Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Im01c22d01-01en (17) - Eja310, Eja430

Download as pdf or txt
Download as pdf or txt
You are on page 1of 83

User’s

Manual Model EJA310 and EJA430


Absolute Pressure and
Gauge Pressure Transmitters
[Style: S2]
IM 01C22D01-01E

IM 01C22D01-01E
17th Edition
CONTENTS

CONTENTS

1. INTRODUCTION ............................................................................................ 1-1


Regarding This Manual ................................................................................. 1-1
1.1 For Safe Use of Product ........................................................................ 1-1
1.2 Warranty ................................................................................................ 1-2
1.3 ATEX Documentation ............................................................................ 1-3

2. HANDLING CAUTIONS ................................................................................ 2-1


2.1 Model and Specifications Check ......................................................... 2-1
2.2 Unpacking ........................................................................................... 2-1
2.3 Storage ................................................................................................ 2-1
2.4 Selecting the Installation Location ...................................................... 2-1
2.5 Pressure Connection ........................................................................... 2-2
2.6 Waterproofing of Cable Conduit Connections .................................... 2-2
2.7 Restrictions on Use of Radio Transceiver .......................................... 2-2
2.8 Insulation Resistance and Dielectric Strength Test ............................ 2-2
2.9 Installation of Explosion Protected Type ............................................ 2-3
2.9.1 FM Approval ................................................................................. 2-3
2.9.2 CSA Certification .......................................................................... 2-5
2.9.3 IECEx Certification ....................................................................... 2-6
2.9.4 CENELEC ATEX (KEMA) Certification ........................................ 2-8
2.9.5 TIIS Certification ......................................................................... 2-11
2.10 EMC Conformity Standards .............................................................. 2-12
2.11 PED (Pressure Equipment Directive) ............................................... 2-12
2.12 Low Voltage Directive ....................................................................... 2-12

3. COMPONENT NAMES .................................................................................. 3-1

4. INSTALLATION ............................................................................................. 4-1


4.1 Precautions ......................................................................................... 4-1
4.2 Mounting .............................................................................................. 4-1
4.3 Changing the Process Connection ..................................................... 4-2
4.4 Rotating Transmitter Section .............................................................. 4-2
4.5 Changing the Direction of Integral Indicator ....................................... 4-3

5. INSTALLING IMPULSE PIPING ................................................................... 5-1


5.1 Impulse Piping Installation Precautions .............................................. 5-1
5.1.1 Connecting Impulse Piping to the Transmitter ............................. 5-1
5.1.2 Routing the Impulse Piping .......................................................... 5-1
5.2 Impulse Piping Connection Examples ................................................ 5-2

6. WIRING .......................................................................................................... 6-1


6.1 Wiring Precautions .............................................................................. 6-1
6.2 Selecting the Wiring Materials ............................................................ 6-1
6.3 Connections of External Wiring to Terminal Box ................................ 6-1
6.3.1 Power Supply Wiring Connection ................................................ 6-1
6.3.2 External Indicator Connection ...................................................... 6-1
6.3.3 BRAIN TERMINAL BT200 Connection ........................................ 6-2
6.3.4 Check Meter Connection .............................................................. 6-2
FD No. IM 01C22D01-01E i IM 01C22D01-01E
17th Edition: Oct. 2008(KP)
All Rights Reserved, Copyright © 1995, Yokogawa Electric Corporation
CONTENTS

6.4 Wiring .................................................................................................. 6-2


6.4.1 Loop Configuration ....................................................................... 6-2
(1) General-use Type and Flameproof Type ...................................... 6-2
(2) Intrinsically Safe Type ................................................................... 6-2
6.4.2 Wiring Installation ......................................................................... 6-3
(1) General-use Type and Intrinsically Safe Type .............................. 6-3
(2) Flameproof Type (TIIS) ................................................................. 6-3
6.5 Grounding ............................................................................................ 6-4
6.6 Power Supply Voltage and Load Resistance ..................................... 6-4

7. OPERATION .................................................................................................. 7-1


7.1 Preparation for Starting Operation ...................................................... 7-1
7.2 Zero Point Adjustment ........................................................................ 7-2
7.2.1 When you can obtain Low Range Value from actual
measured value of 0% (0 kPa, atmospheric pressure); .............. 7-3
7.2.2 When you cannot obtain Low Range Value from actual
measured value of 0%; ................................................................ 7-3
7.3 Starting Operation ............................................................................... 7-4
7.4 Shutting Down Operation .................................................................... 7-4
7.5 Venting or Draining Transmitter Pressure-detector Section ............... 7-4
7.5.1 Draining Condensate .................................................................... 7-4
7.5.2 Venting Gas .................................................................................. 7-5
7.6 Setting the Range Using the Range-setting Switch ........................... 7-5

8. BRAIN TERMINAL BT200 OPERATION ..................................................... 8-1


8.1 BT200 Operation Precautions ............................................................. 8-1
8.1.1 Connecting the BT200 ................................................................. 8-1
8.1.2 Conditions of Communication Line .............................................. 8-1
8.2 BT200 Operating Procedures ............................................................. 8-1
8.2.1 Key Layout and Screen Display ................................................... 8-1
8.2.2 Operating Key Functions .............................................................. 8-2
(1) Alphanumeric Keys and Shift Keys .............................................. 8-2
(2) Function Keys ............................................................................... 8-2
8.2.3 Calling Up Menu Addresses Using the Operating Keys .............. 8-3
8.3 Setting Parameters Using the BT200 ................................................. 8-4
8.3.1 Parameter Summary .................................................................... 8-4
8.3.2 Parameter Usage and Selection .................................................. 8-6
8.3.3 Setting Parameters ....................................................................... 8-7
(1) Tag No. Setup ............................................................................... 8-7
(2) Calibration Range Setup .............................................................. 8-7
(3) Damping Time Constant Setup ..................................................... 8-8
(4) Output Signal Low Cut Mode Setup ............................................. 8-9
(5) Change Output Limits ................................................................... 8-9
(6) Integral Indicator Scale Setup ...................................................... 8-9
(7) Unit Setup for Displayed Temperature ........................................ 8-11
(8) Operation Mode Setup ............................................................... 8-11
(9) Output Status Display/Setup when a CPU Failure ..................... 8-11
(10)Output Status Setup when a Hardware Error Occurs ................. 8-11
(11)Range Change while Applying Actual Inputs .............................. 8-12
(12)Zero Point Adjustment ................................................................ 8-12
(13)Span Adjustment ........................................................................ 8-14
(14)Test Output Setup ....................................................................... 8-15
(15)User Memo Fields ...................................................................... 8-15

ii IM 01C22D01-01E
CONTENTS

8.4 Displaying Data Using the BT200 ..................................................... 8-15


8.4.1 Displaying Measured Data ......................................................... 8-15
8.4.2 Display Transmitter Model and Specifications ........................... 8-15
8.5 Self-Diagnostics ................................................................................ 8-16
8.5.1 Checking for Problems ............................................................... 8-16
(1) Identifying Problems with BT200 ................................................ 8-16
(2) Checking with Integral Indicator ................................................. 8-17
8.5.2 Errors and Countermeasures ..................................................... 8-18

9. MAINTENANCE ............................................................................................. 9-1


9.1 Overview ............................................................................................. 9-1
9.2 Calibration Instruments Selection ....................................................... 9-1
9.3 Calibration ........................................................................................... 9-1
9.4 Disassembly and Reassembly ............................................................ 9-3
9.4.1 Replacing the Integral Indicator ................................................... 9-3
9.4.2 Replacing the CPU Board Assembly ........................................... 9-4
9.4.3 Cleaning and Replacing the Capsule Assembly .......................... 9-5
9.4.4 Replacing the Process Connector Gaskets ................................. 9-6
9.5 Troubleshooting ................................................................................... 9-6
9.5.1 Basic Troubleshooting .................................................................. 9-6
9.5.2 Troubleshooting Flow Charts ....................................................... 9-7

10. GENERAL SPECIFICATIONS .................................................................... 10-1


10.1 Standard Specifications .................................................................... 10-1
10.2 Model and Suffix Codes .................................................................... 10-3
10.3 Optional Specifications ...................................................................... 10-5
10.4 Dimensions ........................................................................................ 10-8

INSTALLATION AND OPERATING PRECAUTIONS FOR


TIIS INTRINSICALLY SAFE EQUIPMENT......................................... EX-A03E

INSTALLATION AND OPERATING PRECAUTIONS FOR


TIIS FLAMEPROOF EQUIPMENT ...................................................... EX-B03E

Customer Maintenance Parts List


DPharp EJA Series Transmitter Section ........................ CMPL 01C22A01-02E
Model EJA310 and EJA430
Absolute and Gauge Pressure Transmitter ......... CMPL 01C22D00-01E

REVISION RECORD

iii IM 01C22D01-01E
1. INTRODUCTION

1. INTRODUCTION
Thank you for purchasing the DPharp electronic • The following safety symbol marks are used in this
pressure transmitter. manual:
The DPharp Pressure Transmitters are precisely
calibrated at the factory before shipment. To ensure WARNING
correct and efficient use of the instrument, please read
this manual thoroughly and fully understand how to Indicates a potentially hazardous situation which,
operate the instrument before operating it. if not avoided, could result in death or serious
injury.
 Regarding This Manual
• This manual should be passed on to the end user.
• The contents of this manual are subject to change
CAUTION
without prior notice.
Indicates a potentially hazardous situation which,
• All rights reserved. No part of this manual may be
if not avoided, may result in minor or moderate
reproduced in any form without Yokogawa’s written
injury. It may also be used to alert against
permission.
unsafe practices.
• Yokogawa makes no warranty of any kind with
regard to this manual, including, but not limited to,
implied warranty of merchantability and fitness for a
particular purpose. IMPORTANT
• If any question arises or errors are found, or if any Indicates that operating the hardware or software
information is missing from this manual, please in this manner may damage it or lead to system
inform the nearest Yokogawa sales office. failure.
• The specifications covered by this manual are
limited to those for the standard type under the
specified model number break-down and do not
cover custom-made instruments. NOTE
• Please note that changes in the specifications, Draws attention to information essential for
construction, or component parts of the instrument understanding the operation and features.
may not immediately be reflected in this manual at
the time of change, provided that postponement of
revisions will not cause difficulty to the user from a Direct current
functional or performance standpoint.
• Yokogawa assumes no responsibilities for this 1.1 For Safe Use of Product
product except as stated in the warranty.
For the protection and safety of the operator and the
• If the customer or any third party is harmed by the instrument or the system including the instrument,
use of this product, Yokogawa assumes no responsi- please be sure to follow the instructions on safety
bility for any such harm owing to any defects in the described in this manual when handling this instru-
product which were not predictable, or for any ment. In case the instrument is handled in contradiction
indirect damages. to these instructions, Yokogawa does not guarantee
safety. Please give your attention to the followings.

NOTE (a) Installation


TM • The instrument must be installed by an expert
For FOUNDATION Fieldbus and HART protocol
versions, please refer to IM 01C22T02-01E and engineer or a skilled personnel. The procedures
IM 01C22T01-01E respectively, in addition to described about INSTALLATION are not permitted
this manual. for operators.

1-1 IM 01C22D01-01E
1. INTRODUCTION

• In case of high process temperature, care should be (f) Modification


taken not to burn yourself because the surface of • Yokogawa will not be liable for malfunctions or
body and case reaches a high temperature. damage resulting from any modification made to this
instrument by the customer.
• The instrument installed in the process is under
pressure. Never loosen the process connector bolts to
avoid the dangerous spouting of process fluid. 1.2 Warranty
• During draining condensate from the pressure- • The warranty shall cover the period noted on the
detector section, take appropriate care to avoid quotation presented to the purchaser at the time of
contact with the skin, eyes or body, or inhalation of purchase. Problems occurred during the warranty
vapors, if the accumulated process fluid may be period shall basically be repaired free of charge.
toxic or otherwise harmful. • In case of problems, the customer should contact the
• When removing the instrument from hazardous Yokogawa representative from which the instrument
processes, avoid contact with the fluid and the was purchased, or the nearest Yokogawa office.
interior of the meter. • If a problem arises with this instrument, please
• All installation shall comply with local installation inform us of the nature of the problem and the
requirement and local electrical code. circumstances under which it developed, including
the model specification and serial number. Any
(b) Wiring diagrams, data and other information you can
• The instrument must be installed by an expert include in your communication will also be helpful.
engineer or a skilled personnel. The procedures • Responsible party for repair cost for the problems
described about WIRING are not permitted for shall be determined by Yokogawa based on our
operators. investigation.
• Please confirm that voltages between the power • The Purchaser shall bear the responsibility for repair
supply and the instrument before connecting the costs, even during the warranty period, if the
power cables and that the cables are not powered malfunction is due to:
before connecting.
- Improper and/or inadequate maintenance by the
(c) Operation purchaser.
• Wait 10 min. after power is turned off, before - Failure or damage due to improper handling, use or
opening the covers. storage which is out of design conditions.
- Use of the product in question in a location not
(d) Maintenance conforming to the standards specified by
• Please do not carry out except being written to a Yokogawa, or due to improper maintenance of the
maintenance descriptions. When these procedures installation location.
are needed, please contact nearest YOKOGAWA - Failure or damage due to modification or repair by
office. any party except Yokogawa or an approved
representative of Yokogawa.
• Care should be taken to prevent the build up of drift,
- Malfunction or damage from improper relocation
dust or other material on the display glass and
of the product in question after delivery.
name plate. In case of its maintenance, soft and dry
- Reason of force majeure such as fires, earthquakes,
cloth is used.
storms/floods, thunder/lightening, or other natural
(e) Explosion Protected Type Instrument disasters, or disturbances, riots, warfare, or
• Users of explosion proof instruments should refer radioactive contamination.
first to section 2.9 (Installation of an Explosion
Protected Instrument) of this manual.
• The use of this instrument is restricted to those who
have received appropriate training in the device.
• Take care not to create sparks when accessing the
instrument or peripheral devices in a hazardous
location.

1-2 IM 01C22D01-01E
1. INTRODUCTION

1.3 ATEX Documentation SF


This procedure is only applicable to the countries in
European Union. Kaikkien ATEX Ex -tyyppisten tuotteiden käyttöhjeet
ovat saatavilla englannin-, saksan- ja ranskankielisinä.
Mikäli tarvitsette Ex -tyyppisten tuotteiden ohjeita
GB omalla paikallisella kielellännne, ottakaa yhteyttä
lähimpään Yokogawa-toimistoon tai -edustajaan.
All instruction manuals for ATEX Ex related products
are available in English, German and French. Should
you require Ex related instructions in your local P
language, you are to contact your nearest Yokogawa
office or representative. Todos os manuais de instruções referentes aos produtos
Ex da ATEX estão disponíveis em Inglês, Alemão e
Francês. Se necessitar de instruções na sua língua
DK relacionadas com produtos Ex, deverá entrar em
contacto com a delegação mais próxima ou com um
Alle brugervejledninger for produkter relateret til representante da Yokogawa.
ATEX Ex er tilgængelige på engelsk, tysk og fransk.
Skulle De ønske yderligere oplysninger om håndtering
af Ex produkter på eget sprog, kan De rette F
henvendelse herom til den nærmeste Yokogawa
afdeling eller forhandler. Tous les manuels d’instruction des produits ATEX Ex
sont disponibles en langue anglaise, allemande et
française. Si vous nécessitez des instructions relatives
I aux produits Ex dans votre langue, veuillez bien
contacter votre représentant Yokogawa le plus proche.
Tutti i manuali operativi di prodotti ATEX
contrassegnati con Ex sono disponibili in inglese,
tedesco e francese. Se si desidera ricevere i manuali D
operativi di prodotti Ex in lingua locale, mettersi in
contatto con l’ufficio Yokogawa più vicino o con un Alle Betriebsanleitungen für ATEX Ex bezogene
rappresentante. Produkte stehen in den Sprachen Englisch, Deutsch
und Französisch zur Verfügung. Sollten Sie die
Betriebsanleitungen für Ex-Produkte in Ihrer
E Landessprache benötigen, setzen Sie sich bitte mit
Ihrem örtlichen Yokogawa-Vertreter in Verbindung.
Todos los manuales de instrucciones para los productos
antiexplosivos de ATEX están disponibles en inglés,
alemán y francés. Si desea solicitar las instrucciones de S
estos artículos antiexplosivos en su idioma local,
deberá ponerse en contacto con la oficina o el Alla instruktionsböcker för ATEX Ex (explosionssäkra)
representante de Yokogawa más cercano. produkter är tillgängliga på engelska, tyska och
franska. Om Ni behöver instruktioner för dessa
explosionssäkra produkter på annat språk, skall Ni
NL kontakta närmaste Yokogawakontor eller representant.

Alle handleidingen voor producten die te maken


hebben met ATEX explosiebeveiliging (Ex) zijn GR
verkrijgbaar in het Engels, Duits en Frans. Neem,
indien u aanwijzingen op het gebied van             ATEX Ex
explosiebeveiliging nodig hebt in uw eigen taal, contact    ,     .
op met de dichtstbijzijnde vestiging van Yokogawa of           Ex 
met een vertegenwoordiger.            
    Yokogawa      .

1-3 IM 01C22D01-01E
1. INTRODUCTION

SK PL

CZ

SLO

LT H

BG
LV

EST RO

1-4 IM 01C22D01-01E
2. HANDLING CAUTIONS

2. HANDLING CAUTIONS
This chapter describes important cautions regarding
how to handle the transmitter. Read carefully before
using the transmitter.
The EJA Series pressure transmitters are thoroughly : Refer to USER'S MANUAL

tested at the factory before shipment. When the F0202.EPS

transmitter is delivered, visually check them to make Figure 2.2 Name Plate Example of TIIS Flameproof Type
sure that no damage occurred during shipment.
Also check that all transmitter mounting hardware 2.2 Unpacking
shown in Figure 2.1 is included. If the transmitter was When moving the transmitter to the installation site,
ordered without the mounting bracket or without the keep it in its original packaging. Then, unpack the
process connector, the transmitter mounting hardware transmitter there to avoid damage on the way.
is not included. After checking the transmitter, repack
it in the way it was delivered until installation.
2.3 Storage
Bolt
Process connector The following precautions must be observed when
Process connector storing the instrument, especially for a long period.
Gasket
U-bolt (a) Select a storage area which meets the following
conditions:
• It is not exposed to rain or water.
• It suffers minimum vibration and shock.
• It has an ambient temperature and relative
humidity within the following ranges.
Mounting bracket Ambient temperature:
(L type)
–40 to 85°C without integral indicator
U-bolt nut Transmitter mounting bolt
–30 to 80°C with integral indicator
Relative humidity:
5% to 100% R.H. (at 40°C)
Preferred temperature and humidity:
approx. 25°C and 65% R.H.
(b) When storing the transmitter, repack it as nearly
as possible to the way it was packed when
delivered from the factory.
(c) If storing a transmitter that has been used,
Mounting bracket thoroughly clean the chambers inside the cover
(Flat type)
F0201.EPS flanges, so that no measured fluid remains in it.
Figure 2.1 Transmitter Mounting Hardware Also make sure before storing that the pressure-
detector and transmitter section are securely
2.1 Model and Specifications mounted.
Check
2.4 Selecting the Installation
The model name and specifications are indicated on the
name plate attached to the case. If the reverse operat- Location
ing mode was ordered (reverse signal), ‘REVERSE’ The transmitter is designed to withstand severe
will be inscribed in field *1. environmental conditions. However, to ensure stable
and accurate operation for years, observe the follow-
ing precautions when selecting an installation
location.

2-1 IM 01C22D01-01E
2. HANDLING CAUTIONS

(a) Ambient Temperature 2.7 Restrictions on Use of Radio


Avoid locations subject to wide temperature
variations or a significant temperature gradient. If Transceiver
the location is exposed to radiant heat from plant
equipments, provide adequate thermal insulation
IMPORTANT
and/or ventilation.
(b) Ambient Atmosphere Although the transmitter has been designed to
Avoid installing the transmitter in a corrosive resist high frequency electrical noise, if a radio
atmosphere. If the transmitter must be installed in a transceiver is used near the transmitter or its
corrosive atmosphere, there must be adequate external wiring, the transmitter may be affected
ventilation as well as measures to prevent intrusion by high frequency noise pickup. To test for such
or stagnation of rain water in conduits. effects, bring the transceiver in use slowly from a
(c) Shock and Vibration distance of several meters from the transmitter,
Select an installation site suffering minimum shock and observe the measurement loop for noise
and vibration (although the transmitter is designed effects. Thereafter, always use the transceiver
to be relatively resistant to shock and vibration). outside the area affected by noise.
(d) Installation of Explosion-protected Transmitters
Explosion-protected transmitters can be installed in
hazardous areas according to the types of gases for 2.8 Insulation Resistance and
which they are certified. See Subsection 2.9
“Installation of Explosion Protected Type Transmit- Dielectric Strength Test
ters.” Since the transmitter has undergone insulation resis-
tance and dielectric strength tests at the factory before
2.5 Pressure Connection shipment, normally these tests are not required.
However, if required, observe the following precau-
WARNING tions in the test procedures.
(a) Do not perform such tests more frequently than is
• Instrument installed in the process is under
absolutely necessary. Even test voltages that do not
pressure. Never loosen the process connector
cause visible damage to the insulation may degrade
bolts to avoid the dangerous spouting of
the insulation and reduce safety margins.
process fluid.
(b) Never apply a voltage exceeding 500 V DC (100 V
• During draining condensate from the pressure-
DC with an internal lightning protector) for the
detector section, take appropriate care to avoid
insulation resistance test, nor a voltage exceeding
contact with the skin, eyes or body, or inhala-
500 V AC (100 V AC with an internal lightning
tion of vapors, if the accumulated process fluid
protector) for the dielectric strength test.
may be toxic or otherwise harmful.
(c) Before conducting these tests, disconnect all signal
lines from the transmitter terminals. Perform the
The following precautions must be observed in order to tests in the following procedure:
safely operate the transmitter under pressure.
• Insulation Resistance Test
(a) Make sure that the two process connector bolts are 1) Short-circuit the + and – SUPPLY terminals in the
tightened firmly. terminal box.
(b) Make sure that there are no leaks in the impulse 2) Turn OFF the insulation tester. Then connect the
piping. insulation tester plus (+) lead wire to the shorted
(c) Never apply a pressure higher than the specified SUPPLY terminals and the minus (–) leadwire to
maximum working pressure. the grounding terminal.
3) Turn ON the insulation tester power and measure
2.6 Waterproofing of Cable the insulation resistance. The voltage should be
applied short as possible to verify that the insula-
Conduit Connections tion resistance is at least 20 MΩ.
Apply a non-hardening sealant to the threads to 4) After completing the test and being very careful not
waterproof the transmitter cable conduit connections. to touch exposed conductors disconnect the
(See Figure 6.4.2a, 6.4.2b and 6.4.2d.) insulation tester and connect a 100 kΩ resistor
between the grounding terminal and the short-

2-2 IM 01C22D01-01E
2. HANDLING CAUTIONS

circuiting SUPPLY terminals. Leave this resistor


WARNING
connected at least one second to discharge any
static potential. Do not touch the terminals while it To preserve the safety of explosionproof equip-
is discharging. ment requires great care during mounting,
• Dielectric Strength Test wiring, and piping. Safety requirements also
1) Short-circuit the + and – SUPPLY terminals in the place restrictions on maintenance and repair
terminal box. activities. Please read the following sections very
2) Turn OFF the dielectric strength tester. Then carefully.
connect the tester between the shorted SUPPLY
terminals and the grounding terminal. Be sure to
connect the grounding lead of the dielectric strength 2.9.1 FM Approval
tester to the ground terminal.
3) Set the current limit on the dielectric strength tester a. FM Intrinsically Safe Type
to 10 mA, then turn ON the power and gradually Caution for FM intrinsically safe type. (Following
increase the test voltage from ‘0’ to the specified contents refer “DOC. No. IFM012-A12 P.1 and 2.”)
voltage. Note 1. Model EJA Series pressure transmitters
4) When the specified voltage is reached, hold it for with optional code /FS1 are applicable for
one minute. use in hazardous locations.
5) After completing this test, slowly decrease the • Applicable Standard: FM3600, FM3610, FM3611,
voltage to avoid any voltage surges. FM3810, ANSI/NEMA250
• Intrinsically Safe for Class I, Division 1, Groups A,
2.9 Installation of Explosion B, C & D. Class II, Division 1, Groups E, F & G
Protected Type and Class III, Division 1 Hazardous Locations.
• Nonincendive for Class I, Division 2, Groups A, B,
In this section, further requirements and differences C & D. Class II, Division 2, Groups E, F & G and
and for explosionproof type instrument are described. Class III, Division 1 Hazardous Locations.
For explosionproof type instrument, the description in • Outdoor hazardous locations, NEMA 4X.
this chapter is prior to other description in this users • Temperature Class: T4
manual. • Ambient temperature: –40 to 60°C
For the intrinsically safe equipment and explosionproof Note 2. Entity Parameters
equipment, in case the instrument is not restored to its • Intrinsically Safe Apparatus Parameters
original condition after any repair or modification [Groups A, B, C, D, E, F and G]
undertaken by the customer, intrinsically safe Vmax = 30 V Ci = 22.5 nF
construction or explosionproof construction is damaged Imax = 165 mA Li = 730 µH
and may cause dangerous condition. Please contact Pmax = 0.9 W
Yokogawa for any repair or modification required to * Associated Apparatus Parameters
the instrument. (FM approved barriers)
Voc ≤ 30 V Ca > 22.5 nF
NOTE Isc ≤ 165 mA La > 730 µH
Pmax ≤ 0.9W
For FOUNDATION Fieldbus explosion protected • Intrinsically Safe Apparatus Parameters
type, please refer to IM 01C22T02-01E. [Groups C, D, E, F and G]
Vmax = 30 V Ci = 22.5 nF
Imax = 225 mA Li = 730 µH
CAUTION Pmax = 0.9 W
* Associated Apparatus Parameters
This instrument is tested and certified as intrinsi-
(FM approved barriers)
cally safe type or explosionproof type. Please
Voc ≤ 30 V Ca > 22.5 nF
note that the construction of the instrument,
Isc ≤ 225 mA La > 730 µH
installation, external wiring, maintenance or
Pmax ≤ 0.9 W
repair is strictly restricted, and non-observance
or negligence of this restriction would result in
dangerous condition.

