Adl300 Syn FP - en
Adl300 Syn FP - en
Adl300 Syn FP - en
SIEIDrive
synchronous motors
ADL300
.... Functions description
and parameters list
Information about this manual
This manual explains the functions and the description of the parameters.
The informations about mechanical installation, electrical connection and fast start-up can be found on the ADV200 Quick
start guide.
The whole set of manuals (included the expansions and field bus manuals) can be found on the CD provided with the
dirve.
Software version
This manual is updated according the software version V 2.X.0
Variation of the number replacing “X” have no influence on the functionality of thedevice.
The identification number of the software version is indicated on the identification plate of the drive or can be checked with
the PAR 490 Firmware ver.rel parameter, menu 2.5..
General information
Note ! In industry, the terms “Inverter”, “Regulator” and “Drive” are sometimes interchanged. In this document, the term “Drive” will be used.
Before using the product, read the safety instruction section carefully. Keep the manual in a safe place and available to
engineering and installation personnel during the product functioning period.
Gefran S.p.A has the right to modify products, data and dimensions without notice. The data can only be used for the prod-
uct description and they can not be understood as legally stated properties.
Indicates a procedure, condition, or statement that, if not strictly observed, could result in personal injury or death.
Indique le mode d’utilisation, la procédure et la condition d’exploitation. Si ces consignes ne sont passtrictement respec-
Warning
tées, il y a des risques de blessures corporelles ou de mort.
Indicates a procedure, condition, or statement that, if not strictly observed, could result in damage to or destruction of
equipment.
Caution Indique et le mode d’utilisation, la procédure et la condition d’exploitation. Si ces consignes ne sont pas strictement res-
pectées, il y a des risques de détérioration ou de destruction des appareils.
Indicates that the presence of electrostatic discharge could damage the appliance. When handling the boards, always
wear a grounded bracelet.
Indique que la présence de décharges électrostatiques est susceptible d’endommager l’appareil. Toujours porter un brace-
let de mise à la terre lors de la manipulation des cartes.
Indicates a procedure, condition, or statement that should be strictly followed in order to optimize these applications.
Indique le mode d’utilisation, la procédure et la condition d’exploitation. Ces consignes doivent êtrerigoureusement respec-
Attention
tées pour optimiser ces applications.
Note! If asynchronous motor control is selected, use the ADL300 Description of functions and list of parameters – Vector inverter for lifts with asyn-
chronous motors manual
Function block
Parameter
Practical example
The following examples illustrate the philosophies and methods with which more or less complex operations are performed
in the single “function blocks”, the results of which represent the output of the block.
* -1
Terminal input Analog input 1X Block Analog input 1X mon
* +1
+1
Ramp ref 1 src Ramp Setpoint Block Ramp ref 1 mon
-1
The diagrams above illustrate the internal processing philosophy of the single “function blocks” and the result of these
changes on the other interconnected “function blocks”.
Note ! This section contains a brief description of the functions of the other parameters in the function blocks not included for the changes in the
example.
The Ramp ref invert src parameter (PAR: 616) can be used to select the source for the command to reverse the “Ramp
setpoint” function block output.
The output signal from the “Ramp setpoint” block is displayed in the Ramp ref 1 mon parameter (PAR: 620).
Legend
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Accessibility :
Indexing of the menu and parameter
E Expert
Parameter identifier
R Read
Parameter description S
W
Size (set value depending on the size of the device)
Write (scrittura)
UM: unit of measure Z parameters that can be modified ONLY with the drive disabled
1.1 250 Output current A FLOAT 16/32BIT 0.0 0.0 0.0 R F__
The drive output current is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.2 252 Output voltage V FLOAT 16/32BIT 0.0 0.0 0.0 R F__
The drive line voltage output is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.3 254 Output frequency Hz FLOAT 16/32BIT 0.0 0.0 0.0 R F__
The drive output frequency is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.7 270 DC link voltage V FLOAT 16/32BIT 0.0 0.0 0.0 ER F__
The direct voltage of the intermediate circuit capacitors is displayed (DC-Bus).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.9 280 Torque current ref A FLOAT 16/32BIT 0.0 0.0 0.0 ER F__
The current reference used for torque control is displayed (in the sensorless vector and field-oriented vector modes).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.10 282 Magnet current ref A FLOAT 16/32BIT 0.0 0.0 0.0 ER F__
The magnetizing current reference is displayed (in the sensorless vector and field-oriented vector modes).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.11 284 Torque current A FLOAT 16/32BIT 0.0 0.0 0.0 ER F__
The actual torque current value is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1.12 286 Magnet current A FLOAT 16/32BIT 0.0 0.0 0.0 ER F__
The actual magnetizing current value is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1 Input enabled.
0 Input disabled.
Example:
0 0 0 0 0 0 0 0 0 0 1 1
Enable
DI 1
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1 Output enabled.
0 Output disabled.
Example:
0 0 0 0 0 0 0 0 0 0 1 1
DO 1
DO 2
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
2.6 488 Drive cont current A FLOAT CALCF 0.0 0.0 RZS F__
The current that the drive can deliver continuously according to size, supply voltage and programmed switching frequency
is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
2.11 510 Time drive power on h.min UINT32 0 0.0 0.0 ER F__
The total time for which the drive has been powered is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
2.12 512 Time drive enable h.min UINT32 0 0.0 0.0 ER F__
The time for which the enable hardware contact on the drive has been connected is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Note! See Appendix to the Quick start guide for further information on the expansion cards.
SLOT 3 indicates the presence of the CAN on the regulation card in versions ADL300-...-C
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
In the field oriented vector mode (Flux vector CL/ Synchronous) an encoder is required for closed loop feedback. With
this mode it is possible to achieve extremely high dynamic responses thanks to the regulation bandwidth, maximum torque
even with the rotor blocked, speed and torque control. Numerous regulation parameters can be used to adjust the drive to
each specific application, for instance adaptive gains, system inertia compensation, etc..
If the Startup wizard procedure is not used, self-tuning of the motor parameters is possible in the self-tuning mode (Autotune).
This procedure must be used for both self-tuning with the engine standing still and with the motor turning.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
0 Easy
1 Expert
The Easy mode gives access to a list of parameters that can be used for rapid drive commissioning. This type of configu-
ration is suitable for the majority of applications.
Setting the parameter to Expert gives access to all the parameters in the firmware. This mode allows an extremely high
level of customization to be achieved in order to exploit the potential of the ADL300 to the full.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
The drive is supplied already incorporating a number of applications developed in the IEC 61331-3 environment. To use
these, configure the desired application, run save parameter, switch the drive off and then on again. In the default configu-
ration the drive starts with the EFC lift application (see menu 5 - LIFT for the description of this application).
Note! The Load Default command (par. 580) does not modify this parameter
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4.6 560 Mains voltage V ENUM 400 V SIZE SIZE ERWZS F__
Setting of the available mains voltage value in Volts. Detection of the undervoltage alarm refers to this value.
0 200 V
1 230 V
2 380 V
3 400 V
4 415 V
5 440 V
6 460 V
7 480 V
8 575 V
9 690 V
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Note! The Load Default command (par. 580) does not modify this parameter.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Note! Important: the default parameters including the LIFT application are reloaded.
This can only be done with the drive disabled.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
When the unit of measure is modified the conversion constants are re-calculated, the units of measure are changed in the
parameter list and the multispeed values are converted into the new unit of measure (the result may contain approxima-
tions due to the conversion calculations).
A variable representing the speed of the cabin in m/s (fpm) is always available (PAR 12210).
There are fixed units of measure for the acceleration and deceleration parameters m/s² (ft/s2), and for jerks m/s³ (ft/s3).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.1.2 11020 Multi speed 0 m/s FLOAT 0.10 -10000 10000 RW F__
Setting of the multispeed 0 value. Can be selected via digital input, fieldbus, etc.
The selected value is the reference for the S-shaped lift ramp.
This setting is taken as the default low speed value.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.1.3 11022 Multi speed 1 m/s FLOAT 1.00 -10000 10000 RW F__
Setting of the multispeed 1 value. Can be selected via digital input, fieldbus, etc.
The selected value is the reference for the S-shaped lift ramp.
This setting is taken as the default high speed value.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.1.4 11024 Multi speed 2 m/s FLOAT 0.40 -10000 10000 RW F__
Setting of the multispeed 2 value. Can be selected via digital input, fieldbus, etc.
The selected value is the reference for the S-shaped lift ramp.
This setting is taken as the default maintenance speed value.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.1.5 11026 Multi speed 3 m/s FLOAT 0.00 -10000 10000 RW F__
Setting of the multispeed 3 value. Can be selected via digital input, fieldbus, etc.
The selected value is the reference for the S-shaped lift ramp.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.1.6 11028 Multi speed 4 m/s FLOAT 0.00 -10000 10000 RW F__
Setting of the multispeed 4 value. Can be selected via digital input, fieldbus, etc.
The selected value is the reference for the S-shaped lift ramp.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.1.7 11030 Multi speed 5 m/s FLOAT 0.00 -10000 10000 RW F__
Setting of the multispeed 5 value. Can be selected via digital input, fieldbus, etc.
The selected value is the reference for the S-shaped lift ramp.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.1.8 11032 Multi speed 6 m/s FLOAT 0.00 -10000 10000 RW F__
Setting of the multispeed 6 value. Can be selected via digital input, fieldbus, etc.
The selected value is the reference for the S-shaped lift ramp.
5.1.9 11034 Multi speed 7 m/s FLOAT 0.00 -10000 10000 RW F__
Setting of the multispeed 7 value. Can be selected via digital input, fieldbus, etc.
The selected value is the reference for the S-shaped lift ramp.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Acceleration Deceleration
The Acc ini Jerk, Acceleration and Acc end jerk values used to execute the acceleration ramp are calculated by multiplying the cor-
responding parameters by the acceleration ramp factor (Percent acc factor), while the Dec ini jerk, Deceleration and Dec end jerk
values used to execute the deceleration ramp are calculated by multiplying the corresponding parameters by the deceleration ramp
factor (Percent dec factor, PAR 11056).
When the Start command is removed, the reference speed is zero regardless of the reference selected in the multispeeds. In this fi-
nal part of the profile the jerk deceleration values are used directly (not multiplied by Percent dec factor, PAR 11056) with the Stop
deceleration parameter as the linear deceleration. The factors for the final section of the profile are also used in case of a Stop lift
emergency condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.2.1 11040 Acc ini Jerk m/s³ FLOAT 0.50 0.01 20 RW F__
Setting of the jerk value for the first part of the acceleration.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.2.3 11044 Acc end jerk m/s³ FLOAT 1.40 0.01 20 RW F__
Setting of the jerk value for the last part of the acceleration.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.2.4 11046 Dec ini jerk m/s³ FLOAT 1.40 0.01 20 RW F__
Setting of the jerk value for the first part of the deceleration.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.2.6 11050 Dec end jerk m/s³ FLOAT 0.50 0.01 20 RW F__
Setting of the jerk value for the last part of the deceleration.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.2.8 11054 Percent acc factor Perc FLOAT 100.00 10 10000 RW F__
Setting of the acceleration factor multiplier.
If set to 100 the ramp uses the factors entered in the parameters.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.2.9 11056 Percent dec factor Perc FLOAT 100.00 10 10000 RW F__
Setting of the deceleration factor multiplier.
If set to 100 the ramp uses the factors entered in the parameters.
If set to a value of less than 100 the lift will tend to decelerate over a longer distance.
If set to a value of more than 100 the lift will tend to decelerate over a shorter distance.
Enable
PLC TO DRIVE SIGNALS
Start fwd /
Start rev
Mlt spd s 0
Mlt spd s 1
Mlt spd s 2
Acceleration Deceleration
Start Fw / Rw
Start magnet.
Open contac.
Running
Close contac
Close brake
Open brake
Wait 0 ref
Starting sequence:
1 Reading of the enable hardware input and checking for alarms (enabling is aborted in case of an alarm)
2 Detection of the Enable and Start commands as set in the Sequence start mode parameter
3 When the Start forward/reverse command is received, a command is sent to close the contactors, depending on the
direction of travel
4 When the time set in Cont close delay has elapsed the internal Enable lift signal is activated
5 The system waits for the magnetisation signal from the drive (Drive ready)
6 At the end of magnetisation the open brake signal is activated
Sequence of movement:
1 The motor is started and moves slowly at the speed set in Smooth start speed for the time indicated in Smooth start
delay
2 At the end of Smooth start delay, movements are managed by the multispeeds and S-shaped ramp
3 When the set speed is exceeded, the Brake 2 mon output signal can be used to check that the brake has actually been
opened
4 The EFC function with space control can be used to change to a slower speed
5 When the Start forward/reverse signal is lowered the signal indicating arrival at the floor is enabled and the start lift
signal is disabled
6 The start command can be sent again until the drive reaches zero speed: the operating conditions are restored.
Stopping sequence:
1 When zero speed is reached the DC stop command is enabled (SSC control)
2 The application waits the time needed to reach zero speed and sends the command to close brakes 1 and 2
3 It waits the time necessary for the brakes to close (Brake close delay) and, if the current is to be reduced with a ramp, it
waits for the current limit to reach zero. The internal Enable lift, arrival zone and DC brake signals are then lowered.
4 The application waits the time set in Contactor open delay and checks that the current supplied is zero, before sending
a command to open the contactors.
It is essential to make sure that whenever a drive alarm condition is generated or the drive is disabled, the drive is stopped
and a command is sent to open the contactors.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
If set to 0 the contactor sequences can be enabled without the Enable command (Enable is only required for motor opera-
tion). The Enable signal can be sent by an auxiliary contact of the output contactors.
If set to 1 the contactor sequences can only be enabled if the Enable command is active.
