Useful Concepts
Useful Concepts
Useful Concepts
The first numeral in the rating indicates the equipment’s protection against
solid objects. To keep out objects larger than 1mm in size, you will need an
IP4* enclosure rating.
The second numeral in the rating indicates the equipment’s protection against
the harmful ingress of water, To keep out spraying of water from all directions,
you will need an IP*4 rating.
So to provide both protections simultaneously, you will need an IP44 enclosure
for the equipment.
NEMA Enclosure Rating
NEMA is an acronym for National Electrical Manufacturers’ Association. This is
a US-based organization who develop and maintain standards for certain
electrical products, primarily for use in North America.
The NEMA enclosure rating system, in addition to ingress protection, is also
concerned with weather-related protection, e.g. protection against icing, sleet
and snow. It also is concerned with the nature of the liquid which is being
protected against – is it corrosive or chemically reactive? These factors will
influence the design of the enclosure and the material it is made from. In the
IEC system, these factors are covered by separate standards.
In the NEMA system, there is no direct equivalent to IEC IP44. The nearest is
NEMA 12, which is closer to IP55. This provides protection against ingress of
dust and against low pressure water jets from all directions.
Why does the middle leg of a three phase transformer have a low reluctance in
the outer two legs of the 3 phase transformer?
The reluctance of the magnetic path around each coil of a three phase
transformer is a function of the length of the core material. The longer the
length of this path for a particular coil, the higher the reluctance and the less
the magnetising inductance.
If you study the three phase core as depicted above, you will note that each
coil has effectively two parallel magnetic paths. Coil A has paths through limbs
B & C. Coil B has paths through limbs A & C. Coil C has paths through limbs A &
B. The average path length for the centre coil B is less than that for outer coils
A & C. So the reluctance of the centre coil’s magnetic path will be less than
that of each of the outer coil, and its inductance will be higher.
So if you run a magnetising current test on a three phase transformer, the
centre winding will always have a lower magnetising current.
What are the differences between a linear transformer and a switching
transformer?
A linear power supply transforms the mains, and rectifies and filters the
transformer secondary to create DC.. This may be further regulated before
connection to the load.
The transformer in this linear power supply is operating at mains frequency (50
or 60Hz) So it has a laminated silicon steel core. The transformer is
comparatively large and heavy.
A switching power supply typically directly rectifies the mains, then “chops”
the resulting DC into the primary of the transformer. The secondary is rectified
and filtered, and a voltage signal is fed back by an optocoupler to the primary
to allow control of the chopper duty cycle to regulate the secondary voltage.
The transformer in this switching power supply is operating at the “chop”
frequency. This may be 20kHz or greater. At this frequency, to transform the
same amount of power as a linear power supply, the transformer will be
comparatively much smaller. The number of turns on each winding will be a lot
less, as a consequence of the high frequency operation. The core will be made
of a ferrite material. The windings (especially the secondary) are likely to be
“multifilar”, that is, having two or more skinnier wires wound in parallel. This
reduces the “skin effect” which is a phenomenon which becomes serious at
high frequency and can increase the effective AC resistance of the winding
wires.
Comparison summary
A linear transformer has a laminated steel core. It will be larger and heavier
than a switch mode transformer.
A switching transformer has a powdered ferrite or similar core. This material
performs well at higher frequencies. It has a high electrical resistance which
eliminates eddy currents in the core. This core may be “gapped” with an
insulator to give the transformer a known inductance, Each winding will have
way fewer turns than an equivalent linear transformer, as a result of running it
at a high frequency. Windings may be multifilar wound to reduce the skin
effect which gets worse at high frequency.
Where are shell type and core type transformer used? Why?
It is a choice made by the designer, mostly. There is no hard and fast rule. But
there are some trends that we see are based on mere practicalities.
Yes, it absolutely can be done. This is done every day. The easiest example for
you to see is for you to drive around and look at utility poles that have 3
transformers hanging on them. These are distribution transformers. You will
likely find them near fast food restaurants and small shopping centers.
This is also done in the transmission system, although typically found in older
systems/equipment. Newer power transformers are generally one transformer
with all three phases isolated inside around a metal core, instead of 3 stand-
alone transformers.
The advantages are plentiful, but the basic, obvious ones are power availability
and capacity. You can get much more true power out of a 3–phase system than
a single phase source.
You can connect 3 single phase transformers, one in each phase, instead of
one 3 phase transformer. They will work just as fine.
But what is the advantage? A 3 phase transformer consumes far lesser
material than 3 single transformers. Space requirements are significantly
smaller, and costs are much lower. Connections also become little
cumbersome. Switchgear also increases.
Yes, three single phase transformer can connect in three seperate phase and
three phase output can take out. Advantage is three transformer no need
same rating. If three phase load is not balanced the one or two transformer
may larger size for extra single phase load. other way if any one transformer
transformer is out of order then others two can run for single phase load.
What is the voltage between neutral and earth in a 3phase system?
In a 3ph/3w system, there is no neutral, so the question is not applicable.
In a 3ph/4w system, the 4th wire (neutral) is the earthed star-point of the
distribution transformer.
Close to the source - the transformer - the voltage of the neutral should be
very near to zero.
If the load on the system is balanced 3ph, then there should never be any
neutral current, so the neutral voltage wrt earth remains at zero.
