Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Sensepoint-Xcd-Technical-Manual Rev 15

Download as pdf or txt
Download as pdf or txt
You are on page 1of 85

TECHNICAL

MANUAL
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Table of Contents
1. Safety 4
Special conditions for safe use – Sensepoint XCD with Flammable Sensor 6
Special conditions for Sensepoint XCD with Oxygen Sensor 7
2. Information 8
3. Introduction 9
Transmitter 10
Accessories 11
Options 13
3.3.1. Modbus® 13
4. Installation 14
Mounting and location 16
Mounting the transmitter 16
Installing the sensor 18
5. Electrical connections 19
Transmitter Wiring 20
Terminal connections 21
Power 22
Cabling 23
Cable and Earth/Ground regimes 23
Ground Terminal Wiring 24
Modbus RTU Wiring 24
6. Default configuration 26
7. Normal Operation 28
Display Screen 28
System Status 29
Magnetic Wand Activation 30
Mode Structure 30
8. First time switch on (Commissioning) 31
9. Response Check and Calibration 34
Zeroing and span calibration 34
9.1.1. Zero Calibration 35
9.1.2. Span Calibration 36
Zeroing and span calibration of Hydrogen Sulfide sensors 39
10. General Maintenance 40
Operational Life 41
11. Servicing 42
Sensor replacement 43
Replacing Modules within the Transmitter 44
Faults and Warnings 45
12. Menu and Advanced Configuration 46
Abort Function 46
Configuration Mode 46
12.2.1. Configuration mode operation table 50
Sensor / Gas Selection 52
12.3.1. Sensor Selection 52
12.3.2. Gas Selection 52
12.3.3. Set Modbus 53
Review Mode 55
13. General specification 58
14. Ordering information 61
15. Warranty statement 63
16. Installation Drawing 64
Mechanical Installation Drawing 64
Electronic Connection Drawing 65
2
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Duct Mounting Drawing 66


Collecting Cone Drawing 67
Mounting Bolt Assy Drawing 68
Mounting Bracket Drawing 69
17. Certification 70
ATEX/UKEX/IECEx Special Conditions for Safe Use 70
Standard and certification 70
Sensepoint XCD ATEX/UKEX Name Plate 71
Sensepoint XCD UL Name Plate 71
Sensepoint XCD Warning Tag 72
Sensor Cartridges Label 73
Special Conditions for Use in European Gas Performance Approval 73
18. Cross Interference and Cross Calibration 74
Cross Interference Table for Toxic and Oxygen 74
Cross Calibration Flammable Gas Detector 75
Meter Multiplication Factors for Sensepoint XCD-IR Propane 78
Appendix A - Modbus® Protocol A-2 79
A.1 Modbus and the Sensepoint XCD 79
A.2 Modbus Registers 80
A.3 User Configurable Parameter List 81
A.4 Ranges of User Configurable Parameter 82

REVISION HISTORY

Rev. ECO No. Date Comment

12 HAA190090 Mar 2020

13 ECN-00210131 May 2022

14 ECN-00230026 May 2023

15 ECN-00230006 Nov 2023

3
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

1. Safety
Ensure that this Technical Manual is read and understood BEFORE installing/ operating/ maintaining
the equipment. Pay attention to Warnings and Cautions. All document Warnings are listed here and
repeated where appropriate at the start of the relevant chapter(s) of this Technical Manual. Cautions
appear in the sections/sub-sections of the document where they apply.

WARNINGS
Sensepoint XCD is designed for installation and use in Zone 1 or 2 hazardous areas in many countries
including Europe and for Class 1 Division 1 or 2 area applications in North America.
Installation must be in accordance with the recognized standards of the appropriate authority in the
country concerned.
Access to the interior of the detector, when carrying out any work, must only be conducted by trained
personnel.
Before carrying out any work ensure local regulations and site procedures are followed. Appropriate
standards must be followed to maintain the overall certification of the detector.
For installations where conduit is used, and the sensor is mounted directly to the Sensepoint XCD,
there must be a ‘Seal Fitting’ installed for each of the cable gland entries within 18 inches of the
Sensepoint XCD. The total distance of the location of these Seal Fittings is 18 inches. (e.g. If all 3 gland
entries are to be used, 3 Seal Fittings should be located, each within 6 inches of the wiring entrance).
In order to maintain electrical safety, the product must not be operated in atmospheres with more than
21 % oxygen. Oxygen deficient atmospheres (Combustible: less than 10 % v/v, Toxic: less than 6 % v/v)
may suppress the sensor output.
If using an anti-seize compound, the threads should be thinly coated with an approved silicone free
compound e.g. petroleum jelly.
To reduce the risk of ignition of hazardous atmosphere, de-classify the area or disconnect the
equipment from the supply circuit before opening the detector enclosure. Keep assembly tightly
closed during operation.
Never attempt to open a junction box/enclosure or replace/refit the sensor in potentially hazardous
atmospheres while power is still applied to the transmitter.
The detector must be earthed/grounded for electrical safety and to limit the effects of radio frequency
interference. Earth/ground points are provided inside and outside the unit. The internal grounding shall
be used as the primary equipment ground. The external terminal is only a supplemental bonding
connection where local authorities permit or require such a connection.
Ensure that all screens/instrument earth/clean earth wiring is earthed/grounded at a single point (either
at the controller or detector - BUT NOT BOTH) to prevent false readings or alarms that may occur due
to potential earth/ground loops.
Take care when handling sensors as they may contain corrosive solutions. Do not tamper with or in
any way disassemble the sensor.
Do not expose to temperatures outside the recommended ranges.
Do not expose sensors under storage conditions to organic solvents or flammable liquids.
At the end of their working life, replacement electrochemical sensors for oxygen and toxic gas must be
disposed of in an environmentally safe manner. Disposal should be according to local waste
management requirements and environmental legislation.
Alternatively, old replaceable sensors may be securely packaged and returned to Honeywell Analytics
clearly marked for environmental disposal.
Electrochemical sensors should NOT be incinerated as this action may cause the cell to emit toxic
fumes.

4
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Refer to the local or national regulations relative to the installation at the site. For Europe see EN60079-
29-2, EN60079-14, EN45544-4 and EN61241-14.
This equipment is designed and constructed as to prevent ignition sources arising, even in the event
of frequent disturbances or equipment operating faults.
The sensor head must be fitted with the supplied weather protection and mounted so that the sinter is
pointing downward to provide ingress protection IPX6.

The weather protection is a potential electrostatic charging hazard. The manufacturer’s instructions
should be observed.
The transmitter has a potential electrostatic charging hazard. To minimize the risk of electrostatic
discharge:
• Ground the transmitter adequately
• Install the transmitter in a manner that will prevent accidental electrostatic discharges, e.g. ensure
that objects do not rub against the housing etc.
• Clean the enclosure with a damp cloth when necessary
The purchaser should make the manufacturer aware of any External effects or Aggressive substances
that the equipment may be exposed to.
The equipment including the flameproof joints is not intended to be repaired.
When choosing cable and cable gland or conductors in conduit, user should take into account
temperature range. Note that it should be greater than at least 90 °C.

Note: The control card must have a suitably rated fuse.

5
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Special conditions for safe use – Sensepoint XCD with


Flammable Sensor
1. Compliance with the Technical Manual is required for safe use of Sensepoint XCD.
2. The following environmental conditions of operation apply for the use of the
Sensepoint XCD:
Temperature: -20°C to +55°C
Relative humidity: 10 % to 90 %
Pressure: 80 kPa to 120 kPa
(extended range for humidity according to EN 60079-29-1)
3. In order to minimize measurement errors, the ambient conditions (temperature,
pressure, humidity) during the calibration of the measuring channels should be as close
as possible to those to be encountered during normal operation.
4. Measuring values from -8 % LEL to +5 % LEL are indicated as ‘0 % LEL’
(4 mA analogue output) in the measuring mode when deadband is on. When deadband is
off, the negative gas reading shall be indicated on display and mA output. Below -8 %LEL
is indicated as negative fault ‘F03’.
5. Measuring values beyond the end of the measuring range are indicated as
100 % LEL and alternately blinking ‘W04’ and ‘W05’. The analogue output is set to 22 mA.
6. Special states for Analogue output:
• ≤ 1 mA: System and other faults
• 2 mA: Start up, Inhibit
• 4 - 20 mA: Gas reading (when deadband is on)
• 2.4 - 20 mA: Gas reading (when deadband is off)
• 22 mA: Over range
7. If the Sensepoint XCD is operating in conjunction with a control unit to analyse the
measuring signal, only Analogue output (mA output) shall be considered as a safety
function and the control unit must operate correctly when the XCD transmits a value
outside of the measuring range.
8. If substances (e. g. sensor poisons) that could interfere with and affect the sensitivity of
the sensing device are to be expected in the atmosphere to be monitored which may cause
a rapid change of sensitivity, the calibration interval shall be reduced.
9. Before use, ensure that any alarm delay set is suitable for the intended application.
10. Some types and concentrations of dust in the measured atmosphere may impair the
measuring function of the gas detector.
11. Use only with the Weather Protection Cup accessory (P/N SPXCDWP). All accessories
are not the scope of EN 60079-29-1 performance approval.
12. The EC-Type examination certificate only applies to the measuring of Methane, Ethane
and Propane in air and up to the Lower Explosive Limit (LEL). Additional subtests of an
ATEX notified body are required for the measuring of other flammable gases, the results
being informed about as addition to this certificate.

6
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Special conditions for Sensepoint XCD with Oxygen


Sensor
1. Compliance with the Technical Manual is required for safe use of Sensepoint XCD.
2. The following environmental conditions of operation apply for the use of Sensepoint XCD
with oxygen sensor:
Temperature: -20°C to +55°C
Relative humidity: 10 % to 90 %
Pressure: 80 kPa to 120 kPa
(extended range for temperature according to EN 50104)
3. In order to minimise measurement errors, the ambient conditions (temperature, pressure,
humidity) during the calibration of the measuring channels should be as close as possible
to those to be encountered during normal operation.
4. Measuring values from 20.7 % v/v up to 21.1 % v/v are indicated as
‘20.9’ % v/v oxygen during operation in the measuring mode. Measuring values below 3
% v/v oxygen are indicated as 0 % v/v oxygen (analogue output 4 mA).
5. Measuring values above the end of the measuring range are indicated as 25 % v/v O2 and
blinking ‘W04’. The analogue output is set to 22 mA.
Fault messages are shown on the display as ‘F-XX’ and the analogue output is set to
1 mA.
6. Special states for Analogue output:
• ≤ 1 mA: System and other faults
• 2 mA: Start up, Inhibit
• 22 mA: Over ranging
7. If the Sensepoint XCD is operating in conjunction with a control unit to analyse the
measuring signal, the control unit must operate correctly when the XCD transmits a value
outside of the measuring range.
8. Use without Weather Protection Cup accessory (P/N SPXCDWP), only.
9. If substances (e. g. sensor poisons) that could interfere with and affect the sensitivity of
the sensing device are to be expected in the atmosphere to be monitored which may cause
a rapid change of sensitivity, the calibration interval shall be reduced.
10. Before use, ensure that any alarm delay set is suitable for the intended application.
11. Before use, consideration must be given to cross sensitivity to other gases. Refer to the
Sensepoint XCD Technical Manual and the Sensor Datasheet for cross interference data.
12. Some types and concentration of dust in the measured atmosphere may impair the
measuring function of the gas detector.
13. The Type Examination Certificate applies to the measurement of oxygen up to 25 % v/v.

7
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

2. Information
This Technical Manual is for use with the Sensepoint XCD range transmitters only.
The Start-up/Surge/In rush current is dependent on the type of power supply used. The typical start-up
current for Sensepoint XCD is less than 800 mA. Measure the start-up current using the specific power
supply before installation to ensure suitability for your application.
Honeywell Analytics can take no responsibility for installation and/or use of its equipment if not done so
in accordance with the appropriate issue and/or amendment of the Technical Manual.
The reader of this Technical Manual should ensure that it is appropriate in all details for the exact
equipment to be installed and/or operated. If in doubt, contact Honeywell Analytics for advice.

The following types of notices are used throughout this Technical Manual:

WARNING
Identifies a hazardous or unsafe practice which could result in severe injury or death to
personnel.

CAUTION
Identifies a hazardous or unsafe practice which could result in minor injury to
personnel, or product or property damage.

NOTE: Identifies useful/additional information.

Every effort has been made to ensure the accuracy of this document, however, Honeywell Analytics can
assume no responsibility for any errors or omissions in this document or their consequences.
Honeywell Analytics would greatly appreciate being informed of any errors or omissions that may be
found in the content of this document.
For information not covered in this document, or if there is a requirement to send comments/corrections
about this document, contact Honeywell Analytics using the contact details given on the back page.

Honeywell Analytics reserve the right to change or revise the information supplied in this
document without notice and without obligation to notify any person or organization of such
revision or change. If information is required that does not appear in this document, contact the
local distributor/agent or Honeywell Analytics.

EU Directive 2012/19/EU: Waste Electrical and Electronic Equipment


(WEEE)
This symbol indicates that the product must not be disposed of as general
industrial or domestic waste. This product should be disposed of through
suitable WEEE disposal facilities. For more information about disposal of this
product, contact your local authority, distributor or the manufacturer.

8
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

3. Introduction
The Sensepoint XCD comprises a gas detector transmitter and a choice of sensors for detecting
flammable gas, toxic gas and oxygen. The construction of Sensepoint XCD allows it to be used in
hazardous area locations; it may also be used in other areas not classified as hazardous.

The transmitter features a display and three programmable relays for controlling external equipment
e.g. alarms, sirens, valves or switches. The transmitter provides an industry standard
3-wire, 4-20 mA source or sink output for connection to a dedicated gas detection control system or
PLC.

Calibration and maintenance are carried out using a Magnetic Wand, this allows a single user to
undertake routine maintenance without needing to access internal components. Sensepoint XCD is
suitable for use in Zone 1 or 2 hazardous areas (International) or Class I Division 1 or 2 area applications
(North America).

Sensepoint XCD comprises of the main parts as shown below.

Cover

Locking

Enclosure

Diagram 1 Exploded View

9
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Transmitter
The transmitter enclosure has three threaded entries. The two cable/conduit entries either side of the
upper part of the transmitter housing are for connecting the power source, signal output and relay
contacts to associated signalling equipment. The bottom entry allows direct connection of the sensor
socket. There is a mounting plate incorporated into the transmitter housing allowing for various mounting
configuration options.

A local LCD provides gas type, concentration, alarm and operating status. The display provides
numerical, bar graph and icon information.

Diagnostic information may also be displayed when the transmitter is interrogated using a magnet. The
transmitter cover has a glass window which allows use of the Magnetic Wand to activate the three-user
interface magnetic switches that are located on the front of the display module. The magnet also enables
a non-intrusive, one-man calibration and configuration facility for the Sensepoint XCD Flammable, Toxic
and Oxygen Gas sensors
The Sensepoint XCD transmitter is designed to work with a variety of gas sensors for detecting
flammable gases. Sensepoint XCD sensors use NDIR infrared and electro-catalytic technologies.
In addition, the Sensepoint XCD transmitter is designed to work with a wide range of toxic gas
sensors. Sensepoint XCD sensors for monitoring toxic gas or oxygen use electro-chemical cell
(ECC) technology. Oxygen sensors measure Oxygen deficiency and enrichment in the range
0 – 25 % v/v. They do not measure inertisation.

Diagram 2 Sensepoint XCD Display and Magnetic Switches

10
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Diagram 3 Sensepoint XCD Flammable, Toxic and Oxygen Sensor Cartridge

Accessories
A range of accessories are available to allow use of Sensepoint XCD in a wide variety of applications.
These including mounting brackets, maintenance tools, weather housings, flow housing, collecting cone,
duct mounting kit and sensor junction boxes.

Magnetic wand
Standard Weather Protection
The magnetic wand (P/N: SPXCDMAG) is
The Standard Weather Protection (P/N: used as a tool to allow the user to
SPXCDWP) is designed to protect the sensor communicate with the Sensepoint XCD
from changes in environmental conditions. This is transmitter for the purpose of configuration,
recommended to be fitted to a Sensepoint XCD calibration and interrogating system status,
sensor for outdoor exposed applications, (supplied with XCD kit).
(supplied with XCD kit).

