30XA080-500
Air-Cooled Liquid Chillers
Installation Instructions
CONTENTS
SAFETY CONSIDERATIONS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-70
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 1 Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 Place, Mount and Rig Unit. . . . . . . . . . . . . 2
PLACING UNIT
MOUNTING UNIT
RIGGING UNIT
Step 3 Cooler Fluid and Drain Piping
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
GENERAL
UNITS WITH A HYDRONIC PUMP PACKAGE
UNITS WITHOUT A HYDRONIC PUMP PACKAGE
DUAL CHILLER CONTROL
COOLER FLUID, VENT, AND DRAIN
COOLER PUMP CONTROL
BRINE UNITS
WATER TREATMENT
PREPARATION FOR YEAR-ROUND OPERATION
Step 4 Fill the Chilled Water Loop . . . . . . . . . . . . 48
WATER SYSTEM CLEANING
WATER TREATMENT
SYSTEM PRESSURIZATION
FILLING THE SYSTEM
SET WATER FLOW RATE
PUMP MODIFICATION/TRIMMING
FREEZE PROTECTION
PREPARATION FOR WINTER SHUTDOWN
Step 5 Make Electrical Connections . . . . . . . . . . 54
POWER SUPPLY
FIELD POWER CONNECTIONS
POWER WIRING
FIELD CONTROL POWER CONNECTIONS
CARRIER COMFORT NETWORK
COMMUNICATION BUS WIRING
NON-CCN COMMUNICATION WIRING
FIELD CONTROL OPTION WIRING
DUAL CHILLER LEAVING WATER SENSOR
Step 6 Install Accessories . . . . . . . . . . . . . . . . . . . . 69
ENERGY MANAGEMENT MODULE
REMOTE ENHANCED DISPLAY
LOW AMBIENT TEMPERATURE OPERATION
MINIMUM LOAD ACCESSORY
UNIT SECURITY/PROTECTION ACCESSORIES
COMMUNICATION ACCESSORIES
SERVICE OPTIONS
CONTROL TRANSFORMER
Step 7 Leak Test Unit . . . . . . . . . . . . . . . . . . . . . . . . . 70
Step 8 Refrigerant Charging . . . . . . . . . . . . . . . . . . 70
DEHYDRATION
REFRIGERANT CHARGE
INTRODUCTION
These instructions cover installation of 30XA080-500 aircooled liquid chillers with electronic controls and units with
factory-installed options (FIOPs). See Fig. 1.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300008-01
Printed in U.S.A.
Form 30XA-5SI
Pg 1
9-06
Replaces: 30XA-1SI
Book 2
Tab 5c
INSTALLATION
Storage If the unit is to be stored for a period of time before installation or start-up, be sure to protect the machine
from construction dirt. Keep protective shipping covers in
place until the machine is ready for installation.
Step 1 Inspect Shipment Inspect unit for dam-
Packaging/Security Options
L Coil Face Shipping Protection (CFSP)
0 CFSP, Skid
1 Skid, Top Crate, Bag
3 CFSP, Coil Trim Panels
4 CFSP, Skid, Coil Trim Panels, Shipping
5 Skid, Top Crate, Bag, Coil Trim Panels
7 CFSP, Coil Trim Panels, Upper & Lower Grilles
8 CFSP, Skid, Coil Trim Panels, Upper & Lower Grilles
9 Skid, Top Crate, Bag, Coil Trim Panels, Upper & Lower Grilles
C CFSP, Trim Panels, Upper & Lower Grilles, Hail Guards
D CFSP, Skid, Coil Trim Panels, Upper & Lower Grilles, Hail Guards
F Skid, Top Crate, Bag, Trim Panels, Upper & Lower Grilles, Hail Guards
Design Series
Unit Sizes
080 140 240
090 160 260
100 180 280
110 200 300
120 220 325
350
400
450
500
Voltage
1 575-3-60
2 380-3-60
4 230-3-60
6 460-3-60
7 200-3-60
Controls/Communication Options
- Navigator Display
0 Navigator Display, EMM
1 Navigator Display, Service Option
2 Navigator Display, EMM, Service Option
3 Touch Pilot Display
4 Touch Pilot Display, EMM
5 Touch Pilot Display, Service Option
6 Touch Pilot Display, EMM, Service Option
7 Navigator Display, BACnet Translator
8 Navigator Display, BACnet Translator, EMM
9 Navigator Display, BACnet Translator, Service Option
B Navigator Display, BACnet Translator, EMM, Service Option
C Touch Pilot Display, BACnet Translator
D Touch Pilot Display, BACnet Translator, EMM
F Touch Pilot Display, BACnet Translator, Service Option
G Touch Pilot Display, BACnet Translator, EMM, Service Option
H Navigator Display, LON Translator
J Navigator Display, LON Translator, EMM
K Navigator Display, LON Translator, Service Option
L Navigator Display, LON Translator, EMM, Service Option
M Touch Pilot Display, LON Translator
N Touch Pilot Display, LON Translator, EMM
P Touch Pilot Display, LON Translator, Service Option
Q Touch Pilot Display, LON Translator, EMM, Service Option
Electrical Options
- Single Point Power, XL, Terminal Block, No Control Transformer
0 Single Point Power, Wye-Delta, Terminal Block, No Control Transformer
3 Dual Point Power, XL, Terminal Block, No Control Transformer
4 Dual Point Power, Wye-Delta, Terminal Block, No Control Transformer
7 Single Point Power, XL, Disconnect, No Control Transformer
8 Single Point Power, Wye-Delta, Disconnect, No Control Transformer
C Dual Point Power, XL, Disconnect, No Control Transformer
D Dual Point Power, Wye-Delta, Disconnect, No Control Transformer
H Single Point Power, XL, Terminal Block, Control Transformer
J Single Point Power, Wye-Delta, Terminal Block, Control Transformer
M Dual Point Power, XL, Terminal Block, Control Transformer
N Dual Point Power, Wye-Delta, Terminal Block, Control Transformer
R Single Point Power, XL, Disconnect, Control Transformer
S Single Point Power, Wye-Delta, Disconnect, Control Transformer
W Dual Point Power, XL, Disconnect, Control Transformer
X Dual Point Power, Wye-Delta, Disconnect, Control Transformer
Cooler/Brine Options
0 Integral Cooler
3 Integral Cooler, Minus One Pass
5 Integral Cooler, Plus One Pass
B Integral Cooler, Brine
F Integral Cooler, Minus One Pass, Brine
H Integral Cooler, Plus One Pass, Brine
EMM
LON
XL
a30-4401
LEGEND
Energy Management Module
Local Operating Network
Across-the-Line Starter
MOUNTING PLATE
0.875 DIA.[22.2]
MOUNTING HOLE
7.88
[200]
3.93
[100]
1.31
[33]
1.75
[44]
DETAIL "A"
5.0
[127]
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
109.0
[2769]
Cooler Tube
Service Area
5.83 [148]
26.5
[673]
65.73
[1670]
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict
Sides and Ends 6 ft from solid surface.
2. Temperature relief devices are located on liquid line and economizer assemblies and have 1/4-in. flare connection.
3. 3/8-in. NPT vents and drains located in each cooler head at each
end of cooler.
4. Drawing depicts unit with standard two-pass cooler. Refer to the
Packaged Chiller Builder program for other configurations.
5. Dimensions are shown in inches; dimensions in brackets are in
millimeters.
a30-4402
TOP VIEW
121.17
[3078]
141.22
[3587]
Piping Entrance
43.85
[1114]
68.06
[1729]
88.04
[2236]
22.2
[565]
41.1
[1044]
Display
Location
(380,460,575v)
Control Box
All Voltages
Optional Non-fused
Disconnect Handle
a30-4403
26.51
[673]
88.04
[2236]
Control
power entry
3.35
[85]
16.1
[409]
8.9
[226]
49.85
[1266]
90.55
[2300]
Display
Location
(200,230v)
FRONT VIEW
109.03
121.17 [2769]
[3078] 141.22
[3587]
90.55
[2300]
5" Victaulic
Entering Water
5" Victaulic
Leaving Water
19.06
10.8 [484]
[274]
19.06
[484] 10.8
[274]
Mounting Holes
Rigging Holes
(See Detail A)
Cooler Drain
3/8 NPT
Cooler Vent
3/8 NPT
53.92
[1370]
88.04
[2236]
68.06
[1729]
90.55
[2300]
MOUNTING
PLATE
7.88
[200]
3.93
[100]
1.31
[33]
1.75
[44]
DETAIL "A"
5.0
[127]
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
4.15
[105]
A
44.11 [1120]
44.11 [1120]
44.11 [1120]
44.11 [1120]
5.51 [140]
30XA UNIT
090
100
110
120
109.0
[2769]
Cooler Tube
Service Area
26.51
[673]
134.73
[3422]
B
86.93 [2208]
87.22 [2215]
87.62 [2226]
87.12 [2213]
188.2
[4780]
TOP VIEW
157.54
[4002]
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict
Sides and Ends 6 ft from solid surface.
2. Temperature relief devices are located on liquid line and economizer assemblies and have 1/4-in. flare connection.
3. 3/8-in. NPT vents and drains located in each cooler head at each end of cooler.
4. Drawing depicts unit with single-point power and standard two-pass cooler.
Refer to the Packaged Chiller Builder program for other configurations.
5. Dimensions are shown in inches; dimensions in brackets are in millimeters.
a30-4404
Piping
Entrance
85.56
[2173]
88.04
[2236]
88.28
[2242]
22.2
[565]
41.1
[1044]
Display
Location
(380,460,575v)
Control Box
All Voltages
Optional Non-fused
Disconnect Handle
a30-4405
26.51
[673]
88.04
[2236]
88.28
[2242]
Control
power entry
10.27
[261]
16.1
[409]
8.9
[226]
157.54
[4002]
78.02
[1982]
134.73
[3422]
78.02
[1982]
FRONT VIEW
188.2
[4780]
19.06
[484]
10.27
[261]
Drain
in
Mounting Holes
Rigging Holes
(See Detail A)
Cooler Drain
3/8 NPT
Cooler Vent
3/8 NPT
19.06
[484]
90.55
[2300]
49.85
[1266]
Display
Location
(200,230v)
85.56
[2173]
53.92
[1370]
85.56
[2173]
19.06
[484]
10.27
[261]
90.55
[2300]
88.28
[2242]
88.04
[2236]
90.55
[2300]
A
44.63 [1134]
44.61 [1133]
10.58
[269]
22.02
[559] 21.28
[541]
5" Victaulic
Leaving Water
5" Victaulic
Entering Water
30XA UNIT
140
160
89.36
[2270]
85.61
[2174]
Control Box
23.62
[600]
5.84 [148]
Display Location
109.0
[2769]
135.06
[3431]
TOP VIEW
235.24
[5975]
235.24
[5975]
BACK VIEW
163.87
[4162]
2.83 [72]
7.23 [182]
90.55
[2300]
Cooler Tube
Service Area
88.04
[2236]
B
115.88 [2943]
115.64 [2937]
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict
Sides and Ends 6 ft from solid surface.
2. Temperature relief devices are located on liquid line and economizer assemblies and have
1/ -in. flare connection.
4
3. 3/8-in. NPT vents and drains located in each
cooler head at each end of cooler.
4. Drawing depicts unit with standard condenser
fans, and standard two-pass cooler. Refer to
the Packaged Chiller Builder program for
other configurations.
5. Dimensions are shown in inches; dimensions
in brackets are in millimeters.
a30-4406
1.58
[2834]
74
[1880]
Control Box
(200/230V)
28.81
[732]
90.55
[2300]
89.36
[2270]
85.61
[2174]
88.04
[2236]
Piping Entrance
Non-fused
Disconnect Handle
for 380, 460, 575 v
Control Box
(all voltages)
Control Box
a30-4407
22.2
[565]
Control Box
(200,230,380,
460,575v)
41.1
[1044]
Optional Non-fused
Disconnect Handle
Control Box
(200,230v)
12.7
[3.23]
88.04
[2236] 89.36
[2270]
Mounting Holes
Rigging Holes
(See Detail A)
Cooler Drain
3/8 NPT
Cooler Vent
3/8 NPT
MOUNTING PL ATE
21.28
[541]
90.55
[2300]
Control Box
incoming power
supply (200,230v)
7.88
[200]
7.2
[182]
2.8 [72]
16.1
[409]
135.03
[3431]
3.93
[100]
1.31
[33]
1.75
[44]
163.87
[4162]
121.49
[3086]
33.96
[863]
out
DETAIL "A"
FRONT VIEW
235.24
[5975]
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
5.0
[127]
109.03
[2769]
42.8
[1087]
2.5
[63.5]
8.9
[226]
Drain
58.08
[1475]
21.28 22.02
[541] [559]
in
90.55
[2300]
10
A
46.12 [1171]
46.15 [1172]
22.48
[571]
11.3
[287]
6" Victaulic
Entering Water
6" Victaulic
Leaving Water
30XA UNIT
180
200
12.7
[323]
Cooler Tube
Service Area
70.16
[1782]
88.04
[2236]
B
143.04 [3633]
142.97 [3631]
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict
Sides and Ends 6 ft from solid surface.
2. Temperature relief devices are located on
liquid line and economizer assemblies and
have 1/4-in. flare connection.
3
3. /8-in. NPT vents and drains located in
each cooler head at each end of cooler.
4. Drawing depicts unit with standard condenser fans, and standard two-pass
cooler. Refer to the Packaged Chiller
Builder program for other configurations.
5. Dimensions are shown in inches; dimensions in brackets are in millimeters.
a30-4408
23.62
[600]
B
177.65
[4512]
BACK VIEW
282.2
[7168]
Control Box
(all voltages)
TOP VIEW
282.22
[7168]
Control Box
(380,460,575v)
90.55
[2300]
61.6
109.39 [1565]
[2779]
158.6
[4028]
120.73
[3067]
Optional Non-fused
Disconnect Handle
for 380, 400, 575v
Control Box
Display Location
70.16
[1782]
88.04
[2236]
Control Box
(200,230v incoming
power supply connection)
28.81
[732]
90.55
[2300]
Piping Entrance
22.2
[565]
41.1
[1044]
Optional Non-fused
Disconnect Handle
Control Box
(200,230v)
7/8" knockouts for
main power entry
(5.55" [141 mm]
hole spacing)
Control Box
(200,230,380,
460,575v)
a30-4174
11
12.7
[323]
88.04
[2236]
42.8
[1087]
2.5
[63.5]
7.88
[200]
18.7
[489]
58.08
[1475]
Cooler Drain
3/8 NPT
3.93
[100]
1.31
[33]
1.75
[44]
177.65
[4512]
DETAIL "A"
FRONT VIEW
282.22
[7168]
78.02
[1982]
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
5.0
[127]
33.97
[863]
MOUNTING PLATE
0.875 DIA.[22.2]
MOUNTING HOLE
Mounting Holes
Rigging Holes
(See Detail A)
90.55
[2300]
Control Box,
incoming Power
Supply (200,
230v)
Cooler Vent
3/8 NPT
78.02
[1982]
11.3
[287]
22.48
[571]
90.55
[2300]
12
22.48
[571]
11.3
[287]
70.16
[1782]
88.04
[2236]
12.7
[323]
B
171.42 [4354]
170.83 [4339]
A
46.17 [1173]
46.23 [1174]
6" Victaulic
Leaving Water
6" Victaulic
Entering Water
30XA UNIT
220
240
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict
Sides and Ends 6 ft from solid surface.
2. Temperature relief devices are located on liquid line and economizer assemblies and have
1/4-in. flare connection.
3. 3/8-in. NPT vents and drains located in each
cooler head at each end of cooler.
4. Drawing depicts unit with standard condenser
fans, and standard two-pass cooler. Refer to
the Packaged Chiller Builder program for other
configurations.
5. Dimensions are shown in inches; dimensions
in brackets are in millimeters.
a30-4409
224.65 [5706]
Control Box
(200,230,380,
460,575v)
BACK VIEW
329.26 [8363]
167.73 [4260]
70.16
[1782]
Optional Non-fused
Disconnect Handle
88.04
[2236]
Piping Entrance
Control Box
(200/230v only)
140.14 [3560]
Control Box
205.6 [5222]
Display Location
TOP VIEW
Incoming power
(200,230v)
329.26 [8363]
Control
Box
28.81 23.62
[732] [600]
90.55
[2300]
108.6 [2758]
Cooler Tube
Service Area
90.55
[2300]
Control
Boxes
a30-4176
13
88.04 [2236]
58.08 [1475]
Cooler Drain
3/8 NPT
18.07
[459]
7.88
[200]
3.93
[100]
1.31
[33]
1.75
[44]
224.65 [5706]
33.97 [863]
5.0
[127]
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
DETAIL "A"
FRONT VIEW
329.26 [8363]
109.03 [2769]
33.96 [863]
MOUNTING PLATE
0.875 DIA.[22.2]
MOUNTING HOLE
Mounting Holes
Rigging Holes
(See Detail A)
90.55
[2300]
Cooler Vent
3/8 NPT
58.08 [1475]
11.3
[287]
22.48
[571]
90.55
[2300]
14
23.63
[600]
12.21
[310]
8" Victaulic
Entering Water
8" Victaulic
Leaving Water
30XA UNIT
260
280
300
B
216.16 [5490]
215.86 [5483]
216.18 [5491]
88.04 [2236]
71.06 [1805]
A
44.22 [1123]
44.30 [1125]
44.32 [1126]
NOTES:
1. Unit must have clearances as
follows:
Top Do not restrict
Sides and Ends 6 ft from solid
surface.