If there are unbalanced (single phase) loads, then the out-of-balance currents
need to flow through the neutral to get back to the transformer. The voltage of
the neutral will be the product of the vector sums of the neutral currents and
the resistance of the neutral wire. This voltage will tend to get larger as the
distance from the transformer increases.
The maximum neutral voltage permissible will depend on the standards of the
distribution company, but should never exceed a few volts in a 400/230v
domestic supply.
So how does this three-phase half-wave rectifier circuit work. The anode of
each diode is connected to one phase of the voltage supply with the cathodes
of all three diodes connected together to the same positive point, effectively
creating a diode-“OR” type arrangement. This common point becomes the
positive (+) terminal for the load while the negative (-) terminal of the load is
connected to the neutral (N) of the supply.
Assuming a phase rotation of Red-Yellow-Blue (VA – VB – VC) and the red phase
(VA) starts at 0o. The first diode to conduct will be diode 1 (D1) as it will have a
more positive voltage at its anode than diodes D2 or D3. Thus diode D1 conducts
for the positive half-cycle of VA while D2 and D3 are in their reverse-biased
state. The neutral wire provides a return path for the load current back to the
supply.
120 electrical degrees later, diode 2 (D2) starts to conduct for the positive half-
cycle of VB (yellow phase). Now its anode becomes more positive than diodes
D1 and D3 which are both “OFF” because they are reversed-biased. Similarly,
120o later VC (blue phase) starts to increase turning “ON” diode 3 (D3) as its
anode becomes more positive, thus turning “OFF” diodes D1 and D2.
Then we can see that for three-phase rectification, whichever diode has a
more positive voltage at its anode compared to the other two diodes it will
automatically start to conduct, thereby giving a conduction pattern of:
D1 D2 D3 as shown.
Half-wave Three-phase Rectifier Conduction Waveform
From the above waveforms for a resistive load, we can see that for a half-wave
rectifier each diode passes current for one third of each cycle, with the output
waveform being three times the input frequency of the AC supply. Therefore
there are three voltage peaks in a given cycle, so by increasing the number of
phases from a single-phase to a three-phase supply, the rectification of the
supply is improved, that is the output DC voltage is smoother.
For a three-phase half-wave rectifier, the supply voltages VA VB and VC are
balanced but with a phase difference of 120o giving:
VA = VP*sin(ωt – 0o)
VB = VP*sin(ωt – 120o)
VC = VP*sin(ωt – 240o)
Thus the average DC value of the output voltage waveform from a 3-phase
half-wave rectifier is given as:
Where: VS is equal to (VL(PEAK) ÷ √3) and where VL(PEAK) is the maximum line-to-
line voltage (VL*1.414).
3-phase Rectification Example No2
A 3-phase full-wave bridge rectifier is required to fed a 150Ω resistive load
from a 3-phase 127 volt, 60Hz delta connected supply. Ignoring the voltage
drops across the diodes, calculate: 1. the DC output voltage of the rectifier and
2. the load current.
1. the DC output voltage:
The RMS (Root Mean Squared) line voltage is 127 volts. Therefore the line-to-
line peak voltage (VL-L(PEAK)) will be:
As the supply is 3-phase, the phase to neutral voltage (VP-N) of any phase will
be:
Thus the average DC output voltage from the 3-phase full-wave rectifier is
given as:
Again, we can reduce the maths a bit by correctly saying that for a given line-
to-line RMS voltage value, in our example 127 volts, the average DC output
voltage is:
As the spaces between each half-wave developed by each diode is now being
filled in by the other diode the average DC output voltage across the load
resistor is now double that of the single half-wave rectifier circuit and is
about 0.637Vmax of the peak voltage, assuming no losses.
Where: VMAX is the maximum peak value in one half of the secondary winding
and VRMS is the rms value.
The peak voltage of the output waveform is the same as before for the half-
wave rectifier provided each half of the transformer windings have the same
rms voltage value. To obtain a different DC voltage output different
transformer ratios can be used.
The main disadvantage of this type of full wave rectifier circuit is that a larger
transformer for a given power output is required with two separate but
identical secondary windings making this type of full wave rectifying circuit
costly compared to the “Full Wave Bridge Rectifier” circuit equivalent.
The Full Wave Bridge Rectifier
Another type of circuit that produces the same output waveform as the full
wave rectifier circuit above, is that of the Full Wave Bridge Rectifier. This
type of single phase rectifier uses four individual rectifying diodes connected in
a closed loop “bridge” configuration to produce the desired output.
The main advantage of this bridge circuit is that it does not require a special
centre tapped transformer, thereby reducing its size and cost. The single
secondary winding is connected to one side of the diode bridge network and
the load to the other side as shown below.
The Diode Bridge Rectifier
The four diodes labelled D1 to D4 are arranged in “series pairs” with only two
diodes conducting current during each half cycle. During the positive half cycle
of the supply, diodes D1 and D2 conduct in series while diodes D3 and D4 are
reverse biased and the current flows through the load as shown below.
The Positive Half-cycle
During the negative half cycle of the supply, diodes D3 and D4 conduct in
series, but diodes D1 and D2 switch “OFF” as they are now reverse biased. The
current flowing through the load is the same direction as before.
