YCAV YCIV Modbus, BACnet MS/TP, N2 Data Map Board: 031-03478

Item Version York P/N Comments


Y.ACS.14.03, Y.ACS.15.03, Y.ACS.16.03, Y.ACS.17.03, 031-03476-001, -002, -003, -
1 Y.ACS.18.03, Y.ACS.19.03, Z.ACS.14.04, Z.ACS.15.03M, 004, -005, -202, -101, -210, - New
Z.ACS.17.03, Z.ACS.19.04, Z.ACS.31.03 104, -AGR, -225
2
3
4
5
6
7
8
9
10

Item BACnet Modbus


Modbus Modbus Data Type Engineering Units Point List Code: S = Standard O = Optional N = Not Available
Ref BACnet Name Object Scaling (See N2 Metasys
Address Supported
Num Instance Note 5) Imperial SI Point List Description 1 2 3 4 5 6 7 8 9 10

ANALOG WRITE POINTS


1 REM_SETP AV1 1026 03,06,16 Div 10 ADF 1 °F °C Remote Setpoint S
2 DMD_LIMIT AV2 1027 03,06,16 Div 10 ADF 2 % FLA % FLA Remote Current Limit Setpoint S
3 SND_LIMIT AV3 1028 03,06,16 Div 10 ADF 3 % % Remote Sound Limit S
4 SPARE AV1 AV4 1029 03,06,16 Div 10 ADF 4 None None Spare N
BINARY WRITE POINTS
5 START_STOP BV1 1538 01,03,05,06,15 N/A BD 1 0/1 0/1 Remote Start / Stop Command [0=Stop, 1=Run] S
6 SPARE_BV1 BV2 1539 01,03,05,06,15 N/A BD 2 0/1 0/1 Spare N
7 SPARE_BV2 BV3 1540 01,03,05,06,15 N/A BD 3 0/1 0/1 Spare N
8 SPARE_BV3 BV3 1541 01,03,05,06,15 N/A BD 3 0/1 0/1 Spare N
ANALOG READ ONLY POINTS
9 LCHLT AI1 514 03,04 x10 ADF 5 °F °C Leaving Chilled Liquid Temperature S
10 ECHLT AI2 515 03,04 x10 ADF 6 °F °C Entering Chilled Liquid Temperature S
11 VSD_IA_TEMP AI3 516 03,04 x10 ADF 7 °F °C VSD Internal Ambient Temperature S
12 S1_SUCT_TEMP AI4 517 03,04 x10 ADF 8 °F °C Sys 1 Suction Temperature S
13 S2_SUCT_TEMP AI5 518 03,04 x10 ADF 9 °F °C Sys 2 Suction Temperature S
14 S3_SUCT_TEMP AI6 519 03,04 x10 ADF 10 °F °C Sys 3 Suction Temperature S
15 S4_SUCT_TEMP AI7 520 03,04 x10 ADF 11 °F °C Sys 4 Suction Temperature S
16 S1_DSCH_TEMP AI8 521 03,04 x10 ADF 12 °F °C Sys 1 Discharge Temperature S
17 S2_DSCH_TEMP AI9 522 03,04 x10 ADF 13 °F °C Sys 2 Discharge Temperature S
18 S3_DSCH_TEMP AI10 523 03,04 x10 ADF 14 °F °C Sys 3 Discharge Temperature S
19 S4_DSCH_TEMP AI11 524 03,04 x10 ADF 15 °F °C Sys 4 Discharge Temperature S
20 OAT AI12 525 03,04 x10 ADF 16 °F °C Ambient Air Temperature S
21 S1_OIL_TEMP AI13 526 03,04 x10 ADF 17 °F °C Sys 1 Oil Temperature S
22 S2_OIL_TEMP AI14 527 03,04 x10 ADF 18 °F °C Sys 2 Oil Temperature S
23 S3_OIL_TEMP AI15 528 03,04 x10 ADF 19 °F °C Sys 3 Oil Temperature S
24 S4_OIL_TEMP AI16 529 03,04 x10 ADF 20 °F °C Sys 4 Oil Temperature S
25 S1_OIL_PRESS AI17 530 03,04 x10 ADF 21 PSI BAR Sys 1 Oil Pressure S
26 S2_OIL_PRESS AI18 531 03,04 x10 ADF 22 PSI BAR Sys 2 Oil Pressure S
27 S3_OIL_PRESS AI19 532 03,04 x10 ADF 23 PSI BAR Sys 3 Oil Pressure S
28 S4_OIL_PRESS AI20 533 03,04 x10 ADF 24 PSI BAR Sys 4 Oil Pressure S
29 S1_SUCT_PRES AI21 534 03,04 x10 ADF 25 PSI BAR Sys 1 Suction Pressure S
30 S2_SUCT_PRES AI22 535 03,04 x10 ADF 26 PSI BAR Sys 2 Suction Pressure S
31 S3_SUCT_PRES AI23 536 03,04 x10 ADF 27 PSI BAR Sys 3 Suction Pressure S

