ACI 318-19 Requirements
ACI 318-19 Requirements
ACI 318-19 Requirements
Outline
4. Beams.
5. One- Way Joist Slabs.
One-Way Slab
7.3.1 Minimum slab thickness
7.3.1.1 For solid non-prestressed slabs not supporting or attached to partitions or other construction likely
to be damaged by large deflections, overall slab thickness ℎ shall not be less than the limits in Table 7.3.1.1,
unless the calculated deflection limits of 7.3.2 are satisfied.
[1] Expression applicable for normal weight concrete and 𝑓𝑓𝑦𝑦 = 420 𝑀𝑀𝑀𝑀𝑀𝑀. For other cases, minimum ℎ shall
be modified in accordance with 7.3.1.1.1 through 7.3.1.1.3 as appropriate.
7.3.1.1.1 For 𝑓𝑓𝑓𝑓 other than 420 MPa, the expressions in Table 7.3.1.1 shall be multiplied by
(0.4 + 𝑓𝑓𝑦𝑦 /700).
7.3.1.1.2 For non-prestressed slabs made of lightweight concrete having 𝒘𝒘𝒄𝒄 in the range of 1440 to
1840 kg/m3, the expressions in Table 7.3.1.1 shall be multiplied by the greater of (a) and (b):
9.6.3.4 If shear reinforcement is required and torsional effects can be neglected according to 9.5.4.1, 𝐴𝐴𝑣𝑣,𝑚𝑚𝑚𝑚𝑚𝑚 shall be
in accordance with Table 9.6.3.4.
9.6.4.2 If torsional reinforcement is required, minimum transverse reinforcement (𝑨𝑨𝒗𝒗 + 𝟐𝟐𝑨𝑨𝒕𝒕 )𝒎𝒎𝒎𝒎𝒎𝒎 /𝒔𝒔 shall be the
greater of (a) and (b):
𝑏𝑏
( a ) 0.062 𝑓𝑓𝑓𝑐𝑐 𝑓𝑓𝑤𝑤
𝑦𝑦𝑦𝑦
𝑏𝑏𝑤𝑤
( b ) 0.35 𝑓𝑓𝑦𝑦𝑦𝑦
9.6.4.3 If torsional reinforcement is required, minimum area of longitudinal reinforcement Aℓ,min shall be the lesser of
(a) and (b):
0.42 𝑓𝑓′𝑐𝑐 𝐴𝐴𝑐𝑐𝑐𝑐 𝐴𝐴𝑡𝑡 𝑓𝑓𝑦𝑦𝑦𝑦 0.42 𝑓𝑓′𝑐𝑐 𝐴𝐴𝑐𝑐𝑐𝑐 0.175𝑏𝑏𝑤𝑤 𝑓𝑓𝑦𝑦𝑦𝑦
(a) − 𝑃𝑃ℎ (b) − 𝑃𝑃ℎ
𝑓𝑓𝑦𝑦 𝑠𝑠 𝑓𝑓𝑦𝑦 𝑓𝑓𝑦𝑦 𝑓𝑓𝑦𝑦𝑦𝑦 𝑓𝑓𝑦𝑦
25.2.1 For parallel non-prestressed reinforcement in a horizontal layer, clear spacing shall be at least the greatest of
25 mm, 𝒅𝒅𝒃𝒃 , and (4/3) 𝒅𝒅𝒂𝒂𝒂𝒂𝒂𝒂 .
25.2.2 For parallel non-prestressed reinforcement placed in two or more horizontal layers, reinforcement in the
upper layers shall be placed directly above reinforcement in the bottom layer with a clear spacing between layers of
at least 25 mm.
7.7.2.3 For non-prestressed and Class T and C prestressed slabs with unbonded tendons, maximum spacing s of
deformed longitudinal reinforcement shall be the lesser of 3h and 450 mm.
7.5.2.3 If primary flexural reinforcement in a slab that is considered to be a T-beam flange is parallel to the
longitudinal axis of the beam, reinforcement perpendicular to the longitudinal axis of the beam shall be provided in
the top of the slab in accordance with (a) and (b). This provision does not apply to joist construction.