2. Temperature relief devices are
located on liquid line and economizer assemblies and have 1/4-in.
flare connection.
3. 3/8-in. NPT vents and drains
located in each cooler head at
each end of cooler.
4. Drawing depicts unit with standard
condenser
fans
and
standard two-pass cooler. Refer
to the Packaged Chiller Builder
program for other configurations.
5. Dimensions are shown in inches;
dimensions in brackets are in
millimeters.
a30-4177
Control Box
Incoming power
(all voltages)
304.71 [7740]
Display Location
BACK VIEW
199.7 [5072]
245.52 [6236]
71.06
[1805] 88.04
[2236]
Piping Entrance
Optional Non-fused
Disconnect Handle
376.2 [9555]
TOP VIEW
376.2 [9555]
28.81 23.62
[732] [600]
90.55
[2300]
188.35 [4784]
B
Cooler Tube
Service Area
Control Box,
incoming power supply
90.55
[2300]
88.04 [2236]
Control Box
All Voltages
15.77 [401]
a30-4178
15
Mounting Holes
Rigging Holes
(See Detail A)
90.55
[2300]
0.875 DIA.[22.2]
MOUNTING HOLE
78.02 [1982]
7.88
[200]
376.2 [9555]
31.96 [812]
3.93
[100]
1.31
[33]
78.02 [1982]
5.0
[127]
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
DETAIL "A"
FRONT VIEW
1.75
[44]
304.71 [7740]
78.02 [1982]
MOUNTING PLATE
16.1
[409]
Cooler Drain
3/8 NPT
Cooler Vent
3/8 NPT
78.02 [1982]
12.21
[310]
23.63
[600]
90.55
[2300]
16
23.63
[600]
12.21
[310]
8" Victaulic
Entering Water
88.04 [2236]
71.06 [1805]
A
42.92 [1090]
42.92 [1090]
Control Box
90.55
[2300]
232.66 [5910]
B
BACK VIEW
246.7 [6267]
292.56 [7431]
Optional Non-fused
Disconnect Handle
Display Location
Control power entry
Control Box
423.24 [10750]
TOP VIEW
423.24 [10750]
349.02 [8865]
Cooler Tube
Service Area
28.81
23.62
[732] [600]
B
246.16 [6252]
246.72 [6267]
30XA UNIT
325
350
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict
Sides and Ends 6 ft from solid surface.
2. Temperature relief devices are located on
liquid line and economizer assemblies and
have 1/4-in. flare connection.
3. 3/8-in. NPT vents and drains located in each
cooler head at each end of cooler.
4. Drawing depicts unit with standard condenser fans and standard two-pass cooler.
Refer to the Packaged Chiller Builder program for other configurations.
5. Dimensions are shown in inches; dimensions in brackets are in millimeters.
8" Victaulic
Leaving Water
a30-4410
71.06
[1805]
88.04
[2236]
Piping Entrance
90.55
[2300]
Control Box
a30-4180
17
15.77 [401]
88.04 [2236]
90.55
[2300]
Mounting Holes
Rigging Holes
(See Detail A)
109.03
[2769]
7.88
[200]
33.96
[863]
3.93
[100]
1.31
[33]
1.75
[44]
78.02
[1982]
5.0
[127]
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
DETAIL "A"
FRONT VIEW
33.97
58.08 [1475]
[863]
349.02
[8865]
423.24
[10750]
MOUNTING PLATE
0.875 DIA.[22.2]
MOUNTING HOLE
16.1
[409]
Cooler Drain
3/8 NPT
Cooler Vent
3/8 NPT
78.02
[1982]
12.21
[310]
23.63
[600]
90.55
[2300]
18
17.92
[455]
8" Victaulic
Entering Water
88.04 [2236]
72.1 [1831]
Piping Entrance
Control Box #1
Circuit 1
BACK VIEW
470.22 [11944]
Optional Non-fused
Disconnect Handles
TOP VIEW
470.22 [11944]
Piping Entrance
53.29 [1354]
63.35 [1609]
119.07 [3024]
Circuit 2
70.02
[1779]
Cooler Tube
Service Area
105.7 [2684]
151.5 [3848]
28.81
[732]
Display Location
Control Box #2
240.69 [6114]
331.58 [8422]
378.95 [9625]
Control Box #2
23.62
[600]
Control Box #1
45.79
[1163]
72.1
88.04 [1831]
[2236]
Control
Box
90.55
[2300]
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict
Sides and Ends 6 ft from solid surface.
2. Temperature relief devices are located on liquid line and economizer assemblies and have
1/ -in. flare connection.
4
3. 3/8-in. NPT vents and drains located in each
cooler head at each end of cooler.
4. Drawing depicts unit with dual-point power
standard condenser fans and standard onepass cooler. Refer to the Packaged Chiller
Builder program for other configurations.
5. Actual cooler consists of two separate coolers
piped in series at the factory. Piping may be
split for rigging.
6. Dimensions are shown in inches; dimensions
in brackets are in millimeters.
a30-4181
90.55
[2300]
Control
Boxes
a30-4182
19
70.02 [1779]
88.04 [2236]
15.77 [401]
78.02 [1982]
78.02 [1982]
3.93
[100]
1.31
[33]
1.75
[44]
5.0
[127]
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
DETAIL "A"
FRONT VIEW
378.95 [9625]
470.22 [11944]
31.96
[812]
MOUNTING PLATE
7.88
[200]
16.1
78.02 [1982]
[409]
53.29 [1354]
17.92
[455]
0.875 DIA.[22.2]
MOUNTING HOLE
Mounting Holes
Rigging Holes
(See Detail A)
17.92
[455]
90.55
[2300]
78.02 [1982]
33.93
[862]
58.08 [1475]
17.92
[455]
90.55
[2300]
20
88.04 [2236]
73.0
88.04 [1854]
[2236]
Piping Entrance
Control
Boxes
90.55
[2300]
Control Box #1
Circuit 1
426.0 [10820]
BACK VIEW
517.26 [13138]
Circuit 2
Display Location
Control Box #2
83.62 [2124]
93.68 [2379]
129.1 [3279]
Cooler Tube
Service Area
152.7 [3879]
198.54 [5043]
Piping Entrance
378.62 [9617]
TOP VIEW
517.26 [13138]
Control Box #2
23.62
[600]
Control Box #1
B
264.7 [6723]
263.99 [6705]
73.0 [1854]
A
44.71 [1136]
44.78 [1137]
17.92
[455]
8" Victaulic
Entering Water
30XA UNIT
450
500
NOTES:
1. Unit must have clearances as follows:
Top Do not restrict
Sides and Ends 6 ft from solid surface.
2. Temperature relief devices are located on
liquid line and economizer assemblies and
have 1/4-in. flare connection.
3
3. /8-in. NPT vents and drains located in
each cooler head at each end of cooler.
4. Drawing depicts unit with dual-point power
standard condenser fans and standard
one-pass cooler. Refer to the Packaged
Chiller Builder program for other configurations.
5. Actual cooler consists of two separate
coolers piped in series at the factory. Piping may be split for rigging.
6. Dimensions are shown in inches; dimensions in brackets are in millimeters.
a30-4183
28.81
[732]
71.06
[1805]
90.55
[2300]
Control
Boxes
a30-4184
21
71.06 [1805]
88.04 [2236]
15.77 [401]
17.92
[455]
17.92
[455]
58.08
18.07
[1475]
[459]
83.62 [2124]
7.88
[200]
109.03
[2769]
58.08
[1475]
3.93
[100]
1.31
[33]
1.75
[44]
5.0
[127]
MOUNTING PLATE
CONTACT SURFACE
TYPICAL 4 PLACES
DETAIL "A"
FRONT VIEW
426.0 [10820]
517.26 [13138]
33.96
[863]
33.97
[863]
MOUNTING PLATE
33.97
[863]
0.875 DIA.[22.2]
MOUNTING HOLE
90.55
[2300]
Mounting Holes
Rigging Holes
(See Detail A)
78.02
[1982]
78.02
[1982]
17.92
[455]
90.55
[2300]
Total
13,748
13,897
15,720
15,878
16,141
M
742
745
N
742
745
Total
17,467
17,659
M
2152
1440
1457
N
991
1385
1401
O
1277
1216
1279
M
337
338
N
337
338
Total
7923
8010
M
976
653
661
N
450
628
635
O
579
551
580
P
868
876
863
Total
23,038
24,901
25,167
P
394
397
391
Total
10 450
11 295
11 416
Total
6236
6304
7130
7202
7322
Fig. 11A Unit Mounting Weights (Units with MCHX Condenser Coils)
22
30XA220-300
30XA080
COOLER SIDE
B
COOLER SIDE
D
C
a30-4419
a30-4423
J
K
H
I
COMPRESSOR SIDE
COMPRESSOR SIDE
30XA325-350
30XA090-120
COOLER SIDE
C
COOLER SIDE
E
D
C
a30-4424
a30-4420
E
COMPRESSOR SIDE
J
I
K
L
COMPRESSOR SIDE
30XA400-500
30XA140,160
COOLER SIDE
C
B
COOLER SIDE
E
D
C
a30-4425
a30-4421
COMPRESSOR SIDE
30XA180-200
E
L
M
N
COMPRESSOR SIDE
LEGEND
MCHX Micro-Channel Heat Exchanger
COOLER SIDE
C
a30-4422
COMPRESSOR SIDE
Fig. 11A Unit Mounting Weights (Units with MCHX Condenser Coils) (cont)
23
Total
11,726
11,958
30XA090-120
30XA140,160
COOLER SIDE
C
Total
5319
5424
COOLER SIDE
C
B
a30-4420
a30-4421
MCHX
E
COMPRESSOR SIDE
COMPRESSOR SIDE
LEGEND
Micro-Channel Heat Exchanger
Fig. 11A Unit Mounting Weights (Units with MCHX Condenser Coils) (cont)
24
Total
12,023
12,255
30XA090-120
30XA140,160
COOLER SIDE
C
Total
5454
5559
COOLER SIDE
C
B
a30-4420
a30-4421
MCHX
E
COMPRESSOR SIDE
COMPRESSOR SIDE
LEGEND
Micro-Channel Heat Exchanger
Fig. 11A Unit Mounting Weights (Units with MCHX Condenser Coils) (cont)
25
L
902
920
566
569
578
Total
14,727
14,887
16,853
17,022
17,362
L
1322
1326
M
856
860
N
856
860
Total
18,834
19,040
L
1342
1343
1348
M
2306
1556
1575
N
1069
1501
1519
O
1354
1293
1357
L
409
417
257
258
262
Total
6680
6753
7644
7721
7876
L
600
601
M
388
390
N
388
390
Total
8543
8636
L
609
609
611
M
1046
706
714
N
485
681
689
O
614
586
616
P
945
953
941
Total
24,578
26,600
26,894
P
428
432
427
Total
11 149
12 066
12 199
Fig. 11B Unit Mounting Weights (Units with Al/Cu Condenser Coils)
26
30XA220-300
30XA080
COOLER SIDE
B
COOLER SIDE
D
C
a30-4419
a30-4423
J
K
H
I
COMPRESSOR SIDE
COMPRESSOR SIDE
30XA325-350
30XA090-120
COOLER SIDE
C
COOLER SIDE
E
D
C
a30-4424
a30-4420
E
COMPRESSOR SIDE
J
I
K
L
COMPRESSOR SIDE
30XA400-500
30XA140,160
COOLER SIDE
C
B
COOLER SIDE
E
D
C
a30-4425
a30-4421
COMPRESSOR SIDE
L
M
N
COMPRESSOR SIDE
30XA180-200
E
COOLER SIDE
C
a30-4422
COMPRESSOR SIDE
Fig. 11B Unit Mounting Weights (Units with Al/Cu Condenser Coils) (cont)
27
A
1273
1299
1312
1346
A
2007
2061
H
1809
1862
Total
12,463
12,706
H
821
845
Total
5653
5763
A
578
589
595
611
A
910
935
30XA090-120
30XA140,160
COOLER SIDE
C
COOLER SIDE
C
B
a30-4420
a30-4421
E
COMPRESSOR SIDE
COMPRESSOR SIDE
Fig. 11B Unit Mounting Weights (Units with Al/Cu Condenser Coils) (cont)
28
A
1273
1299
1312
1346
A
2007
2061
H
1809
1862
Total
12,760
13,003
H
821
845
Total
5788
5898
A
578
589
595
611
A
910
935
30XA090-120
30XA140,160
COOLER SIDE
C
COOLER SIDE
C
B
a30-4420
a30-4421
E
COMPRESSOR SIDE
COMPRESSOR SIDE
Fig. 11B Unit Mounting Weights (Units with Al/Cu Condenser Coils) (cont)
29
L
1014
1032
679
682
699
Total
16,295
16,455
18,662
18,831
19,292
L
1443
1447
M
1037
1041
N
1037
1041
Total
21,005
21,211
L
1462
1464
1468
M
2547
1738
1756
N
1189
1682
1700
O
1474
1413
1477
L
460
468
308
309
317
Total
7391
7464
8465
8542
8751
L
655
656
M
470
472
N
470
472
Total
9528
9621
L
663
664
666
M
1155
788
797
N
539
763
771
O
669
641
670
P
1065
1073
1061
Total
26,990
29,254
29,547
P
483
487
481
Total
12 243
13 269
13 402
Fig. 11C Unit Mounting Weights (Units with Cu/CU Condenser Coils)
30
30XA220-300
30XA080
COOLER SIDE
B
COOLER SIDE
D
C
a30-4419
a30-4423
J
K
H
I
COMPRESSOR SIDE
COMPRESSOR SIDE
30XA325-350
30XA090-120
COOLER SIDE
C
COOLER SIDE
E
D
C
a30-4424
a30-4420
E
COMPRESSOR SIDE
J
I
K
L
COMPRESSOR SIDE
30XA400-500
30XA140,160
COOLER SIDE
C
B
COOLER SIDE
E
D
C
a30-4421
a30-4425
COMPRESSOR SIDE
L
M
N
COMPRESSOR SIDE
30XA180-200
E
COOLER SIDE
C
a30-4422
COMPRESSOR SIDE
Fig. 11C Unit Mounting Weights (Units with Cu/Cu Condenser Coils) (cont)
31
A
1394
1420
1433
1467
A
2188
2242
H
1990
2043
Total
13,669
13,912
H
903
927
Total
6200
6310
A
632
644
650
665
A
992
1017
30XA090-120
30XA140,160
COOLER SIDE
C
COOLER SIDE
C
B
a30-4420
a30-4421
E
COMPRESSOR SIDE
COMPRESSOR SIDE
Fig. 11C Unit Mounting Weights (Units with Cu/Cu Condenser Coils) (cont)
32
A
1394
1420
1433
1467
A
2188
2242
H
1990
2043
Total
13,966
14,209
H
903
927
Total
6335
6445
A
632
644
650
665
A
992
1017
30XA090-120
30XA140,160
COOLER SIDE
C
COOLER SIDE
C
B
a30-4420
a30-4421
E
COMPRESSOR SIDE
COMPRESSOR SIDE
Fig. 11C Unit Mounting Weights (Units with Cu/Cu Condenser Coils) (cont)
33
080
090
100
110
120
140
160
180
200
220
7,674
8,398
7,234
9,959
10,924
9,382
10,186
11,151
9,603
10,326
11,291
9,738
10,471
11,436
9,877
12,760
13,966
12,023
13,003
14,209
12,255
13,590
15,037
12,699
13,712
15,159
12,810
14,727
16,295
13,748
86/86/
60/60/
97/97/
62/62/
108/108/
73/73/
135/108/
100/73/
205/205/
141/141/
225/225/
161/161/
270/225/
179/161/
15
9
15
9
14
8
16.5
220
300
18.5
220
300
150
18.5
220
300
150
20.0
220
300
150
3/
15
10
11
7
(1) 06TT-301
(1) 06TT-301
N/A
6.25/6.25/
(1) 06TT-356
(1) 06TT-301
N/A
6.75/6.25/
11
8
15
10
15
10
14
10
27.5
220
300
150
31.5
220
300
34.0
220
300
37.0
220
300
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
5
2
5
1
4
3
5
2
5
1
4
3
5
2
5
1
4
3
5
2
5
1
4
3
5
2
5
1
4
3
5
2
5
1
5
3
5
2
5
1
5
3
6
2
8
1
6
3
6
2
8
1
6
3
6
2
8
1
6
3
CONDENSER FANS
Fan Speed (rpm) Standard/High Ambient**
No. Blades...Diameter (in.)
