility cb open PCC3300,


Open command status PCC3300V2
Command 1: Active

43599 Utility CB Read Only 0: Open Indicates utility PCC3300,


Position breaker position PCC3300V2
Status 1: Closed
2: Not Available
43600 Load Govern Read/Write 0: Genset kW Use to select how PCC3300,
kW Method generator set kW PCC3300V2
1: Genset kW output will be
w/Utility controlled when
Constraint paralleled to utility.
2: Utility kW
43608 Configurable Read/Write Multiplier: 1 Unit: The event code for PCC3300,
Output #1 this output. PCC2300,
Event Code Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
65530
Sign: U
43610 Configurable Read/Write Multiplier: 1 Unit: The event code for PCC3300,
Output #2 this output. PCC2300,
Event Code Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
65530
Sign: U
43613 Configurable Read/Write Multiplier: 1 Unit: The event code for PCC3300,
Output #20 this output. PCC3300V2
Event Code Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U

Copyright © 2023 Cummins Inc. 716 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43616 Configurable Read/Write Multiplier: 1 Unit: The event code for PCC3300,
Output #21 this output. PCC3300V2
Event Code Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
43619 Configurable Read/Write Multiplier: 1 Unit: The event code for PCC3300,
Output #22 this output. PCC3300V2
Event Code Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
43622 Configurable Read/Write Multiplier: 1 Unit: The event code for PCC3300,
Output #3 this output. PCC2300,
Event Code Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
65530
Sign: U
43625 Configurable Read/Write Multiplier: 1 Unit: The event code for PCC3300,
Output #4 this output. PCC2300,
Event Code Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
65530
Sign: U
43641 Delayed Read/Write 0: Disabled Enables the Delayed PCC3300,
Shutdown Shutdown feature. PCC2300,
Enable 1: Enabled PCC3300V2
43642 Delayed Read/Write Multiplier: 0.1 Unit: seconds Sets the shutdown PCC3300,
Shutdown fault delayed time PCC2300,
Time Delay Offset: 0 Lower Limit: 0 delay for the Delayed PCC3300V2
Size (bits): 16 Upper Limit: 3 Shutdown feature.

Sign: U
43643 Remote Fault Read/Write 0: Disable Trim to enable PCC3300,
Reset Remote Fault Reset. PCC2300,
Enabled 1: Enable Can only reset PCC3300V2
"Warning" Faults
43644 Fail To Read/Write Multiplier: 1 Unit: seconds Trim to set the time for PCC3300,
Shutdown a shutdown fault to be PCC2300,
Delay Offset: 0 Lower Limit: 0 active and the PCC3300V2
Size (bits): 16 Upper Limit: 30 generator set not
shutting down before
Sign: U the Fail to Shutdown
fault occurs.

A029X159 (Issue 31) 717 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43645 LCL Read/Write 0: None Sets low coolant level PCC3300,
Detection fault response to PCC2300,
Response 1: Warning None, Warning or PCC3300V2
2: Shutdown Shutdown.

43646 LCT Warning Read/Write Multiplier: 1 Unit: Minutes Sets time to clear the PCC3300,
Clear Time low coolant temp fault. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 30
Sign: U
43647 LCT Warning Read/Write Multiplier: 1 Unit: Minutes Sets time to set the PCC3300,
Set Time low coolant temp fault. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 30
Sign: U
43648 LCT Warning Read/Write Multiplier: 1 Unit: degF Sets threshold for the PCC3300,
Threshold low coolant temp fault PCC2300,
Offset: 0 Lower Limit: -20 warning. PCC3300V2
Size (bits): 16 Upper Limit: 130
Sign: S
43649 V/Hz Knee Read/Write Multiplier: 0.1 Unit: Hz The voltage will roll off PCC3300,
Frequency (decrease) PCC2300,
Offset: 0 Lower Limit: 0 proportionally to the PCC3300V2
Size (bits): 16 Upper Limit: 10 V/Hz setup, once the
frequency drops below
Sign: U the set point in the
V/Hz Knee Frequency.
This allows the
generator set to
recover faster when
the frequency drops.
43650 V/Hz Rolloff Read/Write Multiplier: 0.1 Unit: % / Hz The amount of voltage PCC3300,
Slop roll off when the PCC2300,
Offset: 0 Lower Limit: 0 frequency is below the PCC3300V2
Size (bits): 16 Upper Limit: 20 knee frequency

Sign: U
43651 12 V High Read Only Multiplier: 0.1 Unit: Vdc Sets 12V high battery PCC3300,
Battery voltage fault threshold. PCC2300,
Voltage Offset: 0 Lower Limit: 14 PCC3300V2
Threshold Size (bits): 16 Upper Limit: 17
Sign: U

Copyright © 2023 Cummins Inc. 718 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43652 12 V Low Read Only Multiplier: 0.1 Unit: Vdc Sets 12V low battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 12 for generator set PCC3300V2
Running Size (bits): 16 Upper Limit: 16 operation while in
Threshold rated mode
Sign: U
43653 12 V Low Read Only Multiplier: 0.1 Unit: Vdc Sets 12V low battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 11 for generator set PCC3300V2
Stopped Size (bits): 16 Upper Limit: 13 operation in all modes
Threshold except rated
Sign: U
43654 12 V Weak Read/Write Multiplier: 0.1 Unit: Vdc Sets 12V weak battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 6 PCC3300V2
Threshold Size (bits): 16 Upper Limit: 10
Sign: U
43655 24 V High Read Only Multiplier: 0.1 Unit: Vdc Sets 24V high battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 28 PCC3300V2
Threshold Size (bits): 16 Upper Limit: 34
Sign: U
43656 24 V Low Read Only Multiplier: 0.1 Unit: Vdc Sets 24V low battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 24 for generator set PCC3300V2
Running Size (bits): 16 Upper Limit: 28 operation while in
Threshold rated mode
Sign: U
43657 24 V Low Read Only Multiplier: 0.1 Unit: Vdc Sets 24V low battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 22 for generator set PCC3300V2
Stopped Size (bits): 16 Upper Limit: 26 operation in all modes
Threshold except rated
Sign: U
43658 24 V Weak Read/Write Multiplier: 0.1 Unit: Vdc Sets 24V weak battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 10 PCC3300V2
Threshold Size (bits): 16 Upper Limit: 16
Sign: U
43659 Adjustable Read/Write Multiplier: 0.01 Unit: rpm/Hz Sets the rpm/Hz PCC3300,
Freq/Speed conversion factor PCC2300,
Gain Offset: 0 Lower Limit: 0 when the Freq to PCC3300V2
Size (bits): 16 Upper Limit: 240 Speed Gain Select
trim is set to this trim
Sign: U

A029X159 (Issue 31) 719 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43660 Alternate Read Only 0: 50 Hz Sets the generator set PCC3300,
Frequency nominal frequency. PCC2300,
Switch 1: 60 Hz PCC3300V2
43661 AVR Gain Read/Write Multiplier: 0.01 Unit: A trim that allows the PCC3300,
Adjust Trim user to modify the PCC2300,
Offset: 0 Lower Limit: 0.05 overall gains of the PCC3300V2
Size (bits): 16 Upper Limit: 10 AVR.

Sign: U
43662 Charging Read/Write Multiplier: 0.1 Unit: seconds Sets the time delay for PCC3300,
Alternator the charging alt failure PCC2300,
Fault Time Offset: 0 Lower Limit: 2 fault PCC3300V2
Delay Size (bits): 16 Upper Limit: 300
Sign: U
43663 Continuous Read/Write Multiplier: 1 Unit: seconds Sets the maximum PCC3300,
Crank amount of time to PCC2300,
Engage Time Offset: 0 Lower Limit: 40 engage the starter PCC3300V2
Size (bits): 16 Upper Limit: 100 when using the
continuous cranking
Sign: U method
43664 Controlled Read/Write Multiplier: 1 Unit: seconds Delay allowed for a PCC3300,
Shutdown shutdown with PCC3300V2
Advance Offset: 0 Lower Limit: 0 cooldown fault prior to
Notice Delay Size (bits): 16 Upper Limit: 300 shutting down the
genset
Sign: U
43665 Crank Read/Write Multiplier: 1 Unit: Sets the maximum PCC3300,
Attempts number of times to PCC2300,
Offset: 0 Lower Limit: 1 engage the starter PCC3300V2
Size (bits): 16 Upper Limit: 7 when attempting to
start engine using the
Sign: U cycle cranking method
43666 Cycle / Cont Read Only 0: Cycle Selects whether to use PCC3300,
Crank Select continuous cranking or PCC2300,
1: Continuous cycle cranking when PCC3300V2
attempting to start
engine
43667 Cycle Crank Read/Write Multiplier: 1 Unit: seconds Sets the maximum PCC3300,
Engage Time amount of time to PCC2300,
Offset: 0 Lower Limit: 2 engage the starter PCC3300V2
Size (bits): 16 Upper Limit: 20 during a single crank
attempt when using
Sign: U the cycle cranking
method

Copyright © 2023 Cummins Inc. 720 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43668 Cycle Crank Read/Write Multiplier: 1 Unit: seconds Rest time between PCC3300,
Rest Time start attempts for cycle PCC2300,
Offset: 0 Lower Limit: 7 crank mode. PCC3300V2
Size (bits): 16 Upper Limit: 40
Sign: U
43669 Delayed Off Read/Write Multiplier: 0.1 Unit: seconds Time delay between PCC3300,
FSO Relay when the Delayed Off PCC2300,
Time Offset: 0 Lower Limit: 0 Command turns off PCC3300V2
Size (bits): 16 Upper Limit: 120 and Run Command
turns off
Sign: U

TABLE 41.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43670 External AVR Read/Write Multiplier: 0.1 Unit: Hz Sets the knee PCC3300,
Knee frequency for the fixed PCC2300,
Frequency Offset: 0 Lower Limit: 0 knee freq logic. PCC3300V2
Size (bits): 16 Upper Limit: 10
Sign: U
43671 External Bias Read/Write 0: Disabled Enables the external PCC3300,
Commands bias (speed and PCC3300V2
Enable 1: Enabled voltage commands) to
the hardware outputs.
43672 Frequency Read/Write Multiplier: 0.01 Unit: Hz A method of adding in PCC3300,
Adjust a frequency offset to PCC2300,
Offset: 0 Lower Limit: -6 the base frequency PCC3300V2
Size (bits): 16 Upper Limit: 6 subject to high and
low limit calibrations.
Sign: S
43673 Genset Read/Write Multiplier: 0.1 Unit: hours Sets the total exercise PCC3300,
Exercise time not including PCC2300,
Time Offset: 0 Lower Limit: 0 warmup at idle or idle PCC3300V2
Size (bits): 16 Upper Limit: 25 cooldown time.

Sign: U
43674 Governor Read Only Multiplier: 0.01 Unit: A trim that allows the PCC3300,
Gain Adjust user to modify the PCC2300,
Offset: 0 Lower Limit: 0.05 overall gain of the PCC3300V2
Size (bits): 16 Upper Limit: 15 governor.

Sign: U

A029X159 (Issue 31) 721 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43675 High Battery Read Only Multiplier: 1 Unit: seconds The time delay until a PCC3300,
Voltage Set high battery voltage PCC2300,
Time Offset: 0 Lower Limit: 2 condition is reported PCC3300V2
Size (bits): 16 Upper Limit: 60 as a fault.

Sign: U
43676 High Battery Read Only Multiplier: 0.1 Unit: Vdc The high battery PCC3300,
Voltage voltage threshold PCC2300,
Threshold Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43677 Idle Read/Write Multiplier: 0.25 Unit: minutes Sets time to run at idle PCC3300,
Cooldown before shutting down PCC2300,
Time Offset: 0 Lower Limit: 0 generator set on PCC3300V2
Size (bits): 16 Upper Limit: 60 normal stops.

Sign: U
43678 Idle Speed Read Only Multiplier: 1 Unit: rpm Sets the speed at PCC3300,
which the engine will PCC2300,
Offset: 0 Lower Limit: 700 idle subject to high PCC3300V2
Size (bits): 16 Upper Limit: and low limit
1100 calibrations.

Sign: U
43679 Idle to Rated Read/Write Multiplier: 0.1 Unit: seconds The time over which PCC3300,
Ramp Time the speed reference is PCC2300,
Offset: 0 Lower Limit: 0 to ramp from idle PCC3300V2
Size (bits): 16 Upper Limit: 30 speed to rated speed.

Sign: U
43680 Idle Warmup Read/Write Multiplier: 1 Unit: degF Coolant temperature PCC3300,
Coolant threshold to end idle PCC2300,
Temp Offset: 0 Lower Limit: -40 warmup time. PCC3300V2
Size (bits): 16 Upper Limit: 300
Sign: S
43681 Idle Warmup Read/Write Multiplier: 1 Unit: seconds Sets maximum idle PCC3300,
Time warmup time. Warmup PCC2300,
Offset: 0 Lower Limit: 0 time may be less if PCC3300V2
Size (bits): 16 Upper Limit: coolant temperature
3600 exceeds threshold.

Sign: U

Copyright © 2023 Cummins Inc. 722 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43682 Load Dump Read/Write 0: Overload Enables the load PCC3300,
Activation dump output as a PCC2300,
Method 1: function of the PCC3300V2
Underfrequency overload and
2: Overload or underfrequency
Underfrequency conditions.

3: Diasabled
43683 Load Dump Read/Write Multiplier: 1 Unit: seconds The time delay until PCC3300,
Overload Set the load dump PCC2300,
Time Offset: 0 Lower Limit: 0 overload condition is PCC3300V2
Size (bits): 16 Upper Limit: 120 set active.
Sign: U
43684 Load Dump Read/Write Multiplier: 1 Unit: % The load dump PCC3300,
Overload overload threshold as PCC2300,
Threshold Offset: 0 Lower Limit: 80 a percentage of the PCC3300V2
Size (bits): 16 Upper Limit: 140 generator set
application rating.
Sign: U
43685 Load Dump Read/Write Multiplier: 1 Unit: Hz The frequency amount PCC3300,
Underfreque which the load dump PCC2300,
ncy Offset Offset: 0 Lower Limit: 0 underfrequency PCC3300V2
Size (bits): 16 Upper Limit: 10 threshold is below the
final frequency
Sign: S reference.
43686 Load Dump Read/Write Multiplier: 1 Unit: seconds The time delay until PCC3300,
Underfreque the load dump PCC2300,
ncy Set Time Offset: 0 Lower Limit: 0 underfrequency PCC3300V2
Size (bits): 16 Upper Limit: 20 condition is set active.

Sign: U
43687 Load Dump Read Only Multiplier: 0.1 Unit: Hz The frequency trip PCC3300,
Underfreque threshold for the load PCC2300,
ncy Offset: 0 Lower Limit: 0 dump underfrequency PCC3300V2
Threshold Size (bits): 16 Upper Limit: 90 condition.

Sign: U
43688 Low Battery Read Only Multiplier: 1 Unit: seconds The time delay until a PCC3300,
Voltage Set low battery voltage PCC2300,
Time Offset: 0 Lower Limit: 2 condition is reported PCC3300V2
Size (bits): 16 Upper Limit: 60 as a fault.

Sign: U

A029X159 (Issue 31) 723 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43689 Low Fuel in Read/Write Multiplier: 1 Unit: seconds Low Fuel in Day Tank PCC3300,
Day Tank Fault time delay from PCC2300,
Time Offset: 0 Lower Limit: 0 switch input. PCC3300V2
Size (bits): 16 Upper Limit: 20
Sign: U
43690 Low Fuel Read/Write Multiplier: 1 Unit: seconds A trim that sets the PCC3300,
Set/Clear delay time for PCC2300,
Time Offset: 0 Lower Limit: 2 generating the inactive PCC3300V2
Size (bits): 16 Upper Limit: 60 and active faults.

Sign: U
43691 Manual Read/Write 0: Normal Use to command idle PCC3300,
Warmup speed or to bypass PCC2300,
Bypass 1: Bypass idle warmup during a PCC3300V2
Warmup manual run.
43692 Max Idle Read/Write Multiplier: 0.1 Unit: minutes Sets the fault time for PCC3300,
Time the Too Long in Idle PCC2300,
Offset: 0 Lower Limit: 0 fault. PCC3300V2
Size (bits): 16 Upper Limit: 20
Sign: U
43693 Nominal Read Only 0: 12V Selects the generator PCC3300,
Battery set’s nominal battery PCC2300,
Voltage 1: 24V operating voltage. PCC3300V2
43694 Prelube Read/Write 0: Disabled Enables Or Disables PCC3300,
Cycle Enable the cyclic mode of PCC2300,
1: Enabled prelube operation. PCC3300V2
43695 Prelube Read/Write Multiplier: 0.1 Unit: hours "Sets the period of the PCC3300,
Cycle Time Prelube Cycle PCC2300,
Offset: 0 Lower Limit: 0.1 Iteration. PCC will PCC3300V2
Size (bits): 16 Upper Limit: truncate any
1000 ‘remainder’ minutes
time set in the ECM
Sign: U when Prelube Owner
is ECS e.g. if 65 or 66
minute is set in ECM
then PCC will show
1.0 hours and 1.1
hours respectively."
43696 Prelube Read/Write 0: Disabled Selects whether the PCC3300,
Function Prelube function is PCC2300,
Enable 1: Enabled enabled or disabled. PCC3300V2
This is Setup mode
interlocked.

Copyright © 2023 Cummins Inc. 724 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43697 Prelube Oil Read/Write Multiplier: 0.1 Unit: psig The oil pressure value PCC3300,
Pressure which when reached PCC2300,
Threshold Offset: 0 Lower Limit: 0 the prelube driver will PCC3300V2
Size (bits): 16 Upper Limit: 10 turn off.

Sign: U
43698 Prelube Read/Write Multiplier: 0.1 Unit: seconds Sets the maximum PCC3300,
Timeout time for which the PCC2300,
Period Offset: 0 Lower Limit: 0 Prelube Driver will PCC3300V2
Size (bits): 16 Upper Limit: 60 Remain ON.

Sign: U
43699 Rated to Idle Read/Write Multiplier: 0.1 Unit: seconds The time over which PCC3300,
Ramp Time the speed reference is PCC2300,
Offset: 0 Lower Limit: 0 to ramp from rated PCC3300V2
Size (bits): 16 Upper Limit: 30 speed to idle speed.

Sign: U
43700 Utility Read Only 0: Not Available Indicates status of the PCC3300,
Availability utility source. PCC3300V2
Status 1: Available
2: Unknown
43701 Utility CB Read Only 0: Inactive Utility cb inhibit PCC3300,
Inhibit command PCC3300V2
Command 1: Active

43702 Utility CB Read Only 0: Inactive Utility cb tripped PCC3300,


Tripped command PCC3300V2
Command 1: Active

43703 Utility Read Only 0: Unknown Indicates utility PCC3300,


Current breaker position based PCC3300V2
Based 1: Closed on current.
Breaker
Position
43704 Utility Read Only Multiplier: 0.1 Unit: Hz Indicates the lower PCC3300,
Frequency drop-out threshold in PCC3300V2
Lower Drop- Offset: 0 Lower Limit: Hz for utility frequency
Out Size (bits): 16 Upper Limit: sensor.
Threshold
Sign: U
43705 Utility Read Only Multiplier: 0.1 Unit: Hz Indicates the lower PCC3300,
Frequency pick-up threshold in PCC3300V2
Lower Pick- Offset: 0 Lower Limit: Hz for utility frequency
Up Threshold Size (bits): 16 Upper Limit: sensor.

Sign: U

A029X159 (Issue 31) 725 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43706 Utility Read Only 0: Unknown Indicates utility PCC3300,
Frequency frequency sensor PCC3300V2
Sensor 1: Picked Up status.
Status 2: Dropped Out
43707 Utility Read Only Multiplier: 0.1 Unit: Hz Indicates the upper PCC3300,
Frequency drop-out threshold in PCC3300V2
Upper Drop- Offset: 0 Lower Limit: Hz for utility frequency
Out Size (bits): 16 Upper Limit: sensor.
Threshold
Sign: U
43708 Utility Read Only Multiplier: 0.1 Unit: Hz Indicates the upper PCC3300,
Frequency pick-up threshold in PCC3300V2
Upper Pick- Offset: 0 Lower Limit: Hz for utility frequency
Up Threshold Size (bits): 16 Upper Limit: sensor.

Sign: U
43709 Utility Loss of Read Only 0: Unknown Indicates utility loss of PCC3300,
Phase phase sensor status. PCC3300V2
Sensor 1: Picked Up
Status 2: Dropped Out
43710 Utility Read Only Multiplier: 1 Unit: Vac Indicates the drop-out PCC3300,
Overvoltage threshold in volts for PCC3300V2
Drop-Out Offset: 0 Lower Limit: utility overvoltage
Threshold Size (bits): 16 Upper Limit: sensor.

Sign: U
43711 Utility Read Only Multiplier: 1 Unit: Vac Indicates the pick-up PCC3300,
Overvoltage threshold in volts for PCC3300V2
Pick-Up Offset: 0 Lower Limit: utility overvoltage
Threshold Size (bits): 16 Upper Limit: sensor.

Sign: U
43712 Utility Read Only 0: Unknown Indicates utility PCC3300,
Overvoltage overvoltage sensor PCC3300V2
Sensor 1: Picked Up status.
Status 2: Dropped Out
43713 Utility Phase Read Only 0: Unknown Indicates utility phase PCC3300,
Rotation rotation sensor status. PCC3300V2
Sensor 1: Picked Up
Status 2: Dropped Out
43714 Utility Read Only Multiplier: 1 Unit: Vac Indicates the drop-out PCC3300,
Undervoltage threshold in volts for PCC3300V2
Drop-Out Offset: 0 Lower Limit: utility undervoltage
Threshold Size (bits): 16 Upper Limit: sensor.

Sign: U

Copyright © 2023 Cummins Inc. 726 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43715 Utility Read Only Multiplier: 1 Unit: Vac Indicates the pick-up PCC3300,
Undervoltage threshold in volts for PCC3300V2
Pick-Up Offset: 0 Lower Limit: utility undervoltage
Threshold Size (bits): 16 Upper Limit: sensor.

Sign: U
43716 Utility Read Only 0: Unknown Indicates utility PCC3300,
Undervoltage undervoltage sensor PCC3300V2
Sensor 1: Picked Up status.
Status 2: Dropped Out
43719 Alternator Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature Alternator Temp 1 PCC2300,
1 (Aux101) Offset: 0 Lower Limit: input from the Aux 101 PCC3300V2
-32767 I/O Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43720 Alternator Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature Alternator Temp 2 PCC2300,
2 (Aux101) Offset: 0 Lower Limit: input from the Aux 101 PCC3300V2
-32767 I/O Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43721 Alternator Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature Alternator Temp 3 PCC2300,
3 (Aux101) Offset: 0 Lower Limit: input from the Aux 101 PCC3300V2
-32767 I/O Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43722 Ambient Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature Ambient Temp input PCC2300,
(Aux101) Offset: 0 Lower Limit: from the Aux 101 I/O PCC3300V2
-32767 Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43723 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
1 Voltage Offset: 0 Lower Limit: -500 1 in Volts. PCC3300V2
Size (bits): 16 Upper Limit: 500
Sign: S

A029X159 (Issue 31) 727 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43724 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
2 Voltage Offset: 0 Lower Limit: -500 2 in Volts. PCC3300V2
Size (bits): 16 Upper Limit: 500
Sign: S
43725 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
3 Voltage Offset: 0 Lower Limit: 3 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43726 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
4 Voltage Offset: 0 Lower Limit: 4 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43727 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
5 Voltage Offset: 0 Lower Limit: 5 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43728 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
6 Voltage Offset: 0 Lower Limit: 6 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43729 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
7 Voltage Offset: 0 Lower Limit: 7 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43730 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
8 Voltage Offset: 0 Lower Limit: 8 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43731 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
1 Voltage Offset: 0 Lower Limit: -500 1 in Volts. PCC3300V2
Size (bits): 16 Upper Limit: 500
Sign: S

Copyright © 2023 Cummins Inc. 728 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43732 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
2 Voltage Offset: 0 Lower Limit: -500 2 in Volts. PCC3300V2
Size (bits): 16 Upper Limit: 500
Sign: S
43733 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
3 Voltage Offset: 0 Lower Limit: 3 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43734 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
4 Voltage Offset: 0 Lower Limit: 4 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43735 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
5 Voltage Offset: 0 Lower Limit: 5 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43736 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
6 Voltage Offset: 0 Lower Limit: 6 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43737 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
7 Voltage Offset: 0 Lower Limit: 7 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43738 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
8 Voltage Offset: 0 Lower Limit: 8 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43739 Battery Read Only 0: Inactive Monitor point for the PCC3300,
Charger AC battery charger failure PCC2300,
Failure 1: Active input from the PCC3300V2
(HMI113) PCCNET Annunciator.

A029X159 (Issue 31) 729 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43740 Drive End Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Bearing Drive End Bearing PCC2300,
Temperature Offset: 0 Lower Limit: Temp input from the PCC3300V2
(Aux101) -32767 I/O Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43741 Exhaust Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Stack Exhaust Stack Temp1 PCC2300,
Temperature Offset: 0 Lower Limit: input from the I/O PCC3300V2
1 (Aux101) -32767 Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43742 Exhaust Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Stack Exhaust Stack Temp2 PCC2300,
Temperature Offset: 0 Lower Limit: input from the I/O PCC3300V2
2 (Aux101) -32768 Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43745 Fuel Level % Read Only Multiplier: 0.1 Unit: % Monitor point for the % PCC3300,
(Aux101) fuel level input from PCC2300,
Offset: 0 Lower Limit: the I/O Module. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
43746 Fuel Level Read Only Multiplier: 1 Unit: Monitor point for the PCC3300,
(Aux101) fuel level (in gallons) PCC2300,
Offset: 0 Lower Limit: input from the I/O PCC3300V2
Size (bits): 16 Upper Limit: Module.

Sign: S
43747 HMI113 Fault Read Only 0: Inactive Monitor point for input PCC3300,
1 Status #1 from the PCC2300,
1: Active Annunciator. PCC3300V2
43748 HMI113 Fault Read Only 0: Inactive Monitor point for input PCC3300,
2 Status #2 from the PCC2300,
1: Active Annunciator. PCC3300V2
43749 HMI113 Fault Read Only 0: Inactive Monitor point for the PCC3300,
3 Status input #3 from the PCC2300,
1: Active Annunciator. PCC3300V2

Copyright © 2023 Cummins Inc. 730 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43750 Intake Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Manifold Intake Manifold Temp PCC2300,
Temperature Offset: 0 Lower Limit: 1 input from the I/O PCC3300V2
1 (Aux101) -32768 Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43751 Low Coolant Read Only 0: Inactive Monitor point for the PCC3300,
Level Low Coolant Level PCC2300,
(HMI113) 1: Active input from the PCCnet PCC3300V2
Annunciator.
43752 Low Fuel Read Only 0: Inactive Monitor point for the PCC3300,
Level Low Fuel Level input PCC2300,
(HMI113) 1: Active from the PCCnet PCC3300V2
Annunciator.
43753 LTA Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature LTA Temperature PCC3300V2
(Aux101) Offset: 0 Lower Limit: -40 input from the I/O
Size (bits): 16 Upper Limit: 300 Module
Sign: S
43755 Non-Drive Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
End Bearing Non-Drive End PCC2300,
Temperature Offset: 0 Lower Limit: Bearing Temp input PCC3300V2
(Aux101) -65534 from the I/O Module.
Size (bits): 16 Upper Limit:
65535
Sign: S
43756 Number of Read Only Multiplier: 1 Unit: Used to monitor the PCC3300,
Connected amount of connected PCC2300,
Bargraph Offset: 0 Lower Limit: 0 Bargraph modules. PCC3300V2
Modules Size (bits): 8 Upper Limit: 255
Sign: U
43757 Oil Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature Oil Temp input from PCC2300,
(Aux101) Offset: 0 Lower Limit: the I/O Module. PCC3300V2
-65534
Size (bits): 16 Upper Limit:
65535
Sign: S

A029X159 (Issue 31) 731 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43758 Modbus Bus Read Only Multiplier: 1 Unit: Modbus bus message PCC3300,
Message count PCC2300,
Count Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43759 Modbus CRC Read Only Multiplier: 1 Unit: Modbus CRC errors PCC3300,
Errors Count count PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43760 Modbus Read Only Multiplier: 1 Unit: Modbus exception PCC3300,
Exception count PCC2300,
Count Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43761 Modbus No Read Only Multiplier: 1 Unit: Modbus no response PCC3300,
Response count PCC2300,
Count Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43762 Modbus Read Only Multiplier: 1 Unit: Modbus slave PCC3300,
Slave message count PCC2300,
Message Offset: 0 Lower Limit: PCC3300V2
Count Size (bits): 16 Upper Limit:
Sign: U
43763 Frequency Read Only Multiplier: 0.001 Unit: Hz Frequency match error PCC3300,
Match Error value used by PCC3300V2
Offset: 0 Lower Limit: frequency match PI
Size (bits): 16 Upper Limit: loop.

Sign: S
43767 Load Govern Read Only Multiplier: 0.01 Unit: % Indicates the final PCC3300,
kVAR Target target setpoint for PCC3300V2
Offset: 0 Lower Limit: generator set kVAR
Size (bits): 16 Upper Limit: output when paralleled
to utility.
Sign: S
43769 Load Govern Read Only Multiplier: 0.01 Unit: % Indicates the final PCC3300,
kW Target target setpoint for PCC3300V2
Offset: 0 Lower Limit: genset kW output
Size (bits): 16 Upper Limit: when paralleled to
utility.
Sign: S

Copyright © 2023 Cummins Inc. 732 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43770 Permissive Read Only 0: Not Allowed Indicates when PCC3300,
Close permissive sync check PCC3300V2
Allowed 1: Allowed conditions have been
met.
43773 Phase Match Read Only Multiplier: 0.01 Unit: deg Phase error signal for PCC3300,
Error the synchronizer PCC3300V2
Offset: 0 Lower Limit: control algorithm.
Size (bits): 16 Upper Limit:
Sign: S
43777 Start Read Only 0: Inactive This is the status of PCC3300,
Type/Configu the Configurable Input PCC2300,
rable Input 1: Active #11. PCC3300V2
#11 Switch
43778 Scheduler Read Only 0: Off Indicates the current PCC3300,
Run run command coming PCC2300,
Command 1: No Load from the scheduler. PCC3300V2
2: With Load
3: Extended
Parallel
43785 Start Read/Write Multiplier: 1 Unit: Number of start PCC3300,
Attempts attempts since the last PCC2300,
Since Reset Offset: 0 Lower Limit: 0 reset. PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
43786 Start Read/Write Multiplier: 1 Unit: Number of start PCC3300,
Attempts attempts since the last PCC2300,
Since Reset Offset: 0 Lower Limit: 0 reset. PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
43787 Total Start Read/Write Multiplier: 1 Unit: Total number of start PCC3300,
Attempts attempts. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U
43788 Total Start Read/Write Multiplier: 1 Unit: Total number of start PCC3300,
Attempts attempts. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U

A029X159 (Issue 31) 733 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43789 Backup Start Read Only 0: Inactive This is the status of PCC3300,
Disconnect/C the Configurable Input PCC3300V2
onfigurable 1: Active #33.
Input #33
Switch
43791 Battery Read Only 0: Inactive Battery Charger Failed PCC3300,
Charger Switch function output PCC2300,
Failed Switch 1: Active status; gives software PCC3300V2
Inactive/Active state.
43792 Battle Short Read Only 0: Inactive Battle Short Switch PCC3300,
Switch function output status PCC2300,
1: Active (Active or Inactive). PCC3300V2
43793 Configurable Read Only 0: Inactive Configurable Input #1 PCC3300,
Input #1 input software state PCC2300,
Switch 1: Active status. Gives software PCC3300V2
Inactive/Active state.
43794 Configurable Read Only 0: Inactive Configurable Input #2 PCC3300,
Input #2 input software state PCC2300,
Switch 1: Active status. Gives software PCC3300V2
Inactive/Active state.
43795 Configurable Read Only 0: Inactive Configurable Input #13 PCC3300,
Input #13 input software state PCC2300,
Switch 1: Active status. Gives software PCC3300V2
Inactive/Active state.
43796 Genset CB Read Only 0: Inactive Generator set cb open PCC3300,
Open command status. PCC3300V2
Command 1: Active

43800 Rated Read/Write Multiplier: 1 Unit: seconds Minimum time to PCC3300,


Cooldown spend at rated speed PCC2300,
Time Offset: 0 Lower Limit: 0 less than 10% load PCC3300V2
Size (bits): 16 Upper Limit: 600 before normal
shutdown is allowed
Sign: U
43801 Rated to Idle Read/Write Multiplier: 0.1 Unit: seconds Sets the delay time for PCC3300,
Transition transitioning from PCC2300,
Delay Offset: 0 Lower Limit: 0 Rated to Idle speed. 0 PCC3300V2
Size (bits): 16 Upper Limit: 10 seconds = feature is
disabled.
Sign: U
43802 Rupture Read/Write Multiplier: 0.1 Unit: seconds Rupture Basin fault PCC3300,
Basin Time time delay PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit: 20
Sign: U

Copyright © 2023 Cummins Inc. 734 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43803 Start Time Read/Write Multiplier: 1 Unit: seconds Sets the time to wait PCC3300,
Delay from receiving a valid PCC2300,
Offset: 0 Lower Limit: 0 remote start signal PCC3300V2
Size (bits): 16 Upper Limit: 300 until starting the
generator set.
Sign: U
43804 Starting to Read/Write Multiplier: 0.1 Unit: seconds The time over which PCC3300,
Rated Ramp the speed reference is PCC2300,
Time Offset: 0 Lower Limit: 0 to ramp from starting PCC3300V2
Size (bits): 16 Upper Limit: 30 speed to rated speed

Sign: U
43805 Time Delay Read/Write Multiplier: 1 Unit: seconds Sets time to run at PCC3300,
to Stop rated speed before PCC2300,
Offset: 0 Lower Limit: 0 going to cooldown at PCC3300V2
Size (bits): 16 Upper Limit: 600 idle. Does not apply to
manual runs
Sign: U
43806 Voltage Read/Write Multiplier: 0.01 Unit: % A trim that allows the PCC3300,
Adjust user to add/subtract PCC2300,
Offset: 0 Lower Limit: -5 an offset to the PCC3300V2
Size (bits): 16 Upper Limit: 5 nominal voltage when
calculating the voltage
Sign: S setpoint
43807 Voltage Read/Write Multiplier: 0.01 Unit: seconds The time period over PCC3300,
Ramp Time which the voltage PCC2300,
Offset: 0 Lower Limit: 0 setpoint command PCC3300V2
Size (bits): 16 Upper Limit: 5 should rise from 0% to
the target voltage
Sign: U
43808 Commit to Read Only 0: Not PTC - indicates if PCC3300,
Transfer Committed system is committed PCC3300V2
State to transferring to
1: Committed generator set
43810 Battle Short Read/Write 0: Inactive Trim to enable Battle PCC3300,
Switch Short via Modbus. PCC2300,
(Modbus) 1: Active PCC3300V2
43811 Exercise Read/Write 0: Inactive Modbus exercise PCC3300,
Switch switch PCC2300,
(Modbus) 1: Active PCC3300V2
43813 Extended Read/Write 0: Inactive Modbus extended PCC3300,
Parallel parallel switch PCC2300,
Switch 1: Active PCC3300V2
(Modbus)
43814 PTC Mode Read/Write 0: Inactive Modbus PTC Mode PCC3300,
Switch switch PCC3300V2
(Modbus) 1: Active

A029X159 (Issue 31) 735 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43815 Start Type Read/Write 0: Emergency PCC3300,
(Modbus) PCC2300,
1: Non PCC3300V2
Emergency
43818 Isolated Bus Read/Write 0: Constant Sets the speed control PCC3300,
Speed method for isolated PCC2300,
Control 1: Droop bus paralleling. PCC3300V2
Method Parameter is also
known as Load Share
Speed Droop Control
Method
43819 Isolated Bus Read/Write 0: Constant Sets the voltage PCC3300,
Voltage control method for PCC2300,
Control 1: Droop isolated bus PCC3300V2
Method paralleling.
43820 Maximum Read/Write Multiplier: 0.1 Unit: seconds Sets the maximum PCC3300,
Parallel Time time that the generator PCC3300V2
(TDMP) Offset: 0 Lower Limit: 0 set can remain
Size (bits): 16 Upper Limit: paralleled to the utility
1800 during closed
transition transfers.
Sign: U
43821 Programmed Read/Write Multiplier: 0.1 Unit: seconds Sets the time delay PCC3300,
Transition from when one source PCC3300V2
Delay Offset: 0 Lower Limit: 0 opens until the other
(TDPT) Size (bits): 16 Upper Limit: 60 closes during open
transition transfers.
Sign: U
43822 Retransfer Read/Write Multiplier: 0.1 Unit: seconds Sets the amount of PCC3300,
Delay time that the utility PCC3300V2
(TDEN) Offset: 0 Lower Limit: 0 source must be
Size (bits): 16 Upper Limit: available before the
1800 control will retranfer to
that source.
Sign: U
43823 Synchronizer Read/Write 0: Phase Match Sets the speed control PCC3300,
Speed method for PCC3300V2
Control 1: Slip synchronizing.
Method Frequency
2: External
43824 Synchronizer Read/Write 0: Voltage Match Sets the voltage PCC3300,
Voltage control method for PCC3300V2
Control 1: External synchronizing.
Method

Copyright © 2023 Cummins Inc. 736 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43825 Transfer Read/Write Multiplier: 0.1 Unit: seconds Sets the amount of PCC3300,
Delay time that the generator PCC3300V2
(TDNE) Offset: 0 Lower Limit: 0 set source must be
Size (bits): 16 Upper Limit: 120 available before the
control will tranfer to
Sign: U that source.
43826 Transition Read/Write 0: Open Sets the load transfer PCC3300,
Type Transition transition type for use PCC3300V2
when Generator set
1: Hard Closed Application Type =
Transition Power Transfer
2: Soft Closed Control.
Transition
43829 Utility Read/Write 0: Load Govern Sets the speed control PCC3300,
Parallel method for utility PCC3300V2
Speed 1: Droop paralleling.
Control
Method
43830 Utility Read/Write 0: Load Govern Sets the voltage PCC3300,
Parallel control method for PCC3300V2
Voltage 1: Droop utility paralleling.
Control Option of 'Load
Method Govern with Droop
Feed Forward' is no
more available.
43831 Aux101 Read/Write 0: Critical Device Selects the generator PCC3300,
Device 0 Response set reaction to a loss PCC2300,
PCCnet of a Device 0 I/O PCC3300V2
Failure 1: Non-Critical Module as critical
Response Device (Shutdown) or non-
Type Response critical (Warning).
43832 Aux101 Read/Write 0: Critical Device Selects the generator PCC3300,
Device 1 Response set reaction to a loss PCC2300,
PCCnet of a Device 1 I/O PCC3300V2
Failure 1: Non-Critical Module as critical
Response Device (Shutdown) or non-
Type Response critical (Warning).
43834 HMI113 Read/Write 0: Critical Device Selects the generator PCC3300,
Annunciator Response set reaction to a loss PCC2300,
PCCnet of an Annunciator as PCC3300V2
Failure 1: Non-Critical critical or non-critical.
Response Device Selecting Critical will
Type Response cause a shutdown
when the Annunciator
looses communication.

A029X159 (Issue 31) 737 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43836 HMI220 Read/Write 0: Critical Device Selects the generator PCC3300,
PCCnet Response set reaction to a loss PCC2300,
Failure of an HMI220 PCC3300V2
Response 1: Non-Critical Operator Panel as
Type Device critical or non-critical.
Response A critical response will
shutdown the
generator set when
PCCnet
communication is lost.
43837 HMI320 Read/Write 0: Critical Device Selects the generator PCC3300,
PCCnet Response set reaction to a loss PCC2300,
Failure of an HMI320 PCC3300V2
Response 1: Non-Critical Operator Panel as
Type Device critical or non-critical.
Response A critical response will
shutdown the
generator set when
PCCnet
communication is lost.
43839 PCCnet Read/Write Multiplier: 1 Unit: seconds Selects the time PCC3300,
Device allowed for arbitration PCC2300,
Failure Time Offset: 0 Lower Limit: 15 to occur before a PCC3300V2
Delay Size (bits): 8 Upper Limit: 250 PCCnet failure fault is
generated.
Sign: U
43840 Test With Read/Write 0: Disabled Use to choose PCC3300,
Load Enable whether a test is with PCC3300V2
1: Enabled load or without load.
43842 Commit to Read/Write 0: Utility PTC - sets point at PCC3300,
Transfer Disconnect which system commits PCC3300V2
Method to transfer to
1: Genset Start generator set.
2: No Commit
43843 Commit to Read/Write Multiplier: 1 Unit: seconds PTC - sets time PCC3300,
Transfer system will wait for PCC3300V2
Timeout Offset: 0 Lower Limit: 0 generator set when
Size (bits): 16 Upper Limit: committed to transfer.
3200
Sign: U
43844 Commit to Read Only Multiplier: 0.05 Unit: sec PTC - remaining time PCC3300,
Transfer system to wait for PCC3300V2
Timer Offset: 0 Lower Limit: generator set when
Size (bits): 16 Upper Limit: committed to transfer.

Sign: U

Copyright © 2023 Cummins Inc. 738 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43845 Modbus Read/Write Multiplier: 1 Unit: seconds Time delay before the PCC3300,
Failure Time control activates the PCC2300,
Delay Offset: 0 Lower Limit: 0 modbus failure fault PCC3300V2
Size (bits): 16 Upper Limit: 10 after the master is
sensed as no longer
Sign: U present.
43846 Modbus Read/Write 0: Do Nothing When set to Reset PCC3300,
Communicati Commands will reset PCC2300,
ons Lost 1: Reset the modbus control PCC3300V2
Response Commands logicals to an inactive
Method state when Modbus
communications are
lost.
43847 Modbus Read/Write 0: Do Nothing Resets all modbus PCC3300,
Clear counters, including PCC2300,
Counters 1: Clear J14 if applicable. PCC3300V2
Counters
43848 Controlled Read/Write Multiplier: 1 Unit: seconds Maximum ramp unload PCC3300,
Shutdown time during a PCC3300V2
Max Ramp Offset: 0 Lower Limit: 0 shutdown with
Unload Time Size (bits): 16 Upper Limit: 300 cooldown
Sign: U
43849 Genset Read/Write Multiplier: 1 Unit: kVAR Sets the generator set PCC3300,
kVAR load govern kVAR PCC3300V2
Setpoint Offset: 0 Lower Limit: base load internal
-20000 operating setpoint in
Size (bits): 16 Upper Limit: units of kVAR.
20000 Requires that Load
Govern kVAR Setpoint
Sign: S Source = Internal and
Load Govern kVAR
Method = Generator
set kVAR.
43850 Genset Read/Write Multiplier: 0.01 Unit: % Sets the generator set PCC3300,
kVAR load govern kVAR PCC3300V2
Setpoint Offset: 0 Lower Limit: -60 base load internal
Percent Size (bits): 16 Upper Limit: 60 operating setpoint
in % of standby kVA
Sign: S rating. Requires that
Load Govern kVAR
Setpoint Source =
Internal and Load
Govern kVAR Method
= Generator set kVAR.

A029X159 (Issue 31) 739 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43851 Genset kW Read/Write Multiplier: 1 Unit: kW Sets the generator set PCC3300,
Setpoint load govern kW base PCC3300V2
Offset: 0 Lower Limit: 0 load internal operating
Size (bits): 16 Upper Limit: setpoint in units of kW.
20000 Requires that Load
Govern kW Setpoint
Sign: S Source = Internal and
Load Govern kW
Method = Generator
set kW.
43852 Genset kW Read/Write Multiplier: 0.01 Unit: % Sets the generator set PCC3300,
Setpoint load govern kW base PCC3300V2
Percent Offset: 0 Lower Limit: 0 load internal operating
Size (bits): 16 Upper Limit: 100 setpoint in % of
standby rating.
Sign: S Requires that Load
Govern kW Setpoint
Source = Internal and
Load Govern kW
Method = Generator
set kW.
43853 Genset Read/Write Multiplier: 0.01 Unit: PF "Sets the load govern PCC3300,
Power Factor setpoint for generator PCC3300V2
Setpoint Offset: 0 Lower Limit: -1 set PF control.
Size (bits): 8 Upper Limit: 1 Requires that Load
Govern kVAR Setpoint
Sign: S Source = Internal and
Load Govern kVAR
Method = Generator
set PF. PF can be set
from –0.8 to –1.0 and
from 0.7 to 1.0"
43854 Load Read/Write 0: Inactive Modbus input for PCC3300,
Demand activating load PCC3300V2
Stop 1: Active demand stop on the
(Modbus) generator set
43855 Load Govern Read/Write 0: Genset kVAR Use to select how PCC3300,
kVAR generator set kVAR PCC3300V2
Method 1: Genset Power output will be
Factor controlled when
2: Utility kVAR paralleled to utility.

3: Utility Power
Factor
43856 Load Govern Read/Write Multiplier: 1 Unit: seconds Sets load govern PCC3300,
kVAR Ramp kVAR ramp load rate PCC3300V2
Load Time Offset: 0 Lower Limit: 0 = Generator set
Size (bits): 16 Upper Limit: 900 Standby kVA * 0.6/
this time.
Sign: U

Copyright © 2023 Cummins Inc. 740 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43857 Load Govern Read/Write Multiplier: 1 Unit: seconds Sets load govern PCC3300,
kVAR Ramp kVAR ramp unload PCC3300V2
Unload Time Offset: 0 Lower Limit: 0 rate = Generator set
Size (bits): 16 Upper Limit: 900 Standby KVA * 0.6/
this time.
Sign: U
43858 Utility Read/Write 0: After Transfer PTC - point in time at PCC3300,
Breaker Delay which system opens PCC3300V2
Opening utility breaker
Point 1: Upon Utility
Failure
43859 Load Govern Read/Write Multiplier: 1 Unit: seconds Sets load govern kW PCC3300,
kW Ramp ramp load rate = PCC3300V2
Load Time Offset: 0 Lower Limit: 0 Generator set Standby
Size (bits): 16 Upper Limit: 900 kW rating/ this time.
Sign: U
43860 Load Govern Read/Write Multiplier: 1 Unit: seconds Sets load govern kW PCC3300,
kW Ramp ramp unload rate = PCC3300V2
Unload Time Offset: 0 Lower Limit: 0 Generator set Standby
Size (bits): 16 Upper Limit: 900 kW rating/ this time.
Sign: U
43862 Slip Read/Write Multiplier: 0.001 Unit: Hz Sets the synchronizer PCC3300,
Frequency slip frequency. PCC3300V2
Offset: 0 Lower Limit: -3 Requires that Sync
Size (bits): 16 Upper Limit: 3 Speed Control Method
= Slip Frequency.
Sign: S
43863 Utility kVAR Read/Write Multiplier: 1 Unit: kVAR Sets the utility kVAR PCC3300,
Setpoint peak shave internal PCC3300V2
Offset: 0 Lower Limit: operating setpoint in
-20000 units of kVAR.
Size (bits): 16 Upper Limit: Requires that Load
20000 Govern kVAR Setpoint
Source = Internal and
Sign: S Load Govern kVAR
Method = Utility kVAR
43864 Utility kVAR Read/Write Multiplier: 0.01 Unit: % Sets the utility kVAR PCC3300,
Setpoint peak shave internal PCC3300V2
Percent Offset: 0 Lower Limit: -320 operating setpoint
Size (bits): 16 Upper Limit: 320 in % of generator set
standby kVA rating.
Sign: S Requires that Load
Govern kVAR Setpoint
Source = Internal and
Load Govern kVAR
Method = Utility kVAR.

A029X159 (Issue 31) 741 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43865 Utility kW Read/Write Multiplier: 1 Unit: kW Sets the utility kW PCC3300,
Constraint minimum load level for PCC3300V2
Offset: 0 Lower Limit: constrained base load
-20000 mode of operation.
Size (bits): 16 Upper Limit: Requires that Load
20000 Govern kW Setpoint
Source = Internal and
Sign: S Load Govern kW
Method = Generator
set kW w/Utility
Constraint.
43866 Utility kW Read/Write Multiplier: 0.01 Unit: % Sets utility kW PCC3300,
Constraint minimum load level for PCC3300V2
Percent Offset: 0 Lower Limit: -320 constrained base load
Size (bits): 16 Upper Limit: 320 mode in % of
generator set standby
Sign: S rating. Requires that
Load Govern kW
Setpoint Source =
Internal and Load
Govern kW Method =
Generator set kW
w/Utility Constraint.
43867 Utility kW Read/Write Multiplier: 1 Unit: kW Sets the utility kW PCC3300,
Setpoint peak shave internal PCC3300V2
Offset: 0 Lower Limit: operating setpoint in
-20000 units of kW. Requires
Size (bits): 16 Upper Limit: that Load Govern kW
20000 Setpoint Source =
Internal and Load
Sign: S Govern kW Method =
Utility kW.
43868 Utility kW Read/Write Multiplier: 0.01 Unit: % Sets the utility kW PCC3300,
Setpoint peak shave internal PCC3300V2
Percent Offset: 0 Lower Limit: -320 operating setpoint
Size (bits): 16 Upper Limit: 320 in % of generator set
standby rating.
Sign: S Requires that Load
Govern kW Setpoint
Source = Internal and
Load Govern kW
Method = Utility kW.

Copyright © 2023 Cummins Inc. 742 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43869 Utility Power Read/Write Multiplier: 0.01 Unit: PF Sets the internal PCC3300,
Factor setpoint for utility PCC3300V2
Setpoint Offset: 0 Lower Limit: 0.7 power factor control
Size (bits): 8 Upper Limit: 1 mode when paralleled
to utility. Requires that
Sign: S Load Govern kVAR
Setpoint Source =
Internal and Load
Govern kVAR Method
= Utility Power Factor.
43870 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 2 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43871 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 4 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43872 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 5 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43873 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 6 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43874 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 7 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U

A029X159 (Issue 31) 743 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43875 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 1 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43876 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 2 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43877 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 3 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43878 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 4 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43879 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 5 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43880 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 6 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43881 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 7 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U

Copyright © 2023 Cummins Inc. 744 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43882 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 8 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43883 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 10 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43884 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 11 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43885 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 12 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43886 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 13 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43887 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 14 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43888 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 15 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U

A029X159 (Issue 31) 745 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43889 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 16 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43890 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 9 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43891 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 10 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U

TABLE 42.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43892 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 11 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43893 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 12 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43894 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 13 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U

Copyright © 2023 Cummins Inc. 746 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43895 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 14 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43896 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 15 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43897 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 16 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43898 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 9 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43900 HMI113 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 1 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43901 HMI113 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 2 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43902 HMI113 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 3 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U

A029X159 (Issue 31) 747 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43903 HMI113 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 4 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43911 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 3 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43912 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 1 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43913 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 8 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.

Sign: U
43914 Transfer/Retr Read/Write 0: Inactive Override switch input PCC3300,
ansfer status from Modbus. PCC3300V2
Override 1: Active
Switch
(Modbus)
43915 Extended Read/Write 0: Disabled Use to enable the PCC3300,
Parallel extended paralleling PCC3300V2
Enable 1: Enabled mode of PTC.
43916 V/Hz Knee Read Only Multiplier: 0.1 Unit: Hz The voltage will roll off PCC2300,
Frequency (decrease) PCC3300,
50Hz Offset: 0 Lower Limit: 0 proportionally to the PCC3300V2
Size (bits): 16 Upper Limit: 10 V/Hz setup, once the
frequency drops below
Sign: U the set point in the
V/Hz Knee Frequency.
This allows the
generator set to
recover faster when
the frequency drops.
This is for 50Hz
frequency.