2-3 IM 01C22D01-01E
2. HANDLING CAUTIONS

• Entity Installation Requirements b. FM Explosionproof Type


Vmax ≥ Voc or Vt, Imax ≥ Isc or It, Caution for FM explosionproof type.
Pmax (IS Apparatus) ≥ Pmax (Barrier) Note 1. Model EJA Series differential, gauge,
Ca ≥ Ci + Ccable, La ≥ Li + Lcable and absolute pressure transmitters with
Note 3. Installation optional code /FF1 are applicable for
• Barrier must be installed in an enclosure that meets use in hazardous locations.
the requirements of ANSI/ISA S82.01. • Applicable Standard: FM3600, FM3615, FM3810,
• Control equipment connected to barrier must not use ANSI/NEMA250
or generate more than 250 V rms or V dc. • Explosionproof for Class I, Division 1, Groups B,
• Installation should be in accordance with ANSI/ISA C and D.
RP12.6 “Installation of Intrinsically Safe Systems for • Dust-ignitionproof for Class II/III, Division 1,
Hazardous (Classified) Locations” and the National Groups E, F and G.
Electric Code (ANSI/NFPA 70). • Outdoor hazardous locations, NEMA 4X.
• The configuration of associated apparatus must be • Temperature Class: T6
FMRC Approved. • Ambient Temperature: –40 to 60°C
• Dust-tight conduit seal must be used when installed • Supply Voltage: 42 V dc max.
in a Class II, III, Group E, F and G environments. • Output signal: 4 to 20 mA
• Associated apparatus manufacturer’s installation Note 2. Wiring
drawing must be followed when installing this • All wiring shall comply with National Electrical
apparatus. Code ANSI/NEPA70 and Local Electrical Codes.
• The maximum power delivered from the barrier • When installed in Division 1, “FACTORY
must not exceed 0.9 W. SEALED, CONDUIT SEAL NOT REQUIRED.”
• Note a warning label worded “SUBSTITUTION OF Note 3. Operation
COMPONENTS MAY IMPAIR INTRINSIC • Keep the “CAUTION” nameplate attached to the
SAFETY,” and “INSTALL IN ACCORDANCE transmitter.
WITH DOC. No. IFM012-A12 P.1 and 2.” CAUTION: OPEN CIRCUIT BEFORE REMOV-
Note 4. Maintenance and Repair ING COVER. SEAL ALL CONDUITS WITHIN
• The instrument modification or parts replacement by 18 INCHES. WHEN INSTALLED IN DIV.1,
other than authorized representative of Yokogawa “FACTORY SEALED, CONDUIT SEAL NOT
Electric Corporation is prohibited and will void REQUIRED.” INSTALL IN ACCORDANCE
Factory Mutual Intrinsically safe and Nonincendive WITH THE INSTRUCTION MANUAL IM 1C22.
Approval. • Take care not to generate mechanical sparking
[Intrinsically Safe] when accessing to the instrument and peripheral
Hazardous Location Nonhazardous Location devices in a hazardous location.
Class I, II, III, Division 1,
Note 4. Maintenance and Repair
Groups A, B, C, D, E, F, G General • The instrument modification or parts replacement
EJA Series Pressure Purpose by other than authorized representative of
Transmitters Safety Barrier Equipment Yokogawa Electric Corporation is prohibited and
+ + + +
will void Factory Mutual Explosionproof Ap-
Supply – – – –
proval.
c. FM Intrinsically Safe Type/FM
Explosionproof Type
[Nonincendive] Model EJA Series pressure transmitters with
Hazardous Location Nonhazardous Location optional code /FU1 can be selected the type
Class I, II, Division 2, of protection (FM Intrinsically Safe or FM
Groups A, B, C, D, E, F, G
Explosionproof) for use in hazardous loca-
Class III, Division 1. General
Purpose tions.
EJA Series Pressure
Transmitters Equipment Note 1. For the installation of this transmitter,
+ + once a particular type of protection is
Supply – – selected, any other type of protection
Not Use cannot be used. The installation must be
Safety Barrier
F0203.EPS in accordance with the description about
the type of protection in this instruction
manual.

2-4 IM 01C22D01-01E
2. HANDLING CAUTIONS

Note 2. In order to avoid confusion, unnecessary [Intrinsically Safe]


marking is crossed out on the label other Hazardous Location Nonhazardous Location
than the selected type of protection when Class I, II, III, Division 1,
the transmitter is installed. Groups A, B, C, D, E, F, G General
EJA Series Pressure Purpose
Transmitters Safety Barrier Equipment
2.9.2 CSA Certification
+ + + +

a. CSA Intrinsically Safe Type Supply – – – –

Caution for CSA Intrinsically safe type. (Following


contents refer to “DOC No. ICS003-A12 P.1-1 and F0204-1.EPS

P.1-2.”) [Nonincendive]
Note 1. Model EJA Series differential, gauge, and Hazardous Location Nonhazardous Location
absolute pressure transmitters with Class I, II, Division 2,
optional code /CS1 are applicable for use Groups A, B, C, D, E, F, G
in hazardous locations Class III General
EJA Series Pressure Purpose
Certificate: 1053843 Equipment
Transmitters
• Applicable Standard: C22.2 No.0, No.0.4, No.25, + +
No.30, No.94, No.142, No.157, No.213 Supply – –
• Intrinsically Safe for Class I, Division 1, Groups A, Not Use
B, C & D. Class II, Division 1, Groups E, F & G Safety Barrier
F0204-2.EPS

and Class III, Division 1 Hazardous Locations.


• Nonincendive for Class I, Division 2, Groups A, B, b. CSA Explosionproof Type
C & D, Class II, Division 2, Groups F & G, and Caution for CSA explosionproof type.
Class III, Hazardous Locations. (not use Safety
Note 1. Model EJA Series differential, gauge, and
Barrier)
absolute pressure transmitters with
• Encl. “Type 4X”
optional code /CF1 are applicable for use
• Temperature Class: T4
in hazardous locations:
• Ambient temperature: –40 to 60°C
Certificate: 1089598
• Process Temperature: 120°C max.
• Applicable Standard: C22.2 No.0, No.0.4, No.25,
Note 2. Entity Parameters
No.30, No.94, No.142
• Intrinsically safe ratings are as follows:
• Explosionproof for Class I, Division 1, Groups B,
Maximum Input Voltage (Vmax) = 30 V
C and D.
Maximum Input Current (Imax) = 165 mA
• Dust-ignitionproof for Class II/III, Division 1,
Maximum Input Power (Pmax) = 0.9 W
Groups E, F and G.
Maximum Internal Capacitance (Ci) = 22.5 nF
• Encl “Type 4X”
Maximum Internal Inductance (Li) = 730 µH
• Temperature Class: T6, T5, and T4
* Associated apparatus (CSA certified barriers)
• Process Temperature: 85°C (T6), 100°C (T5), and
Maximum output voltage (Voc) ≤ 30 V
120°C (T4)
Maximum output current (Isc) ≤ 165 mA
• Ambient Temperature: –40 to 80°C
Maximum output power (Pmax) ≤ 0.9 W
• Supply Voltage: 42 V dc max.
Note 3. Installation
• Output Signal: 4 to 20 mA
• All wiring shall comply with Canadian Electrical
Note 2. Wiring
Code Part I and Local Electrical Codes.
• All wiring shall comply with Canadian Electrical
• The instrument modification or parts replacement
Code Part I and Local Electrical Codes.
by other than authorized representative of
• In hazardous location, wiring shall be in conduit as
Yokogawa Electric Corporation and Yokogawa
shown in the figure.
Corporation of America is prohibited and will void
CAUTION: SEAL ALL CONDUITS
Canadian Standards Intrinsically safe and
WITHIN 50 cm OF THE ENCLOSURE.
nonincendive Certification.
UN SCELLEMENT DOIT ÊTRE
INSTALLÉ À MOINS DE 50 cm DU
BÎTIER.
• When installed in Division 2, “SEALS NOT
REQUIRED.”

2-5 IM 01C22D01-01E
2. HANDLING CAUTIONS

Note 3. Operation 2.9.3 IECEx Certification


• Keep the “CAUTION” label attached to the
Model EJA Series differential, gauge, and
transmitter.
absolute pressure transmitters with
CAUTION: OPEN CIRCUIT BEFORE
optional code /SU2 can be selected the type of
REMOVING COVER.
protection (IECEx Intrinsically Safe/type n or
OUVRIR LE CIRCUIT AVANT
flameproof) for use in hazardous locations.
D´NLEVER LE COUVERCLE.
Note 1. For the installation of this transmitter,
• Take care not to generate mechanical sparking
once a particular type of protection is
when accessing to the instrument and peripheral
selected, any other type of protection
devices in a hazardous location.
cannot be used. The installation must be
Note 4. Maintenance and Repair
in accordance with the description about
• The instrument modification or parts replacement
the type of protection in this instruction
by other than authorized representative of
manual.
Yokogawa Electric Corporation and Yokogawa
Note 2. In order to avoid confusion, unnecessary
Corporation of America is prohibited and will void
marking is crossed out on the label other
Canadian Standards Explosionproof Certification.
than the selected type of protection when
Non-Hazardous Hazardous Locations Division 1 the transmitter is installed.
Locations
Non-hazardous a. IECEx Intrinsically Safe Type / type n
Location Caution for IECEx Intrinsically safe and type n.
Equipment 50 cm Max.
Note 1. Model EJA Series differential, gauge, and
absolute pressure transmitters with
optional code /SU2 are applicable for use
42 V DC Max. Conduit
4 to 20 mA DC Sealing Fitting in hazardous locations
Signal • No. IECEx KEM 06.0007X
EJA Series
• Applicable Standard: IEC 60079-0:2004,
Non-Hazardous Hazardous Locations Division 2
Locations
IEC 60079-11:1999, IEC 60079-15:2005,
IEC 60079-26:2004
Non-hazardous
Location • Type of Protection and Marking Code:
Equipment Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature :–40 to 60°C
• Max. Process Temp.: 120°C
42 V DC Max. • Enclosure: IP67
4 to 20 mA DC Sealing Fitting
Signal Note 2. Entity Parameters
EJA Series
F0205.EPS
• Intrinsically safe ratings are as follows:
Maximum Input Voltage (Ui) = 30 V
c. CSA Intrinsically Safe Type/CSA
Maximum Input Current (Ii) = 165 mA
Explosionproof Type
Maximum Input Power (Pi) = 0.9 W
Model EJA Series pressure transmitters with
Maximum Internal Capacitance (Ci) = 22.5 nF
optional code /CU1 can be selected the type of
Maximum Internal Inductance (Li) = 730 µH
protection (CSA Intrinsically Safe or CSA
• Type "n" ratings are as follows:
Explosionproof) for use in hazardous locations.
Maximum Input Voltage (Ui) = 30 V
Note 1. For the installation of this transmitter,
Maximum Internal Capacitance (Ci) = 22.5 nF
once a particular type of protection is
Maximum Internal Inductance (Li) = 730 µH
selected, any other type of protection
• Installation Requirements
cannot be used. The installation must be
Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
in accordance with the description about
Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
the type of protection in this instruction
Uo, Io, Po, Co, and Lo are parameters of
manual.
barrier.
Note 2. In order to avoid confusion, unnecessary
Note 3. Installation
marking is crossed out on the label other
• In any safety barreir used output current must be
than the selected type of protection when
limited by a resistor 'R' such that Io=Uo/R.
the transmitter is installed.
• The safety barrier must be IECEx certified.

2-6 IM 01C22D01-01E
2. HANDLING CAUTIONS

• Input voltage of the safety barrier must be less [type n]


than 250 Vrms/Vdc. Hazardous Location Nonhazardous Location
• The instrument modification or parts replacement Group IIC, Zone 2
by other than authorized representative of
Yokogawa Electric Corporation and will void EJA Series Pressure IECEx Certified
Transmitters Equipment [nL]
IECEx Intrinsically safe and type n certification.
+ +
• The cable entry devices and blanking elements for
Supply – –
type n shall be of a certified type providing a level
Not Use
of ingress protection of at least IP54, suitable for Safety Barrier
the conditions of use and correctly installed. F0215.EPS

• Electrical Connection: b. IECEx Flameproof Type


The type of electrical connection is stamped near
Caution for IECEx flameproof type.
the electrical connection port according to the
Note 1. Model EJA Series differential, gauge, and
following marking.
absolute pressure transmitters with
optional code /SU2 are applicable for use
in hazardous locations:
• No. IECEx KEM 06.0005
T0202.EPS
• Applicable Standard: IEC60079-0:2004,
IEC60079-1:2003
• Type of Protection and Marking Code:
Ex d IIC T6...T4
Location of the marking • Enclosure: IP67
• Maximum Process Temperature: 120°C (T4),
F0213.EPS
100°C (T5), 85°C (T6)
Note 4. Operation • Ambient Temperature: –40 to 75°C (T4), –40 to
• WARNING: 80°C (T5), –40 to 75°C (T6)
WHEN AMBIENT TEMPERATURE ≥ 55°C, • Supply Voltage: 42 V dc max.
USE THE HEAT-RESISTING CABLES ≥ 90°C. • Output Signal: 4 to 20 mA dc
Note 5. Special Conditions for Safe Use Note 2. Wiring
• WARNING: • In hazardous locations, the cable entry devices shall
IN THE CASE WHERE THE ENCLOSURE OF be of a certified flameproof type, suitable for the
THE PRESSURE TRANSMITTER IS MADE OF conditions of use and correctly installed.
ALUMINUM, IF IT IS MOUNTED IN AN AREA • Unused apertures shall be closed with suitable
WHERE THE USE OF ZONE 0 IS REQUIRED, flameproof certified blanking elements. (The plug
IT MUST BE INSTALLED SUCH, THAT, EVEN attached is certificated as the flame proof IP67 as a
IN THE EVENT OF RARE INCIDENTS, IGNI- part of this apparatus.)
TION SOURCES DUE TO IMPACT AND • In case of ANSI 1/2 NPT plug, ANSI hexagonal
FRICTION SPARKS ARE EXCLUDED. wrench should be applied to screw in.
[Intrinsically Safe] Note 3. Operation
Hazardous Location Nonhazardous Location • WARNING:
Group I/IIC, Zone 0 AFTER DE-ENERGIZING, DELAY 10 MINUTES
BEFORE OPENING.
General • WARNING:
EJA Series Pressure IECEx certified Purpose WHEN AMBIENT TEMPERATURE ≥ 70°C,
Transmitters Safety Barrier Equipment
USE THE HEAT-RESISTING CABLES ≥ 90°C.
+ + + +
• Take care not to generate mechanical sparking
Supply – – – –
when accessing to the instrument and peripheral
devices in a hazardous location.
F0214.EPS Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void IECEx Certification.

2-7 IM 01C22D01-01E
2. HANDLING CAUTIONS

2.9.4 CENELEC ATEX (KEMA) [Installation Diagram]


Certification Hazardous Location Nonhazardous Location

(1) Technical Data


Transmitter
a. CENELEC ATEX (KEMA) Intrinsically Safe + +
Type Supply Safety Barrier *1
– –
Caution for CENELEC ATEX (KEMA)
Intrinsically safe type.
Note 1. Model EJA Series differential, gauge, and
absolute pressure transmitters with F0208.EPS

optional code /KS2 for potentially explo- *1: In any safety barriers used the output current must be limited
by a resistor “R” such that Imaxout-Uz/R.
sive atmospheres:
• No. KEMA 02ATEX1030 X
• Applicable Standard: EN50014:1997, b. CENELEC ATEX (KEMA) Flameproof Type
EN50020:1994, EN50284:1999 Caution for CENELEC ATEX (KEMA) flameproof
• Type of Protection and Marking code: type.
EEx ia IIC T4 Note 1. Model EJA Series differential, gauge, and
• Temperature Class: T4 absolute pressure transmitters with
• Enclosure: IP67 optional code /KF2 for potentially explo-
• Process Temperature: 120°C max. sive atmospheres:
• Ambient Temperature: –40 to 60°C • No. KEMA 02ATEX2148
Note 2. Electrical Data • Applicable Standard: EN50014:1997,
• In type of explosion protection intrinsic safety EEx EN50018:2000
ia IIC only for connection to a certified intrinsically • Type of Protection and Marking Code: EEx d IIC
safe circuit with following maximum values: T6···T4
Ui = 30 V • Temperature Class: T6, T5, and T4
Ii = 165 mA • Enclosure: IP67
Pi = 0.9 W • Maximum Process Temperature:
Effective internal capacitance; Ci = 22.5 nF 85°C (T6), 100°C (T5), and 120°C (T4)
Effective internal inductance; Li = 730 µH • Ambient Temperature: T4 and T6; –40 to 75°C,
Note 3. Installation T5; –40 to 80°C
• All wiring shall comply with local installation Note 2. Electrical Data
requirements. (Refer to the installation diagram) • Supply voltage: 42 V dc max.
Note 4. Maintenance and Repair • Output signal: 4 to 20 mA
• The instrument modification or parts replacement Note 3. Installation
by other than authorized representative of • All wiring shall comply with local installation
Yokogawa Electric Corporation is prohibited and requirement.
will void KEMA Intrinsically safe Certification. • The cable entry devices shall be of a certified
Note 5. Special Conditions for Safe Use flameproof type, suitable for the conditions of use.
• In the case where the enclosure of the Pressure Note 4. Operation
Transmitter is made of aluminium, if it is mounted • Keep the “CAUTION” label to the transmitter.
in an area where the use of category 1 G apparatus CAUTION: AFTER DE-ENERGIZING,
is required, it must be installed such, that, even in DELAY 10 MINUTES BEFORE
the event of rare incidents, ignition sources due to OPENING. WHEN THE AMBIENT
impact and friction sparks are excluded. TEMP.70°C, USE HEAT-RESISTING
CABLES90°C.
• Take care not to generate mechanical sparking
when accessing to the instrument and peripheral
devices in a hazardous location.
Note 5. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void KEMA Flameproof Certification.

2-8 IM 01C22D01-01E
2. HANDLING CAUTIONS

c. CENELEC ATEX (KEMA) Intrinsically Safe • The instrument modification or parts replacement
Type/CENELEC ATEX (KEMA) Flameproof by other than authorized representative of
Type/CENELEC ATEX Type n
Yokogawa Electric Corporation is prohibited and
Model EJA Series pressure transmitters with will void Type of Protection “n”.
optional code /KU2 can be selected the type of
[Installation Diagram]
protection CENELEC ATEX (KEMA) Intrinsi-
cally Safe, Flameproof or CENELEC ATEX Hazardous Location Nonhazardous Location
(Zone 2 only)
Type n for use in hazardous locations. Transmitter
Note 1. For the installation of this transmitter,
+ +
once a particular type of protection is Supply Power Supply
– –
selected, any other type of protection
cannot be used. The installation must be
in accordance with the description about
the type of protection in this user’s F0209.EPS
Ratings of the Power Supply as follows;
manual. Maximum Voltage: 30 V
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when • CENELEC ATEX Type of Protection “Dust”
the transmitter is installed. • Applicable Standard: EN50281-1-1:1997
• Type of Protection and Marking Code: II 1D
• CENELEC ATEX Type of Protection “n” • Maximum surface temperature:
T65°C (Tamb.: 40°C), T85°C (Tamb.: 60°C), and
WARNING T105°C (Tamb.: 80°C)
Note 1. Installation instructions
When using a power supply not having a non-
The cable entry devices and blanking
incendive circuit, please pay attention not to
elements shall be of a certificated type
ignite in the surrounding flammable atmosphere.
providing a level of ingress protection of
In such a case, we recommend using wiring
at least IP6x, suitable for the conditions
metal conduit in order to prevent the ignition.
of use and correctly installed.
• Applicable Standard: EN60079-15
• Referential Standard: IEC60079-0, IEC60079-11 (2) Electrical Connection
• Type of Protection and Marking Code: The type of electrical connection is stamped near
Ex nL IIC T4 the electrical connection port according to the
• Temperature Class: T4 following marking.
• Enclosure: IP67
• Process Temperature: 120°C max.
• Ambient Temperature: –40 to 60°C
Note 1. Electrical Data
Ui = 30 V
Effective internal capacitance; Ci = 22.5 nF
Effective internal inductance; Li = 730 µH
Note 2. Installation
Location of the marking
• All wiring shall comply with local installation
requirements. (refer to the installation diagram) F0200.EPS

Note 3. Maintenance and Repair

2-9 IM 01C22D01-01E
2. HANDLING CAUTIONS

(3) Installation (6) Name Plate


 Name plate
WARNING

• All wiring shall comply with local installation


requirement and local electrical code.
• There is no need of the conduit seal for both of
: Refer to USER'S MANUAL

Division 1 and Division 2 hazardous locations


because this product is sealed at factory.
 Tag plate for flameproof type
• In case of ANSI 1/2 NPT plug, ANSI hexagonal
wrench should be applied to screw in.

(4) Operation
 Tag plate for intrinsically safe type

WARNING

• OPEN CIRCUIT BEFORE REMOVING


COVER. INSTALL IN ACCORDANCE WITH
THIS USER’S MANUAL  Tag plate for type n protection
• Take care not to generate mechanical sparking
when access to the instrument and peripheral
devices in hazardous locations.

 Tag plate for flameproof, intrinsically safe type,


(5) Maintenance and Repair type n protection, and Dust

WARNING D T65⬚C (Tamb.: 40⬚C), T85⬚C (Tamb.: 60⬚C),


and T105⬚C (Tamb.: 80⬚C)

The instrument modification or parts replacement


F0298.EPS
by other than authorized Representative of
MODEL: Specified model code.
Yokogawa Electric Corporation is prohibited and
STYLE: Style code.
will void the certification.
SUFFIX: Specified suffix code.
SUPPLY: Supply voltage.
OUTPUT: Output signal.
MWP: Maximum working pressure.
CAL RNG: Specified calibration range.
DISP MODE: Specified display mode.
OUTPUT MODE: Specified output mode.
NO.: Serial number and year of production*1.
TOKYO 180-8750 JAPAN:
The manufacturer name and the
address*2.
*1: The third figure from the last shows the last one
figure of the year of production. For example, the
production year of the product engraved in “NO.”
column on the name plate as follows is 2001.

12A819857 132

The year 2001


*2: “180-8750” is a zip code which represents the
following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan

2-10 IM 01C22D01-01E
2. HANDLING CAUTIONS

2.9.5 TIIS Certification


CAUTION
a. TIIS Flameproof Type
When selecting cables for TIIS flameproof type
The model EJA Series pressure transmitter with
transmitters, determine the cables' maximum
optional code /JF3, which has obtained certification
allowable heat resistance depending on the
according to technical criteria for explosion-protected
process and ambient temperature condition on
construction of electric machinery and equipment
the transmitter as illustrated in Figure 2.4. Use
(Standards Notification No. 556 from the Japanese
cables having a maximum allowable heat
Ministry of Labor) conforming to IEC standards, is
resistance of at least 60°C for the transmitter in
designed for hazardous areas where inflammable gases
Region A and that of 75°C in Region B.
or vapors may be present. (This allows installation in
Division 1 and 2 areas) Region B
60
50
To preserve the safety of flameproof equipment 45
40
requires great care during mounting, wiring, and Ambient
piping. Safety requirements also place restrictions on Temperature 20
(C) Region A
maintenance and repair activities. Users absolutely
0
must read “Installation and Operating Precautions for
TIIS Flameproof Equipment” at the end of this 20
manual. 20 0 20 40 60 80 100 120
90
Process Temperature (C)
CAUTION F0211.EPS

Figure 2.4 Selecting Cables


(For TIIS flameproof type without integral indicator)

When the fill fluid near the sensor part moves b. TIIS Intrinsically Safe Type
from within, the instrument outputs a failure
The model EJA Series pressure transmitter with optional
signal either high or low of the specific signal. In
code /JS3, which has obtained certification according to
that case, generate the alarm to identify that the
technical criteria for explosionprotected construction of
failure signal is output since the event may
electric machinery and equipment (Standards
invalidate the flameproof approval.
Notification No.556 from the Japanese Ministry of
If the optional integral indicator is equipped, the
Labor) conforming to IEC standards, is designed for
indicator identifies the alarm on its display.
hazardous areas where explosive or inflammable gases
Therefore, no other alarm generation is neces-
or vapors may be present. (This allows installation in
sary.
Division 0, 1 and 2 areas)
Hazardous Location Nonhazardous Location
To preserve the safety of flameproof equipment requires
great care during mounting,wiring, and piping. Safety
4 to 20 mA DC 1 to 5 V DC
requirements also place restrictions on maintenance and
Power DCS repair activities. Users absolutely must read “Installation
Transmitter Display
Supply
and Operating Precautions for TIIS Intrinsically Safe
F0210.EPS
Equipment” at the end of this manual.
Figure 2.3 Example of using DCS (Distributed Control
System)

2-11 IM 01C22D01-01E
2. HANDLING CAUTIONS

CAUTION
2.10 EMC Conformity Standards
EN61326-1 Class A, Table 2 (For use in industrial
For using a safety-barrier with a pressure
locations)
transmitter, the safety-barrier must be certified as
a safety-barrier itself. EN61326-2-3
A safety-barrier must be used under the
following condition.
CAUTION
(1) Condition of the current and voltage limits
This instrument is a Class A product, and it is
Maximum output voltage(Uo) ≤ 28V
designed for use in the industrial environment.
Maximum output current(Io) ≤ 94.3mA
Please use this instrument in the industrial
Maximum output power (Po) ≤ 0.66W
environment only.
(2) Category and Group
Category ia
Group II C NOTE

(3) Relations between a maximum allowed YOKOGAWA recommends customer to apply


inductance and a field wiring inductance, the Metal Conduit Wiring or to use the twisted
between a maximum allowed capacitance pair Shield Cable for signal wiring to conform the
and a field wiring capacitance. requirement of EMC Regulation, when customer
installs the EJA Series Transmitters to the plant.
Lo ≥ Li + Lw
Co ≥ Ci + Cw
(Li = 730µH, Ci=11nF) 2.11 PED (Pressure Equipment
Lo = Maximum external inductance Directive)
Li = Maximum internal inductance EJA series of pressure transmitters are categorized as
Lw = Field wiring inductance pressure accessories of this directive 97/23/EC, which
Go = Maximum external capacitance corresponds to Article 3, Paragraph 3 of PED, denoted
Ci = Maximum internal capacitance as Sound Engineering Practice (SEP).
Cw = Field wiring capacitance

Hazardous Location Nonhazardous


Location
2.12 Low Voltage Directive
4 to 20 mA DC
Applicable standard : EN61010-1
Transmitter Safety Barrier
Lw, Cw (1) Pollution Degree 2
Li=730 µH Lo, Co
Ci=11 nF “Pollution degree” describes the degree to which a
F0212.EPS
Figure 2.5 Diagram for Connecting Safety Barrier solid, liquid, or gas which deteriorates dielectric
strength or surface resistivity is adhering. “ 2” applies
to normal indoor atmosphere. Normally, only non-
conductive pollution occurs. Occasionally, however,
temporary conductivity caused by condensation must
be expected.

(2) Installation Category I


“Overvoltage category (Installation category)” de-
scribes a number which defines a transient overvoltage
condition. It implies the regulattion for impulse
withstand voltage. “I” applies to electrical equipment
which is supplied from the circuit when appropriate
transient overvoltage control means (interfaces) are
provided.

