Kidde AEGIS Conventional Fire Alarm-Suppression Control
Kidde AEGIS Conventional Fire Alarm-Suppression Control
Kidde AEGIS Conventional Fire Alarm-Suppression Control
August 2007
Kidde AEGIS™
Conventional
Fire Alarm-Suppression
Control Unit
ICE OF
O FF
Several different sources of power can be connected to this fire alarm control unit.
Disconnect all sources of power before servicing. Control unit and associated
equipment may be damaged by servicing while the unit is energized. Do not
WARNING attempt to install, service, or operate this control unit until this manual is read
and understood.
System Re-acceptance Test after Re-Programming: To ensure proper system operation, this
system must be retested in accordance with NFPA 72 Chapter 10 after any
programming change. Re-acceptance testing is also required after any addition or
deletion of system components, and after any modification, repair or adjustment to
system hardware or wiring.
CAUTION All components, circuits and system operations known to be affected by a change must
be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change,
up to a maximum of 50 devices, must also be tested and proper system operation
verified.
This system meets FM and ANSI/UL 864 requirements for operation at 32° to 120°F (0 to 49°C) and at a
relative humidity of 93% (non-condensing) @ 90°F (32.2°C). However, the useful life of the system’s
standby batteries and the electronic components may be adversely effected by continuous operation at
these environmental limits. Therefore, it is recommended that this system and its peripherals be installed
in an environment with a nominal room temperature of 60-80°F.
Like all solid state electronic devices, this system may operate erratically or can be damaged when
subjected to lightning induced transients. Although no system is completely immune from lightning
transients and interference, proper grounding will reduce susceptibility. The use of overhead or outside
aerial wiring is not recommended due to the increased susceptibility to nearby lightning strikes.
Consult with the Technical Support Department if any problems are anticipated or encountered.
Do not install electronic assemblies prior to mounting and attaching conduit for field wiring to the enclosure.
Before making modifications, verify that they will not interfere with battery and printed circuit board
locations. Do not overtighten screw terminals. Overtightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed from the body. Use static suppressive packaging
to protect electronic assemblies removed from the control unit.
Follow the instructions in this manual. These instructions must be followed to avoid damage to the control
unit and associated equipment. System operation and reliability depend upon proper installation.
Fire Alarm System Limitations While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
An automatic fire alarm system – typically made up of smoke detectors, heat detectors, manual pull stations,
notification appliances, and a fire alarm control unit with remote-notification capability – can provide early warning
of a developing fire. Such a system, however, does not assure protection against property damage or loss of life
resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls,
on roofs, or on the other side of closed doors. Smoke detectors on one level also may not sense a fire on
GENERAL SAFETY NOTICES The following must be observed to maintain personnel safety.
The following general safety notices supplement specific warnings and cautions appearing in the manual.
The safety precautions in this section must be understood and applied during operation and maintenance.
This manual is to be used by trained distributors/technicians. The entire manual should be read and fully
understood prior to installation.
FIRST AID
Any injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention
immediately.
GENERAL PRECAUTIONS
The following general safety precautions are to be observed at all times:
1. All electrical components associated with equipment shall be installed and grounded in accordance
with NEC and local regulatory requirements.
2. Special precautionary measures are essential to prevent applying power to equipment at any time
maintenance work is in progress.
3. Before working on electrical equipment, use a voltmeter to ensure that system is not energized.
4. When working near electricity, do not use metal rulers, flashlights, metallic pencils, or any other
objects having exposed conductive material.
5. When connecting a meter to terminals for measurement, use a voltage range higher than expected
voltage to be measured.
CHAPTER 2 INSTALLATION
2-1 Installation Materials..................................................................................... 2-1
2-2 Installation Guidelines................................................................................... 2-2
2-3 Installation Procedure ................................................................................... 2-4
2-4 Terminations And Wiring Diagrams ................................................................. 2-14
2-5 Installing the Bezel, P/N 06-220114-001 ......................................................... 2-21
2-6 Installing Optional Dead-Front Panel, P/N 06-220175-001.................................. 2-21
2-7 Installing the Enclosure Door (Standard Door).................................................. 2-21
2-8 Installing the Enclosure Door (Door with Switches) ........................................... 2-21
2-9 Completing the Installation ............................................................................ 2-23
CHAPTER 3 CONFIGURATION
3-1 Entering Site - Specific Configuration .............................................................. 3-1
3-2 Configuration Settings................................................................................... 3-3
CHAPTER 4 OPERATION
4-1 Introduction ................................................................................................ 4-1
4-2 Control Switch Functionality........................................................................... 4-2
CHAPTER 6 TROUBLESHOOTING
6-1 Purpose ...................................................................................................... 6-1
6-2 Trouble Diagnostics ...................................................................................... 6-1
6-3 Trouble Codes and Corrective Action ............................................................... 6-1
CHAPTER 1
GENERAL INFORMATION
1-1 INTRODUCTION
The Kidde AEGIS™ is a versatile, flexible, microprocessor-based conventional fire control unit
which can be used in a wide range of fire alarm and suppression discharge applications.
The Kidde AEGIS is listed/approved with the agencies listed in Table 1-1 for system
classifications as described in the NFPA Standard 72, “National Fire Alarm Code”, ANSI/UL 864
9th edition, “Control Units for Fire Protective Signaling Systems”, and CAN/ULC-S527-99. The
Kidde AEGIS shall be implemented according to the following:
• NFPA Standard 72, “National Fire Alarm Code”
• NFPA Standard 70, “National Electric Code”
• This Installation, Operation, and Maintenance Manual (IOM)
• Any other standards enforced by a local Authority Having Jurisdiction (AHJ)
Type
Agency System Classification
Service Signaling
1
Must be used with ANSI/UL 864 Listed/FM Approved Silent Knight DACT Model 5104B.
2 FM approved to FM requirements, ANSI/UL 864 9th edition, and CAN/ULC S527-99.
3 Per Canadian Building Code, not for use as a high-rise building fire alarm system.
4
For UL and cUL installation, must not exceed 24 hours standby and 5 minutes of alarm.
The Kidde AEGIS is listed/approved for the control and activation of suppression systems listed
in Table 1-2 which the designer/installer should be familiar with.
The designer/installer should also be familiar with the following (as applicable):
• NFPA Standard 70, “National Electric Code® 2002 Edition”
• NFPA Standard 72, “National Fire Alarm Code® 2002 Edition”
• NFPA Standard 75, “Standard for the Protection of Electronic Computer/Data Processing
Equipment”
• NFPA Standard 76, “Fire Protection of Telecommunications Facilities”
• NFPA Standard 101, “Life Safety Code® 2003 Edition”
• NFPA Standard 110, “Standard for Emergency and Standby Power Systems 2002 Edition”
• UL Standard 38, “Manual Signaling Boxes for Fire Alarm Systems”
• UL Standard 268, “Smoke Detectors for Fire Protective Signaling Systems”
• UL Standard 268A, “Smoke Detectors for Duct Application”
• UL Standard 1481, “Power Supplies for Fire Protection Signaling Systems”
• Underwriter Laboratories of Canada (cUL) ULC-S527-99, “Standard of Control Units for Fire
Alarm Systems”
• FM Standards 1011 and 1012, “Approval Standard for Deluge Systems and Preaction
Systems”
• FM Standard 3011, “Central Station Service for Fire Alarms and Protective Equipment
Supervision”
• Any others mandated by the building owner and/or the local Authority Having Jurisdiction
(AHJ)
The Kidde AEGIS consists of the following: Enclosure with Door, Power Supply Unit, Printed
Circuit Board (PCB), and Secondary Standby Batteries (ordered separately).