If set to 2 the contactor sequences can be enabled using the multispeed values. Multispeed values other than 0 cause the
sequence to start. The start command must also be enabled.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
If set to 1 the soft speed is automatically selected after the start command regardless of the selected multispeed. The
duration of the smooth speed depends on the Smooth start delay parameter: if this parameter is set to zero the selected
multispeed is used and not the soft speed. This setting is used in systems with a reducer, as it helps to overcome initial
friction before starting with the profile.
If set to 2 an even slower starting mode is set, which uses the start jerk of the variable acceleration in the smooth start
phase. Depending on the values set in Smooth start speed and Smooth start delay the jerk value is calculated at the
end of the soft start phase with a linear ramp that changes this jerk from 0 to the calculated value.
The use of a variable value jerk obtains a variable start acceleration that follows a parabolic trajectory, enabling extremely
reduced variations in initial speed. This setting is mainly used in systems with gearless motors.
0
Speed ref
Time
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Mechanical constants
The mechanical constant defines the ratio between motor rpm and distance travelled by the cabin.
The ConstMech can be calculated in two ways, depending on which conversion method is used.
Pulley diameter
Motor Gearbox
Pulley
Car weight
Load weight
Counter weight
The mechanical constant is calculated when the drive is turned on and re-calculated each time one of the parameters used to deter-
mine this value is modified (Mechanical calc mode, Full scale speed, Contract speed, Pulley diameter, Gearbox ratio).
The method used to calculate the mechanical constant can be selected regardless of the control mode (SSC, Flux vector OL, Flux
vector CL, Synchronous) or the unit of measure to be used.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
High Speed
Speed Limit
d1
d2
If the slow down sensor is met during acceleration, the distance required to terminate the acceleration and deceleration phases may
be greater than the distance available: in that case the last acceleration jerk is increased to enable correct landing.
d1 Distance
disabled d1
Piano corto (Short Floor) Piano standard (Standard Floor)
Also note that when the position sensor is not enabled in the landing zone, its exact length is not known. To ensure correct decel-
eration this distance is estimated on the basis of the value entered in the Landing zone dist parameter.
When this is equal to zero the distance is calculated on the basis of the value of the low speed and deceleration parameters and
shown in the Landing zone space parameter. The user should make sure this distance is approximately the real length of the land-
ing zone.
In FOC mode the distance is calculated by reading the encoder position.
In the SSC and SLS modes the distance is estimated (SpdRef*Time) and is thus subject to errors due to the difference between the
real speed of the motor and the speed reference.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Lift car
Slow distance
Landing distance
Floor level
Landing sensor
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
When mode 0 (Autoselect) is selected, Slow speed is automatically connected to the multispeed with absolute value of
less and other than zero. If repositioning speeds with a value of less than the Slow speed are used, the multispeed cor-
responding to the floor approach speed must be set.
When mode 9 (Null) is selected the floor approach spaces are never controlled. In this case the profile depends exclu-
sively on the multispeed selected.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
0 Off
1 On
Given the solution that has been selected to calculate the speed profile, before enabling the landing zone function it is im-
portant to verify the exactness of the spaces that have been entered (for both slow down and landing), and of the mechani-
cal constants. Incorrect spaces could result in sudden decelerations and errors in arrival at floor level.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
0 OFF
1 ON
Speed
High speed
Case 1
Case 2
Slow speed Close to Slow Down
Speed
Case 3
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
PAR 11142
Calc space speed
Case 1
PAR 12032
Deceleration space
Time
Deceleration space (PAR 12032) the distance covered during the stop ramp from Calc space hi-speed (PAR 11142)
(high speed) to zero speed.
The parameters that influence the calculation of this distance are: Calc space hi-speed (PAR 11142), Percent dec factor
(PAR 11056), Dec ini jerk (PAR 11046), Deceleration (PAR 11048) and Dec end jerk (PAR 11050).
Speed
PAR 11142
Calc space speed
Case 2
PAR 12032
Deceleration space = A+B
PAR 11020
Slow speed PAR 11052
End deceleration
Time
●● Case 2: S-shaped ramp from high to low speed, low speed zone and subsequent stop
Distance multispeed0 (PAR 11102) = 0, Enable landing sel (PAR 11130) = Disabled, Slow speed (PAR 11120) = Multi-
speed 0.
Deceleration space (PAR 12032) is the distance covered during the slow down ramp from Calc space hi-speed (PAR
11142) (high speed) to Multispeed 0 and during the stop ramp from Calc space hi-speed (PAR 11142) to zero speed. It
does not include the distance covered at constant speed (Low speed).
The parameters that influence the calculation of this distance are: Calc space hi-speed (PAR 11142), [11022] Multispeed
0 (PAR 11020), Percent dec factor (PAR 11056), Dec ini jerk (PAR 11046), Deceleration (PAR 11048), Dec end jerk
(PAR 11050) and Stop deceleration (PAR 11052).
Speed
PAR 11142
Calc space speed
Case 3
PAR 12032
Deceleration space = A+B
PAR 11020
Slow speed
PAR 11052
End deceleration
Time
●● Case 3: S-shaped ramp from high to low speed, low speed zone and subsequent stop
Distance multispeed0 (PAR 11102) ≠ 0 (es.0.5m), Enable landing sel (PAR 11130) = Disabled, Slow speed (PAR
11120) = Multispeed 0.
Deceleration space (PAR 12032) is the distance covered during the slow down ramp from Calc space hi-speed (PAR
11142) to Multispeed 0 and during the stop ramp from Calc space hi-speed (PAR 11142) to zero speed. It does not
include the distance covered at constant speed (Low speed).
The parameters that influence the calculation of this distance are: Calc space hi-speed (PAR 11142), [11022] Multispeed 0
(11020), Percent dec factor (PAR 11056), Dec ini jerk (PAR 11046), Deceleration (PAR 11048) and Dec end jerk (PAR 11050).
PAR 11142
Calc space speed
Case 4
PAR 12032
Deceleration space = A+Landing zone dist
PAR 11132
Landing zone dist
Time
●● Case 4: S-shaped ramp from high to low speed, low speed zone and subsequent stop with “landing control”
Distance multispeed0 (PAR 11102) ≠ 0 (es.0.5m), Enable landing sel (PAR 11130) = Enabled, Slow speed (PAR
11120) = Multispeed 0.
Deceleration space (PAR 12032) is the distance covered during the slow down ramp from Calc space hi-speed (PAR
11142) (high speed) to Multispeed 0 plus Landing zone dist (PAR 11132).
The parameters that influence the calculation of this distance are: Calc space hi-speed (PAR 11142), [11022] Multispeed
0 (PAR 11020), Percent dec factor (PAR 11056), Dec ini jerk (PAR 11046), Deceleration (PAR 11048) and Dec end jerk
(PAR 11050)
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.6.1 11260 Speed emergency mode m/s FLOAT 5.00 3.40E+94 3.40E+94 RW F__
Setting of the speed during movements in the emergency operation condition. Given the low voltage, high speeds cannot
be reached with the drive powered by battery (or emergency module). The speed selected in the multispeed parameter is
therefore ignored and this value is used instead.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Outputs
The output signals of the lift control are connected directly to the PAD parameters as shown in the table below:
These can be accessed from the selection lists and can thus easily be used to configure the relay and digital outputs of the drive.
(refer to the PADS menu for configuration).
The set of lift output signals is contained in the LiftStatusWord, connected to PAR 3720 Lift status word and fieldbus Tx DW1:
5.7.1 11220 Lift enable cmd sel ENUM 1110 0 35 ERW F__
Setting of the source for the enable command.
1110 Digit input E
1210 Digit input 1x
1212 Digit input 2x
1214 Digit input 3x
1216 Digit input 4x
1218 Digit input 5x
1220 Digit input 6x
1222 Digit input 7x
1224 Digit input 8x
1226 Digit input 9x
1228 Digit input 10x
1230 Digit input 11x
1232 Digit input 12x
3702 Run cont mon
3706 Down cont mon
3708 Brake cont mon
3714 Door open mon
3728 PAD 15
6000 Null
6002 One
12250 B0 Lift decomp
12252 B1 Lift decomp
12254 B2 Lift decomp
12256 B3 Lift decomp
12258 B4 Lift decomp
12260 B5 Lift decomp
12262 B6 Lift decomp
12264 B7 Lift decomp
12266 B8 Lift decomp
12268 B9 Lift decomp
12270 B10 Lift decomp
12272 B11 Lift decomp
12274 B12 Lift decomp
12276 B13 Lift decomp
12278 B14 Lift decomp
12280 B15 Lift decomp
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.7.2 11222 Start fwd cmd sel ENUM 1210 0 35 ERW F__
Setting of the source for the start forward command.
1110 Digit input E
1210 Digit input 1x
1212 Digit input 2x
1214 Digit input 3x
1216 Digit input 4x
1218 Digit input 5x
1220 Digit input 6x
1222 Digit input 7x
1224 Digit input 8x
1226 Digit input 9x
1228 Digit input 10x
1230 Digit input 11x
1232 Digit input 12x
3702 Run cont mon
3706 Down cont mon
3708 Brake cont mon
3714 Door open mon
3728 PAD 15
6000 Null
6002 One
12250 B0 Lift decomp
12252 B1 Lift decomp
12254 B2 Lift decomp
12256 B3 Lift decomp
12258 B4 Lift decomp
12260 B5 Lift decomp
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.7.3 11224 Start rev cmd sel ENUM 1212 0 35 ERW F__
Setting of the source for the start reverse command.
1110 Digit input E
1210 Digit input 1x
1212 Digit input 2x
1214 Digit input 3x
1216 Digit input 4x
1218 Digit input 5x
1220 Digit input 6x
1222 Digit input 7x
1224 Digit input 8x
1226 Digit input 9x
1228 Digit input 10x
1230 Digit input 11x
1232 Digit input 12x
3702 Run cont mon
3706 Down cont mon
3708 Brake cont mon
3714 Door open mon
3728 PAD 15
6000 Null
6002 One
12250 B0 Lift decomp
12252 B1 Lift decomp
12254 B2 Lift decomp
12256 B3 Lift decomp
12258 B4 Lift decomp
12260 B5 Lift decomp
12262 B6 Lift decomp
12264 B7 Lift decomp
12266 B8 Lift decomp
12268 B9 Lift decomp
12270 B10 Lift decomp
12272 B11 Lift decomp
12274 B12 Lift decomp
12276 B13 Lift decomp
12278 B14 Lift decomp
12280 B15 Lift decomp
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Ramp
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
All alarms are associated with a parameter to configure the action taken when the alarm is activated.
Activity: used to set the action to be performed after activation of the alarm, as follows.
Action
Ignore The alarm is not included in the alarm list, it is not included in the alarm log, it is not signalled on the
digital outputs, commands to the drive are not modified.
Warning The alarm is included in the alarm list, it is included in the alarm log, it is signalled on the digital
outputs, First alarm information is updated, Enabled alarms information is updated, commands to the
drive are not modified.
Disable The alarm is included in the alarm list, it is included in the alarm log, it is signalled on the digital out-
puts, First alarm information is updated, Enabled alarms information is updated, a stop command is
sent, the motor is disabled and stops due to inertia.
Fast Stop The alarm is included in the alarm list, it is included in the alarm log, it is signalled on the digital
outputs, First alarm information is updated, Enabled alarms information is updated, a Stop command
is sent. The drive is set to zero speed with the maximum available current; when the Speed 0 delay
signal is activated the drive is disabled.
Lift Fast stop When there is an alarm occurrence, lift will be stopped (ramp reference is set to zero) immediately
with fast ramp, after that it will remain in alarm state. Attention: this will cause the cabin to stop out of
floor !
Lift stop When there is an alarm occurrence, lift will continue to run until next stop condition, after that it will
remain in alarm state.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.9.1 11058 Lift fast stop fact FLOAT 10.00 1.00 50.00 RW FVS
This parameter is applied to all ramps when a “Quick stop” alarm occurs.
The default setting is 10 = 1000% (standard ramps multiplied by 10).
To use standard ramps with no multiplication, set 1 = 100%.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Speed
Door open speed
Door
Hold
off
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.9.12 11264 Lift EF al activity ENUM 5 0 5 RW FVS
Setting of the “Lift external fault” alarm.
0 Ignora
1 Avvisa
2 Disabilita
3 Fast stop
4 Lift fast stop
5 Arresto lift
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.9.13 11266 Lift EF hold off ms LONG 1000 0 60000 RW FVS
Maintaining the “Life external fault” alarm.
“Lift EF” is displayed when a “Lift external fault” alarm occurs.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.9.14 11268 Reset Brake Alarm Short 0 - - RW FVS
Resets the Brake Alarm.
1. Open menu 5.9 LIFT ALARMS, and check that the Brake Alarm is on.
2. In the lift alarm menu, select parameter 11268 Reset Brake Alarm (default 0).
3. The system asks for a code, enter release code 5313.
4. Check again to see whether the Brake Alarm has been reset.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
5.9.15 11270 Threshold A3 Float 0.100 0.000 2.000 RW FVS
When the brake is connected, the Brake fault alarm is activated if the movement (in metres) is more than the value set in
parameter 11270 Threshold A3.
7-
8-
9-
Note ! These menues are not available.