Property of Johnson Controls, Inc.


YCAV_IV Native 17 FEB 2017 Subject to change without notice. 1 of 4
Item BACnet Modbus
Modbus Modbus Data Type Engineering Units Point List Code: S = Standard O = Optional N = Not Available
Ref BACnet Name Object Scaling (See N2 Metasys
Address Supported
Num Instance Note 5) Imperial SI Point List Description 1 2 3 4 5 6 7 8 9 10
32 S4_SUCT_PRES AI24 537 03,04 x10 ADF 28 PSI BAR Sys 4 Suction Pressure S
33 S1_DSCH_PRES AI25 538 03,04 x10 ADF 29 PSI BAR Sys 1 Discharge Pressure S
34 S2_DSCH_PRES AI26 539 03,04 x10 ADF 30 PSI BAR Sys 2 Discharge Pressure S
35 S3_DSCH_PRES AI27 540 03,04 x10 ADF 31 PSI BAR Sys 3 Discharge Pressure S
36 S4_DSCH_PRES AI28 541 03,04 x10 ADF 32 PSI BAR Sys 4 Discharge Pressure S
37 S1_MC_FLA AI29 542 03,04 x10 ADF 33 % % Sys 1 Motor Current FLA S
38 S2_MC_FLA AI30 543 03,04 x10 ADF 34 % % Sys 2 Motor Current FLA S
39 S3_MC_FLA AI31 544 03,04 x10 ADF 35 % % Sys 3 Motor Current FLA S
40 S4_MC_FLA AI32 545 03,04 x10 ADF 36 % % Sys 4 Motor Current FLA S
41 S1_OP_HRS AI33 546 03,04 x1 ADF 37 None None Sys 1 Operating Hours S
42 S2_OP_HRS AI34 547 03,04 x1 ADF 38 None None Sys 2 Operating Hours S
43 S3_OP_HRS AI35 548 03,04 x1 ADF 39 None None Sys 3 Operating Hours S
44 S4_OP_HRS AI36 549 03,04 x1 ADF 40 None None Sys 4 Operating Hours S
45 S1_COMP_ST AI37 550 03,04 x1 ADF 41 None None Sys 1 Compressor Starts S
46 S2_COMP_ST AI38 551 03,04 x1 ADF 42 None None Sys 2 Compressor Starts S
47 S3_COMP_ST AI39 552 03,04 x1 ADF 43 None None Sys 3 Compressor Starts S
48 S4_COMP_ST AI40 553 03,04 x1 ADF 44 None None Sys 4 Compressor Starts S
49 S1_HI_MTR_T AI41 554 03,04 x10 ADF 45 °F °C Sys 1 Highest Motor Temperature S
50 S2_HI_MTR_T AI42 555 03,04 x10 ADF 46 °F °C Sys 2 Highest Motor Temperature S
51 S3_HI_MTR_T AI43 556 03,04 x10 ADF 47 °F °C Sys 3 Highest Motor Temperature S
52 S4_HI_MTR_T AI44 557 03,04 x10 ADF 48 °F °C Sys 4 Highest Motor Temperature S
53 VSD_OUT_FR AI45 558 03,04 x10 ADF 49 Hz Hz VSD Output Frequency S
54 S1_FEED AI46 559 03,04 x10 ADF 50 % % Sys 1 Flash Tank Feed Valve % S
