Linear Heat Sensing Cable
Linear Heat Sensing Cable
Linear Heat Sensing Cable
Linear Heat
Detector (LHD)
Models Available
System Sensor 800 series digital linear heat detector and 900
series analogue linear heat detector offer early detection of fire
and overheating conditions in industrial high risk hazards as well
as many types of commercial applications.
Description
The Linear Heat Detection Cable (LHDC) is a continuous heat detector in the form of a cable. It can detect heat at any points
along its entire length. The cable is composed of two twisted shield conductors insulated with a heat sensitive polymer, then
wrapped with a protective tape and finished with an outer covering.
Linear Heat Detection Cable is available in resettable and non-resettable technology. The non-resettable cable is
described as Digital and the resettable as Analogue.
Features
· Multiple configurations for installations:
- Digital type of LHD cables
- Analogue type of LHD cables
· Multiple alarm temperature ratings available for both digital and analogue type
· Maximum zone length (Digital) - 1000 meters
· Maximum zone length (Analogue) – 200 meters
· Resettable temperature up to 120°C (248°F) (Analogue)
· Selectable alarm temperature threshold programmed before shipping (Analogue)
· Normal, fault and alarm indicators on the 900 series modulator (Analogue)
· Compatible with any conventional or intelligent fire alarm panel
· Smoothing algorithms provide false alarm immunity
Typical Wiring Diagrams & Specifications
800 Series:
900 Series:
Ordering Information
Model Description Temperature Ratings UOM
JTW-LD-70-887 70°C (158°F) Meter
JTW-LD-85-887 85°C (185°F) Meter
Digital heat sensing cable, PVC sheath
JTW-LD-105-887 105°C (221°F) Meter
JTW-LD-138-887 138°C (280°F) Meter
JTW-LD-85-887N 85°C (185°F) Meter
JTW-LD-105-887N Digital heat sensing cable, Nylon sheath 105°C (221°F) Meter
800 Series
JTW-LD-138-887N 138°C (280°F) Meter
JTW-LD-70-887S 70°C (158°F) Meter
JTW-LD-85-887S 85°C (185°F) Meter
Digital heat sensing cable, Steel sheath
JTW-LD-105-887S 105°C (221°F) Meter
JTW-LD-138-887S 138°C (280°F) Meter
887/EOL End of Line box for 800 series cable — EA
Pre-selecting range 70 °C~ 130 °C(158°F to 266°F) ,
JTW-LD-997 Analogue heat sensing cable
(factory default setting 85°C (185°F)) Meter
900 Series
997/M Modulator for 900 series cable — EA
997/EOL End of Line box for 900 series cable — EA
Accessories MB Junction Box for 800/900 Series cable — EA
System Sensor Headquarters System Sensor China System Sensor Canada System Sensor Italy System Sensor Far East Ltd System Sensor India
3825 Ohio Avenue 28 Tuan Jie South Road, Ph: 905-812-0767 Ph: 39 040 949 0111 Ph: 852 21919003 Ph: 91 124 2371770-270
St. Charles, IL 60174 Hi-Tech Development Zone Fx: 905-812-0771 Fx: 39 040 382 137 Fx: 852 27366580 Fx: 91 124 2373118
Ph: 630-377-6580 Xi'an, 710075, China
Fx: 630-377-6495 Ph: +86 29 85387800 System Sensor Europe System Sensor Mexico System Sensor Singapore System Sensor Australia
Free Phone: 800-736-7672 Fx: +86 29 88895930 Ph: 44 (0) 1527 406700 Ph: 54 11 4324-1909 Ph: 65 6273 2230 Ph: 61-3-5428 1142
Web: www.systemsensor.com Web: www.systemsensor.com.cn Fx: 44 (0) 1527 406699 Fx: 54 11 4324-5999 Fx: 61-3-5428 1172
Copyright by Xi'an System Sensor Electronics LTD.