0 Off
1 On
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
11.01 1410 Dig output 1X src LINK 16BIT 1062 0 16384 ERW F__
11.02 1412 Dig output 2X src LINK 16BIT 3708 0 16384 ERW F__
11.03 1414 Dig output 3X src LINK 16BIT 3702 0 16384 ERW F__
11.04 1416 Dig output 4X src LINK 16BIT 3714 0 16384 ERW F__
11.05 1418 Dig output 5X src LINK 16BIT 1062 0 16384 ERW F__
11.06 1420 Dig output 6X src LINK 16BIT 3708 0 16384 ERW F__
11.07 1422 Dig output 7X src LINK 16BIT 3702 0 16384 ERW F__
11.08 1424 Dig output 8X src LINK 16BIT 3714 0 16384 ERW F__
The destination associated with the digital input of the expansion card is displayed. The functions that can be associated
with the digital outputs are listed in the “L_DIGSEL1” selection list”.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Note ! These parameters are only available with cards provided with analog inputs.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Select option 0 in order to connect a maximum voltage of ±12.5V (typically ±10V/5mA) to the analog input concerned. If the
signal is used as a reference, reverse the direction of rotation by inverting the voltage polarity.
Select option 1 to connect a max voltage of 12.5V (typically 10V/5mA) or a signal in current from 0 ... 20 mA to the analog
input concerned. The signal must be positive.
Select option 2 to connect a current signal of 4...20 mA to the analog input concerned. The signal must be positive.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
12.3 1604 Analog inp 1X scale FLOAT 1.0 -10.0 10.0 ERW F__
12.15 1654 Analog inp 2X scale FLOAT 1.0 -10.0 10.0 ERW F__
Setting of a multiplier factor to be applied to the relative analog input of the expansion card.
Speed
100%
0
5V 10V
Example :
The speed reference of a drive is assigned with a max external voltage of 5V. With this value the drive must reach the
maximum speed allowed (set using Full scale speed).
As the Analog inp XX scale parameter the scale factor of 2 is entered (10V : 5V)
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
NOTE! The value that is obtained automatically can be changed manually, if necessary, using An inp offset xX.
If the voltage setting on the analog input is more than 1V the “Input value too high” message is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Self-tuning command for the relative analog input gain. Automatic fine tuning of the input. When this command is sent, An
inp XX gain tune is automatically selected so that the available input signal corresponds to the maximum value of the vari-
able.
Two conditions are necessary in order to perform automatic tuning:
- Input voltage greater than 1V or input current greater than 2 mA
- Positive polarity. The value that is found is automatically accepted for the other direction of rotation.
Note! If necessary, the value obtained automatically can be changed manually via An inp XX gain tune.
To perform self-tuning, set the input signal to its maximum value and execute the command. A multiplier factor is calculated
to apply to the input signal value (not considering the Analog inp scale parameter) to reach the full scale value.
If the voltage setting on the analog input is less than 1V the “Input value too low” message is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
12.7 1612 Analog inp 1X top cnt INT16 16384 -32768 +32767 ERW FVS
12.19 1662 Analog inp 2X top cnt INT16 16384 -32768 +32767 ERW FVS
Setting of the upper speed reference limit as a function of the voltage (or current) of the relative analog reference of the
expansion card.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
12.8 1614 Analog inp 1X bottom cnt INT16 -16384 -32768 +32767 ERW FVS
12.20 1664 Analog inp 2X bottom cnt INT16 -16384 -32768 +32767 ERW FVS
Setting of the lower speed reference limit as a function of the voltage (or current) of the relative analog reference of the
expansion card.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
12.9 1616 Analog inp 1X offset cnt INT16 0 -32768 +32767 ERW FVS
12.21 1666 Analog inp 2X offset cnt INT16 0 -32768 +32767 ERW FVS
PAR 1604 = 1
PAR 1616
AnInp Terminal
0 10V
100%
Setting of an offset value to algebrically add to the relative analog input of the expansion card.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
12.10 1618 Analog inp 1X gain FLOAT 1.0 -10.0 10.0 ERW FVS
12.22 1668 Analog inp 2X gain FLOAT 1.0 -10.0 10.0 ERW FVS
This parameter contains the value of the multiplier factor to apply to the analog reference of the expansion card calculated
using the Analog inp gain tune function.
Example :
An external analog reference only reaches a maximum of 9.8V instead of 10V. 1.020 (10V : 9.8V) is entered as the Analog
inp x gain parameter.
The same result can be achieved using the Analog inp x gain tune function. This parameter can be selected from the
keypad menu. The maximum analog value available (in this case 9.8V) must be present on the terminal, with positive
polarity. Press the Enter key on the keypad to start analog reference self-tuning.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
12.11 1626 An inp 1X sign src LINK 16BIT 6000 0 16384 ERW FVS
12.23 1676 An inp 2X sign src LINK 16BIT 6000 0 16384 ERW FVS
Selection of the origin (source) of the signal to be assigned to the relative digital input of the expansion card for selecting
the direction of rotation of the motor. The functions that can be associated with the digital outputs are listed in the “L_DIG-
SEL2” selection list”.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Note ! These parameters are only available with cards provided with analog outputs.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
13.1 1850 Analog out 1X src LINK 16/32BIT 6000 0 16384 ERW F__
13.2 1852 Analog out 2X src LINK 16/32BIT 6000 0 16384 ERW F__
Selection of the origin (source) of the signals that can be placed as variables on the analog outputs of the expansion card.
The functions that can be assigned to the analog outputs are listed in the “L_ANOUT” selection list”.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
13.3 1858 Analog out 1X scale FLOAT 1.0 -10.0 10.0 ERW F__
13.4 1860 Analog out 2X scale FLOAT 1.0 -10.0 10.0 ERW F__
Parameter for setting a multiplier factor of the signal of the relative analog output of the expansion card. It can be used to
amplify or reduce the input value of the relative analog output block.
+10V
1 Par. 1856 (1860) = 1
0V
Internal V
-10V
To display the drive speed, use an analog instrument with field of measurement from 0 ... 2V. This means that, to display
the speed of the drive, a voltage of 2V on the analog output of the drive must correspond to the maximum speed. With a
scale factor of 1 this would be 10V (Scale factor = 2V / 10 V = 0.200).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
13.9 1882 Analog out 1X min cnt INT16 -16384 -32768 +32767 ERW F__
13.10 1884 Analog out 1X max cnt INT16 -16384 -32768 +32767 ERW F__
Setting of the minimum and maximum values for the analog output for the voltage present on analog output 1 of the expan-
sion card.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
13.11 1890 Analog out 2X min cnt INT16 -16384 -32768 +32767 ERW F__
13.12 1892 Analog out 2X max cnt INT16 16384 -32768 +32767 ERW F__
Setting of the minimum and maximum values for the analog output in current or voltage present on analog output 2 of the
expansion card.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Select option 0 to apply a signal in current of 0 ... 20 mA to analog output 2. The signal must be positive.
Select option 1 to apply a signal in current of 4...20 mA to analog output 2.
Select option 2 to apply a maximum voltage of ±12.5V (typically ±10V/5mA) to analog output 2.
Made in ..............
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.1 2000 Rated voltage V FLOAT SIZE 50.0 690.0 RWZS F__
Set the motor rated voltage as indicated on the data plate. This is the voltage the drive must supply
at the motor rated frequency.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.2 2002 Rated current A FLOAT SIZE 1.0 1500.0 RWZS F__
The motor rated current at its rated power (kW / Hp) and voltage (indicated on the motor data plate).
If using a single drive to control several motors connected in parallel (only possible in the SSC mode), enter a value that
corresponds to the sum of the rated currents of all the motors; in this case do not perform any “self-tuning operations”.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.3 2004 Rated speed rpm FLOAT SIZE 10.0 32000.0 RWZS F__
Rated speed of the motor with full load in rpm (rpm = m-1).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.5 2010 Torque constant Nm/A FLOAT SIZE 0.1 120.0 RWZS F__
Setting of the ratio between the torque generated and the rated current of the motor.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.6 2012 EMF constant Wb FLOAT SIZE 0.0 100.0 RWZS F__
Setting of the electromotive force constant, which represents the ratio between the motor voltage and its rated speed (this
can be calculated by dividing the torque constant by √3)
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
The parameter displays the Required message when the motor parameters that have been entered need to be saved.
When they have been saved the parameter indicates Done.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.11 2050 Measured Rs ohm FLOAT CALCF 0.001 200.0 ERWS F__
Measured value of the rotor resistance.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.12 2052 Measured DTL V FLOAT 0.0 0.0 100.0 ERWS F__
Measured value of dead time compensation.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.13 2054 Measured DTS V/A FLOAT 0.0 0.0 100.0 ERWS F__
Measured compensation gradient value.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.14 2056 Measured Lsig mH FLOAT CALCF 0.1 200.0 ERWS F__
Measured leakage inductance value.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Note! Data are not saved permanently. Use the “Save Parameters” command in the DRIVE CONFIG menu to save in the permanent memory.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.1 2100 Encoder pulses ppr UINT16 1024 128 16384 RWZ F__
Setting of the number of feedback encoder impulses. During setup, for incremental sinusoidal encoders + absolute EnDat
and Hiperface encoders this value is set automatically by reading the number of incremental encoder impulses.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.2 2102 Encoder supply V FLOAT 5.2 5.2 CALCF ERWZ F__
Setting of the encoder supply voltage supplied by the relative optional card. Min and max values are modified according to
the type of encoder card applied.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
This parameter is automatically set to HTL when the value set in the Encoder supply parameter is more than 6.0V.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.5 2108 Encoder signal Vpp V FLOAT 1 0.8 1.2 ERWZ F__
Setting of the peak-to-peak voltage value of the encoder signal. Incremental sinusoidal encoders and absolute SinCos
encoders normally produce signals with a peak-to-peak voltage of 1 Vpp. Due to loss of voltage along the cable, the value
of the peak-to-peak voltage signal received by the feedback card could be lower, generating a Speed fbk loss alarm.
This parameter can be used to set the peak-to-peak voltage value of the incremental sinusoidal encoders and absolute
SinCos encoders on the input terminals of the feedback card.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.6 2110 Encoder signal check ENUM Check A-B 0 3 ERWZ F__
Configuration of which incremental digital encoder channels are to be controlled in order to process the Speed fbk loss
alarm signal.
0 Check disabled
1 Check A-B
2 Check A-B-Z
3 Controll A-B-Z-P
Set 1 to check for signal on channels A-B
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
According to international standards, positive references are associated with clockwise motor rotation, seen from the con-
trol side (shaft). To ensure correct operation, the regulation algorithms ensure that positive speed references correspond to
positive speed measurements.
If the motor pulley is mounted on the side opposite the command side, it will turn in an anticlockwise direction when the
speed is positive: to make the pulley turn in a clockwise direction, the motor phase sequence is modified, which inverts
the speed measurement sign. To restore the correct speed measurement sign, invert the incremental encoder A+ and A-
signals and the absolute encoder Sin+ and Sin- signals on the encoder connections. The absolute part cannot be inverted
with Endat and Hiperface absolute encoders.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.10 2132 Encoder mode ENUM Sinus SINCOS CALCI CALCI ERWZ F__
ADL300B: The drive has an integrated encoder card (SinCos & Incremental TTL Encoder). The encoder mode can be
selected in accordance with the following table:
0 None
1 Digital FP
2 Digital F
3 Sinus SINCOS (Default)
Nota: There is no need to restart the drive when the mode is changed.
ADL300A: the drive supports different types of encoder cards. The mode can only be selected if an incremental digital
encoder card is used. If an EN/SSI encoder card is used, the mode is automatically set by the drive in accordance with the
type of encoder detected. For all other encoder cards, the mode is set in accordance with the card used. The modes are
listed in the following table:
Encoder Card
0 None
1 Digital FP EXP-DE-I1R1F2-ADL
2 Digital F (Default) EXP-DE-I1R1F2-AD
3 Sinus EXP-SE-I1R1F2-ADL
4 Sinus SINCOS EXP-SESC-I1R1F2-ADL
5 Sinus ENDAT EXP-EN/SSI-I1R1F2-ADL (*)
6 Sinus SSI
7 Sinus HIPER EXP-HIP-I1R1F2-ADL
(*) The card automatically selects the correct mode in relation to the encoder type.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
15.11 2134 Encoder speed filter ms FLOAT 2.0 0.1 20.0 ERW F__
Setting of the time constant of the filter applied to the feedback encoder pulse reading. The parameter affects both the
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
10..15 Free
16..31 Depends on the encoder
For further details reference should be made to the description of the Speed fbk loss alarm and to the SFL alarms chapter
according to the type of feedback.
Note ! For the correct interpretation of the cause of the alarm trigger, it is necessary to transform the hex code indicated in parameter 15.13 SpdFbk-
Loss code, PAR 2172 , in the corresponding binary and verify in the encoder table that the active bits and related description are used.
Example with encoder Endat:
PAR 2172 = A0H (hex value)
In the table “Speed fbk loss [22] alarm with absolute encoder EnDat” A0 is not indicated in the value column.
A0 should be contemplated as a bitword with meaning A0 -> 10100000 -> bit 5 and bit 7 . The following causes simultaneously intervene:
Bit 5 = 20H Cause: the SSI signal interferences cause an error in the CKS or parity
Bit 7 = 80H Cause: The encoder has detected an incorrect operation and communicates it to the converter through the Error bit. Bits 16..31
present the type of incorrect encoder operation detected.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
This function can only be used with absolute encoders and the default, minimum and maximum values are modified ac-
cording to the type of encoder.
Note ! See section A3.2 of the Appendix to the Quick start guide for further information.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Note ! See section A3.2 of the Appendix to the Quick start guide for further information.
Note ! Current, flux and voltage regulators can be set using the self-tuning procedure. If this is not successful, current and flux regulators can be tuned
manually (this does not apply to voltage regulators, whch must not be modified by the user). The speed regulator must be tuned manually.
Gains are usually adjusted according to the drive speed.