The Negative Half-cycle
The blue plot on the waveform shows the result of using a 5.0uF smoothing
capacitor across the rectifiers output. Previously the load voltage followed the
rectified output waveform down to zero volts. Here the 5uF capacitor is
charged to the peak voltage of the output DC pulse, but when it drops from its
peak voltage back down to zero volts, the capacitor can not discharge as
quickly due to the RC time constant of the circuit.
This results in the capacitor discharging down to about 3.6 volts, in this
example, maintaining the voltage across the load resistor until the capacitor
re-charges once again on the next positive slope of the DC pulse. In other
words, the capacitor only has time to discharge briefly before the next DC
pulse recharges it back up to the peak value. Thus, the DC voltage applied to
the load resistor drops only by a small amount. But we can improve this still by
increasing the value of the smoothing capacitor as shown.
50uF Smoothing Capacitor
Here we have increased the value of the smoothing capacitor ten-fold from
5uF to 50uF which has reduced the ripple increasing the minimum discharge
voltage from the previous 3.6 volts to 7.9 volts. However, using the Partsim
Simulator Circuit we have chosen a load of 1kΩ to obtain these values, but
as the load impedance decreases the load current increases causing the
capacitor to discharge more rapidly between charging pulses.
The effect of a supplying a heavy load with a single smoothing or reservoir
capacitor can be reduced by the use of a larger capacitor which stores more
energy and discharges less between charging pulses. Generally for DC power
supply circuits the smoothing capacitor is an Aluminium Electrolytic type that
has a capacitance value of 100uF or more with repeated DC voltage pulses
from the rectifier charging up the capacitor to peak voltage.
However, there are two important parameters to consider when choosing a
suitable smoothing capacitor and these are its Working Voltage, which must
be higher than the no-load output value of the rectifier and its Capacitance
Value, which determines the amount of ripple that will appear superimposed
on top of the DC voltage.
Too low a capacitance value and the capacitor has little effect on the output
waveform. But if the smoothing capacitor is sufficiently large enough (parallel
capacitors can be used) and the load current is not too large, the output
voltage will be almost as smooth as pure DC. As a general rule of thumb, we
are looking to have a ripple voltage of less than 100mV peak to peak.
The maximum ripple voltage present for a Full Wave Rectifier circuit is not
only determined by the value of the smoothing capacitor but by the frequency
and load current, and is calculated as:
Bridge Rectifier Ripple Voltage
The anode terminal of the diode is connected to the secondary winding of the
transformer. And the three phases of the transformer is connected together at
a common point called neutral. This neutral point provides the negative
terminal to the load and is earthed.
Each diodes conducts for one third of the AC cycle and remaining two diodes
will remains open circuit. The ouput DC voltage will be between the peak value
of supply voltage and half of the supply voltage.
The ripple factor for 3 phase half wave rectifier is derived in the equations
below.
It is evident from the above calculations that the ripple factor for the 3 phase
half wave rectifier is 0.17 i.e. 17%. In single phase half have rectifier the value
of ripple factor is 1.21 and in case of single phase full wave rectifier it
is 0.482. Thus, it is evident that the value of ripple factor in 3 phase rectifier is
very less in comparison to single phase rectifier.
Moreover, the frequency of the ripples in three phase rectifier is very high.
Thus, due to this these ripples can be easily filtered. The ripple frequency in
case of three phase rectifiers is three times of the supply frequency. Due to
this smoothing process is very easy in case of three phase rectifier than that of
single phase rectifier.
3 Phase Full Wave Rectifier
In three phase full wave rectifier six diodes are used. It is also called 6-diode
half wave rectifier. In this each diode conducts for 1/6th part of the AC cycle.
The output DC voltage fluctuations are less in 3 phase full wave rectifiers. The
output voltage fluctuates between maximum value of peak voltage i.e Vsmax
and 86.6% of the maximum voltage.
The advantage of 3 phase full wave rectifiers is that the output voltage is
regulated and do not falls to zero. The output voltage is maintained
between 86.6% of the maximum voltage and the peak value of the voltage.
Thus, it appears regulated.
The main reason behind this low fluctuation in output voltage is the usage of
large number of diodes. It is appropriate to use 6 diodes. This is because if
more than 6 diodes are used the cost of the circuit increases. Moreover, the
circuit complexity increases and no significant increase in the regulation in the
output voltage will be there.
3 Phase Bridge Rectifier
The type of arrangement in bridge form is widely used because there is no
need of centre tap transformer in bridge rectifier. The advantage of using
bridge rectifier is that the load current Idc is 0.95 times of the peak current
flowing through the diode.
The Vdc is approximately 2.34 times of the rms value of AC voltage through the
secondary winding of transformer in 3 phase half eave rectifier. Each diode in 3
phase bridge rectifier carries only 1/3 of the current flowing though the load.
Thus, this type of bridge arrangement is more preferred in various applications
They are used to overcome the shortcomings of single-phase rectifier. We have
already discussed that single-phase rectifiers possess high ripple factor and
high fluctuation in DC output. In order to overcome this drawback, 3 phase
transformers came into existence.
BASIC QUESTIONS & ANSWERS about Transformers
1. What is a Transformer?
ANSWER: A transformer is an electrical apparatus designed to convert
alternating current from one voltage to another. It can be designed to "step
up" or "step down" voltages.