Gassing Cap
Pipe mounting bracket
The gassing cap, also known as calibration cap,
The Pipe Mounting Bracket (P/N: SPXCDMTMB) (P/N: S3KCAL) is an optional accessory to be
is an optional accessory and may be used to used in gas calibration and bump test of the
allow the Sensepoint XCD to be installed onto a Sensepoint XCD.
dedicated mounting post or existing structure at
the desired location.

11
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Collecting cone Duct mounting kit

The Collecting Cone (P/N: SPXCDCC) is an The Duct Mounting Kit (P/N: SPXCDDMK) is an
optional accessory that may be fitted to the optional accessory that is designed for applications
Weather Protection. The collecting cone is to allow the monitoring for the presence of gas
designed for use with lighter than air. inside a Heating, Ventilation or Air Conditioning
(HVAC) duct is required.

Typical Mounting Arrangement


Sunshade Deluge Cover Arrangement

The XCD Sunshade Deluge Cover (P/N:


SPXCDSDP) is an optional accessory that may
be fitted to the integral mounting plate. This
accessory is designed to protect XCD from
overheating in exposed hot and arid climates,
particularly offering additional protection from
thermal shock in Tropical Environments

12
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Options
3.3.1. Modbus®

Note: Modbus® option is NOT tested as part of the performance approvals.

The optional Modbus® interface is one of the most common field buses in the industry and allows the
Sensepoint XCD to connect to a bus of devices and transmit data to PLCs or controllers (see Appendix
A). Connections to the Sensepoint XCD are made through a pluggable terminal block on the Modbus ®
interface circuit board. Modbus® RTU protocol uses ASCII/Hex protocols for communication. and allows
all transmitter/sensor front panel functions to be transmitted using this industrial fieldbus. Modbus ®
protocol is a Master-Slaves protocol. Only one master (at the same time) is connected to the bus and
one or up to 32 slave nodes are also connected to the same serial bus. Modbus ® communication is
always initiated by the master. The slave nodes will never transmit data without receiving a request
from the master node. The slave nodes will never communicate with each other. The master node
initiates only one Modbus® transaction at the same time.
Modbus® option is available only for selected gases. Please refer to chapter 14 Ordering information.
To find out if a unit has the Modbus® option fitted, look at the part number on the product label. Units
fitted with Modbus® have the letter ‘M’ at the end of the part number.

Note: Modbus® is a registered trademark of Schneider Automation Inc.

13
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

4. Installation

WARNINGS
Sensepoint XCD is designed for installation and use in Zone 1 or 2 hazardous areas in many
countries including Europe and for Class 1 Division 1 or 2 area applications in North America.
Installation must be in accordance with the recognized standards of the appropriate authority in
the country concerned.
Access to the interior of the detector, when carrying out any work, must only be conducted by
trained personnel.
Before carrying out any work ensure local regulations and site procedures are followed.
Appropriate standards must be followed to maintain the overall certification of the detector.
Care should be taken when removing and refitting the Sensepoint XCD plug-in Sensor to the
Sensor Socket so that damage to the connection pins can be avoided.
For installations where conduit is used, and the sensor is mounted directly to the Sensepoint
XCD, there must be a ‘Seal Fitting’ installed for each of the cable gland entries within 18
inches of the Sensepoint XCD. For installations where the sensor will be mounted remotely
from Sensepoint XCD, an additional ‘Seal Fittings’ will be required: One at each of the conduit
entries for the power/signal/relay contact outputs and one at the sensor wiring entrance. The
total distance of the location of these Seal Fittings is 18 inches. (e.g. If all 3 gland entries are
to be used, 3 Seal Fittings should be located, each within 6 inches of the wiring entrance).
If using an anti-seize compound, the threads should be thinly coated with an approved silicone
free compound e.g. petroleum jelly.
To reduce the risk of ignition of hazardous atmosphere, de-classify the area or disconnect the
equipment from the supply circuit before opening the detector enclosure. Keep assembly tightly
closed during operation.
Never attempt to open a junction box/enclosure or replace/refit the sensor in potentially
hazardous atmospheres while power is still applied to the transmitter.
The detector must be earthed/grounded for electrical safety and to limit the effects of radio
frequency interference. Earth/ground points are provided inside and outside the unit. Ensure
that all screens/instrument earth/clean earth wiring is earthed/grounded at a single point (either
at the controller or detector - BUT NOT BOTH) to prevent false alarms due to earth/ground
loops.
Take care when handling sensors as they may contain corrosive solutions.
Do not tamper with or in any way disassemble the sensor.
Do not expose to temperatures outside the recommended ranges.
Do not expose sensors under storage conditions to organic solvents or flammable liquids.
At the end of their working life, replacement electrochemical sensors for oxygen and toxic gas
must be disposed of in an environmentally safe manner. Disposal should be according to local
waste management requirements and environmental legislation.
Alternatively, old replaceable sensors may be securely packaged and returned to Honeywell
Analytics clearly marked for environmental disposal.
Electrochemical sensors should NOT be incinerated as this action may cause the cell to emit
toxic fumes.
Refer to the local or national regulations relative to the installation at the site. For Europe see
EN60079-29-2, EN60079-14, EN45544-4 and EN61241-14.

14
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

This equipment is designed and constructed as to prevent ignition sources arising, even in the
event of frequent disturbances or equipment operating faults.
The sensor head must be fitted with the supplied weather protection and mounted so that the
sinter is pointing downward to provide ingress protection IPX6.
The weather protection is a potential electrostatic charging hazard. The manufacturer’s
instructions should be observed.
The transmitter has a potential electrostatic charging hazard. To minimize the risk of
electrostatic discharge:
• Ground the transmitter adequately
• Install the transmitter in a manner that will prevent accidental electrostatic discharges,
e.g. ensure that objects do not rub against the housing etc.
• Clean the enclosure with a damp cloth when necessary
The purchaser should make the manufacturer aware of any External effects or Aggressive substances
that the equipment may be exposed to.

Note: The control card must have a suitably rated fuse.

15
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Mounting and location

CAUTION
The location of gas detectors should be made in accordance with any relevant local
and national legislation, standards or codes of practice. Always replace sensors
with a sensor of the same type.

Gas detectors should be mounted where a potential hazard of gas is most likely to be present.
The following points should be noted when locating gas sensors.

When locating detectors consider the possible damage caused by natural events e.g. rain or flooding.
Consider ease of access to the gas detector for functional testing and servicing. Consider how escaping
gas may behave due to natural or forced air currents.

Note: The placement of gas detectors should be determined following the advice of experts having
specialist knowledge of gas dispersion, experts having knowledge of the process plant system and
equipment involved, safety and engineering personnel. The agreement reached on the location of
detectors should be recorded.

Mounting the transmitter


The Sensepoint XCD transmitter has an integral mounting plate consisting of four mounting holes
on the transmitter body. The transmitter may be fixed directly to a surface mounting, or to a horizontal
or vertical pipe/structure, 40.0-80.0 mm (1.6 to 3.1 inches) in diameter/cross section. The Pipe Mounting
Bracket accessory (optional accessory) may be used for this purpose.

M20 entries for


ATEX/IECEx/AP
Versions and 3/4' NPT
cable/conduit entries on
UL/CSA versions

All dimensions are


shown in mm

Diagram 4 Outline and mounting dimensions

16
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Diagram 5 Mounting arrangements

To mount the Sensepoint XCD transmitter to a Vertical or Horizontal pipe/structure, use the optional
Sensepoint XCD Mounting Kit and following procedure:

Fit the four spring washers, then the plain washers to the M8 x 80 mm SS316 bolts.
Pass the four bolts through the four mounting holes of the transmitter housing.

Note: If the Sensepoint XCD sunshade is to be used then fit the sunshade and the two locking bolts
and washers to the M8 x 80 bolts.

Place the transmitter housing against the mounting position and fit the two ‘U’ channel mounting
bars the other side of the pipe/structure.
Secure bolts to the threaded holes of the ‘U’ channel mounting bars.
Tighten the four bolts securely, (but do not over-tighten) until the transmitter housing cannot be moved
by hand on its mounting position.

Note: For further details of installation refer to chapter 16.

17
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Installing the sensor


The XCD gas sensor cartridge plugs into the XCD Sensor Socket.

Diagram 6 Installing the Sensor

WARNINGS
Care should be taken when removing and refitting the Sensepoint XCD plug-in Sensor to
the Sensor Socket so that damage to the connection pins can be avoided.
If using an anti-seize compound, the threads should be thinly coated with an approved silicone
free compound e.g. petroleum jelly.
Take care when handling old sensors as they may contain corrosive solutions.
Take care when removing or replacing the Sensor Retainer as there may be sharp edges
present on the adjoining threads.
The equipment is designed and constructed as to prevent ignition sources arising, even in the
event of frequent disturbances or equipment operating faults.
The sensor head must be fitted with the supplied weather protection, and mounted so that
the sinter is pointing downward to provide ingress protection IPX6.
The weather protection is a potential electrostatic charging hazard. The manufacturer’s
instructions should be observed.

To install the Sensepoint XCD Sensor Cartridge to the transmitter Sensor Socket:

1. Remove the weather protection (if fitted) from the sensor.


2. Use a 1.5 mm Allen key (hexagonal wrench-included) to loosen the Locking Grub Screw on
the Sensor Retainer.
3. Unscrew and remove the Sensor Retainer.
4. Remove the XCD Sensor Cartridge from its packaging and plug it into the XCD Sensor
Socket, taking care to align the sensor pins with the connector.
5. Refit the Sensor Retainer and tighten the Locking Grub Screw.
6. Refit the weather protection (as required) to the Sensepoint XCD sensor.

18
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

5. Electrical connections
WARNINGS
Sensepoint XCD is designed for installation and use in Zone 1 or 2 hazardous areas in many countries
including Europe and Class 1 Division 1 or 2 area applications in North America.
Installation must be in accordance with the recognized standards of the appropriate authority in the
country concerned.

The transmitter has a potential electrostatic charging hazard. To minimize the risk of electrostatic
discharge:
• Ground the transmitter adequately
• Install the transmitter in a manner that will prevent accidental electrostatic discharges, e.g. ensure
that objects do not rub against the housing etc.
• Clean the enclosure with a damp cloth when necessary

Access to the interior of the detector, when carrying out any work, must only be conducted by trained
personnel.

Before carrying out any work ensure local regulations and site procedures are followed.
Appropriate standards must be followed to maintain the overall certification of the detector.

Care should be taken when removing and refitting the Sensepoint XCD Sensor Cartridge to the Sensor
Socket so that damage to the connection pins can be avoided.

For installations where conduit is used, and the sensor is mounted directly to the Sensepoint XCD,
there must be a ‘Seal Fitting’ installed for each of the cable gland entries within 18 inches of the
Sensepoint XCD. The total distance of the location of these Seal Fittings is 18 inches. (e.g. If all 3 gland
entries are to be used, 3 Seal Fittings should be located, each within 6 inches of the wiring entrance).

If using an anti-seize compound, the threads should be thinly coated with an approved silicone free
compound e.g. petroleum jelly.

To reduce the risk of ignition of hazardous atmosphere, de-classify the area or disconnect the
equipment from the supply circuit before opening the detector enclosure. Keep assembly tightly closed
during operation.

Never attempt to open a junction box/enclosure or replace/refit the sensor in potentially hazardous
atmospheres while power is still applied to the transmitter.

The detector must be earthed/grounded for electrical safety and to limit the effects of radio frequency
interference. Earth/ground points are provided inside and outside the unit. Ensure that all
screens/instrument earth/clean earth wiring is earthed/grounded at a single point (either at the
controller or detector - BUT NOT BOTH) to prevent false alarms due to earth/ground loops.

Take care when handling sensors as they may contain corrosive solutions.
Do not tamper with or in any way disassemble the sensor.
Do not expose to temperatures outside the recommended ranges.
Do not expose sensors under storage conditions to organic solvents or flammable liquids.

At the end of their working life, replacement electrochemical sensors for oxygen and toxic gas must be
disposed of in an environmentally safe manner. Disposal should be according to local waste
management requirements and environmental legislation.
Alternatively, old replaceable sensors may be securely packaged and returned to Honeywell Analytics
clearly marked for environmental disposal.

Electrochemical sensors should NOT be incinerated as this action may cause the cell to emit toxic
fumes.

Refer to the local or national regulations relative to the installation at the site. For Europe see EN60079-
29-2, EN60079-14, EN45544-4 and EN61241-14.

19
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Transmitter Wiring

CAUTION
All electrical connections should be made in accordance with any relevant local or
national legislation, standards or codes of practice.

Diagram 7 XCD Source 3 Wire 4-20 mA (Source)

Diagram 8 XCD Sink 3 Wire 4-20 mA (Sink)

The Sensepoint XCD transmitter may be wired in either Current SOURCE or Current SINK configuration.
These two options are offered to allow greater flexibility in the type of control system that it can be used
with. SOURCE/SINK is selectable via the switch located on the back side of the display module;
accessible by removing the display module during installation / commissioning (see chapter 9).
Note: Terminate cable screen at detector or controller, not both.
A 250 Ohm load resistor (RL) is installed in the factory; When connected to controller, this resistor should
be removed since controller has a load resistor installed internally.

20
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Terminal connections
Note: Ensure that none of the wires in the terminal area cause an obstruction when refitting the Display
Module. Ensure that the socket on the Display Module is fully engaged in the Display Module Connector
on the Terminal Module.

Diagram 9 Terminal module

Terminal Module Networks


Terminal Number Marking Connection Description
1 24V +VE Supply
2 0V -VE Supply(0VDC) Controller Connections
3 4~20mA Current Output Signal
4 COM Drain
Modbus RTU.
5 TxD Modbus B (+)
RS485 (Optional)
6 RxD Modbus A (-)
7 RLY1/NC Normally Closed
Programmable Relay 1
8 RLY1/COM Common
(Default A1)
9 RLY1/NO Normally Open
10 RLY2/NC Normally Closed
Programmable Relay 2
11 RLY2/COM Common
(Default A2)
12 RLY2/NO Normally Open
13 RLY3/NC Normally Closed
Programmable Relay 3
14 RLY3/COM Common
(Default Fault)
15 RLY3/NO Normally Open
Table 1 Transmitter terminal connection

21
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Power
The Sensepoint XCD transmitter requires a power supply from the controller of between 12 Vdc and
32 Vdc. Ensure that a minimum supply of 12 Vdc is measured at the sensor, considering the voltage
drop due to cable resistance.
The maximum loop resistance in the field cable is calculated as follows:

R loop = (V controller – V detector min) / I detector

Example:
The controller is supplying a nominal 24 Vdc (V controller), the detector minimum allowable voltage is
12 Vdc (V detector min), therefore the maximum allowable voltage drop between the controller and detector
is 12 Vdc; this means a voltage drop of 6 V in each core (+ve core and -ve core).

Diagram 10 Power Connection


Power consumption of the detector is 5.0 W. The current required to drive the detector at the minimum
voltage is (I = P / V), 5.0 / 12 = 416.7 mA (I detector).
So, the maximum field cable loop resistance (R loop) = 12 / 0.42 = 28.8 Ohms, or 14.4 Ohms per core
(allowing for component variations, losses, etc.).
The following tables show the maximum cable distances between the controller and transmitter
assuming a voltage drop of 4V in each core and for different cable parameters. The tables are examples
only and actual cable parameters and source power supply voltage for the application should be used
to calculate the maximum cable distance allowed at the installation site.

Typical cable data Maximum Cable length (L)**


Cable size Cable resistance Meters Feet
(cross sectional area) Ω/km (Ω/mi)
2
0.5 mm (20 AWG*) 36.8 (59.2) 391 1284
2
1.0 mm (17 AWG*) 19.5 (31.4) 738 2421
2
1.5 mm (16 AWG*) 12.7 (20.4) 1134 3727
2
2.0 mm (14 AWG*) 10.1 (16.3) 1426 4665
2
2.5 mm (13 AWG*) 8.0 (12.9) 1800 5894
*nearest equivalent **example for 24 Vdc supply voltage
Table 2 Maximum cable distances

22
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Cabling
CAUTION
All unused and used cable/conduit entries must be sealed with a suitable certified
sealing plug and cable gland.

