Timers
Timers
VEYRON II 6KW-48V
MPPT SOLAR INVERTER
Version: 1.0
Table Of Contents
Purpose ............................................................................................................................................................ 1
Scope ............................................................................................................................................................... 1
SAFETY INSTRUCTIONS.................................................................................................................................. 1
INTRODUCTION ............................................................................................................................................... 2
INSTALLATION ................................................................................................................................................. 4
OPERATION ..................................................................................................................................................... 10
SPECIFICATIONS ........................................................................................................................................... 33
Scope
This manual provides safety and installation guidelines as well as information on tools and wiring.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions. Read and
keep this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries and all
appropriate sections of this manual.
2. CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries.
Other types of batteries may burst, causing personal injury and damage.
3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required.
Incorrect re-assembly may result in a risk of electric shock or fire.
4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning.
Turning off the unit will not reduce this risk.
5. CAUTION – Only qualified personnel can install this device with battery.
6. NEVER charge a frozen battery.
7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable
size. It’s very important to correctly operate this inverter/charger.
8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop
a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please
refer to INSTALLATION section of this manual for the details.
10. Fuses are provided as over-current protection for the battery supply.
11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded
wiring system. Be sure to comply with local requirements and regulation to install this inverter.
12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input
short circuits.
13. Warning!! Only qualified service persons are able to service this device. If errors still persist after
following troubleshooting table, please send this inverter/charger back to local dealer or service center
for maintenance.
1
INTRODUCTION
This hybrid PV inverter can provide power to connected loads by utilizing PV power, utility power and battery
power.
Depending on different power situations, this hybrid inverter is designed to generate continuous power from PV
solar modules (solar panels), battery, and the utility. When MPP input voltage of PV modules is within
acceptable range (see specification for the details), this inverter is able to generate power to feed the grid
(utility) and charge battery. Galvanic isolation designed between PV/DC and AC output, so that user could
connect any type of PV array to this Hybrid inverter. See Figure 1 for a simple diagram of a typical solar system
with this hybrid inverter.
2
Product Overview
NOTE: For parallel model installation and operation, please check separate parallel installation guide for the
details.
1. LCD display
2. Status indicator
3. Charging indicator
4. Fault indicator
5. Function buttons
6. Power on/off switch
7. AC input connectors
8. AC output connectors (Load connection)
9. PV connectors
10. Battery connectors
11. Circuit breaker
12. Parallel communication port
13. Current sharing port
14. Dry contact
15. USB communication port
16. RS-232 communication port
17. BMS communication port: CAN, RS-485 or RS-232
3
INSTALLATION
Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should
have received the following items inside of package:
Preparation
Before connecting all wirings, please take off bottom cover by removing two screws as shown below.
4
Install the unit by screwing two screws. It’s recommended to use M4 or M5 screws.
Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current
protector or disconnect device between battery and inverter. It may not be requested to have a disconnect
device in some applications, however, it’s still requested to have over-current protection installed. Please refer
to typical amperage in below table as required fuse or breaker size.
Ring terminal:
5
CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring
terminal. Otherwise, overheating may occur.
CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected
tightly.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure
positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between
inverter and AC input power source. This will ensure the inverter can be securely disconnected during
maintenance and fully protected from over current of AC input.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input
and output connectors.
WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
Be sure to connect PE protective conductor ( ) first.
→Ground (yellow-green)
L1→LINE (brown or black)
N1→Neutral (blue)
L2→LINE (brown or black)
6
N2→Neutral (blue)
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes to restart because it’s required
to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a
short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check
manufacturer of air conditioner if it’s equipped with time-delay function before installation. Otherwise, this
inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes
internal damage to the air conditioner.
PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter
and PV modules.
CAUTION: Please install surge protection device between inverter and PV modules and the recommended
voltage is 500V.
WARNING! Do switch off the inverter before connecting to PV modules. Otherwise, it will cause inverter
damage.
