Cutler-Hammer: M1-1 Safety Switches
Cutler-Hammer: M1-1 Safety Switches
Cutler-Hammer: M1-1 Safety Switches
January 1999
Safety Switches
General Description
M1-1
Description
Safety switches have a number of applications from service entrance to branch circuit protection. They are also horsepower rated for use as motor circuit switches. The Application Guide table, below, summarizes major differences and similarities between the Heavy Duty and General Duty type of Cutler-Hammer Safety Switches. Individual catalog pages and selection tables provide more specific information as to number of poles, voltage, specifications and horsepower ratings. K-Series Switch Design The efficient K-series design utilizes double-break, rotary blade action for high performance and reliability. Here are some of the characteristics of the K-Series type of switch:
s
s s
Clear line terminal shields. Unique Control Pole option visible blade and positive action electrical interlocking. Generous wiring room meeting or exceeding NEC wire bending space, even with field installed crimp lugs. Built-in Fuse Pullers in Type 4 and 12 enclosed switches. Side hinged Type 3R enclosure doors. Tangential knockouts in Type 1 and 3R enclosures through 200A size DH. Stainless steel enclosures for UL Type 4X applications Dust-tight, Watertight and Corrosion Resistant. Type 12 enclosures for 30-200A switches also rated for 3R use when a factory provided drain hole is opened. Rated for 60/75C wire connection.
High visibility handle and nameplate for indication of switch position ON or OFF.
Safety Switch Application Guide See Catalog Selection Tables for specific ratings.
Application/Features Type DG General Duty Safety Switches Type DH Heavy Duty Safety Switches
Type of Facility Maximum Voltages Short Circuit Rating for Non-fused Switches
Residential, Commercial, Light Industrial 240V ac 250V dc in larger sizes 10,000 rms symmetrical amperes
Commercial, Institutional, Industrial 600V ac 250V dc and 600V dc 10,000 rms symmetrical amperes Switches with Class H fuse clips 10,000 rms amperes 800-1200A switches with Class L fusing 200,000 rms Switches with Class R or Class J fusing and 200-800A switches with Class T fuse adaptation 200,000A at 480V and 100,000 rms sym. amperes at 600V 30, 60, 100, 200, 400, 600, 800, 1200 250 Hp at 240V, 500 Hp at 480 and 600V ac Type 1 Indoor, 3R Outdoor Type 4 Watertight and Dust-tight Type 4X Watertight, Dust-tight and Corrosion Resistant Type 12 Indoor falling dust, dirt and liquids Type 12/3R convertible to outdoor use Box Lug (screw pressure) for Al/Cu wire Field or Factory Installed for all sizes Field Installed for K-Series Switches Standard in Type 4 and 12 enclosed switches Field Installed for all other 30-200A switches
Short Circuit Rating with Standard Fuse With Class H fuse clips 10,000 rms symmetrical amperes Clips Short Circuit Rating with Fuse Options Ampere Sizes Maximum Horsepower Ratings UL (NEMA) Enclosure Types Class R fuse adaptation and 400-600A switches with T or J fuse adaptation 100,000 rms amperes 30, 60, 100, 200, 400, 600 200 hp at 240V ac Type 1 General purpose indoor use Type 3R Rainproof and Sleet-Resistant
Terminals Elec. Interlock Snap-switch Type Control Pole Interlock Fuse Pullers
Box Lug (screw pressure) for Al/Cu wire Field Installed Kit, 200-600A sizes Field Installed Kit, 400-600A sizes Not Available
Further Information
CAT.73.01.T.E
CAT.71.01.T.E
M1-2
Safety Switches
Selection Guide
Cutler-Hammer
January 1999
Air Conditioning Disconnect Residential/Commercial/ Air Conditioning/ Heat Pump Disconnects General Duty
Max. 240 Vac Max. 120/240 Vac Single Throw Max. 240 Vac Horsepower Rated Single Throw Max. 600 Vac Horsepower Rated
H H H L
Heavy Duty
Non-Fusible
2, 3 and 4
Single Throw Max. 600 Vac Max. 600 Vac Horsepower Rated
Cartridge Cartridge
H H T (600V) T (240V)
30-200 30-200 30-400 400 600 30-800 40-100 Number of Poles 2 and 3 3 3 3 3 3 3 3
6 6 2 and 3
Non-Fusible Rotary Switches EnviroLine Max. 600 Vac Fuse Type Fusible Non-Fusible Fusible Non-Fusible Fusible Non-Fusible Fusible Non-Fusible Cartridge Cartridge Cartridge Cartridge Non-Fusible Fuse Class H H H H
2, 3, 4 and 6 3, 4
YES
NEMA 12
NEMA 4X Non-Metallic
YES YES
YES YES
General Duty
For residential and commercial applications. Suitable for light duty motor circuits and service entrance. s 30 through 600 amperes. s For use on systems capable of delivering up to 10,000 rms (symmetrical fault current).* s Suitable for service entrance applications unless otherwise noted.