No. Fans (Ckt A/Ckt B/Ckt C)
Total Airflow (cfm) 850 rpm
Total Airflow (cfm) 1140 rpm
850/
9...30
3/3/
55,800
850/
9...30
4/4/
74,400
850/
9...30
4/4/
74,400
124,000
124,000
850/1140
9...30
6/6/
111,600
148,800
850/1140
9...30
6/6/
111,600
148,800
850/1140
9...30
7/6/
120,900
161,200
CONDENSER COILS
No. Coils (Ckt A/Ckt B/Ckt C)
Total Face Area (sq ft)
3/3/
141
4/4/
188
4/4/
188
4/4/
188
6/6/
281
6/6/
281
7/6/
305
N/A
UNIT 30XA
OPERATING WEIGHT (lb)
Al-Cu Condenser Coils
Cu-Cu Condenser Coils
MCHX Condenser Coils
REFRIGERANT TYPE
Refrigerant Charge (lb) Ckt A/Ckt B/Ckt C
Refrigerant Charge (lb) Ckt A/Ckt B/Ckt C (MCHX)
COMPRESSORS
Quantity
Speed (rpm)
(Qty) Compressor Model Number Ckt A
(Qty) Compressor Model Number Ckt B
(Qty) Compressor Model Number Ckt C
Oil Charge (gal), Ckt A/Ckt B/Ckt C
Minimum Capacity Step (%)
Standard
Optional
COOLER
Net Fluid Volume (gal.)
Maximum Refrigerant Pressure (psig)
Maximum Fluid Side Pressure Without Pumps (psig)
Maximum Fluid Side Pressure With Pumps (psig)
WATER CONNECTIONS
Drain (NPT, in.)
Standard, Inlet and Outlet, Victaulic (in.)
Number of Passes
Minus 1 Pass, Inlet and Outlet, Victaulic (in.)
Number of Passes
Plus 1 Pass, Inlet and Outlet, Victaulic (in.)
Number of Passes
CONDENSER FANS
Fan Speed (rpm) Standard/High Ambient
No. Blades...Diameter (in.)
No. Fans (Ckt A/Ckt B/Ckt C)
Total Airflow (cfm) 850 rpm
Total Airflow (cfm) 1140 rpm
CONDENSER COILS
No. Coils (Ckt A/Ckt B/Ckt C)
Total Face Area (sq ft)
11-10
15-9
6/4/
234
N/A
19-8
23-7
27-6
7-425/32
7-67/16
240
260
280
300
325
350
400
450
500
14,887
16,455
13,897
16,853
18,662
15,720
17,022
18,831
15,878
17,362
19,292
16,141
18,834
21,005
17,467
19,040
21,211
17,659
24,578
26,990
23,038
26,600
29,254
24,901
26,894
29,547
25,167
270/270/
193/193/
375/220/
247/156/
375/270/
260/193/
270/270/375
192/192/258
415/205/415
290/135/290
415/270/415
294/193/294
(1) 06TT-356
(1) 06TT-356
(1) 06TU-483
6.75/6.75/7.5
(1) 06TU-554
(1) 06TT-266
(1) 06TU-554
7.5/6.25/7.5
(1) 06TU-554
(1) 06TT-356
(1) 06TU-554
7.5/6.75/7.5
9
6
6
4
7
5
68.0
220
150
75.0
220
150
83.0
220
150
(1) 06TT-356
(1) 06TT-356
N/A
6.75/6.75/
(1) 06TU-483
(1) 06TT-301
N/A
7.5/6.75/
(1) 06TU-483
(1) 06TT-356
N/A
7.5/6.75/
15
10
11
8
13
9
39.0
220
300
42.0
220
300
44.0
220
300
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
6
2
8
1
6
3
8
2
8
1
8
3
8
2
8
1
8
3
8
2
8
1
8
3
8
2
8
1
8
3
8
2
8
1
8
3
8
1
8
1
8
1
850/1140
9...30
7/6/
120,900
161,200
850/1140
9...30
9/6/
139,500
186,000
850/1140
9...30
10/6/
148,800
198,400
850/1140
9...30
6/6/8
186,000
248,000
850/1140
9...30
8/6/8
204,600
272,800
850/1140
9...30
8/6/8
204,600
272,800
7/6/
305
9/6/
352
10/6/
375
6/6/8
469
8/6/8
516
8/6/8
516
12
7
15
10
15
10
9/9/
422
9/9/
422
N/A
27-6
31-5
35-4
39-3
43-2
7-43/4
7-67/16
LEGEND
Cu
Al
EXV
MCHX
N/A
6/4/
234
4/4/
188
Copper
Aluminum
Electronic Expansion Valve
Micro-channel Heat Exchanger
Not Applicable
34
080
090
100
110
120
140
160
180
200
220
3 481
3 809
3 281
4 517
4 955
4 255
4 620
5 058
4 356
4 684
5 122
4 417
4 750
5 187
4 480
5 788
6 335
5 454
5 898
6 445
5 559
6 164
6 821
5 760
6 220
6 876
5 811
6 680
7 391
6 236
39/39/
27.2/27.2/
44/44/
28.1/28.1/
49/49/
33.1/33.1/
102/61.2/
72.1/45.4/
93/93/
64.0/64.0/
(1) 06TS-137
(1) 06TS-137
N/A
20.8/20.8/
(1) 06TS-137
(1) 06TS-137
N/A
20.8/20.8/
15
9
15
9
102/102 122.5/102/
73.0/73.0/ 81.2/73.0/
14
8
15
10
11
7
11
8
15
10
15
10
14
10
104.1
1516.8
119.2
1516.8
128.7
1516.8
140.1
1516.8
2 068
62.5
1516.8
70.0
1516.8
70.0
1516.8
75.7
1516.8
2 068
2 068
2 068
2 068
2 068
2 068
2 068
2 068
2 068
1 034
1 034
1 034
1 034
1 034
1 034
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
5
2
5
1
4
3
5
2
5
1
4
3
5
2
5
1
4
3
5
2
5
1
4
3
5
2
5
1
4
3
5
2
5
1
5
3
5
2
5
1
5
3
6
2
8
1
6
3
6
2
8
1
6
3
6
2
8
1
6
3
CONDENSER FANS
Fan Speed (r/s) Standard/High Ambient**
No. Blades...Diameter (mm)
No. Fans (Ckt A/Ckt B/Ckt C)
Total Airflow (L/s) 14.2 r/s
Total Airflow (L/s) 19.0 r/s
14.2/
9...762
3/3/
26 335
14.2/
9...762
4/4/
35 113
14.2/
9...762
4/4/
35 113
58 522
58 522
14.2/19.0
9...762
6/6/
52 669
70 226
14.2/19.0
9...762
6/6/
52 669
70 226
14.2/19.0
9...762
7/6/
57 059
76 078
CONDENSER COILS
No. Coils (Ckt A/Ckt B/Ckt C)
Total Face Area (sq m)
3/3/
13
4/4/
17
4/4/
17
4/4/
17
6/6/
26
6/6/
26
7/6/
28
N/A
WATER CONNECTIONS
Drain (NPT, in.)
Standard, Inlet and Outlet, Victaulic (in.)
Number of Passes
Minus 1 Pass, Inlet and Outlet, Victaulic (in.)
Number of Passes
Plus 1 Pass, Inlet and Outlet, Victaulic (in.)
Number of Passes
UNIT 30XA
OPERATING WEIGHT (kg)
Al-Cu Condenser Coils
Cu-Cu Condenser Coils
MCHX Condenser Coils
REFRIGERANT TYPE
Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C
Refrigerant Charge (kg) Ckt A/Ckt B/Ckt C (MCHX)
COMPRESSORS
Quantity
Speed (r/s)
(Qty) Compressor Model Number Ckt A
(Qty) Compressor Model Number Ckt B
(Qty) Compressor Model Number Ckt C
Oil Charge (liter), Ckt A/Ckt B/Ckt C
Minimum Capacity Step (%)
Standard
Optional
COOLER
Net Fluid Volume (liters)
Maximum Refrigerant Pressure (kPa)
Maximum Fluid Side Pressure Without
Pumps (kPa)
Maximum Fluid Side Pressure With Pumps
WATER CONNECTIONS
Drain (NPT, in.)
Standard, Inlet and Outlet, Victaulic (in.)
Number of Passes
Minus 1 Pass, Inlet and Outlet, Victaulic (in.)
Number of Passes
Plus 1 Pass, Inlet and Outlet, Victaulic (in.)
Number of Passes
CONDENSER FANS
Fan Speed (r/s) Standard/High Ambient
No. Blades...Diameter (mm)
No. Fans (Ckt A/Ckt B/Ckt C)
Total Airflow (L/s) 14.2 r/s
Total Airflow (L/s) 19.0 r/s
CONDENSER COILS
No. Coils (Ckt A/Ckt B/Ckt C)
Total Face Area (sq m)
3 606
6/4/
22
4 800
N/A
5 994
7 188
8 382
2255
2296.9
240
260
280
300
325
350
400
450
500
6 753
7 464
6 304
7 644
8 465
7 130
7 721
8 542
7 202
7 876
8 751
7 322
8 543
9 528
7 923
8 636
9 621
8 010
11 149
12 243
10 450
12 066
13 269
11 295
12 199
13 402
11 416
(1) 06TT-356
(1) 06TT-356
N/A
25.6/25.6/
(1) 06TU-483
(1) 06TT-301
N/A
28.4/25.6/
(1) 06TU-483
(1) 06TT-356
N/A
28.4/25.6/
15
10
10
8
13
9
12
7
15
10
14
10
(1) 06TT-356
(1) 06TT-356
(1) 06TU-483
25.6/25.6/28.4
(1) 06TU-554
(1) 06TT-266
(1) 06TU-554
28.4/23.7/28.4
(1) 06TU-554
(1) 06TT-356
(1) 06TU-554
28.4/25.6/28.4
9
6
6
4
7
5
147.6
1516.8
159.0
1516.8
166.6
1516.8
257.4
1516.8
283.9
1516.8
314.2
1516.8
2 068
2 068
2 068
2 068
2 068
2 068
1 034
1 034
1 034
3/
3/
3/
3/
3/
3/
3/
3/
3/
6
2
8
1
6
3
8
2
8
1
8
3
8
2
8
1
8
3
14.2/19.0
9...762
7/6/
57 059
76 078
14.2/19.0
9...762
9/6/
65 837
87 782
14.2/19.0
9...762
10/6/
70 226
93 634
7/6/
28
9/6/
33
10/6/
35
8
2
8
1
8
3
8
2
8
1
8
3
8
2
8
1
8
3
9/9/
39
9/9/
39
8
1
8
1
8
1
14.2/19.0
9...762
6/6/8
87 782
117 043
14.2/19.0
9...762
8/6/8
96 561
128 747
14.2/19.0
9...762
8/6/8
96 561
128 747
6/6/8
44
8/6/8
48
8/6/8
48
N/A
8 382
9 576
10 770
2 255
2 300
LEGEND
Cu
Al
EXV
MCHX
N/A
6/4/
22
Pump(s) with pressure/temperature taps and combination valve. Single or Dual, 58.3 r/s
4/4/
17
11 964
13 158
Copper
Aluminum
Electronic Expansion Valve
Micro-channel Heat Exchanger
Not Applicable
35
9829
4466
8849
4021
4795
10553
9573
4350
10936
4969
9866
4483
5408
11901
10831
4922
11162
5072
10092
4586
5511
12127
11057
5024
5132
11293
10223
4645
5570
12258
11188
5084
5193
11427
10357
4706
5631
12392
11322
5145
6266
13788
12628
5739
6814
14994
13834
6287
6371
14018
5843
12858
6919
15225
6392
14065
7237
15925
6669
14675
7895
17372
7327
16122
7285
16030
6717
14780
7943
17477
7375
16227
SUBSTRACT THESE VALUES FOR UNITS W/O PUMPS
30XA080
30XA080-CU
30XA090
30XA090-CU
30XA100
30XA100-CU
30XA110
30XA110-CU
30XA120
30XA120-CU
30XA140
30XA140-CU
30XA160
30XA160-CU
30XA180
30XA180-CU
30XA200
30XA200-CU
30XA090-160
SINGLE PUMP
LBS
KGS
958
435
a30-4427
DUAL PUMP
LBS
KGS
1255
569
a30-4428
Step 3 Cooler Fluid and Drain Piping Connections See Fig. 15-18 for piping applications.
37
a30-4428
38
POWER
FD
FD
CONTROL
BALANCING VALVE/
SHUT OFF*
VIBRATION
ELIMINATORS*
STRAINER*
GATE VALVE*
PUMP
LEGEND
FD
Fused Disconnect
Airflow Through Condenser
Chilled Water Piping
Power Wiring
*Field-installed.
DRAIN
PRESSURE/
SHUTOFF TEMPERATURE TAPS*
VALVE
a30-4114
NOTES:
1. Chiller must be installed level to maintain proper compressor oil return.
2. Piping shown are general points-of-connection guides only and are not
intended for a specific installation. Wiring and piping shown are for a quick
overview of system and are not in accordance with recognized standards.
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System
Design Manual or appropriate ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers) handbook for details.
Fig. 15A 30XA Typical Piping and Wiring (Units without Hydronic Package)
AIRFLOW
FIELD-SUPPLIED
FUSED DISCONNECT
UNIT POWER
FIELD-SUPPLIED
FUSED DISCONNECT
CONTROL POWER
NOTES:
1. Chiller must be installed level to maintain proper
compressor oil return and hydraulics.
2. Wiring and piping shown are general points-ofconnection guides only and are not intended for a
specific installation. Wiring and piping shown are
for a quick overview of system and are not in
accordance with recognized standards.
3. All wiring must comply with applicable local and
national codes.
4. All piping must follow standard piping techniques.
Refer to Carrier System Design Manual or appropriate ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers)
handbook for details.
5. Air separator required as close to chiller as possible (except primary/secondary systems).
6. 20 mesh strainer required for open loop systems.
BALANCING VALVE/
SHUTOFF*
PRESSURE/
TEMPERATURE
TAPS*
VIBRATION
ELIMINATORS*
LEGEND
STRAINER*
Power Wiring
Chilled Water Piping
PUMP
*Field-installed.
