A Review On Issues and Approaches For Microgrid Protection
A Review On Issues and Approaches For Microgrid Protection
A Review On Issues and Approaches For Microgrid Protection
art ic l e i nf o a b s t r a c t
Article history: In a traditional power grid, power generation is done at various potential locations and transmitted into
Received 30 September 2015 power grid and then distributed to the customer premises. The traditional grid incurs heavy investment,
Received in revised form limited reliability, increased emissions of green house gases and increased transmission line losses. It has
31 March 2016
made the utility to opt for connecting numerous renewable based micro sources near the customer
Accepted 9 September 2016
premises, as per their requirement and providing intelligent control for the grid. As a comprehensive
solution, microgrids are suggested by the researchers which would provide reliable, quality and efficient
Keywords: supply to its customers. The connection of microgrid in the existing distribution network makes the
Distributed generation radial network more complicated. It also causes the magnitude of fault current to change dynamically
Fault currents
depending on the modes of operation (grid connected or islanded mode), type of distributed generator,
Microgrid control
status of distributed generators and number of distributed generators. The conventional protection
Renewable energy
Fault current limiter schemes are designed for radial power flow with centralized power generation, which makes the ex-
Inverter isting protection scheme to fail with the microgrid. Hence, an attempt is made to relook into the basic
Communication standards concepts and significance of microgrid, issues faced by the microgrid in the context of protection and
Power distribution protection various protection strategies.
Energy storage & 2016 Elsevier Ltd. All rights reserved.
Over current protection
Contents
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 989
2. Microgrid control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 989
2.1. Centralized control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 989
2.2. Decentralized control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 990
3. Challenges in microgrid protection systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 990
3.1. Dynamics in fault current magnitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 990
3.2. LOM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 990
3.3. Unnecessary disconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 991
3.4. Blinding of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 991
4. Microgrid protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 991
4.1. Current limiter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 992
4.2. Centralized protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 992
4.2.1. Adaptive protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 992
4.3. Protection based on variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 994
4.3.1. Current samples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 994
4.3.2. Wavelet packet transform . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 994
4.3.3. Node voltages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 994
4.3.4. Traveling wave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 994
4.3.5. Local variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 994
4.4. Distance protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 995
n
Corresponding author.
http://dx.doi.org/10.1016/j.rser.2016.09.047
1364-0321/& 2016 Elsevier Ltd. All rights reserved.
B.J. Brearley, R.R. Prabu / Renewable and Sustainable Energy Reviews 67 (2017) 988–997 989
i. DG - status of DG (ON/OFF), type of DG, amount of generation. During islanded mode of operation voltage and frequency of
ii. Load - demand the microgrid is controlled by making one of the inverter fed DG as
iii. Network parameters such as current, voltage at each relay the master unit, which through its control strategy maintains the
point based on the control requirement voltage and frequency. The remaining DGs operate for power
iv. PCC- mode of operation (grid connected/islanded mode) balance with real and reactive power droop. The command for
load shedding is dictated to the LC by MCC.
The central controller involves two major modules namely The drawback in a fully decentralized control system is that
Energy Management Module (EMM) and Protection Coordination since each unit is controlled by its LC based on local information,
Module (PCM). EMM is responsible to provide the set points for the controller is not aware of system-wide variables and other
active, reactive power, voltage, frequency to each LC through local controllers’ actions. In order to overcome this drawback it is better
communication network based on IEC 61850 standard. During grid to have a hybrid controller, in which the decisions taken by the LC
connected mode the central controller. is rechecked by the MCC considering the system wide variables. If
the MCC detects any lack in control, then it immediately sends the
i. Monitor system parameters (above discussed parameters from modified control commands to the LC.
DG, Load, bus whichever parameters are essential for the spe-
cified control)
ii. Schedules economic generation of active and reactive power 3. Challenges in microgrid protection systems
control of the DGs and also demand side management.
iii. Ensure synchronized operation of microgrid with the utility To ensure reliable, safe operation of the power system network
network. proper protective devices with better selectivity, fast operation,
simplicity, flexibility, different setting opportunities and low price
The functions of the central controller in the islanded mode are has to be chosen.