The use of industrial grade, suitably armoured field cable is recommended.

For example, screened 3 cores (plus screen 90 % coverage), suitably mechanically protected copper
cable with a suitable M20 explosion-proof gland, or 3/4’ NPT steel conduit, with 0.5 to 2.5 mm2
(20 to 13 AWG) conductors. Ensure the cable gland is installed correctly and fully tightened. All unused
cable/conduit entries must be sealed with a suitable certified sealing plug (one plug is supplied).

Cable and Earth/Ground regimes


Effective earth/ground bonding is important to ensure good EMC and RFI immunity.
The following diagrams show examples of how to earth/ground bond the cable at enclosures. The same
principles apply to conduit installations. These bonding techniques provide good RFI/EMC performance.
Earth/ground loops must be avoided to prevent the risk of false signal variation.
Controller
Clean / Instrument
Earth Screen

Cable to Transmitter

Cable outer sheath Cable inner sheath

Diagram 11 Controller Grounding

Diagram 12 System grounding

23
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

The earth screen of the field cable should be ‘tied to Earth’ or connected to ground at one point only. It
is common practice to adopt a STAR EARTH connection regime where all instrumentation screens are
connected at one common point.
The screen at the other end of the cable should be ‘parked’ or terminated into a blank terminal.

The following diagrams show how to install the wire into the ground screw of the enclosure.

Loosen the bolt Insert cable Fasten the bolt

Ground Terminal Wiring


Internal Ground connection: Utilize the shield of the wiring cable recommended in the wiring instructions.
For connection to this terminal. Twist the shield wire to avoid stray shield wires, Loosen the screw
sufficiently and wrap the wire around the screw in a ‘U’ shape. Raise the clamp and place the wire
between the clamp and ground base, lower the clamp and tighten the screw to a torque of 6.9 lb-in.

External Ground Connection: If required by local authority, utilize a 4 mm2 copper, (Stranded or Solid),
wire. Loosen the screw sufficiently to enable ‘wrapping the wire around the screw in a ‘U’ shape. Raise
the clamp and place the wire between the clamp and ground base, lower the clamp and tighten the
screw to a torque of 10.4 lb-in.

Modbus RTU Wiring


This is available on Modbus versions only.
Sensepoint XCD supports half-duplex Modbus RTU communications with up to 32 devices using
recommended shield twisted pair wire.
Refer to section12.3.3, Appendix 1 and Appendix 2 for Modbus settings and the Modbus register map.

Type Cable Spec Max Length


Modbus AWM2464 AWG26~AWG12 1,000 meters
Shielded

24
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Notes  refers to the terminal block pin numbers in the Sensepoint XCD terminal module.

Note RT is a termination resistor (120 Ohm is recommended). A termination resistor at the controller
side is not required if it has an internal termination resistor.

25
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

6. Default configuration
The Sensepoint XCD transmitter is supplied with the following default configuration.

Function Value/Setting Meaning


Sensor Type Automatic according to Sensor Sensepoint XCD recognizes the sensor cartridge
type connected according to the gas type within its own sensor family
i.e. mV, EC or O2.
≥0.0<1.0 mA Fault (refer to table 5 chapter 11.3 for details)
2.0 mA or 4.0 mA (17.4mA) Inhibit (during configuration/user settings)
Signal output For Oxygen, 2.0 mA or 17.4 mA
4.0 mA to 20.0 mA Normal gas measurement
22.0 mA Maximum over range
Value is sensor dependent Lower alarm level
Alarm Relay 1* De-energized Energizes on alarm
Contact Normally Open (NO) Closes on alarm
Non-latching
Value is sensor dependent Higher alarm level
Alarm Relay 2* De-energized Energizes on alarm
Contact Normally Open (NO) Closes on alarm
Non-latching
<1 mA Detector Fault
Fault Relay** Energized De-energizes on alarm
Contact Normally Open (NO) Closes on alarm
Non-latching
2.0 mA (default) or 4.0 mA for Signal output inhibited during menu use.
Inhibit Toxic and Flammable If any relay is set to inhibit relay, then inhibit relay will
2.0 mA (default) or 17.4 mA be activated.
For Oxygen
No inhibit timeout. The detector waits for a button
Timeout Disabled press before returning to the previous state/setting.
Timeout period can be set in ‘Configure Inhibit’ menu
in Configuration Mode.
Password 0000 (Disabled) 0000 (Password disabled). If changed then password
is activated.
Location 0000 Optional feature to identify the location or User’s
(Tag Number) ‘Tag’ number of the XCD
Temperature oC User selectable between oC or oF
ID: 1
Modbus ID, baud rates and Parity bit Baud rates: 19,200
Parity bit : EVEN
Deadband On Gas reading is zero if it is within deadband range

Table 3 Default configuration


* Alarm relays automatically reset when reading falls within alarm thresholds. If relay configured to
LATCH, then relays must be reset using the Magnetic Wand.
** Fault state (fault relay and analogue output <1 mA) is always non-latching.

26
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Gas Name Default Range Lower Alarm Lower Alarm Higher Alarm Higher Alarm
Type Type
Oxygen 25.0 % v/v 19.5 % v/v Falling 23.5 % v/v Rising
Hydrogen Sulfide 50.0 ppm 10.0 ppm Rising 20.0 ppm Rising
Carbon Monoxide 300 ppm 100 ppm Rising 200 ppm Rising
Hydrogen 1,000 ppm 200 ppm Rising 400 ppm Rising
Nitrogen Dioxide 10.0 ppm 5.0 ppm Rising 10.0 ppm Rising
Flammable IR 100 % LEL 20 % LEL Rising 40 % LEL Rising
Flammable CAT 100 % LEL 20 % LEL Rising 40 % LEL Rising
Carbon Dioxide IR 2.00 % v/v 0.40 % v/v Rising 0.80 % v/v Rising
For details of how to change the configuration of the Sensepoint XCD refer to chapter 12.

27
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

7. Normal Operation
Sensepoint XCD is supplied configured and ready for use according to the ‘Default Settings’ table
shown above. However, these setting may be tailored to a specific application requirement using
the Sensepoint XCD configuration menu system.
Access to the Sensepoint XCD transmitter’s configuration menus system is via the Magnetic Activation
Tool.

Display Screen
The Sensepoint XCD display features on LCD module with numeric and bar-graph gas concentration
data, alpha-numeric warning and status indication, a target for magnetic switch activation and the
UP/DOWN/ESC/ENTER zones for non-intrusive configuration. The LCD is also backlit with hi-intensity
multi-colour LED indicator to show NORMAL, ALARM and FAULT status.

During normal operation the instrument display shows a steady GREEN backlight.

During Low and High Gas Alarm it displays a flashing RED backlight

During Fault condition the instrument display shows a flashing YELLOW backlight.

The screen is visible through the window of the transmitter’s cover. The display shows the gas
concentration (both graphically and numerically), range, units, alarm/fault status, etc.

Note: The detector display may become sluggish in sub-zero temperatures and possibly unclear at
temperatures below -40 °C, but the detector continues its gas monitoring function. The display is not
damaged and recovers when the temperature increases.

Diagram 13 Example of an O2 Transmitter Display screen – Normal Operation

28
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

System Status
Display indications, current output and relay states for various operational conditions are shown in the
following table. For further details of error messages and troubleshooting see chapter 11.3

System Status
Relay Back
Status Display Current Output
Light
A1 A2 Fault

Fault: F-XX
Circuit or fault number with fault ✓ Yellow,
icon blinking 0-1.0 mA flashing
sensor error
System Fault N/A 0-0.15 mA
Note: In the event of processor failure the watchdog will automatically reset the system for
recovery.
W-XX Green
warning number with fault Dependent on Steady
Warning icon blinking system status

0.0 Green
Normal Gas concentration 4-20 mA Steady

st
Gas concentration. 1 Red,
alarm icon ✓
Alarm 1 4-20 mA flashing
blinking

nd
Gas concentration. 2 Red,
✓1 ✓
Alarm 2 alarm icon blinking 4-20 mA flashing

Full scale icon and Red,


✓ ✓2
Over-range reading blinking 22 mA flashing

2 or 4 mA
Inhibit icon dependent
depending on
on Menu command. If Green
configuration
any relay is set to inhibit Steady
Note:
relay, then inhibit relay
Inhibit 2 or 17.4 mA
will be activated.
for Oxygen
version
Table 4 System status
Notes:
1For Oxygen, A1 relay will not be activated because AL1 is configured to activate above
23.5 % v/v (in Rising Alarm configuration).
2For Oxygen, A2 relay will not be activated because AL2 is configured to activate below

19.5 % v/v (in Falling Alarm configuration).

29
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Magnetic Wand Activation

The magnetic wand is used as a tool to allow the user to interact with
Sensepoint XCD transmitter. Interaction with Sensepoint XCD is
achieved by positioning the Magnetic Wand at one of three different
positions on the front glass window of Sensepoint XCD transmitter.
Activation of the switches is verified by observing the Magnetic Wand
Activation Icon on the LCD display

Hold the Magnetic Wand in position for up to 2 seconds =


Hold the Magnetic Wand in position for 3 seconds or more =

Mode Structure
Sensepoint XCD has three operating modes.

1. Monitoring mode is the normal operating status while Sensepoint XCD measures and displays
gas concentration. The fault/warning status is periodically checked, relay contacts are activated
according to the configuration.
2. Configuration mode this mode allows parameters relating to the configuration of the
Sensepoint XCD functions to be changed according to specific needs. This mode can be
protected by a password mechanism to prevent unauthorized changes being made.
3. Review mode allows the user to view the current configuration settings.

Start - Up

Configuration Monitoring Review


Mode Mode Mode

Diagram 14 Mode Structure

Further details of the information available and configuration options for the Sensepoint
XCD can be found in chapter 12 of this manual.

30
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

8. First time switch on (Commissioning)


WARNING
The following procedure requires the Transmitter Cover to be removed while carrying out
supply voltage checks. Therefore, the appropriate permits to work should be sought in
preparation.

Prior to carrying out any HOT WORK ensure local and site procedures are followed.
Ensure that the associated control panel output actuation is inhibited so as to prevent false
alarms.

CAUTION
The following procedure should be followed carefully and only performed by suitably
trained personnel.

Note: Calibration is mandatory before the detector can be used for gas monitoring. Refer to chapter 9.1
Calibration for the proper procedure.
1. Remove the transmitter housing cover and detach the display unit by lifting the semi- circular
handle and pulling the assembly directly away from the termination module (without twisting it)
2. Configure the detector's analogue output signal configuration for Current SINK or Current
SOURCE operation using the selector switch located on the back of the display module. The
default setting is Current SOURCE.
3. Check that all electrical connections are terminated correctly as per chapter 5.
4. Switch On the external power supply to the transmitter at the safe area gas detection controller
(or PLC).
5. Using a Digital Multi Meter (DMM), check the Supply Voltage at the terminals 1 (24 V) and
2 (0 V), this should be a minimum supply voltage of 12 Vdc or 16 Vdc depending on the
transmitter version (Maximum supply voltage is 32 Vdc)
6. Switch Off the external power to the detector.
7. Refit the Display Module and Cover.

Note: Ensure that none of the wires in the terminal area cause an obstruction when refitting the Display
Module. Ensure that the socket on the Display Module is fully engaged in the Display Module Connector
on the Terminal Module.

31
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

1. Switch On external power to the detector.


2. All the display icons/text/numbers are displayed for 3 seconds.

3. A start up sequence will then be displayed, like the one shown in Diagram 15.

Note: For a full description of each screen shown in Diagram 16 refer to chapter 12.4 ‘Review Mode’ of
this manual.

32
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Diagram 15 Normal Start up procedure (For the CO sensor version)

1. The warm up countdown of 60 seconds (depending on the gas type) is then displayed.
2. Normal Monitoring Mode is then resumed.

33
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

9. Response Check and Calibration


It is recommended to periodically carry out a gas response check on the Sensepoint XCD to ensure
correct operation. This may be done in two ways;

A simple Response Check often referred to as a ‘BUMP TEST’ is a test using calibration gas applied to
the sensor via the nozzle of the Weather Protection or using the Sensepoint XCD Gassing Cap.
If a BUMP TEST is done via the Weather Protection nozzle it may be necessary in windy conditions to
increase the flow rate of the test gas by a further 1 l/min, OR, to shelter the weather protection from the
wind.
A full gas calibration of the sensor as described in the following section, using ONLY the Sensepoint
XCD Gassing Cap (Part No.: S3KCAL).

Zeroing and span calibration

WARNING
As some calibration gases may be hazardous, ensure that outlets from gassing accessories
exhaust safely.

CAUTION
Before initial calibration allow the detector to stabilize for 30 minutes after applying power.
When in zeroing and span calibration mode the current output from the detector is
inhibited (default 2 mA) to avoid false alarms. For Flammable gas calibration use a
calibration gas concentration of between 25 % LEL and 75 % LEL to ensure that the
required accuracy can be attained. For Hydrogen Sulfide type sensors refer to chapter 9.2
before conducting zero and span calibration. For toxic sensors use a calibration gas of
approximately 50 % FSD.

To calibrate the detector, use an appropriate span gas cylinder, constant flow regulator AND the
Sensepoint XCD Gassing Cap (see chapter 3.2). The flow rates used for calibration gas are as follows:

Gas Type Flow rate (l/min)


Air or N2 for Zero 0.5 to 1.0
Flammable CAT 1 to 1.5
O2 0.5 to 1.0
H2S 0.5 to 1.0
CO 0.5 to 1.0
H2 0.5 to 1.0
NO2 0.5 to 1.0
Flammable IR 0.4 to 0.6
CO2 IR 0.4 to 0.6

34
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

A compressed air cylinder (20.9 % v/v oxygen) should be used to perform the zero calibration if the
area where the detector is located contains any residual amount of the target gas. If no residual gas
is present, then the background air can be used to perform the zero calibration. Contact your
Honeywell Analytics representative for details of suitable calibration kits.

To calibrate the detector, follow the procedure below.

Note: The Oxygen sensor does not require a zeroing procedure. Background air (20.9 % v/v oxygen)
can be used to span the oxygen sensor in place of a compressed air cylinder (20.9 % v/v oxygen). For
oxygen sensors only do parts 1-4, 12, 13 (if compressed air cylinder is used), 14-17 and 22 of the
procedure below.

9.1.1. Zero Calibration

WARNING
When calibrating the Flammable IR or CO2 IR sensors, it is essential that the zero
calibration is always followed by a span calibration. The zero calibration must never be
done alone.

Note: When the Flammable-CAT sensor is replaced, it is necessary to re-initialize the baseline. Select
‘InIt bASE’ from the menu system.

1. If the ambient air is NOT considered reliable to use to set the ZERO, then remove the weather
protection and fit the Gassing Cap accessory (see chapter 3.2) onto the sensor and apply a
clean source of zero gas or compressed air.
2. To access the calibration menu, hold the end of the magnet over the switch located at the top
centre of the detector display (✓) for at least 3 seconds and then remove.
3. The display will indicate the first configuration mode menu ‘SEt CAL’.

4. Place the magnet over the ‘✓’ switch again and move to enter the Calibration menu.
5. The display will show the current gas reading, and the ‘ ’ icon flashes.

6. When the zero gas reading is stable use ‘✓’ to confirm zero calibration.
7. If successful the display shows ‘ZEro PASS’ (if not successful, the display shows ‘ZEro FAIL’ and
returns to configuration mode).

35
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

8. If using zero-air, turn it off. Zeroing is complete and saved.


9. The display shows ‘SPAn’ with ‘YES’ flashing.

10. If span calibration is required use ‘✓’ proceed to the next step. If span calibration is not required,
use ‘’ to select ‘No’ and ‘✓’ to return to configuration mode.

WARNING
When calibrating the Flammable IR or CO2 IR sensors, it is essential that the span
calibration is done after a zero calibration.