Fig. 15B 30XA Typical Piping and Wiring (Units with Hydronic Package)
39
40
Distance to
Leaving
Water
Connection
(mm)
3077.8
3069.6
3069.6
3069.6
3069.6
3085.8
3085.8
4512.3
4502.4
5706.2
5706.2
7739.6
7739.6
7739.6
8865.1
8865.1
30XA
UNIT
SIZE*
080
090
100
110
120
140
160
180
200
220
240
260
280
300
325
350
SI
Leaving
W ater
Distance to Leaving
Water Connection
Distance to
Leaving/Entering
Water Connection
Distance to Entering
Water Connection
Cooler
Top View
Height Leaving
Water Connection
Height Entering
Water Connection
Coil
Side View
STANDARD COOLER
PLUS ONE PASS COOLER
MINUS ONE PASS COOLER
Distance to Distance to
Distance to Distance to
Distance to Distance to
Height
Height
Distance
to
Height
Height
Distance
to
Height
Height
Leaving/
Victaulic
Leaving/
Victaulic
Leaving/
Victaulic
Leaving
Entering
Entering
Leaving
Leaving
Entering
Entering
Leaving
Leaving
Entering
Entering
Entering
Connection
Entering
Connection
Entering
Connection
Water
Water
Water
Water
Water
Water
Water
Water
Water
Water
Water
Water
Size
Water
Size
Water
Size
Connection Connection Connection Connection
Connection Connection Connection Connection Connection
Connection Connection Connection Connection Connection
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
484.0
1728.7
3077.8
274.2
127.0
37.9
497.2
1728.7
3077.8
261.0
101.6
55.1
379.1
1728.7
3170.7
379.1
127.0
484.0
1728.7
3069.6
274.2
127.0
29.7
497.2
1728.7
3069.6
261.0
101.6
63.2
379.1
1728.7
3162.6
379.1
127.0
484.0
1728.7
3069.6
274.2
127.0
29.7
497.2
1728.7
3069.6
261.0
101.6
63.2
379.1
1728.7
3162.6
379.1
127.0
484.0
1728.7
3069.6
274.2
127.0
29.7
497.2
1728.7
3069.6
261.0
101.6
63.2
379.1
1728.7
3162.6
379.1
127.0
484.0
1728.7
3069.6
274.2
127.0
29.7
497.2
1728.7
3069.6
261.0
101.6
63.2
379.1
1728.7
3162.6
379.1
127.0
540.5
1756.2
3085.8
268.7
127.0
30.1
540.5
1756.2
3085.8
268.7
127.0
55.0
404.6
1756.2
3170.8
404.6
152.4
540.5
1756.2
3085.8
268.7
127.0
30.1
540.5
1756.2
3085.8
268.7
127.0
55.0
404.6
1756.2
3170.8
404.6
152.4
571.0
1782.1
4512.3
287.0
152.4
1361.4
569.5
1782.1
4587.2
288.5
152.4
1361.4
336.0
1782.1
4587.2
336.0
203.2
571.0
1782.1
4502.4
287.0
152.4
1351.6
569.5
1782.1
4577.4
288.5
152.4
1351.6
336.0
1782.1
4577.4
336.0
203.2
571.0
1782.1
5706.2
287.0
152.4
2555.3
569.5
1782.1
5781.1
288.5
152.4
2555.3
336.0
1782.1
5781.1
336.0
203.2
571.0
1782.1
5706.2
287.0
152.4
2555.3
569.5
1782.1
5781.1
288.5
152.4
2555.3
336.0
1782.1
5781.1
336.0
203.2
600.2
1804.9
7739.6
310.1
203.2
4580.8
593.9
1804.9
7882.8
316.5
203.2
4580.8
413.3
1804.9
7882.8
413.3
203.2
600.2
1804.9
7739.6
310.1
203.2
4580.8
593.9
1804.9
7882.8
316.5
203.2
4580.8
413.3
1804.9
7882.8
413.3
203.2
600.2
1804.9
7739.6
310.1
203.2
4580.8
593.9
1804.9
7882.8
316.5
203.2
4580.8
413.3
1804.9
7882.8
413.3
203.2
600.2
1804.9
8865.1
310.1
203.2
5706.4
593.9
1804.9
9008.4
316.5
203.2
5706.4
413.3
1804.9
9008.4
413.3
203.2
600.2
1804.9
8865.1
310.1
203.2
5706.4
593.9
1804.9
9008.4
316.5
203.2
5706.4
413.3
1804.9
9008.4
413.3
203.2
*30XA400-500 units are equipped with standard coolers only. Refer to unit dimensional drawings for cooler dimensions.
NOTE: Refer to dimensional drawings for all other unit dimensions.
121.2
120.9
120.9
120.9
120.9
121.5
121.5
177.7
177.3
224.7
224.7
304.7
304.7
304.7
349.0
349.0
080
090
100
110
120
140
160
180
200
220
240
260
280
300
325
350
30XA Distance to
Leaving
UNIT
Water
SIZE*
Connection
(in.)
ENGLISH
STANDARD COOLER
PLUS ONE PASS COOLER
MINUS ONE PASS COOLER
Distance to Distance to
Distance to
Distance
Distance to Distance to
Height
Height
Distance to
Height
Height
Distance to
Height
Height
Leaving/
Victaulic
Leaving/
to
Victaulic
Leaving/
Victaulic
Leaving
Entering
Entering
Leaving
Leaving
Entering
Leaving
Leaving
Entering
Entering
Entering
Connection
Entering
Entering
Connection
Entering
Connection
Water
Water
Water
Water
Water
Water
Water
Water
Water
Water
Water
Size
Water
Water
Size
Water
Size
Connection Connection Connection Connection
Connection Connection Connection Connection Connection
Connection Connection Connection Connection Connection
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
(in.)
19.1
68.1
121.2
10.8
5.0
1.5
19.6
68.1
121.2
10.3
4.0
2.2
14.9
68.1
124.8
14.9
5.0
19.1
68.1
120.9
10.8
5.0
1.2
19.6
68.1
120.9
10.3
4.0
2.5
14.9
68.1
124.5
14.9
5.0
19.1
68.1
120.9
10.8
5.0
1.2
19.6
68.1
120.9
10.3
4.0
2.5
14.9
68.1
124.5
14.9
5.0
19.1
68.1
120.9
10.8
5.0
1.2
19.6
68.1
120.9
10.3
4.0
2.5
14.9
68.1
124.5
14.9
5.0
19.1
68.1
120.9
10.8
5.0
1.2
19.6
68.1
120.9
10.3
4.0
2.5
14.9
68.1
124.5
14.9
5.0
21.3
69.1
121.5
10.6
5.0
1.2
21.3
69.1
121.5
10.6
5.0
2.2
15.9
69.1
124.8
15.9
6.0
21.3
69.1
121.5
10.6
5.0
1.2
21.3
69.1
121.5
10.6
5.0
2.2
15.9
69.1
124.8
15.9
6.0
22.5
70.2
177.7
11.3
6.0
53.6
22.4
70.2
180.6
11.4
6.0
53.6
13.2
70.2
180.6
13.2
8.0
22.5
70.2
177.3
11.3
6.0
53.2
22.4
70.2
180.2
11.4
6.0
53.2
13.2
70.2
180.2
13.2
8.0
22.5
70.2
224.7
11.3
6.0
100.6
22.4
70.2
227.6
11.4
6.0
100.6
13.2
70.2
227.6
13.2
8.0
22.5
70.2
224.7
11.3
6.0
100.6
22.4
70.2
227.6
11.4
6.0
100.6
13.2
70.2
227.6
13.2
8.0
23.6
71.1
304.7
12.2
8.0
180.3
23.4
71.1
310.3
12.5
8.0
180.3
16.3
71.1
310.3
16.3
8.0
23.6
71.1
304.7
12.2
8.0
180.3
23.4
71.1
310.3
12.5
8.0
180.3
16.3
71.1
310.3
16.3
8.0
23.6
71.1
304.7
12.2
8.0
180.3
23.4
71.1
310.3
12.5
8.0
180.3
16.3
71.1
310.3
16.3
8.0
23.6
71.1
349.0
12.2
8.0
224.7
23.4
71.1
354.7
12.5
8.0
224.7
16.3
71.1
354.7
16.3
8.0
23.6
71.1
349.0
12.2
8.0
224.7
23.4
71.1
354.7
12.5
8.0
224.7
16.3
71.1
354.7
16.3
8.0
a30-4413
CONTROL
BOX
MASTER CHILLER
OR ISOLATION VALVE
CONTROL
BOX
SLAVE CHILLER
LWT
OR ISOLATION VALVE
DUAL CHILLER
LWT SENSORS
& WELLS
LEGEND
Leaving Water Temperature
Field-Installed Communication Bus (slashes
indicate number of conductor wires)
Field-Installed Wiring
Twisted Pair
a30-4417
CONTROL
BOX
SLAVE CHILLER
PUMP
CONTROL
BOX
MASTER CHILLER
LEGEND
Field-Installed Communication Bus (slashes
indicate number of conductor wires)
Field-Installed Wiring
a30-4418
41
a30-4138
FLOW SWITCH
T1 PP
Heater
FS PP T2
PT
INSIDE
UNIT
PT
D
PT
OUTSIDE
UNIT
Chilled
Water Out
PT
PT
Heater
D
D
E
FS
PP
PT
T1
T2
V
LEGEND
Drain,3/4-in. NPT
Drain, 1/4-in. NPT
Expansion Tank Connection, 3/4-in. NPT
Flow Switch
Pipe Plug, 1/4-in. NPT
Pressure/Temperature Tap
Leaving Water Thermistor
Entering Water Thermistor
Vent, 1/4-in. NPT
Indicates items provided with the
optional hydronic pump package.
Chilled
Water In
Strainer/Suction Guide
Pump
Combination Valve
Pressure Relief*
Isolation Valve*
Flexible Connections*
a30-4414
Pressure Reducing
Fill Valve*
20 Mesh Stainer**
Fig. 20 Typical Piping Diagram on 30XA Units with Hydronic Package Single Pump
42
T1 PP
Heater
FS PP T2
PT HYDRONIC PUMP PACKAGE
D
PT
D
PT
INSIDE
UNIT
OUTSIDE
UNIT
Chilled
Water Out
PT
PT
D
Heater
D
D
E
FS
PP
PT
T1
T2
V
LEGEND
Drain,3/4-in. NPT
Drain, 1/4-in. NPT
Expansion Tank Connection, 3/4-in. NPT
Flow Switch
Pipe Plug, 1/4-in. NPT
Pressure/Temperature Tap
Leaving Water Thermistor
Entering Water Thermistor
Vent, 1/4-in. NPT
Chilled
Water In
Strainer/Suction Guide
Service Valve
Pump
Combination Valve
Pressure Relief*
a30-4415
Flexible Connections*
Isolation Valve*
Pressure Reducing
Fill Valve*
20 Mesh Stainer**
Fig. 21 Typical Piping Diagram on 30XA Units with Hydronic Package Dual Pumps
volume should be increased to 6 to 10 gallons per ton (6.46 to
10.76 liters per kW) of cooling. In order to achieve this
volume, it may be necessary to add a water storage tank to the
water loop. If a storage tank is added to the system, it should be
properly vented so that the tank can be completely filled and all
air eliminated. Failure to do so could cause lack of pump stability and poor system operation. Any storage tank that is placed
in the water loop should have internal baffles to allow thorough
mixing of the fluid. See Fig. 23.
System Piping Proper system design and installation procedures should be followed closely. The system must be
constructed with pressure tight components and thoroughly
tested for installation leaks. Factory-supplied hydronic systems
are available with single or dual (for back-up) pumps. The
factory-installed system includes all of the components above
the line in Fig. 20 and 21.
Installation of water systems should follow sound engineering practice as well as applicable local and industry standards.
Improperly designed or installed systems may cause unsatisfactory operation and/or system failure. Consult a water
treatment specialist or appropriate literature for information
regarding filtration, water treatment, and control devices. Figures 20 and 21 show a typical installation with components that
might be installed with the hydronic package of the 30XA unit.
NOTE: It is recommended for units with the hydronic package
that an inlet isolation (shut-off) valve be placed exterior to the
unit to allow removal and service of the entire pump assembly,
if necessary. The hydronic package is supplied from the factory
GOOD
BAD
BAD
a30-3185
GOOD
T1 PP
Chilled Water Out
Heater
D
FS
PP
T1
T2
V
Chilled Water In
LEGEND
Drain, 3/4-in. NPT
Flow Switch
Pipe Plug, 1/4-in. NPT
Leaving Water Thermistor
Entering Water Thermistor
Vent, 1/4-in. NPT
a30-4416
FS PP T2
090
100
110
120
140
160
180
200
220
240
260
280
300
325
350
400
450
500
Cooler
Number of
Passes
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
Standard
Plus one pass
Minus one pass
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
1
MINIMUM
40 F (4.4 C)
45 F (7.2 C)
Minimum Flow Rate
(gpm)
(L/s)
95
6.0
43
2.7
196
12.4
101
6.4
43
2.7
229
14.4
101
6.4
43
2.7
229
14.4
125
7.9
61
3.8
254
16.0
125
7.9
73
4.6
281
17.7
134
8.5
73
4.6
324
20.4
165
10.4
98
6.2
354
22.3
202
12.7
73
4.6
416
26.2
223
14.1
98
6.2
458
28.9
235
14.8
122
7.7
501
31.6
266
16.8
147
9.3
538
33.9
257
16.2
141
8.9
584
36.8
293
18.5
141
8.9
620
39.1
327
20.6
174
11.0
687
43.3
361
22.8
211
13.3
724
45.7
379
23.9
244
15.4
767
48.4
501
31.6
501
501
* For applications requiring cooler leaving water temperature operation at less than
40 F (4.4 C), the units require the use of antifreeze and application may require
one of the special order brine option. Contact your local Carrier representative for
more information.
For applications requiring cooler entering water temperature operation at less than
45 F (7.2 C), contact your local Carrier representative for unit selection using the
Carrier electronic catalog.
MAXIMUM
60 F (15 C)
70 F (21.1 C)
Maximum Flow Rate
(gpm)
(L/s)
379
23.9
192
12.1
782
49.3
403
25.4
200
12.6
917
57.9
403
25.4
200
12.6
917
57.9
501
31.6
244
15.4
1014
64.0
501
31.6
293
18.5
1124
70.9
538
33.9
293
18.5
1296
81.8
660
41.6
391
24.7
1418
89.5
807
50.9
391
24.7
1662
104.9
892
56.3
391
24.7
1833
115.6
941
59.4
489
30.9
2004
126.4
1063
67.1
587
37.0
2151
135.7
1027
64.8
562
35.5
2334
147.3
1173
74.0
562
35.5
2481
156.5
1308
82.5
697
44.0
2750
173.5
1442
91.0
843
53.2
2897
182.8
1516
95.6
978
61.7
3068
193.6
2004
126.4
2004
2004
NOMINAL
11.4
201.9
12.7
225.5
14.2
244.9
15.5
264.8
16.7
317.8
20.1
365.1
23.0
409.6
25.8
463.9
29.3
505.9
31.9
545.8
34.4
600.3
37.9
642.2
40.5
687.5
43.4
733.4
46.3
775.4
48.9
917.6
57.9
1019.3
64.3
1092.8
68.9
NOTE: Nominal flow rates required at ARI (Air Conditioning and Refrigeration
Institute) conditions 44 F (7 C) leaving fluid temperature, 54 F (12 C) entering
water temperature, 95 F (35 C) ambient. Fouling factor 0.00010 ft2-hr-F/Btu
(0.000018 m2-K/kW).
45
Expansion
Tank(s)
Zone 2
Zone 1
Chiller 2
Chiller 1
Decoupler
Zone 3
a30-4002
Distribution Pump
Air Separator
with Vent
NOTE: Expansion tanks for 30XA hydronic kits must be installed for chillers piped in parallel in the primary water loop.
Fig. 24 Typical Air Separator and Expansion Tank Location on Primary-Secondary Systems
PREPARATION FOR YEAR-ROUND OPERATION In
areas where the piping or unit is exposed to 32 F (0 C) or
lower ambient temperatures, freeze-up protection is required
using inhibited glycol or other suitable corrosion-resistant antifreeze solution and electric heater tapes. Heater tapes on piping
should have a rating for area ambient temperatures and be covered with a suitable thickness of closed-cell insulation. Route
power for the heater tapes from a separately fused disconnect.
Mount the disconnect within sight from the unit per local or
NEC (National Electric Code) codes. Identify disconnect at
heater tape power source with a warning that power must not
be turned off except when servicing unit.
a30-3432
46
To avoid damage to the refrigerant coils and electrical components, use extreme care when drilling screw holes and
screwing in fasteners.
Mount the smaller height baffle on units with a control box
located on the end of the unit. It is recommended that the upper
notches be used for mounting the baffles. This reduces the risk
of damaging the coil while drilling a mounting hole. Loosen
the upper corner post bolts and slide the baffle under the bolt
and washer. Tighten the bolt. Drill holes in the bottom of the
flange of the baffle and mount with two screws to secure the
bottom of the baffle to the corner post. Repeat the process for
the opposite end. See Fig. 26.
To avoid possibility of electrical shock, open all disconnects before installing or servicing this accessory.
305 [12.0]
See Detail A
1880 [74.0]
180 [7.0]
POSITION
30XA080-120
(Facing the control box end)
30XA140-500
(Facing the control box end)
1040 [41.0]
635 [25.0]
1040 [41.0]
1040 [41.0]
18 [0.75]
NOTES:
1. Material: 18 ga. Corrosion Resistant Sheet Metal.
2. Dimensions are in mm [inches].
18 [0.75]
70 [2.75]
31 [1.25]
21 [0.88]
Detail A
Typical Both Flanges
47
a30-3997
SYSTEM
SIDE
STREAM
FILTER
The chilled water pump (if equipped) is rated for 150 psig
(1034 kPa) duty. The maximum cooler fluidside pressure is
300 psig (2068 kPa). Check the pressure rating for all of the
chilled water devices installed. Do not exceed the lowest pressure rated device.
WATER SYSTEM CLEANING Proper water system
cleaning is of vital importance. Excessive particulates in the
water system can cause excessive pump seal wear, reduce or
stop flow, and cause damage of other components.
1. Install a temporary bypass around the chiller to avoid
circulating dirty water and particulates into the pump
package and chiller during the flush. Use a temporary
circulating pump during the cleaning process. Also, be
sure that there is capability to fully drain the system after
cleaning. See Fig. 27.