As discussed earlier, the traditional protection schemes de-
i. Control commands for (a) inverter connected to master DG with signed for radial flow with high fault current for distribution
voltage and frequency control (b) inverter connected to other network will not operate faithfully to an microgrid because of
DGs with real and reactive power balance of microgrid.
bidirectional power flow, dynamic characteristics of DGs, inter-
ii. Provide commands to load controllers to undergo load shedding
mittent nature of the DG and variation in fault current. The major
based on the load criteria, microgrid energy reserves.
challenges faced in the protection [15] of microgrid are
Vth
Ik =
3 Zth (1)
where Vth is the pre-fault voltage at the faulted point and Zth is the
Thevenin's impedance..
Let Zg, Zs, ZL represent the impedance of DG, utility source and
transmission line respectively, then the thevenin’s equivalent cir-
cuit of the network can be represented as Fig. 4. Thevenin’s im-
pedance is calculated as
(Zs + l. ZL ). Zg
Zth = + (1 − l)ZL
(Zs + l. ZL + Zg ) (2)
Fig. 2. Unnecessary disconnection. The contribution of the fault current by the utility is nonlinear
with location and size of DG. Hence in an microgrid when fault
3.3. Unnecessary disconnection occurs at the lower end of the feeder, the grid impedance will be as
large as DG impedance and as a result the short circuit current
When a DG is located close to the substation in a feeder and if it remains well below the pickup current of the feeder relay in the LV
contributes for a fault occurring nearer to substation in a neigh- network which makes the relay to undetect fault and consequently
boring feeder (Fig. 2), then in such case the major portion of the this leads to malfunctioning of the entire protection system [19].
fault current is contributed by the DG. This makes the current to In order to overcome the above said issues, proper protection
exceed the pickup value of the relay available in the healthy feeder strategy has to be evolved for the microgrid to with stand the above
(Relay1) and hence it get tripped before operation of the relay said challenges and to operate efficiently. The subsequent section
corresponding to the faulted feeder (Relay2) [19]. reviews the various protection schemes available for microgrid.
to operate, then the backup device gets into operation. The con- series inverter, thereby the current is being limited appropriately.
ventional system is radial and hence the protection scheme is The insertion of series resistance causes more active power loss;
designed with over current relay and fuses which are very simple. hence a compromise has to be carried out for the selection of R/L
As discussed earlier the introduction of DGs in the existing system ratio. The RL feed forward algorithm functions well, but it circulates
makes the power system network more complicated. Also the fault more active power between the shunt and series inverter. Hence, a
current is unpredictable, since it changes with the mode of op- flux charge model feedback algorithm is used to reduce the active
eration, type of DG and number of DG. Hence, designing an effi- power circulation and to insert a virtual inductance through the
cient protection scheme to cope up with the above said issues is a series inverter using proper control algorithm.
challenging task. The various protection schemes addressed is The fault current limiters are to be optimally located so as to
tabulated (Fig. 5) and the same is discussed. minimize the total co-ordination time involved in all the relays,
the total operating time of the relay, irrespective of the mode of
4.1. Current limiter operation [22].
The Fault Current Limiters (FCL) are placed near the PCC to limit
4.2. Centralized protection
the fault current, contributed by the utility grid to the microgrid
and by the DGs in the microgrid towards the utility. The FCL is kept
In centralized protection, a microgrid has one central unit. The
in minimum position under normal condition (to avoid unwanted
LV microgrid is connected to the MV network using a delta/star
voltage drops and losses) and in maximum position under faulty
transformer. The neutral in star helps to avoid earthing problems
condition [20,21].
during islanding. Four Protection Devices (PD1, PD2, PD3 and PD4)
The fault current limiters can be broadly classified into three
are generally used (Fig. 6). PD1 (voltage and frequency relay) is lo-
types namely, super conducting FCL, solid state FCL, electro-
cated at the PCC, PD2 (directional over current relay) in the feeder,
magnetic FCL. In superconducting type FCL, the current limiting
PD3, PD3a (non directional over current relay) in service connec-
behavior depends on the non linear response of the super-
tions, PD3b (over current protection with fuses) and PD4 (voltage
conducting materials to temperature, current and magnetic fields.
and frequency relay) in DGs. A Microgrid Management System
Hence under faulted condition with heavy fault, any one of these
parameters exceeds the predefined value [21], in such cases cur- (MMS) is used to monitor the status of the microgrid and to set the
rent limiting is done. Under normal condition the current is below rating of the protective devices accordingly. The protective devices
the threshold, hence, the entire current is given to the protective PD1 and PD2 must be fast enough during islanded operation.