2-12 IM 01C22D01-01E
3. COMPONENT NAMES

3. COMPONENT NAMES
Vertical impulse piping type
Process connection
Pressure-detector section

Process connector (Note 1) Horizontal impulse piping type


Cover External indicator
flange External indicator
conduit connection (Note 1)
conduit connection (Note 1)

Terminal box cover Conduit


connection

CPU assembly

Integral
indicator (Note 1) Conduit
Mounting screw connection Zero-
adjustment
screw
Transmitter section
Cover
Setting pin (CN4) flange
Range-setting
switch (Note 1)
(See Subsection 7.6)
Open to atmosphere
Amplifier Cover (∅5mm)
Setting pin (CN4) Burn - out Output at Process connection
position (Note 2) direction burn - out Process connector (Note 1)
H
110% or
HIGH higher
L
H
-5% or
LOW lower (Note3)
L
F0301.EPS

Note 1: See Subsection 10.2, “Model and Suffix Codes,” for


details.
Note 2: Insert the pin (CN4) as shown in the figure above to
set the burn-out direction. The pin is set to the H side
for delivery (unless option code /C1 is specified in the
order).
The setting can be confirmed by calling up parameter
D52 using the BRAIN TERMINAL. Refer to Subsection
8.3.3 (8).
Note 3 : If optional code /F1 is specified, output signal is
–2.5% or lower

Figure 3.1 Component Names

Table 3.1 Display Symbol


Display Symbol Meaning of Display Symbol
The output signal being zero-adjusted is increasing.
The output signal being zero-adjusted is decreasing.
%, Pa, kPa, MPa, kgf/cm2, gf/cm2, mbar, bar, atm,
mmHg, mmH2O, inH2O, inHg, ftH2O, psi, Torr Select one of these sixteen available engineering units for the display.
T0301.EPS

3-1 IM 01C22D01-01E
4. INSTALLATION

4. INSTALLATION

4.1 Precautions Vertical pipe mounting

Before installing the transmitter, read the cautionary


notes in Section 2.4, “Selecting the Installation
Location.” For additional information on the ambient Transmitter
conditions allowed at the installation location, refer to mounting bolt
Subsection 10.1 “Standard Specifications.”
U-bolt nut

Mounting bracket
IMPORTANT
U-bolt
50 mm(2-inch) pipe
• When welding piping during construction, take Horizontal pipe mounting
care not to allow welding currents to flow
through the transmitter.
• Do not step on this instrument after installation.
• For Model EJA430, the atmospheric opening is
Transmitter
located on the low pressure side cover flange. mounting bolt
The opening must not face upward. See
Subsection 10.4, “Dimensions, ” for the location
of the opening. U-bolt nut
Mounting bracket
50 mm(2-inch) pipe U-bolt F0401.EPS

4.2 Mounting Figure 4.2.1 Transmitter Mounting (Horizontal Impulse


Piping Type)
 The transmitter is shipped with the process connec-
Vertical pipe mounting
tion, according to the ordering specifications. To (Process connector upside)
change the orientation of the process connections,
refer to Section 4.3.
 The transmitter can be mounted on a nominal 50
mm (2-inch) pipe using the mounting bracket Mounting bracket
supplied, as shown in Figure 4.2.1 and 4.2.2. The
transmitter can be mounted on either a horizontal or U-bolt nut
a vertical pipe.
 When mounting the bracket on the transmitter, Transmitter
mounting bolt
tighten the (four) bolts that hold the transmitter with U-bolt
a torque of approximately 39 N·m {4kgf·m}. 50 mm(2-inch) pipe
Vertical pipe mounting
(Process connector downside)
Transmitter
mounting bolt
Mounting bracket

U-bolt nut

U-bolt

50 mm(2-inch) pipe
F0402.EPS

Figure 4.2.2 Transmitter Mounting (Vertical Impulse Piping


Type)

4-1 IM 01C22D01-01E
4. INSTALLATION

4.3 Changing the Process Con- 4.4 Rotating Transmitter Section


nection The DPharp transmitter section can be rotated in 90°
segments.
The transmitter is shipped with the process connection
specified at the time of ordering. To make a change 1) Remove the two Allen screws that fasten the
such as modifying the drain (vent) plug(s) attached to transmitter section and capsule assembly, using the
the upside of the cover flange on shipment to be Allen wrench.
attached to the downside follow the procedure below. 2) Rotate the transmitter section slowly in 90° seg-
ments.
To begin, use a wrench to slowly and gently unscrew
3) Tighten the two Allen screws to a torque of 5 N·m.
the drain (vent) plug(s). Then, remove and remount
them on the opposite side. Wrap sealing tape around
the drain (vent) plug threads (*1 in the figure below),
IMPORTANT
and apply a lubricant to the threads of the drain (vent)
screw(s) (*2 below) to screw it (them) in. To tighten Do not rotate the transmitter section more than
the drain (vent) plugs, apply a torque of 34 to 39N·m 180°.
{3.5 to 4 kgf·m}. Tighten the process connector bolts
uniformly to prevent leaks with a torque of 39 to 49
kgf·m {4 to 5 kgf·m}. Vertical impulse piping type

Vertical impulse piping type Pressure-detector section

Bolt
Rotate 90° or 180° segments

Process connector gasket

Conduit connection

Transmitter section
∗1
∗2
Drain/vent plug Horizontal impulse piping type

Horizontal impulse piping type


Transmitter section

Rotate 90° or 180° segments

Conduit connection
Zero-adjustment screw

Pressure-detector section

Note: For a horizontal impulse piping type, moving the F0404.EPS


process connectors from the front side to the
back is not allowed. Figure 4.4 Rotating Transmitter Section
F0403.EPS

Figure 4.3 Changing Process Connection

4-2 IM 01C22D01-01E
4. INSTALLATION

4.5 Changing the Direction of


Integral Indicator

IMPORTANT

Always turn OFF power, release pressure and


remove a transmitter to non-hazardous area
before disassembling and reassmbling an
indicator.

An integral indicator can be installed in the following


three directions. Follow the instructions in section 9.4
for removing and attaching the integral indicator.

F0405.EPS

Figure 4.5 Integral Indicator Direction

4-3 IM 01C22D01-01E
5. INSTALLING IMPULSE PIPING

5. INSTALLING IMPULSE PIPING


5.1 Impulse Piping Installation 5.1.2 Routing the Impulse Piping
Precautions
(1) Process Pressure Tap Angles
The impulse piping that connects the process outputs to
If condensate, gas, sediment or other extraneous
the transmitter must convey the process pressure
material in the process piping gets into the impulse
accurately. If, for example, gas collects in a liquid-
piping, pressure measurement errors may result. To
filled impulse piping, or the drain of a gas-filled
prevent such problems, the process pressure taps must
impulse piping becomes plugged, the impulse piping
be angled as shown in Figure 5.1.2 according to the
will not convey the pressure accurately. Since this will
kind of fluid being measured.
cause errors in the measurement output, select the
proper piping method for the process fluid (gas, liquid,
or steam). Pay careful attention to the following points
NOTE
when routing the impulse piping and connecting the
impulse piping to the transmitter. • If the process fluid is a gas, the taps must be
vertical or within 45° either side of vertical.
5.1.1 Connecting Impulse Piping to the • If the process fluid is a liquid, the taps must be
Transmitter horizontal or below horizontal, but not more
than 45° below horizontal.
(1) Connecting the Impulse Piping to the • If the process fluid is steam or other condens-
Transmitter
ing vapor, the taps must be horizontal or above
Symbols “H” and “L” are shown on a capsule assem- horizontal, but not more than 45° above hori-
bly to indicate high and low pressure side. Connect the zontal.
impulse piping to the “H” side.
[Gas] [Liquid] [Steam]

“H” and “L” are shown 45° 45°


Pressure
Process connection taps 45° 45°

Process connector Process 45° 45°


piping
Bolt F0501.EPS F0502.EPS

Figure 5.1.1 “H” and “L” Symbols on a Capsule Assembly Figure 5.1.2 Process Pressure Tap Angle (For Horizontal
Piping)

(2) Tightening the Process Connector Mount- (2) Position of Process Pressure Taps and
ing Bolts Transmitter
After connecting the impulse piping, tighten the If condensate (or gas) accumulates in the impulse
process connector mounting bolts uniformly. piping, it should be removed periodically by opening
the drain (or vent) plugs. However, this will generate a
transient disturbance in the pressure measurement, and
therefore it is necessary to position the taps and route
the impulse piping so that any extraneous liquid or gas
generated in the leadlines returns naturally to the
process piping.
• If the process fluid is a gas, then as a rule the
transmitter must be located higher than the process
pressure taps.
• If the process fluid is a liquid or steam, then as a
rule the transmitter must be located lower than the
process pressure taps.

5-1 IM 01C22D01-01E
5. INSTALLING IMPULSE PIPING

(3) Impulse Piping Slope 5.2 Impulse Piping Connection


The impulse piping must be routed with only an Examples
upward or downward slope. Even for horizontal
routing, the impulse piping should have a slope of at Figure 5.2 shows examples of typical impulse piping
least 1/10 to prevent condensate (or gases) from connections. Before connecting the transmitter to the
accumulating in the pipes. process, study the transmitter installation location, the
process piping layout, and the characteristics of the
(4) Preventing Freezing process fluid (corrosiveness, toxicity, flammability,
If there is any risk that the process fluid in the impulse etc.), in order to make appropriate changes and
piping or transmitter could freeze or solidify, use a additions to the connection configurations.
steam jacket or heater to maintain the temperature of Note the following points when referring to these
the fluid. piping examples.
• The transmitter impulse piping connection is shown
NOTE for a vertical impulse piping connection configura-
tion in which the direction of connection is either
After completing the connections, close the valves upwards or downwards.
on the process pressure taps (main valves), the • If the impulse piping is long, bracing or supports
valves at the transmitter (stop valves), and the should be provided to prevent vibration.
impulse piping drain valves, so that condensate, • The impulse piping material used must be compat-
sediment, dust and other extraneous material ible with the process pressure, temperature, and
cannot enter the impulse piping. other conditions.
• A variety of process pressure tap valves (main
valves) are available according to the type of
connection (flanged, screwed, welded), construction
(globe, gate, or ball valve), temperature and
pressure. Select the type of valve most appropriate
for the application.

Liquid Gas Steam

Tap valve Union or flange

Union or flange Drain plug


Drain valve Tap valve

Union or
flange
Tee
Tee Tee

Union or flange
Tap valve

Drain valve Drain valve


Drain plug Drain plug
F0503.EPS

Figure 5.2 Impulse Piping Connection Examples

5-2 IM 01C22D01-01E
6. WIRING

6. WIRING

6.1 Wiring Precautions


CAUTION

When selecting cables for TIIS flameproof type


IMPORTANT transmitters, determine cables' maximum allow-
able heat resistance depending on the tempera-
• Lay wiring as far as possible from electrical
ture condition on the transmitter. See Section
noise sources such as large capacity transform-
2.9.5 TIIS Certification for details.
ers, motors, and power supplies.
• Remove electrical connection dust cap before
wiring. (d) In environment where oils, solvents, corrosive gases
• All threaded parts must be treated with water- or liquids may be present, use wires or cables that
proofing sealant. (A non-hardening silicone are resistant to such substances.
group sealant is recommended.) (e) It is recommended that crimp-on solderless terminal
• To prevent noise pickup, do not pass signal lugs (for 4 mm screws) with insulating sleeves be
and power cables through the same ducts. used for leadwire ends.
• Explosion-protected instruments must be wired
in accordance with specific requirements (and,
in certain countries, legal regulations) in order 6.3 Connections of External
to preserve the effectiveness of their explosion- Wiring to Terminal Box
protected features.
• The terminal box cover is locked by an Allen 6.3.1 Power Supply Wiring Connection
head bolt (a shrouding bolt) on CENELEC,
IECEx, and TIIS flameproof type transmitters. Connect the power supply wiring to the SUPPLY +
When the shrouding bolt is driven clockwise by and – terminals.
an Allen wrench, it is going in and cover lock is
released, and then the cover can be opened. Transmitter terminal box
+
See Subsection 9.4 “Disassembly and Reas- Power supply
sembly” for details. –
Refer to The “Installation and Operating
Precautions for TIIS Flameproof Equipment” F0601.EPS

and “Installation and Operating Precautions


Figure 6.3.1 Power Supply Wiring Connection
for TIIS Intrinsically Safe Equipment” at the
end of this manual for correct wiring.
6.3.2 External Indicator Connection
Connect wiring for external indicators to the CHECK +
6.2 Selecting the Wiring Materi- and – terminals.
als (Note) Use a external indicator whose internal resistance is 10 Ω or
(a) Use stranded leadwires or cables which are the less.

same as or better than 600 V grade PVC insulated External indicator


wire (JIS C3307) or equivalent. Power supply
+
(b) Use shielded wires in areas that are susceptible to

electrical noise.
(c) In areas with higher or lower ambient temperatures,
use appropriate wires or cables.
Transmitter terminal box
F0602.EPS

Figure 6.3.2 External Indicator Connection

6-1 IM 01C22D01-01E
6. WIRING

6.3.3 BRAIN TERMINAL BT200 Connec- 6.4.1 Loop Configuration


tion
Since the DPharp uses a two-wire transmission system,
Connect the BT200 to the SUPPLY + and – terminals signal wiring is also used as power wiring.
(Use hooks). The communication line requires a
DC power is required for the transmitter loop. The
reception resistor of 250 to 600 Ω in series.
transmitter and distributor are connected as shown
below.
Transmitter terminal box
+ For details of the power supply voltage and load
Power supply resistance, see Section 6.6; for communications line

requirements, see Subsection 8.1.2.
Ignore the polarity
since the BT200 is
AC-coupled to the (1) General-use Type and Flameproof Type
BT200 terminal box.
F0603.EPS
Hazardous Location Nonhazardous Location
Figure 6.3.3 BT200 Connection
Transmitter terminal box
Distributor
6.3.4 Check Meter Connection (Power supply unit)

Connect the check meter to the CHECK + and –


terminals (use hooks). Receiver
+ instrument
• A 4 to 20 mA DC output signal from the CHECK + –
and – terminals. F0605.EPS

(Note) Use a check meter whose internal resistance is 10 Ω or less. Figure 6.4.1a Connection between Transmitter and
Distributor
Power supply
+
(2) Intrinsically Safe Type

For intrinsically safe type, a safety barrier must be
included in the loop.
Check meter
Transmitter terminal box F0604.EPS
Hazardous Location Nonhazardous Location
Figure 6.3.4 Check Meter Connection
Transmitter terminal box
Distributor
(Power supply unit)
6.4 Wiring
Receiver
instrument
+
CAUTION –

For the intrinsically safe equipment and flame- Safety barrier F0606.EPS
proof equipment, wiring materials and wiring
work for these equipment including peripherals Figure 6.4.1b Connection between Transmitter and
Distributor
are strictly restricted. Users absolutely must read
“Installation and Operating Precautions for TIIS
Intrinsically Safe Equipment” and “Installation
and Operating Precautions for TIIS Flameproof
Equipment” at the end of this manual prior to the
work.

6-2 IM 01C22D01-01E
6. WIRING

6.4.2 Wiring Installation • Measure the cable outer diameter in two directions to
within 1 mm.
(1) General-use Type and Intrinsically Safe • Calculate the average of the two diameters, and use
Type packing with an internal diameter nearest to this value
Make cable wiring using metallic conduit or water- (see Table 6.4.2).
proof glands.
Table 6.4.2 Flameproof Packings and Applicable Cable
• Apply a non-hardening sealant to the terminal box Outer Diameters
connection port and to the threads on the flexible
Wiring Port Applicable
metal conduit for waterproofing. Optional Thread Cable OD Identifying Part
Code Diameter (mm) Mark Number

G11 8 to 10 16 8-10
G 1/2 G9601AM
G12 10.1 to 12 16 10-12
T0601.EPS
Flexible metal conduit • Mounting flameproof packing adapter body to conduit
Apply a non-hardening connection (see Figure 6.4.2c)
sealant to the threads for 1) Screw the flameproof packing adapter into the
Wiring metal waterproofing.
conduit terminal box until the O-ring touches the wiring
Tee port (at least 6 full turns), and firmly tighten the
Drain plug
lock nut.
F0607.EPS
2) Insert the cable through the union cover, the union
Figure 6.4.2a Typical Wiring Using Flexible Metal Conduit coupling, the clamp nut, the clamp ring, the gland,
the washer, the rubber packing, and the packing
box, in that order.
(2) Flameproof Type (TIIS) 3) Insert the end of the cable into the terminal box.
Wire cables through a flameproof packing adapter, or 4) Tighten the union cover to grip the cable. When
using a flameproof metal conduit. tightening the union cover, tighten approximately
one turn past the point where the cable will no
䊏 Wiring cable through flameproof packing adapter
longer move up and down.
for only TIIS flameproof type (see Figure 6.4.2b).
Proper tightening is important. If it is too tight, a
• Use only flameproof packing adapters approved by
circuit break in the cable may occur; if not tight
Yokogawa.
enough, the flameproof effectiveness will be
• Apply a nonhardening sealant to the terminal box
compromised.
connection port and to the threads on the flameproof
5) Fasten the cable by tightening the clamp nut.
packing adapter for waterproofing.
6) Tighten the lock nut on the union cover.
7) Connect the cable wires to each terminal.

Flameproof packing adapter


Apply a non-hardnening
Flexible metal conduit sealant to the threads for
waterproofing.
Wiring metal Apply a non-hardening
conduit sealant to the threads for O-ring
waterproofing. Adapter body
Clamp nut
Tee Lock nut
Wrench Union coupling
Drain plug Packing box
F0608.EPS Lock nut
Rubber packing
Washer Wrench
Figure 6.4.2b Typical Cable Wiring Using Flameproof
Packing Adapter Gland Union cover
Clamp ring
Cable
F0609.EPS

Figure 6.4.2c Installing Flameproof Packing Adapter

6-3 IM 01C22D01-01E
6. WIRING

䊏 Flameproof metal conduit wiring Transmitter terminal box


• A seal fitting must be installed near the terminal box
connection port for a sealed construction. Ground terminal
• Apply a non-hardening sealant to the threads of the (Inside)
terminal box connection port, flexible metal conduit
and seal fitting for waterproofing.

Gas sealing device


Non-hazardous area
Ground terminal
(Outside)
Flameproof flexible
metal conduit

;;
Hazardous area F0611.EPS
Apply a non-hardening
Flameproof
sealant to the threads of Figure 6.5 Ground Terminals
heavy-gauge
these fittings for
steel conduit
waterproofing

Tee Seal fitting


Drain plug After wiring, impregnate the fitting 6.6 Power Supply Voltage and
with a compound to seal tubing.
F0610.EPS
Load Resistance
Figure 6.4.2d Typical Wiring Using Flameproof Metal When configuring the loop, make sure that the external
Conduit load resistance is within the range in the figure below.
(Note) In case of an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.

6.5 Grounding
600
Grounding is always required for the proper operation
of transmitters. Follow the domestic electrical require- External E–10.5
R= Communication
ments as regulated in each country. For a transmitter load 0.0236
applicable range
with built-in lightning protector, grounding should resistance BRAIN and HART
R (Ω)
satisfy Class C requirement (ground resistance of 10⍀
or less).
250
Ground terminals are located on the inside and outside
of the terminal box. Either of these terminals may be
used.

0 10.5 16.4 24.7 42

WARNING Power supply voltage E (V DC)


F0612.EPS

For TIIS flameproof type and intrinsically safe, Figure 6.6 Relationship between Power Supply Voltage
grounding should satisfy Class D requirements and External Load Resistance

(grounding resistance, 100⍀ or less).

6-4 IM 01C22D01-01E
7. OPERATION

7. OPERATION

7.1 Preparation for Starting


Operation
The Model EJA310 and EJA430 pressure transmitter Vent plug (Fill plug)
measure the pressure of liquids, gases, and steam. This
section describes the operation procedure for the
Tap valve
EJA430 as shown in Figure 7.1 (vertical impulse
piping type, high-pressure connection: right side) when
measuring a pressure.
Stop valve

NOTE

Confirm that the process pressure tap valve,


drain valve, and stop valve are closed.

(a) Introduce a process fluid into the impulse piping Drain valve
and then to the transmitter in the following proce-
dure: F0701.EPS

1) Open the tap valve (main valve) to fill the impulse Figure 7.1 Liquid Flow Measurement
piping with process fluid.
2) Gradually open the stop valve to introduce process
fluid into the transmitter pressure-detector section.
3) Confirm that there is no pressure leak in the  Confirming that Transmitter is Operating
Properly
impulse piping, transmitter, or other components.
Using the BT200
(b) Venting Gas from the Transmitter Pressure-detector • If the wiring system is faulty, ‘communication error’
Section appears on the display.
Since the piping in the example of Figure 7.1 is • If the transmitter is faulty, ‘SELF CHECK ERROR’
constructed to be self-venting, no venting operation appears on the display.
is required. If it is not possible to make the piping
self-venting, refer to Subsection 7.5 for instructions. PARAM
C60:SELF CHECK
(c) Turn ON power and connect the BT200. ERROR
Open the terminal box cover, and connect the communication error
BT200 to the SUPPLY + and – terminals.
(d) Using the BT200, confirm that the transmitter is DATA DIAG PRNT ESC
operating properly. Check parameter values or
Communication error Self-diagnostic error
change the setpoints as necessary. See Chapter 8 for
(Faulty wiring) (Faulty transmitter)
BT200 operation. F0702.EPS

If the transmitter is equipped with an integral


indicator, its indication can be used to confirm that
the transmitter is operating properly.

7-1 IM 01C22D01-01E
7. OPERATION

Using the integral indicator 7.2 Zero Point Adjustment


• If the wiring system is faulty, the display stays blank.
• If the transmitter is faulty, an error code will appear Adjust the zero point after operating preparation is
on the display according to the nature of the error. completed.

IMPORTANT

Do not turn off the power to the transmitter


immediately after a zero adjustment. Powering
Self-diagnostic error on off within 30 seconds after a zero adjustment will
the integral indicator
return the adjustment back to the previous
(Faulty transmitter)
F0703.EPS settings.

NOTE The zero point adjustment can be made in either way:


using the zero-adjustment screw of the transmitter or
If any of the error indications above appears on
the BT200 operation.
the display of the integral indicator or BT200,
refer to Subsection 8.5.2 for corrective action. For output signal checking, display the parameter A10:
OUTPUT (%) in the BT200.

 Verify and Change Transmitter Parameter BT200


Setting and Values
The following parameters are the minimum settings PARAM Output signal (%)
A10:OUTPUT(%) display
required for operation. The transmitter has been 0.0 %
A11:ENGR OUTPUT
shipped with these parameters. To confirm or change
A20:AMP TEMP
the values, see Subsection 8.3.3.
• Measuring range..........See Subsection 8.3.3 (2) DATA DIAG PRNT ESC
• Operation mode...........See Subsection 8.3.3 (7)
Zero-adjustment Screw

Zero-adjustment
screw

F0704.EPS

After reviewing this parameter you are prepared to


adjust the zero point. When making the zero adjust-
ment on a pressure transmitter, the process pressure
value does not have to be set to the low limit of the
measurement range (0%). In such case, adjust the
transmitter output signal to the actual measured value
obtained from a high-accuracy pressure measuring
instrument.

7-2 IM 01C22D01-01E
7. OPERATION

7.2.1 When you can obtain Low Range 7.2.2 When you cannot obtain Low Range
Value from actual measured value Value from actual measured value
of 0% (0 kPa, atmospheric pres- of 0%;
sure);
Convert the actual measured value obtained by a digital
For pressure measurement using gauge pressure manometer or a glass gauge into %.
transmitters, follow the step below before zero point
[Example]
adjustment.
1) Close the tap valve (main valve). The measuring range of 50 to 250 kPa; the actual
2) Loosen the fill plug so that the pressure applied to measured value of 130 kPa.
the transmitter is only the head of the seal liquid.
3) Adjust the zero point at this status. 130–50
Actual measured value= x 100=40.0%
4) After the adjustment, close the fill plug and then 250–50
gradually open the tap valve.
 Using the Transmitter Zero-Adjustment Screw
Turn the screw to match the output signal to the actual
 Using the Transmitter Zero-adjustment measured value in %.
Screw
Before adjusting a screw, check that the parameter  Using the BT200
J20: EXT ZERO ADJ displays ENABLE. See Select the parameter J10: ZERO ADJ. Change the
Subsection 8.3.3 (11) for the setting procedure. set point (%) displayed for the parameter to the actual
measured value (%), and press the ENTER key twice.
Use a slotted screwdriver to turn the zero-adjustment
See Subsection 8.3.3 (11) for operation details.
screw. Turn the screw clockwise to increase the output
or counterclockwise to decrease the output. The zero
SET A display at J10
point adjustment can be made with a resolution of J10:ZERO ADJ
–0.0 %
0.01% of the setting range. Since the degree of zero + 000.0
adjustments varies with the screw turning speed, turn
the screw slowly for fine adjustment and quickly for
coarse adjustment. CLR ESC

SET Change setting to the actually


 Using the BT200 J10:ZERO ADJ
–0.0 % measured value (40.0%).
Zero point can be adjusted by simple key operation of + 040.0
Press key twice
the BT200.
for 40% output 10.4 mA DC.
Select parameter J10: ZERO ADJ, and press the
CLR ESC
ENTER key twice. The zero point will be adjusted F0706.EPS

automatically to the output signal 0% (4 mA DC).


Confirm that the setting value displayed for the
parameter is ‘0.0%’ before pressing the ENTER key.
See Subsection 8.3.3 (11) for BT200 operating proce-
dures.

SET
J10:ZERO ADJ A display when parameter
–0.0 %
+ 000.0 J10 is selected.
Press key
twice for 0% output 4 mA DC.
CLR ESC
F0705.EPS

7-3 IM 01C22D01-01E
7. OPERATION

7.3 Starting Operation 7.5 Venting or Draining Transmit-


After completing the zero point adjustment, follow the ter Pressure-detector Section
procedure below to start operation. Since this transmitter is designed to be self-draining
1) Confirm the operating status. If the output signal and self-venting with vertical impulse piping connec-
exhibits wide fluctuations (hunting) due to periodic tions, neither draining nor venting will be required if
variation in the process pressure, use BT200 to the impulse piping is configured appropriately for self-
dampen the transmitter output signal. Confirm the draining or self-venting operation.
hunting using a receiving instrument or the integral If condensate (or gas) collects in the transmitter
indicator, and set the optimum damping time
pressure-detector section, the measured pressure may
constant. See Subsection 8.3.3 (3), “Damping Time be in error. If it is not possible to configure the piping
Constant Setup.” for self-draining (or self-venting) operation, you will
2) After confirming the operating status, perform the
need to loosen the drain (vent) screw on the transmitter
following. to completely drain (vent) any stagnated liquid (gas).
However, since draining condensate or bleeding off gas
IMPORTANT gives the pressure measurement disturbance, this
• Remove the BT200 from the terminal box, and should not be done when the loop is in operation.
confirm that none of the terminal screws are
loosened.
• Close the terminal box cover and the amplifier WARNING
cover. Screw each cover in tightly until it will
Since the accumulated liquid (or gas) may be
not turn further.
toxic or otherwise harmful, take appropriate care
• Two covers are required to be locked on the
to avoid contact with the body, or inhalation of
CENELEC, IECEx, and TIIS Flameproof type
vapors.
transmitters. An Allen head bolts (shrouding
bolts) are provided under edge of the each
cover for locking. When a shrouding bolts are
7.5.1 Draining Condensate
driven counterclockwise by an Allen wrench, it
is coming out and locks up a cover. (See page 1) Gradually open the drain screw or drain plug and
9-3) After locking, the covers should be drain the transmitter pressure-detector section. (See
confirmed not to be opened. Figure 7.5.1.)
• Tighten the zero-adjustment cover mounting 2) When all accumulated liquid is completely re-
screw to fix the cover in position. moved, close the drain screw or drain plug.
3) Tighten the drain screw to a torque of 10 N·m
{1kgf·m}, and the drain plug to a torque of 34 to 39
7.4 Shutting Down Operation N·m {3.5 to 4 kgf ·m}.

Shut down the transmitter operation as follows.


1) Turn off the power.
2) Close the stop valve.
3) Close the tap valve.

NOTE
Drain plug
Whenever shutting down the transmitter for a
long period, remove any process fluid from the Drain screw
transmitter pressure-detector section.
When you loosen the drain screw or drain
plug, the accumulated liquid will be expelled
in the direction of the arrow.
F0707.EPS

Figure 7.5.1 Draining the Transmitter

7-4 IM 01C22D01-01E
7. OPERATION

7.5.2 Venting Gas 6) Press the range-setting push-button. The integral


indicator then displays “HSET.”
1) Gradually open the vent screw to vent gas from the
7) Apply a pressure of 3 MPa to the transmitter. (Note 1)
transmitter pressure-detector section. (See Figure
8) Turn the external zero-adjustment screw in the
7.5.2.)
desired direction. The integral indicator displays the
2) When the transmitter is completely vented, close
output signal in %. (Note 2)
the vent screw.
9) Adjust the output signal to 100% (5 V DC) by
3) Tighen the vent screw to a torque of 10 N·m
rotating the external zero-adjustment screw. Doing
{1kgf·m}.
so completes the HRV setting.
10) Press the range-setting push-button. The transmitter
Vent screw then switches back to the normal operation mode
with the measurement range of 0 to 3 MPa.
Note 1: Wait until the pressure inside the pressure-detector section
has stabilized before proceeding to the next step.
Note 2: If the pressure applied to the transmitter exceeds the previous
LRV (or HRV), the integral indicator may display error
number “Er.07” (In this case, the output signal percent and
“Er.07” are displayed alternately every two seconds).
Although “Er.07” is displayed, you may proceed to the next
Vent screw step. However, should any other error number be displayed,
take the appropriate measure in reference to Subsection
When you loosen the vent screw, the gas 8.5.2, “Errors and Countermeasures.”
escpes in the direction of the arrow.
F0708.EPS

Figure 7.5.2 Venting the Transmitter


IMPORTANT

7.6 Setting the Range Using the • Do not turn off the power to the transmitter
immediately after completion of the change in
Range-setting Switch the LRV and/or HRV setting(s). Note that
With actual pressure being applied to the transmitter, powering off within thirty seconds after setting
the range-setting switch (push-button) located on the will cause a return to the previous settings.
optional integral indicator plate and the external zero- • Changing LRV automatically changes HRV to
adjustment screw allow users to change (re-range) the the following value.
low- and high-limit values for the measurement range HRV = previous HRV + (new LRV – previous LRV)
(LRV and HRV) without using BT200. However, other
changes in the display settings (scale range and • If the range-setting push-button and external
engineering unit) for the integral indicator requires zero-adjustment screw are not touched during a
BT200. range-change operation, the transmitter auto-
matically switches back to the normal operation
Follow the procedure below to change the LRV and mode.
HRV settings.
[Example] Integral indicator

Rerange LRV to 0 and HRV to 3 MPa.