2. Is it Possible to Change Three Phase to Two Phase or Vice-Versa with
Standard Transformers?
ANSWER: Yes. This is a very practical application for standard single phase off-
the-shelf transformers. Some typical voltage combinations are as follows: 480
volts three phase to 240 volts two phase, or 240 volts three phase to 480 volts
two phase, or 240 volts three phase to 240 volts two phase. Please refer to us
for an exact schematic.
3. How Does a Transformer Work?
ANSWER: A transformer works on the magnetic induction principle. It has no
moving parts and is a completely static solid state device, which insures, under
normal operating con¬ditions, a long and trouble-free life. It consists, in its
simplest form, of two or more coils of insulated wire wound on a lami¬nated
steel core. When voltage is introduced to one coil, called the primary, it
magnetizes the iron core. A voltage is induced in the other coil, called the
secondary or output coil. The change of voltage (or voltage ratio) between the
primary and secondary depends on the turns ratio of the two coils.
4. What are Taps and When are They Used?
ANSWER: Taps are provided on some transformers on the high voltage winding
to correct for high or low voltage con¬ditions, and still deliver full rated output
voltages at the sec¬ondary terminals. Standard tap arrangements are at two
and one-half and five percent of the rated primary voltage for both high and
low voltage conditions. For example, if the trans¬former has a 480 volt primary
and the available line voltage is running at 504 volts, the primary should be
connected to the 5% tap above normal in order that the secondary voltage be
maintained at the proper rating.
5. What is the Difference Between "Insulating", "Isolating", and "Shielded
Winding" Transformers?
ANSWER: Insulating and Isolating transformers are identical. These terms are
used to describe the isolation of the primary and secondary windings, or
insulation between the two. A shielded winding transformer, on the other
hand, is designed with a metallic shield between the primary and secondary
windings, providing a safety factor by grounding, thus pre¬venting accidental
contact between windings under faulty con¬ditions. All two, three and four
winding transformers are of the insulating or isolating types. Only
autotransformers, which are a type whose primary and secondary are
connected to each other electrically, are not of the insulating or isolating
variety.
6. Can Transformers be Operated at Voltages other than Nameplate Voltages?
ANSWER: In some cases, transformers can be operated at voltages below the
nameplate rated voltage. In NO case should a transformer be operated at a
voltage in excess of its name- plate rating unless taps are provided for this
purpose. When operating below the rated voltage the KVA capacity is reduced
correspondingly. For example, if a 480 volt primary trans¬former with a 240
volt secondary is operated at 240 volts, the secondary voltage is reduced to
120 volts and if the trans¬former were originally rated 10 KVA, the reduced
rating would be 5 KVA, or in direct proportion to the applied voltage.
7. Can 50-Hz Transformers be Operated at 60 Hz & Vice versa ?
ANSWER: 50 Hz Transformers rated below 1 KVA can be utilized on 60 Hz
service. However - transformers of 1 KVA & Larger rated at 60 HZ should not
be used on 50 Hz service due to higher losses and resultant heat rise .
8. Can Transformers be Used in Parallel?
ANSWER: Single phase transformers can be used in parallel only when their
impedances and voltages are equal. If unequal voltages are used a circulating
current exists in the closed network between the two transformers which will
cause excess heating and result in a shorter life of the transformer. In addition,
impedance values of each transformer must be within > 7.5 % of each other.
For "example: Transformer A has an impedance 4%, transformer B which is to
be parallel to A must have an impedance between the limits of 3.7 % & 4.3%.
When paralleling three phase transformers the same precautions must be
observed as listed above, plus the angular displacement and phasing between
the two transformers must be identical. The resultant KVA when paralleling
two or more transformers is 2 times the nameplate KVA of the smallest
transformer in the parallel system.
9. Can 60 Hz Transformers be Used at Higher Frequencies?
ANSWER: Transformers can be used at fre¬quencies above 50 Hz up through
400 Hz with no limitations provided nameplate voltages are not exceeded.
However, 50 Hz transformers will have less voltage regulation at 400 Hz than at
50 Hz. Where better regulation and smaller physical size are required, contact
us for special 400 Hz designs.
10. What is Meant by Regulation in a Transformer?
ANSWER: Voltage regulation in transformers is the difference between the no
load voltage and the full load voltage. This is usually expressed in terms of
percentage. For example: A transformer delivers 100 volts at no load and the
voltage drops to 95_volts at full load, the regulation would be 5%. Our dry type
distribution transformers generally have regulation from 2% to 4%, depending
on the size and the application for which they are used.
11. What is Meant by Temperature Rise in a Transformer?
ANSWER: Temperature rise in a transformer is the temper¬ature of the
windings and insulation above the existing ambi¬ent or surrounding
temperature, and is determined by the insulation class used in the transformer
coils.
12. What is Meant by Insulation "Class"?
ANSWER: Insulation class was a popular way of referencing insulating materials
in their ability to sustain long life while operating at different temperatures.
Since it Is difficult and at times confusing to describe different insulations by
letter designations, such as A, E, B, F & H; it is better to describe insulation as
"insulation systems".
