Line Protection
Line Protection
Sompol Chumnanvanichkul
G F1
50 I s > 7380 A 50
Zs = 10 ohm
G 50 F2
I s < 6640 A
1
Transmission line protection
Since the impedance of a transmission line
is proportional to its length, for distance
measurement it is appropriate to use a relay
capable of measuring the impedance of a
line up to a predetermined point. Such a
relay is called distance relay ( 21 ).
2
Transmission line protection
ZS Ir Z line
Vs 21 Vr Zr Z load
ZF
Vs 21 VF Z load
3
Transmission line protection
of
of
Operating condition or
Ia
CT Ib
Ic
In
Va
Vb
Vc
CB FUSE
VT
4
Since the relay see current via CT and voltage
via VT, so actual impedance that relay seen is :
I1 / I2 Zp
G
21
VFP
V1 / V2 IFP
ZR = VR = VFP x V2 / V1
IR IFP x I2 / I1
ZR = VFP x I1 / I2
IFP V1 / V2
ZR = ZP x CT ratio
VT ratio
Z = R + jX Ω
5
Relation between rectangular and polar form
Rectangular form Z = R + jX Ω
Polar form PƟ
R = P cos Ɵ
X = P sin Ɵ P =√ R2 + X2
Ɵ = tan-1 X/R
Ɵ2 Ɵ1
R
Load area
Normally pf
-/+ 0.95 – 1.00
( +/- 20o )
R-X diagram
6
Transmission line protection
A B C D
R1+jX1 = Z1/ Ɵ1 R2+jX2 = Z2/ Ɵ2 R3+jX3 = Z3/ Ɵ3
jX
D
X3
Z3
C Ɵ3
X2
Z2
B Ɵ2
X1
Z1
Load area
A Ɵ1 R
R1 R2 R3
A B C
R1+jX1 = Z1/ Ɵ1 R2+jX2 = Z2/ Ɵ2
jX
C
X2
X1
B
A R
R1 R2
Load area
Load impedance change to fault impedance on R – X diagram
7
Compare V restraint with IZ, operate if
V rest < IZ : no account taken of phase angles so
characteristic is a circle
jIX jX
IZ Z
V rest ZF
IR R
Divide by I
jX
C
B
R
8
Mho relay
Directional circular characteristic obtained by
introducing V polarising into the operate circuit.
Input to comparator
V restraint ( VF) from faulty phase
I operate ( IF) from faulty phase
V polarising
VF = self polarised
Or a
Vsound phase = fully cross-polarised combination
of these
VF + xVs.p. = partially cross-polarised
Vpre-fault = memory polarised
9
Phase comparator
Two inputs : S1 and S2
Operation when S2 lags S1 by between 900 and 2700
S2 S2
S2 S1
Operate
S2S2
Restrain when S2 is within +/- 900 of S1
S2 S2 Restrain
S2
S1
S2 S2
V2
S1 = V + IZ
TRIP V3
S2 = V - IZ
IR
Voltage to relay = V
Current to relay = I
Replica impedance = Z
Setting = IZ
- IZ
10
Trip condition : 900 < /S1-S2 < 2700
jX
Z
ZF1
ZF2
TRIP ZF3
when V = IZF
Dividing by I ;
S1 = ZF + Z
-Z S2 = ZF - Z
11
A B C
R1+jX1 = Z1/ Ɵ1 R2+jX2 = Z2/ Ɵ2
jX
HR C
X2
Zone2
X1
B
Zone1
HR
Total
Z
A R
R1 R2
zone2
zone1
Zo
ne
1&
2
R
Quadrilateral
zone3
12
Transmission line protection
A B
ZL
G
21 HR
jX
B HR
R
A
Quadrilateral and HR
Z2
Power swing
blocking band
Z1
Z3 Directional Line
13
Distance relay characteristics
jX
X3 T3
X2 T2
X1B T1B
X1 T1
R1 R1B R2 R3 R
R1E
ZONE CHARACTERISTICS
14
Transmission line protection
What happen if we set zone 1 as 100% line?