5 in.
(127 mm)
14-1/4 in.
(362 mm)
ENCLOSURE
ENCLOSURE SECONDARY
DOOR STANDBY
BATTERIES
The enclosure meets the requirements for NEMA Type 1 and is intended to be used indoors in
a relatively dust-free environment. The enclosure has a hinged door that swings open 180° for
accessibility. The enclosure can be surface or recessed mounted. A trim ring is available for
recessed mounting. The enclosure is constructed of 18 gauge sheet steel. A steel door is held
closed by a key lock. All operator interface switches and indicators are located behind the
locked cover. The enclosure is large enough to house two 12 Vdc, 12 AH batteries required for
standby operation.
The standard enclosure door allows the operator to view the operator interface display
mounted on the PCB behind a plexiglass window. The AEGIS is also available with an alternate
door that allows an abort and manual release switch to be mounted. The manual release switch
incorporates a lift type guard and the abort switch incorporates a safety guard to prevent
inadvertent activation.
The control unit is also suitable for mounting a dead-front panel (P/N 06-220175-001) that is
mandatory for use in Canada. The dead-front is intended to protect the user from inadvertent
access to any exposed potentially hazardous/high voltage components.
The power supply unit mounts behind the circuit board and operates from either 120 Vac 50/60
Hz or 240 Vac 50/60 Hz. It powers the system and also charges a standby battery set which
provides backup in case of loss of power from the AC source.
The battery charger is capable of charging sealed lead-acid 24 Vdc batteries of capacity up to
68 AH. The charge voltage is 27.4 Vdc nominal.
The actual battery capacity used for an application is a function of the units components,
devices and configuration. Refer to Appendix A for battery capacity calculations.
The power supply monitoring circuit provides a trouble signal if any of the following occur:
• Loss of AC input or if AC power falls below 85% of nominal. This causes an immediate
change-over to battery operation and a trouble signal after 30 seconds.
• Detection of a ground fault.
• Low charging current.
• High output voltage
The battery monitoring circuit provides a trouble signal if any of the following occur:
• The battery is installed backwards.
• The battery is disconnected.
• Battery voltage falls below 19.5 V (this condition causes the battery to disconnect and can
only be cleared when primary AC main power is restored).
The printed circuit board provides an interface or terminals for the following:
• Power Supply Unit
• Battery
• Initiating Device Circuits (System Inputs)
• System Outputs
• Operator Interface
• Auxiliary Power Output
RELAY 2 TB10
RELAY 1 TB11
TB13
All alarms, troubles and supervisory signals are received at the control unit and displayed for
the operator. The Operator Interface consists of four main components and are visible and/or
audible through a transparent window:
• LED Indicators
• Control Switches
• Digital Display
• Buzzer
The following is a list of control unit indicators and their LED display color.
AC Power On Green
System Alarm Red
System Supervisory Yellow
System Trouble Yellow
Signal Silenced Yellow
Agent Pre-Release Red
Agent Releasing Red
Agent Post-Release Red
Input Activated Alarm, Manual Release, and Abort — Red
Other — Yellow
Input Trouble Yellow
Release Output Trouble Yellow
NAC Output Trouble Yellow
Ground Fault Yellow
Power Supply Fault Yellow
There are four Control Switches on the Operator Interface. They are:
• Acknowledge — Silences the buzzer which sounds when a new supervisory, alarm, or
trouble is detected. Holding this control switch for five seconds, activates the control unit
Lamp Test. This control switch is also used in conjunction with the System Reset control
switch to enter the configuration mode.
Note: Microprocessor and PCB troubles are latching and cannot be silenced or reset. Refer to
Chapter 6, Troubleshooting.
• Signal Silence — Silences the NAC circuits.
• System Reset — Disconnects power from all input and output circuits and the auxiliary
output for a period of five (5) seconds. This control switch is also used in conjunction with
the Acknowledge control switch to enter the configuration mode.
• Output Disable — Disables the release of agent, and as selected in the system
configuration, the activation of NAC outputs and/or Programmable Relays. This is used
when performing maintenance on the system.
1-4.3.1.4 Buzzer
The buzzer will sound when an alarm, trouble or supervisory condition is present.
The control unit provides two dedicated initiating/detector input circuits, plus a third that can
be used as a Waterflow alarm or an independent initiating/detector input. Inputs from these
circuits are latching. Refer to Chapter 3, Configuration for configuration settings.
Certain jurisdictions require NAC outputs due to Waterflow input to be non-silenceable. The
configuration settings in Chapter 3, Configuration allows the user to select the specific mode
needed for a given application.
Each detector circuit is suitable for Class A or Class B wiring and is capable of operating with
up to 25 smoke/electronic heat detectors and a quantity of contact-closure type devices (up to
the limitation imposed by wiring resistance). For a list of compatible devices, refer to
Appendix B.
Operation of a manual release pull station activates the NACs and initiates the release
sequence. The configured time delay and agent release output is activated after the site
configured time delay. Manual release overrides any other time delay. The circuit is suitable
for either Class A or Class B wiring and any quantity of contact closure type manual release
stations subject to the limitations imposed by the wiring resistance. The manual release will
also override any activated abort switch.
1-4.3.2.3 Abort
Activation of the abort station temporarily delays the impending agent release. Operation of
the abort switch during non-alarm conditions will cause a trouble signal. However, if the Abort
switch is pressed and held during either a non-alarm condition or during a first alarm condition,
and remains held until an alarm pre-release condition exists occurs, the Abort function will
execute as normal, per the configuration setting. The following abort modes are configurable.
Abort Mode 1 (ANSI/UL 864) - When the abort input is received, the release timeout
continues and stops at ten (10) seconds. If the timeout was less than ten (10) seconds when
the abort signal is received, timeout is reset to ten (10) seconds. When the abort is released,
the timeout resumes. Successive aborts are permitted.
Abort Mode 2 (Reset) - When abort is activated, the timer is stopped and the full delay is
loaded into it. The timeout begins when the Abort control switch is released. Successive aborts
are permitted. If Mode 2 is selected with a zero (0) abort delay, the abort is disabled. Mode 2
does not comply with ANSI/UL 864s.
Abort Mode 3 (IRI) - This mode is only valid for cross-zoned release when both initiating
inputs are needed to cause the agent release activation (if selected for single zone, the abort
will be disabled). This mode is similar to Mode 1 with the exception that the abort will function
only if held after the receipt of the first alarm, but prior to the receipt of the second alarm.
Abort activation at any other time is ignored.
Abort Mode 4 (New York City) – When the abort is activated, the timer is stopped and reset
to 120 seconds. The timer will not start as long as the Abort switch is held. The timeout restarts
when the Abort switch is released. Successive Abort switch operations resets the timer back to
the full 120 second delay. Selection of this mode does not have an over-ruling effect on any
programmed manual or auto-release delays, regardless of whether an abort has actually
occurred. In this mode, the delay from a manual release is forced to zero (0), and the auto-
release delay is restricted to a maximum of 30 seconds. NYC Mode does not comply with
ANSI/UL 864.