9.1.2. Span Calibration


1. The display shows the current calibration span gas concentration while flashing the ‘ ’ icon.
Use ‘’ to change the calibration span gas concentration, and ‘✓’ when required span
calibration level is set.

2. The display will show the current gas reading, and the ‘ ’ icon flashes.

3. Connect the regulator to the span gas cylinder.

4. Apply the span gas to the sensor using the Sensepoint XCD Gassing Cap (see chapter 3.2 for
description). The live gas reading is displayed. When the reading is stable, use ‘✓’ to confirm
span calibration.

5. If the sensor has been replaced the following display may be shown.

36
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

6. Use ‘’ to select ‘YES’ if the sensor has been replaced or ‘No’ if it has not been replaced.

7. If the span calibration is successful, the instrument will briefly display ‘SPAn PASS’ (if fails
‘SPAN FAIL’ displayed and returns to configuration mode).

Note: the calibration due warning counter is reset after a successful calibration. See chapter 12.2 for
further details of setting a calibration due warning.

1. The display alternates between ‘Purg gAS’ and the gas reading to indicate that the unit is
expecting the span gas to be removed from the sensor.

2. Promptly switch off the calibration span gas and remove the Sensepoint XCD Gassing Cap
from the sensor to allow the gas to disperse.

3. When the reading falls below 50% of the calibration gas level the display indicates a countdown
(up to 180 seconds dependant on gas type).

4. When the countdown is finished, the calibration procedure is complete.

5. The instrument returns to the ‘Set CAL’ menu. Activate the ‘’ or ‘’ switch to select another
menu or select ‘QuIT’ to return to normal monitoring mode.

37
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Note: Remember to always replace the Weather Protection and other accessories.

38
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Zeroing and span calibration of Hydrogen Sulfide


sensors
Hydrogen Sulfide sensors can be affected by extreme humidity changes. A sudden increase in ambient
humidity can result in a short-term positive drift in the instrument’s reading. A sudden decrease in
ambient humidity can result in a short-term negative drift in the instrument’s reading. These are most
likely to be noticed during calibration with dry or cylinder gas.

When calibrating Hydrogen Sulfide cartridges, the following should be considered while following the
procedure in 10.1:

1. To zero the sensor, use a compressed air cylinder of 20.9 % v/v oxygen (not Nitrogen). Do not
use background air.
Apply the gas to the sensor for three minutes before using ‘✓’ to confirm the zero calibration.

2. If a span calibration is to be performed, the span calibration gas should be applied to the sensor
immediately after the zeroing procedure. Do not allow the sensor to return to ambient air
conditions between steps 2 and 3.

3. Apply the span gas for two minutes before using ‘✓’ to confirm the span calibration.

39
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

10. General Maintenance


WARNINGS
Access to the interior of the transmitter, when carrying out any work, must only be conducted by trained
personnel.
The transmitter has a potential electrostatic charging hazard. To minimize the risk of electrostatic
discharge:
• Ground the transmitter adequately
• Install the transmitter in a manner that will prevent accidental electrostatic discharges, e.g. ensure
that objects do not rub against the housing etc.
• Clean the enclosure with a damp cloth when necessary

Care should be taken when removing and refitting the Sensepoint XCD plug-in Sensor.
Cartridge to the Sensor Socket so that damage to the connection pins can be avoided.

Before carrying out any work ensure local regulations and site procedures are followed. Appropriate
standards must be followed to maintain the overall certification of the sensor and transmitter.
To reduce the risk of ignition of hazardous atmosphere, de-classify the area or disconnect the equipment
from the supply circuit before opening the transmitter enclosure. Keep assembly tightly closed during
operation.
Never attempt to open a junction box/enclosure or replace/refit the sensor in potentially
hazardous atmospheres.
Take care when handling sensors as they may contain corrosive solutions.
Do not tamper with or in any way disassemble the sensor.
Do not expose to temperatures outside the recommended ranges.
Do not expose sensors under storage conditions to organic solvents or flammable liquids.
At the end of their working life, replacement electrochemical sensors for oxygen and toxic gas must be
disposed of in an environmentally safe manner. Disposal should be according to local waste management
requirements and environmental legislation.
Alternatively, old replaceable sensors may be securely packaged and returned to Honeywell Analytics clearly
marked for environmental disposal.

Electrochemical sensors should NOT be incinerated as this action may cause the cell to emit toxic fumes.

Honeywell Analytics recommends that gas detectors are tested and re-calibrated on a six-monthly basis,
or according to site practice. For remote Flammable or Toxic sensors used with the XCD Transmitter,
refer to the individual sensor manuals for specific recommended calibration periods. If a toxic sensor is
exposed to a gas concentration significantly above the measuring range, it shall be calibrated as soon
as possible afterwards.

40
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Operational Life
The pellistors fitted in the Flammable Catalytic sensors are poison resistant to maximize the
operational life of the sensor, however they can suffer from a loss of sensitivity when in the presence
of poisons or inhibitors, e.g. silicones, sulfides, chlorine, lead or halogenated hydrocarbons. A
typical operating life, subject to the presence of poisons/inhibitors is 36 months.

The NDIR (infrared) flammable gas sensor is not affected by the above-mentioned poisons and
therefore, has a longer life span. A typical operating life is 5 years.

The typical life of a toxic gas sensor is dependent on the application, frequency and amount of gas
exposure. Under normal conditions (3 monthly visual inspection and 6 monthly test/re- calibration), the
Sensepoint XCD Oxygen and other toxic sensors have an expected life equal to or greater than 24
months.
Refer to chapter 11.1 for sensor replacement procedures.

CAUTION
Oxygen deficient atmospheres (less than 6 % v/v) may result in inaccuracy of
reading and performance.

41
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

11. Servicing
WARNINGS
Take care when handling sensors as they may contain corrosive solutions. Do not tamper or
in any way dis-assemble the sensor. Do not expose to temperatures outside the
recommended range. Do not expose sensor to organic solvents or flammable liquids.

Care should be taken when removing and refitting the Sensepoint XCD plug-in Sensor
Cartridge to the Sensor Socket so that damage to the connection pins can be avoided.

At the end of their working life, replacement electrochemical sensors for oxygen and toxic gas
must be disposed of in an environmentally safe manner. Disposal should be according to
local waste management requirements and environmental legislation.
Alternatively, old replaceable sensors may be securely packaged and returned to Honeywell
Analytics clearly marked for environmental disposal.

Electrochemical sensors should NOT be incinerated as this action may cause the cell to emit
toxic fumes.

CAUTION
The following procedure should be followed carefully and only performed by suitably
trained personnel.
A fault condition will be signaled by the detector if the sensor is removed with the unit
under power.

42
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Sensor replacement
The Flammable Catalytic and Toxic ECC sensor cartridges that are used with the Sensepoint XCD
Sensor Socket have no serviceable parts. When they have reached the end of their operational life,
simply replace the sensor cartridge.

Diagram 16 Sensor Replacement

To replace the Sensepoint XCD plug-in sensor cartridge use the following procedure:

1. Important: Remove the Power from the Sensepoint XCD Transmitter


2. Remove the Weather Protection or other accessories from the sensor socket thread
3. Loosen the Locking Grub Screw and unscrew the Sensor Retainer
4. Carefully pull the old Sensor from the sensor socket without twisting
5. Fit the new Sensor in its place
6. Calibrate sensor

WARNING
Ensure that the same Gas Type and Range of Sensor is fitted in place of the old Sensor.
Care should be taken when removing and refitting the Sensepoint XCD plug-in Sensor
Cartridge to the Sensor Socket so that damage to the connection pins can be avoided.

The sensor head must be fitted with the supplied weather protection, and mounted so that
the sinter is pointing downward to provide ingress protection IPX6.

The weather protection is a potential electrostatic charging hazard. The manufacturer’s


instructions should be observed.

43
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Replacing Modules within the Transmitter


Two replaceable module assemblies are located within the transmitter housing. The Display Module and
the Terminal Module.
The Display Module is simply removed by unplugging it from the Terminal Module (this procedure is
done during normal installation).

To replace the Terminal Module, use the following procedure:

1. Unscrew and remove the Transmitter Cover

2. Lift the handle and un-plug and remove the Display Module.

3. Unplug the connection terminals and lift them clear of


the Terminal Module.
4. Unplug the connector for the sensor.

5. Loosen and remove the three ‘cross-headed’ screws


that secure the Terminal Module to the Transmitter housing.
6. Carefully lift the Terminal Module from the transmitter housing.

7. Fit the new Terminal Module using the above procedure


in reverse order.

44
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Faults and Warnings


The table below provides details of possible error.
Message Description Action
The unit has not been calibrated for the
configured calibration interval Calibration is
W-01 Calibration needed necessary due to change
of sensor/gas type
Transmitter Temperature limits
W-02 Use ‘✓’ to clear when within limits
exceeded
Re-configure alarm settings such that upper
Alarm setting needs to be
W-03 alarm should not exceed user
configured
configured scale

W-04* Over-range warning Use ‘✓’ to clear when within limits

The sensor is switched off to Make sure that there is no flammable


W-05* prevent it from being gas in the air and use ‘✓’ to clear when within
deteriorated limits
Cycle power to detector. Replace detector
F-01 Internal I2C failure

For Toxic, replace sensor


F-02 Cell failure For Flammable/IR, cycle power to detector.
Replace sensor

F-03 Significant zero drift Re-zero/calibrate

F-04 Unexpected sensor fitted Replace sensor

Reset transmitter. If fault still appear, replace


F-05 EEPROM is corrupted
transmitter
Reset transmitter. If fault still appear, replace
F-06 Low supply voltage
transmitter
Reset transmitter. If fault still appear, replace
F-07 SRS processor failure
transmitter
Reset transmitter. If fault still appear, replace
F-08 RAM read/write fault
transmitter
Reset transmitter. If fault still appear, replace
F-09 Info. memory corrupted
transmitter
Reset transmitter. If fault still appear, replace
F-10 Code Memory corrupted
transmitter
Check load resistor or sink/source mode
F-11 DAC output failure
switch was configured properly
Reset transmitter. If fault still appear, replace
F-12 Heater failure
transmitter

F-13 Supplied voltage failure Check supply voltage. Replace detector

Table 5 Fault and Warning List


Note: W-04 and W-05 are only for flammable catalytic bead sensors. For other gases, gas reading will
blink on the LCD instead of the over-range warning.

45
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

12. Menu and Advanced Configuration


Abort Function
In Review Mode or Configuration Mode the user can escape one step back from the current position
using the Abort Function. To do this the user must activate the Enter switch for more than 3 seconds
with the Magnetic Wand. Switching between each pair of modes or between menus and sub menus are
shown in the following table.

From To Example

Review Mode Monitoring Mode Activate Enter switch for more than 3 seconds while
in Review Mode

Activate Enter switch for more than 3 seconds while


Configuration Mode Monitoring Mode navigating menus in the Configuration Mode

Configuration Mode Configuration Activate Enter switch for more than 3 seconds while
sub menu Mode main menu in a sub menu

Table 6 Transmitter menu switching

Configuration Mode
The table below shows the functions available via the configuration menu that can be displayed on the
transmitter and accessed using the Magnetic Wand.

The instrument will show the main Menu when the ‘Enter’ switch is activated with the Magnetic Wand
and held for at least 3 seconds.

The Menu is password protected to prevent any unauthorized changes. The password is initially
disabled, and the default password is ‘0000’. If the default password is changed to other than ‘0000’,
then the password is enabled automatically and requested when entering Configuration Mode.

With the Menu showing, the following functions can be performed: calibration, bump test, sensor
selection and configuration of parameters such as measuring range, calibration gas level, calibration
interval, inhibit current, inhibit timeout, alarm setting, relay setting, password change, location setting,
temperature unit reading, force analogue output and alarm function checks.

While in Configuration mode, the output current of the transmitter is inhibited to prevent false alarms.
Names, displays and descriptions for each menu item in Configuration Mode are shown in the following
table.

46
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Menu Display Description

Set Calibration Execute zero/span calibration Set


calibration gas level
After zero, the option exists to proceed with span
calibration, or return to the Menu
Initialize Baseline Perform a baseline initialization (flammable-CAT
Note 3 versions only)

Select Sensor Select the type of sensor from the sensor list. This
Note 3 menu is only available for flammable / IR sensor

Select Gas Select the type of gas from the list. This menu is
Note 3 only available for flammable / IR sensor.

Set Range Set measuring range

Configure Inhibit Select inhibit current


Note 1 Set timeout option (5 minutes increments)

Set Password
Enable/disable
password Set password
Default – no password (Select ‘0000’)

Set Calibration
Interval Set calibration interval, 30 to 365 days
User configurable option to display warning

Bump Test Execute a ‘bump’ test to check gas response of the


sensor.

Force Current Force analogue output to test functionality of GD control


system during system commissioning

Set Alarms Set alarm 1, alarm 2 levels, functionality and


Note 2 operation (none/falling/rising)

Set Relays Set relay 1,2,3 type (alarm 1, alarm 2, fault and inhibit)
Note 2 and action (energized/de-energized)

47
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Relay Operation Configure relay on delay time, relay off delay time
Note 2 and latch/non-latch

Set Location Set location (or TAG number)

Set Temperature Change temperature display unit.


Unit °C (Celsius) or °F (Fahrenheit)

Check Alarm Simulate alarm situation to check the alarm system


functions without gas present at the sensor

Set deadband Enable or disable the display deadband

Quit Return to Monitoring mode

Table 7 Transmitter menu descriptions

Note 1: To comply with IEC EN 60079-29-1 and EN 50104, if the Inhibit current is set to 4 mA, the
timeout option must be set. The maximum value for the timeout is 15 minutes.

Note 2: To comply with IEC EN 60079-29-1 and EN50104, the alarms must be configured as latching
by setting the corresponding relay to latching, even if the relay is not being used. If relays are used the
action must be configured as ‘energized’ for fail safe operation.

Note 3: ‘Init. Baseline’, ‘Select Sensor’ and ‘Select Gas’ are available for flammable/IR sensors only.

48
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Menu Switch
No (> 3 Seconds)
Quit/ESC command
Auto quit after no activity of timeout
Abort
Release mA O/P
Inhibit mA O/P Yes

Set Calibration
Interval

Bump Test
Init. Baseline *

Set Alarms
Select Sensor *
Set Relays
Select Gas *
Configuration Mode
(Inhibited) Relay Operation
Set Range
Set Location
Configure Inhibit
Set Temperature
Set Password Unit

Check Alarm
Set Calibration functions
Interval
Set Deadband
Set Password

Diagram 17 Configuration Mode


Note: ‘Init. Baseline’, ’Select Sensor’ and ‘Select Gas’ menus are available for flammable/IR sensors only.