Copyright © 2023 Cummins Inc. 748 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43917 V/Hz Knee Read Only Multiplier: 0.1 Unit: Hz The voltage will roll off PCC2300,
Frequency (decrease) PCC3300,
60Hz Offset: 0 Lower Limit: 0 proportionally to the PCC3300V2
Size (bits): 16 Upper Limit: 10 V/Hz setup, once the
frequency drops below
Sign: U the set point in the
V/Hz Knee Frequency.
This allows the
generator set to
recover faster when
the frequency drops.
This is for 60Hz
frequency.
43918 V/Hz Rolloff Read Only Multiplier: 0.1 Unit: % / Hz The amount of voltage PCC3300,
Slope 50Hz roll off when the PCC2300,
Offset: 0 Lower Limit: 0 frequency is below the PCC3300V2
Size (bits): 16 Upper Limit: 20 knee frequency.

Sign: U
43919 V/Hz Rolloff Read Only Multiplier: 0.1 Unit: % / Hz The amount of voltage PCC3300,
Slope 60Hz roll off when the PCC2300,
Offset: 0 Lower Limit: 0 frequency is below the PCC3300V2
Size (bits): 16 Upper Limit: 20 knee frequency.

Sign: U
43920 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43921 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43922 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43923 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C

A029X159 (Issue 31) 749 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43924 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43925 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43926 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43927 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43928 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43929 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43930 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43931 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C

Copyright © 2023 Cummins Inc. 750 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43932 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43933 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43934 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43935 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43952 Speed/Frequ Read/Write Multiplier: 0.1 Unit: seconds Sets the delay time for PCC3300,
ency Delay generating the PCC2300,
Offset: 0 Lower Limit: 0.5 Speed/Frequency PCC3300V2
Size (bits): 16 Upper Limit: 10 mismatch fault.

Sign: U
43953 Speed/Frequ Read/Write Multiplier: 0.1 Unit: Hz Sets the threshold for PCC3300,
ency generating the PCC2300,
Threshold Offset: 0 Lower Limit: 0.5 Speed/Frequency PCC3300V2
Size (bits): 16 Upper Limit: 20 mismatch fault.

Sign: U
43955 Genset Idle Read Only 0: Disabled Enables or disables PCC3300,
Enable idling of generator set PCC2300,
1: Enabled with external governor. PCC3300V2
43959 Utility Read/Write Multiplier: 1 Unit: kW Sets threshold at PCC3300,
Unloaded which utility source is PCC3300V2
Level Offset: 0 Lower Limit: considered as
-32768 unloaded.
Size (bits): 16 Upper Limit:
32762
Sign: S

A029X159 (Issue 31) 751 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43960 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43961 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43962 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43963 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43964 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43965 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43966 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43967 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 752 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43968 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43969 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43970 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43971 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43972 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43973 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43974 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43975 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 753 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43976 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43977 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43978 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43979 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43980 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43981 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43982 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43983 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 754 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43984 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43985 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43986 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43987 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43988 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43989 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43990 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43991 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 755 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43992 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43993 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43994 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43995 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43996 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43997 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43998 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
43999 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 756 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
44001 Secondary Read Only 0: Disabled "Shows if secondary PCC3300,
Starter starter is configured PCC3300V2
Configuration 1: Enabled for the generator set"
Enabled
44002 Starter in Read Only 0: Primary "Shows which starter PCC3300,
Use is currently in use by PCC3300V2
1: Secondary the generator set"
44003 Secondary Read Only 0: Inactive "Indicates if the PCC3300,
Starter secondary starter is PCC3300V2
Command 1: Active Inactive or Active"
44304 Cycle / Cont Read Only 0: Cycle "Selects whether to PCC3300,
Crank Select use continuous PCC3300V2
(Secondary) 1: Continuous cranking or cycle
cranking when
attempting to start
engine with secondary
starter"
44305 Cycle Crank Read/Write Multiplier: 1 Unit: seconds "Sets the maximum PCC3300,
Engage Time amount of time to PCC3300V2
(Secondary) Offset: 0 Lower Limit: 2 engage the secondary
Size (bits): 16 Upper Limit: 20 starter during a single
crank attempt when
Sign: U using the cycle
cranking method"
44306 Continuous Read/Write Multiplier: 1 Unit: seconds "Sets the maximum PCC3300,
Crank amount of time to PCC3300V2
Engage Time Offset: 0 Lower Limit: 40 engage the secondary
(Secondary) Size (bits): 16 Upper Limit: 100 starter when using the
continuous cranking
Sign: U method"
44307 Crank Read/Write Multiplier: 1 Unit: "Sets the maximum PCC3300,
Attempts number of times to PCC3300V2
(Secondary) Offset: 0 Lower Limit: 1 engage the starter
Size (bits): 16 Upper Limit: 7 when attempting to
start engine in cycle
Sign: U cranking method using
secondary starter"
44308 Cycle Crank Read/Write Multiplier: 1 Unit: seconds "Sets the amount of PCC3300,
Rest Time time to wait between PCC3300V2
(Secondary) Offset: 0 Lower Limit: 7 crank attempts using
Size (bits): 16 Upper Limit: 40 secondary starter in
case of cyclic crank"
Sign: U

A029X159 (Issue 31) 757 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
44309 Preferred Read/Write 0: Use Primary "Lets you choose the PCC3300,
Starter at starter to be used by PCC3300V2
Critical 1: Use generator set in case
Battery Secondary of primary starter
battery becoming low
or weak."
45999 Unrecognize Read Only 0: All Pairs Indicates whether or PCC3300,
d SPN/FMI Recognized not all pairs in current PCC2300,
Status DM1 are recognized. PCC3300V2
1: Pair Not
Recognized
46000 Genset Read Only 0: L1-L2-L3 Generator set phase PCC3300,
Phase rotation PCC2300,
Rotation 1: L1-L3-L2 PCC3300V2
2: Not Available
46001 Utility Phase Read Only 0: L1-L2-L3 Utility phase rotation PCC3300,
Rotation PCC3300V2
1: L1-L3-L2
2: Not Available
46002 Genset Bus Read Only 0: L1-L2-L3 Generator set bus PCC3300,
Phase phase rotation PCC3300V2
Rotation 1: L1-L3-L2
2: Not Available
46003 Base Speed Read Only Multiplier: 0.0625 Unit: rpm Provides a point to PCC3300,
monitor the base PCC2300,
Offset: 0 Lower Limit: speed. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
46004 Base Speed Read Only Multiplier: 0.0625 Unit: rpm Provides a point to PCC3300,
monitor the base PCC2300,
Offset: 0 Lower Limit: speed. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
46005 Final Speed Read Only Multiplier: 0.0625 Unit: rpm Provides a point to PCC3300,
Reference monitor the final speed PCC2300,
Offset: 0 Lower Limit: reference. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
46006 Final Speed Read Only Multiplier: 0.0625 Unit: rpm Provides a point to PCC3300,
Reference monitor the final speed PCC2300,
Offset: 0 Lower Limit: reference. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 758 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46008 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
1 Exhaust Port 1 PCC2300,
Temperature Offset: 0 Lower Limit: -459 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46009 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
2 Exhaust Port 2 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46010 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
3 Exhaust Port 3 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46011 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
4 Exhaust Port 4 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46012 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
5 Exhaust Port 5 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46013 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
6 Exhaust Port 6 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46014 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
7 Exhaust Port 7 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S

A029X159 (Issue 31) 759 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46015 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
8 Exhaust Port 8 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46016 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
9 Exhaust Port 9 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46017 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
10 Exhaust Port 10 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46018 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
11 Exhaust Port 11 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46019 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
12 Exhaust Port 12 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46020 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
13 Exhaust Port 13 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46021 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
14 Exhaust Port 14 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S

Copyright © 2023 Cummins Inc. 760 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46022 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
15 Exhaust Port 15 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46023 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
16 Exhaust Port 16 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46024 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
17 Exhaust Port 17 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46025 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
18 Exhaust Port 18 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46026 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
19 Exhaust Port 19 PCC2300,
Temperature Offset: 0 Lower Limit: Temperature PCC3300V2
–460
Size (bits): 16 Upper Limit:
3155
Sign: S
46027 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
20 Exhaust Port 20 PCC2300,
Temperature Offset: 0 Lower Limit: Temperature PCC3300V2
–460
Size (bits): 16 Upper Limit:
3155
Sign: S
46028 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 1 cylinder 1 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U

A029X159 (Issue 31) 761 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46029 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 2 cylinder 2 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46030 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 3 cylinder 3 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46031 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 4 cylinder 4 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46032 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 5 cylinder 5 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46033 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 6 cylinder 6 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46034 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 7 cylinder 7 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46035 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 8 cylinder 8 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46036 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 9 cylinder 9 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 762 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46037 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 10 cylinder 10 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46038 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 11 cylinder 11 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46039 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 12 cylinder 12 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46040 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 13 cylinder 13 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46041 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 14 cylinder 14 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46042 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 15 cylinder 15 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46043 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 16 cylinder 16 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46044 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 17 cylinder 17 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U

A029X159 (Issue 31) 763 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46045 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 18 cylinder 18 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46048 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 1 Cylinder 1 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46049 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 2 Cylinder 2 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46050 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 3 Cylinder 3 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46051 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 4 Cylinder 4 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46052 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 5 Cylinder 5 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46053 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 6 Cylinder 6 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U

Copyright © 2023 Cummins Inc. 764 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46054 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 7 Cylinder 7 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46055 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 8 Cylinder 8 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46056 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 9 Cylinder 9 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46057 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 10 Cylinder 10 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46058 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 11 Cylinder 11 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46059 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 12 Cylinder 12 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46060 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 13 Cylinder 13 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U

A029X159 (Issue 31) 765 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46061 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 14 Cylinder 14 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46062 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 15 Cylinder 15 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46063 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 16 Cylinder 16 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46064 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 17 Cylinder 17 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46065 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 18 Cylinder 18 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46068 Spark Timing Read Only Multiplier: 0.1 Unit: Degres Spark timing degrees PCC3300,
Cyl 1 for cylinder 1 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46069 Spark Timing Read Only Multiplier: 0.1 Unit: Degres Spark timing degrees PCC3300,
Cyl 2 for cylinder 2 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S

Copyright © 2023 Cummins Inc. 766 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46070 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 3 for cylinder 3 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46071 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 4 for cylinder 4 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46072 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 5 for cylinder 5 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46073 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 6 for cylinder 6 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46074 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 7 for cylinder 7 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46075 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 8 for cylinder 8 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46076 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 9 for cylinder 9 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46077 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 10 for cylinder 10 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S

A029X159 (Issue 31) 767 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46078 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 11 for cylinder 11 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46079 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 12 for cylinder 12 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46080 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 13 for cylinder 13 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46081 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 14 for cylinder 14 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46082 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 15 for cylinder 15 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46083 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 16 for cylinder 16 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46084 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 17 for cylinder 17 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46085 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 18 for cylinder 18 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S

Copyright © 2023 Cummins Inc. 768 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46088 Internal Read Only Multiplier: 0.1 Unit: degF Temperature of the PCC3300,
SSM558 1 engine electronic PCC3300V2
Temperature Offset: 0 Lower Limit: control unit SSM558 1
Size (bits): 16 Upper Limit:
Sign: S
46089 Internal Read Only Multiplier: 0.1 Unit: degF Temperature of the PCC3300,
SSM558 2 engine electronic PCC3300V2
Temperature Offset: 0 Lower Limit: control unit SSM558 2
Size (bits): 16 Upper Limit:
Sign: S

TABLE 43.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46090 Internal Read Only Multiplier: 0.1 Unit: degF Temperature of the PCC3300,
MCM700 engine electronic PCC3300V2
Temperature Offset: 0 Lower Limit: control unit MCM700
Size (bits): 16 Upper Limit:
Sign: S
46091 Derate Read Only 0: NO Derate authorisation PCC3300,
Authorization request from PCC3300V2
1: YES customer.
2: Reserved
3: N/A
4: Network
Failure
46093 Ventilator Read Only 0: OFF Vent Fan status PCC3300,
Fan Status monitor point. PCC3300V2
1: ON
2: TRIPPED
3: N/A
46096 GIB Isolator Read Only 0: Close GIB Isolator Open PCC3300,
Open monitor point. PCC3300V2
(Aux101) 1: Open
2: Reserved
3: N/A
4: Network
Failure

A029X159 (Issue 31) 769 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46097 Alternator Read Only 0: OFF Alternator Heater PCC3300,
Heater status monitor point. PCC3300V2
Status 1: ON
2: TRIPPED
3: N/A
46101 Start Inhibit Read Only 0: Inactive Start Inhibit No1 PCC3300,
No1 monitor point. PCC3300V2
(Aux101) 1: Active
2: Reserved
3: Not Available
4: Network
Failure
46102 Start Inhibit Read Only 0: Inactive Start Inhibit No2 PCC3300,
No2 monitor point. PCC3300V2
(Aux101) 1: Active
2: Reserved
3: Not Available
4: Network
Failure
46103 Start Inhibit Read Only 0: Inactive Start Inhibit No3 PCC3300,
No3 monitor point. PCC3300V2
(Aux101) 1: Active
2: Reserved
3: Not Available
4: Network
Failure
46104 DC PSU Read Only 0: No Engine PSU Not PCC3300,
Unavailable Available monitor PCC3300V2
(Aux101) 1: Yes point.
2: Reserved
3: N/A
4: Network
Failure
46105 Ventilator Read Only 0: No Ventilator Fan Trip PCC3300,
Fan Trip monitor point. PCC3300V2
(Aux101) 1: Yes
2: Reserved
3: N/A
4: Network
Failure

Copyright © 2023 Cummins Inc. 770 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46106 Aux101-3 Read Only Multiplier: 0.01 Unit: Software version of PCC3300,
Software the firmware for the PCC3300V2
Version Offset: 0 Lower Limit: Aux101-3
Size (bits): 16 Upper Limit:
Sign: U
46107 Aux101-4 Read Only Multiplier: 0.01 Unit: Software version of PCC3300,
Software the firmware for the PCC3300V2
Version Offset: 0 Lower Limit: Aux101-4
Size (bits): 16 Upper Limit:
Sign: U
46108 Aux101-5 Read Only Multiplier: 0.01 Unit: Software version of PCC3300,
Software the firmware for the PCC3300V2
Version Offset: 0 Lower Limit: Aux101-5
Size (bits): 16 Upper Limit:
Sign: U
46113 Downstream Read Only 0: Open The result of the FSO PCC3300,
Valve driver output PCC3300V2
Command 1: Closed command logic for fuel
Status 2: Reserved shutoff valve 1

3: N/A
46117 Engine Oil Read Only 0: OFF Engine Oil pre heater PCC3300,
PreHeater command status PCC3300V2
Ctrl Status 1: ON
2: Reserved
3: N/A
4: Network
Failure
46120 Engine Read Only 0: OFF Engine coolant PCC3300,
Coolant circulating pump PCC3300V2
Pump Ctrl 1: ON status
Status 2: Reserved
3: N/A
4: Network
Failure
46124 Coolant Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Pressure Coolant Pressure. PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U

A029X159 (Issue 31) 771 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46125 Coolant 2 Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Pressure Coolant 2 Pressure. PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit: 145
Sign: U
46127 Coolant 2 Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Temperature Coolant 2 PCC3300V2
Offset: 0 Lower Limit: Temperature
Size (bits): 16 Upper Limit:
Sign: S
46128 Compressor Read Only Multiplier: 0.1 Unit: % Engine turbocharger PCC3300,
Bypass compressor bypass PCC3300V2
Position Offset: 0 Lower Limit: actuator position
Size (bits): 16 Upper Limit:
Sign: U
46130 Oil Priming Read Only 0: OFF Status for the priming PCC3300,
Pump pump (ON or OFF) PCC3300V2
Control 1: ON
Status 2: Reserved
3: N/A
4: Network
Failure
46131 Oil Priming Read Only 0: Low Status of the engine PCC3300,
State before start (Pre- PCC3300V2
1: Optimum Lubed or Not)
2: Reserved
3: N/A
4: Network
Failure
46133 Coolant Pre- Read Only 0: Cold Status of the engine PCC3300,
Heated State coolant before start PCC3300V2
1: Heated (Pre-Heated or Not)
2: Reserved
3: N/A
46135 Intake Read Only Multiplier: 0.1 Unit: psi Intake Manifold PCC3300,
Manifold Pressure 1 PCC3300V2
Pressure 1 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 772 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46136 Compressor Read Only Multiplier: 0.1 Unit: kPa Absolute Pressure at PCC3300,
Outlet the outlet of the PCC3300V2
Pressure Offset: 0 Lower Limit: compressor.
Size (bits): 16 Upper Limit:
Sign: U
46137 Turbocharger Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
1 Boost Turbocharger 1 Boost PCC3300V2
Pressure Offset: 0 Lower Limit: Pressure
Size (bits): 16 Upper Limit:
Sign: U
46139 Fuel Valve 1 Read Only Multiplier: 0.1 Unit: psi Absolute Pressure of PCC3300,
Inlet Gas on the inlet side PCC3300V2
Absolute Offset: 0 Lower Limit: of the first system
Pressure Size (bits): 16 Upper Limit: control valve

Sign: U
46140 Fuel Valve 1 Read Only Multiplier: 0.1 Unit: psi Absolute Pressure of PCC3300,
Outlet Gas on the outlet side PCC3300V2
Absolute Offset: 0 Lower Limit: of the first system
Pressure Size (bits): 16 Upper Limit: control valve

Sign: U
46141 Fuel Valve 1 Read Only Multiplier: 0.1 Unit: % PCC3300,
Position PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46142 Fuel Valve 2 Read Only Multiplier: 0.1 Unit: psi Absolute Pressure of PCC3300,
Inlet Gas on the inlet side PCC3300V2
Absolute Offset: 0 Lower Limit: of the second system
Pressure Size (bits): 16 Upper Limit: control valve

Sign: U
46143 Fuel Valve 2 Read Only Multiplier: 0.1 Unit: psi Absolute Pressure of PCC3300,
Outlet Gas on the outlet side PCC3300V2
Absolute Offset: 0 Lower Limit: of the second system
Pressure Size (bits): 16 Upper Limit: control valve

Sign: U
46144 Fuel Valve 2 Read Only Multiplier: 0.1 Unit: % PCC3300,
Position PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U

A029X159 (Issue 31) 773 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46145 Gas Mass Read Only Multiplier: 0.1 Unit: Pounds per Gas Mass Flow value PCC3300,
Flow hour of the engine. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
46146 Gas Mass Read Only Multiplier: 0.1 Unit: Pounds per Gas Mass Flow value PCC3300,
Flow hour of the engine. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
46147 Throttle 1 Read Only Multiplier: 0.1 Unit: % Position of the throttle PCC3300,
Position 1. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46148 Throttle 2 Read Only Multiplier: 0.1 Unit: % Position of the throttle PCC3300,
Position 2. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46155 MCM700 Read Only Multiplier: 0.1 Unit: Vdc Engine Control Module PCC3300,
Battery Battery Voltage. PCC3300V2
Voltage Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65535
Sign: U
46161 SSM558 1 Read Only Multiplier: 0.1 Unit: Vdc SSM558 1 Engine PCC3300,
Isolated Control Module PCC3300V2
Battery Offset: 0 Lower Limit: 0 Isolated Battery
Voltage Size (bits): 16 Upper Limit: Voltage.
65535
Sign: U
46163 SSM558 2 Read Only Multiplier: 0.1 Unit: Vdc SSM558 2 Engine PCC3300,
Isolated Control Module PCC3300V2
Battery Offset: 0 Lower Limit: 0 Isolated Battery
Voltage Size (bits): 16 Upper Limit: Voltage.
65535
Sign: U

Copyright © 2023 Cummins Inc. 774 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46164 Intake Read Only Multiplier: 0.1 Unit: psi Intake Manifold PCC3300,
Manifold Pressure 2 PCC3300V2
Pressure 2 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46166 Exhaust Read Only Multiplier: 0.1 Unit: psi Monitor point for PCC3300,
Back exhaust back pressure PCC3300V2
Pressure Offset: 0 Lower Limit: value
Size (bits): 16 Upper Limit:
Sign: U
46168 Air Filter Read Only Multiplier: 0.1 Unit: psi Monitor point for air PCC3300,
Differential filter differential PCC3300V2
Pressure Offset: 0 Lower Limit: pressure value
Size (bits): 16 Upper Limit:
Sign: S
46170 Gas Mass Read Only Multiplier: 0.1 Unit: Pounds per Gas Mass Flow 2 PCC3300,
Flow 2 hour value of the engine. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
46171 Gas Mass Read Only Multiplier: 0.1 Unit: Pounds per Gas Mass Flow 2 PCC3300,
Flow 2 hour value of the engine. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
46172 Start Inhibit Read Only 0: Inactive Start Inhibit No1 Op PCC3300,
No1 Op monitor point. PCC3300V2
1: Active
2: Reserved
3: Not Available
4: Network
Failure
46173 Start Inhibit Read Only 0: Inactive Start Inhibit No2 Op PCC3300,
No2 Op monitor point. PCC3300V2
1: Active
2: Reserved
3: Not Available
4: Network
Failure

A029X159 (Issue 31) 775 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46174 Start Inhibit Read Only 0: Inactive Start Inhibit No3 Op PCC3300,
No3 Op monitor point. PCC3300V2
1: Active
2: Reserved
3: Not Available
4: Network
Failure
46182 Radiator Fan Read Only 0: Inactive Radiator fan control PCC3300,
control command PCC3300V2
1: Active
46183 Ventilator Read/Write 0: Limited Vent fan control mode, PCC3300,
Fan mode limited or continuous PCC3300V2
1: Continuous
46184 Louvre Read Only 0: Inactive Louvre control PCC3300,
Control PCC3300V2
1: Active
46191 Ventilator Read Only 0: Inactive Ventilator fan control PCC3300,
Fan control command PCC3300V2
1: Active
46192 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 1 PCC3300V2
1 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46193 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 2 PCC3300V2
2 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46194 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 3 PCC3300V2
3 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46195 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 4 PCC3300V2
4 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U

Copyright © 2023 Cummins Inc. 776 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46196 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 5 PCC3300V2
5 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46197 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 6 PCC3300V2
6 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46198 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 7 PCC3300V2
7 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46199 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 8 PCC3300V2
8 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46200 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 9 PCC3300V2
9 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46201 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 10 PCC3300V2
10 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46202 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 11 PCC3300V2
11 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46203 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 12 PCC3300V2
12 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U

A029X159 (Issue 31) 777 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46204 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 13 PCC3300V2
13 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46205 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 14 PCC3300V2
14 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46206 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 15 PCC3300V2
15 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46207 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 16 PCC3300V2
16 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46208 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 17 PCC3300V2
17 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46209 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 18 PCC3300V2
18 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46221 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46222 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C

Copyright © 2023 Cummins Inc. 778 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46223 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46224 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46225 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46226 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46227 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46228 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46229 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46230 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C

A029X159 (Issue 31) 779 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46288 DE/NDE Read/Write 0: Drive End Gives reference point PCC3300,
Cylinder for engine cylinder PCC3300V2
Viewpoint 1: Non-Drive End numbering
Reference 2: Reserved
3: N/A
46289 Start System Read Only 0: Not Tripped Start system trip PCC3300,
Trip (Aux monitor point. PCC3300V2
101) 1: Tripped
2: Reserved
3: N/A
4: Network
Failure
46290 Louvres Read Only 0: Open Louvres Closed PCC3300,
Closed (Aux monitor point. PCC3300V2
101) 1: Closed
2: Reserved
3: N/A
4: Network
Failure
46291 Radiator Fan Read Only 0: Not Tripped Radiator Fan Trip PCC3300,
Trip (Aux monitor point. PCC3300V2
101) 1: Tripped
2: Reserved
3: N/A
4: Network
Failure
46300 LBNG Read/Write 0: Disable Switch to enable or PCC3300,
Genset disable the gas PCC3300V2
Enable 1: Enable specific features and
parameters
46301 Aux101-3 Read/Write 0: Disable Enable the processing PCC3300,
Enable for Aux101-3 PCC3300V2
1: Enable messages
46302 Aux101-4 Read/Write 0: Disable Enable the processing PCC3300,
Enable for Aux101-4 PCC3300V2
1: Enable messages
46303 Aux101-5 Read/Write 0: Disable Enable the processing PCC3300,
Enable for Aux101-5 PCC3300V2
1: Enable messages
46304 Aux101-6 Read/Write 0: Disable Enable the processing PCC3300,
Enable for Aux101-6 PCC3300V2
1: Enable messages

Copyright © 2023 Cummins Inc. 780 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46308 Aux101-3 Read Only Multiplier: 1 Unit: Input Port PCC3300,
Input Port configuration bye for PCC3300V2
Config Offset: 0 Lower Limit: 0 the Aux101-3
Size (bits): 16 Upper Limit: 255
Sign: U
46309 Aux101-4 Read Only Multiplier: 1 Unit: Input Port PCC3300,
Input Port configuration bye for PCC3300V2
Config Offset: 0 Lower Limit: 0 the Aux101-4
Size (bits): 16 Upper Limit: 255
Sign: U
46310 Aux101-5 Read Only Multiplier: 1 Unit: Input Port PCC3300,
Input Port configuration bye for PCC3300V2
Config Offset: 0 Lower Limit: 0 the Aux101-5
Size (bits): 16 Upper Limit: 255
Sign: U
46311 Aux101-3 DI Read Only Multiplier: 1 Unit: Digital Input Port PCC3300,
Active configuration active PCC3300V2
High/Low Offset: 0 Lower Limit: 0 High or active low for
Selection Size (bits): 16 Upper Limit: 255 the Aux101-3
Sign: U
46312 Aux101-4 DI Read Only Multiplier: 1 Unit: Digital Input Port PCC3300,
Active configuration active PCC3300V2
High/Low Offset: 0 Lower Limit: 0 High or active low for
Selection Size (bits): 16 Upper Limit: 255 the Aux101-4
Sign: U
46313 Aux101-5 DI Read Only Multiplier: 1 Unit: Digital Input Port PCC3300,
Active configuration active PCC3300V2
High/Low Offset: 0 Lower Limit: 0 High or active low for
Selection Size (bits): 16 Upper Limit: 255 the Aux101-5
Sign: U
46314 Aux101-3 DI Read Only Multiplier: 1 Unit: Discrete Input PCC3300,
Config Mask configuration bit mask PCC3300V2
Offset: 0 Lower Limit: 0 for the Aux101-3
Size (bits): 16 Upper Limit: 255
Sign: U
46315 Aux101-4 DI Read Only Multiplier: 1 Unit: Discrete Input PCC3300,
Config Mask configuration bit mask PCC3300V2
Offset: 0 Lower Limit: 0 for the Aux101-4
Size (bits): 16 Upper Limit: 255
Sign: U

A029X159 (Issue 31) 781 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46316 Aux101-5 DI Read Only Multiplier: 1 Unit: Discrete Input PCC3300,
Config Mask configuration bit mask PCC3300V2
Offset: 0 Lower Limit: 0 for the Aux101-5
Size (bits): 16 Upper Limit: 255
Sign: U
46323 Vehicle Read/Write 0: Disabled A trim that enables the PCC3300,
Electrical Vehicle Electrical PCC3300V2
Power 2 1: Enabled Power 2 message
PGN65165
Enable
46326 Gaseous Read/Write 0: Disabled A trim that enables the PCC3300,
Fuel Gaseous Fuel PCC3300V2
Pressure 1: Enabled Pressure message
PGN65163
Enable
46327 Fuel Read/Write 0: Disabled A trim that enables the PCC3300,
Information 3 Fuel Information 3 - PCC3300V2
- Gaseous 1: Enabled Gaseous message
PGN64930
Enable
46328 Fuel Read/Write 0: Disabled A trim that enables the PCC3300,
Information 2 Fuel Information 2 - PCC3300V2
- Gaseous 1: Enabled Gaseous message
PGN65153
Enable
46332 Inlet/Exhaust Read/Write 0: Disabled A trim that enables the PCC3300,
Conditions Inlet/Exhaust PCC3300V2
PGN65270 1: Enabled Conditions message
Enable
46333 Knock Count Read/Write 0: Disabled A trim that enables PCC3300,
1 PGN65336 Knock Count 1 PCC3300V2
Enable 1: Enabled message
46334 Knock Count Read/Write 0: Disabled A trim that enables PCC3300,
2 PGN65337 Knock Count 2 PCC3300V2
Enable 1: Enabled message
46335 Knock Count Read/Write 0: Disabled A trim that enables PCC3300,
3 PGN65338 Knock Count 3 PCC3300V2
Enable 1: Enabled message
46336 Knock Count Read/Write 0: Disabled A trim that enables PCC3300,
4 PGN65339 Knock Count 4 PCC3300V2
Enable 1: Enabled message
46337 Knock Count Read/Write 0: Disabled A trim that enables PCC3300,
5 PGN65340 Knock Count 5 PCC3300V2
Enable 1: Enabled message

Copyright © 2023 Cummins Inc. 782 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46338 Ignition Read/Write 0: Disabled A trim that enables the PCC3300,
Timing 1 Ignition Timing 1 PCC3300V2
PGN65154 1: Enabled message
Enable
46339 Ignition Read/Write 0: Disabled A trim that enables the PCC3300,
Timing 2 Ignition Timing 2 PCC3300V2
PGN65155 1: Enabled message
Enable
46340 Ignition Read/Write 0: Disabled A trim that enables the PCC3300,
Timing 3 Ignition Timing 3 PCC3300V2
PGN65156 1: Enabled message
Enable
46341 Ignition Read/Write 0: Disabled A trim that enables the PCC3300,
Timing 4 Ignition Timing 4 PCC3300V2
PGN65157 1: Enabled message
Enable
46342 Ignition Read/Write 0: Disabled A trim that enables the PCC3300,
Timing 5 Ignition Timing 5 PCC3300V2
PGN65158 1: Enabled message
Enable
46344 Start-Enable Read/Write 0: Disable Remote MODBUS PCC3300,
(MODBUS Start-Enable input. PCC3300V2
Input) 1: Enable

46364 Modbus Read/Write 0: Disable Modbus Register PCC3300,


Register Read Only Enable For PCC2300,
Read Only 1: Enable TB15 Modbus PCC3300V2
Enable Communication Port.
46365 Modbus Read/Write 0: Disable Modbus Register PCC3300,
Register Read Only Enable For PCC3300V2
Read Only 1: Enable J14 Modbus
Enable (J14) Communication Port.
46366 Modbus Stop Read/Write 0: 1 Sets the modbus PCC3300,
Bits (J14) number of stop bits for PCC3300V2
1: 2 this node Limited to 1
bit if parity = Odd or
Even
46367 Modbus Bus Read Only Multiplier: 1 Unit: The number of PCC3300,
Message modbus messages PCC3300V2
Count (J14) Offset: 0 Lower Limit: with no response, for
Size (bits): 16 Upper Limit: J14 port only

Sign: U

A029X159 (Issue 31) 783 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46368 Modbus CRC Read Only Multiplier: 1 Unit: The number of PCC3300,
Error Count modbus CRC errors, PCC3300V2
(J14) Offset: 0 Lower Limit: for J14 only.
Size (bits): 16 Upper Limit:
Sign: U
46369 Modbus Read Only Multiplier: 1 Unit: Modbus exception PCC3300,
Exception count, for J14 only. PCC3300V2
Count (J14) Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46370 Modbus No Read Only Multiplier: 1 Unit: Modbus no response PCC3300,
Response count, for J14 only. PCC3300V2
Count (J14) Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46371 Modbus Read Only Multiplier: 1 Unit: The number of PCC3300,
Slave modbus slave PCC3300V2
Message Offset: 0 Lower Limit: messages, for J14
Count (J14) Size (bits): 16 Upper Limit: only.

Sign: U
46372 Modbus Read/Write Multiplier: 1 Unit: Sets the modbus PCC3300,
Node address for this node, PCC3300V2
Address Offset: 0 Lower Limit: 1 for J14 only.
(J14) Size (bits): 8 Upper Limit: 247
Sign: U
46373 Modbus Read/Write 0: 2400 Sets the baud rate for PCC3300,
Baud Rate modbus PCC3300V2
(J14) 1: 4800 communications, for
2: 9600 J14 only.

3: 19200
46374 Modbus Read/Write 0: Even Sets the modbus PCC3300,
Parity (J14) parity for this node, for PCC3300V2
1: Odd J14 only.
2: None
46376 Modbus Read/Write 0: 2400 Baud Sets the modbus baud PCC3300,
Baud Rate rate. PCC2300,
1: 4800 Baud PCC3300V2
2: 9600 Baud
3: 19200 Baud
4: 38400 Baud

Copyright © 2023 Cummins Inc. 784 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46377 Modbus Read/Write 0: Even Sets the modbus PCC3300,
Parity parity for this node PCC2300,
1: Odd PCC3300V2
2: None
46378 Modbus Read/Write Multiplier: 1 Unit: Sets the modbus PCC3300,
Node address for this node PCC2300,
Address Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 8 Upper Limit: 247
Sign: U
46379 Modbus Stop Read/Write 0: 1 Sets the modbus PCC3300,
Bits number of stop bits for PCC2300,
1: 2 this node Limited to 1 PCC3300V2
bit if parity = Odd or
Even
46380 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46381 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46382 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46383 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46384 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

A029X159 (Issue 31) 785 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46385 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46386 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46387 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46388 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46389 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46390 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46391 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46392 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C

Copyright © 2023 Cummins Inc. 786 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46393 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46394 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46395 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46396 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46397 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46398 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46399 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.

Sign: C
46600 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 787 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46601 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46602 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46603 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46604 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46605 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46606 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46607 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46608 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 788 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46609 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46610 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46611 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46612 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46613 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46614 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46615 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46616 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 789 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46617 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46618 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46619 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46620 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46621 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46622 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46623 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46624 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 790 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46625 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

TABLE 44.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46626 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46627 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46628 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46629 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46630 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46631 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 791 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46632 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46633 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46634 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46635 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46636 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46637 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46638 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46639 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 792 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46640 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46641 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46642 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46643 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46644 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46645 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46646 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46647 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 793 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46648 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46649 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46650 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46651 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46652 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46653 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46654 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46655 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 794 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46656 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46657 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46658 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46659 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46660 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46661 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46662 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46663 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 795 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46664 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46665 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46666 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46667 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46668 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46669 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46670 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46671 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 796 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46672 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46673 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46674 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46675 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46676 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46677 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46678 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46679 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 797 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46800 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46801 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46802 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46803 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46804 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46805 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46806 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46807 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 798 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46808 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46809 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46810 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46811 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46812 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46813 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46814 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46815 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 799 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46816 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46817 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46818 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46819 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46820 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46821 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46822 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46823 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 800 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46824 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46825 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46826 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46827 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46828 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46829 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46830 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46831 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 801 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46832 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46833 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46834 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46835 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46836 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46837 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46838 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46839 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 802 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46840 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46841 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46842 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46843 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46844 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46845 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46846 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46847 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 803 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46848 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46849 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46850 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46851 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46852 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46853 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46854 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46855 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 804 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46856 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46857 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46858 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46859 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46860 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46861 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46862 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46863 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 805 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46864 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46865 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46866 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46867 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46868 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46869 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46870 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46871 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 806 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46872 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46873 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46874 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46875 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46876 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46877 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46878 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46879 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 807 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46880 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46881 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46882 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46883 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46884 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46885 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46886 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46887 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 808 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46888 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46889 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46890 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46891 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46892 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46893 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46894 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46895 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 809 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46896 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46897 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46898 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46899 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46900 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46901 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46902 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46903 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 810 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46904 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46905 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46906 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46907 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46908 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46909 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46910 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46911 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 811 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46912 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46913 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46914 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46915 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46916 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46917 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

TABLE 45.

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46918 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 812 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46919 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46920 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46921 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46922 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46923 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46924 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46925 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46926 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 813 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46927 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46928 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46929 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46930 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46931 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46932 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46933 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46934 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 814 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46935 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46936 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46937 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46938 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46939 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46940 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46941 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46942 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 815 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46943 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46944 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46945 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46946 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46947 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46948 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46949 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46950 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 816 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46951 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46952 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46953 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46954 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46955 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46956 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46957 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46958 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 817 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46959 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46960 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46961 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46962 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46963 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46964 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46965 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46966 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 818 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46967 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46968 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46969 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46970 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46971 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46972 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46973 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46974 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 819 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46975 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46976 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46977 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46978 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46979 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46980 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46981 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46982 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 820 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46983 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46984 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46985 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46986 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46987 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46988 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46989 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46990 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

A029X159 (Issue 31) 821 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46991 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46992 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46993 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46994 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46995 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46996 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46997 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46998 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C

Copyright © 2023 Cummins Inc. 822 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46999 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
47002 GK1 (60Hz) Read Only Multiplier: 1 Unit: The governor 60Hz K1 PCC3300,
gain adjust. MODBUS PCC3300V2
Offset: 0 Lower Limit: 0 Access: Read Only
Size (bits): 16 Upper Limit:
65530
Sign: U
47003 GK2 (60Hz) Read Only Multiplier: 1 Unit: The governor 60Hz PCC3300,
integral gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS Access:
Size (bits): 16 Upper Limit: Read Only
65530
Sign: U
47004 GK3 (60Hz) Read Only Multiplier: 1 Unit: The governor 60Hz K3 PCC3300,
gain adjust. MODBUS PCC3300V2
Offset: 0 Lower Limit: 0 Access: Read Only
Size (bits): 16 Upper Limit:
65530
Sign: U
47005 Governor Read Only Multiplier: Unit: The governor 60Hz PCC3300,
Damping 1.52587890625E damping adjust. PCC3300V2
Effect (60Hz) -05 MODBUS
Access:Read Only
Offset: 0 Lower Limit: 0.6
Size (bits): 16 Upper Limit: 0.95
Sign: U
47006 GK1 (50Hz) Read Only Multiplier: 1 Unit: The governor 50Hz K1 PCC3300,
gain adjust. MODBUS PCC3300V2
Offset: 0 Lower Limit: 0 Access: Read Only
Size (bits): 16 Upper Limit:
65530
Sign: U
47007 GK2 (50Hz) Read Only Multiplier: 1 Unit: The governor 50Hz PCC3300,
integral gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS Access:
Size (bits): 16 Upper Limit: Read Only
65530
Sign: U

A029X159 (Issue 31) 823 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47008 GK3 (50Hz) Read Only Multiplier: 1 Unit: The governor 50Hz K3 PCC3300,
gain adjust. MODBUS PCC3300V2
Offset: 0 Lower Limit: 0 Access: Read Only
Size (bits): 16 Upper Limit:
65530
Sign: U
47009 Governor Read Only Multiplier: Unit: The governor 50Hz PCC3300,
Damping 1.52587890625E damping adjust. PCC3300V2
Effect (50Hz) -05 MODBUS
Access:Read Only
Offset: 0 Lower Limit: 0.6
Size (bits): 16 Upper Limit: 0.95
Sign: U
47010 GK1(Idle) Read Only Multiplier: 1 Unit: This trim is used to PCC3300,
adjust gk1 in idle PCC3300V2
Offset: 0 Lower Limit: 0 mode. MODBUS
Size (bits): 16 Upper Limit: Access:Read Only
65530
Sign: U
47011 GK2(Idle) Read Only Multiplier: 1 Unit: This trim is used to PCC3300,
adjust gk2 in idle PCC3300V2
Offset: 0 Lower Limit: 0 mode. MODBUS
Size (bits): 16 Upper Limit: Access: Read Only
65530
Sign: U
47014 Gain Read Only 0: Disable Either enables or PCC3300,
Windowing disables Gain PCC3300V2
Enable 1: Enable Windowing feature.
MODBUS
Access:Read Only
47015 GK1 Read Only Multiplier: 1 Unit: The governor 50Hz K1 PCC3300,
Low(50Hz) low gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS Access:
Size (bits): 16 Upper Limit: Read Only
65530
Sign: U
47016 GK1 Read Only Multiplier: 1 Unit: The governor 60Hz K1 PCC3300,
Low(60Hz) low gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS Access:
Size (bits): 16 Upper Limit: Read Only
65530
Sign: U

Copyright © 2023 Cummins Inc. 824 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47017 GK1 Read Only Multiplier: 1 Unit: The governor 50Hz K1 PCC3300,
High(50Hz) high gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS
Size (bits): 16 Upper Limit: Access:Read Only
65530
Sign: U
47018 GK1 Read Only Multiplier: 1 Unit: The governor 60Hz K1 PCC3300,
High(60Hz) high gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS
Size (bits): 16 Upper Limit: Access:Read Only
65530
Sign: U
47019 Governor Read Only Multiplier: 1 Unit: The speed error PCC3300,
Speed Delta higher limit. MODBUS PCC3300V2
High Offset: 0 Lower Limit: 50 Access:Read Only
Size (bits): 16 Upper Limit:
1000
Sign: U
47020 Governor Read Only Multiplier: 1 Unit: The speed error lower PCC3300,
Speed Delta limit. MODBUS PCC3300V2
Low Offset: 0 Lower Limit: 50 Access: Read Only
Size (bits): 16 Upper Limit:
1000
Sign: U
47021 Intake Read Only 0: PGBU Either PGBU (Onan) PCC3300,
Manifold or EBU (Cummins) PCC3300V2
Temperature 1: EBU sensor. MODBUS
Sensor Type Access : Read Only
47022 Intake Read Only 0: Disable Intake Manifold Temp PCC3300,
Manifold Sensor available or PCC3300V2
Temperature 1: Enable not. MODBUS
Sensor Access : Read Only
Enable
47023 Oil Read Only 0: PGBU Either PGBU(Onan) or PCC3300,
Temperature EBU(Cummins) PCC3300V2
Sensor Type 1: EBU sensor.
47024 Oil Read Only 0: Disable High Oil Temperature PCC3300,
Temperature Sensor available or PCC3300V2
Sensor 1: Enable not.
Enable

A029X159 (Issue 31) 825 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47025 AVR PWM Read Only Multiplier: 0.01 Unit: % The AVR PWM PCC3300,
Command software command. PCC2300,
Offset: 0 Lower Limit: Linear relationship PCC3300V2
Size (bits): 16 Upper Limit: between counts and %
duty cycle with 10000
Sign: U counts=100% duty
cycle. MODBUS
Access : Read Only
47026 Coolant Read Only 0: Disable Coolant Temperature PCC3300,
Temperature 2 Enable PCC3300V2
2 Enable 1: Enable

47027 Start Inhibit Read Only Multiplier: 0.05 Unit: sec Delay progress until a PCC3300,
Delay fault is declared for PCC3300V2
Progress Offset: 0 Lower Limit: start inhibit
Size (bits): 16 Upper Limit:
Sign: U
47028 Genset Read Only 0: Close Indicates the Genset PCC3300,
Voltage Voltage sensing MCB PCC3300V2
Sensing 1: Open status.
MCB status 2: Reserved
3: N/A
4: Network
Failure
47029 Customer Read Only 0: Open Indicates the status of PCC3300,
Gas Valve the Customer Gas PCC3300V2
Status 1: Closed Valve position.
2: Reserved
3: N/A
4: Network
Failure
47030 Crankcase Read Only Multiplier: 0.01 Unit: psi Monitor point for the PCC3300,
Pressure Crankcase Pressure PCC2300,
Extended Offset: 0 Lower Limit: with extended PCC3300V2
-35.67 precision.
Size (bits): 16 Upper Limit: 38
Sign: S
47031 Throttle Delta Read Only Multiplier: 0.1 Unit: psi "The differential PCC3300,
Pressure pressure between the PCC3300V2
Offset: 0 Lower Limit: 0 intake and outlet of a
Size (bits): 16 Upper Limit: throttle valve"
6425.5
Sign: U

Copyright © 2023 Cummins Inc. 826 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47033 Engine Read Only Multiplier: 0.1 Unit: degF Intake temperature of PCC3300,
Turbocharger engine turbocharger 1 PCC3300V2
1 Offset: 0 Lower Limit: -273 compressor.
Compressor Size (bits): 16 Upper Limit:
Intake 1734.968
Temperature
Sign: S
47048 Intake Read/Write 0: Disabled "Trim to enable the PCC2300,
Manifold detection of Intake PCC3300,
Over 1: Enabled Manifold Backfire PCC3300V2
Pressure(IM condition"
OP) Enable
47049 Intake Read/Write 0: SPN 105 "Source for Intake PCC2300,
Manifold Manifold Temperature. PCC3300,
Temperature 1: SPN 52 SPN 105 Default PCC3300V2
Source Source and SPN 52
when the IMOP is
Enabled"
47050 Intake Read/Write Multiplier: 0.1 Unit: degF/secs "Threshold to decide PCC2300,
Manifold the Intake Manifold PCC3300,
Temp Rate Offset: 0 Lower Limit: 2 Backfire condition, PCC3300V2
of Change Size (bits): 8 Upper Limit: 20 Value entered is for
Threshold degF/secs,
Sign: U degF/2secs is
obtained by a scalar of
2 in PCC software "
47051 Gas Read Only Multiplier: 0.1 Unit: degF This parameter is to PCC3300,
Temperature display engine gas PCC3300V2
Offset: 0 Lower Limit: fuel temperature
Size (bits): 16 Upper Limit:
Sign: S
47052 Turbocharger Read Only Multiplier: 0.1 Unit: % To display engine PCC3300,
Wastegate turbocharger PCC3300V2
Position Offset: 0 Lower Limit: wastegate position
Size (bits): 16 Upper Limit:
Sign: U
47100 AT DEF Read Only Multiplier: 0.1 Unit: % "After Treatment PCC3300V2
Tank Level Diesel Exhaust Fluid
Offset: 0 Lower Limit: 0 Tank Level"
Size (bits): 16 Upper Limit:
Sign: U

A029X159 (Issue 31) 827 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47101 AT DEF Read Only Multiplier: 0.01 Unit: % "After Treatment PCC3300V2
Concentratio Diesel Exhaust Fluid
n Offset: 0 Lower Limit: 0 Concentration"
Size (bits): 16 Upper Limit:
Sign: U
47102 AT DEF Read Only Multiplier: 0.1 Unit: degF "After Treatment PCC3300V2
Tank Diesel Exhaust Fluid
Temperature Offset: 0 Lower Limit: -40 Tank Temperature"
Size (bits): 16 Upper Limit:
Sign: S
47103 AT SCR Read Only Multiplier: 0.1 Unit: degF "After Treatment SCR PCC3300V2
Catalyst Catalyst Outlet Gas
Outlet Gas Offset: 0 Lower Limit: Temperature"
Temperature -459.4
Size (bits): 16 Upper Limit:
Sign: S
47104 AT 1 DEF Read Only 0: OFF Driver's warning PCC3300V2
Tank 1 Low indicator for diesel
Level 1: ON Solid exhaust fluid (DEF)
Indicator 2: ON Fast Blink tank low level

3: Not Available
4: Network
Failure
47105 Operator Read Only Multiplier: 1 Unit: Minutes Monitor point for Time PCC3300V2
Inducement To Torque Derate
Time To Offset: 0 Lower Limit: Level 1
Torque Size (bits): 16 Upper Limit:
Derate Level
1 Sign: U

47106 Operator Read Only Multiplier: 1 Unit: Minutes Monitor point for Time PCC3300V2
Inducement To Torque Derate
Time To Offset: 0 Lower Limit: Level 2
Torque Size (bits): 16 Upper Limit:
Derate Level
2 Sign: U

47107 Operator Read Only Multiplier: 1 Unit: Minutes Monitor point for Time PCC3300V2
Inducement To Final Inducement
Time To Offset: 0 Lower Limit: Action
Final Size (bits): 16 Upper Limit:
Inducement
Action Sign: U

Copyright © 2023 Cummins Inc. 828 A029X159 (Issue 31)


8-2023 14. PowerCommand 2.x/3.x Modbus Register Map

Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47108 AT 1 DEF Read Only Multiplier: 0.3 Unit: g/hr '"Monitor Point for PCC3300V2
Actual Urea dosing-1 (Leg-1)
Dosing Offset: 0 Lower Limit: 0 (grams/hour)"
Quantity Size (bits): 16 Upper Limit:
19277
Sign: U
47109 AT 2 DEF Read Only Multiplier: 0.3 Unit: g/hr '"Monitor Point for PCC3300V2
Actual Urea dosing-2 (Leg-2)
Dosing Offset: 0 Lower Limit: 0 (grams/hour)"
Quantity Size (bits): 16 Upper Limit:
19277
Sign: U
47110 AT 2 SCR Read Only Multiplier: 0.1 Unit: degF '"Monitor Point for PCC3300V2
Catalyst SCR out Temperature-
Outlet Gas Offset: 0 Lower Limit: 2 (Leg-2)"
Temperature -459.4
Size (bits): 16 Upper Limit:
3155
Sign: S

A029X159 (Issue 31) 829 Copyright © 2023 Cummins Inc.


14. PowerCommand 2.x/3.x Modbus Register Map 8-2023

This page is intentionally blank.

Copyright © 2023 Cummins Inc. 830 A029X159 (Issue 31)


15 PowerCommand 2.x/3.x/PS0500
Modbus Fault Status Bitmaps
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.

NOTICE
If an address or bit is not listed in this table it is not implemented.

NOTICE
The Master device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.

TABLE 46.

