Mapa de Registro Modbus
Mapa de Registro Modbus
Mapa de Registro Modbus
Control
AUX101/102
DEIF AGC-5
DMC 1000/DMC 1500
ECO Tier4
MCM 3320
PC500/PC550
PC40
PC80
PCC 1301
PowerCommand 1.x/2.x/3.x
PS0500/PS060X
PowerBloc™
English
Original Instructions 8-2023 A029X159 (Issue 31)
Table of Contents
1. IMPORTANT SAFETY INSTRUCTIONS ....................................................................................... 1
1.1 Warning, Caution, and Note Styles Used in This Manual ..................................................... 1
1.2 Fuel and Fumes Are Flammable ............................................................................................ 1
1.2.1 Gaseous Fuels ............................................................................................................. 2
1.2.2 Exhaust Gases Are Deadly.......................................................................................... 2
1.3 Moving Parts Can Cause Severe Personal Injury or Death ................................................... 2
1.4 Do Not Operate in Flammable and Explosive Environments ................................................. 2
1.5 Electrical Shock Can Cause Severe Personal Injury Or Death.............................................. 2
1.5.1 Medium Voltage Equipment (601 V to 15 kV - U.S. and Canada) .............................. 3
1.6 General Safety Precautions.................................................................................................... 3
1.7 Decommissioning and Disassembly ....................................................................................... 6
2. INTRODUCTION............................................................................................................................ 7
2.1 Controllers............................................................................................................................... 7
2.2 Bitmapping .............................................................................................................................. 8
2.2.1 32-Bit Float Representation ......................................................................................... 8
5.1.17 Function Code 4 (04h): Read Input Registers (EIC) (Address, Bit: 593-1370) ..... 192
5.1.18 Function Code 4 (04h): Read Input Registers (EIC) (Address, Bit: 1371-
1994).......................................................................................................................... 199
9. MCM3320................................................................................................................................... 295
9.1 MCM3320 Modbus Register Map ....................................................................................... 295
9.1.1 Modbus Communications......................................................................................... 295
9.1.2 Reference Documents ............................................................................................. 295
9.1.3 Serial Port Configuration.......................................................................................... 295
9.1.4 Device Addresses .................................................................................................... 295
9.1.5 Power-Up Time ........................................................................................................ 295
9.1.6 Response Time ........................................................................................................ 295
9.1.7 Data Formatting ....................................................................................................... 295
9.1.8 Modbus Activity LED................................................................................................ 296
9.1.9 Supported Functions ................................................................................................ 296
9.1.10 Holding Register Function...................................................................................... 296
9.1.11 Preset Single/Preset Multiple Registers Function.................................................. 296
9.1.12 Diagnostic Counters............................................................................................... 296
9.1.13 Register Maps ........................................................................................................ 297
9.1.14 Application Layer.................................................................................................... 297
9.1.15 Read Hold Registers.............................................................................................. 297
9.1.16 Set Single Register ................................................................................................ 297
9.1.17 Modbus Loopback.................................................................................................. 297
9.1.18 Set Multiple Registers ............................................................................................ 298
9.1.19 Modbus Register Table.......................................................................................... 298
DANGER
Indicates a hazardous situation that, if not avoided, will result in death or serious injury.
WARNING
Indicates a hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION
Indicates a hazardous situation that, if not avoided, could result in minor or moderate injury.
NOTICE
Indicates information considered important, but not hazard-related (e.g., messages relating to
property damage).
• Use extreme caution when working on electrical components. High voltages can cause injury or
death. DO NOT tamper with interlocks.
• Follow all applicable state and local electrical codes. Have all electrical installations performed by a
qualified licensed electrician. Tag and lock open switches to avoid accidental closure.
• DO NOT CONNECT GENERATOR SET DIRECTLY TO ANY BUILDING ELECTRICAL SYSTEM.
Hazardous voltages can flow from the generator set into the utility line. This creates a potential for
electrocution or property damage. Connect only through an approved isolation switch or an
approved paralleling device.
WARNING
Moving Parts
Moving parts can cause severe personal injury.
Use extreme caution around moving parts. All guards must be properly fastened to prevent
unintended contact.
WARNING
Toxic Hazard
Used engine oils have been identified by some state and federal agencies to cause cancer or
reproductive toxicity.
Do not ingest, breathe the fumes, or contact used oil when checking or changing engine oil.
Wear protective gloves and face guard.
WARNING
Electrical Generating Equipment
Incorrect operation can cause severe personal injury or death.
Do not operate equipment when fatigued, or after consuming any alcohol or drug.
WARNING
Toxic Gases
Substances in exhaust gases have been identified by some state and federal agencies to cause
cancer or reproductive toxicity.
Do not breathe in or come into contact with exhaust gases.
WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause severe burns or
death.
Do not store fuel, cleaners, oil, etc., near the generator set.
WARNING
High Noise Level
Generator sets in operation emit noise, which can cause hearing damage.
Wear appropriate ear protection at all times.
WARNING
Hot Surfaces
Contact with hot surfaces can cause severe burns.
The unit is to be installed so that the risk of hot surface contact by people is minimized. Wear
appropriate PPE when working on hot equipment and avoid contact with hot surfaces.
WARNING
Electrical Generating Equipment
Incorrect operation and maintenance can result in severe personal injury or death.
Make sure that only suitably trained and experienced service personnel perform electrical and/or
mechanical service.
WARNING
Toxic Hazard
Ethylene glycol, used as an engine coolant, is toxic to humans and animals.
Wear appropriate PPE. Clean up coolant spills and dispose of used coolant in accordance with
local environmental regulations.
WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause severe burns or
death.
Do not use combustible liquids like ether.
WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the starting battery
cables (negative [–] first).
WARNING
Fire Hazard
Materials drawn into the generator set are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from obstructions.
WARNING
Fire Hazard
Materials drawn into the generator set are a fire hazard. Fire can cause severe burns or death.
Make sure the generator set is mounted in a manner to prevent combustible materials from
accumulating under the unit.
WARNING
Fire Hazard
Accumulated grease and oil are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from obstructions. Repair oil
leaks promptly.
NOTICE
Keep multi-type ABC fire extinguishers close by. Class A fires involve ordinary combustible
materials such as wood and cloth. Class B fires involve combustible and flammable liquid fuels
and gaseous fuels. Class C fires involve live electrical equipment. (Refer to NFPA No. 10 in the
applicable region.)
NOTICE
Before performing maintenance and service procedures on enclosed generator sets, make sure
the service access doors are secured open.
NOTICE
Stepping on the generator set can cause parts to bend or break, leading to electrical shorts, or to
fuel leaks, coolant leaks, or exhaust leaks. Do not step on the generator set when entering or
leaving the generator set room.
NOTICE
There is a fixed number of write cycles available in the life of the control. Once these are used
up, the control must be replaced.
NOTICE
Throughout this document, if a parameter is marked for PCC3300 and PCC3300V2, then it is
applicable to both. If it is marked for PCC3300V2, then it is applicable to PCC3300V2 only.
This note is targeted to, but not limited to, the following Modbus registers per Cummins device. If the
device is not listed in the table, please reference the dedicated Modbus register for "Save Trims".
2.2 Bitmapping
Bitmapped registers are based in a 0-bit system. For a 16-bit register, 0 is the low-order bit and 15 is the
high-order bit.
Combine the two registers in binary format to become: 0100 0001 0100 1100 1010 0011 1110 1110
This combined value can be put in the below IEEE 754 format.
S Exponent Fraction
0 1 0 0 0 0 0 1 0 1 0 0 1 1 0 0 1 0 1 0 0 0 1 1 1 1 1 0 1 1 1 0
The value in Exponent is 10000010, which is 130 in decimal. The remaining portion is placed in Fraction,
which is 0.0100 1100 1010 0011 1110 1110 (base 2).
In base 2 (binary), 1.F is 1.0100 1100 1010 0011 1110 1110, which equals 1.29937636852264404296875
in base 1.0
Placing this in the formula results in the following:
(-1)^(0) * 2^(130-127)*(1.29937636852264404296875) = 10.395
Using this method, here is an example on how to write a value of 12.65 amps to Load L1 RMS Current.
• 12.65 can be represented in binary as follows:
◦ 12 = 1100
◦ 0.65 = 0.1010 0110 0110 0110 0110 0110 0110 0110011001100110011001100110011001...
• Combining the two values = 1100. 1010 0110 0110 0110 0110 0110
◦ Total of 23 Fraction points can be included in the format of Figure 1
◦ The above number can be represented in the following binary scientific notation: 1.100 1010
0110 0110 0110 0110 0110 * 2exp3
▪ S = 0 ( since value is positive number)
▪ E = 127 + 3 = 130 (1000 0010) (IEE 754 bias for exponent is 127 for 32 bits)
▪ F = 0.100 1010 0110 0110 0110 0110 0110...
▫ This number can be represented in the below IEEE 754 format.
S Exponent Fraction
0 1 0 0 0 0 0 1 0 1 0 0 1 0 1 0 0 1 1 0 0 1 1 0 0 1 1 0 0 1 1 0
Bit Description
15 Common Alarm
14 Genset Supplying Load
13 Genset Running
12 Not in Auto
11 High Battery Voltage
10 Low Battery Voltage
9 Charger AC Failure
8 Fail to Start
7 Low Coolant Temperature
6 Pre–high Engine Temperature
5 High Engine Temperature
4 Pre–low Oil Pressure
3 Low Oil Pressure
2 Overspeed
1 Low Coolant Level
0 Low Fuel Level
See Chapter 13 Reg. 40016, Section 14.2 Reg. 40716, 40717, and Section 6.1.1
Bit Description
15 Check Genset
14 Ground Fault
13 High AC Voltage
12 Low AC Voltage
11 Under Frequency
10 Overload
9 Overcurrent
8 Short Circuit
Bit Description
7 Reverse KW
6 Reverse kVAR
5 Fail to Sync
4 Fail to Close
3 Load Demand
2 Genset Circuit Breaker Tripped
1 Utility Circuit Breaker Tripped
0 Emergency Stop
Bit Description
15 Source 1 Connected
14 Source 2 Connected
13 NA
12 Not in Auto
11 NA
10 NA
9 Charger AC Failure
8 NA
7 NA
6 NA
5 NA
4 NA
3 NA
2 NA
1 NA
0 NA
Bit Description
15 Source 1 Available
14 Source 2 Available
Bit Description
13 Source 1 Connected
12 Source 2 Connected
11 ATS Common Alarm
10 Not In Auto
9 Test / Exercise In Progress
8 Low Battery Voltage
7 Load Shed
6 Transfer Inhibit
5 Retransfer Inhibit
4 Fail To Close
3 Fail To Disconnect
2 Fail To Synchronize
1 Bypass to Source 1
0 Bypass to Source 2
Bit Description
31 Check Genset
30 Ground Fault
29 High AC Voltage
28 Low AC Voltage
27 Under Frequency
26 Overload Warning OR Overload Shutdown
25 Overcurrent
24 Short Circuit
23 Reverse KW
22 Reverse KVAR
21 Fail to Sync
20 Fail to Close
19 Load Demand
18 Genset Circuit Breaker Tripped
NOTICE
To view 32-bit data of NFPA110 register in Modbus tool, length shall be provided as 2 for 400016
address for read/write values.
Bit Description
15 Source 1 Available
14 Source 2 Available
13 Source 1 Connected
12 Source 2 Connected
11 ATS Common Alarm
10 Not in Auto
9 Test/Excercise in Progress
8 Low Battery Voltage
7 Load Shed
6 Transfer Inhibit
5 Retransfer Inhibit
4 Fail to close
3 Fail to disconnect
2 Fail to Synchronize
1 Bypass To Source 1
0 Bypass To Source 2
Bit Description
15 (LSB) NA
14 NA
13 NA
12 NA
11 NA
10 NA
9 NA
8 NA
7 NA
6 Charger AC Failure
5 NA
4 NA
3 Not in Auto
2 NA
1 Source 2 Connected
0 (MSB) ATS Common Alarm
Bit Description
15 (LSB) NA
14 NA
13 Fail to Synchronize
12 Fail to Disconnect
Bit Description
11 Fail to close
10 Retransfer Inhibit
9 Transfer Inhibit
8 Load Shed
7 NA
6 Test / Exercise in Progress
5 Not in Auto
4 ATS Common Alarm
3 Source 2 Connected
2 Source 1 Connected
1 Source 2 Available
0 (MSB) Source 1 Available
Bit Description
15 (LSB) NA
14 NA
13 NA
12 NA
11 NA
10 NA
9 NA
8 NA
7 NA
6 Charger AC Failure
5 NA
4 NA
3 Not in Auto
2 NA
1 Source 2 Connected
0 (MSB) ATS Common Alarm
Bit Description
15 (LSB) NA
14 NA
13 Fail to Synchronize
12 Fail to Disconnect
11 Fail to Close
10 Retransfer Inhibit
9 Transfer Inhibit
8 Load Shed
7 NA
6 Test / Exercise in Progress
5 Not in Auto
4 ATS Common Alarm
3 Source 2 Connected
2 Source 1 Connected
1 Source 2 Available
0 (MSB) Source 1 Available
NOTICE
If an address or bit is not listed in this table it is not implemented.
System
Addr. Access Specifications Comments
Name
System
Addr. Access Specifications Comments
Name
0: Do Nothing Save configuration parameters or
adjustments to non-volatile
Read/ Do Nothing memory. Perform Save Trims after
43052 Save Trims
Write 1: Save Trims Type: Trim all configurations have been
updated. Do not save trims unless
a change has occurred.
Relay 1
Parameters to allow the Relay to be
Relay 2
turned on/off. The lower 8 bits are
Relay 3 used to store out relay values.
Relay 1 is stored in bit 0 and Relay
Relay 4 Read/ 0: Inactive 8 is stored in bit 7. The upper 8 bits
42001 Default: 0
Relay 5 Write 1: Active are 0. In the event of a power cycle
or reboot, all the output values are
Relay 6 reset to 0. This register is used as
heartbit for AUX101 and indicates a
Relay 7
secure communication.
Relay 8
Relay 9
Relay 10
Relay 11
Relay 12 Read/ 0: Inactive Parameters to allow the Relay to be
42009 Default: 0
Relay 13 Write 1: Active turned on/off.
Relay 14
Relay 15
Relay 16
Read Register that contains the value of
42017 Input 1 Default: NA
Only Input 1.
Read Register that contains the value of
42018 Input 2 Default: NA
Only Input 2.
Read Register that contains the value of
42019 Input 3 Default: NA
Only Input 3.
Read Register that contains the value of
42020 Input 4 Default: NA
Only Input 4.
Read Register that contains the value of
42021 Input 5 Default: NA
Only Input 5.
Read Register that contains the value of
42022 Input 6 Default: NA
Only Input 6.
Read Register that contains the value of
42023 Input 7 Default: NA
Only Input 7.
Read Register that contains the value of
42024 Input 8 Default: NA
Only Input 8.
System
Addr. Access Specifications Comments
Name
Bit 0 of this register is used for
Input 9
Input 9 when AUX102 is available.
Bit 1 of this register is used for
Input 10
Read Input 10 when AUX102 is available.
42025 Default: NA
Only Bit 2 of this register is used for
Input 11
Input 11 when AUX102 is available.
Bit 3 of this register is used for
Input 12
Input 12 when AUX102 is available.
Current Default: NA
Read/
42029 Source 1 mA = CS/10 Set for Analog Input 3.
Write Type: Trim
Settings
Current Default: NA
Read/
42030 Source 2 mA = CS/10 Set for Analog Input 4.
Write Type: Trim
Settings
Current Default: NA
Read/
42031 Source 3 mA = CS/10 Set for Analog Input 5.
Write Type: Trim
Settings
Current Default: NA
Read/
42032 Source 4 mA = CS/10 Set for Analog Input 6.
Write Type: Trim
Settings
0: Sender
Input 1 Read/ Default: NA
42033 1: Switch - Active Low Register to configure Input 1.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 2 Read/ Default: NA
42034 1: Switch - Active Low Register to configure Input 2.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 3 Read/ Default: NA
42035 1: Switch - Active Low Register to configure Input 3.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 4 Read/ Default: NA
42036 1: Switch - Active Low Register to configure Input 4.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 5 Read/ Default: NA
42037 1: Switch - Active Low Register to configure Input 5.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 6 Read/ Default: NA
42038 1: Switch - Active Low Register to configure Input 6.
Settings Write Type: Trim
2: Switch - Active High
System
Addr. Access Specifications Comments
Name
0: Sender
Input 7 Read/ Default: NA
42039 1: Switch - Active Low Register to configure Input 7.
Settings Write Type: Trim
2: Switch - Active High
0: Sender
Input 8 Read/ Default: NA
42040 1: Switch - Active Low Register to configure Input 8.
Settings Write Type: Trim
2: Switch - Active High
NOTICE
If an address or bit is not listed in this table it is not implemented.
Multiplier: Unit:
1.000000000000 Lower Limit: .000 Logical address
MB Logical Read/ Offset: 0
42001 Upper Limit: to be read via Communications
Read Address Write
Size (bits): 16 65535.000 Modbus
Sign: U Default: 0
Multiplier:
Unit:
1.000000000000 Logical data to
MB Logical Read Lower Limit:
42002 Offset: 0 be read via Communications
Read Data Only Upper Limit:
Size (bits): 32 Modbus
Default:
Sign: U
Multiplier:
Unit:
1.000000000000 Hard coded
Read Lower Limit:
42009 Device Type Offset: 0 device type id = Communications
Only Upper Limit:
Size (bits): 16 52 (0x0034)
Default:
Sign: U
Multiplier:
Unit:
0.000100000000
Software Read Lower Limit: Software version Controller
42010 Offset: 0
Version Only Upper Limit: number Information
Size (bits): 16
Default:
Sign: U
Multiplier: The most
Unit:
1.000000000000 recently
Current Fault Read Lower Limit: Fault and Event
42012 Offset: 0 occurring fault
Status Only Upper Limit: Info
Size (bits): 16 which is still
Default: active
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L3N Read Lower Limit: Generator set
42020 Offset: 0 Voltage
Voltage Only Upper Limit: L3N voltage
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Volts
Genset LN 1.000000000000 Generator set
Read Lower Limit:
42021 Average Offset: 0 LN average Voltage
Only Upper Limit:
Voltage Size (bits): 16 voltage
Default
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L1L2 Read Lower Limit: Generator set
42022 Offset: 0 Voltage
Voltage Only Upper Limit: L1L2 voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L2L3 Read Lower Limit: Generator set
42023 Offset: 0 Voltage
Voltage Only Upper Limit: L2L3 voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L3L1 Read Lower Limit: Generator set
42024 Offset: 0 Voltage
Voltage Only Upper Limit: L3L1 voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
Genset LL 1.000000000000 Generator set
Read Lower Limit:
42025 Average Offset: 0 LL average Voltage
Only Upper Limit:
Voltage Size (bits): 16 voltage
Default:
Sign: U
Multiplier:
.100000000000 Unit: % Utility total kW
Offset: 0 Lower Limit: as percent of
Utility Total kW Read
42165 total utility Power
Percent Only Size (bits): 16 Upper Limit: capacity -- used
Sign: S Default: by barograph
Multiplier: Engineering
kW Load Unit: %
.010000000000 units value for
Setpoint Engr Read Lower Limit:
42222 Offset: 0 the kW load Analog Inputs
Units Display Only Upper Limit:
Size (bits): 16 setpoint analog
Value Default:
Sign: S input
Multiplier: Unit: kW
Genset 1.000000000000 Lower Limit: Setpoint for
Read/ Offset: 0 Master Load
42334 Unloaded -32768.000 kW generator set
Write Control
Level Size (bits): 16 Upper Limit: 32767 kW unloaded level
Sign: S Default: 50.000
Multiplier:
Unit:
1.000000000000 Indicates which
Load 1 Add Read/ Lower Limit: 1.000 Load Add Shed
42373 Offset: 0 add level load 1
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 1.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 2 Add Read/ Lower Limit: 1.000 Load Add Shed
42374 Offset: 0 add level load 2
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 2.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 3 Add Read/ Lower Limit: 1.000 Load Add Shed
42375 Offset: 0 add level load 3
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 3.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 4 Add Read/ Lower Limit: 1.000 Load Add Shed
42376 Offset: 0 add level load 4
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 4.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 5 Add Read/ Lower Limit: 1.000 Load Add Shed
42377 Offset: 0 add level load 5
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 5.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 6 Add Read/ Lower Limit: 1.000 Load Add Shed
42378 Offset: 0 add level load 6
Level Write Upper Limit: 6.000 Control
Size (bits): 8 is assigned to
Default: 6.000
Sign: U
Multiplier:
Unit:
1.000000000000 Indicates which
Load 1 Shed Read/ Lower Limit: 0.000 Load Add Shed
42379 Offset: 0 shed level load
Level Write Upper Limit: 5.000 Control
Size (bits): 8 1 is assigned to
Default: 0.000
Sign: U
Unit: second
Multiplier:
1.000000000000 Lower Limit: 0.000
Genset Bus second Sets the delay
Read/ Offset: 0 System
42387 kW Overload time for overload
Write Upper Limit: 120.000 Information
Delay Size (bits): 8 based on kW
second
Sign: U
Default: 60.000
Multiplier: Proportional
Unit: gain for kW
1.000000000000
Read/ Lower Limit: 0.000 closed loop Master Load
42414 kW Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 60.000
Sign: U paralleling
Multiplier: Integral gain for
Unit:
1.000000000000 kW closed loop
Read/ Lower Limit: 0.000 Master Load
42415 kW KI Offset: 0 control in
Write Upper Limit: 255.000 Control
Size (bits): 8 extended
Default: 60.000 paralleling
Sign: U
Multiplier: Proportional
Unit: gain for kVAR
1.000000000000
Read/ Lower Limit: 0.000 closed loop Master Load
42416 kVAR Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 120.000
Sign: U paralleling
Multiplier: Integral gain for
Unit:
1.000000000000 kVAR closed
Read/ Lower Limit: 0.000 Master Load
42417 kVAR KI Offset: 0 loop control in
Write Upper Limit: 255.000 Control
Size (bits): 8 extended
Default: 50.000 paralleling
Sign: U
Multiplier:
Unit: Selects which
1.000000000000
Scheduler Read/ Lower Limit: 1.000 scheduler System
42418 Offset: 0
Program Select Write Upper Limit: 12.000 program to view Scheduler
Size (bits): 8 or edit
Default: 1.000
Sign: U
Unit: minute
Multiplier: Use to adjust
Scheduler 1.000000000000 Lower Limit: 0.000
minute the duration
Exception x Read/ Offset: 0 System
42436 minutes of the
Duration Write Upper Limit: 59.000 Scheduler
Size (bits): 8 selected
Minutes minute
Sign: U exception
Default: 0.000
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 110.000
Genset PT Volts Generator Set
Read/ Offset: 0
42440 Primary PT primary AC Setup
Write Upper Limit:
Voltage Size (bits): 16 voltage
45000.000 Volts
Sign: U
Default: 480
Multiplier: Unit: Volts
Genset PT 1.000000000000 Lower Limit: 110.000 Generator set
Read/ Offset: 0
42441 Secondary Volts Upper Limit: 500 PT secondary AC Setup
Write
Voltage Size (bits): 16 Volts voltage
Sign: U Default: 120
Unit: Amp
Multiplier:
1.000000000000 Lower Limit: 5.000
Genset CT Amp Generator set
Read/ Offset: 0
42442 Primary CT primary AC Setup
Write Upper Limit:
Current Size (bits): 16 current
10000.000 Amp
Sign: U
Default: 100
Multiplier:
Unit: second
High Battery 1.000000000000
Read/ Lower Limit: 2 second Sets high Battery Voltage
42459 Voltage Set Offset: 0 battery voltage
Write Upper Limit: 60 second set time Protection
time Size (bits): 8
Default: 60
Sign: U
Multiplier:
Unit: second
Low Battery 1.000000000000
Read/ Lower Limit: 2 second Sets low battery Battery Voltage
42460 Voltage Set Offset: 0
Write Upper Limit: 60 second voltage set time Protection
Time Size (bits): 8
Default: 60
Sign: U
Multiplier: Difference
Unit: kW between online
Total Spare 1.000000000000
Read Lower Limit: capacity (4 System
42718 Online Offset: 0
Only Upper Limit: generator sets) Information
Capacity Size (bits): 16
Default: and Genset Bus
Sign: S Total kW
Multiplier: Indicates kW
Unit: kW threshold for
Next Gen 1.000000000000
Read Lower Limit: gen bus at Load Demand
42719 Restart Offset: 0
Only Upper Limit: which the next Control
Threshold Size (bits): 16
Default: generator set
Sign: S will restart
Indicates kW
Multiplier: threshold for
Unit: kW
Next Gen 1.000000000000 gen bus at
Read Lower Limit: Load Demand
42720 Shutdown Offset: 0 which the next
Only Upper Limit: Control
Threshold Size (bits): 16 generator set
Default: will load demand
Sign: S
stop
Multiplier: Calculated kW
Unit: kW overload
Genset Bus 1.000000000000
Read Lower Limit: threshold based System
42727 kW Overload Offset: 0
Only Upper Limit: on online Information
Threshold Size (bits): 16
Default: capacity and %
Sign: S setting
Multiplier:
Unit:
Modbus Bus 1.000000000000
Read Lower Limit: Modbus bus
42732 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
Multiplier:
Unit:
1.000000000000
Modbus CRC Read Lower Limit: Modbus CRC
42733 Offset: 0 Communications
Error Count Only Upper Limit: error count
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit:
Modbus 1.000000000000
Read Lower Limit: Modbus
42734 Exception Offset: 0 Communications
Only Upper Limit: exception count
Count Size (bits): 16
Default:
Sign: U
NOTICE
If an address or bit is not listed in this table it is not implemented.
0: Unavailable
Size (bits): 8 1: Dead Energization
Utility Bus Read
42117 status of the PTC Sensors
Status Only Number of Fields: 3 2: Live utility bus
Default:
0: Not Available
Size (bits): 8 1: Not Unloaded Indicates utility
Utility Unload Read Master Load
42208 unloaded
Status Only Number of Fields: 3 2: Unloaded Control
status
Default:
0: Not Available Indicates
Genset Unload Read Size (bits): 8 1: Not Unloaded generator set Master Load
42209
Status Only Number of Fields: 3 2: Unloaded unloaded Control
Default: status
0: Not Enabled
Indicates the
1: No Source connected
Connected state of the
Read Size (bits): 8 PTC State
42224 PTC State 2: Utility Connected power transfer
Only Number of Fields: 5 Machine
3: Genset Connected control
4: Paralleled Read/Write in
Comp.
Default:
Size (bits):8 Indicates
Number of Fields: 2 0: Not Allowed whether any
Sync Check Read Master Sync
42225 1: Allowed sync check
Close Allowed Only Control
Default: conditions for
have been met
Size (bits): 8
0: Synchronizer Off Indicates state
Synchronizer Read Number of Fields: 2 Master Sync
42227 1: Synchronizer On of the
Status Only Control
Default: synchronizer
0: Open
Size (bits): 8 Indicates
Breaker 2 Read 1: Closed Load Add Shed
42230 Number of Fields: 3 position status
Position Only 2: Not Available Control
of breaker 2
Default: Not Available
0: Open
Size (bits): 8 1: Closed Indicates
Breaker 3 Read Load Add Shed
42231 position status
Position Only Number of Fields: 3 2: Not Available Control
of breaker 3
Default: Not Available
0: Open
Size (bits): 8 1: Closed Indicates
Breaker 5 Read Load Add Shed
42233 position status
Position Only Number of Fields: 3 2: Not Available Control
of breaker 5
Default: Not Available
0: Open
Size (bits): 8 1: Closed Indicates
Breaker 6 Read Load Add Shed
42234 position status
Position Only Number of Fields: 3 2: Not Available Control
of breaker 6
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 1 Trip Read Load Add Shed
42235 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 1
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 2 Trip Read Load Add Shed
42236 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 2
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 3 Trip Read Load Add Shed
42237 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 3
Default: Not Available
Size (bits): 8
0: Not Available
Number of Fields: 3 Indicates trip
Breaker 4 Trip Read 1: Normal Load Add Shed
42238 status of
Status Only 2: Tripped Control
breaker 4
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 5 Trip Read Load Add Shed
42239 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 5
Default: Not Available
0: Not Available
Size (bits): 8 1: Normal Indicates trip
Breaker 6 Trip Read Load Add Shed
42240 status of
Status Only Number of Fields: 3 2: Tripped Control
breaker 6
Default: Not Available
0: Do Nothing Indicates
Add Level 2 Read Size (bits):8 Load Add Shed
42253 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 2
0: Do Nothing Indicates
Add Level 3 Read Size (bits): 8 Load Add Shed
42254 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 3
0: Do Nothing Indicates
Add Level 4 Read Size (bits): 8 Load Add Shed
42255 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 4
0: Do Nothing Indicates
Add Level 5 Read Size (bits): 8 Load Add Shed
42256 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 5
0: Do Nothing Indicates
Add Level 6 Read Size (bits): 8 Load Add Shed
42257 1: Add Level status of add
Command Only Number of Fields: 2 Control
Default: Do Nothing level 6
0: Do Nothing Indicates
Shed Level 1 Read / Size (bits): 8 Load Add Shed
42258 1: Shed Level status of shed
Command Write Number of Fields: 2 Control
Default: Do Nothing level 1
0: Do Nothing Indicates
Shed Level 2 Read Size (bits): 8 Load Add Shed
42259 1: Shed Level status of shed
Command Only Number of Fields: 2 Control
Default: Do Nothing level 2
0: Do Nothing Indicates
Shed Level 3 Read / Size (bits): 8 Load Add Shed
42260 1: Shed Level status of shed
Command Write Number of Fields: 2 Control
Default: Do Nothing level 3
0: Do Nothing Indicates
Shed Level 4 Read Size (bits): 8 Load Add Shed
42261 1: Shed Level status of shed
Command Only Number of Fields: 2 Control
Default: Do Nothing level 4
0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 1 Load Add Shed
42274 Level 1 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 2 Load Add Shed
42275 Level 2 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 3 Load Add Shed
42276 Level 3 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 4 Load Add Shed
42277 Level 4 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed Size (bits): 8
Read / shed level 5 Load Add Shed
42278 Level 5 1: Restore Level
Write Number of Fields: 2 has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates add
Add Load 1 Read Size (bits): 8 Load Add Shed
42279 1: Add Load command for
Command Only Number of Fields: 2 Control
Default: Do Nothing load 1
0: Manual
1: Normal Indicates the
PTC Genset 2: Normal Override current
Read Size (bits):8 PTC Operating
42296 Operating 3: Test operating
Only Number of Fields: 6 Mode
Mode 4: Utility Fail mode of the
5: Extended Parallel generator sets
Default:
0: Manual
1: Normal Indicates the
PTC Transfer 2: Normal Override current
Read Size (bits):8 PTC Operating
42297 Pair Operating 3: Test operating
Only Number of Fields: 6 Mode
Mode 4: Utility Fail mode of the
5: Extended Parallel transfer pair
Default:
0: Manual
Priority Control Read / Size (bits): 8 Sets priority
42304 1: Automatic Priority Control
Method Write Number of Fields: 2 control method
Default: Manual
0: Inactive Use to
Clear Fault Read / Size (bits):8 completely Fault and Event
42342 1: Active
History Table Write Number of Fields: 2 clear the fault Info
Default: Inactive history table
Use to
completely
Clear Size (bits):8 0: Inactive clear the
Read / Fault and Event
42343 Occurrence Number of Fields: 2 1: Active counts in faults
Write Info
Table Default: Inactive and events
occurrence
tables
Use to
0: Do Nothing permanently
Genset Reset Size (bits):8
Read / clear all
42344 All Energy 1: Clear Counters Energy
Write Number of Fields: 2 generator set
Meters Default: Do Nothing energy meter
values
Allows protocol
0: PCCNet CT the
Port Protocol Read / Size (bits): 8 PCCNet port to
42359 1: MON Communications
Selection Write Number of Fields: 2 be changed to
Default: PCCNet MON for
troubleshooting
0: Sunday
1: Monday
2: Tuesday Use to adjust
Scheduler Size (bits): 8 3: Wednesday start day of
Read / System
42422 Program x week for the
Write Number of Fields: 7 4: Thursday Scheduler
Start Day selected
5: Friday program
6: Saturday
Default: Sunday
0: 12V DC voltage
Nominal Read / Size (bits): 8 Battery Voltage
42454 1: 24V provided to the
Battery Voltage Write Number of Fields: 2 Protection
Default: 24V control
Use to enable
Genset Online 0: Disable or disable the
Read / Size (bits): 8
42461 Capacity 1: Enable generator set PTC Sensors
Write Number of Fields: 2
Sensor Enable Default: Disable online capacity
sensor
Indicates that
0: Inactive the generator
Gen Bus Base Read Size (bits):8 System
42472 1: Active bus is on base
Load Status Only Number of Fields: 2 Information
Default: load extended
paralleling
Indicates that
0: Inactive the utility bus is
Util Bus Peak Read Size (bits): 8 System
42473 1: Active on peak shave
Shave Status Only Number of Fields: 2 Information
Default: extended
paralleling
0: Stop State of
Extended Size (bits): 8
Read / extended
42600 Parallel Start 1: Start Discrete Inputs
Write Number of Fields: 2 parallel start
Vol Default: Stop volatile input
0: inactive State of
Synchronizer Read / Size (bits): 8 synchronizer
42601 1: Active Discrete Inputs
Enable Vol Write Number of Fields: 2 enable volatile
Default: inactive input
0: inactive State of utility
Utility Source Read / Size (bits): 8
42602 1: Active source failure Discrete Inputs
Failure Vol Write Number of Fields: 2
Default: inactive volatile input
0: No Inhibit State of
Transfer Inhibit Read / Size (bits):16
42603 1: Inhibit transfer inhibit Discrete Inputs
Vol Write Number of Fields: 2
Default: No Inhibit volatile input
0: No Inhibit State of
Retransfer Read / Size (bits):8 retransfer
42604 1: Inhibit Discrete Inputs
Inhibit Vol Write Number of Fields: 2 inhibit volatile
Default: No Inhibit input
0: No Inhibit State of
Gen CB Inhibit Read / Size (bits): 8 generator CB
42605 1: Inhibit Discrete Inputs
Vol Write Number of Fields: 2 inhibit volatile
Default: No Inhibit input
0: No Inhibit State of utility
Util CB Inhibit Read / Size (bits): 8
42606 1: Inhibit CB inhibit Discrete Inputs
Vol Write Number of Fields: 2
Default: No Inhibit volatile input
0: Auto State of
Auto/Manual Read / Size (bits): 8
42607 1: Manual auto/manual Discrete Inputs
Vol Write Number of Fields: 2
Default: Auto volatile input
0: No Override State of
Read / Size (bits): 8
42610 Override Vol 1: Override override Discrete Inputs
Write Number of Fields: 2
Default: No Override volatile input
0: Start State of
Extended Size (bits): 8
Read extended
42611 Parallel Start 1: Stop Discrete Inputs
Only Number of Fields: 2 parallel start
Sw Default: input
0: Inactive State of
Synchronizer Read Size (bits): 8
42612 1: Active synchronizer Discrete Inputs
Enable Sw Only Number of Fields: 2
Default: enable input
0: No Inhibit State of
Transfer Inhibit Read Size (bits): 8
42614 1: Inhibit transfer inhibit Discrete Inputs
Sw Only Number of Fields: 2
Default: input
0: No Inhibit State of
Retransfer Read Size (bits): 8
42615 1: Inhibit retransfer Discrete Inputs
Inhibit Sw Only Number of Fields: 2
Default: inhibit input
0: No Inhibit Sate of
Gen CB Inhibit Read Size (bits): 8
42616 1: Inhibit generator CB Discrete Inputs
Sw Only Number of Fields: 2
Default: inhibit input
0: Stop
Read Size (bits): 8 State of test
42619 Test Start Sw 1: Start Discrete Inputs
Only Number of Fields: 2 start input
Default:
0: No Reset
Read Size (bits): 8 State of fault
42620 Fault Reset Sw 1: Reset Discrete Inputs
Only Number of Fields: 2 reset input
Default:
0: No Override
Read Size (bits): 8 State of
42621 Override Sw 1: Override Discrete Inputs
Only Number of Fields: 2 override input
Default:
0: No Inhibit Indicates state
Read Size (bits): 8
42622 Master Inhibit 1: Inhibit of Master Priority Control
Only Number of Fields: 2
Default: priority inhibit
0: Inactive State of
Gen CB Read Size (bits): 8
42623 1: Active generator CB Discrete Inputs
Tripped Sw Only Number of Fields: 2
Default: tripped input
0: Inactive State of
Gen CB Read / Size (bits): 8 generator CB
42624 1: Active Discrete Inputs
Tripped Vol Write Number of Fields: 2 tripped volatile
Default: Inactive input
0: Inactive State of utility
Util CB Tripped Read Size (bits): 8
42625 1: Active CB tripped Discrete Inputs
Sw Only Number of Fields: 2
Default: input
0: L1–L2–L3
Genset Phase Read Size (bits): 8 Generator set
42627 1: L1–L3–L2 Phase
Rotation Only Number of Fields: 2 phase rotation
Default:
Size (bits): 8 0: L1–L2–L3
Utility Phase Read Utility phase
42628 Number of Fields: 2 1: L1–L3–L2 Phase
Rotation Only rotation
Default:
Size (bits): 8 0: Breaker Open State of Gen1
Gen1 CB Read
42629 Number of Fields: 2 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: input
0: No Inhibit Use to
Network Read / Size (bits): 8
42637 1: Inhibit manually inhibit Priority Control
Master Inhibit Write Number of Fields: 2
Default: No Inhibit the module
0: Gen1
Indicates which
Size (bits): 8 1: Gen2 generator set is
Next Gen To Read Number of Fields: 5 2: Gen3 next to be Load Demand
42721
Restart Only 3: Gen4 restarted if load Control
4: None conditions are
met
Default:
0: Gen1
Size (bits): 8 Indicates which
1: Gen2 generator set is
Number of Fields: 5
Next Gen To Read 2: Gen3 next to be Load Demand
42722
Shutdown Only 3: Gen4 stopped if load Control
4: None conditions are
met
Default:
0: Off Indicates
1: No Load current run
Scheduler Run Read Size (bits): 8 command System
42731 2: With Load
Command Only Number of Fields: 4 coming from Scheduler
3: Extended Parallel the scheduler
Default: function
0: Do Nothing Clears all the
Modbus Clear Read / Size (bits): 8
42737 1: Clear Counters Modbus Communications
Counters Write Number of Fields: 2
Default: Do Nothing counters
Size (bits): 8
0: Normal
Number of Fields: 3 Use to set
Read / 1: Set Clock
42738 Clock Mode clock and save Real Time Clock
Write 2: Save Clock setting
Default: Normal
0: Sunday
1: Monday
2: Tuesday
Size (bits): 8 3: Wednesday Indicates day
Read
42745 Clock Day of week for Real Time Clock
Only Number of Fields: 7 4: Thursday current date
5: Friday
6: Saturday
Default:
NOTICE
If an address or bit is not listed in this table, it is not implemented.
NOTICE
The external device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.
NOTICE
40005 is not implemented.
ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
Frequency Load 40266 40326 40386 40446 40506 0.1 Hz
Total pf Load 40267 40327 40387 40447 40507 0.00005 pf
Total kVA Load 40268 40328 40388 40448 40508 kVA
Total kW Load 40269 40329 40389 40449 40509 kW
Total kVAR Load 40270 40330 40390 40450 40510 kVAR
Volts ab Load 40271 40331 40391 40451 40511 Volts
Volts bc Load 40272 40332 40392 40452 40512 Volts
Volts ca Load 40273 40333 40393 40453 40513 Volts
Volts a Load 40274 40334 40394 40454 40514 Volts
Volts b Load 40275 40335 40395 40455 40515 Volt
Volts c Load 40276 40336 40396 40456 40516 Volts
Amps a Load 40277 40337 40397 40457 40517 Amps
Amps b Load 40278 40338 40398 40458 40518 Amps
Amps c Load 40279 40339 40399 40459 40519 Amps
Percent Amps a Load 40280 40340 40400 40460 40520 0.5 %
Percent Amps b Load 40281 40341 40401 40461 40521 0.5 %
Percent Amps c Load 40282 40342 40402 40462 40522 0.5 %
Frequency SRC1 40283 40343 40403 40463 40523 0.1 Hz
Total pf SRC1 40284 40344 40404 40464 40524 0.00005 PF
Total kVA SRC1 40285 40345 40405 40465 40525
Total kW SRC1 40286 40346 40406 40466 40526
Total kVAR SRC1 40287 40347 40407 40467 40527
Volts ab SRC1 40288 40348 40408 40468 40528
Volts bc SRC1 40289 40349 40409 40469 40529
Volts ca SRC1 40290 40350 40410 40470 40530
Volts a SRC1 40291 40351 40411 40471 40531
Volts b SRC1 40292 40352 40412 40472 40532 Volts
Volts c SRC1 40293 40353 40413 40473 40533
Amps a SCR1 40294 40354 40414 40474 40534 Amps
Amps b SCR1 40295 40355 40415 40475 40535
Amps c SRC1 40296 40356 40416 40476 40536
Percent Amps a SCR1 40297 40357 40417 40477 40537 0.5 %
Percent Amps b SCR1 40298 40358 40418 40478 40538 0.5 %
Percent Amps c SCR1 40299 40359 40419 40479 40539 0.5 %
ATS Raw Data ATS 1 ATS 2 ATS 3 ATS 4 ATS 5 Multiplier Units
Frequency SRC2 40300 40360 40420 40480 40540 0.1 Hz
Total pf SRC2 40301 40361 40421 40481 40541 0.00005 pf
Total kVA SRC2 40302 40362 40422 40482 40542 kVA
Total kW SRC2 40303 40363 40423 40483 40543 kW
Total kVAR SRC2 40304 40364 40424 40484 40544 kVAR
Volts ab SRC2 40305 40365 40425 40485 40545 Volts
Volts bc SRC2 40306 40366 40426 40486 40546 Volts
Volts ca SRC2 40307 40367 40427 40487 40547 Volts
Volts a SRC2 40308 40368 40428 40488 40548 Volts
Volts b SRC2 40309 40369 40429 40489 40549 Volts
Volts c SRC2 40310 40370 40430 40490 40550 Volts
Amps a SRC2 40311 40371 40431 40491 40551 Amps
Amps b SRC2 40312 40372 40432 40492 40552 Amps
Amps c SRC2 40313 40373 40433 40493 40553 Amps
Percent Amps a SRC2 40314 40374 40434 40494 40554 0.5 %
Percent Amps b SRC2 40315 40375 40435 40495 40555 0.5 %
Percent Amps c SRC2 40316 40376 40436 40496 40556 0.5 %
TABLE 13.
Digital State
0 Neutral
1 Source 1 Connected
2 Source 2 Connected
3 Source 1 and 2 Connected
TABLE 14.
Digital Mode
0 Test
1 Utility / Genset
2 Utility / Utility
3 Genset / Genset
TABLE 15.
ATS Raw Data ATS 6 ATS 7 ATS 8 ATS 9 ATS 10 Multiplier Units
Frequency SRC1 40583 40643 40703 40763 40823 0.1 Hz
Total pf SRC1 40584 40644 40704 40764 40824 0.00005 PF
Total kVA SRC1 40585 40645 40705 40765 40825 kVA
Total kW SRC1 40586 40646 40706 40766 40826 kW
Total kVAR SRC1 40587 40647 40707 40767 40827 kVAR
Volts bc SRC1 40588 40648 40708 40868 40828 Volts
Volts bc SRC1 40589 40649 40709 40869 40829 Volts
Volts ca SRC1 40590 40650 40710 40870 40830 Volts
Volts a SRC1 40591 40651 40711 40871 40831 Volts
Volts b SRC1 40592 40652 40712 40872 40832 Volts
Volts c SRC1 40593 40653 40713 40873 40833 Volts
Amps a SCR1 40594 40654 40714 40874 40834 Amps
Amps b SCR1 40595 40655 40715 40875 40835 Amps
Amps c SRC1 40596 40656 40716 40876 40836 Amps
Percent Amps a SCR1 40597 40657 40717 40777 40837 0.5 %
Percent Amps b SCR1 40598 40658 40718 40778 40838 0.5 %
Percent Amps c SCR1 40599 40659 40719 40779 40839 0.5 %
Frequency SRC2 40600 40660 40720 40780 40840 0.1 Hz
Total pf SRC2 40601 40661 40721 40781 40841 0.00005 pf
Total KVA SRC2 40602 40662 40722 40782 40842 kVA
Total kW SRC2 40603 40663 40723 40783 40843 kW
Total KVAR SRC2 40604 40664 40724 40784 40844 kVAR
Volts ab SRC2 40605 40665 40725 40785 40845 Volts
Volts bc SRC2 40606 40666 40726 40786 40846 Volts
Volts ca SRC2 40607 40667 40727 40787 40847 Volts
Volts a SRC2 40608 40668 40728 40788 40848 Volts
Volts b SRC2 40609 40669 40729 40789 40849 Volts
Volts c SRC2 40610 40670 40730 40790 40850 Volts
Amps a SRC2 40611 40671 40731 40791 40851 Amps
Amps b SRC2 40612 40672 40732 40792 40852 Amps
Amps c SRC2 40613 40673 40733 40793 40853 Amps
Percent Amps a SRC2 40614 40674 40734 40794 40854 0.5 %
Percent Amps b SRC2 40615 40675 40735 40795 40855 0.5 %
Percent Amps c SRC2 40616 40676 40736 40796 40856 0.5 %
NOTICE
The external device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.
