Appendix B
Appendix B
Appendix B
APPENDIX - B
Eccentric load
e x = 0.0 mm
e y = 0.0 mm
[ kN, kNm ]
Wedge Anchor BZ plus A4 M8 hef 46
Designed acc. to ETAG 001, Annex C
Assessment ETA-99/0010: MKT BZ plus / BZ-IG
The anchorage is verified. Boundary
Tension loads Shear loads Interaction conditions:
bN [%] bV [%] bN,V [%]
Static / quasi-static action 62.3 4.8 50.2 OK
The calculation applies if the hints on the last page are observed.
MKT Metall-Kunststoff-Technik GmbH & Co.KG - Auf dem Immel 2 - D-67685 Weilerbach - Tel.: +49 (0) 63 74 / 91 16 -0 - Fax: +49 (0) 63 74 / 91 16 60
Design office: E W Cox Middle East L L C
Person in charge: SHA
Construction project: SEVEN HOTEL AND APARTMENTS, THE PALM
Number: CGME-7120-cal-002
Position: RESTRAINT TYPE - R Date: 26/05/2021
APPENDIX - B
Anchor loads:
Anchor 1 2
NSd [kN] 2.79 2.79
MKT Metall-Kunststoff-Technik GmbH & Co.KG - Auf dem Immel 2 - D-67685 Weilerbach - Tel.: +49 (0) 63 74 / 91 16 -0 - Fax: +49 (0) 63 74 / 91 16 60
Design office: E W Cox Middle East L L C
Person in charge: SHA
Construction project: SEVEN HOTEL AND APARTMENTS, THE PALM
Number: CGME-7120-cal-002
Position: RESTRAINT TYPE - R Date: 26/05/2021
APPENDIX - B
Anchor loads:
Anchor 1 2
VSd [kN] 0.50 0.50
Vx,Sd [kN] 0.50 0.50
Vy,Sd [kN] 0.00 0.00
MKT Metall-Kunststoff-Technik GmbH & Co.KG - Auf dem Immel 2 - D-67685 Weilerbach - Tel.: +49 (0) 63 74 / 91 16 -0 - Fax: +49 (0) 63 74 / 91 16 60
Design office: E W Cox Middle East L L C
Person in charge: SHA
Construction project: SEVEN HOTEL AND APARTMENTS, THE PALM
Number: CGME-7120-cal-002
Position: RESTRAINT TYPE - R Date: 26/05/2021
APPENDIX - B
Installation parameters
Thread M = 8 mm
Diameter of drilled hole d0 = 8 mm
Depth of drilled hole h0(1) = 60 mm
Effective anchorage depth hef = 46 mm
Diameter of clearence hole
in the fixture df ≤ 9 mm
Tightening torque Tinst = 20 Nm
Width across nut SW = 13 mm
Remarks
The anchors are without influence of edge distance, if: c ≥ max ( 10 h ef ; 60 d )
Correspond the diameter df of the clearance hole not the specified in Table 4.1 in [1]
or with the design of slotted holes follow the hints in chapter 1.1 in [1].
The calculation regards data for standard thickness of concrete slab.
The design is based on the assumption that the anchor plate remains flat under the acting
forces.
The proof of the capacity of the anchor base component shall be shown according to chapter 7 in [1].
MKT Metall-Kunststoff-Technik GmbH & Co.KG - Auf dem Immel 2 - D-67685 Weilerbach - Tel.: +49 (0) 63 74 / 91 16 -0 - Fax: +49 (0) 63 74 / 91 16 60