devices. In solid state FCL the current limiting behavior is decided The communication between the protective devices, is to be done
based on the ON/OFF of the semiconductor devices. In electro- using the standards IEC 61850 [24]. The operating curve for the
magnetic FCL, the current limiting behavior is decided based on protecting devices for both normal and islanded operation is being
the variation of the magnetic field. set. The MMS sends the status of the microgrid (normal or islanded)
A hybrid superconducting fault current controller [22] is a to the protecting devices. Based on the status of the microgrid, the
combination of super conducting FCL, solid state FCL, electro- protecting devices compare the measured parameter with the op-
magnetic FCL. This is one of the efficient methods suggested to erating curves and correspondingly issues trip signal [25].
limit and control the fault current in the microgrid.
During voltage sag, more line current flows through the line 4.2.1. Adaptive protection
impedance interconnecting the micro and utility grid [23] which It is to be noted that, the introduction of the DGs through the
in turn causes more line current to flow towards the load which microgrid in the existing power system network changes the fault
may damage the power electronic switches in the inverter. Hence current magnitude and fault level. Hence, the power rating of the
to protect the entire circuitry [16] the voltage is set to pre-fault protection devices also has to be revised (increased appropriately).
voltage using shunt inverters with appropriate control loops so as Also the status of the DG, mode of operation and other network
to limit the fault current. changes is to be updated instantaneously to central controller [25–
Later along with the shunt inverter, a series inverter is inserted 28] to devise proper protection scheme. Such type of protection is
and two current limiting algorithms are proposed to limit the cur- adaptive Microgrid protection. Adaptive microgrid protection is
rent during voltage sag [23]. The current limiting algorithms are RL suggested based on over current, differential and on sequence
feed forward current limiting algorithm and flux charge model components. Adaptive protection is done effectively by a commu-
feedback algorithm. During voltage sag at PCC, the voltage at the nication scheme [29,30] working with the help of Transmission
microgrid end is lifted by inserting impedance in series through the Control Protocol/Internet Protocol (TCP/IP) based ethernet network.
B.J. Brearley, R.R. Prabu / Renewable and Sustainable Energy Reviews 67 (2017) 988–997 993
4.2.1.1. Adaptive over current protection. In adaptive over current communication for instantaneous data transfer between terminals of
protection, Microgrid Central Processing Unit (MCPU) forms all the protected element. Differential protection works on the principle
possible meaningful configurations of the microgrid network of Kirchoff’s Current Law (KCL). The time stamped current values is
along with the DG status and store it in an structure called event received from the either end relays of the feeder through commu-
table. Then, for each configuration, fault current seen by each relay nication link. The current at two ends is compared [28], if the current
for all possible fault locations is stored in another structure called difference exceeds the threshold limit then the trip signal will be
fault current table. For each set of configurations, the relay settings provided. For proper protection, the restraint and operating slopes are
with hierarchy of operation of the relay for any particular fault properly designed to avoid the mismatch caused due to the inclusion
with its time delay is also stored in another structure called action of current transformer [34]. The over current protection is kept as the
table [16,26,31,32]. backup protection to improve the reliability [26,27].
For a fixed interval of time the status of the DG and the grid But, the dynamics of microgrid (transition between grid con-
configuration (grid connected or islanded) and current in each relay nected mode and islanded mode) sometimes makes the differ-
location is updated in MCPU periodically. With the help of the event ential scheme to fail. Therefore to make the differential scheme
table, fault current table and action table, appropriate signal will be effective even under transient conditions, advanced differential
given to the appropriate relays in the specific time by the MCPU. protection scheme, based on wide area monitory and high fre-
Because of some reasons if the relay fails to operate, then the relay quency current samples can be applied [35–38].
immediately upstream to the corresponding relay (it should operate
after some back up time based on the action table). 4.2.1.3. Adaptive protection based on sequence components. In the
Similarly, if a fault occurs in the grid, the DGs will contribute adaptive over current and differential protection, all the relays are
the fault current to the grid. Under such situation, the upstream devised with communication assistance which will be costlier.
relay which connects the microgrid to the main grid will operate Hence, to reduce the cost [39] microgrid is devised with a Mi-
to isolate the microgrid from the main grid. If it fails, the sub- crogrid Protection Commander (MPC), several Communication
sequent downstream relay operates which is just the reverse of assisted Microgrid Protection Relays (CMPR) and several Microgrid
the previous case (fault inside microgrid) [33]. Hence, the hier- Protection Relays (MPR) as shown in Fig. 7.