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Engine Magnetic Crankshaft PCC3300,
40400 0 Bitmap 1 115 Speed/Position Shutdown PCC2300,
PCC3300V2
Fault Status Intake Manifold 1 PCC3300,
40400 1 Bitmap 1 122 Pressure:Vtg Above Normal Warning PCC2300,
PCC3300V2
Fault Status Intake Manifold 1 PCC3300,
40400 2 Bitmap 1 123 Pressure:Vtg Below Normal Warning PCC2300,
PCC3300V2
Fault Status Intake Manifold 1 PCC3300,
40400 3 Bitmap 1 124 Pressure:Moderately Warning PCC2300,
Severe PCC3300V2
Fault Status Engine Oil Rifle Pressure PCC3300,
40400 4 Bitmap 1 135 1:Vtg Above Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Oil Rifle Pressure PCC3300,
40400 5 Bitmap 1 141 1:Vtg Below Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Oil Rifle Pressure - PCC3300,
40400 6 Bitmap 1 143 Moderately Severe Warning PCC2300,
PCC3300V2
Fault Status Engine Coolant Temp 1:Vtg PCC3300,
40400 7 Bitmap 1 144 Above Normal Warning PCC2300,
PCC3300V2

A029X159 (Issue 31) 831 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Engine Coolant Temp 1:Vtg PCC3300,
40400 8 Bitmap 1 145 Below Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Coolant PCC3300,
40400 9 Bitmap 1 146 Temp:Moderately Above Derate PCC2300,
Normal PCC3300V2
Fault Status Engine Coolant PCC3300,
40400 10 Bitmap 1 151 Temp:Severely Above Shutdown PCC2300,
Normal PCC3300V2
Fault Status High Coolant Temp PS0500
40400 1 151 Shutdown
Bitmap 1 Shutdown
Fault Status Intake Manifold 1 Temp:Vtg PCC3300,
40400 11 Bitmap 1 153 Above Normal Warning PCC2300,
PCC3300V2
Fault Status Intake Manifold 1 Temp:Vtg PCC3300,
40400 12 Bitmap 1 154 Below Normal Warning PCC2300,
PCC3300V2
Fault Status Intake Manifold 1 PCC3300,
40400 13 Bitmap 1 155 Temp:Severely Above Shutdown PCC2300,
Normal PCC3300V2
Fault Status Sensor Supply 2:Vtg Below PCC3300,
40400 14 Bitmap 1 187 Normal Warning PCC2300,
PCC3300V2
Fault Status Coolant Level Sensor 1:Vtg PCC3300,
40400 15 Bitmap 1 195 Above Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Overspeed PS0500
40400 8 234 Shutdown
Bitmap 1
Fault Status Fail to Start Fault PS0500
40400 10 359 Shutdown
Bitmap 1
Fault Status Low Oil Pressure Shutdown PS0500
40400 2 415 Shutdown
Bitmap 1
Fault Status Shutdown After Battleshort PS0500
40400 11 1123 Shutdown
Bitmap 1
Fault Status Remote E-Stop Fault PS0500
40400 9 1434 Shutdown
Bitmap 1
Fault Status High AC Voltage PS0500
40400 3 1446 Shutdown
Bitmap 1
Fault Status Low AC Voltage PS0500
40400 4 1447 Shutdown
Bitmap 1
Fault Status Underfrequency PS0500
40400 6 1448 Shutdown
Bitmap 1

Copyright © 2023 Cummins Inc. 832 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Overfrequency PS0500
40400 5 1449 Shutdown
Bitmap 1
Fault Status High Current Shutdown PS0500
40400 13 1472 Shutdown
Bitmap 1
Fault Status Common Shutdown PS0500
40400 15 1541 Shutdown
Bitmap 1
Fault Status Loss of AC Voltage Sensing PS0500
40400 7 2335 Shutdown
Bitmap 1
Fault Status Fail To Stop PS0500
40400 0 2677 Shutdown
Bitmap 1
Fault Status Genset CT Ratio Too Small PS0500
40400 14 2814 Shutdown
Bitmap 1
Fault Status MB Network PS0500
40400 12 4799 Shutdown
Bitmap 1
Fault Status Coolant Level Sensor 1:Vtg PCC3300,
40401 0 Bitmap 2 196 Below Normal Warning PCC2300,
PCC3300V2
Fault Status Coolant Level:Below PCC3300,
40401 1 Bitmap 2 197 Normal - Moderately Severe Warning PCC2300,
PCC3300V2
Fault Status Engine Oil Temp Sensor PCC3300,
40401 2 Bitmap 2 212 1:Vtg Above Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Oil Temp Sensor PCC3300,
40401 3 Bitmap 2 213 1:Vtg below Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Oil Temp:Above PCC3300,
40401 4 Bitmap 2 214 Normal - Most severe Shutdown PCC2300,
PCC3300V2
Fault Status Barometric Pressure:Vtg PCC3300,
40401 5 Bitmap 2 221 Above Normal Warning PCC2300,
PCC3300V2
Fault Status Barometric Pressure PCC3300,
40401 6 Bitmap 2 222 Sensor:Vtg Below Normal Warning PCC2300,
PCC3300V2
Fault Status Eng Oil Burn Valve PCC3300,
40401 7 Bitmap 2 223 Solenoid:Vtg Below Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Oil Burn Valve PCC3300,
40401 8 Bitmap 2 224 Solenoid:Vtg Above Normal Warning PCC2300,
PCC3300V2
Fault Status Sensor Supply 2:Vtg Above PCC3300,
40401 9 Bitmap 2 227 Normal Warning PCC2300,
PCC3300V2

A029X159 (Issue 31) 833 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Coolant Pressure:Below PCC3300,
40401 10 Bitmap 2 228 Normal-Most Severe Shutdown PCC2300,
PCC3300V2
Fault Status Coolant Pressure PCC3300,
40401 11 Bitmap 2 231 Sensor:Vtg Above Normal Warning PCC2300,
PCC3300V2
Fault Status Coolant Pressure PCC3300,
40401 12 Bitmap 2 232 Sensor:Vtg Below Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Crankshaft PCC3300,
40401 13 Bitmap 2 234 Speed/Posn:Above Normal Shutdown PCC2300,
PCC3300V2
Fault Status Coolant Level:Below PCC3300,
40401 14 Bitmap 2 235 Normal-Most Severe Shutdown PCC2300,
PCC3300V2
Fault Status Sensor Supply 3:Vtg Below PCC3300,
40401 15 Bitmap 2 238 Normal Warning PCC2300,
PCC3300V2
Fault Status Voltage Supply 3 High Error PCC3300,
40402 0 Bitmap 3 239 Warning PCC2300,
PCC3300V2
Fault Status Radiator Fan Control Driver PCC3300,
40402 1 Bitmap 3 245 Low Error Warning PCC2300,
PCC3300V2
Fault Status Engine Fuel Temp:Above PCC3300,
40402 2 Bitmap 3 261 Normal-Moderately Severe Warning PCC2300,
PCC3300V2
Fault Status Engine Fuel Temp Sensor PCC3300,
40402 3 Bitmap 3 263 1:Vtg Above Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Fuel Temp Sensor PCC3300,
40402 4 Bitmap 3 265 1:Vtg Below Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Fuel Temp:Above PCC3300,
40402 5 Bitmap 3 266 Normal-Most severe Shutdown PCC2300,
PCC3300V2
Fault Status Fuel Pump Pressurizing PCC3300,
40402 6 Bitmap 3 271 Assembly 1:Vtg Below Warning PCC2300,
Normal PCC3300V2
Fault Status Fuel Pump Pressurizing PCC3300,
40402 7 Bitmap 3 272 Assembly 1:Vtg Above Warning PCC2300,
Normal PCC3300V2
Fault Status APC_DIESEL_CYL_PRS_I PCC3300,
40402 8 Bitmap 3 281 MBAL_ERROR Warning PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 834 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status SAE J1939 Muxing PGN PCC3300,
40402 9 Bitmap 3 285 Timeout:Abnormal Update Warning PCC2300,
Rate PCC3300V2
Fault Status SAE J1939 Muxing PCC3300,
40402 10 Bitmap 3 286 Config:Out of Calibration Warning PCC2300,
PCC3300V2
Fault Status Intake Manifold Over PCC3300,
40402 11 Bitmap 3 5669 Pressure - Condition Exists Shutdown PCC2300,
PCC3300V2
Fault Status AMBIENT_AIR_PRESS_KE PCC3300,
40402 13 Bitmap 3 295 YON_ERROR Warning PCC2300,
PCC3300V2
Fault Status RTC PWR Intr:Data Erratic PCC3300,
40402 14 Bitmap 3 319 Intermittent or Wrong Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40402 15 Bitmap 3 322 Cylinder 1:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40403 0 Bitmap 4 323 Cylinder 5:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40403 1 Bitmap 4 324 Cylinder 3:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40403 2 Bitmap 4 325 Cylinder 6:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40403 3 Bitmap 4 331 Cylinder 2:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40403 4 Bitmap 4 332 Cylinder 4:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Electronic Calibration PCC3300,
40403 6 Bitmap 4 342 Code:Out of Calibration Shutdown PCC2300,
PCC3300V2
Fault Status Eng Ctrl:internal h/w failure- PCC3300,
40403 7 Bitmap 4 343 Bad Device/Component Warning PCC2300,
PCC3300V2
Fault Status Injector Power Supply:Bad PCC3300,
40403 8 Bitmap 4 351 Device/Component Warning PCC2300,
PCC3300V2
Fault Status Sensor Supply 1:Vtg Below PCC3300,
40403 9 Bitmap 4 352 Normal Warning PCC2300,
PCC3300V2

A029X159 (Issue 31) 835 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Fail To Start Fault PCC3300,
40403 10 Bitmap 4 359 Shutdown PCC2300,
PCC3300V2
Fault Status Sensor Supply 1:Vtg Above PCC3300,
40403 11 Bitmap 4 386 Normal Warning PCC2300,
PCC3300V2
Fault Status Eng Oil Rifle PCC3300,
40403 12 Bitmap 4 415 Pressure:Below Normal- Shutdown PCC2300,
Most Severe PCC3300V2
Fault Status Water in Fuel PCC3300,
40403 13 Bitmap 4 418 Indicator:Above Normal- Warning PCC2300,
Least Severe PCC3300V2
Fault Status Eng Oil Temp:Above PCC3300,
40403 14 Bitmap 4 421 Normal-Moderately Severe Warning PCC2300,
PCC3300V2
Fault Status COOLANT_LEVEL_READI PCC3300,
40403 15 Bitmap 4 422 NG_INCORRECT Warning PCC2300,
PCC3300V2
Fault Status OIL_TEMPERATURE_IN_R PCC3300,
40404 0 Bitmap 5 425 ANGE_ERROR Warning PCC2300,
PCC3300V2
Fault Status J1939 Datalink:Data PCC3300,
40404 1 Bitmap 5 426 Erratic/Intermittent/Wrong NONE PCC2300,
PCC3300V2
Fault Status CAN Datalink Degraded PCC3300,
40404 2 Bitmap 5 427 Warning PCC2300,
PCC3300V2
Fault Status OIL_PRESSURE_SWITCH PCC3300,
40404 3 Bitmap 5 435 _ERROR Warning PCC2300,
PCC3300V2
Fault Status Low Battery Voltage PCC3300,
40404 4 Bitmap 5 441 Warning PCC2300,
PCC3300V2
Fault Status High Battery Voltage PCC3300,
40404 5 Bitmap 5 442 Warning PCC2300,
PCC3300V2
Fault Status Injector Metering Rail 1 PCC3300,
40404 6 Bitmap 5 449 Pressure:Above Normal Shutdown PCC2300,
PCC3300V2
Fault Status Injector Metering Rail 1 PCC3300,
40404 7 Bitmap 5 451 Pressure:Vtg Above Normal Warning PCC2300,
PCC3300V2
Fault Status Injector Metering Rail 1 PCC3300,
40404 8 Bitmap 5 452 Pressure:Vtg Below Normal Warning PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 836 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Intake Manifold 1 PCC3300,
40404 9 Bitmap 5 488 Temp:Above Normal- Derate PCC2300,
Moderate PCC3300V2
Fault Status Fuel Delivery Pressure:Vtg PCC3300,
40404 10 Bitmap 5 546 Above Normal Warning PCC2300,
PCC3300V2
Fault Status Fuel Delivery Pressure:Vtg PCC3300,
40404 11 Bitmap 5 547 Below Normal Warning PCC2300,
PCC3300V2
Fault Status APC_DIESEL_HIGH_PRS_ PCC3300,
40404 12 Bitmap 5 553 ERROR Warning PCC2300,
PCC3300V2
Fault Status APC_DIESEL_PRS_SIR_E PCC3300,
40404 13 Bitmap 5 554 RROR Warning PCC2300,
PCC3300V2
Fault Status Injector Metering Rail 1 PCC3300,
40404 15 Bitmap 5 559 Pressure:Below Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Shut Down Hot PCC3300,
40405 1 Bitmap 6 611 Condition Exists Warning PCC2300,
PCC3300V2
Fault Status ECM Internal Temperature PCC3300,
40405 2 Bitmap 6 698 Low Error Warning PCC2300,
PCC3300V2
Fault Status Eng Crankshaft Speed/Pos PCC3300,
40405 3 Bitmap 6 689 Warning Warning PCC2300,
PCC3300V2
Fault Status Eng Speed:Cam/Crankshaft PCC3300,
40405 4 Bitmap 6 731 Misalignment Warning PCC2300,
PCC3300V2
Fault Status At Least One ACK:Most PCC3300,
40405 5 Bitmap 6 2661 Severe Fault Shutdown PCC2300,
PCC3300V2
Fault Status CAN Datalink Failed PCC3300,
40405 6 Bitmap 6 781 Shutdown PCC2300,
PCC3300V2
Fault Status Power Lost With Ignition On PCC3300,
40405 7 1117 Warning
Bitmap 6 PCC3300V2
Fault Status Rated to Idle Transition PCC3300,
40405 8 Bitmap 6 1122 NONE PCC2300,
PCC3300V2
Fault Status Delayed Shutdown Fault PCC3300,
40405 9 Bitmap 6 1124 Warning PCC2300,
PCC3300V2

A029X159 (Issue 31) 837 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Battle Short Mode Active PCC3300,
40405 10 Bitmap 6 1131 Warning PCC2300,
PCC3300V2
Fault Status Controlled Shutdown In PCC3300,
40405 11 1132 Warning
Bitmap 6 Process PCC3300V2
Fault Status Engine Derate PCC3300,
40405 13 Bitmap 6 1243 Derate PCC2300,
PCC3300V2
Fault Status Engine Normal Shutdown PCC3300,
Shutdown
40405 14 Bitmap 6 1244 PCC2300,
w/Cooldown
PCC3300V2
Fault Status Engine Shutdown PCC3300,
40405 15 Bitmap 6 1245 Shutdown PCC2300,
PCC3300V2
Fault Status Unrecognized Engine Fault PCC3300,
40406 0 Bitmap 7 1246 Warning PCC2300,
PCC3300V2
Fault Status Engine Shutdown – PCC3300,
40406 1 Bitmap 7 1247 Unannounced Shutdown PCC2300,
PCC3300V2
Fault Status Engine Warning PCC3300,
40406 2 Bitmap 7 1248 Warning PCC2300,
PCC3300V2
Fault Status Ctrl Module ID Input State PCC3300,
40406 3 Bitmap 7 1256 Warning Errior Warning PCC2300,
PCC3300V2
Fault Status Ctrl Module ID I/P State PCC3300,
40406 4 Bitmap 7 1257 shutdown Error Shutdown PCC2300,
PCC3300V2
Fault Status kW Load Setpoint OOR PCC3300,
40406 5 1322 Warning
Bitmap 7 High PCC3300V2
Fault Status kW Load Setpoint OOR PCC3300,
40406 6 1323 Warning
Bitmap 7 Low PCC3300V2
Fault Status kVAR Load Setpoint OOR PCC3300,
40406 7 1324 Warning
Bitmap 7 High PCC3300V2
Fault Status kVAR Load Setpoint OOR PCC3300,
40406 8 1325 Warning
Bitmap 7 Low PCC3300V2
Fault Status Cooldown Completed Fault PCC3300,
40406 9 Bitmap 7 1336 Shutdown PCC2300,
PCC3300V2
Fault Status Eng Oil Lvl Remote PCC3300,
40406 10 Bitmap 7 1357 Reservoir:Below Normal Warning PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 838 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Eng Oil Level Remote PCC3300,
40406 11 Bitmap 7 219 Reservoir: Least Severe Warning PCC2300,
Level PCC3300V2
Fault Status HT Coolant Pressure PCC3300,
40406 12 Bitmap 7 233 Moderate Low Warning PCC2300,
PCC3300V2
Fault Status FSO NON Low Control PCC3300,
40406 13 Bitmap 7 254 Error Shutdown PCC2300,
PCC3300V2
Fault Status Turbo 1 Speed Incorrect PCC3300,
40406 14 Bitmap 7 686 Warning PCC2300,
PCC3300V2
Fault Status ECM Internal Temperature PCC3300,
40406 15 Bitmap 7 697 High Error Warning PCC2300,
PCC3300V2
Fault Status Eng Camshaft Speed/Pos PCC3300,
40407 0 Bitmap 8 1376 Warning Warning PCC2300,
PCC3300V2
Fault Status Custom Overcurrent Fault PCC3300,
40407 1 Bitmap 8 3611 Warning PCC2300,
PCC3300V2
Fault Status Negative Sequence PCC3300,
40407 2 Bitmap 8 3513 Overcurrent Warning PCC2300,
PCC3300V2
Fault Status Fail to Shutdown PCC3300,
40407 3 Bitmap 8 1416 Warning PCC2300,
PCC3300V2
Fault Status Power Down Failure PCC3300,
40407 4 Bitmap 8 1417 Warning PCC2300,
PCC3300V2
Fault Status Local E-Stop PCC3300,
40407 5 Bitmap 8 1433 Shutdown PCC2300,
PCC3300V2
Fault Status Remote E-Stop PCC3300,
40407 6 Bitmap 8 1434 Shutdown PCC2300,
PCC3300V2
Fault Status Low Coolant Temperature PCC3300,
40407 7 Bitmap 8 1435 Warning PCC2300,
PCC3300V2
Fault Status Fail To Crank Fault PCC3300,
40407 8 Bitmap 8 1438 Shutdown PCC2300,
PCC3300V2
Fault Status Low Fuel in Day Tank PCC3300,
40407 9 Bitmap 8 1439 Warning PCC2300,
PCC3300V2

A029X159 (Issue 31) 839 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Low Fuel Level PCC3300,
40407 10 Bitmap 8 1441 Warning PCC2300,
PCC3300V2
Fault Status Weak Battery PCC3300,
40407 11 Bitmap 8 1442 Warning PCC2300,
PCC3300V2
Fault Status Dead Battery PCC3300,
40407 12 Bitmap 8 1443 Shutdown PCC2300,
PCC3300V2
Fault Status Overload PCC3300,
40407 13 Bitmap 8 1444 Warning PCC2300,
PCC3300V2
Fault Status Short Circuit PCC3300,
40407 14 Bitmap 8 1445 Shutdown PCC2300,
PCC3300V2
Fault Status High AC Voltage PCC3300,
40407 15 Bitmap 8 1446 Shutdown PCC2300,
PCC3300V2
Fault Status Low AC Voltage PCC3300,
40408 0 Bitmap 9 1447 Shutdown PCC2300,
PCC3300V2
Fault Status Underfrequency PCC3300,
40408 1 Bitmap 9 1448 Shutdown PCC2300,
PCC3300V2
Fault Status Overfrequency PCC3300,
40408 2 Bitmap 9 1449 Warning PCC2300,
PCC3300V2
Fault Status Reverse kW PCC3300,
40408 3 Bitmap 9 1459 Shutdown PCC2300,
PCC3300V2
Fault Status Loss of Field PCC3300,
40408 4 Bitmap 9 1461 Shutdown PCC2300,
PCC3300V2
Fault Status Not In Auto PCC3300,
40408 5 Bitmap 9 1463 NONE PCC2300,
PCC3300V2
Fault Status Load Dump PCC3300,
40408 6 Bitmap 9 1464 Warning PCC2300,
PCC3300V2
Fault Status Ready To Load PCC3300,
40408 7 Bitmap 9 1465 NONE PCC2300,
PCC3300V2
Fault Status Speed/Frequency Mismatch PCC3300,
40408 8 Bitmap 9 1469 Fault Shutdown PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 840 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status High Current Warning PCC3300,
40408 9 Bitmap 9 1471 Warning PCC2300,
PCC3300V2
Fault Status Overcurrent Shutdown PCC3300,
40408 10 Bitmap 9 1472 Shutdown PCC2300,
PCC3300V2
Fault Status Common Alarm PCC3300,
40408 11 Bitmap 9 1483 None PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40408 12 Bitmap 9 1548 Cylinder 7:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40408 13 Bitmap 9 1549 Cylinder 8:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40408 14 Bitmap 9 1551 Cylinder 10:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40408 15 Bitmap 9 1552 Cylinder 11:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40409 0 Bitmap 10 1553 Cylinder 12:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40409 1 Bitmap 10 1554 Cylinder 13:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40409 2 Bitmap 10 1555 Cylinder 14:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40409 3 Bitmap 10 1556 Cylinder 15:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40409 4 Bitmap 10 1557 Cylinder 16:UnderCurrent Warning PCC2300,
PCC3300V2
Fault Status Genset Breaker Fail To PCC3300,
40409 5 1452 Warning
Bitmap 10 Close PCC3300V2
Fault Status Genset Breaker Fail To PCC3300,
40409 6 1453 Warning
Bitmap 10 Open PCC3300V2
Fault Status Injector Solenoid Driver PCC3300,
40409 7 Bitmap 10 1622 Cylinder 9:UnderCurrent Warning PCC2300,
PCC3300V2

A029X159 (Issue 31) 841 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Real Time Clock Power PCC3300,
40409 8 Bitmap 10 1689 Interrupt Fault Warning PCC2300,
PCC3300V2
Fault Status SENSOR_SUPPLY_5_VOL PCC3300,
40409 9 Bitmap 10 1695 TAGE_HIGH_ERROR Warning PCC2300,
PCC3300V2
Fault Status SENSOR_SUPPLY_5_VOL PCC3300,
40409 10 Bitmap 10 1696 TAGE_LOW_ERROR Warning PCC2300,
PCC3300V2
Fault Status Crankcase Pressure:Vtg PCC3300,
40409 11 Bitmap 10 1843 Above Normal Warning PCC2300,
PCC3300V2
Fault Status Crankcase Pressure:Vtg PCC3300,
40409 12 Bitmap 10 1844 Below Normal Warning PCC2300,
PCC3300V2
Fault Status Water in Fuel Indicator:Vtg PCC3300,
40409 13 Bitmap 10 1845 Above Normal Warning PCC2300,
PCC3300V2
Fault Status Water in Fuel Indicator:Vtg PCC3300,
40409 14 Bitmap 10 1846 Below Normal Warning PCC2300,
PCC3300V2
Fault Status Eng Coolant Temp - PCC3300,
Shutdown
40409 15 Bitmap 10 1847 Shutdown w/Cool PCC2300,
w/Cooldown
PCC3300V2
Fault Status Low Oil Pressure OOR PS0500
40410 6 141 Warning
Bitmap 11 Warning
Fault Status Low Oil Pressure Warning PS0500
40410 5 143 Warning
Bitmap 11
Fault Status Coolant Temp OOR PS0500
40410 2 144 Warning
Bitmap 11 Warning
Fault Status High Coolant Temp PS0500
40410 0 146 Warning
Bitmap 11 Warning
Fault Status Low Battery Voltage PS0500
40410 3 441 Warning
Bitmap 11
Fault Status High Battery Voltage PS0500
40410 4 442 Warning
Bitmap 11
Fault Status Battle Short Mode Active PS0500
40410 7 1131 Warning
Bitmap 11 Fault
Fault Status Fail to Shutdown Fault PS0500
40410 9 1416 Warning
Bitmap 11
Fault Status Low Coolant Temperature PS0500
40410 1 1435 Warning
Bitmap 11

Copyright © 2023 Cummins Inc. 842 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Weak Battery Fault PS0500
40410 10 1442 Warning
Bitmap 11
Fault Status High Current Warning PS0500
40410 11 1471 Warning
Bitmap 11
Fault Status Common Warning PS0500
40410 14 1540 Warning
Bitmap 11
Fault Status Water in Fuel PCC3300,
40410 0 Bitmap 11 1852 Indicator:Above Normal- Warning PCC2300,
Moderate PCC3300V2
Fault Status HMI113 Fault 1 PCC3300,
40410 1 Bitmap 11 11634 Warning PCC2300,
PCC3300V2
Fault Status HMI113 Fault 2 PCC3300,
40410 2 Bitmap 11 11635 Warning PCC2300,
PCC3300V2
Fault Status HMI113 Fault 3 PCC3300,
40410 3 Bitmap 11 11636 Warning PCC2300,
PCC3300V2
Fault Status Eng Oil Change Interval PCC3300,
40410 5 Bitmap 11 1891 Warning PCC2300,
PCC3300V2
Fault Status J39_EGR_VALVE_COMM_ PCC3300,
40410 6 Bitmap 11 1893 TIMEOUT_ERROR Warning PCC2300,
PCC3300V2
Fault Status J39_VGT_COMM_TIMEOU PCC3300,
40410 7 Bitmap 11 1894 T_ERROR Warning PCC2300,
PCC3300V2
Fault Status EGR_DL_VALVE_STUCK_ PCC3300,
40410 8 Bitmap 11 1896 ERROR Warning PCC2300,
PCC3300V2
Fault Status EGR_DELTA_P_IR_LOW_ PCC3300,
40410 9 Bitmap 11 1899 ERROR Warning PCC2300,
PCC3300V2
Fault Status Utility Loss Of Phase PCC3300,
40410 11 1912 Warning
Bitmap 11 PCC3300V2
Fault Status Genset Loss Of Phase PCC3300,
40410 12 1913 Warning
Bitmap 11 PCC3300V2
Fault Status Utility Phase Rotation PCC3300,
40410 13 1914 Warning
Bitmap 11 PCC3300V2
Fault Status Genset Phase Rotation PCC3300,
40410 14 1915 Warning
Bitmap 11 PCC3300V2
Fault Status Sync Check OK PCC3300,
40410 15 1916 NONE
Bitmap 11 PCC3300V2

A029X159 (Issue 31) 843 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Maintenance Required - PS0500
40410 13 6226 Warning
Bitmap 11 Condition Exists
Fault Status Current Imbalance - PS0500
40410 12 6227 Warning
Bitmap 11 Condition Exists
Fault Status Charging Alternator Failure PS0500
40410 8 2678 Warning
Bitmap 11 Fault
Fault Status High Fuel Level PCC3300,
40411 0 Bitmap 12 1917 Warning PCC2300,
PCC3300V2
Fault Status Very Low Fuel Level PCC3300,
40411 1 Bitmap 12 1918 Shutdown PCC2300,
PCC3300V2
Fault Status EGR_DL_VOLTAGE_HIGH PCC3300,
40411 2 Bitmap 12 1933 _ERROR Warning PCC2300,
PCC3300V2
Fault Status EGR_DL_VOLTAGE_LOW PCC3300,
40411 3 Bitmap 12 1934 _ERROR Warning PCC2300,
PCC3300V2
Fault Status EGR_DL_COMMAND_SOU PCC3300,
40411 4 Bitmap 12 1935 RCE_ERROR Warning PCC2300,
PCC3300V2
Fault Status Crankcase Pressure - Data PCC3300,
40411 5 Bitmap 12 1942 Erratic, Intermittent, or Warning PCC2300,
Incorrect PCC3300V2
Fault Status CBR_DENSITY_DERATE_ PCC3300,
40411 6 Bitmap 12 1943 ERROR_ID NONE PCC2300,
PCC3300V2
Fault Status HMI113 Output PCC3300,
40411 7 Bitmap 12 1944 Configuration Fault Warning PCC2300,
PCC3300V2
Fault Status EGR_DL_EDU_TMPTR_HI PCC3300,
40411 8 Bitmap 12 1961 GH_ERROR Warning PCC2300,
PCC3300V2
Fault Status CRANKCASE_PRESSURE PCC3300,
40411 9 Bitmap 12 1974 _LEAST_SEV_HIGH Warning PCC2300,
PCC3300V2
Fault Status Eng Crankshaft PCC3300,
40411 10 Bitmap 12 1992 Speed/Posn:Above Normal Shutdown PCC2300,
PCC3300V2
Fault Status Maximum Parallel Time PCC3300,
40411 11 1999 Warning
Bitmap 12 PCC3300V2
Fault Status Sensor Supply 4:Vtg Above PCC3300,
40411 12 Bitmap 12 2185 Normal Warning PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 844 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Sensor Supply 4:Vtg Below PCC3300,
40411 13 Bitmap 12 2186 Normal Warning PCC2300,
PCC3300V2
Fault Status Fuel Pump Delivery PCC3300,
40411 14 Bitmap 12 2215 Pressure:Below Normal Warning PCC2300,
PCC3300V2
Fault Status Injector Metering Rail 1 PCC3300,
40411 15 Bitmap 12 2249 Press Hi Warning PCC2300,
PCC3300V2
Fault Status Fuel Pump Delivery PCC3300,
40412 0 Bitmap 13 2261 Pressure:Above Normal Warning PCC2300,
PCC3300V2
Fault Status Fuel Pump Delivery-Below PCC3300,
40412 1 Bitmap 13 2262 Normal Warning PCC2300,
PCC3300V2
Fault Status Electric Lift Pump for Eng PCC3300,
40412 2 Bitmap 13 2265 Fuel:Vtg Above Normal Warning PCC2300,
PCC3300V2
Fault Status Electric Lift Pump for Eng PCC3300,
40412 3 Bitmap 13 2266 Fuel:Vtg Below Normal Warning PCC2300,
PCC3300V2
Fault Status APC_DIESEL_FLOW_HIG PCC3300,
40412 4 Bitmap 13 2292 H_ERROR Warning PCC2300,
PCC3300V2
Fault Status APC_DIESEL_FLOW_LOW PCC3300,
40412 5 Bitmap 13 2293 _ERROR Warning PCC2300,
PCC3300V2
Fault Status Electronic Fuel Injection PCC3300,
40412 6 Bitmap 13 2311 Control Valve Warning PCC2300,
PCC3300V2
Fault Status Utility Available PCC3300,
40412 7 2328 NONE
Bitmap 13 PCC3300V2
Fault Status Utility Undervoltage PCC3300,
40412 8 2331 Warning
Bitmap 13 PCC3300V2
Fault Status Utility Connected PCC3300,
40412 9 2332 NONE
Bitmap 13 PCC3300V2
Fault Status Genset Connected PCC3300,
40412 10 2333 NONE
Bitmap 13 PCC3300V2
Fault Status Excitation/Loss of AC PCC3300,
40412 11 Bitmap 13 2335 Voltage Sensing Shutdown PCC2300,
PCC3300V2
Fault Status Too Long in Idle PCC3300,
40412 13 Bitmap 13 2342 Warning PCC2300,
PCC3300V2

A029X159 (Issue 31) 845 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Utility Overvoltage PCC3300,
40412 14 2358 Warning
Bitmap 13 PCC3300V2
Fault Status Fan Control:Vtg Above PCC3300,
40412 15 Bitmap 13 2377 Normal Warning PCC2300,
PCC3300V2
Fault Status Utility Breaker Fail To Close PCC3300,
40413 0 2396 Warning
Bitmap 14 PCC3300V2
Fault Status Utility Breaker Fail To Open PCC3300,
40413 1 2397 Warning
Bitmap 14 PCC3300V2
Fault Status Base Load PCC3300,
40413 2 3226 NONE
Bitmap 14 PCC3300V2
Fault Status Peak Shave PCC3300,
40413 3 3227 NONE
Bitmap 14 PCC3300V2
Fault Status Engine Intake Air Heater 1 PCC3300,
40413 4 Bitmap 14 2555 Circuit Voltage High Warning PCC2300,
PCC3300V2
Fault Status Engine Intake Air Heater 1 PCC3300,
40413 5 Bitmap 14 2556 Circuit - Voltage Low Warning PCC2300,
PCC3300V2
Fault Status Charging Alternator Failure PCC3300,
40413 6 Bitmap 14 2678 Fault Warning PCC2300,
PCC3300V2
Fault Status Genset Available PCC3300,
40413 7 2965 NONE
Bitmap 14 PCC3300V2
Fault Status Test/Exercise is Active Fault PCC3300,
40413 8 Bitmap 14 2971 NONE PCC2300,
PCC3300V2
Fault Status Field Overload PCC3300,
40413 9 Bitmap 14 2972 Shutdown PCC2300,
PCC3300V2
Fault Status CHARGE_PRESS_IR_ERR PCC3300,
40413 10 Bitmap 14 2973 OR Warning PCC2300,
PCC3300V2
Fault Status Manual Switch PCC3300,
40413 11 Bitmap 14 2943 Configuration Fault Warning PCC2300,
PCC3300V2
Fault Status Auto Switch Configuration PCC3300,
40413 12 Bitmap 14 2944 Fault Warning PCC2300,
PCC3300V2
Fault Status Genset AC Meter Failed PCC3300,
40413 13 Bitmap 14 2914 Shutdown PCC2300,
PCC3300V2
Fault Status Genset Bus AC Meter PCC3300,
40413 14 2915 Warning
Bitmap 14 Failed PCC3300V2

Copyright © 2023 Cummins Inc. 846 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Utility AC Meter Failed PCC3300,
40413 15 2916 Warning
Bitmap 14 PCC3300V2
Fault Status Genset CT Ratio Too Small PCC3300,
40414 0 Bitmap 15 2814 Shutdown PCC2300,
PCC3300V2
Fault Status Genset CT Ratio Too Large PCC3300,
40414 1 Bitmap 15 2815 Warning PCC2300,
PCC3300V2
Fault Status Genset PT Ratio Too Small PCC3300,
40414 2 Bitmap 15 2816 Shutdown PCC2300,
PCC3300V2
Fault Status Genset PT Ratio Too Large PCC3300,
40414 3 Bitmap 15 2817 Warning PCC2300,
PCC3300V2
Fault Status Genset Bus PT Ratio Too PCC3300,
40414 4 2818 Shutdown
Bitmap 15 Small PCC3300V2
Fault Status Genset Bus PT Ratio Too PCC3300,
40414 5 2819 Warning
Bitmap 15 Large PCC3300V2
Fault Status Utility PT Ratio Too Small PCC3300,
40414 6 2821 Shutdown
Bitmap 15 PCC3300V2
Fault Status Utility PT Ratio Too Large PCC3300,
40414 7 2822 Warning
Bitmap 15 PCC3300V2
Fault Status AUX101 0 Input 1 Fault PCC3300,
40414 8 Bitmap 15 5182 Warning PCC2300,
PCC3300V2
Fault Status Aux101 0 Input 2 Fault PCC3300,
40414 9 Bitmap 15 2621 Warning PCC2300,
PCC3300V2
Fault Status Aux101 0 Input 3 Fault PCC3300,
40414 10 Bitmap 15 2622 Warning PCC2300,
PCC3300V2
Fault Status Aux101 0 Input 4 Fault PCC3300,
40414 11 Bitmap 15 2623 Warning PCC2300,
PCC3300V2
Fault Status Aux101 0 Input 5 Fault PCC3300,
40414 12 Bitmap 15 2624 Warning PCC2300,
PCC3300V2
Fault Status Aux101 0 Input 6 Fault PCC3300,
40414 13 Bitmap 15 2625 Warning PCC2300,
PCC3300V2
Fault Status Aux101 0 Input 7 Fault PCC3300,
40414 14 Bitmap 15 2626 Warning PCC2300,
PCC3300V2

A029X159 (Issue 31) 847 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Aux101 0 Input 8 Fault PCC3300,
40414 15 Bitmap 15 2627 Warning PCC2300,
PCC3300V2
Fault Status Aux101 1 Input 1 Fault PCC3300,
40415 0 Bitmap 16 2882 Warning PCC2300,
PCC3300V2
Fault Status Aux101 1 Input 2 Fault PCC3300,
40415 1 Bitmap 16 2883 Warning PCC2300,
PCC3300V2
Fault Status Aux101 1 Input 3 Fault PCC3300,
40415 2 Bitmap 16 2884 Warning PCC2300,
PCC3300V2
Fault Status Aux101 1 Input 4 Fault PCC3300,
40415 3 Bitmap 16 2885 Warning PCC2300,
PCC3300V2
Fault Status Aux101 1 Input 5 Fault PCC3300,
40415 4 Bitmap 16 2886 Warning PCC2300,
PCC3300V2
Fault Status Aux101 1 Input 6 Fault PCC3300,
40415 5 Bitmap 16 2887 Warning PCC2300,
PCC3300V2
Fault Status Aux101 1 Input 7 Fault PCC3300,
40415 6 Bitmap 16 2888 Warning PCC2300,
PCC3300V2
Fault Status Aux101 1 Input 8 Fault PCC3300,
40415 7 Bitmap 16 2889 Warning PCC2300,
PCC3300V2
Fault Status Aux102 0 Expansion Input 9 PCC3300,
40415 8 Bitmap 16 2628 Fault Warning PCC2300,
PCC3300V2
Fault Status Aux102 0 Expansion Input PCC3300,
40415 9 Bitmap 16 2629 10 Fault Warning PCC2300,
PCC3300V2
Fault Status Aux102 0 Expansion Input PCC3300,
40415 10 Bitmap 16 2631 11 Fault Warning PCC2300,
PCC3300V2
Fault Status Aux102 0 Expansion Input PCC3300,
40415 11 Bitmap 16 2632 12 Fault Warning PCC2300,
PCC3300V2
Fault Status Aux102 1 Expansion Input 9 PCC3300,
40415 12 Bitmap 16 2891 Fault Warning PCC2300,
PCC3300V2
Fault Status Aux102 1 Expansion Input PCC3300,
40415 13 Bitmap 16 2892 10 Fault Warning PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 848 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Aux102 1 Expansion Input PCC3300,
40415 14 Bitmap 16 2893 11 Fault Warning PCC2300,
PCC3300V2
Fault Status Aux102 1 Expansion Input PCC3300,
40415 15 Bitmap 16 2894 12 Fault Warning PCC2300,
PCC3300V2
Fault Status PCCnet Device Failed PCC3300,
40416 0 Bitmap 17 2895 Warning Warning PCC2300,
PCC3300V2
Fault Status PCCnet Device Failed PCC3300,
40416 1 Bitmap 17 2896 Shutdown Shutdown PCC2300,
PCC3300V2
Fault Status Genset Bus Voltage OOR PCC3300,
40416 2 2917 Warning
Bitmap 17 Warning PCC3300V2
Fault Status Utility Voltage OOR PCC3300,
40416 3 2918 Warning
Bitmap 17 Warning PCC3300V2
Fault Status Utility Current OOR PCC3300,
40416 4 2919 Warning
Bitmap 17 Warning PCC3300V2
Fault Status Genset Bus Current OOR PCC3300,
40416 5 2921 Warning
Bitmap 17 Warning PCC3300V2
Fault Status Genset Neutral Current PCC3300,
40416 6 2922 Warning
Bitmap 17 OOR Warning PCC3300V2
Fault Status Genset Bus kW OOR PCC3300,
40416 7 2923 Warning
Bitmap 17 Warning PCC3300V2
Fault Status Genset Bus kVAR OOR PCC3300,
40416 8 2924 Warning
Bitmap 17 Warning PCC3300V2
Fault Status Genset Bus kVA OOR PCC3300,
40416 9 2925 Warning
Bitmap 17 Warning PCC3300V2
Fault Status Utility kW OOR Warning PCC3300,
40416 10 2926 Warning
Bitmap 17 PCC3300V2
Fault Status Utility kVAR OOR Warning PCC3300,
40416 11 2927 Warning
Bitmap 17 PCC3300V2
Fault Status Utility kVA OOR Warning PCC3300,
40416 12 2928 Warning
Bitmap 17 PCC3300V2
Fault Status Ground Current OOR PCC3300,
40416 13 3599 Warning
Bitmap 17 Warning PCC3300V2
Fault Status AUX101 Device ID Fault PCC3300,
40416 14 Bitmap 17 2931 Shutdown PCC2300,
PCC3300V2
Fault Status Utility Unloaded Event PCC3300,
40416 15 2779 NONE
Bitmap 17 PCC3300V2

A029X159 (Issue 31) 849 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Setup Mode Shutdown PCC3300,
40417 0 Bitmap 18 4358 Shutdown PCC2300,
PCC3300V2
Fault Status AUX101 Oil Temp OOR Hi PCC3300,
40417 3 Bitmap 18 2932 Warning PCC2300,
PCC3300V2
Fault Status AUX101 Oil Temp OOR PCC3300,
40417 4 Bitmap 18 2933 Low Warning PCC2300,
PCC3300V2
Fault Status Exhaust Stack Temp Left PCC3300,
40417 5 Bitmap 18 2657 Bank Above Threshold Warning PCC2300,
PCC3300V2
Fault Status Exhaust Stack Temp 1 PCC3300,
40417 6 Bitmap 18 2947 OOR Low Warning PCC2300,
PCC3300V2
Fault Status High Exhaust Stack PCC3300,
40417 7 Bitmap 18 2949 Temperature 1 Warning PCC2300,
PCC3300V2
Fault Status Exhaust Stack Temp Right PCC3300,
40417 8 Bitmap 18 2653 Bank Above Threshold Warning PCC2300,
PCC3300V2
Fault Status Exhaust Stack Temp 2 PCC3300,
40417 9 Bitmap 18 2946 OOR Low Warning PCC2300,
PCC3300V2
Fault Status High Exhaust Stack PCC3300,
40417 10 Bitmap 18 2948 Temperature 2 Warning PCC2300,
PCC3300V2
Fault Status Ambient Temp OOR High PCC3300,
40417 11 Bitmap 18 2934 Warning PCC2300,
PCC3300V2
Fault Status Ambient Temp OOR Low PCC3300,
40417 12 Bitmap 18 2935 Warning PCC2300,
PCC3300V2
Fault Status Fuel Level OOR High PCC3300,
40417 13 Bitmap 18 2936 Warning PCC2300,
PCC3300V2
Fault Status Fuel Level OOR Low PCC3300,
40417 14 Bitmap 18 2937 Warning PCC2300,
PCC3300V2
Fault Status Alternator Temp 1 OOR PCC3300,
40417 15 Bitmap 18 2951 High Warning PCC2300,
PCC3300V2
Fault Status Alternator Temp 1 OOR PCC3300,
40418 0 Bitmap 19 2952 Low Warning PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 850 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status High Alternator Temp 1 PCC3300,
40418 1 Bitmap 19 2953 Warning PCC2300,
PCC3300V2
Fault Status Alternator Temp 2 OOR PCC3300,
40418 2 Bitmap 19 2954 High Warning PCC2300,
PCC3300V2
Fault Status Alternator Temp 2 OOR PCC3300,
40418 3 Bitmap 19 2955 Low Warning PCC2300,
PCC3300V2
Fault Status High Alternator Temp 2 PCC3300,
40418 4 Bitmap 19 2956 Warning PCC2300,
PCC3300V2
Fault Status Alternator Temp 3 OOR PCC3300,
40418 5 Bitmap 19 2957 High Warning PCC2300,
PCC3300V2
Fault Status Alternator Temp 3 OOR PCC3300,
40418 6 Bitmap 19 2958 Low Warning PCC2300,
PCC3300V2
Fault Status High Alternator Temp 3 PCC3300,
40418 7 Bitmap 19 2959 Warning PCC2300,
PCC3300V2
Fault Status Intake Manifold Temp 1 PCC3300,
40418 8 Bitmap 19 2992 OOR High Warning PCC2300,
PCC3300V2
Fault Status Intake Manifold Temp 1 PCC3300,
40418 9 Bitmap 19 2978 OOR Low Warning PCC2300,
PCC3300V2
Fault Status Drive End Bearing Temp PCC3300,
40418 10 Bitmap 19 2981 OOR High Warning PCC2300,
PCC3300V2
Fault Status Drive End Bearing Temp PCC3300,
40418 11 Bitmap 19 2982 OOR Low Warning PCC2300,
PCC3300V2
Fault Status High Drive End Bearing PCC3300,
40418 12 Bitmap 19 2983 Temperature Warning PCC2300,
PCC3300V2
Fault Status Non-Drive End Bearing PCC3300,
40418 13 Bitmap 19 2984 Temp OOR High Warning PCC2300,
PCC3300V2
Fault Status Non-Drive End Bearing PCC3300,
40418 14 Bitmap 19 2985 Temp OOR Low Warning PCC2300,
PCC3300V2
Fault Status High Non-Drive End PCC3300,
40418 15 Bitmap 19 2986 Bearing Temperature Warning PCC2300,
PCC3300V2

A029X159 (Issue 31) 851 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Rupture Basin PCC3300,
40419 0 Bitmap 20 2945 Warning PCC2300,
PCC3300V2
Fault Status High Alternator Temp PCC3300,
40419 1 Bitmap 20 2979 Switch fault Warning PCC2300,
PCC3300V2
Fault Status Battery Charger Failed Fault PCC3300,
40419 2 Bitmap 20 2993 Warning PCC2300,
PCC3300V2
Fault Status Earth/Ground Fault PCC3300,
40419 3 Bitmap 20 2938 Warning PCC2300,
PCC3300V2
Fault Status Modbus Failure Fault PCC3300,
40419 4 Bitmap 20 2939 Warning PCC2300,
PCC3300V2
Fault Status Low Coolant Level #2 PCC3300,
40419 5 Bitmap 20 2977 Warning PCC2300,
PCC3300V2
Fault Status Speed Bias OOR High PCC3300,
40419 6 Bitmap 20 1978 Warning PCC2300,
PCC3300V2
Fault Status Voltage Bias OOR Low PCC3300,
40419 7 Bitmap 20 2541 Warning PCC2300,
PCC3300V2
Fault Status Voltage Bias OOR High PCC3300,
40419 8 Bitmap 20 2539 Warning PCC2300,
PCC3300V2
Fault Status Configurable Input #1 PCC3300,
40419 9 Bitmap 20 1573 NONE PCC2300,
PCC3300V2
Fault Status Configurable Input #2 PCC3300,
40419 10 Bitmap 20 1312 NONE PCC2300,
PCC3300V2
Fault Status Configurable Input #13 PCC3300,
40419 11 Bitmap 20 1317 NONE PCC2300,
PCC3300V2
Fault Status Configurable Input #14 PCC3300,
40419 12 Bitmap 20 1318 NONE PCC2300,
PCC3300V2
Fault Status Speed Bias OOR Low PCC3300,
40419 13 Bitmap 20 1979 Warning PCC2300,
PCC3300V2
Fault Status Both Engine Speed Signals PCC3300,
40419 14 Bitmap 20 236 Lost: Most Severe Level Shutdown PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 852 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Device Calibration Update PCC3300,
40419 15 3629 Warning
Bitmap 20 Recommended PCC3300V2
Fault Status Customer Input Fault PS0500
40420 0 1312 Shutdown
Bitmap 21
Fault Status Device Calibration Update PCC3300,
40420 0 Bitmap 21 3631 Required Shutdown PCC2300,
PCC3300V2
Fault Status Water In Fuel Indicator PCC3300,
40420 1 Bitmap 21 428 Sensor: Volt Above Normal Warning PCC2300,
PCC3300V2
Fault Status Water In Fuel Indicator PCC3300,
40420 2 Bitmap 21 429 Sensor: Volt Below Normal Warning PCC2300,
PCC3300V2
Fault Status Sensor Supply 6 Circuit PCC3300,
40420 3 Bitmap 21 515 OORH Warning PCC2300,
PCC3300V2
Fault Status Sensor Supply 6 Circuit PCC3300,
40420 4 Bitmap 21 516 OORL Warning PCC2300,
PCC3300V2
Fault Status Crankcase Pressure High: PCC3300,
40420 5 Bitmap 21 555 Above Normal Warning PCC2300,
PCC3300V2
Fault Status Turbocharger 1 Comp PCC3300,
40420 6 Bitmap 21 691 Intake Temp:Volt Above Warning PCC2300,
Normal PCC3300V2
Fault Status Turbocharger 1 Comp PCC3300,
40420 7 Bitmap 21 692 Intake Temp:Volt Below Warning PCC2300,
Normal PCC3300V2
Fault Status Exh Aft Oxidation Catalyst PCC3300,
40420 8 Bitmap 21 1664 Missing Warning PCC2300,
PCC3300V2
Fault Status Aft Oxidation Catalyst PCC3300,
40420 9 Bitmap 21 1691 Efficiency: Below Normal Warning PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter PCC3300,
40420 10 Bitmap 21 1879 Pressure OORH Warning PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter PCC3300,
40420 11 Bitmap 21 1881 Pressure OORL Warning PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter PCC3300,
40420 12 Bitmap 21 1883 Pressure: Incorrect Warning PCC2300,
PCC3300V2

A029X159 (Issue 31) 853 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status VGT Actuator Controller Out PCC3300,
40420 13 Bitmap 21 1898 of Calibration Warning PCC2300,
PCC3300V2
Fault Status Inj 1 Rail Pressure: Above PCC3300,
40420 14 Bitmap 21 1911 Normal Severe Level Warning PCC2300,
PCC3300V2
Fault Status Aftertreatment DPF PCC3300,
40420 15 Bitmap 21 1921 Differential Pressure Warning PCC2300,
PCC3300V2
Fault Status Aftertreatment DPF PCC3300,
40421 0 Bitmap 22 1922 Differential Pressure Severe Shutdown PCC2300,
PCC3300V2
Fault Status ECU Power Output Volt: PCC3300,
40421 1 Bitmap 22 1938 Below Normal Warning PCC2300,
PCC3300V2
Fault Status VGT Actuator Driver PCC3300,
40421 2 Bitmap 22 1962 Temperature: Above Warning PCC2300,
Normal PCC3300V2
Fault Status Aft Particulate Filter Missing PCC3300,
40421 3 Bitmap 22 1993 Warning PCC2300,
PCC3300V2
Fault Status VGT Actuator Driver Circuit: PCC3300,
40421 4 Bitmap 22 2198 Unknown Cause Warning PCC2300,
PCC3300V2
Fault Status Turbo Charger 1 Speed: PCC3300,
40421 5 Bitmap 22 2288 Above Normal NONE PCC2300,
PCC3300V2
Fault Status EGR Valve Control Circuit: PCC3300,
40421 7 Bitmap 22 2353 Current OORH Warning PCC2300,
PCC3300V2
Fault Status Fuel Filter Pressure: Above PCC3300,
40421 8 Bitmap 22 2372 Normal Warning PCC2300,
PCC3300V2
Fault Status Exhaust Pressure: OORH PCC3300,
40421 9 Bitmap 22 2373 Warning PCC2300,
PCC3300V2
Fault Status Exhaust Pressure: OORL PCC3300,
40421 10 Bitmap 22 2374 Warning PCC2300,
PCC3300V2
Fault Status VGT Actuator: Mechanical PCC3300,
40421 11 Bitmap 22 2387 Sys Not Responding Warning PCC2300,
PCC3300V2
Fault Status VGT Actuator Controller: PCC3300,
40421 12 Bitmap 22 2449 Out of Calibration Shutdown PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 854 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust Gar Pressure: PCC3300,
40421 13 Bitmap 22 2554 Incorrect Warning PCC2300,
PCC3300V2
Fault Status VGT Actuator Controller: PCC3300,
40421 14 Bitmap 22 2634 Bad Device/Component Shutdown PCC2300,
PCC3300V2
Fault Status VGT Actuator Driver PCC3300,
40421 15 Bitmap 22 2635 Condition Exists Shutdown PCC2300,
PCC3300V2
Fault Status VGT Actuator Circuit: PCC3300,
40422 0 Bitmap 23 2636 Abnormal Update Rate Shutdown PCC2300,
PCC3300V2
Fault Status Aft Catalyst Face Plugged: PCC3300,
40422 1 Bitmap 23 2637 Reason Unknown NONE PCC2300,
PCC3300V2
Fault Status Aftertreatment DPF PCC3300,
40422 2 Bitmap 23 2639 Differential Press Least NONE PCC2300,
Severe PCC3300V2
Fault Status Exhaust Gas Recirculation PCC3300,
40422 3 Bitmap 23 2753 Temp: Above Normal Shutdown PCC2300,
PCC3300V2
Fault Status Diesel Particulate Filter Int PCC3300,
40422 4 Bitmap 23 2754 Press: Above Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Inj Bank 1 Barcode: PCC3300,
40422 5 Bitmap 23 2765 Out Of Calibration NONE PCC2300,
PCC3300V2
Fault Status Particulate Trap Regen PCC3300,
40422 6 Bitmap 23 2777 Inhibit: Condition Exists NONE PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter Outlet PCC3300,
40422 7 Bitmap 23 3133 Pressure: OORH Warning PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter Outlet PCC3300,
40422 8 Bitmap 23 3134 Pressure: OORL Warning PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter PCC3300,
40422 9 Bitmap 23 3135 Pressure: Data Eratic Warning PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter PCC3300,
40422 10 Bitmap 23 3245 System: Not Responding Warning PCC2300,
PCC3300V2
Fault Status Aft Catalyst Intake PCC3300,
40422 11 Bitmap 23 3251 Temp:Data Valid:Above Shutdown PCC2300,
Normal PCC3300V2