WARNING! Do NOT connect negative and positive terminal of PV modules to the ground.
PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
7
Please follow below steps to implement PV module connection:
1. Remove insulation sleeve 10 mm for positive and negative conductors.
2. Check correct polarity of connection cable from PV modules and PV input
connectors. Then, connect positive pole (+) of connection cable to positive
pole (+) of PV input connector. Connect negative pole (-) of connection
cable to negative pole (-) of PV input connector.
Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws as shown below.
8
Communication Connection
Serial Connection
Please use supplied communication cable to connect to inverter and PC. Insert bundled CD into a computer and
follow on-screen instruction to install the monitoring software. For the detailed software operation, please
check user manual of software inside of CD.
Bluetooth Connection
This series is built in Bluetooth technology. You may simply go to google play to install “WatchPower”. It allows
wireless communication up to 6~7m in an open space.
9
OPERATION
Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch
(located on the bottom of the unit) to turn on the unit.
LED indicators
LCD display
Function keys
LED Indicator
LED Indicator Messages
Solid On Output is powered by utility in Line mode.
Green
Flashing Output is powered by battery or PV in battery mode.
Solid On Battery is fully charged.
Green
Flashing Battery is charging.
Solid On Fault occurs in the inverter.
Red
Flashing Warning condition occurs in the inverter.
Function Keys
Function Key Description
ESC To exit setting mode
UP To go to previous selection
DOWN To go to next selection
ENTER To confirm the selection in setting mode or enter setting mode
10
LCD Display Icons
Output Information
Battery Information
1.933V/cell ~ 2.017V/cell
11
> 2.017V/cell
< 1.892V/cell
1.892V/cell ~ 1.975V/cell
> 2.058V/cell
Load Information
Indicates overload.
0%~24% 25%~49%
50%~74% 75%~100%
12
LCD Setting
General Setting
After pressing and holding “ ” button for 3 seconds, the unit will enter setting mode. Press “ ” or “ ”
button to select setting programs. And then, press “ ” button to confirm the selection or “ ” button to exit.
Setting Programs:
13
UPS If selected, acceptable AC input
voltage range will be within
170-280VAC.
14
Restart disable (Default) Restart enable
09 Output frequency
10 Output voltage
240V
15
54V (Default)
18 Alarm control
16
Backlight on (Default) Backlight off
20 Backlight control
L3 phase:
17
Default setting: 42.0V If self-defined is selected in
program 5, this program can be
set up. Setting range is from
40.0V to 54.0V. Increment of
each click is 0.1V. Low DC cut-off
voltage will be fixed to setting
29 Low DC cut-off voltage value no matter what percentage
of load is connected.
SOC 10% (default) If any type of lithium battery is
selected in program 5, this
program can be set up. Setting
range is from 5% to 90%
120min (Default)
30days (Default)
18
Enable Disable (Default)
Equalization activated
39 If equalization function is enabled in program 33, this program can
immediately
be set up. If “Enable” is selected in this program, it’s to activate
battery equalization immediately and LCD main page will shows
“ ”. If “Disable” is selected, it will cancel equalization function
until next activated equalization time arrives based on program 37
Low DC cut off voltage or SOC 10% (default for Lithium) If any type of lithium battery is
60 SOC percentage on selected in program 05, this
second output parameter value will be displayed
in percentage and value setting is
based on battery capacity
percentage. Setting range is from
0% to 95%. Increment of each
click is 5%.
Disable (Default) Setting range is disable and then
from 0 min to 990 min.
Increment of each click is 5 min.
Setting discharge time on *If the battery discharge time
61
the second output achieves the setting time in
program 61 and the program 60
function is not triggered, the
output will be turned off.
00~23 (Default) Setting range is from 00 to 23.
Increment of each click is 1 hour.