archy of operation of the relay will be reversed which is also stored Each MPR/CMPR has five modules namely the (i) directional
in the MCPU in separate table. In order to distinguish the fault module (ii) islanded protection module (iii) grid connected pro-
inside the microgrid and outside (main grid) the microgrid the tection module (iv) interfacing module (v) trip module. The di-
MCPU determines the direction of current in the PCC. If the di- rectional module determines the power flow direction and also
rection is forward it assumes the fault to be inside the microgrid calculates fault ratio (indicates change in sequence components
and follows the corresponding hierarchy table and if the current from normal condition to fault condition). The grid connected and
direction is reversed then it considers that the fault is in the utility islanded protection module is designed in such a way so as to offer
and it follows the relay sequence operation accordingly. protection in the specified modes respectively. The interfacing
module has a neutral voltage displacement and synchronism
4.2.1.2. Adaptive differential protection. The Differential protection check function. The neutral voltage displacement function is used
relays are generally used to protect equipment such as distributed to detect fault on the grid side to activate islanded operation. The
generators, transformers and short transmission lines. The differential synchronism check function is used to ensure proper reconnection
protection operates well for an internal fault. But, it requires a reliable of the small grid back to the main grid.
994 B.J. Brearley, R.R. Prabu / Renewable and Sustainable Energy Reviews 67 (2017) 988–997
The microgrid network is divided in several smaller areas and a difference in spectral energy is set as 1 and in case of islanded
CMPR is placed in each area to look after the protection in that mode the threshold is set as 0.3 [41,42].
particular zone. Several MPR are also installed within this zone.
The difference between CMPR and MPR is that the CMPR can 4.3.2. Wavelet packet transform
communicate with the MPC, but the MPR don’t have such com- Wavelet packet transform is used to extract, parameterize and
munication technology. In addition to this fuses, reclosures and localize all frequency contents in a processed signal. It decouples
sectionalizes are also available to offer better protection [29,40]. signal into time and frequency localized signals that parameterize
The CMPR sends the fault detection signal (whether it has iden- the frequency contents of the processed signal. Since Power elec-
tified any fault or not) and the direction of the fault to the MPC. The tronic controllers are used, the three phase quantity is converted
MPC receives such information’s from all the CMPRs within its net- into dq frame and then WPT is applied to the dq signal [43].
work and then judges the region in which the fault has occurred Minimum Description Length (MDL) data criteria is used for se-
based on the received information. The MPC again waits for a while lecting optimal wavelet basis function and is found that Doube-
to receive the recent information regarding the direction. Based on chies db4 wavelet function as optimal.
the recent information, it further verifies the faulted part and finally The high frequency sub bands WPT coefficient of dq axis
sends the tripping signal to the corresponding CMPR and wait signal component contains signatures which can facilitate detecting and
for all other CMPRs. In case, if the corresponding CMPR fails to op- classifying transient disturbances as fault or non fault. For doing so
erate, then after some time delay the circuit breaker issues a failure current samples, ia, ib, ic are collected and converted into dq
tripping signal to its neighboring circuit breakers. After a pre-calcu- component. Xdq ¼ Id2 þIq2, if idq≠0, then it identifies as some fault
lated time delay, the neighboring circuit breaker gets tripped off, has occurred and vice versa [43,44].
thereby it provides both primary and back up protection.
Once a fault is reported in the small microgrid by the MPC, the 4.3.3. Node voltages
corresponding sub network gets isolated from the remaining mi- In this method, the node voltages are set as state variables. If
crogrid network. If fault further persist, then the sub-network
the residue between the measured voltage value and the state
waits for a while whether the MPR inside its network gets acti-
estimated voltage value is very high then it implies the presence of
vated. If the MPR is able to locate and isolate the fault then the
fault, if not, the line is said to be healthy. The state variables are
remaining area of the sub-network remains working autono-
estimated for a sub-area. Hence communication required in this
mously. If not the entire sub-network will be kept in off condition
protection scheme is less [45].
till the clearance of fault. After the clearance of fault the sub-
network will be synchronized back to the microgrid network.