(a) Slab reinforcement perpendicular to the beam shall be designed to resist the factored load on the
overhanging slab width assumed to act as a cantilever.
(b) Only the effective overhanging slab width in accordance with 6.3.2 need be considered.
7.6.4.1 Reinforcement shall be provided to resist shrinkage and temperature stresses in accordance with 24.4.
24.4.3.1 Deformed reinforcement to resist shrinkage and temperature stresses shall conform to Table 20.2.2.4(a) and
shall be in accordance with 24.4.3.2 through 24.4.3.5.
24.4.3.2 The ratio of deformed shrinkage and temperature reinforcement area to gross concrete area shall be greater
than or equal to 0.0018.
24.4.3.3 The spacing of deformed shrinkage and temperature reinforcement shall not exceed the lesser of 5h and 450
mm.
24.4.3.4 At all sections where required, deformed reinforcement used to resist shrinkage and temperature stresses
shall develop 𝑓𝑓𝑓𝑓 in tension.
For 𝒇𝒇𝒚𝒚 exceeding 550 MPa, the calculated deflection limits in 8.3.2 shall be satisfied assuming a reduced modulus
of rupture 𝑓𝑓𝑟𝑟 = 0.41 𝑓𝑓′𝑐𝑐 .
Table 8.3.1.1 Minimum thickness of non-prestressed two-way slabs without interior beams (𝑚𝑚𝑚𝑚)[1] :
[1] 𝑙𝑙𝑛𝑛 is the clear span in the long direction, measured face-to-face of supports (mm).
[2] For 𝑓𝑓𝑦𝑦 between values given in the table, minimum thickness shall be calculated by liner interpolation.
[3] Drop panels as given in 8.2.4.
[4] Slabs with beams between columns along exterior edges. Exterior panels shall be considered to be without edge
beams if 𝜶𝜶𝒇𝒇 is less than 0.8.
(a) The drop panel shall project below the slab at least one-fourth of the adjacent slab thickness.
(b) (b) The drop panel shall extend in each direction from the centerline of support a distance not less
than one-sixth the span length measured from center-to-center of supports in that direction.
8.2.5 A shear cap, where used to increase the critical section for shear at a slab-column joint, shall project below the
slab soffit and extend horizontally from the face of the column a distance at least equal to the thickness of the
projection below the slab soffit.
8.3.1.2 For non-prestressed slabs with beams spanning between supports on all sides, overall slab thickness h shall
satisfy the limits in Table 8.3.1.2, unless the calculated deflection limits of 8.3.2 are satisfied.
[1] 𝛼𝛼𝑓𝑓𝑓𝑓 is the average value of 𝛼𝛼𝑓𝑓 for all beams on edges of a panel.
[2] 𝑙𝑙𝑛𝑛 is the clear span in the long direction, measured face-to-face of supports (mm).
[3] β is the ratio of clear spans in long to short directions of slab.
8.3.1.2.1 At discontinuous edges of slabs conforming to 8.3.1.2, an edge beam with 𝛼𝛼𝑓𝑓 ≥ 0.80 shall be provided,
or the minimum thickness required by (b) or (d) of Table 8.3.1.2 shall be increased by at least 10 percent in the
panel with a discontinuous edge.
8.3.1.4 If single- or multiple-leg stirrups are used as shear reinforcement, the slab thickness shall be sufficient to
satisfy the requirements for d in 22.6.7.1
22.6.7.1 Single- or multiple-leg stirrups fabricated from bars or wires shall be permitted to be used as shear
reinforcement in slabs and footings satisfying (a) and (b):
(a) d is at least 150 mm.
(b) d is at least 𝟏𝟏𝟏𝟏𝒅𝒅𝒃𝒃 , where 𝒅𝒅𝒃𝒃 is the diameter of the stirrups.