49
12.2.1. Configuration mode operation table
Configuration mode allows the user to perform calibration and configure parameters such as full-scale range, calibration gas level, calibration interval,

Sensepoint XCD Technical Manual


inhibit current & timeout, alarm settings, relay settings, set a password, etc. To activate Configuration mode, hold the magnet over the ENTER switch
for at least 3 seconds and then remove. Configuration mode can be password protected to prevent unauthorized personnel from changing parameters.
Initially the password is set to ‘0000’ meaning it is disabled. While in Configuration mode, the output current of the detector is inhibited to prevent false
alarms.
Use the table below to help navigate the menus and make configuration changes. The menus are shown in the left-hand column. Use
 to select the required menu and ‘✓’ to enter. Follow the information and instructions in the table from left to right from the required menu.
OK OK OK OK
‘SPAN’ DISPLAYED AND ‘YES’ GAS NAME, CURRENT CONCENTRATION AND
GAS NAME, ZERO CONCENTRATION AND FLASHING TO ASK IF YOU NOW ‘GAS’ TARGET CONCENTRATION
WANT TO PERFORM SPAN FLASHING ‘ ’ ICON DISPLAYED. APPLY SPAN GAS
FLASHING ‘ ’ ICON DISPLAYED. APPLY ZERO CALIBRATION. USE ‘ ’ TO PROCEED FLASHING AND ‘ ’ ICON DISPLAYED. AND USE ‘ ’ WHEN READING STABLE. IF OK ‘PASS’
SEt GAS AND USE ‘ ’ WHEN READING IS
OR USE TO SELECT ‘No’ AND USE TO CHANGE GAS & ‘PurG’ DISPLAYED (IF FAIL ‘SPAN FAIL’ DISPLAYED
CAL1 STABLE. ‘ZEro PASS’ DISPLAYED IF OK, ‘ZEro
RETURN TO MENU MODE. CONCENTRATION AND ‘ ’ TO START AND RETURNS TO MENU). REMOVE SPAN GAS.
FAIL’ IF NOT SPAN CALIBRATION. WHEN READING <50% OF SPAN POINT,
COUNTDOWN BEGINS & UNIT RETURNS TO MENU
MODE.
InIt 2 ‘InIt bASE” DISPLAYED AND RETURN TO
bASE MENU MODE WHEN COMPLETED

‘SEnS’ DISPLAYED WITH SENSOR TYPE IF SENSOR TYPE IS CHANGED, ‘CAL


DISPLAYED. USE TO SELECT YES’ DISPLAYED TO ASK
SEL2 IF YOU NOW WANT TO PERFORM
DIFFERENT SESNOR.
SENS CALIBRATION. USE ‘ ’ TO PROCEED
OR USE TO SELECT ‘No’ AND
RETURN TO MENU MODE.
‘9AS’ DISPLAYED WITH GAS TYPE IF GAS TYPE IS CHANGED,
DISPLAYED. USE TO SELECT ‘CAL YES’ DISPLAYED TO ASK IF YOU
SEL DIFFERENT GAS. NOW WANT TO PERFORM
9AS2 CALIBRATION. USE ‘ ’ TO
PROCEED OR USE TO SELECT
‘No’ AND RETURN TO MENU MODE.
IF RANGE IS CHANGED, ‘CAL’ IF RANGE IS CHANGED, ‘ALrm’
BAR GRAPH INDICATING CURRENT RANGE, DISPLAYED AND ‘YES’ FLASHING TO DISPLAYED AND ‘YES’ FLASHING TO
SEt ‘rAn9’ DISPLAYED & CURRENT RANGE ASK IF YOU NOW WANT TO ASK IF YOU NOW WANT TO MODIFY
UNIT RETURNS TO MENU MODE
rAn9 FLASHES. USE TO SELECT DIFFERENT PERFORM CALIBRATION. USE ‘ ’ TO ALARM SETTINGS. USE ‘ ’ TO
RANGE PROCEED OR USE TO SELECT PROCEED OR USE TO SELECT
‘No’. ‘No’ AND RETURN TO MENU MODE.

‘Inhb’ DISPLAYED WITH ‘ ’ ICON ‘tImE’ DISPLAYED WITH ‘ ’ ICON.


FLASHING. CURRENT INHIBIT mA VALUE FLASHING CURRENT INHIBIT
ConF FLASHES. USE TO SELECT NEW VALUE TIMEOUT PERIOD (MINUTES) UNIT RETURNS TO MENU MODE
Inhb4 (2 OR 4mA TOXICS, OR 2 OR 17.4mA FLASHES. USE TO SET NEW
OXYGEN VERSION). TIMEOUT. (IF SET TO 0 OUTPUT IS

SPXCDHMANEN Issue 15
PERMANENTLY INHIBITED)
‘PASS’ DISPLAYED WITH FIRST DIGIT PLACE
ICON OF THE PASSCODE FLASHING.
SEt USE TO SELECT 1ST DIGIT OF CURRENT UNIT RETURNS TO MENU MODE
PASS PASSWORD. USE TO MOVE TO NEXT
DIGIT AND SET REST OF PASSCODE.

50
1
Refer to chapter 9.1 for detailed zero and span calibration procedures. A detector fitted with an oxygen sensor will skip the zeroing procedure. Re-calibrate the detector if left un-powered
for periods more than 24 hours.

Sensepoint XCD Technical Manual


UNIT TRANSMITS THE CURRENT
Forc ‘Forc’ DISPLAYED WITH ‘ ’ ICON. DEFAULT IF YOU WANT TO EXIT FROM THIS
Curr FORCE CURRENT ‘4.00’ FLASHES. USE MENU, USE ABORT FUNCTION
TO CHANGE TO REQUIRED mA LEVEL.
‘duE’ DISPLAYED AND ‘No’, ‘LCd’ OR
CAL ‘Int’ DISPLAYED WITH CURRENT
‘ALL’ FLASHING. USE TO
CALIBRATION INTERVAL FLASHING. USE UNIT RETURNS TO MENU MODE
Int33 TO CHANGE INTERVAL. SELECT REQUIRED CAL DUE
WARNING OUTPUT.
UNIT RETURNS TO MENU MODE
PEAK READING DISPLAYED WITH OUTPUT WARNING: DO NOT RETURN TO
bumP CURRENT GAS CONCENTRATION
NORMAL MODE UNTIL CURRENT GAS
INHIBITED ‘ ’ ICON AND PEAK STRING DISPLAYED WITH OUTPUT INHIBITED CONCENTRATION HAS FALLEN
tESt FLASHING. APPLY BUMP TEST GAS AND ‘ ’ ICON FLASHING. BELOW A1 LIMIT OR THE DETECTOR
CHECK PEAK READING ON DISPLAY. WILL GIVE AN ALARM
‘AL2’, ICON DISPLAYED AND
‘AL1’, ICON DISPLAYED AND CURRENT
SEt ‘AL1’ DISPLAYED WITH ‘NonE’, ‘rISE’ CURRENT ALARM LEVEL 2 ‘AL2’ DISPLAYED WITH ‘NonE’, ‘rISE’ OR ‘FALL’
ALARM LEVEL 1 CONCENTRATION
OR ‘FALL’ FLASHING. USE TO CONCENTRATION FLASHES. USE FLASHING. USE TO SELECT REQUIRED ALARM
ALrm FLASHES. USE TO CHANGE TO
SELECT REQUIRED ALARM ACTION. TO CHANGE TO REQUIRED ACTION AND USE ‘ ’ TO RETURN TO MENU MODE.
REQUIRED CONCENTRATION LEVEL. CONCENTRATION LEVEL.

‘Rl2’ DISPLAYED AND ‘AL1’, ‘AL2’, ‘Inht’


Set ‘rL1’ DISPLAYED AND ‘AL1’, ‘AL2’, ‘Inht’ or ‘rL1’ DISPLAYED AND ‘dEEn’ or ‘Enr9’
or ‘FLt’ FLASHES. USE TO ‘rL2’ DISPLAYED AND ‘dEEn’ or ‘Enr9’ FLASHES. USE
‘FLt’ FLASHES. USE TO CHANGE TO FLASHES. USE TO CHANGE TO
rLY5 REQUIRED RELAY TARGET. REQUIRED RELAY ACTION.
CHANGE TO REQUIRED RELAY TO CHANGE TO REQUIRED RELAY
TARGET. ACTION.
‘rL3’ DISPLAYED AND ‘AL1’, ‘AL2’, ‘Inht’ or ‘rL3’ DISPLAYED AND ‘dEEn’ or ‘Enr9’
‘FLt’ FLASHES. USE TO CHANGE TO FLASHES. USE TO CHANGE TO UNIT RETURNS TO MENU MODE
REQUIRED RELAY TARGET. REQUIRED RELAY ACTION.
‘rLY’, ‘OFF’ DISPLAYED AND
‘rLY’, ‘ON’ DISPLAYED AND CURRENT ‘Ltch’ DISPLAYED AND ‘YES’ or ‘No’
rlY CURRENT RELAY-OFF TIME
UNIT RETURNS TO MENU MODE
RELAY-ON TIME FLASHES. USE TO FLASHES. USE TO CHANGE TO
OPr 5 CHANGE TO REQUIRED RELAY-ON DELAY.
FLASHES. USE TO CHANGE TO
REQUIRED LATCH OPTION.
REQUIRED RELAY-OFF DELAY.
‘Loc’ DISPLAYED WITH FIRST 4 CHARACTERS
OF THE LOCATION STRING. USE ‘Loc’ DISPLAYED NEW LOCATION
TO CHANGE THE 1ST STRING. THE STRING MOVES
Set CHARACTER OF CURRENT LOCATION RIGHT-TO-LEFT TO SHOW WHOLE
Loc STRING. USE CHARACTERS TWICE. THEN UNIT
TO MOVE TO NEXT CHARACTER AND SET AUTOMATICALLY RETURNS TO
REST OF STRING. MAXIMUM 12 MENU MODE.
CHARACTERS CAN BE SET.

‘tEmP’ DISPLAYED WITH ‘OC’ OR ‘OF’


tEmP UNIT RETURNS TO MENU MODE
FLASHING. USE TO CHANGE TO
UnIt REQUIRED TEMPERATURE UNIT.

SPXCDHMANEN Issue 15
tESt ‘Forc’ DISPLAYED and ’AL1’ FLASHING TO GAS NAME, CURRENT GAS
SELECT TEST-REQURED ALARM. USE ‘ ’ CONCENTRATION DISPLAYED AND UNIT RETURNS TO MENU MODE
ALrm TO FORCE ALARM1. ‘ ’ ICON AND AL ICON FLASHE.

Set ‘dEAd DISPLAYED ‘On/OFF’ SETTING


FLASHING. USE TO CHANGE TO
dEAd REQUIRED DEADBAND SETTING
QUITS MENU MODE AND RETURNS TO
9uIt MONITORING MODE

OK OK OK OK
2
This menu is only available and visible when the unit is fitted with flammable/IR sensor.
3
The calibration due warning counter is automatically reset after a successful calibration.
4
To comply with IEC EN 60079-29-1 and EN 50104, if the Inhibit current is set to 4 mA, the timeout option must be set. The maximum value for the timeout is 15 minutes.
5
To comply with IEC EN 60079-29-1 and EN50104, the alarms must be configured as latching by setting the corresponding relay to latching, even if the relay is not being used. If relays
are used the action must be configured as ‘energized’ for fail safe operation.

51
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Sensor / Gas Selection


Note: This Configuration option is not available for Sensepoint XCD units with EC sensors.

12.3.1. Sensor Selection


‘Select Sensor’ sets the identity of the type of mV sensor attached to the Sensepoint XCD when it
does not detect the sensor type automatically. When the sensor type is detected by Sensepoint XCD
automatically, the current sensor type can be confirmed in this menu.

The available mV sensors are as follows:

Ir-1 NDIR Infrared CO2 0-2 % v/v


Ir-3 NDIR Infrared Methane 0-100 % LEL
Ir-4 NDIR Infrared Propane 0-100 % LEL
Cb-1 Catalytic 0-100 % LEL

12.3.2. Gas Selection

Use ‘SEL gAS’ to set the target gas for sensors capable of detecting multiple gases. The available gases
are as follows:

Sensor type Gas type Gas Name displayed

Ir-1 CO2 CO2


Ir-3 mEt mEt
Ir-4 Propane PrO
Cb-1 Str1 to Str8 FLM

Gas selection is dependent on the type of sensor attached to the Sensepoint XCD. If Ir-1/Ir-3/Ir-4
sensor is attached, then gas type is detected by the Sensepoint XCD automatically (for example
CO2/mEt/ProP). When a type Cb-1 sensor is attached to the Sensepoint XCD, a user can select the gas
from Str1 (1*) to Str8 (8*). For more information on star rating, refer to chapter 18.2.

Note: For standard calibration (calibration gas = target gas) the following parameters are to be used:
Methane Star Rating 6* Gas Str 6 100 % LEL = 4.4 % v/v
Propane Star Rating 5* Gas Str 5 100 % LEL = 1.7 % v/v

The current configuration of the XCD is displayed and by using the ‘✓’ switch to enter ‘SEL gAS’ menu.
To select a flammable gas, use ‘’ to move through the list, then use ‘✓’ to make the selection or
abort function to discard the selection and return to menu mode.
If type of gas is changed, calibration prompt will appear to ask if you want to perform calibration.

52
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Diagram 18 Gas Selection

12.3.3. Set Modbus


Set id->Set Modbus slave ID->Set Baud rate->Set Parity
1. Slave ID shall be set 1~247
2. Baud rate setting 9600 or 19200
3. Parity setting (No, Even, Odd)
From the Configuration Mode screen, select ‘✓’. To set the Modbus Slave ID, use the up-down
‘▲▼’switches to move to the desired position and use ‘✓’ to select it. Again, using the ‘▲▼’switches,
increment or decrement the value until the desired value appears, selects the value and moves to the
next setting.

53
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

The communications baud rate and Parity Setting can also be set from this screen by using the ‘▲▼’
switches to navigate to the baud rate display then selecting ‘✓’. Using the ‘▲▼’switches, highlight the
proper baud rate or parity setting and select ‘✓’. Default is Slave ID 1, 19200bps and even parity.

Note: The ‘Set ID’ menu is available only for Sensepoint XCD equipped with Modbus option.

54
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Review Mode
The instrument will enter Review mode when the ‘Enter’ switch is activated with the Magnetic Wand and
held for around one second.

Names, displays and descriptions for each review item in Review Mode are shown in the following table.

Item name Display Description


Software version S/W version of transmitter

SRS version S/W version of SRS (watch dog)

EEP version EEPROM parameter version

Gas Gas type

Measuring range A user selected measuring range

Calibration level Calibration gas level

Calibration due Estimated time to next calibration

Alarm 1

Alarm settings for Alarm 1


Alarm 2

Alarm settings for Alarm 2


Location Location in which the transmitter is installed

55
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Item name Display Description


Power Power voltage*

Temperature Internal Transmitter temperature*


Maximum

Peak conc. Maximum concentration detected up to now

Test Result There is no fault detected.

Table 8 Transmitter menu descriptions

Note *: Power voltage and internal transmitter temperature may be different from actual value due to
measuring accuracy and internal heating components.

56
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Menu switch
(1 ~ 3 seconds)
Review Monitoring
Mode Mode
Abort

Auto end to cycle

Test Result

SRS version Peak Reading

EERPOM version Temperature

Gas type Supplied input voltage

Measuring range Location

Calibration Gas Level Alarm settings

Calibration Due

2 seconds pause for every steps


Diagram 19 Review Mode

57
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

13. General specification


Sensepoint XCD Transmitter.
Use 3-wire, 4-20 mA, gas detector transmitter for use with directly installed flammable and toxic gas sensors. For the
protection of personnel and plant from flammable and toxic gas hazards.
Electrical
Input Voltage Range: 16 to 32 Vdc (24 Vdc nominal) for ATEX/IECEx/AP Versions
12 to 32 Vdc (24 Vdc nominal) for UL/CSA version
Max Power Consumption: Max 5 Watts. at 24 Vdc (see chapter 2 regarding maximum in rush
current) Current output 4-20 mA (Source or Sink)
≥0.0<1.0 mA Fault (refer to table 5 chapter 11.3 for further details).
4.0 mA to 20.0 mA Normal gas measurement
2.0 mA or 4.0 mA (17.4 mA) Inhibit (during configuration/user settings)
22.0 mA Maximum over range
Max load resistance 250 Ω
2 2
Terminals 15 x screw terminals suitable for wire diameter 0.5 mm to 2.5 mm (20 AWG
to 13 AWG).
Relays 3 x 5 A@250 VAC. Selectable normally open or normally closed (switch) and
energized/de-energized (programmable).
Communication RS485, Modbus RTU
Construction
Material Epoxy painted aluminium alloy or 316 Stainless Steel
Weight Aluminum alloy: 1.7 kg, 316 Stainless Steel: 3.7 kg
Mounting Pole or wall mounting
Entries 2 x M20 (for ATEX/IECEx/AP Approval) or 2x3/4’ NPT (for UL Approval)
Certification
China GB Ex d IIC T4 GB3836.1&2 -2000, PA, (CCCF)
Korea KTL Ex d IIC T6 (-40ºC to +65ºC)
US UL - Class I, Division 1, Groups B, C and D, Class I, Division 2, Groups B, C & D, Class II,
Division, Groups E, F & G, Class II, Division 2, Groups F & G. -40ºC to+65ºC
European ATEX/UKEX II 2 GD Ex db IIC T6 Gb (Ta -40ºC to +65ºC) T5 (Ta -40ºC to +75ºC) Ex tb IIIC T85ºC Db (Ta -40°C
to +65°C) IP66 T100ºC (Ta -40°C to +75°C)

IEC Ex II 2 GD Ex db IIC T6 Gb (Ta -40ºC to +65ºC) T5 (Ta -40ºC to +75ºC) Ex tb IIIC T85ºC Db (Ta -40°C to
International +65°C) IP66 T100ºC (Ta -40ºC to +75ºC)
EN50271, EN60079-29-1 (Flammable), EN50104 (Oxygen), EN45544 (Toxic)
Performance MED (O2, FL-CAT, FL-IR), ABS (FL-CAT, FL-IR, H2S), CCS (O2, FL, Toxic), BV(H2S)
Marine
CE EN50270:2015 EN61000-6-4:2007
Environmental
IP Rating IP66 in accordance with EN60529:1992
Operating -40ºC to +75ºC/ -40ºF to +167ºF
Note: The detector display may become illegible at temperatures below -40°C, but the detector continues its gas
Temperature monitoring function. The display is not damaged and recovers when the temperature rises back above -20 °C.