Total gains used by the speed regulator are calculated as shown in the following examples. Results are in engineering units:
Speed reg P1 gain (PAR 2200)
Total proportional gain = * Speed reg P gain (PAR 2236)
100%
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.1 2200 Speed reg P1 gain perc INT16 100 0 1000 RW F__
Setting of the proportional gain of the speed regulator, set 1.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.2 2202 Speed reg I1 gain perc INT16 100 0 1000 RW F__
Setting of the integral gain of the speed regulator, set 1. Increasing the proportional gain value increases the proportional
action of the regulator
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.3 2204 Speed reg P2 gain perc INT16 100 0 1000 RW F__
Setting of the proportional gain of the speed regulator, set 2.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.4 2206 Speed reg I2 gain perc INT16 100 0 1000 RW F__
Setting of the integral gain of the speed regulator, set 2. Increasing the proportional gain value increases the proportional
action of the regulator
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.5 2208 Speed reg P3 gain perc INT16 100 0 1000 ERW F__
Setting of the proportional gain of the speed regulator, set 3.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.6 2210 Speed reg I3 gain perc INT16 100 0 1000 ERW F__
Setting of the integral gain of the speed regulator, set 3. Increasing the proportional gain value increases the proportional
action of the regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.7 2228 Speed reg P0 gain perc INT16 100 0 1000 ERW F__
Setting of the proportional gain of the speed regulator at zero speed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.8 2230 Speed reg I0 gain perc INT16 100 0 1000 ERW F__
Setting of the integral gain of the speed regulator at zero speed. Increasing the proportional gain value increases the pro-
portional action of the regulator
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.9 2218 Gain adp spd thr2_1 perc FLOAT 10.0 0.0 100.0 ERW F__
Setting of the speed threshold for changing gains from set 1 to set 2.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.10 2220 Gain adp spd band2_1 perc FLOAT 5.0 0.0 100.0 ERW F__
Setting of the band within which gains vary between set 1 and set 2. The use of this parameter ensures a smooth transition
between the two parameter sets.
16.11 2222 Gain adp spd thr3_2 perc FLOAT 0.0 0.0 100.0 ERW F__
Setting of the speed threshold for changing gains from set 3 to set 2.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.12 2224 Gain adp spd band3_2 perc FLOAT 0.0 0.0 100.0 ERW F__
Setting of the band within which gains vary between set 3 and set 2. The use of this parameter ensures a smooth transition
between the two parameter sets.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.13 2246 Gain adp spd thr0_2 perc FLOAT 0.0 0.0 100.0 ERW F__
Setting of the speed threshold for changing gains from set 0 to set 2.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.14 2248 Gain adp spd band0_2 perc FLOAT 0.0 0.0 100.0 ERW F__
Setting of the band within which gains vary between set 0 and set 2. The use of this parameter ensures a smooth transition
between the two parameter sets.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
PAR 2200 %
Speed reg P1 gain
PAR 2202 %
Speed reg I1 gain
Speed reference
Gain
PAR 2220
Gain adp spd band2_1 (%)
PAR 2204
Speed reg P2 gain (%)
PAR 2200
Speed reg P1 gain (%)
Speed ref
PAR 2206
Speed reg I2 gain (%)
PAR 2202
Speed reg I1 gain (%)
Speed ref
0
PAR 2218
Gain adp spd thr2_1 (%)
PAR 2208
Speed reg P3 gain (%)
PAR 2204
Speed reg P2 gain (%)
PAR 2200
Speed reg P1 gain (%)
Speed ref
PAR 2210
Speed reg I3 gain (%)
PAR 2206
Speed reg I2 gain (%)
PAR 2202
Speed reg I1 gain (%)
Speed ref
0
PAR 2222 PAR 2218
Gain adp spd thr3_2 (%) Gain adp spd thr2_1 (%)
PAR 2224
_ _
Gain adp spd band3_2 (%)
PAR 2220
_
Gain adp spd band2_1 (%)
PAR 2228
Speed reg P0 gain (%)
PAR 2204
Speed reg P2 gain (%)
PAR 2200
Speed reg P1 gain (%)
PAR 2208
Speed reg P3 gain (%)
PAR 2230
Speed reg I0 gain (%)
PAR 2206
Speed reg I2 gain (%)
PAR 2202
Speed reg I1 gain (%)
PAR 2210
Speed reg I3 gain (%)
Speed ref
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.16 2232 Spd reg P gain Inuse perc INT16 16/32BIT 100 0 1000 ER F__
The current proportional coefficient of the speed regulator is displayed as a percentage.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.17 2234 Spd reg I gain Inuse perc INT16 16/32BIT 100 0 1000 ER F__
The current integral coefficient of the speed regulator is displayed as a percentage.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.18 2236 Speed reg P gain N/rpm FLOAT CALCF 0.0 500.0 ERWS F__
Setting of the proportional coefficient of the speed regulator.
16.19 2238 Speed reg I time ms FLOAT CALCF 1.0 5000.0 ERWS F__
Setting of the integral coefficient of the speed regulator. Reducing the integral time value increases the integral action of
the regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.20 2240 Inertia kgm2 FLOAT SIZE 0.001 100.0 RWZS F__
Setting of total inertia of the application with reference to the motor shaft. When this parameter is modified, all speed regu-
lator gains are initialised according to the value specified by parameter PAR 2242. An increase in the dynamic response of
the speed regulator to a variation in the reference, can be modified by changing the current value during the acceleration/
deceleration phase, to counter the applied machine inertia.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
16.21 2242 Bandwidth rad/s FLOAT SIZE 1.0 500.0 RWZS F__
Setting of the bandwidth. Increasing the setting of this parameter increases the dynamic response and makes the system
more rigid.
17.1 2250 Current reg P gain V/A FLOAT CALCF 0.0 0.0 ERWS F__
Setting of the proportional coefficient of the current regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.2 2252 Current reg I time ms FLOAT CALCF 0.01 10000.0 ERWS F__
Setting of the integral coefficient of the current regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.3 2270 Voltage reg P gain Wb/V FLOAT CALCF 0.0 0.0 ERWS F__
Setting of the proportional coefficient of the voltage regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.4 2272 Voltage reg I time s FLOAT CALCF 0.1 100.0 ERWS F__
Setting of the integral coefficient of the voltage regulator.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.5 2280 Dead time limit V FLOAT SIZE 0.0 50.0 ERWS F__
Setting of the dead time voltage compensation value.
The dead time compensation function (Dead time compensation), compensates the distortion of output voltage caused
by the voltage drop on the IGBT devices and their switching characteristics.
Distortion of output voltage could cause irregular motor rotation.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.6 2282 Dead time slope V/A FLOAT SIZE 0.0 200.0 ERWS F__
Setting of the dead time compensation slope value.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.7 2290 Voltage base V FLOAT CALCF 50.0 690.0 ERWS F__
Setting of the basic voltage of the motor. This parameter is calculated automatically by the self-tuning procedure.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.8 2292 Voltage margin perc FLOAT 5.0 0.0 10.0 ERWS F__
Setting of the voltage regulation margin according to the available voltage. In case of a Voltage base setting close to or
equal to the actual mains value, Voltage margin represents the margin allowable by the voltage regulation to perform
rapid current variations when load steps are suddenly applied.
A value of 5% allows a very fast response to load steps but with a loss of output voltage and thus power output (reduced
power output).
The minimum value (1%) allows a maximum output voltage (around 98%) of the mains voltage to be achieved but with loss
of quality of the dynamic response.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
17.9 132 Magnet current lim A FLOAT 0.0 0.0 CALCF ERWZS F__
Setting of the magnetisation current when running at speeds of more than the rated motor speed.
18.1 2350 Torque curr lim Pos A FLOAT 16/32BIT CALCF 0.0 CALCF ERWS F__
Setting of the active torque limit of the drive for the positive current direction (clockwise rotation and anti-clockwise brak-
ing).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.2 2352 Torque curr lim Neg A FLOAT 16/32BIT CALCF 0.0 CALCF ERWS F__
Setting of the active torque limit of the drive for the negative current direction (anti-clockwise rotation and clockwise brak-
ing).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.3 2354 Torque curr lim sel ENUM Sorg limcoppia 0 3 ERWZ F__
Setting of the type of behaviour of the drive in the current limit condition.
0 Off
1 T clim +/-
2 T clim mot/gen
3 T limit src
If set to 0 no specific type of current limitation is set.
If set to 1 the active positive torque limit is Torque curr lim Pos and the active negative torque limit is Torque curr lim
Neg.
torque torque
Torque curr lim Pos Torque curr lim Pos Torque curr lim Pos
speed speed
Torque limits with Torque curr lim Sel = 1 Torque limits with Torque curr lim sel = 2
If set to 3 the torque limits are symmetrical. The torque reference is the value of Torque curr lim Pos. This mode is not
managed with SSC control mode.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.4 2358 Torque limit src LINK 16/32BIT 3726 0 16384 ERWZ F__
Selection of the origin (source) of the signal to be used for the torque current limit. The signals that can be associated with
the function are listed in the “L_LIM” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.5 2360 Torque climPos Inuse A FLOAT 16/32BIT 0.0 0.0 0.0 ER F__
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.6 2362 Torque climNeg Inuse A FLOAT 16/32BIT 0.0 0.0 0.0 ER F__
The negative torque limit value currently being used is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.7 2380 Dig torque ref 1 perc FLOAT 16/32BIT 0.0 -300.0 300.0 ERW F__
Setting of a digital torque reference. The current reference value is proportional to the active motor current and determines
the torque value. The sign determines the torque direction.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.8 2382 Torque ref 1 src LINK 16/32BIT 3104 0 16384 ERWZ F__
Selection of the origin (source) of the signal to be used for the torque reference. The signals that can be associated with
the function are listed in the “L_VREF” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.9 2384 Torque ref filter ms FLOAT 1.0 0.1 10.0 ERW F__
Setting of a filter on the torque reference.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
18.10 2386 Torque ref perc FLOAT 16/32BIT 0.0 0.0 0.0 ER F__
The value of the torque reference is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.1.1 3100 Inertia comp kgm2 FLOAT 0.0 0.0 100.0 ERWS F__
Total value of the inertia on the motor shaft in Kgm² identified during the self-tuning procedure. If known, this value can also
be set manually by the user.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.1.3 3104 Inertia comp mon perc FLOAT 16/32BIT 0.0 0.0 0.0 ER F__
The value of inertia compensation on the function block output is displayed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.2.2 3202 Motor ovld factor perc FLOAT 150.0 100.0 300.0 ERWS F__
Setting of the motor overload value. Percentage value of the motor rated current (par. 2002 Rated current).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.2.3 3204 Motor ovld time s FLOAT 30.0 10.0 300.0 ERWS F__
Setting of the motor overload duration in seconds. It represents the moment in which the protection (“Motor Overload”) is
enabled, if the motor current value is above the overload set in the Motor ovld factor parameter. This alarm can be as-
signed to a programmable digital output (Motor overload trip).
The trip time depends on the motor current value and is as follows:
Trip time [s]
19.2.4 3206 Motor service factor perc FLOAT 100.0 25.0 200.0 ERWS F__
Setting of the motor service factor. This is the difference between the peak current and rated current. It is used to calculate
the thermal image of the motor.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.2.5 3216 Motor fan type ENUM Servo fan 0 1 ERW FVS
This parameter is used to set the type of motor cooling system.
0 Auto fan
1 Servo fan
Auto fan indicates the presence of a fan unit mounted on the motor shaft that therefore turns at a speed proportional to the mo-
tor speed. Cooling is not very effective at low motor speeds.
Servo fan indicates the presence of an independent fan unit that therefore always runs at the rated speed. It ensures optimum
cooling efficiency at all motor speeds.
When the current motor speed is below (PAR 2004 Rated speed / 2) and PAR 3216 Motor fan type = Auto fan; , the MOTOR
OVERLOAD protection intervention time must be reduced as cooling is insufficient.
At below (PAR 2004 Rated speed / 2) the protection intervention time is reduced by reducing the direct current of the MOTOR
OVERLOAD function.
When the motor speed is equal to (PAR 2004 Rated speed / 2) the direct current of the MOTOR OVERLOAD function is equal
to PAR 2002 Rated current * PAR 3206 Motor service factor, , whereas below that limit it is modified following a linear pattern
until PAR 2002 Rated current * 3206 Motor service factor * PAR 3218 Motor derat factor when the motor speed reaches
zero.
The overload current of the MOTOR OVERLOAD function is obtained by PAR 2002 Rated current * 3206 Motor service factor
* PAR 3202 Motor ovld factor and is the maximum current that can circulate in the motor. If the MOTOR OVERLOAD function
is enabled the drive automatically sets the torque current limit so that Iout max. does not exceed this value.
With the MOTOR OVERLOAD function a current equal to the Overload level is supplied to the motor for the maximum time set
in PAR 3204 Motor ovld time, The slower the motor speed, the shorter the time allowed (see figure at beginning of chapter).
After the set time, the MOTOR OVERLOAD function automatically sets the torque current limit so that Iout max. does not exceed
the direct current of the MOTOR OVERLOAD function.
When the motor current speed exceeds (PAR 2004 Rated speed / 2) and PAR 3216 Motor fan type = Auto fan, the direct cur-
rent is not reduced as cooling is sufficient.
When PAR 3216 Motor fan type = Servo fan, the direct current is not reduced as cooling is sufficient.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.2.6 3218 Motor derat factor perc FLOAT 50.0 0.0 100.0 ERWS FVS
This parameter is used to set the derating factor. The value is expressed as a percentage of PAR 2002 Rated current *
PAR 3206 Motor service factor.
When the current motor speed is below (PAR 2004 Rated speed / 2) and PAR 3216 Motor fan type = Auto fan, the protec-
tion intervention time must be reduced as cooling is insufficient.