13. Is One Insulation System Better Than Another?
ANSWER: Not necessarily. For example: Small fractional KVA transformers use
the class 105°C insulation system, which is 55°C rise. The class 150°C insulation
system, which is 80° C rise, has generally been superseded by a class 185° C
insulation system, which is 115° C rise. Medium KVA size transformers,
approximately 371/2 KVA and larger, are generally manufactured using a 220°
C insulation system, which is 150° C rise. All of these insulation systems from
105° C through 220° C will normally have approximately the same number of
years operating life. A well designed transformer, observing these temperature
limits, should have a life expectancy of approximately 20-25 years.
14. Why Should Dry Type Transformers Never be Overloaded?
ANSWER: Overloading of a transformer results in excessive temperature. This
excessive temperature causes overheating which will result in rapid
deterioration of the insulation and cause complete failure of the transformer
coils.
15. Are Temperature Rise and Actual Surface Temperature Related?
ANSWER: No. This can be compared with an ordinary light bulb. The filament
temperature of a light bulb can exceed 2000 degrees, yet the surface
temperature of the bulb is low enough to permit touching with bare hands.
16. What is Meant by "Impedance" in Transformers?
ANSWER: Impedance is the current limiting characteristic of a transformer and
is expressed in percentage.
17. Why is Impedance Important?
ANSWER: It is used for determining the interrupting capacity of a circuit
breaker or fuse employed to protect the primary of a transformer.
18. Can Single Phase Transformers be Used for Three Phase Applications?
ANSWER: Yes. Three phase transformers are sometimes not readily available
whereas single phase transformers can gen¬erally be found in stock. Three
single phase transformers can be used in delta connected primary and wye or
delta connected secondary. They should never be connected wye pri¬mary to
wye secondary, since is will result in unstable Secondary voltages. The
equivalent three phase capacity when properly connected of three single
phase transformers is three times the nameplate rating of each single phase
transformer, or example: Three 10 KVA single phase transformers will
accommodate a 30 KVA three phase load.
19. WHAT is ZIG ZAG Grounding Transformer
ANSWER: Three Single Phase Transformers can be connected to have a three
phase Zig Zag Transformer. This system can be used for either grounding or
developing a fourth WIRE from a three phase neutral. An example would be to
change a 480 V — three phase — three wire system to a 480Y/277 V — three
phase — four wire system.
20. What Color are generally used for Dry Type Transformers?
ANSWER: Normally ligh gray is used on: Single phase 50 VA through 25 KVA
and on three phase 3 KVA through 15 KVA. Light gray is used with a pleasing
blue-gray on the side and top covers on — Single phase 37 ½ KVA through 250
KVA and three phase 20 KVA through 750 KVA.
21. How Do You Select a Transformer to Operate in an Ambient Higher Than
40° Centigrade?
ANSWER: If the 24 hour average ambient does not exceed 40° C, standard
transformers can be used. When the ambient exceeds 40° C use the following
chart for de-rating standard transformers.
Maximum Maximum
Ambient Percentage of
Loading
40° C 100%
50° C 92%
60° C 85%
70° C 78%
Instead of ordering custom built transformers to operate in ambient higher
than 40° C, it is more economical to use a standard transformer of a larger KVA
rating.
22. Can Transformers be Reconnected as Autotransformers to Increase Their
KVA Rating?
ANSWER: Several of standard single phase transformers can be connected as
autotransformers. The KVA capacity will be greatly increased when used as an
Autotransformer, in comparison to the nameplate KVA as an insulating
transformer. Examples of autotransformer applications are changing 600 volts
to 480 volts in either single phase or three phase; changing 480 volts to 240
volts single three phase or vice versa; or the developing of a fourth vire
(neutral) from a 480 volt three phase three wire system or obtaining 277 volts
single phase. This voltage is normally used for operating fluorescent lamps or
similar devices requiring 277 volts.
23. What is Corona and How Does it Affect Dry Type Transformers?
ANSWER: Corona — a type of localized discharge resulting from transient
gaseous ionization in insulation sys¬tems when the voltage stress exceeds a
critical value." In a dry type transformer, part of the insulation system is air,
which is referred to in the definition as gas. If a transformer is not designed
properly and the insulation is overworked, it will result in the development of
ionization of the air which in turn causes deteriorating affects on the insulation
of the trans¬former. This will result in an extremely short life of the
trans¬former. Our transformers are designed so that they are corona-free even
at voltages considerably higher than recommended operating voltages. The
reason is, if a momen¬tary transient voltage occurs and causes corona
inception, the design of the transformer is such that the corona extinction
voltage level is appreciably higher than the operating voltage level; therefore,
corona will not be present during operation.
24. What is BIL and How Does it Apply to our Transformers ?
ANSWER: BIL is an abbreviation for Basic Impulse Level. Impulse tests are
dielectric tests that consist of the applica¬tion of a high frequency steep wave
front voltage between windings, and between windings and ground. The Basic
Impulse Level of a transformer is a method of expressing the voltage surge
(lightning, switching surges, etc.) that a trans¬former will tolerate without
breakdown. All transformers manufactured for 600 volts and below will
with¬stand BIL rating, which is 10 KV. This assures the user that he will not
experience breakdowns when his system is properly protected with lightning
arrestors or similar surge protection devices.