Note : Use a thin bar which
has a blunt tip, e.g.,
1) Connect the transmitter and apparatus as shown in a hexagonal wrench,
Figure 9.3.1 and warm up for at least five minutes. to press the range-
2) Press the range-setting push-button. setting push-button

The integral indicator then displays “LSET.”


3) Apply a pressure of 0 kPa (atmospheric pressure) to
Range-setting switch
the transmitter. (Note 1) (Push-button)
F0709.EPS
4) Turn the external zero-adjustment screw in the
desired direction. The integral indicator displays the Figure 7.6 Range-setting Switch
output signal in %. (Note 2)
5) Adjust the output signal to 0% (1 V DC) by rotating
the external zero-adjustment screw. Doing so
completes the LRV setting.

7-5 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

8. BRAIN TERMINAL BT200


OPERATION
The DPharp is equipped with BRAIN communica- 8.2 BT200 Operating Procedures
tions capabilities, so that range changes, Tag No.
setup, monitoring of self-diagnostic results, and zero 8.2.1 Key Layout and Screen Display
point adjustment can be handled by remote control
via BT200 BRAIN TERMINAL or CENTUM CS Figure 8.2.1a shows the arrangement of the operating
console. This section describes procedures for setting keys on the BT200 keypad, and Figure 8.2.1b shows
parameters using the BT200. For details concerning the BT200 screen component.
the BT200, see IM 01C00A11-01E, “BT200 User’s
Manual.”

LCD
8.1 BT200 Operation Precau- (21 character × 8 lines)

tions
8.1.1 Connecting the BT200
The transmitter and the BT200 can be connected
either to the BT200 connection hooks in the transmit- Function keys
ter terminal box or to a relaying terminal board.
Movement keys

ENTER key

Control room Power ON/OFF key


Relaying
terminals Terminal board
Alphanumeric keys

Distributor

Shift keys
F0803.EPS

F0801.EPS
Figure 8.2.1a BT200 Key Layout
Figure 8.1.1 Connecting the BT200

MENU SCREEN
Messages
8.1.2 Conditions of Communication Line MENU
A:DISPLAY
BATTERY
B:SENSOR TYPE
Menu choices
Cable resistance Rc Screen title

HOME SET ADJ ESC

Power PARAMETER SCREEN


cc
supply PARAM
A10:OUTPUT Function
100.0 %
Parameters A11:ENGR. OUTPUT commands
1000 mmH20
DPharp A20:AMP TEMP
Load Cable 23 deg C
resistance R resistance Rc DATA DI AG PRNT
F0804.EPS
 Loop resistance = R + 2Rc
= 250 to 600 Ω Figure 8.2.1b BT200 Screen Component
 Loop capacitance = 0.22 µF max. BT200
F0802.EPS

Figure 8.1.2 Conditions of Communication Line


8-1 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

8.2.2 Operating Key Functions Use the function key [F1] CODE to enter symbols.
The following symbols will appear in sequence, one
(1) Alphanumeric Keys and Shift Keys at a time, at the cursor each time you press [F1]
You can use the alphanumeric keys in conjunction CODE:
with the shift keys to enter symbols, as well as
/ . – , + * ) ( ’ & % $ # ” !
alphanumeric keys.
To enter characters next to these symbols, press [ > ]
to move the cursor.

Entry Key-in Sequence


Alphanumeric keys symbol command
l/m
(I) (/) (m)
T0803.EPS
Shift keys
F0805.EPS

(2) Function Keys


a. Entering Digits, Symbols, and Spaces The functions of the function keys depend on the
Simply press the alphanumeric keys. function commands on display.

Entry Key-in Sequence


MENU
–4 A:DISPLAY
B:SENSOR TYPE
0.3

1 –9
HOME SET ADJ ESC Function commands
T0801.EPS

b. Entering Letters (A through Z) Function keys


Press an alphanumeric key following a shift key to F0808.EPS

enter the letter shown on that side which the shift key
represents. You must press the shift key before
Function Command List
entering each letter.
Command Function
ADJ Displays the ADJ menu
Left-side letter on the Right-side letter on
alphanumeric key the alphanumeric key CAPS/caps Selects uppercase or lowercase
CODE Selects symbols
F0806 .EPS
CLR Erases input data or deletes all data
Entry Key-in Sequence DATA Updates parameter data

W DEL Deletes one character


DIAG Calls the self-check panel
IC
ESC Returns to the most recent display
J. B HOME Displays the menu panel
T0802.EPS
NO Quits setup and returns to the previous display
Use the function key [F2] CAPS to select between
uppercase and lowercase (for letters only). The case OK Proceeds to the next panel

toggles between uppercase and lowercase each time PARM Enters the parameter number setup mode
you press [F2] CAPS. SET Displays the SET menu
SLOT Returns to the slot selection panel
UTIL Calls the utility panel
Entering uppercase Entering lowercase
*COPY Prints out parameters on display
CODE CAPS CLR ESC CODE caps CLR ESC
*FEED Paper feed
*LIST Lists all parameters in the menu
Entry Key-in Sequence *PON/POFF Automatic printout mode on or off
to lower case *PRNT Changes to the print mode
Boy *GO Starts printing
(B) (o) (y) *STOP Cancels printing
F0807.EPS
* Available on BT200-P00 (with printer).
T0804.EPS

8-2 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

8.2.3 Calling Up Menu Addresses Using the Operating Keys

––WELCOME–– UTILITY The utility screen contains the


BRAIN TERMINAL 1.ID following items.
ID: BT200 2.SECURITY CODE
STARTUP 3.LANGUAGE SELECT 1. BT200 ID settings
SCREEN check connection 4.LCD CONTRAST 2. Security code settings
push ENTER key 5.PRINTER ADJUST
3. Switching language of messages
UTIL FEED esc (Japanese or English)
4. LCD contrast setting
5. Adjusting printout tone
(UTIL)
(BT200-P00 only)

PARAM
01:MODEL
EJA430-DA
INITIAL 02:TAG NO. FUNC
DATA YOKOGAWA 1.MENU
SCREEN 03:SELF CHECK (ESC) 2.UPLOAD TO BT200
GOOD 3.DOWNLOAD TO INST
OK 4.PRINT ALL DATA

HOME SET ADJ ESC

(SET) (ADJ)
(HOME MENU SCREEN) (SET MENU SCREEN) (ADJ MENU SCREEN)
MENU MENU MENU
A.DISPLAY C.SETTING J.ADJUST
B.SENSOR TYPE D.AUX SET 1 K.TEST
MENU E.AUX SET 2 M.MEMO
SCREEN H:AUTO SET P:RECORD

HOME SET ADJ ESC HOME SET ADJ ESC HOME SET ADJ ESC

PARAM PARAM
A60:SELF CHECK C60:SELF CHECK
GOOD GOOD

PARAM PARAM PARAM


A21:CAPSULE TEMP C22:HIGH RANGE J60:SELF CHECK
PARA- 26.5 deg C 100 kPa GOOD
METER DATA DIAG PRNT ESC DATA DIAG PRNT ESC
SCREEN
PARAM PARAM PARAM
A10:OUTPUT(%) C10:TAG NO. J10:ZERO ADJ
50.0 % YOKOGAWA 0.0 %
DATA DIAG
A11:ENGR, PRNT
OUTPUT ESC DATA DIAG
C20:PRESS UNITPRNT ESC DATA DIAG
J11:ZERO DEV PRNT ESC
20.0 M kPa 22.2 %
A20:AMP TEMP C21:LOW RANGE J20:EXT. ZERO ADJ
24.5 deg C 0 kPa ENABLE
DATA DIAG PRNT ESC DATA DIAG PRNT ESC DATA DIAG PRNT ESC

SET See “BT200 Instruction Manual” for details


C10:TAG NO. concerning uploading and downloading parameters
SETUP YOKOGAWA
SCREEN YOKOGAWA and printouts (BT200-P00).

CODE CAPS CLR ESC


F0809.EPS

8-3 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

8.3 Setting Parameters Using the BT200


8.3.1 Parameter Summary
Instruments to which applicable:
F: Differential pressure transmitters EJA110, EJA120, EJA118W, EJA118N, EJA118Y, and EJA115
P: Pressure transmitters EJA310, EJA430, EJA438W, and EJA438N
L: Liquid level transmitters EJA210 and EJA220
Applica-
Rewrita- bility
No. Item Description Remarks Default Value
bility F P L
01 MODEL Model+capsule type —

02 TAG NO. Tag number — 16 alphanumerics


03 SELF CHECK Self-diagnostic result — GOOD/ERROR
A DISPLAY Measured data display — Menu name
A10 OUTPUT (%) Output (in %) — –5 to 110%*3
A11 ENGR. Output (in engineering — –19999 to 19999
OUTPUT units)
A20 AMP TEMP Amplifier temperature — Unit specified in D30
A21 CAPSULE Capsule temperature — Unit specified in D30
TEMP
A30 STATIC Static pressure — Unit specified in D31*1 —

PRESS
A40 INPUT Input (indicated as the — –32000 to 32000
value after zeroing)
A60 SELF CHECK Self-diagnostic — GOOD/ERROR, CAP MODULE FAULT, AMP MODULE FAULT,
messages OUT OF RANGE, OUT OF SP RANGE*1, OVER TEMP (CAP),
OVER TEMP (AMP), OVER OUTPUT, OVER DISPLAY,
ILLEGAL LRV, ILLEGAL HRV, ILLEGAL SPAN, and
ZERO ADJ OVER
B SENSOR Sensor type — Menu name
TYPE
B10 MODEL Model+span — 16 uppercase alphanumerics
B11 STYLE NO.Style number —

B20 LRL Lower range-limit — –32000 to 32000


B21 URL Upper range-limit — –32000 to 32000
B30 MIN SPAN Minimum span — –32000 to 32000
B40 MAX STAT.P.
Maximum static — —

pressure*6
B60 SELF CHECK Self-diagnostic — Same as A60
messages
C SETTING Setting data — Menu name
C10 TAG. NO. Tag number 16 alphanumerics As specified when ordered.
C20 PRESS UNIT Measurement range Selected from mmH2O, mmAq, As specified when ordered.
units mmWG, mmHg, Torr, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm2, kgf/cm2,
inH2O, inHg, ftH2O, psi, or atm
C21 LOW RANGE Measurement range, –32000 to 32000(but within As specified when ordered.
lower range value measurement range)
C22 HIGH Measurement range, –32000 to 32000(but within As specified when ordered.
RANGE higher range value measurement range)
C30 AMP Damping time constant Selected from 0.2*2, 0.5, 1.0, 2.0, 2.0 s
DAMPING 4.0, 8.0, 16.0, 32.0, or 64.0 sec.
C40 OUTPUT Output mode and Selected from OUT:LIN; DSP:LIN, As specified when ordered. — —

MODE integral indicator mode OUT:LIN; DSP:SQR, If not specified,


OUT:SQR; DSP:SQR OUT: LIN; DSP: LIN.
C60 SELF CHECK Self-diagnostic — Same as A60
messages
D AUX SET 1 Auxiliary setting data 1 — Menu name
D10 LOW CUT Low cut 0.0 to 20.0% 10.0%
D11 LOW CUT Low cut mode LINEAR/ZERO LINEAR
MODE
D15 OUT LIMIT(L) Lower output range-limit –5.0 to 110.0% –5.0%*1
D16 OUT LIMIT(H) Upper output range-limit –5.0 to 110.0% 110.0%
D20 DISP SELECT Display selection NORMAL %/USER SET, As specified when ordered.
USER & %/INP PRES, PRES & %
D21 DISP UNIT Engineering unit for 8 uppercase
display alphanumerics
D22 DISP LRV Engineering range, –19999 to 19999 As specified when ordered.
lower range value
D23 DISP HRV Engineering range, –19999 to 19999 As specified when ordered.
higher range value
D30 TEMP UNIT Temperature setting deg C/deg F deg C
units
*1: Unless otherwise specified by order. When optional code /F1 is specified, substitute the value –5 with –2.5.
T0805.EPS

8-4 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

Applica-
No. Item Description Rewrita- Remarks bility
Default Value
bility F P L
D AUX SET 1 Auxiliary setting data 1 — Menu name
D31 STAT. P. UNIT Static pressure setting Selected from mmH2O, mmAq, As specified when ordered. —

units mmWG, mmHg, Torr, Pa, hPa, kPa, If not specified, MPa.
MPa, mbar, bar, gf/cm2, kgf/cm2,
inH2O, inHg, ftH2O, psi, or atm
D40 REV OUTPUT Output reversal NORMAL/REVERSE If not specified, NORMAL.
D45 H/L SWAP Impulse piping NORMAL/REVERSE*4 NORMAL — —
accessing direction
D52 BURN OUT CPU error —
HIGH/LOW, –5 to 110%*3 HIGH
D53 ERROR OUT Hardware error HOLD/HIGH/LOW, –5 to 110%*3 HIGH
D60 SELF CHECK Self-diagnostic — Same as A60
messages
E AUX SET 2 Auxiliary setting data 2 — Menu name
E10 DFS MODE DFS mode OFF/ON*5 ON —

E14 TEMP Reference temperature AMP. TEMP/CAP. TEMP*5 CAP. TEMP —

SELECT sensor
E15 TEMP ZERO Zero shift 10.00*5 0.00 —

conpensation setup
E30 BI DIRE Bidirectional mode OFF/ON OFF — —

MODE
E50 AUTO Auto-recover from OFF/ON ON
RECOVER sensor error
E60 SELF CHECK Self-diagnostic — Same as A60
messages
H AUTO SET Automatic setup — Menu name
H10 AUTO LRV Automatic measure- –32000 to 32000 Displays the same data as
ment range lower C21.
range value setup
H11 AUTO HRV Automatic –32000 to 32000 Displays the same data as
measurement range C22.
higher range value
setup
H60 SELF CHECK Self-diagnostic — Same as A60
messages
J ADJUST Adjustment data — Menu name
J10 ZERO ADJ Automatic zero –5 to 110.0%*3
adjustment
J11 ZERO DEV. Manual zero
adjustment
J15 SPAN ADJ Manual span adjustment –10.00 to 10.00% 0.00%
J20 EXT. ZERO External zero- ENABLE/INHIBIT
ADJ adjustment screw
permission
J30 OUTPUT 4mA 4mA adjustment –10.00 to 10.00% 0.00%
J31 OUTPUT 20mA 20mA adjustment –10.00 to 10.00% 0.00%
J60 SELF CHECK Self-diagnostic — Same as A60
messages
K TEST Tests — Menu name
K10 OUTPUT in % Test output % setting –5 to 110.0%*3 Displays ‘ACTIVE’
while executing
K60 SELF CHECK Self-diagnostic — Same as A60
messages
M MEMO Memo — Menu name
M10 MEMO 1 Memo 8 uppercase alphanumerics
M20 MEMO 2 Memo 8 uppercase alphanumerics
M30 MEMO 3 Memo 8 uppercase alphanumerics
M40 MEMO 4 Memo 8 uppercase alphanumerics
M50 MEMO 5 Memo 8 uppercase alphanumerics
M60 SELF CHECK Self-diagnostic — Same as A60
messages
P RECORD History of the errors —

P10 ERROR REC 1 Last error Display the error


P11 ERROR REC 2 One time before Display the error
P12 ERROR REC 3 Two time before Display the error
P13 ERROR REC 4 Three time before Display the error
P60 SELF CHECK Self-diagnostic —
Same as A60
messages
*1: In case of Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.
*2: When Optional code /F1 is specified, substitute the value with 0.1.
*3: When Optional code /F1 is specified, substitute the value –5 with –2.5.
*4: Not applicable for Model EJA115.
*5: Applicable only for Model EJA118W, EJA118N, EJA118Y, EJA438W, and EJA438N.
*6: See MWP(max. working pressure) on the nameplate. B40 shows an approximate value of maximum pressure for the capsule.
T0806.EPS

8-5 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

8.3.2 Parameter Usage and Selection


IMPORTANT
Before describing the procedure for setting param-
eters, we present the following table showing how If the transmitter is turned off within 30 seconds
the parameters are used and in what case. after parameters have been set, the set data
will not be stored and the terminal returns to
previous settings.

Table 8.3.1 Parameter Usage and Selection


Setup Item Description
Tag No. setup Sets the Tag No. (using 16 alphanumeric characters).
 P.8-7 Note: Up to 8 alphanumerics (upper case letters) can be used in the BT100.
Calibration range setup Sets the calibration range for 4 to 20 mA DC. Sets three data items: range unit, input value
 P.8-7 at 4 mA DC (LRV), and input value at 20 mA DC (HRV).
Note: LRV and HRV can be specified with range value specifications up to 5 digits
(excluding any decimal point) within the range of –32000 to 32000.
Damping time constant setup Adjusts the output response speed for 4 to 20 mA DC.
 P.8-8 Can be set in 9 increments from 0.2 to 64 s.
Output signal low cut mode setup Used to stabilize output near 0%: forcing output to 0% for input below a specific value.
 P.8-9
Change the output limits Change the range of normal output.
 P.8-9
Integral indicator scale range and Sets the following 5 types of integral indicator scale ranges and units:
unit setup % scale indicator, user set scale indicator, alternate indication of user set scale
 P.8-9 and % scale, input pressure display, alternate indication of input pressure and % scale
When using the user set scale, 4 types of data can be set:
user set scale setting, unit (BT200 only), display value at 4 mA DC (LRV), and display
value at 20 mA DC (HRV).
Note: LRV and HRV can be specified with range value specifications up to 5
digits (excluding any decimal point) within the range of –19999 to 19999.
Unit setup for displayed temperature Sets a unit for temperatures displayed on the BT200.
 P.8-11
Operation mode (normal/reverse Reverses the direction for 4 to 20 mA DC output relative to input.
signal) setup Reverse mode is used for applications in which safety requires that output be
 P.8-11 driven toward 20 mA if input is lost.
Output status display/setup when Displays the status of 4 to 20 mA DC output when a CPU failure. The parameter
a CPU failure  P.8-11 of the standard unit is fixed to the high limit value.
Output status setup when a hardware Sets the status of the 4 to 20 mA DC output when an abnormal status is detected
error occurs with the capsule or the amplifier as the result of self-diagnosis. One of the
 P.8-11 following statuses; last held, high limit, and low limit values, can be selected.
Range change (while applying Range for 4 to 20 mA DC signal is set with actual input applied. Sets 20 mA DC output
actual inputs) precisely with respect to user’s reference instrument output. Note that DPharp is calibrated
 P.8-12 with high accuracy before shipment, so span should be set using the normal range setup.
Zero point adjustment Adjusts zero point. This can be done either using the external zero-adjustment screw on
 P.8-12 the transmitteror using the BT200.
Span adjustment Adjust the characterization curve. All the transmitters are calibrated at factory and this
 P.8-14 adjustment is normally not necessary for most cases. Use for specific purposes.
Test output (fixed current output) Used for loop checks.
setup  P.8-15 Output can be set freely from –5% to 110% in 1% steps.
User memo fields Allows user to enter up to 5 items of any desired text in up to 8 uppercase
 P.8-15 alphanumeric characters per item.
T0807.EPS

8-6 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

8.3.3 Setting Parameters


SET This is the panel for confirming
C10:TAG NO.
Set or change the parameters as necessary. After YOKOGAWA
FIC-1a
set data. The set data items flash.
completing these, do not fail to use the “DIAG” key PRINTER OFF When all items have been confir-
F2:PRINTER ON
to confirm that “GOOD” is displayed for the self- FEED POFF NO
med, press the
diagnostic result at _60: SELF CHECK. again. (To go back to the setting
panel, press the (NO) key.
(1) Tag No. Setup (C10: TAG NO) SET The DPharp TAG NO. was
C10:TAG NO.
Use the procedure below to change the Tag No. Up FIC-1a overwritten.
to 16 alphanumeric characters can be entered. Press the (OK) key to
FEED NO OK
return to the parameter panel.
Press the (NO) key to
PARAM
• Example: Set a Tag No. to FIC-1a C10:TAG NO.
FIC-1a
return to the setting panel.
C20:PRESS UNIT
kPa
Press the key to turn on C21:LOW RANGE
the BT200. 0 kPa
DATA DIAG PRNT ESC
<When power is off>

F0811.EPS

––WELCOME–– Connect DPharp and BT200 using


BRAIN TERMINAL
ID: BT200 a communication cable and press
check connection the key. (2) Calibration Range Setup
push ENTER key

UTIL FEED a. Setting Calibration Range Unit


PARAM Displays the name of connected (C20: PRESS UNIT)
01:MODEL
EJA430-DA DPharp model, TAG NO. and The unit is set at the factory before shipment if
02:TAG NO.
YOKOGAWA diagnostics information. Press the
03:SELF CHECK specified at the time of order. Follow the procedure
GOOD (OK) key after confirmation.
OK below to change the unit.
MENU Press the (SET) key to
A:DISPLAY
B:SENSOR TYPE display the SET menu panel. • Example: Change the unit from mmH2O to kPa.
SET Use the or
HOME SET ADJ ESC C20:PRESS UNIT
mmH20
< mmWG > key to select “kPa.”
MENU Select C: SETTING and press the < mmHG >
C:SETTING < Torr > Press the key twice
D:AUX SET 1 key. < kPa >
E:AUX SET 2
H:AUTO SET ESC to enter the setting.
SET
HOME SET ADJ ESC C20:PRESS UNIT Press the (OK) key.
kPa
MENU Select C10: TAG NO. and press
C10:TAG NO.
YOKOGAWA the key.
C20:PRESS UNIT
kPa FEED NO OK
C21:LOW RANGE
0 kPa
DATA DIAG PRNT ESC
mmH2O
SET Set the new TAG NO. (FIC-1a). mmAq
C10:TAG NO.
mmWG
YOKOGAWA FOKOGAWA mmHg
YOKOGAWA
FIKOGAWA Torr
kPa
CODE CAPS CLR ESC FICOGAWA
MPa
FIC-GAWA mbar
FIC-1AWA bar
gf/cm2
kgf/cm2
FIC-1aWA inH2O
FIC-1a inHg
ftH2O
SET Set TAG NO. and press the psi
C10:TAG NO. atm
YOKOGAWA key. Pa
FIC-1a _
hPa

CODE caps CLE ESC F0812.EPS

When you have made an entry mistake, return


the cursor using the key, then reenter.

F0810.EPS

8-7 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

b. Setting Calibration Range Lower


Range Value and Higher Range Value • Example 2: With present settings of 0 to 30 kPa,
(C21: LOW RANGE, C22: HIGH set the Higher range value to10 kPa.
RANGE) SET
C22:HIGH RANGE
Set 10.
These range values are set as specified in the order 30 kPa Press the key twice
+ 10
before the instrument is shipped. Follow the proce- to enter the setting.
dure below to change the range. DEL CLR ESC

SET Press the (OK) key.


• The measurement span is determined by the high C22:HIGH RANGE
10 kPa
and low range limit values. In this instrument,
changing the low range value also automatically
FEED NO OK
changes the high range value, keeping the span
constant. PARAM The low range value is not
C20:PRESS UNIT
kPa changed, so the span changes.
C21:LOW RANGE
0 kPa
• Example 1: With present settings of 0 to 30 kPa, C22:HIGH RANGE
10 kPa
set the lower range value to 0.5 kPa. DATA DIAG PRNT ESC

SET Set 0.5. F0814.EPS


C21:LOW RANGE
0 kPa
+ 0.5 Press the key twice to
enter the setting.
(3) Damping Time Constant Setup
DEL CLR ESC (C30: AMP DAMPING)
SET When the instrument is shipped, the damping time
C21:LOW RANGE Press the (OK) key.
0.5 kPa constant is set at 2.0 seconds. Follow the procedure
below to change the time constant.
FEED NO OK

SET
C20:PRESS UNIT
The higher range value is changed • Example: Change from 2.0 sec to 4.0 sec.
kPa
C21:LOW RANGE while the span remains constant.
SET
0.5 kPa C30:AMP DAMPING Use the or key to
C22:HIGH RANGE 2.0 sec
30.5 kPa < 2.0 sec > select 4.0 sec.
DATA DIAG PRNT ESC < 4.0 sec >
< 8.0 sec > Press the key twice to
< 16.0 sec >
ESC enter the setting.
Span = Higher range value – Lower range value
SET
C30:AMP DAMPING Press the (OK) key.
F0813.EPS 4.0 sec

FEED NO OK
• Note, however, that changing the higher range value 0.2sec
does not cause the lower range value to change. 0.5sec
1.0sec
Thus, changing the higher range value also changes
2.0sec
the span.
4.0sec
• Calibration range can be specified with range value
8.0sec
specifications up to 5 digits (excluding any decimal 16.0sec
32.0sec
point) for low or high range limits within the range 64.0sec
of –32000 to 32000.
F0815.EPS

Note1: The damping time constant set here is the damping time
constant for the amplifier assembly. The damping time
constant for the entire transmitter is the sum of the values for
the amplifier assembly and for the capsule assembly. For the
capsule assembly damping time constant (fixed), see the
“General Specifications” found at the end of this manual.
(See Chapter 10.)

When optional code /F1 is specified, the default value is set


at 0.1 seconds.

8-8 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

(4) Output Signal Low Cut Mode Setup (5) Change Output Limits
(D10: LOW CUT, D11: LOW CUT MODE) (D15:OUT LIMIT(L), D16:OUT LIMIT(H))
Low cut mode can be used to stabilize the output The range of normal output is preset at factory from
signal near the zero point. The low cut point can be -5.0 to 110.0% unless otherwise specified, and the
set in a range from 0 to 20% of output. (Hysteresis of output is limited with these upper and lower values.
cut point: ±1%) This output range can be changed, for example, to
meet the requirements of NAMUR, etc. within the
Select “ZERO” as the low cut mode.
settable range. Set the lower limit with D15:OUT
LIMIT(L) and upper limit with D16:OUT LIMIT(H).
 LOW CUT mode ZERO at 10%
Settable range : -5.0 to 110.0 (%)
Lower limit < Upper limit
50
(6) Integral Indicator Scale Setup
Output(%) The following 5 displays are available for integral
indicators.
10
D20: DISP SELECT Description
and Display and Related parameters
0 10 50
Input(%) NORMAL % Indicates –5 to 110% range
F0816.EPS depending on the Measurement
range (C21, C22).
A10:OUTPUT (%)
• Example: Change the low cut setting range 45.6 %
from 5% to 10%, and the low USER SET Indicates values depending on the
cut mode from LINEAR to ZERO. Engineering range (D22, D23).(Note 1)
Units set using Engineering unit
SET Set “10.” (D21) are not indicated.
D10:LOW CUT
5.0 %
+ 10.0 Press the key twice to
A11:ENGR.OUTPUT
enter the setting. 20.0 M
CLR ESC
USER & % Indicates user set and % alternately
SET Press the (OK) key. in 3 second intervals.
D10:LOW CUT
10.0 %
Next, the [D11: LOW CUT MODE] A10:OUTPUT (%)
45.6 %
setting panel is displayed.
A11:ENGR. OUTPUT
FEED NO OK
20.0 M
SET Use the or key INP PRES Indicates input pressure.(Note 2)
D11:LOW CUT MODE
LINEAR Indication limits –19999 to 19999.
< LINEAR > to select ZERO.
< ZERO >
Press the key twice to A40:INPUT
ESC
enter the setting. 456 kPa

SET Press the (OK) key. PRES & % Indicates input pressure and %
D11:LOW CUT MODE
ZERO alternately in 3 second intervals.