At below (PAR 2004 Rated speed / 2) sthe protection intervention time is reduced by reducing the direct current of the
MOTOR OVERLOAD function.
When the motor speed is equal to (PAR 2004 Rated speed / 2) ) the direct current of the MOTOR OVERLOAD function
is equal to PAR 2002 Rated current * PAR 3206 Motor service factor, whereas below that limit it is modified following a
linear pattern until PAR 2002 Rated current * PAR 3206 Motor service factor * PAR 3218 Motor derat factor when the
motor speed reaches zero.
The overload current of the MOTOR OVERLOAD function is obtained by PAR 2002 Rated current * PAR 3206 Motor
service factor * PAR 3202 Motor ovld factor and is the maximum current that can circulate in the motor. If the MOTOR
OVERLOAD function is enabled the drive automatically sets the torque current limit so that Iout max. does not exceed this
value.
With the MOTOR OVERLOAD function a current equal to the Overload level is supplied to the motor for the maximum time
set in PAR 3204 Motor ovld time, The slower the motor speed, the shorter the time allowed (see graphs).
After the set time, the MOTOR OVERLOAD function automatically sets the torque current limit so that Iout max. does not
exceed the direct current of the MOTOR OVERLOAD function.
If the value of parameter 3202 Motor ovld factor is 100 % the overload current of the Motor Overload function is equal
to the continuous current of the Motor Overload function. In this case the drive behaves as if the overload cycle has been
executed and so sets the torque current limit so that Iout max is not more than the continuous current, i.e. Rated current
(PAR 2002) * Motor service factor (PAR 3206) * Motor derat factor (PAR 3218).
We recommend setting parameter 3218 Motor derat factor to a value so that Rated current (PAR 2002) * Motor service
factor (PAR 3206) * Motor derat factor (PAR 3218) produces a result that is more than the motor magnetisation current.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.3.2 3252 Bres value ohm FLOAT SIZE 7.0 1000.0 ERWS F__
Setting of the ohm value of the external braking resistor
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.3.3 3254 Bres cont power kW FLOAT SIZE 0.1 100.0 ERWS F__
Setting of the power that can be continuously dissipated by the external braking resistor.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.3.4 3256 Bres overload factor FLOAT SIZE 1.5 10.0 ERWS F__
Setting of the external resistor overload factor.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.3.5 3258 Bres overload time s FLOAT SIZE 0.5 50.0 ERWS F__
Setting of the intervention time of the external braking resistor overload.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.4.2 3302 Par set select src LINK 16BIT 6000 0 16384 ERWZ F__
Selection of the origin (source) of the signal to be used to select the parameter set to be used. The terminal or digital com-
mand that can be associated with this function can be selected from among those available in the “L_DIGSEL2” selection
list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.4.3 3304 Par set select mon ENUM 16BIT Set 0 0 0 ER F__
The parameter set currently in use is displayed.
0 Set 0
1 Set 1
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
This function copies parameter set 0 onto set 1. Before enabling management of the double parameter set, the first set
should be programmed with the correct values.
When the first set is ready, the second can be activated as follows:
1 Activate management of the double parameter set by enabling parameter 3300 Par set enable.
2 Copy set 0 onto set 1 using command 3306 Par set 0 to 1 copy.
This creates an initial parameter base in set 1 to which changes can be made.
Save the parameters.
3 Activate set 1 using parameter 3302 Par set select src.
To select set 1 manually, set this parameter to “One”.
Otherwise select the desired source.
4 Modify the parameters in set 1 as necessary.
5 Save the parameters.
When the double parameter set is active, the number of the set being used is shown next to the number of each parameter
on the keypad.
When the double parameter set is active, any parameters that need to be the same in the two sets must be modified in
each set separately.
Parameters are only saved in the set that is active at the time. To save both sets, you must first save one and then select
and save the other.
Note! Any changes to the parameters regarding the “parameter sets”, performed when enabled, will be lost at the next switching unless a Par set 0
to 1 copy command is sent.
To save data permanently (even when the drive is switched off), send the Save parameters command (DRIVE CONFIG menu).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.5.1 3650 Dig compare input 1 perc FLOAT 32BIT 0.0 -100.0 100.0 ERW F__
Setting of the digital value of the first element of comparison.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.5.2 3652 Dig compare input 2 perc FLOAT 32BIT 0.0 -100.0 100.0 ERW F__
Setting of the digital value of the second element of comparison.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.5.3 3660 Compare input 1 src LINK 32BIT 3650 0 16384 ERW F__
Selection of the origin (source) of the signal to be used as the first term of comparison. The values that can be selected in
the compare function are listed in the “L_CMP” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.5.4 3662 Compare input 2 src LINK 32BIT 3652 0 16384 ERW F__
Selection of the origin (source) of the signal to be used as the second term of comparison. The values that can be selected
in the compare function are listed in the “L_CMP” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.5.6 3672 Compare window perc FLOAT 0.0 0.0 100.0 ERW F__
Setting of the tolerance window for comparing the Compare input 1 and Compare input 2 signals.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
19.5.7 3674 Compare delay s FLOAT 0.0 0.0 30.0 ERW F__
Setting of the delay for signalling the result of the comparison.
19.6 - FUNCTIONS/PADS
The general variables are used to exchange data between the various components of a Bus system. They are similar to the variables
of a PLC. Pads can be used, for example, to send information from a fieldbus to an optional card. All Pads can be read and written.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
20.3.2 4022 Fieldbus M->S1 sys ENUM Not assigned 0 10 ERW F__
20.3.6 4032 Fieldbus M->S2 sys ENUM Not assigned 0 10 ERW F__
20.3.10 4042 Fieldbus M->S3 sys ENUM Not assigned 0 10 ERW F__
20.3.14 4052 Fieldbus M->S4 sys ENUM Not assigned 0 10 ERW F__
20.3.18 4062 Fieldbus M->S5 sys ENUM Not assigned 0 10 ERW F__
20.3.22 4072 Fieldbus M->S6 sys ENUM Not assigned 0 10 ERW F__
20.3.26 4082 Fieldbus M->S7 sys ENUM Not assigned 0 10 ERW F__
20.3.30 4092 Fieldbus M->S8 sys ENUM Not assigned 0 10 ERW F__
20.3.34 4102 Fieldbus M->S9 sys ENUM Not assigned 0 10 ERW F__
20.3.38 4112 Fieldbus M->S10 sys ENUM Not assigned 0 10 ERW F__
20.3.42 4122 Fieldbus M->S11 sys ENUM Not assigned 0 10 ERW F__
20.3.46 4132 Fieldbus M->S12 sys ENUM Not assigned 0 10 ERW F__
20.3.50 4142 Fieldbus M->S13 sys ENUM Not assigned 0 10 ERW F__
20.3.54 4152 Fieldbus M->S14 sys ENUM Not assigned 0 10 ERW F__
20.3.58 4162 Fieldbus M->S15 sys ENUM Not assigned 0 10 ERW F__
20.3.62 4172 Fieldbus M->S16 sys ENUM Not assigned 0 10 ERW F__
Setting of the format of the datum received on the channel. When the src parameter is programmed, the format is auto-
matically programmed on the relative sys. If the src parameter is reset to null, the format does not change. The value of the
format can be selected from the following list, according to the parameter selected as the source:
0 Not assigned
1 Count 16
2 Count 32
3 Fill 16
4 Fill 32
5 Mdplc 16
6 Mdplc 32
7 EU
8 Eu float
9 Par 16
10 Par 32
If set to 0 the channel is not assigned.
If set to 1 the datum is assigned a 16-bit count.
If set to 2 the datum is assigned a 32-bit count.
Note! If the sys parameter is not assigned, none of the subsequent fieldbus channels are read, even if programmed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
20.3.4 4026 Fieldbus M->S1 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.8 4036 Fieldbus M->S2 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.12 4046 Fieldbus M->S3 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.16 4056 Fieldbus M->S4 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.20 4066 Fieldbus M->S5 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.24 4076 Fieldbus M->S6 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.28 4086 Fieldbus M->S7 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.32 4096 Fieldbus M->S8 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.36 4106 Fieldbus M->S9 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.40 4116 Fieldbus M->S10 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.44 4126 Fieldbus M->S11 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.48 4136 Fieldbus M->S12 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.52 4146 Fieldbus M->S13 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.56 4156 Fieldbus M->S14 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.60 4166 Fieldbus M->S15 div FLOAT 1.0 1.0 1000.0 ERW F__
20.3.64 4176 Fieldbus M->S16 div FLOAT 1.0 1.0 1000.0 ERW F__
The Div M->Sx fieldbus parameters can be used to increase the resolution of the datum sent on the bus to the drive in the
corresponding channel in EU and EU_float exchange mode. The parameter value is used by the drive as the divider of the
incoming datum, so that a number with decimal digits can be transferred.
Example : Div M->Sx fieldbus = 10, M->S1 fieldbus par = Ramp ref src 1, Sys M->S1 fieldbus = Eu. If the PLC sends
the decimal value 1000 on the first word the value of ramp ref 1 on the drive is 1000/10 = 100.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
20.4.2 4182 Fieldbus S->M1 sys ENUM Not assigned 0 10 ERW F__
20.4.6 4192 Fieldbus S->M2 sys ENUM Not assigned 0 10 ERW F__
20.4.10 4202 Fieldbus S->M3 sys ENUM Not assigned 0 10 ERW F__
20.4.14 4212 Fieldbus S->M4 sys ENUM Not assigned 0 10 ERW F__
20.4.18 4222 Fieldbus S->M5 sys ENUM Not assigned 0 10 ERW F__
20.4.22 4232 Fieldbus S->M6 sys ENUM Not assigned 0 10 ERW F__
20.4.26 4242 Fieldbus S->M7 sys ENUM Not assigned 0 10 ERW F__
20.4.30 4252 Fieldbus S->M8 sys ENUM Not assigned 0 10 ERW F__
20.4.34 4262 Fieldbus S->M9 sys ENUM Not assigned 0 10 ERW F__
20.4.38 4272 Fieldbus S->M10 sys ENUM Not assigned 0 10 ERW F__
20.4.42 4282 Fieldbus S->M11 sys ENUM Not assigned 0 10 ERW F__
20.4.46 4292 Fieldbus S->M12 sys ENUM Not assigned 0 10 ERW F__
20.4.50 4302 Fieldbus S->M13 sys ENUM Not assigned 0 10 ERW F__
20.4.54 4312 Fieldbus S->M14 sys ENUM Not assigned 0 10 ERW F__
20.4.58 4322 Fieldbus S->M15 sys ENUM Not assigned 0 10 ERW F__
20.4.62 4332 Fieldbus S->M16 sys ENUM Not assigned 0 10 ERW F__
Setting of the format of the datum sent to the channel. When the src parameter is programmed, the format is programmed
as Eu or MDPLC 16. If the src parameter is reset to null, the datum format does not change. The value of the format can
be selected from the following list:
0 Not assigned
1 Count 16
2 Count 32
3 Fill 16
4 Fill 32
5 Mdplc 16
6 Mdplc 32
7 EU
8 Eu float
9 Par 16
10 Par 32
Note! If the sys parameter is not assigned, none of the subsequent channels are transferred to the fieldbus, even if programmed.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
20.4.4 4186 Fieldbus S->M1 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.8 4196 Fieldbus S->M2 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.12 4206 Fieldbus S->M3 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.16 4216 Fieldbus S->M4 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.20 4226 Fieldbus S->M5 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.24 4236 Fieldbus S->M6 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.28 4246 Fieldbus S->M7 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.32 4256 Fieldbus S->M8 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.36 4266 Fieldbus S->M9 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.40 4276 Fieldbus S->M10 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.44 4286 Fieldbus S->M11 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.48 4296 Fieldbus S->M12 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.52 4306 Fieldbus S->M13 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.56 4316 Fieldbus S->M14 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.60 4326 Fieldbus S->M15 mul FLOAT 1.0 1.0 1000.0 ERW F__
20.4.64 4336 Fieldbus S->M16 mul FLOAT 1.0 1.0 1000.0 ERW F__
The “Fieldbus S->Mx mul” parameters are multipliers that the drive applies to the datum before sending it to the bus. It is
therefore possible to increase the resolution of some values read in EU and EU_float mode, also using decimal digits.
Note! The drive does not check that the multiplied parameter expressed in bits fits in a 16-bit integer. You must make sure that the multiplier is com-
patible with the maximum value of the exchanged parameter and that it does not exceed the maximum size of 32768.
20.5.1 4400 Word bit0 src LINK 16BIT 6000 0 16384 ERW F__
20.5.2 4402 Word bit1 src LINK 16BIT 6000 0 16384 ERW F__
20.5.3 4404 Word bit2 src LINK 16BIT 6000 0 16384 ERW F__
20.5.4 4406 Word bit3 src LINK 16BIT 6000 0 16384 ERW F__
20.5.5 4408 Word bit4 src LINK 16BIT 6000 0 16384 ERW F__
20.5.6 4410 Word bit5 src LINK 16BIT 6000 0 16384 ERW F__
20.5.7 4412 Word bit6 src LINK 16BIT 6000 0 16384 ERW F__
20.5.8 4414 Word bit7 src LINK 16BIT 6000 0 16384 ERW F__
20.5.9 4416 Word bit8 src LINK 16BIT 6000 0 16384 ERW F__
20.5.10 4418 Word bit9 src LINK 16BIT 6000 0 16384 ERW F__
20.5.11 4420 Word bit10 src LINK 16BIT 6000 0 16384 ERW F__
20.5.12 4422 Word bit11 src LINK 16BIT 6000 0 16384 ERW F__
20.5.13 4424 Word bit12 src LINK 16BIT 6000 0 16384 ERW F__
20.5.14 4426 Word bit13 src LINK 16BIT 6000 0 16384 ERW F__
20.5.15 4428 Word bit14 src LINK 16BIT 6000 0 16384 ERW F__
20.5.16 4430 Word bit15 src LINK 16BIT 6000 0 16384 ERW F__
Selection of the origin (source) of the signal to be used for coding in Word comp. This function allows the user to compose
a single word composed of 16 signals, each of which can be selected from among those listed in the “L_DIGSEL1” selec-
tion list”.