2. Be sure to use a cleaning agent that is compatible with
all system materials. Be especially careful if the system
contains any galvanized or aluminum components. Both
detergent-dispersant and alkaline-dispersant cleaning
agents are available.
3. It is recommended to fill the system through a water
meter. This provides a reference point for the future for
loop volume readings, and it also establishes the correct
quantity of cleaner needed in order to reach the required
concentration.
4. Use a feeder/transfer pump to mix the solution and fill the
system. Circulate the cleaning system for the length of
time recommended by the cleaning agent manufacturer.
a. After cleaning, drain the cleaning fluid and flush the
system with fresh water.
b. A slight amount of cleaning residue in the system can
help keep the desired, slightly alkaline, water pH of 8
to 9. Avoid a pH greater than 10, since this will
adversely affect pump seal components.
c. A side stream filter is recommended (see Fig. 28 during the cleaning process. Filter side flow rate should
be enough to filter the entire water volume every 3 to
4 hours. Change filters as often as necessary during
the cleaning process.
d. Remove temporary bypass when cleaning is complete.
A suction guide with an internal strainer is standard on all
30XA units with factory-installed hydronic packages. This
strainer allows removal of particulates from the chilled
water loop. Using the combination valve and the field-installed
isolation valve at the inlet, the strainer can be isolated from the
chilled water loop to be cleaned.
a30-4412
TO DRAIN
The Carrier ComfortLink controls provided have a builtin feature to remind building owners or operators to clean the
strainer at a pre-set time interval. Properly installed, cleaned
and maintained systems will rarely need the strainer cleaned
after the initial fill. This time interval is user-configurable.
Ideally, the chilled water loop will be cleaned before the unit
is connected. If the run-in screen is left in the suction guide/
strainer, it is recommended that the Service Maintenance be set
to alert the operator within 24 hours of start-up to be sure that
the run-in screen in the suction guide/strainer is removed after
24 hours of operation.
NOTE: The suction guide/strainer must be removed after the
first 24 hours of operation.
To set the time for the parameter, go to Time Clock/MCFG/
W.FIL in the handheld Navigator display. To set the time for
the parameter with the Touch Pilot display, go to Main
Menu/Service/MAINTCFG/wfilter_c. Values for this item are
input in days.
WATER TREATMENT Fill the fluid loop with water (or
brine) and a corrosion-resistant inhibitor suitable for the water
of the area. Consult the local water treatment specialist for
characteristics of system water and a recommended inhibitor
for the cooler fluid loop.
SYSTEM PRESSURIZATION A proper initial cold fill
pressure must be established before filling of the unit. The
initial cold fill pressure is the pressure applied at the filling
point to fill a system to its highest point, plus a minimum
pressure at the top of the system (4 psig minimum [27.6 kPa])
to operate air vents and positively pressurize the system. The
expansion tank is very important to system pressurization. The
expansion tank serves several purposes:
1. Provide NPSHR (Net Positive Suction Head Required)
for the pump to operate satisfactorily.
2. Set system pressure.
3. Accommodate expansion/contraction of water due to
temperature changes.
4. Acts as a pressure reference for the pump.
The expansion tank pressure must be set BEFORE the
system is filled. Follow the manufacturers recommendation
for instructions on setting the pressure in the expansion tank.
NPSHR information is provided on the Pump Curves in
Fig. 29-32 for units with factory-installed hydronic kits. See
Table 4 for pump impeller sizes.
Once the system is pressurized, the pressure at the connection point of the expansion tank to water piping will not change
unless the water loop volume changes (either due to addition/
subtraction of water or temperature expansion/contraction).
The pressure at this point remains the same regardless of
whether or not the pump is running.
30XA UNIT
TO DRAIN
TEMPORARY
BYPASS
a30-4411
30XA UNIT
TEMPORARY
PUMP
TEMPORARY
PUMP
SYSTEM
DILUTED
CLEANING
AGENT
DILUTED
CLEANING
AGENT
TEMPORARY
BYPASS
48
SINGLE/DUAL PUMP
FTV-5 in.
PUMP
Hp
Option Code*
090-160
5
7.5
10
15
1
2
3
4
SINGLE PUMP
Impeller Dia.
Rpm
(in.)
3450
4.5
3450
5
3450
5.4
3450
6.1
Pump Curve
Option Code*
I
I
I
I
7
8
B
C
DUAL PUMP
Impeller Dia.
Rpm
(in.)
3450
4.5
3450
5
3450
5.4
3450
6.1
*Option Code refers to the Hydronics Option (position 11) in the model number. See Fig. 1 for option identification.
49
Pump Curve
II
II
II
II
30XA140
30XA090,100
160
140
160
120
100
80
60
40
20
0
0
100
200
300
400
140
120
3
100
80
60
40
20
0
500
GPM
100
300
400
500
400
500
GPM
a30-4431
a30-4434
30XA160
30XA110
160
160
140
200
120
100
80
2
1
60
40
20
0
0
100
200
300
400
140
120
3
100
80
60
40
20
0
500
GPM
100
200
300
GPM
a30-4432
a30-4435
30XA120
Selection
1
2
3
4
160
140
120
100
80
2
1
60
40
20
0
0
100
200
300
400
500
GPM
a30-4433
50
Pump
Single 5HP
Single 7.5HP
Single 10HP
Single 15HP
30XA140
30XA090,100
160
160
140
C
Available Head (Feet )
140
120
100
80
60
40
120
B
100
80
60
40
20
20
0
0
100
200
300
400
500
100
200
a30-4436
500
30XA160
160
160
C
140
Available Head (Feet )
140
120
100
80
60
40
120
B
100
80
60
40
20
20
0
0
100
200
300
400
500
100
200
300
GPM
GPM
a30-4437
a30-4440
30XA120
Selection
7
8
B
C
160
140
Available Head (Feet )
400
a30-4439
30XA110
300
GPM
GPM
120
B
100
80
60
40
20
0
0
100
200
300
400
500
GPM
a30-4438
51
Pump
Dual 5HP
Dual 7.5HP
Dual 10HP
Dual 15HP
400
500
Head Pressure
(m) ft of Fluid
3450 RPM
39
52
62
70
5.75 in
74
77
77
77
5.25 in
74
5.00 in
70
(27.4) 90 4.75 in
62
4.50 in
20 hp
(18.3) 60
15 hp
52%
10 hp
(9.1) 30
N
P
S
H
r
(0.0) 0
a30-4441
0
0.00
7.5 hp
5 hp
3 hp
NPSHr
100
6.31
200
12.62
300
18.93
Flow Rate
400
25.24
500
31.54
(gpm)
(l/s)
LEGEND
NPSHr Net Positive Suction Head (Pressure) Required
NOTE: Refer to Fig. 1 for option identification. Refer to Table 4 for more information.
Fig. 31 Pump Curve I for Hydronic Package Single Pump (Fresh Water)
Head Pressure
(m) ft of Fluid
3450 RPM
39
52
62
70
5.75 in
74
77
77
5.25 in
77
74
5.00 in
70
(27.4) 90 4.75 in
62
4.50 in
20 hp
(18.3) 60
15 hp
52%
10 hp
(9.1) 30
N
P
S
H
r
(0.0) 0
a30-4442
0
0.00
7.5 hp
5 hp
3 hp
NPSHr
100
6.31
200
12.62
300
18.93
400
25.24
500
31.54
Flow Rate
LEGEND
NPSHr Net Positive Suction Head (Pressure) Required
NOTE: Refer to Fig. 1 for option identification. Refer to Table 4 for more information.
Fig. 32 Pump Curve II for Hydronic Package Dual Pump (Fresh Water)
52
(gpm)
(l/s)
1. If the unit has optional heater tapes on the cooler and the
cooler will not be drained, do not shut off power disconnect during off-season shutdown. If the unit has optional
heater tapes on the cooler and the cooler is drained, open
the circuit breaker for the heater, CB-13 or shut off power
during off-season shutdown.
2. Draining the fluid from the system is highly recommended. If the unit is equipped with a hydronic package, there
are additional drains in the pump housing and strainer
that must be opened to allow for all for all of the water to
drain.
3. Isolate the cooler from the rest of the system with water
shutoff valves.
4. Replace the drain plug and completely fill the cooler with
a mixture of water and a suitable corrosion-inhibited antifreeze solution such as propylene glycol. The concentration should be adequate to provide freeze protection to
15 F (8.3 C) below the expected low ambient temperature conditions. Anti-freeze can be added through the
vent on top of the cooler. If the unit has a hydronic pump
package, the pump must be treated in the same manner.
5. Leave the cooler filled with the antifreeze solution for the
winter, or drain if desired. Be sure to deenergize heaters
(if installed) as explained in Step 1 to prevent damage.
Use an approved method of disposal when removing antifreeze solution.
At the beginning of the next cooling season, be sure that
there is refrigerant pressure on each circuit before refilling
cooler, add recommended inhibitor, and reset the CB-HT (circuit breaker heater) (if opened) or restore power.
53
Maximum wire size that the unit terminal block or nonfused disconnect will accept is 500 kcmil.
POWER WIRING All power wiring must comply with applicable local and national codes. Install field-supplied branch
circuit fused disconnect per NEC of a type that can be locked
OFF or OPEN. Disconnect must be within sight and readily accessible from the unit in compliance with NEC Article 440-14.
In the power box, 7/8 in. holes are provided for power entry.
The holes will need to bee enlarged to accept the appropriate
conduit. NEC also requires all conduits from a conditioned
space to the power box(es) be sealed to prevent airflow and
moisture into the control box.
54
a30-4443
55
Fig. 33 Control and Power Wiring Schematic
Table 5 30XA080-350* Electrical Data, Single Point (Standard Condenser Fan Motors)
UNIT
30XA
080
090
100
110
120
140
160
180
200
220
240
260
280
300
325
350
UNIT VOLTAGE
Supplied
V-Hz
(3 Ph)
NUMBER
OF
COND
Min Max
REQD
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
6
6
6
6
6
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
10
10
10
10
10
10
10
10
10
10
12
12
12
12
12
12
12
12
12
12
13
13
13
13
13
13
13
13
13
13
15
15
15
16
16
16
16
16
16
18
18
18
18
18
18
NO HYDRONIC PACKAGE
ICF
Rec
MCA MOCP
Fuse
WD
XL
Size
315.5
400
484.2 1170.2
350
347.6
450
549.6 1338.6
400
157.7
200
242.1
585.1
175
121.2
150
191.9
465.9
150
183.5
250
289.7
704.7
225
334.0
450
499.1 1185.1
400
368.0
500
566.0 1355.0
450
167.0
225
249.6
592.6
200
128.5
175
197.8
471.8
150
194.5
250
298.6
713.6
225
364.6
500
536.7 1278.7
400
401.3
500
607.8 1461.8
450
182.3
250
268.4
639.4
200
139.5
175
211.7
508.7
175
212.7
250
321.7
770.7
250
405.7
500
536.7
450
446.2
600
607.8
500
202.4
250
268.4
639.4
225
155.5
200
211.7
508.7
175
236.4
300
321.7
770.7
300
438.6
600
569.6
500
482.2
600
643.8
600
218.4
300
284.4
655.4
250
168.4
225
224.5
521.5
200
255.3
350
340.6
789.6
300
534.7
800
796.7
700
588.5
800
906.1
700
267.3
400
398.4 1030.4
350
205.0
300
315.5
821.5
250
311.2
450
478.9 1243.9
350
621.1
800
997.6
700
682.8 1000 1136.1
800
309.7
450
498.4 1306.4
350
238.1
350
396.3 1042.3
300
361.1
500
598.9 1577.9
450
673.2
800
935.2
800
740.9 1000 1058.5
1000
336.6
450
467.6 1099.6
400
258.3
350
368.8
874.8
300
391.5
500
559.2 1324.2
450
769.6 1000 1146.0
1000
846.0 1000 1299.2
1000
383.9
500
572.6 1380.6
450
294.8
400
453.0 1099.0
350
447.2
600
685.0 1664.0
500
850.2 1200 1152.0
1000
935.1 1200 1305.9
1200
424.7
600
575.6 1383.6
500
326.3
450
455.4 1101.4
400
494.5
700
688.6 1667.6
600
910.0 1200 1211.8
1200
1001.1 1200 1371.8
1200
455.0
600
605.9 1413.9
600
349.6
450
478.7 1124.7
400
529.5
700
723.5 1702.5
600
516.5
700
777.6 1999.6
600
396.4
500
616.2 1594.2
450
600.2
800
933.9 2412.9
700
549.7
800
810.9 2032.9
700
422.1
600
641.9 1619.9
500
638.7
800
972.4 2451.4
800
610.9
800
810.9 2032.9
700
468.7
600
641.9 1619.9
600
710.3 1000
972.4 2451.4
800
624.3
800
885.5 2107.5
700
479.1
600
698.9 1676.9
600
724.7 1000 1058.4 2537.4
800
685.5
800
885.5 2107.5
800
525.7
700
698.9 1676.9
600
796.3 1000 1058.4 2537.4 1000
350.0
385.7
175.0
134.9
204.2
380.6
419.0
190.3
145.9
222.4
421.7
463.9
210.4
161.9
246.1
454.6
499.9
226.4
174.8
265.0
550.7
606.2
275.3
211.4
320.9
637.1
700.5
317.7
244.5
370.8
450
500
225
175
250
500
500
250
175
300
500
600
250
225
300
600
600
300
225
350
800
800
400
300
450
800
1000
450
350
500
LEGEND
ICF
Instantaneous Current Flow
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
WD
Wye-Delta
XL
Across-the-Line
*30XA400-500 units are not available with single point power.
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
515.1
583.7
257.6
204.2
308.3
552.7
625.5
276.4
218.1
331.3
552.7
625.5
276.4
218.1
331.3
585.6
661.5
292.4
230.9
350.3
812.7
923.8
406.4
321.9
488.6
1013.6
1153.8
506.4
402.7
608.6
1201.1
1372.7
600.6
478.2
723.3
1294.7
1479.5
647.4
515.1
780.3
647.4
515.1
780.3
663.4
527.9
799.3
1038.4
827.9
1253.6
1314.4
1048.7
1587.6
Rec
Fuse
Size
400
450
200
150
225
450
500
225
175
250
500
600
250
200
300
500
600
250
200
300
700
700
350
250
400
800
800
400
300
450
357.2
450
522.3 1208.3 400
393.6
500
591.7 1380.7 450
178.6
225
261.2
604.2 200
137.7
175
207.0
481.0 150
208.6
250
312.6
727.6 250
387.8
500
559.9 1301.9 450
427.0
500
633.5 1487.5 500
193.9
250
280.0
651.0 225
148.8
200
220.9
517.9 175
226.7
300
335.7
784.7 250
428.9
600
559.9
500
471.9
600
633.5
600
214.0
300
280.0
651.0 250
164.8
225
220.9
517.9 200
250.4
350
335.7
784.7 300
461.8
600
592.8
600
507.8
600
669.4
600
230.0
300
296.0
667.0 300
177.7
225
233.8
530.8 200
269.4
350
354.7
803.7 300
557.9
800
819.9
700
614.1
800
931.8
700
278.9
400
410.0 1042.0 350
214.3
300
324.7
830.7 250
325.3
450
493.0 1258.0 400
644.3
800 1020.8
800
708.5 1000 1161.7
800
321.3
450
510.0 1318.0 400
247.4
350
405.6 1051.6 300
375.2
500
612.9 1591.9 450
CONTROL CIRCUIT
Voltage
MCA
1 PH,
and
60 Hz
MOCP
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
4. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG (American Wire Gage)
to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to 799.9 amps
is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to 1199.9 amps
is 250 kcmil to 500 kcmil.