A029X159 (Issue 31) 855 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Particulate Filter Int Temp: PCC3300,
40422 12 Bitmap 23 3253 Above Normal Mod Sev Shutdown PCC2300,
PCC3300V2
Fault Status Particulate Filter Int Temp: PCC3300,
40422 13 Bitmap 23 3254 Above Normal Warning PCC2300,
PCC3300V2
Fault Status Particulate Filter Out Temp: PCC3300,
40422 14 Bitmap 23 3255 Above Normal Mod Sev Shutdown PCC2300,
PCC3300V2
Fault Status Particulate Filter Outlet PCC3300,
40422 15 Bitmap 23 3256 Temp: Above Normal Warning PCC2300,
PCC3300V2
Fault Status Particulate Filter Int Temp: PCC3300,
40423 0 Bitmap 24 3311 Above Normal Severe Shutdown PCC2300,
PCC3300V2
Fault Status Paticulate Filter Out Temp: PCC3300,
40423 1 Bitmap 24 3312 Above Normal Severe Shutdown PCC2300,
PCC3300V2
Fault Status Aft Catalyst Intake PCC3300,
40423 2 Bitmap 24 3313 Temperature: Below Normal Warning PCC2300,
PCC3300V2
Fault Status Aft Catalyst Intake PCC3300,
40423 3 Bitmap 24 3314 Temperature: Above Warning PCC2300,
Normal PCC3300V2
Fault Status Aft Catalyst Intake PCC3300,
40423 4 Bitmap 24 3315 Temperature: Incorrect Warning PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter Intake PCC3300,
40423 5 Bitmap 24 3316 Temperature: OORL Warning PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter Intake PCC3300,
40423 6 Bitmap 24 3317 Temperature: OORH Warning PCC2300,
PCC3300V2
Fault Status Af Particulate Filter Intake PCC3300,
40423 7 Bitmap 24 3318 Temp: Data Incorrect Warning PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter Outlet PCC3300,
40423 8 Bitmap 24 3319 Temp Circuit: OORH Warning PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter Outlet PCC3300,
40423 9 Bitmap 24 3321 Temp Circuit: OORL Warning PCC2300,
PCC3300V2
Fault Status Aft Particulate Filter Outlet PCC3300,
40423 10 Bitmap 24 3322 Temp: Data Incorrect Warning PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 856 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Aft Catalyst Intake Temp PCC3300,
40423 11 Bitmap 24 3325 Swapped: Out Of Cal Warning PCC2300,
PCC3300V2
Fault Status Gain Adjust Potentiometer PCC3300,
40423 12 Bitmap 24 3694 Circuit: OORL Warning PCC2300,
PCC3300V2
Fault Status Frequency Adjust PCC3300,
40423 13 Bitmap 24 3695 Potentiometer Circuit: Warning PCC2300,
OORL PCC3300V2
Fault Status Droop Adjust Potentiometer PCC3300,
40423 14 Bitmap 24 3696 Circuit: OORL Warning PCC2300,
PCC3300V2
Fault Status RAM Refresh Error PCC3300,
40423 15 Bitmap 24 3697 Shutdown PCC2300,
PCC3300V2
Fault Status Battery 1 Voltage: Below PCC3300,
40424 0 Bitmap 25 3724 Normal Warning PCC2300,
PCC3300V2
Fault Status Common Rail Fuel Press PCC3300,
40424 1 Bitmap 25 3727 Relief Valve: Not Resp NONE PCC2300,
PCC3300V2
Fault Status Common Rail Fuel PCC3300,
40424 2 Bitmap 25 3741 Pressure: Above Normal Warning PCC2300,
PCC3300V2
Fault Status Engine Protection System PCC3300,
40424 3 Bitmap 25 3931 Approaching Shutdown Shutdown PCC2300,
PCC3300V2
Fault Status Inducement Approaching: PCC3300,
40424 4 Bitmap 25 4135 Performance is Active Warning PCC2300,
PCC3300V2
Fault Status Prelube Cycle failed PCC3300,
40424 5 4883 Warning
Bitmap 25 PCC3300V2
Fault Status Prelube Pump Stuck ON PCC3300,
40424 6 4884 Warning
Bitmap 25 PCC3300V2
Fault Status Engine Crank Without PCC3300,
40424 7 4946 NONE
Bitmap 25 Prelube Condition Exists PCC3300V2
Fault Status Prelube Cycle failed during PCC3300,
40424 8 5149 Shutdown
Bitmap 25 Non-Emergency start PCC3300V2
Fault Status Genset Overload PCC3300,
40424 9 Bitmap 25 5135 Shutdown PCC2300,
PCC3300V2
Fault Status Intake air restriction PCC3300,
40424 10 5151 Warning
Bitmap 25 indicator 1 active PCC3300V2

A029X159 (Issue 31) 857 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Intake air restriction PCC3300,
40424 11 5152 Warning
Bitmap 25 indicator 2 active PCC3300V2
Fault Status Intake air restriction PCC3300,
40424 12 5153 Warning
Bitmap 25 indicator 3 active PCC3300V2
Fault Status Intake air restriction PCC3300,
40424 13 5154 Warning
Bitmap 25 indicator 4 active PCC3300V2
Fault Status Battery Charger 2 Failed PCC3300,
40424 14 5164 Warning
Bitmap 25 Fault PCC3300V2
Fault Status Battery Charger 3 Failed PCC3300,
40424 15 5165 Warning
Bitmap 25 Fault PCC3300V2
Event Status Exh Gas Temp Cyl 14 PCC3300,
40425 0 Bitmap 2 637 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 16 PCC3300,
40425 1 Bitmap 2 638 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Engine Oil Change Needed PCC3300,
40425 2 Bitmap 2 649 NONE PCC2300,
PCC3300V2
Event Status Pre Oil Filter Pressure PCC3300,
40425 3 Bitmap 2 1367 OORH NONE PCC2300,
PCC3300V2
Event Status Pre Oil Filter Pressure PCC3300,
40425 4 Bitmap 2 1368 OORL NONE PCC2300,
PCC3300V2
Event Status Aux Temp 1 Sensor OORH PCC3300,
40425 5 Bitmap 2 1369 NONE PCC2300,
PCC3300V2
Event Status Start Enable Device 1: PCC3300,
40425 6 Bitmap 2 1373 Cause Unknown NONE PCC2300,
PCC3300V2
Event Status Post Oil Filter Pressure PCC3300,
40425 7 Bitmap 2 1377 OORH NONE PCC2300,
PCC3300V2
Event Status Post Oil Filter Pressure PCC3300,
40425 8 Bitmap 2 1378 OORL NONE PCC2300,
PCC3300V2
Event Status Intake Manifold 1 Pressure PCC3300,
40425 9 Bitmap 2 1383 OORH NONE PCC2300,
PCC3300V2
Event Status Intake Manifold 1 Pressure PCC3300,
40425 10 Bitmap 2 1384 OORL NONE PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 858 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Event Status Intake Manifold 2 Pressure PCC3300,
40425 11 Bitmap 2 1385 OORH NONE PCC2300,
PCC3300V2
Event Status Intake Manifold 2 Pressure PCC3300,
40425 12 Bitmap 2 1386 OORL NONE PCC2300,
PCC3300V2
Event Status Aux Temp 1 Sensor OORL PCC3300,
40425 13 Bitmap 2 1596 NONE PCC2300,
PCC3300V2
Event Status ECM Critical Internal PCC3300,
40425 14 Bitmap 2 1597 Failure: Bad Device NONE PCC2300,
PCC3300V2
Event Status Exhaust Gas Temperature PCC3300,
40425 15 Bitmap 2 2651 Right Manifold: OORH NONE PCC2300,
PCC3300V2
Event Status Exhaust Gas Temperature PCC3300,
40426 0 Bitmap 3 2652 Right Manifold: OORL NONE PCC2300,
PCC3300V2
Event Status Exhaust Gas Temperature PCC3300,
40426 1 Bitmap 3 2655 Left Manifold: OORH NONE PCC2300,
PCC3300V2
Event Status Exhaust Gas Temperature PCC3300,
40426 2 Bitmap 3 2656 Left Manifold: OORL NONE PCC2300,
PCC3300V2
Event Status CBR_TFC_DERATE_ERR PCC3300,
40426 3 Bitmap 3 2346 OR_ID NONE PCC2300,
PCC3300V2
Event Status SCR Sys Cleaning Inhibited PCC3300,
40426 4 5631 NONE
Bitmap 3 due to System Timeout PCC3300V2
Event Status SCR Sys Cleaning Inhibited PCC3300,
40426 5 5632 NONE
Bitmap 3 due to Inhibit Switch PCC3300V2
Event Status Diesel Particulate Filter PCC3300,
40426 10 3753 NONE
Bitmap 3 Active Regen Inhibited PCC3300V2
Event Status Aftertreatment Diesel PCC3300,
40426 12 4842 NONE
Bitmap 3 Exhaust Fluid Quality High PCC3300V2
Fault Status Battery Charger 4 Failed PCC3300,
40427 0 5166 Warning
Bitmap 26 Fault PCC3300V2
Fault Status System Network Failure PCC3300,
40427 1 4872 Warning
Bitmap 26 PCC3300V2
Fault Status Genset Failed to Come PCC3300,
40427 2 4873 Warning
Bitmap 26 Online PCC3300V2
Fault Status Load Demand Version PCC3300,
40427 3 4874 Warning
Bitmap 26 Incompatibility PCC3300V2

A029X159 (Issue 31) 859 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Genset Ineligible For Load PCC3300,
40427 4 4875 NONE
Bitmap 26 Demand PCC3300V2
Fault Status Genset Lost On System PCC3300,
40427 5 4876 Warning
Bitmap 26 Network PCC3300V2
Fault Status System Settings Not PCC3300,
40427 6 4877 Warning
Bitmap 26 Synchronized PCC3300V2
Fault Status Check System Network PCC3300,
40427 7 4878 Warning
Bitmap 26 Installation PCC3300V2
Fault Status Load Demand Setup Error PCC3300,
40427 8 4879 Warning
Bitmap 26 PCC3300V2
Fault Status System Genset ID Conflict PCC3300,
40427 9 4881 Warning
Bitmap 26 PCC3300V2
Fault Status Genset Bus Overload PCC3300,
40427 10 4882 Warning
Bitmap 26 PCC3300V2
Fault Status Load Demand Genset Bus PCC3300,
40427 11 5145 Warning
Bitmap 26 Failure PCC3300V2
Fault Status Exhaust Stack Temp Left PCC3300,
40427 12 Bitmap 26 2658 Bank Above Sh Threshold Shutdown PCC2300,
PCC3300V2
Fault Status Crankcase Pressure:Above PCC3300,
40427 13 Bitmap 26 556 Normal-Most Severe Shutdown PCC2300,
PCC3300V2
Fault Status Auxiliary Input 1 Active- PCC3300,
40427 14 Bitmap 26 2619 Condition Exists Warning PCC2300,
PCC3300V2
Fault Status Exhaust Stack Temp Right PCC3300,
40427 15 Bitmap 26 2654 Bank Above Sh Threshold Shutdown PCC2300,
PCC3300V2
Fault Status AmpSentry Maintenance PCC3300,
40428 0 Bitmap 32 5399 Mode Active NONE PCC2300,
PCC3300V2
Fault Status OTIS Read Failed – PCC3300,
40428 1 5492 Warning
Bitmap 32 Unknown Reason PCC3300V2
Fault Status ECM Write Failed – Multiple PCC3300,
40428 2 5489 Warning
Bitmap 32 Tools connected to ECM PCC3300V2
Fault Status ECM Write Failed – PCC3300,
40428 3 5491 Warning
Bitmap 32 Unknown Reason PCC3300V2
Fault Status ECM Write Failed – Data PCC3300,
40428 4 5493 Warning
Bitmap 32 Save Failure PCC3300V2
Fault Status Prelube Setup Fault - PCC3300,
40428 5 5529 Warning
Bitmap 32 Condition Exists PCC3300V2

Copyright © 2023 Cummins Inc. 860 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Auxiliary PWM Driver 1 PCC3300,
40428 6 2557 Warning
Bitmap 32 Circuit OOR High PCC3300V2
Fault Status Turbocharger 1 Compressor PCC3300,
40428 8 743 Warning
Bitmap 32 Intake Pressure Error PCC3300V2
Fault Status Injector Metering Rail 1 PCC3300,
40428 9 755 Warning
Bitmap 32 Pressure System Error PCC3300V2
Fault Status UFD_INJECTOR_1_ERRO PCC3300,
40428 10 Bitmap 32 1139 R Warning PCC2300,
PCC3300V2
Fault Status UFD_INJECTOR_2_ERRO PCC3300,
40428 11 Bitmap 32 1141 R Warning PCC2300,
PCC3300V2
Fault Status UFD_INJECTOR_3_ERRO PCC3300,
40428 12 Bitmap 32 1142 R Warning PCC2300,
PCC3300V2
Fault Status UFD_INJECTOR_4_ERRO PCC3300,
40428 13 Bitmap 32 1143 R Warning PCC2300,
PCC3300V2
Fault Status UFD_INJECTOR_5_ERRO PCC3300,
40428 14 Bitmap 32 1144 R Warning PCC2300,
PCC3300V2
Fault Status UFD_INJECTOR_6_ERRO PCC3300,
40428 15 Bitmap 32 1145 R Warning PCC2300,
PCC3300V2
Event Status Not in Auto PS0500
40430 0 1463 NONE
Bitmap 1
Event Status Ready To Load PS0500
40430 1 1468 NONE
Bitmap 1
Event Status Common Alarm PS0500
40430 2 1483 NONE
Bitmap 1
Event Status Cold Start Advance - PS0500
40430 3 5671 NONE
Bitmap 1 Condition Exists
Event Status Common Warning PCC3300,
40430 0 Bitmap 1 1540 NONE PCC2300,
PCC3300V2
Event Status Common Shutdown PCC3300,
40430 1 Bitmap 1 1541 NONE PCC2300,
PCC3300V2
Event Status Exh Gas Temp Cyl 1 PCC3300,
40430 2 Bitmap 1 621 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 3 PCC3300,
40430 3 Bitmap 1 622 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2

A029X159 (Issue 31) 861 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Event Status Exh Gas Temp Cyl 5 PCC3300,
40430 4 Bitmap 1 623 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 7 PCC3300,
40430 5 Bitmap 1 624 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 9 PCC3300,
40430 6 Bitmap 1 625 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 11 PCC3300,
40430 7 Bitmap 1 626 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 13 PCC3300,
40430 8 Bitmap 1 627 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 15 PCC3300,
40430 9 Bitmap 1 628 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 2 PCC3300,
40430 10 Bitmap 1 631 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 4 PCC3300,
40430 11 Bitmap 1 632 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 6 PCC3300,
40430 12 Bitmap 1 633 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 8 PCC3300,
40430 13 Bitmap 1 634 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 10 PCC3300,
40430 14 Bitmap 1 635 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2
Event Status Exh Gas Temp Cyl 12 PCC3300,
40430 15 Bitmap 1 636 Deviation Low: Below NONE PCC2300,
Normal PCC3300V2

TABLE 47.

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status EPS Main Channel Lost PCC3300,
40431 0 Gas Bitmap 121 Error Warning PCC3300V2
1

Copyright © 2023 Cummins Inc. 862 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Oil Inlet Pressure High Error PCC3300,
40431 1 Gas Bitmap 136 Warning PCC3300V2
1
Fault Status Oil Inlet Pressure Low Error PCC3300,
40431 2 Gas Bitmap 137 Warning PCC3300V2
1
Fault Status Oil Overpressure Error PCC3300,
40431 3 Gas Bitmap 142 Warning PCC3300V2
1
Fault Status Intake Manifold Temp 2 PCC3300,
40431 4 Gas Bitmap 156 OORH Warning PCC3300V2
1
Fault Status Intake Manifold Temp 2 PCC3300,
40431 5 Gas Bitmap 157 OORL Warning PCC3300V2
1
Fault Status Intake Manifold Temp 2 PCC3300,
40431 6 Gas Bitmap 158 High Shutdown PCC3300V2
1
Fault Status Intake Manifold 3 Temp PCC3300,
40431 7 Gas Bitmap 159 OORH Warning PCC3300V2
1
Fault Status Intake Manifold 3 Temp PCC3300,
40431 8 Gas Bitmap 161 OORL Warning PCC3300V2
1
Fault Status Intake Manifold 3 Temp PCC3300,
40431 9 Gas Bitmap 162 High Shutdown PCC3300V2
1
Fault Status Intake Manifold 4 Temp PCC3300,
40431 10 Gas Bitmap 163 OORH Warning PCC3300V2
1
Fault Status Intake Manifold 4 Temp PCC3300,
40431 11 Gas Bitmap 164 OORL Warning PCC3300V2
1
Fault Status Intake Manifold 4 Temp PCC3300,
40431 12 Gas Bitmap 165 High Shutdown PCC3300V2
1
Fault Status Throttle_Driver_Feedback_ PCC3300,
Shutdown
40431 13 Gas Bitmap 175 High_Error PCC3300V2
w/Cooldown
1
Fault Status Throttle_Driver_Feedback_ PCC3300,
Shutdown
40431 14 Gas Bitmap 176 Low_Error PCC3300V2
w/Cooldown
1
Fault Status Throttle_Actuator_Error PCC3300,
Shutdown
40431 15 Gas Bitmap 177 PCC3300V2
w/Cooldown
1

A029X159 (Issue 31) 863 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Low Fuel Pressure PCC3300,
40432 0 Gas Bitmap 2118 Warning PCC2300,
2 PCC3300V2
Fault Status Fuel System on Secondary PCC3300,
40432 1 Gas Bitmap 5365 Source - Condition Exists Warning PCC2300,
2 PCC3300V2
Fault Status Red Stop Lamp Driver PCC3300,
40432 2 Gas Bitmap 244 OORL Warning PCC3300V2
2
Fault Status Exhaust Gas Temp Sensor PCC3300,
40432 3 Gas Bitmap 246 1 OORH Warning PCC3300V2
2
Fault Status Exhaust Gas Temp Sensor PCC3300,
40432 4 Gas Bitmap 247 1 OORL Warning PCC3300V2
2
Fault Status Exhaust Gas Temp Sensor PCC3300,
40432 5 Gas Bitmap 248 1 High Warning PCC3300V2
2
Fault Status Oil Level Low Error PCC3300,
Shutdown
40432 6 Gas Bitmap 253 PCC3300V2
w/Cooldown
2
Fault Status Fuel Control Valve Out of PCC3300,
40432 8 Gas Bitmap 277 Adj Warning PCC3300V2
2
Fault Status Powerdown Data Lost Error PCC3300,
40432 9 Gas Bitmap 346 Warning PCC3300V2
2
Fault Status Manifold_Absolute_Pressur PCC3300,
40432 10 Gas Bitmap 354 e_1_High_Error Warning PCC3300V2
2
Fault Status Manifold_Absolute_Pressur PCC3300,
40432 11 Gas Bitmap 355 e_1_Low_Error Warning PCC3300V2
2
Fault Status J1708 Link Cannot Transmit PCC3300,
40432 12 Gas Bitmap 412 Error NONE PCC3300V2
2
Fault Status J1708 Link Not Fast PCC3300,
40432 13 Gas Bitmap 414 Enough Error NONE PCC3300V2
2
Fault Status Gas_Mass_Flow_High_Erro PCC3300,
40432 14 Gas Bitmap 453 r Warning PCC3300V2
2
Fault Status Gas_Mass_Flow_Low_Error PCC3300,
40432 15 Gas Bitmap 454 Warning PCC3300V2
2

Copyright © 2023 Cummins Inc. 864 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Spark_Timing_B_Error PCC3300,
Shutdown
40433 0 Gas Bitmap 458 PCC3300V2
w/Cooldown
3
Fault Status Spark_Timing_A_Error PCC3300,
Shutdown
40433 1 Gas Bitmap 459 PCC3300V2
w/Cooldown
3
Fault Status Spark_Reference_B_Error PCC3300,
Shutdown
40433 2 Gas Bitmap 461 PCC3300V2
w/Cooldown
3
Fault Status Spark_Reference_A_Error PCC3300,
Shutdown
40433 3 Gas Bitmap 462 PCC3300V2
w/Cooldown
3
Fault Status Isolated Battery Voltage PCC3300,
40433 4 Gas Bitmap 477 Low Error Warning PCC3300V2
3
Fault Status Isolated Battery Voltage PCC3300,
40433 5 Gas Bitmap 478 High Error Warning PCC3300V2
3
Fault Status Throttle Pos 1 Feedback PCC3300,
40433 6 Gas Bitmap 512 OOR High Warning PCC3300V2
3
Fault Status Throttle Pos 1 Feedback PCC3300,
40433 7 Gas Bitmap 513 OOR Low Warning PCC3300V2
3
Fault Status Fuel Control Valve 2 OORH PCC3300,
Shutdown
40433 8 Gas Bitmap 557 PCC3300V2
w/Cooldown
3
Fault Status Fuel Control Valve 2 OORL PCC3300,
40433 9 Gas Bitmap 558 Warning PCC3300V2
3
Fault Status Heavy_Knock_Error_1_(A1) PCC3300,
Shutdown
40433 10 Gas Bitmap 561 PCC3300V2
w/Cooldown
3
Fault Status Heavy_Knock_Error_2_(B1) PCC3300,
Shutdown
40433 11 Gas Bitmap 562 PCC3300V2
w/Cooldown
3
Fault Status Heavy_Knock_Error_3_(A2) PCC3300,
Shutdown
40433 12 Gas Bitmap 563 PCC3300V2
w/Cooldown
3
Fault Status Heavy_Knock_Error_4_(B2) PCC3300,
Shutdown
40433 13 Gas Bitmap 564 PCC3300V2
w/Cooldown
3
Fault Status Heavy_Knock_Error_5_(A3) PCC3300,
Shutdown
40433 14 Gas Bitmap 565 PCC3300V2
w/Cooldown
3

A029X159 (Issue 31) 865 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Heavy_Knock_Error_6_(B3) PCC3300,
Shutdown
40433 15 Gas Bitmap 566 PCC3300V2
w/Cooldown
3
Fault Status Heavy_Knock_Error_7_(A4) PCC3300,
Shutdown
40434 0 Gas Bitmap 567 PCC3300V2
w/Cooldown
4
Fault Status Heavy_Knock_Error_8_(B4) PCC3300,
Shutdown
40434 1 Gas Bitmap 568 PCC3300V2
w/Cooldown
4
Fault Status Heavy_Knock_Error_9_(A5) PCC3300,
Shutdown
40434 2 Gas Bitmap 569 PCC3300V2
w/Cooldown
4
Fault Status Knock Cyl 1 (A1) OORL PCC3300,
40434 3 Gas Bitmap 571 Warning PCC3300V2
4
Fault Status Knock Cyl 2 (B1) OORL PCC3300,
40434 4 Gas Bitmap 572 Warning PCC3300V2
4
Fault Status Knock Cyl 3 (A2) OORL PCC3300,
40434 5 Gas Bitmap 573 Warning PCC3300V2
4
Fault Status Knock Cyl 4 (B2) OORL PCC3300,
40434 6 Gas Bitmap 574 Warning PCC3300V2
4
Fault Status Knock Cyl 5 (A3) OORL PCC3300,
40434 7 Gas Bitmap 575 Warning PCC3300V2
4
Fault Status Knock Cyl 6 (B3) OORL PCC3300,
40434 8 Gas Bitmap 576 Warning PCC3300V2
4
Fault Status Knock Cyl 7 (A4) OORL PCC3300,
40434 9 Gas Bitmap 577 Warning PCC3300V2
4
Fault Status Knock Cyl 8 (B4) OORL PCC3300,
40434 10 Gas Bitmap 578 Warning PCC3300V2
4
Fault Status Knock Cyl 9 (A5) OORL PCC3300,
40434 11 Gas Bitmap 579 Warning PCC3300V2
4
Fault Status High Side DRV3 High PCC3300,
40434 12 Gas Bitmap 584 Control Error Warning PCC3300V2
4
Fault Status High Side DRV3 Low PCC3300,
40434 13 Gas Bitmap 585 Control Error Warning PCC3300V2
4

Copyright © 2023 Cummins Inc. 866 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust_Backpressure_Hig PCC3300,
40434 14 Gas Bitmap 591 h_Error Warning PCC3300V2
4
Fault Status Exhaust_Backpressure_Lo PCC3300,
40434 15 Gas Bitmap 592 w_Error Warning PCC3300V2
4
Fault Status Turbo 1 Overspeed PCC3300,
40435 0 Gas Bitmap 595 Warning Error Warning PCC3300V2
5
Fault Status Turbo 1 Inlet Pressure High PCC3300,
40435 1 Gas Bitmap 618 Warning PCC3300V2
5
Fault Status Turbo 2 Inlet Press High PCC3300,
40435 2 Gas Bitmap 619 Warning PCC3300V2
5
Fault Status Exhaust Temp 1 (A1) High PCC3300,
Shutdown
40435 3 Gas Bitmap 641 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 3 (A2) High PCC3300,
Shutdown
40435 4 Gas Bitmap 642 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 5 (A3) High PCC3300,
Shutdown
40435 5 Gas Bitmap 643 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 7 (A4) High PCC3300,
Shutdown
40435 6 Gas Bitmap 644 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 9 (A5) High PCC3300,
Shutdown
40435 7 Gas Bitmap 645 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 11 (A6) High PCC3300,
Shutdown
40435 8 Gas Bitmap 646 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 13 (A7) High PCC3300,
Shutdown
40435 9 Gas Bitmap 647 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 15 (A8) High PCC3300,
Shutdown
40435 10 Gas Bitmap 648 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 17 (A9) High PCC3300,
Shutdown
40435 11 Gas Bitmap 651 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 2 (B1) High PCC3300,
Shutdown
40435 12 Gas Bitmap 652 Serious Error PCC3300V2
w/Cooldown
5

A029X159 (Issue 31) 867 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust Temp 4 (B2) High PCC3300,
Shutdown
40435 13 Gas Bitmap 653 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 6 (B3) High PCC3300,
Shutdown
40435 14 Gas Bitmap 654 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 8 (B4) High PCC3300,
Shutdown
40435 15 Gas Bitmap 655 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 10 (B5) High PCC3300,
Shutdown
40436 0 Gas Bitmap 656 Serious Error PCC3300V2
w/Cooldown
6
Fault Status Exhaust Temp 12 (B6) High PCC3300,
Shutdown
40436 1 Gas Bitmap 657 Serious Error PCC3300V2
w/Cooldown
6
Fault Status Exhaust Temp 14 (B7) High PCC3300,
Shutdown
40436 2 Gas Bitmap 658 Serious Error PCC3300V2
w/Cooldown
6
Fault Status Exhaust Gas Temp Cyl 1 PCC3300,
40436 3 Gas Bitmap 671 (A1) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 3 PCC3300,
40436 4 Gas Bitmap 672 (A2) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 5 PCC3300,
40436 5 Gas Bitmap 673 (A3) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 7 PCC3300,
40436 6 Gas Bitmap 674 (A4) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 9 PCC3300,
40436 7 Gas Bitmap 675 (A5) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 11 PCC3300,
40436 8 Gas Bitmap 676 (A6) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 13 PCC3300,
40436 9 Gas Bitmap 677 (A7) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 15 PCC3300,
40436 10 Gas Bitmap 678 (A8) OORL Warning PCC3300V2
6
Fault Status Turbo 2 Speed Moderate PCC3300,
40436 11 Gas Bitmap 683 High Warning PCC3300V2
6

Copyright © 2023 Cummins Inc. 868 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Turbo 2 Speed Moderate PCC3300,
40436 12 Gas Bitmap 684 Low Warning PCC3300V2
6
Fault Status Turbo 2 Speed Incorrect PCC3300,
40436 13 Gas Bitmap 685 Warning PCC3300V2
6
Fault Status Turbo 1 Speed Low PCC3300,
40436 15 Gas Bitmap 687 Warning PCC3300V2
6
Fault Status Exhaust Gas Temp 2 (B1) PCC3300,
40437 2 Gas Bitmap 721 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 4 (B2) PCC3300,
40437 3 Gas Bitmap 722 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 6 (B3) PCC3300,
40437 4 Gas Bitmap 723 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 8 (B4) PCC3300,
40437 5 Gas Bitmap 724 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 10 (B5) PCC3300,
40437 6 Gas Bitmap 725 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 12 (B6) PCC3300,
40437 7 Gas Bitmap 726 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 14 (B7) PCC3300,
40437 8 Gas Bitmap 727 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 16 (B8) PCC3300,
40437 9 Gas Bitmap 728 OORL Warning PCC3300V2
7
Fault Status Starter Air Pressure OORL PCC3300,
40437 10 Gas Bitmap 736 Warning PCC3300V2
7
Fault Status Starter Air Pressure OORH PCC3300,
40437 11 Gas Bitmap 737 Warning PCC3300V2
7
Fault Status Starter Air Press PCC3300,
40437 12 Gas Bitmap 738 Underpressure Error Warning PCC3300V2
7
Fault Status Air Filter Restriction PCC3300,
40437 13 Gas Bitmap 741 Pressure High Error Warning PCC3300V2
7

A029X159 (Issue 31) 869 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Air Filter Restriction PCC3300,
40437 14 Gas Bitmap 742 Pressure Low Error Warning PCC3300V2
7
Fault Status Gas_Mass_Flow_In_Range PCC3300,
40437 15 Gas Bitmap 751 _Error Warning PCC3300V2
7
Fault Status Exhaust_Gas_Oxygen_In_ PCC3300,
40438 0 Gas Bitmap 752 Range_Error Warning PCC3300V2
8
Fault Status Intake Manifold 1 Temp PCC3300,
Shutdown
40438 1 Gas Bitmap 783 Abnormal PCC3300V2
w/Cooldown
8
Fault Status COP_Overboost_Error PCC3300,
Shutdown
40438 2 Gas Bitmap 1213 PCC3300V2
w/Cooldown
8
Fault Status Heavy_Knock_Error_10_(B PCC3300,
Shutdown
40438 3 Gas Bitmap 1274 5) PCC3300V2
w/Cooldown
8
Fault Status Heavy_Knock_Error_12_(B PCC3300,
Shutdown
40438 4 Gas Bitmap 1281 6) PCC3300V2
w/Cooldown
8
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40438 5 Gas Bitmap 1285 rror_13_(A7) PCC3300V2
w/Cooldown
8
Fault Status Heavy_Knock_Error_13_(A PCC3300,
Shutdown
40438 6 Gas Bitmap 1286 7) PCC3300V2
w/Cooldown
8
Fault Status Heavy_Knock_Error_14_(B PCC3300,
Shutdown
40438 7 Gas Bitmap 1291 7) PCC3300V2
w/Cooldown
8
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40438 8 Gas Bitmap 1295 rror_15_(A8) PCC3300V2
w/Cooldown
8
Fault Status Heavy_Knock_Error_15_(A PCC3300,
Shutdown
40438 9 Gas Bitmap 1296 8) PCC3300V2
w/Cooldown
8
Fault Status Heavy_Knock_Error_18_(B PCC3300,
Shutdown
40438 10 Gas Bitmap 1311 9) PCC3300V2
w/Cooldown
8
Fault Status Oil Filter Restriction Error PCC3300,
40438 11 Gas Bitmap 1362 Warning PCC3300V2
8
Fault Status Fail To Synchronize PCC3300,
40438 13 Gas Bitmap 1457 Warning PCC3300V2
8

Copyright © 2023 Cummins Inc. 870 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Sync Phase Rotation PCC3300,
40438 14 Gas Bitmap 1458 Mismatch Warning PCC3300V2
8
Fault Status ECM Software mismatch PCC3300,
Shutdown
40438 15 Gas Bitmap 1474 PCC3300V2
w/Cooldown
8
Fault Status Exhaust Gas Temp 3 (A2) PCC3300,
40439 0 Gas Bitmap 1521 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 5 (A3) PCC3300,
40439 1 Gas Bitmap 1522 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 7 (A4) PCC3300,
40439 2 Gas Bitmap 1523 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 9 (A5) PCC3300,
40439 3 Gas Bitmap 1524 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 11 (A6) PCC3300,
40439 4 Gas Bitmap 1525 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 13 (A7) PCC3300,
40439 5 Gas Bitmap 1526 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 15 (A8) PCC3300,
40439 6 Gas Bitmap 1527 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 17 (A9) PCC3300,
40439 7 Gas Bitmap 1528 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 2 (B1) PCC3300,
40439 8 Gas Bitmap 1529 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 6 (B3) PCC3300,
40439 9 Gas Bitmap 1531 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 8 (B4) PCC3300,
40439 10 Gas Bitmap 1532 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 10 (B5) PCC3300,
40439 11 Gas Bitmap 1533 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 12 (B6) PCC3300,
40439 12 Gas Bitmap 1534 OORH Warning PCC3300V2
9

A029X159 (Issue 31) 871 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust Gas Temp 14 (B7) PCC3300,
40439 13 Gas Bitmap 1535 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 16 (B8) PCC3300,
40439 14 Gas Bitmap 1536 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 18 (B9) PCC3300,
40439 15 Gas Bitmap 1537 OORH Warning PCC3300V2
9
Fault Status EPS Backup Channel Lost PCC3300,
40440 0 Gas Bitmap 1545 Warning PCC3300V2
10
Fault Status EPS Main Channel Lost PCC3300,
40440 1 Gas Bitmap 1546 Warning PCC3300V2
10
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40440 2 Gas Bitmap 1579 rror_12_(B6) PCC3300V2
w/Cooldown
10
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40440 3 Gas Bitmap 1581 rror_14_(B7) PCC3300V2
w/Cooldown
10
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40440 4 Gas Bitmap 1582 rror_16_(B8) PCC3300V2
w/Cooldown
10
Fault Status Heavy_Knock_Error_16_(B PCC3300,
Shutdown
40440 5 Gas Bitmap 1583 8) PCC3300V2
w/Cooldown
10
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40440 6 Gas Bitmap 1587 rror_17_(A9) PCC3300V2
w/Cooldown
10
Fault Status Heavy_Knock_Error_17_(A PCC3300,
Shutdown
40440 7 Gas Bitmap 1588 9) PCC3300V2
w/Cooldown
10
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40440 8 Gas Bitmap 1593 rror_18_(B9) PCC3300V2
w/Cooldown
10
Fault Status Exhaust Gas Temp, Cyl 1 PCC3300,
40440 9 Gas Bitmap 1618 (A1) OORH Warning PCC3300V2
10
Fault Status Exhaust Gas Temp, Cyl 4 PCC3300,
40440 10 Gas Bitmap 1619 (B2) OORH Warning PCC3300V2
10
Fault Status Intake Manif Press 2 OORH PCC3300,
40440 11 Gas Bitmap 1636 Warning PCC3300V2
10

Copyright © 2023 Cummins Inc. 872 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Intake Manif Press 2 OORL PCC3300,
40440 12 Gas Bitmap 1637 Warning PCC3300V2
10
Fault Status CAN_Throttle_Internal_Fail PCC3300,
Shutdown
40440 13 Gas Bitmap 1737 ure_Error PCC3300V2
w/Cooldown
10
Fault Status CAN_Throttle_Internal_Faul PCC3300,
40440 14 Gas Bitmap 1738 t_Error Warning PCC3300V2
10
Fault Status Engine Throttle Control PCC3300,
40440 15 Gas Bitmap 1739 Condition Exists Warning PCC3300V2
10
Fault Status CAN_Throttle_High_Temp_ PCC3300,
40441 0 Gas Bitmap 1741 Warning_Error Warning PCC3300V2
11
Fault Status CAN_Throttle_Temp_Limitin PCC3300,
40441 1 Gas Bitmap 1742 g_Error Warning PCC3300V2
11
Fault Status Throttle Ctrl 2 OOR High PCC3300,
Shutdown
40441 2 Gas Bitmap 1743 PCC3300V2
w/Cooldown
11
Fault Status Throttle Ctrl 2 OOR Low PCC3300,
Shutdown
40441 3 Gas Bitmap 1744 PCC3300V2
w/Cooldown
11
Fault Status Throttle Ctrl 2 Incorrect PCC3300,
Shutdown
40441 4 Gas Bitmap 1745 PCC3300V2
w/Cooldown
11
Fault Status Throttle Ctrl 2 Out of PCC3300,
Shutdown
40441 5 Gas Bitmap 1746 Adjustment PCC3300V2
w/Cooldown
11
Fault Status Throttle Ctrl 2 Bad Device PCC3300,
Shutdown
40441 6 Gas Bitmap 1747 PCC3300V2
w/Cooldown
11
Fault Status Throttle Ctrl 2 Root PCC3300,
40441 7 Gas Bitmap 1748 Unknown Warning PCC3300V2
11
Fault Status Throttle Ctrl 2 Condition PCC3300,
40441 8 Gas Bitmap 1749 Exists Warning PCC3300V2
11
Fault Status Throttle Ctrl 2 Warning High PCC3300,
40441 9 Gas Bitmap 1751 Warning PCC3300V2
11
Fault Status Throttle Ctrl 2 Moderate PCC3300,
40441 10 Gas Bitmap 1752 High Warning PCC3300V2
11

A029X159 (Issue 31) 873 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Fuel Shutoff 2 OOR High PCC3300,
40441 11 Gas Bitmap 1753 Warning PCC3300V2
11
Fault Status Fuel Tmp 2 OOR High PCC3300,
40441 12 Gas Bitmap 1754 Warning PCC3300V2
11
Fault Status Fuel Tmp 2 OOR Low PCC3300,
40441 13 Gas Bitmap 1755 Warning PCC3300V2
11
Fault Status Gas Flow 2 OOR High PCC3300,
40441 14 Gas Bitmap 1756 Warning PCC3300V2
11
Fault Status Gas Flow 2 OOR Low PCC3300,
40441 15 Gas Bitmap 1757 Warning PCC3300V2
11
Fault Status Gas Flow 2 Incorrect Data PCC3300,
40442 0 Gas Bitmap 1758 Warning PCC3300V2
12
Fault Status FCV 2 Pos Feedback PCC3300,
Shutdown
40442 1 Gas Bitmap 1759 Incorrect PCC3300V2
w/Cooldown
12
Fault Status FCV_Actuator_Error_1761 PCC3300,
Shutdown
40442 2 Gas Bitmap 1761 PCC3300V2
w/Cooldown
12
Fault Status Int Man 2 Tmp Moderate PCC3300,
40442 3 Gas Bitmap 1984 High Warning PCC3300V2
12
Fault Status FCV 2 In Pr OOR High PCC3300,
40442 4 Gas Bitmap 1765 Warning PCC3300V2
12
Fault Status FCV 2 In Pr OOR Low PCC3300,
40442 5 Gas Bitmap 1766 Warning PCC3300V2
12
Fault Status FCV 2 Out Pr OOR High PCC3300,
40442 6 Gas Bitmap 1767 Warning PCC3300V2
12
Fault Status FCV 2 Out Pr OOR Low PCC3300,
40442 7 Gas Bitmap 1768 Warning PCC3300V2
12
Fault Status E_Shutd Indication OORH PCC3300,
40442 8 Gas Bitmap 1769 Warning PCC3300V2
12
Fault Status E_Shutd Indication OORL PCC3300,
40442 9 Gas Bitmap 1771 Warning PCC3300V2
12

Copyright © 2023 Cummins Inc. 874 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Eng Derate Request OORH PCC3300,
40442 10 Gas Bitmap 1772 Warning PCC3300V2
12
Fault Status Eng Derate Request OORL PCC3300,
40442 11 Gas Bitmap 1773 Warning PCC3300V2
12
Fault Status Oil Priming Pump OORH PCC3300,
40442 12 Gas Bitmap 1774 Warning PCC3300V2
12
Fault Status Oil Priming Pump OORL PCC3300,
40442 13 Gas Bitmap 1775 Warning PCC3300V2
12
Fault Status Power Conservation Control PCC3300,
40442 14 Gas Bitmap 3362 OORH Warning PCC3300V2
12
Fault Status Power Conservation Control PCC3300,
40442 15 Gas Bitmap 3363 OORL Warning PCC3300V2
12
Fault Status Engine_Heater_Control_Dri PCC3300,
40443 0 Gas Bitmap 1778 ver_High_Error Warning PCC3300V2
13
Fault Status Engine_Heater_Control_Dri PCC3300,
40443 1 Gas Bitmap 1779 ver_Low_Error Warning PCC3300V2
13
Fault Status Shutd Request OOR High PCC3300,
40443 2 Gas Bitmap 1781 Warning PCC3300V2
13
Fault Status Shutd Request OOR Low PCC3300,
40443 3 Gas Bitmap 1782 Warning PCC3300V2
13
Fault Status Coolant_Pump_Control_Dri PCC3300,
40443 4 Gas Bitmap 1783 ver_High_Error Warning PCC3300V2
13
Fault Status Coolant_Pump_Control_Dri PCC3300,
40443 5 Gas Bitmap 1784 ver_Low_Error Warning PCC3300V2
13
Fault Status Oil_Priming_Pump_Manual PCC3300,
40443 6 Gas Bitmap 1785 _Override_Input_On Warning PCC3300V2
13
Fault Status Oil_Priming_Pump_Stuck_ PCC3300,
40443 7 Gas Bitmap 1786 On_Error Warning PCC3300V2
13
Fault Status Post_Lube_Oil_Priming_Err PCC3300,
40443 8 Gas Bitmap 1787 or Warning PCC3300V2
13

A029X159 (Issue 31) 875 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Maintenance_Lube_Oil_Pri PCC3300,
40443 9 Gas Bitmap 1788 ming_Error Warning PCC3300V2
13
Fault Status Pre_Start_Lube_Oil_Primin PCC3300,
Shutdown
40443 10 Gas Bitmap 1789 g_Error PCC3300V2
w/Cooldown
13
Fault Status Failure_To_Meet_Load_Sp PCC3300,
Shutdown
40443 11 Gas Bitmap 1791 eed_Error PCC3300V2
w/Cooldown
13
Fault Status Idle when CB Closed PCC3300,
40443 12 Gas Bitmap 1792 Warning PCC3300V2
13
Fault Status Speed/Posit sensor out of PCC3300,
40443 13 Gas Bitmap 1793 Adj Warning PCC3300V2
13
Fault Status Fire Detected PCC3300,
40443 14 Gas Bitmap 1794 Shutdown PCC3300V2
13
Fault Status Compressor_Bypass_Positi PCC3300,
40443 15 Gas Bitmap 1795 on_High_Error Warning PCC3300V2
13
Fault Status Compressor_Bypass_Positi PCC3300,
40444 0 Gas Bitmap 1796 on_Low_Error Warning PCC3300V2
14
Fault Status Compressor Bypass ctrl PCC3300,
40444 1 Gas Bitmap 1797 OORH Warning PCC3300V2
14
Fault Status Compressor Bypass ctrl PCC3300,
40444 2 Gas Bitmap 1798 OORL Warning PCC3300V2
14
Fault Status CB_Position_Err_Status PCC3300,
40444 3 Gas Bitmap 1799 Warning PCC3300V2
14
Fault Status HIGH_SIDE_DRV2_High_C PCC3300,
40444 4 Gas Bitmap 1811 ontrol_Error (VPS) Warning PCC3300V2
14
Fault Status HIGH_SIDE_DRV2_Low_C PCC3300,
40444 5 Gas Bitmap 1812 ontrol_Error (VPS) Warning PCC3300V2
14
Fault Status Valve_Proving_System_Tes PCC3300,
40444 6 Gas Bitmap 1813 t_Failed_Warning_Error Warning PCC3300V2
14
Fault Status Valve_Proving_System_Tes PCC3300,
Shutdown
40444 7 Gas Bitmap 1814 t_Failed_Shutdown_Error PCC3300V2
w/Cooldown
14

Copyright © 2023 Cummins Inc. 876 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status RLY14_High_Control_Error PCC3300,
40444 8 Gas Bitmap 1815 Warning PCC3300V2
14
Fault Status Oil PreHtr Ctrl OOR Low PCC3300,
40444 9 Gas Bitmap 1816 Warning PCC3300V2
14
Fault Status Oil_Pre- PCC3300,
40444 10 Gas Bitmap 1817 Heater_Tripped_Error Warning PCC3300V2
14
Fault Status Oil_Pre- PCC3300,
40444 11 Gas Bitmap 1818 Heater_Not_Warming_Error Warning PCC3300V2
14
Fault Status Common AC Aux CB PCC3300,
40444 12 Gas Bitmap 1819 tripped Warning PCC3300V2
14
Fault Status Min_FSO_Speed_Error PCC3300,
Shutdown
40444 13 Gas Bitmap 1821 PCC3300V2
w/Cooldown
14
Fault Status LT Coolant Level Low PCC3300,
Shutdown
40444 14 Gas Bitmap 1822 Shutdown Error PCC3300V2
w/Cooldown
14
Fault Status LT Coolant Level Low PCC3300,
40444 15 Gas Bitmap 1823 Warning Error Warning PCC3300V2
14
Fault Status Idle_Rated_Trans_Oil_Tem PCC3300,
40445 0 Gas Bitmap 1824 p_Low_Error Warning PCC3300V2
15
Fault Status Dirty_Oil_Level_Error PCC3300,
40445 1 Gas Bitmap 1825 Warning PCC3300V2
15
Fault Status ECM Software incompatible PCC3300,
Shutdown
40445 2 Gas Bitmap 1826 PCC3300V2
w/Cooldown
15
Fault Status Fuel_Inlet_Pressure_High_ PCC3300,
40445 3 Gas Bitmap 1827 Error Warning PCC3300V2
15
Fault Status Fuel_Inlet_Pressure_Low_E PCC3300,
40445 4 Gas Bitmap 1828 rror Warning PCC3300V2
15
Fault Status Vent_Gas_Valve_Error PCC3300,
Shutdown
40445 5 Gas Bitmap 1829 PCC3300V2
w/Cooldown
15
Fault Status Upstream_FSO_Valve_Erro PCC3300,
Shutdown
40445 6 Gas Bitmap 1831 r PCC3300V2
w/Cooldown
15

A029X159 (Issue 31) 877 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Downstream_FSO_Valve_E PCC3300,
Shutdown
40445 7 Gas Bitmap 1832 rror PCC3300V2
w/Cooldown
15
Fault Status Engine_Heater_Trip_Error PCC3300,
40445 8 Gas Bitmap 1833 Warning PCC3300V2
15
Fault Status Coolant_Pump_Trip_Error PCC3300,
40445 9 Gas Bitmap 1834 Warning PCC3300V2
15
Fault Status Oil_Priming_Pump_Tripped PCC3300,
40445 10 Gas Bitmap 1835 _Error Warning PCC3300V2
15
Fault Status LCP_(LT)_Low_Serious_Err PCC3300,
Shutdown
40445 11 Gas Bitmap 1836 or PCC3300V2
w/Cooldown
15
Fault Status Permanent_FS_Cam_Sync PCC3300,
Shutdown
40445 12 Gas Bitmap 1837 _Lost_Error PCC3300V2
w/Cooldown
15
Fault Status Partial_Engine_Overload_S PCC3300,
Shutdown
40445 13 Gas Bitmap 1838 hutdown_Error PCC3300V2
w/Cooldown
15
Fault Status Fuel_Supply_Pressure_Hig PCC3300,
40445 14 Gas Bitmap 1839 h_Error Warning PCC3300V2
15
Fault Status Fuel_Supply_Pressure_Low PCC3300,
40445 15 Gas Bitmap 1841 _Error Warning PCC3300V2
15
Fault Status Radiator_Fan_Trip_Error PCC3300,
40446 0 Gas Bitmap 1842 Warning PCC3300V2
16
Fault Status Exhaust Aft Inlet O2 OOR PCC3300,
40446 1 Gas Bitmap 1858 High Warning PCC3300V2
16
Fault Status Exhaust Aft Inlet O2 OOR PCC3300,
40446 2 Gas Bitmap 1859 Low Warning PCC3300V2
16
Fault Status Exhaust Aft Inlet O2 PCC3300,
40446 3 Gas Bitmap 1861 Incorrect Warning PCC3300V2
16
Fault Status Exhaust Aft Out O2 OOR PCC3300,
40446 4 Gas Bitmap 1862 High Warning PCC3300V2
16
Fault Status Exhaust Aft Outlet O2 OOR PCC3300,
40446 5 Gas Bitmap 1863 Low Warning PCC3300V2
16

Copyright © 2023 Cummins Inc. 878 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust Aft Outlet O2 PCC3300,
40446 6 Gas Bitmap 1864 Incorrect Warning PCC3300V2
16
Fault Status Int Man 3 Tmp Moderate PCC3300,
40446 7 Gas Bitmap 1985 High Warning PCC3300V2
16
Fault Status Int Man 4 Tmp Moderate PCC3300,
40446 8 Gas Bitmap 1986 High Warning PCC3300V2
16
Fault Status Coolant_Inlet_Temperature PCC3300,
40446 9 Gas Bitmap 2111 _(LT)_High_Error Warning PCC3300V2
16
Fault Status Coolant_Inlet_Temperature PCC3300,
40446 10 Gas Bitmap 2112 _(LT)_Low_Error Warning PCC3300V2
16
Fault Status CIT_(LT)_High_Warning_Er PCC3300,
40446 11 Gas Bitmap 2113 ror Warning PCC3300V2
16
Fault Status CIT_(LT)_High_Serious_Err PCC3300,
40446 12 Gas Bitmap 2114 or Shutdown PCC3300V2
16
Fault Status LT_Coolant_Pressure_High PCC3300,
40446 13 Gas Bitmap 2115 _Error Warning PCC3300V2
16
Fault Status LT_Coolant_Pressure_Low PCC3300,
40446 14 Gas Bitmap 2116 _Error Warning PCC3300V2
16
Fault Status LCP_(LT)_Low_Warning_Er PCC3300,
40446 15 Gas Bitmap 2117 ror Warning PCC3300V2
16
Fault Status Exhaust_Temp_1_(A1)_Hig PCC3300,
40447 0 Gas Bitmap 2121 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_3_(A2)_Hig PCC3300,
40447 1 Gas Bitmap 2122 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_5_(A3)_Hig PCC3300,
40447 2 Gas Bitmap 2123 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_7_(A4)_Hig PCC3300,
40447 3 Gas Bitmap 2124 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_9_(A5)_Hig PCC3300,
40447 4 Gas Bitmap 2125 h_Warning_Error Warning PCC3300V2
17

A029X159 (Issue 31) 879 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust_Temp_11_(A6)_Hi PCC3300,
40447 5 Gas Bitmap 2126 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_13_(A7)_Hi PCC3300,
40447 6 Gas Bitmap 2127 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_15_(A8)_Hi PCC3300,
40447 7 Gas Bitmap 2128 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_17_(A9)_Hi PCC3300,
40447 8 Gas Bitmap 2129 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_2_(B1)_Hig PCC3300,
40447 9 Gas Bitmap 2131 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_4_(B2)_Hig PCC3300,
40447 10 Gas Bitmap 2132 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_6_(B3)_Hig PCC3300,
40447 11 Gas Bitmap 2133 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_8_(B4)_Hig PCC3300,
40447 12 Gas Bitmap 2134 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_10_(B5)_Hi PCC3300,
40447 13 Gas Bitmap 2135 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_12_(B6)_Hi PCC3300,
40447 14 Gas Bitmap 2136 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_14_(B7)_Hi PCC3300,
40447 15 Gas Bitmap 2137 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_16_(B8)_Hi PCC3300,
40448 0 Gas Bitmap 2138 gh_Warning_Error Warning PCC3300V2
18
Fault Status Exhaust_Temp_18_(B9)_Hi PCC3300,
40448 1 Gas Bitmap 2139 gh_Warning_Error Warning PCC3300V2
18
Fault Status Start_Air_Pressure_High_Er PCC3300,
40448 2 Gas Bitmap 2141 ror Warning PCC3300V2
18
Fault Status Start_Air_Pressure_Low_Er PCC3300,
40448 3 Gas Bitmap 2142 ror Warning PCC3300V2
18

