Design Community Gollapudi
Design Community Gollapudi
Design Community Gollapudi
I) Design Parametres:-
As per soil test report,safe load carrying capacity 375mm dia DUR piles
for 6.00m depth is = 260.00KN
Providing five piles,the load carrying capacity of the pile cap will be 1300.00KN
Hence,ultimate load carrying capacity of the pile cap after accounting for water table and 1462.50KN > Total
group action = load
Hence O.K
PC1
Z
375Ø DUR
3117
1 2
2085
1410
X 3 X
14
Critical Sections 4
10 5
for shear Critical Section
for bending about
X-axis
Critical Section
for bending about
Z-axis Z
III) Calculation of pile reactions:-
2 2
Load on 'i' th pile Pi = Q/n ± Mzxi/∑x ± Mxzi/∑z
All the pile reactions are safe.Hence the design of the pile cap is carried out for the pile cap
dimensions given below:-
Pile Reactions contributing to bending moment & corresponding lever arm about critical section:-
262.15mm
However assume 750mm over all depth,then effective depth comes to 690.00mm
250.54mm
However assume 750mm over all depth,then effective depth comes to 690.00mm
The critical section for punching shear is located at d/2 from the face of the column.
The critical section of one way shear is at a distance of 'd' from the face of the column
Pile reactions contributing to one-way shear for the sections located at a distance 'd' from the face of column
1 P1 306.06
P4 243.29
549.35
2 P2 311.21
P5 248.44
559.65
3 P1 55.0908
P2 56.0178
111.1086
4 P4 43.7922
P5 44.7192
88.5114
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.47
0.588 >0.389
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile
force ' H ' resulting from truss action,because av /d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 557.52KN
Area of steel required to resist the above above tensile force A st = 1281.66sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
I) Design Parametres:-
As per soil test report,safe load carrying capacity 375mm dia DUR piles
for 5.00m depth is = 230.00KN
As per clause 5.2.7.2 of IS:2911(Part III)-1980,the minimum spacing between the centre to centre of bored DUR
piles should not be less than 1.5Du.
Providing four piles,load carrying capacity of the pile cap after accounting for water table will be 690.00KN
690.00KN
Hence,ultimate load carrying capacity of the pile cap = 1035.00KN > Total load
Hence O.K
1.41
1.41
X X
Y
As such,the dimensions of the pile cap of as given below:-
The length of pile cap proposed = 2.085m
The width of pile cap proposed = 2.085m
Distance between c/c of piles = L = 1.410m
Depth of pile cap assumed = D = 0.650m
Effective depth = d = 0.565m
Shear span av = 0.405m
192.57mm
However assume 650mm overall depth,then the effective depth comes to 567.00mm
Hence No.of 16mm dia bars to be provided within pile diametre = 13Nos
201.42mm
However assume 650mm overall depth,then the effective depth comes to 567.00mm
Hence No.of 16mm dia bars to be provided within pile diametre = 13Nos
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 2.8
0.944 >0.392
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
H = Pu/24Ld[3L2-b2] = 181.29KN
Area of steel required to resist the above above tensile force A st = 416.76sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
I) Design Parametres:-
As per soil test report,safe load carrying capacity 375mm dia DUR piles
for 5.00m depth is = 230.00KN
Hence,ultimate load carrying capacity of the 3 pile cap after accounting for water table = 776.25KN > Total load
Hence O.K
0.70
375mm Ø DUR
1
1.4
X X
2.09
155.38mm
However assume 650mm overall depth,then the effective depth comes to 567.00mm
Hence No.of 16mm dia bars to be provided within pile diametre = 10Nos
155.38mm
However assume 750mm overall depth,then the effective depth comes to 567.00mm
Hence No.of 16mm dia bars to be provided within pile diametre = 10Nos
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.6
0.504 >0.364
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
H = Pu/24Ld[3L2-b2] = 127.57KN
Area of steel required to resist the above above tensile force A st = 293.26sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
I) Design Parametres:-
As per soil test report,safe load carrying capacity 375mm dia DUR piles
for 5.00m depth is = 230.00KN
Ultimate load carrying capacity of the pile cap after accounting for water table = 524.40KN > Total load
Hence O.K
2.09
0.70
1.41
254.57mm
However assume 750mm overall depth,then the effective depth comes to 690.00mm
Hence No.of 16mm dia bars to be provided within pile diametre = 6Nos
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.94
0.698 >0.511
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 229.55KN
Area of steel required to resist the above above tensile force A st = 527.70sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-
I) Design Parametres:-
As per soil test report,safe load carrying capacity 300mm dia DUR piles
for 5.00m depth is = 170.00KN
Hence,ultimate load carrying capacity of the pile cap after accounting for water table = 382.50KN > Total load
Hence O.K
1.73
0.60
1.13
180.24mm
However assume 600mm overall depth,then the effective depth comes to 540.00mm
Hence No.of 16mm dia bars to be provided within pile diametre = 5Nos
The critical section of one way shear is at a distance of 'd' from the face of the column
The design shear strength of concrete for the above steel percentage from
As per clause 40.5.1 of IS 456:2000,the shear strength can be increased by 2d/a v times for the sections located
at a distance closer than 2d from concentrated load or face of support,where a v is the shear span
2d/av = 1.93
0.755 >0.442
Though,the truss action is not pre-dominant,the tensile reinforcement should be checked for horizontal tensile force ' H '
resulting from truss action,because av/d ratio is not more than 2.
Hd=(Pu/2)[L/2-a/4]
H = Pu/8d[2L-a] = 132.03KN
Area of steel required to resist the above above tensile force A st = 303.52sqmm
The tensile reinforcement provided is more than the above value.Hence O.K
d) Bursting steel:-