The values of the sectioned sizes are converted into a single word.
................ .........
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
20.6.2 4452 Word decomp src LINK 16BIT 4450 0 16384 ERW F__
Selection of the origin (source) of the word to be decoded by the “Word decomp” block. Each bit that is part of the word
to be decoded is associated with the output channel of the “Word decomp” block. The variables that can be used for this
function can be selected from among those listed in the “L_WDECOMP” selection list”
......... ................
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
For some alarms, behaviour can be configured separately for each signal, while for the others the Disable drive is executed. Indi-
vidual signals can also be sent to a programmable digital output.
Activity Ignore The alarm is not included in the list of alarms, it is not included in the alarm log, it is not
signalled on the digital outputs, no drive commands are modified.
Warning The alarm is included in the list of alarms, it is included in the alarm log, it is signalled on
the digital outputs, the First alarm information is updated, the Alarm enabled information
is updated, no drive commands are modified.
Disable Drive The alarm is included in the list of alarms, it is included in the alarm log, it is signalled on
the digital outputs, the First alarm information is updated, the Alarm enabled information
is updated, a command is sent to stop and disable the motor, which stops due to inertia.
Stop The alarm is included in the list of alarms, it is included in the alarm log, it is signalled
on the digital outputs, the First alarm information is updated, the Alarm enabled informa-
tion is updated, a Stop command is sent. When the zero speed is reached the drive is
disabled. If Ramp control mode is enabled, the drive moves to the zero speed with the
set ramp time; when the Speed delay 0 signal is activated the drive is disabled. If Speed
control mode is enabled, the drive moves to the zero speed with the maximum current
possible; when the Speed delay 0 signal is activated the drive is disabled. If Torque
control mode is enabled, the drive moves to the zero speed with the time set by the load;
when the Speed delay 0 signal is activated the drive is disabled.
Fast stop The alarm is included in the list of alarms, it is included in the alarm log, it is signalled on
the digital outputs, the First alarm information is updated, the Alarm enabled information
is updated, a Fast Stop command is sent. When the zero speed is reached the drive is
disabled. If Ramp control mode is enabled, the drive moves to the zero speed with the
set fast stop ramp time (deceleration time 3); when the Speed delay 0 signal is activated
the drive is disabled. If Speed control mode is enabled, the drive moves to the zero
speed with the maximum current possible; when the Speed delay 0 signal is activated
the drive is disabled. If Torque control mode is enabled, the drive moves to the zero
speed with the set load time; when the Speed delay 0 signal is activated the drive is
disabled.
n alarms with Activity = Ignore or Warning can be enabled at the same time.
If an alarm with Activity = Stop or Fast Stop is enabled and another alarm with an Activity other than Ignore or Warning is enabled,
the drive stops and is disabled.
Not all alarms allow the controlled stopping of the drive. The following table shows the possibility of setting the Activities for the
individual alarm signals.
ExtFlt ü ü ü ü ü
Motor OT ü ü ü ü ü
Overspeed ü ü ü ü ü
SpdRefLoss ü ü ü ü ü
SpdFbkLoss ü ü ü ü ü
Drive ovld ü ü ü ü ü
Motor ovld ü ü ü ü ü
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.1 4500 Fault reset src LINK 16BIT 6000 0 16384 RW F__
Selection of the origin (source) of the signal to be used for the command to reset the drive after an alarm. The terminal that
can be used for this function can be selected from among those listed in the “L_DIGSEL2” selection list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.5 4508 ExtFlt restart time ms UINT16 1000 120 30000 RW F__
Setting of the time within which the External Fault alarm must be reset in order to perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.10 4526 MotorOT restart time ms UINT16 1000 120 30000 RW F__
Setting of the time within which the Motor Overtemperature alarm must be reset in order to perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.12 4540 Overspeed threshold rpm INT16 INT32 CALCI 0 CALCI RW F__
Setting of the threshold above which the overspeed alarm Overspeed is enabled.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.24 4584 HTsens restart time ms UINT16 20000 120 60000 ERW F__
Setting of the time within which the HT sensor alarm must be reset in order to perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.27 4604 InAir restart time ms UINT16 1000 120 30000 ERW F__
Setting of the time within which the Intakeair OT alarm must be reset in order to perform automatic restart.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.30 4612 Desat restart time ms UINT16 2000 1000 10000 ERW F__
Setting of the time within which the Desaturation alarm must be reset in order to perform automatic restart. (Time with
alarm signal active + 1000 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.32 4622 IOverC restart time ms UINT16 2000 1000 10000 ERW F__
Setting of the time within which the Overcurrent alarm must be reset in order to perform automatic restart. (Time with
alarm signal active + 1000 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.34 4632 OverV restart time ms UINT16 2000 1000 10000 ERW F__
Setting of the time within which the Overvoltage alarm must be reset in order to perform automatic restart. (Time with
alarm signal active + 1000 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.36 4642 UnderV restart time ms UINT16 1000 120 10000 ERW F__
Setting of the time within which the Undervoltage alarm must be reset in order to perform automatic restart. (Time with
alarm signal active + 100 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.41 4664 PhLoss restart time ms UINT16 1000 120 10000 ERW F__
Setting of the time within which the Phase loss alarm must be reset in order to perform automatic restart. (Time with alarm
signal active + 100 msec).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Note! The motor brake must be closed while running this test!
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.44 4680 GroundFault thr perc FLOAT 10.0 0.0 150.0 ERWS F__
Setting of the threshold for the ground short circuit alarm Ground Fault.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.45 4700 Alarm dig sel 1 ENUM Nessun allarme 0 40 ERW F__
21.46 4702 Alarm dig sel 2 ENUM Nessun allarme 0 40 ERW F__
21.47 4704 Alarm dig sel 3 ENUM Nessun allarme 0 40 ERW F__
21.48 4706 Alarm dig sel 4 ENUM Nessun allarme 0 40 ERW F__
Setting of the alarm signal to enable on a digital output. The digital output is selected using parameters Alm dig out mon
1÷4, which can be enabled in the L_DIGSEL1 selection list.
0 No alarm
1 Overvoltage
2 Undervoltage
3 Ground fault
4 Overcurrent
5 Desaturation
6 MultiUndervolt
7 MultiOvercurr
8 MultiDesat
9 Heatsink OT
10 HeatsinkS OTUT
11 Intakeair OT
12 Motor OT
13 Drive overload
14 Motor overload
15 Bres overload
16 Phaseloss
17 Opt Bus fault
18 Opt 1 IO fault
19 Opt 2 IO fault
20 Opt Enc fault
21 External fault
22 Speed fbk loss
23 Overspeed
24 Speed ref loss
25 Emg stop alarm
26 Power down
27 Phaseloss out
28 OV safety
29 Safety failure
30 Not Used4
31 Not Used5
32 Not Used6
33 Plc1 fault
34 Plc2 fault
35 Plc3 fault
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
21.49 4720 Alm autoreset time s FLOAT 0.0 0.0 60.0 ERW F__
Setting of the time interval that must pass before executing an automatic reset.
If no alarms are enabled the drive is set to restart.
If some alarms are still enabled the drive is set to execute a new attempt at automatic reset.
At each attempted reset a counter increases. If the limit set in the Alm autoreset number parameter is reached the drive is
set to make no more attempts at reset and waits for a user reset.
The counter is set to zero when an automatic reset or user reset is performed and no alarms are enabled.
If the parameter is 0 the function is disabled.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
This is the menu in which the log of previous alarms is saved, with the time the alarm occurred (in relation to the Time drive power
on parameter). The alarms are displayed starting from the most recent (No. 1) up to the furthest back in time (No. 30). Up to 30
alarm signals can be displayed. The sub-code is used by service technicians to identify the specific type of alarm. Press the ▲ and
▼ keys to scroll the screen pages of the alarm log. The alarm log cannot be deleted.
Alarm number
1 PhaseLoss Alarm description
110:32 0000H
2 Undervoltage
110:25 0000H Sub-code
Time alarm
occurred
3 SpdFbkLoss
110:20 0000H
4 Overspeed
109:25 0000H
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
- 2388 Torque ref nofilter perc FLOAT 16BIT 0.0 0.0 0.0 ER F__
The torque control reference current without filter is displayed (in sensorless vector and field-oriented vector mode).
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
L_ANOUT 760
664
Ramp out mon
Speed setpoint
(*)
1.5
1214
1216
Digital input 3X mon
Digital input 4X mon
(*)
(*)
6000 Null (*) 260 Motor speed 1.6 1218 Digital input 5X mon (*)
626 Ramp ref out mon (*) 262 Motor speed nofilter (*) 1220 Digital input 6X mon (*)
760 Ramp out mon (*) 2150 Encoder speed 15.11 1222 Digital input 7X mon (*)
664 Speed setpoint 1.5 250 Output current 1.1 1224 Digital input 8X mon (*)
260 Motor speed 1.6 252 Output voltage 1.2 1226 Digital input 9X mon (*)
262 Motor speed nofilter (*) 254 Output frequency 1.3 1228 Digital input10X mon (*)
2150 Encoder speed 15.11 280 Torque current ref 1.9 1230 Digital input11X mon (*)
250 Output current 1.1 282 Magnet current ref 1.10 1232 Digital input12X mon (*)
252 Output voltage 1.2 284 Torque current 1.11 1062 Drive OK (*)
254 Output frequency 1.3 286 Magnet current 1.12 1064 Drive ready (*)
280 Torque current ref 1.9 2386 Torque ref 18.10 934 Ref is 0 (*)
282 Magnet current ref 1.10 2388 Torque ref nofilter (*) 936 Ref is 0 delay (*)
284 Torque current 1.11 270 DC link voltage 1.7 944 Speed is 0 (*)
286 Magnet current 1.12 1600 Analog input 1X mon 12.1 946 Speed is 0 delay (*)
2360 Torque climPos Inuse 18.5 1650 Analog input 2X mon 12.12 1066 Enable state mon 1.16
2362 Torque climNeg Inuse 18.6 368 Drive overload accum 1.14 1068 Start state mon 1.17
2386 Torque ref 18.10 3212 Motor overload accum 1.13 1070 FastStop state mon 1.18
2388 Torque ref nofilter (*) 3260 Bres overload accum 1.15 1024 Enable cmd mon 9.9
270 DC link voltage 1.7 4024 Fieldbus M->S1 mon 20.3.3 1026 Start cmd mon 9.10
3104 Inertia comp mon 19.1.3 4034 Fieldbus M->S2 mon 20.3.7 1028 FastStop cmd mon 9.11
1600 Analog input 1X mon 12.1 4044 Fieldbus M->S3 mon 20.3.11 4708 Alm dig out mon 1 (*)