The setting of non-compliant delays with New York City Abort is not error-
WARNING trapped or over-ruled by the control unit.
The circuit is suitable for either Class A or Class B wiring and any quantity of contact closure
type abort stations subject to the limitations imposed by the wiring resistance.
The Supervisory Circuits accept inputs from monitoring devices such as pressure switches on
agent cylinders or sprinkler systems.
The AEGIS has three dedicated notification appliance circuits (NAC). Any NAC can be
configured in system configuration to operate on or more on First Alarm, Pre-Release, and
Releasing conditions. In the case that the control unit is being used in a non-suppression
application, the three NACs may be configured to operate on Alarm from DET 1, DET 2, and
DET 3. Each circuit is driven independently and is user configurable for either Class A (Style Z)
or Class B (Style Y) operation with the following coded patterns:
• 60 beats per minute (BPM)
• 120 beats per minute (BPM)
• Temporal
• Continuous
The three circuits are supervised, power-limited, and are compatible with conventional UL
listed, 24 Vdc notification appliances. They can also be used with the following synchronizable
horns and strobes:
• MT series multi-tone horns and horn/strobes
• NS series horn/strobes
• NH series horns
• RSS(P) series strobes
The MT and NS series network appliances provide the option to use silencable horns and non-
silenceable strobes on the same NAC.
Multiple NAC circuits (connected to audible devices only) programmed with the same master
code pattern are synchronized, regardless of any differing starting times that preceded their
concurrent operation.
The control unit is designed for user selection of an intelligent synchronization feature. This
feature allows the silenceable horn to be shut off while the strobe continues to flash in
synchronized fashion. Each NAC is rated 1.5A at 24 Vdc and is suitable for polarized 24 Vdc
appliances only.
The AEGIS has two (2) dedicated, independently controlled Class B ARCs compatible with
devices listed in Appendix B.
The release circuit may be programmed for an ON time of 90 seconds for Control Heads and
either 10 minutes, 15 minutes or On-until-reset for Deluge/Pre-Action Solenoids. When
programmed for initiators, the ARC remains ON for 200 milliseconds.
The ARCs can be configured to activate on a variety of conditions based on inputs from manual
release, detection circuits and supervisory circuits. Activation of the ARCs can be delayed from
0 to 60 seconds (in 10 second increments) in automatic release mode. Manual Release can be
delayed from 0 to 30 seconds (in 10 second increments).
The ARCs are suitable to operate different release device types on both circuits. In other words,
ARC1 may activate solenoids and ARC2 may activate an initiator. See Chapter 2, Installation.
ARCs are not inherently power-limited. For the circuits to be power-limited, the ARC should be field
terminated with an in-line supervisory device P/N 06-220023-001. ARCs activating initiators cannot
be made power-limited.
The Kidde AEGIS has three independently programmable relays and one dedicated Trouble
relay. The relays are Form-C type with contacts rated 3A @ 30 VDC / 120 VAC (resistive).
The three programmable relays are normally in the de-energized condition and will energize
upon receipt of one of the following listed conditions. These relays will latch on change of state
and shall remain latched until manually reset by the System Reset control switch.
• 1st Alarm: (DET 1, DET 2, DET 3/WF, or Manual Release)
Note: DET 3/WF will only be active if it’s part of the activation condition.
• 1st Alarm: (DET 1, DET 2, DET 3/WF, SUPV 1, or Manual Release)
Note: SUPV 1 will only be active if it’s part of the activation condition.
• Agent Pre-Release Condition
• Agent Release Condition
• Manual Release Input
• Waterflow Input
• Abort Input
• Supervisory Input
• Any Alarm: (DET 1, DET 2, DET 3/WF, or Manual Release)
The trouble relay is "normally energized” with AC Power ON and will de-energize upon receipt
of a trouble condition. This change is non-latching and the relay will revert to its normal state
upon removal of the trouble state. For Central Station operation, especially with an intermittent
AC power supply, it may be desirable to delay the change of state of the trouble relay in case
of AC power failure. See Chapter 3, Configuration to enable this configuration.
The AEGIS provides one auxiliary power output rated 1 Amp at 24 Vdc (Nominal) and is
intended to be used with 4-wire devices such as Flame Detectors, Smoke Detectors, etc. All
applicable compatible devices contained in this manual may be used. For FM installations, use
FM Approved Flame Detectors.
Note: Operation of the System Reset control switch will interrupt the Auxiliary Power Output
for a period of time not exceeding five (5) seconds.
CHAPTER 2
INSTALLATION
Check and ensure that the received shipment of the Kidde AEGIS™ unit consists of:
Description Quantity
The materials listed below are not supplied with the system, but are required for installation.
• No. 10 or 3/16-inch mounting hardware
Take special care when installing the system and follow the guidelines given in the following
paragraphs.
Install electrical conduit and wiring in accordance with applicable National Electrical Code,
NFPA Standard and state and local building code requirements.
The incoming AC voltage must be stable and within the permissible voltage range. This is
especially important in new construction where incoming power may be high or unstable, and
temporary connections may cause large inductive voltage spikes.
Most supervised circuits use voltage or current sensing circuits that are sensitive to induced
voltages on the sensor wiring.
Do not under any circumstances run AC power, speaker, PA, intercom or switch
control wiring with inductive loads in the same conduit or in the immediate vicinity
CAUTION of sensor wiring. Control unit damage or malfunction may result.
The system should never be connected to a conduit or green wire circuit that is also
used to power resistance heating, motors, fans, air-conditioning equipment or
fluorescent lighting circuits. Leakage currents from these types of circuits into the
ground return could damage sensitive system components.
A separate earth ground or cold water pipe with properly bypassed water meter
should be used. All external devices such as horns or alarm bells should have their
housings grounded. All low-level signal cables should have foil shielding and a
drain wire to be installed in their own grounded metallic conduit.
Ground only one end of the drain wire or shield, since a ground on both ends will
provide a current path and thus subject the circuit to induced RF currents and
noise. A minimum alternative would be to use shielded #16 AWG twisted pair wire.
Adequate lightning protection must be provided for the incoming power at the
CAUTION building entry. Arrestor circuitry and earth grounding should be in accordance with
article 250 of the National Electric Code.
There is no known protective device available that is capable of protecting
equipment from damage caused by a direct lightning hit due to the extremely high
energy released (10 million to 100 million volts at 10,000 to 30,000 or more
amperes). However, line surges from indirect strikes and voltage spikes induced
through power line load switching can be minimized by the addition of transient
suppressors.
Although the Kidde AEGIS circuits have transient protection devices, additional
protection is required in areas subject to above average lightning activity or
induced voltage spikes and fluctuations due to power line load switching.
For all subassemblies, strip 1/2-inch (13 mm) and leave straight for insertion beneath head of
screw on one side only (do not loop conductor around screw). If using stranded conductor,
twist and tin or use terminal lug.
Table 2-3 lists wiring gauge recommendations, resistance, and maximum length.
Refer to Appendix C for maximum allowable wire resistance for alarm signaling and initiating
circuits.
Operating power for all initiating and indicating circuits is provided by the power supply. 4-wire
24 Vdc smoke detectors and other listed, compatible external 24 Vdc loads may be powered
from the power auxiliary output. DC load calculations must be performed to determine if the
power supply is capable of providing the total system current demand. The calculations will
also determine the minimum standby battery capacity in accordance with applicable NFPA
codes. Refer to Appendix A for Battery Capacity Calculations.