NOTICE
40005 is unused.
Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Total kW 40017 40072 40127 40182 40237
NFPA 110 (See Table 3 on page
40018 40073 40128 40183 40238
11)
NFPA Extended (See Table 4 on
40019 40074 40129 40184 40239
page 11)
Frequency 40020 40075 40130 40185 40240 0.1 Hz
Total pf 40021 40076 40131 40186 40241 0.00005 pf
Total kVA 40022 40077 40132 40187 40242 kVA
Total kW 40023 40078 40133 40188 40243 kW
Total kVAR 40024 40079 40134 40189 40244 kVAR
Volts ab 40025 40080 40135 40190 40245 Volts
Volts bc 40026 40081 40136 40191 40246 Volts
Volts ca 40027 40082 40137 40192 40247 Volts
Volts a 40028 40083 40138 40193 40248 Volts
Volts b 40029 40084 40139 40194 40249 Volt
Volts c 40030 40085 40140 40195 40250 Volts
Amps a 40031 40086 40141 40196 40251 Amps
Amps b 40032 40087 40142 40197 40252 Amps
Amps c 40033 40088 40143 40198 40253 Amps
Percent Amps a 40034 40089 40144 40199 40254 0.5 %
Percent Amps b 40035 40090 40145 40200 40255 0.5 %
Percent Amps c 40036 40091 40146 40201 40256 0.5 %
Battery Voltage 40037 40092 40147 40202 40257 0.1 Volts
Oil Pressure 40038 40093 40148 40203 40258 0.1 kPa
Oil Temp 40039 40094 40149 40204 40259 0.1 Deg K
Coolant Temp 40040 40095 40150 40205 40260 0.1 Deg K
Fuel Rate 40041 40096 40151 40206 40261 0.001 GPH
Engine RPM 40042 40097 40152 40207 40262 RPM
Engine Starts 40043 40098 40153 40208 40263 Starts
Engine Runtime High 40044 40099 40154 40209 40264
Engine Runtime Low 40045 40100 40155 40210 40265 0.1 Sec
Total kWH High 40046 40101 40156 40211 40266
Total kWH Low 40047 40102 40157 40212 40267 KWH
Total Fuel High 40048 40103 40158 40213 40268
Total Fuel Low 40049 40104 40159 40214 40269 0.01 GAL
Generator Raw Data Gen 1 Gen 2 Gen 3 Gen 4 Gen 5 Multiplier Units
Bus Frequency 40050 40105 40160 40215 40270 0.1 Hz
Bus Volts ab 40051 40106 40161 40216 40271 Volts
Bus Volts bc 40052 40107 40162 40217 40272 Volts
Bus Volts ca 40053 40108 40163 40218 40273 Volts
Bus Volts a 40054 40109 40164 40219 40274 Volts
Bus Volts b 40055 40110 40165 40220 40275 Volts
Bus Volts c 40056 40111 40166 40221 40276 Volts
Customer Faults 40057 40112 40167 40222 40277
Network Faults 40058 40113 40168 40223 40278
Customer Faults 40059 40114 40169 40224 40279
ES State (See Table 17 on page
40060 40115 40170 40225 40280
284)
Load Share State (See Table 18 on
40061 40116 40171 40226 40281
page 285)
Load Govern State kW (See Table
40062 40117 40172 40227 40282
22 on page 286)
Load Govern State kVAR (SeeTable
40063 40118 40173 40228 40283
20 on page 285)
TABLE 16.
Digital State
0 Stopped
1 Start Pending
2 Warm-up at Idle
3 Running
4 Cooldown at Rated
5 Cooldown at idle
TABLE 17.
Digital ES State
0 Standby
1 Dead Bus Close
2 Synchronizing
Digital ES State
3 Load Share
4 Load Govern
TABLE 18.
TABLE 19.
TABLE 20.
TABLE 21.
TABLE 22.
NOTICE
If an address or bit is not listed in this table it is not implemented.
FAULT CODE 3697 - Engine Control Module Calibration Memory - Bad Intelligent Device or
Component
Associated Procedures
Procedure Title Procedure Number Service Model Name Bulletin Number
Engine Control Module Refer to Procedure 019-031 ISF2.8 CM2220 EC2CF 4310641
Engine Control Module Refer to Procedure 019-031 ISF2.8 CM2220 E ISF2.8 4022178
CM2220 AN
ISF2.8 CM2220 IAN
Engine Control Module Refer to Procedure 019-031 ISF3.8 CM2220 ISF3.8 4021704
CM2220 AN
ISF3.8 CM2220 IAN
Engine Control Module Refer to Procedure 019-031 ISF2.8 CM2220 F122 5467376
Engine Control Module Refer to Procedure 019-031 ISF3.8 CM2220 F103 4310839
Engine Control Module Refer to Procedure 019-031 ISB4.5, ISB6.7, ISD4.5, and 4022188
ISD6.7 CM2150 SN
Engine Control Module Refer to Procedure 019-031 ISV5.0 CM3230 V104 4367291
Engine Control Module Refer to Procedure 019-031 ISL8.9 CM2150 SN 4022190
Engine Control Module Refer to Procedure 019-031 ISM11 CM876 SN 4022196
Engine Control Module Refer to Procedure 019-031 ISZ13 CM2150 4022133
Engine Control Module Refer to Procedure 019-031 ISX15 CM2250 4022250
GX CM2250
Engine Control Module Refer to Procedure 019-031 ISX12/ISX11.9 CM2250 2883445
Engine Control Module Refer to Procedure 019-031 QSL9 CM2250 4022256
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2250 4022255
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2250 EC 2883621
Engine Control Module Refer to Procedure 019-031 QSB3.3 CM2250 EC 2883647
Engine Control Module Refer to Procedure 019-031 QSX15 CM2250 ECF 2883557
Engine Control Module Refer to Procedure 019-031 PowerGen QSX15 CM2250 4310661
ECF
Engine Control Module Refer to Procedure 019-031 PowerGen QSX15 CM2250 4310664
Engine Control Module Refer to Procedure 019-031 QSX11.9 CM2250 ECF 2883561
Engine Control Module Refer to Procedure 019-031 ISB6.7 CM2350 B101 2883567
Engine Control Module Refer to Procedure 019-031 ISL9 CM2350 L101 4310787
Engine Control Module Refer to Procedure 019-031 ISX12 CM2350 X102 4310646
Engine Control Module Refer to Procedure 019-031 ISX15 CM2350 X101 4310641
Engine Control Module Refer to Procedure 019-031 ISX15 CM2250 SN 4310736
Engine Control Module Refer to Procedure 019-031 ISB4.5 CM2350 B104 4332646
Engine Control Module. Refer to Procedure 019-031 ISB6.7 CM2350 B103 4332641
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2350 B105 4332778
Engine Control Module Refer to Procedure 019-031 QSL9 CM2350 L102 4332796
Engine Control Module Refer to Procedure 019-031 ISB/ISD4.5 CM2150 B119 4358465
Engine Control Module Refer to Procedure 019-031 ISB/ISD6.7 CM2150 B120 4358470
Engine Control Module Refer to Procedure 019-031 ISL8.9 CM2350 L110 4358475
Engine Control Module Refer to Procedure 019-031 ISF3.8 CM2220 F110 4358480
Engine Control Module Refer to Procedure 019-031 QSL9 M CM2250 L106 4358343
Engine Control Module Refer to Procedure 019-031 QSZ13 CM2150 Z101 4358364
Engine Control Module Refer to Procedure 019-031 QSZ13 CM2150 Z102 4358369
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2350 B112 4358498
Associated Procedures
Procedure Title Procedure Number Service Model Name Bulletin Number
Engine Control Module Refer to Procedure 019-031 QSF2.8 CM2880 F105 4358561
Engine Control Module Refer to Procedure 019-031 ISL9 CM2350 L111 4367223
Engine Control Module Refer to Procedure 019-031 QSB4.5 CM2350 B106 4367376
Engine Control Module Refer to Procedure 019-031 QSF3.8 CM2350 F107 4367316
Engine Control Module Refer to Procedure 019-031 QSG12 CM2350 G110 4367323
Engine Control Module Refer to Procedure 019-031 QSF2.8 CM2880 F114 4383734
Engine Control Module Refer to Procedure 019-031 ISF2.8 CM2220 F117 4388578
Engine Control Module Refer to Procedure 019-031 QSL9 CM2350 L107 4367386
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2250 B128 4388601
Engine Control Module Refer to Procedure 019-031 QSL9 CM2250 L115 4388626
Engine Control Module Refer to Procedure 019-031 QSF3.8 CM2350 F118 4388708
Engine Control Module Refer to Procedure 019-031 QSF3.8 CM2350 F119 4388703
Engine Control Module Refer to Procedure 019-031 ISF3.8 CM2220 F116 4383664
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2350 B130 4388668
Engine Control Module Refer to Procedure 019-031 QSL9 CM2350 L118 4388673
Engine Control Module Refer to Procedure 019-031 QSB4.5 CM2350 B122 4388767
Engine Control Module Refer to Procedure 019-031 ISF2.8 CM2220 F126 5411159
Engine Control Module Refer to Procedure 019-031 X15 CM2350 X114B 5411181
Engine Control Module Refer to Procedure 019-031 X15 CM2350 X116B 5411186
Engine Control Module Refer to Procedure 019-031 B6.7 CM2350 B121B 5411223
Engine Control Module Refer to Procedure 019-031 ISB6.7 CM2350 B142 5411131
Engine Control Module Refer to Procedure 019-031 QSX15 CM2250 X115 4388739
Engine Control Module Refer to Procedure 019-031 QSB4.5 CM2250 B131 4388774
Engine Control Module Refer to Procedure 019-031 QSB3.3 CM2250 B137 5411058
Engine Control Module Refer to Procedure 019-031 L9 CM2350 L116B 5411330
Engine Control Module Refer to Procedure 019-031 F3.8 CM350 F120B 5411237
Engine Control Module Refer to Procedure 019-031 B4.5 CM2350 B129B 5411247
Engine Control Module Refer to Procedure 019-031 B6.7 CM2350 B135B 5411257
Engine Control Module Refer to Procedure 019-031 B4.5 CM2350 B147B 5411252
Engine Control Module Refer to Procedure 019-031 B6.7 CM2350 B148B 5411262
Engine Control Module Refer to Procedure 019-031 L9 CM2350 L119B 5411267
Engine Control Module Refer to Procedure 019-031 QSB6.7 CM2350 B145 5411273
Engine Control Module Refer to Procedure 019-031 QSL9 CM2350 L122 5411278
Engine Control Module Refer to Procedure 019-031 QSB4.5 CM2350 B144 5411382
Engine Control Module Refer to Procedure 019-031 L9 CM2350 L123B 5411465
Engine Control Module Refer to Procedure 019-031 QSF2.8 CM2880 F124 5411484
Engine Control Module Refer to Procedure 019-031 QSF2.8 CM2880 F131 5411489
Engine Control Module Refer to Procedure 019-031 ISF4.5 CM2220 F123 5411320
Engine Control Module Refer to Procedure 019-031 QSF3.8 CM2350 F125 5411494
Engine Control Module Refer to Procedure 019-031 QSX15 CM2350 X118 5467247
Engine Control Module Refer to Procedure 019-031 QSG12 CM2350 G113 5467252
Engine Control Module Refer to Procedure 019-031 R2.8 CM2220 R101B 5467556
Engine Control Module Refer to Procedure 019-031 F3.8 CM2350 F132B 5467327
Engine Control Module Refer to Procedure 019-031 ISB5.9 CM2880 B110 4332883
Engine Control Module Refer to Procedure 019-031 B6.7 CM2350 B136C 5504194
Engine Control Module Refer to Procedure 019-031 L9 CM2350 L120C 5504199
Engine Control Module Refer to Procedure 019-031 ISF3.8 CM2220 F134B 5504165
Associated Procedures
Procedure Title Procedure Number Service Model Name Bulletin Number
Engine Control Module Refer to Procedure 019-031 F3.8 CM2350 F133C 5504278
Engine Control Module Refer to Procedure 019-031 F3.8 CM2350 F128C 5504273
Engine Control Module Refer to Procedure 019-031 B4.5 CM2350 B145C 5504283
Engine Control Module Refer to Procedure 019-031 F2.8 CM2620 F135B 5504616
Engine Control Module Refer to Procedure 019-031 F2.8 CM2620 F136B 5504621
Engine Control Module Refer to Procedure 019-031 F3.8 CM2620 F137B 5579617
Engine Control Module Refer to Procedure 019-031 F4.5 CM2620 F139B 5579622
TROUBLESHOOTING STEPS
STEP 1: Check the fault codes.
STEP 1A: Check for active fault codes.
Condition:
• Turn keyswitch ON.
• Connect INSITE™ electronic servicetool.
Action Specification/Repair Next Step
Check the fault codes. Fault Code 111 active? Fault Code 111
• Use INSITE™ electronic service YES troubleshooti ng tree.
tool to read the fault codes. Fault Code 111 active? 2A
NO
Condition:
• Connect all components.
• Turn keyswitch ON.
• Connect INSITE™ electronic service tool.
Action Specification/Repair Next Step
Use INSITE™ electronic service tool Fault Code 3697 active after 2B
to calibrate the ECM with the latest calibrating the ECM?
engine calibration. Refer to the YES
calibration revisions listed in the ECM Repair:
Calibration Revision History to find
Replace the ECM. Refer to Procedure
the latest calibration available for the
engine being serviced. 019-031 in the Associated Procedures
Table.
• Use INSITE™ electronic service
tool to find the present ECM Fault Code 3697 active after 2B
code and revision number in the calibrating the ECM?
ECM. The ECM code and NO
revision number are found in the
Calibration Information section
of System ID and Dataplate in
Features and Parameters.
NOTICE
If an address or bit is not listed in this table it is not implemented.
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Logical
MB logical Read / Offset: 0 address to be
42001 Upper Limit: Communications
Read Address Write read via
Size (bits):16 65535.000 Modbus
Sign: U Default: 0
Multiplier:
Unit: NA
1.000000000000 Logical data to
MB Logical Read Lower Limit:
42002 Offset: 0 be read via Communications
Read Data Only Upper Limit:
Size (bits): 32 Modbus
Default:
Sign: U
Save
configuration
parameters or
adjustments to
non-volatile
memory.
0: Do Nothing Perform Save
Save Read / Controller
42004 1: Save Trims Trims after all
Adjustments Write Information
Default: Do Nothing configurations
have been
updated. Do
not save trims
unless a
change has
occurred.
Multiplier:
Unit: Volts
1.000000000000
Genset L1N Read Lower Limit: Volts Generator set
42018 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L1N voltage
Size (bits): 16
Default
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L2N Read Lower Limit: Volts Generator set
42019 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L2N voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
1.000000000000
Genset L3N Read Lower Limit: Volts Generator set
42020 Offset: 0 Voltage
Voltage Only Upper Limit: Volts L3N voltage
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: Volts
Genset LN 1.000000000000 Generator set
Read Lower Limit: Volts
42021 Average Offset: 0 LN average Voltage
Only Upper Limit: Volts
Voltage Size (bits): 16 voltage
Default:
Sign: U
Multiplier: Utility L1
Unit: % current as % of
Utility L1 .100000000000
Read Lower Limit: % utility total
42162 Current Offset: 0 Current
Only Upper Limit: % current
Percent Size (bits): 16
Default: capacity - used
Sign: U by bargraph
Multiplier: Utility L2
Unit: % current as % of
Utility L2 .100000000000
Read Lower Limit: % utility total
42163 Current Offset: 0 Current
Only Upper Limit: % current
Percent Size (bits): 16
Default: capacity - used
Sign: U by bargraph
Multiplier: Utility L3
Unit: % current as
Utility L3 .100000000000
Read Lower Limit: % as % of utility
42164 Current Offset: 0 Current
Only Upper Limit: % total current
Percent Size (bits): 16
Default: capacity - used
Sign: U by bargraph
Multiplier: Utility total kW
Unit: %
.100000000000 as percent of
Utility Total kW Read Lower Limit %
42165 Offset: 0 total utility Power
Percent Only Upper Limit: %
Size (bits): 16 capacity - used
Default: by bargraph
Sign: S
Utility
Multiplier: frequency as
Unit: %
Utility .100000000000 percent of
Read Lower Limit: %
42166 Frequency Offset: 0 system Frequency
Only Upper Limit: %
Percent Size (bits): 16 frequency -
Default: used by
Sign: U
bargraph
Multiplier:
Unit: %
.100000000000
Utility L1L2 Read Lower Limit: % Utility L1L2
42167 Offset: 0 Voltage
Voltage % Only Upper Limit: % voltage %
Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: %
.100000000000
Utility L2L3 Read Lower Limit: % Utility L2L3
42168 Offset: 0 Voltage
Voltage % Only Upper Limit: % voltage %
Size (bits): 16
Default:
Sign: U
Multiplier: Engineering
kW Load Unit: %
.010000000000 units value for
Setpoint Engr Read Lower Limit: %
42222 Offset: 0 the kW load Analog Inputs
Units Display Only Upper Limit: %
Size (bits): 16 setpoint analog
Value Default:
Sign: S input
Faults have
0: Inactive occurred which
System Read prevent normal System
42228 1: Active
Lockout Status Only system Information
Default: operation;
reset faults
0: Open
1: Closed Indicates the
Breaker 1 Read Load Add Shed
42229 position status
Position Only 2: Not Available Control
of breaker 1
Default: Not Available
0: Open
1: Closed Indicates the
Breaker 2 Read Load Add Shed
42230 position status
Position Only 2: Not Available Control
of breaker 2
Default: Not Available
0: Open
1: Closed Indicates the
Breaker 3 Read Load Add Shed
42231 position status
Position Only 2: Not Available Control
of breaker 3
Default: Not Available
0: Open
1: Closed Indicates the
Breaker 4 Read Load Add Shed
42232 position status
Position Only 2: Not Available Control
of breaker 4
Default: Not Available
0: Do Nothing Indicates
Add Level 2 Read Load Add Shed
42253 1: Add Level status of add
Command Only Control
Default: Do Nothing level 2
0: Do Nothing Indicates
Add Level 3 Read Load Add Shed
42254 1: Add Level status of add
Command Only Control
Default: Do Nothing level 3
0: Do Nothing Indicates
Add Level 4 Read Load Add Shed
42255 1: Add Level status of add
Command Only Control
Default: Do Nothing level 4
0: Do Nothing Indicates
Add Level 5 Read Load Add Shed
42256 1: Add Level status of add
Command Only Control
Default: Do Nothing level 5
0: Do Nothing Indicates
Add Level 6 Read Load Add Shed
42257 1: Add Level status of add
Command Only Control
Default: Do Nothing level 6
0: Do Nothing Indicates
Shed Level 1 Read Load Add Shed
42258 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 1
0: Do Nothing Indicates
Shed Level 2 Read Load Add Shed
42259 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 2
0: Do Nothing Indicates
Shed Level 3 Read Load Add Shed
42260 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 3
0: Do Nothing Indicates
Shed Level 5 Read Load Add Shed
42262 1: Add Level status of shed
Command Only Control
Default: Do Nothing level 5
0: Do Nothing Indicates if
Restored Shed
Read shed level 1 Load Add Shed
42274 Level 1 1: Add Level
Only has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restored Shed
Read shed level 2 Load Add Shed
42275 Level 2 1: Add Level
Only has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restored Shed
Read shed level 3 Load Add Shed
42276 Level 3 1: Add Level
Only has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restored Shed
Read shed level 4 Load Add Shed
42277 Level 4 1: Add Level
Only has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restored Shed
Read shed level 5 Load Add Shed
42278 Level 5 1: Add Level
Only has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates add
Add Load 1 Read Load Add Shed
42279 1: Add Level command for
Command Only Control
Default: Do Nothing load 1
Multiplier: Engineering
Unit: VDC
Battery Voltage .010000000000 units value for
Read Lower Limit: VDC
42291 Engr Units Offset: 0 the battery Analog Inputs
Only Upper Limit: VDC
Display Value Size (bits): 16 voltage analog
Default Input
Sign: U
Multiplier: Voltage level
kVAR Master Unit: VDC
.010000000000 commanded to
Load Control Read Lower Limit: VDC
42292 Offset: 0 kVAR Master Analog Inputs
Output Only Upper Limit: VDC
Size (bits): 16 load control
Predictor Value Default
Sign: S analog output
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 10 kW Read/ Offset: 0 Sets generator System
42314 Upper Limit:
Rating Write 10 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 11 kW Read/ Sets generator System
42315 Offset: 0 Upper Limit:
Rating Write 11 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Multiplier: Unit: kW
1.000000000000 Lower Limit: .000 kW
Genset 12 kW Read/ Offset: 0 Sets generator System
42316 Upper Limit:
Rating Write 12 kW rating Information
Size (bits): 16 32000.000 kW
Sign: S Default: 0
Unit: Seconds
Multiplier:
.100000000000 Lower Limit: .000 Set the
Programmed Seconds
Read/ Offset: 0 programmed
42317 Transition PTC Timers
Write Upper Limit: 60.000 transition time
Delay (TDPT) Size (bits): 16
Seconds delay
Sign: U
Default: 3
Unit: Seconds
Multiplier:
.100000000000 Lower Limit: .000
Seconds Sets the
Transfer Delay Read/ Offset: 0
42318 transfer time PTC Timers
(TDNE) Write Upper Limit: 120.000
Size (bits): 16 delay
Seconds
Sign: U
Default: 10
Unit: Seconds
Multiplier:
.100000000000 Lower Limit: .000
Seconds Sets the
Retransfer Read/ Offset: 0
42319 transfer time PTC Timers
Delay (TDEN) Write Upper Limit: 1800.000
Size (bits): 16 delay
Seconds
Sign: U
Default: 600
0: Inactive Use to
Clear Fault Read/ completely Fault and Event
42342 1: Active
History Table Write clear the fault Info
Default: Inactive history table
Allows protocol
0: PCCNet of the PCCNet
Port Protocol Read/ port to be
42359 1: MON Communications
Selection Write changed to
Default: PCCNet MON for
troubleshooting
Multiplier: Proportional
Unit: NA gain for kW
1.00000000000
Read/ Lower Limit: .000 closed loop Master Load
42414 kW Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 60
Sign: U paralleling
Multiplier: Integral gain
Unit: NA
1.00000000000 for kW closed
Read/ Lower Limit: .000 Master Load
42415 kW KI Offset: 0 loop control in
Write Upper Limit: 255.000 Control
Size (bits): 16 extended
Default: 60 paralleling
Sign: U
Multiplier: Proportional
Unit: NA gain for kVAR
.100000000000
Read/ Lower Limit: .000 closed loop Master Load
42416 kVAR Kp Offset: 0
Write Upper Limit: 1000.000 control in Control
Size (bits): 16 extended
Default: 120
Sign: U paralleling
0: Sunday
1: Monday
2: Tuesday Use to adjust
Scheduler 3: Wednesday start day of
Read/ System
42422 Program x week for the
Write 4: Thursday Scheduler
Start Day selected
5: Friday program
6: Saturday
Default: Sunday
Multiplier: Unit: hour
1.00000000000 Lower Limit: .000 hour Use to adjust
Scheduler
Read/ Offset: 0 start hour for System
42423 Program x Upper Limit: 23.000
Write the selected Scheduler
Start Hour Size (bits): 16 hour program
Sign: U Default: 0
Unit: minute
Multiplier:
1.00000000000 Lower Limit: .000 Use to adjust
Scheduler minute
Read/ Offset: 0 start minute for System
42424 Program x
Write Upper Limit: 59.000 the selected Scheduler
Start Minute Size (bits): 16
minute program
Sign: U
Default: 0
Multiplier: Unit: hour
1.00000000000 Lower Limit: .000 hour Use to adjust
Scheduler
Read/ Offset: 0 duration hours System
42425 Program x Upper Limit: 23.000
Write for the selected Scheduler
Duration Hours Size (bits): 16 hour program
Sign: U Default: 0
Unit: minute
Multiplier: Use to adjust
Scheduler 1.000000000000 Lower Limit: .000:
minute the duration
Exception x Read/ Offset: 0 System
42436 minutes of the
Duration Write Upper Limit: 59.000: Scheduler
Size (bits): 16 selected
Minutes minute
Sign: U exception
Default: 0
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Genset PT Volts Generator set
Read/ Offset: 0
42440 Primary PT primary AC Setup
Write Upper Limit:
Voltage Size(bits): 16 voltage
45000.000 Volts
Sign: U
Default: 480
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Genset PT Volts Generator set
Read/ Offset: 0
42441 Secondary PT secondary AC Setup
Write Upper Limit: 500.000
Voltage Size(bits): 16 voltage
Volts
Sign: U
Default: 120
Unit: Amps
Multiplier:
1.000000000000 Lower Limit: 5.000
Genset CT Amps Generator set
Read/ Offset: 0
42442 Primary CT primary AC Setup
Write Upper Limit:
Current Size(bits): 16 current
25000.000 Volts
Sign: U
Default: 100
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Utility PT Volts
Read/ Offset: 0 Utility PT
42445 Primary AC Setup
Write Upper Limit: primary voltage
Voltage Size(bits): 16
45000.000 Volts
Sign: U
Default: 480
Unit: Volts
Multiplier:
1.000000000000 Lower Limit: 100.000
Utility PT Volts Utility PT
Read/ Offset: 0
42446 Secondary secondary AC Setup
Write Upper Limit: 500.000
Voltage Size(bits): 16 voltage
Volts
Sign: U
Default: 120
Unit: Amps
Multiplier:
1.000000000000 Lower Limit: 5.000
Utility CT Amps
Read/ Offset: 0 Utility CT
42447 Primary AC Setup
Write Upper Limit: primary current
Current Size(bits): 16
25000.000 Amps
Sign: U
Default: 100
Generator set
Multiplier: Unit: kW kW capacity
Load Add Shed 1.000000000000 Lower Limit: .000 kW that must be
Required Read/ Offset: 0 Load Add Shed
42449 Upper Limit: online to start
Online Write Control
Size(bits): 16 32767.000 kW timed load
Capacity
Sign: S Default: 0 add : 0
disables this
Sets how much
Multiplier: Unit: kW capacity must
Load Demand 1.000000000000 Lower Limit: .000 kW always be
Minimum Read/ Offset: 0 Load Demand
42450 Upper Limit: online
Online Write Control
Size(bits): 16 32767.000 kW regardless of
Capacity
Sign: S Default: 0 what the load
is
0: 12V DC voltage
Nominal Read/ Battery Voltage
42454 1: 24V provided to the
Battery Voltage Write Protection
Default: 24V control
Unit: VDC
Multiplier:
.0100000000000 Lower Limit: 28.000
24V High VDC Sets 24V high
Read/ Offset: 0 Battery Voltage
42455 Battery Voltage battery voltage
Write Upper Limit: 34.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 32
Unit: VDC
Multiplier:
.0100000000000 Lower Limit: 22.000
24V Low VDC Sets 24V low
Read/ Offset: 0 Battery Voltage
42456 Battery Voltage battery voltage
Write Upper Limit: 26.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 24
Unit: VDC
Multiplier:
.0100000000 Lower Limit: 14.000
12V High VDC Sets 12V high
Read/ Offset: 0 Battery Voltage
42457 Battery Voltage battery voltage
Write Upper Limit: 17.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 16
Unit: VDC
Multiplier:
.010000000000 Lower Limit: 11.000
12 V Low VDC Sets 12V low
Read/ Offset: 0 Battery Voltage
42458 Battery Voltage battery voltage
Write Upper Limit: 13.000 Protection
Threshold Size(bits): 16 fault threshold
VDC
Sign: U
Default: 12
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42470 Upper Limit: Discrete Outputs
Output7 Code Write configurable
Size(bits): 16 65535.000 output 7
Sign: U Default: 0
Multiplier: Unit: NA
1.000000000000 Lower Limit: .000 Event or fault
Configurable Read/ Offset: 0 code tied to
42471 Upper Limit: Discrete Outputs
Output8 Code Write configurable
Size(bits): 16 65535.000 output 8
Sign: U Default: 343
0: Stop State of
Extended
Read / extended
42600 Parallel Start 1: Start Discrete Inputs
Write parallel start
Vol Default: Stop volatile input
0: Inactive State of
Synchronizer Read / synchronizer
42601 1: Active Discrete Inputs
Enable Vol Write enable volatile
Default: Inactive input
0: Inactive State of utility
Utility Source Read /
42602 1: Active source failure Discrete Inputs
Fail Vol Write
Default: Inactive volatile input
0: No Inhibit State of
Transfer Inhibit Read /
42603 1: Inhibit transfer inhibit Discrete Inputs
Vol Write
Default: No Inhibit volatile input
0: No Inhibit State of
Retransfer Read / retransfer
42604 1: Inhibit Discrete Inputs
Inhibit Vol Write inhibit volatile
Default: No Inhibit input
0: No Inhibit State of
Gen CB Inhibit Read / generator CB
42605 1: Inhibit Discrete Inputs
Vol Write inhibit volatile
Default: No Inhibit input
0: No Inhibit State of utility
Utility CB Read /
42606 1: Inhibit CB inhibit Discrete Inputs
Inhibit Vol Write
Default: No Inhibit volatile input
0: Auto State of
Auto/Manual Read/
42607 1: Manual auto/manual Discrete Inputs
Vol Write
Default: Auto volatile input
0: No Override State of
Read/
42610 Override Vol 1: Override override Discrete Inputs
Write
Default: No Override volatile input
0: Stop State of
Extended
Read extended
42611 Parallel Start 1: Start Discrete Inputs
Only parallel start
Sw Default: input
0: Inactive State of
Synchronizer Read
42612 1: Active synchronizer Discrete Inputs
Enable Sw Only
Default: enable input
0: No Inhibit Status of
Transfer Inhibit Read
42614 1: Inhibit transfer inhibit Discrete Inputs
Sw Only
Default: input
0: No Inhibit Status of
Retransfer Read
42615 1: Inhibit retransfer Discrete Inputs
Inhibit Sw Only
Default: inhibit input
0: No Inhibit State of
Gen CB Inhibit Read
42616 1: Inhibit generator CB Discrete Inputs
Sw Only
Default: inhibit input
0: No Inhibit
Utility CB Read State of utility
42617 1: Inhibit Discrete Inputs
Inhibit Sw Only CB inhibit input
Default:
0: Auto
Auto/Manual Read State of auto /
42618 1: Manual Discrete Inputs
Sw Only manual input
Default:
0: Stop
Read State of test
42619 Test Start Sw 1: Start Discrete Inputs
Only start input
Default:
0: No Reset
Read State of fault
42620 Fault Reset Sw 1: Reset Discrete Inputs
Only reset input
Default:
0: No Override
Read State of
42621 Override Sw 1: Override Discrete Inputs
Only override input
Default:
0: No Inhibit Indicates state
Read
42622 Master Inhibit 1: Inhibit of Master Priority Control
Only
Default: priority inhibit
0: Inactive State of
Genset CB Read
42623 1: Active generator CB Discrete Inputs
Tripped Sw Only
Default: tripped input
0: Inactive State of
Genset CB Read/ generator CB
42624 1: Active Discrete Inputs
Tripped Vol Write tripped volatile
Default: Inactive input
0: Inactive State of Utility
Utility CB Read
42625 1: Active CB tripped Discrete Inputs
Tripped Sw Only
Default: input
0: L1-L2-L3
Genset Phase Read Generator set
42627 1: L1-L3-L2 Phase
Rotation Only phase rotation
Default:
0: L1-L2-L3
Utility Phase Read Utility phase
42628 1: L1-L3-L2 Phase
Rotation Only rotation
Default:
0: Breaker Open State of Gen1
Gen1 CB Read
42929 1: Breaker Closed CB position Discrete Inputs
Position Sw Only
Default: Open input
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42646 ATS 7 Position position status
Only 3: Source 2 Connected Control
of ATS 7
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
Read Load Add Shed
42647 ATS 8 Position position status
Only 3: Source 2 Connected Control
of ATS 8
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 11 Read Load Add Shed
42674 position status
Position Only 3: Source 2 Connected Control
of ATS 11
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 12 Read Load Add Shed
42675 position status
Position Only 3: Source 2 Connected Control
of ATS 12
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 13 Read Load Add Shed
42676 position status
Position Only 3: Source 2 Connected Control
of ATS 13
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 14 Read Load Add Shed
42677 position status
Position Only 3: Source 2 Connected Control
of ATS 14
4: Paralleled
Default: Not Available
0: Not Available
1: No Source Connected
2: Source 1 Connected Indicates
ATS 15 Read Load Add Shed
42678 position status
Position Only 3: Source 2 Connected Control
of ATS 15
4: Paralleled
Default: Not Available
0: No Connection Indicates
1: Connected overall state of
Read
42699 PCCNet Status the PCCNet Communications
Only 2: Connecting communication
Default: s bus
0: Gen Does Not Exist
1: Offline For load
Gen1 2: Waiting For Gen
Read demand use - Load Demand
42700 Availability
Only 3: Online indicates status Control
State
4: Failed of Gen1
Default:
0: Gen Does Not Exist 1: Offline
2: Waiting For Gen For load
Gen2
Read demand use - Load Demand
42701 Availability 3: Online
Only indicates status Control
State 4: Failed of Gen2
Default:
0: Gen Does Not Exist 1: Offline For load
Gen3 2: Waiting For Gen
Read demand use - Load Demand
42702 Availability
Only 3: Online 4: Failed indicates status Control
State
Default: of Gen3
Indicates how
Multiplier: many of the
Unit: NA
Total Number 1.000000000000 generator sets
Read Lower Limit: System
42717 of Gensets Offset: 0 are online
Only Upper Limit: Information
Online Size (bits): 16 which are
Default: sensed by CB
Sign: U
position
Multiplier: Difference
Unit: kW between
Total Spare 1.000000000000
Read Lower Limit: kW sensed online System
42718 Online Offset: 0
Only Upper Limit: kW capacity and Information
Capacity Size (bits): 16
Default: generator set
Sign: S bus total kW
Multiplier: Indicates kW
Unit: kW threshold for
Next Gen 1.000000000000
Read Lower Limit: kW generator bus Load Demand
42719 Shutdown Offset: 0
Only Upper Limit: kW at which next Control
Threshold Size (bits): 16
Default: generator set
Sign: S will restart
Indicates kW
Multiplier: threshold for
Unit: kW
Next Gen 1.000000000000 generator bus
Read Lower Limit: kW Load Demand
42720 Shutdown Offset: 0 at which the
Only Upper Limit: kW Control
Threshold Size (bits): 16 next generator
Default: set will load
Sign: S
demand stop
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Next Gen Read next to be Load Demand
42721 8: Gen9
Restart Only restarted if load Control
9: Gen10 conditions are
10: Gen11 met
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
Multiplier: Calculated kW
Unit: kW overload
Genset Bus 1.000000000000
Read Lower Limit: kW threshold System
42727 kW Overload Offset: 0
Only Upper Limit: kW based on Information
Status Size (bits): 16
Default: online capacity
Sign: S and % setting
Indicates
Genset Bus 0: No Overload whether
Read System
42728 kW Overload 1: Overload generator bus
Only Information
Status Default: is overloaded
based on kW
0: Off Indicates
1: No Load current run
Scheduler Run Read command System
42731 2: With Load
Command Only coming from Scheduler
3: Extended Parallel scheduler
Default: function
Multiplier:
Unit: NA
Modbus Bus 1.000000000000
Read Lower Limit: Modbus
42732 Message Offset: 0 Communications
Only Upper Limit: message count
Count Size (bits): 16
Default:
Sign: U
Multiplier:
Unit: NA
1.000000000000
Modbus CRC Read Lower Limit: Modbus CRC
42733 Offset: 0 Communications
Error Count Only Upper Limit: error count
Size (bits): 16
Default:
Sign: U
0: Normal
1: Set Clock Use to set
Read/
42738 Clock Mode clock and save Real Time Clock
Write 2: Save Clock setting
Default: Normal
Unit: year
Multiplier:
1.000000000000 Lower Limit: .000 year
Use to set or
Read/ Offset: 0 Upper Limit: 99.000
42739 Clock Year read current Real Time Clock
Write year
Size (bits): 16 year
Default: Read from
Sign: U
RTC chip
Unit: month
Multiplier: Lower Limit: 1.000
1.000000000000 month Use to set or
Read/ Offset: 0
42740 Clock Month Upper Limit: 12.000 read current Real Time Clock
Write
Size (bits): 16 month month
Sign: U Default: Read from
RTC chip
Unit: date
Multiplier: Lower Limit: 1.000
1.000000000000 date Use to set or
Read/ Offset: 0
42741 Clock Date Upper Limit: 31.000 read current Real Time Clock
Write
Size (bits): 16 date date
Sign: U Default: Read from
RTC chip
0: Do Nothing Indicates
Add Level 8 Read Load Add Shed
42763 1: Add Level status of add
Command Only Control
Default: Do Nothing level 8
0: Do Nothing Indicates
Add Level 9 Read Load Add Shed
42764 1: Add Level status of add
Command Only Control
Default: Do Nothing level 9
0: Do Nothing Indicates
Shed Level 6 Read Load Add Shed
42770 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 6
0: Do Nothing Indicates
Shed Level 7 Read Load Add Shed
42771 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 7
0: Do Nothing Indicates
Shed Level 8 Read Load Add Shed
42772 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 8
0: Do Nothing Indicates
Shed Level 9 Read Load Add Shed
42773 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 9
0: Do Nothing Indicates if
Restore Shed
Read shed level 6 Load Add Shed
42778 Level 6 1: Restore Level
Only has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed
Read/ shed level 7 Load Add Shed
42779 Level 7 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed
Read/ shed level 8 Load Add Shed
42780 Level 8 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed
Read/ shed level 9 Load Add Shed
42781 Level 9 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen5 Online Read hours Total online System
42782 Offset: 0
Time Only Upper Limit: time for Gen5 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0
Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen6 Online Read hours Total online System
42784 Offset: 0
Time Only Upper Limit: time for Gen6 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0
Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen7 Online Read hours Total online System
42786 Offset: 0
Time Only Upper Limit: time for Gen7 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0
Unit: hours
Multiplier:
.000277777780 Lower Limit: .000
Gen8 Online Read hours Total online System
42788 Offset: 0
Time Only Upper Limit: time for Gen8 Information
Size (bits): 32
1193046.000 hours
Sign: U
Default: 0
0: Gen1
1: Gen2
2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7 Indicates which
7: Gen8 generator set is
Read Load Demand
42814 GenI 8: Gen9 currently GenI
Only Control
9: Gen10 for load
10: Gen11 demand
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Default:
0: Do Nothing Indicates
Add Level 12 Read Load Add Shed
42823 1: Add Level status of add
Command Only Control
Default: Do Nothing level 12
0: Do Nothing Indicates
Add Level 13 Read Load Add Shed
42824 1: Add Level status of add
Command Only Control
Default: Do Nothing level 13
0: Do Nothing Indicates
Add Level 14 Read Load Add Shed
42825 1: Add Level status of add
Command Only Control
Default: Do Nothing level 14
0: Do Nothing Indicates
Add Level 15 Read Load Add Shed
42826 1: Add Level status of add
Command Only Control
Default: Do Nothing level 15
0: Do Nothing Indicates
Add Level 16 Read Load Add Shed
42827 1: Add Level status of add
Command Only Control
Default: Do Nothing level 16
0: Do Nothing Indicates
Add Level 17 Read Load Add Shed
42828 1: Add Level status of add
Command Only Control
Default: Do Nothing level 17
0: Do Nothing Indicates
Add Level 18 Read Load Add Shed
42829 1: Add Level status of add
Command Only Control
Default: Do Nothing level 18
0: Do Nothing Indicates
Shed Level 10 Read Load Add Shed
42838 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 10
0: Do Nothing Indicates
Shed Level 11 Read Load Add Shed
42839 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 11
0: Do Nothing Indicates
Shed Level 12 Read Load Add Shed
42840 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 12
0: Do Nothing Indicates
Shed Level 13 Read Load Add Shed
42841 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 13
0: Do Nothing Indicates
Shed Level 14 Read Load Add Shed
42842 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 14
0: Do Nothing Indicates
Shed Level 16 Read Load Add Shed
42844 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 16
0: Do Nothing Indicates
Shed Level 17 Read Load Add Shed
42845 1: Shed Level status of shed
Command Only Control
Default: Do Nothing level 17
0: Do Nothing Indicates if
Restore Shed
Read/ shed level 10 Load Add Shed
42854 Level 10 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed
Read/ shed level 11 Load Add Shed
42855 Level 11 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed
Read/ shed level 12 Load Add Shed
42856 Level 12 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed
Read/ shed level 13 Load Add Shed
42857 Level 13 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed
Read/ shed level 14 Load Add Shed
42858 Level 14 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed
Read/ shed level 15 Load Add Shed
42859 Level 15 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed
Read/ shed level 16 Load Add Shed
42860 Level 16 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
0: Do Nothing Indicates if
Restore Shed
Read/ shed level 17 Load Add Shed
42861 Level 17 1: Restore Level
Write has been Control
Command Default: Do Nothing restored
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen9 Online Read Hours Total online System
42862 Offset: 0
Time Only Upper Limit: time for Gen9 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen10 Online Read Hours Total online System
42864 Offset: 0
Time Only Upper Limit: time for Gen10 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: Hours
Multiplier:
.000277777780 Lower Limit: .000
Gen11 Online Read Hours Total online System
42866 Offset: 0
Time Only Upper Limit: time for Gen11 Information
Size (bits): 32
1193046.00 Hours
Sign: U
Default: 0
Unit: kVAR
Multiplier: Lower Limit: .000 Sets the base
1.000000000000 kVAR load kVAR
Genset Bus
Read Offset: 0 setpoint in Master Load
42945 kVAR Setpoint Upper Limit:
/Write 32bit in closed Control
32bit Size (bits): 32 2147483647.000 loop extended
Sign: S kVAR paralleling
Default: 0
Unit: kW
Multiplier:
1.000000000000 Lower Limit: Setpoint for
Genset -2147483648.000 kW
Read Offset: 0 generator set Master Load
42947 Unloaded
/Write Upper Limit: unloaded level Control
Level 32bit Size (bits): 32
2147483647.000 kW in 32bit
Sign: S
Default:50
Unit: kW Sets the peak
Multiplier:
1.000000000000 Lower Limit: shave kW
Utility Bus kW Read -2147483648.000 kW setpoint in Master Load
42949 Offset: 0
Setpoint 32bit /Write Upper Limit: 32bit in closed Control
Size (bits): 32 loop extended
2147483647.000 kW
Sign: S paralleling
Default: 100
Unit: kW sets the utility
Multiplier:
1.000000000000 Lower Limit: kW constraint
Utility Bus kW -2147483648.000 kW
Read / Offset: 0 level in 32bit Master Load
42951 Constraint
write Upper Limit: for base load Control
Level 32bit Size (bits): 32
2147483647.000 kW extended
Sign: S paralleling
Default: 100
Multiplier: Calculated kW
Unit: kW overload
Genset Bus 1.000000000000
Read Lower Limit: kW threshold in System
42977 kW Overload Offset: 0
Only Upper Limit: kW 32bit based on Information
Threshold 32bit Size(bits): 32
Default: online capacity
Sign: S and % setting
NOTICE
If an address or bit is not listed in this table it is not implemented.