If setting range is from 00 to 08,
Setting time interval to the second output will be turned
62
turn on second output on until 09:00. During this
period, it will be turned off if any
setting value in program 60 or 61
is reached.
19
Not reset(Default) Reset
3 days 5 days
30 days 60 days
20
Display Setting
The LCD display information will be switched in turns by pressing “ ” or “ ” key. The selectable
information is switched as the following table in order.
Input frequency=50Hz
Input frequency
PV voltage=260V
PV voltage
PV current = 2.5A
PV current
PV power = 500W
PV power
21
AC and PV charging current=50A
PV charging current=50A
Charging current
AC charging current=50A
PV charging power=500W
Charging power
AC charging power=500W
Output frequency=50Hz
Output frequency
22
Load percent=70%
Load percentage
Load in VA
When load is larger than 1kVA (≧1KVA), load in VA
will present x.xkVA like below chart.
Load in Watt
When load is larger than 1kW (≧1KW), load in W
will present x.xkW like below chart.
23
Battery voltage=25.5V, Inverter temperature
=50°C
Real date.
24
Real time 13:20.
Real time.
25
Operating Mode Description
Operating mode Behaviors LCD display
Battery is charged by utility.
26
Charging by utility and PV energy.
Charging by utility.
Fault mode
Note:
*Fault mode: Errors are
PV energy and utility
caused by inside circuit error
can charge batteries.
or external reasons such as
over temperature, output
Charging by PV energy.
short circuited and so on.
No charging.
Charging by utility.
27
Power from utility.
28
Faults Reference Code
Fault Code Fault Event Icon on
01 Fan is locked when inverter is off.
02 Over temperature
10 PV over current
11 PV over voltage
29
Warning Indicator
Warning
Warning Event Audible Alarm Icon flashing
Code
Beep three times every
01 Fan is locked when inverter is on.
second
30
BATTERY EQUALIZATION
Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like
stratification, a condition where acid concentration is greater at the bottom of the battery than at the top.
Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this
condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it’s recommended to
equalize battery periodically.
When to Equalize
In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is
active immediately, the controller will start to enter Equalize stage.
31
However, in Equalize stage, when battery equalized time is expired and battery voltage doesn’t rise to battery
equalization voltage point, the charge controller will extend the battery equalized time until battery voltage
achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when
battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.
32
SPECIFICATIONS
Table 1 Line Mode Specifications
INVERTER MODEL 6KW-48V
33
Table 2 Inverter Mode Specifications
INVERTER MODEL 6KW-48V
34
Table 3 Charge Mode Specifications
Utility Charging Mode
INVERTER MODEL 6KW-48V
Charging Current (UPS)
120A
@ Nominal Input Voltage
Flooded
58.4
Bulk Charging Battery
Voltage AGM / Gel
56.4
Battery
Floating Charging Voltage 54Vdc
Overcharge Protection 64Vdc
Charging Algorithm 3-Step
Battery Voltage, per cell Charging Current, %
2.43Vdc (2.35Vdc)
Voltage
2.25Vdc
100%
Charging Curve
50%
T0 T1
T1 = 10* T0, minimum 10mins, maximum 8hrs
Current
Time
Bulk Absorption Maintenance
(Constant Current) (Constant Voltage) (Floating)
Solar Input
INVERTER MODEL 6KW-48V
Rated Power 6500W
Max. PV Array Open Circuit
500Vdc
Voltage
PV Array MPPT Voltage Range 120Vdc~430Vdc
Max. Input Current 27A
35
Table 4 General Specifications
INVERTER MODEL 6KW-48V
Safety Certification CE
Operating Temperature
-10°C to 50°C
Range
Storage temperature -15°C~ 60°C
Humidity 5% to 95% Relative Humidity (Non-condensing)
Dimension
140 x 295 x 468
(D*W*H), mm
Net Weight, kg 12
36
TROUBLE SHOOTING
Problem LCD/LED/Buzzer Explanation / Possible cause What to do
Unit shuts down LCD/LEDs and buzzer
automatically will be active for 3 The battery voltage is too low 1. Re-charge battery.
during startup seconds and then (<1.91V/Cell) 2. Replace battery.
process. complete off.
