12 Eaton - CAP320 - CAPT340 - CAH330 - DS - Sep17
12 Eaton - CAP320 - CAPT340 - CAH330 - DS - Sep17
12 Eaton - CAP320 - CAPT340 - CAH330 - DS - Sep17
This range of intelligent addressable sensors have been The heat sensor (CAH330) can be set to one of 3
specifically designed to operate with Eaton’s Cooper modes 77ºC / 92ºC and rate of rise. These sensors are
intelligent addressable fire systems. designed to be used in environments where the ambient
conditions might cause false alarms if smoke detection
All sensors are third party approved to the relevant were to be used, for example where there is a high
section of EN54 (part 7 for smoke detectors & part 5 for level of dust, fumes, steam or smoke under normal
heat detectors). conditions.
Technical Specification
Code CAP320 CAPT340 CAH330
Description Optical Smoke Sensor Photo-Thermal Sensor Multi-Mode Heat Sensor
Standards EN54 Pt7 2000 + A1:2002, EN54 Pt17 EN54 Pt5 2000 + A1:2002, EN54 Pt7 2000 + A1:2002, EN54 Pt 17 EN54 Pt5 2000 + A1:2002, EN54 Pt17
Specification
Mounting position Ceiling in open areas Ceiling in open areas Ceiling in open areas
Mounting options Surface mount with CAB300 base Surface mount with CAB300 base Surface mount with CAB300 base
Area coverage 100m² (subject to local standard) 100m² (subject to local standard) 100m² (subject to local standard)
System wiring Min. 1.5mm, 2 core loop or spur Min. 1.5mm, 2 core loop or spur Min. 1.5mm, 2 core loop or spur
Heat Class
Indication 360° visibility light pipe 360° visibility light pipe 360° visibility light pipe
Environmental
Physical
Dimensions Excel Base (Dia x D) 101mm x 33mm 101mm x 43mm 101mm x 43mm
Dimensions Incl Base (Dia x D) 104mm x 45mm 104mm x 55m 104mm x 55mm
Compatibility
Suitable for use with Cooper Intelligent Addressable Fire SystemsCooper Intelligent Addressable Fire Systems Cooper Intelligent Addressable Fire Systems