5. Data provided circuit 1/circuit 2 where there are two circuits.
56
Table 5 30XA080-350* Electrical Data, Single Point (Standard Condenser Fan Motors) (cont)
UNIT
30XA
080
090
100
110
120
140
160
180
200
220
240
260
280
300
325
350
UNIT VOLTAGE
Supplied
V-Hz
(3 Ph)
Min
Max
NUMBER
OF
COND
REQD
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
6
6
6
6
6
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
10
10
10
10
10
10
10
10
10
10
12
12
12
12
12
12
12
12
12
12
13
13
13
13
13
13
13
13
13
13
15
15
15
16
16
16
16
16
16
18
18
18
18
18
18
MCA
364.4
401.6
182.2
140.6
212.9
395.0
434.9
197.5
151.7
231.1
436.1
479.9
217.6
167.7
254.8
469.0
515.8
233.6
180.5
273.7
565.1
622.1
282.5
217.1
329.6
651.5
716.4
324.9
250.2
379.5
450
500
225
175
250
500
500
250
200
300
600
600
300
225
350
600
700
300
225
350
800
800
400
300
450
800
1000
450
350
500
529.5
599.6
264.8
209.9
317.0
567.1
641.5
283.6
223.8
340.1
567.1
641.5
283.6
223.8
340.1
600.0
677.4
299.6
236.7
359.0
827.1
939.7
413.6
327.6
497.3
1028.0
1169.7
513.6
408.5
617.3
1215.5
1388.6
607.8
483.9
732.0
1309.1
1495.5
654.6
520.8
789.1
654.6
520.8
789.1
670.6
533.7
808.0
1045.6
833.6
1262.3
1321.6
1054.5
1596.3
Rec
Fuse
Size
400
450
200
175
250
450
500
225
175
300
500
600
250
200
300
600
600
300
200
300
700
700
350
250
400
800
1000
400
300
450
MCA
379.0
417.7
189.5
146.5
221.8
409.6
451.1
204.8
157.5
239.9
450.7
496.0
224.9
173.5
263.6
483.6
531.9
240.9
186.4
282.6
579.7
638.2
289.8
223.0
338.5
666.1
732.6
332.2
256.1
388.4
500
500
250
175
250
500
600
250
200
300
600
600
300
225
350
600
700
300
250
350
800
800
400
300
450
800
1000
450
350
500
544.1
615.8
272.1
215.8
325.8
581.7
657.6
290.9
229.7
348.9
581.7
657.6
290.9
229.7
348.9
614.6
693.5
306.9
242.5
367.9
841.7
955.9
420.9
333.5
506.2
1042.6
1185.8
520.9
414.3
626.1
1230.1
1404.8
615.1
489.8
740.8
1323.7
1511.6
661.9
526.7
797.9
661.9
526.7
797.9
677.9
539.5
816.9
1052.9
839.5
1271.2
1328.9
1060.3
1605.1
Rec
Fuse
Size
450
500
225
175
250
450
500
225
175
300
500
600
250
200
300
600
600
300
225
350
700
800
350
250
400
800
1000
400
300
450
CONTROL CIRCUIT
Voltage
MCA
1 PH,
and
60 Hz
MOCP
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
LEGEND
ICF
Instantaneous Current Flow
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
WD
Wye-Delta
XL
Across-the-Line
*30XA400-500 units are not available with single point power.
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
57
Table 6 30XA080-500 Electrical Data, Dual Point (Standard Condenser Fan Motors)
UNIT
30XA
080
090
100
110
120
140
160
180
200
220
240
260
280
300
325
350
400
450
500
ICF
MCA
MOCP
WD
XL
NO HYDRONIC PACKAGE
ICF
MOCP
WD
XL
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
460-60
575-60
380-60
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
414
518
342
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
506
633
418
3/3
3/3
3/3
3/3
3/3
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
9/6
9/6
9/6
173.3/173.3
190.9/190.9
86.6/ 86.6
66.5/ 66.5
100.7/100.7
182.9/182.9
201.5/201.5
91.4/ 91.4
70.3/ 70.3
106.5/106.5
199.9/199.9
220.0/220.0
99.9/ 99.9
76.4/ 76.4
116.5/116.5
241.0/199.9
264.9/220.0
120.0/ 99.9
92.5/ 76.4
140.2/116.5
241.0/241.0
264.9/264.9
120.0/120.0
92.5/ 92.5
140.2/140.2
370.0/199.9
407.2/220.0
185.0/ 99.9
141.9/ 76.4
215.1/116.5
423.5/241.0
465.6/264.9
211.3/120.0
162.2/ 92.5
246.0/140.2
370.0/370.0
407.2/407.2
185.0/185.0
141.9/141.9
215.1/215.1
423.5/423.5
465.6/465.6
211.3/211.3
162.2/162.2
246.0/246.0
504.2/423.5
554.7/465.6
252.1/211.3
193.7/162.2
293.3/246.0
504.2/498.2
554.7/548.0
252.1/249.1
193.7/191.3
293.3/289.7
343.9/211.3
263.8/162.2
399.0/246.0
250/
300/
125/
110/
150/
300/
300/
150/
110/
175/
300/
350/
150/
125/
175/
400/
450/
200/
150/
225/
400/
450/
200/
150/
225/
600/
700/
300/
225/
350/
700/
800/
350/
250/
400/
600/
700/
300/
225/
350/
700/
800/
350/
250/
400/
800/
800/
400/
300/
500/
800/
800/
400/
300/
500/
500/
450/
600/
250
300
125
110
150
300
300
150
110
175
300
350
150
125
175
300
350
150
125
175
400
450
200
150
225
300
350
150
125
175
400
450
200
150
225
600
700
300
225
350
700
800
350
250
400
700
800
350
250
400
800
800
400
300
500
350
250
400
342.0/342.0
392.9/392.9
171.0/171.0
137.2/137.2
206.9/206.9
348.0/348.0
399.5/399.5
174.0/174.0
139.6/139.6
210.5/210.5
372.0/372.0
426.5/426.5
186.0/186.0
148.6/148.6
225.5/225.5
372.0/372.0
426.5/426.5
186.0/186.0
148.6/148.6
225.5/225.5
372.0/372.0
426.5/426.5
186.0/186.0
148.6/148.6
225.5/225.5
632.0/372.0
724.8/426.5
316.0/186.0
252.4/148.6
382.8/225.5
800.0/372.0
918.8/426.5
400.0/186.0
320.4/148.6
483.8/225.5
632.0/632.0
724.8/724.8
316.0/316.0
252.4/252.4
382.8/382.8
800.0/800.0
918.8/918.8
400.0/400.0
320.4/320.4
483.8/483.8
806.0/800.0
925.4/918.8
403.0/400.0
322.8/320.4
487.4/483.8
806.0/800.0
925.4/918.8
403.0/400.0
322.8/320.4
487.4/483.8
605.0/400.0
483.6/320.4
732.7/483.8
1028.0/1028.0
1181.9/1181.9
514.0/ 514.0
411.2/ 411.2
621.9/ 621.9
1034.0/1034.0
1188.5/1188.5
517.0/ 517.0
413.6/ 413.6
625.5/ 625.5
1114.0/1114.0
1280.5/1280.5
557.0/ 557.0
445.6/ 445.6
674.5/ 674.5
557.0/557.0
445.6/445.6
674.5/674.5
557.0/557.0
445.6/445.6
674.5/674.5
948.0/557.0
758.4/445.6
1147.8/674.5
1208.0/557.0
966.4/445.6
1462.8/674.5
948.0/ 948.0
758.4/ 758.4
1147.8/1147.8
1208.0/1208.0
966.4/ 966.4
1462.8/1462.8
1211.0/1208.0
968.8/ 966.4
1466.4/1462.8
1211.0/1208.0
968.8/ 966.4
1466.4/1462.8
1827.0/1208.0
1461.6/ 966.4
2211.7/1462.8
Rec
Fuse
Size
225/225
250/250
110/110
80/ 80
125/125
225/225
250/250
110/110
90/ 90
125/125
250/250
300/300
125/125
90/ 90
150/150
300/250
350/300
150/125
110/ 90
175/150
300/300
350/350
150/150
110/110
175/175
450/250
500/300
225/125
175/ 90
300/150
600/300
600/350
250/150
200/110
300/175
450/450
500/500
225/225
175/175
300/300
600/600
600/600
250/250
200/200
300/300
600/600
700/600
300/250
250/200
350/300
600/600
700/700
300/300
250/250
350/350
450/250
350/200
500/300
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
9/7
9/7
9/7
10/6
10/6
10/6
9/9
9/9
9/9
9/9
9/9
9/9
8/12
8/12
8/12
8/14
8/14
8/14
8/14
8/14
8/14
343.9/252.1
263.8/193.7
399.0/293.3
408.0/249.1
312.8/191.3
474.2/289.7
343.9/343.9
263.8/263.8
399.0/399.0
405.0/343.9
310.4/263.8
470.5/399.0
340.9/452.0
261.4/347.2
395.4/525.8
402.0/553.6
308.0/424.4
466.9/643.3
402.0/604.9
308.0/463.9
466.9/703.0
500/ 400
450/ 300
600/ 500
700/ 400
500/ 300
800/ 500
500/ 500
450/ 450
600/ 600
700/ 500
500/ 450
800/ 600
500/ 600
450/ 450
600/ 700
700/ 800
500/ 600
800/ 800
700/ 800
500/ 600
800/1000
605.0/403.0
483.6/322.8
732.7/487.4
608.0/400.0
486.0/320.4
736.3/483.8
605.0/605.0
483.6/483.6
732.7/732.7
605.0/605.0
483.6/483.6
732.7/732.7
602.0/602.9
481.2/476.3
729.1/719.9
602.0/753.6
481.2/597.6
729.1/905.5
602.0/804.9
481.2/637.1
729.1/965.2
1827.0/1211.0
1461.6/ 968.8
2211.7/1466.4
1830.0/1208.0
1464.0/ 966.4
2215.3/1462.8
1827.0/1827.0
1461.6/1461.6
2211.7/2211.7
1827.0/1827.0
1461.6/1461.6
2211.7/2211.7
1824.0/1410.9
1459.2/1122.3
2208.1/1698.9
1824.0/1975.6
1459.2/1575.6
2208.1/2384.5
1824.0/2026.9
1459.2/1615.1
2208.1/2444.2
450/300
350/250
500/350
500/300
400/250
600/350
450/450
350/350
500/500
500/450
400/350
600/500
450/500
350/400
500/600
500/700
400/500
600/800
500/700
400/600
600/800
MCA
LEGEND
Instantaneous Current Flow
Minimum Circuit Amps
Maximum Overcurrent Protection
Wye-Delta
Across-the-Line
182.9/198.9
201.5/219.2
91.4/ 99.4
70.3/ 76.7
106.5/116.1
199.9/215.9
220.0/237.7
99.9/107.9
76.4/ 82.8
116.5/126.2
241.0/215.9
264.9/237.7
120.0/107.9
92.5/ 82.8
140.2/126.2
241.0/257.0
264.9/282.6
120.0/128.0
92.5/ 98.9
140.2/149.9
370.0/215.9
407.2/237.7
185.0/107.9
141.9/ 82.8
215.1/126.2
423.5/257.0
465.6/282.6
211.3/128.0
162.2/ 98.9
246.0/149.9
300/300
300/350
150/150
110/125
175/175
300/350
350/350
150/175
125/125
175/200
400/350
450/350
200/175
150/125
225/200
400/400
450/450
200/200
150/150
225/250
600/350
700/350
300/175
225/125
350/200
700/400
800/450
350/200
250/150
400/250
348.0/364.0
399.5/417.2
174.0/182.0
139.6/146.0
210.5/220.2
372.0/388.0
426.5/444.2
186.0/194.0
148.6/155.0
225.5/235.2
372.0 /388.0
426.5/444.2
186.0/194.0
148.6/155.0
225.5/235.2
372.0/388.0
426.5/444.2
186.0/194.0
148.6/155.0
225.5/235.2
632.0/388.0
724.8/444.2
316.0/194.0
252.4/155.0
382.8/235.2
800.0/388.0
918.8/444.2
400.0/194.0
320.4/155.0
483.8/235.2
1034.0/1050.0
1188.5/1206.2
517.0/ 525.0
413.6/ 420.0
625.5/ 635.2
1114.0/1130.0
1280.5/1298.2
557.0/ 565.0
445.6/ 452.0
674.5/ 684.2
557.0/ 565.0
445.6/ 452.0
674.5/ 684.2
557.0/ 565.0
445.6/ 452.0
674.5/ 684.2
948.0/ 565.0
758.4/ 452.0
1147.8/ 684.2
1208.0/ 565.0
966.4/ 452.0
1462.8/ 684.2
Rec
Fuse
Size
225/250
250/300
110/125
90/ 90
125/150
250/300
300/300
125/150
90/100
150/150
300/300
350/300
150/150
110/100
175/150
300/350
350/350
150/150
110/125
175/200
450/300
500/300
225/150
175/100
300/150
600/350
600/350
250/150
200/125
300/200
MCA
CONTROL CIRCUIT
Voltage
MCA
1 PH,
and
60 Hz
MOCP
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
40
40
40
40
40
40
40
40
40
40
40
40
50
50
50
50
50
50
50
50
50
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
58
Table 6 30XA080-500 Electrical Data, Dual Point (Standard Condenser Fan Motors) (cont)
UNIT
30XA
080
090
100
110
120
140
160
180
200
220
240
260
280
300
325
350
400
450
500
ICF
MCA
MOCP
WD
XL
UNIT VOLTAGE
Supplied
V-Hz
(3 Ph)
NUMBER
OF
COND
Min Max
REQD
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
460-60
575-60
380-60
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
414
518
342
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
506
633
418
3/3
3/3
3/3
3/3
3/3
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
9/6
9/6
9/6
182.9/206.1
201.5/227.1
91.4/103.0
70.3/ 79.6
106.5/120.5
199.9/223.1
220.0/245.7
99.9/111.5
76.4/ 85.7
116.5/130.6
241.0/223.1
264.9/245.7
120.0/111.5
92.5/ 85.7
140.2/130.6
241.0/264.2
264.9/290.6
120.0/131.6
92.5/101.8
140.2/154.3
370.0/223.1
407.2/245.7
185.0/111.5
141.9/ 85.7
215.1/130.6
423.5/264.2
465.6/290.6
211.3/131.6
162.2/101.8
246.0/154.3
300/300
300/350
150/150
110/125
175/175
300/350
350/400
150/175
125/125
175/200
400/350
450/400
200/175
150/125
225/200
400/400
450/450
200/200
150/150
225/250
600/350
700/400
300/175
225/125
350/200
700/400
800/450
350/200
250/150
400/250
348.0/371.2
399.5/425.2
174.0/185.6
139.6/148.9
210.5/224.6
372.0/395.2
426.5/452.2
186.0/197.6
148.6/157.9
225.5/239.6
372.0/395.2
426.5/452.2
186.0/197.6
148.6/157.9
225.5/239.6
372.0/395.2
426.5/452.2
186.0/197.6
148.6/157.9
225.5/239.6
632.0/395.2
724.8/452.2
316.0/197.6
252.4/157.9
382.8/239.6
800.0/395.2
918.8/452.2
400.0/197.6
320.4/157.9
483.8/239.6
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
9/7
9/7
9/7
10/6
10/6
10/6
9/9
9/9
9/9
9/9
9/9
9/9
8/12
8/12
8/12
8/14
8/14
8/14
8/14
8/14
8/14
MCA
1034.0/1057.2
1188.5/1214.2
517.0/ 528.6
413.6/ 422.9
625.5/ 639.6
1114.0/1137.2
1280.5/1306.2
557.0/ 568.6
445.6/ 454.9
674.5/ 688.6
557.0/ 568.6
445.6/ 454.9
674.5/ 688.6
557.0/ 568.6
445.6/ 454.9
674.5/ 688.6
948.0/ 568.6
758.4/ 454.9
1147.8/ 688.6
1208.0/ 568.6
966.4/ 454.9
1462.8/ 688.6
Rec
Fuse
Size
225/250
250/300
110/125
90/100
125/150
250/300
300/300
125/150
90/100
150/175
300/300
350/300
150/150
110/100
175/175
300/350
350/350
150/175
110/125
175/200
450/300
500/300
225/150
175/100
300/175
600/350
600/350
250/175
200/125
300/200
182.9/213.3
201.5/235.1
91.4/106.6
70.3/ 82.5
106.5/124.9
199.9/230.3
220.0/253.6
99.9/115.1
76.4/ 88.6
116.5/134.9
241.0/230.3
264.9/253.6
120.0/115.1
92.5/ 88.6
140.2/134.9
241.0/271.4
264.9/298.5
120.0/135.2
92.5/104.6
140.2/158.6
370.0/230.3
407.2/253.6
185.0/115.1
141.9/ 88.6
215.1/134.9
423.5/271.4
465.6/298.5
211.3/135.2
162.2/104.6
246.0/158.6
300/300
300/350
150/150
110/125
175/175
300/350
350/400
150/175
125/125
175/200
400/350
450/400
200/175
150/125
225/200
400/400
450/450
200/200
150/150
225/250
600/350
700/400
300/175
225/125
350/200
700/400
800/450
350/200
250/150
400/250
348.0/378.4
399.5/433.2
174.0/189.2
139.6/151.8
210.5/228.9
372.0/402.4
426.5/460.2
186.0/201.2
148.6/160.8
225.5/243.9
372.0/402.4
426.5/460.2
186.0/201.2
148.6/160.8
225.5/243.9
372.0/402.4
426.5/460.2
186.0/201.2
148.6/160.8
225.5/243.9
632.0/402.4
724.8/460.2
316.0/201.2
252.4/160.8
382.8/243.9
800.0/402.4
918.8/460.2
400.0/201.2
320.4/160.8
483.8/243.9
1034.0/1064.4
1188.5/1222.2
517.0/ 532.2
413.6/ 425.8
625.5/ 643.9
1114.0/1144.4
1280.5/1314.2
557.0/ 572.2
445.6/ 457.8
674.5/ 692.9
557.0/ 572.2
445.6/ 457.8
674.5/ 692.9
557.0/ 572.2
445.6/ 457.8
674.5/ 692.9
948.0/ 572.2
758.4/ 457.8
1147.8/ 692.9
1208.0/ 572.2
966.4/ 457.8
1462.8/ 692.9
Rec
Fuse
Size
225/250
250/300
110/125
90/100
125/150
250/300
300/300
125/150
90/110
150/175
300/300
350/300
150/150
110/110
175/175
300/350
350/350
150/175
110/125
175/200
450/300
500/300
225/150
175/110
300/175
600/350
600/350
250/175
200/125
300/200
LEGEND
Instantaneous Current Flow
Minimum Circuit Amps
Maximum Overcurrent Protection
Wye-Delta
Across-the-Line
MCA
CONTROL CIRCUIT
Voltage
MCA
1 PH,
and
60 Hz
MOCP
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
115
40
40
40
40
40
40
40
40
40
40
40
40
50
50
50
50
50
