Catalog C7

CABLE
ACCESSORIES

Experience & Reliability

Cable
Accessories
Table of Contents
INSIDE.................................................................................PAGE

200 A Loadbreak Products


15 kV Loadbreak Products
Ratings & Specifications................................................4-5
Loadbreak Elbows.........................................................6-7
Loadbreak Inserts.............................................................8
Loadbreak Accessories.....................................................9
Grounding Accessories...................................................10
Loadbreak Junctions.................................................11-12
Stacking Dimensions......................................................13
25/28 kV Loadbreak Products
Ratings & Specifications............................................14-15
Loadbreak Elbows.....................................................16-17
Loadbreak Inserts...........................................................18
Loadbreak Accessories...................................................19
Grounding Accessories...................................................20
Loadbreak Junctions.................................................21-22
Stacking Dimensions......................................................23
Fused Elbows.............................................................24-25
35 kV Loadbreak Products
Ratings & Specifications............................................26-27
Loadbreak Elbows.....................................................28-29

C7 Page 2 | July 2019


Table of Contents
INSIDE.................................................................................PAGE

600 A Deadbreak Products


15/25/28 kV Deadbreak Products
Ratings & Specifications............................................30-31
Deadbreak Bolted T-Body System............................32-33
Deadbreak ETP Elbow Termination System.............34-35
Deadbreak LRTP Elbow Termination System...........36-37
Modular Splicing Kits.....................................................38
Deadbreak Accessories..............................................39-43
Deadbreak Junctions......................................................44
TapMaster™ Junctions..............................................45-46
Stacking Dimensions......................................................47
35 kV Deadbreak Products
Ratings & Specifications............................................48-49
Deadbreak Bolted T-Body System............................50-51
Deadbreak ETP Elbow Termination System.............52-53
Deadbreak Accessories..............................................54-56
Deadbreak Junctions......................................................57
Underground Arresters
Ratings & Specifications............................................58-60
Arrester Selection...........................................................61
15 kV Underground Arresters..................................62-63
25/28 kV Underground Arresters.............................64-65
35 kV Underground Arresters..................................66-69

Reference Material....................................................70-71

C7 Page 3 | July 2019


200 A Loadbreak
15 kV PRODUCTS

C7 Page 4 | July 2019


15 kV LOADBREAK PRODUCTS

RATINGS & SPECIFICATIONS

GENERAL INFORMATION
RATINGS
Hubbell 15 kV, 200 A Separable Connectors are fully Max. continuous voltage................. 8.3 kV phase-to-ground
14.4 kV phase-to-phase
shielded, insulated, and submersible products that
Continuous current.......................... 200 A rms
provide a means to mate or disconnect cable to
switchgear, transformers, or sectionalizing equipment
on power distribution systems. They are designed
SHORT-TIME CURRENT RATINGS
for pad-mounted or subsurface applications, where 0.17 seconds duration...................... 10,000 A rms symmetrical
the components may be exposed to direct sunlight or 3.00 seconds duration...................... 3,500 A rms symmetrical
continuously submerged in water up to 6 feet (2m).

All 15 kV loadbreak products and accessories are INSULATION WITHSTAND VOLTAGES


designed and tested to meet or exceed all applicable Basic Impulse Level........................... 95 kV crest
requirements of IEEE and ANSI including the following: (1.2 x 50 µsec. wave)
IEEE Std. 386 for Separable Connectors (Interface 5) 60 Hertz (one minute)..................... 34 kV rms
IEEE Std. 592 for Exposed Semi-conducting Shields Corona Extinction Voltage.............. 11 kV rms
ANSI Std. C119.4 for Electrical Connectors (5 pC)

These devices are suitable for energized loadmake/


loadbreak operations when using an 8’ shotgun-type SWITCHING

hot stick on grounded WYE systems(1). They are

1-phase and 3-phase circuits 10 loadmake/loadbreak
also fully interchangeable with other manufacturer’s
8.3 kV phase-to-ground, 14.4 operations at 200 A with
products that conform to the electrical requirements of kV maximum across the open 70-80% lagging power factor.
IEEE Std. 386. contacts.

Hubbell 15 kV products are designed for use in FAULT CLOSURE


ambient temperatures between -40°C and +65°C and One fault-close operation at 8.3 kV phase-to-ground, or 14.4
can be operated energized between -20°C and +65°C. kV phase-to-phase; 10,000 A rms symmetrical, 10 cycles, (0.17
Loadbreak devices should not be operated, while seconds).
energized, at elevations over 6,000 feet.

All rubber components are manufactured using


peroxide-cured insulating and conductive compounds. PRODUCTION TESTS
100% factory test for partial discharge and either AC HI-POT (34
kV for 60 seconds) or impulse (BIL) (95 kV 1.2 x 50 µsec. wave).
(1) Contact the factory for recommendations for use on
ungrounded, resistance grounded, or delta systems.

Performance C7 Page 5 | July 2019


15 kV LOADBREAK ELBOWS

Hubbell 15 kV Loadbreak Elbows are designed and tested to meet all


requirements of IEEE Std. 386. The operating interface will mate with
any product that conforms to IEEE Std. 386, Interface 5.

Elbows can be supplied with a capacitive test point that allows for the
installation of faulted circuit indicators and will indicate the presence of
voltage when interrogated with a high-impedance meter.

Bi-metal compression lug meets all requirements of ANSI Std.


C119.4 for Class A connectors.

The integral seal elbow eliminates the need for a separate sealing
kit. The integral seal elbow is supplied with mastic strips to form a
barrier around the neutral wires. There are external grip hooks on
the integral seal elbow boot for easier installation.

SELECTION & ORDERING INFORMATION

Determine the diameter over the cable’s insulation by finding it in the


manufacturer’s catalog or by measuring it (do not measure over the
extruded semi-con). Select an elbow size so that the insulation falls
within the elbow’s range.

Select a connector code that identifies the conductor size and stranding.

The standard long, bi-metal connector can be replaced with a ProbeLok


connector, or an all copper connector for use on copper conductors only. Cable Dimension Reference
Decide if a capacitive test point is required.

The elbow can be supplied with a separate, cold-shrink seal kit for
jacketed concentric neutral cable, or it can be furnished with a separate
adapter kit for copper tape shield cables.

The standard elbow housing can be supplied as an integral elbow seal


housing.

Components:
215LBP Probe kit complete with pin wrench
200LUGBx Standard, long bi-metal lug
200LUGPx ProbeLok lug
200LUGCx All copper lug

To have a bushing insert packaged with the elbow, add ‘BI’ to the end of the part number. For example: 215LEJ45BI.

625SK52 Cold Shrink Cable Seal Kit for JCN cable with an overall diameter of 0.95” to 1.94”
625SK60 Tape Shield Adapter Kit for cable with an overall diameter of 0.83” to 1.95”

C7 Page 6 | July 2019


CATALOG NUMBER ORDERING INFORMATION

Example: Integral seal elbow for 1/0 stranded, 175 mil cable with a test point is: 215LEJ45T

2 1 5 L E

Hubbell Product Prefix

J = Integral Seal* J = Seal Kit


Blank = Without S = Shield Adapter Kit
G = Ground Kit for Integral Seal
* Integral seal only available for size 4 & 5 housings Blank = None

Select Housing Code from Column 1 T = Test Point


Blank = Without
Cable Insulation Cable Insulation
Housing Code Range (Inches) Range (mm)
3 0.495 - 0.730 12,5 - 18,5
3 or 4
4 0.635 - 0.905 16,1 - 23, 0
C = Copper Lug
4 or 5 P = ProbeLok Lug
5 0.760 - 1.135 19,3 - 28, 8 Blank = Without

Select Connector Code from Column 1, or 0 for without Connector

Connector AWG or 15 kV - 175mil 15 kV - 220mil 25 kV - 260mil


Code kcmil Stranding (Inches) (Inches) (Inches)

#6 Stranded & Compressed 0.527 - 0.622 0.617 - 0.717


1 #4 Compact & Solid 0.557 - 0.652 0.647 - 0.747
#4 Stranded & Compressed 0.575 - 0.670 0.665 - 0.765
#3 Compact & Solid 0.579 - 0.671 0.671 - 0.769
2 #3 Stranded & Compressed 0.604 - 0.698 0.694 - 0.793
#2 Compact & Solid 0.610 - 0.705 0.700 - 0.800 0.780 - 0.880
3 #2 Stranded & Compressed 0.635 - 0.730 0.725 - 0.825 0.805 - 0.905
#1 Compact & Solid 0.645 - 0.735 0.735 - 0.830 0.805 - 0.905
#1 Stranded & Compressed 0.675 - 0.770 0.765 - 0.855 0.835 - 0.935
4 0.680 - 0.775 0.770 - 0.865
1/0 Compact & Solid 0.835 - 0.940
1/0 Stranded & Compressed 0.715 - 0.810 0.805 - 0.905 0.875 - 0.980
5 0.715 - 0.815 0.805 - 0.905
2/0 Compact & Solid 0.875 - 0.980
2/0 Stranded & Compressed 0.760 - 0.855 0.850 - 0.950 0.920 - 1.025
6 0.765 - 0.860 0.855 - 0.955
3/0 Compact & Solid 0.925 - 1.030
3/0 Stranded & Compressed 0.810 - 0.905 0.900 - 1.000 0.970 - 1.075
7 0.815 - 0.910 0.905 - 1.005 0.975 - 1.080
4/0 Compact & Solid
4/0 Stranded & Compressed 0.865 - 0.965 0.955 - 1.060 1.025 - 1.135
8 0.880 - 0.965 0.970 - 1.060 1.040 - 1.135
250 Compact

*These ranges are taken from the AEIC/ICEA industry cable standards

C7 Page 7 | July 2019


15 kV LOADBREAK INSERTS

The Hubbell Loadbreak Bushing Insert meets all requirements of IEEE Std. 386. It is designed for installation on
transformers, switches or other equipment having a 200 A bushing well that meets the requirements of IEEE Std.
386, Interface 3. When mated with a comparably rated elbow or other accessory, the bushing insert provides a fully
shielded and submersible connection. The bushing insert contains an all-copper current path from the female contact
to the bushing well and internal connection to the switch or transformer.

215BI
Bushing Insert
Internal hex broach accepts a 5/16” wrench for proper
installation torque.

Yellow seating indicator provides a positive indication


that the mating product is fully installed.

215FTI
Feed-thru Insert
Creates a tap position in an existing apparatus

Converts a radial-feed transformer to a loop-feed unit.

Supplied with an auxiliary hold-down bail.

Contains an internal ratchet mechanism to facilitate


proper alignment and torque.

C7 Page 8 | July 2019


Experience
15 kV LOADBREAK ACCESSORIES
215ICI
Insulating Cap
and
215ICC
Insulating Cap with Conductive Cuff
Used as a temporary or permanent cover on an energized operating
interface. Standard product has an insulating cuff. An optional
conductive cuff is available. Both units are supplied with a 36-inch
long lead for grounding.

215SB
Standoff Bushing
Provides a temporary or permanent parking position for energized
loadbreak elbows. The bracket permits mounting on the apparatus
parking stand.

215FT
Feed-thru - Horizontal Bracket
and
215FTV
Feed-thru - Vertical Bracket
A two-position junction in a bracket that can be installed on the
apparatus parking stand. Provides a means to test, phase, ground,
or park an energized elbow. They can also be used to by-pass a
transformer or to add arrester protection at the open point.

225TR
Test Rod
Fits into loadbreak bushings, junctions, and other products that
contain a loadbreak interface and is used with test meters to
determine if the circuit is energized or not.

SL150
Silicone Lubricant
Silicone lubricant for all separable connectors. Supplied
in a 5.3 oz (150 g.) tube. Sold in cartons of 24 tubes.

C7 Page 9 | July 2019


15 kV LOADBREAK GROUNDING ACCESSORIES

215GB
Grounded Bushing
Provides a temporary ground. Contains a fully functioning
loadbreak mechanism and has a fault current rating of
10,000 A for 10 cycles. Can be installed with a hotstick.

T6003091
Grounding Bushing with Clamp
This set includes a loadbreak bushing and bronze T6000466
ground clamp connected by a 4-ft. yellow 1/0 cable. A tin-
plated copper connector joins the cable to the bushing. A
threaded copper ferrule connects the cable to the clamp.
Fault current rating for each set: 10,000 A for 10 cycles.

C6000729
Grounding Elbow
Each set includes a yellow elbow, 6 feet of 1/0 copper
grounding cable with yellow jacket, and bronze T6000466
ground clamp. Fault current rating for each set: 10,000 A
for 10 cyles.

C6003102
Three-Phase Grounding Elbow Sets for
Switches & Transformers
Each set includes a three-way terminal block assembly, three 6-ft.
lengths of 1/0 copper ground cable with yellow jacket, a bronze
T6000466 ground clamp and three elbows. Fault current rating for
each set: 10,000 A for 10 cycles.

Grounding Component Parts:


200GB6LUG 1-hole copper lug for 1/0 grounding cable (grounding bushing component)
215GBHSG 200 A 15 kV Grounding Bushing Housing
215GEHSG 200 A 15 kV Grounding Elbow Housing
215LBP 200 A 15 kV Loadbreak Probe
200LUGC6 2/0 all copper lug for use with 1/0 grounding cable
200LUGC7 3/0 all copper lug for use with 2/0 grounding cable

C7 Page 10 | July 2019


15 kV LOADBREAK JUNCTIONS
JUNCTION SELECTION AND ORDERING

Example: 4-point junction, supplied with a SS bracket is: 215J4B

2 1 5 J

Hubbell Product Prefix

2 = 2 Position
3 = 3 Position
4 = 4 Position

B = With Bracket
U = With U-Straps

JUNCTION DESCRIPTION

Hubbell junctions are used to sectionalize cables or as center. Yellow seating indicator rings provide a positive
feed-thrus for making lateral taps. indication that the mating product is fully installed.

They are available in two, three and four tap units and, Junctions with the corrosion-resistant stain­less steel
when con­nected with loadbreak elbows, have ratings mounting bracket allow back plate mounting angles of
as shown on the 15 kV Loadbreak Product Ratings & 30, 45, or 60 degrees. This bracket can be adjusted for
Specifications sheet. horizontal mounting to a flat surface. Junctions can also
be ordered with only U-straps for surface mounting.
Each tap works independently of the others contained
on the same unit. Adjacent taps are 3.24 inches center to

Junction Component Parts:


200JUNCMF Junction Adjustable Mounting Feet Only, Stainless Steel (1 Pair)
215J2BRKT Junction Bracket, Stainless Steel w/Adjustable Feet, 2 Position
215J3BRKT Junction Bracket, Stainless Steel w/Adjustable Feet, 3 Position
215J4BRKT Junction Bracket, Stainless Steel w/Adjustable Feet, 4 Position

Performance
215US1 Junction U-strap, Stainless Steel w/Hardware

C7 Page 11 | July 2019


Fault Closure
One Fault-Close Operation at max 8.3 kV Phase-to-Ground, or
max 14.4 kV Phase-to-Phase; max 10,000 A rms Symmetrical,
10 Cycles (0.17 Sec.).
___________________________________________________
Production Tests

15 kV LOADBREAK JUNCTIONS 100% factory tested for Partial Discharge and either AC 60 Hz
(34 kV for 60 Sec.) or Impulse (BIL) (95 kV 1.2 x 50 μSec. wave).