Copyright © 2023 Cummins Inc. 880 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status SAP_Overpressure_Error PCC3300,
40448 4 Gas Bitmap 2143 Warning PCC3300V2
18
Fault Status Exhaust Temp 16 (B8) High PCC3300,
Shutdown
40448 5 Gas Bitmap 2144 Serious Error PCC3300V2
w/Cooldown
18
Fault Status Exhaust Temp 18 (B9) High PCC3300,
Shutdown
40448 6 Gas Bitmap 2145 Serious Error PCC3300V2
w/Cooldown
18
Fault Status EGT 17 (A9) OOR Low PCC3300,
40448 7 Gas Bitmap 2146 Warning PCC3300V2
18
Fault Status EGT 18 (B9) OOR Low PCC3300,
40448 8 Gas Bitmap 2147 Warning PCC3300V2
18
Fault Status Oil_Filter_Outlet_Pressure_ PCC3300,
40448 9 Gas Bitmap 2154 High_Error Warning PCC3300V2
18
Fault Status Oil_Filter_Outlet_Pressure_ PCC3300,
40448 10 Gas Bitmap 2155 Low_Error Warning PCC3300V2
18
Fault Status Int Man 2 Tmp Abnormal PCC3300,
Shutdown
40448 11 Gas Bitmap 2157 Rate PCC3300V2
w/Cooldown
18
Fault Status Int Man 3 Tmp Abnormal PCC3300,
Shutdown
40448 12 Gas Bitmap 2158 Rate PCC3300V2
w/Cooldown
18
Fault Status Int Man 4 Tmp Abnormal PCC3300,
Shutdown
40448 13 Gas Bitmap 2159 Rate PCC3300V2
w/Cooldown
18
Fault Status Exhaust O2 OOR High PCC3300,
40448 14 Gas Bitmap 2188 Warning PCC3300V2
18
Fault Status ST_Throttle_Press_Err_Stat PCC3300,
40448 15 Gas Bitmap 2191 us Warning PCC3300V2
18
Fault Status Exhaust O2 OOR Low PCC3300,
40449 0 Gas Bitmap 2192 Warning PCC3300V2
19
Fault Status RAM_Image_Word_Error PCC3300,
40449 1 Gas Bitmap 2217 Warning PCC3300V2
19
Fault Status Exhaust O2 Moderate High PCC3300,
40449 2 Gas Bitmap 2219 Warning PCC3300V2
19

A029X159 (Issue 31) 881 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust O2 Moderate Low PCC3300,
40449 3 Gas Bitmap 2221 Warning PCC3300V2
19
Fault Status Knock 11 (A6) Moderate PCC3300,
Shutdown
40449 4 Gas Bitmap 2281 High PCC3300V2
w/Cooldown
19
Fault Status Knock 11 (A6) Critical High PCC3300,
Shutdown
40449 5 Gas Bitmap 2282 PCC3300V2
w/Cooldown
19
Fault Status Fuel Shutoff 2 OOR Low PCC3300,
40449 6 Gas Bitmap 2298 Warning PCC3300V2
19
Fault Status Red Lamp OOR High PCC3300,
40449 7 Gas Bitmap 2315 Warning PCC3300V2
19
Fault Status Amber Lamp OOR High PCC3300,
40449 8 Gas Bitmap 2316 Warning PCC3300V2
19
Fault Status Amber Lamp OOR Low PCC3300,
40449 9 Gas Bitmap 2317 Warning PCC3300V2
19
Fault Status Fuel_Outlet_Pressure_High PCC3300,
40449 10 Gas Bitmap 2427 _Error Warning PCC3300V2
19
Fault Status Fuel_Outlet_Pressure_Low PCC3300,
40449 11 Gas Bitmap 2428 _Error Warning PCC3300V2
19
Fault Status Total Real Power Circuit PCC3300,
40449 12 Gas Bitmap 2453 OORH Warning PCC3300V2
19
Fault Status Total Real Power Circuit PCC3300,
40449 13 Gas Bitmap 2454 OORL Warning PCC3300V2
19
Fault Status Speed_Bias_Low_Error PCC3300,
40449 14 Gas Bitmap 2455 Warning PCC3300V2
19
Fault Status Speed_Bias_High_Error PCC3300,
40449 15 Gas Bitmap 2456 Warning PCC3300V2
19
Fault Status Max_Total_Misfire_Error PCC3300,
Shutdown
40450 0 Gas Bitmap 2457 PCC3300V2
w/Cooldown
20
Fault Status Cylinder_2_(B1)_Total_Misfi PCC3300,
40450 1 Gas Bitmap 2458 re_Error Warning PCC3300V2
20

Copyright © 2023 Cummins Inc. 882 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Cylinder_4_(B2)_Total_Misfi PCC3300,
40450 2 Gas Bitmap 2459 re_Error Warning PCC3300V2
20
Fault Status Cylinder_6_(B3)_Total_Misfi PCC3300,
40450 3 Gas Bitmap 2461 re_Error Warning PCC3300V2
20
Fault Status Cylinder_8_(B4)_Total_Misfi PCC3300,
40450 4 Gas Bitmap 2462 re_Error Warning PCC3300V2
20
Fault Status Cylinder_10_(B5)_Total_Mi PCC3300,
40450 5 Gas Bitmap 2463 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_12_(B6)_Total_Mi PCC3300,
40450 6 Gas Bitmap 2464 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_14_(B7)_Total_Mi PCC3300,
40450 7 Gas Bitmap 2465 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_16_(B8)_Total_Mi PCC3300,
40450 8 Gas Bitmap 2466 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_18_(B9)_Total_Mi PCC3300,
40450 9 Gas Bitmap 2467 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_1_(A1)_Total_Misfi PCC3300,
40450 10 Gas Bitmap 2469 re_Error Warning PCC3300V2
20
Fault Status Cylinder_3_(A2)_Total_Misfi PCC3300,
40450 11 Gas Bitmap 2471 re_Error Warning PCC3300V2
20
Fault Status Cylinder_5_(A3)_Total_Misfi PCC3300,
40450 12 Gas Bitmap 2472 re_Error Warning PCC3300V2
20
Fault Status Cylinder_7_(A4)_Total_Misfi PCC3300,
40450 13 Gas Bitmap 2473 re_Error Warning PCC3300V2
20
Fault Status Cylinder_9_(A5)_Total_Misfi PCC3300,
40450 14 Gas Bitmap 2475 re_Error Warning PCC3300V2
20
Fault Status Cylinder_11_(A6)_Total_Mi PCC3300,
40450 15 Gas Bitmap 2476 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_13_(A7)_Total_Mi PCC3300,
40451 0 Gas Bitmap 2477 sfire_Error Warning PCC3300V2
21

A029X159 (Issue 31) 883 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Cylinder_15_(A8)_Total_Mi PCC3300,
40451 1 Gas Bitmap 2478 sfire_Error Warning PCC3300V2
21
Fault Status Cylinder_17_(A9)_Total_Mi PCC3300,
40451 2 Gas Bitmap 2479 sfire_Error Warning PCC3300V2
21
Fault Status Start_Before_Ready_Error PCC3300,
Shutdown
40451 3 Gas Bitmap 2482 PCC3300V2
w/Cooldown
21
Fault Status Continuous_Starter_Failure PCC3300,
Shutdown
40451 4 Gas Bitmap 2483 _Error PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 1 PCC3300,
Shutdown
40451 5 Gas Bitmap 2484 (A1) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 3 PCC3300,
Shutdown
40451 6 Gas Bitmap 2485 (A2) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 5 PCC3300,
Shutdown
40451 7 Gas Bitmap 2486 (A3) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 7 PCC3300,
Shutdown
40451 8 Gas Bitmap 2487 (A4) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 9 PCC3300,
Shutdown
40451 9 Gas Bitmap 2488 (A5) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 11 PCC3300,
Shutdown
40451 10 Gas Bitmap 2489 (A6) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 13 PCC3300,
Shutdown
40451 11 Gas Bitmap 2491 (A7) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 15 PCC3300,
Shutdown
40451 12 Gas Bitmap 2492 (A8) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 17 PCC3300,
Shutdown
40451 13 Gas Bitmap 2493 (A9) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 2 PCC3300,
Shutdown
40451 14 Gas Bitmap 2494 (B1) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 4 PCC3300,
Shutdown
40451 15 Gas Bitmap 2495 (B2) Abnormal Rate PCC3300V2
w/Cooldown
21

Copyright © 2023 Cummins Inc. 884 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust Temperature 6 PCC3300,
Shutdown
40452 0 Gas Bitmap 2496 (B3) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 8 PCC3300,
Shutdown
40452 1 Gas Bitmap 2497 (B4) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 10 PCC3300,
Shutdown
40452 2 Gas Bitmap 2498 (B5) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 12 PCC3300,
Shutdown
40452 3 Gas Bitmap 2499 (B6) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 14 PCC3300,
Shutdown
40452 4 Gas Bitmap 2511 (B7) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 16 PCC3300,
Shutdown
40452 5 Gas Bitmap 2512 (B8) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 18 PCC3300,
Shutdown
40452 6 Gas Bitmap 2513 (B9) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Compressor_Outlet_Pressu PCC3300,
40452 7 Gas Bitmap 2517 re_High_Error Warning PCC3300V2
22
Fault Status Compressor_Outlet_Pressu PCC3300,
40452 8 Gas Bitmap 2518 re_Low_Error Warning PCC3300V2
22
Fault Status Bank_Id_Error PCC3300,
Shutdown
40452 9 Gas Bitmap 2521 PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 10 Gas Bitmap 2522 rror_1_(A1) PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 11 Gas Bitmap 2523 rror_2_(B1) PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 12 Gas Bitmap 2524 rror_3_(A2) PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 13 Gas Bitmap 2525 rror_4_(B2) PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 14 Gas Bitmap 2526 rror_5_(A3) PCC3300V2
w/Cooldown
22

A029X159 (Issue 31) 885 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 15 Gas Bitmap 2527 rror_6_(B3) PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40453 0 Gas Bitmap 2528 rror_7_(A4) PCC3300V2
w/Cooldown
23
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40453 1 Gas Bitmap 2529 rror_8_(B4) PCC3300V2
w/Cooldown
23
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40453 2 Gas Bitmap 2531 rror_9_(A5) PCC3300V2
w/Cooldown
23
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40453 3 Gas Bitmap 2532 rror_10_(B5) PCC3300V2
w/Cooldown
23
Fault Status ECM_Overtemp_Error PCC3300,
Shutdown
40453 4 Gas Bitmap 2544 PCC3300V2
w/Cooldown
23
Fault Status DG_Air_Compressor_Trip_ PCC3300,
40453 5 Gas Bitmap 2567 Error Warning PCC3300V2
23
Fault Status Throttle Pos 2 Feedback PCC3300,
40453 6 Gas Bitmap 2643 OOR High Warning PCC3300V2
23
Fault Status Throttle Pos 2 Feedback PCC3300,
40453 7 Gas Bitmap 2644 OOR Low Warning PCC3300V2
23
Fault Status Gas Supply Pr Moderate PCC3300,
40453 9 Gas Bitmap 2724 High Warning PCC3300V2
23
Fault Status Gas Supply Pr Moderate PCC3300,
40453 10 Gas Bitmap 2725 Low Warning PCC3300V2
23
Fault Status Exh Gas Tmp Critical High PCC3300,
Shutdown
40453 11 Gas Bitmap 2737 PCC3300V2
w/Cooldown
23
Fault Status Bank_A_CCD_Failed_Error PCC3300,
Shutdown
40453 12 Gas Bitmap 2766 PCC3300V2
w/Cooldown
23
Fault Status Bank_B_CCD_Failed_Error PCC3300,
Shutdown
40453 13 Gas Bitmap 2767 PCC3300V2
w/Cooldown
23
Fault Status CAN Parent Communication PCC3300,
Shutdown
40453 14 Gas Bitmap 2768 Incorrect PCC3300V2
w/Cooldown
23

Copyright © 2023 Cummins Inc. 886 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status CAN Child Com Incorrect PCC3300,
Shutdown
40453 15 Gas Bitmap 2769 PCC3300V2
w/Cooldown
23
Fault Status COT_Low_Error PCC3300,
40454 0 Gas Bitmap 2789 Warning PCC3300V2
24
Fault Status COT_Low_Serious_Error PCC3300,
Shutdown
40454 1 Gas Bitmap 2793 PCC3300V2
w/Cooldown
24
Fault Status Ign Shutd Relay OOR High PCC3300,
40454 2 Gas Bitmap 2794 Warning PCC3300V2
24
Fault Status Ign Shutd Relay OOR Low PCC3300,
40454 3 Gas Bitmap 2795 Warning PCC3300V2
24
Fault Status Partial_Engine_Overload_W PCC3300,
40454 4 Gas Bitmap 2796 arning_Error Warning PCC3300V2
24
Fault Status Inlet Gas Diff Pressure PCC3300,
40454 5 Gas Bitmap 2797 OOR High Warning PCC3300V2
24
Fault Status Inlet Gas Diff Pressure PCC3300,
40454 6 Gas Bitmap 2798 OOR Low Warning PCC3300V2
24
Fault Status IMOP_Compressor_Outlet_ PCC3300,
Shutdown
40454 7 Gas Bitmap 2799 Presure_Delta_Error PCC3300V2
w/Cooldown
24
Fault Status IMOP_Compressor_Outlet_ PCC3300,
Shutdown
40454 8 Gas Bitmap 2811 Pressure_Maximum_Error PCC3300V2
w/Cooldown
24
Fault Status Exhaust_Temp_1_(A1)_Dev PCC3300,
40454 9 Gas Bitmap 2837 iation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_3_(A2)_Dev PCC3300,
40454 10 Gas Bitmap 2838 iation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_5_(A3)_Dev PCC3300,
40454 11 Gas Bitmap 2839 iation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_7_(A4)_Dev PCC3300,
40454 12 Gas Bitmap 2841 iation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_9_(A5)_Dev PCC3300,
40454 13 Gas Bitmap 2842 iation_Error Warning PCC3300V2
24

A029X159 (Issue 31) 887 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust_Temp_11_(A6)_D PCC3300,
40454 14 Gas Bitmap 2843 eviation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_13_(A7)_D PCC3300,
40454 15 Gas Bitmap 2844 eviation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_15_(A8)_D PCC3300,
40455 0 Gas Bitmap 2845 eviation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_17_(A9)_D PCC3300,
40455 1 Gas Bitmap 2846 eviation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_2_(B1)_Dev PCC3300,
40455 2 Gas Bitmap 2847 iation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_4_(B2)_Dev PCC3300,
40455 3 Gas Bitmap 2848 iation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_6_(B3)_Dev PCC3300,
40455 4 Gas Bitmap 2849 iation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_8_(B4)_Dev PCC3300,
40455 5 Gas Bitmap 2851 iation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_10_(B5)_D PCC3300,
40455 6 Gas Bitmap 2852 eviation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_12_(B6)_D PCC3300,
40455 7 Gas Bitmap 2853 eviation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_14_(B7)_D PCC3300,
40455 8 Gas Bitmap 2854 eviation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_16_(B8)_D PCC3300,
40455 9 Gas Bitmap 2855 eviation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_18_(B9)_D PCC3300,
40455 10 Gas Bitmap 2856 eviation_Error Warning PCC3300V2
25
Fault Status Turbo_1_Overspeed_Critica PCC3300,
Shutdown
40455 11 Gas Bitmap 2857 l_Error PCC3300V2
w/Cooldown
25
Fault Status Turbo_2_Overspeed_Critica PCC3300,
Shutdown
40455 12 Gas Bitmap 2858 l_Error PCC3300V2
w/Cooldown
25

Copyright © 2023 Cummins Inc. 888 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Alt Heater Ctrl OOR High PCC3300,
40455 13 Gas Bitmap 2859 Warning PCC3300V2
25
Fault Status Alt Heater Ctrl OOR Low PCC3300,
40455 14 Gas Bitmap 2861 Warning PCC3300V2
25
Fault Status Gen Alternator 1st Start PCC3300,
40455 15 Gas Bitmap 2862 Cond Exists Warning PCC3300V2
25

TABLE 48.

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status EPS Main Channel Lost PCC3300,
40431 0 Gas Bitmap 121 Error Warning PCC3300V2
1
Fault Status Oil Inlet Pressure High Error PCC3300,
40431 1 Gas Bitmap 136 Warning PCC3300V2
1
Fault Status Oil Inlet Pressure Low Error PCC3300,
40431 2 Gas Bitmap 137 Warning PCC3300V2
1
Fault Status Oil Overpressure Error PCC3300,
40431 3 Gas Bitmap 142 Warning PCC3300V2
1
Fault Status Intake Manifold Temp 2 PCC3300,
40431 4 Gas Bitmap 156 OORH Warning PCC3300V2
1
Fault Status Intake Manifold Temp 2 PCC3300,
40431 5 Gas Bitmap 157 OORL Warning PCC3300V2
1
Fault Status Intake Manifold Temp 2 PCC3300,
40431 6 Gas Bitmap 158 High Shutdown PCC3300V2
1
Fault Status Intake Manifold 3 Temp PCC3300,
40431 7 Gas Bitmap 159 OORH Warning PCC3300V2
1
Fault Status Intake Manifold 3 Temp PCC3300,
40431 8 Gas Bitmap 161 OORL Warning PCC3300V2
1
Fault Status Intake Manifold 3 Temp PCC3300,
40431 9 Gas Bitmap 162 High Shutdown PCC3300V2
1

A029X159 (Issue 31) 889 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Intake Manifold 4 Temp PCC3300,
40431 10 Gas Bitmap 163 OORH Warning PCC3300V2
1
Fault Status Intake Manifold 4 Temp PCC3300,
40431 11 Gas Bitmap 164 OORL Warning PCC3300V2
1
Fault Status Intake Manifold 4 Temp PCC3300,
40431 12 Gas Bitmap 165 High Shutdown PCC3300V2
1
Fault Status Throttle_Driver_Feedback_ PCC3300,
Shutdown
40431 13 Gas Bitmap 175 High_Error PCC3300V2
w/Cooldown
1
Fault Status Throttle_Driver_Feedback_ PCC3300,
Shutdown
40431 14 Gas Bitmap 176 Low_Error PCC3300V2
w/Cooldown
1
Fault Status Throttle_Actuator_Error PCC3300,
Shutdown
40431 15 Gas Bitmap 177 PCC3300V2
w/Cooldown
1
Fault Status Low Fuel Pressure PCC3300,
40432 0 Gas Bitmap 2118 Warning PCC2300,
2 PCC3300V2
Fault Status Fuel System on Secondary PCC3300,
40432 1 Gas Bitmap 5365 Source - Condition Exists Warning PCC2300,
2 PCC3300V2
Fault Status Red Stop Lamp Driver PCC3300,
40432 2 Gas Bitmap 244 OORL Warning PCC3300V2
2
Fault Status Exhaust Gas Temp Sensor PCC3300,
40432 3 Gas Bitmap 246 1 OORH Warning PCC3300V2
2
Fault Status Exhaust Gas Temp Sensor PCC3300,
40432 4 Gas Bitmap 247 1 OORL Warning PCC3300V2
2
Fault Status Exhaust Gas Temp Sensor PCC3300,
40432 5 Gas Bitmap 248 1 High Warning PCC3300V2
2
Fault Status Oil Level Low Error PCC3300,
Shutdown
40432 6 Gas Bitmap 253 PCC3300V2
w/Cooldown
2
Fault Status Fuel Control Valve Out of PCC3300,
40432 8 Gas Bitmap 277 Adj Warning PCC3300V2
2
Fault Status Powerdown Data Lost Error PCC3300,
40432 9 Gas Bitmap 346 Warning PCC3300V2
2

Copyright © 2023 Cummins Inc. 890 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Manifold_Absolute_Pressur PCC3300,
40432 10 Gas Bitmap 354 e_1_High_Error Warning PCC3300V2
2
Fault Status Manifold_Absolute_Pressur PCC3300,
40432 11 Gas Bitmap 355 e_1_Low_Error Warning PCC3300V2
2
Fault Status J1708 Link Cannot Transmit PCC3300,
40432 12 Gas Bitmap 412 Error NONE PCC3300V2
2
Fault Status J1708 Link Not Fast PCC3300,
40432 13 Gas Bitmap 414 Enough Error NONE PCC3300V2
2
Fault Status Gas_Mass_Flow_High_Erro PCC3300,
40432 14 Gas Bitmap 453 r Warning PCC3300V2
2
Fault Status Gas_Mass_Flow_Low_Error PCC3300,
40432 15 Gas Bitmap 454 Warning PCC3300V2
2
Fault Status Spark_Timing_B_Error PCC3300,
Shutdown
40433 0 Gas Bitmap 458 PCC3300V2
w/Cooldown
3
Fault Status Spark_Timing_A_Error PCC3300,
Shutdown
40433 1 Gas Bitmap 459 PCC3300V2
w/Cooldown
3
Fault Status Spark_Reference_B_Error PCC3300,
Shutdown
40433 2 Gas Bitmap 461 PCC3300V2
w/Cooldown
3
Fault Status Spark_Reference_A_Error PCC3300,
Shutdown
40433 3 Gas Bitmap 462 PCC3300V2
w/Cooldown
3
Fault Status Isolated Battery Voltage PCC3300,
40433 4 Gas Bitmap 477 Low Error Warning PCC3300V2
3
Fault Status Isolated Battery Voltage PCC3300,
40433 5 Gas Bitmap 478 High Error Warning PCC3300V2
3
Fault Status Throttle Pos 1 Feedback PCC3300,
40433 6 Gas Bitmap 512 OOR High Warning PCC3300V2
3
Fault Status Throttle Pos 1 Feedback PCC3300,
40433 7 Gas Bitmap 513 OOR Low Warning PCC3300V2
3
Fault Status Fuel Control Valve 2 OORH PCC3300,
Shutdown
40433 8 Gas Bitmap 557 PCC3300V2
w/Cooldown
3

A029X159 (Issue 31) 891 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Fuel Control Valve 2 OORL PCC3300,
40433 9 Gas Bitmap 558 Warning PCC3300V2
3
Fault Status Heavy_Knock_Error_1_(A1) PCC3300,
Shutdown
40433 10 Gas Bitmap 561 PCC3300V2
w/Cooldown
3
Fault Status Heavy_Knock_Error_2_(B1) PCC3300,
Shutdown
40433 11 Gas Bitmap 562 PCC3300V2
w/Cooldown
3
Fault Status Heavy_Knock_Error_3_(A2) PCC3300,
Shutdown
40433 12 Gas Bitmap 563 PCC3300V2
w/Cooldown
3
Fault Status Heavy_Knock_Error_4_(B2) PCC3300,
Shutdown
40433 13 Gas Bitmap 564 PCC3300V2
w/Cooldown
3
Fault Status Heavy_Knock_Error_5_(A3) PCC3300,
Shutdown
40433 14 Gas Bitmap 565 PCC3300V2
w/Cooldown
3
Fault Status Heavy_Knock_Error_6_(B3) PCC3300,
Shutdown
40433 15 Gas Bitmap 566 PCC3300V2
w/Cooldown
3
Fault Status Heavy_Knock_Error_7_(A4) PCC3300,
Shutdown
40434 0 Gas Bitmap 567 PCC3300V2
w/Cooldown
4
Fault Status Heavy_Knock_Error_8_(B4) PCC3300,
Shutdown
40434 1 Gas Bitmap 568 PCC3300V2
w/Cooldown
4
Fault Status Heavy_Knock_Error_9_(A5) PCC3300,
Shutdown
40434 2 Gas Bitmap 569 PCC3300V2
w/Cooldown
4
Fault Status Knock Cyl 1 (A1) OORL PCC3300,
40434 3 Gas Bitmap 571 Warning PCC3300V2
4
Fault Status Knock Cyl 2 (B1) OORL PCC3300,
40434 4 Gas Bitmap 572 Warning PCC3300V2
4
Fault Status Knock Cyl 3 (A2) OORL PCC3300,
40434 5 Gas Bitmap 573 Warning PCC3300V2
4
Fault Status Knock Cyl 4 (B2) OORL PCC3300,
40434 6 Gas Bitmap 574 Warning PCC3300V2
4
Fault Status Knock Cyl 5 (A3) OORL PCC3300,
40434 7 Gas Bitmap 575 Warning PCC3300V2
4

Copyright © 2023 Cummins Inc. 892 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Knock Cyl 6 (B3) OORL PCC3300,
40434 8 Gas Bitmap 576 Warning PCC3300V2
4
Fault Status Knock Cyl 7 (A4) OORL PCC3300,
40434 9 Gas Bitmap 577 Warning PCC3300V2
4
Fault Status Knock Cyl 8 (B4) OORL PCC3300,
40434 10 Gas Bitmap 578 Warning PCC3300V2
4
Fault Status Knock Cyl 9 (A5) OORL PCC3300,
40434 11 Gas Bitmap 579 Warning PCC3300V2
4
Fault Status High Side DRV3 High PCC3300,
40434 12 Gas Bitmap 584 Control Error Warning PCC3300V2
4
Fault Status High Side DRV3 Low PCC3300,
40434 13 Gas Bitmap 585 Control Error Warning PCC3300V2
4
Fault Status Exhaust_Backpressure_Hig PCC3300,
40434 14 Gas Bitmap 591 h_Error Warning PCC3300V2
4
Fault Status Exhaust_Backpressure_Lo PCC3300,
40434 15 Gas Bitmap 592 w_Error Warning PCC3300V2
4
Fault Status Turbo 1 Overspeed PCC3300,
40435 0 Gas Bitmap 595 Warning Error Warning PCC3300V2
5
Fault Status Turbo 1 Inlet Pressure High PCC3300,
40435 1 Gas Bitmap 618 Warning PCC3300V2
5
Fault Status Turbo 2 Inlet Press High PCC3300,
40435 2 Gas Bitmap 619 Warning PCC3300V2
5
Fault Status Exhaust Temp 1 (A1) High PCC3300,
Shutdown
40435 3 Gas Bitmap 641 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 3 (A2) High PCC3300,
Shutdown
40435 4 Gas Bitmap 642 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 5 (A3) High PCC3300,
Shutdown
40435 5 Gas Bitmap 643 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 7 (A4) High PCC3300,
Shutdown
40435 6 Gas Bitmap 644 Serious Error PCC3300V2
w/Cooldown
5

A029X159 (Issue 31) 893 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust Temp 9 (A5) High PCC3300,
Shutdown
40435 7 Gas Bitmap 645 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 11 (A6) High PCC3300,
Shutdown
40435 8 Gas Bitmap 646 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 13 (A7) High PCC3300,
Shutdown
40435 9 Gas Bitmap 647 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 15 (A8) High PCC3300,
Shutdown
40435 10 Gas Bitmap 648 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 17 (A9) High PCC3300,
Shutdown
40435 11 Gas Bitmap 651 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 2 (B1) High PCC3300,
Shutdown
40435 12 Gas Bitmap 652 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 4 (B2) High PCC3300,
Shutdown
40435 13 Gas Bitmap 653 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 6 (B3) High PCC3300,
Shutdown
40435 14 Gas Bitmap 654 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 8 (B4) High PCC3300,
Shutdown
40435 15 Gas Bitmap 655 Serious Error PCC3300V2
w/Cooldown
5
Fault Status Exhaust Temp 10 (B5) High PCC3300,
Shutdown
40436 0 Gas Bitmap 656 Serious Error PCC3300V2
w/Cooldown
6
Fault Status Exhaust Temp 12 (B6) High PCC3300,
Shutdown
40436 1 Gas Bitmap 657 Serious Error PCC3300V2
w/Cooldown
6
Fault Status Exhaust Temp 14 (B7) High PCC3300,
Shutdown
40436 2 Gas Bitmap 658 Serious Error PCC3300V2
w/Cooldown
6
Fault Status Exhaust Gas Temp Cyl 1 PCC3300,
40436 3 Gas Bitmap 671 (A1) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 3 PCC3300,
40436 4 Gas Bitmap 672 (A2) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 5 PCC3300,
40436 5 Gas Bitmap 673 (A3) OORL Warning PCC3300V2
6

Copyright © 2023 Cummins Inc. 894 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust Gas Temp Cyl 7 PCC3300,
40436 6 Gas Bitmap 674 (A4) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 9 PCC3300,
40436 7 Gas Bitmap 675 (A5) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 11 PCC3300,
40436 8 Gas Bitmap 676 (A6) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 13 PCC3300,
40436 9 Gas Bitmap 677 (A7) OORL Warning PCC3300V2
6
Fault Status Exhaust Gas Temp Cyl 15 PCC3300,
40436 10 Gas Bitmap 678 (A8) OORL Warning PCC3300V2
6
Fault Status Turbo 2 Speed Moderate PCC3300,
40436 11 Gas Bitmap 683 High Warning PCC3300V2
6
Fault Status Turbo 2 Speed Moderate PCC3300,
40436 12 Gas Bitmap 684 Low Warning PCC3300V2
6
Fault Status Turbo 2 Speed Incorrect PCC3300,
40436 13 Gas Bitmap 685 Warning PCC3300V2
6
Fault Status Turbo 1 Speed Low PCC3300,
40436 15 Gas Bitmap 687 Warning PCC3300V2
6
Fault Status Exhaust Gas Temp 2 (B1) PCC3300,
40437 2 Gas Bitmap 721 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 4 (B2) PCC3300,
40437 3 Gas Bitmap 722 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 6 (B3) PCC3300,
40437 4 Gas Bitmap 723 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 8 (B4) PCC3300,
40437 5 Gas Bitmap 724 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 10 (B5) PCC3300,
40437 6 Gas Bitmap 725 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 12 (B6) PCC3300,
40437 7 Gas Bitmap 726 OORL Warning PCC3300V2
7

A029X159 (Issue 31) 895 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust Gas Temp 14 (B7) PCC3300,
40437 8 Gas Bitmap 727 OORL Warning PCC3300V2
7
Fault Status Exhaust Gas Temp 16 (B8) PCC3300,
40437 9 Gas Bitmap 728 OORL Warning PCC3300V2
7
Fault Status Starter Air Pressure OORL PCC3300,
40437 10 Gas Bitmap 736 Warning PCC3300V2
7
Fault Status Starter Air Pressure OORH PCC3300,
40437 11 Gas Bitmap 737 Warning PCC3300V2
7
Fault Status Starter Air Press PCC3300,
40437 12 Gas Bitmap 738 Underpressure Error Warning PCC3300V2
7
Fault Status Air Filter Restriction PCC3300,
40437 13 Gas Bitmap 741 Pressure High Error Warning PCC3300V2
7
Fault Status Air Filter Restriction PCC3300,
40437 14 Gas Bitmap 742 Pressure Low Error Warning PCC3300V2
7
Fault Status Gas_Mass_Flow_In_Range PCC3300,
40437 15 Gas Bitmap 751 _Error Warning PCC3300V2
7
Fault Status Exhaust_Gas_Oxygen_In_ PCC3300,
40438 0 Gas Bitmap 752 Range_Error Warning PCC3300V2
8
Fault Status Intake Manifold 1 Temp PCC3300,
Shutdown
40438 1 Gas Bitmap 783 Abnormal PCC3300V2
w/Cooldown
8
Fault Status COP_Overboost_Error PCC3300,
Shutdown
40438 2 Gas Bitmap 1213 PCC3300V2
w/Cooldown
8
Fault Status Heavy_Knock_Error_10_(B PCC3300,
Shutdown
40438 3 Gas Bitmap 1274 5) PCC3300V2
w/Cooldown
8
Fault Status Heavy_Knock_Error_12_(B PCC3300,
Shutdown
40438 4 Gas Bitmap 1281 6) PCC3300V2
w/Cooldown
8
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40438 5 Gas Bitmap 1285 rror_13_(A7) PCC3300V2
w/Cooldown
8
Fault Status Heavy_Knock_Error_13_(A PCC3300,
Shutdown
40438 6 Gas Bitmap 1286 7) PCC3300V2
w/Cooldown
8

Copyright © 2023 Cummins Inc. 896 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Heavy_Knock_Error_14_(B PCC3300,
Shutdown
40438 7 Gas Bitmap 1291 7) PCC3300V2
w/Cooldown
8
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40438 8 Gas Bitmap 1295 rror_15_(A8) PCC3300V2
w/Cooldown
8
Fault Status Heavy_Knock_Error_15_(A PCC3300,
Shutdown
40438 9 Gas Bitmap 1296 8) PCC3300V2
w/Cooldown
8
Fault Status Heavy_Knock_Error_18_(B PCC3300,
Shutdown
40438 10 Gas Bitmap 1311 9) PCC3300V2
w/Cooldown
8
Fault Status Oil Filter Restriction Error PCC3300,
40438 11 Gas Bitmap 1362 Warning PCC3300V2
8
Fault Status Fail To Synchronize PCC3300,
40438 13 Gas Bitmap 1457 Warning PCC3300V2
8
Fault Status Sync Phase Rotation PCC3300,
40438 14 Gas Bitmap 1458 Mismatch Warning PCC3300V2
8
Fault Status ECM Software mismatch PCC3300,
Shutdown
40438 15 Gas Bitmap 1474 PCC3300V2
w/Cooldown
8
Fault Status Exhaust Gas Temp 3 (A2) PCC3300,
40439 0 Gas Bitmap 1521 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 5 (A3) PCC3300,
40439 1 Gas Bitmap 1522 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 7 (A4) PCC3300,
40439 2 Gas Bitmap 1523 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 9 (A5) PCC3300,
40439 3 Gas Bitmap 1524 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 11 (A6) PCC3300,
40439 4 Gas Bitmap 1525 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 13 (A7) PCC3300,
40439 5 Gas Bitmap 1526 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 15 (A8) PCC3300,
40439 6 Gas Bitmap 1527 OORH Warning PCC3300V2
9

A029X159 (Issue 31) 897 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust Gas Temp 17 (A9) PCC3300,
40439 7 Gas Bitmap 1528 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 2 (B1) PCC3300,
40439 8 Gas Bitmap 1529 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 6 (B3) PCC3300,
40439 9 Gas Bitmap 1531 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 8 (B4) PCC3300,
40439 10 Gas Bitmap 1532 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 10 (B5) PCC3300,
40439 11 Gas Bitmap 1533 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 12 (B6) PCC3300,
40439 12 Gas Bitmap 1534 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 14 (B7) PCC3300,
40439 13 Gas Bitmap 1535 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 16 (B8) PCC3300,
40439 14 Gas Bitmap 1536 OORH Warning PCC3300V2
9
Fault Status Exhaust Gas Temp 18 (B9) PCC3300,
40439 15 Gas Bitmap 1537 OORH Warning PCC3300V2
9
Fault Status EPS Backup Channel Lost PCC3300,
40440 0 Gas Bitmap 1545 Warning PCC3300V2
10
Fault Status EPS Main Channel Lost PCC3300,
40440 1 Gas Bitmap 1546 Warning PCC3300V2
10
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40440 2 Gas Bitmap 1579 rror_12_(B6) PCC3300V2
w/Cooldown
10
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40440 3 Gas Bitmap 1581 rror_14_(B7) PCC3300V2
w/Cooldown
10
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40440 4 Gas Bitmap 1582 rror_16_(B8) PCC3300V2
w/Cooldown
10
Fault Status Heavy_Knock_Error_16_(B PCC3300,
Shutdown
40440 5 Gas Bitmap 1583 8) PCC3300V2
w/Cooldown
10

Copyright © 2023 Cummins Inc. 898 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40440 6 Gas Bitmap 1587 rror_17_(A9) PCC3300V2
w/Cooldown
10
Fault Status Heavy_Knock_Error_17_(A PCC3300,
Shutdown
40440 7 Gas Bitmap 1588 9) PCC3300V2
w/Cooldown
10
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40440 8 Gas Bitmap 1593 rror_18_(B9) PCC3300V2
w/Cooldown
10
Fault Status Exhaust Gas Temp, Cyl 1 PCC3300,
40440 9 Gas Bitmap 1618 (A1) OORH Warning PCC3300V2
10
Fault Status Exhaust Gas Temp, Cyl 4 PCC3300,
40440 10 Gas Bitmap 1619 (B2) OORH Warning PCC3300V2
10
Fault Status Intake Manif Press 2 OORH PCC3300,
40440 11 Gas Bitmap 1636 Warning PCC3300V2
10
Fault Status Intake Manif Press 2 OORL PCC3300,
40440 12 Gas Bitmap 1637 Warning PCC3300V2
10
Fault Status CAN_Throttle_Internal_Fail PCC3300,
Shutdown
40440 13 Gas Bitmap 1737 ure_Error PCC3300V2
w/Cooldown
10
Fault Status CAN_Throttle_Internal_Faul PCC3300,
40440 14 Gas Bitmap 1738 t_Error Warning PCC3300V2
10
Fault Status Engine Throttle Control PCC3300,
40440 15 Gas Bitmap 1739 Condition Exists Warning PCC3300V2
10
Fault Status CAN_Throttle_High_Temp_ PCC3300,
40441 0 Gas Bitmap 1741 Warning_Error Warning PCC3300V2
11
Fault Status CAN_Throttle_Temp_Limitin PCC3300,
40441 1 Gas Bitmap 1742 g_Error Warning PCC3300V2
11
Fault Status Throttle Ctrl 2 OOR High PCC3300,
Shutdown
40441 2 Gas Bitmap 1743 PCC3300V2
w/Cooldown
11
Fault Status Throttle Ctrl 2 OOR Low PCC3300,
Shutdown
40441 3 Gas Bitmap 1744 PCC3300V2
w/Cooldown
11
Fault Status Throttle Ctrl 2 Incorrect PCC3300,
Shutdown
40441 4 Gas Bitmap 1745 PCC3300V2
w/Cooldown
11

A029X159 (Issue 31) 899 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Throttle Ctrl 2 Out of PCC3300,
Shutdown
40441 5 Gas Bitmap 1746 Adjustment PCC3300V2
w/Cooldown
11
Fault Status Throttle Ctrl 2 Bad Device PCC3300,
Shutdown
40441 6 Gas Bitmap 1747 PCC3300V2
w/Cooldown
11
Fault Status Throttle Ctrl 2 Root PCC3300,
40441 7 Gas Bitmap 1748 Unknown Warning PCC3300V2
11
Fault Status Throttle Ctrl 2 Condition PCC3300,
40441 8 Gas Bitmap 1749 Exists Warning PCC3300V2
11
Fault Status Throttle Ctrl 2 Warning High PCC3300,
40441 9 Gas Bitmap 1751 Warning PCC3300V2
11
Fault Status Throttle Ctrl 2 Moderate PCC3300,
40441 10 Gas Bitmap 1752 High Warning PCC3300V2
11
Fault Status Fuel Shutoff 2 OOR High PCC3300,
40441 11 Gas Bitmap 1753 Warning PCC3300V2
11
Fault Status Fuel Tmp 2 OOR High PCC3300,
40441 12 Gas Bitmap 1754 Warning PCC3300V2
11
Fault Status Fuel Tmp 2 OOR Low PCC3300,
40441 13 Gas Bitmap 1755 Warning PCC3300V2
11
Fault Status Gas Flow 2 OOR High PCC3300,
40441 14 Gas Bitmap 1756 Warning PCC3300V2
11
Fault Status Gas Flow 2 OOR Low PCC3300,
40441 15 Gas Bitmap 1757 Warning PCC3300V2
11
Fault Status Gas Flow 2 Incorrect Data PCC3300,
40442 0 Gas Bitmap 1758 Warning PCC3300V2
12
Fault Status FCV 2 Pos Feedback PCC3300,
Shutdown
40442 1 Gas Bitmap 1759 Incorrect PCC3300V2
w/Cooldown
12
Fault Status FCV_Actuator_Error_1761 PCC3300,
Shutdown
40442 2 Gas Bitmap 1761 PCC3300V2
w/Cooldown
12
Fault Status Int Man 2 Tmp Moderate PCC3300,
40442 3 Gas Bitmap 1984 High Warning PCC3300V2
12

Copyright © 2023 Cummins Inc. 900 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status FCV 2 In Pr OOR High PCC3300,
40442 4 Gas Bitmap 1765 Warning PCC3300V2
12
Fault Status FCV 2 In Pr OOR Low PCC3300,
40442 5 Gas Bitmap 1766 Warning PCC3300V2
12
Fault Status FCV 2 Out Pr OOR High PCC3300,
40442 6 Gas Bitmap 1767 Warning PCC3300V2
12
Fault Status FCV 2 Out Pr OOR Low PCC3300,
40442 7 Gas Bitmap 1768 Warning PCC3300V2
12
Fault Status E_Shutd Indication OORH PCC3300,
40442 8 Gas Bitmap 1769 Warning PCC3300V2
12
Fault Status E_Shutd Indication OORL PCC3300,
40442 9 Gas Bitmap 1771 Warning PCC3300V2
12
Fault Status Eng Derate Request OORH PCC3300,
40442 10 Gas Bitmap 1772 Warning PCC3300V2
12
Fault Status Eng Derate Request OORL PCC3300,
40442 11 Gas Bitmap 1773 Warning PCC3300V2
12
Fault Status Oil Priming Pump OORH PCC3300,
40442 12 Gas Bitmap 1774 Warning PCC3300V2
12
Fault Status Oil Priming Pump OORL PCC3300,
40442 13 Gas Bitmap 1775 Warning PCC3300V2
12
Fault Status Power Conservation Control PCC3300,
40442 14 Gas Bitmap 3362 OORH Warning PCC3300V2
12
Fault Status Power Conservation Control PCC3300,
40442 15 Gas Bitmap 3363 OORL Warning PCC3300V2
12
Fault Status Engine_Heater_Control_Dri PCC3300,
40443 0 Gas Bitmap 1778 ver_High_Error Warning PCC3300V2
13
Fault Status Engine_Heater_Control_Dri PCC3300,
40443 1 Gas Bitmap 1779 ver_Low_Error Warning PCC3300V2
13
Fault Status Shutd Request OOR High PCC3300,
40443 2 Gas Bitmap 1781 Warning PCC3300V2
13

A029X159 (Issue 31) 901 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Shutd Request OOR Low PCC3300,
40443 3 Gas Bitmap 1782 Warning PCC3300V2
13
Fault Status Coolant_Pump_Control_Dri PCC3300,
40443 4 Gas Bitmap 1783 ver_High_Error Warning PCC3300V2
13
Fault Status Coolant_Pump_Control_Dri PCC3300,
40443 5 Gas Bitmap 1784 ver_Low_Error Warning PCC3300V2
13
Fault Status Oil_Priming_Pump_Manual PCC3300,
40443 6 Gas Bitmap 1785 _Override_Input_On Warning PCC3300V2
13
Fault Status Oil_Priming_Pump_Stuck_ PCC3300,
40443 7 Gas Bitmap 1786 On_Error Warning PCC3300V2
13
Fault Status Post_Lube_Oil_Priming_Err PCC3300,
40443 8 Gas Bitmap 1787 or Warning PCC3300V2
13
Fault Status Maintenance_Lube_Oil_Pri PCC3300,
40443 9 Gas Bitmap 1788 ming_Error Warning PCC3300V2
13
Fault Status Pre_Start_Lube_Oil_Primin PCC3300,
Shutdown
40443 10 Gas Bitmap 1789 g_Error PCC3300V2
w/Cooldown
13
Fault Status Failure_To_Meet_Load_Sp PCC3300,
Shutdown
40443 11 Gas Bitmap 1791 eed_Error PCC3300V2
w/Cooldown
13
Fault Status Idle when CB Closed PCC3300,
40443 12 Gas Bitmap 1792 Warning PCC3300V2
13
Fault Status Speed/Posit sensor out of PCC3300,
40443 13 Gas Bitmap 1793 Adj Warning PCC3300V2
13
Fault Status Fire Detected PCC3300,
40443 14 Gas Bitmap 1794 Shutdown PCC3300V2
13
Fault Status Compressor_Bypass_Positi PCC3300,
40443 15 Gas Bitmap 1795 on_High_Error Warning PCC3300V2
13
Fault Status Compressor_Bypass_Positi PCC3300,
40444 0 Gas Bitmap 1796 on_Low_Error Warning PCC3300V2
14
Fault Status Compressor Bypass ctrl PCC3300,
40444 1 Gas Bitmap 1797 OORH Warning PCC3300V2
14

Copyright © 2023 Cummins Inc. 902 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Compressor Bypass ctrl PCC3300,
40444 2 Gas Bitmap 1798 OORL Warning PCC3300V2
14
Fault Status CB_Position_Err_Status PCC3300,
40444 3 Gas Bitmap 1799 Warning PCC3300V2
14
Fault Status HIGH_SIDE_DRV2_High_C PCC3300,
40444 4 Gas Bitmap 1811 ontrol_Error (VPS) Warning PCC3300V2
14
Fault Status HIGH_SIDE_DRV2_Low_C PCC3300,
40444 5 Gas Bitmap 1812 ontrol_Error (VPS) Warning PCC3300V2
14
Fault Status Valve_Proving_System_Tes PCC3300,
40444 6 Gas Bitmap 1813 t_Failed_Warning_Error Warning PCC3300V2
14
Fault Status Valve_Proving_System_Tes PCC3300,
Shutdown
40444 7 Gas Bitmap 1814 t_Failed_Shutdown_Error PCC3300V2
w/Cooldown
14
Fault Status RLY14_High_Control_Error PCC3300,
40444 8 Gas Bitmap 1815 Warning PCC3300V2
14
Fault Status Oil PreHtr Ctrl OOR Low PCC3300,
40444 9 Gas Bitmap 1816 Warning PCC3300V2
14
Fault Status Oil_Pre- PCC3300,
40444 10 Gas Bitmap 1817 Heater_Tripped_Error Warning PCC3300V2
14
Fault Status Oil_Pre- PCC3300,
40444 11 Gas Bitmap 1818 Heater_Not_Warming_Error Warning PCC3300V2
14
Fault Status Common AC Aux CB PCC3300,
40444 12 Gas Bitmap 1819 tripped Warning PCC3300V2
14
Fault Status Min_FSO_Speed_Error PCC3300,
Shutdown
40444 13 Gas Bitmap 1821 PCC3300V2
w/Cooldown
14
Fault Status LT Coolant Level Low PCC3300,
Shutdown
40444 14 Gas Bitmap 1822 Shutdown Error PCC3300V2
w/Cooldown
14
Fault Status LT Coolant Level Low PCC3300,
40444 15 Gas Bitmap 1823 Warning Error Warning PCC3300V2
14
Fault Status Idle_Rated_Trans_Oil_Tem PCC3300,
40445 0 Gas Bitmap 1824 p_Low_Error Warning PCC3300V2
15

A029X159 (Issue 31) 903 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Dirty_Oil_Level_Error PCC3300,
40445 1 Gas Bitmap 1825 Warning PCC3300V2
15
Fault Status ECM Software incompatible PCC3300,
Shutdown
40445 2 Gas Bitmap 1826 PCC3300V2
w/Cooldown
15
Fault Status Fuel_Inlet_Pressure_High_ PCC3300,
40445 3 Gas Bitmap 1827 Error Warning PCC3300V2
15
Fault Status Fuel_Inlet_Pressure_Low_E PCC3300,
40445 4 Gas Bitmap 1828 rror Warning PCC3300V2
15
Fault Status Vent_Gas_Valve_Error PCC3300,
Shutdown
40445 5 Gas Bitmap 1829 PCC3300V2
w/Cooldown
15
Fault Status Upstream_FSO_Valve_Erro PCC3300,
Shutdown
40445 6 Gas Bitmap 1831 r PCC3300V2
w/Cooldown
15
Fault Status Downstream_FSO_Valve_E PCC3300,
Shutdown
40445 7 Gas Bitmap 1832 rror PCC3300V2
w/Cooldown
15
Fault Status Engine_Heater_Trip_Error PCC3300,
40445 8 Gas Bitmap 1833 Warning PCC3300V2
15
Fault Status Coolant_Pump_Trip_Error PCC3300,
40445 9 Gas Bitmap 1834 Warning PCC3300V2
15
Fault Status Oil_Priming_Pump_Tripped PCC3300,
40445 10 Gas Bitmap 1835 _Error Warning PCC3300V2
15
Fault Status LCP_(LT)_Low_Serious_Err PCC3300,
Shutdown
40445 11 Gas Bitmap 1836 or PCC3300V2
w/Cooldown
15
Fault Status Permanent_FS_Cam_Sync PCC3300,
Shutdown
40445 12 Gas Bitmap 1837 _Lost_Error PCC3300V2
w/Cooldown
15
Fault Status Partial_Engine_Overload_S PCC3300,
Shutdown
40445 13 Gas Bitmap 1838 hutdown_Error PCC3300V2
w/Cooldown
15
Fault Status Fuel_Supply_Pressure_Hig PCC3300,
40445 14 Gas Bitmap 1839 h_Error Warning PCC3300V2
15
Fault Status Fuel_Supply_Pressure_Low PCC3300,
40445 15 Gas Bitmap 1841 _Error Warning PCC3300V2
15

Copyright © 2023 Cummins Inc. 904 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Radiator_Fan_Trip_Error PCC3300,
40446 0 Gas Bitmap 1842 Warning PCC3300V2
16
Fault Status Exhaust Aft Inlet O2 OOR PCC3300,
40446 1 Gas Bitmap 1858 High Warning PCC3300V2
16
Fault Status Exhaust Aft Inlet O2 OOR PCC3300,
40446 2 Gas Bitmap 1859 Low Warning PCC3300V2
16
Fault Status Exhaust Aft Inlet O2 PCC3300,
40446 3 Gas Bitmap 1861 Incorrect Warning PCC3300V2
16
Fault Status Exhaust Aft Out O2 OOR PCC3300,
40446 4 Gas Bitmap 1862 High Warning PCC3300V2
16
Fault Status Exhaust Aft Outlet O2 OOR PCC3300,
40446 5 Gas Bitmap 1863 Low Warning PCC3300V2
16
Fault Status Exhaust Aft Outlet O2 PCC3300,
40446 6 Gas Bitmap 1864 Incorrect Warning PCC3300V2
16
Fault Status Int Man 3 Tmp Moderate PCC3300,
40446 7 Gas Bitmap 1985 High Warning PCC3300V2
16
Fault Status Int Man 4 Tmp Moderate PCC3300,
40446 8 Gas Bitmap 1986 High Warning PCC3300V2
16
Fault Status Coolant_Inlet_Temperature PCC3300,
40446 9 Gas Bitmap 2111 _(LT)_High_Error Warning PCC3300V2
16
Fault Status Coolant_Inlet_Temperature PCC3300,
40446 10 Gas Bitmap 2112 _(LT)_Low_Error Warning PCC3300V2
16
Fault Status CIT_(LT)_High_Warning_Er PCC3300,
40446 11 Gas Bitmap 2113 ror Warning PCC3300V2
16
Fault Status CIT_(LT)_High_Serious_Err PCC3300,
40446 12 Gas Bitmap 2114 or Shutdown PCC3300V2
16
Fault Status LT_Coolant_Pressure_High PCC3300,
40446 13 Gas Bitmap 2115 _Error Warning PCC3300V2
16
Fault Status LT_Coolant_Pressure_Low PCC3300,
40446 14 Gas Bitmap 2116 _Error Warning PCC3300V2
16

