Diesel generator set

C series

Specification sheet
200 kWe, 250 kVA Prime

Our energy working for you.TM

Lowest life cycle cost Single source power assurance


‘C series’ design features have made Cummins® diesel, the Design, manufacture and testing of engine, alternator, enclosure
standard for comparison of operating economy, reliability and and other accessories is done by Cummins India/ Channel
long life. When all cost factors like initial purchase, fuel, lube oil, partners (Powerica Limited) for that optimum performance
maintenance and overhaul are considered, the bottom line will integrity and is backed by countrywide product support network
show that this Cummins ® ‘C series’ will deliver the lowest life with single source responsibility for the entire package.
cycle cost.
Standard scope
Heavy duty, durable and emission Engine: Cummins® ‘C series’, direct injection, water cooled
compliant engine, 6 cylinder, in-line, 4 stroke, rated at 1500 RPM,
Cummins ® ‘C series’ diesel engine comes with heavy duty conforming to ISO 3046 / BS 5514 has the following
features, bigger size camshaft, optimized turbo-matching and is specifications:
yet compact in size with optimum power to weight ratio making
it the obvious choice for your long-term power needs. - Digital electronic governor
- In-line fuel pump
The genset powered by the reliable - Optimised turbocharger
Cummins ® ‘C series’ diesel engine - Stainless steel exhaust flexible coupling
meets stringent exhaust emission - Silencer
tests as per MOEF norms without - Radiator
sacrificing fuel efficiency at normal - Coolant inhibitor
operating loads. - Plate-type lube oil cooler
- Spin-on filters - coolant, fuel & lube oil
- Dry-type, heavy duty replaceable paper element air cleaner
with restriction indicator
- Flywheel housing and flywheel to suit single bearing alternator
- Electrical starter motor
Silent Power - Battery charging alternator
- First fill lube oil
Cummins ® 250 kVA enclosure is so designed as to have
optimum performance and serviceability over the complete Alternator: Stamford brushless alternator
operating range. The enclosure is compact with integral fuel tank
and is designed for ease in maintenance. The powder coated - Self-excited, self regulated
enclosure is manufactured on latest CNC machines to ensure - Class ‘H’ insulation
superior finish and durability. - Salient pole revolving field
- Single bearing
- Digital automatic voltage regulator (part of PCC 1301)

© 2009 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy
working for you.” are trademarks of Cummins Power Generation. Other company product
names may be trademarks or service marks of others. Specifications are subject to change
without notice.
PGBU/CIL/005/C 250 kVA/Powerica/February 2009/Qty.
Genset controller: Cummins PowerCommand ® PCC 1301 Acoustic enclosure:
microprocessor based integrated generator set monitoring,
- Specially designed to meet stringent MOEF/ CPCB norms of
metering, protection and control system with built-in torque
75 dBA @ 1mtr at 75% load under free field conditions
matched Volts/Hz overload control.
- Designed to have optimum serviceability
- Air inlet louvers specially designed to operate at rated load
even at 50 deg C air inlet temp.
- Made on special purpose CNC machines for consistency in
quality and workmanship
- Powder coated for long lasting service life and superior finish
- With UV resistant powder coating, can withstand extreme
environments
- Use of stainless steel hardware
- Insulation material meets exacting IS 8183 specs for better
attenuation

Single control for all genset functions:


- Digital governing
- Digital voltage control
- Engine control
- Operator interface
- Protection
- Advanced control functions

Standard features of genset controller:


Engine
Metering Protection
- RPM - Low lube oil pressure - Fail to crank
- Battery voltage - High water temp. - Fail to start Control panel: Powder coated control panel manufactured
- Lube oil pressure - High /low DC voltage - Sensor failure
- Coolant temp. - Weak battery
with 14 / 16 gauge CRCA sheet provides:
- Running hours - Overspeed
- MCCB of suitable rating with overload and short circuit
Alternator protection
Metering Protection - Combined meter for KW, kVA and PF
- 3 phase voltage - Under voltage - Field overload
(L-L and L-N) - Over voltage
- KWh meter
- 3 phase current - Over current - Current transformers
- Frequency - Under/ over-frequency - Aluminum busbars of suitable capacity with incoming and
- kVA - Loss of sensing outgoing terminations
- Indicating lamps for “DG On” and “Load On”
Others
- Battle switch function - Instrument fuses/ MCB duly wired and ferruled
- Delay start/ stop
- Configurable cranking cycle
- Sleep mode time Optionals
Engine: Coolant heater with thermostatic switch and lube oil
Accessories: heater
- Silencer suitably optimized to meet stringent sound emission Alternator: Thermistors, space heater
standards laid down by MOEF / CPCB
Control panel: AMF control panel, battery charger, remote/
- Base rail with integral fuel tank (375 litres capacity) is provided
auto start panel, auto/ manual synchronizing panel, audio-visual
with drain plug, air vent, inlet and outlet connection, level
annunciation and indication lamps for engine faults
indicator, manhole etc.
- 2 x 12 V dry, uncharged batteries with connecting leads and Others: Mobile sets with canopy
terminals

www.cumminsindia.com
Our energy working for you.TM
© 2009 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy
working for you.” are trademarks of Cummins Power Generation. Other company product
names may be trademarks or service marks of others. Specifications are subject to change
without notice.
PGBU/CIL/005/C 250 kVA/Powerica/February 2009/Qty.
Technical data
Generator set specifications
Model CP 250 D5 P
Prime Power Rating kVA 250
Output Voltage and Frequency 415 Volts, 50 Hz
Power Factor 0.8 (lag)
No. of phases 3 phase

Engine specifications
Make Cummins
Model 6CTAA8.3G4
No. of cylinders 6, in- line
Aspiration Turbocharged-Air to air cooled
Bore x Stroke 114 mm x 135 mm
Displacement 8.3 ltrs
Output - Prime 310 bhp / 231 KW
Fuel consumption @ 75% load with Radiator & Fan 40.8 ltr/hr
Fuel consumption @ 100% load with Radiator & Fan 53.3 ltr/hr
Typical lube oil consumption @ full load 0.14 ltr/hr
Total wet weight ( engine + radiator) 968 kg
Length x Width x Height (engine) 1129 x 711 x 1171 mm
Compression Ratio 15.3 : 1
Piston Speed 6.75 m/s
Governor / Class Electronic / A1
Lubricating oil sytem capacity 32 ltrs
Coolant capacity (engine + radiator) 42 ltrs
Combustion air intake @ 100% load (+/- 5%) 17.1 m 3/min
Fan air flow across radiator 23976 cfm
Exhaust Temperature 523 oC
Battery Capacity / Rating 180 AH, 2 X 12 V

Alternator specifications
Make Stamford
Frame size / Model No. HC4C
Voltage Regulation + 1%
Insulation Class H
Standard Enclosure IP 23
Winding Pitch 2 / 3 Pitch
Stator Winding Double layer lap
Rotor Dynamically balanced
Wave form distortion No load < 1.8 %, non distorting balanced linear load < 5 %
Telephone Interference Factor Better than 50
Total Harmonic Factor Better than 2%

Conformance standards
IS 4722, BS 5000, IS 1460, ISO 8528, BS 5514, ISO 3046

Rating definitions
Prime Power (PRP): - Fuel consumption data is based on diesel having specific
Applicable for supplying power to varying electrical load for gravity of 0.85 and conforming to IS:1460
unlimited hours. Prime Power (PRP) is in accordance with - Oil consumption data is based on oil having specific gravity of
ISO 8528. Ten percent overload capability is available in 0.89 and meeting CF4 API categories
accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. - Fuel consumption tolerance is +5%

Emergency Standby Power (ESP):