1. The battery voltage is far too 1. Check if batteries and the
No response after low. (<1.4V/Cell) wiring are connected well.
No indication.
power on. 2. Battery polarity is connected 2. Re-charge battery.
reversed. 3. Replace battery.
Input voltage is
Check if AC breaker is tripped
displayed as 0 on the
Input protector is tripped and AC wiring is connected
LCD and green LED is
well.
flashing.
1. Check if AC wires are too
Mains exist but the
thin and/or too long.
unit works in
Insufficient quality of AC power. 2. Check if generator (if
battery mode. Green LED is flashing.
(Shore or Generator) applied) is working well or if
input voltage range setting is
correct. (UPSAppliance)
Set “Solar First” as the priority of Change output source priority
Green LED is flashing.
output source. to Utility first.
When the unit is
turned on, internal LCD display and LEDs Check if battery wires are
Battery is disconnected.
relay is switched on are flashing connected well.
and off repeatedly.
Reduce the connected load by
Overload error. The inverter is
Fault code 07 switching off some
overload 110% and time is up.
equipment.
Check if wiring is connected
Output short circuited. well and remove abnormal
load.
Fault code 05
Temperature of internal converter
Check whether the air flow of
component is over 120°C. (Only
the unit is blocked or whether
available for 1-3KVA models.)
the ambient temperature is
Internal temperature of inverter
Fault code 02 too high.
component is over 100°C.
Battery is over-charged. Return to repair center.
Fault code 03 Check if spec and quantity of
Buzzer beeps The battery voltage is too high. batteries are meet
continuously and requirements.
red LED is on.
Fault code 01 Fan fault Replace the fan.
Output abnormal (Inverter voltage 1. Reduce the connected
Fault code 06/58 below than 190Vac or is higher load.
than 260Vac) 2. Return to repair center
Fault code
Internal components failed. Return to repair center.
08/09/53/57
Fault code 51 Over current or surge.
Restart the unit, if the error
Fault code 52 Bus voltage is too low. happens again, please return
to repair center.
Fault code 55 Output voltage is unbalanced.
If the battery is connected
Battery is not connected well or
Fault code 56 well, please return to repair
fuse is burnt.
center.
37
Appendix I: Parallel function
1. Introduction
This inverter can be used in parallel with two different operation modes.
1. Parallel operation in single phase with up to 9 units. The supported maximum output power is
54W/54KVA.
2. Maximum nine units work together to support three-phase equipment. Seven units support one phase
maximum. The supported maximum output power is 54KW/54KVA and one phase can be up to
42KW/42KVA.
NOTE: If this unit is bundled with share current cable and parallel cable, this inverter is default supported
parallel operation. You may skip section 3. If not, please purchase parallel kit and install this unit by following
instruction from professional technical personnel in local dealer.
2. Package Contents
In parallel kit, you will find the following items in the package:
Step 2: Remove two screws as below chart and remove 2-pin and 14-pin cables. Take out the board under the
communication board.
38
Step 3: Remove two screws as below chart to take out cover of parallel communication.
Step 8: Put wire cover back to the unit. Now the inverter is providing parallel operation function.
39
4. Mounting the Unit
When installing multiple units, please follow below chart.
NOTE: For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx.
50 cm above and below the unit. Be sure to install each unit in the same level.
5. Wiring Connection
NOTICE: It’s requested to connect to battery for parallel operation.
The cable size of each inverter is shown as below:
Recommended battery cable and terminal size for each inverter:
Ring Terminal Ring terminal:
Torque
Model Wire Size Cable Dimensions
value
mm2 D (mm) L (mm)
6KW-48
2*4 AWG 44 6.4 49.7 2~3
V
WARNING: Be sure the length of all battery cables is the same. Otherwise, there
will be voltage difference between inverter and battery to cause parallel inverters
not working.