4 POSITION ADJUSTABLE BRACKET


30°, 45°, 60° and 90°

Bracket & U-strap Dimensions


Bracket Mounting Angles

A
3.24 IEEE STD 386 INTERFACE 5
TYP

8.4

4.6

CATALOG # POINTS A B C
Part Number No. Positions 2
215J2B A 13.9 B 2.0 C
16.9
215J3B 3 20.3 4.4 19.7
215J2B 2
215J4B 4 13.9 23.5 2.0 7.7 16.9
22.8

215J3B 3 20.3 }
4.4 19.7
HUBBELL POWER SYSTEMS, Inc.
215J4B 4 23.5 POWER SYSTEMS, INC
7.7 22.8
200A 15kV JUNCTION
TITLE

C ONTENTS ARE CONFIDENTIAL AND THE


EXCLUSIVE PROPERTY OF HUBBELL
POWER SYSTEMS. NO PUBLIC ATION,
U-Strap Dimensions DISTRIBUTION OR C OPIES MAY BE MADE SIZE DWG NO. CAT / PART / ASSY NO. REV

SB -- 0
WITHOUT THE WRITTEN CONSENT OF
HUBBELL POWER SYSTEMS.
HUBBELL POWER SYSTEMS UNPUBLISHED 215JXB
REV DATE DO NOT SCALE
DRN BY BvB 1 OF 1
ALL RIGHTS RESERVED UNDER THE
11/20/18 C OPYRIGHT LAWS. THIS DRAWING
DATE 11/20/18 SHEET

C7 Page 12 | July 2019


15 kV STACKING DIMENSIONS

15 kV Standoff Bushing
A 215SB
B E
15 kV Bushing Insert
15 kV Elbow 215BI
215LExx E
CAUTION:---

15 kV Feed-Thru
215FTx

C E
15 kV Junction w/ U-Strap
215JxU
15 kV Elbow Arrester
215ELAxx E

15 kV Feed-Thru Insert
215FTI

E
D

15 kV Insulating Cap 15 kV Junction w/ Bracket


215ICI 215JxB

15 kV Parkingstand Arrester
215PLAxx
E

Overall 15 kV Product Stacking Dimensions


Product Product Elbow + Product Elbow + Product Arrester + Product Cap + Product
(E) (A + E) (B + E) (C + E) (D + E)

215SB - 15 kV Standoff Bushing 5.34" 9.54" 9.18" 9.02" 8.11"


215BI - 15 kV Bushing Insert 4.69" 8.89" 8.53" 8.57" 7.46"
215FTx - 15 kV Feed-Thru 6.24" 10.44" 10.08" 9.92" 9.01"
215JxU - 15 kV Junction w/U-strap 5.90" 10.10" 9.74" 9.58" 8.67"
215FTI - 15 kV Feed-Thru Insert 8.95" 13.15" 12.79" 12.63" 11.72"
215JxB - 15 kV Junction w/Bracket 8.11" 12.31" 11.95" 11.79" 10.88"
215PLAxx - 15 kV Parkingstand Arrester 7.18" 11.38" 11.02" N/A 9.95"

C7 Page 13 | July 2019


200 A Loadbreak
25/28 kV PRODUCTS

C7 Page 14 | July 2019


25/28 kV LOADBREAK PRODUCTS

RATINGS & SPECIFICATIONS

GENERAL INFORMATION
RATINGS
Hubbell 25/28 kV, 200 A Separable Connectors are Max. continuous voltage................. 16.2 kV phase-to-ground
fully shielded, insulated, and submersible products 28.0 kV phase-to-phase
Continuous current.......................... 200 A rms
that provide a means to mate or disconnect cable to
switchgear, transformers, or sectionalizing equipment
on power distribution systems. They are designed
SHORT-TIME CURRENT RATINGS
for pad-mounted or subsurface applications, where
the components may be exposed to direct sunlight or 0.17 seconds duration...................... 10,000 A rms symmetrical
3.00 seconds duration...................... 3,500 A rms symmetrical
continuously submerged in water up to 6 feet (2m).

All 25/28 kV loadbreak products and accessories are


designed and tested to meet or exceed all applicable
INSULATION WITHSTAND VOLTAGES
Basic Impulse Level........................... 125 kV crest
requirements of IEEE and ANSI, including the following: (1.2 x 50 µsec. wave)
IEEE Std 386 for Separable Connectors (Interface 7A) 60 Hertz (one minute)..................... 45 kV rms
IEEE Std. 592 for Exposed Semi-conducting Shields Corona Extinction Voltage.............. 21.5 kV rms
ANSI Std. C119.4 for Electrical Connectors (5 pC)

These devises are suitable for energized loadmake/


loadbreak operations when using an 8’ shotgun-type SWITCHING
hot stick on grounded WYE systems(1). They are
also fully interchangeable with other manufacturer’s 1-phase and 3-phase circuits 10 loadmake/loadbreak
products that conform to the electrical requirements of 16.2 kV phase-to-ground, 28.0 operations at 200 A with
IEEE Std. 386. kV maximum across the open 70-80% lagging power
contacts. factor.
Hubbell 25/28 kV products are designed for use in
ambient temperatures between -40°C and +65°C and
FAULT CLOSURE
One fault-close operation at 16.2 kV phase-to-ground, or
can be operated energized between -20°C and +65°C. 28.0 kV phase-to-phase; 10,000 A rms symmetrical, 10 cycles,
Loadbreak devices should not be operated, while (0.17 seconds).
energized, at elevations over 6,000 feet.

All rubber components are manufactured using PRODUCTION TESTS


peroxide-cured insulating and conductive compounds. 100% factory test for partial discharge and either AC HI-POT
(45 kV for 60 seconds) or impulse (BIL) (125 kV 1.2 x 50 µsec.
wave.)
(1) Contact the factory for recommendations for use on
ungrounded, resistance grounded, or delta systems.

Performance C7 Page 15 | July 2019


25/28 kV LOADBREAK ELBOWS

HUBBELL 25/28 kV Loadbreak Elbows are designed and tested to meet


all requirements of IEEE Std. 386. The operating interface will mate with
any product that conforms to IEEE Std. 386, Interface 7A.

Elbows can be supplied with a capacitive test point that allows for the
installation of faulted circuit indicators and will indicate the presence of
voltage when interrogated with a high-impedance meter.

Bi-metal compression lug meets all requirements of ANSI Std. C119.4 for
Class A connectors.

The integral seal elbow eliminates the need for a separate sealing kit.
The integral seal elbow is supplied with mastic strips to form a barrier
around the neutral wires. There are external grip hooks on the integral
seal elbow boot for easier installation.

SELECTION & ORDERING INFORMATION

Determine the diameter over the cable’s insulation by finding it in the


manufacturer’s catalog or by measuring it (do not measure over the
extruded semi-con). Select an elbow size so that the insulation falls
within the elbow’s range.

Select a connector code that identifies the conductor size and stranding.

The standard long, bi-metal connector can be replaced with a ProbeLok


connector, or an all copper connector for use on copper conductors only.
Cable Dimension Reference
Decide if a capacitive test point is required.

The elbow can be supplied with a separate, cold-shrink seal kit for
jacketed concentric neutral cable, or it can be furnished with a separate
adapter kit for copper tape shield cables.

The standard elbow housing can be supplied as an integral elbow seal


housing.

Components:
225LBP Probe kit complete with pin wrench
200LUGBx Standard, long bi-metal lug
200LUGPx ProbeLok lug
200LUGCx All copper lug

To have a bushing insert packaged with the elbow, add ‘BI’ to the end of the part number. For example: 228LEJ45BI.

625SK52 Cold Shrink Cable Seal Kit for JCN cable with an overall diameter of 0.95” to 1.94”
625SK60 Tape Shield Adapter Kit for cable with an overall diameter of 0.83” to 1.95”

C7 Page 16 | July 2019


CATALOG NUMBER ORDERING INFORMATION

Example: Integral seal elbow for 1/0 stranded, 260 mil cable with a test point is: 228LEJ45T

2 2 8 L E

Hubbell Product Prefix

J = Integral Seal* J = Seal Kit


Blank = Without S = Shield Adapter Kit
G = Ground Kit for Integral Seal
*Integral seal only available for size 4 housing Blank = None

Select Housing Code from Column 1 T = Test Point


Blank = Without
Cable Insulation Cable Insulation
Housing Code Range (Inches) Range (mm)
3 0.610 - 0.880 15,5 - 22,4
4 0.800 - 1.140 20,3 - 29,0
5 0.920 -1.310 23,4 - 33,3
1.070 - 1.310 27,2 - 33,3 C = Copper Lug
6 P = ProbeLok Lug
Blank = Without

Select Connector Code from Column 1, or 0 for without Connector

Connector AWG or 15 kV - 175mil 15 kV - 220mil 25 kV - 260mil 35 kV - 345mil 35 kV - 420mil


Code kcmil Stranding (Inches) (Inches) (Inches) (Inches) (Inches)

2 #2 Compact & Solid 0.610 - 0.705 0.700 - 0.800 0.780 - 0.880


#2 Stranded & Compressed 0.635 - 0.730 0.725 - 0.825 0.805 - 0.905
3 #1 Compact & Solid 0.645 - 0.735 0.735 - 0.830 0.805 - 0.905
#1 Stranded & Compressed 0.675 - 0.770 0.765 - 0.855 0.835 - 0.935
4 1/0 Compact & Solid 0.680 - 0.775 0.770 - 0.865 0.835 - 0.940 1.010 - 1.120 1.160 - 1.260
1/0 Stranded & Compressed 0.715 - 0.810 0.805 - 0.905 0.875 - 0.980 1.045 - 1.155 1.190 - 1.130
5 2/0 Compact & Solid 0.715 - 0.815 0.805 - 0.905 0.875 - 0.980 1.045 - 1.160 1.195 - 1.310
6 2/0 Stranded & Compressed 0.760 - 0.855 0.850 - 0.950 0.920 - 1.025 1.090 - 1.200 1.245 - 1.350
3/0 Compact & Solid 0.765 - 0.860 0.855 - 0.955 0.925 - 1.030 1.095 - 1.205
3/0 Stranded & Compressed 0.810 - 0.905 0.900 - 1.000 0.970 - 1.075 1.140 - 1.255
7 4/0 Compact & Solid 0.815 - 0.910 0.905 - 1.005 0.975 - 1.080 1.145 - 1.260
4/0 Stranded & Compressed 0.865 - 0.965 0.955 - 1.060 1.025 - 1.135 1.195 - 1.310
8 250 Compact 0.880 - 0.965 0.970 - 1.060 1.040 - 1.135 1.210 - 1.315
*These ranges are taken from the AEIC/ICEA industry cable standards

C7 Page 17 | July 2019


25/28 kV LOADBREAK INSERTS

The Hubbell Loadbreak Bushing Insert meets all requirements of IEEE Std. 386. It is designed for installation on
transformers, switches or other equipment having a 200 A bushing well that meets the requirements of IEEE Std.
386, Interface 3. When mated with a comparably rated elbow or other accessory, the bushing insert provides a fully
shielded and submersible connection. The bushing insert contains an all-copper current path from the female contact
to the bushing well and internal connection to the switch or transformer.

225BI
Bushing Insert
Internal hex broach accepts a 5/16” wrench for proper
installation torque.

Vented yellow seating indicator ring provides a positive


indication that the mating product is fully installed and
assists in minimizing no-load, partial vacuum flashovers.

228FTI
Feed-thru Insert
Creates a tap position in an existing apparatus

Converts a radial-feed transformer to a loop-feed unit.

Supplied with an auxiliary hold-down bail.

Contains an internal ratchet mechanism to facilitate


proper alignment.

C7 Page 18 | July 2019


Experience
25/28 kV LOADBREAK ACCESSORIES

9U01BEW500
Insulating Cap
Used as a temporary or permanent cover on an energized operating
interface. Standard product has an insulating cuff. The insulating cap
is supplied with a 36-inch long lead for grounding.

228SB
Standoff Bushing
Provides a temporary or permanent parking position for energized
loadbreak elbows. The bracket permits mounting on the apparatus
parking stand.

228FT
Feed-thru - Horizontal Bracket
and
228FTV
Feed-thru - Vertical Bracket

The feed-thru can be used to test, phase, isolate, or ground a cable,


add an arrester at the open point, or by-pass a transformer. The
bracket allows it to be assembled into the apparatus parking stand
with a hotstick.

225TR
Test Rod
Fits into loadbreak bushings, junctions, and other products that
contain a loadbreak interface and is used with test meters to
determine if the circuit is energized or not.

SL150
Silicone Lubricant
Silicone lubricant for all separable connectors. Supplied in a 5.3
oz (150 g.) tube. Sold in cartons of 24 tubes.

C7 Page 19 | July 2019


25/28 kV LOADBREAK GROUNDING ACCESSORIES

225GB
Grounded Bushing
Provides a temporary ground. Contains a fully functioning
loadbreak mechanism and is designed to handle one fault-
close of up to 10,000 A for 10 cycles. Can be installed with a
hotstick.

T6003092
Grounding Bushing with Clamp
This set includes a loadbreak bushing and bronze T6000466
ground clamp connected by a 4-ft. yellow 1/0 cable. A tin-
plated copper connector joins the cable to the bushing. A
threaded copper ferrule connects the cable to the clamp.
Fault current rating for each set: 10,000 A for 10 cycles.

T6002131
Grounding Elbow
Each set includes a yellow elbow, 6 feet of 1/0 copper
grounding cable with yellow jacket, and bronze T6000466
ground clamp. Fault current rating for each set: 10,000 A for
10 cyles.

C6003103
Three-Phase Grounding Elbow Sets for Switches
& Transformers
Each set includes a three-way terminal block assembly, three 6-ft.
lengths of 1/0 copper ground cable with yellow jacket, a bronze
T6000466 ground clamp and three elbows. Fault current rating for
each set: 10,000 A for 10 cycles.

Grounding Component Parts:


200GB6LUG 1-hole copper lug for 1/0 grounding cable (grounding bushing component)
225GBHSG 200 A 25 kV Grounding Bushing Housing
225GEHSG 200 A 25 kV Grounding Elbow Housing
225LBP 200 A 25 kV Loadbreak Probe
200LUGC6 2/0 all copper lug for use with 1/0 grounding cable
200LUGC7 3/0 all copper lug for use with 2/0 grounding cable

C7 Page 20 | July 2019


25/28 kV LOADBREAK JUNCTIONS
JUNCTION SELECTION AND ORDERING

Example: 4-point junction, supplied with a SS bracket is: 228J4B

2 2 8 J

Hubbell Product Prefix

2 = 2 Position
3 = 3 Position
4 = 4 Position

B = With Bracket
U = With U-Straps

JUNCTION DESCRIPTION

Hubbell junctions are used to sectionalize cables or as seating indicator rings provide a positive indication
feed-thrus for making lateral taps. that the mating product is fully installed and assists in
minimizing no-load, partial vacuum flashovers.
They are available in two, three and four tap units and,
when con­nected with loadbreak elbows, have ratings Junctions with the corrosion-resistant stain­less steel
as shown on the 25/28 kV Loadbreak Product Ratings & mounting bracket allow back plate mounting angles of
Specifications sheet. 30, 45, or 60 degrees. This bracket can be adjusted for
horizontal mounting to a flat surface. Junctions can also
Adjacent taps are 4.0” center to center. Vented yellow be ordered with only U-straps for horizontal surface
mounting.