4.3.4. Traveling wave
The traveling waves are extracted by Mathematical Morphol-
4.3. Protection based on variables ogy Filters (MMF) which develops apparent feature of dilation and
erosion signals. Two wave fronts are extracted (one at first half of
The Microgrid protection can also be done based on various the line and the other at the second half of the line) and its time
parameters such as samples of current, voltage, angles, traveling and polarity are stored. If fault occurs in first half then product of
wave, Wavelet Packet Transform (WPT) and Total Harmonic Dis- the polarities of the two wave fronts has the positive value and if it
tortion (THD) which is discussed in detail below. lies in the second half then it will be negative [4].
Distance protection which offer high selectivity is applied where Kb is the branch coefficient which is calculated as
majorly in transmission lines. The impedance is calculated at each i3 i + i2
relay point using the formula Kb = = 1
i1 i1 (12)
V
Zm = m The new relay settings make the protection scheme to work
im (4) effectively for grid connected and islanded mode with good se-
where Vm is the measured voltage and im is the measured current lectivity and sensitivity [48,49].
at the relay point. Under normal condition, the measured im- The dynamics in relay setting due to the topological changes
pedance includes the load impedance and hence the value is high. occurring in the network based on status of DG and circuit
But, in case if there is any fault in the line then in such cases the breakers is incorporated for distance protection with the help of a
measured impedance will be equal to the line impedance alone, central controller. The relay setting for all possible configurations
(depending on status of DG, CB) is calculated offline and stored in
which is very low. Hence, by comparing the measured impedance
an action table. Similar to the adaptive over current protection
with set value, the occurrence of fault and whether the occurred
here also whenever a change is felt in the network, immediately
fault is within the particular protection zone is identified.
the central controller updates the relay setting by referring with
Usually for a region three zones of protection is offered. Zone
the action table and informs the same with the appropriate relays.
1 protection is instantaneous protection which covers 80% of the
zone. Zone 2 protection covers the area uncovered by zone 1. Zone
4.5. Multi agent protection
3 offers back up protection for the adjacent line. Both zone2 and
zone 3 operates with definite time, time of operation of zone 3 is
A multi agent is a group of intelligent hardware and software
greater than 2. The set value is chosen in such a way that
agent distributed in the network and work together to achieve a
Zset1 oZset2 oZset3. The set value is calculated as
global goal, here its efficient protection of microgrid.
Zset1 = Kr1 × Zline (5) The architecture for multi agent scheme designed for adaptive
over current protection involves three layers namely equipment layer,
substation layer and system layer (Fig. 9). The over current relays
Zset2 = Kr2 × (Zline + Z set1) (6) located in various parts of microgrid network forms the equipment
layer. The equipment layer is the lowest layer in the multi agent
network which involves measurement agent, protector agent, mobile
Zset 3 = Kr 3 × (Zline + Z set2 ) (7) agent and performer agent. The measurement agent monitors the
local parameters (current and voltage) and transfers it to the protector
where Kr1, Kr2, Kr3 are the reliability coefficient of each zone, agent. From the received local variables, protector agent checks
usually set as a value between 0.8 and 0.85 whether fault has occurred or not (by comparing the monitored local
The distance protection if applied with microgrid, (Fig. 8) for a variables with the set value). If it detects fault then it sends in-
fault at k, the DG connected at Bus 3 also contributes to the fault formation to the performer agent and the performer agent trips sui-
current. The DG impedance will also be get added along with the table Circuit Breakers so as to isolate the faulty part. Mobile agents
line impedance. Hence the impedance seen from the line23 is high exchange the information of the equipment to the substation layer.
compared to impedance at bus 2. The impedance measured by The substation layer communicates with the equipment layer and
relay R 23 is transfers the information to the system layer. The substation layer
Vm i Z + i3Zk involves region agent and management agent. The region agents
Zm = = 1 line23 transmit the information obtained from mobile agent to system layer
im i1 (8)
and to management agent. The management agent calculates the
The measured impedance becomes larger than the set value as settings of the relays incorporating the topological changes occurred
per Eq. (8) and the protection scheme lacks in selectivity. Thus the in the microgrid network and then transfers it to protector agent.
measuring impedance in the upstream/downstream network gets The highest layer forms the system layer. The system layer
disturbed with the inclusion of DG with considerable capacity. To which is the control center for microgrid network, monitors the
reduce the impact of the infeed current by DG in the protection entire network by communicating with substation layer. It updates
scheme the set value of the relays are recalculated as itself with recent information of the network which includes local
variables such as status of CBs, status of DG, current, voltage. Based
Zset1 = Kr1 × Zline (9) on these variables it run the load flow and also calculates the
996 B.J. Brearley, R.R. Prabu / Renewable and Sustainable Energy Reviews 67 (2017) 988–997
References
[30] BrahmaSMGirgisAA, Development of adaptive protection scheme for dis- microgrid protection. IET Gener Transm Distrib 8(2):2014;310–20.
tribution systems with high penetration of distributed generation. IEEE Trans [42] Kar Susmita, Samantaray SR. Combined S transform and data mining based
Power Deliv 19;53-63. intelligent microgrid protection scheme. IEEE Int Conf 2014.