A10:OUTPUT (%)
45.6 %
FEED NO OK
A40:INPUT
PARAM 456 kPa
D10:LOW CUT
10.0 %
D11:LOW CUT MODE (Note 1) Scale range can be specified with range limit specifications up
ZERO to 5 digits (excluding any decimal point) for low or high range
D20:DISP SELECT
NORMAL % limits within the range of –19999 to 19999.
DATA DIAG PRNT ESC
The range with decimals is available to the third decimal place.
(Note 2) It indicates the value after zeroing.
F0817.EPS
T0808.EPS

See (a.) through (c.) for each setting procedure.

8-9 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

b. Setting User-set Engineering Unit


% indication and User-set engineering (D21: DISP UNIT)
input pressure unit display
This parameter allows entry of the engineering units
indication
to be displayed on the BT200. When the instrument
D20: DISP SELECT D20: DISP SELECT is shipped, this is set as specified in the order.
NORMAL % USER SET
INP PRES USER & % Follow the procedure below to change this setting.
PRES & %
This parameter need not be set for % display.
Set for user-set
Transmitter is set engineering unit display. • Example: Set an engineering unit M.
for “% display” when
SET Set “M.”
shipped. D21:DISP UNIT
D21: DISP UNIT M_ Press the key twice to
Set a unit to be enter the setting.
displayed on the BT200. CODE CAPS CLR ESC

SET Press the (OK) key.


D21:DISP UNIT
M
D22: DISP LRV
Set a numeric value for
engineering unit for 4 mA FEED NO OK
output (LRV).
F0820.EPS

c. Lower and Higher Range Value Setup


D23: DISP HRV in Engineering Unit (D22: DISP LRV,
Set a numeric value for D23: DISP HRV)
engineering unit for 20 mA
These parameter items are used to set the lower and
output (HRV).
F0818.EPS
higher range values for the engineering unit display.
When the instrument is shipped, these are set as
a. Display Selection (D20: DISP SELECT) specified in the order. Follow the procedure below to
Follow the instructions given to the below to change change these settings. Note that these parameters
the range of integral indication scales. need not be set for % display.
When USER SET is selected, the user set values of
integral indication and A11: ENGR. OUTPUT • Example: Set lower range value (LRV) to –50
parameter are indicated. and higher range value (HRV) to 50.
Setting LRV
SET Set “–50.”
D22:DISP LRV
0M
Press the key twice to
• Example: Set the integral indicator scale to - 50

engineering units display. enter the setting.


DEL CLR ESC
SET Use the or key
D20:DISP SELECT
NORMAL % Setting HRV
<NORMAL %> to select “USER SET.”
<USER SET>
SET Set “50.”
D23:DISP HRV
<USER & %> Press the key twice to 100M
<INP PRES> + 50 Press the key twice to
ESC enter the setting.
enter the setting.
SET DEL CLR ESC
D20:DISP SELECT Press the (OK) key.
USER SET
SET Press the (OK) key.
D23:DISP HRV
50M
FEED NO OK

FEED NO OK
The “%” disappears from the
PARAM
integral indicator display. D21:DISP UNT
M
D22:DISP LRV
– 50M
D23:DISP HRV
F0819.EPS 50M
DATA DIAG PRNT ESC

F0821.EPS

8-10 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

(7) Unit Setup for Displayed Temperature (9) Output Status Display/Setup when a CPU
(D30: TEMP UNIT) Failure (D52: BURN OUT)
When the instrument is shipped, the temperature units This parameter displays the status of 4 to 20 mA DC
are set to degC. Follow the procedure below to output if a CPU failure occurs. In case of a failure,
change this setting. Note that changing the unit here communication is disabled.
changes the unit for A20: AMP TEMP (amplifier
Setting of HIGH or LOW is enabled. This is done
temperature) and A21: CAPSULE TEMP (capsule
with the pin (CN4) on the CPU assembly. See
temperature).
Chapter 3 for details.
Standard specifications
• Example: Change the unit for the temperature The parameter is set to HIGH. If a failure, the
display. transmitter outputs the signal of 110% or higher. The
SET Use the or key to parameter D53: ERROR OUT is set to HIGH from
D30:TEMP UNIT
deg C
< deg C > select “deg F.” the factory.
< deg F >
Press the key twice to Optional code/C1
ESC
enter the setting. The parameter is set to LOW. If a failure, output
F0822.EPS which is –5%*1 or lower is generated. The parameter
D53: ERROR OUT is set to LOW from the factory.
(8) Operation Mode Setup
*1 : When optional code /F1 is specified, substitute the value with
(D40: REV OUTPUT) –5 with –2.5.
This parameter allows the direction of the 4 to 20
mA output to be reversed with respect to input.
• Example: Standard specifications
Follow the procedure below to make this change.
D52: BURN OUT pin (CN4) position: H
HIGH
• Example: Change 4 to 20 mA output to 20 to
4 mA output. • Example: Optional code/C1
SET Use the or key D52: BURN OUT pin (CN4) position: L
D40:REV OUTPUT
NORMAL LOW
< NORMAL > to select REVERSE.
< REVERSE>
Press the key twice to F0824.EPS
ESC
enter the setting.
(10) Output Status Setup when a Hardware
F0823.EPS
Error Occurs (D53: ERROR OUT)
This parameter allows the setting of the output status
when a hardware error occurs. The following three
selections are available.
(a) HOLD; Outputs the last value held before the
error occurred.
(b) HIGH; Outputs an output of 110% when an error
has occurred.
(c) LOW; Outputs an output of –5%*1 when an error
has occurred.
Note: A hardware error means CAP MODULE FAULT of Er.01 or
AMP MODULE FAULT of Er. 02 which are shown in 8.5.2
“Errors and Countermeasures.”)
*1 : When optional code /F1 is specified, substitute the value with
–5 with –2.5.

• Example: Set the output status to LOW when


a hardware error occurs.
SET
D53:ERROR OUT Use the or key
HIGH
< HIGH> to select “LOW.”
< LOW>
< HOLD>
Press the key twice to
ESC
enter the setting.
F0825.EPS

8-11 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

(11) Range Change while Applying Actual Note that changing the higher range value does not
Inputs (H10: AUTO LRV, H11: AUTO cause the lower range value to change but does
HRV)
change the span.
This feature allows the lower and higher range values
to be set up automatically with the actual input
applied. If the lower and higher range values are set, • Example 2: When the higher range value is to
C21: LOW RANGE and C22: HIGH RANGE are be changed to 10 kPa with the
changed at this same time. present setting of 0 to 30 kPa, take
the following action with an input
Follow the procedure in the figure below. pressure of 10 kPa applied.
The measurement span is determined by the higher
SET
and lower range values. Changing the lower range H11:AUTO HRV
Press the key twice.
30 kPa
value results in the higher range value changing auto- + 30 The higher range value is changed
matically, keeping the span constant. to 10 kPa.
ESC

SET Press the (OK) key.


• Example 1: When changing the lower range H11:AUTO HRV
10.000 kPa
value to 0.5 kPa for the present
setting of 0 to 30 kPa, take the
FEED NO OK
following action with input pressure
of 0.5 kPa applied. PARAM The lower range value is not
H10:AUTO LRV
0 kPa
H11:AUTO HRV changed, so the span changes.
10.000 kPa
SET Press the key twice.
H10:AUTO LRV
H60:SELF CHECK Parameter C22 is changed at the
GOOD
0 kPa DATA DIAG PRNT ESC
+ 0 The lower range value is changed same time.
to 0.5 kPa. F0827.EPS
ESC

SET Press the (OK) key.


H10:AUTO LRV
0.5000 kPa (12) Zero Point Adjustment
(J10: ZERO ADJ, J11: ZERO DEV,
J20: EXT ZERO ADJ)
FEED NO OK
The DPharp supports several adjustment methods.
PARAM The higher range value is changed
H10:AUTO LRV Select the method best suited for the conditions of
0.5000 kPa
H11:AUTO HRV keeping the span constant. your application.
30.500 kPa
H60:SELF CHEC
GOOD
Parameters C21 and C22 are Note that output signal can be checked by displaying
DATA DIAG PRNT ESC
changed at the same time. parameter A10:OUTPUT (%) on the BT200.
F0826.EPS

Adjustment Method Description


Using the BT200 Set the present input to 0%.
Adjust for 0% output at input level of
0%.
Adjust output to the reference value
obtained using other means.
If the input level cannot easily be
made 0% (because of tank level,
etc.), adjust output to the reference
value obtained using other means,
such as a sight glass.
Using the external Adjust zero point using the zero-
zero-adjustment adjustment screw on the transmitter.
screw This permits zero adjustment without
using the BT200. Accurately adjust
the output current to 4 mA DC or
other target output value using an
ammeter that accuratly reads output
currents.
T0809.EPS

8-12 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

(a) Follow the procedure below when setting the (b)-2 Follow the procedure below to use J11: ZERO
present output to 0% (4 mA). DEV.

Output is 0.5%. A10:OUTPUT (%)


Present output is 41.0%.
A10:OUTPUT (%) 41.0 %
0.5 % Output error = 40.0 – 41.0 = –1.0%.

SET Since “J11: ZERO DEV.” contains


SET
J10:ZERO ADJ Press the key twice. J11:ZERO DEV.
2.50 %
0.0 % 0 the previous correction, obtain the
+ 000.0
correction value by adding –1.0% to
ESC
CLR ESC it. 2.50% + (–1.0%) = 1.50%

SET
J10:ZERO ADJ Zero adjustment is completed. SET Set the correction value, 1.50.
J11:ZERO DEV.
0.0 % 2.50 %
Press the (OK) key. 1.50 Press the key twice.

FEED NO OK ECS

A10:OUTPUT (%) Output is 0%. A10:OUTPUT (%) The output is changed to 40%.
0.0 % 40.0 %

F0830.EPS
F0828.EPS

(b) In tank level measurement, if the actual level When the zero point is adjusted, the displayed value
cannot be brought to zero for zero adjustment, of A40 is as follows.
then the output can be adjusted to correspond to
the actual level obtained using another measuring [Example]
instrument such as a glass gauge. When the zero point is shifted by 20 kPa for the
actual pressure, the parameter of A40 indicates 50
[Example] kPa.
Measurement range: 50 to 250 kPa, Actual value:
130 kPa.
70 kPa
Actual value 50 kPa
Actual = –Measurement range lower range value
x 100
value(%) Measurement range higher range value
–Measurement range lower range value Zero
20 kPa adjustment
Zero adjustment
130–50 volume(J11)
0 kPa 0 kPa
= x 100=40.0%
250–50 Actual differential Input value
pressure/pressure of A40 F0839.EPS

(b)-1 Follow the procedure below to use J10: ZERO


ADJ.

A10:OUTPUT (%)
Present output is 41.0%.
41.0 %

SET Enter the present actual level, 40%.


J10:ZERO ADJ
0.0 %
+ 040.0 Press the key twice.

CLR ESC

A10:OUTPUT (%) The output is changed to 40%.


40.0 %

F0829.EPS

8-13 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

(c) Zero Point Adjustment Using the External Zero You can manually perform the trimming procedure
Adjustment Screw by using J15: SPAN ADJ.
• Enabling/inhibiting of zero point adjustment using • Span adjustment value
the external zero-adjustment screw on the transmitter The span adjustment value is calculated as follows.
(J20: EXT ZERO ADJ)
Follow the procedure below to enable or inhibit zero Span adjustment value (%) = P1  A40 100
P1
point adjustment from the zero-adjustment screw on
P1: Actual differential pressure/pressure value
the transmitter.
A40: Input (indicated as the value after zeroing)
This is set to “ENABLE” when the instrument is
shipped. Measurement pressure

• Example: Inhibiting zero adjustment by the


external zero-adjustment screw A40

SET Use the or key to


J20:EXIT ZERO ADJ
ENABLE
< ENABLE > select “INHIBIT.” Applied pressure
< INHIBIT> P1
Press the key twice to 0 F0846.EPS

ESC
enter the setting.
F0831.EPS

• Zero point adjustment using external zero-adjust-


ment screw on the transmitter • Example: For the range of 0 to 30 kPa.
A40: INPUT = 30.15 kPa
Turn the zero-adjustment screw on the outside of the J15: SPAN ADJ = 0.15 %
transmitter case using a slotted screwdriver. Turn the
screw to the right to increase the zero point or to the Suppose that a standard pressure of 30 kPa is applied and
the value of the parameter of A40: INPUT is 30.15 kPa.
left to decrease the zero output; the zero adjusts in Firstly, obtain the slope error for the span as follows;
increments of 0.01% of the range setting.
Note that the amount of adjustment to the zero point P1  A40
Span adjustment value (%) = 100
P1
changes according to the speed at which the screw is
turned. To make fine adjustments, turn the screw 30.0030.15
  100 = 0.5 (%)
30.00
slowly; to make coarse adjustments, turn the screw
quickly. Add 0.5% to 0.15% of the current value to calculate the
accumulated span adjustment value.
Note: When a zero point adjustment has been made, do not turn
0.15  (0.50) = 0.35
off the transmitter less than 30 seconds after adjustment.

SET
J15:SPAN ADJ
Set 0.35.
0.15 %
(13) Span Adjustment - 0.35 Press key twice.
Each DPharp EJA series transmitter is factory
DEL CLR ESC
characterized according to the specification. Mount-
ing position effects or zero shifts caused by static SET
J15:SPAN ADJ
Press the (OK) key.
-0.35 %
pressure are typically compensated by a zero adjust-
ment.
FEED NO OK
A span adjustment is a function to correct the slope
error from a zero point in characterizing 100% point Note: Enter 0.00 to J15: SPAN ADJ to reset the
(HRV). This function can be used when span drifts span adjustment to the initial value at the
may be caused or characterization to the specific shipment.
pressure standard is required.
F0847.EPS

Therefore, the zero point adjustment should always


be performed before the upper point adjustment in
order to maintain the pitch between zero and 100%
points within the calibration range.

8-14 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

(14) Test Output Setup (K10: OUTPUT X%) 8.4 Displaying Data Using the
This feature can be used to output a fixed current BT200
from 3.2 mA (–5%) to 21.6 mA (110%) for loop
checks. 8.4.1 Displaying Measured Data
Note: When optional code /F1 is specified, output range is from
The BT200 can be used to display measured data.
3.6mA(–2.5%) to 21.6mA(110%).
The measured data is updated automatically every 7
• Example: Output 12 mA (50%) fixed current. seconds. In addition, the display can be updated to
the present data value at any time by pressing the
SET Set “50.0%.”
K10:OUTPUT X % (DATA) key. For parameters associated with the
0.0 %
+ 050.0 Press the key twice to display of measured data, see Subsection 8.3.1,
output a fixed current at 50%. “Parameter Summary.”
ESC

SET “Active” is displayed while this is


K10:OUTPUT X %
50.0 % ACTIVE • Example: Display output.
being executed.
MENU
Press the (OK) key to cancel A:DISPLAY
FEED NO OK B:SENSOR TYPE
the fixed current output.

F0832.EPS
HOME SET ADJ ESC

PARAM Display “A10: OUTPUT (%).”


A10:OUTPUT (%)
XX.X %
IMPORTANT A11:ENGR.OUTPUT
YY.Y %
A20:AMP TEMP
ZZ deg C
1. Test output is held for approximately 10 DATA DIAG PRNT ESC
Data is updated automatically
minutes, and then released automatically after at 7-second intervals.
PARAM communi
the time has elapsed. Even if the BT200 A10:OUTPUT (%)

power supply is turned off or the communica- A11:ENGR.OUTPUT

A20:AMP TEMP
tion cable is disconnected during test output,
it is held for approximately 10 minutes.
2. Press the (OK) key to release test output F0834.EPS

immediately.
8.4.2 Display Transmitter Model and
Specifications
(15) User Memo Fields (M: MEMO) The BT200 can be used to display the model and
This feature provides 5 user memo fields, each specifications of the transmitter.
holding up to 8 alphanumeric characters. Up to 5
items such as inspection date, inspector, and other
• Example: View transmitter model name.
information can be saved in these fields.
MENU Press .
A:DISPLAY
B:SENSOR TYPE
• Example: Save an inspection date of January
30, 1995.
HOME SET ADJ ESC
PARAM Set “95.1.30” in the order of year,
M10:MEMO 1

M20:MEMO 2 month, and day.


M30:MEMO 3 Press the key twice to
DATA DIAG PRNT ESC
enter the setting. PARAM
SET B10:MODEL For the associated
M10:MEMO 1 EJA430-DA parameters, see Subsection
95.1.30_
B11:STYLE NO. 8.3.1, Parameter Summary.
S1.01
B20:LRL
– 98.07 kPa
ESC
DATA DIAG PRNT ESC

F0833.EPS
F0835.EPS

8-15 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

8.5 Self-Diagnostics • Example 3: Checking the history of the errors


8.5.1 Checking for Problems MENU
J:ADJUST
Connect the BT200 to the
K:TEST transmitter, and call item “P.”
M:MEMO
(1) Identifying Problems with BT200 P:RECORD

The following four areas can be checked. HOME SET ADJ ESC

(a) Whether connections are good. PARAM


P10:ERROR REC 1
(b) Whether BT200 was properly operated. ERROR
P11:ERROR REC 2
(c) Whether settings were properly entered. ERROR
P12:ERROR REC 3
(d) History of the errors. GOOD
DATA DIAG PRNT ESC
See examples below.
P10: “ERROR REC 1” displays the last error.
P11: “ERROR REC 2” displays the error one time before
• Example 1: Connection errors
the last error occurred.
––WELCOME–– Press the key. P12: “ERROR REC 3” displays the error two times before
BRAIN TERMINAL
ID: BT200
When the panel shown on the left the last error occurred.
check connection
push ENTER key appears, press the key. P13: “ERROR REC 4” displays the error three times before
UTIL FEED the last error occurred.

Since communications will be The history of up to four errors can be stored. When the 5th
unsuccessful if there is a problem error has occurred, it is stored in “P10”. The error stored in
communication error
“P13” will be deleted, and then, the error in “P12” will be
in the connection to the BT200, the
copied to “P13”. In this sequence, the history of the most
ESC display at the left will appear.
previously occurred error will be removed from memory.
Recheck the connection. “GOOD” will be displayed if there was no previous error.
Press the (OK) key.
SET Select P10: ERROR REC1 and
P10:ERROR REC 1
ERROR press the key to display
< ERROR >
< ILLEGAL LRV > the error message.
• Example 2: Setting entry errors < ILLEGAL HRV >

ESC
PARAM The initial data panel shows the
01:MODEL
EJA430-DA <(a) SETUP PANEL>
02:TAG NO. result of current transmitter
YOKOGAWA
03:SELF CHECK diagnostics. For the details of the messages listed below, see Table
ERROR
OK 8.5.1 Error Message Summary.

PARAM Press the (DIAG) key in the


C20:PRESS UNIT CAP MODULE FAULT OVER TEMP (CAP) ILLEGAL LRV
kPa
C21:LOW RANGE parameter panel to go to the AMP MODULE FAULT OVER TEMP (AMP) ILLEGAL HRV
600 kPa
C22:HIGH RANGE diagnostics panel OUT OF RANGE OVER OUTPUT ILLEGAL SPAN
600 kPa
DATA DIAG PRNT ESC OUT OF SP RANGE OVER DISPLAY ZERO ADJ OVER
(C60: SELF CHECK).
DIAG An error message is displayed Note 1: Press the key twice in the setting panel
C60:SELF CHECK
ERROR
< ERROR > when an error occurs in the (panel 1) to clear all error message (P10 to P13)
< ILLEGAL LRV >
diagnostics panel. information.
FEED PRNT ESC Note 2: After two hours from when an error occurs, the error
message of that error will be recorded. Therefore,
F0836.EPS if you switch off the transmitter within two hours from
when the error occurs, there is no history of that
error stored in the transmitter, and this function is
meaningless.
F0837.EPS

8-16 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

(2) Checking with Integral Indicator

NOTE

If an error is detected in the self-diagnostic, an


error number is displayed on the integral
indicator. If there is more than one error, the
error number changes at two-second intervals.
See Table 8.5.1 regarding the error numbers.

F0838.EPS

Figure 8.5.1 Identifying Problems Using the Integral


Indicator

8-17 IM 01C22D01-01E
8. BRAIN TERMINAL BT200 OPERATION

8.5.2 Errors and Countermeasures


The table below shows a summary of error messages.
Table 8.5.1 Error Message Summary

Integral
Output Operation
Indicator BT200 Display Cause Countermeasure
during Error
Display
None GOOD
---- ERROR
Er. 01 CAP MODULE Capsule problem.*1 Outputs the signal Replace the capsule
FAULT (Hold, High, or Low) when error keeps
set with parameter appearing even after
D53. restart.*2

Er. 02 AMP MODULE Amplifier problem. Outputs the signal Replace amplifier.
FAULT (Hold, High, or Low)
set with parameter
D53.
Er. 03 OUT OF RANGE Input is outside Outputs high range Check input.
measurement range limit value or low
limit of capsule. range limit value.
Er. 04 OUT OF SP Static pressure Displays present Check line pressure
RANGE exceeds specified output. (static pressure).
range.*3
Er. 05 OVER TEMP Capsule temperature Displays present Use heat insulation or
(CAP) is outside range output. make lagging to keep
(–50 to 130°C). temperature within
range.
Er. 06 OVER TEMP Amplifier temperature Displays present Use heat insulation or
(AMP) is outside range output. make lagging to keep
(–50 to 95°C). temperature within
range.
Er. 07 OVER OUTPUT Output is outside high Outputs high or low Check input and range
or low range limit range limit value. setting, and change
value. them as needed.
Er. 08 OVER DISPLAY Displayed value is Displays high or low Check input and
outside high or low range limit value. display conditions and
range limit value. modify them as
needed.
Er. 09 ILLEGAL LRV LRV is outside setting Holds output Check LRV and
range. immediately before modify as needed.
error occurrence.
Er. 10 ILLEGAL HRV HRV is outside setting Holds output Check HRV and
range. immediately before modify as needed.
error occurrence.
Er. 11 ILLEGAL SPAN SPAN is outside Holds output Check SPAN and
setting range. immediately before change as needed.
error occurrence.
Er. 12 ZERO ADJ OVER Zero adjustment is too Displays present Readjust zero point.
large. output.
*1: This error code appears at a capsule problem or when an illegal overpressure is applied to the
pressure sensor.
*2: If the normal pressure is regained, the Er.01 will disappear according to the setting of the parameter
of E50: AUTO RECOVER. When the E50: AUTO RECOVER is set to ON(defalut setting), the Er.01
will disappear automatically. When the E50: AUTO RECOVER is set to OFF, restart the transmitter
to cancel Er.01. If no error code appears then, perform necessary adjustment such as zero-adjust-
ment to continue the operation. If the error code still exists, replace the capsule assembly.
*3: For Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is
not a measured value.
T0811 .EPS

8-18 IM 01C22D01-01E
9. MAINTENANCE

9. MAINTENANCE

9.1 Overview 9.2 Calibration Instruments Se-


lection
WARNING Table 9.2.1 shows the instruments required for calibra-
tion. Select instruments that will enable the transmitter
Since the accumulated process fluid may be to be calibrated or adjusted to the required accuracy.
toxic or otherwise harmful, take appropriate care
to avoid contact with the body, or inhalation of The calibration instruments should be handled carefully
vapors during draining condensate or venting so as to maintain the specified accuracy.
gas in transmitter pressure-detector section and
even after dismounting the instrument from the
process line for maintenance.
9.3 Calibration
Use the procedure below to check instrument operation
Maintenance of the transmitter is easy due to its and accuracy during periodic maintenance or trouble-
modular construction. This chapter describes the shooting.
procedures for calibration, adjustment, and the disas- 1) Connect the instruments as shown in Figure 9.3.1
sembly and reassembly procedures required for and warm up the instruments for at least five
component replacement. minutes.
Since the transmitters are precision instruments,
carefully and thoroughly read the following sections IMPORTANT
for proper handling during maintenance.
• To adjust the transmitter for highest accuracy,
make adjustments with the power supply
IMPORTANT voltage and load resistance including leadwire
resistances set close to the conditions under
• As a rule, maintenance of this transmitter which the transmitter is installed.
should be implemented in a maintenance • If the measurement range 0% point is 0 kPa or
service shop where the necessary tools are shifted in the positive direction (suppressed
provided. zero), the reference pressure should be applied
• The CPU assembly contains sensitive parts as shown in the figure.
that may be damaged by static electricity. If the measurement range 0% point is shifted in
Exercise care so as not to directly touch the the negative direction (elevated zero), the
electronic parts or circuit patterns on the board, reference pressure should be applied using a
for example, by preventing static electrification vacuum pump.
by using grounded wrist straps when handling • Do not perform the calibration procedure until
the assembly. Also take precautions such as the transmitter is at room temperature.
placing a removed CPU assembly into a bag
with an antistatic coating.
2) Apply reference pressures of 0%, 50%, and 100% of
the measurement range to the transmitter. Calculate
the errors (differences between digital voltmeter
readings and reference pressures) as the pressure is
increased from 0% to 100% and is decreased from
100% to 0%, and confirm that the errors are within
the required accuracy.

9-1 IM 01C22D01-01E
9. MAINTENANCE

Table 9.2.1 Instruments Required for Calibration


Name Yokogawa-recommended Instrument Remarks
Power
supply Model SDBT or SDBS distributor 4 to 20 mA DC signal

Load Model 2792 standard resistor [250 Ω ±0.005%, 3 W]


resistor Load adjustment resistor [100 Ω ±1%, 1 W]
Model 2501 A digital multimeter
Voltmeter
Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)
Model MT220 precision digital manometer
1) For 10 kPa class
Accuracy: ±(0.015% of rdg + 0.015% of F.S.) . . . . . for 0 to 10 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . . for -10 to 0 kPa
2) For 130 kPa class
Accuracy: ±0.02% of rdg . . . . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa
±5digits .......................... for 0 to 25 kPa
Digital ±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . . for -80 to 0 kPa Select a manometer having
manometer 3) For 700 kPa class a pressure range close to
Accuracy: ±(0.02% of rdg + 3digits) . . . . . . . . . . . . . for 100 to 700 kPa that of the transmitter.
±5 digits ......................... for 0 to 100 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . . for -80 to 0 kPa
4) For 3000 kPa class
Accuracy: ±(0.02% of rdg + 10 digits) . . . . . . . . . . . for 0 to 3000 kPa
±(0.2% of rdg + 0.1% of F.S.) . . . . . . . . . for -80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ±(0.03% of rdg + 6 digits) . . . . . . . . . . . . for 0 to 130 kPa abs
Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, 25 kPa {2500 mmH2O} Requires air pressure
Accuracy: ±0.05% of F.S. supply.
Pressure
generator Dead weight gauge tester 25 kPa {2500mmH2O} Select the one having a
Accuracy: ±0.03% of setting pressure range close to
that of the transmitter.
Model 6919 pressure regulator (pressure pump) Prepare the vacuum pump
Pressure
Pressure range: 0 to 133 kPa {1000 mmHg} for negative pressure
source
ranges.
T0901.EPS

Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and management
procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1% level, there are
difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa representatives from which the
instrument was purchased or the nearest Yokogawa office.