Junction Component Parts:


200JUNCMF Junction Adjustable Mounting Feet Only, Stainless Steel (1 Pair)
228J2BRKT Junction Bracket, Stainless Steel w/Adjustable Feet, 2 Position
228J3BRKT Junction Bracket, Stainless Steel w/Adjustable Feet, 3 Position
228J4BRKT Junction Bracket, Stainless Steel w/Adjustable Feet, 4 Position

Performance
228US1 Junction U-strap, Stainless Steel w/Hardware

C7 Page 21 | July 2019


25/28 kV LOADBREAK JUNCTIONS

Bracket & U-strap Dimensions


Bracket Mounting Angles
Dimension Junction Part Number
228J2B 228J3B 228J4B
X1 23.45 23.45 23.45
X2 6.86 10.86 14.86
B1 6.55 to 10.55 6.55 to 10.55 10.55 to 14.55
B2 11.22 to 15.22 11.22 to 15.22 15.22 to 19.22
B3 15.89 to 19.89 15.89 to 19.89 19.89 to 23.89
B4 16.40 to 20.40 16.40 to 20.40 20.40 to 24.40
B5 21.07 to 25.07 21.07 to 25.07 25.07 to 29.07
B6 25.74 to 29.74 25.74 to 29.74 29.74 to 33.74
Note: Dimensions in Inches

[X1]

.83

U-Strap Dimensions
5.00
3.36
[X2]
.50
[B1] (2) .33 x
.41 Slots
8.13
[B2]
[B2]
[B3]
6.86
Inside Bracket Feet Dimensions
U-Strap Dimensions

[X1]
8.13

10.86

[B4] 8.13

[B5]
[B5]
[B6] 14.86

Outside Bracket Feet Dimensions

C7 Page 22 | July 2019


25/28 kV STACKING DIMENSIONS

25/28 kV Standoff Bushing


228SB

25/28 kV Bushing Insert


25/28 kV Elbow 225BI
228LExx

25/28 kV Feed-Thru
228FT

25/28 kV Junction w/ U-Strap


228JxU
25/28 kV Elbow Arrester
225ELAxx

25/28 kV Feed-Thru Insert


228FTI

25/28 kV Insulating Cap 25/28 kV Junction w/ Bracket


9U01BEW500 228JxB

25/28 kV Parkingstand Arrester


225PLAxx

Overall 25/28 kV Product Stacking Dimensions


Product Product Elbow + Product Elbow + Product Arrester + Product Cap + Product
(E) (A + E) (B + E) (C + E) (D + E)

228SB - 25/28 kV Standoff Bushing 7.85" 12.26" 11.85" 11.77" 11.85"


225BI - 25/28 kV Bushing Insert 5.92" 10.33" 9.92" 9.84" 9.92"
228FT - 25/28 kV Feed-Thru 6.22" 10.63" 10.22" 10.14" 10.22"
228JxU - 25/28 kV Junction w/U-strap 7.62" 12.03" 11.62" 11.54" 11.62"
228FTI - 25/28 kV Feed-Thru Insert 8.60" 13.01" 12.60" 12.52" 12.60"
228JxB - 25/28 kV Junction w/Bracket 8.29" 12.70" 12.29" 12.21" 12.29"
225PLAxx - 25/28 kV Parkingstand Arrester 7.72" 12.13" 11.72" N/A 11.72"

C7 Page 23 | July 2019


15/25/28 kV FUSED ELBOWS

Hubbell Fused Elbows are designed for 15 kV or 25/28 kV applications.


They combine a fully-shielded and insulated loadbreak elbow with full
range current-limiting, non-expulsion fuse protection.

The Hubbell Fused Elbow provides a quick and cost effective solution
for adding fused reliability to underground distribution systems. When
mated with a comparable loadbreak bushing, or other devices with an in-
terface that conforms to IEEE Std. 386, the Hubbell Fused Elbow provides
a fully shielded and submersible connection.

All Hubbell Fused Elbows are designed and tested to meet the require-
ments of IEEE Std. 386.

Accepts Cooper™ or Hi-Tech® fuses


NOTE: All fuses sold separately.

SELECTION & ORDERING INFORMATION


Determine the diameter over the cable’s insulation by finding it in the
manufacturer’s catalog or by measuring it (do not measure over the
extruded semi-con). Select an elbow size so that the insulation falls
within the elbow’s range.

Determine manufacturer of fuse to be used.

Select a connector code that identifies the conductor size and stranding.

The elbow can be supplied with a separate, cold-shrink seal kit for
jacketed concentric neutral cable, or it can be furnished with a separate Cable Dimension Reference
adapter kit for copper tape shield cables.

Components:
625SK52 Cold Shrink Cable Seal Kit for JCN cable with an overall diameter of 0.95” to 1.95”
625SK60 Tape Shield Adapter Range - 0.83” to 1.95”
200FEKITCx To order replacement hardware for installation of a Cooper™ fuse, determine the
connector code using chart on the next page
200FEKITHx To order replacement hardware for installation of a Hi-Tech® fuse, determine the
connector code using chart on the next page

C7 Page 24 | July 2019


CATALOG NUMBER ORDERING INFORMATION

Example: 28 kV Fused elbow using Hi-Tech® fuse for 1/0 stranded 260mil cable is: 228FEHB5

2 F E

15 = 15 kV Voltage Class
28 = 25/28 kV Voltage Class J = Seal Kit
S = Shield Adapter Kit
Blank = Neither
C = Cooper™ Fuse
H = Hi-Tech® Fuse

Select Housing Code from Column 1

Housing Code Cable Insulation Cable Insulation


Range (Inches) Range (mm)
A 0.610 - 0.823 15.5 - 20.9
B 0.720 - 0.985 18.3 - 25.0
B or C
C 0.920 - 1.185 23.4 - 30.1

Select Connector Code from Column 1, or 0 for without Connector

Connector AWG or 15 kV - 175mil 15 kV - 220mil 25 kV - 260mil 35 kV - 345mil


Code kcmil Stranding (Inches) (Inches) (Inches) (Inches)

2 #2 Compact & Solid 0.610 - 0.705 0.700 - 0.800 0.780 - 0.880


#2 Stranded & Compressed 0.635 - 0.730 0.725 - 0.825 0.805 - 0.905
3 #1 Compact & Solid 0.645 - 0.735 0.735 - 0.830 0.805 - 0.905
#1 Stranded & Compressed 0.675 - 0.770 0.765 - 0.855 0.835 - 0.935
4 1/0 Compact & Solid 0.680 - 0.775 0.770 - 0.865 0.835 - 0.940 1.010 - 1.120
1/0 Stranded & Compressed 0.715 - 0.810 0.805 - 0.905 0.875 - 0.980 1.045 - 1.155
5 2/0 Compact & Solid 0.715 - 0.815 0.805 - 0.905 0.875 - 0.980 1.045 - 1.160
6 2/0 Stranded & Compressed 0.760 - 0.855 0.850 - 0.950 0.920 - 1.025 1.090 - 1.200
3/0 Compact & Solid 0.765 - 0.860 0.855 - 0.955 0.925 - 1.030 1.095 - 1.205
3/0 Stranded & Compressed 0.810 - 0.905 0.900 - 1.000 0.970 - 1.075 1.140 - 1.255
7 4/0 Compact & Solid 0.815 - 0.910 0.905 - 1.005 0.975 - 1.080 1.145 - 1.260
4/0 Stranded & Compressed 0.865 - 0.965 0.955 - 1.060 1.025 - 1.135 1.195 - 1.310
8 250 Compact 0.880 - 0.965 0.970 - 1.060 1.040 - 1.135 1.210 - 1.315
*These ranges are taken from the AEIC/ICEA industry cable standards

C7 Page 25 | July 2019


200 A Loadbreak
35 kV PRODUCTS

C7 Page 26 | July 2019


35 kV LOADBREAK PRODUCTS

RATINGS & SPECIFICATIONS


GENERAL INFORMATION
Hubbell 35 kV, 200 A Separable Connectors are fully
shielded, insulated, and submersible products that
provide a means to mate or disconnect cable to RATINGS
switchgear, transformers, or sectionalizing equipment Max. continuous voltage................. 21.1 kV phase-to-ground
on power distribution systems. They are designed for 36.6 kV phase-to-phase
Continuous current.......................... 200 A rms
pad-mounted or subsurface applications, where the
components may be exposed to direct sunlight or
continuously submerged in water up to 6 feet (2m).
SHORT-TIME CURRENT RATINGS
All 35 kV loadbreak elbows are designed and tested to
0.17 seconds duration...................... 10,000 A rms symmetrical
meet or exceed all applicable requirements of IEEE and
3.00 seconds duration...................... 3,500 A rms symmetrical
ANSI, including the following:
IEEE Std. 386 for Separable Connectors (Interface 8)
IEEE Std. 592 for Exposed Semi-conducting Shields
INSULATION WITHSTAND VOLTAGES
ANSI Std. C119.4 for Electrical Connectors
Basic Impulse Level........................... 150 kV crest
(1.2 x 50 µsec. wave)
These devises are suitable for energized loadmake/ 60 Hertz (one minute)..................... 50 kV rms
loadbreak operations when using an 8’ shotgun-type Corona Extinction Voltage.............. 26 kV rms
hot stick on grounded WYE systems(1). They are (5 pC)
also fully interchangeable with other manufacturer’s
products that conform to the electrical requirements of SWITCHING
IEEE Std. 386.
1-phase and 3-phase circuits 10 loadmake/loadbreak
Hubbell 35 kV products are designed for use in 21.1 kV phase-to-ground, operations at 200 A with 70-
ambient temperatures between -40°C and +65°C and 36.6 kV maximum across the 80% lagging power factor.
can be operated energized between -20°C and +65°C. open contacts.
Loadbreak devices should not be operated, while
energized, at elevations over 6,000 feet. FAULT CLOSURE
One fault-close operation at 21.1 kV phase-to-ground, or
All rubber components are manufactured using 36.6 kV phase-to-phase; 10,000 A rms symmetrical, 10 cycles,
peroxide-cured insulating and conductive compounds. (0.17 seconds).

(1) Contact the factory for recommendations for use on PRODUCTION TESTS
ungrounded, resistance grounded, or delta systems. 100% factory test for partial discharge and either AC HI-POT (50 kV
for 60 seconds) or impulse (BIL) (150 kV 1.2 x 50 µsec. wave).

Performance C7 Page 27 | July 2019


35 kV LOADBREAK ELBOWS

HUBBELL 35 kV Loadbreak Elbows are designed and tested


to meet all requirements of IEEE Std. 386. The operating
interface will mate with any product that conforms to
IEEE Std. 386, Interface 8.

Elbows can be supplied with a capacitive test point that


allows for the installation of faulted circuit indicators and
will indicate the presence of voltage when interrogated
with a high-impedance meter.

Bi-metal compression lug meets all requirements of ANSI


Std. C119.4 for Class A connectors.

SELECTION & ORDERING INFORMATION


Cable Dimension Reference
Determine the diameter over the cable’s insulation
by finding it in the manufacturer’s catalog or by
measuring it (do not measure over the extruded
semi-con). Select an elbow size so that the insulation
falls within the elbow’s range.

Select a connector code that identifies the conductor


size and stranding.

The standard long, bi-metal connector can be


replaced with a ProbeLok connector, or an all copper
connector for use on all copper conductor only.

Decide if a capacitive test point is required.

The elbow can be supplied with a separate, cold-shrink seal kit for jacketed concentric neutral cable,
or it can be furnished with a separate adapter kit for copper tape shield cables.

Components:
236LBP Probe kit complete with pin wrench
200LUGBx Standard, long bi-metal lug
200LUGPx ProbeLok lug
200LUGCx All copper lug

625SK52 Cold Shrink Cable Seal Kit for JCN cable with an overall diameter of 0.97” to 1.95”
625SK60 Tape Shield Adapter Range - 0.83” to 1.95”

C7 Page 28 | July 2019


CATALOG NUMBER ORDERING INFORMATION

Example: Loadbreak elbow for 1/0 stranded, 345 mil cable with a test point is: 236LE55T

2 3 6 L E 5

Hubbell Product Prefix


J = Seal Kit
S = Shield Adapter Kit
Blank = Neither

Select Housing Code from Column 1 T = Test Point


Cable Insulation Cable Insulation Blank = Without
Housing Code Range (Inches) Range (mm)
5 1.020 - 1.310 25,9 - 33,3

C = Copper Lug
P = ProbeLok Lug
Blank = Without

Select Connector Code from Column 1, or 0 for without Connector


25kV - 260 mil 35kV-345mil
Connector Code AWG or kcmil Stranding (Inches) (Inches)
4 1/0 Compact & Solid --- 1.010 - 1.120
1/0 Stranded & Compressed --- 1.045 - 1.155
5 2/0 Compact & Solid --- 1.045 - 1.160
2/0 Stranded & Compressed --- 1.090 - 1.200
6
3/0 Compact & Solid --- 1.095 - 1.205
3/0 Stranded & Compressed --- 1.140 - 1.255
7 4/0 Compact & Solid --- 1.145 - 1.260
4/0 Stranded & Compressed 1.025 - 1.135 1.195 - 1.310
8 250 Compact 1.040 - 1.135 1.210 - 1.315

*These ranges are taken from the AEIC/ICEA industry cable standards

C7 Page 29 | July 2019


600 A Deadbreak
15/25/28 kV PRODUCTS

C7 Page 30 | July 2019


15/25/28 kV DEADBREAK PRODUCTS

RATINGS & SPECIFICATIONS


GENERAL INFORMATION
The Hubbell 600 A 25/28 kV Deadbreak T-body RATINGS
offers an easy and reliable method of terminating
Max. continuous voltage................. 16.2 kV phase-to-ground
and splicing main feeder circuits. The Deadbreak 28.0 kV phase-to-phase
T-Body is a fully shielded, molded rubber connector. Continuous current.......................... 600 A rms
(Aluminum components)
The Deadbreak T-body is designed to terminate
power cables with copper or aluminum conductors
SHORT-TIME CURRENT RATINGS
ranging in size from #2 AWG to 1250 kcmil.
0.17 seconds duration...................... 25,000 A rms symmetrical
It may be installed on any 600 A rated apparatus
3.00 seconds duration...................... 10,000 A rms symmetrical
bushing that meets IEEE Std. 386 Interface 11.
Cable adapters accommodate power cable
insulation diameters from 0.530 to 1.935 inches. INSULATION WITHSTAND VOLTAGES
Basic Impulse Level........................... 125 kV crest
The Hubbell Deadbreak T-body has been designed (1.2 x 50 μsec. wave)
and tested to meet the requirement of IEEE 60 Hertz (one minute)..................... 45 kV rms
Std. 386 and IEEE Std. 592. Conformance to Corona Extinction Voltage.............. 21.5 kV rms
these industry standard ensures mechanical and (5 pC)
electrical interchangeability with other products of
manufacturers that are also in conformance with
OVERLOAD CURRENT
these standards.
4 hour rating.................................... 900 A rms

PRODUCTION TESTS
100% factory test for partial discharge and either AC HI-POT
(45 kV for 60 seconds) or impulse (BIL) (125 kV 1.2 x 50 μsec. wave).

Performance C7 Page 31 | July 2019


DEADBREAK BOLTED T-BODY SYSTEM

The Hubbell Power Systems 600 A 25/28 kV rated The T-body can be ordered with or without a capacitive
Deadbreak Bolted T-body System is designed to test point.
terminate medium voltage underground distribution Bolted T-body systems provide an economical means of
cable to switchgear, transformers, sectionalizing terminating cable in applications where the visible open
cabinets and underground distribution vault and ground will be achieved through the use of an
applications. The Bolted T-body system is comprised of a internal switch and viewing window. In addition, it can be
standard 600 A T-body, an unthreaded compression lug, combined with other Bolted T-body kits and/or deadbreak
a cable adapter and a basic insulating plug with cap. junctions to construct a multi-way separable splice.