Applicable for supplying power to varying electrical load for
the duration of power interruption of a reliable utility source.
Emergency Standby Power (ESP) is in accordance with
ISO 8528. Fuel Stop power in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.

www.cumminsindia.com
Our energy working for you.TM
© 2009 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy
working for you.” are trademarks of Cummins Power Generation. Other company product
names may be trademarks or service marks of others. Specifications are subject to change
without notice.
PGBU/CIL/005/C 250 kVA/Powerica/February 2009/Qty.
Typical enclosed genset dimensions*
Genset Model Rating (kVA) Length (mm) Width (mm) Height (mm) Weight (kgs.) (Dry)
CP 250 D5 P 250 kVA 4850 1700 2050 5424

Cummins India Limited Powerica Limited


Power Generation Business Unit 501 Dakshina Building, Sector 11, CBD
35A/1/2, Erandawana, Belapur, Navi Mumbai - 400 614
Pune 411 038. India Tel.: (02422) 66562525/ 66562510
Tel.: (91) 020-6602 7525 Fax: (91) 020-6602 8090 Fax: (02422) 27566239/ 40012692
Email: dgsets@vsnl.com
Cummins Power Generation Offices: Website: www.powericaltd.com
Location: Tel: Fax:
Bangalore: (080) 2361 3831/ 2361 1958 (080) 2361 4552 Powerica Ltd. - Regional and branch offices:
Chandigarh: (0172) 2240373 (0172) 224 0371 Location: Tel: Fax:
Chennai: (044) 2446 8110/ 2446 8113 (044) 2491 1120 Ahmedabad (079) 2646 7591/ 2646 8550 (079) 2646 7591
Delhi: (011) 4161 8357/ 61 (011) 4161 8357/ 61 Aurangabad (0240) 235 2232/ 232 5132 (0240) 233 9785
Hyderabad: (040) 2766 3017 (040) 2767 8892 Bangalore (080) 2226 8746/2225 7338 (080) 2225 8649
Indore: (0731) 645 1042/ 09826 42717 Chennai (044) 2826 0281/ 2827 6374 (044) 2826 0281
Jaipur: (0141) 236 4944 (0141) 403 8794 Coimbatore (0422) 249 5125/ 249 6125 (0422) 249 5125
Kolkata: (033) 2287 8065/ 2247 2481 (033) 2290 3839 Faridabad (0129) 227 5010/ 404 2177 (0129) 227 5416
Lucknow: (0522) 278 6718/ 278 8959 (0522) 278 7880 Goa (0832) 645 4381/ 243 8587 (0832) 243 8587
Mohali: (0172) 224 0373 (0172) 224 0371/ 72 Hubli (0836) 227 1262
Mumbai: (022) 2756 6351/ 52/ 53/ 54 (022) 2756 6355 Hyderabad (040) 2781 9906/ 2781 2861 (040) 2781 2210
Vadodara: (0265) 232 4207/ 654 0390/ (0265) 308 3010 Kochi (0484) 235 3595/ 236 5906 (0484) 236 5906
Kolkata (033) 2287 0331/3022 2231 (033) 2287 0331
Madurai (0452) 420 0081 (0452) 420 0082
Nagpur (0712) 259 1062/ 645 4117 (0712) 259 1035
Authorised
Nasik (0253) 329 9349/ 257 6779 (0253) 257 6779
Representative
Navi Mumbai (022) 4001 2600/ 2757 4568 (022) 4001 2692
Pune (020) 2546 0991/ 2546 5430 (020) 2546 0991
Vijaywada (0866) 257 0792/ 257 9435 (0866) 662 2752
www.cumminsindia.com Vishakapatnam (0891) 663 0791 (0891) 663 0792
Our energy working for you.TM

© 2009 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working
for you.” are trademarks of Cummins Power Generation. Other company product names may be trademarks or service marks of others. Specifications are subject to change without notice.
PGBU/CIL/005/C 250 kVA/Powerica/February 2009/Qty.

You might also like