Operating Continuous 20-90 % RH (non-condensing), Intermittent 10-99 % RH (non-condensing)


Humidity
Operating 90-110 kPa (EC Toxic Sensors), 80-120 kPa (EC Oxygen, Catalytic Bead and Infrared Sensors)
Pressure
Storage -25°C to +65°C (-13°F to +149°F)
Conditions (detector
and accessories)

58
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Detectable Gases & Performance (See notes below)


Gas User Selectable Default Steps User Default Response Recovery Time for Accuracy Operating Temperature* Default alarm points Lowest Alarm Performance
Full Accuracy Range Selectable Cal Time (T90) Toxic Sensors Level Approved
Scale Range Cal Gas Point secs (T10) secs Min Max A1 A2
Range

Electrochemical Sensors
7
Oxygen 25.0%V/V only 25.0%V/V n/a20.9%V/V 20.9%V/V <30 40 <+/-0.5%V/V -20°C / -4°F 55°C / 131°F 19.5%V/V▼ 23.5%V/V▲ 5%V/V ✔
(Fixed)
Hydrogen Sulfide 10.0 to 100.0ppm 50.0ppm 1.0ppm 30 to 70% 25.0ppm <50 40 <+/-1ppm -20°C / -4°F 55°C / 131°F 10.0ppm▲ 20.0ppm▲ 1.0ppm ✔
Carbon Monoxide 100 to 1,000ppm 300ppm 100pp of 100ppm <30 40 <+/-6ppm -20°C / -4°F 55°C / 131°F 100ppm▲ 200ppm▲ 15ppm ✔
m selected
Hydrogen 1,000ppm only 1,000ppm n/a full-scale 500ppm <65 110 <+/-25ppm -20°C / -4°F 55°C / 131°F 200ppm▲ 400ppm▲ 100ppm
Nitrogen Dioxide** 10.0 to 50.0 ppm 10.0 ppm 5.0 range 5.0 ppm <40 75 +/-3ppm or +/- -20°C / -4°F 55°C / 131°F 5ppm ▲ 10ppm▲ 0.6ppm
ppm 20%
Catalytic Bead Sensors 25 to 95 %
Flammable 1 to 8* 20 to 100%LEL 100%LEL 10%LE of 50%LEL <258 N/A <+/-1.5%LEL -20°C / -4°F 55°C / 131°F 20%LEL▲ 40%LEL▲ 10-40%LEL Methane,
L selected dependent on and
full-scale star rating Propane
range
Infrared Sensors
Methane 20 to 100%LEL 100%LEL 10%LE 30 to 70% 50%LEL <30 N/A <+/-1.5%LEL -20°C / -4°F 55°C / 131°F 20%LEL▲ 40%LEL▲ 10%LEL ✔
L of
Propane 20 to 100%LEL 100%LEL 10%LE selected 50%LEL <30 N/A <+/-1.5%LEL -20°C / -4°F 55°C / 131°F 20%LEL▲ 40%LEL▲ 10%LEL ✔
L full-scale
Carbon Dioxide 2.00%V/V only 2.00%V/V n/a range 1.00%V/V <30 100 <+/-0.04%V/V -20°C / -4°F 55°C / 131°F 0.40%V/V▲ 0.80%V/V▲ 0.25%V/V

Carbon Dioxide 5.00%V/V only 5.00%V/V n/a 2.50%V/V <60 <70 <+/-0.2%V/V -20°C / -4°F 50°C / 122°F 0.40%V/V▲ 0.80%V/V▲ 0.25%V/V

59
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

▲ - Rising Alarm ▼ - Falling Alarm


NOTES
Performance figures are taken at 20~25°C;
1. measured using a sample humidity of 50 % RH, applicable between 10 and 90 % of full scale,
2. measured using test units calibrated at 50 % of full scale,
3. measured at 1000 cc/min for Methane CAT, 500 cc/min for O2, Toxic and Methane/Carbon Dioxide IR with calibration cup (S3KCAL).
4. Toxic and Oxygen sensor recovery times are taken at 20°C, 50 % RH and 500 cc/min with calibration cup (S3KCAL).
5. The maximum recommended alarm level for flammable sensors according to EN60079-29-1 is 60 % LEL.
6. Please note that XCD oxygen transmitter is intended for the measurement of oxygen deficiency or enrichment and not for inertisation measurements.
7. Response time (T90) under test conditions of EN 50104 ≤ 38 s
8. Response time (T90) under test conditions of EN 60079-29-1 for methane ≤ 55 s, for propane ≤ 60 s.
Response time (T90) may increase when operating in lower or higher temperature conditions or when gas is introduced with the Weather Protection accessory (SPXCDWP) fitted. Methane IR sensor is calibrated and linearized
only for Methane. Should it be exposed to other HC then non-linear response is expected. For linearized operation other than Methane contact Honeywell for alternate parts. Flammable CAT and Methane IR is calibrated at the
factory 50 % LEL Methane (2.5 % v/v). This calibration enables 100% functional test prior to dispatch. This calibration does not remove need for calibration & test as part of commissioning at site.
For gases other than Methane the unit has to be calibrated at site using target gas.Data represents typical values, and system conditioning may be required to achieve stated result. Contact Honeywell for details.

* Extended operating temperature range of -40°C to +65°C (-40°F to +149°F) for all sensor except for IR and H2 EC sensors, with an accuracy of +/- 30 % of applied gas from -20°C to -40°C (-4°F to -40°F) and +55°C to +65°C
(+131°F to +149°F). For the Methane IR Sensors, the accuracy is +/-10 % LEL from - 20°C to -40°C.
Long term operation at this range may cause decline in sensor performance.

** Care should be taken when setting alarm points lower than 3 ppm especially in high humidity conditions (higher than 50 % RH), since the gas reading could be lower than the actual concentration. Contact
Honeywell Analytics for any additional data or details.

60
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

14. Ordering information


Part number Description
Sensepoint XCD transmitter and sensor KIT (ATEX/IECEx/AP*, LM25 and M20 Entry)
SPXCDALMFX ATEX/IECEx/AP* Methane CAT 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with LM25, M20 Entry
SPXCDALMRX ATEX/IECEx/AP* Methane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with LM25, M20 Entry
SPXCDALMPX ATEX/IECEx/AP* Propane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with LM25, M20 Entry
SPXCDALMO1 ATEX/IECEx/AP* Oxygen 25.0% v/v with LM25, M20 Entry
SPXCDALMHX ATEX/IECEx/AP* Hydrogen Sulfide 0-50ppm (10.0 to 100.0ppm, 1ppm) with LM25, M20 Entry
SPXCDALMCX ATEX/IECEx/AP* Carbon Monoxide 0-500ppm (100 to 1000ppm, 100ppm) with LM25, M20 Entry
SPXCDALMG1 ATEX/IECEx/AP* Hydrogen 0-1000ppm with LM25, M20 Entry
SPXCDALNNX ATEX/IECEx/AP* Nitrogen Dioxide 0-50ppm with Aluminum alloy, M20 Entry
SPXCDALMB1 ATEX/IECEx/AP* approved Carbon Dioxide IR 0-2.00% v/v with LM25, M20 Entry
SPXCDALMB2 ATEX/IECEx/AP* approved Carbon Dioxide IR 0-5.00% v/v with LM25, M20 Entry
Sensepoint XCD transmitter and sensor KIT (ATEX/IECEx/AP*, 316SS and M20 Entry)
SPXCDASMFX ATEX/IECEx/AP* approved Methane CAT 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, M20 Entry
SPXCDASMRX ATEX/IECEx/AP* approved Methane IR 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, M20 Entry
SPXCDASMPX ATEX/IECEx/AP* approved Propane IR 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, M20 Entry
SPXCDASMO1 ATEX/IECEx/AP* approved Oxygen 25.0% v/v with 316SS, M20 Entry
SPXCDASMHX ATEX/IECEx/AP* approved Hydrogen Sulfide 0-50ppm (10.0 to 100.0ppm, 1ppm) with 316SS, M20 Entry
SPXCDASMCX ATEX/IECEx/AP* approved Carbon Monoxide 0-300ppm (100 to 1000ppm, 100ppm) with 316SS, M20 Entry
SPXCDASMG1 ATEX/IECEx/AP* approved Hydrogen 0-1000ppm with 316SS, M20 Entry
SPXCDASNNX ATEX/IECEX/ AP* approved Nitrogen Dioxide 0-50ppm with SS316, M20 Entry
SPXCDASMB1 ATEX/IECEx/AP* approved Carbon Dioxide IR 0-2.00% v/v with 316SS, M20 Entry
SPXCDASMB2 ATEX/IECEx/AP* approved Carbon Dioxide IR 0-5.00% v/v with 316SS, M20 Entry
Sensepoint XCD transmitter and sensor KIT (UL, LM25 and 3/4' NPT Entry)
SPXCDULNFX UL/cUL approved Methane CAT 0-100%LEL (20 to 100%LEL, 10%LEL) with LM25, 3/4’ NPT Entry
SPXCDULNRX UL/cUL approved Methane IR 0-100%LEL (20 to 100%LEL, 10%LEL) with LM25, 3/4’ NPT Entry
SPXCDULNPX UL/cUL approved Propane IR 0-100%LEL (20 to 100%LEL, 10%LEL) with LM25, 3/4’ NPT Entry
SPXCDULNO1 UL/cUL approved Oxygen 25.0% v/v with LM25, 3/4’ NPT Entry
SPXCDULNHX UL/cUL approved Hydrogen Sulfide 0-50ppm (10.0 to 100.0ppm, 1ppm) with LM25, 3/4’ NPT Entry
SPXCDULNCX UL/cUL approved Carbon Monoxide 0-300ppm (100 to 1000ppm, 100ppm) with LM25, 3/4’ NPT Entry
SPXCDULNG1 UL/cUL approved Hydrogen 0-1000ppm with LM25, 3/4’ NPT Entry
SPXCDULNNX UL approved SP XCD Nitrogen Dioxide 0-50ppm with LM25, 3/4’ NPT Entry
SPXCDULNB1 UL/cUL approved Carbon Dioxide IR 0-2.00% v/v with LM25, 3/4’ NPT Entry
SPXCDULNB2 UL/cUL approved Carbon Dioxide IR 0-5.00% v/v with LM25, 3/4’ NPT Entry
Sensepoint XCD transmitter and sensor KIT (UL, 316SS and 3/4’ NPT Entry)
SPXCDUSNFX UL/cUL approved Methane CAT 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, 3/4’ NPT Entry
SPXCDUSNRX UL/cUL approved Methane IR 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, 3/4’ NPT Entry
SPXCDUSNPX UL/cUL approved Propane IR 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, 3/4’ NPT Entry
SPXCDUSNO1 UL/cUL approved Oxygen 25.0% v/v with 316SS, 3/4’ NPT Entry
SPXCDUSNHX UL/cUL approved Hydrogen Sulfide 0-50ppm (10.0 to 100.0ppm, 1ppm) with 316SS, 3/4’ NPT Entry
SPXCDUSNCX UL/cUL approved Carbon Monoxide 0-300ppm (100 to 1000ppm, 100ppm) with 316SS, 3/4’ NPT Entry
SPXCDUSNG1 UL/cUL approved Hydrogen 0-1000ppm with 316SS, 3/4’ NPT Entry
SPXCDUSNNX UL approved SP XCD Nitrogen Dioxide 0-50ppm with SS316, 3/4’ NPT Entry
SPXCDUSNB1 UL/cUL approved Carbon Dioxide IR 0-2.00% v/v with 316SS, 3/4’ NPT Entry
SPXCDUSNB2 UL/cUL approved Carbon Dioxide IR 0-5.00% v/v with 316SS, 3/4’ NPT Entry
Sensepoint XCD transmitter and sensor KIT (ATEX/IECEx/AP*, LM25 and M20 Entry with Modbus)
SPXCDALMFXM ATEX/IECEx/AP* Methane CAT 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with LM25, M20 Entry, with Modbus
SPXCDALMRXM ATEX/IECEx/AP* Methane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with LM25, M20 Entry, with Modbus
SPXCDALMPXM ATEX/IECEx/AP* Propane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with LM25, M20 Entry, with Modbus
SPXCDALMO1M ATEX/IECEx/AP* Oxygen 25.0% v/v with LM25, M20 Entry, with Modbus
SPXCDALMHXM ATEX/IECEx/AP* Hydrogen Sulfide 0-50ppm (10.0 to 100.0ppm, 1ppm) with LM25, M20 Entry, with Modbus
SPXCDALMCXM ATEX/IECEx/AP* Carbon Monoxide 0-500ppm (100 to 1000ppm, 100ppm) with LM25, M20 Entry, with Modbus
SPXCDALMG1M ATEX/IECEx/AP* Hydrogen 0-1000ppm with LM25, M20 Entry, with Modbus
SPXCDALNNXM ATEX/IECEX /AP approved Nitrogen Dioxide 0-50ppm with LM25, M20 Entry, With Modbus
SPXCDALMB1M ATEX/IECEx/AP* approved Carbon Dioxide IR 0-2.00% v/v with LM25, M20 Entry, with Modbus
SPXCDALMB2M ATEX/IECEx/AP* approved Carbon Dioxide IR 0-5.00% v/v with LM25, M20 Entry, with Modbus
Sensepoint XCD transmitter and sensor KIT (ATEX/IECEx/AP*, 316SS and M20 Entry with Modbus)
SPXCDASMFXM ATEX/IECEx/AP* approved Methane CAT 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, M20 Entry, with Modbus
SPXCDASMRXM ATEX/IECEx/AP* approved Methane IR 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, M20 Entry, with Modbus
SPXCDASMPXM ATEX/IECEx/AP* approved Propane IR 0-100%LEL (20 to 100%LEL, 10%LEL) with 316SS, M20 Entry, with Modbus
SPXCDASMO1M ATEX/IECEx/AP* approved Oxygen 25.0% v/v with 316SS, M20 Entry, with Modbus
SPXCDASMHXM ATEX/IECEx/AP* approved Hydrogen Sulfide 0-50ppm (10.0 to 100.0ppm, 1ppm) with 316SS, M20 Entry, with Modbus
SPXCDASMCXM ATEX/IECEx/AP* approved Carbon Monoxide 0-300ppm (100 to 1000ppm, 100ppm) with 316SS, M20 Entry, with Modbus
SPXCDASMG1M ATEX/IECEx/AP* approved Hydrogen 0-1000ppm with 316SS, M20 Entry, with Modbus
SPXCDASNNXM ATEX/IECEX /AP approved Nitrogen Dioxide 0-50ppm with SS316, M20 Entry, With Modbus
SPXCDASMB1M ATEX/IECEx/AP* approved Carbon Dioxide IR 0-2.00% v/v with 316SS, M20 Entry, with Modbus
SPXCDASMB2M ATEX/IECEx/AP* approved Carbon Dioxide IR 0-5.00% v/v with 316SS, M20 Entry, with Modbus
UL APPROVAL (Epoxy Coated Aluminum Alloy, LM25, With Modbus)
SPXCDULNFXM UL/cUL approved Flammable CAT 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with LM25, 3/4’ NPT Entry, with Modbus
SPXCDULNRXM UL/cUL approved Methane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with LM25, 3/4’ NPT Entry, with Modbus
SPXCDULNPXM UL/cUL approved Propane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with LM25, 3/4’ NPT Entry, with Modbus
SPXCDULNO1M UL/cUL approved Oxygen 25.0% v/v with LM25, 3/4’ NPT Entry, with Modbus
SPXCDULNHXM UL/cUL approved Hydrogen Sulfide 0-50ppm (10.0 to 100.0ppm, 1ppm) with LM25, 3/4’ NPT Entry, with Modbus