Fault
Addr. Bit# System Name Event Name Response
Code
Utility Main Breaker Position Contact
42500 0 Fault Status Bitmap 1 1455 Warning
Warning
42500 1 Fault Status Bitmap 1 2396 Utility Main Breaker Fail To Close Warning Warning
42500 2 Fault Status Bitmap 1 2397 Utility Main Breaker Fail To Open Warning Warning
42500 3 Fault Status Bitmap 1 1219 Utility Main Breaker Tripped Warning Warning
42500 4 Fault Status Bitmap 1 1914 Utility Bus Phase Rotation Warning Warning
42500 5 Fault Status Bitmap 1 1912 Utility Bus Loss Of Phase Warning Warning
42500 6 Fault Status Bitmap 1 2331 Utility Bus Undervoltage Warning Warning
42500 7 Fault Status Bitmap 1 2358 Utility Bus Overvoltage Warning Warning
42500 8 Fault Status Bitmap 1 1223 Utility Bus Frequency Warning Warning
42500 21 Fault Status Bitmap 1 4137 Advanced Grid Protection Warning Warning
42500 22 Fault Status Bitmap 1 3924 Utility Reverse kW Warning Warning
42500 23 Fault Status Bitmap 1 2939 Modbus Communication Failure Warning Warning
42500 24 Fault Status Bitmap 1 2648 Remote IO Communication Failure Warning Warning
42500 25 Fault Status Bitmap 1 1689 Real Time Clock Power Interrupt Warning Warning
42500 26 Fault Status Bitmap 1 1335 AC Metering Out Of Range Warning Warning
42500 27 Fault Status Bitmap 1 1999 Maximum Parallel Time Warning Warning
42500 28 Fault Status Bitmap 1 343 Hardware Failure Warning Warning
42500 29 Fault Status Bitmap 1 1456 Synchronizer Output Limit Warning Warning
42500 30 Fault Status Bitmap 1 2416 Calibration Checksum Warning Warning
42500 31 Fault Status Bitmap 1 353 EEPROM Write Error Warning Warning
Genset Main Breaker Position Contact
42502 0 Fault Status Bitmap 2 1454 Warning
Warning
42502 1 Fault Status Bitmap 2 1452 Genset Main Breaker Fail To Close Warning Warning
42502 2 Fault Status Bitmap 2 1453 Genset Main Breaker Fail To Open Warning
42502 3 Fault Status Bitmap 2 1328 Genset Main Breaker Tripped Warning Warning
42502 4 Fault Status Bitmap 2 1915 Genset Bus Phase Rotation Warning Warning
42502 5 Fault Status Bitmap 2 1913 Genset Bus Loss Of Phase Warning Warning
42502 6 Fault Status Bitmap 2 1225 Genset Bus Undervoltage Warning Warning
42502 7 Fault Status Bitmap 2 1224 Genset Bus Overvoltage Warning Warning
42502 8 Fault Status Bitmap 2 1226 Genset Bus Frequency Warning Warning
42502 22 Fault Status Bitmap 2 441 Low Battery Voltage Warning Warning
42502 23 Fault Status Bitmap 2 442 High Battery Voltage Warning Warning
42502 24 Fault Status Bitmap 2 1541 Genset Failed To Come Online Warning Warning
Fault
Addr. Bit# System Name Event Name Response
Code
42502 25 Fault Status Bitmap 2 2647 Load Demand Setup Warning Warning
42502 26 Fault Status Bitmap 2 1444 Genset Bus Overload Warning Warning
42502 27 Fault Status Bitmap 2 1989 kW Load Control Output Limit Warning Warning
42502 28 Fault Status Bitmap 2 1991 kVAR Load Control Output Limit Warning Warning
42502 29 Fault Status Bitmap 2 1121 Failure To Disconnect Warning Warning
Synchronizer Phase Rotation Mismatch
42502 30 Fault Status Bitmap 2 1458 Warning
Warning
42502 31 Fault Status Bitmap 2 1457 Fail To Synchronize Warning Warning
42505 0 Fault Status Bitmap 1 1222 Not In Automatic Event Event
42505 1 Fault Status Bitmap 1 1483 Common Warning Event Event
42505 2 Fault Status Bitmap 1 2965 Genset Bus Available Event Event
42505 3 Fault Status Bitmap 1 2328 Utility Bus Available Event Event
42505 4 Fault Status Bitmap 1 2333 Genset Bus Connected Event Event
42505 5 Fault Status Bitmap 1 2332 Utility Bus Connected Event Event
42505 6 Fault Status Bitmap 1 2971 Test / Extended Parallel Event Event
42505 7 Fault Status Bitmap 1 1916 Synchronized Event Event
42505 8 Fault Status Bitmap 1 1534 Load Control Output Event Event
42505 9 Fault Status Bitmap 1 2781 Genset Source Unloaded Event Event
42505 10 Event Status Bitmap 1 2779 Utility Source Unloaded Event Event
42505 11 Event Status Bitmap 1 3226 Genset Bus Base Load Event Event
42505 12 Event Status Bitmap 1 3227 Utility Bus Peak Shave Event Event
NOTICE
If an address or bit is not listed in this table it is not implemented.
NOTICE
If an address or bit is not listed in this table it is not implemented.
PC500/550 (PC5xx)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40001 U ENUM 64= PC500/PC550
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40002 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40003 U Configurable from User Interface
Sensor assigned to Analog Input on No scaling is required. The scaled
40004 S NA
PC5xx value is displayed.
Sensor assigned to Discrete Input 1 on
40005 U NA
PC5xx
Sensor assigned to Discrete Input 2 on
40006 U NA
PC5xx
Sensor assigned to Discrete Output 1
40007 U NA
status on PC5xx
Sensor assigned to Discrete Output 2
40008 U NA
status on PC5xx
PC500/550 (Device 1)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40011 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40012 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40013 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40014 U ENUM
2=Not Communicating
Communications Error Counter 40015 U
PC500/550 (Device 4)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40041 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40042 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40043 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40044 U ENUM
2=Not Communicating
Communications Error Counter 40045 U
Last Successful Communication
40046 U Bitfield See Note 5
(Year, Month)
Last Successful Communication
40047 U Bitfield See Note 5
(Day, Hour, Minutes)
Last Successful Communication
40048 U Bitfield See Note 5
(Seconds, Milliseconds)
PC500/550 (Device 5)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40051 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
0=N/A, 1=3300, 2=2300, 4=1301,
Device Model 40052 U ENUM 8=1302, 16=2100, 32=3100,
64=3200, 128=3201
Modbus TCP Unit ID 40053 U Configurable from User Interface
0=Communicating,
Modbus Communication Status 40054 U ENUM
2=Not Communicating
Communications Error Counter 40055 U
Last Successful Communication See Note 5
40056 U Bitfield
(Year, Month)
Last Successful Communication See Note 5
40057 U Bitfield
(Day, Hour, Minutes)
Last Successful Communication See Note 5
40058 U Bitfield
(Seconds, Milliseconds)
PC500/550 (Device 6)
Modbus
Parameter Sign Units Comments
Register
Device Type in Configuration 40061 U ENUM 1=Genset, 2=ATS, 4=AUX101/102
NOTES:
1. Modbus TCP can be enabled/disabled in the PC500/550 User Interface (Setup > Modbus Settings).
2. Default Modbus TCP port is 502 and is configurable in the PC500/550 User Interface (Setup > Modbus Settings).
No more than 2 Modbus TCP sessions can be established at a time.
3. PC5xx provides READ ONLY access over Modbus TCP.
4. PC500/550 registers return details about all configured devices in PC5xx (Generator Set, ATS, AUX101/102) and
can be accessed using Modbus TCP Unit ID 255 (default for PC500/550).
5. In PC500/550 registers, Devices 1 through 12 are numbered in the same order as they are arranged in the
Interface Device Configuration grid. To access details of these devices over Modbus TCP, the user must use the
Modbus TCP Unit ID (returned by register 4xxx3) in the query.
6. Bitmap registers indicating Last Successful Communication (4xxx6, 4xxx7, 4xxx8) are formatted as below:
7. Site IOs (sensors) and AUX101/102 data cannot be accessed over Modbus TCP.
Generator Set
Modbus
Scale Sign Units Description Comments
Register
40001 1 U ENUM Switch Position 0=Off, 1=AUTO, 2=Manual
0=Stopped, 1=Pending, 2=Warm
Up, 3=Running, 4=Cool Down
40002 1 U ENUM Control State (rated),
5=Cool Down (idle)
40003 1 U Fault Code
0=Normal, 1=Warning,
2=Derate,
40004 1 U ENUM Fault Type
3=Shutdown w/Cooldown,
4=Shutdown
40005 1 U Bitfield NFPA110 See Table 3 on page 11
40006 1 U Bitfield NFPA Extended See Table 4 on page 11
40007 1 U Volts L1N Voltage
40008 1 U Volts L2N Voltage
40009 1 U Volts L3N Voltage
40010 1 U Volts L1L2 Voltage
40011 1 U Volts L2L3 Voltage
40012 1 U Volts L3L1 Voltage
40013 1 U Amps L1 Current
Generator Set
Modbus
Scale Sign Units Description Comments
Register
40014 1 U Amps L2 Current
40015 1 U Amps L3 Current
40016 1 S kVA Total kVA
40017 0.01 U Hz Frequency
40018 0.1 U % PercentAmps APhase
40019 0.1 U % PercentAmps BPhase
40020 0.1 U % PercentAmps CPhase
40021 1 S kW Total kW
40022 0.01 S Total Power Factor
40023 0.01 S Volts Battery Voltage
40024 0.1 S psi Oil Pressure
40025 0.1 S _F Oil Temperature
40026 0.1 S _F Coolant Temperature
40027 1 U GPH Fuel Rate
40028 0.1 U Gallons Fuel Level
40029 1 U RPM Average Engine Speed
40030 1 U Engine Starts
40031 0.1 U Hours Engine Runtime
ATS
Modbus
Scale Sign Units Description Comments
Register
0=Test 1=Utility/Genset,
40001 1 U ENUM Mode 2=Utility/Utility,
3=Genset/Genset
0=None,
1=EngineStartASource2,
2=EngineStartBSource1,
3=NormaltoEmergency (TDNE),
4=EmergencytoNormal (TDEN),
40002 1 U ENUM Active Transfer Timer 5=EngineCooldownA (TDECa),
6=EngineCooldownB (TDECb),
7=ProgramTransition (TDPT),
8=Transfer Pend./Elevator
(TDEL),
255=Unknown
ATS
Modbus
Scale Sign Units Description Comments
Register
40003 1 U Fault Code
40004 1 U ENUM Fault Type 0=No Faults, 1=Warning
40005 1 U Bitfield NFPA110 See Table 5 on page 12
40006 1 U Bitfield NFPA Extended See Table 6 on page 12
40007 1 U Volts L1N Voltage (Load)
40008 1 U Volts L2N Voltage (Load)
40009 1 U Volts L3N Voltage (Load)
40010 1 U Volts L1L2 Voltage (Load)
40011 1 U Volts L2L3 Voltage (Load)
40012 1 U Volts L3L1 Voltage (Load)
40013 1 U Amps L1 Current (Load)
40014 1 U Amps L2 Current (Load)
40015 1 U Amps L3 Current (Load)
40016 1 S kW Total kW (Load)
40017 0.01 S Total Power Factor (Load)
40018 1 S kVAR Total kVAR (Load)
40019 1 S kVA Total kVA (Load)
40020 0.01 U Hz Frequency (Load)
40021 0.1 U % PercentAmps APhase (Load)
40022 0.1 U % PercentAmps BPhase (Load)
40023 0.1 U % PercentAmps CPhase (Load)
40024 1 U Volts L1N Voltage Source1
40025 1 U Volts L2N Voltage Source1
40026 1 U Volts L3N Voltage Source1
40027 1 U Volts L1L2 Voltage Source1
40028 1 U Volts L2L3 Voltage Source1
40029 1 U Volts L3L1 Voltage Source1
40037 0.01 U Hz Frequency Source1
40041 1 U Volts L1N Voltage Source2
40042 1 U Volts L2N Voltage Source2
40043 1 U Volts L3N Voltage Source2
40044 1 U Volts L1L2 Voltage Source2
ATS
Modbus
Scale Sign Units Description Comments
Register
40045 1 U Volts L2L3 Voltage Source2
40046 1 U Volts L3L1 Voltage Source2
40054 0.01 U Hz Frequency Source2
Condition Description
0 Disabled Digital Input
1 Not Active Alarm
2 Warning Alarm
3 Shutdown Alarm
4 Electrical Trip Alarm
5–7 Reserved
8 Inactive Indication (No String)
9 Inactive Indication (Displayed String)
10 Active Indication
11–14 Reserved
15 Unimplemented Alarm
439426 9/16 - Battery Low Voltage Read Size (Bits): 16 Battery low
12/16 Only Sign: U voltage alarm
439426 13/16 - Battery High Voltage Read Size (Bits): 16 Battery high
16/16 Only Sign: U voltage alarm
The control shall respond to any function code other than those listed above by sending an exception
response of Illegal Function (01).
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the holding register read request is not defined on the control.
• The first register in the holding register read request does not allow for the full representation of a
numeric value. This would occur if the first register in the read request is not mapped to the most
significant 2 bytes of a binary value parameter.
• The last register in the holding register read request does not allow for the full representation of a
numeric value. This would occur if the last register in the read request is not mapped to the least
significant 2 bytes of a binary value parameter.
Read requests for string type parameters where not every register associated with the string is in the
request shall return only the requested portion of the string.
The control shall respond to any read request to address not defined in the control by returning 0xFFFF
data for that address.
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the input register read request is not defined on the control.
• The first register in the input register read request does not allow for the full representation of a
numeric value. This would occur if the first register in the read request is not mapped to the most
significant 2 bytes of a parameter.
• The last register in the input register read request does not allow for the full representation of a
numeric value. This would occur if the last register in the read request is not mapped to the least
significant 2 bytes of a parameter.
The Input Registers support by each port on the control are listed in the Read Input Registers Table
below.
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The register in the holding register write request is not defined on the control.
• The register in the holding register write request does not allow for the full writing of a numeric value.
This would occur if the register is part of a numeric parameter that requires more than one address
to represent.
• If writing to a string values, the register in the holding register write request is not the first register of
that string.
Write requests for string type parameters where not every register associated with the string is in the
request shall write only the requested portion of the string.
Write requests to this control may return an Illegal Data Value exception code 03. This means that the
requested write failed to occur.
Write requests for string type parameters where not every register associated with the string is in the
request shall write only the requested portion of the string.
Write requests to this control may return an Illegal Data Value exception code 03. This means that some
or all of the requested writes failed to occur. It is the responsibility of the requestor to read the data again
to determine which parameters were not written to their requested new values and to respond as
necessary.
For any of these function codes, if there is an internal problem within the control software that prevents the
control from completing the requested action, the control will return a Server Device Failure exception
code of 04.
For any of these function codes while using Modbus TCP only, if data requests come from the Client and
fill up internal Modbus TCP Server message queue's faster than the protocol can process these data
requests, the control will return a Slave Device Busy exception code of 06.
The following configuration options shall be available for each port the control that supports the Modbus
RTU protocol. See the controller Modbus register map for individual register assignments for these
parameters on any given port.
NOTICE
Changes to the Modbus Baud Rate and the Modbus Parity and Stop Bit Selection parameters will
immediately be reflected on the serial port being configured. Any Modbus commands in progress
on that port in the old communications settings will fail until the Modbus master also updates its
communications settings to match those of the slave.
The control represents abnormal states in the data by using the five most positive values of the data to
convey that these abnormal states exist. The states will only be applicable to numeric parameters with the
following data types:
• UINT8, INT8, UINT16, INT16, UINT32, INT32, UINT64, INT64, FLOAT32 (signed and unsigned 8 bit
thru 64-bit parameters and 32-bit floating-point parameters)
Note that enumerated parameters and parameters with a floating-point data type will not follow this
abnormal state representation methods.
Note that this leaves the usable data range for extended data types to the following:
• For unsigned integer datatypes: 0 to (2^size - 6)
• For signed datatypes: -2^(size/2) to (2^(size/2) - 6)
• For float32: -3.4028234663852886 x 10+38 to +3.4028224522648084 x 10+38
When reading a register that contains information in an 8-bit data type, the data will be put the least
significant byte of the register. If the data type is unsigned, the upper byte will be populated with zero's. If
the data type is signed, the upper byte will be sign extended with the sign bit value of the data byte.
When writing a register that contains information that is expected to be in an 8-bit data type, the control
will expect the data to be in the least significant byte of the register and ignore the upper byte.
For numeric parameters requiring more than one Register to represent the data, the Register Address
listed in the Controller’s Modbus Register Map represents the most significant 2 bytes of the data. The
additional bytes of the data will always be provided in Register Address + 1, Register Address + 2, and
Register Address +3 as appropriate.
For string parameters, the first two characters in the string will be mapped to the Register Address listed in
the Controllers Modbus Register Map. Additional characters will be provided in the following registers. For
example, for the string "String1" at address 40031, the characters will be mapped the following registers:
40031: "St" 40032: "ri" 40033: "ng" 40034: "1_"
Each port instance of Modbus RTU Slave Protocol shall support interface to the following read input
registers through function code 04. These are the only input registers supported by this control.
The following table applies for each instance of the Modbus RTU protocol on any control and will return
the data from the port being read only.
Modbus TCP Protocol (server) implementation shall support interface to the following read input registers
through function code 04. These are the only input registers supported by this control.
The following table applies for the only instance of the Modbus TCP protocol on any control and will return
the data from the port being read only.
The Modbus TCP server can only handle 1 Modbus transaction at a time per Client/Server connection. If
the Modbus TCP server does not respond to a request in a timely manner (i.e. a Client side transaction
timeout occurs), it is recommended that the Client disconnect from the Server and then reconnect before
attempting another Modbus transaction.
NOTICE
Earlier versions of this software may not support all of the Modbus registers in the table below. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.
NOTICE
For the PS0500 control, Modbus functionality is ONLY available from software version 6.02 and
later.
NOTICE
If an address or bit is not listed in the table below, it has not been implemented.
NOTICE
The master device can read 1-16 contiguous registers, write 1-16 contiguous registers, or read
diagnostic counters.
43074 Alternator L3- Read and Multiplier: 0.0001 60 Hz line 3 to neutral PC1.x,
N 60Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.
43075 Alternator L1- Read and Multiplier: 0.0001 50 Hz line 1 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.
43076 Alternator L2- Read and Multiplier: 0.0001 50 Hz line 2 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.
43077 Alternator L3- Read and Multiplier: 0.0001 50 Hz line 3 to neutral PC1.x,
N 50Hz Write Offset: 0 metering voltage calibration PS0500
Voltage Size(Bits): 16 *Note: For the PS0500
Display control, SW versions lower
Sign: U
Adjust than 6.03, the range is 6000
Units: %
to 14000. For the PS0500
Lower Limit: 9000* control, SW versions higher
Upper Limit: 11000* than 6.03, the range is 9000
Default: 10000 to 11000.
43348 Clock Month Read Write Multiplier : 1 Use to set or read the current PC 1.x
Offset: 0 month
Size (Bits) : 8
Sign: U
Units: NA
Lower Limit: 1
Upper Limit: 12
Default: NA
TABLE 33. PCC1301 MODBUS MAPPING FOR PARAMETERS HAVING DIFFERENT LIMITS AS COMPARED
TO PC1.X AND PS05000
47041 Scheduler Read Write 0. AM User can set the AM/PM period PC 1.x
Prog Start 1. PM for the Scheduler
Period
47042 Transfer Read Write 0. Disable Trim to enable transfer switch PC 1.x
Switch 1. Enable feedback logic
Feedback
Enable
NOTICE
Earlier versions of software may not support all of the Modbus registers in the following table. If
a particular register is not available in your installation, it is possible that the Modbus connection
is working but the controller software does not support that particular register.
NOTICE
If an address or bit is not listed in this table it is not implemented.
NOTICE
The Master device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.
NOTICE
The lowest Modbus register value is considered as the High Register Value and the highest
Modbus register value is considered as the Low Register Value.
NOTICE
Throughout this document, if a parameter is marked for PCC3300 and PCC3300V2, then it is
applicable to both. If it is marked for PCC3300V2, then it is applicable to PCC3300V2 only.
TABLE 34.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40010 Control Read Only 0: Off Current position of the PCC3300,
Switch generator set switch PCC2300,
Position 1: Manual panel Off-Run-Auto PCC3300V2
2: Auto switch as seen by the
generator set control.
Modbus mapping shall
be in both addresses
40580 and 40010. For
40010 Modbus Only:
0: Off 1: Auto 2:
Manual
40012 Most Recent Read Only Multiplier: 1 Unit: Fault Code This Modbus Register PCC3300,
Fault or displays most recent PCC2300,
Warning Offset: 0 Lower Limit: Fault or Warning. It is PCC3300V2
Size (bits): 16 Upper Limit: not mapped with any
logical.
Sign: U
40013 Modbus Read Only 0: None This register returns PCC3300,
register the Fault Type of the PCC2300,
40013 1: Warning Fault Code. This is not PCC3300V2
2: Shutdown associated with any
logical.
40014 Genset % Read Only Multiplier: 0.01 Unit: % Monitors the total PCC3300,
Standby generator set standby PCC2300,
Total kW Offset: 0 Lower Limit: KW percentage PCC3300V2
Size (bits): 16 Upper Limit: output.
Sign: S
40018 Genset L1N Read Only Multiplier: 1 Unit: Vac Generator set L1N PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40019 Genset L2N Read Only Multiplier: 1 Unit: Vac Generator set L2N PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40020 Genset L3N Read Only Multiplier: 1 Unit: Vac Generator set L3N PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40022 Genset L1L2 Read Only Multiplier: 1 Unit: Vac Generator set L1L2 PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40023 Genset L2L3 Read Only Multiplier: 1 Unit: Vac Generator set L2L3 PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40024 Genset L3L1 Read Only Multiplier: 1 Unit: Vac Generator set L3L1 PCC3300,
Voltage voltage PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40025 Genset LL Read Only Multiplier: 1 Unit: Vac Generator set Line to PCC3300,
Average Line average voltage PCC2300,
Voltage Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40026 Genset L1 Read Only Multiplier: 1 Unit: Amps Monitors the generator PCC3300,
Current set L1 current value. PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40027 Genset L2 Read Only Multiplier: 1 Unit: Amps Generator set L2 PCC3300,
Current current PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40028 Genset L3 Read Only Multiplier: 1 Unit: Amps Generator set L3 PCC3300,
Current current PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40029 Genset Read Only Multiplier: 1 Unit: Amps Generator set average PCC3300,
Average current PCC2300,
Current Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40030 Genset Read Only Multiplier: 1 Unit: Amps Generator set neutral PCC3300,
Neutral current PCC3300V2
Current Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40031 Genset L1 Read Only Multiplier: 1 Unit: kW Generator set L1 kW PCC3300,
kW PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40032 Genset L2 Read Only Multiplier: 1 Unit: kW Generator set L2 kW PCC3300,
kW PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40033 Genset L3 Read Only Multiplier: 1 Unit: kW Generator set L3 kW PCC3300,
kW PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40034 Genset Total Read Only Multiplier: 1 Unit: kW Generator set total kW PCC3300,
kW PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40035 Genset L1 Read Only Multiplier: 1 Unit: kVAR Generator set L1 PCC3300,
kVAR KVAR PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40036 Genset L2 Read Only Multiplier: 1 Unit: kVAR Generator set L2 Kvar PCC3300,
kVAR PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-32768
Size (bits): 16 Upper Limit:
32762
Sign: S
40037 Genset L3 Read Only Multiplier: 1 Unit: kVAR Generator set L3 Kvar PCC3300,
kVAR PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40038 Genset Total Read Only Multiplier: 1 Unit: kVAR Generator set total PCC3300,
kVAR kVAR PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40039 Genset Total Read Only Multiplier: 0.01 Unit: PF Generator set total PCC3300,
Power Factor power factor PCC2300,
Offset: 0 Lower Limit: (L1+L2+L3) PCC3300V2
Size (bits): 8 Upper Limit:
Sign: S
40040 Genset L1 Read Only Multiplier: 1 Unit: kVA Generator set L1 kVA PCC3300,
kVA PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40041 Genset L2 Read Only Multiplier: 1 Unit: kVA Generator set L2 kVA PCC3300,
kVA PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40042 Genset L3 Read Only Multiplier: 1 Unit: kVA Generator set L3 kVA PCC3300,
kVA PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40043 Genset Total Read Only Multiplier: 1 Unit: kVA Generator set total PCC3300,
kVA kVA PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40046 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total PCC3300,
Negative negative kWh PCC2300,
kWh Offset: 0 Lower Limit: accumulation PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40047 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total PCC3300,
Negative negative kWh PCC2300,
kWh Offset: 0 Lower Limit: accumulation PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40048 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total PCC3300,
Positive kWh positive kWh PCC2300,
Offset: 0 Lower Limit: 0 accumulation PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
40049 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total PCC3300,
Positive kWh positive kWh PCC2300,
Offset: 0 Lower Limit: 0 accumulation PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
40050 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total net PCC3300,
Net kWh kWh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-2147483648
Size (bits): 32 Upper Limit:
2147483643
Sign: S
40051 Genset Total Read Only Multiplier: 1 Unit: kWh Generator set total net PCC3300,
Net kWh kWh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-2147483648
Size (bits): 32 Upper Limit:
2147483643
Sign: S
40052 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total PCC3300,
Negative negative kVARh PCC2300,
kVARh Offset: 0 Lower Limit: accumulation PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40053 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total PCC3300,
Negative negative kVARh PCC2300,
kVARh Offset: 0 Lower Limit: accumulation PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40054 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total PCC3300,
Positive positive kVARh PCC2300,
kVARh Offset: 0 Lower Limit: 0 accumulation PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40055 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total PCC3300,
Positive positive kVARh PCC2300,
kVARh Offset: 0 Lower Limit: 0 accumulation PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
40056 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total net PCC3300,
Net kVARh kVARh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-2147483648
Size (bits): 32 Upper Limit:
2147483643
Sign: S
40057 Genset Total Read Only Multiplier: 1 Unit: kVARh Generator set total net PCC3300,
Net kVARh kVARh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-2147483648
Size (bits): 32 Upper Limit:
2147483643
Sign: S
40058 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Standby L1 set standby L1 current PCC2300,
Current Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40059 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Standby L2 set standby L2 current PCC2300,
Current Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40060 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Standby L3 set standby L3 current PCC2300,
Current Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40061 Battery Read Only Multiplier: 0.001 Unit: Vdc "Battery voltage value. PCC3300,
Voltage Modbus and PCCnet PCC2300,
Offset: 0 Lower Limit: has different multiplier PCC3300V2
Size (bits): 16 Upper Limit: value. For Modbus
use only,
Sign: U multiplier/units = 0.1
Volts"
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40062 Oil Pressure Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Oil Pressure. Modbus PCC2300,
Offset: 0 Lower Limit: and PCCnet have PCC3300V2
Size (bits): 16 Upper Limit: different multiplier
value. For modbus
Sign: U use only,
Multiplier/Units = 1kPa
40063 Oil Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Temperature Oil Temperature PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
40064 Coolant Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Temperature Coolant Temperature. PCC2300,
Offset: 0 Lower Limit: Modbus mapping shall PCC3300V2
Size (bits): 16 Upper Limit: be to both 46126 and
40064 addresses. For
Sign: S Modbus use only,
Multiplier/Units = 0.1C
40065 Intake Read Only Multiplier: 0.1 Unit: degF To monitor Intake PCC3300,
Manifold Manifold Temperature. PCC2300,
Temperature Offset: 0 Lower Limit: -40 This parameter PCC3300V2
Size (bits): 16 Upper Limit: 410 represents "Intake
Manifold Temperature
Sign: S 1".
40066 Fuel Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Temperature Fuel Temperature PCC2300,
Offset: 0 Lower Limit: -40 PCC3300V2
Size (bits): 16 Upper Limit: 410
Sign: S
40067 Fuel Rate Read Only Multiplier: 0.05 Unit: gal/hr Monitor point for the PCC3300,
Fuel Rate PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40068 Average Read Only Multiplier: 0.125 Unit: rpm Monitor point for the PCC3300,
Engine Average Engine PCC2300,
Speed Offset: 0 Lower Limit: Speed. Modbus and PCC3300V2
Size (bits): 16 Upper Limit: PCCnet have different
multiplier value. For
Sign: U modbus use only,
Multiplier/Units = 1
RPM
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40070 Engine Read Only Multiplier: 0.05 Unit: hours Amount of time that PCC3300,
Running the engine has been PCC2300,
Time Offset: 0 Lower Limit: running. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40071 Engine Read Only Multiplier: 0.05 Unit: hours Amount of time that PCC3300,
Running the engine has been PCC2300,
Time Offset: 0 Lower Limit: running. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40072 Total Fuel Read Only Multiplier: 0.1 Unit: gallons Total fuel consumption PCC3300,
Consumption since start of engine. PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40073 Total Fuel Read Only Multiplier: 0.1 Unit: gallons Total fuel consumption PCC3300,
Consumption since start of engine. PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40074 Total Read/Write Multiplier: 1 Unit: Total number of PCC3300,
Number of generator set runs. PCC2300,
Runs Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U
40075 Total Read/Write Multiplier: 1 Unit: Total number of PCC3300,
Number of generator set runs. PCC2300,
Runs Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40076 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40077 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40078 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40079 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40080 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40081 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40082 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40083 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40084 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40085 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40086 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40087 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40088 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40089 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40090 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40091 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40092 Runs Reset Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Time stamp record of the PCC2300,
Offset: 0 Lower Limit: last time the Run PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40076 - 40092 for
17 char of this string.
40096 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40097 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40098 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40099 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40100 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40101 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40102 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40103 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40104 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40105 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40106 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40107 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40108 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40109 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40110 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40111 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40112 Start Read/Write Multiplier: 1 Unit: Real Time Clock PCC3300,
Attempts stamp record of the PCC2300,
Reset Time Offset: 0 Lower Limit: last time the Start PCC3300V2
Size (bits): 144 Upper Limit: Attempts were reset.
This parameter is
Sign: C READ/WRITE for Mon
and PCCNet and
READ ONLY for
ModBus. Modbus
implementation or the
Real time stamp will
use 40096 - 0112 for
17 char of this string.
40118 Utility L1N Read Only Multiplier: 1 Unit: Vac Utility L1N voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40119 Utility L2N Read Only Multiplier: 1 Unit: Vac Utility L2N voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40120 Utility L3N Read Only Multiplier: 1 Unit: Vac Utility L3N voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40122 Utility L1L2 Read Only Multiplier: 1 Unit: Vac Utility L1L2 voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40123 Utility L2L3 Read Only Multiplier: 1 Unit: Vac Utility L2L3 voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40124 Utility L3L1 Read Only Multiplier: 1 Unit: Vac Utility L3L1 voltage PCC3300,
Voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40125 Utility LL Read Only Multiplier: 1 Unit: Vac Utility Line to Line PCC3300,
Average average voltage PCC3300V2
Voltage Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40126 Utility L1 Read Only Multiplier: 1 Unit: Amps Utility L1 current PCC3300,
Current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40127 Utility L2 Read Only Multiplier: 1 Unit: Amps Utility L2 current PCC3300,
Current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40128 Utility L3 Read Only Multiplier: 1 Unit: Amps Utility L3 current PCC3300,
Current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40131 Utility L1 kW Read Only Multiplier: 1 Unit: kW Utility L1 kW PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40132 Utility L2 kW Read Only Multiplier: 1 Unit: kW Utility L2 kW PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40133 Utility L3 kW Read Only Multiplier: 1 Unit: kW Utility L3 kW PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40134 Utility Total Read Only Multiplier: 1 Unit: kW Utility total kW PCC3300,
kW PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40135 Utility L1 Read Only Multiplier: 1 Unit: kVAR Utility L1 Kvar PCC3300,
kVAR PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40136 Utility L2 Read Only Multiplier: 1 Unit: kVAR Utility L2 Kvar PCC3300,
kVAR PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40137 Utility L3 Read Only Multiplier: 1 Unit: kVAR Utility L3 Kvar PCC3300,
kVAR PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40138 Utility Total Read Only Multiplier: 1 Unit: kVAR Utility total kVAR PCC3300,
kVAR PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40139 Utility Total Read Only Multiplier: 0.01 Unit: PF Utility total power PCC3300,
Power Factor factor PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
40140 Utility L1 kVA Read Only Multiplier: 1 Unit: kVA Utility L1 kVA PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40141 Utility L2 kVA Read Only Multiplier: 1 Unit: kVA Utility L2 kVA PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40142 Utility L3 kVA Read Only Multiplier: 1 Unit: kVA Utility L3 kVA PCC3300,
PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40143 Utility Total Read Only Multiplier: 1 Unit: kVA Utility total kVA PCC3300,
kVA PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40144 Utility Read Only Multiplier: 0.001 Unit: Hz Utility line frequency PCC3300,
Frequency PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40145 Utility Read Only Multiplier: 0.001 Unit: Hz Utility line frequency PCC3300,
Frequency PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40146 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total negative PCC3300,
Negative kWh accumulation PCC3300V2
kWh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40147 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total negative PCC3300,
Negative kWh accumulation PCC3300V2
kWh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40148 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total positive PCC3300,
Positive kWh kWh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40149 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total positive PCC3300,
Positive kWh kWh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40150 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total net kWh PCC3300,
Net kWh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40151 Utility Total Read Only Multiplier: 1 Unit: kWh Utility total net kWh PCC3300,
Net kWh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: S
40152 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total negative PCC3300,
Negative kVARh accumulation PCC3300V2
kVARh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40153 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total negative PCC3300,
Negative kVARh accumulation PCC3300V2
kVARh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40154 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total positive PCC3300,
Positive kVARh accumulation PCC3300V2
kVARh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40155 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total positive PCC3300,
Positive kVARh accumulation PCC3300V2
kVARh Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40156 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total net kVARh PCC3300,
Net kVARh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: S
40157 Utility Total Read Only Multiplier: 1 Unit: kVARh Utility total net kVARh PCC3300,
Net kVARh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: S
40158 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L1N Voltage L1N voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40159 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L2N Voltage L2N voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40160 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L3N Voltage L3N voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40162 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L1L2 Voltage L1L2 voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40163 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L2L3 Voltage L2L3 voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40164 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
L3L1 Voltage L3L1 voltage PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40165 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
LL Average Line to Line average PCC3300V2
Voltage Offset: 0 Lower Limit: voltage
Size (bits): 16 Upper Limit:
Sign: U
40166 Genset Bus Read Only Multiplier: 1 Unit: Amps Generator set Bus L1 PCC3300,
L1 Current current PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
40167 Genset Bus Read Only Multiplier: 1 Unit: Amps Generator set Bus L2 PCC3300,
L2 Current current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40168 Genset Bus Read Only Multiplier: 1 Unit: Amps Generator set Bus L3 PCC3300,
L3 Current current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40171 Genset Bus Read Only Multiplier: 1 Unit: kW Generator set Bus L1 PCC3300,
L1 kW kW PCC3300V2
Offset: 0 Lower Limit:
-32768
Size (bits): 16 Upper Limit:
32762
Sign: S
40172 Genset Bus Read Only Multiplier: 1 Unit: kW Generator set Bus L2 PCC3300,
L2 kW kW PCC3300V2
Offset: 0 Lower Limit:
-32768
Size (bits): 16 Upper Limit:
32762
Sign: S
40173 Genset Bus Read Only Multiplier: 1 Unit: kW Generator set Bus L3 PCC3300,
L3 kW kW PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40174 Genset Bus Read Only Multiplier: 1 Unit: kW Generator set Bus PCC3300,
Total kW total kW PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40175 Genset Bus Read Only Multiplier: 1 Unit: kVAR Generator set bus L1 PCC3300,
L1 kVAR Kvar PCC3300V2
Offset: 0 Lower Limit:
-32678
Size (bits): 16 Upper Limit:
32672
Sign: S
40176 Genset Bus Read Only Multiplier: 1 Unit: kVAR Generator set bus L2 PCC3300,
L2 kVAR Kvar PCC3300V2
Offset: 0 Lower Limit:
-32768
Size (bits): 16 Upper Limit:
32762
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40177 Genset Bus Read Only Multiplier: 1 Unit: kVAR Generator set bus L3 PCC3300,
L3 kVAR Kvar PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40178 Genset Bus Read Only Multiplier: 1 Unit: kVAR Generator set bus PCC3300,
Total kVAR total kVAR PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
40179 Genset Bus Read Only Multiplier: 0.01 Unit: PF Generator set Bus PCC3300,
Total Power Total power factor PCC3300V2
Factor Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
40180 Genset Bus Read Only Multiplier: 1 Unit: kVA Generator set Bus L1 PCC3300,
L1 kVA kVA PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40181 Genset Bus Read Only Multiplier: 1 Unit: kVA Generator set Bus L2 PCC3300,
L2 kVA kVA PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40182 Genset Bus Read Only Multiplier: 1 Unit: kVA Generator set Bus L3 PCC3300,
L3 kVA kVA PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40183 Genset Bus Read Only Multiplier: 1 Unit: kVA Generator set bus PCC3300,
Total kVA total kVA PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
TABLE 35.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40184 Genset Bus Read Only Multiplier: 0.001 Unit: Hz Generator set bus line PCC3300,
Frequency frequency PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40185 Genset Bus Read Only Multiplier: 0.001 Unit: Hz Generator set bus line PCC3300,
Frequency frequency PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
40186 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total total negative kWh PCC3300V2
Negative Offset: 0 Lower Limit: accumulation
kWh Size (bits): 32 Upper Limit:
Sign: U
40187 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total total negative kWh PCC3300V2
Negative Offset: 0 Lower Limit: accumulation
kWh Size (bits): 32 Upper Limit:
Sign: U
40188 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total Positive total positive kWh PCC3300V2
kWh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
40189 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total Positive total positive kWh PCC3300V2
kWh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
40190 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total Net total net kWh PCC3300V2
kWh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: S
40191 Genset Bus Read Only Multiplier: 1 Unit: kWh Generator set bus PCC3300,
Total Net total net kWh PCC3300V2
kWh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40192 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set bus PCC3300,
Total total negative kVARh PCC3300V2
Negative Offset: 0 Lower Limit: accumulation
kVARh Size (bits): 32 Upper Limit:
Sign: U
40193 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set bus PCC3300,
Total total negative kVARh PCC3300V2
Negative Offset: 0 Lower Limit: accumulation
kVARh Size (bits): 32 Upper Limit:
Sign: U
40194 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set bus PCC3300,
Total Positive total positive kVARh PCC3300V2
kVARh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
40195 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set bus PCC3300,
Total Positive total positive kVARh PCC3300V2
kVARh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
40196 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set Bus PCC3300,
Total Net total net kVARh PCC3300V2
kVARh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: S
40197 Genset Bus Read Only Multiplier: 1 Unit: kVARh Generator set Bus PCC3300,
Total Net total net kVARh PCC3300V2
kVARh Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: S
40198 Ground Read Only Multiplier: 0.1 Unit: amps Ground current PCC3300,
Current PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
40199 Genset Read Only Multiplier: 0.01 Unit: % Genset Negative PCC3300,
Negative Sequence Current as PCC2300,
Sequence Offset: 0 Lower Limit: Percent of Standby PCC3300V2
Current % Size (bits): 16 Upper Limit: Current Rating
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40200 LVRT Read Only Multiplier: 1 Unit: Counter to keep track PCC3300,
Counter of number of LVRT PCC3300V2
Offset: 0 Lower Limit: 0 Events
Size (bits): 16 Upper Limit:
65535
Sign: U
40201 Coolant Read Only 0: PGBU Either PGBU(Onan) or PCC3300,
Temperature EBU(Cummins) PCC3300V2
Sensor Type 1: EBU sensor. MODBUS
Access: Read Only
40202 LVRT Enable Read Only 0: Disabled Displays whether the PCC3300,
Status LVRT Functionality PCC3300V2
1: Enabled has been enabled to
detect LVRT Events.
40207 Battery Read Only Multiplier: 0.001 Unit: Vdc The Battery Charger PCC3300,
Charger Alternator Flash PCC2300,
Alternator Offset: 0 Lower Limit: 0 Voltage after all PCC3300V2
Flash Size (bits): 16 Upper Limit: 35 scaling and validity
Voltage checks.
Sign: U
40208 Battery 1 Read Only Multiplier: 0.01 Unit: Vdc Battery 1 Voltage PCC3300,
Voltage measured through PCC3300V2
(Aux101) Offset: 0 Lower Limit: 0 AUX101. Applicable
Size (bits): 16 Upper Limit: when multiple
3850 batteries are used.
Sign: U
40209 Battery 2 Read Only Multiplier: 0.01 Unit: Vdc Battery 2 Voltage PCC3300,
Voltage measured through PCC3300V2
(Aux101) Offset: 0 Lower Limit: 0 AUX101. Applicable
Size (bits): 16 Upper Limit: when multiple
3850 batteries are used.
Sign: U
40210 External Read Only Multiplier: 0.01 Unit: % Monitor point for the PCC3300,
Speed Bias external speed bias PCC2300,
Input Offset: 0 Lower Limit: -100 input. PCC3300V2
Size (bits): 16 Upper Limit: 100
Sign: S
40211 External Read Only Multiplier: 0.01 Unit: % Monitor point for the PCC3300,
Voltage Bias external voltage bias PCC2300,
Input Offset: 0 Lower Limit: -100 input. PCC3300V2
Size (bits): 16 Upper Limit: 100
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40212 Battery 3 Read Only Multiplier: 0.01 Unit: Vdc Battery 3 Voltage PCC3300,
Voltage measured through PCC3300V2
(Aux101) Offset: 0 Lower Limit: 0 AUX101. Applicable
Size (bits): 16 Upper Limit: when multiple
3850 batteries are used.
Sign: U
40213 Battery 4 Read Only Multiplier: 0.01 Unit: Vdc Battery 4 Voltage PCC3300,
Voltage measured through PCC3300V2
(Aux101) Offset: 0 Lower Limit: 0 AUX101. Applicable
Size (bits): 16 Upper Limit: when multiple
3850 batteries are used.
Sign: U
40226 Speed Bias Read Only Multiplier: 0.01 Unit: Vdc Configurable analog PCC3300,
Output / output voltage output PCC3300V2
Configurable Offset: 0 Lower Limit: value (predicted)
Analog Size (bits): 16 Upper Limit:
output #1
Output Sign: S
Predictor
40227 Voltage Bias Read Only Multiplier: 0.01 Unit: Vdc Configurable analog PCC3300,
Output / output voltage output PCC3300V2
Configurable Offset: 0 Lower Limit: value (predicted)
Analog Size (bits): 16 Upper Limit:
output #2
Output Sign: S
Predictor
40228 Amber Read Only 0: Inactive Engine Control PCC3300,
Warning System indicates a PCC2300,
Lamp Status 1: Active warning condition. PCC3300V2
40229 Barometric Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Absolute Barometric Absolute PCC2300,
Pressure Offset: 0 Lower Limit: Pressure. Displayed PCC3300V2
Size (bits): 16 Upper Limit: as "Ambient Pressure"
in the HMI.
Sign: U
40230 Boost Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Pressure Boost Absolute PCC2300,
Offset: 0 Lower Limit: Pressure PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40231 CAN Datalink Read Only 0: Inactive Indicates the status of PCC3300,
Status the CAN datalink PCC2300,
1: Active PCC3300V2
2: Failed
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40232 Crankcase Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Pressure Crankcase Pressure. PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-35.67
Size (bits): 16 Upper Limit: 38
Sign: S
40235 ECM Derate Read Only 0: No Derate Request made by the PCC3300,
Request Request ECS for a reduction in PCC2300,
load PCC3300V2
1: Derate
Request
2: Error
3: Don't Care
40236 Engine Read Only 0: ECM Monitor point for the PCC3300,
Application output of the Engine PCC2300,
Type 1: Hydro- application type. Either PCC3300V2
Mechanical ECM (CAN) or Hydro-
Mechanical.
40238 PGI Major Read Only Multiplier: 1 Unit: "Displays Power PCC3300,
Version Generation Interface PCC2300,
Offset: 0 Lower Limit: 0 Major Version to which PCC3300V2
Size (bits): 8 Upper Limit: 255 Engine Software is
complying"
Sign: U
40239 PGI Minor Read Only Multiplier: 1 Unit: "Displays Power PCC3300,
Version Generation Interface PCC2300,
Offset: 0 Lower Limit: 0 Minor Version to which PCC3300V2
Size (bits): 8 Upper Limit: 255 Engine Software is
complying"
Sign: U
40240 PGI Read Only Multiplier: 1 Unit: "Displays Power PCC3300,
Informational Generation Interface PCC2300,
Version Offset: 0 Lower Limit: 0 Informational Version PCC3300V2
Size (bits): 8 Upper Limit: 255 to which Engine
Software is complying"
Sign: U
40242 Aftercooler Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Temperature Aftercooler PCC2300,
Offset: 0 Lower Limit: -40 Temperature. PCC3300V2
Size (bits): 16 Upper Limit: 410
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40243 Internal ECM Read Only Multiplier: 0.1 Unit: degF "Internal temperature PCC3300,
Module 1 of the engine PCC3300V2
Temperature Offset: 0 Lower Limit: electronic control
Size (bits): 16 Upper Limit: module 1"
Sign: S
40244 Internal ECM Read Only Multiplier: 0.1 Unit: degF "Internal temperature PCC3300,
Module 2 of the engine PCC3300V2
Temperature Offset: 0 Lower Limit: electronic control
Size (bits): 16 Upper Limit: module 2"
Sign: S
40245 Internal ECM Read Only Multiplier: 0.1 Unit: degF "Internal temperature PCC3300,
Module 3 of the engine PCC3300V2
Temperature Offset: 0 Lower Limit: electronic control
Size (bits): 16 Upper Limit: module 3"
Sign: S
40246 Internal ECM Read Only Multiplier: 0.1 Unit: degF "Internal temperature PCC3300,
Module 4 of the engine PCC3300V2
Temperature Offset: 0 Lower Limit: electronic control
Size (bits): 16 Upper Limit: module 4"
Sign: S
40247 ECM Module Read Only Multiplier: 0.1 Unit: Vdc "Engine Control PCC3300,
1 Battery Module 1 Battery PCC3300V2
Voltage Offset: 0 Lower Limit: 0 Voltage."
Size (bits): 16 Upper Limit:
65535
Sign: U
40248 ECM Module Read Only Multiplier: 0.1 Unit: Vdc "Engine Control PCC3300,
2 Battery Module 2 Battery PCC3300V2
Voltage Offset: 0 Lower Limit: 0 Voltage."
Size (bits): 16 Upper Limit:
65535
Sign: U
40249 ECM Module Read Only Multiplier: 0.1 Unit: Vdc "Engine Control PCC3300,
3 Battery Module 3 Battery PCC3300V2
Voltage Offset: 0 Lower Limit: 0 Voltage."
Size (bits): 16 Upper Limit:
65535
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40250 ECM Module Read Only Multiplier: 0.1 Unit: Vdc "Engine Control PCC3300,
4 Battery Module 4 Battery PCC3300V2
Voltage Offset: 0 Lower Limit: 0 Voltage."
Size (bits): 16 Upper Limit:
65535
Sign: U
40254 Fuel Supply Read Only Multiplier: 0.1 Unit: psi "Monitor point for the PCC3300,
Pressure Fuel Supply Pressure. PCC2300,
Offset: 0 Lower Limit: 0 Displayed as Fuel PCC3300V2
Size (bits): 16 Upper Limit: 145 Supply Pressure in the
HMI."
Sign: U
40257 Intake Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Manifold 4 Intake Manifold 4 PCC2300,
Temperature Offset: 0 Lower Limit: -40 Temperature PCC3300V2
Size (bits): 16 Upper Limit: 410
Sign: S
40258 Fuel Outlet Read Only Multiplier: 0.1 Unit: psi "Monitor point for the PCC3300,
Pressure Fuel Outlet Pressure PCC2300,
Offset: 0 Lower Limit: Pressure. Displayed PCC3300V2
Size (bits): 32 Upper Limit: as Fuel Rail Pressure
in the HMI."