s 200-600 amperes features K-series design. s Horsepower rated. s Fusible and non-fusible switches. One-pole S/N through four-wire; 120/240, and 240 Vac. s Ample wire bending space provides for easier installation.
* Note: With class R fuses 100-600A switches may be used on systems capable of delivering 100,000 rms.
M
Heavy Duty
For heavy commercial and industrial applications where reliable performance and service continuity are critical. s 30 through 1200 amperes. s 600 Vac, 600 Vdc maximum. s May be rated up to 100,000 rms symmetrical when used with Class J or R fuses; and the 400 to 1200 ampere switches are rated at 200,000 rms symmetrical when used with Class J, L, or R fuses. s Horsepower rated. s Suitable for service entrance use.
s Visible double break rotary blade mechanism. Two points of contact provide a positive open and close, easier operation, and also help prevent contact burning for longer contact life. s Triple padlocking capability. Personnel safety feature since the large hasp can accommodate up to three 3/8-inch shank locks. Cabinet door can be further padlocked at the top and bottom. s Interlocking mechanism. Door cannot be opened when the handle is in the ON position. Built-in defeater mechanism provides for user access when necessary.
CAT.71.01.T.E
Cutler-Hammer
January 1999
Safety Switches
Selection Guide
M1-3
A compact safety switch thats ideal for use in heavy industry...when an in sight disconnecting means is required for two-speed motors that are remote from their motor control devices. s s s s 600 Vac, 250 Vdc maximum. 30 through 200 amperes. Fusible or non-fusible. Trunk-type latches keep the cover tightly closed and a neoprene gasket seals out moisture and dust from the switch assembly.
s Visible double break rotary blade mechanism. Two points of contact provide a positive open and close, easier operation, and also help prevent contact burning for longer contact life. s Clear line shield protection. s Built-in fuse pullers. s Clearly visible handle. s Triple padlocking capability. Cabinet door can be further padlocked at the top and bottom.
Used to transfer service from a normal power source to an alternate source...or to switch from one load circuit to another. s Recommended for systems where the available fault current does not exceed 100,000 rms symmetrical. s 30 through 800 ampere switches are horsepower rated. s 600 Vac, 250 Vdc maximum. s Also suitable for use on systems capable of delivering 100,000 rms symmetrical fault current when used with Class J, R, or T fuses. s Fusible or non-fusible. s Load break rated and approved for service entrance. s Wiring conguration from factory allows a single load to be supplied by a normal or alternate source. Can be eld modied to allow two loads to be alternately supplied by a single power source. s Non-fusible double throw switch can be used to feed a single throw fusible switch, the normal method to provide manual transfer from one power source to another in 800 ampere and larger switches.
s Ample wire bending space provides for easier installation. s Visible double break rotary blade mechanism. Two points of contact provide a positive open and close, easier operation, and also help prevent contact burning for longer contact life. s Triple padlocking capability. Personnel safety feature since the large hasp can accommodate up to three 3/8-inch shank locks. s Clearly visible handle. The position (ON or OFF) can be clearly seen from a distance. s Additional locking capability. Cabinet door can be further padlocked at the top and bottom. s Clear line shield protects against accidental contact with energized parts. Probe holes enable the user to test if the line side is energized without removing the shield. s Tangential knockouts on sides, top, and bottom. Enables any size of conduit to be mounted close to the wall, providing for cable installation closer to the wall and a neat appearance.
Enclosed Rotary
Provide users with the ability to lock directly wired motor loads in the OFF position to comply with new OSHA lockout/tagout regulations. Also for machine applications that require compact, economical disconnect switches. s Meets NEC article 430 requirements for a separate disconnect means within sight of all motor loads. s Padlockable in the OFF position (up to three padlocks) to meet OSHA lockout requirements.
s Available in 40, 80, and 100 ampere ratings. s 600 Vac, three- and four-pole non-fusible device. s Rated at highest available Hp rating (at 480 Vac, 40A-20 Hp, 80A-40 Hp, 100A-50 Hp). s Rated for making and breaking loads. s Accepts auxiliary contacts. Capability to signal PLC controllers. s Ground lug connection provided.