Supply pressure Pressure source


Using pressure Using pressure
generator source with
manometer Model MT220
P Pressure generator P precision digital manometer
Reference pressure Reference pressure

Load resistance, Power Load resistance, Power


250 Ω supply 250 Ω supply
E E
Load Rc R Load Rc R
adjusting adjusting
resistance, V resistance, V
100 Ω Digital voltmeter 100 Ω Digital voltmeter

F0901.EPS

Figure 9.3.1 Instrument Connections

9-2 IM 01C22D01-01E
9. MAINTENANCE

9.4 Disassembly and Reassem- 9.4.1 Replacing the Integral Indicator

bly
CAUTION
This section describes procedures for disassembly and
reassembly for maintenance and component replace-
Cautions for TIIS Flameproof Type Transmit-
ment.
ters
Always turn OFF power and shut off and release Users are prohibited by law from modifying the
pressures before disassembly. Use proper tools for all construction of a flameproof type transmitter.
operations. Table 9.4.1 shows the tools required. This would invalidate the agency approval and
Table 9.4.1 Tools for Disassembly and Reassembly the transmitter’s use in such rated area.
Thus the user is prohibited from using a flame-
Tool Quantity Remarks
proof type transmitter with its integral indicator
Phillips screwdriver 1 JIS B4633, No. 2
Slotted screwdriver 1
removed, or from adding an integral indicator to
Allen wrenches 2 JIS B4648 a transmitter. If such modification is absolutely
One each, nominal 3 and required, contact Yokogawa.
5 mm Allen wrenches
Wrench 1 Width across flats, 17 mm
Torque wrench 1 This subsection describes the procedure for replacing
Adjustable wrench 1 an integral indicator. (See Figure 9.4.2)
Socket wrench 1 Width across flats, 16 mm
Socket driver 1 Width across flats, 5.5 mm  Removing the Integral Indicator
Tweezers 1
T0902.EPS
1) Remove the cover.
2) Supporting the integral indicator by hand, loosen its
two mounting screws.
CAUTION
3) Dismount the LCD board assembly from the CPU
Precautions for CENELEC, IECEx, and TIIS assembly.
Flameproof Type Transmitters When doing this, carefully pull the LCD board
• Flameproof type transmitters must be, as a assembly straight forward so as not to damage the
rule, removed to a non-hazardous area for connector pins between it and the CPU assembly.
maintenance and be disassembled and reas-
sembled to the original state. For details, see
“Installation and Operating Precautions for TIIS
Flameproof Equipment” later in this manual.
• On the flameproof type transmitters the two
covers are locked, each by an Allen head bolt
(shrouding bolt). When a shrouding bolt is
driven clockwise by an Allen wrench, it is going
in and cover lock is released, and then the
cover can be opened.
When a cover is closed it should be locked by a
shrouding bolt without fail. Tighten the shroud-
ing bolt to a torque of 0.7 N·m.

Shrouding Bolt

Shrouding Bolt

Figure 9.4 Shrouding Bolts

9-3 IM 01C22D01-01E
9. MAINTENANCE

 Attaching the Integral Indicator 9.4.2 Replacing the CPU Board Assembly
Integral indicator can be installed in the following three
This subsection describes the procedure for replacing
directions.
the CPU assembly. (See Figure 9.4.2)

 Removing the CPU Assembly


1) Remove the cover. If an integral indicator is
mounted, refer to Subsection 9.4.1 and remove the
indicator.
2) Turn the zero-adjustment screw to the position
(where the screw head slot is horizontal) as shown
F0910.EPS
in Figure 9.4.2.
Figure 9.4.1 Installation Direction of Indicator 3) Disconnect the output terminal cable (cable with
1) Align both the LCD board assembly and CPU brown connector at the end). When doing this,
assembly connectors and engage them. lightly press the side of the CPU assembly connec-
2) Insert and tighten the two mounting screws. tor and pull the cable connector to disengage.
3) Replace the cover. 4) Use a socket driver (width across flats, 5.5mm) to
loosen the two bosses.
Output terminal cable 5) Carefully pull the CPU assembly straight forward to
remove it.
6) Disconnect the flat cable (cable with black connec-
Press tor at the end) that connects the CPU assembly and
forward
the capsule.
LCD board
assembly
NOTE
Integral
indicator Be careful not to apply excessive force to the
CPU assembly when removing it.
Boss Flat cable
CPU assembly Zero-adjustment
Bracket screw pin
(for zero-adjustment  Mounting the CPU Assembly
screw pin)
1) Connect the flat cable (with black connector)
Cover Mounting
screw between the CPU assembly and the capsule.
2) Connect the output terminal cable (with brown
F0903.EPS
connector).
Figure 9.4.2 Removing and Attaching LCD Board Assem-
bly and CPU Assembly
NOTE

Make certain that the cables are free of pinching


between the case and the CPU assembly edge.

3) Align and engage the zero-adjustment screw pin


with the groove on the bracket on the CPU assem-
bly. Then insert the CPU board assembly straight
onto the post in the amplifier case.
4) Tighten the two bosses. If the transmitter is
equipped with an integral indicator, refer to Subsec-
tion 9.4.1 to mount the indicator.

9-4 IM 01C22D01-01E
9. MAINTENANCE

 Removing the Capsule Assembly


NOTE

Confirm that the zero-adjustment screw pin is


IMPORTANT
placed properly in the groove on the bracket
prior to tightening the two bosses. If it is not, the Exercise care as follows when cleaning the
zero-adjustment mechanism will be damaged. capsule assembly.
• Handle the capsule assembly with care, and be
especially careful not to damage or distort the
5) Replace the cover.
diaphragms that contact the process fluid.
• Do not use a chlorinated or acidic solution for
9.4.3 Cleaning and Replacing the Capsule cleaning.
Assembly • Rinse thoroughly with clean water after clean-
ing and dry thoroughly.
This subsection describes the procedures for cleaning
and replacing the capsule assembly. (See Figure 9.4.3.)
1) Remove the CPU assembly as shown in Subsection
9.4.2.
CAUTION 2) Remove the two Allen screws that connect the
transmitter section and pressure-detector section.
Cautions for Flameproof Type Transmitters 3) Separate the transmitter section and pressure-
Users are prohibited by law from modifying the detector section.
construction of a flameproof type transmitter. If 4) Remove the nuts from the four flange bolts.
you wish to replace the capsule assembly with 5) Hold the capsule assembly by hand and remove the
one of a different measurement range, contact cover flange.
Yokogawa. 6) Remove the capsule assembly.
The user is permitted, however, to replace a 7) Clean the capsule assembly or replace with a new
capsule assembly with another of the same one.
measurement range. When doing so, be sure to  Reassembling the Capsule Assembly
observe the following. 1) Insert the capsule assembly between the flange
• The replacement capsule assembly must have bolts, paying close attention to the relative positions
the same part number as the one being re- of the H (high pressure side) and L (low pressure
placed. side) marks on the capsule assembly.
• The section connecting the transmitter and Replace the two capsule gaskets with new gaskets.
capsule assembly is a critical element in 2) Install the cover flange on the high pressure side,
preservation of flameproof performance, and and use a torque wrench to tighten the four nuts
must be checked to verify that it is free of uniformly to a torque of 39 N·m {4kgf·m}.
dents, scratches, and other defects. 3) After the pressure-detector section has been reas-
• After completing maintenance, be sure to sembled, a leak test must be performed to verify
securely tighten the Allen screws that fasten that there are no pressure leaks.
the transmitter section and pressure-detector 4) Reattach the transmitter section to the pressure-
section together. detector section.
5) Tighten the two Allen screws. (Tighten the screws
to a torque of 5 N·m)
6) Install the CPU assembly according to Subsection
9.4.2.
7) After completing reassembly, adjust the zero point
and recheck the parameters.

9-5 IM 01C22D01-01E
9. MAINTENANCE

Pressure-detector section 9.5 Troubleshooting


Nut
If any abnormality appears in the measured values, use
Cover flange the troubleshooting flow chart below to isolate and
Allen screw remedy the problem. Since some problems have
complex causes, these flow charts may not identify all.
If you have difficulty isolating or correcting a problem,
contact Yokogawa service personnel.

9.5.1 Basic Troubleshooting


Capsule gasket
Flange bolt First determine whether the process variable is actually
abnormal or a problem exists in the measurement
system.
If the problem is in the measurement system, isolate
Tranamitter section the problem and decide what corrective action to take.
F0904.EPS
This transmitter is equipped with a self-diagnostic
Figure 9.4.3 Removing and Mounting the Pressure- function which will be useful in troubleshooting; see
detector Section
Section 8.5 for information on using this function.

: Areas where self-diagnostic offers support


9.4.4 Replacing the Process Connector
Gaskets
Abnormalities appear in measurement.
This subsection describes process connector gasket
replacement. (See Figure 9.4.4.)
(a) Loosen the two bolts, and remove the process YES Is process variable
itself abnormal?
connectors.
(b) Replace the process connector gaskets.
(c) Remount the process connectors. Tighten the bolts Inspect the NO
Measurement system problem
process system.
securely and uniformly with a torque of 39 to 49
N·m {4 to 5 kgf·m}, and verify that there are no
pressure leaks. Isolate problem in
measurement system.

Bolt

Process connector
YES Does problem exist in
Process connector gasket
receiving instrument?

NO
Inspect receiver.

Environmental conditions Transmitter itself

Check/correct
F0905.EPS Check transmitter.
environmental conditions.
Figure 9.4.4 Removing and Mounting the Process Operating conditions
Connector

Check/correct operating
conditions.
F0906.EPS

Figure 9.5.1 Basic Flow and Self-Diagnostics

9-6 IM 01C22D01-01E
9. MAINTENANCE

9.5.2 Troubleshooting Flow Charts Output travels beyond 0% or 100%.

The following sorts of symptoms indicate that transmitter


may not be operating properly. Connect BRAIN TERMINAL and check self-diagnostics.
Example : • There is no output signal.
• Output signal does not change even though
process variable is known to be varying.
• Output value is inconsistent with value
Does the self- YES
inferred for process variable.
diagnostic indicate problem
location?

Connect BRAIN TERMINAL and check self-diagnostics. NO Refer to error message summary in
Subsection 8.5.2 to take actions.

Does the self-diagnostic YES


indicate problem location? Is power supply NO
polarity correct?

NO Refer to error message summary in


Subsection 8.5.2 to take actions. YES Refer to Section 6.3 to check/correct
polarity at each terminal from power
supply to the terminal box.

Is power supply NO
polarity correct? Are valves opened or NO
closed correctly?

YES Refer to Section 6.3 to check/correct


polarity at each terminal from power YES Fully open tap and stop valves, and
supply to the terminal box. fully close drain valve.

Are power
NO
supply voltage and load
resistance correct? YES
Is there any pressure leak?

YES Refer to Section 6.6 for rated voltage


and load resistance. NO
Fix pressure leaks, paying particular
attention to connections for impulse
piping, pressure-detector section, etc.

Are valves opened or NO


closed correctly? Is zero point NO
adjusted correctly?

YES Fully open tap and stop valves, and


fully close drain valve. YES Adjust the zero point.

Contact Yokogawa service personnel.


YES F0908.EPS
Is there any pressure leak?

NO Fix pressure leaks, paying particular


attention to connections for impulse
piping,pressure-detector section, etc.

Is there
continuity through the NO
transmitter loop wiring?
Do the loop numbers
match?

Find/correct broken conductor or


YES
wiring error.

Contact Yokogawa service personnel.


F0907.EPS

9-7 IM 01C22D01-01E
9. MAINTENANCE

Large output error.

Connect BRAIN TERMINAL and check self-diagnostics.

Does the self- YES


diagnostic indicate problem
location?

NO Refer to error message summary in


Subsection 8.5.2 to take actions.

Are valves opened or NO


closed correctly?

YES Fully open tap and stop valves, and


fully close drain valve.

Is impulse piping NO
connected correctly?

YES Refer to individual model user manuals


and connect piping as appropriate for
the measurement purpose.

Are power supply NO


voltage and load resistance
correct?

YES Refer to Section 6.6 for rated voltage


and load resistance.

Is transmitter
installed where there is YES
marked variation in
temperature?

Provide lagging and/or cooling, or allow


NO adequate ventilation.

Were appropriate NO
instruments used for
calibration?

YES Refer to Section 9.2 when selecting


instruments for calibration.

NO
Is output adjusted correctly?

YES Adjust the output.

Contact Yokogawa service personnel.


F0909.EPS

9-8 IM 01C22D01-01E
10. GENERAL SPECIFICATIONS

10. GENERAL SPECIFICATIONS

10.1 Standard Specifications Failure Alarm:


Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more (standard)
Refer to IM 01C22T02-01E for Fieldbus communi-
Down-scale: –5%, 3.2 mA DC or less
cation type marked with “䉫”. –2.5%, 3.6 mA DC or less (Optional
code /F1)
䊉 Performance Specifications Note: Applicable for Output signal code D and E
See General Specifications sheet, GS 01C22D01-
Damping Time Constant (1st order):
00E and GS 01C22E01-00E.
The sum of the amplifier and capsule damping
䊉 Functional Specifications time constant must be used for the overall time
constant. Amp damping time constant is adjustable
Span & Range Limits from 0.2 to 64 seconds.
EJA310*: Capsule (Silicone Oil) L, M, A, and B
Measurement Time Constant (approx. sec) 0.2
psi mbar mmHg
Span MPa
and Range
(/D1) (/D3) (/D4) T1003.EPS

0.67 to 0.2 to Ambient Temperature Limits:


Span 6.7 to 100 5 to 75
10 kPa 2.95 inHg * Safety approval codes may affect limits.
L
0 to 0 to –40 to 85°C (–40 to 185°F),
Range 0 to 100 0 to 75
10 kPa 2.95 inHg –30 to 80°C (–22 to 176°F) with LCD Display
3.4 to 1 to
Span 34 to 1300 25 to 960 Process Temperature Limits:
130 kPa 38 inHg
M * Safety approval codes may affect limits.
0 to 0 to
Range 0 to 1300 0 to 960 Capsule M, A, and B
130 kPa 38 inHg
–40 to 120°C (–40 to 248°F)
0.6 to 0.6 to Capsule L
Span 0.06 to 3 8.6 to 430
30 bar 30 kgf/cm2
A –40 to 100°C (–40 to 212°F)
0 to
Range 0 to 3 0 to 430 0 to 30 bar Maximum Overpressure:
30 kgf/cm2
T1001.EPS See General Specifications sheet.
* The above units are in absolute terms.
EJA430: Working Pressure Limits (Silicone Oil)
Maximum Pressure Limit:
Measurement
Span MPa psi bar kgf/cm2 See ‘Model and Suffix Codes.’
and Range (/D1) (/D3) (/D4)
Span 0.06 to 3 8 to 430 0.6 to 30 0.6 to 30 Minimum Pressure Limit:
A Capsule Pressure
Range –0.1 to 3 –15 to 430 –1 to 30 –1 to 30
L, M, A (EJA310) See Figure 1.
Span 0.46 to 14 66 to 2000 4.6 to 140 4.6 to 140 A, B (EJA430) See GS 01C22E01-00E
B
Range –0.1 to 14 –15 to 2000 –1 to 140 –1 to 140
T1002.EPS
䊉 Installation
Zero Adjustment Limits: Supply & Load Requirements “䉫”:
Zero can be fully elevated or suppressed, within * Safety approvals can affect electrical requirements.
the Lower and Upper Range Limits of the capsule. See Section 6.6, ‘Power Supply Voltage and Load
Resistance.’
External Zero Adjustment “䉫”:
External zero is continuously adjustable with Supply Voltage “䉫”:
0.01% incremental resolution of span. Span may 10.5 to 42 V DC for general use and flameproof type
be adjusted locally using the digital indicator with 10.5 to 32 V DC for lightning protector (Optional code
range switch. /A)
10.5 to 30 V DC for intrinsically safe, Type n,
Output “䉫”: nonincendive, or non-sparking type
Two wire 4 to 20 mA DC output with digital 10.5 to 28 V DC for TIIS intrinsically safe type
communications, linear or square root program-
mable. BRAIN or HART FSK protocol are superim- EMC Conformity Standards “䉫”: ,
posed on the 4 to 20 mA signal. EN61326-1 Class A, Table 2 (For use in industrial
lications)
EN61326-2-3

10-1 IM 01C22D01-01E
10. GENERAL SPECIFICATIONS

Communication Requirements “䉫”: Non-wetted Parts Materials:


BRAIN Bolting;
Communication Distance; SCM435 or SUS630
Up to 2 km (1.25 miles) when using CEV polyethyl- Housing;
ene-insulated PVC-sheathed cables. Low copper cast-aluminum alloy with polyurethane
Communication distance varies depending on type paint (Munsell 0.6GY3.1/2.0)
of cable used. Degrees of Protection;
Load Capacitance; IP67, NEMA4X, JIS C0920 immersion proof
0.22 µF or less (see note) Cover O-rings;
Load Inductance; Buna-N
3.3 mH or less (see note) Data plate and tag;
Input Impedance of communicating device; SUS304 or SUS316 (option)
10 kΩ or more at 2.4 kHz. Fill Fluid;
Note: For general-use and Flameproof type. Silicone or Fluorinated oil (option)
For Intrinsically safe type, please refer to Weight:
‘Optional Specifications.’ 3.9 kg (8.6 lb) without mounting bracket or process
HART connector (EJA430)
Communication Distance; Connections:
Up to 1.5 km (1 mile) when using multiple twisted Refer to the ‘Model and Suffix Codes’ to specify
pair cables. Communication distance varies the process and electrical connection type.
depending on type of cable used.
Use the following formula to determine cable 100{750}
length for specific applications:
M and A capsule
65 x 106 (Cf + 10,000)
L= -
(R x C) C L capsule
Where: 10{75}
L = length in meters or feet
R = resistance in Ω (including barrier resistance)
2.7{20}
C = cable capacitance in pF/m or pF/ft Working
Cf = maximum shunt capacitance of receiving pressure Applicable range
kPa abs 1{7.5}
devices in pF/m or pF/ft
{mmHg abs}
䊉 Physical Specifications 0.46
{3.45}
Wetted Parts Materials: 0.13{1}
Diaphragm, Cover flange, Process connector and 0.1{0.75}
Drain/Vent Plug;
See ‘Model and Suffix Codes’
Capsule Gasket;
Teflon-coated SUS316L 0.013{0.1}
Process Connector Gasket; 0.01{0.075} -40 0 40 80 120 (248)
PTFE Teflon (-40) (32) (104) (176) 85
(185)
Process temperature °C(°F)
F1001.EPS

Figure 1. Working Pressure and Process Temperature

<Settings When Shipped “䉫”>


Tag Number As specified in order *1 Calibration Range
Lower Range Value As specified in order
Output Mode ‘Linear’
Calibration Range As specified in order
Display Mode ‘Linear’ Higher Range Value
Operation Mode ‘Normal’ unless otherwise specified in order Selected from mmH2O, mmAq, mmWG,
Calibration Range mmHg, Torr, Pa, hPa, kPa, MPa, mbar,
Damping Time ‘2 sec.’ Units bar, gf/cm2, kgf/cm2, inH2O, inHg, ftH2O,
Constant psi, or atm.(Only one unit can be specified)
T1004E.EPS
Note 1: If Tag No. is no more than 16 alphanumeric characters (including - and ·), it will be written into
the tag plate and amplifier memory settings.

10-2 IM 01C22D01-01E
10. GENERAL SPECIFICATIONS

10.2 Model and Suffix Codes


䊉 Model EJA310 [Style: S2]

Model Suffix Codes Description


EJA310 . . . . . . . . . . . . . . . . . . . . . Absolute pressure transmitter
Output Signal -D . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
-E . . . . . . . . . . . . . (Note 1) 4 to 20 mA DC with digital communication (HART protocol)
(Note 4)
-F . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol)
Measurement span L . . . . . . . . . . . . . . . . . . 0.67 to 10 kPa {5 to 75 mmHg}
(capsule) M . . . . . . . . . . . . . . . . . . 1.3 to 130 kPa {9.6 to 960 mmHg}
A . . . . . . . . . . . . . . . . . . 0.03 to 3 MPa {0.3 to 30 kgf/cm2}
Wetted parts material [Body] (Note 3) [Capsule] [Vent plug]
S . . . . . . . . . . . . . . . . . SCS14A SUS316L(Note 2) SUS316
Process connections 0 . . . . . . . . . . . . . . . . without process connector (Rc1/4 female on the cover flanges)
1 . . . . . . . . . . . . . . . . with Rc1/4 female process connector
2 . . . . . . . . . . . . . . . . with Rc1/2 female process connector
3 . . . . . . . . . . . . . . . . with 1/4 NPT female process connector
4 . . . . . . . . . . . . . . . . with 1/2 NPT female process connector
5 . . . . . . . . . . . . . . . . without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts material [Maximum working pressure]
(L capsule) (M capsule) (A capsule)
A . . . . . . . . . . . . . . SCM435 10 kPa abs 130 kPa abs 3 MPa abs
{75 mmHg abs} {960 mmHg abs} {30 kgf/cm2 abs}
B . . . . . . . . . . . . . . SUS630 10 kPa abs 130 kPa abs 3 MPa abs
{75 mmHg abs} {960 mmHg abs} {30 kgf/cm2 abs}
Installation -2 . . . . . . . . . . . . . Vertical impulse piping type, right side high pressure, process connector upside
-3 . . . . . . . . . . . . . Vertical impulse piping type, right side high pressure, process connector downside
-6 . . . . . . . . . . . . . Vertical impulse piping type, left side high pressure, process connector upside
-7 . . . . . . . . . . . . . Vertical impulse piping type, left side high pressure, process connector downside
-8 . . . . . . . . . . . . . Horizontal impulse piping type, right side high pressure
-9 . . . . . . . . . . . . . Horizontal impulse piping type, left side high pressure
Electrical connection 0 . . . . . . . . . . . . G1/2 female, one electrical connection
2 . . . . . . . . . . . . 1/2 NPT female, two electrical connections without blind plug
3 . . . . . . . . . . . . Pg 13.5 female, two electrical connections without blind plug
4 . . . . . . . . . . . . M20 female, two electrical connections without blind plug
5 . . . . . . . . . . . . G1/2 female, two electrical connections and a blind plug
7 . . . . . . . . . . . . 1/2 NPT female, two electrical connections and a blind plug
8 . . . . . . . . . . . . Pg 13.5 female, two electrical connections and a blind plug
9 . . . . . . . . . . . . M20 female, two electrical connections and a blind plug
A . . . . . . . . . . . . G1/2 female, two electrical connections and a SUS316 blind plug
C . . . . . . . . . . . . 1/2 NPT female, two electrical connections and a SUS316 blind plug
Integral indicator D . . . . . . . . . . . Digital indicator
E . . . . . . . . . . . Digital indicator with the range setting switch
N . . . . . . . . . . . (None)
Mounting bracket A . . . . . . . . . SECC Carbon steel 2-inch pipe mounting (flat type)
B . . . . . . . . . SUS304 2-inch pipe mounting (flat type)
J . . . . . . . . . SUS316 2-inch pipe mounting (flat type)
C . . . . . . . . . SECC Carbon steel 2-inch pipe mounting (L type)
D . . . . . . . . . SUS304 2-inch pipe mounting (L type)
K . . . . . . . . . SUS316 2-inch pipe mounting (L type)
N . . . . . . . . . (None)
Optional codes /䊐 Optional specification
T1005.EPS
Example: EJA310-DMS5A-92NN/䊐
Note 1: Refer to IM 01C22T01-01E for HART Protocol version.
Note 2: Diaphragm; Hastelloy C-276. Other wetted parts materials; SUS316L.
Note 3: Body; Material of cover flanges and process connectors.
Note 4: Refer to IM 01C22T02-01E for Fieldbus communication.

10-3 IM 01C22D01-01E
10. GENERAL SPECIFICATIONS

䊉 Model EJA430 [Style: S2]

Model Suffix Codes Description


EJA430 ........................ Gauge pressure transmitter
Output Signal -D . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication (BRAIN protocol)
-E . . . . . . . . . . . . . . . . . (Note 1) 4 to 20 mA DC with digital communication (HART protocol)
-F . . . . . . . . . . . . . . . . . (Note 5) Digital communication (FOUNDATION Fieldbus protocol)
Measurement A..................... 0.06 to 3 MPa{0.6 to 30 kgf/cm2}
span(capsule) B..................... 0.46 to 14 MPa{4.6 to 140 kgf/cm2}
Wetted parts material [Body] (Note 4) [Capsule] [Vent plug]
S.................... SCS14A SUS316L (Note 2) SUS316
H.................... SCS14A Hastelloy C-276 (Note 3) SUS316
M.................... SCS14A Monel (Note 3) SUS316
T.................... SCS14A Tantalum (Note 3) SUS316
A.................... Hastelloy C-276 equivalent (Note 6) Hastelloy C-276 (Note 3) Hastelloy C-276
D.................... Hastelloy C-276 equivalent (Note 6) Tantalum (Note 3) Hastelloy C-276
B.................... Monel equivalent (Note 7) Monel Monel
Process connection 0................... without process connector (Rc1/4 female on the cover flanges)
1................... with Rc1/4 female process connector
2................... with Rc1/2 female process connector
3................... with 1/4 NPT female process connector
4................... with 1/2 NPT female process connector
5................... without process connector (1/4 NPT female on the cover flanges)
Bolts and nuts material [Maximum working pressure]
(A capsule) (B capsule)
A................. SCM435 3 MPa {30 kgf/cm2} 14 MPa {140 kgf/cm2}
B................. SUS630 3 MPa {30 kgf/cm2} 14 MPa {140 kgf/cm2}
Installation -2 . . . . . . . . . . . . . . . Vertical impulse piping type, right side high pressure, process connector upside
-3 . . . . . . . . . . . . . . . Vertical impulse piping type, right side high pressure, process connector downside
-6 . . . . . . . . . . . . . . . Vertical impulse piping type, left side high pressure, process connector upside
-7 . . . . . . . . . . . . . . . Vertical impulse piping type, left side high pressure, process connector downside
-8 . . . . . . . . . . . . . . . Horizontal impulse piping type, right side high pressure
-9 . . . . . . . . . . . . . . . Horizontal impulse piping type, left side high pressure
Electrical connection 0............... G1/2 female, one electrical connection
2............... 1/2 NPT female, two electrical connections without blind plug
3............... Pg 13.5 female, two electrical connections without blind plug
4............... M20 female, two electrical connections without blind plug
5............... G1/2 female, two electrical connections and a blind plug
7............... 1/2 NPT female, two electrical connections and a blind plug
8............... Pg 13.5 female, two electrical connections and a blind plug
9............... M20 female, two electrical connections and a blind plug
Integral indicator A............... G1/2 female, two electrical connections and a SUS316 blind plug
C............... 1/2 NPT female, two electrical connections and a SUS316 blind plug
D............. Digital indicator
Mounting bracket E............. Digital indicator with the range setting switch
N............. (None)
A............ SECC Carbon steel 2-inch pipe mounting (flat type)
B............ SUS304 2-inch pipe mounting (flat type)
J............ SUS316 2-inch pipe mounting (flat type)
Optional codes C............ SECC Carbon steel 2-inch pipe mounting (L type)
D............ SUS304 2-inch pipe mounting (L type)
K............ SUS316 2-inch pipe mounting (L type)
N............ (None)
/䊐 Optional specification
T1006.EPS
Example: EJA430-DAS5A-92NN/䊐
Note 1: Refer to IM 01C22T01-01E for HART Protocol version.
Note 2: Diaphragm; Hastelloy C-276. Other wetted parts materials; SUS316L.
Note 3: Diaphragm and other wetted parts.
Note 4: Body; Material of cover flanges and process connectors. Material of cover to atmosphere;
SCS14A.
Note 5: Refer to IM 01C22T02-01E for Fieldbus communication.
Note 6: Indicated material is equivalent to ASTM CW-12MW.
Note 7: Indicated material is equivalent to ASTM M35-2.
10-4 IM 01C22D01-01E
10. GENERAL SPECIFICATIONS

10.3 Optional Specifications


Item Description Code
FM Explosionproof Approval *1
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
Hazardous (classified) locations, indoors and outdoors (NEMA 4X) FF1
Division 2, ‘SEALS NOT REQUIRED’,
Temp. Class: T6
Amb. Temp.: –40 to 60⬚C (–40 to 140⬚F)
FM Intrinsically safe Approval *1
Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1,
Factory Mutual (FM) Groups E, F & G and Class III, Division 1 Hazardous Locations.
Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division. 2,
Groups E, F & G, and Class III, Division 1 Hazardous Locations.
Enclosure: “NEMA 4X”, Temp. Class: T4, Amb. Temp.: –40 to 60⬚C (–40 to 140⬚F) FS1
Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 ␮H
[Groups C, D, E, F and G]
Vmax=30 V, Imax=225 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 ␮H
Combined FF1 and FS1 *1 FU1
CENELEC ATEX (KEMA) Flameproof Approval *2
Certificate: KEMA 02ATEX2148
II 2G EExd IIC T4, T5, T6 KF2
Amb. Temp.: T5; –40 to 80⬚C ( –40 to 176⬚F), T4 and T6; –40 to 75⬚C ( –40 to 167⬚F)
Max. process Temp.: T4; 120⬚C (248⬚F), T5; 100⬚C (212⬚F), T6; 85⬚C (185⬚F)
CENELEC ATEX (KEMA) Intrinsically safe Approval *2
Certificate: KEMA 02ATEX1030X
II 1G EEx ia IIC T4, Amb. Temp.: –40 to 60⬚C (–40 to 140⬚F) KS2
CENELEC ATEX
Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 ␮H
Combined KF2, KS2 and Type n *2
Type n
II 3G Ex nL IIC T4, Amb. Temp.: –40 to 60°C (–40 to 140°F)
Ui=30 V DC, Ci=22.5 nF, Li=730 µH KU2
Dust
II 1D maximum surface temperature T65°C (149⬚F) {Tamb.: 40°C (104⬚F)},
T85°C (185⬚F) {Tamb.: 60°C (140⬚F)}, T105°C (221⬚F) {Tamb.: 80°C (176⬚F)}
T1007.EPS
*1: Applicable for Electrical connection code 2 and 7 (1/2 NPT female).
*2: Applicable for Electrical connection code 2, 4, 7 and 9 (1/2 NPT and M20 female).