25.2.1 For parallel non-prestressed reinforcement in a horizontal layer, clear spacing shall be at least the greatest of
25 mm, 𝒅𝒅𝒃𝒃 , and (4/3) 𝒅𝒅𝒂𝒂𝒂𝒂𝒂𝒂 .
25.2.2 For parallel non-prestressed reinforcement placed in two or more horizontal layers, reinforcement in the
upper layers shall be placed directly above reinforcement in the bottom layer with a clear spacing between layers of
at least 25 mm.
8.7.2.2 For non-prestressed solid slabs, maximum spacing S of deformed longitudinal reinforcement shall be the
lesser of 2h and 450 mm at critical sections, and the lesser of 3h and 450 mm at other sections.
8.7.3.1 At exterior corners of slabs supported by edge walls or where one or more edge beams have a value of 𝛼𝛼𝑓𝑓
greater than 1.0, reinforcement at top and bottom of slab shall be designed to resist 𝑀𝑀𝑢𝑢 per unit width due to corner
effects equal to the maximum positive 𝑀𝑀𝑢𝑢 per unit width in the slab panel.
8.7.3.1.1 Factored moment due to corner effects, 𝑀𝑀𝑢𝑢 , shall be assumed to be about an axis perpendicular to the
diagonal from the corner in the top of the slab and about an axis parallel to the diagonal from the corner in the
bottom of the slab.
8.7.3.1.2 Reinforcement shall be provided for a distance in each direction from the corner equal to one-fifth the
longer span.
8.7.3.1.3 Reinforcement shall be placed parallel to the diagonal in the top of the slab and perpendicular to the
diagonal in the bottom of the slab. Alternatively, reinforcement shall be placed in two layers parallel to the sides of
the slab in both the top and bottom of the slab.
Notes:
1. Applies when B-2 or B-2 has 𝛼𝛼𝑓𝑓 > 1.0
2. Maximum bar spacing 2ℎ, Where ℎ = slab thickness.
8.7.6.1 Single-leg, simple-U, multiple-U, and closed stirrups shall be permitted as shear reinforcement.
8.7.6.3 If stirrups are provided, location and spacing shall be in accordance with Table 8.7.6.3
8.7.7.1 Headed shear stud reinforcement shall be permitted if placed perpendicular to the plane of the slab.
8.7.7.1.1 The overall height of the shear stud assembly shall be at least the thickness of the slab minus the sum of (a)
through (c):
8.8.1 General
8.8.1.1 Non-prestressed two-way joist construction consists of a monolithic combination of regularly spaced ribs
and a top slab designed to span in two orthogonal directions.
8.8.1.2 Width of ribs shall be at least 100 mm at any location along the depth.
8.8.1.3 Overall depth of ribs shall not exceed 3.5 times the minimum width.
8.8.1.4 Clear spacing between ribs shall not exceed 750 mm.
8.8.1.5 𝑽𝑽𝒄𝒄 shall be permitted to be taken as 1.1 times the value calculated in 22.5.
8.8.1.6 For structural integrity, at least one bottom bar in each joist shall be continuous and shall be anchored to
develop 𝑓𝑓𝑦𝑦 at the face of supports.
8.8.1.7 Reinforcement area perpendicular to the ribs shall satisfy slab moment strength requirements, considering
load concentrations, and shall be at least the shrinkage and temperature reinforcement area in accordance with 24.4.
8.8.1.8 Two-way joist construction not satisfying the limitations of 8.8.1.1 through 8.8.1.4 shall be designed as slabs
and beams.
The Reinforced Concrete Buildings Design Eng. Sami Alezzo
Two-Way Joist Slab ( Waffle Slab )
8.8.2.1 If permanent burned clay or concrete tile fillers of material having a unit compressive strength at least equal
to 𝑓𝑓′𝑐𝑐 in the joists are used, 8.8.2.1.1 and 8.8.2.1.2 shall apply.
8.8.2.1.1 Slab thickness over fillers shall be at least the greater of one-twelfth the clear distance between ribs and 40
mm.