61
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

SPXCDULNCXM UL/cUL approved Carbon Monoxide 0-500ppm (100 to 1000ppm, 100ppm) with LM25, 3/4’ NPT Entry, with Modbus
SPXCDULNG1M UL/cUL approved Hydrogen 0-1000ppm with LM25, 3/4’ NPT Entry, with Modbus
SPXCDULNNXM UL/cUL approved Nitrogen Dioxide 0-50ppm with LM25, 3/4’ NPT Entry, with Modbus
SPXCDULNB1M UL/cUL approved Carbon Dioxide IR 0-2% v/v with LM25, 3/4’ NPT Entry, with Modbus
SPXCDULNB2M UL/cUL approved Carbon Dioxide IR 0-5% v/v with LM25, 3/4’ NPT Entry, with Modbus
UL APPROVAL (Epoxy Coated Stainless Steel, SS316, With Modbus)
SPXCDUSNFXM UL/cUL approved Flammable CAT 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with SS316, 3/4’ NPT Entry, with Modbus
SPXCDUSNRXM UL/cUL approved Methane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with SS316, 3/4’ NPT Entry, with Modbus
SPXCDUSNPXM UL/cUL approved Propane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) with SS316, 3/4’ NPT Entry, with Modbus
SPXCDUSNO1M UL/cUL approved Oxygen 25.0% v/v with SS316, 3/4’ NPT Entry, with Modbus
SPXCDUSNHXM UL/cUL approved Hydrogen Sulfide 0-50ppm (10.0 to 100.0ppm, 1ppm) with SS316, 3/4’ NPT Entry, with Modbus
SPXCDUSNCXM UL/cUL approved Carbon Monoxide 0-500ppm (100 to 1000ppm, 100ppm) with SS316, 3/4’ NPT Entry, with Modbus
SPXCDUSNG1M UL/cUL approved Hydrogen 0-1000ppm with SS316, 3/4’ NPT Entry, with Modbus
SPXCDUSNNXM UL/cUL approved Nitrogen Dioxide 0-50ppm with SS316, 3/4’ NPT Entry, with Modbus
SPXCDUSNB1M UL/cUL approved Carbon Dioxide IR 0-2% v/v with SS316, 3/4’ NPT Entry, with Modbus
SPXCDUSNB2M UL/cUL approved Carbon Dioxide IR 0-5% v/v with SS316, 3/4’ NPT Entry, with Modbus
Replacement sensor Cartridge
SPXCDXSFXSS Methane CAT 0-100%LEL (20,0 to 100.0%LEL, 10%LEL)
SPXCDXSRXSS Methane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL)
SPXCDXSPXSS Propane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL)
SPXCDXSO1SS Oxygen 25.0% v/v only
SPXCDXSHXSS Hydrogen Sulfide 0-50ppm (10.0 to 100.0ppm, 1ppm)
SPXCDXSCXSS Carbon Monoxide 0-500ppm (100 to 1000ppm, 100ppm)
SPXCDXSG1SS Hydrogen 0-1000ppm only
SPXCDXSNXSS Nitrogen Dioxide 0-10ppm (10.0 to 50.0ppm)
SPXCDXSB1SS Carbon Dioxide IR 0-2.00% v/v only
SPXCDXSB2SS Carbon Dioxide IR 0-5.00% v/v only
Accessories
S3KCAL Calibration cap
SPXCDCC Collecting cone for use with lighter than air gases
SPXCDDMK Duct mounting kit
SPXCDMTBR Pipe Mounting bracket (including fixings and hex wrench set)
SPXCDSDP Sunshade / Deluge Protection
SPXCDHMANEN Hard Copy Manual in English language
SPXCDHMANCN Hard Copy Manual in Chinese language
SPXCDHMANKR Hard Copy Manual in Korean language
Spares
SPXCDDMT12 Replacement display module (O2 & Toxic)
SPXCDDMF12 Replacement display module (FL & IR)
SPXCDTMO12 Replacement terminal module (O2)
SPXCDTMT12 Replacement terminal module (Toxic)
SPXCDTMF12 Replacement terminal module (FL & IR)
SPXCDMBUS Replacement Modbus Module
SPXCDSERVK Service Kit containing all o-rings, terminal module and locking screws
SPXCDTOOLK Factory toolkit containing magnetic wand and hex wrenches for locking and earth screws
SPXCDTMK Terminal block set
SPXCDNPTP 3/4’ NPT Plug
SPXCDM20P M20 Plug
SPXCDMANCD Instruction manual CD-ROM
SPXCDNADP 3/4’ NPT to M20 Adaptor
SPXCDWP Weather Protection
SPXCDSRLS Sensor Retainer with locking screw
SPXCDEBS Earth Bracket and Screws
Special Flammable Gas Calibration
SPXCDSFGC1 Special Flammable Gas Calibration, 0-100%LEL, 1*
SPXCDSFGC2 Special Flammable Gas Calibration, 0-100%LEL, 2*
SPXCDSFGC3 Special Flammable Gas Calibration, 0-100%LEL, 3*
SPXCDSFGC4 Special Flammable Gas Calibration, 0-100%LEL, 4*
SPXCDSFGC5 Special Flammable Gas Calibration, 0-100%LEL, 5*
SPXCDSFGC7 Special Flammable Gas Calibration, 0-100%LEL, 7*
SPXCDSFGC8 Special Flammable Gas Calibration, 0-100%LEL, 8*
Note: If no Special Flammable Gas Calibration part no. is included on PO, a Methane (6* calibration will be supplied)

* AP approvals include GB & PA for China and KTL for Korea.

62
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

15. Warranty statement


All products are designed and manufactured to the latest internationally recognized standards by
Honeywell Analytics under a Quality Management system that is certified to ISO 9001. As such
Honeywell Analytics warrants its products against defective parts and workmanship and will repair or
(at its option) replace any instruments which are or may become defective under proper use within
12 months from date of commissioning by an approved Honeywell Analytics representative or 18
months from date of shipment from Honeywell Analytics, whichever is the sooner. This warranty does
not cover disposable batteries or damage caused by accident, abuse, abnormal operating conditions
or poisoning of sensor.

Defective goods must be returned to Honeywell Analytics premises accompanied by a detailed


description of any issue. Where return of goods is not practicable Honeywell Analytics reserves the
right to charge for any site attendance where any fault is not found with the equipment. Honeywell
Analytics shall not be liable for any loss or damage whatsoever or howsoever occasioned which may
be a direct or indirect result of the use or operation of the Contract Goods by the Buyer or any Party.

This warranty covers instrument and parts sold to the Buyer only by authorized distributors, dealers
and representatives as appointed by Honeywell Analytics. The warranties set out in this clause are
not pro rata, i.e. the initial warranty period is not extended by virtue of any works carried out there
under.

In no event will Honeywell Analytics be liable for any incidental damages, consequential damages,
special damages, punitive damages, statutory damages, indirect damages, loss of profits, loss of
revenues, or loss of use, even if informed of the possibility of such damages. Honeywell Analytics
liability for any claims arising out of or related to this product will in no case exceed the order value.
To the extent permitted by applicable law, these limitations and exclusions will apply regardless of
whether liability arises from breach of contract, warranty, tort (including but not limited to negligence),
by operation of law, or otherwise.

63
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

16. Installation Drawing


Mechanical Installation Drawing

64
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Electronic Connection Drawing

65
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Duct Mounting Drawing

66
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Collecting Cone Drawing

67
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Mounting Bolt Assy Drawing

68
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Mounting Bracket Drawing

69
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

17. Certification
ATEX/UKEX/IECEx Special Conditions for Safe Use
Sensor:
The integral supply cables shall be protected from impact and be suitably terminated.

The attachment thread has a 2.5 mm wide undercut. This shall be taken into consideration if the
sensor is attached to a flameproof enclosure in order to maintain the minimum engaged thread
length.

Equipotential bonding shall be provided by the mounting arrangements.

The sensor cartridge to housing joint maximum gap is 0.035mm which is less than that permitted. This
joint shall not be enlarged in service.

When fitted with the supplied weather guard, the sensor head must be mounted so that the sinter is
pointing downward to provide ingress protection IPX6.

The weather guard is a potential electrostatic charging hazard. The manufacturer's instructions should
be observed.

Transmitter:
The transmitter has a potential electrostatic charging hazard. To minimize the risk of electrostatic
discharge:
• Ground the transmitter adequately
• Install the transmitter in a manner that will prevent accidental electrostatic discharges, e.g. ensure
that objects do not rub against the housing etc.
• Clean the enclosure with a damp cloth when necessary

Standard and certification


Certificate Standard

UL E480011 Class I, Division 1, Groups B, C and D, Class I, Division 2, Groups B, C & D, Class II,
Division, Groups E, F & G, Class II, Division 2, Groups F & G. -40ºC to+65ºC

ATEX Sensor head: EN IEC 60079-0:2018


UL 21 ATEX 2620X EN IEC 60079-1:2014
Transmitter: EN IEC 60079-31:2014
UL 21 ATEX 2619X
Sensor head:
II 2 GD Ex db IIC T6 Gb (Ta -40°C to +65°C) T4 (Ta -40°C to +75°C)
Ex tb IIIC T85°C Db (Ta -40°C to +65°C) IP6X, T135°C (Ta -40°C to +75°C)
Transmitter:
II 2 GD Ex db IIC T6 Gb (Ta -40ºC to +65ºC) T5 (Ta -40ºC to +75ºC)
Ex tb IIIC T85ºC Db (Ta -40°C to +65°C) IP66 T100ºC (Ta -40°C to +75°C)
IECEx Sensor head: IEC 60079-0:2017, 7th Ed
IECEx UL 21.0106X IEC 60079-1:2014, 7th Ed+Corr.1(2018)
Transmitter: IEC 60079-31:2013, 2nd Ed
IECEx UL 21.0105X
Sensor head:
Ex db IIC T6 Gb (Ta -40°C to +65°C) T4 (Ta -40°C to +75°C)
Ex tb IIIC T85°C Db (Ta -40°C to +65°C) IP6X, T135°C (Ta -40°C to +75°C)
Transmitter:
Ex db IIC T6 Gb (Ta -40ºC to +65ºC) T5 (Ta -40ºC to +75ºC)
Ex tb IIIC T85ºC Db (Ta -40°C to +65°C) IP66 T100ºC (Ta -40ºC to +75ºC)
UKEX UL21UKEX2359X
UL21UKEX2360X

70
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Sensepoint XCD ATEX/UKEX Name Plate

Sensepoint XCD UL Name Plate

71
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Sensepoint XCD Warning Tag

72
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Sensor Cartridges Label

Special Conditions for Use in European Gas


Performance Approval
Sensepoint XCD is approved for European Gas Performance with the following specific conditions:

• IEC/EN 60079-29-1 for CH4 and C3H8 with the measuring range 0 – 100 % LEL

• EN 45544-1/-3:2015 for CO (0 – 300 ppm) and H2S (0 – 50 ppm)

• EN 50104:2010 for O2 with the measuring range 0 – 25 % v/v (no inertisation)

• Only 4 – 20 mA is considered as a safety function. The other outputs are optional signals
outside the scope of the European gas performance approval. 4-20 mA output is refreshed at
least every two seconds.

• Analogue output signal status as a safety function:

≤ 1 mA: System and other faults

2 mA: Start-up, inhibit

4 – 20 mA: Gas reading range (when deadband is on)

22 mA: Over-range

• Analogue output shall be tested at least once a year to verify the operation of safety function.
Refer to chapter 9 of this manual for gas calibration and bump test. Refer to chapter 12.2 of
this manual for “FORCE CURRENT” menu.

• Sensepoint XCD flammable catalytic sensor would produce higher gas measurement when
located in 90° with respect to the air velocity. It is prohibited to install Sensepoint XCD
flammable catalytic sensor at 90° with respect to the air velocity for an application requiring
IEC/EN 60079-29-1 compliance.

73
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

18. Cross Interference and Cross Calibration


Cross Interference Table for Toxic and Oxygen
This below table shows the relative cross sensitivity of the Sensepoint XCD to other gases. ‘Gas Type’
indicates the sensor type fitted to the Sensepoint XCD. ‘Gas Type Applied’ indicates the gas that may
be applied to that sensor and the resulting reading.
Gas type Gas Type Applied Concentration Unit Reading Unit

% v/v (change O2
O2 Carbon Dioxide 5 % v/v 0.1
reading) per % v/v CO2
Ammonia 50 ppm 0 ppm H2S
Carbon Monoxide 100 ppm <2 ppm H2S
Carbon Dioxide 5000 ppm 0 ppm H2S
Chlorine 0.5 ppm 0 ppm H2S
H2S Ethylene 100 ppm 0 ppm H2S
Hydrogen 100 ppm 0 ppm H2S
Hydrogen Sulfide 10 ppm 10 ppm H2S
Nitrogen Monoxide 25 ppm 0 ppm H2S
Nitrogen Dioxide 3 ppm 0 ppm H2S
Sulfur Dioxide 2 ppm 0 ppm H2S
Acetone 1000 ppm 0 ppm CO
Acetylene 40 ppm 80 ppm CO
Ammonia 100 ppm 0 ppm CO
Carbon Monoxide 100 ppm 100 ppm CO
Chlorine 2 ppm 0 ppm CO
CO Ethanol 2000 ppm 3 ppm CO
Ethylene 100 ppm 85 ppm CO
Hydrogen 100 ppm 20 ppm CO
Hydrogen 25 ppm 0 ppm CO
Iso-Propanol 200 ppm 0 ppm CO
Nitrogen Monoxide 50 ppm 8 ppm CO
Nitrogen Dioxide 800 ppm 20 ppm CO
Sulfur Dioxide 50 ppm 0.5 ppm CO
Carbon Monoxide 300 ppm ≤60 ppm H2
Hydrogen Sulfide 15 ppm <3 ppm H2
Sulfur Dioxide 5 ppm 0 ppm H2
H2 Nitrogen Monoxide 35 ppm >10 ppm H2
Nitrogen Dioxide 5 ppm 0 ppm H2
Chlorine 1 ppm 0 ppm H2
Hydrogen Cyanide 10 ppm »3 ppm H2
Hydrogen Chloride 5 ppm 0 ppm H2
Ethylene 100 ppm >80 ppm H2

Table 9 Cross Interference

74
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Cross Calibration Flammable Gas Detector


Note: Not a scope for performance approval
For greater accuracy, a catalytic gas detector should be calibrated using a certified gas/air mixture equal
to 50 % LEL of the actual target gas intended to be monitored.
However, it is not always practical to obtain every detectable type of hydrocarbon gas in a calibration-
ready, certified and verifiable form. Therefore, it is possible to carry out a ‘cross calibration’ using another
hydrocarbon gas/air mixture.
When the Sensepoint XCD Combustible LEL sensor is to be calibrated with a gas which is different to
the gas or vapour to be detected, the following cross calibration procedure may be followed:

CAUTION
Where the user calibrates any sensor using a different gas, responsibility for identifying and
recording calibration rests with the user. Refer to the local regulations where appropriate.