Position the enclosure in a readily accessible and easily visible location. Ensure there is
1-1/2 ft. (457 mm) clearance or more in front and to the door hinge side of the enclosure for
the door to swing open completely.
The type of hardware is at the discretion of the installer, but must be in accordance with good
electrical and safety practices.
19 in.
(483 mm)
66 in.
(1676 mm)
MAX.
FLOOR
14-1/4 in.
(362 mm)
13-1/8 in.
(333 mm)
9-1/8 in.
(232 mm)
5-1/8 in.
(130 mm)
1-1/8 in.
(29 mm)
1-1/2 in.
(38 mm)
TOP VIEW
1/2 in.
(13 mm)
5 in.
(127 mm)
GROUND
STUD
8 in.
(203 mm)
18-13/16 in.
17 in. (978 mm)
(432 mm)
19 in.
(483 mm)
GROUND
STUD
14-1/4 in.
(362 mm)
5 in.
(127 mm)
TOP VIEW
18-13/16 in.
WALL CUTOUT (978 mm) 19-1/8 in.
(486 mm)
14-3/8 in.
(365 mm) 5 in.
(127 mm)
2. Position and plumb the back box in the opening made in Step 1. Ensure that the front edge
of the back box is at least 3/4-inch (19 mm) from the surface of the wall. Secure the back
box to the wall with appropriate mounting bolts (up to 1/4-20).
3. Attach wiring conduit to the enclosure through the enclosure knockouts, and pull the
required number of wires through the conduit to the enclosure. Leave approximately 2 to
3 feet (600 to 900 mm) of wire length in the enclosure for future internal connections.
A Trim Ring (P/N 76-600000-007) can be used to enhance the final installed appearance of a
semi-flush mounted AEGIS unit.
1-1/2 in.
(38 mm) TYP.
ALL AROUND
14-9/16 in.
(370 mm)
INSIDE
23-13/16 in.
(605 mm) 20-13/16 in.
(529 mm)
INSIDE
17-9/16 in.
(446 mm)
1-3/4 in.
(44 mm)
MIN.
COVER
Use a ground strap to prevent static discharge that could damage the power
CAUTION supply.
1. Make sure the control unit location is dry and that the enclosure is free of construction dust
and metal shavings prior to installing the power supply.
2. Remove the power supply unit from its shipping carton.
3. The AEGIS unit is supplied with one of two equivalent power supplies. Compare the
terminal block wiring legend on the provided power supply with the diagrams in Figure 2-6
and connect the wiring harness as shown.
4. Connect the Power Supply Wiring Harness (P/N 06-220025-001) to the power supply unit.
Next connect the fork end of the green ground wire (P/N 06-129928-002) to the
earth-ground terminal of the power supply unit. Refer to Figure 2-6 and Figure 2-7 for wire
harness and earth-ground connections.
NEUTRAL
TO PSU J2
+ 24 V
- 24 V
LINE
GND
CONNECTOR ON
PCB
WHT/BLK
WHT
BLK
RED
GRN
OR
NEUTRAL
TO PSU J2
GND
LINE
- V
- V
+V
+V
CONNECTOR ON
PCB
WHT/BLK
WHT
BLK
RED
GRN
ATTENTION!
THE CONTROL UNIT IS SUPPLIED WITH ONE OF TWO EQUIVALENT
POWER SUPPLIES. COMPARE THE TERMINAL BLOCK WIRING LEGEND
ON THE PROVIDED POWER SUPPLY WITH THE DIAGRAMS AND
CONNECT THE WIRING HARNESS AS SHOWN IN THE APPLICABLE DIAGRAM.
FASTENING TAB
FOR SCREW
230 V
115 V
RETENTION
TABS
TYP (2)
Use a ground strap to prevent static discharge that could damage sensitive
CAUTION components on the Printed Control Board.
1. Make sure the control unit location is dry and that the enclosure is free of construction dust
and metal shavings prior to installing the PCB.
AC PROTECTIVE COVER
(WITH STANDOFF)
2. Securely screw one each of the eight (8) 2-3/8 inch (60 mm) aluminum standoffs
(P/N 06-118533-001) onto each of the eight (8) threaded PEMs on enclosure backbox (top
three rows) as shown in Figure 2-8.
Note: Do not use the bottom row of threaded PEMs.
3. Slip on a wrist ground strap and clip the ground strap to the earth ground in the enclosure.
Do not remove the PCB from its shipping carton unless you have established a common
earth-ground potential among yourself, the enclosure, and the PCB shipping carton.
4. Remove the PCB from its shipping carton and position each of its eight (8) mounting holes
over one of the aluminum standoffs so that the AC-input terminal block is in the lower-left
corner.
5. Secure the PCB to the standoffs using the seven (7) 8-32 x 5/16 (8 mm) (P/N 06-250354-
082). Do not tighten the screws at this time.
The PCB mounting hole in the lower left corner utilizes a longer nylon screw that also holds
the AC Safety Cover in place. See Paragraph 2-3.4.1.
6. Place the free end of the longer of the two factory-installed Earth-Ground wires under the
screw assembly of the PCB (marked detail A in Figure 2-9). Tighten the remaining eight
screws. Be careful not to over-tighten.
7. Plug the harness from the power-supply unit into Connector J2 in the lower-left-hand
corner of the PCB.
TB10
TB11
TB12
A
AC SUPPLY SELECT SWITCH (S6)
TB19
TB13
The control unit uses AC power (by others) as the primary power source, together with a 24 Vdc
standby battery.
Use caution when connecting AC power to the control unit. High-voltage and
AC-powered circuits are present in the control unit. Be sure to take suitable
WARNING precautions and to adequately ground the control unit to reduce the risk of
electrical shock.
AC power must be provided to the control unit using a 3-conductor 14 AWG cable. The AC
power cable shall be run through a one-inch conduit from a dedicated, 15-ampere circuit
breaker. The conduit must be attached to the left side of the enclosure through one of the
upper left corner knockouts.
PROTECTIVE COVER
FOR AC POWER INPUT
ENCLOSURE WALL
POWER CONNECTIONS
FROM AC SUPPLY
TO PSU
EARTH GND
4. To install the Protective Cover for AC Power input, fold along scored lines as shown in
Figure 2-10.
5. Insert spacer and align thru holes and spacer with PCB standoff in lower left corner.
6. Attach to PCB with nylon screw.
TB12
BATT OUT
12 V 12 V
BATTERY BATTERY
TB12
BATT OUT
12 V 12 V
BATTERY BATTERY
ADDITIONAL BATTERY
CABLES TYP (BY INSTALLER)
BATTERY HARNESS (P/N 06-129925-002)
NOTE:
12 V 12 V LOCATE ALL BATTERIES IN A COMMON BATTERY
BATTERY BATTERY CABINET, OR IN CLOSE-COUPLED BATTERY CABINETS
WITH ALL BATTERY CABLES IN A CONDUIT.
The PCB provides the following input and output terminations as shown in Figure 2-12.