9.3.1.1 For non-prestressed beams not supporting or attached to partitions or other construction likely to be
damaged by large deflections, overall beam depth h shall satisfy the limits in Table 9.3.1.1, unless the
calculated deflection limits of 9.3.2 are satisfied.
[1] Expression applicable for normal weight concrete and 𝑓𝑓𝑦𝑦 = 420 𝑀𝑀𝑀𝑀𝑀𝑀. For other cases, minimum ℎ shall
be modified in accordance with 9.3.1.1.1 through 7.3.1.1.3 as appropriate.
9.3.1.1.1 For 𝑓𝑓𝑓𝑓 other than 420 MPa, the expressions in Table 9.3.1.1 shall be multiplied by
(0.4 + 𝑓𝑓𝑦𝑦 /700).
7.3.1.1.2 For non-prestressed beams made of lightweight concrete having 𝒘𝒘𝒄𝒄 in the range of 1440 to
1840 kg/m3, the expressions in Table 9.3.1.1 shall be multiplied by the greater of (a) and (b):
9.3.2.1 For non-prestressed beams not satisfying 9.3.1 and for prestressed beams, immediate and time-
dependent deflections shall be calculated in accordance with 24.2 and shall not exceed the limits in
24.2.2
9.6.1.1 A minimum area of flexural reinforcement,𝐴𝐴𝑠𝑠,𝑚𝑚𝑚𝑚𝑚𝑚 , shall be provided at every section where
tension reinforcement is required by analysis.
9.6.1.2 𝐴𝐴𝑠𝑠,𝑚𝑚𝑚𝑚𝑚𝑚 shall be the larger of (a) and (b), except as provided in 9.6.1.3. For a statically determinate
beam with a flange in tension, the value of 𝑏𝑏𝑤𝑤 shall be the smaller of 𝑏𝑏𝑓𝑓 and 2𝑏𝑏𝑤𝑤 . The value of 𝑓𝑓𝑦𝑦 shall be
limited to a maximum of 550 𝑀𝑀𝑃𝑃𝑎𝑎.
0.25 𝑓𝑓𝑓𝑐𝑐
(a) 𝑏𝑏𝑤𝑤 𝑑𝑑
𝑓𝑓𝑦𝑦
1.4
(b) 𝑏𝑏𝑤𝑤 𝑑𝑑
𝑓𝑓𝑦𝑦
9.6.1.3 If 𝐴𝐴𝑠𝑠 provided at every section is at least one-third greater than 𝐴𝐴𝑠𝑠 required by analysis, 9.6.1.1
and 9.6.1.2 need not be satisfied.
9.6.3.4 If shear reinforcement is required and torsional effects can be neglected according to 9.5.4.1,
𝐴𝐴𝑣𝑣,𝑚𝑚𝑚𝑚𝑚𝑚 shall be in accordance with Table 9.6.3.4.
𝑏𝑏𝑤𝑤
0.062 𝑓𝑓𝑓𝑐𝑐 (a)
𝑓𝑓𝑦𝑦𝑦𝑦
Non-prestressed Greater of:
𝑏𝑏𝑤𝑤
0.35 (b)
𝑓𝑓𝑦𝑦𝑦𝑦
9.6.4.1 A minimum area of torsional reinforcement shall be provided in all regions where 𝑻𝑻𝒖𝒖 ≥ ∅ 𝑻𝑻𝒕𝒕𝒕𝒕 in
accordance with 22.7.
