Diesel Generating Set BF-C350: Standby Power 50Hz 260KW / 325KVA Prime Power 50Hz 240KW / 300KVA
Diesel Generating Set BF-C350: Standby Power 50Hz 260KW / 325KVA Prime Power 50Hz 240KW / 300KVA
Diesel Generating Set BF-C350: Standby Power 50Hz 260KW / 325KVA Prime Power 50Hz 240KW / 300KVA
MODEL BF-C350
Standby Power(50Hz) 260KW / 325KVA
Prime Power(50Hz) 240KW / 300KVA
Standard Features
General Features:
Engine (CCEC Cummins MTAA11-G3)
Radiator 40OC max, fans are driven by belt, with
safety guard
24V charge alternator
Alternator: single bearing alternator IP23, insulation
class H/H
Absorber
Dry type air filter, double fuel filter, oil filter, coolant
filter
Main line circuit breaker
Standard control panel
Two12V batteries, rack and cable PHOTO FOR REFERENCE ONLY
Ripple flex exhaust pipe, exhaust siphon, flange,
muffler
User manual
Generator Ratings
Standby Prime
P.F Standby
Voltage HZ Phase Ratings Ratings
(COS¢) Amps
(KW/KVA) (KW/KVA)
440/254 50 3 0.8 426 260/325 240/300
415/240 50 3 0.8 452 260/325 240/300
400/230 50 3 0.8 469 260/325 240/300
380/220 50 3 0.8 493 260/325 240/300
Prime Power (PRP): Prime power is available for an unlimited number of annual hours in variable
load application, in accordance with GB/T2820(eqv ISO8528); A 10% overload capability is available for
a period of 1 hour within a 12-hour period of operation.
Standby Power Rating (ESP): The standby power rating is applicable for supplying emergency power
for the duration of a utility power interruption. No overload, utility parallel or negotiated outage operation
capability is available at this rating.
Sales Promises
Baifa Power provides a full line of brand new and high quality products. Each and every unit is strictly
factory tested.
Warranty is according to our standard conditions: a, 15 months, counted on the day BAIFA sold to the
first buyer; b, One year after installation; c, 1000 running hours (accumulated); subject to the earlier one.
Service and parts are available from Baifa Power or distributors in your location.
GENERAL DATA
Compliance with GB755, BS5000, VDE0530, NEMAMG1-22, IED34, CSA C22 and AS1359
standards.
Alternator Data
Number of Phase: 3
Connecting Type: 3 Phase and 4 Wires, “Y” type connecting
Number of Bearing: 1
Power Factor: 0.8
Protection Grade: IP23
Altitude: ≤1000m
Exciter Type: Brushless, self-exciting
Insulation Class, Temperature Rise: H/H
Telephone Influence Factor (TIF): <50
THF: <2%
Alternator Capacity: 300KVA
Alternator Efficiencies: 93.0%
Options
Soundproof Type
Overall Size: 4225×1460×2150(mm)
Weight: 3770kg
Trailer Type
Overall Size: 5030×2440×2880(mm)
Weight: 5130kg