A029X159 (Issue 31) 905 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status LCP_(LT)_Low_Warning_Er PCC3300,
40446 15 Gas Bitmap 2117 ror Warning PCC3300V2
16
Fault Status Exhaust_Temp_1_(A1)_Hig PCC3300,
40447 0 Gas Bitmap 2121 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_3_(A2)_Hig PCC3300,
40447 1 Gas Bitmap 2122 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_5_(A3)_Hig PCC3300,
40447 2 Gas Bitmap 2123 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_7_(A4)_Hig PCC3300,
40447 3 Gas Bitmap 2124 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_9_(A5)_Hig PCC3300,
40447 4 Gas Bitmap 2125 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_11_(A6)_Hi PCC3300,
40447 5 Gas Bitmap 2126 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_13_(A7)_Hi PCC3300,
40447 6 Gas Bitmap 2127 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_15_(A8)_Hi PCC3300,
40447 7 Gas Bitmap 2128 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_17_(A9)_Hi PCC3300,
40447 8 Gas Bitmap 2129 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_2_(B1)_Hig PCC3300,
40447 9 Gas Bitmap 2131 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_4_(B2)_Hig PCC3300,
40447 10 Gas Bitmap 2132 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_6_(B3)_Hig PCC3300,
40447 11 Gas Bitmap 2133 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_8_(B4)_Hig PCC3300,
40447 12 Gas Bitmap 2134 h_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_10_(B5)_Hi PCC3300,
40447 13 Gas Bitmap 2135 gh_Warning_Error Warning PCC3300V2
17

Copyright © 2023 Cummins Inc. 906 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust_Temp_12_(B6)_Hi PCC3300,
40447 14 Gas Bitmap 2136 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_14_(B7)_Hi PCC3300,
40447 15 Gas Bitmap 2137 gh_Warning_Error Warning PCC3300V2
17
Fault Status Exhaust_Temp_16_(B8)_Hi PCC3300,
40448 0 Gas Bitmap 2138 gh_Warning_Error Warning PCC3300V2
18
Fault Status Exhaust_Temp_18_(B9)_Hi PCC3300,
40448 1 Gas Bitmap 2139 gh_Warning_Error Warning PCC3300V2
18
Fault Status Start_Air_Pressure_High_Er PCC3300,
40448 2 Gas Bitmap 2141 ror Warning PCC3300V2
18
Fault Status Start_Air_Pressure_Low_Er PCC3300,
40448 3 Gas Bitmap 2142 ror Warning PCC3300V2
18
Fault Status SAP_Overpressure_Error PCC3300,
40448 4 Gas Bitmap 2143 Warning PCC3300V2
18
Fault Status Exhaust Temp 16 (B8) High PCC3300,
Shutdown
40448 5 Gas Bitmap 2144 Serious Error PCC3300V2
w/Cooldown
18
Fault Status Exhaust Temp 18 (B9) High PCC3300,
Shutdown
40448 6 Gas Bitmap 2145 Serious Error PCC3300V2
w/Cooldown
18
Fault Status EGT 17 (A9) OOR Low PCC3300,
40448 7 Gas Bitmap 2146 Warning PCC3300V2
18
Fault Status EGT 18 (B9) OOR Low PCC3300,
40448 8 Gas Bitmap 2147 Warning PCC3300V2
18
Fault Status Oil_Filter_Outlet_Pressure_ PCC3300,
40448 9 Gas Bitmap 2154 High_Error Warning PCC3300V2
18
Fault Status Oil_Filter_Outlet_Pressure_ PCC3300,
40448 10 Gas Bitmap 2155 Low_Error Warning PCC3300V2
18
Fault Status Int Man 2 Tmp Abnormal PCC3300,
Shutdown
40448 11 Gas Bitmap 2157 Rate PCC3300V2
w/Cooldown
18
Fault Status Int Man 3 Tmp Abnormal PCC3300,
Shutdown
40448 12 Gas Bitmap 2158 Rate PCC3300V2
w/Cooldown
18

A029X159 (Issue 31) 907 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Int Man 4 Tmp Abnormal PCC3300,
Shutdown
40448 13 Gas Bitmap 2159 Rate PCC3300V2
w/Cooldown
18
Fault Status Exhaust O2 OOR High PCC3300,
40448 14 Gas Bitmap 2188 Warning PCC3300V2
18
Fault Status ST_Throttle_Press_Err_Stat PCC3300,
40448 15 Gas Bitmap 2191 us Warning PCC3300V2
18
Fault Status Exhaust O2 OOR Low PCC3300,
40449 0 Gas Bitmap 2192 Warning PCC3300V2
19
Fault Status RAM_Image_Word_Error PCC3300,
40449 1 Gas Bitmap 2217 Warning PCC3300V2
19
Fault Status Exhaust O2 Moderate High PCC3300,
40449 2 Gas Bitmap 2219 Warning PCC3300V2
19
Fault Status Exhaust O2 Moderate Low PCC3300,
40449 3 Gas Bitmap 2221 Warning PCC3300V2
19
Fault Status Knock 11 (A6) Moderate PCC3300,
Shutdown
40449 4 Gas Bitmap 2281 High PCC3300V2
w/Cooldown
19
Fault Status Knock 11 (A6) Critical High PCC3300,
Shutdown
40449 5 Gas Bitmap 2282 PCC3300V2
w/Cooldown
19
Fault Status Fuel Shutoff 2 OOR Low PCC3300,
40449 6 Gas Bitmap 2298 Warning PCC3300V2
19
Fault Status Red Lamp OOR High PCC3300,
40449 7 Gas Bitmap 2315 Warning PCC3300V2
19
Fault Status Amber Lamp OOR High PCC3300,
40449 8 Gas Bitmap 2316 Warning PCC3300V2
19
Fault Status Amber Lamp OOR Low PCC3300,
40449 9 Gas Bitmap 2317 Warning PCC3300V2
19
Fault Status Fuel_Outlet_Pressure_High PCC3300,
40449 10 Gas Bitmap 2427 _Error Warning PCC3300V2
19
Fault Status Fuel_Outlet_Pressure_Low PCC3300,
40449 11 Gas Bitmap 2428 _Error Warning PCC3300V2
19

Copyright © 2023 Cummins Inc. 908 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Total Real Power Circuit PCC3300,
40449 12 Gas Bitmap 2453 OORH Warning PCC3300V2
19
Fault Status Total Real Power Circuit PCC3300,
40449 13 Gas Bitmap 2454 OORL Warning PCC3300V2
19
Fault Status Speed_Bias_Low_Error PCC3300,
40449 14 Gas Bitmap 2455 Warning PCC3300V2
19
Fault Status Speed_Bias_High_Error PCC3300,
40449 15 Gas Bitmap 2456 Warning PCC3300V2
19
Fault Status Max_Total_Misfire_Error PCC3300,
Shutdown
40450 0 Gas Bitmap 2457 PCC3300V2
w/Cooldown
20
Fault Status Cylinder_2_(B1)_Total_Misfi PCC3300,
40450 1 Gas Bitmap 2458 re_Error Warning PCC3300V2
20
Fault Status Cylinder_4_(B2)_Total_Misfi PCC3300,
40450 2 Gas Bitmap 2459 re_Error Warning PCC3300V2
20
Fault Status Cylinder_6_(B3)_Total_Misfi PCC3300,
40450 3 Gas Bitmap 2461 re_Error Warning PCC3300V2
20
Fault Status Cylinder_8_(B4)_Total_Misfi PCC3300,
40450 4 Gas Bitmap 2462 re_Error Warning PCC3300V2
20
Fault Status Cylinder_10_(B5)_Total_Mi PCC3300,
40450 5 Gas Bitmap 2463 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_12_(B6)_Total_Mi PCC3300,
40450 6 Gas Bitmap 2464 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_14_(B7)_Total_Mi PCC3300,
40450 7 Gas Bitmap 2465 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_16_(B8)_Total_Mi PCC3300,
40450 8 Gas Bitmap 2466 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_18_(B9)_Total_Mi PCC3300,
40450 9 Gas Bitmap 2467 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_1_(A1)_Total_Misfi PCC3300,
40450 10 Gas Bitmap 2469 re_Error Warning PCC3300V2
20

A029X159 (Issue 31) 909 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Cylinder_3_(A2)_Total_Misfi PCC3300,
40450 11 Gas Bitmap 2471 re_Error Warning PCC3300V2
20
Fault Status Cylinder_5_(A3)_Total_Misfi PCC3300,
40450 12 Gas Bitmap 2472 re_Error Warning PCC3300V2
20
Fault Status Cylinder_7_(A4)_Total_Misfi PCC3300,
40450 13 Gas Bitmap 2473 re_Error Warning PCC3300V2
20
Fault Status Cylinder_9_(A5)_Total_Misfi PCC3300,
40450 14 Gas Bitmap 2475 re_Error Warning PCC3300V2
20
Fault Status Cylinder_11_(A6)_Total_Mi PCC3300,
40450 15 Gas Bitmap 2476 sfire_Error Warning PCC3300V2
20
Fault Status Cylinder_13_(A7)_Total_Mi PCC3300,
40451 0 Gas Bitmap 2477 sfire_Error Warning PCC3300V2
21
Fault Status Cylinder_15_(A8)_Total_Mi PCC3300,
40451 1 Gas Bitmap 2478 sfire_Error Warning PCC3300V2
21
Fault Status Cylinder_17_(A9)_Total_Mi PCC3300,
40451 2 Gas Bitmap 2479 sfire_Error Warning PCC3300V2
21
Fault Status Start_Before_Ready_Error PCC3300,
Shutdown
40451 3 Gas Bitmap 2482 PCC3300V2
w/Cooldown
21
Fault Status Continuous_Starter_Failure PCC3300,
Shutdown
40451 4 Gas Bitmap 2483 _Error PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 1 PCC3300,
Shutdown
40451 5 Gas Bitmap 2484 (A1) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 3 PCC3300,
Shutdown
40451 6 Gas Bitmap 2485 (A2) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 5 PCC3300,
Shutdown
40451 7 Gas Bitmap 2486 (A3) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 7 PCC3300,
Shutdown
40451 8 Gas Bitmap 2487 (A4) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 9 PCC3300,
Shutdown
40451 9 Gas Bitmap 2488 (A5) Abnormal Rate PCC3300V2
w/Cooldown
21

Copyright © 2023 Cummins Inc. 910 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust Temperature 11 PCC3300,
Shutdown
40451 10 Gas Bitmap 2489 (A6) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 13 PCC3300,
Shutdown
40451 11 Gas Bitmap 2491 (A7) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 15 PCC3300,
Shutdown
40451 12 Gas Bitmap 2492 (A8) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 17 PCC3300,
Shutdown
40451 13 Gas Bitmap 2493 (A9) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 2 PCC3300,
Shutdown
40451 14 Gas Bitmap 2494 (B1) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 4 PCC3300,
Shutdown
40451 15 Gas Bitmap 2495 (B2) Abnormal Rate PCC3300V2
w/Cooldown
21
Fault Status Exhaust Temperature 6 PCC3300,
Shutdown
40452 0 Gas Bitmap 2496 (B3) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 8 PCC3300,
Shutdown
40452 1 Gas Bitmap 2497 (B4) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 10 PCC3300,
Shutdown
40452 2 Gas Bitmap 2498 (B5) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 12 PCC3300,
Shutdown
40452 3 Gas Bitmap 2499 (B6) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 14 PCC3300,
Shutdown
40452 4 Gas Bitmap 2511 (B7) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 16 PCC3300,
Shutdown
40452 5 Gas Bitmap 2512 (B8) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Exhaust Temperature 18 PCC3300,
Shutdown
40452 6 Gas Bitmap 2513 (B9) Abnormal Rate PCC3300V2
w/Cooldown
22
Fault Status Compressor_Outlet_Pressu PCC3300,
40452 7 Gas Bitmap 2517 re_High_Error Warning PCC3300V2
22
Fault Status Compressor_Outlet_Pressu PCC3300,
40452 8 Gas Bitmap 2518 re_Low_Error Warning PCC3300V2
22

A029X159 (Issue 31) 911 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Bank_Id_Error PCC3300,
Shutdown
40452 9 Gas Bitmap 2521 PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 10 Gas Bitmap 2522 rror_1_(A1) PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 11 Gas Bitmap 2523 rror_2_(B1) PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 12 Gas Bitmap 2524 rror_3_(A2) PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 13 Gas Bitmap 2525 rror_4_(B2) PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 14 Gas Bitmap 2526 rror_5_(A3) PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40452 15 Gas Bitmap 2527 rror_6_(B3) PCC3300V2
w/Cooldown
22
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40453 0 Gas Bitmap 2528 rror_7_(A4) PCC3300V2
w/Cooldown
23
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40453 1 Gas Bitmap 2529 rror_8_(B4) PCC3300V2
w/Cooldown
23
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40453 2 Gas Bitmap 2531 rror_9_(A5) PCC3300V2
w/Cooldown
23
Fault Status Continuous_Light_Knock_E PCC3300,
Shutdown
40453 3 Gas Bitmap 2532 rror_10_(B5) PCC3300V2
w/Cooldown
23
Fault Status ECM_Overtemp_Error PCC3300,
Shutdown
40453 4 Gas Bitmap 2544 PCC3300V2
w/Cooldown
23
Fault Status DG_Air_Compressor_Trip_ PCC3300,
40453 5 Gas Bitmap 2567 Error Warning PCC3300V2
23
Fault Status Throttle Pos 2 Feedback PCC3300,
40453 6 Gas Bitmap 2643 OOR High Warning PCC3300V2
23
Fault Status Throttle Pos 2 Feedback PCC3300,
40453 7 Gas Bitmap 2644 OOR Low Warning PCC3300V2
23

Copyright © 2023 Cummins Inc. 912 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Gas Supply Pr Moderate PCC3300,
40453 9 Gas Bitmap 2724 High Warning PCC3300V2
23
Fault Status Gas Supply Pr Moderate PCC3300,
40453 10 Gas Bitmap 2725 Low Warning PCC3300V2
23
Fault Status Exh Gas Tmp Critical High PCC3300,
Shutdown
40453 11 Gas Bitmap 2737 PCC3300V2
w/Cooldown
23
Fault Status Bank_A_CCD_Failed_Error PCC3300,
Shutdown
40453 12 Gas Bitmap 2766 PCC3300V2
w/Cooldown
23
Fault Status Bank_B_CCD_Failed_Error PCC3300,
Shutdown
40453 13 Gas Bitmap 2767 PCC3300V2
w/Cooldown
23
Fault Status CAN Parent Communication PCC3300,
Shutdown
40453 14 Gas Bitmap 2768 Incorrect PCC3300V2
w/Cooldown
23
Fault Status CAN Child Com Incorrect PCC3300,
Shutdown
40453 15 Gas Bitmap 2769 PCC3300V2
w/Cooldown
23
Fault Status COT_Low_Error PCC3300,
40454 0 Gas Bitmap 2789 Warning PCC3300V2
24
Fault Status COT_Low_Serious_Error PCC3300,
Shutdown
40454 1 Gas Bitmap 2793 PCC3300V2
w/Cooldown
24
Fault Status Ign Shutd Relay OOR High PCC3300,
40454 2 Gas Bitmap 2794 Warning PCC3300V2
24
Fault Status Ign Shutd Relay OOR Low PCC3300,
40454 3 Gas Bitmap 2795 Warning PCC3300V2
24
Fault Status Partial_Engine_Overload_W PCC3300,
40454 4 Gas Bitmap 2796 arning_Error Warning PCC3300V2
24
Fault Status Inlet Gas Diff Pressure PCC3300,
40454 5 Gas Bitmap 2797 OOR High Warning PCC3300V2
24
Fault Status Inlet Gas Diff Pressure PCC3300,
40454 6 Gas Bitmap 2798 OOR Low Warning PCC3300V2
24
Fault Status IMOP_Compressor_Outlet_ PCC3300,
Shutdown
40454 7 Gas Bitmap 2799 Presure_Delta_Error PCC3300V2
w/Cooldown
24

A029X159 (Issue 31) 913 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status IMOP_Compressor_Outlet_ PCC3300,
Shutdown
40454 8 Gas Bitmap 2811 Pressure_Maximum_Error PCC3300V2
w/Cooldown
24
Fault Status Exhaust_Temp_1_(A1)_Dev PCC3300,
40454 9 Gas Bitmap 2837 iation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_3_(A2)_Dev PCC3300,
40454 10 Gas Bitmap 2838 iation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_5_(A3)_Dev PCC3300,
40454 11 Gas Bitmap 2839 iation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_7_(A4)_Dev PCC3300,
40454 12 Gas Bitmap 2841 iation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_9_(A5)_Dev PCC3300,
40454 13 Gas Bitmap 2842 iation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_11_(A6)_D PCC3300,
40454 14 Gas Bitmap 2843 eviation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_13_(A7)_D PCC3300,
40454 15 Gas Bitmap 2844 eviation_Error Warning PCC3300V2
24
Fault Status Exhaust_Temp_15_(A8)_D PCC3300,
40455 0 Gas Bitmap 2845 eviation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_17_(A9)_D PCC3300,
40455 1 Gas Bitmap 2846 eviation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_2_(B1)_Dev PCC3300,
40455 2 Gas Bitmap 2847 iation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_4_(B2)_Dev PCC3300,
40455 3 Gas Bitmap 2848 iation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_6_(B3)_Dev PCC3300,
40455 4 Gas Bitmap 2849 iation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_8_(B4)_Dev PCC3300,
40455 5 Gas Bitmap 2851 iation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_10_(B5)_D PCC3300,
40455 6 Gas Bitmap 2852 eviation_Error Warning PCC3300V2
25

Copyright © 2023 Cummins Inc. 914 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust_Temp_12_(B6)_D PCC3300,
40455 7 Gas Bitmap 2853 eviation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_14_(B7)_D PCC3300,
40455 8 Gas Bitmap 2854 eviation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_16_(B8)_D PCC3300,
40455 9 Gas Bitmap 2855 eviation_Error Warning PCC3300V2
25
Fault Status Exhaust_Temp_18_(B9)_D PCC3300,
40455 10 Gas Bitmap 2856 eviation_Error Warning PCC3300V2
25
Fault Status Turbo_1_Overspeed_Critica PCC3300,
Shutdown
40455 11 Gas Bitmap 2857 l_Error PCC3300V2
w/Cooldown
25
Fault Status Turbo_2_Overspeed_Critica PCC3300,
Shutdown
40455 12 Gas Bitmap 2858 l_Error PCC3300V2
w/Cooldown
25
Fault Status Alt Heater Ctrl OOR High PCC3300,
40455 13 Gas Bitmap 2859 Warning PCC3300V2
25
Fault Status Alt Heater Ctrl OOR Low PCC3300,
40455 14 Gas Bitmap 2861 Warning PCC3300V2
25
Fault Status Gen Alternator 1st Start PCC3300,
40455 15 Gas Bitmap 2862 Cond Exists Warning PCC3300V2
25

TABLE 49.

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Exhaust Gas Temperature PCC3300,
41400 0 479 Warning
Bitmap 31 Data Incorrect PCC3300V2
Fault Status Fuel Filter Press Hi Above PCC3300,
41400 1 2343 NONE
Bitmap 31 Normal PCC3300V2
Fault Status Inj Solenoid Driver 1 Calib PCC3300,
41400 2 2442 Warning
Bitmap 31 Error PCC3300V2
Fault Status Inj Solenoid Driver 2 Calib PCC3300,
41400 3 2443 Warning
Bitmap 31 Error PCC3300V2
Fault Status Inj Solenoid Driver 3 Calib PCC3300,
41400 4 2444 Warning
Bitmap 31 Error PCC3300V2
Fault Status Inj Solenoid Driver 4 Calib PCC3300,
41400 5 2445 Warning
Bitmap 31 Error PCC3300V2

A029X159 (Issue 31) 915 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Inj Solenoid Driver 5 Calib PCC3300,
41400 6 2446 Warning
Bitmap 31 Error PCC3300V2
Fault Status Inj Solenoid Driver 6 Calib PCC3300,
41400 7 2447 Warning
Bitmap 31 Error PCC3300V2
Fault Status J1939 Network 2 Data PCC3300,
41400 8 3329 NONE
Bitmap 31 Incorrect PCC3300V2
Fault Status J1939 Network 3 Data PCC3300,
41400 9 3331 NONE
Bitmap 31 Incorrect PCC3300V2
Fault Status J1939 Network 4 Data PCC3300,
41400 10 4437 NONE
Bitmap 31 Incorrect PCC3300V2
Fault Status AUX101-3 Communication PCC3300,
41400 11 5377 Warning
Bitmap 31 Lost Fault PCC3300V2
Fault Status AUX101-4 Communication PCC3300,
41400 12 5378 Warning
Bitmap 31 Lost Fault PCC3300V2
Fault Status Starter Air Supply Pressure PCC3300,
41400 13 5287 Warning
Bitmap 31 Low PCC3300V2
Fault Status Starter Air Tank Volume PCC3300,
41400 14 5288 Warning
Bitmap 31 Low PCC3300V2
Fault Status Allow Start Override Active PCC3300,
41400 15 5148 Warning
Bitmap 31 Cond Exists PCC3300V2
Fault Status Maintain ECU Power Lamp PCC3300,
41401 0 4952 Warning
Bitmap 33 OOR Low PCC3300V2
Fault Status Turbocharger Actuator S/W PCC3300,
41401 1 4956 Warning
Bitmap 33 Out of Calibration PCC3300V2
Fault Status Variable Geometry PCC3300,
41401 2 Bitmap 33 4957 Turbocharger Actuator Warning PCC3300V2
Software
Fault Status VGT Actuator Driver Circuit PCC3300,
41401 3 5177 Warning
Bitmap 33 Abnormal update rate PCC3300V2
Fault Status Engine Air Filter Differential PCC3300,
41401 4 5576 Warning
Bitmap 33 Press Least Severe PCC3300V2
Fault Status Fuel Filter Differential Press PCC3300,
41401 5 5585 Warning
Bitmap 33 Moderately Severe PCC3300V2
Fault Status Exhaust Gas Recirculation PCC3300,
41401 6 1867 Warning
Bitmap 33 Temperature Error PCC3300V2
Fault Status Engine Torque Limit PCC3300,
41401 7 2998 Warning
Bitmap 33 Feature Special Instructions PCC3300V2
Fault Status Coolant Level Sensor PCC3300,
41401 8 3614 Warning
Bitmap 33 Received N/W Data in Error PCC3300V2
Fault Status COOLANT_LEVEL_MODE PCC3300,
41401 9 Bitmap 33 2448 RATELY_LOW Warning PCC2300,
PCC3300V2

Copyright © 2023 Cummins Inc. 916 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Engine Fan Clutch 2 PCC3300,
41401 10 3633 Warning
Bitmap 33 Control Circuit OOR High PCC3300V2
Fault Status Engine Fan Clutch 2 PCC3300,
41401 11 3634 Warning
Bitmap 33 Control Circuit OOR Low PCC3300V2
Fault Status High Press Common Rail PCC3300,
41401 12 4265 Warning
Bitmap 33 Fuel Press Relief Valve Err PCC3300V2
Fault Status Fan Speed High - Most PCC3300,
41401 13 4789 Warning
Bitmap 33 Severe Level PCC3300V2
Fault Status Engine Air Filter Differential PCC3300,
41401 14 3341 Warning
Bitmap 33 Pressure High PCC3300V2
Fault Status Fan Speed Low - Most PCC3300,
41401 15 4791 Warning
Bitmap 33 Severe Level PCC3300V2
Fault Status NOx limits exceeded - Cond PCC3300,
41402 0 3543 Warning
Bitmap 34 Exists PCC3300V2
Fault Status Engine Wait to Start Lamp - PCC3300,
41402 1 3555 Warning
Bitmap 34 Abnormal PCC3300V2
Fault Status Fan Speed Error Shutdown PCC3300,
41402 2 2412
Bitmap 34 w/Cooldown PCC3300V2
Fault Status Maintain ECU Power Lamp PCC3300,
41402 3 4951 Warning
Bitmap 34 OOR High PCC3300V2
Fault Status HPCR Fuel Pressure Relief PCC3300,
41402 4 4262 Warning
Bitmap 34 Valve OOR High PCC3300V2
Fault Status HPCR Fuel Pressure Relief PCC3300,
41402 5 4263 Warning
Bitmap 34 Valve OOR Low PCC3300V2
Fault Status HPCR Fuel Pressure Relief PCC3300,
41402 7 4867 Warning
Bitmap 34 Valve - Condition Exists PCC3300V2
Fault Status At Least One ACK:Mod PCC3300,
41402 8 Bitmap 34 2662 Severe Fault Warning PCC2300,
PCC3300V2
Fault Status Fuel Pump Intake Pressure PCC3300,
41402 9 581 Warning
Bitmap 34 Sensor OOR Hi PCC3300V2
Fault Status Fuel Pump Intake Pressure PCC3300,
41402 10 582 Warning
Bitmap 34 Sensor OOR Lo PCC3300V2
Fault Status Low Fuel Pump Intake PCC3300,
41402 11 583 Warning
Bitmap 34 Pressure PCC3300V2
Fault Status Low Fuel Pump Intake PCC3300,
41402 12 1379 NONE
Bitmap 34 Pressure - None severity PCC3300V2
Fault Status High Fuel Pump Intake PCC3300,
41402 13 1389 NONE
Bitmap 34 Pressure PCC3300V2
Fault Status Unknown Shutdown at Idle PCC3300,
41402 14 Bitmap 34 5134 Shutdown PCC2300,
PCC3300V2

A029X159 (Issue 31) 917 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Unknown Shutdown at PCC3300,
41402 15 Bitmap 34 5637 Startup Shutdown PCC2300,
PCC3300V2
AT Fault AT1 Outlet NOx Sensor PCC3300,
41403 0 Status 1887 Circuit OOR Low Warning PCC3300V2
Bitmap 2
AT Fault AT1 DOC Intake Temp PCC3300,
41403 1 Status 4534 Sensor Circuit OOR Low Warning PCC3300V2
Bitmap 2
AT Fault AT1 DEF Tank Temp PCC3300,
41403 2 Status 4731 Sensor Out of Calibration Warning PCC3300V2
Bitmap 2
AT Fault Aftertreatment 1 Outlet NOx PCC3300,
41403 3 Status 2771 Sensor Abnormal Warning PCC3300V2
Bitmap 2
AT Fault AT1 DEF Tank Level PCC3300,
41403 4 Status 4732 Sensor Out of Calibration Warning PCC3300V2
Bitmap 2
AT Fault AT1 Diesel Exhaust Fluid PCC3300,
41403 5 Status 2976 Dosing Unit Temp. Error Warning PCC3300V2
Bitmap 2
AT Fault AT1 SCR Intake Temp. PCC3300,
41403 6 Status 3142 Sensor Circuit OOR High Warning PCC3300V2
Bitmap 2
AT Fault AT1 SCR Intake Temp. PCC3300,
41403 7 Status 3143 Sensor Circuit OOR Low Warning PCC3300V2
Bitmap 2
AT Fault AT1 SCR Intake PCC3300,
41403 8 Status 3144 Temperature Sensor Error Warning PCC3300V2
Bitmap 2
AT Fault AT1 SCR Outlet Temp. PCC3300,
41403 9 Status 3146 Sensor Circuit OOR High Warning PCC3300V2
Bitmap 2
AT Fault AT1 SCR Outlet Temp. PCC3300,
41403 10 Status 3147 Sensor Circuit OOR Low Warning PCC3300V2
Bitmap 2
AT Fault AT1 SCR Outlet PCC3300,
41403 11 Status 3148 Temperature Sensor Error Warning PCC3300V2
Bitmap 2
AT Fault AT1 SCR Catalyst System PCC3300,
41403 12 Status 3151 Missing Condition Warning PCC3300V2
Bitmap 2
AT Fault Aftertreatment 1 SCR Outlet PCC3300,
41403 13 Status 3165 Temperature High Shutdown PCC3300V2
Bitmap 2

Copyright © 2023 Cummins Inc. 918 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
AT Fault AT1 Warm Up DOCE Low PCC3300,
41403 14 Status 3173 Warning PCC3300V2
Bitmap 2
AT Fault AT1 DEF Tank Level PCC3300,
41403 15 Status 4769 Sensor Abnormal Rate Warning PCC3300V2
Bitmap 2 Change
AT Fault AT1 SCR Intake Temp. PCC3300,
41404 0 Status 3229 High - Most Severe Level Shutdown PCC3300V2
Bitmap 3
AT Fault AT1 SCR Intake Temp. PCC3300,
Shutdown
41404 1 Status 3231 High - Moderate Severe PCC3300V2
w/Cooldown
Bitmap 3 Level
AT Fault AT1 SCR Outlet PCC3300,
Shutdown
41404 2 Status 3235 Temperature High PCC3300V2
w/Cooldown
Bitmap 3
AT Fault AT1 DEF Line Heater 1 PCC3300,
41404 3 Status 3237 Circuit OOR High Warning PCC3300V2
Bitmap 3
AT Fault AT1 DEF Line Heater 1 PCC3300,
41404 4 Status 3238 Circuit OOR Low Warning PCC3300V2
Bitmap 3
AT Fault AT1 DEF Line Heater 2 PCC3300,
41404 5 Status 3239 Circuit OOR High Warning PCC3300V2
Bitmap 3
AT Fault AT1 DEF Line Heater 2 PCC3300,
41404 6 Status 3241 Circuit OOR Low Warning PCC3300V2
Bitmap 3
AT Fault AT1 DEF Tank Heater PCC3300,
41404 7 Status 3242 Mechanical System Error Warning PCC3300V2
Bitmap 3
AT Fault AT1 DEF Line Heater 1 PCC3300,
41404 8 Status 3258 Open Circuit Warning PCC3300V2
Bitmap 3
AT Fault AT1 DEF Line Heater 2 PCC3300,
41404 9 Status 3261 Open Circuit Warning PCC3300V2
Bitmap 3
AT Fault AT DEF Line Heater 3 PCC3300,
41404 10 Status 3422 Circuit OOR High Warning PCC3300V2
Bitmap 3
AT Fault AT DEF Line Heater 3 PCC3300,
41404 11 Status 3423 Circuit OOR Low Warning PCC3300V2
Bitmap 3
AT Fault AT DEF Line Heater 3 PCC3300,
41404 12 Status 3425 Open Circuit Warning PCC3300V2
Bitmap 3

A029X159 (Issue 31) 919 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
AT Fault Low AT1 Diesel Exhaust PCC3300,
41404 13 Status 3497 Fluid Tank Level Warning PCC3300V2
Bitmap 3
AT Fault AT1 DEF Tank Level Low PCC3300,
41404 14 Status 3498 Warning PCC3300V2
Bitmap 3
AT Fault Aftertreatment 1 Outlet NOx PCC3300,
41404 15 Status 3545 Sensor - Abnormal Warning PCC3300V2
Bitmap 3
AT Fault Aftertreatment Diesel PCC3300,
41405 0 Status 3547 Exhaust Fluid Tank Empty Warning PCC3300V2
Bitmap 4
AT Fault AT1 Diesel Exhaust Fluid PCC3300,
41405 1 Status 3558 Dosing Unit OOR High Warning PCC3300V2
Bitmap 4
AT Fault AT1 Diesel Exhaust Fluid PCC3300,
41405 2 Status 3559 Dosing Unit OOR Low Warning PCC3300V2
Bitmap 4
AT Fault AT DEF Line Heater Relay PCC3300,
41405 3 Status 3562 OOR High Warning PCC3300V2
Bitmap 4
AT Fault AT DEF Line Heater Relay PCC3300,
41405 4 Status 3563 OOR Low Warning PCC3300V2
Bitmap 4
AT Fault AT DEF Dosing Valve Open PCC3300,
41405 5 Status 3567 Circuit Warning PCC3300V2
Bitmap 4
AT Fault AT DEF Dosing Valve PCC3300,
41405 6 Status 3568 Mechanical system Error Warning PCC3300V2
Bitmap 4
AT Fault AT1 Diesel Exhaust Fluid PCC3300,
41405 7 Status 3571 Pressure Sensor OOR High Warning PCC3300V2
Bitmap 4
AT Fault AT1 Diesel Exhaust Fluid PCC3300,
41405 8 Status 3572 Pressure Sensor OOR Low Warning PCC3300V2
Bitmap 4
AT Fault AT1 Diesel Exhaust Fluid PCC3300,
41405 9 Status 3574 Pressure Sensor Low Warning PCC3300V2
Bitmap 4
AT Fault AT1 Diesel Exhaust Fluid PCC3300,
41405 10 Status 3575 Pressure Sensor High Warning PCC3300V2
Bitmap 4
AT Fault AT Diesel Exhaust Fluid PCC3300,
41405 11 Status 3577 Return Valve OOR High Warning PCC3300V2
Bitmap 4

Copyright © 2023 Cummins Inc. 920 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
AT Fault AT Diesel Exhaust Fluid PCC3300,
41405 12 Status 3578 Return Valve OOR Low Warning PCC3300V2
Bitmap 4
AT Fault AT SCR Catalyst PCC3300,
41405 13 Status 3582 Conversion Efficiency Low Warning PCC3300V2
Bitmap 4
AT Fault AT1 Outlet NOx Sensor PCC3300,
41405 14 Status 3583 Heater - Abnormal Warning PCC3300V2
Bitmap 4
AT Fault AT1 Diesel Exhaust Fluid PCC3300,
41405 15 Status 3596 Pressure Sensor Error Warning PCC3300V2
Bitmap 4
AT Fault AT1 Intake NOx Sensor PCC3300,
41406 0 Status 3649 Heater - Abnormal Warning PCC3300V2
Bitmap 5
AT Fault AT1 Outlet NOx Sensor PCC3300,
41406 1 Status 3681 Power Supply Error Warning PCC3300V2
Bitmap 5
AT Fault AT1 DOC Intake PCC3300,
41406 2 Status 5386 Temperature Error Warning PCC3300V2
Bitmap 5
AT Fault AT1 Outlet NOx Sensor - PCC3300,
41406 3 Status 3717 Out of Calibration Warning PCC3300V2
Bitmap 5
AT Fault Aftertreatment 1 Intake NOx PCC3300,
41406 4 Status 3725 Sensor - Abnormal Warning PCC3300V2
Bitmap 5
AT Fault AT1 DOC Intake PCC3300,
41406 5 Status 5387 Temperature Most Severe Shutdown PCC3300V2
Bitmap 5 Level
AT Fault AT1 Intake NOx Sensor - PCC3300,
41406 6 Status 3748 Data not Rational Warning PCC3300V2
Bitmap 5
AT Fault AT1 Outlet NOx Sensor - PCC3300,
41406 7 Status 3749 Data not Rational Warning PCC3300V2
Bitmap 5
AT Fault AT1 DOC Intake Temp PCC3300,
41406 8 Status 5388 Moderately Severe Level Shutdown PCC3300V2
Bitmap 5
AT Fault AT DEF Quality Low - PCC3300,
41406 9 Status 3867 Moderately Severe level Warning PCC3300V2
Bitmap 5
AT Fault AT Diesel Exhaust Fluid PCC3300,
41406 10 Status 3868 Quality Error Warning PCC3300V2
Bitmap 5

A029X159 (Issue 31) 921 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
AT Fault AT DEF Quality Sensor PCC3300,
41406 11 Status 3876 Mech system Error Warning PCC3300V2
Bitmap 5
AT Fault AT1 DOC Intake PCC3300,
41406 12 Status 5389 Temperature Least Severe Warning PCC3300V2
Bitmap 5 Level
AT Fault AT Diesel Exhaust Fluid PCC3300,
41406 13 Status 3878 Quality Sensor Data error Warning PCC3300V2
Bitmap 5
AT Fault AT DOC Temperature PCC3300,
41406 14 Status 5391 Sensor Module - Abnormal Warning PCC3300V2
Bitmap 5
AT Fault AT SCR Temperature PCC3300,
41406 15 Status 4152 Sensor Module - Abnormal Warning PCC3300V2
Bitmap 5
AT Fault AT1 DEF Dosing Unit PCC3300,
41407 0 Status 4155 Heater Relay OOR High Warning PCC3300V2
Bitmap 6
AT Fault AT1 DEF Dosing Unit PCC3300,
41407 1 Status 4156 Heater Relay OOR Low Warning PCC3300V2
Bitmap 6
AT Fault AT DEF Return Valve PCC3300,
41407 2 Status 4157 Mechanical system Error Warning PCC3300V2
Bitmap 6
AT Fault AT DOC Temperature PCC3300,
41407 3 Status 5392 Sensor Module - Bad Warning PCC3300V2
Bitmap 6 device
AT Fault AT SCR Temperature PCC3300,
41407 4 Status 4159 Sensor Module - Bad Warning PCC3300V2
Bitmap 6 Device
AT Fault AT DOC Temperature PCC3300,
41407 5 Status 5393 Sensor Module OOR High Warning PCC3300V2
Bitmap 6
AT Fault AT DOC Temperature PCC3300,
41407 6 Status 5394 Sensor Module OOR Low Warning PCC3300V2
Bitmap 6
AT Fault AT DOC Temp Sensor Root PCC3300,
41407 7 Status 5395 Cause Not Known Warning PCC3300V2
Bitmap 6
AT Fault AT SCR Temperature PCC3300,
41407 8 Status 4164 Sensor Module OOR High Warning PCC3300V2
Bitmap 6
AT Fault AT SCR Temperature PCC3300,
41407 9 Status 4165 Sensor Module OOR Low Warning PCC3300V2
Bitmap 6

Copyright © 2023 Cummins Inc. 922 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
AT Fault AT SCR Temperature PCC3300,
41407 10 Status 4166 Sensor Module High Warning PCC3300V2
Bitmap 6
AT Fault AT1 DEF Dosing Unit PCC3300,
41407 11 Status 4168 Heater OOR High Warning PCC3300V2
Bitmap 6
AT Fault AT1 DEF Dosing Unit PCC3300,
41407 12 Status 4169 Heater OOR Low Warning PCC3300V2
Bitmap 6
AT Fault Selective Catalytic PCC3300,
41407 13 Status 4171 Reduction Temperature Warning PCC3300V2
Bitmap 6 Low
AT Fault AT DOC Temperature PCC3300,
41407 14 Status 5396 Sensor Module High Warning PCC3300V2
Bitmap 6
AT Fault AT1 DOC System - Special PCC3300,
Shutdown
41407 15 Status 5617 Instructions PCC3300V2
w/Cooldown
Bitmap 6
AT Fault AT DEF Quality - Received PCC3300,
41408 0 Status 4241 Network Data Error Warning PCC3300V2
Bitmap 7
AT Fault AT1 Diesel Exhaust Fluid PCC3300,
41408 1 Status 4243 Temperature 2 - Abnormal Warning PCC3300V2
Bitmap 7
AT Fault Aftertreatment System PCC3300,
Shutdown
41408 2 Status 5362 Normal Shutdown Request PCC3300V2
w/Cooldown
Bitmap 7
AT Fault Aftertreatment system PCC3300,
41408 3 Status 5363 Datalink Degraded Warning PCC3300V2
Bitmap 7
AT Fault AT1 DEF Dosing PCC3300,
41408 4 Status 4249 Temperature - Abnormal Warning PCC3300V2
Bitmap 7
AT Fault AT SCR Temp Sensor PCC3300,
41408 6 Status 4261 Module - Root Cause Warning PCC3300V2
Bitmap 7 Unknown
AT Fault AT Diesel Exhaust Fluid PCC3300,
41408 7 Status 4277 Quality - Abnormal Warning PCC3300V2
Bitmap 7
AT Fault AT1 DEF Tank PCC3300,
41408 8 Status 4572 Temperature - Abnormal Warning PCC3300V2
Bitmap 7
AT Fault AT1 SCR Catalyst System - PCC3300,
41408 9 Status 4585 Special Instructions Shutdown PCC3300V2
Bitmap 7

A029X159 (Issue 31) 923 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
AT Fault AT SCR Actual Dosing PCC3300,
41408 10 Status 4658 Reagent Quantity Low Warning PCC3300V2
Bitmap 7
AT Fault AT1 DEF Tank Level PCC3300,
41409 0 Status 4739 Sensor - Root Cause Warning PCC3300V2
Bitmap 8 Unknown
AT Fault AT DEF Quality Sensor PCC3300,
41409 1 Status 4741 Open Circuit Warning PCC3300V2
Bitmap 8
AT Fault AT DEF Quality Sensor PCC3300,
41409 2 Status 4742 Short Circuit Warning PCC3300V2
Bitmap 8
AT Fault AT1 DEF Temperature 2 PCC3300,
41409 3 Status 4743 Sensor Open Circuit Warning PCC3300V2
Bitmap 8
AT Fault AT1 DEF Temperature 2 PCC3300,
41409 4 Status 4744 Sensor Short Circuit Warning PCC3300V2
Bitmap 8
AT Fault AT1 DEF Temperature 2 - PCC3300,
41409 5 Status 4745 Root Cause Unknown Warning PCC3300V2
Bitmap 8
AT Fault AT1 DEF Property - Root PCC3300,
41409 6 Status 4768 Cause Unknown Warning PCC3300V2
Bitmap 8
AT Fault AT DEF Replenishment PCC3300,
41409 7 Status 5711 Failure Warning PCC3300V2
Bitmap 8
AT Fault AT1 DEF Dosing Valve 1 PCC3300,
41410 0 Status 3565 OOR High Warning PCC3300V2
Bitmap 9
AT Fault AT DEF Quality low PCC3300,
41410 1 Status 3866 Warning Warning PCC3300V2
Bitmap 9
AT Fault AT1 DEF Tank Level PCC3300,
41410 2 Status 4677 Abnormal Update Rate Warning PCC3300V2
Bitmap 9
AT Fault AT Intake Oxygen Sensor PCC3300,
41410 3 Status 4747 Data not Rational - High Warning PCC3300V2
Bitmap 9
AT Fault AT Intake Oxygen Sensor PCC3300,
41410 4 Status 4748 Data not Rational - Low Warning PCC3300V2
Bitmap 9
AT Fault AT Outlet Oxygen Sensor PCC3300,
41410 5 Status 4749 Data not Rational - High Warning PCC3300V2
Bitmap 9

Copyright © 2023 Cummins Inc. 924 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
AT Fault AT Outlet Oxygen Sensor PCC3300,
41410 6 Status 4751 Data not Rational - Low Warning PCC3300V2
Bitmap 9
AT Fault AT1 DEF Tank Level2 PCC3300,
41410 7 Status 5176 Abnormal Update Rate Warning PCC3300V2
Bitmap 9
AT Fault AT1 SCR Intake Temp. PCC3300,
41410 8 Status 5247 High Warning Warning PCC3300V2
Bitmap 9
AT Fault AT1 SCR Conversion PCC3300,
41410 9 Status 5655 Efficiency Warning PCC3300V2
Bitmap 9
AT Fault AT1 Outlet NOx Sensor PCC3300,
41410 10 Status 5689 Error Warning PCC3300V2
Bitmap 9
AT Fault AT1 Outlet NOx Sensor PCC3300,
41410 11 Status 5838 Abnormal Rate of Change Warning PCC3300V2
Bitmap 9
AT Fault AT1 DEF Pump Command PCC3300,
41410 12 Status 5864 OOR High Warning PCC3300V2
Bitmap 9
AT Fault AT1 DEF Pump Command PCC3300,
41410 13 Status 5865 OOR Low Warning PCC3300V2
Bitmap 9
AT Fault AT DEF Dosing Unit Relay PCC3300,
41410 14 Status 5866 Feedback OOR High Warning PCC3300V2
Bitmap 9
AT Fault AT DEF Dosing Unit Relay PCC3300,
41410 15 Status 5867 Feedback OOR Low Warning PCC3300V2
Bitmap 9
AT Fault AT1 SCR System PCC3300,
41411 0 Status 5887 Hydrocarbon High NONE PCC3300V2
Bitmap 10
AT Fault AT1 SCR System PCC3300,
41411 1 Status 5888 Hydrocarbon High Warning Warning PCC3300V2
Bitmap 10
AT Fault AT1 SCR System PCC3300,
41411 2 Status 5889 Hydrocarbon High Shutdown PCC3300V2
Bitmap 10 Shutdown
AT Fault AT1 DEF Pressure PCC3300,
41411 3 Status 5935 Mechanical System Error Warning PCC3300V2
Bitmap 10
AT Fault AT1 DEF Pressure High PCC3300,
41411 4 Status 5936 Warning Warning PCC3300V2
Bitmap 10

A029X159 (Issue 31) 925 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
AT Fault AT1 Out Nox Sens Error PCC3300,
41411 5 Status 6464 NONE PCC3300V2
Bitmap 10
AT Fault AT1 DEF Tank Heater PCC3300,
41411 6 Status 6475 Mechanical Error NONE PCC3300V2
Bitmap 10
AT Fault AT1 DEF Tank Heater Low PCC3300,
41411 7 Status 6476 NONE PCC3300V2
Bitmap 10
AT Fault AT1 DEF Line Heater Relay PCC3300,
41411 8 Status 6477 OOR High NONE PCC3300V2
Bitmap 10
AT Fault AT1 DEF Line Heater Relay PCC3300,
41411 9 Status 6478 OOR Low NONE PCC3300V2
Bitmap 10
AT Fault AT1 DEF Tank Heater OOR PCC3300,
41411 10 Status 6479 High NONE PCC3300V2
Bitmap 10
AT Fault AT1 DEF Tank Heater OOR PCC3300,
41411 11 Status 6481 Low NONE PCC3300V2
Bitmap 10
AT Fault AT1 DEF Tank Level Out of PCC3300,
41411 12 Status 6526 Calibration Error NONE PCC3300V2
Bitmap 10
AT Fault AT1 DEF Line Heater1 PCC3300,
41411 13 Status 6531 OOR High NONE PCC3300V2
Bitmap 10
AT Fault AT1 DEF Line Heater1 PCC3300,
41411 14 Status 6532 OOR Low NONE PCC3300V2
Bitmap 10
AT Fault AT1 DEF Line Heater2 PCC3300,
41411 15 Status 6533 OOR High NONE PCC3300V2
Bitmap 10
AT Fault AT1 DEF Line Heater2 PCC3300,
41412 0 Status 6534 OOR Low NONE PCC3300V2
Bitmap 11
AT Fault AT1 DEF Line Heater3 PCC3300,
41412 1 Status 6535 OOR High NONE PCC3300V2
Bitmap 11
AT Fault AT1 DEF Line Heater3 PCC3300,
41412 2 Status 6536 OOR Low NONE PCC3300V2
Bitmap 11
AT Fault AT1 DEF Temperature 2 PCC3300,
41412 3 Status 6619 Abnormal Update Rate NONE PCC3300V2
Bitmap 11

Copyright © 2023 Cummins Inc. 926 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
AT Fault AT1 SCR System Soot High PCC3300,
41412 4 Status 6692 NONE PCC3300V2
Bitmap 11
AT Fault AT1 SCR System Soot High PCC3300,
41412 5 Status 6693 Warning Warning PCC3300V2
Bitmap 11
AT Fault AT1 SCR System Soot High PCC3300,
41412 6 Status 6694 Shutdown Shutdown PCC3300V2
Bitmap 11
AT Fault AT DEF Quality Low PCC3300,
41412 7 Status 6752 NONE PCC3300V2
Bitmap 11
AT Fault AT1 SCR System Cleaning PCC3300,
41412 8 Status 7268 Incomplete Error NONE PCC3300V2
Bitmap 11
AT Fault AT1 SCR System Cleaning PCC3300,
41412 9 Status 7269 Incomplete Error Warning Warning PCC3300V2
Bitmap 11
Fault Status Engine Wait to Start Lamp - PCC3300,
41416 0 4252 NONE
Bitmap 35 Condition Exists PCC3300V2
Fault Status Water in Fuel Indicator 2 PCC3300,
41416 1 4688 Warning
Bitmap 35 Sensor OOR Hi PCC3300V2
Fault Status Water in Fuel Indicator 2 PCC3300,
41416 2 4689 Warning
Bitmap 35 Sensor OOR Lo PCC3300V2
Fault Status High Water in Fuel Sensed PCC3300,
41416 3 5366 Warning
Bitmap 35 by Indicator 2 - Warning PCC3300V2
Fault Status High Water in Fuel Sensed PCC3300,
41416 4 5367 Shutdown
Bitmap 35 by Indicator 2-Shutdown PCC3300V2
Fault Status Dead Battery Warning PCC3300,
41416 5 5713 Warning
Bitmap 35 PCC3300V2
Fault Status Primary Starting System PCC3300,
41416 6 5714 Warning
Bitmap 35 Failed PCC3300V2
Fault Status IMR 2 Pressure Sensor PCC3300,
41416 7 483 Warning
Bitmap 35 Circuit Shorted to High PCC3300V2
Fault Status IMR 2 Pressure Sensor PCC3300,
41416 8 484 Warning
Bitmap 35 Circuit Shorted to Low PCC3300V2
Fault Status Cylinder Cut-Off System PCC3300,
41416 9 7823 Warning
Bitmap 35 failure PCC3300V2
Fault Status Cylinder Cut-Off System PCC3300,
41416 10 7824 Warning
Bitmap 35 State & Feedback Mismatch PCC3300V2
Fault Status DPF 1 Conditions Not Met PCC3300,
41416 11 3396 Warning
Bitmap 35 for Active Regeneration PCC3300V2

A029X159 (Issue 31) 927 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Intake Throttle Sensor PCC3300,
41416 12 3539 Warning
Bitmap 35 Circuit shorted to High PCC3300V2
Fault Status Intake Throttle Sensor PCC3300,
41416 13 3541 Warning
Bitmap 35 Circuit shorted to Low PCC3300V2
Fault Status Vehicle Identification PCC3300,
41416 15 4517 Warning
Bitmap 35 Number - Out of Calibration PCC3300V2
Fault Status High ECM Internal PCC3300,
41417 0 699 Warning
Bitmap 36 Temperature PCC3300V2
Fault Status Memory Write Failed PCC3300,
41417 1 5718 Warning
Bitmap 36 PCC3300V2
Fault Status Power Lost During Memory PCC3300,
41417 2 5719 Warning
Bitmap 36 Save PCC3300V2
Fault Status Auto Trims Save Failed PCC3300,
41417 3 5721 Warning
Bitmap 36 PCC3300V2
Fault Status Manual Trims Save Failed PCC3300,
41417 4 5722 Shutdown
Bitmap 36 PCC3300V2
Fault Status Paralleling Cable Not PCC3300,
41417 5 5723 NONE
Bitmap 36 Detected - Condition Exists PCC3300V2
Fault Status ASO Position Switch PCC3300,
41417 6 5221 Shutdown
Bitmap 36 mismatch PCC3300V2
Fault Status Max time exceeded since PCC3300,
41417 7 5292 Warning
Bitmap 36 last ASOV System test PCC3300V2
Fault Status ASO Solenoid out of range PCC3300,
41417 8 3139 Warning
Bitmap 36 high PCC3300V2
Fault Status ASO Solenoid out of range PCC3300,
41417 9 3141 Warning
Bitmap 36 low PCC3300V2
Fault Status Engine Air Shutoff - Mech. PCC3300,
41417 10 4484 Shutdown
Bitmap 36 Sys. Not Responding PCC3300V2
Fault Status ASOV E-Stop Active PCC3300,
41417 11 5291 Shutdown
Bitmap 36 PCC3300V2
Fault Status Intake Manifold Pressure PCC3300,
41417 12 3722 Shutdown
Bitmap 36 Bank Imbalance PCC3300V2
Fault Status Intake Manifold Vacuum PCC3300,
41417 13 4729 Shutdown
Bitmap 36 Detected – Bank 1 PCC3300V2
Fault Status Intake Manifold Vacuum PCC3300,
41417 14 5114 Shutdown
Bitmap 36 Detected – Bank 2 PCC3300V2
Fault Status Secondary Engine PCC3300,
41417 15 3131 Shutdown
Bitmap 36 Overspeed PCC3300V2
Fault Status "Throttle_Driver_Feedback_ PCC3300,
41418 0 5879 Warning
Bitmap 37 High_Error" PCC3300V2

Copyright © 2023 Cummins Inc. 928 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status "Throttle_Driver_Feedback_ PCC3300,
41418 1 5881 Warning
Bitmap 37 Low_Error" PCC3300V2
Fault Status Copy - PCC3300,
41418 2 Bitmap 37 5882 "Throttle_Driver_Feedback_ Warning PCC3300V2
Low_Error"
Fault Status Engine Witness Test Abort - PCC2300
41418 3 5788 Warning
Bitmap 37 Condition Exists
Fault Status Fail To Stop PCC3300,
41418 4 Bitmap 37 2677 Shutdown PCC2300,
PCC3300V2
Fault Status CRITICAL_CEN_NOT_ACC PCC3300,
Shutdown
41418 5 Bitmap 37 2727 ESSIBLE_ERROR PCC2300,
w/Cooldown
PCC3300V2
Fault Status J1939 Data Link 2 Engine PCC3300,
41418 6 Bitmap 37 1135 Network - Abnormal Shutdown PCC2300,
PCC3300V2
Fault Status J1939 Data Link 2 Eng PCC3300,
41418 7 Bitmap 37 782 Network No Data Recvd Shutdown PCC2300,
PCC3300V2
Fault Status J1939 Data Link 2 Eng PCC3300,
41418 8 Bitmap 37 5949 Network Special Shutdown PCC2300,
Instructions PCC3300V2
Fault Status Nominal Voltage Setup PCC3300,
41418 9 Bitmap 37 6487 OOR Shutdown PCC2300,
PCC3300V2
Fault Status At Least One Uncleared PCC3300,
41418 10 Bitmap 37 6598 ECS Shutdown Fault Exists Warning PCC2300,
PCC3300V2
Fault Status Fuel Pump Delivery PCC3300,
41418 11 Bitmap 37 2216 Pressure Warning PCC2300,
PCC3300V2
Fault Status Exhaust Gas Temperature PCC3300,
41418 12 Bitmap 37 6251 Bank Imbalance Warning PCC2300,
PCC3300V2
Fault Status Exhaust Gas Temperature PCC3300,
41418 13 Bitmap 37 6252 Shutdown PCC2300,
PCC3300V2
Fault Status Engine Fuel Delivery PCC3300,
41418 14 Bitmap 37 6719 Pressure Shutdown PCC2300,
PCC3300V2
Fault Status Engine Diesel Fuel Metering PCC3300,
41418 15 5863 Warning
Bitmap 37 Valve P Err PCC3300V2
Fault Status ECUs Reported DTCs PCC3300,
41419 0 5875 Shutdown
Bitmap 38 Affecting Operation PCC3300V2

A029X159 (Issue 31) 929 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Other ECUs Reported PCC3300,
41419 1 5876 Warning
Bitmap 38 DTCs Affecting Operation PCC3300V2
Fault Status Diesel Exhaust Fluid PCC3300,
41419 2 5777 Warning
Bitmap 38 Pressure 2 - Data Erratic PCC3300V2
Fault Status Ambient Temp(J11) OOR PCC2300
41419 3 249 Warning
Bitmap 38 High
Fault Status Ambient Temp(J11) OOR PCC2300
41419 4 256 Warning
Bitmap 38 Low
Fault Status Cold Start Idle - Active PCC3300,
41419 5 Bitmap 38 6638 NONE PCC2300,
PCC3300V2
Fault Status Alternate Frequency PCC3300,
41419 6 6818 Shutdown
Bitmap 38 Mismatch-MLD PCC3300V2
Fault Status Nominal Voltage Mismatch- PCC3300,
41419 7 6778 Shutdown
Bitmap 38 MLD PCC3300V2
Fault Status Under Excitation Fault PCC3300,
41419 8 6875 Shutdown
Bitmap 38 PCC3300V2
Fault Status Engine Friction Below PCC3300,
41419 9 7548 NONE
Bitmap 38 Baseline - Least Severe PCC3300V2
Fault Status Engine Friction Below PCC3300,
41419 10 Bitmap 38 7549 Baseline - Moderately Warning PCC3300V2
Severe
Fault Status Engine Friction Above PCC3300,
41419 11 7551 NONE
Bitmap 38 Baseline - Least Severe PCC3300V2
Fault Status Engine Friction Above PCC3300,
41419 12 Bitmap 38 7552 Baseline - Moderately Warning PCC3300V2
Severe
Fault Status Engine Friction Devn Above PCC3300,
41419 13 7553 Warning
Bitmap 38 Baseline - Mod Severity PCC3300V2
Fault Status Engine Friction Devn Above PCC3300,
41419 14 7554 Shutdown
Bitmap 38 Baseline - Most Severe PCC3300V2
Fault Status Alternator Feedback Power PCC3300,
41419 15 7555 Shutdown
Bitmap 38 PCC3300V2

TABLE 50.