Sign: U
40259 Fuel Outlet Read Only Multiplier: 0.1 Unit: psi "Monitor point for the PCC3300,
Pressure Fuel Outlet Pressure PCC2300,
Offset: 0 Lower Limit: Pressure. Displayed PCC3300V2
Size (bits): 32 Upper Limit: as Fuel Rail Pressure
in the HMI."
Sign: U
40260 Intake Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Manifold 2 Intake Manifold 2 PCC2300,
Temperature Offset: 0 Lower Limit: -40 Temperature PCC3300V2
Size (bits): 16 Upper Limit: 410
Sign: S
40261 Intake Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Manifold 3 Intake Manifold 3 PCC2300,
Temperature Offset: 0 Lower Limit: -40 Temperature PCC3300V2
Size (bits): 16 Upper Limit: 410
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40264 Percent Read Only Multiplier: 1 Unit: % Monitor point for the PCC3300,
Engine percent engine torque PCC2300,
Torque/Duty Offset: 0 Lower Limit: output and the PCC3300V2
Cycle Size (bits): 16 Upper Limit: governor percent duty
cycle output when
Sign: S used with the HM
ECM
40276 Post-Filter Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Oil Pressure Post-Filter Oil PCC2300,
Offset: 0 Lower Limit: 0 Pressure PCC3300V2
Size (bits): 16 Upper Limit: 145
Sign: U
40277 Pre-Filter Oil Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Pressure Pre-Filter Oil Pressure PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit: 145
Sign: U
40278 Configurable Read Only 0: Inactive Configurable Input #14 PCC3300,
Input #14 input software state PCC2300,
Switch 1: Active status. Gives software PCC3300V2
Inactive/Active state
40279 Turbocharger Read Only Multiplier: 1 Unit: rpm Monitor point for the PCC3300,
1 Speed Turbocharger 1 Speed PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40280 Turbocharger Read Only Multiplier: 1 Unit: rpm Monitor point for the PCC3300,
1 Speed Turbocharger 1 Speed PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40281 Turbocharger Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
2 Boost Turbocharger 2 Boost PCC2300,
Pressure Offset: 0 Lower Limit: Pressure PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
40282 Water in Fuel Read Only 0: No Water in Fuel PCC3300,
Indicator Indication PCC2300,
1: Yes PCC3300V2
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40283 Controller Read Only 0: Off The controller mode PCC3300,
Mode PCC2300,
1: Ready PCC3300V2
2: Setup
3: Starting
4: Idle
5: Rated
6: Stop Normal
7: Stop
Emergency
8: Factory Test
9: Wait to Power
Down
10: Regeneration
40285 Power Down Read Only Multiplier: 1 Unit: seconds Timer to count down PCC3300,
Mode Timer the time before the PCC2300,
Offset: 0 Lower Limit: 0 control goes to sleep PCC3300V2
Size (bits): 16 Upper Limit: 600
Sign: U
40290 Controller On Read/Write Multiplier: 1 Unit: Seconds Controller ON time in PCC3300,
Time seconds. Upper limit is PCC2300,
Offset: 0 Lower Limit: 0 136 years. PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U
40291 Controller On Read/Write Multiplier: 1 Unit: Seconds Controller ON time in PCC3300,
Time seconds. Upper limit is PCC2300,
Offset: 0 Lower Limit: 0 136 years. PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U
40298 Runs Since Read/Write Multiplier: 1 Unit: Number of runs since PCC3300,
Reset the last reset. Upper PCC2300,
Offset: 0 Lower Limit: 0 limit is 2^32 - 1. PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40299 Runs Since Read/Write Multiplier: 1 Unit: Number of runs since PCC3300,
Reset the last reset. Upper PCC2300,
Offset: 0 Lower Limit: 0 limit is 2^32 - 1. PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
40300 Remote Start Read/Write 0: Inactive Modbus Remote Start PCC3300,
Switch(Modb PCC2300,
us) 1: Active PCC3300V2
40301 Fault Reset Read/Write 0: Inactive Modbus fault reset. PCC3300,
(Modbus) PCC2300,
1: Active PCC3300V2
40320 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40321 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40322 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40323 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40324 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40325 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40326 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40327 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40328 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40329 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40330 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40331 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40332 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40333 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40334 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40335 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40336 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40337 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40338 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40339 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No1 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active
Sign: C
40340 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40341 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40342 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40343 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40344 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40345 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40346 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40347 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40348 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40349 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40350 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40351 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40352 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40353 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40354 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40355 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40356 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40357 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40358 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40359 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No2 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40360 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40361 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40362 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40363 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40364 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40365 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40366 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40367 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40368 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40369 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40370 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40371 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40372 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40373 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40374 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40375 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40376 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40377 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40378 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40379 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
No3 Fault character string for PCC3300V2
Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40380 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40381 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40382 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40383 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40384 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40385 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40386 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40387 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40388 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40389 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40390 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40391 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40392 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40393 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40394 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40395 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40396 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40397 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40398 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
40399 Start Inhibit Read/Write Multiplier: 1 Unit: Trim to define the 20 PCC3300,
Modbus character string for PCC3300V2
Fault Text Offset: 0 Lower Limit: use by the Operator
Size (bits): 168 Upper Limit: panel when this fault
becomes active.
Sign: C
TABLE 36.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40500 Low Fuel Read Only 0: Inactive Low Fuel input PCC3300,
Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
40501 Low Read Only 0: Inactive This is the status of PCC3300,
Fuel/Configur the Configurable Input PCC2300,
able Input #6 1: Active #6. PCC3300V2
Switch
40503 Differential Read Only 0: Inactive Differential fault trip PCC3300,
Fault Trip monitor point. PCC3300V2
1: Active
2: Reserved
3: Not Available
40509 PTC Mode Read Only 0: Inactive PTC Mode Switch PCC3300,
Switch function output status. PCC3300V2
1: Active Gives software
Inactive/Active state
40510 Extended Read Only 0: Inactive This is the status of PCC3300,
Parallel/Confi the Configurable Input PCC3300V2
gurable Input 1: Active #32.
#32 Switch
40512 Remote E- Read Only 0: Inactive Remote E-stop input PCC3300,
stop Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40513 Remote Start Read Only 0: Inactive Remote Start input PCC3300,
Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
40515 Retransfer Read Only 0: Inactive This is the status of PCC3300,
Inhibit/Config the Configurable Input PCC3300V2
urable Input 1: Active #21.
#21 Switch
40516 Rupture Read Only 0: Inactive Rupture Basin input PCC3300,
Basin Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
40517 Rupture Read Only 0: Inactive This is the status of PCC3300,
Basin/Config the Configurable Input PCC2300,
urable Input 1: Active #12. PCC3300V2
#12 Switch
40519 Start Type Read Only 0: Inactive Start Type input PCC3300,
Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
40521 Sync Read Only 0: Inactive This is the status of PCC3300,
Enable/Confi the Configurable Input PCC3300V2
gurable Input 1: Active #30.
#30 Switch
40524 Transfer Read Only 0: Inactive This is the status of PCC3300,
Inhibit/Config the Configurable Input PCC3300V2
urable Input 1: Active #20.
#20 Switch
40525 Utility CB Read Only 0: Inactive This is the status of PCC3300,
Inhibit/Config the Configurable Input PCC3300V2
urable Input 1: Active #25.
#25 Switch
40526 Utility CB Read Only 0: Inactive This is the status of PCC3300,
Pos the Configurable Input PCC3300V2
B/Configurab 1: Active #23.
le Input #23
Switch
40527 Utility CB Read Only 0: Inactive This is the status of PCC3300,
Tripped/Confi the Configurable Input PCC3300V2
gurable Input 1: Active #24.
#24 Switch
40528 Utility Single Read Only 0: Inactive This is the status of PCC3300,
Mode the Configurable Input PCC3300V2
Verify/Config 1: Active #29.
urable Input
#29 Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40530 Utility CB Read Only 0: Inactive Utility CB Pos A input PCC3300,
Pos A Switch software state status. PCC3300V2
1: Active Gives software
Inactive/Active state
40531 Utility CB Read Only 0: Inactive Utility CB Pos B input PCC3300,
Pos B Switch software state status. PCC3300V2
1: Active Gives software
Inactive/Active state
40535 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #1 output’s status is PCC2300,
Status 1: Active Inactive or Active PCC3300V2
40536 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #2 output’s status is PCC2300,
Status 1: Active Inactive or Active PCC3300V2
40537 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #20 output’s status is PCC3300V2
Status 1: Active Inactive or Active
40538 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #21 output’s status is PCC3300V2
Status 1: Active Inactive or Active
40539 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #22 output’s status is PCC3300V2
Status 1: Active Inactive or Active
40540 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #3 output’s status is PCC2300,
Status 1: Active Inactive or Active PCC3300V2
40541 Configurable Read Only 0: Inactive Indicates if the PCC3300,
Output #4 output’s status is PCC2300,
Status 1: Active Inactive or Active PCC3300V2
40542 Delayed Off / Read Only 0: Inactive Indicates if the PCC3300,
Configurable output’s status is PCC2300,
Output #10 1: Active Inactive or Active PCC3300V2
Status
40543 Fuel Shutoff Read/Write 0: Inactive Indicates if the PCC3300,
Status output’s status is PCC2300,
1: Active Inactive or Active PCC3300V2
40547 Keyswitch Read Only 0: Inactive Indicates if the PCC3300,
Status output’s status is PCC2300,
1: Active Inactive or Active PCC3300V2
40549 Load Dump / Read Only 0: Inactive Indicates if the PCC3300,
Configurable output’s status is PCC2300,
Output #11 1: Active Inactive or Active PCC3300V2
Status
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40550 Local Status Read Only 0: Inactive Indicates if the PCC3300,
/ output’s status is PCC2300,
Configurable 1: Active Inactive or Active PCC3300V2
Output #7
Status
40552 Oil Priming Read Only 0: Inactive Indicates if the PCC3300,
Pump / output’s status is PCC2300,
Configurable 1: Active Inactive or Active PCC3300V2
Output #6
Status
40553 Ready To Read Only 0: Inactive Indicates if the PCC3300,
Load output’s status is PCC2300,
/Configurable 1: Active Inactive or Active PCC3300V2
Output #5
Status
40554 Run Relay Read Only 0: Inactive Indicates if the PCC3300,
#1 Status output’s status is PCC2300,
1: Active Inactive or Active PCC3300V2
40555 Run Relay Read Only 0: Inactive Indicates if the PCC3300,
#2 Status output’s status is PCC2300,
1: Active Inactive or Active PCC3300V2
40556 Speed/Voltag Read Only 0: Inactive Indicates if the PCC3300,
e Bias Relay output’s status is PCC3300V2
Status 1: Active Inactive or Active
40561 Common Read Only 0: Inactive The status of the PCC3300,
Alarm Fault Common Alarm Fault PCC2300,
Status 1: Active PCC3300V2
40562 Common Read Only 0: Inactive The status of the PCC3300,
Shutdown common shutdown PCC2300,
Command 1: Active command PCC3300V2
40563 Common Read Only 0: Inactive The status of the PCC3300,
Shutdown Common Shutdown PCC2300,
Event Status 1: Active Event PCC3300V2
40565 Common Read Only 0: Inactive The status of the PCC3300,
Warning Common Warning PCC2300,
Event Status 1: Active Event PCC3300V2
40570 Fault Reset Read Only 0: Inactive One shot due to fault PCC3300,
Command reset switch being PCC2300,
1: Active active. PCC3300V2
40577 Base Read Only Multiplier: 0.001 Unit: Hz Provides a point to PCC3300,
Frequency monitor the base PCC2300,
Offset: 0 Lower Limit: frequency PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40578 Base Read Only Multiplier: 0.001 Unit: Hz Provides a point to PCC3300,
Frequency monitor the base PCC2300,
Offset: 0 Lower Limit: frequency PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
40586 Excitation Read Only 0: Disabled Shows the enable PCC3300,
State status of the excitation PCC2300,
1: Enabled enabled = regulator PCC3300V2
on.
40587 Exercise Read Only 0: Inactive The output of the PCC3300,
Command Exercise Command PCC2300,
1: Active OR logic PCC3300V2
2: Reserved
3: Not Available
40589 Exercise Read Only Multiplier: 0.1 Unit: hours Time remaining until PCC3300,
Time exercise stop PCC2300,
Remaining Offset: 0 Lower Limit: 0 sequence begins PCC3300V2
Size (bits): 16 Upper Limit: 25
Sign: U
40592 Battle Short Read Only 0: Inactive Indicates status of PCC3300,
Command battle short inputs PCC2300,
1: Active PCC3300V2
40595 Final Read Only Multiplier: 0.001 Unit: Hz The frequency scaled PCC3300,
Frequency version of the final PCC2300,
Reference Offset: 0 Lower Limit: 0 speed reference PCC3300V2
Size (bits): 32 Upper Limit: 100
Sign: U
40596 Final Read Only Multiplier: 0.001 Unit: Hz The frequency scaled PCC3300,
Frequency version of the final PCC2300,
Reference Offset: 0 Lower Limit: 0 speed reference PCC3300V2
Size (bits): 32 Upper Limit: 100
Sign: U
40600 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40601 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40602 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40603 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40604 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40605 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40606 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40607 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40608 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40609 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40610 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40611 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40612 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40613 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40614 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40615 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #1 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40620 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40621 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40622 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40623 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40624 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40625 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40626 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40627 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40628 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40629 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40630 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40631 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40632 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40633 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40634 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40635 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #2 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40640 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40641 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40642 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40643 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40644 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40645 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40646 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40647 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40648 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40649 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40650 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40651 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40652 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40653 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40654 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40655 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #13 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40660 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40661 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40662 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40663 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40664 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40665 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40666 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40667 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40668 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40669 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40670 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40671 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40672 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40673 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40674 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40675 Configurable Read/Write Multiplier: 1 Unit: Trim to define the 16 PCC3300,
Input #14 character string for PCC2300,
Fault Text Offset: 0 Lower Limit: use by the Operator PCC3300V2
Size (bits): 136 Upper Limit: panel when this fault
becomes active.
Sign: C
40709 Device Type Read Only Multiplier: 1 Unit: This modbus register PCC3300,
(Modlon) is created for Modlon PCC3300V2
Offset: 0 Lower Limit: register mapping. This
Size (bits): 8 Upper Limit: parameter is not
associated with any
Sign: U logical.
40710 Control Read Only 0: Off This modbus register PCC3300,
Switch is created for Modlon PCC3300V2
Position 1: Manual register mapping.
(Modlon) 2: Auto
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40711 Genset Run Read Only 0: Stop This modbus register PCC3300,
Sequence is created for Modlon PCC3300V2
State 1: Time Delay to register mapping.
(Modlon) Start
2: Warmup at
Idle
3: Rated Freq
and Voltage
4: Cooldown /
Stop Delay
5: Cooldown at
Idle
6: Rated to Idle
Trasition Delay
40712 Most Recent Read Only Multiplier: 1 Unit: Fault Code This modbus register PCC3300,
Fault or is created for Modlon PCC3300V2
Warning Offset: 0 Lower Limit: register mapping. This
(Modlon) Size (bits): 16 Upper Limit: modbus register is not
associated with any
Sign: U logical Address
40713 Fault Type Read Only 0: None This modbus register PCC3300,
(Modlon) is created for modlon PCC3300V2
1: Warning register mapping. This
2: Derate modbus register is not
associated with any
3: Shutdown with logical address.
Cooldown
4: Shutdown
40714 Genset % Read Only Multiplier: 0.5 Unit: % This modbus register PCC3300,
Standby is created for modlon PCC3300V2
Total kW Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Monitors the total
generator set standby
Sign: U KW percentage
output. Modbus has
different multiplier than
PCCnet. For Modlon
use only, use
multiplier 0.5 %
40715 Genset Total Read Only Multiplier: 1 Unit: kW This modbus register PCC3300,
kW (Modlon is created for modlon PCC3300V2
GenStatus) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set total
kW.
Sign: S
TABLE 37.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40716 NFPA 110 Read Only Multiplier: 1 Unit: This modbus register PCC3300,
Logical is created for modlon PCC3300V2
Status Offset: 0 Lower Limit: register mapping. 32-
(Modlon) Size (bits): 32 Upper Limit: bit number to
represent the status of
Sign: U the NFPA 110 logical.
See NFPA110 bitmap.
40717 NFPA 110 Read Only Multiplier: 1 Unit: This modbus register PCC3300,
Logical is created for modlon PCC3300V2
Status Offset: 0 Lower Limit: register mapping. 32-
(Modlon) Size (bits): 32 Upper Limit: bit number to
represent the status of
Sign: U the NFPA 110 logical.
See NFPA110 bitmap.
40718 Genset Read Only Multiplier: 0.1 Unit: Hz This modbus register PCC3300,
Frequency is created for modlon PCC3300V2
OP (Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set
Frequency OP.
Sign: U Modbus has different
multiplier than
PCCnet. For Modlon
use only,
Multiplier/Units = 0.1
Hz
40719 Genset Total Read Only Multiplier: Unit: PF This modbus register PCC3300,
Power Factor 0.00005 is created for modlon PCC3300V2
(Modlon) register mapping.
Offset: 0 Lower Limit: Generator set total
Size (bits): 16 Upper Limit: power factor
(L1+L2+L3). Modbus
Sign: S and PCCnet has
different multiplier
value. For Modlon,
use 0.00005 PF.
40720 Genset Total Read Only Multiplier: 1 Unit: kVA This modbus register PCC3300,
kVA is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set total
kVA
Sign: U
40721 Genset Total Read Only Multiplier: 1 Unit: kW This modbus register PCC3300,
kW (Modlon is created for modlon PCC3300V2
GenACData) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set total kW
in Gen AC Data.
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40722 Genset Total Read Only Multiplier: 1 Unit: kVAR This modbus register PCC3300,
kVAR is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set total
kVAR
Sign: S
40723 Genset L1L2 Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L1L2
voltage
Sign: U
40724 Genset L2L3 Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L2L3
voltage
Sign: U
40725 Genset L3L1 Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L3L1
voltage
Sign: U
40726 Genset L1N Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L1N
voltage
Sign: U
40727 Genset L2N Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L2N
voltage
Sign: U
40728 Genset L3N Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L3N
voltage
Sign: U
40729 Genset L1 Read Only Multiplier: 1 Unit: Amps This modbus register PCC3300,
Current is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Monitors the generator
set L1 current value.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40730 Genset L2 Read Only Multiplier: 1 Unit: Amps This modbus register PCC3300,
Current is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L2
current
Sign: U
40731 Genset L3 Read Only Multiplier: 1 Unit: Amps This modbus register PCC3300,
Current is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Generator set L3
current
Sign: U
40732 Genset % Read Only Multiplier: 0.5 Unit: % This modbus register PCC3300,
Standby L1 is created for modlon PCC3300V2
Current Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Monitors the generator
set standby L1 current
Sign: U percentage output.
Modbus and PCCnet
have different
multiplier value. For
modlon use 0.5 %
40733 Genset % Read Only Multiplier: 0.5 Unit: % This modbus register PCC3300,
Standby L2 is created for modlon PCC3300V2
Current Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Monitors the generator
set standby L2 current
Sign: U percentage output.
Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.5 %
40734 Genset % Read Only Multiplier: 0.5 Unit: % This modbus register PCC3300,
Standby L3 is created for modlon PCC3300V2
Current Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Monitors the generator
set standby L3 current
Sign: U percentage output.
Modbus and PCCnet
has different multiplier
value. For Modlon use
0.5 %
40735 Battery Read Only Multiplier: 0.1 Unit: Vdc This modbus register PCC3300,
Voltage is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Battery voltage value.
Modbus and PCCnet
Sign: U has different multiplier
value. For Modlon use
0.1Volts
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40736 Oil Pressure Read Only Multiplier: 0.1 Unit: kPa This modbus register PCC3300,
(Modlon) is created for modlon PCC3300V2
Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Monitor point for the
Oil Pressure. Modbus
Sign: U and PCCnet have
different multiplier
value. For modlon,
use 0.1 KPA
40737 Oil Read Only Multiplier: 0.1 Unit: degK This modbus register PCC3300,
Temperature is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Monitor point for the
Oil Temperature.
Sign: S Modbus and PCCnet
has different multiplier
value. For Modlon use
0.1 deg Kelvin
40738 Coolant Read Only Multiplier: 0.1 Unit: degK This modbus register PCC3300,
Temperature is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Monitor point for the
Coolant Temperature.
Sign: S Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.1deg Kelvin.
40739 Intake Read Only Multiplier: 0.1 Unit: degK This modbus register PCC3300,
Manifold is created for modlon PCC3300V2
Temperature Offset: 0 Lower Limit: -40 register mapping. To
(Modlon) Size (bits): 16 Upper Limit: 410 monitor Intake
Manifold Temperature.
Sign: S Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.1 deg Kelvin
40740 Fuel Read Only Multiplier: 0.1 Unit: degK This modbus register PCC3300,
Temperature is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: -40 register mapping.
Size (bits): 16 Upper Limit: 410 Monitor point for the
Fuel Temperature.
Sign: S Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.1 deg Kelvin.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40741 Fuel Rate Read Only Multiplier: 0.01 Unit: gal/hr This modbus register PCC3300,
(Modlon) is created for modlon PCC3300V2
Offset: 0 Lower Limit: register mapping.
Size (bits): 16 Upper Limit: Monitor point for the
Fuel Rate. Modbus
Sign: U and PCCnet has
different multiplier
value. For Modlon,
use 0.01 gph
40742 Average Read Only Multiplier: 1 Unit: rpm This modbus register PCC3300,
Engine is created for modlon PCC3300V2
Speed Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Monitor point for the
Average Engine
Sign: U Speed. Modbus and
PCCnet have different
multiplier value. For
Modlon, use 1 rpm.
40743 Total Read Only Multiplier: 1 Unit: This modbus register PCC3300,
Number of is created for modlon PCC3300V2
Runs Offset: 0 Lower Limit: 0 register mapping.
(Modlon) Size (bits): 32 Upper Limit: Total number of
4294967295 generator set runs.
Sign: U
40744 Engine Read Only Multiplier: 0.1 Unit: seconds This modbus register PCC3300,
Running is created for modlon PCC3300V2
Time Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Total engine run time.
Modbus has different
Sign: U multiplier than
PCCnet. For Modbus,
use 0.1 sec
40745 Engine Read Only Multiplier: 0.1 Unit: seconds This modbus register PCC3300,
Running is created for modlon PCC3300V2
Time Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Total engine run time.
Modbus has different
Sign: U multiplier than
PCCnet. For Modbus,
use 0.1 sec
40746 Genset Total Read Only Multiplier: 1 Unit: kWh This modbus register PCC3300,
Net kWh is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
-2147483648 Generator set total net
Size (bits): 32 Upper Limit: kWh accumulation
2147483643
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40747 Genset Total Read Only Multiplier: 1 Unit: kWh This modbus register PCC3300,
Net kWh is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
-2147483648 Generator set total net
Size (bits): 32 Upper Limit: kWh accumulation
2147483643
Sign: S
40748 Total Fuel Read Only Multiplier: 0.01 Unit: gallons This modbus register PCC3300,
Consumption is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 32 Upper Limit: Total fuel consumption
since start of engine.
Sign: U Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.01 Gallons
40749 Total Fuel Read Only Multiplier: 0.01 Unit: gallons This modbus register PCC3300,
Consumption is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: register mapping.
Size (bits): 32 Upper Limit: Total fuel consumption
since start of engine.
Sign: U Modbus and PCCnet
has different multiplier
value. For Modlon,
use 0.01 Gallons
40750 Utility/Genset Read Only Multiplier: 0.1 Unit: Hz This modbus register PCC3300,
Bus is created for modlon PCC3300V2
Frequency Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility line frequency or
Generator set Bus
Sign: U Frequency depending
on Paralleling
Application. Modbus
and PCCnet has
different multiplier
value. For Modlon,
use 0.1 Hz.
40751 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L1L2 is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L1L2 Voltage or
Generator set Bus
Sign: U L1L2 voltage
depending on
paralleling application.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40752 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L2L3 is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L2L3 voltage
Sign: U
40753 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L3L1 is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L3L1 voltage or
Generator set Bus
Sign: U L3L1 voltage
depending on
paralleling application.
40754 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L1N is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L1N voltage or
Generator set Bus
Sign: U L1N voltage
depending on
paralleling application.
40755 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L2N is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L2N voltage or
Generator set Bus
Sign: U L2N voltage
depending on
paralleling application.
40756 Utility/Genset Read Only Multiplier: 1 Unit: Vac This modbus register PCC3300,
Bus L3N is created for modlon PCC3300V2
Voltage Offset: 0 Lower Limit: register mapping.
(Modlon) Size (bits): 16 Upper Limit: Utility L3N voltage or
Generator set Bus
Sign: U L3N voltage
depending on
paralleling application.
40757 Customer Read Only Multiplier: 1 Unit: This modbus register PCC3300,
Faults is created for modlon PCC3300V2
(Modlon) Offset: 0 Lower Limit: 0 register mapping. 16
Size (bits): 16 Upper Limit: bit fault bitmap for
65530 modbus interface.
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40760 ES State Read Only 0: Standby This modbus register PCC3300,
(Modlon) is created for modlon PCC3300V2
1: Dead Bus register mapping.
2: Synchronize Internal paralleling
status variable
3: Load Share
4: Load Govern
40761 Load Read Only 0: Inactive This modbus register PCC3300,
Demand is created for modlon PCC3300V2
Stop 1: Active register mapping.
Command Modbus input for load
(Modlon) demand stop
command.
40764 Genset CB Read Only 0: Open This modbus register PCC3300,
Position is created for modlon PCC3300V2
Status 1: Closed register mapping.
(Modlon) 2: Not Available indicates generator set
breaker position
40765 Utility CB Read Only 0: Open This modbus register PCC3300,
Position is created for modlon PCC3300V2
Status 1: Closed register mapping.
(Modlon) 2: Not Available indicates utility breaker
position
40766 Remote Start Read/Write 0: Inactive This modbus register PCC3300,
Switch(Modlo is created for modlon PCC3300V2
n) 1: Active register mapping.
Modbus Remote Start
40767 Fault Reset Read/Write 0: Inactive This modbus register PCC3300,
(Modlon) is created for modlon PCC3300V2
1: Active register mapping.
Modbus fault reset.
40768 System Read Only 0: Inactive Indicates PCC3300,
Network communication status PCC3300V2
Datalink 1: Active of the local generator
Status 2: Failed set on System
Network (used for load
demand).
40769 Load Read/Write Multiplier: 0.1 Unit: hours Run hour accumulator PCC3300,
Demand used for load demand PCC3300V2
Genset Run Offset: 0 Lower Limit: 0 run hour equalization.
Hours Size (bits): 32 Upper Limit: This is writable.
999999.9
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40770 Load Read/Write Multiplier: 0.1 Unit: hours Run hour accumulator PCC3300,
Demand used for load demand PCC3300V2
Genset Run Offset: 0 Lower Limit: 0 run hour equalization.
Hours Size (bits): 32 Upper Limit: This is writable.
999999.9
Sign: U
40771 Load Read Only 0: Inactive Indicates the status of PCC3300,
Demand the spare capacity PCC3300V2
Spare 1: Active request input. When
Capacity ACTIVE additional
Request spare capacity (set by
Status Load Demand Spare
Capacity Request
Value) is requested.
40772 System Read Only 0: OFF Indicates the status of PCC3300,
Network the on-board CAN PCC3300V2
Termination 1: ON termination resistor
Resistor 2: Reserved switch (S1).
Switch
Status 3: N/A
4: Network
Failure
40773 Genset ID Read/Write 0: Gen1 Generator set PCC3300,
identifier. All load PCC3300V2
1: Gen2 demand generator
2: Gen3 sets must have a
unique Generator set
3: Gen4 ID.
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40774 Load Read/Write Multiplier: 1 Unit: kW Sets the kW value of PCC3300,
Demand additional capacity to PCC3300V2
Spare Offset: 0 Lower Limit: 0 be requested from the
Capacity Size (bits): 32 Upper Limit: system when the Load
Request 80000 Demand Spare
Value Capacity Request
Sign: U Status is YES.
40775 Load Read/Write Multiplier: 1 Unit: kW Sets the kW value of PCC3300,
Demand additional capacity to PCC3300V2
Spare Offset: 0 Lower Limit: 0 be requested from the
Capacity Size (bits): 32 Upper Limit: system when the Load
Request 80000 Demand Spare
Value Capacity Request
Sign: U Status is YES.
40776 Load Read/Write 0: Disable Disables or Enables PCC3300,
Demand load demand on this PCC3300V2
Genset 1: Enable genset only. When set
Enable to disable the genset
is not included in the
load demand system
and can be removed
without triggering a
com error.
40777 System Read Only 0: Out of Sync Indicates whether the PCC3300,
Settings system settings on the PCC3300V2
Status 1: In Sync local genset are in
2: Standalone sync with ones from
other genset in the
network.
40778 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40779 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40780 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40781 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40782 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40783 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40784 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40785 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40786 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40787 ECM 2 Code Read Only Multiplier: 1 Unit: "ECM 2 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40788 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40789 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40790 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40791 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40792 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40793 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40794 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40795 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40796 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40797 ECM 3 Code Read Only Multiplier: 1 Unit: "ECM 3 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
40800 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40801 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40802 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40803 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40804 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40805 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40806 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40807 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40808 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40809 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40810 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40811 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40812 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40813 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40814 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40815 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40816 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40817 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40818 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40819 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40820 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40821 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40822 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40823 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40824 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40825 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40826 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40827 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40828 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40829 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40830 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40831 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40832 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40833 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40834 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40835 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40836 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40837 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40838 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40839 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
40840 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40841 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40842 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40843 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40844 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40845 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40846 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40847 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40848 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40849 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40850 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40851 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40852 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40853 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40854 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40855 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40856 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40857 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40858 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40859 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40860 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40861 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40862 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40863 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40864 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40865 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40866 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40867 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40868 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40869 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40870 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40871 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40872 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40873 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40874 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40875 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40876 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40877 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40878 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40879 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40880 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40881 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40882 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40883 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40884 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40885 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40886 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40887 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40888 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40889 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40890 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40891 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40892 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40893 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40894 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40895 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40896 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40897 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40898 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40899 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40900 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40901 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40902 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40903 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40904 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40905 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40906 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40907 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40908 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40909 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40910 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40911 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40912 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40913 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40914 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
TABLE 38.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40915 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40916 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40917 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40918 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40919 Aux102 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40920 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40921 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40922 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40923 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40924 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40925 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40926 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40927 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40928 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40929 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40930 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40931 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40932 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40933 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40934 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40935 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40936 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40937 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40938 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40939 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 9 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40940 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40941 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40942 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40943 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40944 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40945 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40946 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40947 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40948 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40949 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40950 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40951 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40952 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40953 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40954 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40955 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40956 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40957 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40958 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40959 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 10 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40960 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40961 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40962 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40963 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40964 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40965 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40966 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40967 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40968 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40969 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40970 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40971 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40972 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40973 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40974 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40975 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40976 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40977 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40978 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40979 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 11 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40980 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40981 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40982 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40983 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40984 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40985 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40986 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40987 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40988 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40989 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40990 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40991 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40992 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40993 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40994 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40995 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40996 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40997 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
40998 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
40999 Aux102 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Fault 12 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
41000 Load Read/Write 0: Disable Disables or Enables PCC3300,
Demand load demand PCC3300V2
System 1: Enable operation of all
Enable connected gensets.
41001 Load Read/Write 0: Run Hours Sets the sequencing PCC3300,
Demand Equalization priority for load PCC3300V2
Type demand.
1: Fixed
Sequence
41002 Load Read/Write 0: kW Sets whether the load PCC3300,
Demand demand start/stop PCC3300V2
Threshold 1: %kW control is based on a
Method relative (%) or
absolute (kW)
threshold.
41003 Load Read/Write Multiplier: 1 Unit: % When the ratio of load PCC3300,
Demand to capacity is greater PCC3300V2
Start Offset: 0 Lower Limit: 25 than this value the
Threshold Size (bits): 8 Upper Limit: 100 next genset will start.
(%kW) Must be greater than
Sign: U Load Demand Stop
Threshold by at least
5%.
41004 Load Read/Write Multiplier: 1 Unit: kW When surplus capacity PCC3300,
Demand is less than this value PCC3300V2
Start Offset: 0 Lower Limit: 5 the next genset will
Threshold Size (bits): 16 Upper Limit: start. Must be less
(kW) 5000 than Load Demand
Stop Threshold (kW).
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41005 Load Read/Write Multiplier: 1 Unit: % When the ratio of load PCC3300,
Demand to capacity is less than PCC3300V2
Stop Offset: 0 Lower Limit: 20 this value the next
Threshold Size (bits): 8 Upper Limit: 95 genset will stop. Must
(%kW) be less than Load
Sign: U Demand Start
Threshold by at least
5%.
41006 Load Read/Write Multiplier: 1 Unit: kW When surplus capacity PCC3300,
Demand is greater than this PCC3300V2
Stop Offset: 0 Lower Limit: 5 value the next genset
Threshold Size (bits): 16 Upper Limit: will stop. Must be
(kW) 5000 greater than Load
Demand Start
Sign: U Threshold (kW).
41007 Load Read/Write Multiplier: 1 Unit: hours When the difference PCC3300,
Demand Run between Load PCC3300V2
Hours Offset: 0 Lower Limit: 1 Demand Genset Run
Differential Size (bits): 16 Upper Limit: 250 Hours between any
running genset and
Sign: U any stopped genset
reaches this value the
stopped genset will be
started.
41008 Load Read/Write Multiplier: 1 Unit: seconds Sets the time delay PCC3300,
Demand that the system waits PCC3300V2
Genset Fail Offset: 0 Lower Limit: 10 for a genset to come
Delay Size (bits): 16 Upper Limit: 900 online before declaring
it as failed.
Sign: U
41009 Load Read/Write Multiplier: 1 Unit: seconds Sets the time delay PCC3300,
Demand before gensets are PCC3300V2
Initial Delay Offset: 0 Lower Limit: 60 allowed to stop after
Size (bits): 16 Upper Limit: initial start or after
1500 resuming halted load
demand.
Sign: U
41010 Load Read/Write Multiplier: 1 Unit: seconds Sets the time delay PCC3300,
Demand before next genset is PCC3300V2
Start Delay Offset: 0 Lower Limit: 0 allowed to start.
Size (bits): 16 Upper Limit:
1500
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41011 Load Read/Write Multiplier: 1 Unit: seconds Sets the time delay PCC3300,
Demand before next genset is PCC3300V2
Stop Delay Offset: 0 Lower Limit: 60 allowed to stop.
Size (bits): 16 Upper Limit:
1500
Sign: U
41012 Clear Lost Read/Write 0: No When set to YES all PCC3300,
Gensets gensets in state "Lost" PCC3300V2
Local 1: Yes will change to state
"Gen Does Not Exist"
in order to clear Lost
Genset Warning.
41013 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 1. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
1 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41014 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 2. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
2 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41015 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 3. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
3 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41016 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 4. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
4 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41017 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 5. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
5 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41018 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 6. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
6 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41019 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 7. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
7 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41020 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 8. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
8 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41021 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 9. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
9 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41022 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 10. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
10 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41023 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 11. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
11 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41024 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 12. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
12 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41025 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 13. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
13 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41026 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 14. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
14 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41027 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 15. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
15 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41028 Load Read Only 0: Gen1 Assigns a genset to PCC3300,
Demand fixed priority 16. Used PCC3300V2
Fixed Priority 1: Gen2 when Load Demand
16 2: Gen3 Type is set to Fixed
Sequence.
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
41030 Synchronize Read/Write 0: No When set to YES PCC3300,
System system settings from PCC3300V2
Settings 1: Yes the genset will be
broadcasted and
synchronized to all
other gensets in the
network.
41031 Battery Read Only 0: Inactive Battery Charger 2 PCC3300,
Charger 2 Failed Switch function PCC3300V2
Failed Switch 1: Active output status; gives
software
Inactive/Active state
41032 Battery Read Only 0: Inactive Battery Charger 3 PCC3300,
Charger 3 Failed Switch function PCC3300V2
Failed Switch 1: Active output status; gives
software
Inactive/Active state
41033 Battery Read Only 0: Inactive Battery Charger 4 PCC3300,
Charger 4 Failed Switch function PCC3300V2
Failed Switch 1: Active output status; gives
software
Inactive/Active state
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41034 Intake Air Read Only 0: Inactive Intake Air Restriction PCC3300,
Restriction Indicator 1 fault switch PCC3300V2
Indicator 1 1: Active function output status;
fault switch gives software
Inactive/Active state
41035 Intake Air Read Only 0: Inactive Intake Air Restriction PCC3300,
Restriction Indicator 2 fault switch PCC3300V2
Indicator 2 1: Active function output status;
fault switch gives software
Inactive/Active state
41036 Intake Air Read Only 0: Inactive Intake Air Restriction PCC3300,
Restriction Indicator 3 fault switch PCC3300V2
Indicator 3 1: Active function output status;
fault switch gives software
Inactive/Active state
41037 Intake Air Read Only 0: Inactive Intake Air Restriction PCC3300,
Restriction Indicator 4 fault switch PCC3300V2
Indicator 4 1: Active function output status;
fault switch gives software
Inactive/Active state
41038 Starter Air Read Only 0: Inactive "Starter Air Supply PCC3300,
Supply Pressure Low Fault PCC3300V2
Pressure 1: Active Switch function output
Low Fault status; gives software
Switch Inactive/Active"
41039 Starter Air Read Only 0: Inactive "Starter Air Tank PCC3300,
Tank Volume Volume Low Fault PCC3300V2
Low Fault 1: Active Switch function output
Switch status; gives software
Inactive/Active state"
41040 Instantaneou Read Only Multiplier: Unit: kg/hr Instantaneous PCC3300,
s HC 0.0078125 Emissions Parameter PCC3300V2
received via PGN
Offset: 0 Lower Limit: 130900 from ECM.
Size (bits): 16 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41041 Instantaneou Read Only Multiplier: Unit: kg/hr Instantaneous PCC3300,
s NOx 0.0078125 Emissions Parameter PCC3300V2
received via PGN
Offset: 0 Lower Limit: 130900 from ECM.
Size (bits): 16 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41042 Instantaneou Read Only Multiplier: Unit: kg/hr Instantaneous PCC3300V2
s CO 0.0078125 Emissions Parameter PCC3300,
received via PGN
Offset: 0 Lower Limit: 130900 from ECM.
Size (bits): 16 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41043 Instantaneou Read Only Multiplier: Unit: kg/hr Instantaneous PCC3300,
s PM 0.0078125 Emissions Parameter PCC3300V2
received via PGN
Offset: 0 Lower Limit: 130900 from ECM.
Size (bits): 16 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41044 Instantaneou Read Only Multiplier: Unit: kg/hr Instantaneous PCC3300,
s SO2 0.0078125 Emissions Parameter PCC3300V2
received via PGN
Offset: 0 Lower Limit: 130900 from ECM.
Size (bits): 16 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41045 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of HC received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41046 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of HC received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41047 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of NOx received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41048 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of NOx received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41049 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of CO received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41050 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of CO received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41051 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of PM received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41052 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of PM received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41053 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of SO2 received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41054 12 Month Read Only Multiplier: Unit: kg 12 Month Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of SO2 received via PGN
Offset: 0 Lower Limit: 130901 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41055 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of HC received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41056 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of HC received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41057 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of NOx received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41058 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of NOx received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41059 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of CO received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41060 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of CO received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41061 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of PM received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41062 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of PM received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41063 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of SO2 received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41064 Lifetime Read Only Multiplier: Unit: kg Lifetime Rolling Total PCC3300,
Rolling Total 0.0078125 Emissions Parameter PCC3300V2
Of SO2 received via PGN
Offset: 0 Lower Limit: 130902 from ECM.
Size (bits): 32 Upper Limit: The value is for
indication only, no
Sign: U accuracy figures are
available.
41065 Reverse Read Only Multiplier: 0.01 Unit: % Sets the Reverse PCC3300V2
kVAR kVAR fault trip
Threshold Offset: 0 Lower Limit: 15 threshold as
Size (bits): 16 Upper Limit: 50 percentage of Standby
kVA rating.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41066 Reverse Read Only Multiplier: 0.1 Unit: seconds Sets the Reverse PCC3300V2
kVAR Time kVAR fault trip time
Delay Offset: 0 Lower Limit: 1 delay.
Size (bits): 16 Upper Limit: 60
Sign: U
41067 High AC Read Only Multiplier: 0.01 Unit: % Percent of desired PCC3300V2
Voltage voltage at which High
Threshold Offset: 0 Lower Limit: 105 AC Voltage fault
Size (bits): 16 Upper Limit: 125 becomes active.
Sign: U
41068 High AC Read Only 0: Inverse Time “Fixed Time” setup PCC3300V2
Voltage Trip allows a greater time
Characteristi 1: Fixed Time delay until shutdown
c when voltage
overshoots (good for
starting motors). When
the control is set up to
operate as “Inverse
Time”, the fault will be
more sensitive to
voltage spikes and will
trip more rapidly.
41069 High AC Read Only Multiplier: 0.1 Unit: seconds Time delay before PCC3300V2
Voltage High AC Voltage fault
Delay Offset: 0 Lower Limit: 0.1 becomes active.
Size (bits): 8 Upper Limit: 10
Sign: U
41070 Low AC Read Only Multiplier: 0.01 Unit: % Percent of desired PCC3300V2
Voltage voltage at which Low
Threshold Offset: 0 Lower Limit: 50 AC Voltage fault
Size (bits): 16 Upper Limit: 95 becomes active.
Sign: U
41071 Low AC Read Only Multiplier: 0.1 Unit: seconds Time delay before Low PCC3300V2
Voltage AC Voltage fault
Delay Offset: 0 Lower Limit: 2 becomes active
Size (bits): 8 Upper Limit: 20
Sign: U
41072 Reverse kW Read Only Multiplier: 0.01 Unit: % Sets the Reverse kW PCC3300V2
Threshold fault trip threshold as
Offset: 0 Lower Limit: 5 percentage of Standby
Size (bits): 16 Upper Limit: 30 kW rating.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41073 Reverse kW Read Only Multiplier: 0.1 Unit: seconds Sets the Reverse kW PCC3300V2
Time Delay fault trip time delay
Offset: 0 Lower Limit: 1
Size (bits): 8 Upper Limit: 15
Sign: U
41074 Overfrequen Read Only Multiplier: 0.1 Unit: Hz Number of Hertz PCC3300V2
cy Threshold Alternator Line
Offset: 0 Lower Limit: 2 Frequency may be
Size (bits): 8 Upper Limit: 10 over nominal
frequency before
Sign: U Overfrequency fault
becomes active.
41075 Overfrequen Read Only Multiplier: 0.1 Unit: seconds Time delay before PCC3300V2
cy Delay Overfrequency fault
Offset: 0 Lower Limit: 1 becomes active.
Size (bits): 8 Upper Limit: 20
Sign: U
41076 Underfreque Read Only Multiplier: 0.1 Unit: Hz Number of Hertz PCC3300V2
ncy Alternator Line
Threshold Offset: 0 Lower Limit: 0.1 Frequency may be
Size (bits): 16 Upper Limit: 10 under nominal
frequency before
Sign: U Underfrequency fault
becomes active.
41077 Underfreque Read Only Multiplier: 0.1 Unit: seconds Time delay before the PCC3300V2
ncy Delay Underfrequency fault
Offset: 0 Lower Limit: 1 becomes active.
Size (bits): 8 Upper Limit: 20
Sign: U
41078 Custom Read Only 0: Disabled use to enable custom PCC3300V2
Overcurrent time overcurrent
Protection 1: Enabled protection
Enable
41079 Custom Read Only Multiplier: 0.1 Unit: % % standby current PCC3300V2
Overcurrent above which custom
Threshold Offset: 0 Lower Limit: 50 overcurrent feature
Size (bits): 16 Upper Limit: 150 starts timing
Sign: U
41080 Custom Read Only Multiplier: 0.001 Unit: seconds sets the timing PCC3300V2
Overcurrent characteristic of
Time Offset: 0 Lower Limit: 0.1 custom overcurrent
Characteristi Size (bits): 16 Upper Limit: 65
c
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41081 Aux101 Read Only Multiplier: 1 Unit: degF Low limit for the LBNG PCC3300V2
LBNG Aux 101 I/O Module
Alternator Offset: 0 Lower Limit: 0 Alternator Temp Out
Temp OOR Size (bits): 16 Upper Limit: 509 of Range faults.
High Limit
Sign: U
41082 Aux101 Read Only Multiplier: 1 Unit: degF Low limit for the LBNG PCC3300V2
LBNG Aux 101 I/O Module
Alternator Offset: 0 Lower Limit: 0 Alternator Temp Out
Temp OOR Size (bits): 16 Upper Limit: 509 of Range faults.
Low Limit
Sign: U
41083 Aux101 Read Only Multiplier: 1 Unit: degF High limit for the PCC3300V2
LBNG LBNG Aux 101 I/O
Drive/Non- Offset: 0 Lower Limit: 0 Module Drive/Non-
Drive End Size (bits): 16 Upper Limit: 509 Drive End Bearing
Bearing Temp Out of Range
Temp OOR Sign: U faults.
High Limit
41084 Aux101 Read Only Multiplier: 1 Unit: degF Low limit for the LBNG PCC3300V2
LBNG Aux 101 I/O Module
Drive/Non- Offset: 0 Lower Limit: 0 Drive/Non-Drive End
Drive End Size (bits): 16 Upper Limit: 509 Bearing Temp Out of
Bearing Range faults.