10-5 IM 01C22D01-01E
10. GENERAL SPECIFICATIONS

Item Description Code


CSA Explosionproof Approval *1
Certificate: 1089598
Explosionproof for Class I, Division 1, Groups B, C and D
Dustignitionproof for Class II/III, Division 1, Groups E, F and G
Division2 ‘SEALS NOT REQUIRED’ , Temp. Class: T4, T5, T6 Encl Type 4x CF1
Max. Process Temp.: T4; 120⬚C (248⬚F), T5; 100⬚C (212⬚F), T6; 85⬚C (185⬚F)
Amb. Temp.: –40 to 80⬚C (–40 to 176⬚F)
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required. Primary seal failure annunciation: at the zero adjustment
screw
Canadian Standards
Association (CSA) CSA Intrinsically safe Approval *1
Certificate: 1053843
Intrinsically Safe for Class I, Groups A, B, C and D Class II and III, Groups E, F and G
Nonincendive for Class I, Division 2, Groups A, B, C and D Class II, Division 2,
Groups F and G and Class III (not use Safety Barrier)
Encl Type 4x, Temp. Class: T4, Amb. Temp.: –40 to 60⬚C (–40 to 140⬚F) CS1
Vmax=30 V, Imax=165 mA, Pmax=0.9 W, Ci=22.5 nF, Li=730 ␮H
Process Sealing Certification
Dual Seal Certified by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required. Primary seal failure annunciation: at the zero adjustment
screw
Combined CF1 and CS1 *1 CU1
IECEx Intrinsically safe, type n and FlameproofApproval *2
Intrinsically safe and type n
Certificate: IECEx KEM 06.0007X
Ex ia IIC T4, Ex nL IIC T4 Enclosure: IP67
Amb. Temp.: –40 to 60⬚C (–40 to 140⬚F), Max. Process Temp.: 120⬚C (248⬚F)
Electrical Parameters: [Ex ia] Ui=30 V, Ii=165 mA, Pi=0.9 W, Ci=22.5 nF, Li=730 ␮H
IECEx
[Ex nL] Ui=30 V, Ci=22.5 nF, Li=730 ␮H SU2
Scheme
Flameproof
Certificate: IECEx KEM 06.0005
Ex d IIC T6...T4 Enclosure: IP67
Max.Process Temp.: T4;120⬚C (248⬚F), T5;100⬚C (212⬚F), T6; 85⬚C (185⬚F)
Amb.Temp.: –40 to 75⬚C (–40 to 167⬚F) for T4, –40 to 80⬚C (–40 to 176⬚F) for T5,
–40 to 75⬚C (–40 to 167⬚F) for T6
TIIS Flameproof Approval, Ex do IIC T4X *3
JF3
Amb. Temp.: –20 to 60⬚C, Process Temp.: –20 to 120⬚C
TIIS certification TIIS Intrinsically safe Approval, Ex ia IIC T4
Certificate: C14632 JS3
Amb. Temp.: –20 to 60⬚C, Process Temp.: –20 to 120⬚C
Attached flameproof Electrical connection: G1/2 female 1 pc. G11
packing adapter Applicable cable: O. D. 8 to 12 mm 2 pcs. G12
T1009.EPS
*1: Applicable for Electrical connection code 2 and 7 (1/2 NPT female).
*2: Applicable for Electrical connection code 2, 4 and 7 (1/2 NPT and M20 female).
*3: See certificate list of TIIS flameproof Approval below.

Without integral indicator Without integral indicator


S C15296 C15297

Wetted parts H, A C15298 C15299


material code T, D C15300 C15301
M, B C05302 C05303
T1010.EPS

10-6 IM 01C22D01-01E
10. GENERAL SPECIFICATIONS

Item Description Code


Amplifier cover only P䊐
Color change
Painting Amplifier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Epoxy resin-baked coating X1
Exterior parts on the amplifier housing (name plates, tag plate, zero-adjustment screw,
316 SST exterior parts HC
stopper screw) will become 316 or 316L SST.
Transmitter power supply voltage: 10.5 to 32 V DC (10.5 to 30 V DC for intrinsically
safe type, 9 to 32 V DC for Fieldbus communication type.) A
Lightning protector
Allowable current: Max. 6000 A (1⫻40 µs), Repeating 1000 A (1⫻40 µs) 100 times
Degrease cleansing treatment K1
Oil-prohibited use Degrease cleansing treatment with fluorinated oil filled capsule.
Operating temperature –20 to 80 ⬚C K2

Degrease cleansing and dehydrating treatment K5


Oil-prohibited use
with dehydrating treatment Degrease cleansing and dehydrating treatment with fluorinated oilfilled capsule.
Operating temperature –20 to 80 ⬚C K6

P calibration (psi unit) D1


(See Table for Span
Calibration units bar calibration (bar unit) D3
and Range Limits)
M calibration (kgf/cm2 unit) D4
Sealing treatment to Sealant (liquid silicone rubber) is coated on surfaces of SUS630 nuts used
SUS630 nuts for cover flange mounting. Y

Long vent Total vent plug Length: 112 mm (standard, 32 mm), Material: SUS316 U
Fast response Update time: 0.125 sec or less, see GS for the response time F1
Failure alarm down-scale *1 Output status at CPU failure and hardware error is –5%, 3.2 mA or less. C1
Failure alarm down-scale: output status at CPU failure and
C2
Output signal limits: hardware error is –5%, 3.2 mA or less.
NAMUR NE43 compliant *1
3.8 mA to 20.5 mA Failure alarm up-scale: output status at CPU failure and
C3
hardware error is 110%, 21.6 mA or more.
Stainless steel Amplifier housing material; SCS14A stainless steel (equivalent to SUS316 cast stainless
E1
amplifier housing steel or ASTM CF-8M)
Gold-plate Gold-plated diaphragm A1
Stainless steel tag plate SUS304 tag plate wired onto transmitter N4

130 Pa abs {1 mmHg abs} Minimum input pressure: 130 Pa abs{1 mmHg abs} at range calibrating testing S1

Cover flange M01


Mill Certificate
Cover flange, Process connector M11
Test Pressure: 50 kPa{0.5 kgf/cm2} Capsule L, M T04
Pressure test/ Nitrogen(N2) Gas
Test Pressure: 3 MPa{30 kgf/cm2} Capsule A T03
Leak test Certificate Retention time: 10 minutes
Test Pressure: 14 MPa{140 kgf/cm2} Capsule B T02
T1008.EPS

* 1: Applicable for Output signal code D and E. The hardware error indicates faulty amplifier or
capsule. When combining with Optional code F1, output status for down-scale is –2.5%,
3.6 mA DC or less.

10-7 IM 01C22D01-01E
10. GENERAL SPECIFICATIONS

10.4 Dimensions
䊉 Model EJA310 and EJA430 [Style: S2]

Vertical Impulse Piping Type


Process connector upside (INSTALLATION CODE ‘6’) (For CODE ‘2’, ‘3’ or ‘7’,
refer to the notes below.)

Process connector External indicator


(Optional) conduit connection
259(10.20) Blind plug
(Optional)
197 (7.76) 110 (4.33)
97 146 (5.75) High Low
27
(3.82) pressure
(1.06)
pressure
Process side (Note 1) side
connections
(2.83)
72

(1.81)
46

(5.83)
(3.07)

148
ø78
234(9.21)

Terminal
(4.02)

side
102

Internal
indicator
Ground (Optional)
terminal Conduit
connection Open to
Mounting bracket
( 2.09)

Vent/Drain atmosphere (Note 3)


(L-type, Optional) 12
53

plugs (0.47) (ø9mm)


Zero
adjustment
2-inch pipe (O.D. 60.5mm)
F1002.EPS

Horizontal Impulse Piping Type


(INSTALLATION CODE ‘9’) (For CODE ‘8’, refer to the notes below.)

Conduit 110 (4.33)


94 72 connection
12 Zero
(3.70) (2.83) (0.47) adjustment
Internal
indicator
(3.07)

(Optional) Terminal
ø78

External indicator
conduit connection side
(7.76)
197

Blind plug

(5.75)
(6.38)

(Optional)
146
Ground
162

terminal
Shrouding bolt
(Note 4) High Low
pressure pressure
side (Note 1) side
Process
connection Open to
Process Vent plugs atmosphere (Note 3)
27 (1.06)
(4.88)

46 connector (ø5mm)
124

(1.81) (Optional) Drain plugs 64 (2.52)


125 (4.92)
Mounting bracket
(Flat-type, Optional)
(1.85)
47

2-inch pipe (O.D. 60.5mm)

F1003.EPS

Note 1: When INSTALLATION CODE ‘2’, ‘3’ or ‘8’ is selected, high and low pressure side on above
figure are reversed.
(i. e. High pressure side is on the left side.)
Note 2: When INSTALLATION CODE ‘3’ or ‘7’ is selected, process connetion and mounting bracket on
above figure are reversed.
Note 3: Applicable for EJA430.
Note 4: Applicable only for ATEX, IECEx, and TIIS Flameproof type.

10-8 IM 01C22D01-01E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS INTRINSICALLY SAFE EQUIPMENT

INSTALLATION AND OPERATING PRECAUTIONS FOR


TIIS INTRINSICALLY SAFE EQUIPMENT

Apparatus Certified Under Technical Criteria (IEC-compatible Standards)


and from “RECOMMENDED PRACTICES for Explosion-Protected Electri-
cal Installations in General Industries,” published in 1979

1. General words, they are not safe products involved with factors such
as chemical reactions, geographical changes or the like other
The following describes precautions on electrical apparatus than affected by electric energy from the equipment itself.
of intrinsically safe construction (hereinafter referred to as
intrinsically safe apparatus).

Following the Labor Safety and Health Laws of Japan, an 2. Electrical Apparatus of Intrinsic
intrinsically safe apparatus must undergo type tests in order Safety Type of Explosion-
to be certified by the Technical Institute of Industrial Safety, Protected Construction
Inc. These tests are required to satisfy either the technical
criteria for electrical machinery and equipment in compliance The intrinsic safety type of explosion-protected construction
with explosionproof standards involving inflammable gases is a method of protection applicable to a circuit or part of a
or vapors and for machinery and equipment having circuit in which, under prescribed test conditions, no spark or
explosionproof performance (standards notification no. 556 thermal effect, whether produced normally or accidentally, is
from the Japanese Ministry of Labor) (hereinafter referred to capable of causing a prescribed explosive gas to ignite. In
as technical criteria), in conformity with IEC Standards, or other words, electrical apparatus of this construction is
the “Recommended Practice for Explosion-Protected intended to suppress electrical energy thereby preventing
Electrical Installations in General Industries,” published in ignition of a given explosive gas atmosphere even though
1979. Such a certified apparatus can be used in hazardous spark or high thermal effect occurs in the electric circuitry.
locations where inflammable gases or vapors may be present. Intrinsically safe electrical apparatus generally comprise
Certified apparatus includes a certification label and an intrinsically safe apparatus installed in a hazardous location
equipment nameplate with the specifications necessary for and a safety barrier (associated apparatus), installed in a non-
explosion requirements as well as precautions on explosion hazardous location, aimed at preventing electrical energy
protection. Please confirm these precautionary items and use from flowing into the electric circuitry of intrinsically safe
them to meet specification requirements. apparatus.

For electrical wiring and maintenance servicing, please refer However, battery-operated, portable intrinsically safe
to “Internal Wiring Rules” in the Electrical Installation apparatus or the like may be used alone.
Technical Standards as well as “USER’S GUIDELINES for
Electrical Installations for Explosive Gas Atmospheres in
General Industry,” published in 1994.
3. Terminology
(1) Intrinsically safe apparatus: Electrical apparatus in which
all the circuits are intrinsically safe circuits.
To meet intrinsically safe requirements, equipment that can (2) Associated apparatus: Electrical apparatus in which there
be termed an “intrinsically safe apparatus” must: are both intrinsically safe circuits and non-intrinsically
safe circuits that can affect the safety of intrinsically safe
(1) be certified by the Technical Institute of Industrial
circuits.
Safety, Inc. in accordance with the Labor Safety and
(3) Safety barrier: A specific type of associated apparatus,
Health Laws of Japan and have the appropriate mark of
which consists mainly of safety barrier elements, and
certification labeled on its case, and
serves to limit the flow of excessive electrical energy,
(2) be used in compliance with the specifications marked on
which is capable of causing ignition of a given explosive
its certification label, equipment nameplate and
gas or vapour of a non-intrinsically safe circuit into
precautionary information furnished.
concerned intrinsically safe circuits.
Note: Intrinsically safe apparatus satisfy their performance under (4) Apparatus of category “ia”: Intrinsically safe electrical
specific conditions. They are not always absolutely safe under apparatus and associated apparatus which are incapable
every operational and environmental condition. In other of causing ignition of a given explosive gas or vapour
with the appropriate safety factors such as:

1 EX-A03E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS INTRINSICALLY SAFE EQUIPMENT

— when up to two countable faults are applied and, in (2) For pressure transmitters, pH transmitters, temperature
detectors and the like, safety barriers that can be
addition,
combined are already specified. Other safety barriers
— when non-countable faults produce an onerous cannot be used.
condition.
(5) Apparatus of category “ib”: Intrinsically safe electrical Note 2: Testing Intrinsically Safe System
An assembly (as a system) in which intrinsically safe
apparatus and associated apparatus which are incapable
apparatus and safety barriers are combined is assessed to
of causing ignition of a given explosive gas or vapour, ensure that its safety requirements are satisfied. A tested and
with the appropriate safety factors such as: certified system incorporates a certification number
— when up to one countable fault is applied and, in (intrinsically safe apparatus and safety barriers have the same
certification number).
addition,
— when non-countable faults produce an onerous Note 3: Impossible Combinations of Apparatus Certified Under
condition. Different Standards
(6) Safety rating: A rating to be designated to intrinsically Intrinsically safe apparatus certified under technical criteria
and safety barriers certified under the “Recommended
safe apparatus as well as associated apparatus and is the
Practice for Explosion-Protected Electrical Installations in
maximum rating allowable for maintaining intrinsic General Industries” (1979) and vice versa cannot be
safety of concerned intrinsically safe circuits. combined even if their combination requirements are
satisfied.

4. Caution on Combining Intrinsi-


cally Safe Apparatus and 5. Installation of Intrinsically Safe
Safety Barriers Apparatus and Safety Barriers
(1) A combination of certified intrinsically safe apparatus (1) Classification of installation location
and safety barriers needs to satisfy combination Intrinsically safe apparatus may be installed, depending upon
requirements. If intrinsically safe apparatus specify applicable gases, in a hazardous area in Zone 0, 1 or 2 (Note
safety barriers for combination, safety barriers other than 4 below), where the specified gases are present. However,
specified cannot be used (see Note 1 for more details). note that apparatus certified under Technical Criteria, in
(2) Certified intrinsically safe systems specify specific safety category “ib” shall be installed only in Zone 1 or 2. Safety
barriers in combination with intrinsically safe apparatus. barriers (associated apparatus) that are combined with these
So safety barriers other than specified cannot be used intrinsically safe apparatus shall be installed only in a non-
(see Note 2 for more details). hazardous area. In cases where safety barriers are installed in
(3) Other than limitations of combining intrinsically safe a hazardous area, they shall be enclosed, for example, in a
apparatus and safety barriers as given in (1) and (2) flameproof enclosure.
above, two or more pieces of apparatus certified under
Note 4: Hazardous areas are classified in zones based upon the
different standards cannot be combined with each other frequency of the appearance and the duration of an explosive
(see Note 3 for more details). In addition, bear in mind gas atmosphere as follows:
that classifications of explosion protection such as “IIA,” Zone 0: An area in which an explosive gas atmosphere is
“IIB” and “IIC” and category “ia” and “ib” limit a present continuously or is present for long periods.
Zone 1: An area in which an explosive gas atmosphere is
combination of intrinsically safe apparatus and safety likely to occur in normal operation.
barriers. Zone 2: An area in which an explosive gas atmosphere is not
For more details, see the “Type Certificate Guide for likely to occur in normal operation and if it does
Explosion-Protected Constructionfor Electrical occur it will exist for a short period only.
Machinery and Equipment,” issued by the Japanese
Ministry of Labour, the Research Institute of Industrial (2) Ambient temperature limits for intrinsically
Safety. safe apparatus
Intrinsically safe apparatus shall be installed in a location
Note 1: Testing Apparatus where the ambient temperature ranges from –20° to +40°C
Intrinsically safe apparatus and safety barriers are assessed (for those certified under Technical Criteria) or –10° to
individually to ensure that their safety requirements are +40°C (for those certified under the “Recommended Practice
satisfied. Tested and certified intrinsically safe apparatus and
safety barriers incorporate individual certification numbers. for Explosion-Protected Electrical Installations in General
A combination of intrinsically safe apparatus and safety Industries” (1979). However, some field-mounted
barriers involves the following two limitations:
(1) A safety barrier which meets the combination require-
ments by referring to its safety rating and combination
parameters shall be selected.

2 EX-A03E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS INTRINSICALLY SAFE EQUIPMENT

intrinsically safe apparatus may be used at an ambient Installations for Explosive Gas Atmospheres in General
temperature up to 60°C. So, specifications should be checked Industry” issued in 1994 by the Japanese Ministry of Labour,
before installing intrinsically safe apparatus. the Research Institute of Industrial Safety.

If the intrinsically safe apparatus are exposed to direct


(1) Requirements for maintenance personnel
sunshine or radiant heat from plant facilities, appropriate
Maintenance and inspection of intrinsically safe apparatus
thermal protection measures shall be taken.
and safety barriers shall be conducted by maintenance
personnel skilled in intrinsically safe construction and
6. Wiring for Intrinsically Safe installation of electrical devices as well as capable of
Circuits applying associated rules.

In intrinsically safe construction, safety shall be maintained (2) Maintenance and Inspection
as an intrinsically safe system involving intrinsically safe (a) Visual inspection
apparatus and safety barriers connected thereto, and electrical Visually inspect the external connections of intrinsically
wiring (through intrinsically safe circuits) interconnected safe apparatus and safety barriers, and cables for damage
between them. In other words, even when safety or corrosion as well as other mechanical and structural
requirements are maintained individually by intrinsically safe defects.
apparatus and safety barriers, they shall not be affected by (b) Adjustments
electrical or magnetic energy caused by electrical wiring. Zero, span and sensitivity adjustments shall be made
To make electrical wiring for intrinsically safe circuits, you with applicable adjusting potentiometers and mechanical
must: adjustment screws.
These maintenance adjustments shall be made in a non-
(a) refer to the equipment configuration diagram and make hazardous location.
electrical wiring properly;
(b) prevent intrinsically safe wiring from being contacted
with non-intrinsically safe wiring, and separate the CAUTION
intrinsically safe circuit from other electrical circuits;
(c) prevent intrinsically safe wiring from being If intrinsically safe apparatus and safety barriers
electrostatically and magnetically affected by non- require maintenance service and checking, a
intrinsically safe wiring; gas detector shall be used to ensure that there
(d) reduce wiring inductance and capacitance produced is no explosive gas in the location (mainte-
between the intrinsically safe apparatus and safety nance servicing shall be conducted in a non-
barrier where possible, and use a shorter cable between hazardous location).
the intrinsically safe apparatus and safety barrier than
specified if the maximum permissible inductance of the
cable is specified as operating conditions; (3) Repair
(e) conform to conditions of installation such as wiring Intrinsically safe apparatus and safety barriers shall be
method, earthing or the like, if any; and repaired by manufacturers.
(f) protect the outer sheath of cables from damage with
appropriate measures. (4) Prohibition of modifications and specifica-
tion changes
Do not attempt to make modifications or change specifica-
tions which may affect safety.
7. Maintenance and Inspection of
Intrinsically Safe Apparatus
and Safety Barriers
Maintenance and inspection of intrinsically safe apparatus
and safety barriers shall be limited to within the instructions
described in applicable instruction manuals. If other than this
is required, contact the manufacturers. For more information,
refer to the “USER’S GUIDELINES for Electrical

3 EX-A03E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT

INSTALLATION AND OPERATING PRECAUTIONS FOR


TIIS FLAMEPROOF EQUIPMENT

Apparatus Certified Under Technical Criteria


(IEC-compatible Standards)

1. General construction is of completely enclosed type and its enclosure


shall endure explosive pressures in cases where explosive
The following describes precautions on electrical apparatus gases or vapours entering the enclosure cause explosion. In
of flameproof construction (hereinafter referred to as addition, the enclosure construction shall be such that flame
flameproof apparatus) in explosion-protected apparatus. caused by explosion does not ignite gases or vapours outside
Following the Labour Safety and Health Laws of Japan, the enclosure.
flameproof apparatus is subjected to type tests to meet either In this manual, the word "flameproof" is applied to the
the technical criteria for explosionproof electrical machinery flameproof equipment combined with the types of protection
and equipment (standards notification no. 556 from the "e", "o", "i", and "d" as well as flameproof equipment.
Japanese Ministry of Labour) (hereinafter referred to as
technical criteria), in conformity with the IEC Standards, or
the “Recommended Practice for Explosion-Protected 3. Terminology
Electrical Installations in General Industries,” published in
1979. These certified apparatus can be used in hazardous (1) Enclosure
locations where explosive or inflammable gases or vapours An outer shell of an electrical apparatus, which encloses live
may be present. parts and thus is needed to configure explosion-protected
construction.
Certified apparatus includes a certification label and an
equipment nameplate with the specifications necessary for (2) Shroud
explosion requirements as well as precautions on explosion
A component part which is so designed that the fastening of
protection. Please confirm these precautionary items and use
joint surfaces cannot be loosened unless a special tool is
them to meet specification requirements.
used.
For electrical wiring and maintenance servicing, please refer
to “Internal Wiring Rules” in the Electrical Installation (3) Enclosure internal volume
Technical Standards as well as “USER’S GUIDELINES for This is indicated by:— the total internal volume of the
Electrical Installations for Explosive Gas Atmospheres in flameproof enclosure minus the volume of the internal
General Industry,” published in 1994. components essential to equipment functions.

To meet flameproof requirements, equipment that can be (4) Path length of joint surface
termed “flameproof” must: On a joint surface, the length of the shortest path through
(1) Be certified by a Japanese public authority in accordance which flame flows from the inside to outside of the
with the Labour Safety and Health Laws of Japan and flameproof enclosure. This definition cannot be applied to
have a certification label in an appropriate location on its threaded joints.
case, and
(5) Gaps between joint surfaces
(2) Be used in compliance with the specifications marked on
its certification label, equipment nameplate and The physical distance between two mating surfaces, or
precautionary information furnished. differences in diameters if the mating surfaces are cylindrical.

2. Electrical Apparatus of Flame- Note: The permissible sizes of gaps between joint surfaces, the path
length of a joint surface and the number of joint threads are
proof Type of Explosion- determined by such factors as the enclosure’s internal
Protected Construction volume, joint and mating surface construction, and the
explosion classification of the specified gases and vapours.
Electrical apparatus which is of flameproof construction is
subjected to a type test and certified by the Japanese Ministry
of Labour aiming at preventing explosion caused by electrical
apparatus in a factory or any location where inflammable
gases or vapours may be present. The flameproof

1 EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT

4. Installation of Flameproof • Specific cables shall be used as recommended by the


Apparatus “USER’S GUIDELINES for Electrical Installations for
Explosive Gas Atmospheres in General Industry,”
(1) Installation Area published in 1994.
Flameproof apparatus may be installed, in accordance with • In necessary, appropriate protective pipes (conduit or
applicable gases, in a hazardous area in Zone 1 or 2, where flexible pipes), ducts or trays shall be used for
the specified gases are present. Those apparatus shall not be preventing the cable run (outside the cable glands) from
installed in a hazardous area in Zone 0. damage.
• To prevent explosive atmosphere from being propagated
Note: Hazardous areas are classified in zones based upon the
form Zone 1 or 2 hazardous location to any different
frequency of the appearance and the duration of an explosive
gas atmosphere as follows: location or non-hazardous location through the protective
Zone 0: An area in which an explosive gas atmosphere is pipe or duct, apply sealing of the protective pipes in the
present continuously or is present for long periods. vicinity of individual boundaries, or fill the ducts with
Zone 1: An area in which an explosive gas atmosphere is
sand appropriately.
likely to occur in normal operation.
Zone 2: An area in which an explosive gas atmosphere is not • When branch connections of cables, or cable connections
likely to occur in normal operation and if it does with insulated cables inside the conduit pipes are made,
occur it will exist for a short period only. a flameproof or increased-safety connection box shall be
(2) Environmental Conditions used. In this case, flameproof or increased-safety cable
The standard environmental condition for the installation of glands meeting the type of connection box must be used
flameproof apparatus is limited to an ambient temperature for cable connections to the box.
range from –20°C to +40°C (for products certified under (2) Flameproof Metal Conduit Wiring
Technical Criteria). However, some field-mounted • For the flameproof metal conduit wiring or insulated
instruments may be certified at an ambient temperature up to wires shall be used as recommended by the USER’S
+60°C as indicated on the instrument nameplates. If the GUIDELINES for Electrical Installations for Explosive
flameproof apparatus are exposed to direct sunshine or Gas Atmospheres in General Industry, published in
radiant heat from plant facilities, appropriate thermal 1994.
protection measures shall be taken. • For conduit pipes, heavy-gauge steel conduits
conforming to JIS C 8305 Standard shall be used.
• Flameproof sealing fittings shall be used in the vicinity
5. External Wiring for Flameproof
of the wiring connections, and those fittings shall be
Apparatus filled with sealing compounds to complete sealing of the
Flameproof apparatus require cable wiring or flameproof apparatus. In addition, to prevent explosive gases,
metal conduits for their electrical connections. For cable moisture, or flame caused by explosion form being
wiring, cable glands (cable entry devices for flameproof type) propagated through the conduit, always provide sealing
to wiring connections shall be attached. For metal conduits, fittings to complete sealing of the conduit in the
attach sealing fittings as close to wiring connections as following locations:
possible and completely seal the apparatus. All non-live (a) In the boundaries between the hazardous and non-
metal parts such as the enclosure shall be securely grounded. hazardous locations.
For details, see the “USER’S GUIDELINES for Electrical (b) In the boundaries where there is a different
Installations for Explosive Gas Atmospheres in General classification of hazardous location.
Industry,” published in 1994. • For the connections of the apparatus with a conduit pipe
or its associated accessories, G-type parallel pipe threads
(1) Cable Wiring (JIS B 0202) shall be used to provide a minimum of
• For cable wiring, cable glands (cable entry devices for five-thread engagement to complete tightness. In
flameproof type) specified or supplied with the apparatus addition, since these parallel threads do not have sealing
shall be directly attached to the wiring connections to property, nonhardening sealant such as liquid gaskets
complete sealing of the apparatus. shall thus be applied to those threads for ensuring
• Screws that connect cable glands to the apparatus are waterproofness.
those for G-type parallel pipe threads (JIS B 0202) with • If metal conduits need flexibility, use flameproof flexible
no sealing property. To protect the apparatus from fittings.
corrosive gases or moisture, apply nonhardening sealant
such as liquid gaskets to those threads for waterproofing.