55 S2_FEED AI47 560 03,04 x10 ADF 51 % % Sys 2 Flash Tank Feed Valve % S
56 S3_FEED AI48 561 03,04 x10 ADF 52 % % Sys 3 Flash Tank Feed Valve % S
57 S4_FEED AI49 562 03,04 x10 ADF 53 % % Sys 4 Flash Tank Feed Valve % S
58 S1_OP_CODE AI50 563 03,04 x1 ADF 54 None None Sys 1 Operational Code S
59 S2_OP_CODE AI51 564 03,04 x1 ADF 55 None None Sys 2 Operational Code S
60 S3_OP_CODE AI52 565 03,04 x1 ADF 56 None None Sys 3 Operational Code S
61 S4_OP_CODE AI53 566 03,04 x1 ADF 57 None None Sys 4 Operational Code S
62 S1_FTL_CODE AI54 567 03,04 x1 ADF 58 None None Sys 1 Fault Code S
63 S2_FLT_CODE AI55 568 03,04 x1 ADF 59 None None Sys 2 Fault Code S
64 S3_FTL_CODE AI56 569 03,04 x1 ADF 60 None None Sys 3 Fault Code S
65 S4_FLT_CODE AI57 570 03,04 x1 ADF 61 None None Sys 4 Fault Code S
66 S1_LEVEL AI58 571 03,04 x10 ADF 62 % % Sys 1 Flash Tank Level % S
67 S2_LEVEL AI59 572 03,04 x10 ADF 63 % % Sys 2 Flash Tank Level % S
68 S3_LEVEL AI60 573 03,04 x10 ADF 64 % % Sys 3 Flash Tank Level % S
69 S4_LEVEL AI61 574 03,04 x10 ADF 65 % % Sys 4 Flash Tank Level % S
70 S1_FAN_STG AI62 575 03,04 x1 ADF 66 None None Sys 1 Condenser Fan Stage S
71 S2_FAN_STG AI63 576 03,04 x1 ADF 67 None None Sys 2 Condenser Fan Stage S
72 S3_FAN_STG AI64 577 03,04 x1 ADF 68 None None Sys 3 Condenser Fan Stage S
73 S4_FAN_STG AI65 578 03,04 x1 ADF 69 None None Sys 4 Condenser Fan Stage S
74 LEAD AI66 579 03,04 x1 ADF 70 None None Lead System S
75 LCHLT_SETP AI67 580 03,04 x10 ADF 71 °F °C Leaving Chilled Liquid Setpoint S
76 LCHLT_CUTOUT AI68 581 03,04 x10 ADF 72 °F °C Leaving Chilled Liquid Cutout S
77 S1_DRAIN AI69 582 03,04 x10 ADF 73 % % Sys 1 Flash Tank Drain Valve % S
78 S2_DRAIN AI70 583 03,04 x10 ADF 74 % % Sys 2 Flash Tank Drain Valve % S
79 S3_DRAIN AI71 584 03,04 x10 ADF 75 % % Sys 3 Flash Tank Drain Valve % S
80 S4_DRAIN AI72 585 03,04 x10 ADF 76 % % Sys 4 Flash Tank Drain Valve % S
81 SUCT_PRS_CUT AI73 586 03,04 x10 ADF 77 PSI BAR Suction Pressure Cutout S
82 VSD_DCB_V_13 AI74 587 03,04 x1 ADF 78 Volts Volts VSD DC Bus Voltage Sys 1/3 S