New EnviroLine
Cutler-Hammer is introducing a new line of safety switches designed for your special application and/or extreme environmental conditions. s All Stainless Steel Switch primarily for use in the meatpacking and food processing industries or any application where water is frequently used to hose down equipment. In addition to the stainless steel NEMA 4X enclosure, the interior mechanism, back pan, and springs are all stainless steel. Ratings for these Heavy Duty switches are 30-400 amperes, 240-600 Vac, available as fusible and non-fusible switches. s Window Switches These switches are available with either an upper window over the switch contacts or a lower window over the fuse block. The upper window provides visual verication of ON/OFF status. The lower window switch allows for visual verication of fuse status if used in conjunction with Littelfuse, Inc fuses with blown fuse indicator. Ratings are 30-800 amperes, 240-600 Vac, fusible and non-fusible. Available in NEMA 12/3R, 4X stainless steel enclosures.
s Receptacle Switches These Heavy Duty Switches are pre-wired and interlocked to polarized receptacles for three-phase, threewire, grounded type power plugs. These are used for portable power applications such as welders, infrared ovens, batch feeders, conveyors, truck and marine docks. Receptacles are interlocked to handle mechanisms so that power plugs may not be inserted or removed when the switch is in the ON position unless noted otherwise. Ratings are 30-100 amperes, 600 Vac, NEMA 12, 4X stainless steel enclosures. s Non-Metallic Switch This switch has a KRYDON enclosure. This is a compression molded berglass reinforced polyester enclosure, which is capable of withstanding almost any corrosive environment. Ratings are 30-200 amperes, 240-600 Vac, fusible and non-fusible. Enclosure is NEMA 4X rated.
CAT.71.01.T.E
M1-4
Safety Switches
Catalog Numbering System, Features
Cutler-Hammer
January 1999
Safety Switch Catalog Numbering System Does not apply to Air Conditioning Disconnects.
DH
Switch Type DP = General Duty/ Plug Fuse DG = General Duty/ Cartridge Fuse DH = Heavy Duty DT = Double Throw DR = Rotary Switch
3
Poles/Blades 1 = 1-Pole 2 = 2-Poles 3 = 3-Poles 4 = 4-Poles 6 = 6-Poles
1
Amperes 1 = 30 Amps 2 = 60 Amps 3 = 100 Amps 4 = 200 Amps 5 = 400 Amps 6 = 600 Amps 7 = 800 Amps 8 = 1200 Amps
LW
Options Blank = No Viewing Window W = Upper Viewing Window LW = Lower Viewing Window X = All Stainless
NEMA Enclosures Rating G = NEMA 1 R = NEMA 3R D = NEMA 12 P = NEMA 4 (Painted Steel) W = NEMA 4X Corrosion Resistant (Stainless Steel) C = NEMA 4X Non-Metallic
Series K = Design All General Duty Switches Above 200 Ampere and All Heavy Duty Switches Incorporate K-Series Switch Design Features Listed Below B = Design General Duty 30-100 Amps C = Design 1200A Only
All General Duty Switches Above 200 Ampere and All Heavy Duty Switches Incorporate These K-Series Switch Design Features
Visible Double Break Rotary Blade Mechanism Two points of contact provide a positive open and close, easier operation, and also help prevent contact burning for longer contact life. Clear Line Shield Protects against accidental contact with energized parts. Probe holes enable the user to test if the line side is energized without removing the shield. Clearly Visible Handle The position (ON or OFF) can be clearly seen from a distance and the length provides for easy operation. Interlocking Mechanism Door cannot be opened when the handle is in the ON position. Defeater mechanism provides for user access when necessary.
Triple Padlocking Capability Personnel safety feature since the large hasp can accommodate up to three 3/8-inch shank locks.
Tangential Knockouts An ample number are provided on the top, bottom, and sides of both NEMA Types 1 and 3R enclosures.
Built-In Fuse Pullers (NEMA 12 and 4X Only) Provides easy removal of fuses.
Additional Locking Capability Cabinet door can be further padlocked at the top and bottom.
Bolt-On Hub Kits For Switches in a NEMA Type 3R, 12, 4, 4X enclosure.