Z1A
A B Z1B C
Z1B
Z1C
Zone1 Error
15
Transmission line protection
Stepped distance protection
- 3 zone of protection, zone1, zone2, zone3
- 3 difference tripping time Z3A+T3A
Z2A+T2A
Z1A
Z3B+ T3B
Z2B+ T2B
A B Z1B C
Z1B
Z2B+ T2B
Z3B+ T3B Z1C
Z2C+T2C
Z3C+ T3C
A B C D
R1+jX1 = Z1/ Ɵ1 R2+jX2 = Z2/ Ɵ2 R3+jX3 = Z3/ Ɵ3
jX
D
X3
Zone3
C
X2
Zone2
B
X1
Zone1
A R
R1 R2 R3
16
A B C D Zone3
R1+jX1 = Z1/ Ɵ1 R2+jX2 = Z2/ Ɵ2 R3+jX3 = Z3/ Ɵ3
B
Zone2
jX C
D Zone1
C
Zone3
A Zone2
C B
Zone1
Zone2 B
BA
Zone1
A
A R
A B C D
R1+jX1 = Z1/ Ɵ1 R2+jX2 = Z2/ Ɵ2 R3+jX3 = Z3/ Ɵ3
jX
D
A R
17
A B C D
R1+jX1 = Z1/ Ɵ1 R2+jX2 = Z2/ Ɵ2 R3+jX3 = Z3/ Ɵ3
jX
D
A R
18
Ex Calculation of 21
Data
- Base voltage =115 kV
- Base MVA = 100 MVA
- CT ratio = 800/5
- PT ratio 115/115 kV/V
- Conductor type : 477 MCM AAC – 590 A
Data
- Length of line AB = 70 km, line BC = 30 km, line BD = 50 km
- Impedance data :
AB : Z1= Z2 = 9.7 + j29.1 Ωp , Z0 = 25.4 + j101 Ωp
BC : Z1= Z2 = 5.8 + j16.9 Ωp
BD : Z1= Z2 = 8 + j25 Ωp
C
21 D
A B
19
Multiply by 0.16, so
AB : Z1= Z2 = 1.55 + j4.65 Ωs , Z0 = 4 + j16.1 Ωs
= 4.91 71.5° Ωs
BC : Z1= Z2 = 0.92 + j2.7 Ωs
BD : Z1= Z2 = 1.28 + j4 Ωs
Setting
Zone 1 = 85% line AB = 4.17 71.5° Ωs
Zone2 = 120% line AB = 5 71.5° Ωs , 0.5 sec
Zone3 = 100% line AB + 120% line BD = 9.94 71.9° Ωs ,1 sec
jX
zone3
zone2
B
zone1
71.5°
R
A
20
Earth fault compensate
Kn = ( Z0 – Z1 ) / 3Z1
= 0.799 6.15°
Tele Protection
21
Transmission line protection
Because zone 1 cannot clear fault at the end
of line ( 15-20 % ), fault must be cleared by
zone 2 with delay time T2. Too slow!
To solve this problem ‘ communication system ’
is required.