Bolted T-body
System

THREADED
STUD BASIC INSULATING
INSULATING PLUG
PLUG CAP
INTEGRAL T-BODY
BUSHING

UNTHREADED
COMPRESSION LUG

CABLE ADAPTER

SELECTION & ORDERING INFORMATION Cable Dimension Reference

Determine the diameter over the cable’s insulation


by finding it in the manufacturer’s catalog or by
measuring it (do not measure over the extruded semi-
con). Select a cable adapter so that the insulation falls
within the its range.

Select a connector code that identifies the


conductor size and stranding.

Decide if a capacitive test point is required.

The elbow can be supplied with a separate, cold-


shrink seal kit for jacketed concentric neutral cable,
or it can be furnished with a separate adapter kit
for copper tape shield cables.

C7 Page 32 | July 2019


CATALOG NUMBER ORDERING INFORMATION
Example: The part number for 25/28 kV Bolted Elbow kit for 500 stranded, 260 mil cable with an insulation diameter of 1.415” and a test point is: 625BTLM33T

6 2 5 B T

Hubbell Product Prefix J = Seal Kit


S = Shield Adapter Kit
Blank = Neither

T = Test Point
Select Cable Adapter Code from Column 1 Blank = Without
Cable Adapter Cable Insulation Cable Insulation
Code Range (Inches) Range (mm)
E .530 - .680 13,5 - 17,3
F .640 - .820 16,3 - 20,8
Select Connector Code from Column 1 or 2
G .760 - .950 19,3 - 24,1
H .850 - 1.050 21,6 - 26,7 Shear Bolt
15 kV - 175mil 15 kV - 220mil 25 kV - 260mil 35 kV - 345mil
Connector Connector AWG or (Inches)
J .980 - 1.180 24,9 - 30,0 Code Code kcmil Stranding (Inches) (Inches) (Inches)
K 1.090 - 1.310 27,7 - 33,3 #2 Stranded & Compressed 0.635 - 0.730 0.725 - 0.825
22 #1 Compact & Solid 0.645 - 0.735 0.735 - 0.830
L 1.180 - 1.465 30,0 - 37,2 0.805 - 0.905
#1 Stranded & Compressed 0.675 - 0.770 0.765 - 0.855 0.835 - 0.935
LM 1.280 - 1.430 32,5 - 36,3 23 1/0 Compact & Solid 0.680 - 0.775 0.770 - 0.865 0.835 - 0.940 1.010 - 1.120
1/0 Stranded & Compressed 0.715 - 0.810 0.805 - 0.905 0.875 - 0.980 1.045 - 1.155
M 1.370 - 1.630 34,8 - 41,4 24 2/0 Compact & Solid 0.715 - 0.815 0.805 - 0.905 0.875 - 0.980 1.045 - 1.160
U1
N 1.515 - 1.780 38,5 - 45,2 25 2/0 Stranded & Compressed 0.760 - 0.855 0.850 - 0.950 0.920 - 1.025 1.090 - 1.200
3/0 Compact & Solid 0.765 - 0.860 0.855 - 0.955 0.925 - 1.030 1.095 - 1.205
P 1.725 - 1.935 43,8 - 49,1 3/0 Stranded & Compressed 0.810 - 0.905 0.900 - 1.000 0.970 - 1.075 1.140 - 1.255
26 4/0 Compact & Solid 0.815 - 0.910 0.905 - 1.005 0.975 - 1.080 1.925 - 1.260
27 4/0 Stranded & Compressed 0.865 - 0.965 0.955 - 1.060 1.025 - 1.135 1.195 - 1.310
250 0.880 - 0.965 1.010 - 1.115 1.025 - 1.135 1.210 - 1.315
Deadbreak Bolted Elbow Component Parts:
Compact & Solid
28 250 Stranded & Compressed 0.920 - 1.020 1.010 - 1.115 1.080 - 1.190 1.250 - 1.370
29 350 Compact 0.980 - 1.065 1.070 - 1.155 1.140 - 1.230 1.310 - 1.410
U2
Description Catalog # 30 350 Stranded & Compressed 1.025 - 1.130 1.115 - 1.220 1.185 - 1.295 1.355 - 1.475
T-Body with Test Point 625TBT 32 500 Compact 1.100 - 1.185 1.190 - 1.275 1.260 - 1.350 1.430 - 1.530
500 Stranded & Compressed 1.150 - 1.260 1.240 - 1.355 1.310 - 1.430 1.480 - 1.605
T-Body without Test Point 625TB
33 600 Compact 1.185 - 1.270 1.275 - 1.365 1.345 - 1.440 1.575 - 1.615
35 600 Stranded & Compressed 1.235 - 1.350 1.325 - 1.445 1.395 - 1.520 1.565 - 1.695
Aluminum Insulating Plug 625BIP 700 Compact 1.245 - 1.335 1.335 - 1.430 1.405 - 1.500 1.575 - 1.680
U3
with Cap 36 750 Compact 1.280 - 1.365 1.370 - 1.460 1.440 - 1.535 1.610 - 1.710
700 Stranded & Compressed 1.305 - 1.420 1.395 - 1.515 1.465 - 1.590 1.635 - 1.765
5/8” - 11 UNC Threaded 625SA 38 750 Stranded & Compressed 1.340 - 1.456 1.430 - 1.550 1.500 - 1.625 1.670 - 1.800
900 Compact 1.370 - 1.455 1.460 - 1.550 1.530 - 1.625 1.700 - 1.800
Aluminum Stud
39 800 Stranded & Compressed 1.370 - 1.455 1.460 - 1.580 1.530 - 1.655 1.700 - 1.835
Cable Adapter 625CAx 40 900 Stranded & Compressed 1.430 - 1.550 1.520 - 1.645 1.590 - 1.720 1.760 - 1.895
U4 1000 Compact 1.430 - 1.515 1.520 - 1.610 1.590 - 1.685 1.760 - 1.865
Compression Connector 625LUGxx 41 1000 Stranded & Compressed 1.485 - 1.610 1.575 - 1.705 1.645 - 1.775 1.815 - 1.955

Shear Bolt Connector 625LUGUx


Notes:
Cable Sizing Kit 625CKxxx Connectors can be used for both aluminum and copper cable conductors.
Contact representative for conductors not listed above.

C7 Page 33 | July 2019


DEADBREAK ETP ELBOW TERMINATION SYSTEM

The Hubbell Power Systems 600 A 15 kV or 25/28 kV The ETP system is ideal for applications where a 200 A tap
rated Deadbreak ETP (Elbow Tap Plug) Termination System is desired for test or ground purposes, with the visible open
is designed to terminate medium voltage underground achieved through use of an internal switch and a viewing
distribution cable to switchgear, transformers, window. The ETP is also ideal for adding a 200 A tap to an
sectionalizing cabinets and underground distribution existing 600 A elbow termination.
vault applications. The ETP system is comprised of a
standard 600 A T-body, an unthreaded compression lug, The 200 A loadbreak interface can be either 15 kV or 25/28 kV
a cable adapter and the ETP. The T-body can be ordered rated. This interface allows for live test, visible ground, addition
with or without a capacitive test point. of a 200 A tap, or installation of an elbow arrester to protect your
underground distribution system from voltage surges.

ETP
Elbow Termination System

THREADED
STUD ELBOW INSULATING CAP
TAP PLUG (OPTIONAL)
INTEGRAL
T-BODY
BUSHING

UNTHREADED
COMPRESSION LUG

CABLE ADAPTER

C7 Page 34 | July 2019


CATALOG NUMBER ORDERING INFORMATION
Example: The part number for 25/28 kV ETP kit for 500 stranded, 260 mil cable with an insulation diameter of 1.415” and an insulating cap is: 625ETPLM33C

6 E T P

J = Seal Kit
S = Shield Adapter Kit
Blank = Neither

15 = 15 kV Voltage Class C = 200 A Insulating Cap


25 = 25/28 kV Voltage Class Blank = Without

T = Test Point
Blank = Without
Select Cable Adapter Code from Column 1
Cable Adapter Cable Insulation Cable Insulation
Code Range (Inches) Range (mm)
Select Connector Code from Column 1 or 2
E .530 - .680 13,5 - 17,3
F .640 - .820 16,3 - 20,8 Shear Bolt
Connector Connector AWG or 15 kV - 175mil 15 kV - 220mil 25 kV - 260mil 35 kV - 345mil
G .760 - .950 19,3 - 24,1 Code kcmil Stranding (Inches) (Inches) (Inches) (Inches)
Code
H .850 - 1.050 21,6 - 26,7 #2 Stranded & Compressed 0.635 - 0.730 0.725 - 0.825
J .980 - 1.180 24,9 - 30,0 22 #1 Compact & Solid 0.645 - 0.735 0.735 - 0.830 0.805 - 0.905
K 1.090 - 1.310 27,7 - 33,3 #1 Stranded & Compressed 0.675 - 0.770 0.765 - 0.855 0.835 - 0.935
23 1/0 Compact & Solid 0.680 - 0.775 0.770 - 0.865 0.835 - 0.940 1.010 - 1.120
L 1.180 - 1.465 30,0 - 37,2 24 1/0 Stranded & Compressed 0.715 - 0.810 0.805 - 0.905 0.875 - 0.980 1.045 - 1.155
U1 2/0 Compact & Solid 0.715 - 0.815 0.805 - 0.905 0.875 - 0.980 1.045 - 1.160
LM 1.280 - 1.430 32,5 - 36,3 2/0 Stranded & Compressed 0.760 - 0.855 0.850 - 0.950 0.920 - 1.025 1.090 - 1.200
M 1.370 - 1.630 34,8 - 41,4 25 3/0 Compact & Solid 0.765 - 0.860 0.855 - 0.955 0.925 - 1.030 1.095 - 1.205
1.515 - 1.780 38,5 - 45,2 26 3/0 Stranded & Compressed 0.810 - 0.905 0.900 - 1.000 0.970 - 1.075 1.140 - 1.255
N 4/0 Compact & Solid 0.815 - 0.910 0.905 - 1.005 0.975 - 1.080 1.925 - 1.260
P 1.725 - 1.935 43,8 - 49,1 27 4/0 Stranded & Compressed 0.865 - 0.965 0.955 - 1.060 1.025 - 1.135 1.195 - 1.310
250 Compact & Solid 0.880 - 0.965 1.010 - 1.115 1.025 - 1.135 1.210 - 1.315
28 250 Stranded & Compressed 0.920 - 1.020 1.010 - 1.115 1.080 - 1.190 1.250 - 1.370
Deadbreak ETP Elbow Component Items: U2 29 350 Compact 0.980 - 1.065 1.070 - 1.155 1.140 - 1.230 1.310 - 1.410
30 350 Stranded & Compressed 1.025 - 1.130 1.115 - 1.220 1.185 - 1.295 1.355 - 1.475
Description Catalog # 32 500 Compact 1.100 - 1.185 1.190 - 1.275 1.260 - 1.350 1.430 - 1.530
500 Stranded & Compressed 1.150 - 1.260 1.240 - 1.355 1.310 - 1.430 1.480 - 1.605
T-Body with Test Point 625TBT 33 600 Compact 1.185 - 1.270 1.275 - 1.365 1.345 - 1.440 1.575 - 1.615
T-Body without Test Point 625TB 35 600 Stranded & Compressed 1.235 - 1.350 1.325 - 1.445 1.395 - 1.520 1.565 - 1.695
700 Compact 1.245 - 1.335 1.335 - 1.430 1.405 - 1.500 1.575 - 1.680
15 kV Elbow Tap Plug (ETP) 615ETP U3 36 750 Compact 1.280 - 1.365 1.370 - 1.460 1.440 - 1.535 1.610 - 1.710
700 Stranded & Compressed 1.305 - 1.420 1.395 - 1.515 1.465 - 1.590 1.635 - 1.765
25/28 kV Elbow Tap Plug (ETP) 625ETP 38 750 Stranded & Compressed 1.340 - 1.456 1.430 - 1.550 1.500 - 1.625 1.670 - 1.800
900 Compact 1.370 - 1.455 1.460 - 1.550 1.530 - 1.625 1.700 - 1.800
5/8” - 11 UNC Threaded 625SA 39 800 Stranded & Compressed 1.370 - 1.455 1.460 - 1.580 1.530 - 1.655 1.700 - 1.835
Aluminum Stud 900 Stranded & Compressed 1.430 - 1.550 1.520 - 1.645 1.590 - 1.720 1.760 - 1.895
U4 40 1000 Compact 1.430 - 1.515 1.520 - 1.610 1.590 - 1.685 1.760 - 1.865
15 kV Insulating Cap 215ICI 41 1000 Stranded & Compressed 1.485 - 1.610 1.645 - 1.775 1.815 - 1.955
1.575 - 1.705
25/28 kV Insulating Cap 9U01BEW500
Notes:
Cable Adapter 625CAx Connectors can be used for both aluminum and copper cable conductors.
Contact representative for conductors not listed above.
Compression Connector 625LUGxx
Shear Bolt Connector 625LUGUx
Cable Sizing Kit 625CKxxx

C7 Page 35 | July 2019


DEADBREAK LRTP ELBOW TERMINATION SYSTEM

The Hubbell Power Systems 600 A 15 kV or 25/28 kV The LRTP system is ideal for applications where the
rated Deadbreak LRTP (Loadbreak Reducing Tap Plug) termination will be moved to achieve a visible break and
Termination System is designed to connect medium ground. The integral termination system, T-body and
voltage underground distribution cable to switchgear, LRTP as one unit, makes it easier to install and remove
transformers, sectionalizing cabinets and underground from the mating bushing interface.
distribution vault applications.
The LRTP system uses a threaded compression lug The 200 A loadbreak interface can be either 15 kV
allowing the LRTP to be threaded into the T-body or 25/28 kV rated. This interface allows for live test,
forming an integral termination system. The T-body phasing and visible ground. In addition, it can be used
can be ordered with or without a capacitive test point. to add a tap, or install an elbow arrester to protect your
underground distribution system from voltage surges.