Note: Table 10 lists a selection of hydrocarbon compounds and states a reference figure or ‘Star
Rating’ according to the reaction they produce in relation to other hydrocarbons. An eight-star (8*) gas
produces the highest output, while a one-star (1*) gas produces the lowest output.
No. Gas Star Rating
1 Acetone 4*
2 Ammonia 7*
3 Benzene 3*
4 Butanone 3*
5 Butane 4*
6 Butyl acetate 1*
7 Butyl acrylate 1*
8 Cyclohexane 3*
9 Cyclohexanone <1*
10 Diethyl ether 4*
11 Ethane 6*
12 Ethanol 5*
13 Ethyl acetate 3*
14 Ethylene 5*
15 Heptane 3*
16 Hexane 3*
17 Hydrogen 6*
18 Methane 6*
19 Methanol 5*
20 MIBK 3*
21 Octane 3*
22 Pentane 3*
23 Propane 5*
24 Propan-2-ol 4*
25 Styrene 2*
26 Tetra hydrafuran 4*
27 Toluene 3*
28 Triethylamine 3*
29 Xylene 2*

Table 10 Star Rating of Gases

75
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

To cross calibrate the Sensepoint XCD flammable gas detector:


Obtain the star rating for both the calibration test gas and the gas to be detected from Table 10
These values may then be used in Table 11 to obtain the required calibration span setting when a 50 %
LEL test gas is applied to the detector.

Table 11 Calibration span setting


Note: These settings must only be used with a calibration gas concentration of 50 % LEL.

If a sensor is to be used to detect a gas other than that for which it was calibrated and there is no
intention to use an equivalent calibration gas to re-calibrate the sensor, then the required correction
factor may be obtained from Table 12

The reading shown on the gas detector controller or transmitter display should be multiplied by this
number in order to obtain a more accurate gas concentration result.

0.64

Table 12 Correction factors


Note:
Since catalytic sensors require oxygen for correct operation, a mixture of gas in air should always be
used for calibration purposes.
Assuming average performance of the sensor, the sensitivity information in Tables 10 to 12 is
normally accurate to + or - 30 %.

76
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Working Example:
If the target gas to be detected is 0-100 % LEL Ethylene and the only calibration gas available to re-
calibrate the sensor is Methane (at 50 % LEL concentration), the procedure is as follows:
Look up the star rating for each gas in Table 10.

Gas No. 14, Ethylene = 5*


Gas no. 18, Methane = 6*

Then, look up the span settings for a 50 % LEL calibration gas in Table 11 by selecting the row of figures
next to the 6* in the ‘calibration gas’ column. Select the figure in the 5* column of the ‘gas to be detected’
chapter.

This means that during re-calibration, the span gas setting on the gas detector transmitter or controller
should be set to 62 % LEL to give an accurate measuring scale for 0-100 % LEL Ethylene, when using
50 % LEL Methane as the calibration gas.

Contact your local Honeywell Analytics sales or service distributor, or regional office if further clarification
or additional information be required.

77
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Meter Multiplication Factors for Sensepoint XCD-IR


Propane

It is possible to apply a linear cross reference factor to the output of a sensor characterized for propane
and achieve the results shown in the graph below.
Reasonable accuracy is maintained to at least the 50 % LEL equivalent values of the cross-referred
gasses.

XCD IR Propane Sensor (Full scale 2 % v/v or 100 % LEL)

Diagram 20 . Sensepoint XCD-IR (Propane) Sensor with linear cross-reference factor applied

Use the following multiplying factors to cross-refer to the propane reading:


Gas Multiplication Factor
Ethylene 3.43
nButane 0.97
nPentane 0.89
Table 13 Multiplying Factors

CAUTION
These factors only apply to gas concentrations expressed in % Volume terms. When
using a linear cross-reference factor, the temperature compensation is based upon
propane, and there may be errors at temperatures away from the calibration
temperature.

Note: Honeywell Analytics recommends that users verify the accuracy of their instruments using test
gasses wherever possible. Cross-referred measurements should be used as a guide only, not as
absolute values.

78
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

Appendix A - Modbus® Protocol A-2


A.1 Modbus and the Sensepoint XCD
The Sensepoint XCD gas detector may be fitted with the optional Modbus board. Information on the
Modbus Upgrade Kit can be found in chapter 14 Ordering Information. The Sensepoint XCD supports
Modbus/RTU over an RS-485 physical layer. The interface is isolated and includes a switchable 120
Ohm termination resistor. Baud rates 9,600 or 19,200 are supported with 19,200 as the default. Most of
the operations that are possible with local user interface can also be performed over the Modbus
interface.

See chapter 5.2 and 5.7 for information on installing the optional Modbus hardware. See chapter 12.3.3
Configure Menu – Set ID Settings for information on setting the Modbus baud rate and parity using the
local user interface.

The suggested polling interval is 0.2 to 1 seconds depending on cable type, length and connected nodes.

79
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

A.2 Modbus Registers


Modbus Information R/W Type Size Note
Register
Address
30001 Main SW Version of XCD R u8 1
30002 EEP Version of XCD R u8 1
30003 WatchDog s/w Version of XCD R u8 2
30004 Location string R 12 chars 6
30010 Modbus slave ID R u8 1
30011 Monitor Status R u16 1 Upper byte: Function
Lower byte: Instrument Mode
30012 Inhibit current(mA) R u8 1 20 means 2.0mA
30013 Reserved R u16 1
30014 Active Alarm R u32 2 bit 0 Alarm 1 is active
bit 1 Alarm 2 is active
30016 Latched Alarm R u32 2 bit 0 Alarm 1 is active
bit 1 Alarm 2 is active
30018 Active Fault R u32 2 bit 0 ~ 4: warnings, W1 ~ W5
bit 5: reserved
bit 6 ~ 18: faults, F1 ~ F13
bit 19 ~ 31: reserved
30020 Latched Fault R u32 2 bit 0 ~ 4: warnings, W1 ~ W5
bit 5: reserved
bit 6 ~ 18: faults, F1 ~ F13
bit 19 ~ 31: reserved
40001 Systern ID code R u16 1 Upper Byte: Type Code: 0x25
Lower Byte: My Address
40002 Systern ID code R u16 1 Upper Byte: Type Code: 0x25
Lower Byte: My Address: Dummy Spacer
40003 Gas reading R f32 2
40005 Fault and Warning R u16 1 Fault = 1100 + Number
Warning = Number as is
40006 Alarm, fault and warning state R u8 1 bit 0 Alarm 1 is active
bit 1 Alarm 2 is active
bit 2,3 for future expansion bit 4 Warning is active
bit 5 Fault is active
bit 6,7 for future expansion
Note: Latching relay setting latches Modbus values in
register 40006.

40007 Monitor state monitoring R u8 1 1: Normal


2: Warm Up after power on
3: Inhibit
12: Calibration
40008 Reserved R u16 1
40009 Calibration Due R f32 2
40011 Measuring Unit R u8 1 4: PPM
3: %Vol
5: %LEL
1: mg/m3v
40012 Peak Reading R f32 2 Peak Reading
40014 Reserved R u16 3
40017 Temperature (oC) R s16 1
40018 Reserved R u16 28
40046 Measuring Gas name string R 14 chars 7
40053 Reserved R s16 1
40054 Temperature (oF) R s16 1
40055 Reserved R u16 1
40056 Relay Status R u8 1 1: Energized, 0: De-energized
40057 Power Supply R f32 2
40059 Calibration Interval R/W u16 1
40060 Alarm Type R/W u8 1 High nibble: Alarm 2 Type
Low nibble: Alarm 1 Type
0: Disable, 1: Rising, 2: Falling
40061 Inhibit timeout R/W u16 1
40062 Relay configuration R/ u16 1 Bit 0, 1: Relay 1 Type
W Bit 2, 3: Relay 2 Type
Bit 4, 5: Relay 3 Type
Bit 6 ~ 8: Relay 1 Status ~ Relay 3 Status
Bit 9 : Relay latch option

80
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

A.3 User Configurable Parameter List


Menu Item Description
Set Calibration Zero calibration level Set zero calibration gas level
Set Calibration Span calibration level Set span calibration gas level
Select Sensor Type of sensor Type of sensor from the sensor list.
Available only for the flammable / IR sensors.
Select Gas Type of gas Type of gas from the sensor list.
Available only for the flammable / IR sensors.
Set Range Measuring range Measuring range
Configure Inhibit Inhibit current Inhibit current
Configure Inhibit Inhibit timeout Inhibit timeout
Set Password Password Password required for entering the Configuration mode
Set Calibration Interval Calibration Interval Calibration Interval
Set Alarms Alarm 1 level Alarm 1 level
Set Alarms Alarm 1 rising/falling option Alarm 1 rising/falling option
Set Alarms Alarm 2 level Alarm 2 level
Set Alarms Alarm 2 rising/falling option Alarm 2 rising/falling option
Set Relays Relay 1 type Type of relay 1 (Alarm 1, Alarm 2, Fault, Inhibit)
Set Relays Relay 1 action Type of relay 1 action (deenergize, energize)
Set Relays Relay 2 type Type of relay 2 (Alarm 1, Alarm 2, Fault, Inhibit)
Set Relays Relay 2 action Type of relay 2 action (deenergize, energize)
Set Relays Relay 3 type Type of relay 3 (Alarm 1, Alarm 2, Fault, Inhibit)
Set Relays Relay 3 action Type of relay 3 action (deenergize, energize)
Relay Operation Relay on delay time Relay on delay time
Relay Operation Relay off delay time Relay off delay time
Relay Operation Relay latch option Relay latch option
Set Location Location tag Location tag
Set Temperature Unit Temperature unit Temperature unit
Set Deadband Deadband option Deadband is included in the measuring range or not

81
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

A.4 Ranges of User Configurable Parameter


CH4 - Propane Propane -
CH4 -IR
Menu Item Sub Item O2 CO H2S CAT -CAT IR
(Ir-3)
(cb-3) (cb-4) (Ir-4)

Set
Zero and span factor The zero factor and span factor are updated by an internal calibration algorithm.
Calibration

Default N/A N/A N/A cb-4 cb-4 Ir-3 Ir-4

Select Sensor Item 1 N/A N/A N/A Ir-7 Ir-7

Item 11 N/A N/A N/A cb-3 cb-3

Default str6 str6 mEt Prop

Item 1 N/A N/A N/A str1 str1 mEt Prop

Item 2 N/A N/A N/A str2 str2

Item 3 N/A N/A N/A str3 str3

Select Gas Item 4 N/A N/A N/A str4 str4

Item 5 N/A N/A N/A str5 str5

Item 6 N/A N/A N/A str6 str6

Item 7 N/A N/A N/A str7 str7

Item 11 N/A N/A N/A str8 str8

Default N/A 300 50 100 100 100 100

Set Range Min N/A 100 10 20 10 20 20

Max N/A 1000 100 100 100 100 100

Default 2 2 2 2 2 2 2
Current

Min 2 2 2 2 2 2 2

Max 17.4 4 4 4 4 4 4
Configure
Inhibit
Default 0 0 0 0 0 0 0
Timeout

Min 0 0 0 0 0 0 0

Max 60 60 60 60 60 60 60

Default 0 0000 0000 0000 0000 0000 0000

Set Password Min 0 0000 0000 0000 0000 0000 0000

Max 999 9999 9999 9999 9999 9999 9999

Default 180 180 180 180 180 180 180


Set
Calibration Min 365 365 365 365 365 365 365
Interval
Max 30 30 30 30 30 30 30

level - Default 19.5 100 10 20 20 20 20


Alarm 1

Set Alarms level - Min 5 15 1 10 10 10 10

level - Max 25 300 50 100 100 100 20

82
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

CH4 - Propane Propane -


CH4 -IR
Menu Item Sub Item O2 CO H2S CAT -CAT IR
(Ir-3)
(cb-3) (cb-4) (Ir-4)

Func. - Default rise rise rise rise rise rise rise

Item 1 rise rise rise rise rise rise rise

Item 2 fall fall fall fall fall fall fall

Item 3 none none none none none none none

level - Default 23.5 200 20 40 40 40 40

level - Min 5 15 1 10 10 10 10

level - Max 2 300 50 100 100 100 40


Alarm 2

Func. - Default rise rise rise rise rise rise rise

Item 1 rise rise rise rise rise rise rise

Item 2 fall fall fall fall fall fall fall

Item 3 none none none none none none none

Func. - Default 7 AL1 AL1 AL1 AL1 AL1 AL1

Item 1 AL1 AL1 AL1 AL1 AL1 AL1 AL1

Item 2 AL2 AL2 AL2 AL2 AL2 AL2 AL2

Item 3 Inhb Inhb Inhb Inhb Inhb Inhb Inhb


Relay 1

Item 4 Flt Flt Flt Flt Flt Flt Flt

Oper. - Default dEEn dEEn dEEn dEEn dEEn dEEn dEEn

Item 1 dEEn dEEn dEEn dEEn dEEn dEEn dEEn

Item 2 Enrg Enrg Enrg Enrg Enrg Enrg Enrg

Func. - Default AL2 AL2 AL2 AL2 AL2 AL2 AL2

Item 1 AL1 AL1 AL1 AL1 AL1 AL1 AL1

Item 2 AL2 AL2 AL2 AL2 AL2 AL2 AL2


Set Relays
Item 3 Inhb Inhb Inhb Inhb Inhb Inhb Inhb
Relay 2

Item 4 Flt Flt Flt Flt Flt Flt Flt

Oper. - Default dEEn dEEn dEEn dEEn dEEn dEEn dEEn

Item 1 dEEn dEEn dEEn dEEn dEEn dEEn dEEn

Item 2 Enrg Enrg Enrg Enrg Enrg Enrg Enrg

Func. - Default Flt Flt Flt Flt Flt Flt Flt

Item 1 AL1 AL1 AL1 AL1 AL1 AL1 AL1

Item 2 AL2 AL2 AL2 AL2 AL2 AL2 AL2


Relay 3

Item 3 Inhb Inhb Inhb Inhb Inhb Inhb Inhb

Item 4 Flt Flt Flt Flt Flt Flt Flt

Oper. - Default Enrg Enrg Enrg Enrg Enrg Enrg Enrg

83
Sensepoint XCD Technical Manual SPXCDHMANEN Issue 15

CH4 - Propane Propane -


CH4 -IR
Menu Item Sub Item O2 CO H2S CAT -CAT IR
(Ir-3)
(cb-3) (cb-4) (Ir-4)

Item 1 dEEn dEEn dEEn dEEn dEEn dEEn dEEn

Item 2 Enrg Enrg Enrg Enrg Enrg Enrg Enrg

Default 0 0 0 0 0 0 0
On delay
Min 0 0 0 0 0 0 0

Max 180 180 180 180 180 180 180

Default 0 0 0 0 0 0 0
Off delay

Relay
Min 0 0 0 0 0 0 0
Operation

Max 300 300 300 300 300 300 300

Default no no no no no no no
Relay latch

Item 1 no no no no no no no

Item 2 yes yes yes yes yes yes yes

Default 000000000000
Set Location
Min/Max A string consisting of 12 ASCII characters.

Default On On On On On On On

Deadband Item 1 On On On On On On On

Item 2 Off Off Off Off Off Off Off

Default ℃ ℃ ℃ ℃ ℃ ℃ ℃
Set Item1 ℃ ℃ ℃ ℃ ℃ ℃ ℃
Temperature
Unit
Item2 ℉ ℉ ℉ ℉ ℉ ℉ ℉

84
Find out more
www.sps.honeywell.com

Contact Honeywell Analytics:

Europe, Middle East, Africa, India


Life Safety Distribution GmbH
Javastrasse 2
8604 Hegnau Switzerland
Tel: +41 (0)44 943 4300
Fax: +41 (0)44 943 4398
India Tel: +91 124 4752700
gasdetection@honeywell.com

Americas
Honeywell Analytics Inc.
405 Barclay Blvd.
Lincolnshire, IL 60069 USA
Tel: +1 847 955 8200
Toll free: +1 800 538 0363
Fax: +1 847 955 8210
detectgas@honeywell.com

Asia Pacific
Honeywell Co., Ltd.
5F SangAm IT Tower
434, Worldcup buk-ro, Mapo-gu
Seoul 03922, Republic of Korea
Tel: +82 (0) 2 6909 0300
analytics.ap@honeywell.com

Technical Services
EMEAI: HAexpert@honeywell.com
US: ha.us.service@honeywell.com
AP: ha.ap.service@honeywell.com

www.sps.honeywell.com

Issue 15 11/2023
3001M5001 SPXCDHMANEN
© 2023 Honeywell Analytics
12573

81

You might also like