SecoRMU 12kV-24kV New Compact Gas Insulated Ring Main Unit

Main Technical Data


12/17.5/24kV SecoRMU Rating and electrical performance

Load Break Vacuum


Item Unit Switch-fuse Unit
Switch Unit Circuit-breaker Unit

Rated Voltage kV 12/17.5/24 12/17.5/24 12/17.5/24

Rated Current A 630 (1)* 630

Rated Frequency Hz 50 /60 50/60 50/60

Rated power Freq withstand voltage (1 min) kV 28/50/50 28/50/50 28/50/50

Rated lightening impulse withstand voltage (peak) kV 75/125/125 75/125/125 75/125/125

Rated short-circuit making current kA (peak) 52 82 52

20kA-3s 20kA-3s
Rated short time withstand current (main circuit) - -
25kA-1s 25kA-1s

Rated short-circuit breaking current kA - 31.5 20

Product Description
52 52
Peak withstand current for main circuit kA (peak) -
65 65

O-0.3s-CO-180s-CO
Operating Sequence - - -
O-0.3s-CO-15s-CO

Electrical Endurance Capability class - E2 for load switch E2 for load switch E2 for breaker

Transfer Current A - 1400 -

Rated mainly active load-breaking current A 630 (1)* -

Rated closed-loop breaking current A 630 - -

Rated cable-charging breaking current A 16 - 31.5

Rated earth fault breaking current A 10 - -

Rated cable- and line-charging breaking current under


A 45 - -
earth fault conditions

Mechanical Endurance times 5000 5000 10000

Dimension (W@ D@ H) mm 350@ 800@ 1380 350@ 800@ 1380 350@ 800@ 1380

Weight kg 160 180 200

Cable compartment 20kA 1s


Internal arc degree
Gas tank 20kA 1s

Enclosure IP3X
IP Degree
Gas tank IP67

SF6 Gas pressure at 20ņ 0. 03MPa-relative

SF6 Gas Annual Leakage Rate <0.1%

Thickness of stainless steel gas tank 3.0mm

Electric operation control voltage 24/48/110/220V DC 110/220V AC

(1)* Depending on the current rating of the fuse-link. Please refer to transformer-fuse selection table in page 34.