LRTP
Elbow Termination System

INSULATING CAP
T-BODY LOADBREAK
(OPTIONAL)
REDUCING
INTEGRAL TAP PLUG
BUSHING

THREADED
COMPRESSION LUG

CABLE ADAPTER

C7 Page 36 | July 2019


CATALOG NUMBER ORDERING INFORMATION
Example: The part number for 25/28 kV LRTP kit for 500 stranded, 260 mil cable with an insulation diameter of 1.415” and a test point: 625LRTPLM33T

6 L R T P

J = Seal Kit
S = Shield Adapter Kit
Blank = Neither
15 = 15 kV Voltage Class
25 = 25/28 kV Voltage Class C = 200 A Insulating Cap
Blank = Without

T = Test Point
Select Cable Adapter Code from Column 1 Blank = Without
Cable Adapter Cable Insulation Cable Insulation
Code Range (Inches) Range (mm)
Select Connector Code from Column 1
E .530 - .680 13,5 - 17,3
F .640 - .820 16,3 - 20,8 Connector AWG or 15 kV - 175mil 15 kV - 220mil 25 kV - 260mil 35 kV - 345mil
kcmil Stranding (Inches) (Inches) (Inches) (Inches)
G .760 - .950 19,3 - 24,1 Code
H .850 - 1.050 21,6 - 26,7 #2 Stranded & Compressed 0.635 - 0.730 0.725 - 0.825
22 #1 Compact & Solid 0.645 - 0.735 0.735 - 0.830 0.805 - 0.905
J .980 - 1.180 24,9 - 30,0 #1 Stranded & Compressed 0.675 - 0.770 0.765 - 0.855 0.835 - 0.935
K 1.090 - 1.310 27,7 - 33,3 23 1/0 Compact & Solid 0.680 - 0.775 0.770 - 0.865 0.835 - 0.940 1.010 - 1.120
L 1/0 Stranded & Compressed 0.715 - 0.810 0.805 - 0.905 0.875 - 0.980 1.045 - 1.155
1.180 - 1.465 30,0 - 37,2 24 2/0 Compact & Solid 0.715 - 0.815 0.805 - 0.905 0.875 - 0.980 1.045 - 1.160
LM 1.280 - 1.430 32,5 - 36,3 25 2/0 Stranded & Compressed 0.760 - 0.855 0.850 - 0.950 0.920 - 1.025 1.090 - 1.200
3/0 Compact & Solid 0.765 - 0.860 0.855 - 0.955 0.925 - 1.030 1.095 - 1.205
M 1.370 - 1.630 34,8 - 41,4 3/0 Stranded & Compressed 0.810 - 0.905 0.900 - 1.000 0.970 - 1.075 1.140 - 1.255
26 4/0 0.815 - 0.910 0.905 - 1.005 0.975 - 1.080 1.925 - 1.260
N 1.515 - 1.780 38,5 - 45,2 Compact & Solid

27 4/0 Stranded & Compressed 0.865 - 0.965 0.955 - 1.060 1.025 - 1.135 1.195 - 1.310
P 1.725 - 1.935 43,8 - 49,1 250 Compact & Solid 0.880 - 0.965 1.010 - 1.115 1.025 - 1.135 1.210 - 1.315
28 250 Stranded & Compressed 0.920 - 1.020 1.010 - 1.115 1.080 - 1.190 1.250 - 1.370
29 350 Compact 0.980 - 1.065 1.070 - 1.155 1.140 - 1.230 1.310 - 1.410

Deadbreak LRTP Component Items: 30 350 Stranded & Compressed 1.025 - 1.130 1.115 - 1.220 1.185 - 1.295 1.355 - 1.475
32 500 Compact 1.100 - 1.185 1.190 - 1.275 1.260 - 1.350 1.430 - 1.530
500 Stranded & Compressed 1.150 - 1.260 1.240 - 1.355 1.310 - 1.430 1.480 - 1.605
Description Catalog # 33 600 Compact 1.185 - 1.270 1.275 - 1.365 1.345 - 1.440 1.575 - 1.615
T-Body with Test Point 625TBT 35 600 Stranded & Compressed 1.235 - 1.350 1.325 - 1.445 1.395 - 1.520 1.565 - 1.695
700 Compact 1.245 - 1.335 1.335 - 1.430 1.405 - 1.500 1.575 - 1.680
T-Body without Test Point 625TB 36 750 Compact 1.280 - 1.365 1.370 - 1.460 1.440 - 1.535 1.610 - 1.710
700 Stranded & Compressed 1.305 - 1.420 1.395 - 1.515 1.465 - 1.590 1.635 - 1.765
15 kV Loadbreak Reducing Tap 615LRTP 38 750 Stranded & Compressed 1.340 - 1.456 1.430 - 1.550 1.500 - 1.625 1.670 - 1.800
Plug (LRTP) 900 Compact 1.370 - 1.455 1.460 - 1.550 1.530 - 1.625 1.700 - 1.800
39 800 Stranded & Compressed 1.370 - 1.455 1.460 - 1.580 1.530 - 1.655 1.700 - 1.835
25/28 kV Loadbreak Reducing Tap 625LRTP 900 Stranded & Compressed 1.430 - 1.550 1.520 - 1.645 1.590 - 1.720 1.760 - 1.895
Plug (LRTP) 40 1000 Compact 1.430 - 1.515 1.520 - 1.610 1.590 - 1.685 1.760 - 1.865
41 1000 Stranded & Compressed 1.485 - 1.610 1.575 - 1.705 1.645 - 1.775 1.815 - 1.955
15 kV Insulating Cap 215ICI
Notes:
25/28 kV Insulating Cap 9U01BEW500 Connectors can be used for both aluminum and copper cable conductors.
Cable Adapter 625CAx Contact representative for conductors not listed above.

Compression Connector 625LUGxx


Cable Sizing Kit 625CKxxx

C7 Page 37 | July 2019


MODULAR SPLICING KITS

6 2 5 L

Hubbell Product Prefix

1 = 1 Elbow, 2 Insulating Plugs


2 = 2 Elbows, 2 Insulating Plugs, 1 Connecting Plug
3 = 3 Elbows, 2 Insulating Plugs, 2 Connecting Plugs
4 = 4 Elbows, 2 Insulating Plugs, 3 Connecting Plugs

T = Test Point
Blank = Without

The Hubbell 600 A Deadbreak T-body can also be used The basic Catalog Number will be 625L_. By inserting
to splice power cables by connecting multiple T-bodies the splice code, “2” immediately following the “L” in
using other accessory products. the basic catalog number, the catalog number to order
is a 625L2. All “non-size” sensitive components will be
To order a Modular Splicing Kit, simply build your included in the kit when ordering. You must order “size
catalog number using the indicator above. sensitive” components separately.
Compression connectors can be used for both aluminum
To order Hubbell Modular Splicing kits you must first and copper cable conductors.
specify the splicing application by selecting the Splicing
Code that represents your application.

Example: The application requires a separable


connector without test point between two 25/28 kV,
500kcmil power cables. Referring to the chart above,
the splicing code to be used is “2”.

C7 Page 38 | July 2019


15/25/28 kV DEADBREAK ACCESSORIES

625CP
Connecting Plug
The Connecting Plug is exclusively for joining or connecting
two or more 600 A T-bodies or bushing extenders. The
Connecting Plug incorporates a straight through aluminum
bus for the transfer of current between the mating 600 A
T-bodies. To tighten, a 3/8” hex wrench is inserted into
broached holes in each end of bus bar.

625BIP
Basic Insulating Plug
The Basic Insulating Plug is a key component of every Hubbell
600 A Deadbreak T-body Kit and is required to secure the 600 A T-body
in place. The 1” hex located on top of the Basic Insulating Plug doubles
as a means of tightening the T-body on to its mating part and also as a
capacitive test point.

Note: To have the stud included in the kit, add “S” to


the part number. To have the stud pre-installed add
“SP” to the part number.

C7 Page 39 | July 2019


15/25/28 kV DEADBREAK ACCESSORIES

625IC
Insulating Cap

The 600 A Insulating Cap isolates unused 600 A interfaces. It is insu-


lated and fully shielded to provide submersible protection for ener-
gized 15 kV and 25/28 kV deadbreak interfaces. To avoid low-energy
discharge from the outer conductive shield, the 36” long braided lead
wire should be grounded.

625ICSP
Short Insulating Cap
The Short Insulating Cap provides the same function as the standard
625IC but utilizes less space. The stud is also permanently installed.

625BE
Bushing Extender

The bushing extender is used to increase the distance between


the 600 A bushing interface and the 600 A T-body. The
extender is insulated and shielded to protect deadfront integrity.

9_ _BA
Bushing Adapter

The Bushing Adapter provides a means to reduce a 600 A


bushing to a 200 A loadbreak interface. The BA is fault close rated for
10,000 A and complies with IEEE Std. 386. The adapter is fault close
rated for 10,000 A, complies with IEEE Std. 386, and is available in both
15 kV and 25/28 kV ratings.

9 B A

15 = 15 kV Voltage Class
25 = 25/28 kV Voltage Class

C7 Page 40 | July 2019


15/25/28 kV DEADBREAK ACCESSORIES

625SB
Standoff Bushing
The 25/28 kV Standoff Bushing provides a single deadbreak
interface used to isolate and sectionalize an energized cable.
The Standoff Bushing is designed to be installed in the
parking stand mounted on a transformer or other device. A
grounding lug is provided on the bracket for attachment of
a ground wire.

625GB
Grounded Bushing
The 25/28 kV Grounded Bushing provides a single
deadbreak interface used to achieve a visible ground on
de-energized cables.

Note: To have the stud included in the kit, add an “S”


to the part number. To have the stud pre-installed add
an “SP” to the part number.

Deadbreak Components:
625SK52 Cold Shrink Cable Seal Kit for JCN cable
with an overall diameter of 0.97” to 1.95”
625SK53 Cold Shrink Cable Seal Kit for JCN cable
with an overall diameter of 1.25” to 2.65”
625SK60 Tape Shield Adapter Kit for cable with an
overall diameter of 0.83” to 1.95”
625SK61 Tape Shield Adapter Kit for cable with an
overall diameter of 1.25” to 2.65”
625SK62 Tape Shield Adapter Kit for cable with an
overall diameter of 1.63” to 2.67”

C7 Page 41 | July 2019


15/25/28 kV DEADBREAK ACCESSORIES

6_ _ ETP
Elbow Tap Plug
The 600 A Elbow Tap Plug is designed to add a 200 A loadbreak
interface to an existing 600 A deadbreak T-Body. It is ideal for
retrofitting an existing bolted elbow with a 200 A tap or for new
applications. A common application is for testing and grounding 600
A systems. The ETP is fault close rated to 10,000 A, complies with IEEE
Std. 386 and is available in both 15 kV and 25/28 kV ratings.

6 E T P

15 = 15 kV Voltage Class
25 = 25/28 kV Voltage Class

6_ _ LRTP
Loadbreak Reducing Tap Plug

The 600 A Loadbreak Reducing Tap Plug is designed to add a 200 A


loadbreak interface device to an existing 600 A deadbreak
T-Body using a bolted connection. A common application is for
grounding and isolating 600 A systems. The LRTP is fault close rated
to 10,000 A, complies with IEEE Std. 386 and is available in both 15 kV
and 25/28 kV ratings.

6 L R T P

15 = 15 kV Voltage Class
25 = 25/28 kV Voltage Class

C7 Page 42 | July 2019


625CA_
Cable Adapter

Cable Adapter Code Range (Inches) Range (mm)


6 2 5 C A E 0.530 - 0.675 13,5 - 17,3
F 0.640 - 0.820 16,3 - 20,8
G 0.760 - 0.950 19,3 - 24,1
H 0.850 - 1.050 21,6 - 26,7
J 0.980 - 1.180 24,9 - 30,0
K 1.090 - 1.310 27,7 - 33,3
L 1.180 - 1.465 30,0 - 37,2
LM 1.280 - 1.430 32,5 - 36,3
M 1.370 - 1.630 34,8 - 41,4
N 1.515 - 1.780 38,5 - 45,2
P 1.725 - 1.935 43,8 - 49,1

625LUG_ _
Compression/Shear Bolt Connectors
Shear Bolt Connector Concentric
Connector Contact Solid
6 2 5 L U G Code Code Compressed
22 #2 #1
23 #1 1/0
24 1/0 2/0
U1
25 2/0 3/0
26 3/0 4/0
27 4/0 250
28 250 300
29 300 350
U2 30 350 400
31 400 450
32 450 500/550
33 500 600
34 550 650
U3 35 600 700
36 650 750
38 700/750 900
39 800 ---
*Connectors can be used for both aluminum and
40 900 1000
copper cable conductors. U4
41 1000 ---
44 1250 ---

C7 Page 43 | July 2019


25/28 kV DEADBREAK JUNCTIONS
JUNCTION SELECTION AND ORDERING

Example: 4-point junction, supplied with U-straps: 625J4U

6 2 5 J

Hubbell Product Prefix

2 = 2 Position
3 = 3 Position
4 = 4 Position

B = With Bracket
U = With U-straps

JUNCTION DESCRIPTION
Hubbell junctions sectionalize feeders or provide a Junctions are available with a stainless steel mounting
lateral tap. They are available in two, three and four bracket which includes two integral parking stands and
point configurations. a ground lug. Junctions can also be ordered with only
U-straps for surface mounting.
Standard 600 A products contain an aluminum bus
bar and mate with any 15/25/28 kV rated separable
connector.

Junction Component Parts:


625US1 Junction U-strap, Stainless Steel

C7 Page 44 | July 2019


TAPMASTER™ MULTI-POINT JUNCTION

The 25/28 kV TapMaster™ Junction offers a complete change in design approach, addressing the issues of space
savings in vaults and enclosures, mounting flexibility and the flexibility of locating parking stands to accept accessory
products required to operate and maintain a distribution system.

3, 4, 5, or 6 pt junction with any configuration of 600 A interfaces and 200 A wells needed for any project.

Product Features Product Benefits


Hubbell TapMaster™ Multi-Point Junctions are designed The TapMaster™ Junction provides a simple solution
and tested to meet IEEE Std. 386. They are available to taking 200 A taps off a 600 A system with
with three to six positions and are ‘built’ to the user’s increased flexibility to operate and maintain the
specification utilizing any combination of IEEE 200 A distribution system. It eliminates the need to stack
wells and 600 A bushing interfaces. They have all copper 200 A taps on a 600 A T-body. It provides both
an easy method to disconnect a 600 A elbow from
current carrying components.
a junction location without moving 200 A cable
and the flexibility to design a junction location with
TapMaster™ junctions can be surface mounted in provisions for testing and grounding by simply adding
sectionalizing cabinets or are available with a stainless a well location where a standard bushing insert and
steel adjustable bracket for vault wall mounting. insulating cap can be installed for future use. This
location can be used to test and ground without
moving cables or “breaking down” the installation.
It may also be used as an arrester location.

The modular concept allows the user to easily specify


three to six positions with any combinations of 600 A
or 200 A interfaces. An adjustable mounting bracket
permits positioning upward or downward to accept
connecting cables.

C7 Page 45 | July 2019


CATALOG NUMBER ORDERING INFORMATION

6 2 8 T M

Hubbell Product Prefix

6 = ANSI 600 A Interface


2 = ANSI 200 A Well Interface
Blank = Neither B = With Bracket
U = With U-Straps

No. Positions Dimension (A) Dimension (B) Dimension (C)


3 23.0 (584) 21.8 (554) 7.4 (188)
4 27.0 (686) 25.8 (655) 11.4 (290)
5 31.0 (787) 29.8 (757) 15.4 (391)
6 35.0 (889) 33.8 (859) 19.4 (493)

C7 Page 46 | July 2019


STACKING DIMENSIONS
The diagram below shows typical Cable Accessories combinations and includes the dimensions for each part as they
pertain to this diagram. Choose a desired combination and add up the dimensions of each part to obtain the distance
the complete unit would extend from the equipment face plate. Example: A 600 A Standoff Bushing with a 600 A
T-Body and a 15kV Elbow Tap Plug and a 15 kV Elbow Arrester would have a stacking dimension of 16.83 inches (4.46
+ 0.51 + 8.52 + 3.34).