Recommended AC input and output cable size for each inverter:
Model AWG no. Torque
6KW-48V 10 AWG 1.2~ 1.6Nm
You need to connect the cables of each inverter together. Take the battery cables for example: You need to use
a connector or bus-bar as a joint to connect the battery cables together, and then connect to the battery
terminal. The cable size used from joint to battery should be X times cable size in the tables above. “X” indicates
the number of inverters connected in parallel.
Regarding AC input and output, please also follow the same principle.
CAUTION!! Please install the breaker at the battery and AC input side. This will ensure the inverter can be
securely disconnected during maintenance and fully protected from over current of battery or AC input. The
recommended mounted location of the breakers is shown in the figures in 5-1 and 5-2.
Recommended breaker specification of battery for each inverter:
Model 1 unit*
6KW-48V 125A/70VDC
*If you want to use only one breaker at the battery side for the whole system, the rating of the breaker should
40
be X times current of 1 unit. “X” indicates the number of inverters connected in parallel.
Recommended breaker specification of AC input with single phase:
Model 2 units 3 units 4 units 5 units 6 units 7 units 8 units 9 units
80A/ 120A/ 160A/ 200A/ 240A/ 280A/ 320A/ 360A/
6KW-48V
230VAC 230VAC 230VAC 230VAC 230VAC 230VAC 230VAC 230VAC
Note1: Also, you can use 50A breaker for 4KW/5KW for only 1 unit and install one breaker at its AC input in
each inverter.
Note2: Regarding three-phase system, you can use 4-pole breaker directly and the rating of the breaker
should be compatible with the phase current limitation from the phase with maximum units
Recommended battery capacity
Battery Capacity for 400AH 600AH 800AH 1000AH 1200AH 1400AH 1600AH 1800AH
6KW-48V
WARNING! Be sure that all inverters will share the same battery bank. Otherwise, the inverters will transfer to
fault mode.
41
5-1. Parallel Operation in Single phase
Two inverters in parallel:
Power Connection
N
L
N
Load L
Communication Connection
N
L
N
Load L
42
Communication Connection
N
L
N
Load L
Communication Connection
N
L
N
Load L
43
Communication Connection
N
L
N
Load L
Communication Connection
N
L
N
Load L
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼
44
Eight inverters in parallel:
Power Connection
N
L
N
Load L
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼ ❽
N
L
N
Load L
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼ ❽ ❾
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
45
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼ ❽ ❾
Three inverters in one phase, three inverters in second phase and two inverter for the third phase:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼ ❽
Three inverters in one phase, two inverters in second phase and two inverters for the third phase:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
❶ ❷ ❸ ❹ ❺ ❻ ❼
46
Two inverters in each phase:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
Seven inverters in one phase and one inverter for the other two phases:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
P1
P2 P3
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
Note: If there is only one unit in one phase, this unit doesn’t need to connect the current sharing cable.
Or you connect it like as below:
47
⑧
Four inverters in one phase and one inverter for the other two phases:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
Three inverters in one phase, two inverters in second phase and one inverter for the third phase:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
48
Communication Connection
Three inverters in one phase and only one inverter for the remaining two phases:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
Two inverters in two phases and only one inverter for the remaining phase:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
49
Communication Connection
Two inverters in one phase and only one inverter for the remaining phases:
Power Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
Communication Connection
P1 P2 P3
N
L1
L2
L3
N
Load L1
L2
L3
50
Communication Connection
WARNING: Do not connect the current sharing cable between the inverters which are in different phases.
Otherwise, it may damage the inverters.
6. PV Connection
Please refer to user manual of single unit for PV Connection.
CAUTION: Each inverter should connect to PV modules separately.