25. What is Polarity, When Associated With a Transformer?
ANSWER: Polarity is the instantaneous voltage obtained from the primary
winding in relation to the secondary winding. Transformers 600 volts and
below are normally connected in additive polarity — that is, the terminals of
the high voltage and low voltage windings on the left hand side are connected
together, This leaves one high voltage and one low voltage terminal
unconnected. When the trans¬former is excited, the resultant voltage
appearing across a voltmeter will be the sum of the high and low voltage
wind¬ings. This is useful when connecting single phase transform¬ers in
parallel for three phase operations. Polarity is a term used only with single
phase transformers.
26. What is Meant by Indoor or Outdoor Transformers?
ANSWER: Indoor transformers are ordinarily defined as trans¬formers suitable
for indoor operation only. Outdoor trans¬formers are intended for indoor or
outdoor operation. The transformers illustrated in this catalog may be used for
either indoor or outdoor operation. However, it is desirable to supply some
protection for the transformer such that it will be shielded from direct
exposure to rain, snow, or submersion in water.
27. Will a Transformer Change Three Phase to Single Phase?
ANSWER: A transformer will not act as a phase changing device when
attempting to change three phase to single phase. There is no way that a
transformer will take three phase in and deliver single phase out while at the
same time presenting a balanced load to the three phase supply system. There
are, however, circuits available to change three phase to two phase or vice
versa using standard dual wound trans¬formers.
28. Range of our Dry Type Transformers?
ANSWER: We manufactures the most complete line available of boost-buck
transformers for applications ranging from 80 to 520 volts single or three
phase.
Further complete engineering and manufacturing facili¬ties are available for
custom designed transformers — frac¬tional through 5000 KVA ratings, low
voltage through 15 KV. Some of the applications in which these custom built
trans¬formers are used are — instrumentation, telecommunications,
computer peripherals, rectifiers, reactors, oven and heating applications, and
various others to match the customer's exact specifications. These
transformers are available in vari¬ous temperature rise and insulation systems,
along with pos¬sible convection, forced air, water, or oil cooling as required by
the customer.
29. How Do You Size a Transformer for Operating a DC Motor?
ANSWER: There are no straight forward simple formulas which can be used in
sizing transformers to operate DC motors. However, the transformer size can
be calculated accurately when the circuit is known for rectifying the AC to DC
for operating the motor. There are a great variety of circuits now in common
use for changing AC to DC. One of the more common circuits is the three phase
full wave bridge circuit employing three SCR's and three diodes.
30. What is Meant by "Balanced Loading" on Single Phase Transformer
Applications?
ANSWER: Since most single phase transformers have a sec¬ondary voltage of
120/240, they will be operated as a three wire system. Care must be taken in
properly distributing the load as the transformer secondary consists of 2
separate 120 volt windings. Each 120 volt winding is rated at one-half the
nameplate KVA rating. For example: A 10 KVA transformer, 120/240 volt
secondary is to service an 8 KVA load at 240 volts and two 1 KVA loads at 120
volts each.
If the incorrect method is used, winding A will be loaded at 6 KVA, and winding
B will be loaded at 4 KVA. These do total 10 KVA but, since each winding is only
rated at 5 KVA (V2 of nameplate rating), we have an overloaded transformer
and a certain failure.
31. What About Balanced Loading on Three Phase?
ANSWER: Each phase of a three phase transformer must be considered as a
single phase transformer when determining loading. For example: A 45 KVA
three phase transformer with a 208Y/120 volt secondary is to service 4 loads at
120 volts single phase each. These loads are 10 KVA, 5 KVA, 8 KVA, and 4 KVA.
Note that maximum loading on any phase does not exceed 10 KVA. Each phase
has a 15 KVA capacity.
5. Scott T Transformers
This is another popular method of generating a single phase supply from a
three phase supply this time using two single phase transformers, The “Main
Transformer” and the “Teaser Transformer” The main transformer is
connected to 2 of the 3 supply lines of the 3 phase system. The teaser
transformer primary is connected between a centre tap on the primary of the
main transformer and the third supply line. Typical currents in the three lines
for the 5KVA load at 400V are 7.5Amps / 10.6Amps / 14.5Amps.
Scott T transformers can be used to supply two separate single phase loads or
the output of the transformers can be joined to supply one single phase load
The main transformer rating is equivalent to 90% of the load rating and the
teaser transformer about 70% giving a total of 160% of the load rating
6.Le-Blanc Transformers
The final 3 phase to single phase converter transformer is the Le-Blanc
transformer. The 5KVA 400V will have line currents of 3.9Amps / 10.6Amps /
14.5Amps
The Earthing or neutral grounding transformer may be two winding with a zig-
zag connected primary and a star connected secondary or a single winding
three phase auto-transformer with windings interconnected star or zig-zag.
Earthing transformer is a three limbed core type transformer having two
equally balanced windings on each core. One set of windings is connected in
stare to provide the neutral point. The others ends of this set of windings are
connected to the second set of windings as shown in figure.
only.
Electrostatic shield.
What is an electrostatic shield?
The electrostatic shield is simply a grounded single turn of conductive
nonferrous foil placed between coils to divert primary noise to ground. The
conductive foil completely enclosing the windings will provide a ground path
for primary circuit noise and has the advantage that a very much smaller
capacitance exists between primary and secondary coils than in the case of a
simple Faraday shield. The enclosing shield will not re-radiate the noise signal,
and will provide effective electromagnetic noise reduction. Typically, according
to Topaz at a distance of 18 inches from a transformer's geometric center, the
field strength will be less than 0.1 gauss, and will roughly follow inverse cube
laws.