25 kV Basic Insulating Plug 25 kV Standoff Bushing


625BIP 625SB

15 kV Elbow Tap Plug


615ETP
15 kV Elbow Arrester 25 kV Groundoff
215ELAxx Bushing
625GB

15 kV Loadbreak
Reducing Tap Plug
615LRTP
15 kV Insulating Cap
215ICx 600A Deadbreak
25 kV Bushing Extender Junction W/U-Strap
625BE 625JxU

25 kV Elbow Tap Plug


625ETP
25 kV Elbow Arrester
225ELAxx
600A Deadbreak
Junction W/Bracket
625JxB
25 kV Loadbreak
Reducing Tap Plug
625LRTP
25 kV Insulating Cap
9U01BEW500 TapMaster Junction
W/U-Strap
628TMxxxxxxU
25 kV Connecting Plug 25 kV T-Body
625CP 625TB
25 kV Insulating Cap
625IC
TapMaster Junction
25 kV Basic Insulating Cap 25 kV T-Body W/Bracket
625BIP 625TB 628TMxxxxxxB

25 kV Integral
Bushing

C7 Page 47 | July 2019


600 A Deadbreak
35 kV PRODUCTS

C7 Page 48 | July 2019


35 kV DEADBREAK PRODUCTS

RATINGS & SPECIFICATIONS


GENERAL INFORMATION
The Hubbell 600 A 35 kV Deadbreak T-body offers RATINGS
an easy and reliable method of terminating and Max. continuous voltage................. 21.1 kV phase-to-ground
splicing main feeder circuits. The Deadbreak T-Body 36.6 kV phase-to-phase
is a fully shielded, molded rubber connector. Continuous current.......................... 600 A rms
(Aluminum components)
The Deadbreak T-body is designed to terminate
power cables with copper or aluminum conductors
SHORT-TIME CURRENT RATINGS
ranging in size from #2 AWG to 1250 kcmil.
0.17 seconds duration...................... 25,000 A rms symmetrical
It may be installed on any 600 A rated apparatus
3.00 seconds duration...................... 10,000 A rms symmetrical
bushing that meets IEEE Std. 386 Interface 13.
Cable adapters accommodate power cable
insulation diameters from 0.530 to 1.935 inches. INSULATION WITHSTAND VOLTAGES
Basic Impulse Level........................... 150 kV crest
The Hubbell Deadbreak T-body has been designed (1.2 x 50 μsec. wave)
and tested to meet the requirement of IEEE 60 Hertz (one minute)..................... 50 kV rms
Std. 386 and IEEE Std. 592. Conformance to the Corona Extinction Voltage.............. 26 kV rms
industry standards ensures mechanical and electrical (5 pC)
interchangeability with other manufacturer’s
products that are also in conformance with these
OVERLOAD CURRENT
standards.
4 hour rating.................................... 900 A rms

PRODUCTION TESTS
100% factory test for partial discharge and either AC HI-POT
(50 kV for 60 seconds) or impulse (BIL) (150 kV 1.2 x 50 μsec. wave).

Performance C7 Page 49 | July 2019


DEADBREAK BOLTED T-BODY SYSTEM

The Hubbell Power Systems 600 A 35 kV rated a basic insulating plug with cap. The T-body can be
Deadbreak Bolted T-body System is designed to ordered with or without a capacitive test point.
terminate medium voltage underground distribution Bolted T-body systems provide an economical means of
cable to switchgear, transformers, sectionalizing terminating cable in applications where the visible open
cabinets and underground distribution vault and ground will be achieved through the use of an
applications. The Bolted T-body system is comprised of a internal switch and viewing window. In addition, it can be
standard 600 A T-body, an unthreaded compression lug, combined with other Bolted T-body kits and/or deadbreak
a cable adapter and junctions to construct a multi-way separable splice.

Bolted T-body
System

THREADED
STUD BASIC INSULATING
INSULATING PLUG
PLUG CAP
INTEGRAL T-BODY
BUSHING

UNTHREADED
COMPRESSION LUG

CABLE ADAPTER

SELECTION & ORDERING INFORMATION Cable Dimension Reference

Determine the diameter over the cable’s insulation


by finding it in the manufacturer’s catalog or by
measuring it (do not measure over the extruded
semi-con). Select a cable adapter so that the
insulation falls within the its range.

Select a connector code that identifies the


conductor size and stranding.

Decide if a capacitive test point is required.

The elbow can be supplied with a separate, cold-


shrink seal kit for jacketed concentric neutral cable,
or it can be furnished with a separate adapter kit
for copper tape shield cables.

C7 Page 50 | July 2019


CATALOG NUMBER ORDERING INFORMATION
Example: The part number for 35 kV Bolted Elbow kit for 500 stranded, 260 mil cable with an insulation diameter of 1.55” and a test point is: 635BTL33T

6 3 5 B T

Hubbell Product Prefix J = Seal Kit


S = Shield Adapter Kit
Blank = Neither

T = Test Point
Select Cable Adapter Code from Column 1 Blank = Without
Cable Adapter Cable Insulation Cable Insulation
Code Range (Inches) Range (mm)
D .750 - .985 19.05 - 25.0
Select Connector Code from Column 1 or 2
E 0.930 - 1.040 23.6 - 26.4
Shear Bolt Connector AWG 25 kV - 35 kV - 35 kV -
F 980 - 1.115 24.9 - 28.3 Connector or Stranding 260mil 345mil 420mil
Code Code kcmil (Inches) (Inches) (Inches)
G 1.040 - 1.175 26.4 - 29.8
H 1.095 - 1.240 27.8 - 31.5 22 #1 Comp & Sol 0.805 - 0.905

J 1.160-1.305 29.5 - 33.1 #1 Str & Compr 0.835 - 0.935


23
1/0 Comp & Sol 0.835 - 0.940 1.010 - 1.120 1.060 - 1.265
K 1.220-1.375 31.0 - 34.9
1/0 Str & Compr 0.875 - 0.980 1.045 - 1.155 1.185 - 1.305
L 1.285-1.395 32.6 - 35.4 24
2/0 Comp & Sol 0.875 - 0.980 1.045 - 1.160 1.200 - 1.305
M 1.355-1.520 34.4 - 39.0
U1 2/0 Str & Compr 0.920 - 1.025 1.090 - 1.200 1.230 - 1.350
N 1.485-1.595 37.7 - 40.5 25
3/0 Comp & Sol 0.925 - 1.030 1.095 - 1.205 1.245 - 1.355
P 1.530-1.640 38.9 - 41.7 3/0 Str & Compr 0.970 - 1.075 1.140 - 1.255 1.280 - 1.400
26
Q 1.575-1.685 40.0 - 42.8 4/0 Comp & Sol 0.975 - 1.080 1.160 - 1.255 1.300 - 1.405
R 1.665-1.785 42.3 - 45.3 4/0 Str & Compr 1.025 - 1.135 1.195 - 1.310 1.335 - 1.460
27
S 1.755-1.875 45.1 - 47.6 250 Compact & Sol 1.025 - 1.135 1.210 - 1.315 1.350 - 1.475
T 1.845-1.965 46.9 - 50.0 28 250 Str & Compr 1.080 - 1.190 1.250 - 1.370 1.390 - 1.530
29 350 Compact 1.140 - 1.230 1.310 - 1.410 1.450 - 1.570
U 1.935-2.055 49.1 - 52.2 U2
30 350 Str & Compr 1.185 - 1.295 1.355 - 1.475 1.495 - 1.635
V 2.025-2.145 51.4 - 54.5
32 500 Compact 1.260 - 1.350 1.430 - 1.530 1.570 - 1.690
500 Str & Compr 1.310 - 1.430 1.480 - 1.605 1.620 - 1.770
33
Deadbreak Bolted Elbow Component Parts: 600 Comp 1.345 - 1.440 1.575 - 1.615 1.655 - 1.780
600 Str & Compr 1.395 - 1.520 1.565 - 1.695 1.705 - 1.860
Description Catalog # 35
700 Compact 1.405 - 1.500 1.575 - 1.680 1.715 - 1.870
T-Body with Test Point 635TBT U3
36 750 Compact 1.440 - 1.535 1.610 - 1.710 1.750 - 1.875
T-Body without Test Point 635TB 700 Str & Compr 1.465 - 1.590 1.635 - 1.765 1.775 - 1.930
Aluminum Insulating Plug 635BIP 38 750 Str & Compr 1.500 - 1.625 1.670 - 1.800 1.810 - 1.965
with Cap 900 Compact 1.530 - 1.625 1.700 - 1.800 1.840 - 1.965
5/8” - 11 UNC Threaded 635SA 39 800 Str & Compr 1.530 - 1.655 1.700 - 1.835 1.840 - 1.995
Aluminum Stud 900 Str & Compr 1.590 - 1.720 1.760 - 1.895 1.900 - 2.060
40
Cable Adapter 635CAx U4 1000 Compact 1.590 - 1.685 1.760 - 1.865 1.900 - 2.025
Compression Connector 625LUGxx 41 1000 Str & Compr 1.645 - 1.775 1.815 - 1.955 1.955 - 2.115
44 1250 Str & Compr 2.100 - 2.265
Shear Bolt Connector 625LUGUx
Cable Sizing Kit 635CKxxx Notes:
Connectors can be used for both aluminum and copper cable conductors.
Contact representative for conductors not listed above.

C7 Page 51 | July 2019


DEADBREAK ETP ELBOW TERMINATION SYSTEM

The Hubbell Power Systems 600 A 35 kV rated Deadbreak The ETP system is ideal for applications where a 200 A
ETP (Elbow Tap Plug) Termination System is designed to tap is desired for test or ground purposes, with the
terminate medium voltage underground distribution visible open achieved through use of an internal switch
cable to switchgear, transformers, sectionalizing cabinets and a viewing window. The ETP is also ideal for adding a
and underground distribution vault applications. The 200 A tap to an existing 600 A elbow termination.
ETP system is comprised of a standard 600 A T-body, an
unthreaded compression lug, a cable adapter and the The 200 A loadbreak interface can be either 35 kV rated.
ETP. The T-body can be ordered with or without a capaci- This interface allows for live test, visible ground, addition
tive test point. of a 200 A tap, or installation of an elbow arrester to protect
your underground distribution system from voltage surges.

ETP
Elbow Termination System

THREADED
STUD ELBOW INSULATING CAP
TAP PLUG (OPTIONAL)
INTEGRAL
T-BODY
BUSHING

UNTHREADED
COMPRESSION LUG

CABLE ADAPTER

C7 Page 52 | July 2019


CATALOG NUMBER ORDERING INFORMATION
Example: The part number for a 35 kV ETP kit for 500 stranded 345mil cable with an insulation diameter of 1.55” and an insulating cap is: 635ETPN33C

6 3 5 E T P

J = Seal Kit
Hubbell Product Prefix S = Shield Adapter Kit
Blank = Neither

C = 200 A Insulating Cap


Blank = Without

T = Test Point
Blank = Without
Select Cable Adapter Code from Column 1
Cable Adapter Cable Insulation Cable Insulation
Code Range (Inches) Range (mm)
Select Connector Code from Column 1 or 2
D .750 - .985 19.05 - 25.0
Shear Bolt Connector AWG 25 kV - 35 kV - 35 kV -
E 0.930 - 1.040 23.6 - 26.4 Connector or Stranding 260mil 345mil 420mil
Code Code kcmil (Inches) (Inches) (Inches)
F 980 - 1.115 24.9 - 28.3
G 1.040 - 1.175 26.4 - 29.8 22 #1 Comp & Sol 0.805 - 0.905

H 1.095 - 1.240 27.8 - 31.5 #1 Str & Compr 0.835 - 0.935


23
1/0 Comp & Sol 0.835 - 0.940 1.010 - 1.120 1.060 - 1.265
J 1.160-1.305 29.5 - 33.1
1/0 Str & Compr 0.875 - 0.980 1.045 - 1.155 1.185 - 1.305
K 1.220-1.375 31.0 - 34.9 24
2/0 Comp & Sol 0.875 - 0.980 1.045 - 1.160 1.200 - 1.305
L 1.285-1.395 32.6 - 35.4
U1 2/0 Str & Compr 0.920 - 1.025 1.090 - 1.200 1.230 - 1.350
M 1.355-1.520 34.4 - 39.0 25
3/0 Comp & Sol 0.925 - 1.030 1.095 - 1.205 1.245 - 1.355
N 1.485-1.595 37.7 - 40.5 3/0 Str & Compr 0.970 - 1.075 1.140 - 1.255 1.280 - 1.400
26
P 1.530-1.640 38.9 - 41.7 4/0 Comp & Sol 0.975 - 1.080 1.160 - 1.255 1.300 - 1.405
Q 1.575-1.685 40.0 - 42.8 4/0 Str & Compr 1.025 - 1.135 1.195 - 1.310 1.335 - 1.460
27
R 1.665-1.785 42.3 - 45.3 250 Compact & Sol 1.025 - 1.135 1.210 - 1.315 1.350 - 1.475
S 1.755-1.875 45.1 - 47.6 28 250 Str & Compr 1.080 - 1.190 1.250 - 1.370 1.390 - 1.530
29 350 Compact 1.140 - 1.230 1.310 - 1.410 1.450 - 1.570
T 1.845-1.965 46.9 - 50.0 U2
30 350 Str & Compr 1.185 - 1.295 1.355 - 1.475 1.495 - 1.635
U 1.935-2.055 49.1 - 52.2
32 500 Compact 1.260 - 1.350 1.430 - 1.530 1.570 - 1.690
V 2.025-2.145 51.4 - 54.5
500 Str & Compr 1.310 - 1.430 1.480 - 1.605 1.620 - 1.770
33
Deadbreak ETP Elbow Component Items: 600 Comp 1.345 - 1.440 1.575 - 1.615 1.655 - 1.780
600 Str & Compr 1.395 - 1.520 1.565 - 1.695 1.705 - 1.860
35
Description Catalog # 700 Compact 1.405 - 1.500 1.575 - 1.680 1.715 - 1.870
U3
T-Body with Test Point 635TBT 36 750 Compact 1.440 - 1.535 1.610 - 1.710 1.750 - 1.875
T-Body without Test Point 635TB 700 Str & Compr 1.465 - 1.590 1.635 - 1.765 1.775 - 1.930
Elbow Tap Plug (ETP) 635ETP 38 750 Str & Compr 1.500 - 1.625 1.670 - 1.800 1.810 - 1.965
900 Compact 1.530 - 1.625 1.700 - 1.800 1.840 - 1.965
5/8” - 11 UNC Threaded 635SA
Aluminum Stud 39 800 Str & Compr 1.530 - 1.655 1.700 - 1.835 1.840 - 1.995
900 Str & Compr 1.590 - 1.720 1.760 - 1.895 1.900 - 2.060
Insulating Cap 635IC 40
U4 1000 Compact 1.590 - 1.685 1.760 - 1.865 1.900 - 2.025
Cable Adapter 635CAx
41 1000 Str & Compr 1.645 - 1.775 1.815 - 1.955 1.955 - 2.115
Compression Connector 625LUGxx 44 1250 Str & Compr 2.100 - 2.265
Shear Bolt Connector 625LUGUx Notes:
Connectors can be used for both aluminum and copper cable conductors.
Cable Sizing Kit 635CKxxx Contact representative for conductors not listed above.

C7 Page 53 | July 2019


35 KV DEADBREAK ACCESSORIES

635BIP
Basic Insulating Plug
The Basic Insulating Plug is a key component of every Hubbell
600 A Deadbreak T-body Kit and is required to secure the 600 A T-body
in place. The 1” hex located on top of the Basic Insulating Plug doubles
as a means of tightening the T-body on to its mating part and also as a
capacitive test point.

Note: To have the stud included in the kit, add an “S”


to the part number. To have the stud pre-installed add
an “SP” to the part number.

635IC
Insulating Cap

The 600 A Insulating Cap isolates unused 600 A interfaces. It is insu-


lated and fully shielded to provide submersible protection for ener-
gized 35 kV deadbreak interfaces. To avoid low-energy discharge from
the outer conductive shield, the 36” long braided lead wire should be
grounded.

635BE
Bushing Extender

The bushing extender is used to increase the distance between


the 600 A bushing interface and the 600 A T-body. The
extender is insulated and shielded to protect deadfront integrity.