9.6.4.2 If torsional reinforcement is required, minimum transverse reinforcement (𝑨𝑨𝒗𝒗 + 𝟐𝟐𝑨𝑨𝒕𝒕 )𝒎𝒎𝒎𝒎𝒎𝒎 /𝒔𝒔 shall
be the greater of (a) and (b):
𝑏𝑏𝑤𝑤
( a ) 0.062 𝑓𝑓𝑓𝑐𝑐
𝑓𝑓𝑦𝑦𝑦𝑦
𝑏𝑏𝑤𝑤
( b ) 0.35
𝑓𝑓𝑦𝑦𝑦𝑦
9.6.4.3 If torsional reinforcement is required, minimum area of longitudinal reinforcement 𝑨𝑨𝒍𝒍,𝒎𝒎𝒎𝒎𝒎𝒎 shall be the lesser
of (a) and (b):
0.42 𝑓𝑓′𝑐𝑐 𝐴𝐴𝑐𝑐𝑐𝑐 𝐴𝐴𝑡𝑡 𝑓𝑓𝑦𝑦𝑦𝑦 0.42 𝑓𝑓′𝑐𝑐 𝐴𝐴𝑐𝑐𝑐𝑐 0.175𝑏𝑏𝑤𝑤 𝑓𝑓𝑦𝑦𝑦𝑦
(a) − 𝑝𝑝ℎ (b) − 𝑝𝑝ℎ
𝑓𝑓𝑦𝑦 𝑠𝑠 𝑓𝑓𝑦𝑦 𝑓𝑓𝑦𝑦 𝑓𝑓𝑦𝑦𝑦𝑦 𝑓𝑓𝑦𝑦
25.2.1 For parallel non-prestressed reinforcement in a horizontal layer, clear spacing shall be at least the greatest of
25 mm, 𝒅𝒅𝒃𝒃 , and (4/3) 𝒅𝒅𝒂𝒂𝒂𝒂𝒂𝒂 .
25.2.2 For parallel non-prestressed reinforcement placed in two or more horizontal layers, reinforcement in the
upper layers shall be placed directly above reinforcement in the bottom layer with a clear spacing between layers of
at least 25 mm.
9.7.2.3 For non-prestressed and Class C prestressed beams with h exceeding 900 mm, longitudinal skin
reinforcement shall be uniformly distributed on both side faces of the beam for a distance h/2 from the
tension face. Spacing of skin reinforcement shall not exceed s given in 24.3.2, where 𝑪𝑪𝒄𝒄 is the clear cover
from the skin reinforcement to the side face. It shall be permitted to include skin reinforcement in
strength calculations if a strain compatibility analysis is made.
24.3.2 Spacing of bonded reinforcement closest to the tension face shall not exceed the limits in
Table 24.3.2, where cc is the least distance from surface of deformed or prestressed reinforcement to
the tension face. Calculated stress in deformed reinforcement, 𝑓𝑓𝑠𝑠 , and calculated change in stress in
bonded prestressed reinforcement, ∆𝑓𝑓𝑠𝑠 , shall be in accordance with 24.3.2.1 and 24.3.2.2,
respectively.
9.7.6.2.1 If required, shear reinforcement shall be provided using stirrups, hoops, or longitudinal bent
bars.
2
𝜆𝜆𝑠𝑠 =
1+0.004 𝑑𝑑
