Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Linear Heat Sensing Cable

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

800 900 Series

Linear Heat
Detector (LHD)

Models Available
System Sensor 800 series digital linear heat detector and 900
series analogue linear heat detector offer early detection of fire
and overheating conditions in industrial high risk hazards as well
as many types of commercial applications.

900 series 800 series

Description
The Linear Heat Detection Cable (LHDC) is a continuous heat detector in the form of a cable. It can detect heat at any points
along its entire length. The cable is composed of two twisted shield conductors insulated with a heat sensitive polymer, then
wrapped with a protective tape and finished with an outer covering.

Linear Heat Detection Cable is available in resettable and non-resettable technology. The non-resettable cable is
described as Digital and the resettable as Analogue.

800 Series Digital LHD Cable (Non-Resettable)


The 800 series is a fixed temperature and non-resettable digital cable. The cable contains insulators which melt at a specific
temperature. At the rated temperature, the heat sensitive polymeric insulation creates pressure between conductors,
permitting them make contact with each other thereby initiating an alarm signal at the control panel. The LHDC is installed
in conjunction with an end-of-line (EOL) device for continuity monitoring and a junction box (optional) for leader wire
connection.
900 Series Analogue LHD Cable (Resettable)
The 900 series is an analogue heat sensing cable containing insulators of which resistance varies proportionally to changes
in temperature. Analogue cable is installed in conjunction with an end-of-line (EOL) device for continuity monitoring and a
modulator providing selectable alarm thresholds (programmed before shipping), fire and fault outputs. This cable is self-
restorable after the fire event as long as its temperature does not exceed specified resettable temperature limit of 120°C
(248°F). Alarm temperature setting ranges between 70°C to 130°C (158°F to 266°F). Customer can specify its own alarm
temperature setting. The factory default setting is set at 85°C (185°F).

Features
· Multiple configurations for installations:
- Digital type of LHD cables
- Analogue type of LHD cables
· Multiple alarm temperature ratings available for both digital and analogue type
· Maximum zone length (Digital) - 1000 meters
· Maximum zone length (Analogue) – 200 meters
· Resettable temperature up to 120°C (248°F) (Analogue)
· Selectable alarm temperature threshold programmed before shipping (Analogue)
· Normal, fault and alarm indicators on the 900 series modulator (Analogue)
· Compatible with any conventional or intelligent fire alarm panel
· Smoothing algorithms provide false alarm immunity
Typical Wiring Diagrams & Specifications
800 Series:

900 Series:

Physical/Operating Specifications JTY-LD-N*-887 JTY-LD-997


Type of Cable Digital Analogue
70°C (158°F, not available for Nylon sheath), 70°C to 130°C (Set by factory, default setting 85°C )
Alarm Temperature
85°C (185°F), 105°C (221°F), 138°C (280.4°F) 158°F to 266°F (Set by factory, default setting
-25°C to (N* - 20)°C 185°F)
-25°C to (Alarm Temp. - 20) °C
Operating Temperature Range ≦
-13°F to (N* - 36) °F -13°F to (Alarm Temp. - 36) °F
Reset Temperature NA 120°C (248°F)
Max Zone Length 1000m 200m
Min Bend Radius 1.5 cm 1.5 cm
Standard Roll Length 200m or 600m 200m or 600m
Conductor Material Steel Steel
Outer Sheath Option PVC/Nylon/Steel PVC/Nylon/Steel
Weight 1.8kg/100m (1.2lb/100ft)( PVC sheath) 1.4kg/100m (0.94lb/100ft)( PVC sheath)
Electrical Specifications JTY-LD-N*-887 JTY-LD-997
Operating Voltage / Contact Ratings NA 20 – 26 VDC
Standby Current NA 25mA
Alarm and Fault Current NA 45mA
Resistance 0.32ohms/m (0.1ohms/ft) NA
* N denotes for 70/85/105/138°C

Ordering Information
Model Description Temperature Ratings UOM
JTW-LD-70-887 70°C (158°F) Meter
JTW-LD-85-887 85°C (185°F) Meter
Digital heat sensing cable, PVC sheath
JTW-LD-105-887 105°C (221°F) Meter
JTW-LD-138-887 138°C (280°F) Meter
JTW-LD-85-887N 85°C (185°F) Meter
JTW-LD-105-887N Digital heat sensing cable, Nylon sheath 105°C (221°F) Meter
800 Series
JTW-LD-138-887N 138°C (280°F) Meter
JTW-LD-70-887S 70°C (158°F) Meter
JTW-LD-85-887S 85°C (185°F) Meter
Digital heat sensing cable, Steel sheath
JTW-LD-105-887S 105°C (221°F) Meter
JTW-LD-138-887S 138°C (280°F) Meter
887/EOL End of Line box for 800 series cable — EA
Pre-selecting range 70 °C~ 130 °C(158°F to 266°F) ,
JTW-LD-997 Analogue heat sensing cable
(factory default setting 85°C (185°F)) Meter
900 Series
997/M Modulator for 900 series cable — EA
997/EOL End of Line box for 900 series cable — EA
Accessories MB Junction Box for 800/900 Series cable — EA

System Sensor Headquarters System Sensor China System Sensor Canada System Sensor Italy System Sensor Far East Ltd System Sensor India
3825 Ohio Avenue 28 Tuan Jie South Road, Ph: 905-812-0767 Ph: 39 040 949 0111 Ph: 852 21919003 Ph: 91 124 2371770-270
St. Charles, IL 60174 Hi-Tech Development Zone Fx: 905-812-0771 Fx: 39 040 382 137 Fx: 852 27366580 Fx: 91 124 2373118
Ph: 630-377-6580 Xi'an, 710075, China
Fx: 630-377-6495 Ph: +86 29 85387800 System Sensor Europe System Sensor Mexico System Sensor Singapore System Sensor Australia
Free Phone: 800-736-7672 Fx: +86 29 88895930 Ph: 44 (0) 1527 406700 Ph: 54 11 4324-1909 Ph: 65 6273 2230 Ph: 61-3-5428 1142
Web: www.systemsensor.com Web: www.systemsensor.com.cn Fx: 44 (0) 1527 406699 Fx: 54 11 4324-5999 Fx: 61-3-5428 1172
Copyright by Xi'an System Sensor Electronics LTD.