C7 Page 54 | July 2019


35 KV DEADBREAK ACCESSORIES
635ETP
Elbow Tap Plug
The 600 A Elbow Tap Plug is designed to add a 200 A loadbreak
interface to an existing 600 A deadbreak T-Body. It is ideal for
retrofitting an existing bolted elbow with a 200 A tap or for new
applications. A common application is for testing and grounding
600 A systems. The ETP is fault close rated to 10,000 A and
complies with IEEE Std. 386. The 200 A interface is IEEE Std. 386
Interface 7B (the 35kV small interface).

Deadbreak Components:
625SK52 Cold Shrink Cable Seal Kit for JCN cable
with an overall diameter of 0.97” to 1.94”
625SK53 Cold Shrink Cable Seal Kit for JCN cable
with an overall diameter of 1.25” to 2.65”

625SK60 Tape Shield Adapter Kit for cable with an


overall diameter of 0.83” to 1.95”
625SK61 Tape Shield Adapter Kit for cable with an
overall diameter of 1.25” to 2.65”
625SK62 Tape Shield Adapter Kit for cable with an
overall diameter of 1.63” to 3.67”

C7 Page 55 | July 2019


35 KV DEADBREAK ACCESSORIES
635CA_
Cable Adapter

Cable Adapter Code Range (Inches) Range (mm)


6 3 5 C A D 0.750 - 0.985 19.05 - 25.0
E 0.930 - 1.040 23.6 - 26.4
F 0.980 - 1.115 24.9 - 28.3
G 1.040 - 1.175 26.4 - 29.8
H 1.095 - 1.240 27.8 - 31.5
J 1.160 - 1.305 29.5 - 33.1
K 1.220 - 1.375 31.0 - 34.9
L 1.285 - 1.395 32.6 - 35.4
M 1.355 - 1.520 34.4 - 39.0
N 1.485 - 1.595 37.7 - 40.5
P 1.530 - 1.640 38.9 - 41.7
Q 1.575 - 1.685 40.0 - 42.8
R 1.665 - 1.785 42.3 - 45.3
S 1.755 - 1.875 45.1 - 47.6
T 1.845 - 1.965 46.9 - 50.0
U 1.935 - 2.055 49.1 - 52.2
625LUG_ _ V 2.025 - 2.145 51.4 - 54.5
Compression/Shear Bolt Connectors

Shear Bolt Connector Concentric


6 2 5 L U G Connector
Code Code Compressed Contact Solid

22 #2 #1
23 #1 1/0
24 1/0 2/0
U1
25 2/0 3/0
26 3/0 4/0
27 4/0 250
28 250 300
29 300 350
U2 30 350 400
31 400 450
32 450 500/550
33 500 600
34 550 650
U3 35 600 700
36 650 750
38 700/750 900
39 800 ---
*Connectors can be used for both aluminum and
copper cable conductors. 40 900 1000
U4
41 1000 ---
44 1250 ---
C7 Page 56 | July 2019
35 KV DEADBREAK JUNCTIONS
JUNCTION SELECTION AND ORDERING

Example: Example: 4- point junction, supplied with U-straps: 635J4U

6 3 5 J

Hubbell Product Prefix

2 = 2 Position
3 = 3 Position
4 = 4 Position

B = With Bracket
U = With U-straps

JUNCTION DESCRIPTION
Hubbell junctions sectionalize feeders or provide a Junctions are available with a stainless steel mounting
lateral tap. They are available in two, three and four bracket which includes two integral parking stands and
point configurations. a ground lug. Junctions can also be ordered with only
U-straps for surface mounting.
Standard 600 A products contain an aluminum bus bar
and mate with any 35 kV rated separable connector.

Junction Component Parts:


635US1 Junction U-strap, Stainless Steel

C7 Page 57 | July 2019


Underground Arresters
15/25/28/35 kV PRODUCTS

C7 Page 58 | July 2019


UNDERGROUND ARRESTERS

RATINGS & SPECIFICATIONS


GENERAL INFORMATION
Hubbell elbow and parkingstand lightning arresters
Design Tests are gapless, metal oxide varistor (MOV) type surge
High Current, Short 2 discharges of 65 kA Crest arresters. They are designed to provide shielded,
Duration dead-front arrester protection for 15/25/28/35 kV
Low Current, Long 20 Surges of 75 A for underground systems. The arresters limit over-voltages
Duration 2,000 µsec. duration to acceptable levels, protecting equipment and
Operating Duty 22 Operations of 5 kA
extending service life.
Cycle Crest 8 x 20 µsec.
The critical values for parkingstand and elbow
Safe Failure Mode Verify blocks do not
breach sidewall lightning arresters are the discharge voltage (IR)
and the IEEE Std. 386 interface class. In general, the
lower the discharge voltage, the better the protection
Production Tests margin. Hubbell parkingstand and elbow lightning
Polymer Housing Only per IEEE Std. 386 arresters are non-fragmenting.
Partial Discharge Voltage Level (5 pC sensitivity)
Hubbell underground arresters fully conform to the
AC 60 Hz, 1 minute withstand or BIL impulse lightning
safe-failure mode per IEEE Std. C62.11. The standard
withstand requires that should the arrester fail, the blocks will
not be ejected through the body or side wall of the
Periodic Fluoroscope Analysis
housing. The MOV blocks should exit out the bottom,
down and away from equipment.

Production Tests Application:


Complete Unit per IEEE Std. C62.11 Hubbell parkingstand and elbow lightning arresters are
designed to mate with 200 A loadbreak interfaces that
Partial Discharge Voltage Level
(10pC sensitivity) conform to IEEE Std. 386. The parkingstand lightning
arrester contains a defined interface, while the elbow
Reference Voltage
lightning arrester mates with a defined interface.
Power Frequency
A Hubbell arrester installed at the end of a radial
system or at both ends of an open point in a loop
circuit will provide excellent protection against high
voltage surges resulting from lightning or switching.
When combined with an Ohio Brass PVR (Riser Pole)
arrester, optimum protection can be achieved.

60 Hz Temporary Overvoltage Capability with Prior Duty Hubbell arresters are fully shielded and submersible,
(60° C Ambient) either continuously or intermittently, to a depth of 6
feet (2m).

Installation:
Voltage Per Unit MCOV

The Hubbell arrester should be installed utilizing an 8’


shotgun type hotstick.

Performance Characteristics:
Tests were performed in accordance with applicable
sections of IEEE Std. 386 (Separable Insulated
Connector Systems for Power Distribution Systems
Above 600 V) and IEEE Std. C62.11 (Metal Oxide Surge
Arresters for Alternating Current Power Circuits) with
Time Duration - Seconds
test levels chosen that represent typical underground
distribution systems.

C7 Page 59 | July 2019


UNDERGROUND ARRESTERS

COMMON TERMS:
Discharge Voltage: The voltage the arrester
develops while discharging a surge to ground. The
lower the voltage, the better the protection

MCOV: Maximum Continuous Operating Voltage

MOV: Metal Oxide Varistors

TOV: Temporary Over-Voltage

PRODUCT FEATURES:
Pulling Eye provides positive hotstick operation.
The pulling eye strength exceeds 500 lbs of force.

Insulation consists of peroxide-cured EPDM rubber


that offers proven, uncompromised reliability and
dimensional stability.

Molded Shield of conductive peroxide-cured EPDM


rubber meets all requirements of IEEE Std. 592 for
exposed semi-conducting shields.

Drain Wire Tab provides a contact point to attach a


#14 ground wire to ensure the shield is at ground
potential and maintains deadfront construction.

Fiberglass Wrap ensures that the MOV block stack


remains in one piece and prevents the blocks from
breaching the side wall should the arrester fail.

ID Band provides clear visual identification of


arrester MCOV and duty cycle ratings.

Flexible Lead is #4 AWG copper rope lay conductor


595 strand (7 x 85). Ends are soldered to prevent
fraying. Standard length is 36” long. Other lead
lengths are available.

MOV Blocks are the same as used in Ohio Brass


overhead arresters.

C7 Page 60 | July 2019


ARRESTER SELECTION

Normally Recommended MCOV for Various System Voltages


Hubbell Elbow/Parkingstand System L-L Voltage (kV) Arrester MCOV (kV)
Lightning Arrester Selection Impedance
Nominal Maximum Grounded Neutral Grounded or
Ungrounded
Selection of the arrester size is based upon the
2.40 2.54 2.55 2.55
maximum continuous operating voltage (MCOV) line-
4.16 4.37 2.55 5.10
to-ground that is applied across the arrester in service. 4.80 5.04 5.10 5.10
For arresters on effectively grounded systems, this is 6.90 7.26 5.10 7.65
normally the maximum line-to-ground voltage – e.g., 12.00 12.70 7.65 12.70
7.65 kV on a 12.47 kV multi-grounded system. 12.47 13.20 7.65 15.30
13.20 13.97 8.40 15.30
For ungrounded or impedance-grounded systems, the 13.80 14.52 8.40 15.30
MCOV should be at least 90 percent of maximum 20.78 22.00 12.70 22.00
phase-to-phase voltage. Smaller arresters than shown 22.86 24.20 15.30 24.40
may be used; contact your Hubbell Power Systems 23.00 24.34 15.30 24.40
account representative for details. 24.94 26.20 15.30 ---
27.00 28.00 17.00 ---
34.50 36.20 22.00 ---

Protective Characteristics

0.5 µsec Maximum Discharge Voltage (kV Crest)


Catalog MCOV Rating kV 5 kA Max
Number kV 1.5 kA 3.0 kA 5.0 kA 10 kA 20 kA
IR-kV
2_ _ _LA03 2.55 3 12.5 9.8 10.3 11.0 12.3 14.3
2_ _ _LA06 5.1 6 25.0 19.5 20.5 22.0 24.5 28.5
2_ _ _LA09 7.65 9 33.5 26.8 28.0 30.0 33.0 39.0
2_ _ _LA10 8.4 10 36.0 27.0 29.5 31.5 36.0 41.5
2_ _ _LA12 10.2 12 50.0 39.0 41.0 44.0 49.0 57.0
2_ _ _LA15 12.7 15 58.5 45.5 48.5 52.0 57.5 67.5
2_ _ _LA18 15.3 18 67.0 52.0 56.0 60.0 66.0 78.0
2_ _ _LA21 17.0 21 73.0 55.0 60.0 64.0 73.0 84.0
2_ _ _LA24 19.5 24 92.0 71.5 76.5 82.0 90.5 106.5
2_ _ _LA27 22.0 27 100.5 78.0 84.0 90.0 99.0 117.0
2_ _ _LA30 24.4 30 108.0 81.0 88.5 94.5 108.0 131.5

C7 Page 61 | July 2019


15 kV UNDERGROUND ARRESTERS
PRODUCT FEATURES:

Fiberglass Wrap ensures that the MOV block stack remains in one piece and
prevents the blocks from breaching the side wall should the arrester fail.

ID Band provides clear visual identification of arrester MCOV and duty cycle
ratings.

Flexible Lead is #4 AWG copper rope lay conductor 595 strand (7 x 85).
Ends are soldered to prevent fraying. Standard length is 36” long.
Other lead lengths are available.

MOV Blocks are the same as used in Ohio Brass overhead arresters.

Protective Characteristics
Catalog MCOV Rating 0.5 µsec. 5 kA Maximum Discharge Voltage (kV Crest)
Number kV kV Max IR-kV 8x20 µsec. Current Wave
1.5 kA 3.0 kA 5.0 kA 10 kA 20 kA
215_LA03 2.55 3 12.5 9.8 10.3 11 12.3 14.3
215_LA06 5.1 6 25 19.5 20.5 22 24.5 28.5
215_LA09 7.65 9 33.5 26 28 30 33 39
215_LA10 8.4 10 36 27 29.5 31.5 36 41.5
215_LA12 10.2 12 50 39 41 44 49 57
215_LA15 12.7 15 58.5 45.5 48.5 52.0 57.5 67.5
215_LA18 15.3 18 67.0 52.0 56.0 60.0 66.0 78.0

Normally Recommended MCOV for Various System Voltages


System L-L Voltage (kV) Arrester MCOV (kV)
Grounded Impedance Grounded
Nominal Maximum Neutral or Ungrounded
2.40 2.54 2.55 2.55
4.16 4.37 2.55 5.10
4.80 5.04 5.10 5.10
6.90 7.26 5.10 7.65
12.00 12.70 7.65 12.70
12.47 13.20 7.65 15.30
13.20 13.97 8.40 15.30
13.80 14.52 8.40 15.30

Hubbell URD Arrester Selection


Selection of the arrester size is based upon the maximum continuous operating voltage (MCOV) line-to-
ground that is applied across the arrester in service. For arresters on effectively grounded systems, this is
normally the maximum line-to-ground voltage – e.g., 7.65 kV on a 12.47 kV multi-grounded system.

For ungrounded or impedance-grounded systems, the MCOV should be at least 90 percent of maximum
phase-to-phase voltage. If you need assistance with arrester selection, please contact your Hubbell Power
Systems account representative for details.

C7 Page 62 | July 2019


15 kV CATALOG NUMBER ORDERING INFORMATION

Example: Elbow arrester for use on a grounded 13.8 kV L-L system is: 215ELA10

2 1 5 L A

Hubbell Product Prefix

E = Elbow Arrester
P = Parkingstand

Select Rating from Column 1


Rating (kV) MCOV (kV)
03 2.55
06 5.1
09 7.65
10 8.4
12 10.2
15* 12.7 215ELA _ _
18* 15.3
* Not available in Parkingstand Lightning Arrester

ELA Reference Data:


Catalog IEEE Std. 386 MCOV Rated Dimensions Inch (mm) Weight
Number Interface (kV) Voltage (kV) A B C Lbs (kg)
215ELA03 2.55 3
215ELA06 5.1 6
215ELA09 7.65 9 7.4 6.6 2.9 3.7 1.7
15 kV Class
215ELA10 Interface 5 8.4 10 (188) (168) (74)
215ELA12 10.2 12
215ELA15 12.7 15 10.2
215ELA18 15.3 18 5.2 2.4
(259)

PLA Reference Data:


Catalog IEEE Std. 386 MCOV Rated Weight
Number Interface (kV) Voltage (kV) Lbs (kg)

215PLA03 2.55 3
215PLA06 5.1 6
15 kV Class
215PLA09 Interface 5 7.65 9 4.6 (2.09)
215PLA10 8.4 10 215PLA _ _
215PLA12 10.2 12

C7 Page 63 | July 2019


25/28 kV UNDERGROUND ARRESTERS
PRODUCT FEATURES:

Fiberglass Wrap ensures that the MOV block stack remains in one piece and
prevents the blocks from breaching the side wall should the arrester fail.

ID Band provides clear visual identification of arrester MCOV and duty cycle
ratings.

Flexible Lead is #4 AWG copper rope lay conductor 595 strand (7 x 85).
Ends are soldered to prevent fraying. Standard length is 36” long.
Other lead lengths are available.