Temp OOR Sign: U
Low Limit
41085 Application Read Only 0: Standby Selects genset's PCC3300V2
Rating Select standby/prime/base
1: Prime application rating.
2: Base
41086 AVR Read Only Multiplier: 0.01 Unit: Increases or PCC3300V2
Damping decreases the output
Effect (50 Offset: 0 Lower Limit: 0 response of the AVR.
Hz) Size (bits): 16 Upper Limit: A lower input value will
99.99 increase the transient
response. A higher
Sign: U value will decrease the
transient response.
41087 AVR Read Only Multiplier: 0.01 Unit: Increases or PCC3300V2
Damping decreases the output
Effect (60 Offset: 0 Lower Limit: 0 response of the AVR.
Hz) Size (bits): 16 Upper Limit: A lower input value will
99.99 increase the transient
response. A higher
Sign: U value will decrease the
transient response.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41088 V/Hz Method Read Only 0: Fixed Knee Sets the knee PCC3300V2
Frequency frequency logic
characteristic of the
1: Relative Knee V/Hz curve either fixed
Frequency knee or relative (to
Target Speed) knee
frequency.
41089 AmpSentry Read Only 0: Disable "Disable Override PCC3300V2
Maintenance function for AmpSentry
Mode 1: Enable Maintenance Mode.
Disable Used for engineering
Override purposes and heavy
motors starting that
may look like a short
circuit"
41090 High Read Only Multiplier: 1 Unit: degF High Alternator PCC3300V2
Alternator Temperature 1
Temperature Offset: 0 Lower Limit: 100 Shutdown Threshold
1 Shutdown Size (bits): 16 Upper Limit: for the I/O Module
Threshold 1000 Fault (AUX 101)
Sign: S
41091 High Read Only Multiplier: 0.1 Unit: seconds High Alternator PCC3300V2
Alternator Temperature 1
Temperature Offset: 0 Lower Limit: 1 Shutdown Time for the
1 Shutdown Size (bits): 16 Upper Limit: 30 I/O Module Fault (AUX
Time 101)
Sign: U
41092 High Read Only Multiplier: 1 Unit: degF High Alternator Temp PCC3300V2
Alternator 1 Threshold for the I/O
Temperature Offset: 0 Lower Limit: 100 Module fault. Warning
1 Threshold Size (bits): 16 Upper Limit: Threshold
(Aux101) 1000
Sign: S
41093 High Read Only Multiplier: 0.1 Unit: seconds High Alternator Temp PCC3300V2
Alternator 1 fault time for the I/O
Temperature Offset: 0 Lower Limit: 0.1 Module fault. Warning
1 Time Size (bits): 16 Upper Limit: 30 Time
(Aux101)
Sign: U
41094 High Read Only Multiplier: 1 Unit: degF High Alternator PCC3300V2
Alternator Temperature 2
Temperature Offset: 0 Lower Limit: 100 Shutdown Threshold
2 Shutdown Size (bits): 16 Upper Limit: for the I/O Module
Threshold 1000 Fault
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41095 High Read Only Multiplier: 0.1 Unit: seconds High Alternator PCC3300V2
Alternator Temperature 2
Temperature Offset: 0 Lower Limit: 1 Shutdown Time for the
2 Shutdown Size (bits): 16 Upper Limit: 30 I/O Module Fault
Time
Sign: U
41096 High Read Only Multiplier: 1 Unit: degF High Alternator Temp PCC3300V2
Alternator 2 Threshold for the I/O
Temperature Offset: 0 Lower Limit: 100 Module fault. Warning
2 Threshold Size (bits): 16 Upper Limit: Threshold
(Aux101) 1000
Sign: S
41097 High Read Only Multiplier: 0.1 Unit: seconds High Alternator Temp PCC3300V2
Alternator 2 fault time for the I/O
Temperature Offset: 0 Lower Limit: 0.1 Module fault. Warning
2 Time Size (bits): 16 Upper Limit: 30 Time.
(Aux101)
Sign: U
41098 High Read Only Multiplier: 1 Unit: degF High Alternator PCC3300V2
Alternator Temperature 3
Temperature Offset: 0 Lower Limit: 100 Shutdown Threshold
3 Shutdown Size (bits): 16 Upper Limit: for the I/O Module
Threshold 1000 Fault
Sign: S
41099 High Read Only Multiplier: 0.1 Unit: seconds High Alternator PCC3300V2
Alternator Temperature 3
Temperature Offset: 0 Lower Limit: 1 Shutdown Time for the
3 Shutdown Size (bits): 16 Upper Limit: 30 I/O Module Fault
Time
Sign: U
41100 High Read Only Multiplier: 1 Unit: degF High Alternator Temp PCC3300V2
Alternator 3 Threshold for the I/O
Temperature Offset: 0 Lower Limit: 100 Module fault. Warning
3 Threshold Size (bits): 16 Upper Limit: Threshold
(Aux101) 1000
Sign: S
41101 High Read Only Multiplier: 0.1 Unit: seconds High Alternator Temp PCC3300V2
Alternator 3 fault time for the I/O
Temperature Offset: 0 Lower Limit: 1 Module fault. Warning
3 Time Size (bits): 16 Upper Limit: 30 Time.
(Aux101)
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41102 AUX101 DE Read Only 0: Disable Enables the Drive End PCC3300V2
Temp Bearing Temperature
Shutdown 1: Enable shutdown Fault for
Fault Enable Non LBNG
applications.
41103 High Drive Read Only Multiplier: 1 Unit: degF High Drive End PCC3300V2
End Bearing Bearing Temperature
Temperature Offset: 0 Lower Limit: 100 Shutdown Threshold
Shutdown Size (bits): 16 Upper Limit: for the I/O Module
Threshold 1000 Fault
Sign: S
41104 High Drive Read Only Multiplier: 0.1 Unit: seconds High Drive End PCC3300V2
End Bearing Bearing Temperature
Temperature Offset: 0 Lower Limit: 1 Shutdown Time for the
Shutdown Size (bits): 16 Upper Limit: 30 I/O Module Fault
Time
Sign: U
41105 High Drive Read Only Multiplier: 1 Unit: degF High Drive End PCC3300V2
End Bearing Bearing Temp
Temperature Offset: 0 Lower Limit: 100 Threshold for the I/O
Threshold Size (bits): 16 Upper Limit: Module fault.
(Aux101) 1000
Sign: S
41106 High Drive Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
End Bearing the High Drive End
Temperature Offset: 0 Lower Limit: 0.1 Bearing Temp fault
Time Size (bits): 16 Upper Limit: 30 becomes active, from
(Aux101) the I/O Module.
Sign: U
41107 High Exhaust Read Only Multiplier: 1 Unit: degF High Exhaust Stack PCC3300V2
Stack Temp 1 Threshold for
Temperature Offset: 0 Lower Limit: 200 the I/O Module fault.
1 Threshold Size (bits): 16 Upper Limit:
(Aux101) 1600
Sign: S
41108 High Exhaust Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Stack the High Exhaust
Temperature Offset: 0 Lower Limit: 0.1 Stack Temp 1 fault
1 Time Size (bits): 16 Upper Limit: 30 becomes active, from
(Aux101) the I/O Module.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41109 High Exhaust Read Only Multiplier: 1 Unit: degF High Exhaust Stack PCC3300V2
Stack Temp 2 Threshold for
Temperature Offset: 0 Lower Limit: 200 the I/O Module fault.
2 Threshold Size (bits): 16 Upper Limit:
(Aux101) 1600
Sign: S
41110 High Exhaust Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Stack the High Exhaust
Temperature Offset: 0 Lower Limit: 0.1 Stack Temp 2 fault
2 Time Size (bits): 16 Upper Limit: 30 becomes active, from
(Aux101) the I/O Module.
Sign: U
41111 High Oil Read Only Multiplier: 1 Unit: degF High Oil Temp PCC3300V2
Temperature Threshold for the I/O
Threshold Offset: 0 Lower Limit: 100 Module HOT fault.
(Aux101) Size (bits): 16 Upper Limit: 300
Sign: S
41112 High Oil Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Temperature the High Oil Temp
Time Offset: 0 Lower Limit: 0.1 fault becomes active,
(Aux101) Size (bits): 16 Upper Limit: 30 from the I/O Module.
Sign: U
41113 High Intake Read Only Multiplier: 1 Unit: degF High Intake Manifold PCC3300V2
Manifold Temp 1 Threshold for
Temperature Offset: 0 Lower Limit: 100 the I/O Module fault.
1 Threshold Size (bits): 16 Upper Limit: 270
(Aux101)
Sign: S
41114 High Intake Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Temperature the High Intake
1 Time Offset: 0 Lower Limit: 0.1 Manifold Temp 1 fault
(Aux101) Size (bits): 16 Upper Limit: 30 becomes active, from
the I/O Module.
Sign: U
41115 AUX101 Read Only 0: Disable Enables the Non Drive PCC3300V2
NDE Temp End Bearing
Shutdown 1: Enable Temperature
Fault Enable shutdown Fault for
Non LBNG
applications.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41116 High Non- Read Only Multiplier: 1 Unit: degF High Non-Drive End PCC3300V2
Drive End Bearing Temperature
Bearing Offset: 0 Lower Limit: 100 Shutdown Threshold
Temperature Size (bits): 16 Upper Limit: for the I/O Module
Shutdown 1000 Fault
Threshold
Sign: S
41117 High Non- Read Only Multiplier: 0.1 Unit: seconds High Non-Drive End PCC3300V2
Drive End Bearing Temperature
Bearing Offset: 0 Lower Limit: 1 Shutdown Time for the
Temperature Size (bits): 16 Upper Limit: 30 I/O Module Fault
Shutdown
Time Sign: U
41118 High Non- Read Only Multiplier: 1 Unit: degF High Non-Drive End PCC3300V2
Drive End Bearing Temp
Bearing Offset: 0 Lower Limit: 100 Threshold for the I/O
Temperature Size (bits): 16 Upper Limit: Module fault.
Threshold 1000
(Aux101)
Sign: S
41119 High Non- Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Drive End the High Non-Drive
Bearing Offset: 0 Lower Limit: 0.1 End Bearing Temp
Temperature Size (bits): 16 Upper Limit: 30 fault becomes active,
Time from the I/O Module.
(Aux101) Sign: U
41120 High Fuel Read Only Multiplier: 0.1 Unit: % High Fuel Level PCC3300V2
Level Threshold for the I/O
Threshold Offset: 0 Lower Limit: 50 Module fault.
(Aux101) Size (bits): 16 Upper Limit: 100
Sign: U
41121 High Fuel Read Only Multiplier: 0.1 Unit: seconds The time delay until PCC3300V2
Level Time the High Fuel Level
(Aux101) Offset: 0 Lower Limit: 0.1 fault becomes active,
Size (bits): 16 Upper Limit: 30 from the I/O Module.
Sign: U
41122 Low Fuel Read Only Multiplier: 0.1 Unit: % Low Fuel Level PCC3300V2
Level Threshold for the I/O
Threshold Offset: 0 Lower Limit: 10 Module fault.
(Aux101) Size (bits): 16 Upper Limit: 70
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41123 Low Fuel Read Only Multiplier: 0.1 Unit: seconds Low Fuel Level fault PCC3300V2
Level Time time for the I/O
(Aux101) Offset: 0 Lower Limit: 0.1 Module fault.
Size (bits): 16 Upper Limit: 30
Sign: U
41124 Very Low Read Only Multiplier: 0.1 Unit: % Very Low Fuel Level PCC3300V2
Fuel Level Threshold for the AUX
Threshold Offset: 0 Lower Limit: 0 101 I/O Module fault.
(Aux101) Size (bits): 16 Upper Limit: 50
Sign: U
41125 Very Low Read Only Multiplier: 0.1 Unit: seconds Very Low Fuel Level PCC3300V2
Fuel Level fault time for the AUX
Time Offset: 0 Lower Limit: 0.1 101 I/O Module fault.
(Aux101) Size (bits): 16 Upper Limit: 30
Sign: U
41126 Fuel Level Read Only Multiplier: 1 Unit: Ohm During setup this trim PCC3300V2
100 Percent is set the 100%
Resistance Offset: 0 Lower Limit: 30 resistance, when the
(Aux101) Size (bits): 16 Upper Limit: fuel tank is full.
2500
Sign: U
41127 Fuel Level Read Only Multiplier: 1 Unit: Ohm Trim to set the 0% (or PCC3300V2
Zero Percent empty) resistance
Resistance Offset: 0 Lower Limit: 0 level on the sensor for
(Aux101) Size (bits): 16 Upper Limit: the tank to be
2500 measured.
Sign: U
41128 Fuel Tank Read Only Multiplier: 1 Unit: gallons Trim to set the fuel PCC3300V2
Capacity tank capacity.
(Aux101) Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
15000
Sign: U
41129 Aux101 Read Only 0: Disable Enables the Aux 101 PCC3300V2
Alternator I/O Module Alternator
Temperature 1: Enable Temp Out of Range
OOR Check faults. For use with
Enable either LBNG or non-
LBNG gensets.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41130 Aux101 Read Only Multiplier: 0.1 Unit: seconds Time limit for the Aux PCC3300V2
Alternator 101 I/O Module
Temperature Offset: 0 Lower Limit: 0 Alternator Temp Out
OOR Time Size (bits): 16 Upper Limit: 10 of Range faults. For
use with either LBNG
Sign: U or non-LBNG gensets.
41131 Aux101 Read Only 0: Disable Enable the Aux 101 PCC3300V2
Ambient I/O Module Ambient
Temp OOR 1: Enable Temp Out of Range
Check faults
Enable
41132 Aux101 Drive Read Only 0: Disable Enable the Aux 101 PCC3300V2
End Bearing I/O Module Drive End
Temperature 1: Enable Bearing Temp Out of
OOR Check Range faults. For use
Enable with either LBNG or
non-LBNG gensets.
41133 Aux101 Read Only Multiplier: 0.01 Unit: Vdc High limit for the Aux PCC3300V2
Drive/Non- 101 I/O Module
Drive End Offset: 0 Lower Limit: 0 Drive/Non-Drive End
Bearing Size (bits): 16 Upper Limit: 5 Bearing Temp Out of
Temp OOR Range faults.
High Limit Sign: S
41134 Aux101 Read Only Multiplier: 0.01 Unit: Vdc Low limit for the Aux PCC3300V2
Drive/Non- 101 I/O Module
Drive End Offset: 0 Lower Limit: 0 Drive/Non-Drive End
Bearing Size (bits): 16 Upper Limit: 5 Bearing Temp Out of
Temp OOR Range faults.
Low Limit Sign: S
41135 Aux101 Read Only Multiplier: 0.1 Unit: seconds Time limit for the Aux PCC3300V2
Drive/Non- 101 I/O Module
Drive End Offset: 0 Lower Limit: 0 Bearing Temp Out of
Bearing Size (bits): 16 Upper Limit: 10 Range faults. For use
Temperature with either LBNG or
OOR Time Sign: U non-LBNG gensets.
41136 Aux101 Read Only 0: Disable Enables the Aux 101 PCC3300V2
Exhaust I/O Module Exhaust
Stack Temp 1: Enable Stack Temp 1 Out of
1 OOR Range fault.
Check
Enable
41137 Aux101 Read Only 0: Disable Enables the Aux 101 PCC3300V2
Exhaust I/O Module Exhaust
Stack Temp 1: Enable Stack Temp 2 Out of
2 OOR Range fault.
Check
Enable
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41138 Aux101 Read Only Multiplier: 0.01 Unit: Vdc High limit for the Aux PCC3300V2
Exhaust 101 I/O Module
Stack Temp Offset: 0 Lower Limit: 0 Exhaust Stack Temp
OOR High Size (bits): 16 Upper Limit: 5 Out of Range faults.
Limit
Sign: S
41139 Aux101 Read Only Multiplier: 0.01 Unit: Vdc Low limit for the Aux PCC3300V2
Exhaust 101 I/O Module
Stack Temp Offset: 0 Lower Limit: 0 Exhaust Stack Temp
OOR Low Size (bits): 16 Upper Limit: 5 Out of Range faults.
Limit
Sign: S
41140 Aux101 Read Only Multiplier: 0.1 Unit: seconds Time limit for the Aux PCC3300V2
Exhaust 101 I/O Module
Stack Temp Offset: 0 Lower Limit: 0 Exhaust Stack Temp
OOR Time Size (bits): 16 Upper Limit: 10 Out of Range faults.
Sign: U
41141 Aux101 Fuel Read Only 0: Disable Enables the Aux 101 PCC3300V2
Level OOR I/O Module Fuel Level
Check 1: Enable Out of Range fault.
Enable
41142 Aux101 Fuel Read Only Multiplier: 0.01 Unit: Vdc High limit for the Aux PCC3300V2
Level OOR 101 I/O Module Fuel
High Limit Offset: 0 Lower Limit: 0 Level Out of Range
Size (bits): 16 Upper Limit: 5 fault.
Sign: S
41143 Aux101 Fuel Read Only Multiplier: 0.01 Unit: Vdc Low limit for the Aux PCC3300V2
Level OOR 101 I/O Module Fuel
Low Limit Offset: 0 Lower Limit: 0 Level Out of Range
Size (bits): 16 Upper Limit: 5 fault.
Sign: S
41144 Aux101 Fuel Read Only Multiplier: 0.1 Unit: seconds Time limit for the Aux PCC3300V2
Level OOR 101 I/O Module Fuel
Time Offset: 0 Lower Limit: 0 Level Out of Range
Size (bits): 16 Upper Limit: 10 fault.
Sign: U
41145 Aux101 Read Only 0: Disable Enables the Aux 101 PCC3300V2
Intake I/O Module Intake
Manifold 1: Enable Manifold Temp Out of
Temp OOR Range faults.
Check
Enable
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41146 Aux101 Non- Read Only 0: Disable Enables the Aux 101 PCC3300V2
Drive End I/O Module Non-Drive
Bearing 1: Enable End Bearing Temp
Temperature Out of Range faults.
OOR Check For use with either
Enable LBNG or non-LBNG
gensets.
41147 Aux101 Oil Read Only 0: Disable Enables the Aux 101 PCC3300V2
Temp OOR I/O Module Oil Temp
Check 1: Enable Out of Range faults.
Enable
41148 Aux101 Read Only Multiplier: 0.01 Unit: Vdc High limit for the Aux PCC3300V2
Oil/Ambient/I 101 I/O Module Oil
ntake Offset: 0 Lower Limit: 0 Temp Ambient Temp
Manifold Size (bits): 16 Upper Limit: 5 and Intake Manifold
Temp OOR Temp Out of Range
High Limit Sign: S faults
41149 Aux101 Read Only Multiplier: 0.01 Unit: Vdc Low limit for the Aux PCC3300V2
Oil/Ambient/I 101 I/O Module Oil
ntake Offset: 0 Lower Limit: 0 Temp Ambient Temp
Manifold Size (bits): 16 Upper Limit: 5 and Intake Manifold
Temp OOR Temp Out of Range
Low Limit Sign: S faults
41150 Aux101 Read Only Multiplier: 0.1 Unit: seconds Time limit for the Aux PCC3300V2
Oil/Ambient/I 101 I/O Module Oil
ntake Offset: 0 Lower Limit: 0 Temp Ambient Temp
Manifold Size (bits): 16 Upper Limit: 10 and Intake Manifold
Temp OOR Temp Out of Range
Time Sign: U faults
41151 Excitation Read Only 0: Shunt The type of excitation PCC3300V2
Source power source PMG or
1: PMG Shunt
2: Auxiliary
Winding
41152 High LTA Read Only Multiplier: 1 Unit: degF "High LTA PCC3300V2
Temperature Temperature
Threshold Offset: 0 Lower Limit: -40 Threshold for the I/O
(Aux101) Size (bits): 16 Upper Limit: 300 Module fault"
Sign: S
41153 High LTA Read Only Multiplier: 0.1 Unit: seconds "Time limit for the Aux PCC3300V2
Temperature 101 I/O Module High
Time Offset: 0 Lower Limit: 0 LTA Temperature
(Aux101) Size (bits): 16 Upper Limit: 30 faults"
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41154 Aux101 LTA Read Only Multiplier: 0.01 Unit: Vdc "High limit for the Aux PCC3300V2
Temperature 101 I/O Module LTA
OOR High Offset: 0 Lower Limit: 0 Temperature Out of
Limit Size (bits): 16 Upper Limit: 5 Range faults."
Sign: U
41155 Aux101 LTA Read Only Multiplier: 0.01 Unit: Vdc "Low limit for the Aux PCC3300V2
Temperature 101 I/O Module LTA
OOR Low Offset: 0 Lower Limit: 0 Temperature Out of
Limit Size (bits): 16 Upper Limit: 5 Range faults."
Sign: U
41156 Aux101 LTA Read Only Multiplier: 0.1 Unit: seconds "Time limit for the Aux PCC3300V2
Temperature 101 I/O Module LTA
OOR Time Offset: 0 Lower Limit: 0 Temperature Out of
Size (bits): 16 Upper Limit: 10 Range faults"
Sign: U
41157 Aux101 LTA Read Only 0: Disabled "Enables the AUX101 PCC3300V2
Temperature I/O Module LTA
OOR Check 1: Enabled Temperature Out Of
Enable Range Faults."
41158 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 1 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
41158 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 1 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41159 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 2 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41159 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 2 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41160 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 3 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41160 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 3 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41161 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 4 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41161 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 4 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41162 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 5 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41162 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 5 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41163 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 6 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41163 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 6 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41164 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 7 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41164 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 7 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41165 Aux101 0 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 8 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41165 Aux101 0 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 8 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41166 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 1 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41166 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 1 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41167 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 2 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41167 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 2 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41168 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 3 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41168 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 3 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41169 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 4 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41169 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 4 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41170 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 5 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41170 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 5 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
41171 Aux101 1 Read Only 0: Analog Input Selects whether the PCC3300V2
Analog Input input will be active
6 Sensor 1: Switch Input - open, active closed, or
Type Active Closed an analog input.
2: Switch Input -
Active Open
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41172 Aux101 1 Read Only 0: Do Nothing Selects the type of PCC3300V2
Analog Input analog input sensor.
6 Function 1: Oil
Pointer Temperature
2: Exhaust Stack
Temperature 1
3: Exhaust Stack
Temperature 2
4: Ambient
Temperature
5: Fuel Level
6: Alternator
Temperature 1
7: Alternator
Temperature 2
8: Alternator
Temperature 3
9: Intake
Manifold
Temperature 1
10: Drive End
Bearing
Temperature
11: Non-Drive
End Bearing
Temperature
12: LTA
Temperature
13: Bank A
Pressure Sensor
14: Bank B
Pressure Sensor
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41173 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 7 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41173 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 7 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41174 Aux101 1 Read Only 0: Default 11: Exercise Selects disrete input PCC3300V2
Input 8 Switch fault/event for this
Function input.
Pointer 1: Do Nothing 12: Battle Short
Switch
2: Manual Run 13: Battery
Switch Charger Failed
Switch
3: Low Fuel in 14: Low Engine
Day Tank Switch Temperature
Switch
4: Low Coolant 15: Speed Droop
Switch #2 Enable Switch
5: High Alt 16: Voltage
Temperature Droop Enable
Switch Switch
6: Ground Fault 17: Fire Fault
Switch Switch
7: PTC Mode 18: Differential
Switch Fault Switch
8: Load Demand 19: Rated/Idle
Inhibit Switch Switch
9: Load Demand 20: AMM
Spare Capacity Enabled
Request
10: Ramp 21: Intake Air
Load/Unload Restriction
Switch Indicator 1 fault
switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41174 Aux101 1 Read Only 22: Intake Air 33: Cam Switch Selects disrete input PCC3300V2
Input 8 Restriction Location 4 fault/event for this
Function Indicator 2 fault input.
Pointer switch
23: Intake Air 34: Paralleling
Restriction Cable Detect
Indicator 3 fault
switch
24: Intake Air 35: DEF Tank
Restriction Detector
Indicator 4 fault
switch
25: Battery 36: Low Fuel
Charger 2 Failed Pressure Switch
Switch
26: Battery 37: Bank A
Charger 3 Failed Pressure Switch
Switch
27: Battery 38: Bank B
Charger 4 Failed Pressure Switch
Switch
28: Starter Air 39: Start Signal
Supply Pressure Integrity Switch
Low Fault Switch
29: Starter Air 40: Charging
Tank Volume Alternator Fuse
Low Fault Switch Failure Switch
30: Cam Switch 41: STC Bank A
Location 1 Pressure Switch
31: Cam Switch 42: STC Bank B
Location 2 Pressure Switch
32: Cam Switch 43:
Location 3 Transfer/Retrans
fer Override
Switch
41175 Configurable Read Only 0: None If the configurable PCC3300V2
Input #1 input #1 is configured
Fault 1: Warning as a fault input, this
Response 2: Shutdown sets the fault level
3: Shutdown
w/Cooldown
4: Derate
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41176 Configurable Read Only 0: None If the configurable PCC3300V2
Input #2 input #2 is configured
Fault 1: Warning as a fault input, this
Response 2: Shutdown sets the fault level
3: Shutdown
w/Cooldown
4: Derate
41177 Start Read Only 0: Active Closed Start Type input PCC3300V2
Type/Configu software logic state
rable Input 1: Active Open inversion bypass
#11 Active control
State
Selection
41178 Speed Bias Read Only Multiplier: 0.01 Unit: Vdc The analog value that PCC3300V2
Output / corresponds to the
Configurable Offset: 0 Lower Limit: -10 high engineering value
Analog Size (bits): 16 Upper Limit: 10 (scaling unit) and
output #1 upper clamp
Analog Out Sign: S
High
Function
Setpoint
41179 Speed Bias Read Only Multiplier: 0.01 Unit: Vdc The analog value that PCC3300V2
Output / corresponds to the
Configurable Offset: 0 Lower Limit: -10 high engineering value
Analog Size (bits): 16 Upper Limit: 10 (scaling unit) and
output #1 upper clamp
Analog Out Sign: S
High Setpoint
41180 Speed Bias Read Only Multiplier: 0.01 Unit: Vdc The analog value that PCC3300V2
Output / corresponds to the
Configurable Offset: 0 Lower Limit: -10 Low engineering value
Analog Size (bits): 16 Upper Limit: 10 (scaling unit) and
output #1 lower clamp
Analog Out Sign: S
Low Function
Setpoint
41181 Speed Bias Read Only Multiplier: 0.01 Unit: Vdc The analog value that PCC3300V2
Output / corresponds to the
Configurable Offset: 0 Lower Limit: -10 Low engineering value
Analog Size (bits): 16 Upper Limit: 10 (scaling unit) and
output #1 lower clamp
Analog Out Sign: S
Low Setpoint
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41182 Speed Bias Read Only 0: Default Pointes to the fucntion PCC3300V2
Output / that controls the
Configurable 1: Do Nothing analog output
Analog 2: Genset
Output #1 Average Voltage
Analog
Output 3: Genset
Function Average Current
Pointer
4: Genset Total
Power Factor
5: Genset
Frequency
6: Genset Total
kW
7: Genset Total
kVAR
8: Engine Speed
9: Coolant
Temperature
10: Oil Pressure
11: Oil
Temperature
12: Intake
Manifold
Temperature
13: Genset %
Application Total
kW
41183 Speed Bias Read Only Multiplier: 1 Unit: The engingeering PCC3300V2
Output / value that corresponds
Configurable Offset: 0 Lower Limit: to the High Analog
Analog -32768 output value (scaling
output #1 Size (bits): 16 Upper Limit: unit)
Engineering 32762
In High
Function Sign: S
Setpoint
41184 Speed Bias Read Only Multiplier: 1 Unit: The engingeering PCC3300V2
Output / value that corresponds
Configurable Offset: 0 Lower Limit: to the High Analog
Analog -32768 output value (scaling
output #1 Size (bits): 16 Upper Limit: unit)
Engineering 32762
In High
Setpoint Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41185 Speed Bias Read Only Multiplier: 1 Unit: The engineering value PCC3300V2
Output / that corresponds to
Configurable Offset: 0 Lower Limit: the Low Analog output
Analog -32768 value (scaling unit)
output #1 Size (bits): 16 Upper Limit:
Engineering 32762
In Low
Function Sign: S
Setpoint
41186 Speed Bias Read Only Multiplier: 1 Unit: The engineering value PCC3300V2
Output / that corresponds to
Configurable Offset: 0 Lower Limit: the Low Analog output
Analog -32768 value (scaling unit)
output #1 Size (bits): 16 Upper Limit:
Engineering 32762
In Low
Setpoint Sign: S
41187 Maintenance Read Only Multiplier: 0.01 Unit: hours Displays Maintenance PCC3300V2
Due wrt ERT required with respect
Offset: 0 Lower Limit: 0 to Engine Running
Size (bits): 32 Upper Limit: Hours
4294967295
Sign: U
41188 Maintenance Read Only Multiplier: 0.01 Unit: hours Displays Maintenance PCC3300V2
Due wrt ERT required with respect
Offset: 0 Lower Limit: 0 to Engine Running
Size (bits): 32 Upper Limit: Hours
4294967295
Sign: U
41189 ECM HOT Read Only Multiplier: 0.1 Unit: degF "Displays High Engine PCC3300V2
Warning Oil Temperature
Threshold Offset: 0 Lower Limit: Warning Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: S CAN(OTIS)"
41190 ECM HOT Read Only Multiplier: 0.1 Unit: degF "Displays High Engine PCC3300V2
Shutdown Oil Temperature
Threshold Offset: 0 Lower Limit: Shutdown Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: S CAN(OTIS)"
41191 ECM HCP Read Only Multiplier: 0.1 Unit: psi "Displays High PCC3300V2
Warning Crankcase Pressure
Threshold Offset: 0 Lower Limit: Warning Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: S CAN(OTIS)"
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41192 ECM HCP Read Only Multiplier: 0.1 Unit: psi "Displays High PCC3300V2
Shutdown Crankcase Pressure
Threshold Offset: 0 Lower Limit: Shutdown Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: U CAN(OTIS)"
41193 ECM Read Only Multiplier: 1 Unit: rpm "Displays Engine PCC3300V2
Overspeed Overspeed Shutdown
Shutdown Offset: 0 Lower Limit: Threshold received via
Threshold Size (bits): 16 Upper Limit: ECM over
CAN(OTIS)"
Sign: U
41194 ECM LOP Read Only Multiplier: 0.01 Unit: psi "Displays Low Engine PCC3300V2
Warning Oil Pressure Warning
Threshold Offset: 0 Lower Limit: Threshold value for
(1500 rpm) Size (bits): 16 Upper Limit: 1500 rpm received via
ECM over
Sign: S CAN(OTIS)"
41195 ECM LOP Read Only Multiplier: 0.01 Unit: psi "Displays Low Engine PCC3300V2
Warning Oil Pressure Warning
Threshold Offset: 0 Lower Limit: Threshold value for
(1800 rpm) Size (bits): 16 Upper Limit: 1800 rpm received via
ECM over
Sign: S CAN(OTIS)"
41196 ECM LOP Read Only Multiplier: 0.01 Unit: psi "Displays Low Engine PCC3300V2
Shutdown Oil Pressure
Threshold Offset: 0 Lower Limit: Shutdown Threshold
(1500 rpm) Size (bits): 16 Upper Limit: value for 1500 rpm
received via ECM over
Sign: S CAN(OTIS)"
41197 ECM LOP Read Only Multiplier: 0.01 Unit: psi "Displays Low Engine PCC3300V2
Shutdown Oil Pressure
Threshold Offset: 0 Lower Limit: Shutdown Threshold
(1800 rpm) Size (bits): 16 Upper Limit: value for 1800 rpm
received via ECM over
Sign: S CAN(OTIS)"
41198 ECM HCT Read Only Multiplier: 0.1 Unit: degF "Displays High PCC3300V2
Warning Coolant Temperature
Threshold Offset: 0 Lower Limit: Warning Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: S CAN(OTIS)"
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41199 ECM HCT Read Only Multiplier: 0.1 Unit: degF "Displays High PCC3300V2
Shutdown/w Coolant Temperature
Cooldown Offset: 0 Lower Limit: Shutdown with
Threshold Size (bits): 16 Upper Limit: Cooldown Threshold
value received via
Sign: S ECM over
CAN(OTIS)"
41200 ECM HCT Read Only Multiplier: 0.1 Unit: degF "Displays High PCC3300V2
Shutdown Coolant Temperature
Threshold Offset: 0 Lower Limit: Shutdown Threshold
Size (bits): 16 Upper Limit: value received via
ECM over
Sign: S CAN(OTIS)"
41300 AmpSentry Read Only 0: Inactive "A protection mode PCC3300,
Maintenance that causes the PCC2300,
Mode Status 1: Active alternator to shutdown PCC3300V2
instantly when a short
circuit is detected.
Used to limit arc flash
energy with personnel
working around set."
41303 Fuel System Read/Write 0: Diesel Type of fuel and PCC3300,
ignition system used PCC2300,
1: Gas by genset. PCC3300V2
41304 Gas Fuel Read/Write 0: Natural Gas "Trim to set the type of PCC2300,
Type gaseous fuel." PCC3300,
1: Propane PCC3300V2
2: Dual
41305 Low Fuel Read Only 0: Inactive "Displays PCC2300,
Pressure Inactive/Active status PCC3300,
Switch 1: Active of Switch. Activates if PCC3300V2
Status Low Fuel Pressure
switch remains active
for Fuel Pressure
Fault delay."
41306 Maintenance Read/Write Multiplier: 1 Unit: hours Sets Hours for PCC3300V2
ERT Interval Maintenance
Offset: 0 Lower Limit: 250 Diagnostic
Size (bits): 16 Upper Limit:
5000
Sign: U
41307 Maintenance Read/Write Multiplier: 1 Unit: Sets Real Time Clock PCC3300V2
RTC Date Date for Maintenance
Interval Offset: 0 Lower Limit: 1 Diagnostic
Size (bits): 8 Upper Limit: 31
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
41308 Maintenance Read/Write Multiplier: 1 Unit: Sets Real Time Clock PCC3300V2
RTC Month Month for
Interval Offset: 0 Lower Limit: 1 Maintenance
Size (bits): 8 Upper Limit: 12 Diagnostic
Sign: U
41309 Maintenance Read/Write Multiplier: 1 Unit: Sets Real Time Clock PCC3300V2
RTC Year Year for Maintenance
Interval Offset: 0 Lower Limit: 0 Diagnostic
Size (bits): 8 Upper Limit: 99
Sign: U
42000 Load Read Only 0: Off Indicates the status of PCC3300,
Demand Load Demand PCC3300V2
State 1: Halted operation.
2: Initial Delay
3: Load Monitor
42001 Load Read Only Multiplier: 1 Unit: kW Indicates the total load PCC3300,
Demand of System Network PCC3300V2
Genset Bus Offset: 0 Lower Limit: 0 connected gensets
Total kW Size (bits): 32 Upper Limit:
80000
Sign: U
42002 Load Read Only Multiplier: 1 Unit: kW Indicates the total load PCC3300,
Demand of System Network PCC3300V2
Genset Bus Offset: 0 Lower Limit: 0 connected gensets
Total kW Size (bits): 32 Upper Limit:
80000
Sign: U
42003 Load Read Only Multiplier: 1 Unit: kW Indicates the amount PCC3300,
Demand of unused online kW PCC3300V2
Surplus Offset: 0 Lower Limit: 0 bus capacity (spinning
Capacity Size (bits): 32 Upper Limit: reserve).
80000
Sign: U
42004 Load Read Only Multiplier: 1 Unit: kW Indicates the amount PCC3300,
Demand of unused online kW PCC3300V2
Surplus Offset: 0 Lower Limit: 0 bus capacity (spinning
Capacity Size (bits): 32 Upper Limit: reserve).
80000
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42005 Load Read Only Multiplier: 1 Unit: kW Indicates the total PCC3300,
Demand amount of online kW PCC3300V2
Online Offset: 0 Lower Limit: 0 bus capacity for load
Capacity Size (bits): 32 Upper Limit: demand. Only gensets
80000 which are eligible for
load demand count.
Sign: U
42006 Load Read Only Multiplier: 1 Unit: kW Indicates the total PCC3300,
Demand amount of online kW PCC3300V2
Online Offset: 0 Lower Limit: 0 bus capacity for load
Capacity Size (bits): 32 Upper Limit: demand. Only gensets
80000 which are eligible for
load demand count.
Sign: U
TABLE 39.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42007 Load Read Only Multiplier: 1 Unit: seconds Indicates the time PCC3300,
Demand remaining before PCC3300V2
Initial Delay Offset: 0 Lower Limit: 0 generator sets are
Timer Size (bits): 16 Upper Limit: allowed to stop after
1500 initial start or after
resuming halted load
Sign: U demand. This timer is
set by Load Demand
Initial Delay.
42008 Load Read Only Multiplier: 1 Unit: seconds Indicates the time PCC3300,
Demand remaining before next PCC3300V2
Start Delay Offset: 0 Lower Limit: 0 generator set is
Timer Size (bits): 16 Upper Limit: allowed to start. This
1500 timer is set by Load
Demand Start Delay.
Sign: U
42009 Load Read Only Multiplier: 1 Unit: seconds Indicates the time PCC3300,
Demand remaining before next PCC3300V2
Stop Delay Offset: 0 Lower Limit: 0 generator set is
Timer Size (bits): 16 Upper Limit: allowed to stop. This
1500 timer is set by Load
Demand Stop Delay.
Sign: U
42010 Load Read Only 0: No Indicates when the PCC3300,
Demand current load and spare PCC3300V2
Spare 1: Yes capacity requirements
Capacity are satisfied.
Available
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42011 Load Read Only Multiplier: 1 Unit: kW Indicates the total kW PCC3300,
Demand value of all currently PCC3300V2
Total Spare Offset: 0 Lower Limit: 0 active spare capacity
Capacity Size (bits): 32 Upper Limit: requests in the
Requested 80000 system.
Sign: U
42012 Load Read Only Multiplier: 1 Unit: kW Indicates the total kW PCC3300,
Demand value of all currently PCC3300V2
Total Spare Offset: 0 Lower Limit: 0 active spare capacity
Capacity Size (bits): 32 Upper Limit: requests in the
Requested 80000 system.
Sign: U
42013 Load Read Only Multiplier: 1 Unit: kW The kW load at which PCC3300,
Demand the next generator set PCC3300V2
Next Start Offset: 0 Lower Limit: 0 will be started.
Threshold Size (bits): 32 Upper Limit:
(kW) 80000
Sign: U
42014 Load Read Only Multiplier: 1 Unit: kW The kW load at which PCC3300,
Demand the next generator set PCC3300V2
Next Start Offset: 0 Lower Limit: 0 will be started.
Threshold Size (bits): 32 Upper Limit:
(kW) 80000
Sign: U
42015 Load Read Only Multiplier: 1 Unit: kW The kW load at which PCC3300,
Demand the next generator set PCC3300V2
Next Stop Offset: 0 Lower Limit: 0 will be stopped.
Threshold Size (bits): 32 Upper Limit:
(kW) 80000
Sign: U
42016 Load Read Only Multiplier: 1 Unit: kW The kW load at which PCC3300,
Demand the next generator set PCC3300V2
Next Stop Offset: 0 Lower Limit: 0 will be stopped.
Threshold Size (bits): 32 Upper Limit:
(kW) 80000
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42017 Load Read Only 0: Gen1 Indicates the next PCC3300,
Demand generator set to start PCC3300V2
Next Gen to 1: Gen2 by ID.
Start 2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
42018 Load Read Only 0: Gen1 Indicates the next PCC3300,
Demand generator set to stop PCC3300V2
Next Gen to 1: Gen2 by ID.
Stop 2: Gen3
3: Gen4
4: Gen5
5: Gen6
6: Gen7
7: Gen8
8: Gen9
9: Gen10
10: Gen11
11: Gen12
12: Gen13
13: Gen14
14: Gen15
15: Gen16
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42019 Load Read Only 0: Inactive Indicates the status of PCC3300,
Demand the Load Demand PCC3300V2
Inhibit Local 1: Active Inhibit input. When
ACTIVE all the
generator sets will
start.
42020 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42021 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42022 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42023 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42024 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42025 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42026 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
42027 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42028 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
42029 ECM 4 Code Read Only Multiplier: 1 Unit: "ECM 4 Calibration ID PCC3300,
(DM19)" PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 88 Upper Limit:
Sign: C
43000 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L1 PCC2300,
L1 Current Offset: 0 Lower Limit: current percentage PCC3300V2
Size (bits): 16 Upper Limit: output.
Sign: U
43001 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L2 PCC2300,
L2 Current Offset: 0 Lower Limit: current percentage PCC3300V2
Size (bits): 16 Upper Limit: output.
Sign: U
43002 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L1 KVA PCC2300,
L1 kVA Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43003 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L3 PCC2300,
L3 Current Offset: 0 Lower Limit: current percentage PCC3300V2
Size (bits): 16 Upper Limit: output.
Sign: U
43004 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L2 KVA PCC2300,
L2 kVA Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43005 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L3 KVA PCC2300,
L3 kVA Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43006 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L1 KW PCC2300,
L1 kW Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
43007 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L2 KW PCC2300,
L2 kW Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
43008 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the generator PCC3300,
Application set application L3 KW PCC2300,
L3 kW Offset: 0 Lower Limit: percentage output. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
43009 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the total PCC3300,
Application generator set PCC2300,
Total kVA Offset: 0 Lower Limit: application KVA PCC3300V2
Size (bits): 16 Upper Limit: percentage output.
Sign: U
43010 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the total PCC3300,
Application generator set PCC2300,
Total kW Offset: 0 Lower Limit: application KW PCC3300V2
Size (bits): 16 Upper Limit: percentage output.
Sign: S
43017 Genset % Read Only Multiplier: 0.1 Unit: % Monitors the total PCC3300,
Standby generator set standby PCC2300,
Total kVA Offset: 0 Lower Limit: KVA percentage PCC3300V2
Size (bits): 16 Upper Limit: output.
Sign: U
43018 Genset Read Only Multiplier: 0.1 Unit: kVA The generator set PCC3300,
Application KVA rating. PCC2300,
kVA rating Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43019 Genset Read Only Multiplier: 0.1 Unit: kW The generator set KW PCC3300,
Application rating. PCC2300,
kW rating Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43020 Genset Read Only Multiplier: 1 Unit: Amps The value of the PCC3300,
Application generator set PCC2300,
Nominal Offset: 0 Lower Limit: application nominal PCC3300V2
Current Size (bits): 16 Upper Limit: current. Displayed as
"Genset Application
Sign: U Rated Current" in HMI
43021 Genset Read Only Multiplier: 0.01 Unit: % Generator set average PCC3300,
Average voltage percentage. PCC2300,
Voltage% Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43030 Genset L1 Read Only Multiplier: 0.01 Unit: PF Generator set L1 PCC3300,
Power Factor power factor PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 8 Upper Limit:
Sign: S
43031 Genset L1L2 Read Only Multiplier: 0.01 Unit: Degrees Generator set L1L2 PCC3300,
Phase voltage phase angle PCC2300,
Difference Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43032 Genset L1L2 Read Only Multiplier: 0.01 Unit: % Generator set L1L2 PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43033 Genset L1N Read Only Multiplier: 0.01 Unit: % Generator set L1N PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43044 Genset L2 Read Only Multiplier: 0.01 Unit: PF Generator set L2 PCC3300,
Power Factor power factor PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-1.28
Size (bits): 8 Upper Limit: 1.27
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43045 Genset L2L3 Read Only Multiplier: 0.01 Unit: Degrees Generator set L2L3 PCC3300,
Phase voltage phase angle PCC2300,
Difference Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
655.3
Sign: U
43046 Genset L2L3 Read Only Multiplier: 0.01 Unit: % Generator set L2L3 PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43047 Genset L2N Read Only Multiplier: 0.01 Unit: % Generator set L2N PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
655.3
Sign: U
43058 Genset L3 Read Only Multiplier: 0.01 Unit: PF Generator set L3 PCC3300,
Power Factor power factor PCC2300,
Offset: 0 Lower Limit: PCC3300V2
-1.28
Size (bits): 8 Upper Limit: 1.22
Sign: S
43059 Genset L3L1 Read Only Multiplier: 0.01 Unit: Degrees Generator set L3L1 PCC3300,
Phase voltage phase angle PCC2300,
Difference Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
655.3
Sign: U
43060 Genset L3L1 Read Only Multiplier: 0.01 Unit: % Generator set L3L1 PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
655.3
Sign: U
43061 Genset L3N Read Only Multiplier: 0.01 Unit: % Generator set L3N PCC3300,
Voltage% voltage% PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43062 Genset Read Only Multiplier: 0.1 Unit: kVA KVA rating for the PCC3300,
Standby kVA generator set in PCC2300,
rating Offset: 0 Lower Limit: Standby configuration. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43063 Genset Read Only Multiplier: 0.1 Unit: kW KW rating for the PCC3300,
Standby kW generator set in PCC2300,
rating Offset: 0 Lower Limit: Standby configuration. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43064 Genset Read Only Multiplier: 1 Unit: Amps The value of the PCC3300,
Standby generator set standby PCC2300,
Nominal Offset: 0 Lower Limit: nominal current. PCC3300V2
Current Size (bits): 16 Upper Limit: Displayed as "Genset
Standby Rated
Sign: U Current" in HMI
43065 Genset Total Read Only Multiplier: 1 Unit: kVAh Generator set total PCC3300,
kVAh kVAh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
43066 Genset Total Read Only Multiplier: 1 Unit: kVAh Generator set total PCC3300,
kVAh kVAh accumulation PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
43067 Genset Total Read Only Multiplier: 0.01 Unit: % Total KVAR's per PCC3300,
kVARs per Standby KVA. PCC2300,
Standby kVA Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
43111 Genset Bus Read Only Multiplier: 0.01 Unit: PF Generator set Bus L1 PCC3300,
L1 Power power factor PCC3300V2
Factor Offset: 0 Lower Limit:
-1.28
Size (bits): 8 Upper Limit: 1.22
Sign: S
43112 Genset Bus Read Only Multiplier: 0.01 Unit: Degrees Generator set bus PCC3300,
L1L2 Phase L1L2 voltage phase PCC3300V2
Difference Offset: 0 Lower Limit: angle
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43125 Genset Bus Read Only Multiplier: 0.01 Unit: PF Generator set Bus L2 PCC3300,
L2 Power power factor PCC3300V2
Factor Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
43126 Genset Bus Read Only Multiplier: 0.01 Unit: Degrees Generator set bus PCC3300,
L2L3 Phase L2L3 voltage phase PCC3300V2
Difference Offset: 0 Lower Limit: angle
Size (bits): 16 Upper Limit:
Sign: U
43139 Genset Bus Read Only Multiplier: 0.01 Unit: PF Generator set Bus L3 PCC3300,
L3 Power power factor PCC3300V2
Factor Offset: 0 Lower Limit:
-1.28
Size (bits): 8 Upper Limit: 1.22
Sign: S
43140 Genset Bus Read Only Multiplier: 0.01 Unit: Degrees Generator set bus PCC3300,
L3L1 Phase L3L1 voltage phase PCC3300V2
Difference Offset: 0 Lower Limit: angle
Size (bits): 16 Upper Limit:
Sign: U
43143 Genset Bus Read Only Multiplier: 1 Unit: kVAh Generator set bus PCC3300,
Total kVAh total kVAh PCC3300V2
Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
43144 Genset Bus Read Only Multiplier: 1 Unit: kVAh Generator set bus PCC3300,
Total kVAh total kVAh PCC3300V2
Offset: 0 Lower Limit: accumulation
Size (bits): 32 Upper Limit:
Sign: U
43146 Paralleling Read/Write 0: None Determines what the PCC3300,
Application function of the Other PCC3300V2
1: Utility Meter is.