1650 Analog input 2X mon 12.12 4054 Fieldbus M->S4 mon 20.3.15 4710 Alm dig out mon 2 (*)
368 Drive overload accum 1.14 4064 Fieldbus M->S5 mon 20.3.19 4712 Alm dig out mon 3 (*)
3212 Motor overload accum 1.13 4074 Fieldbus M->S6 mon 20.3.23 4714 Alm dig out mon 4 (*)
3260 Bres overload accum 1.15 4084 Fieldbus M->S7 mon 20.3.27 362 Drive overload trip (*)
2232 Spd reg P gain Inuse 16.16 4094 Fieldbus M->S8 mon 20.3.31 3214 Motor overload trip (*)
2234 Spd reg I gain Inuse 16.17 4104 Fieldbus M->S9 mon 20.3.35 3262 Bres overload trip (*)
4024 Fieldbus M->S1 mon 20.3.3 4114 Fieldbus M->S10 mon 20.3.39 366 Drive overload 80% (*)
4034 Fieldbus M->S2 mon 20.3.7 4124 Fieldbus M->S11 mon 20.3.43 4454 Bit0 decomp mon 20.6.3
4044 Fieldbus M->S3 mon 20.3.11 4134 Fieldbus M->S12 mon 20.3.47 4456 Bit1 decomp mon 20.6.4
4054 Fieldbus M->S4 mon 20.3.15 4144 Fieldbus M->S13 mon 20.3.51 4458 Bit2 decomp mon 20.6.5
4064 Fieldbus M->S5 mon 20.3.19 4154 Fieldbus M->S14 mon 20.3.55 4460 Bit3 decomp mon 20.6.6
4074 Fieldbus M->S6 mon 20.3.23 4164 Fieldbus M->S15 mon 20.3.59 4462 Bit4 decomp mon 20.6.7
4084 Fieldbus M->S7 mon 20.3.27 4174 Fieldbus M->S16 mon 20.3.63 4464 Bit5 decomp mon 20.6.8
4094 Fieldbus M->S8 mon 20.3.31 3700 Lift enable 19.6.1 4466 Bit6 decomp mon 20.6.9
4104 Fieldbus M->S9 mon 20.3.35 3702 Run cont mon 19.6.2 4468 Bit7 decomp mon 20.6.10
4114 Fieldbus M->S10 mon 20.3.39 3704 Up cont mon 19.6.3 4470 Bit8 decomp mon 20.6.11
4124 Fieldbus M->S11 mon 20.3.43 3706 Down cont mon 19.6.4 4472 Bit9 decomp mon 20.6.12
4134 Fieldbus M->S12 mon 20.3.47 3708 Brake cont mon 19.6.5 4474 Bit10 decomp mon 20.6.13
4144 Fieldbus M->S13 mon 20.3.51 3710 Lift dc brake 19.6.6 4476 Bit11 decomp mon 20.6.14
4154 Fieldbus M->S14 mon 20.3.55 3712 Brake 2 mon 19.6.7 4478 Bit12 decomp mon 20.6.15
4164 Fieldbus M->S15 mon 20.3.59 3714 Door open mon 19.6.8 4480 Bit13 decomp mon 20.6.16
4174 Fieldbus M->S16 mon 20.3.63 3716 Lift start 19.6.9 4482 Bit14 decomp mon 20.6.17
3700 Lift enable 19.6.1 3718 Pad 10 19.6.10 4484 Bit15 decomp mon 20.6.18
3702 Run cont mon 19.6.2 3720 Lift status word 19.6.11 3700 Lift enable 19.6.1
3704 Up cont mon 19.6.3 3722 Pad 12 19.6.12 3702 Run cont mon 19.6.2
3706 Down cont mon 19.6.4 3724 Pad 13 19.6.13 3704 Up cont mon 19.6.3
3708 Brake cont mon 19.6.5 3726 Ramp down limit 19.6.14 3706 Down cont mon 19.6.4
3710 Lift dc brake 19.6.6 3728 PAD 15 19.6.15 3708 Brake cont mon 19.6.5
3712 Brake 2 mon 19.6.7 3730 Lift wdec input 19.6.16 3710 Lift dc brake 19.6.6
3714 Door open mon 19.6.8 3712 Brake 2 mon 19.6.7
(1)
the XXXX parameter changes according 3714 Door open mon 19.6.8
3716 Lift start 19.6.9 to the src parameter used:
3718 Pad 10 19.6.10 3716 Lift start 19.6.9
3720 Lift status word 19.6.11 3660 Compare input 1 src 3718 Pad 10 19.6.10
3722 Pad 12 19.6.12 (1)
= 3650 Dig compare input 1 19.5.1 3720 Lift status word 19.6.11
3724 Pad 13 19.6.13 3722 Pad 12 19.6.12
3662 Compare input 2 src 3724 Pad 13 19.6.13
3726 Ramp down limit 19.6.14 (1)
= 3652 Dig compare input 2 19.5.2 3726 Ramp down limit 19.6.14
3728 PAD 15 19.6.15
3730 Lift wdec input 19.6.16 3728 PAD 15 19.6.15
5008 Test gen out 23.1.5 L_DIGSEL1 3730
6006
Lift wdec input
Current limit state
19.6.16
(*)
6000 Null (*) 764 Ramp acc state (*)
L_CMP 6002 One (*) 766 Ramp dec state (*)
1110 Digital input E mon (*) 4780 Alarm PLC (*)
XXXX (1) 3676 Compare output 19.5.8
1210 Digital input 1X mon (*)
626 Ramp ref out mon (*)
1212 Digital input 2X mon (*)
L_DIGSEL2 944
946
Speed is 0
Speed is 0 delay
(*)
(*)
664
260
Speed setpoint
Motor speed
1.5
1.6
6000 Null (*) 1066 Enable state mon 1.16 262 Motor speed nofilter (*)
6002 One (*) 1068 Start state mon 1.17 2150 Encoder speed 15.11
1110 Digital input E mon (*) 1070 FastStop state mon 1.18 250 Output current 1.1
1210 Digital input 1X mon (*) 1024 Enable cmd mon 9.9 252 Output voltage 1.2
1212 Digital input 2X mon (*) 1026 Start cmd mon 9.10 254 Output frequency 1.3
1214 Digital input 3X mon (*) 1028 FastStop cmd mon 9.11 280 Torque current ref 1.9
1216 Digital input 4X mon (*) 4708 Alm dig out mon 1 (*) 282 Magnet current ref 1.10
1218 Digital input 5X mon (*) 4710 Alm dig out mon 2 (*) 284 Torque current 1.11
1220 Digital input 6X mon (*) 4712 Alm dig out mon 3 (*) 286 Magnet current 1.12
1222 Digital input 7X mon (*) 4714 Alm dig out mon 4 (*) 2360 Torque climPos Inuse 18.5
1224 Digital input 8X mon (*) 362 Drive overload trip (*) 2362 Torque climNeg Inuse 18.6
1226 Digital input 9X mon (*) 3214 Motor overload trip (*) 2386 Torque ref 18.10
1228 Digital input10X mon (*) 3262 Bres overload trip (*) 2388 Torque ref nofilter (*)
1230 Digital input11X mon (*) 366 Drive overload 80% (*) 270 DC link voltage 1.7
1232 Digital input12X mon (*) 4454 Bit0 decomp mon 20.6.3 2162 Encoder position 15.12
4454 Bit0 decomp mon 20.6.3 4456 Bit1 decomp mon 20.6.4 2154 Virtual position 23.2.2
4456 Bit1 decomp mon 20.6.4 4458 Bit2 decomp mon 20.6.5 2156 Revolutions 23.2.3
4458 Bit2 decomp mon 20.6.5 4460 Bit3 decomp mon 20.6.6 3104 Inertia comp mon 19.1.3
4460 Bit3 decomp mon 20.6.6 4462 Bit4 decomp mon 20.6.7 1600 Analog input 1X mon 12.1
4462 Bit4 decomp mon 20.6.7 4464 Bit5 decomp mon 20.6.8 1650 Analog input 2X mon 12.12
4464 Bit5 decomp mon 20.6.8 4466 Bit6 decomp mon 20.6.9 368 Drive overload accum 1.14
4466 Bit6 decomp mon 20.6.9 4468 Bit7 decomp mon 20.6.10 3212 Motor overload accum 1.13
4468 Bit7 decomp mon 20.6.10 4470 Bit8 decomp mon 20.6.11 3260 Bres overload accum 1.15
4470 Bit8 decomp mon 20.6.11 4472 Bit9 decomp mon 20.6.12 272 Heatsink temperature 1.8
4472 Bit9 decomp mon 20.6.12 4474 Bit10 decomp mon 20.6.13 1060 Sequencer status (*)
4474 Bit10 decomp mon 20.6.13 4476 Bit11 decomp mon 20.6.14 4432 Word comp mon 20.5.17
4476 Bit11 decomp mon 20.6.14 4478 Bit12 decomp mon 20.6.15 4372 DS402 status word (*)
4478 Bit12 decomp mon 20.6.15 4480 Bit13 decomp mon 20.6.16 4024 Fieldbus M->S1 mon 20.3.3
4480 Bit13 decomp mon 20.6.16 4482 Bit14 decomp mon 20.6.17 4034 Fieldbus M->S2 mon 20.3.7
4482 Bit14 decomp mon 20.6.17 4484 Bit15 decomp mon 20.6.18 4044 Fieldbus M->S3 mon 20.3.11
4484 Bit15 decomp mon 20.6.18 3700 Lift enable 19.6.1 4054 Fieldbus M->S4 mon 20.3.15
3700 Lift enable 19.6.1 3702 Run cont mon 19.6.2 4064 Fieldbus M->S5 mon 20.3.19
3702 Run cont mon 19.6.2 3704 Up cont mon 19.6.3 4074 Fieldbus M->S6 mon 20.3.23
3704 Up cont mon 19.6.3 3706 Down cont mon 19.6.4 4084 Fieldbus M->S7 mon 20.3.27
3706 Down cont mon 19.6.4 3708 Brake cont mon 19.6.5 4094 Fieldbus M->S8 mon 20.3.31
3708 Brake cont mon 19.6.5 3710 Lift dc brake 19.6.6 4104 Fieldbus M->S9 mon 20.3.35
3710 Lift dc brake 19.6.6 3712 Brake 2 mon 19.6.7 4114 Fieldbus M->S10 mon 20.3.39
3712 Brake 2 mon 19.6.7 3714 Door open mon 19.6.8 4124 Fieldbus M->S11 mon 20.3.43
3714 Door open mon 19.6.8 3716 Lift start 19.6.9 4134 Fieldbus M->S12 mon 20.3.47
3716 Lift start 19.6.9 3718 Pad 10 19.6.10 4144 Fieldbus M->S13 mon 20.3.51
3718 Pad 10 19.6.10 3720 Lift status word 19.6.11 4154 Fieldbus M->S14 mon 20.3.55
3720 Lift status word 19.6.11 3722 Pad 12 19.6.12 4164 Fieldbus M->S15 mon 20.3.59
3722 Pad 12 19.6.12 3724 Pad 13 19.6.13 4174 Fieldbus M->S16 mon 20.3.63
3724 Pad 13 19.6.13 3726 Ramp down limit 19.6.14 3700 Lift enable 19.6.1
3726 Ramp down limit 19.6.14 3728 PAD 15 19.6.15 3702 Run cont mon 19.6.2
3728 PAD 15 19.6.15 3730 Lift wdec input 19.6.16 3704 Up cont mon 19.6.3
3730 Lift wdec input 19.6.16 6006 Current limit state (*) 3706 Down cont mon 19.6.4
3676 Compare output 19.5.8 764 Ramp acc state (*) 3708 Brake cont mon 19.6.5
766 Ramp dec state (*) 3710 Lift dc brake 19.6.6
4780 Alarm PLC (*) 3712 Brake 2 mon 19.6.7
L_DIGSEL3 3676 Compare output 19.5.8 3714 Door open mon 19.6.8
3716 Lift start 19.6.9
XXXX (2) (2)
the XXXX parameter changes according 3718 Pad 10 19.6.10
6000 Null (*) to the src parameter used: 3720 Lift status word 19.6.11
1218 Digital input 5X mon (*) 3722 Pad 12 19.6.12
1220 Digital input 6X mon (*) 1014 Local/remote src 3724 Pad 13 19.6.13
1222 Digital input 7X mon (*) (2)
= 1012 Dig local/remote (*) 3726 Ramp down limit 19.6.14
1224 Digital input 8X mon (*) 3728 PAD 15 19.6.15
1226 Digital input 9X mon (*) 3730 Lift wdec input 19.6.16
1228 Digital input10X mon (*) L_FBS2M 4770 First alarm (*)
1230 Digital input11X mon (*) 1200 Digital input X mon 1.19
1232 Digital input12X mon (*) XXXX (3)
5008 Test gen out 23.1.5
1062 Drive OK (*) 6000 Null (*)
1064 Drive ready (*) 6002 One (*) (3)
the XXXX parameter changes according
934 Ref is 0 (*) 626 Ramp ref out mon (*) to the src parameter used:
936 Ref is 0 delay (*) 760 Ramp out mon (*)
4340 DS402 cw src 3706 Down cont mon 19.6.4 3726 Ramp down limit 19.6.14
(3)
= 4024 Fieldbus M->S1 mon 20.3.3 3708 Brake cont mon 19.6.5 3728 PAD 15 19.6.15
3710 Lift dc brake 19.6.6 3730 Lift wdec input 19.6.16
3712 Brake 2 mon 19.6.7 5008 Test gen out 23.1.5
L_LIM 3714 Door open mon 19.6.8
3716 Lift start 19.6.9
6000 Null (*)
3718 Pad 10 19.6.10 L_SCOPE
1600 Analog input 1X mon 12.1
3720 Lift status word 19.6.11
1650 Analog input 2X mon 12.12 6000 Null (*)
3722 Pad 12 19.6.12
4024 Fieldbus M->S1 mon 20.3.3
3724 Pad 13 19.6.13
4034 Fieldbus M->S2 mon 20.3.7
4044 Fieldbus M->S3 mon 20.3.11
3726
3728
Ramp down limit
PAD 15
19.6.14
19.6.15
L_VREF
4054 Fieldbus M->S4 mon 20.3.15
3730 Lift wdec input 19.6.16 XXXX (5)
4064 Fieldbus M->S5 mon 20.3.19
5008 Test gen out 23.1.5 1600 Analog input 1X mon 12.1
4074 Fieldbus M->S6 mon 20.3.23
4084 Fieldbus M->S7 mon 20.3.27 1650 Analog input 2X mon 12.12
(4)
the XXXX parameter changes according 4024 Fieldbus M->S1 mon 20.3.3
4094 Fieldbus M->S8 mon 20.3.31
to the src parameter used: 4034 Fieldbus M->S2 mon 20.3.7
4104 Fieldbus M->S9 mon 20.3.35
4114 Fieldbus M->S10 mon 20.3.39 4044 Fieldbus M->S3 mon 20.3.11
610 Ramp ref 1 src 4054 Fieldbus M->S4 mon 20.3.15
4124 Fieldbus M->S11 mon 20.3.43 (4)
= 600 Dig ramp ref 1 6.1
4134 Fieldbus M->S12 mon 20.3.47 4064 Fieldbus M->S5 mon 20.3.19
4144 Fieldbus M->S13 mon 20.3.51 4074 Fieldbus M->S6 mon 20.3.23
612 Ramp ref 2 src 4084 Fieldbus M->S7 mon 20.3.27
4154 Fieldbus M->S14 mon 20.3.55 (4)
= 602 Dig ramp ref 2 6.2
4164 Fieldbus M->S15 mon 20.3.59 4094 Fieldbus M->S8 mon 20.3.31
4174 Fieldbus M->S16 mon 20.3.63 4104 Fieldbus M->S9 mon 20.3.35
650 Ramp ref 3 src 4114 Fieldbus M->S10 mon 20.3.39
3700 Lift enable 19.6.1 (4)
= 640 Dig ramp ref 3 6.8
3702 Run cont mon 19.6.2 4124 Fieldbus M->S11 mon 20.3.43
3704 Up cont mon 19.6.3 4134 Fieldbus M->S12 mon 20.3.47
652 Ramp ref 4 src 4144 Fieldbus M->S13 mon 20.3.51
3706 Down cont mon 19.6.4 (4)
= 642 Dig ramp ref 4 6.9
3708 Brake cont mon 19.6.5 4154 Fieldbus M->S14 mon 20.3.55
3710 Lift dc brake 19.6.6 4164 Fieldbus M->S15 mon 20.3.59
3712 Brake 2 mon 19.6.7 4174 Fieldbus M->S16 mon 20.3.63
3714 Door open mon 19.6.8 L_REF 3700
3702
Lift enable
Run cont mon
19.6.1
19.6.2
3716 Lift start 19.6.9
3718 Pad 10 19.6.10 626 Ramp ref out mon (*) 3704 Up cont mon 19.6.3
3720 Lift status word 19.6.11 664 Speed setpoint 1.5 3706 Down cont mon 19.6.4
3722 Pad 12 19.6.12 262 Motor speed nofilter (*) 3708 Brake cont mon 19.6.5
3724 Pad 13 19.6.13 2150 Encoder speed 15.11 3710 Lift dc brake 19.6.6