𝐴𝐴𝑣𝑣 𝑓𝑓𝑦𝑦 𝑑𝑑
The beam’s nominal steel shear strength is calculated by: 𝑉𝑉𝑠𝑠 =
𝑠𝑠
The designer usually calculate the required 𝑉𝑉𝑠𝑠 and then determine the stirrup size and spacing, so
𝑉𝑉
equation is rearranged as: 𝐴𝐴𝑣𝑣 ⁄𝑠𝑠 = 𝑠𝑠
𝑓𝑓𝑦𝑦 𝑑𝑑
𝐴𝐴𝑣𝑣 𝑓𝑓𝑦𝑦𝑦𝑦 𝑑𝑑
The required stirrup spacing to satisfy strength requirement is: 𝑠𝑠 ≤
𝑣𝑣𝑠𝑠
where the required nominal shear strength provided by shear reinforcement: 𝑉𝑉𝑠𝑠 = 𝑉𝑉𝑢𝑢 ⁄∅ − 𝑉𝑉𝑐𝑐
Minimum shear 𝑑𝑑
∅𝑉𝑉𝑐𝑐 ⁄2 < 𝑉𝑉𝑢𝑢 ≤ ∅𝑉𝑉𝑐𝑐 𝑠𝑠 ≤ ≤ 600𝑚𝑚𝑚𝑚 9.6.3.1
reinforcement 2
∅𝑉𝑉𝑐𝑐 + ∅ 0.33 𝑓𝑓𝑓𝑐𝑐 𝑏𝑏𝑤𝑤 𝑑𝑑 < 𝑉𝑉𝑢𝑢 ≤ ∅𝑉𝑉𝑐𝑐 + ∅ 0.66 𝑓𝑓𝑓𝑐𝑐 𝑏𝑏𝑤𝑤 𝑑𝑑 Non-prestressed 𝑑𝑑
𝑠𝑠 ≤ ≤ 300𝑚𝑚𝑚𝑚
4
3∅𝑉𝑉𝑐𝑐 < 𝑉𝑉𝑢𝑢 ≤ 5 ∅𝑉𝑉𝑐𝑐 9.7.6.2.2
Prestressed 3ℎ
𝑠𝑠 ≤ ≤ 300𝑚𝑚𝑚𝑚
0.33 𝑓𝑓𝑓𝑐𝑐 𝑏𝑏𝑤𝑤 𝑑𝑑 < 𝑉𝑉𝑠𝑠 ≤ 0.66 𝑓𝑓𝑓𝑐𝑐 𝑏𝑏𝑤𝑤 𝑑𝑑 8
𝑉𝑉𝑢𝑢 > ∅𝑉𝑉𝑐𝑐 + ∅ 0.66 𝑓𝑓𝑓𝑐𝑐 𝑏𝑏𝑤𝑤 𝑑𝑑
𝑑𝑑
𝑠𝑠𝑚𝑚𝑚𝑚𝑚𝑚 ≤ ≤ 600𝑚𝑚𝑚𝑚
2
𝑑𝑑
𝑠𝑠𝑚𝑚𝑚𝑚𝑚𝑚 ≤ ≤ 300𝑚𝑚𝑚𝑚
4
𝑑𝑑
𝑠𝑠𝑚𝑚𝑚𝑚𝑚𝑚 ≤ ≤ 300𝑚𝑚𝑚𝑚
2
9.7.6.3.3 Spacing of transverse torsional reinforcement shall not exceed the lesser of 𝑃𝑃ℎ /8 and 300 mm.
9.2.4.4 For torsional design according to 22.7, the overhanging flange width used to calculate 𝐴𝐴𝑐𝑐𝑐𝑐 , 𝐴𝐴𝑔𝑔 , and 𝑝𝑝𝑐𝑐𝑐𝑐
shall be in accordance with (a) and (b):
Where:
ℎ𝑏𝑏 is the greater of the projection of
the beam above or below the slab.
Figure: Torsional section properties 𝐴𝐴𝑐𝑐𝑐𝑐 and 𝑃𝑃𝑐𝑐𝑐𝑐 for interior and
edge beams cast monolithically with the slab.
22.7.2.1 The value of 𝑓𝑓𝑓𝑐𝑐 used to calculate 𝑇𝑇𝑡𝑡𝑡 and 𝑇𝑇𝑐𝑐𝑐𝑐 shall not exceed 8.3 MPa .
22.7.2.2 The values of 𝑓𝑓𝑦𝑦 and 𝑓𝑓𝑦𝑦𝑦𝑦 for longitudinal and transverse torsional reinforcement shall not exceed
the limits in 20.2.2.4.
R22.7.2.2 The upper limit of 420 𝑀𝑀𝑀𝑀𝑀𝑀 on the values of 𝑓𝑓𝑦𝑦 and 𝑓𝑓𝑦𝑦𝑦𝑦 used in design is intended to control
diagonal crack width.
22.7.4.1 Threshold torsion 𝑇𝑇𝑡𝑡𝑡 shall be calculated in accordance with Table 22.7.4.1(a) for solid cross
sections and Table 22.7.4.1(b) for hollow cross sections, where 𝑁𝑁𝑢𝑢 is positive for compression and
negative for tension.
