Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Multron MX201 V1.1 Zone Mod

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

MX Series

Intelligent Fire Alarm Systems

MX201
Addressable Zone Monitor Module

Features and Benefits


 EN54-18 Compliance
 Built-in MCU Processor with Digital Addressing
 Intelligent Self-diagnosis of open circuit
 Enhanced Interference Resistance by using multilevel wave filtering process
 LED Status Indicator
 Onsite Adjustable Parameter
 Loop and External Power Input
 Aesthetically pleasing design
 Parallel connecting up to 16 Conventional Detectors
 Surface mounting with Base for ease of installation

Overview
The MX201 Addressable Zone Monitor unit is an addressable interface module, which integrates Conventional
Detectors or Manual Call Points to the Addressable System. When any of the connected devices are in alarm
status, the unit will transmit the alarm signal to the Fire Alarm Panel, which generates alarm and displays its
address. The unit is compatible with most commonly used Conventional Devices and has the function of
checking short or open circuit of the output connection by means of End-of-Line Resistor (EOLR). The fault
massage includes open circuit, short circuit or any removal of the detectors.

Manufactured in compliance to European Standards, EN 54 Part 18, the unit is aesthetically pleasing with
unobtrusive design that will complement modern building designs. The Plug-in type construction enables ease
of installation and maintenance.

The unit incorporates an intelligent processor that provides automatic monitoring for both open and short
circuit of the input signal line. The MX201 Module is compatible to the MX Series Intelligent Addressable Fire
Alarm System, produced by single manufacturer to avoid addressable communication compatibility problem.

Multron Systems Pte Ltd DATA SHEET


217 Kallang Bahru, Multron Building Copyright © The information contained in this
Data Sheets remains the property of Multron
Singapore 339 347 Systems Pte Ltd, and is not to be altered or
: (65) 6395 6868 reproduce without permission.
Multron reserves the right to change any
: (65) 6395 6869 specification without prior notice.
: info @ multron.com.sg Version : 31-03-2018
MX Series
Intelligent Fire Alarm Systems
Technical Specification

Approvals and Standards EN54-18:2005/AC2007


Loop Power : 24VDC (16V to 28V)
Input Voltage
External PSU : 20 to 28VDC
Loop Standby : 1.3mA, Alarm : 5mA
Current Consumption
External PSU Standby : 10mA Alarm : 60mA
Control Output Voltage 24VDC (Only for MX130 Beam Detector usage, avoid any short circuit)
End of line Resistance 5.1Kohms ¼ W
Protocol/Addressing Proprietary Value range from 1 to 254
Indicator Status Normal : Single blink Active : Steady Fault: Double Blink
Material / Colour ABS White Glossy finishing
Dimension 108mm Width x 86mm Height x 38mm Depth
Weight 154g (with Base) 83g (without Base)
Operating Temperature -10°C to +50°C
Ingress Protection Rating IP30
Humidity 0 to 95% Relative Humidity, Non condensing