TB13
7 6 7 6
3 3
1 2 1 2
EOL RESISTOR
1+ 2+ 2- 1- 5.1K, 0.5 W
P/N 06-129025-002
7 6 7 6
3 3
1 2 1 2
1+ 2+ 2- 1-
EOL RESISTOR
TB1, TB2, TB3 5.1K, 0.5 W
P/N 06-129025-002
EOL RESISTOR
1+ 2+ 2- 1- 5.1K, 0.5 W
P/N 06-129025-002
1+ 2+ 2- 1-
EOL RESISTOR
5.1K, 0.5 W
TB1, TB2, TB3, TB4, P/N 06-129025-002
TB5, TB6, OR TB7
LEGEND
+ +
- -
EOL RESISTOR
5.1K, 0.5 W
P/N 06-129025-002
1+ 2+ 2- 1-
+ +
- -
EOL RESISTOR
1+ 2+ 2- 1- 5.1K, 0.5 W
P/N 06-129025-002
LEGEND
TB14 OR TB15
RED BLK
SOLENOID
P/N 06-220023-001
IN-LINE RELEASING DEVICE - MUST
BE INSTALLED CLOSE NIPPLED TO
SOLENOID ENCLOSURES
TB14 OR TB15
SOLENOID
TB14 OR TB15
BLK RED
SOLENOID
BLK RED
TB14 OR TB15
SOLENOID
TB14 OR TB15
BLACK
N.C.
WHITE
N.O.
NOTE
TO MAKE THIS A POWER LIMITED CIRCUIT, ADD IN-LINE RELEASING
DEVICES (P/N 06-220023-001) AS SHOWN IN FIGURE 2-15C.
Figure 2-15E. Agent Release Circuit for XV and CXV Control Heads
TB14 OR TB15
Note: 1. Polarities must be observed for solenoids P/N 890181 and 48650001.
2. The inline releasing device P/N 06-220023-001 must be close nippled
to Solenoid enclosures.
3. The ARC is Non-Power-Limited when in-line device is not used.
4. Route Non-Powered-Limited wiring at least 1/4-inch away from all Power-Limited
wiring. See Appendix F. Do not attach Power-Limited wiring to the same
terminal block.
5. When firing initiators, the limiting resistor must have a rating of 1 watt minimum.
6. Control Head P/N 90-487100-001 when used with the control unit must
include Solenoid P/N 83-100034-001 and Microswitch P/N 87-120039-001.
MOUNTING SCREWS
DEAD-FRONT
PANEL (SIDE VIEW)
DEAD-FRONT
PANEL
Note: Switch guard is keyed and can only be installed one way.
4. Install locking nut on the abort switch.
5. Install abort switch from back of enclosure door. Attach pushbutton switch guard and
tighten.
SWITCH
MANUAL GUARD
RELEASE
SWITCH LOCKING
MANUAL RELEASE NUT
INTERNAL
TOOTH
LOCKWASHER
ABORT AND LOCKING RING
SWITCH
LOCKING
ABORT PUSHBUTTON NUT
SWITCH
GUARD
6. Attach black wires from switch wire harness to the right side of the toggle switch as shown
in Figure 2-18.
7. Route switch wire harness as shown in Figure 2-18.
8. Install cable clamps and 8-32 kep nuts to secure switch wire harness to enclosure door.
9. Run the black wires from the Manual Release switch to TB4 on the PCB. Refer to
Figure 2-13 through Figure 2-15 for wiring configurations.
10. Run the white wires from the Abort switch to TB5 on the PCB. Refer to Figure 2-13 through
Figure 2-15 for wiring configurations.
Power-limited wiring from the front cover Manual Release and Abort switches
to their respective terminal blocks on the PCB must be routed to maintain a
CAUTION 1/4-inch distance from non-power-limited wiring. Refer to Appendix F for more
details.
- WHITE WIRES
TO TB5
- BLACK WIRES
TO TB4
BLACK WIRES
FROM SWITCH
WIRE HARNESS
CABLE CLAMP
MANUAL
AND 8-32 KEP NUT
RELEASE
(SUPPLIED)
SWITCH
(TYP 3 PLACES)
REAR VIEW
CHAPTER 3
CONFIGURATION
The Kidde AEGIS™ is suitable for a wide variety of applications by means of configuring its
inputs and outputs. Inputs and outputs are configured via the operator interface. The following
sections details on how to enter or change configuration settings.
POSITION
1 2 3
To enter the configuration setting mode, you must enter the factory default password (186)
via the operator interface. Ensure that no alarms or supervisories are present and perform the
following.
1 Press and hold the Acknowledge control switch and within five (5) seconds,
press the System Reset control switch.
The control unit exits the configuration mode upon status change, or if more than five (5)
minutes have expired since the last control switch press. Only saved changes are retained by
the control unit.
In the event that the entered password is incorrect, the display reads "Err" for three (3)
seconds and then prompts for entering the password again by displaying "0" as the first digit.
When at the "Err" display, press the Signal Silence control switch to display a random 3 digit
code. Make a note of the code and call Technical Support. The control unit does not timeout
(exit out of the configuration mode) when the display reads the random 3-digit code.
Note: Do not press any buttons while this 3 digit code is being displayed.
Technical Support will translate this 3 digit code to a new password that will work only on a
control unit displaying the original random code for one time only. When given the Temporary
Password (the 3 digit code should still be displayed), press the Signal-Silence control switch.
The display is now exactly as it would be to enter a password:
Enter the Temporary Password in the same manner as entering a regular Password.
When the password has been accepted (and the first configuration item is being displayed
"00x", where x is the left most digit of the Temporary Password), you should:
1. either press the Signal Silence control switch in order to accept and save the current
Temporary Password as a Permanent Password; OR
2. enter the desired Password in configuration items 0, 1, and 2, and then press the Signal
Silence control switch in order to accept and save it.
This section describes the configuration settings for the AEGIS unit. Use Table 3-1 to set the
configuration settings.
• To advance to the next selection for an item, press the Output Disable control switch.
• To advance to the next item, press the Acknowledge control switch.
• To accept a configuration setting change and exit the Configuration menu at any step in
the process, press the Signal Silence control switch. Check the configuration by starting
the configuration process again, checking all items, and exiting by pressing System Reset
after inspecting the last item.
• To exit the configuration menu at any time, press the System Reset control switch. This
reverts the control unit to its previous state.
Note: The control unit takes about five (5) seconds to boot up after exiting the configuration
menu.
POSITION
1 2 3
Configuration
Default
Number Configuration Item Configuration (Position 3) Selection
Mode
(Position 1, 2)
Configuration
Default
Number Configuration Item Configuration (Position 3) Selection
Mode
(Position 1, 2)
Configuration
Default
Number Configuration Item Configuration (Position 3) Selection
Mode
(Position 1, 2)
Configuration
Default
Number Configuration Item Configuration (Position 3) Selection
Mode
(Position 1, 2)
Configuration
Default
Number Configuration Item Configuration (Position 3) Selection
Mode
(Position 1, 2)
Configuration
Default
Number Configuration Item Configuration (Position 3) Selection
Mode
(Position 1, 2)
Configuration
Default
Number Configuration Item Configuration (Position 3) Selection
Mode
(Position 1, 2)
Configuration
Default
Number Configuration Item Configuration (Position 3) Selection
Mode
(Position 1, 2)
Configuration
Default
Number Configuration Item Configuration (Position 3) Selection
Mode
(Position 1, 2)
Configuration
Default
Number Configuration Item Configuration (Position 3) Selection
Mode
(Position 1, 2)
Configuration
Default
Number Configuration Item Configuration (Position 3) Selection
Mode
(Position 1, 2)
NOTES:
1. If "circuit not used" is selected, do NOT install an EOL as the control unit needs to see open
circuit. Using an EOL will cause trouble.