MOV Blocks are the same as used in Ohio Brass overhead arresters.
Protective Characteristics
Catalog MCOV Rating 0.5 µsec 5 kA Maximum Discharge Voltage (kV Crest)
Number kV kV Max IR-kV 8x20 µsec. Current Wave
1.5 kA 3.0 kA 5.0 kA 10 kA 20 kA
225_LA09 7.65 9 33.5 26 28 30 33 39
225_LA10 8.4 10 36 27 29.5 31.5 36 41.5
225_LA12 10.2 12 50 39 41 44 49 57
225_LA15 12.7 15 58.5 45.5 48.5 52 57.5 67.5
225_LA18 15.3 18 67.0 52 56 60 66 78
225_LA21 17.0 21 73 55 60 64 73 84

Normally Recommended MCOV for Various System Voltages


System L-L Voltage (kV) Arrester MCOV (kV)
Grounded Impedance Grounded
Nominal Maximum Neutral or Ungrounded
6.9 7.26 5.1 7.65
12.0 12.7 7.65 12.7
12.47 13.2 7.65 15.3
13.2 13.97 8.4 15.3
13.8 14.52 8.4 15.3
20.78 22 12.7 22
22.86 24.2 15.3 24.4
23 24.34 15.3 24.4
24.94 26.2 15.3 -
27 28 17 -
34.5 36.2 22 -

Hubbell URD Arrester Selection


Selection of the arrester size is based upon the maximum continuous operating voltage (MCOV) line-to-
ground that is applied across the arrester in service. For arresters on effectively grounded systems, this is
normally the maximum line-to-ground voltage – e.g., 15.3 kV on a 23.0 kV multi-grounded system.

For ungrounded or impedance-grounded systems, the MCOV should be at least 90 percent of maximum
phase-to-phase voltage. If you need assistance with arrester selection, please contact your Hubbell Power
Systems account representative for details.

C7 Page 64 | July 2019


25 kV CATALOG NUMBER ORDERING INFORMATION

Example: Elbow arrester for use on a grounded 23.0 kV L-L system is: 225ELA18

2 2 5 L A

Hubbell Product Prefix


A
E = Elbow Arrester
P = Parkingstand

Select Rating from Column 1


Rating (kV) MCOV (kV) B
09 7.65
10 8.4
12 10.2
15 12.7
18 15.3
225ELA _ _
21 17.0

ELA Reference Data: 8.2"(208)

Catalog IEEE Std. 386 MCOV Rated Dimensions Inch (mm) Weight
Number Interface (kV) Voltage (kV) A B C Lbs (kg)
225ELA09 7.65 9
6.6
225ELA10 8.4 10 3.7 1.7
(168)
225ELA12 25/28 kV Class 10.2 12 7.9 3.1
225ELA15 Interface 7A 12.7 15 (201) (79)
10.2 5.2 2.4
225ELA18 15.3 18
(259) 10.2"(259)
225ELA21 17 21

PLA Reference Data:


Catalog IEEE Std. 386 MCOV Rated Weight
Number Interface (kV) Voltage (kV) Lbs (kg)

225PLA09 7.65 9
225PLA10 8.4 10
225PLA12 25/28 kV Class 10.2 12 4.6 2.09
225PLA15 Interface 7A 12.7 15
225PLA18 15.3 18 225PLA _ _
225PLA21 17 21

C7 Page 65 | July 2019


35 KV SMALL INTERFACE UNDERGROUND ARRESTERS
HUBBELL 35 kV Elbow Arresters are designed and tested to meet all requirements of IEEE Std. 386. The operating
interface will mate with any product that conforms to IEEE Std. 386, Interface 7B.
PRODUCT FEATURES:

Fiberglass Wrap ensures that the MOV block stack remains in one piece and prevents the blocks
from breaching the side wall should the arrester fail.

ID Band provides clear visual identification of arrester MCOV and duty cycle ratings.

Flexible Lead is #4 AWG copper rope lay conductor 595 strand (7 x 85).
Ends are soldered to prevent fraying. Standard length is 36” long.
Other lead lengths are available.

MOV Blocks are the same as used in Ohio Brass overhead arresters.

Protective Characteristics
Catalog MCOV Rating 0.5 µsec. 5 kA Maximum Discharge Voltage (kV Crest)
Number kV kV Max IR-kV 8x20 µsec. Current Wave
1.5 kA 3.0 kA 5.0 kA 10 kA 20 kA
235ELA24 19.5 24 92.0 71.5 76.5 82.0 90.5 106.5
235ELA27 22.0 27 100.5 78.0 84.0 90.0 99.0 117.0
235ELA30 24.4 30 108.0 81.0 88.5 94.5 108.0 124.5

Normally Recommended MCOV for Various System Voltages


System L-L Voltage (kV) Arrester MCOV (kV)
Grounded Impedance Grounded
Nominal Maximum Neutral or Ungrounded
6.9 7.26 5.1 7.65
12.0 12.7 7.65 12.7
12.47 13.2 7.65 15.3
13.2 13.97 8.4 15.3
13.8 14.52 8.4 15.3
20.78 22 12.7 22
22.86 24.2 15.3 24.4
23 24.34 15.3 24.4
24.94 26.2 15.3 -
27 28 17 -
34.5 36.2 22 -

Hubbell URD Arrester Selection


Selection of the arrester size is based upon the maximum continuous operating voltage (MCOV) line-
toground that is applied across the arrester in service. For arresters on effectively grounded systems, this
is normally the maximum line-to-ground voltage – e.g., 22.0 kV on a 34.5 kV multi-grounded system.

For ungrounded or impedance-grounded systems, the MCOV should be at least 90 percent of maximum
phase-to-phase voltage. If you need assistance with arrester selection, please contact your Hubbell Power
Systems account representative for details.

C7 Page 66 | July 2019


35KV SMALL INTERFACE CATALOG NUMBER
ORDERING INFORMATION
Example: Elbow arrester for use on a grounded 34.5 kV L-L system is: 235ELA27

2 3 5 E L A

Hubbell Product Prefix A

Select Rating from Column 1

Rating (kV) MCOV (kV)


24 19.5 B
27 22
30 24.4

235ELA_ _
235ELA _ _

ELA Reference Data:


Catalog IEEE Std. 386 MCOV Rated Dimensions Inch (mm) Weight
Number Interface (kV) Voltage (kV) A B C Lbs (kg)

235ELA24 19.5 24 10.2 (168) 5.2 2.4


35 kV Class 7.9 3.1
235ELA27 22 27 (201) 13.7 (79)
Fig. 7B 6.5 2.9
235ELA30 24.4 30 (348)

Caution
This product is only compatible with a 35 kV small interface, Interface 7B of IEEE Std.
386. It is not compatible with a 35 kV large interface, Interface 8 of IEEE Std. 386.

See next page for 35kV Large Interface Arresters

C7 Page 67 | July 2019


35 KV LARGE INTERFACE UNDERGROUND ARRESTERS
HUBBELL 35 kV Large Interface Elbow Arresters are designed and tested to meet all requirements of IEEE Std. 386.
The operating interface will mate with any product that conforms to IEEE Std. 386, Interface 8.
PRODUCT FEATURES:

Fiberglass Wrap ensures that the MOV block stack remains in one piece and prevents the blocks
from breaching the side wall should the arrester fail.

ID Band provides clear visual identification of arrester MCOV and duty cycle ratings.

Flexible Lead is #4 AWG copper rope lay conductor 595 strand (7 x 85).
Ends are soldered to prevent fraying. Standard length is 36” long.
Other lead lengths are available.

MOV Blocks are the same as used in Ohio Brass overhead arresters.

Protective Characteristics
Catalog MCOV Rating 0.5 µsec. 5 kA Maximum Discharge Voltage (kV Crest)
Number kV kV Max IR-kV 8x20 µsec. Current Wave
1.5 kA 3.0 kA 5.0 kA 10 kA 20 kA 40kA
236ELA27 22.0 27 88 70.8 75.4 80.4 90.5 104.6 130.7
236ELA30 24.4 30 97.8 78.7 83.8 89.3 100.6 116.2 145.2
236ELA33 26.9 33 107.6 86.6 92.2 98.3 110.7 127.9 159.8
236ELA36 29 36 117.4 94.4 100.5 107.2 120.7 139.4 174.3

Normally Recommended MCOV for Various System Voltages


System L-L Voltage (kV) Arrester MCOV (kV)
Grounded Impedance Grounded
Nominal Maximum Neutral or Ungrounded
6.9 7.26 5.1 7.65
12.0 12.7 7.65 12.7
12.47 13.2 7.65 15.3
13.2 13.97 8.4 15.3
13.8 14.52 8.4 15.3
20.78 22 12.7 22
22.86 24.2 15.3 24.4
23 24.34 15.3 24.4
24.94 26.2 15.3 -
27 28 17 -
34.5 36.2 22 -

Hubbell URD Arrester Selection


Selection of the arrester size is based upon the maximum continuous operating voltage (MCOV) line-to-
ground that is applied across the arrester in service. For arresters on effectively grounded systems, this is
normally the maximum line-to-ground voltage – e.g., 22.0 kV on a 34.5 kV multi-grounded system.

For ungrounded or impedance-grounded systems, the MCOV should be at least 90 percent of maximum
phase-to-phase voltage. If you need assistance with arrester selection, please contact your Hubbell Power
Systems account representative for details.

C7 Page 68 | July 2019


35 kV LARGE INTERFACE CATALOG NUMBER
ORDERING INFORMATION
Example: Elbow arrester for use on a grounded 34.5 kV L-L system is: 236ELA27

2 3 6 E L A

Hubbell Product Prefix

Select Rating from Column 1


Rating (kV) MCOV (kV)
27 22
30 24.4
33 26.9
36 29

16

236ELA_ _
235ELA _ _

ELA Reference Data:


Catalog IEEE Std. 386 MCOV Rated Dimensions Inch (mm) Weight
Number Interface (kV) Voltage (kV) A B C Lbs (kg)

236ELA24 19.5 24
236ELA27 22 27
35 kV Class 9.2 13.9 4.0
236ELA30 24.4 30 6.5 2.9
Interface 9 (233 ) (353) (101)
236ELA33 27 33
236ELA36 29 36

Caution
This product is only compatible with a 35 kV large interface, Interface 8 of IEEE Std.
386. It is not compatible with a 35 kV small interface, Interface 7B of IEEE Std. 386.

See previous pages for 35 kV Small Interface Arresters

C7 Page 69 | July 2019


REFERENCE MATERIAL

AEIC/ICEA Cable Std. Concentric Stranded Compressed Stranded Compact Stranded Solid
Insulation
AWG or Voltage Min Dia. Max Dia. Min Dia. Max Dia. Min Dia. Max Dia. Min Dia. Max Dia.
Wall
kcmil Class (kV) (inches) (inches) (inches) (inches) (inches) (inches) (inches) (inches)
Thickness
.175 15 0.645 0.730 0.635 0.720 0.620 0.705 0.610 0.695
.220 15 0.735 0.825 0.725 0.815 0.710 0.800 0.700 0.790
#2
.260 25 --- --- --- --- --- --- --- ---
.345 35 --- --- --- --- --- --- --- ---
.175 15 0.685 0.770 0.675 0.760 0.655 0.735 0.645 0.725
.220 15 0.775 0.865 0.765 0.855 0.745 0.830 0.735 0.820
#1
.260 25 0.845 0.935 0.835 0.925 0.815 0.905 0.805 0.895
.345 35 --- --- --- --- --- --- --- ---
.175 15 0.725 0.810 0.715 0.800 0.690 0.775 0.680 0.760
.220 15 0.815 0.905 0.805 0.895 0.780 0.865 0.770 0.855
1/0
.260 25 0.885 0.980 0.875 0.965 0.850 0.940 0.835 0.925
.345 35 1.055 1.155 1.045 1.145 1.020 1.120 1.010 1.110
.175 15 0.775 0.855 0.760 0.845 0.730 0.815 0.715 0.800
.220 15 0.865 0.950 0.850 0.935 0.820 0.905 0.805 0.895
2/0
.260 25 0.935 1.025 0.920 1.010 0.890 0.980 0.875 0.965
.345 35 1.105 1.200 1.090 1.190 1.060 1.160 1.045 1.145
.175 15 0.825 0.905 0.810 0.895 0.775 0.860 0.765 0.845
.220 15 0.915 1.000 0.900 0.985 0.865 0.955 0.855 0.940
3/0
.260 25 0.985 1.075 0.970 1.060 0.935 1.030 0.925 1.015
.345 35 1.155 1.255 1.140 1.240 1.105 1.205 1.095 1.195
.175 15 0.880 0.965 0.865 0.950 0.830 0.910 0.815 0.895
.220 15 0.970 1.060 0.955 1.045 0.920 1.005 0.905 0.990
4/0
.260 25 1.040 1.135 1.025 1.115 0.990 1.080 0.975 1.065
.345 35 1.210 1.310 1.195 1.295 1.160 1.260 1.145 1.245
.175 15 0.935 1.020 0.920 1.005 0.880 0.965
.220 15 1.025 1.115 1.010 1.100 0.970 1.060
250 --- ---
.260 25 1.095 1.190 1.080 1.175 1.040 1.135
.345 35 1.265 1.370 1.250 1.350 1.210 1.315
.175 15 1.045 1.130 1.025 1.110 0.980 1.065
.220 15 1.135 1.220 1.115 1.200 1.070 1.155
350 --- ---
.260 25 1.205 1.295 1.185 1.275 1.140 1.230
.345 35 1.375 1.475 1.355 1.455 1.310 1.410
.175 15 1.175 1.260 1.150 1.235 1.100 1.185
.220 15 1.265 1.355 1.240 1.330 1.190 1.275
500 --- ---
.260 25 1.335 1.430 1.310 1.405 1.260 1.350
.345 35 1.505 1.605 1.480 1.580 1.430 1.530

C7 Page 70 | July 2019


REFERENCE MATERIAL

AEIC/ICEA Cable Std. Concentric Stranded Compressed Stranded Compact Stranded Solid
AWG or Insulation
Wall Voltage Min Dia. Max Dia. Min Dia. Max Dia. Min Dia. Max Dia. Min Dia. Max Dia.
kcmil Thickness Class (kV) (inches) (inches) (inches) (inches) (inches) (inches) (inches) (inches)
.175 15 1.265 1.350 1.235 1.325 1.185 1.270
.220 15 1.355 1.445 1.325 1.415 1.275 1.365
600 --- ---
.260 25 1.425 1.520 1.395 1.490 1.345 1.440
.345 35 1.595 1.695 1.565 1.670 1.515 1.615
.175 15 1.335 1.420 1.305 1.390 1.245 1.335

.220 15 1.425 1.515 1.395 1.485 1.335 1.430


700 --- ---
.260 25 1.495 1.590 1.465 1.560 1.405 1.500

.345 35 1.665 1.765 1.635 1.740 1.575 1.680

.175 15 1.370 1.455 1.340 1.425 1.280 1.365

.220 15 1.460 1.550 1.430 1.520 1.370 1.460


750 --- ---
.260 25 1.530 1.625 1.500 1.595 1.440 1.535

.345 35 1.700 1.800 1.670 1.770 1.610 1.710

.175 15 1.400 1.490 1.370 1.455 1.310 1.395

.220 15 1.490 1.580 1.460 1.550 1.400 1.490


800 --- ---
.260 25 1.560 1.655 1.530 1.625 1.470 1.565

.345 35 1.730 1.835 1.700 1.805 1.640 1.740

.175 15 1.465 1.550 1.430 1.520 1.370 1.455

.220 15 1.555 1.645 1.520 1.610 1.460 1.550


900 --- ---
.260 25 1.625 1.720 1.590 1.685 1.530 1.625

.345 35 1.795 1.895 1.760 1.865 1.700 1.800

.175 15 1.520 1.610 1.485 1.575 1.430 1.515

.220 15 1.610 1.705 1.575 1.670 1.520 1.610


1000 --- ---
.260 25 1.680 1.775 1.645 1.740 1.590 1.685

.345 35 1.850 1.955 1.815 1.920 1.760 1.865

C7 Page 71 | July 2019


NOTES

C7 Page 72 | July 2019


NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.
©
Copyright 2017 Hubbell Incorporated
CA03022E

Never Compromise TM