3726 Ramp down limit 19.6.14 1600 Analog input 1X mon 12.1 3712 Brake 2 mon 19.6.7
3728 PAD 15 19.6.15 1650 Analog input 2X mon 12.12 3714 Door open mon 19.6.8
3730 Lift wdec input 19.6.16 4024 Fieldbus M->S1 mon 20.3.3 3716 Lift start 19.6.9
5008 Test gen out 23.1.5 4034 Fieldbus M->S2 mon 20.3.7 3718 Pad 10 19.6.10
4044 Fieldbus M->S3 mon 20.3.11 3720 Lift status word 19.6.11
4054 Fieldbus M->S4 mon 20.3.15 3722 Pad 12 19.6.12
L_MLTREF 4064 Fieldbus M->S5 mon 20.3.19 3724 Pad 13 19.6.13
4074 Fieldbus M->S6 mon 20.3.23 3726 Ramp down limit 19.6.14
XXXX (4)
4084 Fieldbus M->S7 mon 20.3.27 3728 PAD 15 19.6.15
1600 Analog input 1X mon 12.1 4094 Fieldbus M->S8 mon 20.3.31 3730 Lift wdec input 19.6.16
1650 Analog input 2X mon 12.12 4104 Fieldbus M->S9 mon 20.3.35 6000 Null (*)
2150 Encoder speed 15.11 4114 Fieldbus M->S10 mon 20.3.39 5008 Test gen out 23.1.5
4024 Fieldbus M->S1 mon 20.3.3 4124 Fieldbus M->S11 mon 20.3.43
4034 Fieldbus M->S2 mon 20.3.7 4134 Fieldbus M->S12 mon 20.3.47
(5)
the XXXX parameter changes according
4044 Fieldbus M->S3 mon 20.3.11 4144 Fieldbus M->S13 mon 20.3.51 to the src parameter used:
4054 Fieldbus M->S4 mon 20.3.15 4154 Fieldbus M->S14 mon 20.3.55
4064 Fieldbus M->S5 mon 20.3.19 4164 Fieldbus M->S15 mon 20.3.59 2382 Torque ref 1 src
4074 Fieldbus M->S6 mon 20.3.23 4174 Fieldbus M->S16 mon 20.3.63
(5)
= 2380 Dig torque ref 1 18.7
4084 Fieldbus M->S7 mon 20.3.27 3700 Lift enable 19.6.1
4094 Fieldbus M->S8 mon 20.3.31 3702 Run cont mon 19.6.2
4104 Fieldbus M->S9 mon 20.3.35 3704 Up cont mon 19.6.3
4114 Fieldbus M->S10 mon 20.3.39 3706 Down cont mon 19.6.4
L_WDECOMP
4124 Fieldbus M->S11 mon 20.3.43 3708 Brake cont mon 19.6.5
4134 Fieldbus M->S12 mon 20.3.47 XXXX (6)
3710 Lift dc brake 19.6.6 6000 Null (*)
4144 Fieldbus M->S13 mon 20.3.51 3712 Brake 2 mon 19.6.7
4154 Fieldbus M->S14 mon 20.3.55 6002 One (*)
3714 Door open mon 19.6.8 4432 Word comp mon 20.5.17
4164 Fieldbus M->S15 mon 20.3.59 3716 Lift start 19.6.9
4174 Fieldbus M->S16 mon 20.3.63 4024 Fieldbus M->S1 mon 20.3.3
3718 Pad 10 19.6.10 4034 Fieldbus M->S2 mon 20.3.7
3700 Lift enable 19.6.1 3720 Lift status word 19.6.11
3702 Run cont mon 19.6.2 4044 Fieldbus M->S3 mon 20.3.11
3722 Pad 12 19.6.12 4054 Fieldbus M->S4 mon 20.3.15
3704 Up cont mon 19.6.3 3724 Pad 13 19.6.13
(6)
the XXXX parameter changes according
to the src parameter use:
Main features:
1) The “Mandatory Protocol boot-up” is managed.
2) The SYNC function is implemented.
3) The PDO asynchronous assignment is managed.
4) The Node Guarding and HearthBeat protocols are managed.
5) The emergency message is managed (“EMERGENCY”).
6) The Dynamic ID distribution function (DBT slave) is not managed.
7) A “Generic Pre-Defined Master/Slave connection” is implemented to simplify the Master tasks during the initialization
phase.
8) “Inhibit-Times” (in units of 100 uS) can be modified.
9) The high-resolution synchronization is not supported.
10) “TIME STAMP” is not managed.
11) On the access of the structured parameters, the OFFhex option subindex (access to the whole object) is not managed.
12) In order to obtain a higher efficiency level, only the “Expedited” data transfer (max. 4 Bytes) of the SDO services is managed.
13) The “communication profile area” parameters are not saved by a save command, which on the other hand works on
the “manufacturer-specific” and “profile” areas.
1.1.3 Monitoring
The ADL300 drive supports the Node Guarding and HeartBeat mechanism. The Node Guarding configuration can be per-
formed through the master via the standard Object Dictionary elements (1006h, 100Ch, 100Dh).
The Node Guarding threshold (maximum time between two NodeGuarding messages received from ADL) is calculated as:
“Guard time” x “LifeTime Factor”
The HeartBeat is configured by means of the objects 1016h and 1017h. The threshold in this case is calculated as:
“HeartBeat Time” x “LifeTime Factor”.
The default settings shown therefore correspond to the use of the NodeGuarding protocol with a threshold of 100ms x 3
and a threshold control even on Sync at 64ms x 3. The HeartBeat is disabled.
The following table lists the used communication objects with their priority level and the Message Identifier; the “Resulting
COB-ID” is obtained by adding the Node-ID (card address) to the number.
OBJECT PRIORITY MESSAGE ID
1st SDO rx 6 1792 700h+NodeId
1st SDO tx 6 1536 600h+NodeId
1st PDO rx 2 1408 580h+NodeId
1st PDO tx 2 512 200h+NodeId
2nd PDO rx 2 384 180h+NodeId
2nd PDO tx 2 768 300h+NodeId
3st PDO rx 2 640 280h+NodeId
3st PDO tx 2 512 400h+NodeId
4th PDO rx 2 384 380h+NodeId
4th PDO tx 2 768 500h+NodeId
EMERGENCY 1 640 480h+NodeId
NODE GUARDING & HB not used 220 600h+NodeId
SYNC 0 128 80h
Table 1.4.1: Communication Objects
The master NodeGuarding message is a remote type (remote RTR bit set in COB-ID). All other messages used by this
implementation of the CANopen are not RTR.
The objects shown in bold in the table allow writing of the parameters assigned with the exchange of data in the
PDO.
The allocation criterion is variable, and depends on the size (in bytes) of the parameter exchanged.
• Fieldbus baudrate = Sets the network baud rate. Values available for CANopen: 125k, 250k, 500k, 1M
• Fieldbus address = address of this slave node in the network, accepted values from 1 to 127
• Fieldbus M->S enable = if set to Off data in the RPDOs are not processed by the drive
• Fieldbus alarm mode = if set to 1 the drive generates Opt Bus Fault errors relating to the loss of communication (Bus
Loss) even when the drive is not enabled.
• Fieldbus state = state of the communication for this node on the CANopen network: Stop, Pre-Operational, Opera-
tional.
The drive can both read and write the Process Data Channel data.
A datum can be made both of 2 and 4 bytes. The word “data” refers to any quantity of bytes included between 0 and 16, if
the byte total number required is not higher than 32.
Example:
It is possible to have:
Drive
Input
CANopen PDO Rx
PDC Output
interface PDO Tx
Data mapping in PDOs is performed on the basis of the data format set in Fieldbus M->Sn sys according to the following
rules:
– PDOs are filled starting from RPDO1
– When the PDO contains 4 words it is full and the next RPDO is filled with a maximum of 4 PDOs
– 32-bit data (long or float) cannot be split among PDOs, they must be placed inside the PDO (an alarm is generated)
– PDOs containing fewer than 4 words can be created, using Fieldbus M->Sn dest= None but assigned (Fieldbus
M->Sn sys other than Not Assigned, Fill16 or Fill32) after an assigned datum.
(N.B.: if assigned as Fill16 or Fill32, the datum is included in the PDO anyway)
– At the first Fieldbus M->Sn sys = Not Assigned parameter the PDOs are complete. The size of the last PDO thus
depends on the data that have been assigned.
Example:
Writing the value 1m/s in the PAR 11020 Multi speed 0 (2B0C hex).
The ipaCan parameter and relative value is written by first inserting the lower part of the address in hexadecimal and then
the higher part (Value to be written LL-LH-HL-HH).
MessageID Writing Code Lower part Higher part Subindex Value of Value of Value of Value of
IpaCan IpaCan parameter LL parameter LH parameter HL parameter HH
601h 22h 0Ch 43h 01h 01h 00h 00h 00h
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
MessageID Writing Code Lower part Higher part Subindex Value of Value of Value of Value of
IpaCan IpaCan parameter LL parameter LH parameter HL parameter HH
601h 60h 0Ch 43h 01h 01h 00h 00h 00h
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
MessageID Writing Code Lower part Higher part Subindex Not significant Not significant Not significant Not significant
IpaCan IpaCan
601h 40h 0Ch 43h 01h 00h 00h 00h 00h
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
MessageID Reading code Lower part Higher part Subindex Value of data
IpaCan IpaCan
601h 43h 0Ch 43h 01h 01h 00h 00h 00h
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
Index Subindex
0Ch 4Bh 01h 01h 00h 00h 00h
Drive parameter value
to be assigned to SDO
Drive parameter index
Subindex
In case an error occurs during the parameter reading or setting, the CANopen interface sends an Abort domain transfer
message; the value of Application-error-codes has the following meanings:
Error class Error code Additional code (hex) Meaning
6 0 0 Parameter doesn’t exist
8 0 22 Acces failed because of present
device state
6 1 2 Read/Write only error
8 0 0 Generic error
6 9 32 Minimum value
6 9 31 Maximum value
5 4 0 SDO time_out
5 4 1 Invalid command
3 9 30 Invalid value
In the example, it is assumed that the drive is node 1 and the CANopen communication takes place with a baud rate of
500k. Make sure that all fieldbus settings and configurations are only effective after the drive’s next reset.
Program the fieldbus menu parameters as shown in the following figure:
The status is pre-operational and the CAN led on the local Keypad is flashing.
Under these conditions, the process communication channels are not active.
At the end from the drive’s programming (see below) and communication can be activated by the master through the NMT
“start node” command.
Upon receipt of this command, the FieldBus parameter goes into the Operational condition and the CAN led on the keypad
goes from flashing to fixed. Only at this point are the process channels active.
CAN
CAN connector (XC)
CAN LED L SH H
Prg
Enter
LEDs Meaning
CAN (green)
Off Stop
Flashing Pre-operational
On Operational
“Expert” mode:
Now all lift sequences are controlled via the LiftWdecomp bits in the same way as described in the manual using digital
inputs.
In a similar manner, after a drive save and restart, the correct Slave → Master channel programming can be checked:
If the PAR 4000 Fieldbus type parameter is set to DS402 the drive works with the standard profile for Drives & Motion
Control Ver 2.0 and contains Device Identity 192H (402) in object 1000h.
The ADL300 drive supports Velocity Mode.
In the default configuration the drive is automatically set to use PDOs No. 6 (DS402 section 7.2.1 & 7.2.2 ), mapped onto
RPDO1 and TPDO1 with COB-ID 200h & 180h +NodeId
(1) The unit of measure for objects 6042h, 6043h, 6044h is expressed in rpm
(2) Object 6060h is only available in that it is mandatory. As the drive only supports Velocity Mode, the value of this object is not modifiable.
The device operates as a DS402 state machine (refer to CiA DSP 402 V 2.0, section 10.1.1) :
Power Fault 13
Disabled
Fault
Start
Reaction Active
0 14
Not Ready to
Fault
Switch On
1 15
Switch On
Disabled
2 7
Ready to
Switch On
Power 3 6 10 12
Enabled
9 8 Switched On
4 5
11
Operation Quick Stop
Enable Activ
16
GEFRAN S.p.A.
Manuale ADL300 SYN FP -EN
Via Sebina 74 Drive & Motion Control Unit Rev. 0.1 - 24-6-2013
25050 Provaglio d’Iseo (BS) ITALY Via Carducci 24 Technical Assistance :
technohelp@gefran.com
Ph. +39 030 98881 21040 Gerenzano [VA] ITALY
Fax +39 030 9839063 Ph. +39 02 967601 Customer Service :
motioncustomer@gefran.com
info@gefran.com Fax +39 02 9682653 Ph. +39 02 96760500
www.gefran.com infomotion@gefran.com Fax +39 02 96760278
1S9SEN