2: Genset Bus
43162 Utility L1 Read Only Multiplier: 0.01 Unit: PF Utility L1 power factor PCC3300,
Power Factor PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43163 Utility L1L2 Read Only Multiplier: 0.01 Unit: Degrees Utility L1L2 voltage PCC3300,
Phase phase angle PCC3300V2
Difference Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
43176 Utility L2 Read Only Multiplier: 0.01 Unit: PF Utility L2 power factor PCC3300,
Power Factor PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
43177 Utility L2L3 Read Only Multiplier: 0.01 Unit: Degrees Utility L2L3 voltage PCC3300,
Phase phase angle PCC3300V2
Difference Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
43190 Utility L3 Read Only Multiplier: 0.01 Unit: PF Utility L3 power factor PCC3300,
Power Factor PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: S
43191 Utility L3L1 Read Only Multiplier: 0.01 Unit: Degrees Utility L3L1 voltage PCC3300,
Phase phase angle PCC3300V2
Difference Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
43194 Utility Total Read Only Multiplier: 1 Unit: kVAh Utility total kVAh PCC3300,
kVAh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
43195 Utility Total Read Only Multiplier: 1 Unit: kVAh Utility total kVAh PCC3300,
kVAh accumulation PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
43196 Exhaust Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Stack Exhaust Stack PCC3300V2
Temperature Offset: 0 Lower Limit: -459 Temperature Right
Right Bank Size (bits): 16 Upper Limit: Bank received from
3155 ECM
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43197 Exhaust Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Stack Exhaust Stack PCC3300V2
Temperature Offset: 0 Lower Limit: -459 Temperature Left
Left Bank Size (bits): 16 Upper Limit: Bank received from
3155 ECM
Sign: S
43200 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43201 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43202 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43203 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43204 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43205 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43206 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43207 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43208 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43209 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43210 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43211 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43212 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43213 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43214 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43215 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43216 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43217 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43218 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43219 Genset Read Only Multiplier: 1 Unit: Number identifying the PCC3300,
Model model of this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43200
- 43219 for the 20 char
Sign: C of this string. Uses
logical numbers 2064 -
2083 to hold each of
the 20 characters.
43220 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43221 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43222 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43223 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43224 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43225 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43226 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43227 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43228 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43229 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43230 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43231 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43232 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43233 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43234 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43235 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43236 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43237 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43238 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43239 Genset Read Only Multiplier: 1 Unit: Serial number of PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set. Modbus PCC3300V2
Size (bits): 168 Upper Limit: uses addresses 43220
- 43239 for the 20 char
Sign: C of this string. Uses
logical addresses
2048 - 6063 to store
the first 16 characters.
The last 4 are stored
in 691-694.
43240 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43241 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43242 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43243 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43244 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43245 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43246 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43247 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43248 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43249 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43250 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43251 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43252 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43253 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43254 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43255 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43256 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43257 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43258 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set's PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43259 Alternator Read Only Multiplier: 1 Unit: Number identifying this PCC3300,
Model generator set' s PCC2300,
Number Offset: 0 Lower Limit: alternator model PCC3300V2
Size (bits): 168 Upper Limit: number. Modbus uses
addresses 43240 -
Sign: C 43259 for the 20 char
text string.
43260 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43261 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43262 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43263 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43264 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43265 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43266 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43267 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43268 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
TABLE 40.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43269 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43270 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43271 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43272 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43273 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43274 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43275 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43276 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43277 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43278 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43279 Alternator Read Only Multiplier: 1 Unit: Unique number PCC3300,
Serial identifying this PCC2300,
Number Offset: 0 Lower Limit: generator set's PCC3300V2
Size (bits): 168 Upper Limit: alternator serial
number. Modbus uses
Sign: C addresses 43260 -
43279 for the 20 char
text string.
43280 Coolant Read Only 0: Inactive Coolant Level input PCC3300,
Level Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
43281 Coolant Read Only 0: Inactive This is the status of PCC3300,
Level/Config the Configurable Input PCC2300,
urable Input 1: Active #5. PCC3300V2
#5 Switch
43283 Fault Reset Read Only 0: Inactive Fault Reset input PCC3300,
Switch software state status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
43284 Fault Read Only 0: Inactive This is the status of PCC3300,
Reset/Config the Configurable Input PCC2300,
urable Input 1: Active #10. PCC3300V2
#10 Switch
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43285 Genset CB Read Only 0: Inactive This is the status of PCC3300,
Inhibit/Config the Configurable Input PCC3300V2
urable Input 1: Active #28.
#28 Switch
43286 Genset CB Read Only 0: Inactive This is the status of PCC3300,
Pos the Configurable Input PCC3300V2
B/Configurab 1: Active #26.
le Input #26
Switch
43287 Genset CB Read Only 0: Inactive This is the status of PCC3300,
Tripped/Confi the Configurable Input PCC3300V2
gurable Input 1: Active #27.
#27 Switch
43289 Genset CB Read Only 0: Inactive Generator set CB Pos PCC3300,
Pos A Switch A input software state PCC3300V2
1: Active status. Gives software
Inactive/Active state
43290 Genset CB Read Only 0: Inactive Generator set CB Pos PCC3300,
Pos B Switch B input software state PCC3300V2
1: Active status. Gives software
Inactive/Active state
43292 Ground Fault Read Only 0: Inactive Ground Fault Switch PCC3300,
Switch function output status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
43293 High Alt Read Only 0: Inactive High Alt Temp Switch PCC3300,
Temp Switch function output status. PCC2300,
1: Active Gives software PCC3300V2
Inactive/Active state
43295 Load Read Only 0: Inactive This is the status of PCC3300,
Demand the Configurable Input PCC3300V2
Stop/Configu 1: Active #31.
rable Input
#31 Switch
43296 Local E-stop Read Only 0: Inactive Monitors the E-Stop PCC3300,
Switch switch. PCC2300,
1: Active PCC3300V2
43297 Low Coolant Read Only 0: Inactive Low Coolant #2 PCC3300,
#2 Switch Switch function output PCC2300,
1: Active status. Gives software PCC3300V2
Inactive/Active state
43298 Low Engine Read Only 0: Inactive Low Engine PCC3300,
Temperature Temperarure Switch PCC2300,
Switch 1: Active function output status. PCC3300V2
Gives software
Inactive/Active state
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43299 Low Fuel In Read Only 0: Inactive Low Fuel In Day Tank PCC3300,
Day Tank Switch function output PCC2300,
Switch 1: Active status. Gives software PCC3300V2
Inactive/Active state
43300 Genset Bus Read/Write 0: Delta Delta or Wye for Utility PCC3300,
Delta/Wye connection PCC3300V2
Connection 1: Wye
43301 Genset Bus Read Only Multiplier: 1 Unit: Vac Generator set Bus PCC3300,
Nominal nominal voltage PCC3300V2
Voltage Offset: 0 Lower Limit: 110
Size (bits): 16 Upper Limit:
45000
Sign: U
43302 Genset Read Only 0: Delta Delta or Wye for PCC3300,
Delta/Wye Generator set PCC2300,
Connection 1: Wye connection PCC3300V2
43303 Genset Read Only Multiplier: 1 Unit: Vac Generator set nominal PCC3300,
Nominal line-line voltage PCC2300,
Voltage Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 16 Upper Limit:
45000
Sign: U
43304 Single/3 Read Only 0: Single Phase Setup mode PCC3300,
Phase interlocked. Generator PCC2300,
Connection 1: Three Phase set's single phase/3 PCC3300V2
phase metering setup
configuration.
43306 Utility Read/Write 0: Delta Delta or Wye for Utility PCC3300,
Delta/Wye connection PCC3300V2
Connection 1: Wye
43307 Utility Read Only Multiplier: 1 Unit: Vac Utility nominal voltage PCC3300,
Nominal PCC3300V2
Voltage Offset: 0 Lower Limit: 110
Size (bits): 16 Upper Limit:
45000
Sign: U
43309 Overfrequen Read/Write 0: Disabled Enables PCC3300,
cy Enable overfrequency PCC2300,
1: Enabled diagnostic witness PCC3300V2
test.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43310 Overload Read/Write Multiplier: 1 Unit: seconds The time delay until an PCC3300,
Warning Set overload condition is PCC2300,
Time Offset: 0 Lower Limit: 1 reported as a fault PCC3300V2
Size (bits): 8 Upper Limit: 120
Sign: U
43311 Overload Read/Write Multiplier: 0.01 Unit: % Sets the Overload PCC3300,
Warning Warning fault trip PCC2300,
Threshold Offset: 0 Lower Limit: 70 threshold as PCC3300V2
Size (bits): 16 Upper Limit: 140 percentage of
generator set
Sign: U application kW rating.
43312 Overload Read/Write Multiplier: 1 Unit: seconds The time delay until an PCC3300,
Shutdown overload condition is PCC2300,
Set Time Offset: 0 Lower Limit: 1 reported as Shutdown PCC3300V2
Size (bits): 8 Upper Limit: 120 fault
Sign: U
43313 Overload Read/Write Multiplier: 0.01 Unit: % "Sets the Overload PCC3300,
Shutdown Shutdown fault trip PCC2300,
threshold Offset: 0 Lower Limit: 70 threshold as PCC3300V2
Size (bits): 16 Upper Limit: percentage of
655.35 generator set
application kW rating
Sign: U in the range of 70 to
140%. To disable the
Overload shutdown
fault set the value to
655.35 or Not
Available."
43314 Prelube Read/Write 0: GCS Selects whether PCC3300,
Function prelube function is PCC3300V2
Owner 1: ECS being controlled by
GCS or ECS
43338 CAN Failure Read/Write Multiplier: 1 Unit: Sets the maximum PCC3300,
Retries number of CAN PCC2300,
Offset: 0 Lower Limit: 0 communication retries PCC3300V2
Size (bits): 8 Upper Limit: 10
Sign: U
43339 Auto Sleep Read/Write 0: Awake in Auto Trim that determines if PCC3300,
Enable the control will Stay PCC2300,
1: Sleep in Auto Awake in Auto mode PCC3300V2
or Fall asleep in Auto
mode.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43340 Max Setup Read/Write Multiplier: 1 Unit: Seconds Max time allowed in PCC3300,
Mode Time Setup Mode. PCC2300,
Offset: 0 Lower Limit: 30 PCC3300V2
Size (bits): 16 Upper Limit:
3600
Sign: U
43341 Power Down Read/Write 0: Disable Trim to enable sleep PCC3300,
Mode Enable mode PCC2300,
1: Enable PCC3300V2
43342 Power Down Read/Write Multiplier: 1 Unit: seconds Timer setting for the PCC3300,
Mode Time Power Down delay PCC2300,
Delay Offset: 0 Lower Limit: 0 feature PCC3300V2
Size (bits): 16 Upper Limit: 600
Sign: U
43343 Setup Mode Read/Write 0: Disable Voltatile to allow entry PCC3300,
Enable into Setup Mode PCC2300,
1: Enable PCC3300V2
43344 Clock Date Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
current date. PCC2300,
Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 8 Upper Limit: 31
Sign: U
43345 Clock Hour Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
current hour. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 23
Sign: U
43346 Clock Minute Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
current minute. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 59
Sign: U
43347 Clock Mode Read/Write 0: Normal Use to set the real PCC3300,
time clock and save PCC2300,
1: Set Clock settings. PCC3300V2
2: Save Clock
43348 Clock Month Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
current month. PCC2300,
Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 8 Upper Limit: 12
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43349 Clock Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
Second current second. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 59
Sign: U
43350 Clock Year Read/Write Multiplier: 1 Unit: Use to set or read the PCC3300,
current year. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 99
Sign: U
43351 Daylight Read/Write Multiplier: 1 Unit: Use to set the hour of PCC3300,
Savings End the day when daylight PCC2300,
Hour Offset: 0 Lower Limit: 2 savings time ends. PCC3300V2
Size (bits): 8 Upper Limit: 19
Sign: U
43352 Daylight Read/Write Multiplier: 1 Unit: Use to set the month PCC3300,
Savings End when daylight savings PCC2300,
Month Offset: 0 Lower Limit: 1 time ends. PCC3300V2
Size (bits): 8 Upper Limit: 12
Sign: U
43353 Daylight Read/Write 0: First Use to set the week of PCC3300,
Savings End Occurrence the month when PCC2300,
Week daylight savings time PCC3300V2
Occurrence 1: Second ends.
in Month Occurrence
2: Third
Occurrence
3: Fourth
Occurrence
4: Last
Occurrence
43354 Daylight Read/Write 0: Sunday Use to set the day of PCC3300,
Savings Start the week when PCC2300,
Day 1: Monday daylight savings time PCC3300V2
2: Tuesday starts.
3: Wednesday
4: Thursday
5: Friday
6: Saturday
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43355 Daylight Read/Write Multiplier: 1 Unit: Use to set the hour of PCC3300,
Savings Start the day when daylight PCC2300,
Hour Offset: 0 Lower Limit: 2 savings time starts. PCC3300V2
Size (bits): 8 Upper Limit: 19
Sign: U
43356 Daylight Read/Write Multiplier: 1 Unit: Use to set the month PCC3300,
Savings Start when daylight savings PCC2300,
Month Offset: 0 Lower Limit: 1 time starts. PCC3300V2
Size (bits): 8 Upper Limit: 12
Sign: U
43357 Daylight Read/Write 0: First Use to set the week of PCC3300,
Savings Start Occurrence the month when PCC2300,
Week daylight savings time PCC3300V2
Occurrence 1: Second starts.
in Month Occurrence
2: Third
Occurrence
3: Fourth
Occurrence
4: Last
Occurrence
43358 Daylight Read/Write Multiplier: 1 Unit: Minutes Use to set the amount PCC3300,
Savings of daylight savings PCC2300,
Time Offset: 0 Lower Limit: 0 time adjustment PCC3300V2
Adjustment Size (bits): 8 Upper Limit: 120 applied.
Sign: U
43359 Daylight Read/Write 0: Disabled Use to enable the PCC3300,
Savings daylight savings time PCC2300,
Time Enable 1: Enabled feature. PCC3300V2
43360 Exercise Read/Write 0: Disabled Enables the exercise PCC3300,
Scheduler scheduler. PCC2300,
Enable 1: Enabled PCC3300V2
43361 Reset Fuel Read/Write 0: Inactive The reset trip fuel PCC3300,
Consumption consumption PCC2300,
1: Active command. PCC3300V2
43362 Reset Runs Read/Write 0: Inactive The reset runs PCC3300,
command. PCC2300,
1: Active PCC3300V2
43363 Reset Start Read/Write 0: Inactive The reset start PCC3300,
Attempts attempts command. PCC2300,
1: Active PCC3300V2
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43364 Scheduler Read/Write Multiplier: 1 Unit: Used to select an PCC3300,
Exception exception to adjust. PCC2300,
Select Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 8 Upper Limit: 6
Sign: U
43369 Scheduler Read/Write 0: Disable Used to enable or PCC3300,
Exception x disable the selected PCC2300,
Enable 1: Enable exception. PCC3300V2
43374 Scheduler Read/Write Multiplier: 1 Unit: Used to select a PCC3300,
Program program to adjust. PCC2300,
Select Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 8 Upper Limit: 12
Sign: U
43377 Scheduler Read/Write 0: Disable Used to enable or PCC3300,
Program x disable the selected PCC2300,
Enable 1: Enable program. PCC3300V2
43379 Scheduler Read/Write 0: No Load Used to adjust the run PCC3300,
Program x mode for the selected PCC3300V2
Run Mode 1: With Load program.
2: Extended
Parallel
43383 Daylight Read/Write 0: Sunday Use to set the day of PCC3300,
Savings End the week when PCC2300,
Day 1: Monday daylight savings time PCC3300V2
2: Tuesday ends.
3: Wednesday
4: Thursday
5: Friday
6: Saturday
43502 Idle Rated Read Only 0: Idle The output command PCC3300,
Command of the Idle/Rated Logic PCC2300,
1: Rated PCC3300V2
43507 Load Dump Read Only 0: Inactive Monitors the state of PCC3300,
Overload the load dump PCC2300,
Condition 1: Active overload detection PCC3300V2
2: Reserved algorithm
3: Not Available
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43508 Load Dump Read Only 0: Inactive The state of the load PCC3300,
Underfreque dump underfrequency PCC2300,
ncy 1: Active detection algorithm PCC3300V2
Condition 2: Reserved
3: Not Available
43509 Low Battery Read Only Multiplier: 0.1 Unit: Vdc The low battery PCC3300,
Voltage voltage threshold PCC2300,
Running Offset: 0 Lower Limit: when the generator PCC3300V2
Threshold Size (bits): 16 Upper Limit: set is in rated mode
Sign: U
43510 Low Battery Read Only Multiplier: 0.1 Unit: Vdc The low battery PCC3300,
Voltage voltage threshold PCC2300,
Stopped Offset: 0 Lower Limit: when the generator PCC3300V2
Threshold Size (bits): 16 Upper Limit: set is not in rated
mode
Sign: U
43511 Low Battery Read Only Multiplier: 0.1 Unit: Vdc The selection of the PCC3300,
Voltage running or stopped PCC2300,
Threshold Offset: 0 Lower Limit: threshold PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43516 Prelube Read Only 0: Crank After Set to a required PCC3300,
Mode Prelube mode based on the PCC2300,
type of starting PCC3300V2
1: Crank With requirement
Prelube
2: Prelube Only
43517 Prelube Read Only 0: Complete The monitor point for PCC3300,
State the prelube state. PCC2300,
1: Armed PCC3300V2
2: Prelube
Output ON
3: Prelube
Output OFF
4: Enable Crank
43524 Remote Start Read Only 0: Stop The output of the PCC3300,
Command Remote Start PCC2300,
1: Start Command OR logic PCC3300V2
43530 Speed and Read Only 0: Inactive Monitor point for the PCC3300,
Voltage Bias command which PCC3300V2
Relay 1: Active closes the on-board
Command relay enabling the
voltage and speed
bias outputs.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43533 Start Read Only Multiplier: 1 Unit: seconds Time remaining until PCC3300,
Countdown start is initiated PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit: 300
Sign: U
43538 Starter Read Only 0: Inactive State of hardware PCC3300,
Command output. PCC2300,
1: Active PCC3300V2
2: Reserved
3: Not Available
43539 Stop Read Only Multiplier: 1 Unit: seconds Time remaining until PCC3300,
Countdown generator set stops PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
5000
Sign: U
43543 Time At No Read Only Multiplier: 1 Unit: seconds Amount of time the PCC3300,
Load generator set has run PCC2300,
Offset: 0 Lower Limit: 0 at no load PCC3300V2
Size (bits): 16 Upper Limit: 600
Sign: U
43544 Time at Read Only Multiplier: 1 Unit: seconds Amount of time spend PCC3300,
Rated in Rated Cooldown PCC2300,
Cooldown Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
5000
Sign: U
43547 Voltage Read Only Multiplier: 0.01 Unit: % The voltage setpoint PCC3300,
Setpoint command PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit: 150
Sign: U
43550 Weak Battery Read Only Multiplier: 0.1 Unit: Vdc Monitor point for the PCC3300,
Threshold weak battery voltage PCC2300,
Offset: 0 Lower Limit: 6 threshold PCC3300V2
Size (bits): 16 Upper Limit: 16
Sign: U
43551 Weak Battery Read/Write Multiplier: 1 Unit: seconds The time delay until a PCC3300,
Voltage Set weak battery condition PCC2300,
Time Offset: 0 Lower Limit: 1 is reported as a fault PCC3300V2
Size (bits): 16 Upper Limit: 5
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43553 Synchronizer Read Only 0: Synchronizer Indicates whether PCC3300,
Status Off synchronizer is on or PCC3300V2
off
1: Synchronizer
On
43554 Active Read Only Multiplier: 0.1 Unit: seconds Countdown value of PCC3300,
Transition the active transition PCC3300V2
Timer Offset: 0 Lower Limit: timer
Size (bits): 16 Upper Limit:
Sign: U
43555 Active Read Only 0: None Indicates the active PCC3300,
Transition transition type for PTC PCC3300V2
Type 1: Programmed
Transition
2: Transfer
3: Retransfer
4: Max Parallel
43558 ES State Read Only 0: Standby Internal paralleling PCC3300,
status variable PCC3300V2
1: Dead Bus
2: Synchronize
3: Load Share
4: Load Govern
43560 Genset CB Read Only 0: Inactive Generator set cb close PCC3300,
Close command status PCC3300V2
Command 1: Active
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43566 Genset CB Read Only 0: Inactive Generator set cb PCC3300,
Tripped tripped command PCC3300V2
Command 1: Active
43568 Genset Read Only Multiplier: 0.1 Unit: Hz Indicates the lower PCC3300,
Frequency drop-out threshold in PCC3300V2
Lower Drop- Offset: 0 Lower Limit: Hz for generator set
Out Size (bits): 16 Upper Limit: frequency sensor
Threshold
Sign: U
43569 Genset Read Only Multiplier: 0.1 Unit: Hz Indicates the lower PCC3300,
Frequency pick-up threshold in PCC3300V2
Lower Pick- Offset: 0 Lower Limit: Hz for generator set
Up Threshold Size (bits): 16 Upper Limit: frequency sensor
Sign: U
43570 Genset Read Only 0: Unknown Indicates generator set PCC3300,
Frequency frequency sensor PCC3300V2
Sensor 1: Picked Up status
Status 2: Dropped Out
43571 Genset Read Only Multiplier: 0.1 Unit: Hz Indicates the upper PCC3300,
Frequency drop-out threshold in PCC3300V2
Upper Drop- Offset: 0 Lower Limit: Hz for generator set
Out Size (bits): 16 Upper Limit: frequency sensor
Threshold
Sign: U
43572 Genset Read Only Multiplier: 0.1 Unit: Hz Indicates the upper PCC3300,
Frequency pick-up threshold in PCC3300V2
Upper Pick- Offset: 0 Lower Limit: Hz for generator set
Up Threshold Size (bits): 16 Upper Limit: frequency sensor
Sign: U
43573 Genset Loss Read Only 0: Unknown Indicates generator set PCC3300,
of Phase loss of phase sensor PCC3300V2
Sensor 1: Picked Up status
Status 2: Dropped Out
43574 Genset Read Only Multiplier: 1 Unit: Vac Indicates the drop-out PCC3300,
Overvoltage threshold in volts for PCC3300V2
Drop-Out Offset: 0 Lower Limit: generator set
Threshold Size (bits): 16 Upper Limit: overvoltage sensor
Sign: U
43575 Genset Read Only Multiplier: 1 Unit: Vac Indicates the pick-up PCC3300,
Overvoltage threshold in volts for PCC3300V2
Pick-Up Offset: 0 Lower Limit: generator set
Threshold Size (bits): 16 Upper Limit: overvoltage sensor
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43576 Genset Read Only 0: Unknown Indicates generator set PCC3300,
Overvoltage overvoltage sensor PCC3300V2
Sensor 1: Picked Up status
Status 2: Dropped Out
43577 Genset Read Only 0: Unknown Indicates generator set PCC3300,
Phase phase rotation sensor PCC3300V2
Rotation 1: Picked Up status
Sensor 2: Dropped Out
Status
43578 Genset Read Only Multiplier: 1 Unit: Vac Indicates the drop-out PCC3300,
Undervoltage threshold in volts for PCC3300V2
Drop-Out Offset: 0 Lower Limit: generator set
Threshold Size (bits): 16 Upper Limit: undervoltage sensor
Sign: U
43579 Genset Read Only Multiplier: 1 Unit: Vac Indicates the pick-up PCC3300,
Undervoltage threshold in volts for PCC3300V2
Pick-Up Offset: 0 Lower Limit: generator set
Threshold Size (bits): 16 Upper Limit: undervoltage sensor
Sign: U
43580 Genset Read Only 0: Unknown Indicates generator set PCC3300,
Undervoltage undervoltage sensor PCC3300V2
Sensor 1: Picked Up status
Status 2: Dropped Out
43584 Paralleling Read Only 0: Isochronous Indicates which speed PCC3300,
Speed control algorithm is in PCC2300,
Control Mode 1: Droop effect PCC3300V2
2: Synchronize
3: Load Share
4: Load Govern
43585 Paralleling Read Only 0: Isochronous Indicates which PCC3300,
Voltage voltage control PCC2300,
Control Mode 1: Droop algorithm is in effect PCC3300V2
2: Synchronize
3: Load Share
4: Load Govern
43589 PTC Read Only 0: Open Indicates the transition PCC3300,
Operating Transition type currently in effect PCC3300V2
Transition
Type 1: Hard Closed
Transition
2: Soft Closed
Transition
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43590 PTC State Read Only 0: PTC Not Indicates the PCC3300,
Enabled connected state of the PCC3300V2
Power Transfer
1: No Source Control
Connected
2: Utility
Connected
3: Genset
Connected
4: Paralleled
43597 Utility CB Read Only 0: Inactive Utility cb close PCC3300,
Close command status PCC3300V2
Command 1: Active
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43616 Configurable Read/Write Multiplier: 1 Unit: The event code for PCC3300,
Output #21 this output. PCC3300V2
Event Code Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
43619 Configurable Read/Write Multiplier: 1 Unit: The event code for PCC3300,
Output #22 this output. PCC3300V2
Event Code Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
43622 Configurable Read/Write Multiplier: 1 Unit: The event code for PCC3300,
Output #3 this output. PCC2300,
Event Code Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
65530
Sign: U
43625 Configurable Read/Write Multiplier: 1 Unit: The event code for PCC3300,
Output #4 this output. PCC2300,
Event Code Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 16 Upper Limit:
65530
Sign: U
43641 Delayed Read/Write 0: Disabled Enables the Delayed PCC3300,
Shutdown Shutdown feature. PCC2300,
Enable 1: Enabled PCC3300V2
43642 Delayed Read/Write Multiplier: 0.1 Unit: seconds Sets the shutdown PCC3300,
Shutdown fault delayed time PCC2300,
Time Delay Offset: 0 Lower Limit: 0 delay for the Delayed PCC3300V2
Size (bits): 16 Upper Limit: 3 Shutdown feature.
Sign: U
43643 Remote Fault Read/Write 0: Disable Trim to enable PCC3300,
Reset Remote Fault Reset. PCC2300,
Enabled 1: Enable Can only reset PCC3300V2
"Warning" Faults
43644 Fail To Read/Write Multiplier: 1 Unit: seconds Trim to set the time for PCC3300,
Shutdown a shutdown fault to be PCC2300,
Delay Offset: 0 Lower Limit: 0 active and the PCC3300V2
Size (bits): 16 Upper Limit: 30 generator set not
shutting down before
Sign: U the Fail to Shutdown
fault occurs.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43645 LCL Read/Write 0: None Sets low coolant level PCC3300,
Detection fault response to PCC2300,
Response 1: Warning None, Warning or PCC3300V2
2: Shutdown Shutdown.
43646 LCT Warning Read/Write Multiplier: 1 Unit: Minutes Sets time to clear the PCC3300,
Clear Time low coolant temp fault. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 30
Sign: U
43647 LCT Warning Read/Write Multiplier: 1 Unit: Minutes Sets time to set the PCC3300,
Set Time low coolant temp fault. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 8 Upper Limit: 30
Sign: U
43648 LCT Warning Read/Write Multiplier: 1 Unit: degF Sets threshold for the PCC3300,
Threshold low coolant temp fault PCC2300,
Offset: 0 Lower Limit: -20 warning. PCC3300V2
Size (bits): 16 Upper Limit: 130
Sign: S
43649 V/Hz Knee Read/Write Multiplier: 0.1 Unit: Hz The voltage will roll off PCC3300,
Frequency (decrease) PCC2300,
Offset: 0 Lower Limit: 0 proportionally to the PCC3300V2
Size (bits): 16 Upper Limit: 10 V/Hz setup, once the
frequency drops below
Sign: U the set point in the
V/Hz Knee Frequency.
This allows the
generator set to
recover faster when
the frequency drops.
43650 V/Hz Rolloff Read/Write Multiplier: 0.1 Unit: % / Hz The amount of voltage PCC3300,
Slop roll off when the PCC2300,
Offset: 0 Lower Limit: 0 frequency is below the PCC3300V2
Size (bits): 16 Upper Limit: 20 knee frequency
Sign: U
43651 12 V High Read Only Multiplier: 0.1 Unit: Vdc Sets 12V high battery PCC3300,
Battery voltage fault threshold. PCC2300,
Voltage Offset: 0 Lower Limit: 14 PCC3300V2
Threshold Size (bits): 16 Upper Limit: 17
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43652 12 V Low Read Only Multiplier: 0.1 Unit: Vdc Sets 12V low battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 12 for generator set PCC3300V2
Running Size (bits): 16 Upper Limit: 16 operation while in
Threshold rated mode
Sign: U
43653 12 V Low Read Only Multiplier: 0.1 Unit: Vdc Sets 12V low battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 11 for generator set PCC3300V2
Stopped Size (bits): 16 Upper Limit: 13 operation in all modes
Threshold except rated
Sign: U
43654 12 V Weak Read/Write Multiplier: 0.1 Unit: Vdc Sets 12V weak battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 6 PCC3300V2
Threshold Size (bits): 16 Upper Limit: 10
Sign: U
43655 24 V High Read Only Multiplier: 0.1 Unit: Vdc Sets 24V high battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 28 PCC3300V2
Threshold Size (bits): 16 Upper Limit: 34
Sign: U
43656 24 V Low Read Only Multiplier: 0.1 Unit: Vdc Sets 24V low battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 24 for generator set PCC3300V2
Running Size (bits): 16 Upper Limit: 28 operation while in
Threshold rated mode
Sign: U
43657 24 V Low Read Only Multiplier: 0.1 Unit: Vdc Sets 24V low battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 22 for generator set PCC3300V2
Stopped Size (bits): 16 Upper Limit: 26 operation in all modes
Threshold except rated
Sign: U
43658 24 V Weak Read/Write Multiplier: 0.1 Unit: Vdc Sets 24V weak battery PCC3300,
Battery voltage fault threshold PCC2300,
Voltage Offset: 0 Lower Limit: 10 PCC3300V2
Threshold Size (bits): 16 Upper Limit: 16
Sign: U
43659 Adjustable Read/Write Multiplier: 0.01 Unit: rpm/Hz Sets the rpm/Hz PCC3300,
Freq/Speed conversion factor PCC2300,
Gain Offset: 0 Lower Limit: 0 when the Freq to PCC3300V2
Size (bits): 16 Upper Limit: 240 Speed Gain Select
trim is set to this trim
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43660 Alternate Read Only 0: 50 Hz Sets the generator set PCC3300,
Frequency nominal frequency. PCC2300,
Switch 1: 60 Hz PCC3300V2
43661 AVR Gain Read/Write Multiplier: 0.01 Unit: A trim that allows the PCC3300,
Adjust Trim user to modify the PCC2300,
Offset: 0 Lower Limit: 0.05 overall gains of the PCC3300V2
Size (bits): 16 Upper Limit: 10 AVR.
Sign: U
43662 Charging Read/Write Multiplier: 0.1 Unit: seconds Sets the time delay for PCC3300,
Alternator the charging alt failure PCC2300,
Fault Time Offset: 0 Lower Limit: 2 fault PCC3300V2
Delay Size (bits): 16 Upper Limit: 300
Sign: U
43663 Continuous Read/Write Multiplier: 1 Unit: seconds Sets the maximum PCC3300,
Crank amount of time to PCC2300,
Engage Time Offset: 0 Lower Limit: 40 engage the starter PCC3300V2
Size (bits): 16 Upper Limit: 100 when using the
continuous cranking
Sign: U method
43664 Controlled Read/Write Multiplier: 1 Unit: seconds Delay allowed for a PCC3300,
Shutdown shutdown with PCC3300V2
Advance Offset: 0 Lower Limit: 0 cooldown fault prior to
Notice Delay Size (bits): 16 Upper Limit: 300 shutting down the
genset
Sign: U
43665 Crank Read/Write Multiplier: 1 Unit: Sets the maximum PCC3300,
Attempts number of times to PCC2300,
Offset: 0 Lower Limit: 1 engage the starter PCC3300V2
Size (bits): 16 Upper Limit: 7 when attempting to
start engine using the
Sign: U cycle cranking method
43666 Cycle / Cont Read Only 0: Cycle Selects whether to use PCC3300,
Crank Select continuous cranking or PCC2300,
1: Continuous cycle cranking when PCC3300V2
attempting to start
engine
43667 Cycle Crank Read/Write Multiplier: 1 Unit: seconds Sets the maximum PCC3300,
Engage Time amount of time to PCC2300,
Offset: 0 Lower Limit: 2 engage the starter PCC3300V2
Size (bits): 16 Upper Limit: 20 during a single crank
attempt when using
Sign: U the cycle cranking
method
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43668 Cycle Crank Read/Write Multiplier: 1 Unit: seconds Rest time between PCC3300,
Rest Time start attempts for cycle PCC2300,
Offset: 0 Lower Limit: 7 crank mode. PCC3300V2
Size (bits): 16 Upper Limit: 40
Sign: U
43669 Delayed Off Read/Write Multiplier: 0.1 Unit: seconds Time delay between PCC3300,
FSO Relay when the Delayed Off PCC2300,
Time Offset: 0 Lower Limit: 0 Command turns off PCC3300V2
Size (bits): 16 Upper Limit: 120 and Run Command
turns off
Sign: U
TABLE 41.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43670 External AVR Read/Write Multiplier: 0.1 Unit: Hz Sets the knee PCC3300,
Knee frequency for the fixed PCC2300,
Frequency Offset: 0 Lower Limit: 0 knee freq logic. PCC3300V2
Size (bits): 16 Upper Limit: 10
Sign: U
43671 External Bias Read/Write 0: Disabled Enables the external PCC3300,
Commands bias (speed and PCC3300V2
Enable 1: Enabled voltage commands) to
the hardware outputs.
43672 Frequency Read/Write Multiplier: 0.01 Unit: Hz A method of adding in PCC3300,
Adjust a frequency offset to PCC2300,
Offset: 0 Lower Limit: -6 the base frequency PCC3300V2
Size (bits): 16 Upper Limit: 6 subject to high and
low limit calibrations.
Sign: S
43673 Genset Read/Write Multiplier: 0.1 Unit: hours Sets the total exercise PCC3300,
Exercise time not including PCC2300,
Time Offset: 0 Lower Limit: 0 warmup at idle or idle PCC3300V2
Size (bits): 16 Upper Limit: 25 cooldown time.
Sign: U
43674 Governor Read Only Multiplier: 0.01 Unit: A trim that allows the PCC3300,
Gain Adjust user to modify the PCC2300,
Offset: 0 Lower Limit: 0.05 overall gain of the PCC3300V2
Size (bits): 16 Upper Limit: 15 governor.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43675 High Battery Read Only Multiplier: 1 Unit: seconds The time delay until a PCC3300,
Voltage Set high battery voltage PCC2300,
Time Offset: 0 Lower Limit: 2 condition is reported PCC3300V2
Size (bits): 16 Upper Limit: 60 as a fault.
Sign: U
43676 High Battery Read Only Multiplier: 0.1 Unit: Vdc The high battery PCC3300,
Voltage voltage threshold PCC2300,
Threshold Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43677 Idle Read/Write Multiplier: 0.25 Unit: minutes Sets time to run at idle PCC3300,
Cooldown before shutting down PCC2300,
Time Offset: 0 Lower Limit: 0 generator set on PCC3300V2
Size (bits): 16 Upper Limit: 60 normal stops.
Sign: U
43678 Idle Speed Read Only Multiplier: 1 Unit: rpm Sets the speed at PCC3300,
which the engine will PCC2300,
Offset: 0 Lower Limit: 700 idle subject to high PCC3300V2
Size (bits): 16 Upper Limit: and low limit
1100 calibrations.
Sign: U
43679 Idle to Rated Read/Write Multiplier: 0.1 Unit: seconds The time over which PCC3300,
Ramp Time the speed reference is PCC2300,
Offset: 0 Lower Limit: 0 to ramp from idle PCC3300V2
Size (bits): 16 Upper Limit: 30 speed to rated speed.
Sign: U
43680 Idle Warmup Read/Write Multiplier: 1 Unit: degF Coolant temperature PCC3300,
Coolant threshold to end idle PCC2300,
Temp Offset: 0 Lower Limit: -40 warmup time. PCC3300V2
Size (bits): 16 Upper Limit: 300
Sign: S
43681 Idle Warmup Read/Write Multiplier: 1 Unit: seconds Sets maximum idle PCC3300,
Time warmup time. Warmup PCC2300,
Offset: 0 Lower Limit: 0 time may be less if PCC3300V2
Size (bits): 16 Upper Limit: coolant temperature
3600 exceeds threshold.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43682 Load Dump Read/Write 0: Overload Enables the load PCC3300,
Activation dump output as a PCC2300,
Method 1: function of the PCC3300V2
Underfrequency overload and
2: Overload or underfrequency
Underfrequency conditions.
3: Diasabled
43683 Load Dump Read/Write Multiplier: 1 Unit: seconds The time delay until PCC3300,
Overload Set the load dump PCC2300,
Time Offset: 0 Lower Limit: 0 overload condition is PCC3300V2
Size (bits): 16 Upper Limit: 120 set active.
Sign: U
43684 Load Dump Read/Write Multiplier: 1 Unit: % The load dump PCC3300,
Overload overload threshold as PCC2300,
Threshold Offset: 0 Lower Limit: 80 a percentage of the PCC3300V2
Size (bits): 16 Upper Limit: 140 generator set
application rating.
Sign: U
43685 Load Dump Read/Write Multiplier: 1 Unit: Hz The frequency amount PCC3300,
Underfreque which the load dump PCC2300,
ncy Offset Offset: 0 Lower Limit: 0 underfrequency PCC3300V2
Size (bits): 16 Upper Limit: 10 threshold is below the
final frequency
Sign: S reference.
43686 Load Dump Read/Write Multiplier: 1 Unit: seconds The time delay until PCC3300,
Underfreque the load dump PCC2300,
ncy Set Time Offset: 0 Lower Limit: 0 underfrequency PCC3300V2
Size (bits): 16 Upper Limit: 20 condition is set active.
Sign: U
43687 Load Dump Read Only Multiplier: 0.1 Unit: Hz The frequency trip PCC3300,
Underfreque threshold for the load PCC2300,
ncy Offset: 0 Lower Limit: 0 dump underfrequency PCC3300V2
Threshold Size (bits): 16 Upper Limit: 90 condition.
Sign: U
43688 Low Battery Read Only Multiplier: 1 Unit: seconds The time delay until a PCC3300,
Voltage Set low battery voltage PCC2300,
Time Offset: 0 Lower Limit: 2 condition is reported PCC3300V2
Size (bits): 16 Upper Limit: 60 as a fault.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43689 Low Fuel in Read/Write Multiplier: 1 Unit: seconds Low Fuel in Day Tank PCC3300,
Day Tank Fault time delay from PCC2300,
Time Offset: 0 Lower Limit: 0 switch input. PCC3300V2
Size (bits): 16 Upper Limit: 20
Sign: U
43690 Low Fuel Read/Write Multiplier: 1 Unit: seconds A trim that sets the PCC3300,
Set/Clear delay time for PCC2300,
Time Offset: 0 Lower Limit: 2 generating the inactive PCC3300V2
Size (bits): 16 Upper Limit: 60 and active faults.
Sign: U
43691 Manual Read/Write 0: Normal Use to command idle PCC3300,
Warmup speed or to bypass PCC2300,
Bypass 1: Bypass idle warmup during a PCC3300V2
Warmup manual run.
43692 Max Idle Read/Write Multiplier: 0.1 Unit: minutes Sets the fault time for PCC3300,
Time the Too Long in Idle PCC2300,
Offset: 0 Lower Limit: 0 fault. PCC3300V2
Size (bits): 16 Upper Limit: 20
Sign: U
43693 Nominal Read Only 0: 12V Selects the generator PCC3300,
Battery set’s nominal battery PCC2300,
Voltage 1: 24V operating voltage. PCC3300V2
43694 Prelube Read/Write 0: Disabled Enables Or Disables PCC3300,
Cycle Enable the cyclic mode of PCC2300,
1: Enabled prelube operation. PCC3300V2
43695 Prelube Read/Write Multiplier: 0.1 Unit: hours "Sets the period of the PCC3300,
Cycle Time Prelube Cycle PCC2300,
Offset: 0 Lower Limit: 0.1 Iteration. PCC will PCC3300V2
Size (bits): 16 Upper Limit: truncate any
1000 ‘remainder’ minutes
time set in the ECM
Sign: U when Prelube Owner
is ECS e.g. if 65 or 66
minute is set in ECM
then PCC will show
1.0 hours and 1.1
hours respectively."
43696 Prelube Read/Write 0: Disabled Selects whether the PCC3300,
Function Prelube function is PCC2300,
Enable 1: Enabled enabled or disabled. PCC3300V2
This is Setup mode
interlocked.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43697 Prelube Oil Read/Write Multiplier: 0.1 Unit: psig The oil pressure value PCC3300,
Pressure which when reached PCC2300,
Threshold Offset: 0 Lower Limit: 0 the prelube driver will PCC3300V2
Size (bits): 16 Upper Limit: 10 turn off.
Sign: U
43698 Prelube Read/Write Multiplier: 0.1 Unit: seconds Sets the maximum PCC3300,
Timeout time for which the PCC2300,
Period Offset: 0 Lower Limit: 0 Prelube Driver will PCC3300V2
Size (bits): 16 Upper Limit: 60 Remain ON.
Sign: U
43699 Rated to Idle Read/Write Multiplier: 0.1 Unit: seconds The time over which PCC3300,
Ramp Time the speed reference is PCC2300,
Offset: 0 Lower Limit: 0 to ramp from rated PCC3300V2
Size (bits): 16 Upper Limit: 30 speed to idle speed.
Sign: U
43700 Utility Read Only 0: Not Available Indicates status of the PCC3300,
Availability utility source. PCC3300V2
Status 1: Available
2: Unknown
43701 Utility CB Read Only 0: Inactive Utility cb inhibit PCC3300,
Inhibit command PCC3300V2
Command 1: Active
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43706 Utility Read Only 0: Unknown Indicates utility PCC3300,
Frequency frequency sensor PCC3300V2
Sensor 1: Picked Up status.
Status 2: Dropped Out
43707 Utility Read Only Multiplier: 0.1 Unit: Hz Indicates the upper PCC3300,
Frequency drop-out threshold in PCC3300V2
Upper Drop- Offset: 0 Lower Limit: Hz for utility frequency
Out Size (bits): 16 Upper Limit: sensor.
Threshold
Sign: U
43708 Utility Read Only Multiplier: 0.1 Unit: Hz Indicates the upper PCC3300,
Frequency pick-up threshold in PCC3300V2
Upper Pick- Offset: 0 Lower Limit: Hz for utility frequency
Up Threshold Size (bits): 16 Upper Limit: sensor.
Sign: U
43709 Utility Loss of Read Only 0: Unknown Indicates utility loss of PCC3300,
Phase phase sensor status. PCC3300V2
Sensor 1: Picked Up
Status 2: Dropped Out
43710 Utility Read Only Multiplier: 1 Unit: Vac Indicates the drop-out PCC3300,
Overvoltage threshold in volts for PCC3300V2
Drop-Out Offset: 0 Lower Limit: utility overvoltage
Threshold Size (bits): 16 Upper Limit: sensor.
Sign: U
43711 Utility Read Only Multiplier: 1 Unit: Vac Indicates the pick-up PCC3300,
Overvoltage threshold in volts for PCC3300V2
Pick-Up Offset: 0 Lower Limit: utility overvoltage
Threshold Size (bits): 16 Upper Limit: sensor.