2. DET 1, DET 2, and DET 3/WF will activate first alarm ONLY IF it is part of the ARC activation
condition.
3. SUPV 1 will activate first alarm ONLY IF it is part of the ARC activation condition.
4. If Initiator is selected for any Release circuit output, the respective Power-Limited switch setting
is ignored.
5. The NAC will be driven by both ARC 1 and ARC 2. However the first ARC to reach each state is
given precedence. Once its cycle is complete, the other ARC, if active, will gain control.
6. The NAC may be related to neither ARC if the control unit is used for non-suppression
applications. Also see notes 8 to 10.
7. An OFF condition is different from NOT USED and will require that an EOL be installed.
8. In addition to being selectable for NACx First Alarm, the various tones are also selectable in the
condition that both ARCs are not used and one of DET 1, DET 2 or DET 3/WF is in alarm.
9. In addition to being selectable for NACx Pre-Release, the various tones are also selectable in the
condition that both ARCs are not used and two of DET 1, DET 2 or DET 3/WF are in alarm.
10. In addition to being selectable for NACx Releasing, the various tones are also selectable in the
condition that both ARCs are not used and all of DET 1, DET 2 and DET 3/WF are in alarm.
CHAPTER 4
OPERATION
4-1 INTRODUCTION
This chapter explains how to read the control unit display, interpret the LEDs, and how to reset
the unit. The following are the operational modes of the control unit:
• Normal Mode
• Alarm Signal
• Supervisory Signal
• Trouble Signal State
In the normal mode, the control unit continuously monitors all inputs and outputs for any
change of state. In the normal mode the Green AC ON LED is the only illuminated LED. The
buzzer and NACs are silent, The Programmable Relays are de-energized, and the Trouble relay
is energized.
In the Alarm state, the control unit has detected one or more active inputs on its input circuits.
The states of Alarm are:
1. First Alarm — caused when input is received from:
• DET 1, or
• DET 2, or
• DET 3 (Detector or Waterflow), or
• Manual Release
2. Pre-Release — caused when input is received from:
• DET 1 in Single-Zone release mode, or
• DET 2 in Single-Zone release mode, or
• DET 1 and DET 2 in Cross-Zone Mode, or
• DET 1 and DET 3 (Waterflow) in Cross-Zone mode, or
• DET 2 and DET 3 (Waterflow) in Cross-Zone mode, or
• DET 1 and Supv 1 in Cross-Zone mode, or
• DET 2 and Supv 1 in Cross-Zone mode, or
• Manual Release
3. Releasing — caused when the pre-release countdown timer has counted down to zero. In
this state, the control unit is actively in the process of activating its Agent Release
Circuit(s).
4. Post-Release — condition when the control unit has released Agent.
In the supervisory state, the control unit has detected a change in state of one or both of its
supervisory input circuits, or its PCB mounted Output Disable switch. A flashing LED indicates
one or more unacknowledged supervisory events. A steady LED indicates all supervisory
events have been acknowlwdged. The LED turns off when the AEGIS receives supervisory-off
messages from all initiating devices that reported supervisory conditions.
In the trouble state, the control unit has detected one or more active troubles such as AC
failure, open circuits, short circuits, ground faults, activation of abort during non-alarm
condition, and so on. In the trouble mode, the Trouble LED and circuit-specific LED will flash,
the internal buzzer will sound, and the trouble relay will de-energize.
With the exception of microprocessor or PCB troubles, all other troubles may be acknowledged
either automatically (i.e., the trouble event reverts to normal condition) or manually by the
operator by pressing the Acknowledge or System Reset control switches.
Illegal button presses, or illegal combinations of button presses, shall result in a momentary
display of "Err".
4-2.1 Acknowledge
Pressing the Acknowledge control switch during an active trouble, supervisory, or alarm allows
the operator to signal the AEGIS that a new event currently being displayed is understood. The
AEGIS control unit’s buzzer will silence and all flashing Alarm, Trouble, or Supervisory LEDs
will light steady.
Pressing the Signal Silence control switch at any alarm state will turn on the Signal Silenced
LED and silence all NACs unless configured otherwise (non-silenceable).
Resets the system including turning off outputs and interrupting power to all input and output
circuits for a period of five (5) seconds.
CHAPTER 5
TESTING AND MAINTENANCE
The Kidde AEGIS™ must be inspected, tested and maintained in accordance with the
requirements of NFPA 72 (latest edition), and/or the local Authority Having Jurisdiction (AHJ).
Two different sources of power can be connected to the control unit. Disconnect
both sources of power and critical components such as special extinguishing
systems and relays controlling facility-power shutoff before servicing the
WARNING control unit. The control unit and associated equipment may be damaged by
connecting or disconnecting wiring while the control unit is energized.
For inspection, testing and maintenance of the associated extinguishing system, refer to the
manufacturers instructions and the standards and codes that apply to that systems.
The frequency shall be per NFPA 72 (latest edition) stated below, or as required by the local
Authority Having Jurisdiction (AHJ), whichever is more stringent.
5-3 TESTING
Generally, if one of the batteries is low, the other(s) will soon fail. It is advisable to replace all
the batteries in a set when one requires replacement. Any battery that has been in service for
36 months or more must be replaced.
The following sequence will display the battery open circuit voltage and charge current:
1. Press and hold Acknowledge and Signal Silence control switches simultaneously for five
(5) seconds. As long as both keys are pressed, the battery voltage is displayed for three
(3) seconds, and then the battery current. These alternate every three (3) seconds.
2. The battery test will exit if either control switch is released, or if a control unit status
change occurs.
Battery voltage will be as shown in Figure 5-1. The units are in Volts.
Battery charge current will be as shown in Figure 5-2. The units are in Amps.
Before replacing batteries, disconnect AC power. Batteries should be replaced at least once
every 36 months, or as directed by the local Authority Having Jurisdiction. Do not install a
battery set whose open circuit voltage is less than 22 volts.
CHAPTER 6
TROUBLESHOOTING
6-1 PURPOSE
This chapter provides diagnostic information, probable causes, and the method(s) to return the
Kidde AEGIS to proper operating conditions.
Prior to taking corrective action or performing any maintenance functions, you must refer to
Paragraph 5-1 and follow the instructions specified there.
Diagnostics allow the operator to determine the cause of trouble. To access the diagnostic
function, the control unit needs to have at least one active trouble condition. Perform the
following:
1 Press and hold the Signal Silence control switch for five (5) seconds. A 3-digit
Trouble code will be displayed until the Signal Silence control switch is
released (sample on right).
2 If multiple troubles exist, the display will blink one second on, one second off,
and the trouble codes will sequence to the next code every time the display
illuminates. When all codes have been displayed, the sequence will repeat until
the Signal Silence control switch is released (sample on right).
006 Low Battery Check battery voltage, must be greater than 20.5 Vdc in the absence
of primary power. When voltage drops as low as 19.5 Vdc, the
charger will disconnect and the outputs will be isolated.