Isolation transformers with electrostatic shields are used for power supplies
for sensitive equipment such as computers or laboratory instruments. An
isolation transformer is designed to address the problems associated with
referencing its internal shields to ground. It is constructed with two isolated
Faraday shields between the primary and secondary windings. The shield,
which is closest to the primary winding, is connected to the common power
supply ground and the shield closest to the secondary winding is connected to
the shield of the circuit to be isolated. The use of two shields in the
construction of the isolation transformer diverts high frequency noise, which
would normally be coupled across the transformer to the grounds of the circuit
in which they occur. The two shields provide more effective isolation of the
primary and secondary circuits by also isolating their grounds.
The isolation transformer adds a third capacitance between the two Faraday
shields, which may allow coupling of high frequency noise between the system
grounds. However, increasing the separation between the two Faraday shields
normally minimizes this third capacitance. Additionally, the dielectric effect of
the shields plus the increased separation of the windings significantly reduce
the inter-capacitance between the windings.
Since inter-winding capacitance is the primary path by which significant power
line and transient related noise couples to the system, more information is
needed to describe what occurs. During the time power is being transferred
between transformer windings, noise potentials between the primary circuits
and ground is similarly coupled to the secondary through both capacitive and
resistive paths. This noise appears in three forms normally in a transformer
circuit: common-mode, transverse mode, and electromagnetic.
Common - Mode Noise
This noise appears between both sides of a power line and ground. Since this
noise is referenced to the power system ground, the most obvious method of
eliminating this noise is by grounding the transformer center tap to the system
ground via the lowest impedance path possible. Internal transformer designs,
which separate the coils to reduce capacitive coupling, have some advantage,
but it also increases leakage inductance and reduces the power transfer.
Transverse - Mode
Transverse-mode noise is much more difficult to eliminate than common-mode
noise. The key here is to differentiate between power and noise, and then
reduce the noise. Noise and power are separated by the difference in their
frequencies. The most effective transformer would be a design exactly
opposite to a audio transformer. The purpose is to transfer the power required
by the load at the fundamental power frequency and to eliminate all higher
and lower frequencies. Sub-harmonic frequencies are attenuated by operating
the transformer at relatively high flux density, which is effective in reducing or
eliminating them. Above the fundamental frequency, noise is reduced by
introducing as much leakage inductance as possible, consistent with good
power transfer to the secondary.
Transverse-mode noise appears as a voltage across both the primary and
secondary windings of an isolation transformer. It occurs when a common-
mode noise signal causes current to flow in the primary winding (or secondary
winding), and from there to ground via capacitance to a grounded shield.
Common-mode noise can also be transformed into 'transverse-mode noise,
and thereby, through magnetic coupling, contaminate the secondary of an
isolation transformer. Normally, by the proper selection of core loss verses
primary winding inductance, a well-designed isolation transformer will
eliminate the majority of this type of noise. Here again, grounding the
transformer shield to the lowest impedance path available, will result in noise
currents using this return path rather than some other higher impedance path
to the noise source ground.
Electromagnetic Noise
Electromagnetic noise does not constitute a major problem in most
applications, but is sometimes critical in some recording or digital data
systems, and in making electromagnetic interference measurements.
Rack Level Applications
The most effective application of isolation transformers is with racks of
equipment. A rack acts as an outer shield for internal instruments, while
serving as the zero-signal reference for system output signals. Isolation
transformers are used to control shield currents, and to break up the mutual
capacitance between rack instrumentation and an unknown power ground.
The main benefit of using an isolation transformer with a rack of equipment is
the enhanced control of currents in the equipment shields. Any potential
differences between the utility power ground and the rack's ground will cause
currents to flow in the loop. The isolation transformer allows these "ground"
currents to be directed through a portion of the rack's shielding which will not
effect the operation of sensitive circuits and completely isolates these currents
from the internal equipment reference conductors.
Room Level Applications
It is often necessary to isolate EMC test enclosures from noisy building
grounds. Not only can isolation transformers be used to effectively decouple
building power, but also since they also act as tuned circuits; they reduce the
differential noise from external equipment, which reaches your screen room.
While it is recognized as a second isolation transformer inside the test room
will greatly reduce power line ambient, this section will only consider using
transformers on the power lines to a typical screen room. As with any
transformer, isolation transformers radiate magnetic fields. Physically locating
the transformer adjacent to, or connected to, a screen room may increase
rather than decrease ambient noise. Since the physical case of a transformer,
as well as the primary winding shield, are normally connected to the third-wire
power ground of the supplied power, the secondary winding shield must be
isolated from the transformer case and connected only to the conduit shield
going to the shielded room to achieve proper ground isolation. The conduit
acts as an RF shield for the room's power and completes the connection
between the shielded room and the secondary winding shield in the
transformer. If the transformer is three phase and supplies more than one
room, the best application for isolation between rooms is to use only one
phase for each room, with a limit of three rooms per transformer. With this
approach, power line filters will effectively isolate the room while providing
practical noise attenuation. Proper transformer design, wiring, and, above all,
grounding, are the only effective means of reducing the three types of noise
problems. Grounding should be controlled and use the lowest impedance path
possible (i.e., bonding) to the central reference ground system to insure
maximum attenuation of noise sources. To achieve the maximum protection
from a transformer, not only must it be applied properly, but also the
transformer should be one specially designed for isolation usage. The Shielded
three phase isolation transformers have all the feature of the standard 3 phase
plus they also incorporate a full metallic shield (usually copper or aluminum)
between the 3 phase primary and 3 phase secondary windings. This
electrostatic shield or Faraday Shield, is connected to earth ground and
performs two functions: Its attenuates (filters) voltage transients (voltage
spikes). These shielded 3 phase isolation transformers have an attenuation
ratio of 100 to 1. It filters common mode noise, Attenuation of approximately
30 decibels. The shield three phase isolation transformer is preferred over the
standard three phase isolation transformer because it provides protection to
sensitive and critical equipment. When more that one shielded 3 phase
isolation transformer is used between the source and the load, it is referred to
as a " cascading" and greatly improves power quality.