CAT.71.01.T.E
Cutler-Hammer
January 1999
Safety Switches
Accessories, Hubs, Lug Data
M1-5
Accessories
Description Catalog Number
Neutral Kits/Ground Kits 200A DG, DH (NEMA 1, 3R Enclosures) 30-60A DH 100A DH 200A DH (NEMA 4X, 12 Enclosures) 1200A DH 400A DG, DH 600A DG, DH 400-600A Fusible DT 30-100A DT 200 A DT 400A Non-Fusible DT 600 Non-Fusible DT Ground Lug Kits 30-100A DG, DH, DT 200A DG, DH, DT 400-600A DG, 400-800A DH, 400-800A DT Control Pole Kit 400-600A DG, 30-800A DH, 30-200A DT Electrical Interlock Kits All Switches (except 30-100A DG, 1200A DH) 2NO/2NC All Switches (except 30-100A DG, 1200A DH) 2NO/2NC 1200 A DH 2NO/2NC Copper Lug Kits 30A DH, DT (order one kit for 3 poles) 60A DH, DT (order one kit for 3 poles) 100A DH, DT (order one kit for 3 poles) 200A DH (order one kit for 3 poles) 400A DG, DH (order one kit for each pole) 600A DG, DH (order one kit for each pole) Crimp Lug Pad Kit 400-600A DG, DH (order one kit for 3 poles) 800A DG, DH (order one kit for each pole) 400-800A Neutral DG, DH (order one kit per switch) Special Lug Kit (750 kcmil) 600A DG, DH (order one kit for each pole) Fuse Puller Kits 30-60A DH (order one kit for 3 poles) 60A DH (4 pole switch only) 100A DH (order one kit for 3 poles) 200A DH (order one kit for 3 poles) J Fuse Adapter Kits 60A 240V DH, DT (order one kit for 3 poles) 60A 600V DH, DT (order one kit for each pole) 400A 600V DT (order one kit for 6 poles) 600A 240-600V DH only R Fuse Adapter Kits 30-60A DG 30A 240V DH, DT 30A 600V DH, DT, 60A 240V DH, DT 60A 600V DH, DT 100A 240-600V DH, DT 200A 240-600V DH, DT 400A 240-600V DH, DT 600A 240-600V DH, DT T Fuse Adapter Kits 200A 240V DH (order one kit for 3 poles) 200A 600V DH (order one kit for 3 poles) 400A 240V DG, DH (order one kit for each pole) 400A 600V DG, DH (order one kit for each pole) 600A 240V DG, DH (order one kit for each pole) 600A 600V DG, DH (order one kit for each pole) 800A 240V DG, DH (order one kit for each pole) 800A 600V DG, DH (order one kit for each pole) Auxiliary Contacts for Rotary Switches
DG200NK DH030NK DH100NK DH200NK DS1200NC DS400NK DS600NK DS800NK DT100NK DT200NK DT400NK DT600NK DS100GK DS200GK DS468GK DS16CP DS200EK1 DS200EK2 DS1200EK2 DS16CL DS26CL DS36CL DS46CL DS56CL DS66CL
DS12FK
DS426TK
DS16CP
DS56CK DS76CK DS800CNK DS750KL DS30FP DS60FP DS100FP DS200FP DS22JK DS26JK DT400JK DS600JK DG32RK DS12FK DS16FK DS26FK DS36FK DS46FK DS56FK DS66FK DS426TK DS466TK DS526TK DS566TK DS626TK DS666TK DS726TK DS766TK C362AC1 C362AC3 C362AC5
DS100GK
DS200EK1
M
DH030NK
CAT.71.01.T.E
M1-6
Safety Switches
Accessories, Hubs, Lug Data
Cutler-Hammer
January 1999
Hubs
Plate Type Hubs
For NEMA Type 3R Enclosures (Up to 200 Amperes)
Group 1 General Duty, Heavy Duty, Double Throw Through 100A Conduit Size Inches 3/4 1 1-1/4 1-1/2 2 mm 19.0 25.4 31.8 38.1 50.8 Catalog Number DS075H1 DS100H1 DS125H1 DS150H1 DS200H1 Group 2 General Duty, Heavy Duty, Double Throw 200A Conduit Size Inches 2 2-1/2 3 mm 50.8 63.5 76.2 Catalog Number DS200H2 DS250H2 DS300H2
Catalog Number DS900AK Adapter Kit Permits Installation of Group 1 Hubs on 200 Ampere Type General Duty, Heavy Duty and Double Throw Switches
DS075H1
C401 Hubs
For NEMA 4X Non-Metallic Enclosures Only
Conduit Size Inches 3/4 1 1-1/4 1-1/2 2 2-1/2 3 mm 19.0 25.4 31.8 38.1 50.8 63.5 76.2 Conduit Hub Catalog Number C401AC2 C401AC3 C401AC4 C401AC5 C401AC6 C401AC7 C401AC8 Ground Bushing Catalog Number C401CC2 C401CC3 C401CC4 C401CC5 C401CC6 C401CC7 C401CC8
Grounding bushings are required when metallic conduit is used for a ground conductor.