50
50
50
50
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
59
Table 6 30XA080-500 Electrical Data, Dual Point (Standard Condenser Fan Motors) (cont)
UNIT
30XA
080
090
100
110
120
140
160
180
200
220
240
260
280
300
325
350
400
450
500
ICF
MCA
MOCP
WD
XL
UNIT VOLTAGE
Supplied
V-Hz
(3 Ph)
Min
Max
NUMBER
OF
COND
REQD
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
3/3
3/3
3/3
3/3
3/3
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
9/6
9/6
9/6
9/7
9/7
9/7
10/6
10/6
10/6
9/9
9/9
9/9
9/9
9/9
9/9
8/12
8/12
8/12
8/14
8/14
8/14
8/14
8/14
8/14
MOCP
182.9/227.9
201.5/251.2
91.4/113.9
70.3/ 88.3
106.5/133.7
199.9/244.9
220.0/269.8
99.9/122.4
76.4/ 94.4
116.5/143.8
241.0/244.9
264.9/269.8
120.0/122.4
92.5/ 94.4
140.2/143.8
241.0/286.0
264.9/314.7
120.0/142.5
92.5/110.5
140.2/167.5
370.0/244.9
407.2/269.8
185.0/122.4
141.9/ 94.4
215.1/143.8
423.5/286.0
465.6/314.7
211.3/142.5
162.2/110.5
246.0/167.5
300/350
300/350
150/175
110/125
175/200
300/350
350/400
150/175
125/125
175/225
400/350
450/400
200/175
150/125
225/225
400/450
450/500
200/225
150/175
225/250
600/350
700/400
300/175
225/125
350/225
700/450
800/500
350/225
250/175
400/250
LEGEND
Instantaneous Current Flow
Minimum Circuit Amps
Maximum Overcurrent Protection
Wye-Delta
Across-the-Line
WD
XL
348.0/393.0
399.5/449.3
174.0/196.5
139.6/157.6
210.5/237.8
372.0/417.0
426.5/476.3
186.0/208.5
148.6/166.6
225.5/252.8
372.0/417.0
426.5/476.3
186.0/208.5
148.6/166.6
225.5/252.8
372.0/417.0
426.5/476.3
186.0/208.5
148.6/166.6
225.5/252.8
632.0/417.0
724.8/476.3
316.0/208.5
252.4/166.6
382.8/252.8
800.0/417.0
918.8/476.3
400.0/208.5
320.4/166.6
483.8/252.8
1034.0/1079.0
1188.5/1238.3
517.0/ 539.5
413.6/ 431.6
625.5/ 652.8
1114.0/1159.0
1280.5/1330.3
557.0/ 579.5
445.6/ 463.6
674.5/ 701.8
557.0/ 579.5
445.6/ 463.6
674.5/ 701.8
557.0/ 579.5
445.6/ 463.6
674.5/ 701.8
948.0/ 579.5
758.4/ 463.6
1147.8/ 701.8
1208.0/ 579.5
966.4/ 463.6
1462.8/ 701.8
Rec
Fuse
Size
225/300
250/300
110/150
90/110
125/175
250/300
300/350
125/150
90/110
150/175
300/300
350/350
150/150
110/110
175/175
300/350
350/400
150/175
110/150
175/200
450/300
500/350
225/150
175/110
300/175
600/350
600/400
250/175
200/150
300/200
CONTROL CIRCUIT
Voltage
MCA
1 PH,
and
60 Hz
MOCP
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
50
115
50
115
50
115
50
115
50
115
50
115
50
115
50
115
50
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
60
140
160
180
200
220
240
260
280
300
325
350
ICF
MCA
MOCP
WD
XL
UNIT VOLTAGE
Supplied
V-Hz
(3 Ph)
Min Max
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
NUMBER
OF
COND
REQD
10
10
10
10
10
10
10
10
10
10
12
12
12
12
12
12
12
12
12
12
13
13
13
13
13
13
13
13
13
13
15
15
15
16
16
16
16
16
16
18
18
18
18
18
18
NO HYDRONIC PACKAGE
ICF
Rec
MCA MOCP
Fuse
WD
XL
Size
562.0
800
838.9
700
618.8
800
952.8
700
281.0
400
419.5 1051.5
350
216.3
300
332.5
838.5
250
328.3
450
504.6 1269.6
400
642.7
800 1036.7
800
706.9 1000 1179.4
800
320.5
450
518.0 1326.0
400
247.2
350
412.1 1058.1
300
374.9
500
622.8 1601.8
450
703.9
800
980.8
800
775.0 1000 1109.1
1000
351.9
450
490.4 1122.4
400
271.1
350
387.3
893.3
300
410.8
500
587.2 1352.2
450
795.6 1000 1189.6
1000
875.0 1200 1347.5
1000
396.9
500
594.4 1402.4
450
305.8
400
470.7 1116.7
350
463.8
600
711.7 1690.7
600
876.7 1200 1200.4
1000
964.6 1200 1359.4
1200
438.0
600
599.8 1407.8
500
337.6
450
475.0 1121.0
400
511.5
700
718.3 1697.3
600
933.0 1200 1256.7
1200
1026.7 1200 1421.6
1200
466.5
600
628.3 1436.3
600
359.5
450
497.0 1143.0
400
544.4
700
751.2 1730.2
600
529.1
700
806.6 2028.6
600
407.4
500
639.7 1617.7
500
616.7
800
969.3 2448.3
700
563.0
800
840.5 2062.5
700
433.6
600
665.9 1643.9
500
656.2
800 1008.8 2487.8
800
619.6
800
840.5 2062.5
700
476.7
600
665.9 1643.9
600
722.3 1000 1008.8 2487.8 1000
638.1
800
915.6 2137.6
700
491.2
600
723.5 1701.5
600
743.0 1000 1095.6 2574.6 1000
694.6
800
915.6 2137.6
800
534.2
700
723.5 1701.5
600
809.1 1000 1095.6 2574.6 1000
800
800
400
300
450
800
1000
450
350
500
LEGEND
Instantaneous Current Flow
Minimum Circuit Amps
Maximum Overcurrent Protection
Wye-Delta
Across-the-Line
854.9
970.5
427.5
338.9
514.3
1052.7
1197.1
526.0
418.5
632.5
1059.5
844.9
1279.3
1334.0
1064.5
1611.5
Rec
Fuse
Size
700
800
350
250
400
800
1000
400
300
450
700
644.4
800
978.5
800
292.6
400
431.1 1063.1
350
225.6
300
341.8
847.8
250
342.3
450
518.7 1283.7
400
665.9
800 1059.9
800
732.5 1000 1205.0
1000
332.1
450
529.6 1337.6
400
256.5
350
421.4 1067.4
300
388.9
500
636.8 1615.8
450
CONTROL CIRCUIT
Voltage
MCA
1 PH,
and
60 Hz
MOCP
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
61
Table 7 30XA140-500 Electrical Data, Single Point (High Ambient Option) (cont)
UNIT VOLTAGE
Supplied
UNIT
30XA
140
160
180
200
220
240
260
280
300
325
350
ICF
MCA
MOCP
WD
XL
V-Hz
(3 Ph)
Min
Max
NUMBER
OF
COND
REQD
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
10
10
10
10
10
10
10
10
10
10
12
12
12
12
12
12
12
12
12
12
13
13
13
13
13
13
13
13
13
13
15
15
15
16
16
16
16
16
16
18
18
18
18
18
18
MCA
592.4
652.4
296.2
228.4
346.7
673.1
740.5
335.7
259.4
393.3
869.3
986.5
434.7
344.6
523.0
1067.1
1213.0
533.2
424.3
641.2
1066.7
850.6
1288.0
1341.2
1070.3
1620.2
LEGEND
Instantaneous Current Flow
Minimum Circuit Amps
Maximum Overcurrent Protection
Wye-Delta
Across-the-Line
Rec
Fuse
Size
700
800
350
300
400
800
1000
400
300
450
MCA
607.0
668.6
303.5
234.3
355.5
687.7
756.6
343.0
265.2
402.1
883.9
1002.6
442.0
350.5
531.9
1081.7
1229.1
540.5
430.1
650.0
1074.0
856.5
1296.9
1348.5
1076.1
1629.0
Rec
Fuse
Size
700
800
350
300
400
800
1000
400
300
450
CONTROL CIRCUIT
Voltage
MCA
1 PH,
and
60 Hz
MOCP
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
62
140
160
180
200
220
240
260
280
300
325
350
400
450
500
ICF
MCA
MOCP
WD
XL
UNIT VOLTAGE
Supplied
V-Hz
(3 Ph)
NUMBER
OF
COND
Min Max REQD
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
9/6
9/6
9/6
9/7
9/7
9/7
10/6
10/6
10/6
9/9
9/9
9/9
9/9
9/9
9/9
8/12
8/12
8/12
8/14
8/14
8/14
8/14
8/14
8/14
MCA
383.8/211.9
422.6/233.3
191.9/105.9
147.7/ 81.4
223.9/124.0
434.8/249.1
478.1/273.9
216.9/124.1
167.0/ 95.9
253.3/145.4
383.8/383.8
422.6/422.6
191.9/191.9
147.7/147.7
223.9/223.9
434.8/434.8
478.1/478.1
216.9/216.9
167.0/167.0
253.3/253.3
515.9/434.8
567.8/478.1
258.0/216.9
198.8/167.0
301.0/253.3
515.9/505.1
567.8/555.8
258.0/252.6
198.8/194.5
301.0/294.5
349.1/216.9
268.6/167.0
406.2/253.3
349.1/258.0
268.6/198.8
406.2/301.0
411.0/252.6
315.9/194.5
478.9/294.5
349.1/349.1
268.6/268.6
406.2/406.2
405.6/349.1
311.6/268.6
472.4/406.2
343.7/461.1
264.2/355.2
399.7/537.9
400.2/560.2
307.3/430.7
465.8/652.8
400.2/608.8
307.3/468.0
465.8/709.3
NO HYDRONIC PACKAGE
ICF
MOCP
WD
XL
600/ 300
700/ 350
300/ 150
225/ 125
350/ 200
700/ 400
800/ 450
350/ 200
250/ 150
400/ 225
600/ 600
700/ 700
300/ 300
225/ 225
350/ 350
700/ 700
800/ 800
350/ 350
250/ 250
400/ 400
800/ 700
800/ 800
400/ 350
300/ 250
500/ 400
800/ 800
800/ 800
400/ 400
300/ 300
500/ 450
500/ 350
450/ 250
600/ 400
500/ 400
450/ 300
600/ 500
600/ 400
500/ 300
800/ 450
500/ 500
450/ 450
600/ 600
600/ 500
500/ 450
800/ 600
500/ 600
400/ 450
600/ 700
600/ 800
500/ 600
700/ 800
600/ 800
500/ 600
700/1000
660.8/391.2
756.7/447.8
330.4/195.6
263.9/156.3
400.2/237.1
828.8/391.2
950.7/447.8
414.4/195.6
331.9/156.3
501.2/237.1
660.8/660.8
756.7/756.7
330.4/330.4
263.9/263.9
400.2/400.2
828.8/828.8
950.7/950.7
414.4/414.4
331.9/331.9
501.2/501.2
839.6/828.8
962.6/950.7
419.8/414.4
336.2/331.9
507.8/501.2
839.6/828.8
962.6/950.7
419.8/414.4
336.2/331.9
507.8/501.2
626.6/414.4
500.9/331.9
758.8/501.2
626.6/419.8
500.9/336.2
758.8/507.8
632.0/414.4
505.2/331.9
765.4/501.2
626.6/626.6
500.9/500.9
758.8/758.8
626.6/626.6
500.9/500.9
758.8/758.8
621.2/622.9
496.6/492.7
752.3/744.6
621.2/781.2
496.6/619.9
752.3/939.2
621.2/829.7
496.6/657.3
752.3/995.7
962.4/ 566.6
769.9/ 453.3
1165.2/ 686.1
1222.4/ 566.6
977.9/ 453.3
1480.2/ 686.1
962.4/ 962.4
769.9/ 769.9
1165.2/1165.2
1222.4/1222.4
977.9/ 977.9
1480.2/1480.2
1227.8/1222.4
982.2/ 977.9
1486.8/1480.2
1227.8/1222.4
982.2/ 977.9
1486.8/1480.2
1848.6/1222.4
1478.9/ 977.9
2237.8/1480.2
1848.6/1227.8
1478.9/ 982.2
2237.8/1486.8
1854.0/1222.4
1483.2/ 977.9
2244.4/1480.2
1848.6/1848.6
1478.9/1478.9
2237.8/2237.8
1848.6/1848.6
1478.9/1478.9
2237.8/2237.8
1843.2/1430.9
1474.6/1138.7
2231.3/1723.6
1843.2/2003.2
1474.6/1597.9
2231.3/2418.2
1843.2/2051.7
1474.6/1635.3
2231.3/2474.7
Rec
Fuse
Size
450/250
500/300
225/125
175/100
300/150
600/300
600/350
300/150
200/125
300/175
450/450
500/500
225/225
175/175
300/300
600/600
600/600
300/300
200/200
300/300
700/600
700/600
350/300
250/200
400/300
700/600
700/700
350/300
250/250
400/350
450/300
350/200
500/300
450/350
350/250
500/400
500/300
400/250
600/350
450/450
350/350
500/500
500/450
400/350
600/500
450/600
350/400
500/600
500/700
400/500
600/800
500/700
400/600
600/800
LEGEND
Instantaneous Current Flow
Minimum Circuit Amps
Maximum Overcurrent Protection
Wye-Delta
Across-the-Line
MCA
383.8/227.9
422.6/251.0
191.9/113.9
147.7/ 87.8
223.9/133.7
434.8/265.1
478.1/291.6
216.9/132.1
167.0/102.3
253.3/155.1
660.8/407.2
756.7/465.5
330.4/203.6
962.4/574.6
263.9/162.7
769.9/459.7
400.2/246.8 1165.2/695.8
828.8/407.2
950.7/465.5
414.4/203.6 1222.4/574.6
331.9/162.7
977.9/459.7
501.2/246.8 1480.2/695.8
Rec
Fuse
Size
450/300
500/300
225/150
175/110
300/175
600/350
600/350
300/175
200/125
300/200
CONTROL CIRCUIT
Voltage
MCA
1 PH,
and
60 Hz
MOCP
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
50
115
50
115
50
115
50
115
50
115
50
115
50
115
50
115
50
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
63
Table 8 30XA140-500 Electrical Data, Dual Point (High Ambient Option) (cont)
UNIT
30XA
140
160
180
200
220
240
260
280
300
325
350
400
450
500
ICF
MCA
MOCP
WD
XL
UNIT VOLTAGE
Supplied
V-Hz
(3 Ph)
NUMBER
OF
COND
Min Max
REQD
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
9/6
9/6
9/6
9/7
9/7
9/7
10/6
10/6
10/6
9/9
9/9
9/9
9/9
9/9
9/9
8/12
8/12
8/12
8/14
8/14
8/14
8/14
8/14
8/14
MCA
383.8/235.1
422.6/259.0
191.9/117.5
147.7/ 90.7
223.9/138.0
434.8/272.3
478.1/299.6
216.9/135.7
167.0/105.2
253.3/159.5
660.8/414.4
756.7/473.4
330.4/207.2
263.9/165.6
400.2/251.2
828.8/414.4
950.7/473.4
414.4/207.2
331.9/165.6
501.2/251.2
Rec
Fuse
Size
450/300
500/300
962.4/578.2 225/150
769.9 /462.6 175/110
1165.2/700.2 300/175
600/350
600/350
1222.4/578.2 300/175
977.9/462.6 200/125
1480.2/700.2 300/200
LEGEND
Instantaneous Current Flow
Minimum Circuit Amps
Maximum Overcurrent Protection
Wye-Delta
Across-the-Line
MCA
383.8/242.3
422.6/266.9
191.9/121.1
147.7/ 93.5
223.9/142.4
434.8/279.5
478.1/307.6
216.9/139.3
167.0/108.1
253.3/163.8
660.8/421.6
756.7/481.4
330.4/210.8
263.9/168.4
400.2/255.5
828.8/421.6
950.7/481.4
414.4/210.8
331.9/168.4
501.2/255.5
962.4/581.8
769.9/465.4
1165.2/704.5
1222.4/581.8
977.9/465.4
1480.2/704.5
Rec
Fuse
Size
450/300
500/350
225/150
175/110
300/175
600/350
600/400
300/175
200/125
300/200
CONTROL CIRCUIT
Voltage
MCA
1 PH,
and
60 Hz
MOCP
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
50
115
50
115
50
115
50
115
50
115
50
115
50
115
50
115
50
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
64
Table 8 30XA140-500 Electrical Data, Dual Point (High Ambient Option) (cont)
UNIT
30XA
140
160
180
200
220
240
260
280
300
325
350
400
450
500
ICF
MCA
MOCP
WD
XL
UNIT VOLTAGE
Supplied
V-Hz
(3 Ph)
Min
Max
NUMBER
OF
COND
REQD
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
230-60
200-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
460-60
575-60
380-60
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
207
187
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
414
518
342
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
253
220
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
506
633
418
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/4
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
6/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
7/6
9/6
9/6
9/6
9/7
9/7
9/7
10/6
10/6
10/6
9/9
9/9
9/9
9/9
9/9
9/9
8/12
8/12
8/12
8/14
8/14
8/14
8/14
8/14
8/14
MOCP
383.8/256.9
422.6/283.1
191.9/128.4
147.7/ 99.4
223.9/151.2
434.8/294.1
478.1/323.7
216.9/146.6
167.0/113.9
253.3/172.7
600/350
700/400
300/175
225/150
350/225
700/450
800/500
350/225
250/175
400/250
LEGEND
Instantaneous Current Flow
Minimum Circuit Amps
Maximum Overcurrent Protection
Wye-Delta
Across-the-Line
WD
XL
660.8/436.2
756.7/497.5
330.4/218.1
263.9/174.3
400.2/264.4
828.8/436.2
950.7/497.5
414.4/218.1
331.9/174.3
501.2/264.4
962.4/589.1
769.9/471.3
1165.2/713.4
1222.4/589.1
977.9/471.3
1480.2/713.4
Rec
Fuse
Size
450/300
500/350
225/150
175/125
300/175
600/350
600/400
300/175
200/150
300/200
CONTROL CIRCUIT
Voltage
MCA
1 PH,
and
60 Hz
MOCP
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
40
115
50
115
50
115
50
115
50
115
50
115
50
115
50
115
50
115
50
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. Cooler heater is wired into the control circuit so it is always operable as long as the
control power supply disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are required.