Property of Johnson Controls, Inc.


YCAV_IV Native 17 FEB 2017 Subject to change without notice. 2 of 4
Item BACnet Modbus
Modbus Modbus Data Type Engineering Units Point List Code: S = Standard O = Optional N = Not Available
Ref BACnet Name Object Scaling (See N2 Metasys
Address Supported
Num Instance Note 5) Imperial SI Point List Description 1 2 3 4 5 6 7 8 9 10
83 VSD_DCB_V_24 AI75 588 03,04 x1 ADF 79 Volts Volts VSD DC Bus Voltage Sys 2/4 S
84 REM_SETPOINT AI76 589 03,04 x10 ADF 80 °F °C Remote Leaving Chilled Liquid Setpoint S
85 S1_SUC_SHEAT AI77 590 03,04 x10 ADF 81 °F (diff) °C (diff) Sys 1 Suction Superheat S
86 S2_SUC_SHEAT AI78 591 03,04 x10 ADF 82 °F (diff) °C (diff) Sys 2 Suction Superheat S
87 S3_SUC_SHEAT AI79 592 03,04 x10 ADF 83 °F (diff) °C (diff) Sys 3 Suction Superheat S
88 S4_SUC_SHEAT AI80 593 03,04 x10 ADF 84 °F (diff) °C (diff) Sys 4 Suction Superheat S
89 COOLING_RNG AI81 594 03,04 x10 ADF 85 °F °C Cooling Range S
90 S1_DSC_SHEAT AI82 595 03,04 x10 ADF 86 °F (diff) °C (diff) Sys 1 Discharge Superheat S
91 S2_DSC_SHEAT AI83 596 03,04 x10 ADF 87 °F (diff) °C (diff) Sys 2 Discharge Superheat S
92 S3_DSC_SHEAT AI84 597 03,04 x10 ADF 88 °F (diff) °C (diff) Sys 3 Discharge Superheat S
93 S4_DSC_SHEAT AI85 598 03,04 x10 ADF 89 °F (diff) °C (diff) Sys 4 Discharge Superheat S
Sys 1 System State [0=Stopped, 1=Running, 2=Faulted,
94 S1_SYS_STATE AI86 599 03,04 x1 ADF 90 None None S
4=Locked Out, 5=Pre-Run
Sys 2 System State [0=Stopped, 1=Running, 2=Faulted,
95 S2_SYS_STATE AI87 600 03,04 x1 ADF 91 None None S
4=Locked Out, 5=Pre-Run
Sys 3 System State [0=Stopped, 1=Running, 2=Faulted,
96 S3_SYS_STATE AI88 601 03,04 x1 ADF 92 None None S
4=Locked Out, 5=Pre-Run
Sys 4 System State [0=Stopped, 1=Running, 2=Faulted,
97 S4_SYS_STATE AI89 602 03,04 x1 ADF 93 None None S
4=Locked Out, 5=Pre-Run
98 S1_MTR_OVER AI90 603 03,04 x1 ADF 94 Amps Amps Sys 1 Motor Current Overload Setting S
99 S2_MTR_OVER AI91 604 03,04 x1 ADF 95 Amps Amps Sys 2 Motor Current Overload Setting S
100 S3_MTR_OVER AI92 605 03,04 x1 ADF 96 Amps Amps Sys 3 Motor Current Overload Setting S
101 S4_MTR_OVER AI93 606 03,04 x1 ADF 97 Amps Amps Sys 4 Motor Current Overload Setting S
BINARY READ ONLY POINTS
102 S13_ALARM BI1 1282 01,02,03 N/A BD5 0/1 0/1 Sys 1/3 Alarm [0=No Alarm, 1=Alarm] S
103 S24_ALARM BI2 1283 01,02,03 N/A BD6 0/1 0/1 Sys 2/4 Alarm [0=No Alarm, 1=Alarm] S
104 EVAP_HEATER BI3 1284 01,02,03 N/A BD7 0/1 0/1 Evaporator Heater Status S
105 EVAP_PUMP BI4 1285 01,02,03 N/A BD8 0/1 0/1 Evaporator Pump Status S
106 S1_COMP_RUN BI5 1286 01,02,03 N/A BD9 0/1 0/1 Sys 1 Compressor Run Status S
107 S2_COMP_RUN BI6 1287 01,02,03 N/A BD10 0/1 0/1 Sys 2 Compressor Run Status S
108 S3_COMP_RUN BI7 1288 01,02,03 N/A BD11 0/1 0/1 Sys 3 Compressor Run Status S
109 S4_COMP_RUN BI8 1289 01,02,03 N/A BD12 0/1 0/1 Sys 4 Compressor Run Status S
110 S1_ECON_SV BI9 1290 01,02,03 N/A BD13 0/1 0/1 Sys 1 Economizer Solenoid Valve Status S
111 S2_ECON_SV BI10 1291 01,02,03 N/A BD14 0/1 0/1 Sys 2 Economizer Solenoid Valve Status S
112 S3_ECON_SV BI11 1292 01,02,03 N/A BD15 0/1 0/1 Sys 3 Economizer Solenoid Valve Status S
113 S4_ECON_SV BI12 1293 01,02,03 N/A BD16 0/1 0/1 Sys 4 Economizer Solenoid Valve Status S
114 WATER_GLYCOL BI13 1294 01,02,03 N/A BD17 0/1 0/1 Cooling Type [0=Water, 1=Glycol] S
115 LOCAL_REMOTE BI14 1295 01,02,03 N/A BD18 0/1 0/1 Local Remote Control Mode [0=Local, 1=Remote] S
116 DISP_UNITS BI15 1296 01,02,03 N/A BD19 0/1 0/1 Display Units [0=Imperial, 1=SI] S