2 EX-B03E
INSTALLATION AND OPERATING PRECAUTIONS FOR TIIS FLAMEPROOF EQUIPMENT

6. Maintenance of Flameproof requirements for flameproof apparatus (however, bear in


Apparatus mind that the apparatus must always be restored to its
original condition). If you attempt to repair the
To maintain the flameproof apparatus, do the following. (For flameproof apparatus, company-specified components
details, see Chapter 10 “MAINTENANCE OF EXPLOSION- shall be used.
PROTECTED ELECTRICAL INSTALLATION” in the (d) Before starting to service the apparatus, be sure to check
USER’S GUIDELINES for Electrical Installations for all parts necessary for retaining the requirements for
Explosive Gas Atmospheres in General Industry.) flameproof apparatus. For this, check that all screws,
bolts, nuts, and threaded connections have properly been
(1) Maintenance servicing with the power on. tightened.
Flameproof apparatus shall not be maintenance-serviced with
(3) Prohibition of specification changes and
its power turned on. However, in cases where maintenance
modifications
servicing is to be conducted with the power turned on, with
Do not attempt to change specifications or make
the equipment cover removed, always use a gas detector to
modifications involving addition of or changes in external
check that there is no explosive gas in that location. If it
wiring connections.
cannot be checked whether an explosive gas is present or not,
maintenance servicing shall be limited to the following two
items:

(a) Visual inspection 7. Selection of Cable Entry


Visually inspect the flameproof apparatus, metal
Devices for Flameproof Type
conduits, and cables for damage or corrosion, and other
mechanical and structural defects.
(b) Zero and span adjustments
These adjustments should be made only to the extent
IMPORTANT
that they can be conducted from the outside without The cable glands (cable entry devices for flameproof
opening the equipment cover. In doing this, great care type) conforming to IEC Standards are certified in
must be taken not to cause mechanical sparks with tools. combination with the flameproof apparatus. So,
(2) Repair Yokogawa-specified cable entry devices for flameproof
If the flameproof apparatus requires repair, turn off the power type shall be used to meet this demand.
and transport it to a safety (non-hazardous) location. Observe
the following points before attempting to repair the
apparatus. References:
(1) Type Certificate Guide for Explosion-Protected
(a) Make only such electrical and mechanical repairs as will
Construction Electrical Machinery and Equipment
restore the apparatus to its original condition. For the
(relating to Technical Standards Conforming to Interna-
flameproof apparatus, the gaps and path lengths of joints
tional Standards), issued by the Technical Institution of
and mating surfaces, and mechanical strength of
Industrial Safety, Japan
enclosures are critical factors in explosion protection.
(2) USER’S GUIDELINES for Electrical Installations for
Exercise great care not to damage the joints or shock the
Explosive Gas Atmospheres in General Industry (1994),
enclosure.
issued by the Japanese Ministry of Labour, the Research
(b) If any damage occurs in threads, joints or mating
Institute of Industrial Safet
surfaces, inspection windows, connections between the
transmitter and terminal box, shrouds or clamps, or
external wiring connections which are essential in
flameproofness, contact Yokogawa Electric Corporation.

CAUTION

Do not attempt to re-process threaded connections or


refinish joints or mating surfaces.

(c) Unless otherwise specified, the electrical circuitry and


internal mechanisms may be repaired by component
replacement, as this will not directly affect the

3 EX-B03E
Customer DPharp EJA Series
Maintenance Transmitter Section
Parts List

5
2 4
11
A 10

12
13 1
2 2
1

14

6
7-1 7-2
8 9
5

Item Part No. Qty Description

1 Bellow 2 Cover
F9341RA Cast-aluminum alloy
F9341RJ SCS14A stainless steel
2 F9341JP 2 O-ring
3 Below 1 Case Assembly (Note 1)

F9341AA Cast-aluminum alloy for G1/2


F9341AC Cast-aluminum alloy for G1/2 (two electrical connections)
F9341AE Cast-aluminum alloy for 1/2 NPT (two electrical connections)
F9341AH Cast-aluminum alloy for M20 (two electrical connections)
F9341AJ Cast-aluminum alloy for Pg13.5 (two electrical connections)

F9341AR SCS14A stainless steel for 1/2 NPT (two electrical connections)
4 – 1 Name Plate
5 Bellow 4 Screw
F9900RG For cast-aluminum alloy case assembly
F9900RR For SCS14A stainless steel case assembly

6 F9341KL 1 Tag Plate


7-1 Below 1 CPU Assembly
F9342AB For BRAIN protocol version (Except TIIS Intrinsically safe type)
F9342AL For HART protocol version (Except TIIS Intrinsically safe type)
F9342AJ For BRAIN protocol version TIIS Intrinsically safe type (Optional code /JS3)

F9342AD For BRAIN protocol version TIIS Intrinsically safe type with /F1(Optional code /JS3 and /F1)
F9342AF For BRAIN protocol version (Optional code /F1)
F9342AM For HART protocol version with write protection switch (Optional code /F1)
7-2 F9342BF For FOUNDATION Fieldbus protocol
F9342BG For FOUNDATION Fieldbus protocol with PID/LM function (Optional code /LC1)
8 F9900RP 2 Cap Screw
9 Y9612YU 2 Screw
10 Below 1 Plug
F9340NW For Pg13.5
F9340NX For M20
G9330DP For G1/2
G9612EB For 1/2 NPT
11 Bellow 1 Cover Assembly
F9341FM Cast-aluminum alloy
F9341FJ SCS14A stainless steel
12 Below 1 LCD Board Assembly For integral indicator
F9342BL Without range-setting switch
F9342BM With range-setting switch
13 F9342MK 2 Mounting Screw
14 F9300PB 2 Label

Note 1 : Applicable for BRAIN and HART Protocol version (Output signal code D and E).
For FOUNDATION Fieldbus protocol version (Output signal code F), contact Yokogawa local office.

All Rights Reserved, Copyright © 1995, Yokogawa Electric Corporation. CMPL 01C22A01-02E
14th Edition: Oct. 2008(KP)
Yokogawa Electric Corporation
Customer Mode EJA310 and EJA430
Maintenance Absolute and Gauge Pressure Transmitter
Parts List (Pressure-detector Section)

Horizontal Impulse Piping Type

15

11
18
Low pressure side
19
16
1
3 21–1
4

5 3
 For EJA310 low pres-
10 6 sure side cover flange

12
22
21–2
23 13 14

All Rights Reserved, Copyright © 1999, Yokogawa Electric Corporation. CMPL 01C22D00-01E
5th Edition: Apr. 2006(YK)
Yokogawa Electric Corporation
2

Vertical Impulse Piping Type

14
Low pressure side
3
21–1
13 1
11–1
3

12

2
8 22
10
9  For EJA310 low pres-
23 sure side cover flange

18
21–2
20
17 15

Item Part No. Qty Description

1 — 1 Capsule Assembly (see Table 1, Table 2, Table 3 and Table 4 on page 5) (Note 1)
2 F9300AJ 1 O-Ring
3 Below 2 Gasket
F9340GA Teflon-coated SUS316L Stainless Steel (for EJA310 and EJA430 with
F9340GC Teflon-coated SUS316L Stainless Steel (degreased) Wetted Parts Material code S)
F9340GE PTFE Teflon
F9340GF PTFE Teflon (degreased) (for EJA430 with Wetted Parts Material code H, M, T, A, D and B)
4 Below 1 Cover Flange for EJA310 and EJA430 (High Pressure Side) (Note 2) (Note 4)
F9340VA Rc 1/4 SCS14A Stainless Steel (for EJA310 and EJA430 with Wetted Parts Material code S)
F9340VB 1/4 NPT For Horizontal Impulse Piping Type

F9340VC Rc 1/4 SCS14A Stainless Steel (for EJA310 and EJA430 with Wetted Parts Material code S)
F9340VD 1/4 NPT For Vertical Impulse Piping Type
F9340VP Rc 1/4 SCS14A Stainless Steel (for EJA430 with Wetted Parts Material code H, M and T)
F9340VR 1/4 NPT For Horizontal Impulse Piping Type
F9340VN Rc 1/4
SCS14A Stainless Steel (for EJA430 with Wetted Parts Material code H, M and T)
F9340VQ 1/4 NPT For Vertical Impulse Piping Type
F9340VS Rc 1/4 Hastelloy C-276 equivalent (for EJA430 with Wetted Parts Material code A and D)
F9340VT 1/4 NPT For Horizontal Impulse Piping Type
F9340VU Rc 1/4 Hastelloy C-276 equivalent (for EJA430 with Wetted Parts Material code A and D)
F9340VV 1/4 NPT For Vertical Impulse Piping Type
F9340TP Rc 1/4 Monel equivalent (for EJA430 with Wetted Parts Material code B)
F9340TR 1/4 NPT For Horizontal Impulse Piping Type
F9340TN Rc 1/4 Monel equivalent (for EJA430 with Wetted Parts Material code B)
F9340TQ 1 1/4 NPT For Vertical Impulse Piping Type
5 Below Vent Plug

F9340SA R 1/4 SUS316 Stainless Steel (for EJA310 and EJA430 with Wetted Parts
F9340SB 1/4 NPT Material code S, H, M and T)
F9340SE R 1/4
F9340SF 1/4 NPT Hastelloy C-276 (for EJA430 with Wetted Parts Material code A and D)
F9340SS R 1/4
Monel (for EJA430 with Wetted Parts Material code B)
F9340ST 1/4 NPT
6 Below 1 Vent Screw
D0114PB SUS316 Stainless Steel (for EJA310 and EJA430 with Wetted Parts Material code S, H, M and T)
F9340SK Hastelloy C-276 (for EJA430 with Wetted Parts Material code A and D)
F9270HG Monel (for EJA430 with Wetted Parts Material code B)

Apr. 2006
Subject to change without notice. Printed in Japan.
CMPL 01C22D00-01E
3

Item Part No. Qty Description

7 Below 1 Drain Plug (Note 2)


F9200CS R 1/4 SUS316 Stainless Steel (for EJA310 and EJA430
D0114RZ 1/4 NPT with Wetted Parts Material code S, H, M and T)
F9340SL R 1/4
F9340SM 1/4 NPT Hastelloy C-276 (for EJA430 with Wetted Parts Material code A and D)

F9340SW R 1/4
D0117MS 1/4 NPT Monel (for EJA430 with Wetted Parts Material code B)
8 Below 1 Drain/Vent Plug
F9340SC R 1/4 SUS316 Stainless Steel (for EJA310 and EJA430
F9340SD 1/4 NPT with Wetted Parts Material code S, H, M and T)
F9340SG R 1/4
F9340SH 1/4 NPT Hastelloy C-276 (for EJA430 with Wetted Parts Material code A and D)
F9340SU R 1/4
F9340SV 1/4 NPT Monel (for EJA430 with Wetted Parts Material code B)
9 Below 1 Drain/Vent Screw

F9270HE SUS316 Stainless Steel (for EJA310 and EJA430 with Wetted Parts Material code S, H, M and T)
F9340SJ Hastelloy C-276 (for EJA430 with Wetted Parts Material code A and D)
D0117MR Monel (for EJA430 with Wetted Parts Material code B)
10 Below 4 Bolt
F9340AB SCM435 Chrome Molybdenum Steel

F9340AC SUS630 Stainless Steel


11 Below 4 Nut
F9275KL SCM435 Chrome Molybdenum Steel
F9275KH SUS630 Stainless Steel
12 Below 1 Gasket

D0114RB PTFE Teflon


U0102XC PTFE Teflon (degreased)
13 Below 1 Process Connector(Note 2)
F9340XY Rc 1/4
F9340XW Rc 1/2 SCS14A Stainless Steel (for EJA310 and EJA430
with Wetted Parts Material code S, H, M and T)
F9340XZ 1/4 NPT
F9340XX 1/2 NPT
F9340WY Rc 1/4
F9340WW Rc 1/2
F9340WZ 1/4 NPT Hastelloy C-276 equivalent (for EJA430
with Wetted Parts Material code A and D)
F9340WX 1/2 NPT
F9340TY Rc 1/4
F9340TW Rc 1/2 Monel equivalent (for EJA430 with
F9340TZ 1/4 NPT Wetted Parts Material code B)
F9340TX 1/2 NPT
14 Below 2 Bolt
X0100MN SCM435 Chrome Molybdenum Steel
F9273DZ SUS630 Stainless Steel
15 Below 4 Bolt
F9270AY S15C Carbon Steel

F9273CZ SUS XM7 Stainless Steel


16 Below 1 Bracket Assembly (Flat type)
F9270AW SECC Carbon Steel
F9300TJ SECC Carbon Steel (for Epoxy resin-baked coating)
F9300TA SUS304 Stainless Steel

17 Below 1 Bracket Assembly (L type)


F9340EA SECC Carbon Steel
F9340EB SECC Carbon Steel (for Epoxy resin-baked coating)
F9340EC SUS304 Stainless Steel
18 D0117XL-A 1 U-Bolt/Nut Assembly, SUS304 Stainless Steel

19 Below 1 Bracket (Flat type)


F9270AX SECC Carbon Steel
F9300TN SECC Carbon Steel (for Epoxy resin-baked coating)
F9300TE SUS304 Stainless Steel
20 Below 1 Bracket (L type)

F9340EF SECC Carbon Steel


F9340EG SECC Carbon Steel (for Epoxy resin-baked coating)
F9340EM SUS304 Stainless Steel
21-1 Below 1 Cover Flange for EJA430 (Low Pressure Side) (Note 4)
F9340VE For Horizontal Impulse Piping Type
SCS14A Stainless Steel
F9340VF For Vertical Impulse Piping Type (for Wetted Parts Material code S)
F9340RJ For Horizontal Impulse Piping Type SCS14A Stainless Steel
F9340RK For Vertical Impulse Piping Type (for Wetted Parts Material code H, M, T, A and B)
21-2 F9340VK 1 Cover Flange for EJA310, SCS14A Stainless Steel (Low Pressure Side) (Note 4)
22 Below 1 Vent Plug (degreased), SUS316 Stainless Steel

F9275EC R 1/4
F9275ED 1/4 NPT
23 F9275EE 1 Needle Assembly (degreased), SUS316 Stainless Steel

(Note 1) In case of degrease cleansing treatment (Optional code/K1 or K5), consult YOKOGAWA local office.
(However, see Table 1, Table 2, Table 3 and Table 4 in case of Optional code/K2 or K6)
(Note 2) In case of degrease cleansing treatment (Optional code/K1, K2, K5 or K6), consult YOKOGAWA local office.
(Note 3) The Plug Qty is 1 for Vertical Impulse Piping Type.
(Note 4) These Cover Flanges shall be applied to the model with the Style Code "S2" which was supplied from Aug. 16, 1996.

Apr. 2006
Subject to change without notice. Printed in Japan.
CMPL 01C22D00-01E
4

 Capsule Assembly Part Number


 EJA310
Table 1. EJA310 Capsule Assembly Part Number (Item 1)
For General-use type, Flameproof type and Intrinsically safe type (Except TIIS Intrinsically safe type)
Installation of High Pressure Capsule Part No. Part No.
Transmitter Side Code (*1) (*2)
L F9349HA F9352HA
Right M F9349JA F9352JA
Horizontal Impulse A F9349KA F9352KA
Piping Type L F9349HB F9352HB
Left M F9349JB F9352JB
A F9349KB F9352KB
L F9349HC F9352HC
Right M F9349JC F9352JC
Vertical Impulse A F9349KC F9352KC
Piping Type L F9349HD F9352HD
Left M F9349JD F9352JD
A F9349KD F9352KD

Table 2. EJA310 Capsule Assembly Part Number (Item 1)


For TIIS Intrinsically safe type (/JS3)
Installation of High Pressure Capsule Part No. Part No.
Transmitter Side Code (*1) (*2)
L F9378FA F9378TA
Right M F9378GA F9378UA
Horizontal Impulse A F9378HA F9378VA
Piping Type L F9378FB F9378TB
Left M F9378GB F9378UB
A F9378HB F9378VB
L F9378FC F9378TC
Right M F9378GC F9378UC
Vertical Impulse A F9378HC F9378VC
Piping Type L F9378FD F9378TD
Left M F9378GD F9378UD
A F9378HD F9378VD

 EJA430
Table 3. EJA430 Capsule Assembly Part Number (Item 1)
For General-use type, Flameproof type and Intrinsically safe type (Except TIIS Intrinsically safe type)
Installation of High Pressure Capsule Wetted Parts Material Code
Transmitter Side Code S (*1) S (*2) H, A T, D M, B
Horizontal A F9349LA F9352LA F9349LE F9349LJ F9349LN
Right
Impulse B F9349MA F9352MA F9349ME F9349MJ F9349MN
Piping Type A F9349LB F9352LB F9349LF F9349LK F9349LP
Left
B F9349MB F9352MB F9349MF F9349MK F9349MP
Vertical A F9349LC F9352LC F9349LG F9349LL F9349LQ
Right
Impulse B F9349MC F9352MC F9349MG F9349ML F9349MQ
Piping Type A F9349LD F9352LD F9349LH F9349LM F9349LR
Left
B F9349MD F9352MD F9349MH F9349MM F9349MR

Table 4. EJA430 Capsule Assembly Part Number (Item 1)


For TIIS Intrinsically safe type (/JS3)
Installation of High Pressure Capsule Wetted Parts Material Code
Transmitter Side Code S(*1) S(*2) H, A T, D M, B
A F9378JA F9378WA F9378JE F9378JJ F9378JN
Right
Horizontal Impulse B F9378KA F9378XA F9378KE F9378KJ F9378KN
Piping Type A F9378JB F9378WB F9378JF F9378JK F9378JP
Left
B F9378KB F9378XB F9378KF F9378KK F9378KP
A F9378JC F9378WC F9378JG F9378JL F9378JQ
Right
Vertical Impulse B F9378KC F9378XC F9378KG F9378KL F9378KQ
Piping Type A F9378JD F9378WD F9378JH F9378JM F9378JR
Left
B F9378KD F9378XD F9378KH F9378KM F9378KR

*1. Silicone oil filled capsule (Standard)


*2. Fluorinated oil filled capsule (for oil-prohibited use: Optional code /K2 or K6)

Apr. 2006
Subject to change without notice. Printed in Japan.
CMPL 01C22D00-01E
REVISION RECORD
Title: Model EJA310 and EJA430 Absolute Pressure and Gauge Pressure
Transmitter
Manual No.: IM 01C22D01-01E
Edition Date Page Revised Item
9th Sep. 1998 2-14 2.10 • Delete EMC Conformity Standards Tables and move the
section to page 2-14.
2-15 2.10 • Remove Page 2-15.
8-19 8.3.2(8) • Correction made in BURN OUT figure.
11-2 11.1.2 • Add Electrical connection code 7, 8, and 9.
11-6 11.2.1 • Add Wetted parts material code M.
11-7 11.2.2 • Add Wetted parts material code M.
• Add Elactrical connection code 7, 8, and 9.
CMPL CMPL 1C22A1-02E 4th 5th
Page 2 • Add Part No. to Item 3 (For PG13.5 and M20).
• Add Part No. to Item 10 (For 1/2 NPT, Pg13.5, and M20).
CMPL 1C22E1-01E 6th 7th
Page 5 • Add Wetted parts material code M to Table 1 and 2.
10th Feb. 2000  Changed to Electronic File Format.
Revised a book in a new format.
(The location of contents and the associated page numbers may
not coincide with the one in old editions.)
Major Revised Items:
1. Explosion class and option code of JIS flameproof approval.
Explosion class: Ex ds IIC T4(old) to Ex do IIC T4X(new).
Option code: /JF1(old) to /JF3(new)
2. Option code for flameproof packing adapter for JIS flameproof
approval.
Option code: /G1 and /G2(old) to /G11 and /G12(new)
3. Add “Pa” and “hPa” as the unit for calibration range.
4. Part number change for CPU Board Assembly.

2-9 2.9 • Add Figure 2.3 Example of using DCS.


• Add Figure 2.4 Selecting Cables.
2.10 • Add AS/NZS 2064 1/2 to EMI, EMC Conformity Standards.
6-1 6.2 • Add selection in the case of JIS flameproof type.
6-3 6.4.2 • Change option code for flame packing adapter.
Option code: G1 and G2 G11 and G12
Change Applicable cable O.D. and Identifying mark.
Part number: G9601AH G9601AM
Change the figure of flame proof packing adapter in Figure 6.4.2c.
8-4 8.3.1 • Add Pa and hPa to C20 and D31.
  • Installation and Operating Precautions for JIS Intrinsically Safe
and Explosionproof Equipment:
EX-A01E EX-A03E, EX-B01E EX-B03E
10-3 10.2 • Add Wetted parts material code B.
10-5 10.3 • Add Optional code F1.
CMPL CMPL 1C22A1-02E 5th 6th
• Change a format.
• Change and add Part No. of Item 7-1, CPU assembly:
Change; F9342BC F9342BB, F9342BK F9342BJ
Add; F9342AF, F9342AM
• Change Part No. of Item 10, Plug:
G9330DK G9330DP
CMPL 1C22B0-01E 1st
• Combine CMPL 1C22B1-01E and 1C22B3-01E.

11th Sep. 2000 2-8 2.9.4.b • Change ambient temperature limit and add Caution for cable
wiring.
2-9 2.9.5.b Add Caution for /JS3
3-1 3 Add Note for /F1
8-4,8-5 8.3.1 Add parameter E10, E14 and E15. Add Note for /F1.
8-8 8.3.3(3) Add Note for /F1.

REVISION RECORD.EPS

IM 01C22D01-01E
Edition Date Page Revised Item
11th Sep. 2000 8-12 8.3.3(11)(12)
(Continued) Add Note for /F1.
8-15 8.3.3(16) Add Note for /F1.
10-1 10.1 Change the capsule damping time constant.
10-4 10.3 Add /JS3 and delete /JS1.
Change Amb.Temp. for /KF1.
CMPL CMPL 1C22A1-02E 6th 7th
• Add Parts No. to item 7-1 (For /JS3 and /F1).
• Add Parts No. to item 7-2 (For /LC1).
CMPL 1C22A1-02E 7th 8th
• Add Note for Case Assembly.
CMPL 1C22B0-01E 1st 2nd
• Change Parts No. of Capsule Assembly for JIS Intrinsically safe
type.

12th July 2001 2-10 2.10 • Change EMC Conformity number.


8-4, 8-5 8.3.1 • Add footnote (*6) to B40, Maximum static pressure in Parameter
Summary.
10-3 10.2 • Change the maximum working pressure to 16 MPa.
CMPL CMPL 1C22A1-02E 8th 9th (Manual Change)
• Change Part No. of CPU Assembly for BRAIN protocol.
F9342BB F9342AB
CMPL 1C22A1-02E 9th 10th (Manual Change)
• Change Part No. of CPU Assembly for HART protocol.
F9342BH F9342AL
CMPL 1C22A1-02E 10th CMPL 01C22A01-02E 11th
• Delete Part No. of Name Plate.
• Change Part No. of Screw.
F9303JU Y9303JU
CMPL 1C22B0-01E 2nd CMPL 01C22B00-01E 3rd
Page 3 • Add Wetted parts material code D.
Page 5 • Add Wetted parts material code B to Table 2.

13th May 2002 1-2 1.1 • Add “1.1 For Safety Using.”
2-7 2.9.4 • Add descriptions based on ATEX directive.
10-4 10.3 • Add Optional code K2.
10-5 • Add Optional code C2 and C3.
• Change Optional code T02 to T12

14th Apr. 2003 2-8 2.9.4 • Add Option code KU2.


2-11 2.11 • Add PED (Pressure Equipment Directive).
10-5 10.3 • Add Option code KU2.

15th Apr. 2006 1-2 1.1 • Add (e) Explosion Protected Type Instrument and (f) Modification
1-3 1.3 • Add “1.3 ATEX Document”
2-6 2.9.3 • Add “IECEx Certification” and delete “SAA Certification”
2-11 2.9.5 • JIS Certification TIIS Certification
2-12 2.12 • Add Low Voltage Directive
10-5, 10-6 10.3 • Add Certificate numbers and Applicable standards
10-6 • Add option code /SU2 and delete option code /SU1
10-7 • Add option code /PR and /N4
CMPL CMPL 01C22A01-02E 11th 01C22A01-02E 12th
JIS Intrinsically safe type TIIS Intrinsically safe type
CMPL 01C22D00-01E 4th 01C22D00-01E 5th
JIS Intrinsically safe type TIIS Intrinsically safe type

16th Jan. 2008 1-1 • Add direct current symbol.


1-4 • Add 11 European languages for ATEX documentation.
2-3+ 2.9.1 • Add applicable standard and certificate number for appovals.
2-12 2.10 • Add EMC caution note.
4-3 4.5 • Add section of changing the direction of integral indicator.
8-13 8.3.3 (11) • Add figure for A40.
9-4 9.4.1 • Add figure of integral indicator direction.
10-5, -6 10.3 • Delete applicable standard from the table.
CMPL CMPL 01C22A01-02E 12th CMPL 01C22A01-02E 13t
• Delete logo from the tag plate.
REVISION RECORD.EPS

IM 01C22D01-01E
Edition Date Page Revised Item
17th Oct. 2008 2-9 2.9.4 Change explosion protection marking for type n from EEx to Ex.
2-12 2.10 Update EMC conformity standards.
7-1 7.1 Modify layout.
8-4 and 8-5 8.3.1 Add new parameters.
8-6 8.3.2 Add items in table 8.3.1.
8-9 and later 8.3.3 Add (5) Change Output Limit and (13) Span Adjustment.
Re-number the items.
8-18 8.5.2 Modify descriptions and notes for Er.01.
9-1 9.3 Add a note for calibration.
9-5 9.4.3 Add a note for cleaning.
10-3, 10-4 10.2 Add new suffix codes.
10-6, 10-7 10.3 Add Sealing statement for CSA.standards., Add /HC.
10-8 10.4 Correct errors.
CMPL CMPL 1C22A01-02E 13th 14th
Change part No .of item 5 and 8.
REVISION RECORD.EPS

IM 01C22D01-01E

You might also like