007 Reversed Battery Verify Battery polarity.
008 Detector #1 Open Circuit Look for discontinuity in detector #1 wiring.
Check for missing/incorrect value 5.1K resistor.
009 Detector #2 Open Circuit Look for discontinuity in Detector #2 wiring.
Check for missing/incorrect value 5.1K resistor.
010 Detector #3/Waterflow Open Look for discontinuity in Detector #3/Waterflow wiring.
Circuit
Check for missing/incorrect value 5.1K resistor.
011 Manual Release Open Circuit Look for discontinuity in manual release circuit wiring.
Check for missing/incorrect value 5.1K resistor.
012 Supervisory #1 Open Circuit Look for discontinuity in Supervisory #1 wiring.
Check for missing/incorrect value 5.1K resistor.
013 Supervisory #2 Open Circuit Look for discontinuity in Supervisory #2 wiring.
Check for missing/incorrect value 5.1K resistor.
014 Invalid Abort Abort station activated in non-alarm condition.
015 Abort Open Circuit Look for discontinuity in circuit wiring.
016 ARC #1 Short Circuit Troubleshoot ARC #1 wiring by breaking-up circuit to isolate the
short.
017 ARC #1 Open Circuit Look for discontinuity in ARC #1 wiring.
Check ARC #1 configuration.
018 ARC #2 Short Circuit Troubleshoot ARC #2 wiring by breaking-up circuit to isolate the
short.
019 ARC #2 Open Circuit Look for discontinuity in ARC #2 wiring.
Check ARC #2 configuration.
020 NAC #1 Short Circuit Troubleshoot NAC #1 wiring by breaking-up circuit to isolate the
short.
021 NAC #1 Open Circuit Look for discontinuity in NAC #1 wiring.
Check for missing/incorrect value 5.1K resistor.
022 NAC #2 Short Circuit Troubleshoot NAC #1 wiring by breaking-up circuit to isolate the
short.
023 NAC #2 Open Circuit Look for discontinuity in NAC #1 wiring.
Check for missing/incorrect value 5.1K resistor.
024 NAC #3 Short Circuit Troubleshoot NAC #1 wiring by breaking-up circuit to isolate the
short.
025 NAC #3 Open Circuit Look for discontinuity in NAC #1 wiring.
Check for missing/incorrect value 5.1K resistor.
026 ARC #1 Not Open Circuit Check configuration to make sure ARC #1 is enabled.
027 ARC #2 Not Open Circuit Check configuration to make sure ARC #2 is enabled.
028 Serial Cable Connected Remove serial cable.
CHAPTER 7
PARTS LIST
APPENDIX A
BATTERY CAPACITY CALCULATIONS
To calculate battery capacity for a specific application, first select the duration for which
standby and alarm power is required using Table A-1.
Local or Central Station (Protected Premises) Fire Alarm Systems per NFPA 72 24 hours 5 minutes
Clean Agent Suppression Systems per NFPA 12, 12A, 12B, and 2001 24 hours 5 minutes
Deluge or Pre-Action Water Spray Systems per Factory Mutual 90 hours 10 minutes
Table A-2 lists the power consumption of the various system components.
1 The standby and alarm values for the AEGIS include the Trouble Relay.
2
The Auxiliary Power Output current value stated is the maximum allowed.
3 The Standby current stated for Ionization, Photoelectric, Electronic Heat, Duct and Contact Heat Detectors is
for each detector. The Alarm current is for the Detection Circuit.
4 The current value stated for the Notification Appliance Circuits is the maximum each.
5 For the Alarm current values of Steady Release Solenoids, refer to Appendix B.
6 Momentary Agent Release Solenoids and Initiators are negligible in their current requirements and do not
Use Table A-3 to calculate the Standby and Alarm Power requirement of the Kidde AEGIS.
A-3.1 Procedure
1. Insert the actual count of components and devices into the Standby Quantity column.
2. Insert the quantity of these components devices which can be in alarm into the Alarm
Quantity column.
3. Multiply the quantity count by the Each — Standby and Alarm Power and insert these
values into the Total column.
4. Calculate the sum of the values in the Total Standby and Total Alarm columns to arrive
at the Total Standby Power and Total Alarm Power in milliamperes.
5. Divide the mA values for Total Power in Amperes.
Total Power in mA
Total Power in Amperes
1
The Auxiliary Power Output current value stated is the maximum allowed. See Note 6 below.
2
The value stated for the Programmable Relays is for each individual relay when energized.
3 Standby currents should be considered for all Ionization, Photoelectric, Duct and Heat Detectors in the three
Detection Circuits. However, since only one detector can be in Alarm, the Alarm current should only be con-
sidered for the entire Detection Circuit.
4 The value stated for the NACs is the maximum for each. See Note 6 below.
5 For the Alarm current values of Steady Release Solenoids, refer to Appendix B.
6 Since the Power Supply of the Kidde AEGIS unit is rated at 5.4 Amps, the system designer should ensure
that the system circuits are loaded so as to keep the calculated alarm current equal to or less than 5.4
Amps.
Based on the “Duration” for which battery backup is required (refer to Paragraph A-1) and the
Total Standby Power and Total Alarm Power values (refer to Paragraph A-3), the next step
is to calculate the battery capacity in Ampere-Hours (AH) using Table A-4.
Multiply Duration
Total Power Required (Amps) Equals Ampere-Hour (AH)
By (Hours)
Note: 1. The above battery capacity calculation and subsequent selection assumes that the
battery is installed in ambient room temperatures. If installed in below ambient, consult
the battery manufacturer for requirement of additional deration factors not considered
above.
2. 5 minutes = 0.083 hours
10 minutes = 0.167 hours
APPENDIX B
LIST OF AGENCY LISTED COMPATIBLE DEVICES
Electronic 135°F Fixed with 15°F ROR Heat Detector THD-7052 70-520000-001
I Resistance Max.
12 14 16 18
Device (Min.) (Max.) On Time Number per Agency
AWG AWG AWG AWG
Amps Ohms Circuits
* Must be used in conjunction with Microswitch P/N 87-120039-001 for momentary operation.
83-131025-001 * 3 Momentary 1
* The maximum circuit resistance for this device must be 10 ohms, regardless of the number used. The firing current will be
2.5 Amps.
APPENDIX C
TECHNICAL SPECIFICATIONS
Item Description
A NUMBER OF HAZARDS One (1)
B POWER
AC Main Input 120 Vac/240 Vac 50/60 Hz (90 to 264 Vrms, 47 to 63 Hz)
Current Consumption
3.2 Amps
120 Vac:
1.6 Amps
240 Vac:
Required Breaker 15 Amps
Power Supply Output 5.4 Amps @ 27 Vdc
Battery Charger Output 6 Amps @ 27 Vdc
Battery Capacity Up to 68 AH @ 24 Vdc
Battery Cutout Voltage 18.6 Vdc
Auxiliary Power Output 1 Amp maximum @ 24 Vdc Nominal
Battery Transfer 85% of 120 Vac
85% of 240 Vac
C Input Circuits
C.1 Detection Circuits Three (3)
- Two (2) for Suppression Input
- Third configurable as either independent Detection Circuit or
for Waterflow
Compatible Devices - 25 conventional electronic Smoke/Heat detectors listed in
Appendix B.
- A quantity of Normally-Open contact-closure devices subject
to maximum allowable wiring resistance.