NOTES
1 Units have Native BACnet MS/TP, Modbus RTU, and N2 communications. No external Gateway is required for these interfaces unless the customer is using Connected Services.
2 BACnet Object Types: 0 = Analog In, 1 = Analog Out, 2 = Analog Value, 3 = Binary In, 4 = Binary Out, 8 = Device, 15 = Alarm Notification (0-127 are reserved ASHRAE Objects)
3 WC = Inches of water Column, CFM = Cubic Feet per Minute, FPM = Feet Per Minute, PSI = Pounds per Square Inch, Pa = Pascals, kPa = kiloPascals, PPM = Parts Per Million, kJ/kg = kiloJoules per kilogram
4 Values that are not applicable due to unit configuration and options will be sent as zero (0).
5 Modbus values are all of type signed. Scaling values in x10 (Bold) indicate scaling in metric is x100. Scaling and signing may not be modified in the field.
6
7
8
9
10

Property of Johnson Controls, Inc.


YCAV_IV Native 17 FEB 2017 Subject to change without notice. 3 of 4
Code Value Operational Code Code Value Fault/Inhibit Code
63 Manual Override 0 No Fault Code
64 Daily Schedule Shutdown 1 Low Ambient Temperature
65 Unit Switch OFF 2 High Ambient Temperature
66 Remote Controlled Shutdown 3 Low Chilled Liquid Temperature
67 Loss Of External Communications 4
68 Flow Switch Shutdown 5 Low RTC Battery Voltage
69 VSD Cooling Shutdown 6 Invalid Number of Compressors Selected
70 Serial Number Shutdown 7 VSD Communications Failure
71 Password Shutdown (AGR) 8 Pre-charge Low DC Bus Voltage (Unit)
72 9 Pre-charge DC Bus Voltage Imbalance (Unit)
73 10 High DC Bus Voltage (Unit)
74 No Run Permissive 11 Low DC Bus Voltage (Unit)
75 Anti-Recycle Timer Active 12 DC Bus Voltage Imbalance (Unit)
76 System Switch OFF 13 High VSD Ambient Temperature
77 System Not Running 14 Single Phase Input (Unit)
78 System Running 15 VSD Power Supply Fault
79 Discharge Pressure Limiting 16 VSD Logic Board Fault
80 Suction Pressure Limiting 17 Motor Current Overload (Hardware)
81 Motor Current Limiting 18 CT Plug Fault
82 19
83 ISN/BAS Motor Current Limiting 20
84 Remote Motor Current Limiting 21
85 System Shutting Down 22
86 VSD Pre-Charging 23
87 VSD Baseplate Temp Limiting 24
88 VSD Internal Ambient Temp Limiting 25
89 Sound Limiting 26
90 ISN Sound Limiting 27 High Discharge Pressure (Software)
91 Remote Sound Limiting 28 High Differential Oil Pressure
92 Pulldown Motor Current Limiting 29 Low Differential Oil Pressure
93 Cooling Demand Shutdown 30 Low Suction Pressure
94 System HPCO (Fan Special) 31 High Discharge Temperature
95 32 High Oil Temperature
96 33 Low Suction Superheat
97 34 Sensor Failure
98 35 Low Motor Current
99 36 High Motor Temperature
100 37 Pre-charge Low DC Bus Voltage (System 1/3, 2/4)
101 38 Pre-charge DC Bus Voltage Imbalance (System 1/3, 2/4)
102 39 High DC Bus Voltage (System 1/3, 2/4)
103 40 Low DC Bus Voltage (System 1/3, 2/4)
104 41 DC Bus Voltage Imbalance (System 1/3, 2/4)
105 42 High Motor Current
106 43 Motor Current Overload (Software)
107 44 IGBT Gate Driver Fault
108 45 High Baseplate Temperature
109 46 Single Phase Input (System 1/3, 2/4)
110 47 VSD Run Signal Fault
111 48 High Discharge Pressure (Hardware - HPCO)
112 49 High Flash Tank Level
113 50 Control Voltage Fault
114 51 Low Discharge Superheat

Property of Johnson Controls, Inc.


YCAV_IV Native 17 FEB 2017 Subject to change without notice. 4 of 4