22
Transmission line protection
1. Permissive underreach transfer trip ( PUTT )
- Send carrier by zone 1
- High speed trip ( by pass T2 ) when
zone 2 start and carrier received
& &
Z1 Z1
Trip Trip 1
Z2 T2 1
T2 Z2
Z3 T3 T3 Z3
23
Permissive Underreach Scheme
END
ZONE
Z3G
Z2G
Z1G
A G H J
Z1H
Z2H
Z3H
END
ZONE
Z1H
Z2H
Z3H
INTERNAL FAULT
24
Transmission line protection
2. Permissive overreach transfer trip ( POTT )
- Send carrier by zone 2
- High speed trip ( bypass T2 ) when
zone 2 start and carrier received
& &
Z1 Z1
Trip Trip 1
Z2 T2 1
T2 Z2
Z3 T3 T3 Z3
25
Permissive Overreach Scheme
END
ZONE
Z3G
Z2G
Z1G
A G H J
Z1H
Z2H
Z3H
END
ZONE
Z1H
Z2H
Z3H
INTERNAL FAULT
26
Transmission line protection
Benefit of teleprotection
- clear fault 100% line as fast as zone 1
- no more over trip
- also initiate recloser as zone 1
27
POWER SWING BLOCKING
R
X2
T2 LOAD AREA
X1B T1B
t
X1 T1
R1 R1B R2 R3 R4
R
R1E
28
POWER SWING BLOCKING
Wrong operation!
29
POWER SWING BLOCKING
jX
X4 T4
X3 T3
R
X2
T2 LOAD AREA
X1B T1B
X1 T1
t
FAULT R1 R1B R2 R3 R4
R
R1E
R
X2
T2 LOAD AREA
X1B T1B
X1 T1
t
PSW R1 R1B R2 R3 R4
R
R1E
30
Transmission line protection
Fuse failure
Distance relay calculate impedance by the
ratio of voltage to current. If voltage goes to zero,
impedance will be zero also. Zero impedance
means fault is very close to distance relay and
should trip the transmission line.
31
Transmission line protection
Switch OnTo Fault ( SOTF )
For safty in transmission line maintenance, the
line should be grounded for all 3 phases. After
finish the job, sometime ground are forgotten to
remove from line. When CB is closed, it closed to
fault.
32
SWITCH ON TO FAULT
A B
21
A B
Manual Close
21
A B
21 SOTF
A B
SWITCH ON TO FAULT
A 21 21
B
A 21 Z1 Z1 21 B
Auto-reclose
A 21 21
B
21 SOTF 21
33
STUB PROTECTION
500 kV BUS NO.2
LINE
Pickup Current
.
500 kV BUS NO.1
34
DEAD TIME
Dead time
35
Transmission line protection
Synchrocheck relay ( 25 )
- Supervise recloser relay befor close circuit
breaker by check voltage level, frequency, and
phase angle at both sides of circuit breaker
(Sync. Function , BH-LH or LL-LB)
A B
79 PT LINE PT LINE 79
25 25
PT BUS PT BUS
36
Synchrocheck
Minimum voltage = 80% Vn
Voltage Check
AUTO-RECLOSE OPERATION
1. Relay initiate
4. 79CO “ON”
5. CB ready
37
Back up Protection
Principle of Breaker failure
Measure the duration of fault current from the
instance at which any relay operates to trip
circuit breaker. If current is still flowing after
preselected time delay, it is considered that the
circuit breaker has failed to trip.
Back up Protection
Principle of Breaker failure
Normally breaker failure timer should less than
zone 2 timer of distance relay at remote end
substation to limit the tripping area only in
substation that breaker fail.
38
Back up Protection POSITIVE
50BF
Back up Protection
Function of Breaker failure
When breaker fail to trip, the tripping and
interlocking of all other circuit breakers
connected to the failed circuit breaker will be
initiated. Another lockout relay, 86BF, is
required.
39
Back up Protection
MAIN BUS
1 2 3
4
MAIN AND TRANSFER BUS
2 5 8
3 6 9
40
MAIN BUS NO.1
Back up Protection
1 4 7
2 5 8
3 6 9
Back up Protection
4
1 2 3 5 6
BREAKER COUPLER
41
Back up Protection
4
1 2 3 5 6
BREAKER COUPLER
A
Back up Protection
B
1 4
2 5
Communication link
3 6
42
A
Back up Protection
B
1 4
2 5
Communication link
3 6
62BF
Time delay = 300 ms (115 kV)
200 ms (230, 500 kV)
43