CAT.71.01.T.E
Cutler-Hammer
January 1999
Safety Switches
Dimensions
M1-7
Figure 1
W D
Figure 2
6-3/4 8-7/8 8-3/4 11-1/4 12-5/8
H W D
14-1/4
Figure 3
W D
H C L
CAT.71.01.T.E
M1-8
Safety Switches
Dimensions
Cutler-Hammer
January 1999
Figure 1
W D
Heavy Duty, Fusible, 240 and 600V, 3-Pole Solid Neutral, Single Throw
Ampere Rating NEMA 1, 3R W H D NEMA 12, 4XSS W H D
Figure 2
W D
CAT.71.01.T.E
Cutler-Hammer
January 1999
Safety Switches
Technical Data
M1-9
Heavy Duty, Fusible and Non-Fusible, 480V With Time Delay Fuses
Ampere Rating 1 Phase AC 3 Phase AC
3 10 15 15
7-1/2 20 30 50
Heavy Duty, Fusible and Non-Fusible, 600V With Time Delay Fuses
Ampere Rating 1 Phase AC 3 Phase AC
3 10 15 15
10 25 30 50
CAT.71.01.T.E
Cutler-Hammer
January 1999
Typical Specifications
General Duty
General Furnish and install, where indicated, general duty type safety switches having the electrical characteristics, ratings and modifications shown on the drawings. UL, Federal and NEMA Specifications All switches shall be Underwriters Laboratories Inc., File No. E5239 listed, comply with UL98 and meet NEMA KS-1 specifications. Qualifications A. For equipment specified herein, the manufacturer shall be ISO 9000 certified. B. The manufacturer of this equipment shall have produced similar electrical equipment for a minimum period of seven (7) years. Manufacturer A. Cutler-Hammer. Ratings A. Safety switches shall be rated for a maximum of 240 Volts Ac, single-pole through 3-pole with optional solid neutral. B. Switches shall have short circuit ratings as shown on the drawings or as herein scheduled, but not less than 100,000 amperes RMS (symmetrical fault current). C. Ampere ratings of 30 through 600. D. Switches shall be horsepower rated. E. Suitable for service entrance applications unless otherwise noted.
C. The fuses will be easy to access. Bail Handle is not acceptable. D. NEMA 3R will be a side opening cover. Wiring/Termination A. All wire connectors and terminals shall be of the anti-turn solderless type and shall be suitable for copper and aluminum wire of the sizes indicated. B. All safety switches where marked shall be suitable for use with 60/75 degree C rated wire. C. All switches shall conform to the latest NEC wire bending space requirements. Enclosure A. Safety switch shall have NEMA 1 general purpose or NEMA 3R rainproof enclosures as indicated on the drawings. B. The cover shall have door interlock to prevent the switch being opened in the ON position. C. The handle will be red and easily recognizable, and is padlockable in the OFF position. D. The door shall have a one-piece lockable hasp. E. The side, top and bottom sides shall have tangential knockouts. F. The back of enclosure shall have concentric knockouts. Finish A. Enclosure shall be phosphated and finished with a medium light gray ASA 61 enamel. The finish paint shall be of a type to which field applied paint will adhere. Factory Testing A. The standard factory tests shall be performed on the equipment provided under this section. All tests shall be in accordance with the latest version of UL and NEMA.
Heavy Duty
General Furnish and install, where indicated, heavy duty type safety switches having the electrical characteristics, ratings and modifications shown on the drawings. UL, Federal and NEMA Specifications All switches shall be listed with Underwriters Laboratories Inc., under File No. E5239, comply with UL98 and meet NEMA KS-1 specifications and previous Federal Specification WS-865c Type HD. Qualifications A. For equipment specified herein, the manufacturer shall be ISO 9000 certified. B. The manufacturer of this equipment shall have produced similar electrical equipment for a minimum period of seven (7) years. Manufacturer A. Cutler-Hammer. Ratings A. Safety switches shall be rated for 240 Volts Ac, Dc or 600 Volts Ac 2-pole through 6-pole. B. Switches shall have short circuit ratings as shown on the drawings or as herein scheduled, but not less than 100,000 amperes RMS (at 600 volt) with Class J or R fuses. The 400 to 1200 ampere switches are rated 200,000 RMS (at 480 volt) when used with Class J, L, or R fuses. C. Ampere ratings of 30 through 1200. D. Switches shall be horsepower rated. E. Suitable for service entrance applications unless otherwise noted. F. Fusible and Non-fusible switches.