22.7.4.1 Cracking torsion 𝑇𝑇𝑐𝑐𝑐𝑐 shall be calculated in accordance with Table 22.7.5.1for solid cross
sections and hollow cross sections, where 𝑁𝑁𝑢𝑢 is positive for compression and negative for tension.
22.7.6.1 For non-prestressed and prestressed members, 𝑇𝑇𝑛𝑛 shall be the lesser of (a) and (b):
where 𝐴𝐴0 shall be determined by analysis, θ shall not be taken less than 30 degrees nor greater than 60
degrees; 𝐴𝐴𝑡𝑡 is the area of one leg of a closed stirrup resisting torsion; 𝐴𝐴𝑙𝑙 is the area of longitudinal
torsional reinforcement; and 𝑃𝑃ℎ is the perimeter of the centerline of the outermost closed stirrup.
22.7.6.1.1 In Eq. (22.7.6.1a) and (22.7.6.1b), it shall be permitted to take 𝐴𝐴0 equal to 0.85𝐴𝐴0ℎ .
22.7.1 General
22.7.3.1 If 𝑇𝑇𝑢𝑢 ≥ ∅𝑇𝑇𝑐𝑐𝑐𝑐 and 𝑇𝑇𝑢𝑢 is required to maintain equilibrium, the member shall be designed to resist 𝑇𝑇𝑢𝑢 .
22.7.3.2 In a statically indeterminate structure where 𝑇𝑇𝑢𝑢 ≥ ∅𝑇𝑇𝑐𝑐𝑐𝑐 and a reduction of 𝑇𝑇𝑢𝑢 can occur due to
redistribution of internal forces after torsional cracking, it shall be permitted to reduce 𝑇𝑇𝑢𝑢 to ∅𝑇𝑇𝑐𝑐𝑐𝑐 , where
the cracking torsion 𝑇𝑇𝑐𝑐𝑐𝑐 is calculated in accordance with 22.7.5.
22.7.3.3 If 𝑇𝑇𝑢𝑢 is redistributed in accordance with 22.7.3.2, the factored moments and shears used for design
of the adjoining members shall be in equilibrium with the reduced torsion.
2 2
𝑉𝑉𝑢𝑢 𝑇𝑇𝑢𝑢 𝑃𝑃ℎ 𝑉𝑉𝑐𝑐
+ ≤ 𝜑𝜑 + 0.66 𝑓𝑓𝑐𝑐′
𝑏𝑏𝑤𝑤 𝑑𝑑 1.7𝐴𝐴2𝑜𝑜𝑜 𝑏𝑏𝑤𝑤 𝑑𝑑
9.8.1 General
9.8.1.1 Non-prestressed one-way joist construction consists of a monolithic combination of regularly spaced ribs
and a top slab designed to span in one direction.
9.8.1.2 Width of ribs shall be at least 100 mm at any location along the depth.
9.8.1.3 Overall depth of ribs shall not exceed 3.5 times the minimum width.
9.8.1.4 Clear spacing between ribs shall not exceed 750 mm.
9.8.1.5 𝑽𝑽𝒄𝒄 shall be permitted to be taken as 1.1 times the value calculated in 22.5.
8.8.1.6 For structural integrity, at least one bottom bar in each joist shall be continuous and shall be anchored to
develop 𝑓𝑓𝑦𝑦 at the face of supports.
8.8.1.7 Reinforcement area perpendicular to the ribs shall satisfy slab moment strength requirements, considering
load concentrations, and shall be at least the shrinkage and temperature reinforcement area in accordance with 24.4.
9.8.1.8 One-way joist construction not satisfying the limitations of 9.8.1.1 through 9.8.1.4 shall be designed as slabs
and beams.
8.8.2.1 If permanent burned clay or concrete tile fillers of material having a unit compressive strength at least equal
to 𝑓𝑓′𝑐𝑐 in the joists are used, 9.8.2.1.1 and 9.8.2.1.2 shall apply.
9.8.2.1.1 Slab thickness over fillers shall be at least the greater of one-twelfth the clear distance between ribs and 40
mm.
You
eng.samialezzo@gmail.com
(+971) 525515820