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Generator Total Real Power PCC3300,
41420 0 7825 Shutdown
Bitmap 39 Sensing Failure PCC3300V2
Fault Status Bank Cut-Off FSO Failure PCC3300,
41420 1 7697 Shutdown
Bitmap 39 PCC3300V2

Copyright © 2023 Cummins Inc. 930 A029X159 (Issue 31)


8-2023 15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Eng Diesel Fuel Metering PCC3300,
41420 2 5862 Warning
Bitmap 39 Valve Pos-Abv Normal PCC3300V2
Fault Status Ctrl Module Identification I/P PCC3300,
41420 3 6253 Shutdown
Bitmap 39 State Err Spl Instr PCC3300V2
Fault Status Engine Diesel Fuel Metering PCC3300,
41420 4 6573 NONE
Bitmap 39 Valve Temp Mod Hi PCC3300V2
Fault Status Engine Diesel Fuel Metering PCC3300,
41420 5 6574 Warning
Bitmap 39 Valve Temp Hi PCC3300V2
Fault Status Fuel Filter Diff Press Above PCC3300,
41420 6 344 NONE
Bitmap 39 Normal Least Severe PCC3300V2
Fault Status Engine ECU Temp: Above PCC3300,
41420 7 3379 Warning
Bitmap 39 Normal PCC3300V2
Fault Status Start Signal Integrity Failure PCC3300,
41420 8 Bitmap 39 7892 Warning PCC2300,
PCC3300V2
Fault Status Failed Normal Start Attempt PCC3300,
41420 9 Bitmap 39 7243 Warning PCC2300,
PCC3300V2
Fault Status Charging Alternator Fuse PCC3300,
41420 10 8632 Warning
Bitmap 39 Failure PCC3300V2
Fault Status Engine Charge Air Cooler PCC3300,
41421 0 3478 Warning
Bitmap 40 Outlet Temperature Error PCC3300V2
Fault Status Engine Turbocharger Lube PCC3300,
41421 1 3917 Warning
Bitmap 40 Oil Pressure low Warning PCC3300V2
Fault Status Engine Brake Active Lamp PCC3300,
41421 2 4293 Warning
Bitmap 40 OOR High PCC3300V2
Fault Status Engine Brake Active Lamp PCC3300,
41421 3 4294 Warning
Bitmap 40 OOR Low PCC3300V2
Fault Status Battery 1 Voltage High PCC3300,
41421 4 6256 NONE
Bitmap 40 PCC3300V2
Fault Status Battery 1 Voltage Low PCC3300,
41421 5 6257 NONE
Bitmap 40 PCC3300V2
Fault Status Electric Lift Pump for Eng PCC3300,
41421 6 6258 NONE
Bitmap 40 Fuel Supply OOR High PCC3300V2
Fault Status Electric Lift Pump for Eng PCC3300,
41421 7 6259 NONE
Bitmap 40 Fuel Supply OOR Low PCC3300V2
Fault Status Fan Control Circuit OOR PCC3300,
41421 8 6263 NONE
Bitmap 40 High PCC3300V2
Fault Status Fan Control Circuit OOR PCC3300,
41421 9 6264 NONE
Bitmap 40 Low PCC3300V2
Fault Status Crankcase Breather Filter PCC3300,
41421 10 6336 NONE
Bitmap 40 Heater OOR High PCC3300V2

A029X159 (Issue 31) 931 Copyright © 2023 Cummins Inc.


15. PowerCommand 2.x/3.x/PS0500 Modbus Fault Status Bitmaps 8-2023

ModBus System Control


Bit Number Fault Code Event Name Response
Address Name Boards
Fault Status Crankcase Breather Filter PCC3300,
41421 11 6337 NONE
Bitmap 40 Heater OOR Low PCC3300V2
Fault Status Fan Speed High PCC3300,
41421 12 6467 NONE
Bitmap 40 PCC3300V2
Fault Status Fan Speed Low PCC3300,
41421 13 6468 NONE
Bitmap 40 PCC3300V2
Fault Status Coolant Level Sensor 1 PCC3300,
41421 14 6522 NONE
Bitmap 40 OOR Low PCC3300V2
Fault Status Coolant Level Sensor 1 PCC3300,
41421 15 6523 NONE
Bitmap 40 OOR High PCC3300V2
Fault Status Engine Oil Temperature PCC3300,
41422 0 6524 NONE
Bitmap 41 Sensor 1 OOR High PCC3300V2
Fault Status Engine Oil Temperature PCC3300,
41422 1 6525 NONE
Bitmap 41 Sensor 1 OOR Low PCC3300V2
Fault Status Engine Speed Root Cause PCC3300,
41422 2 6595 NONE
Bitmap 41 Unknown PCC3300V2
Fault Status Engine Turbocharger Speed PCC3300,
41422 3 7135 Warning
Bitmap 41 High Warning PCC3300V2
Fault Status Bank A STC Failure on Low PCC3300V2
41422 4 8636 Warning
Bitmap 41 Load
Fault Status Bank B STC Failure on Low PCC3300V2
41422 5 8637 Warning
Bitmap 41 Load
Fault Status Bank A STC Failure on PCC3300V2
41422 6 8638 Shutdown
Bitmap 41 High Load
Fault Status Bank B STC Failure on PCC3300V2
41422 7 8639 Shutdown
Bitmap 41 High Load
Fault Status Bank A Pressure OORH PCC3300V2
41422 8 8641 Warning
Bitmap 41
Fault Status Bank A Pressure OORL PCC3300V2
41422 9 8642 Warning
Bitmap 41
Fault Status Bank B Pressure OORH PCC3300V2
41422 10 8643 Warning
Bitmap 41
Fault Status Bank B Pressure OORL PCC3300V2
41422 11 8644 Warning
Bitmap 41
Fault Status Maintenance Required - PCC3300V2
41422 12 6226 Warning
Bitmap 41 Condition Exists
Fault Status Crankcase Pres 2 below PCC3300V2
41423 0 13266 Warning
Bitmap 42 normal Moderately Severe
Fault Status PTC Manual Mode Active PCC3300,
41423 3 13438 NONE
Bitmap 42 PCC3300V2

Copyright © 2023 Cummins Inc. 932 A029X159 (Issue 31)


16 PS060X Modbus Register Map
16.1 General Instructions
16.1.1 Modbus RTU Supported Functions
The control supports the Modbus function codes described below. The control shall respond to any
function code other than those listed by sending an exception response of Illegal Function (01).
Read Holding Registers (Function Code 03)
The control provides the ability to read 1 to 125 consecutive holding registers.
The control shall respond to any read request to address not defined in the control by returning 0xFFFF
data for that address.
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the holding register read request is not defined on the control.
• The first register in the holding register read request does not allow for the full representation of a
numeric value. This would occur if the first register in the read request is not mapped to the most
significant 2 bytes of a binary value parameter.
• The last register in the holding register read request does not allow for the full representation of a
numeric value. This would occur if the last register in the read request is not mapped to the least
significant 2 bytes of a binary value parameter.
Read requests for string type parameters where not every register associated with the string is in the
request shall return only the requested portion of the string.
Read Input Registers (Function Code 04)
The control provides the ability to read 1 to 125 consecutive input registers.
The control shall respond to any read request to address not defined in the control by returning 0xFFFF
data for that address.
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the input register read request is not defined on the control.
• The first register in the input register read request does not allow for the full representation of a
numeric value. This would occur if the first register in the read request is not mapped to the most
significant 2 bytes of a parameter.
• The last register in the input register read request does not allow for the full representation of a
numeric value. This would occur if the last register in the read request is not mapped to the least
significant 2 bytes of a parameter.
The Input Registers support by each port on the control are listed in the Read Input Registers Table
below.
Write Single Holding Register (Function Code 06)
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The register in the holding register write request is not defined on the control.
• The register in the holding register write request does not allow for the full writing of a numeric value.
This would occur if the register is part of a numeric parameter that requires more than one address
to represent.

A029X159 (Issue 31) 933 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

• If writing to a string values, the register in the holding register write request is not the first register of
that string.
Write requests for string type parameters where not every register associated with the string is in the
request shall write only the requested portion of the string, null terminating the remainder of the string.
Write requests to this control may return an Illegal Data Value exception code 03. This means that the
requested write failed to occur.
Write Multiple Holding Registers (Function Code 16)
The control provides the ability to write to 1 to 123 consecutive holding registers.
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the holding register write request is not defined on the control.
• The first register in the holding register write request does not allow for the full writing of a numeric
value. This would occur if the first register in the write request is not mapped to the most significant
2 bytes of a parameter.
• The last register in the holding register write request does not allow for the full writing of a numeric
value. This would occur if the last register in the write request is not mapped to the least significant 2
bytes of a parameter.
• If string values are in the write request, the first register for any string is not within the requested
register range.
Write requests for string type parameters where not every register associated with the string is in the
request shall write only the requested portion of the string, null terminating the remainder of the string.
Write requests to this control may return an Illegal Data Value exception code 03. This means that some
or all of the requested writes failed to occur. It is the responsibility of the requestor to read the data again
to determine which parameters were not written to their requested new values and to respond as
necessary.

16.1.2 Modbus RTU Serial Port Configuration Options


The following configuration options shall be available for each port the control that supports the Modbus
RTU protocol. See the controller Modbus register map for individual register assignments for these
parameters on any given port.

TABLE 51. CONFIGURATION OPTIONS

Parameter Name Description Specification


Modbus Node Address Sets this ports node address. Multiplier: 1
Offset: 0
Size (bits): 16
Sign: U
Unit:
Lower Limit: 1
Upper Limit: 247

Copyright © 2023 Cummins Inc. 934 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Parameter Name Description Specification


Modbus Baud Rate Sets this ports baud rate. 0: 2400
1: 4800
2: 9600
3: 19200
4: 28800
5: 38400
6: 57600
7: 115200
Modbus Parity and Stop Bit Selection Sets this ports parity and stop bit 0: No Parity (1 Stop)
communications settings. 1: No Parity (2 Stop)
2: Even Parity (1 Stop)
3: Odd Parity (1 Stop)
Modbus Failure Time Delay Sets the time delay for the detection Multiplier: 1
of the lack of Modbus packets on the Offset: 0
communications bus. Size (bits): 8
Sign: U
Unit: seconds
Lower Limit: 1
Upper Limit: 60

NOTICE
Changes to the Modbus Baud Rate and the Modbus Parity and Stop Bit Selection parameters will
be immediately reflected on the serial port being configured. Any Modbus commands in progress
on that port in the old communications settings will fail until the Modbus master also updates its
communications settings to match those of the slave.

Modbus RTU Extended Status information


The control represents abnormal states in the data by using the five most positive values of the data to
convey that these abnormal states exist. The states will only be applicable to numeric parameters with the
following data types:
• UINT8, INT8, UINT16, INT16, UINT32, INT32, UINT64, INT64 (signed and unsigned 8-bit through
64-bit parameters)
Note that enumerated parameters and parameters with a floating point data type will not follow these
abnormal state representation methods.
The following abnormal states are supported:
Supported Abnormal States

A029X159 (Issue 31) 935 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Value Examples
Examples of
Abnormal State Value Description Unsigned 2-Byte Signed 2-Byte Failures
Integer Value Integer Value
This data shall An on controller
Hardware/ represented as 4 less hardware/component
than the highest 65531 32763 failure that provides
Component Failure positive value for that data like voltage,
parameter. current and power
Data that comes from
This data shall be
a network that has
represented as 3 less
failed such as sensor
Network Failed Data than the highest 65532 32764
data coming from I/O
positive value for that
modules on a PCCnet
parameter.
or CAN network
Data that has been
determined to be out
This data shall be of range LOW or out
represented as 2 less of range (when there
Out of Range Low than the highest 65533 32765 is no distinction
positive value for that between out of range
parameter. high and out of range
low) due to an open
sensor
Data that has been
determined to be out
This data shall be of range HIGH or out
represented as 1 less of range (when there
Out of Range
than the highest 65534 32766 is no distinction
High/Out of Range
positive value for that between out of range
parameter. high and out of range
low) due to an open
sensor
Parameters which are
not available due to
This data shall be
the sensor not being
Unsupported (Not represented as the
65535 32767 installed or not
Available) Data highest positive value
enabled in the
for that parameter.
controller’s
configuration

Working with 8-Bit Data Types


When reading a register that contains information in an 8 bit data type, the data will be put the least
significant byte of the register. If the data type is unsigned, the upper byte will be populated with zeros. If
the data type is signed, the upper byte will be sign extended with the sign bit value of the data byte.
When writing a register that contains information that is expected to be in an 8 bit data type, the control
will expect the data to be in the least significant byte of the register and ignore the upper byte.
Representation of Multi-Register Parameters
• For numeric parameters requiring more than one Register to represent the data, the Register
Address listed in the Controllers Modbus Register Map represents the most significant 2 bytes of the
data. The additional bytes of the data will always be provided in Register Address + 1, Register
Address + 2, and Register Address +3 as appropriate.

Copyright © 2023 Cummins Inc. 936 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

• For string parameters, the first two characters in the string will be mapped to the Register Address
listed in the Controllers Modbus Register Map. Additional characters will be provided in the following
registers. For example, for the string "String1" at address 400031, the characters will be mapped the
following registers:
400031: "St" 400032: "ri" 400033: "ng" 400034: "1_"
Modbus RTU Slave Protocol Support for Read Input Registers
Each port instance of Modbus RTU Slave Protocol shall support interface to the following read input
registers through function code 04. These are the only input registers supported by this control.
The following table applies for each instance of the Modbus RTU protocol on any control and will return
the data from the port being read only.

TABLE 52. READ INPUT REGISTERS TABLE

Register Data Size Scaling


Name Description
Address Type (Registers) Factor
This parameter contains the
quantity of messages that
this port has detected on
30001 Bus Message Count the communications system uint32 2 1
since its last restart, clear
counters operation, or
power-up.
This parameter stores
quantity of CRC errors
encountered by this port
30003 Bus CRC Error Count uint32 2 1
since its last restart, clear
counters operation, or
power-up.
This parameter contains the
quantity of exception
responses returned by this
30005 Bus Exception Error Count uint32 2 1
port since its last restart,
clear counters operation, or
power-up.
This parameter contains the
quantity of messages
addressed to this port for
30007 Server No Response Count which it has returned no uint32 2 1
response since its last
restart, clear counters
operation, or power-up,
The parameter contains the
quantity of messages
addressed to this port that it
30009 Server Message Count uint32 2 1
has processed since its last
restart, clear counters
operation, or power-up.

A029X159 (Issue 31) 937 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Register Data Size Scaling


Name Description
Address Type (Registers) Factor
This parameter holds the
Modbus Time Stamp at year of the time stamp
30011 uint8 1 1
Counter Reset - Year record when counters were
cleared last time.
This parameter holds the
Modbus Time Stamp at month of the time stamp
30012 uint8 1 1
Counter Reset - Month record when counters were
cleared last time.
This parameter holds the
day of the month of the time
Modbus Time Stamp at
30013 stamp record when uint8 1 1
Counter Reset - Date
counters were cleared last
time.
This parameter holds the
Modbus Time Stamp at hour of the time stamp
30014 uint8 1 1
Counter Reset – Hour record when counters were
cleared last time.
This parameter holds the
Modbus Time Stamp at minute of the time stamp
30015 uint8 1 1
Counter Reset - Minute record when counters were
cleared last time.
This parameter holds the
Modbus Time Stamp at seconds of the time stamp
30016 uint8 1 1
Counter Reset - Seconds record when counters were
cleared last time.
This parameter maintains
Modbus Time Since Last the time in seconds since
30017 uint32 2 1
Counter Reset the last reset of Modbus
diagnostic counters.

16.2 PS060X Modbus Register Map


The controller contains data that can be read by a master device communicating via Modbus RTU
protocol on a two-wire RS485 multi-drop bus. The Cummins control is a slave unit.
For more information about the Modbus protocol, refer to Modbus Application Protocol V1.1b3 and
Modbus Serial Line Implementation Guide V1.02, which are both available at www.modbus.org.
See also the NFPA 110 Bitmap (PS060X) section.
PS060X RS485 Pins
• A (+): TB15-3
• B (-): TB15-4
• Common: TB15-1

TABLE 53. ACCESS LEVELS

Level Description

Copyright © 2023 Cummins Inc. 938 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Read Only This defines the specific parameter as a read-only type.


Guest This defines the specific parameter as read or write type.
Technician An authorized service person must set the Modbus communication port access level parameter to
"Technician" through the service tool to enable writing.

NOTICE
If an address or bit is not listed in the table below, it has not been implemented.

NOTICE
The master device can read 1-16 contiguous registers, write 1-16 contiguous registers, or read
diagnostic counters.

NOTICE
To connect with the Modbus tool, set the TB15 Protocol selection parameter to “Modbus” via a
service tool or LCD, which will immediately disconnect the PC tool. To reconnect the PC tool, set
the TB15 protocol selection to “Mon through Display configuration”, or enter "0" in the specific
TB15 protocol selection Modbus resistor address.

NOTICE
Earlier versions of this software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the Modbus
connection is working but the controller software does not support that particular register.

TABLE 54. PS060X MODBUS REGISTER MAP

Addr Parameter Access Specifications Description Control


400009 Application Read Only Multiplier: 1 The common device type PS060X
Device Type Size (Bits): 16 identifier parameter for all
Data Type: uint16 PGBASE applications
Unit: NA
Lower Limit: 0
Upper Limit: 65535
400010 Control Read Only 0: Off Current position of the PS060X
Switch 1: Auto generator set switch panel
Position 2: Manual Off-Run-Auto switch as seen
by the generator set control

A029X159 (Issue 31) 939 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


400011 Genset State Read Only 0: Off Provides the state in which PS060X
1: Stop the generator set is currently
2: Preheat present
3: Precrank
4: Crank
5: Starter Disconnect
6: PreRamp
7: Ramp
8: Running
9: Fault Shutdown
10: Prerun Setup
11: Runtime Setup
12: Factory Test
13: Waiting For Powerdown
400012 Current Fault Read Only Multiplier: 1 Fault number of active fault; PS060X
Size (Bits): 16 clears when all faults are
Data Type: uint16 Inactive
Unit: NA
Lower Limit: 0
Upper Limit: 65535
400013 Current Fault Read Only 0: None Displays fault severity of PS060X
Severity 1: Warning recently occurred fault
2: Shutdown
400016 NFPA 110 Read Only Multiplier: 1 32-bit number to represent PS060X
Fault Register Size (Bits): 32 the status of the NFPA 110
Data Type: uint32 fault register; refer to the
NFPA 110 Bitmap (PS060X)
Unit: NA
section
Lower Limit: 0
Upper Limit: 4294967295
400018 Genset L1-N Read Only Multiplier: 1 RMS Voltage between Line 1 PS060X
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400019 Genset L2-N Read Only Multiplier: 1 RMS Voltage between Line 2 PS060X
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000

Copyright © 2023 Cummins Inc. 940 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


400020 Genset L3-N Read Only Multiplier: 1 RMS Voltage between Line 3 PS060X
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400022 Genset L1-L2 Read Only Multiplier: 1 RMS Voltage between Line 1 PS060X
RMS Voltage Size (Bits): 16 and Line 2
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400023 Genset L2-L3 Read Only Multiplier: 1 RMS Voltage between Line 2 PS060X
RMS Voltage Size (Bits): 16 and Line 3
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400024 Genset L3-L1 Read Only Multiplier: 1 RMS Voltage between Line 3 PS060X
RMS Voltage Size (Bits): 16 and Line 1
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400026 Genset L1 Read Only Multiplier: 1 RMS Current through Line 1 PS060X
RMS Current Size (Bits): 16
Data Type: uint16
Unit: Amps
Lower Limit: 0
Upper Limit: 10000
400027 Genset L2 Read Only Multiplier: 1 RMS Current through Line 2 PS060X
RMS Current Size (Bits): 16
Data Type: uint16
Unit: Amps
Lower Limit: 0
Upper Limit: 10000
400028 Genset L3 Read Only Multiplier: 1 RMS Current through Line 3 PS060X
RMS Current Size (Bits): 16
Data Type: uint16
Unit: Amps
Lower Limit: 0
Upper Limit: 10000

A029X159 (Issue 31) 941 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


400031 Genset L1 Read Only Multiplier: 1 kW value at Line 1 PS060X
kW Size (Bits): 16
Data Type: int16
Unit: kW
Lower Limit: -10000
Upper Limit: 10000
400032 Genset L2 Read Only Multiplier: 1 kW value at Line 2 PS060X
kW Size (Bits): 16
Data Type: int16
Unit: kW
Lower Limit: -10000
Upper Limit: 10000
400033 Genset L3 Read Only Multiplier: 1 kW value at Line 3 PS060X
kW Size (Bits): 16
Data Type: int16
Unit: kW
Lower Limit: -10000
Upper Limit: 10000
400034 Genset Total Read Only Multiplier: 1 Sum of kW values of all PS060X
kW Size (Bits): 16 phases
Data Type: int16
Unit: kW
Lower Limit: -10000
Upper Limit: 10000
400035 Genset L1 Read Only Multiplier: 1 kVAR value at Line 1 PS060X
kVAr Size (Bits): 16
Data Type: int16
Unit: kVAr
Lower Limit: -10000
Upper Limit: 10000
400036 Genset L2 Read Only Multiplier: 1 kVAR value at Line 2 PS060X
kVAr Size (Bits): 16
Data Type: int16
Unit: kVAr
Lower Limit: -10000
Upper Limit: 10000
400037 Genset L3 Read Only Multiplier: 1 kVAR value at Line 3 PS060X
kVAr Size (Bits): 16
Data Type: int16
Unit: kVAr
Lower Limit: -10000
Upper Limit: 10000

Copyright © 2023 Cummins Inc. 942 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


400038 Genset Total Read Only Multiplier: 1 Total kVAR Value PS060X
kVAr Size (Bits): 16
Data Type: int16
Unit: kVAr
Lower Limit: -10000
Upper Limit: 10000
400040 Genset L1 Read Only Multiplier: 1 kVA value at Line 1 PS060X
kVA Size (Bits): 16
Data Type: uint16
Unit: kVA
Lower Limit: 0
Upper Limit: 10000
400041 Genset L2 Read Only Multiplier: 1 kVA value at Line 2 PS060X
kVA Size (Bits): 16
Data Type: uint16
Unit: kVA
Lower Limit: 0
Upper Limit: 10000
400042 Genset L3 Read Only Multiplier: 1 kVA value at Line 3 PS060X
kVA Size (Bits): 16
Data Type: uint16
Unit: kVA
Lower Limit: 0
Upper Limit: 10000
400043 Genset Total Read Only Multiplier: 1 Sum of kVA values of all PS060X
kVA Size (Bits): 16 phases
Data Type: uint16
Unit: kVA
Lower Limit: 0
Upper Limit: 10000
400044 Genset Read Only Multiplier: 0.01 Measured Frequency for PS060X
Frequency Size (Bits): 16 Meter1
Data Type: uint16
Unit: Hz
Lower Limit: 0
Upper Limit: 100
400058 Genset L1 Read Only Multiplier: 0.1 % RMS Current value at Line PS060X
RMS Size (Bits): 16 1
Current % Data Type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 1000

A029X159 (Issue 31) 943 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


400059 Genset L2 Read Only Multiplier: 0.1 % RMS Current value at Line PS060X
RMS Size (Bits): 16 2
Current % Data Type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 1000
400060 Genset L3 Read Only Multiplier: 0.1 % RMS Current value at Line PS060X
RMS Size (Bits): 16 3
Current % Data Type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 1000
400061 Battery Read Only Multiplier: 0.001 Measured battery voltage PS060X
Voltage Size (Bits): 16 value.
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 41
400062 Oil Pressure Read Only Multiplier: 0.1 Metered Engine Oil Pressure PS060X
Size (Bits): 16
Data Type: uint16
Unit: psi
Lower Limit: 0
Upper Limit: 900
400063 Oil Read Only Multiplier: 0.1 Monitor point for Oil PS060X
Temperature Size (Bits): 16 Temperature
Data Type: int16
Unit: degF
Lower Limit: 459.4
Upper Limit: 3154.9
400064 Coolant Read Only Multiplier: 0.1 Metered Engine Coolant PS060X
Temperature Size (Bits): 16 Temperature value in DegF
Data Type: int16
Unit: degF
Lower Limit: -40
Upper Limit: 410
400065 Intake Read Only Multiplier: 0.1 Monitor point for Intake PS060X
Manifold Size (Bits): 16 Manifold Temperature
Temperature Data Type: int16
Unit: degF
Lower Limit: 40
Upper Limit: 410

Copyright © 2023 Cummins Inc. 944 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


400066 Fuel Read Only Multiplier: 0.1 Monitor point for Fuel PS060X
Temperature Size (Bits): 16 Temperature
Data Type: int16
Unit: degF
Lower Limit: 40
Upper Limit: 410
400068 Average Read Only Multiplier: 0.125 Average Engine Speed used PS060X
Engine Size (Bits): 16 for controls and governing.
Speed Data Type: uint16
Unit: rpm
Lower Limit: 0
Upper Limit: 8191.875
400069 Start Guest Multiplier: 1 Number of times generator PS060X
Attempts Size (Bits): 16 set start request has been
Data Type: uint16 provided over the life of unit.
Unit: NA
Lower Limit: 0
Upper Limit: 65535
400070 Engine Guest Multiplier: 0.05 Engine Running time in PS060X
Running Time Size (Bits): 32 hours; pper limit is 13.6 years
Data Type: uint32
Unit: Hours
Lower Limit: 0
Upper Limit: 119304.65
400118 Utility L1-N Read Only Multiplier: 1 RMS Voltage between Line 1 PS060X
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400119 Utility L2-N Read Only Multiplier: 1 RMS Voltage between Line 2 PS060X
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400120 Utility L3-N Read Only Multiplier: 1 RMS Voltage between Line 3 PS060X
RMS Voltage Size (Bits): 16 and Neutral
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000

A029X159 (Issue 31) 945 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


400122 Utility L1-L2 Read Only Multiplier: 1 RMS Voltage between Line 1 PS060X
RMS Voltage Size (Bits): 16 and Line 2
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400123 Utility L2-L3 Read Only Multiplier: 1 RMS Voltage between Line 2 PS060X
RMS Voltage Size (Bits): 16 and Line 3
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400124 Utility L3-L1 Read Only Multiplier: 1 RMS Voltage between Line 3 PS060X
RMS Voltage Size (Bits): 16 and Line 1
Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 45000
400144 Utility Read Only Multiplier: 0.001 Measured Frequency for PS060X
Frequency Size (Bits): 32 Meter 2
Data Type: uint32
Unit: Hz
Lower Limit: 0
Upper Limit: 100
400146 Customer Read Only 0: IsFalse Digital status of Customer PS060X
Input #5 1: IsTrue Input #5

400147 Customer Read Only 0: IsFalse Digital status of Customer PS060X


Input #6 1: IsTrue Input #6

400148 Diagnostic Read Only 0: IsFalse Digital output command to PS060X


Output #7 1: IsTrue Customer Output #7
Output Status
400149 Diagnostic Read Only 0: IsFalse Digital output command to PS060X
Output #8 1: IsTrue Customer Output #8
Output Status
400150 Diagnostic Read Only 0: IsFalse Digital output command to PS060X
Output #9 1: IsTrue Customer Output #9
Output Status
400151 Diagnostic Guest Multiplier: 1 Sets the diagnostic code to PS060X
Output #4 Size (Bits): 16 activate Customer Output #4
Fault Code Data Type: uint16 actuator
Unit: N/A
Lower Limit: 0
Upper Limit: 65535

Copyright © 2023 Cummins Inc. 946 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


400152 Diagnostic Guest Multiplier: 1 Sets the diagnostic code to PS060X
Output #6 Size (Bits): 16 activate Customer Output #6
Fault Code Data Type: uint16 actuator
Unit: N/A
Lower Limit: 0
Upper Limit: 65535
400153 Diagnostic Guest Multiplier: 1 Sets the diagnostic code to PS060X
Output #5 Size (Bits): 16 activate Customer Output #5
Fault Code Data Type: uint16 actuator
Unit: N/A
Lower Limit: 0
Upper Limit: 65535
400154 Customer Guest 0: None Fault response for Customer PS060X
Input #4 Fault 1: Warning Input #4
Response 2: Shutdown
400155 Customer Guest 0: None Fault response for Customer PS060X
Input #5 Fault 1: Warning Input #5
Response 2: Shutdown
400156 Customer Guest 0: None Fault response for Customer PS060X
Input #6 Fault 1: Warning Input #6
Response 2: Shutdown
400157 Customer Read Only 0: IsFalse Digital status of Customer PS060X
Input #4 1: IsTrue Input #4

400160 TB17-4 Guest 0: Not Connected Sets the value of TB17-4 PS060X
Sensor 1: Diagnostic Input #4 Sensor Selection
Selection
400161 TB17-5 Guest 0: Not Connected Sets the value of TB17-5 PS060X
Sensor 1: Diagnostic Input #5 Sensor Selection
Selection
400162 TB17-6 Guest 0: Not Connected Sets the value of TB17-6 PS060X
Sensor 1: Diagnostic Input #6 Sensor Selection
Selection
400207 Charging Read Only Multiplier: 0.001 Measured Charging PS060X
Alternator Size (Bits): 16 Alternator voltage value
Voltage Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 41
400228 Amber Read Only 0: Inactive Engine Conrol System PS060X
Warning 1: Active warning condition
Lamp Status

A029X159 (Issue 31) 947 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


400230 Boost Read Only Multiplier: 0.1 Monitor point for Boost PS060X
Pressure Size (Bits): 16 Absolute Pressure
Data Type: uint16
Unit: psi
Lower Limit: 0
Upper Limit: 145
400231 CAN Datalink Read Only 0: Inactive Status of CAN Datalink PS060X
Status 1: Active
2: Failed
400232 Crankcase Read Only Multiplier: 0.1 Monitor point for Crankcase PS060X
Pressure Size (Bits): 16 Pressure
Data Type: int16
Unit: psi
Lower Limit: 36.2
Upper Limit: 40.0
400238 PGI Major Read Only Multiplier: 1 Power Generation Interface PS060X
Version Size (Bits): 8 Major Version to which
Data Type: uint8 Engine Software is complying
Unit: N/A
Lower Limit: 0
Upper Limit: 255
400239 PGI Minor Read Only Multiplier: 1 Power Generation Interface PS060X
Version Size (Bits): 8 Minor Version to which
Data Type: uint8 Engine Software is complying
Unit: N/A
Lower Limit: 0
Upper Limit: 255
400240 PGI Read Only Multiplier: 1 Power Generation Interface PS060X
Informational Size (Bits): 8 Informational Version to
Version Data Type: uint8 which Engine Software is
complying
Unit: N/A
Lower Limit: 0
Upper Limit: 255
400254 Fuel Supply Read Only Multiplier: 0.1 Monitor point for Fuel Supply PS060X
Pressure Size (Bits): 16 Pressure
Data Type: uint16
Unit: psi
Lower Limit: 0
Upper Limit: 145

Copyright © 2023 Cummins Inc. 948 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


400258 Fuel Outlet Read Only Multiplier: 0.1 Monitor point for Fuel Outlet PS060X
Pressure Size (Bits): 32 Pressure (Fuel Rail Pressure)
Data Type: uint32
Unit: psi
Lower Limit: 0
Upper Limit: 36404
400264 Percent Read Only Multiplier: 1 Monitor point for the percent PS060X
Engine Size (Bits): 16 engine torque output and the
Torque/Duty Data Type: int16 governor percent duty cycle
Cycle output when used with the
Unit: Percent
HM ECM
Lower Limit: 125
Upper Limit: 125
400300 Modbus Guest 0: Inactive Modbus Remote Start PS060X
Remote Start 1: Active
400301 Modbus Fault Guest 0: Inactive Fault reset via Modbus PS060X
Reset 1: Active
400302 Network Guest 0: Inactive Displays network shutdown PS060X
Shutdown 1: Active Modbus command as
Modbus received from Modbus
Command master; set to simulate the
associated diagnostic
400535 Diagnostic Guest Multiplier: 1 Sets the diagnostic code to PS060X
Output #1 Size (Bits): 16 activate Customer Output #1
Fault Code Data Type: uint16 actuator
Unit: NA
Lower Limit: 0
Upper Limit: 65535
400536 Diagnostic Guest Multiplier: 1 Sets the diagnostic code to PS060X
Output #2 Size (Bits): 16 activate Customer Output #2
Fault Code Data Type: uint16 actuator
Unit: NA
Lower Limit: 0
Upper Limit: 65535
400540 Diagnostic Read Only 0: IsFalse The digital output command PS060X
Output #3 1: IsTrue to the Customer Output #3
Output Status
400541 Diagnostic Read Only 0: IsFalse The digital output command PS060X
Output #4 1: IsTrue to the Customer Output #4
Output Status
400543 Fuel Shutoff Read Only 0: IsFalse The digital output command PS060X
Output Status 1: IsTrue to the Fuel Shutoff actuator

400547 Keyswitch Guest 0: Inactive Status of Keyswitch PS060X


Command 1: Active command

A029X159 (Issue 31) 949 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


400552 Diagnostic Read Only 0: IsFalse The digital output command PS060X
Output #6 1: IsTrue to the Customer Output #6
Output Status
400553 Diagnostic Read Only 0: IsFalse The digital output command PS060X
Output #5 1: IsTrue to the Customer Output #5
Output Status
400557 Starter Read Only 0: IsFalse The digital output command PS060X
Output Status 1: IsTrue to the Starter actuator

400585 Exhaust Gas Read Only Multiplier: 0.1 Monitor point for Exhaust Gas PS060X
Temperature Size (Bits): 16 Temperature
Data Type: int16
Unit: degF
Lower Limit: 459.4
Upper Limit: 3154.9
400597 SCR Thermal Read Only 0: Inactive Indicates that the exhaust PS060X
Management 1: Active temperatures have been
Active 2: Not Available elevated for regeneration of
the SCR aftertreatment
3: Network Failure
system or in preparation of
regeneration of the SCR
aftertreatment system
400616 DPF Thermal Read Only 0: Inactive Indicates that the exhaust PS060X
Management 1: Active temperatures have been
Active 2: Not Available elevated for regeneration of
the diesel particulate filter
3: Network Failure
aftertreatment system or in
preparation of regeneration of
the diesel particulate
aftertreatment system
400617 AT Diesel Read Only Multiplier: 0.1 Indicates the temperature of PS060X
Oxidation Size (Bits): 16 engine combustion by
Catalyst Data Type: int16 products entering the diesel
Intake Gas oxidation catalyst in exhaust
Unit: degF
Temperature bank 1
Lower Limit: 459.4
Upper Limit: 3154.9
400709 Application Read Only Multiplier: 1 The common device type PS060X
Device Type Size (Bits): 16 identifier parameter for all
Data Type: uint16 PGBASE applications
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401000 Metering Technician 0: Three Phase Wye Used to select the phase PS060X
Phase Config 1: Three Phase Delta configuration and Delta/Wye
2: Single Phase configuration for AC power
distribution
3: Split Phase

Copyright © 2023 Cummins Inc. 950 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


401001 Customer Guest 0: None The fault response for PS060X
Input #3 Fault 1: Warning Customer Input #3
Response 2: Shutdown
401002 Active Read Only Multiplier: 1 First entry of Active shutdown PS060X
Shutdown Size (Bits): 16 fault code present in Active
Fault Code Data Type: uint16 Shutdown Fault table
Row 1
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401003 Active Read Only Multiplier: 1 Second entry of Active PS060X
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 2 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401004 Active Read Only Multiplier: 1 Third entry of Active PS060X
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 3 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401005 Active Read Only Multiplier: 1 Fourth entry of Active PS060X
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 4 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401006 Active Read Only Multiplier: 1 Fifth entry of Active shutdown PS060X
Shutdown Size (Bits): 16 fault code present in Active
Fault Code Data Type: uint16 Shutdown Fault table
Row 5
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401007 Active Read Only Multiplier: 1 Sixth entry of Active PS060X
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 6 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535

A029X159 (Issue 31) 951 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


401008 Active Read Only Multiplier: 1 Seventh entry of Active PS060X
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 7 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401009 Active Read Only Multiplier: 1 Eighth entry of Active PS060X
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 8 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401010 Active Read Only Multiplier: 1 Ninth entry of Active PS060X
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 9 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401011 Active Read Only Multiplier: 1 Tenth entry of Active PS060X
Shutdown Size (Bits): 16 shutdown fault code present
Fault Code Data Type: uint16 in Active Shutdown Fault
Row 10 table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401012 Active Read Only Multiplier: 1 First entry of Active warning PS060X
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 1 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401013 Active Read Only Multiplier: 1 Second entry of Active PS060X
Warning Fault Size (Bits): 16 warning fault code present in
Code Row 2 Data Type: uint16 Active warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401014 Active Read Only Multiplier: 1 Third entry of Active warning PS060X
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 3 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535

Copyright © 2023 Cummins Inc. 952 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


401015 Active Read Only Multiplier: 1 Fourth entry of Active warning PS060X
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 4 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401016 Active Read Only Multiplier: 1 Fifth entry of Active warning PS060X
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 5 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401017 Active Read Only Multiplier: 1 Sixth entry of Active warning PS060X
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 6 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401018 Active Read Only Multiplier: 1 Seventh entry of Active PS060X
Warning Fault Size (Bits): 16 warning fault code present in
Code Row 7 Data Type: uint16 Active warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401019 Active Read Only Multiplier: 1 Eighth entry of Active warning PS060X
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 8 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401020 Active Read Only Multiplier: 1 Ninth entry of Active warning PS060X
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 9 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401021 Active Read Only Multiplier: 1 Tenth entry of Active warning PS060X
Warning Fault Size (Bits): 16 fault code present in Active
Code Row 10 Data Type: uint16 warning Fault table
Unit: NA
Lower Limit: 0
Upper Limit: 65535

A029X159 (Issue 31) 953 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


401022 Auto Mains Guest 0: Disable Used to enable or disable the PS060X
Failure 1: Enable Auto Mains Failure Feature
Enable
401023 Load Transfer Guest 0: GTEC Provides the type of Load PS060X
Switch Type 1: Contact Pair Transfer Switch

401024 AMF State Read Only 0: AMF Not Available Provides the state in which PS060X
1: Transfer Retransfer Off the Auto Mains Failure is
2: Utility Pickup currently present
3: Utility Dropout
4: Genset Starting
5: Transfer Start
6: Utility CB Opened
7: Genset CB Closed
8: Transfer Complete
9: Retransfer Start
10: Genset CB Opened
11: Utility CB Closed
12: Retransfer Complete
13: Transfer Fail
14: Retransfer Fail
401025 Transfer Read Only 0: Not Available Provides value of Transfer PS060X
Switch 1: At Utility switch feedback status
Feedback 2: At Genset
Status
3: Unknown Open
4: Unknown Closed
402355 Time Delay Guest Multiplier: 0.1 Provides the value of Time PS060X
Engine Start Size (Bits): 16 Delay Engine Start (TDES)
Data Type: uint16
Unit: sec
Lower Limit: 0
Upper Limit: 3600
402356 Time Delay Guest Multiplier: 0.1 Provides the value of Time PS060X
Engine Size (Bits): 16 Delay Engine Cooldown
Cooldown Data Type: uint16 (TDEC)
Unit: sec
Lower Limit: 0
Upper Limit: 3600
402357 AT DEF Tank Read Only Multiplier: 0.1 After Treatment Diesel PS060X
Level Size (Bits): 16 Exhaust Fluid Tank Level
Data Type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 100

Copyright © 2023 Cummins Inc. 954 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


402358 AT DEF Read Only Multiplier: 0.1 After Treatment Diesel PS060X
Concentration Size (Bits): 16 Exhaust Fluid Concentration
Data Type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 100
402359 AT DEF Tank Read Only Multiplier: 1 After Treatment Diesel PS060X
Temperature Size (Bits): 16 Exhaust Fluid Tank
Data Type: int16 Temperature
Unit: degF
Lower Limit: 40
Upper Limit: 410
402360 Aftertreatmen Read Only Multiplier: 1 Temperature of engine PS060X
t SCR Size (Bits): 16 combustion by products
Catalyst Data Type: int16 leaving the SCR catalyst
outlet Gas exhaust in exhaust bank 1
Unit: degF
Temperature
Lower Limit: 459.4
Upper Limit: 3154.943
402361 AT 2 SCR Read Only Multiplier: 0.1 Temperature of engine PS060X
Catalyst Size (Bits): 16 combustion by products
Outlet Gas Data Type: int16 leaving the SCR catalyst
Temperature exhaust in exhaust bank 2
Unit: degF
Lower Limit: 459.4
Upper Limit: 3154.9
402362 AT 1 DEF Read Only Multiplier: 1 Quantity of diesel exhaust PS060X
Actual Dosing Size (Bits): 16 fluid injected in the
Quantity Data Type: uint16 aftertreatment 1 system
Unit: g/f
Lower Limit: 0
Upper Limit: 19277
402363 AT 2 DEF Read Only Multiplier: 1 Actual reducing agent PS060X
Actual Dosing Size (Bits): 16 quantity of SCR system
Quantity Data Type: uint16
Unit: g/f
Lower Limit: 0
Upper Limit: 19277
402365 Operator Read Only Multiplier: 1 Monitor point for Time to PS060X
Inducement Size (Bits): 16 Torque Derate Level 1
Time To Data Type: uint16
Torque
Unit: min
Derate Level
1 Lower Limit: 0
Upper Limit: 64255

A029X159 (Issue 31) 955 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


402366 Operator Read Only Multiplier: 1 Monitor point for Time to PS060X
Inducement Size (Bits): 16 Torque Derate Level 2
Time To Data Type: uint16
Torque
Unit: min
Derate Level
2 Lower Limit: 0
Upper Limit: 64255
402367 Operator Read Only Multiplier: 1 Monitor point for Time to Final PS060X
Inducement Size (Bits): 16 Inducement Action
Time To Final Data Type: uint16
Inducement
Unit: min
Action
Lower Limit: 0
Upper Limit: 64255
402368 AT 1 DEF Read Only 0: OFF Driver's warning indicator for PS060X
Tank 1 Low 1: On Solid diesel exhaust fluid (DEF)
Level 2: On Fast Blink tank low level
Indicator
3: Not Available
4: Network Failure
403000 Genset Technician Multiplier: 1 Nominal voltage for the PS060X
Nominal Size (Bits): 16 source
Voltage Data Type: uint16
Unit: V
Lower Limit: 1
Upper Limit: 45000
403001 System Operator 0: 50 Hz AC frequency of the power PS060X
Nominal 1: 60 Hz system
Frequency
403005 Charging Guest 0: Disable Used to disable the controller PS060X
Alternator 1: Enable related charging alternator
Enable functions
403006 Start Time Technician Multiplier: 1 Time delay before engine PS060X
Delay Size (Bits): 16 cranks after remote start
Data Type: uint16 status becomes active
Unit: sec
Lower Limit: 0
Upper Limit: 300
403007 Stop Time Technician Multiplier: 1 Time delay after which the PS060X
Delay Size (Bits): 16 engine initiation of
Data Type: uint16 cooldown/stop sequence.
Unit: sec
Lower Limit: 0
Upper Limit: 600

Copyright © 2023 Cummins Inc. 956 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


403008 Crank Guest Multiplier: 1 The trim provides number of PS060X
Attempts Size (Bits): 16 crank attempts for each
Data Type: uint16 genset start request
Unit: NA
Lower Limit: 1
Upper Limit: 7
403009 Cycle Crank Guest Multiplier: 1 Sets the time to engage the PS060X
Engage Time Size (Bits): 16 starter during a single crank
Data Type: uint16 attempt for cycle crank mode
Unit: sec
Lower Limit: 2
Upper Limit: 20
403010 Cycle Crank Guest Multiplier: 1 Sets the starter rest time PS060X
Rest Time Size (Bits): 16 between start attempts for
Data Type: uint16 cycle crank mode
Unit: sec
Lower Limit: 7
Upper Limit: 40
403011 Battleshort Guest 0: Disable Used to enable or disable the PS060X
Enable 1: Enable Battle short Feature.