Sign: U
43712 Utility Read Only 0: Unknown Indicates utility PCC3300,
Overvoltage overvoltage sensor PCC3300V2
Sensor 1: Picked Up status.
Status 2: Dropped Out
43713 Utility Phase Read Only 0: Unknown Indicates utility phase PCC3300,
Rotation rotation sensor status. PCC3300V2
Sensor 1: Picked Up
Status 2: Dropped Out
43714 Utility Read Only Multiplier: 1 Unit: Vac Indicates the drop-out PCC3300,
Undervoltage threshold in volts for PCC3300V2
Drop-Out Offset: 0 Lower Limit: utility undervoltage
Threshold Size (bits): 16 Upper Limit: sensor.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43715 Utility Read Only Multiplier: 1 Unit: Vac Indicates the pick-up PCC3300,
Undervoltage threshold in volts for PCC3300V2
Pick-Up Offset: 0 Lower Limit: utility undervoltage
Threshold Size (bits): 16 Upper Limit: sensor.
Sign: U
43716 Utility Read Only 0: Unknown Indicates utility PCC3300,
Undervoltage undervoltage sensor PCC3300V2
Sensor 1: Picked Up status.
Status 2: Dropped Out
43719 Alternator Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature Alternator Temp 1 PCC2300,
1 (Aux101) Offset: 0 Lower Limit: input from the Aux 101 PCC3300V2
-32767 I/O Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43720 Alternator Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature Alternator Temp 2 PCC2300,
2 (Aux101) Offset: 0 Lower Limit: input from the Aux 101 PCC3300V2
-32767 I/O Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43721 Alternator Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature Alternator Temp 3 PCC2300,
3 (Aux101) Offset: 0 Lower Limit: input from the Aux 101 PCC3300V2
-32767 I/O Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43722 Ambient Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature Ambient Temp input PCC2300,
(Aux101) Offset: 0 Lower Limit: from the Aux 101 I/O PCC3300V2
-32767 Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43723 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
1 Voltage Offset: 0 Lower Limit: -500 1 in Volts. PCC3300V2
Size (bits): 16 Upper Limit: 500
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43724 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
2 Voltage Offset: 0 Lower Limit: -500 2 in Volts. PCC3300V2
Size (bits): 16 Upper Limit: 500
Sign: S
43725 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
3 Voltage Offset: 0 Lower Limit: 3 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43726 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
4 Voltage Offset: 0 Lower Limit: 4 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43727 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
5 Voltage Offset: 0 Lower Limit: 5 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43728 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
6 Voltage Offset: 0 Lower Limit: 6 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43729 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
7 Voltage Offset: 0 Lower Limit: 7 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43730 Aux101 0 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 0 analog input PCC2300,
8 Voltage Offset: 0 Lower Limit: 8 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43731 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
1 Voltage Offset: 0 Lower Limit: -500 1 in Volts. PCC3300V2
Size (bits): 16 Upper Limit: 500
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43732 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
2 Voltage Offset: 0 Lower Limit: -500 2 in Volts. PCC3300V2
Size (bits): 16 Upper Limit: 500
Sign: S
43733 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
3 Voltage Offset: 0 Lower Limit: 3 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43734 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
4 Voltage Offset: 0 Lower Limit: 4 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43735 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
5 Voltage Offset: 0 Lower Limit: 5 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43736 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
6 Voltage Offset: 0 Lower Limit: 6 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43737 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
7 Voltage Offset: 0 Lower Limit: 7 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43738 Aux101 1 Read Only Multiplier: 0.01 Unit: Vdc Monitor point for the PCC3300,
Analog Input module 1 analog input PCC2300,
8 Voltage Offset: 0 Lower Limit: 8 in Volts. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43739 Battery Read Only 0: Inactive Monitor point for the PCC3300,
Charger AC battery charger failure PCC2300,
Failure 1: Active input from the PCC3300V2
(HMI113) PCCNET Annunciator.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43740 Drive End Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Bearing Drive End Bearing PCC2300,
Temperature Offset: 0 Lower Limit: Temp input from the PCC3300V2
(Aux101) -32767 I/O Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43741 Exhaust Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Stack Exhaust Stack Temp1 PCC2300,
Temperature Offset: 0 Lower Limit: input from the I/O PCC3300V2
1 (Aux101) -32767 Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43742 Exhaust Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Stack Exhaust Stack Temp2 PCC2300,
Temperature Offset: 0 Lower Limit: input from the I/O PCC3300V2
2 (Aux101) -32768 Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43745 Fuel Level % Read Only Multiplier: 0.1 Unit: % Monitor point for the % PCC3300,
(Aux101) fuel level input from PCC2300,
Offset: 0 Lower Limit: the I/O Module. PCC3300V2
Size (bits): 16 Upper Limit:
Sign: S
43746 Fuel Level Read Only Multiplier: 1 Unit: Monitor point for the PCC3300,
(Aux101) fuel level (in gallons) PCC2300,
Offset: 0 Lower Limit: input from the I/O PCC3300V2
Size (bits): 16 Upper Limit: Module.
Sign: S
43747 HMI113 Fault Read Only 0: Inactive Monitor point for input PCC3300,
1 Status #1 from the PCC2300,
1: Active Annunciator. PCC3300V2
43748 HMI113 Fault Read Only 0: Inactive Monitor point for input PCC3300,
2 Status #2 from the PCC2300,
1: Active Annunciator. PCC3300V2
43749 HMI113 Fault Read Only 0: Inactive Monitor point for the PCC3300,
3 Status input #3 from the PCC2300,
1: Active Annunciator. PCC3300V2
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43750 Intake Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Manifold Intake Manifold Temp PCC2300,
Temperature Offset: 0 Lower Limit: 1 input from the I/O PCC3300V2
1 (Aux101) -32768 Module.
Size (bits): 16 Upper Limit:
32762
Sign: S
43751 Low Coolant Read Only 0: Inactive Monitor point for the PCC3300,
Level Low Coolant Level PCC2300,
(HMI113) 1: Active input from the PCCnet PCC3300V2
Annunciator.
43752 Low Fuel Read Only 0: Inactive Monitor point for the PCC3300,
Level Low Fuel Level input PCC2300,
(HMI113) 1: Active from the PCCnet PCC3300V2
Annunciator.
43753 LTA Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature LTA Temperature PCC3300V2
(Aux101) Offset: 0 Lower Limit: -40 input from the I/O
Size (bits): 16 Upper Limit: 300 Module
Sign: S
43755 Non-Drive Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
End Bearing Non-Drive End PCC2300,
Temperature Offset: 0 Lower Limit: Bearing Temp input PCC3300V2
(Aux101) -65534 from the I/O Module.
Size (bits): 16 Upper Limit:
65535
Sign: S
43756 Number of Read Only Multiplier: 1 Unit: Used to monitor the PCC3300,
Connected amount of connected PCC2300,
Bargraph Offset: 0 Lower Limit: 0 Bargraph modules. PCC3300V2
Modules Size (bits): 8 Upper Limit: 255
Sign: U
43757 Oil Read Only Multiplier: 1 Unit: degF Monitor point for the PCC3300,
Temperature Oil Temp input from PCC2300,
(Aux101) Offset: 0 Lower Limit: the I/O Module. PCC3300V2
-65534
Size (bits): 16 Upper Limit:
65535
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43758 Modbus Bus Read Only Multiplier: 1 Unit: Modbus bus message PCC3300,
Message count PCC2300,
Count Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43759 Modbus CRC Read Only Multiplier: 1 Unit: Modbus CRC errors PCC3300,
Errors Count count PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43760 Modbus Read Only Multiplier: 1 Unit: Modbus exception PCC3300,
Exception count PCC2300,
Count Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43761 Modbus No Read Only Multiplier: 1 Unit: Modbus no response PCC3300,
Response count PCC2300,
Count Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
43762 Modbus Read Only Multiplier: 1 Unit: Modbus slave PCC3300,
Slave message count PCC2300,
Message Offset: 0 Lower Limit: PCC3300V2
Count Size (bits): 16 Upper Limit:
Sign: U
43763 Frequency Read Only Multiplier: 0.001 Unit: Hz Frequency match error PCC3300,
Match Error value used by PCC3300V2
Offset: 0 Lower Limit: frequency match PI
Size (bits): 16 Upper Limit: loop.
Sign: S
43767 Load Govern Read Only Multiplier: 0.01 Unit: % Indicates the final PCC3300,
kVAR Target target setpoint for PCC3300V2
Offset: 0 Lower Limit: generator set kVAR
Size (bits): 16 Upper Limit: output when paralleled
to utility.
Sign: S
43769 Load Govern Read Only Multiplier: 0.01 Unit: % Indicates the final PCC3300,
kW Target target setpoint for PCC3300V2
Offset: 0 Lower Limit: genset kW output
Size (bits): 16 Upper Limit: when paralleled to
utility.
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43770 Permissive Read Only 0: Not Allowed Indicates when PCC3300,
Close permissive sync check PCC3300V2
Allowed 1: Allowed conditions have been
met.
43773 Phase Match Read Only Multiplier: 0.01 Unit: deg Phase error signal for PCC3300,
Error the synchronizer PCC3300V2
Offset: 0 Lower Limit: control algorithm.
Size (bits): 16 Upper Limit:
Sign: S
43777 Start Read Only 0: Inactive This is the status of PCC3300,
Type/Configu the Configurable Input PCC2300,
rable Input 1: Active #11. PCC3300V2
#11 Switch
43778 Scheduler Read Only 0: Off Indicates the current PCC3300,
Run run command coming PCC2300,
Command 1: No Load from the scheduler. PCC3300V2
2: With Load
3: Extended
Parallel
43785 Start Read/Write Multiplier: 1 Unit: Number of start PCC3300,
Attempts attempts since the last PCC2300,
Since Reset Offset: 0 Lower Limit: 0 reset. PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
43786 Start Read/Write Multiplier: 1 Unit: Number of start PCC3300,
Attempts attempts since the last PCC2300,
Since Reset Offset: 0 Lower Limit: 0 reset. PCC3300V2
Size (bits): 32 Upper Limit:
4294967290
Sign: U
43787 Total Start Read/Write Multiplier: 1 Unit: Total number of start PCC3300,
Attempts attempts. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U
43788 Total Start Read/Write Multiplier: 1 Unit: Total number of start PCC3300,
Attempts attempts. PCC2300,
Offset: 0 Lower Limit: 0 PCC3300V2
Size (bits): 32 Upper Limit:
4294967295
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43789 Backup Start Read Only 0: Inactive This is the status of PCC3300,
Disconnect/C the Configurable Input PCC3300V2
onfigurable 1: Active #33.
Input #33
Switch
43791 Battery Read Only 0: Inactive Battery Charger Failed PCC3300,
Charger Switch function output PCC2300,
Failed Switch 1: Active status; gives software PCC3300V2
Inactive/Active state.
43792 Battle Short Read Only 0: Inactive Battle Short Switch PCC3300,
Switch function output status PCC2300,
1: Active (Active or Inactive). PCC3300V2
43793 Configurable Read Only 0: Inactive Configurable Input #1 PCC3300,
Input #1 input software state PCC2300,
Switch 1: Active status. Gives software PCC3300V2
Inactive/Active state.
43794 Configurable Read Only 0: Inactive Configurable Input #2 PCC3300,
Input #2 input software state PCC2300,
Switch 1: Active status. Gives software PCC3300V2
Inactive/Active state.
43795 Configurable Read Only 0: Inactive Configurable Input #13 PCC3300,
Input #13 input software state PCC2300,
Switch 1: Active status. Gives software PCC3300V2
Inactive/Active state.
43796 Genset CB Read Only 0: Inactive Generator set cb open PCC3300,
Open command status. PCC3300V2
Command 1: Active
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43803 Start Time Read/Write Multiplier: 1 Unit: seconds Sets the time to wait PCC3300,
Delay from receiving a valid PCC2300,
Offset: 0 Lower Limit: 0 remote start signal PCC3300V2
Size (bits): 16 Upper Limit: 300 until starting the
generator set.
Sign: U
43804 Starting to Read/Write Multiplier: 0.1 Unit: seconds The time over which PCC3300,
Rated Ramp the speed reference is PCC2300,
Time Offset: 0 Lower Limit: 0 to ramp from starting PCC3300V2
Size (bits): 16 Upper Limit: 30 speed to rated speed
Sign: U
43805 Time Delay Read/Write Multiplier: 1 Unit: seconds Sets time to run at PCC3300,
to Stop rated speed before PCC2300,
Offset: 0 Lower Limit: 0 going to cooldown at PCC3300V2
Size (bits): 16 Upper Limit: 600 idle. Does not apply to
manual runs
Sign: U
43806 Voltage Read/Write Multiplier: 0.01 Unit: % A trim that allows the PCC3300,
Adjust user to add/subtract PCC2300,
Offset: 0 Lower Limit: -5 an offset to the PCC3300V2
Size (bits): 16 Upper Limit: 5 nominal voltage when
calculating the voltage
Sign: S setpoint
43807 Voltage Read/Write Multiplier: 0.01 Unit: seconds The time period over PCC3300,
Ramp Time which the voltage PCC2300,
Offset: 0 Lower Limit: 0 setpoint command PCC3300V2
Size (bits): 16 Upper Limit: 5 should rise from 0% to
the target voltage
Sign: U
43808 Commit to Read Only 0: Not PTC - indicates if PCC3300,
Transfer Committed system is committed PCC3300V2
State to transferring to
1: Committed generator set
43810 Battle Short Read/Write 0: Inactive Trim to enable Battle PCC3300,
Switch Short via Modbus. PCC2300,
(Modbus) 1: Active PCC3300V2
43811 Exercise Read/Write 0: Inactive Modbus exercise PCC3300,
Switch switch PCC2300,
(Modbus) 1: Active PCC3300V2
43813 Extended Read/Write 0: Inactive Modbus extended PCC3300,
Parallel parallel switch PCC2300,
Switch 1: Active PCC3300V2
(Modbus)
43814 PTC Mode Read/Write 0: Inactive Modbus PTC Mode PCC3300,
Switch switch PCC3300V2
(Modbus) 1: Active
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43815 Start Type Read/Write 0: Emergency PCC3300,
(Modbus) PCC2300,
1: Non PCC3300V2
Emergency
43818 Isolated Bus Read/Write 0: Constant Sets the speed control PCC3300,
Speed method for isolated PCC2300,
Control 1: Droop bus paralleling. PCC3300V2
Method Parameter is also
known as Load Share
Speed Droop Control
Method
43819 Isolated Bus Read/Write 0: Constant Sets the voltage PCC3300,
Voltage control method for PCC2300,
Control 1: Droop isolated bus PCC3300V2
Method paralleling.
43820 Maximum Read/Write Multiplier: 0.1 Unit: seconds Sets the maximum PCC3300,
Parallel Time time that the generator PCC3300V2
(TDMP) Offset: 0 Lower Limit: 0 set can remain
Size (bits): 16 Upper Limit: paralleled to the utility
1800 during closed
transition transfers.
Sign: U
43821 Programmed Read/Write Multiplier: 0.1 Unit: seconds Sets the time delay PCC3300,
Transition from when one source PCC3300V2
Delay Offset: 0 Lower Limit: 0 opens until the other
(TDPT) Size (bits): 16 Upper Limit: 60 closes during open
transition transfers.
Sign: U
43822 Retransfer Read/Write Multiplier: 0.1 Unit: seconds Sets the amount of PCC3300,
Delay time that the utility PCC3300V2
(TDEN) Offset: 0 Lower Limit: 0 source must be
Size (bits): 16 Upper Limit: available before the
1800 control will retranfer to
that source.
Sign: U
43823 Synchronizer Read/Write 0: Phase Match Sets the speed control PCC3300,
Speed method for PCC3300V2
Control 1: Slip synchronizing.
Method Frequency
2: External
43824 Synchronizer Read/Write 0: Voltage Match Sets the voltage PCC3300,
Voltage control method for PCC3300V2
Control 1: External synchronizing.
Method
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43825 Transfer Read/Write Multiplier: 0.1 Unit: seconds Sets the amount of PCC3300,
Delay time that the generator PCC3300V2
(TDNE) Offset: 0 Lower Limit: 0 set source must be
Size (bits): 16 Upper Limit: 120 available before the
control will tranfer to
Sign: U that source.
43826 Transition Read/Write 0: Open Sets the load transfer PCC3300,
Type Transition transition type for use PCC3300V2
when Generator set
1: Hard Closed Application Type =
Transition Power Transfer
2: Soft Closed Control.
Transition
43829 Utility Read/Write 0: Load Govern Sets the speed control PCC3300,
Parallel method for utility PCC3300V2
Speed 1: Droop paralleling.
Control
Method
43830 Utility Read/Write 0: Load Govern Sets the voltage PCC3300,
Parallel control method for PCC3300V2
Voltage 1: Droop utility paralleling.
Control Option of 'Load
Method Govern with Droop
Feed Forward' is no
more available.
43831 Aux101 Read/Write 0: Critical Device Selects the generator PCC3300,
Device 0 Response set reaction to a loss PCC2300,
PCCnet of a Device 0 I/O PCC3300V2
Failure 1: Non-Critical Module as critical
Response Device (Shutdown) or non-
Type Response critical (Warning).
43832 Aux101 Read/Write 0: Critical Device Selects the generator PCC3300,
Device 1 Response set reaction to a loss PCC2300,
PCCnet of a Device 1 I/O PCC3300V2
Failure 1: Non-Critical Module as critical
Response Device (Shutdown) or non-
Type Response critical (Warning).
43834 HMI113 Read/Write 0: Critical Device Selects the generator PCC3300,
Annunciator Response set reaction to a loss PCC2300,
PCCnet of an Annunciator as PCC3300V2
Failure 1: Non-Critical critical or non-critical.
Response Device Selecting Critical will
Type Response cause a shutdown
when the Annunciator
looses communication.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43836 HMI220 Read/Write 0: Critical Device Selects the generator PCC3300,
PCCnet Response set reaction to a loss PCC2300,
Failure of an HMI220 PCC3300V2
Response 1: Non-Critical Operator Panel as
Type Device critical or non-critical.
Response A critical response will
shutdown the
generator set when
PCCnet
communication is lost.
43837 HMI320 Read/Write 0: Critical Device Selects the generator PCC3300,
PCCnet Response set reaction to a loss PCC2300,
Failure of an HMI320 PCC3300V2
Response 1: Non-Critical Operator Panel as
Type Device critical or non-critical.
Response A critical response will
shutdown the
generator set when
PCCnet
communication is lost.
43839 PCCnet Read/Write Multiplier: 1 Unit: seconds Selects the time PCC3300,
Device allowed for arbitration PCC2300,
Failure Time Offset: 0 Lower Limit: 15 to occur before a PCC3300V2
Delay Size (bits): 8 Upper Limit: 250 PCCnet failure fault is
generated.
Sign: U
43840 Test With Read/Write 0: Disabled Use to choose PCC3300,
Load Enable whether a test is with PCC3300V2
1: Enabled load or without load.
43842 Commit to Read/Write 0: Utility PTC - sets point at PCC3300,
Transfer Disconnect which system commits PCC3300V2
Method to transfer to
1: Genset Start generator set.
2: No Commit
43843 Commit to Read/Write Multiplier: 1 Unit: seconds PTC - sets time PCC3300,
Transfer system will wait for PCC3300V2
Timeout Offset: 0 Lower Limit: 0 generator set when
Size (bits): 16 Upper Limit: committed to transfer.
3200
Sign: U
43844 Commit to Read Only Multiplier: 0.05 Unit: sec PTC - remaining time PCC3300,
Transfer system to wait for PCC3300V2
Timer Offset: 0 Lower Limit: generator set when
Size (bits): 16 Upper Limit: committed to transfer.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43845 Modbus Read/Write Multiplier: 1 Unit: seconds Time delay before the PCC3300,
Failure Time control activates the PCC2300,
Delay Offset: 0 Lower Limit: 0 modbus failure fault PCC3300V2
Size (bits): 16 Upper Limit: 10 after the master is
sensed as no longer
Sign: U present.
43846 Modbus Read/Write 0: Do Nothing When set to Reset PCC3300,
Communicati Commands will reset PCC2300,
ons Lost 1: Reset the modbus control PCC3300V2
Response Commands logicals to an inactive
Method state when Modbus
communications are
lost.
43847 Modbus Read/Write 0: Do Nothing Resets all modbus PCC3300,
Clear counters, including PCC2300,
Counters 1: Clear J14 if applicable. PCC3300V2
Counters
43848 Controlled Read/Write Multiplier: 1 Unit: seconds Maximum ramp unload PCC3300,
Shutdown time during a PCC3300V2
Max Ramp Offset: 0 Lower Limit: 0 shutdown with
Unload Time Size (bits): 16 Upper Limit: 300 cooldown
Sign: U
43849 Genset Read/Write Multiplier: 1 Unit: kVAR Sets the generator set PCC3300,
kVAR load govern kVAR PCC3300V2
Setpoint Offset: 0 Lower Limit: base load internal
-20000 operating setpoint in
Size (bits): 16 Upper Limit: units of kVAR.
20000 Requires that Load
Govern kVAR Setpoint
Sign: S Source = Internal and
Load Govern kVAR
Method = Generator
set kVAR.
43850 Genset Read/Write Multiplier: 0.01 Unit: % Sets the generator set PCC3300,
kVAR load govern kVAR PCC3300V2
Setpoint Offset: 0 Lower Limit: -60 base load internal
Percent Size (bits): 16 Upper Limit: 60 operating setpoint
in % of standby kVA
Sign: S rating. Requires that
Load Govern kVAR
Setpoint Source =
Internal and Load
Govern kVAR Method
= Generator set kVAR.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43851 Genset kW Read/Write Multiplier: 1 Unit: kW Sets the generator set PCC3300,
Setpoint load govern kW base PCC3300V2
Offset: 0 Lower Limit: 0 load internal operating
Size (bits): 16 Upper Limit: setpoint in units of kW.
20000 Requires that Load
Govern kW Setpoint
Sign: S Source = Internal and
Load Govern kW
Method = Generator
set kW.
43852 Genset kW Read/Write Multiplier: 0.01 Unit: % Sets the generator set PCC3300,
Setpoint load govern kW base PCC3300V2
Percent Offset: 0 Lower Limit: 0 load internal operating
Size (bits): 16 Upper Limit: 100 setpoint in % of
standby rating.
Sign: S Requires that Load
Govern kW Setpoint
Source = Internal and
Load Govern kW
Method = Generator
set kW.
43853 Genset Read/Write Multiplier: 0.01 Unit: PF "Sets the load govern PCC3300,
Power Factor setpoint for generator PCC3300V2
Setpoint Offset: 0 Lower Limit: -1 set PF control.
Size (bits): 8 Upper Limit: 1 Requires that Load
Govern kVAR Setpoint
Sign: S Source = Internal and
Load Govern kVAR
Method = Generator
set PF. PF can be set
from –0.8 to –1.0 and
from 0.7 to 1.0"
43854 Load Read/Write 0: Inactive Modbus input for PCC3300,
Demand activating load PCC3300V2
Stop 1: Active demand stop on the
(Modbus) generator set
43855 Load Govern Read/Write 0: Genset kVAR Use to select how PCC3300,
kVAR generator set kVAR PCC3300V2
Method 1: Genset Power output will be
Factor controlled when
2: Utility kVAR paralleled to utility.
3: Utility Power
Factor
43856 Load Govern Read/Write Multiplier: 1 Unit: seconds Sets load govern PCC3300,
kVAR Ramp kVAR ramp load rate PCC3300V2
Load Time Offset: 0 Lower Limit: 0 = Generator set
Size (bits): 16 Upper Limit: 900 Standby kVA * 0.6/
this time.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43857 Load Govern Read/Write Multiplier: 1 Unit: seconds Sets load govern PCC3300,
kVAR Ramp kVAR ramp unload PCC3300V2
Unload Time Offset: 0 Lower Limit: 0 rate = Generator set
Size (bits): 16 Upper Limit: 900 Standby KVA * 0.6/
this time.
Sign: U
43858 Utility Read/Write 0: After Transfer PTC - point in time at PCC3300,
Breaker Delay which system opens PCC3300V2
Opening utility breaker
Point 1: Upon Utility
Failure
43859 Load Govern Read/Write Multiplier: 1 Unit: seconds Sets load govern kW PCC3300,
kW Ramp ramp load rate = PCC3300V2
Load Time Offset: 0 Lower Limit: 0 Generator set Standby
Size (bits): 16 Upper Limit: 900 kW rating/ this time.
Sign: U
43860 Load Govern Read/Write Multiplier: 1 Unit: seconds Sets load govern kW PCC3300,
kW Ramp ramp unload rate = PCC3300V2
Unload Time Offset: 0 Lower Limit: 0 Generator set Standby
Size (bits): 16 Upper Limit: 900 kW rating/ this time.
Sign: U
43862 Slip Read/Write Multiplier: 0.001 Unit: Hz Sets the synchronizer PCC3300,
Frequency slip frequency. PCC3300V2
Offset: 0 Lower Limit: -3 Requires that Sync
Size (bits): 16 Upper Limit: 3 Speed Control Method
= Slip Frequency.
Sign: S
43863 Utility kVAR Read/Write Multiplier: 1 Unit: kVAR Sets the utility kVAR PCC3300,
Setpoint peak shave internal PCC3300V2
Offset: 0 Lower Limit: operating setpoint in
-20000 units of kVAR.
Size (bits): 16 Upper Limit: Requires that Load
20000 Govern kVAR Setpoint
Source = Internal and
Sign: S Load Govern kVAR
Method = Utility kVAR
43864 Utility kVAR Read/Write Multiplier: 0.01 Unit: % Sets the utility kVAR PCC3300,
Setpoint peak shave internal PCC3300V2
Percent Offset: 0 Lower Limit: -320 operating setpoint
Size (bits): 16 Upper Limit: 320 in % of generator set
standby kVA rating.
Sign: S Requires that Load
Govern kVAR Setpoint
Source = Internal and
Load Govern kVAR
Method = Utility kVAR.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43865 Utility kW Read/Write Multiplier: 1 Unit: kW Sets the utility kW PCC3300,
Constraint minimum load level for PCC3300V2
Offset: 0 Lower Limit: constrained base load
-20000 mode of operation.
Size (bits): 16 Upper Limit: Requires that Load
20000 Govern kW Setpoint
Source = Internal and
Sign: S Load Govern kW
Method = Generator
set kW w/Utility
Constraint.
43866 Utility kW Read/Write Multiplier: 0.01 Unit: % Sets utility kW PCC3300,
Constraint minimum load level for PCC3300V2
Percent Offset: 0 Lower Limit: -320 constrained base load
Size (bits): 16 Upper Limit: 320 mode in % of
generator set standby
Sign: S rating. Requires that
Load Govern kW
Setpoint Source =
Internal and Load
Govern kW Method =
Generator set kW
w/Utility Constraint.
43867 Utility kW Read/Write Multiplier: 1 Unit: kW Sets the utility kW PCC3300,
Setpoint peak shave internal PCC3300V2
Offset: 0 Lower Limit: operating setpoint in
-20000 units of kW. Requires
Size (bits): 16 Upper Limit: that Load Govern kW
20000 Setpoint Source =
Internal and Load
Sign: S Govern kW Method =
Utility kW.
43868 Utility kW Read/Write Multiplier: 0.01 Unit: % Sets the utility kW PCC3300,
Setpoint peak shave internal PCC3300V2
Percent Offset: 0 Lower Limit: -320 operating setpoint
Size (bits): 16 Upper Limit: 320 in % of generator set
standby rating.
Sign: S Requires that Load
Govern kW Setpoint
Source = Internal and
Load Govern kW
Method = Utility kW.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43869 Utility Power Read/Write Multiplier: 0.01 Unit: PF Sets the internal PCC3300,
Factor setpoint for utility PCC3300V2
Setpoint Offset: 0 Lower Limit: 0.7 power factor control
Size (bits): 8 Upper Limit: 1 mode when paralleled
to utility. Requires that
Sign: S Load Govern kVAR
Setpoint Source =
Internal and Load
Govern kVAR Method
= Utility Power Factor.
43870 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 2 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43871 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 4 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43872 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 5 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43873 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 6 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43874 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 7 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43875 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 1 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43876 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 2 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43877 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 3 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43878 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 4 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43879 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 5 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43880 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 6 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43881 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 7 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43882 Aux101 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 8 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43883 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 10 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43884 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 11 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43885 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 12 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43886 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 13 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43887 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 14 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43888 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 15 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43889 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 16 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43890 Aux102 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 9 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43891 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 10 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
TABLE 42.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43892 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 11 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43893 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 12 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43894 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 13 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43895 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 14 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43896 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 15 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43897 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 16 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43898 Aux102 1 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 9 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43900 HMI113 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 1 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43901 HMI113 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 2 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43902 HMI113 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 3 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43903 HMI113 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 4 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43911 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 3 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43912 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 1 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43913 Aux101 0 Read/Write Multiplier: 1 Unit: Parameter to allow for PCC3300,
Output 8 the entry of the PCC2300,
Fault/Event Offset: 0 Lower Limit: 0 fault/event code which PCC3300V2
Size (bits): 16 Upper Limit: will turn the output
65530 relay on and off.
Sign: U
43914 Transfer/Retr Read/Write 0: Inactive Override switch input PCC3300,
ansfer status from Modbus. PCC3300V2
Override 1: Active
Switch
(Modbus)
43915 Extended Read/Write 0: Disabled Use to enable the PCC3300,
Parallel extended paralleling PCC3300V2
Enable 1: Enabled mode of PTC.
43916 V/Hz Knee Read Only Multiplier: 0.1 Unit: Hz The voltage will roll off PCC2300,
Frequency (decrease) PCC3300,
50Hz Offset: 0 Lower Limit: 0 proportionally to the PCC3300V2
Size (bits): 16 Upper Limit: 10 V/Hz setup, once the
frequency drops below
Sign: U the set point in the
V/Hz Knee Frequency.
This allows the
generator set to
recover faster when
the frequency drops.
This is for 50Hz
frequency.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43917 V/Hz Knee Read Only Multiplier: 0.1 Unit: Hz The voltage will roll off PCC2300,
Frequency (decrease) PCC3300,
60Hz Offset: 0 Lower Limit: 0 proportionally to the PCC3300V2
Size (bits): 16 Upper Limit: 10 V/Hz setup, once the
frequency drops below
Sign: U the set point in the
V/Hz Knee Frequency.
This allows the
generator set to
recover faster when
the frequency drops.
This is for 60Hz
frequency.
43918 V/Hz Rolloff Read Only Multiplier: 0.1 Unit: % / Hz The amount of voltage PCC3300,
Slope 50Hz roll off when the PCC2300,
Offset: 0 Lower Limit: 0 frequency is below the PCC3300V2
Size (bits): 16 Upper Limit: 20 knee frequency.
Sign: U
43919 V/Hz Rolloff Read Only Multiplier: 0.1 Unit: % / Hz The amount of voltage PCC3300,
Slope 60Hz roll off when the PCC2300,
Offset: 0 Lower Limit: 0 frequency is below the PCC3300V2
Size (bits): 16 Upper Limit: 20 knee frequency.
Sign: U
43920 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43921 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43922 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43923 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43924 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43925 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43926 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43927 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43928 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43929 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43930 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43931 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43932 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43933 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43934 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43935 Genset Read/Write Multiplier: 1 Unit: Name for the PCC3300,
Source generator set source. PCC2300,
Name Offset: 0 Lower Limit: PCC3300V2
Size (bits): 136 Upper Limit:
Sign: C
43952 Speed/Frequ Read/Write Multiplier: 0.1 Unit: seconds Sets the delay time for PCC3300,
ency Delay generating the PCC2300,
Offset: 0 Lower Limit: 0.5 Speed/Frequency PCC3300V2
Size (bits): 16 Upper Limit: 10 mismatch fault.
Sign: U
43953 Speed/Frequ Read/Write Multiplier: 0.1 Unit: Hz Sets the threshold for PCC3300,
ency generating the PCC2300,
Threshold Offset: 0 Lower Limit: 0.5 Speed/Frequency PCC3300V2
Size (bits): 16 Upper Limit: 20 mismatch fault.
Sign: U
43955 Genset Idle Read Only 0: Disabled Enables or disables PCC3300,
Enable idling of generator set PCC2300,
1: Enabled with external governor. PCC3300V2
43959 Utility Read/Write Multiplier: 1 Unit: kW Sets threshold at PCC3300,
Unloaded which utility source is PCC3300V2
Level Offset: 0 Lower Limit: considered as
-32768 unloaded.
Size (bits): 16 Upper Limit:
32762
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43960 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43961 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43962 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43963 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43964 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43965 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43966 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43967 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43968 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43969 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43970 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43971 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43972 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43973 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43974 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43975 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43976 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43977 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43978 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43979 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
1 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43980 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43981 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43982 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43983 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43984 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43985 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43986 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43987 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43988 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43989 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43990 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43991 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
43992 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43993 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43994 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43995 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43996 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43997 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43998 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
43999 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
2 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
44001 Secondary Read Only 0: Disabled "Shows if secondary PCC3300,
Starter starter is configured PCC3300V2
Configuration 1: Enabled for the generator set"
Enabled
44002 Starter in Read Only 0: Primary "Shows which starter PCC3300,
Use is currently in use by PCC3300V2
1: Secondary the generator set"
44003 Secondary Read Only 0: Inactive "Indicates if the PCC3300,
Starter secondary starter is PCC3300V2
Command 1: Active Inactive or Active"
44304 Cycle / Cont Read Only 0: Cycle "Selects whether to PCC3300,
Crank Select use continuous PCC3300V2
(Secondary) 1: Continuous cranking or cycle
cranking when
attempting to start
engine with secondary
starter"
44305 Cycle Crank Read/Write Multiplier: 1 Unit: seconds "Sets the maximum PCC3300,
Engage Time amount of time to PCC3300V2
(Secondary) Offset: 0 Lower Limit: 2 engage the secondary
Size (bits): 16 Upper Limit: 20 starter during a single
crank attempt when
Sign: U using the cycle
cranking method"
44306 Continuous Read/Write Multiplier: 1 Unit: seconds "Sets the maximum PCC3300,
Crank amount of time to PCC3300V2
Engage Time Offset: 0 Lower Limit: 40 engage the secondary
(Secondary) Size (bits): 16 Upper Limit: 100 starter when using the
continuous cranking
Sign: U method"
44307 Crank Read/Write Multiplier: 1 Unit: "Sets the maximum PCC3300,
Attempts number of times to PCC3300V2
(Secondary) Offset: 0 Lower Limit: 1 engage the starter
Size (bits): 16 Upper Limit: 7 when attempting to
start engine in cycle
Sign: U cranking method using
secondary starter"
44308 Cycle Crank Read/Write Multiplier: 1 Unit: seconds "Sets the amount of PCC3300,
Rest Time time to wait between PCC3300V2
(Secondary) Offset: 0 Lower Limit: 7 crank attempts using
Size (bits): 16 Upper Limit: 40 secondary starter in
case of cyclic crank"
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
44309 Preferred Read/Write 0: Use Primary "Lets you choose the PCC3300,
Starter at starter to be used by PCC3300V2
Critical 1: Use generator set in case
Battery Secondary of primary starter
battery becoming low
or weak."
45999 Unrecognize Read Only 0: All Pairs Indicates whether or PCC3300,
d SPN/FMI Recognized not all pairs in current PCC2300,
Status DM1 are recognized. PCC3300V2
1: Pair Not
Recognized
46000 Genset Read Only 0: L1-L2-L3 Generator set phase PCC3300,
Phase rotation PCC2300,
Rotation 1: L1-L3-L2 PCC3300V2
2: Not Available
46001 Utility Phase Read Only 0: L1-L2-L3 Utility phase rotation PCC3300,
Rotation PCC3300V2
1: L1-L3-L2
2: Not Available
46002 Genset Bus Read Only 0: L1-L2-L3 Generator set bus PCC3300,
Phase phase rotation PCC3300V2
Rotation 1: L1-L3-L2
2: Not Available
46003 Base Speed Read Only Multiplier: 0.0625 Unit: rpm Provides a point to PCC3300,
monitor the base PCC2300,
Offset: 0 Lower Limit: speed. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
46004 Base Speed Read Only Multiplier: 0.0625 Unit: rpm Provides a point to PCC3300,
monitor the base PCC2300,
Offset: 0 Lower Limit: speed. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
46005 Final Speed Read Only Multiplier: 0.0625 Unit: rpm Provides a point to PCC3300,
Reference monitor the final speed PCC2300,
Offset: 0 Lower Limit: reference. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
46006 Final Speed Read Only Multiplier: 0.0625 Unit: rpm Provides a point to PCC3300,
Reference monitor the final speed PCC2300,
Offset: 0 Lower Limit: reference. PCC3300V2
Size (bits): 32 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46008 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
1 Exhaust Port 1 PCC2300,
Temperature Offset: 0 Lower Limit: -459 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46009 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
2 Exhaust Port 2 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46010 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
3 Exhaust Port 3 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46011 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
4 Exhaust Port 4 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46012 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
5 Exhaust Port 5 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46013 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
6 Exhaust Port 6 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46014 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
7 Exhaust Port 7 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46015 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
8 Exhaust Port 8 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46016 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
9 Exhaust Port 9 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46017 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
10 Exhaust Port 10 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46018 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
11 Exhaust Port 11 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46019 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
12 Exhaust Port 12 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46020 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
13 Exhaust Port 13 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46021 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
14 Exhaust Port 14 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46022 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
15 Exhaust Port 15 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46023 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
16 Exhaust Port 16 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46024 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
17 Exhaust Port 17 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46025 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
18 Exhaust Port 18 PCC2300,
Temperature Offset: 0 Lower Limit: -460 Temperature PCC3300V2
Size (bits): 16 Upper Limit:
3155
Sign: S
46026 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
19 Exhaust Port 19 PCC2300,
Temperature Offset: 0 Lower Limit: Temperature PCC3300V2
–460
Size (bits): 16 Upper Limit:
3155
Sign: S
46027 Exhaust Port Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
20 Exhaust Port 20 PCC2300,
Temperature Offset: 0 Lower Limit: Temperature PCC3300V2
–460
Size (bits): 16 Upper Limit:
3155
Sign: S
46028 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 1 cylinder 1 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46029 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 2 cylinder 2 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46030 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 3 cylinder 3 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46031 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 4 cylinder 4 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46032 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 5 cylinder 5 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46033 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 6 cylinder 6 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46034 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 7 cylinder 7 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46035 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 8 cylinder 8 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46036 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 9 cylinder 9 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46037 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 10 cylinder 10 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46038 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 11 cylinder 11 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46039 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 12 cylinder 12 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46040 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 13 cylinder 13 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46041 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 14 cylinder 14 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46042 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 15 cylinder 15 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46043 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 16 cylinder 16 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46044 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 17 cylinder 17 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46045 Knock Level Read Only Multiplier: 1 Unit: % Knock Level for PCC3300,
Cylinder 18 cylinder 18 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 8 Upper Limit:
Sign: U
46048 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 1 Cylinder 1 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46049 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 2 Cylinder 2 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46050 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 3 Cylinder 3 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46051 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 4 Cylinder 4 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46052 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 5 Cylinder 5 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46053 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 6 Cylinder 6 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46054 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 7 Cylinder 7 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46055 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 8 Cylinder 8 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46056 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 9 Cylinder 9 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46057 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 10 Cylinder 10 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46058 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 11 Cylinder 11 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46059 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 12 Cylinder 12 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46060 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 13 Cylinder 13 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46061 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 14 Cylinder 14 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46062 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 15 Cylinder 15 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46063 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 16 Cylinder 16 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46064 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 17 Cylinder 17 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46065 Knock Count Read Only Multiplier: 1 Unit: Knock count value for PCC3300,
Cyl 18 Cylinder 18 PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65530
Sign: U
46068 Spark Timing Read Only Multiplier: 0.1 Unit: Degres Spark timing degrees PCC3300,
Cyl 1 for cylinder 1 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46069 Spark Timing Read Only Multiplier: 0.1 Unit: Degres Spark timing degrees PCC3300,
Cyl 2 for cylinder 2 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46070 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 3 for cylinder 3 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46071 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 4 for cylinder 4 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46072 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 5 for cylinder 5 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46073 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 6 for cylinder 6 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46074 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 7 for cylinder 7 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46075 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 8 for cylinder 8 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46076 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 9 for cylinder 9 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46077 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 10 for cylinder 10 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46078 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 11 for cylinder 11 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46079 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 12 for cylinder 12 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46080 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 13 for cylinder 13 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46081 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 14 for cylinder 14 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46082 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 15 for cylinder 15 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46083 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 16 for cylinder 16 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46084 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 17 for cylinder 17 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
46085 Spark Timing Read Only Multiplier: 0.1 Unit: Degrees Spark timing degrees PCC3300,
Cyl 18 for cylinder 18 PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: S
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46088 Internal Read Only Multiplier: 0.1 Unit: degF Temperature of the PCC3300,
SSM558 1 engine electronic PCC3300V2
Temperature Offset: 0 Lower Limit: control unit SSM558 1
Size (bits): 16 Upper Limit:
Sign: S
46089 Internal Read Only Multiplier: 0.1 Unit: degF Temperature of the PCC3300,
SSM558 2 engine electronic PCC3300V2
Temperature Offset: 0 Lower Limit: control unit SSM558 2
Size (bits): 16 Upper Limit:
Sign: S
TABLE 43.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46090 Internal Read Only Multiplier: 0.1 Unit: degF Temperature of the PCC3300,
MCM700 engine electronic PCC3300V2
Temperature Offset: 0 Lower Limit: control unit MCM700
Size (bits): 16 Upper Limit:
Sign: S
46091 Derate Read Only 0: NO Derate authorisation PCC3300,
Authorization request from PCC3300V2
1: YES customer.
2: Reserved
3: N/A
4: Network
Failure
46093 Ventilator Read Only 0: OFF Vent Fan status PCC3300,
Fan Status monitor point. PCC3300V2
1: ON
2: TRIPPED
3: N/A
46096 GIB Isolator Read Only 0: Close GIB Isolator Open PCC3300,
Open monitor point. PCC3300V2
(Aux101) 1: Open
2: Reserved
3: N/A
4: Network
Failure
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46097 Alternator Read Only 0: OFF Alternator Heater PCC3300,
Heater status monitor point. PCC3300V2
Status 1: ON
2: TRIPPED
3: N/A
46101 Start Inhibit Read Only 0: Inactive Start Inhibit No1 PCC3300,
No1 monitor point. PCC3300V2
(Aux101) 1: Active
2: Reserved
3: Not Available
4: Network
Failure
46102 Start Inhibit Read Only 0: Inactive Start Inhibit No2 PCC3300,
No2 monitor point. PCC3300V2
(Aux101) 1: Active
2: Reserved
3: Not Available
4: Network
Failure
46103 Start Inhibit Read Only 0: Inactive Start Inhibit No3 PCC3300,
No3 monitor point. PCC3300V2
(Aux101) 1: Active
2: Reserved
3: Not Available
4: Network
Failure
46104 DC PSU Read Only 0: No Engine PSU Not PCC3300,
Unavailable Available monitor PCC3300V2
(Aux101) 1: Yes point.
2: Reserved
3: N/A
4: Network
Failure
46105 Ventilator Read Only 0: No Ventilator Fan Trip PCC3300,
Fan Trip monitor point. PCC3300V2
(Aux101) 1: Yes
2: Reserved
3: N/A
4: Network
Failure
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46106 Aux101-3 Read Only Multiplier: 0.01 Unit: Software version of PCC3300,
Software the firmware for the PCC3300V2
Version Offset: 0 Lower Limit: Aux101-3
Size (bits): 16 Upper Limit:
Sign: U
46107 Aux101-4 Read Only Multiplier: 0.01 Unit: Software version of PCC3300,
Software the firmware for the PCC3300V2
Version Offset: 0 Lower Limit: Aux101-4
Size (bits): 16 Upper Limit:
Sign: U
46108 Aux101-5 Read Only Multiplier: 0.01 Unit: Software version of PCC3300,
Software the firmware for the PCC3300V2
Version Offset: 0 Lower Limit: Aux101-5
Size (bits): 16 Upper Limit:
Sign: U
46113 Downstream Read Only 0: Open The result of the FSO PCC3300,
Valve driver output PCC3300V2
Command 1: Closed command logic for fuel
Status 2: Reserved shutoff valve 1
3: N/A
46117 Engine Oil Read Only 0: OFF Engine Oil pre heater PCC3300,
PreHeater command status PCC3300V2
Ctrl Status 1: ON
2: Reserved
3: N/A
4: Network
Failure
46120 Engine Read Only 0: OFF Engine coolant PCC3300,
Coolant circulating pump PCC3300V2
Pump Ctrl 1: ON status
Status 2: Reserved
3: N/A
4: Network
Failure
46124 Coolant Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Pressure Coolant Pressure. PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46125 Coolant 2 Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
Pressure Coolant 2 Pressure. PCC3300V2
Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit: 145
Sign: U
46127 Coolant 2 Read Only Multiplier: 0.1 Unit: degF Monitor point for the PCC3300,
Temperature Coolant 2 PCC3300V2
Offset: 0 Lower Limit: Temperature
Size (bits): 16 Upper Limit:
Sign: S
46128 Compressor Read Only Multiplier: 0.1 Unit: % Engine turbocharger PCC3300,
Bypass compressor bypass PCC3300V2
Position Offset: 0 Lower Limit: actuator position
Size (bits): 16 Upper Limit:
Sign: U
46130 Oil Priming Read Only 0: OFF Status for the priming PCC3300,
Pump pump (ON or OFF) PCC3300V2
Control 1: ON
Status 2: Reserved
3: N/A
4: Network
Failure
46131 Oil Priming Read Only 0: Low Status of the engine PCC3300,
State before start (Pre- PCC3300V2
1: Optimum Lubed or Not)
2: Reserved
3: N/A
4: Network
Failure
46133 Coolant Pre- Read Only 0: Cold Status of the engine PCC3300,
Heated State coolant before start PCC3300V2
1: Heated (Pre-Heated or Not)
2: Reserved
3: N/A
46135 Intake Read Only Multiplier: 0.1 Unit: psi Intake Manifold PCC3300,
Manifold Pressure 1 PCC3300V2
Pressure 1 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46136 Compressor Read Only Multiplier: 0.1 Unit: kPa Absolute Pressure at PCC3300,
Outlet the outlet of the PCC3300V2
Pressure Offset: 0 Lower Limit: compressor.