51
7. LCD Setting and Display
Setting Program:
52
Fault code display:
80 CAN fault
81 Host loss
82 Synchronization loss
8. Commissioning
Parallel in single phase
Step 1: Check the following requirements before commissioning:
Correct wire connection
Ensure all breakers in Line wires of load side are open and each Neutral wires of each unit are connected
together.
Step 2: Turn on each unit and set “PAL” in LCD setting program 28 of each unit. And then shut down all units.
NOET: It’s necessary to turn off switch when setting LCD program. Otherwise, the setting can not be
programmed.
Step 3: Turn on each unit.
LCD display in Master unit LCD display in Slave unit
53
Step 4: Switch on all AC breakers of Line wires in AC input. It’s better to have all inverters connect to utility at
the same time. If not, it will display fault 82 in following-order inverters. However, these inverters will
automatically restart. If detecting AC connection, they will work normally.
LCD display in Master unit LCD display in Slave unit
Step 5: If there is no more fault alarm, the parallel system is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the
load.
Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and three phases are
matched with unit setting, they will work normally. Otherwise, the AC icon will flash and they will not work
in line mode.
LCD display in L1-phase unit LCD display in L2-phase unit LCD display in L3-phase unit
Step 5: If there is no more fault alarm, the system to support 3-phase equipment is completely installed.
Step 6: Please switch on all breakers of Line wires in load side. This system will start to provide power to the
load.
Note 1: To avoid overload occurring, before turning on breakers in load side, it’s better to have whole system in
operation first.
Note 2: Transfer time for this operation exists. Power interruption may happen to critical devices, which cannot
bear transfer time.
54
9. Trouble shooting
Situation
Fault Solution
Fault Event Description
Code
1. Restart the inverter.
2. Check if L/N cables are not connected reversely in all inverters.
3. For parallel system in single phase, make sure the sharing are
Current feedback into
connected in all inverters.
60 the inverter is
For supporting three-phase system, make sure the sharing cables are
detected.
connected in the inverters in the same phase, and disconnected in the
inverters in different phases.
4. If the problem remains, please contact your installer.
1. Update all inverter firmware to the same version.
The firmware version 2. Check the version of each inverter via LCD setting and make sure the
71 of each inverter is not CPU versions are same. If not, please contact your instraller to provide
the same. the firmware to update.
3. After updating, if the problem still remains, please contact your installer.
The output current of
1. Check if sharing cables are connected well and restart the inverter.
72 each inverter is
2. If the problem remains, please contact your installer.
different.
80 CAN data loss
1. Check if communication cables are connected well and restart the
81 Host data loss
inverter.
Synchronization data
82 2. If the problem remains, please contact your installer.
loss
1. Make sure all inverters share same groups of batteries together.
2. Remove all loads and disconnect AC input and PV input. Then, check
The battery voltage of battery voltage of all inverters. If the values from all inverters are close,
83 each inverter is not the please check if all battery cables are the same length and same material
same. type. Otherwise, please contact your installer to provide SOP to calibrate
battery voltage of each inverter.
3. If the problem still remains, please contact your installer.
1. Check the utility wiring conncetion and restart the inverter.
AC input voltage and 2. Make sure utility starts up at same time. If there are breakers installed
84 frequency are detected between utility and inverters, please be sure all breakers can be turned
different. on AC input at same time.
3. If the problem remains, please contact your installer.
1. Restart the inverter.
2. Remove some excessive loads and re-check load information from LCD
AC output current
85 of inverters. If the values are different, please check if AC input and
unbalance
output cables are in the same length and material type.
3. If the problem remains, please contact your installer.
1. Switch off the inverter and check LCD setting #28.
2. For parallel system in single phase, make sure no 3P1, 3P2 or 3P3 is set
AC output mode
86 on #28.
setting is different.
For upporting three-phase system, make sure no “PAL” is set on #28.
3. If the problem remains, please contact your installer.
55