Key Points //
If the main transformer has a turn’s ratio of 1: 1, then the teaser transformer
requires a turn’s ratio of 0.866: 1 for balanced operation.
The principle of operation of the Scott connection can be most easily seen by
first applying a current to the teaser secondary windings, and then applying a
current to the main secondary winding, calculating the primary currents
separately and superimposing the results.
Application
Main application is for For Industrial Furnace Transformer.
For Traction Purpose:
The power is obtained from the 220 kV or 132 kV or 110 kV or 66 kV, three-
phase, effectively earthed transmission network of the State Electricity Board,
through single-phase transformers or Scott connected transformer installed at
the Traction Substation.
The primary winding of the single-phase transformer is connected to two
phases of the transmission network or where Scott-connected transformer is
used, the primary windings are connected to the three phases of the
transmission network.
The single-phase transformers at a Traction Substation are connected to the
same two phases of the transmission network (referred as single-phase
connection), or alternatively to different pairs of phases- the three single phase
transformers forming a delta-connection on the primary side.[/info_b0x]
Out of three single-phase transformers, one transformer feeds the overhead
equipment (OHE) on one side of the Traction Substation, another feeds the
OHE on the other side of the Traction Substation, and the third remains as
standby. Thus the two single-phase transformers which feed the OHE
constitute an open-delta connection (alternatively, referred as V-connection)
on the three-phase transformers network.
The Scott-connected transformer and V-connected single-phase transformers
are effective in reducing voltage imbalance on the transmission network. The
spacing between adjacent substations is normally between 70 and 100 km.
Form Factor
Definition: The ratio of the root mean square value to the average value of an
alternating quantity (current or voltage) is called Form Factor. The average of
all the instantaneous values of current and voltage over one complete cycle is
known as the average value of the alternating quantities.
Mathematically, it is expressed as:
Ir.m.s and Er.m.s are the roots mean square values of the current and the voltage
respectively, and Iav and Eav are the average values of the alternating current
and the voltage respectively.
For the current varying sinusoidally, the Form Factor is given as:
REVIEW:
The amplitude of an AC waveform is its height as depicted on a graph over
time. An amplitude measurement can take the form of peak, peak-to-peak,
average, or RMS quantity.
Peak amplitude is the height of an AC waveform as measured from the zero
mark to the highest positive or lowest negative point on a graph. Also known
as the crest amplitude of a wave.
Peak-to-peak amplitude is the total height of an AC waveform as measured
from maximum positive to maximum negative peaks on a graph. Often
abbreviated as “P-P”.
Average amplitude is the mathematical “mean” of all a waveform’s points
over the period of one cycle. Technically, the average amplitude of any
waveform with equal-area portions above and below the “zero” line on a
graph is zero. However, as a practical measure of amplitude, a waveform’s
average value is often calculated as the mathematical mean of all the
points’ absolute values (taking all the negative values and considering them
as positive). For a sine wave, the average value so calculated is approximately
0.637 of its peak value.
“RMS” stands for Root Mean Square, and is a way of expressing an AC
quantity of voltage or current in terms functionally equivalent to DC. For
example, 10 volts AC RMS is the amount of voltage that would produce the
same amount of heat dissipation across a resistor of given value as a 10 volt DC
power supply. Also known as the “equivalent” or “DC equivalent” value of an
AC voltage or current. For a sine wave, the RMS value is approximately 0.707
of its peak value.
The crest factor of an AC waveform is the ratio of its peak (crest) to its RMS
value.
The form factor of an AC waveform is the ratio of its RMS value to its average
value.
Analog, electromechanical meter movements respond proportionally to
the average value of an AC voltage or current. When RMS indication is
desired, the meter’s calibration must be “skewed” accordingly. This means that
the accuracy of an electromechanical meter’s RMS indication is dependent on
the purity of the waveform: whether it is the exact same waveshape as the
waveform used in calibrating.
The crest factor is the ratio between the value of the peak current or
voltage(IM or UM) and its r.m.s. value.
E.m.f Equation of Transformer
=4 f Φm Wb/s or volt
Now, rate of change of flux per turn means induced e.m.f in volts.
∴ average e.m.f/ turn = 4 f Φm volt
If the magnitude of flux Φ varies sinusoidally, then the r.m.s value of induced
e.m.f is obtained by multiplying the average value with from factor.