Size (bits): 16 Upper Limit:
Sign: U
46137 Turbocharger Read Only Multiplier: 0.1 Unit: psi Monitor point for the PCC3300,
1 Boost Turbocharger 1 Boost PCC3300V2
Pressure Offset: 0 Lower Limit: Pressure
Size (bits): 16 Upper Limit:
Sign: U
46139 Fuel Valve 1 Read Only Multiplier: 0.1 Unit: psi Absolute Pressure of PCC3300,
Inlet Gas on the inlet side PCC3300V2
Absolute Offset: 0 Lower Limit: of the first system
Pressure Size (bits): 16 Upper Limit: control valve
Sign: U
46140 Fuel Valve 1 Read Only Multiplier: 0.1 Unit: psi Absolute Pressure of PCC3300,
Outlet Gas on the outlet side PCC3300V2
Absolute Offset: 0 Lower Limit: of the first system
Pressure Size (bits): 16 Upper Limit: control valve
Sign: U
46141 Fuel Valve 1 Read Only Multiplier: 0.1 Unit: % PCC3300,
Position PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46142 Fuel Valve 2 Read Only Multiplier: 0.1 Unit: psi Absolute Pressure of PCC3300,
Inlet Gas on the inlet side PCC3300V2
Absolute Offset: 0 Lower Limit: of the second system
Pressure Size (bits): 16 Upper Limit: control valve
Sign: U
46143 Fuel Valve 2 Read Only Multiplier: 0.1 Unit: psi Absolute Pressure of PCC3300,
Outlet Gas on the outlet side PCC3300V2
Absolute Offset: 0 Lower Limit: of the second system
Pressure Size (bits): 16 Upper Limit: control valve
Sign: U
46144 Fuel Valve 2 Read Only Multiplier: 0.1 Unit: % PCC3300,
Position PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46145 Gas Mass Read Only Multiplier: 0.1 Unit: Pounds per Gas Mass Flow value PCC3300,
Flow hour of the engine. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
46146 Gas Mass Read Only Multiplier: 0.1 Unit: Pounds per Gas Mass Flow value PCC3300,
Flow hour of the engine. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
46147 Throttle 1 Read Only Multiplier: 0.1 Unit: % Position of the throttle PCC3300,
Position 1. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46148 Throttle 2 Read Only Multiplier: 0.1 Unit: % Position of the throttle PCC3300,
Position 2. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46155 MCM700 Read Only Multiplier: 0.1 Unit: Vdc Engine Control Module PCC3300,
Battery Battery Voltage. PCC3300V2
Voltage Offset: 0 Lower Limit: 0
Size (bits): 16 Upper Limit:
65535
Sign: U
46161 SSM558 1 Read Only Multiplier: 0.1 Unit: Vdc SSM558 1 Engine PCC3300,
Isolated Control Module PCC3300V2
Battery Offset: 0 Lower Limit: 0 Isolated Battery
Voltage Size (bits): 16 Upper Limit: Voltage.
65535
Sign: U
46163 SSM558 2 Read Only Multiplier: 0.1 Unit: Vdc SSM558 2 Engine PCC3300,
Isolated Control Module PCC3300V2
Battery Offset: 0 Lower Limit: 0 Isolated Battery
Voltage Size (bits): 16 Upper Limit: Voltage.
65535
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46164 Intake Read Only Multiplier: 0.1 Unit: psi Intake Manifold PCC3300,
Manifold Pressure 2 PCC3300V2
Pressure 2 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46166 Exhaust Read Only Multiplier: 0.1 Unit: psi Monitor point for PCC3300,
Back exhaust back pressure PCC3300V2
Pressure Offset: 0 Lower Limit: value
Size (bits): 16 Upper Limit:
Sign: U
46168 Air Filter Read Only Multiplier: 0.1 Unit: psi Monitor point for air PCC3300,
Differential filter differential PCC3300V2
Pressure Offset: 0 Lower Limit: pressure value
Size (bits): 16 Upper Limit:
Sign: S
46170 Gas Mass Read Only Multiplier: 0.1 Unit: Pounds per Gas Mass Flow 2 PCC3300,
Flow 2 hour value of the engine. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
46171 Gas Mass Read Only Multiplier: 0.1 Unit: Pounds per Gas Mass Flow 2 PCC3300,
Flow 2 hour value of the engine. PCC3300V2
Offset: 0 Lower Limit:
Size (bits): 32 Upper Limit:
Sign: U
46172 Start Inhibit Read Only 0: Inactive Start Inhibit No1 Op PCC3300,
No1 Op monitor point. PCC3300V2
1: Active
2: Reserved
3: Not Available
4: Network
Failure
46173 Start Inhibit Read Only 0: Inactive Start Inhibit No2 Op PCC3300,
No2 Op monitor point. PCC3300V2
1: Active
2: Reserved
3: Not Available
4: Network
Failure
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46174 Start Inhibit Read Only 0: Inactive Start Inhibit No3 Op PCC3300,
No3 Op monitor point. PCC3300V2
1: Active
2: Reserved
3: Not Available
4: Network
Failure
46182 Radiator Fan Read Only 0: Inactive Radiator fan control PCC3300,
control command PCC3300V2
1: Active
46183 Ventilator Read/Write 0: Limited Vent fan control mode, PCC3300,
Fan mode limited or continuous PCC3300V2
1: Continuous
46184 Louvre Read Only 0: Inactive Louvre control PCC3300,
Control PCC3300V2
1: Active
46191 Ventilator Read Only 0: Inactive Ventilator fan control PCC3300,
Fan control command PCC3300V2
1: Active
46192 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 1 PCC3300V2
1 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46193 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 2 PCC3300V2
2 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46194 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 3 PCC3300V2
3 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46195 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 4 PCC3300V2
4 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46196 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 5 PCC3300V2
5 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46197 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 6 PCC3300V2
6 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46198 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 7 PCC3300V2
7 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46199 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 8 PCC3300V2
8 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46200 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 9 PCC3300V2
9 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46201 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 10 PCC3300V2
10 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46202 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 11 PCC3300V2
11 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46203 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 12 PCC3300V2
12 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46204 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 13 PCC3300V2
13 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46205 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 14 PCC3300V2
14 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46206 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 15 PCC3300V2
15 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46207 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 16 PCC3300V2
16 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46208 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 17 PCC3300V2
17 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46209 Engine Spark Read Only Multiplier: 1 Unit: V Spark Plug Voltage for PCC3300,
Plug Voltage Cylinder 18 PCC3300V2
18 Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46221 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46222 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46223 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46224 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46225 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46226 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46227 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46228 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46229 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
46230 ECM Code Read Only Multiplier: 1 Unit: "ECM 1 Calibration ID PCC3300,
(DM19)" PCC2300,
Offset: 0 Lower Limit: PCC3300V2
Size (bits): 88 Upper Limit:
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46288 DE/NDE Read/Write 0: Drive End Gives reference point PCC3300,
Cylinder for engine cylinder PCC3300V2
Viewpoint 1: Non-Drive End numbering
Reference 2: Reserved
3: N/A
46289 Start System Read Only 0: Not Tripped Start system trip PCC3300,
Trip (Aux monitor point. PCC3300V2
101) 1: Tripped
2: Reserved
3: N/A
4: Network
Failure
46290 Louvres Read Only 0: Open Louvres Closed PCC3300,
Closed (Aux monitor point. PCC3300V2
101) 1: Closed
2: Reserved
3: N/A
4: Network
Failure
46291 Radiator Fan Read Only 0: Not Tripped Radiator Fan Trip PCC3300,
Trip (Aux monitor point. PCC3300V2
101) 1: Tripped
2: Reserved
3: N/A
4: Network
Failure
46300 LBNG Read/Write 0: Disable Switch to enable or PCC3300,
Genset disable the gas PCC3300V2
Enable 1: Enable specific features and
parameters
46301 Aux101-3 Read/Write 0: Disable Enable the processing PCC3300,
Enable for Aux101-3 PCC3300V2
1: Enable messages
46302 Aux101-4 Read/Write 0: Disable Enable the processing PCC3300,
Enable for Aux101-4 PCC3300V2
1: Enable messages
46303 Aux101-5 Read/Write 0: Disable Enable the processing PCC3300,
Enable for Aux101-5 PCC3300V2
1: Enable messages
46304 Aux101-6 Read/Write 0: Disable Enable the processing PCC3300,
Enable for Aux101-6 PCC3300V2
1: Enable messages
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46308 Aux101-3 Read Only Multiplier: 1 Unit: Input Port PCC3300,
Input Port configuration bye for PCC3300V2
Config Offset: 0 Lower Limit: 0 the Aux101-3
Size (bits): 16 Upper Limit: 255
Sign: U
46309 Aux101-4 Read Only Multiplier: 1 Unit: Input Port PCC3300,
Input Port configuration bye for PCC3300V2
Config Offset: 0 Lower Limit: 0 the Aux101-4
Size (bits): 16 Upper Limit: 255
Sign: U
46310 Aux101-5 Read Only Multiplier: 1 Unit: Input Port PCC3300,
Input Port configuration bye for PCC3300V2
Config Offset: 0 Lower Limit: 0 the Aux101-5
Size (bits): 16 Upper Limit: 255
Sign: U
46311 Aux101-3 DI Read Only Multiplier: 1 Unit: Digital Input Port PCC3300,
Active configuration active PCC3300V2
High/Low Offset: 0 Lower Limit: 0 High or active low for
Selection Size (bits): 16 Upper Limit: 255 the Aux101-3
Sign: U
46312 Aux101-4 DI Read Only Multiplier: 1 Unit: Digital Input Port PCC3300,
Active configuration active PCC3300V2
High/Low Offset: 0 Lower Limit: 0 High or active low for
Selection Size (bits): 16 Upper Limit: 255 the Aux101-4
Sign: U
46313 Aux101-5 DI Read Only Multiplier: 1 Unit: Digital Input Port PCC3300,
Active configuration active PCC3300V2
High/Low Offset: 0 Lower Limit: 0 High or active low for
Selection Size (bits): 16 Upper Limit: 255 the Aux101-5
Sign: U
46314 Aux101-3 DI Read Only Multiplier: 1 Unit: Discrete Input PCC3300,
Config Mask configuration bit mask PCC3300V2
Offset: 0 Lower Limit: 0 for the Aux101-3
Size (bits): 16 Upper Limit: 255
Sign: U
46315 Aux101-4 DI Read Only Multiplier: 1 Unit: Discrete Input PCC3300,
Config Mask configuration bit mask PCC3300V2
Offset: 0 Lower Limit: 0 for the Aux101-4
Size (bits): 16 Upper Limit: 255
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46316 Aux101-5 DI Read Only Multiplier: 1 Unit: Discrete Input PCC3300,
Config Mask configuration bit mask PCC3300V2
Offset: 0 Lower Limit: 0 for the Aux101-5
Size (bits): 16 Upper Limit: 255
Sign: U
46323 Vehicle Read/Write 0: Disabled A trim that enables the PCC3300,
Electrical Vehicle Electrical PCC3300V2
Power 2 1: Enabled Power 2 message
PGN65165
Enable
46326 Gaseous Read/Write 0: Disabled A trim that enables the PCC3300,
Fuel Gaseous Fuel PCC3300V2
Pressure 1: Enabled Pressure message
PGN65163
Enable
46327 Fuel Read/Write 0: Disabled A trim that enables the PCC3300,
Information 3 Fuel Information 3 - PCC3300V2
- Gaseous 1: Enabled Gaseous message
PGN64930
Enable
46328 Fuel Read/Write 0: Disabled A trim that enables the PCC3300,
Information 2 Fuel Information 2 - PCC3300V2
- Gaseous 1: Enabled Gaseous message
PGN65153
Enable
46332 Inlet/Exhaust Read/Write 0: Disabled A trim that enables the PCC3300,
Conditions Inlet/Exhaust PCC3300V2
PGN65270 1: Enabled Conditions message
Enable
46333 Knock Count Read/Write 0: Disabled A trim that enables PCC3300,
1 PGN65336 Knock Count 1 PCC3300V2
Enable 1: Enabled message
46334 Knock Count Read/Write 0: Disabled A trim that enables PCC3300,
2 PGN65337 Knock Count 2 PCC3300V2
Enable 1: Enabled message
46335 Knock Count Read/Write 0: Disabled A trim that enables PCC3300,
3 PGN65338 Knock Count 3 PCC3300V2
Enable 1: Enabled message
46336 Knock Count Read/Write 0: Disabled A trim that enables PCC3300,
4 PGN65339 Knock Count 4 PCC3300V2
Enable 1: Enabled message
46337 Knock Count Read/Write 0: Disabled A trim that enables PCC3300,
5 PGN65340 Knock Count 5 PCC3300V2
Enable 1: Enabled message
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46338 Ignition Read/Write 0: Disabled A trim that enables the PCC3300,
Timing 1 Ignition Timing 1 PCC3300V2
PGN65154 1: Enabled message
Enable
46339 Ignition Read/Write 0: Disabled A trim that enables the PCC3300,
Timing 2 Ignition Timing 2 PCC3300V2
PGN65155 1: Enabled message
Enable
46340 Ignition Read/Write 0: Disabled A trim that enables the PCC3300,
Timing 3 Ignition Timing 3 PCC3300V2
PGN65156 1: Enabled message
Enable
46341 Ignition Read/Write 0: Disabled A trim that enables the PCC3300,
Timing 4 Ignition Timing 4 PCC3300V2
PGN65157 1: Enabled message
Enable
46342 Ignition Read/Write 0: Disabled A trim that enables the PCC3300,
Timing 5 Ignition Timing 5 PCC3300V2
PGN65158 1: Enabled message
Enable
46344 Start-Enable Read/Write 0: Disable Remote MODBUS PCC3300,
(MODBUS Start-Enable input. PCC3300V2
Input) 1: Enable
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46368 Modbus CRC Read Only Multiplier: 1 Unit: The number of PCC3300,
Error Count modbus CRC errors, PCC3300V2
(J14) Offset: 0 Lower Limit: for J14 only.
Size (bits): 16 Upper Limit:
Sign: U
46369 Modbus Read Only Multiplier: 1 Unit: Modbus exception PCC3300,
Exception count, for J14 only. PCC3300V2
Count (J14) Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46370 Modbus No Read Only Multiplier: 1 Unit: Modbus no response PCC3300,
Response count, for J14 only. PCC3300V2
Count (J14) Offset: 0 Lower Limit:
Size (bits): 16 Upper Limit:
Sign: U
46371 Modbus Read Only Multiplier: 1 Unit: The number of PCC3300,
Slave modbus slave PCC3300V2
Message Offset: 0 Lower Limit: messages, for J14
Count (J14) Size (bits): 16 Upper Limit: only.
Sign: U
46372 Modbus Read/Write Multiplier: 1 Unit: Sets the modbus PCC3300,
Node address for this node, PCC3300V2
Address Offset: 0 Lower Limit: 1 for J14 only.
(J14) Size (bits): 8 Upper Limit: 247
Sign: U
46373 Modbus Read/Write 0: 2400 Sets the baud rate for PCC3300,
Baud Rate modbus PCC3300V2
(J14) 1: 4800 communications, for
2: 9600 J14 only.
3: 19200
46374 Modbus Read/Write 0: Even Sets the modbus PCC3300,
Parity (J14) parity for this node, for PCC3300V2
1: Odd J14 only.
2: None
46376 Modbus Read/Write 0: 2400 Baud Sets the modbus baud PCC3300,
Baud Rate rate. PCC2300,
1: 4800 Baud PCC3300V2
2: 9600 Baud
3: 19200 Baud
4: 38400 Baud
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46377 Modbus Read/Write 0: Even Sets the modbus PCC3300,
Parity parity for this node PCC2300,
1: Odd PCC3300V2
2: None
46378 Modbus Read/Write Multiplier: 1 Unit: Sets the modbus PCC3300,
Node address for this node PCC2300,
Address Offset: 0 Lower Limit: 1 PCC3300V2
Size (bits): 8 Upper Limit: 247
Sign: U
46379 Modbus Stop Read/Write 0: 1 Sets the modbus PCC3300,
Bits number of stop bits for PCC2300,
1: 2 this node Limited to 1 PCC3300V2
bit if parity = Odd or
Even
46380 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46381 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46382 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46383 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46384 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46385 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46386 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46387 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46388 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46389 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46390 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46391 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46392 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46393 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46394 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46395 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46396 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46397 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46398 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46399 HMI113 Fault Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
3 Text text string to enter the PCC2300,
Offset: 0 Lower Limit: configurable fault text PCC3300V2
Size (bits): 168 Upper Limit: for this fault.
Sign: C
46600 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46601 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46602 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46603 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46604 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46605 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46606 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46607 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46608 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46609 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46610 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46611 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46612 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46613 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46614 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46615 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46616 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46617 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46618 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46619 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46620 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46621 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46622 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46623 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46624 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46625 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
TABLE 44.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46626 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46627 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46628 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46629 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46630 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46631 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46632 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46633 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46634 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46635 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46636 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46637 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46638 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46639 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46640 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46641 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46642 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46643 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46644 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46645 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46646 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46647 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46648 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46649 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46650 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46651 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46652 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46653 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46654 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46655 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46656 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46657 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46658 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46659 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 1 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46660 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46661 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46662 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46663 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46664 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46665 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46666 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46667 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46668 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46669 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46670 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46671 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46672 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46673 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46674 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46675 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46676 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46677 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46678 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46679 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 2 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46800 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46801 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46802 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46803 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46804 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46805 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46806 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46807 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46808 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46809 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46810 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46811 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46812 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46813 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46814 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46815 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46816 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46817 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46818 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46819 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46820 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46821 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46822 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46823 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46824 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46825 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46826 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46827 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46828 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46829 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46830 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46831 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46832 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46833 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46834 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46835 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46836 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46837 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46838 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46839 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46840 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46841 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46842 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46843 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46844 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46845 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46846 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46847 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46848 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46849 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46850 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46851 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46852 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46853 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46854 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46855 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46856 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46857 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46858 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46859 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46860 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46861 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46862 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46863 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46864 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46865 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46866 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46867 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46868 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46869 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46870 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46871 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46872 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46873 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46874 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46875 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46876 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46877 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46878 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46879 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46880 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46881 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46882 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46883 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46884 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46885 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46886 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46887 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46888 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46889 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46890 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46891 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46892 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46893 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46894 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46895 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46896 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46897 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46898 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46899 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 3 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46900 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46901 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46902 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46903 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46904 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46905 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46906 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46907 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46908 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46909 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46910 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46911 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46912 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46913 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46914 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46915 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46916 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46917 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
TABLE 45.
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46918 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46919 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 4 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46920 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46921 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46922 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46923 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46924 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46925 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46926 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46927 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46928 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46929 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46930 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46931 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46932 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46933 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46934 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46935 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46936 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46937 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46938 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46939 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 5 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46940 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46941 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46942 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46943 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46944 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46945 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46946 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46947 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46948 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46949 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46950 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46951 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46952 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46953 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46954 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46955 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46956 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46957 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46958 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46959 Aux101 1 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 6 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46960 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46961 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46962 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46963 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46964 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46965 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46966 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46967 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46968 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46969 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46970 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46971 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46972 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46973 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46974 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46975 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46976 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46977 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46978 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46979 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 7 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46980 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46981 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46982 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46983 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46984 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46985 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46986 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46987 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46988 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46989 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46990 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46991 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46992 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46993 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46994 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46995 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46996 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46997 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
46998 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
46999 Aux101 0 Read/Write Multiplier: 1 Unit: Twenty (20) character PCC3300,
Input 8 Fault text field to allow for PCC2300,
Text Offset: 0 Lower Limit: the entry of the PCC3300V2
Size (bits): 168 Upper Limit: displayed configurable
fault text.
Sign: C
47002 GK1 (60Hz) Read Only Multiplier: 1 Unit: The governor 60Hz K1 PCC3300,
gain adjust. MODBUS PCC3300V2
Offset: 0 Lower Limit: 0 Access: Read Only
Size (bits): 16 Upper Limit:
65530
Sign: U
47003 GK2 (60Hz) Read Only Multiplier: 1 Unit: The governor 60Hz PCC3300,
integral gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS Access:
Size (bits): 16 Upper Limit: Read Only
65530
Sign: U
47004 GK3 (60Hz) Read Only Multiplier: 1 Unit: The governor 60Hz K3 PCC3300,
gain adjust. MODBUS PCC3300V2
Offset: 0 Lower Limit: 0 Access: Read Only
Size (bits): 16 Upper Limit:
65530
Sign: U
47005 Governor Read Only Multiplier: Unit: The governor 60Hz PCC3300,
Damping 1.52587890625E damping adjust. PCC3300V2
Effect (60Hz) -05 MODBUS
Access:Read Only
Offset: 0 Lower Limit: 0.6
Size (bits): 16 Upper Limit: 0.95
Sign: U
47006 GK1 (50Hz) Read Only Multiplier: 1 Unit: The governor 50Hz K1 PCC3300,
gain adjust. MODBUS PCC3300V2
Offset: 0 Lower Limit: 0 Access: Read Only
Size (bits): 16 Upper Limit:
65530
Sign: U
47007 GK2 (50Hz) Read Only Multiplier: 1 Unit: The governor 50Hz PCC3300,
integral gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS Access:
Size (bits): 16 Upper Limit: Read Only
65530
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47008 GK3 (50Hz) Read Only Multiplier: 1 Unit: The governor 50Hz K3 PCC3300,
gain adjust. MODBUS PCC3300V2
Offset: 0 Lower Limit: 0 Access: Read Only
Size (bits): 16 Upper Limit:
65530
Sign: U
47009 Governor Read Only Multiplier: Unit: The governor 50Hz PCC3300,
Damping 1.52587890625E damping adjust. PCC3300V2
Effect (50Hz) -05 MODBUS
Access:Read Only
Offset: 0 Lower Limit: 0.6
Size (bits): 16 Upper Limit: 0.95
Sign: U
47010 GK1(Idle) Read Only Multiplier: 1 Unit: This trim is used to PCC3300,
adjust gk1 in idle PCC3300V2
Offset: 0 Lower Limit: 0 mode. MODBUS
Size (bits): 16 Upper Limit: Access:Read Only
65530
Sign: U
47011 GK2(Idle) Read Only Multiplier: 1 Unit: This trim is used to PCC3300,
adjust gk2 in idle PCC3300V2
Offset: 0 Lower Limit: 0 mode. MODBUS
Size (bits): 16 Upper Limit: Access: Read Only
65530
Sign: U
47014 Gain Read Only 0: Disable Either enables or PCC3300,
Windowing disables Gain PCC3300V2
Enable 1: Enable Windowing feature.
MODBUS
Access:Read Only
47015 GK1 Read Only Multiplier: 1 Unit: The governor 50Hz K1 PCC3300,
Low(50Hz) low gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS Access:
Size (bits): 16 Upper Limit: Read Only
65530
Sign: U
47016 GK1 Read Only Multiplier: 1 Unit: The governor 60Hz K1 PCC3300,
Low(60Hz) low gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS Access:
Size (bits): 16 Upper Limit: Read Only
65530
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47017 GK1 Read Only Multiplier: 1 Unit: The governor 50Hz K1 PCC3300,
High(50Hz) high gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS
Size (bits): 16 Upper Limit: Access:Read Only
65530
Sign: U
47018 GK1 Read Only Multiplier: 1 Unit: The governor 60Hz K1 PCC3300,
High(60Hz) high gain adjust. PCC3300V2
Offset: 0 Lower Limit: 0 MODBUS
Size (bits): 16 Upper Limit: Access:Read Only
65530
Sign: U
47019 Governor Read Only Multiplier: 1 Unit: The speed error PCC3300,
Speed Delta higher limit. MODBUS PCC3300V2
High Offset: 0 Lower Limit: 50 Access:Read Only
Size (bits): 16 Upper Limit:
1000
Sign: U
47020 Governor Read Only Multiplier: 1 Unit: The speed error lower PCC3300,
Speed Delta limit. MODBUS PCC3300V2
Low Offset: 0 Lower Limit: 50 Access: Read Only
Size (bits): 16 Upper Limit:
1000
Sign: U
47021 Intake Read Only 0: PGBU Either PGBU (Onan) PCC3300,
Manifold or EBU (Cummins) PCC3300V2
Temperature 1: EBU sensor. MODBUS
Sensor Type Access : Read Only
47022 Intake Read Only 0: Disable Intake Manifold Temp PCC3300,
Manifold Sensor available or PCC3300V2
Temperature 1: Enable not. MODBUS
Sensor Access : Read Only
Enable
47023 Oil Read Only 0: PGBU Either PGBU(Onan) or PCC3300,
Temperature EBU(Cummins) PCC3300V2
Sensor Type 1: EBU sensor.
47024 Oil Read Only 0: Disable High Oil Temperature PCC3300,
Temperature Sensor available or PCC3300V2
Sensor 1: Enable not.
Enable
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47025 AVR PWM Read Only Multiplier: 0.01 Unit: % The AVR PWM PCC3300,
Command software command. PCC2300,
Offset: 0 Lower Limit: Linear relationship PCC3300V2
Size (bits): 16 Upper Limit: between counts and %
duty cycle with 10000
Sign: U counts=100% duty
cycle. MODBUS
Access : Read Only
47026 Coolant Read Only 0: Disable Coolant Temperature PCC3300,
Temperature 2 Enable PCC3300V2
2 Enable 1: Enable
47027 Start Inhibit Read Only Multiplier: 0.05 Unit: sec Delay progress until a PCC3300,
Delay fault is declared for PCC3300V2
Progress Offset: 0 Lower Limit: start inhibit
Size (bits): 16 Upper Limit:
Sign: U
47028 Genset Read Only 0: Close Indicates the Genset PCC3300,
Voltage Voltage sensing MCB PCC3300V2
Sensing 1: Open status.
MCB status 2: Reserved
3: N/A
4: Network
Failure
47029 Customer Read Only 0: Open Indicates the status of PCC3300,
Gas Valve the Customer Gas PCC3300V2
Status 1: Closed Valve position.
2: Reserved
3: N/A
4: Network
Failure
47030 Crankcase Read Only Multiplier: 0.01 Unit: psi Monitor point for the PCC3300,
Pressure Crankcase Pressure PCC2300,
Extended Offset: 0 Lower Limit: with extended PCC3300V2
-35.67 precision.
Size (bits): 16 Upper Limit: 38
Sign: S
47031 Throttle Delta Read Only Multiplier: 0.1 Unit: psi "The differential PCC3300,
Pressure pressure between the PCC3300V2
Offset: 0 Lower Limit: 0 intake and outlet of a
Size (bits): 16 Upper Limit: throttle valve"
6425.5
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47033 Engine Read Only Multiplier: 0.1 Unit: degF Intake temperature of PCC3300,
Turbocharger engine turbocharger 1 PCC3300V2
1 Offset: 0 Lower Limit: -273 compressor.
Compressor Size (bits): 16 Upper Limit:
Intake 1734.968
Temperature
Sign: S
47048 Intake Read/Write 0: Disabled "Trim to enable the PCC2300,
Manifold detection of Intake PCC3300,
Over 1: Enabled Manifold Backfire PCC3300V2
Pressure(IM condition"
OP) Enable
47049 Intake Read/Write 0: SPN 105 "Source for Intake PCC2300,
Manifold Manifold Temperature. PCC3300,
Temperature 1: SPN 52 SPN 105 Default PCC3300V2
Source Source and SPN 52
when the IMOP is
Enabled"
47050 Intake Read/Write Multiplier: 0.1 Unit: degF/secs "Threshold to decide PCC2300,
Manifold the Intake Manifold PCC3300,
Temp Rate Offset: 0 Lower Limit: 2 Backfire condition, PCC3300V2
of Change Size (bits): 8 Upper Limit: 20 Value entered is for
Threshold degF/secs,
Sign: U degF/2secs is
obtained by a scalar of
2 in PCC software "
47051 Gas Read Only Multiplier: 0.1 Unit: degF This parameter is to PCC3300,
Temperature display engine gas PCC3300V2
Offset: 0 Lower Limit: fuel temperature
Size (bits): 16 Upper Limit:
Sign: S
47052 Turbocharger Read Only Multiplier: 0.1 Unit: % To display engine PCC3300,
Wastegate turbocharger PCC3300V2
Position Offset: 0 Lower Limit: wastegate position
Size (bits): 16 Upper Limit:
Sign: U
47100 AT DEF Read Only Multiplier: 0.1 Unit: % "After Treatment PCC3300V2
Tank Level Diesel Exhaust Fluid
Offset: 0 Lower Limit: 0 Tank Level"
Size (bits): 16 Upper Limit:
Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47101 AT DEF Read Only Multiplier: 0.01 Unit: % "After Treatment PCC3300V2
Concentratio Diesel Exhaust Fluid
n Offset: 0 Lower Limit: 0 Concentration"
Size (bits): 16 Upper Limit:
Sign: U
47102 AT DEF Read Only Multiplier: 0.1 Unit: degF "After Treatment PCC3300V2
Tank Diesel Exhaust Fluid
Temperature Offset: 0 Lower Limit: -40 Tank Temperature"
Size (bits): 16 Upper Limit:
Sign: S
47103 AT SCR Read Only Multiplier: 0.1 Unit: degF "After Treatment SCR PCC3300V2
Catalyst Catalyst Outlet Gas
Outlet Gas Offset: 0 Lower Limit: Temperature"
Temperature -459.4
Size (bits): 16 Upper Limit:
Sign: S
47104 AT 1 DEF Read Only 0: OFF Driver's warning PCC3300V2
Tank 1 Low indicator for diesel
Level 1: ON Solid exhaust fluid (DEF)
Indicator 2: ON Fast Blink tank low level
3: Not Available
4: Network
Failure
47105 Operator Read Only Multiplier: 1 Unit: Minutes Monitor point for Time PCC3300V2
Inducement To Torque Derate
Time To Offset: 0 Lower Limit: Level 1
Torque Size (bits): 16 Upper Limit:
Derate Level
1 Sign: U
47106 Operator Read Only Multiplier: 1 Unit: Minutes Monitor point for Time PCC3300V2
Inducement To Torque Derate
Time To Offset: 0 Lower Limit: Level 2
Torque Size (bits): 16 Upper Limit:
Derate Level
2 Sign: U
47107 Operator Read Only Multiplier: 1 Unit: Minutes Monitor point for Time PCC3300V2
Inducement To Final Inducement
Time To Offset: 0 Lower Limit: Action
Final Size (bits): 16 Upper Limit:
Inducement
Action Sign: U
Parameter/
Modbus Modbus Control
System Specifications Description
Address Access Boards
Name
47108 AT 1 DEF Read Only Multiplier: 0.3 Unit: g/hr '"Monitor Point for PCC3300V2
Actual Urea dosing-1 (Leg-1)
Dosing Offset: 0 Lower Limit: 0 (grams/hour)"
Quantity Size (bits): 16 Upper Limit:
19277
Sign: U
47109 AT 2 DEF Read Only Multiplier: 0.3 Unit: g/hr '"Monitor Point for PCC3300V2
Actual Urea dosing-2 (Leg-2)
Dosing Offset: 0 Lower Limit: 0 (grams/hour)"
Quantity Size (bits): 16 Upper Limit:
19277
Sign: U
47110 AT 2 SCR Read Only Multiplier: 0.1 Unit: degF '"Monitor Point for PCC3300V2
Catalyst SCR out Temperature-
Outlet Gas Offset: 0 Lower Limit: 2 (Leg-2)"
Temperature -459.4
Size (bits): 16 Upper Limit:
3155
Sign: S
NOTICE
If an address or bit is not listed in this table it is not implemented.
NOTICE
The Master device can read 1-40 contiguous registers, write 1-40 contiguous registers, or read
diagnostic counters.
TABLE 46.
TABLE 47.
TABLE 48.
TABLE 49.
TABLE 50.
• If writing to a string values, the register in the holding register write request is not the first register of
that string.
Write requests for string type parameters where not every register associated with the string is in the
request shall write only the requested portion of the string, null terminating the remainder of the string.
Write requests to this control may return an Illegal Data Value exception code 03. This means that the
requested write failed to occur.
Write Multiple Holding Registers (Function Code 16)
The control provides the ability to write to 1 to 123 consecutive holding registers.
The control will return an Illegal Address exception code 02 if any of the following conditions occur:
• The first register in the holding register write request is not defined on the control.
• The first register in the holding register write request does not allow for the full writing of a numeric
value. This would occur if the first register in the write request is not mapped to the most significant
2 bytes of a parameter.
• The last register in the holding register write request does not allow for the full writing of a numeric
value. This would occur if the last register in the write request is not mapped to the least significant 2
bytes of a parameter.
• If string values are in the write request, the first register for any string is not within the requested
register range.
Write requests for string type parameters where not every register associated with the string is in the
request shall write only the requested portion of the string, null terminating the remainder of the string.
Write requests to this control may return an Illegal Data Value exception code 03. This means that some
or all of the requested writes failed to occur. It is the responsibility of the requestor to read the data again
to determine which parameters were not written to their requested new values and to respond as
necessary.
NOTICE
Changes to the Modbus Baud Rate and the Modbus Parity and Stop Bit Selection parameters will
be immediately reflected on the serial port being configured. Any Modbus commands in progress
on that port in the old communications settings will fail until the Modbus master also updates its
communications settings to match those of the slave.
Value Examples
Examples of
Abnormal State Value Description Unsigned 2-Byte Signed 2-Byte Failures
Integer Value Integer Value
This data shall An on controller
Hardware/ represented as 4 less hardware/component
than the highest 65531 32763 failure that provides
Component Failure positive value for that data like voltage,
parameter. current and power
Data that comes from
This data shall be
a network that has
represented as 3 less
failed such as sensor
Network Failed Data than the highest 65532 32764
data coming from I/O
positive value for that
modules on a PCCnet
parameter.
or CAN network
Data that has been
determined to be out
This data shall be of range LOW or out
represented as 2 less of range (when there
Out of Range Low than the highest 65533 32765 is no distinction
positive value for that between out of range
parameter. high and out of range
low) due to an open
sensor
Data that has been
determined to be out
This data shall be of range HIGH or out
represented as 1 less of range (when there
Out of Range
than the highest 65534 32766 is no distinction
High/Out of Range
positive value for that between out of range
parameter. high and out of range
low) due to an open
sensor
Parameters which are
not available due to
This data shall be
the sensor not being
Unsupported (Not represented as the
65535 32767 installed or not
Available) Data highest positive value
enabled in the
for that parameter.
controller’s
configuration
• For string parameters, the first two characters in the string will be mapped to the Register Address
listed in the Controllers Modbus Register Map. Additional characters will be provided in the following
registers. For example, for the string "String1" at address 400031, the characters will be mapped the
following registers:
400031: "St" 400032: "ri" 400033: "ng" 400034: "1_"
Modbus RTU Slave Protocol Support for Read Input Registers
Each port instance of Modbus RTU Slave Protocol shall support interface to the following read input
registers through function code 04. These are the only input registers supported by this control.
The following table applies for each instance of the Modbus RTU protocol on any control and will return
the data from the port being read only.
Level Description
NOTICE
If an address or bit is not listed in the table below, it has not been implemented.
NOTICE
The master device can read 1-16 contiguous registers, write 1-16 contiguous registers, or read
diagnostic counters.
NOTICE
To connect with the Modbus tool, set the TB15 Protocol selection parameter to “Modbus” via a
service tool or LCD, which will immediately disconnect the PC tool. To reconnect the PC tool, set
the TB15 protocol selection to “Mon through Display configuration”, or enter "0" in the specific
TB15 protocol selection Modbus resistor address.
NOTICE
Earlier versions of this software may not support all of the Modbus registers in the following
table. If a particular register is not available in your installation, it is possible that the Modbus
connection is working but the controller software does not support that particular register.
400160 TB17-4 Guest 0: Not Connected Sets the value of TB17-4 PS060X
Sensor 1: Diagnostic Input #4 Sensor Selection
Selection
400161 TB17-5 Guest 0: Not Connected Sets the value of TB17-5 PS060X
Sensor 1: Diagnostic Input #5 Sensor Selection
Selection
400162 TB17-6 Guest 0: Not Connected Sets the value of TB17-6 PS060X
Sensor 1: Diagnostic Input #6 Sensor Selection
Selection
400207 Charging Read Only Multiplier: 0.001 Measured Charging PS060X
Alternator Size (Bits): 16 Alternator voltage value
Voltage Data Type: uint16
Unit: V
Lower Limit: 0
Upper Limit: 41
400228 Amber Read Only 0: Inactive Engine Conrol System PS060X
Warning 1: Active warning condition
Lamp Status
400585 Exhaust Gas Read Only Multiplier: 0.1 Monitor point for Exhaust Gas PS060X
Temperature Size (Bits): 16 Temperature
Data Type: int16
Unit: degF
Lower Limit: 459.4
Upper Limit: 3154.9
400597 SCR Thermal Read Only 0: Inactive Indicates that the exhaust PS060X
Management 1: Active temperatures have been
Active 2: Not Available elevated for regeneration of
the SCR aftertreatment
3: Network Failure
system or in preparation of
regeneration of the SCR
aftertreatment system
400616 DPF Thermal Read Only 0: Inactive Indicates that the exhaust PS060X
Management 1: Active temperatures have been
Active 2: Not Available elevated for regeneration of
the diesel particulate filter
3: Network Failure
aftertreatment system or in
preparation of regeneration of
the diesel particulate
aftertreatment system
400617 AT Diesel Read Only Multiplier: 0.1 Indicates the temperature of PS060X
Oxidation Size (Bits): 16 engine combustion by
Catalyst Data Type: int16 products entering the diesel
Intake Gas oxidation catalyst in exhaust
Unit: degF
Temperature bank 1
Lower Limit: 459.4
Upper Limit: 3154.9
400709 Application Read Only Multiplier: 1 The common device type PS060X
Device Type Size (Bits): 16 identifier parameter for all
Data Type: uint16 PGBASE applications
Unit: NA
Lower Limit: 0
Upper Limit: 65535
401000 Metering Technician 0: Three Phase Wye Used to select the phase PS060X
Phase Config 1: Three Phase Delta configuration and Delta/Wye
2: Single Phase configuration for AC power
distribution
3: Split Phase
401024 AMF State Read Only 0: AMF Not Available Provides the state in which PS060X
1: Transfer Retransfer Off the Auto Mains Failure is
2: Utility Pickup currently present
3: Utility Dropout
4: Genset Starting
5: Transfer Start
6: Utility CB Opened
7: Genset CB Closed
8: Transfer Complete
9: Retransfer Start
10: Genset CB Opened
11: Utility CB Closed
12: Retransfer Complete
13: Transfer Fail
14: Retransfer Fail
401025 Transfer Read Only 0: Not Available Provides value of Transfer PS060X
Switch 1: At Utility switch feedback status
Feedback 2: At Genset
Status
3: Unknown Open
4: Unknown Closed
402355 Time Delay Guest Multiplier: 0.1 Provides the value of Time PS060X
Engine Start Size (Bits): 16 Delay Engine Start (TDES)
Data Type: uint16
Unit: sec
Lower Limit: 0
Upper Limit: 3600
402356 Time Delay Guest Multiplier: 0.1 Provides the value of Time PS060X
Engine Size (Bits): 16 Delay Engine Cooldown
Cooldown Data Type: uint16 (TDEC)
Unit: sec
Lower Limit: 0
Upper Limit: 3600
402357 AT DEF Tank Read Only Multiplier: 0.1 After Treatment Diesel PS060X
Level Size (Bits): 16 Exhaust Fluid Tank Level
Data Type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 100
403012 TB16-10 Guest 0: Not Connected Used to set the value of PS060X
Sensor 1: Diagnostic Input #1 TB16-10 Sensor Selection
Selection 2: Battle Short
403019 Electronic Read and 0: Disable Electronic Governor enable PS060X
Governor Write 1: Enable feature
Enable
403020 Initial Crank Read and Multiplier: 0.1 Electronic governing initial PS060X
Fueling Duty Write Size (Bits): 16 duty cycle setting
Cycle Data type: uint16
Unit: %
Lower Limit: 0
Upper Limit: 100
403021 Initial Crank Read and Multiplier: 0.1 Time spent at Initial Crank PS060X
Fueling Write Size (Bits): 8 Fueling Command
Period Data Type: uint8
Unit: Sec
Lower Limit: 0
Upper Limit: 10
403599 Customer Read Only 0: IsFalse The digital status of Customer PS060X
Input #2 1: IsTrue Input #2
403645 LCL Technician 0: None Sets low coolant level fault PS060X
Detection 1: Warning response
Response 2: Shutdown
403821 Time Delay Operator Multiplier: 0.1 Provides the value of Time PS060X
Programmed Size (Bits): 16 Delay Programmed Transition
Transition Data Type: uint16 (TDPT)
Unit: sec
Lower Limit: 0
Upper Limit: 600
403822 Time Delay Guest Multiplier: 0.1 Provides the Value of Time PS060X
Emergency to Size (Bits): 16 Delay Emergency to Normal
Normal Data Type: uint16 (TDEN)
Unit: sec
Lower Limit: 0
Upper Limit: 1800
410001 Genset Read Only Multiplier: 0.1 Average power factor of all PS060X
Average Size (Bits): 32 line power factors
Power Factor Data Type: float32
Unit:
Lower Limit: –1
Upper Limit: 1
410007 Genset L1 Read Only Multiplier: 0.1 Active energy exported PS060X
Exported Size (Bits): 32 by Line 1
kWh Data Type: float32
Unit: kWh
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38
410009 Genset L1 Read Only Multiplier: 0.1 Reactive energy imported PS060X
Imported Size (Bits): 32 by Line 1
kVarh Data Type: float32
Unit: kVarh
Lower Limit: 3.40E+38
Upper Limit: 3.40E+38
Bit Description
0 Low fuel level
1 Low coolant level
2 Over speed
3 Low oil pressure
4 Pre-low oil pressure
5 High engine temperature
Bit Description
0 Emergency stop
1 Utility circuit breaker tripped
2 Genset circuit breaker tripped
3 Load demand
4 Fail to close
5 Fail to sync
6 Reverse KVAR
7 Reverse KW
8 Short circuit
9 Overcurrent
10 Overload
11 Under frequency
12 Low AC voltage
13 High AC voltage
14 Ground fault
15 Check genset
Bit Description
0 Louver breaker position
1 Louver open relay position
2 Louver close relay position
3 Louver 1 open
4 Louver 1 close
5 Louver 2 open
6 Louver 2 close
7 Louver 3 open
8 Louver 3 close
9 Utility breaker positon
10 NA
11 Ventilation fan fault
12 Cooling fan 1 and 2 contactor position
13 Cooling fan 1 breaker position
14 Cooling fan 2 breaker position
15 Cooling fan 3 and 4 contactor position
Bit Description
0 Cooling fan 3 breaker position
1 Cooling fan 4 breaker position
2 Cooling fan 5 and 6 contactor position
3 Cooling fan 5 breaker position
4 Cooling fan 6 breaker position
5 Ventilation fan 7 and 8 contactor position
6 Ventilation fan 7 breaker position
7 Ventilation fan 8 breaker position
Bit Description
0 Louver manual open
1 Louver manual close
2 NA
3 NGR ground fault
4 Cooling fan container door open alarm
5 Fire alarm
6 PCC Key Switch
7 PCC ready to load
8 Louver open command
9 Louver close command
10 Cooling fan 1 and 2 run command
11 Cooling fan 3 and 4 run command
12 Cooling fan 5 and 6 run command
13 Ventilation fan run command
14 Fuel valve open command
15 Emergency shutdown command
Bit Description
0 Louver breaker open warning
1 Louver open relay warning
2 Louver close relay warning
3 Louver 1 open warning
4 Louver 1 close warning
5 Louver 2 open warning
6 Louver 2 close warning
7 Louver 3 open warning
8 Louver 3 close warning
9 Utility breaker open warning
10 NA
11 Ventilation fan fault
12 Cooling fan 1 and 2 contactor warning
13 Cooling fan 1 breaker open warning
14 Cooling fan 2 breaker open warning
15 Cooling fan 3 and 4 contactor warning
Bit Description
0 Cooling fan 3 breaker open warning
1 Cooling fan 4 breaker open warning
2 Cooling fan 5 and 6 contactor warning
3 Cooling fan 5 breaker open warning
4 Cooling fan 6 breaker open warning
5 Ventilation fan 7 and 8 contactor warning
6 Ventilation fan 7 breaker open warning
7 Ventilation fan 8 breaker open warning
Bit Description
0 Aux alternator voltage warning
1 Genset container temperature high warning
2 Genset container temperature high alar
3 ATS postion warning
4 Cooling fan container door open alarm
5 PLC fault warning
6 PLC cell battery low voltage warning
7
8
9
10
11
12
13
14
15
Bit Description