403012 TB16-10 Guest 0: Not Connected Used to set the value of PS060X
Sensor 1: Diagnostic Input #1 TB16-10 Sensor Selection
Selection 2: Battle Short
403019 Electronic Read and 0: Disable Electronic Governor enable PS060X
Governor Write 1: Enable feature
Enable
403020 Initial Crank Read and Multiplier: 0.1 Electronic governing initial PS060X
Fueling Duty Write Size (Bits): 16 duty cycle setting
Cycle Data type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 100
403021 Initial Crank Read and Multiplier: 0.1 Time spent at Initial Crank PS060X
Fueling Write Size (Bits): 8 Fueling Command
Period Data Type: uint8
Unit: Sec
Lower Limit: 0
Upper Limit: 10

A029X159 (Issue 31) 957 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


403022 Crank Fueling Read and Multiplier: 0.1 Electronic Governing Start PS060X
Ramp Rate Write Size (Bits): 16 ramp duty cycle setting
Data Type: uint16
Unit: %/Sec
Lower Limit: 5
Upper Limit: 100
403023 Max Crank Read and Multiplier: 0.1 Electronic Governing PS060X
Fuel Duty Write Size (Bits): 16 Maximum duty cycle setting
Cycle Data Type: uint16
Unit: %
Lower Limit: 50
Upper Limit: 100
403024 Governor Read and Multiplier: 1 Electronic Governing Gain PS060X
Gain Adjust Write Size (Bits): 16 Setting
Data Type: uint16
Unit: %
Lower Limit: 5
Upper Limit: 1000
403025 GK2 Gain Read and Multiplier: 1 Electronic Governing K2 gain PS060X
Adjust Write Size (Bits): 16 setting
Data Type: uint16
Unit: %
Lower Limit: 5
Upper Limit: 1000
403026 Governor Read and Multiplier: 1 Electronic Governor Damping PS060X
Damping Write Size (Bits): 16 Adjustment
Effect Adjust Data Type: uint16
Unit: %
Lower Limit: 95
Upper Limit: 105
403027 Crank Exit Read and Multiplier: 0.1 Electronic Governing Crank PS060X
Fuel Duty Write Size (Bits): 16 Exit Fuel duty cycle setting
Cycle Data Type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 100
403028 Dither Factor Read and Multiplier: 0.01 Electronic Governing Dither PS060X
Write Size (Bits): 16 Factor setting
Data Type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 30

Copyright © 2023 Cummins Inc. 958 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


403029 Governor Read and Multiplier: 0.01 Electronic governing start PS060X
Ramp Time Write Size (Bits): 16 ramp time setting
Data Type: uint16
Unit: sec
Lower Limit: 0
Upper Limit: 30
403030 Governor Read and Multiplier: 1 Engine Speed at which the PS060X
Enable Write Size (Bits): 16 governor is enabled
Engine Data Type: uint16
Speed
Unit: r/min (rpm)
Lower Limit: 601
Upper Limit: 1400
403031 Minimum Read and Multiplier: 1 Setting for Electronic PS060X
Duty Cycle Write Size (Bits): 8 Governor minimum Duty
Data Type: uint8 Cycle
Unit: %
Lower Limit: 0
Upper Limit: 100
403032 Maximum Read and Multiplier: 1 Setting for Electronic PS060X
Duty Cycle Write Size (Bits): 8 Governor maximum Duty
Data Type: uint8 Cycle
Unit: %
Lower Limit: 0
Upper Limit: 100
403033 Genset Model Guest Multiplier: 1 Number identifying the model PS060X
Number Size (Bits): 168 of this generator set
Data Type: string20
Unit: NA
Lower Limit: 0
Upper Limit: 9999999999
403049 Genset Serial Guest Multiplier: 1 Serial number for identifying PS060X
Number Size (Bits): 168 this generator set
Data Type: string20
Unit: NA
Lower Limit: 0
Upper Limit: 9999999999
403065 Customer Guest 0: None The fault response for PS060X
Input #1 Fault 1: Warning Customer Input #1
Response 2: Shutdown
403066 Customer Guest 0: None The fault response for PS060X
Input #2 Fault 1: Warning Customer Input #2
Response 2: Shutdown

A029X159 (Issue 31) 959 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


403067 Diagnostic Read Only 0: IsFalse The digital output command PS060X
Output #1 1: IsTrue to the Customer Output #1
Output Status
403068 Diagnostic Read Only 0: IsFalse The digital output command PS060X
Output #2 1: IsTrue to the Customer Output #2
Output Status
403309 Over Guest 0: Disable Enables overfrequency PS060X
Frequency 1: Enable diagnostic
Shutdown
Enable
403344 Clock Day Technician Multiplier: 1 Provides the value of Clock PS060X
Size (Bits): 8 Day
Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 31
403345 Clock Hour Technician Multiplier: 1 Provides the value of Clock PS060X
Size (Bits): 8 Hour
Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 23
403346 Clock Minute Technician Multiplier: 1 Provides the value of Clock PS060X
Size (Bits): 8 Minute
Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 59
403347 Clock Mode Technician 0: Normal Set the value of Clock Mode PS060X
1: Set Clock
2: Save Clock
403348 Clock Month Technician Multiplier: 1 Provides the value of Clock PS060X
Size (Bits): 8 Month
Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 12
403349 Clock Second Technician Multiplier: 1 Provides the value of Clock PS060X
Size (Bits): 8 Second
Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 59

Copyright © 2023 Cummins Inc. 960 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


403350 Clock Year Technician Multiplier: 1 Provides the value of Clock PS060X
Size (Bits): 8 Year
Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 99
403351 Daylight Technician Multiplier: 1 Provides the value of Daylight PS060X
Saving End Size (Bits): 8 Saving End Hour
Hour Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 23
403352 Daylight Technician Multiplier: 1 Provides the value of Daylight PS060X
Saving End Size (Bits): 8 Saving End Month
Month Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 12
403353 Daylight Technician 0: Invalid Provides the value of Daylight PS060X
Saving End 1: First Occurrence Saving End Week
Week 2: Second Occurrence
3: Third Occurrence
4: Fourth Occurrence
5: Last Occurrence
403354 Daylight Technician 0: Sunday Provides the value of Daylight PS060X
Saving Start 1: Monday Saving Start Day
Day 2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
403355 Daylight Technician Multiplier: 1 Provides the value of Daylight PS060X
Saving Start Size (Bits): 8 Saving Start Hour
Hour Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 23
403356 Daylight Technician Multiplier: 1 Provides the value of Daylight PS060X
Saving Start Size (Bits): 8 Saving Start Month
Month Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 12

A029X159 (Issue 31) 961 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


403357 Daylight Technician 0: Invalid Provides the value of Daylight PS060X
Saving Start 1: First Occurrence Saving Start Week
Week 2: Second Occurrence
3: Third Occurrence
4: Fourth Occurrence
5: Last Occurrence
403358 Daylight Technician Multiplier: 1 Value of Daylight Saving PS060X
Saving Time Size (Bits): 8 Time Adjustment
Adjustment Data Type: uint8
Unit: min
Lower Limit: 0
Upper Limit: 120
403359 Daylight Technician 0: Disable Used to Enable or Disable the PS060X
Saving Time 1: Enable value of Daylight Saving Time
Enable
403376 Scheduler Guest Multiplier: 1 Used to adjust the length in PS060X
Program Size (Bits): 8 minutes for the selected
Duration Data Type: uint8 program.
Minute
Unit: min
Lower Limit: 1
Upper Limit: 60
403377 Scheduler Guest 0: Disable Used to enable or disable the PS060X
Program 1: Enable selected program
Enable
403378 Scheduler Guest 0: Weekly Used to adjust the repeat PS060X
Program 1: Bi-Monthly interval for the selected
Repeat 2: Monthly program
Interval
3: Quarterly
4: Semi-Annualy
403380 Scheduler Guest 0: Sunday Used to adjust the start day PS060X
Program Start 1: Monday of the week for the selected
Day 2: Tuesday program
3: Wednesday
4: Thursday
5: Friday
6: Saturday
403381 Scheduler Guest Multiplier: 1 Used to adjust the start hour PS060X
Program Start Size (Bits): 8 for the selected program
Hour Data Type: uint8
Unit: Hours
Lower Limit: 0
Upper Limit: 23

Copyright © 2023 Cummins Inc. 962 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


403382 Scheduler Guest Multiplier: 1 Used to adjust the start PS060X
Program Start Size (Bits): 8 minute for the selected
Minute Data Type: uint8 program
Unit: min
Lower Limit: 0
Upper Limit: 59
403383 Daylight Technician 0: Sunday Provides the value of Daylight PS060X
Saving End 1: Monday Saving End Day
Day 2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
403511 Low Battery Read Only Multiplier: 0.1 Holds low battery voltage PS060X
Voltage Size (Bits): 16 fault threshold value based
Threshold Data Type: uint16 upon 12V/24V
Unit: V
Lower Limit: 0
Upper Limit: 99
403550 Weak Battery Read Only Multiplier: 0.1 Holds weak battery voltage PS060X
Voltage Size (Bits): 16 fault threshold value based
Threshold Data Type: uint16 upon 12V/24V
Unit: V
Lower Limit: 0
Upper Limit: 99
403551 Weak Battery Guest Multiplier: 1 The time delay until a weak PS060X
Voltage Set Size (Bits): 8 battery condition is reported
Time Data Type: uint8 as a fault
Unit: sec
Lower Limit: 1
Upper Limit: 5
403562 Customer Read Only 0: IsFalse The digital status of Customer PS060X
Input #3 1: IsTrue Input #3

403599 Customer Read Only 0: IsFalse The digital status of Customer PS060X
Input #2 1: IsTrue Input #2

403645 LCL Technician 0: None Sets low coolant level fault PS060X
Detection 1: Warning response
Response 2: Shutdown

A029X159 (Issue 31) 963 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


403647 Low Coolant Guest Multiplier: 1 Sets time to set the low PS060X
Temperature Size (Bits): 8 coolant temperature fault
Warning Set Data Type: uint8
Time
Unit: min
Lower Limit: 0
Upper Limit: 30
403648 Low Coolant Guest Multiplier: 1 Sets threshold for the low PS060X
Temperature Size (Bits): 16 coolant temperature fault
Warning Data Type: uint16 warning
Threshold
Unit: degF
Lower Limit: -20
Upper Limit: 130
403651 High Battery Guest Multiplier: 0.1 Sets 12V high battery voltage PS060X
Voltage Size (Bits): 16 fault threshold
Threshold Data Type: uint16
12V
Unit: V
Lower Limit: 14
Upper Limit: 17
403652 Low Battery Guest Multiplier: 0.1 Sets 12V low battery voltage PS060X
Voltage Size (Bits): 16 fault threshold for generator
Running Data Type: uint16 set operation while in rated
Threshold mode
Unit: V
12V
Lower Limit: 12
Upper Limit: 16
403653 Low Battery Guest Multiplier: 0.1 Sets 12V low battery voltage PS060X
Voltage Size (Bits): 8 fault threshold for generator
Stopped Data Type: uint8 set operation in all modes
Threshold except rated
Unit: V
12V
Lower Limit: 10
Upper Limit: 13
403654 Weak Battery Guest Multiplier: 0.1 Sets 12V weak battery PS060X
Voltage Size (Bits): 16 voltage fault threshold
Threshold Data Type: uint16
12V
Unit: V
Lower Limit: 6
Upper Limit: 10
403655 High Battery Guest Multiplier: 0.1 Sets 24V high battery voltage PS060X
Voltage Size (Bits): 16 fault threshold
Threshold Data Type: uint16
24V
Unit: V
Lower Limit: 28
Upper Limit: 34

Copyright © 2023 Cummins Inc. 964 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


403656 Low Battery Guest Multiplier: 0.1 Sets 24V low battery voltage PS060X
Voltage Size (Bits): 16 fault threshold for generator
Running Data Type: uint16 set operation while in rated
Threshold mode
Unit: V
24V
Lower Limit: 24
Upper Limit: 28
403657 Low Battery Guest Multiplier: 0.1 Sets 24V low battery voltage PS060X
Voltage Size (Bits): 16 fault threshold for generator
Stopped Data Type: uint16 set operation in all modes
Threshold except rated
Unit: V
24V
Lower Limit: 22
Upper Limit: 26
403658 Weak Battery Guest Multiplier: 0.1 Sets 24V weak battery PS060X
Voltage Size (Bits): 16 voltage fault threshold
Threshold Data Type: uint16
24V
Unit: V
Lower Limit: 10
Upper Limit: 16
403662 Charging Guest Multiplier: 1 Sets the time delay for the PS060X
Alternator Set Size (Bits): 16 charging alt failure fault
Time Data Type: uint16
Unit: sec
Lower Limit: 2
Upper Limit: 300
403676 High Battery Read Only Multiplier: 0.1 Holds high battery voltage PS060X
Voltage Size (Bits): 16 fault threshold value based
Threshold Data Type: uint16 upon 12V/24V
Unit: V
Lower Limit: 0
Upper Limit: 99
403688 Low Battery Guest Multiplier: 1 The time delay until a low PS060X
Voltage Set Size (Bits): 8 battery voltage condition is
Time Data Type: uint8 reported as a fault
Unit: sec
Lower Limit: 2
Upper Limit: 60
403693 Nominal Guest 0: Twelve Volt Selects the nominal battery PS060X
Battery 1: TwentyFour Volt operating voltage
Voltage

A029X159 (Issue 31) 965 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


403745 Fuel Level Read Only Multiplier: 1 Measured fuel level value in PS060X
Percent Offset: 0 percent
Size (Bits): 16
Sign: U
Unit: Percent
Lower Limit: 0
Upper Limit: 65535
403746 Fuel Level Read Only Multiplier: 1 Measured fuel level value in PS060X
Sensor Offset: 0 litre
(A052T244) Size (Bits): 16
Sign: U
Unit: Litre
Lower Limit: 0
Upper Limit: 9999
403748 ATS Read Only Multiplier: 1 Displays 16-bit number to PS060X
Extended Offset: 0 represent the status of the
Annunciation Size (Bits): 16 NFPA 110 fault register for
ATS
Sign: U
Unit: Percent
Lower Limit: 0
Upper Limit: 65535
403778 Exercise Read Only 0: Inactive Indicates state of an exercise PS060X
Scheduler 1: Active scheduler
State 2: Abort
403793 Customer Read Only 0: IsFalse The digital status of Customer PS060X
Input #1 1: IsTrue Input #1

403821 Time Delay Operator Multiplier: 0.1 Provides the value of Time PS060X
Programmed Size (Bits): 16 Delay Programmed Transition
Transition Data Type: uint16 (TDPT)
Unit: sec
Lower Limit: 0
Upper Limit: 600
403822 Time Delay Guest Multiplier: 0.1 Provides the Value of Time PS060X
Emergency to Size (Bits): 16 Delay Emergency to Normal
Normal Data Type: uint16 (TDEN)
Unit: sec
Lower Limit: 0
Upper Limit: 1800

Copyright © 2023 Cummins Inc. 966 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


403825 Time Delay Guest Multiplier: 1 Provides the value of Time PS060X
Normal to Size (Bits): 16 Delay Normal to Emergency
Emergency Data Type: uint16 (TDNE)
Unit: sec
Lower Limit: 0
Upper Limit: 300
403828 Maintenance Guest Multiplier: 1 Sets real time clock Date for PS060X
RTC Date Size (Bits): 8 Maintenance Diagnostic
Interval Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 31
403829 Maintenance Guest Multiplier: 1 Sets real time clock month for PS060X
RTC Month Size (Bits): 8 Maintenance Diagnostic
Interval Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 12
403830 Maintenance Guest Multiplier: 1 Sets real time clock year for PS060X
RTC Year Size (Bits): 8 Maintenance Diagnostic
Interval Data Type: uint8
Unit: NA
Lower Limit: 0
Upper Limit: 99
403831 Maintenance Read Only Multiplier: 0.01 Displays Maintenance PS060X
Due WRT Size (Bits): 32 required with respect to
ERT Data Type: uint32 engine running hours
Unit: hours
Lower Limit: 0
Upper Limit: 119304.65
403952 Speed/Frequ Guest Multiplier: 0.1 Sets delay time for generating PS060X
ency Conflict Size (Bits): 16 the Speed/Frequency
Shutdown Set Data Type: uint16 mismatch fault
Time
Unit: sec
Lower Limit: 0.5
Upper Limit: 10
403953 Speed/Frequ Guest Multiplier: 0.1 Sets the threshold for PS060X
ency Conflict Size (Bits): 16 generating the
Shutdown Data Type: uint16 Speed/Frequency mismatch
Threshold fault
Unit: Hz
Lower Limit: 0.5
Upper Limit: 20

A029X159 (Issue 31) 967 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


405999 Unrecognized Read Only 0: All Pairs Recognized DM1 recognition status PS060X
SPN/FMI 1: Pair Not Recognized
Status
406109 Engine Read Only 0: Engine Stopped Current state or mode of PS060X
Operating 1: Prestart operation by the engine.
State 2: Starting Added Network Failure as
enum option
3: Warmup
4: Running
5: Cooldown
6: Engine Stopping
7: Post Run
8: Out of Range
9: N/A
10: Network Failure
406124 Coolant Read Only Multiplier: 0.1 Monitor point for Coolant PS060X
Pressure Size (Bits): 16 Pressure
Data Type: int16
Unit: psi
Lower Limit: 0
Upper Limit: 100
408025 TB15 Modbus Technician Multiplier: 1 This trim allows for the PS060X
Inactivity Size (Bits): 8 configuring of the Modbus
Interval Data Type: uint8 failure time delay for this port.
Unit: sec
Lower Limit: 1
Upper Limit: 60
408028 TB15 Modbus Technician Multiplier: 1 This ports node address is PS060X
Node Size (Bits): 8 configurable from 1 to 247.
Address Data Type: uint8
Unit: NA
Lower Limit: 1
Upper Limit: 247
408029 TB15 Modbus Administrator 0: Guest Used to select the Access PS060X
Access Level 1: Operator Level of this port
2: Technician
408031 TB15 UART Technician 0: MON Used to select the active PS060X
Protocol 1: Modbus protocol on this port
Selection
408033 TB15 Modbus Technician 0: None (1 Stop) This trim allows configuring of PS060X
Parity Stop 1: None (2 Stop) the parity and stop bits for
Bit Selection 2: Even (1 Stop) this port.
3: Odd (1 Stop)

Copyright © 2023 Cummins Inc. 968 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


408035 TB15 Modbus Read Only 0: Not Available Updates TB15 ports Modbus PS060X
Activity 1: Inactive communication activity
Status 2: Bus Active
3: Local Active
408038 TB15 Modbus Technician 0: 2400 Sets the TB15 ports' baud PS060X
Baud Rate 1: 4800 rate
Selection 2: 9600
3: 19200
4: 28800
5: 38400
6: 57600
7: 115200
408039 Save Trims Operator 0: IsFalse Setting this parameter to PS060X
1: IsTrue IsTrue will trigger a save of all
non-volatile trims on the
entire device.
408041 TB15 Modbus Technician 0: Inactive Setting this to active clears all PS060X
Clear 1: Active the Modbus status counters
Counters for TB15 port.
408047 Reset Fuel Technician 0: Inactive Reset trip fuel consumption PS060X
Consumption 1: Active command

410001 Genset Read Only Multiplier: 0.1 Average power factor of all PS060X
Average Size (Bits): 32 line power factors
Power Factor Data Type: float32
Unit:
Lower Limit: –1
Upper Limit: 1
410007 Genset L1 Read Only Multiplier: 0.1 Active energy exported PS060X
Exported Size (Bits): 32 by Line 1
kWh Data Type: float32
Unit: kWh
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38
410009 Genset L1 Read Only Multiplier: 0.1 Reactive energy imported PS060X
Imported Size (Bits): 32 by Line 1
kVarh Data Type: float32
Unit: kVarh
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38

A029X159 (Issue 31) 969 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

Addr Parameter Access Specifications Description Control


410015 Genset L1 Read Only Multiplier: 0.1 Generator set L1 kVAh PS060X
kVah Size (Bits): 32 accumulation
Data Type: float32
Unit: kVah
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38
410021 Genset L1 Read Only Multiplier: 0.1 Generator set L1 Power PS060X
Power Factor Size (Bits): 32 Factor
Data Type: float32
Unit:
Lower Limit: –1
Upper Limit: 1
410031 Genset L2 Read Only Multiplier: 0.1 Active energy exported PS060X
Exported Size (Bits): 32 by Line 2
kWh Data Type: float32
Unit: kWh
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38
410033 Genset L2 Read Only Multiplier: 0.1 Reactive energy imported PS060X
Imported Size (Bits): 32 by Line 2
kVarh Data Type: float32
Unit: kVarh
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38
410039 Genset L2 Read Only Multiplier: 0.1 Generator set L2 kVAh PS060X
kVah Size (Bits): 32 accumulation
Data Type: float32
Unit: kVah
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38
410045 Genset L2 Read Only Multiplier: 0.1 Generator set L2 Power PS060X
Power Factor Size (Bits): 32 Factor
Data Type: float32
Unit:
Lower Limit: –1
Upper Limit: 1
410055 Genset L3 Read Only Multiplier: 0.1 Active energy exported PS060X
Exported Size (Bits): 32 by Line 3
kWh Data Type: float32
Unit: kWh
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38

Copyright © 2023 Cummins Inc. 970 A029X159 (Issue 31)


8-2023 16. PS060X Modbus Register Map

Addr Parameter Access Specifications Description Control


410057 Genset L3 Read Only Multiplier: 0.1 Reactive energy imported PS060X
Imported Size (Bits): 32 by Line 3
kVarh Data Type: float32
Unit: kVarh
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38
410063 Genset L3 Read Only Multiplier: 0.1 Generator set L3 kVAh PS060X
kVah Size (Bits): 32 accumulation
Data Type: float32
Unit: kVah
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38
410069 Genset L3 Read Only Multiplier: 0.1 Generator set L3 Power PS060X
Power Factor Size (Bits): 32 Factor
Data Type: float32
Unit:
Lower Limit: –1
Upper Limit: 1
410082 Genset Total Read Only Multiplier: 0.1 Total Active energy exported PS060X
Exported Size (Bits): 32 by Genset
kWh Data Type: float32
Unit: KWh
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38
410084 Genset Total Read Only Multiplier: 0.1 Total reactive energy PS060X
Imported Size (Bits): 32 imported by Genset
kVarh Data Type: float32
Unit: kVarh
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38
410090 Genset Total Read Only Multiplier: 0.1 Generator set total kVAh PS060X
kVah Size (Bits): 32 accumulation
Data Type: float32
Unit: kVah
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38

A029X159 (Issue 31) 971 Copyright © 2023 Cummins Inc.


16. PS060X Modbus Register Map 8-2023

This page is intentionally blank.

Copyright © 2023 Cummins Inc. 972 A029X159 (Issue 31)


17 PowerBloc
17.1 PLC Modbus Register Bitmap
TABLE 55. PLC MODBUS REGISTER BITMAP

Address Parameter Access Specifications Description Control


40010 G_Controller_Switch_Po Read Only 0: Off Current position of the
sition 1: Auto generator switch panel
2: Manual Off–Run–Auto switch as
seen by the generator set
control
40011 G_Gen_RunSeq_State Read Only 0: Stop The current state of the
1: Time Delay to start generator set
2: Warm up at idle
3: Rated Freq and
Voltage
4: Cooldown/Stop
Delay
5: Cooldown at Idle
6: Rated to Idle
Transition
40014 G_Percent_kW Read Only Multiplier: 0.01 Monitors the total
Offset: 0 generator set standby
Size (bits): 16 KW percentage output
Sign: S
Units: %
Lower Limit:
Upper Limit:
40016 G_NFPA_110(1) Read Only Multiplier: 1.0 16–bit number to
Offset: 0 represent the status of
Size (bits): 16 the NFPA 110 logical.
See Table 56 on page
Sign: U
997.
Units: NA
Lower Limit:
Upper Limit:
40017 G_NFPA_110(2) Read Only Multiplier: 1.0 16–bit number to
Offset: 0 represent the status of
Size (bits): 16 the NFPA 110 logical.
See Table 57 on page
Sign: U
998.
Units: NA
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 973 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


40018 G_L1N_Volt Read Only Multiplier: 1 Generator set L1–N
Offset: 0 voltage
Size (bits): 16
Sign: U
Units: VAC
Lower Limit:
Upper Limit:
40019 G_L2N_Volt Read Only Multiplier: 1 Generator set L2–N
Offset: 0 voltage
Size (bits): 16
Sign: U
Units: VAC
Lower Limit:
Upper Limit:
40020 G_L3N_Volt Read Only Multiplier: 1 Generator set L3–N
Offset: 0 voltage
Size (bits): 16
Sign: U
Units: VAC
Lower Limit:
Upper Limit:
40021 GN_LN_Avg_Volt Read Only Multiplier: 1 Generator set Line to
Offset: 0 Neutral average voltage
Size (bits): 16
Sign: U
Units: VAC
Upper Limit: NA
Default: 0
40022 G_L1L2_Volt Read Only Multiplier: 1 Generator set L1–L2
Offset: 0 voltage
Size (bits): 16
Sign: U
Units: VAC
Lower Limit:
Upper Limit:
40023 G_L2L3_Volt Read Only Multiplier: 1 Generator set L2–L3
Offset: 0 voltage
Size (bits): 16
Sign: U
Units: VAC
Lower Limit:
Upper Limit:

Copyright © 2023 Cummins Inc. 974 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


40024 G_L3L1_Volt Read Only Multiplier: 1 Generator set L3–L1
Offset: 0 voltage
Size (bits): 16
Sign: U
Units: VAC
Lower Limit:
Upper Limit:
40025 GN_LL_Avg_Volt Read Only Multiplier: 1 Generator set Line to
Offset: 0 Line average voltage
Size (bits): 16
Sign: U
Units: VAC
Lower Limit:
Upper Limit:
40026 G_L1_Amp Read Only Multiplier: 1 Monitors the generator
Offset: 0 set L1 current value
Size (bits): 16
Sign: U
Units: Amps
Lower Limit:
Upper Limit:
40027 G_L2_Amp Read Only Multiplier: 1 Generator set L2 current
Offset: 0
Size (bits): 16
Sign: U
Units: Amps
Lower Limit:
Upper Limit:
40028 G_L3_Amp Read Only Multiplier: 1 Generator set L3 current
Offset: 0
Size (bits): 16
Sign: U
Units: Amps
Lower Limit:
Upper Limit:
40029 G_Avg_Current Read Only Multiplier: 1 Generator set average
Offset: 0 current
Size (bits): 16
Sign: U
Units: Amps
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 975 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


40030 G_Current_N Read Only Multiplier: 1 Generator set neutral
Offset: 0 current
Size (bits): 16
Sign: U
Units: VAC
Lower Limit:
Upper Limit:
40031 G_L1_kW Read Only Multiplier: 1 Generator set L1 kW
Offset: 0
Size (bits): 16
Sign: S
Units: kW
Lower Limit: –32768
Upper Limit: 32762
40032 G_L2_kW Read Only Multiplier: 1 Generator set L2 kW
Offset: 0
Size (bits): 16
Sign: S
Units: kW
Lower Limit: –32768
Upper Limit: 32762
40033 G_L3_kW Read Only Multiplier: 1 Generator set L3 kW
Offset: 0
Size (bits): 16
Sign: S
Units: kW
Lower Limit: –32768
Upper Limit: 32762
40034 G_Total_kW Read Only Multiplier: 1 Generator set total kW
Offset: 0
Size (bits): 16
Sign: S
Units: kW
Lower Limit:
Upper Limit:
40035 G_L1_kVAR Read Only Multiplier: 1 Generator set L1 kVAR
Offset: 0
Size (bits): 16
Sign: U
Units: kVAR
Lower Limit:
Upper Limit:

Copyright © 2023 Cummins Inc. 976 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


40036 G_L2_kVAR Read Only Multiplier: 1 Generator set L2 kVAR
Offset: 0
Size (bits): 16
Sign: U
Units: kVAR
Lower Limit:
Upper Limit:
40037 G_L3_kVAR Read Only Multiplier: 1 Generator set L3 kVAR
Offset: 0
Size (bits): 16
Sign: U
Units: kVAR
Lower Limit:
Upper Limit:
40038 G_Total_kVAR Read Only Multiplier: 1 Generator set total kVAR
Offset: 0
Size (Bits): 16
Sign: U
Units: kVAR
Lower Limit:
Upper Limit:
40039 G_Total_PF Read Only Multiplier: 0.01 Generator set total power
Offset: 0 factor (L1+L2+L3)
Size (bits): 8
Sign: S
Units: PF
Lower Limit:
Upper Limit:
40040 G_L1_kVA Read Only Multiplier: 1 Generator set L1 kVA
Offset: 0
Size (bits): 16
Sign: U
Units: kVA
Lower Limit:
Upper Limit:
40041 G_L2_kVA Read Only Multiplier: 1 Generator set L2 kVA
Offset: 0
Size (bits): 16
Sign: U
Units: kVA
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 977 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


40042 G_L3_kVA Read Only Multiplier: 1 Generator set L3 kVA
Offset: 0
Size (bits): 16
Sign: U
Units: kVA
Lower Limit:
Upper Limit:
40043 G_Total_kVA Read Only Multiplier: 1 Generator set total kVA
Offset: 0
Size (bits): 16
Sign: U
Units: kVA
Lower Limit:
Upper Limit:
40044 G_Frequency Read Only Multiplier: 1 Generator set Frequency
Offset: 0 OP
Size (bits): 16
Sign: U
Units: Hz
Lower Limit: NA
Upper Limit: NA
40046–40047 G_Neg_kWh Read Only Multiplier: 1 Generator set total
Offset: 0 negative kWh
Size (bits): 32 accumulation
Sign: U
Units: kWh
Lower Limit:
Upper Limit:
40048–40049 G_Pos_kWh Read Only Multiplier: 1 Generator set total
Offset: 0 positive kWh
Size (Bits): 32 accumulation
Sign: U
Units: kWh
Lower Limit:
Upper Limit:
4294967290

Copyright © 2023 Cummins Inc. 978 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


40050–40051 G_Tot_kWh Read Only Multiplier: 1 Generator set total net
Offset: 0 kWh accumulation
Size (bits): 32
Sign: S
Units: kWh
Lower Limit:
–2147483648
Upper Limit:
2147483643
40052–40053 G_Neg_kVARh Read Only Multiplier: 1 Generator set total
Offset: 0 negative kVARh
Size (bits): 32 accumulation
Sign: U
Units: kVARh
Lower Limit:
Upper Limit:
40054–40055 G_Pos_kVAh Read Only Multiplier: 1 Generator set total
Offset: 0 positive kVARh
Size (bits): 16 accumulation
Sign: U
Units: kVARh
Lower Limit:
Upper Limit:
4294967290
40056–40057 G_kVARh Read Only Multiplier: 1 Generator set total net
Offset: 0 kVARh accumulation
Size (bits): 16
Sign: U
Units: kVARh
Lower Limit:
–2147483648
Upper Limit:
2147483643
40061 G_Battery_Volt Read Only Multiplier: 1 Battery voltage value
Offset: 0
Size (bits): 16
Sign: U
Units: V
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 979 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


40062 G_Oil_Pre Read Only Multiplier: 1 Monitor point for the Oil
Offset: 0 Pressure
Size (bits): 16
Sign: U
Units: kPA
Lower Limit:
Upper Limit:
40063 G_Oil_Temp Read Only Multiplier: 0.1 Monitor point for the Oil
Offset: 0 Temperature
Size (bits): 16
Sign: S
Units: °F
Lower Limit:
Upper Limit:
40064 G_Coolant_Temp Read Only Multiplier: 0.1 Monitor point for the
Offset: 0 Coolant Temperature
Size (bits): 16
Sign: S
Units: °C
Lower Limit:
Upper Limit:
40065 G_IMT_Temp Read Only Multiplier: 0.1 To monitor Intake
Offset: 0 Manifold Temperature 1
Size (bits): 16
Sign: S
Units: °F
Lower Limit: –40
Upper Limit: 410
40066 G_Fuel_Temp Read Only Multiplier: 0.1 Monitor point for Fuel
Offset: 0 Temperature
Size (bits): 16
Sign: S
Units: °F
Lower Limit: –40
Upper Limit: 410
40067 G_Fuel_Rate Read Only Multiplier: 0.05 Monitor point for the Fuel
Offset: 0 Rate
Size (bits): 16
Sign: S
Units: gal/hr
Lower Limit:
Upper Limit:

Copyright © 2023 Cummins Inc. 980 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


40068 G_Engine_Speed Read Only Multiplier: 1 Monitor point for the
Offset: 0 Average Engine Speed
Size (bits): 16
Sign: U
Units: RPM
Lower Limit:
Upper Limit:
40069 G_Tot_StAmpOP Read Only Multiplier: 1 Total number of start
Offset: 0 attempts
Size (bits): 16
Sign: U
Units: NAr
Lower Limit:
Upper Limit: 65535
40070–40071 G_Eng_Runtime Read Only Multiplier: 0.1 Total engine run time
Offset: 0
Size (bits): 32
Sign: U
Units: seconds
Lower Limit:
Upper Limit:
40072–40073 G_Tot_Fuel_Consp Read Only Multiplier: 0.1 Total fuel consumption
Offset: 0 since start of engine
Size (bits): 32
Sign: U
Units: gallons
Lower Limit:
Upper Limit:
40074–40075 G_Tot_num_Runs Read Only Multiplier: 1 Total number of
Offset: 0 generator set runs
Size (bits): 32
Sign: U
Units:
Lower Limit:
Upper Limit:
4294967295
40125 G_Utility_Volt Read Only Multiplier: 1 Utility Line to Line
Offset: 0 average voltage
Size (bits): 16
Sign: U
Units: VAC
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 981 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


40165 G_GenBus_LL_Avg_Volt Read Only Multiplier: 1 Generator set Bus Line to
Offset: 0 Line average voltage
Size (bits): 16
Sign: U
Units: VAC
Lower Limit:
Upper Limit:
40230 G_Bosst_Pre Read Only Multiplier: 0.1 Monitor point for Boost
Offset: 0 Absolute Pressure
Size (bits): 16
Sign: U
Units: psi
Lower Limit:
Upper Limit:
40232 G_Crankcase_Pre Read Only Multiplier: 0.1 Monitor point for
Offset: 0 Crankcase Pressure
Size (bits): 16
Sign: S
Units: psi
Lower Limit:
Upper Limit:
40242 G_Aftercooler_Temp Read Only Multiplier: 0.1 Monitor point for
Offset: 0 Aftercooler Temperature
Size (bits): 16
Sign: S
Units: °F
Lower Limit: –40
Upper Limit: 410
Default: NA
40243 G_ECM_Temp Read Only Multiplier: 0.1 Internal temperature of
Offset: 0 the engine electronic
Size (bits): 16 control module 1
Sign: S
Units: °F
Lower Limit: NA
Upper Limit: NA
Default: NA
40264 G_Eng_PercentTor Read Only Multiplier: 1 Monitor point for percent
Offset: 0 engine torque output and
Size (bits): 16 governor percent duty
cycle output when used
Sign: S
with the HM ECM
Units: %
Lower Limit: –40
Upper Limit: 410

Copyright © 2023 Cummins Inc. 982 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


40282 G_Eng_WIF Read Only 0: No Water in Fuel Indication
1: Yes
40283 G_Controller_Mode Read Only 0: OFF The controller mode
1: Ready
2: Setup
3: Starting
4: Idle
5: Rated
6: Stop Normal
7: Stop Emergency
8: Factory Test
9: Wait to Power
Down
40290–40291 G_Controller_RunTime Read Only Multiplier: 1 Controller On time in
Offset: 0 seconds
Size (bits): 32
Sign: U
Units: seconds
Lower Limit: 0
Upper Limit:
4294967295 (136
years)
Default: NA
40501 G_Cfg_Input6_Low_Fuel Read Only 0: Inactive Status of low fuel level
_Shutdonw 1: Active shutdown event

40517 G_Leakage_Alr Read Only 0: Inactive Status of leakage warning


1: Active event

40563 G_Gen_Shutdown Read Only 0: Inactive Status of common


1: Active shutdown event

40565 G_Gen_Warning Read Only 0: Inactive Status of common


1: Active warning event

43220 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses


Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 983 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


43221 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43222 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43223 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43224 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43225 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43226 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:

Copyright © 2023 Cummins Inc. 984 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


43227 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43228 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43229 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43230 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43231 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43232 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 985 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


43233 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43234 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43235 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43236 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43237 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43238 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:

Copyright © 2023 Cummins Inc. 986 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


43239 G_Gen_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43220–43239 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set.
Units:
Lower Limit:
Upper Limit:
43260 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43261 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43262 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43263 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43264 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 987 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


43265 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43266 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43267 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43268 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43269 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43270 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:

Copyright © 2023 Cummins Inc. 988 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


43271 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43272 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43273 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43275 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43275 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43276 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 989 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


43277 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43278 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43279 G_Alt_SN Read Only Multiplier: 1 Modbus uses addresses
Offset: 0 43260–43279 for the 20
Size (bits): 16 characters of the serial
number of this generator
Sign: C
set alternator.
Units:
Lower Limit:
Upper Limit:
43281 G_HT_LCL_Warning Read Only 0: Inactive Indicates the Coolant low
1: Active level warning event

43562 G_Gen_CB_Pos Read Only 0: Open Indicates generator set


1: Closed breaker position
2: Not Available
43719 G_AltWind_Temp Read Only Multiplier: 1 Monitor point for the
Offset: 0 Alternator Temperature
Size (bits): 16
Sign: S
Units: °F
Lower Limit: –32767
Upper Limit: 32762
43740 G_AltBearing_Temp Read Only Multiplier: 1 Monitor point for the
Offset: 0 Drive End Bearing
Size (bits): 16 Temperature
Sign: S
Units: °F
Lower Limit: –32767
Upper Limit: 32762

Copyright © 2023 Cummins Inc. 990 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


43741 G_Exhaust_Temp Read Only Multiplier: 1 Monitor point for the
Offset: 0 Exhaust Stack
Size (bits): 16 Temperature
Sign: S
Units: °F
Lower Limit: –32767
Upper Limit: 32762
43793 G_Cfg_Input1_High_Fuel Read Only 0: Inactive Status of high fuel level
_Level_Warning 1: Active warning event

43794 G_Cfg_Input2_Low_Fuel Read Only 0: Inactive Status of low fuel level


_Level_Warning 1: Active warning event

43795 G_Cfg_Input13_PLC Read Only 0: Inactive Signal for


Shutdown 1: Active G_Cfg_Input13_PLC_Sh
utdown
46124 G_Coolant_Pre Read Only Multiplier: 0.1 Monitor point for the
Offset: 0 Coolant Pressure
Size (bits): 8
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA
46135 G_Intake_Pre Read Only Multiplier: 0.1 Intake Manifold Pressure
Offset: 0 1
Size (bits): 16
Sign: U
Units: psi
Lower Limit: NA
Upper Limit: NA
48001 StatusWord1 Read Only Multiplier: 1 16–bit number to
Offset: 0 represent the status of
Size (bits): 16 the PowerBloc IO. See
Table 58 on page 999.
Sign: U
Units:
Lower Limit:
Upper Limit:
48002 StatusWord2 Read Only Multiplier: 1 16–bit number to
Offset: 0 represent the status of
Size (bits): 16 the PowerBloc IO. See
Table 59 on page 999.
Sign: U
Units:
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 991 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


48003 StatusWord3 Read Only Multiplier: 1 16–bit number to
Offset: 0 represent the status of
Size (bits): 16 the PowerBloc IO. See
Table 60 on page 1000.
Sign: U
Units:
Lower Limit:
Upper Limit:
48004 AlarmWord1 Read Only Multiplier: 1 16–bit number to
Offset: 0 represent the status of
Size (bits): 16 the PowerBloc alarm
event. See Table 61 on
Sign: U
page 1001.
Units:
Lower Limit:
Upper Limit:
48005 AlarmWord2 Read Only Multiplier: 1 16–bit number to
Offset: 0 represent the status of
Size (bits): 16 the PowerBloc alarm
event. See Table 62 on
Sign: U
page 1001.
Units:
Lower Limit:
Upper Limit:
48006 AlarmWord3 Read Only Multiplier: 1 16–bit number to
Offset: 0 represent the status of
Size (bits): 16 the PowerBloc alarm
event. See Table 63 on
Sign: U
page 1002.
Units:
Lower Limit:
Upper Limit:
48008 AlarmWord4 Read Only Multiplier: 1 16–bit number to
Offset: 0 represent the status of
Size (bits): 16 the PowerBloc alarm
event. See Table 64 on
Sign: U
page 1002.
Units:
Lower Limit:
Upper Limit:
48129 ChargerFail Read Only 0: Inactive Indicates Charger Failure
1: Active Warning event

48130 ChargerLowVoltAlarm Read Only 0: Inactive Indicates Charger Low


1: Active Voltage Warning event

Copyright © 2023 Cummins Inc. 992 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


48101 C_Container_Temp_L Read Only Multiplier: 1 Monitor point for
Offset: 0 Container Temperature 1
Size (bits): 16
Sign: S
Units: °C
Lower Limit:
Upper Limit:
48102 C_Container_Hum_L Read Only Multiplier: 1 Monitor point for
Offset: 0 Container Humidity 1
Size (bits): 16
Sign: U
Units: %
Lower Limit:
Upper Limit:
48103 C_Container_Temp_R Read Only Multiplier: 1 Monitor point for
Offset: 0 Container Temperature 2
Size (bits): 16
Sign: S
Units: °C
Lower Limit:
Upper Limit:
48104 C_Container_Hum_R Read Only Multiplier: 1 Monitor point for
Offset: 0 Container Humidity 2
Size (bits): 16
Sign: U
Units: %
Lower Limit:
Upper Limit:
48105 C_AuxAlt_Volt_A Read Only Multiplier: 1 Monitor point for Aux
Offset: 0 Alternator Line to neutral
Size (bits): 16 voltage A
Sign: U
Units: Volt
Lower Limit:
Upper Limit:
48106 C_AuxAlt_Volt_B Read Only Multiplier: 1 Monitor point for Aux
Offset: 0 Alternator Line to neutral
Size (bits): 16 voltage B
Sign: U
Units: Volt
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 993 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


48107 C_AuxAlt_Volt_C Read Only Multiplier: 1 Monitor point for Aux
Offset: 0 Alternator Line to neutral
Size (Bits): 16 voltage C
Sign: U
Units: Volt
Lower Limit:
Upper Limit:
48108 C_AuxAlt_Volt_AB Read Only Multiplier: 1 Monitor point for Aux
Offset: 0 Alternator Line to Line
Size (bits): 16 voltage AB
Sign: U
Units: Volt
Lower Limit:
Upper Limit:
48109 C_AuxAlt_Volt_BC Read Only Multiplier: 1 Monitor point for Aux
Offset: 0 Alternator Line to Line
Size (bits): 16 voltage BC
Sign: U
Units: Volt
Lower Limit:
Upper Limit:
48110 C_AuxAlt_Volt_CA Read Only Multiplier: 1 Monitor point for Aux
Offset: 0 Alternator Line to Line
Size (bits): 16 voltage CA
Sign: U
Units: Volt
Lower Limit:
Upper Limit:
48111 C_AuxAlt_Freq Read Only Multiplier: 0.01 Monitor point for Aux
Offset: 0 Alternator Frequency A
Size (bits): 16
Sign: U
Units: Hz
Lower Limit:
Upper Limit:
48115 C_NGR_Current Read Only Multiplier: 1 Monitor point for NGR
Offset: 0 Current
Size (bits): 16
Sign: U
Units: Amps
Lower Limit:
Upper Limit:

Copyright © 2023 Cummins Inc. 994 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


48116 C_NGR_Temp Read Only Multiplier: 1 Monitor point for NGR
Offset: 0 Temperature
Size (bits): 16
Sign: U
Units: °C
Lower Limit:
Upper Limit:
48131 C_NGR_Humidity Read Only Multiplier: 1 Monitor point for NGR
Offset: 0 Humidity
Size (bits): 16
Sign: U
Units: %
Lower Limit:
Upper Limit:
48132 C_NGR_GND Read Only 0: Inactive Indicate NGR ground
1: Active fault shutdown event

48133 Rad_S_12 Read Only Multiplier: 1 Monitor point for Cooling


Offset: 0 Fan 1 and 2 runtime
Size (bits): 16
Sign: U
Units: seconds
Lower Limit:
Upper Limit:
48134 Rad_M_12 Read Only Multiplier: 1 Monitor point for Cooling
Offset: 0 Fan 1 and 2 runtime
Size (bits): 16
Sign: U
Units: minutes
Lower Limit:
Upper Limit:
48135 Rad_H_12 Read Only Multiplier: 1 Monitor point for Cooling
Offset: 0 Fan 1 and 2 runtime
Size (bits): 16
Sign: U
Units: hours
Lower Limit:
Upper Limit:
48136 Rad_S_34 Read Only Multiplier: 1 Monitor point for Cooling
Offset: 0 Fan 3 and 4 runtime
Size (bits): 16
Sign: U
Units: seconds
Lower Limit:
Upper Limit:

A029X159 (Issue 31) 995 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

Address Parameter Access Specifications Description Control


48137 Rad_M_34 Read Only Multiplier: 1 Monitor point for Cooling
Offset: 0 Fan 3 and 4 runtime
Size (bits): 16
Sign: U
Units: minutes
Lower Limit:
Upper Limit:
48138 Rad_H_34 Read Only Multiplier: 1 Monitor point for Cooling
Offset: 0 Fan 3 and 4 runtime
Size (bits): 16
Sign: U
Units: hours
Lower Limit:
Upper Limit:
48139 Rad_S_56 Read Only Multiplier: 1 Monitor point for Cooling
Offset: 0 Fan 5 and 6 runtime
Size (bits): 16
Sign: U
Units: seconds
Lower Limit:
Upper Limit:
48140 Rad_M_56 Read Only Multiplier: 1 Monitor point for Cooling
Offset: 0 Fan 5 and 6 runtime
Size (bits): 16
Sign: U
Units: minutes
Lower Limit:
Upper Limit:
48141 Rad_H_56 Read Only Multiplier: 1 Monitor point for Cooling
Offset: 0 Fan 5 and 6 runtime
Size (bits): 16
Sign: U
Units: hours
Lower Limit:
Upper Limit:
48142 Vent_S Read Only Multiplier: 1 Monitor point for the
Offset: 0 Ventilator Fan runtime
Size (bits): 16
Sign: U
Units: seconds
Lower Limit:
Upper Limit:

Copyright © 2023 Cummins Inc. 996 A029X159 (Issue 31)


8-2023 17. PowerBloc

Address Parameter Access Specifications Description Control


48143 Vent_M Read Only Multiplier: 1 Monitor point for
Offset: 0 Ventilator Fan runtime
Size (Bits): 16
Sign: U
Units: minutes
Lower Limit:
Upper Limit:
48144 Vent_H Read Only Multiplier: 1 Monitor point for
Offset: 0 Ventilator Fan runtime
Size (Bits): 16
Sign: U
Units: hours
Lower Limit:
Upper Limit:
48127 ChargerCellVolt Read Only Multiplier: 1 Monitor point for battery
Offset: 0 charger cell voltage
Size (bits): 16
Sign: U
Units: Volt
Lower Limit:
Upper Limit:
48128 ChargerOutputVolt Read Only Multiplier: 1 Monitor point for battery
Offset: 0 charger output voltage
Size (bits): 16
Sign: U
Units: Volt
Lower Limit:
Upper Limit:

17.2 NFPA 110 Bitmaps


17.2.1 NFPA 110(1) Bitmap
TABLE 56. NFPA 110(1) BITMAP

Bit Description
0 Low fuel level
1 Low coolant level
2 Over speed
3 Low oil pressure
4 Pre-low oil pressure
5 High engine temperature

A029X159 (Issue 31) 997 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

6 Pre-high engine temperature


7 Low coolant temperature
8 Fail to start
9 Charger AC failure
10 Low battery voltage
11 High battery voltage
12 Not in auto
13 Genset running
14 Genset supplying load
15 Common alarm

See Register 40016 in Section 17.1.

17.2.2 NFPA 110(2) Bitmap


TABLE 57. NFPA 110(2) BITMAP

Bit Description
0 Emergency stop
1 Utility circuit breaker tripped
2 Genset circuit breaker tripped
3 Load demand
4 Fail to close
5 Fail to sync
6 Reverse KVAR
7 Reverse KW
8 Short circuit
9 Overcurrent
10 Overload
11 Under frequency
12 Low AC voltage
13 High AC voltage
14 Ground fault
15 Check genset

See Register 40017 in Section 17.1.

Copyright © 2023 Cummins Inc. 998 A029X159 (Issue 31)


8-2023 17. PowerBloc

17.3 StatusWord Bitmaps


17.3.1 StatusWord 1 Bitmap
TABLE 58. STATUSWORD 1 BITMAP

Bit Description
0 Louver breaker position
1 Louver open relay position
2 Louver close relay position
3 Louver 1 open
4 Louver 1 close
5 Louver 2 open
6 Louver 2 close
7 Louver 3 open
8 Louver 3 close
9 Utility breaker positon
10 NA
11 Ventilation fan fault
12 Cooling fan 1 and 2 contactor position
13 Cooling fan 1 breaker position
14 Cooling fan 2 breaker position
15 Cooling fan 3 and 4 contactor position

See Register 48001 in Section 17.1.

17.3.2 StatusWord 2 Bitmap


TABLE 59. STATUSWORD 2 BITMAP

Bit Description
0 Cooling fan 3 breaker position
1 Cooling fan 4 breaker position
2 Cooling fan 5 and 6 contactor position
3 Cooling fan 5 breaker position
4 Cooling fan 6 breaker position
5 Ventilation fan 7 and 8 contactor position
6 Ventilation fan 7 breaker position
7 Ventilation fan 8 breaker position

A029X159 (Issue 31) 999 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

8 ATS on utility position


9 ATS on utility position
10 Fuel valve open
11 Fuel valve close
12 Fuel valve manual open
13 Cooling fan 1 and 2 fault
14 Cooling fan 3 and 4 fault
15 Cooling fan 5 and 6 fault

See Register 48002 in Section 17.1.

17.3.3 StatusWord 3 Bitmap


TABLE 60. STATUSWORD 3 BITMAP

Bit Description
0 Louver manual open
1 Louver manual close
2 NA
3 NGR ground fault
4 Cooling fan container door open alarm
5 Fire alarm
6 PCC Key Switch
7 PCC ready to load
8 Louver open command
9 Louver close command
10 Cooling fan 1 and 2 run command
11 Cooling fan 3 and 4 run command
12 Cooling fan 5 and 6 run command
13 Ventilation fan run command
14 Fuel valve open command
15 Emergency shutdown command

See Register 48003 in Section 17.1.

Copyright © 2023 Cummins Inc. 1000 A029X159 (Issue 31)


8-2023 17. PowerBloc

17.4 AlarmWord Bitmaps


17.4.1 AlarmWord 1 Bitmap
TABLE 61. ALARMWORD 1 BITMAP

Bit Description
0 Louver breaker open warning
1 Louver open relay warning
2 Louver close relay warning
3 Louver 1 open warning
4 Louver 1 close warning
5 Louver 2 open warning
6 Louver 2 close warning
7 Louver 3 open warning
8 Louver 3 close warning
9 Utility breaker open warning
10 NA
11 Ventilation fan fault
12 Cooling fan 1 and 2 contactor warning
13 Cooling fan 1 breaker open warning
14 Cooling fan 2 breaker open warning
15 Cooling fan 3 and 4 contactor warning

See Register 48004 in Section 17.1.

17.4.2 AlarmWord 2 Bitmap


TABLE 62. ALARMWORD 2 BITMAP

Bit Description
0 Cooling fan 3 breaker open warning
1 Cooling fan 4 breaker open warning
2 Cooling fan 5 and 6 contactor warning
3 Cooling fan 5 breaker open warning
4 Cooling fan 6 breaker open warning
5 Ventilation fan 7 and 8 contactor warning
6 Ventilation fan 7 breaker open warning
7 Ventilation fan 8 breaker open warning

A029X159 (Issue 31) 1001 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

8 Fuel valve open warning


9 Fuel valve close warning
10 Cooling fan 1 and 2 fault warning
11 Cooling fan 3 and 4 fault warning
12 Cooling fan 5 and 6 fault warning
13 Aux alternator frequency warning
14 NGR ground fault alarm
15 Fire alarm

See Register 48005 in Section 17.1.

17.4.3 AlarmWord 3 Bitmap


TABLE 63. ALARMWORD 3 BITMAP

Bit Description
0 Aux alternator voltage warning
1 Genset container temperature high warning
2 Genset container temperature high alar
3 ATS postion warning
4 Cooling fan container door open alarm
5 PLC fault warning
6 PLC cell battery low voltage warning
7
8
9
10
11
12
13
14
15

See Register 48006 in Section 17.1.

17.4.4 AlarmWord 4 Bitmap


TABLE 64. ALARMWORD 4 BITMAP

Bit Description

Copyright © 2023 Cummins Inc. 1002 A029X159 (Issue 31)


8-2023 17. PowerBloc

0 PCC comm fault warning


1 Container temperature sensor 1 comm fault
warning
2 Container temperature sensor 2 comm fault
warning
3 NGR comm fault warning
4
5 Powermeter comm fault warning
6 Battery charger comm fault warning
7
8
9
10
11
12
13
14
15

See Register 48008 in Section 17.1.

A029X159 (Issue 31) 1003 Copyright © 2023 Cummins Inc.


17. PowerBloc 8-2023

This page is intentionally blank.

Copyright © 2023 Cummins Inc. 1004 A029X159 (Issue 31)