F. Fusible and non-fusible switches. Construction A. Safety switch design must have quick-make/quick-break operating mechanism. B. Double-break rotary action shaft and switchblade shall be manufactured as one common component. Pivot point is not acceptable.
CAT.71.01.T.E
Cutler-Hammer
January 1999
Safety Switches
Typical Specifications
M1-11
Construction A. Safety switch design must have quick-make/quick-break operating mechanism. B. Switch shall have deionizing arc chutes to confine and suppress the arcs produced by contacts under load. C. Double-break rotary action shaft and switchblade shall be manufactured as one common component. Pivot point is not acceptable. D. Switches shall have built-in fuse pullers for type 4 and 12. E. Switch shall have clear line shields to prevent accidental contact with line terminals. Wiring/Termination A. All wire connectors and terminals shall be of the anti-turn solderless type and shall be suitable for copper and aluminum wire of the sizes indicated. B. All safety switches where marked shall be suitable for use with 60/75 degree C rated wire. C. All switches shall conform to the latest NEC wire bending space requirements. Enclosure A. Safety switch shall have NEMA 1 general purpose, NEMA 3R rainproof, NEMA 12 dust-tight, NEMA 4 painted steel, NEMA 4X stainless steel or NEMA 4X nonmetallic enclosures as indicated on the drawings. B. The cover shall have door interlock to prevent the switch being opened in the ON position. C. Defeat mechanism for door interlock must be front accessible. D. The handle will be red and easily recognizable, and be pad-lockable in the OFF position. E. The door shall have a one-piece lockable hasp.
F. The side, top and bottom sides shall have tangential knockouts. G. The back of enclosure shall have concentric knockouts. H. Enclosures shall be predrilled to accommodate field installable neutral. Finish A. Enclosure shall be phosphated and finished with a medium light gray ASA 61 enamel. The finish paint shall be of a type to which field applied paint will adhere. Factory Testing A. The standard factory tests shall be performed on the equipment provided under this section. All tests shall be in accordance with the latest version of UL and NEMA.
B. Switches shall be suited for use on systems where the available fault current of 100,000 amperes RMS symmetrical when used with Class J, R, or T fuses. C. Ampere ratings of 30 through 800. D. Switches shall be horsepower rated. E. Load break rated and approved for service entrance applications unless otherwise noted. F. Fusible and non-fusible switches. Construction A. Safety switch design must have quick-make/quick-break operating mechanism with two points of contact. B. Switch shall have deionizing arc chutes to confine and suppress the arcs produced by contacts opening under load. C. Double-break rotary action shaft and switchblade shall be manufactured as one common component. Pivot point is not acceptable. D. Switch shall have clear line shields to prevent accidental contact with line terminals. Wiring/Termination A. Wiring configuration from the factory shall allow a single load to be supplied by a normal or alternate source. It can be field modified to allow two loads to be alternately supplied by a single power source. B. All wire connectors and terminals shall be of the anti-turn solderless type and shall be suitable for copper and aluminum wire of the sizes indicated. C. All safety switches where marked shall be suitable for use with 60/ 75 degree C rated wire. D. All switches shall conform to the latest NEC wire bending space requirements.
Double Throw
General Furnish and install for use as a transfer switch where indicated doublethrow switches having the electrical characteristics, ratings and modifications shown on the drawings. UL, Federal and NEMA Specifications All switches shall be listed with Underwriters Laboratories Inc., under File No. E5239, comply with UL98 and meet NEMA KS-1 specifications and previous Federal Specification WS-865c Type HD. Qualifications A. For equipment specified herein, the manufacturer shall be ISO 9000 certified. B. The manufacturer of this equipment shall have produced similar electrical equipment for a minimum period of seven (7) years. Manufacturer A. Cutler-Hammer. Ratings A. Safety switches shall be rated for 240 Volts Ac, Dc or 600 Volts Ac 2-pole through 6-pole.
CAT.71.01.T.E
Cutler-Hammer
January 1999
For a complete product specification in CSI format, see CutlerHammer Product Specification Guide, section 16441.
CAT.71.01.T.E