Circuit Type - Class A (Style D) or Class B (Style B) supervised
- Detects Opens and Ground Faults
- Power Limited
Circuit Voltage Nominal 24 Vdc, 28 Vdc maximum
Maximum Line Resistance 100 ohms per loop
Maximum Alarm Current 70 mA
End-of-Line Resistor 5.1K, 5%, 1/2 W
Item Description
C.2 Manual Release One (1)
Compatible Devices A quantity of Normally-Open contact-closure devices subject to maximum
allowable wiring resistance.
Circuit Type - Class A (Style D) or Class B (Style B) supervised
- Detects Opens and Ground Faults
- Power Limited
Circuit Voltage Nominal 24 Vdc, 28 Vdc maximum
Maximum Line Resistance 100 ohms per loop
Maximum Current 10 mA
End-of-Line Resistor 5.1K, 5%, 1/2 W
C.3 Abort Input One (1)
Compatible Devices A quantity of Normally-Open contact-closure devices subject to maximum
allowable wiring resistance.
Circuit Type - Class A (Style D) or Class B (Style B) supervised
- Detects Opens and Ground Faults
- Power Limited
Circuit Voltage Nominal 24 Vdc, 28 Vdc maximum
Maximum Line Resistance 100 ohms per loop
Maximum Current 10 mA
End-of-Line Resistor 5.1K, 5%, 1/2 W
C.4 Supervisory Input Two (2)
Compatible Devices A quantity of Normally-Open contact-closure devices subject to maximum
allowable wiring resistance.
Circuit Type - Class A (Style D) or Class B (Style B) supervised
- Detects Opens and Ground Faults
- Power Limited
Circuit Voltage Nominal 24 Vdc, 28 Vdc maximum
Maximum Line Resistance 100 ohms per loop
Maximum Current 10 mA
End-of-Line Resistor 5.1K, 5%, 1/2 W
Item Description
D OUTPUT CIRCUITS
D.1 Notification Appliance Three (3)
- NAC 1: First Alarm Condition
- NAC 2: Pre-Release Condition
- NAC 3: Release Condition
Compatible Devices A quantity of Polarized 24 Vdc Notification Appliances subject to the
maximum current and maximum allowable voltage drop per circuit.
Circuit type - Class A (Style Y) or Class B (Style Z) supervised
- Detects Opens and Ground Faults
- Power Limited
Circuit Voltage Nominal 24 Vdc, 28 Vdc maximum
Total Voltage Drop at End-of- 2V
Line
End-of-Line Resistor 5.1K, 5%, 1/2 W
D.2 Output Relays Four (4)
- Programmable: Three (3), normally de-energized with power on
- Trouble: One (1), normally energized with power on
Relay Type Voltage free, Form-C (1 N.O. and 1 N.C.)
Contact Rating 3 Amps @ 30 Vdc (resistive)
D.3 Releasing Circuits Two (2)
- ARC 1
- ARC 2
Compatible Devices On each circuit the following devices listed in Appendix B
- 1 or 2 Control Head Solenoids
- 1 Initiator
- 1 or 2 FM Pre-Action/Deluge/Sprinkler Solenoids
Releasing Configurations - Solenoids on both ARC 1 and ARC 2
- Solenoids on ARC 1 and one Initiator on ARC 2 or vice-versa
- One Initiator on both ARC 1 and ARC 2
Circuit Type - Class B (Style Z) supervised
- Detects Opens and Ground Faults
- Normally no Short detection and non-Power Limited
- Except with Initiators, power limiting and short circuit detection options
enabled with In-line Diode-Resistor device
Operating Voltage Nominal 24 Vdc, 28 Vdc maximum
End-of-Line Resistor Not required
Item Description
E ENCLOSURE
Degree of Protection NEMA 1
Material of Construction 18 Gauge (0.053 inches or 1.35 mm) sheet steel
Color Red
Assembled Dimensions
- With Standard Door 14-1/4 in. Width x 5 in. Depth x 19 in. Height
(362 mm x 127 mm x 483 mm)
APPENDIX D
FM RULES FOR PREACTION/DELUGE SYSTEMS
Kidde AEGIS™ applications which require Factory Mutual (FM) approved Pre-Action and/or
Deluge Systems must conform to the following guidelines:
• Detection Zone 1 (Det1), Detection Zone 2 (Det2) and Waterflow (W'Flow) Initiating
Circuits must be configured for Class A, Style D wiring.
• The Battery backup system must provide for 90 hours of Standby operation followed by 10
minutes of Alarm operation. Refer Appendix A for calculations.
• The Agent Release Output must be configured for Deluge Solenoid activation. The Solenoid
Activation Time must be set either for:
– 10 minutes, or
– 15 minutes, or
– On-until-reset.
The wiring connection of the Control Unit to the Deluge Solenoids must be as detailed in the
Installation section of this Manual.
APPENDIX E
CENTRAL STATION OPERATION
The Kidde AEGIS™ should be configured for Central Station operation as follows:
• One of the three (3) Programmable Relays should be configured for any alarm. For
example:
2,
1 3, OR 1
4
• The Trouble Relay should be set to delay AC Failure Response by a period acceptable to
the local AHJ. For example:
1 15 X
A Silent Knight DACT Model 5104B must be wired to the control unit, as shown in Figure E-1.
Refer to the Model 5104B Installation Manual for information regarding connection of the DACT
to telephone lines for Alarm and Trouble transmission(s).
Note 1: Wiring must be installed in conduit within 20 feet.
Note 2: Central Station is not suitable for use with Canadian applications.
TB 8
NO NC C
TROUBLE
1 2 3 4 5 6 7 8 9 10 1112
RELAY 4.7K
TB 9, TB10, or TB11
NO NC C
PROGRAMMABLE
4.7K
RELAYS
SUPERVISORY
TB 9, TB10, or TB11
NO NC C
PROGRAMMABLE
4.7K
RELAYS
PROGRAMMED FOR
GENERAL ALARM
APPENDIX F
ROUTINGS FOR POWER-LIMITED AND
NON-POWER-LIMITED WIRING
This appendix provides guidelines for power-limited and non-power-limited wiring requirements.
The following wiring requirements shall be observed:
• Power-limited and non-power-limited wiring must be physically separated within the
control-unit enclosure
• All power-limited wiring must be separated by at least 1/4-inch (6 mm) from any
non-power-limited wiring
• Power-limited and non-power-limited wiring cannot enter and exit the control-unit
enclosure through the same knockout or conduit.
Figure F-1 shows typical wiring for power-limited and non-power-limited circuits.
TB10
TB11
TB13
RELEASE CIRCUITS
(TB14 AND TB15) CAN BE
WIRED AS POWER-LIMITED
OR NON-POWER-LIMITED
BATTERY WIRING
These instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection with
installation, operation and maintenance. All specifications subject to change without no-
tice. Should further information be desired or should particular problems arise which are
not covered sufficiently for the purchaser’s purposes, the matter should be referred to
A UTC Fire & Security Company KIDDE-FENWAL INC., Ashland, Massachusetts
400 Main Street
Ashland, MA 01721 P/N 06-236716-001 Rev. AB ©2007 Kidde-Fenwal, Inc. All Rights Reserved.
Ph: 508.881.2000 Printed in USA
Fax: 508.881.8920
www.kiddefiresystems.com