[31] Oudalov Alexandre, Fidigatti Antonio. Adaptive network protection in micro- [43] ASaleh S, et al. Implementing and testing D-q WPT based digital protection
grids. Int J Distrib Energy Resour 2009;4(3):201–25. for microgrid systems. IEEE Trans Ind Appl 2014;50(3).
[32] Amir HEtemadi, Iravani Reza. Overcurrent and overload protection of directly [44] Saleh SA. Signature coordinated digital multi relay protection for microgrid
voltage controlled distributed resources in a microgrid. IEEE Trans Ind Elec- systems. (September). IEEE Trans Power Electron 2014;29(9).
tron 2013;60(0):12. [45] JanssenPierre. Monitoring, protection and fault location in power distribution
[33] Laaksonen Hannu, Ishchenko Dmitry. Adaptive protection and microgrid networks using system-wide measurements. Ph.D. thesis submitted in Eco-
control design for Hailuoto Island. IEEE Trans Smart Grid 2014;5(3). lePolytechnique; 2013.
[34] Ustun Taha Selim, Zayegh Aladin, Ozansoy Cagil. Differential protection of [46] Casagrande E, Woon WL, Zeineldin HH. A differential sequence component
microgrids with central protection unit support. IEEE 2013. protection scheme for microgrids with inverter-based distributed generators.
[35] Nthontho MPChowdhury SPWinberg SChowdhury S. Protection of domestic IEEE Trans Smart Grid 2014;5(1):29–37.
solar photovoltaic based microgrid. In: 11th international conference on de- [47] Salehi V, Mohamed A, Mazloomzadeh A, Mohammed OA. Laboratory-based
velopments in power system protection; 2012. p. 1–6. smart power system, Part II: Control, monitoring, and protection. IEEE Trans
[36] SorotommeE. A differential zone protection scheme for microgrids. In: IEEE Smart Grid 2012;3(3):1405–17.
international conference; 2013. [48] Lin Hengwei, Guerrero Josep M, Quintero Juan Carlos Vasquez, Liu Chengxi.
[37] Haron Ahmad Razani, Mohamed Azah, Shareef Hussain. Co-ordination of over Distance protection for microgrids in distribution system. In: 41st annual
current, directional and differential relay for the protection of microgrid sys- conference of IEEE industrial electronics society. IECON 2015:000731–6.
tem. Sci Direct, Procedia Technol 2013;11:366–73. [49] Lin Hengwei, Guerrero Josep M, Quintero Juan Carlos Vasquez, Liu Chengxi.
[38] Mohammad E, Mohammad Liang Che, Shahidehpour Khodayar. Adaptive Adaptive Distance Protection for Microgrids. In: 41st annual conference of
protection system for microgrid. IEEE Electrif Mag 2014. IEEE industrial electronics society. IECON 2015:000725–30.
[39] Zamani MA, Sidhu TS, Yazdani A. A protection strategy and microprocessor- [50] Colson CM, Nehrir MH. A review of challenges to real-time power manage-
based relay for low-voltage microgrids. IEEE Trans Power Deliv 2011;26 ment of microgrids. In: Power & energy society general meeting, 2009. PES ‘09
(3):1873–83. IEEE 2009:1–8.
[40] Zamani MA, Sidhu TS, Yazdani A. Investigations into the control and protection [51] Coury DV, Throp JS, Hopkinson KM, Birman KP. Agent technology applied to
of an existing distribution network to operate as a microgrid: a case study. adaptive relay setting for multi-terminal lines. IEEE PES SM, Seattle 2000.
IEEE Trans Ind Electron 2014;61(4):1904–15. [52] kulasekera Asitha Lakruwan. Multi agent based control and protection for an
[41] Kar SSamantaray SR. Time-frequency transform-based differential scheme for inverter based microgrid.Sri Lanka: University of Moratuwa; 2012.