65
080
090
100
110
120
140
160
180
200
220
240
260
280
300
325
350
400
450
500
VOLTAGE
3 PH
60 Hz
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
COMBI*
Power
Circuit 1 (& 2)**
Circuit 1 (& 2)
Circuit 1 (& 2)
Circuit 1 (& 2)
Circuit 1 (& 2)
Circuit 1 (& 2)
Circuit 1 (& 2)
Control
Yes
Yes
Yes
Yes
Yes
No
No
Circuit 1 (& 2)
Circuit 1 (& 2)
Circuit 1 (& 2)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Circuit 1 (& 2)
Circuit 1 (& 2)
Circuit 1 (& 2)
Yes
Yes
Yes
Circuit 1
Circuit 1
Circuit 1
No
No
No
Circuit 1 (& 2)
Circuit 1 (& 2)
Circuit 1 (& 2)
PEB2
Power
Control
Circuit 1 (& 2)
Circuit 1 (& 2)
No
No
Circuit 2
Circuit 2
Circuit 2
Yes
Yes
Yes
66
CONDENSER
FANS
COMPRESSOR
B
LRA (All Units)
RLA
A
LRA (All Units)
FLA
High
Ambient
Standard
XL
Temp
Cond. Fans
Cond. Fans (850 rpm)
(1140 rpm)
200
3/3
11.9
6.6
1081.0
230
3/3
10.8
6.0
940.0
080
380
3/3
6.5
3.6
569.0
460
3/3
5.5
3.0
470.0
575
3/3
4.3
2.4
376.0
200
4/4
11.9
6.6
1081.0
230
4/4
10.8
6.0
940.0
090
380
4/4
6.5
3.6
569.0
460
4/4
5.5
3.0
470.0
575
4/4
4.3
2.4
376.0
200
4/4
11.9
6.6
1357.0
230
4/4
10.8
6.0
1180.0
100
380
4/4
6.5
3.6
714.0
460
4/4
5.5
3.0
590.0
575
4/4
4.3
2.4
472.0
200
4/4
11.9
6.6
1357.0
230
4/4
10.8
6.0
1180.0
110
380
4/4
6.5
3.6
714.0
460
4/4
5.5
3.0
590.0
575
4/4
4.3
2.4
472.0
200
4/4
11.9
6.6
1357.0
230
4/4
10.8
6.0
1180.0
120
380
4/4
6.5
3.6
714.0
460
4/4
5.5
3.0
590.0
575
4/4
4.3
2.4
472.0
200
6/4
11.9
6.6
2162.0
230
6/4
10.8
6.0
1880.0
140
380
6/4
6.5
3.6
1138.0
460
6/4
5.5
3.0
940.0
575
6/4
4.3
2.4
752.0
200
6/4
11.9
6.6
2714.0
230
6/4
10.8
6.0
2360.0
160
380
6/4
6.5
3.6
1428.0
460
6/4
5.5
3.0
1180.0
575
6/4
4.3
2.4
944.0
200
6/6
11.9
6.6
2162.0
230
6/6
10.8
6.0
1880.0
180
380
6/6
6.5
3.6
1138.0
460
6/6
5.5
3.0
940.0
575
6/6
4.3
2.4
752.0
200
6/6
11.9
6.6
2714.0
230
6/6
10.8
6.0
2360.0
200
380
6/6
6.5
3.6
1428.0
460
6/6
5.5
3.0
1180.0
575
6/6
4.3
2.4
944.0
200
7/6
11.9
6.6
2714.0
230
7/6
10.8
6.0
2360.0
220
380
7/6
6.5
3.6
1428.0
460
7/6
5.5
3.0
1180.0
575
7/6
4.3
2.4
944.0
200
7/6
11.9
6.6
2714.0
230
7/6
10.8
6.0
2360.0
240
380
7/6
6.5
3.6
1428.0
460
7/6
5.5
3.0
1180.0
575
7/6
4.3
2.4
944.0
380
9/6
6.5
3.6
2143.0
260
460
9/6
5.5
3.0
1770.0
575
9/6
4.3
2.4
1416.0
380
9/7
6.5
3.6
2143.0
280
460
9/7
5.5
3.0
1770.0
575
9/7
4.3
2.4
1416.0
380
9/7
6.5
3.6
2143.0
300
460
9/7
5.5
3.0
1770.0
575
9/7
4.3
2.4
1416.0
380
9/9
6.5
3.6
2143.0
325
460
9/9
5.5
3.0
1770.0
575
9/9
4.3
2.4
1416.0
380
9/9
6.5
3.6
2143.0
350
460
9/9
5.5
3.0
1770.0
575
9/9
4.3
2.4
1416.0
380
8/12
6.5
3.6
1428.0
400
460
8/12
5.5
3.0
1180.0
575
8/12
4.3
2.4
944.0
380
8/14
6.5
3.6
1138.0
450
460
8/14
5.5
3.0
940.0
575
8/14
4.3
2.4
752.0
380
8/14
6.5
3.6
1428.0
500
460
8/14
5.5
3.0
1180.0
575
8/14
4.3
2.4
944.0
LEGEND
LRA Locked Rotor Amps
WD Wye Delta
RLA Rated Load Amps
XL Across-the-Line
WD
345.0
300.0
182.0
150.0
120.0
345.0
300.0
182.0
150.0
120.0
437.0
380.0
230.0
190.0
152.0
437.0
380.0
230.0
190.0
152.0
437.0
380.0
230.0
190.0
152.0
690.0
600.0
363.0
300.0
240.0
863.0
750.0
454.0
375.0
300.0
690.0
600.0
363.0
300.0
240.0
863.0
750.0
454.0
375.0
300.0
863.0
750.0
454.0
375.0
300.0
863.0
750.0
454.0
375.0
300.0
684.0
565.0
452.0
684.0
565.0
452.0
684.0
565.0
452.0
684.0
565.0
452.0
684.0
565.0
452.0
454.0
375.0
300.0
363.0
300.0
240.0
454.0
375.0
300.0
RLA
High
Ambient
Standard
Temp
Cond. Fans
Cond. Fans (850 rpm)
(1140 rpm)
130.9
118.9
68.8
59.4
45.4
134.3
122.0
70.6
61.0
46.6
148.4
134.9
78.3
67.5
51.3
180.9
164.7
95.4
82.0
62.9
180.9
164.7
95.4
82.0
62.9
280.8
255.2
147.7
127.6
97.5
325.2
296.0
171.3
147.6
112.9
280.8
255.2
147.7
127.6
97.5
325.2
296.0
171.3
147.6
112.9
387.3
352.3
204.2
176.1
134.8
387.3
352.3
204.2
176.1
134.8
277.9
240.4
183.7
277.9
240.4
183.7
330.8
285.6
218.2
277.9
240.4
183.7
330.8
285.6
218.2
204.2
176.1
134.8
147.7
127.6
97.5
204.2
176.1
134.8
136.8
124.2
71.9
62.1
47.5
140.0
127.1
73.5
63.6
48.6
154.8
140.7
81.6
70.4
53.5
190.7
173.6
100.6
86.4
66.3
190.7
173.6
100.6
86.4
66.3
293.9
267.2
154.6
133.6
102.0
340.6
310.0
179.4
154.6
118.2
293.9
267.2
154.6
133.6
102.0
340.6
310.0
179.4
154.6
118.2
406.6
369.8
214.3
184.9
141.5
406.6
369.8
214.3
184.9
141.5
293.0
253.5
193.7
293.0
253.5
193.7
350.3
302.4
231.0
293.0
253.5
193.7
350.3
302.4
231.0
214.3
184.9
141.5
154.6
133.6
102.0
214.3
184.9
141.5
67
XL
WD
High
Ambient
Standard
Temp
Cond. Fans
Cond. Fans (850 rpm)
(1140 rpm)
C
LRA (All Units)
XL
WD
RLA
High
Ambient
Standard
Temp
Cond. Fans
Cond. Fans (850 rpm)
(1140 rpm)
1081.0 345.0
130.9
136.8
940.0 300.0
118.9
124.2
569.0 182.0
68.8
71.9
470.0 150.0
59.4
62.1
376.0 120.0
45.4
47.5
1081.0 345.0
134.3
140.0
940.0 300.0
122.0
127.1
569.0 182.0
70.6
73.5
470.0 150.0
61.0
63.6
376.0 120.0
46.6
48.6
1357.0 437.0
148.4
154.8
1180.0 380.0
134.9
140.7
714.0 230.0
78.3
81.6
590.0 190.0
67.5
70.4
472.0 152.0
51.3
53.5
1357.0 437.0
148.4
154.8
1180.0 380.0
134.9
140.7
714.0 230.0
78.3
81.6
590.0 190.0
67.5
70.4
472.0 152.0
51.3
53.5
1357.0 437.0
180.9
190.7
1180.0 380.0
164.7
173.6
714.0 230.0
95.4
100.6
590.0 190.0
82.0
86.4
472.0 152.0
62.9
66.3
1357.0 437.0
148.4
154.8
1180.0 380.0
134.9
140.7
714.0 230.0
78.3
81.6
590.0 190.0
67.5
70.4
472.0 152.0
51.3
53.5
1357.0 437.0
180.9
190.7
1180.0 380.0
164.7
173.6
714.0 230.0
95.4
100.6
590.0 190.0
82.0
86.4
472.0 152.0
62.9
66.3
2162.0 690.0
280.8
293.9
1880.0 600.0
255.2
267.2
1138.0 363.0
147.7
154.6
940.0 300.0
127.6
133.6
752.0 240.0
97.5
102.0
2714.0 863.0
325.2
340.6
2360.0 750.0
296.0
310.0
1428.0 454.0
171.3
179.4
1180.0 375.0
147.6
154.6
944.0 300.0
112.9
118.2
2714.0 863.0
325.2
340.6
2360.0 750.0
296.0
310.0
1428.0 454.0
171.3
179.4
1180.0 375.0
147.6
154.6
944.0 300.0
112.9
118.2
2714.0 863.0
387.3
406.6
2360.0 750.0
352.3
369.8
1428.0 454.0
204.2
214.3
1180.0 375.0
176.1
184.9
944.0 300.0
134.8
141.5
1428.0 454.0
171.3
179.4
1180.0 375.0
147.6
154.6
944.0 300.0
112.9
118.2
1428.0 454.0
204.2
214.3
1180.0 375.0
176.1
184.9
944.0 300.0
134.8
141.5
1428.0 454.0
204.2
214.3
1180.0 375.0
176.1
184.9
944.0 300.0
134.8
141.5
2143.0 684.0
277.9
293.0
1770.0 565.0
240.4
253.5
1416.0 452.0
183.7
193.7
2143.0 684.0
277.9
293.0
1770.0 565.0
240.4
253.5
1416.0 452.0
183.7
193.7
1428.0 454.0
204.2
214.3
293.0 2143.0
277.9
293.0
1180.0 375.0
176.1
184.9
253.5 1770.0
240.4
253.5
944.0 300.0
134.8
141.5
193.7 1416.0
183.7
193.7
2143.0 684.0
330.8
350.3
2143.0 684.0
330.8
350.3
1770.0 565.0
285.6
302.4
1770.0 565.0
285.6
302.4
1416.0 452.0
218.2
231.0
1416.0 452.0
218.2
231.0
2143.0 684.0
330.8
350.3
2143.0 684.0
330.8
350.3
1770.0 565.0
285.6
302.4
1770.0 565.0
285.6
302.4
1416.0 452.0
218.2
231.0
1416.0 452.0
218.2
231.0
NOTES:
1. For 30XA080-350 units with dual power supply, main power supply 1 uses refrigerant
circuit A components to calculate MCA and MOCP. Main power supply 2 uses refrigerant circuit B components to calculate MCA and MOCP.
2. 30XA400-500 units have dual power supply. Main power supply 1 uses refrigerant circuit C components to calculate MCA and MOCP. Main power supply 2 uses refrigerant
circuit A and B components to calculate MCA and MOCP.
7.5
10
15
UNIT VOLTAGE
V-Hz (3 Ph)
230-60
208-60
460-60
575-60
380-60
230-60
208-60
460-60
575-60
380-60
230-60
208-60
460-60
575-60
380-60
230-60
208-60
460-60
575-60
380-60
30XA
UNIT SIZE
090-160
090-160
090-160
090-160
2. Cut the CCN wire and strip the ends of the red (+), white
(ground), and black () conductors. Substitute appropriate colors for different colored cables.
3. Connect the red wire to (+) terminal on TB3 of the plug,
the white wire to COM terminal, and the black wire to the
() terminal.
4. The RJ14 CCN connector on TB3 can also be used, but is
only intended for temporary connection (for example, a
laptop computer running service tool).
PART NUMBER
Regular Wiring
Plenum Wiring
1895
A21451
A48301
8205
884421
D6451
M13402
M64430
6130
68
BLK
CCN
CCN
RED
LEN
WHT
CCN
CCN
SHIELD
BLK
LEN
RED
RED
BLK
CCN
CCN
WHT
LEN
WHT
TO NEXT
DEVICE
a30-4001
CCN
LEN
LEGEND
Carrier Comfort Network
Local Equipment Network
1/4-18 NPT
6" MINIMUM
CLEARANCE FOR
THERMISTOR
REMOVAL
1.188 in.
2.315 in.
a30-3999
WIRE TIE
LOOP
THERMISTOR WIRE
AND SECURE
TO CHILLED WATER PIPE
a30-4000
REFRIGERANT CHARGE